Sunteți pe pagina 1din 1

Loop Simulator The Loop Simulator Professional simulates the

common analog devices to assist maintenance


5. Output Mode Selection
A specific output type can be selected via on-
9. Device Options
- Resolution Step selection
Professional personnel and integrators in analog input testing, screen menus. - Adjustable Sleep timer with Disable Option
troubleshooting and application development. In Current 2-Wire and Current Source modes - Adjustable Screen Dim timer
1. Batteries preconfigured output settings between 4mA and - Adjustable Screen Brightness
The device uses two AA-size Ni-MH rechargeable 20mA are available with 1mA or 0.1mA 10. External Loop Power Considerations
batteries. Alkaline batteries can be used with increments.
2-Wire Current circuit requires an external loop
reduced battery life. Battery Voltage Source mode uses preset values
indicator provides estimated power supply (usually 24VDC).
between 0 and 10V with 1V or 0.1V increments. Some sourcing Analog Input modules can provide
remaining battery capacity.
6. Step Increment Selection (Firmware revision loop power as well. Follow the Analog Input
2. Navigation keys
2015-050 or higher) Module specification for a power supply
The universal set of keys
allows menu navigation and "0.1" or "1.0" steps are selectable under the selection.
parameter changes. Device Options Menu -> Resolution. In Current Source mode, Loop Simulator will
provide the loop power and voltage signal source
3. Turn Device On/Off 7. Calibration Mode allows individual correction using internal boost converter powered by 2 AA
To turn device ON press Cancel key
of each integer (xx.0) output point. Alkaline or rechargeable Ni-MH batteries.
once.
To enter the Calibration Mode press OK after Warning: Selecting Current Source or Voltage
To turn Device OFF press and hold
selecting a desired integer output value. Mode with an externally powered loop can
Cancel key until shutdown message
While in Calibration Mode the specific output damage simulator.
shown, then release Cancel key.
can be corrected using up and down keys.
Power icon will be displayed during In Current Source and Two-Wire modes, Loop
OK will save new values, Cancel will revert to the
countdown. Simulator will monitor the externally provided
Analog Input Tester original settings.
4-20 mA Two-Wire Device Simulator 4. Reset to Factory Defaults voltage. If combined loop voltage over 30V is
Turn device power Off 8. Engineering Unit Scaling allows the simulator detected, device will de-activate output signal
4-20 mA Loop Current Source to display output in engineering units along with
0-10 Volt Source Press and hold OK key, then press and release and HIGH VOLTAGE message will be displayed.
Cancel key. Hold OK during countdown raw current and voltage. Independent scaling Pressing Cancel will re-activate device.
WWW.PLCTOOLS.COM
Release OK when prompted. units are available for current and voltage modes.
Product of USA

SPECIFICATION DISCLAIMER
Current Output 4-20mA Two-Wire Device This device is intended to provide general
4-20mA Current Source assistance with current loop and analog input
Output Range 4mA to 20mA debugging, testing and application development.
Fixed Steps 1mA or 0.1mA increments It should not be permanently used in live
Output Accuracy 1% of full scale at 25C production systems.
Accordingly, production system must be tested
Load Range 0-500 Ohm
and commissioned with calibrated instruments to
Voltage Output 0-10 V Voltage Source ensure safe and reliable operation.
Output Range 0V to 10V
IN NO EVENT SHALL THE DEVICE
Fixed Steps 1V or 0.1V increments MANUFACTURER BE LIABLE FOR ANY DAMAGES
Output Accuracy 1% of full scale at 25C OF ANY KIND INCLUDING DIRECT, INDIRECT,
Minimum Load 20kOhm INCIDENTAL, CONSEQUENTIAL, LOSS OF PROFIT
Protection Reverse Polarity OR DAMAGE.
Over-current (El. Fuse) The examples and diagrams in this manual are
Open Wire (Current) included for illustrative purposes only. Because of
Excessive Loop Voltage the many variables and requirements associated
Output Short (Voltage) with any particular installation, the device
Power Supply manufacturer cannot assume responsibility or
liability for actual use based on the examples and
Internal Power Battery 2xAA
diagrams.
Ni-MH or Alkaline Before making any decision or taking any action
2-Wire Current 12-30V DC External Power that might affect your equipment, you should
Temperature range 0-50C consult a qualified professional advisor.
Important: This device is not a calibrator, it
can't be used for Input module, sensor or
instrument calibration.
Do Not Operate Device Unless Area Is
Non-Hazardous