Sunteți pe pagina 1din 13

AC-UPS Product Line

Overview configurations Gutor UPS product line

Dual UPS Dual UPS


Function Single UPS Par. Red. UPS
Independent Synchronised
Upstream supply 1 - 2 feeders 1 - 3 feeders 1 - 4 feeders 1 - 3 feeders
Bypass Single Single Dual Single
Parallel
UPS Single Dual-Indp. Dual-Synch.
Redundant
Battery Single Redundant Dual Dual
UPS - Dist. (A/B) Single Single Dual Dual
Cabling Single Single Dual Dual
Downstream Dist. Single Single Dual Dual
C Distribution N/A N/A N/A STS - C. Dist.
Loads Single Single Dual Dual/Single
Maintenance On Bypass UPS power UPS power UPS power

Confidential Property of Schneider Electric | Page 1

UPS configuration
Basic units | All in one industrial solution UPS versus modular UPS

Confidential Property of Schneider Electric | Page 2


All in one Solution UPS

Bypass section including 3 Pos. Manual Bypass Switch


Bypass
Input

Basic UPS SSW. Byp.

Secured Load Bus


Rectifier Inverter SSW. Inv.
Rectifier
Input

Battery Bank

Basic UPS with 100% galvanic isolation ( ) and bypass section.


The basic UPS configuration will be used in all Gutor AC-UPS solutions.
Confidential Property of Schneider Electric | Page 3

All in one Industrial Solution UPS versus Modular UPS


All in one industrial solution Modular solution
Bypass mains

SSW

All parts included in monitoring and


regulation circuit
Rec. mains

EN SSW

Output
EA

Aux. charger
for battery SSW
back-up time
>30min
3-Position Manual Bypass Switch can be included
in the industrial solution.
For the modular solution, it will typically be an external
2-Position Manual Bypass Switch. Integrated part of modular UPS solution, parts outside this box
are typically not included in monitoring and regulation
and could come from different suppliers.

Confidential Property of Schneider Electric | Page 4


All in one Industrial Solution UPS versus Modular UPS
Topics All in one Industrial Solution Modular UPS
UPS
Applications/Industries Oil & Gas, Nuclear Power, Power Datacenters, banks, healthcare,
Generation, Chemical, Mining, telecom, hospital, airport,
Transport, other industrial processes semiconductor

UPS Function Prevent loss of control over critical Prevent data loss and costly
processes, often involving human server shutdowns
safety Provide continuous operation of
mission critical facilities
Electrical Environment Unstable, dirty electrical supply Stable and clean electrical
(transients, surges, distortions), supply (voltage, frequency,
electro-magnetic interference waveform)
little electro-magnetic
interference
Ambient conditions Wide ranges in temperature Regulated temperature
(-10 - 55C/14 - 131F) (20 - 30C/68 - 86F)
Humidity: (0-95%) Humidity
Vibrations (seismic, shock) (10-55% non condensing)
Presence of dust, gases, etc Little or no vibration, dust,
gases

Confidential Property of Schneider Electric | Page 5

All in one Industrial Solution UPS versus Modular UPS

Topics All in one Industrial Solution Modular UPS


UPS
Flexibility and customisation Each system engineered Typically not required
according to customer needs (off the shelf)
Project management approach Limited selection of options may
Full customisation, including be offered
testing and documentation

Lifetime and services Lifetime 20-30 years Lifetime of 5-10 years


Comprehensive service program (depending on market segment)
during lifetime, including spare Retrofit rarely done
parts and maintenance Life cycle monitoring program

Confidential Property of Schneider Electric | Page 6


All in one Industrial Solution UPS versus Modular UPS
Topics All in one Industrial Solution Modular UPS
UPS
Galvanic isolation Standard option as integrated part Standard no galvanic isolation.
of system External transformers can be
added, but not included in
monitoring/regulation =>
Output tolerance +/- 3%
Batteries Different types of batteries used, Generally sealed lead-acid
including NiCd as well as both technology
sealed (valve regulated) and vented Batteries are standardised
lead-acid batteries Battery charging may not be
Battery choice tailored to customer temperature-adapted
specifications
Battery charging adapted to
temperature - increases battery
lifetime
Battery back-up >30min. Internal oversized rectifier to reduce Not designed for long battery
recharge time back-up time => Long recharge
time or additional external
charger will added, not
included in overall HMI

Confidential Property of Schneider Electric | Page 7

All in one Industrial Solution UPS versus Modular UPS


Topics All in one Industrial Modular UPS
Solution UPS
DC earth fault Standard option as integrated part Typical not included even not as
of the system option.
Static transfer switch 100 % rated static transfer switch Integrated in each module
in inverter as well as in bypass contactor in inverter output and
static in bypass.
Cooling N+1 fans with internal RPM No redundant fans, typically with
monitoring, as option 100% out internal RPM monitoring.
redundant fans Redundancy secured by adding
one module

HMI Monitoring of all main component Individual HMI on each module (all
included in the centralised HMI additional compon-ents are not
included in HMI)

Single phase output Standard solution Not available above 10KVA


May be realised by adding a
transformer between two phases

Confidential Property of Schneider Electric | Page 8


UPS solutions in detail
AC and DC

Confidential Property of Schneider Electric | Page 9

UPS solutions in detail

UPS technology all in one solution UPS


DC UPS systems
Single
Parallel Redundant
Dual
Detailed Single Line Wiring Diagram

AC UPS systems
Single
Parallel Redundant
Dual Independent
Dual Synchronised
Detailed Single Line Wiring Diagram

Construction Details

Confidential Property of Schneider Electric | Page 10


AC-UPS Product Line
DC Single UPS Configuration

Confidential Property of Schneider Electric | Page 11

AC-UPS Product Line


DC Parallel Redundant UPS Configuration

Confidential Property of Schneider Electric | Page 12


AC-UPS Product Line
DC Dual Independent UPS Configuration

Confidential Property of Schneider Electric | Page 13

AC-UPS Product Line


DC detailed Single Line Wiring
Q004
Rectifier X002
B+, B-

A030
T001 L001 V015 Q003
X001 Q001 F026 X004

Mains Load
L1, L2, L3 L+, L-
PE

U I IDC + UDC IBatt


CB02
A003 A002 Rectifier A004 A005
RFI /
Fuse
Fuse Isolation Fuse Fuse

Transformer
E001...
Fan
Control
A050... Speed monitored heavy duty fans

PSU AC
A071 INTERFACE / PSU PSU DC

Redundant internal Power Supplies


A070 CCU (Charger Control unit)
A025 A077 A073
EXTERNAL RELAY FRONT PANEL = Option
CONNECTION BOARD BOARD LCD
OPERATING
STATUS LED ALARM
DISPLAY OPERATION
INDICATION

Confidential Property of Schneider Electric | Page 14


AC-UPS Product Line
AC Single UPS Configuration

Double Conversion UPS System with PWM Inverter

Confidential Property of Schneider Electric | Page 15

AC-UPS Product Line


AC Parallel Redundant UPS Configuration

Confidential Property of Schneider Electric | Page 16


AC-UPS Product Line
Features & Benefits - Parallel / Redundant System

Features Benefits
No master/slave system All systems can work as masters. Possible to switch individual units
OFF for service.

Bus system for Two control cables between each unit


communication

Priority control The system will stay in the highest possible operational mode. The
system will save battery capacity as long as enough energy can be
taken from the mains.
Active load sharing Each unit takes the same percentage of the actual load

Up to nine units can be For redundancy or power increase


switched in parallel

Masterlogic for parallel Disabling of parallel communication if one unit is disconnected /


coordination coupling switch open

Independent batteries for Avoids the danger of a single battery acting as a common failure point
each unit

Confidential Property of Schneider Electric | Page 17

AC-UPS Product Line


AC Dual Independent UPS Configuration

Confidential Property of Schneider Electric | Page 18


AC-UPS Product Line
AC Dual Synchronized UPS Configuration

Confidential Property of Schneider Electric | Page 19

AC-UPS Product Line


AC System with Stand-alone Inverter Configuration

Confidential Property of Schneider Electric | Page 20


AC-UPS Product Line
AC detailed Single Line Wiring Diagram

Bypass Isola- Battery Choke


tion Trans- Inverter
former

Static
Switch

Rectifier
Isolation Rectifier Inverter
Transformer Isolation
Transformer

Confidential Property of Schneider Electric | Page 21

AC-UPS Product Line


AC detailed Single Line Wiring Diagram
Segregated Bypass Panel

Manual 3 Position Bypass Switch

Redundant internal Power Supplies

Speed monitored heavy duty fans

Confidential Property of Schneider Electric | Page 22


AC-UPS Product Line
Constructional Details

Control electronis on hinged panel


Direct access to all power modules
Individual component identification
Fan replacement with system on
Halogen free wiring and components
Fully segregated manual bypass section
Segregated incomer section

Confidential Property of Schneider Electric | Page 23

Questions?

Confidential Property of Schneider Electric | Page 24


THANK YOU.

Confidential Property of Schneider Electric | Page 25

S-ar putea să vă placă și