Sunteți pe pagina 1din 11

CP1H

1
CP1H
Revision History

Revision code Date Revised content


- November 2005 Original production
2 CP1H

1.1. CP1H

1.1.1 CPU Unit Information

CS/CJ SmartActiveparts_E\PLC\
Unit Type Directory Title CPU Unit Information
CP1H CP1H

Function Displays information of the CPU unit.

Display and Operation Details

1
3

Setting/
No. Item Description
Display
1 Unit Information Display Displays the unit type, unit version, and lot No. of the CPU.
Detailed
2 Display Displays revision, PCB revision, software revision, work area, and serial No. of the CPU unit.
Information
3 Details Setting Displays the Detailed Information (2) of the CPU unit.
Remarks

* Use this Smart Active Parts on System Version 6 or later.


* Some items may not be displayed depending on the unit that you use.
1
CP1H

1.1.2 DIP Switch Setting information

CS/CJ SmartActiveparts_E\PLC\
Unit Type Directory Title Dip switch setting
CP1H CP1H

Function Displays the DIP switch settings of the CPU unit.

Display and Operation Details

Setting/
No. Item Description
Display
1 DIP switch No. Display Displays the function of each DIP switch.
Status of
2 Display Displays the current setting of each DIP switch. The white square shows where a switch is set.
DIP switches
Description of Scroll displays the functional description on each DIP switch. Press buttons to scroll the
3 Display
DIP switches display.
Remarks

* Use this Smart Active Parts on System Version 6 or later.


* This Smart Active Parts is used only for monitoring, but not for switching DIP switches.
* SW 1 to 6 are displayed for CP1H, and SW 1 to 8 are displayed for CS/CJ.
2 CP1H

1.1.3 Analog Input Monitor

SmartActiveparts_E\PLC\
Unit Type CP1H-XA Directory Title Analog input monitor
CP1H

Function Displays the present value and status of analog input.

Display and Operation Details

1
3

Setting/
No. Item Description
Display
Setting/
1 Analog Input CH Displays analog input CH. (Changing the label allows you to set any text that you want to display.)
Display
Monitor displays the present value.
2 Present Value Display
Not in use is displayed when an AD is not used.
Disconnection
3 Display A red lamp is lit and Disconnected is displayed when an AD is not connected.
Error Display
Remarks

* Use this Smart Active Parts on System Version 6 or later.


1
CP1H

1.1.4 Analog Output Monitor

SmartActiveparts_E\PLC\
Unit Type CP1H-XA Directory Title Analog output monitor
CP1H

Function Displays the present value and status of analog output.

Display and Operation Details

Setting/
No. Item Description
Display
Setting/
1 Analog Output CH Displays analog output CH. (Changing the label allows you to set any text that you want to display.)
Display
Monitor displays the present value.
2 Present Value Display
Not in use is displayed when an AD is not used.
Remarks

* Use this Smart Active Parts on System Version 6 or later.


2 CP1H

1.1.5 Memory Cassette Transfer

SmartActiveparts_E\PLC\ Titl
Unit Type CP1H Directory Memory cassette transfer
CP1H e

Function Saves, reads, and verifies the memory cassette.

Display and Operation Details

1 3

Setting/
No. Item Description
Display
Select an area to which you transfer the data. Press either a displayed text or a check box. The
1 Target Area Setting
areas with the boxes checked will be the transfer targets.
Transfer to
2 Setting Saves the selected items from the PLC memory to the memory cassette.
Memory Cassette
Transfer from
3 Setting Reads the selected items from the memory cassette to the PLC memory.
Memory Cassette
4 Verification Setting Verifies the selected items in the memory cassette with that of the PLC memory.
Remarks

* Use this Smart Active Parts on System Version 6 or later.


* When PLC operation is in either monitor mode or operation mode, the confirmation dialog whether to switch to program mode will be
displayed before starting transfer or verification. When you do not switch mode (No is selected), the process will not be performed. If mode is
changed, the confirmation dialog whether to switch back to the PLC original operation mode after transfer or verification is completed. If mode
is not switched back to the original operation mode (No is selected), program mode is kept after the process.
* Transfer progress status is displayed in the progress bar.
* A dialog with a red lamp for a mismatched area will be displayed when verification is not matched. Areas with lamp lit are mismatched.
* Please note that the verification mismatch lamp will not be lit when data of both the memory cassette and the PLC are invalid. The lamp is
lit only when one of them is invalid.
* Selected items cannot be verified using an initialized memory cassette. (The error dialog is displayed.)
1
CP1H

1.1.6 Data Memory Default Value Backup

SmartActiveparts_E\PL
Unit Type CP1H Directory Title Data memory default value backup
C\CP1H

Function Saves the default value of data memory to the flash memory built in the CPU unit because it is battery-less operation.

Display and Operation Details

Setting/
No. Item Description
Display
1 Data memory save Setting Saves the default value of data memory to the flash memory of the CPU unit.
Remarks

* Use this Smart Active Parts System Version 6 or later.


* When data in the flash memory is effective the overwrite confirmation dialog is displayed. Data will be saved by pressing Yes. When data
is not effective, data memory will be saved without the dialog displayed.
* Saving process status is displayed in the progress bar.
2 CP1H

1.1.7 Analog Volume

SmartActiveparts_E\PLC\
Unit Type CP1H Directory Title Analog volume monitor
CP1H

Function Displays the present value of analog volume.

Display and Operation Details

1
2

Setting/
No. Item Description
Display
Setting/
1 Analog Volume Displays analog volume. (Changing the label allows you to set any text that you want to display.)
Display
2 Present Value Display Displays the present value in decimal format and always monitors it
Remarks

* Please note that the 7 segment LEDs at the front of CP1H are displayed in hexadecimal format while they are displayed in decimal format
on this Smart Active Parts.
1
CP1H

1.1.8 External Analog Setting Input Monitor

SmartActiveparts_E\PL
Unit Type CP1H Directory Title External analog setting input monitor
C\CP1H

Function Displays the present value of external analog setting input.

Display and Operation Details

1
2

Setting/
No. Item Description
Display
External Analog Setting/ Displays external analog setting input. (Changing the label allows you to set any text that you want
1
Setting Input Display to display.)
2 Present Value Display Displays the present value in decimal format and always monitors it
Remarks
2 CP1H

1.1.9 Error Log

CS/CJ SmartActiveparts_E\PLC\
Unit Type Directory Title Error log
CP1H CP1H

Function Displays CPU error log.

Display and Operation Details

2 3 4 5

Setting/
No. Item Description
Display
Displays two error logs; the latest one is on the upper side. Up to 20 logs can be displayed by
switching pages.
Current error: This lamp indicates that there is an error occurred. To display the latest information,
press the Read button.
1 Error Log Display
Date & Time: Displays the date and time when an error occurred.
Error content: Displays error content.
Error code: Displays a failure code.
Detail code: Displays a code for the error content.
Displays the error history on the previous page (newer error)
2 Previous Page Setting
Cannot be used when the latest error is displayed.
Displays the error history on the next page (older error)
3 Next Page Setting
Cannot be used when the oldest error is displayed.
4 Read Setting Reads error histories and displays them in order from the latest one.
5 Clear Error Setting Clears error histories.
Remarks

* Use this Smart Active Parts on System Version 6 or later.


* This Smart Active Parts cannot be used with CS1D. (Duplex error is not displayed).