1. Number of barrels =2
2. Size of barrel =3 m 2.5 m
3. Bank level =254 m
4. Drain H.F.L =253.25 m
5. Uplift at base of barrel =4.5 t/m2
6. Unit weight of dry earth =1.6 t/m3
7. Unit weight of saturated earth =2.0 t/m3
8. Weight of submerged earth =1.0 t/m3
9. Angle of internal friction in all =30
conditions
Design
Assume the thickness of the frame 30 cm all through so that the effective length of horizontal
and vertical members are 3.3 m and 2.8 m.
1
Hydraulic Structures Structural Design of Syphon
1. Distribution factors
At joint A For A B,
2.8
For AB 0.46 For A D,
2.8 3.3
Therefore, distribution factors:
3.3
For AD 0.54
2.8 3.3 For
At joint D
For D A=0.54
D C=0.46
2. Dead loads
Weight of barrels per meter of length 4 3.3 3 2.8 0.3 2.4 15.6t m
Total dead load/m of length of barrels 15.6 4.9 6.9 49.4t m
2
Hydraulic Structures Structural Design of Syphon
3. Earth pressure
a. Dry earth pressure above saturation line (from R.L. 253.25 m to R.L. 254.00 m)
b. Saturated earth pressure (from R.L. 253.25 m to R.L. 248.45 m).
1 sin 1
Corresponding to 30 , c p
1 sin 3
4. Fixing moments
w 2 5.62 3.32
a. On span AB 5.1t m
12 12
6.5 3.32
b. On span CD 5.9 t m
12
c. On span AD
3.07 2.82 3.73 2.82
M AD 2.985t m
12 30
3.07 2.82 3.73 2.82
M DA 3.475t m
12 20
3
Hydraulic Structures Structural Design of Syphon
Joint C D A B
Member CD DC DA AD AB BA
D. factor 0.46 0.54 0.54 0.46
F.E.M. -5.9 +5.9 -3.475 +2.985 -5.1 +5.1
Balance -1.115 -1.31 +1.142 +0.973
C.O. -0.5575 +0.57 -0.655 +0.485
Balance -0.2622 -0.3078 +0.3537 +0.3013
C.O. -0.1311 +0.177 -0.1539 +0.151
Balance -0.081 -0.096 +0.083 +0.0708
C.O. -0.041 +0.042 -0.048 +0.035
Balance -0.019 -0.023 +0.026 +0.022
-6.630 +4.423 -4.423 +3.733 -3.733 +5.771
5. Design moments
a. Span AB
Net moments at center and face of span AB
5.62 3.3 5.62 0.152
Sagging moment at face 0.15 1.33t m
2 2
3.15
Fixing moment at face 3.73 5.771 3.73 5.68t m
3.3
Net fixing moments at face 5.68 1.33 4.35t m
5.62 3.32
Sagging moment at center 7.65t m
8
3.73 5.771
Fixing moment at center 4.75t m
2
Net sagging moment at center 7.65 4.75 2.9t m
b. Span CD
6.5 3.3 6.5 0.152
Sagging moment at face 0.15 1.54 t m
2 2
3.15
Fixing moment at face 4.423 6.63 4.423 6.529 t m
3.3
Net fixing moment at face 6.529 1.54 4.98t m
4
Hydraulic Structures Structural Design of Syphon
6.5 3.32
Sagging moment at center 8.85t m
8
6.63 4.423
Fixing moment at center 5.53t m
2
Net sagging moments at center 8.85 5.53 3.32t m
c. Span AD
5
Hydraulic Structures Structural Design of Syphon
Span Fixing moment (-ve) at face (t.m) Sagging moment (+ve) at center (t.m)
AB 4.35 2.9
16 mm bars@ 12.5cm c/c (up) 12 mm bars@ 10 cm c/c (down)
CD 4.98 3.32
16 mm bars@ 11.25cm c/c 16 mm bars@ 16.25cm c/c
AD 3.3 0.76
16 mm bars@ 16.25cm c/c 12 mm bars@ 25cm c/c
6. Thickness of members
Maximum moment in the barrels=4.98 t.m
The minimum effective thickness (d) required for bending moment is
M
d
bQ
4.98 1000 100
23.29 cm
100 9.18
Adopt 27.5 cm effective depth and 30 cm overall thickness for all members.
7. Reinforcement
a. Span AB and BE
At face (hogging moment, -ve steel)
4.35 1000 100
At 15.38cm 2
6
1200 27.5
7
Provide 16 mm bars @ 12.5 cm c/c (up)
At center (sagging moment, +ve steel)
2.9 1000 100
At 10.25cm 2
6
1200 27.5
7
Provide 12 mm bars @ 10 cm c/c (down)
b. Span CD and CF
At face
4.98 1000 100
At 17.6 cm 2
6
1200 27.5
7
Provide 16 mm bars @ 11.25 cm c/c
At center
3.32 1000 100
At 11.74 cm 2
6
1200 27.5
7
Provide 16 mm bars @ 16.25 cm c/c
c. Span AD and EF
6
Hydraulic Structures Structural Design of Syphon
At face
3.3 1000 100
At 11.7 cm 2
6
1200 27.5
7
Provide 16 mm bars @ 16.25 cm c/c
At center
0.764 1000 100
At 2.70 cm 2
6
1200 27.5
7
Provide 12 mm bars @ 25 cm c/c
4
12 1.13
14 1.54
16 2.01
18 2.54