Section 1. General Specifications
Content Unit Specification
Phase 3
Refrigerant R22
Number of Poles 2
U-V 2.806
Winding Resistance
U-W 2.806
[at 25C (77F]
V-W 2.651
Notes
2 Motor specifications in the table are the average values for your reference.
4 Certifications:
CCC certificate No.2002020704000230.
UL certificate No.SA13037.
5 Expiration of Specification
Expiration of this specification shall be effected until issuing a notice with indication of the expiration date from the
issued date . In case of improvement or elimination of this specification , it shall be handled by the revision record
2.1 Performance
Hz 50 60 Remark
Power Source (3PH)
V 380 440
W 14,500 17,900 7%
Capacity
(BTU/hr) 49,474 61,075 reference
Input Power W 4,540 5,550 7%
Current A 7.90 8.20 7%
Hz 50 60
Power Source (3PH)
V 380 440
Notes
Conditions
Compressor Temp. C (F) 10~60(50~140)
2.4 Others
Content Unit Specification
L.P. S. MPa(G)/psig 1.6(232)
Design Pressure
H. P. S. MPa(G)/psig 3.0(435)
Insulation Resistance M 100 (without refrigerant)
Dielectric Strength V 2400 (1 second)
Residual Moisture mg 300
Note:
1. The insulation resistance be measured with a DC500V megohm tester.
3
Section 3. Standard Accessories
Nameplate A-5102-DSB 0
4
Section 4. Compressor Protection
FOR LIQUID
REFRIGERANT
CHARGING
CAPILLARY
LIQUID LINE
SERVICE
OUTDOOR VALVE
INDOOR
HEAT HEAT
EXCHANGER EXCHANGER
GAS LINE
REVERSING SERVICE VALVE
VALVET
LOW
PRESSURE
SWITCH
COMPRESSOR CRANKCASE
HEATER
5
Section 5. Operating Envelope
70 Transient Operation
60
Condensing Temperature
50
Normal Operation
40
30
20
10
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Evaporating Temperature
6
Section 6. Application Standard & Limit
Standard: Applicable to ordinary conditions in Japan JIS B8616 or standards relative to JIS B8616, such as standard rating
conditions, maximum operating conditions, low temperature conditions, etc.
Limit: Applicable to transitional brief period of time, such as start-up and beginning of defrost mode.
No. Item Standard Limit Note
1 Refrigerant R22(Meet the standard of Japan JIS K1517)
-15~12(554 F) -25~15(-1359 F)
2 Evaporating Temp. Comp. Suction Pressure
0.20~0.62MPa(G)(2990psig) 0.10~0.69MPa(G)(14.5100psig)
90(194 F) Max.
6 Shell Bottom Temp. Evaporating Temp.+12(21 F) Min. Operating
Voltage at compressor
9 Running Voltage Within 10% of the rated voltage
terminals.
Three Phase Models: 85% of the rated voltage min. Voltage at compressor
10 Starting Voltage
Single Phase Models: 90% of the rated voltage min. terminals.
On Period: Until the oil level returns to the center of the lower bearing For at least 7 minutes -
11 On/Off Cycling on/3 minutes-off is
Off Period: Until balance of high and low pressure is obtained recommendable.
Abnormal Pressure Pressure Rise: 3.0MPa(G) (435psig) Max. By high pressure switch
15
Rise/Drop Pressure Drop: 0.03MPa(G) (4.35psig) Min. By low pressure switch
System Moisture
16 200ppm Max.
Level
System 1 Vol.% Max. 24 hrs. after vacuuming:
17 Uncondensable Gas
Residual Oxygen 0.1 Vol.% Max. 1.01kPa Max.
Level
18 Tilt 5Deg.Max.
Operation beyond the above limits must be approved by Dalian SANYO Compressor Co., Ltd. (G): Gauge Pressure
7
Notes
1 Installation should be completed within 15 minutes after removing the rubber plugs.
4 Liquid refrigerant should be charged on liquid line between condenser and receiver. Do not charge the liquid refrigerant
on the suction or discharge pipe of the compressor.
7 Crankcase heater is required when the oil sump temperature is too low to meet the requirement of item 6 on page7.
8 Voltage fluctuation between compressor terminals, during operation, shall be within 2% of the rated voltage.
8
Section 7. Selection of Electrical Wire
Voltage drop may occur due to the large current draw during compressor starting.
We recommend selecting the wire size from the table below.
terminal plate compressor
indoor
outdoor
power
terminal
source indoor compressor
plate
5m max. 10m max. 15m max. 20m max. 30m max. 50m max. 1m max.
20max. 2.0 2.0 2.0 3.5 5.5 8.0 2.0
30max. 3.5 5.5 14.0
40max. 3.5 5.5 8.0
50max. 8.0 14.0 22.0
60max. 5.5
70max. 3.5 8.0 14.0 3.5
80max. 22.0 30.0
90max. 14.0
100max. 8.0 38.0
110max.
120max. 5.5 22.0 30.0
140max. 14.0 50.0 5.5
160max. 22.0
180max. 38.0 60.0 8.0
200max. 8.0 30.0
220max. 50.0 80.0
240max. 14.0
6.3 Caution of Ground
The internal motor protector does not protect the compressor against all possible conditions.
Please be sure that the system utilizes the ground connection when installed in the field.
9
No. Part Code Qty Name
238.2 1 809 850 88 1 Compressor
[9.378]
2 A-0101-DSB 1 Terminal Box Cover
190.5
3 A-0201-DSB 1 Terminal Box Clip
[7.505]
HOLE 4 A-0301-DSB 1 Insulating Grommet
4-18 0.709
5 A-5102-DSB 1 Nameplate
6 B-0101-DSB 1 Screw Special
[9.378]
[7.505]
.5 .0
]
238.2
190.5
13
[5 140
12 740]
[4
0.
.
3
[4.889]
[5.169]
124.1
131.3
41.
5 31.0
0
45.
77.2
1 DISCHARGE TUBE 13.1 [3.039]
10
[0.516]
[2.685]
68.2
3 [0.878]
U W
[2.923]
74.2
[17.785]
451.4
[16.567]
420.8
176.4
TERMINAL
4 [6.9502]
[12.249]
310.9
[10.205]
259.0
5 Part Code
D-0101-DSB
[0.985]
25.0
Name
6
Compressor Outline Drawing
No. Part QTY Name
1 M-0101-DSB 4 Mounting Grommet
2 M-0201-DSB 4 Mounting Sleeve
3 B-0101-DSB 1 Screw Special
1 40
[1.575]
M8 BOLT
[1.260]
2
WASHER
32
WASHER SPRING
8
[0.315] 3
COMPRESSOR BASE
6 ]
R1 630 20
0.
[R [0.787]
24
[1.811]
[0.945]
[1.811]
46.0
M4[1.575]
[1.457]
37.0
46
19
11
[0.748]
1
11
[0.433]
[R R
2 0. 3 8.6
11 [0.339]
8]
10.6
[0.417]
[0.394]
[1.811]
10
[1.496]
46
38
19
[0.748]
Part Code
M-5101-DSB
Name
Mounting Parts Listing
`
1125 [44.291]
12
1086 [42.756]
60 [2.362]
410 [2.362]
0.000 60[2.362]
1148 0
-5
[45.197 -0.197 ]
410 [2.362] 1000 0
-5 [39.370
0.000
-0.197 ]
60 [2.362]
90[3.543]
Part Code
D-0201-DSB
Name
Packing Dimensions
120
80985088XXXXXXXXX
DALIAN SANYO COMPRESSOR CO.,LTD.
80
13
MFG.DATE XXXX.XX.XX
XXXXXX
SERIAL NO. XXXXXXX
MADE IN CHINA
Part Code
A-5102-DSB
Name
Nameplate
SWITCH V
POWER
SUPPLY INTERNAL
50Hz PROTECTOR
380~415V
R
U W
S
T
COMPRESSOR
MAGNETIC SWITCH
R C
S B
14
POWER
SUPPLY T A
50Hz
220V
REVERSAL
DEFENSIBLE RELAY
CRANKCASE HEATER
Part Code
E-0910-DSB
Name
Wiring Diagram