Sunteți pe pagina 1din 132

Pipe

Shields
Inc.

1. 2.

3.

4.
1. Cold insulated pipe anchors with axial stops.

2. Custom cryogenic pipe supports fabricated for an LNG facility.

3. 274 custom hot pipe shoes rush project which were delivered in
three weeks.

4. Insulated pipe supports designed for cryogenic temperatures


down to -320F in an LNG facility.

5. Custom high temperature pipe supports for a granular activated


5. carbon manufacturing plant.
Pipe
Shields
Inc.

Pipe TABLE
Shields,
OF CONTENTS
Inc.
General Introduction.................................................................................................................................................... 5

Temperature, Dimensional and Material Variances................................................................................................. 6-12

Use of the Insulated Pipe Support Selection Guide.............................................................................................. 13-18


Table 1: Water Service-Pipe Supported from Above or Below............................................................. 13
Table 2: Steam/Gas/Air Service-Pipe Supported from Above or Below.............................................. 14
Table 3: Water Service-Pipe Supported from Above in Clevis or 2-Bolt Hanger............................... 15
Table 4: Steam/Gas/Air Service-Pipe Supported from Above in Clevis or 2-Bolt Hanger.................. 16
Table 5: Water Service-Pipe Supported from Below on Pipe Roll or Above..................................... 17
Table 6: Steam/Gas/Air Service-Pipe Supported from Below on Pipe Roll or Above...................... 18

Section A: Pre-Insulated Pipe Support - Commerical & Light Industrial 19-34


Introduction/Index.................................................................................................................................................. 20-21
Insulated Pipe Support..................................................................................................................... 22-34
Model A1000: Regular Duty................................................................................................... 22
Model A2000: Regular Duty w/ Extended Insulation............................................................... 23
Model A3000: Extra Heavy Bottom Jacket.............................................................................. 24
Model A4000: Extra Heavy Bottom Jacket with exterior Insulation........................................... 25
Model A5000: With Load Distribution Plate............................................................................. 26
Model A6000: With Load Distribution Plate with exterior Insulation.......................................... 27
Model A7000: Heavy Duty with Load Bearing Plate................................................................. 28
Model A7200: Heavy Duty with Load Bearing Plate................................................................. 29
Model A7400: Heavy Duty with Load Bearing Plate................................................................. 30
Model A8000: Heavy Duty with Load Bearing Plate................................................................. 31
Model A8200: Heavy Duty with Load Bearing Plate................................................................. 32
Model A8400: Heavy Duty with Load Bearing Plate................................................................. 33
Model A9000: Heavy Duty for use with Rod Hangers............................................................... 34

Section B: Pre-Insulated Pipe Support - Heavy Industrial - Base Mounted 35-47


Introduction/Index.................................................................................................................................................... 36-39
Sliding Insulated Pipe Support-Heavy Duty, Base Mounted........................................................ 40-47
Model B1000: ....................................................................................................................... 40
Model B1100: ........................................................................................................................ 41
Model B1200: ....................................................................................................................... 42
Model B1300: ........................................................................................................................ 43
Model B2000: ........................................................................................................................ 44
Model B2100: ........................................................................................................................ 45
Model B2200: ........................................................................................................................ 46
Model B2300: ....................................................................................................................... 47
Guided Insulated Pipe Support-Heavy Duty, Base Mounted....................................................... 48-55
Model B3000: ...................................................................................................................... 48
Model B3100: ........................................................................................................................ 49
Model B3200: ........................................................................................................................ 50
Model B3300: ........................................................................................................................ 51
Model B4000: ........................................................................................................................ 52
Model B4100: ........................................................................................................................ 53

1
Pipe
Shields
Inc.

Model B4200: ....................................................................................................................... 54


Model B4300: ....................................................................................................................... 55
Wide Base Sliding Insulated Pipe-Support-Heavy Duty, Base Mounted....................................... 56-63
Model B5000: ....................................................................................................................... 56
Model B5100: ....................................................................................................................... 57
Model B5200: ....................................................................................................................... 58
Model B5300: ....................................................................................................................... 59
Model B6000: ....................................................................................................................... 60
Model B6100: ....................................................................................................................... 61
Model B6200: ....................................................................................................................... 62
Model B6300: ....................................................................................................................... 63
Laterally Restrained Insulated Pipe Support-Heavy Duty, Base Mounted............................ 64-71
Model B7000: ....................................................................................................................... 64
Model B7100: ....................................................................................................................... 65
Model B7200: ....................................................................................................................... 66
Model B7300: ....................................................................................................................... 67
Model B8000: ....................................................................................................................... 68
Model B8100: ....................................................................................................................... 69
Model B8200: ....................................................................................................................... 70
Model B8300: ....................................................................................................................... 71

Section C: Insulated Pipe Support - Heavy Industrial - Anchors 72-85


Introduction/Index............................ ........................................................................................................................ 72-73
Welded Tee Pipe Anchor Small Bore.............................................................................................. 74-77
Model C1000, Model C1010, Model C1020, Model C1030..................................................... 74
Model C1100, Model C1110 , Model C1120, Model C1130..................................................... 75
Model C2000, Model C2010, Model C2020, Model C2030..................................................... 76
Model C2100, Model C2110, Model C2120, Model C2130 .................................................... 77
Insulated Friction Pipe Anchor ................................................................................................. 78-81
Model C3000: ....................................................................................................................... 78
Model C3100: ....................................................................................................................... 79
Model C3200: ....................................................................................................................... 80
Model C3300: ....................................................................................................................... 81
Insulated Positive Anchor.............................................................................................................. 82-85
Model C4000, Model C4010, Model C4020, Model C4030 .................................................. 82
Model C4100, Model C4110, Model C4120, Model C4130................................................... 83
Model C4200, Model C4210, Model C4220, Model C4230 .................................................. 84
Model C4300, Model C4310, Model C4320, Model C4330................................................... 85

Section D: Insulated Pipe Support - Heavy Industrial - Hung 86-99
Introduction/Index.................................................................................................................................................... 86-87
Insulated 2-Bolt Hanger..................................................................................................................... 88-93
Model D1000...................................................................................................................... 88
Model D2000:...................................................................................................................... 89
Model D3000:..................................................................................................................... 90
Model D3100:....................................................................................................................... 91
Model D3200:..................................................................................................................... 92
Model D3300:....................................................................................................................... 93
Insulated 2-Rod Hanger..................................................................................................................... 94-99
Model D4000:.................................................................................................................... 94

2
Pipe
Shields
Inc.
95
Model
D5000: .................................................................................................................................... 96
Model
D6000: .................................................................................................................................... 97
Model
D6100: .................................................................................................................................... 98
Model
D6200: .................................................................................................................................... 99
Model
D6300: ....................................................................................................................................
100-109
Section E: Insulated Pipe Support - Pipe Riser Clamp 100-101
Introduction/Index....................................................................................................................................................102-105
Insulated Pipe Riser Clamps for Downlward Loads...................................................................... 102
Model E1000, Model E1010, Model E1020, Model E1030.................................................... 103
Model E1100, Model E1110, Model E1120, Model E1130.................................................... 104
Model E1200, Model E1210, Model E1220, Model E1230.................................................... 105
Model E1300, Model E1310, Model E1320, Model E1330....................................................106-109
Insulated Pipe Riser Clamps for Upward or Downward Loads.................................................... 106
Model E2000, Model E2010, Model E2020, Model E2030. .................................................. 107
Model E2100, Model E2110, Model E2120, Model E2130..................................................... 108
Model E2200, Model E2210, Model E2220, Model E2230.................................................... 109
Model E2300, Model E2310, Model E2320, Model E2330 ...................................................
110-128
Section G: Pipe Clamps, Pipe Guide Straps, Pipe Guide U-Bolts 110-106
Introduction/Index............................................................................................................................................. 112
Model G1000: Pipe Shield Clamp....................................................................................................... 113
Model G1200: Pipe ClampTubing Clamp - Neoprene Sleeved............................................................... 114
Model G2000: Pipe Clamp Shield Guide Strap...................................................................................... 115
Model G2200: Pipe ClampTubing Clamp - Neoprene Sleeved............................................................... 116
Model G3000: Pipe Guide U-Bolt Shield Guide U-Bolt............................................................................
119-125
Completed Projects...................................................................................................................................................
127-128
FrequentlyAsked Questions........................................................................................................................................

3
Pipe
Shields
Inc.

1. 2.

3.
1. Pre-insulated pipe shoes made with carbon steel.

2. High temperature support with an outside diameter of 58 and are


capable of handling temperatures up to 1500F. They are fabricated
from a combination of carbon steel for the top and stainless steel for
the bottom.

3. 60 hot shoes for a chemical plant in Texas. These shoes are used
in processes where it is imperative that thermal energy is not lost
through the pipe support.
4. 4. Hot shoes fabricated from steel carbon with a red oxide and
calcium sillicate insulation.

4
Pipe
Shields
Inc.

GENERAL INTRODUCTION

P ipe Shields, Inc. pioneered the first insulated pipe support in 1971 for use on HVAC and plumbing lines.
These supports were designed because fiberglass pipe insulation is not strong enough to carry the load
at the point of support without crushing. The various methods contractors employed to compensate for this
weakness were inconsistent, non-uniform and labor intensive, often resulting in damage to the vapor barrier
and/or pipe insulation. The insulated pipe support filled the need for an energy efficient, economical and
practical support.

Pipe Shields, Inc. has developed a large and growing family of insulated pipe supports, using its standard
concept of incorporating materials strong enough to carry the load while insulating the pipe at the same
time. No welding to the pipe is required (except for insulated positive anchors and insulated pipe riser
clamps) and no direct metal-to-metal heat path exists. Insulated pipe supports meet an assortment of
requirements, including:

Pipe supported on: Anchors


o Flat Surface Pipe Hangers
o Pipe Roll Pipe Riser Clamps
o Clevis Hanger Thermal Growth Small or Large
Gas Maximum Support Spacing
Steam Light, Medium or Heavy Loads
Super Heated Steam Ultra-High Temperatures
Chilled Water Minimum Overhead Clearance
Styrene Minimum Horizontal Clearance
Guide Supports Minimum Field Labor
Sliding Supports Minimum Friction Loads
Restrained Supports Easy Installation

Other products designed, manufactured and supplied not included in this catalog are:

1. Seismic pipe restraints


2. Heat-traced pre-insulated pipe supports
3. Pipe supports used in computer chip, styrene plants and oil refineries
4. Pipe supports for solar energy projects to accommodate expansion travels in excess of
5- 0

Our highly sophisticated products are a direct result of years of research, engineering and
design to develop cost efficient products for the power, petrochemical, chemical and commercial
markets. We work closely with engineering firms and in-house engineering departments of
owners to provide working solutions to meet their engineering challenges. We have established
proprietary specifications that have now become an industry standard used by owners, engineers
and contractors throughout the world markets.

If you have a pipe support need not met by any of the items described in this catalog, please
contact us at
707-447-5014 or 1-800-538-7007.

5
Pipe
Shields
Inc.

TEMPERATURE, DIMENSIONAL AND MATERIAL VARIANCES


Temperature Ranges
Pipe Shields, Inc. strongly recommends the following temperature ranges for our standard insulation
material:

Material Temperature

Calcium Silicate +40oF to + 1200oF


Note: Can be increased to 1800F using higher density Calcium Silicate

Polyurethane -275oF to +275oF

Permali/Insulam -328oF to +248oF

Foamglas -450oF to +900oF

Material Variances
Our standard paint finish is SP150 red oxide primer which meets full EPA and California safety regulations.
Other paint finishes are available upon request which include:

Hot dipped galvanized


Inorganic zinc (CZ11HS)
Dupont (Corlar) 25P epoxy
SP145 grey oxide
Carbothane 134HG
Carbozinc 859

Slide plate material and other field welded material are coated with deoxaluminate (silver coating).

Model Designation for Alternate Insulation Materials


Polyurethane Add U after Catalog Model Number Example: B1000U
Urethane/Foamglas Add UF after Catalog Model Number Example: B1000UF
Calcium Silicate/Foamglas Add CF after Catalog Model Number Example: B1000CF

6 www.pipeshields.com/materials
Pipe
Shields
Inc.

MATERIALS
Calcium Silicate
Calcium Silicate often serves as the insulation for pipe supports in high temperature applications. Calcium
Silicate is also known as Thermo-12/Gold. It is an insulating material composed of hydrous calcium silicate
which, because of its light weight, low thermal conductivity and exceptional structural strength is ideal for
the insulation of high temperature piping and equipment. Sometimes it is also used as block insulation. The
pipe insulation comes in a complete selection of sizes. Block styles are available for application to various
flat and curved surface areas.

Some of Calcium Silicates major advantages and applications are given below:

Major Advantages:
Temperature Range to 1200F
Exceptional Strength
Low Thermal Conductivity
Easy Application: available sizes and shapes reduce the number of required joints and make
Calcium Silicate easy to work with.
Energy Savings: low thermal conductivity provides significant energy savings.
Adaptable: Calcium Silicate can also be used on a various shapes and sizes of surfaces.
Fire Resistant
Low Chloride Content: low corrosivity
Asbestos-Free

Major Applications:
Hot Line Pipe Supports in Power Generation and Process Industries.
Indoor and Outdoor Piping and Equipment.
Block Insulation - insulation of various flat and curved surface areas.

Polyurethane
Polyurethane is different from most plastic materials in that it can be tailored to meet various load
requirements of varying applications. Polyurethane foams are produced by reacting an equal ratio
of di- or polyisocyanurates with polyols, in the presence of water, which acts as the blowing agent.
Polyisocyanurates are formed when a higher ratio of di- or polyisocyanate are mixed with the polyol. All
rigid foams made from polyisocyanrate systems have some form of polyurethane in them and can be
called polyurethane foam. The physical properties differ very little at high densities. Polyisocyanurate
foams are used in applications where dimensional stability over 200oF is
required. However, for cryogenic applications, where your pipeline insulation
is not exposed to high temperatures, PUF is an acceptable substitution.

A common method used to obtain a change in load capacity is a change in


density. At Pipe Shields, we offer 10 lbs. / ft3, 14 lbs. / ft3, and 20 lbs. / ft3
densities.

Density varies when the amount of blowing agent (water content) changes.
The density of polyurethane decreases with increase in water content (See
Fig. 1). This relationship can be shown as follows:

W = 3.706 / D1.126
Where: W = % of water content
D = Density of foam (lbs./ft3.)

7
Pipe
Shields
Inc.

In addition to density, the strength of a rigid urethane foam is also influenced by many factors such as
catalyst, surfactant, type of mixing, the type of foaming system: base polyol and isosyanate, and the
influence of each of these on the foam cell structure.

Rigid urethane foams generally have an elastic region in which stress is nearly proportional to strain. They
do not exactly follow Hookes Law (stress is proportional to strain) because the curve is very slightly S
shaped. Fig. 2 shows this in detail.

Polyurethane is anisotropic, or polyurethane is stronger in the direction of foam rise. At Piping Technology
and Products, the anisotropic character or directional properties of our polyurethane is reduced by
overloading the mold used to form the polyurethane. By overloading the mold, we can control the cell
structure and provide uniform physical properties. A relationship between compressive strength and the
density of the foam is given in Fig. 3.

Polyurethane is a thermosetting
material; however, it does soften
slightly with increased temperature
and hardens somewhat at very low
temperatures. Softening at high temperatures
affects the polyurethane in two ways:
(a) loss of strength properties and (b)
change in foam dimensions (particularly low-
density foams). Low temperatures generally
have very little effect on polyurethane
properties other than to make them a little
harder and more brittle. See Fig. 4 for these
effects.

Rigid polyurethane foams have a relatively large amount of cross-linking as the foam expands. Our
suppliers of the raw chemicals control the degree of cross-linking by functionality (higher functionality
produces more cross-links) and molecular weight of the components in the blend. The rigid cells provide the
poured foam with strength and the interior space provides low thermal conductivity. Water is used as the
blowing agent for foam in this 10 to 40 lb. density range.

The relationship between temperature,


thermal conductivity and the density of
polyurethane foam is shown in Fig. 5.

The relationships of foams density with


its Elastic Modulus in Compression,
Tensile Strength, Elastic Modulus in
Tension, and Shear Strength are given
in Figs. 6 through 9 respectively. Please
see the following for the respective
curves.

Pipe Shields has a complete


manufacturing facility for production
of polyurethane required for pipe supports. We invite our customers to visit our facility and observe the
fabrication of insulated pipe supports of all types.

8
Pipe
Shields
Inc.

DENSITY COMPRESSIVE FLEXURAL TENSILE MODULUS OF CLOSED TEMPERA- K-FAC- THERMAL SHEAR DENSITY WATER
STRENGTH STRENGTH TRENGTH ELASTICITY CELL TURE (F) TOR CONDUCTIV- (flatwise (lb/in^3) ABSORP-
(psi) (flatwise with (with grain) (psi) CONTENT CONTINUOUS ITY (btu/hr m^2 1/8" thk. TION (%)
grain) (psi) (psi) (%) OPERATION F) Psi)

PUF 200 400 300 6,000.00 95 -300 0.08 0.16 180 0.1157 0.22
(10pcf)
PUF 300 600 500 11,000.00 95 -300 0.12 0.2 200 0.1736 0.18
(14pcf)
PUF 500 1,100.00 600 20,000.00 95 -300 0.14 0.25 400 0.2893 0.13
(20pcf)

Foamglas
Foamglas insulation is a lightweight, rigid insulation composed of millions of completely sealed glass
cells. Each cell serves as an insulating agent. Foamglas is widely used in the cryogenic and hot line
pipe supports and is fabricated in various ranges of shapes, thicknesses and sizes to meet the particular
requirements of an application.

One unique advantage that Foamglas has is its very low moisture absorption. Since, Foamglas insulation
is full of closed glass cells, it resists moisture in both liquid and vapor form. This guarantees the long
term performance of the insulation. Foamglas insulations resistance to moisture ensures that, properly
installed, it retains its original thermal efficiency.

The major advantages and applications of Foamglas insulation are listed below. For details about the
physical and mechanical properties of the Foamglas material, please refer to the table.

Major Advantages:
Constant Insulating Efficiency
Fire Protection
Corrosion Resistance
Long Term Dimensional Stability
Physical Strength
Major Applications:
Cryogenic and Hot Line Pipe Supports
Cryogenic Tanks and Vessels
Chilled and Hot Water Service Lines
Overfit and Revitalize the Old Insulation
Composite Insulation Systems for Special Conditions

9
Pipe
Shields
Inc.

Density Foamglas (8 pcf)


Compressive Strength (psi) 100.00
Flexural Strength (flat wise with grain) (psi) 80.00
Tensile Strength (with grain)(psi) N/A
Modulus of Elasticity (psi) 1.4 10^5
Closed Cell Content (%) N/A
Temperature (F)-Continuous Operation 500 max.
K-Factor N/A
Thermal Conductivity (btu-in/HR-ft^2-F) 0.32
Shear (flat wise) (1/8" thk.) (psi) N/A
Density (lb/in^3) 0.0046
Water Absorption (%) 0.2%

Permali or Insulam or Laminated Beechwood


Permali or Insulam or Laminated Beechwood is an insulating material used in applications which
require high tensile and compressive strength (see table below). In addition, due to its exceptional
resistance to moisture, it serves as a suitable insulator where the support (flare lines & dummy legs)
is exposed to harsh environment elements. Permali or Insulam is a phenolic laminated (densified,
impregnated wood) product made from carefully selected thin beechwood veneers. These wood layers
are impregnated under vacuum conditions with a special synthetic resin and then densified through the
application of heat and pressure. The result is a homogenous material that combines the great strength
and toughness of wood fibers with the excellent stability and dielectric properties of the most advanced
thermosetting. The phenolic laminated block material is furnished with cross-directional fibers as shown
in the figure.

NOTE: Cross laminated.


For components in compression or for
parts stressed in more than one direction.
Sizes to suit most applications.

Density Permali (82 pcf)


Compressive Strength (psi) 30,000.00
Flectual Strength (flatwise with grain) (psi) 15,000.00
Tensile Strength (with grain)(psi) 15,000.00
Modulus of Elasticity (psi) 2.0 x 10^6
Closed Cell Content (%) N/A
Temperature(F)-Continuous Operation 221.00
K-Factor N/A
Thermal Conductivity (btu/hr m^2 F) 0.0018
Shear (flatwise) (1/8 thick) (psi) 7200.00
Density (lb/in^3) 0.0469
Water Absorption (%) 0.75

10
Pipe
Shields
Inc.

Foamglas Technical Information


Foamglas insulation is a lightweight, rigid insulation composed of millions of completely sealed glass
cells. Each cell serves as an insulating agent. Foamglas is widely used in the cryogenic and hot line
pipe supports and is fabricated in various ranges of shapes, thicknesses and sizes to meet the particu-
lar requirements of an application.

One unique advantage that Foamglas has is its very low moisture absorption. Since, Foamglas in-
sulation is full of closed glass cells, it resists moisture in both liquid and vapor form. This guarantees the
long term performance of the insulation. Foamglas insulations resistance to moisture ensures that,
properly installed, it retains its original thermal efficiency.

The major advantages and applications of Foamglas insulation are listed below. For details about the
physical and mechanical properties of the Foamglas material, please refer to the table.

Major Advantages:
Constant Insulating Efficiency
Fire Protection
Corrosion Resistance
Long Term Dimensional Stability
Physical Strength

Major Applications:
Cryogenic and Hot Line Pipe Supports
Cryogenic Tanks and Vessels
Chilled and Hot Water Service Lines
Overfit and Revitalize the Old Insulation
Composite Insulation Systems for Special ConditionsFoamglas Technical Information

Foamglas insulation is a lightweight, rigid insulation composed of millions of completely sealed glass
cells. Each cell serves as an insulating agent. Foamglas is widely used in the cryogenic and hot line
pipe supports and is fabricated in various ranges of shapes, thicknesses and sizes to meet the
particular requirements of an application.

Density Foam Glass(8 pcf)


Compressive Strength (psi) 400.00
Flexural Strength (flat wise with grain) (psi) 80.00
Tensile Strength (with grain)(psi) N/A
Modulus of Elasticity (psi) 1.3 10^6
Closed Cell Content (%) N/A
Temperature (F)-Continuous Operation 500 max.
K-Factor N/A
Thermal Conductivity
0.7000
(btu/hr m^2 F)
Shear (flat wise) (1/8 thk.) (psi) N/A
Density (lb/in^3) 0.0046
Water Absorption (%) 0.070

11
Pipe
Shields
Inc. Insulated Pipe Support Selection Guide
USE OF THE INSULATED PIPE SUPPORT SELECTION GUIDE

The tables on the following pages will assist you in making a selection of the proper and most economic
insulated pipe support for your application.

These Selection Guide Tables are organized by:

1. SERVICE
A. Water
B. Steam, Gas, or Air

2. APPLICATION
A. Pipe supported from below
a. On flat surface
b. On pipe roll
B. Pipe supported from above
a. In clevis or 2-bolt hanger

Service Configuration Spacing Guide


Water Support from Above Clevis or 2-bolt clamp View Selection Table 3

Support from Below On Flat Surface View SelectionTable 1

On Pipe Roll View Selection Table 5

Steam, Gas, or Air Support from Above Clevis or 2-Bolt Clamp View Selection Table 4

Support from Below On Flat Surface View Selection Table 2

On Pipe Roll View Selection Table 6

The product data sheets describing each model refer to other models in the catalog with features such as
load rating, axial or lateral travel, or restraint, etc. which you may have an interest.

If you have a pipe support need not met by any of the items described in this catalog, please contact us at
707-447-5014 or 1-800-538-7007.

12 www.pipeshields.com/selectionguide
Pipe
Shields
Insulated Pipe Support Selection Guide Inc.

TABLE 1
SERVICE: WATER

APPLICATION: PIPE SUPPORTED FROM ABOVE OR BELOW

Pipe Shields Model:


Commercial Light Industrial Heavy Industrial Rated for Combined
w/ Load Distribution Plate on Slide Pad Lateral and Vertical Loads
Pipe Size For
(inches) reference:
ASME
B31.1

B1000 B1100 B1200 B1300


B2000 B2100 B2200 B2300
B3000 B3100 B3200 B3300
B4000 B4100 B4200 B4300
A1000 A3000 A5000 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300
A2000 A4000 A6000 A7000 A7200 A7400 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300
maximum hanger support spacing (feet)

1/2 7 11 12
3/4 7 12 13
1 7 13 14
1 1/2 9 15 16
2 10 15 17
2 1/2 11 12 14 16 21
3 12 12 13 17 20 35 45 55 32 45 55
3 1/2 13 12 13 16 19 35 45 55 33 45 55
4 14 13 14 17 19 35 45 55 35 45 55
5 16 12 14 16 17 35 45 55 33 45 55
6 17 10 12 13 14 26 34 45 55 30 45 55
8 19 7 8 11 12 21 29 45 55 26 45 55
10 22 6 6 7 10 18 25 24 45 55 21 42 55
12 23 8 14 20 31 20 40 55 65 17 36 54 64
14 25 8 13 22 31 20 40 55 65 18 35 53 65
16 27 12 21 28 19 37 55 65 16 34 50 65
18 28 10 19 26 17 34 52 65 15 30 46 61
20 30 9 17 23 15 31 46 62 14 27 41 55
24 32 14 18 12 24 36 48 10 21 32 43
60 33 10 12 11 21 32 43 9 19 29 39
63 35 9 18 28 37 8 16 24 33
42 36 8 16 24 32 7 14 21 28

Note: The maximum hanger spacing shown in Table 1 are derived from load ratings (see Product Data Sheets) of Pipe Shields, Inc.
models, assuming weight of standard pipe, water, and 2 insulation. The customer should be guided by the hanger spacings allowed
by the applicable code or the project engineers specifications before making a selection. Refer to the appropriate Product Data
Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.

Example: Given: Pipe Diameter: 8 standard weight


Service: Water
Support Spacing: 20 - 0
Determine: Insulated pipe support model number
Method: In table 1, for 8 pipe size, find the model(s) rated for handling 20- 0 or greater support spacing. In
this case, Model A7200 is selected since it is capable of handling 21-0 support spacing. The Index Sheets to Sections A & B
indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In
this example, if the support is required to handle +/-4 1/2 of axial travel, Model B2000 would be selected (Section B Index &
Product Data Sheet B2000).

www.pipeshields.com/table1 13
Pipe
Shields
Inc. Insulated Pipe Support Selection Guide
TABLE 2
SERVICE: STEAM, GAS OR AIR

APPLICATION: PIPE SUPPORTED FROM ABOVE OR BELOW

Pipe Shields Model:


Commercial Light Industrial Heavy Industrial Rated for Combined
w/ Load Distribution Plate on Slide Pad Lateral and Vertical Loads
Pipe Size For
(inches) reference:
ASME
B31.1
B1000 B1100 B1200 B1300
B2000 B2100 B2200 B2300
B3000 B3100 B3200 B3300
B4000 B4100 B4200 B4300
A1000 A3000 A5000 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300
A2000 A4000 A6000 A7000 A7200 A7400 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300
maximum hanger support spacing (feet)

1/2 8 11 12
3/4 9 12 13
1 9 14 15
1 1/2 12 17 19
2 13 18 20
2 1/2 14 15 16 20 25
3 15 15 17 21 26 40 50 60 40 50 60
3 16 16 18 21 25 40 50 60 40 50 60
1/2 17 17 19 23 26 40 50 60 40 50 60
4 19 17 20 22 25 40 50 60 40 50 60
5
6 21 16 18 20 22 40 40 50 60 40 50 60
8 24 12 14 17 19 35 40 50 60 40 50 60
10 26 10 10 13 17 31 40 40 50 60 36 50 60
12 30 9 9 15 26 37 45 36 50 60 70 32 50 60 70
14 32 8 9 15 25 40 45 38 50 60 70 34 50 60 70
16 35 8 8 14 24 40 45 39 50 60 70 25 50 60 70
18 37 14 24 40 45 38 50 60 70 34 50 60 70
20 39 14 22 40 45 36 50 60 70 32 50 60 70
24 42 11 20 36 45 32 50 60 70 28 50 60 70
60 44 10 18 32 39 33 50 60 70 30 50 60 70
63 48 9 15 27 33 50 60 70 29 50 60 70
42 50 12 23 31 50 60 70 28 50 60 70

Note: The maximum hanger spacing shown in Table 2 are derived from load ratings (see Product Data Sheets) of Pipe Shields, Inc.
models, assuming weight of standard pipe, and 2 insulation. The customer should be guided by the hanger spacings allowed by the
applicable code or the project engineers specifications before making a selection. Refer to the appropriate Product Data Sheets for
additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.

Example: Given: Pipe Diameter: 8 standard weight


Service: Steam
Support Spacing: 30 - 0
Determine: Insulated pipe support model number
Method: In table 2, for 8 pipe size, find the model(s) rated for handling 30- 0 or greater support spacing. In
this case, Model A7200 is selected since it is capable of handling 35-0 support spacing. The Index Sheets to Sections A & B
indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In
this example, if the support is required to handle +/-4 1/2 of axial travel, Model B2000 would be selected (Section B Index &
Product Data Sheet B2000).

14 www.pipeshields.com/table2
Pipe
Shields
Insulated Pipe Support Selection Guide Inc.

TABLE 3
SERVICE: WATER

APPLICATION: PIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER

Pipe Shields Model:


Clevis Hanger 2-Bolt Hanger

Pipe Size For


(inches) reference:
ASME
B31.1
D1000
D2000
A1000 A3000 D4000 D3000 D3100 D3200 D3300
A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300
maximum hanger support spacing (feet)
1/2 7 11 12 13
3/4 7 12 13 15
1 7 14 15 17 19
1 1/2 9 16 18 19 22
2 10 17 18 21 29
2 1/2 11 16 18 21 24
3 12 17 18 20 25
3 1/2 13 16 17 19 22
4 14 16 18 19 22
5 16 15 16 19 21 40
6 17 14 15 16 21 40
8 19 13 13 15 22 32
10 22 12 13 14 24 28
12 23 11 12 13 22 26
14 25 11 12 13 20 23
16 27 10 11 12 21 26 40
18 28 9 10 11 18 22 33
20 30 9 9 10 16 18 28 37
24 32 8 9 15 19 29 38
30 33 11 13 19 26

Note: The maximum hanger spacing shown in Table 3 are derived from load ratings (see Product Data Sheets) of Pipe Shields, Inc.
models, assuming weight of standard pipe, water, and 2 insulation. The customer should be guided by the hanger spacings allowed
by the applicable code or the project engineers specifications before making a selection. Refer to the appropriate Product Data
Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.

Example: Given: Pipe Diameter: 8 standard weight


Service: Water
Support Spacing: 20 - 0
Determine: Insulated pipe support model number
Method: In table 3, for 8 pipe size, find the model(s) rated for handling 20- 0 or greater support spacing. In
this case, Model D3000 is selected since it is capable of handling 22-0 support spacing. The Index Sheets to Sections A & D
indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In
this example, if the clearance is above the support limited, Model D6000 might be selected (Section D Index & Product Data
Sheet D6000).

www.pipeshields.com/table3 15
Pipe
Shields
Inc. Insulated Pipe Support Selection Guide
TABLE 4
SERVICE: STEAM, GAS OR AIR

APPLICATION: PIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER

Pipe Shields Model:


Clevis Hanger 2-Bolt Hanger
For
Pipe Size reference:
(inches) ASME
B31.1

D1000
D2000
A1000 A3000 D4000 D3000 D3100 D3200 D3300
A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300
maximum hanger support spacing (feet)
1/2 8 11 12 13
3/4 9 12 13 15
1 9 15 16 19 21
1 1/2 12 19 20 22 26
2 13 20 22 25 36
2 1/2 14 20 22 25 29
3 15 21 24 26 32
3 1/2 16 21 23 25 29
4 17 23 24 26 31
5 19 22 24 28 30 55
6 21 22 23 24 32 55
8 24 21 22 25 25 52
10 26 20 22 24 40 45
12 30 20 21 24 40 45
14 32 21 23 25 38 55 60
16 35 21 22 25 40 55 60
18 37 21 22 25 40 49 60
20 39 21 22 25 38 44 60 65
24 42 20 21 24 40 50 60 65
30 44 34 51 60 65

Note: The maximum hanger spacing shown in Table 4 are derived from load ratings (see Product Data Sheets) of Pipe Shields, Inc.
models, assuming weight of standard pipe, and 2 insulation. The customer should be guided by the hanger spacings allowed by the
applicable code or the project engineers specifications before making a selection. Refer to the appropriate Product Data Sheets for
additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.

Example: Given: Pipe Diameter: 8 standard weight


Service: Steam
Support Spacing: 24 - 0
Determine: Insulated pipe support model number
Method: In table 4, for 8 pipe size, find the model(s) rated for handling 24- 0 or greater support spacing. In
this case, Model A9000 is selected since it is capable of handling 25-0 support spacing. The Index Sheets to Sections A & D
indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In
this example, if the clearance is above the support limited, Model D6000 might be selected (Section D Index & Product Data
Sheet D6000).

16 www.pipeshields.com/table4
Pipe
Shields
Insulated Pipe Support Selection Guide Inc.

TABLE 5
SERVICE: WATER

APPLICATION: PIPE SUPPORTED FROM BELOW ON PIPE ROLL OR ABOVE

Pipe Shields Model:


Commerical Light Industrial w/ Load Distribution Plate

Pipe Size For refer-


(inches) ence: ASME
B31.1

A3000 A5000
A4000 A6000 A8000 A8200 A8400
maximum hanger support spacing (feet)
1/2 7 12
3/4 7 13
1 7 13
1 1/2 9 15
2 10 15
2 1/2 11 12 15 18
3 12 12 15 17
3 1/2 13 12 12 16
4 14 13 15 16
5 16 14 15
6 17 12 13 24
8 19 9 10 19
10 22 10 16 22
12 23 12 23 31
14 25 11 21 28
16 27 10 19 25
18 28 9 17 23
20 30 8 15 20
24 32 12 16
30 33 9 12

Note: The maximum hanger spacing shown in Table 5 are derived from load ratings (see Product Data Sheets) of Pipe Shields, Inc.
models, assuming weight of standard pipe, water, and 2 insulation. The customer should be guided by the hanger spacings allowed
by the applicable code or the project engineers specifications before making a selection. Refer to the appropriate Product Data
Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.

Example: Given: Pipe Diameter: 8 standard weight


Service: Water
Support Spacing: 18 - 0
Determine: Insulated pipe support model number
Method: In table 5, for 8 pipe size, find the model(s) rated for handling 18- 0 or greater support spacing. In
this case, Model A8200 is selected since it is capable of handling 19-0 support spacing. The Index Sheet to Section A indicates
some of the differences between models. Check Product Data Sheet for description before making a final selection. If greater
support spacings are desired, see Section B (Base Mounted Supports).

www.pipeshields.com/table5 17
Pipe
Shields
Inc. Insulated Pipe Support Selection Guide
TABLE 6
SERVICE: STEAM, GAS OR AIR

APPLICATION: PIPE SUPPORTED FROM BELOW ON PIPE ROLL OR ABOVE

Pipe Shields Model:


Commerical Light Industrial w/ Load Distribution Plate

Pipe Size For refer-


(inches) ence: ASME
B31.1

A3000 A5000
A4000 A6000 A8000 A8200 A8400
maximum hanger support spacing (feet)
1/2 8 12
3/4 9 13
1 9 14
1 1/2 12 17
2 13 18
2 1/2 14 15 18 22
3 15 15 19 21
3 1/2 16 16 19 21
4 17 17 20 23
5 19 20 22
6 21 18 20 36
8 24 15 17 31
10 26 11 17 27 38
12 30 13 23 40 50
14 32 13 22 40 50
16 35 13 22 39 50
18 37 12 21 38 50
20 39 12 20 36 49
24 42 11 18 33 44
30 44 9 16 29 39
36 48 8 13 24
42 50 11 20

Note: The maximum hanger spacing shown in Table 6 are derived from load ratings (see Product Data Sheets) of Pipe Shields, Inc.
models, assuming weight of standard pipe, and 2 insulation. The customer should be guided by the hanger spacings allowed by the
applicable code or the project engineers specifications before making a selection. Refer to the appropriate Product Data Sheets for
additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.

Example: Given: Pipe Diameter: 8 standard weight


Service: Water
Support Spacing: 25 - 0
Determine: Insulated pipe support model number
Method: In table 6, for 8 pipe size, find the model (s) rated for handling 25-0 or greater support spacing. In
this case, Model A8200 is selected since it is capable of handling 25-0 or 31-0 support spacing. The Index Sheet to Section A
indicates some of the differences between models. Check Product Data Sheet for description before making a final selection. If
greater support spacings are desired, see Section B (Base Mounted Supports).

18 www.pipeshields.com/table6
Pipe
Shields
Inc.

19
Pipe
Shields
Inc. Introduction: Section A

INTRODUCTION

SECTION A

PRE-INSULATED PIPE SUPPORTS

APPLICATION Commercial and Light Industrial

Most commercial applications are well served by Models A1000 and A2000, which are recommended for
use on common 10-0 hanger space for small bore pipe sizes (see Selection Guide). However, should the
need arise, because of increased hanger spacing or the manner in which the insulated support is mounted,
heavier duty supports are available.

As is readily seen in the Section Index on the following page, some models are meant for installation
only in a clevis hanger, on a flat surface, or on a pipe roll. Other models may be installed in any two or
all three mounting methods.

The load ratings (see Product Data Sheets) reflect consideration for the manner in which each of these
models will be mounted.

Note: In the A7000 through A7400 Series and the A8000 through A8400 Series, the higher the
model number, the higher the load rating.

We are committed to providing the most economical and appropriate insulated pipe support to satisfy the
requirements of the piping system.

If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
707-447-5014 or 1-800-538-7007.

Please acquaint yourself with the selection guide at the front of this catalog and the section index on
the page following this introduction, for assistance in determining the most appropriate support for your
application.

20
Pipe
Shields
Section A Index Inc.
PRE-INSULATED PIPE SUPPORTS

COMMERCIAL AND LIGHT INDUSTRIAL


PIPE PRIMARY INSTALLED ON
A1000, A3000, A9000 SIZE APPLICATION FLAT CLEVIS PIPE
MODEL RANGE HOT COLD SURFACE HANGER ROLL DUTY

A1000 1/2 - 24 X X X LIGHT


A2000 1/2 - 24 X X X LIGHT
A3000 1/2 - 24 X X X MEDIUM
A3000 1/2 - 4 X X MEDIUM
A5000, A7000 - A8400
A4000 1/2 - 24 X X X MEDIUM
A4000 1/2 - 4 X X MEDIUM

A5000 2 1/2 - 42 X X X MED/HEAVY


A6000 2 1/2 - 42 X X X MED/HEAVY
A7000 2 1/2 - 42 X X X HEAVY
A7200 6 - 42 X X X HEAVIER
A7400 10 - 30 X X X HEAVIEST
A8000 2 1/2 - 42 X X X HEAVY
A1000, A3000, A9000
A8200 6 - 42 X X X HEAVIER
A8400 10 - 30 X X X HEAVIEST

A9000 1/2 - 24 X X X HEAVY

TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 2 IPS
3. Insulation Thickness 2-1/2
4. Model Number A1000
EXAMPLE:(20) 2 x 2-1/2 A1000

www.pipeshields.com/a-series 21
A1000, A3000, A9000
Pipe
Shields
Inc.A1000, A3000, A9000 Model A1000 Insulated Pipe Support Regular Duty

MAXIMUM LOAD
RATING (LBS)
On Flat In Clevis
Pipe
Surface Hanger
Size
(a) (c) (b) (c)
A
1/2 35 40
INCHES
3/4 40 45
1 60 65
1 1/4 70 80
Oper. Mult. 1 1/2 100 110
Temp. Factor 2 125 140
o
F "F" 2 1/2 150 200
500 0.90 3 180 250
750 0.75 3 1/2 225 300
1000 0.50 4 270 350
Hardware sold separately. 1200 0.30 5 350 450
Note: For higher load ratings, see A3000, A9000. TABLE III 6 400 550
8 450 750
The load ratings represent average values obtained in accordance with accepted 10 500 1000
methods and are subject to normal manufacturing variations. Dimensions and ratings 12 550 1200
are subject to change without notice. 14 575 1400
16 600 1600
a) To develop maximum load rating, width of support surface should be at 18 625 1800
least 1/2 of dimension A in Table II. 20 675 2000
24 750 2300
b) To develop maximum load rating, use band, ring or clevis hanger with TABLE I
manufacturers load rating equal to or greater than values shown in Table I.
Contact factory for other dimensions,
c) To obtain load ratings for operating temperatures of 500 F and higher, temperatures, and loads.
Available in all insulation thicknesses.
multiply load rating by factor F in Table III.

Iron Insulation Thickness Copper


Pipe 1/2 3/4 1 1 1/2 2 2 1/2 3 3 1/2 4 Tubing
Size A B A B A B A B A B A B A B A B A B Size O.D.
1/2 - 1 1/2 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 5/8 - 1 5/8
2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 2 1/8
2 1/2 - 4 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 2 5/8 - 4 1/8
5 6 20 6 20 6 20 6 20 9 20 9 20 9 20 5 1/8
6-7 6 20 6 20 6 20 6 20 9 16 9 16 9 16 6 1/8
8 - 10 9 16 9 16 9 16 9 16 9 16 9 16 8 1/8 -10 1/8
12 - 18 12 16 12 16 12 16 12 16 12 16 12 16 12 1/8
20 - 24 18 16 18 16 18 16 18 16 18 16 18 16
TABLE II "B" = gauge of sheet metal jacket

Application: Features: Material Data:

Model A1000 is designed for use on: Compact A1000: Applicable PSI spec. doc.: No. 205
Hot water Steam
Easy installation
Cold water Air Standard Insulation: Calcium silicate
Eliminates welding to pipe
Chilled water Gas asbestos-free, treated with water
Dual temperature Vacuum
Overlapping galvanized sheet metal jacket
repellant
Minimizes heat loss and/or condensation
Jackets: Galvanized steel ASTM A-653
Intended for installation on: Copper tubing sizes available
Other I.D.s and/or O.D.s available on request Glue: Industrial contact adhesive
Flat surfaces
Band, ring or clevis pipe hanger Clamps available (see G-series)
Clevis available (see PTP fig. 83) Formal submittal sheets available.
Temperature Range:
Standard: +40F to +1200F CalSil Insulation Performance test results on file:
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Available upon request.
Add U after the model number (i.e., A1000U)

22 www.pipeshields.com/a1000
A2000, A4000
Pipe
A1000, A3000, A9000 Regular Duty with Shields
Model A2000 Insulated Pipe Support Extended Insulation Inc.
1"
TYP
MAXIMUM LOAD
RATING (LBS)
On Flat In Clevis
Pipe
Surface Hanger
Size
(a) (c) (b) (c)
A
1/2 35 40
INCHES
3/4 40 45
1 60 65
1 1/4 70 80
Oper. Mult. 1 1/2 100 110
Temp. Factor 2 125 140
o
F "F" 2 1/2 150 200
500 0.90 3 180 250
750 0.75 3 1/2 225 300
1000 0.50 4 270 350
Hardware sold separately 1200 0.30 5 350 450
Note: For higher load ratings, see A4000, A9000. TABLE III 6 400 550
8 450 750
The load ratings represent average values obtained in accordance with accepted 10 500 1000
methods and are subject to normal manufacturing variations. Dimensions and ratings 12 550 1200
are subject to change without notice. 14 575 1400
16 600 1600
a) To develop maximum load rating, width of support surface should be at 18 625 1800
least 1/2 of dimension A in Table II. 20 675 2000
24 750 2300
b) To develop maximum load rating, use band, ring or clevis hanger with TABLE I
manufacturers load rating equal to or greater than values shown in Table I.
Contact factory for other dimensions, temperatures,
and loads.
c) To obtain load ratings for operating temperatures of 500F and higher, Available in all insulation thicknesses.
multiply load rating by factor F in Table III.

Iron Insulation Thickness Copper


Pipe 1/2 3/4 1 1 1/2 2 2 1/2 3 3 1/2 4 Tubing
Size A B A B A B A B A B A B A B A B A B Size O.D.
1/2 - 1 1/2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 5/8 - 15/8
2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 2 1/8
2 1/2 - 4 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 2 5/8 - 4 1/8
5 6 20 6 20 6 20 6 20 9 20 9 20 9 20 5 1/8
6-7 6 20 6 20 6 20 6 20 9 16 9 16 9 16 6 1/8
8 - 10 9 16 9 16 9 16 9 16 9 16 9 16 8 1/8 -10 1/8
12 - 18 12 16 12 16 12 16 12 16 12 16 12 16 12 1/8
20 - 24 18 16 18 16 18 16 18 16 18 16 18 16
TABLE II B = gauge of sheet metal jacket

Application: Features: Material Data:

Model A2000 is designed for use on: Compact


A2000: Applicable PSI spec. doc.: No. 205
Cold water Easy installation
Insulation: Calcium silicate asbestos-
Chilled water Eliminates welding to pipe
free, treated with water repellant
Overlapping galvanized sheet metal jacket
Jackets: Galvanized steel ASTM A-653
Intended for installation on: Minimizes heat loss and/or condensation
Glue: Industrial contact adhesive
Flat surfaces Calcium silicate insulation extends 1 beyond the
galvanized sheet metal jacket providing for an
Band, ring or clevis pipe hanger
easier vapor barrier joint with the pipe insulation Formal submittal sheets available.
Copper tubing sizes available
Temperature Range: Other I.D.s and/or O.D.s available on request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Clamps available (see G-series)
Cryogenic: -275F to +275F Urethane Insulation.
Clevis available (see PTP fig. 83)
Add U after the model number (i.e., A2000U)
Performance test results on file:
Available upon request.

www.pipeshields.com/a2000 23
PipeA1000, A3000, A9000
A1000, A3000, A9000

Shields Extra Heavy


Inc. Model A3000 Insulated Pipe Support Bottom Jacket

MAXIMUM LOAD
RATING (LBS)
On Flat On Pipe In Ring
Pipe Surface Roll or Clevis
Size Hanger
A (a) (d) (b) (d) (c) (d)
1/2 40 35 45
INCHES

3/4 45 40 50
Oper. Mult. 1 65 60 70
Temp. Factor 1 1/4 80 70 90
o
F "F"
1 1/2 110 100 120
500 0.90 2 140 125 155
750 0.75 2 1/2 165 150 220
1000 0.50 3 200 180 275
Hardware sold separately 1200 0.30 3 1/2 250 225 325
Note: For higher load ratings, see A5000, A9000. TABLE III 4 300 270 375
5 400 475
The load ratings represent average values obtained in accordance with accepted 6 450 575
methods and are subject to normal manufacturing variations. Dimensions and 8 500 800
ratings are subject to change without notice. 10 525 See 1100
12 575 1300
a) To develop maximum load rating, width of support surface should be at 14 600 1500
least 1/2 of dimension A in Table II. 16 625 A5000 1700
18 650 1900
b) Divide A in Table II by 6 to find maximum allowable travel on pipe roll 20 700 2100
(+/- from centered position). 24 775 2400
TABLE I
c) To develop maximum load rating, use band, ring or clevis hanger with
manufacturers load rating equal to or greater than values shown in Table I. Contact factory for other dimensions,
temperatures, and loads.
Available in all insulation thicknesses.
d) To obtain load ratings for operating temperatures of 500F and higher,
multiply load rating by factor F in Table III.

Iron Insulation Thickness Copper


Pipe 1/2 3/4 1 1 1/2 2 2 1/2 3 3 1/2 4 Tubing
Size A B A B A B A B A B A B A B A B A B Size O.D.
1/2 - 1 1/2 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 5/8 -1 5/8
2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 2 1/8
2 1/2 - 4 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 2 5/8 - 4 1/8
5 6 20 6 20 6 20 6 20 9 20 9 20 9 20 5 1/8
6-7 6 20 6 20 6 20 6 20 9 16 9 16 9 16 6 1/8
8 - 10 9 16 9 16 9 16 9 16 9 16 9 16 8 1/8 -10 1/8
12 - 18 12 16 12 16 12 16 12 16 12 16 12 16 12 1/8
20 - 24 18 16 18 16 18 16 18 16 18 16 18 16
TABLE II "B" = gauge of sheet metal jacket (bottom jac ket approx. 2 X ga. of top jacket)

Application: Features: Material Data:

Model A3000 is designed for use on: Compact


A3000: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Overlapping galvanized sheet metal jacket
Minimizes heat loss and/or condensation Jackets: Galvanized Steel ASTM A-653
Dual temperature Vacuum
Double thickness bottom jacket for added structural Glue: Industrial contact adhesive
Intended for installation on: strength and abrasive wear resistance
Flat surfaces Copper tubing sizes available
Formal submittal sheets available
Pipe rolls Other I.D.s and/or O.D.s available on request
Band, ring or clevis pipe hanger Clamps available (see G-series)
Clevis available (see PTP fig. 83)
Temperature Range:
Standard: +40F to +1200F CalSil Insulation Performance test results on file:
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Available upon request.
Add U after the model number (i.e., A3000U)

24 www.pipeshields.com/a3000
A1000, A3000, A9000 Pipe
A2000, A4000
Extra Heavy Bottom Jacket
Shields
Model A4000 Insulated Pipe Support with extended Insulation
Inc.
1"
TYP
MAXIMUM LOAD
RATING (LBS)
On Flat On Pipe In Ring
Pipe Surface Roll or Clevis
Size Hanger
A (a) (d) (b) (d) (c) (d)
1/2 40 35 45
INCHES

3/4 45 40 50
Oper. Mult. 1 65 60 70
Temp. Factor 1 1/4 80 70 90
o
F "F"
1 1/2 110 100 120
500 0.90 2 140 125 155
750 0.75 2 1/2 165 150 220
1000 0.50 3 200 180 275
Hardware sold separately 1200 0.30 3 1/2 250 225 325
Note: For higher load ratings, see A6000, A9000. TABLE III 4 300 270 375
5 400 475
The load ratings represent average values obtained in accordance with accepted 6 450 575
methods and are subject to normal manufacturing variations. Dimensions and 8 500 800
ratings are subject to change without notice. 10 525 See 1100
12 575 1300
a) To develop maximum load rating, width of support surface should be at 14 600 1500
least 1/2 of dimension A in Table II. 16 625 A6000 1700
18 650 1900
b) Divide A in Table II by 6 to find maximum allowable travel on pipe roll 20 700 2100
(+/- from centered position). 24 775 2400
TABLE I
c) To develop maximum load rating, use band, ring or clevis hanger with
manufacturers load rating equal to or greater than values shown in Table I. Contact factory for other dimensions,
temperatures, and loads.
Available in all insulation thicknesses.
d) To obtain load ratings for operating temperatures of 500F and higher,
multiply load rating by factor F in Table III.

Iron Insulation Thickness Copper


Pipe 1/2 3/4 1 1 1/2 2 2 1/2 3 3 1/2 4 Tubing
Size A B A B A B A B A B A B A B A B A B Size O.D.
1/2 - 1 1/2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 5/8-1 5/8
2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 2 1/8
2 1/2 - 4 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 2 5/8 - 4 1/8
5 6 20 6 20 6 20 6 20 9 20 9 20 9 20 5 1/8
6-7 6 20 6 20 6 20 6 20 9 16 9 16 9 16 6 1/8
8 - 10 9 16 9 16 9 16 9 16 9 16 9 16 8 1/8 -10 1/8
12 - 18 12 16 12 16 12 16 12 16 12 16 12 16 12 1/8
20 - 24 18 16 18 16 18 16 18 16 18 16 18 16
TABLE II "B" = gauge of sheet metal jacket (bottom jac ket approx. 2 X ga. of top jacket)

Application: Features: Material Data:


Compact
Model A4000 is designed for use on:
Easy installation A4000: Applicable PSI spec. doc.: No. 205
Cold water Eliminates welding to pipe
Overlapping galvanized sheet metal jacket Insulation: Calcium silicate asbestos-
Chilled water Double thickness bottom jacket for added structural free, treated with water repellant
strength and abrasive wear resistance
Minimizes heat loss and/or condensation Jackets: Galvanized steel ASTM A-653
Intended for installation on: Calcium silicate insulation extends 1 beyond the
Flat surfaces galvanized sheet metal jacket providing for an easier Glue: Industrial contact adhesive
vapor barrier joint with the pipe
Pipe rolls Copper tubing sizes available
Band, ring or clevis pipe hanger Other I.D.s and/or O.D.s available on request Formal submittal sheets available
Clamps available (see G-series)
Temperature Range: Clevis available (see PTP fig. 83)
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Performance test results on file:
Add U after the model number (i.e., A4000U) Available upon request.

www.pipeshields.com/a4000 25
Pipe
Shields
Inc. With load
Model A5000 Insulated Pipe Support distribution plate

MAXIMUM LOAD Max. Axial


RATING (LBS) Travel
Pipe (inches)
On Flat On Pipe on
Size
Surface Roll Pipe Roll
A B C
(a) (b) (b) +/-
2 1/2 200 180 9 6 1/4 2
A5000, A7000 - A8400 3 250 225 9 6 1/4 2
7000 - A8400 3 1/2 300 270 9 6 1/4 2
4 350 315 9 6 1/4 2
5 450 400 9 6 1/4 2
6 500 450 9 6 1/4 2
8 625 550 9 6 1/4 2
10 650 575 9 6 1/4 2
12 925 825 12 9 3/8 3
14 1000 900 12 9 3/8 3
C THK. 16 1100 975 12 9 1/2 3
18 1200 1075 12 9 1/2 3
B
20 1300 1150 12 9 1/2 3
A 24 1400 1250 12 9 3/4 3
INCHES
30 1500 1350 12 9 3/4 3
36 1500 1350 12 9 3/4 3
Oper. Mult. 42 1500 1350 12 9 3/4 3
Temp. Factor TABLE I
o
F "F"
500 0.90 Contact factory for other dimensions, temperatures, and loads. Available in
all insulation thicknesses.
750 0.75
1000 0.50
1200 0.30
TABLE II

Hardware sold separately


Note: For higher load ratings, see A7000

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subject to change without notice. Contact fac tory for current information.

a) To develop maximum load rating, width of support surf ace should be at least 1/2 of dimension B in Table I.

b) To obtain load ratings for operating temperatures of 500 oF and higher, multiply maximum load rating by factor F in Table II.

Application: Features: Material Data:

Model A5000 is designed for use on: Compact A5000: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-free,
Cold water Air Eliminates welding to pipe
treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Overlapping galvanized sheet metal jacket
Minimizes heat loss and/or condensation Load distribution Plate: Carbon steel
ASTM A-36
Intended for installation on: Load distribution plate integral with bottom
Flat surfaces jacket Coating: Primer coated or hot-dip galvanized
Other I.D.s and/or O.D.s available on request Other coatings available upon request
Pipe rolls
Glue: Industrial contact adhesive
Performance test results on file:
Temperature Range:
Standard: +40F to +1200F CalSil Insulation Available upon request
Note: Up to 1800F available upon request. Formal submittal sheets available
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A5000U)

26 www.pipeshields.com/a5000
Pipe
With load distribution plate
Shields
Model A6000 Insulated Pipe Support with exterior Insulation
Inc.

MAXIMUM LOAD Max. Axial


RATING (LBS) Travel
Pipe (inches)
On Flat On Pipe on
Size
Surface Roll Pipe Roll
A B C
(a) (b) (b) +/-
2 1/2 200 180 9 6 1/4 2
3 250 225 9 6 1/4 2
, A7000 A6000
- A8400 3 1/2 300 270 9 6 1/4 2
4 350 315 9 6 1/4 2
5 450 400 9 6 1/4 2
6 500 450 9 6 1/4 2
8 625 550 9 6 1/4 2
1"
TYP
10 650 575 9 6 1/4 2
12 925 825 12 9 3/8 3
14 1000 900 12 9 3/8 3
16 1100 975 12 9 1/2 3
C THK.
18 1200 1075 12 9 1/2 3
20 1300 1150 12 9 1/2 3
B
24 1400 1250 12 9 3/4 3
A
INCHES
30 1500 1350 12 9 3/4 3
36 1500 1350 12 9 3/4 3
Oper. Mult. 42 1500 1350 12 9 3/4 3
Temp. Factor TABLE I
o
F "F"
500 0.90 Contact factory for other dimensions, temperatures, and loads. Available in
all insulation thicknesses.
750 0.75
1000 0.50
1200 0.30
TABLE II

Hardware sold separately


Note: For higher load ratings, see A7000

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subject to change without notice. Contact fac tory for current information.

a) To develop maximum load rating, width of support surf ace should be at least 1/2 of dimension B in Table I.

b) To obtain load ratings for operating temperatures of 500 oF and higher, multiply maximum load rating by factor F in Table II.

Application: Features: Material Data:

Model A6000 is designed for use on: Compact A6000: Applicable PSI spec. doc.: No. 205
Cold water Easy installation
Insulation: Calcium Silicate asbestos-
Chilled water Eliminates welding to pipe
free, treated with water repellant
Copper tubing sizes available
Jackets: Galvanized Steel ASTM A-653
Intended for installation on: Overlapping galvanized sheet metal jacket
Flat surfaces Minimizes heat loss and/or condensation Load distribution Plate: Carbon steel
ASTM A-36
Pipe rolls Load distribution plate integral with bottom
jacket Coating : Primer coated or hot-dip galvanized
Calcium silicate insulation extends 1 beyond Other coatings available upon request
Temperature Range:
Standard: +40F to +1200F CalSil Insulation the galvanized sheet metal jacket providing
Glue: Industrial contact adhesive
Note: Up to 1800F available upon request. for an easier vapor barrier joint with the pipe
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A6000U) Other I.D.s and/or O.D.s available on request
Formal submittal sheets available
Performance test results on file:
Available upon request

www.pipeshields.com/a6000 27
Pipe
Shields Heavy Duty with
Inc. Model A7000 Insulated Pipe Support load bearing plate

MAXIMUM
LOAD RTG.
Pipe (LBS)
Size On Flat A B C
Surface
(a)
2 1/2 250 6 3 1/4
3 300 6 3 1/4
3 1/2 350 6 3 1/4
4 400 6 3 1/4
5 500 6 3 1/4
6 550 6 3 1/4
A5000, A7000 - A8400
A5000, A7000 - A8400 8 700 6 3 1/4
10 875 9 6 3/8
12 1600 9 6 3/8
14 1650 9 6 3/8
16 1850 9 6 1/2
18 2000 9 6 1/2
20 2100 9 6 1/2
24 2300 9 6 3/4
30 2500 9 6 3/4
C THK.
36 2500 9 6 3/4
42 2500 9 6 3/4
B TABLE I
A
INCHES
Contact factory for other dimensions,
temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see A7200

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subj ect to change without notice. Contact factory for current information.

a) To develop maximum load rating, width of support sur face should be at least 1/2 of dimension B in Table I.

Application: Features: Material Data:

Model A7000 is designed for use on: Compact A7000: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Minimizes heat loss and/or condensation
Insulating structural inserts for load transfer Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Intended for installation on: Overlapping galvanized sheet metal jacket
repellant.
Flat surfaces Load distribution plate integral with bottom
Pipe rolls, see A8000 jacket Load distribution Plate: Carbon steel
ASTM A-36
Clevis hangers, see A9000 Other I.D.s and/or O.D.s available on request
Coating: Primer coated or hot-dip galvanized
Temperature Range: Performance test results on file: Other coatings available upon request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request Glue: Industrial contact adhesive
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A7000U) Formal submittal sheets available

28 www.pipeshields.com/a7000
Pipe
Heavy Duty with Shields
Model A7200 Insulated Pipe Support load bearing plate Inc.

MAXIMUM
LOAD RTG.
(LBS)
Pipe On Flat
Size Surface A B C
(a)
6 1000 9 6 1/2
8 1250 9 6 1/2
10 1550 9 6 5/8
12 2250 9 6 5/8
14 2780 9 6 5/8
16 3300 9 6 3/4
A5000, A7000 - A5000,
A8400 A7000 - A8400 18 3600 9 6 3/4
20 3800 9 6 3/4
24 4100 9 6 1
30 4500 9 6 1
36 4500 9 6 1
42 4500 9 6 1
TABLE I

C THK.
Contact factory for other dimensions,
temperatures, and loads. Available in all
B insulation thicknesses.
A
INCHES

Note: For higher load ratings, see A7400, B1100

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subj ect to change without notice. Contact factory for current information.

a) To develop maximum load rating, width of support sur face should be at least 1/2 of dimension B in Table I.

Application: Features: Material Data:

Model A7200 is designed for use on: Compact A7200: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Minimizes heat-loss and/or condensation
Insulating structural inserts for load transfer Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Intended for installation on: Overlapping galvanized sheet metal jacket
repellant
Flat surfaces Load distribution plate integral with bottom
Pipe rolls, see A8200 jacket Load distribution Plate: Carbon steel
ASTM A-36
Clevis hangers, see A9000 Other I.D.s and/or O.D.s available on request
Coating: Primer coated or hot-dip galvanized
Temperature Range: Performance test results on file: Other coatings available upon request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request Glue: Industrial contact adhesive
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A7200U) Formal Submittal Sheets available

www.pipeshields.com/a7200 29
Pipe
Shields Heavy Duty with
Inc. Model A7400 Insulated Pipe Support load bearing plate

MAXIMUM
LOAD RTG.
(LBS)
Pipe On Flat
Size Surface A B C
(a)
10 2100 9 6 3/4
12 3400 9 6 3/4
14 3900 9 6 3/4
16 4400 9 6 1
18 4800 9 6 1
20 5100 9 6 1
A5000, A7000 - A8400
, A7000 - A8400 24 5500 9 6 1
30 5500 9 6 1
36 6500 9 6 1
42 7500 9 6 1
TABLE I

Contact factory for other dimensions,


temperatures, and loads. Available in all
insulation thicknesses.
C THK.

A
INCHES

Note: For higher load ratings, see B1200

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subj ect to change without notice. Contact factory for current information.

a) To develop maximum load rating, width of support sur face should be at least 1/2 of dimension B in Table I.

Application: Features: Material Data:

Model A7400 is designed for use on: Compact A7400: Applicable PSI spec. doc.: No. 205.
Hot water Steam Easy installation
Insulation: Calcium Silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized Steel ASTM A-653
Dual temperature Vacuum Minimizes heat-loss and/or condensation
Insulating structural inserts for load transfer Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Intended for installation on: Overlapping galvanized sheet metal jacket
repellant.
Flat surfaces Load distribution plate integral with bottom
Pipe rolls, see A8400 jacket Load distribution Plate: Carbon steel
ASTM A-36
Clevis hangers, see A9000 Other I.D.s and/or O.D.s available on request
Coating: Primer coated or hot-dip galvanized
Temperature Range: Performance Test Results on File: Other coatings available upon request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request Glue: Industrial contact adhesive
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A7400U) Formal Submittal Sheets available

30 www.pipeshields.com/a7400
Pipe
Heavy Duty with Shields
Model A8000 Insulated Pipe Support load bearing plate Inc.

MAXIMUM
LOAD RTG. Max. Axial
(LBS) Travel
(Inches)
Pipe On on
Size Pipe A B C Pipe Roll
Roll
2 1/2 225 9 6 1/4 2
3 250 9 6 1/4 2
3 1/2 300 9 6 1/4 2
4 350 9 6 1/4 2
5 450 9 6 1/4 2
A5000, A7000 - A8400 6 500 9 6 1/4 2
8 625 9 6 1/4 2
000 - A8400
10 875 12 9 3/8 4
12 1400 12 9 3/8 4
14 1475 12 9 3/8 4
16 1650 12 9 1/2 4
18 1800 12 9 1/2 4
20 1875 12 9 1/2 4
24 2050 12 9 3/4 4
30 2250 12 9 3/4 4
36 2250 12 9 3/4 4
C THK. 42 2250 12 9 3/4 4
TABLE I

B
Contact factory for other dimensions, temperatures, and
loads. Available in all insulation thicknesses.
A
INCHES

Hardware sold separately


Note: For higher load ratings, see A8200

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subj ect to change without notice. Contact factory for current information.

Application: Features: Material Data:

Model A8000 is designed for use on: Compact A8000: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Minimizes heat loss and/or condensation
Insulating structural inserts for load transfer Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Intended for installation on: Overlapping galvanized sheet metal jacket
repellant
Flat surfaces, see A7000 Load distribution plate integral with bottom
Pipe rolls jacket Load distribution Plate: Carbon steel
ASTM A-36
Clevis hangers, see A9000 Other I.D.s and/or O.D.s available on request
Coating: Primer coated or hot-dip galvanized.
Temperature Range: Performance test results on file: Other coatings available upon request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request Glue: Industrial contact adhesive
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A8000U) Formal submittal sheets available

www.pipeshields.com/a8000 31
Pipe
Shields Heavy Duty with
Inc.
Model A8200 Insulated Pipe Support load bearing plate

MAXIMUM
LOAD RTG. Max. Axial
(LBS) Travel
(Inches)
Pipe On on
Size Pipe A B C Pipe Roll
Roll
6 900 12 9 1/2 3
8 1125 12 9 1/2 3
10 1375 12 9 5/8 3
12 2550 12 9 5/8 3
000 - A8400
A5000, A7000 - A8400 14 2650 12 9 5/8 3
16 2950 12 9 3/4 3
18 3200 12 9 3/4 3
20 3375 12 9 3/4 3
24 3675 12 9 1 3
30 4050 12 9 1 3
36 4050 12 9 1 3
42 4050 12 9 1 3
TABLE I
C THK.

Contact factory for other dimensions, temperatures, and


B
loads. Available in all insulation thicknesses.
A
INCHES

Hardware sold separately


Note: For higher load ratings, see A8400, B1100

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subj ect to change without notice. Contact factory for current information.

Application: Features: Material Data:

Model A8200 is designed for use on: Compact A8200: Applicable PSI spec. doc.: No. 205.
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Minimizes heat loss and/or condensation
Insulating structural inserts for load transfer Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Intended for installation on: Overlapping galvanized sheet metal jacket
repellant
Pipe rolls Load distribution plate integral with bottom
Flat surfaces, see A7200 jacket Load distribution Plate: Carbon steel
ASTM A-36
Clevis hangers, see A9000 Other I.D.s and/or O.D.s available on request
Coating: Primer coated or hot-dip galvanized
Temperature Range: Performance test results on file: Other coatings available upon request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request Glue: Industrial contact adhesive
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A8200U) Formal submittal sheets available

32 www.pipeshields.com/a8200
Pipe
Heavy Duty with Shields
Model A8400 Insulated Pipe Support load bearing plate Inc.

MAXIMUM
LOAD RTG. Max. Axial
(LBS) Travel
(Inches)
Pipe On on
Size Pipe A B C Pipe Roll
Roll
10 1875 12 9 1 2 1/4
12 3400 12 9 1 2 1/4
14 3500 12 9 1 2 1/4
16 3950 12 9 1 2 1/4
, A7000 -A5000,
A8400 A7000 - A8400 18 4300 12 9 1 2 1/4
20 4550 12 9 1 2 1/4
24 4950 12 9 1 2 1/4
30 5450 12 9 1 2 1/4
36 6450 12 9 1 2 1/4
42 7450 12 9 1 2 1/4
TABLE I

Contact factory for other dimensions, temperatures, and


C THK. loads. Available in all insulation thicknesses.

A
INCHES

Hardware sold separately


Note: For higher load ratings, see B1200

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subj ect to change without notice. Contact factory for current information.

Application: Features: Material Data:

Model A8400 is designed for use on: Compact A8400: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold water Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Copper tubing sizes available
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Minimizes heat loss and/or condensation
Insulating structural inserts for load transfer Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Intended for installation on: Overlapping galvanized sheet metal jacket
repellant
Pipe rolls Load distribution plate integral with bottom
Flat surfaces, see A7400 jacket Load distribution Plate: Carbon steel
ASTM A-36
Clevis hangers, see A9000 Other I.D.s and/or O.D.s available on request
Coating: Primer coated or hot-dip galvanized
Temperature Range: Performance test results on file: Other coatings available upon request
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request Glue: Industrial contact adhesive
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A8400U) Formal submittal sheets available

www.pipeshields.com/a8400 33
Pipe
Shields Heavy Duty for use
Inc. Model A9000 Insulated Pipe Support with rod hangers
A1000, A3000, A9000 MAXIMUM
LOAD RTG.
A1000, A3000, A9000
(LBS)
In Ring
Pipe or Clevis
Size Hanger
(a)
1/2 50
3/4 55
1 80
1 1/4 100
1 1/2 130
2 175
A
INCHES
2 1/2 250
3 300
3 1/2 350
4 400
5 550
6 600
Hardware sold separately 8 900
Note: For higher load ratings, see D1000, D3000 10 1200
12 1450
The load ratings represent average values obtained in accordance with accepted methods and are subject 14 1650
to normal manufacturing variations. Dim ensions and ratings are subject to change without notice. 16 1900
18 2150
a) To develop maximum load rating use band, ring or clevis hanger with manufacturers load rating 20 2400
equal to or greater than values shown in Table I. 24 2750
TABLE I

Contact factory for other dimensions,


temperatures, and loads. Available in all
insulation thicknesses.

Iron Insulation Thickness Copper


Pipe 1/2 3/4 1 1 1/2 2 2 1/2 3 3 1/2 4 Tubing
Size A B A B A B A B A B A B A B A B A B Size O.D.
1/2 - 1 1/2 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 5/8-1 5/8
2 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 2 1/8
2 1/2 - 4 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 2 5/8 - 4 1/8
5 6 20 6 20 6 20 6 20 9 20 9 20 9 20 5 1/8
6-7 6 20 6 20 6 20 6 20 9 16 9 16 9 16 6 1/8
8 - 10 9 16 9 16 9 16 9 16 9 16 9 16 8 1/8 -10 1/8
12 - 18 12 16 12 16 12 16 12 16 12 16 12 16 12 1/8
20 - 24 18 16 18 16 18 16 18 16 18 16 18 16
TABLE II "B" = gauge of sheet metal jacket (bottom jac ket approx. 2 X ga. of top jacket)

Application: Features: Material Data:

Model A9000 is designed for use on: Compact A9000: Applicable PSI spec. doc.: No. 205
Hot water Steam Easy installation
Insulation: Calcium silicate asbestos-
Cold wwater Air Eliminates welding to pipe
free, treated with water repellant
Chilled water Gas Overlapping galvanized sheet metal
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum jacket
Minimizes heat loss and/or condensation Structural Inserts: High-density calcium
Insulating structural inserts for load transfer silicate asbestos-free, treated with water
Intended for installation on:
Copper tubing available repellant
Band, ring or clevis pipe hangers
Flat surfaces, see A7000 Other I.D.s and/or O.D.s available on Glue: Industrial contact adhesive
Pipe rolls, see A8000 request Formal submittal sheets available

Temperature Range: Performance test results on file:


Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., A9000U)

34 www.pipeshields.com/a9000
Pipe
Shields
Inc.

35
Pipe
Shields
Inc. Introduction: Section B

INTRODUCTION
SECTION B
PRE-INSULATED PIPE SUPPORTS - Base Mounted
APPLICATION Heavy Industrial and Large HVAC Distribution Systems

Features:
Accommodation of thermal movement
Provision or lateral guide or restraint
Minimization of side friction loads
Wide range of maximum load requirements for each pipe size

Note: In each model number series (for example: B1000 through B1300 Series), the higher the
model number, the higher the load rating.

Models B1000 - B1300 Sliding supports free to travel axially and laterally.

Models B2000 - B2300 Same as B1000 - B1300 except can accommodate greater axial travel.

Models B3000 - B3300 Sliding supports with lateral guides.

Models B4000 - B4300 Same as B3000 - B3300 except can accommodate greater axial travel.

Models B5000 - B5300 Same as B1000 - B1300 except can accommodate greater lateral travel.

Models B6000 - B6300 Same as B2000 - B2300 except can accommodate greater lateral travel.

Models B7000 - B7300 Same as B3000 - B3300 except with reduced vertical load ratings to allow greater
lateral loads. Minimum side friction is assured by the addition of lateral slide pads.

Models B8000 - B8300 Same as B4000 - B4300 except with reduced vertical load ratings to allow greater
lateral loads. Minimum side friction is assured by the addition of lateral slide pads.

To meet special thermal movement requirements, Pipe Shields, Inc. has provided supports that have
accommodated axial travels in excess of five (5) feet. By modifying our standard pipe support concept
with combinations of structural insulation materials, steel base and strap design, and slide plate
configuration, we can readily and economically respond to virtually any pipe support requirement.

If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
707-447-5014 or 1-800-538-7007.

Please acquaint yourself with the selection guide at the front of this catalog and the section index
on the page following this introduction, for assistance in determining the most appropriate support
for your application.

36
Pipe
Shields
Section B Index Inc.
PRE-INSULATED PIPE SUPPORTS

HEAVY INDUSTRIAL - BASE MOUNTED


PIPE TRAVEL
B1000 SIZE (INCHES) +/- LATERAL
MODEL RANGE AXIAL LATERAL GUIDE DUTY

B1000 1/2 - 42 1.5 1.5 NO MEDIUM


B1100 1/2 - 42 1.5 1.5 NO HEAVY
B1200 1/2 - 42 1.5 1.5 NO HEAVIER
B2000
B1300 1/2 - 42 1.5 1.5 NO HEAVIEST

B2000 1/2 - 42 4.5 1.5 NO MEDIUM


B2100 1/2 - 42 4.5 1.5 NO HEAVY
B2200 1/2 - 42 4.5 1.5 NO HEAVIER
B3000
B2300 1/2 - 42 4.5 1.5 NO HEAVIEST

B3000 1/2 - 42 1.5 0 YES MEDIUM


B3100 1/2 - 42 1.5 0 YES HEAVY
B3200 1/2 - 42 1.5 0 YES HEAVIER
B4000 B3300 1/2 - 42 1.5 0 YES HEAVIEST

B4000 1/2 - 42 4.5 0 YES MEDIUM


B4100 1/2 - 42 4.5 0 YES HEAVY
B4200 1/2 - 42 4.5 0 YES HEAVIER
B4300 1/2 - 42 4.5 0 YES HEAVIEST

www.pipeshields.com/b-series 37
Pipe
Shields
Inc. Section B Index
PRE-INSULATED PIPE SUPPORTS

HEAVY INDUSTRIAL - BASE MOUNTED


PIPE TRAVEL
B5000 SIZE (INCHES) +/- LATERAL
MODEL RANGE AXIAL LATERAL GUIDE DUTY

B5000 1/2 - 42 1.5 1.5 - 4.5 NO MEDIUM


B5100 1/2 - 42 1.5 1.5 - 4.5 NO HEAVY
B6000
B5200 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIER
B5300 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIEST

B6000 1/2 - 42 4.5 1.5 - 4.5 NO MEDIUM


B6100 1/2 - 42 4.5 1.5 - 4.5 NO HEAVY
B7000 B6200 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIER
B6300 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIEST

B7000 1/2 - 42 1.5 0 YES MEDIUM


B7100 1/2 - 42 1.5 0 YES HEAVY
B8000 B7200 1/2 - 42 1.5 0 YES HEAVIER
B7300 1/2 - 42 1.5 0 YES HEAVIEST

B8000 1/2 - 42 4.5 0 YES MEDIUM


B8100 1/2 - 42 4.5 0 YES HEAVY
B8200 1/2 - 42 4.5 0 YES HEAVIER
B8300 1/2 - 42 4.5 0 YES HEAVIEST

38 www,pipeshields.com/b-series
Pipe
Shields
Section B Index Inc.

THE FOLLOWING TABLE ILLUSTRATES


BOTTOM-O F-PIPE TO TOP-OF-STEEL DIMENSIONS
(DIMENSION B) FOR B MODEL PIPE SUPPORTS AND C M ODEL PIPE ANCHORS FOR
INTERMEDIATE INSULATION THICKNESS

PIPE INSULATION THICKNESS


SIZE 3 1/2 4 1/2 5 1/2 6 6 1/2 7 7 1/2 8 8 1/2 9 9 1/2 10
3 6 6 8 8 8 10 12 12 12 12 13 14
3 1/2 6 6 8 8 8 10 12 12 12 12 13 14
4 6 6 8 8 8 10 12 12 12 12 13 14
5 6 6 8 8 8 10 12 12 12 12 13 14
6 6 6 8 8 8 10 12 12 12 12 13 14
8 6 8 8 8 10 10 12 12 12 12 13 14
10 6 8 8 8 10 10 12 12 12 12 13 14
12 6 8 8 8 10 10 12 12 12 12 13 14
14 6 8 8 8 10 10 12 12 12 12 13 14
16 6 8 8 10 10 10 12 12 12 12 13 14
18 6 8 8 10 10 10 12 12 12 12 13 14
20 6 8 8 10 10 10 12 12 12 12 13 14
24 6 8 8 10 10 10 12 12 12 12 13 14
30 8 8 10 10 10 10 12 12 12 12 13 14
36 8 8 10 10 10 10 12 12 12 12 13 14
42 8 8 10 10 10 10 12 12 12 12 13 14

COMMENTS:

The insulation thickness shown on the Product Data Sheets in Sections B and C are in
even 1 increments. The table shown here provides Bottom-of-Pipe to Top-of-Steel dimensions
(B Dimensions) for 3 1/2, 4 1/2, 5 1/2, 6, 6 1/2, 7, 7 1/2, 8, 8 1/2, 9, 9 1/2, and 10 insulation
thicknesses. Check with factory if you require a B dimension other than those shown in this table.

TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 18 IPS
3. Insulation Thickness 2
4. Model Number B1000

EXAMPLE: (20) 18 x 2 B1000

www.pipeshields.com/b-series 39
Pipe
Shields Heavy Duty,
Inc.
Model B1000 Sliding Insulated Pipe Support Base Mounted
B1000
1/2" MAX.
B5000LATERAL TRAVEL
"L" MAX.
E LATERAL TRAVEL 9"

E 9"

PIPE 1 1/2" MAX.

PIPE AXIAL TRAVEL 1 1/2" MAX.


AXIAL TRAVEL
B.O.P.
B.O.P.

B
B
T.O.S.
T.O.S.

3"

C 6"
3"

C 6"
STEEL MOUNTING PLATE
STEEL MOUNTING PLATE
POLYETHYLENE SLIDE PAD
POLYETHYLENE SLIDE PAD

3"
3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions
and ratings are subject to change without notice.

Note: For higher load ratings, see: B1100 - For greater axial travel, see: B2000 - For lateral restraint, see: B3000 - For lateral travel, see: B5000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
1 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25
2 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875
6 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125
10 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125
12 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B1000 is designed for use on: All pipe sizes B1000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B1000U) Available upon request Formal Submittal Sheets available

40 www,pipingtech.com/b1000
Pipe
Heavy Duty, Shields
Model B1100 Sliding Insulated Pipe Support Base Mounted Inc.
B1000
1/2" MAX.
B5000LATERAL TRAVEL
"L" MAX.
LATERAL TRAVEL
E 9"

E 9"

PIPE PIPE
1 1/2" MAX.
AXIAL TRAVEL 1 1/2" MAX.
AXIAL TRAVEL
B.O.P.
B.O.P.

B B

T.O.S. T.O.S.

3"

C 6"
3"

C 6"
STEEL MOUNTING PLATE
STEEL MOUNTING PLATE
POLYETHYLENE SLIDE PAD
POLYETHYLENE SLIDE PAD

3"

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B1200 - For greater axial travel, see: B2100 - For lateral restraint, see: B3100 - For lateral travel, see: B5100.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B1100 is designed for use on: All pipe sizes B1100: Applicable PSI spec. doc.: No. 209.
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant.
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653.
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant.
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36.
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated.
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional).
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized.
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B1100U) Available upon request. Formal submittal sheets available

www.pipeshields.com/b1100 41
Pipe
Shields Heavy Duty,
Inc. Model B1200 Sliding Insulated Pipe Support Base Mounted
B1000

B5000 1/2" MAX.


LATERAL TRAVEL "L" MAX.
LATERAL TRAVEL
E 9"
E 9"

PIPE PIPE 1 1/2" MAX. 1 1/2" MAX.


AXIAL TRAVEL AXIAL TRAVEL

B.O.P. B.O.P.

B
B
T.O.S.
T.O.S.
3"

C 6"

3"

C 6" STEEL MOUNTING PLATE


POLYETHYLENE
STEEL MOUNTING SLIDE
PLATEPAD
POLYETHYLENE SLIDE PAD
3"

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B1300 - For greater axial travel, see: B2200 - For lateral restraint, see: B3200 - For lateral travel, see: B5200.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B1200 is designed for use on: All pipe sizes B1200: Applicable PSI spec. doc.: No. 209.
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant.
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653.
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant.
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36.
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated.
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional).
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on sile: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B1200U) Available upon request. Formal Submittal Sheets available

42 www.pipeshields.com/b1200
Pipe
Heavy Duty, Shields
Model B1300 Sliding Insulated Pipe Support Base Mounted Inc.
B1000
1/2" MAX.
B5000 LATERAL TRAVEL
"L" MAX.
E LATERAL TRAVEL 9"

E 9"

PIPE 1 1/2" MAX.

PIPE AXIAL TRAVEL 1 1/2" MAX.


AXIAL TRAVEL
B.O.P.
B.O.P.

B
B
T.O.S.
T.O.S.

3"

C 6"
3"

C 6"
STEEL MOUNTING PLATE
STEEL MOUNTING PLATE
POLYETHYLENE SLIDE PAD
POLYETHYLENE SLIDE PAD

3"

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings contact factory - For greater axial travel, see: B2300 - For lateral restraint, see: B3300 - For lateral travel, see: B5300.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
3 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B1300 is designed for use on: All pipe sizes B1300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized Steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B1300U) Available upon request Formal submittal sheets available

www.pipeshields.com/b1300 43
Pipe
Shields Heavy Duty,
Inc. Model
B2000 B2000 Sliding Insulated Pipe Support Base Mounted
B5000
"L" MAX.
1/2" MAX. LATERAL TRAVEL
LATERAL TRAVEL
E 9"

E 15"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

PIPE B.O.P.
4 1/2" MAX.
AXIAL TRAVEL

B.O.P. B

T.O.S.
B
3"
T.O.S.

C 3" 6"

STEEL MOUNTING PLATE


C 12"
POLYETHYLENE SLIDE PAD

STEEL MOUNTING PLATE


3"
POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B2100 - For lesser axial travel, see: B1000 - For lateral restraint, see: B4000 - For lateral travel, see: B6000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
1 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25
2 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875
6 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125
10 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125
12 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B2000 is designed for use on: All pipe sizes B2000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B2000U) Available upon request Formal submittal sheets available

44 www.pipeshields.com/b2000
Pipe
Heavy Duty, Shields
Model B2100 Sliding Insulated Pipe Support
B2000 Base Mounted Inc.
B5000
"L" MAX.
1/2" MAX. LATERAL TRAVEL
LATERAL TRAVEL
E 9"
E 15"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

PIPE B.O.P.
4 1/2" MAX.
AXIAL TRAVEL

B.O.P. B

T.O.S.
B
3"
T.O.S.

3"
C 6"

STEEL MOUNTING PLATE


C 12"
POLYETHYLENE SLIDE PAD

STEEL MOUNTING PLATE


3"
POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B2200 - For lesser axial travel, see: B1100 - For lateral restraint, see: B4100 - For lateral travel, see: B6100.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B2100 is designed for use on: All pipe sizes B2100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B2100U) Available upon request. Formal submittal sheets available

www.pipeshields.com/b2100 45
Pipe
Shields Heavy Duty,
Inc. Model
B2000 B2200 Sliding Insulated Pipe Support Base Mounted

1/2" MAX.
B5000LATERAL TRAVEL
"L" MAX.
LATERAL TRAVEL
E 15"

E 9"

PIPE PIPE
4 1/2" MAX.
AXIAL TRAVEL1 1/2" MAX.
AXIAL TRAVEL
B.O.P.
B.O.P.

B
B
T.O.S. T.O.S.

3"
3"

C 6"
C 12"

STEEL MOUNTING PLATE


STEEL MOUNTING PLATE
POLYETHYLENE SLIDE PAD
POLYETHYLENE SLIDE PAD

3"

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B2300 - For lesser axial travel, see: B1200 - For lateral restraint, see: B4200 - For lateral travel, see: B6200.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B2200 is designed for use on: All pipe sizes B2200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B2200U) Available upon request. Formal Submittal Sheets available

46 www.pipeshields.com/b2200
Pipe
Heavy Duty, Shields
Model B2300 Sliding Insulated Pipe Inc.
B2000 Support Base Mounted

B5000LATERAL
1/2" MAX.
TRAVEL
"L" MAX.
LATERAL TRAVEL
E 15"
E 9"

PIPE PIPE
4 1/2" MAX.
AXIAL TRAVEL
1 1/2" MAX.
AXIAL TRAVEL

B.O.P. B.O.P.

B B

T.O.S. T.O.S.

3"

3"

C 6"
C 12"

STEEL MOUNTING PLATE


STEEL MOUNTINGSLIDE
POLYETHYLENE PLATEPAD
POLYETHYLENE SLIDE PAD

3"

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For lesser axial travel, see: B1300 - For lateral restraint, see: B4300 - For lateral travel, see: B6300.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
3 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model B2300 is designed for use on: All pipe sizes B2300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized Steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized.
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B2300U) Available upon request. Formal submittal sheets available

www.pipeshields.com/b2300 47
Pipe
Shields Heavy Duty,
Inc.
Model
B3000 B3000 Guided Insulated Pipe Support Base Mounted

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR STEEL MOUNTING PLATE


TYP WITH RESTRAINTS
C 6"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B3100 - For greater axial travel, see: B4000 - For lateral travel, see: B5000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 175 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
1 225 4 6.5 3.875 4 7 4.875 4 7.5 5.937 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 1/2 325 4 6.5 4.375 4 7 5.5 4 8.5 7 4 9 8 6 10 9 6 12 11.25 8 13.5 13.25
2 375 4 7 5 4 7.5 6.0625 4 8.5 7 4 9 8 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 460 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 530 4 7.5 6.062 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 840 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 1050 4 10 8.25 4 11 9.25 4 12 10.25 4 13 11.375 6 13.5 12.375 6 15 14.875 8 16.5 16.875
6 1275 4 11 9.25 4 12 10.25 4 13 11.375 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 1700 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 17.875 8 19 20.125
10 2000 4 15 13.625 4 15.5 14.875 4 16.5 15.875 6 17 16.875 6 18 18.125 6 19 20.125 8 20.5 22.125
12 2200 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 2500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 2900 4 20.5 19.125 4 21 20.125 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 3200 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 3400 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 3600 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 4700 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 5500 4 36.5 39.625 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 6200 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B3000 is designed for use on: All pipe sizes B3000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat Surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B3000U) Available upon request. Formal submittal sheets available

48 www.pipeshields.com/b3000
Pipe
Heavy Duty,
Shields
Model B3100 Guided Insulated Pipe Support
B3000
Base Mounted
Inc.

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR STEEL MOUNTING PLATE


TYP WITH RESTRAINTS
C 6"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B3200 - For greater axial travel, see: B4100 - For lateral travel, see: B5100

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 350 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 450 4 6.5 3.875 4 7 5 4 7.5 6.062 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 1/2 650 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 750 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 920 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1060 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 1680 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 2100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 2550 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 3400 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 4000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 4400 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 5000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 5800 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 6400 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 6800 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 7200 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 9400 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 11000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 12400 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B3100 is designed for use on: All pipe sizes B3100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized.
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B3100U) Available upon request. Formal submittal sheets available

www.pipeshields.com/b3100 49
Pipe
Shields Heavy Duty,
Inc. B3000
Model B3200 Guided Insulated Pipe Support Base Mounted

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR STEEL MOUNTING PLATE


TYP WITH RESTRAINTS
C 6"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B3300 - For greater axial travel, see: B4200 - For lateral travel, see: B5200.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
3/4 700 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 900 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 1/2 1300 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1500 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1800 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
3 2100 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 3350 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 4200 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 5100 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 6800 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 8000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 8800 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 10000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 11600 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 12800 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 13600 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 14400 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 18800 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 22000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 24800 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B3200 is designed for use on: All pipe sizes B3200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B3200U) Available upon request. Formal submittal sheets available

50 www.pipeshields.com/b3200
Pipe
Heavy Duty, Shields
Model B3300 Guided Insulated Pipe Support
B3000 Base Mounted Inc.

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR STEEL MOUNTING PLATE


TYP WITH RESTRAINTS
C 6"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For greater axial travel, see: B4300 - For lateral travel, see: B5300

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
3/4 700 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 900 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 1/2 1300 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1500 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1800 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
3 2100 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 3350 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 4200 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 5100 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 6800 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 8000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 8800 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 10000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 11600 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 12800 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 13600 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 14400 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 18800 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 22000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 24800 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B3300 is designed for use on: All pipe sizes B3300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy Installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized Steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat Surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance Test Results on File: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B3300U) Available upon request. Formal Submittal Sheets available

www.pipeshields.com/b3300 51
Pipe
Shields Heavy Duty,
Inc. Model B4000 Guided Insulated Pipe Support Base Mounted

B4000

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR
TYP C 12"
STEEL MOUNTING PLATE
WITH RESTRAINTS

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B4100 - For lateral travel, see: B6000.
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 175 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
1 225 4 6.5 3.875 4 7 4.875 4 7.5 5.937 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 1/2 325 4 6.5 4.375 4 7 5.5 4 8.5 7 4 9 8 6 10 9 6 12 11.25 8 13.5 13.25
2 375 4 7 5 4 7.5 6.0625 4 8.5 7 4 9 8 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 460 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 530 4 7.5 6.062 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 840 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 1050 4 10 8.25 4 11 9.25 4 12 10.25 4 13 11.375 6 13.5 12.375 6 15 14.875 8 16.5 16.875
6 1275 4 11 9.25 4 12 10.25 4 13 11.375 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 1700 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 17.875 8 19 20.125
10 2000 4 15 13.625 4 15.5 14.875 4 16.5 15.875 6 17 16.875 6 18 18.125 6 19 20.125 8 20.5 22.125
12 2200 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 2500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 2900 4 20.5 19.125 4 21 20.125 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 3200 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 3400 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 3600 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 4700 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 5500 4 36.5 39.625 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 6200 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B4000 is designed for use on: All pipe sizes B4000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B4000U) Available upon request. Formal submittal sheets available

52 www.pipeshields.com/b4000
Pipe
Heavy Duty, Shields
Model B4100 Guided Insulated Pipe Support Base Mounted Inc.
B4000

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR
TYP C 12"
STEEL MOUNTING PLATE
WITH RESTRAINTS

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B4200 - For lateral travel, see: B6100.
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 350 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 450 4 6.5 3.875 4 7 5 4 7.5 6.062 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 1/2 650 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 750 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 920 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1060 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 1680 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 2100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 2550 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 3400 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 4000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 4400 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 5000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 5800 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 6400 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 6800 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 7200 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 9400 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 11000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 12400 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B4100 is designed for use on: All pipe sizes B4100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B4100U) Available upon request. Formal Submittal Sheets available

www.pipeshields.com/b4100 53
Pipe
Shields Heavy Duty,
Inc. Model B4200 Guided Insulated Pipe Support Base Mounted

B4000

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR
TYP C 12"
STEEL MOUNTING PLATE
WITH RESTRAINTS

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B4300 - For lateral travel, see: B6200.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 500 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 650 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 1/2 950 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1100 4 7 5 4 7.5 6.1875 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1350 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1600 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 2500 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 3100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 3800 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 5100 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 6000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 6600 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 7500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 8700 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 9600 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 10200 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 10800 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 14100 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 16500 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 18600 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B4200 is designed for use on: All pipe sizes B4200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B4200U) Available upon request. Formal submittal sheets available

54 www.pipeshields.com/b4200
Pipe
Heavy Duty, Shields
Model B4300 Guided Insulated Pipe Support Base Mounted Inc.
B4000

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

1/8" CLR
B TYP

T.O.S.

4"

1/8" CLR
TYP C 12"
STEEL MOUNTING PLATE
WITH RESTRAINTS

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 20% of vertical load, contact factory. Available in
all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For lateral travel, see: B6300.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
3/4 700 4 6 3.375 4 6.5 4.5 4 7 5.5 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 900 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 1/2 1300 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1500 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1800 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
3 2100 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 3350 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 4200 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 5100 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 6800 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 8000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 8800 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 10000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 11600 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 12800 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 13600 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 14400 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 18800 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 22000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 24800 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125

Application: Features: Material Data:

Model B4300 is designed for use on: All pipe sizes B4300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
Temperature Range: mounting plate
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request. Performance test results on file: Other coatings available upon request
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., B4300U) Available upon request. Formal submittal sheets available

www.pipeshields.com/b4300 55
Pipe
Shields Heavy Duty,
Inc. Model B5000 Wide Base Sliding Insulated Pipe Support Base Mounted
B5000
"L" MAX.
LATERAL TRAVEL

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 6"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B5100 - For greater axial travel, see: B6000 - For lateral restraint, see: B3000 - For lateral travel, see: B1000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
3/4 175 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
1 225 4 5.75 3.875 4 6.75 4.875 4 7.75 5.937 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 1/2 325 4 6.25 4.375 4 7.25 5.5 4 8.75 7 4 9.75 8 6 10.75 9 6 12.75 11.25 8 14.75 13.25
2 375 4 6.75 5 4 7.75 6.0625 4 8.75 7 4 9.75 8 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 460 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.25 8 15.75 14.5
3 530 4 7.75 6.062 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 840 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 1050 4 9 8.25 4 10 9.25 4 11 10.25 4 12 11.375 6 13 12.375 6 15 14.875 8 17 16.875
6 1275 4 9.5 9.25 4 10.5 10.25 4 11.5 11.375 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 1700 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 17.875 8 18.5 20.125
10 2000 4 11.5 13.625 4 12.5 14.875 4 13.5 15.875 6 14.5 16.875 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 2200 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 2500 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 2900 4 14 19.125 4 15 20.125 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 3200 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 3400 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 3600 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 4700 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 5500 4 27.5 39.625 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 6200 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B5000 is designed for use on: All pipe sizes B5000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B5000U)

56 www.pipeshields.com/b5000
Pipe
Heavy Duty,
Shields
Model B5100 Wide Base Sliding Insulated Pipe Support Base Mounted
Inc.
B5000
"L" MAX.
LATERAL TRAVEL

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 6"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B5200 - For greater axial travel, see: B6100 - For lateral restraint, see: B3100 - For lateral travel, see: B1100.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
3/4 350 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 450 4 5.75 3.875 4 6.75 5 4 7.75 6.062 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 1/2 650 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 750 4 6.75 5 4 7.75 6.0625 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 920 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.25 8 15.75 14.5
3 1060 4 7.75 6.187 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 1680 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 2100 4 9 8.5 4 10 9.5 4 11 10.5 4 12 11.625 6 13 12.625 6 15 14.875 8 17 16.875
6 2550 4 9.5 9.5 4 10.5 10.5 4 11.5 11.625 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 3400 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 18.125 8 18.5 20.125
10 4000 4 11.5 13.875 4 12.5 15.125 4 13.5 16.125 6 14.5 17.125 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 4400 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 5000 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 5800 4 14 19.375 4 15 20.375 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 6400 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 6800 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 7200 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 9400 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 11000 4 27.5 40.125 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 12400 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B5100 is designed for use on: All pipe sizes B5100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B5100U)

www.pipeshields.com/b5100 57
Pipe
Shields Heavy Duty,
Inc.
Model B5200 Wide Base Sliding Insulated Pipe Support Base Mounted
B5000
"L" MAX.
LATERAL TRAVEL

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 6"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B5300 - For greater axial travel, see: B6200 - For lateral restraint, see: B3200 - For lateral travel, see: B1200.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
3/4 500 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 650 4 5.75 4 4 6.75 5 4 7.75 6.062 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
1 1/2 950 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1100 4 6.75 5 4 7.75 6.1875 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 1350 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.25 8 15.75 14.5
3 1600 4 7.75 6.187 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 2500 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 3100 4 9 8.5 4 10 9.5 4 11 10.5 4 12 11.625 6 13 12.625 6 15 14.875 8 17 16.875
6 3800 4 9.5 9.5 4 10.5 10.5 4 11.5 11.625 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 5100 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 18.125 8 18.5 20.125
10 6000 4 11.5 13.875 4 12.5 15.125 4 13.5 16.125 6 14.5 17.125 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 6600 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 7500 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 8700 4 14 19.375 4 15 20.375 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 9600 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 10200 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 10800 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 14100 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 16500 4 27.5 40.125 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 18600 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B5200 is designed for use on: All pipe sizes B5200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B5200U)

58 www.pipeshields.com/b5200
Pipe
Heavy Duty,
Shields
Model B5300 Wide Base Sliding Insulated Pipe Support Base Mounted
Inc.
B5000
"L" MAX.
LATERAL TRAVEL

E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 6"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For greater axial travel, see: B6300 - For lateral restraint, see: B3300 - For lateral travel, see: B1300.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 5.25 3.375 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
3/4 700 4 5.25 3.375 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
1 900 4 5.75 4 4 6.75 5 4 7.75 6.062 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
1 1/2 1300 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1500 4 6.75 5 4 7.75 6.0625 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 1800 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
3 2100 4 7.75 6.187 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 3350 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 4200 4 9 8.5 4 10 9.5 4 11 10.5 4 12 11.625 6 13 12.625 6 15 14.875 8 17 16.875
6 5100 4 9.5 9.5 4 10.5 10.5 4 11.5 11.625 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 6800 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 18.125 8 18.5 20.125
10 8000 4 11.5 13.875 4 12.5 15.125 4 13.5 16.125 6 14.5 17.125 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 8800 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 10000 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 11600 4 14 19.375 4 15 20.375 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 12800 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 13600 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 14400 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 18800 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 22000 4 27.5 40.125 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 24800 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B5300 is designed for use on: All pipe sizes B5300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B5300U)

www.pipeshields.com/b5300 59
Pipe
Shields Heavy Duty,
Inc.
Model B6000 Wide Base Sliding Insulated Pipe Support Base Mounted
B6000 "L" MAX.
LATERAL TRAVEL
B5000 15"
E "L" MAX.
LATERAL TRAVEL

E 9"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.
PIPE 1 1/2" MAX.
AXIAL TRAVEL
B
B.O.P.
T.O.S.

B
3"
T.O.S.

3"
C 12"

C STEEL
6" MOUNTING PLATE

POLYETHYLENE SLIDE PAD

STEEL MOUNTING PLATE


3" POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B6100 - For lateral restraint, see: B4000 - For minimal lateral travel, see: B2000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
3/4 175 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
1 225 4 5.75 3.875 4 6.75 4.875 4 7.75 5.937 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 1/2 325 4 6.25 4.375 4 7.25 5.5 4 8.75 7 4 9.75 8 6 10.75 9 6 12.75 11.25 8 14.75 13.25
2 375 4 6.75 5 4 7.75 6.0625 4 8.75 7 4 9.75 8 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 460 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.25 8 15.75 14.5
3 530 4 7.75 6.062 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 840 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 1050 4 9 8.25 4 10 9.25 4 11 10.25 4 12 11.375 6 13 12.375 6 15 14.875 8 17 16.875
6 1275 4 9.5 9.25 4 10.5 10.25 4 11.5 11.375 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 1700 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 17.875 8 18.5 20.125
10 2000 4 11.5 13.625 4 12.5 14.875 4 13.5 15.875 6 14.5 16.875 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 2200 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 2500 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 2900 4 14 19.125 4 15 20.125 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 3200 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 3400 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 3600 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 4700 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 5500 4 27.5 39.625 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 6200 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B6000 is designed for use on: All pipe sizes B6000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal Submittal Sheets available
Add U after the model number (i.e., B6000U)

60 www.pipeshields.com/b6000
Pipe
Heavy Duty,
Shields
Model B6100 Wide Base Sliding Insulated Pipe Support Base Mounted
Inc.
B6000 "L" MAX.
LATERAL TRAVEL

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 12"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B6200 - For lateral restraint, see: B4100 - For minimal lateral travel, see: B2100.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
3/4 350 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 450 4 5.75 3.875 4 6.75 5 4 7.75 6.062 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 1/2 650 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 750 4 6.75 5 4 7.75 6.0625 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 920 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.25 8 15.75 14.5
3 1060 4 7.75 6.187 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 1680 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 2100 4 9 8.5 4 10 9.5 4 11 10.5 4 12 11.625 6 13 12.625 6 15 14.875 8 17 16.875
6 2550 4 9.5 9.5 4 10.5 10.5 4 11.5 11.625 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 3400 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 18.125 8 18.5 20.125
10 4000 4 11.5 13.875 4 12.5 15.125 4 13.5 16.125 6 14.5 17.125 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 4400 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 5000 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 5800 4 14 19.375 4 15 20.375 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 6400 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 6800 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 7200 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 9400 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 11000 4 27.5 40.125 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 12400 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B6100 is designed for use on: All pipe sizes B6100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B6100U)

www.pipeshields.com/b6100 61
Pipe
Shields Heavy Duty,
Inc. Model B6200 Wide Base Sliding Insulated Pipe Support Base Mounted
B6000 "L" MAX.
LATERAL TRAVEL

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 12"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B6300 - For lateral restraint, see: B4200 - For minimal lateral travel, see: B2200.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.125
3/4 500 4 5.25 3.25 4 6.25 4.375 4 7.25 5.375 4 8.75 7 6 9.75 8 6 11.75 10 8 13.75 12.25
1 650 4 5.75 4 4 6.75 5 4 7.75 6.062 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
1 1/2 950 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1100 4 6.75 5 4 7.75 6.1875 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 1350 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.25 8 15.75 14.5
3 1600 4 7.75 6.187 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 2500 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 3100 4 9 8.5 4 10 9.5 4 11 10.5 4 12 11.625 6 13 12.625 6 15 14.875 8 17 16.875
6 3800 4 9.5 9.5 4 10.5 10.5 4 11.5 11.625 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 5100 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 18.125 8 18.5 20.125
10 6000 4 11.5 13.875 4 12.5 15.125 4 13.5 16.125 6 14.5 17.125 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 6600 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 7500 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 8700 4 14 19.375 4 15 20.375 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 9600 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 10200 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 10800 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 14100 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 16500 4 27.5 40.125 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 18600 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B6200 is designed for use on: All pipe sizes B6200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized.
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B6200U)

62 www.pipeshields.com/b6200
Pipe
Shields
Heavy Duty,
Model B6300 Wide Base Sliding Insulated Pipe Support Inc.
Base Mounted
B6000 "L" MAX.
LATERAL TRAVEL

E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

3"

C 12"

STEEL MOUNTING PLATE


POLYETHYLENE SLIDE PAD

3"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For lateral restraint, see: B4300 - For minimal lateral travel, see: B2300.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load L = +/- 1-1/2 L = +/- 1-3/4 L = +/- 2 L = +/- 2-1/4 L = +/- 2-1/2 L = +/- 3 L = +/- 3-1/2
B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 5.25 3.375 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
3/4 700 4 5.25 3.375 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
1 900 4 5.75 4 4 6.75 5 4 7.75 6.062 4 8.75 7.125 6 9.75 8.125 6 11.75 10.125 8 13.75 12.25
1 1/2 1300 4 6.25 4.5 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1500 4 6.75 5 4 7.75 6.0625 4 8.75 7.125 4 9.75 8.125 6 10.75 9.125 6 12.75 11.25 8 14.75 13.25
2 1/2 1800 4 7.25 5.5 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
3 2100 4 7.75 6.187 4 8.75 7.125 4 9.75 8.125 4 10.75 9.125 6 11.75 10.125 6 13.75 12.375 8 15.75 14.625
4 3350 4 8.25 7.25 4 9.25 8.25 4 10.25 9.25 4 11.25 10.25 6 12.25 11.375 6 14.25 13.375 8 16.25 15.625
5 4200 4 9 8.5 4 10 9.5 4 11 10.5 4 12 11.625 6 13 12.625 6 15 14.875 8 17 16.875
6 5100 4 9.5 9.5 4 10.5 10.5 4 11.5 11.625 4 12.5 12.625 6 13.5 13.625 6 15.5 15.875 8 17.5 17.875
8 6800 4 10.5 11.625 4 11.5 12.625 4 12.5 13.625 6 13.5 14.875 6 14.5 15.875 6 16.5 18.125 8 18.5 20.125
10 8000 4 11.5 13.875 4 12.5 15.125 4 13.5 16.125 6 14.5 17.125 6 15.5 18.125 6 17.5 20.125 8 19.5 22.125
12 8800 4 12.5 16.125 4 13.5 17.125 4 14.5 18.125 6 15.5 19.125 6 16.5 20.125 6 18.5 22.125 8 20.5 24.125
14 10000 4 13 17.125 4 14 18.125 4 15 19.125 6 16 20.125 6 17 21.125 6 19 23.125 8 21 25.125
16 11600 4 14 19.375 4 15 20.375 6 16 21.375 6 17 22.375 6 18 23.375 8 20 25.375 8 22 27.375
18 12800 4 15 21.375 4 16 22.375 6 17 23.375 6 18 24.375 6 19 25.375 8 21 27.375 8 23 29.375
20 13600 4 16 23.375 4 17 24.375 6 18 25.375 6 19 26.375 6 20 27.375 8 22 29.375 8 24 31.375
24 14400 4 18.5 27.375 4 19.5 28.375 6 20 29.375 6 21 30.375 6 22 31.375 8 24 33.375 8 26 35.375
30 18800 4 23.5 33.625 6 24 34.625 6 25 35.625 6 25.5 36.625 6 26 37.625 8 27.5 39.625 8 29 41.625
36 22000 4 27.5 40.125 6 28.5 41.125 6 29 42.125 6 29.5 43.125 6 30.5 44.125 8 32 46.125 8 33.5 48.125
42 24800 4 32 46.125 6 32.5 47.125 6 33.5 48.125 6 34 49.125 6 34.5 50.125 8 36 52.125 8 37.5 54.125

Application: Features: Material Data:

Model B6300 is designed for use on: All pipe sizes B6300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal Submittal Sheets available
Add U after the model number (i.e., B6300U)

www.pipeshields.com/b6300 63
Pipe
Shields Heavy Duty,
Inc. Model B7000 Laterally Restrained Insulated Pipe Support Base Mounted

B7000
E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP C 6"
STEEL MOUNTING PLATE

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B7100 - For greater axial travel, see: B8000 - For lateral travel, see: B5000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 125 4 3.5 3.25 4 4 4.375 4 4.5 5.375 4 6 7 6 6.5 8 6 8.5 10 8 10 12.125
3/4 155 4 3.5 3.25 4 4 4.375 4 4.5 5.375 4 6 7 6 6.5 8 6 8.5 10 8 10 12.125
1 200 4 4 3.875 4 4.5 4.875 4 5 5.937 4 6 7 6 6.5 8 6 8.5 10 8 10 12.25
1 1/2 290 4 4 4.375 4 4.5 5.5 4 6 7 4 6.5 8 6 7.5 9 6 9.5 11.25 8 11 13.25
2 335 4 4.5 5 4 5 6.0625 4 6 7 4 6.5 8 6 7.5 9.125 6 9.5 11.25 8 11 13.25
2 1/2 410 4 4.5 5.5 4 6 7.125 4 6.5 8.125 4 7.5 9.125 6 8.5 10.125 6 10 12.25 8 11.5 14.5
3 475 4 6.5 6.062 4 7.5 7.125 4 8 8.125 4 9 9.125 6 10 10.125 6 11.5 12.375 8 13 14.625
4 750 4 7.5 7.25 4 8 8.25 4 9 9.25 4 10 10.25 6 11 11.375 6 12.5 13.375 8 14 15.625
5 940 4 8 8.25 4 9 9.25 4 10 10.25 4 11 11.375 6 11.5 12.375 6 13 14.875 8 14.5 16.875
6 1140 4 9 9.25 4 10 10.25 4 11 11.375 4 11.5 12.625 6 12.5 13.625 6 14 15.875 8 15.5 17.875
8 1500 4 11 11.625 4 11.5 12.625 4 12.5 13.625 6 13 14.875 6 14 15.875 6 15.5 17.875 8 16.5 20.125
10 1800 4 13.5 13.625 4 14 14.875 4 15 15.875 6 15.5 16.875 6 16.5 18.125 6 17.5 20.125 8 19 22.125
12 1950 4 15 16.125 4 15.5 17.125 4 16.5 18.125 6 17 19.125 6 17.5 20.125 6 19 22.125 8 20.5 24.125
14 2250 4 16 17.125 4 17 18.125 4 17.5 19.125 6 18 20.125 6 19 21.125 6 20.5 23.125 8 21.5 25.125
16 2600 4 17.5 19.125 4 18 20.125 6 19 21.375 6 19.5 22.375 6 20.5 23.375 8 21.5 25.375 8 23 27.375
18 2850 4 19.5 21.375 4 20 22.375 6 21 23.375 6 21.5 24.375 6 22 25.375 8 23.5 27.375 8 25 29.375
20 3050 4 21 23.375 4 21.5 24.375 6 22 25.375 6 23 26.375 6 23.5 27.375 8 25 29.375 8 26.5 31.375
24 3200 4 24 27.375 4 25 28.375 6 25.5 29.375 6 26.5 30.375 6 27 31.375 8 28.5 33.375 8 30 35.375
30 4200 4 29.5 33.625 6 30 34.625 6 31 35.625 6 31.5 36.625 6 32 37.625 8 33.5 39.625 8 35 41.625
36 4900 4 34 39.625 6 35 41.125 6 35.5 42.125 6 36 43.125 6 37 44.125 8 38.5 46.125 8 40 48.125
42 5550 4 39 46.125 6 39.5 47.125 6 40.5 48.125 6 41 49.125 6 41.5 50.125 8 43 52.125 8 44.5 54.125

Application: Features: Material Data:

Model B7000 is designed for use on: All pipe sizes B7000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized Steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal Submittal Sheets available
Add U after the model number (i.e., B7000U)

64 www.pipeshields.com/b7000
Pipe
Heavy Duty, Shields
Model B7100 Laterally Restrained Insulated Pipe Support Base Mounted Inc.

B7000
E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP C 6"
STEEL MOUNTING PLATE

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B7200 - For lateral restraint, see: B8100 - For minimal lateral travel, see: B5100.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 250 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.125
3/4 310 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.25
1 400 4 5.5 3.875 4 6 5 4 6.5 6.062 4 7.5 7 6 8 8 6 10 10 8 11.5 12.25
1 1/2 580 4 5.5 4.5 4 6 5.5 4 7.5 7.125 4 8 8.125 6 9 9.125 6 11 11.25 8 12.5 13.25
2 670 4 6 5 4 6.5 6.0625 4 7.5 7.125 4 8 8.125 6 9 9.125 6 11 11.25 8 12.5 13.25
2 1/2 820 4 6.5 5.5 4 8 7.125 4 8.5 8.125 4 9.5 9.125 6 10.5 10.125 6 12 12.25 8 13.5 14.5
3 950 4 7 6.187 4 8 7.125 4 8.5 8.125 4 9.5 9.125 6 10.5 10.125 6 12 12.375 8 13.5 14.625
4 1500 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 1880 4 9.5 8.5 4 10.5 9.5 4 11.5 10.5 4 12.5 11.625 6 13 12.625 6 14.5 14.875 8 16 16.875
6 2280 4 10 9.5 4 11 10.5 4 12 11.625 4 12.5 12.625 6 13.5 13.625 6 15 15.875 8 16.5 17.875
8 3000 4 13 11.625 4 13.5 12.625 4 14.5 13.625 6 15 14.875 6 16 15.875 6 17.5 18.125 8 18.5 20.125
10 3600 4 14.5 13.875 4 15 15.125 4 16 16.125 6 16.5 17.125 6 17.5 18.125 6 18.5 20.125 8 20 22.125
12 3900 4 16.5 16.125 4 17 17.125 4 18 18.125 6 18.5 19.125 6 19 20.125 6 20.5 22.125 8 22 24.125
14 4500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 5200 4 19 19.375 4 19.5 20.375 6 20.5 21.375 6 21 22.375 6 22 23.375 8 23 25.375 8 24.5 27.375
18 5700 4 21 21.375 4 21.5 22.375 6 22.5 23.375 6 23 24.375 6 23.5 25.375 8 25 27.375 8 26.5 29.375
20 6100 4 22.5 23.375 4 23 24.375 6 23.5 25.375 6 24.5 26.375 6 25 27.375 8 26.5 29.375 8 28 31.375
24 6400 4 25.5 27.375 4 26.5 28.375 6 27 29.375 6 28 30.375 6 28.5 31.375 8 30 33.375 8 31.5 35.375
30 8400 4 31.5 33.625 6 32 34.625 6 33 35.625 6 33.5 36.625 6 34 37.625 8 35.5 39.625 8 37 41.625
36 9800 4 36 40.125 6 37 41.125 6 37.5 42.125 6 38 43.125 6 39 44.125 8 40.5 46.125 8 42 48.125
42 11100 4 41.5 46.125 6 42 47.125 6 43 48.125 6 43.5 49.125 6 44 50.125 8 45.5 52.125 8 47 54.125

Application: Features: Material Data:

Model B7100 is designed for use on: All pipe sizes B7100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B7100U)

www.pipeshields.com/b7100 65
Pipe
Shields Heavy Duty,
Inc. Model B7200 Laterally Restrained Insulated Pipe Support Base Mounted

B7000
E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP C 6"
STEEL MOUNTING PLATE

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B7300 - For greater axial travel, see: B8200 - For lateral travel, see: B5200.
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 375 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.125
3/4 465 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.25
1 600 4 5.5 4 4 6 5 4 6.5 6.062 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
1 1/2 870 4 6 4.5 4 6.5 5.5 4 8 7.125 4 8.5 8.125 6 9.5 9.125 6 11.5 11.25 8 13 13.25
2 1005 4 7 5 4 7.5 6.1875 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1230 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1425 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 2250 4 9.5 7.25 4 10 8.25 4 11 9.25 4 12 10.25 6 13 11.375 6 14.5 13.375 8 16 15.625
5 2820 4 12.5 8.5 4 13 9.5 4 14.5 10.5 4 16 11.625 6 17 12.625 6 19 14.875 8 20.5 16.875
6 3420 4 12 9.5 4 13.5 10.5 4 15 11.625 4 16 12.625 6 17.5 13.625 6 18.5 15.875 8 20.5 17.875
8 4500 4 16 11.625 4 17 12.625 4 18.5 13.625 6 19 14.875 6 20 15.875 6 21.5 18.125 8 23 20.125
10 5400 4 19 13.875 4 19.5 15.125 4 20.5 16.125 6 21 17.125 6 22 18.125 6 23.5 20.125 8 25.5 22.125
12 5850 4 21 16.125 4 21.5 17.125 4 22.5 18.125 6 23.5 19.125 6 24 20.125 6 26 22.125 8 27.5 24.125
14 6750 4 22 17.125 4 23 18.125 4 24 19.125 6 24.5 20.125 6 25.5 21.125 6 27.5 23.125 8 28.5 25.125
16 7800 4 23.5 19.375 4 24 20.375 6 25 21.375 6 26 22.375 6 27 23.375 8 28 25.375 8 29 27.375
18 8550 4 25.5 21.375 4 26.5 22.375 6 27.5 23.375 6 28 24.375 6 28.5 25.375 8 29.5 27.375 8 31 29.375
20 9150 4 28 23.375 4 28.5 24.375 6 29 25.375 6 29.5 26.375 6 30 27.375 8 31.5 29.375 8 33 31.375
24 9600 4 31 27.375 4 32 28.375 6 32.5 29.375 6 33 30.375 6 34 31.375 8 35.5 33.375 8 37 35.375
30 12600 4 37 33.625 6 38 34.625 6 38.5 35.625 6 39.5 36.625 6 40.5 37.625 8 42 39.625 8 43.5 41.625
36 14700 4 43 40.125 6 43.5 41.125 6 44.5 42.125 6 45.5 43.125 6 46 44.125 8 47.5 46.125 8 49.5 48.125
42 16650 4 49 46.125 6 50 47.125 6 51 48.125 6 51.5 49.125 6 52.5 50.125 8 54 52.125 8 55.5 54.125

Application: Features: Material Data:

Model B7200 is designed for use on: All pipe sizes B7200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat Surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal Submittal Sheets available
Add U after the model number (i.e., B7200U)

66 www.pipeshields.com/b7200
Pipe
Heavy Duty,
Shields
Model B7300 Laterally Restrained Insulated Pipe Support Base Mounted
Inc.
B7000
E 9"

PIPE 1 1/2" MAX.


AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP C 6"
STEEL MOUNTING PLATE

POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For greater axial travel, see: B8300 - For lateral travel, see: B5300.
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 500 4 5 3.375 4 5.5 4.5 4 6 5.5 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
3/4 620 4 5 3.375 4 5.5 4.5 4 6 5.5 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
1 800 4 5.5 4 4 6 5 4 6.5 6.062 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
1 1/2 1160 4 6 4.5 4 6.5 5.5 4 8 7.125 4 8.5 8.125 6 9.5 9.125 6 11.5 11.25 8 13 13.25
2 1340 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1640 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
3 1900 4 8 6.187 4 9 7.125 4 9.5 8.125 4 10.5 9.125 6 11.5 10.125 6 13 12.375 8 14.5 14.625
4 3000 4 10 7.25 4 10.5 8.25 4 11.5 9.25 4 12.5 10.25 6 13.5 11.375 6 15 13.375 8 16.5 15.625
5 3760 4 13 8.5 4 13.5 9.5 4 15 10.5 4 16.5 11.625 6 17.5 12.625 6 19.5 14.875 8 21 16.875
6 4560 4 13 9.5 4 14.5 10.5 4 16 11.625 4 17 12.625 6 18.5 13.625 6 19.5 15.875 8 21.5 17.875
8 6000 4 17 11.625 4 18 12.625 4 19.5 13.625 6 20 14.875 6 21 15.875 6 22.5 18.125 8 24 20.125
10 7200 4 20 13.875 4 20.5 15.125 4 21.5 16.125 6 22 17.125 6 23 18.125 6 24.5 20.125 8 26.5 22.125
12 7800 4 21.5 16.125 4 22 17.125 4 23 18.125 6 24 19.125 6 24.5 20.125 6 26.5 22.125 8 28 24.375
14 9000 4 22.5 17.125 4 23.5 18.125 4 24.5 19.125 6 25 20.125 6 26 21.125 6 28 23.375 8 29 25.375
16 10400 4 24.5 19.375 4 25 20.375 6 26 21.375 6 27 22.375 6 28 23.375 8 29 25.375 8 30 27.375
18 11400 4 26.5 21.375 4 27.5 22.375 6 28.5 23.375 6 29 24.375 6 29.5 25.375 8 30.5 27.375 8 32 29.375
20 12200 4 29 23.375 4 29.5 24.375 6 30 25.375 6 30.5 26.375 6 31 27.375 8 32.5 29.375 8 34 31.375
24 12800 4 31.5 27.375 4 32.5 28.375 6 33 29.375 6 33.5 30.375 6 34.5 31.375 8 36 33.625 8 37.5 35.625
30 16800 4 37.5 33.625 6 38.5 34.625 6 39 35.625 6 40 37.125 6 41 38.125 8 42.5 40.125 8 44 42.125
36 19600 4 44 40.125 6 44.5 41.125 6 45.5 42.125 6 46.5 43.125 6 47 44.125 8 48.5 46.125 8 50.5 48.125
42 22200 4 50 46.125 6 51 47.125 6 52 48.125 6 52.5 49.125 6 53.5 50.125 8 55 52.125 8 56.5 54.125

Application: Features: Material Data:

Model B7300 is designed for use on: All pipe sizes B7300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B7300U)

www.pipeshields.com/b7300 67
Pipe
Shields Heavy Duty,
Inc. Model B8000 Laterally Restrained Insulated Pipe Support Base Mounted

B8000
E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP STEEL MOUNTING PLATE
C 12"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B8100 - For lateral travel, see: B6000.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 125 4 3.5 3.25 4 4 4.375 4 4.5 5.375 4 6 7 6 6.5 8 6 8.5 10 8 10 12.125
3/4 155 4 3.5 3.25 4 4 4.375 4 4.5 5.375 4 6 7 6 6.5 8 6 8.5 10 8 10 12.125
1 200 4 4 3.875 4 4.5 4.875 4 5 5.937 4 6 7 6 6.5 8 6 8.5 10 8 10 12.25
1 1/2 290 4 4 4.375 4 4.5 5.5 4 6 7 4 6.5 8 6 7.5 9 6 9.5 11.25 8 11 13.25
2 335 4 4.5 5 4 5 6.0625 4 6 7 4 6.5 8 6 7.5 9.125 6 9.5 11.25 8 11 13.25
2 1/2 410 4 4.5 5.5 4 6 7.125 4 6.5 8.125 4 7.5 9.125 6 8.5 10.125 6 10 12.25 8 11.5 14.5
3 475 4 6.5 6.062 4 7.5 7.125 4 8 8.125 4 9 9.125 6 10 10.125 6 11.5 12.375 8 13 14.625
4 750 4 7.5 7.25 4 8 8.25 4 9 9.25 4 10 10.25 6 11 11.375 6 12.5 13.375 8 14 15.625
5 940 4 8 8.25 4 9 9.25 4 10 10.25 4 11 11.375 6 11.5 12.375 6 13 14.875 8 14.5 16.875
6 1140 4 9 9.25 4 10 10.25 4 11 11.375 4 11.5 12.625 6 12.5 13.625 6 14 15.875 8 15.5 17.875
8 1500 4 11 11.625 4 11.5 12.625 4 12.5 13.625 6 13 14.875 6 14 15.875 6 15.5 17.875 8 16.5 20.125
10 1800 4 13.5 13.625 4 14 14.875 4 15 15.875 6 15.5 16.875 6 16.5 18.125 6 17.5 20.125 8 19 22.125
12 1950 4 15 16.125 4 15.5 17.125 4 16.5 18.125 6 17 19.125 6 17.5 20.125 6 19 22.125 8 20.5 24.125
14 2250 4 16 17.125 4 17 18.125 4 17.5 19.125 6 18 20.125 6 19 21.125 6 20.5 23.125 8 21.5 25.125
16 2600 4 17.5 19.125 4 18 20.125 6 19 21.375 6 19.5 22.375 6 20.5 23.375 8 21.5 25.375 8 23 27.375
18 2850 4 19.5 21.375 4 20 22.375 6 21 23.375 6 21.5 24.375 6 22 25.375 8 23.5 27.375 8 25 29.375
20 3050 4 21 23.375 4 21.5 24.375 6 22 25.375 6 23 26.375 6 23.5 27.375 8 25 29.375 8 26.5 31.375
24 3200 4 24 27.375 4 25 28.375 6 25.5 29.375 6 26.5 30.375 6 27 31.375 8 28.5 33.375 8 30 35.375
30 4200 4 29.5 33.625 6 30 34.625 6 31 35.625 6 31.5 36.625 6 32 37.625 8 33.5 39.625 8 35 41.625
36 4900 4 34 39.625 6 35 41.125 6 35.5 42.125 6 36 43.125 6 37 44.125 8 38.5 46.125 8 40 48.125
42 5550 4 39 46.125 6 39.5 47.125 6 40.5 48.125 6 41 49.125 6 41.5 50.125 8 43 52.125 8 44.5 54.125

Application: Features: Material Data:

Model B8000 is designed for use on: All pipe sizes B8000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal Submittal Sheets available
Add U after the model number (i.e., B8000U)

68 www.pipeshields.com/b8000
Pipe
Heavy Duty,
Shields
Model B8100 Laterally Restrained Insulated Pipe Support Base Mounted
Inc.

B8000
E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP STEEL MOUNTING PLATE
C 12"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B8200 - For lateral travel, see: B6100.

Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 250 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.125
3/4 310 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.25
1 400 4 5.5 3.875 4 6 5 4 6.5 6.062 4 7.5 7 6 8 8 6 10 10 8 11.5 12.25
1 1/2 580 4 5.5 4.5 4 6 5.5 4 7.5 7.125 4 8 8.125 6 9 9.125 6 11 11.25 8 12.5 13.25
2 670 4 6 5 4 6.5 6.0625 4 7.5 7.125 4 8 8.125 6 9 9.125 6 11 11.25 8 12.5 13.25
2 1/2 820 4 6.5 5.5 4 8 7.125 4 8.5 8.125 4 9.5 9.125 6 10.5 10.125 6 12 12.25 8 13.5 14.5
3 950 4 7 6.187 4 8 7.125 4 8.5 8.125 4 9.5 9.125 6 10.5 10.125 6 12 12.375 8 13.5 14.625
4 1500 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 1880 4 9.5 8.5 4 10.5 9.5 4 11.5 10.5 4 12.5 11.625 6 13 12.625 6 14.5 14.875 8 16 16.875
6 2280 4 10 9.5 4 11 10.5 4 12 11.625 4 12.5 12.625 6 13.5 13.625 6 15 15.875 8 16.5 17.875
8 3000 4 13 11.625 4 13.5 12.625 4 14.5 13.625 6 15 14.875 6 16 15.875 6 17.5 18.125 8 18.5 20.125
10 3600 4 14.5 13.875 4 15 15.125 4 16 16.125 6 16.5 17.125 6 17.5 18.125 6 18.5 20.125 8 20 22.125
12 3900 4 16.5 16.125 4 17 17.125 4 18 18.125 6 18.5 19.125 6 19 20.125 6 20.5 22.125 8 22 24.125
14 4500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 5200 4 19 19.375 4 19.5 20.375 6 20.5 21.375 6 21 22.375 6 22 23.375 8 23 25.375 8 24.5 27.375
18 5700 4 21 21.375 4 21.5 22.375 6 22.5 23.375 6 23 24.375 6 23.5 25.375 8 25 27.375 8 26.5 29.375
20 6100 4 22.5 23.375 4 23 24.375 6 23.5 25.375 6 24.5 26.375 6 25 27.375 8 26.5 29.375 8 28 31.375
24 6400 4 25.5 27.375 4 26.5 28.375 6 27 29.375 6 28 30.375 6 28.5 31.375 8 30 33.375 8 31.5 35.375
30 8400 4 31.5 33.625 6 32 34.625 6 33 35.625 6 33.5 36.625 6 34 37.625 8 35.5 39.625 8 37 41.625
36 9800 4 36 40.125 6 37 41.125 6 37.5 42.125 6 38 43.125 6 39 44.125 8 40.5 46.125 8 42 48.125
42 11100 4 41.5 46.125 6 42 47.125 6 43 48.125 6 43.5 49.125 6 44 50.125 8 45.5 52.125 8 47 54.125

Application: Features: Material Data:

Model B8100 is designed for use on: All pipe sizes B8100: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized Steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon Steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat Surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE Optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B8100U)

www.pipeshields.com/b8100 69
Pipe
Shields Heavy Duty,
Inc. Model B8200 Laterally Restrained Insulated Pipe Support Base Mounted

B8000
E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP STEEL MOUNTING PLATE
C 12"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: B8300 - For lateral travel, see: B6200.
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 375 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.125
3/4 465 4 5 3.25 4 5.5 4.375 4 6 5.375 4 7.5 7 6 8 8 6 10 10 8 11.5 12.25
1 600 4 5.5 4 4 6 5 4 6.5 6.062 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
1 1/2 870 4 6 4.5 4 6.5 5.5 4 8 7.125 4 8.5 8.125 6 9.5 9.125 6 11.5 11.25 8 13 13.25
2 1005 4 7 5 4 7.5 6.1875 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1230 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1425 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 2250 4 9.5 7.25 4 10 8.25 4 11 9.25 4 12 10.25 6 13 11.375 6 14.5 13.375 8 16 15.625
5 2820 4 12.5 8.5 4 13 9.5 4 14.5 10.5 4 16 11.625 6 17 12.625 6 19 14.875 8 20.5 16.875
6 3420 4 12 9.5 4 13.5 10.5 4 15 11.625 4 16 12.625 6 17.5 13.625 6 18.5 15.875 8 20.5 17.875
8 4500 4 16 11.625 4 17 12.625 4 18.5 13.625 6 19 14.875 6 20 15.875 6 21.5 18.125 8 23 20.125
10 5400 4 19 13.875 4 19.5 15.125 4 20.5 16.125 6 21 17.125 6 22 18.125 6 23.5 20.125 8 25.5 22.125
12 5850 4 21 16.125 4 21.5 17.125 4 22.5 18.125 6 23.5 19.125 6 24 20.125 6 26 22.125 8 27.5 24.125
14 6750 4 22 17.125 4 23 18.125 4 24 19.125 6 24.5 20.125 6 25.5 21.125 6 27.5 23.125 8 28.5 25.125
16 7800 4 23.5 19.375 4 24 20.375 6 25 21.375 6 26 22.375 6 27 23.375 8 28 25.375 8 29 27.375
18 8550 4 25.5 21.375 4 26.5 22.375 6 27.5 23.375 6 28 24.375 6 28.5 25.375 8 29.5 27.375 8 31 29.375
20 9150 4 28 23.375 4 28.5 24.375 6 29 25.375 6 29.5 26.375 6 30 27.375 8 31.5 29.375 8 33 31.375
24 9600 4 31 27.375 4 32 28.375 6 32.5 29.375 6 33 30.375 6 34 31.375 8 35.5 33.375 8 37 35.375
30 12600 4 37 33.625 6 38 34.625 6 38.5 35.625 6 39.5 36.625 6 40.5 37.625 8 42 39.625 8 43.5 41.625
36 14700 4 43 40.125 6 43.5 41.125 6 44.5 42.125 6 45.5 43.125 6 46 44.125 8 47.5 46.125 8 49.5 48.125
42 16650 4 49 46.125 6 50 47.125 6 51 48.125 6 51.5 49.125 6 52.5 50.125 8 54 52.125 8 55.5 54.125

Application: Features: Material Data:

Model B8200 is designed for use on: All pipe sizes B8200: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat Surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal Submittal Sheets available
Add U after the model number (i.e., B8200U)

70 www.pipeshields.com/b8200
Pipe
Heavy Duty, Shields
Model B8300 Laterally Restrained Insulated Pipe Support Base Mounted Inc.

B8000
E 15"

PIPE
4 1/2" MAX.
AXIAL TRAVEL

B.O.P.

T.O.S.

4"
1/8" CLR
TYP STEEL MOUNTING PLATE
C 12"
POLYETHYLENE SLIDE PAD

4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. If lateral load is greater than 50% of actual vertical load, contact factory. Available
in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - For lateral travel, see: B6300.
Pipe Vert. Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 500 4 5 3.375 4 5.5 4.5 4 6 5.5 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
3/4 620 4 5 3.375 4 5.5 4.5 4 6 5.5 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
1 800 4 5.5 4 4 6 5 4 6.5 6.062 4 7.5 7.125 6 8 8.125 6 10 10.125 8 11.5 12.25
1 1/2 1160 4 6 4.5 4 6.5 5.5 4 8 7.125 4 8.5 8.125 6 9.5 9.125 6 11.5 11.25 8 13 13.25
2 1340 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1640 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
3 1900 4 8 6.187 4 9 7.125 4 9.5 8.125 4 10.5 9.125 6 11.5 10.125 6 13 12.375 8 14.5 14.625
4 3000 4 10 7.25 4 10.5 8.25 4 11.5 9.25 4 12.5 10.25 6 13.5 11.375 6 15 13.375 8 16.5 15.625
5 3760 4 13 8.5 4 13.5 9.5 4 15 10.5 4 16.5 11.625 6 17.5 12.625 6 19.5 14.875 8 21 16.875
6 4560 4 13 9.5 4 14.5 10.5 4 16 11.625 4 17 12.625 6 18.5 13.625 6 19.5 15.875 8 21.5 17.875
8 6000 4 17 11.625 4 18 12.625 4 19.5 13.625 6 20 14.875 6 21 15.875 6 22.5 18.125 8 24 20.125
10 7200 4 20 13.875 4 20.5 15.125 4 21.5 16.125 6 22 17.125 6 23 18.125 6 24.5 20.125 8 26.5 22.125
12 7800 4 21.5 16.125 4 22 17.125 4 23 18.125 6 24 19.125 6 24.5 20.125 6 26.5 22.125 8 28 24.375
14 9000 4 22.5 17.125 4 23.5 18.125 4 24.5 19.125 6 25 20.125 6 26 21.125 6 28 23.375 8 29 25.375
16 10400 4 24.5 19.375 4 25 20.375 6 26 21.375 6 27 22.375 6 28 23.375 8 29 25.375 8 30 27.375
18 11400 4 26.5 21.375 4 27.5 22.375 6 28.5 23.375 6 29 24.375 6 29.5 25.375 8 30.5 27.375 8 32 29.375
20 12200 4 29 23.375 4 29.5 24.375 6 30 25.375 6 30.5 26.375 6 31 27.375 8 32.5 29.375 8 34 31.375
24 12800 4 31.5 27.375 4 32.5 28.375 6 33 29.375 6 33.5 30.375 6 34.5 31.375 8 36 33.625 8 37.5 35.625
30 16800 4 37.5 33.625 6 38.5 34.625 6 39 35.625 6 40 37.125 6 41 38.125 8 42.5 40.125 8 44 42.125
36 19600 4 44 40.125 6 44.5 41.125 6 45.5 42.125 6 46.5 43.125 6 47 44.125 8 48.5 46.125 8 50.5 48.125
42 22200 4 50 46.125 6 51 47.125 6 52 48.125 6 52.5 49.125 6 53.5 50.125 8 55 52.125 8 56.5 54.125

Application: Features: Material Data:

Model B8300 is designed for use on: All pipe sizes B8300: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Stainless steel to UHMW polyethylene slide asbestos free, treated with water repellant
Intended for installation on: Steel Straps/Base: Carbon steel ASTM A-36
Other I.D.s and/or O.D.s available on request
Flat surfaces Fasteners: ASTM A-307 plated
Factory mounted polyethylene slide pad on steel
Slide Pad: UHMW Polyethylene (PTFE optional)
mounting plate
Temperature Range: Coating: Primer coated or hot dipped galvanized
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request
Note: Up to 1800F available upon request. Performance test results on file:
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Formal submittal sheets available
Add U after the model number (i.e., B8300U)

www.pipeshields.com/b8300 71
Pipe
Shields
Inc. Introduction: Section C

INTRODUCTION
SECTION C

PIPE ANCHORS

APPLICATION Heavy Industrial and Large HVAC Distribution Systems

TYPES Welded and Insulated

Note: These anchors have been designed to provide dimensional compatibility with the base
mounted supports in Section B.

Models C1000 Welded Tee Anchor for carbon steel pipe sizes 3 to 6. See Product
Data Sheet for model numbers used with other pipe materials.

Models C1100 Welded Tee No Moment Anchor for carbon steel pipe sizes 3 to 6.
No weld required to sub-structure. See Product Data Sheet for model numbers
used with other pipe materials.

Models C2000 Welded Anchor similar to C1000 except for 8 pipe and larger.

Models C2100 Welded No Moment Anchor similar to C1100 except for 8 pipe and larger.

Models C3000 - C3300 Friction Anchors for relatively light axial forces and infrequent thermal
cycling. The higher the model number in this series, the higher the load rating.

Models C4000 - C4300 Insulated Positive Anchors for heavy axial forces. The higher the model
number in this series, the higher the load rating.

If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
707-447-5014 or 1-800-538-7007.

Please acquaint yourself with the selection guide at the front of this catalog and the section index
on the page following this introduction, for assistance in determining the most appropriate support
for your application.

72
Pipe
Shields
Section C Index Inc.

WELDED PIPE ANCHORS


PIPE FIELD
AXIAL LOAD
SIZE WELD TO ROTATIONAL
C1000 CAPACITY
MODEL RANGE INSULATION PIPE RESTRAINT

C1100
C1000 3-6 NO YES YES HEAVIEST

3-6 NO YES NO HEAVIEST


C2000 C1100

YES
C2000 8 - 30 NO YES HEAVIEST
C2100

C3000
8 - 30 NO YES NO HEAVIEST
C2100

C3000 1/2 - 42 YES NO NO LIGHTEST


C3100 1/2 - 42 YES NO NO LIGHTER
C3200 1/2 - 42 YES NO NO LIGHT
C4000 C3300 1/2 - 42 YES NO NO MED/LIGHT

C4000 1 - 42 YES YES NO LIGHTEST


C4100 1 - 42 YES YES NO LIGHTER
C4200 1 - 42 YES YES NO LIGHT
C4300 1 - 42 YES YES NO MED/LIGHT

TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 4 IPS
3. Insulation Thickness 2
4. Model Number C1000

EXAMPLE: (20) 4 x 2 C1000

www.pipeshields.com/c-series 73
Pipe
Shields Model C1000, Model C1010,
Inc. Model C1020, Model C1030 Welded Tee Pipe Anchor Small Bore
C1000

1/4"
"D" DIA.
B
(4) HOLES

C 1/4" 4"

A 6"

Dimensions and ratings are subject to change without notice.


Available in all insulation thickness.
Note:
For no moment anchor, see: C1100
For insulated friction anchor, see: C3000
For large bore welded anchor, see: C2000
For insulated positive anchor, see: C4000

Insulation Thickness
Pipe 1" 2" 3" 4" 5" 6" 7"
Size A C D B B B B B B B
3 3 1.75 0.56 4 4 6 6 8 8 10
3.5 3.5 2.25 0.56 4 4 6 6 8 8 10
4 4 2.75 0.56 4 4 6 6 8 8 10
5 5 3.5 0.69 4 4 6 6 8 8 10
6 6 4.5 0.69 4 4 6 6 8 8 10

Application: Features: Material Data:

Model C1000 and C1030 are designed for use on: Supplied with bolt holes for choice of bolting or C1000: A36 Carbon Steel.
Pipe Sizes through 6 welding to support structure.
C1010: A387 Gr. 22 Chrome-Moly Steel.
Model No. For use with Pipe Material Bottom-of-pipe to top-of-steel matches base
mounted insulated supports. See B Series.
C1020: A515 Gr. 70 Carbon Silicon Steel.
C1000 Carbon Steel
Broad selection of materials to match pipe
C1010 Chrome-Moly
material and eliminate galvanic action. C1030: 304L Stainless Steel.
C1020 Carbon Silicon
C1030 Stainless
Primer Coating: Primer coated or
hot dipped galvanized. Other coatings
available upon request.

Other materials available upon request.


Formal submittal sheets available.

74 www.pipeshields.com/c1000
Pipe
Model C1100, Model C1110, Shields
Model C1120, Model C1130 Welded C1100
Tee Pipe Anchor Small Bore Inc.

1/4"
B

1/4"

A 6"

Dimensions and ratings are subject to change without notice.


Available in all insulation thickness.
Note:
For welded anchor, see: C1000
For insulated friction anchor, see: C3000
For large bore welded anchor, see: C2100
For insulated positive anchor, see: C4000

Insulation Thickness
Pipe 1" 2" 3" 4" 5" 6" 7"
Size A B B B B B B B
3 3 4 4 6 6 8 8 10
3.5 3.5 4 4 6 6 8 8 10
4 4 4 4 6 6 8 8 10
5 5 4 4 6 6 8 8 10
6 6 4 4 6 6 8 8 10

Application: Features: Material Data:

Model C1100 and C1130 are designed for use on: Supplied with bolt holes for choice of bolting or C1100: A36 Carbon Steel.
Pipe Sizes through 6 welding to support structure.
C1110: A387 Gr. 22 Chrome-Moly Steel.
Model No. For use with Pipe Material Bottom-of-pipe to top-of-steel matches base
mounted insulated supports. See B Series.
C1120: A515 Gr. 70 Carbon Silicon Steel.
C1100 Carbon Steel
Broad selection of materials to match pipe
C1110 Chrome-Moly
material and eliminate galvanic action. C1130: 304L Stainless Steel.
C1120 Carbon Silicon
C1130 Stainless
Primer Coating: Primer coated or
hot dipped galvanized. Other coatings
available upon request.

Other materials available upon request.


Formal submittal sheets available

www.pipeshields.com/c1100 75
Pipe
Shields Model C2000, Model C2010,
Inc. Model C2020, Model C2030 Welded Tee Pipe Anchor Large Bore
C2000

"D" DIA.
(4) HOLES

C G E

A F

Dimensions and ratings are subject to change without notice. Contact us for current information.
Available in all insulation thickness.

Note:
For small bore welded tee anchor, see: C1000
For large bore no moment anchor , see: C2100
For insulated friction anchor, see: C3000
For insulated positive anchor, see: C4000

Insulation Thickness
Pipe 1" 2" 3" 4" 5" 6" 7"
Size A C D E F G B B B B B B B
8 6 4 0.69 9 12 0.38 4 4 6 6 8 8 10
10 6 4 0.69 9 12 0.38 4 4 6 6 8 8 10
12 6 4 0.81 9 12 0.38 4 4 6 6 8 8 10
14 6 4 0.81 9 12 0.38 4 4 6 6 8 8 10
16 6 4 0.81 9 12 0.38 4 6 6 8 8 10 10
18 9 6.5 0.94 15 18 0.5 4 6 6 8 8 10 10
20 9 6.5 0.94 15 18 0.5 4 6 6 8 8 10 10
24 9 6.5 0.94 15 18 0.5 4 6 6 8 8 10 10
30 12 9 1.06 15 18 0.5 4 6 6 8 8 10 10

Application: Features: Material Data:

Model C2000 and C2030 are designed for use on: Supplied with bolt holes for choice of bolting or C2000: A36 Carbon Steel.
Pipe Sizes through 8 through 30 welding to support structure.
C2010: A387 Gr. 23 Chrome-Moly Steel.
Model No. For use with Pipe Material Bottom-of-pipe to top-of-steel matches base
mounted insulated supports. See B Series.
C2020: A515 Gr. 70 Carbon Silicon Steel.
C2000 Carbon Steel
Broad selection of materials to match pipe
C2010 Chrome-Moly
material and eliminate galvanic action. C2030: 304L Stainless Steel.
C2020 Carbon Silicon
C2030 Stainless Slots in central web for insulation banding.
Primer Coating: Primer coated or
hot dipped galvanized. Other coatings
available upon request.

Other materials available upon request.

Formal submittal sheets available

76 www.pipeshields.com/c2000
Pipe
Model C2100, Model C2110, Shields
Model C2120, Model C2130 Welded Tee Pipe Anchor Large Bore Inc.

C2100

A F

Dimensions and ratings are subject to change without notice.


Available in all insulation thickness.

Note:
For welded anchor, see: C2000
For small bore welded teeno moment anchor, see: C1100
For insulated friction anchor, see: C3000
For insulated positive anchor, see: C4000

Insulation Thickness
Pipe 1" 2" 3" 4" 5" 6" 7"
Size A F G B B B B B B B
8 6 12 0.38 4 4 6 6 8 8 10
10 6 12 0.38 4 4 6 6 8 8 10
12 6 12 0.38 4 4 6 6 8 8 10
14 6 12 0.38 4 4 6 6 8 8 10
16 6 12 0.38 4 6 6 8 8 10 10
18 9 18 0.5 4 6 6 8 8 10 10
20 9 18 0.5 4 6 6 8 8 10 10
24 9 18 0.5 4 6 6 8 8 10 10
30 12 18 0.5 4 6 6 8 8 10 10

Application: Features: Material Data:

Model C2100 and C2130 are designed for use on: Supplied with bolt holes for choice of bolting or C2100: A36 Carbon Steel.
Pipe Sizes through 8 through 30 welding to support structure.
C2110: A387 Gr. 11 Chrome-Moly Steel.
Model No. For use with Pipe Material Bottom-of-pipe to top-of-steel matches base
mounted insulated supports. See B Series.
C2120: A515 Gr. 70 Carbon Silicon Steel.
C2100 Carbon Steel
Broad selection of materials to match pipe
C2110 Chrome-Moly
material and eliminate galvanic action. C2130: 304L Stainless Steel.
C2120 Carbon Silicon
C2130 Stainless
Primer Coating: Primer coated or
hot dipped galvanized. Other coatings
available upon request.

Other materials available upon request.


Formal submittal sheets available

www.pipeshields.com/c2100 77
Pipe
Shields
Inc. Model C3000 Insulated Friction Pipe Anchor
C3000

E 9"

PIPE
B.O.P.

T.O.S.

C 6"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C3100, C4000.

Load Rating
Pipe Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4" Insul. Thk. = 5"
Size Vert. Lat. Axial
Lbs Lbs Lbs B C E B C E B C E B C E B C E B C E B C E
1/2 140 70 28 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 175 88 35 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
1 225 113 45 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 163 65 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25
2 375 188 75 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 230 92 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 530 265 106 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 840 420 168 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 1050 525 210 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875
6 1275 638 255 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 1700 850 340 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125
10 2000 1000 400 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125
12 2200 1100 440 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 2500 1250 500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 2900 1450 580 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 3200 1600 640 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 3400 1700 680 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 3600 1800 720 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 4700 2350 940 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 5500 2750 1100 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 6200 3100 1240 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model C3000 is designed for use on: All pipe sizes C3000: Applicable PSI spec. doc.: No. 209
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Where thermal cycle are infrequent asbestos-free, treated with water repellant
Other I.D.s and/or O.D.s available on request
Where axial forces are relatively light or in balance Steel Straps/Base: Carbon steel ASTM A-36
Bottom-of-pipe to top-of-shield matches insulated
Intended for installation on: Fasteners: ASTM A-307 plated
Flat Surfaces supports in B series
Coating: Primer coated or hot dipped galvanized
Performance test results on file: Other coatings available upon request
Temperature Range:
Standard: +40F to +1200F CalSil Insulation
Available upon request. Formal submittal sheets available
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., C3000U)

78 www.pipeshields.com/c3000
Pipe
Shields
Model C3100 Insulated Friction Pipe Anchor Inc.
C3000

E 9"

PIPE
B.O.P.

T.O.S.

C 6"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C3200, C4100.


Load Rating
Pipe Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4" Insul. Thk. = 5"
Size Vert. Lat. Axial
Lbs Lbs Lbs B C E B C E B C E B C E B C E B C E B C E
1/2 280 140 56 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 350 175 70 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 450 225 90 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 325 130 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 750 375 150 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 460 184 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1060 530 212 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 1680 840 336 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 2100 1050 420 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 2550 1275 510 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 3400 1700 680 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 4000 2000 800 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 4400 2200 880 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 5000 2500 1000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 5800 2900 1160 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 6400 3200 1280 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 6800 3400 1360 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 7200 3600 1440 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 9400 4700 1880 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 11000 5500 2200 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 12400 6200 2480 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model C3100 is designed for use on: All pipe sizes C3100: Applicable PSI spec. doc.: No. 209.
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant.
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653.
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Where thermal cycle are infrequent asbestos-free, treated with water repellant.
Other I.D.s and/or O.D.s available on request
Where axial forces are relatively light or in balance Steel Straps/Base: Carbon steel ASTM A-36.
Bottom-of-pipe to top-of-shield matches insulated
Fasteners: ASTM A-307 plated.
supports in B series
Intended for installation on: Coating: Primer coated or hot dipped galvanized.
Flat surfaces Performance test results on file: Other coatings available upon request.
Available upon request. Formal submittal sheets available
Temperature Range:
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., C3100U)

www.pipeshields.com/c3100 79
Pipe
Shields
Inc. Model C3200 Insulated Friction Pipe Anchor
C3000

E 9"

PIPE
B.O.P.

T.O.S.

C 6"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C3300, C4200.

Load Rating
Pipe Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4" Insul. Thk. = 5"
Size Vert. Lat. Axial
Lbs Lbs Lbs B C E B C E B C E B C E B C E B C E B C E
1/2 400 200 80 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 500 250 100 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 650 325 130 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 475 190 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1100 550 220 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 675 270 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1600 800 320 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 2500 1250 500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 3100 1550 620 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 3800 1900 760 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 5100 2550 1020 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 6000 3000 1200 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 6600 3300 1320 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 7500 3750 1500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 8700 4350 1740 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 9600 4800 1920 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 10200 5100 2040 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 10800 5400 2160 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 14100 7050 2820 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 16500 8250 3300 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 18600 9300 3720 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model C3200 is designed for use on: All pipe sizes C3200: Applicable PSI spec. doc.: No. 209.
Hot water Steam Insulation: Calcium Silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant.
Eliminates welding to pipe Jackets: Galvanized Steel ASTM A-653.
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Where thermal cycle are infrequent asbestos-free, treated with water repellant.
Other I.D.s and/or O.D.s available on request
Where axial forces are relatively light or in balance Steel Straps/Base: Carbon Steel ASTM A-36.
Bottom-of-pipe to top-of-shield matches insulated
Fasteners: ASTM A-307 plated.
Intended for installation on: supports in B series
Coating: Primer coated or hot dipped galvanized.
Flat surfaces
Performance test results on file: Other coatings available upon request.
Temperature Range:
Standard: +40F to +1200F CalSil Insulation
Available upon request. Formal submittal sheets available
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., C3200U)

80 www.pipeshields.com/c3200
Pipe
Shields
Model C3300 Insulated Friction Pipe Anchor Inc.
C3000

E 9"

PIPE
B.O.P.

T.O.S.

C 6"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C4300.

Load Rating
Pipe Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4" Insul. Thk. = 5"
Size Vert. Lat. Axial
Lbs Lbs Lbs B C E B C E B C E B C E B C E B C E B C E
1/2 550 275 110 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
3/4 700 350 140 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 900 450 180 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 650 260 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1500 750 300 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 900 360 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
3 2100 1050 420 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 3350 1675 670 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 4200 2100 840 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 5100 2550 1020 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 6800 3400 1360 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 8000 4000 1600 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 8800 4400 1760 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 10000 5000 2000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 11600 5800 2320 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 12800 6400 2560 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 13600 6800 2720 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 14400 7200 2880 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 18800 9400 3760 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 22000 11000 4400 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 24800 12400 4960 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125

Application: Features: Material Data:

Model C3300 is designed for use on: All pipe sizes C3300: Applicable PSI spec. doc.: No. 209.
Hot water Steam Insulation: Calcium silicate asbestos-free,
Easy installation
Cold water Air treated with water repellant.
Eliminates welding to pipe Jackets: Galvanized steel ASTM A-653.
Chilled water Gas
Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Dual temperature Vacuum
Insulating structural inserts for load transfer Structural Inserts: High-density calcium silicate
Where thermal cycle are infrequent asbestos-free, treated with water repellant.
Other I.D.s and/or O.D.s available on request
Where axial forces are relatively light or in balance Steel Straps/Base: Carbon Steel ASTM A-36.
Bottom-of-pipe to top-of-shield matches insulated
Fasteners: ASTM A-307 plated.
supports in B series
Intended for installation on: Coating: Primer coated or hot dipped galvanized.
Flat Surfaces Performance test results on file: Other coatings available upon request.

Temperature Range: Available upon request. Formal submittal sheets available


Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., C3300U)

www.pipeshields.com/c3300 81
Pipe
Shields Model C4000, Model C4010,
Inc. Model C4020, Model C4030 Insulated Positive Pipe Anchor
C4000

E 7"

PIPE
B.O.P.

B
T.O.S.

C 4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C4100.


If thrust plate thickness D is greater than pipe wall thickness, consult factory.

Load Rating
Pipe Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4"
Vert. Lat. Axial
Size
Lbs Lbs Lbs B C D E B C D E B C D E B C D E B C D E B C D E
1 200 100 410 4 2 0.1875 4.125 4 2.5 0.1875 5.125 4 3 0.25 6.187 4 4 0.25 7.25 6 4.5 0.25 8.25 6 6.5 0.25 10.25
1 1/2 290 145 590 4 2 0.1875 4.625 4 2.5 0.1875 5.625 4 4 0.25 7.25 4 4.5 0.25 8.25 6 5.5 0.25 9.25 6 7.5 0.25 11.375
2 360 180 730 4 2.5 0.1875 5.125 4 3 0.1875 6.1875 4 4 0.25 7.25 4 4.5 0.25 8.25 6 5.5 0.25 9.25 6 7.5 0.3125 11.375
2 1/2 440 220 890 4 2.5 0.1875 5.625 4 4 0.1875 7.25 4 4.5 0.25 8.25 4 5.5 0.25 9.25 6 6.5 0.25 10.25 6 8 0.3125 12.375
3 530 265 1400 4 3 0.1875 6.187 4 4 0.25 7.25 4 4.5 0.25 8.25 4 5.5 0.3125 9.25 6 6.5 0.3125 10.25 6 8 0.375 12.375
4 840 420 1730 4 4 0.1875 7.25 4 4.5 0.25 8.25 4 5.5 0.25 9.25 4 6.5 0.3125 10.25 6 7.5 0.3125 11.375 6 9 0.375 13.375
5 1050 525 2060 4 4.5 0.1875 8.25 4 5.5 0.25 9.25 4 6.5 0.25 10.25 4 7.5 0.3125 11.375 6 8 0.3125 12.375 6 9.5 0.375 14.625
6 1275 638 2400 4 5.5 0.1875 9.25 4 6.5 0.25 10.25 4 7.5 0.25 11.375 4 8 0.3125 12.375 6 9 0.3125 13.375 6 10.5 0.375 15.625
8 1700 850 3020 4 7.5 0.1875 11.375 4 8 0.25 12.375 4 9 0.25 13.375 6 9.5 0.3125 14.625 6 10.5 0.3125 15.625 6 12 0.375 17.625
10 2000 1000 3700 4 9 0.1875 13.625 4 9.5 0.25 14.875 4 10.5 0.25 15.875 6 11 0.3125 16.875 6 12 0.3125 17.875 6 13 0.375 19.875
12 2200 1100 4320 4 10.5 0.1875 15.625 4 11 0.25 16.875 4 12 0.25 17.875 6 12.5 0.3125 18.875 6 13 0.3125 19.875 6 14.5 0.375 21.875
14 2500 1250 4700 4 11 0.1875 16.625 4 12 0.25 17.875 4 12.5 0.25 18.875 6 13 0.3125 19.875 6 14 0.3125 20.875 6 15.5 0.375 22.875
16 2900 1450 5340 4 12.5 0.1875 18.625 4 13 0.25 19.875 6 14 0.25 20.875 6 14.5 0.3125 21.875 6 15.5 0.3125 22.875 8 16.5 0.375 24.875
18 3200 1600 5970 4 14 0.1875 20.625 4 14.5 0.25 21.875 6 15.5 0.25 22.875 6 16 0.3125 23.875 6 16.5 0.3125 24.875 8 18 0.375 26.875
20 3400 1700 6600 4 15.5 0.1875 22.625 4 16 0.25 23.875 6 16.5 0.25 24.875 6 17.5 0.3125 25.875 6 18 0.3125 26.875 8 19.5 0.375 28.875
24 3600 1800 7850 4 18 0.1875 26.625 4 19 0.25 27.875 6 19.5 0.25 28.875 6 20.5 0.3125 29.875 6 21 0.3125 30.875 8 22.5 0.375 32.875
30 4700 2350 9740 4 22.5 0.1875 33.125 6 23 0.25 34.125 6 24 0.25 35.125 6 24.5 0.3125 36.125 6 25 0.3125 37.125 8 26.5 0.375 39.125
36 5500 2750 11600 4 26.5 0.1875 39.125 6 27.5 0.25 40.125 6 28 0.25 41.125 6 28.5 0.3125 42.125 6 29.5 0.3125 43.125 8 31 0.375 45.125
42 6200 3100 13500 4 31 0.1875 45.125 6 31.5 0.25 46.125 6 32.5 0.25 47.125 6 33 0.3125 48.125 6 33.5 0.3125 49.125 8 35 0.375 51.125

Application: Features: Material Data:

Model C4000 through C4030 are designed for All pipe sizes C4000 - C4030: specification document: No. 209.
use on: Steel Inner Thrust Plates (supplied loose):
Easy installation
Hot water Steam Model ASTM For Pipe Material
Overlapping galvanized sheet metal jacket
Cold water Air C4000 A36 Carbon Steel
Insulating structural inserts for load transfer C4010 A387GR.22 Chrome-Moly
Chilled water Gas
Other I.D.s and/or O.D.s available on request C4020 A515GR.70 Carbon Silicon
Dual temperature Vacuum C4030 A304L Stainless Steel
Where large axial forces must be resisted Bottom-of-pipe to top-of-shield matches insulated
Structural Inserts: High-density calcium silicate.
supports in B series Asbestos-free, treated with water repellant.
Intended for installation on: Jackets: Galvanized Steel ASTM A-653.
Performance test results on file:
Flat Surfaces Steel Straps & Base: Carbon Steel ASTM A-36
Available upon request.
Glue: Industrial contact adhesive.
Temperature Range: Coating: Primer coated or hot dipped galvanized.
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request.
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Fasteners: ASTM A-307 plated.
Add U after the model number (i.e., C4000U)
Formal submittal sheets available

82 www.pipeshields.com/c4000
Pipe
Model C4100, Model C4110, Shields
Model C4120, Model C4130 Insulated Positive Pipe Anchor Inc.
C4000

E 7"

PIPE
B.O.P.

B
T.O.S.

C 4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C4200.


If thrust plate thickness D is greater than pipe wall thickness, consult factory.
Load Rating
Pipe Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4"
Vert. Lat. Axial
Size
Lbs Lbs Lbs B C D E B C D E B C D E B C D E B C D E
1 400 200 640 4 2.5 0.25 5.375 4 3 0.25 6.437 4 4 0.25 7.5 6 4.5 0.25 8.5 6 6.5 0.3125 10.5
1 1/2 580 290 930 4 2.5 0.25 5.875 4 4 0.25 7.5 4 4.5 0.3125 8.5 6 5.5 0.3125 9.5 6 7.5 0.3125 11.625
2 720 360 1160 4 3 0.25 6.4375 4 4 0.25 7.5 4 4.5 0.3125 8.5 6 5.5 0.3125 9.5 6 7.5 0.3125 11.625
2 1/2 870 435 1410 4 4 0.25 7.5 4 4.5 0.25 8.5 4 5.5 0.3125 9.5 6 6.5 0.3125 10.5 6 8 0.375 12.625
3 1060 530 2400 4 4 0.3125 7.5 4 4.5 0.3125 8.5 4 5.5 0.375 9.5 6 6.5 0.375 10.5 6 8 0.5 12.625
4 1680 840 2900 4 4.5 0.3125 8.5 4 5.5 0.3125 9.5 4 6.5 0.375 10.5 6 7.5 0.375 11.625 6 9 0.5 13.625
5 2100 1050 3400 4 5.5 0.3125 9.5 4 6.5 0.3125 10.5 4 7.5 0.375 11.625 6 8 0.375 12.625 6 9.5 0.5 14.875
6 2550 1275 3900 4 6.5 0.3125 10.5 4 7.5 0.3125 11.625 4 8 0.375 12.625 6 9 0.375 13.625 6 10.5 0.5 15.875
8 3400 1700 4850 4 8 0.3125 12.625 4 9 0.3125 13.625 6 9.5 0.375 14.875 6 10.5 0.375 15.875 6 12 0.5 17.875
10 4000 2000 5850 4 9.5 0.3125 15.125 4 10.5 0.3125 16.125 6 11 0.375 17.125 6 12 0.375 18.125 6 13 0.5 20.125
12 4400 2200 6800 4 11 0.3125 17.125 4 12 0.3125 18.125 6 12.5 0.375 19.125 6 13 0.375 20.125 6 14.5 0.5 22.125
14 5000 2500 7350 4 12 0.3125 18.125 4 12.5 0.3125 19.125 6 13 0.375 20.125 6 14 0.375 21.125 6 15.5 0.5 23.125
16 5800 2900 8320 4 13 0.3125 20.125 6 14 0.3125 21.125 6 14.5 0.375 22.125 6 15.5 0.375 23.125 8 16.5 0.5 25.125
18 6400 3200 9240 4 14.5 0.3125 22.125 6 15.5 0.3125 23.125 6 16 0.375 24.125 6 16.5 0.375 25.125 8 18 0.5 27.125
20 6800 3400 10200 4 16 0.3125 24.125 6 16.5 0.3125 25.125 6 17.5 0.375 26.125 6 18 0.375 27.125 8 19.5 0.5 29.125
24 7200 3600 12000 4 19 0.3125 28.125 6 19.5 0.3125 29.125 6 20.5 0.375 30.125 6 21 0.375 31.125 8 22.5 0.5 33.125
30 9400 4700 14900 6 23 0.3125 34.375 6 24 0.3125 35.375 6 24.5 0.375 36.375 6 25 0.375 37.375 8 26.5 0.5 39.375
36 11000 5500 17750 6 27.5 0.3125 40.375 6 28 0.3125 41.375 6 28.5 0.375 42.375 6 29.5 0.375 43.375 8 31 0.5 45.375
42 12400 6200 20500 6 31.5 0.3125 46.375 6 32.5 0.3125 47.375 6 33 0.375 48.375 6 33.5 0.375 49.375 8 35 0.5 51.375

Application: Features: Material Data:

Model C4100 through C4130 are designed for All pipe sizes C4100 - C4130: specification document: No. 209.
use on: Easy installation Steel Inner Thrust Plates (supplied loose):
Hot water Steam Model ASTM For Pipe Material
Overlapping galvanized sheet metal jacket
Cold water Air C4100 A36 Carbon Steel
Insulating structural inserts for load transfer
Chilled water Gas C4110 A387GR.22 Chrome-Moly
Other I.D.s and/or O.D.s available on request C4120 A515GR.70 Carbon Silicon
Dual temperature Vacuum C4130 A304L Stainless Steel
Bottom-of-pipe to top-of-shield matches insulated
Where large axial forces must be resisted Structural Inserts: High-density calcium silicate.
supports in B series
Asbestos-free, treated with water repellant.
Intended for installation on: Performance test results on file: Jackets: Galvanized Steel ASTM A-653.
Flat Surfaces Available upon request. Steel Straps & Base: Carbon Steel ASTM A-36
Glue: Industrial contact adhesive.
Temperature Range: Coating: Primer coated or hot dipped galvanized.
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request.
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Fasteners: ASTM A-307 plated.
Add U after the model number (i.e., C4100U)
Formal submittal sheets available

www.pipeshields.com/c4100 83
Pipe
Shields Model C4200, Model C4210,
Inc. Model C4220, Model C4230 Insulated Positive Pipe Anchor
C4000

E 7"

PIPE
B.O.P.

B
T.O.S.

C 4"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load ratings, see: C4300.


If thrust plate thickness D is greater than pipe wall thickness, consult factory.
Load Rating
Pipe Insul. Thk. = 2" Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4"
Vert. Lat. Axial
Size
Lbs Lbs Lbs B C D E B C D E B C D E B C D E
1 600 300 900 4 3 0.3125 6.687 4 4 0.3125 7.75 6 4.5 0.3125 8.75 6 6.5 0.3125 10.75
1 1/2 870 435 1290 4 4 0.3125 7.75 4 4.5 0.3125 8.75 6 5.5 0.375 9.75 6 7.5 0.375 11.875
2 1090 545 1620 4 4 0.3125 7.75 4 4.5 0.3125 8.75 6 5.5 0.375 9.75 6 7.5 0.375 11.875
2 1/2 1310 655 1960 4 4.5 0.3125 8.75 4 5.5 0.375 9.75 6 6.5 0.375 10.75 6 8 0.375 12.875
3 1600 800 3450 4 4.5 0.375 8.75 4 5.5 0.5 9.75 6 6.5 0.5 10.75 6 8 0.5 12.875
4 2500 1250 4100 4 5.5 0.375 9.75 4 6.5 0.5 10.75 6 7.5 0.5 11.875 6 9 0.5 13.875
5 3100 1550 4750 4 6.5 0.375 10.75 4 7.5 0.5 11.875 6 8 0.5 12.875 6 9.5 0.5 15.125
6 3800 1900 5400 4 7.5 0.375 11.875 4 8 0.5 12.875 6 9 0.5 13.875 6 10.5 0.5 16.125
8 5100 2550 6675 4 9 0.375 13.875 6 9.5 0.5 15.125 6 10.5 0.5 16.125 6 12 0.5 18.125
10 6000 3000 8000 4 10.5 0.375 16.375 6 11 0.5 17.375 6 12 0.5 18.375 6 13 0.5 20.375
12 6600 3300 9300 4 12 0.375 18.375 6 12.5 0.5 19.375 6 13 0.5 20.375 6 14.5 0.5 22.375
14 7500 3750 10000 4 12.5 0.375 19.375 6 13 0.5 20.375 6 14 0.5 21.375 6 15.5 0.5 23.375
16 8700 4350 11300 6 14 0.375 21.375 6 14.5 0.5 22.375 6 15.5 0.5 23.375 8 16.5 0.5 25.375
18 9600 4800 12500 6 15.5 0.375 23.375 6 16 0.5 24.375 6 16.5 0.5 25.375 8 18 0.5 27.375
20 10200 5100 13800 6 16.5 0.375 25.375 6 17.5 0.5 26.375 6 18 0.5 27.375 8 19.5 0.5 29.375
24 10800 5400 16300 6 19.5 0.375 29.375 6 20.5 0.5 30.375 6 21 0.5 31.375 8 22.5 0.5 33.375
30 14100 7050 20100 6 24 0.375 35.625 6 24.5 0.5 36.625 6 25 0.5 37.625 8 26.5 0.5 39.625
36 16500 8250 23900 6 28 0.375 41.625 6 28.5 0.5 42.625 6 29.5 0.5 43.625 8 31 0.5 45.625
42 16500 8250 23900 6 32.5 0.375 47.625 6 33 0.5 48.625 6 33.5 0.5 49.625 8 35 0.5 51.625

Application: Features: Material Data:

Model C4200 through C4230 are designed for All pipe sizes C4200 - C4230: specification document: No. 209.
use on: Easy installation Steel Inner Thrust Plates (supplied loose):
Hot water Steam Model ASTM For Pipe Material
Overlapping galvanized sheet metal jacket
Cold water Air C4200 A36 Carbon Steel
Positive stop - axial, lateral, vertical C4210 A387GR.22 Chrome-Moly
Chilled water Gas
Other I.D.s and/or O.D.s available on request C4220 A515GR.70 Carbon Silicon
Dual temperature Vacuum C4230 A304L Stainless Steel
Bottom-of-pipe to top-of-shield matches insulated
Where large axial forces must be resisted Structural Inserts: High-density calcium silicate.
supports in B series Asbestos-free, treated with water repellant.
Intended for installation on: Performance test results on file: Jackets: Galvanized steel ASTM A-653.
Flat surfaces Steel Straps & Base: Carbon steel ASTM A-36
Available upon request.
Glue: Industrial contact adhesive.
Temperature Range: Coating: Primer coated or hot dipped galvanized.
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request.
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Fasteners: ASTM A-307 plated.
Add U after the model number (i.e., C4200U)
Formal submittal sheets available

84 www.pipeshields.com/c4200
Pipe
Model C4300, Model C4310, Shields
Model C4320, Model C4330 Insulated Positive Pipe Anchor Inc.
C4300

E 9"

PIPE
B.O.P.

B
T.O.S.

C 6"

Contact factory for other dimensional, temperature, load, or axial travel requirements. Available in all insulation thickness.

The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.

Dimensions and ratings are subject to change without notice.

Note: For higher load rating contact factory - If thrust plate thickness D is greater than pipe wall thickness, consult factory.
Load Rating
Pipe Insul. Thk. = 2-1/2" Insul. Thk. = 3" Insul. Thk. = 4"
Vert. Lat. Axial
Size
Lbs Lbs Lbs B C D E B C D E B C D E
1 910 455 1360 4 4 0.375 8 6 4.5 0.5 9 6 6.5 0.5 11
1 1/2 1310 655 1970 4 4.5 0.5 9 6 5.5 0.5 10 6 7.5 0.5 12.125
2 1640 820 2460 4 4.5 0.5 9 6 5.5 0.5 10 6 7.5 0.5 12.125
2 1/2 1980 990 2980 4 5.5 0.5 10 6 6.5 0.5 11 6 8 0.625 13.125
3 2420 1210 3620 4 5.5 0.5 10 6 6.5 0.5 11 6 8 0.625 13.125
4 3110 1555 4660 4 6.5 0.5 11 6 7.5 0.5 12.125 6 9 0.625 14.125
5 3840 1920 5760 4 7.5 0.5 12.125 6 8 0.5 13.125 6 9.5 0.625 15.375
6 4570 2285 6860 4 8 0.5 13.125 6 9 0.625 14.125 6 10.5 0.625 16.375
8 5950 2975 8930 6 9.5 0.5 15.375 6 10.5 0.625 16.375 6 12 0.625 18.375
10 7420 3710 11130 6 11 0.5 17.375 6 12 0.625 18.375 6 13 0.625 20.375
12 8800 4400 13200 6 12.5 0.5 19.625 6 13 0.625 20.625 6 14.5 0.625 22.625
14 10000 5000 15000 6 13 0.5 20.625 6 14 0.625 21.625 6 15.5 0.625 23.625
16 11600 5800 17400 6 14.5 0.5 22.625 6 15.5 0.625 23.625 8 16.5 0.625 25.625
18 12800 6400 19200 6 16 0.5 24.625 6 16.5 0.625 25.625 8 18 0.625 27.625
20 13600 6800 20400 6 17.5 0.5 26.625 6 18 0.625 27.625 8 19.5 0.625 29.625
24 14400 7200 21600 6 20.5 0.5 30.625 6 21 0.625 31.625 8 22.5 0.625 33.625
30 18800 9400 28200 6 24.5 0.5 37.125 6 25 0.625 38.125 8 26.5 0.625 40.125
36 22000 11000 33000 6 28.5 0.5 43.125 6 29.5 0.625 44.125 8 31 0.625 46.125
42 24800 12400 37200 6 33 0.5 49.125 6 33.5 0.625 50.125 8 35 0.625 52.125

Application: Features: Material Data:

Model C4300 through C4330 are designed for All pipe sizes C4300 - C4330: specification document: No. 209.
use on: Easy Installation Steel Inner Thrust Plates (supplied loose):
Hot Water Steam Model ASTM For Pipe Material
Overlapping galvanized sheet metal jacket
Cold Water Air C4300 A36 Carbon Steel
Positive stop - axial, lateral, vertical C4310 A387GR.11 Chrome-Moly
Chilled Water Gas
Other I.D.s and/or O.D.s available on request C4320 A515GR.70 Carbon Silicon
Dual Temperature Vacuum C4330 A304L Stainless Steel
Bottom-of-pipe to top-of-shield matches insulated
Where large axial forces must be resisted Structural Inserts: High-density calcium silicate.
supports in B series Asbestos-free, treated with water repellant.
Intended for installation on: Performance test results on file: Jackets: Galvanized Steel ASTM A-653.
Flat surfaces Steel Straps & Base: Carbon Steel ASTM A-36
Available upon request.
Glue: Industrial contact adhesive.
Temperature Range: Coating: Primer coated or hot dipped galvanized.
Standard: +40F to +1200F CalSil Insulation Other coatings available upon request.
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Fasteners: ASTM A-307 plated.
Add U after the model number (i.e., C4300U)
Formal Submittal Sheets available

www.pipeshields.com/c4300 85
Pipe
Shields
Inc. Introduction: Section D

INTRODUCTION
SECTION D

PRE-INSULATED PIPE SUPPORTS Hanger Type

APPLICATION Heavy Industrial and Large HVAC Distribution Systems

Note: These supports were designed to take advantage of maximum hanger spacings and/or
to accommodate thermal loads or loads due to the presence of valves or other pipe systems
components.

Models D1000 D2000 Two-bolt hanger insulated supports for up to 4 pipe size.

Models D3000 D3300 Two-bolt hanger insulated supports for 1 through 42 pipe size.

Models D4000 D5000 Double-rod hung insulated supports for up to 4 pipe size. Designed to
accommodate minimum overhead clearance conditions.

Models D6000 D6300 Double-rod insulated supports for 5 through 30 pipe size. Designed to
accommodate minimum overhead clearance conditions.

By modifying our standard pipe support concept with combinations of structural insert materials and
strap design, we can readily and economically respond to virtually any pipe support requirement.

If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
707-447-5014 or 1-800-538-7007.

Please acquaint yourself with the selection guide at the front of this catalog and the section index on
the page following this introduction, for assistance in determining the most appropriate support for your
application.

86
Pipe
Shields
Section D Index Inc.
PRE-INSULATED PIPE SUPPORTS

HANGER TYPE

PIPE PRIMARY
SIZE APPLICATION SPECIAL
D1000, D3000
MODEL RANGE HOT COLD FEATURES DUTY

D1000 1/2 - 4 X 2 - BOLT HEAVY


D2000 1/2 - 4 X 2 - BOLT HEAVY
D3000 1 - 42 X X 2 - BOLT HEAVY
D3100 1 - 42 X X 2 - BOLT EXTRA-HEAVY
D3200 1 - 42 X X 2 - BOLT HEAVIER
D4000, D6000 D3300 1 - 42 X X 2 - BOLT HEAVIEST

MIN. OVERHEAD
D4000 1/2 - 4 X CLEARANCE HEAVY
D5000 1/2 - 4 X " HEAVY
D6000 5 - 30 X X " HEAVY
D6100 5 - 30 X X " EXTRA-HEAVY
D6200 16 - 30 X X " HEAVIER
D6300 20 - 30 X X " HEAVIEST

TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 2 IPS
3. Insulation Thickness 3
4. Model Number D1000

EXAMPLE: (20) 2 x 3 D1000

www.pipeshields.com/d-series 87
Pipe
Shields
Inc. Model D1000 Insulated 2-Bolt Hanger
D1000, D3000

D F

C
BEAD
(TYP.)

A
E

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Iron Vert Insul. Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4" Thk. 5"
Size lbs. A B C D E F E F E F E F E F
1/2 65 1/8x 1 1/2 0.38 0.69 0.56 2.38 4 3.44 4 4.75 6 5.75 6 6.81 6
3/4 75 1/8x 1 1/2 0.38 0.69 0.56 2.38 4 3.44 4 4.75 6 5.75 6 6.81 6
1 90 1/8x 1 1/2 0.38 0.69 0.56 2.69 4 3.72 4 4.75 6 5.75 6 6.81 6
1 1/2 150 1/8x 1 1/2 0.38 0.69 0.56 2.94 4 4.25 4 5.25 6 6.31 6 7.31 6
2 245 1/4x 1 1/2 0.50 0.81 0.63 3.56 6 4.63 6 5.63 6 6.69 6 7.69 6
2 1/2 290 1/4x 1 1/2 0.50 0.81 0.63 3.81 6 5.13 6 6.13 9 7.19 9 8.31 9
3 365 1/4x 1 1/2 0.63 1.06 0.63 4.22 6 5.25 6 6.25 9 7.31 9 8.44 9
4 475 1/4x 1 1/2 0.63 1.06 0.63 4.75 6 5.75 6 6.81 9 7.81 9 8.94 9
TABLE I

Application: Features: Material Data:

Model D1000 is designed for use on: Compact D1000: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium Silicate Asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes Jackets: Galvanized Steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Steel Straps: Carbon Steel ASTM A-36
Minimizes heat loss and/or condensation Glue: Industrial contact adhesive.
Intended to be hung from threaded rod. Coating: Primer coated or hot dipped galvanized.
Other I.D.s and/or O.D.s available on request
Other coatings available upon request.
Temperature Range: Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Formal submittal sheets available
Cryogenic: -275F to +275F Urethane Insulation.
Available upon request.
Add U after the model number (i.e., D1000U)

88 www.pipeshields.com/d1000
Pipe
Shields
Model D2000 Insulated 2-Bolt Hanger
D2000 Inc.

D F

C 1"
(TYP.)
BEAD
(TYP.)

A
E

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Iron Vert Insul. Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4" Thk. 5"
Size lbs. A B C D E F E F E F E F E F
1/2 65 1/8x 1 1/2 0.38 0.69 0.56 2.38 6 3.44 6 4.75 6 5.75 6 6.81 6
3/4 75 1/8x 1 1/2 0.38 0.69 0.56 2.38 6 3.44 6 4.75 6 5.75 6 6.81 6
1 90 1/8x 1 1/2 0.38 0.69 0.56 2.69 6 3.72 6 4.75 6 5.75 6 6.81 6
1 1/2 150 1/8x 1 1/2 0.38 0.69 0.56 2.94 6 4.25 6 5.25 6 6.31 6 7.31 6
2 245 1/4x 1 1/2 0.50 0.81 0.63 3.56 6 4.63 6 5.63 6 6.69 6 7.69 6
2 1/2 290 1/4x 1 1/2 0.50 0.81 0.63 3.81 6 5.13 6 6.13 9 7.19 9 8.31 9
3 365 1/4x 1 1/2 0.63 1.06 0.63 4.22 6 5.25 6 6.25 9 7.31 9 8.44 9
4 475 1/4x 1 1/2 0.63 1.06 0.63 4.75 6 5.75 6 6.81 9 7.81 9 8.94 9
TABLE I

Application: Features: Material Data:

D2000 is designed for use on: Compact D2000: Applicable PSI specification document:
Cold water Easy installation No. 209.
Chilled water Insulation: Calcium silicate Asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Copper tubing sizes and pipe sizes Jackets: Galvanized steel ASTM A-653.
Intended to be hung from threaded rod Overlapping galvanized sheet metal jacket Steel Straps: Carbon steel ASTM A-36
Minimizes heat loss and/or condensation Glue: Industrial contact adhesive.
Temperature Range: Coating: Primer coated or hot dipped galvanized.
Standard: +40F to +1200F CalSil Insulation Other I.D.s and/or O.D.s available on request
Other coatings available upon request.
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Fasteners: ASTM A-307 plated.
Add U after the model number (i.e., D2000U)
Calcium silicate insulation extend 1 beyond the
galvanized sheet metal jacket providing for an Formal submittal sheets available
easier wet lag butt joint with the pipe insulation.

Performance test results on file:


Available upon request.

www.pipeshields.com/d2000 89
Pipe
Shields
Inc. D1000, D3000 Model D3000 Insulated 2-Bolt Hanger

D F

C
BEAD
(TYP.)

A
E

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings, see: D3100.


Vert Insul. Insul. Insul. Insul. Insul.
Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4" Thk. 5"
Size lbs. A B C D E F E F E F E F E F
1 285 3/16x2 0.375 0.675 0.75 2.81 6 3.84 6 4.88 6 5.88 6 6.94 6
1 1/2 320 3/16x2 0.375 0.675 0.75 3.06 6 4.38 6 5.38 6 6.44 6 7.44 6
2 320 3/16x2 0.375 0.675 0.75 3.31 6 4.38 6 5.38 6 6.44 6 7.44 6
2 1/2 540 1/4x2 0.375 0.675 0.75 3.69 6 5 6 6 6 7.06 6 8.19 6
3 540 1/4x2 0.375 0.675 0.75 3.97 6 5 6 6 6 7.06 6 8.19 6
4 770 1/4x3 0.5 0.84 0.75 4.63 6 5.63 6 6.69 6 7.69 6 8.81 6
5 1125 3/8x3 0.5 0.84 0.75 5.38 6 6.38 6 7.44 6 8.56 6 9.56 6
6 1430 3/8x3 0.625 1.05 0.75 6 6 7.06 6 8.06 6 9.18 6 10.19 6
8 1805 1/2x3 0.625 1.05 0.75 7.31 6 8.31 6 9.44 6 10.44 6 11.44 6
10 2310 1/2x3 0.75 1.05 0.75 8.44 6 9.56 6 10.56 6 11.56 6 12.56 6
12 2705 5/8x3 0.75 1.05 0.75 9.69 6 10.69 6 11.69 6 12.69 6 13.69 6
14 2705 5/8x3 0.75 1.05 0.75 10.19 6 11.19 6 12.18 6 13.19 6 14.19 6
16 3035 5/8x3 0.875 1.315 1 11.31 6 12.31 6 13.31 6 14.31 6 15.31 6
18 3750 3/4x3 0.875 1.315 1 12.56 6 13.56 6 14.56 6 15.56 6 16.56 6
20 3855 3/4x3 1 1.315 1 13.69 6 14.69 6 15.69 6 16.69 6 17.69 6
24 4935 1x3 1 1.315 1 16.19 6 17.19 6 18.19 6 19.18 6 20.19 6
30 5295 1x3 1.25 1.66 1.25 19.44 6 20.44 6 21.44 6 22.44 6 23.44 6
36 7855 1x6 1.25 1.66 1.25 22.44 9 23.44 9 24.44 9 25.44 9 26.44 9
42 7970 1x6 1.25 1.66 1.25 25.44 9 26.44 9 27.44 9 28.44 9 29.44 9
TABLE I

Application: Features: Material Data:

D3000 is designed for use on: Compact D3000: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Eliminates welding to pipe Insulation: Calcium silicate asbestos-free,
Chilled water Gas treated with water repellant.
Copper tubing sizes and pipe sizes
Dual temperature Vacuum Jackets: Galvanized steel ASTM A-653.
Overlapping galvanized sheet metal jacket
Glue: Industrial contact adhesive
Minimizes heat loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from threaded rod.
Other I.D.s and/or O.D.s available on request silicate asbestos free, treated with water
repellant.
Temperature Range: Steel Straps: Carbon steel ASTM A-36.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Fasteners: ASTM A-307 plated.
Cryogenic: -275F to +275F Urethane Insulation. Coating: Primer coated or hot dipped galvanized.
Available upon request.
Add U after the model number (i.e., D3000U) Other coatings available upon request
Formal submittal sheets available

90 www.pipeshields.com/d3000
Pipe
D1000, D3000 Shields
Model D3100 Insulated 2-Bolt Hanger Inc.

D F

C
BEAD
(TYP.)

A
E

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings, see: D3200.


Vert Insul. Insul. Insul. Insul. Insul.
Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4" Thk. 5"
Size lbs. A B C D E F E F E F E F E F
1 510 3/16x3 0.375 0.675 0.75 2.81 6 3.84 6 4.88 6 5.88 6 6.94 6
1 1/2 605 1/4x3 0.375 0.675 0.75 3.19 6 4.5 6 5.5 6 6.56 6 7.56 6
2 605 1/4x3 0.375 0.675 0.75 3.44 6 4.5 6 5.5 6 6.56 6 7.56 6
2 1/2 810 1/4x3 0.5 0.84 0.75 3.81 6 5.13 6 6.13 6 7.19 6 8.31 6
3 1125 3/8x3 0.5 0.84 0.75 4.34 6 5.38 6 6.38 6 7.44 6 8.56 6
4 1720 3/8x3 0.625 1.05 0.75 5 6 6 6 7.06 6 8.06 6 9.19 6
5 2340 1/2x3 0.75 1.05 0.75 5.88 6 6.88 6 7.94 6 9.06 6 10.06 6
6 2705 1/2x3 0.75 1.05 0.75 6.38 6 7.44 6 8.44 6 9.56 6 10.56 6
8 3605 5/8x3 0.875 1.315 1 7.69 6 8.69 6 9.81 6 10.81 6 11.81 6
10 3630 5/8x3 0.875 1.315 1 8.69 6 9.81 6 10.81 6 11.81 6 12.81 6
12 4660 3/4x3 1 1.315 1 10.19 6 11.19 6 12.19 6 13.19 6 14.19 6
14 4660 3/4x3 1 1.315 1 10.69 6 11.69 6 12.69 6 13.69 6 14.69 6
16 6820 3/4x5 1.25 1.66 1.25 11.94 9 12.94 9 13.94 9 14.94 9 15.94 9
18 6820 3/4x5 1.25 1.66 1.25 12.94 9 13.94 9 14.94 9 15.94 9 16.94 9
20 7970 1x6 1.25 1.66 1.25 14.44 9 15.44 9 16.44 9 17.44 9 18.44 9
24 10285 1x6 1.5 1.9 1.25 16.69 9 17.69 9 18.69 9 19.69 9 20.69 9
30 10600 1x6 1.5 1.9 1.25 19.69 9 20.69 9 21.69 9 22.69 9 23.69 9
36 13020 1 1/4x6 2 2.375 1.75 23.69 9 24.69 9 25.69 9 26.69 9 27.69 9
42 13020 1 1/4x6 2 2.375 1.75 26.69 9 27.69 9 28.69 9 29.69 9 30.69 9
TABLE I

Application: Features: Material Data:

D3100 is designed for use on: Compact D3100: Applicable PSI specification document:
Hot Water Steam Easy installation No. 209
Cold Water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant
Chilled Water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653
Dual Temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from threaded rod silicate asbestos free, treated with water
Other I.D.s and/or O.D.s available on request
repellant
Temperature Range: Steel Straps: Carbon steel ASTM A-36
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Fasteners: ASTM A-307 plated
Cryogenic: -275F to +275F Urethane Insulation. Coating: Primer coated or hot dipped galvanized
Available upon request.
Add U after the model number (i.e., D3100U) Other coatings available upon reques
Formal submittal sheets available

www.pipeshields.com/d3100 91
Pipe D1000, D3000
Shields
Inc. Model D3200 Insulated 2-Bolt Hanger

D F

C
BEAD
(TYP.)

A
E

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings, see: D3300.


Vert Insul. Insul. Insul. Insul. Insul.
Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4" Thk. 5"
Size lbs. A B C D E F E F E F E F E F
1 850 1/4x4 1/2 0.625 1.05 0.75 3.19 9 4.22 9 5.25 9 6.25 9 7.31 9
1 1/2 1215 1/4x4 1/2 0.625 1.05 0.75 3.44 9 4.75 9 5.75 9 6.81 9 7.81 9
2 1215 1/4x4 1/2 0.625 1.05 0.75 3.69 9 4.75 9 5.75 9 6.81 9 7.81 9
2 1/2 1215 1/4x4 1/2 0.625 1.05 0.75 3.94 9 5.25 9 6.25 9 7.31 9 8.44 9
3 1805 3/8x4 1/2 0.625 1.05 0.75 4.47 9 5.5 9 6.5 9 7.56 9 8.69 9
4 2585 3/8x4 1/2 0.75 1.05 0.75 5.13 9 6.13 9 7.19 9 8.19 9 9.31 9
5 2705 1/2x4 1/2 0.75 1.05 0.75 5.88 9 6.88 9 7.94 9 9.06 9 10.06 9
6 3750 1/2x4 1/2 0.875 1.315 1 6.5 9 7.56 9 8.56 9 9.69 9 10.69 9
8 4215 1/2x5 1 1.315 1 7.81 9 8.81 9 9.94 9 10.94 9 11.94 9
10 6045 5/8x5 1.25 1.66 1.25 9.06 9 10.19 9 11.19 9 12.19 9 13.19 9
12 7770 3/4x5 1.25 1.66 1.25 10.44 9 11.44 9 12.44 9 13.44 9 14.44 9
14 7770 3/4x5 1.25 1.66 1.25 10.94 9 11.94 9 12.94 9 13.94 9 14.94 9
16 7970 1x5 1.25 1.66 1.25 12.44 9 13.44 9 14.44 9 15.44 9 16.44 9
18 11270 1x5 1.5 1.9 1.25 13.69 9 14.69 9 15.69 9 16.69 9 17.69 9
20 11465 1x6 1.5 1.9 1.25 14.69 9 15.69 9 16.69 9 17.69 9 18.69 9
24 12220 1x6 2 2.375 1.75 17.06 9 18.06 9 19.06 9 20.06 9 21.06 9
30 16480 1 1/4x6 2 2.375 1.75 20.69 9 21.69 9 22.69 9 23.69 9 24.69 9
36 17370 1 1/4x8 2 2.375 1.75 23.69 12 24.69 12 25.69 12 26.69 12 27.69 12
42 17370 1 1/4x8 2 2.375 1.75 26.69 12 27.69 12 28.69 12 29.69 12 30.69 12
TABLE I

Application: Features: Material Data:

D3200 is designed for use on: Compact D3200: Applicable PSI specification document:
Hot water Steam Easy installation No. 209
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from threaded rod silicate asbestos free, treated with water
Other I.D.s and/or O.D.s available on request
repellant
Temperature Range: Steel Straps: Carbon steel ASTM A-36.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance Test Results on File: Fasteners: ASTM A-307 plated.
Cryogenic: -275F to +275F Urethane Insulation. Coating: Primer coated or hot dipped galvanized.
Available upon request.
Add U after the model number (i.e., D3200U) Other coatings available upon request

Formal submittal sheets available

92 www.pipeshields.com/d3200
Pipe
D1000, D3000 Shields
Model D3300 Insulated 2-Bolt Hanger Inc.

D F

C
BEAD
(TYP.)

A
E

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Note: For higher load ratings contact factory. Contact factory for current inform ation.

Vert Insul. Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4" Thk. 5"
Size lbs. A B C D E F E F E F E F E F
1 1135 1/4x6 0.625 1.05 0.75 3.188 9 4.22 9 5.25 9 6.25 9 7.31 9
1.5 1630 1/4x6 0.625 1.05 0.75 3.44 9 4.75 9 5.75 9 6.81 9 7.81 9
2 1715 1/4x6 0.625 1.05 0.75 3.69 9 4.75 9 5.75 9 6.81 9 7.81 9
2.5 1805 3/8x6 0.625 1.05 0.75 4.19 9 5.5 9 6.5 9 7.56 9 8.69 9
3 2705 3/8x6 0.75 1.05 0.75 4.59 9 5.63 9 6.63 9 7.69 9 8.81 9
4 3445 3/8x6 0.875 1.315 1 5.25 9 6.25 9 7.31 9 8.31 9 9.44 9
5 3750 1/2x6 0.875 1.315 1 6 9 7 9 8.06 9 9.19 9 10.19 9
6 4935 1/2x6 1 1.315 1 6.75 9 7.81 9 8.81 9 9.94 9 10.94 9
8 7215 5/8x6 1.25 1.66 1.25 8.06 9 9.06 9 10.19 9 11.19 9 12.19 9
10 7257 5/8x6 1.25 1.66 1.25 9.06 9 10.19 9 11.19 9 12.19 9 13.19 9
12 9320 3/4x6 1.5 1.9 1.25 10.69 9 11.69 9 12.69 9 13.69 9 14.69 9
14 9320 3/4x6 1.5 1.9 1.25 11.19 9 12.19 9 13.19 9 14.19 9 15.19 9
16 11465 1x6 1.5 1.9 1.25 12.69 9 13.69 9 14.69 9 15.69 9 16.69 9
18 14445 1x6 2 2.375 1.75 14.06 9 15.06 9 16.06 9 17.06 9 18.06 9
20 16580 1 1/4x6 2 2.375 1.75 15.69 9 16.69 9 17.69 9 18.69 9 19.69 9
24 19005 1 1/4x6 2 2.375 1.75 17.69 9 18.69 9 19.69 9 20.69 9 21.69 9
30 20605 1 1/4x8 2 2.375 1.75 20.69 12 21.69 12 22.69 12 23.69 12 24.69 12
36 24905 1 1/2x8 2.5 3.508 1.75 24.44 12 25.44 12 26.44 12 27.44 12 28.44 12
42 24905 1 1/2x8 2.5 3.508 1.75 27.44 12 28.44 12 29.44 12 30.44 12 31.44 12
TABLE I

Application: Features: Material Data:

D3300 is designed for use on: Compact D3300: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from threaded rod silicate asbestos free, treated with water
Other I.D.s and/or O.D.s available on request
repellant.
Temperature Range: Steel Straps: Carbon steel ASTM A-36.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request.
Fasteners: ASTM A-307 plated.
Cryogenic: -275F to +275F Urethane Insulation.
Performance test results on file: Coating: Primer coated or hot dipped galvanized.
Add U after the model number (i.e., D3300U) Available upon request. Other coatings available upon request
Formal submittal sheets available

www.pipeshields.com/d3300 93
Pipe
Shields D4000, D6000
Inc. Model D4000 Insulated 2-Rod Hanger

D E
THREADED ROD
(BY OTHERS)

BEAD
(TYP.)
B

1/4" THK.
TOP STRAP
C

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are subject
to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load rating contact factory

Vert Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4"
Size lbs. A B C D E C D E C D E C D E
1/2 65 1/8x1 1/2 0.375 1.63 4.75 6 2.69 6.875 6 4.0 9.5 6 5.0 11.5 6
3/4 75(a) 1/8x1 1/2 0.375 1.63 4.75 6 2.69 6.875 6 4.0 9.5 6 5.0 11.5 6
1 90 1/8x1 1/2 0.375 1.94 5.375 6 2.97 7.437 6 4.0 9.5 6 5.0 11.5 6
1 1/2 130 1/8x1 1/2 0.375 2.19 5.875 6 3.50 8.5 6 4.5 10.5 6 5.56 12.625 6
2 245 1/4x1 1/2 0.375 2.44 6.875 6 3.50 9 6 4.5 11 6 5.56 13.125 6
2 1/2 290 1/4x1 1/2 0.375 2.69 7.375 6 4.0 10 6 5.0 12 9 6.06 14.125 9
3 365 1/4x1 1/2 0.375 2.97 7.937 6 4.0 10 6 5.0 12 9 6.06 14.125 9
4 475 1/4x1 1/2 0.375 3.5 9 6 4.5 11 6 5.56 13.125 9 6.56 15.125 9
TABLE I

Application: Features: Material Data:

D4000 is designed for use on: Compact D4000: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from two threaded rods in silicate asbestos free, treated with water
close overhead clearance conditions. Other I.D.s and/or O.D.s available on request
repellant.
Steel Straps: Carbon steel ASTM A-36.
Temperature Range: Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation Performance test results on file:
Note: Up to 1800F available upon request. Coating: Primer coated or hot dipped galvanized.
Available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Other coatings available upon request
Add U after the model number (i.e., D4000U) Formal submittal sheets available

94 www.pipeshields.com/d4000
Pipe
Shields
Model D5000 Insulated 2-Rod Hanger
D5000 Inc.

D E
THREADED ROD
(BY OTHERS)
1"
(TYP.)
BEAD
(TYP.)
B

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load rating contact factory

Vert Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4"
Size lbs. A B C D E C D E C D E C D E
1/2 65 1/8x1 1/2 0.375 1.63 4.75 6 2.69 6.875 6 4.0 9.5 6 5.0 11.5 6
3/4 75 1/8x1 1/2 0.375 1.63 4.75 6 2.69 6.875 6 4.0 9.5 6 5.0 11.5 6
1 90 1/8x1 1/2 0.375 1.94 5.375 6 2.97 7.437 6 4.0 9.5 6 5.0 11.5 6
1 1/2 130 1/8x1 1/2 0.375 2.19 5.875 6 3.50 8.5 6 4.5 10.5 6 5.56 12.625 6
2 245 1/4x1 1/2 0.375 2.44 6.875 6 3.50 9 6 4.5 11 6 5.56 13.125 6
2 1/2 290 1/4x1 1/2 0.375 2.69 7.375 6 4.0 10 6 5.0 12 9 6.06 14.125 9
3 365 1/4x1 1/2 0.375 2.97 7.937 6 4.0 10 6 5.0 12 9 6.06 14.125 9
4 475 1/4x1 1/2 0.375 3.5 9 6 4.5 11 6 5.56 13.125 9 6.56 15.125 9
TABLE I

Application: Features: Material Data:

D5000 is designed for use on: Compact D5000: Applicable PSI specification document:
Cold water Easy installation No. 209.
Chilled water Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Intended to be hung from two threaded rods in Overlapping galvanized sheet metal jacket
close overhead clearance conditions. Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Minimal overhead clearance requirement silicate asbestos free, treated with water
Temperature Range: repellant.
Standard: +40F to +1200F CalSil Insulation
Other I.D.s and/or O.D.s available on request
Note: Up to 1800F available upon request. Steel Straps: Carbon steel ASTM A-36.
Cryogenic: -275F to +275F Urethane Insulation. Fasteners: ASTM A-307 plated.
Add U after the model number (i.e., D5000U)
Performance test results on file: Coating: Primer coated or hot dipped galvanized.
Available upon request. Other coatings available upon request
Formal submittal sheets available

www.pipeshields.com/d5000 95
Pipe
Shields D4000, D6000
Inc. Model D6000 Insulated 2-Rod Hanger

D E
THREADED ROD
(BY OTHERS)

BEAD
(TYP.)
B

1/4" THK.
TOP STRAP
C

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings, see: D6100.

Vert Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4"
Size lbs. A B C D E C D E C D E C D E
5 600 1/2x3 0.375 4.13 11 6 5.13 13 6 6.18 15.125 6 7.31 17.375 6
6 800 1/2x3 0.375 4.63 12 6 5.68 14.125 6 6.68 16.125 6 7.81 18.375 6
8 1300 1/2x3 0.500 5.68 14.375 6 6.68 16.375 6 7.81 18.625 6 8.81 20.625 6
10 2000 1/2x3 0.500 6.69 16.375 6 7.81 18.625 6 8.81 20.625 6 9.81 22.625 9
12 2400 5/8x3 0.625 7.81 19.375 6 8.81 21.375 6 9.81 23.375 6 10.81 25.375 9
14 2500 5/8x3 0.625 8.31 20.375 6 9.31 22.375 6 10.31 24.375 9 11.31 26.375 9
16 3300 3/4x3 0.750 9.31 22.875 6 10.31 24.875 9 11.31 26.875 9 12.31 28.875 9
18 3500 3/4x3 0.750 10.31 24.875 9 11.31 26.875 9 12.31 28.875 9 13.31 30.875 12
20 3600 3/4x3 0.750 11.31 26.875 9 12.31 28.875 9 13.31 30.875 9 14.31 32.875 12
24 4500 1x3 0.750 13.31 31.625 9 14.31 33.625 12 15.31 35.625 12 16.31 37.625 12
30 4800 1x3 0.750 16.31 37.625 12 17.31 39.625 12 18.31 41.625 12 19.31 43.625 12
TABLE I

Application: Features: Material Data:

D6000 is designed for use on: Compact D6000: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from two threaded rods in Minimal overhead clearance requirement silicate asbestos free, treated with water
close overhead clearance conditions. repellant.
Other I.D.s and/or O.D.s available on request
Steel Straps: Carbon steel ASTM A-36.
Temperature Range: Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Coating: Primer coated or hot dipped galvanized.
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Other coatings available upon request
Add U after the model number (i.e., D6000U)

Formal submittal sheets available

96 www.pipeshields.com/d6000
Pipe
D4000, D6000 Shields
Model D6100 Insulated 2-Rod Hanger Inc.

D E
THREADED ROD
(BY OTHERS)

BEAD
(TYP.)
B

1/4" THK.
TOP STRAP
C

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings, see: D6200.

Vert Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4"
Size lbs. A B C D E C D E C D E C D E
5 1200 1/2x3 0.50 4.13 11.25 6 5.13 13.25 6 6.18 15.375 6 7.31 17.625 6
6 1600 1/2x3 0.50 4.63 12.25 6 5.68 14.375 6 6.68 16.375 6 7.81 18.625 6
8 2600 1/2x3 0.63 5.68 14.625 6 6.68 16.625 6 7.81 18.875 6 8.81 20.875 6
10 4000 5/8x3 0.75 6.69 17.125 6 7.81 19.375 6 8.81 21.375 6 9.81 23.375 9
12 4800 3/4x3 0.75 7.81 19.875 6 8.81 21.875 6 9.81 23.875 6 10.81 25.875 9
14 5000 3/4x3 0.75 8.31 20.875 6 9.31 22.875 6 10.31 24.875 9 11.31 26.875 9
16 6150 1x3 0.88 9.31 24.125 6 10.31 26.125 9 11.31 28.125 9 12.31 30.125 9
18 6150 1x4 1/2 0.88 10.31 26.125 9 11.31 28.125 9 12.31 30.125 9 13.31 32.125 9
20 6150 1x4 1/2 0.88 11.31 28.125 9 12.31 30.125 9 13.31 32.125 9 14.31 34.125 12
24 8550 1x4 1/2 1.00 13.31 32.375 9 14.31 34.375 12 15.31 36.375 12 16.31 38.375 12
30 8550 1x4 1/2 1.25 16.31 38.875 12 17.31 40.875 12 18.31 42.875 12 19.31 44.875 12
TABLE I

Application: Features: Material Data:

D6100 is designed for use on: Compact D6100: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from two threaded rods in Minimal overhead clearance requirement silicate asbestos free, treated with water
close overhead clearance conditions. repellant.
Other I.D.s and/or O.D.s available on request
Steel Straps: Carbon steel ASTM A-36.
Temperature Range: Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Coating: Primer coated or hot dipped galvanized.
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Other coatings available upon request
Add U after the model number (i.e., D6100U)

Formal submittal sheets available

www.pipeshields.com/d6100 97
Pipe
Shields
Inc. Model D6200 Insulated 2-Rod Hanger
D4000, D6000

D E
THREADED ROD
(BY OTHERS)

BEAD
(TYP.)
B

1/4" THK.
TOP STRAP
C

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings, see: D6300.

Vert Insul. Insul. Insul. Insul.


Pipe load Thk. 1" Thk. 2" Thk. 3" Thk. 4"
Size lbs. A B C D E C D E C D E C D E
16 6600 1x4 1/2 1.25 9.31 24.875 6 10.31 26.875 9 11.31 28.875 9 12.31 30.875 9
18 7000 1x4 1/2 1.25 10.31 26.875 9 11.31 28.875 9 12.31 30.875 9 13.31 32.875 9
20 7200 1x4 1/2 1.25 11.31 28.875 9 12.31 30.875 9 13.31 32.875 9 14.31 34.875 12
24 9000 1x4 1/2 1.25 13.31 32.875 9 14.31 34.875 12 15.31 36.875 12 16.31 38.875 12
30 9600 1x4 1/2 1.25 16.31 38.875 12 17.31 40.875 12 18.31 42.875 12 19.31 44.875 12
TABLE I

Application: Features: Material Data:

D6200 is designed for use on: Compact D6200: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from two threaded rods in Minimal overhead clearance requirement silicate asbestos free, treated with water
close overhead clearance conditions. repellant.
Other I.D.s and/or O.D.s available on request
Steel Straps: Carbon steel ASTM A-36.
Temperature Range: Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Coating: Primer coated or hot dipped galvanized.
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Other coatings available upon request
Add U after the model number (i.e., D6200U)

Formal submittal sheets available

98 www.pipeshields.com/d6200
Pipe
D4000, D6000 Shields
Model D6300 Insulated 2-Rod Hanger Inc.

D E
THREADED ROD
(BY OTHERS)

BEAD
(TYP.)
B

1/4" THK.
TOP STRAP
C

The load ratings represent average values obtained in accordance with accepted test
methods and are subject to normal manufacturing variations. Dimensions and ratings are
subject to change without notice. Available in all insulation thickness.

Contact factory for current inform ation.

Note: For higher load ratings contact factory.

Vert Bolt Insul. Insul. Insul. Insul.


Pipe load Torq Thk. 1" Thk. 2" Thk. 3" Thk. 4"
Size lbs. ft-lbs A B C D E C D E C D E C D E
20 8200 50 1x6 1.25 11.31 28.875 9 12.31 30.875 9 13.31 32.875 9 14.31 34.875 12
24 11400 50 1x6 1.50 13.31 33.375 9 14.31 35.375 12 15.31 37.375 12 16.31 39.375 12
30 11400 50 1x6 1.50 16.31 39.375 12 17.31 41.375 12 18.31 43.375 12 19.31 45.375 12
TABLE I

Application: Features: Material Data:

D6300 is designed for use on: Compact D6300: Applicable PSI specification document:
Hot water Steam Easy installation No. 209.
Cold water Air Insulation: Calcium silicate asbestos-free,
Eliminates welding to pipe
treated with water repellant.
Chilled water Gas Copper tubing sizes and pipe sizes
Jackets: Galvanized steel ASTM A-653.
Dual temperature Vacuum Overlapping galvanized sheet metal jacket Glue: Industrial contact adhesive
Minimizes heat-loss and/or condensation Structural Inserts: High-density calcium
Intended to be hung from two threaded rods in Minimal overhead clearance requirement silicate asbestos free, treated with water
close overhead clearance conditions. repellant.
Other I.D.s and/or O.D.s available on request
Steel Straps: Carbon steel ASTM A-36.
Temperature Range: Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Performance test results on file: Coating: Primer coated or hot dipped galvanized.
Cryogenic: -275F to +275F Urethane Insulation. Available upon request. Other coatings available upon request
Add U after the model number (i.e., D6300U)
Formal submittal sheets available

www.pipeshields.com/d6300 99
Pipe
Shields
Inc. Introduction: Section E

INTRODUCTION
SECTION E

INSULATED PIPE RISER CLAMPS

APPLICATION Commercial, Light and Heavy Industrial and Large HVAC Distribution Systems

Models E1000 E1300 Insulated pipe riser clamps for restraint of downward loads only.
These models require the field welding of two (2) factory supplied thrust plates
against the upper side of the riser clamp. The higher the model number in this
series, the higher the load rating.

Models E2000 E2300 Insulated Pipe Riser Clamps for restraint of either, or both, upward or
downward loads. These models require field welding of two (2) factory supplied
thrust plates on both the upper and lower sides of the riser clamp. The higher
the model number in this series, the higher the load rating.

Pipe Shields, Inc. can also supply similar clamps (not catalogued) for the support of pipe insulation.
Insulated clamps (not catalogued) can be supplied for use as pipe guides on vertical risers.

If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
707-447-5014 or 1-800-538-7007.

Please acquaint yourself with the selection guide at the front of this catalog and the section index on
the page following this introduction, for assistance in determining the most appropriate support for your
application.

100
Pipe
Shields
Section E Index Inc.

INSULATED PIPE RISER CLAMPS

E1000

PIPE PRIMARY
SIZE APPLICATION
MODEL RANGE DOWNWARD UPWARD DUTY

E1000 2 - 24 X MEDIUM
E1100 2 - 24 X HEAVY
E1200 2 - 24 X HEAVIER
E1300 12 - 24 X HEAVIEST
E2000 2 - 24 X X MEDIUM
E2100 2 - 24 X X HEAVY
E2200 2 - 24 X X HEAVIER
E2300 12 - 24 X X HEAVIEST

TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 4 IPS
3. Insulation Thickness 2
4. Model Number E1000

EXAMPLE: (20) 4 x 2 E1000

www.pipeshields.com/e-series 101
Pipe Model E1000, Model E1010,
Shields
Inc. Model E1020, Model E1030 Insulated Pipe Riser Clamps for Downward Loads
E1000

B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) One pair thrust plates supplied loose for field Note: For higher load ratings, see: E1100.
welding, top only. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs. A B C D E F G H F G H F G H F G H
2 250 0.63 0.25 0.25 x 3.00 1.50 0.625 3.69 5.69 5.13 4.75 6.75 7.25 5.75 7.75 9.25 6.81 8.81 11.38
2 1/2 300 0.63 0.25 0.25 x 3.00 1.50 0.625 3.94 5.94 5.63 5.25 7.25 8.25 6.25 8.25 10.25 7.31 9.31 12.38
3 400 0.63 0.25 0.25 x 3.00 1.50 0.625 4.22 6.22 6.19 5.25 7.25 8.25 6.25 8.25 10.25 7.31 9.31 12.38
4 600 0.63 0.25 0.25 x 3.00 1.50 0.625 4.75 6.75 7.25 5.75 7.75 9.25 6.81 8.81 11.38 7.81 9.81 13.38
5 800 0.63 0.25 0.25 x 3.00 1.50 0.625 5.25 7.25 8.25 6.25 8.25 10.25 7.31 9.31 12.38 8.44 10.44 14.63
6 1000 0.63 0.25 0.25 x 4.00 2.00 0.625 5.75 7.75 9.25 6.81 8.81 11.38 7.81 9.81 13.38 8.94 10.94 15.63
8 1300 0.63 0.25 0.25 x 4.00 2.00 0.625 6.81 8.81 11.38 7.81 9.81 13.38 8.94 10.94 15.63 9.94 11.94 17.63
10 1600 0.63 0.38 0.38 x 5.00 3.00 0.625 8.06 10.31 13.63 9.19 11.44 15.88 10.19 12.44 17.88 11.19 13.44 19.88
12 1700 0.63 0.38 0.38 x 5.00 3.00 0.625 9.19 11.44 15.88 10.19 12.44 17.88 11.19 13.44 19.88 12.19 14.44 21.88
14 2000 0.88 0.38 0.38 x 5.00 3.00 0.625 9.69 11.94 16.88 10.69 12.94 18.88 11.69 13.94 20.88 12.69 14.94 22.88
16 2300 0.88 0.38 0.38 x 5.00 3.00 0.625 10.69 12.94 18.88 11.69 13.94 20.88 12.69 14.94 22.88 13.69 15.94 24.88
18 2500 0.88 0.38 0.38 x 5.00 3.00 0.625 11.69 13.94 20.88 12.69 14.94 22.88 13.69 15.94 24.88 14.69 16.94 26.88
20 2700 0.88 0.38 0.38 x 5.00 3.00 0.625 12.69 14.94 22.88 13.69 15.94 24.88 14.69 16.94 26.88 15.69 17.94 28.88
24 2800 0.88 0.38 0.38 x 5.00 3.00 0.625 14.69 17.19 26.88 15.69 18.19 28.88 16.69 19.19 30.88 17.69 20.19 32.88

Application: Features: Material Data:


Model E1000 through E1030 is designed for All pipe sizes E1000 - E1030: specification document: No. 206.
use on:
Easy installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E1000 A36 Carbon-Steel
Chilled water Gas E1010 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E1020 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E1030 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Vertical runs of insulated pipe with downward Eliminates condensation sweating on chilled with water repellant.
load only. Jackets: Galvanized steel ASTM A-653.
water risers
Other: Glue: Industrial contact adhesive
Structural Inserts: High-density calcium silicate
For handling both upward and downward
asbestos free, treated with water repellant.
loads, see E2000 Performance test results on file: Steel Straps/Base:Carbon steel ASTM A-36.
Temperature Range: Available upon request. Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Other coatings available upon request.
Add U after the model number (i.e., E1000U)
Formal submittal sheets available

102 www.pipeshields.com/e1000
Model E1100, Model E1110, Pipe
Shields
Model E1120, Model E1130 Insulated Pipe Riser Clamps for Downward Loads
E1000
Inc.

B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) One pair thrust plates supplied loose for field Note: For higher load ratings, see: E1200.
welding, top only. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
2 500 0.63 0.38 0.38 x 3.00 1.50 0.625 3.94 6.19 5.38 5.00 7.25 7.50 6.00 8.25 9.50 7.06 9.31 11.63
2 1/2 600 0.63 0.38 0.38 x 3.00 1.50 0.625 4.19 6.44 5.88 5.50 7.75 8.50 6.50 8.75 10.50 7.56 9.81 12.63
3 800 0.63 0.38 0.38 x 3.00 1.50 0.625 4.47 6.72 6.44 5.50 7.75 8.50 6.50 8.75 10.50 7.56 9.81 12.63
4 1200 0.63 0.38 0.38 x 3.00 1.50 0.625 5.00 7.25 7.50 6.00 8.25 9.50 7.06 9.31 11.63 8.06 10.31 13.63
5 1600 0.63 0.38 0.38 x 4.00 2.00 0.625 5.50 7.75 8.50 6.50 8.75 10.50 7.56 9.81 12.63 8.69 10.94 14.88
6 2000 0.63 0.38 0.38 x 4.00 2.00 0.625 6.00 8.25 9.50 7.06 9.31 11.63 8.06 10.31 13.63 9.19 11.44 15.88
8 2600 0.63 0.50 0.50 x 4.00 2.00 0.625 7.31 9.81 11.88 8.31 10.81 13.88 9.44 11.94 16.13 10.44 12.94 18.13
10 3200 0.88 0.50 0.50 x 5.00 3.00 0.625 8.31 10.81 13.88 9.44 11.94 16.13 10.44 12.94 18.13 11.44 13.94 20.13
12 3400 0.88 0.50 0.50 x 5.00 3.00 0.625 9.44 11.94 16.13 10.44 12.94 18.13 11.44 13.94 20.13 12.44 14.94 22.13
14 4000 0.88 0.50 0.50 x 5.00 3.00 0.75 10.06 12.69 17.13 11.06 13.69 19.13 12.06 14.69 21.13 13.06 15.69 23.13
16 4600 0.88 0.50 0.50 x 6.00 4.00 0.75 11.06 13.69 19.13 12.06 14.69 21.13 13.06 15.69 23.13 14.06 16.69 25.13
18 5000 0.88 0.50 0.50 x 6.00 4.00 0.75 12.06 14.69 21.13 13.06 15.69 23.13 14.06 16.69 25.13 15.06 17.69 27.13
20 5400 0.88 0.50 0.50 x 6.00 4.00 0.75 13.06 15.69 23.13 14.06 16.69 25.13 15.06 17.69 27.13 16.06 18.69 29.13
24 5600 0.88 0.50 0.50 x 6.00 4.00 0.75 15.06 17.69 27.13 16.06 18.69 29.13 17.06 19.69 31.13 18.06 20.69 33.13

Application: Features: Material Data:


Model E1100 through E1130 is designed for use All pipe sizes E1100 - E1130: specification document: No. 206.
on:
Easy installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E1100 A36 Carbon-Steel
Chilled water Gas E1110 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E1120 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E1130 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Vertical runs of insulated pipe with downward Eliminates condensation sweating on chilled with water repellant.
load only. Jackets: Galvanized steel ASTM A-653.
water risers
Other: Glue: Industrial contact adhesive
Structural Inserts: High-density calcium silicate
For handling both upward and downward
asbestos free, treated with water repellant.
loads, see E2100 Performance test results on file: Steel Straps/Base:Carbon steel ASTM A-36.
Temperature Range: Available upon request. Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Other coatings available upon request.
Add U after the model number (i.e., E1100U)
Formal submittal sheets available

www.pipeshields.com/e1100 103
Pipe
Shields Model E1200, Model E1210,
Inc. Model E1220, Model E1230
E1000 Insulated Pipe Riser Clamps for Downward Loads

B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) One pair thrust plates supplied loose for field Note: For higher load ratings, see: E1300.
welding, top only. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
2 750 0.63 0.50 0.50 x 3.00 1.50 0.625 4.19 6.19 5.63 5.25 7.25 7.75 6.25 8.25 9.75 7.31 9.31 11.88
2 1/2 900 0.63 0.50 0.50 x 3.00 1.50 0.625 4.44 6.44 6.13 5.75 7.75 8.75 6.75 8.75 10.75 7.81 9.81 12.88
3 1200 0.63 0.50 0.50 x 3.00 1.50 0.625 4.72 6.72 6.69 5.75 7.75 8.75 6.75 8.75 10.75 7.81 9.81 12.88
4 1800 0.63 0.50 0.50 x 4.00 2.00 0.625 5.25 7.25 7.75 6.25 8.25 9.75 7.31 9.31 11.88 8.31 10.31 13.88
5 2400 0.63 0.50 0.50 x 4.00 2.00 0.625 5.75 7.75 8.75 6.75 8.75 10.75 7.81 9.81 12.88 8.94 10.94 15.13
6 3000 0.88 0.50 0.50 x 5.00 3.00 0.625 6.25 8.25 9.75 7.31 9.31 11.88 8.31 10.31 13.88 9.44 11.44 16.13
8 3900 0.88 0.50 0.50 x 5.00 3.00 0.625 7.31 9.31 11.88 8.31 10.31 13.88 9.44 11.44 16.13 10.44 12.44 18.13
10 4800 0.88 0.50 0.50 x 6.00 4.00 0.75 8.44 10.69 13.88 9.56 11.81 16.13 10.56 12.81 18.13 11.56 13.81 20.13
12 5100 1.13 0.50 0.50 x 6.00 4.00 0.75 9.56 11.81 16.13 10.56 12.81 18.13 11.56 13.81 20.13 12.56 14.81 22.13
14 6000 1.13 0.50 0.50 x 6.00 4.00 0.75 10.06 12.31 17.13 11.06 13.31 19.13 12.06 14.31 21.13 13.06 15.31 23.13
16 6900 1.13 0.50 0.50 x 7.00 5.00 0.88 11.19 13.44 19.13 12.19 14.44 21.13 13.19 15.44 23.13 14.19 16.44 25.13
18 7500 1.13 0.50 0.50 x 7.00 5.00 0.88 12.19 14.44 21.13 13.19 15.44 23.13 14.19 16.44 25.13 15.19 17.44 27.13
20 8100 1.13 0.50 0.50 x 7.00 5.00 0.88 13.19 15.44 23.13 14.19 16.44 25.13 15.19 17.44 27.13 16.19 18.44 29.13
24 8400 1.13 0.50 0.50 x 7.00 5.00 0.88 15.19 17.69 27.13 16.19 18.69 29.13 17.19 19.69 31.13 18.19 20.69 33.13

Application: Features: Material Data:


Model E1200 through E1230 is designed for All pipe sizes E1200 - E1230: specification document: No. 206.
use on:
Easy installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E1200 A36 Carbon-Steel
Chilled water Gas E1210 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E1220 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E1230 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium Silicate asbestos-free, treated
Vertical runs of insulated pipe with downward Eliminates condensation sweating on chilled with water repellant.
load only. Jackets: Galvanized Steel ASTM A-653.
water risers
Glue: Industrial contact adhesive
Other:
Structural Inserts: High-density calcium silicate
For handling both upward and downward asbestos free, treated with water repellant.
loads, see E2200 Performance test results on file: Steel Straps/Base:Carbon Steel ASTM A-36.
Available upon request. Fasteners: ASTM A-307 plated.
Temperature Range:
Standard: +40F to +1200F CalSil Insulation Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request.
Other coatings available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., E1200U) Formal Submittal Sheets available

104 www.pipeshields.com/e1200
Pipe
Model E1300, Model E1310, Shields
Model E1320, Model E1330 E1000
Insulated Pipe Riser Clamps for Downward Loads Inc.

B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) One pair thrust plates supplied loose for field welding, top only.
Note: For higher load ratings contact factory. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
12 6800 1.13 0.50 0.50 x 7.00 5.00 0.875 9.69 11.94 16.13 10.69 12.94 18.13 11.69 13.94 20.13 12.69 14.94 22.13
14 8000 1.13 0.50 0.50 x 7.00 5.00 0.875 10.19 12.44 17.13 11.19 13.44 19.13 12.19 14.44 21.13 13.19 15.44 23.13
16 9200 1.13 0.63 0.63 x 7.00 5.00 1.00 11.44 13.69 19.38 12.44 14.69 21.38 13.44 15.69 23.38 14.44 16.69 25.38
18 10000 1.13 0.63 0.63 x 7.00 5.00 1.00 12.44 14.69 21.38 13.44 15.69 23.38 14.44 16.69 25.38 15.44 17.69 27.38
20 10800 1.13 0.63 0.63 x 7.00 5.00 1.00 13.44 15.69 23.38 14.44 16.69 25.38 15.44 17.69 27.38 16.44 18.69 29.38
24 11200 1.13 0.63 0.63 x 7.00 5.00 1.25 15.69 18.19 27.38 16.69 19.19 29.38 17.69 20.19 31.38 18.69 21.19 33.38

Application: Features: Material Data:

Model E1300 through E1330 is designed for All pipe sizes E1300 - E1330: specification document: No. 206.
use on: Easy installation Steel Inner Thrust Plates:
Hot water Steam Positive stop - axially downward Model ASTM For Pipe Material
Cold water Air May be supported from below or above E1300 A36 Carbon-Steel
Chilled water Gas Overlapping galvanized sheet metal jacket E1310 A387GR.22 Chrome-Moly
E1320 A515GR.70 Carbon Silicon
Dual temperature Vacuum Insulating structural inserts for load transfer E1330 A304L Stainless Steel
Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Eliminates condensation sweating on chilled with water repellant.
Intended for installation on: Jackets: Galvanized steel ASTM A-653.
Vertical runs of insulated pipe with downward water risers
Glue: Industrial contact adhesive
load only.
Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
Other: Performance test results on file: Steel Straps/Base:Carbon steel ASTM A-36.
For handling both upward and downward
Available upon request. Fasteners: ASTM A-307 plated.
loads, see E2300
Coating: Primer coated or hot dipped galvanized

Temperature Range: Other coatings available upon request.


Standard: +40F to +1200F CalSil Insulation Formal submittal sheets available
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., E1300U)

www.pipeshields.com/e1300 105
Pipe
Shields Model E2000, Model E2010,
Inc. Model E2020, Model E2030 Insulated Pipe Riser Clamps for Upward or Downward Loads
E2000
B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) Two pair thrust plates supplied loose for field Note: For higher load ratings, see: E2100.
welding, top and bottom. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
2 250 0.63 0.25 0.25 x 3.00 1.50 0.625 3.69 5.69 5.13 4.75 6.75 7.25 5.75 7.75 9.25 6.81 8.81 11.38
2 1/2 300 0.63 0.25 0.25 x 3.00 1.50 0.625 3.94 5.94 5.63 5.25 7.25 8.25 6.25 8.25 10.25 7.31 9.31 12.38
3 400 0.63 0.25 0.25 x 3.00 1.50 0.625 4.22 6.22 6.19 5.25 7.25 8.25 6.25 8.25 10.25 7.31 9.31 12.38
4 600 0.63 0.25 0.25 x 3.00 1.50 0.625 4.75 6.75 7.25 5.75 7.75 9.25 6.81 8.81 11.38 7.81 9.81 13.38
5 800 0.63 0.25 0.25 x 3.00 1.50 0.625 5.25 7.25 8.25 6.25 8.25 10.25 7.31 9.31 12.38 8.44 10.44 14.63
6 1000 0.63 0.25 0.25 x 4.00 2.00 0.625 5.75 7.75 9.25 6.81 8.81 11.38 7.81 9.81 13.38 8.94 10.94 15.63
8 1300 0.63 0.25 0.25 x 4.00 2.00 0.625 6.81 8.81 11.38 7.81 9.81 13.38 8.94 10.94 15.63 9.94 11.94 17.63
10 1600 0.63 0.38 0.38 x 5.00 3.00 0.625 8.06 10.31 13.63 9.19 11.44 15.88 10.19 12.44 17.88 11.19 13.44 19.88
12 1700 0.63 0.38 0.38 x 5.00 3.00 0.625 9.19 11.44 15.88 10.19 12.44 17.88 11.19 13.44 19.88 12.19 14.44 21.88
14 2000 0.88 0.38 0.38 x 5.00 3.00 0.625 9.69 11.94 16.88 10.69 12.94 18.88 11.69 13.94 20.88 12.69 14.94 22.88
16 2300 0.88 0.38 0.38 x 5.00 3.00 0.625 10.69 12.94 18.88 11.69 13.94 20.88 12.69 14.94 22.88 13.69 15.94 24.88
18 2500 0.88 0.38 0.38 x 5.00 3.00 0.625 11.69 13.94 20.88 12.69 14.94 22.88 13.69 15.94 24.88 14.69 16.94 26.88
20 2700 0.88 0.38 0.38 x 5.00 3.00 0.625 12.69 14.94 22.88 13.69 15.94 24.88 14.69 16.94 26.88 15.69 17.94 28.88
24 2800 0.88 0.38 0.38 x 5.00 3.00 0.625 14.69 17.19 26.88 15.69 18.19 28.88 16.69 19.19 30.88 17.69 20.19 32.88

Application: Features: Material Data:


Model E2000 through E2030 is designed for All pipe sizes E2000 - E2030: specification document: No. 206.
use on:
Easy installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially upward or downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E2000 A36 Carbon-Steel
Chilled water Gas E2010 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E2020 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E2030 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Vertical runs of insulated pipe with upward and/ Eliminates condensation sweating on chilled with water repellant.
or downward load. Jackets: Galvanized steel ASTM A-653.
water risers
Glue: Industrial contact adhesive
Other: Structural Inserts: High-density calcium silicate
For handling downward loads only, see E1000 asbestos free, treated with water repellant.
Performance test results on file: Steel Straps/Base:Carbon steel ASTM A-36.
Temperature Range: Available upon request. Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Coating: Primer coated or hot dipped galvanized
Note: Up to 1800F available upon request.
Cryogenic: -275F to +275F Urethane Insulation. Other coatings available upon request.
Add U after the model number (i.e., E2000U)
Formal Submittal Sheets available

106 www.pipeshields.com/e2000
Pipe
Model E2100, Model E2110, Shields
Model E2120, Model E2130 Insulated Pipe Riser Clamps for Upward or Downward Loads Inc.
E2000
B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) Two pairs thrust plates supplied loose for field Note: For higher load ratings, see: E2200.
welding, top and bottom. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
2 500 0.63 0.38 0.38 x 3.00 1.50 0.625 3.94 6.19 5.38 5.00 7.25 7.5 6.00 8.25 9.5 7.06 9.31 11.63
2 1/2 600 0.63 0.38 0.38 x 3.00 1.50 0.625 4.19 6.44 5.88 5.50 7.75 8.5 6.50 8.75 10.5 7.56 9.81 12.63
3 800 0.63 0.38 0.38 x 3.00 1.50 0.625 4.47 6.72 6.44 5.50 7.75 8.5 6.50 8.75 10.5 7.56 9.81 12.63
4 1200 0.63 0.38 0.38 x 3.00 1.50 0.625 5.00 7.25 7.5 6.00 8.25 9.5 7.06 9.31 11.63 8.06 10.31 13.63
5 1600 0.63 0.38 0.38 x 4.00 2.00 0.625 5.50 7.75 8.5 6.50 8.75 10.5 7.56 9.81 12.63 8.69 10.94 14.88
6 2000 0.63 0.38 0.38 x 4.00 2.00 0.625 6.00 8.25 9.5 7.06 9.31 11.63 8.06 10.31 13.63 9.19 11.44 15.88
8 2600 0.63 0.50 0.50 x 4.00 2.00 0.625 7.31 9.81 11.88 8.31 10.81 13.88 9.44 11.94 16.13 10.44 12.94 18.13
10 3200 0.88 0.50 0.50 x 5.00 3.00 0.625 8.31 10.81 13.88 9.44 11.94 16.13 10.44 12.94 18.13 11.44 13.94 20.13
12 3400 0.88 0.50 0.50 x 5.00 3.00 0.625 9.44 11.94 16.13 10.44 12.94 18.13 11.44 13.94 20.13 12.44 14.94 22.13
14 4000 0.88 0.50 0.50 x 5.00 3.00 0.75 10.06 12.69 17.13 11.06 13.69 19.13 12.06 14.69 21.13 13.06 15.69 23.13
16 4600 0.88 0.50 0.50 x 6.00 4.00 0.75 11.06 13.69 19.13 12.06 14.69 21.13 13.06 15.69 23.13 14.06 16.69 25.13
18 5000 0.88 0.50 0.50 x 6.00 4.00 0.75 12.06 14.69 21.13 13.06 15.69 23.13 14.06 16.69 25.13 15.06 17.69 27.13
20 5400 0.88 0.50 0.50 x 6.00 4.00 0.75 13.06 15.69 23.13 14.06 16.69 25.13 15.06 17.69 27.13 16.06 18.69 29.13
24 5600 0.88 0.50 0.50 x 6.00 4.00 0.75 15.06 17.69 27.13 16.06 18.69 29.13 17.06 19.69 31.13 18.06 20.69 33.13

Application: Features: Material Data:


Model E2100 through E2130 is designed for All pipe sizes E2100 - E2130: specification document: No. 206.
use on:
Easy Installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially upward or downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E2100 A36 Carbon-Steel
Chilled water Gas E2110 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E2120 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E2130 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Vertical runs of insulated pipe with upward and/ Eliminates condensation sweating on chilled with water repellant.
or downward load. Jackets: Galvanized steel ASTM A-653.
water risers
Glue: Industrial contact adhesive
Other:
Structural Inserts: High-density calcium silicate
For handling downward loads only, see E1200 asbestos free, treated with water repellant.
Performance Test Results on File: Steel Straps/Base:Carbon steel ASTM A-36.
Temperature Range: Available upon request. Fasteners: ASTM A-307 plated.
Standard: +40F to +1200F CalSil Insulation
Note: Up to 1800F available upon request. Coating: Primer coated or hot dipped galvanized
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., E2100U) Other coatings available upon request.

Formal submittal sheets available

www.pipeshields.com/e2100 107
Pipe
Shields Model E2200, Model E2210,
Inc. Model E2220, Model E2230 Insulated Pipe Riser Clamps for Upward or Downward Loads

E2000
B
C

F G

PIPE

A H

a) If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b) Two pairs thrust plates supplied loose for field Note: For higher load ratings, see: E2200.
welding, top and bottom. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
2 750 0.63 0.38 0.38 x 3.00 1.50 0.625 3.94 6.19 5.38 5.00 7.25 7.5 6.00 8.25 9.5 7.06 9.31 11.63
2 1/2 900 0.63 0.38 0.38 x 3.00 1.50 0.625 4.19 6.44 5.88 5.50 7.75 8.5 6.50 8.75 10.5 7.56 9.81 12.63
3 1200 0.63 0.38 0.38 x 3.00 1.50 0.625 4.47 6.72 6.44 5.50 7.75 8.5 6.50 8.75 10.5 7.56 9.81 12.63
4 1800 0.63 0.38 0.38 x 3.00 1.50 0.625 5.00 7.25 7.5 6.00 8.25 9.5 7.06 9.31 11.63 8.06 10.31 13.63
5 2400 0.63 0.38 0.38 x 4.00 2.00 0.625 5.50 7.75 8.5 6.50 8.75 10.5 7.56 9.81 12.63 8.69 10.94 14.88
6 3000 0.63 0.38 0.38 x 4.00 2.00 0.625 6.00 8.25 9.5 7.06 9.31 11.63 8.06 10.31 13.63 9.19 11.44 15.88
8 3900 0.63 0.50 0.50 x 4.00 2.00 0.625 7.31 9.81 11.88 8.31 10.81 13.88 9.44 11.94 16.13 10.44 12.94 18.13
10 4800 0.88 0.50 0.50 x 5.00 3.00 0.625 8.31 10.81 13.88 9.44 11.94 16.13 10.44 12.94 18.13 11.44 13.94 20.13
12 5100 0.88 0.50 0.50 x 5.00 3.00 0.625 9.44 11.94 16.13 10.44 12.94 18.13 11.44 13.94 20.13 12.44 14.94 22.13
14 6000 0.88 0.50 0.50 x 5.00 3.00 0.75 10.06 12.69 17.13 11.06 13.69 19.13 12.06 14.69 21.13 13.06 15.69 23.13
16 6900 0.88 0.50 0.50 x 6.00 4.00 0.75 11.06 13.69 19.13 12.06 14.69 21.13 13.06 15.69 23.13 14.06 16.69 25.13
18 7500 0.88 0.50 0.50 x 6.00 4.00 0.75 12.06 14.69 21.13 13.06 15.69 23.13 14.06 16.69 25.13 15.06 17.69 27.13
20 8100 0.88 0.50 0.50 x 6.00 4.00 0.75 13.06 15.69 23.13 14.06 16.69 25.13 15.06 17.69 27.13 16.06 18.69 29.13
24 8400 0.88 0.50 0.50 x 6.00 4.00 0.75 15.06 17.69 27.13 16.06 18.69 29.13 17.06 19.69 31.13 18.06 20.69 33.13

Application: Features: Material Data:


Model E2200 through E2230 is designed for All pipe sizes E2200 - E2230: specification document: No. 209.
use on:
Easy installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially upward or downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E2200 A36 Carbon-Steel
Chilled water Gas E2210 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E2220 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E2230 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Vertical runs of insulated pipe with upward and/ Eliminates condensation sweating on chilled with water repellant.
or downward load. Jackets: Galvanized steel ASTM A-653.
water risers
Other: Glue: Industrial contact adhesive
Structural Inserts: High-density calcium silicate
For handling downward loads only, see E1200
asbestos free, treated with water repellant.
Performance Test Results on File: Steel Straps/Base:Carbon steel ASTM A-36.
Temperature Range:
Standard: +40F to +1200F CalSil Insulation Available upon request. Fasteners: ASTM A-307 plated.
Note: Up to 1800F available upon request. Coating: Primer coated or hot dipped galvanized
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., E2200U) Other coatings available upon request.

Formal submittal sheets available

108 www.pipeshields.com/e2200
Pipe
Model E2300, Model E2310, Shields
Model E2320, Model E2330 Insulated Pipe Riser Clamps for Upward or Downward Loads Inc.
E2000
B
C

F G

PIPE

A H

a. If thrust plate thickness B is greater than


pipe wall thickness, consult factory.

b. Two pairs thrust plates supplied loose for field welding, top and bottom.
Note: For higher load ratings contact factory. Available in all insulation thickness.

Vert
Pipe Load Insul. Thk. = 1" Insul. Thk. = 2" Insul. Thk. = 3" Insul. Thk. = 4"
Size lbs A B C D E F G H F G H F G H F G H
12 6800 1.13 0.50 0.50 x 7.00 5.00 0.875 9.69 11.94 16.13 10.69 12.94 18.13 11.69 13.94 20.13 12.69 14.94 22.13
14 8000 1.13 0.50 0.50 x 7.00 5.00 0.875 10.19 12.44 17.13 11.19 13.44 19.13 12.19 14.44 21.13 13.19 15.44 23.13
16 9200 1.13 0.63 0.63 x 7.00 5.00 1.00 11.44 13.69 19.38 12.44 14.69 21.38 13.44 15.69 23.38 14.44 16.69 25.38
18 10000 1.13 0.63 0.63 x 7.00 5.00 1.00 12.44 14.69 21.38 13.44 15.69 23.38 14.44 16.69 25.38 15.44 17.69 27.38
20 10800 1.13 0.63 0.63 x 7.00 5.00 1.00 13.44 15.69 23.38 14.44 16.69 25.38 15.44 17.69 27.38 16.44 18.69 29.38
24 11200 1.13 0.63 0.63 x 7.00 5.00 1.25 15.69 18.19 27.38 16.69 19.19 29.38 17.69 20.19 31.38 18.69 21.19 33.38

Application: Features: Material Data:


Model E2300 through E2330 is designed for All pipe sizes E2300 - E2330: specification document: No. 209.
use on:
Easy installation Steel Inner Thrust Plates:
Hot water Steam
Positive stop - axially upward or downward Model ASTM For Pipe Material
Cold water Air
May be supported from below or above E2300 A36 Carbon-Steel
Chilled water Gas E2310 A387GR.22 Chrome-Moly
Overlapping galvanized sheet metal jacket
Dual temperature Vacuum E2320 A515GR.70 Carbon Silicon
Insulating structural inserts for load transfer E2330 A304L Stainless Steel
Intended for installation on: Other I.D.s and/or O.D.s Available on Request Insulation: Calcium silicate asbestos-free, treated
Vertical runs of insulated pipe with upward and/ Eliminates condensation sweating on chilled with water repellant.
or downward load. Jackets: Galvanized steel ASTM A-653.
water risers
Other: Glue: Industrial contact adhesive
Structural Inserts: High-density calcium silicate
For handling downward loads only, see E1300
asbestos free, treated with water repellant.
Performance test results on file: Steel Straps/Base:Carbon steel ASTM A-36.
Temperature Range:
Standard: +40F to +1200F CalSil Insulation Available upon request. Fasteners: ASTM A-307 plated.
Note: Up to 1800F available upon request. Coating: Primer coated or hot dipped galvanized.
Cryogenic: -275F to +275F Urethane Insulation.
Add U after the model number (i.e., E2300U). Other coatings available upon request.

Formal submittal sheets available

www.pipeshields.com/e2300 109
Pipe
Shields
Inc. Introduction: Section G

INTRODUCTION
SECTION G

PIPE CLAMPS, PIPE GUIDE STRAPS, PIPE GUIDE U-BOLTS

APPLICATION For installation on standard 1-5/8 width framing channel.

The models listed in the Section Index are selected based upon the following considerations:

FOR USE WITH


Bare Pipe
Bare Copper Tubing
Insulated Pipe Support

PURPOSE
Clamp
Guide

DUTY
Light
Heavy

If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
707-447-0030 or 1-800-538-7007.

Please acquaint yourself with the selection guide at the front of this catalog and the section index on
the page following this introduction, for assistance in determining the most appropriate support for your
application.

110
Pipe
Shields
Section G Index Inc.

PIPE CLAMPS, PIPE GUIDE STRAPS, PIPE GUIDE U-BOLTS


FOR USE ON PURPOSE
BARE
G1000
BARE COPPER INSULATED
MODEL PIPE TUBING PIPE SUPPORT CLAMP GUIDE DUTY

G1200

G1000 X X X LIGHT

G2000

G1200 X X X LIGHT

X X
HEAVY
G2200

G2000 X X

G3000

G2200 X X X HEAVY

G3000 X X X LIGHT
TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 2 IPS
3. Insulation Thickness 2-1/2
4. Model Number G1000
5. For use on (bare pipe or insulated pipe support model) A1000

EXAMPLE: (20) 2 x 2-1/2 G1000 (For use on A1000)

www.pipeshields.com/g-series 111
Pipe
Shields G1000
Inc. Model G1000 Pipe Shield Clamp

A307 PLD. BOLT 1/4 CLR 1 1/4"

"A" A36 STL.


1 3/8" STRAPS
PSI MODEL
A SERIES

B.O.P.

T.O.S.

1 5/8"
REF

*PSI A-Series Model purchased separately

Maximum
Lateral
Pipe Size Load - Lbs
3/4 50 Insulation
1 50 Thicknesses
1-1/4 50 0
1-1/2 50 1/2
2 50 3/4
2-1/2 50 1
3 50 1-1/2
3-1/2 50 2
4 50 2-1/2
5 50 3
6 50 3-1/2
8 50 4
10 50 TABLE II
12 50
TABLE I

Contact factory for pipe sizes or insulation thicknesses not shown.

Note: For neoprene lined clamps, see: G1200; For bolt-on clamps,
see: G2000; For U-bolts, see: G3000.

Insulation and Framing Channel sold separately.

Application: Features: Material Data:

Model G1000 is designed for use on: Easy installation G1000: Applicable PSI specification document:
Hot Water Steam Rugged No. 208.
Cold Water Air Fits standard 1-5/8 width framing channel Steel A: Galvanized steel 11 ga. X 1-1/4 wide
Sized to clamp on O.D. of bare pipe ASTM A-653
Chilled Water Gas
Dual Temperature Vacuum Sized to clamp on O.D. of insulated pipe Fasteners: ASTM A-307 Plated.
support models A1000 through A7400 Formal submittal sheets available
Complete with top bolt and nut
Intended for installation on: Other sizes available on request
Standard 1-5/8 width framing channels

112 www.pipeshields.com/g1000
Pipe
Neoprene Shields
Model G1200 G1200
Pipe Clamp Tubing Clamp Sleeved Inc.

A307 PLD. BOLT 1/4 CLR 1 1/4"

"A" A36 STL.


1 3/8" STRAPS
1/4"x2"
NEOPRENE

1 5/8"
REF

Maximum
Lateral
Pipe Size Load - Lbs.
3/4 50 Copper Maximum
1 50 Tubing Lateral
1-1/4 50 O.D. Load - Lbs.
1-1/2 50 1-1/8 50
2 50 1-3/8 50
2-1/2 50 1-5/8 50
3 50 2-1/8 50
3-1/2 50 2-5/8 50
4 50 3-1/8 50
5 50 3-5/8 50
6 50 4-1/8 50
8 50 TABLE II
10 50
12 50
TABLE I

Contact factory for pipe sizes not shown.

Note: For neoprene lined clamps, see: G1000; For bolt-on clamps,
see: G2200; For U-bolts, see: G3000

Framing Channel sold separately.

Application: Features: Material Data:

Model G1200 is designed for use on: Easy installation G1200: Applicable PSI specification document:
Hot water Air Rugged No. 208.
Fits standard 1-5/8 width framing channel Steel A: Galvanized Steel 11 ga. X 1-1/4 wide
Cold water Gas
ASTMA-653
Chilled water Vacuum Sized to clamp on O.D. of bare pipe or bare
Fasteners: ASTMA-307 Plated.
Dual temperature
copper tubing
Sleeve : 1/4 thick X 2 wide closed cell
Vibration isolator
Complete with top bolt and nut neoprene..
Intended for installation on: Other sizes available on request Formal submittal sheets available
Standard 1-5/8 width Framing Channels Neoprene sleeve eliminates galvanic action
between clamp, framing channel and copper
tubing.

www.pipeshields.com/g1200 113
Pipe
Shields
Inc. G2000 Model G2000 Pipe Clamp Shield Guide Strap

A307 PLD. BOLT 0 CLR 1 1/2"

1 /16" CLR
"A" A36 STL.
(TYP) 1 3/4" STRAPS
(TYP 3 PLCS)
PSI MODEL
A SERIES

1/2-13 UNC
1 5/8"
1/16" CLR
CHANNEL NUT
REF.
(TYP)

*PSI A-Series Model purchased separately


Maximum
Lateral
Pipe Size Load - Lbs.
Insulation
3/4 200 Thicknesses
1 200 0
1-1/4 200
1/2
1-1/2 200
3/4
2 400
2-1/2 400 1
1-1/2
3 400
2
3-1/2 400 2-1/2
4 400
3
5 400
3-1/2
6 400 4
8 400
TABLE II
10 400
12 400
TABLE I

Contact factory for pipe sizes or insulation thicknesses not shown.

Note: For neoprene lined straps, see: G2200; For pipe/shield


clamps, see: G1000; For U-bolts, see: G3000.

Insulation and Framing Channel sold separately.

Application: Features: Material Data:

Model G2000 is designed for use on: Easy installation G2000: Applicable PSI specification
Hot Water Steam Rugged document: No. 208.
Cold Water Air Bolts to standard 1-5/8 width framing channel
Steel A: ASTM A-36 1/4 X 1-1/2
Chilled Water Gas Sized to clamp on O.D. of bare pipe
Fasteners: ASTM A-307 Plated.
Dual Temperature Vacuum Sized to provide approximately 1/16 radial
clearance around O.D. of insulated pipe Coating: Primer coating or hot dipped
support models A1000 through A7400 galvanized. Other coatings available upon
Intended for installation on:
Complete with top bolt and nut plus two (2) tie request.
Standard 1-5/8 width Framing Channels down bolts and channel nuts with springs
Other sizes available on request
Formal submittal sheets available

114 www.pipeshields.com/g2000
Pipe
Neoprene Shields
G2200
Model G2200 Pipe Clamp Tubing Clamp Sleeved Inc.

A307 PLD. BOLT 0 CLR 1 1/2"

"A" A36 STL.


1 3/4" STRAPS
(TYP 3 PLCS)
1/4"x2"
NEOPRENE

1/2-13 UNC
1 5/8"
CHANNEL NUT
REF.

Maximum
Lateral
Pipe Size Load - Lbs
Copper Maximum
3/4 200
Tubing Lateral
1 200 O.D. Load - Lbs
1-1/4 200
1-1/2 200 1-1/8 200
2 400 1-3/8 200
2-1/2 400 1-5/8 200
3 400 2-1/8 400
2-5/8 400
3-1/2 400 3-1/8 400
4 400
3-5/8 400
5 400
4-1/8 400
6 400 TABLE II
8 400
10 400
12 400
TABLE I

Contact factory for pipe sizes not shown.

Note: For neoprene lined clamps, see: G2000; For bolt-on clamps,
see: G2200; For U-bolts, see: G3000.

Framing Channel sold separately.

Application: Features: Material Data:

Model G2200 is designed for use on: Easy installation G2200: Applicable PSI specification
Hot water Air Rugged document: No. 208.
Cold water Gas Bolts to standard 1-5/8 width framing channel Steel A: ASTM A-36 1/4 X 1-1/2
Chilled water Vacuum Sized to clamp on O.D. of bare pipe or bare Fasteners: ASTM A-307 Plated.
Dual temperature copper tubing. Sleeve : 1/4 thick X 2 wide closed cell
Vibration isolator neoprene.
Complete with top bolt and nut plus two Coating: Primer coated or hot dipped
Intended for installation on: (2) tie down bolts and channel nuts with galvanized. Other coatings available upon
Standard 1-5/8 width Framing Channels springs. request.
Other sizes available on request
Neoprene sleeve eliminates galvanic Formal submittal sheets available
action between clamp, framing and
copper tubing.

www.pipeshields.com/g2200 115
Pipe
Shields
Inc. Model G3000 Pipe Guide U-Bolt Shield Guide U-Bolt

G3000

1/16" CLR
"D" ROD
(TYP)

PSI MODEL
A SERIES

A307
PLD. BOLTS
B

*PSI A-Series Model purchased separately

Insulation and plate sold separately.

Contact factory for pipe, tube sizes, or insulation thicknesses not shown.

Note: For pipe clamps, see: G1000, G1200, G2000, G2200; For shield
clamps, see: G1000; For shield guide straps, see: G2000.

Maximum Insulation Thickness


Pipe Lateral D-Rod BARE 1/2 3/4 1 1-1/2 2 2-1/2 3 4
Size Load-Lbs Thread A B A B A B A B A B A B A B A B A B
1/2 50 1/4-20 1.25 2.75 2.5 3.38 2.88 3.63 3.38 3.88 4.5 4.38 5.5 4.88 7.13 5.88 8.13 6.25 10.13 7.25
3/4 50 1/4-20 1.5 3 2.5 3.38 2.88 3.63 3.38 3.88 4.5 4.38 5.5 4.88 7.13 5.88 8.13 6.25 10.13 7.25
1 50 1/4-20 1.75 3 2.88 3.63 3.38 3.88 4 4.25 5 4.63 6.25 5.25 7.13 5.88 8.13 6.25 10.13 7.25
1-1/4 50 3/8-16 2.25 3.5 3.38 4.13 3.38 4.13 4.13 4.38 5.63 5.13 6.25 5.5 7.25 6 8.25 6.50 10.25 7.50
1-1/2 50 3/8-16 2.5 3.63 3.5 4.13 4.13 4.38 4.63 4.63 5.63 5.13 7.25 6 8.25 6.5 9.25 7.00 11.25 8.00
2 50 3/8-16 2.88 3.88 4.13 4.38 4.63 4.63 5.13 4.88 6.25 5.5 7.25 6 8.25 6.5 9.25 7.00 11.25 8.00
2-1/2 50 1/2-13 3.5 4.38 4.88 4.88 5.38 5.13 5.88 5.38 7.5 6.25 8.5 6.75 9.5 7.25 10.50 7.75 12.50 8.75
3 50 1/2-13 4.13 4.63 5.38 5.13 5.88 5.38 6.38 5.63 7.5 6.25 8.5 6.75 9.5 7.25 10.50 7.75 12.50 8.75
3-1/2 50 1/2-13 4.63 4.88 5.88 5.38 6.38 5.75 7.5 6.25 8.5 6.75 9.5 8.63 10.5 7.75 11.50 8.25 13.50 9.25
4 50 1/2-13 5.13 5.13 6.38 5.75 7.5 6.25 7.5 6.25 8.5 6.75 9.5 8.63 10.5 7.75 11.50 8.25 13.50 9.25
TABLE I

Application: Features: Material Data:

Model G3000 is designed for use on: Easy installation G3000: Applicable PSI specification document:
Hot water Steam Sized to provide approximately 1/16 to 1/8 No.208
radial clearance around O.D. of bare pipe or Steel: Low carbon threaded rod.
Cold water Air
insulated pipe support models A1000 through
Chilled water Gas A7000 Hex Nuts: ASTM A-563 Gr. A.
Dual temperature Vacuum Complete with 4 hex nuts and 4 plain washers Coating: Primer coating or hot dipped
galvanized. Other coatings available upon
Other sizes available on request
request.
Formal submittal sheets available

116 www.pipeshields.com/g3000
Pipe
Shields
Inc.

1. 2.

3.
1. Insulated pipe support with
temperature range of 40F to 1200F.

2. Cryogenic shoes.

3. Finished with hot dipped galvanized.

4. Pre-insulated pipe supports coated


with red oxide paint.

4.

117
Pipe
Shields
Inc.

1.

2.

4.

3.
1. Cryogenic shoes.

2. Pre-insulated pipe support with hot


dipped galvanized finish.

3. Cold Shoes.

4.Hot dipped galvanized finish on high


temperature pipe supports.

5. Pre-insulated supports for an LNG


plant in Algeria.

5.

118
Pipe
Shields
Completed Projects Inc.
Aerospace Banks

Bell Helicopter Bank of America (Los Angeles & Berkeley)


Boeing Colorado National Bank (Denver, CO)
Hughes Aircraft Commercial National Bank (Shreveport)
Hughes Helicopter Crocker Bank (Salinas, CA)
Lockheed First Federal Savings & Loan (Calhoun, CA)
Martin Marietta First Interstate Bank (Denver, CO)
McDonnell-Douglas Aircraft Household Bank (Monterey, CA)
NASA San Francisco, CA Federal Savings (CA)
Security Savings & Loan (Salina, KS)
Airports Utica Savings Bank (Utica)

American Airlines Alliance Airport (Ft.Worth,TX) Breweries


American Airlines (Tulsa,OK)
Dulles International Airport Utility Bldg. Adolph Coors (Golden,CO)
Fresno Air Terminal Miller (Trenton, OH)
Greater Orlando International Airport Molson (Montreal, Quebec)
Greensboro/High Point/Winston Salem Airport
Greensboro Regional Airport Cogeneration
Luis Munoz Marin Airport (Hato Rey, PR)
Portland International Airport AES/Deepwater Cogeneration Plant (TX)
Raleigh-Durham Airport Altavista Cogen (VA)
Riyadh International Airport Basic Foods (CA)
San Francisco, CA Airport CFI Cogeneration Plant
Stapleton International Airport California Portland Cement
CamdenCogeneration Plant (NJ)
Automotive CBC - SRC Combined Cycle Plant (CA)
Cogentrix (Rocky Mt, NC)
American Honda Dow Chemical-Phase I, II, III (LA)
Bendix Dow Elsta (The Netherlands)
BMW Dow Midland Cogen (Midland, Ml)
Chrysler Derwent Cogen (United Kingdom)
CPC Fisher Detroit Resource Recovery (Detroit, MI)
Cummins East County Regoinal Center
Firestone Encogen (Sweetwater, TX)
Ford Fraser Paper Co. (Edmunston, Canada)
General Motors Gilroy Foods (CA)
Goodyear GWF Power Systems
Hyundai Hershey Chocolate Cogeneration Plant (PA)
Mack Truck Hopewell Cogen (VA)
Navistar Louisiana-Pacific (CA)
Nippondenso LSWhitewater Cogen (WI)
Toyota Nevada Power (NV)
PT&T Cogeneration Facility (CA)
Pawtucket Cogen (RI)
RJ Reynolds (NC)
San Diego State University (CA)
Tampa Electric Co. (FL)
Teesside Cogen (Middlesbrough, UK)
TransCanada Kapuskasing
TransCanada North Bay

www.pipeshields.com/major-projects 119
Pipe
Shields
Inc. Completed Projects
Ultrasystems Alta Vista Cogen Sperry
Wabash River Generating (IN) Syntex
Western Cogen (CA) Tektronix
Texas Instruments
Commercial Trilogy
Varian
Denver International Airport Xerox
Dulles Airport
Henry Ford Health System Construction
NW Airlines
University of Michigan East Engineering Building Aker Construction, Inc.
University of Michigan Medical Science Caterpillar Tractor Co.
University of North Carolina Caterpillar Tractor Co. Bldg. D (Peoria, IL)
Caterpillar Tractor Co. Bldg. AD (Peoria, IL)
Computer Facilities Caterpillar Tractor Co. Bldg. N (Peoria, IL)
Caterpillar Tractor Co. Bldg. BB (Peoria, IL)
Alps Electronics Caterpillar Tractor Co. Bldg. J (Peoria, IL)
Amdahl Caterpillar Tractor Co. Bldg.W (Peoria, IL)
Burroughs Caterpillar Office Expansion (Peoria, IL)
Burroughs Wellcome Caterpillar Steam Heat (Mapleton, IL)
Digital Caterpillar Bldg. R2 (Mossville, IL)
Dysan Caterpillar Bldg. KK (East Peoria, IL)
Fairchild Ferguson
Fairchild Wafer Fabrication Lauren Engineers and Constructors, Inc.
Fujitsu Offenhauser Company
Gates Computer Quality Plus Services
General Electric Vibra-Conn
Hewlett-Packard Oregon
Hewlett-Packard California Correctional Facilities/Prisons
Hewlett-Packard Colorado
Hewlett-Packard Washington Avenal Medium Security Prison
Hewlett-Packard Ohio Baldwin County Courthouse & Jail (AL)
Hewlett-Packard Idaho Birmingham Jail Building (AL)
Honeywell Marine Bullock County Correctional Center
IBM California Medical Facility
Intel Carribbean Interconnect (PR) Fairfax Detention Center (Fairfax, VA)
InfelCUB (AZ) Fresno County Jail (CA)
Intel Oregon Jail Building (Birmingham, AL)
Intel Ireland North Dakota State Penetentiary
Intel Israel PeoriaCounty Jail (Peoria, IL)
Intel California Regional Justice Center (Kent, WA)
Intel New Mexico Southern Maximum Security Complex (CA)
International Rectifier Spring Creek Correctional Facility
Johnson Controls State Penitentiary (Bismarck, CA)
Micron Walla Walla State Penitentiary
Monolithic Memories
Motorola White Oak Food
NCR
National Semiconductor American Maize Products
Perkin-Elmer Basic
Signetics Beringer Vineyards

120 www.pipeshields.com/major-projects
Pipe
Shields
Completed Projects Inc.

Corn Products International Audrain County Medical Center (St. Louis, MO)
Del Monte Aultman Hospital (Canton,OH)
General Foods Bakersfield Memorial Hospital (Bakersfield, CA)
General Mills Baptist Hospital (Birmingham, AL)
Gilroy Baptist Memorial Hospital East (Memphis, TN)
Hershey Chocolate Bartholomew Hospital (Columbus, IN)
Humboldt Creamery Beth Israel Hospital (Denver, CO)
Pepsi-Cola Boulder Community Hospital (Boulder, CO)
Peter Paul-Cadbury Brighton Community Hospital (Brighton, CO)
Pioneer National Foods Brooks Memorial Hospital (Dunkirk, NY)
Ragu Foods Childrens Hospital (San Francisco, CA)
Ralston Purina Community Memorial Hospital (Ventura, CA)
Wrigleys Gum Cottage Hospital (Santa Barbara, CA)
Crippled Childrens Hospital (Richmond, VA)
Highrises and Office Buildings Dameron Hospital (Stockton, CA)
David Grant Medical Facility (Fairfield, CA)
One Concord Center (Concord, CA) Delray Community Hospital (Delray Beach, FL)
101 California (San Francisco, CA) East & West Alabama Medical Center (AL)
12 Wyandotte Plaza (Kansas City) El Camino Hospital (Mountain View, CA)
#2 Corporate Center (Concord, CA) Fresno Community Hospital (Fresno, CA)
2405 Grand Building (Kansas City) Greenville Memorial Hospital (Greenville, SC)
333 Bush (San Francisco, CA) Guernsey Memorial Hospital (Cambridge, OH)
456 Montgomery (San Francisco, CA) Harrisburg State Hospital (Harrisburg, PA)
595 Market Street (San Francisco, CA) Holy Name of Jesus Hospital (Gadsden, AL)
The Broadmoor Hotel (Colorado Springs) Kaiser Hospital (Fontana, CA)
Bay Hill Four (San Bruno, CA) Kaiser Hospital (Oakland, CA)
Blount International Office Building (AL) Kaiser Hospital (Vallejo, CA)
Bowman Grey School/Med. Research Tower (NC) Kaiser Hospital (Sacramento, CA)
Capital South Hotel (Columbus, OH) Kaiser Hospital (West Los Angeles, CA)
Chevron (Denver, CO) Kaiser Medical Center (Denver, CO)
Chevron (San Ramon, CA) Kaiser Permanente Medical Center (Riverside,CA)
Crown Center (Kansas City, MO) Kaiser Permanente Medical Center (Vacaville, CA)
Dean Whitter Reynolds (Dallas, TX) Kaiser Sunset Hospital (Long Beach, CA)
DuPont (Research Triangle Park, NC) Lutheran General Hospital (Park Ridge, IL)
EastTower (Chicago, IL) Merritt Hospital (Oakland, CA)
Elihu Harris Office Bldg. (Oakland, CA) Mills Hospital (Marin, CA)
First Stamford Place (Stamford, CT) Moffitt Hospital (San Francisco, CA)
Georgia Power Co. Office Tower (Atlanta, GA) Mt. Zion Hospital (San Francisco, CA)
WW Grainger Corporate Hdqrtrs (Skoki, IL) New David Grant Medical Facility (Travis AFB)
Hacienda Midrise (Pleasanton, CA) Olive View MedicalCenter (Sylmar, CA)
Hilton Hotel (Cairo, Egypt) Pleasant Valley Hospital (Camarillo, CA)
MGM Grand (Las Vegas, NV) Porter Memorial Hospital (Denver, CO)
MGM Hotel (Reno,NV) Presbyterian Hospital (Denver, CO)
Mission Viejo Office Bldg (CO) Queen Alia Heart Institute (Ammaivjoidah)
Redding Medical Center (Redding, CA)
Hospitals Robert Packard Hospital (Syracuse, NY)
Rose Medical Center (Denver, CO)
Affiliated Hospital Center (Boston) Salinas Valley Memorial Hospital (Salinas, CA)
Aga Khan Hosp. & Med. College (Pakistan) San Francisco, CA General Hospital (San
Alta Bates Hospital (Berkeley, CA) Francisco,CA)
American Cancer Research (Denver, CO) Santa Monica Hospital (Santa Monica, CA)

www.pipeshields.com/major-projects 121
Pipe
Shields
Inc. Completed Projects
Shriners Hospital (Sacramento, CA) Laboratories
St. Francis Hospital (Memphis, TN)
St. Joseph Hospital (Denver,CO) Abbott-Ross Laboratories
St. Lukes Hospital (Tempe, AZ) Bio-Rad Labs
Stanford Medical Center (Stanford, CA) Cetus Labs
Sutter General Hospital (Sacramento, CA) Chem/Vet LabBuilding,University of Wyoming
Thunderbird Samaritan Hospital (Pheonix, AZ) Colorado State University Controlled Lab
Univ. of Cincinnati, OH General Hospital ( OH) Cutter Laboratories
Univ. of Michigan Burn Center (Detroit, MI) Genentech
Univ. of Michigan Hospital (Detroit, MI) Miles Lab (Clayton, NC)
VA Hospital (Martinez, CA) Newport Aquaculture Lab
VA Medical Centers Sandia Molten Salt Receiver
Ventura County Hospital (Ventura, CA) Sandia Radiation Hardening Circuits Facility
West Alabama Medical Center (Montgomery, AL) Sphio Research and Development
Surge Building - Stanford Hospital
Industrial Underwriters Laboratories
UC Berkeley SSCL Lab
3M UC Davis Agricultural Sciences Lab
Ascension Industries, Inc. UC Lawrence Livermore Lab Bldg. 490/494
Boeing 25-01 University of Delaware-Colburn Lab
Boeing 25-02 Zoecon Labs
Boeing 40-37
Boeing 40-41 Military and/or Government
Boeing Hot GasTest Facility
Boeing MBU-2 Air National Guard Hangar/Harrisburgh Intl
Boeing Site Development Airport
Boeing Skin & Spar Facility Ames Research, Moffett Field
Caterpillar Army Defense Depot Mech. Freight Term.
Chrysler Technology Center (Memphis)
Chrysler/CTC Environmental Lab Brooke Army Medical Center
Cummins Engine Cape Canaveral
Eastman Chemicals Castle AFB Medical/Dental Facility
Ford Cold Fluids David Grant Med. Fac. Travis AFB (Fairfield,CA)
Ford (Lima, OH) Elmendorf AFB, Satcom Ground Terminal
G.E. Silicones Federal Bureau of Investigation (San Francisco,
Genentech CA)
Huls America (R.C.) Fourth Antenna Raydome Support (Mathews,
Hyundai 100,000 MTA SM Plant NC)
Intel Energy Center (Folsom,CA) Hamilton AFB
Intel JP2 King Khalid Military City (Saudi Arabia)
Intel UF2 Kings Bay Rtl.
Intel-Rio Rancho Knights Ferry Administration Building
Kodak Lawrence Radiation Lab Building 3.2
Loctite Lowry AFB
Nissan Motor Manufacturing Medical/Dental Facility (Castle AFB)
Proctor & Gamble McClellan AFB (CA)
Toyota, Building 100 Navy Submarine Spt. Fac./Pier Steam Pit (San
Uniroyal Diego)
Pentagon
Sandia Radiation Hardening Facility
United Technology (Colorado Springs, CO)

122 www.pipeshields.com/major-projects
Pipe
Shields
Completed Projects Inc.

United Technologies Corporation (Coyote, CA) Sun Oil - Sun Refinery & Market
Warren AFB Tennessee Eastman - Eastman FGAP Proj.
Weapon Systems Support Facility (China Lake, CA) Unocal 250 KW Demp Plant
Wyoming International Guard (Cheyenne, WY) Vista Chemical
Westlake Styrene Corporation
Petrochemical Yukong Oxychem (China)

Allied Signal Pharmaceutical


Amoco Project
ARCO Chem American Pharmaseal
Ashland Petroleum Hydrogen Plant Bayer-Miles
ATOChem Ciba-Geigy Corporation
Chevron Asphalt Plant Eli Lilly
Chevron St. James Eli Lilly Building C644
China Petrochem Eli Lilly Bldg 98
Citcon Eli Lilly K8 Cafeteria
Cosmar Eli Lilly Research Center
CVIP, Inc Eli Lilly T29
DeepwaterIodines Eythyl Corporation
Dow Elsta Genentech - SSF
Dow Flame Kit Genentech - Vacaville
Dow Hydro Carbons (Ft. Saskatchewan, Canada) L.Lynch & Company Ltd
Dow (Freeport, TX) Merck Project B
Dow - Hydro Carbons Project Miles Lab
Dow - Oyster Creek Connection Pfizer Groton
Dow - Tiger Bay Pfizer Litesse
DuPont Beaumont MMA Project Roche Carolina
DuPont Sabine San Ramon Fuel Cell Pilot Plant
DuPont - Cooper River Shared Brine/Upjohn
DuPont (Corpus Christi, TX) Upjohn
DuPont (Gulf States)
DuPont (Taiwan) Power
Ethyl Corporation
Exxon Alvin W. Vogtle
Formosa Heavy Industries (Taiwan) Arkansas Nuclear One
Gulf Coast Fractionators Bellefonte - 1 & 2
Hitachi Boardman Fossil Fuel Plant
Hoechst Celanese Millhaven Resins Callaway 1
Huntsman Styrene Camden Cogen
ICI Americas Colstrip Fossil Fuel Plant
Koch Refinery Crystal River - 3
Mobay Corporation Diablo Canyon -1 & 2
Mobil Bakersfield DuPont
Monsanto Environmental Chemical Ebasco
Nan Ya Plastics (South Carolina) Exxon
Occidental Chemical/Bipheyl Florida Power & Light (Ft. Lauderdale, FL)
Petro-Chem Development Company Ghazlan
Sadaf Gordonsville
Samsung HB Robinson
Shell Chemical, BPA - 4 Indian Point - 3
Star Enterprises - Star Port Arthur Joseph M. Farley -1 & 2

www.pipeshields.com/major-projects 123
Pipe
Shields
Inc. Completed Projects
Labadie Fossil Fuel Plant Albuquerque Law Enforcement Center
Laguna Verde -1 & 2 Bessemer Civic Center
Lauderdale Re-Power Bulk Mail Facility (Pittsburgh)
Limerick - 1 & 2 Clay County Justice Center
LS Whitewater Cleveland Public Library
Miller Steam Plant Communications Emergency Operations Ctr.
Montana Power, Units 3 & 4 Denver, CO Museum of Natural History
Monticello Foothill Community Law & Justice Center
Nevada Power Hayward Hall of Justice
North Anna -1 & 2 Humboldt County Courthouse
Nuclear One 1 Loop Transportation Center (Chicago, IL)
Pawnee Fossil Fuel Plant Los Angeles Metro System
Peach Bottom - 2 & 3 Lucas State Office Bldg. Chiller Addition (IA)
Plant Scherer - Units 1 & 2 Montgomery Courthouse
Plant Scherer - Unit 4 Montgomery Fire Station
RanchoSeco Moscone Convention Center
San Onofre -1,2 & 3 Mountain Bell (Colorado Springs, CO)
Satsop Power Plant Ntl. Archives, Federal Records (San Bruno,CA)
Seabrook -1 & 2 Ohio Theater (Columbus, OH)
Shearon Harris -1 Opera House (San Francisco, CA)
Sioux Fossil Fuel Plant San Jose Convention Center
Sithe San Jose Museum of Art
St. Lucie Shasta CountyJustice Building
Surry Social Security Headquarters (Richmond, VA)
Susquehanna 1 & 2 Sunnyvale Public Safety Building
TECO (Florida) Tallahassee Capitol Complex
Transcanada North Bay US Embassy (Moscow)
Transcanada Kapuskasing US Federal Courthouse (San Jose, CA)
Turkey Point - 3 & 4
Vogtle 1 Pulp & Paper
Wabash Coal Gasification (Indiana)
Wabash River Gen. Station Celanese Fibers Operations
Watts Bar 1 & 2 Champion Paper Company
Wolf Creek Fraser Paper Company
WPPSS 1 & 4 Louisiana-Pacific
WPPSS 2 Olin Corporation, Ecusta Paper & Film Group
WPPSS 3 & 5 Wallula - Ponderosa Pulp & Paper (WA)
Weyerhaeuser
Process
Refineries
3M
EI DuPont Experimental Station Amoco Gas Plant (Evanston, WY)
Haliburton Headquarters Plant Exxon (Baytown,TX)
Kimberly Clark Kuwait National Petroleum Refinery
Meredith Burda Plant Ultramar Canada, Inc. - Vacuum Unit
Northwest Pipeline LNG II Plant
Proctor & Gamble Schools
Whitney Canyon Gas Plant
Public Works Aga Khan Hospital & Medical College
4th District Court (Chicago, IL) (Pakistan)
Alameda County Offices Basic Science Building, University of Alabama

124 www.pipeshields.com/major-projects
Pipe
Shields
Completed Projects Inc.
Bellarmine College, ODonnell Hall RJ Reynolds Building 95-1
Bowman Grey School of Medicine (NC) RJ Reynolds Downtown Building
Brigham Young University RJ Reynolds Flanor Building
Buffalo State University (Buffalo, NY) RJ Reynolds Leaf Storage Warehouse
Cherry Creek Elementary School (Denver, CO) RJ Reynolds M &K Warehouse
Cherry Creek High School (Denver,CO) RJ Reynolds Plaza Building
Copperfield Junior High School (TX) RJ Reynolds Skinners Warehouse
Douglas County High School (Denver, CO) RJ Reynolds Switch Gear Relocation
Harvard University (MA) RJ Reynolds Tobaccoville
James Madison Univ. Heat Recovery Project RJ Reynolds Whitaker Park
Lowry High School (Winnemucca, NV)
Lurleen Wallace Cancer Institute(Unv. of AL) Waste Treatment
Mendocino College
Michigan State University (East Lansing, MI) Cedar Creek Sewage Treatment Plant
New Bradford Central School (Bradford, NY) Lead-Deadwood Sewage Treatment
Northwestern University (Chicago, IL) Manitowoc Wastewater Treatment Plant
Santa Clara University Energy Center Pacific Gas & Electric Waste Line (Antioch, CA)
Stanford Psychiatric Building Rawhide River Project
Stanley School (Stanley, ND) Red Oaks Waste Water Treatment Plant (Red Oak,
State University (Oswego, NY) IA)
UC Davis Life Science Building (Davis, CA) Rock Creek Sewage Treatment Plant
UC Davis Cole B San Francisco Waste Treatment
UC Davis, Veterinary Hospital Solid Waste Recovery System (Newport News,VA)
UCSF, CA Sunnyvale Sewage Treatment Plant
UCSF, CA Koret Vision Waste Treatment Facility (Medway, MA)
UCLA Louis Factor Health Sciences Building
University of Akron
University of Alabama
University of Delaware (Newark, DE)
University of Michigan (Ann Arbor, MI)
UNC Chiller (Chapel Hill)
University of Tennessee College ofMedicine
Universityof Wyoming
Wayne State University, Outpatient Clinic
Western Michigan University
West Jefferson Junior High School (Denver, CO)
WMU Goldsworth (Kalamazoo, MI)

Solar

SEGS I & II (Daggett, CA)

Tobacco

Phillip Morris
RJ Reynolds Building 50-1
RJ Reynolds Building 601-11
RJ Reynolds Building 611-16
RJ Reynolds Building 611-7
RJ Reynolds Building 631-1
RJ Reynolds Building 90-3

www.pipeshields.com/major-projects 125
Pipe
Shields
Inc. FAQs

FREQUENTLY ASKED QUESTIONS


Why should I use insulated pipe supports?

The insulated pipe support can save you money on your bid and on the job. On commercial and light
industrial work, when an insulated pipe support is installed in a clevis hanger, the Insulation Contractor
never touches the pipe hanger and only needs to make a simple butt joint between the pipe insulation and
the insulated support. The Mechanical Contractor does not have to return for expensive, final adjustment.
On heavy industrial work, on alloy steel or stainless steel pipe, there is no welding, no pre-heat or
post-heat, no certified welders and no x-ray inspection required. On any type of work, if otherwise
permitted, there is an insulated pipe support available which will allow you to maximize the support spacing
and, thus, reduce the number of supports required on the job. The Insulation Contractor should reduce his
bid to allow for labor and materials not used.

What is the primary reason why I should consider insulated pipe supports in my building/plant?

Insulated pipe supports are energy conservation devices and continue to pay for themselves over the full
life of the building/plant. On request, Pipe Shields, Inc. will make an economic analysis for your
particular application.

Are there any other reasons why I should consider insulated pipe supports?

Insulated pipe supports also provide reduction in noise and vibration. Insulated pipe supports on hot lines
provide for personnel comfort and protection in tunnels, corridors, mechanical rooms and other tight places.
Insulated pipe supports on hot lines also often result in a reduced heat load for an air conditioning system
to handle. Insulated pipe supports permit the Insulating Contractor to make a perfect vapor barrier seal
which is also effective against the damaging effect of water intrusion - a condition impossible to achieve
with a welded shoe configuration.

How do I know which models to use?

The catalog is arranged to simplify the selection process. To obtain the most benefit from the catalog,
familiarize yourself with the Selection Guide, Product Data and Indexes to the various sections of the
catalog. In addition, many of the product data sheets have references to other models having features such
as higher load ratings or provisions for thermal expansion or physical restraint.

Why are there so many models of insulated pipe supports?

The load rating of each support is often dependent upon how the support is mounted (flat surface, roller,
clevis hanger). Heavy valve loads, wind loads, and/or thermal loads may have to be accommodated.
Provision for axial and/or lateral travel, due to thermal growth, may have to be made. The pipe may require
guiding or restraint. Supports mounted on 10'-0 centers do not require the load carrying capability that is
required by supports on 40'-0 centers. These and other considerations resulted in the creation of a family
of insulated pipe supports enabling the customer to select the most economic unit sufficient for the purpose
intended.

126 www.pipeshields.com/faqs
Pipe
Shields
FAQs Inc.

Why does the same model commercial support (example A3000) have three different load ratings?

When this cylindrical shaped support is mounted on a flat surface, its load carrying capability is limited
because there is only line contact at the underside of the support. Similarly, there is an even greater
limitation on the load carrying capability of this model when mounted on pipe rolls because of the point
contact resulting in deformation of the sheet metal jacket and/or damage to the calcium silicate insulation
under heavy loads. In a ring or clevis hanger, however, the load is well distributed through the lower 180
section, permitting higher load ratings.

Why can't I specify pipe supports the "old way"?

Weld-on supports represent heat sink conditions with resulting energy loss. Expensive like materials,
welding and inspection procedures are often required on high temperature alloy steel pipe to minimize
the likelihood of stress corrosion and to assure a sound weld. Available standard catalog hangers may
not permit the maximization of support spacing and the resulting minimization of the number of supports
required on the job - possible with the use of pre-insulated pipe supports. Today's light density fiberglass
insulation has insufficient compressive strength to support most pipe loads without crushing out - often
requiring the contractor to be innovative at each support point. Load rated insulated pipe supports offer an
appropriate and economic solution.

My design requirements are special and I do not find exactly what I want in your catalog. Why don't
I design a pipe support for myself?

Pipe Shields, Inc. has developed a "standard concept" for its family of insulated pipe supports. Utilizing that
concept, we have been able to readily modify it and adapt it to meet a wide variety of applications. Many of
these modifications and adaptations have not been included in this catalog. In addition, the materials and
design configurations have been extensively tested and/or analyzed, allowing Pipe Shields, Inc. to readily
and economically respond to any pipe support need. As experts in the insulated pipe support field, we can
save you expensive design time - especially on "fast-track" projects.

How long does it take to install an insulated pipe support?

This depends upon the size and model considered. The popular commercial and light industrial supports
up through 8 pipe size can generally be installed by one man in half-a-minute or less. The two halves, with
their overlapping jackets, merely slip together over the pipe at the point of support. If for any reason, the
support must be relocated, it is just as easy to remove and move, as it was to install in the first place. The
larger the diameter, heavy industrial supports may require the time of two men for 15 minutes plus a welder
to attach the base plate to the support structure. As with the small bore commercial supports, these too are
easy to relocate.

Why dont I add Pipe Shields, Inc.'s name to a list of methods and/or vendors currently in our
specifications?

To control the quality of pipe supports on the project, it is necessary to avoid the ambiguity present in
many of today's existing specifications. The Insulating Contractor must be made aware that the purchase
and installation of insulated pipe supports are responsibilities of the Mechanical Contractor, so that his bid
may be adjusted accordingly. To assist you, we have prepared typical, general mechanical specifications
for insulated pipe supports which may be found elsewhere in this catalog. If you have a current set of
specifications, send it to us for our review and recommendations.

www.pipeshields.com/faqs 127
Pipe
Shields
Inc. FAQs
Can heat trace lines be accommodated?

Pipe Shields, Inc. has supplied many insulated pipe supports, each with one or more grooves to handle
heat traces. Advise us of the number, size, configuration and orientation of your heat tracing and we can
readily and economically incorporate the necessary groove(s) in the supports you require.

How can I make certain that insulated pipe supports will be used in my facility?

Whether you have an in-house engineering capability or sub-contract the engineering effort to an outside
firm, you should make clear that one or more of the typical General Mechanical Specifications, included
elsewhere in this catalog, are followed. Over the years, specifications have become so ambiguous that
they often result in a complete license to have anything but what the owner/operator wishes installed on the
project. In addition, a properly written specification places the responsibility for the purchase and installation
of insulated pipe supports with the Mechanical Contractor, resulting in a lower bid - (and lower total project
cost) from the Insulating Contractor. Pipe Shields, Inc. has an open offer to work with you and/or your
Engineer, to review your current specifications and provide recommendations to assure that the most
economic and appropriate supports are used on your project.

Is there any reason to consider insulated pipe supports on chilled water lines?

Old-style sheet metal insulation "protection" shields, when used with today's low density fiberglass
insulation, often damages the very insulation and vapor barrier they are supposed to protect when the
shield moves in relation to a clevis hanger, becomes unbalanced, and cuts through both the vapor barrier
and the insulation. An insulated pipe support provides the best protection against condensation/sweating
problems and enhances the life of the insulation system.

High temperature insulated pipe support. The base, clamps, nuts, jackets and bolts are all
fabricated from hot-dipped galvanized carbon steel. The cold shoes have 3 thick high density
calcium silicate insulation, and are designed for 12 - 42 diameter pipes. The dimensions are
47 L X 51 W X 16 H.

128 www.pipeshields.com/faqs
Pipe
Shields
Inc.

1. 2.

4.

3.
1. 25-7/8 Diameter high temperature supports for a rush
job.

2. 48 Guided pre-insulated pipe supports for high


temperatures.

3. Hot shoes for a power plant in Argentina.

4. These cryogenic supports are fabricated from 20 PCF


polyurethane insulation, weigh 650 lb. each and are de-
signed for 30 diameter pipe.

5. 58 Diameter high temperature rotational and axial


stop insulated supports.
5.
Pipe
Shields
Inc. Pipe Shields, Inc. Product Catalog
a subsidiary of Piping Technology & Products, Inc.

Engineered Pipe Supports Pre-Insulated Pipe Supports


(Variables, Constants & Big Ton (Hot Shoes for High Temp.
Springs) Pipe Lines, Cold Shoes for
Cryogenic Lines)
Expansion Joints (Metallic Bellows,
Thick Wall, Thin Wall, Furnace Bags. Support Assembly
Rectangular, Slip-Type, Fabric) Components (Pipe Hangers,
Clamps & Risers, Saddle
Pipe Shoes, Guides & Anchors Supports & Coverings,
(Pipe Shoes & Stands, Cylinder Hardware, Rods & U-Bolts,
Pipe Guides, Anchors) Hold-Down Clamps, Beam
Attachments, Clevis Hangers)
Plant Location: site: www.pipeshields.com Slide Plates (PTFE, 25% Glass
Filled, Bronzphite, Marinite, Dynamic Restraints
3701 Holmes Road www.pipingtech.com Graphite) (Hydraulic Shock & Sway
Houston, TX 77051-1545 email: info@pipeshields.com Supressors, Vibration Control
info@pipingtech.com ASME/Misc. Fabricated Products Sway Braces, Mechanical
Mailing Address: (ASME Pressure Vessels Tanks, Pig Snubbers, Sway Struts)
P.O. Box 34506 Phone: (800) 538-7007 Launchers & Receivers, Duct &
Houston, TX 77234-4506 (713) 731-0030 Transition Pieces, Spectacle & Line Value-Added Services (24x7
Fax: (707) 447-4641 Blinds, Bellmouth Reducers, Quick-Turn / Emergency,
Sales Office:
O (713) 731-8640 Instrument Supports, Dampers / Stress Analysis / Product
5030 Business Center Dr. St. 210 Louvers, Conical Strainers) Testing, Engineering & Design,
Fairfield, CA 94534 Field Services)

2nd Edition

Piping Technology & Products, Inc.

Copyright 2014 Pipe Shields Inc. Printed in USA 25M December 2014 2nd Edition