Sunteți pe pagina 1din 2

Design of Trombone Cooler for Gasses

Temperatures

Hot Fluid Cold Fluid Differences


Highest Temp 200 C 80 C 120 C
Lowest Temp 100 C 30 C 70 C
Difference 100 C 50 C 50 C

12070
LMTD=
120
( )
ln
70
= 90 C

100 50
R= 50 =2 S= 170 = 0.3

From graph we find value of Ft


Ft = 0.95 Corrected LMTD = 86 C

Heat duty to be removed =Q = 3.5 x 105 Kj/Hr Mass flow rate of water required =
5
3.510
4.1986 = 1670 Kj/Hr

Hot Fluid at Tube Side


Taking 3-inch pipe of schedule 40

At = 0.00476 m^2 L = 2.4 m

Internal Diameter = 0.077 m


Outer Diameter =0.089 m
G = 3643/0.0047 = 7.8x105 Kj/Hr
= 2 x 10^-5 Pa. s
Re = 5.8 x 105
From graph
Jh = 0.003
K = 160
By using equation
Hi = 0.13
Hio = 0.13*0.077/0.089 = 0.112

Shell Side Calculations


G = 1670/2*2.4 = 348
Taverage = 55 C
= 0.00102 Kg/ms
Re = 4G/ = 6 x 10 ^ 6
From equation

Ho = 1020
Uc = 1020*0.112/(1020+0.112)= 102

Heat Transfer Area = Q/U Tlmtd


A = 38 m2
Number of Tubes Required
A/AtL = 38/ 0.716 = 53 tubes

S-ar putea să vă placă și