1.83 m 1.34 m
1.34 m 1.5 m
2.25 m
2.3 m 3.4 m 2.3 m
2.25 m
B 2.25 m
2.25 m
C2
Floor Area : 29 m2
Sprinkler spacing (maximum) : 4.6 m
Sprinkler spacing (minimum) : 1.83 m
Protection Area : 20.9 m2
CALCULATION SHEET
FIRE WATER DEMAND
2m 2.3 m
2m 2m
C 2.3 m
2m
2m
2m
B
2m
A
C2
Sprinkler distance along the wall (maximum) (S) : 1.83 m
Sprinkler distance across the room (maximum) (L) : 2 m
Protection area of coverage per sprinkler (As) : 14.64 m2
Density / Application Rate : 4.10 L/min/m2
Minimum Flow per Sprinkler (Q) : 60.024 L/min
K-Factor : 80.6 L/min/bar1/2
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 0.6 bar
Sprinkler Quantity : 2
Total Flow : 120 L/min
4. SUMMARY
Scenario 1: Lab 1st Floor on fire
Sprinkler system Lab 1st floor : 0 L/min
Pillar Hydrant WH-06 : 946 L/min
Total Fire Water Requirement 946.353 L/min