Sunteți pe pagina 1din 5

*****************************************************************

*****************************************************************
MODEL: MIFIIPI55E20HI00
Firmware version 4.01
DATE: 10-Feb-17 5:41:56 PM
*****************************************************************
*****************************************************************

*****************************************************************
******************SETTINGS***************************************
*****************************************************************
_________________________________________________________________
*** THERMAL MODEL 49 ***
Trip Enable 49............................... No
Pickup 49.................................... 1 In
Alarm Level 49............................... 80 %
Heat Time 49................................. 6 min
Cool Time 49................................. 1 T1
_________________________________________________________________

_________________________________________________________________
*** GROUND IOC 50G2 ***
Trip Enable 50G2............................. No
Pickup 50G2.................................. 1 In
Delay 50G2................................... 0 s
_________________________________________________________________

_________________________________________________________________
*** GROUND IOC 50G1 ***
Trip Enable 50G1............................. No
Pickup 50G1.................................. 1 In
Delay 50G1................................... .5 s
_________________________________________________________________

_________________________________________________________________
*** PHASE IOC 50P2 ***
Trip Enable 50P2............................. No
Pickup 50P2.................................. 1 In
Delay 50P2................................... 0 s
_________________________________________________________________

_________________________________________________________________
*** PHASE IOC 50P1 ***
Trip Enable 50P1............................. No
Pickup 50P1.................................. 2 In
Delay 50P1................................... .5 s
_________________________________________________________________

_________________________________________________________________
*** GROUND TOC 51G ***
Trip Enable 51G.............................. Yes
Pickup 51G................................... .2 In
Curve 51G.................................... DEFINITE TIME
TD Mult 51G.................................. 1
Def Time 51G................................. .8 s
_________________________________________________________________

_________________________________________________________________
*** PHASE TOC 51P ***
Trip Enable 51P.............................. Yes
Pickup 51P................................... 1.2 In
Curve 51P.................................... DEFINITE TIME
TD Mult 51P.................................. 1
Def Time 51P................................. .8 s
_________________________________________________________________

_________________________________________________________________
*** PRODUCT SETUP ***
Relay Operation.............................. READY
Frequency.................................... 50
Phase CT Ratio............................... 120
Ground CT Ratio.............................. 120
_________________________________________________________________

_________________________________________________________________
*** BF TO OPEN ***
Function..................................... No
Delay........................................ 400 ms
_________________________________________________________________

_________________________________________________________________
*** COLD LOAD PICKUP ***
Function..................................... No
Outage Time.................................. 2 s
On Load Time................................. 1 s
Phase IOC Mult............................... 1
Phase TOC Mult............................... 1
_________________________________________________________________

_________________________________________________________________
*** COUNTERS ***
I^2 MAX Value................................ 999 kA2
_________________________________________________________________

_________________________________________________________________
*** OSCILLOGRAPHY MASK ***
Oscillo by communic.......................... No
Oscillo by digital input..................... No
Oscillo by tripping.......................... No
Oscillo by pickup............................ No
_________________________________________________________________

_________________________________________________________________
*** EVENT MASK ***
50P1 Pickup.................................. Yes
50G1 Pickup.................................. Yes
51P Pickup................................... Yes
51G Pickup................................... Yes
50P2 Pickup.................................. Yes
50G2 Pickup.................................. Yes
49 Alarm..................................... Yes
50P1 disabled (by DI)........................ Yes
50P2 disabled (by DI)........................ Yes
50G1 disabled (by DI)........................ Yes
50G2 disabled (by DI)........................ Yes
51P disabled (by DI)......................... Yes
51G disabled (by DI)......................... Yes
49 disabled (by DI).......................... Yes
Trip disabled (by DI)........................ Yes
50P1 Trip.................................... Yes
50G1 Trip.................................... Yes
51P Trip..................................... Yes
51G Trip..................................... Yes
50P2 Trip.................................... Yes
50G2 Trip.................................... Yes
49 Trip...................................... Yes
General trip................................. Yes
Protection status............................ Yes
Output 1..................................... Yes
Output 2..................................... Yes
Output 3..................................... Yes
Output 4..................................... Yes
Digital Input 1.............................. Yes
Digital Input 2.............................. Yes
Sett. change disable......................... Yes
Trip operation by input...................... Yes
Trip operation by command.................... Yes
Reset latch aux.............................. Yes
Close Breaker operation...................... Yes
Settings group change........................ Yes
Oscillo trigg by DI.......................... Yes
Oscillo trigg by comm........................ Yes
Cold load Pickup............................. Yes
Breaker 52A.................................. Yes
Breaker 52B.................................. Yes
Breaker Closed............................... Yes
BF to open................................... Yes
I^2 Alarm.................................... Yes
Settings change.............................. Yes
EEPROM Failure............................... Yes
User settings................................ Yes
_________________________________________________________________

_________________________________________________________________
*** USER CURVE ***
A Parameter.................................. .05 s
B Parameter.................................. 0 s
P Parameter.................................. .04
Q Parameter.................................. 1
K Parameter.................................. 0 s
_________________________________________________________________

_________________________________________________________________
*** THERMAL MODEL 49 (group 2) ***
Trip Enable 49............................... No
Pickup 49 T2................................. 1 In
Alarm Level 49 T2............................ 80 %
Heat Time 49 T2.............................. 6 min
Cool Time 49 T2.............................. 1 T1
_________________________________________________________________

_________________________________________________________________
*** GROUND IOC 50G2 (group 2) ***
Trip Enable 50G2 T2.......................... No
Pickup 50G2 T2............................... 1 In
Delay 50G2 T2................................ 0 s
_________________________________________________________________

_________________________________________________________________
*** GROUND IOC 50G1 (group 2) ***
Trip Enable 50G1 T2.......................... No
Pickup 50G1 T2............................... 1 In
Delay 50G1 T2................................ 0 s
_________________________________________________________________

_________________________________________________________________
*** PHASE IOC 50P2 (group 2) ***
Trip Enable 50P2 T2.......................... No
Pickup 50P2 T2............................... 1 In
Delay 50P2 T2................................ 0 s
_________________________________________________________________

_________________________________________________________________
*** PHASE IOC 50P1 (group 2) ***
Trip Enable 50P1 T2.......................... No
Pickup 50P1 T2............................... 1 In
Delay 50P1 T2................................ 0 s
_________________________________________________________________

_________________________________________________________________
*** GROUND TOC 51G (group 2) ***
Trip Enable 51G T2........................... No
Pickup 51G T2................................ .5 In
Curve 51G T2................................. DEFINITE TIME
TD Mult 51G T2............................... .5
Def Time 51G T2.............................. 1 s
_________________________________________________________________

_________________________________________________________________
*** PHASE TOC 51P (group 2) ***
Trip Enable 51P T2........................... No
Pickup 51P T2................................ .5 In
Curve 51P T2................................. DEFINITE TIME
TD Mult 51P T2............................... .5
Def Time 51P T2.............................. 1 s
_________________________________________________________________
_________________________________________________________________
*** ADV. GENERAL SETTINGS ***
IDENTIFICATION............................... MIF II
Settings Group............................... 1
Trip Min Time................................ 200 ms
_________________________________________________________________

S-ar putea să vă placă și