DESIGNERS GUIDE

This publication gives a general description of


design parameters.
It is responsibility of the users to ensure that their
use is appropriate for any particular application and
that such application complies with all relevant local
and national legislation, standards, codes of
practice and other requirements.
HOLEDECK and its subsidiaries hereby disclaim all
liability howsoever arising from any error in or
omission from this publication and all consequences
of relying on it.
HOLEDECK is a registered trademark.
TABLE OF CONTENTS

A. DESIGN PARAMETERS

1. PRODUCT DIMENSIONS
2. SPANS
3. OVERHANGS
4. PILLARS POSITION
5. BACUS
6. HOLES
7. LOAD BEARING WALLS
8. PARTITIONS UNION
9. STRUCTURAL PARAMETERS

B. VARIANTES HOLEDECK

1. ONE-WAY HOLEDECK
2. POST-TENSIONED HOLEDDECK
3. TRIANGULAR WAFFLE

C. POSIBILIDADES ESPACIALES Y EJEMPLOS DE DISEO

1. STANDARD SPANS
2. LARGE SPANS
3. OVERHANGS
4. FREE POSITION OF SUPPORTS
5. CHANGES OF DIRECTION
6. CURVE GEOMETRY
7. HOLEDECK + BEAMS
8. HOLES
9. LOAD BEARING WALLS
10. ONE-WAY HOLEDECK
11. POST-TENSIONED HOLEDECK
12. TRIANGULAR WAFFLE

D. GLOSARY

E. REGULATION CODES

1
DESIGN PARAMETERS

1. PRODUCT DIMENSIONES
Holedeck is modulated according to a distance
between centres of 80 x 80 cm. It allows
accommodating facilities and elements designed for
standard roofs of 60 cm.

The standard edge is 45 cm. Compression layer


varies from 5 to 10 cm depending on the span and
the loads that the slab has to support.

Holedeck perforations have an area of 0.067 m2. It is possible the simultaneous passage of diferents
services systems.

2
2. SPANS

Holedeck supports spans between


7.5 m and 12.5 m. For longer
spans will be necessary post-
tensioning in 1 to 2 directions.

Spans = 7,5 12,5 m

Short spans (7,5 9 m) Standard spans (9 10,5 m) Long spans (10,5 12 m)

3
3. CANTILEVER
Latticework overhang
Holedeck is perfect for the attainment
of different types of cantilevers:
latticework, passable or habitable
overhangs

Passable overhang

Habitable overhang

SECTION DETAIL.
RESOLUTION OF OVERHANGS

The maximum length of the


cantilever is 4.5 m.
However it will depend on
different factors:

Spans
Permanent loads.
Variable loads.

4
4. PILLARS POSITION
The correct distribution of pillars for a waffle slab pathway is to form a grid as regular as possible, with spans
that differ less than 1 meter. It is important that the supports are attainment separate to the slab edges.
Holedeck, however, supports any distribution of the pillars, facilitating a freedom design and avoiding the
problems of fit a reasonable and compatible structure with partitions.

REGULAR GRID

VARIABLE SPANS GRID

FREE POSITION OF SUPPORTS

5
5. ABACUS
It is not necessary to off-hook the abacus. It will be always
embedded in the thickness of the slab, without
acknowledging their presence clambering underneath

As a minimum we recommend an
abacus dimension of 0.10 L. This
measure will change depending on
the next parameters or factors:
- Geometric requirements of
modulation and staking parts.
- Edge pillars and overhangs.
- Spans decompensation
- Localized loads

3 x 3 (short spans) 4 x 4 (standard spans) 5 x 5 (long spans)

Depending on the regulations it


will be possible to replace the
abacuses by beams. Perforations
will be able to be made in the
beams before the spill of the
concrete.

6
6. HOLES
Holedeck supports holes with the measures indicated in the following image, depending on the distance to
the pillars:

For more complex holes it would be necessary to make a preliminary analysis; it is impossible to establish
fixed rules that solve all cases. However, it is recommended to extend the beams which border the gaps to
the pillars if it is possible; if it were not possible, anchor them in the abacus or solvents areas nerves.

Smaller holes can be made putting a special


part in the cuvette before pouring the
concrete. These holes are perfect for passing
facilities or allow the passage of the solar
light.

7
7. LOAD BEARING WALLS

In the cases which load bearing walls instead of


pillars, it will not be necessary to made abacuses to
resist the punching efforts.

8. PARTITIONS UNION

It is recommended that the partitions be in the


structural nerves or in the solid parts of the
slab.

1 Auxiliary part
2 Acoustic Band
3 Partition

In any case, you can resolve it putting false


ceiling in the pertinent area

1 Auxiliary part
2 Acoustic Band
3 Partition
4 False ceiling

8
9. STRUCTURAL PARAMETERS
Resistance to bending: the inertia of the section, compared with the
same area of a conventional reinforced concrete slab is 18 times
greater.
Horizontal seismic Digs: compared to conventional waffle slab
HOLEDECK reduces its weight by around 15%. This causes the
horizontal thrust in case of earthquake decrease by 8 to 10%.

Structural parameters:
A 1.075cm2
Ix 251.310cm4

Approximate Amounts table armed Holedeck


Under light load
Reinforced top, bottom and mesh including, nerves area

9
HOLEDECK VERSIONS

1. POST-TENSIONED HOLEDECK

With the post-tensioning system Holedeck can span up to 18 meters. Post-tensioning can be in one or both
directions.

2. ONE-WAY HOLEDECK 3. TRIANGULAR WAFFLE

10
SPATIAL POSIBILITIES AND DESIGN EXAMPLES

HOLEDECK allows almost total freedom in the design of floor plans. In the table are given just a few ideas of
the possibilities offered by:

11
GLOSARY

Span: distance between two parallel and consecutive lines of supports.


Supports band: it is the slab band of the slab with wide to each side of the support equal
to 0,25 L2. The support bands include the beams, in case of existing.
Central band: she is the limited one by two bands of supports. .
Abacus: zone of a slab around a support or its capital that is made solid with or without
rebound. In solid slabs it cant exist and, if it exists, it can go accompanied of a capital. In
waffle slabs its existence is mandatory, being able to go accompanied or not of capital.
Capital: widening of the superior end of a support that serves as union between this one
and the slab.
Cantilever: end of a structural element that stand out the wall or element that maintains
them and that has possibility of turn and displacement.
Post tensioned concrete: concrete that is put under tension by means of cables inserted
in its cases, once this one has hardened.
Beam/traverse: structural element that is placed horizontally and served as support of
loads of other structural elements.
Edge beam: beam located between two structural pillars and that serves to support the
edge of a cover or built the framework for.
Edge: thickness of the forged one.
Bucket: recoverable mold of formwork for the accomplishment of waffle slabs.
Punching: failure of a firm one under the effect of one loads direct excessive, that causes
a collapse located of the firm one in the load point. The effort of punching in a piece is
caused by tractions due to the tangential tensions produced by a load or reaction located
in a small surface of a bidirectional concrete element, around the support.

12
REGULATION CODES

- Spain:

CDIGO TCNICO DE LA EDIFICACIN (CTE).

- DB SE: Seguridad estructural. Bases de clculo


- DB SE-AE: Seguridad estructural. Acciones de la edificacin
- DB SE-C: Seguridad estructural. Cimientos
- DB HR: Proteccin frente al Ruido
- DB SI: Seguridad en caso de incendio.

INSTRUCCIN DE HORMIGN ESTRUCTURAL (EHE 08)


NORMAS TECNOLGICAS DE LA EDIFICACIN (NTE)

- European Union: EUROCODE (EC).

- France: CODE DE LA CONSTRUCTION ET DE L'HABITATION.

- United Kingdom: UNITED KINGDOM BUILDING REGULATIONS.

- Holland: BOUWBESLUIT 2012

- Switzerland: NATIONAL BOARD OF HOUSING, BUILDING AND PLANNING BUILDING


REGULATIONS. BOVERKET BUILDING CODE (BBR).

- United States: Code from AMERICAN CONCRETE INSTITUTE (ACI).

- Canada: NATIONAL BUILDING CODE OF CANADA (NBCC).

- Bolivia: REGLAMENTO BOLIVIANO DE CONSTRUCCIN DE EDIFICACIONES. RBC.

- Argentina: REGLAMENTO INPRES-CIRSOC 103 - REGLAMENTO ARGENTINO PARA


CONSTRUCCIONES SISMORRESISTENTES. PARTE II AO 2005 - CONSTRUCCIONES DE
HORMIGON ARMADO.

- Mexico: REGLAMENTO DE CONSTRUCCIONES DISTRITO FEDERAL. NORMAS MEXICANAS


ONNCCE (NMX-C-ONNCCE).

HOLEDECK INTERNATIONAL
PHONE +34 91 502 14 27
c\ Juan de Urbieta 10, bjo
28007 MADRID
SPAIN
info@holedeck.com
www.holedeck.com

13