Sunteți pe pagina 1din 19

SOC - Selected Optimized

Coordination
Coordination tables for
motor protection
Important notice
This book is the result of a web search made from Selected Optimized Coordination - Coordination tables for motor protection
(https://applications.it.abb.com/SOC) made on 16 dic 2016.
Please always refer to https://applications.it.abb.com/SOC for the lastest updated information.

Used filters:
Protection Device:Fuses
Protection Device:440Vac
Short-Circuit Current:65
Starter Type:DOL-NS
Coordination Type:IEC Type 2
Motor Rated Power:22

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page i
Index
Fuses...................................................................................................................................................................................................................1
440Vac.............................................................................................................................................................................................................1
100 kA..........................................................................................................................................................................................................1
DOL-NS...................................................................................................................................................................................................1
IEC Type 2...........................................................................................................................................................................................1
EOL..................................................................................................................................................................................................1
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - aM + EOL.....................................................................................................1
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + EOL.....................................................................................................3
TOL..................................................................................................................................................................................................5
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + TOL.....................................................................................................5
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + TOL.....................................................................................................7
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - aM + TOL.....................................................................................................9
UMC.................................................................................................................................................................................................11
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - aM + UMC...................................................................................................11
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + UMC....................................................................................................14

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page ii
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - aM + EOL
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :EOL
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :no Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :15/07/2014

Motor Fuses IEC Contactor Overload Relay


Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
0,18 0,53 OS32GD03P 2 OFAF000AM2 AF09 EF19-1.0 * 0,30 - 1,00 1,00

0,25 0,74 OS32GD03P 2 OFAF000AM2 AF09 EF19-1.0 * 0,30 - 1,00 1,00

0,37 1,00 OS32GD03P 2 OFAF000AM2 AF09 EF19-2.7 * 0,80 - 2,70 1,40

0,55 1,30 OS32GD03P 4 OFAF000AM4 AF09 EF19-2.7 * 0,80 - 2,70 2,70

0,75 1,70 OS32GD03P 4 OFAF000AM4 AF09 EF19-2.7 * 0,80 - 2,70 2,70

1,10 2,40 OS32GD03P 4 OFAF000AM4 AF09 EF19-2.7 * 0,80 - 2,70 2,70

1,50 3,20 OS32GD03P 6 OFAF000AM6 AF09 EF19-6.3 * 1,90 - 6,30 4,30

2,20 4,30 OS32GD03P 10 OFAF000AM10 AF09 EF19-6.3 * 1,90 - 6,30 5,70

3,00 5,70 OS32GD03P 10 OFAF000AM10 AF09 EF19-18.9 * 5,70 - 18,90 7,20

4,00 7,40 OS32GD03P 16 OFAF000AM16 AF09 EF19-18.9 * 5,70 - 18,90 9,50

5,50 10,10 OS32GD03P 16 OFAF000AM16 AF12 EF19-18.9 * 5,70 - 18,90 11,50

7,50 13,60 OS32GD03P 25 OFAF000AM25 AF16 EF19-18.9 * 5,70 - 18,90 16,00

11,00 19,30 OS32GD03P 32 OFAF000AM32 AF26 EF45-30 * 9,00 - 30,00 23,00

15,00 25,40 OS32GD03P 40 OFAF000AM40 AF30 EF45-30 * 9,00 - 30,00 28,00

18,50 30,70 OS32GD03P 50 OFAF000AM50 AF38 EF45-45 * 15,00 - 45,00 32,00

22,00 35,90 OS125GD03P 80 OFAF000AM80 AF52 EF65-70 * 25,00 - 70,00 45,00

30,00 48,20 OS125GD03P 80 OFAF000AM80 AF65 EF65-70 * 25,00 - 70,00 55,00

37,00 58,00 OS125GD03P 100 OFAF00AM100 AF80 EF96-100 * 36,00 - 100,00 65,00

45,00 70,00 OS125GD03P 125 OFAF00AM125 AF96 EF96-100 * 36,00 - 100,00 80,00

55,00 85,00 OS125GD03P 160 OFAF00AM160 AF116 EF146-150 * 54,00 - 150,00 110,00

75,00 116,00 OS250D03P 200 OFAF1AM200 AF190 EF205-210 * 63,00 - 210,00 135,00

90,00 140,00 OS250D03P 200 OFAF1AM200 AF205 EF205-210 * 63,00 - 210,00 160,00

110,00 171,00 OS250D03P 250 OFAF1AM250 AF265 EF370-380 * 115,00 - 380,00 205,00

132,00 202,00 OS400D03P 315 OFAF2AM315 AF265 EF370-380 * 115,00 - 380,00 250,00

160,00 245,00 OS400D03P 355 OFAF2AM355 AF305 EF370-380 * 115,00 - 380,00 290,00

200,00 307,00 OS630D03P 500 OFAF3AM500 AF400 EF460-500 * 150,00 - 500,00 370,00

250,00 377,00 OS630D03P 630 OFAF3AM630 AF460 EF460-500 * 150,00 - 500,00 460,00

315,00 473,00 OS800D03P 800 OFAM3AM800 AF580 EF750-800 * 250,00 - 800,00 580,00

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 1 of 16
Motor Fuses IEC Contactor Overload Relay
Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
355,00 535,00 OS800D03P 800 OFAM3AM800 AF580 EF750-800 * 250,00 - 800,00 580,00

400,00 605,00 OS800D03P 800 OFAM3AM800 AF750 EF750-800 * 250,00 - 800,00 610,00

500,00 745,00 OS1250DA03P 1000 OFAF4AAM1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 760,00

560,00 832,00 OS1250DA03P 1250 OFAF4AAM1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 950,00

630,00 929,00 OS1250DA03P 1250 OFAF4AAM1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 950,00
Comments:
*: selected trip class of Electronic overload relay.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 2 of 16
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + EOL
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :EOL
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :no Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :15/07/2014

Motor Fuses IEC Contactor Overload Relay


Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
0,12 0,39 OS32GD03P 2 OFAF000H2 AF09 EF19-1.0 * 0,30 - 1,00 0,54

0,18 0,53 OS32GD03P 4 OFAF000H4 AF09 EF19-1.0 * 0,30 - 1,00 1,00

0,25 0,74 OS32GD03P 4 OFAF000H4 AF09 EF19-1.0 * 0,30 - 1,00 1,00

0,37 1,00 OS32GD03P 6 OFAF000H6 AF09 EF19-2.7 * 0,80 - 2,70 2,00

0,55 1,30 OS32GD03P 6 OFAF000H6 AF09 EF19-2.7 * 0,80 - 2,70 2,00

0,75 1,70 OS32GD03P 6 OFAF000H6 AF09 EF19-2.7 * 0,80 - 2,70 2,00

1,10 2,40 OS32GD03P 10 OFAF000H10 AF09 EF19-2.7 * 0,80 - 2,70 2,70

1,50 3,20 OS32GD03P 10 OFAF000H10 AF09 EF19-6.3 * 1,90 - 6,30 3,40

2,20 4,30 OS32GD03P 16 OFAF000H16 AF09 EF19-6.3 * 1,90 - 6,30 5,00

3,00 5,70 OS32GD03P 20 OFAF000H20 AF09 EF19-6.3 * 1,90 - 6,30 6,30

4,00 7,40 OS32GD03P 25 OFAF000H25 AF09 EF19-18.9 * 5,70 - 18,90 7,80

5,50 10,10 OS32GD03P 40 OFAF000H40 AF26 EF19-18.9 * 5,70 - 18,90 13,00

7,50 13,60 OS32GD03P 50 OFAF000H50 AF26 EF19-18.9 * 5,70 - 18,90 17,00

11,00 19,30 OS32GD03P 63 OFAF000H63 AF26 EF45-30 * 9,00 - 30,00 23,00

15,00 25,40 OS125GD03P 80 OFAF000H80 AF30 EF45-30 * 9,00 - 30,00 28,00

18,50 30,70 OS125GD03P 80 OFAF000H80 AF38 EF45-45 * 15,00 - 45,00 32,00

22,00 35,90 OS125GD03P 125 OFAF00H125 AF52 EF65-70 * 25,00 - 70,00 45,00

30,00 48,20 OS125GD03P 125 OFAF00H125 AF65 EF65-70 * 25,00 - 70,00 55,00

37,00 58,00 OS125GD03P 160 OFAF00H160 AF80 EF96-100 * 36,00 - 100,00 65,00

45,00 70,00 OS125GD03P 160 OFAF00H160 AF96 EF96-100 * 36,00 - 100,00 72,00

55,00 85,00 OS250D03P 200 OFAF1H200 AF116 EF146-150 * 54,00 - 150,00 93,00

75,00 116,00 OS250D03P 250 OFAF1H250 AF140 EF146-150 * 54,00 - 150,00 130,00

90,00 140,00 OS400D03P 315 OFAF2H315 AF205 EF205-210 * 63,00 - 210,00 165,00

110,00 171,00 OS400D03P 315 OFAF2H315 AF265 EF370-380 * 115,00 - 380,00 205,00

132,00 202,00 OS400D03P 400 OFAF2H400 AF265 EF370-380 * 115,00 - 380,00 240,00

160,00 245,00 OS630D03P 500 OFAF3H500 AF305 EF370-380 * 115,00 - 380,00 290,00

200,00 307,00 OS630D03P 630 OFAF3H630 AF400 EF460-500 * 150,00 - 500,00 370,00

250,00 377,00 OS630D03P 630 OFAF3H630 AF400 EF460-500 * 150,00 - 500,00 400,00

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 3 of 16
Motor Fuses IEC Contactor Overload Relay
Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
315,00 473,00 OS800D03P 800 OFAF3H800 AF580 EF750-800 * 250,00 - 800,00 580,00

355,00 535,00 OS800D03P 800 OFAF3H800 AF580 EF750-800 * 250,00 - 800,00 580,00

400,00 605,00 OS800D03P 800 OFAF3H800 AF750 EF750-800 * 250,00 - 800,00 610,00

500,00 745,00 OS1250DA03P 1000 OFAF4AH1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 780,00

560,00 832,00 OS1250DA03P 1250 OFAF4AH1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 950,00

630,00 929,00 OS1250DA03P 1250 OFAF4AH1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 950,00
Comments:
*: selected trip class of Electronic overload relay.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 4 of 16
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + TOL
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :TOL
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :no Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :13/05/2014

Motor Fuses IEC Contactor Overload Relay


Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
0,12 0,39 OS32GD03P 2 OFAF000H2 AF09 TF42-0.41 0,31 - 0,41 0,41

0,18 0,53 OS32GD03P 2 OFAF000H2 AF09 TF42-0.55 0,42 - 0,55 0,55

0,25 0,74 OS32GD03P 4 OFAF000H4 AF09 TF42-1.0 0,74 - 1,00 1,00

0,37 1,00 OS32GD03P 6 OFAF000H6 AF09 TF42-1.3 1,00 - 1,30 1,30

0,55 1,30 OS32GD03P 6 OFAF000H6 AF09 TF42-1.7 1,30 - 1,70 1,70

0,75 1,70 OS32GD03P 6 OFAF000H6 AF09 TF42-2.3 1,70 - 2,30 2,00

0,75 1,70 OS32GD03P 10 OFAF000H10 AF09 TF42-2.3 1,70 - 2,30 2,30

1,10 2,40 OS32GD03P 10 OFAF000H10 AF09 TF42-3.1 2,30 - 3,10 3,10

1,50 3,20 OS32GD03P 16 OFAF000H16 AF09 TF42-4.2 3,10 - 4,20 4,20

2,20 4,30 OS32GD03P 20 OFAF000H20 AF09 TF42-5.7 4,20 - 5,70 5,20

3,00 5,70 OS32GD03P 25 OFAF000H25 AF09 TF42-7.6 5,70 - 7,60 6,80

4,00 7,40 OS32GD03P 25 OFAF000H25 AF09 TF42-7.6 5,70 - 7,60 7,60

4,00 7,40 OS32GD03P 32 OFAF000H32 AF09 TF42-10 7,60 - 10,00 9,00

5,50 10,10 OS32GD03P 32 OFAF000H32 AF16 TF42-13 10,00 - 13,00 11,50

5,50 10,10 OS63GD03P 40 OFAF000H40 AF26 TF42-13 10,00 - 13,00 13,00

7,50 13,60 OS63GD03P 40 OFAF000H40 AF26 TF42-16 13,00 - 16,00 15,50

9,00 16,30 OS63GD03P 50 OFAF000H50 AF26 TF42-20 16,00 - 20,00 19,00

11,00 19,30 OS63GD03P 50 OFAF000H50 AF26 TF42-20 16,00 - 20,00 19,00

11,00 19,30 OS63GD03P 63 OFAF000H63 AF26 TF42-24 20,00 - 24,00 23,00

15,00 25,40 OS100GD03P 63 OFAF000H63 AF30 TF42-29 24,00 - 29,00 26,00

18,50 30,70 OS100GD03P 80 OFAF000H80 AF30 TF42-35 29,00 - 35,00 32,00

22,00 35,90 OS100GD03P 80 OFAF000H80 AF38 TF42-38 35,00 - 38,00 38,00

22,00 35,90 OS100GD03P 100 OFAF000H100 AF40 TF65-40 30,00 - 40,00 40,00

25,00 40,80 OS100GD03P 100 OFAF000H100 AF52 TF65-47 36,00 - 47,00 44,00

30,00 48,20 OS125GD03P 125 OFAF00H125 AF65 TF65-53 44,00 - 53,00 55,00

37,00 58,00 OS160GD03P 160 OFAF00H160 AF80 TF96-68 57,00 - 68,00 65,00

45,00 70,00 OS160GD03P 160 OFAF00H160 AF96 TF96-78 65,00 - 78,00 78,00

55,00 85,00 OS250D03P 200 OFAF1H200 AF96 TF96-87 75,00 - 87,00 87,00

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 5 of 16
Motor Fuses IEC Contactor Overload Relay
Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
75,00 116,00 OS250D03P 224 OFAF1H224 AF140 TF140DU-135 100,00 - 135,00 120,00

90,00 140,00 OS250D03P 250 OFAF1H250 AF190 TA200DU-150 110,00 - 150,00 135,00

110,00 171,00 OS400D03P 315 OFAF2H315 AF205 TA200DU-175 130,00 - 175,00 175,00

132,00 202,00 OS400D03P 315 OFAF2H315 AF265 TA450DU-235 165,00 - 235,00 235,00

160,00 245,00 OS400D03P 400 OFAF2H400 AF265 TA450DU-310 220,00 - 310,00 265,00

200,00 307,00 OS400D03P 400 OFAF2H400 AF370 TA450DU-310 220,00 - 310,00 310,00

200,00 307,00 OS630D03P 630 OFAF3H630 AF370 E500DU-500 * 150,00 - 500,00 370,00

250,00 377,00 OS630D03P 630 OFAF3H630 AF400 E500DU-500 * 150,00 - 500,00 400,00

315,00 473,00 OS800D03P 800 OFAF3H800 AF580 E800DU-800 * 250,00 - 800,00 580,00

355,00 535,00 OS800D03P 800 OFAF3H800 AF580 E800DU-800 * 250,00 - 800,00 580,00

400,00 605,00 OS800D03P 800 OFAF3H800 AF750 E800DU-800 * 250,00 - 800,00 610,00

400,00 605,00 OS1250DA03P 1000 OFAF4AH1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 800,00

500,00 745,00 OS1250DA03P 1000 OFAF4AH1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 800,00

560,00 832,00 OS1250DA03P 1250 OFAF4AH1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 1000,00

630,00 929,00 OS1250DA03P 1250 OFAF4AH1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 1000,00
Comments:
* : selected trip class of E_DU

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 6 of 16
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + TOL
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :TOL
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :no Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :13/05/2014

Motor Fuses IEC Contactor Overload Relay


Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
0,12 0,39 OS32GD03P 2 OFAF000H2 AF09 TF42-0.41 0,31 - 0,41 0,41

0,18 0,53 OS32GD03P 2 OFAF000H2 AF09 TF42-0.55 0,42 - 0,55 0,55

0,25 0,74 OS32GD03P 4 OFAF000H4 AF09 TF42-1.0 0,74 - 1,00 1,00

0,37 1,00 OS32GD03P 6 OFAF000H6 AF09 TF42-1.3 1,00 - 1,30 1,30

0,55 1,30 OS32GD03P 6 OFAF000H6 AF09 TF42-1.7 1,30 - 1,70 1,70

0,75 1,70 OS32GD03P 6 OFAF000H6 AF09 TF42-2.3 1,70 - 2,30 2,00

0,75 1,70 OS32GD03P 10 OFAF000H10 AF09 TF42-2.3 1,70 - 2,30 2,30

1,10 2,40 OS32GD03P 10 OFAF000H10 AF09 TF42-3.1 2,30 - 3,10 3,10

1,50 3,20 OS32GD03P 16 OFAF000H16 AF09 TF42-4.2 3,10 - 4,20 4,20

2,20 4,30 OS32GD03P 20 OFAF000H20 AF09 TF42-5.7 4,20 - 5,70 5,20

3,00 5,70 OS32GD03P 25 OFAF000H25 AF09 TF42-7.6 5,70 - 7,60 6,80

4,00 7,40 OS32GD03P 25 OFAF000H25 AF09 TF42-7.6 5,70 - 7,60 7,60

4,00 7,40 OS32GD03P 32 OFAF000H32 AF09 TF42-10 7,60 - 10,00 9,00

5,50 10,10 OS32GD03P 32 OFAF000H32 AF16 TF42-13 10,00 - 13,00 11,50

5,50 10,10 OS63GD03P 40 OFAF000H40 AF26 TF42-13 10,00 - 13,00 13,00

7,50 13,60 OS63GD03P 40 OFAF000H40 AF26 TF42-16 13,00 - 16,00 15,50

9,00 16,30 OS63GD03P 50 OFAF000H50 AF26 TF42-20 16,00 - 20,00 19,00

11,00 19,30 OS63GD03P 50 OFAF000H50 AF26 TF42-20 16,00 - 20,00 19,00

11,00 19,30 OS63GD03P 63 OFAF000H63 AF26 TF42-24 20,00 - 24,00 23,00

15,00 25,40 OS100GD03P 63 OFAF000H63 AF30 TF42-29 24,00 - 29,00 26,00

18,50 30,70 OS100GD03P 80 OFAF000H80 AF30 TF42-35 29,00 - 35,00 32,00

22,00 35,90 OS100GD03P 80 OFAF000H80 AF38 TF42-38 35,00 - 38,00 38,00

22,00 35,90 OS100GD03P 100 OFAF000H100 AF40 TF65-40 30,00 - 40,00 40,00

25,00 40,80 OS100GD03P 100 OFAF000H100 AF52 TF65-47 36,00 - 47,00 44,00

30,00 48,20 OS125GD03P 125 OFAF00H125 AF65 TF65-53 44,00 - 53,00 55,00

37,00 58,00 OS160GD03P 160 OFAF00H160 AF80 TF96-68 57,00 - 68,00 65,00

45,00 70,00 OS160GD03P 160 OFAF00H160 AF96 TF96-78 65,00 - 78,00 78,00

55,00 85,00 OS250D03P 200 OFAF1H200 AF96 TF96-87 75,00 - 87,00 87,00

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 7 of 16
Motor Fuses IEC Contactor Overload Relay
Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
75,00 116,00 OS250D03P 224 OFAF1H224 AF140 TF140DU-135 100,00 - 135,00 120,00

90,00 140,00 OS250D03P 250 OFAF1H250 AF190 TA200DU-150 110,00 - 150,00 135,00

110,00 171,00 OS400D03P 315 OFAF2H315 AF205 TA200DU-175 130,00 - 175,00 175,00

132,00 202,00 OS400D03P 315 OFAF2H315 AF265 TA450DU-235 165,00 - 235,00 235,00

160,00 245,00 OS400D03P 400 OFAF2H400 AF265 TA450DU-310 220,00 - 310,00 265,00

200,00 307,00 OS400D03P 400 OFAF2H400 AF370 TA450DU-310 220,00 - 310,00 310,00

200,00 307,00 OS630D03P 630 OFAF3H630 AF370 E500DU-500 * 150,00 - 500,00 370,00

250,00 377,00 OS630D03P 630 OFAF3H630 AF400 E500DU-500 * 150,00 - 500,00 400,00

315,00 473,00 OS800D03P 800 OFAF3H800 AF580 E800DU-800 * 250,00 - 800,00 580,00

355,00 535,00 OS800D03P 800 OFAF3H800 AF580 E800DU-800 * 250,00 - 800,00 580,00

400,00 605,00 OS800D03P 800 OFAF3H800 AF750 E800DU-800 * 250,00 - 800,00 610,00

400,00 605,00 OS1250DA03P 1000 OFAF4AH1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 800,00

500,00 745,00 OS1250DA03P 1000 OFAF4AH1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 800,00

560,00 832,00 OS1250DA03P 1250 OFAF4AH1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 1000,00

630,00 929,00 OS1250DA03P 1250 OFAF4AH1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 1000,00
Comments:
* : selected trip class of E_DU

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 8 of 16
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - aM + TOL
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :TOL
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :no Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :14/05/2014

Motor Fuses IEC Contactor Overload Relay


Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
0,18 0,53 OS32GD03P 2 OFAF000AM2 AF09 TF42-0.74 0,55 - 0,74 0,74

0,25 0,74 OS32GD03P 2 OFAF000AM2 AF09 TF42-1.0 0,74 - 1,00 1,00

0,37 1,00 OS32GD03P 2 OFAF000AM2 AF09 TF42-1.3 1,00 - 1,30 1,30

0,55 1,30 OS32GD03P 4 OFAF000AM4 AF09 TF42-1.7 1,30 - 1,70 1,70

0,75 1,70 OS32GD03P 4 OFAF000AM4 AF09 TF42-2.3 1,70 - 2,30 2,30

1,10 2,40 OS32GD03P 4 OFAF000AM4 AF09 TF42-3.1 2,30 - 3,10 3,00

1,50 3,20 OS32GD03P 6 OFAF000AM6 AF09 TF42-4.2 3,10 - 4,20 4,20

2,20 4,30 OS32GD03P 10 OFAF000AM10 AF09 TF42-5.7 4,20 - 5,70 5,70

3,00 5,70 OS32GD03P 10 OFAF000AM10 AF09 TF42-7.6 5,70 - 7,60 7,60

4,00 7,40 OS32GD03P 10 OFAF000AM10 AF09 TF42-7.6 5,70 - 7,60 7,60

4,00 7,40 OS32GD03P 10 OFAF000AM10 AF09 TF42-10 7,60 - 10,00 9,00

5,50 10,10 OS32GD03P 20 OFAF000AM20 AF16 TF42-13 10,00 - 13,00 13,00

7,50 13,60 OS32GD03P 25 OFAF000AM25 AF26 TF42-16 13,00 - 16,00 16,00

9,00 16,30 OS32GD03P 25 OFAF000AM25 AF26 TF42-20 16,00 - 20,00 20,00

11,00 19,30 OS32GD03P 25 OFAF000AM25 AF26 TF42-20 16,00 - 20,00 20,00

11,00 19,30 OS32GD03P 25 OFAF000AM25 AF26 TF42-24 20,00 - 24,00 23,00

15,00 25,40 OS32GD03P 40 OFAF000AM40 AF30 TF42-29 24,00 - 29,00 28,00

18,50 30,70 OS32GD03P 40 OFAF000AM40 AF30 TF42-35 29,00 - 35,00 28,00

22,00 35,90 OS63GD03P 50 OFAF000AM50 AF38 TF42-38 35,00 - 38,00 33,00

25,00 40,80 OS63GD03P 63 OFAF000AM63 AF52 TF65-47 36,00 - 47,00 44,00

30,00 48,20 OS125GD03P 80 OFAF000AM80 AF65 TF65-53 44,00 - 53,00 53,00

37,00 58,00 OS125GD03P 80 OFAF000AM80 AF65 TF65-60 50,00 - 60,00 60,00

45,00 70,00 OS125GD03P 125 OFAF00AM125 AF96 TF96-78 65,00 - 78,00 78,00

55,00 85,00 OS125GD03P 125 OFAF00AM125 AF96 TF96-87 75,00 - 87,00 87,00

55,00 85,00 OS125GD03P 125 OFAF00AM125 AF116 TF140DU-90 66,00 - 90,00 90,00

75,00 116,00 OS125GD03P 160 OFAF00AM160 AF140 TF140DU-135 100,00 - 135,00 120,00

90,00 140,00 OS250D03P 200 OFAF1AM200 AF190 TA200DU-150 110,00 - 150,00 150,00

110,00 171,00 OS250D03P 250 OFAF1AM250 AF265 TA450DU-235 165,00 - 235,00 200,00

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 9 of 16
Motor Fuses IEC Contactor Overload Relay
Rated Rated Switch-Fuse Rating Type and Size Type Type Trip Current range Max
Power Current Type gG /aM Class [A] allowed
[A] [A] load
current
[A]
132,00 202,00 OS250D03P 250 OFAF1AM250 AF265 TA450DU-235 165,00 - 235,00 235,00

160,00 245,00 OS400D03P 315 OFAF2AM315 AF265 TA450DU-310 220,00 - 310,00 250,00

200,00 307,00 OS400D03P 355 OFAF2AM355 AF370 TA450DU-310 220,00 - 310,00 310,00

200,00 307,00 OS630D03P 500 OFAF3AM500 AF400 E500DU-500 * 150,00 - 500,00 400,00

250,00 377,00 OS630D03P 500 OFAF3AM500 AF400 E500DU-500 * 150,00 - 500,00 400,00

250,00 377,00 OS630D03P 630 OFAF3AM630 AF460 E500DU-500 * 150,00 - 500,00 460,00

315,00 473,00 OS800D03P 800 OFAM3AM800 AF580 E800DU-800 * 250,00 - 800,00 580,00

355,00 535,00 OS800D03P 800 OFAM3AM800 AF580 E800DU-800 * 250,00 - 800,00 580,00

400,00 605,00 OS800D03P 800 OFAM3AM800 AF750 E800DU-800 * 250,00 - 800,00 630,00

500,00 745,00 OS1250DA03P 1000 OFAF4AAM1000 AF1350 E1250DU-1250 * 375,00 - 1250,00 800,00

560,00 832,00 OS1250DA03P 1250 OFAF4AAM1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 1000,00

630,00 929,00 OS1250DA03P 1250 OFAF4AAM1250 AF1650 E1250DU-1250 * 375,00 - 1250,00 1000,00
Comments:
* : selected trip class of E_DU

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 10 of 16
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - aM + UMC
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :UMC
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :yes Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :15/07/2014

Motor Fuses IEC Conta Current Overload Relay


ctor transformer
R Rat Switch-F R Type and Type Type T Type T Current Ma
at ed use ati Size u ri range [A] x
e Cur Type ng r p allo
d ren g n C we
P t G s l d
o [A] /a a loa
w M s d
er [A s cur
] ren
t
[A]
0,1 0,53 OS32GD03 2 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 1,00
8 P 2

0,2 0,74 OS32GD03 2 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 1,00
5 P 2

0,3 1,00 OS32GD03 2 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 1,40
7 P 2

0,5 1,30 OS32GD03 4 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 2,70
5 P 4

0,7 1,70 OS32GD03 4 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 2,70
5 P 4

1,1 2,40 OS32GD03 4 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 2,70
0 P 4

1,5 3,20 OS32GD03 6 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 4,30
0 P 6

2,2 4,30 OS32GD03 10 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 6,30
0 P 10

3,0 5,70 OS32GD03 10 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 7,20
0 P 10

4,0 7,40 OS32GD03 16 OFAF000AM AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 9,50
0 P 16

5,5 10,1 OS32GD03 16 OFAF000AM AF12 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 11,5
0 0 P 16 0

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 11 of 16
Motor Fuses IEC Conta Current Overload Relay
ctor transformer
R Rat Switch-F R Type and Type Type T Type T Current Ma
at ed use ati Size u ri range [A] x
e Cur Type ng r p allo
d ren g n C we
P t G s l d
o [A] /a a loa
w M s d
er [A s cur
] ren
t
[A]
7,5 13,6 OS32GD03 25 OFAF000AM AF16 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 16,0
0 0 P 25 0

11, 19,3 OS32GD03 32 OFAF000AM AF26 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 18,9
00 0 P 32 0

15, 25,4 OS32GD03 40 OFAF000AM AF30 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 28,0
00 0 P 40 0

18, 30,7 OS63GD03 50 OFAF000AM AF38 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 33,0
50 0 P 50 0

22, 35,9 OS125GD0 80 OFAF000AM AF52 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 45,0
00 0 3P 80 0

30, 48,2 OS125GD0 80 OFAF000AM AF65 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 55,0
00 0 3P 80 0

37, 58,0 OS125GD0 10 OFAF00AM1 AF80 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 65,0
00 0 3P 0 00 185R/4 185,00 0

45, 70,0 OS125GD0 12 OFAF00AM1 AF96 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 80,0
00 0 3P 5 25 185R/4 185,00 0

55, 85,0 OS125GD0 16 OFAF00AM1 AF116 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 110,
00 0 3P 0 60 185R/4 185,00 00

75, 116, OS250D03 20 OFAF1AM20 AF190 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 135,
00 00 P 0 0 185R/4 185,00 00

90, 140, OS250D03 20 OFAF1AM20 AF205 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 160,
00 00 P 0 0 185R/4 185,00 00

11 171, OS250D03 25 OFAF1AM25 AF265 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 185,


0,0 00 P 0 0 185R/4 185,00 00
0

13 202, OS400D03 31 OFAF2AM31 AF265 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 180,00 - 240,


2,0 00 P 5 5 310R/4 310,00 00
0

16 245, OS400D03 35 OFAF2AM35 AF305 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 180,00 - 290,


0,0 00 P 5 5 310R/4 310,00 00
0

20 307, OS630D03 50 OFAF3AM50 AF400 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 300,00 - 370,


0,0 00 P 0 0 500R/4 500,00 00
0

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 12 of 16
Motor Fuses IEC Conta Current Overload Relay
ctor transformer
R Rat Switch-F R Type and Type Type T Type T Current Ma
at ed use ati Size u ri range [A] x
e Cur Type ng r p allo
d ren g n C we
P t G s l d
o [A] /a a loa
w M s d
er [A s cur
] ren
t
[A]
25 377, OS630D03 50 OFAF3AM50 AF400 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 300,00 - 400,
0,0 00 P 0 0 500R/4 500,00 00
0

31 473, OS800D03 80 OFAM3AM80 AF580 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 300,00 - 500,


5,0 00 P 0 0 500R/4 500,00 00
0

35 535, OS800D03 80 OFAM3AM80 AF580 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 580,


5,0 00 P 0 0 850R/4 850,00 00
0

40 605, OS800D03 80 OFAM3AM80 AF750 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 610,


0,0 00 P 0 0 850R/4 850,00 00
0

50 745, OS1250DA 10 OFAF4AAM1 AF1350 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 760,


0,0 00 03P 00 000 850R/4 850,00 00
0

56 832, OS1250DA 12 OFAF4AAM1 AF1650 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 850,


0,0 00 03P 50 250 850R/4 850,00 00
0

Comments:
*: selected trip class of UMC22/100.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 13 of 16
Fuses - 440Vac - 100kA - DOL-NS - IEC Type 2 - gG + UMC
Coordination tables for motor protection
SOC - Selected Optimized Coordination

SCPD type :Fuses Rated voltage :440 Vac


Short circuit current :100 kA Starting type :DOL-NS
Coordination type :IEC Type 2 Overload relay :UMC
Disconnecting Mean present :no Backup / limitor present :no
Current Transformer present :yes Frequency :50-60 Hz
Motor Efficiency Class :IE1 + IE2 Created on date :15/07/2014

Motor Fuses IEC Conta Current Overload Relay


ctor transformer
R Rat Switch-F Ra Type Type Type T Type T Current Ma
at ed use Type tin and Size u ri range [A] x
ed Cur g r p allo
P ren g n C we
o t G s la d
w [A] /a s loa
er M s d
[A cur
] ren
t
[A]
0,1 0,39 OS32GD03 2 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 0,54
2 P 2

0,1 0,53 OS32GD03 4 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 1,00
8 P 4

0,2 0,74 OS32GD03 4 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 1,00
5 P 4

0,3 1,00 OS32GD03 6 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 2,00
7 P 6

0,5 1,30 OS32GD03 6 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 2,00
5 P 6

0,7 1,70 OS32GD03 6 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 2,00
5 P 6

1,1 2,40 OS32GD03 10 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 3,20
0 P 10

1,5 3,20 OS32GD03 16 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 4,30
0 P 16

2,2 4,30 OS32GD03 20 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 5,70
0 P 20

3,0 5,70 OS32GD03 25 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 7,80
0 P 25

4,0 7,40 OS32GD03 32 OFAF000H AF09 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 9,50
0 P 32

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 14 of 16
Motor Fuses IEC Conta Current Overload Relay
ctor transformer
R Rat Switch-F Ra Type Type Type T Type T Current Ma
at ed use Type tin and Size u ri range [A] x
ed Cur g r p allo
P ren g n C we
o t G s la d
w [A] /a s loa
er M s d
[A cur
] ren
t
[A]
5,5 10,1 OS32GD03 40 OFAF000H AF26 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 13,0
0 0 P 40 0

7,5 13,6 OS32GD03 50 OFAF000H AF26 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 16,0
0 0 P 50 0

11, 19,3 OS32GD03 63 OFAF000H AF26 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 23,0
00 0 P 63 0

15, 25,4 OS125GD0 80 OFAF000H AF30 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 28,0
00 0 3P 80 0

18, 30,7 OS125GD0 80 OFAF000H AF38 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 33,0
50 0 3P 80 0

22, 35,9 OS125GD0 12 OFAF00H1 AF52 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 45,0
00 0 3P 5 25 0

30, 48,2 OS125GD0 12 OFAF00H1 AF65 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 55,0
00 0 3P 5 25 0

37, 58,0 OS125GD0 16 OFAF00H1 AF80 UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 0,24 - 63,00 63,0
00 0 3P 0 60 0

45, 70,0 OS125GD0 16 OFAF00H1 AF96 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 72,0
00 0 3P 0 60 185R/4 185,00 0

55, 85,0 OS250D03 20 OFAF1H20 AF116 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 93,0
00 0 P 0 0 185R/4 185,00 0

75, 116, OS250D03 25 OFAF1H25 AF140 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 130,
00 00 P 0 0 185R/4 185,00 00

90, 140, OS400D03 31 OFAF2H31 AF205 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 60,00 - 165,
00 00 P 5 5 185R/4 185,00 00

11 171, OS400D03 31 OFAF2H31 AF265 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 180,00 - 202,


0,0 00 P 5 5 310R/4 310,00 00
0

13 202, OS400D03 40 OFAF2H40 AF265 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 180,00 - 250,


2,0 00 P 0 0 310R/4 310,00 00
0

16 245, OS630D03 50 OFAF3H50 AF305 KORC 4L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 180,00 - 290,


0,0 00 P 0 0 310R/4 310,00 00
0

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 15 of 16
Motor Fuses IEC Conta Current Overload Relay
ctor transformer
R Rat Switch-F Ra Type Type Type T Type T Current Ma
at ed use Type tin and Size u ri range [A] x
ed Cur g r p allo
P ren g n C we
o t G s la d
w [A] /a s loa
er M s d
[A cur
] ren
t
[A]
20 307, OS630D03 63 OFAF3H63 AF400 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 300,00 - 370,
0,0 00 P 0 0 500R/4 500,00 00
0

25 377, OS800D03 80 OFAF3H80 AF580 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 300,00 - 470,


0,0 00 P 0 0 500R/4 500,00 00
0

31 473, OS800D03 80 OFAF3H80 AF580 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 580,


5,0 00 P 0 0 850R/4 850,00 00
0

35 535, OS800D03 80 OFAF3H80 AF580 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 580,


5,0 00 P 0 0 850R/4 850,00 00
0

40 605, OS800D03 80 OFAF3H80 AF750 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 610,


0,0 00 P 0 0 850R/4 850,00 00
0

50 745, OS1250DA 10 OFAF4AH1 AF1350 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 780,


0,0 00 03P 00 000 850R/4 850,00 00
0

56 832, OS1250DA 12 OFAF4AH1 AF1650 KORC 5L UMC22-FBP.0;UMC100-FBP.0;UMC100.3 DC;UMC100.3 UC * 450,00 - 850,


0,0 00 03P 50 250 850R/4 850,00 00
0

Comments:
*: selected trip class of UMC22/100.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.
Page 16 of 16