500e/01/97
INTRODUCTION
1
TECHNICAL FEATURES COMMISSIONING AND MAINTENANCE
The following types of flame detectors are suitable: - The wiring must be checked exactly when commissioning
- Ionisation probe, temperature resistant material, well the installation. Incorrect wiring could damage the con-
insulated (material and insulation same as for ignition trol box, putting the safety of the burner system at risk.
electrode). - The chosen fuse rating must not, on any account, be
- IRD 1020 infra-red flicker detector (see doc. 746) higher than the value given in the technical data. Failure to
observe this instruction could, in the case of a short circuit,
Flame detection using an ionisation probe is only possible have serious consequences for the control box or burner
in conjunction with mains supplies which provide a neu- system.
tral earth connection. - For safety reasons, it must be ensured that the control box
performs at least one normal shut-down during every
24 hour period.
2. Safety - Switch off or disconnect the power before plugging in or
unplugging the unit.
In terms of design/construction and programme sequence, - Burner control boxes are responsible for the safety of the
the TFI 812 control boxes conform to the presently appli- system and should not be opened.
cable European standards and regulations.
2. Routine checks
3. Installation
On commissioning or after servicing the burner system, or
At the baseplate: if the system has not been in operation for a long period, a
- 3 earth terminals, with an additional tag for the burner check of the safety-relevant control box functions must be
earth. made.
- 3 neutral terminals, with a fixed, internal through connection
to the neutral input, terminal 8. a) Attempt to start with gas valve closed:
- 2 independent terminals, which can be used as desired. - At the end of the safety interval
- 2 separate slide-in plates and 2 fixed, threaded knock- -> Lockout
outs (PG 11 thread) as well as 2 knock-outs underneath,
facilitate wiring of the baseplate. b) After a normal start, with the burner in operation, close
the gas valve:
General: - At the end of the safety interval, system attempts to
- Can be mounted in any position, insulated as per IP 44 restart
standard (unaffected by water spray). -> Lockout
The control box and detector probe should not, however,
be subjected to excessive vibration.
- The applicable installation regulations must be observed 3. Possible faults
during installation.
Burner does not start:
- Fault in electrical supply, thermostat OFF
- Mains voltage too low
2
WIRING AND SEQUENCE DIAGRAMS TFI 812.2
Ph
10A max. HS ST GW RT
1 2 3 4 5 6 7 8 9
HS Main switch
GW Gas proving switch
ST Safety thermostat
RT Controlling thermostat
IS Ionisation probe
Z Ignition
IS Z V1 V2 SA V1 Solenoid valve, 1st stage
N V2 Solenoid valve, 2nd stage
SA remote lockout indicator
B tw Pre-ignition time
approx. 15 sec. (mod. 5)
approx. 10 sec. (mod. 10)
ts Safety time 5 sec. (mod. 5)
tw ts tv2 10 sec. (mod. 10)
tv2 2nd stage delay approx. 20 sec.
IRD CONNECTION
blue Kl. 8
IRD 1020 black Kl. 1
brown Kl. 9
b
RF
v1
z
B s
R26
SA
1 8 5 6 3 4 7
Ion
N V1 V2 ZT SA
3
DIMENSIONS WITH BASEPLATE TFI 812 MEASUREMENT OF THE FLAME SIGNAL
4,5
38,5
E 1
TFI 812
62,5
24
PG 11
+
60
86 The signal should
- be greater than 5 A
0 - 10 A
Insert plate
24 0 - 100 A
Reset button The Satronic Ionimeter
is ideal for making
this measurement.
30
35
44
Earth
30
25
16
M4
Underside cable
30 entry 16 mm
57-60
29 50 44 35
3
13.5
21.8
14
4.5
26
104
15.1
48
4
17
20.5