Sunteți pe pagina 1din 11

Proceedings of the ASME 2016 PVP PRESSURE VESSELS & PIPING CONFERENCE

PVP2016
July 17-21, 2016, Vancouver, BC, Canada

PVP2016-63088

A PRACTICAL APPROACH TO MITIGATE THE EXCESSIVE VIBRATION OF A PIPING SYSTEM


SUBJECTED TO FLOW-INDUCED EXCITATION

Reza Azizian Paolo Torrado


Engineering & Inspection Services Engineering & Inspection Services
Metairie, LA, USA Metairie, LA, USA

vibration may lead to fatigue crack propagation and


ABSTRACT consequently may cause system failure. It is imperative that once
a vibration problem is identified an assessment be performed in
Vibration is a common problem in industrial facilities which a timely fashion. For this reason, it is necessary to educate
may lead to the propagation of undesired high stress levels industry of the current assessment technologies and to further
induced by the deflection of a component as well as the improve upon existing assessment techniques.
interaction between different metallic components. In a piping
system, a long term excessive vibration may cause fatigue and Fixed equipment vibration is considered a multidisciplinary field
fretting-wear which may result in system failure. In the present which requires knowledge in process engineering, fluid
work, excessive vibration problems in a piping system were mechanics, fluid-structure interaction, rotating equipment
explored in greater detail. Different sources of vibration, as well vibration, structural vibration, and acoustic vibration. A
as proper approaches to evaluate and assess the integrity of the vibration assessment consists of five main steps [5]: (1) diagnose
system, were investigated. A case study of a piping system the troubled system by measuring vibration levels and
subjected to flow-induced excitation was assessed. This frequencies, (2) utilize recognized standards to identify areas of
assessment was established based upon both numerical modeling concern, (3) identify possible excitation sources, particularly
of the system utilizing CAESAR II software and vibration flow-induced vibration (FIV) (4) model system to determine
readings of the piping system while operating in an industrial fundamental vibration parameters including: natural frequencies,
facility. Furthermore, an experimental modal analysis was mode shapes, and system dynamic response, (5) investigate
implemented using MEscope software to calibrate the numerical possible system modifications to eliminate or attenuate excessive
model. Theoretical and operational modal analyses were vibration.
performed in order to adopt proper modifications to mitigate the
excessive vibration. Excessive vibration may occur when the natural frequency of a
system coincides with the frequency of an excitation source. The
1. INTRODUCTION physical behavior of a troubled system needs to be measured in
Mechanical failure of a system due to excessive vibration can order to quantify damage and determine a proper course of
lead to grave environmental, economic or human health action. It is important to perform a thorough diagnosis of a
consequences. Data gathered in the UK sector of the North Sea system by measuring different parameters such as pressure
has shown that over twenty percent of pipe failures were caused fluctuation, acceleration, and dynamic strain. The proper choice
by vibration and fatigue [1]. Fixed equipment in industrial plants of method and type of measuring equipment will depend on the
such as piping systems, pressure vessels and steel structures can system response and excitation mechanisms.
suffer from excessive vibration [2-4] . Long term excessive

1 Copyright 2016 by ASME


The vibration technician should consider several factors before excitation mechanisms. The excitation mechanisms were then
system behavior is measured. Some of these include identifying categorized as flow-induced vibration (FIV), acoustic-induced
critical locations to take the measurements, installing sensors vibration (AIV), pressure pulsation vibration (PPV), and two-
properly, adopting mounting solutions for high temperature phase flow induced vibration (TPV) [3, 5].
equipment, and defining proper signal conditioning parameters.
Measuring of the system behavior will help to quantify the level Flow-induced vibration (FIV) inside of a piping system may
of vibration but more importantly it will provide valuable insight occur as a result of oscillating flow, multi-phase flow, and
in identifying the system modes that have been exited and the geometric constraints [5]. The most common types of flow-
source of this excitation. Vibration sources can be categorized as induced excitation are turbulence and vortex-shedding. A piping
low frequency (<30 Hz), medium frequency (30 Hz to 300 Hz), system may also experience high levels of vibration caused by
and high frequency (>300 Hz). Classification of the excitation releasing high frequency energy downstream of a pressure
frequency allows identification of the excitation mechanisms [3, reducing device such as control valves and relief valves. This
6]. Some of the phenomena within these categories that can type of excessive vibration is categorized as acoustic induced
cause excessive vibration include flow-induced excitation, vibration (AIV) [1].
pressure pulsation, and high frequency acoustic-induced
vibration. Flow induced vibration is usually initiated due to Pressure pulsation may also cause to excessive vibration in a
geometric constrains in the system. Vortex-shedding and piping system. The pulsation could be initiated by a piece of
turbulence excitations are the most common type of flow- rotating equipment as well as a pressure drop as a result of
induced excitations [7]. Pressure pulsation may be caused by a geometrical constraints [5]. The pulsation frequencies may be
piece of rotating equipment and generate distinct frequencies generated at integral multiples of the pump-operating speed and
which are integral multiples of the equipment operating speed multiples of the number of pump plunger, blades or vanes [6].
[6]. Furthermore, a loosely supported piping system may This pulsation may lead to an excessive vibration when its
experience interactions between the pipe and its supports [8-10]. frequency coincides with the systems acoustic and structural
This may subsequently lead to the propagation of high frequency natural frequencies. The excessive vibration due to pressure
vibration due to impact and friction [11, 12]. pulsation could be reduced by utilizing a discharge dampener or
suction stabilizer [6].
Azizian and Torrado [5] have recently provided insights into the
vibration of fixed equipment including piping system subjected
to flow-induced vibration. In current study, excessive vibration
problems in a piping system were explored in greater detail. The
criteria to assess the integrity of a piping system experiencing a
high level of vibration due to flow-induced excitation were
investigated. An experimental program was conducted to acquire
vibration data including dominant frequencies and acceleration
levels. For this purpose, a portable multi-channel vibration
analyzer and industrial uni-axial accelerometers were utilized.
Different sources of vibration including pressure pulsation
caused by rotating equipment, high frequency acoustic,
turbulence, and vortex shedding excitations were investigated. In
addition, a modal analysis was performed utilizing piping stress
analysis software, CAESAR II [13]. This analysis provided
corrective actions to reduce the excessive vibration by
maintaining a twenty percent separation between the natural
frequencies of the system and the likely excitation frequencies. Figure 1 A schematic of a piping system and sources of vibration
The corrective modifications may increase thermal stress on the classifications [5]
piping system which enforced the necessity to evaluate the
piping thermal stress. Figure 1 shows a schematic of a piping system experiencing a
high level of vibration. This schematic illustrates two lines of
2. SOURCE OF VIBRATION fluid including gas (blue line) and liquid (yellow line). These two
The first step in evaluating and assessing a piping system lines are then mixed and form a two-phase flow (Red line).
experiencing high levels of vibration is to identify the source of Different possible source of vibration are highlighted in the
vibration. This step may be intricate due to different types of schematic. These sources of vibration are not generally taken
mechanism involved as the source of excitations. In this research into consideration in a preliminary design stage and may not be
a piping system, experiencing a high level of vibration in an evaluated until a visual excessive vibration or a failure occurs
industrial facility, was chosen as a case study. Figure 1 illustrates [3].
a schematic of the concerned piping system and the likelihood

2 Copyright 2016 by ASME


2.1 Flow-Induced vibration shedding frequency (f) is determined using Strouhal number (St),
Modeling of a structure conveying flow may be dependent upon flow velocity (U), and obstruction characteristic length (D) based
the type of a flow regime as well as the type of coupling between on the following equation:
a structure and a flow. A flow regime could be categorized as
steady or unsteady [7] . Fluid structure interaction (FSI) is an = / (1)
event which a structure is excited with an unsteady-flow. In this
event, a coupled relationship between a structure and a flow are The vortex-shedding excitation, usually in tandem with
considered as result of their interaction forces [14]. Flow induced turbulence excitation, may lead to an excessive vibration when
vibration (FIV), however, is an occasion which a structure is its exclusive frequency coincides with an external resonator
excited with a steady-flow. In this type of vibration, an frequency. The resonator frequencies could be fluid acoustic
uncoupled condition is assumed between a structure and a flow natural frequencies or structural natural frequencies. Figure 2
[14]. illustrates the regions experiencing turbulence in tandem with
vortex shedding in a piping systems geometrical constraints
Modeling of a structure based upon the FSI concept is including a tee-connection, a dual elbow, and a reducer.
challenging due to the difficulties to model the fluid forces as
well as to model the coupled reaction between the fluid forces The energy flux due to a turbulent excitation can be quantified
and the structure response. Considering a detailed modeling as using a factor called pressure resistant coefficient (tot) as follows
per FSI usually leads to a more precise results. On the other hand, [15]:
modeling of a structure using the FIV concept is simpler to
implement due to considering an uncoupled condition. This type
= , (2)
of structural modeling is less time consuming in terms of 2 2
computation. However, the uncoupled simplification may affect
the accuracy of the simulation result. where Pin is the total pressure of the systems inlet, Pout is the
mean static pressure of the systems outlet, is the density of
fluid and U is the mean velocity in the piping system.

Turbulence excitations, inside of a piping system, may be


categorized based on their nature of propagation including: (1)
propagation due to geometrical constraints, and (2) propagation
caused by the flow characteristic (phase and energy) as well as
the type of rotating equipment which drives the flow inside of
the piping system.

Shiraishi et al. [15] classified the turbulence flow inside of a


piping system considering the system geometrical constraints as
follows:

(1) Turbulence initiated due to the piping systems inlet and


branch conditions,
(2) Turbulence propagated in the boundary layer of the pipe
wall,
(3) Turbulence associated with separation and
reattachment of the flow inside of a piping system, and
(4) Turbulence propagated in the outer region of an elbow.

In general, flow kinetic energy, 2 2, may represent the


likelihood of the turbulence excitation. However, the phase of
flow, as well as the type of rotating equipment (such as
Figure 2 Regions experiencing flow-induced excitation:
(a) Tee-connection (b) Dual elbow (c) Reducer [5] reciprocating machinery, positive displacement pumps and
centrifugal compressors), may affect the assessment concerning
Turbulence and vortex shedding are examples of FIV or FSI in a the likelihood of excitation.
piping system. These events may occur in tee-connections,
valves, reducers, shallow cavities, or elbows as a result of a flow 2.2 Two-Phase Flow Induced Vibration
separation and re-attachment as well as pressure fluctuations due Excessive vibration in a piping system may be initiated as a
to flow experiencing geometrical constraints [15]. Vortex- result of a two-phase flow (gas and liquid). This event may occur
due to reaction forces cause by intermittent movement of large

3 Copyright 2016 by ASME


bubbles. Figure 3 classifies flow patterns inside of a horizontal 2.3 Acoustic Induced Vibration (AIV)
pipe. These classifications characterize the severity of excitation A piping system may experience a high frequency excitation as
force due to a non-homogenous flow distribution [2]. a result of flow passing through pressure reducing devices such
as relief valves, compressor recycle valves, depressurizing
valves, or restriction orifices [1]. This type of event is
categorized as acoustic induced vibration (AIV). A broad-band
high frequency between 300 Hz to 1500 Hz may be initiated in
downstream of the pressure reducing devices while AIV is
propagated in a piping system. Figure 5 illustrates the shell
vibration of a piping system experiencing AVI at 650 Hz [5].

Figure 3 Flow classification in horizontal piping (Nakamura et al. [2])


(Reproduced by permission)

This classification of a flow pattern allows the excitation level to


be quantified [7]. As shown in Figure 4, Weisman [16] developed
a flow pattern map based upon the superficial liquid flow Figure 5 Shell mode vibration of a 6 pipe subjected to AIV at 650 Hz
using ABAQUS [5, 17]
velocity (VSL) and the superficial gas velocity (V SG). Two
correction factors, 1 and 2, were also adopted to account for
Carucci and Mueller [18] developed an empirical design
the physical property and pipe diameter variations. The
guideline based upon the generated sound level and pipe
superficial velocities are given by [16]:
diameter. The sound level occurring immediately downstream of
a pressure reducing device may be quantified using Equation 5
= (1 ) , (3)
[18]:
= , (4)
12 3.6 1.2
where is the void fraction, UG is the gas mean velocity and UL = 10 [2 ( ) ( ) ] + 126.1, (5)
1
is the liquid mean velocity.
The flow-rate of gas and liquid should be controlled to avoid a where is the sound power level, M is the mass flow-rate, P1
two phase flow turbulence caused by an intermittent flow is the upstream pressure, P2 is the downstream pressure, T is the
including plug flow, slug flow or forth flow. On the other hand, temperature and W is the molecular weight. Figure 6, shows the
the initial distribution between gas and liquid phases in a piping Eisinger fatigue allowable limit [19] for a piping system
inlet and outlet connections may also contribute the level of the experiencing AIV. This allowable limit was established based on
excitation forces. This could be regulated using a proper angle of the relationship between sound power level (as quantified in
connection and a distribution system. Equation 5) and a dimensionless ratio of the pipe diameter to
wall thickness.

Figure 4 Flow classifications in a horizontal pipe [16], (Reproduced by


Figure 6 Eisigner fatigue allowable for acoustic induced vibration [18, 19]
permission)
(Reproduced with permission)

4 Copyright 2016 by ASME


In addition to Eisinger guideline [19], Health and Safety model are three important aspects of this assessment [5].
Executive [20] and the Energy Institute [3] also developed Adopting a proper vibration measurement approach plays a vital
guidelines using the concept of the likelihood of failure (LOF) to role in this step-wise assessment. For instance, using dynamic
determine acceptable design criteria for piping systems subjected strain gauges is the proper method to capture a high frequency
to acoustic induced vibration (AIV) [5]. vibration while for a low frequency vibration utilizing
accelerometers is recommended [3, 6]. However, there are
3. PROBLEM DEFINTION AND VIBRATION limitations to utilize the aforementioned sensors based upon the
ASSESSMENT operating conditions of the system as well as the sensors
A piping system experiencing high levels of vibration while mounting solutions. In addition to examining the vibration level,
operating in an industrial facility was chosen as a case study in vibration measurement may be performed to extract modal
this paper. A vibration audit program should be implemented to parameters of a system including natural frequencies, mode
assess the integrity of the piping system concerning the shapes and damping ratios. This estimation of system
acceptable level of vibration. Furthermore, the excessive identification is called experimental modal analysis (EMA) [21].
vibration should be studied in greater detail using a numerical This could be achieved by implementing an output-input modal
model. The vibration study may then provide recommendations analysis utilizing the excitation force (input) of a calibrated-
to reduce the excessive vibration levels. As shown in Figure 7, a hammer test as well as a system response (output) using
step-wise assessment procedure was adopted to implement the accelerometers. However, a proper implementation of EMA for
vibration audit (Figure 7-A) and to perform the vibration study a piping system while operating in an industrial facility is
(Figure 7-B). The acceptability of vibration levels, identification challenging due to the
of probable excitation sources, and updating the numerical

Figure 7 Step-wise flowchart to assess and mitigate excessive vibration: (A) Vibration Audit; (B) Vibration Study [5]

5 Copyright 2016 by ASME


necessity of ceasing the operation in order to take the vibration 3.1 VIBRATION MEASUREMENT
measurement [5]. The EMA method could only be implemented Vibration readings were taken along the piping system while the
on an stationary system (non-operating system) which may lead unit was operating. As shown in Figure 8, fifteen critical
to neglecting some of the effect associated with a system locations (config.1 to config.15) along the piping system were
operation including neglecting fluid mass, active or non-active identified to measure the level of vibration. For each location of
support conditions and pipe pre-tension conditions [5]. The concern, acceleration was measured in three orthogonal
aforementioned EMA methods restrictions lead to the directions including: north-south (X), west-east (Z), and vertical
development of a new type of analysis, known as operational (Y) directions (see figure 9).
modal analysis (OMA) [22]. The OMA method only requires a
systems out-put response to extract its modal parameters. The data were acquired using an OROS systems portable multi-
Therefore, this method could be implemented on a system while channel vibration analyzer and industrial PCB uni-axial
it is operating in an industrial facility. The modal parameters accelerometers with 100 mV/g sensitivity. The accelerometers
determined by the EMA or OMA method can be subsequently were attached to curved surface magnets and mounted on the
utilized to calibrate an FEA model [5]. piping system as illustrated in Figure 9.

Figure 8 CAESAR model of a piping system and measurement locations [5]

6 Copyright 2016 by ASME


Accelerometer-1 Table 1 shows the measured dominant excitation frequencies.
These results indicated that the frequncy of 6.25 Hz, 8.125 Hz,
10 Hz, 11.88 Hz, 34.38 Hz and 63 Hz are the dominent
excitation frequencies along the piping system. Table 2 shows
the average spectrum velocities associated with the measured
dominant excitation frequencies. These results reported a
Accelerometer-2 maximum spectrum velocity of 0.67 inch/sec at the measurment
location of C.5.

Table 1 Measured dominant excitation frequencies (Hz) [5]


Accelerometer-3 C.1 C.2 C.3 C.4 C.5 C.6 C.7 C.8
x-dir. 25 6.25 6.25 6.25 6.25 6.25 6.25 6.25
y-dir. 6.25 6.25 6.25 6.25 6.25 63 6.25 34.38
z-dir. 6.25 6.25 11.88 11.88 6.25 6.25 6.25 6.25
C.9 C.10 C.11 C.12 C.13 C.14 C.15
x-dir. 6.25 6.25 6.25 6.25 6.25 22.5 10
y-dir. 34.38 6.25 6.25 34.38 8.125 6.25 6.25
z-dir. 6.25 6.25 6.25 6.25 6.25 6.25 6.25
Figure 9 Accelerometer configuration and mounting direction
The resultant measurements were then post processed by Table 2 Measured average spectrum velocities (inch/sec) associated with
calculating FFT average spectrum, overall RMS velocity and the dominant frequencies (Table 1) [5]
zero-up crossing frequency. For each point of measurement, a C.1 C.2 C.3 C.4 C.5 C.6 C.7 C.8
comparative figure was constructed (as shown in Figure 10). The
x-dir. 0.30 0.47 0.65 0.61 0.67 0.68 0.59 0.64
figure consists of EI vibration limits [3] and the recorded average
spectrum. For FFT average spectrum computation, 1601 spectral y-dir. 0.21 0.20 0.21 0.15 0.08 0.04 0.05 0.05
lines of frequency resolution were adopted with a frequency
z-dir. 0.35 0.21 0.28 0.31 0.29 0.36 0.34 0.53
range of 0 to 1000 Hz. A linear spectrum averaging method with
26 frequency averages was also utilized. For each measurement C.9 C.10 C.11 C.12 C.13 C.14 C.15
location, time domain responses and averaged spectrums of three
parameters including acceleration, velocity and displacement x-dir. 0.63 0.56 0.64 0.57 0.04 0.05 0.19
were recorded. y-dir. 0.044 0.042 0.063 0.047 0.097 0.07 0.09

z-dir. 0.636 0.65 0.311 0.137 0.164 0.187 0.64

The measured dominant excitation frequencies could be


utilized to identify the likely frequency ranges associated with
the sources of vibration.

Table 3 classifies the common sources of vibration in a piping


system based on their range of frequencies. These classifications
identify the distinct frequencies associated with rotating
equipments pulsation, cavitation, acoustic vibration, and flow-
induced vibration. Low frequencies of 6.25 Hz, 11.88 Hz, and a
band of 25-30 Hz were detected as flow-induced frequencies.
Furthermore, a band of 60-65 Hz, likely attributed to a piece of
rotating equipment, was identified.

Figure 10 comparisons between velocity average spectrum and Energy Institute


vibration limits

7 Copyright 2016 by ASME


Table 3 Source of vibration categorization [5] Therefore, the vortex-shedding frequencies were calculated for
Possible Source of Criteria Associated Dominant the aforementioned locations having the flow-rates of 4,000
Vibration Frequencies
lbs/hr and 137,000 lbs/hr for the gas and the liquid lines,
Rotating Equipment Rotating equipment speed A band of 60-65 Hz respectively. Furthermore, a 5 percent corrosion allowance was
pulsation and its integral multiples considered in the calculations. The calculated vortex-shedding
Cavitation and flushing High frequency response No frequencies and the associated dominant measured frequencies
(>300Hz) are listed in Table 3.
High frequency Acoustic High frequency response No
(associated with Relief (>500Hz) Table 3 Vortex shedding frequency calculation
valve & Control valve ) Calculated Associated measured
frequency frequency
Turbulence and Vortex Frequency less than 30Hz 6.25 Hz, 11.88 Hz, a (Vortex-Shedding )
Shedding band of 25-30 Hz Dual elbow
11.90 11.88
3 to 1.5
Figure 11 compares the measured vibration level, along the reducer 23.81 Range of 25-30 Hz
piping system, against the Energy Institute (EI) guideline [3].
This guideline classifies the severity of vibration level in three 1.5to 6 piping
6.84 6.25 Hz
main categories based on the risk of fatigue-damage occurring in
a piping system. Vibration levels are categorized as either
problem, concern or acceptable. Based on the
Figure 12 illustrates the trends and the levels of RMS velocities
aforementioned classifications, the vibration levels associated
for the dominant measured excitation frequencies for the fifteen
with the frequency band of 60-65 Hz were categorized as
measurement locations along the piping system. These trends
acceptable while the frequencies associated with 6.25 Hz,
provided valuable insights into the possible source of vibration
11.88 Hz and 25-30 Hz were classified as concern. According
and their dissipative behavior along the piping system. The trend
to EI guidelines [3], the problem zone has a high risk of fatigue
indicated that the highest vibration levels are attributed to a
damage, while the concern zone has a potential risk for fatigue
frequency of 6.25 Hz and are mostly located in x-direction of the
damage.
measurement locations (3) to (12). Figure 3-b and 3-c shows the
trends for dominant excitation frequencies of 11.88 Hz and 25
Hz, respectively. These trends indicated that the vibration levels
were reduced along measurement locations (3) to (14). Figure 3-
d exhibits the trend for a frequency of 60 Hz which has a
negligible contribution to the overall vibration level [5].

Figure 11 Energy Institute vibration levels allowable [3] and measured


velocities (Flowchart taken from Guidelines for the avoidance of vibration
induced fatigue in process pipework published by the Energy Institute)

As mentioned earlier, vortex shedding in tandem with


turbulence excitation may resonate the structural natural
frequencies. Therefore, it is important to identify the critical
locations that are potentially creating excitation frequencies due
to vortex shedding. These points of concern are listed as follows:

(1) Dual elbow (Figure 8: config.3 and config.4)


(2) 3x1.5 reducer, (Figure 8: config.1)
(3) 1.5 to 6 piping connection (Figure 8: before config.1)

8 Copyright 2016 by ASME


some of the excessive vibration in existing piping systems were
associated with loosely supporting conditions. Therefore, a
detailed piping support modeling ensures a precise estimation of
the system vibration parameters such as natural frequencies and
mode shapes. To obtain a realistic modal parameters, the
numerical simulation was calibrated utilizing an experimental
modal analysis (EMA). An operational modal analysis (Output-
Only) was performed utilizing MEScope software as shown in
Figure 13. A set of ODF-FRF measurements was constructed by
using the amplitude of the Auto Power Spectrum (APS) and the
phase of Cross Power Spectrum (CPS) [22]. Consequently the
FRFs were curve fitted to estimate the natural frequencies of the
system as listed in Table 4.

Reference Point
(Z-direction)

Figure 13 The MEscope model to perform OMA

Table 4 Measured natural frequencies


Modes of Measured natural
Vibration frequency (Hz)
Mode 1 6.21 Hz
Mode 2 7.76 Hz
Mode 3 11.89 Hz
Mode 4 14.82 Hz

Figure 12 RMS Velocity versus measurement locations Mode 5 16.67 Hz


along the piping system [5] Mode 6 19.73 Hz
4. Modal Analysis and Corrective Modifications Mode 7 22.23 Hz
Figure 8 shows a 3-D piping systems model. CAESAR II
Mode 8 25.31 Hz
software [13] was utilized to model and analysis the system. It
is very important to carefully model all details of the piping Mode 9 28.31 Hz
system particularly the support specifications. The support
direction, stiffness and the length of the piping spans may greatly Mode 10 30.49 Hz
affect the analysis result. The Sukaih study [23] indicated that

9 Copyright 2016 by ASME


In this study, the dominant frequencies of 6.25 Hz, 11.88 Hz and mechanisms were investigated including two-phase flow
25-30 Hz were measured in the system frequency response. classifications, turbulence flow intensity, vortex-shedding
Furthermore, the likely excitation frequencies were classified to frequency, and sound level intensity for acoustic induced
find a correlation between the measure frequencies and the excitation. The vibration reading results indicated a strong
possible source of excitation frequencies. This classification correlation between the dominant excitation frequencies and the
categorized the aforementioned dominant frequencies as the calculated vortex-shedding frequencies as the likely source of
flow-induced excitation category. Therefore, the vortex- vibration. Furthermore, an assessment procedure was adopted to
shedding frequencies were calculated at a tee connection, a mitigate the excessive vibration in the piping system. This
reducer, and a dual elbow with frequencies of 6.8 Hz, 23.8 Hz procedure includes a step-wise flowchart to measure and
and 11.9 Hz, respectively. The modal analysis of the piping evaluate the level of vibration as well as further numerical
system also indicated that the 1st, 3rd and 7th natural frequencies analyses to implement corrective actions [5].
were located near the calculated vortex-shedding frequencies.
This situation may lead to the existing excessive vibration in the A piping system, operating in an industrial facility, was chosen
system [5]. for a case study. Experimental and numerical modal analyses
were conducted to identify the likelihood excitation mechanisms
To reduce this level of vibration, two strategies should be and adopt the proper corrective actions to eliminate the source of
adopted: (1) Elimination of the source of vibration, (2) vibration and reduce the level of vibration.
Separation between the excitation frequencies and the systems
natural frequencies by a minimum of twenty percent as per the
Energy Institute guidelines [3]. NOMENCLATURE

Figure 14 shows the corrective actions based on the f Vortex-shedding frequency [Hz]
aforementioned strategies. The tee-connection and the reducer, St Strouhal number
associated with the dominant measured excitation frequencies, U Flow mean velocity [in/sec]
were replaced by a pipe with a larger diameter. This modification D Characteristic length [in]
will decrease the initiated vortex-shedding frequency. On other tot Pressure resistant coefficient
hand, additional supports were incorporated into the model to Flow density [lbs/in 3]
increase the natural frequencies of the system and ensure a Void Fraction
twenty percent separation between the excitation frequencies and VSL Superficial liquid flow velocity [in/sec]
the systems natural frequencies. As shown in Figure 13, these VSG Superficial gas flow velocity [in/sec]
support modifications consisted of adding three additional UL Liquid mean velocity [in/sec]
supports at the locations 1, 2 and 3, fixed in the X and Z UG Gas mean velocity [in/sec]
directions, as well as anchoring and fixing the existing support Lw Sound power level [dB]
at the location 4. P1 Upstream pressure [psi]
P2 Downstream pressure [psi]
T Temperature [F]
M Mass flow rate [lbs/sec]

REFERENCES
1. Bruce, R.D., A.S. Bommer, and T.E. LePage, Solving
acoustic-induced vibration problems in the design
stage. Sound Vib, 2013: p. 8-11.
2. Nakamura, T., et al., Flow-induced vibrations:
Classifications and lessons from practical experiences.
2013: Butterworth-Heinemann.
3. EnergyInstitute(EI), Guidelines for the Avoidance of
Vibration Induced Fatigue Failure in Process
Pipework. 2008: London.
Figure 14 Piping system highlighted corrective modifications 4. Azizian, R. and N. Mureithi. A Hybrid Friction Model
for Dynamic Modeling of Stick-Slip Behaviour. in
CONCLUSION ASME 2013 Pressure Vessels and Piping Conference.
In this study, likely excitation mechanisms in a piping system 2013. American Society of Mechanical Engineers.
transmitting fluid were discussed such as flow-induced vibration 5. Azizian, R. and P. Torrado, Insights Into Fixed
(FIV), acoustic-induced vibration (AIV), and pressure pulsation. Equipment Vibration How a Piping System Was
Different parameters which can quantify the excitation

10 Copyright 2016 by ASME


Affected by Flow-Induced Vibration. Inspectioneering, 23. Sukaih, N., A practical, systematic and structured
2015. 21(6). approach to piping vibration assessment. International
6. Olson, D.E., Pipe vibration testing and analysis. journal of pressure vessels and piping, 2002. 79(8): p.
Companion guide to the ASME boiler & pressure 597-609.
vessel code (Vol. Chapter 37). New York, NY: ASME,
2002.
7. Blevins, R.D., Flow-induced vibration. 1990.
8. Azizian, R., Dynamic Modeling of Tube-Support
Interaction in Heat Exchangers. 2012, cole
Polytechnique de Montral.
9. Azizian, R. and N. Mureithi, Numerical Analysis of
Fretting-Wear With a Hybrid Elastoplastic Friction
Model. Journal of Pressure Vessel Technology, 2014.
136(3): p. 031303.
10. Azizian, R. and N. Mureithi. Numerical Analysis of
Intermittent Stick-Slip Behaviour of Tube-Support
Interaction in Heat-Exchangers. in ASME 2012
Pressure Vessels and Piping Conference. 2012.
American Society of Mechanical Engineers.
11. Azizian, R., N. Mureithi, and T. Sawadogo. Dynamic
modeling of heat exchanger tube-to-support
Interaction. in 6th CNS International Steam Generator
Conference, Toronto, Canada, Nov. 2009.
12. Azizian, R. and N. Mureithi, A Simple Empirical Model
for TubeSupport Normal Impact Interaction. Journal
of Pressure Vessel Technology, 2014. 136(5): p.
051303.
13. CEASAR II, PAULIN Reseach Group. 2014: Richmond
Ave., Houson, Tx.
14. Moussou, P., et al. Industrial cases of FSI due to
internal flows. in Proc. of the 9th Int. Conf. on Pressure
Surges. 2004.
15. Shiraishi, T., et al., Resistance and fluctuating pressures
of a large elbow in high Reynolds numbers. Journal of
fluids engineering, 2006. 128(5): p. 1063-1073.
16. Weisman, J. and S. Kang, Flow pattern transitions in
vertical and upwardly inclined lines. International
Journal of Multiphase Flow, 1981. 7(3): p. 271-291.
17. ABAQUS, Dassault Systemes. 6.13-1(2014): 166 valey
St., Providence, RI.
18. Carucci, V. and R. Mueller. Acoustically induced piping
vibration in high-capacity pressure reducing systems. in
Mechanical Engineering. 1983. ASME-AMER SOC
MECHANICAL ENG 345 E 47TH ST, NEW YORK,
NY 10017.
19. Eisinger, F., Designing piping systems against
acoustically induced structural fatigue. Journal of
Pressure vessel technology, 1997. 119(3): p. 379-383.
20. HealthandSaftetyExecutive, Transient Vibration
guidelines for fast acting valves screening assessment.
2002: UK.
21. Rainieri, C. and G. Fabbrocino, Operational modal
analysis of civil engineering structures. 2014: Springer.
22. Schwarz, B. and M. Richardson, Post-processing
ambient and forced response bridge data to obtain
modal parameters. Proceedings of IMAC-XIX, 2001.

11 Copyright 2016 by ASME

S-ar putea să vă placă și