Catnic
April 2005
8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page ii
Contents
Page Introduction
2 Leaders in Technical Innovation
3 Help When You Need It
4 Catnic Service Package
Lintel Guidelines
5 How to Select a Lintel
6 Catnic Lintels Benefits
10 Lintel Selector - Cavity Walls
11 Lintel Selector - All Products
12 Installing a Cavity Wall Lintel
13 Installing a Lintel Supporting Concrete Floors
Products
14 Cougar Open Back Lintels
24 Classic Combined Box Lintels
31 CXL Lintels
34 Cavity Wall Eaves Lintels
38 Timber Frame Lintels
41 Installing a Timber Frame Lintel
42 External Solid Wall Lintels
46 Internal Partition and Loadbearing Wall Lintels
Extended Range
52 Standard Arch Lintels
53 Bespoke Lintels
54 Fabricated Arch Lintels
55 Enquiry Form - Fabricated Arch Lintels
56 Fabricated Corner and Bay Lintels
57 Enquiry Form - Fabricated Bay Lintels
58 Corner Lintels
59 Enquiry Form - Bay and Corner Lintels
Accessories
61 Lintel Arch Centres
62 Stop Ends
63 Weep Vents and Soffit Cladding
Catnic has pioneered the steel lintel for more than three generations and designs,
Catnic is committed to providing the building industry Catnics sales and technical teams are dedicated to
manufactures and supplies the construction industry with technically superior
with new and improved products, borne from investment matching the quality of our products with the excellence
products. Catnics reputation has been earned through constant technical innovation
in design and manufacturing technologies. of our service, from the professional voice at the end of
and leading the UK lintel market.
the telephone to our on-site consultation.
Catnic means:
Catnic was the First: Corus The strongest brand in the industry Full service support for customers
To develop the steel lintel in the UK and the first to An international company with steel at the heart of its A partnership approach to the way we work Catnic has been at the forefront of lintel design for over
gain BBA Approval strategic focus, Corus has many operations worldwide Dedicated haulier - liveried lorries 35 years. Our reputation for exceptional quality and
Servicing builders, architects, specifiers technical expertise ur webs satisfaction
Manufacturer to employ the revolutionary two-part and is united by a strong corporate brand. The Corus visit visit has ensured customers
it o i
s
our website our website
te
vi
corrosion protection system on its lintel as a logo is a symbol of confidence and a mark and merchants and loyalty in the products and services that we offer.
om
ww
om
ww
standard offering of quality and service. Committed to both national and independent
www.catnic.com w w
.c
.c
To gain both BBA approval and the coveted Kitemark merchants Catnics team:
.c .c a t n ic
a t n ic
to BS 5977 Corus is focused on achieving sustainable profitability, Investment in plant and machinery and the latest Are professional and experienced
To incorporate a built in Damp Proof Course into offer an unrivalled customer service package and places technologies our wtrained
Are extensively ebs our webs
visit
sit i sit i
te
our website
vi
te
vi
its lintels the highest value on the health, safety and well being Continuously dedicated to research and development Have comprehensive product and industry knowledge
www.catnic.com
om
ww
om
ww
To provide a built-in plaster key of its employees and customers. of the industry and our product ranges Have a committed parent company who are Investors
w w
.c
.c
in People .Corus.
c a t n ic .c a t n i c
Far from just leading, Catnic in fact has worked over the We hope that you will find this Lintel Product Selector
years with the BSI to establish the standards for lintels both useful and informative. Should you require any visit
our website
in this country, and continues to develop and invest in further assistance or information about our other
improving on these standards with its extensive range of product ranges then please call us on 029 2033 7900. www. .com
om
w
w
w.
products and unique features. c atnic.c
Cougar Open Back Lintels 1st corrosion protection layer galvanised steel
2nd corrosion protection layer black polyester coating
Catnic Lintels
Our rigid adherence to quality control and compliance
is your guarantee of technical superiority
Material
Catnic Cougar and Classic lintels are manufactured from
high quality grade galvanised steel to BS EN 10327:2004
Catnics Cougar Open Back (page 14) lintels are easy to Parts L1 & L2 of the Building Regulations
Approved Documents DX51D & Z275, with a black coloured polyester resin finish.
use profiles allowing masonry to be built up continuously on
both the inner and outer leaves saving time and cost on Catnics lintels comply with the amended Approved
Document L regulations. Catnics compliance illustrates their Damp Proof Course Quality control checks on the incoming steel include:
site. Cougars are fully insulated by moulding expanded
position as technical leaders, always striving for continuous The design of Catnic Cougar open back and combined Dimensional tolerances
polystyrene bead into the CG style lintel, forming a ribbed
improvement in more energy efficient construction practices. box lintels incorporates a built in DPC, and any water Mechanical properties
finish on the underside to provide a plaster key. The rigid
penetrating the cavity automatically transfers across the Thickness
slotted base on CL & CU lintels provides plaster adhesion
Load ratios sloping face of the lintel and is disposed of externally. In Quality of the galvanising
and avoids the hazards of working with mesh.
Safe working loads, as defined by BS 5977: Part 2 for areas of sheltered to medium exposed weather conditions
cavity wall lintels refer to uniform distributed loads there is no need to install a separate DPC. Quality control checks during manufacture include:
Catnics Classic Combined Box (page 24) lintel is a
applied in the inner to outer leaf ratios: Dimensions
robust design which resists twisting during construction
1:1 For lintels supporting masonry only Quality Thickness
and saves on blockwork and installation costs. Classics are
3:1 For lintels normally carrying timber floors Catnic lintels are manufactured to the highest quality and Weld quality
insulated using full height, continuous expanded
5:1 For lintels normally carrying concrete floors are continually assessed both internally and by numerous Quality and accuracy of the black coating
polystyrene board which is secured within the box.
The CL & CU lintel range refers to uniformly distributed external, independent organisations. All quality assurance Insulation
loads in the ratio of 19:1 when non standard or unusual systems comply with BS EN ISO 9001: 2000.
loading conditions occur.
001/05-H/GC
CLA50/100 - CLB50/100 CLA70/100 - CLB70/100 CLA90/100 - CLB90/100 115 50-65 102 CN3, CN4 Combined Box Lintel 26
18 20 22
001/05-EGC CUB50/100 - CU50/100 CUB70/100 - CU70/100 CUB90/100 - CU90/100 100 90-105 102 CN14 Combined Box Lintel 27
001/05-UC
CN3 26 CN3* CN4* 26 115 75-90 102 CN14 Combined Box Lintel 27
CN4 26 CN14** 27
7NC 100-115 50 140-150 CN42 Combined Box Lintel Wide Outer Leaf 27
001/05-UC
125 50-65 102 CN43, CN44 Combined Box Lintel Wide Inner Leaf 28
521/05-H/GC
001/05-EGC CG50/125 19 CG70/125 21 CG90/125 23 130 50-55 102 CN43, CN44 Combined Box Lintel Wide Inner Leaf 28
CGH50/125 19 CGH70/125 21 CGH90/125 23 140 50-65 102 CN11, CN12 Combined Box Lintel Wide Inner Leaf 29
125mm
521/058-N
HC/GC
CLA50/125 - CLB50/125 CLA70/125 - CLB70/125 CLA90/125 - CLB90/125 150 50-55 102 CN11, CN12 Combined Box Lintel Wide Inner Leaf 29
19 21 23
001/05-EGC
CUB50/125 - CU50/125 CUB70/125 - CU70/125 CUB90/125 - CU90/125 135-150 75 102 CN57, CN58 Combined Box Lintel Wide Inner Leaf 30
521/05-UC
44NC
521/05-H/GC
100-115 90-105 N/A CGE90/100 Open Back Eaves Lintel 36
CLA50/125 - CLB50/125 CLA70/125 - CLB70/125 CLA90/125 - CLB90/125
19 23
521/05-EGC
CUB50/125 - CU50/125 CUB70/125 - CU70/125 21 CUB90/125 - CU90/125 125-140 90-105 N/A CGE90/125 Wide Inner Leaf Open Back Eaves Lintel 36
521/05-UC
CN11 29 CN57 30 100 50-75 N/A CN55 Box Eaves Lintel 37
34NC
CN12 29 CN58 30 N/A 50-60 102 CTF5 Timber Frame Lintel 40
521/05-UC
N/A 60-70 102 CTF6 Timber Frame Lintel 40
N/A 70-80 102 CTF7 Timber Frame Lintel 40
* Suitable for5270mm
1/05-EGC cavity only ** Suitable for 75mm-85mm cavity only
N/A 35-60 102 CN23 Timber Frame Lintel 40
44NC
The above table represents our standard stock range of cavity wall lintels. For any requirements that fall outside of these N/A 102 CN48, CN49 External Solid Wall 45
521/05-EGC
N/A 102 CNZ94, CNZ95, CNZ96, CNZ97 External Solid Wall 45
parameters please contact Technical Services on 029 2033 7900 for advice on Catnics extensive range of special lintels
N/A 215 CN50, CN51 External Solid Wall 45
75 N/A CN92 Internal Partition Lintel 48
100 N/A CN100, CN102 Internal Partition Lintel 48
100 N/A CN5X, CN6X, CN99/438 Internal Partition Lintel 48
140-150 N/A CN56X, CN66X, CN99/436 Internal Partition Lintel 49
Ensure a nominal
150mm end bearing
Ensure lintel is
at each end.* Block inner leaf
not damaged. In addition to the cavity wall installation guide, please
read the following for installing concrete floors with
Catnic steel lintels. Concrete floor
Additional notes
Do Do not
Install a separate DPC in severe exposure conditions. Use damaged lintels When using the Catnic CL & CU Open back range
A Catnic Cougar Open Back or Classic Combined Box with concrete floors, always ensure that the
Apply point loads without prior consultation. Where the
lintel with an additional DPC membrane installed in blockwork is built tight against the inner vertical face
loading or a substantial part of it is applied as
accordance with normal practice provides the best of the lintel, and that a mortar joint is added to the
concentrated loads, each concentrated load must be
possible protection (page 64)
supported over a length of lintel of not less than 200mm. top of the blockwork so that the floor units have an
Locate the window/door frame so that the drip on the In such cases, the total loading must not produce even spread over the inner flange of the lintel
front of the lintel projects forward of the drip on the front bending moments or shear forces greater than those
of the frame. It is good building practice to insert a produced by the uniformly distributed loads specified in Avoid shock loading lintels during the installation of
flexible joint between the lintel and the top of the frame the relevant data tables Continuous concrete floor units and also any sideways loading
solid infill
while being lifted into position
Ensure that timber floor joists and roof trusses have a
full block depth between them and the lintel flange on
Allow blockwork to overhang the lintel by more
than 25mm
block 521/09UC
Precast flooring units should be laid on a mortar
Cougar Open Back Lintels
Apply concrete floor loads without ensuring that the total bearing of the full inner leaf wall width and should
Refer to the Catnic How to Install a Lintel Supporting loads are checked by a structural engineer, or by Catnic not be dragged over supports
Concrete Floors or the Steel Lintel Manufacturers Technical Services
Association guidelines (available on request) when using Avoid loading newly laid floors with building materials
Do not cut CG or CGH type lintels under any
Classic Combined Box or CL & CU Open Back Lintels to Lintels must be built-in as illustrated, ensuring that the
circumstances
support concrete floors
blockwork infill is well-jointed during construction and
Apply point loads directly on lintel flanges
Consider the use of our soffit cladding for all coastal Catnic CU Open Back Lintel compatible with the strength of the masonry above.
sites (refer to page 63 & 64)