NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

SUBSTRATE CLADDING PANELS HAVE TO BE SATISFIED.

FIXING

THERMOPAD FixU T, THICKNESS 5 mm


art.No 05.001.5

WASHER

THERMAL INSULATION LAYER

BRACKET FixU T, FIXED SUPPORT


art.No 02.ft.190

T PROFILE 80x60x2 mm
art.No 01.2.80602.6 RAINSCREEN SYSTEM

art.No 04.4.4812.1 QV1


MECHANICAL FASTENING SYSTEM
HPL PANEL FUNDERMAX USING VISIBLE RIVETS

CLADDING PANELS
art.No 04.4.518.2
FIXED POINT FLEXIBLE POINT
FUNDERMAX MAX EXTERIOR

DRAWING

01 HORIZONTAL SECTION

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
art.No 04.4.4812.1
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


FIXING CLADDING PANELS HAVE TO BE SATISFIED.

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

T PROFILE 80x60x2 mm
art.No 01.2.80602.6

HPL PANEL FUNDERMAX

art.No 04.4.518.2

art.No 04.4.4812.1
RAINSCREEN SYSTEM
FIXING
QV1
BRACKET FixU T, FIXED SUPPORT
MECHANICAL FASTENING SYSTEM
art.No 02.ft.190 USING VISIBLE RIVETS
THERMOPAD FixU T, THICKNESS 5 mm
art.No 05.001.5 CLADDING PANELS

FUNDERMAX MAX EXTERIOR

THERMAL INSULATION LAYER DRAWING

SUBSTRATE 02 VERTICAL SECTION

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

SUBSTRATE _ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
THERMAL INSULATION LAYER SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

HPL PANEL FUNDERMAX _ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE
CLADDING PANELS HAVE TO BE SATISFIED.

art.No 04.4.518.2

FIXING

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

WASHER

BRACKET FixU L, FLEXIBLE SUPPORT RAINSCREEN SYSTEM


art.No 02.fl.190

QV1
MECHANICAL FASTENING SYSTEM
L PROFILE 60x40x2 mm
art.No 01.1.60402.6
USING VISIBLE RIVETS

CLADDING PANELS
art.No 04.4.4812.1

FUNDERMAX MAX EXTERIOR

DRAWING

03 EXTERNAL CORNER

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
FIXING
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.
THERMOPAD FixU T, THICKNESS 5 mm
art.No 05.001.5

WASHER

BRACKET FixU T, FIXED SUPPORT


art.No 02.ft.190

L PROFILE 60x40x2 mm
art.No 01.1.60402.6

art.No 04.4.4812.1

HPL PANEL FUNDERMAX RAINSCREEN SYSTEM

QV1
art.No 04.4.518.2 MECHANICAL FASTENING SYSTEM
USING VISIBLE RIVETS

CLADDING PANELS

FUNDERMAX MAX EXTERIOR


THERMAL INSULATION LAYER
DRAWING
SUBSTRATE
04 INTERNAL CORNER

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SUBSTRATE SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
THERMAL INSULATION LAYER
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

T PROFILE 80x60x2 mm
art.No 01.2.80602.6

art.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

HPL PANEL FUNDERMAX RAINSCREEN SYSTEM

QV1
MECHANICAL FASTENING SYSTEM
art.No 04.4.518.2 USING VISIBLE RIVETS

L PROFILE 40x40x2 mm CLADDING PANELS


art.No 01.1.40402.6

FUNDERMAX MAX EXTERIOR


PERFORATED ALUMINUIM SHEET
DRAWING
SELF-DRILLING SCREW
L PROFILE 60x40x2 mm 05 VERTICAL SECTION_FACADE BASE
art.No 01.1.60402.6
EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
ALUMINIUM SHEET
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
PERFORATED ALUMINIUM SHEET
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


L PROFILE 40x40x2 mm CLADDING PANELS HAVE TO BE SATISFIED.
art.No 01.1.40402.6

art.No 04.4.518.2

HPL PANEL FUNDERMAX

BRACKET FixU T, FIXED SUPPORT


art.No 02.ft.190

FIXING

art.No 04.4.4812.1

THERMOPAD FixU T, THICKNESS 5 mm


art.No 05.001.5 RAINSCREEN SYSTEM

QV1
T PROFILE 80x60x2 mm MECHANICAL FASTENING SYSTEM
art.No 01.2.80602.6 USING VISIBLE RIVETS

CLADDING PANELS

FUNDERMAX MAX EXTERIOR

THERMAL INSULATION LAYER DRAWING

SUBSTRATE
06 VERTICAL SECTION_ROOFBORDER COVER

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

SELF-DRILLING SCREW

FIXING
THERMOPAD FixU L, THICKNESS 5 mm
art.No 05.001.1

WASHER

THERMAL INSULATION LAYER

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

RAINSCREEN SYSTEM

L PROFILE 60x40x2 mm
art.No 01.1.60402.6 QV1
MECHANICAL FASTENING SYSTEM
art.No 04.4.4812.1 USING VISIBLE RIVETS

HPL PANEL FUNDERMAX CLADDING PANELS

art.No 04.4.518.2 FUNDERMAX MAX EXTERIOR

DRAWING

07.1 HORIZONTAL SECTION_WINDOW REVEAL

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

SELF-DRILLING SCREW

FIXING
THERMOPAD FixU L, THICKNESS 5 mm
art.No 05.001.1

WASHER

THERMAL INSULATION LAYER

ALUMINIUM SHEET

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

RAINSCREEN SYSTEM

L PROFILE 60x40x2 mm
art.No 01.1.60402.6 QV1
MECHANICAL FASTENING SYSTEM
art.No 04.4.4812.1 USING VISIBLE RIVETS

HPL PANEL FUNDERMAX CLADDING PANELS

art.No 04.4.518.2 FUNDERMAX MAX EXTERIOR

DRAWING

07.2 HORIZONTAL SECTION_WINDOW REVEAL

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


SUBSTRATE
AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
THERMAL INSULATION LAYER
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


T PROFILE 80x60x2 mm CLADDING PANELS HAVE TO BE SATISFIED.
art.No 01.2.80602.6

art.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

HPL PANEL FUNDERMAX

art.No 04.4.518.2
L PROFILE 40x40x2 mm RAINSCREEN SYSTEM
art.No 01.1.40402.6

PERFORATED ALUMINIUM SHEET QV1


MECHANICAL FASTENING SYSTEM
L PROFILE 60x40x2 mm USING VISIBLE RIVETS
art.No 01.1.60402.6

SELF-DRILLING SCREW CLADDING PANELS

FUNDERMAX MAX EXTERIOR

DRAWING

08.1 VERTICAL SECTION_WINDOW LINTEL

EDITION

JANUARY 2015
8.1 SUBSTRATE
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
THERMAL INSULATION LAYER
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


T PROFILE 80x60x2 mm CLADDING PANELS HAVE TO BE SATISFIED.
art.No 01.2.80602.6

art.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

HPL PANEL FUNDERMAX

art.No 04.4.518.2

L PROFILE 40x40x2 mm RAINSCREEN SYSTEM


art.No 01.1.40402.6

ALUMINIUM SHEET QV1


MECHANICAL FASTENING SYSTEM
SELF-DRILLING SCREW USING VISIBLE RIVETS

CLADDING PANELS

FUNDERMAX MAX EXTERIOR

DRAWING

08.2 VERTICAL SECTION_WINDOW LINTEL

EDITION

JANUARY 2015
8.2 NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
art.No 04.4.4812.1
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
FIXING OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


BRACKET FixU L, FLEXIBLE SUPPORT CLADDING PANELS HAVE TO BE SATISFIED.
art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

T PROFILE 80x60x2 mm
art.No 01.2.80602.6

HPL PANEL FUNDERMAX

RAINSCREEN SYSTEM
art.No 04.4.518.2
L PROFILE 60x40x2 mm
art.No 01.1.60402.6 QV1
MECHANICAL FASTENING SYSTEM
ALUMINIUM SHEET USING VISIBLE RIVETS

CLADDING PANELS

FUNDERMAX MAX EXTERIOR

DRAWING

08.3 VERTICAL SECTION_WINDOW LINTEL

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

SELF-DRILLING SCREW

ALUMINIUM SHEET

PERFORATED ALUMINIUM SHEET

L PROFILE 40x40x2 mm
art.No 01.1.40402.6

art.No 04.4.518.2

HPL PANEL FUNDERMAX

T PROFILE 80x60x2 mm
art.No 01.2.80602.6

RAINSCREEN SYSTEM

FIXING
QV1
MECHANICAL FASTENING SYSTEM
art.No 04.4.4812.1
USING VISIBLE RIVETS
BRACKET FixU T, FIXED SUPPORT
art.No 02.ft.190 CLADDING PANELS

THERMOPAD FixU T, THICKNESS 5 mm


art.No 05.001.5 FUNDERMAX MAX EXTERIOR

DRAWING

THERMAL INSULATION LAYER


09 VERTICAL SECTION_WINDOW SILL
SUBSTRATE
EDITION

JANUARY 2015