Sub Station Vertical Break Disconnector

The ABB Series R single break, insulator Terminals


operated disconnector has been designed Termination arrangements comply with the
for both rural distribution and substation requirements of AS2395-1980
type disconnector applications and
complying with Australian Standard AS1306 Mounting
(1985) and IEC 129. The Vertibreak disconnector is suitable for horizontal
pole top mounting as well as horizontal or vertical
Features mounting in a mid-pole situation. The 12kV/24k V
Simple robust design with minimum disconnector is designed to be mounted on a single
moving parts. steel angle across phase bearer. Either horizontal or
Elimination of pantograph joints. vertical mounting can be effected using the same pole
Reduced interphase clearance. bracket and fittings.
Minimal maintenance to current
carrying parts For 36kV applications double across phase bearers
High through fault rating. can be used.
Minimum operating effort. The Vertibreak range is readily adaptable for
Suitable for wood or concrete pole substation structure mounting.
or steel structure mounting.
Operating Equipment
Insulators Standard operating equipment options include:
The disconnector is fitted with single piece 50mm x 50mm fibre glass operating downrods.
non-puncturable porcelain insulators Hinged intermediate supports with
coloured munsell grey. fibre glass/pipe or pipe/pipe clevis
connections.
Current Carrying Assembly

Current carrying parts are manufactured


from HD HC copper with up to 2000 amp
continuous rating. Moving contacts have
lead in feature and straight parallel sides to
ensure low effort operation, reduce plating
wear and ensure contact alignment during
closing operation. The hinge end is
designed with seperate contacts so that the
current path is not through the joint, and to
provide blade alignment during the closing
operation.

ABB Power Distribution


SERIES R
Sub Station Vertical Break Disconnector

1600/2000A CONTACT ARRANGEMENT


25 NB galvanised pipe downrod runners. Arcing Contacts are suitable for distribution applications
Operating handle with provision for where limited interrupting capacity is required such as
padlocking in the OPEN or CLOSED de-energising short lengths of lines or switching
positions. The handle also features transformer magnetising currents.
earthing termination stud.
b. EZIBREAK Interrupters
Operating accessories are suitable for
These units provide reliable interruption of currents
attachment to either wood or concrete
beyond the range of Flicker arcing contacts such
poles.
as magnetising current of larger transformers, loop
currents and medium to long lengths of distribution
Load Breaking lines as well as normal load currents.
The following alternatives are available:
a. Arcing Contacts
Flicker type (quick break) Arcing
Contacts are manufactured of stainless
steel rod.

Technical Schedule
RATED
VOLTAGE U kV 12 24 36
RATED LIGHTNING
IMPULSE UL kVp 125 170 200
WITHSTAND VOLTAGE
RATED In A 800 1250 1600 2000 800 1250 1600 2000 800 1250 1600 2000
CURRENT
NUMBER OF OPERATIONS
WITH MAINLY ACTIVE _ Unit 15 15 15 15 15 15 15 15 15 15 15 15
LOAD
RATED SHORT TIME Ith kA 25 20 25 20 31.5 31.5 31.5 31.5 25 20 25 20 31.5 31.5 31.5 31.5 25 20 25 20 31.5 31.5 31.5 31.5
WITHSTAND CURRENT

RATED DURATION OF
tth S 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3
SHORT CIRCUIT

MASS M Kg 76 81 85 90 81 86 90 95 182 182 197 197

ABB Power Distribution


SERIES R
Sub Station Vertical Break Disconnector

*NOTE
Individual Phase Assemblies
mounted at 750mm centres.

ABB Power Distribution


Bapaume Road
Moorebank, NSW 2170
CAT NO. AU 3425