1 Introduction

Training

2 Project Administration /
Exercises
DIGSI 4

Power System Protection 3


Function Device Parameterization

CFC / Display / Control


4 CFC-Exercises

5 CFC-Function Modules

6 Commissioning and Test


Functions

Settings of Communication
7 interfaces

8 Process Data Analysis

Siemens Power Academy 10


Siemens AG
Siemens Power Academy

Dr. M.R. Ganjavi


PTD SE PTI NC Erlangen
Tel: +49 9131 733854
Fax: +49 9131 735017
Mohammad-reza.ganjavi@siemens.com

01_A0: Introduction
Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - History
PC-Operating- DIGSI DIGSI Delivery
System Symbol Version

DOS V2 1991
Windows 3.x
Windows 95 V3.3 1998
Win. NT 4.0
OS/2 Warp

Windows 95 V4.0 1999


Win. NT 4.0
Windows 98/2000/ME/XP
neu: Windows Vista
-Professional V4.8 2008
01_A0: Introduction
Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Targets of DIGSI 4 Basic Course

Using DIGSI 4 efficiently

Using the DIGSI 4 Project Manager in an


optimal way
Proceeding how to do the settings

Interpretation of trip logs

Evaluation of fault records

Engineering of CFC-charts, change of the


I/O-Configuration matrix
To know the opportunities of the default
display editor

01_A0: Introduction
Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Training configuration in DIGSI 4 training course

Instructor

6 x 7SJ63x

SIPROTEC SIPROTEC SIPROTEC SIPROTEC SIPROTEC SIPROTEC


7SC64-0000-ABC
7SC64-0000-ABC 7SC64-0000-ABC 7SC64-0000-ABC 7SC64-0000-ABC 7SC64-0000-ABC
RU N ERROR
RU N ERROR RU N ERROR RU N ERROR RU N ERROR RU N ERROR

M EN U
M EN U M EN U M EN U M EN U M EN U

LED C T RL ES C E N TE R E N TE R E N TE R E N TE R E N TE R E N TE R
LED CT RL ES C LED C T RL ES C LED C T RL ES C LED C T RL ES C LED C T RL ES C

Lo c a l F1 7 8 9 Lo c a l F1 Lo c a l F1 Lo c a l F1 Lo c a l F1 Lo c a l F1
7 8 9 7 8 9 7 8 9 7 8 9 7 8 9

Rem ote F2 4 5 6 Re m o t e F2 4 5 6 Rem ote F2 4 5 6 Rem ote F2 4 5 6 Rem ote F2 4 5 6 Rem ote F2 4 5 6

F3 1 2 3 F3 F3 F3 F3 F3
Te s t 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
Tes t Te s t Te s t Te s t Te s t

F4 . 0 +/- F4 F4 F4 F4 F4
No rm a l . 0 +/- . 0 +/- . 0 +/- . 0 +/- . 0 +/-
No r m a l No rm a l No rm a l No rm a l No rm a l

1 2 3 4 5 6

01_A0: Introduction
Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

The modular Programm of DIGSI 4

DIGSI 4
Basic - Programm
Project and Device-Manager
- Supports device templates-

Scope of Operation & Commissioning, IEC, Visualization of


functionality Control Test Mode PROFIBUS, fault records
Engineering MODBUS,
I/O-Matrix DNP, ...

Additional programms
Display Editor to create and SIGRA to visualize and Graphic-Tools
edit the default and control evaluate fault records trip characteristics
displays Impedance diagrams

DIGSI Remote
SIMATIC CFC 4
central- remote operation
Logic editor
using modems

01_A0: Introduction
Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Versions of DIGSI 4
Order-Code.
DIGSI 4 Variants
Basic 7XS5400-0AA00
with License for up to 10 PCs
7XS5402-0AA00
Professional
Complete version with all options
incl. SIGRA and Remote
7XS5405-0AA00
Basis Upgrade DIGSI 3->4
7XS5406-0AA00
Professional Upgrade DIGSI 3->4

01_A0: Introduction
Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Versions of DIGSI 4
Variants Order-Code.

SIGRA 4 7XS5410-0AA00
Evaluation of fault records
Option for DIGSI 4

DIGSI 4 Remote 7XS5440-0AA00


Software for remote operation
Option for DIGSI 4

DIGSI 4 Demo 7XS5401-0AA00


Multimedia presentation

01_A0: Introduction
Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

PC- Hardware-Requirements for DIGSI 4

Minimum PC-requirements Recommended PC-HW

Pentium with 800 MHz


Pentium 1,6 GHz
128 MB RAM
700 MB on harddisk 256 MB RAM
700MB on harddisk
1 serial Port
1 serial Port
CD-ROM drive
Win95 or Win 98
CD-ROM drive
WIN NT4.0, Win 2000/ME/XP-Prof.
Explorer 6.0
Win 95 or Win 98
WIN NT4.0, Win 2000/ME/XP-Professional
Explorer 6.0
01_A0: Introduction
Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 operating program

Configuration matrix Parameterization

Change relay display

Test Fault
evaluation

Logic Editor

01_A0: Introduction
Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - The manager that keeps order

Easy management of relays in projects


Selection of relays from a catalog
Archiving, export, and import
Variation management
Plug and play
Reading out process data with single-
keystroke operation
Work like in MS Windows Explorer
Any station topologies
Same platform as for SICAM Substation
Automation System

01_A0: Introduction
Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - A single DIGSI for every version of every relay

Uniqu
e !!!

01_A0: Introduction
Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - The function tree with a pivotal function

Function tree has a pivotal


function in operation
"What you see is what you
need
Graphic visualization of the
tripping characteristic
Comparison of parameters
Structured tab card dialogs
01_A0: Introduction
Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - The allocation matrix, a clear overview

Routing of indications,
measured/metered values,
commands to
inputs/outputs, LEDs, CFC,
buffers, system interface,
feeder control diagram
Matrix instead of nested
operating sequences
Popup menus provide the
options
Overview using filter,
hiding/showing

Version: B 5_Page 13
No incorrect
01_A0: input possible
Introduction
Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Test functions, decisive for commissioning

Testing and diagnostic functions


Quick and problem-free testing of
wiring
Output of indications via the system
interface
Opening and closing of relays
...

01_A0: Introduction
Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Fault analysis with SIGRA


Time-signal curves, circle
diagrams, vector
diagrams, barcharts
Calculation of positive-
sequence impedances,
rms values, symmetrical
components, vectors,
and much more
Quick and easy
measurement using two
cursors
Adding further fault
recordings (e.g. from the
remote end of a line)
Synchronization of fault
recordings
Also for fault recordings
of relays from other
manufacturers
01_A0: Introduction
Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Programming SIPROTEC with CFC

PLC integrated into the SIPROTEC 4 relays


Fully graphic, no progamming skills required
Libraries with standard blocks
Dragging blocks from the catalog into the chart,
then linking with a mouse click
Connecting block inputs and outputs with
information items (measured values,
indications, circuit breaker positions, ...)
Consistency check with guarantee of
effectiveness of the protection
01_A0: Introduction
Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Typical CFC applications

Extension of the release condition for a switching command


(e.g. by the position of a further disconnector and the information item "spring charged")
Display of an application-specific group indication in an LED
(single indications logically combined with operators, such as AND, OR, NOT)
Display of a new dynamic symbol for an item of equipment in the
display
(various states calculated by the CFC logic)
Switchover of the parameter group
(on phase currents dropping below a limit value)
Blinking alarm LED if the switching authority is set to "LOCAL"
Implementation of a protection function not offered in the relay
(e.g. "Reverse power protection" or "Efficiency monitoring")
Forced sequence switching after pressing a function key on the
relay
(e.g. automatic grounding)
Step-by-step load shedding on power deficit
(calculation of suitable feeders by the CFC logic)
...
01_A0: Introduction
Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Adapting the relay display with the


Display Editor

Changing the basic displays and feeder


control diagrams preconfigured in the
factory
Operation like with a conventional
image editor
Libraries with static and dynamic
symbols, including user symbols
Linking of the dynamic symbol with the
associated item of equipment,
measured value, ...
Typical diagrams can be stored as
templates

01_A0: Introduction
Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Station configuration for busbar protection

Busbar protection 7SS52 now also


operable with DIGSI 4 (V4.30)
Operation like the Display Editor
Libraries with static and dynamic
symbols, including user symbols
Linking of dynamic symbols with the
associated item of equipment,
measured value, ...
Typical diagrams can be stored as
templates
On-line visualization (HMI)
01_A0: Introduction
Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - Some advantages

1 program
for all tasks

1 program
for all relays

User
friendly

Standardized
over the bay and
station control levels

01_A0: Introduction
Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI - Requirements

Minimum PC requirements Recommended PC hardware

Pentium from 800 MHz Pentium from 1,6GHz

256 MB RAM
128 MB RAM

700 MB memory space on


700 MB memory space on harddisk
harddisk
1 serial port
1 serial port CD-ROM drive

CD-ROM drive MS Windows 95/98/ME


NT4/2000/XP Prof.
MS Windows 95/98/ME
NT4/2000/XP Prof.

01_A0: Introduction
Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI - Order structure

Product description Variant Order No.

DIGSI 4 Basic 7XS5400 - 0 AA00


Software for configuring and With license for 10 computers
operating protection units from On CD-ROM
SIEMENS Authorization by license number
MS Windows program, executable Demo 7XS5401 - 0 AA00
under MS Windows NT 4 / 95 / 98 / Multimedia presentation with operating
2000 / ME videos for demonstration and training
Incl. device templates, In addition: Demo version of
Comtrade Viewer, characteristic DIGSI 4 Basic (without communication
visualization, with unit)
manual in electronic form On CD-ROM and on Demo-CD-ROM
Professional 7XS5402 - 0 AA00
Complete version: Basic and all optional
packages
On CD-ROM
Authorization by license number
Basic Upgrade 7XS5405 - 0 AA00
Contains the packages Basic and
SIGRA.
Full version with license for 10
computers
For licensed users of previous versions
On CD-ROM
Authorization by license number
Professional Upgrade 7XS5406 - 0 AA00
Complete version: Basic and all optional
packages
With a license for 10 computers
For licensed users of previous versions
On CD-ROM

01_A0: Introduction
Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI - We support you


Demo programs (on CD-ROM)
DIGSI 4 DEMO
SIGRA 4 TRIAL & DEMO
Training
www.siemens.com/power-academy-td
In German and English, in Nuremberg,
but also "locally" anywhere in the world
Energy Customer Support Center
www.siprotec.com in Service or Contact tab
Phone: +49 1805 247 000
eMail: support.energy@siemens.com
FAQ: www.siemens.com/energy-support
Newsletter
www.siprotec.com in Software/DIGSI4 tab
3-4 times a year: information about products,
hints & tricks, solutions, coming training dates
Internet
www.digsi.com
Soon: On-line forms for product registration, hotline
queries, software order configuration as a service
01_A0: Introduction
Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 System and Device Management

Installing DIGSI 4

Managing Projects

Working with the Devices

Optimizing Parameterization

02_A0: Project Administration


Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Install - Uninstall


Installation from CD Rom:
ADMINISTRATOR-rights are required

DIGSI 4 components

device drivers for SIPROTEC 4

Sequence:
start Windows
Insert CD ROM - Autostart of Installation

insert licence number of product card

selection of components

Deinstallation:
via system settings remove Software...
(only that procedure will delete the entries in the registry-file)

02_A0: Project Administration


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - The Structure of Projects in the DIGSI 4


Manager

System component hierarchy at your convenience

Project
System
Station
Feeder
Device
Modems
Phone Book

02_A0: Project Administration


Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - New Project

Select the corresponding


dialog box
Enter project name
Define storage location

02_A0: Project Administration


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Folders

Basic structure

Folders can contain the following objects

Further folders
SIPROTEC 4 devices
V3/V2 devices
SIPROTEC 4 versions
Modem connections

02_A0: Project Administration


Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Project Structure

02_A0: Project Administration


Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise:
Create & structure project - Part I

Create a new project (Project 1).

Insert the folders (hierarchy levels) like in


the shown structure with the according
names.

02_A0: Project Administration


Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Insert Device

Open device catalog


Select device
Drag & Drop the device in
the project structure

02_A0: Project Administration


Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Specification

Properties

02_A0: Project Administration


Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise:
Create & structure project - Part II

Insert the following SIPROTEC 4 relays:

Region North:
Relay on the table
Substation 1: 7SJ610 V4.4
Feeder 1: 7SJ622 V4.6
Feeder 2: 7SJ631 V4.6
Modem connection

02_A0: Project Administration


Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Administrate V2/V3 Device

In DIGSI 4 Manager
SIPROTEC relays of
recent releases (V2,
V3) can be
administrated:
Before inserting
they have to be
generated in DIGSI V3.

02_A0: Project Administration


Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Administration of V3-Projects

In DIGSI 4 Manager projects of recent releases (V3 DIGSI-projects) can be


administrated:
Before inserting they have to be generated in DIGSI V3.

02_A0: Project Administration


Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise:
Create & structure project - Part III

Insert an older relay into the folder


Feeder 6th Avenue.

02_A0: Project Administration


Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Object Properties

SIPROTEC 4
Device
properties

02_A0: Project Administration


Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Object properties of V2/V3 relays

V2/V3 Device
Properties

02_A0: Project Administration


Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Save Project / Close

Save project

Save as...

- with / without rearrangement


- define storage location
Save

Close project

02_A0: Project Administration


Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise: DIGSI 4 - Save / copy / delete

Create a new project (Project 2)


Copy the folder Substation 2 from the first project (Project 1) into the new
project.
Insert a new folder with the name 110 kV in the folder
substation 2.
Copy the folders Feeder 1 and Feeder 2 from the first project (Project 1).
Move the relay 7SJ631 V4.1 from Feeder 2 to Feeder 1
Delete the relay 7SJ622 in Feeder 2.
Insert a new relay of the type 7SJ610 V4.0.
Specificate the order number MLFB and look at the object properties.

02_A0: Project Administration


Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Open Projects

Menu item File Open


Automatic presetting
after Program start
(global default setting)
Latest edited projects
Hidden / moved

02_A0: Project Administration


Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Archiving / Retrieving of Projects

Project archiving - first steps

Make basic settings


- Select the archiving program of your choice
- Set folder to archiving / retrieving

Configuration of archiving program


- Archive beyond floppy disk
- Consistency check
- Overwriting of objects with identical names
- Automatic creation of archive path

02_A0: Project Administration


Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Archiving / Retrieving of Projects

Basic settings

Archiving
Retrieving

02_A0: Project Administration


Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Project Archiving

Project archiving

02_A0: Project Administration


Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Retrieving Projects

Retrieving projects

Select archive/source
Select a destination

02_A0: Project Administration


Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Delete / Reorganize Projects

Delete projects

individual
several

Reorganize projects

02_A0: Project Administration


Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise:
Archive/Delete/Retrieve

Archive the project Project 1 into the file system (C:\Floppy).


Delete the Project Project 1
Close the project Project 2 and reopen it.
Retrieve the archived project Project 1 from the file system.

02_A0: Project Administration


Version: B 5_Page 24 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Optimization and Parameterization

Use of functions beyond the projects:

Copy
Move
Model parameterization

for objects
Project
Folder
Device

02_A0: Project Administration


Version: B 5_Page 25 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Generate Copies/Variants

A selected relay can be copied:


Edit > Copy and Edit > Paste
The new relay comes up
Note: The new relay has a new internal address. Original and copy are
different.

For a selected relay a variant can be generated:


Edit > Create variant
The new relay variant comes up.
Note: The variant has the same address like the original relay. Original and
variant are not different!

02_A0: Project Administration


Version: B 5_Page 26 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Copy versus variant

A relay must be copied, when there are two or more


relays of the same type and the parameters should be
copied.
In this case the new relay must be initialized first (to
get a new internal address).
For a relay a variant must be created, when there are
multiple parameter settings are required for one relay.
The relay has to be initialized only once, because the
variants have all the same address.

02_A0: Project Administration


Version: B 5_Page 27 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device variants - Import and Export

Original: scheduled set Export


from the Project Department

Version: IBS set


from the Commissioning Department

Import

Version: operator set


from the Operations Department

02_A0: Project Administration


Version: B 5_Page 28 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device variants

A device variant is generated as follows

Generate a variant of an existing


SIPROTEC 4 device

Import device data

Plug & Play connection to a


SIPROTEC 4 device

02_A0: Project Administration


Version: B 5_Page 29 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Export Device Data

Open dialog box


Define destination
Start exporting procedure

02_A0: Project Administration


Version: B 5_Page 30 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Importing Device Data


Import device data as SIPROTEC 4 variant

Open dialog box


Select Import File
Start the import procedure

02_A0: Project Administration


Version: B 5_Page 31 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Importing Device Data


Import device data as SIPROTEC 4 device

Open dialog box


Select Import File
Start importing procedure

02_A0: Project Administration


Version: B 5_Page 32 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Working with variants

Create a new variant of your relay (in Region North): My relay 1. Change
one parameter.

Export the variant into the file system (Myrelay1.dex on C:\Floppy).

a) Import the exported file as a SIPROTEC 4 variant: My relay 2.

Change the parameterization of the original relay.

b) Import the exported file directly as SIPROTEC 4 device and replace the
original relay.

02_A0: Project Administration


Version: B 5_Page 33 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Parameterization and Configuration

Overview
Device parameterization and configuration in the Offline mode
Configuration of information
CFC logical functions
DIGSI 4 Editor for default and control display
Settings transfer to device
Settings change in the Offline mode
Save settings change in the Offline mode
Exercises

03_A0: Device Parameterization


Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Setting Block

Possible storage locations for a device setting block:

Data structure of the DIGSI 4 settings computer

Memory of the SIPROTEC 4 device

External storage medium (for ex. floppy disks)

03_A0: Device Parameterization


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device in the Offline Mode

Working with SIPROTEC 4


data in the Offline mode

03_A0: Device Parameterization


Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Settings

Open device
Open tree view
Select Settings

03_A0: Device Parameterization


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Configuration

Selecting the
device configuration

03_A0: Device Parameterization


Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Setting Groups

Editing

Display activated group

Switching

Copy

Reset

Export protection settings

03_A0: Device Parameterization


Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Setting Group Definition

Define Setting Group

03_A0: Device Parameterization


Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Changing Setting Group

Direct selection
in the DIGSI 4
Dialog
Binary input
Telegram
(IEC60870-5-103)

03_A0: Device Parameterization


Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Editing of Device Settings

Cross group
settings
defintion

03_A0: Device Parameterization


Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Editing System Data

Higher-level
device data
definition

03_A0: Device Parameterization


Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Defining Interfaces

Definition of the
PC Interface
Settings

03_A0: Device Parameterization


Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Time Synchronization

Setting of the
device time
synchronization

03_A0: Device Parameterization


Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Password Protection

Password
assignment

03_A0: Device Parameterization


Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Password Protection

Password

Definition
Change

03_A0: Device Parameterization


Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Password Protection

Password

Deactivation
Activation

03_A0: Device Parameterization


Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Password Protection

Reset all passwords

03_A0: Device Parameterization


Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Parameterization

Configuration of information

Configuration of CFC functions

Configuration of default and control displays (ASB)

03_A0: Device Parameterization


Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of Information

03_A0: Device Parameterization


Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of Information

Structure of the matrix

Information
Source
Destination

Information blocks
- general
- protection functions
- indications, measured values, statistics
- functional scope related
- user-defined

03_A0: Device Parameterization


Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of Information

Working with the matrix

Configuration

Insertion of information

Change of view
- expanding / collapsing of groups and columns

Filtering
- as to information
- as to type of configuration

03_A0: Device Parameterization


Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Object Properties

Single Point
Indication SP

03_A0: Device Parameterization


Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Graphical Display

Default display

- Not operator-controllable

- Indication of operational statuses, measured values, texts

Control display

- Release of switching operations

- Indication of operational statuses, measured values, texts

03_A0: Device Parameterization


Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Default and Control Display

03_A0: Device Parameterization


Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

CFC blocks to link information


- creating group indications
- defining interlocking checks

Configuration steps
- starting CFC
- inserting chart
- inserting module
- defining order of execution
- interconnecting blocks

03_A0: Device Parameterization


Version: B 5_Page 24 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

Starting of CFC

03_A0: Device Parameterization


Version: B 5_Page 25 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

03_A0: Device Parameterization


Version: B 5_Page 26 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

03_A0: Device Parameterization


Version: B 5_Page 27 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4

Load settings to the device

Change and save settings in the Online mode

03_A0: Device Parameterization


Version: B 5_Page 28 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - The Online Mode

Loading of the settings


Change of individual settings
Indications, measured values, retrieval of fault records
Device control

Execute test functions


Device reset and resume
Setting of clock and date

03_A0: Device Parameterization


Version: B 5_Page 29 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Interfaces

User interface
- DIGSI 4 direct connection

Service interface
- DIGSI 4 modem connection

System interface (e.g. IEC61850, PROFIBUS)


- connection to control center

03_A0: Device Parameterization


Version: B 5_Page 30 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Initialization

The online mode

03_A0: Device Parameterization


Version: B 5_Page 31 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Setting up of Device Connection

Open device
Parameterize connection

03_A0: Device Parameterization


Version: B 5_Page 32 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Saving Settings

hard disk DIGSI 4 SIPROTEC 4 device


computer

03_A0: Device Parameterization


Version: B 5_Page 33 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Information and Interfaces

Definition of Information
Device Information Model
Types of Information
Information Type: Annunciation
Information Type: Control without Feedback
Information Type: Control with Feedback
Information Type: Measurement & Power Meter

03_A0: Device Information and Interface


Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Definition of Information

An information is an event, value, or command that has meaning for device


and should be processed in the protection device and/or control system.
Example:
Information: Circuit breaker door position is closed
Value : CLOSED / OPEN
Example:
Information: Circuit breaker position
Value : ON / OFF / INTERMIDIATE / ERROR
Example:
Information: Indicate phase A current (IL1=) in primary value
Value : 250.0 A

03_A0: Device Information and Interface


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
DIGSI 4 - Device Information Model
Siemens Power Academy
(Configuration Matrix)
Output
Resources
Communication Resources

Front panel Interface (Port A, local service interface)


Binary Output #p
System Interface (Port B, system interface to substation control)
Service Interface (Port C , remote service interface DIGSI/Modem)
LED #q
Add. Serial Interfaces (Port D&E, Inter-Relay Interface )
e.g. RTD-Box, Remote differential or distance relays
CFC #r
SIPROTEC 4 device
Input Resources
Buffers #t
Binary Input #m
Display #s
Function Key #n
Control Menu
CFC #k (Controllable on the Display)
Information Xn

Source Information Destination


03_A0: Device Information and Interface
Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Information Model (Configuration Matrix)

03_A0: Device Information and Interface


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Information Model (Configuration Matrix)

03_A0: Device Information and Interface


Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Device Information Encoding


Single Point Information
Source (One bit encoded information) Destination

U-
Bit n
U+ Bit n meaning
Logic 1: Active High
(on voltage presence) Logic 0 OFF / Open
Logic 1 ON / Close
Logic 1: Active Low
(on voltage absence)

Example
Binary input #8
CB Door Is Closed LED #5
Logic 1: Active High
(Lits when Open)

03_A0: Device Information and Interface


Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Encoding

Double Point Information


Source (Two bit encoded information) Destination
U+ Bit n Bit n+1 Bit n meaning
U- (52a) (52b)
Bit n+1
U+
Logic 0 0 Intermediate/Error
Circuit Logic 0 1 OFF
X
Breaker Logic 1 0 ON
Logic 1 1 Error

Example

Binary input #9 #8 Disconnector Status Interlocking


CFC logic

03_A0: Device Information and Interface


Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Annunciations Destination


SP outgoing information to:
Binary Outputs YES
LEDs YES
CFCs YES
SP or DP incoming information from: System Interface YES
Binary Inputs YES NO Buffers YES
Function Keys YES NO Display YES
CFCs YES NO Control Menu YES
System Interface NO YES
(only IEC 61850) DP outgoing information to:
Binary Outputs NO
LEDs NO
CFCs YES
System Interface YES
Buffers YES
Display YES
Control Menu YES

03_A0: Device Information and Interface


Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Annunciations Destination


SP outgoing information to:
Binary Outputs YES
LEDs YES

SP or DP Internal information from: CFCs YES

Binary Inputs NO System Interface YES

Function Keys YES Buffers YES

CFCs YES Display YES

System Interface NO Control Menu YES

DP outgoing information to:


Binary Outputs NO
LEDs NO
CFCs YES
System Interface YES
Buffers YES
Display YES
Control Menu YES

03_A0: Device Information and Interface


Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Annunciations Destination


Note: Two or more binary inputs define
the position number of the transformer
tap changer.
e.g. 4 binary input for 16 tap positions
SP outgoing information to:
Binary Outputs NO
Incoming information from: LEDs NO
Binary Inputs YES CFCs NO
Function Keys NO System Interface NO
CFCs NO Buffers YES
System Interface NO Display YES
Control Menu YES

03_A0: Device Information and Interface


Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Annunciations Destination


SP outgoing information to:
Binary Outputs YES
LEDs YES
SP Internal information from: CFCs YES
Binary Inputs NO System Interface YES
Function Keys YES Buffers YES
CFCs YES Display YES
System Interface NO Control Menu NO

VI outgoing information to:


Binary Outputs NO
VI Internal information from:
LEDs NO
Analog Inputs, Internal calculation
CFCs YES
Note: source and information
are fixed and can not be System Interface YES
selected/deleted in the Buffers YES
configuration matrix.
Display YES
Control Menu NO

03_A0: Device Information and Interface


Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Annunciations Destination

Measured/Metered Value
External Measured Value Information to:
Information from:
Measured Value Window NO
CFCs YES CFCs YES
System Interface YES System Interface YES
(only IEC 61850) Metered Value Window YES
Display YES

03_A0: Device Information and Interface


Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Control Circuits
Single Control Double Control Double Control Double Control Double Control
(S) (D2) (D4) (D12) (D3)
U+ U+ U+ U+ U+ U+ U+ U+ U+

Trip Trip Close Trip Close Trip Close Trip Close


&
Close Coil Coil Coil Coil Coil Coil Coil Coil
Coils U- U- U-

U- U- U- U- U-

52b Feedback Command


Command Control U+
U-
52a SP indication Executed
Started Interlock U+ Chatter
or
Check Blocking
DP indication
Circuit Breaker
X
03_A0: Device Information and Interface
Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Commands Destination


Without Feedback

SP outgoing information to:


Binary Outputs YES
Command information from: LEDs NO
CFCs YES
CFCs YES System Interface NO
System Interface YES Buffers YES
Display YES
Control Menu YES

03_A0: Device Information and Interface


Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Commands Destination


With Feedback

SP outgoing information to:


Binary Outputs YES
Command information from: LEDs NO
CFCs YES
CFCs YES System Interface NO
System Interface YES Buffers YES
Display YES
Control Menu YES
Feedback information from:

One binary input as SP indication


or
Two binary inputs as DP indication.

03_A0: Device Information and Interface


Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy
DIGSI 4 - Device Information Types

Source Measurement Destination


Measured, Limit Value
Information to:
Measured and Limit Value
Information from:
Measured Value Window YES
CFCs YES
CFCs YES YES YES
Analog Inputs Yes NO YES System Interface YES

System Interface NO YES NO Metered Value Window NO

(only IEC 61850) Display YES

Power metered Value


Power metered Value
Information to:
Information from:

Measured Value Window NO


Measured Value YES NO
CFCs YES
Binary Inputs NO YES
System Interface YES
Metered Value Window YES
Display YES

03_A0: Device Information and Interface


Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting - group in dependence


of the current

Setting group B becomes active if all line currents drop below 5% of the rated
nominal current.
Otherwise, setting group A is active.

04_A0: CFC-Exercises
Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 1: Enable the Setting Group Change Option
Enable the Setting Group Change Option in the Device Configuration.

04_A0: CFC-Exercises
Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 2: Configure the Setting Group Change Option
Open the Setting Group Change Option (double-click).
Set parameter 0302 to binary input.

04_A0: CFC-Exercises
Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 3: Allocation
Open the Configuration Matrix (Masking I/O). Bit 1
0 1
Bit 0

Assign the information item >Set Group Bit 0 0 A C


to C (source CFC !)

1 B D

Only >Set Group


Bit 0 changes
between A and B

04_A0: CFC-Exercises
Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 4: Allocation
Assign the currents to C (destination CFC !)

04_A0: CFC-Exercises
Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting group dependend on the


current
Step 5: Build the CFC program
Use the following function blocks:

Lower Setpoint: Q = Val < Limit


This function block outputs a signal when the
measured value Val drops below the specified limit
value Limit. It can only be applied in the
MW_BEARB priority class for measured values.

X1 X2
AND: Y = X1 * X2 (+)
Y
X1 X2 Y
0 0 0
X1 1 0 0
Y 0 1 0
X2 & 1 1 1

04_A0: CFC-Exercises
Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 5: Build the CFC program

04_A0: CFC-Exercises
Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time

After pressing the F1 key setting group B is active during the first 10 seconds.

Then, setting group A gets active again.

04_A0: CFC-Exercises
Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC


2. Save the Configuration Matrix
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC


2. Save the Configuration Matrix
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 1: Allocation of informations

Insert a new information item of the type Internal Single-Point Indication (Tagging)
in the matrix and assign it to the F1 function key and to CFC (destination CFC).

04_A0: CFC-Exercises
Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC


2. Save the Configuration Matrix
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 2: Save the allocated information

Save the allocated information.

04_A0: CFC-Exercises
Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 3: Insert a new CFC chart

Open the folder named CFC, insert a new CFC chart, give it a good name and
open it.

04_A0: CFC-Exercises
Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 4: Draw a CFC chart
The TI
MER ru
ns onl
Use the TIMER block. y in PLC
or PLC
1!

R => Timer Reset Q=(S+T2) * T1 * R


S => Timer Start QT1= T1 * R
QT2= T2 * R

QT1 T1 T1

QT2 T2 T2

Delay Prolongation
T1 and T2 timer function Q is delayed by T1 Q corresponds to S prolonged by T2

04_A0: CFC-Exercises
Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 4: Draw a CFC chart

Insert a TIMER
block via
Drag & Drop.

04_A0: CFC-Exercises
Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 4: Draw a CFC chart

Connect the input S (Start TIMER)


to the information Start (configured to F1)

04_A0: CFC-Exercises
Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 4: Draw a CFC chart

Set the value for the timer T1 to 10000 ms.

04_A0: CFC-Exercises
Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 4: Draw a CFC chart

Connect the output QT1 (HIGH applies for as long as the T1 timer is running)
to the information >Set Group Bit 0

04_A0: CFC-Exercises
Version: B 5_Page 24 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 25 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 26 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

CFC - Continuous Function Chart


(IEC Standard 1131 = High Flexibility)

4 priority classes for various tasks


PLC (Fast PLC)
Blocking protection functions
Few modules only
Automatic start after change-of-state at the input
PLC1 (Slow PLC)
Most frequent priority class (e.g. for TIMER applications)
Automatic start after change-of-state at the input
SFS (Switchgear interlocking)
Verifying the switchgear interlocking
Automatic start like PLC plus when activating a control command
MW (Measured value processing)
Configuring and comparing measured values
Implementing additional protection functions such as Reverse power (ANSI
32) and Power factor (ANSI 55)
Automatic start every 600 ms

04_A0: CFC-Exercises
Version: B 5_Page 27 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 5: Shift chart in the proper priority class

Open the Run-time Editor


To change the priority class: Grab your good name folder (by left mouse
key) and drag & drop it into the desired priority-class folder p menu (Shift
+ F11).
If you want to prepare
the NEXT CFC chart
inserted to run under
another priority class
then first select the
desired priority class
then click on edit
then predecessor for
insert position and
then ok

04_A0: CFC-Exercises
Version: B 5_Page 28 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 29 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 30 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 6: Let the system verify the run sequence

Obviously, you dont have to change the run


sequence as the TIMER is the only block
running in the chart.

Changes must, however, be made if several function blocks are


placed and some of them are maybe in the wrong order

04_A0: CFC-Exercises
Version: B 5_Page 31 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 6: Let the system verify the run sequence

In this case, the run sequence must be changed


as the TIMER has the number 2 in the chart, i.e.
it will be executed after the OR block.

In this case, click on


Options and then on
optimize run sequence.

04_A0: CFC-Exercises
Version: B 5_Page 32 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 33 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence ;
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 34 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 7: Compile the CFC chart

Compile the chart.

04_A0: CFC-Exercises
Version: B 5_Page 35 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence ;
7. Compile the chart
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 36 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence ;
7. Compile the chart ;
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 37 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 8: Save the parameter set

Close the chart and save the parameter set.

04_A0: CFC-Exercises
Version: B 5_Page 38 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence ;
7. Compile the chart ;
8. Save and download the parameter set

04_A0: CFC-Exercises
Version: B 5_Page 39 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Follow the CFC standard procedure!

1. Allocate necessary informations to CFC ;


2. Save the Configuration Matrix ;
3. Insert and name a new CFC chart ;
4. Draw the chart ;
5. Shift the chart in the proper priority class ;
6. Let the system verify the run sequence ;
7. Compile the chart ;
8. Save and download the parameter set ;

04_A0: CFC-Exercises
Version: B 5_Page 40 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 3: Change the setting group dep. on the time


and the current
Normally, group A is active.
Group B is active:
during the first 10 seconds after pressing the F1 key
or
if all phase currents drop below 5% of the rated nominal
current.
Combine the solution from exercise 1 with that from exercise
2 by using the following block:

X1
OR: Y = X1 + X2 (+)
X2 Y
X1 X2 y
0 0 0
1 0 1
X1 0 1 1
Y
X2 1 1 1 1

04_A0: CFC-Exercises
Version: B 5_Page 41 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 3: Change the settings group


Solution - Allocation
Connect the two charts via an additional internal single-point indication:
Chart I < 5: Priority class MW_BEARB Chart 10s after start: Priority class PLC1_BEARB

Matrix

Destination
CFC
Source
CFC

Insert a new internal


single-point indication
in the matrix and
allocate it to CFC
(destination and
source!)
04_A0: CFC-Exercises
Version: B 5_Page 42 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 3: Change the settings group


Solution - CFC
1 Chart I < 5 (priority class MW_BEARB):

2 Chart 10s after start (priority class PLC1_BEARB):

04_A0: CFC-Exercises
Version: B 5_Page 43 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 4: Time control 1 (2) Simple switching


sequence

When F1 is pressed, LED1 is lit for 5 seconds.

Then LED2 is lit for 15 seconds.

04_A0: CFC-Exercises
Version: B 5_Page 44 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 4: Time control 1 (2) Simple switching


sequence
Solution
1

2 Priority class: PLC1 (slow PLC)

04_A0: CFC-Exercises
Version: B 5_Page 45 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 5: Time control 2 (2) - Flashing

A LED flashes when F1 is pressed.

It goes off when F2 is applied.

04_A0: CFC-Exercises
Version: B 5_Page 46 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 5: Time control 2 (2) - Flashing


Solution
1

2 Priority class: PLC1 (slow PLC)

OR

04_A0: CFC-Exercises
Version: B 5_Page 47 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 6: Power Direction


A new dynamic symbol (arrow) on the default display of the device is to
indicate the power direction.

04_A0: CFC-Exercises
Version: B 5_Page 48 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 6: Power Direction


Solution - Allocation
Allocate the required measured value P= (power) to the destination CFC.

Create an internal double-point indication required


to indicate the power direction on the default
display.

04_A0: CFC-Exercises
Version: B 5_Page 49 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 6: Power Direction


Solution - CFC

Evaluate the power direction by using the blocks UPPER_SETPOINT and


LOWER_SETPOINT.
Use BUILD_DI to create the previously defined double-point indication P-
direction.

04_A0: CFC-Exercises
Version: B 5_Page 50 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 6: Power Direction


Solution - Display Editor

Create 3 static symbols to visualise


the states shown below.

Create a dynamic symbol of the


type Symbol to be filled with the 3
static symbols.

Place the dynamic symbol on the


default display and connect it to the
new double-point indication.

04_A0: CFC-Exercises
Version: B 5_Page 51 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 7: Interlocking expansion

Expand the default interlocking conditions:

The switch commands for the circuit breaker, isolating switch and
grounding switch are only admitted if
no SF6-Loss indication is present

04_A0: CFC-Exercises
Version: B 5_Page 52 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 7: Interlocking expansion


Solution

1 Allocate SF6-Loss to CFC as destination.

04_A0: CFC-Exercises
Version: B 5_Page 53 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
Feedback of devices: Interlock conditions:
2

Breaker DP

Disc.Swit. DP

AND
EarthSwit. DP
52 Close IntSP
AND
52 Open IntSP
AND
You have to expand the Disc.Close IntSP
already existing chart in AND
the priority class SFS Disc.Open IntSP
(Interlocking). AND
E Sw Open IntSP
E Sw Close IntSP

04_A0: CFC-Exercises
Version: B 5_Page 54 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
2a Modify the interlock condition 52 Close on the page A1:
No SF6-Loss
to the other interlock
conditions

52 Close IntSP
SF6-Loss SP

2b Modify the interlock condition 52 Open on the page A2:

52 Open IntSP
No SF6-Loss

2c Modify the interlock condition Disc.Close on the page A2:

Disc.Close IntSP

No SF6-Loss

04_A0: CFC-Exercises
Version: B 5_Page 55 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
2d Modify the interlock condition Disc.Open on the page A2:

Disc.Open IntSP

No SF6-Loss

2e Modify the interlock condition E Sw Close/E Sw Open on the page A2:

E Sw Close IntSP
E Sw Open IntSP

No SF6-Loss

04_A0: CFC-Exercises
Version: B 5_Page 56 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 8: Create new interlocking conditions

Create the new interlocking conditions for closing the...

Breaker: Disconnector=ON AND Earth switch=OFF


Disconnector: Breaker=OFF AND Earth switch=OFF
Earth switch: Breaker=OFF AND Disconnector=OFF

Opening the switches should be possible in non-interlocked state!

04_A0: CFC-Exercises
Version: B 5_Page 57 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - Allocation
1

04_A0: CFC-Exercises
Version: B 5_Page 58 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - Assign a release condition
2

04_A0: CFC-Exercises
Version: B 5_Page 59 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - CFC
Use the following block to evaluate the feedback information (double-point indication)
of a command:

DI to BOOL: Y = VAL = IS_ON & IS_OFF

This block checks a double-point indication for the


states ON, OFF, 00 or 11 and produces a signal
as the result.
VAL IS_OFF IS_ON

y = 1, if ... { 00
01
10
11
0
1
0
1
0
0
1
1

04_A0: CFC-Exercises
Version: B 5_Page 60 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - CFC This module issues a HIGH
signal at the output y if the Release conditions for tripping
disconnector is closed. the circuit breaker:
Disconnector=CLOSE AND
Ground switch=OPEN

This module issues a HIGH


signal at the output y if the
ground switch is open.

04_A0: CFC-Exercises
Version: B 5_Page 61 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 9: Controlling via the function keys


Close
The circuit breaker (2-pole CLOSE, 1-pole OPEN) is to be
controlled via the function keys: F1=Close, F2=Trip. Trip
Use the following blocks to create a command and a double-
point indication:

BOOL_TO_CO The switch command is specified via the parameters


ORIGIN, PROP, VAL and TIME and is tripped via a signal
at the Trig input.
ORIGIN origin of the cause
PROP general command properties
TIME output time for the command
VAL switching direction (ON or OFF)

BUILD_DI This module transforms two input signals into one


double-point indication. The double-point indication
consists of the 2 bits VAL_OFF and VAL_ON.
TYP_DP_I defines the type of the double-point
indication: with distinction of 00 and 11 or without.

04_A0: CFC-Exercises
Version: B 5_Page 62 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 9: Controlling via the function keys


Solution
1

F2 Trip IntSP
F1 Close IntSP Q0 F-Key CF_D12

04_A0: CFC-Exercises
Version: B 5_Page 63 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 10: Controlling via a single function key

Expand exercise 9 so that closing and tripping is initiated alternately via the
same function key (F1).

NEG: Y= X1
X1 Y
X1 1 Y X1 0 1
(+)
Y
1 0

D-Flipflop
The signal at the input D is Clk D Q
issued at the output Q, if a rising 0 0 0
edge is recognised at the input 1 0 0
Clk. 0 1 0
1 1 1

04_A0: CFC-Exercises
Version: B 5_Page 64 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Exercise 10: Controlling via a single function key


Solution
1

2 Priority class: PLC1 (Slow PLC)

F1 Switch IntSP
Trip

Close

04_A0: CFC-Exercises
Version: B 5_Page 65 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Selection Guide for Function Modules and Task Levels

05_A0: CFC-Function Modules


Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

05_A0: CFC-Function Modules


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

05_A0: CFC-Function Modules


Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

05_A0: CFC-Function Modules


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Online Mode

Open Device in Online Mode

Plug & Play (First the device has to be initialized)

Hardware Test

06_A0: Commissioning and Test Functions


Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Online Mode


Open Device in Online Mode

06_A0: Commissioning and Test Functions


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Plug & Play

06_A0: Commissioning and Test Functions


Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Plug & Play

06_A0: Commissioning and Test Functions


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Parameter Comparison


Offline-/Offline and Online-/Offline

06_A0: Commissioning and Test Functions


Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Parameter Comparison


Offline-/Offline and Online-/Offline

06_A0: Commissioning and Test Functions


Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Change / Transmission of single parameters in


online mode

06_A0: Commissioning and Test Functions


Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Control of switching devices

06_A0: Commissioning and Test Functions


Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Hardware Test

06_A0: Commissioning and Test Functions


Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Hardware Test

06_A0: Commissioning and Test Functions


Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Hardware Test

06_A0: Commissioning and Test Functions


Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Hardware Test

06_A0: Commissioning and Test Functions


Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Hardware Test

06_A0: Commissioning and Test Functions


Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Hardware Test


Exercise
Parametrize the IEC103-protocol as system interface and insert
any communication address
Initialize your device on the table
establish the communication to the device
Set the transmission blocking mode
Control the event log with respect to alarms
Start the test mode and simulate a closed circuit-breaker as
well as an open disconnector and earthing switch by way of
addressing the binary inputs
Verify the response of your device by the integrated interface
Deacivate the transmission blocking mode
Change within the test mode to action generate indications
Send the indication >LED Reset
Verify the response of your device by the integrated interface
and reset that indication

06_A0: Commissioning and Test Functions


Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 Test In- and Outputs / Control of devices

Activate the chatter-blocking

Simulate a chattering at the binary inputs of the feedback information of the Q1 and

check the reaction via menu Control

Switch off the earthing switch Q5

Set the acquisition blocking for Q5 via the integral keypad

substitute the position of Q5 to ON (integral keypad)

check the indication via menu `Control

06_A0: Commissioning and Test Functions


Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 Test In- and Outputs / Control of devices

Set the acquisition blocking for CB and simulate a change of the


CB-position OFF/ON via the binary inputs

Check the reaction

Set the output blocking for switching device Q1 and try to control it

Check the indication via Menu Control

Check the reaction and remove the acquisition blocking


as well as the output blocking for all devices

06_A0: Commissioning and Test Functions


Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Commissioning and Test Functions

Test mode

Data Transmission blocking

Process data retrieval

Operational indication

Operational measuring values

06_A0: Commissioning and Test Functions


Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Test Mode

06_A0: Commissioning and Test Functions


Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Data Transmission Blocking

06_A0: Commissioning and Test Functions


Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Retrieval of Process Data

06_A0: Commissioning and Test Functions


Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Event Log

06_A0: Commissioning and Test Functions


Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Event Log

06_A0: Commissioning and Test Functions


Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Measurement of Operational Values

06_A0: Commissioning and Test Functions


Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Event Log

06_A0: Commissioning and Test Functions


Version: B 5_Page 24 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Event Log

06_A0: Commissioning and Test Functions


Version: B 5_Page 25 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Event Log

06_A0: Commissioning and Test Functions


Version: B 5_Page 26 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Event Log

06_A0: Commissioning and Test Functions


Version: B 5_Page 27 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Process Data


Exercise

Open the device via plug&play


Change e.g. the pick up value for O/C-protection, as well
as one I/O- configuration and save that change only at the device
Do a on-/offline comparison
Save the changes on PC
Create two test records
Save the records and the event Log to retrieve them in
the off-line mode
Copy the logs and records from the plug&play-variant to
the master file of first exercise
Check the presence in the master device file

06_A0: Commissioning and Test Functions


Version: B 5_Page 28 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Which facilities does SIPROTEC 4 offer ?


IEC-Interface
IEC 61850 substation ethernet communication
The "VDEW-interface " is international standard IEC 60870-5-103
(without parameterizing)
According to recommendation of VDEW switching operations are
possible
PROFIBUS-Interface
PROFIBUS FMS is a protocol which includes all functions. Excellent
in conjunction with SICAM
PROFIBUS DP a protocol for simpler applications in conjunction
with automatization systems for industrial application.
Additional interfaces
Modbus
DNP 3
...........
07_A0: Setting of Communicationinterfaces
Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Which features does SIPROTEC 4 offer

variable interfaces

as fibre optics or electrical

exchangeable
refittable

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Communication: Setup with IEC 60870-5-103

To load dispatcher

SICAM SCADA

IEC 60870-5-103 e.g. RS 485


IEC 60870-5-103 z.B, point to point

STATION

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Select the communication interfaces

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Set the IEC address

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

IEC Parameter

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Masking with IEC protocol

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Communication: Setup with Profibus FMS

To Load dispatcher

DIGSI 4

Profibus FMS SICAM

SUB-STATION

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Setting the communication interface

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Setting of the Profibus FMS Addresses

PROFIBUS FMS (SICAM SAS)


PROFIBUS FMS (DIGSI 4 via PC)

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

FMS Parameters on PC

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

FMS Parameters at the device

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Masking with FMS Protocol

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Communication: Setup with additional protocols


e.g. Profibus DP
To load dispatcher

e.g Profibus DP SIMATIC S7

STATION

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Additional protocols e.g. Profibus DP

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Additional Protocols
Select the Mapping-file and Address

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Additional Protocols e.g. Profibus DP


7SJ6-Standardmapping 3-1 bis 3-4

Output 7 7 8 3 Double commands


29 29 24 5 Single commands
Input 7 7 8 3 Double annunciations
146 114 64 26 Single annunciations
25 10 21 8 Measurement values
6 2 6 2 counter values
2 1 1 0 value annunciations

9 9 8 2 Bytes Output
100 48 80 28 Bytes Input

The volume of the data-objects which are offered via Profibus-DP


(Number of the Commands, Annunciations, Measuring values,
Counter values in Output- resp. Input direction) is exclusively
determined by the selection of a Standardmapping.
07_A0: Setting of Communicationinterfaces
Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Marshalling of Informations

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Scaling of Measuring Values

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Communication: Setup via Service Interface C

To Load Dispatcher

DIGSI 4
Public phone conn.

Office

Modem
IEC 870-5
STATION

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 for Remote communication via Service Interface

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Communication: Setup via Operator Interface

To Load Dispatcher

STATION

DIGSI 4

IEC 870-5

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 via Operator Interface

07_A0: Setting of Communicationinterfaces


Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Process Data Analysis

Representation of indications and measured values


Retrieval of fault records with DIGSI 4
The COMTRADE format
Parameterization of fault record representation
Definition of user profile
Angle measuring
Fourier analysis
Impedance calculation
Export of fault records

08_A0: Process Data Analysis


Version: B 5_Page 1 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Evaluation of Fault record

The following data are used for the evaluation:

Measured values recorded in the device fault record

Characteristics calculated by SIGRA 4, for ex. impedance

Binary signals

Data of other fault records for comparison

08_A0: Process Data Analysis


Version: B 5_Page 2 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Generation of RIO-File in DIGSI 4 (Part 1)

Only relevant for


distance protection !

08_A0: Process Data Analysis


Version: B 5_Page 3 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

Generation of RIO-File in DIGSI 4 (Part 2)

Only relevant for


distance protection !

FALSE at I(nom) = 1A
TRUE at I(nom) = 5A

08_A0: Process Data Analysis


Version: B 5_Page 4 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Indication / Measured Value Indication

Evaluation of fault record data via the SIGRA 4 views:

Time signal

Vector diagrams

Circle diagram

Harmonic components

08_A0: Process Data Analysis


Version: B 5_Page 5 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Time Signal View

08_A0: Process Data Analysis


Version: B 5_Page 6 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Vector Diagram View

08_A0: Process Data Analysis


Version: B 5_Page 7 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Circle Diagram View

08_A0: Process Data Analysis


Version: B 5_Page 8 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Harmonic Component View

08_A0: Process Data Analysis


Version: B 5_Page 9 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Graphical Structure of a Fault Record

The graphical interface of a fault records consists of the following:

Views with as many diagrams as you like

Diagrams with as many signals as you like

Signals of any view and diagram


- analog signals
- binary signals
- status signals

08_A0: Process Data Analysis


Version: B 5_Page 10 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Diagrams / Signals

Insert / Assign

Copy

Delete

Define Properties

08_A0: Process Data Analysis


Version: B 5_Page 11 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Object Properties

Diagram properties

08_A0: Process Data Analysis


Version: B 5_Page 12 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Signal Assignment

08_A0: Process Data Analysis


Version: B 5_Page 13 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Structure of Fault Records

A fault record has the following components:

*.CFG - COMTRADE configuration file

*.DAT - COMTRADE file (measured values)

*.RIO - protection settings (optional)

*.DG4 - SIGRA 4 session connection memory

08_A0: Process Data Analysis


Version: B 5_Page 14 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Exporting of Fault Records

Open Record Object

Select Fault Record

Open Export Dialog

Define Export File

Export Fault in the COMTRADE format

08_A0: Process Data Analysis


Version: B 5_Page 15 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

DIGSI 4 - Definition of Setting Values for Fault


Records

Open the Fault


Record dialog box
in the settings
mode
Set values
Transfer values
to device

08_A0: Process Data Analysis


Version: B 5_Page 16 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - The COMTRADE Format

08_A0: Process Data Analysis


Version: B 5_Page 17 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - The .dat Data File

0000000000,0000000000,-00118,000030,000084,000150,-00108,-00038,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 First set of data


0000000001,0000001666,-00126,000098,000024,000113,-00162,000052,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000002,0000003332,-00081,000114,-00035,000036,-00142,000110,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000003,0000004998,-00024,000124,-00104,-00057,-00107,000168,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
The contents of the .DAT data files
0000000004,0000006664,000039,000080,-00120,-00115,-00030,000150,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 can be viewed in the Text Editor. The
0000000005,0000008330,000101,000026,-00129,-00168,000054,000117,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 figures are separated by commas.
The data file can be edited in external
programs like Excel.

0000000596,0000992936,000081,-00116,000029,-00039,000146,-00105,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000597,0000994602,000022,-00125,000097,000054,000110,-00161,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000598,0000996268,-00037,-00086,000117,000113,000039,-00147,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000599,0000997934,-00101,-00030,000126,000166,-00050,-00116,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000600,0000999600,-00117,000027,000086,000149,-00104,-00043,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
Last set of data
1. ...... ......... 6.1. .. ...... 19

Scanning value of the analog Value of the 19 binary values (0 or 1)


channels (analog channel multiplied
by its factor)
Time scale in ms

Number of the scanning value

08_A0: Process Data Analysis


Version: B 5_Page 18 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Frequency Analysis

Fourier : A periodic signal can be divided up into its frequency contents.

sig

0 1 N-1 k

Period with scanning values


N/2 N-1

2 2
sig = Am * cos m k + Bm * sin m k
m=0 k=0 N N
Sum value of N scanning values per supply period

Frequency content (m=0 direct component, m=1 fundamental component, m=2 second harmonic

08_A0: Process Data Analysis


Version: B 5_Page 19 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Frequency Analysis

direct fundamental 2. harmonic


component component

C0 C1 C2

0 1 2 3 4 N/2 N/2+1 l

For N scanning valued per supply period


DIGSI can calculate N/2 spectral lines by
way of the Fourier analysis.
N-1

2
2

sig = C0 + C1 * cos ( l k+w1) + C2 * cos ( 2 k +w2 ) + .........


N N
k=0

Cm = Am2 + Bm2 wl = arctan(Bm / Am)

08_A0: Process Data Analysis


Version: B 5_Page 20 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Process Data Analysis

Parameterization of fault records

Definition of user profile

Synchronization of fault record

08_A0: Process Data Analysis


Version: B 5_Page 21 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Measuring a Fault Record

Tools for fault record measuring:

Zoom
Table
- assignment of measured signals
- assignment of times
Cursor behavior
- magnetic (on status signals) pointer
- snapping (on samples) pointer

Status signals

08_A0: Process Data Analysis


Version: B 5_Page 22 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Parameterization of Fault Record

Parameterize
channels
(Network Nodes)

08_A0: Process Data Analysis


Version: B 5_Page 23 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Parameterization of Fault Record

Parameterize
Network Nodes

08_A0: Process Data Analysis


Version: B 5_Page 24 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - User Profiles

Define and save

Use

Define assignment

Delete

Insert device type

08_A0: Process Data Analysis


Version: B 5_Page 25 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - User Profiles

Define
Save
Use
Delete

08_A0: Process Data Analysis


Version: B 5_Page 26 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - User Profiles

Assign

08_A0: Process Data Analysis


Version: B 5_Page 27 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Synchronization Procedure

Insert comparison fault record B


Insert empty diagram in the Time Signal view
Insert signal of fault record A, for ex. phase voltage in short circuit
Insert comparison signal from fault record B
Cursor position
- Cursor 1 on synchronous point signal fault record A
- Cursor 2 on synchronous point signal fault record B
Select Synchronize Fault Records (menu command)
Check synchronous points and displacement
Trigger synchronization

08_A0: Process Data Analysis


Version: B 5_Page 28 Energy Sector Siemens AG
DIGSI 4 Basic
Siemens Power Academy

SIGRA 4 - Dialog Box

08_A0: Process Data Analysis


Version: B 5_Page 29 Energy Sector Siemens AG
DIGSI 4 Basic