Sunteți pe pagina 1din 79

OPERATION AND MAINTENANCE MANUAL

HIGH PRESSURE CARBON DIOXIDE

MARINE FIRE SUPPRESSION SYSTEM

Prepared for:
EASTERN SHIPBUILDING GROUP
2200 Nelson Street
Panama City, FL 32402

286 FT OSV BOLDINI S.A.


HULL NOS. 155, 156, 157, 158 & 159
ESG P.O. NOS.: A402589, A402590, A402591, A402592 &
A402593
HILLER FILE: JG-6855, JG-6857, JG-6859, JG-6861 & JG-6863

Prepared by:
HILLER SYSTEMS
3751 JOY SPRINGS DRIVE
MOBILE, AL 36693
(251)-661-1275
FOREWORD

The following manual is intended to be used by personnel responsible for the operation
and general periodic maintenance of the CO2 Fire Suppression System. Whenever you
undertake to inspect, test, maintain or service this system, keep in mind that you are
accepting the responsibility for the safety of peoples lives and protection of property and
equipment. This equipment is designed and manufactured to meet the highest
requirements. However, if this equipment is not maintained properly, it may not be
capable of doing the job it is intended to do.
TABLE OF CONTENTS

SECTION DESCRIPTION

I Carbon Dioxide As An Extinguishing Agent

II General Descriptions of Standard Equipment

III Operating Instructions

IV Post Fire Procedures

V System Maintenance & Testing


Mfg (Ansul) Recharge, Inspection & Maintenance
Excerpts from USCG Approval Manual (Modified for Material)

VI Drawings
System Diagrams (Reduced Size: 11 x 17)

VII Component Data


Mfg (Ansul) Component Data (Reference Sheets)
I. CARBON DIOXIDE AS AN EXTINGUISHING AGENT

Carbon Dioxide is a colorless, odorless, electrically non-conductive gas with an approximate


density 50% greater than air. It suppresses fire by reducing the oxygen content of the
atmosphere to a point where combustion cannot be sustained.

Carbon Dioxide is acceptable for use in occupied spaces. Care must be taken, and appropriate
alarms shall be used, to ensure that all personnel are evacuated from the protected space prior to
discharging the system.

Toxicity: In low concentrations, CO2 is only mildly toxic. Concentrations of 9% or greater can
result in loss of consciousness almost immediately. This is due to the lack of oxygen rather than
any toxicity in the CO2.

Cleanliness: Carbon Dioxide is clean, leaves no residue, thereby eliminating costly after-fire
clean-up, and keeping expensive down-time to a minimum. Most materials such as steel,
stainless steel, aluminum, brass, and other metals as well as plastics, rubber and electronic
components are unaffected by exposure to Carbon Dioxide.

Other Safety Considerations: The high pressure discharge of Carbon Dioxide from the system
nozzle(s) can create noise loud enough to be startling. The high velocity discharge can be
significant enough to dislodge objects located directly in the discharge path. Enough turbulence
may be created in the enclosure to move unsecured paper and other light objects. Direct contact
with the vaporizing agent being discharged from the nozzle(s) will have a chilling effect on
objects, and can cause frostbite burns to the skin. The liquid phase vaporizes rapidly when
mixed with air and limits the chilling hazard to the immediate vicinity of the nozzle(s).

Carbon Dioxide is colorless. Discharging into humid atmospheres may cause a reduction of
visibility for a short time, due to fogging and /or the production of dry ice snow.

If it becomes necessary for a person to enter a space before it is thoroughly ventilated, this may
be accomplished by using a fresh air mask or other type of self-contained breathing apparatus.
DO NOT USE a filter type of mask or a canister gas mask. No one should enter such a space
without a person as observer and standby located outside the space.

Should a person be overcome by carbon dioxide, it is essential that the person be immediately
rescued from the space containing the gas. To revive a person so overcome, give plenty of fresh
air and apply artificial respiration (as in the case of drowning) without the use of carbon dioxide as
a stimulant. Call a physician.

An ammonia inhalant may be used and the person should be kept warm by the application of
friction and heat to the extremities.

Storage: Carbon Dioxide is stored in high pressure cylinders as a combination of liquid and gas.
At 70F (21C), approximately 70 percent by weight of cylinder weight is liquid CO2. The
pressure within the cylinder depends on the temperature, being 504 pounds per square inch at 32
degrees F and 850 pounds per square inch at 70 degrees F. The carbon dioxide content is never
determined by using a pressure gauge. The amount of carbon dioxide in a cylinder can be
determined only by weighing the cylinder.
II. GENERAL DESCRIPTION OF STANDARD EQUIPMENT

Protected Spaces (See Drawings for details):


TANK FARM
PORT ENGINE ROOM
STARBOARD ENGINE ROOM
BOW THRUSTER ROOM
EMEGENCY GENERATOR ROOM
PAINT LOCKER

CO2 EQUIPMENT DESCRIPTION AND FUNCTIONS

1. Storage

Ansul carbon-dioxide fire suppression systems store the suppression agent in


high-pressure steel cylinders. Each cylinder is equipped with a valve assembly
and a flexible discharge hose to control the discharge. The cylinder valve
assemblies attach to the distribution piping by means of the flexible hoses.

Actuation of the suppression system is initiated by one or two control head(s),


which attach to the control ports of the cylinder valve(s) on the pilot cylinder(s).
The remaining cylinder(s) are actuated by pressure within the pipe manifold
created from the discharging pilot cylinder(s).

Single cylinder suppression systems utilize cylinder straps to affix the storage
cylinders to bulkheads or other rigid structural members. Marine cylinder
brackets and clamps are employed for multiple cylinder suppression systems to
secure the cylinders and absorb the discharge reactions and to facilitate system
servicing and maintenance.

WARNING: PRESSURIZED (CHARGED) CYLINDERS ARE EXTREMELY


HAZARDOUS AND IF NOT HANDLED PROPERLY, ARE CAPABLE OF
VIOLENT DISCHARGE. THIS MAY RESULT IN SERIOUS BODILY INJURY,
DEATH, OR PROPERTY DAMAGE. ALWAYS HANDLE CARBON DIOXIDE
CYLINDERS ACCORDING TO THE INSTRUCTIONS IN THIS MANUAL.

2. Cylinder and Valve Assemblies

Carbon dioxide is stored in steel cylinders as a liquid under its own vapor
pressure. The cylinders are manufactured in accordance with Department of
Transportation requirements. Each cylinder is equipped with a forged brass
valve assembly, which contains a safety pressure relief for protection against
over pressurization, a discharge outlet and a filling inlet.

The cylinder valve mates with a control head and flexible discharge hose for
agent release and distribution purposes. This cylinder contains a CV98 type
valve. The valve is a pressure seat type and is sealed against leakage by the
pressure of the carbon dioxide within the cylinder.

120 pound cylinder/valve assemblies are used for this Fire Suppression System.
The 120-lb. cylinders have a CV98 valve and a 5/8 inch ID discharge hose.
50 pound cylinder/valve assemblies are used for this Fire Suppression System.
The 50-lb. cylinders have a CV98 valve and a 5/8 inch ID discharge hose.

WARNING: CYLINDERS ARE FACTORY-EQUIPPED WITH A PROTECTION


CAP THREADED SECURELY OVER THE VALVE ASSEMBLY. THIS DEVICE
IS A SAFETY FEATURE AND PROVIDES PROTECTION DURING HANDLING.
THIS CAP MUST BE INSTALLED AT ALL TIMES EXCEPT WHEN THE
CYLINDERS ARE CONNECTED INTO THE SYSTEM PIPING OR BEING
FILLED. DO NOT REMOVE OR HANDLE A CARBON DIOXIDE CYLINDER
UNLESS THE PROTECTION CAP IS INSTALLED.

3. Flexible Hoses

Flexible discharge hoses are used to provide the interconnection between the
cylinder valve and the distribution manifold or piping. The 5/8 inch ID hose is
used with the 120-Ib. & 50-lb. cylinders. The hose contains a swivel female
connection for the CV98 valve and a NPT male thread for the pipe manifold.

WARNING: FLEXIBLE HOSES MUST BE CONNECTED TO THE SYSTEM


PIPING BEFORE ATTACHING TO THE CYLINDER VALVES TO PREVENT
INJURY IN THE EVENT OF AN INADVERTENT CARBON DIOXIDE
DISCHARGE.

4. Cylinder Bracketing

Marine cylinder brackets and clamps are designed to rigidly support the installed
carbon dioxide cylinders. The bracketing components are constructed of heavy
structural steel. Bracket assemblies are available in modules for two to six
cylinders and can also be mated together for combination over six. Bracketing
can be assembled to support single row, double row or back-to-back rows of
cylinders. Bracketing uprights and weigh rail supports are also available for
weighing cylinders in place. Bracketing components are painted with a red
enamel coating. Uprights and back frame assemblies can be bolted or welded
together.

5. Actuation

Actuation of the suppression system is initiated by use of the control heads.


Control heads are components that attach to the control ports of the carbon
dioxide cylinder valve assemblies and stop valves. The control head(s) initiates
the suppression system discharge by means of local and/or remote actuation
which allows the carbon dioxide to pressurize the system piping envelope and
operate the system.

One control head is required for suppression systems with one or two cylinders.
Two control heads are required for suppression systems that have three or more
carbon dioxide cylinders.

WARNING: CONTROL HEADS MUST BE IN THE SET POSITION BEFORE


ATTACHING TO THE CYLINDER VALVES TO PREVENT ACCIDENTAL
CARBON DIOXIDE DISCHARGE.
Lever Release Actuator (Control Head).

The manual lever release actuator provides a manual means of CO2 agent
actuation by direct manual actuation of its pull lever (i.e, LOCAL) or cable
actuation when used in conjunction with a remote manual pull station (i.e.,
REMOTE). The control head is equipped with an operating lever secured in the
SET position by a safety/locking pin. By removing the locking pin, the lever can
be rotated to the OPEN position, thereby operating the component utilizing the
control head. The control head is assembled on the cylinder valves and stop
valves. The locking pin can be used to prevent accidental discharge when
installing a cable operated system; however, this pin and wire MUST be removed
when used in conjunction with a remote pull station and cable installation is
complete. NOTE: Failure to complete this step will cause system to NOT
actuate when pull station(s) is used.

Pressure-Operated Stackable Actuator

The pressure-operated stackable actuator, PN 428566, is necessary when


pneumatic actuation is required on any selector valve. This actuator is installed
directly on top of the selector valve, a lever release must be installed on top of
the actuator, and a in. pressure line must be attached to the 1/8 in. pressure
port on the side of the actuator. The actuator must be manually reset after use
by pushing the stem back into the actuation body. The actuator is constructed of
brass. When installed in actuation line, Selector valve pneumatic actuation line
kit, PN 436127, must also be utilized.

Connecting Link.

The connecting link is used to connect the lever release actuators located on the
pilot cylinders, employing the CV-98 valves. An opening in the end of the link
allows connection of the wire rope for cable pull actuated systems.

Stainless Steel Actuation Hose

The Stainless Steel Actuation Hose is used to connect the actuation line flared
tees between each agent tank. The hose has the same thread, 7/16-20, as the
flared tees. The actuation hose allows flexibility between the rigid actuation
piping and the tank valve. Maximum Bend Radius: 27/32 in. (21 mm).

6. Valves

Selector (Directional) Valve

The directional stop valve is used to direct the flow of carbon dioxide into a single
hazard or with various types of multiple hazard system compartments. Every
valve must have a lever release actuator installed to it. The directional valve can
be operated manually (LOCAL) or by means of a cable pull station (REMOTE).
The directional valve is installed in the distribution manifold.

Check Valve

The check valve is used in directional valve arrangements that utilize a common
set of carbon dioxide cylinders to protect multiple spaces of unequal sizes. The
check valves divide the cylinder assemblies into sub-sets, for discharge of the
required amount of carbon dioxide into each protected space. Refer to the
system drawings for requirements
Isolation Valve

The isolation valve is used in conjunction with selector valve systems, and can
be used to isolate pressure operated alarms and shut down devices. It is
designed to withstand a minimum burst pressure of 6000 psi (413.7 bar) and is
tested to a working pressure, with carbon dioxide, of 900 psi (62.1 bar).

7. Discharge Nozzles (Refer to drawings for type and size)

Discharge nozzles control the distribution of carbon dioxide into the protected
area or onto the protected equipment (or process). Ansul discharge nozzles are
designed to provide the proper combination of flow rate and discharge pattern to
protect vital equipment in a total-flooding manner. The Ansul discharge nozzles
are permanently marked to identify the nozzles code number.

Baffle Nozzle, Type B and BL.

The Baffle type nozzle is used in total flooding applications only. Placed around
the outside edge and near the overhead allows for a 180 fan spray of carbon
dioxide. Discharge rates depend upon orifice size and nozzle pressure. The B
type nozzle consists of a single orifice ranging in sizes from 1 to 14 with an inlet
connection to the distribution piping at NPT. The BL type nozzle consists of
orifice sizes from 9 to 16 with an inlet connection to the distribution piping at
NPT. A strainer is included on nozzles having a code orifice number of 3 or less.

8. Auxiliary Equipment

Auxiliary equipment consists of supplementary items required for a functional


carbon dioxide system, such as time delays, pressure switches and trips, and
other related hardware including warning and instruction plates.

Time Delay

The time delay assembly consists of a cylinder assembly with a manual release
to allow instant override of the delay. The length of the delay is factory set and is
not adjustable. The delay time is listed at 70F. Actual delay times may with
ambient conditions and installation variations. This assembly is installed in the
piping manifold arrangement directly after the pilot (control) cylinders to allow
alarms to sound, as well as shutdown equipment and ventilation prior to carbon
dioxide discharge. The outlet port is connected to the downstream piping or
carbon dioxide manifold for pressure operated (slave cylinder actuation) control.
Time delays are available in 30 or 68 second increments.

Marine Actuation Station

The marine actuation station is used to release the system pilot cylinders by
means of compressed nitrogen gas. The station comes equipped with
stainless steel compression fittings or attaching O.D. stainless steel tubing.
The enclosure is rainproof, constructed of 16 ga. Galvanized steel and is
equipped with a draw pull catch. Actuation pressure is achieved by means of an
LT-20-L Nitrogen cartridge.
Pressure Operated Siren

Pressure-operated siren(s) are connected to the distribution piping and uses the
pressure of the discharged carbon dioxide for activation. The carbon dioxide
pressure creates a high pitch and high decibel wail. The siren is used as a
means of predischarge alarm warning personnel to evacuate the space prior to
discharge. The pressure within the piping system will also allow the siren to
alarm through most of the discharge time.

Pressure-Operated Switches

The pressure-operated switch is connected to the distribution piping and utilizes


the pressure of the discharging carbon dioxide for activation. The carbon dioxide
pressure displaces a piston, which toggles the electrical switch. The piston can
also be operated manually by pulling upward on the stem. These switches are
used to annunciate alarms and shut down ventilation and other equipment. The
standard switch is double pole, single-throw (DPST). Other switch types and
styles are also available. Refer to system drawings for the pressure switch used.

Safety Header

The safety header is a device used to relieve high pressure build-up in a closed
section of piping. If actuation pressure should get inadvertently trapped and
should an increase in temperature cause the pressure to rise to a dangerous
level, the burst disc in the header safety will rupture, allowing the pressure to
escape.

Header Vent Plug

The header vent plug is used to release low pressure build up that may occur in
closed systems utilizing time delays or selector valves. The header vent plug
should also be installed on cylinder sides of the check valves on both main and
reserve systems to relieve any pressure that may leak past the check valve and
accidentally actuate the reserve system while the main system is discharging.

Instruction and Warning Nameplates

Instruction and warning nameplates are included throughout the system


installation. These plates provide operating personnel the proper operating
instructions and appropriate precautions in the event of system operation or an
emergency.

Warning:

Warning VACATE plates are required and shall be located at each pressure
operated alarm siren. This plate provides warning to personnel to vacate the
space once alarm sounds.

Warning ENTRANCE plates are required and shall be located at each spaces
entrance to the compartment. This plate provides the precaution nary measures
to personnel to warn that the space contains and is protected by a carbon dioxide
fire extinguishing system and not to enter the space.

Instruction:

Operating instruction plates are required and located throughout the system
installation. These plates are provided to allow personnel the information and
instruction to the proper actions required in case of system operation.
9. Optional Equipment

Optional equipment consists of supplementary or other accessory items required


for a functional carbon dioxide system, such as weigh scales, special tools, other
related hardware and miscellaneous alarms.

Discharge Indicator

The discharge indicator is installed in the discharge piping to visually indicate a


system discharge. When carbon dioxide is discharged, a piston pushes the outer
nameplate off, exposing the inner nameplate System Discharge. This
component is optional. Refer to the system drawings for the use of this device.

Weigh Scale

The weigh scale gives direct reading of the weight of the cylinders. This
arrangement provides simplified weighing for cylinders in place without
disconnecting them from the cylinder bank. The scale consists of a scale, beam,
yoke and weigh hook. The weigh scale hook shall be placed on the cylinder
foundation weigh bar for proper weighing of the cylinder.
III. OPERATING INSTRUCTIONS
This Ansul fire extinguishing system is manually operated. It is imperative that there be as little
delay as possible in carrying out the following instructions, as the effectiveness of the carbon
dioxide is materially increased by smothering the fire in its early stages.

WARNING: Alert and evacuate personnel from fire hazard area immediately
on detection of a fire and where possible prior to actuation of the system.

OPERATION: For Tank Farm, Port Engine Rm, STBD Engine Rm & Bow Thruster Rm

Remote

Remote manual fire extinguishing system operation is performed as follows:


Proceed to location of Remote actuation station marked for hazard afire.

1. Pull the operating handle marked CYLINDER RELEASE.


2. Pull the operation handle marked VALVE RELEASE.

Alarm sounds 68 seconds prior to gas discharge, warning personnel to evacuate


space. Equipment and ventilation systems will shutdown.

Local

If remote actuation station fails to operate, discharge the system at cylinder bank.

Discharge cylinder(s) by operating the lever control heads release actuators


connecting link mounted on the control cylinder(s). Immediately operate lever of
control head mounted on the control valve.

WARNING: DO NOT ENTER HAZARD AREA IN WHICH FIRE HAS BEEN


EXTINGUISHED WITH AN OPEN FLAME OR LIGHTED CIGARETTE, AS THE
POSSIBLE PRESENCE OF FLAMMABLE VAPORS MAY CAUSE RE-
IGNITION OR EXPLOSION. BE SURE FIRE IS COMPLETELY
EXTINGUISHED BEFORE VENTILATING AREA. BEFORE PERMITTING
ANYONE TO ENTER THE SPACE, VENTILATE AREA THOROUGHLY OR
ENSURE SELF-CONTAINED BREATHING APPARATUS IS BEING USED.

OPERATION: For Emergency Generator Rm & Paint Locker

Remote

Remote manual fire extinguishing system operation is performed as follows:


Proceed to location of Remote actuation station marked for hazard afire.

1. Pull the operating handle marked CYLINDER RELEASE.


2. Pull the operation handle marked VALVE RELEASE.

Alarm sounds 30 seconds prior to gas discharge, warning personnel to evacuate


space. Equipment and ventilation systems will shutdown.

Local

If remote actuation station fails to operate, discharge the system at cylinder bank.
Discharge cylinder(s) by operating the lever control heads release actuators
connecting link mounted on the control cylinder(s). Immediately operate lever of
control head mounted on the control valve.

WARNING: DO NOT ENTER HAZARD AREA IN WHICH FIRE HAS BEEN


EXTINGUISHED WITH AN OPEN FLAME OR LIGHTED CIGARETTE, AS THE
POSSIBLE PRESENCE OF FLAMMABLE VAPORS MAY CAUSE RE-
IGNITION OR EXPLOSION. BE SURE FIRE IS COMPLETELY
EXTINGUISHED BEFORE VENTILATING AREA. BEFORE PERMITTING
ANYONE TO ENTER THE SPACE, VENTILATE AREA THOROUGHLY OR
ENSURE SELF-CONTAINED BREATHING APPARATUS IS BEING USED.

Sequence of Events

1. Upon operation of the manual pull stations at the hazard egress:


A) Pressure switch activated upon system actuation
B) Pre-discharge Time delay activated (60 seconds)
C) Predischarge Siren Sounds to evacuate area
D) CO2 release after time delay period

2. System may be operated locally at the cylinder bank. Follow local


procedures. CO2 will discharge normally. Time delay by-pass if operated
will discharge CO2 immediately.

Periodically Testing the System

1. The system should be tested at regular intervals to ensure its operational


reliability and optimum performance.
IV. POST FIRE PROCEDURES

After a CO2 system discharge, qualified fire suppression system maintenance personnel
must perform post fire maintenance. Observe all warnings especially those pertaining to
the length of elapsed time before entering the hazard area following discharge.

WARNING: DO NOT ENTER THE HAZARD WITH AN OPEN FLAME OR LIGHTED


CIGARETTE. THE POSSIBLE PRESENCE OF FLAMMABLE VAPORS MAY CAUSE
RE-IGNITION OF FLAMMABLE VAPORS OR EXPLOSION. FOR DEEP SEATED
HAZARDS, THE SPACE MUST BE KEPT TIGHTLY CLOSED FOR 20 TO 60 MINUTES
AFTER SYSTEM DISCHARGE. BE SURE FIRE IS COMPLETELY EXTINGUISHED
BEFORE VENTILATING AREA. BEFORE PERMITTING ANYONE TO ENTER THE
HAZARD, VENTILATE AREA THOROUGHLY OR USE SELF-CONTAINED
BREATHING APPARATUS.

1. Remove discharged cylinders and return to an Ansul distributor for refurbishment and
recharge immediately after use. (See maintenance instructions).

2. Reset ANY pressure-operated switch(es). (See piping layout for quantity and
approximate location.)

3. Reset manual control head(s). Replace any control head that fails to reset properly.
Follow the manufacturers procedures.

WARNING: VERIFY CONTROL HEAD IS IN SET POSITION WITH PLUNGER FULLY


RETRACTED BEFORE INSTALLING ON A CHARGED CYLINDER. CONTROL HEAD
IN THE RELEASED POSITION WITH PLUNGER EXTENDED WILL CAUSE
CYLINDER TO DISCHARGE, RESULTING IN POSSIBLE PROPERTY OR
EQUIPMENT DAMAGE, PERSONAL INJURY OR DEATH.

4. If system was operated by mechanical pull boxes:

A) Reset the cable leading to the pull box. Work the cable back and forth several
times to make certain that it does not bind. Replace broken glass in pull box.
B) Remove control head(s) from cylinder(s), and reset lever release actuators.
Make sure plunger is retracted into body (SET) position. Reinstall lever release
actuator control heads to cylinder(s). Tighten mounting nuts securely.

5. Inspect the orifices of all nozzles to make certain that they are NOT obstructed. DO
NOT REMOVE any nozzle tip from its bowl.

6. Remove the cap(s) from any dirt trap(s) or remove LAST nozzle located at end of
distribution piping and inspect for foreign matter. Replace cap or nozzle wrench tight.

7. Reset ANY distributing valve(s) to its normal position.

8. Reset ANY discharge indicator in cylinder manifold. (If installed)


NOTE: Not all manifolds have a discharge indicator; it depends on system design.

9. Reinstall the recharged cylinder(s). (See maintenance instructions).


V. SYSTEM MAINTENANCE AND TESTING

System Testing and Maintenance is intended to be performed by manufacturer trained and


authorized service technicians completely familiar with CO2 Fire Suppression Systems and the
dangers they may pose to maintenance personnel as well as persons occupying the hazard area.

A. CARBON DIOXIDE EQUIPMENT TESTING AND MAINTENANCE

WARNING: CO2 CYLINDER VALVE ASSEMBLIES MUST BE HANDLED, INSTALLED, AND


SERVICED ONLY BY TRAINED PERSONNEL IN ACCORDANCE WITH THE INSTRUCTIONS
CONTAINED IN THIS SECTION AND COMPRESSED GAS ASSOCIATED (CGA)
PAMPHLETS C-1, C-6, G-6, AND P-1. CGA PAMPHLETS MAY BE OBTAINED FROM
COMPRESSED GAS ASSOCIATION, 123S JEFFERSON DAVIS HIGHWAY, ARLINGTON, VA
22022.

BEFORE PERFORMING MAINTENANCE PROCEDURES, REFER TO THE MATERIAL


SAFETY DATA SHEETS AND ANY SAFETY BULLETINS IN THE APPENDIX.

ALL PRESSURIZED EQUIPMENT MUST BE ISOLATED FROM ACTUATION DEVICES PRIOR


TO PERFORMING SYSTEM MAINTENANCE. OBSERVE ALL SAFETY PRECAUTIONS
APPLICABLE TO HANDLING PRESSURIZED EQUIPMENT. RECHARGE OF CO2 CYLINDER
VALVE ASSEMBLIES MUST BE ACCOMPLISHED ONLY BY ANSUL DISTRIBUTORS.

1. General

Fire suppression systems require proper care to ensure normal operation at all times.
Periodic inspections must be made to determine the exact condition of the system
equipment. A regular program of systematic maintenance is essential for proper
operation of the carbon dioxide system. A periodic maintenance schedule must be
followed and an inspection log maintained for ready reference. As a minimum, the log
should record inspection interval, inspection procedure, maintenance performed, if any as
a result of inspection, and name of inspector performing task. If inspection indicated
areas of rust or corrosion, immediately clean and repaint the area.

2. Preventive Maintenance

Perform preventive maintenance as instructed below. The inspection procedures and


intervals are recommended and can be modified to fit into normal facility schedules
providing the intervals do not exceed the time periods indicated.

Monthly

Inspect hazard area system components.

Semi-Annually

Check CO2 cylinder weights.


Test pressure switch.
Every 2 years

Blow out distribution piping.

Every 5 years

Inspect and/or hydrostatically test CO2 cylinders and flexible discharge hoses.

3. Inspection and Test Procedures

Inspection Procedures - Monthly

1. Make a general inspection survey of all cylinders and equipment for damaged
or missing parts. If any equipment requires replacement refer to the appropriate
instructions.

2. Ensure access to each hazard area manual release stations, discharge


nozzles, and cylinders are unobstructed and there are no obstructions to the
operation of the equipment or distribution of carbon dioxide.

3. Inspect CO2 lever release actuator control heads for physical damage,
deterioration, corrosion, distortion, cracks, dirt, and loose couplings. Tighten
loose couplings. Replace control head if damage is found. If necessary, clean
as indicated in appropriate instructions.

4. Inspect carbon dioxide cylinder and valve assembly for leakage, physical
damage such as cracks, dents, distortions, and worn parts. Check burst disc for
damage and replace if necessary. If necessary, clean cylinder and associated
parts as indicated in the appropriate instructions.

5. Inspect cylinder straps, cradles, and attaching hardware for loose, damaged,
or broken parts. Check straps and associated parts for corrosion, oil, grease,
grime, etc. Tighten loose hardware. Replace damaged parts. If necessary,
clean as indicated in the appropriate instructions.

6. Inspect flexible discharge hoses for loose fittings, damaged threads, cracks,
rust, kinks, distortion, dirt, and frayed wire braids. Tighten loose fittings and
replace hoses, which have stripped threads. If necessary, clean as indicated in
the appropriate instructions.

7. Inspect discharge manifold for physical damage, corrosion, and dirt. Inspect
manifold support brackets and clamps for looseness and damage. Inspect
connections to manifold for tightness. Inspect check valves, where applicable,
for deformation, leakage, cracks, wear, corrosion, and dirt. Secure loose parts.
Replace damaged parts. If necessary, clean as indicated in the appropriate
instructions.

8. Inspect discharge nozzles for dirt and physical damage. Replace damaged
nozzles. If nozzles are dirty or clogged, refer to the paragraph on cleaning.

CAUTION: Nozzles must never be painted. The part number of each nozzle
is stamped on the nozzle. Nozzles must be replaced by nozzles of the
same part number. Nozzles must never be interchanged, since random
interchanging of nozzles will adversely affect proper CO2 distribution within
a hazard area.
9. Inspect pressure switches for deformations, cracks, dirt or other damage.
Replace switch if damage is found.

Semi-Annual Weighing of CO2 Cylinders

WARNING: THE CO2 CYLINDERS ARE EQUIPPED WITH A HIGH RATE


DISCHARGE VALVE, WHICH WHEN ACTUATED, WILL OPEN, REMAIN
OPEN, AND CAN NOT BE CLOSED. ACCIDENTAL ACTUATION OF THE
DISCHARGE VALVE ON AN UNSECURED, DISCONNECTED CYLINDER
WILL RESULT IN A DISCHARGE THRUST CAPABLE OF PROPELLING THE
CYLINDER TO VELOCITIES THAT WILL CAUSE SEVERE PROPERTY
DAMAGE AND BODILY INJURY.

IT IS THEREFORE EXTREMELY IMPORTANT THAT THE EXACT SEQUENCE


OF CYLINDER REMOVAL ALWAYS BE FOLLOWED. FURTHERMORE,
CYLINDER REMOVAL OR CYLINDER REPLACEMENT MUST ALWAYS BE
SUPERVISED TO ASSURE FULL COMPLIANCE WITH THE INSTRUCTIONS
IN THIS MANUAL.

1. Remove control head at the coupling nut only (if control head is not present,
proceed to Step 3).

2. Attach protection cap to the actuation port.

3. Loosen cylinder clamps and bracket framing so cylinders can move freely.

4. Hook scale on weighing angle, and slip yoke under cylinder valve assembly.

5. Pull down until cylinder is just clear of floor and lever is horizontal.

6. Read weight directly off scale. The scale is calibrated to compensate for
leverage. Empty cylinder weight is stamped on the cylinder assembly; therefore,
deduct empty weight from scale reading. The result is the amount, known as the
charge weight of carbon dioxide in the cylinder.

7. If charge weight loss exceeds 10%, follow Cylinder Removal Instruction and
forward cylinder WITH DISCHARGE AND CONTROL HEADS REMOVED AND
SAFETY CAP AND PROTECTION CAP INSTALLED to a recognized ANSUL
distributor.

8. After all cylinders have been weighed, tighten cylinder clamps and framing.

9. Reinstall release actuator control heads on cylinders.

10. Tighten control head coupling nuts securely.

Pressure Switch Test

Perform pressure switch test as follows:

1. Contact appropriate personnel and obtain authorization for shutdown.

2. Check that hazard area operations controlled by pressure switch are


operative.
3. Manually operate switch.

4. Check that hazard area operations controlled by pressure switch shut down.

5. Return pressure switch to SET position.

6. Reactivate all systems shut down by pressure switch. This includes power
and ventilation systems, equipment, etc.

Two Year Inspection

Before blowing out system, remove the dust caps from the ends of the
distribution piping to allow any foreign matter to blow clear. Blow out all
distribution piping with dry air or CO2 to make sure it is not obstructed.

WARNING: DO NOT USE WATER OR OXYGEN TO BLOW OUT PIPE LINES.


THE USE OF OXYGEN IS ESPECIALLY DANGEROUS AS THE POSSIBLE
PRESENCE OF EVEN A MINUTE QUANTITY OF OIL MAY CAUSE AN
EXPLOSION.

1. Remove any caps on dirt traps from piping to allow any foreign matter to blow
clear.

2. Remove all carbon dioxide cylinders from manifold. Isolate flexible hoses
and/or secure to the pipe manifolds.

3. Remove release actuator control heads from pilot cylinder(s).

4. Open distributing valve(s) and keep open long enough to ensure cleanliness.

5. Secure space and evacuate all personnel. Discharge test cylinder(s) into
system manifold.

6. Ensure the release actuator control heads are in the set position. Reconnect
all control heads to pilot cylinders.

7. Reconnect all carbon dioxide cylinders to manifold.


5 Year Inspection and Test Guidelines

Carbon Dioxide Cylinders

CAUTION: These guidelines do not apply to cylinders containing


commodities other than C02.

All ANSUL CO2 cylinders are designed, fabricated, and factory tested to comply
with DOT CFR 49 Regulations 3A- or 3AA- as stamped on each cylinder.

CO2 cylinders must be hydrostatically tested and marked in accordance with


DOT CFR 174.04-1 as follows:

1. Any cylinder which has been discharged or removed from the system
subsequent to five (5) years from the date of the last hydrostatic test, as
indicated by the marking on the cylinder shoulder, must be emptied, retested,
and remarked.

2. A cylinder continuously in service for a period of time exceeding five (5) years
must, after twelve (12) years have elapsed from the date of the previous test
and marking, be removed from service, its contents discharged, and the
cylinder retested and remarked.

3. A cylinder must also be hydrostatic tested and remarked immediately if the


cylinder shows evidence of distortion, damage, cracks, corrosion, or
mechanical damage. Any cylinder failing the hydrostatic pressure test must
be destroyed.

Flexible Hoses

Flexible connections between cylinders and distribution piping must be renewed


or tested at a pressure 1,000 psig (6.9 MPa). At test pressure, the pressure must
not drop at a rate greater than 150 psi (1.03 MPa) per minute for a two minute
period. The test must be performed when the cylinders are retested.

4. Cleaning

Remove dirt from metallic parts using a lint-free cloth moistened with dry cleaning
solvent. Dry parts with clean, dry, lint-free cloth or air blow dry. Wipe non-metallic parts
with clean, dry, lint-free cloth. Remove corrosion with crocus cloth.

5. Nozzle Service

Service nozzles after use as follows:

1. Clean outside of nozzles with rag or soft brush.

2. Examine discharge orifices for damage or blockage. If nozzles appear to be blocked,


unscrew nozzles and clean by immersing in dry cleaning solvent and drying
thoroughly with lint-free cloth. Replace damaged nozzles. Nozzles must be replaced
with same part number.
6. Repairs

Replace all damaged parts during inspection. Replacement procedures for CO2 cylinders
are provided below. For replacement of other system components, refer to drawings and
component assembly drawings provided for guidance. Part numbers of the components
are provided on the drawings.

7. Removal of Cylinders

CO2 Cylinders

WARNING: WHEN REMOVING CHARGED CYLINDERS, ALWAYS


DISCONNECT THE FLEXIBLE DISCHARGE HOSES FIRST. THIS WILL
ELIMINATE THE POSSIBILITY OF DISCHARGING THE CO2 RESULTING IN
POSSIBLE EQUIPMENT AND PROPERTY DAMAGE OR INJURY TO
PERSONNEL.

These instructions must be carefully performed in the exact order given when
any cylinder or group of cylinders is to be removed at any time.

1. Remove flexible discharge hoses from cylinder valve by loosening swivel


mounting nut. On multiple cylinder installations, swing discharge hoses away
from cylinder and allow to hang.

2. Remove all release actuator control heads from the pilot cylinder valve(s) by
loosening mounting nut.

3. Screw large top protection cap to treads on top of cylinder valve. Cap control
head outlet by screwing on side protection cap.

4. Remove cylinder clamps and bracket framing.

5. Remove cylinder.

WARNING: CYLINDER CAP MUST BE SCREWED ON TO PREVENT


DAMAGE TO CYLINDER VALVE DURING REMOVAL. DAMAGE TO
CYLINDER VALVE COULD CAUSE CYLINDER TO DISCHARGE, CAUSING
POSSIBLE EQUIPMENT AND PROPERTY DAMAGE OR INJURY TO
PERSONNEL. THIS CAP IS NOT INCLUDED IN THE EMPTY WEIGHT OF
THE CYLINDER.

8. Installation of Cylinders

CO2 Cylinders

WARNING: WHEN INSTALLING CHARGED CYLINDERS, ALWAYS


REPLACE THE DISCHARGE HOSES LAST. THIS WILL ELIMINATE THE
POSSIBILITY OF DISCHARGING THE CO2, RESULTING IN POSSIBLE
EQUIPMENT AND PROPERTY DAMAGE OR INJURY TO PERSONNEL.

These instructions must be carefully performed in the exact order given below
when any cylinder or group of cylinder is to be installed at any time.

1. Place fully charged cylinder in cylinder rack before removing cylinder cap.
2. Install the cylinder clamps and bracket framing and tighten bolts only enough
to allow for turning of cylinder as may be required later.

3. Remove the cylinder cap and top protection cap from the cylinder valve.
Remove the side protection cap from the cylinder valve to be equipped with
control head(s). Return cap to the storeroom.

4. Turn cylinder so that the cylinder valve outlet points in the proper direction
with flexible hose, tighten bolts of the cylinder bracket and clamps farming
securely.

5. Make certain release actuator control head(s) has been reset as follows:

NOTE: When two heads are connected in tandem with system connecting link,
make certain BOTH are completely reset BEFORE assembling to
cylinder valves.

Lever Release Actuator (Control Head)


a. Return lever to SET position. The plunger should fully recede into the
control head body.
b. Replace locking pin and secure.

6. Install control heads on pilot cylinder valves and tighten mounting nuts.
d. Remove safety/locking pin.

7. Assemble discharge hose(s) to cylinder valve(s) and tighten mounting nut.

WARNING: TO AVOID ACCIDENTAL DISCHARGE, DO NOT INSTALL THE


DISCHARGE HOSE UNTIL CONTROL HEAD HAS BEEN INSTALLED ON
THE CYLINDER VALVE.

9. Cylinder Recharge

CAUTION: CO2 cylinders must not be recharged without a retest if more than five
(5) years have elapsed from the date of last test. Retest shall be in accordance
with the requirements of CER 49, Paragraph 173.34.

Recharge of ANSUL CO2 cylinders should only be performed by an authorized ANSUL


distributor.
APPENDIX A
MATERIAL SAFETY DATA SHEETS

CO2
APPENDIX B
SAFETY BULLETINS
APPENDIX C
TEST FORMS
RECORD OF CYLINDER WEIGHTS
Cylinder Temp. Pressure Tare Gross Date Inspector Cylinder Temp. Pressure Tare Gross Date Inspector
Serial Weight Weight Serial Weight Weight
No. No.
VI. DRAWINGS
VII. COMPONENT DATA
Engineering Submittal
Approved
Rev. Item Description By By Date
- 1. MANUFACTURER COMPONENT DATA SHEETS MH BR 05-22-12
-
-

General Notes

HILLER SYSTEMS, INC.


3751 JOY SPRINGS DRIVE
MOBILE, ALABAMA 36693
Client:
Eastern Shipbuilding Group
2200 Nelson Street
Panama City, FL. 32402
Title:
COMPONENT DATA SHEETS
286 OSV - BOLDINI S.A.
CARBON DIOXIDE FIRE FIGHTING SYSTEM
ESG P.O. Nos. A402589, A402590, A402591, A402592 & A402593
ESG Hull Nos. 155, 156, 157, 158 & 159
2 10-JG6855-CALC CO2 FIRE FIGHTING SYSTEM (Calculations)
1 10-FP-JG6855-DWG CO2 FIRE FIGHTING SYSTEM DIAGRAM
REF. No. DOCUMENT No. DESCRIPTION (TITLE)
Generated By: M. HEIDELBERG
Checked By: B. ROBERTS
Document: Bill Roberts Hiller Systems, Inc.
Approved By: B. ROBERTS (05-22-11) Approved
DOCUMENT NO: 10-JG6855-CDS Rev: ( - )
COVER SHEET 1 of 1
System Components

High Pressure Carbon Dioxide CV-98 Cylinder Shipping Assembly

Description The cylinders are shipped with a maintenance record card


The CV-98 cylinder is factory filled with carbon dioxide. A and protective shipping cap attached to the threaded neck of
single cylinder may be used or multiple cylinders can be each cylinder. This cap entirely encloses and protects the
manifolded together to obtain the required quantity of agent valve while in shipment.
for total flooding or local application methods. The CV-98 The 35 and 50 lb (15.9 and 22.7 kg) cylinders are manufac-
cylinder can be actuated electrically, pneumatically, and/or tured with a bent siphon tube which allows for either hori-
manually with approved valve actuation components. zontal or vertical mounting. When mounting the cylinders in
Note: Operational temperature range of 0-130 F any position other than vertical, the safety relief of the valve
(17.8-54.4 C). must face upwards so the bottom opening of the siphon
tube is directly downward, at the lowest point in the cylinder.

Component Material Thread Size/Type Approvals and Standards

Cylinder Steel 1-11 1/2 NPT, Female Meets DOT 3A1800, 3AA1800, or 3AA2300;
Also meets TC3AM138, TC3AAM138,
TC3AM176, or TC3AAM176.

CV-98 Valve Brass 1-11 1/2 NPT, Male x 1 5/16-12UN-3A


Outlet Thread Male

Valve/Tank UL; ULC (EX-2968) and listed for use with


Assembly FM Approved Systems

Protective Steel 3.125-11 NS1, Female


Shipping Cap

Shipping
Assembly Weight of CO2 Approximate Weight Dimension A Dimension B
Part No. lb (kg) lb (kg) in. (mm) in. (mm)
Finish: Red Enamel Paint

426246 75 (34.0) 215 (97.5) 57 3/4 (1467) 9 1/4 (235)


426149 100 (45.4) 286 (129.7) 60 1/4 (1530) 10 3/4 (273)
426612 (LC) 100 (45.4) 286 (129.7) 60 1/4 (1530) 10 1/2 (268)
428421 120 (54.4) 390 (176.9) 66 5/8 (1692) 11 (279)
Finish: Red Epoxy Paint

426243 35 (15.9) 110 (49.9) 35 3/4 (908) 8 1/2 (216)


426245 50 (22.7) 155 (70.3) 52 3/4 (1340) 8 1/2 (216)
426247 75 (34.0) 215 (97.5) 57 3/4 (1467) 9 1/4 (235)
426613 (LC) 100 (45.4) 255 (115.7) 60 1/4 (1530) 10 1/2 (268)
428422 120 (54.4) 342 (155.1) 66 5/8 (1692) 11 (279)

1-1
1.125-18 THREADED
CYLINDER SHIPPING CAP FOR RELEASE
ATTACHMENTS OR
SHIPPING CAP
VALVE SHIPPING CAP
CV-98 VALVE DISCHARGE BEND OUTLET
WITH RECOIL VALVE
RECORD TAG
(MATES WITH FLEXIBLE
SIPHON TUBE ADAPTOR DISCHARGE BEND, PART
SIPHON TUBE NO. 427082)

FILL PORT (MATES


SAFETY RELIEF WITH FILL ADAPTOR,
DISC (BURST PART NO. 423659)
PRESSURE 2700-
A
3000 PSI, TESTED
HEIGHT PER CGA S-1.1)
TO
OUTLET

001416

B 001816

Note: Use Flexible Discharge Bend (Part No. 427082) when attaching valve to supply pipe or manifold.

CV-98 CO2 VALVE


The CV-98 valve has a ten (10) year warranty. The valve
requires no internal maintenance. The valve is sealed
closed and must never be disassembled. If there is ever a
malfunction of the CV-98 valve, the complete valve must be
sent back to ANSUL for warranty replacement. If the exter-
nal seal is broken, the warranty is voided.

TYCO FIRE PROTECTION PRODUCTS Copyright 2011 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-9880-2
System Components

High Pressure Carbon Dioxide CV-98 Valve Flexible Discharge Bend

Description Shipping Assembly


The CV-98 valve Flexible Discharge Bend (Part No. 427082) Part No. Description
is a 5/8 in. (1.59 cm) I.D. extra-heavy flexible hose which
connects the valve discharge outlet to the fixed piping or 427082 Flexible discharge bend
header manifold. The discharge bend has a female 1 5/16- 42430 Washer
12-UN-3B thread for connecting to the valve outlet and a
male 1/2 in. NPT thread for connecting to the fixed piping or
manifold. The discharge bend will withstand a pressure of
9000 psi (621 bar). Its flexible connection allows for easy
alignment of multiple cylinder banks to fixed piping. Each
bend has a built-in check valve that prevents loss of agent
should the system discharge while any cylinder is removed.
The female adaptor should only be hand tight plus a half
turn with a wrench
The minimum bend radius is 7.5 in. (19 cm).

Thread Size/Type
Component Material Valve End Manifold End Approvals

5/8 in. Flexible SAE 100 R2 1 5/16-12-UN-3B 1/2 NPT Male UL (EX-2968); Listed for use
Discharge Bend Type AT Female with FM Approved systems

18 7/8 IN.
(47.9 cm)
FEMALE ADAPTOR
(THREAD 1 5/16 IN.-12N-3) 1/2 IN. NPT
(BRASS UNS C-36000) MALE COUPLING

CHECK
SWAGE ON

MANIFOLD END
VALVE END

007514

1-2

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90132-2
System Components

High Pressure Carbon Dioxide Lever Release Actuator

Description
Component Material Approvals
The manual lever release actuator provides a manual
All Manual Brass with Listed for use with
means of actuating cylinder valves and selector valves. This
Cable-pull Stainless FM Approved
can be accomplished by direct manual actuation of its pull
Actuators Steel Pin systems;
lever or cable actuation when used in conjunction with a
UL Listed (EX-4510)
remote manual pull station. When used with a remote
manual pull station, the pull station must contain the
components necessary to meet the actuator lever traveling
Shipping
requirements of 7 in. (178 mm) and not exceed 40 lb
Assembly
(18 kg) to operate.
Part No. Description
The actuator is shipped with ring pin and chain attached. If
the ring pin is not required, it must be removed. Failure to 423309 Lever Release (1 1/8-18 mounting
remove the ring pin/chain assembly will prevent system thread) Mounts directly to a CV-98
actuation if a remote cable pull actuation system is cylinder valve.
employed and the ring pin is accidentally installed in the 70846 Lever Release (1 1/4-18 mounting
actuator. thread) Mounts directly to an HF
Three actuators are available. Each is designed for a electric actuator.
specific component. 427207 Lever Release (1 1/8-18 mounting
thread) Mounts directly to the 1 in.,
2 in., 3 in., and 4 in. selector valves.
Mounts directly to pressure operated
stackable actuator (Part No. 428566).
Actuator has the handle painted red.

3 7/8 IN.*
(9.8 cm)
PIN

3 7/8 IN.
(9.8 cm) 000897

WIDTH: 2 3/4 IN. (7 cm)

* Add 1 9/16 in. (3.9 cm) to height when lever is in the straight up position.

Note: The lever actuator used on a CV-90 valve must not


be used on a CV-98 valve.

1-8

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2006028
System Components

High Pressure Carbon Dioxide Connecting Link

Description
The connecting link is used to connect two lever releases
Shipping Assembly
together when two pilot cylinders are required for actuation.
The connecting link can be used on lever releases installed Part No. Description
on CV-98 ANSUL carbon dioxide valves. 42514 Connecting link
One size connecting link is available for all size cylinders.

Component Material Paint Approvals


Connecting Link Steel Red Enamel UL (EX-2968)

PIVOT PIN FLEXLOCK HEX NUT

2 5/16 IN.
(5.87 cm)

14 1/4 IN. (36.2 cm)

3/4 IN.
(19 mm)

007978

001885

1-24

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90225-1
System Components

High Pressure Carbon Dioxide Actuation Components

Description
7/16 20 1/4 IN. NPT
The Stainless Steel Actuation Hose is used to connect the J.I.C. MALE
actuation line flared tees between each agent tank. The
hose has the same thread, 7/16-20, as the flared tees. The
actuation hose allows flexibility between the rigid actuation
piping and the tank valve. 006385

Minimum Bend Radius: 27/32 in. (21 mm)

Shipping
Assembly
Part No. Description 7/16-20 7/16-20
000433

31809 Stainless Steel Braided Hose,


16 in. (40.6 cm) Female-to-Female
32335 Stainless Steel Braided Hose,
20 in. (50.8 cm) Female-to-Female
32336 Stainless Steel Braided Hose,
24 in. (60.9 cm) Female-to-Female
73596 Stainless Steel Braided Hose,
12 in. (30.5 cm) Male-to-Female
73597 Stainless Steel Braided Hose,
16 in. (40.6 cm) Male-to-Female
73598 Stainless Steel Braided Hose,
20 in. (60.9 cm) Male-to-Female
415142 Stainless Steel Braided Hose,
32 in. (81.3 cm) Male-to-Female
430815 Stainless Steel Braided Hose,
42 in. (107cm) Male-to-Female

Additional Actuation Fittings


Part No.
_______ Description
_________
73236 CV-98 Actuation Adapter
32338 Male Straight Connector
(7/16-20 JIC x 1/4 in. NPT)
32334 Male Elbow
(7/16-20 JIC x 1/8 in. NPT)
31810 Male Elbow (7/16-20 JIC x 1/4 in. NPT)
418359 Male Branch Tee (7/16-20 JIC x 1/8 in. NPT)
31811 Male Branch Tee (7/16-20 JIC x 1/4 in. NPT)

1-44

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2009157
ANSUL
System Components
U.S.C.G. APPROVAL NO. 162.162/1/0 REV. 0
UL EX-4510 3-1-03 Page 1-17a

Marine Actuation Station Two Step (S.O.L.A.S.)

Description
The marine actuation station is used to release the system
Shipping
pilot cylinders by means of compressed nitrogen gas. This
Assembly Part No. Description
is accomplished by pulling the operating handle marked
CYLINDER RELEASE which punctures the nitrogen car- 418731 Marine Actuation Station
tridge, allowing the gas to flow to a pilot port located on the Two Step
pilot cylinders, and pulling the operating handle marked 87012 LT-20-L Nitrogen Cartridge
VALVE RELEASE which punctures the nitrogen cartridge,
allowing the gas to flow to a pressure operated selector
valve. Component Material Approvals
The marine actuation station comes equipped with 1/4 in. Marine Actuation Steel UL Listed
stainless steel compression fittings for attaching 1/4 in. Station Two Step (EX-4510)
O.D. stainless steel tubing. The enclosure is rainproof, con-
structed of 16 ga. galvanized steel and is equipped with a
draw pull catch.
Actuation pressure is achieved by means of an LT-20-L
Nitrogen cartridge, Part No. 87012.

6 IN.
C (152 mm)
V
Y
INSTRUCTION A L
CHART L I
V N
E D 13 IN.
E (330 mm)
TO
R R 12 IN.
VALVE
E PULL CATCH (305 mm)
L R
E
L

NITROGEN
CARTRIDGE

COMPRESSION
FITTING FOR 1/4 IN.
OD S.S. TUBE 10 IN.
(254 mm)

TO
CYLINDER 3 IN. 000694
(76 mm)
System Components
U.S.C.G. APPROVAL NO. 162.162/1/0 REV. 0
UL EX-4510 3-1-03 Page 1-17b

MAXIMUM LENGTH RUN (FEET)


0 50 100 150 200 250 300

.020

58
.025
.028

67
.030
WALL THICKNESS (INCHES)

94
.035
.035

150
.040

.049
.045

.050

.055

.060
1/4 IN. STAINLESS
STEEL TUBE
.065
.065

.070

MAXIMUM LENGTH OF ACTUATION TUBING FROM REMOTE STATION TO CYLINDERS


001382

NOTE: Vent Plug, Part No. 1732, must be utilized in actuation line near system actuator.

ANSUL and INERGEN are trademarks of Ansul Incorporated or its affiliates.

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003034 2003 Ansul Incorporated Litho in U.S.A.
System Components

High Pressure Carbon Dioxide Header Vent Plug

Description
The header vent plug is used to release low pressure build
up that may occur in a closed system utilizing time delays Shipping Assembly
or selector valves. The header vent plug functions by Part No. Description
releasing small amounts of pressure caused by a leaking 40309 Header vent plug
valve that would otherwise cause back-pressure actuation
of the system. When high pressures are encountered, as in
a system discharge, the seal contacts the seat, stopping
the flow of agent from the header vent plug. The header
vent plug should also be installed on the cylinder sides of
the check valves on both main and reserve systems to
relieve any pressure that may leak past the check valve and
accidentally actuate the reserve system while the main sys-
tem is discharging.

Component Material Thread Size/Type Approvals


Vent Plug Body: Brass 1/2 IN. NPT Male UL (EX-2968);
Spring: Bronze Listed for use with
Seal: Neoprene FM Approved systems

STEM
BODY SPRING
CHECK SEAL

CHECK
WASHER CUP

1/2 IN. NPT

7/8 IN. 29/32 IN.


(2.2 cm) (2.3 cm)
000707a
000707b

1-35

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90188-1
System Components

High Pressure Carbon Dioxide Pneumatic Time Delay

Description The time delay is activated by pressure from the pilot cylin-
To meet the requirements of NFPA 12, a mechanical time ders when they are released. After discharge is completed,
delay is required for all carbon dioxide systems that protect the time delay can be returned to service by following the
Normally Occupied or Occupiable spaces protected with procedure in the Resetting and Recharge section of the
total flooding systems, or local application systems where ANSUL Carbon Dioxide Design, Installation, Recharge and
the discharge exposes personnel to concentrations of car- Maintenance Manual. The length of time is factory set and is
bon dioxide in excess of 7.5 percent. These are areas where not adjustable. A manual release is incorporated on the time
it is necessary to evacuate personnel prior to the discharge delay valve to allow instant override of the time delay. The
of a carbon dioxide system. For improved accuracy, the time time delay is available in delay settings of 10, 30, 68, and 88
delay uses nitrogen from an LT-10 cartridge (Part No. seconds.
423423) to power the factory set delay mechanism. The Caution: Use only approved LT-10-R nitrogen cartridges
time delay is installed in the discharge piping, either directly (Part No. 423423). Use of unapproved cartridges will
after the control (pilot) cylinder, or further along the piping. result in improper system operation.

Component Material Thread Size/Type Approvals


Time Delay (10, 30, Valve: Brass 3/4 in. NPT Female UL (EX-2968); Listed for use
68, and 88 second) Accumulator: Steel with FM Approved systems
Booster: Brass

Shipping Assembly
Part No. Description

437715 10 second pneumatic time delay


437716 30 second pneumatic time delay
437717 68 second pneumatic time delay
437718 88 second pneumatic time delay
423423 LT-10-R cartridge shipping assembly

1-31
8 1/2 IN.
(21.6 cm)

2 3/4 IN.
(7 cm)

7 1/4 IN.
(18.4 cm)

7 3/4 IN.
(19.7 cm)

9 7/8 IN.
(25.1 cm)

7 5/16 IN.
(18.6 cm)

15 1/2 IN.
(39.4 cm)

12 7/8 IN.
(32.7 cm)

008608

LT-10-R, Part No. 423423, needs to be ordered separately.

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90207-1
ANSUL
Carbon Dioxide System Components

Check Valve

Description
Check valves are used in main/reserve systems and on cylinders required for protecting a larger hazard. Only the
systems protecting multiple hazards of different volumes cylinders needed for the particular hazard are activated.
using selector valves to control the direction of agent flow. The check valves are available in sizes from 1/2 in. through
On main/reserve systems the check valve prevents pressur- 3 in. Three body styles are available: threaded, weld neck
ization of the reserve system manifold by blocking the flow flange, and threaded flange. The weld neck flange style
of carbon dioxide from the main system. The check valve valves are supplied with two (2) 600 lb. weld neck, flat
allows gas flow from the reserve (if actuated) to pass faced, forged steel flanges, complete with bolts, nuts and
through into the distribution piping. On selector valve sys- gaskets.
tems, the check valve prevents the cylinders from the
selected hazard from pressurizing the manifold of the

Component Material Thread Size/Type Body Type Approvals

Check Valve Bronze 1/2 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

Check Valve Bronze 3/4 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

Check Valve Bronze 1 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

Check Valve Bronze 1 1/4 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

Check Valve Bronze 1 1/2 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

Check Valve Bronze 2 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

Check Valve Bronze 2 1/2 in. NPT Female Threaded U.S. Coast Guard (162.038/7/0)
UL (EX-2968)
FM Approved

1-36
Component Material Thread Size/Type Body Type Approvals

Check Valve Body: N/A 2 in. Weld U.S. Coast Guard (162.038/7/0)
Bronze Neck Flange UL (EX-2968)
Flange: FM Approved
Steel

Check Valve Body: N/A 2 1/2 in. U.S. Coast Guard (162.038/7/0)
Bronze Weld Neck UL (EX-2968)
Flange: Flange FM Approved
Steel

Check Valve Body: N/A 3 in. Weld U.S. Coast Guard (162.038/7/0)
Bronze Neck Flange UL (EX-2968)
Flange: FM Approved
Steel

Check Valve Body: 3 in. NPT Threaded U.S. Coast Guard (162.038/7/0)
Bronze Flange UL (EX-2968)
Flange: FM Approved
Steel

Shipping Assembly
Part No. Description

40860 1/2 in. check valve threaded


40852 3/4 in. check valve threaded
41470 1 in. check valve threaded
41549 1 1/4 in. check valve threaded
41463 1 1/2 in. check valve threaded
40649 2 in. check valve threaded
40656 2 1/2 in. check valve threaded
40794 2 in. check valve weld neck flange
46095 2 1/2 in. check valve weld neck flange
40672 3 in. check valve weld neck flange
40665 3 in. check valve threaded flange

Check Valve - Threaded


Dimension A Dimension B
Valve Size in. (cm) in. (cm)
A
1/2 in. 3 (7.6) 2 5/8 (6.6)
3/4 in. 3 5/8 (9.2) 3 1/8 (7.9)
1 in. 4 1/8 (10.4) 3 3/4 (9.5)
1 1/4 in. 5 (12.7) 4 1/2 (11.4)
BONNET 1 1/2 in. 5 1/2 (13.9) 5 1/8 (13)
SPRING
2 in. 6 1/2 (16.5) 5 3/4 (14.6)
B
CHECK
2 1/2 in. 8 (20.3) 6 3/4 (17.1)

BODY

000679a
Check Valve - Flanged
Dimension A Dimension B
Valve Size in. (cm) in. (cm)
A
2 in. 10 1/4 (26) 7 1/2 (19)
2 1/2 in. 10 3/4 (27.3) 8 11/16 (22.1)
3 in. 11 1/2 (29.2) 9 1/2 (24.1)

000683

Check Valve - Threaded Flange


B
Valve Dimension A Dimension B Dimension C
A Size in. (cm) in. (cm) in. (cm)
SPRING
BONNET
3 in. 11 1/2 (29.2) 15 (38.1) 9 1/2 (24.1)

CHECK

BODY
001817

ANSUL INCORPORATED, ONE STANTON STREET, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90215 1997 Ansul Incorporated Litho in U.S.A.
System Components

High Pressure Carbon Dioxide Selector Valves

Description
Selector valves are used to direct the flow of CO2 into a Selector valves can be manually operated by mounting a
single hazard of a multiple hazard system. lever actuator either directly onto the valve, onto the top of
When pneumatic actuation is required for any selector the pressure operated stackable actuator, or onto the top of
valve, the following must be ordered separately: a the electric actuator. See Lever Release Actuator
Stackable Actuator Assembly, Part No. 428566, and Component Sheet for correct actuator.
Selector Valve Pneumatic Actuation Line Kit, Part No. Note: The Selector Valve Adaptor, Part No. 430832, can
436127. also be used to retrofit older model 1/2 in. through 2 1/2 in.
When electric actuation is required for any selector valve, a selector valves, Part Nos. 57428-57433, when used in
Booster Actuator, Part No. 428949, and HF electric actua- conjunction with Lever Release, Part No. 427207 and the
tor, Part No. 73327, must be ordered separately. Pressure Operated Stackable Actuator, Part No. 428566.

Component Material Thread Size/Type Approvals


1 in. Selector Valve Bronze 1 in. NPT Female UL (EX-2968);
(Used for 1/2 in., 3/4 in. Listed for use with
and 1 in. pipe sizes) FM Approved systems

2 in. Selector Valve Bronze 2 in. NPT Female UL (EX-2968);


(Used for 1 1/4 in., Listed for use with
1 1/2 in. and 2 in. FM Approved systems
pipe sizes)

2 in., 2 1/2 in., 3 in. Ductile 3 in. Flange UL (EX-2968);


Selector Valve Iron American Standard Listed for use with
Raised Face FM Approved systems

4 in. Selector Valve Ductile 4 in. Flange UL (EX-2968);


Iron American Standard Listed for use with
Raised Face FM Approved systems

1-7
Shipping Assembly
Part No. Description
427185 1 in. selector valve threaded
427150 2 in. selector valve threaded
57433 2, 2 1/2, 3 in. selector valve flanged
57445 4 in. selector valve flanged
428566 Pressure operated stackable actuator
428949 Booster Actuator

1 1/8 18 UNEF
1 1/8 18 UNEF SELECTOR VALVE ADAPTOR,
PART NO. 430832

C
C
600 LB AMERICAN
STANDARD
RAISED FACE
FLANGE (INLET
AND OUTLET)
B (MATING B
FLANGES
SUPPLIED BY
OTHERS)

008140 006035

A
NOTE: FOR 2 IN. and 2 1/2 IN. FLANGE SELECTOR VALVES,
USE A 3 IN. FLANGE VALVE.
3 IN. AND 4 IN. FLANGED VALVE 1 IN. AND 2 IN. THREADED VALVE

Shipping Shipping
Selector Assembly Shipping
Valve Sizes Part No. Body A B C Weight
1 in. 427185 Threaded 5 1/2 in. 2 9/16 7 16 lb
1 in. NPT female (140 mm) (67 mm) (178 mm) (7.3 kg)
2 in. 427150 Threaded 7 1/2 in. 3 1/2 8 9/16 33 lb
2 in. NPT female (191 mm) (89 mm) (218 mm) (15.0 kg)
2 in., 2 1/2 in., 57433 Flanged 13 in. 6 1/8 14 1/2 117 lb
3 in. 3 in. (330 mm) (156 mm) (368 mm) (53.0 kg)
4 in. 57445 Flanged 4 in. 16 8 3/4 18 1/8 262 lb
(406 mm) (222 mm) (460 mm) (118.8 kg)

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2002130-1
System Components

High Pressure Carbon Dioxide Pressure Operated Stackable Actuator

Description
1 1/8 18 UNEF
The pressure operated stackable actuator, Par t No.
2.309
428566, is necessary when pneumatic actuation is required
on any selector valve. This actuator is installed directly on
top of the selector valve, a lever release (Part No. 427207)
must be installed on top of the actuator, and a 1/4 in. pres-
sure line must be attached to the 1/8 in. pressure port on
the side of the actuator. The actuator must be manually
reset after use by pushing the stem back up into the actua-
tor body. The actuator is constructed of brass.
When installed in actuation line, Selector Valve Pneumatic
Actuation Line Kit, Part No. 436127, must also be utilized. 2.926

Component Material Approvals


Pressure Operated Brass Listed for use
Stackable Actuator with FM Approved
1/8 IN. NPT
systems; PRESSURE
PORT
UL Listed (EX-2968)

Shipping Assembly 006036

Part No. Description 1 1/8 18 UNEF

428566 Pressure operated


stackable actuator
436127 Selector valve pneumatic
actuation line kit

1-6

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2002131-1
System Components

High Pressure Carbon Dioxide Lever Release Actuator

Description
Component Material Approvals
The manual lever release actuator provides a manual
All Manual Brass with Listed for use with
means of actuating cylinder valves and selector valves. This
Cable-pull Stainless FM Approved
can be accomplished by direct manual actuation of its pull
Actuators Steel Pin systems;
lever or cable actuation when used in conjunction with a
UL Listed (EX-4510)
remote manual pull station. When used with a remote
manual pull station, the pull station must contain the
components necessary to meet the actuator lever traveling
Shipping
requirements of 7 in. (178 mm) and not exceed 40 lb
Assembly
(18 kg) to operate.
Part No. Description
The actuator is shipped with ring pin and chain attached. If
the ring pin is not required, it must be removed. Failure to 423309 Lever Release (1 1/8-18 mounting
remove the ring pin/chain assembly will prevent system thread) Mounts directly to a CV-98
actuation if a remote cable pull actuation system is cylinder valve.
employed and the ring pin is accidentally installed in the 70846 Lever Release (1 1/4-18 mounting
actuator. thread) Mounts directly to an HF
Three actuators are available. Each is designed for a electric actuator.
specific component. 427207 Lever Release (1 1/8-18 mounting
thread) Mounts directly to the 1 in.,
2 in., 3 in., and 4 in. selector valves.
Mounts directly to pressure operated
stackable actuator (Part No. 428566).
Actuator has the handle painted red.

3 7/8 IN.*
(9.8 cm)
PIN

3 7/8 IN.
(9.8 cm) 000897

WIDTH: 2 3/4 IN. (7 cm)

* Add 1 9/16 in. (3.9 cm) to height when lever is in the straight up position.

Note: The lever actuator used on a CV-90 valve must not


be used on a CV-98 valve.

1-8

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2006028
System Components

High Pressure Carbon Dioxide Header Safety

Description
The header safety is a device used to relieve high pressure
build-up in a closed section of piping. If actuation pressure
should get inadvertently trapped and should an increase in SAFETY DISC NUT SAFETY DISC
temperature cause the pressure to rise to a dangerous
level, the burst disc in the header safety will rupture, allow-
ing the pressure to escape. The header safety is available
with 1/2 in. or 3/4 in. NPT threads.

Shipping Assembly SAFETY DISC


WASHER
1/2 IN. OR
Part No. Description 3/4 IN. NPT

40094 1/2 in. header safety 000706b

40076 3/4 in. header safety


78756 Replacement burst disc,
rupture at 2400 to 2800 psi
(165.5 to 193 bar)

Component Material Thread Size/Type Approvals


Header Safety Brass 1/2 or 3/4 in. NPT Male UL (EX-2968);
Listed for use with FM Approved systems

1-34

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90187-1
System Components

High Pressure Carbon Dioxide Pressure Switch 3PST

Description
The pressure switch is operated by the carbon dioxide pres- Shipping Assembly
sure when the system is discharged. This pressure switch Part No. Description
can be used to open or close three-phase electrical circuits
to either shut down equipment or turn on lights or alarms. 42344 Pressure Switch 3PST
The three pole, single throw (3PST) pressure switch is con-
structed with a gasketed, water tight housing. The housing is
constructed of malleable iron, painted red. A 1/4 in. NPT
pressure inlet is used to connect the 1/4 in. pipe from the
carbon dioxide system. Minimum operating pressure is
50 psi (3.5 bar).

Component Material Thread Size/Type Electric Rating Approvals


Pressure Switch Switch: BAKELITE Conduit Inlet: 30A 240 VAC UL (EX-2968);
3PST Housing: Malleable Iron 3/4 in. NPT Female 20A 600 VAC Listed for use
Piston: Brass Pressure Inlet: 3 HP 120 VAC with FM
1/4 in. NPT Female 7.5 HP 240 VAC Approved
15 HP 600 VAC systems
3 PHASE AC

4 IN.
(10.1 cm) 3 3/4 IN.
3 1/16 IN. (9.5 cm)
RESET KNOB
A (7.7 cm) MOISTURE-PROOF GASKET

SNAP LOCK-RING 3/4 IN.


NPT
O RING GASKET
PISTON ROD

SPRING
5 3/16 IN. HALF ROUND ARM
(13.1 cm)
3 7/8 IN. TOGGLE SWITCH WITH FULLY
(9.8 cm) ENCLOSED BAKELITE BASE
SPACER
HALF ROUND ARM BRASS
SWITCH
SPRING HOUSING
008341 NAMEPLATE

PISTON ROD
000715a
PISTON O RING GASKET
PISTON
4 9/32 IN. 000715b
MOUNTING PISTON-SPOT NUT
HOLES SWIVEL NUT

UNION 3/4 IN.


HEX BUSHING BRASS PLUG
3/8 IN. X 1/4 IN.

A SECTION A A

BAKELITE is a trademark of Union Carbide Corp.

1-40

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90199-1
System Components

High Pressure Carbon Dioxide Warning Signs

Description
The following warning plates are required either inside or Mounting Hole Size: 7/32 in. (0.56 cm)
outside the hazard area to warn personnel that the space is Approvals: UL (EX-2968), listed for use with FM Approved
protected by a carbon dioxide system and no one should systems
enter after a discharge without being properly protected.
The warning plates are furnished with four mounting holes Material: Aluminum
for ease of installation.

Part No. 425309 Sign In Every Protected Area Part No. 425310 Sign at Every Entrance
to Protected Space

10 in. (25 cm) x 10 in. (25 cm)


10 in. (25 cm) x 10 in. (25 cm)

Part No. 425311 Sign In Every Nearby Space Where Part No. 425312 Sign at Each Manual Actuation Station
CO2 Can Accumulate to Hazardous Levels

10 in. (25 cm) x 6.5 in. (16.5 cm)


10 in. (25 cm) x 10 in. (25 cm)

1-23
Part No. 433625 Sign at Every Entrance to Protected Part No. 433626 Sign Outside Each Entrance to
Space for Systems Provided with Wintergreen Odorizer Carbon Dioxide Storage Room

10 in. (25 cm) x 6.5 in. (16.5 cm)

10 in. (25 cm) x 10 in. (25 cm)

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2006043
System Components

High Pressure Carbon Dioxide Discharge Nozzle Baffle Type

Description
The baffle type nozzle is used in total flood applications Discharge rate depends upon nozzle pressure and orifice
only. Placed around the outside edge or placed near the size. Baffle type nozzles are available in orifice sizes 1
ceiling approximately 15 to 20 ft (4.6 to 6.1 m) on centers in through 16. The nozzle is supplied in natural brass.
a room or any enclosed space, each nozzle provides a Note: When ordering, specify orifice code required:
180 fan spray of CO2, spreading the extinguishing gas Example Part No. 426121 10.5.
quickly and efficiently throughout the protected space.

Component Material Thread Size/Type Orifice Size Approvals


Baffle Type with Nozzle: Brass 1/2 in. NPT Male 1 through 3 UL (EX-2968);
Strainer Strainer: Monel Listed for use with
FM Approved systems
Baffle Type Brass 1/2 in. NPT Male 3.5 through 14 UL (EX-2968);
Listed for use with
FM Approved systems
Baffle Type BL Brass 3/4 in. NPT Male 9 through 16 UL (EX-2968);
Listed for use with
FM Approved systems

1-18
Baffle Type Nozzle With or Without Strainer (Baffle Type with Strainer)
STRAINER
FORGED 1/2 IN. NPT
BRASS BODY

DISCHARGE ORIFICE

ORIFICE SIZE STAMPED


ON THIS SURFACE

2 5/8 IN.
(6.6 cm)

000662a

1 3/4 IN.
(4.4 cm) 000662b

Shipping Assembly
Part No. Description Orifice Code
426119 Baffle type with strainer nozzle 13
426120 Baffle type without strainer 3.5 14

Baffle Type BL Nozzle

3/4 IN. NPT


3 5/16 IN.
(84 cm)
3 1/4 IN.
(8.2 cm)

DISCHARGE ORIFICE

STAMPED
FORGED
NOZZLE CODE
BRASS BODY 000664b

2 1/4 IN.
000664a (5.7 cm)

Shipping Assembly
Part No. Description Orifice Code
426121 Baffle type BL nozzle 9 16

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90224-3
System Components

High Pressure Carbon Dioxide Cylinder Bracketing

Description
The cylinder bracketing is designed to rigidly support the included) or welded together, which ever makes the instal-
installed carbon dioxide cylinders. The bracketing compo- lation more convenient. For weighing cylinders, a scale and
nents are constructed of heavy structual steel. Bracket lifting yoke is also available.
assemblies are available in modules for two to six cylinders Refer to the Installation and Appendix sections of the
and can also be mated together for any combination over Design manual for further details.
six. Bracketing can be assembled to support single row,
double row or back-to-back rows of cylinders. Bracketing
uprights and weigh rail supports are also available for Component Material Finish Approvals
weighing cylinders in place. Bracketing components are Bracketing Steel Red UL (EX-2968);
painted with a red enamel coating. Uprights and back Paint Listed for use with
frame assemblies can be bolted (fasteners are not FM Approved systems

Shipping Assembly
Part No. Description
45120 35 lb (15.9 kg) and 50 lb (22.7 kg) cylinder strap (single cylinder)
45244 35 lb (15.9 kg) and 50 lb (22.7 kg) cylinder channel with nuts and bolts (single cylinder)
45121 75 lb (34 kg) cylinder strap (single cylinder)
45261 75 lb (34 kg) cylinder channel with nuts and bolts (single cylinder)
45122 100 lb (45.4 kg) cylinder strap (single cylinder)
45245 100 lb (45.4 kg) cylinder channel with nuts and bolts (single cylinder)
427704 120 lb (54.4 kg) cylinder strap (single cylinder)
427705 120 lb (54.4 kg) cylinder channel with nuts and bolts (single cylinder)
79638 Back frame assembly (2 cylinder)
79639 Back frame assembly (3 cylinder)
79640 Back frame assembly (4 cylinder)
79641 Back frame assembly (5 cylinder)
79642 Back frame assembly (6 cylinder)
73257 Upright (used either for right or left side)
426592 120 lb (54.4 kg) upright (used either for right or left side)
73553 Single row or back-to-back row bracket foot (left side)
73554 Single row or back-to-back row bracket foot (right side)
73555 Double row bracket foot (left side)
73556 Double row bracket foot (right side)
73256 Center upright (required when weighing seven or more cylinders in a row)
79413 Connector (required to hook together back frames for seven or more cylinders)
73250 10.5 in. (26.7 cm) carriage bolt with nut (for single row 50 lb (22.7 kg) cylinders)
73251 11 in. (27.9 cm) carriage bolt with nut (for single row 75 lb (34 kg) cylinders)
73252 12.5 in. (31.8 cm) carriage bolt with nut (for single row 100 lb (45.4 kg) cylinders)
418502 13 in. (33.0 cm) carriage bolt with nut (for single row 120 lb (54.4 kg) cylinders)
73253 21 in. (53.3 cm) carriage bolt with nut (for double row 50 lb (22.7 kg) cylinders)
73254 22 in. (55.9 cm) carriage bolt with nut (for double row 75 lb (34 kg) cylinders)
73255 26 in. (66 cm) carriage bolt with nut (for double row 100 lb (45.4 kg) cylinders)
418503 27 in. (68.6 cm) carriage bolt with nut (for double row 120 lb (54.4 kg) cylinders)
73266 Weigh rail (two cylinder)
73267 Weigh rail (three cylinder)
73268 Weigh rail (four cylinder)
73269 Weigh rail (five cylinder)
73270 Weigh rail (six cylinder)
1-19
Shipping Assembly
Part No. Description
73091 Cylinder clamp (2 cylinders)
73092 Cylinder clamp (3 cylinders)
71683 Weigh rail support (single row)
71682 Weigh rail support (double row)
71684 Weigh rail support (back-to-back)
74241 Scale
69877 Lifting yoke

WEIGH RAIL
SUPPORT

UPRIGHT

WEIGH RAIL

BACK FRAME

CYLINDER
CLAMP

CARRIAGE BOLT
WITH NUT

RIGHT
BRACKET FOOT

0001838
LEFT BRACKET FOOT

TYCO FIRE PROTECTION PRODUCTS Copyright 2010 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 715-735-7411 Form No. F-90183-2

S-ar putea să vă placă și