Sunteți pe pagina 1din 5

WinCC Runtime Advanced (RT Advanced)

WinCC Runtime Advanced

WinCC Runtime Advanced

The following tables of system limits help you assess whether your project conforms to the system

limits of a given HMI device.

The specified maximum values are not additive. It cannot be guaranteed that configurations running

on the devices at the full system limits will be functional.

In addition to the specified limits, allowances must be made for restrictions imposed by configuration

memory resources.

Tags

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of tags in the project 6144 12288

Number of PowerTags 128 - 4096 128 8192

Number of elements per array 1600 1600

Number of local tags 2048 4096

Number of structures 999 999

Number of structure elements 400 400

Alarms

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of alarm classes 32 32

Number of discrete alarms 4000 6000

Number of analog alarms 500 500

Length of an alarm in characters 80 80

Number of process values per alarm 8 8

Size of the alarm buffer 1024 2048

Number of queued alarm events 500 500

Screens

-1-
WinCC Runtime Advanced (RT Advanced)

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of screens 500 750

Number of fields per screen 400 600

Number of tags per screen 400 400

Number of complex objects per screen


1) 40 40

Complex objects include: Bars, sliders, symbol library, clock, and all objects from the Con
1)
trols area.

Recipes

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of recipes 999 1000

Number of elements per recipe


1) 2000 2000

User data length in KB per data record 256 512

Number of data records per recipe 5000 5000

Reserved memory for data records in the in


-- --
ternal Flash

1) If arrays are used, each array element counts as one recipe element

Logs

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of logs 100 100

Number of entries per log (including all log

segments)
1) 500000 500000

Number of log segments 400 400

Cyclic trigger for tag logging 1 s 1 s

Number of tags that can be logged per log 6144 12288

-2-
WinCC Runtime Advanced (RT Advanced)

The number of entries for the "segmented circular log" logging method is the total number

1) for all sequential logs. The product of the number of sequential logs and the number of data

records per sequential log may not exceed the system limit

Trends

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of trends 800 800

Text lists and graphics lists

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of graphics lists 500 500

Number of text lists 500 500

Number of entries per text or graphics list 3500 500

Number of graphic objects 2000 4000

Number of text elements 30000 40000

Scripts

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of scripts 200 200

Communication

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of connections 8 8

Number of OPC connections including OPC


8 8
UA

Number of connections based on "SIMATIC


16 16
HMI HTTP"

-3-
WinCC Runtime Advanced (RT Advanced)

Maximum number of connected


4
1) 4
1)
Sm@rtClients (including a service client)

Help system

KTP400 TP700, TP1500 TP1900 TP2200


KP400 KP700 KP1500
TP900,
KP900
TP1200,
KP1200
Number of characters in a
320
1) 320
1) 320
1) 320
1) 320
1)
help text
500
2) 500
2) 500
2) 500
2) 500
2)

1) For devices with HMI device version 12 or lower

2) For devices with HMI device version higher than 12

Languages

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of runtime languages 32 32

Scheduler

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Time-triggered tasks
1) 48 48

1) Event-triggered tasks are not relevant for the system limits

User administration

-4-
WinCC Runtime Advanced (RT Advanced)

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Number of user groups 50 50

Number of authorizations 32 32

Number of users 100 100

Project

WinCC Runtime Ad WinCC Runtime Advanced


vanced Device version as of 13
Device version prior to
13
Size of the project file "*.fwc" No limiting No limiting

-5-

S-ar putea să vă placă și