Transducer1:

. .
Test Object - Device Settings
. . .
Substation/Bay:
Substation: TRAM 500KV Substation MEKONG 2.2 - PHU
address: MY- TAN THANH- BA
RIA VUNG TAU
Bay: Bay address:
. . .
Device:
Name/descriptio MEASUREMENT Manufacturer: FRANCE
n: TRANSDUCER
Device type: PAR 1233 B TNE 4F Device address:
1636
Serial/model 2318484 D
number:
Additional info MEKONG 2.2
1:
Additional info
2:

Test Object - Transducer Settings


.
Transducer General Settings:
Output type: Current
Full Scale Error Ref.: 0 .. +max
Angle Calculation: Phi(V) - Phi(I)
Settling time: 3.00 s
CT Starpoint Connection:
. . . .
Function Name: Active
Power
Number of phases: 3
Tolerance: 0.50 %
Type of Characteristic: Linear
symmetrical: No
Saturation Output: 22.00 mA
Minimum Input: -36.000 W Minimum Output: 4.00 mA
Knee Point Input: n/a Knee Point n/a
Output:
Maximum Input: 900.000 W Maximum Output: 20.00 mA

Test Settings
Point 1 2 3 4 5
Nominal Input: -30.000 MW 165.000 MW 360.000 MW 555.000 MW 750.000 MW
Test runs: 1 1 1 1 1
Voltage L1: 288675.135 V 288675.135 V 288675.135 V 288675.135 V 288675.135 V
Phase (V) L1: 0.000 0.000 0.000 0.000 0.000
Current L1: 34.641 A 190.526 A 415.692 A 640.859 A 866.025 A
Phase (I) L1: 180.000 0.000 0.000 0.000 0.000
cos (Phi) L1: -1.0000 1.0000 1.0000 1.0000 1.0000
Voltage L2: 288675.135 V 288675.135 V 288675.135 V 288675.135 V 288675.135 V
Phase (V) L2: -120.000 -120.000 -120.000 -120.000 -120.000
Current L2: 34.641 A 190.526 A 415.692 A 640.859 A 866.025 A
Phase (I) L2: 60.000 -120.000 -120.000 -120.000 -120.000
cos (Phi) L2: -1.0000 1.0000 1.0000 1.0000 1.0000
Voltage L3: 288675.135 V 288675.135 V 288675.135 V 288675.135 V 288675.135 V
Phase (V) L3: 120.000 120.000 120.000 120.000 120.000
Current L3: 34.641 A 190.526 A 415.692 A 640.859 A 866.025 A
Phase (I) L3: -60.000 120.000 120.000 120.000 120.000
cos (Phi) L3: -1.0000 1.0000 1.0000 1.0000 1.0000
Frequency: 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
Waveform: Sine Sine Sine Sine Sine

Applies to: Current Current Current Current Current


Actual Input: -23.341 MW 127.541 MW 278.402 MW 429.259 MW 580.184 MW
Actual Output: 4.137 mA 7.232 mA 10.326 mA 13.421 mA 16.517 mA
Error 6.659 MW -37.460 MW -81.598 MW -125.741 MW -169.816 MW
Absolute:
Error Relative: 22.198 % -22.703 % -22.666 % -22.656 % -22.642 %
Device Error: 0.854 % -4.803 % -10.461 % -16.121 % -21.771 %
Std. Dev.
Absolute:
Std. Dev.
Relative:
Std. Dev.
Device:
Assessment: Failed Failed Failed Failed Failed

Sweep Test Settings


Sweep type: No sweep test
From: n/a
To: n/a
Points: n/a
Step Size: n/a

Sweep Test Results


Assessment: n/a

Comment

. .
Test Module
Name: OMICRON Transducer Version: 3.00
Test Start: 28-Nov-2016 14:49:11 Test End: 28-Nov-2016 14:49:31
User Name: Manager:
Company:

.
Test State:
Test
failed