Catnic

Lintel Product Selector

April 2005
8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page ii

Catnic - The Name to


Build a Reputation On

Contents
Page Introduction
2 Leaders in Technical Innovation
3 Help When You Need It
4 Catnic Service Package

Lintel Guidelines
5 How to Select a Lintel
6 Catnic Lintels Benefits
10 Lintel Selector - Cavity Walls
11 Lintel Selector - All Products
12 Installing a Cavity Wall Lintel
13 Installing a Lintel Supporting Concrete Floors

Products
14 Cougar Open Back Lintels
24 Classic Combined Box Lintels
31 CXL Lintels
34 Cavity Wall Eaves Lintels
38 Timber Frame Lintels
41 Installing a Timber Frame Lintel
42 External Solid Wall Lintels
46 Internal Partition and Loadbearing Wall Lintels

Extended Range
52 Standard Arch Lintels
53 Bespoke Lintels
54 Fabricated Arch Lintels
55 Enquiry Form - Fabricated Arch Lintels
56 Fabricated Corner and Bay Lintels
57 Enquiry Form - Fabricated Bay Lintels
58 Corner Lintels
59 Enquiry Form - Bay and Corner Lintels

Accessories
61 Lintel Arch Centres
62 Stop Ends
63 Weep Vents and Soffit Cladding

Technical Specifications & Quality Assurances


64 Where to Use a Separate DPC
65 Quality Assurance
66 Technical Information
67 The Environment
68 Technical Specification & Glossary
69 Technical Enquiry Request Form

Lintel Product Selector 1


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 2

Catnic - Leaders in Help When You Need It


Technical Innovation Fully committed to providing first class
service support

Catnic has pioneered the steel lintel for more than three generations and designs,
Catnic is committed to providing the building industry Catnics sales and technical teams are dedicated to
manufactures and supplies the construction industry with technically superior
with new and improved products, borne from investment matching the quality of our products with the excellence
products. Catnics reputation has been earned through constant technical innovation
in design and manufacturing technologies. of our service, from the professional voice at the end of
and leading the UK lintel market.
the telephone to our on-site consultation.
Catnic means:
Catnic was the First: Corus The strongest brand in the industry Full service support for customers
To develop the steel lintel in the UK and the first to An international company with steel at the heart of its A partnership approach to the way we work Catnic has been at the forefront of lintel design for over
gain BBA Approval strategic focus, Corus has many operations worldwide Dedicated haulier - liveried lorries 35 years. Our reputation for exceptional quality and
Servicing builders, architects, specifiers technical expertise ur webs satisfaction
Manufacturer to employ the revolutionary two-part and is united by a strong corporate brand. The Corus visit visit has ensured customers
it o i
s
our website our website

te
vi
corrosion protection system on its lintel as a logo is a symbol of confidence and a mark and merchants and loyalty in the products and services that we offer.

om
ww
om
ww
standard offering of quality and service. Committed to both national and independent
www.catnic.com w w

.c
.c
To gain both BBA approval and the coveted Kitemark merchants Catnics team:
.c .c a t n ic
a t n ic
to BS 5977 Corus is focused on achieving sustainable profitability, Investment in plant and machinery and the latest Are professional and experienced
To incorporate a built in Damp Proof Course into offer an unrivalled customer service package and places technologies our wtrained
Are extensively ebs our webs
visit
sit i sit i

te
our website

vi
te
vi
its lintels the highest value on the health, safety and well being Continuously dedicated to research and development Have comprehensive product and industry knowledge
www.catnic.com

om
ww
om
ww
To provide a built-in plaster key of its employees and customers. of the industry and our product ranges Have a committed parent company who are Investors
w w

.c
.c
in People .Corus.
c a t n ic .c a t n i c
Far from just leading, Catnic in fact has worked over the We hope that you will find this Lintel Product Selector
years with the BSI to establish the standards for lintels both useful and informative. Should you require any visit
our website
in this country, and continues to develop and invest in further assistance or information about our other
improving on these standards with its extensive range of product ranges then please call us on 029 2033 7900. www. .com

om
w
w
w.
products and unique features. c atnic.c

2 Lintel Product Selector Lintel Product Selector 3


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 4

Catnic Service Package How to Select a Lintel


Unsurpassed technical service and support from You need to know 3 things:
our experienced, helpful and friendly team 1 The wall construction 2 The length of lintel required 3 The load to be applied on the lintel
Once you have established each of the above, you will be able to choose the correct
lintel for your job by referring to the relevant tables in this guide

Technical support 1. Wall Construction External Solid Wall 2. Lintel Length


001/05HGC
Experienced engineers qualified in construction enable Catnic Once you have determined your wall There are three forms The length of lintel required is
to offer an advisory service to anyone engaged on building construction please refer to the lintel of lintel for external calculated by establishing the total
projects, regardless of size, from a private house extension, to selector on page 11 solid walls: width of the structural opening and
a major housing development or commercial building. single element adding 150mm (200mm for CXL
Cavity Wall
lintels for a single lintels) end bearing allowance for
If the construction is a
Free scheduling service leaf of brickwork each end. For example, an 1800mm
cavity wall, see the
CLASS The Catnic Lintel Advanced Scheduling System is two-piece lintels shaped to carry structural opening will require a
Open
001Back
/07HGClintel section
the most comprehensive, enviable lintel scheduling service the two separate leaves of a 2100mm lintel (2200mm for CXL).
on page 14, or the
available. One concise document leaves no room for 215mm fair face brick wall
Classic lintel section on 3. Applied Load
confusion or misunderstanding. CLASS clearly provides: box profile lintels which have a toe
page 24. You will need to know All lintels are designed to carry a
A description of each lintel, its location, price and for use in solid brick or block walls
the cavity wall dimensions to choose specific safe working load (SWL).
The Catnic service package includes: delivery time from 200mm 215mm thick
the correct lintel: If you are not skilled in the method
Experienced and dedicated team of lintel sales Guaranteed structural adequacy Lintels suitable for use in external
the external leaf dimension of load assessment, or the load has
representatives A site summary solid wall constructions can be found
the cavity dimension
001/09Hincluding
GC not been supplied to you by a third
Fully trained, professional internal customer support team on page 42.
To access the benefits of CLASS free of charge, simply insulation party, then please contact Catnic
for all your needs; from placing orders, to enquiring about
send your project drawings (dimensional plans, sections the internal leaf dimension Internal Partition Technical Services on
prices or deliveries
and elevations), floor layout and roof carcass, (along with a Also, please refer to the Lintel and Load Bearing Wall 029 2033 7900 for advice.
Comprehensive range of back-up literature from desk top
copy of the technical enquiry form in the back of this Selector on page 10. Lintels for internal
technical guides, to pocket and installation guides Once you have established:
Product Selector) to our Technical team. partitions and load
On-line help via Catnic.com Timber Frame 1 your wall construction
bearing walls come in
CAD details available on-line or CD-ROM providing For timber frame 2 lintel length
Design service for bespoke lintels three styles:
instant access to lintel drawings constructions, you 3 applied load
In addition to its standard range, Catnic design and corrugated lintels
Technical enquiry forms to accompany your drawings need to know: you will be able to choose the
manufacture a huge range of specials. The bespoke for non-load bearing applications
ensuring necessary information is received and turned the external
CN92 CN102 perfect Catnic lintel for your job by
range is designed and fabricated to satisfy features such as channel section lintels for loadings
around in a timely manner leaf dimension referring to the relevant tables in this
long spans, chamfered brickwork, reduced toe lintels for involving floor joists or blockwork
On-site sales and technical support when required cavity dimension Product Selector.
cant bricks, arched openings and other applications where box profile lintels for heavier loads
Technical hotline Once you have these dimensions,
non-standard construction is utilised. For further including point loads and wider
Dedicated hauliers for all your deliveries please refer to the Timber Frame
information please turn to page 52 of this guide. openings. These lintels are featured
Consultation at every stage of your job lintels section on page 38.
on page 46.
Free lintel scheduling and specification via CLASS Telephone Technical Services on
Extensive range of standard and bespoke lintels 029 2033 7900
Structural calculations for Local Authority approval if and or alternatively fax your enquiry on
when required 029 2086 0135

4 Lintel Product Selector Lintel Product Selector 5


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 6

Superb Corrosion resistance High quality galvanised steel PLUS


black polyester powder coating.

Cougar Open Back Lintels 1st corrosion protection layer galvanised steel
2nd corrosion protection layer black polyester coating

The first lintel manufacturer to achieve both BBA


approval and the BSI Kitemark showing commitment
to quality has always been at the top of our agenda.

Fully insulated CFC &


HCFC - free full height
insulation maximises
thermal efficiency and
Part L compliant.

Built in Plaster key


Avoids the hazards of
working with mesh key.
The unique design of
perforated base plates
on CL/CU lintels
minimises cold bridging
without affecting
Catnic was the first to powder coat lintels in the industry,
structural performance.
and are the only manufacturer to employ the famous black
finish - as standard - on top of a galvanised base material,
with no additional premiums to be paid.

This double protection gives Catnic lintels inherent


Negligible cold bridging due to base design benefits over those offered by other manufacturers
Independently tested with appropriate finishes to using only pre-or post-galvanised steel techniques.
achieve 1 hour fire rating Both these processes rely on just one coating of zinc to
Efficient plaster key provide cathodic protection. The zinc protects the steel
Manufactured under a quality assurance system to but is itself liable to rust with aqueous solutions leaching
Built in DPC Conforms to NHBC required Product Benefits & Design Features BS EN ISO 9001: 2000 from the building fabric, and therefore corrode.
profile. No additional DPC is required in many Self - weight of lintel allows easy handling solutions Catnics black polyester coating process provides an
areas of the UK, making construction quicker Profile shape designed for use without a separate DPC, The cavity wall lintel range are structurally sound without the effective barrier against moisture or chemical attack
and easier, giving extra peace of mind but also whilst providing additional support when required need for any base plate thus making them thermally efficient, leached from the masonry construction through
saving on time and cost. Where a DPC is BBA and BSI kitemark certified products removing any doubt about the effect of cold bridging. using both systems.
required, the lintel profile is shaped to support Corrosion protected
the DPC during construction. Safe working lintel loads are provided throughout this The Black Lintel = Improved Corrosion Protection The protection system complies fully with the chemical and
product selector with reference to various differential Many Catnic lintels employ not one but two methods of physical test requirements outlined in Table 2 of BS5977:
loading arrangements which are common to traditional protection against corrosion attack: the unique, PART 2: 1983 for lintels having their own built-in Damp
cavity wall construction sophisticated Duplex double protection system. Proof Course (DPC).

6 Lintel Product Selector Lintel Product Selector 7


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 8

Catnic Lintels
Our rigid adherence to quality control and compliance
is your guarantee of technical superiority

Material
Catnic Cougar and Classic lintels are manufactured from
high quality grade galvanised steel to BS EN 10327:2004
Catnics Cougar Open Back (page 14) lintels are easy to Parts L1 & L2 of the Building Regulations
Approved Documents DX51D & Z275, with a black coloured polyester resin finish.
use profiles allowing masonry to be built up continuously on
both the inner and outer leaves saving time and cost on Catnics lintels comply with the amended Approved
Document L regulations. Catnics compliance illustrates their Damp Proof Course Quality control checks on the incoming steel include:
site. Cougars are fully insulated by moulding expanded
position as technical leaders, always striving for continuous The design of Catnic Cougar open back and combined Dimensional tolerances
polystyrene bead into the CG style lintel, forming a ribbed
improvement in more energy efficient construction practices. box lintels incorporates a built in DPC, and any water Mechanical properties
finish on the underside to provide a plaster key. The rigid
penetrating the cavity automatically transfers across the Thickness
slotted base on CL & CU lintels provides plaster adhesion
Load ratios sloping face of the lintel and is disposed of externally. In Quality of the galvanising
and avoids the hazards of working with mesh.
Safe working loads, as defined by BS 5977: Part 2 for areas of sheltered to medium exposed weather conditions
cavity wall lintels refer to uniform distributed loads there is no need to install a separate DPC. Quality control checks during manufacture include:
Catnics Classic Combined Box (page 24) lintel is a
applied in the inner to outer leaf ratios: Dimensions
robust design which resists twisting during construction
1:1 For lintels supporting masonry only Quality Thickness
and saves on blockwork and installation costs. Classics are
3:1 For lintels normally carrying timber floors Catnic lintels are manufactured to the highest quality and Weld quality
insulated using full height, continuous expanded
5:1 For lintels normally carrying concrete floors are continually assessed both internally and by numerous Quality and accuracy of the black coating
polystyrene board which is secured within the box.
The CL & CU lintel range refers to uniformly distributed external, independent organisations. All quality assurance Insulation
loads in the ratio of 19:1 when non standard or unusual systems comply with BS EN ISO 9001: 2000.
loading conditions occur.

8 Lintel Product Selector Lintel Product Selector 9


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 10

Lintel Selector - Cavity Walls Lintel Selector - All Products

Inner Leaf Cavity Outer Leaf Lintel Codes Application Page


based on 102mm external leaf dimension 100-115 50-65 102 CG50/100, CGH50/100, CLA50/100, Open Back Lintel 18
CLB50/100, CUB50/100, CU50/100 Open Back Lintel
125-140 50-65 102 CG50/125, CGH50/125, CLA50/125, Wide Inner Leaf Open Back Lintel 19
Inner Block size (mm) Cavity 50-65mm Page Cavity 70-85mm Page Cavity 90-105mm Page
CLB50/125, CUB50/125, CU50/125 Wide Inner Leaf Open Back Lintel
001/05-H/GC 100-115 70-85 102 CG70/100, CGH70/100, CLA70/100, Open Back Lintel 20
CG50/100 18 CG70/100 20 CG90/100 22 CLB70/100, CUB70/100, CU70/100 Open Back Lintel
CGH50/100 18 CGH70/100 20 CGH90/100 22
001/05-H/GC 125-140 70-85 102 CG70/125, CGH70/125, CLA70/125, Wide Inner Leaf Open Back Lintel 21
100mm

CLA50/100 - CLB50/100 CLA70/100 - CLB70/100 CLA90/100 - CLB90/100


18 20 22 CLB70/125, CUB70/125, CU70/125 Wide Inner Leaf Open Back Lintel
CUB50/100 - CU50/100 CUB70/100 - CU70/100 CUB90/100 - CU90/100
001/05-UC
100-115 90-105 102 CG90/100, CGH90/100, CLA90/100, Open Back Lintel 22
CN7 25 CN3 26 CN14 27
CN8 25 CN4 26 CLB90/100, CUB90/100, CU90/100 Open Back Lintel
7NC
125-140 90-105 102 CG90/125, CGH90/125, CLA90/125, Wide Inner Leaf Open Back Lintel 23
001/05-UC

CLB90/125, CUB90/125, CU90/125 Wide Inner Leaf Open Back Lintel


000011//0055--HE/G
GCC
CG50/100 18 CG70/100 20 CG90/100 22 100 50-65 102 CN7, CN8 Combined Box Lintel 25
8NC CGH50/100 18 CGH70/100 20 CGH90/100 22 100 70-85 102 CN3, CN4 Combined Box Lintel 26
115mm

001/05-H/GC

CLA50/100 - CLB50/100 CLA70/100 - CLB70/100 CLA90/100 - CLB90/100 115 50-65 102 CN3, CN4 Combined Box Lintel 26
18 20 22
001/05-EGC CUB50/100 - CU50/100 CUB70/100 - CU70/100 CUB90/100 - CU90/100 100 90-105 102 CN14 Combined Box Lintel 27
001/05-UC

CN3 26 CN3* CN4* 26 115 75-90 102 CN14 Combined Box Lintel 27
CN4 26 CN14** 27
7NC 100-115 50 140-150 CN42 Combined Box Lintel Wide Outer Leaf 27
001/05-UC
125 50-65 102 CN43, CN44 Combined Box Lintel Wide Inner Leaf 28
521/05-H/GC

001/05-EGC CG50/125 19 CG70/125 21 CG90/125 23 130 50-55 102 CN43, CN44 Combined Box Lintel Wide Inner Leaf 28
CGH50/125 19 CGH70/125 21 CGH90/125 23 140 50-65 102 CN11, CN12 Combined Box Lintel Wide Inner Leaf 29
125mm

521/058-N
HC/GC

CLA50/125 - CLB50/125 CLA70/125 - CLB70/125 CLA90/125 - CLB90/125 150 50-55 102 CN11, CN12 Combined Box Lintel Wide Inner Leaf 29
19 21 23
001/05-EGC
CUB50/125 - CU50/125 CUB70/125 - CU70/125 CUB90/125 - CU90/125 135-150 75 102 CN57, CN58 Combined Box Lintel Wide Inner Leaf 30
521/05-UC

CN43 28 100-115 50 102 CXL240 Extreme Heavy Duty Lintel 33


CN44 28 100-140 50-70 102 CXL265 Extreme Heavy Duty Lintel 33
34NC

521/05-UC 100-140 70-90 102 CXL290 Extreme Heavy Duty Lintel 33


521/05-H/GC
521/05-EGC
100-115 50-85 N/A CGE50/100 Open Back Eaves Lintel 36
CG50/125 19 CG70/125 21 CG90/125 23
CGH50/125 19 CGH70/125 21 CGH90/125 23 125-140 50-85 N/A CGE50/125 Wide Inner Leaf Open Back Eaves Lintel 36
140mm

44NC

521/05-H/GC
100-115 90-105 N/A CGE90/100 Open Back Eaves Lintel 36
CLA50/125 - CLB50/125 CLA70/125 - CLB70/125 CLA90/125 - CLB90/125
19 23
521/05-EGC
CUB50/125 - CU50/125 CUB70/125 - CU70/125 21 CUB90/125 - CU90/125 125-140 90-105 N/A CGE90/125 Wide Inner Leaf Open Back Eaves Lintel 36
521/05-UC
CN11 29 CN57 30 100 50-75 N/A CN55 Box Eaves Lintel 37
34NC
CN12 29 CN58 30 N/A 50-60 102 CTF5 Timber Frame Lintel 40
521/05-UC
N/A 60-70 102 CTF6 Timber Frame Lintel 40
N/A 70-80 102 CTF7 Timber Frame Lintel 40
* Suitable for5270mm
1/05-EGC cavity only ** Suitable for 75mm-85mm cavity only
N/A 35-60 102 CN23 Timber Frame Lintel 40
44NC

Note: N/A 200-215 CN71, CN81, CN99/394 External Solid Wall 44

The above table represents our standard stock range of cavity wall lintels. For any requirements that fall outside of these N/A 102 CN48, CN49 External Solid Wall 45
521/05-EGC
N/A 102 CNZ94, CNZ95, CNZ96, CNZ97 External Solid Wall 45
parameters please contact Technical Services on 029 2033 7900 for advice on Catnics extensive range of special lintels
N/A 215 CN50, CN51 External Solid Wall 45
75 N/A CN92 Internal Partition Lintel 48
100 N/A CN100, CN102 Internal Partition Lintel 48
100 N/A CN5X, CN6X, CN99/438 Internal Partition Lintel 48
140-150 N/A CN56X, CN66X, CN99/436 Internal Partition Lintel 49

10 Lintel Product Selector Lintel Product Selector 11


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 12

Installing a Cavity Wall Lintel Installing a Lintel Supporting Concrete Floors


521/05UC
Ensure lintel is level along its length.

Ensure a nominal
150mm end bearing
Ensure lintel is
at each end.* Block inner leaf
not damaged. In addition to the cavity wall installation guide, please
read the following for installing concrete floors with
Catnic steel lintels. Concrete floor

Ensure lintel is fully bedded


on bricklaying mortar. Check that the correct lintel is being used according
to the manufacturers lintel schedule/design criteria
Structural opening
or clear span. Bed the lintel on full blocks and allow mortar to cure
before applying concrete floor loads
Ensure lintel is level along its width.
Raise both leaves of cavity wall together and allow
In cavity walls, raise inner and outer leaves
masonry to cure sufficiently before applying heavy
supported by lintel together.
loads. Alternatively prop the lintel if large loads are to
Masonry above lintels should be allowed be applied to fresh masonry
Ensure wall dimensions are correct.
to cure before applying floor or roof loads.
When using the Classic Combined Box Lintel with
* For advice on installations where end bearings concrete floors, always ensure that a mortar joint is 521/07UC
Ensure that masonry overhang does not can be reduced to not less than 100mm, please
exceed 25mm. contact Catnic Technical Services Department
added to the top of the box section/blockwork so that
on 029 2033 7900. the floor units have an even spread over the inner box
of the lintel Lintel
Ensure no more than half the safe working load
(SWL) is carried by the outer leaf where the lintel Brick outer leaf
carries an external cavity wall. The wall should also
be restrained laterally near the top.
Inner Leaf Cavity Outer Leaf Typical Combined Box Lintel, supporting a concrete floor

Additional notes
Do Do not
Install a separate DPC in severe exposure conditions. Use damaged lintels When using the Catnic CL & CU Open back range
A Catnic Cougar Open Back or Classic Combined Box with concrete floors, always ensure that the
Apply point loads without prior consultation. Where the
lintel with an additional DPC membrane installed in blockwork is built tight against the inner vertical face
loading or a substantial part of it is applied as
accordance with normal practice provides the best of the lintel, and that a mortar joint is added to the
concentrated loads, each concentrated load must be
possible protection (page 64)
supported over a length of lintel of not less than 200mm. top of the blockwork so that the floor units have an
Locate the window/door frame so that the drip on the In such cases, the total loading must not produce even spread over the inner flange of the lintel
front of the lintel projects forward of the drip on the front bending moments or shear forces greater than those
of the frame. It is good building practice to insert a produced by the uniformly distributed loads specified in Avoid shock loading lintels during the installation of
flexible joint between the lintel and the top of the frame the relevant data tables Continuous concrete floor units and also any sideways loading
solid infill
while being lifted into position
Ensure that timber floor joists and roof trusses have a
full block depth between them and the lintel flange on
Allow blockwork to overhang the lintel by more
than 25mm
block 521/09UC
Precast flooring units should be laid on a mortar
Cougar Open Back Lintels
Apply concrete floor loads without ensuring that the total bearing of the full inner leaf wall width and should
Refer to the Catnic How to Install a Lintel Supporting loads are checked by a structural engineer, or by Catnic not be dragged over supports
Concrete Floors or the Steel Lintel Manufacturers Technical Services
Association guidelines (available on request) when using Avoid loading newly laid floors with building materials
Do not cut CG or CGH type lintels under any
Classic Combined Box or CL & CU Open Back Lintels to Lintels must be built-in as illustrated, ensuring that the
circumstances
support concrete floors
blockwork infill is well-jointed during construction and
Apply point loads directly on lintel flanges
Consider the use of our soffit cladding for all coastal Catnic CU Open Back Lintel compatible with the strength of the masonry above.
sites (refer to page 63 & 64)

12 Lintel Product Selector Lintel Product Selector 13


8753_Catnic_Lintel_68pp 15/3/05 29/3/05 3:49 pm Page 14

Cavity Wall Lintels


Two styles available for use in cavity wall construction:
Catnic Cougar Open Back lintels & CU lintels
incorporate insulation, built-in plaster key
and built-in DPC.

14 Lintel Product Selector Lintel Product Selector 15