Sunteți pe pagina 1din 7

C L A S I F I CA C I O N N O R T E A M E R I CA N A A R E A S P E L I G R O S A S

Ejemplo NEC 500-503 NEC 505


_____________________________________________________________________________________________

CLASE I Acetileno Grupo A IIC


(Gases y Vapores) Hidrgeno Grupo B IIC or IIB+H2
Etileno Grupo C IIB
Propano Grupo D IIA
_____________________________________________________________________________________________

CLASE II Polvo Metlico Grupo E


Polvio De Carbon Grupo F
Polvo De Granos Grupo G
_____________________________________________________________________________________________

CLASE III Procesamiento De No Hay Subgrupos


(Fibras y Particulas Madera, Papel Y
En Suspensin) Algodon.

GRUPOS DE GASES

Norte America CENELEC


Gases Peligrosos NEC Artculo 500 EN 50 014
Tpicos (Clase I) IEC
_____________________________________________________________________

ACETILENO A IIC
_____________________________________________________________________

HYDROGENO B IIC or IIB +H2


_____________________________________________________________________

ETILENO C IIB
_____________________________________________________________________

PROPANO D IIA

La clasificacin de los gases y temperaturas de


ignioin se relacionan con las mezclas de gas y
aire a temperatura ambiente y presin.

1
TRIANGULO DE COMBUSTION

CLASIFICACION DE AREAS
Peligro Peligro
Condiciones
Continuo Intermitente
Peligrosas Y
Anormales
________________________________________________________________________________________________

Norte Amrica Divisin 1 Divisin 1


Divisin 2
/NEC500-503
________________________________________________________________________________________________

IEC/CENELEC/EUROPA Zona 0 Zona 1 Zona


2
/NEC505+ (Zona 20 polvo) (Zona 21 polvo) (Zona 22
polvo)
________________________________________________________________________________________________

CATEGORIAS DE G1 G2 G3
SEGURIDAD
PARA VAPORES*
________________________________________________________________________________________________

CATEGORIAS DE D1 D2 D3
SEGURIDAD
PARA POLVOS*

Zonas, Divisiones Y Categoras de Seguridad: Medida de la probalidad que el peligro este


presente. Esto define el mtodo de proteccin que puede ser empleado. El Cdigo Nacional
Elctrico (NEC) es una marca registrada de La National Fire Protection Association (NFPA) NEC
505 cubre gases y vapores explosivos., solamente de acuerdo a la directriz Estadounidense 94/9
EU (ATEX).

2
TEMPERATURE CLASSIFICATION

Max. Temperatura NEC IEC79-8 EN 50 014


Superficial(C) Tabla 500-3(d) T Clasificacin
___________________________________________________________________________________

450C T1 T1 T1
___________________________________________________________________________________

300C T2 T2 T2
___________________________________________________________________________________

280C T2A -- --
___________________________________________________________________________________

260C T2B -- --
___________________________________________________________________________________

230C T2C -- --
___________________________________________________________________________________

215C T2D -- --
___________________________________________________________________________________

200C T3 T3 T3
___________________________________________________________________________________

180C T3A -- --
___________________________________________________________________________________

165C T3B -- --
___________________________________________________________________________________

160C T3C -- --
___________________________________________________________________________________

135C T4 T4 T4
___________________________________________________________________________________

120C T4A -- --
___________________________________________________________________________________

100C T5 T5 T5
___________________________________________________________________________________

85C T6 T6 T6

Una lista completa de gases y clasificaiones de temperaturas es publicada en el Code-Digest de


Crouse-Hinds.

Metodos de Proteccion Contra Explosion


Mtodo de Permitio Pemitido IEC CENELEC
Code letter
Proteccin Para Divisin Para Zona Estndar Estndar
IEC Ex...

CENELEC
79- EN 50...
EEx...
________________________________________________________________________________________________________

Requerimientos - - 0 014
-
Generales
________________________________________________________________________________________________________

3
Inmersin 1 or 2 1 or 2 6 015
o
en Aceite
________________________________________________________________________________________________________

Presurizado 1 or 2 1 or 2 2 016
p
________________________________________________________________________________________________________

Encapsulado en
Polvo O Arena 2 1 or 2 5 017
q
________________________________________________________________________________________________________

A Prueba de
Explosin - 1 or 2 1 018
d
________________________________________________________________________________________________________

Seguridad
Aumentada 2 1 or 2 7 019
e
________________________________________________________________________________________________________

Seguridad 1 or 2 0*,1 or 2 11 020(aparatos)


ia or ib

Intrinseca 039(Sistema)
________________________________________________________________________________________________________

Sellado 1 or 2 1 or 2 - -
-
de Fabrica
________________________________________________________________________________________________________

Aparatos
Electricos 2 2 15 021(pending)
n
Con proteccin
tipo "n"^
________________________________________________________________________________________________________

Encapsulado - 1 or 2 18 028
m
________________________________________________________________________________________________________

Especial - 1 or 2 Ninguno** Ninguno


s
________________________________________________________________________________________________________

*1A: Zona 0, 1, 2; 1B: Zona 1,2, Excluyendo Zona 0 ** ME


^ Incluye, O-Chispa, Respiracion Restrigida, Sellado Hermticamete, No-Incendiario, Etc.

Organismos de Certificacion En Norte-America Y


Estados Unidos
Pais Organismo de Pais
Organismo de
Certificacin
Certificacin
__________________________________________________________________________________________

4
EUA Underwriters
Laboratories EUA Factory
Mutual
__________________________________________________________________________________________

EUA ETL Canada CSA


__________________________________________________________________________________________

Mxico ANCE Austria TUV-


A
__________________________________________________________________________________________

Austria BVFA Belgica


ISSEP
__________________________________________________________________________________________

Dinamarca DEMKO Finlandia VTT


__________________________________________________________________________________________

Francia INERIS Francia LCIE


__________________________________________________________________________________________

Italy CESI Holanda KEMA


__________________________________________________________________________________________

Noruega NEMKO Espaa LOM


__________________________________________________________________________________________

Suecia SP Reino Unido


BASEEFA/EECS
__________________________________________________________________________________________

Reino Unido SCS Alemania PTB


__________________________________________________________________________________________

Alemania BVS

Indices de Proteccin: Codigos (IP) y Tipos


Nema
Primer Digito Segundo Digito
Proteccin Contra Slidos Proteccin Contra Lquidos
_____________________________________________________ __________________________________________________________

0 - Sin Proteccin 0 - Sin Proteccin


_____________________________________________________ __________________________________________________________

1 - Objetos Iguales O Mayores A 50 1 - Caida de Agua Vertical


mm __________________________________________________________
_____________________________________________________
2 - Caida de Agua Con Un ngulo de
2 - Objetos Iguales O Mayores A Entre 75-105
12.5 mm __________________________________________________________
_____________________________________________________
3 - Agua Atomizada
3 - Objetos Iguales O Mayores A __________________________________________________________

2.5 mm 4 - Salpicadoras de Aqua


_____________________________________________________ __________________________________________________________

4 - Objetos Iguales O Mayores A 5 - Chorros de Agua


1.0 mm __________________________________________________________
_____________________________________________________
6 - Golpes de Mar; Fuertes Chorros de
5 - Protegido Contra Polvo Agua
_____________________________________________________ __________________________________________________________

6 - Hermtico Al Polvo 7 - Efectos de Inmersin


_____________________________________________________ __________________________________________________________

8 - Inmersin Indefinida
__________________________________________________________

5
Ejemplo: IP56

Primer Dgito Segundo Dgito


Proteccin Contra Slidos Proteccin Contra Lquidos
_____________________________________________________ __________________________________________________________

0 - Sin Proteccin 0 - Sin Proteccin


_____________________________________________________ __________________________________________________________

1 - Objectos Iguales O Mayores A 1 - Cada de Agua Vertical


50 mm __________________________________________________________
_____________________________________________________
2 - Cada de Agua Con Un ngulo de
2 - Objectos Iguales O Mayores A Entre 75-105
12.5 mm __________________________________________________________
_____________________________________________________
3 - Agua Atomizada
3 - Objectos Iguales O Mayores A __________________________________________________________

2.5 mm 4 - Salpicadoras de Aqua


_____________________________________________________ __________________________________________________________

4 - Objectos Iguales O Mayores A 5 - Chorros de Agua


1.0 mm __________________________________________________________
_____________________________________________________
6 - Golpes de Mar; Fuertes Chorros de
5 - Protegido Contra el Polvo Agua
_____________________________________________________ __________________________________________________________

6 - Hermtico al Polvo 7 - Efectos de Inmersin


_____________________________________________________ __________________________________________________________

8 - Inmersin Indefinida
__________________________________________________________

Equivalencia de Envolventes Tipo NEMA A Clasificacion Segun IEC


(No Puede de Ser Empleada Para Convertir Clasificacin Segun IEC Al Tipo
NEMA)

Envolventes NEMA Tipo Envolventes IEC


Designacion de la
Clasificacion
____________________________________________________________________________

3 IP54
____________________________________________________________________________

3R IP54
____________________________________________________________________________

3S IP54
____________________________________________________________________________

4 and 4X IP56
____________________________________________________________________________

5 IP52
____________________________________________________________________________

6 and 6P IP67
____________________________________________________________________________

12 and 12K IP52

Tipo de Envolvente s, Segun NEMA Y UL.


Envolvente Tipo 3
Las Envolventes Tipo 3 Son Empleadas En Lugares Exteriores, Principalmente Para - Proveer Un
Grado de Proteccin Contra Polvo En El Ambiente, Lluvia, Granizo Y - Formacin Externa de
Hielo.
6
Envolvente Tipo 3R
Las Envolventes Tipo 3R Son Empleadas En Lugares Exteriores, Principalmente Para - Proveer
Un Grado de Proteccin Contra Lluvia Y Formacin Externa de Hielo.

Envolentes Tipo 3S
Las Envolventes Tipo 3S Son Empleadas En Lugares Exteriores, Principalmente Para-Proveer
Un Grado de Proteccin Contra Lluvia, Granizo, Polvo Y Para Permitir La- Operacin de
Mecanismos Externos Cuando Neva.

Envolventes Tipo 4
Las Envolventes Tipo 4 Son Empleadas En Lugares Exteriores, Principalments Para-Proveer Un
Grado de Proteccin Contra Polvo Por Tolvaneras Y Lluvia, Salpicaduras de Agua, Chorro
Directo de Agua Y Formacion Externa de Hielo.

Envolventes Tipo 4X
Las Envolventes Tipo 4X Son Empleadas En Lugares Exteriores, Principalmente Para Proveer
Un Grado de Proteccin Contra Corrosin, Polvo Por Tolvaneras, Lluvia, Salpigadura de Agua,
Chorro Directo de Agua Y Formacin Externa de Hielo.

Envolventes Tipo 7
Las Envolventes Tipo 7 Son Empleadas En Lugares Interiores Clasificados Como Clase I,
Grupos A, B, C D, Definidos En El Cdigo Nacional Elctrico NEC.

Envolventes Tipo 9
Las Envolventes Tipo 9 Son Empleadas En Lugares Interiores Clasificados Como Clase II,
Grupos E, F G, Definidos En El Cdigo Nacional Elctrico NEC.

Type 12 Enclosure
Type 12 enclosures are intended
for indoor use primarily to provide degree of protection against dust, falling dirt and dripping
noncorrosive liquids.