Compound Wall

Data :-

There is a filling of 1.2 m in proposed site from neighbor site level.


Type of soil is murmur at 1.8 m deep below the neighbors plot level.
And soil SBC is taken as 20 T/m at depth of 1.8m
Compound wall is designed as retaining cum compound wall.
Soil density is taken as 2200 kg/m ( soil + water unit weight )
Angle of repose taken as 25 ( assumed .

Self weight of structure

Sl. No. Area unit wt moment arm load moment

a 0.02 2500 0.09 43.75 4.082


b 0.28 2000 0.12 552 63.48
c 0.45 2400 0.3 1080 324
d 0.45 2400 0.38 1080 405
e 0.54 2400 0.45 1296 583.2
f 0.66 2400 0.55 1584 871.2
g 0.81 2400 0.68 1944 1312.2

total 7579.75 3563.162

Soil intensity

Sl. No. Area unit wt moment arm load moment

s1 0.45 2200 0.98 990 965.25


s2 0.36 2200 1.05 792 831.6
s3 0.27 2200 1.13 594 668.25
s4 0.15 2200 1.23 330 404.25

total 2706 2869.35

Total load 10285.75

Total Moment 6432.512 Resisting moment

Design Data:-
Density of soil taken :- 2200 kg/m
:- 25
SBC of soil :- 20 T/m

Overturning pressure due to soil :-

w h * [ 1 - sin ]
6 [ 1 + sin ]

Page 1 of 4
w= 2200 Sin 25 = 0.42
h= 3 1 - sin 25 = 0.58
= 25 1 + sin 25 = 1.42

((1-sin)/(1+sin)) =
0.41
Overturning = 4018.18 kg.m

1. Check for overturnig :-

Resisting moment > 1.5 * overturning moment due to soil

6432.512 > 6027.27

Factor of safety = resisting moment / overturning moment


1.6 > 1.5

Therefore, safe

2. Check for Sability :-

Factor of safety = ( * W ) / p

= 0.5
W= 10285.75

p = (1/3) * w * (h/3) = 3300 kg/m

Factor of safety = 1.56 > 1.5

Therefore, safe

3. Check for Eccentricity :-

e=(b/2)-z z = total moment / total load


z = 0.63
b (m) = 1.35

e = 0.05 < b/6 0.23

Therefore, safe

4. Intensity of pressure at base :-

p=(W/b)*(1((6*e)/b))

p (max) = 9299.302 kg/m

p (min) = 5938.846 kg/m

p (max) and p (min) are less than SBC of soil. Therefore, safe

Page 2 of 4
Compound Wall

Coping in PCC 1:2:4


a

Brick Work in C.M 1:6

0.23
1.2 Note : 1. All dimensions are in Meters.
2. Not to scale

b PCC 1:2:4

0.15 Soil filled up

s1
0.75 c
Neighbor Weep holes
Site 0.6 1.2

d s2
G.L 0.6

0.75

0.6 e Coursed rubble masonry in C.M 1:5


s3
0.9

0.6 f s4

1.1

0.6 g
1.35 PCC in 1:4:8

0.1

1.5
Note:-
1. Brick work in superstructure to be in CM 1:6.
2. Brick wall to be plastered in CM 1:5,15 mm thick.
3. Coursed rubble masonry in CM 1:5. And racking finish to be provided.
4. Bond stone shall be provided at every 1.2 m horizontally and 0.6m vertically staggered at every course.
5. Construction joint to be provided at every interval of 6 m, 20 mm thick.
6. 75 mm dia pipe at 1 m interval to be provided horizontally and vertically staggered.
7. Weep hole should be given a fall of 1.8 from back of compound wall
8. Minimum height of weep hole from the base is 300 mm above the ground level.
9. Any changes in details to be consulted with respective Executive Engineer.