Sunteți pe pagina 1din 4

Acoustic Calculation of Ventilation Systems

For more info:


http://www.engineeringtoolbox.com/accoustic-calculation-ventilation-d_70.html
If you are signed into your Google Account - select "File > Make a copy" to make your own copy to mo

Octave Band Center F


63 125 250
1 Sound Power Fan 102 99 98
2 Safety Factors 3 3 3
10 Room and terminal effect -5 -5 -5
11 Allowance for end reflection -12 -8 -4
12 Ductwork attenuation -17 -17 -9
13 Elbow attentuation 0 0 -7
14 Power level split, branch to terminals -6 -6 -6
15 Power level split, main duct to branch duct -10 -10 -10
0 0 0
0 0 0
0 0 0
0 0 0
20 Resulting Sound Power Fan 55 56 60
21 Sound Pressure Criterion 59 48 40
22 Silencer Requirements -4 8 20

Acoustic Calculation of Ventilation System

120

100

80

60
120

100

80

60

Sound Power (dB) 40

20

0
63 125 250 500 1,000 2,000 4,000 8,000

-20

-40

Frequency (Hz)
html
make your own copy to modify!!

Octave Band Center Frequency (Hz)


500 1,000 2,000 4,000 8,000
98 97 95 86 81
3 3 3 3 3
-5 -5 -5 -5 -5
-1 0 0 0 0
-5 -5 -5 -5 -5
-15 -25 -25 -29 -15
-6 -6 -6 -6 -6
-10 -10 -10 -10 -10
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
59 49 47 34 43
34 30 27 25 23
25 19 20 9 20

of Ventilation System

1 Sound Power Fan


2 Safety Factors
10 Room and terminal effect
11 Allowance for end reflection
12 Ductwork attenuation
13 Elbow attentuation
1 Sound Power Fan
2 Safety Factors
10 Room and terminal effect
11 Allowance for end reflection
12 Ductwork attenuation
13 Elbow attentuation
14 Power level split, branch to terminals
15 Power level split, main duct to branch duct
Row 17
Row 18
Row 19
Row 20
20 Resulting Sound Power Fan
2,000 4,000 8,000 21 Sound Pressure Criterion
22 Silencer Requirements