Project Name : Mullins

System : 1 Zone : 1 Room : Main Living Area


Niles, Mich, United States

SOUTH BEND, MICHIANA REGIONAL AP, INDIANA

Summer Outdoor F: 88.0 Summer Indoor F: 75 Design Grains: 33 Daily Range: MEDIUM

Winter Outdoor F: 5.0 Winter Indoor F: 70 Cooling RH: 50% Elevation (Ft): 774

Cooling Loads
Duct Name Area Sensible Latent
Windows
14.8% Windows & Glass Doors 231 1,878 0
19.1%
Skylights 0 0 0
Doors 80 603 0
Doors Above Grade Walls 1,728 1,356 0
6.1% Floors 0 0 0
Internal Ceiling 1,872 1,872 0
24.4% Above Grade
Ventilation 0 0 0
Walls
Infiltration 0 273 0
13.8%
Internal 0 2,400 0
Infiltration Duct 0 1,459 0
2.8% Ceiling
Blower Heat 0 0 0
19% AED Excursion 0 0 0

Total 3,911 9,841 0

Heating Loads
Name Area Heat Loss
Doors
Windows & Glass Doors 231 0
Duct 8.8%
Skylights 0 0
22.8%
Doors 80 1,508
Above Grade Walls 1,728 6,627
Below Grade Walls 1,476 0
Above Grade Ceiling 1,872 2,434
Walls Ventilation 0 0
Infiltration 38.5% Infiltration 0 2,732
15.9% Internal 0 0
Floors 0 0
Ceiling Duct 0 3,924
14.1% Humidification 0 0
Hot Water Piping 0 0

Total 5,387 17,224

AED Graph

4,000
Approved ACCA MJ8
HTM
Calculations
Average
3,000 Average
* 1.3
Btuh

2,000
Calculations are based on the ACCA Manual J 8th Edition and
are approved by ACCA. All computed calculations are
1,000 estimates on building use, weather data, and inputted values
such a R-Values, window types, duct loss, etc. Equipment
selections should meet both the latent and sensible gain as
0 well as building heat loss. See Cool Calc Manual S Report for
8 9 10 11 12 13 14 15 16 17 18 19 equipment sizing verification.
Hours

Prepared by: Cool Calc Version 1.0.0 Beta - www.coolcalc.com