Internal partitioning
Forms of internal separation Protection against direct contact Typical forms of internal separation
to IEC/EN 60439-1 with hazardous parts belonging to are differentiated depending on how
the functional unit (degree of the compartment or subsection is
protection must be at least IP XXB). constructed:
Low-voltage switchgear assemblies
can be divided by means of partitions Limitation of possibility of fault arc
or barriers into seperate occurrence.
compartments or enclosed protected Protection against the passage of
spaces. The aim of forming seperate solid foreign bodies from one
compartments or enclosed protected functional unit into an adjacent one
spaces which contain the functional (degree of protection shall be at
units is: least IP 2X).
Form 1
Possible with MODAN P, F, R, W
and G
No internal separation
Form 2a
Possible with MODAN P, F, R, W The terminals of external
and G with Form 2b conductors do not need to be
separated from the busbars.
Separation of busbars from the
functional units
Form 2b
Possible with MODAN P, F, R, W The terminals for external
and G conductors need to be separated
from the busbars.
Separation of busbars from the
functional units
46 01/03 TB46-015GB
Supplementary information
Internal partitioning
Form 3a
Form 3b
Possible with MODAN P, R1) and W The terminals for external
conductors need to be separated
Separation of the terminals for
from the busbars.
external conductors from functional
units, but not from one another
Form 4a
Possible with MODAN P, F and R1) Terminals for external conductors
which are an integral part of the
Internal separation between
functional unit
busbars and functional units as well
as functional units among one
another, including the terminals for
external conductors which are an
integral part of the functional unit
Form 4b
Possible with MODAN P and R2) Terminals for external conductors
which are not an integral part of the
Internal separation between
functional unit, which however are
busbars and functional units as well
in an individual, separate, enclosed
as functional units among one
protected space or compartment
another, including the terminals for
external conductors which are an
integral part of the functional unit
1) only with SSL and SSKL switch-fuse units and P removable compartments
2) only with SSL and SSKL switch-fuse units
The form of separation and higher reasons, switching cannot be carried withdrawable modules), are equipped
degrees of protection (where greater out unless the installation is live. as standard with a higher form of
than IP2X or IPXX B) shall be agreed Depending on operational separation, such as Form 3b, for
between the manufacturer and the requirements, the distribution example. Separation in accordance
end user. Internal separation is used sections can optimally be designed with Form 2b, i.e. separation between
for the protection of personnel and of with various Forms of separation. busbars and functional units, is
the system where work is being Distribution sections, which should recommended in every case.
carried out on the switchgear permit straightforward removal of
assembly, and where for operational functional units (such as those with