SAFETY
FOR LIFE S280-42-1
Optional
Power Auxiliary Switch
Control Supply
Interface Receptacle
Receptacle
Figure 15.
Type NOVA recloser cable receptacles with internal voltage sensing option. (Type NOVA recloser with 14-pin
control interface shown.
15
Type NOVA Three-Phase, Microprocessor-Controlled Recloser Installation and Operation Instructions
Figure 17.
Connect control cables, power cables, and sensor cables Form 5 control Voltage Sensor receptacle.
to the control. Verify that the proper cable/receptacle con-
nections are made. Improper cable connections can result
in damage to the recloser and/or control.
Complete the control programming before making the
high-voltage line connections. Refer to the Operation
section of this manual. Verify the correct voltage rating of
the equipment. Verify the correct control programming for
ratio and phase angle correction for the voltage rating of
the equipment.
Make appropriate electrical connections to the terminals of
the recloser. Verify the correct load-side (vertical bushings)
and source-side (horizontal bushings) terminal connec-
tions. This is required for correct operation of the internal Internal
voltage sensor. Energize recloser and confirm the voltage Voltage Sensor
outputs in the control. Receptacle
16
!
SAFETY
FOR LIFE S280-42-1
Operation TABLE 8
Form 5 Control Settings Adjusted Voltage Sensor Ratio/PT Ratio
The Form 5 control must be programmed with an adjusted Recloser Control
voltage sensor ratio and a phase angle correction; refer to Form 5
Tables 8 and 9. These are entered in the Form 5, Voltage Form 4D Adj. Voltage Form 6
Sensor Parameters screen (Figure 19). Recloser PT Ratio Sensor Ratio PT Ratio
The Form 5 control Recloser Interface (RIF) module NOVA 15 1175:1 140.84:1 1100:1
must be set to 12 V for the source side bushings. (The NOVA 27 2360:1 281.69:1 2200:1
load side bushings are not configured to work with the
internal voltage sensing option and are set as described NOVA 38 2360:1 281.69:1 2200:1
in the Form 5 Programming Guide.) Also, the Phantom
Phase feature can not be enabled on the Form 5 control
when using the voltage sensing option. TABLE 9
Phase Angle Adjustment
Refer to Service Information S280-79-10 for installation
and operation information of the Form 5 control. Voltage Sensor Phase Shift, NOVA 15
Refer to Service Information S280-79-2 for more infor- Cable Length* Form 4D Form 5 Form 6
mation on programming the Form 5 control. 3.05 m (10 ft.) -2.9 -3.3 -177.8
6.10 m (20 ft.) -3.5 -4.1 -177.0
9.15 m (30 ft.) -4.1 -4.9 -176.2
12.2 m (40 ft.) -4.7 -5.7 -175.4
12000.0
15.25 m (50 ft.) -5.3 -6.5 -174.6
Phase Shift, NOVA 27 and NOVA 15
with extended BIL
Form 4D Form 5 Form 6
3.05 m (10 ft.) -3.3 -4.0 -176.0
6.10 m (20 ft.) -3.9 -4.8 -175.2
12 140.84 -3.3 9.15 m (30 ft.) -4.5 -5.6 -174.4
12.2 m (40 ft.) -5.0 -6.4 -173.6
120 120 15.25 m (50 ft.) -5.6 -7.2 -172.8
Phase Shift, NOVA 38 and NOVA 27
12 140.84 -3.3 with extended BIL
Form 4D Form 5 Form 6
120 120 3.05 m (10 ft.) -5.9 -6.6 -174.2
6.10 m (20 ft.) -6.5 -7.4 -173.4
12 140.84 -3.3 9.15 m (30 ft.) -7.1 -8.2 -172.6
12.2 m (40 ft.) -7.7 -9.0 -171.8
120 120 15.25 m (50 ft.) -8.3 -9.8 -171.0
Figure 19. For Form 5 controls, the phase shift is adjusted -0.8 for
Form 5 control Voltage Sensor Parameters screen. each additional 3.05 m (10 ft.) of cable.
For Form 6 controls, the phase shift is adjusted +0.8 for
each additional 3.05 m (10 ft.) of cable.
Note: Form 4D controls running firmware version 1.2.0 or
newer use the Phase Angle Adjustment(s) listed in Table
9. Form 4D controls running previous versions of firm-
ware will require adding 180 degrees of phase shift to
the listed values in table 9.
*Maximum cable length is 15.25 m (50 ft.).
17
Type NOVA Three-Phase, Microprocessor-Controlled Recloser Installation and Operation Instructions
Form 4D and Form 6 Control Settings When programming either control, the PT connection must
be set for a Wye connection. Also, the Phantom Phase fea-
The Form 4D and Form 6 controls must be programmed ture must be disabled.
with a PT ratio and a phase angle adjustment; refer
to Tables 8 and 9. These are entered in the System Refer to Service Information S280-104-2 for more
Configuration screen (Figures 20 and 21). information on programming the Form 4D control.
Refer to Service Information S280-70-4 for more infor-
mation on programming the Form 6 control.
Figure 20.
Form 4D control System Configuration screen.
Figure 21.
Form 6 control System Configuration screen.
18
!
SAFETY
FOR LIFE S280-42-1
Accessories
Auxiliary Switch Terminals
A three-stage auxiliary switch can be provided as an The standard terminal is an eyebolt, 1/0500 mcm (630
accessory. Each stage has two independent contacts A). Eyebolt, 4/01000 mcm (800 A), 2-hole and 4-hole
that permit any desired combination of a (follow state flat- pad terminals, and stud-type terminals are available as
of recloser contacts) and b (opposite recloser contacts) an accessory (Figure 22).
positions. The switch contacts are insulated for 600 V and The eyebolt, flat-pad, and stud terminals are made of cop-
have a continuous current rating of 10 A. Their interrupting per alloys. Cooper Power Systems recommends terminal
ratings are shown in Table 10. connection to copper wires to optimize the electrical con-
nection. Aluminum cables may produce aluminum oxide
TABLE 10 sufficient to compromise the electrical connections.
Auxiliary Switch Interrupting Ratings
Non- Non- Anti-oxide coatings for temporary protection of wire-
Inductive Inductive Inductive Inductive brushed, aluminum cable connections to flat-pad or stud
ac ac dc dc terminals must be maintained at intervals determined by
Volts (A) (A) (A) (A) the customer based on load current, climate, and other
installation conditions.
24 15.0 20.0
48 7.5 10.0 Eyebolt terminals are recommended for copper conduc-
120 60 80 tors only.
125 1.5 2.0
240 30 60
250 0.45 0.5
19
Type NOVA Three-Phase, Microprocessor-Controlled Recloser Installation and Operation Instructions
Dimension B
NOVA 15 791
110 kV BIL (31.25)
NOVA 15 847
125 kV BIL (33.25)
NOVA 27 847
125 kV BIL (33.25)
NOVA 27 946
Pole 150 kV BIL (37.25)
NOVA 38 946
170 kV BIL (37.25)
1089
(43.0)
637
(25.0)
592 Min.
(23.25) A
Mounting
Holes 290 N
E
P
O
for (11.5)
0.75 Bolts
686 mm
(27 in)
779
(30.75)
Pole
Pole
Figure 22.
Dimensions of Type NOVA recloser with pole-mounting hanger accessory.
20
!
SAFETY
FOR LIFE S280-42-1
Arrester-Mounting Brackets
The arrester-mounting bracket accessory (Figure 23) can
be bolted to the recloser frame and pole-mounting hanger
for the addition of inboard and outboard arresters. The
arresters are not included with the brackets.
12 (0.50)
323 Min. Mounting Bolt
396
(15.5) (12.75)
468
(18.5) 350 388
(13.75) (15.5)
350 388
468 (13.75) (15.5)
(18.5)
396
240 43
425 (15.5) 105
(9.5) (1.75)
(16.75) (4.25)
941
(37)
288
(11.25)
406
(16)
686
(27)
Inboard Arrester-
Mounting Accessory
Pole
Pole
NOTE: All dimensions are mm (inches).
Dimensions shown are approximate.
Figure 23.
Dimensions of Type NOVA recloser with pole-mounting hanger and arrester-mounting bracket accessories.
21