Overview

The space-saving basic variants

Interface for the connection of expansion modules, up to 24 digital inputs, 20 (16) digital outputs, 8 analog inputs
and 8 (2) analog outputs can be addressed

With connection option for LOGO! TD text display (can be connected to all LOGO! 0BA6 and 0BA7 basic versions);
LOGO! TDE can be connected with LOGO! 8 or higher
New for LOGO! 8

All basic units with integrated web server

Same enclosure width as LOGO! 0BA6 (4 MW)

All basic units with Ethernet interface for communication with LOGO!, SIMATIC Controllers, SIMATIC Panels and
PCs

Use of standard micro CF cards


LOGO! 0BA7 versions:

Ethernet interface for communication with SIMATIC Controller, SIMATIC Panel and PC

Networking of max. 8 LOGO! devices

Use of standard CF card or SIMATIC memory card

Design
LOGO! 0BA6:
Relay outputs with up to 10 A output current (not LOGO! 24).

Integrated display field with parameterizable backlight (4 x 12 characters).

Integrated operator control panel.

Integrated EEPROM memory for control program and setpoint values.

Optional program module for copying and know-how protection.


Optional battery module and combined battery/program module for backing up the integral real-time clock over 2
years.

Integral real-time clock with automatic summer/winter time adjustment.

8 digital inputs, 4 digital outputs.

4 inputs as analog inputs in 12/24 V DC variants (0 to 10 V); inputs can also be used digitally.

4 inputs can be used for high-speed counting up to 5 kHz (DC versions only).

Interface for the connection of expansion modules, up to 24 digital inputs, 16 digital outputs, 8 analog inputs and 2
analog outputs can be addressed.

Interface for connecting the LOGO! TD text display.

Up to 200 function blocks per user program


LOGO! 0BA7:
Ethernet interface (replaces the serial programming interface of the previous series)

Relay outputs with max. 10 A output current

Integrated display field with parameterizable backlight (4 x 12 characters).

Integrated operator control panel.

Integrated EEPROM memory for control program and setpoint values.

Optional standard SD cards or SIMATIC memory cards

Integral real-time clock with automatic summer/winter time adjustment.

Backup of the integrated real-time clock for 20 days.

8 digital inputs, 4 digital outputs.

4 inputs as analog inputs in 12/24 V DC variants (0 to 10 V); inputs can also be used digitally.

4 inputs can be used for high-speed counting up to 5 kHz (DC versions only).

Interface for the connection of expansion modules, up to 24 digital inputs, 16 digital outputs, 8 analog inputs and 2
analog outputs can be addressed.

Interface for connecting the LOGO! TD text display.


LOGO! 8:
Ethernet port

Relay outputs with max. 10 A output current

Integrated display field with parameterizable backlight (6 x 16 characters, 3 background colors).

Integrated operator control panel.

Integrated EEPROM memory for control program and setpoint values.

Optional standard micro CF cards

Integral real-time clock with automatic summer/winter time adjustment.

Backup of the integrated real-time clock for 20 days.

8 digital inputs, 4 digital outputs.

4 inputs as analog inputs in 12/24 V DC variants (0 to 10 V); inputs can also be used digitally.

4 inputs can be used for high-speed counting up to 5 kHz (DC versions only).
Interface for the connection of expansion modules, up to 24 digital inputs, 20 digital outputs, 8 analog inputs and 8
analog outputs can be addressed.

Connection of LOGO! TDE via Ethernet.

Function

Integrated basic and special functions:

o Basic logic functions:


AND, OR, NOT, NAND, NOR, XOR, positive/negative pulse edge evaluation.

o Special functions:
ON delay, latching ON delay, OFF delay, impulse relay, locking relay, counter (forward/backward), time switch, interval
time-delay relay, operating hours counter, trigger, asynchronous pulse generator, year time switch, comfort light switch
function, random generator, staircase light switch function as per DIN 18015-2, edge-triggered interval time-delay relay,
combined ON/OFF delay, analog comparator, analog trigger, analog delta trigger, analog watchdog, analog amplifier, text
and variable display, shift register, soft key function, PI controller, ramp function, analog multiplexer, PWM function, analog
arithmetic function, function for detecting errors in the analog arithmetic function.

200/400 function blocks can be linked.

Up to 27/64 bit memories


(including restart bit memory, bit memory for controlling the backlight of the integral display and the LOGO! TD, bit memory
for switching between 2 parameterizable character sets in the message text).

Integrated retentivity.

Password protection.
Function available as an option
Additional know-how protection with the program module or CF/micro CF card available as an option.

Backup of the integrated real-time clock of LOGO! 0BA6 with the optionally available battery module and combined
battery/program module for 2 years

Backup of the integrated real time clock of LOGO! 0BA7 and LOGO! 8 for 20 days.

Connection of the optionally available LOGO! TD text display to all ..0BA6 Basic versions
Additional functions for LOGO! 0BA7
Data logging to internal memory or CF card (up to 2 000 records)

Macros (user-defined functions) for LOGO! Soft Comfort V7

400 function blocks can be interlinked

16 analog bit memories

64 open terminals

4 8-bit shift registers

New special functions:


Astronomical clock, analog filter, mean value calculation, min/max value, stop watch

Diagnostic functions
Additional functions for LOGO! 8
Data logging to internal memory or micro CF card (up to 20 000 records)
Macros (user-defined functions) for LOGO! Soft Comfort

400 function blocks can be interlinked

64 analog bit memories

64 open terminals

4 8-bit shift registers

Extended diagnostic functions

Technical specifications
6ED1052-1CC01-0BA8 6ED1052-1MD00- 6ED1052- 6ED1052-1FB00-
0BA8 1HB00-0BA8 0BA8
Installationtype/mounting

Mounting on35mmDINrail,4 on35mmDINrail, on35mmDIN on35mmDIN


spacingunitswide 4spacingunitswide rail,4spacing rail,4spacing
unitswide unitswide

Supplyvoltage

12VDC Yes

24VDC Yes Yes Yes

115VDC Yes

230VDC Yes

permissiblerange,lowerlimit 20.4 V 10.8 V 20.4 V 100 V


(DC)

permissiblerange,upperlimit 28.8 V 28.8 V 28.8 V 253 V


(DC)

24VAC Yes

115VAC Yes

230VAC Yes

Timeofday

Timeswitchingclocks

Powerreserve 480 h 480 h 480 h 480 h

Digitalinputs

Numberofdigitalinputs 8;Ofwhich4canbeused 8;Ofwhich4can 8 8


inanalogmode(0to10V) beusedinanalog
mode(0to10V)

Digitaloutputs

Numberofdigitaloutputs 4;Transistor 4;Relays 4;Relays 4;Relays


short-circuitprotection Yes;electrical(1A) No;externalfusing No;external No;external
necessary fusingnecessary fusingnecessary

Outputcurrent

forsignal"1" 0.3 A 10 A

permissiblerangefor0to
55C,max.
Relayoutputs

Switchingcapacityof
contacts

o with 3A 3A 3A

inductiveload,max.

o with 10 A 10 A 10 A

resistiveload,max.
EMC

Emissionofradiointerference
acc.toEN55011

LimitclassB,for Yes;Radiointerference Yes Yes Yes


suppressionaccordingto
useinresidentialareas EN55011,LimitValueClass
B

Degreeandclassofprotection

IP20 Yes Yes Yes Yes

Standards,approvals,
certificates

CSAapproval Yes Yes Yes Yes

ULapproval Yes Yes Yes Yes

FMapproval Yes Yes Yes Yes

Developedinaccordancewith Yes Yes Yes Yes


IEC61131

accordingtoVDE0631 Yes Yes Yes Yes

Marineapproval

Marineapproval Yes Yes Yes Yes

Ambientconditions

Operatingtemperature

Min. 0 C 0 C 0 C 0 C

max. 55 C 55 C 55 C 55 C
Dimensions

Width 71.5 mm 71.5 mm 71.5 mm 71.5 mm

Height 90 mm 90 mm 90 mm 90 mm

Depth 60 mm 60 mm 60 mm 60 mm

6ED1052-1MD00-0BA7 6ED1052-1FB00-0BA7

Installationtype/mounting

Mounting on35mmDINrail,6spacingunitswide on35mmDINrail,6spacingunitswide

Supplyvoltage

12VDC Yes

24VDC Yes

115VDC Yes

230VDC Yes

permissiblerange,lowerlimit(DC) 10.8 V 100 V

permissiblerange,upperlimit(DC) 28.8 V 253 V

115VAC Yes

230VAC Yes

Timeofday

Timeswitchingclocks

Powerreserve 480 h 480 h

Digitalinputs

Numberofdigitalinputs 8;Ofwhich4canbeusedinanalog 8
mode(0to10V)

Digitaloutputs

Numberofdigitaloutputs 4;Relays 4;Relays

short-circuitprotection No;externalfusingnecessary No;externalfusingnecessary

Relayoutputs

Switchingcapacityof
contacts

o withinductive 3A 3A

load,max.

o withresistive 10 A 10 A
load,max.
EMC

Emissionofradiointerferenceacc.
toEN55011

LimitclassB,foruse Yes;Radiointerferencesuppression Yes;Radiointerferencesuppression


accordingtoEN55011,LimitValueClass accordingtoEN55011,LimitValueClassB
inresidentialareas B

Degreeandclassofprotection

IP20 Yes Yes

Standards,approvals,certificates

CSAapproval Yes Yes

ULapproval Yes Yes

FMapproval Yes Yes

DevelopedinaccordancewithIEC Yes Yes


61131

accordingtoVDE0631 Yes Yes

Marineapproval

Marineapproval Yes Yes

Ambientconditions

Operatingtemperature

Min. 0 C 0 C

max. 55 C 55 C

Dimensions

Width 107 mm 107 mm

Height 90 mm 90 mm

Depth 55 mm 55 mm

6ED1052-1CC01-0BA6 6ED1052-1MD00- 6ED1052- 6ED1052-1FB00-


0BA6 1HB00-0BA6 0BA6
Installationtype/mounting

Mounting on35mmDINrail,4 on35mmDINrail, on35mmDIN on35mmDIN


spacingunitswide 4spacingunitswide rail,4spacing rail,4spacing
unitswide unitswide

Supplyvoltage

12VDC Yes
24VDC Yes Yes Yes

115VDC Yes

230VDC Yes

permissiblerange,lowerlimit 20.4 V 10.8 V 20.4 V 100 V


(DC)

permissiblerange,upperlimit 28.8 V 28.8 V 28.8 V 253 V


(DC)

24VAC Yes

115VAC Yes

230VAC Yes

Timeofday

Timeswitchingclocks

Powerreserve 80 h 80 h 80 h 80 h

Digitalinputs

Numberofdigitalinputs 8;Ofwhich4canbeused 8;Ofwhich4can 8 8


inanalogmode(0to10V) beusedinanalog
mode(0to10V)

Digitaloutputs

Numberofdigitaloutputs 4;Transistor 4;Relays 4;Relays 4;Relays

short-circuitprotection Yes;electrical(1A) No;externalfusing No;external No;external


necessary fusingnecessary fusingnecessary

Outputcurrent

forsignal"1" 0.3 A

permissiblerangefor0to
55C,max.
Relayoutputs

Switchingcapacityof
contacts

o with 3A 3A 3A

inductiveload,max.

o with 10 A 10 A 10 A

resistiveload,max.
EMC

Emissionofradiointerference
acc.toEN55011

LimitclassB,for Yes;Radiointerference Yes Yes Yes


useinresidentialareas suppressionaccordingto
EN55011,LimitValueClass
B

Degreeandclassofprotection

IP20 Yes Yes Yes Yes

Standards,approvals,
certificates

CSAapproval Yes Yes Yes Yes

ULapproval Yes Yes Yes Yes

FMapproval Yes Yes Yes Yes

Developedinaccordancewith Yes Yes Yes Yes


IEC61131

accordingtoVDE0631 Yes Yes Yes Yes

Marineapproval

Marineapproval Yes Yes Yes Yes

Ambientconditions

Operatingtemperature

Min. 0 C 0 C 0 C 0 C

max. 55 C 55 C 55 C 55 C

Dimensions

Width 72 mm 72 mm 72 mm 72 mm

Height 90 mm 90 mm 90 mm 90 mm

Depth 55 mm 55 mm 55 mm 55 mm