Sunteți pe pagina 1din 818

N:N Network

Parallel Link
Computer Link
Inverter Communication
Non-Protocol Communication
Programming Communication
Remote Maintenance

FX SERIES PROGRAMMABLE CONTROLLERS

USER'S MANUAL

Data Communication Edition

RS-232C Interface
FX3U-232-BD FX1N-232-BD
FX3U-232ADP(-MB) FX0N-232ADP
FX3G-232-BD FX-232ADP
FX2N-232-BD FX2N-232IF
FX2NC-232ADP
RS-485 Interface
FX3U-485-BD FX2NC-485ADP
FX3U-485ADP(-MB) FX1N-485-BD
FX3G-485-BD FX0N-485ADP
FX3G-485-BD-RJ FX-485ADP
FX2N-485-BD
RS-485/232C Converter
FX-485PC-IF
RS-422 Interface
FX3U-422-BD FX2N-422-BD
FX3G-422-BD FX1N-422-BD
USB Interface
FX3U-USB-BD
Ethernet
FX3U-ENET-ADP
Safety Precaution
(Read these precautions before use.)

Before installation, operation, maintenance or inspection of this product, thoroughly read through and understand
this manual and all of the associated manuals. Also, take care to handle the module properly and safely.
This manual classifies the safety precautions into two categories: and .

Indicates that incorrect handling may cause hazardous conditions, resulting in


death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting in


medium or slight personal injury or physical damage.

Depending on the circumstances, procedures indicated by may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it
to the end user.

1. DESIGN PRECAUTIONS

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the service power supply for sensors varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
To maintain the safety of the programmable controller system against unauthorized access from external devices
via the network, take appropriate measures. To maintain the safety against unauthorized access via the Internet,
take measures such as installing a firewall.

Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
Install module so that excessive force will not be applied to the built-in programming port, power connectors, I/O
connectors, communication connectors, or communication cables.
Failure to do so may result in wire damage/breakage or PLC failure.

(1)
Safety Precaution
(Read these precautions before use.)

2. WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.

Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due
to abnormal data written to the PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the PLC. However, do not use common
grounding with heavy electrical systems.
Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

3. STARTUP AND MAINTENANCE PRECAUTIONS

Do not touch any terminal while the PLC's power is on.


Doing so may cause electric shock or malfunctions.
Before cleaning or retightening terminals, cut off all phases of the power supply externally.
Failure to do so may cause electric shock.
Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual
and the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
Do not change the program in the PLC from two or more peripheral equipment devices at the same time.
(i.e. from a programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.

Do not disassemble or modify the PLC.


Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
Turn off the power to the PLC before connecting or disconnecting any extension cable.
Failure to do so may cause equipment failures or malfunctions.
Turn of the power to the PLC before attaching or detaching the peripheral devices, expansion boards, special
adapters, and expansion memory cassette.
Failure to do so may cause equipment failures or malfunctions.

(2)
FX Series PLC User's Manual - Data Communication Edition

FX Series Programmable Controllers


User's Manual [Data Communication Edition]

Manual number JY997D16901


Manual revision N
Date 7/2016

Foreword
This manual explains the "serial communication" provided for MELSEC-F FX Series Programmable
Controllers and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

1
FX Series PLC User's Manual - Data Communication Edition

Outline Precautions
This manual provides information for the use of the FX Series Programmable Controllers. The manual has
been written to be used by trained and competent personnel. The definition of such a person or persons is
as follows:
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety aspects regarding to automated equipment.
2) Any commissioning or maintenance engineer must be of a competent nature, trained and qualified to
the local and national standards required to fulfill the job. These engineers should also be trained in
the use and maintenance of the completed product. This includes being familiar with all associated
manuals and documentation for the product. All maintenance should be carried out in accordance with
established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance with established safety practices. The operators should also be
familiar with documentation that is connected with the actual operation of the completed equipment.
Note: The term 'completed equipment' refers to a third party constructed device that contains or uses the
product associated with this manual
This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions into the system.
When combining this product with other products, please confirm the standards and codes of regulation to
which the user should follow. Moreover, please confirm the compatibility of this product with the system,
machines, and apparatuses to be used.
If there is doubt at any stage during installation of the product, always consult a professional electrical
engineer who is qualified and trained in the local and national standards. If there is doubt about the
operation or use, please consult your local Mitsubishi Electric representative.
Since the examples within this manual, technical bulletin, catalog, etc. are used as reference; please use it
after confirming the function and safety of the equipment and system. Mitsubishi Electric will not accept
responsibility for actual use of the product based on these illustrative examples.
The content, specification etc. of this manual may be changed for improvement without notice.
The information in this manual has been carefully checked and is believed to be accurate; however, if you
notice any doubtful point, error, etc., please contact your local Mitsubishi Electric representative.

Registration
Microsoft, Windows, Windows NT and Windows Vista are either registered trademarks or trademarks
of Microsoft Corporation in the United States and/or other countries.
MODBUS is the registered trademark of Schneider Electric SA.
Ethernet is a trademark of Xerox Corporation.
PC-9800 is the registered trademark of NEC Corporation.
Anywire and ANYWIREASLINK is a trademark of Anywire Corporation.
LONWORKS is a registered trademark of Echelon Corporation in the United States and/or other
countries.
DeviceNet is a trademark of ODVA (Open DeviceNet Vender Association, Inc.).
Phillips is a registered trademark of Phillips Screw Company.
Short Mail are trademarks or registered trademarks of NTT DOCOMO, INC.
The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.

2
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

Table of Contents
SAFETY PRECAUTIONS .................................................................................................. (1)

A.Common Items

1. Introduction A-1

1.1 Communication Types .................................................................................................................A-1


1.2 Outline and Features of Communication Types...........................................................................A-3
1.2.1 CC-Link Network ..........................................................................................................................A-3
1.2.2 Ethernet communication...............................................................................................................A-6
1.2.3 N:N Network .................................................................................................................................A-7
1.2.4 Parallel Link ..................................................................................................................................A-8
1.2.5 Computer Link ..............................................................................................................................A-9
1.2.6 Inverter Communication .............................................................................................................A-10
1.2.7 Non-protocol Communication .....................................................................................................A-11
1.2.8 MODBUS Communication..........................................................................................................A-12
1.2.9 Programming Communication ....................................................................................................A-13
1.2.10 Remote Maintenance ...............................................................................................................A-16
1.2.11 CC-Link/LT Network .................................................................................................................A-17
1.2.12 AnyWireASLINK .......................................................................................................................A-18
1.2.13 AS-i system ..............................................................................................................................A-19
1.2.14 Internet Mail Sending................................................................................................................A-20
1.2.15 Short Mail Sending ...................................................................................................................A-21

2. Communication Types and Communication Equipment A-23

2.1 Relationship between Equipment and Communication Types...................................................A-23


2.2 Communication Equipment Applicability Map ............................................................................A-24
2.2.1 FX3U and FX3UC (D, DS, DSS) PLCs........................................................................................A-24
2.2.2 FX3UC-32MT-LT(-2) PLCs .........................................................................................................A-28
2.2.3 FX3G and FX3GC PLCs..............................................................................................................A-30
2.2.4 FX3S PLC ...................................................................................................................................A-32
2.2.5 FX2N and FX2NC PLCs ..............................................................................................................A-34
2.2.6 FX1S, FX1N, and FX1NC PLCs...................................................................................................A-36
2.2.7 FX0N PLCs .................................................................................................................................A-38
2.2.8 FX1, FX2(FX), FX2C, FX0 and FX0S PLCs (reference)..............................................................A-38
2.3 Combination of Communication Equipment (Block Diagram) ....................................................A-40
2.3.1 How to look at combination pages..............................................................................................A-40
2.3.2 For FX3U Series .........................................................................................................................A-41
2.3.3 For FX3UC(D, DS, DSS) Series..................................................................................................A-43
2.3.4 For FX3UC-32MT-LT(-2) ............................................................................................................A-45
2.3.5 For FX3G Series .........................................................................................................................A-47
2.3.6 For FX3GC Series.......................................................................................................................A-50
2.3.7 For FX3S Series .........................................................................................................................A-52
2.3.8 For FX2N Series .........................................................................................................................A-53
2.3.9 For FX2NC Series .......................................................................................................................A-55
2.3.10 For FX1N Series .......................................................................................................................A-57
2.3.11 For FX1NC Series .....................................................................................................................A-59
2.3.12 For FX1S Series .......................................................................................................................A-61
2.3.13 For FX0N Series .......................................................................................................................A-62
2.3.14 For FX2(FX) and FX2C Series (reference) ...............................................................................A-64

3
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

3. Outline of Communication Setting in the FX Series A-65

3.1 Setting Method ...........................................................................................................................A-65


3.2 Communication Setting Using Parameter Method (GX Works2) ...............................................A-67
3.2.1 Operating procedure...................................................................................................................A-67
3.2.2 Correspondence between parameter setting and each communication type.............................A-68
3.3 Communication Setting in Parameter Method (FXGP/WIN) ......................................................A-69
3.3.1 Operating procedure...................................................................................................................A-69
3.3.2 Correspondence between parameter setting and each communication type.............................A-71
3.4 Extension of Ports (For FX3G, FX3GC, FX3U, FX3UC) ..............................................................A-72
3.4.1 Extension of Port (For FX3G, FX3GC PLC) ................................................................................A-72
3.4.2 Extension of Port (For FX3U, FX3UC PLC).................................................................................A-74
3.4.3 Limitation when ch1 and ch2 are used at the same time ...........................................................A-75

4. Version Number A-76

4.1 Manufacturer's serial number check method .............................................................................A-76


4.1.1 Checking the nameplate.............................................................................................................A-76
4.1.2 Checking the front of the product ...............................................................................................A-77
4.2 Version check.............................................................................................................................A-77

5. Introduction of Manuals (Type, Reading Method and Acquisition Method) A-78

5.1 Rank and Use Method of This Manual.......................................................................................A-78


5.2 Introduction of Related Manuals ................................................................................................A-79
5.2.1 Manual for communication types in FX PLCs.............................................................................A-79
5.2.2 Manuals related to FX PLCs.......................................................................................................A-79
5.2.3 Communication equipment (option)............................................................................................A-82
5.2.4 Related options for communication ............................................................................................A-84

6. Abbreviations, Generic Names and Terms Used in This Manual A-85

4
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

B. N:N Network

1. Outline B-3

1.1 Outline of System.........................................................................................................................B-3


1.2 Procedures Before Operation ......................................................................................................B-4
1.3 Communication Type Applicability in PLC ...................................................................................B-5
1.3.1 Applicable versions.......................................................................................................................B-5
1.3.2 Version check ...............................................................................................................................B-5
1.3.3 How to look at the manufacturer's serial number .........................................................................B-5
1.3.4 Products whose production was stopped .....................................................................................B-5
1.4 Programming Tool Applicability....................................................................................................B-6
1.4.1 For applicable versions.................................................................................................................B-6
1.4.2 For non-applicable versions (setting an alternative model) ..........................................................B-8

2. Specifications B-9

2.1 Communication Specifications (Reference) .................................................................................B-9


2.2 Link Specifications .....................................................................................................................B-10
2.2.1 Link patterns and number of link points in each FX Series ........................................................B-10
2.2.2 Link time .....................................................................................................................................B-11

3. System Configuration and Equipment Selection B-12

3.1 System Configuration.................................................................................................................B-12


3.2 Applicable FX PLC and Communication Equipment..................................................................B-13

4. Wiring B-18

4.1 Wiring Procedure .......................................................................................................................B-18


4.2 Selecting Cables and Terminal Resistors ..................................................................................B-19
4.2.1 Twisted pair cable.......................................................................................................................B-19
4.2.2 10BASE-T cable .........................................................................................................................B-19
4.2.3 Connecting cables ......................................................................................................................B-20
4.2.4 Connecting terminal resistors .....................................................................................................B-22
4.3 Connection Diagram ..................................................................................................................B-23
4.4 Grounding ..................................................................................................................................B-25

5. Communication Setting (Initialization) in FX Programmable Controller B-26

5.1 Check Procedure .......................................................................................................................B-26


5.2 Communication Setting Using Parameter Method (GX Works2) ...............................................B-27
5.2.1 Operating procedure...................................................................................................................B-27
5.3 Communication Settings Using Parameter Method (FXGP/WIN) ..............................................B-28
5.3.1 Operating procedure...................................................................................................................B-28

6. Test Run (Communication Test) B-29

6.1 Test Procedure...........................................................................................................................B-29


6.2 Creating Programs for the Communication Testing ...................................................................B-31
6.2.1 Creating a program for the master station..................................................................................B-31
6.2.2 Creating a program for each slave station..................................................................................B-32

5
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

7. Creating Programs B-33

7.1 Checking Contents of Related Devices......................................................................................B-33


7.2 Creating Programs for Master Station (Station No. 0) ...............................................................B-35
7.3 Creating Programs for Slave Station (Station No. "n")...............................................................B-38
7.4 Cautions on Program Creation...................................................................................................B-40

8. Practical Program Examples B-41

8.1 Practical Example 1 (Pattern 2) .................................................................................................B-41


8.1.1 System configuration example ...................................................................................................B-41
8.1.2 Contents of operations and corresponding program numbers ...................................................B-41
8.1.3 Setting contents..........................................................................................................................B-42
8.1.4 Setting program for master station .............................................................................................B-42
8.1.5 Setting program for slave station (No. 1)....................................................................................B-44
8.1.6 Setting program for slave station (No. 2)....................................................................................B-46

9. Troubleshooting B-48

9.1 Checking FX PLC Version Applicability .....................................................................................B-48


9.2 Checking Communication Status Based on LED Indication ......................................................B-48
9.3 Checking Installation and Wiring................................................................................................B-48
9.4 Checking Sequence Program ....................................................................................................B-48
9.5 Checking Setting Contents and Errors.......................................................................................B-50
9.6 Checking Absence/Presence of Data Transfer Errors ...............................................................B-50
9.6.1 Check while data transfer sequence is being executed .............................................................B-50
9.6.2 Checking data transfer sequence errors ....................................................................................B-51
9.6.3 Checking error codes .................................................................................................................B-51

10. Related Data B-54

10.1 Related Device List ..................................................................................................................B-54


10.1.1 For FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs....................B-54
10.1.2 For FX0N and FX1S PLCs ........................................................................................................B-58
10.2 Details of Related Devices .......................................................................................................B-60
10.2.1 Parameter setting [M8038] .......................................................................................................B-60
10.2.2 Channel setting [M8179]...........................................................................................................B-60
10.2.3 Serial communication error [M8063 and M8438]......................................................................B-60
10.2.4 Data transfer sequence error [M8138 to M8190] [M504 to M511]............................................B-61
10.2.5 Data transfer sequence ON [M8191] [M503]............................................................................B-61
10.2.6 Serial communication error code [D8063 and D8438]..............................................................B-61
10.2.7 Corresponding station number settings status [D8173]............................................................B-62
10.2.8 Slave station quantity setting status [D8174]............................................................................B-62
10.2.9 Refresh range setting status [D8175] .......................................................................................B-62
10.2.10 Station number settings [D8176] ............................................................................................B-62
10.2.11 Slave station quantity setting [D8177] ....................................................................................B-63
10.2.12 Refresh range setting [D8178]................................................................................................B-63
10.2.13 Number of retries [D8179] ......................................................................................................B-64
10.2.14 Monitoring time setting [D8180]..............................................................................................B-64
10.2.15 Present link scan time [D8201] [D201] ...................................................................................B-64
10.2.16 Maximum link scan time [D8202] [D202] ................................................................................B-65
10.2.17 Data transfer sequence error count [D8203 to D8210] [D203 to D210] .................................B-65
10.2.18 Data transfer error code [D8211 to D8218] [D211 to D218] ...................................................B-66
10.2.19 Operation mode display [D8419 and D8439] .........................................................................B-67

6
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

C. Parallel Link

1. Outline C-3

1.1 Outline of System........................................................................................................................ C-3


1.2 Procedures Before Operation ..................................................................................................... C-4
1.3 Communication Type Applicability in PLC .................................................................................. C-5
1.3.1 Applicable versions...................................................................................................................... C-5
1.3.2 Version check .............................................................................................................................. C-5
1.3.3 Products whose production was stopped .................................................................................... C-5
1.4 Programming Tool Applicability................................................................................................... C-6
1.4.1 For applicable versions................................................................................................................ C-6
1.4.2 For non-applicable versions (setting an alternative model) ......................................................... C-8

2. Specifications C-9

2.1 Communication Specifications (Reference) ................................................................................ C-9


2.2 Link Specifications .................................................................................................................... C-10
2.2.1 PLC communication type applicability status ............................................................................ C-10
2.2.2 Link time .................................................................................................................................... C-10
2.3 Link Device Numbers and Number of Points ............................................................................ C-11
2.3.1 For FX0N, FX1S and FX3S Series ............................................................................................. C-11
2.3.2 For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U and FX3UC Series.... C-12

3. System Configuration and Selection C-13

3.1 System Configuration................................................................................................................ C-13


3.1.1 Rule for connection.................................................................................................................... C-13
3.2 Configuration of Each Group..................................................................................................... C-14
3.3 Applicable FX PLC and Communication Equipment................................................................. C-18

4. Wiring C-24

4.1 Wiring Procedure ...................................................................................................................... C-24


4.2 Selecting Cables and Terminal Resistors ................................................................................. C-25
4.2.1 Twisted pair cable...................................................................................................................... C-25
4.2.2 10BASE-T cable ........................................................................................................................ C-25
4.2.3 Connecting cables ..................................................................................................................... C-26
4.2.4 Optical fiber cable...................................................................................................................... C-27
4.2.5 Connecting terminal resistors .................................................................................................... C-28
4.3 Connection Diagram ................................................................................................................. C-29
4.3.1 For FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs .................................................................... C-29
4.3.2 For FX1S, FX1N, FX1NC, FX2N and FX2NC PLCs .................................................................... C-30
4.3.3 For FX2(FX) and FX2C PLCs .................................................................................................... C-31
4.4 Grounding ................................................................................................................................. C-31

5. Communication Setting (Initialization) in FX Programmable Controller C-32

5.1 Check Procedure ...................................................................................................................... C-32


5.2 Communication Setting Using Parameter Method (GX Works2) .............................................. C-33
5.2.1 Operating procedure.................................................................................................................. C-33
5.3 Communication Setting Using Parameter Method (FXGP/WIN)............................................... C-34
5.3.1 Operating procedure.................................................................................................................. C-34

7
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

6. Test Run (Communication Test) C-35

6.1 Test Procedure.......................................................................................................................... C-35


6.2 Creating Programs for the Communication Test....................................................................... C-36
6.2.1 For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U or FX3UC Series....... C-36
6.2.2 For FX0N, FX1S or FX3S Series ................................................................................................ C-37

7. Creating Programs C-38

7.1 Regular Parallel Link Mode ....................................................................................................... C-38


7.1.1 Checking contents of related devices........................................................................................ C-38
7.1.2 Creating programs for master station ........................................................................................ C-40
7.1.3 Creating programs for slave station........................................................................................... C-41
7.2 High Speed Parallel Link Mode................................................................................................. C-42
7.2.1 Checking contents of related devices........................................................................................ C-42
7.2.2 Creating programs for master station ........................................................................................ C-44
7.2.3 Creating programs for slave station........................................................................................... C-45
7.3 Cautions on Program Creation.................................................................................................. C-46

8. Practical Program Examples C-47

8.1 Practical Example 1 (Regular Parallel Link Mode).................................................................... C-47


8.1.1 System configuration example .................................................................................................. C-47
8.1.2 Setting contents......................................................................................................................... C-47
8.1.3 Program for master station ........................................................................................................ C-48
8.1.4 Program for slave station........................................................................................................... C-48

9. Troubleshooting C-49

9.1 Checking FX PLC Version Applicability .................................................................................... C-49


9.2 Checking Communication Status Based on LED Indication ..................................................... C-49
9.3 Checking Installation and Wiring............................................................................................... C-49
9.4 Checking Sequence Program ................................................................................................... C-49
9.5 Checking Absence/Presence of Errors ..................................................................................... C-51

10. Related Data C-52

10.1 Related Device List ................................................................................................................. C-52


10.2 Details of Related Devices ...................................................................................................... C-53
10.2.1 Parallel link master station declare [M8070]............................................................................ C-53
10.2.2 Channel setting [M8178].......................................................................................................... C-53
10.2.3 Parallel link slave station declare [M8071] .............................................................................. C-53
10.2.4 High-speed parallel link mode [M8162] ................................................................................... C-53
10.2.5 Parallel link ON [M8072].......................................................................................................... C-54
10.2.6 Parallel link setting error [M8073] ............................................................................................ C-54
10.2.7 Serial communication error [M8063 and M8438]..................................................................... C-54
10.2.8 Error judgement time setting [D8070]...................................................................................... C-54
10.2.9 Serial communication error code [D8063 and D8438]............................................................. C-55
10.2.10 Operation mode display [D8419 and D8439] ........................................................................ C-55

8
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

D. Computer Link

1. Outline D-3

1.1 Outline of System........................................................................................................................ D-3


1.2 Procedures Before Operation ..................................................................................................... D-4
1.3 Communication Type Applicability in PLC .................................................................................. D-5
1.3.1 Applicable versions...................................................................................................................... D-5
1.3.2 Version check .............................................................................................................................. D-5
1.3.3 How to look at the manufacturer's serial number ........................................................................ D-5
1.3.4 Products whose production was stopped .................................................................................... D-5
1.4 Programming Tool Applicability................................................................................................... D-6
1.4.1 For applicable versions................................................................................................................ D-6
1.4.2 For non-applicable versions (setting an alternative model) ......................................................... D-8

2. Specifications D-9

2.1 Communication Specifications (Reference) ................................................................................ D-9


2.2 Link Specifications .................................................................................................................... D-10
2.2.1 Applicable commands and number of device points ................................................................. D-10
2.2.2 Applicable device ranges........................................................................................................... D-11
2.2.3 Link time .................................................................................................................................... D-13

3. System Configuration and Equipment Selection D-14

3.1 System Configuration................................................................................................................ D-14


3.2 Applicable FX PLC and Communication Equipment................................................................. D-15
3.2.1 For communication in accordance with RS-232C ..................................................................... D-15
3.2.2 For communication in accordance with RS-485 ........................................................................ D-21

4. Wiring D-27

4.1 Wiring Procedure ...................................................................................................................... D-28


4.2 Selecting Connection Method ................................................................................................... D-29
4.2.1 For communication in accordance with RS-232C (1-to-1 connection) ...................................... D-29
4.2.2 For communication in accordance with RS-485 (RS-422) (1-to-N connection)......................... D-29
4.3 Selecting Cables and Terminal Resistors (RS-485).................................................................. D-30
4.3.1 Twisted pair cable...................................................................................................................... D-30
4.3.2 10BASE-T cable ........................................................................................................................ D-30
4.3.3 Connecting cables ..................................................................................................................... D-31
4.3.4 Connecting terminal resistors .................................................................................................... D-33
4.4 Connection Diagram for RS-232C ............................................................................................ D-34
4.4.1 Connection diagram between FX PLC and personal computer ................................................ D-34
4.4.2 Connection diagram between FX-485PC-IF and personal computer........................................ D-34
4.5 Connection Diagram for RS-485 and RS-422........................................................................... D-35
4.5.1 One-pair wiring .......................................................................................................................... D-35
4.5.2 Two-pair wiring .......................................................................................................................... D-37
4.5.3 Switching of 1 pair / 2 paired wiring (FX3G-485-BD-RJ) ........................................................... D-39
4.6 Grounding ................................................................................................................................ D-39

9
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

5. Communication Setting in FX Programmable Controller D-40

5.1 Communication Setting Methods .............................................................................................. D-40


5.2 Communication Setting Using Parameter Method (GX Works2) .............................................. D-41
5.2.1 Operating procedure.................................................................................................................. D-41
5.3 Communication Settings Using Parameter Method (FXGP/WIN) ............................................. D-43
5.3.1 Operating procedure.................................................................................................................. D-43

6. Control Procedures and Setting Methods D-45

6.1 Data Flow by Link...................................................................................................................... D-45


6.2 Important Points in Computer Link............................................................................................ D-46
6.2.1 Operations of PLC caused by data transfer .............................................................................. D-46
6.3 How to Understand Control Procedure ..................................................................................... D-47
6.4 Basic Formats of Dedicated Protocol........................................................................................ D-47
6.4.1 Control procedure format 1........................................................................................................ D-48
6.4.2 Control procedure format 4........................................................................................................ D-49
6.4.3 Contents of set items in each control procedure (protocol) ....................................................... D-50
6.4.4 Time-out time setting ................................................................................................................. D-53
6.5 Transfer Sequence Time Chart and Communication Time....................................................... D-54
6.5.1 When computer reads data from PLC ....................................................................................... D-54
6.5.2 When computer writes data to PLC........................................................................................... D-54
6.5.3 Transfer time in transfer sequence............................................................................................ D-55
6.6 Transfer Data in Character Area ............................................................................................... D-56
6.6.1 When bit device memory is read or written ............................................................................... D-56
6.6.2 When word device memory is read or written ........................................................................... D-57

7. Commands D-58

7.1 BR Command [Reads Device Memory in 1-Bit Units]............................................................... D-59


7.2 WR Command [Reads Device Memory in 1-Word Units] ......................................................... D-60
7.3 QR Command [Reads Device Memory in 1-Word Units] .......................................................... D-62
7.4 BW Command [Writes Device Memory in 1-Bit Units] .............................................................. D-64
7.5 WW Command [Writes Device Memory in 1-Word Units]......................................................... D-65
7.6 QW Command [Writes Device Memory in 1-Word Units] ......................................................... D-67
7.7 BT Command [Tests Device Memory in 1-Bit Units (by Writing Arbitrarily)] ............................. D-69
7.8 WT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)]........................ D-70
7.9 QT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)] ........................ D-72
7.10 RR/RS Command [Remotely Sets PLC to RUN/STOP Mode] ............................................... D-73
7.10.1 Contents of remote control to set RUN or STOP mode........................................................... D-73
7.10.2 Condition validating remote control to set RUN or STOP mode.............................................. D-73
7.10.3 Remote control specification method and specification examples .......................................... D-74
7.11 PC Command [Reads PLC Model Name]............................................................................... D-75
7.11.1 PLC model name (CPU) and read contents ............................................................................ D-75
7.11.2 Control procedure specification method and specification example........................................ D-75
7.12 GW Command [Offers Global Function] ................................................................................. D-77
7.12.1 Contents of control .................................................................................................................. D-77
7.12.2 Global function control procedure specification method and specification example ............... D-77
7.13 On-demand Function .............................................................................................................. D-78
7.13.1 Special data registers and special auxiliary relays used in on-demand function..................... D-78
7.13.2 Control procedures in on-demand function ............................................................................. D-80
7.13.3 On-demand function specification method and specification examples .................................. D-82
7.14 TT Command [Loop-back Test] .............................................................................................. D-85

10
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

8. Troubleshooting D-86

8.1 Checking FX PLC Version Applicability .................................................................................... D-86


8.2 Checking Communication Status Based on LED Indication ..................................................... D-86
8.3 Checking Installation and Wiring............................................................................................... D-86
8.4 Checking Sequence Program ................................................................................................... D-86
8.5 Checking Error Codes............................................................................................................... D-88
8.5.1 Error codes when NAK is sent................................................................................................... D-88
8.5.2 Error codes in PLC .................................................................................................................... D-89

9. Related Data D-90

9.1 Related Device List ................................................................................................................... D-90


9.2 Details of Related Devices ........................................................................................................ D-92
9.2.1 Serial communication error [M8063 and M8438]....................................................................... D-92
9.2.2 Communication setting keep [M8120] ....................................................................................... D-92
9.2.3 Global function ON [M8126 and M8426] ................................................................................... D-92
9.2.4 On-demand send processing [M8127 and M8427] ................................................................... D-92
9.2.5 On-demand error flag [M8128 and M8428] ............................................................................... D-93
9.2.6 On-demand data word/byte changeover [M8129 and M8429] .................................................. D-93
9.2.7 Serial communication error code [D8063 and D8438]............................................................... D-93
9.2.8 Communication format setting [D8120 and D8420]................................................................... D-94
9.2.9 Station number settings [D8121 and D8421]............................................................................. D-95
9.2.10 On-demand data head device number specification [D8127 and D8427] ............................... D-96
9.2.11 On-demand data quantity specification [D8128 and D8428] ................................................... D-96
9.2.12 Time-out time setting [D8129 and D8429]............................................................................... D-97
9.2.13 Operation mode display [D8419 and D8439] .......................................................................... D-97
9.3 Communication Setting Method Using Sequence Program...................................................... D-98
9.3.1 Setting procedure ...................................................................................................................... D-98
9.3.2 Caution on communication setting using sequence program.................................................... D-98
9.4 ASCII Code Table ..................................................................................................................... D-99

11
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

E. Inverter Communication

1. Outline E-3

1.1 Outline of System.........................................................................................................................E-3


1.2 Procedures Before Operation ......................................................................................................E-4
1.3 Communication Type Applicability in PLC ...................................................................................E-5
1.3.1 For applicable versions.................................................................................................................E-5
1.3.2 Version check ...............................................................................................................................E-5
1.3.3 How to look at the manufacturer's serial number .........................................................................E-5
1.4 Programming Tool Applicability....................................................................................................E-6
1.4.1 For applicable versions.................................................................................................................E-6
1.4.2 For non-applicable versions (setting an alternative model) ..........................................................E-7

2. Specifications E-8

2.1 Communication Specifications (Reference) .................................................................................E-8


2.2 Connectable Mitsubishi General-purpose Inverters .....................................................................E-8
2.3 Link Specifications .......................................................................................................................E-9
2.3.1 When monitoring inverter operations (PLC inverter)................................................................E-9
2.3.2 When controlling inverter operations (PLC inverter) ................................................................E-9
2.3.3 Parameters (PLC inverter).......................................................................................................E-9
2.4 Execution Times in Inverter Communication Instructions ..........................................................E-10
2.4.1 Outline ........................................................................................................................................E-10
2.4.2 Calculation method.....................................................................................................................E-12
2.4.3 Calculation example ...................................................................................................................E-14

3. System Configuration and Selection E-16

3.1 System Configuration.................................................................................................................E-16


3.2 Applicable FX PLC and Communication Equipment..................................................................E-18

4. Wiring E-23

4.1 Wiring Procedure .......................................................................................................................E-24


4.2 Selecting Cables and Connection Devices ................................................................................E-25
4.2.1 S500, E500, A500, F500, V500, D700 and E700 Series (PU connector) ..................................E-25
4.2.2 A500, F500 and V500 Series (FR-A5NR) ..................................................................................E-26
4.2.3 F800, A800, F700 and A700 Series (built-in RS-485 terminal) ..................................................E-27
4.2.4 E700 Series (FR-E7TR) .............................................................................................................E-28
4.3 Connection Cables.....................................................................................................................E-29
4.3.1 10BASE-T cable .........................................................................................................................E-29
4.3.2 Twisted pair cable (recommended) ............................................................................................E-29
4.3.3 Connecting cables ......................................................................................................................E-30
4.4 Connection Devices (RJ45 Connector and Distributor) .............................................................E-31
4.5 Connecting Terminal Resistors ..................................................................................................E-32
4.6 Wiring a Shielding Wire (Class-D grounding).............................................................................E-33
4.7 Connector in Inverter..................................................................................................................E-34
4.8 Connection Diagram ..................................................................................................................E-36
4.8.1 For S500, E500, A500, F500 , V500 and D700 Series (PU connector) .....................................E-36
4.8.2 For A500, F500 and V500 Series (FR-A5NR) ...........................................................................E-38
4.8.3 For E700 Series (PU connector) ................................................................................................E-39
4.8.4 For E700 Series (FR-E7TR) .......................................................................................................E-43
4.8.5 For F800, A800, F700 and A700 Series (built-in RS-485 terminal)............................................E-46
4.8.6 Switching of 1 pair / 2 paired wiring (FX3G-485-BD-RJ) ............................................................E-47
4.9 Grounding ..................................................................................................................................E-47

12
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

5. Communication Setting in Inverter E-48

5.1 Communication Port and Applicable Parameters ......................................................................E-48


5.2 S500 Series (When Connected to RS-485 Port)........................................................................E-50
5.2.1 Contents of parameter setting ....................................................................................................E-50
5.2.2 Parameter setting method (reference)........................................................................................E-51
5.3 E500 Series (When Connected to PU Port)...............................................................................E-53
5.3.1 Contents of parameter setting ....................................................................................................E-53
5.3.2 Parameter setting method (reference)........................................................................................E-54
5.4 V500, F500 and A500 Series (Connection to PU Port)..............................................................E-56
5.4.1 Contents of parameter setting ....................................................................................................E-56
5.4.2 Parameter setting method (reference)........................................................................................E-57
5.5 V500, F500 and A500 Series (Connection to FR-A5NR)...........................................................E-59
5.5.1 Contents of parameter setting ....................................................................................................E-59
5.5.2 Parameter setting method (reference)........................................................................................E-59
5.6 E700, D700 Series (when PU port, FR-E7TR is connected) .....................................................E-60
5.6.1 Contents of parameter setting ....................................................................................................E-60
5.6.2 Parameter setting method (reference)........................................................................................E-62
5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)........................................E-64
5.7.1 Contents of parameter setting ....................................................................................................E-64
5.7.2 Parameter setting method (reference)........................................................................................E-65
5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)........................................E-67
5.8.1 Contents of parameter setting ....................................................................................................E-67
5.8.2 Parameter setting method (reference)........................................................................................E-68
5.9 Cautions on Setting....................................................................................................................E-69

6. Communication Setting in FX Programmable Controller E-70

6.1 Parameter Assigning Method.....................................................................................................E-70


6.2 Communication Setting Using Parameter Method (GX Works2) ...............................................E-71
6.2.1 Operating procedure...................................................................................................................E-71
6.3 Communication Setting Using Parameter Method (FXGP/WIN)................................................E-73
6.3.1 Operating procedure...................................................................................................................E-73

7. Creating Programs (FX2N, FX2NC) E-75

7.1 Checking Contents of Related Devices......................................................................................E-75


7.2 Common Items in Inverter Communication Instructions ............................................................E-76
7.2.1 Inverter communication types (EXTR K10 to K13).....................................................................E-76
7.2.2 Function and operation...............................................................................................................E-76
7.2.3 Instruction completion and error flag operation ..........................................................................E-78
7.2.4 Cautions on programming ..........................................................................................................E-80
7.3 Inverter Operation Monitoring Instruction (PLCInverter) [EXTR K10].....................................E-81
7.3.1 Function and operation...............................................................................................................E-81
7.3.2 Inverter instruction codes ...........................................................................................................E-81
7.4 Inverter Operation Control Instruction (PLCInverter) [EXTR K11]..........................................E-82
7.4.1 Function and operation...............................................................................................................E-82
7.4.2 Inverter instruction codes ...........................................................................................................E-82
7.5 Inverter Parameter Reading Instruction (PLCInverter) [EXTR K12] .......................................E-83
7.5.1 Function and operation...............................................................................................................E-83
7.5.2 Inverter parameter number.........................................................................................................E-83
7.5.3 Program example of "second parameter specification code" .....................................................E-83
7.6 Inverter Parameter Writing Instruction (PLCInverter) [EXTR K13] .........................................E-84
7.6.1 Function and operation...............................................................................................................E-84
7.6.2 Inverter parameter number.........................................................................................................E-84
7.6.3 Program example of "second parameter specification code" .....................................................E-84

13
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

7.7 Second Parameter Specification Codes ....................................................................................E-85


7.7.1 S500 Series ................................................................................................................................E-85
7.7.2 E500 Series ................................................................................................................................E-85
7.7.3 A500 Series ................................................................................................................................E-86

8. Practical Program Examples (FX2N, FX2NC) E-87

8.1 Practical Example 1 ...................................................................................................................E-87


8.1.1 System configuration example ...................................................................................................E-87
8.1.2 Contents of operation .................................................................................................................E-87
8.1.3 Program example .......................................................................................................................E-88
8.2 Practical Example 2 ...................................................................................................................E-91
8.2.1 System configuration example ...................................................................................................E-91
8.2.2 Contents of operation .................................................................................................................E-91
8.2.3 Program example .......................................................................................................................E-92

9. Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC) E-96

9.1 Differences between FX2N, FX2NC and FX3S, FX3G, FX3GC, FX3U, FX3UC ...........................E-96
9.2 Contents of Related Devices......................................................................................................E-97
9.3 Common Items in Inverter Communication Instructions ............................................................E-98
9.3.1 Inverter communication types (IVCK to IVMC)...........................................................................E-98
9.3.2 Function and operation...............................................................................................................E-98
9.3.3 Instruction completion and error flag operation ........................................................................E-100
9.3.4 Cautions on programming ........................................................................................................E-102
9.4 Inverter Operation Monitoring Instruction (PLCInverter) [FNC270 / IVCK]...........................E-104
9.4.1 Function and operation.............................................................................................................E-104
9.4.2 Inverter instruction codes .........................................................................................................E-104
9.5 Inverter Operation Control Instruction (PLCInverter) [FNC271 / IVDR]................................E-105
9.5.1 Function and operation.............................................................................................................E-105
9.5.2 Inverter instruction codes .........................................................................................................E-105
9.6 Inverter Parameter Reading (PLCInverter) [FNC272 / IVRD]...............................................E-106
9.6.1 Function and operation.............................................................................................................E-106
9.6.2 Inverter instruction codes .........................................................................................................E-106
9.6.3 Program example of "second parameter specification code" ...................................................E-106
9.7 Inverter Parameter Writing (PLCInverter) [FNC273 / IVWR] ................................................E-108
9.7.1 Function and operation.............................................................................................................E-108
9.7.2 Inverter instruction codes .........................................................................................................E-108
9.7.3 Program example of "second parameter specification code" ...................................................E-108
9.8 Inverter Parameter Batch Writing (PLCInverter) [FNC274 / IVBWR] ...................................E-109
9.8.1 Function and operation.............................................................................................................E-109
9.9 Controls Operations and Monitors Operations of an Inverter with a Single
Command(PLCInverter)[FNC275 / IVMC]............................................................................E-110
9.9.1 Function and operation.............................................................................................................E-110
9.9.2 Applicable inverters ..................................................................................................................E-111
9.9.3 Applicable programming tool ....................................................................................................E-111
9.10 Second Parameter Specification Codes ................................................................................E-112
9.10.1 S500 Series ............................................................................................................................E-112
9.10.2 E500 Series ............................................................................................................................E-112
9.10.3 A500 Series ............................................................................................................................E-113
9.10.4 F500 Series ............................................................................................................................E-114
9.10.5 V500 Series ............................................................................................................................E-114
9.10.6 F700 Series ............................................................................................................................E-114
9.10.7 A700 Series ............................................................................................................................E-115
9.10.8 E700 and D700 Series ...........................................................................................................E-116
9.10.9 F800 Series ............................................................................................................................E-117
9.10.10 A800 Series ..........................................................................................................................E-118

14
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

10. Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC) E-119

10.1 Practical Example 1 ...............................................................................................................E-119


10.1.1 System configuration example ...............................................................................................E-119
10.1.2 Contents of operation .............................................................................................................E-119
10.1.3 Program example ...................................................................................................................E-120
10.2 Practical Example 2 ...............................................................................................................E-125
10.2.1 System configuration example ...............................................................................................E-125
10.2.2 Contents of operation .............................................................................................................E-125
10.2.3 Program example ...................................................................................................................E-126

11. Troubleshooting E-134

11.1 Checking FX PLC Version Applicability (FX2N and FX2NC Series) .......................................E-134
11.2 Checking Communication Status Based on LED Indication ..................................................E-134
11.3 Checking Installation ..............................................................................................................E-134
11.4 Checking Sequence Program ................................................................................................E-134
11.4.1 Checking inverter operation status .........................................................................................E-135
11.5 Checking Absence/Presence of Errors ..................................................................................E-136
11.6 Error Codes............................................................................................................................E-136

12. Related Data E-139

12.1 Related Device List (FX2N, FX2NC) .......................................................................................E-139


12.2 Details of Related Devices (FX2N, FX2NC)............................................................................E-140
12.2.1 Instruction execution complete [M8029] .................................................................................E-140
12.2.2 Extension ROM cassette check [M8104]................................................................................E-140
12.2.3 Communication port busy [M8155].........................................................................................E-140
12.2.4 Communication error or parameter error [M8156]..................................................................E-140
12.2.5 Communication error latch [M8157] .......................................................................................E-141
12.2.6 Extension ROM cassette type code [D8104]..........................................................................E-141
12.2.7 Extension ROM cassette version [D8105]..............................................................................E-141
12.2.8 Inverter response waiting time [D8154] ..................................................................................E-141
12.2.9 Step number of instruction using communication port [D8155] ..............................................E-141
12.2.10 Error code [D8156] ...............................................................................................................E-142
12.2.11 Error occurrence step number latch [D8157]........................................................................E-143
12.3 Related Device List (FX3S, FX3G, FX3GC, FX3U, FX3UC) ....................................................E-144
12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC) .........................................E-145
12.4.1 Instruction execution complete [M8029] .................................................................................E-145
12.4.2 Serial communication error [M8063 and M8438]....................................................................E-145
12.4.3 Inverter communication ON [M8151 and M8156]...................................................................E-145
12.4.4 Inverter communication error [M8152, M8153, M8157 and M8158].......................................E-146
12.4.5 IVBWR instruction error [M8154 and M8159] (only in FX3U and FX3UC PLCs) ....................E-146
12.4.6 Serial communication error code [D8063 and D8438]............................................................E-146
12.4.7 Inverter response waiting time [D8150 and D8155] ...............................................................E-146
12.4.8 Step number of instruction using communication port [D8151 and D8156] ...........................E-147
12.4.9 Inverter communication error code [D8152 and D8157].........................................................E-147
12.4.10 Inverter communication error occurrence step [D8153 and D8158].....................................E-150
12.4.11 IVBWR instruction error parameter number [D8154 and D8159]
(only in FX3U and FX3UC PLCs)...........................................................................................E-150
12.4.12 Operation mode display [D8419 and D8439] .......................................................................E-150
12.5 FREQROL Inverter Parameter List ........................................................................................E-151
12.5.1 Parameters in V500, F500, A500, E500, and S500 Series ....................................................E-151
12.5.2 Parameters in F700, A700, E700 and D700 Series ...............................................................E-173
12.5.3 Parameters in F800 and A800 Series ....................................................................................E-190
12.5.4 Communication parameters ...................................................................................................E-208

15
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

F.Non-Protocol Communication (RS/RS2 Instruction)

1. Outline F-3

1.1 Outline of System.........................................................................................................................F-3


1.2 Procedures Before Operation ......................................................................................................F-7
1.3 Communication Type Applicability in PLC ...................................................................................F-8
1.3.1 Applicable versions.......................................................................................................................F-8
1.3.2 Version check ...............................................................................................................................F-8
1.3.3 How to look at the manufacturer's serial number .........................................................................F-8
1.3.4 Products whose production was stopped .....................................................................................F-8
1.4 Programming Tool Applicability....................................................................................................F-9
1.4.1 For applicable versions.................................................................................................................F-9
1.4.2 For non-applicable versions (setting an alternative model) ........................................................F-11

2. Specifications F-12

2.1 Communication Specifications (Reference) ...............................................................................F-12


2.2 Data Communication Specifications ..........................................................................................F-13
2.2.1 Communication type applicability in PLC ...................................................................................F-13
2.3 Number of Transfer Data ...........................................................................................................F-14

3. System Configuration and Selection F-15

3.1 System Configuration.................................................................................................................F-15


3.2 Applicable FX PLC and Communication Equipment..................................................................F-16
3.2.1 For communication in accordance with RS-232C ......................................................................F-16
3.2.2 For communication in accordance with RS-485 .........................................................................F-22

4. Wiring F-27

4.1 Wiring Procedure .......................................................................................................................F-27


4.2 Selecting Cables and Terminal Resistors ..................................................................................F-28
4.2.1 When using ch0 in FX3G, FX3GC PLC .......................................................................................F-28
4.2.2 Twisted pair cable.......................................................................................................................F-28
4.2.3 10BASE-T cable .........................................................................................................................F-29
4.2.4 Connecting cables ......................................................................................................................F-30
4.2.5 Connecting terminal resistors .....................................................................................................F-32
4.3 Connection Diagram ..................................................................................................................F-33
4.3.1 Connector pin arrangement in communication equipment operating in accordance
with RS-232C .............................................................................................................................F-33
4.3.2 Wiring for communication in accordance with RS-232C ............................................................F-33
4.3.3 Wiring for communication in accordance with RS-485 ...............................................................F-35
4.4 Grounding ..................................................................................................................................F-39

5. Communication Setting in FX Programmable Controller F-40

5.1 Communication Setting Method Mechanism..............................................................................F-40


5.2 Communication Setting Using Parameter Method (GX Works2) ...............................................F-41
5.2.1 Operating procedure...................................................................................................................F-41
5.3 Communication Setting Using Parameter Method (FXGP/WIN)................................................F-43
5.3.1 Operating procedure...................................................................................................................F-43

16
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

6. Creating Programs (RS Instruction) F-45

6.1 Checking Contents of Related Devices......................................................................................F-45


6.2 How to Use RS Instruction .........................................................................................................F-46
6.2.1 Applicable frames .......................................................................................................................F-46
6.2.2 Function and operation...............................................................................................................F-47
6.2.3 Send/receive data and amount of data.......................................................................................F-48
6.2.4 Operation when data is sent.......................................................................................................F-50
6.2.5 Operation when data is received ................................................................................................F-50
6.3 Operation of Control Line ...........................................................................................................F-52
6.3.1 FX2N (before Ver. 2.00), FX2(FX), FX2C, FX0N, FX1S, FX1N and FX1NC PLCs .......................F-52
6.3.2 FX2N (Ver. 2.00 or later), FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs......................F-54
6.4 Important Points in Creating Programs ......................................................................................F-56
6.5 Communication Error .................................................................................................................F-56

7. Practical Program Example (RS Instruction) F-57

7.1 Example of Printing Using RS Instruction (Using RS-232C Connection)...................................F-57

8. Creating Programs (RS2 Instruction) F-59

8.1 Checking Contents of Related Devices......................................................................................F-59


8.2 How to Use RS2 Instruction .......................................................................................................F-62
8.2.1 Applicable frames .......................................................................................................................F-63
8.2.2 Function and operation...............................................................................................................F-65
8.2.3 Send/receive data and amount of data.......................................................................................F-66
8.2.4 Operation when data is sent.......................................................................................................F-68
8.2.5 Operation when data is received ................................................................................................F-68
8.2.6 Sum check code .........................................................................................................................F-71
8.3 Operation of Control Line ...........................................................................................................F-72
8.4 Important Points in Creating Programs ......................................................................................F-75
8.5 Communication Error .................................................................................................................F-75

9. Practical Program Example (RS2 Instruction) F-76

9.1 Example of Printing Using RS2 Instruction (Using RS-232C Connection).................................F-76

10. When Combined with Another Communication F-78

10.1 Other Communication Type Used Together ............................................................................F-78


10.2 When Combined with Programming Communication ..............................................................F-79
10.2.1 For FX2N and FX2NC PLCs......................................................................................................F-79
10.2.2 For FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs ...................................................................F-80
10.3 When Combined with Computer Link Communication.............................................................F-81
10.4 When Combined with Programming Communication ..............................................................F-82
10.5 Using RS2 Instruction and Computer Link Communication Together......................................F-83
10.6 Communication Setting Method Using Sequence Program.....................................................F-84
10.6.1 Communication setting for RS instruction ................................................................................F-84
10.6.2 Communication setting for RS2 instruction ..............................................................................F-86

17
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

11. Troubleshooting F-87

11.1 Checking FX PLC Version Applicability ...................................................................................F-87


11.2 Checking Communication Status Based on LED Indication ....................................................F-87
11.3 Checking Installation ................................................................................................................F-87
11.4 Checking Sequence Program ..................................................................................................F-88
11.4.1 Checking communication port settings (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)......F-89
11.5 Checking the Absence/Presence of Errors ..............................................................................F-89

12. Related Data F-90

12.1 Related Device List (RS Instruction) ........................................................................................F-90


12.2 Details of related devices (RS instruction) ...............................................................................F-91
12.2.1 Serial communication error [M8063].........................................................................................F-91
12.2.2 Communication setting keep [M8120] ......................................................................................F-91
12.2.3 Sending wait flag [M8121] ........................................................................................................F-91
12.2.4 Sending request [M8122] .........................................................................................................F-91
12.2.5 Receiving complete flag [M8123] .............................................................................................F-92
12.2.6 Carrier detection flag [M8124] ..................................................................................................F-92
12.2.7 Time-out check flag [M8129] ....................................................................................................F-92
12.2.8 Serial communication error code [D8063] ................................................................................F-93
12.2.9 Communication format setting [D8120] ....................................................................................F-94
12.2.10 Remaining amount of data to be sent [D8122] .......................................................................F-94
12.2.11 Amount of data already received [D8123] ..............................................................................F-95
12.2.12 Header [D8124] ......................................................................................................................F-95
12.2.13 Terminator [D8125].................................................................................................................F-95
12.2.14 Time-out time setting time [D8129].........................................................................................F-95
12.2.15 Communication parameter display [D8405] ...........................................................................F-95
12.2.16 Operation mode display [D8419] ............................................................................................F-96
12.3 Related Devices (RS2 Instruction) ...........................................................................................F-96
12.4 Details of Related Devices (RS2 Instruction) ...........................................................................F-97
12.4.1 Serial communication error [M8062, M8063 and M8438].........................................................F-97
12.4.2 Sending wait flag [M8371, M8401 and M8421] ........................................................................F-98
12.4.3 Sending request [M8372, M8402 and M8422] .........................................................................F-98
12.4.4 Receiving complete flag [M8373, M8403 and M8423] .............................................................F-98
12.4.5 Carrier detection flag [M8404 and M8424] ...............................................................................F-99
12.4.6 Data set ready (DSR) flag [M8405 and M8425] .......................................................................F-99
12.4.7 Time-out check flag [M8379, M8409 and M8429] ....................................................................F-99
12.4.8 Serial communication error code [D8062, D8063 and D8438] ...............................................F-100
12.4.9 Communication format setting [D8370, D8400 and D8420] ...................................................F-101
12.4.10 Amount of remaining send data [D8372, D8402 and D8422]...............................................F-102
12.4.11 Amount of data already received [D8373, D8403 and D8423] .............................................F-102
12.4.12 Communication parameter display [D8405 and D8425].......................................................F-102
12.4.13 Time-out time setting [D8379, D8409 and D8429] ...............................................................F-102
12.4.14 Header [D8380, D8381, D8410, D8411, D8430 and D8431] ...............................................F-103
12.4.15 Terminator [D8382, D8383, D8412, D8413, D8432 and D8433]..........................................F-103
12.4.16 Receiving sum (receive data) [D8384, D8414 and D8434] ..................................................F-104
12.4.17 Receiving sum (calculation result) [D8385, D8415 and D8435] ...........................................F-104
12.4.18 Sending sum [D8386, D8416 and D8436]............................................................................F-104
12.4.19 Operation mode display [D8389, D8419 and D8439]...........................................................F-105
12.5 ASCII Code Table ..................................................................................................................F-106

18
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

G.Non-Protocol Communication (FX2N-232IF)

1. Outline G-3

1.1 Features ...................................................................................................................................... G-3


1.2 Procedures Before Operation ..................................................................................................... G-4
1.3 Communication Type Applicability in PLC .................................................................................. G-5
1.3.1 Applicable versions...................................................................................................................... G-5
1.3.2 Products whose production was stopped .................................................................................... G-5
1.4 Programming Tool Applicability................................................................................................... G-6
1.4.1 For applicable versions................................................................................................................ G-6
1.4.2 For non-applicable versions (setting an alternative model) ......................................................... G-7

2. Specification G-8

2.1 Communication Specifications .................................................................................................... G-8

3. System Configuration and Selection G-9

3.1 System Configuration.................................................................................................................. G-9


3.2 Applicable FX PLC and Communication Equipment................................................................... G-9
3.3 Connection to PLC .................................................................................................................... G-10

4. Wiring G-12

4.1 Pin Arrangement ....................................................................................................................... G-12


4.2 Connection to External Equipment with Terminal Specifications (without Control Line)........... G-12
4.3 Connection to External Equipment with Terminal Specifications (with Control Line)................ G-13
4.3.1 Standard RS-232C mode .......................................................................................................... G-13
4.3.2 Interlink connection mode.......................................................................................................... G-13
4.4 Connection to External Equipment with Modem Specifications ................................................ G-13

19
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

5. Creating Programs G-14

5.1 Outline of Communication between FX PLC and 232IF ........................................................... G-14


5.1.1 For FROM and TO instructions ................................................................................................. G-14
5.1.2 For direct specification of buffer memory (U\G) .................................................................. G-14
5.2 FROM and TO Instructions ....................................................................................................... G-15
5.2.1 FROM instruction....................................................................................................................... G-15
5.2.2 TO instruction ............................................................................................................................ G-16
5.3 Direct Specification of Buffer Memory (U\G)....................................................................... G-17
5.4 Buffer Memory (BFM)................................................................................................................ G-18
5.4.1 Buffer memory list...................................................................................................................... G-18
5.4.2 Communication format <BFM #0>............................................................................................. G-20
5.4.3 Command <BFM #1> ................................................................................................................ G-24
5.4.4 Maximum number of receivable bytes <BFM #2> ..................................................................... G-25
5.4.5 Receiving timeout time <BFM #3> ............................................................................................ G-25
5.4.6 Sending header <BFM #5 (highest-order 2 bytes) and BFM #4 (lowest-order 2 bytes)>.......... G-25
5.4.7 Sending terminator <BFM #7 (highest-order 2 bytes) and BFM #6 (lowest-order 2 bytes)>..... G-25
5.4.8 Receiving header <BFM #9 (highest-order 2 bytes) and BFM #8 (lowest-order 2 bytes)> ....... G-25
5.4.9 Receiving terminator <BFM #11 (highest-order 2 bytes) and BFM #10 (lowest-order 2 bytes)>... G-26
5.4.10 Receiving suspension waiting time <BFM #12>...................................................................... G-26
5.4.11 Amount of remaining send data <BFM #13>........................................................................... G-26
5.4.12 Amount of received data buffers <BFM #14>.......................................................................... G-26
5.4.13 Sending sum result <BFM #15> .............................................................................................. G-27
5.4.14 Receiving sum result <BFM #16> ........................................................................................... G-27
5.4.15 Time from CS ON to sending start <BFM #20>....................................................................... G-27
5.4.16 Time from actual sending completion to RS OFF <BFM #21>................................................ G-27
5.4.17 Status <BFM #28>................................................................................................................... G-28
5.4.18 Error code <BFM #29> ............................................................................................................ G-29
5.4.19 Model code <BFM #30> .......................................................................................................... G-29
5.4.20 Number of bytes to be sent <BFM #1000>.............................................................................. G-29
5.4.21 Send data buffer <BFM #1001 to 1256> ................................................................................. G-29
5.4.22 Number of received bytes <BFM #2000>................................................................................ G-29
5.4.23 Receive data buffer <BFM #2001 to 2256>............................................................................. G-29
5.4.24 Preliminary receive data buffer for interlink connection mode <BFM #2257 to 2271> ............ G-29
5.5 Operation of Control Line .......................................................................................................... G-30
5.5.1 When control line is not provided [BFM #0, (b9, b8) = (0, 0)].................................................... G-30
5.5.2 When control line is in standard RS-232C mode [BFM #0, (b9, b8) = (0, 1)] ............................ G-31
5.5.3 When control line is in RS-232C interlink mode [BFM #0, (b9, b8) = (1, 1)].............................. G-32

6. Practical Program Examples G-33

6.1 Example of Sending/Receiving 16-Bit Buffer Length Data........................................................ G-33


6.2 Sending/Receiving 8-Bit Buffer Length Data............................................................................. G-37

7. Troubleshooting G-41

7.1 Check Items .............................................................................................................................. G-41


7.2 Error Codes............................................................................................................................... G-41

20
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

H.Programming Communication

1. Outline H-3

1.1 Outline of System........................................................................................................................ H-3


1.2 Procedures Before Operation ..................................................................................................... H-4
1.3 Communication Type Applicability in PLC .................................................................................. H-5
1.3.1 Applicable PLC ............................................................................................................................ H-5
1.3.2 Products whose production was stopped .................................................................................... H-5
1.4 Programming Tool Applicability................................................................................................... H-6
1.4.1 For applicable versions................................................................................................................ H-6
1.4.2 For non-applicable versions (setting an alternative model) ......................................................... H-8

2. System Configuration and Selection H-9

2.1 System Configuration.................................................................................................................. H-9


2.1.1 For communication equipment operating in accordance with RS-422 ........................................ H-9
2.1.2 For communication equipment operating in accordance with RS-232C.................................... H-10
2.1.3 For communication equipment operating in accordance with USB ........................................... H-10
2.1.4 For Ethernet adapter ................................................................................................................. H-11
2.2 Applicable FX PLC and Communication Equipment................................................................. H-12
2.3 Caution on Selection ................................................................................................................. H-23
2.3.1 When using 422BD.................................................................................................................... H-23
2.3.2 When using 232BD or 232ADP ................................................................................................. H-24
2.3.3 Other cautions ........................................................................................................................... H-24

3. Selecting Connection Cables H-25

3.1 Connection Procedure .............................................................................................................. H-25


3.2 Connector Shape in Each Product............................................................................................ H-26
3.3 Combinations of Connection Cables......................................................................................... H-27
3.3.1 Handy programming panel ........................................................................................................ H-27
3.3.2 Personal computer .................................................................................................................... H-28

4. Connection Cables and Interfaces H-32

4.1 Simplified Tables....................................................................................................................... H-32


4.1.1 Cable connector shape correspondence table .......................................................................... H-32
4.1.2 Cable combination simplified table ............................................................................................ H-33
4.2 Cable Connection Diagrams ..................................................................................................... H-35
4.2.1 Personal computer connection cable - No. A ............................................................................ H-35
4.2.2 Connector conversion cable (commercial product) - No. B ....................................................... H-37
4.2.3 FX-10P/FX-20P/FX-30P connection cable - No. C.................................................................... H-37

5. Communication Setting (Initialization) in FX Programmable Controller H-38

5.1 Check Procedure ...................................................................................................................... H-38


5.2 Communication Setting Using Parameter Method (GX Works2) .............................................. H-39
5.2.1 Operating procedure.................................................................................................................. H-39
5.3 Communication Setting Using Parameter Method (FXGP/WIN)............................................... H-40
5.3.1 Operating procedure.................................................................................................................. H-40

21
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

6. Connection Setting for Personal Computer H-41

6.1 Connection Setting (GX Works2) .............................................................................................. H-41


6.1.1 Setting RS-232C or USB, communication port, and transmission speed.................................. H-42
6.1.2 Setting for using GOT transparent function ............................................................................... H-44
6.1.3 Setting communication time check and number of retries......................................................... H-45
6.2 Connection Setting (FXGP/WIN)............................................................................................... H-46
6.2.1 Setting communication port and transmission speed ................................................................ H-46
6.3 Communication Test (GX Works2) ........................................................................................... H-47

7. Troubleshooting H-48

7.1 Checking PLC Version Applicability .......................................................................................... H-48


7.2 Checking Programming Tool Applicability................................................................................. H-48
7.3 Checking Communication Status Based on LED Indication ..................................................... H-48
7.4 Checking Installation ................................................................................................................. H-48
7.5 Checking Parameters in PLC.................................................................................................... H-48
7.6 Checking Sequence Program ................................................................................................... H-48
7.7 Checking Programming Tool Setting ........................................................................................ H-50
7.8 Checking Absence/Presence of Errors ..................................................................................... H-50
7.9 Operation mode display [D8419 and D8439] (FX3S, FX3G, FX3GC, FX3U, FX3UC) ................ H-51

22
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

I.Remote Maintenance

1. Outline I-3

1.1 Outline of System.......................................................................................................................... I-3


1.1.1 Maintenance for programs in PLC................................................................................................. I-3
1.1.2 File transfer between personal computers (supported only by FXGP/WIN).................................. I-4
1.2 Procedures Before Operation ....................................................................................................... I-5
1.3 Communication Type Applicability in PLC .................................................................................... I-6
1.3.1 Applicable versions........................................................................................................................ I-6
1.3.2 Version check ................................................................................................................................ I-6
1.3.3 Products whose production was stopped ...................................................................................... I-6
1.4 Programming Tool Applicability..................................................................................................... I-7
1.4.1 Programming tool for setting modem connected to PLC............................................................... I-7
1.4.2 Programming software for remote maintenance ......................................................................... I-11
1.4.3 Cautions on using FXGP/WIN ..................................................................................................... I-12

2. Specifications I-13

2.1 Communication Specifications (Reference) ................................................................................ I-13

3. System Configuration and Selection I-14

3.1 System Configuration.................................................................................................................. I-14


3.2 Setting Applicable FX PLC and Communication Equipment....................................................... I-15
3.3 Selecting Modem ........................................................................................................................ I-20
3.3.1 List of modems whose operations are confirmed ........................................................................ I-21

4. Wiring I-23

4.1 Wiring Procedure ........................................................................................................................ I-23


4.2 Connection Diagram ................................................................................................................... I-24

5. How to Setup Modems on the PLC Side I-25

5.1 Setting Using GX Works2 ........................................................................................................... I-25


5.1.1 Setting communication by way of RS-232C port ......................................................................... I-25
5.1.2 Modem initialization setting using parameter method ................................................................. I-27
5.1.3 Setting AT command for unregistered modem............................................................................ I-29
5.2 Setting Using FXGP/WIN ............................................................................................................ I-33
5.2.1 Setting communication by way of RS-232C port ......................................................................... I-33
5.2.2 Modem initialization setting using parameter method ................................................................. I-34
5.2.3 Setting AT command for unregistered modem............................................................................ I-35
5.3 Cautions on Use.......................................................................................................................... I-37

6. How to Setup Modems on the PC Side for Remote Access I-38

6.1 Setting Using GX Works2 ........................................................................................................... I-38


6.1.1 Registering AT command for connected modem ........................................................................ I-38
6.1.2 Creating telephone directory (if necessary)................................................................................. I-40
6.2 Setting Using FXGP/WIN ............................................................................................................ I-42
6.2.1 Registering AT command for connected modem ........................................................................ I-42
6.2.2 Registering line connection destination ....................................................................................... I-45

23
FX Series PLC User's Manual - Data Communication Edition
Table of Contents

7. Connecting Line I-46

7.1 Preparing for Connection of PLC ................................................................................................ I-46


7.2 Line Connection Procedure......................................................................................................... I-47
7.2.1 For GX Works2............................................................................................................................ I-47
7.2.2 For FXGP/WIN ............................................................................................................................ I-51

8. Troubleshooting I-54

8.1 Checking FX PLC Applicability.................................................................................................... I-54


8.2 Checking Programming Tool Applicability................................................................................... I-54
8.3 Checking Communication Status Based on LED Indication ....................................................... I-54
8.4 Checking Installation ................................................................................................................... I-54
8.5 Checking Modem Specifications ................................................................................................. I-55
8.6 Checking Setting in PLC ............................................................................................................. I-55
8.6.1 Checking parameters in PLC....................................................................................................... I-55
8.6.2 Checking AT command setting.................................................................................................... I-56
8.6.3 Checking sequence program....................................................................................................... I-57
8.7 Checking Programming Tool Setting .......................................................................................... I-58
8.8 Checking Absence/Presence of Errors ....................................................................................... I-58
8.9 Operation mode display [D8419 and D8439] (FX3S, FX3G, FX3GC, FX3U, FX3UC) .................. I-59

9. Related Information I-60

9.1 ASCII Code Table ....................................................................................................................... I-60

Appendix A: Discontinued models Apx.-1

24
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.1 Communication Types

Common Items
1. Introduction
This manual explains the communication types supported by FX PLCs. B
This chapter explains the serial communication (in accordance with RS-232C, RS-485/RS-422), various link

N:N Network
communication types, etc. and states the applicable FX PLCs.

1.1 Communication Types


The table below shows the communication types supported by the FX Series.
C

Parallel Link
Reference
Link
subsection
Connects FX PLCs as remote device stations to the CC-Link system
whose master station is a MELSEC A/QnA PLC.
Function
Connects FX PLCs as remote device stations and intelligent device
stations to the CC-Link system whose master station is a MELSEC D
CC-Link Q PLC. 1.2.1

Computer Link
Constructs a CC-Link system whose master station is an FX PLC.
Line control in the decentralized or centralized method and information
Application
transfer from/to the host network.
Function Easily enables data link between FX PLCs.
N:N Network
Application Line control in the decentralized or centralized method.
1.2.3
E
Function Easily enables data link between FX PLCs.

Communication
Inverter
Parallel link 1.2.4
Application Line control in the decentralized or centralized method.
Connects a personal computer or another computer as the master
Function station, and connects FX PLCs as slave stations.
Computer link Protocols in a computer support computer link protocol formats 1 and 4. 1.2.5
Application Data acquisition and centralized control. F
Function Communicates with and controls Mitsubishi inverter FREQROL.

(RS/RS2 Instruction)
Communication
Non-Protocol
Inverter
Operation monitoring, writing of control values, referencing and 1.2.6
communication Application
changing parameters, etc.
Enables MODBUS communication with MODBUS-compatible
MODBUS Function
equipment in accordance with RS-232C or RS-485. 1.2.8
communication
Application Line control in the decentralized or centralized method. G
Reference

(FX2N-232IF)
Communication
Non-Protocol
Ethernet communication
subsection
Connects the FX PLC to a high-order system such as personal
Function computer or workstation via Ethernet (100BASE-TX or 10BASE-T)
Ethernet using TCP/IP or UDP/IP communication protocol. 1.2.2
Application
Line control in the decentralized or centralized method and information
transfer from/to the host network.
H
Communication
Programming

Reference
General-purpose serial communication
subsection
Receives and sends data from/to various pieces of equipment with an
Function
Non-protocol RS-232C or RS-485 interface in non-protocol procedures.
1.2.7
communication
Application
Data reception and sending from/to a personal computer, bar code
reader, printer and other various measuring instruments. I
Maintenance
Remote

Reference
Sequence program
subsection
Adds RS-232C, RS-422, USB and Ethernet ports in addition to the
Programming Function
provided RS-422 port in PLCs. 1.2.9
communication
Application Simultaneously connection of two display units, programming tools, etc.
Connects with a PLC located in a remote location through a modem Apx.A
Function and telephone line to enable program transfer and remote monitoring
models
Discontinued

Remote
access. 1.2.10
maintenance
Application Maintenance of sequence programs in FX PLCs.

A-1
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.1 Communication Types

Reference
I/O link
subsection
CC-Link/LT Function Constructs a CC-Link/LT system whose master station is an FX PLC.
(built in
1.2.11
FX3UC-32MT- Application Wire-conserving network inside control panel and unit.
LT(-2))
Constructs an AnyWireASLINK system whose master station is an FX
Function
AnyWireASLINK PLC. 1.2.12
Application Wire-conserving network inside control panel and unit.
Constructs an AS-i (Actuator Sensor Interface) system whose master
Function
AS-i system block is an FX PLC. 1.2.13
Application Wire-conserving network inside control panel and unit.
Installs remote I/O units near I/O equipment in remote locations to
Function
MELSEC I/O link conserve wiring.
Application ON/OFF control of I/O equipment in a remote location.
Reference
Electronic mail sending
subsection
Sends internet mail to personal computers and cellular phones using
Function
the RS-232C communication in PLCs.
Internet mail 1.2.14
Monitoring of unmanned facilities, facilities located in remote locations
Application
and facilities inside factories.
Function Sends short mails to cellular phones in the NTT DoCoMo network.
Short mail 1.2.15
Application Notice of material shortage, error contents, operating time, etc.

A-2
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2 Outline and Features of Communication Types

Common Items
This section outlines the communication types supported by FX PLCs.

1.2.1 CC-Link Network


B
For details, refer to the FX2N-16CCL-M USERS MANUAL.

N:N Network
For details, refer to the FX3U-16CCL-M USERS MANUAL.
For details, refer to the FX2N-32CCL USERS MANUAL.
For details, refer to the FX3U-64CCL USERS MANUAL.

1. Outline
C
1) When the master station is an A/QnA PLC

Parallel Link
ACPU, Master
QnACPU station

Terminal resistor D

Computer Link
Terminal resistor

Remote Remote I/O Inverter, Sensor, solenoid valve,


FXCPU device for CC-Link AC servo, etc. etc.
station E

Communication
Inverter
Number of connectable units : 64 maximum
Total extension distance : 1200 m (3937' 0")

2) When the master station is a Q PLC


F
Master
QCPU

(RS/RS2 Instruction)
Communication
Non-Protocol
station

Terminal resistor

Terminal resistor G

(FX2N-232IF)
Communication
Non-Protocol
Intelligent Remote Remote I/O Inverter, Sensor, solenoid valve,
FXCPU device FXCPU device
station station for CC-Link AC servo, etc. etc.

Number of connectable units : 64 maximum H


Total extension distance : 1200 m (3937' 0")
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-3
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

3) When the master station is an FX2N-16CCL-M

Master station
FXCPU FX2N-16CCL-M

Terminal resistor
Terminal resistor

Remote Remote I/O Inverter, Sensor, solenoid valve,


FXCPU device for CC-Link AC servo, etc. etc.
station

Number of connectable units : Remote I/O station 7 maximum


: Remote device station 8 maximum
Total extension distance : 1200 m (3937' 0")
4) When the master station is an FX3U-16CCL-M

Master station
FXCPU
FX3U-16CCL-M

Terminal resistor
Terminal resistor

Intelligent Remote Remote I/O Inverter, Sensor, solenoid valve,


FXCPU device FXCPU device
station station for CC-Link AC servo, etc. etc.

Number of connectable units : Remote I/O station 8 maximum


: Remote device station + Intelligent device station* 1 8 maximum
Total extension distance : 1200 m (3937' 0")
*1. Local stations can not be connected.
2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX2(FX), FX2N, FX3G, FX3U,
PLC FX0N FX1S FX1N FX1NC FX3S
FX2C FX2NC FX3GC FX3UC

FX2N-
(Ver. 1.10 (Ver. 2.20
FX Series 16CCL-M
or later) or later)
master station
connectivity FX3U- *2
16CCL-M
*2 (Ver. 2.20
or later)
FX Series
FX2N-
remote device station
32CCL
connectivity
FX Series
FX3U- *3
intelligent device *3
64CCL (Ver. 2.20
station connectivity or later)

*2. FX3G and FX3GC PLCs Ver. 2.00 or later, or FX3U and FX3UC PLCs Ver. 3.10 or later support the
access function to other FX Series PLC main units connected to FX3U-64CCL.
*3. The table below shows versions of GX Works2 and GX Developer that support the access function to
other FX Series PLC main units via CC-Link.

PLC connected PLC main unit accessed


through FX3G FX3GC FX3U FX3UC
GX Developer QCPU(Q mode) Ver. 8.78G or later Ver. 8.72A or later Ver. 8.72A or later
QCPU(Q mode) Ver. 1.08J or later Ver. 1.77F or later Ver. 1.08J or later Ver. 1.08J or later
GX Works2 FXCPU*2 + Ver. 1.87R or later Ver. 1.87R or later Ver. 1.73B or later Ver. 1.73B or later
FX3U-16CCL-M

A-4
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
3. Communication targets

Common Items
Equipment operating in accordance with the CC-Link standard

4. Function
Master station allows connection of remote device station, remote I/O station (inverters, AC servos, sensors,
solenoid valves, etc.) supporting the CC-Link network to achieve data link.
FX PLCs are classified as master stations, remote device stations or intelligent device stations.
B

N:N Network
5. Applications
Decentralized or centralized control of the line, reception and sending of information from/to the host network,
etc.

6. Detailed information on CC-Link C


For details on CC-Link and connectable equipment, refer to the CC-Link Partner Association's homepage or

Parallel Link
catalogues (issued by the CC-Link Partner Association).
CC-Link Partner Association's homepage: http://www.cc-link.org/

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-5
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.2 Ethernet communication


For details, refer to FX3U-ENET-ADP Users Manual.
1. Outline
Network Range (Only within LAN)
Router

SNTP server Hub

FX3U-ENET-ADP Local
station
External device External device

GX Works2

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX2N,FX2NC FX3S FX3G, FX3GC FX3U, FX3UC

Communication
applicability
*1 (Ver. 2.00 or (Ver. 3.10 or
later) later)

*1. The FX3U-ENET-ADP Ver. 1.20 or later is applicable to the FX3S PLC.
3. Applicable software
Use the following version when setting the FX3U-ENET-ADP or connecting using MELSOFT:
Product name Model name Applicability
GX Works2 SWDNC-GXW2-E Ver. 1.73B or later*2

*2. Ver. 1.492N or later supports the FX3S PLC.


Ver. 1.87R or later supports the FX3G, FX3GC PLCs.
Caution
Setting and others are disabled when using nonapplicable versions.
4. Communication targets
Ethernet-compatible equipment
5. Function
The FX3U-ENET-ADP can connect FX3S, FX3G, FX3GC, FX3U, FX3UC Series PLCs to a high-order system
such as personal computer via Ethernet (100BASE-TX or 10BASE-T) using TCP/IP or UDP communication
protocol.
6. Applications
1) Collects and changes the PLC data.
(Communication using the MELSEC communication protocol)
2) Reads, writes and verifies programs, and monitors and tests device values in the main unit remotely.
(Communicates with GX Works2 via Ethernet through MELSOFT connection.)
3) Executes monitoring remotely using a web browser.
(The data monitoring function enables monitoring the information and device values in the main unit and
FX3U-ENET-ADP using a web browser.)

A-6
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.3 N:N Network

Common Items
Refer to the "N:N Network" section.

1. Outline
B
RS-485

RS-485

RS-485
FX CPU FX CPU FX CPU
Station Station Station

N:N Network
Terminal No. 0 No. 1 No. 7
resistor Terminal
resistor

Number of connectable FX PLCs : 8 maximum (station Nos. 0 to 7)


Total extension distance : 500 m (1640' 5") [50 m (164' 0") when 485BD is connected] C
For FX3U PLC (pattern 2)

Parallel Link
Station No. 0 Station No. 1 Station No. 7
M1000 to M1063 M1000 to M1063 M1000 to M1063
D0 to D7 D0 to D7 D0 to D7
M1064 to M1127 M1064 to M1127 M1064 to M1127
D10 to D17 D10 to D17 D10 to D17 D

Computer Link

M1448 to M1511 M1448 to M1511 M1448 to M1511


D70 to D77 D70 to D77 D70 to D77

2. Applicable PLCs
E

Communication
Inverter
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX1S,FX1N, FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX2N FX2NC FX3S
FX1NC FX3GC FX3UC

Communication


(Ver. 2.00 or

(Ver. 2.00 or
F
applicability

(RS/RS2 Instruction)
Communication
Non-Protocol
later) later)

3. Communication targets
Between FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC Series PLCs

4. Function G
This network allows up to eight connected FX PLCs to automatically transfer data among the connected

(FX2N-232IF)
Communication
Non-Protocol
PLCs.
In the network, data can be transferred among PLCs for devices determined in the refresh range, and those
devices can be monitored by every PLC.

5. Applications
By this network, data link can be achieved in a small-scale system, and the machine information can be
H
Communication
Programming

transferred between machines.

I
Maintenance
Remote

Apx.A
models
Discontinued

A-7
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.4 Parallel Link


Refer to the "Parallel Link" section.

1. Outline
RS-485

RS-485
FX CPU FX CPU
Master Slave
Terminal station station
resistor
Terminal
resistor
Master station Slave station
M800 to M899 M800 to M899
D490 to D499 D490 to D499
M900 to M999 M900 to M999
D500 to D509 D500 to D509
100 bit devices (M) and 10 word devices (D)
Number of connectable FX PLCs: 2
Total extension distance: 500 m (1640' 5") [50 m (164' 0") when 485BD is connected]*1

*1. The distance is different for the FX2-40AW/AP.

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX1S,FX1N, FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX2N FX2NC FX3S
FX1NC FX3GC FX3UC

Communication
(Ver. 1.20 or (Ver. 1.04 or
applicability
later) later)

3. Communication targets
Between FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC
Series PLCs

4. Function
This network automatically transfers data for 100 bit devices (M) and 10 data registers (D) between two PLCs
of the same series.
Between PLCs in the FX0N, FX1S or FX3S Series, data can be transferred for 50 bit devices (M) and 10 data
registers (D).

5. Applications
Information can be transferred between two FX PLCs.
(It is recommended to use the N:N Network when connecting two PLCs of the same series among the FX1S,
FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC Series. N:N Network functionality supports
linking of up to eight FX PLC units, therefore it offers excellent future expandability options.)

A-8
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.5 Computer Link

Common Items
Refer to the "Computer Link" section.

1. Outline
1) 1-to-N connection (RS-485) B
A computer link

N:N Network
RS-485

RS-485

RS-485
Terminal FXCPU FXCPU ACPU
RS-232C resistor


RS-485 Terminal
resistor
Personal computer FX-485PC-IF C

Parallel Link
Number of connectable FX/A PLCs : 16 maximum
Total extension distance : 500 m (1640' 5") [50 m (164' 0") when 485BD is connected]

2) 1-to-1 connection (RS-232C)


D

Computer Link
RS-232C

FXCPU

Personal computer
E
Number of connectable FX PLCs : 1

Communication
Inverter
Total extension distance : 15 m (49' 2")

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
F
FX1S,FX1N, FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX2N FX2NC FX3S

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1NC FX3GC FX3UC

Communication
(Ver. 3.30 or (Ver. 1.20 or (Ver. 1.06 or
applicability
later) later) later)

3. Communication targets G

(FX2N-232IF)
Communication
Non-Protocol
Between FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U, FX3UC Series
PLCs, A Series PLCs and personal computers

4. Function
This link allows connection of up to sixteen FX or A (including A1FX CPU) PLCs to a personal computer for
data transfer when the personal computer directly specifies devices in the connected PLCs. H
Communication
Programming

5. Applications
By this link, production, inventory, etc. can be controlled.

I
Maintenance
Remote

Apx.A
models
Discontinued

A-9
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.6 Inverter Communication


Refer to the "Inverter Communication" section.

1. Outline
RS-485

FXCPU

Terminal Terminal
resistor resistor
Inverter Inverter Inverter

Number of connectable inverters : 8 maximum


Total extension distance : 500 m (1640' 5") [50 m (164' 0") when 485BD is connected]

2. Applicable PLCs
:Applicable
:Not applicable
FX2N, FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX3S
FX2NC FX3GC FX3UC
Communication

applicability

3. Communication targets
1) For FX2N or FX2NC PLC
FREQROL Series (S500, E500 and A500) inverters
2) For FX3S, FX3G, FX3GC, FX3U or FX3UC PLC
FREQROL Series (S500, E500, A500, F500, V500, D700, E700, A700, F700, A800 and F800) inverters

The table below shows PLC versions applicable to each inverter.


FREQROL-S500/ FREQROL-F500/ FREQROL-F700/ FREQROL-D700/ FREQROL-A800/
PLC
E500/A500 V500 A700 E700 F800
FX2N,
Ver. 3.00 or later
FX2NC
FX3S Ver. 1.00 or later Ver.1.10 or later
FX3G Ver. 1.10 or later Ver.2.22 or later
FX3GC Ver. 1.40 or later Ver.2.22 or later
FX3U Ver. 2.20 or later Ver. 2.32 or later Ver.3.11 or later
FX3UC Ver. 1.00 or later Ver. 2.20 or later Ver. 2.32 or later Ver.3.11 or later

4. Function
This communication allows the connection of inverters (computer link) in accordance with RS-485 to control
operations and change parameters.

5. Applications
Operations with up to eight inverters can be controlled from a PLC.

A-10
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.7 Non-protocol Communication

Common Items
Refer to the "Non-protocol Communication (RS/RS2 instruction)" section.
Refer to the "Non-protocol Communication (FX2N-232IF)" section.

1. Outline
B

N:N Network
RS-485
RS-422/
FXCPU
500 m (1640' 5")
Bar code maximum
Personal computer reader Printer [50 m (164' 0") when
485BD is connected]
C

Parallel Link
RS-232C
FXCPU
15 m (49' 2")
Bar code maximum
Personal computer reader Printer
D
RS-232C RS-422

Computer Link
Converter
FX-232AWC-H
FX-232AWC *1
FXCPU
FX-232AW
Bar code 15m (49' 2") FX-422CAB0
Personal computer reader Printer maximum
Standard built-in port E
(RS-422)

Communication
Inverter
*1. Available only in FX3G, FX3GC PLC.

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable F
1) Non-protocol communication (RS instruction)

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX2N FX2NC FX3S
FX3GC FX3UC

Communication
(Ver. 3.00 (Ver. 1.20 (Ver. 1.06
applicability
or later) or later) or later) G

(FX2N-232IF)
Communication
Non-Protocol
2) Non-protocol communication (RS2 instruction)
FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX2N,FX2NC FX3S
FX3GC FX3UC
Communication

applicability H
3) Non-protocol communication (FX2N-232IF)
Communication
Programming

FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX2N,FX2NC FX3S
FX3GC FX3UC
Communication

applicability
I
3. Communication targets
Maintenance
Remote

Bar code readers, printers, personal computers (micro computer boards), measuring instruments, etc.

4. Function
This communication allows non-protocol serial communication between equipment with an RS-232C or RS-
422/RS-485 interface. Apx.A
5. Applications
models
Discontinued

Communication with a bar code reader, printer, personal computer (micro computer board), measuring
instrument, etc.

A-11
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.8 MODBUS Communication


For details, refer to FX3S/FX3G/FX3GC/FX3U/FX3UC User's Manual
- MODBUS Serial Communication Edition.

1. Outline
1) In the case of the RS-485
RS-485

RS-485

RS-485
FXCPU FXCPU FXCPU
master slave slave
Terminal No.1 No.32
resistor
Terminal resistor

Number of connectable units: Master 1


: Slave 32 maximum
Total extension distance : 500 m (16405) maximum

2) In the case of the RS-232C


RS-232C

RS-232C

FXCPU FXCPU
master slave

Number of connectable units: Master 1


: Slave 1
Total extension distance : 15 m (492) maximum

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX3U,
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX2N,FX2NC FX3S FX3G FX3GC
FX3UC

Communication
(Ver. 1.30 (Ver. 2.40
applicability
or later) or later)

3. Communication targets
MODBUS-compatible equipment

4. Function
This function enables MODBUS communication with MODBUS-compatible equipment in accordance with
RS-232C or RS-485.

5. Applications
Line control in the decentralized or centralized method.

A-12
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.9 Programming Communication

Common Items
Refer to the "Programming Communication" section.

1. Outline
1) Standard built-in port in accordance with RS422 (programming tool or personal computer) B
Programming tool

N:N Network
RS-422 Cable
FX-10P(-E)/FX-20P(-E)/FX-30P, etc. C

Parallel Link
Programming
tool
FX-232AWC-H
FX-232AWC FXCPU
FX-232AW
Cable Cable
RS-232C RS-232CRS-422
converter Standard built-in port
(RS-422) D

Computer Link
Personal
computer FX-USB-AW
Cable
USB
USBRS-422
converter
2) Communication equipment operating in accordance with RS-422 (programming tool or personal E
computer)

Communication
Inverter
Programming tool

RS-422 Cable
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX-10P(-E)/FX-20P(-E)/FX-30P, etc.

Programming
tool
RS-422

FX-232AWC-H
FX-232AWC FXCPU
Cable
FX-232AW
RS-232CRS-422
Cable G
RS-232C
converter

(FX2N-232IF)
Communication
Non-Protocol
Personal
computer FX-USB-AW
Cable
USB
USBRS-422 H
converter
Communication
Programming

3) Communication equipment operating in accordance with RS-232C (personal computer)


Programming tool
RS-232C

Cable
FXCPU
I
RS-232C
Maintenance
Remote

Personal computer
4) Standard built-in port in accordance with USB (personal computer)
Programming tool

Apx.A
FXCPU
models
Discontinued

USB
Cable
Personal
computer USB Standard built-in port

A-13
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

5) Communication equipment operating in accordance with USB (personal computer)


Programming tool

USB
FXCPU
USB Cable
Personal computer

6) Ethernet adapter (personal computer)


Programming tool

adapter
Ethernet
FXCPU
Ethernet
Cable Cable

Hub

adapter
Ethernet
Personal computer
FXCPU
Cable

A-14
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
2. Applicable PLCs

Common Items
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
PLC FX2(FX), FX2C FX0N FX1S, FX1N FX1NC FX2N FX2NC
Standard built-in port in
accordance with RS-422
B

N:N Network
Communication equipment
operating in accordance with
RS-422(-BD)
Communication (-BD)
equipment operating
in accordance with (ADP) C
RS-232C

Parallel Link
Standard built-in port in

accordance with USB
Communication equipment
operating in accordance with
USB(-BD)*1 D
Ethernet adapter

Computer Link
FX3UC FX3UC
PLC FX3S FX3G FX3GC FX3U
(D, DS, DSS) (LT, LT-2)
Standard built-in port in

accordance with RS-422
Communication equipment
E

Communication
Inverter
operating in accordance with
RS-422(-BD)
Communication (-BD)
equipment operating
in accordance with (ADP)
RS-232C F
Standard built-in port in

(RS/RS2 Instruction)
Communication
Non-Protocol

accordance with USB
Communication equipment
operating in accordance with
USB(-BD)*1
G
Ethernet adapter *2 (Ver. 2.00 (Ver. 2.00 or (Ver. 3.10 (Ver. 3.10 or (Ver. 3.10 or

(FX2N-232IF)
Communication
Non-Protocol
or later) later) or later) later) later)

*1. When using USB communication with a model that does not support USB communication equipment
(-BD), use the FX-USB-AW.
However, FX2(FX) and FX2C PLCs do not support the FX-USB-AW. Use the standard built-in port in
accordance with USB in the FX3S, FX3G and FX3GC PLCs. H
Communication
Programming

*2. The FX3U-ENET-ADP Ver. 1.20 or later is applicable to the FX3S PLC.

3. Communication targets
Personal computer and programming tool

4. Function I
This communication allows connection of a personal computer or programming tool to a standard port built in
Maintenance
Remote

a PLC or optional connector to execute sequence programs.

5. Applications
1) Programs can be changed and monitored using a personal computer or programming tool.
2) A personal computer (for changing programs) can be directly connected in accordance with RS-232C. Apx.A
models
Discontinued

3) While the standard programming connector built in an FX PLC is used for connecting a display unit, a
personal computer or programming tool can be connected at the same time for monitoring and
transferring data.

A-15
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.10 Remote Maintenance


Refer to the "Remote Maintenance" section.

1. Outline
1) Remote access (GX Works2, GX Developer or FXGP/WIN)
Programming tool
Line
(such as general subscriber's

RS-232C
telephone line)
FXCPU

Personal computer Modem Modem

2) File transfer (FXGP/WIN)


Programming tool Programming
Line tool
(such as general subscriber's
telephone line)

Personal computer Modem Modem Personal computer

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX2N, FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX1S,FX1N,FX1NC FX3S
FX2NC FX3GC FX3UC
Communication applicability

3. Communication target
Personal computer (GX Works2, GX Developer or FXGP/WIN)

4. Function
This communication allows connection between a modem on the PLC side and a modem on the personal
computer side through a line (cellular phone or general subscribers telephone line) for PLC monitoring or
transferring from the personal computer.
The FXGP/WIN allows transfer of file data between personal computers.

5. Applications
By this communication, programs in a PLC located in a remote location can be changed and maintained.

A-16
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.11 CC-Link/LT Network

Common Items
For FX3UC-32MT-LT(-2) built-in CC-Link/LT master, refer to FX3UC Hardware Edition.
For the FX2N-64CL-M, refer to FX2N-64CL-M USERS MANUAL (Detailed Volume).

1. Outline
Main line length
B

N:N Network
Master
FXCPU
Terminal resistor
Terminal
resistor C
Remote Remote Remote Remote Remote

Parallel Link
I/O I/O I/O I/O I/O Branch line
length
Remote
I/O

Number of connectable units : 64 (stations) D


Total extension length : 500 m (1640' 5") (main line length)

Computer Link
2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable E
FX2N, FX3G, FX3U,

Communication
Inverter
PLC FX2(FX),FX2C FX0N FX1S FX1N,FX1NC FX3S
FX2NC FX3GC FX3UC
Communication applicability

3. Communication target
Equipment operating in accordance with the CC-Link/LT network standard F

(RS/RS2 Instruction)
Communication
Non-Protocol
4. Function
This network allows remote control of I/O information for sensors, lamps, etc.
Input (X) numbers and output (Y) numbers can be handled, and I/O points can be assigned continuously even
if 2-point or 4-point type remote I/O units are being used.

5. Applications G
Wire conservation for inputs and outputs.

(FX2N-232IF)
Communication
Non-Protocol
6. Detailed information on CC-Link/LT
For product information on CC-Link, refer to the CC-Link Partner Association's homepage or catalogues
(issued by the CC-Link Partner Association).
CC-Link Partner Association's homepage: http://www.cc-link.org/ H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-17
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.12 AnyWireASLINK
For details, refer to the FX3U-128ASL-M User's Manual.

1. Outline

Terminating
FXCPU AnyWireASLINK unit
master
Slave
module

Slave
module

Slave Slave
module module

Number of connectable units : 128 maximum


Total extension distance : 200 m (6562)
The FX3U-128ASL-M AnyWireASLINK master block is jointly developed and manufactured by Mitsubishi and
Anywire Corporation.

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX2(FX), FX1N, FX2N, FX3G, FX3U,
PLC FX0N FX1S FX3S
FX2C FX1NC FX2NC FX3GC FX3UC
Communication

applicability (Ver. 2.20 or later)

3. Communication targets
Slave modules for AnyWireASLINK

4. Function
This network allows remote control of I/O information for sensors and LED.

5. Applications
Wire conservation for inputs and outputs.

A-18
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.13 AS-i system

Common Items
For details, refer to the FX2N-32ASI-M User's Manual.

1. Outline
AS-i flat cable B
AS-i

N:N Network
FXCPU
master
Slave

Repeater

AS-i power AS-i power


C
Slave Slave Slave

Parallel Link
supply supply

Number of connectable units : 31 slave units


Total extension distance : 100 m (328' 1")
[300 m (984' 3") maximum when two repeaters are connected]
Terminal resistors are not required. D

Computer Link
2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable

PLC FX2(FX),FX2C FX0N FX1S FX1N,FX1NC FX2N FX2NC FX3S


FX3G, FX3U, E
FX3GC FX3UC

Communication
Inverter
Communication applicability *1

*1. FX2NC-MT-D/UL and FX2NC-M-DSS(-T-DS) PLCs are not applicable.

3. Communication targets
Slave units (sensors and actuators) for AS-i
F

(RS/RS2 Instruction)
Communication
Non-Protocol
4. Function
This network allows remote control of I/O information for sensors and actuators (slave units). The automatic
address assignment function enables easy replacement of a slave unit when it has failed.

5. Applications G
Wire conservation for inputs and outputs.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-19
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

1.2.14 Internet Mail Sending


For the detains, refer to the FX-232DOPA USERS MANUAL.
(Only Japanese manual is available for this product.)

1. Outline
FX-232DOPA

RS-232C
FXCPU

DoPa Mobile Ark Antenna


9601D
Provider

In accordance with DoPa

Internet

Cellular phone

Personal computer

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
FX2N, FX3G, FX3U,
PLC FX2(FX),FX2C FX0N FX1S FX1N,FX1NC FX3S
FX2NC FX3GC FX3UC
Communication applicability

3. Communication targets
Personal computer and cellular phone which can receive internet mails

4. Function
This setting sends an electronic mail from a PLC to notify the facility operation status, etc. to a personal
computer or cellular phone which can receive electronic mails.
This function is applicable through dial-up connection to a mail server using a combination of FX-232DOPA
and DoPa Mobile Ark9601D by NTT DoCoMo.

5. Applications
Monitoring of unmanned facilities, monitoring of facilities located in distant places, monitoring of facilities
inside factories and distribution of logging data

A-20
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

A
1.2.15 Short Mail Sending

Common Items
For details, refer to the FX1S/FX1N/FX2N/FX1NC/FX2NC PLC PROGRAMMING MANUAL.
(Only the Japanese Manual is available.)

1. Outline
Line
B

N:N Network
(such as general subscriber's NTT DoCoMo
RS-232C

telephone line) Short Mail Center


FXCPU

Modem

Parallel Link
Cellular phone

2. Applicable PLCs
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
D

Computer Link
FX2(FX), FX1N, FX3G, FX3U,
PLC FX0N FX1S FX2N FX2NC FX3S
FX2C FX1NC FX3GC FX3UC
Communication

applicability (Ver. 3.00 or later) (Ver. 3.00 or later)

3. Communication targets
E

Communication
Inverter
Cellular phones by NTT DoCoMo with a contract for i-mode or short mail

4. Function
This function sends a short mail from a PLC to notify the facility operation status, etc. to a cellular phone by
NTT DoCoMo which can receive short mails.
This function is applicable through connection in a line to a Short Mail Center of NTT DoCoMo. F

(RS/RS2 Instruction)
Communication
Non-Protocol
5. Applications
Monitoring of unmanned facilities, monitoring of facilities located in distant places and monitoring of facilities
in factories

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-21
FX Series PLC User's Manual - Data Communication Edition 1 Introduction
Common Items 1.2 Outline and Features of Communication Types

MEMO

A-22
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.1 Relationship between Equipment and Communication Types

Common Items
2. Communication Types and Communication Equipment
This chapter explains which communication types are supported by serial ports of communication equipment B
and connectors of networks.

N:N Network
For the communication equipment required in the system configuration, refer to a description later.
Refer to "2.3 Combination of Communication Equipment (Block Diagram)".

2.1 Relationship between Equipment and Communication Types


C

Parallel Link
The figure below shows the relationship between communication equipment and communication types:

Communication adapter Built-in port


Link I/O link
N:N Network
Parallel link
CC-Link/LT D
(built in for FX3UC-32MT-LT(-2))
Computer link

Computer Link
Inverter communication General-purpose serial communication
MODBUS communication
Ethernet communication Non-protocol communication
Ethernet (RS2 instruction)
General-purpose serial communication
Non-protocol communication
Sequence program
Programming communication
E
(RS/RS2 instruction)

Communication
Inverter
Sequence program
Programming communication
Remote maintenance
Electronic mail sending
Internet mail F
Short mail

(RS/RS2 Instruction)
Communication
Non-Protocol
Communication types
G
FX PLC main unit

(FX2N-232IF)
Communication
Non-Protocol
Expansion board Special function equipment
Link Link
H
Communication
Programming

N:N Network CC-Link


Parallel link
Computer link General-purpose serial communication
Inverter communication Non-protocol communication
General-purpose serial communication (FX2N-232IF)

Non-protocol communication I/O link I


(RS/RS2 instruction) CC-Link/LT
Maintenance
Remote

Sequence program
AnyWireASLINK

AS-i system
Programming communication MELSEC I/O LINK
Remote maintenance
Electronic mail sending
Electronic mail sending
Internet mail
Internet mail
Apx.A
Short mail
models
Discontinued

A-23
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2 Communication Equipment Applicability Map


The table below shows the communication types applicable in each FX Series and includes the supporting
communication equipment. The communication types can be used when a built-in port or piece of
communication equipment is connected, but some of them may not be applicable at the same time.
2.2.1 FX3U and FX3UC (D, DS, DSS) PLCs

Data Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter MODBUS
CC-Link
Network link link communication communication
MODBUS
Product
Manual name (Obtain manuals if necessary.) This manual Communication
manual
Edition
FX3U-USB-BD USB
FX3U-232-BD
*1
FX3U-232ADP(-MB) RS-232C *6
FX2N-232IF
FX3U-485-BD *5 *5
RS-485
FX3U-485ADP(-MB)*1 *5 *5 *6
FX3U-422-BD
RS-422
Standard built-in port
FX3U
PLC FX2N-16CCL-M *2
FX3U-16CCL-M *3*4
FX2N-32CCL
FX3U-64CCL
FX2N-64CL-M
FX3U-128ASL-M
FX2N-32ASI-M
FX2N-16LNK-M
FX3U-ENET-ADP*1

*1. The expansion board is required to connect the FX3U PLC.


*2. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/
or FX2N-32ASI-M.
*3. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*4. The FX3U-16CCL-M can be used at the same time with the FX3U-128ASL-M when CC-Link parameters
are set using network parameters.
*5. Two channels cannot be set at the same time in N:N Network and parallel link.
N:N Network and parallel link cannot be used together.
*6. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.
*7. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*8. The FX2N-32ASI-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/
or FX2N-16CCL-M.
*9. Two channels cannot be set at the same time in remote maintenance.

A-24
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
B

N:N Network
Ethernet General-purpose Mail
Wire-reducing network Sequence program
communication communication sending
Non-protocol CC-Link/ AnyWire AS-i MELSEC- Remote Internet mail
Ethernet Programming
communication LT ASLINK system I/O LINK maintenance sending

FX-232DOPA C
Product manual This manual Product manual This manual
User's Manual

Parallel Link

*9

*9

D

Computer Link





E

Communication
Inverter




*4*7
F

(RS/RS2 Instruction)
Communication
Non-Protocol
*8


(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-25
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Data Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter MODBUS
CC-Link
Network link link communication communication
MODBUS
Product
Manual name (Obtain manuals if necessary.) This manual Communication
manual
Edition
FX3U-232ADP(-MB) *6
RS-232C
FX2N-232IF*1
*5 *5
FX3U-485ADP(-MB) RS-485 *6
Standard built-in port RS-422
FX2N-16CCL-M*1 *2
FX3UC FX3U-16CCL-M*1 *3*4
(D,DS, *1
DSS) FX2N-32CCL
PLC FX3U-64CCL*1
FX2N-64CL-M*1
FX3U-128ASL-M*1
*1
FX2N-32ASI-M
FX2N-16LNK-M*1
FX3U-ENET-ADP
*1. The FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3UC PLC.
*2. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/
or FX2N-32ASI-M.
*3. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*4. The FX3U-16CCL-M can be used at the same time with the FX3U-128ASL-M when CC-Link parameters
are set using network parameters.
*5. Two channels cannot be set at the same time in N:N Network and parallel link.
N:N Network and parallel link cannot be used together.
*6. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.
*7. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*8. The FX2N-32ASI-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/
or FX2N-16CCL-M.
*9. Two channels cannot be set at the same time in remote maintenance.

A-26
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
Ethernet General-purpose Mail
Wire-reducing network Sequence program
communication communication sending
Non-protocol CC-Link/ AnyWire AS-i MELSEC- Remote Internet mail
Ethernet Programming
communication LT ASLINK system I/O LINK maintenance sending

Product manual This manual Product manual This manual


FX-232DOPA B
User's Manual

N:N Network
*9


C

Parallel Link





D

Computer Link
*4*7

*8


E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-27
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2.2 FX3UC-32MT-LT(-2) PLCs

Data Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter MODBUS
CC-Link
Network link link communication communication
MODBUS
Product
Manual name (Obtain manuals if necessary.) This manual Communication
manual
Edition
FX3U-USB-BD USB
FX3U-232-BD
FX3U-232ADP(-MB)*1 RS-232C *7
FX2N-232IF*2
FX3U-485-BD *6 *6
RS-485
FX3U-485ADP(-MB)*1 *6 *6 *7
FX3U-422-BD
RS-422
Standard built-in port
FX3UC-
32MT- FX2N-16CCL-M*2 *3
LT(-2)
FX3U-16CCL-M*2 *4*5
PLC
FX2N-32CCL*2
*2
FX3U-64CCL
FX2N-64CL-M*2
Built-in type CC-Link/

LT master
FX3U-128ASL-M*2
FX2N-32ASI-M*2
FX3U-ENET-ADP*1

*1. The expansion board is required to connect the FX3UC-32MT-LT(-2) PLC.


*2. The FX2NC-CNV-IF or FX3UC-IPS-5V is required to connect the FX3UC-32MT-LT(-2) PLC.
*3. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/
or FX2N-32ASI-M.
*4. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*5. The FX3U-16CCL-M can be used at the same time with the FX3U-128ASL-M when CC-Link parameters
are set using network parameters.
*6. Two channels cannot be set at the same time in N:N Network and parallel link.
N:N Network and parallel link cannot be used together.
*7. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.
*8. For the FX2N-64CL-M, refer to FX2N-64CL-M User's Manual.
For FX3UC built-in CC-Link/LT master, refer to FX3UC Hardware Edition.
*9. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*10. The FX2N-32ASI-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/
or FX2N-16CCL-M.
*11. Two channels cannot be set at the same time in remote maintenance.

A-28
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
Ethernet General-purpose Mail
Wire-reducing network Sequence program
communication communication sending
Non-protocol CC-Link/ AnyWire AS-i MELSEC- Remote Internet mail
Ethernet
communication LT ASLINK system I/OLINK
Programming
maintenance sending B

N:N Network
FX-232DOPA
Product manual This manual Product manual This manual
User's Manual


*11

*11 C

Parallel Link





D

Computer Link




*8
E

Communication
Inverter
*8

*5*9
*10



F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-29
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2.3 FX3G and FX3GC PLCs

Data Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter MODBUS
CC-Link
Network link link communication communication
MODBUS
Product
Manual name (Obtain manuals if necessary.) This manual Communication
manual
Edition
Standard built-in port USB
FX3G-232-BD
RS-232C
FX3U-232ADP(-MB)*1 *6
FX3G-485-BD *5 *5
FX3G-485-BD-RJ RS-485 *5 *5
FX3U-485ADP(-MB)*1 *5 *5 * 6
FX3G-422-BD
FX3G RS-422
PLC Standard built-in port
FX2N-16CCL-M *2

FX3U-16CCL-M *3*4
FX2N-32CCL
FX3U-64CCL
FX2N-64CL-M
FX3U-128ASL-M
FX3U-ENET-ADP*1
Standard built-in port USB
FX3U-232ADP(-MB) RS-232C * 6
FX3U-485ADP(-MB) RS-485 *5 *5 * 6
Standard built-in port RS-422
FX2N-16CCL-M*10 *2
FX3GC
PLC FX3U-16CCL-M*10 *3*4
FX2N-32CCL*10
FX3U-64CCL*10
FX2N-64CL-M*10
FX3U-128ASL-M*10
FX3U-ENET-ADP

*1. The FX3G-CNV-ADP is required to connect the FX3G PLC.


*2. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M and/or FX3U-128ASL-M.
*3. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M.
*4. The FX3U-16CCL-M can be used at the same time with the FX3U-128ASL-M when CC-Link parameters
are set using network parameters.
*5. Two channels cannot be set at the same time in N:N Network and parallel link.
N:N Network and parallel link cannot be used together.
*6. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.
*7. Only the RS2 instruction is supported.
*8. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M.
*9. Two channels cannot be set at the same time in remote maintenance.
*10. The FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect the FX3GC PLC.

A-30
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
Ethernet General-purpose Mail
Wire-reducing network Sequence program
communication communication sending
Non-protocol CC-Link/ AnyWire AS-i MELSEC- Remote Internet mail
Ethernet
communication LT ASLINK system I/O LINK
Programming
maintenance sending B

N:N Network
FX-232DOPA
Product manual This manual Product manual This manual
User's Manual


*9

*9 C

Parallel Link




*7
D

Computer Link





E

Communication
Inverter
*4*8


*9






F

(RS/RS2 Instruction)
Communication
Non-Protocol
*7













G

(FX2N-232IF)
Communication
Non-Protocol

*4*8

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-31
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2.4 FX3S PLC

Data Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter MODBUS
CC-Link
Network link link communication communication
MODBUS
Product
Manual name (Obtain manuals if necessary.) This manual Communication
manual
Edition
Standard built-in port USB
FX3G-232-BD
RS-232C
FX3U-232ADP(-MB)*1 * 2
FX3G-485-BD
FX3S
FX3G-485-BD-RJ RS-485
PLC
FX3U-485ADP(-MB)*1 * 2
FX3G-422-BD
RS-422
Standard built-in port
FX3U-ENET-ADP*1

*1. The FX3S-CNV-ADP is required to connect the FX3S PLC.


*2. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-32
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
Ethernet General-purpose
Wire-reducing network Sequence program Mail sending
communication communication
Non-protocol MELSEC-I/O Remote Internet mail
Ethernet
communication
CC-Link/LT AS-i system
LINK
Programming
maintenance sending B

N:N Network
FX-232DOPA
Product manual This manual Product manual This manual
User's Manual

Parallel Link




D

Computer Link

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-33
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2.5 FX2N and FX2NC PLCs

Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter
CC-Link
Network link link communication

Product
Manual name (Obtain manuals if necessary.) This manual
manual

FX2N-232-BD
FX2NC-232ADP*1
RS-232C
FX0N-232ADP*1 *3
FX2N-232IF
FX2N-485-BD
FX2NC-485ADP*1 RS-485
FX2N FX0N-485ADP*1
PLC FX2N-422-BD
RS-422
Standard built-in port
FX2N-16CCL-M *2
FX2N-32CCL
FX2N-64CL-M
FX2N-32ASI-M
FX2N-16LNK-M
FX2NC-232ADP
FX0N-232ADP RS-232C *3
FX2N-232IF*4
FX2NC-485ADP
RS-485
FX0N-485ADP
FX2NC Standard built-in port RS-422
PLC
FX2N-16CCL-M*4 *2
FX2N-32CCL*4
FX2N-64CL-M*4
FX2N-32ASI-M*4
FX2N-16LNK-M*4

*1. The FX2N-CNV-BD is required to connect the FX2N PLC.


*2. The FX2N-16CCL-M cannot be used at the same time with the FX2N-32ASI-M.
*3. It is recommended to use a connector or thin type FX2NC-232ADP (9-pin D-Sub).
*4. The FX2NC-CNV-IF is required to connect the FX2NC PLC.
*5. The FX2NC-MT-D/UL and FX2NC-M-DSS(-T-DS) does not support this connection.

A-34
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
General-purpose
I/O link Sequence program Mail sending
communication
Non-protocol
communication
CC-Link/
LT
AS-i
system
MELSEC-I/O
LINK
Programming
Remote
maintenance
Internet mail
sending
Short mail
sending
B

N:N Network
FX1S, FX1N, FX2N,
FX-232DOPA FX1NC, FX2NC
This manual Product manual This manual
User's Manual Programming
Manual


C

Parallel Link
*3 *3 *3 *3 *3




D

Computer Link




E

Communication
Inverter
*2


*3 *3 *3
*3 *3
F

(RS/RS2 Instruction)
Communication
Non-Protocol




G

(FX2N-232IF)
Communication
Non-Protocol
*2*5

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-35
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2.6 FX1S, FX1N, and FX1NC PLCs

Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter
CC-Link
Network link link communication
Product
Manual name (Obtain manuals if necessary.) This manual
manual
FX1N-232-BD
FX2NC-232ADP*1 RS-232C
FX0N-232ADP*1 *2
FX1S FX1N-485-BD
PLC FX2NC-485ADP*1 RS-485
FX0N-485ADP*1
FX1N-422-BD
RS-422
Standard built-in port
FX1N-232-BD
FX2NC-232ADP*1 RS-232C
FX0N-232ADP*1 *2
FX1N-485-BD
FX2NC-485ADP*1 RS-485
FX0N-485ADP*1
FX1N
FX1N-422-BD
PLC RS-422
Standard built-in port
FX2N-16CCL-M *3
FX2N-32CCL
FX2N-64CL-M
FX2N-32ASI-M
FX2N-16LNK-M
FX2NC-232ADP
RS-232C
FX0N-232ADP *2

FX2NC-485ADP
RS-485
FX0N-485ADP
FX1NC Standard built-in port RS-422
PLC FX2N-16CCL-M*4 *3
FX2N-32CCL*4
FX2N-64CL-M*4
FX2N-32ASI-M*4
FX2N-16LNK-M*4

*1. The FX1N-CNV-BD is required to connect the FX1S or FX1N PLC.


*2. It is recommended to use a connector or thin type FX2NC-232ADP (9-pin D-Sub).
*3. The FX2N-16CCL-M cannot be used at the same time with the FX2N-32ASI-M.
*4. The FX2NC-CNV-IF is required to connect the FX1NC PLC.

A-36
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
General-purpose
I/O link Sequence program Mail sending
communication
Non-protocol
communication
CC-Link/LT AS-i system
MELSEC-I/O
LINK
Programming
Remote
maintenance
Internet mail
sending
B

N:N Network
FX-232DOPA
This manual Product manual This manual
User's Manual


*2

*2

*2

*2 C

Parallel Link




D

Computer Link


*2 *2 *2 *2



E

Communication
Inverter





F

(RS/RS2 Instruction)
Communication
Non-Protocol

*3


*2 *2 *2
G
*2

(FX2N-232IF)
Communication
Non-Protocol









H
Communication
Programming


*3

I
Maintenance
Remote

Apx.A
models
Discontinued

A-37
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

2.2.7 FX0N PLCs

Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter
CC-Link
Network link link communication
Product
Manual name (Obtain manuals if necessary.) This manual
manual
FX2NC-232ADP
RS-232C
FX0N-232ADP *1

FX2NC-485ADP
RS-485
FX0N-485ADP
FX0N Standard built-in port RS-422
PLC FX2N-16CCL-M
FX2N-32CCL
FX2N-64CL-M
FX2N-32ASI-M
FX2N-16LNK-M

*1. It is recommended to use a connector or thin type FX2NC-232ADP (9-pin D-Sub).


*2. Only Japanese manual is available for this product.

2.2.8 FX1, FX2(FX), FX2C, FX0 and FX0S PLCs (reference)

Link
Communication Communication
PLC
equipment specifications N:N Parallel Computer Inverter
CC-Link
Network link link communication
Product
Manual name (Obtain manuals if necessary.) This manual
manual
FX1
Standard built-in port RS-422
PLC
FX-232ADP RS-232C

FX2(FX) FX-485ADP RS-485


PLC FX-40AW
FX2C Optical
PLC FX-40AP
communication
Standard built-in port RS-422
FX0
Standard built-in port RS-422
PLC
FX0S
Standard built-in port RS-422
PLC

*1. Only Japanese manual is available for this product.

A-38
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.2 Communication Equipment Applicability Map

Common Items
General-purpose
I/O link Sequence program Mail sending
communication
Non-protocol
communication
CC-Link/LT AS-i system
MELSEC-I/O
LINK
Programming
Remote
maintenance
Internet mail
sending
B

N:N Network
FX-232DOPA
This manual Product manual This manual
User's Manual*2

*1
C

Parallel Link




D

Computer Link

Communication
Inverter
General-purpose
I/O link Sequence program Mail sending F
communication

(RS/RS2 Instruction)
Communication
Non-Protocol
Non-protocol MELSEC-I/O Remote Internet mail
CC-Link/LT AS-i system Programming
communication LINK maintenance sending
FX-232DOPA
This manual Product manual This manual
User's Manual*1

(FX2N-232IF)
Communication
Non-Protocol


H
Communication
Programming



I
Maintenance
Remote

Apx.A
models
Discontinued

A-39
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

2.3 Combination of Communication Equipment (Block Diagram)


The block diagram below shows combinations of optional communication equipment applicable in each FX Series.

2.3.1 How to look at combination pages

FX Series name Communication equipment connection type Applicable communication type

FX1N Series

A B C For special function units/blocks C , refer to the next page.


FX PLC main
unit mounting A , B and C indicate the mounting position.
(For the mounting procedure, refer to the
position respective communication equipment manual.)
B

RS-485 European
terminal block

FX1N-485-BD
N:N Network
B A
Parallel link
Selection
European Computer link
example
terminal block Non-protocol
communication
A
FX1N-CNV-BD FX2NC-485ADP

M3 terminal
block

FX0N-485ADP

RS-422 8-pin MINI-DIN, Programming


Connection female communication
condition
One line can be selected.

FX1N-422-BD
B A

European
terminal block

A Non-protocol
FX1N-CNV-BD FX2NC-485ADP communication

M3 terminal
block

FX0N-485ADP

RS-232C 9-pin D-Sub,


male

FX1N-232-BD Computer link


B A Non-protocol
communication
9-pin D-Sub, Programming
male communication
Remote
maintenance
FX1N-CNV-BD FX2NC-232ADP A

25-pin
D-Sub,
female

FX0N-232ADP

A-40
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.2 For FX3U Series

Common Items
FX3U Series

A B C For special function units/blocks C refer to the next page.


A , B , and C indicate the mounting position. (For the mounting procedure, refer to the
respective communication equipment manual.)
B

N:N Network
Either FX3U-
B ch1 232ADP(-MB),
FX3U-485ADP(-MB)
or FX3U-ENET-ADP
RDA

RS-485
RD
RDB

can be selected. European terminal N:N Network


SDA

SD SDB

block
SG

A ch2 Parallel link


Computer link
FX3U-485-BD European terminal
block Non-protocol
C
communication

Parallel Link
B A ch1
Inverter
FX3U-485ADP(-MB) communication
European terminal
block MODBUS *1
communication

FX3U-CNV-BD
B
FX3U-485ADP(-MB)
D
ch1

Computer Link
RS-422 8-pin MINI-DIN, Programming
female communication

FX3U-422-BD
B ch1 E

Communication
Inverter
RDA
RD
RDB

SD
SDA

SDB European terminal


block
SG

A ch2
FX3U-485-BD European terminal Non-protocol
communication
B A block
ch1
F
FX3U-485ADP(-MB)

(RS/RS2 Instruction)
Communication
Non-Protocol
European terminal
block

FX3U-CNV-BD FX3U-485ADP(-MB)
B ch1

RS-232C
RD

SD

9-pin D-Sub, male Computer link


G

(FX2N-232IF)
Communication
Non-Protocol
A ch2 Non-protocol
communication
FX3U-232-BD MODBUS
9-pin D-Sub, male
communication*1
B A ch1
Programming
communication
FX3U-232ADP(-MB)
9-pin D-Sub, male
Remote
maintenance
H
Communication
Programming

FX3U-232-BD FX3U-232ADP(-MB)
B ch1

USB
I
RD

SD

USB Mini-B connector Programming


communication
Maintenance
Remote

FX3U-USB-BD
A ch2
B A ch1
Ethernet Ethernet
Modular jack Programming Apx.A
FX3U-ENET-ADP communication
models
Discontinued

Modular jack
FX3U-CNV-BD FX3U-ENET-ADP

*1. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-41
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX3U Series
A , B , and C indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)
A B C
For special adapters with communication type A and communication
expansion boards B , refer to the previous page.

For master station

CC-Link
M3/M3.5
terminal block*4
FX 2N-16CCL-M
E
R
R
O
R

FX 3U -16CCL-M*1*2 FX 2N -16CCL-M *3

For remote device station


M3 terminal block CC-Link

FX2N-32CCL

For intelligent device station


M3 terminal block

FX3U-64CCL*2
Up to 8 units can be selected.

POW
ER
SD
RD

9-pin D-Sub, male Non-protocol


communication

FX2N-232IF

Dedicated connector CC-Link/LT

FX2N-64CL-M

European
AnyWireASLINK
terminal block

FX 3U-128ASL-M*2*5
U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX2N-32ASI-M
M3 terminal block AS-i system
MOD SE
E T PRJ
MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*6

M3 terminal block MELSEC-I/O LINK

FX2N-16LNK-M
*1.
The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M and/or the FX2N-32ASI-M.
*2.
Only one unit can be connected to the main unit.
*3.
The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/or
the FX2N-32ASI-M.
*4. The terminal screw size is "M3" in the FX3U-16CCL-M.
The terminal screw size is "M3.5" in the FX2N-16CCL-M.
*5. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*6. The FX2N-32ASI-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/or the
FX2N-16CCL-M.
Only one station can be used for the whole system.
Limitation in the number of connectable units
Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Therefore, the total current consumption larger than the plc current capacity reduces the number of
connectable units.
For details, refer to the respective FX PLC manual.

A-42
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.3 For FX3UC(D, DS, DSS) Series

Common Items
FX3UC(D, DS, DSS) Series

A B For special function units/blocks B , refer to the next page.


B
A and B indicate the mounting position.

N:N Network
(For the mounting procedure, refer to the respective communication equipment manual.)
Either FX3U-
232ADP(-MB),
FX3U-485ADP(-MB)
or FX3U-ENET-ADP
RS-485 A ch1 can be selected. European
terminal block


N:N Network
Parallel link
C
A

Parallel Link
ch2
Computer link

FX3U-485ADP
European Non-protocol
terminal block communication
(-MB)
Inverter
communication
FX3U-485ADP
(-MB)
MODBUS
communication*1
D

Computer Link
RS-422 A ch1
European
E

Communication
Inverter
terminal block

A ch2

FX3U-485ADP European Non-protocol


(-MB) terminal block
communication
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U-485ADP
(-MB)

(FX2N-232IF)
Communication
Non-Protocol
RS-232C A ch1
9-pin D-Sub, Computer link
male

A
Non-protocol
communication H
ch2
Communication
Programming

MODBUS *1
communication
FX3U-232ADP 9-pin D-Sub,
male Programming
(-MB) communication
Remote
FX3U-232ADP maintenance
(-MB) I
Maintenance
Remote

A ch2

A ch1
Modular jack
Ethernet Ethernet
FX3U-ENET-ADP Programming Apx.A
communication
Modular jack
models
Discontinued

FX3U-ENET-ADP

*1. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-43
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX3UC(D, DS, DSS) Series


A and B indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)
A B
For special adapters with communication type A , refer to the previous
page.

For master
station
FX 2N -16CCL-M CC-Link M3/M3.5
terminal
E
R
R
O
R

block*4
FX2NC-CNV-IF FX3U-16CCL-M*1*2 FX 2N -16CCL-M*3

For remote
device
station
M3 terminal block CC-Link

FX3UC-1PS-5V FX2N-32CCL
For intelligent
device
station
M3 terminal block

FX3U-64CCL*2
Up to 8 units can be selected.

POWER
SD

Non-protocol
RD

9-pin D-Sub,
male communication

FX2N-232IF

Dedicated CC-Link/LT
connector

FX2N-64CL-M

European AnyWireASLINK
terminal block

FX 3U-128ASL-M*2*5
U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX2N-32ASI-M

MOD SE
M3 terminal block AS-i system
PRJ
E T
MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*6

M3 terminal block MELSEC-I/O LINK

FX2N-16LNK-M
*1. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M and/or the FX2N-32ASI-M.
*2. Only one unit can be connected to the main unit.
*3. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/or
the FX2N-32ASI-M.
*4. The terminal screw size is "M3" in the FX3U-16CCL-M.
The terminal screw size is "M3.5" in the FX2N-16CCL-M.
*5. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*6. The FX2N-32ASI-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/or
the FX2N-16CCL-M.
Only one station can be used for the whole system.
Limitation in the number of connectable units
Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Accordingly, when the total current consumption is larger than the current capacity of the PLC, it is necessary
to add the power block FX3UC-1PS-5V.
For details, refer to the respective FX PLC manual.

A-44
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.4 For FX3UC-32MT-LT(-2)

Common Items
FX3UC-32MT-LT(-2)

A B C For special function units/blocks C , refer to the next page.


A , B and C indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)
B

N:N Network
B ch1 Either FX3U-
232ADP(-MB),
RDA
FX3U-485ADP(-MB)
RS-485
RD

or FX3U-ENET-ADP N:N Network


RDB

SDA

can be selected.
SD SDB

European Parallel link


SG

terminal block
A Computer link
FX3U-485-BD ch2
European
Non-protocol C
communication

Parallel Link
B A terminal block
ch1 Inverter
communication
FX3U-485ADP(-MB) MODBUS *1
European communication
terminal block
FX3U-CNV-BD
B
FX3U-485ADP(-MB)
D
ch1

Computer Link
RS-422 8-pin MINI-DIN, Programming
female communication

FX3U-422-BD
B ch1 E

Communication
Inverter
RDA
RD

European
RDB

SDA

SD

terminal block
SDB

SG

A ch2
FX3U-485-BD European Non-protocol
terminal block communication
B A ch1 F
FX3U-485ADP(-MB)

(RS/RS2 Instruction)
Communication
Non-Protocol
European
terminal block

FX3U-CNV-BD FX3U-485ADP(-MB)
B ch1

RS-232C
RD
G
9-pin D-Sub, Computer link

(FX2N-232IF)
Communication
Non-Protocol
SD

male
A ch2 Non-protocol
communication
FX3U-232-BD 9-pin D-Sub, MODBUS
male communication*1
B A ch1 Programming
FX3U-232ADP(-MB)
9-pin D-Sub,
communication
Remote
H
Communication
Programming

male maintenance

FX3U-CNV-BD FX3U-232ADP(-MB)
B ch1

USB
RD

SD
USB Mini-B connector Programming I
communication
Maintenance
Remote

FX3U-USB-BD A ch2
B A ch1
Ethernet Ethernet

FX3U-ENET-ADP
Modular jack Programming Apx.A
communication
models
Discontinued

Modular jack
FX3U-CNV-BD FX3U-ENET-ADP

*1. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-45
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX3UC-32MT-LT(-2)
A , B and C indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)
A B C
For special adapters with communication type A and communication
expansion boards B , refer to the previous page.

For master
station
M3/M3.5
FX 2N -16CCL-M CC-Link terminal
E
R
R
O
R block* 4

FX3U -16CCL-M* * FX 2N-16CCL-M*


1 2 3
FX2NC-CNV-IF

For remote
device
station
M3 terminal block CC-Link

FX3UC-1PS-5V FX2N-32CCL

For intelligent
device
Up to 7 units can be selected.

station M3 terminal block

*2
FX3U-64CCL

POWER
SD
RD

9-pin D-Sub, Non-protocol


male communication

For FX3UC-32MT-LT(-2)
built-in. FX2N-232IF Dedicated
connector

Dedicated CC-Link/LT
connector

FX2N-64CL-M

European
AnyWireASLINK
terminal block

FX 3U-128ASL-M*2*5

U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX2N-32ASI-M
M3 terminal block AS-i system
MOD SE
E T PRJ
MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*6
*1. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M and/or the FX2N-32ASI-M.
*2. Only one unit can be connected to the main unit.
*3. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/or
the FX2N-32ASI-M.
*4. The terminal screw size is "M3" in the FX3U-16CCL-M.
The terminal screw size is "M3.5" in the FX2N-16CCL-M.
*5. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M and/or FX2N-32ASI-M.
*6. The FX2N-32ASI-M cannot be used at the same time with the FX3U-16CCL-M, FX3U-128ASL-M and/or
the FX2N-16CCL-M.
Only one station can be used for the whole system.
Limitation in the number of connectable units
Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Accordingly, when the total current consumption is larger than the current capacity of the PLC, it is necessary
to add the power block FX3UC-1PS-5V.
For details, refer to the respective FX PLC manual.

A-46
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.5 For FX3G Series

Common Items
1. FX3G Series (14-point, 24-point type)

A B C For special function units/blocks C , refer to the this section 3. B

N:N Network
A , B and C indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)
B ch1
RS-485 European
terminal block N:N Network
FX3G-485-BD Parallel link
C

Parallel Link
B ch1 Computer link
Non-protocol
RJ45 connector communication
FX3G-485-BD-RJ Inverter

B A ch1
communication
MODBUS
D
communication*1

Computer Link
European
terminal block
FX3G-CNV-ADP FX3U-485ADP(-MB)

B ch1
RS-422 8-pin MINI-DIN,
female
Programming
communication
E

Communication
Inverter
FX3G-422-BD

B ch1
European
terminal block
FX3G-485-BD F

(RS/RS2 Instruction)
Communication
Non-Protocol
B ch1
Non-protocol
RJ45 connector communication
FX3G-485-BD-RJ

B A ch1 G

(FX2N-232IF)
Communication
Non-Protocol
European
terminal block
FX3G-CNV-ADP FX3U-485ADP(-MB)

B ch1 Computer link


RS-232C 9-pin D-sub,
male
Non-protocol
communication
H
Communication
Programming

FX3G-232-BD MODBUS
communication*1
B A ch1
Programming
9-pin D-sub, communication
male
Remote
FX3G-CNV-ADP FX3U-232ADP(-MB) maintenance I
Maintenance
Remote

B A ch1
Ethernet
Ethernet
Modular jack Programming
communication
FX3G-CNV-ADP FX3U-ENET-ADP

*1. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.


Apx.A
models
Discontinued

A-47
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

2. FX3G Series (40-point, 60-point type)

A B C D For special function units/blocks D, refer to the this section 3.


A , B , C and indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)

B ch1 Only either A or


C can be used
RS-485
as ch2.
European
terminal block
FX3G-485-BD
N:N Network
RJ45
B ch1 connector Parallel link
C ch2
European Computer link
terminal block Non-protocol
FX3G-485-BD-RJ communication
FX3G-485-BD
B Inverter
C ch2 communication
A ch2
*1 RJ45 MODBUS
connector communication*2
FX3G-CNV-ADP A ch1 FX3G-485-BD-RJ
FX3U-485ADP(-MB) European
terminal block
B ch1
FX3U-485ADP(-MB) European
RS-422 terminal block
8-pin MINI-DIN,
FX3G-422-BD Either FX3U- female
C ch2 Programming
B ch1 232ADP(-MB) or communication
FX3U-485ADP 8-pin MINI-DIN,
female
(-MB) can be
selected. FX3G-422-BD
FX3G-485-BD European
terminal block
B ch1 RJ45
connector
A ch2
*1
European
Non-protocol
FX3G-485-BD-RJ communication
terminal block
B A ch1
FX3U-485ADP(-MB)
European
terminal block
FX3G-CNV-ADP FX3U-485ADP(-MB)

RS-232C B ch1 Computer link


9-pin D-Sub,
male
C ch2 MODBUS
communication*2
FX3G-232-BD 9-pin D-Sub,
male Non-protocol
A ch2 communication
B A ch1 *1 FX3G-232-BD
9-pin D-Sub, Programming
male communication
FX3U-232ADP(-MB) Remote
FX3G-CNV-ADP FX3U-232ADP(-MB) 9-pin D-Sub,
male maintenance
A ch2
B A ch1 *1
Modular
Ethernet jack Ethernet
FX3U-ENET-ADP Programming
Modular communication
FX3G-CNV-ADP FX3U-ENET-ADP jack

*1. Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or FX3G-2EYT-BD is used.
*2. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-48
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
3. FX3G Series (Special unit/special block diagram)

Common Items
, , and indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.

For special adapters with communication type and


communication expansion board , , refer to this section 1,2.
B

N:N Network
For master station
M3/M3.5
FX2N-16CCL-M CC-Link
terminal block*4
C
E
R
R
O
R

FX3U-16CCL-M*1*2 FX2N-16CCL-M *3

Parallel Link
For remote device station
Up to 8 units can be selected

M3 terminal block CC-Link

D
FX2N-32CCL

Computer Link
For intelligent device station
M3 terminal block

*2
E
FX3U-64CCL

Communication
Inverter
Dedicated connector CC-Link/LT

F
FX2N-64CL-M

(RS/RS2 Instruction)
Communication
Non-Protocol
European
AnyWireASLINK
terminal block

FX 3U-128ASL-M*2*5 G

(FX2N-232IF)
Communication
Non-Protocol
*1. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M.
*2. Only one unit can be connected to the main unit.
*3. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M and/or FX3U-128ASL-M.
*4. The terminal screw size is "M3" in the FX3U-16CCL-M.
The terminal screw size is "M3.5" in the FX2N-16CCL-M. H
*5. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M.
Communication
Programming

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Accordingly, the number of connectable units depends on the system configuration.
For details, refer to the respective FX PLC manual.
I
Maintenance
Remote

Apx.A
models
Discontinued

A-49
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

2.3.6 For FX3GC Series


FX3GC Series

A B For special function units/blocks B , refer to the next page.

A and B indicate the mounting position.


(For the mounting procedure, refer to the respective communication equipment manual.)
Either FX3U-
232ADP(-MB),
A FX3U-485ADP(-MB)
ch1 or FX3U-ENET-ADP
RS-485 can be selected. European N:N Network
terminal block Parallel link
Computer link
A ch2 Non-protocol
communication
FX3U-485ADP(-MB)
European Inverter
terminal block communication
MODBUS *1
communication
FX3U-485ADP(-MB)

A ch1

RS-422 European
terminal block

A ch2
FX3U-485ADP(-MB) Non-protocol
communication
European
terminal block

FX3U-485ADP(-MB)

A ch1 Computer link


Non-protocol
communication
RS-232C 9-pin D-Sub, MODBUS
male communication*1
Programming
FX3U-232ADP(-MB) A ch2 communication

9-pin D-Sub,
Remote
maintenance
male

FX3U-232ADP(-MB)

A ch2

Modular jack
A Ethernet
ch1
FX3U-ENET-ADP Programming
Ethernet communication
Modular jack

FX3U-ENET-ADP

*1. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-50
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
FX3GC Series

Common Items
A and B indicate the mounting position.
A B (For the mounting procedure, refer to the respective communication equipment manual.)

For special adapters with communication type A , refer to the previous


page.
B

N:N Network
B B
For master station
M3/M3.5
CC-Link
terminal block*4
C
FX2N-16CCL-M
E
R
R
O
R

FX3U-16CCL-M*1*2 FX2N-16CCL-M *3

Parallel Link
FX2NC-CNV-IF
Up to 8 units can be selected.

B B
For remote
device
station
M3 terminal block CC-Link
D

Computer Link
FX3UC-1PS-5V FX2N-32CCL
B For intelligent
device
station
M3 terminal block
E

Communication
Inverter
*2
FX3U-64CCL
B

Dedicated CC-Link/LT
connector
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX2N-64CL-M
B

European
AnyWireASLINK
terminal block

FX 3U-128ASL-M*2*5 G

(FX2N-232IF)
Communication
Non-Protocol
*1. The FX3U-16CCL-M cannot be used at the same time with the FX2N-16CCL-M.
*2. Only one unit can be connected to the main unit.
*3. The FX2N-16CCL-M cannot be used at the same time with the FX3U-16CCL-M and/or FX3U-128ASL-M.
*4. The terminal screw size is "M3" in the FX3U-16CCL-M.
The terminal screw size is "M3.5" in the FX2N-16CCL-M. H
*5. The FX3U-128ASL-M cannot be used at the same time with the FX2N-16CCL-M.
Communication
Programming

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Accordingly, when the total current consumption is larger than the current capacity of the PLC, it is necessary
to add the power block FX3UC-1PS-5V.
For details, refer to the respective FX PLC manual. I
Maintenance
Remote

Apx.A
models
Discontinued

A-51
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

2.3.7 For FX3S Series


FX3S Series

A B C For special function units/blocks C are not connectable.

A , B and C indicate the mounting position.


(For the mounting procedure, refer to the respective communication equipment manual.)
B
RS-485 European
terminal block
N:N Network
FX3G-485-BD
Parallel link
B Computer link
Non-protocol
RJ45 connector communication

FX3G-485-BD-RJ Inverter
communication

B A
MODBUS *1
communication
European
terminal block
FX3S-CNV-ADP FX3U-485ADP(-MB)

B
RS-422 8-pin MINI-DIN, Programming
female communication

FX3G-422-BD

B
European
terminal block
FX3G-485-BD

RJ45 connector Non-protocol


communication

FX3G-485-BD-RJ

B A
European
terminal block
FX3S-CNV-ADP FX3U-485ADP(-MB)

B
Computer link
RS-232C
9-pin D-Sub,male Non-protocol
communication
FX3G-232-BD MODBUS
communication*1
B A Programming
communication
9-pin D-Sub,male
Remote
maintenance
FX3S-CNV-ADP FX3U-232ADP(-MB)

B A
Ethernet
Ethernet
Modular jack Programming
communication
FX3S-CNV-ADP FX3U-ENET-ADP

*1. Only the FX3U-485ADP-MB and FX3U-232ADP-MB support MODBUS communication.

A-52
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.8 For FX2N Series

Common Items
FX2N Series

A B D C For special function units/blocks C , refer to the next page.


B

N:N Network
A , B , C and D indicate the mounting position.
(For the mounting procedure, refer to the respective communication equipment manual.)
B
RS-485 European
terminal block

N:N Network
C
FX2N-485-BD

Parallel Link
Parallel link
B A
Computer link
European
terminal block Non-protocol
communication
A Inverter
FX2N-CNV-BD FX2NC-485ADP
M3 terminal
communication D

Computer Link
block
D
FX0N-485ADP
B Essential when inverter
communication is used.
RS-422 FX2N-ROM-E1
8-pin MINI-DIN, Programming E
female communication

Communication
Inverter
FX2N-422-BD
B

European
F
One line can be selected.

terminal block

(RS/RS2 Instruction)
Communication
Non-Protocol
FX2N-485-BD
B A Non-protocol
communication
European
terminal block
G
A

(FX2N-232IF)
Communication
Non-Protocol
FX2N-CNV-BD FX2NC-485ADP
M3 terminal
block
B

RS-232C
FX0N-485ADP
H
9-pin D-Sub, male
Communication
Programming

FX2N-232-BD
B A Computer link

9-pin D-Sub, male


Non-protocol
communication I
Programming
Maintenance
Remote

communication
A Remote
FX2N-CNV-BD FX2NC-232ADP maintenance
25-pin
D-Sub, Short mail
female sending
D Apx.A
FX0N-232ADP
models
Discontinued

Essential when the short mail


sending is used
FX2N-ROM-E1

A-53
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX2N Series

B D A , B , C and D indicate the mounting position.


A C
(For the mounting procedure, refer to the respective communication equipment manual.)

For special adapters with communication type A , communication


expansion board B and function extension memory
cassettes D , refer to the previous page.

For master station


FX2N-16CCL-M CC-Link
M3.5 terminal block
E
R
R
O
R

FX2N-16CCL-M*1
CC-Link
C

For remote device station


M3 terminal block

FX2N-32CCL
C
Up to 8 units can be selected.

POWER
SD
RD

9-pin D-Sub, male Non-protocol


communication

FX2N-232IF
C

Dedicated connector CC-Link/LT

FX2N-64CL-M
C U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX2N -32ASI-M
M3 terminal block AS-i system
MOD SE
E T PRJ
MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*2
C

M3 terminal block MELSEC-I/O LINK

FX2N-16LNK-M

*1. The FX2N-16CCL-M cannot be used at the same time with the FX2N-32ASI-M.
*2. The FX2N-32ASI-M cannot be used at the same time with the FX2N-16CCL-M.

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Therefore, the total current consumption larger than the PLC current capacity reduces the number of
connectable units.
For details, refer to the respective FX PLC manual.

A-54
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.9 For FX2NC Series

Common Items
FX2NC Series

For special function units/blocks C , refer to the next page.


A
D
C
B
A , C and D indicate the mounting position.

N:N Network
(For the mounting procedure, refer to the respective communication equipment manual.)
A

RS-485
European terminal block
C

Parallel Link
FX2NC-485ADP
N:N Network
A
Parallel link
Computer link
M3 terminal block
Non-protocol
communication D
Inverter

Computer Link
FX0N-485ADP communication
D

Essential when inverter communication is used

Communication
Inverter
FX2NC-ROM-CE1
A

RS-422
One line can be selected.

European terminal block


F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX2NC-485ADP Non-protocol
communication
A

M3 terminal block

(FX2N-232IF)
Communication
Non-Protocol
FX0N-485ADP
A

RS-232C
9-pin D-Sub, male

H
FX2NC-232ADP
Communication
Programming

A Computer link
Non-protocol
communication
25-pin D-Sub, male Programming
communication
Short mail
I
FX0N-232ADP sending
Maintenance
Remote

Essential when the short mail sending is used

Apx.A
FX2NC-ROM-CE1
models
Discontinued

A-55
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX2NC Series

A C A , C and D indicate the mounting position.


D (For the mounting procedure, refer to the respective communication equipment manual.)

For special adapters with communication type A and function


extension memory boards D , refer to the previous page.

C C
For master
station
M3.5 terminal block
FX2N-16CCL-M CC-Link
E
R
R
O
R

FX2NC-CNV-IF FX2N-16CCL-M*1
CC-Link
C
For remote
device
station
M3 terminal block

FX2N-32CCL
C
Up to 4 units can be selected.

POWER
SD
RD

9-pin D-Sub, male Non-protocol


communication

FX2N-232IF
C

Dedicated connector CC-Link/LT

FX2N-64CL-M
C U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX 2N-32ASI-M
M3 terminal block AS-i system
MOD SE PRJ
E T MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*2*3
C

M3 terminal block MELSEC-I/O LINK

FX2N-16LNK-M

*1. The FX2N-16CCL-M cannot be used at the same time with the FX2N-32ASI-M.
*2. The FX2N-32ASI-M cannot be used at the same time with the FX2N-16CCL-M.
*3. The FX2NC-MT-D/UL and FX2NC-M-DSS(-T-DS) are not supported.

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Therefore, the total current consumption larger than the plc current capacity reduces the number of
connectable units.
For details, refer to the respective FX PLC manual.

A-56
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.10 For FX1N Series

Common Items
FX1N Series

A B C For special function units/blocks C , refer to the next page.


B
A , B and C indicate the mounting position.

N:N Network
(For the mounting procedure, refer to the respective communication equipment manual.)
B

RS-485 European
terminal block
C
FX1N-485-BD N:N Network

Parallel Link
Parallel link
B A Computer link
Non-protocol
European communication
terminal block

A
D
FX1N-CNV-BD FX2NC-485ADP

Computer Link
M3 terminal
block
B
FX0N-485ADP
RS-422 8-pin MINI-DIN, Programming E
female communication

Communication
Inverter
FX1N-422-BD
B
One line can be selected.

European F
terminal block

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1N-485-BD
B A
Non-protocol
European
communication
G
terminal block

(FX2N-232IF)
Communication
Non-Protocol
A
FX1N-CNV-BD FX2NC-485ADP
M3 terminal
block

B
H
Communication
Programming

FX0N-485ADP
RS-232C
9-pin D-Sub, male

FX1N-232-BD
B A Computer link I
Non-protocol
Maintenance
Remote

communication
9-pin D-Sub, male Programming
communication
A Remote
FX1N-CNV-BD FX2NC-232ADP maintenance
25-pin Apx.A
D-Sub,
models
Discontinued

female

FX0N-232ADP

A-57
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX1N Series

A B C A , B and C indicate the mounting position.


(For the mounting procedure, refer to the respective communication equipment manual.)

For special adapters with communication type A and communication


expansion boards B , refer to the previous page.

For master station


FX2N-16CCL-M CC-Link
M3.5 terminal block
E
R
R
O
R

FX2N-16CCL-M*1
CC-Link
C

For remote device station


M3 terminal block
Up to 8 units can be selected.

FX2N-32CCL

Dedicated connector CC-Link/LT

FX2N-64CL-M
C U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX2N -32ASI-M
M3 terminal block AS-i system
MOD SE PRJ
E T MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*2

M3 terminal block MELSEC-I/O LINK

FX2N-16LNK-M

*1. The FX2N-16CCL-M cannot be used at the same time with the FX2N-32ASI-M.
*2. The FX2N-32ASI-M cannot be used at the same time with the FX2N-16CCL-M.

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Accordingly, the number of connectable units depends on the system configuration.
For details, refer to the respective FX PLC manual.

A-58
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.11 For FX1NC Series

Common Items
FX1NC Series

A C For special function units/blocks C , refer to the next page.


B
A and C indicate the mounting position.

N:N Network
(For the mounting procedure, refer to the respective communication equipment manual.)
A

RS-485
European terminal block
N:N Network C

Parallel Link
Parallel link
FX2NC-485ADP
Computer link
A Non-protocol
communication
M3 terminal block
D

Computer Link
FX0N-485ADP
A
One line can be selected.

RS-422
European terminal block
E

Communication
Inverter
FX2NC-485ADP Non-protocol
communication
A

M3 terminal block
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX0N-485ADP
A

RS-232C
9-pin D-Sub, male
Computer link
Non-protocol G
communication

(FX2N-232IF)
Communication
Non-Protocol
FX2NC-232ADP
Programming
A communication
Remote
maintenance
25-pin D-Sub, female

H
FX0N-232ADP
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-59
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

FX1NC Series

A C A and C indicate the mounting position.


(For the mounting procedure, refer to the respective communication equipment manual.)

For special adapters with communication type A , refer to the


previous page.

C C
For master
station
FX2N-16CCL-M CC-Link
M3.5 terminal block
E
R
R
O
R

FX2NC-CNV-IF FX2N-16CCL-M*1
CC-Link
C
For remote
device station
M3 terminal block
Up to 2 units can be selected.

FX2N-32CCL
C

Dedicated connector CC-Link/LT

FX2N-64CL-M
C U
ASI
ASI
ACTIVE

POWE
ADDRESS/ R
ERROR

FX2N-32ASI-M
M3 terminal block AS-i system
MOD SE
PRJ
E T MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M*2
C

M3 terminal block MELSEC-I/O LINK

FX2N-16LNK-M

*1. The FX2N-16CCL-M cannot be used at the same time with the FX2N-32ASI-M.
*2. The FX2N-32ASI-M cannot be used at the same time with the FX2N-16CCL-M.

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC.
Accordingly, the number of connectable units depends on the system configuration.
For details, refer to the respective FX PLC manual.

A-60
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

A
2.3.12 For FX1S Series

Common Items
FX1S Series

A B C C special units/blocks are not connectable.


B
A , B and C indicate the mounting position.

N:N Network
(For the mounting procedure, refer to the respective communication equipment manual.)
B

RS-485 European
terminal block
C
N:N Network
FX1N-485-BD

Parallel Link
Parallel link
B A Computer link
Non-protocol
European communication
terminal block

A
D
FX1N-CNV-BD FX2NC-485ADP

Computer Link
M3 terminal
block
B
FX0N-485ADP
RS-422 8-pin MINI-DIN, Programming E
female communication

Communication
Inverter
FX1N-422-BD
B
One line can be selected.

European
terminal block
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1N-485-BD
B A
Non-protocol
European
terminal block
communication
G

(FX2N-232IF)
Communication
Non-Protocol
A
FX1N-CNV-BD FX2NC-485ADP
M3 terminal
block

B
H
FX0N-485ADP
Communication
Programming

RS-232C
9-pin D-Sub, male

FX1N-232-BD
B A
Computer link I
Non-protocol
Maintenance
Remote

communication
9-pin D-Sub, male Programming
communication
A Remote
maintenance
FX1N-CNV-BD FX2NC-232ADP
25-pin Apx.A
D-Sub,
models
Discontinued

female

FX0N-232ADP

A-61
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

2.3.13 For FX0N Series


FX0N Series

A C For special function units/blocks C , refer to the next page.

A and C indicate the mounting position.


(For the mounting procedure, refer to the respective communication equipment manual.)
A

RS-485
European terminal block
N:N Network
Parallel link
FX2NC-485ADP
Computer link
A Non-protocol
communication
M3 terminal block

FX0N-485ADP
A
One line can be selected.

RS-422
European terminal block

FX2NC-485ADP Non-protocol
communication
A

M3 terminal block

FX0N-485ADP
A

RS-232C
9-pin D-Sub, male

Computer link
FX2NC-232ADP
Non-protocol
A communication

25-pin D-Sub, female

FX0N-232ADP

A-62
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

Common Items
FX0N Series

A and C indicate the mounting position.


A C (For the mounting procedure, refer to the respective communication equipment manual.)

B
For special adapters with communication type A , refer to the

N:N Network
previous page.

For remote device station


M3 terminal block CC-Link C

Parallel Link
Up to 4 units can be selected.

FX2N-32CCL
C U
ASI
ASI
ACTIVE

POWE

D
ADDRESS/ R
ERROR

M3 terminal block
FX 2N -32ASI-M AS-i system
MOD SE PRJ

Computer Link
E T MODE
PRG
ENABLE
FROM/
TO
CONFIG
ERR

FX2N-32ASI-M
C

M3 terminal block
MELSEC-I/O LINK E

Communication
Inverter
FX2N-16LNK-M

Limitation in the number of connectable units


Connected special function units/blocks operate using the 24V DC or 5V DC power supply of the PLC. F
Therefore, the total current consumption larger than the plc current capacity reduces the number of

(RS/RS2 Instruction)
Communication
Non-Protocol
connectable units.
For details, refer to the respective FX PLC manual.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-63
FX Series PLC User's Manual - Data Communication Edition 2 Communication Types and Communication Equipment
Common Items 2.3 Combination of Communication Equipment (Block Diagram)

2.3.14 For FX2(FX) and FX2C Series (reference)

FX2(FX),FX2C Series

A indicate the mounting position.


A (For the mounting procedure, refer to the respective communication equipment manual.)

RS-485
M3.5 terminal block Computer link

FX-485ADP
A

RS-232C Computer link


One line can be selected.

25-pin D-Sub, female Non-protocol


communication

FX-232ADP
A

Dedicated
M3.5 terminal block Parallel link

FX2-40AW
A

Dedicated Connector for Parallel link


optical fiber

FX2-40AP

A-64
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.1 Setting Method

Common Items
3. Outline of Communication Setting in the FX Series
This chapter describes which communication parameters can be changed for the following communication B
types, and provides methods on how to change them.

N:N Network
Computer link
Inverter communication
Non-protocol communication (RS/RS2 instruction)
Internet mail sending C

Parallel Link
3.1 Setting Method
The following two communication setting methods are available for FX PLCs. Either method can be used, but
the method using parameters is recommended.

1. Setting methods
D

Computer Link
1) Specify the settings using parameters in the programming tool
Register the settings in parameters, transfer it to the PLC and turn the PLC's power OFF and then ON.
(This method is not available in FX2(FX), FX2C, and FX0N PLCs.)
(This method is not available for ch0 in FX3G, FX3GC PLCs.)
2) Directly specify the settings in a sequence program E
Prepare a sequence program which sets the communication format, station number and time-out time

Communication
Inverter
setting, and then transfer the program to the PLC.
Caution
Regardless of the method chosen above, a PLC operates the same way. If both methods are selected,
priority is given to the method using parameters.
F
2. Communication setting method availability in each FX PLC

(RS/RS2 Instruction)
Communication
Non-Protocol
FX Series FX2(FX),FX2C FX0N FX1S FX1N,FX1NC FX2N,FX2NC FX3S FX3G,FX3GC FX3U,FX3UC
Parameter method *1
Program method

*1. Only ch1 and ch2 are available. G

(FX2N-232IF)
Communication
Non-Protocol
3. Setting flow
PLC memory Transferred ch1 Computer link
when power RS instruction
Setting window Inverter communication
is turned ON
Parameter area Programming communication
Parameter
method
D8120 Communication format
D8121 Station number settings
H
Program area
Communication
Programming

D8129 Time-out time setting


[MOV H D8120] Written by In FX3S, FX3G, FX3GC,
[MOV K D8121]
program FX3U and FX3UC

[MOV K D8129]
ch0 RS2 instruction Ch0 is available only
D8370 Communication format in the FX3G, FX3GC PLC.
D8379 Time-out time setting The setting method
I
In FX3S, FX3G, FX3GC,
FX3U and FX3UC Written by ch1 RS2 instruction using parameter cannot
Sequence Program [MOV H D8370] program be used for ch0.
D8400 Communication format
Maintenance
Remote

program for method [MOV K D8379] Only ch1 is available


D8409 Time-out time setting
set values Written by in the FX3S PLC.
[MOV H D8400] program
ch2 Computer link
[MOV K D8409] RS instruction
Written by Inverter communication
[MOV H D8420] Programming communication
program
[MOV K D8421]
[MOV K D8429]
D8420 Communication format
D8421 Station number settings
Apx.A
D8429 Time-out time setting
models
Discontinued

When both methods are selected at the same time, priority is given to
the contents set using the parameter method.

A-65
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.1 Setting Method

4. Time at which the settings become valid


1) Specifying the settings using parameters in the programming tool:
When the PLC power is turned ON, the contents of the parameters are automatically transferred to the
PLC.
As soon as the parameters are transferred to the PLC, the settings become valid.
2) Directly specifying the settings in a sequence program:
To enable the settings, write data after turning the PLC mode to RUN from STOP, and then reboot the
PLC's power.

A-66
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.2 Communication Setting Using Parameter Method (GX Works2)

A
3.2 Communication Setting Using Parameter Method (GX Works2)

Common Items
Communication settings may be changed by the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 3.3. B
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

N:N Network
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

3.2.1 Operating procedure


With GX Works2 open, follow the steps in this section for activating the serial communication setting method.
C
1 Opening the parameter setting window

Parallel Link
In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar.
D

Computer Link
E

Communication
Inverter
2 Setting the serial communication (parameters)
Click the [PLC System(2)] tab on the dialog box. F
When using programming communication, parallel link, N:N Network or remote maintenance, do

(RS/RS2 Instruction)
Communication
Non-Protocol
not check the "Operate Communication Setting" box.
When using computer link, inverter communication or non-protocol communication (RS/RS2
instruction) function, check the "Operate Communication Setting" box, and then set each item.
Click [End].
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

3 Writing parameters to the PLC


Apx.A
Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
models
Discontinued

[Execute].

A-67
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.2 Communication Setting Using Parameter Method (GX Works2)

3.2.2 Correspondence between parameter setting and each communication type


The table below shows the communication types and set items which can be set using parameters:

Non-protocol communication (FX2N-232IF)


Non-protocol communication
(RS/RS2 instruction)

Programming communication
MODBUS communication
Ethernet communication

Inverter communication
Set item Contents Remarks

Internet mail sending

Remote maintenance
CC-Link/LT network
Short mail sending
CC-Link network

AnyWireASLINK
Computer link
N:N Network

AS-i system
Parallel link

RS2
RS
Non-protocol

communication
Protocol
Dedicated

protocol
7-bit
Data length
8-bit
None
Parity Odd
Even
1-bit
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.

This communication is not executed in this setting.


This communication is not executed in this setting.

This communication is not executed in this setting.


This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
Stop bit
2-bit
*1
38400
19200
9600
Transmission speed 4800
(bps) 2400
1200
600
300
Header Invalid/valid
Terminator Invalid/valid
Control cable Invalid/valid
Regular/

Hardware type RS-232C
RS-485
Not
Control mode Invalid
selectable
Sum check Invalid/valid
Transmission control Format 1
procedure Format 4
Station number
00 to 0F
settings
Time-out time setting 1 to 255
Reference page B C D E F G H I

*1. Only available for FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

A-68
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.3 Communication Setting in Parameter Method (FXGP/WIN)

A
3.3 Communication Setting in Parameter Method (FXGP/WIN)

Common Items
Communication settings may be changed by the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with FXGP/WIN.
Ch0 and Ch 2 cannot be set using FXGP/WIN. B
For details on GX Works2 operating procedure, refer to section 3.2.

N:N Network
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

3.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already
C

Parallel Link
started up.

1 Adjusting serial setting (parameter)


Select [Option] [Serial setting (parameter)] from the toolbar.
The following dialog appears according to absence/presence of parameter settings.
D

Computer Link
1. When there are no parameter settings
There is no communication setting.
When using the programming communication, parallel link, N:N Network or remote maintenance, click the
[No] button.
When using computer link, inverter communication, or non-protocol communication (RS instruction) function, E
click the [Yes] button.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-69
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.3 Communication Setting in Parameter Method (FXGP/WIN)

2. When there are already parameter settings


There is communication setting. Confirm the setting contents.
When using programming communication, parallel link, N:N Network or remote maintenance, click the [Clear]
button.

A-70
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.3 Communication Setting in Parameter Method (FXGP/WIN)

A
3.3.2 Correspondence between parameter setting and each communication type

Common Items
The table below shows the communication types and items which can be set using parameters:

Non-protocol communication (RS instruction)


B

Non-protocol communication (FX2N-232IF)

N:N Network
Programming communication
C

MODBUS communication
Ethernet communication
Set item Contents Remarks

Inverter communication

Internet mail sending

Remote maintenance

Parallel Link
CC-Link/LT network
Short mail sending
CC-Link network

AnyWireASLINK
Computer link
N:N Network

AS-i system
Parallel link
D

Computer Link
Non-protocol

Protocol communication
Dedicated protocol

Data length
7-bit
8-bit




E

Communication
Inverter
None
Parity Odd
Even
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.

This communication is not executed in this setting.


This communication is not executed in this setting.

This communication is not executed in this setting.


This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
This communication is not executed in this setting.
1-bit
Stop bit
2-bit F

(RS/RS2 Instruction)
Communication
Non-Protocol
19200
9600
4800
Baud rate (bps) 2400
1200 G
600

(FX2N-232IF)
Communication
Non-Protocol
300
Header Invalid/valid
Terminator Invalid/valid
Control cable Invalid/valid
Regular/RS-232C




H
Communication
Programming

Hardware type
RS-485
Not
Control mode Invalid
selectable
Sum check Invalid/valid
Transmission control Format 1 I
procedure Format 4
Maintenance
Remote

Station number settings 00 to 0F


Time-out time setting 1 to 255
Reference page B C D E F G H I

Apx.A
models
Discontinued

A-71
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.4 Extension of Ports (For FX3G, FX3GC, FX3U, FX3UC)

3.4 Extension of Ports (For FX3G, FX3GC, FX3U, FX3UC)


In FX3G, FX3GC, FX3U and FX3UC PLCs, up to two communication port channels can be connected using a
communication expansion board and communication special adapter.
Point

Only one channel can be connected to the FX3G PLC (14-point and 24-point type).
The standard built-in port (RS-422) can be used as ch0 when the non-protocol communication function
(RS2 instruction) is used in the FX3G, FX3GC PLC.
Refer to the "Non-protocol Communication (RS/RS2 instruction)" section.
When a CF card special adapter is connected to the PLC, it is handled in the same way as a
communication special adapter, and occupies one communication port channel.
For details, refer to FX3U-CF-ADP Users Manual.
When a FX3U-8AV-BD, FX3G-8AV-BD, FX3G-4EX-BD or FX3G-2EYT-BD is connected to the PLC, it is
handled in the same way as a communication expansion board, and occupies one communication port
channel.
When the FX3U-ENET-ADP is used, one communication port is occupied. Only one FX3U-ENET-ADP unit
can be connected at the last stage (left end) of the main unit and special adapters.
For details, refer to FX3U-ENET-ADP Users Manual.

3.4.1 Extension of Port (For FX3G, FX3GC PLC)

1. For FX3G PLC (40-point, 60-point type)


The communication expansion board connected to the option connector 1 or the first communication special
adapter works as ch1, and the communication expansion board connected to the option connector 2 or the
second communication special adapter works as ch2.
When using a communication expansion board When using two communication special
and a communication special adapter together adapters
Communication Communication Communication Communication
special adapter expansion board special adapter special adapter
(ch1) FX3G-CNV-ADP (ch2) (ch2) *1 (ch1) FX3G-CNV-ADP

Analog special Standard built-in port (RS-422) Analog special Standard built-in port (RS-422)
adapter (ch0) adapter (ch0)
*1. Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or FX3G-2EYT-BD is used.

When using one communication expansion board


Communication Communication
expansion board expansion board
(ch1) (ch2)

Standard built-in port (RS-422) Standard built-in port (RS-422)


(ch0) (ch0)

A-72
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.4 Extension of Ports (For FX3G, FX3GC, FX3U, FX3UC)

A
When using two communication expansion board

Common Items
Communication Communication
expansion board expansion board
(ch1) (ch2)

N:N Network
Standard built-in port (RS-422)
(ch0)

2. For FX3G PLC (14-point, 24-point type)


One communication port channel can be connected to the FX3G PLC main unit (14-point and 24-point type).
C

Parallel Link
It is not allowed to connect two communication special adapters.
Communication Communication
special adapter expansion board
(ch1) FX3G-CNV-ADP (ch1)

Computer Link
E
Analog special Standard built-in port (RS-422) Standard built-in port (RS-422)

Communication
Inverter
adapter (ch0) (ch0)

3. For FX3GC PLC


Communication Communication
special adapter special adapter F
(ch2) (ch1) Standard built-in port (RS-422)

(RS/RS2 Instruction)
Communication
Non-Protocol
(ch0)

(FX2N-232IF)
Communication
Non-Protocol
Analog special
adapter

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-73
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.4 Extension of Ports (For FX3G, FX3GC, FX3U, FX3UC)

3.4.2 Extension of Port (For FX3U, FX3UC PLC)


When a communication expansion board and communication special adapter are used, the board is handled
as ch 1 and the adapter is handled as ch 2.
When connecting two communication special adapters using the FX3U-CNV-BD*1, the one closer to the main
unit is handled as ch 1 and the farther one is handled as ch 2.
When a FX3U-8AV-BD or CF card special adapter is used, however, it occupies one communication port
channel.
*1. When using the FX3UC(D, DS, DSS) PLC, the FX3U-CNV-BD is not required.

1. For FX3U PLC


When using a communication expansion board When using two communication special
and a communication special adapter together adapters
Communication Communication Communication Communication
special adapter expansion board special adapter special adapter
(ch2) (ch1) (ch2) (ch1)
FX3U-CNV-BD

FX 3U -4AD-ADP FX 3U -4AD-ADP FX 3 U -4AD-ADP FX 3U -4AD-ADP


FX 3U -4AD-ADP FX 3U -4AD-ADP FX 3U -4AD-ADP FX 3U -4AD-ADP
P O WE R P O WE R P O WE R P O WE R
P O WE R P O WE R P O WE R P O WE R

RDA
RD
RDB

SDA

SD SDB

SG

Analog special High speed input/output Analog special High speed input/output
adapter special adapter*2 adapter special adapter*2
*2. When using high speed special input/output adapters, make sure to connect them to the PLC main
unit first before connecting communication special adapters, CF card special adapter and analog
special adapters.
2. For FX3UC(D,DS,DSS) PLC
Communication Analog Communication
special adapter special special adapter
(ch2) adapter (ch1)

FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP


POWER POWER POWER POWER

3. For FX3UC-32MT-LT(-2) PLC


When using a communication expansion board When using two communication special
and a communication special adapter together adapters
Communication Communication
special adapter Communication Analog special adapter
(ch2) Analog Communication special adapter special (ch1)
special expansion board (ch2) adapter
adapter (ch1) FX3U-CNV-BD

FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP FX3U-4AD-ADP


POWER POWER POWER POWER POWER POWER POWER POWER

RDA
RD
RDB

SDA

SD SDB

SG

A-74
FX Series PLC User's Manual - Data Communication Edition 3 Outline of Communication Setting in the FX Series
Common Items 3.4 Extension of Ports (For FX3G, FX3GC, FX3U, FX3UC)

A
3.4.3 Limitation when ch1 and ch2 are used at the same time

Common Items
When using ch1 and ch2 at the same time, available communication type combinations are limited. For
details, refer to the table below.
When a CF card special adapter, FX3U-8AV-BD, FX3G-8AV-BD, FX3G-4EX-BD, FX3G-2EYT-BD or the FX3U-
ENET-ADP is used, one communication port (1ch) is occupied. However, the occupied communication port
does not apply any restrictions to the combination of communication functions when ch1 and ch2 are used at
B

N:N Network
the same time.

Communication
channel: ch2 Communication channel: ch1
C

Parallel Link
RD A

RD

RD B

SD A

SD SD B

SG

Communication
special adapter
Expansion
board
Communication
special adapter
Expansion
board
FX3G/FX3GC/FX3U/FX3UC PLC D

Computer Link
: Applicable, : Not applicable

Communication setting for ch1

MODBUS Computer Inverter


Non-protocol Non-protocol
Programming Remote
E
communication N:N Network Parallel link link communication communication communication communication maintenance

Communication
Inverter
(RS instruction) (RS2 instruction)

MODBUS
communication

N:N Network
(Example 1) (Example 2)

Parallel link
F
Communication setting for ch2

Computer link

(RS/RS2 Instruction)
Communication
Non-Protocol
Inverter
communication
Non-protocol
communication *1
(RS instruction)
Non-protocol
communication
(RS2 instruction)

G
Programming

(FX2N-232IF)
Communication
Non-Protocol

communication

Remote *2
maintenance

*1. Ch2 cannot be set for non-protocol communication (RS instruction). H


*2. When using remote maintenance on ch2, use GX Works2 or GX Developer.
Communication
Programming

For applicable versions of GX Works2 and GX Developer,


refer to I. Remote Maintenance Subsection 1.4.1 or 1.4.2.

Example 1:
When "parallel link" is set for ch1, the "N:N Network" cannot be set for ch2.
Example 2:
I
Maintenance
Remote

When "computer link" is set for ch1, the "N:N Network" can be set for ch2.

Apx.A
models
Discontinued

A-75
FX Series PLC User's Manual - Data Communication Edition 4 Version Number
Common Items 4.1 Manufacturer's serial number check method

4. Version Number

4.1 Manufacturer's serial number check method


The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT"
indicated on the front of the product.

4.1.1 Checking the nameplate


The year and month of production of the PLC main unit can be checked from the manufacturer's serial
number "S/N" indicated on the label adhered to the right side of the product.
Example nameplate (manufacture's serial number : 1010001)

Right side

* Actual product nameplate differs


from the example shown above.

<Product during December, 2009 or earlier> <Product from January, 2010>

9 Z 0 0 0 1 1 0 1 0 0 0 1

Control number Control number


Month (Example: Dec.): Month (Example: Jan.):
1 to 9 = January to September, 1 to 9 = January to September,
X = October, Y = November, Z = December X = October, Y = November, Z = December
Year (Example: 2009): Last digit of year Year (Example: 2010): Last two digit of year

A-76
FX Series PLC User's Manual - Data Communication Edition 4 Version Number
Common Items 4.2 Version check

A
4.1.2 Checking the front of the product

Common Items
The year and month of production of the PLC main unit can be checked from the manufacturer's serial
number "LOT" on the front (at the bottom) of the product.
The "LOT" indication is provided only with the following PLC main units.
Main unit "LOT" indication adoption time B
FX3S Series PLC March 2013 and later (From first product)

N:N Network
FX3G Series PLC October 2008 and later
FX3GC Series PLC January 2012 and later (From first product)
FX3U Series PLC January 2009 and later
FX3UC Series PLC January 2009 and later C

Parallel Link
Example: FX3U-48MR/ES

Computer Link
<Product during December, 2009 or earlier> <Product from January, 2010>

9 Z 1 0 1 E

Communication
Inverter
Month (Example: Dec.): Month (Example: Jan.):
1 to 9 = January to September, 1 to 9 = January to September,
X = October, Y = November, Z = December X = October, Y = November, Z = December
Year (Example: 2009): Last digit of year Year (Example: 2010): Last two digit of year
F

(RS/RS2 Instruction)
Communication
Non-Protocol
4.2 Version check
The PLC version can be checked by reading the last three digits of device D8001.

D8001 2 4 2 5 1 G
PLC type and

(FX2N-232IF)
Communication
Non-Protocol
version Version information (Example: Ver. 2.51)
PLC type (Example: 24 = FX2N, FX2NC, FX3U or FX3UC Series)

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-77
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.1 Rank and Use Method of This Manual

5. Introduction of Manuals (Type, Reading Method and


Acquisition Method)
This chapter specifies the manuals related to PLC main units for each communication type.

5.1 Rank and Use Method of This Manual


When communication equipment is connected, an FX PLC can offer various communication options.

PLC

Wiring and installation of PLC


HARDWARE MANUAL, HANDY MANUAL Supplied with
(which is supplied with each product)
User's Manual Separate manual
(for FX3S, FX3G, FX3GC, FX3U and FX3UC)
Sequence program
PROGRAMMING MANUAL Separate manual

Communication equipment

Installation and name of each part


INSTALLATION MANUAL Supplied with
(which is supplied with each product)

Manuals supplied with each communication equipment are shown at the section 5.2.
This information is provided for convenience to offer the terminal layout, external
dimensions, etc., and may not be up-to-date.

Communication types

N:N Network Parallel link Computer link Inverter Non-protocol Other


communication communication communication
How to use each communication type
This User's Manual -
manual Separate manual
Communication Control Edition
This manual specifies the setting method, cable connection, program examples and
troubleshooting for each communication type.

A-78
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.2 Introduction of Related Manuals

A
5.2 Introduction of Related Manuals

Common Items
This section shows major manuals required to use the communication types in this manual.
Manuals for PLC main units and manuals for communication equipment are classified separately.
"Separate manual" shown in the "Included/separate manual" column indicates that the manual is supplied
separately. "Included" indicates that the manual is included with each product. B

N:N Network
5.2.1 Manual for communication types in FX PLCs

Included/separate
Manual name Manual number Contents
document
Manuals for data communication C
FX Series Users Manual - Separate manual Describes the contents of communication types

Parallel Link
JY997D16901
Data Communication Edition (this manual) supported by FX Series PLCs.
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series User's Manual Explains the MODBUS serial communication
JY997D26201 Separate manual
- MODBUS Serial network in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs.
Communication Edition D

Computer Link
5.2.2 Manuals related to FX PLCs
For instructions used in sequence programs, refer to the PROGRAMMING MANUAL.
For hardware specifications and wiring of the PLC, refer to the HANDY MANUAL or USERS MANUAL.

Manual name Manual number


Included/separate
Contents
E
document

Communication
Inverter
Manuals for PLC main unit
FX3U Series
For detailed explanation, refer to the FX3U Series User's Manual - Hardware Edition.
I/O specifications, wiring and installation of the
FX3U Series
Hardware Manual
JY997D50301 Included PLC main unit FX3U extracted from the FX3U F
Series User's Manual - Hardware Edition.

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U Series Details about the hardware including I/O
User's Manual - Hardware JY997D16501 Separate manual specifications, wiring, installation and
Edition maintenance of the FX3U PLC main unit.
FX3UC Series
For detailed explanation, refer to the FX3UC Series User's Manual - Hardware Edition. G
I/O specifications, wiring and installation of the

(FX2N-232IF)
Communication
Non-Protocol
FX3UC(D, DS, DSS) Series PLC main unit FX3UC (D, DS, DSS) extracted
JY997D50501 Included
Hardware Manual from the FX3UC Series User's Manual - Hardware
Edition.
I/O specifications, wiring and installation of the
FX3UC-32MT-LT-2 Series
Hardware Manual
JY997D31601 Included
PLC main unit FX3UC-32MT-LT-2 extracted from
the FX3UC Series User's Manual - Hardware H
Edition.
Communication
Programming

FX3UC Series Details about the hardware including I/O


User's Manual - Hardware JY997D28701 Separate manual specifications, wiring, installation and
Edition maintenance of the FX3UC PLC main unit.
FX3G Series
For detailed explanation, refer to the FX3G Series Users Manual - Hardware Edition. I
I/O specifications, wiring and installation of the
Maintenance
Remote

FX3G Series
JY997D46001 Included PLC main unit FX3G extracted from the FX3G
Hardware Manual
Series User's Manual - Hardware Edition.
FX3G Series Details about the hardware including I/O
User's Manual - Hardware JY997D31301 Separate manual specifications, wiring, installation and
Edition maintenance of the FX3G PLC main unit. Apx.A
models
Discontinued

A-79
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.2 Introduction of Related Manuals

Included/separate
Manual name Manual number Contents
document
FX3GC Series
For detailed explanation, refer to the FX3GC Series User's Manual - Hardware Edition.
I/O specifications, wiring and installation of the
FX3GC Series
JY997D45201 Included PLC main unit FX3GC extracted from the FX3GC
Hardware Manual
Series User's Manual - Hardware Edition.
FX3GC Series Details about the hardware including I/O
User's Manual - Hardware JY997D45401 Separate manual specifications, wiring, installation and
Edition maintenance of the FX3GC PLC main unit.
FX3S Series
For detailed explanation, refer to the FX3S Series Users Manual - Hardware Edition.
I/O specifications, wiring and installation of the
FX3S Series
JY997D48301 Included PLC main unit FX3S extracted from the FX3S
Hardware Manual
Series User's Manual - Hardware Edition.
I/O specifications, built-in analog specifications,
FX3S-30M/E-2AD wiring and installation of the PLC main unit
JY997D51701 Included
Hardware Manual FX3S-30M/E-2AD extracted from the FX3S
Series User's Manual - Hardware Edition.
FX3S Series Details about the hardware including I/O
User's Manual - Hardware JY997D48601 Separate manual specifications, wiring, installation and
Edition maintenance of the FX3S PLC main unit.
FX2N Series
Describes the contents of the FX2N PLC
FX2N Series
JY992D66301 Included hardware including the specifications, wiring and
HARDWARE MANUAL
installation procedure.
FX2NC Series
Describes the contents of the FX2NC(DSS, DS)
FX2NC (DSS, DS) Series
JY992D76401 Included PLC hardware including the specifications, wiring
HARDWARE MANUAL
and installation procedure.
Describes the contents of the FX2NC(D/UL) PLC
FX2NC (D/UL) Series
JY992D87201 Included hardware including the specifications, wiring and
HARDWARE MANUAL
installation procedure.
FX1N Series
Describes the contents of the FX1N PLC
FX1N Series
JY992D89301 Included hardware including the specifications, wiring and
HARDWARE MANUAL
installation procedure.
FX1NC Series*1
Describes the contents of the FX1NC PLC
FX1NC Series
JY992D92101 Included hardware including the specifications, wiring and
HANDY MANUAL
installation procedure.
FX1S Series
Describes the contents of the FX1S PLC
FX1S Series
JY992D83901 Included hardware including the specifications, wiring and
HARDWARE MANUAL
installation procedure.
FX0N Series
Describes the contents of the FX0N PLC
FX0N Series
JY992D47501 Included hardware including the specifications, wiring and
HARDWARE MANUAL
installation procedure.
FX2(FX) Series
Describes the contents of the FX PLC hardware
FX Series
JY992D47401 Included including the specifications, wiring and installation
HARDWARE MANUAL
procedure.
FX2C Series*2
Describes the contents of the FX2C PLC
FX2C Series
JY992D59001 Included hardware including the specifications, wiring and
HANDY MANUAL
installation procedure.

*1. FX1NC Series PLC Manual is available only in Japanese.


*2. FX2C Series PLC Manual is available only in Japanese.

A-80
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.2 Introduction of Related Manuals

A
Included/separate

Common Items
Manual name Manual number Contents
document
Manuals for programming
FX3S/FX3G/FX3GC/FX3U/FX3UC Explains basic instructions and applied
Programming Manual - Basic & JY997D16601 Separate manual instructions available in the FX3S/FX3G/FX3GC/
Applied Instruction Edition FX3U/FX3UC PLC. B
FX1S, FX1N, FX2N, FX1NC,

N:N Network
Explains instructions applicable in the FX1S,
FX2NC JY992D88101 Separate manual
FX1N, FX2N, FX1NC and FX2NC PLCs.
PROGRAMMING MANUAL
FX0, FX0S, FX0N, FX1, FX2, FX2C Explains instructions available in the FX0, FX0S,
JY992D48301 Separate manual
PROGRAMMING MANUAL FX0N, FX1, FX2, FX2C PLCs.
MELSEC-Q/L/F Structured
Programming methods, specifications, functions,
C
Programming Manual SH080782 Separate manual

Parallel Link
etc. required to create structured programs
(Fundamentals)
FXCPU Structured
Devices, parameters, etc. provided in structured
Programming Manual JY997D26001 Separate manual
projects of GX Works2
[Device & Common]
FXCPU Structured
Programming Manual JY997D34701 Separate manual
Sequence instructions provided in structured D
projects of GX Works2

Computer Link
[Basic & Applied Instruction]
FXCPU Structured
Application functions provided in structured
Programming Manual JY997D34801 Separate manual
projects of GX Works2
[Application Functions]

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-81
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.2 Introduction of Related Manuals

5.2.3 Communication equipment (option)


The table below specifies the manuals for communication equipment operating in accordance with RS-232C,
RS-422, RS-485 or USB and for the Ethernet adapter.

Included/separate
Manual name Manual number Contents
document
For communication in accordance with RS-232C
Describes the contents of the RS-232C
FX3U-232-BD communication expansion board, FX3U-232-BD
JY997D12901 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX3G-232-BD communication expansion board, FX3G-232-BD
JY997D32001 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX2N-232-BD communication expansion board, FX2N-232-BD
JY992D63201 Included
USER'S GUIDE hardware including the specifications and installation
procedure.
Describes the contents of the RS-232C
FX1N-232-BD communication expansion board, FX1N-232-BD
JY992D84401 Included
USER'S GUIDE hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX3U-232ADP communication special adapter, FX3U-232ADP
JY997D13701 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX3U-232ADP-MB communication special adapter, FX3U-232ADP-MB
JY997D26401 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX2NC-232ADP communication special adapter, FX2NC-232ADP
JY997D01101 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX0N-232ADP communication special adapter, FX0N-232ADP
JY992D51201 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX-232ADP communication special adapter, FX-232ADP
JY992D48801 Included
USER'S GUIDE hardware including the specifications and
installation procedure.
Describes the contents of the RS-232C
FX2N-232IF communication special extension block, FX2N-
JY992D73501 Included
HARDWARE MANUAL 232IF hardware including the specifications and
installation procedure.
For communication in accordance with RS-422
Describes the contents of the RS-422 communication
FX3U-422-BD
JY997D13101 Included expansion board, FX3U-422-BD hardware including the
INSTALLATION MANUAL
specifications and installation procedure.
Describes the contents of the RS-422 communication
FX3G-422-BD
JY997D32101 Included expansion board, FX3G-422-BD hardware including
INSTALLATION MANUAL
the specifications and installation procedure.
Describes the contents of the RS-422 communication
FX2N-422-BD
JY992D66101 Included expansion board, FX2N-422-BD hardware including the
USER'S GUIDE
specifications and installation procedure.

A-82
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.2 Introduction of Related Manuals

A
Included/separate

Common Items
Manual name Manual number Contents
document
Describes the contents of the RS-422 communication
FX1N-422-BD
JY992D84101 Included expansion board, FX1N-422-BD hardware including the
USER'S MANUAL
specifications and installation procedure.
For communication in accordance with RS-485(422) B

N:N Network
Describes the contents of the RS-485 communication
FX3U-485-BD
JY997D13001 Included special expansion board, FX3U-485-BD hardware
INSTALLATION MANUAL
including the specifications and installation procedure.
Describes the contents of the RS-485 communication
FX3G-485-BD
JY997D32201 Included special expansion board, FX3G-485-BD hardware
INSTALLATION MANUAL
including the specifications and installation procedure. C
Describes the contents of the RS-485 communication

Parallel Link
FX3G-485-BD-RJ
JY997D51501 Included special expansion board, FX3G-485-BD-RJ hardware
INSTALLATION MANUAL
including the specifications and installation procedure.
Describes the contents of the RS-485 communication
FX2N-485-BD
JY992D73401 Included expansion board, FX2N-485-BD including the
HARDWARE MANUAL
specifications and installation procedure. D
Describes the contents of the RS-485 communication

Computer Link
FX1N-485-BD
JY992D84201 Included expansion board, FX1N-485-BD hardware including the
USER'S GUIDE
specifications and installation procedure.
Describes the contents of the RS-485 communication
FX3U-485ADP
JY997D13801 Included special adapter, FX3U-485ADP hardware including the
INSTALLATION MANUAL
specifications and installation procedure.
E
Describes the contents of the RS-485 communication

Communication
Inverter
FX3U-485ADP-MB
JY997D26301 Included special adapter, FX3U-485ADP-MB hardware including
INSTALLATION MANUAL
the specifications and installation procedure.
Describes the contents of the RS-485 communication
FX2NC-485ADP
JY997D01201 Included special adapter, FX2NC-485ADP hardware including
INSTALLATION MANUAL
the specifications and installation procedure.
Describes the contents of the RS-485 communication
F
FX0N-485ADP

(RS/RS2 Instruction)
Communication
Non-Protocol
JY992D53101 Included special adapter, FX0N-485ADP hardware including the
INSTALLATION MANUAL
specifications and installation procedure.
For communication in accordance with USB
Describes the contents of the USB
FX3U-USB-BD
USER'S MANUAL
JY997D13501 Included
communication expansion board, FX3U-USB-BD
hardware including the specifications and
G

(FX2N-232IF)
Communication
Non-Protocol
installation procedure.
For communication in accordance with Ethernet
Describes the contents of the Ethernet
FX3U-ENET-ADP communication special adapter, FX3U-ENET-ADP
JY997D47401 Included
INSTALLATION MANUAL hardware including the specifications and
installation procedure. H
Communication
Programming

FX3U-ENET-ADP Describes FX3U-ENET-ADP Ethernet


JY997D45801 Separate manual
USER'S MANUAL communication special adapter details.

I
Maintenance
Remote

Apx.A
models
Discontinued

A-83
FX Series PLC User's Manual - Data Communication Edition 5 Introduction of Manuals (Type, Reading Method and Acquisition Method)
Common Items 5.2 Introduction of Related Manuals

5.2.4 Related options for communication


The table below specifies the manuals for products required to use communication equipment (options)
above in the system configuration.

Included/separate
Manual name Manual number Contents
document
Connector conversion board
Describes the contents of the FX3U-CNV-BD
FX3U-CNV-BD
JY997D13601 Included special adapter connection board hardware
INSTALLATION MANUAL
including the installation procedure.
Describes the contents of the FX2N-CNV-BD
FX2N-CNV-BD JY992D63601 Included special adapter connection board hardware
including the installation procedure.
Describes the contents of the FX1N-CNV-BD
FX1N-CNV-BD JY992D84701 Included special adapter connection board hardware
including the installation procedure.
Connector conversion adapter
Describes the contents of the FX3G-CNV-ADP
FX3G-CNV-ADP
JY997D32301 Included special adapter connection conversion adapter
INSTALLATION MANUAL
hardware including the installation procedure
Describes the contents of the FX3S-CNV-ADP
FX3S-CNV-ADP
JY997D48801 Included special adapter connection conversion adapter
INSTALLATION MANUAL
hardware including the installation procedure
RS-485/RS-232C converter for computer link communication
Describes the contents of the FX-485-PC-IF-SET
FX-485-PC-IF-SET
JY992D81801 Included interface unit hardware including the
HARDWARE MANUAL
specifications and installation procedure.
FX-30P
Describes the contents of the FX-30P Handy
FX-30P
JY997D34201 Included Programming Panel hardware including the
INSTALLATION MANUAL
specifications and installation procedure.
Describes the contents of the FX-30P Handy
FX-30P Programming Panel hardware including the
JY997D34401 Separate manual
OPERATION MANUAL specifications and installation procedure as well
as programming operations.

A-84
FX Series PLC User's Manual - Data Communication Edition 6 Abbreviations, Generic Names and Terms Used in This Manual
Common Items 5.2 Introduction of Related Manuals

Common Items
6. Abbreviations, Generic Names and Terms Used in This
Manual
B

N:N Network
The table below shows abbreviations, generic names and terms used in this manual.

1. Programmable controllers
Abbreviation/
Name
generic name
C
Programmable controllers

Parallel Link
Generic name of FX1, FX2(FX), FX2C, FX0, FX0S, FX0N, FX1S, FX1N, FX1NC, FX2N,
FX PLC or FX CPU
FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC Series PLCs
FX3U Series Generic name of FX3U Series PLCs
FX3U PLC or main unit Generic name of FX3U Series PLC main units
FX3UC Series Generic name of FX3UC Series PLCs D

Computer Link
FX3UC PLC or main unit Generic name of FX3UC Series PLC main units
FX3G Series Generic name of FX3G Series PLCs
FX3G PLC or main unit Generic name of FX3G Series PLC main units
FX3GC Series Generic name of FX3GC Series PLCs
FX3GC PLC or main unit Generic name of FX3GC Series PLC main units E
FX3S Series Generic name of FX3S Series PLCs

Communication
Inverter
FX3S PLC or main unit Generic name of FX3S Series PLC main units
FX2N Series Generic name of FX2N Series PLCs
FX2N PLC or main unit Generic name of FX2N Series PLC main units
FX2NC Series Generic name of FX2NC Series PLCs
Generic name of FX2NC-M(-T), FX2NC-MT-D/UL, and FX2NC-M-DSS(-T-DS)
F
FX2NC PLC or main unit

(RS/RS2 Instruction)
Communication
Non-Protocol
Series PLC main units
FX2NC-M(-T)
FX2NC-16MR-T, FX2NC-16MT, FX2NC-32MT, FX2NC-64MT, and FX2NC-96MT
PLC
FX2NC-MT-D/UL
FX2NC-16MT-D/UL, FX2NC-32MT-D/UL, FX2NC-64MT-D/UL, and FX2NC-96MT-D/UL
PLC
FX2NC-M-DSS FX2NC-16MR-T-DS, FX2NC-16MT-DSS, FX2NC-32MT-DSS, FX2NC-64MT-DSS, and
G

(FX2N-232IF)
Communication
Non-Protocol
(-T-DS) PLC FX2NC-96MT-DSS
FX1N Series Generic name of FX1N Series PLCs
FX1N PLC or main unit Generic name of FX1N Series PLC main units
FX1NC Series Generic name of FX1NC Series PLCs

FX1NC PLC or main unit


Generic name of FX1NC Series PLC main units H
Only Japanese manual is available for this product.
Communication
Programming

FX1S Series Generic name of FX1S Series PLCs


FX1S PLC or main unit Generic name of FX1S Series PLC main units
FX0N Series Generic name of FX0N Series PLCs
FX0N PLC or main unit Generic name of FX0N Series PLC main units
FX0 Series Generic name of FX0 Series PLCs
I
Maintenance
Remote

FX0 PLC or main unit Generic name of FX0 Series PLC main units
FX0S Series Generic name of FX0S Series PLCs
FX0S PLC or main unit Generic name of FX0S Series PLC main units
FX2(FX) Series Generic name of FX2(FX) Series PLCs
FX2(FX) PLC or main
Generic name of FX2(FX) Series PLC main units
Apx.A
unit
models
Discontinued

FX2C Series Generic name of FX2C Series PLCs


FX2C PLC or main unit Generic name of FX2C Series PLC main units

A-85
FX Series PLC User's Manual - Data Communication Edition 6 Abbreviations, Generic Names and Terms Used in This Manual
Common Items 5.2 Introduction of Related Manuals

Abbreviation/
Name
generic name
FX1 Series Generic name of FX1 Series PLCs
Generic name of FX1 Series PLC main units
FX1 PLC or main unit
Only Japanese manual is available for this product.
Q PLC Generic name of CPU units QCPU (Q mode) and QCPU (A mode)
Generic name of CPU units Q00JCPU, Q00CPU, Q01CPU, Q02CPU, Q02HCPU,
QCPU (Q mode)
Q06HCPU, Q12HCPU, and Q25HCPU
QCPU (A mode) Generic name of CPU units Q02CPU-A, Q02HCPU-A, and Q06HCPU-A
QnA PLC Generic name of CPU units QnACPU (large type) and QnACPU (small type)
Generic name of CPU units Q2ACPU, Q2ACPU-S1, Q3ACPU, Q4ACPU, and
QnACPU (large type)
Q4ARCPU
QnACPU (small type) Generic name of CPU units Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU, and Q2ASHCPU-S1
A PLC Generic name of CPU units ACPU (large type), ACPU (small type), and A1FXCPU
ACPU (large type) Generic name of CPU units AnUCPU, AnACPU, AnNCPU, and A0J2(H)CPU
ACPU (small type) Generic name of CPU units A2US(H)CPU, AnS(H)CPU, and A1SJ(H)CPU
A1FXCPU Generic name of CPU unit A1FXCPU

2. Expansion boards and special adapters


Abbreviation/
Name
generic name
Expansion board
Generic name of input/output expansion board, communication expansion boards,
Expansion board special adapter connection boards, analog expansion boards and analog potentiometer
expansion boards
Input/output expansion
Generic name of input/output expansion board
board
4EX-BD FX3G-4EX-BD
2EYT-BD FX3G-2EYT-BD
Communication expansion
board or communication Generic name of communication expansion boards
board
232BD FX3U-232-BD, FX3G-232-BD, FX2N-232-BD, and FX1N-232-BD
422BD FX3U-422-BD, FX3G-422-BD, FX2N-422-BD, and FX1N-422-BD
485BD FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ, FX2N-485-BD, and FX1N-485-BD
USBBD FX3U-USB-BD
Analog expansion board Generic name of analog expansion board
2AD-BD FX3G-2AD-BD
1DA-BD FX3G-1DA-BD
Analog potentiometer
Generic name of analog potentiometer expansion board
expansion board
8AV-BD FX3U-8AV-BD, FX3G-8AV-BD
Special adapter connection
board or connector Generic name of CNVBD
conversion board
CNVBD FX3U-CNV-BD, FX2N-CNV-BD, and FX1N-CNV-BD
Special adapters
Generic name of high speed input/output special adapters, CF card special adapter,
Special adapter
communication special adapters and analog special adapters
High speed input/output Generic name of high speed input special adapters and high speed output special
special adapter adapters
2HSY-ADP FX3U-2HSY-ADP
4HSX-ADP FX3U-4HSX-ADP

A-86
FX Series PLC User's Manual - Data Communication Edition 6 Abbreviations, Generic Names and Terms Used in This Manual
Common Items 5.2 Introduction of Related Manuals

A
Abbreviation/

Common Items
Name
generic name
CF card special adapter Generic name of CF card special adapter
CF-ADP FX3U-CF-ADP
Communication special
adapter or communication Generic name of communication special adapters B
adapter

N:N Network
232ADP FX3U-232ADP(-MB), FX2NC-232ADP, FX0N-232ADP, and FX-232ADP
485ADP FX3U-485ADP(-MB), FX2NC-485ADP, FX0N-485ADP, and FX-485ADP
ENET-ADP FX3U-ENET-ADP
Special adapters
Special adapter connection
C

Parallel Link
conversion adapter or
Generic name of CNVADP
connection conversion
adapter
CNVADP FX3G-CNV-ADP, FX3S-CNV-ADP

3. Extension equipment D
Abbreviation/

Computer Link
Name
generic name
Extension equipment
Generic name of extension blocks, powered extension units, special function blocks
Extension equipment
and special function units
Special function unit Generic name of special function units E
Special function block Generic name of special function block

Communication
Inverter
232IF Generic name of FX2N-232IF

4. Networks
Abbreviation/
generic name
Name
F
Open field networks CC-Link and CC-Link/LT

(RS/RS2 Instruction)
Communication
Non-Protocol
Generic name of CC-Link master station and CC-Link remote device stations and
CC-Link equipment
CC-Link intelligent device stations
Generic name of CC-Link master station with model name FX2N-16CCL-M or
CC-Link master (station)
FX3U-16CCL-M
CC-Link remote station Generic name of remote I/O stations and remote device stations G

(FX2N-232IF)
Communication
Non-Protocol
CC-Link intelligent device
Generic name of CC-Link intelligent device station with model name FX3U-64CCL
station
Generic name of CC-Link/LT master station, CC-Link/LT remote I/O stations, power
CC-Link/LT equipment
supply adapters, and dedicated power supplies
CC-Link/LT master Generic name of built-in type CC-Link/LT master and (additional) CC-Link/LT master
Built-in type CC-Link/LT
H
Generic name of built-in type CC-Link/LT master built in to the FX3UC-32MT-LT(-2)
master
Communication
Programming

(Additional) CC-Link/LT
Generic name of CC-Link/LT master station with model name FX2N-64CL-M
master
Power supply adapter Generic name of units connecting the power supply to the CC-Link/LT system
Dedicated power supply Generic name of power supplies connected to the CC-Link/LT system
AnyWire
I
Maintenance
Remote

AnyWireASLINK master Generic name of AnyWireASLINK master station with model name FX3U-128ASL-M
AS-i system
AS-i master Generic name of AS-i system master station with model name FX2N-32ASI-M
MESEC I/O LINK
MELSEC I/O LINK master Generic name of MELSEC I/O LINK master station with model name FX2N-16LNK-M Apx.A
models
Discontinued

Ethernet
Generic name of Ethernet communication special adapter with model name
Ethernet adapter
FX3U-ENET-ADP

A-87
FX Series PLC User's Manual - Data Communication Edition 6 Abbreviations, Generic Names and Terms Used in This Manual
Common Items 5.2 Introduction of Related Manuals

5. Peripheral equipment
Abbreviation/
Name
generic name
Peripheral equipment
Generic name of programming software, handy programming panels, and display
Peripheral equipment
units
Programming tools
Programming tool Generic name of programming software and handy programming panels
Programming software Generic name of programming software
Generic name of programming software packages SWDNC-GXW2-J and
GX Works2
SWDNC-GXW2-E
Generic name of programming software packages SWD5C-GPPW-J and
GX Developer
SWD5C-GPPW-E
FXGP/WIN Generic name of programming software packages FX-PCS/WIN and FX-PCS/WIN-E
Handy programming panel Generic name of FX-30P, FX-20P(-E)-SET0, FX-20P(-E), FX-10P-SET0 and
(HPP) FX-10P(-E)
Display units
GOT1000 Series Generic name of GT16, GT15, GT14, GT11 and GT10
GOT-900 Series Generic name of GOT-A900 and GOT-F900 Series
GOT-A900 Series Generic name of GOT-A900 Series
GOT-F900 Series Generic name of GOT-F900 Series
Internet mail sending tools
Mail sending units Generic name of FX-232DOPA mail sending units
FX-232DOPA mail sending main units
FX-232DOPA Only Japanese manual is available for this product.
These products can only be used in Japan.

6. Others
Abbreviation/
Name
generic name
Inverters
Generic name of Mitsubishi F800, A800, F700, A700, E700, D700, V500, F500, A500,
FREQROL inverter
E500, and S500 Series inverters
Communication
Generic name of communication equipment operating in accordance with RS-232C,
communication equipment operating in accordance with RS-422, communication
Communication equipment equipment operating in accordance with RS-485, communication equipment operating
in accordance with USB, and communication equipment operating in accordance with
Ethernet
Communication
equipment operating in
Generic name of 232BD, 232ADP, and 232IF
accordance with RS-
232C
Communication
equipment operating in Generic name of 422BD
accordance with RS-422
Communication
equipment operating in Generic name of 485BD and 485ADP
accordance with RS-485
Communication
equipment operating in Generic name of USB BD
accordance with USB
Communication
equipment operating in Generic name of special adapter connectable to the Ethernet
accordance with Ethernet

A-88
FX Series PLC User's Manual - Data Communication Edition 6 Abbreviations, Generic Names and Terms Used in This Manual
Common Items 5.2 Introduction of Related Manuals

A
Abbreviation/

Common Items
Name
generic name
Personal computers
Personal computers supporting Windows in which GX Works2, GX Developer or
Personal computer FXGP/WIN is installed
Refer to the manual for each software product for supported Windows versions. B
Generic name of Windows 95, Windows 98, Windows Me, Windows NT4.0,

N:N Network
Windows Windows 2000, Windows XP, Windows Vista, Windows 7, Windows 8, Windows 8.1
and Windows 10
Windows 95 Abbreviation of Microsoft Windows 95
Windows 98 Abbreviation of Microsoft Windows 98
Windows Me Abbreviation of Microsoft Windows Millennium Edition
C

Parallel Link
Windows NT4.0 Abbreviation of Microsoft Windows NT4.0 Workstation
Windows 2000 Abbreviation of Microsoft Windows 2000 Professional
Abbreviation of Microsoft Windows XP Professional and Microsoft Windows
Windows XP
XP Home Edition
Abbreviation of Microsoft Windows Vista Ultimate Operating System
D

Computer Link
Microsoft Windows Vista Enterprise Operating System
Windows Vista Microsoft Windows Vista Business Operating System
Microsoft Windows Vista Home Premium Operating System
Microsoft Windows Vista Home Basic Operating System
Abbreviation of Microsoft Windows 7 Enterprise Operating System E
Microsoft Windows 7 Ultimate Operating System

Communication
Inverter
Windows 7 Microsoft Windows 7 Professional Operating System
Microsoft Windows 7 Home Premium Operating System
Microsoft Windows 7 Starter Operating System
Abbreviation of Microsoft Windows 8 Operating System
Windows 8 Microsoft Windows 8 Pro Operating System F
Microsoft Windows 8 Enterprise Operating System

(RS/RS2 Instruction)
Communication
Non-Protocol
Abbreviation of Microsoft Windows 8.1 Operating System
Windows 8.1 Microsoft Windows 8.1 Pro Operating System
Microsoft Windows 8.1 Enterprise Operating System
Microsoft Windows 10 Home Operating System G
Microsoft Windows 10 Pro Operating System

(FX2N-232IF)
Communication
Non-Protocol
Windows 10
Microsoft Windows 10 Enterprise Operating System
Microsoft Windows 10 Education Operating System

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

A-89
FX Series PLC User's Manual - Data Communication Edition 6 Abbreviations, Generic Names and Terms Used in This Manual
Common Items 5.2 Introduction of Related Manuals

MEMO

A-90
FX Series PLC User's Manual - Data Communication Edition
N:N Network

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
B. N:N Network
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains the "N:N Network" provided for the MELSEC-F FX Series Programmable Controllers
Maintenance
Remote

and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

B-1
FX Series PLC User's Manual - Data Communication Edition
N:N Network

B-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
N:N Network 1.1 Outline of System

Common Items
1. Outline
This chapter explains the N:N Network. B

N:N Network
1.1 Outline of System
The N:N Network allows connection of up to eight FX PLCs via mutually linked devices through
communication in accordance with RS-485.
C
1) One of three patterns can be selected according to the number of devices to be linked (except FX0N and

Parallel Link
FX1S PLCs).
2) Data link is automatically updated among a maximum of eight FX PLCs.
3) The available total extension distance is 500 m (1640' 5") maximum (when only the 485ADP is used in
the configuration).
D

Computer Link
Important points and reference
System chapter/section

8 units ....... Number of linked units


500 m (1640' 5") [50 m (164' 0") when 485BD is included] ....... Total extension distance
For the specifications,
FX PLC FX PLC FX PLC refer to Chapter 2. E
Master station Slave station No. 1 Slave station No. 2

Communication
Inverter
.......
To check applicable PLC
models, refer to Section 1.3.

+ + +
Communication
equipment operating
Communication
equipment operating
Communication
equipment operating
F
For selection,
in accordance with .......

(RS/RS2 Instruction)
Communication
Non-Protocol
in accordance with in accordance with refer to Chapter 3.
RS-485 RS-485 RS-485

For wiring,
....... refer to Chapter 4.

Bit devices Transfer Bit devices Transfer Bit devices ....... The number of linked devices
M1000 to M1063
direction
M1000 to M1063
direction
M1000 to M1063
can be selected among three
patterns.
G
M1064 to M1127 M1064 to M1127 M1064 to M1127 For details, refer to Chapter 2.

(FX2N-232IF)
Communication
Non-Protocol
M1128 to M1191 M1128 to M1191 M1128 to M1191
...

...

...

M1448 to M1511 M1448 to M1511 M1448 to M1511


Word devices Word devices Word devices The link information can be
D0 to D7 D0 to D7 D0 to D7 monitored in the master
D10 to D17 D10 to D17 D10 to D17 station and all slave stations.
D20 to D27 D20 to D27 D20 to D27 H
...

...

...

Communication
Programming

D70 to D77 D70 to D77 D70 to D77

The figure above shows the maximum number of linked devices. There are differences in the specifications and
limitations depending on the selected link pattern and FX Series.

I
Maintenance
Remote

Apx.A
models
Discontinued

B-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
N:N Network 1.2 Procedures Before Operation

1.2 Procedures Before Operation


The flow chart below shows the N:N Network setting procedures up until data link:

N:N Network

Refer to Chapter 1.

Outline Outline of system


Applicable PLC versions
Applicable programming tools
Refer to Chapter 2.

Check communication specifications. Communication specifications


Number of link points and time
Number of system devices
Refer to Chapter 3.

Determine system configuration and selection. System configuration


Select communication equipment.
Refer to Chapter 4.

Perform wiring. Wiring procedure


One-pair wiring using twisted cables
Wiring example

Programming tool

Connect PLC.*1

Refer to Chapter 5.
Perform PLC communication setting
Serial communication setting in PLC
(initialization).
Communication setting is not required.
(Check only unset items.)
Turn ON power. Refer to Chapter 6.
Perform test run (communication test and
Communication test
judgement method).
Create test programs.

Refer to Chapter 7.

Create programs. Communication parameter setting


programs
Basic program
Based on SD/RD lamp lighting status and Error indication program example
contents of error check devices, verify that Detailed explanation of setting devices
communication is normally executed.
If there is abnormality, refer to the troubleshooting
(Chapter 9).

Refer to Chapter 8.

Practical program examples Program examples of pattern 2 are shown.

*1 For the method to connect a programming tool to a PLC, refer to the "Programming Communication" section in this
manual or the respective programming tool manual.
For details on operating procedures, refer to the respective programming tool manual.

B-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
N:N Network 1.3 Communication Type Applicability in PLC

A
1.3 Communication Type Applicability in PLC

Common Items
1.3.1 Applicable versions
The communication type is applicable in the following versions. B
:Applicable (If applicable versions of main units are limited, they are described inside ( ).)

N:N Network
:Not applicable
PLC Applicability (applicable version) Remarks
FX3UC Series
FX3U Series
FX3GC Series
C

Parallel Link
FX3G Series
FX3S Series
FX2NC Series
FX2N Series (Ver. 2.00 or later)*1
FX1NC Series D

Computer Link
FX1N Series
FX1S Series The link device range is limited.
FX0N Series *1 The link device range is limited.
(Ver. 2.00 or later)
FX0S Series N:N Network option is not provided.
FX0 Series N:N Network option is not provided. E
FX2C Series N:N Network option is not provided.

Communication
Inverter
FX2(FX) Series N:N Network option is not provided.
FX1 Series N:N Network option is not provided.

*1. Applicable in products manufactured in October, 1997 and later (manufacturers serial No.: 7X**** and
later). F

(RS/RS2 Instruction)
Communication
Non-Protocol
1.3.2 Version check
The PLC version can be checked by reading the last three digits of device D8001.
For a detailed description of the version check, refer to A. Common Items Section 4.2.
G
1.3.3 How to look at the manufacturer's serial number

(FX2N-232IF)
Communication
Non-Protocol
The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT"
indicated on the front of the product.
For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Section 4.1.
H
Communication
Programming

1.3.4 Products whose production was stopped


Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A.
To see the latest available products, refer to the general catalog.
I
Maintenance
Remote

Apx.A
models
Discontinued

B-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
N:N Network 1.4 Programming Tool Applicability

1.4 Programming Tool Applicability

1.4.1 For applicable versions


The programming tool is applicable for each FX Series from the following version:
1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later -
FX-30P Ver. 1.50 or later -
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 3.00 or later
FX-20P-MFXC-E
FX-10P-E Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW5 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 4.00 or later
FX-20P-MFXD-E
FX-10P-E Ver. 4.00 or later

B-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
N:N Network 1.4 Programming Tool Applicability

A
Product name Model name Applicable version Remarks

Common Items
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later) B
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units

N:N Network
models and versions supporting the list editor function.

2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs C
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later

Parallel Link
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units

FX3G PLC
models and versions supporting the list editor function.
D

Computer Link
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later

GOT1000 Series display units


Refer to manuals of GOT1000 Series display units for applicable
models and versions supporting the list editor function. E

Communication
Inverter
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. F
FX3S PLC

(RS/RS2 Instruction)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
G
FX2N and FX2NC PLCs

(FX2N-232IF)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW2 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.00 or later
FX-PCS-KIT/98
FX-PCS/98-3
SW1PC-FXGP/98(-3,-5)
SW1PC-FXGP/98-3
Ver. 4.00 or later
Ver. 4.00 or later
H
Communication
Programming

FX-PCS-KIT/V-3 SW1PC-FXGP/V3 Ver. 2.00 or later -


FX-A7PHP-KIT SW1RX-GPPFX Ver. 3.00 or later
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
FX-20P-MFXC
Ver. 4.00 or later I
Maintenance
Remote

FX-10P(-SET0) Ver. 3.00 or later


GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later) Apx.A
models
Discontinued

Refer to manuals of GOT1000 Series display units for applicable


GOT1000 Series display units
models and versions supporting the list editor function.

B-7
FX Series PLC User's Manual - Data Communication Edition 1 Outline
N:N Network 1.4 Programming Tool Applicability

Product name Model name Applicable version Remarks


FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 5.00 or later
-
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 5.00 or later
FX-20P-MFXD
FX-10P(-SET0) Ver. 4.00 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

1.4.2 For non-applicable versions (setting an alternative model)


Even programming tool not applicable to a PLC can create programs when an alternative model is set.
In this case, however, programming is enabled only in the function ranges provided for the alternative PLC
model such as instructions and program size.
Model to be
Model to be set Priority: High Low
programmed
FX3UC Series FX3UC FX2N FX2(FX)
FX3U Series FX3UC, FX3U FX2N FX2(FX)
*1
FX3GC Series FX3G, FX3GC FX1N FX2N*1
FX3G Series FX3G FX1N*1 FX2N*1
FX3S Series FX3S FX3G FX1N*1
FX2NC Series FX2NC, FX2N FX2(FX)
FX2N Series FX2N FX2(FX)
FX1NC Series FX1NC, FX1N FX2N FX2(FX)
FX1N Series FX1N FX2N FX2(FX)
FX1S Series FX1S FX2(FX)
FX0N Series FX0N FX2(FX)
FX0S Series FX0S FX2(FX)
FX0 Series FX0 FX2(FX)
FX2C Series FX2C, FX2(FX) FX2(FX)
FX2(FX) Series FX2(FX)
FX1 Series FX1

*1. "FX2N" is selected when the FX-10P(-E) is used.

Point
In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

B-8
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
N:N Network 2.1 Communication Specifications (Reference)

Common Items
2. Specifications
This chapter explains the communication specifications and performance. B

N:N Network
2.1 Communication Specifications (Reference)
Communication is executed according to the (fixed) specifications shown in the table below. Specification
items such as baud rate cannot be changed.
C

Parallel Link
Item Specifications Remarks
Number of connectable units 8 maximum
Transmission standard RS-485 standard
500 m (1640' 5") or less
Maximum total extension Distance varies depending on
distance
[50 m (164' 0") or less when 485BD
is included in system]
communication equipment type. D

Computer Link
Protocol type N:N Network
Control procedure
Half-duplex,
Communication method
bidirectional communication
Baud rate 38400 bps E

Communication
Inverter
Start bit
Character Data bit
Fixed
format Parity bit
Stop bit
Header F
Fixed

(RS/RS2 Instruction)
Communication
Non-Protocol
Terminator
Control line
Sum check Fixed

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-9
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
N:N Network 2.2 Link Specifications

2.2 Link Specifications

2.2.1 Link patterns and number of link points in each FX Series


The number of occupied link points varies depending on the number of slave stations used.
For example, when three slave stations are connected in "Pattern 1", M1000 to M1223 and D0 to D33 are
occupied, and unoccupied devices can be used as general devices for control.
(Link devices for unconnected slave stations can be used as general devices for control, but it is
recommended to leave them in the unoccupied status if slave stations may be added in the future.)
: Applicable
: Not applicable
PLC Series Pattern 0 Pattern 1 Pattern 2
FX3U, FX3UC Series
FX3G, FX3GC Series
FX3S Series
FX2N, FX2NC Series
FX1N, FX1NC Series
FX1S Series
FX0N Series

Pattern 0 Pattern 1 Pattern 2


Bit Word Bit Word Bit Word
Station No. device (M) device (D) device (M) device (D) device (M) device (D)
4 in each 32 in each 4 in each 64 in each 8 in each
0
station station station station station
Master Station
D 0 to D 3 M1000 to M1031 D 0 to D 3 M1000 to M1063 D 0 to D 7
station No. 0
Station
D10 to D13 M1064 to M1095 D10 to D13 M1064 to M1127 D10 to D17
No. 1
Station
D20 to D23 M1128 to M1159 D20 to D23 M1128 to M1191 D20 to D27
No. 2
Station
D30 to D33 M1192 to M1223 D30 to D33 M1192 to M1255 D30 to D37
No. 3
Slave Station
D40 to D43 M1256 to M1287 D40 to D43 M1256 to M1319 D40 to D47
stations No. 4
Station
D50 to D53 M1320 to M1351 D50 to D53 M1320 to M1383 D50 to D57
No. 5
Station
D60 to D63 M1384 to M1415 D60 to D63 M1384 to M1447 D60 to D67
No. 6
Station
D70 to D73 M1448 to M1479 D70 to D73 M1448 to M1511 D70 to D77
No. 7

B-10
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
N:N Network 2.2 Link Specifications

A
2.2.2 Link time

Common Items
The link time indicates the cycle time in which link devices are updated.
The link time varies depending on the number of linked units (master station and slave stations) and the
number of linked devices as shown in the table below.
Unit: ms B
Pattern 0 Pattern 1 Pattern 2

N:N Network
Number of
linked 0 bit-devices 32 bit-devices 64 bit-devices
stations 4 word-devices 4 word-devices 8 word-devices
2 18 22 34
3 26 32 50
C
4 33 42 66

Parallel Link
5 41 52 83
6 49 62 99
7 57 72 115
8 65 82 131
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-11
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
N:N Network 3.1 System Configuration

3. System Configuration and Equipment Selection


This chapter explains the configuration of the communication equipment operating in accordance with RS-
485 and the system selection required by FX PLCs.

3.1 System Configuration


This section outlines the system configuration required to use the N:N Network.
Connect (optional) equipment operating in accordance with RS-485 to the FX PLC main unit.

1 , 2 , 3 and 4 indicate the communication equipment combination patterns.

Communication equipment operating Total extension


in accordance with RS-485 FX PLC Important point in selection distance

1
This is the communication board built 50 m
+ into the PLC, reducing the installation
(164' 0")
area.

Communication
board

2
Attach the special adapter connection
board to the main unit, and then 500 m
+ + attach the communication adapter to (1640' 5")
the left side of the main unit.

Communication Special adapter


adapter connection
board

3
Attach the connector conversion
adapter to the main unit, and then 500 m
+ + attach the communication adapter to (1640' 5")
the left side of the main unit.

Communication Connector
adapter conversion
adapter

4
+ Attach the communication adapter to 500 m
the left side of the main unit. (1640' 5")

Communication
adapter

For communication equipment combinations for each FX Series, refer to the next page.

B-12
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
N:N Network 3.2 Applicable FX PLC and Communication Equipment

A
3.2 Applicable FX PLC and Communication Equipment

Common Items
Select a (optional) communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the external dimensions are different between the units shown in "FX2NC-485ADP/
FX0N-485ADP". Select either one. B
- In the table below, only the cable is different between the units shown in "FX3G-485-BD/FX3G-485-BD-

N:N Network
RJ". Select either one.
- N:N Network is not provided for the FX1, FX2(FX), FX2C, FX0 and FX0S PLCs.
Total extension
FX Series Communication equipment (option) Check
distance
C

Parallel Link
500 m
(1640' 5")

FX2NC-485ADP FX0N-485ADP
FX0N
(European terminal block) (Terminal block) D

Computer Link
50 m
(164' 0")
FX1N-485-BD
(European terminal block) E

Communication
Inverter
FX1S + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP F


(European terminal block) (Terminal block)

(RS/RS2 Instruction)
Communication
Non-Protocol
50 m
(164' 0")
FX1N-485-BD G
(European terminal block)

(FX2N-232IF)
Communication
Non-Protocol
FX1N + + 500 m
(1640' 5") H
Communication
Programming

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0") I
Maintenance
Remote

FX2N-485-BD

FX2N + + 500 m Apx.A


(1640' 5")
models
Discontinued

FX2N-CNV-BD FX2NC-485ADP FX2N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

B-13
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
N:N Network 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3S
+ 500 m
(1640' 5")

FX3S-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3G
(14-point, 24-point 500 m
type) (1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

When using channel 1 (ch 1)

ch1 ch1

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch1 when connected to
the option connector 1.
FX3G
ch1
(40-point, 60-point
type)

500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

B-14
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
N:N Network 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch2 ch2
B

N:N Network
50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch2 when connected to
the option connector 2.
C

Parallel Link
ch1 ch2
FX3G
(40-point, 60-point
type)

500 m D
(1640' 5")

Computer Link
FX3G-CNV-ADP FX3U-ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
When using channel 1 (ch 1)
E

Communication
Inverter
ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
F
SD SD B

SG

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U-485-BD
(European terminal block)

ch1
FX3U

G
+ 500 m
(1640' 5")

(FX2N-232IF)
Communication
Non-Protocol
FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-15
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
N:N Network 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch1 ch2

+
RD

SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
ch1 ch2
FX3U

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

500 m
(1640' 5")

FX2NC-485ADP FX0N-485ADP
FX1NC (European terminal block) (Terminal block)

500 m
(1640' 5")

FX2NC-485ADP FX0N-485ADP
FX2NC (European terminal block) (Terminal block)

When using channel 1 (ch 1)


ch1

500 m
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)
When using channel 2 (ch 2)

ch1 ch2
FX3GC

+ 500 m
(1640' 5")

FX3U-ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).

B-16
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
N:N Network 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

B
500 m

N:N Network
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)
When using channel 2 (ch 2)
C
ch1 ch2

Parallel Link
FX3UC
(D, DS, DSS)
+ 500 m

FX3U-232ADP(-MB), FX3U-485ADP(-MB)
(1640' 5")
D
FX3U-485ADP(-MB), (European terminal block)

Computer Link
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
When using channel 1 (ch 1)
ch1
E

Communication
Inverter
RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)
F
ch1

(RS/RS2 Instruction)
Communication
Non-Protocol
+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB) G
(European terminal block)

(FX2N-232IF)
Communication
Non-Protocol
When using channel 2 (ch 2)
ch1 ch2

+ H
RD

FX3UC-32MT-LT SD

(-2) 500 m
Communication
Programming

(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
I
ch1 ch2
Maintenance
Remote

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB) Apx.A
FX3U-485ADP(-MB), (European terminal block)
models
Discontinued

FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

B-17
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.1 Wiring Procedure

4. Wiring
This chapter explains the wiring.

WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.

WIRING PRECAUTIONS

Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents
due to abnormal data written to the PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the PLC. However, do not use common
grounding with heavy electrical systems.
Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure
that the screwdriver does not touch the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

4.1 Wiring Procedure

1 Preparing for wiring


Prepare cables and terminal resistors required for wiring.
For details, refer to Section 4.2.

2 Turning OFF the power to the PLC


Before starting any wiring work, make sure that the PLC power is OFF.
3 Connecting the power supply (FX0N-485ADP only)
Connect the power supply to the 24V DC power terminal.
4 Wiring communication equipment
Connect communication equipment operating in accordance with RS-485.
For details, refer to Section 4.3.

B-18
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.2 Selecting Cables and Terminal Resistors

A
4.2 Selecting Cables and Terminal Resistors

Common Items
Select cables using the procedure described below.

4.2.1 Twisted pair cable


B
Use shielded twisted pair cables for connecting communication equipment operating in accordance with RS-

N:N Network
485.
The table below shows recommended model names and manufacturers of cables used for wiring.

1. Recommended cables

Manufacturer Model name Remarks


C

Parallel Link
SPEV(SB)-0.2-2P Two-pair cable of 0.2 mm2
Mitsubishi Cable Industries, Ltd. SPEV(SB)-MPC-0.2 3P Three-pair cable of 0.2 mm2
SPEV(SB)-0.5-2P Two-pair cable of 0.5 mm2

Showa Holdings Co., Ltd.


KMPEV-SB CWS-178 0.2SQ 2P Two-pair cable of 0.2 mm2
D
KMPEV-SB CWS-178 0.5SQ 2P Two-pair cable of 0.5 mm2

Computer Link
DPEV SB 0.3 3P Three-pair cable of 0.3 mm2
Sumitomo Electric Industries, Ltd.
DPEV SB 0.5 3P Three-pair cable of 0.5 mm2
D-KPEV-SB 0.2 3P Three-pair cable of 0.2 mm2
The Furukawa Electric Co., Ltd.
D-KPEV-SB 0.5 3P Three-pair cable of 0.5 mm2 E

Communication
Inverter
IPEV-SB 2P 0.3 mm2 Two-pair cable of 0.3 mm2
Fujikura Ltd.
IPEV-SB 2P 0.5 mm2 Two-pair cable of 0.5 mm2

2. Cable structural drawing (reference)


Pair F

(RS/RS2 Instruction)
Communication
Non-Protocol
Shield

G
Two-pair cable structural

(FX2N-232IF)
Communication
Non-Protocol
drawing example Three-pair cable structural
drawing example

4.2.2 10BASE-T cable


H
10BASE-T cables used in LAN wiring for a personal computer can be connected to FX3G-485-BD-RJ.
Communication
Programming

1. Selection procedure when purchasing


1) Cable type : 10BASE-T cable (Category 3 or higher)
2) Connection specifications : Straight type
3) Connector : RJ45 connector (Connector with metal frame is used) I
Maintenance
Remote

2. Cautions on using commercial cables


Pay attention to the following point when purchasing commercial cables.
Use shielded cables. Make sure to connect the shield to the metal frame of the connector, and perform
class D grounding.
Apx.A
models
Discontinued

B-19
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.2 Selecting Cables and Terminal Resistors

4.2.3 Connecting cables

1. European type terminal block


The FX3G-485-BD-RJ terminal block is used for grounding.
The other options use shielded twisted pair cables for connecting communication equipment operating in
accordance with RS-485.
The table below shows applicable cables and tightening torques.
Cable size when Cable size when Bar terminal with Tool size
Tightening
one cable is two cables are Insulating sleeve
torque A B
connected connected (cable size)
FX3U-485-BD
FX3G-485-BD AWG22 to Applicable 0.22 to 0.25
AWG22 0.4 (0.01") 2.5 (0.09")
FX3U-485ADP AWG20 (AWG22 to AWG20) Nm
(-MB)
FX3G-485-BD- 0.5 to 0.6
AWG20 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
RJ Nm
FX2N-485-BD 0.5 to 0.6
AWG26 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
FX1N-485-BD Nm
AWG26 to AWG26 to 0.4 to 0.5
FX2NC-485ADP Not applicable 0.6 (0.03") 3.5 (0.14")
AWG16 AWG20 Nm

Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
With regard to the cable end treatment, use a stranded cable or solid cable as it is, or use a bar terminal with
insulating sleeve.
FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD and FX2NC-485ADP cannot use a bar terminal with insulating
sleeve.
When using a stranded cable or solid cable as it is
- Twist the end of a stranded cable so that wires do not get barbed.
- Do not plate the end of the cable.
FX3G-485-BD, FX3U-485-BD, FX3G-485-BD-RJ,
FX3U-485ADP(-MB) FX2N-485-BD, FX1N-485-BD FX2NC-485ADP

Approx. 9 mm Approx. 6 mm Approx. 8 mm


(0.35") (0.23") (0.31")

When using a bar terminal with insulating sleeve Insulating sleeve Contact area
Because it is difficult to insert a cable into an insulating sleeve (Crimp area)
depending on the thickness of the cable sheath, select the proper cable
according to the outline drawing. 8 mm (0.31")
<Reference> 2.6 mm
(0.1") 14 mm
Manufacturer Model name Caulking tool (0.55")

CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
(or CRIMPFOX 6T-F*2)

*1. Old model name : CRIMPFOX ZA 3


*2. Old model name : CRIMPFOX UD 6

B-20
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.2 Selecting Cables and Terminal Resistors

A
Tool

Common Items
Select a
When tightening a terminal on the European terminal block, use a small screwdriver
with a
commercial straight shape screwdriver whose tip is shown in the figure to straight tip.
the right.

Note A B
For size A and size B,
B
If the diameter of screwdriver grip is too small, tightening torque will not refer to the table above.

N:N Network
be able to be achieved. To achieve the appropriate tightening torque
shown in the previous page, use the following screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
<Reference>
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB) C
Manufacturer Model name

Parallel Link
Phoenix Contact Co., Ltd. SZS 0.4 2.5

FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD, FX2NC-485ADP


Manufacturer Model name
Phoenix Contact Co., Ltd. SZF 1-0.6 3.5 D

Computer Link
2. Terminal block
In the FX0N-485ADP and FX-485ADP, the terminal screw size is "M3".
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 Nm. E
Do not tighten terminal screws with a torque outside the above-mentioned range.

Communication
Inverter
Failure to do so may cause equipment failures or malfunctions.
When wiring one cable to one terminal
Terminal Crimp
screw terminal
6.2mm(0.24")
3.2(0.13")
F

(RS/RS2 Instruction)
Communication
Non-Protocol
or less
3.2(0.13")
6.2mm(0.24") Terminal
or less

When wiring two cables to one terminal


G

(FX2N-232IF)
Communication
Non-Protocol
3.2(0.13")
6.2mm(0.24") Terminal Crimp
or less screw terminal
6.3mm(0.25")
or more
H
3.2(0.13")
Communication
Programming

6.2mm(0.24") Terminal
or less 6.3mm(0.25")
or more

I
Maintenance
Remote

Apx.A
models
Discontinued

B-21
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.2 Selecting Cables and Terminal Resistors

4.2.4 Connecting terminal resistors


Make sure to provide a terminal resistor at the end of each line. Brown Precision
In the case of one-pair wiring, connect a terminal resistor to the RDA-RDB signal
terminal of the communication equipment.

1. Terminal resistor type


1 1 1 =110
Use two terminal resistors of 110 , 1/2 W. (101)
Among the terminal resistors supplied with the communication equipment, select
ones with the color codes shown to the right.

2. When using the FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ or FX3U-485ADP(-MB)


The FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB) have built-in terminal resistors.
Set the terminal resistor selector switch accordingly.
FX3U-485-BD FX3U-485ADP(-MB)

Terminal
resistor 330
Terminal
selector OPEN resistor selector
switch
switch
110

FX3G-485-BD
Remove the upper terminal block before changing over the switch in the FX3G-485-BD.

Removal: Loosen the terminal block mounting screws, and remove the terminal block.
Installation: Attach the terminal block, and tighten the terminal block mounting screws.
Tightening torque: 0.4 to 0.5 Nm
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do
so may cause equipment failures or malfunctions.

For installation and removal of the terminal block, use the


Select a
recommended tool shown below or a tool having straight tip (such as
screwdriver
screwdriver) as shown in the right figure. with a
<Reference> straight tip.
Manufacturer Model name
Phoenix Contact Co., Ltd. SZS 0.4 2.5
0.4mm 2.5mm
(0.01") (0.09")

Terminal resistor
selector switch

Terminal block mounting screws

FX3G-485-BD-RJ

Terminal resistor
selector switch

B-22
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.3 Connection Diagram

A
4.3 Connection Diagram

Common Items
Use one-pair wiring for an N:N Network.
FX3U-485-BD FX3U-485-BD
FX3G-485-BD FX3G-485-BD
FX2N-485-BD
FX1N-485-BD
FX2N-485-BD
FX1N-485-BD
B
FX3U-485ADP(-MB) FX0N-485ADP FX3U-485ADP(-MB) FX2NC-485ADP

N:N Network
SDA SDA SDA SDA
(TXD+) (TXD+) (TXD+) (TXD+)

Terminal SDB SDB SDB SDB Terminal


resistor:
110
(TXD-) (TXD-) (TXD-) (TXD-) resistor:
110 C
RDA RDA RDA RDA

Parallel Link
*3 *3
(RXD+) (RXD+) (RXD+) (RXD+)

RDB RDB RDB RDB


(RXD-) (RXD-) (RXD-) (RXD-)

SG
LINK
SG
SG D

Computer Link
FG*2 SG
Class-D grounding Class-D grounding
(resistance: 100 or less)*1 (resistance: 100 or less)*1

*1 Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to the FX2N-485-BD, FX1N-485-BD,
FX3U-485-BD, FX3G-485-BD, FX2NC-485ADP or FX3U-485ADP(-MB). E
*2 Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring Class-D grounding.

Communication
Inverter
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
*3 Make sure to provide a terminal resistor at the end of each line.
The FX3U-485-BD, FX3G-485-BD and FX3U-485ADP(-MB) have a built-in terminal resistor. Set the terminal resistor selector
switch accordingly.
The FX0N-485ADP, FX2NC-485ADP, FX2N-485-BD and FX1N-485-BD are supplied together with terminal resistors.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-23
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.3 Connection Diagram

FX3G-485-BD-RJ
FX3G-485-BD-RJ Distributor (BMJ-8) Distributor (BMJ-8) FX3G-485-BD-RJ
RDA 5 5 5 5 5 5 RDA
RDB 4 4 4 4 4 4 RDB
SDA 3 3 3 3 3 3 SDA
SDB 6 6 6 6 6 6 SDB
SG 1 1 1 1 1 1 SG
2 2 2 2 2 2
Terminal Terminal
resistor 7 7 7 7 7 7 resistor
*2 8 8 8 8 8 8 *2
Connector metal frame 5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Connector metal frame
*1 *1
Class-D Class-D Class-D
Class-D grounding grounding grounding
grounding *1 *1 *1

5 4 3 6 1 2 7 8 Connector metal frame 5 4 3 6 1 2 7 8 Class-D

Connector metal frame


(Terminal resistor grounding (Terminal resistor
selector switch: selector switch:
110)*2 110)*2
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB
SG

SG
FX3G-485-BD-RJ FX3G-485-BD-RJ
(Terminal resistor selector switch: Open) (Terminal resistor selector switch: Open)

*1. Use shielded cables, and make sure to perform class D grounding on the shield.
When using the terminal block to connect ground, wire the ground wire only to either one of two
poles of the terminal block.
*2. Make sure to provide a terminal resistor at the end of each line. Set the terminal resistor selector
switch accordingly.
Prepare the following devices if necessary.
Product name Model name Manufacturer
RJ45 connector TM11AP-88P HIROSE ELECTRIC CO., LTD.
BMJ-8
Distributor BMJ-8-28N (No internal connection of the No. 2 and 8 pin) HACHIKO ELECTRIC CO., LTD.
(Do not use a plug with terminal resistor)

The FX3G-485-BD-RJ has a built-in wiring circuit switch.


Set the wiring circuit switch to 1 pair.

Wiring circuit
switch

B-24
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
N:N Network 4.4 Grounding

A
4.4 Grounding

Common Items
Grounding should be performed as stated below.
The grounding resistance should be 100 or less.
Independent grounding should be performed for best results.
When independent grounding can not be performed, perform "shared grounding" as shown in the following
B

N:N Network
figure.
For details, refer to the Hardware Edition of each series.

PLC Other PLC Other PLC Other


equipment equipment equipment

C
Independent grounding Shared grounding Common grounding

Parallel Link
Best condition Good condition Not allowed

The grounding wire size should be AWG 14 (2 mm2) or larger.


The grounding point should be close to the PLC, and all grounding wires should be as short as possible.

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-25
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
N:N Network 5.1 Check Procedure

5. Communication Setting (Initialization) in FX


Programmable Controller
The communication setting is not required in FX PLCs for the N:N network.
Using the following procedure, verify that the communication setting is not specified for another
communication type and verify that the setting is correct.
When using this communication function in ch1 in an FX3S, FX3G, FX3GC, FX3U or FX3UC PLC, check D8120
and D8400 using the following procedure.
When using this communication function in ch2 in an FX3G, FX3GC, FX3U or FX3UC PLC, check D8420 using
the following procedure.
In other PLCs, use D8120 for verification.

5.1 Check Procedure

1 Monitoring D8120 (D8400, D8420)


Turn ON the power to the PLC while it is in STOP mode, and monitor D8120 (D8400, D8420).

1. When the value of D8120 (D8400, D8420) is "0"


The communication setting is not provided.

2. When the value of D8120 (D8400, D8420) is any value other than "0"
The communication setting is provided.

2 Checking absence/presence of parameter setting


Check for the absence/presence using the GX Works2, GX Developer, FXGP/WIN or FX-30P.
1) GX Works2 operating procedure (For details, refer to Section 5.2.)
2) FXGP/WIN operating procedure (For details, refer to Section 5.3.)
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

3 Checking absence/presence of sequence program setting


Check whether or not a write instruction is programmed for D8120 (D8400, D8420).

1. When such an instruction is programmed


Program example: (for D8120)
Change the program as shown below, and then change the PLC mode from STOP to RUN.
M8002 FNC 12
MOV H23F6 D8120 Program example
Initial pulse
The value varies depending on
the communication setting.

M8002 FNC 12
MOV H0000 D8120 Changed program
Initial pulse

2. When such an instruction is not programmed


Proceed to the next step.

4 Monitoring D8120 (D8400, D8420) again, and confirming that its value is "0"

B-26
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
N:N Network 5.2 Communication Setting Using Parameter Method (GX Works2)

A
5.2 Communication Setting Using Parameter Method (GX Works2)

Common Items
Communication setting may be changed using the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 5.3. B
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

N:N Network
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.2.1 Operating procedure


This subsection explains the serial communication setting method.
Suppose that GX Works2 is already started up.
C

Parallel Link
1 Opening the parameter setting window
In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar. D

Computer Link
E

Communication
Inverter
F
2 Setting the serial communication (parameters)

(RS/RS2 Instruction)
Communication
Non-Protocol
Select a channel to be used, and click the [PLC System(2)] tab on the dialog box.
Make sure that the "Operate Communication Setting" check box is clear.
If a check mark is there, clear it.
Click [End].
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

3 Writing parameters and program to the PLC Apx.A


Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
models
Discontinued

[Execute].

B-27
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
N:N Network 5.3 Communication Settings Using Parameter Method (FXGP/WIN)

5.3 Communication Settings Using Parameter Method (FXGP/WIN)


Communication setting may be changed using the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with FXGP/WIN.
Ch2 cannot be set using FXGP/WIN.
For details on GX Works2 operating procedure, refer to section 5.2.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already
started up.

1 Adjusting serial setting (parameter)


Double-click [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of parameter settings.

1. When there are no parameter settings


The dialog box shown below appears to indicate that there are no communication settings.
Click the [No] button.
In this case, the next step is not required.

2. When there are already parameter settings


The dialog box shown below appears to indicate that there are communication settings.
Click the [Clear] button to delete the communication settings from parameters.
Transfer parameters to the PLC using the following step.

2 Writing a sequence program (parameters) to the PLC


Select [PLC] [Transfers] [Write] from the toolbar, and click [OK] button.

B-28
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
N:N Network 6.1 Test Procedure

Common Items
6. Test Run (Communication Test)
This chapter explains the communication test procedures for the N:N Network. B
It is recommended to first wire the master station and slave stations, initialize communication settings in the

N:N Network
FX PLCs, and then execute the communication test using the following procedure to confirm proper
operation.

6.1 Test Procedure


C

Parallel Link
1 Creating programs for the communication test
Create new programs for the communication test for the master station and slave stations.
For program examples, refer to Section 6.2.
D
2

Computer Link
Transferring the program to each PLC
Turn ON the power to each PLC, and transfer the program.

3 Validating the communication setting E


When the PLC is in RUN mode, set it to STOP mode once, and then set it to RUN mode again.

Communication
Inverter
Or turn OFF the power of the master station and all slave stations in communication, and then turn
ON the power of these stations at the same time.

4 Confirming flashing of the communication status indicator lamps (SD and RD)
F
Confirm that the built-in SD and RD lamps of the communication equipment are flashing.

(RS/RS2 Instruction)
Communication
Non-Protocol
If they are off, take proper action while referring to the troubleshooting procedures described later.

5 Confirming the link of the master station


Set the PLC inputs (X000 to X003) to ON or OFF in the master station, and confirm that the outputs G
(Y000 to Y003) turn ON or OFF in each slave station.

(FX2N-232IF)
Communication
Non-Protocol
Set the inputs X000 to
X003 to ON or OFF.
Slave station No. 1 Slave station No. 2

H
Communication
Programming

Master station
Confirm that the inputs in the Confirm that the inputs in the
master station turn ON or OFF master station turn ON or OFF
according to the outputs Y000 according to the outputs Y000 I
to Y003. to Y003.
Maintenance
Remote

Apx.A
models
Discontinued

B-29
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
N:N Network 6.1 Test Procedure

6 Confirming the link of slave stations


Set the PLC inputs (X000 to X003) to ON or OFF in each slave station, and confirm that the outputs
(Y004 to Y007, Y010 to Y013, Y014 to Y017... Y030 to Y033) turn ON or OFF in each slave station.
Set the inputs X000 to Set the inputs X000 to
X003 to ON or OFF. X003 to ON or OFF.
Master station Slave station No. 1 Slave station No. 2

Confirm that the inputs (X000 to


Confirm that the inputs (X000 to
Confirm that the inputs (X000 to

X003) in the slave station No. 1 X003) in the slave station No. 2 X003) in the slave station No. 1
turn ON or OFF according to the turn ON or OFF according to the turn ON or OFF according to the
outputs (Y004 to Y007) outputs (Y010 to Y013) outputs (Y004 to Y007)
respectively. respectively. respectively.
Confirm that the inputs (X000 to

X003) in the slave station No. 2
turn ON or OFF according to the
outputs (Y010 to Y013)
respectively.

If unable to establish link, refer to "Chapter 9. Troubleshooting".

Assignment of inputs and outputs (link devices)


The table below shows devices used in the test programs shown later:

Station No. Input (X) Link device Output (Y)


0 Master station X000 to X003 D0 Y000 to Y003
1 Slave station No. 1 X000 to X003 D10 Y004 to Y007
2 Slave station No. 2 X000 to X003 D20 Y010 to Y013
3 Slave station No. 3 X000 to X003 D30 Y014 to Y017
4 Slave station No. 4 X000 to X003 D40 Y020 to Y023
5 Slave station No. 5 X000 to X003 D50 Y024 to Y027
6 Slave station No. 6 X000 to X003 D60 Y030 to Y033
7 Slave station No. 7 X000 to X003 D70 Y034 to Y037

B-30
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
N:N Network 6.2 Creating Programs for the Communication Testing

A
6.2 Creating Programs for the Communication Testing

Common Items
Create the programs shown below for the master station and each slave station.
(In the communication test, set the refresh range to pattern 0.)

6.2.1 Creating a program for the master station B

N:N Network
Create the program shown below for the communication test. (This program is not required during actual
operation.)
M8038
FNC 12 K0 D8176
0
MOV
C
Set the number of slave stations to D8177.

Parallel Link
FNC 12 K2 D8177
MOV The setting range is from K1 to K7.

FNC 12 K0 D8178
MOV
D

Computer Link
FNC 12 K3 D8179
MOV

FNC 12 K5 D8180
E
MOV

Communication
Inverter
When using ch1, this step is not required.
M8179 When using ch2, program "OUT M8179".
(Only in the FX3G, FX3GC, FX3U and FX3UC)
F
M8000 Step for writing information from the master station (master

(RS/RS2 Instruction)
Communication
Non-Protocol
FNC 12 K1X000 D0 station slave station)
28
MOV The contents of X000 to X003 in the master station are
transferred to outputs (Y) in this slave station.

M8000 Steps for reading information from a slave station (slave


34 FNC 12 D10 K1Y004 station master station)
MOV By using link devices, read information from all slave G
stations.

(FX2N-232IF)
Communication
Non-Protocol
The table below shows the link devices to be used:
FNC 12 D20 K1Y010 Slave station No. Link device Output (Y)
MOV 1 D10 Y004 to Y007
2 D20 Y010 to Y013
3
4
D30
D40
Y014 to Y017
Y020 to Y023
H
Communication
Programming

5 D50 Y024 to Y027


FNC 12 D70 K1Y034 6 D60 Y030 to Y033
MOV 7 D70 Y034 to Y037

Specify device numbers for the


connected slave stations. I
Maintenance
Remote

END

Caution

1) When using a PLC (such as an FX1S and FX3S Series PLC) with a small number of outputs, transfer
information from slave stations to auxiliary relays (M), etc., and then monitor the auxiliary relays using a Apx.A
programming tool. (Example: Change "K1Y004" to "K1M4".)
models
Discontinued

2) In the circuit from step 34, create a program for link devices (MOV instruction) for all connected slave
stations.

B-31
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
N:N Network 6.2 Creating Programs for the Communication Testing

6.2.2 Creating a program for each slave station


Create the program shown below for the communication test. (This program is not required during actual
operation.)
Determine the station number of each slave station, and then transfer a program corresponding to the station
number to each slave station.
Assign station numbers from "1" in the ascending order. (Use one station number only once. Do not skip
station numbers.)

M8038
FNC 12 Set the slave station number to D8176.
0 K1 D8176
MOV The setting range is from K1 to K7.

When using ch1, this step is not required.


M8179 When using ch2, program "OUT M8179".
(Only in the FX3G, FX3GC, FX3U and FX3UC)

Step for writing information from a slave station (slave


M8000 station master station)
FNC 12 K1X000 D10 Transfer the contents of X000 to X003 in this slave station
8
MOV to a link device. The link device varies depending on the
station number.
The table below shows the link devices to be used:
Specify the link device
number for this slave Slave station No. Link device Output (Y)
station. 1 D10 Y004 to Y007
2 D20 Y010 to Y013
3 D30 Y014 to Y017
4 D40 Y020 to Y023
5 D50 Y024 to Y027
6 D60 Y030 to Y033
7 D70 Y034 to Y037

M8000 Step for reading information from the master station (master
FNC 12 station slave station)
14 D0 K1Y000 The contents of X000 to X003 in the master station are
MOV
transferred to outputs (Y) in this slave station.

Steps for reading information from another slave station


FNC 12 D20 K1Y010 (another slave stations this slave station)
MOV By using link devices, read information from all other slave
stations.
The table below shows the link devices to be used:
FNC 12 D30 K1Y014 Slave station No. Link device Output (Y)
MOV 1 D10 Y004 to Y007
2 D20 Y010 to Y013
3 D30 Y014 to Y017
4 D40 Y020 to Y023
5 D50 Y024 to Y027
FNC 12 D70 K1Y034 6 D60 Y030 to Y033
MOV 7 D70 Y034 to Y037

Specify link device numbers for


other slave stations. (Do not specify
the device number (D10) for this
slave station.)
END

Caution

1) When using a PLC (such as an FX1S and FX3S Series PLC) with a small number of outputs, transfer
information from slave stations to auxiliary relays (M), etc., and then monitor the auxiliary relays using a
programming tool. (Example: Change "K1Y004" to "K1M4".)
2) In the circuit from step 14, specify link devices for other slave stations.

B-32
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.1 Checking Contents of Related Devices

Common Items
7. Creating Programs
This chapter explains how to set the N:N Network and how to create programs. B
In N:N Network, pattern 0, 1 or 2 can be set according to the refresh range value. The number of used

N:N Network
devices varies depending on the pattern.
In N:N Network using (including) the FX0N or FX1S Series, only pattern 0 is applicable.

7.1 Checking Contents of Related Devices


C

Parallel Link
The tables below show the devices used by the N:N Network.

1. Devices for setting the N:N Network


These devices are used for setting the N:N Network. Setting these devices is essential for using N:N Network.

Device Name Description Set value D


This device is a flag for setting communication parameters, and is used to

Computer Link
Parameter
M8038 check for absence/presence of N:N Network program also.
setting
Do not set this device to ON in the sequence program.
Set the channel of the communication port to be used (in the FX3G, FX3GC,
FX3U and FX3UC).
M8179 Channel setting
When "OUT M8179" program does not exist: ch 1
When "OUT M8179" program exists: ch 2
E

Communication
Inverter
Set the station number used in the N:N Network.
Station number
D8176 Master station: 0, slave station: 1 to 7 0 to 7
settings
[Initial value: 0]
Set the total number of slave stations.
Slave station
D8177
quantity setting
This setting is not required in PLCs working as slave stations.
[Initial value: 7]
1 to 7
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Select the desired pattern of device points used for communication.
Refresh range This setting is not required in PLCs working as slave stations.
D8178 0 to 2
setting [Initial value: 0]
Only pattern 0 is applicable when a FX0N or FX1S Series is included.
When a response is not given even after communication is repeated the
Number of
specified number of times, it is regarded as an error. G
D8179 Errors in other stations can be checked. 0 to 10

(FX2N-232IF)
Communication
Non-Protocol
retries
This setting is not required in PLCs working as slave stations.
[Initial value: 3]
Set the time (50 to 2550 ms) for communication error in 10 ms units.
D8180 Monitoring time This setting is not required in PLCs working as slave stations. 5 to 255
[Initial value: 5] H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-33
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.1 Checking Contents of Related Devices

2. Devices for determining errors in the N:N Network


These devices are used for determining errors in the N:N Network. Use them to output link errors to the
outside and interlock sequence programs.
Different devices are used between the FX0N/FX1S Series and the FX1N/FX1NC/FX2N/FX2NC/FX3S/FX3G/
FX3GC/FX3U/FX3UC Series. Use devices according to the PLCs used.

Device
FX1N, FX1NC, FX2N, FX2NC, Name Description
FX0N,
FX3S, FX3G, FX3GC,
FX1S
FX3U, FX3UC
Master station data
This device turns ON when a data transfer
M504 M8183 transfer sequence
sequence error occurs in the master station.
error
Slave station data
This device turns ON when a data transfer
M505 to M511*1 M8184 to M8190*2 transfer sequence
sequence error occurs in a slave station.
error
Data transfer This device remains ON while the N:N
M503 M8191
sequence ON Network is operating.

*1. Station No. 1: M505, Station No. 2: M506, Station No. 3: M507... Station No. 7: M511
*2. Station No. 1: M8184, Station No. 2: M8185, Station No. 3: M8186... Station No. 7: M8190

3. Link devices
These devices are used for sending and receiving information among the PLCs. The device numbers used
and number of devices vary depending on the station number set in D8176 (station number settings) and the
pattern set in D8178 (refresh range setting).
1) In the case of pattern 0

0 (master
Station No. 1 2 3 4 5 6 7
station)
Word device
D10 to D20 to D30 to D40 to D50 to D60 to D70 to
(4 points for D0 to D3
D13 D23 D33 D43 D53 D63 D73
each station)

2) In the case of pattern 1

0 (master
Station No. 1 2 3 4 5 6 7
station)
Bit devices
M1000 to M1064 to M1128 to M1192 to M1256 to M1320 to M1384 to M1448 to
(32 points for
M1031 M1095 M1159 M1223 M1287 M1351 M1415 M1479
each station)
Word device
D10 to D20 to D30 to D40 to D50 to D60 to D70 to
(4 points for D0 to D3
D13 D23 D33 D43 D53 D63 D73
each station)

3) In the case of pattern 2

0 (master
Station No. 1 2 3 4 5 6 7
station)
Bit devices
M1000 to M1064 to M1128 to M1192 to M1256 to M1320 to M1384 to M1448 to
(64 points for
M1063 M1127 M1191 M1255 M1319 M1383 M1447 M1511
each station)
Word device
D10 to D20 to D30 to D40 to D50 to D60 to D70 to
(8 points for D0 to D7
D17 D27 D37 D47 D57 D67 D77
each station)

Caution
When creating a program, do not change the information in devices used by other stations. If such
information is changed, other stations will not operate normally.

B-34
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.2 Creating Programs for Master Station (Station No. 0)

A
7.2 Creating Programs for Master Station (Station No. 0)

Common Items
Create programs for the master station.
Arbitrarily create programs for reading and writing link devices.
Program for setting the N:N Network
Make sure to start the program for setting the N:N Network
B
Parameter setting from step 0.

N:N Network
M8038
FNC 12 K0 D8176 Station number setting: 0 (master station)
0 MOV Station number "0" indicates the master station.

Slave station quantity setting: 2 (2 slave stations)


C
FNC 12 K2 D8177 Set the number of connected slave stations.

Parallel Link
MOV [Setting range: 1 to 7]

Refresh range setting: 1 (pattern 1)


FNC 12
MOV
K1 D8178 Set the pattern of devices used in communication.
[Setting range: 0 to 2] D
(Only pattern 0 is applicable in the FX0N or FX1S

Computer Link
Series.)

Number of retries: 3 (3 times)


FNC 12 K3 D8179 Set the number of retrying communication after a link
MOV error is detected.
[Setting range: 0 to 10]
E

Communication
Inverter
Monitoring time: 5 (50 ms)
FNC 12 K5 D8180 Set the time by which communication error is determined.
MOV [Setting range: 5 to 255]

Channel Set the communication port to be used.


setting When using ch1, this step is not required. F
M8179 When using ch2, program "OUT M8179".

(RS/RS2 Instruction)
Communication
Non-Protocol
(in the FX3G, FX3GC, FX3U and FX3UC)

Cautions on setting up the N:N Network


Note the following cautions when creating a program using Structured Ladder, FBD or ST programming in the G
FX1S, FX1N, FX1NC, FX2N or FX2NC PLC.

(FX2N-232IF)
Communication
Non-Protocol
When setting up the N:N Network in a program using Structured Ladder or FBD programming, connect the
ENO output to the EN input for the MOV instruction.
<Program example>
Parameter setting
M8038 MOV MOV MOV MOV
H
Communication
Programming

EN ENO EN ENO EN ENO EN ENO


K0 s d D8176 K2 s d D8177 K1 s d D8178 K3 s d D8179

MOV
EN
s
ENO
d
I
K5 D8180
Maintenance
Remote

When setting up the N:N Network in a program using ST programming, use the MOV instruction as shown
in the following program example.
<Program example>
MOV(MOV(MOV(MOV(MOV(M8038, K0, D8176), K2, D8177), K1, D8178), K3, D8179), K5, D8180); Apx.A
models
Discontinued

B-35
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.2 Creating Programs for Master Station (Station No. 0)

Station No. 1 Program for indicating link errors


Data transfer sequence error
This program is required to indicate the N:N Network status.
M8184
Y000 When a link error occurs in the station No. 1, Y000 is
Station No. 2 set to ON.
Data transfer sequence error
M8185
Y001 When a link error occurs in the station No. 2, Y001 is set
to ON.
Create this step for each connected slave station.
Note that the devices to be used are different
depending on the PLC Series.
For FX0N and FX1S Series:
M505 to M511 (station No. 1 to station No. 7)
For any series other than FX0N and FX1S Series:
M8184 to M8190 (station No. 1 to station No. 7)
Data transfer sequence ON
M8191
Y010 While the N:N Network is executed, Y010 remains ON.
Note that the devices to be used are different
depending on the PLC Series.
For FX0N and FX1S Series: M503
For any series other than FX0N and FX1S Series: M8191

Program for writing link devices


(master station slave station)
This program is required to write information from the
X000 master station to each slave station.
M1000 The information from X000 is written to M1000 (link device).

X002
M1001 The information from X002 is written to M1001 (link device).

M10
M1002 The information from M10 is written to M1002 (link device).

M8000
FNC 12 The information from M100 to M115 is written to M1010 to
K4M100 K4M1010 M1025 (link devices).
MOV

The information from D100 is written to D0 (link device).


FNC 12 D100 D0 * In pattern 0, bit devices are not applicable.
MOV Use word devices only.

Program for reading link devices


(master station slave station)
Station No. 1
Data transfer This program is required to read information from each
sequence error slave station to the master station.
M8184 M1064 Monitor link errors in each slave station, and read them.
M0 The information from M1064 (link device) is read to M0.

M1065
Y011 The information from M1065 (link device) is read to Y011.

M1066
M15 The information from M1066 (link device) is read to M15.

FNC 12 K4M1070 K4Y020 The information from M1070 to M1085 (link devices) is
MOV read to Y020 to Y037.

FNC 12 D10 D110 The information from D10 (link device) is read to D110.
MOV

B-36
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.2 Creating Programs for Master Station (Station No. 0)

Common Items
Station No. 2
Data transfer
sequence error
M8185 M1128
M1 The information from M1128 (link device) is read to M1.
B
M1129

N:N Network
Y012 The information from M1129 (link device) is read to Y012.

M1130
M18 The information from M1130 (link device) is read to M18.
C
FNC 12 The information from M1140 to M1155 (link devices) is

Parallel Link
K4M1140 K4M20 read to M20 to M35.
MOV

FNC 12 D20 D200 The information from D20 (link device) is read to D200.
MOV

For details on link devices, refer to Section 7.1. D


For cautions on program creation, refer to Section 7.4.

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-37
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.3 Creating Programs for Slave Station (Station No. "n")

7.3 Creating Programs for Slave Station (Station No. "n")


Create programs for the slave stations.
Arbitrarily create programs for reading and writing link devices.
Program for setting the N:N Network
Make sure to start the program for setting the N:N Network
Parameter setting from step 0.
M8038
FNC 12 K1 D8176 Station number setting: 1 (slave station)
0 MOV Set the station number of each slave station.
Only set the station number for the slave station;
Other settings are not required.

Channel Set the communication port to be used (in the FX3G, FX3GC,
setting FX3U and FX3UC).
M8179 When using ch1, this step is not required.
When using ch2, program "OUT M8179".

Program for indicating link errors


Station No. 0 This program is required to indicate the N:N Network status.
Data transfer sequence error
M8183
Y000 When a link error occurs in station No. 0, Y000 is set to ON.
Station No. 2
Data transfer sequence error
M8185
Y001 When a link error occurs in station No. 2, Y001 is set to ON.
Create this step for each connected slave station.
Note that the devices to be used are different depending
on the PLC Series.
For FX0N and FX1S Series:
M504 to M511 (station No. 0 to station No. 7)
For any series other than FX 0N and FX1S Series:
M8183 to M8190 (station No. 0 to station No. 7)

Data transfer sequence ON


M8191
Y010 While the N:N Network is executed, Y010 remains ON.
Note that the devices to be used are different
depending on the PLC Series.
For FX0N and FX1S Series: M503
For any series other than FX 0N and FX1S Series: M8191

Program for writing link devices


(slave station master or slave station)
This program is required to write information from a slave
station to the master station or another slave station.
X000
M1064 The information from X000 is written to M1064 (link device).

X002
M1065 The information from X002 is written to M1065 (link device).

M10
M1066 The information from M10 is written to M1066 (link device).

M8000
FNC 12 K4M100 K4M1070 The information from M100 to M115 is written to M1070 to
MOV M1085 (link devices).

FNC 12 D100 D10 The information from D100 is written to D10 (link device).
MOV
* In pattern 0, bit devices are not available.
Use word devices only.

B-38
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.3 Creating Programs for Slave Station (Station No. "n")

Common Items
Program for reading link devices
(slave station master or slave station)
This program is required to read information from the
master station or another slave station to a slave station.
Station No. 0
Data transfer Monitor link errors in each slave station, and read them. B
sequence error

N:N Network
M8183 M1000
M0 The information from M1000 (link device) is read to M0.

M1001
Y011 The information from M1001 (link device) is read to Y011. C

Parallel Link
M1002
M15 The information from M1002 (link device) is read to M15.

FNC 12
MOV
K4M1010 K4Y020
The information from M1010 to M1025 (link devices) is
read to Y020 to Y037. D

Computer Link
FNC 12 D0 D110 The information from D0 (link device) is read to D110.
MOV

Station No. 2
Data transfer
sequence error
E

Communication
Inverter
M8185 M1128
M1 The information from D1128 (link device) is read to M1.

M1129
Y012 The information from D1129 (link device) is read to Y012.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
M1130
M18 The information from D1130 (link device) is read to M18.

FNC 12
MOV
K4M1140 K4M20 The information from M1140 to M1155 (link devices) is
read to M20 to M35. G

(FX2N-232IF)
Communication
Non-Protocol
FNC 12 D20 D200 The information from D20 (link device) is read to D200.
MOV

For details on link devices, refer to Section 7.1.


For cautions on program creation, refer to Section 7.4.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-39
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
N:N Network 7.4 Cautions on Program Creation

7.4 Cautions on Program Creation

1. Effect on the operation cycle


When the N:N Network is used, the operation cycle in each PLC becomes longer by about 10% regardless of
the number of linked stations and adopted communication patterns.

2. Program for setting the N:N Network


1) Make sure to create a program for setting the N:N Network from step 0 using M8038 (drive contact).
Otherwise, the N:N Network is disabled.
2) Do not set M8038 to ON using a program or programming tool.
3) Set station numbers consecutively. If a station number that is used twice or more is skipped, link will not
be achieved normally.
4) Pay close attention when setting up the N:N Network for the master station in a program using Structured
Ladder, FBD or ST programming in the FX1S, FX1N, FX1NC, FX2N or FX2NC PLC.
For details, refer to Section 7.2.

3. Program for reading link devices


Do not change the contents of link devices at other stations.
1) When a link error (data transfer sequence error) occurs, the link device information is held in the status
just before occurrence of the link error.
Create a fail-safe program which does not cause abnormality even if a link error occurs.

4. Cautions on using FX0N/FX1S PLCs


1) Link pattern when FX0N/FX1S PLCs are used or included
When FX0N/FX1S PLCs are included in the system, make sure to set pattern 0 in D8178 (refresh range
setting).
If any other pattern is set, data transfer error occurs in all FX0N/FX1S PLCs included in the system, and
the link time becomes longer.
2) When user devices are occupied as system devices
In FX0N/FX1S PLCs, M503 to M511 and D201 to D255 are handled as devices dedicated to the N:N
Network, and cannot be handled as general devices any more. Do not set these devices to ON or OFF
using a user program, display unit or programming tool.
If these devices are set to ON or OFF, the N:N Network may malfunction.

5. Cautions on using FX3G/FX3GC/FX3U/FX3UC PLCs


1) Only ch 1 or ch 2 can be set in the N:N Network.
2) Do not use the N:N Network and parallel link at the same time.
(For example, it is not allowed to use ch1 for the N:N Network and use ch2 for parallel link.)

6. Link device update timing


Link device update in N:N network is executed in the interrupt processing.
Because the interrupt processing is generated asynchronously from operations of the sequence program, it
may be performed during ladder operation.

B-40
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

Common Items
8. Practical Program Examples
This chapter shows practical programs. B

N:N Network
8.1 Practical Example 1 (Pattern 2)
This program example adopts pattern 2 which uses the maximum number of link devices.
When an FX0N or FX1S PLC is included, however, only pattern 0 is applicable.
C

Parallel Link
8.1.1 System configuration example
The example below shows a system configuration in which three FX PLCs are linked.
FX2N PLC FX2N PLC FX2N PLC
D

Computer Link
FX2N-485-BD FX2N-485-BD FX2N-485-BD

Communication
Inverter
Station No. 0 (master station) Station No. 1 (slave station) Station No. 2 (slave station)
- Refresh range: 64-bit devices and 8 word devices (pattern 2)
- Number of retries: 5
- Monitoring time: 70 ms
F

(RS/RS2 Instruction)
Communication
Non-Protocol
8.1.2 Contents of operations and corresponding program numbers
The program examples shown later execute the data processing shown in the table below.
The operation No. corresponds to the operation [1] (for example) indicated in the programs shown later.
Operation
No.
Data source Data change destination and contents G

(FX2N-232IF)
Communication
Non-Protocol
Bit device link
Inputs X000 to X003 Slave station No. 1 Outputs Y010 to Y013
[1] Master station
(M1000 to M1003) Slave station No. 2 Outputs Y010 to Y013
Inputs X000 to X003 Master station Outputs Y014 to Y017
[2] Slave station No. 1
(M1064 to M1067) Slave station No. 2 Outputs Y014 to Y017 H
Inputs X000 to X003 Master station Outputs Y020 to Y023
Communication
Programming

[3] Slave station No. 2


(M1128 to M1131) Slave station No. 1 Outputs Y020 to Y023
Word device link
Master station Data register D1 Slave station No. 1 Set value of counter C1
[4]
Slave station No. 1 Contact of counter C1 (M1070) Master station Output Y005
I
Master station Data register D2 Slave station No. 2 Set value of counter C2
Maintenance
Remote

[5]
Slave station No. 2 Contact of counter C2 (M1140) Master station Output Y006
Slave station No. 1 Data register D10 Slave station No. 1 (D10) + Slave
[6] Master station
Slave station No. 2 Data register D20 station No. 2 (D20) is stored to D3.
Master station Data register D0 Master station (D0) + Slave station
[7]
Slave station No. 2 Data register D20
Slave station No. 1
No. 2 (D20) is stored to D11. Apx.A
models
Discontinued

Master station Data register D0 Master station (D0) + Slave station


[8] Slave station No. 2
Slave station No. 1 Data register D10 No. 1 (D10) is stored to D21.

B-41
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

8.1.3 Setting contents


The program examples shown later adopt the following communication parameters:

System device Master station Station No. 1 Station No. 2 Contents


D8176 K0 K1 K2 Station number settings
D8177 K2 Total number of slave stations: 2
D8178 K2 Refresh range: Pattern 2
D8179 K5 Number of retries: 5
D8180 K7 Monitoring time: 70 ms

8.1.4 Setting program for master station


For the master station setting program, refer to the program shown below.
The program shown below consists of three blocks, "parameter setting program", "error indication program"
and "operation program".

1. Parameter setting program

Make sure to start from step 0.

Parameter setting
M8038
FNC 12 K 0 D8176 Station number settings: 0 (master station)
0
MOV

FNC 12 K 2 D8177 Slave station quantity setting: 2 (2 slave stations)


MOV

FNC 12 K 2 D8178 Refresh range setting: 2 (pattern 2)


MOV

FNC 12 K 5 D8179 Number of retries setting: 5 (5 times)


MOV

FNC 12 K 7 D8180 Monitoring time setting: 7 (70 ms)


MOV

Caution
Pay close attention when setting up the N:N Network for the master station in a program using Structured
Ladder, FBD or ST programming in the FX1S, FX1N, FX1NC, FX2N or FX2NC PLC.
For details, refer to Section 7.2.

2. Error indication program


Because the master station does not recognize errors within itself (the master station), programs for errors
within itself are not required.

Data transfer sequence error in slave station No. 1


M8184
Y001
Data transfer sequence error in slave station No. 2
M8185
Y002
Data transfer sequence ON
M8191
Y003

B-42
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

A
3. Operation program

Common Items
RUN monitor
M8000
MOV K1X000 K1M1000 Operation [1]
Data transfer sequence error
in slave station No. 1 B
M8184

N:N Network
MOV K1M1064 K1Y014 Operation [2]

Data transfer sequence error


in slave station No. 2
M8185
MOV K1M1128 K1Y020 Operation [3] C

Parallel Link
Data transfer sequence error
in slave station No. 1
M8184
MOV K 10 D 1

Operation [4] D
C1 contact of slave station No. 1

Computer Link
M1070
Y005

Data transfer sequence error


in slave station No. 2
M8185
MOV K 10 D 2
E

Communication
Inverter
Operation [5]
C2 contact of slave station No. 2
M1140
Y006
Data transfer
sequence
Data transfer
sequence error F
error in slave in slave station

(RS/RS2 Instruction)
Communication
Non-Protocol
station No. 1 No. 2
M8184 M8185
ADD D 10 D 20 D 3 Operation [6]

MOV K 10 D 0
Operation [7]
Operation [8]
G

(FX2N-232IF)
Communication
END Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-43
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

8.1.5 Setting program for slave station (No. 1)


For the slave station setting program, refer to the program shown below.
The program shown below consists of three blocks, "parameter setting program", "error indication program"
and "operation program".

1. Parameter setting program


Make sure to start from step 0.

Parameter setting
M8038
FNC 12 K 1 D8176 Station number settings: 1 (slave station No. 1)
0
MOV

2. Error indication program


Because slave station No. 1 does not recognize errors within itself (slave station No. 1), programs for errors
within itself are not required.

Data transfer sequence error in master station


M8183
Y000

Data transfer sequence error in slave station No. 2


M8185
Y002
Data transfer sequence ON
M8191
Y003

B-44
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

A
3. Operation program

Common Items
Counter reset
X001
RST C 1

Master station
B

N:N Network
Data transfer sequence error
M8183
MOV K1M1000 K1Y010 Operation [1]

MOV K1X000 K1M1064 Operation [2] C

Parallel Link
Data transfer
sequence error in
slave station No. 2
M8185
MOV K1M1128 K1Y020 Operation [3]

Counter input
X000
D

Computer Link
C1
D1

C1 Operation [4]
Y005

E
M1070

Communication
Inverter
Data transfer
sequence
error in slave Slave station No. 2
station No. 2 C2 contact
M8185 M1140
Y006 Operation [5]
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Operation [6]
MOV K 10 D 10 Operation [8]
Data transfer
sequence
error in slave
station No. 2
M8185
ADD D 0 D 20 D 11 Operation [7] G

(FX2N-232IF)
Communication
END Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-45
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

8.1.6 Setting program for slave station (No. 2)


For the slave station setting program, refer to the program shown below.
The program shown below consists of three blocks, "parameter setting program", "error indication program"
and "operation program".

1. Parameter setting program


Make sure to start from step 0.

Parameter setting
M8038
FNC 12 K 2 D8176 Station number settings: 2 (slave station No. 2)
0
MOV

2. Error indication program


Because slave station No. 2 does not recognize errors within itself (slave station No. 2), programs for errors
within itself are not required.

Data transfer sequence error in master station


M8183
Y000

Data transfer sequence error in slave station No. 1


M8184
Y002
Data transfer sequence ON
M8191
Y003

B-46
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
N:N Network 8.1 Practical Example 1 (Pattern 2)

A
3. Operation program

Common Items
Counter reset
X001
RST C 2
B
Master station

N:N Network
Data transfer sequence error
M8183
MOV K1M1000 K1Y010 Operation [1]

Data transfer
sequence error in
slave station No. 1
M8184
C
MOV K1M1064 K1Y014 Operation [2]

Parallel Link
MOV K1X000 K1M1128 Operation [3]
Data transfer
sequence
error in slave Slave Station No. 1 D
station No. 1 C1 contact

Computer Link
M8184 M1070
Y005 Operation [4]

Counter input
X000
C2
E

Communication
Inverter
D2

C2
Y006 Operation [5]

F
M1140

(RS/RS2 Instruction)
Communication
Non-Protocol
Operation [6]
MOV K 10 D 20 Operation [7]
Data transfer
sequence
error in slave G
station No. 1

(FX2N-232IF)
Communication
Non-Protocol
M8184
ADD D 0 D 10 D 21 Operation [8]

END
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-47
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
N:N Network 9.1 Checking FX PLC Version Applicability

9. Troubleshooting
This chapter explains troubleshooting.

9.1 Checking FX PLC Version Applicability


Verify that the FX Series PLC main unit is an applicable version.
For the version applicability check, refer to Section 1.3.

9.2 Checking Communication Status Based on LED Indication


Check the status of the "RD" and "SD" indicator LEDs provided in the optional equipment.

LED status
Operation status
RD SD
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received.
Off Off Data is not sent nor received.
While the N:N Network is executed normally, both LEDs flash brightly.
If they do not flash, check the wiring and the communication setting in the master and slave stations.

9.3 Checking Installation and Wiring

1. Mounting status
If the communication equipment is not securely connected to the PLC, communication is not possible.
For mounting method, refer to the respective communication equipment manual.

2. Power supply (For FX0N-485ADP)


The FX0N-485ADP requires a driving power supply. Verify that the power supply is correctly provided.

3. Wiring
Verify that the wiring to all communication equipment is correct. If the communication equipment is wired
incorrectly, communication is not possible.
For wiring method check, refer to Chapter 4.

9.4 Checking Sequence Program

1. Communication setting in the sequence program


Verify that the parallel link is not set. Using both the parallel link and the N:N Network at the same time is not
allowed.
Verify that the communication format (D8120, D8400 and D8420) is set correctly. Communication is not
possible if a communication port is set twice or more.
After changing any setting, make sure to reboot the PLC's power.
For communication setting, refer to Chapter 5.

2. Communication setting using parameters


Verify that the communication settings using parameters are suitable for use. Do not set parameters for the
N:N Network. If the communication settings are not suitable for use, communication will not function correctly.
After changing the setting, make sure to reboot the PLCs power.
For the communication setting, refer to Chapter 5.

B-48
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
N:N Network 9.4 Checking Sequence Program

A
3. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)

Common Items
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in N:N network.
After changing the setting, make sure to reboot the PLC's power.

4. N:N network and MODBUS communication (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
If N:N network and MODBUS communication are set in a same channel, N:N network is executed, but
MODBUS communication is ignored.
B

N:N Network
In this case, the error "Communication port is occupied in another communication, (Error code 203)" is stored
in D8402/D8422 for the corresponding channel in the PLC.
For details of MODBUS communication errors and error devices, refer to the FX3S/FX3G/FX3GC/
FX3U/FX3UC Series User's Manual - MODBUS Serial Communication Edition.

5. Presence of VRRD and VRSC instructions C


1) Except FX3G, FX3U and FX3UC PLCs

Parallel Link
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, reboot the PLCs power.
2) In FX3G PLC
- In the case of the 14 points and 24-point type
Verify that the VRRD and VRSC instructions are not used in the program. D
If these instructions are used, delete them, reboot the PLC's power.

Computer Link
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions.
After deleting these instructions, reboot the PLC's power. E
3) In FX3U and FX3UC PLCs

Communication
Inverter
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power.

6. Presence of RS instruction (except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Verify that the RS instruction is not used in the program.
If this instruction is used, delete it, reboot the PLC's power.

7. Presence of RS and RS2 instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power. G

(FX2N-232IF)
Communication
Non-Protocol
8. Presence of EXTR instruction (in FX2N and FX2NC PLCs)
Verify that the EXTR instruction is not used in the program.
If this instruction is used, delete it, then reboot the PLCs power.

9. Presence of IVCK, IVDR, IVRD, IVWR, IVBWR*1, and IVMC instructions (in FX3S, FX3G,
FX3GC, FX3U and FX3UC PLCs)
H
Communication
Programming

Verify that the IVCK, IVDR, IVRD, IVWR, IVBWR and IVMC instructions are not being used for the same
channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.
*1. Only available for FX3U and FX3UC PLCs.

10.Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs) I
Maintenance
Remote

Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.

11.Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and
FX3UC PLCs)
Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the Apx.A
same channel.
models
Discontinued

If these instructions are used for the same channel, delete them, reboot the PLCs power.

B-49
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
N:N Network 9.5 Checking Setting Contents and Errors

9.5 Checking Setting Contents and Errors

1. Checking the setting contents


Verify that the N:N Network is set correctly.
Each FX PLC has devices for checking the setting. Verify that the correct contents are stored in the devices
shown in the table below.
Device Name Description
D8173 Station number settings status Provided to check the station number.
D8174 Slave station quantity setting status Provided to check the number of slave stations.
D8175 Refresh range setting status Provided to check the refresh range.
If the correct contents are not stored in the devices above, check the sequence program.

2. Checking setting errors


1) Error flags
If the parameter setting includes an error, the serial communication error flag turns ON.
Verify that the devices shown in the table below are ON.
Device Name Description
Turns ON when abnormality occurs during serial communication
M8063 Serial communication error 1 (ch 1)
using ch 1.
Turns ON when abnormality occurs during serial communication
M8438 Serial communication error 2 (ch 2)
using ch 2.

When using the N:N Network on ch 1, check M8063.


When using the N:N Network on ch 2, check M8438.
2) Error codes
When the serial communication error flag turns ON, the error code is stored in the device specified in the
table below.
Device Name Error code Description
6308 N:N Network parameter setting error
D8063 Serial communication error code 1 (ch 1)
6309 N:N Network setting error
3808 N:N Network parameter setting error
D8438 Serial communication error code 2 (ch 2)
3809 N:N Network setting error

Caution
The serial communication error flags and serial communication error codes are not cleared even when
communication is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

9.6 Checking Absence/Presence of Data Transfer Errors


Verify that link errors have not occurred in the master station and slave stations. Link errors can be checked
using the flags specified below.

9.6.1 Check while data transfer sequence is being executed


While the N:N Network is being executed, the data transfer sequence ON flag remains ON.
Verify that the device specified in the table below is ON.
FX Series Device Name Description
FX1N, FX1NC, FX2N,
FX2NC, FX3S, FX3G, M8191 Remains ON while data transfer is being
FX3GC, FX3U, FX3UC Data transfer sequence ON flag
executed.
FX0N, FX1S M503

B-50
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
N:N Network 9.6 Checking Absence/Presence of Data Transfer Errors

A
9.6.2 Checking data transfer sequence errors

Common Items
When a link error occurs in the master station or slave station, the data transfer sequence error flag turns ON.
The data transfer sequence error flag varies depending on the FX Series and station number. Refer to the
table below.

Master
Slave Slave Slave Slave Slave Slave Slave B
FX Series station station station station station station station
station

N:N Network
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7
FX1N, FX1NC, FX2N,
FX2NC, FX3S, FX3G, M8183 M8184 M8185 M8186 M8187 M8188 M8189 M8190
FX3GC, FX3U, FX3UC
FX0N, FX1S M504 M505 M506 M507 M508 M509 M510 M511 C

Parallel Link
9.6.3 Checking error codes
When a data transfer sequence error occurs, the corresponding data transfer sequence error flag turns ON,
and the error code is stored in the corresponding data register.
For error codes, refer to the next page. D

Computer Link
1. Error storing device
The data register used to store the data transfer error code varies depending on the FX Series and station
number. Refer to the table below.

Slave Slave Slave Slave Slave Slave Slave


FX Series
Master
station
station station station station station station station E
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7

Communication
Inverter
FX1N, FX1NC, FX2N,
FX2NC, FX3S, FX3G, D8211 D8212 D8213 D8214 D8215 D8216 D8217 D8218
FX3GC, FX3U, FX3UC
FX0N, FX1S D211 D212 D213 D214 D215 D216 D217 D218
F
2. Error code list

(RS/RS2 Instruction)
Communication
Non-Protocol
The data register for storing the data transfer error code stores the corresponding error code. When a data
transfer sequence error occurs, refer to the error code list shown below, and confirm the check points.

Station Station
Error in which which
code
Error name
error detected
Contents of error Check point G
occurred error

(FX2N-232IF)
Communication
Non-Protocol
Slave station did not respond to the
Wiring and power
01H Monitoring timeout L M sending request from the master station
supply
within the monitoring time.
An unexpected slave station responded
02H
Station number
error
L M to the sending request by the master
Station number
settings
H
station.
Communication
Programming

The counter value included in the


03H Counter error L M parameter data is different from the Wiring
counter value given by a slave station.
Wiring, power
Message format The message given by the slave station
04H
error
L M, L
is incorrect.
supply and station
number settings
I
Maintenance
Remote

The master station did not give a sending


Wiring and power
11H Monitoring timeout M L request to the next slave station within
supply
the monitoring timer.
Wiring, power
Message format The message from the master station is
14H M L supply and station
error incorrect.
number settings
Apx.A
models
Discontinued

Wiring, power
Slave station no
21H
response error
L L*1 The specified slave station does not exist. supply and station
number settings

B-51
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
N:N Network 9.6 Checking Absence/Presence of Data Transfer Errors

Station Station
Error in which which
Error name Contents of error Check point
code error detected
occurred error
An unexpected slave station responded
Station number Station number
22H
error
L L*1 to the sending request by the master
settings
station.
The counter value included in the
23H Counter error L L*1 parameter data is different from the Wiring
counter value given by a slave station.
Before parameters had been received,
Parameter not Wiring and power
31H
received
L L*2 sending request was received from the
supply
master station.
M: Master station, L: Slave station
*1. Any slave station other than the slave station in which error occurred
*2. Station in which error occurred

B-52
Common Items N:N Network Parallel Link Computer Link Inverter Non-Protocol Non-Protocol Programming Remote Discontinued

Apx.A
E

I
A

H
F

Communication Communication Communication Communication Maintenance models


(RS/RS2 Instruction) (FX2N-232IF)
9 Troubleshooting
9.6 Checking Absence/Presence of Data Transfer Errors

B-53
MEMO
FX Series PLC User's Manual - Data Communication Edition
N:N Network
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.1 Related Device List

10. Related Data

10.1 Related Device List

10.1.1 For FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs

1. Bit devices

Device Initial Detec-


Name Description R/W
number value tion
Devices for communication setting
M8038 Parameter setting Communication parameter setting flag M, L R
Sets the communication port channel to be used
M8179 Channel setting M, L R/W
(in the FX3G, FX3GC, FX3U and FX3UC).
Devices for checking communication status

Serial communication Turns ON when abnormality occurs in serial


M8063 M, L R
error 1 (ch 1) communication using ch 1.

Turns ON when abnormality occurs in serial


Serial communication
M8438 communication using ch 2 (in the FX3G, FX3GC, M, L R
error 2 (ch 2)
FX3U and FX3UC).
Data transfer Turns ON when a data transfer sequence error
M8183 L R
sequence error occurs in the master station.
Turns ON when a data transfer sequence error
M8184 Data transfer occurs in a slave station.
M, L R
to M8190 sequence error However, data transfer sequence errors within
the slave station itself cannot be detected.
Data transfer Remains ON while data transfer is being
M8191 M, L R
sequence ON executed.
R : Read only (used as a contact in program)
R/W : Read or Write
M : Master station (station No. 0)
L : Slave station (station No. 1 to 7)

B-54
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.1 Related Device List

Common Items
B

N:N Network
C

Parallel Link
Master Slave station Slave station Slave station Slave station Slave station Slave station Slave station
station No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7

Computer Link

E

Communication
Inverter

F
M8184 M8185 M8186 M8187 M8188 M8189 M8190

(RS/RS2 Instruction)
Communication
Non-Protocol

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-55
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.1 Related Device List

2. Word devices (data registers)

Device Initial Detec-


Name Description R/W
number value tion
Devices for checking
Corresponding station
D8173 Provided to check the station number. M, L R
number settings status
Slave station quantity
D8174 Provided to check the number of slave stations. M, L R
setting status
Refresh range setting
D8175 Provided to check the refresh range. M, L R
status
Serial communication Stores the serial communication error code for
D8063 M, L R
error code 1 (ch 1) ch 1.
Operation mode display Stores the communication type being used by
D8419 M, L R
(ch 1) ch 1. (in the FX3S, FX3G, FX3GC, FX3U and FX3UC)
Serial communication Stores the serial communication error code for
D8438 M, L R
error code 2 (ch 2) ch 2. (in the FX3G, FX3GC, FX3U and FX3UC)
Operation mode display Stores the communication type being used by
D8439 M, L R
(ch 2) ch 2. (in the FX3G, FX3GC, FX3U and FX3UC)
Devices for communication setting
Corresponding station
D8176 Provided to set the station number. 0 M, L R/W
number settings
Slave station quantity Provided to set the number of slave stations used
D8177 7 M R/W
setting in communication.
D8178 Refresh range setting Provided to set the refresh range. 0 M R/W
D8179 Number of retries Provided to set the number of retry times. 3 M R/W
D8180 Monitoring time Provided to set the no-response monitoring time. 5 M R/W
Devices for checking communication status
D8201 Present link scan time Current value of the network cycle time M R
D8202 Maximum link scan time Maximum value of the network cycle time M R
Data transfer sequence Amount of data sequence errors that occurred in
D8203 L R
error count the master station
Amount of data sequence errors that occurred in
D8204 Data transfer sequence a slave station.
M, L R
to D8210 error count However, data sequence errors occurring within
the slave station itself cannot be counted.
Data transmission error
D8211 Stores the error code for the master station. L R
code
Stores the error code for a slave station.
D8212 Data transmission error
However, data sequence errors occurring within M, L R
to D8218 code
the slave station itself cannot be counted.
R : Read only
R/W : Read or Write
M : Master station (station No. 0)
L : Slave station (station No. 1 to 7)

B-56
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.1 Related Device List

Common Items
Master Slave station Slave station Slave station Slave station Slave station Slave station Slave station
station No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7

N:N Network

Parallel Link

Computer Link

Communication
Inverter


(RS/RS2 Instruction)
Communication
Non-Protocol

D8204 D8205 D8206 D8207 D8208 D8209 D8210 G

(FX2N-232IF)
Communication
Non-Protocol

D8212 D8213 D8214 D8215 D8216 D8217 D8218


H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-57
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.1 Related Device List

10.1.2 For FX0N and FX1S PLCs

1. Bit devices
Device Initial Detec-
Name Description R/W
number value tion
Devices for communication setting
M8038 Parameter setting Communication parameter setting flag M, L R
Devices for checking communication status
Turns ON when a data transfer sequence
M504 Data transfer sequence error L R
error occurs in the master station.
Turns ON when a data transfer sequence
error occurs in a slave station.
M505 to M511 Data transfer sequence error M, L R
However, data transfer sequence errors within
the slave station itself cannot be detected.
Remains ON while data transfer is being
M503 Data transfer sequence ON M, L R
executed.
R: Read only (used as a contact in program)
M: Master station (station No. 0) L: Slave station (station No. 1 to 7)

2. Word devices (data registers)


Device Initial Detec-
Name Description R/W
number value tion
Devices for checking
Corresponding station
D8173 Provided to check the station number. M, L R
number settings status
Slave station quantity setting Provided to check the number of slave
D8174 M, L R
status stations.
D8175 Refresh range setting status Provided to check the refresh range. M, L R
Devices for communication setting
Corresponding station
D8176 Provided to set the station number. 0 M, L R/W
number settings
Provided to set the number of slave stations
D8177 Slave station quantity setting 7 M R/W
used in communication.
D8178 Refresh range setting Provided to set the refresh range. 0 M R/W
D8179 Number of retries Provided to set the number of retries. 3 M R/W
Provided to set the no-response monitoring
D8180 Monitoring time 5 M R/W
time.
Devices for checking communication status
Stores the current value of the network cycle
D201 Present link scan time M R
time.
Stores the maximum value of the network
D202 Maximum link scan time M R
cycle time.
Data transfer sequence error Stores the amount of data sequence errors
D203 L R
count that occurred in the master station.
Amount of data sequence errors that
Data transfer sequence error occurred in a slave station.
D204 to D210 M, L R
count However, data sequence errors that occurred
within the slave station itself cannot be counted.
D211 Data transmission error code Stores the error code for the master station. L R
Stores the error code for a slave station.
D212 to D218 Data transmission error code However, data sequence errors that occurred M, L R
within the slave station itself cannot be counted.
D219 to D255 Not applicable Provided for the internal processing.
R: Read only R/W: Read or Write
M: Master station (station No. 0) L: Slave station (station No. 1 to 7)

B-58
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.1 Related Device List

Common Items
Master Slave station Slave station Slave station Slave station Slave station Slave station Slave station
station No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7
B

N:N Network

Parallel Link
M505 M506 M507 M508 M509 M510 M511

Computer Link
Master Slave station Slave station Slave station Slave station Slave station Slave station Slave station
station No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7
E

Communication
Inverter

(RS/RS2 Instruction)
Communication
Non-Protocol

(FX2N-232IF)
Communication
Non-Protocol


H

Communication
Programming

D204 D205 D206 D207 D208 D209 D210 I


Maintenance
Remote

D212 D213 D214 D215 D216 D217 D218

Apx.A
models
Discontinued

B-59
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

10.2 Details of Related Devices


The devices described below are used in the N:N Network.

10.2.1 Parameter setting [M8038]


This device works as the communication parameter setting flag.

1. Stations requiring program setting


Setting is required for the master station and slave stations.

2. Detailed contents
"LD M8038" provided in step 0 starts the parameter setting, and the last instruction in this circuit block finishes
the setting.
(This sequence program is not executed in every scan cycle.)

3. Cautions on use
Do not set this device to ON using a program or programming tool.

10.2.2 Channel setting [M8179]


This device works as the channel setting flag (in the FX3G, FX3GC, FX3U and FX3UC).

1. Stations requiring program setting


Setting is required for the master station and slave stations.

2. Detailed contents
When using ch 2 as the communication port, set this device to ON in the sequence program.
When using ch 1, the sequence program is not required.

10.2.3 Serial communication error [M8063 and M8438]


These devices turn ON when an error is included in the parameters used to set the N:N Network. (M8438 is
available in the FX3G, FX3GC, FX3U and FX3UC.)

1. Stations requiring program setting


Setting is required for the master station and slave stations to check the communication status.

2. Detailed contents
M8063 turns ON when an error is included in the parameters used to set N:N Network using ch 1.
M8438 turns ON when an error is included in the parameters used to set N:N Network using ch 2.

3. Cautions on use
Do not set these devices to ON using a program or programming tool.
Serial communication errors are not cleared even when communication is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

B-60
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

A
10.2.4 Data transfer sequence error [M8138 to M8190] [M504 to M511]

Common Items
These devices turn ON when a data transfer sequence error occurs in the master station or a slave station.

1. Stations requiring program setting


Setting is required for the master station and slave stations.
However, setting for the station itself is not required. B

N:N Network
2. Detailed contents
A used device varies depending on the FX Series.
Slave Slave Slave Slave Slave Slave Slave
Master
FX Series station station station station station station station
station
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7
FX1N, FX1NC, FX2N,
C

Parallel Link
FX2NC, FX3S, FX3G, M8183 M8184 M8185 M8186 M8187 M8188 M8189 M8190
FX3GC, FX3U, FX3UC
FX0N, FX1S M504 M505 M506 M507 M508 M509 M510 M511

3. Cautions on use
Data transfer sequence errors in a station itself cannot be detected. D
Do not set these devices to ON using a program or programming tool.

Computer Link
10.2.5 Data transfer sequence ON [M8191] [M503]
This device remains ON while data transfer is being from or to in the master station or slave station.

1. Stations requiring program setting E


Setting is required for the master station and slave stations.

Communication
Inverter
2. Detailed contents
The device used varies depending on the FX Series.

FX Series Data transfer sequence ON


FX1N, FX1NC, FX2N, F
FX2NC, FX3S, FX3G, M8191

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3GC, FX3U, FX3UC
FX0N, FX1S M503

3. Cautions on use
Do not set this device to ON using a program or programming tool. G

(FX2N-232IF)
Communication
Non-Protocol
10.2.6 Serial communication error code [D8063 and D8438]
These devices store the serial communication error code (D8438 is available in the FX3G, FX3GC, FX3U and
FX3UC).

1. Stations requiring program setting H


Setting is required for the master station and slave stations to check the error code.
Communication
Programming

2. Detailed contents
The following error code is stored when a serial communication error occurs.

Error code
ch1 ch2 Description I
Maintenance
Remote

D8063 D8438
6308 3808 N:N Network parameter setting error
6309 3809 N:N Network setting error

3. Cautions on use Apx.A


Serial communication errors are not cleared even after communication has recovered its normal status.
models
Discontinued

Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

B-61
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

10.2.7 Corresponding station number settings status [D8173]


This device is used to check the stations own station number settings status.

1. Stations requiring program setting


Setting is required for the master station and slave stations to check the setting status.

2. Detailed contents
The contents stored in the corresponding station number settings device D8176 are stored in D8173.

3. Cautions on use
Do not change the preset numeric value using a program or programming tool.

10.2.8 Slave station quantity setting status [D8174]


Use this device to check the number of slave stations set in the master station.

1. Stations requiring program setting


Setting is required for the master station and slave stations to check the setting status.

2. Detailed contents
The contents stored in the slave station quantity setting device D8177 in the master station are stored in
D8174.

3. Cautions on use
Do not change a preset numeric value using a program or programming tool.

10.2.9 Refresh range setting status [D8175]


Use this device to check the refresh range set in the master station.

1. Stations requiring program setting


Setting is required for the master station and slave stations to check the setting status.

2. Detailed contents
The contents stored in the refresh range setting device D8178 in the master station are stored in D8175.

3. Cautions on use
Do not change a preset numeric value using a program or programming tool.

10.2.10 Station number settings [D8176]


Set a value ranging from 0 to 7 to the special data register D8176 (initial value: 0).

1. Stations requiring program setting


The master and slave stations require program setting.

2. Detailed contents

Set value Description


0 Master station
Slave station number
1 to 7
Examples: "1" Station No. 1, "5" Station No. 5

B-62
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

A
10.2.11 Slave station quantity setting [D8177]

Common Items
Set a value ranging from 1 to 7 to the special data register D8177 (initial value: 7).

1. Stations requiring program setting


The master station requires program setting, and slave stations do not require program setting.
B
2. Detailed contents

N:N Network
Set value Description Set value Description
0 Not applicable 4 Four slave stations are connected.
1 One slave station is connected. 5 Five slave stations are connected.
2 Two slave stations are connected. 6 Six slave stations are connected.
C

Parallel Link
3 Three slave stations are connected. 7 Seven slave stations are connected.

10.2.12 Refresh range setting [D8178]


Set a value ranging from 0 to 2 to the special data register D8178 (initial value: 0). D

Computer Link
1. Stations requiring program setting
The master station requires program setting, and slave stations do not require program setting.

2. Pattern applicability in FX PLC

FX Series
Pattern (set value) E
Pattern 0 (0) Pattern 1 (1) Pattern 2 (2)

Communication
Inverter
FX0N PLC Not applicable Not applicable
FX1S PLC Not applicable Not applicable
FX1N, FX1NC PLC
FX2N, FX2NC PLC F
FX3S PLC

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3G, FX3GC PLC
FX3U, FX3UC PLC

3. Number and assignment of link devices


The number of link devices varies depending on the selected pattern, but the head device number remains
G

(FX2N-232IF)
Communication
Non-Protocol
the same.
It is recommended to leave unused numbers in the unused status to enable pattern change in the future.

Pattern 0 Pattern 1 Pattern 2


Bit device Word device Bit device Word device Bit device Word device
Station
No.
(M) (D) (M) (D) (M) (D) H
Communication
Programming

4 in each 32 in each 4 in each 64 in each 8 in each


0
station station station station station
0 D 0 to D 3 M1000 to M1031 D 0 to D 3 M1000 to M1063 D 0 to D 7
1 D10 to D13 M1064 to M1095 D10 to D13 M1064 to M1127 D10 to D17
2 D20 to D23 M1128 to M1159 D20 to D23 M1128 to M1191 D20 to D27 I
3 D30 to D33 M1192 to M1223 D30 to D33 M1192 to M1255 D30 to D37
Maintenance
Remote

4 D40 to D43 M1256 to M1287 D40 to D43 M1256 to M1319 D40 to D47
5 D50 to D53 M1320 to M1351 D50 to D53 M1320 to M1383 D50 to D57
6 D60 to D63 M1384 to M1415 D60 to D63 M1384 to M1447 D60 to D67
7 D70 to D73 M1448 to M1479 D70 to D73 M1448 to M1511 D70 to D77 Apx.A
models
Discontinued

B-63
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

4. Cautions on use
1) Cautions on using FX0N and FX1S PLCs
When FX0N and/or FX1S PLCs are included in the system, make sure to set the refresh range to pattern
0.
If any other pattern is selected, data transfer error will occur in all FX0N and FX1S PLCs included in the
system, and the link time will become longer.
2) Occupied devices
The devices used in each pattern are occupied for the N:N Network in all stations.
Make sure that such devices are not used in general programs.

10.2.13 Number of retries [D8179]


Set a value ranging from 0 to 10 to the special data register D8179 (initial value: 3).

1. Stations requiring program setting


The master station requires program setting, and slave stations do not require program setting.

2. Detailed contents
When any response is not given after the specified number of retries, the irresponsive station is regarded as
having a data transfer sequence error by other stations.

10.2.14 Monitoring time setting [D8180]


Set a vale ranging from 5 to 255 to the special data register D8180 in "10 ms" units (initial value: 5 [50 ms]).

1. Stations requiring program setting


The master station requires program setting, and slave stations do not require program setting.

2. Detailed contents
If data transfer between the master station and a slave station requires time longer than the monitoring time
set here, the master station or slave station is regarded as abnormal.

10.2.15 Present link scan time [D8201] [D201]


This device stores the current value of the network cycle in the N:N Network (unit: 10 ms).

1. Stations requiring program setting


The master station requires program setting.

2. Detailed contents
The device used varies depending on the FX Series.

FX Series Data transfer sequence ON


FX1N, FX1NC, FX2N,
FX2NC, FX3S, FX3G, D8201
FX3GC, FX3U, FX3UC
FX0N, FX1S D201

3. Cautions on use
Do not change the preset numeric value using a program or programming tool.

B-64
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

A
10.2.16 Maximum link scan time [D8202] [D202]

Common Items
This device stores the maximum value of the network cycle in the N:N Network (unit: 10 ms).

1. Stations requiring program setting


The master station requires program setting.
B
2. Detailed contents

N:N Network
The device used varies depending on the FX Series.

FX Series Data transfer sequence ON


FX1N, FX1NC, FX2N,
FX2NC, FX3S, FX3G, D8202 C
FX3GC, FX3U, FX3UC

Parallel Link
FX0N, FX1S D202

3. Cautions on use
Do not change the preset numeric value using a program or programming tool.
D
10.2.17 Data transfer sequence error count [D8203 to D8210] [D203 to D210]

Computer Link
These devices store the amount of data transfer sequence errors that occurred in the master station and
slave stations.

1. Stations requiring program setting


The master and slave stations require program setting.
E

Communication
Inverter
However, setting for the station itself is not required.

2. Detailed contents
The device used varies depending on the FX Series.
Slave Slave Slave Slave Slave Slave Slave
FX Series
Master
station
station station station station station station station F
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1N, FX1NC, FX2N,
FX2NC, FX3S, FX3G, D8203 D8204 D8205 D8206 D8207 D8208 D8209 D8210
FX3GC, FX3U, FX3UC
FX0N, FX1S D203 D204 D205 D206 D207 D208 D209 D210
G
3. Cautions on use

(FX2N-232IF)
Communication
Non-Protocol
Data transfer sequence errors that occurred within the station itself cannot be detected.
Do not change a preset numeric value using the program or programming tool.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-65
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

10.2.18 Data transfer error code [D8211 to D8218] [D211 to D218]


These devices store the error code in the master station and slave stations.

1. Stations requiring program setting


The master station requires program setting.
However, this setting for the station itself is not required.

2. Detailed contents
1) The device used varies depending on the FX Series.
Slave Slave Slave Slave Slave Slave Slave
Master
FX Series station station station station station station station
station
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7
FX1N, FX1NC, FX2N, FX2NC,
D8211 D8212 D8213 D8214 D8215 D8216 D8217 D8218
FX3S, FX3G, FX3GC, FX3U, FX3UC
FX0N, FX1S D211 D212 D213 D214 D215 D216 D217 D218

2) Error code list


Station Station
Error in which which
Error name Contents of error Check point
code error detected
occurred error
Slave station did not respond to the
Wiring and power
01H Monitoring timeout L M sending request from the master station
supply
within the monitoring time.
An unexpected slave station responded
Station number Station number
02H L M to the sending request by the master
error settings
station.
The counter value included in the
03H Counter error L M parameter data is different from the Wiring
counter value given by a slave station.
Wiring, power
Message format The message given by the slave station
04H L M, L supply and station
error is incorrect.
number settings
The master station did not give a sending
Wiring and power
11H Monitoring timeout M L request to the next slave station within
supply
the monitoring timer.
Wiring, power
Message format The message from the master station is
14H M L supply and station
error incorrect.
number settings
Wiring, power
Slave station no
21H
response error
L L*1 The specified slave station does not exist. supply and station
number settings
An unexpected slave station responded
Station number Station number
22H
error
L L*1 to the sending request by the master
settings
station.
The counter value included in the
23H Counter error L L*1 parameter data is different from the Wiring
counter value given by a slave station.
Before parameters had been received,
Parameter not Wiring and power
31H
received
L L*2 sending request was received from the
supply
master station.
M: Master station, L: Slave station
*1. Any slave station other than the slave station in which error occurred
*2. Station in which error occurred

3. Cautions on use
Data transfer sequence errors that occurred within the station itself cannot be detected.
Do not change the preset numeric value using a program or programming tool.

B-66
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

A
10.2.19 Operation mode display [D8419 and D8439]

Common Items
These devices store the communication type being used. (in the FX3S, FX3G, FX3GC, FX3U and FX3UC)

1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
When communication port ch1 is used, D8419 stores the communication type.
B

N:N Network
When communication port ch2 is used, D8439 stores the communication type.

The table below shows the contents of the communication type codes.
Code Description
0 Programming communication
C
1 PP modem mode

Parallel Link
2 Protocol dedicated to computer link
3 N:N Network
4 RS instruction
5 RS2 instruction
6 Parallel link
D

Computer Link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication
10 CF-ADP
11 ENET-ADP E
12 Input/output expansion board is used.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

B-67
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
N:N Network 10.2 Details of Related Devices

MEMO

B-68
FX Series PLC User's Manual - Data Communication Edition
Parallel Link

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
C. Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains "parallel link" provided for the MELSEC-F FX Series Programmable Controllers and
Maintenance
Remote

should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

C-1
FX Series PLC User's Manual - Data Communication Edition
Parallel Link

C-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Parallel Link 1.1 Outline of System

Common Items
1. Outline
This chapter explains the parallel link. B

N:N Network
1.1 Outline of System
The parallel link allows connection between two FX PLCs of the same series to mutually link devices.
C
1) According to the number of devices to be linked, either pattern can be selected between the regular mode

Parallel Link
and the high speed mode.
2) Data link is automatically updated between up to two FX PLCs.
3) The total extension distance is 500 m (1640' 5") maximum (when only the 485ADPs are used except,
when the 485BDs are used with FX2(FX)/FX2C PLCs).
D

Computer Link
Important points and reference
System chapter/section

2 units ....... Number of linked units


500 m (1640' 5") [50 m (164' 0") when 485BD is used] ....... Total extension distance

FX PLC FX PLC
For specifications,
refer to Chapter 2. E

Communication
Inverter
To check applicable
....... PLC models,
refer to Section 1.3.

+ +
Communication
equipment operating
Communication
equipment operating
.......
For selection, F
in accordance with in accordance with
refer to Chapter 3.

(RS/RS2 Instruction)
Communication
Non-Protocol
RS-485 RS-485

.......
For wiring,
refer to Chapter 4.
Master station Slave station
....... The number of linked
Bit devices Transfer direction Bit devices
devices can be selected
among two patterns.
G
M800 to M899 M800 to M899

(FX2N-232IF)
Communication
Non-Protocol
For details,
M900 to M999 M900 to M999 refer to Chapter 2.

Word devices Word devices

D490 to D499 D490 to D499


H
D500 to D509 D500 to D509
Communication
Programming

The figure above shows the maximum number of linked devices. There are differences in the specifications and
limitation depending on the selected link pattern and FX Series.

I
Maintenance
Remote

Apx.A
models
Discontinued

C-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Parallel Link 1.2 Procedures Before Operation

1.2 Procedures Before Operation


The flow chart below shows the Parallel Link setting procedures up until data link:

Parallel link

Refer to Chapter 1.

Outline Outline of system


Applicable PLC versions
Applicable programming tools
Refer to Chapter 2.

Check communication specifications. Communication specifications


Number of link points and link time
Number of system devices
Refer to Chapter 3.

Determine system configuration and selection. System configuration


Select communication equipment.
Refer to Chapter 4.

Perform wiring. Wiring procedure


Wiring using twisted cables
Wiring example

Programming tool

Connect PLC*1

Refer to Chapter 5.
Perform PLC communication setting
PLC serial communication setting
(initialization).
Communication setting is not required.
(Check only unset items.)
Turn ON power. Refer to Chapter 6.

Perform test run (communication test). Communication test


Create test programs.

Refer to Chapter 7.

Create programs. Communication parameter setting


programs
Basic program
Based on SD/RD lamp lighting status and Error indication program example
contents of error check devices, verify that Detailed explanation of setting devices
communication is being executed normally.
If there are problems, refer to the troubleshooting
(Chapter 9).

Refer to Chapter 8.
Program examples in the regular parallel link mode
Practical program examples
are shown.

*1 For the programming tool to PLC connection procedure, refer to the "Programming Communication" section in this
manual or the respective programming tool manual.
For details on operating procedures, refer to the respective programming tool manual.

C-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Parallel Link 1.3 Communication Type Applicability in PLC

A
1.3 Communication Type Applicability in PLC

Common Items
1.3.1 Applicable versions
The communication types are applicable in the following versions. B
: Applicable (If applicable versions of main units are limited, they are described inside ( ).)

N:N Network
: Not applicable
PLC Applicability (applicable version) Remarks
FX3UC Series
FX3U Series
FX3GC Series
C

Parallel Link
FX3G Series
FX3S Series The link device range is limited.
FX2NC Series
FX2N Series (Ver. 1.04 or later)
FX1NC Series D
FX1N Series

Computer Link

FX1S Series The link device range is limited.
FX0N Series (Ver. 1.20 or later) The link device range is limited.
FX0S Series Parallel link is not provided.
FX0 Series Parallel link is not provided. E
The high-speed link mode is supported in Ver. 3.07 and

Communication
Inverter
FX2C Series
later.
The high-speed link mode is supported in Ver. 3.07 and
FX2(FX) Series
later.
FX1 Series Parallel link is not provided.
F
1.3.2 Version check

(RS/RS2 Instruction)
Communication
Non-Protocol
The PLC version can be checked by reading the last three digits of device D8001.
For a detailed description of the version check, refer to A. Common Items Section 4.2.

1.3.3 Products whose production was stopped G

(FX2N-232IF)
Communication
Non-Protocol
Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A.
To see the latest available products, refer to the general catalog.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Parallel Link 1.4 Programming Tool Applicability

1.4 Programming Tool Applicability

1.4.1 For applicable versions


The programming tool is applicable of main units for each FX Series from the following version:

1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 3.00 or later
FX-20P-MFXC-E
FX-10P-E Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW5 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 4.00 or later
FX-20P-MFXD-E
FX-10P-E Ver. 4.00 or later

C-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Parallel Link 1.4 Programming Tool Applicability

A
Product name Model name Applicable version Remarks

Common Items
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later) B
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units

N:N Network
models and versions supporting the list editor function.

2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs C
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later

Parallel Link
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units

FX3G PLC
models and versions supporting the list editor function.
D

Computer Link
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later

GOT1000 Series display units


Refer to manuals of GOT1000 Series display units for applicable
models and versions supporting the list editor function. E

Communication
Inverter
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. F
FX3S PLC

(RS/RS2 Instruction)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
G
FX2N and FX2NC PLCs

(FX2N-232IF)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW2 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.00 or later
FX-PCS-KIT/98
FX-PCS/98-3
SW1PC-FXGP/98(-3,-5)
SW1PC-FXGP/98-3
Ver. 4.00 or later
Ver. 4.00 or later
H
Communication
Programming

FX-PCS-KIT/V-3 SW1PC-FXGP/V3 Ver. 2.00 or later -


FX-A7PHP-KIT SW1RX-GPPFX Ver. 3.00 or later
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
FX-20P-MFXC
Ver. 4.00 or later I
Maintenance
Remote

FX-10P(-SET0) Ver. 3.00 or later


GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later) Apx.A
models
Discontinued

Refer to manuals of GOT1000 Series display units for applicable


GOT1000 Series display units
models and versions supporting the list editor function.

C-7
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Parallel Link 1.4 Programming Tool Applicability

Product name Model name Applicable version Remarks


FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 5.00 or later
-
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 5.00 or later
FX-20P-MFXD
FX-10P(-SET0) Ver. 4.00 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

1.4.2 For non-applicable versions (setting an alternative model)


Even programming tool not applicable to a PLC can create programs when an alternative model is set.
In this case, however, programming is enabled only in the function ranges provided for the alternative PLC
model such as instructions and program size.

Model to be
Model to be set Priority: High Low
programmed
FX3UC Series FX3UC FX2N FX2(FX)
FX3U Series FX3UC, FX3U FX2N FX2(FX)
*1
FX3GC Series FX3G, FX3GC FX1N FX2N*1
FX3G Series FX3G FX1N*1 FX2N*1
FX3S Series FX3S FX3G FX1N*1
FX2NC Series FX2NC, FX2N FX2(FX)
FX2N Series FX2N FX2(FX)
FX1NC Series FX1NC, FX1N FX2N FX2(FX)
FX1N Series FX1N FX2N FX2(FX)
FX1S Series FX1S FX2(FX)
FX0N Series FX0N FX2(FX)
FX0S Series FX0S FX2(FX)
FX0 Series FX0 FX2(FX)
FX2C Series FX2C, FX2(FX) FX2(FX)
FX2(FX) Series FX2(FX)
FX1 Series FX1

*1. "FX2N" is selected when the FX-10P(-E) is used.

Point
In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

C-8
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Parallel Link 2.1 Communication Specifications (Reference)

Common Items
2. Specifications
This chapter explains the communication specifications and performance of the parallel link. B

N:N Network
2.1 Communication Specifications (Reference)
The parallel link is executed using the (fixed) communication specifications shown in the table below.
Specification items such as baud rate cannot be changed.
C
Item Specifications Remarks

Parallel Link
Number of connectable units 2 maximum (1:1)
Transmission standard RS-485 or RS-422 standard
500 m (1640' 5") or less
FX3UC, FX3U, FX3GC, FX3G, FX3S,
Maximum FX2NC, FX2N, FX1NC, FX1N, FX1S, FX0N
total PLCs
[50 m (164' 0")or less when D
extension 485BD is included in system]

Computer Link
distance Wire link: 10 m (32' 9") or less Wire link: FX2-40AW
FX2(FX), FX2C PLCs
Optical fiber: 50 m (164' 0") or less Optical fiber: FX2-40AP
Protocol type Parallel link
Control procedure

Communication method
Half-duplex, E
bidirectional communication

Communication
Inverter
FX3UC, FX3U, FX3GC, FX3G, FX3S PLCs 115200bps
Baud rate FX2NC, FX2N, FX1NC, FX1N, FX1S, FX0N,
19200bps
FX2C, FX2(FX) PLCs
Start bit
Character Data bit
F
Fixed

(RS/RS2 Instruction)
Communication
Non-Protocol
format Parity bit
Stop bit
Header
Fixed
Terminator
Control line G

(FX2N-232IF)
Communication
Non-Protocol
Sum check Fixed

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-9
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Parallel Link 2.2 Link Specifications

2.2 Link Specifications

2.2.1 PLC communication type applicability status


: Applicable (If applicable versions of main units are limited, they are described inside ( ).)
: Not applicable
Regular parallel link mode applicability High speed parallel link mode applicability
PLC
(applicable version) (applicable version)
FX3UC Series
FX3U Series
FX3GC Series
FX3G Series
FX3S Series
FX2NC Series
FX2N Series (Ver. 1.04 or later) (Ver. 1.04 or later)
FX1NC Series
FX1N Series
FX1S Series
FX0N Series (Ver. 1.20 or later) (Ver. 1.20 or later)
FX0S Series
FX0 Series
FX2C Series (Ver. 3.07 or later)
FX2(FX) Series (Ver. 3.07 or later)

2.2.2 Link time


The link time indicates the cycle time in which link devices are updated.
The link time varies depending on the link mode as shown in the tables below.

1. For FX3S, FX3G, FX3GC, FX3U and FX3UC Series

Link mode Time


Regular parallel link mode 15 ms + Master station operation cycle (ms) + Slave station operation cycle (ms)
High speed parallel link mode 5 ms + Master station operation cycle (ms) + Slave station operation cycle (ms)

2. For FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC, FX2N and FX2NC Series

Link mode Time


Regular parallel link mode 70 ms + Master station operation cycle (ms) + Slave station operation cycle (ms)
High speed parallel link mode 20 ms + Master station operation cycle (ms) + Slave station operation cycle (ms)

C-10
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Parallel Link 2.3 Link Device Numbers and Number of Points

A
2.3 Link Device Numbers and Number of Points

Common Items
2.3.1 For FX0N, FX1S and FX3S Series

Regular parallel link mode High speed parallel link mode


B
Mode

N:N Network
Bit device (M) Word device (D) Bit device (M) Word device (D)
Type 50 in each station 10 in each station 0 2 in each station
Master station M400 to M449 D230 to D239 D230, D231
Slave station M450 to M499 D240 to D249 D240, D241
C
1. Regular parallel link mode

Parallel Link
FX0N, FX1S, FX3S FX0N, FX1S, FX3S

M400 to M449 M400 to M449


M450 to M499
Automatic update
M450 to M499 D

Computer Link
D230 to D239 D230 to D239
M8000 Automatic update M8000
D240 to D249 D240 to D249
M8070 M8071
RUN RUN
Master station Slave station
monitor monitor
E
For the master station, set M8070 to ON. For the slave station, set M8071 to ON.

Communication
Inverter
2. High speed parallel link mode

FX0N, FX1S, FX3S FX0N, FX1S, FX3S


F

(RS/RS2 Instruction)
Communication
Non-Protocol
M8000 M8000
M8070 M8071
RUN D230, D231 D230, D231 RUN
monitor Master station monitor Slave station
Automatic update
M8162
D240, D241 D240, D241
M8162 G

(FX2N-232IF)
Communication
Non-Protocol
High speed parallel link High speed parallel link
mode mode
For the master station, set M8070 and M8162 to ON. For the slave station, set M8071 and M8162 to ON.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-11
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Parallel Link 2.3 Link Device Numbers and Number of Points

2.3.2 For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U and FX3UC Series

Regular parallel link mode High speed parallel link mode


Mode
Bit device (M) Word device (D) Bit device (M) Word device (D)
Type 100 in each station 10 in each station 0 2 in each station
Master station M800 to M899 D490 to D499 D490, D491
Slave station M900 to M999 D500 to D509 D500, D501

1. Regular parallel link mode

FX2(FX), FX2C, FX2(FX), FX2C,


FX1N, FX1NC, FX1N, FX1NC,
FX2N, FX2NC, M800 to M899 M800 to M899 FX2N, FX2NC,
FX3G, FX3GC, Automatic update FX3G, FX3GC,
FX3U, FX3UC M900 to M999 M900 to M999 FX3U, FX3UC

D490 to D499 D490 to D499


M8000 Automatic update M8000
D500 to D509 D500 to D509
M8070 M8071
RUN RUN
monitor Master station monitor Slave station

For the master station, set M8070 to ON. For the slave station, set M8071 to ON.

2. High speed parallel link mode


FX2(FX), FX2C, FX2(FX), FX2C,
FX1N, FX1NC, FX1N, FX1NC,
FX2N, FX2NC, FX2N, FX2NC,
FX3G, FX3GC, FX3G, FX3GC,
FX3U, FX3UC FX3U, FX3UC
M8000 M8000
M8070 M8071
RUN D490, D491 D490, D491 RUN
monitor Master station monitor Slave station
Automatic update
D500, D501 D500, D501
M8162 M8162
High speed parallel link High speed parallel link
mode mode
For the master station, set M8070 and M8162 to ON. For the slave station, set M8071 and M8162 to ON.

C-12
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.1 System Configuration

Common Items
3. System Configuration and Selection
This chapter explains the configuration of communication equipment operating in accordance with RS-485 B
and the system selection required by FX PLCs.

N:N Network
3.1 System Configuration
This section outlines the system configuration required to use the parallel link.
Add (optional) communication equipment operating in accordance with RS-485 to an FX PLC main unit.
C

Parallel Link
3.1.1 Rule for connection
When using the parallel link, PLCs in the same group can be connected as shown in the table below.

Group PLC Series D

Computer Link
1 FX3U and FX3UC Series
2 FX3G and FX3GC Series
3 FX3S Series
4 FX2N and FX2NC Series
5 FX1N and FX1NC Series E

Communication
Inverter
6 FX1S Series
7 FX0N Series
8 FX2(FX) and FX2C Series

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-13
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.2 Configuration of Each Group

3.2 Configuration of Each Group

1 , 2 and 3 indicate the communication equipment combination patterns.

1. Group 1 (FX3U and FX3UC PLCs)


Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

1
RDA

RD

+
RDB

SDA

SD SDB

SG

Communication FX3U Series This is the communication board 50 m


board built into the PLC, reducing the
installation area. (164' 0")
RDA

RD

+
RDB

SDA

SD SDB

SG

Communication
board FX3UC-32MT-LT(-2)

2
+ +

Attach the expansion board to the


Communication
adapter
Expansion
board
FX3U Series main unit, and then attach the 500 m
communication adapter to the left (1640' 5")
side of the main unit.

+ +

Communication Expansion FX3UC-32MT-LT(-2)


adapter board

+ Attach the communication adapter 500 m


to the left side of the main unit.
(1640' 5")

Communication FX3UC Series


adapter (D, DS, DSS)

For communication equipment combinations for each FX Series, refer to the next section.

C-14
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.2 Configuration of Each Group

A
2. Group 2 (FX3G and FX3GC PLCs)

Common Items
Communication equipment operating Total extension
in accordance with RS-485
FX PLC Important point in selection
distance

This is the communication board 50 m


B
+ built into the PLC, reducing the

N:N Network
installation area. (164' 0")
Communication FX3G Series
board

C
2 Attach the connector conversion

Parallel Link
adapter to the main unit, and then 500 m
+ + attach the communication adapter (1640' 5")
to the left side of the main unit.

Communication Connector
adapter conversion adapter
FX3G Series
D

Computer Link
3

+ Attach the communication adapter 500 m


to the left side of the main unit.
(1640' 5") E

Communication
Inverter
Communication FX3GC Series
adapter

For communication equipment combinations for each FX Series, refer to the next section.

3. Group 3 (FX3S PLC)


F

(RS/RS2 Instruction)
Communication
Non-Protocol
Communication equipment operating Total extension
in accordance with RS-485
FX PLC Important point in selection
distance

+
This is the communication board
built into the PLC, reducing the
50 m G
(164' 0")

(FX2N-232IF)
Communication
Non-Protocol
installation area.
Communication FX3S Series
board

2 Attach the connector conversion


H
500 m
Communication
Programming

adapter to the main unit, and then


+ + attach the communication adapter (1640' 5")
to the left side of the main unit.

Communication Connector FX3S Series


adapter conversion adapter
I
Maintenance
Remote

For communication equipment combinations for each FX Series, refer to the next section.

Apx.A
models
Discontinued

C-15
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.2 Configuration of Each Group

4. Group 4 (FX2N and FX2NC PLCs)


Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

1
This is the communication board
+ built into the PLC, reducing the 50 m
installation area. (164' 0")
Communication
board FX2N Series
2 Attach the special adapter
connection board to the main unit,
+ + and then attach the communication 500 m
adapter to the left side of the main (1640' 5")
unit.
Communication Special adapter FX2N Series
adapter connection board
3
+ Attach the communication adapter 500 m
to the left side of the main unit. (1640' 5")

Communication FX2NC Series


adapter
For communication equipment combinations for each FX Series, refer to the next section.

5. Group 5 (FX1N and FX1NC PLCs)


Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

1
This is the communication board 50 m
+ built into the PLC, reducing the
(164' 0")
installation area.
Communication
board FX1N Series

2 Attach the special adapter


connection board to the main unit, 500 m
+ + and then attach the communication
(1640' 5")
adapter to the left side of the main
unit.
Communication Special adapter FX1N Series
adapter connection board

3
+ Attach the communication adapter 500 m
to the left side of the main unit. (1640' 5")
Communication FX1NC Series
adapter
For communication equipment combinations for each FX Series, refer to the next section.

C-16
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.2 Configuration of Each Group

A
6. Group 6 (FX1S PLC)

Common Items
Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

1
+
This is the communication board
built into the PLC, reducing the
50 m B
installation area. (164' 0")

N:N Network
Communication
board FX1S Series

2 Attach the special adapter


connection board to the main unit, 500 m
+ + and then attach the communication
adapter to the left side of the main
(1640' 5") C
unit.

Parallel Link
Communication Special adapter FX1S Series
adapter connection board

For communication equipment combinations for each FX Series, refer to the next section.
D
7. Group 7 (FX0N PLC)

Computer Link
Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

1
+ Attach the communication adapter 500 m E
to the left side of the main unit.
(1640' 5")

Communication
Inverter
Communication FX0N Series
adapter

For communication equipment combinations for each FX Series, refer to the next section.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
8. Group 8 (FX2(FX) and FX2C PLCs)
Communication equipment using Total extension
optical fiber or in accordance FX PLC Important point in selection distance
with RS-485

1
Attach the communication adapter G
+ to the left side of the main unit. 50 m

(FX2N-232IF)
Communication
Non-Protocol
Perform wiring using optical fiber (164' 0")
cables.
Communication FX2(FX)/FX2C Series
adapter
2
Attach the communication adapter
to the left side of the main unit.
H
+ Perform wiring using twisted pair 10 m
Communication
Programming

cables. (32' 9")


Communication FX2(FX)/FX2C Series
adapter

For communication equipment combinations for each FX Series, refer to the next section.
I
Maintenance
Remote

Apx.A
models
Discontinued

C-17
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.3 Applicable FX PLC and Communication Equipment

3.3 Applicable FX PLC and Communication Equipment


Select a (optional) communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the external dimensions are different between the units shown in "FX2NC-485ADP/
FX0N-485ADP". Select either one.
- In the table below, only the cable is different between the units shown in "FX3G-485-BD/FX3G-485-BD-
RJ". Select either one.
- The parallel link is not provided for the FX1, FX0 and FX0S PLCs.
Total extension
FX Series Communication equipment (option) Check
distance

500 m
(1640' 5")

FX0N FX2NC-485ADP FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0")
FX1N-485-BD
(European terminal block)

FX1S + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0")
FX1N-485-BD
(European terminal block)

FX1N + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0")

FX2N-485-BD

FX2N + + 500 m
(1640' 5")

FX2N-CNV-BD FX2NC-485ADP FX2N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

C-18
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.3 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance

50 m
(164' 0") B

N:N Network
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3S
+ 500 m
C

Parallel Link
(1640' 5")

FX3S-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

D
50 m

Computer Link
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3G
E

Communication
Inverter
(14-point, 24-point
500 m
type)
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

When using channel 1 (ch 1)


F

(RS/RS2 Instruction)
Communication
Non-Protocol
ch1 ch1

50 m
(164' 0") G

(FX2N-232IF)
Communication
Non-Protocol
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch1 when connected to
the option connector 1.
FX3G
(40-point, 60-point
type)
ch1
H
Communication
Programming

500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block) I
Maintenance
Remote

Apx.A
models
Discontinued

C-19
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.3 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch2 ch2

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch2 when connected to
the option connector 2.

ch1 ch2
FX3G
(40-point, 60-point
type)

500 m
(1640' 5")
FX3G-CNV-ADP FX3U- ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
When using channel 1 (ch 1)

ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)

ch1
FX3U

+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

C-20
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.3 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch1 ch2

B
+
RD

N:N Network
SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
C

Parallel Link
port channel.
ch1 ch2
FX3U

+ + 500 m
D

Computer Link
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
E

Communication
Inverter
500 m
(1640' 5")

FX1NC FX2NC-485ADP
(European terminal block)
FX0N-485ADP
(Terminal block)
F

(RS/RS2 Instruction)
Communication
Non-Protocol
500 m
(1640' 5")
G
FX2NC-485ADP FX0N-485ADP

(FX2N-232IF)
Communication
Non-Protocol
FX2NC (European terminal block) (Terminal block)

When using channel 1 (ch 1)


ch1

H
500 m
Communication
Programming

(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)
When using channel 2 (ch 2)
I
ch1 ch2
Maintenance
Remote

FX3GC

+ 500 m
(1640' 5")

FX3U-ADP(-MB) FX3U-485ADP(-MB) Apx.A


(Where represents (European terminal block)
models
Discontinued

232 and 485).

C-21
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.3 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

500 m
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)
When using channel 2 (ch 2)
ch1 ch2

FX3UC
(D, DS, DSS)
+ 500 m
(1640' 5")
FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
When using channel 1 (ch 1)
ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)

ch1

+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)
When using channel 2 (ch 2)
ch1 ch2

+
RD

FX3UC-32MT-LT SD

(-2) 500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
ch1 ch2

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

C-22
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Parallel Link 3.3 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance

50 m
(164' 0")
B

N:N Network
FX2-40AP
(for optical fiber)

C
FX2(FX)

Parallel Link
10 m
(32' 9")

FX2-40AW
(for wire link)

Computer Link
50 m
(164' 0")

FX2-40AP
(for optical fiber) E

Communication
Inverter
FX2C 10 m
(32' 9")

FX2-40AW
F

(RS/RS2 Instruction)
Communication
Non-Protocol
(for wire link)

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-23
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.1 Wiring Procedure

4. Wiring
This chapter explains the wiring.

WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.

WIRING PRECAUTIONS

Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents
due to abnormal data written to the PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the PLC. However, do not use common
grounding with heavy electrical systems.
Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure
that the screwdriver does not touch the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

4.1 Wiring Procedure

1 Preparing for wiring


Prepare cables and terminal resistors required for wiring.
For details, refer to Section 4.2.

2 Turning OFF the power to the PLC


Before starting any wiring work, make sure that the power to the PLC is OFF.
3 Connecting the power supply (FX0N-485ADP only)
Connect the power supply to the 24V DC power terminal.
4 Wiring communication equipment
Connect communication equipment operating in accordance with RS-485.
For details, refer to Section 4.3.

C-24
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.2 Selecting Cables and Terminal Resistors

A
4.2 Selecting Cables and Terminal Resistors

Common Items
Select cables using the procedure described below.

4.2.1 Twisted pair cable


B
Use shielded twisted pair cables for connecting communication equipment operating in accordance with RS-

N:N Network
485.
The table below shows recommended model names and manufacturers of cables used for wiring.

1. Recommended cables
Manufacturer Model name Remarks C
SPEV(SB)-0.2-2P Two-pair cable of 0.2 mm2

Parallel Link
Mitsubishi Cable Industries, Ltd. SPEV(SB)-MPC-0.2 3P Three-pair cable of 0.2 mm2
SPEV(SB)-0.5-2P Two-pair cable of 0.5 mm2
KMPEV-SB CWS-178 0.2SQ 2P Two-pair cable of 0.2 mm2
Showa Holdings Co., Ltd.
KMPEV-SB CWS-178 0.5SQ 2P Two-pair cable of 0.5 mm2 D

Computer Link
DPEV SB 0.3 3P Three-pair cable of 0.3 mm2
Sumitomo Electric Industries, Ltd.
DPEV SB 0.5 3P Three-pair cable of 0.5 mm2
D-KPEV-SB 0.2 3P Three-pair cable of 0.2 mm2
The Furukawa Electric Co., Ltd.
D-KPEV-SB 0.5 3P Three-pair cable of 0.5 mm2
E
IPEV-SB 2P 0.3 mm2 Two-pair cable of 0.3 mm2

Communication
Inverter
Fujikura Ltd.
IPEV-SB 2P 0.5 mm2 Two-pair cable of 0.5 mm2

2. Cable structural drawing (reference)


Pair
F
Shield

(RS/RS2 Instruction)
Communication
Non-Protocol
Two-pair cable structural
G
Three-pair cable structural

(FX2N-232IF)
Communication
Non-Protocol
drawing example
drawing example

4.2.2 10BASE-T cable


10BASE-T cables used in LAN wiring for a personal computer can be connected to FX3G-485-BD-RJ. H
1. Selection procedure when purchasing
Communication
Programming

1) Cable type : 10BASE-T cable (Category 3 or higher)


2) Connection specifications : One-pair wiring: Straight type
Two-pair wiring: Cross type (Use a cross cable with the following connection)
5 5
4
3
4
3
I
Maintenance
Remote

6 6
1 1
2 2
7 7
8 8
3) Connector : RJ45 connector (Connector with metal frame is used)
2. Cautions on using commercial cables
Apx.A
models
Discontinued

Pay attention to the following point when purchasing commercial cables.


Use shielded cables. Make sure to connect the shield to the metal frame of the connector, and perform
class D grounding.

C-25
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.2 Selecting Cables and Terminal Resistors

4.2.3 Connecting cables

1. European type terminal block


The FX3G-485-BD-RJ terminal block is used for grounding.
The other options use shielded twisted pair cables for connecting communication equipment operating in
accordance with RS-485.
The table below shows applicable cables and tightening torques.
Cable size when Cable size when Bar terminal with Tool size
Tightening
one cable is two cables are Insulating sleeve
torque A B
connected connected (cable size)
FX3U-485-BD
FX3G-485-BD AWG22 to Applicable 0.22 to 0.25
AWG22 0.4 (0.01") 2.5 (0.09")
FX3U-485ADP AWG20 (AWG22 to AWG20) Nm
(-MB)
FX3G-485-BD- 0.5 to 0.6
AWG20 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
RJ Nm
FX2N-485-BD 0.5 to 0.6
AWG26 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
FX1N-485-BD Nm
AWG26 to AWG26 to 0.4 to 0.5
FX2NC-485ADP Not applicable 0.6 (0.03") 3.5 (0.14")
AWG16 AWG20 Nm

Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
With regard to the cable end treatment, use a stranded cable or solid cable as it is, or use a bar terminal with
insulating sleeve.
FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD and FX2NC-485ADP cannot use a bar terminal with insulating
sleeve.
When using a stranded cable or solid cable as it is
- Twist the end of a stranded cable so that wires do not get barbed.
- Do not plate the end of the cable.
FX3G-485-BD, FX3U-485-BD, FX3G-485-BD-RJ,
FX3U-485ADP(-MB) FX2N-485-BD, FX1N-485-BD FX2NC-485ADP

Approx. 9 mm Approx. 6 mm Approx. 8 mm


(0.35") (0.23") (0.31")

When using a bar terminal with insulating sleeve Insulating sleeve Contact area
Because it is difficult to insert a cable into an insulating sleeve (Crimp area)
depending on the thickness of the cable sheath, select the proper cable
according to the outline drawing. 8 mm (0.31")
<Reference> 2.6 mm
(0.1") 14 mm
Manufacturer Model name Caulking tool (0.55")

CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
(or CRIMPFOX 6T-F*2)

*1. Old model name : CRIMPFOX ZA 3


*2. Old model name : CRIMPFOX UD 6

C-26
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.2 Selecting Cables and Terminal Resistors

A
Tool

Common Items
Select a
When tightening a terminal on the European terminal block, use a small screwdriver
commercial straight shape screwdriver whose tip is shown in the figure to with a
straight tip.
the right.

Note
If the diameter of screwdriver grip is too small, tightening torque will not
A B
For size A and size B,
B
refer to the table above.

N:N Network
be able to be achieved. To achieve the appropriate tightening torque
shown in the previous page, use the following screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
<Reference>
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB)
Manufacturer Model name C

Parallel Link
Phoenix Contact Co., Ltd. SZS 0.4 2.5

FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD, FX2NC-485ADP


Manufacturer Model name
Phoenix Contact Co., Ltd. SZF 1-0.6 3.5
D
2. Terminal block

Computer Link
In the FX0N-485ADP and FX-485ADP, the terminal screw size is "M3".
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 Nm.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions. E
When wiring one cable to one terminal

Communication
Inverter
Terminal Crimp
3.2(0.13") screw terminal
6.2mm(0.24")
or less
3.2(0.13") F
6.2mm(0.24") Terminal

(RS/RS2 Instruction)
Communication
Non-Protocol
or less
When wiring two cables to one terminal
3.2(0.13")
6.2mm(0.24") Terminal Crimp
or less
6.3mm(0.25")
screw terminal G

(FX2N-232IF)
Communication
Non-Protocol
or more

3.2(0.13")
6.2mm(0.24") Terminal
or less 6.3mm(0.25")
or more
H
Communication
Programming

4.2.4 Optical fiber cable


Two optical fiber cables are required.
1. Cable types I
Maintenance
Remote

Cable Length Remarks


F-OFC-M10 10 m (32' 9") Optical connector CA9104AP manufactured by Hitachi is already connected.
F-OFC-M30 30 m (98' 5") Optical connector CA9104AP manufactured by Hitachi is already connected.
F-OFC-M50 50 m (164' 0") Optical connector CA9104AP manufactured by Hitachi is already connected.
Apx.A
2. Cautions on wiring
models
Discontinued

Separate the optical connector from strong electric cables as much as possible.
Connect devices with the smallest load to the output terminals Y000 to Y003 which are located near the
optical connector.

C-27
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.2 Selecting Cables and Terminal Resistors

4.2.5 Connecting terminal resistors


In the case of one-pair wiring, connect a terminal resistor to the RDA-RDB signal Brown Precision
terminal of the communication equipment.
In the case of two-pair wiring, connect a terminal resistor to the RDA-RDB signal
terminal and SDA-SDB terminal of the communication equipment.
1. Terminal resistor type 1 1 1 =110
In the case of one-pair wiring, use two terminal resistors of 110 , 1/2 W. (101)
In the case of two-pair wiring, use four terminal resistors of 330 , 1/4 W. Orange Brown Precision
Among the terminal resistors supplied with the communication equipment, select
ones with the color codes shown to the right.
2. When using the FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ or
FX3U-485ADP(-MB) 3 3 1 =330
The FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB) (101)
have built-in terminal resistors.
Set the terminal resistor selector switch accordingly.
FX3U-485-BD FX3U-485ADP(-MB)

Terminal
330
resistor Terminal
selector OPEN resistor selector
switch
switch 110

FX3G-485-BD
Remove the upper terminal block before changing over the switch in the FX3G-485-BD.

Removal: Loosen the terminal block mounting screws, and remove the terminal block.
Installation: Attach the terminal block, and tighten the terminal block mounting screws.
Tightening torque: 0.4 to 0.5 Nm
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do
so may cause equipment failures or malfunctions.
For installation and removal of the terminal block, use the
recommended tool shown below or a tool having straight tip (such as Select a
screwdriver) as shown in the right figure. screwdriver
<Reference> with a
straight tip.
Manufacturer Model name
Phoenix Contact Co., Ltd. SZS 0.4 2.5
0.4mm 2.5mm
(0.01") (0.09")

Terminal resistor
selector switch

Terminal block mounting screws


FX3G-485-BD-RJ

Terminal resistor
selector switch

C-28
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.3 Connection Diagram

A
4.3 Connection Diagram

Common Items
4.3.1 For FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs

1. In the case of one-pair wiring


B

N:N Network
FX3U-485-BD, FX3G-485-BD FX3U-485-BD, FX3G-485-BD
FX3G-485-BD-RJ*1 FX3G-485-BD-RJ*1
FX3U-485ADP(-MB) FX3U-485ADP(-MB)
SDA SDA
(TXD+) (TXD+)
C
Terminal SDB
SDB Terminal

Parallel Link
resistor (TXD-) (TXD-) resistor
110 110
RDA RDA
(RXD+) (RXD+)
*2 *2
RDB
RDB
(RXD-) (RXD-) D

Computer Link
SG SG

Class-D grounding (resistance: 100 or less)*3

*1. Inside FX3G-485-BD-RJ, SDA and RDA are connected and SDB and RDB are connected respectively
E

Communication
Inverter
when 1-pair wiring is adopted. Signals are not connected to pins Nos. 4 and 5 of the RJ45 connector. For
cables of FX3G-485-BD-RJ, refer to Subsection 4.2.2.
Make sure to perform class D grounding on the shield of connected cables.
*2. The FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB) have a built-in terminal resistor.
Set the terminal resistor selector switch to 110 .
*3. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
F

(RS/RS2 Instruction)
Communication
Non-Protocol
the FX3U-485-BD, FX3G-485-BD or FX3U-485ADP(-MB).

2. In the case of two-pair wiring


FX3U-485-BD, FX3G-485-BD FX3U-485-BD, FX3G-485-BD
FX3G-485-BD-RJ *4 FX3G-485-BD-RJ *4
FX3U-485ADP(-MB) FX3U-485ADP(-MB) G

(FX2N-232IF)
Communication
Non-Protocol
SDA SDA
(TXD+) (TXD+)
*5 *5
SDB SDB
(TXD-) (TXD-)
RDA RDA H
(RXD+) (RXD+)
Communication
Programming

*5 *5
RDB RDB
Terminal (RXD-) (RXD-) Terminal
resistor resistor
330 SG SG 330
2 2
I
Maintenance
Remote

Class-D grounding (resistance: 100 or less)*6

*4. For cables of FX3G-485-BD-RJ, refer to Subsection 4.2.2.


Make sure to perform class D grounding on the shield of connected cables.
*5. The FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB) have a built-in terminal resistor.
Set the terminal resistor selector switch to 330 . Apx.A
models
Discontinued

*6. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
the FX3U-485-BD, FX3G-485-BD or FX3U-485ADP(-MB).

C-29
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.3 Connection Diagram

3. Switching of 1 pair / 2 paired wiring (FX3G-485-BD-RJ)


The FX3G-485-BD-RJ has a built-in wiring circuit switch.
Set the wiring circuit switch to 1 pair / 2 pair.

Wiring circuit
switch

4.3.2 For FX1S, FX1N, FX1NC, FX2N and FX2NC PLCs

1. In the case of one-pair wiring


FX2N-485-BD FX2N-485-BD
FX2NC-485ADP FX1N-485-BD FX0N-485ADP FX0N-485ADP FX1N-485-BD FX2NC-485ADP
SDA SDA SDA SDA SDA SDA
(TXD+) (TXD+) (TXD+) (TXD+) (TXD+) (TXD+)

Terminal SDB SDB SDB SDB SDB SDB Terminal


resistor (TXD-) (TXD-) (TXD-) (TXD-) (TXD-) (TXD-) resistor
110 110
RDA RDA RDA RDA RDA RDA
(RXD+) (RXD+) (RXD+) (RXD+) (RXD+) (RXD+)
RDB RDB RDB RDB RDB RDB
(RXD-) (RXD-) (RXD-) (RXD-) (RXD-) (RXD-)
LINK LINK
SG SG
SG SG

SG FG FG*2 SG

Class-D grounding (resistance: 100 or less)*1

*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
the FX2N-485-BD, FX1N-485-BD or FX2NC-485ADP.
*2. Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring
Class-D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.

C-30
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Parallel Link 4.4 Grounding

A
2. In the case of two-pair wiring

Common Items
FX2N-485-BD FX2N-485-BD
FX2NC-485ADP FX1N-485-BD FX0N-485ADP FX0N-485ADP FX1N-485-BD FX2NC-485ADP
SDA SDA SDA SDA SDA SDA
(TXD+) (TXD+) (TXD+) (TXD+) (TXD+) (TXD+)
B
SDB SDB SDB SDB SDB SDB

N:N Network
(TXD-) (TXD-) (TXD-) (TXD-) (TXD-) (TXD-)
RDA RDA RDA RDA RDA RDA
(RXD+) (RXD+) (RXD+) (RXD+) (RXD+) (RXD+)
RDB RDB RDB RDB RDB RDB
Terminal (RXD-) (RXD-) (RXD-) (RXD-) (RXD-) (RXD-) Terminal
C
resistor resistor

Parallel Link
330 LINK LINK 330
2 SG SG 2
SG SG

SG FG FG*2 SG

Computer Link
Class-D grounding (resistance: 100 or less)*1

*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
the FX2N-485-BD, FX1N-485-BD or FX2NC-485ADP.
*2. Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring
Class-D grounding. E
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.

Communication
Inverter
4.3.3 For FX2(FX) and FX2C PLCs

FX2-40AW FX2-40AW FX2-40AP FX2-40AP


F
SA SA T R

(RS/RS2 Instruction)
Communication
Non-Protocol
SB SB R T

SG*1 SG*1
G

(FX2N-232IF)
Communication
Non-Protocol
*1. Connect the SG terminal to the SG terminal in each PLC (main unit).

4.4 Grounding
Grounding should be performed as stated below.
H
Communication
Programming

The grounding resistance should be 100 or less.


Independent grounding should be performed for best results.
When independent grounding can not be performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the Hardware Edition of each series. I
Other Other Other
Maintenance
Remote

PLC equipment PLC equipment PLC equipment

Independent grounding Shared grounding Common grounding


Best condition Good condition Not allowed

The grounding wire size should be AWG 14 (2 mm2) or larger.


Apx.A
models
Discontinued

The grounding point should be close to the PLC, and all grounding wires should be as short as possible.

C-31
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
Parallel Link 5.1 Check Procedure

5. Communication Setting (Initialization) in FX


Programmable Controller
The communication setting is not required in FX PLCs for parallel link.
If the communication setting is already provided for another communication type or for checking the existing
communication setting, perform the following procedure.
When using this communication function in ch1 in an FX3S, FX3G, FX3GC, FX3U or FX3UC PLC, check D8120
and D8400 using the following procedure.
When using this communication function in ch2 in an FX3G, FX3GC, FX3U or FX3UC PLC, check D8420 using
the following procedure.
In other PLCs, use D8120 for verification.

5.1 Check Procedure

1 Monitoring D8120 (D8400, D8420)


Turn ON the power to the PLC while it is in STOP mode, and monitor D8120 (D8400, D8420).

1. When the value of D8120 (D8400, D8420) is "0"


The communication setting is not provided.

2. When the value of D8120 (D8400, D8420) is any value other than "0"
The communication setting is provided.

2 Checking absence/presence of parameter setting


Check absence/presence using the GX Works2, GX Developer, FXGP/WIN or FX-30P.
1) GX Works2 operating procedure (For details, refer to Section 5.2.)
2) FXGP/WIN operating procedure (For details, refer to Section 5.3.)
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

3 Checking absence/presence of sequence program setting


Check whether or not a write instruction is programmed for D8120 (D8400, D8420).

1. When such an instruction is programmed


Program example: (for D8120)
Change the program as shown below, and then change the PLC mode from STOP to RUN.
M8002 FNC 12
MOV H23F6 D8120 Program example
Initial pulse
The value varies depending on
the communication setting.

M8002 FNC 12
MOV H0000 D8120 Changed program
Initial pulse

2. When such an instruction is not programmed


Proceed to the next step.

4 Monitoring D8120 (D8400, D8420) again, and confirming that its value is "0"

C-32
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
Parallel Link 5.2 Communication Setting Using Parameter Method (GX Works2)

A
5.2 Communication Setting Using Parameter Method (GX Works2)

Common Items
Communication settings may be changed using the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 5.3. B
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

N:N Network
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.2.1 Operating procedure


This subsection explains the serial communication setting method.
Suppose that GX Works2 is already started up.
C

Parallel Link
1 Opening the parameter setting window
In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar. D

Computer Link
E

Communication
Inverter
2 Setting the serial communication (parameters) F

(RS/RS2 Instruction)
Communication
Non-Protocol
Click the [PLC System(2)] tab in the dialog box.
Select a channel to be used, and make sure that the "Operate Communication Setting" box is
cleared.
If a check mark is there, clear it.
Click [End].
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

3 Writing parameters and program to the PLC Apx.A


Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
models
Discontinued

[Execute].

C-33
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
Parallel Link 5.3 Communication Setting Using Parameter Method (FXGP/WIN)

5.3 Communication Setting Using Parameter Method (FXGP/WIN)


Communication settings may be changed using the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with FXGP/WIN.
Ch2 cannot be set using FXGP/WIN.
For details on GX Works2 operating procedure, refer to section 5.2.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already
started up.

1 Adjusting serial setting (parameter)


Double-click [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of parameter settings.

1. When there are no parameter settings


The dialog box shown below appears to indicate that there are no communication settings.
Click the [No] button.
In this case, the next step is not required.

2. When there are already parameter settings


The dialog box shown below appears to indicate that there are communication settings.
Click the [Clear] button to delete the communication settings from parameters.
Transfer parameters to the PLC using the following step.

2 Writing a sequence program (parameters) to the PLC


Select [PLC] [Transfers] [Write] from the toolbar, and click [OK] button.

C-34
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
Parallel Link 6.1 Test Procedure

Common Items
6. Test Run (Communication Test)
This chapter explains the communication test procedures for the parallel link. B
It is recommended to wire the master station and slave station, initialize communication settings in the FX

N:N Network
PLCs, and then execute the communication test using the following procedure to confirm the proper
operation.

6.1 Test Procedure


C

Parallel Link
1 Creating programs for the communication test
Create new programs for the communication test for the master station and slave station.
For program examples, refer to Section 6.2.
D
2

Computer Link
Transferring the program to each PLC
Turn ON the power to each PLC, and transfer the program.

3 Validating the communication setting E


When the PLC is in RUN mode, set it to STOP mode once, and then set it to RUN mode again.

Communication
Inverter
Or turn OFF the power of the master station and slave station, and then turn ON the power to both
stations at the same time.

4 Confirming flashing of the communication status indicator lamps (SD and RD)
F
Confirm that the built-in SD and RD lamps of the communication equipment are flashing.

(RS/RS2 Instruction)
Communication
Non-Protocol
If they are off, take proper action while referring to the troubleshooting procedures described later.

5 Confirming the link of the master station


Set the PLC inputs (X000 to X003) to ON or OFF in the master station, and confirm that the outputs G
(Y000 to Y003) turn ON or OFF in the slave station.

(FX2N-232IF)
Communication
Non-Protocol
Set the inputs X000 to
X003 to ON or OFF.
Slave station
H
Communication
Programming

Master station
Confirm that the outputs Y000 to Y003
of the slave station turn ON or OFF I
according to the inputs of the master
Maintenance
Remote

station.

Apx.A
models
Discontinued

C-35
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
Parallel Link 6.2 Creating Programs for the Communication Test

6 Confirming the link of the slave station


Set the PLC inputs (X000 to X003) to ON or OFF in the slave station, and confirm that the outputs
(Y000 to Y003) turn ON or OFF in the master station.
Set the inputs X000 to
X003 to ON or OFF.
Master station

Confirm that the outputs Y000 to Y003 Slave station


of the slave station turn ON or OFF
according to the inputs of the master
station.

If unable to establish link, refer to "9. Troubleshooting".

6.2 Creating Programs for the Communication Test


Create the programs shown below for the master station and slave station.

6.2.1 For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U or FX3UC Series

1. Program for communication test (for the master station)


Create the program shown below for the communication test. (This program is not required during actual
operation.)
M8000
0 M8070

MOV K500 D8070

M8000 (In the FX3G, FX3GC, FX3U and FX3UC)


8 M8178 This step is not required when using ch 1.
When using ch 2, set M8178 to ON.
M8000
11 MOV K1X000 K1M800

MOV K1M900 K1Y000

22 END

C-36
FX Series PLC User's Manual - Data Communication Edition 6 Test Run (Communication Test)
Parallel Link 6.2 Creating Programs for the Communication Test

A
2. Program for communication test (for the slave station)

Common Items
Create the program shown below for the communication test. (This program is not required during actual
operation.)
M8000
0 M8071
B

N:N Network
MOV K500 D8070

M8000 (In the FX3G, FX3GC, FX3U and FX3UC)


8 M8178 This step is not required when using ch 1.
When using ch 2, set M8178 to ON.

11
M8000
MOV K1X000 K1M900
C

Parallel Link
MOV K1M800 K1Y000

22 END
D

Computer Link
6.2.2 For FX0N, FX1S or FX3S Series

1. Master station communication test program


Create the program shown below for the communication test. (This program is not required during actual
operation.)
E

Communication
Inverter
M8000
0 M8070

MOV K500 D8070

M8000
F

(RS/RS2 Instruction)
Communication
Non-Protocol
8 MOV K1X000 K1M400

MOV K1M450 K1Y000

19 END G

(FX2N-232IF)
Communication
Non-Protocol
2. Slave station communication test program
Create the program shown below for the communication test. (This program is not required during actual
operation.)
M8000 H
0 M8071
Communication
Programming

MOV K500 D8070

M8000
8 K1X000 K1M450
MOV
I
Maintenance
Remote

MOV K1M400 K1Y000

19 END

Apx.A
models
Discontinued

C-37
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.1 Regular Parallel Link Mode

7. Creating Programs
The parallel link has two modes, regular parallel link mode and high speed parallel link mode.
Program settings and the number of device to be used are different in each mode.
When connecting FX PLCs in the parallel link, use the same mode in both PLCs.

7.1 Regular Parallel Link Mode


This section explains the program setting method in the regular parallel link mode.

7.1.1 Checking contents of related devices


The tables below show devices used in the parallel link.

1. Devices for setting the parallel link


These devices are used for setting the parallel link. The setting of these devices is essential to use the
parallel link.

Device Name Description


Parallel link master station
M8070 Set this device to ON when linking a PLC as the master station.
declare
Parallel link slave station
M8071 Set this device to ON when linking a PLC as the slave station.
setting
Set the channel of communication port to be used (in the FX3G,
FX3GC, FX3U and FX3UC).
M8178 Channel setting
When this device is OFF: ch1
When this device is ON: ch2
Set the time for judging error in the parallel link data communication.
D8070 Error judgement time (ms)
[Initial value: 500]

2. Devices for judging errors in the parallel link


These devices are used for judging errors in the parallel link. Use them to output link errors to the outside and
interlock sequence programs.

Device Name Description


M8072 Parallel link ON This device remains ON while the parallel link is executed.
Master/slave station setting This device turns ON when there is an error in the setting of the
M8073
error master station or slave station.
M8063 Link error This device turns ON when a communication error occurs.

C-38
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.1 Regular Parallel Link Mode

A
3. Link devices

Common Items
1) Sending devices for the master station
These devices are used for sending the information from the master station to the slave station.
To prevent malfunctions, do not change the setting of these devices in the slave station.
The device numbers used and number of devices vary depending on the PLC type. For applicable
devices, refer to the tables below. B
a) For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U or FX3UC Series

N:N Network
Number of
Device Description
devices
Bit device M800 to M899 100 The devices in the slave station are automatically updated
Word device D490 to D499 10 to the status of devices in the master station.
C
b) For FX0N, FX1S or FX3S Series

Parallel Link
Number of
Device Description
devices
Bit device M400 to M449 50 The devices in the slave station are automatically updated
Word device D230 to D239 10 to the status of devices in the master station.
D
2) Sending devices for the slave station

Computer Link
These devices are used for sending the information from the slave station to the master station.
To prevent malfunctions, do not change the setting of these devices in the master station.
The device numbers used and number of devices vary depending on the PLC type. For applicable
devices, refer to the tables below.
a) For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U or FX3UC Series E
Number of

Communication
Inverter
Device Description
devices
Bit device M900 to M999 100 The devices in the master station are automatically updated
Word device D500 to D509 10 to the status of devices in the slave station.

b) For FX0N, FX1S or FX3S Series F


Number of

(RS/RS2 Instruction)
Communication
Non-Protocol
Device Description
devices
Bit device M450 to M499 50 The devices in the master station are automatically updated
Word device D240 to D249 10 to the status of devices in the slave station.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-39
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.1 Regular Parallel Link Mode

7.1.2 Creating programs for master station


Create programs for the master station.
RUN monitor
Master station setting Program for setting the master station
M8000
M8070 M8070 is set to ON to set a PLC as the master station.

Channel setting
(In the FX3G, FX3GC, FX3U and FX3UC)
M8178 When using ch 1, this step is not required.
When using ch 2, set M8178 to ON".

Parallel link ON Program for indicating link errors


M8072
Y010 When the parallel link is interrupted or the setting is
Master/ defective, Y10 is set to ON.
slave station
setting error

M8073

RUN monitor Program for writing link devices (master station slave
M8000 station)
FNC 12 K1X000 Link device The information on X000 to X003 is written to link
MOV devices.
For PLC series other than the FX0N, FX1S or FX3S:
M800 to M899
X010 For FX0N, FX1S or FX3S Series: M400 to M449
C0
K100

FNC 12 C0 Link device The current value of C0 is written to link devices.


MOV
For PLC series other than the FX0N, FX1S or FX3S:
D490 to D499
For FX0N, FX1S or FX3S Series: D230 to D239

RUN monitor Program for reading link devices (slave station


M8000 master station)
FNC 12 Link device K1Y000 The information on link devices is read to Y000 to Y003.
MOV
For PLC series other than the FX0N, FX1S or FX3S:
M900 to M999
For FX0N, FX1S or FX3S Series: M450 to M499
FNC 12 Link device D10 The current value of link devices is read to D10, and
MOV
it is made the setting value of C1.
X010 For PLC series other than the FX0N, FX1S or FX3S:
D500 to D509
C1 For FX0N, FX1S or FX3S Series: D240 to D249
D10

C-40
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.1 Regular Parallel Link Mode

A
7.1.3 Creating programs for slave station

Common Items
Create programs for the slave station.
RUN monitor
Slave station setting Program for setting the slave station
M8000
M8071 M8071 is set to ON to set a PLC as the slave station. B

N:N Network
Channel setting
(In the FX3G, FX3GC, FX3U and FX3UC)
M8178 When using ch 1, this step is not required.
When using ch 2, set M8178 to ON".

Parallel link ON Program for indicating link errors C


M8072

Parallel Link
Y010 When the parallel link is interrupted or the setting is
Master/ defective, Y10 is set to ON.
slave station
setting error

M8073
D

Computer Link
RUN monitor Program for writing link devices (slave station master
M8000 station)
FNC 12 K1X000 Link device The information on X000 to X003 is written to link
MOV devices.
For PLC series other than the FX0N, FX1S or FX3S:
X010
M900 to M999
For FX0N, FX1S or FX3S Series: M450 to M499
E
C0

Communication
Inverter
K100

FNC 12 C0 Link device The current value of C0 is written to link devices.


MOV F
For PLC series other than the FX0N, FX1S or FX3S :

(RS/RS2 Instruction)
Communication
Non-Protocol
D500 to D509
For FX0N, FX1S or FX3S Series: D240 to D249

RUN monitor Program for reading link devices (master station


M8000 slave station)
FNC 12 Link device K1Y000 The information on link devices is read to Y000 to Y003.
MOV
For PLC series other than the FX0N, FX1S or FX3S:
G
M800 to M899

(FX2N-232IF)
Communication
Non-Protocol
For FX0N, FX1S or FX3S Series: M400 to M449
FNC 12 Link device D10 The current value of link devices is read to D10, and
MOV
it is made the setting value of C1.
X010 For PLC series other than the FX0N, FX1S or FX3S:
D490 to D499
C1
D10
For FX0N, FX1S or FX3S Series: D230 to D239
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-41
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.2 High Speed Parallel Link Mode

7.2 High Speed Parallel Link Mode


This section explains the program setting method in the high speed parallel link mode.

7.2.1 Checking contents of related devices


The tables below show devices used in the parallel link.

1. Devices for setting the parallel link


These devices are used for setting the parallel link. Setting of these devices is essential in using the parallel
link.

Device Name Description


Parallel link master station
M8070 Set this device to ON when linking a PLC as the master station.
declare
Parallel link slave station
M8071 Set this device to ON when linking a PLC as the slave station.
declare
High speed parallel link
M8162 Set this device to ON when using the high speed parallel link mode.
mode
Set the channel of communication port to be used (in the FX3G,
FX3GC, FX3U and FX3UC).
M8178 Channel setting
When this device is OFF: ch1
When this device is ON: ch2
Set the time for judging error in the parallel link data communication.
D8070 Error judgement time (ms)
[Initial value: 500]

2. Devices for judging errors in the parallel link


These devices are used for judging errors in the parallel link. Use them to output link errors to the outside and
interlock sequence programs.

Device Name Description


M8072 Parallel link ON This device remains ON while the parallel link is executed.
Master/slave station setting This device turns ON when there is an error in the setting of the
M8073
error master station or slave station.
M8063 Link error This device turns ON when a communication error occurs.

3. Link devices
1) Sending devices for the master station
These devices are used for sending the information from the master station to the slave station.
To prevent malfunctions, do not change the setting of these devices in the slave station.
The device numbers used and number of devices vary depending on the PLC type. For applicable
devices, refer to the tables below.
a) For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U or FX3UC Series

Number of
Device Description
devices
The devices in the slave station are automatically updated
Word device D490, D491 2
to the status of devices in the master station.
b) For FX0N, FX1S or FX3S Series

Number of
Device Description
devices
The devices in the slave station are automatically updated
Word device D230, D231 2
to the status of devices in the master station.

C-42
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.2 High Speed Parallel Link Mode

A
2) Sending devices for the slave station

Common Items
These devices are used for sending the information from the slave station to the master station.
To prevent malfunctions, do not change the setting of these devices in the master station.
The device numbers used and number of devices vary depending on the PLC type. For applicable
devices, refer to the tables below.
a) For FX2(FX), FX2C, FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U or FX3UC Series B

N:N Network
Number of
Device Description
devices
The devices in the master station are automatically updated
Word device D500, D501 2
to the status of devices in the slave station.
b) For FX0N, FX1S or FX3S Series C

Parallel Link
Number of
Device Description
devices
The devices in the master station are automatically updated
Word device D240, D241 2
to the status of devices in the slave station.

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-43
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.2 High Speed Parallel Link Mode

7.2.2 Creating programs for master station


Create programs for the master station.
RUN monitor
Master station setting Program for setting the master station
M8000
M8070 M8070 is set to ON to set a PLC as the master station.

High speed parallel


link mode
M8162 M8162 is set to ON to set the high speed parallel link
mode.

Channel setting
(In the FX3G, FX3GC, FX3U and FX3UC)
M8178 When using ch 1, this step is not required.
When using ch 2, set M8178 to ON".

Parallel link ON Program for indicating link errors


M8072
Y010 When the parallel link is interrupted or the setting is
Master/ defective, Y10 is set to ON.
slave station
setting error

M8073

RUN monitor Program for writing link devices (master station slave
M8000 station)
FNC 12 K1X000 Link device The information on X000 to X003 is written to link
MOV devices.
For PLC series other than the FX0N, FX1S or FX3S:
D490 and D491
X010 For FX0N, FX1S or FX3S Series: D230 and D231
C0
K100

FNC 12 C0 Link device The current value of C0 is written to link devices.


MOV
For PLC series other than the FX0N, FX1S or FX3S :
D490 and D491
For FX0N, FX1S or FX3S Series: D230 and D231

RUN monitor Program for reading link devices (slave station


M8000 master station)
FNC 12 Link device K1Y000 The information on link devices is read to Y000 to Y003.
MOV
For PLC series other than the FX0N, FX1S or FX3S:
D500 and D501
For FX0N, FX1S or FX3S Series: D240 and D241
FNC 12 Link device D10 The current value of link devices is read to D10, and
MOV
it is made the setting value of C1.
X010 For PLC series other than the FX0N, FX1S or FX3S:
D500 and D501
C1 For FX0N, FX1S or FX3S Series: D240 and D241
D10

C-44
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.2 High Speed Parallel Link Mode

A
7.2.3 Creating programs for slave station

Common Items
Create programs for the slave station.
RUN monitor
Slave station setting Program for setting the slave station
M8000
M8071 M8071 is set to ON to set a PLC as the slave station. B

N:N Network
High speed parallel
link mode
M8162 M8162 is set to ON to set the high speed parallel link
mode.

Channel setting
(In the FX3G, FX3GC, FX3U and FX3UC) C
M8178 When using ch 1, this step is not required.

Parallel Link
When using ch 2, set M8178 to ON".

Parallel link ON Program for indicating link errors


M8072
Y010 When the parallel link is interrupted or the setting is
Master/
slave station
setting error
defective, Y10 is set to ON.
D

Computer Link
M8073

RUN monitor Program for writing link devices (slave station master
M8000
FNC 12
station) E
K1X000 Link device The information on X000 to X003 is written to link

Communication
Inverter
MOV devices.
For PLC series other than the FX0N, FX1S or FX3S:
D500 and D501
X010 For FX0N, FX1S or FX3S Series: D240 and D241
C0
K100 F

(RS/RS2 Instruction)
Communication
Non-Protocol
FNC 12 C0 Link device The current value of C0 is written to link devices.
MOV
For PLC series other than the FX0N, FX1S or FX3S:
D500 and D501
For FX0N, FX1S or FX3S Series: D240 and D241
G
RUN monitor Program for reading link devices (master station

(FX2N-232IF)
Communication
Non-Protocol
M8000 slave station)
FNC 12 Link device K1Y000 The information on link devices is read to Y000 to Y003.
MOV
For PLC series other than the FX0N, FX1S or FX3S:
D490 and D491
FNC 12
MOV
Link device D10
For FX0N, FX1S or FX3S Series: D230 and D231
The current value of link devices is read to D10, and H
it is made the setting value of C1.
Communication
Programming

X010 For PLC series other than the FX0N, FX1S or FX3S:
D490 and D491
C1 For FX0N, FX1S or FX3S Series: D230 and D231
D10

I
Maintenance
Remote

Apx.A
models
Discontinued

C-45
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs
Parallel Link 7.3 Cautions on Program Creation

7.3 Cautions on Program Creation

1. Program for reading link devices


1) Do not change the contents of link devices for the other station.
2) When a link error occurs, the link device information remains the same as the status just before the error.
Create a fail-safe program which does not cause abnormality even if a link error occurs.

2. Cautions on using FX3G, FX3GC, FX3U, FX3UC PLCs


1) Only ch1 or ch2 can be set in the parallel link.
2) Do not use the N:N Network and the parallel link at the same time.
(For example, it is not allowed to use ch1 for the N:N Network and simultaneously use ch2 for the parallel
link.)

C-46
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
Parallel Link 8.1 Practical Example 1 (Regular Parallel Link Mode)

Common Items
8. Practical Program Examples
This chapter shows practical programs examples. B

N:N Network
8.1 Practical Example 1 (Regular Parallel Link Mode)
When many link devices are required, use the regular parallel link mode.
C
8.1.1 System configuration example

Parallel Link
The example below shows a system configuration in which two FX2N PLCs are linked.
FX2N PLC FX2N PLC

Computer Link
FX2N-485-BD FX2N-485-BD

Master station Slave station


E

Communication
Inverter
- Link range: 100-bit devices and 10-word devices (regular parallel link mode)
- Error judgement time: 500 ms

8.1.2 Setting contents


F
The program examples shown later adopt the following communication parameters:

(RS/RS2 Instruction)
Communication
Non-Protocol
Device Description
M8070 Parallel link master station setting
M8071 Parallel link slave station setting
D8070 Communication error judgement time
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-47
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples
Parallel Link 8.1 Practical Example 1 (Regular Parallel Link Mode)

8.1.3 Program for master station


For the master station, refer to the program shown below.
RUN monitor
M8000
M8070

RUN monitor
M8000 The ON/OFF status of inputs X000 to X007 in the master
FNC 12 K2X000 K2M800
MOV station is output to Y000 to Y007 in the slave station.

FNC 20 When the calculation result (D0 + D2) in the master


D0 D2 D490 station is moved to D490 of the slave station.
ADD

FNC 12 The ON/OFF status of M0 to M7 in the slave station is


K2M900 K2Y000 output to Y000 to Y007 in the master station.
MOV

X010
The value of D10 in the slave station is stored to the timer
T0 setting (T0) in the master station.
D500

8.1.4 Program for slave station


For the slave station, refer to the program shown below.
RUN monitor
M8000
M8071

RUN monitor
M8000
FNC 12 K2M800 K2Y000 The ON/OFF status of inputs X000 to X007 in the master
MOV station is output to Y000 to Y007 in the slave station.

When the calculation result (D0 + D2) in the master


FNC 10 D490 K100 M10 station is 100 or less, Y010 is set to ON in the slave
CMP station.

M10
Y010

FNC 12 The ON/OFF status of M0 to M7 in the slave station is


K2M0 K2M900 output to Y000 to Y007 in the master station.
MOV

X010
FNC 12 The value of D10 in the slave station stored to the timer
D10 D500 setting (T0) in the master station.
MOV

C-48
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
Parallel Link 9.1 Checking FX PLC Version Applicability

Common Items
9. Troubleshooting
This chapter explains troubleshooting. B

N:N Network
9.1 Checking FX PLC Version Applicability
Verify that the FX PLC main unit is an applicable version.
For the version applicability check, refer to Section 1.3.
C

Parallel Link
9.2 Checking Communication Status Based on LED Indication
Check the status of the "RD" and "SD" indicator LEDs provided in the optional equipment.

LED status
Operation status
D
RD SD

Computer Link
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received.
Off Off Data is not sent or received. E
While the parallel link is executed normally, both LEDs flash brightly.

Communication
Inverter
If they do not flash, check the wiring and the communication setting in the master and slave stations.

9.3 Checking Installation and Wiring


F
1. Mounting status

(RS/RS2 Instruction)
Communication
Non-Protocol
If the communication equipment is not securely connected to the PLC, communication is not possible.
For the mounting method, refer to the respective communication equipment manual.

2. Power supply (for FX0N-485ADP)


The FX0N-485ADP requires a driving power supply. Verify that the power supply is correctly provided. G

(FX2N-232IF)
Communication
Non-Protocol
3. Wiring
Verify that the wiring to all communication equipment is correct. If the communication equipment is wired
incorrectly, communication is not possible.
For wiring method check, refer to Chapter 4.

H
9.4 Checking Sequence Program
Communication
Programming

1. Communication setting in the sequence program


Verify that N:N Network (D8173 to D8180) is not set. Using both the parallel link and N:N Network at the same
time is not allowed.
Verify that the communication format (D8120, D8400 and D8420) is set correctly. Communication is not I
possible if a communication port is set twice or more.
Maintenance
Remote

After changing any setting, make sure to cycle power to the PLC.
For communication setting, refer to Chapter 5.
2. Communication setting using parameters
Verify that the communication settings using parameters are suitable for use. If the communication settings
are not suitable for the purpose of use, communication will not function correctly. Apx.A
After changing any setting, make sure to reboot the PLCs power.
models
Discontinued

For communication setting, refer to Chapter 5.

C-49
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
Parallel Link 9.4 Checking Sequence Program

3. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in parallel link.
After changing the setting, make sure to reboot the PLC's power.
4. Presence of VRRD and VRSC instructions
1) Except FX3G, FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, reboot the PLCs power.
2) In FX3G PLC
- In the case of the 14 points and 24-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, reboot the PLC's power.
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions.
After deleting these instructions, reboot the PLC's power.
3) In FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power.
5. Presence of RS instruction (except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS instruction is not used in the program.
If this instruction is used, delete it, reboot the PLCs power.
6. Presence of RS and RS2 instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.
7. Presence of EXTR instruction (in FX2N and FX2NC PLCs)
Verify that the EXTR instruction is not used in the program.
If this instruction is used, delete it, then reboot the PLCs power.

8. Presence of IVCK, IVDR, IVRD, IVWR, IVBWR*1, and IVMC instructions (in FX3S, FX3G,
FX3GC, FX3U and FX3UC PLCs)
Verify that the IVCK, IVDR, IVRD, IVWR, IVBWR and IVMC instructions are not being used for the same
channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.
*1. Only available for FX3U and FX3UC PLCs.
9. Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.

10.Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and
FX3UC PLCs)
Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the
same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.

C-50
FX Series PLC User's Manual - Data Communication Edition 9 Troubleshooting
Parallel Link 9.5 Checking Absence/Presence of Errors

A
9.5 Checking Absence/Presence of Errors

Common Items
Verify that errors have not occurred in the master station and slave station. Errors can be checked using the
flags shown below.
1. Checking the device M8072
While the parallel link is established, M8072 remains ON.
B

N:N Network
If M8072 is OFF, an error has occurred in the parallel link setting or communication.
2. Checking the device M8073
If the parallel link is not set correctly, M8073 turns ON.
If M8073 is ON, verify that the master station and slave station are set correctly in sequence programs.
3. Devices for checking link errors C

Parallel Link
1) Checking the error flags M8063 and M8438 (in the FX3G, FX3GC, FX3U and FX3UC)
If a communication error occurs in the parallel link, the serial communication error flag turns ON.
When ch1 is used, M8063 turns ON. When ch2 is used in the FX3G, FX3GC, FX3U and FX3UC, M8438
turns ON.
When the serial communication error flag turns ON, the error code is stored in D8063 or D8438.
2) Checking the error code
D

Computer Link
When a communication error occurs in parallel link using ch 1, the error code is stored in D8063.
When a communication error occurs in parallel link using ch 2, the error code is stored in D8438.
The table below shows the details of error codes.
Device Error code Description Action
0000 No error E
6312 Character error in parallel link

Communication
Inverter
D8063
6313 Sum check error in parallel link
Verify that the parallel link
6314 Format error in parallel link setting programs are set
0000 No error correctly. Check the wiring
D8438 also.
3812 Character error in parallel link
(in FX3G, FX3GC, FX3U and
3813 Sum check error in parallel link
F
FX3UC)

(RS/RS2 Instruction)
Communication
Non-Protocol
3814 Format error in parallel link

Caution
The devices for checking link errors are not cleared even after communication errors are reset.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
G

(FX2N-232IF)
Communication
Non-Protocol
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

C-51
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
Parallel Link 10.1 Related Device List

10. Related Data

10.1 Related Device List

1. Bit devices

Device Initial Detec-


Name Description R/W
number value tion
Devices for communication setting
Parallel link master
M8070 Links a PLC as the master station when it turns ON. M W
station setting
Parallel link slave
M8071 Links a PLC as the slave station when it turns ON. L W
station setting
High speed parallel Turns ON when two-word device communication
M8162 M, L W
link mode mode is selected.
Sets the communication port to be used. (in the FX3G,
M8178 Channel setting FX3GC, FX3U and FX3UC) M, L W
OFF: ch1, ON: ch2
Devices for checking communication status
M8072 Parallel link ON Remains ON while the parallel link is being executed. M, L R
Parallel link setting Turns ON when an error is included in the setting
M8073 M, L R
error contents of the master station or slave station.
Serial communication Turns ON when an error occurs in serial
M8063 M, L R
error 1 (ch 1) communication using ch 1.
Turns ON when an error occurs in serial
Serial communication
M8438 communication using ch 2. (in the FX3G, FX3GC, FX3U M, L R
error 2 (ch 2)
and FX3UC)
R: Read only (used as a contact in program)
W: Write only
M: Master station
L: Slave station

2. Word devices (data registers)

Device Initial Detec-


Name Description R/W
number value tion
Devices for communication setting
Sets the error judgement time for data
D8070 Error judgement time 500 M, L W
communication in the parallel link.
Devices for checking communication status
Serial communication Stores the error code when an error occurs in serial
D8063 0000 M, L R
error code 1 (ch 1) communication using ch 1.
Stores the error code when an error occurs in serial
Serial communication
D8438 communication using ch 2. (in the FX3G, FX3GC, FX3U 0000 M, L R
error code 2 (ch 2)
and FX3UC)
Devices for checking
Operation mode Stores the communication type being used by
D8419 M, L R
display (ch 1) ch 1. (in the FX3S, FX3G, FX3GC, FX3U and FX3UC)
Operation mode Stores the communication type being used by
D8439 M, L R
display (ch 2) ch 2. (in the FX3G, FX3GC, FX3U and FX3UC)
R: Read only
W: Write only
M: Master station
L: Slave station

C-52
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
Parallel Link 10.2 Details of Related Devices

A
10.2 Details of Related Devices

Common Items
The devices described below are used in parallel link.

10.2.1 Parallel link master station declare [M8070]


B
When this device is set to ON, the PLC is handled as the master station in the parallel link.

N:N Network
1. Applicable stations
The master station requires program setting.

2. Detailed contents
In the FX PLC to be handled as the master station, set M8070 to "normally ON" using M8000.
C

Parallel Link
3. Cautions on use
Set this device to ON in a sequence program.

10.2.2 Channel setting [M8178]


D
This device works as the channel setting flag (in the FX3G, FX3GC, FX3U and FX3UC).

Computer Link
1. Applicable stations
The master and slave station require program setting.

2. Detailed contents
When using ch 2 as the communication port, set this device to ON in the sequence program.
E

Communication
Inverter
When using ch 1, the sequence program is not required.

10.2.3 Parallel link slave station declare [M8071]


When this device is set to ON, the PLC is handled as the slave station in the started communication.
F
1. Applicable stations

(RS/RS2 Instruction)
Communication
Non-Protocol
The slave station requires program setting.

2. Detailed contents
In the FX PLC to be handled as a slave station, set M8071 to "normally ON" using M8000.

3. Cautions on use G

(FX2N-232IF)
Communication
Non-Protocol
Set this device to ON using a sequence program.

10.2.4 High-speed parallel link mode [M8162]


When M8162 turns OFF, the regular parallel link mode is selected. When M8162 turns ON, the high-speed
parallel link mode is selected. H
Communication
Programming

1. Applicable stations
The master and slave station require program setting.

2. Detailed contents
The table below shows the number of link devices.
I
Maintenance
Remote

Regular parallel link mode High-speed parallel link mode


PLC
Bit device (M) Word device (D) Bit device (M) Word device (D)
FX2(FX), FX2C, FX1N, FX1NC,
FX2N, FX2NC, FX3G, FX3GC, 100 in each station 10 in each station 0 2 in each station
FX3U, FX3UC
FX0N, FX1S, FX3S 50 in each station 10 in each station 0 2 in each station
Apx.A
models
Discontinued

3. Cautions on use
Set this device to ON using a sequence program.

C-53
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
Parallel Link 10.2 Details of Related Devices

10.2.5 Parallel link ON [M8072]


This device is provided to verify that the parallel link is being executed.

1. Applicable stations
The master and slave station may check parallel link status.

2. Detailed contents
M8072 remains ON while the parallel link is being executed normally, and remains OFF while the parallel link
is not being executed normally.

10.2.6 Parallel link setting error [M8073]


This device is provided to verify that the setting is correct in the master station and slave station in the parallel
link.

1. Applicable stations
The master and slave station may check parallel link status.

2. Detailed contents
M8073 remains OFF when the setting is correct in the master station or slave station, and turns ON when the
setting is incorrect.

10.2.7 Serial communication error [M8063 and M8438]


These devices are provided to check communication errors. (M8438 is available only in the FX3G, FX3GC,
FX3U and FX3UC.)

1. Applicable stations
The master and slave station may check parallel link status.

2. Detailed contents
M8063 turns ON when an error occurs using parallel link on ch 1. When M8063 turns ON, the error code is
stored in D8063.
M8438 turns ON when an error occurs using parallel link on ch 2. When M8438 turns ON, the error code is
stored in D8438.

3. Cautions on use
Do not set these devices to ON using a program or programming tool.
Serial communication errors are not cleared even when communication is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

10.2.8 Error judgement time setting [D8070]


This device is provided to set the error judgment time (initial value: 500 ms).

1. Applicable stations
The master and slave station may check parallel link status.

2. Detailed contents
When data transmission requires more time than the time set here, it is regarded as error.

3. Cautions on use
Set the error judgment time for the master station to a value twice or more the scan time in the slave station.
If the error judgment time is less than twice the scan time, a serial communication error may occur.

C-54
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
Parallel Link 10.2 Details of Related Devices

A
10.2.9 Serial communication error code [D8063 and D8438]

Common Items
These devices store the serial communication error code. (D8438 is available only in the FX3G, FX3GC, FX3U
and FX3UC.)

1. Applicable stations
The master and slave station may check the serial communication error code.
B

N:N Network
2. Detailed contents
The table below shows the details of error codes.
Device Error code Description Action
0000
6312
No error
Character error in parallel link
C
D8063

Parallel Link
(ch 1) 6313 Sum check error in parallel link
Verify that the parallel link
6314 Format error in parallel link setting programs are
0000 No error correct, and check the wiring
also.
D8438 3812 Character error in parallel link
(ch 2) 3813 Sum check error in parallel link D

Computer Link
3814 Format error in parallel link

3. Cautions on use
Do not set this device to ON using a program or programming tool.
Serial communication errors code are not cleared even when communication is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is E
turned off and on.

Communication
Inverter
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

10.2.10 Operation mode display [D8419 and D8439]


F
These devices store the communication type being used. (in the FX3S, FX3G, FX3GC, FX3U and FX3UC)

(RS/RS2 Instruction)
Communication
Non-Protocol
1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.
G
The table below shows the contents of the communication type codes.

(FX2N-232IF)
Communication
Non-Protocol
Code Description
0 Programming communication
1 PP modem mode
2 Protocol dedicated to computer link H
3 N:N Network
Communication
Programming

4 RS instruction
5 RS2 instruction
6 Parallel link
7
8
Inverter instruction
Variable analog potentiometer expansion board is used.
I
Maintenance
Remote

9 MODBUS communication
10 CF-ADP
11 ENET-ADP
12 Input/output expansion board is used.
Apx.A
models
Discontinued

C-55
FX Series PLC User's Manual - Data Communication Edition 10 Related Data
Parallel Link 10.2 Details of Related Devices

MEMO

C-56
FX Series PLC User's Manual - Data Communication Edition
Computer Link

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
D. Computer Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains "computer link" provided for the MELSEC-F FX Series Programmable Controllers and
Maintenance
Remote

should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

D-1
FX Series PLC User's Manual - Data Communication Edition
Computer Link

D-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Computer Link 1.1 Outline of System

Common Items
1. Outline
This chapter explains computer link. B

N:N Network
1.1 Outline of System
Computer link allows connection of up to sixteen FX PLCs and A PLCs to a personal computer working as the
master station to link data.
C
1) Up to sixteen PLCs can be connected in computer link.

Parallel Link
2) Applicable computer link protocols are the same as dedicated supported computer link protocols units in
the A Series PLC. (But the supported formats and commands are limited.)

Important points and reference


System chapter/section
D
In the case of RS-485 16 units

Computer Link
....... Number of linked units
500 m (1640' 5") [50 m (164' 0") when 485BD is used] ....... Total extension distance
For the specifications,
Personal computer FX PLC FX PLC refer to Chapter 2.
Station No. 0 (00H) Station No. 15 (0FH)
E
To check applicable PLC

Communication
Inverter
... .......
models, refer to Section 1.3.

+ +
Communication Communication
FX-485PC-IF
equipment operating equipment operating For selection,
in accordance with
RS-485
in accordance with
RS-485
.......
refer to Chapter 3. F

(RS/RS2 Instruction)
Communication
Non-Protocol
.......
For wiring,
refer to Chapter 4.

In the case of RS-232C


15 m (49' 2")
G
Personal computer FX PLC

(FX2N-232IF)
Communication
Non-Protocol
Station No. 0 (00H)

+ H
Communication
Communication
Programming

equipment operating
in accordance with
RS-232C

The number of devices handled all at once varies depending on the command and the types of devices.
I
Maintenance
Remote

Apx.A
models
Discontinued

D-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Computer Link 1.2 Procedures Before Operation

1.2 Procedures Before Operation


The flow chart below shows the Computer Link setting procedures up until data link.

Computer link

Refer to Chapter 1.

Outline Outline of system


Applicable PLC versions
Applicable programming tools
Refer to Chapter 2.

Check communication specifications. Communication specifications


Link time
Number of devices
Refer to Chapter 3.

Determine system configuration and selection. System configuration


Select communication equipment.
Refer to Chapter 4.

Perform wiring. Wiring procedure


Wiring example

Programming tool

Connect PLC*1

Refer to Chapter 5.

Perform PLC communication setting. PLC serial communication setting


Communication setting

Refer to Chapter 6.

Computer link Computer link


Dedicated protocol format
Transfer sequence time chart and
Refer to Chapter 7. communication time

Commands Commands
Applicable command list
Specification method
Based on SD/RD lamp lighting status and On-demand function
contents of error check devices, verify that
communication is being executed normally.
If there are problems, refer to the troubleshooting
(Chapter 8).

*1 For the programming tool to PLC connection procedure, refer to the "Programming Communication" section in this
manual or the respective programming tool manual.
For details on operating procedures, refer to the respective programming tool manual.

D-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Computer Link 1.3 Communication Type Applicability in PLC

A
1.3 Communication Type Applicability in PLC

Common Items
1.3.1 Applicable versions
The communication type is applicable in the following versions. B
: Applicable (If applicable versions of main units are limited, they are described inside ( ).)

N:N Network
: Not applicable
PLC Applicability (applicable version) Remarks
FX3UC Series
FX3U Series
FX3GC Series
C

Parallel Link
FX3G Series
FX3S Series
FX2NC Series
FX2N Series (Ver. 1.06 or later) The version can be checked by monitoring D8001.
FX1NC Series D
FX1N Series

Computer Link

FX1S Series
FX0N Series (Ver. 1.20 or later) The version can be checked by monitoring D8001.
FX0S Series Computer link is not provided.
FX0 Series Computer link is not provided. E
FX2C Series (Ver. 3.30 or later)*1

Communication
Inverter
FX2(FX) Series (Ver. 3.30 or later)*1
FX1 Series Computer link is not provided.

*1. Applicable in products manufactured in June, 1996 and later (manufacturers serial No.: 66**** and
later). F

(RS/RS2 Instruction)
Communication
Non-Protocol
1.3.2 Version check
The PLC version can be checked by reading the last three digits of device D8001.
For a detailed description of the version check, refer to A. Common Items Section 4.2.
G
1.3.3 How to look at the manufacturer's serial number

(FX2N-232IF)
Communication
Non-Protocol
The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT"
indicated on the front of the product.
For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Section 4.1.
H
1.3.4 Products whose production was stopped
Communication
Programming

Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A.
To see the latest available products, refer to the general catalog.
I
Maintenance
Remote

Apx.A
models
Discontinued

D-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Computer Link 1.4 Programming Tool Applicability

1.4 Programming Tool Applicability

1.4.1 For applicable versions


The programming tool is applicable for each FX Series from the following version shown:

1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30PSWDNC-GXW2-E Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 3.00 or later
FX-20P-MFXC-E
FX-10P-E Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW5 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 4.00 or later
FX-20P-MFXD-E
FX-10P-E Ver. 4.00 or later

D-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Computer Link 1.4 Programming Tool Applicability

A
Product name Model name Applicable version Remarks

Common Items
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later) B
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units

N:N Network
models and versions supporting the list editor function.

2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs C
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later

Parallel Link
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
D

Computer Link
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. E

Communication
Inverter
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. F
FX3S PLC

(RS/RS2 Instruction)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
G

(FX2N-232IF)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW2 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.00 or later
FX-PCS-KIT/98 SW1PC-FXGP/98(-3,-5) Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 4.00 or later
H
Communication
Programming

FX-PCS-KIT/V-3 SW1PC-FXGP/V3 Ver. 2.00 or later -


FX-A7PHP-KIT SW1RX-GPPFX Ver. 3.00 or later
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
FX-20P-MFXC
Ver. 4.00 or later
I
Maintenance
Remote

FX-10P(-SET0) Ver. 3.00 or later


GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later) Apx.A
Refer to manuals of GOT1000 Series display units for applicable
models
Discontinued

GOT1000 Series display units


models and versions supporting the list editor function.

D-7
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Computer Link 1.4 Programming Tool Applicability

Product name Model name Applicable version Remarks


FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 5.00 or later
-
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 5.00 or later
FX-20P-MFXD
FX-10P(-SET0) Ver. 4.00 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

1.4.2 For non-applicable versions (setting an alternative model)


Even programming tool not applicable to a PLC can create programs when an alternative model is set.
In this case, however, programming is enabled only in the function ranges provided for the alternative PLC
model such as instructions and program size.

Model to be programmed Model to be set Priority: High Low


FX3UC Series FX3UC FX2N FX2(FX)
FX3U Series FX3U, FX3UC FX2N FX2(FX)
FX3GC Series FX3G, FX3GC FX1N*1 FX2N*1
FX3G Series FX3G FX1N*1 FX2N*1
FX3S Series FX3S FX3G FX1N*1
FX2NC Series FX2NC, FX2N FX2(FX)
FX2N Series FX2N FX2(FX)
FX1NC Series FX1NC, FX1N FX2N FX2(FX)
FX1N Series FX1N FX2N FX2(FX)
FX1S Series FX1S FX2(FX)
FX0N Series FX0N FX2(FX)
FX0S Series FX0S FX2(FX)
FX0 Series FX0 FX2(FX)
FX2C Series FX2C, FX2(FX) FX2(FX)
FX2(FX) Series FX2(FX)
FX1 Series FX1

*1. "FX2N" is selected when the FX-10P(-E) is used.

Point
In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

D-8
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Computer Link 2.1 Communication Specifications (Reference)

Common Items
2. Specifications
This chapter explains the communication specifications and performance. B

N:N Network
2.1 Communication Specifications (Reference)
Communication is executed within the specifications shown in the table below. The baud rate, etc. can be
changed in the parameter settings of a programming tool or in a sequence program.
C

Parallel Link
Item Specifications Remarks
Number of connectable units 16 maximum
Transmission standard RS-485 or RS-232C standard
RS-485: 500 m (1640' 5") or less
Maximum total extension
distance
[50 m (164' 0") or less when 485BD is
included in system]
Distance varies depending
on communication equipment type.
D

Computer Link
RS-232C: 15 m (49' 2") or less
Protocol type Computer link (dedicated protocol) Formats 1 and 4 are applicable.
Control procedure
Communication method Half-duplex, bidirectional communication
300, 600, 1200, 2400, 4800, 9600, 19200 or E
Baud rate *1

Communication
Inverter
38400 bps
Start bit Fixed
Character Data bit 7 or 8-bit
format Parity bit None, odd or even
Stop bit 1 or 2-bit F
Header Fixed

(RS/RS2 Instruction)
Communication
Non-Protocol
Terminator Fixed
Control line Fixed
Sum check Provided or not provided

*1. FX3U and FX3UC Series PLC Ver. 2.41 or later, and FX3S, FX3G, FX3GC Series PLC is applicable. G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-9
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Computer Link 2.2 Link Specifications

2.2 Link Specifications

2.2.1 Applicable commands and number of device points

Number of points processed in


Command
one-time update
Name Contents of processing FX2(FX),
FX3S,
Sym- ASCII FX2C,
FX0N, FX1S FX3G, FX3GC,
bol code FX1N, FX1NC,
FX3U, FX3UC
FX2N, FX2NC
Unit:
BR 42H, 52H Reads bit devices in 1 point units. 54 256 256
Bit
13 words 32 words 32 words
Reads bit devices in 16 point units.
WR 57H, 52H 208 points 512 points 512 points
Batch
reading Unit: Read word devices in 1 point units. 13*4 64*2 64*2
Word 32 words
Reads bit devices in 16 point units.
512 points
QR*1 51H, 52H
Read word devices in 1 point units. 64*2
Unit:
BW 42H, 57H Writes bit devices in 1 point units. 46 160 160
Bit
10 words 10 words 10 words
Device memory

Writes bit devices in 16 point units.


WW 57H, 57H 160 points 160 points 160 points
Batch
writing Unit: Writes word devices in 1 point units. 11*5 64*2 64*2
Word 10 words
Writes bit devices in 16 point units.
*1 51H, 57H 160 points
QW
Writes word devices in 1 point units. 64*2
Unit: Specifies bit devices arbitrarily in 1
BT 42H, 54H 10 20 20
Bit point units, and sets or resets them.
Specifies bit devices arbitrarily in 16 6 words 10 words 10 words
point units, and sets or resets them. 96 points 160 points 160 points
Test WT 57H, 54H
Specifies word devices arbitrarily in 1
(random
point units, and writes them. 6*3 10*3 10*3
writing) Unit:
Word Specifies bit devices arbitrarily in 16 10 words

point units, and sets or resets them. 160 points
QT*1 51H, 54H
Specifies word devices arbitrarily in 1
point units, and writes them.
10*3

Remote RUN RR 52H, 52H Requests remote RUN or remote


Remote STOP RS 52H, 53H STOP to PLC.
PLC


PLC model
PC 50H, 43H Reads PLC model name.
name reading
Turns global signal ON or OFF
Global GW 47H, 57H (M8126 in FX Series) in all PLCs 1 1 1
connected in computer link.
Maximum Maximum Maximum
quantity quantity quantity
Set the sending request flag to ON in
specified in specified in specified in
On-demand PLC (only when 1-to-1 connection is
sequence sequence sequence
adopted in system configuration).
program: program: program:
13 words 64 words 64 words
Returns received characters back to 25 254 254
Loop-back test TT 54H, 54H
the computer as they are. characters characters characters
*1. Available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.
*2. 32 points when 32-bit counters (C200 to C255) are specified.
*3. 32-bit counters (C200 to C255) are not applicable.
*4. 6 points when 32-bit counters (C200 to C255) are specified.
*5. 5 points when 32-bit counters (C200 to C255) are specified.

D-10
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Computer Link 2.2 Link Specifications

A
2.2.2 Applicable device ranges

Common Items
The tables below show devices and device number ranges applicable for the device memory access.
Construct each of the BR, BW, BT, WR, WW, and WT commands in five characters.
Device + Device number = 5 characters
1 character 4 characters
B

N:N Network
2 characters for timer or counter 3 characters for timer or counter

Construct each of the QR, QW, and QT commands in seven characters.


Device + Device number = 7 characters
1 character
2 characters for timer or counter
6 characters
5 characters for timer or counter
C

Parallel Link
1. Bit devices
FX PLCs do not support timer coils (TC) and counter coils (CC).
Device Available
Device number range (character)
Device
number commands
expression BR, WR, QR,
D
FX2(FX), FX1N, FX2N, FX3G, FX3U,

Computer Link
FX1S FX0N FX3S Decimal/ BW, WW, QW,
FX2C FX1NC FX2NC FX3GC FX3UC Octal BT WT QT
X0000 X0000 X0000 X0000 X0000 X0000 X0000
X0000 to
to to to to to to to
Input X0267
X0017 X0177 X0177 X0337 X0017 X0177 X0377
relay
(X)

X000000 X000000 X000000
to to to E
X000017 X000177 X000377

Communication
Inverter
Octal
Y0000 Y0000 Y0000 Y0000 Y0000 Y0000 Y0000
Y0000 to
to to to to to to to
Output Y0267
Y0015 Y0177 Y0177 Y0337 Y0015 Y0177 Y0377
relay
(Y) Y000000 Y000000 Y000000
to to to
Y000015 Y000177 Y000377 F
M0000 M0000

(RS/RS2 Instruction)
Communication
Non-Protocol
Auxil- M0000 to M0511 M0000 to M1535 to to M0000 to M7679
iary M3071 M1535
relay M000000
(M) M000000 to
to
M007679
M001535

S0000 to S0127 S0000 to S0999


S0000
to S0000 to S4095
G
State S0255

(FX2N-232IF)
Communication
Non-Protocol
relay
(S) S000000
S000000 to
to
S004095
S000255
Special M8000 to M8254 M8000 to M8255 M8000 to M8511
auxiliary
relay M008000 to M008511 H
(M)
Communication
Programming

TS000 to TS000 to TS000 to Decimal


TS000 to TS063 TS000 to TS255
Timer TS137 TS319 TS511
contact TS00000 TS00000 TS00000
(T) to to to
TS00137 TS00319 TS00511
CS000 CS000 CS000 I
to to to
Maintenance
Remote

CS031 CS031 CS031


CS000 to CS255 CS000 to CS255
CS235 CS235 CS200
to to to
Counter CS255 CS254 CS255
contact
(C) CS00000
to
CS00031 CS00000 to Apx.A

CS00200 CS00255
models
Discontinued

to
CS00255

D-11
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Computer Link 2.2 Link Specifications

2. Word devices

Device Available
Device number range (character)
number commands
Device expression BR, WR, QR,
FX2(FX), FX1N, FX2N, FX3G, FX3U,
FX1S FX0N FX3S Decimal/ BW, WW, QW,
FX2C FX1NC FX2NC FX3GC FX3UC
Octal BT WT QT
TN000 TN000 TN000
Timer TN000 to
TN000 to TN255 to to to
TN063
current TN137 TN319 TN511
value TN00000 TN00000 TN00000
(T) to to to
TN00137 TN00319 TN00511
CN000 CN000 CN000
to to to
CN031 CN031 CN031
CN235 CN235
CN000 to CN255
CN200
CN000 to CN255 *1
Counter to to to
current CN255 CN254 CN255
value CN00000
(C) to
CN00031 CN00000 to

CN00200 CN00255
*1
to
CN00255
D0000 D0000
D0000 to D0000 to
to to D0000 to D7999
Data D0255 D7999
D0999 D2999 Decimal
register
D000000
(D) D000000 to
to
D007999
D002999
D1000 D1000
File
to to
register D2499 D2999
(D)

RAM D6000
file to
register D7999
(D)
Exten- R0000 to R9999
sion R000000 R000000
register to to
(R) R023999 R032767
Special D8000 to
D8000 to D8255 D8000 to D8511
data D8255
register
D008000 to D008511
(D)
*1. The WT and QT commands do not support 32-bit counters (C200 to C255).

Caution
1) When using bit devices in a command requiring specification in 1-word units, make sure that the head
device number is a multiple of "8".
2) Special auxiliary relays and special data registers are classified into ones for read only, write only and
ones for system only.
If data is written to any range in which writing is not allowed, an error may occur in the PLC.
For details on special auxiliary relays and special data registers, refer to the manual of the PLC.
3) In FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the PLCs cannot
access the program area (in the built-in RAM, memory cassette and built-in EEPROM) when users set file
registers (D).
In FX 3U and FX3UC PLCs, extension registers (R) cannot access extension file registers (ER) in a
mounted memory cassette.
In FX3G, FX3GC PLCs, extension registers (R) cannot access extension file registers (ER).

D-12
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Computer Link 2.2 Link Specifications

A
2.2.3 Link time

Common Items
1. Data transfer
Data transfer Data transfer
Interval time B

N:N Network
2. Data transfer time
Time to read continuous word devices (timers, counters or data registers) in one station = (21*1 + 4 Number
of read points*2) Time to send or receive 1 character (ms) + Interval time + Maximum scan time (special
data register D8012) in PLC 3 + Message waiting time
C
Time to write continuous word devices (timers, counters or data registers) in one station = (20*1 + 4 Number

Parallel Link
of written points*2) Time to send or receive 1 character (ms) + Interval time + Maximum scan time (special
data register D8012) in PLC + Message waiting time
*1. This is the number of characters when the protocol format 1 is used and the sum check is not
provided.
When the protocol format 4 is used, add "4" to this value. D
When the sum check is provided, add "4" to this value also.

Computer Link
*2. The number of points is counted in 1-word units.

3. Time to send or receive one character


The table below shows the time required to send or receive one character when the start bit is 1-bit, the data
length is 7-bit, the parity is 1-bit, and the stop bit is 1-bit.
E
Transmission speed (baud rate) (bps) Time to send or receive 1 character (ms)

Communication
Inverter
300 33.34
600 16.67
1200 8.34
2400 4.17
4800 2.08 F
9600 1.04

(RS/RS2 Instruction)
Communication
Non-Protocol
19200 0.52
38400*3 0.26

The tables below show the data transfer times depending on the number of continuously read or written word
devices at the transmission speeds of 9600 bps and 19200 bps when the message waiting time is 0 ms*4, the G
maximum scan time is 20 ms, and the interval time is 100 ms.

(FX2N-232IF)
Communication
Non-Protocol
<When the transmission speed is 9600 bps> Unit : sec <When the transmission speed is 19200 bps> Unit : sec
Number of Number of stations Number of Number of stations
data points 1 8 16 data points 1 8 16
10
32
0.3
0.4
1.9
2.6
3.7
5.2
10
32
0.2
0.3
1.6
2.0
3.2
3.9
H
Communication
Programming

64 0.5 3.7 7.3 64 0.4 2.5 5.0

When the types of read or written devices increase, "Data transfer time shown in above table Number of
device types" is required.
When the number of read or written points exceeds "64"*5, the transfer time increase.
Accordingly, for achieving efficient data transfer, it is recommended to decrease the number of types of I
transferred devices and use as many continuous device numbers as possible.
Maintenance
Remote

*3. Available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.
*4. The message waiting time is "0" when the RS-485 interface and two-pair wiring are used.
The message waiting time is "0" also when the RS-232C interface is used.
When one-pair wiring is adopted, a message waiting time of 70 to 150 ms is required for each transfer.
Add this message waiting time. Apx.A
models
Discontinued

*5. The maximum number of points is as follows for the FX0N and FX1S PLCs:
Maximum number of read points : 13
Maximum number of written points: 11

D-13
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.1 System Configuration

3. System Configuration and Equipment Selection


This chapter explains the system configuration and communication equipment selection operating in
accordance with RS-485 or RS-232C required by FX PLCs.

3.1 System Configuration


This section outlines the system configuration required to use computer link.
Connect (optional) equipment operating in accordance with RS-485 or RS-232C to the FX PLC main unit.

1 , 2 , 3 and 4 indicate the communication equipment combination patterns.

Communication equipment operating Total extension


in accordance with RS-485 or FX PLC Important point in selection distance
RS-232C

1 RS-485: 50 m
This is the communication board built
(164' 0")
+ into the PLC, reducing the installation
RS-232C: 15 m
area.
(49' 2")

Communication
board

2 RS-485: 500 m
Attach the special adapter connection
board to the main unit, and then (1640' 5")
+ + attach the communication adapter to RS-232C: 15 m
the left side of the main unit. (49' 2")

Special adapter
Communication connection
adapter board

3
Attach the connector conversion RS-485: 500 m
+ + adapter to the main unit, and (1640' 5")
then attach the communication RS-232C: 15 m
adapter to the left of the main unit. (49' 2")

Communication Connector
adapter conversion
adapter

4
RS-485: 500 m
Attach the communication adapter to
+ the left side of the main unit.
(1640' 5")
RS-232C: 15 m
(49' 2")

Communication
adapter

For communication equipment combinations for each FX Series, refer to the next page.

D-14
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

A
3.2 Applicable FX PLC and Communication Equipment

Common Items
Select a (optional) communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the external dimensions are different between the units shown in "FX2NC-485ADP/
FX0N-485ADP". Select either one. B
- In the table below, only the outside dimensions and D-SUB connector shape are different between units

N:N Network
shown in "FX2NC-232ADP/FX0N-232ADP". Select either one.
- In the table below, only the cable is different between the units shown in "FX3G-485-BD/FX3G-485-BD-
RJ". Select either one.
- Computer link is not provided for the FX1, FX0 or FX0S PLCs.
C
3.2.1 For communication in accordance with RS-232C

Parallel Link
Total extension
FX Series Communication equipment (option) Check
distance

Computer Link
15 m
(49' 2")

FX0N FX2NC-232ADP FX0N-232ADP


(9-pin D-Sub, male) (25-pin D-Sub, female)
E

Communication
Inverter
15 m
(49' 2")
FX1N-232-BD
(9-pin D-Sub, male)
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1S + + 15 m
(49' 2")

FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD


(9-pin D-Sub, male)
FX0N-232ADP
(25-pin D-Sub, female) G

(FX2N-232IF)
Communication
Non-Protocol
15 m
(49' 2")
FX1N-232-BD
(9-pin D-Sub, male) H
Communication
Programming

FX1N + + 15 m
(49' 2")

FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP


I
Maintenance
Remote

(9-pin D-Sub, male) (25-pin D-Sub, female)

Apx.A
models
Discontinued

D-15
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance

15 m
(49' 2")
FX2N-232-BD
(9-pin D-Sub, male)

FX2N
+ + 15 m
(49' 2")

FX2N-CNV-BD FX2NC-232ADP FX2N-CNV-BD FX0N-232ADP


(9-pin D-Sub, male) (25-pin D-Sub, female)

15 m
(49' 2")

FX3G-232-BD
(9-pin D-Sub, male)

FX3S
+ 15 m
(49' 2")

FX3S-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)

15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)

FX3G
(14-point, 24-point
15 m
type)
(49' 2")

FX3G-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)

D-16
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)

ch1

N:N Network
15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)
The communication equipment works as ch1 when connected to
the option connector 1.
C

Parallel Link
15 m
(49' 2")
D

Computer Link
FX3G-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)
When using channel 2 (ch 2)

FX3G
(40-point, 60-point E
type)

Communication
Inverter
15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)
The communication equipment works as ch2 when connected to F
the option connector 2.

(RS/RS2 Instruction)
Communication
Non-Protocol
15 m G
(49' 2")

(FX2N-232IF)
Communication
Non-Protocol
FX3G-CNV-ADP FX3U- ADP(-MB) FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-17
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)

ch1

15 m
RD

(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)

ch1

+ 15 m
(49' 2")

FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)

ch1 ch2

+
RD

FX3U SD

15 m
(49' 2")
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV)

When a FX3U-8AV-BD is used, it occupies one communication port


channel.
ch1 ch2

+ + 15 m
(49' 2")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

15 m
(49' 2")

FX2NC-232ADP FX0N-232ADP
FX1NC (9-pin D-Sub, male) (25-pin D-Sub, female)

15 m
(49' 2")

FX2NC-232ADP FX0N-232ADP
FX2NC (9-pin D-Sub, male) (25-pin D-Sub, female)

D-18
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

B
15 m

N:N Network
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)


C
ch1 ch2

Parallel Link
FX3GC

+ 15 m
(49' 2")

FX3U-232ADP(-MB), FX3U-232ADP(-MB) D
FX3U-485ADP(-MB) (9-pin D-Sub, male)

Computer Link
When using channel 1 (ch 1)
ch1

15 m
E

Communication
Inverter
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)


ch1 ch2
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3UC
(D, DS, DSS)
+ 15 m
(49' 2")
FX3U-232ADP(-MB),
FX3U-485ADP(-MB),
FX3U-232ADP(-MB)
(9-pin D-Sub, male)
G

(FX2N-232IF)
Communication
Non-Protocol
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-19
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

15 m
RD

(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)

ch1

+ 15 m
(49' 2")

FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)


ch1 ch2

+
RD

FX3UC-32MT-LT SD

(-2) 15 m
(49' 2")
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV)
When a FX3U-8AV-BD is used, it occupies one communication port
channel.
ch1 ch2

+ + 15 m
(49' 2")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

15 m
(49' 2")

FX-232ADP
FX2(FX) (25-pin D-Sub, female)

15 m
(49' 2")

FX-232ADP
FX2C (25-pin D-Sub, female)

D-20
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

A
3.2.2 For communication in accordance with RS-485

Common Items
Total extension
FX Series Communication equipment (option) Check
distance

N:N Network
500 m
(1640' 5")

FX0N FX2NC-485ADP FX0N-485ADP


(European terminal block) (Terminal block)
C

Parallel Link
50 m
(164' 0")
FX1N-485-BD
(European terminal block)

Computer Link
FX1S + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP
(European terminal block)
FX1N-CNV-BD FX0N-485ADP
(Terminal block) E

Communication
Inverter
50 m
(164' 0")
FX1N-485-BD
(European terminal block) F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1N + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP


G

(FX2N-232IF)
Communication
Non-Protocol
(European terminal block) (Terminal block)

50 m
(164' 0")

FX2N-485-BD
H
Communication
Programming

FX2N + + 500 m
(1640' 5")
I
FX2N-CNV-BD FX2NC-485ADP FX2N-CNV-BD FX0N-485ADP
Maintenance
Remote

(European terminal block) (Terminal block)

Apx.A
models
Discontinued

D-21
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3S
+ 500 m
(1640' 5")

FX3S-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3G
(14-point, 24-point
type) 500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

When using channel 1 (ch 1)

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch1 when connected to
the option connector 1.
FX3G
(40-point, 60-point
type)

500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

D-22
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

N:N Network
50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch2 when connected to
the option connector 2. C

Parallel Link
FX3G
(40-point, 60-point
type)

500 m D
(1640' 5")

Computer Link
FX3G-CNV-ADP FX3U- ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
When using channel 1 (ch 1)
E

Communication
Inverter
ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
F
SD SD B

SG

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U-485-BD
(European terminal block)

ch1
FX3U

G
+ 500 m
(1640' 5")

(FX2N-232IF)
Communication
Non-Protocol
FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-23
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch1 ch2

+
RD

SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.

ch1 ch2
FX3U

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

500 m
(1640' 5")

FX2NC-485ADP FX0N-485ADP
FX1NC (European terminal block) (Terminal block)

500 m
(1640' 5")

FX2NC-485ADP FX0N-485ADP
FX2NC (European terminal block) (Terminal block)

When using channel 1 (ch 1)


ch1

500 m
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


ch1 ch2
FX3GC

+ 500 m
(1640' 5")

FX3U- ADP(-MB) FX3U-485ADP(-MB)


(Where represents (European terminal block)
232 and 485).

D-24
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

B
500 m

N:N Network
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


C
ch1 ch2

Parallel Link
FX3UC
(D, DS, DSS)
+ 500 m

FX3U-232ADP(-MB), FX3U-485ADP(-MB)
(1640' 5")
D
FX3U-485ADP(-MB), (European terminal block)

Computer Link
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
When using channel 1 (ch 1)
ch1 E

Communication
Inverter
RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)
F
ch1

(RS/RS2 Instruction)
Communication
Non-Protocol
+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
G
(European terminal block)

(FX2N-232IF)
Communication
Non-Protocol
When using channel 2 (ch 2)
ch1 ch2

FX3UC-32MT-LT
+ H
RD

(-2)
SD

500 m
Communication
Programming

(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
I
ch1 ch2
Maintenance
Remote

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB) Apx.A
FX3U-485ADP(-MB), (European terminal block)
models
Discontinued

FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

D-25
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Equipment Selection
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance

500 m
(1640' 5")

FX-485ADP
FX2 (Terminal block)

500 m
(1640' 5")

FX-485ADP
FX2C (Terminal block)

D-26
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 3.2 Applicable FX PLC and Communication Equipment

Common Items
4. Wiring
This chapter explains the wiring. B

N:N Network
WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
C

Parallel Link
operation after installation or wiring work.
Failure to do so may cause electric shock.

WIRING PRECAUTIONS
D

Computer Link
Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents
due to abnormal data written to the PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the PLC. However, do not use common E
grounding with heavy electrical systems.

Communication
Inverter
Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure F
that the screwdriver does not touch the partition part of the terminal block.

(RS/RS2 Instruction)
Communication
Non-Protocol
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires. G
- Do not solder-plate the electric wire ends.

(FX2N-232IF)
Communication
Non-Protocol
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-27
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.1 Wiring Procedure

4.1 Wiring Procedure

1 Selecting the connection method


Select the wiring method suitable to the application.
For details, refer to Section 4.2.

2 Preparing for wiring


Prepare cables and terminal resistors required for wiring.
For details, refer to Section 4.3.

3 Turning OFF the PLC power


Before starting any wiring work, make sure that the PLC power is OFF.

4 Connecting the power supply (FX0N-485ADP only)


Connect the power supply to the 24V DC power terminal.

5 Wiring communication equipment


Connect communication equipment operating in accordance with RS-485 or RS-232C.
For communication in accordance with RS-232C, refer to Section 4.4.
For communication in accordance with RS-485, refer to Section 4.5.

D-28
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.2 Selecting Connection Method

A
4.2 Selecting Connection Method

Common Items
When using computer link, communication can be achieved in accordance with RS-232C or RS-485 (422).
In FX3G, FX3GC, FX3U and FX3UC PLCs, computer link is applicable in up to two channels at the same time. In
such a case, communication can be achieved in accordance with RS-232C on both channels, in accordance
with RS-485 on both channels, or in accordance with RS-232C on one channel and RS-485 on the other B
channel.

N:N Network
4.2.1 For communication in accordance with RS-232C (1-to-1 connection)
With communication in accordance with RS-232C, 1-to-1 connection is applicable. Make sure that the total
extension distance is 15 m (49' 2") or less. C
Personal computer FX PLC

Parallel Link
+ D
Communication equipment operating

Computer Link
in accordance with RS-232C

15 m (49' 2") or less

Communication
Inverter
4.2.2 For communication in accordance with RS-485 (RS-422) (1-to-N connection)
With communication in accordance with RS-485 (RS-422), up to 16 PLCs can be connected. Make sure that
the total extension distance is 500 m (1640' 5") or less [50 m (164' 0") or less when 485BD is included].
Personal computer FX PLC
Station No. 0
FX PLC
Station No. 15
F

(RS/RS2 Instruction)
Communication
Non-Protocol
RS-232C/RS-485 ...
communication
converter
+ +
FX-485PC-IF
Communication equipment
operating in accordance
Communication equipment
operating in accordance
G
with RS-485 with RS-485

(FX2N-232IF)
Communication
Non-Protocol
One-pair wiring and two-pair wiring are applicable for communication in accordance with RS-485 (RS-422).
The wiring method is determined for each application. Refer to the table below, and perform suitable wiring. H
One-pair Two-pair
Communication
Programming

wiring wiring
When the message waiting time*2 should be 70 ms or less
*1
Computer link When the message waiting time*2 may be more than 70 ms *3
When the on-demand function is used I
: Recommended wiring method, : Applicable wiring method, : Non-applicable wiring method
Maintenance
Remote

*1. When computer link is added to an existing system, adopt the wiring method used in the existing
system.
*2. For the message waiting time, refer to Subsection 6.4.3.
*3. "Echo transfer" is generated when the FX-485PC-IF is used in the one-pair wiring. Apx.A
Take proper countermeasures in the computer so that the echo transfer can be ignored.
models
Discontinued

D-29
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.3 Selecting Cables and Terminal Resistors (RS-485)

4.3 Selecting Cables and Terminal Resistors (RS-485)


Select cables using the procedure described below.

4.3.1 Twisted pair cable


Use shielded twisted pair cables for connecting communication equipment operating in accordance with RS-
485.
The table below shows recommended model names and manufacturers of cables used in wiring.

1. Recommended cables

Manufacturer Model name Remarks


SPEV(SB)-0.2-2P Two-pair cable of 0.2 mm2
Mitsubishi Cable Industries, Ltd. SPEV(SB)-MPC-0.2 3P Three-pair cable of 0.2 mm2
SPEV(SB)-0.5-2P Two-pair cable of 0.5 mm2
KMPEV-SB CWS-178 0.2SQ 2P Two-pair cable of 0.2 mm2
Showa Holdings Co., Ltd.
KMPEV-SB CWS-178 0.5SQ 2P Two-pair cable of 0.5 mm2
DPEV SB 0.3 3P Three-pair cable of 0.3 mm2
Sumitomo Electric Industries, Ltd.
DPEV SB 0.5 3P Three-pair cable of 0.5 mm2
D-KPEV-SB 0.2 3P Three-pair cable of 0.2 mm2
The Furukawa Electric Co., Ltd.
D-KPEV-SB 0.5 3P Three-pair cable of 0.5 mm2
IPEV-SB 2P 0.3 mm2 Two-pair cable of 0.3 mm2
Fujikura Ltd.
IPEV-SB 2P 0.5 mm2 Two-pair cable of 0.5 mm2

2. Cable structural drawing (reference)


Pair
Shield

Two-pair cable structural


drawing example Three-pair cable structural
drawing example

4.3.2 10BASE-T cable


10BASE-T cables used in LAN wiring for a personal computer can be connected to FX3G-485-BD-RJ.

1. Selection procedure when purchasing


1) Cable type : 10BASE-T cable (Category 3 or higher)
2) Connection specifications : Straight type
3) Connector : RJ45 connector (Connector with metal frame is used)

2. Cautions on using commercial cables


Pay attention to the following point when purchasing commercial cables.
Use shielded cables. Make sure to connect the shield to the metal frame of the connector, and perform
class D grounding.

D-30
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.3 Selecting Cables and Terminal Resistors (RS-485)

A
4.3.3 Connecting cables

Common Items
1. European type terminal block
The FX3G-485-BD-RJ terminal block is used for grounding.
The other options use shielded twisted pair cables for connecting communication equipment operating in
accordance with RS-485. B
The table below shows applicable cables and tightening torques.

N:N Network
Cable size when Cable size when Bar terminal with Tool size
Tightening
one cable is two cables are Insulating sleeve
torque A B
connected connected (cable size)
FX3U-485-BD
FX3G-485-BD AWG22 to
AWG22
Applicable 0.22 to 0.25
0.4 (0.01") 2.5 (0.09")
C
FX3U-485ADP AWG20 (AWG22 to AWG20) Nm

Parallel Link
(-MB)
FX3G-485-BD- 0.5 to 0.6
AWG20 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
RJ Nm
FX2N-485-BD 0.5 to 0.6
FX1N-485-BD
AWG26 to AWG16 Not applicable
Nm
0.6 (0.03") 3.5 (0.14")
D
AWG26 to AWG26 to 0.4 to 0.5

Computer Link
FX2NC-485ADP Not applicable 0.6 (0.03") 3.5 (0.14")
AWG16 AWG20 Nm

Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
With regard to the cable end treatment, use a stranded cable or solid cable as it is, or use a bar terminal with
insulating sleeve. E
FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD and FX2NC-485ADP cannot use a bar terminal with insulating

Communication
Inverter
sleeve.
When using a stranded cable or solid cable as it is
- Twist the end of a stranded cable so that wires do not get barbed.
- Do not plate the end of the cable.
FX3G-485-BD, FX3U-485-BD, FX3G-485-BD-RJ, FX2NC-485ADP
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U-485ADP(-MB) FX2N-485-BD, FX1N-485-BD

Approx. 9 mm
(0.35")
Approx. 6 mm
(0.23")
Approx. 8 mm
(0.31") G

(FX2N-232IF)
Communication
Non-Protocol
When using a bar terminal with insulating sleeve Insulating sleeve Contact area
Because it is difficult to insert a cable into an insulating sleeve (Crimp area)
depending on the thickness of the cable sheath, select the proper cable
according to the outline drawing. 8 mm (0.31")
<Reference> 2.6 mm

Manufacturer Model name Caulking tool


(0.1") 14 mm
(0.55") H
Communication
Programming

CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
(or CRIMPFOX 6T-F*2)

*1. Old model name : CRIMPFOX ZA 3


*2. Old model name : CRIMPFOX UD 6
I
Maintenance
Remote

Apx.A
models
Discontinued

D-31
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.3 Selecting Cables and Terminal Resistors (RS-485)

Tool Select a
When tightening a terminal on the European terminal block, use a small screwdriver
with a
commercial straight shape screwdriver whose tip is shown in the figure to straight tip.
the right.

Note A B
For size A and size B,
If the diameter of screwdriver grip is too small, tightening torque will not refer to the table above.
be able to be achieved. To achieve the appropriate tightening torque
shown in the previous page, use the following screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
<Reference>
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB)
Manufacturer Model name
Phoenix Contact Co., Ltd. SZS 0.4 2.5

FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD, FX2NC-485ADP


Manufacturer Model name
Phoenix Contact Co., Ltd. SZF 1-0.6 3.5

2. Terminal block
In the FX0N-485ADP and FX-485ADP, the terminal screw size is "M3".
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 Nm.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
When wiring one cable to one terminal
Terminal Crimp
3.2(0.13") screw terminal
6.2mm(0.24")
or less
3.2(0.13")
6.2mm(0.24") Terminal
or less

When wiring two cables to one terminal


3.2(0.13")
6.2mm(0.24") Terminal Crimp
or less screw terminal
6.3mm(0.25")
or more

3.2(0.13")
6.2mm(0.24") Terminal
or less 6.3mm(0.25")
or more

D-32
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.3 Selecting Cables and Terminal Resistors (RS-485)

A
4.3.4 Connecting terminal resistors

Common Items
Make sure to provide a terminal resistor at the end of each line. Brown Precision
In the case of one-pair wiring, connect a terminal resistor to the RDA-RDB signal
terminal of the communication equipment.
In the case of two-pair wiring, connect a terminal resistor to the RDA-RDB signal
terminal and SDA-SDB terminal of the communication equipment. B
1 1 1 =110

N:N Network
1. Terminal resistor type (101)
In the case of one-pair wiring, use two terminal resistors of 110 , 1/2 W. Orange Brown Precision
In the case of two-pair wiring, use four terminal resistors of 330 , 1/4 W.
Among the terminal resistors supplied with the communication equipment, select
ones with the color codes shown to the right.
2. When using the FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ or 3 3 1 =330
C
FX3U-485ADP(-MB)

Parallel Link
(101)
The FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB)
have built-in terminal resistors.
Set the terminal resistor selector switch accordingly.
FX3U-485-BD FX3U-485ADP(-MB)
D

Computer Link
Terminal 330
resistor Terminal
selector OPEN resistor selector
switch
switch 110

E
FX3G-485-BD

Communication
Inverter
Remove the upper terminal block before changing over the switch in the FX3G-485-BD.

Removal: Loosen the terminal block mounting screws, and remove the terminal block.
Installation: Attach the terminal block, and tighten the terminal block mounting screws.
Tightening torque: 0.4 to 0.5 Nm
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do F
so may cause equipment failures or malfunctions.

(RS/RS2 Instruction)
Communication
Non-Protocol
For installation and removal of the terminal block, use the recommended
Select a
tool shown below or a tool having straight tip (such as screwdriver) as screwdriver
shown in the right figure. with a
<Reference> straight tip.

Manufacturer Model name G


Phoenix Contact Co., Ltd. SZS 0.4 2.5 0.4mm 2.5mm

(FX2N-232IF)
Communication
Non-Protocol
(0.01") (0.09")

Terminal resistor
selector switch H
Communication
Programming

Terminal block mounting screws


I
FX3G-485-BD-RJ
Maintenance
Remote

Terminal resistor
selector switch
Apx.A
models
Discontinued

D-33
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.4 Connection Diagram for RS-232C

4.4 Connection Diagram for RS-232C


Representative wiring examples are shown in this section. When pin numbers in the external equipment are
different, wire the pins as shown below.

4.4.1 Connection diagram between FX PLC and personal computer

External equipment operating in accordance


PLC side
with RS-232C
FX3U-232-BD When CS and When DR and
FX3G-232-BD RS are used ER are used
Name FX2NC- FX0N-
FX2N-232-BD 232ADP 232ADP FX-232ADP Name Name
FX1N-232-BD 9-pin 25-pin 9-pin 25-pin
FX3U-232ADP(-MB) D-Sub D-Sub D-Sub D-Sub
FG 1 FG 1 FG 1
RD(RXD) 2 3 RD(RXD) 2 3 RD(RXD) 2 3
SD(TXD) 3 2 SD(TXD) 3 2 SD(TXD) 3 2
ER(DTR) 4 20 RS(RTS) 7 4 ER(DTR) 4 20
SG(GND) 5 7 SG(GND) 5 7 SG(GND) 5 7
DR(DSR) 6 6 CS(CTS) 8 5 DR(DSR) 6 6

4.4.2 Connection diagram between FX-485PC-IF and personal computer

485PC-IF Personal computer


Signal name Pin No. Signal name
SD (TXD) 2 SD (TXD)
RD (RXD) 3 RD (RXD)
RS (RTS) 4 RS (RTS)
CS (CTS) 5 CS (CTS)
DR (DSR) 6 DR (DSR)
SG (GND) 7 SG (GND)
ER (DTR) 20 ER (DTR)

D-34
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.5 Connection Diagram for RS-485 and RS-422

A
4.5 Connection Diagram for RS-485 and RS-422

Common Items
4.5.1 One-pair wiring

Communication
FX3U-485-BD
FX3G-485-BD B
equipment operating FX2N-485-BD

N:N Network
in accordance with FX1N-485-BD
RS-485 FX0N-485ADP FX3U-485ADP(-MB) FX2NC-485ADP
SDA SDA SDA SDA
(TXD+) (TXD+) (TXD+) (TXD+)

Terminal
resistor:
SDB
(TXD-)
SDB
(TXD-)
SDB
(TXD-)
SDB
(TXD-)
Terminal
resistor: C
110 110

Parallel Link
RDA RDA RDA RDA
*3 *3
(RXD+) (RXD+) (RXD+) (RXD+)

RDB RDB RDB RDB


(RXD-) (RXD-) (RXD-) (RXD-)

LINK LINK D
SG
SG SG

Computer Link
FG*2 Class-D grounding Class-D grounding
SG
(resistance: 100 or less)*1 (resistance: 100 or less)*1

*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
the FX2N-485-BD, FX1N-485-BD, FX3G-485-BD, FX3U-485-BD, FX2NC-485ADP or E
FX3U-485ADP(-MB).

Communication
Inverter
*2. Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring
Class-D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
*3. Make sure to provide a terminal resistor at the end of each line.
The FX3U-485-BD, FX3G-485-BD and FX3U-485ADP(-MB) have a built-in terminal resistor. F
Set the terminal resistor selector switch accordingly

(RS/RS2 Instruction)
Communication
Non-Protocol
The FX0N-485ADP, FX2NC-485ADP, FX2N-485-BD and FX1N-485-BD are supplied together with
terminal resistors.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-35
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.5 Connection Diagram for RS-485 and RS-422

FX3G-485-BD-RJ
Communication
equipment operating
in accordance
with RS-485 Distributor (BMJ-8) Distributor (BMJ-8) FX3G-485-BD-RJ
SDA
(TXD+) 5 5 5 5 5 RDA
Terminal SDB 4 4 4 4 4 RDB
resistor (TXD-) 3 3 3 3 3 SDA
110 RDA 6 6 6 6 6 SDB
*2
(RXD+) 1 1 1 1 1 SG
RDB 2 2 2 2 2
(RXD-) Terminal
7 7 7 7 7 resistor
LINK
SG 8 8 8 8 8 *2

5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Connector metal frame


*1
Class-D Class-D Class-D Class-D
grounding grounding grounding grounding
*1 *1 *1
*1
5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Class-D
Connector metal frame

Connector metal frame


grounding (Terminal resistor
selector switch:
110)*2
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB
SG

SG
FX3G-485-BD-RJ FX3G-485-BD-RJ
(Terminal resistor selector switch: Open) (Terminal resistor selector switch: Open)

*1. Use shielded cables, and make sure to perform class D grounding on the shield.
When using the terminal block to connect ground of FX3G-485-BD-RJ, wire the ground wire only to
either one of two poles of the terminal block.
*2. Make sure to provide a terminal resistor at the end of each line. Set the FX3G-485-BD-RJ terminal
resistor selector switch accordingly.
Prepare the following devices if necessary.
Product name Model name Manufacturer
RJ45 connector TM11AP-88P HIROSE ELECTRIC CO., LTD.
BMJ-8
Distributor BMJ-8-28N (No internal connection of the No. 2 and 8 pin) HACHIKO ELECTRIC CO., LTD.
(Do not use a plug with terminal resistor)

D-36
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.5 Connection Diagram for RS-485 and RS-422

A
4.5.2 Two-pair wiring

Common Items
FX3U-485-BD
Communication FX3G-485-BD
equipment operating FX2N-485-BD
in accordance with FX1N-485-BD
RS-485/RS-422 FX0N-485ADP FX3U-485ADP(-MB) FX2NC-485ADP
SDA SDA SDA SDA B
(TXD+) (TXD+) (TXD+) (TXD+)

N:N Network
SDB SDB SDB SDB
*3 *3
(TXD-) (TXD-) (TXD-) (TXD-)

RDA RDA RDA RDA


(RXD+) (RXD+) (RXD+) (RXD+)
C
RDB RDB RDB RDB

Parallel Link
*3 *3
(RXD-) (RXD-) (RXD-) (RXD-)
Terminal Terminal
resistor: resistor:
330 LINK LINK 330
2 SG 2
SG SG

FG*2 Class-D grounding


(resistance: 100 or less)*1
Class-D grounding
(resistance: 100 or less)*1
SG
D

Computer Link
*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
the FX2N-485-BD, FX1N-485-BD, FX3G-485-BD, FX3U-485-BD, FX2NC-485ADP or
FX3U-485ADP(-MB).
*2. Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring
Class-D grounding. E
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.

Communication
Inverter
*3. Make sure to provide a terminal resistor at the end of each line.
The FX3U-485-BD, FX3G-485-BD and FX3U-485ADP(-MB) have a built-in terminal resistor.
Set the terminal resistor selector switch accordingly.
The FX0N-485ADP, FX2NC-485ADP, FX2N-485-BD and FX1N-485-BD are supplied together with
terminal resistors. F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-37
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.5 Connection Diagram for RS-485 and RS-422

FX3G-485-BD-RJ
Communication equipment
operating in accordance
with RS-485/RS-422
Distributor (BMJ-8) Distributor (BMJ-8) FX3G-485-BD-RJ
SDA
(TXD+) 5 5 5 5 5 RDA
SDB 4 4 4 4 4 RDB
*2
(TXD-) 3 3 3 3 3 SDA
RDA 6 6 6 6 6 SDB
(RXD+) 1 1 1 1 1 SG
*2 RDB 2 2 2 2 2 Terminal
Terminal (RXD-) resistor
7 7 7 7 7 *2
resistor LINK Terminal
8 8 8 8 8 resistor
330 SG
2 5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Connector metal frame
*1
Class-D Class-D Class-D Class-D
grounding grounding grounding grounding
*1 *1 *1 *1

5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Class-D
Connector metal frame

Connector metal frame


grounding (Terminal resistor
selector switch:
330)*2
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB
SG

SG
FX3G-485-BD-RJ FX3G-485-BD-RJ
(Terminal resistor selector switch: Open) (Terminal resistor selector switch: Open)

*1. Use shielded cables, and make sure to perform class D grounding on the shield.
When using the terminal block to connect ground of FX3G-485-BD-RJ, wire the ground wire only to
either one of two poles of the terminal block.
*2. Make sure to provide a terminal resistor at the end of each line. Set the FX3G-485-BD-RJ terminal
resistor selector switch accordingly.
Prepare the following devices if necessary.
Product name Model name Manufacturer
RJ45 connector TM11AP-88P HIROSE ELECTRIC CO., LTD.
BMJ-8
Distributor BMJ-8-28N (No internal connection of the No. 2 and 8 pin) HACHIKO ELECTRIC CO., LTD.
(Do not use a plug with terminal resistor)

D-38
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Computer Link 4.6 Grounding

A
4.5.3 Switching of 1 pair / 2 paired wiring (FX3G-485-BD-RJ)

Common Items
The FX3G-485-BD-RJ has a built-in wiring circuit switch.
Set the wiring circuit switch to 1 pair / 2 pair.

N:N Network
Wiring circuit
switch

Parallel Link
4.6 Grounding
Grounding should be performed as stated below.
D
The grounding resistance should be 100 or less.

Computer Link
Independent grounding should be performed for best results.
When independent grounding can not be performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the Hardware Edition of each series.

PLC Other PLC Other PLC Other E


equipment equipment equipment

Communication
Inverter
Independent grounding Shared grounding Common grounding
Best condition Good condition Not allowed

The grounding wire size should be AWG 14 (2 mm2) or larger.


F
The grounding point should be close to the PLC, and all grounding wires should be as short as possible.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-39
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Computer Link 5.1 Communication Setting Methods

5. Communication Setting in FX Programmable Controller


This chapter explains the communication setting method types and setting methods for computer link.

5.1 Communication Setting Methods


This section explains the communication setting methods and setting procedures in FX PLCs.

1. Setting method types


1) Specifying the setting using parameters in the sequence programming software:
Register the setting as parameters by executing communication setting on the personal computer screen
using the sequence programming software, and transfer them to a PLC.
(This method using parameters is not available for FX2(FX), FX2C, or FX0N PLCs.)
2) Specifying the setting by writing data to special data registers:
Create a sequence program specifying the communication format, station number settings and time-out
time setting, and then transfer the sequence program to a PLC.
Caution
A PLC operates in the same way regardless of the selected method shown above. If both methods are
selected, priority is given to the method using parameters.

2. Communication setting method applicability for each FX Series


FX Series Specification using parameters Specification using special data registers
FX1S, FX1N, FX1N, FX2N, FX2NC,
FX3S, FX3G(ch1), FX3GC(ch1), (Recommended)
FX3U(ch1), FX3UC(ch1)
FX3G(ch2), FX3GC(ch2),

FX3U(ch2), FX3UC(ch2)
FX2(FX), FX2C, FX0N
For the detailed contents of special data registers, refer to Section 9.2.
Setting data write method to special data registers, refer to Section 9.3.

3. Setting data flow


PLC memory Transferred
Setting window when power
is turned ON ch1: Computer link
Parameter area
Parameter D8120 Communication format
method D8121 Station number settings
Program area D8129 Time-out time setting
[MOV H D8120] Written by
program
[MOV H D8121]
[MOV K D8129] In FX3G, FX3GC, FX3U and FX3UC

ch2: Computer link

Sequence Program D8420 Communication format


program for method D8421 Station number settings
set values D8429 Time-out time setting

When both methods are used at the same time,


priority is given to the contents set in the parameter
method.

D-40
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Computer Link 5.2 Communication Setting Using Parameter Method (GX Works2)

A
4. Time at which the settings become valid

Common Items
1) When specifying the setting using parameters:
When the PLC power is turned ON, the parameters set using the parameter setting window in the
sequence programming software are automatically transferred to the PLC.
As soon as the parameters are transferred to the PLC, the setting becomes valid.
After the program (parameters) are transferred to the PLC, it is necessary to reboot the PLCs power. B
2) When specifying the setting by writing data to special data registers:

N:N Network
Set the PLC mode from STOP to RUN, write the required data, reboot the PLCs power.
As soon as the PLC power is turned ON, the setting becomes valid.
Caution
Since the special data registers (D8120, D8121, D8129) is a battery backed area in the case of the FX2N,
FX2NC, FX3U and FX3UC series, a value cannot be normally saved when the battery is discharge (or after a C
battery error occurs).

Parallel Link
Therefore, keep in mind that a computer link setting may not be possible in this case.

5.2 Communication Setting Using Parameter Method (GX Works2)


Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
D

Computer Link
parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 5.3.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.2.1 Operating procedure E

Communication
Inverter
This subsection explains the serial communication setting method.
Suppose that GX Works2 is already started up.

1 Opening the parameter setting window


In the project view area of the navigation window, double-click [Parameter] [PLC Parameter]. F
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from

(RS/RS2 Instruction)
Communication
Non-Protocol
the menu bar.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-41
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Computer Link 5.2 Communication Setting Using Parameter Method (GX Works2)

2 Setting the serial communication (parameters)


Click the [PLC System(2)] tab on the dialog box.

3 Setting the serial communication (parameters)


Select a channel and check the box labeled "Operate Communication Setting" box, then adjust the
parameters for that channel.
Click [End].

Adjust the settings on the personal computer to match those set here.

4 Writing parameters to the PLC


Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
[Execute].

D-42
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Computer Link 5.3 Communication Settings Using Parameter Method (FXGP/WIN)

A
5.3 Communication Settings Using Parameter Method (FXGP/WIN)

Common Items
Communication settings may be changed by the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with FXGP/WIN.
Ch2 cannot be set using FXGP/WIN. B
For details on GX Works2 operating procedure, refer to section 5.2.

N:N Network
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already
C

Parallel Link
started up.

1 Displaying the serial setting (parameter)


Select [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of parameter setting.
D

Computer Link
1. When there are no parameter settings
There are no communication settings. Click the [Yes] button.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-43
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Computer Link 5.3 Communication Settings Using Parameter Method (FXGP/WIN)

2. When there are already parameter settings


The existing communication setting contents are displayed.

2 Adjusting serial setting (parameter)


Execute the communication setting as shown below.

Adjust the settings on the personal computer to match those set here.

3 Writing a sequence program (parameters) to the PLC


Select [PLC] [Transfers] [Write] from the toolbar, and click [OK] button.

D-44
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.1 Data Flow by Link

Common Items
6. Control Procedures and Setting Methods
B
6.1 Data Flow by Link

N:N Network
The figures below show images of data flow achieved when data is read from or written to a PLC CPU and
the status is controlled.
In the case of communication in accordance with RS-232C, ignore "485PC-IF" and regard "485ADP" as
"232ADP". C

Parallel Link
1. When the computer reads data from the PLC
485PC-IF 485ADP PLC CPU
Computer RS-232C RS-485
[2] Command [3] [4]
[9] Various data [8] [7] Sequence
OS*1
[12] Response [13] [14]
OS*1
program D
[1] Request

Computer Link
Device [5] Read
[10] [11] memory [6] Data
information Interface for
(read) signal Device
PLC CPU conversion memory, etc.
information
(read)
E

Communication
Inverter
2. When the computer writes data to the PLC
RS-232C 485PC-IF 485ADP PLC CPU
Computer [2] Command, RS-485
data, etc. [3] [4]

OS*1 OS*1
Sequence
program
F
[8] Response [7] [6]

(RS/RS2 Instruction)
Communication
Non-Protocol
[1] Request

Device [5] Write


memory
information Device
(written) memory, etc.
PLC CPU
information
(written) G

(FX2N-232IF)
Communication
Non-Protocol
3. When the PLC sends data to the computer (on-demand function)
485PC-IF 485ADP PLC CPU
Computer
RS-232C RS-485

OS*1
[6] Data [5] [4] Data
OS*1
Sequence H
program
Communication
Programming

On-demand
data
[7] [2]
Write [3] Data Read [1] Sending
Device request
+
memory, etc. Data writing

I
Maintenance
Remote

*1. The OS (standing for "Operating System") indicates the software used to efficiently operate the
resources including the CPUs, memories, terminals, files, and networks using user programs, etc.

Apx.A
models
Discontinued

D-45
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.2 Important Points in Computer Link

6.2 Important Points in Computer Link


This section explains important points to be understood before creating programs for computer link.

6.2.1 Operations of PLC caused by data transfer


The PLC operations and scan time using computer link are as described below.

1. While the PLC is in RUN mode


For requests from the computer, the PLC executes access for one request during each END processing.
Sending and receiving are executed as interrupts.
Accordingly, when sending and receiving are executed, the scan time is longer by about 10%. The scan time
can be checked in D8010 to D8012 in the PLC.

2. Condition in which the transfer sequence in the PLC is initialized


The transfer sequence in the PLC is initialized in the following cases:
- When the power is turned ON
- When regular sending/receiving is completed
- When the control code "EOT" or "CL" is received in each format
- When the control code "NAK" is sent
- When the time-out time setting is detected
For details on the time-out time setting, refer to Subsection 6.4.4.

3. Occurrence of framing error in the computer


When a commercial interface in accordance with RS-485 is used in the computer, a framing error may occur
while nothing is sent from the PLC to the computer depending on the interface in the computer.
To cope with this nonconformity, let the computer ignore any data until the PLC sends STX, ACK or NAK.

4. Response of "NAK" from the PLC


When an error is detected, the PLC sends NAK to the computer.

5. Command sending from the computer


When sending commands from the computer to the PLC, wait for the interval times in the following table or
more after the PLC finishes receiving data in response to the previous command, and then send the next
command.
PLC Interval times
FX3U, FX3UC 300 s
FX2N, FX2NC, FX3S, FX3G, FX3GC 100 s
FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC two scan times

D-46
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.3 How to Understand Control Procedure

A
6.3 How to Understand Control Procedure

Common Items
This section explains how to understand the transfer data shown in the later description of each function.

1. When the computer reads data from the PLC (computer PLC)
A C B

N:N Network
E A
Computer side N Data C Data
Q K
S
PLC side T Data
X

B C

Parallel Link
[1] Parts A and C indicate transfer from the computer to the PLC.
[2] Part B indicates transfer from the PLC to the computer.
[3] Create a program in the computer so that each data is transferred in turn from the left to the right, and
that the data is transferred in the order "A B C" as a whole.
(Example: In the part A, data is transferred in turn from the right starting from "ENQ".)

2. When the computer writes data to the PLC (computer PLC)


D

Computer Link
A

E
Computer side N Data
Q
A
PLC side C
K
Data
E

Communication
Inverter
B

[1] Part A indicates transfer from the computer to the PLC.


[2] Part B indicates transfer from the PLC to the computer.
[3] Create a program in the computer so that each data is transferred in turn from the left to the right, and
that the data is transferred in the order "A B" as a whole. F
(Example: In the part A, data is transferred in turn from the right starting from "ENQ".)

(RS/RS2 Instruction)
Communication
Non-Protocol
6.4 Basic Formats of Dedicated Protocol
There are two types of control procedures in dedicated protocols.
CR and LF are not added to each block in format 1. CR and LF are added to each block in format 4. G
(The format names are the same as those used in the computer link units for A Series PLCs.)

(FX2N-232IF)
Communication
Non-Protocol
This section explains the contents of control procedures and the contents of each item specified in the control
procedures in each format.
The basic format of control procedures (protocols) is as shown below:
For details, refer to Subsections 6.4.1 and 6.4.2.
*1 *2 H
Communication
Programming
Message waiting time

Control code CR LF
Sum check code
Station number
Control code

PLC number

Command

Character

I
Maintenance
Remote

*1. Whether or not the sum check code is added can be specified using a parameter.
*2. Whether or not the control code is added can be specified by selecting the protocol type.
Apx.A
models
Discontinued

D-47
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.4 Basic Formats of Dedicated Protocol

6.4.1 Control procedure format 1


The table below shows the control procedure for format 1.
Description Control procedure (protocol)

PLC No.
Station
No.
A
Transfer order K
*
or

Sum check
Command
E A

PLC No.

Message

PLC No.
wait time
Station

Station
Character

code
No.

No.
N area A C
When
computer Computer side Q K

reads data PLC side

Sum check
S E

PLC No.
Station
from PLC Character

code
No.
T area B T
X X

or *
N

PLC No.
Station

Error
code
No.
A
K

*
Sum check
Command

E
Message
PLC No.

wait time
Station

Character
code
No.

N area C
Computer side Q
When PLC side Transfer order A
PLC No.
Station

computer
No.

C
writes data to K
PLC
or

N
PLC No.
Station

Error
code
No.

A
K

1) The sum check code is added only when "sum check code provided" is selected.
The sum check code is not added when "sum check code not provided" is selected.
2) When "sum check code provided" is selected, the sum check is executed only to the character
Remarks areas marked with "*" in the figure above.
3) The contents of "Character area A", "Character area B" and "Character area C" vary depending
on the contents of transfer, but do not vary depending on the control procedure format.
For details on character contents, refer to "7. Commands".

D-48
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.4 Basic Formats of Dedicated Protocol

A
6.4.2 Control procedure format 4

Common Items
The table below shows the control procedure for format 4.
Description Control procedure (protocol)

N C L B

PLC No.
Station
No.
A

N:N Network
Transfer order K RF

*
or

Sum check
Command
E C L A C L

PLC No.
PLC No.

Message
wait time

Station
Station
Character
C

code

No.
No.
N area A C
When RF RF
computer Computer side Q K

Parallel Link
reads data PLC side

Sum check
S E C L

PLC No.
Station
Character

code
from PLC

No.
T area B T
X X RF

or *
D
N C L

PLC No.

Computer Link
Station

Error
code
No.
A
K RF

*
E
Sum check
Command

Communication
Inverter
E C L
Message
PLC No.

wait time
Station

Character
code
No.

N area C
RF
Computer side Q
When PLC side Transfer order A C L
PLC No.
Station

computer
No.

C
writes data to
PLC
K RF F

(RS/RS2 Instruction)
Communication
Non-Protocol
or

N C L
PLC No.
Station

Error
code
No.

A
K RF
G
1) The sum check code is added only when "sum check code provided" is selected.

(FX2N-232IF)
Communication
Non-Protocol
The sum check code is not added when "sum check code not provided" is selected.
2) When "sum check code provided" is selected, the sum check is executed only to the character
Remarks areas marked with "*" in the figure above.
3) The contents of "Character area A", "Character area B" and "Character area C" vary depending
on the contents of transfer, but do not vary depending on the control procedure format.
For details on character contents, refer to "7. Commands". H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-49
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.4 Basic Formats of Dedicated Protocol

6.4.3 Contents of set items in each control procedure (protocol)


This subsection explains the contents of the data used in each control procedure.

1. Control codes
The table below shows control codes.
Signal name Code Description Signal name Code Description
STX 02H Start of Text LF 0AH Line Feed
ETX 03H End of Text CL 0CH Clear
EOT 04H End of Transmission CR 0DH Carriage Return
ENQ 05H Enquiry NAK 15H Negative Acknowledge
ACK 06H Acknowledge

1) When the PLC receives ENQ or ACK, it initializes the transfer sequence and begins receiving.
2) When the PLC receives EOT or CL as shown below, it initializes the transfer sequence.
At this time, the PLC gives no response.
For format 1 For format 4

E EC L
O O
T T RF

or or

C CC L

Computer side L Computer side L R F


PLC side PLC side

3) In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, a waiting time of 2 scan times or more is required from
sending of the EOT/CL code from the computer to sending of the next message.

2. Station number
The station number indicates a number provided in each PLC to determine to which PLC the computer
accesses.
The station number is specified in hexadecimal.
In FX Series PLCs, set the station number using parameters. The setting range is from 00H to 0FH.
For the station number setting method in A Series PLCs, refer to the respective A Series PLC manual.
Computer
FX FX FX FX
Series Series Series Series
485PC-IF 485 ADP 485 ADP 485 ADP 485 ADP
Station No. 0 Station No. 1 Station No. 2 Station No. 15
(00H) (01H) (02H) (0FH)

In FX2(FX), FX2C and FX0N PLCs, set a value to D8121.


M8002
MOV H0 D8121
Initial pulse

For details on the program, refer to Section 9.3.


Cautions on setting station numbers

1) Do not overlap station numbers. If the same number is set for two or more stations, the transfer data is
destroyed and normal communication is not possible.
2) It is not necessary to set consecutive station numbers as shown in the setting example above. Any station
numbers in the setting range (00H to 0FH) are applicable.
(Examples: Station numbers may be set arbitrarily. Some station numbers may be skipped.)

D-50
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.4 Basic Formats of Dedicated Protocol

A
3. PLC number

Common Items
The PLC number is used to identify a PLC to be accessed when computer link is combined with the
MELSECNET (II) or MELSECNET/B in A Series PLCs. The PLC number of each FX Series PLC is fixed to
"FFH", and converted into two-digit ASCII code.
When the on-demand function is used, however, the PLC number is automatically changed to "FEH" by the
PLC.
For the PLC number of an A Series PLC used together with the MELSECNET (II) or MELSECNET/B, refer to
B

N:N Network
the respective A Series PLC manual.

4. Command
A command specifies the contents of access executed by the computer to a PLC.
A command is converted into a two-digit ASCII code.
For an explanation of commands, refer to Chapter 7. C

Parallel Link
5. Message waiting time
The message waiting time should be specified because some computers require more time before receiving
additional data. Set the waiting time according to the specifications of each computer.
Set the waiting time within the range from 0 to 150 ms in 10-ms units. 10 ms is handled as "1H", and a value
ranging from "0H (0)" to "FH (15)" is converted into a one-digit ASCII code.
When executing communication using the 485PC-IF in a 1-to-N system adopting the one-pair wiring, make
D

Computer Link
sure to set the message waiting time to 70 ms (7) or more. When the scan time of a PLC in the system
exceeds 70 ms, set the message waiting time to the maximum scan time or higher.

Example: When the message waiting time is set to 100 ms


Message waiting time (100 ms)
E

Communication
Inverter
"A"
Computer side
PLC side

The waiting time should be the interval


F
Sending is started 100 ms or later.

(RS/RS2 Instruction)
Communication
Non-Protocol
times in the following table or more.

PLC Interval times


FX3U, FX3UC 300 s
FX2N, FX2NC, FX3S, FX3G, FX3GC 100 s
FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC two scan times
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-51
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.4 Basic Formats of Dedicated Protocol

6. Sum check code


The sum check code indicates a two-digit ASCII code converted from the least significant byte (8-bit) of the
sum check target data added as hexadecimal data.
Using the FX PLC parameters, set whether or not the sum check code is added in the message.
- When "sum check code provided" is selected, the sum check code is added in the message during
sending. During receiving, the sum check code is compared with the value calculated from the received
data to check the received data.
- When "sum check code not provided" is selected, the sum check code is not added, so the received
data is not checked either. A calculation example of the sum check code is shown below.

Example: When the station number "0", PLC number "FF", command "BR (device memory batch read)",
message waiting time "30 ms" and data "ABCD" are transferred in format 1, the sum check code
value is as shown below:

E Station PLC Com- Mes- Character area Sum


N No. No. mand sage
wait
check
time code
Q 00 FF BR A B C D BD
3
Computer side 05H 30H 30H 46H 46H 42H 52H 33H 41H 42H 43H 44H 42H 44H
PLC side S
T 00 FF ...
X
30H+30H+46H+46H+42H+52H+33H+41H+42H+43H+44H=2BDH
02H 30H 30H 46H 46H
Total from "station number" to "character area"
Last two 30 ms
digits (Message waiting time)

D-52
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.4 Basic Formats of Dedicated Protocol

A
6.4.4 Time-out time setting

Common Items
When the receiving of data from the computer is interrupted and is not restarted within the preset time (time-
out time setting), the PLC regards the situation as a timeout error and initializes the transfer sequence.

1. Time-out time setting range


The time-out time setting can be set using parameters or sequence program.
B

N:N Network
In the FX2(FX), FX2C and FX0N Series, however, the parameter setting method is not applicable.
When setting the time-out time setting in a sequence program, write a value for ch1 to D8129, and a value for
ch2 (in the FX3G, FX3GC, FX3U and FX3UC Series) to D8429 (unit: 10 ms).
However, D8429 (ch2) cannot be set in sequence programs.
The setting range is different between the parameter method and the sequence program method.
1) Details of setting range C

Parallel Link
Setting range in sequence program
FX Series Setting range in parameter
(D8129 (ch1) and D8429 (ch2))
FX2(FX), FX2C Not applicable 1 to 3276 (10 to 32760 ms)
FX0N Not applicable 1 to 255 (10 to 2550 ms)
FX1S, FX1N, FX1NC 1 to 255 (10 to 2550 ms) 1 to 255 (10 to 2550 ms) D
FX2N, FX2NC, FX3S 1 to 255 (10 to 2550 ms) 1 to 3276 (10 to 32760 ms)

Computer Link
ch1 1 to 255 (10 to 2550 ms) 1 to 3276 (10 to 32760 ms)
FX3G, FX3GC, FX3U, FX3UC
ch2 1 to 3276 (10 to 32760 ms) Not applicable

When the set value is "0", it is handled as "100 ms".


E
2) Example of setting program

Communication
Inverter
When setting the time-out time setting to 60 ms
M8002
MOV K6 D8129
Initial pulse
For details on the program, refer to Section 9.3. F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Caution on programming
The time-out time setting is not updated until the next character data is received. Set a time to receive a
character according to the transmission speed (baud rate).
For one character (12-bit), the minimum set value of the time-out time setting is as shown below:
Baud rate (bps) Time to receive one character (ms) Time-out time setting (minimum set value) G
300 40 50 ms (5)

(FX2N-232IF)
Communication
Non-Protocol
600 20 30 ms (3)
1200 10 20 ms (2)
2400 5 10 ms (1)
4800 2.5 10 ms (1)
9600 1.25 10 ms (1)
H
Communication
Programming

19200 0.625 10 ms (1)


38400 0.312 10 ms (1)

I
Maintenance
Remote

Apx.A
models
Discontinued

D-53
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.5 Transfer Sequence Time Chart and Communication Time

6.5 Transfer Sequence Time Chart and Communication Time


This section explains the communication time chart between the computer and the PLC.
As shown in the figures below, communication between the computer and the PLC is always executed after
"END". The scan time is extended by the communication time.

6.5.1 When computer reads data from PLC

E A
N C
Q K
Computer
Waiting time
(TW) T3 T4 T5
Interface
S
T It should be the interval times in the following
X table or more.
processing
Reading

This time is "0" when the message waiting time is


not set or when the waiting time is shorter than the
communication time with the CPU.
PLC
T0 T1 T2

Sequence
program
Step 0 Step 0 Step 0
END END END END
The PLC watches the time elapse. When it reaches the
transmission time, the PLC starts the transmission. If not,
the PLC evaluate the time elapse in the END process of
the next step.

PLC Interval times


FX3U, FX3UC 300 s
FX2N, FX2NC, FX3S, FX3G, FX3GC 100 s
FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC two scan times

6.5.2 When computer writes data to PLC

E
N
Q
Computer
Waiting time
(TW) T3
Interface
Data is
written.
processing
Writing

This time is "0" when the message waiting time is


not set or when the waiting time is shorter than the
communication time with the CPU.
PLC
T0 T1 T2

Sequence
program
Step 0 Step 0 Step 0
END END END END

D-54
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.5 Transfer Sequence Time Chart and Communication Time

A
6.5.3 Transfer time in transfer sequence

Common Items
This subsection explains how to calculate the approximate time after the computer starts data transfer and
the PLC gives a response until all communication is completed.
For the contents of T0 to T5, refer to the previous page.

1. When the computer reads data from the PLC B

N:N Network
Communication time = T0 + (T1 + Longer time between T2 and TW) + T3 + T4 + T5

1
T0, T3, T5 = Number of bits in one character (1 + 7 (8) + 0 (1) + 1 (2))
Baud rate
Number of characters Start
bit
Data length
(7 or 8)
Parity bit
(0 or 1)
Stop bit
(1 or 2)
C

Parallel Link
T1: Maximum one scan time (Because data is read from the PLC during the END processing while the
PLC is in RUN mode, reading requires up to one scan time depending on the sending timing.
Reading requires about 1 ms while the PLC is in STOP mode.)
T2: END processing time in the PLC executing data transfer
T4: Scan time or longer (In the case of wiring in the 1-to-N configuration, T4 should be longer than the
time-out time setting (D8129) extended by one scan time.)
D

Computer Link
TW: Message waiting time

2. When the computer writes data to the PLC


Communication time = T0 + (T1 + Longer time between T2 and TW) + T3

T0, T3 =
1
Number of bits in one character (1 + 7 (8) + 0 (1) + 1 (2)) E
Baud rate

Communication
Inverter
Number of characters Start Data length Parity bit Stop bit
bit (7 or 8) (0 or 1) (1 or 2)

T1: Maximum one scan time (Because data is written to the PLC during the END processing while the
PLC is in RUN mode, writing requires up to one scan time depending on the sending timing. Writing F
requires about 1 ms while the PLC is in STOP mode.)

(RS/RS2 Instruction)
Communication
Non-Protocol
T2: END processing time in the PLC executing data transfer
TW: Message waiting time

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-55
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.6 Transfer Data in Character Area

6.6 Transfer Data in Character Area


This section explains the transfer data in the character area sent and received between the computer and a
PLC using each command.
The transfer data explained below is handled as the character area B in reading and the character area C in
writing.
For character areas, refer to Subsections 6.4.1 and 6.4.2.

6.6.1 When bit device memory is read or written


The bit device memory is handled in 1-bit (1-point) units or in 1-word (16-point) units.
The transfer data in each case is explained below.

1) In 1-bit (1-point) units


When the bit device memory is handled in 1-bit (1-point) units, a specified number of devices starting
from the specified head device are expressed in turn from the left end in "1 (31H)" for the ON status or "0
(30H)" for the OFF status.
Example: When indicating the ON/OFF status of five devices starting from M10
Head device Number
of
devices
M 0 0 1 0 0 5 1 0 1 0 1
4DH 30H 30H 31H 30H 30H 35H 31H 30H 31H 30H 31H

Indicates that M14 is ON.


Indicates that M13 is OFF.
Indicates that M12 is ON.
Indicates that M11 is OFF.
Indicates that M10 is ON.

2) In 1-word (16-point)" units


When the bit device memory is handled in 1-word (16-point) units, one word is expressed in 4-bit units in
turn from the most significant bit in hexadecimal.
Example: When indicating the ON/OFF status of 32 devices starting from M16
Because devices are handled in 16 point units,
the number of device is "02".
Head device Number Data Data
of
devices
M 0 0 1 6 0 2 A B 1 2 3 4 C D
4DH 30H 30H 31H 36H 30H 32H 41H 42H 31H 32H 33H 34H 43H 44H

A B 1 2 3 4 C D

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1 0 1 0 1 0 1 1 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 1 1 0 0 1 1 0 1
M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32

D-56
FX Series PLC User's Manual - Data Communication Edition 6 Control Procedures and Setting Methods
Computer Link 6.6 Transfer Data in Character Area

A
6.6.2 When word device memory is read or written

Common Items
In the case of word device memory, one word is expressed in 4-bit units in turn from the most significant bit in
hexadecimal.

Example 1: When indicating the contents stored in the data registers D350 and D351
B
Head device Number Data Data

N:N Network
of
devices
D 0 3 5 0 0 2 5 6 A B 1 7 0 F
44H 30H 33H 35H 30H 30H 32H 35H 36H 41H 42H 31H 37H 30H 46H

5 6 A B 1 7 0 F C

Parallel Link
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 1 0 1 0 1 1 0 1 0 1 0 1 0 1 1 0 0 0 1 0 1 1 1 0 0 0 0 1 1 1 1

Indicates that D350 stores "56ABH ("22187" Indicates that D351 stores "170FH ("5903"
in decimal)". in decimal)".
D
*1
Example 2: When indicating the contents stored in the 32-bit counter C200

Computer Link
Head device Number Data Data
of
devices
C N 2 0 0 0 1 1 2 3 4 5 6 7 8
44H 4EH 32H 30H 30H 30H 31H 31H 32H 33H 34H 35H 36H 37H 38H

E
1 2 3 4 5 6 7 8

Communication
Inverter
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0

Indicates that C200 stores "12345678H ("305,419,896" in decimal)".


F

(RS/RS2 Instruction)
Communication
Non-Protocol
*1. For indicating the current value of C200, use "CN200".

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-57
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 6.6 Transfer Data in Character Area

7. Commands
This chapter explains specification methods and specification examples of commands in dedicated protocols
used in computer link communication type.
For control procedures in dedicated protocols, refer to "6. Control Procedures and Setting Methods".
The table below shows a reference section for each command.
Applicable PLC
FX2(FX), FX2C, FX0N, Reference
Command Contents of processing FX3S, FX3G, FX3GC,
FX1S, FX1N, FX1NC, section
FX3U, FX3UC
FX2N, FX2NC
BR Reads bit devices in 1-point units. 7.1
Reads bit devices in 16-point units, or
WR 7.2
word devices in 1-point units.
Reads bit devices in 16-point units, or
QR 7.3
word devices in 1-point units.
BW Writes bit devices in 1-point units. 7.4
Writes bit devices in 16-point units, or
WW 7.5
word devices in 1-point units.
Writes bit devices in 16-point units, or
QW 7.6
word devices in 1-point units.
Specifies bit devices arbitrarily in 1-point
BT units, and sets or resets them (forcibly 7.7
sets them to ON or OFF).
Specifies bit devices arbitrarily in 16-point
units, and sets or resets them (forcibly
WT sets them to ON or OFF). Or specifies 7.8
word devices arbitrarily in 1-point units,
and writes data to them.
Specifies bit devices arbitrarily in 16-point
units, and sets or resets them (forcibly
QT sets them to ON or OFF). Or specifies 7.9
word devices arbitrarily in 1-point units,
and writes data to them.
Sets a PLC to RUN mode in remote
RR
control.
7.10
Sets a PLC to STOP mode in remote
RS
control.
PC Reads the PLC model name code. 7.11
Turns the global function ON or OFF in all
GW 7.12
linked PLCs.
Offers the on-demand function (by which
a PLC gives a sending request), and does 7.13
not offer any command.
Returns received characters back to the
TT 7.14
computer as they are.

D-58
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.1 BR Command [Reads Device Memory in 1-Bit Units]

A
7.1 BR Command [Reads Device Memory in 1-Bit Units]

Common Items
This section explains the control procedure specification method and specification example when the bit
device memory is read all at once.

1. Specification method B
The specification method in the control procedure format 1 is shown below:

N:N Network
Number of device points
Batch read command (unit: bit) Character area A (2 characters (hexadecimal)

"0 (30H)" indicates the OFF

Sum check
Message
wait time
status.
PLC No.

PLC No.
E A
Station

Station
Head device
C

code
"1 (31H)" indicates the ON
No.

No.
N BR (5 characters) C
status.
Computer side Q K

Parallel Link
PLC side

Sum check
S E

PLC No.
Station
Read device range

code
No.
T * T
specification
X X

Character area B D
* Data on specified number of device points

Computer Link
(Characters of specified number of device points)

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 256*1 (Use "00H" to specify 256 points.)
- Head device number + Number of device points -1 Maximum device number
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.
E

Communication
Inverter
*1. 54 in the FX0N and FX1S Series

2. Specification example
When reading the contents of five devices X040 to X044 in the PLC whose station number is 5 (while the
message waiting time is set to 100 ms)
(When X040 and X043 are OFF and X041, X042 and X044 are ON)
F

(RS/RS2 Instruction)
Communication
Non-Protocol
E This range is regarded as the A
N 0 5 F F B R A X 0 0 4 0 0 5 4 7 sum check target. C 0 5 F F
Q K
Computer side 05H 30H 35H 46H 46H 42H 52H 41H 58H 30H 30H 34H 30H 30H 35H 34H 37H 06H 30H 35H 46H 46H
PLC side
This range is regarded as the
sum check target.
S E
T 0 5 F F 0 1 1 0 1 T 0 5
G
X X

(FX2N-232IF)
Communication
Non-Protocol
02H 30H 35H 46H 46H 30H 31H 31H 30H 31H 03H 30H 35H

Indicates that X044 is


ON.
Indicates that X043 is
OFF. H
Indicates that X042 is
Communication
Programming

ON.
Indicates that X041 is
ON.
Indicates that X040 is
OFF.

Point
I
Maintenance
Remote

The message wait time is specified in 10-ms units within the range from 0 to 150 ms, and expressed in
hexadecimal within the range from 0 to FH. For example, "100 ms" is expressed as "A".

Apx.A
models
Discontinued

D-59
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.2 WR Command [Reads Device Memory in 1-Word Units]

7.2 WR Command [Reads Device Memory in 1-Word Units]


This section explains the control procedure specification method and specification examples when the word
device memory is read all at once or when the bit device memory is read (in 16-point units) all at once.

1. Specification method
The specification method in the control procedure format 1 is shown below:
Number of device points
Batch read command (unit: word) Character area A (2 characters (hexadecimal)

Sum check
Message
wait time
E A
PLC No.

PLC No.
One device uses 4 characters.
Station

Station
Head device

code
No.

No.
N WR Four digits (hexadecimal) C
(5 characters) express one word data.
Computer side
Q K

PLC side

Sum check
S E

PLC No.
Station
Read device range

code
No.
specification T * T
X X

Character area B
* Data on specified number of device points
(Characters of specified number of device points)

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 64*1 (32*1 in case of bit devices)
- Head device number + Number of device points ("Number of devices 16" in case of bit devices) -1
Maximum device number
- When 32-bit devices (CN200 to CN255) are read, one device point is handled as two word data.
Accordingly, up to 32 device points*2 can be specified.
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.
*1. Up to 13 device points in the FX0N and FX1S Series
*2. Up to 6 device points in the FX0N and FX1S Series

2. Specification examples
Example 1: When reading the contents of thirty-two devices from X040 to X077 in the PLC whose station
number is 5 (while the message waiting time is set to 0 ms)

E
N 0 5 F F W R 0 X 0 0 4 0 0 2 4 8
Q
Computer side 05H 30H 35H 46H 46H 57H 52H 30H 58H 30H 30H 34H 30H 30H 32H 34H 38H
PLC side
This range is regarded as the
sum check target.
A
This range is regarded as the C 0 5 F F
sum check target. K
06H 30H 35H 46H 46H

S E
T 0 5 F F 1 2 3 4 A B C D T 0 8
X X
02H 30H 35H 46H 46H 31H 32H 33H 34H 41H 42H 43H 44H 03H 30H 38H

1 2 3 4 A B C D

0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 1 0 1 0 1 0 1 1 1 1 0 0 1 1 0 1

X X X X X X X X X X X X X X X X X X
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
5 5 5 5 4 4 4 4 4 7 7 7 7 6 6 6 6 6
7 2 1 0 7 3 2 1 0 7 2 1 0 7 3 2 1 0

D-60
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.2 WR Command [Reads Device Memory in 1-Word Units]

A
Point

Common Items
The WR command handles data in 1-word units. When reading thirty-two devices from X040 to X077, specify
the number of device points as "02" (One point specifies 16 devices.)
Example 2: When reading the present value of two devices from T123 and T124 in the PLC whose station
number is 5 (while the message waiting time is set to 0 ms)
B
E

N:N Network
N 0 5 F F W R 0 T N 1 2 3 0 2 6 4 This range is regarded as the
Q sum check target.
Computer side 05H 30H 35H 46H 46H 57H 52H 30H 54H 4EH 31H 32H 33H 30H 32H 36H 34H
PLC side
This range is regarded as the S E
sum check target. T 0 5 F F 7 B C 9 1 2 3 4 T B 3
X X
02H 30H 35H 46H 46H 37H 42H 43H 39H 31H 32H 33H 34H 03H 42H 33H
C

Parallel Link
A Indicates that the current value of T123 is "7BC9H
C 0 5 F F (hexadecimal) (which is "31689" in decimal).
K Indicates that the current value of T124 is "1234H
06H 30H 35H 46H 46H
(hexadecimal) (which is "4660" in decimal).
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-61
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.3 QR Command [Reads Device Memory in 1-Word Units]

7.3 QR Command [Reads Device Memory in 1-Word Units]


This section explains the control procedure specification method and specification examples when the word
device memory is read all at once or when the bit device memory is read (in 16-point units) all at once.
This command is available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

1. Specification method
The specification method in the control procedure format 1 is shown below:
Batch read command Number of device points
(unit: word) (2 characters (hexadecimal)
Character area A
One device uses 4 characters.

Sum check
E Four digits (hexadecimal) A
PLC No.

Message

PLC No.
wait time
Station

Station
Head device express one data word .

code
N QR
No.

No.
(7 characters) C
Computer side Q K
PLC side Data on

Sum check
S E

PLC No.
Station
Read device range specified

code
No.
T number of T
specification
X device points X

Character area B

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 64 (32 for bit devices)
- Head device number + Number of device points ("Number of devices 16" for bit devices) -1
Maximum device number
- When 32-bit devices (CN00200 to CN00255) are read, one device point is handled as two word data.
Accordingly, up to 32 device points can be specified.
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.

2. Specification examples (For FX3U and FX3UC PLCs)


Example 1: When reading the contents of thirty-two devices from X040 to X077 in the PLC whose station
number is 5 (while the message waiting time is set to 0 ms)

E
N 0 5 F F Q R 0 X 0 0 0 0 4 0 0 2 A 2
Q
Computer side 05H 30H 35H 46H 46H 51H 52H 30H 58H 30H 30H 30H 30H 34H 30H 30H 32H 41H 32H
PLC side
This range is regarded as the sum
check target.
A
This range is regarded as the C 0 5 F F
sum check target. K
06H 30H 35H 46H 46H

S E
T 0 5 F F 1 2 3 4 A B C D T C 8
X X
02H 30H 35H 46H 46H 31H 32H 33H 34H 41H 42H 43H 44H 03H 43H 38H

1 2 3 4 A B C D

0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 1 0 1 0 1 0 1 1 1 1 0 0 1 1 0 1
X X X X X X X X X X
0 0 0 0 0 0 0 0 0 0
5 5 4 4 4 7 7 6 6 6
7 0 7 1 0 7 0 7 1 0

D-62
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.3 QR Command [Reads Device Memory in 1-Word Units]

A
Example 2: When reading the contents of two devices from R30000 to R30001 in the PLC whose station

Common Items
number is 5 (while the message waiting time is set to 0 ms)

E
N 0 5 F F Q R 0 R 0 3 0 0 0 0 0 2 9 B
Q
Computer side 05H 30H 35H 46H 46H 51H 52H 30H 52H 30H 33H 30H 30H 30H 30H 30H 32H 39H 42H B
PLC side

N:N Network
This range is regarded as the
sum check target.
A
This range is regarded as the C 0 5 F F
sum check target. K
06H 30H 35H 46H 46H

S E C
T 0 5 F F 7 B C 9 1 2 3 4 T B 3

Parallel Link
X X
02H 30H 35H 46H 46H 37H 42H 43H 39H 31H 32H 33H 34H 03H 42H 33H

Indicates that the value of R30000 is "7BC9H" (hexadecimal)


(which is "31689" in decimal).
Indicates that the value of R30001 is "1234H" (hexadecimal) D
(which is "4660" in decimal).

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-63
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.4 BW Command [Writes Device Memory in 1-Bit Units]

7.4 BW Command [Writes Device Memory in 1-Bit Units]


This section explains the control procedure specification method and shows a specification example when the
bit device memory is written all at once.

1. Specification method
The specification method in the control procedure format 1 is shown below:
Number of device points
Batch write command (unit: bit) Character area A (2 characters (hexadecimal)

Sum check
Message
wait time
E
PLC No.
Station

Head device

code
No.

N BW (5 characters) *
Computer side
Q

PLC side
A

PLC No.
Station
Written device range

No.
specification C
K
"0 (30H)" indicates the OFF status.
"1 (31H)" indicates the ON status.
* Data on specified number of device points
(Characters of specified number of device points)

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 160*1
- Head device number + Number of device points -1 Maximum device number
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal
respectively.
*1. 46 in the FX0N and FX1S Series

2. Specification example
When writing data to five devices from M903 to M907 in the PLC whose station number is 0 (while the
message waiting time is set to 0 ms)
This range is regarded as the sum check target.

E
N 0 0 F F B W 0 M 0 9 0 3 0 5 0 1 1 0 1 2 6
Q
Computer side 05H 30H 30H 46H 46H 42H 57H 30H 4DH 30H 39H 30H 33H 30H 35H 30H 31H 31H 30H 31H 32H 36H
PLC side
Specifies to turn M903 OFF. A
C 0 0 F F
Specifies to turn M904 ON. K
Specifies to turn M905 ON. 06H 30H 30H 46H 46H
Specifies to turn M906 OFF.
Specifies to turn M907 ON.

D-64
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.5 WW Command [Writes Device Memory in 1-Word Units]

A
7.5 WW Command [Writes Device Memory in 1-Word Units]

Common Items
This section explains the control procedure specification method and shows a specification examples when
the word device memory is written all at once or when the bit device memory is written (in 16-point units) all at
once.

1. Specification method
B

N:N Network
The specification method in the control procedure format 1 is shown below:
Number of device points
Batch write command (unit: word) Character area C (2 characters (hexadecimal)

Sum check
Message
wait time
E
PLC No.
Station

Head device

code
No.

N W W (5 characters) *

Parallel Link
Computer side
Q

PLC side
A

PLC No.
Station
Written device

No.
C
range specification
K
One device uses 4 characters. D
Four digits (hexadecimal) express

Computer Link
one data word.
* Data on specified number of device points
(Characters of specified number of device points)

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 64*1 (10 in case of bit devices) E
- Head device number + Number of device points ("Number of devices x 16" in case of bit devices) -1

Communication
Inverter
Maximum device number
- When 32-bit devices (CN200 to CN255) are written, one device point is handled as two word data.
Accordingly, up to 32 device points*2 can be specified.
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.
*1. Up to 11 device points in the FX0N and FX1S Series
F

(RS/RS2 Instruction)
Communication
Non-Protocol
*2. Up to 5 device points in the FX0N and FX1S Series

2. Specification examples
Example 1: When writing data to thirty-two devices from M640 to M671 in the PLC whose station number is
0 (while the message waiting time is set to 0 ms)
G

(FX2N-232IF)
Communication
Non-Protocol
E
N 0 0 F F W W 0 M 0 6 4 0 0 2 2 3 4 7 A B 9 6 0 5
Q
Computer side 05H 30H 30H 46H 46H 57H 57H 30H 4DH 30H 36H 34H 30H 30H 32H 32H 33H 34H 37H 41H 42H 39H 36H 30H 35H
PLC side
This range is regarded as the A
sum check target. C 0 0 F F
K H
06H 30H 30H 46H 46H
Communication
Programming

2 3 4 7 A B 9 6

0 0 1 0 0 0 1 1 0 1 0 0 0 1 1 1 1 0 1 0 1 0 1 1 1 0 0 1 0 1 1 0

M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
M
6
I
Maintenance
Remote

5 5 5 4 4 4 4 7 7 6 5 5 5 5
5 4 3 3 2 1 0 1 0 9 9 8 7 6

Point
The WW command handles data in 1-word units. When writing data to thirty-two devices from M640 to M671,
specify the number of device points as "02" (One point specifies 16 devices.) Apx.A
models
Discontinued

D-65
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.5 WW Command [Writes Device Memory in 1-Word Units]

Example 2: When writing data to two devices D0 and D1 in the PLC whose station number is 0 (while the
message waiting time is set to 0 ms)

E
N 0 0 F F W W 0 D 0 0 0 0 0 2 1 2 3 4 A C D 7 F 9
Q
Computer side 05H 30H 30H 46H 46H 57H 57H 30H 44H 30H 30H 30H 30H 30H 32H 31H 32H 33H 34H 41H 43H 44H 37H 46H 39H
PLC side
A
C 0 0 F F
K
This range is regarded as the sum check target.
06H 30H 30H 46H 46H
Indicates that "1234H (hexadecimal) (which is "4660" in decimal) is written to D0.
Indicates that "ACD7H (hexadecimal) (which is "-21289" in decimal) is written to D1.

D-66
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.6 QW Command [Writes Device Memory in 1-Word Units]

A
7.6 QW Command [Writes Device Memory in 1-Word Units]

Common Items
This section explains the control procedure specification method and shows a specification examples when
the word device memory is written all at once or when the bit device memory is written (in 16-point units) all at
once.
This command is available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs. B

N:N Network
1. Specification method
The specification method in the control procedure format 1 is shown below:
Batch write command Number of device points
(unit: word) (2 characters (hexadecimal)
Character area C C

Parallel Link
Data on

Sum check
E
PLC No.

Message
wait time
Station

Head device specified

code
N QW
No.

(7 characters) number of
Computer side Q device points
PLC side A

PLC No.
Station
Written device range
D

No.
C
specification
K

Computer Link
One device uses 4 characters. Four digits
(hexadecimal) express one data word.

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 64 (10 in case of bit devices)
- Head device number + Number of device points ("Number of devices 16" in case of bit devices) -1 E
Maximum device number

Communication
Inverter
- When 32-bit devices (CN00200 to CN00255) are written, one device point is handled as two word data.
Accordingly, up to 32 device points can be specified.
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.

2. Specification examples (For FX3U and FX3UC PLCs) F


Example 1: When writing data to thirty-two devices from M640 to M671 in the PLC whose station number is

(RS/RS2 Instruction)
Communication
Non-Protocol
5 (while the message waiting time is set to 0 ms)

E
N 0 5 F F Q W 0 M 0 0 0 6 4 0 0 2 2 3 4 7 A B 9 6 6 4
Q
Computer side 05H 30H 35H 46H 46H 51H 57H 30H 4DH 30H 30H 30H 36H 34H 30H 30H 32H 32H 33H 34H 37H 41H 42H 39H 36H 36H 34H G
PLC side
A

(FX2N-232IF)
Communication
Non-Protocol
This range is regarded as the
sum check target. C 0 5 F F
K
06H 30H 35H 46H 46H

2 3 4 7 A B 9 6

0 0 1 0 0 0 1 1 0 1 0 0 0 1 1 1 1 0 1 0 1 0 1 1 1 0 0 1 0 1 1 0
H
Communication
Programming

M M M M M M M M M M
6 6 6 6 6 6 6 6 6 6
5 4 4 4 4 7 6 6 5 5
6 8 7 1 0 1 4 3 7 6

I
Maintenance
Remote

Apx.A
models
Discontinued

D-67
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.6 QW Command [Writes Device Memory in 1-Word Units]

Example 2: When writing data to two devices from R30000 to R30001 in the PLC whose station number is 5
(while the message waiting time is set to 0 ms)

E
N 0 5 F F Q W 0 R 0 3 0 0 0 0 0 2 7 B C 9 1 2 3 4 5 F
Q
Computer side 05H 30H 35H 46H 46H 51H 57H 30H 52H 30H 33H 30H 30H 30H 30H 30H 32H 37H 42H 43H 39H 31H 32H 33H 34H 35H 46H
PLC side
A
C 0 5 F F
K
This range is regarded as the
sum check target. 06H 30H 35H 46H 46H

Indicates that "7BC9H (hexadecimal) (which is "31689" in decimal) is written to R30000.


Indicates that "1234H (hexadecimal) (which is "4660" in decimal) is written to R30001.

D-68
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.7 BT Command [Tests Device Memory in 1-Bit Units (by Writing Arbitrarily)]

A
7.7 BT Command [Tests Device Memory in 1-Bit Units (by Writing Arbitrarily)]

Common Items
This section explains the control procedure specification method and shows a specification example when the
bit device memory is specified arbitrarily and written all at once.

1. Specification method B
The specification method in the control procedure format 1 is shown below:

N:N Network
Test (write arbitrarily) command (unit: bit) Character area A

Set or reset

Set or reset

Sum check
Message
wait time
PLC No.
E
Station

Device Device

code
No.

N BT *
Computer side
Q (5 characters) (5 characters)
C

Parallel Link
PLC side
A

PLC No.
Station
1 character

No.
"0 (30H)" indicates reset (setting to OFF). C
"1 (31H)" indicates set (setting to ON). K

* Number of device points


(2 characters (hexadecimal)) D

Computer Link
Point

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 20*1
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal. E
*1. 10 in the FX0N and FX1S Series

Communication
Inverter
2. Specification example
When writing data for setting M50 to ON, S100 to OFF and Y001 to ON in the PLC whose station number is 5
(while the message waiting time is set to 0 ms)
This range is regarded as the sum check target. F

(RS/RS2 Instruction)
Communication
Non-Protocol
E
N 0 5 F F B T 0 0 3 M 0 0 5 0 1 S 0 1 0 0 0 Y 0 0 0 1 1 E C
Q
Computer side 05H 30H 35H 46H 46H 42H 54H 30H 30H 33H 4DH 30H 30H 35H 30H 31H 53H 30H 31H 30H 30H 30H 59H 30H 30H 30H 31H 31H 45H 43H
PLC side
A
Set (ON) Reset (OFF) Set (ON)
C 0 5 F F
K
G

(FX2N-232IF)
Communication
Non-Protocol
06H 30H 35H 46H 46H

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-69
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.8 WT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)]

7.8 WT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)]
This section explains the control procedure specification method and shows a specification example when the
word device memory and bit device memory (in 16-point units) are specified arbitrarily and written all at once.
Word devices and bit devices (in 16-point units) can be specified together. However, the WT command
cannot handle 32-bit word devices C200 to C255 (CN200 to CN255).

1. Specification method
The specification method in the control procedure format 1 is shown below:
Test (write arbitrarily) command (unit: word) Character area A

Message
wait time
E Number of
PLC No.
Station

device points Device Data Device Data


No.

N WT (2 characters (5 characters) (4 characters) (5 characters) (4 characters)


Q (hexadecimal))
Computer side
PLC side
When specifying bit devices, One device uses 4 characters. Four digits
specify the head device. (hexadecimal) express one data word.
Sum check
code

A
PLC No.
Station
No.

C
K

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 10*1 (in unit of 10*1 in case of bit devices (One unit indicates 16 points.))
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.
3) The WT command cannot handle 32-bit word devices C200 to C255 (CN200 to CN255).
*1. 6 in the FX0N and FX1S Series

D-70
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.8 WT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)]

A
2. Specification example

Common Items
When writing data for setting the current value of D500 to "1234H", Y100 to Y117 to "BCA9H" and the current
value of C100 to "64H" in the PLC whose station number is 5 (while the message waiting time is set to 0 ms)
This range is regarded as the sum check target.

E B
N 0 5 F F W T 0 0 3 D 0 5 0 0 1 2 3 4 Y 0 1 0 0 B C A 9

N:N Network
Q
Computer side 05H 30H 35H 46H 46H 57H 54H 30H 30H 33H 44H 30H 35H 30H 30H 31H 32H 33H 34H 59H 30H 31H 30H 30H 42H 43H 41H 39H
PLC side

B C A 9
C
Indicates that "1234H (which is "4660"

Parallel Link
1 0 1 1 1 1 0 0 1 0 1 0 1 0 0 1
in decimal)" is written to D500.
Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
This range is regarded as the 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0
sum check target. 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Each bit is reset (OFF) in the case of "0", and
D
set (ON) in the case of "0".

Computer Link
C N 1 0 0 0 0 6 4 0 7

43H 4EH 31H 30H 30H 30H 30H 36H 34H 30H 37H

A
C 0 5 F F
K E
Indicates that "64H (which is "100" in decimal)" 06H 30H 30H 46H 46H

Communication
Inverter
is written to the current value of C100.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-71
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.9 QT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)]

7.9 QT Command [Tests Device Memory in 1-Word Units (by Writing Arbitrarily)]
This section explains the control procedure specification method and shows a specification example when the
word device memory and bit device memory (in 16-point units) are specified arbitrarily and written all at once.
Word devices and bit devices (in 16-point units) can be specified together. However, the QT command cannot
handle 32-bit word devices C200 to C255 (CN00200 to CN00255).
This command is available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

1. Specification method
The specification method in the control procedure format 1 is shown below:
Command for test (by writing arbitrarily in 1-word units) Character area A

(2 characters)
device points
Message
wait time
PLC No.

E
Number of
Station

Data on
Device Device
No.

N QT devices
Q (7 characters) (4 characters) (7 characters)
Computer side
PLC side
Sum check

Data on
code

devices
(4 characters)

A
PLC No.
Station
No.

C
K

1) Specify the device point range while satisfying the following conditions:
- 1 Number of device points 10 (in unit of 10 in case of bit devices (One unit indicates 16 points.))
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal.
3) Word devices and bit devices (in 16-point units) can be specified together.
4) The QT command cannot handle 32-bit word devices C200 to C255 (CN00200 to CN00255).

2. Specification example
When writing data for setting the current value of R12000 to "1234H" and Y100 to Y117 to "BCA9H" in the
PLC whose station number is 5 (while the message waiting time is set to 0 ms)
This range is regarded as the sum check target.

E
N 0 5 F F Q T 0 0 2 R 0 1 2 0 0 0 1 2 3 4
Q
Computer side 05H 30H 35H 46H 46H 51H 57H 30H 30H 32H 52H 30H 31H 32H 30H 30H 30H 31H 32H 33H 34H
PLC side
This range is regarded as the
sum check target.

Y 0 0 0 1 0 0 B C A 9 E 3

59H 30H 30H 30H 31H 30H 30H 42H 43H 41H 39H 45H 33H

A
C 0 5 F F
K
06H 30H 35H 46H 46H
B C A 9

1 0 1 1 1 1 0 0 1 0 1 0 1 0 0 1

Y Y Y Y Y
1 1 1 1 1
1 1 0 0 0
7 0 7 1 0

D-72
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.10 RR/RS Command [Remotely Sets PLC to RUN/STOP Mode]

A
7.10 RR/RS Command [Remotely Sets PLC to RUN/STOP Mode]

Common Items
This section explains the control procedure specification method and shows a specification example when the
computer remotely sets the PLC mode to RUN or STOP.

7.10.1 Contents of remote control to set RUN or STOP mode B

N:N Network
When the computer executes remote control of the PLC mode to RUN or STOP, the forced RUN mode is
activated in the PLC, and the special auxiliary relays M8035, M8036 and M8037 are controlled as follows:
Remote RUN mode control
When the RR command (which sets remote RUN mode in control) is executed in the computer, the PLC
sets M8035 and M8036 to activate the forced RUN mode. C
If the RR command is executed while the PLC is in RUN mode, however, the PLC status does not change,

Parallel Link
and the PLC returns the remote error code (18H) to the computer.
Remote STOP mode control
When the RS command (which sets remote STOP mode in control) is executed in the computer, the PLC
executes the following processing.
If the RS command is executed while the PLC is in STOP mode, the PLC status does not change, and the D
PLC returns the remote error code (18H) to the computer.

Computer Link
Remote control to set to
STOP mode

NO E
Forced RUN mode

Communication
Inverter
YES

Special auxiliary relay PLC returns remote error code (18H) to


M8037 is set to ON. computer, and PLC status does not change.

F
Special auxiliary relays

(RS/RS2 Instruction)
Communication
Non-Protocol
M8035, M8036 and
M8037 are set to OFF.

PLC switches to
STOP mode.
G

(FX2N-232IF)
Communication
Non-Protocol
7.10.2 Condition validating remote control to set RUN or STOP mode

Remote RUN mode control


The PLC is in STOP mode.
(The built-in RUN/STOP selector switch is set to STOP.) H
(In an FX2(FX) or FX2C PLC, the RUN terminal in the PLC is OFF, and the built-in RUN/STOP selector
Communication
Programming

switch is set to STOP.)


Remote STOP mode control
The PLC is in RUN mode (forced RUN mode) without using the RUN terminal or built-in RUN/STOP
selector switch.
I
Maintenance
Remote

Point
When the PLC power is turned OFF and then ON after the RR command is executed by the computer, all of
the special auxiliary relays M8035, M8036 and M8037 are set to OFF. As a result, the PLC switches to STOP
mode.
Apx.A
models
Discontinued

D-73
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.10 RR/RS Command [Remotely Sets PLC to RUN/STOP Mode]

7.10.3 Remote control specification method and specification examples


This subsection explains the control procedure specification method and specification examples when remote
RUN or STOP mode control is executed.

1. Specification method
The specification method in the control procedure format 1 is shown below:
RR command to remotely set the PLC to the RUN mode
RS command to remotely set the PLC to the STOP mode

Sum check
Message
wait time
E
PLC No.
RR
Station

code
No.

N or
Q RS
Computer side
PLC side
A

PLC No.
Station
No.
C
K

Express the station number, PLC number, number of device points and sum check code in hexadecimal
respectively.

2. Specification examples
Example 1: When remotely setting the PLC whose station number is 5 to RUN mode (while the message
waiting time is set to 0 ms)
This range is regarded as
the sum check target.

E
N 0 5 F F R R 0 C 5
Q
Computer side 05H 30H 35H 46H 46H 52H 52H 30H 43H 35H
PLC side
A
C 0 5 F F
K
06H 30H 35H 46H 46H

Example 2: When remotely setting the PLC whose station number is 0 to STOP mode (while the message
waiting time is set to 0 ms)
This range is regarded as
the sum check target.

E
N 0 0 F F R S 0 C 1
Q
Computer side 05H 30H 30H 46H 46H 52H 53H 30H 43H 31H
PLC side A
C 0 0 F F
K
06H 30H 30H 46H 46H

D-74
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.11 PC Command [Reads PLC Model Name]

A
7.11 PC Command [Reads PLC Model Name]

Common Items
This section explains the control procedure specification method and specification example when the model
name of a PLC linked to the computer is read.

7.11.1 PLC model name (CPU) and read contents B

N:N Network
Model name code Model name code
PLC model name (CPU) PLC model name (CPU)
(hexadecimal) (hexadecimal)
FX2(FX), FX2C 8DH A2CCPU 9AH
FX0N 8EH A2USCPU 82H
FX1S F2H A2CPU-S1, A2USCPU-S1 83H
C

Parallel Link
FX1N, FX1NC 9EH A3CPU, A3NCPU A3H
FX2N, FX2NC 9DH A3ACPU 94H
FX3S F5H A3HCPU, A3MCPU A4H
FX3G, FX3GC F4H A3UCPU 84H
FX3U, FX3UC F3H A4UCPU 85H D
A0J2HCPU 98H A52GCPU 9AH

Computer Link
A1CPU, A1NCPU A1H A73CPU A3H
A1SCPU, A1SJCPU 98H A7LMS-F A3H
A2CPU(-S1), A2NCPU(-S1), A2SCPU A2H AJ72P25/R25 ABH
A2ACPU 92H AJ72LP25/BR15 8BH E
A2ACPU-S1 93H

Communication
Inverter
7.11.2 Control procedure specification method and specification example

1. Specification method
The specification method for control procedure format 1 is shown below:
F

(RS/RS2 Instruction)
Communication
Non-Protocol
PC command to read the PLC model name
Sum check
Message
wait time

E A
PLC No.

PLC No.
Station

Station
code
No.

No.

N PC C
Computer side
Q Character area B K
G
PLC side

(FX2N-232IF)
Communication
Non-Protocol
Sum check

S E
PLC No.
Station

PLC model
code
No.

T name T
X (2 characters) X

Express the station number, PLC number, number of device points and sum check code in hexadecimal
respectively. H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-75
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.11 PC Command [Reads PLC Model Name]

2. Specification example
When reading the model name of the PLC whose station number is 15 (while the message waiting time is set
to 0 ms)
This range is regarded as
the sum check target.

E This range is regarded as A


N 0 F F F P C 0 C 5 the sum check target. C 0 F F F
Q K
Computer side 05H 30H 46H 46H 46H 50H 43H 30H 43H 35H 06H 30H 46H 46H 46H
PLC side
S E
T 0 F F F 8 D T 8 1
X X
02H 30H 46H 46H 46H 38H 44H 03H 38H 31H

The example above indicates that the model name of the target PLC is the FX2(FX) or FX2C Series.

D-76
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.12 GW Command [Offers Global Function]

A
7.12 GW Command [Offers Global Function]

Common Items
The global function executed in the computer sets a special auxiliary relay to ON or OFF in all PLCs linked to
the computer in the multi-drop link method. For A Series PLCs, however, refer to the respective A Series PLC
manual.
This section explains the control procedure specification method and specification example when the global B
function is used.

N:N Network
7.12.1 Contents of control
The global function sets a special auxiliary relay to ON or OFF in all FX Series PLCs linked to the computer.
M8126 is set to ON or OFF in PLCs except the FX3G, FX3GC, FX3U and FX3UC Series.
In FX3G, FX3GC, FX3U and FX3UC PLCs, M8126 is set to ON or OFF in computer link using ch1, and M8426 is
C

Parallel Link
set to ON or OFF in computer link using ch2.
In A Series PLCs, Xn2 is set to ON or OFF for all PLCs linked to the computer.
In the control procedure, specify the station number "FFH" so that all stations are handled as targets.
If any value other than "FFH" is specified, a special auxiliary relay is set to ON or OFF only in a station with
the specified station number.
D
In this function, PLCs do not give any response to the GW command from the computer.

Computer Link
When the PLC power is turned OFF or when the PLC is set to STOP mode, the special auxiliary relay
M8126 or M8426 is set to OFF and the processing request in the global function is cleared.

7.12.2 Global function control procedure specification method and specification example
E
This subsection explains the control procedure specification method and specification example when the

Communication
Inverter
global function is executed from the computer.

1. Specification method
The specification method in the control procedure format 1 is shown below:
GW command to execute
the global command
Character area A F

(RS/RS2 Instruction)
Communication
Non-Protocol
Sum check
Message
wait time

E
PLC No.

Factor
Station

code
No.

N GW number
Q (1 character)
Computer side
PLC side When the data value is "1 (31H)", M8126 or M8426 is set to ON.
When the data value is "0 (30H)", M8126 or M8426 is set to OFF. G

(FX2N-232IF)
Communication
Non-Protocol
Express the station number, PLC number, number of device points and sum check code in hexadecimal
respectively.

2. Specification example
When setting to ON the special auxiliary relay M8126 of M8426 in all FX PLCs (In all of A Series PLCs in
computer link, however, Xn2 is set to ON.) H
Communication
Programming

This range is regarded as the sum


check target.

E
N F F F F G W 0 1 1 7
Q
Computer side 05H 46H 46H 46H 46H 47H 57H 30H 31H 31H 37H I
PLC side Indicates that the special auxiliary relay M8126 or
Maintenance
Remote

M8426 is set to ON in target stations.


Specify "FFH" for handling all stations as targets.
When handling only one station as a target, specify the station
number (ranging from 00 to 0F) of the target station.

Apx.A
models
Discontinued

D-77
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

7.13 On-demand Function


When there is data to be sent from a PLC to the computer, the on-demand function can specify the data
register area storing the data to be sent, and let the PLC start sending.
When data is sent between the computer and a PLC, only the computer can start data transmission.
When there is emergency data to be sent from a PLC to the computer, the on-demand function is applicable
to let the PLC begin sending data to the computer.
PLC
D8127 Head device number (n)
D8128 Data length (m)
Sequence
Computer
program D(n)
D(n+m-1)

Point
This function is applicable when the computer and the PLC CPU have the 1-to-1 configuration.

7.13.1 Special data registers and special auxiliary relays used in on-demand function
The tables below show the special data registers and special auxiliary relays used in the on-demand function.

1. In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs and when ch1 is used in FX3G, FX3GC,
FX3U and FX3UC PLCs
Device Name Description
Remains ON while the on-demand function is being executed.
On-demand send
M8127*1 processing ON: On-demand data is being sent.
OFF: Sending of on-demand data is completed.
Turns ON when an error is included in a specified value to be sent in the on-
demand function.
M8128 On-demand error flag
ON: Error is included.
OFF: Error is not included.
Specifies the unit (byte or word) of data handled in the on-demand function.
On-demand byte/word
M8129 ON: Unit = Byte (8-bit)
changeover
OFF: Unit = Word (16-bit)
On-demand head device Sets the head data register device number containing the data to be sent
D8127
number specification using the on-demand function in a sequence program.
On-demand data quantity Sets the amount of data to be sent using the on-demand function in a
D8128
specification sequence program.

*1. FX0N, FX1S, FX1N and FX1NC PLCs do not support this device.

D-78
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

A
2. When ch2 is used in FX3G, FX3GC, FX3U and FX3UC PLCs

Common Items
Device Name Description
Remains ON while the on-demand function is being executed.
On-demand send
M8427 ON: On-demand data is being sent.
processing
OFF: Sending of on-demand data is completed.
Turns ON when an error is included in a specified value to be sent in the on- B
demand function.

N:N Network
M8428 On-demand error flag
ON: Error is included.
OFF: Error is not included.
Specifies the unit (byte or word) of data handled in the on-demand function.
On-demand byte/word
M8429 ON: Unit = Byte (8-bit)
changeover
OFF: Unit = Word (16-bit) C
On-demand head device Sets the head data register device number containing the data to be sent

Parallel Link
D8427
number specification using the on-demand function in a sequence program.
On-demand data quantity Sets the amount of data to be sent using the on-demand function in a
D8428
specification sequence program.

Point
D

Computer Link
The on-demand send processing signal (M8127 or M8427) turns ON when the PLC gives a request to
send data to the computer, and turns OFF when sending of the specified data is completed. Use this signal
for interlock to prevent giving two or more on-demand requests at the same time.
While the on-demand send processing signal is ON, the PLC cannot receive commands sent from the
computer. E

Communication
Inverter
Amount of on-demand data and number of data registers used for sending according to the unit
specification (word or byte)
When the specified unit is a word:
The amount of on-demand data is equivalent to the number of data registers to be sent.
When the specified unit is a byte: F
Two on-demand data units use one data register for sending.

(RS/RS2 Instruction)
Communication
Non-Protocol
Example: When the amount of on-demand data is "5", the number of data registers for sending is "3".

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-79
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

7.13.2 Control procedures in on-demand function


This subsection explains the control procedures for the on-demand function.
When using ch2 in an FX3G, FX3GC, FX3U or FX3UC Series PLC, exchange special auxiliary relays (M) and
special data registers (D) according to the table below.
All PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs
FX3G, FX3GC, FX3U and FX3UC PLCs (ch2)
FX3G, FX3GC, FX3U and FX3UC PLCs (ch1)
M8127*1 M8427
M8128 M8428
M8129 M8429
D8127 D8427
D8128 D8428

*1. FX0N, FX1S, FX1N and FX1NC PLCs do not support this device.
1) Control procedure in the PLC

Sending of on-demand data

Checks unit (word or byte) of


data to be sent ........ It is checked whether M8129 is ON or OFF.
ON: Unit = byte (8-bit)
OFF: Unit = word (16-bit)
Writes data to be sent to data
registers ........ Data to be sent is written to data registers.

Resets on-demand error ........ The on-demand error flag M8128 turns OFF.
(While M8128 is ON, the on-demand function is disabled.)

Starts on-demand function ........ The head device (data register) number storing the on-
demand data is written to D8127, and the amount of data is
written to D8128.
When a request is accepted, M8127 is set to ON.
When sending is complete, M8127 turns OFF.
Checks for sending error ........ If the on-demand error flag M8128 is ON, it means that data
was not sent due to an error in the specified value to be sent.
When there
is error When there is
no error

Sending is completed

D-80
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

A
2) Control procedure in the computer

Common Items
Receiving of on-demand data

Judges whether receive data is ........ To the on-demand data, the PLC adds "FE" as the PLC B
on-demand data or data given
number. Only when the PLC number of the received data is

N:N Network
by command execution.
"FE", the received data should be processed as on-demand
data.

Data processing
C

Parallel Link
Completion of receiving

3) Time chart when the on-demand function is requested


While the computer is sending data D

Computer Link
E A
N [2] On-demand data C
Q K
Computer side [3]
PLC side
S
T E
X

Communication
Inverter
[1]
On-demand send processing
M8127

PLC
Writes data to be sent and
amount of data to be sent.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
[1] As soon as an on-demand request is given, the on-demand send processing signal M8127 turns ON.
[2] After receiving of command data (ENQ ~) from the computer is completed, the PLC sends on-demand
data.
[3] After the sending of on-demand data is complete, the PLC sends response data (STX ~) to the
command data (ENQ ~). G

(FX2N-232IF)
Communication
Non-Protocol
While the computer is receiving data
[3]

E A
N
Q
On-demand data C
K
H
Computer side
Communication
Programming

PLC side
S
T
X

On-demand send processing I


M8127 [2]
Maintenance
Remote

[1]

Writes data to be sent and


PLC amount of data to be sent.

[1] As soon as an on-demand request is given, the on-demand send processing signal M8127 turns ON.
[2] After the sending of response data (STX ~) to the command data (ENQ ~) from the computer is
Apx.A
models
Discontinued

completed, the PLC sends on-demand data.


[3] After the receiving of on-demand data is complete, the computer sends response data (ACK ~) to the
sending of the response data (STX ~) from the PLC.

D-81
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

7.13.3 On-demand function specification method and specification examples


This subsection explains the on-demand function specification method and specification examples.
When using ch2 in an FX3G, FX3GC, FX3U or FX3UC Series PLC, exchange special auxiliary relays (M) and
special data registers (D) according to the table below.
All PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs
FX3G, FX3GC, FX3U and FX3UC PLCs (ch2)
FX3G, FX3GC, FX3U and FX3UC PLCs (ch1)
M8127*1 M8427
M8128 M8428
M8129 M8429
D8127 D8427
D8128 D8428

*1. FX0N, FX1S, FX1N and FX1NC PLCs do not support this device.

1. Specification method
The specification method in the control procedure format 1 is shown below:
Added by PLC

Computer side
PLC side

Sum check
S E
PLC No.
Station

Data to be

code
No.

T T
sent
X X

ON
On-demand send processing OFF
M8127
Write the head device number (data register)
Writes data to be sent and
storing the data to be sent to the special data
PLC register D8127.
amount of data to be sent.
Write the amount of data to the special data
register D8218.

1) Specify the data quantity specification range while satisfying the following condition:
- Amount of data 40H (= 64 in decimal)
2) The PLC adds "FE" as the PLC number.
3) Express the station number, PLC number, number of device points and sum check code in hexadecimal.

IMPORTANT
Do not use the on-demand function when the system configuration is not 1-to-1 type.
If the on-demand function is used in the multi-drop link system in which the computer and PLC CPUs have
the 1-to-N configuration, the transfer data and on-demand send data in the control procedure format 1 or 4
are destroyed, and normal data sending is not possible.

D-82
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

A
2. Specification example 1

Common Items
When sending the data stored in the data registers D100 and D101 by a trigger from a sequence program
(when the station number is 0 and the data unit to be sent is set to "word")

Computer side The PLC number "FE" is automatically added by the PLC.
PLC side S E B
T 0 0 F E 1 2 3 4 5 6 7 8 T 9 2

N:N Network
X X
02H 30H 30H 46H 45H 31H 32H 33H 34H 35H 36H 37H 38H 03H 39H 32H

M8127

Writes data to be
C
sent and amount of

Parallel Link
PLC It turns ON when an error is
data to be sent.
included in the specified
value for sending.
On-demand D8127 100 M8128 ON/OFF
command [1] D8128 2 M8129 OFF
[2] Data is sent in 4-bit units
D100
D101
1234H
5678H starting from highest-order bits. D

Computer Link
Sequence program example

M8000
0 M8129 ........ The data unit is set to "word" value.

3
X000 M8002
PLS M0 ........
The startup command is the pulse operation E
type.

Communication
Inverter
M0 M8127
7 MOV H1234 D100
........ Data to be sent is set.
MOV H5678 D101
The on-demand error flag is reset.
RST M8128 ........ (The on-demand function is disabled while
M8128 is ON.) F
RST Y000

(RS/RS2 Instruction)
Communication
Non-Protocol
RST Y001

MOV K100 D8127 The head device number storing the data to be
........ sent and the amount of data are specified, and

M8127 M8128
MOV K2 D8128 the on-demand function is started up.
G
33 SET Y000

(FX2N-232IF)
Communication
Non-Protocol
M8127 M8128
........ On-demand error is checked for, and the check
37 SET Y001 result is output.

40 END
M8128 OFF: Data is sent normally.
H
ON: Data is not sent because an
Communication
Programming

error occurred.

I
Maintenance
Remote

Apx.A
models
Discontinued

D-83
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.13 On-demand Function

3. Specification example 2
When sending the data stored in the data registers D100 and D101 by a trigger from a sequence program
(when the station number is 0 and the data unit to be sent is set to "byte")

The PLC number "FE" is automatically added by the PLC.


Computer side
PLC side S E
T 0 0 F E 3 4 1 2 7 8 5 6 T 9 2
X X
02H 30H 30H 46H 45H 31H 32H 33H 34H 37H 38H 35H 36H 03H 39H 32H

M8127

Writes data to be
PLC sent and amount of It turns ON when an error is
data to be sent.
included in the specified
value for sending.
On-demand D8127 100 M8128 ON/OFF
command [1] D8128 4 M8129 ON
Data is sent in 4-bit units, in
[2] D100 1234H the order "lowest-order 8-bit
D101 5678H
highest-order 8-bit".

Sequence program example

M8000
0 M8129 ........ The data unit is set to "byte" value.
X000 M8002
3 PLS M0 ........ The startup command is the pulse operation type.
M0 M8127
7 MOV H1234 D100
........ Data to be sent is set.
MOV H5678 D101
The on-demand error flag is reset.
RST M8128 ........ (The on-demand function is disabled while M8128 is
ON.)
RST Y000

RST Y001

MOV K100 D8127 The head device number storing the data to be sent
........ and the amount of data are specified, and the on-
MOV K4 D8128 demand function is started up.
M8127 M8128
33 SET Y000
M8127 M8128 ........ On-demand error is checked for, and the check result
37 is output.
SET Y001

40 END
M8128 OFF: Data is sent normally.
ON: Data is not sent because an
error occurred.

D-84
FX Series PLC User's Manual - Data Communication Edition 7 Commands
Computer Link 7.14 TT Command [Loop-back Test]

A
7.14 TT Command [Loop-back Test]

Common Items
The loop-back test function checks whether or not communication between the computer and a PLC is normal.
This section explains the control procedure specification method and specification example when the loop-
back test function is used.

1. Specification method
B

N:N Network
The specification method in the control procedure format 1 is shown below:

Loop-back test command Character area A

Data

Character

Sum check
Message
wait time
E
PLC No.
Station

length
(Data for

code
No.

N TT character
Q 2 characters (hexadecimal)
Computer side length)

Parallel Link
PLC side Data

Character

Sum check
S E

PLC No.
Station

length
2 characters (hexadecimal) (Data for

code
No.
T character
T
X length) X

Character area B D

Computer Link
1) Specify the character length specification range while satisfying the following condition:
- 1 Character length 254
2) Express the station number, PLC number, number of device points and sum check code in hexadecimal
respectively.
E
2. Specification example

Communication
Inverter
When executing the loop-back test to the PLC whose station number is 0 using the data "ABCDE" (while the
message waiting time is set to 0 ms)

This range is regarded as the


sum check target.
F
E

(RS/RS2 Instruction)
Communication
Non-Protocol
N 0 0 F F T T 0 0 5 A B C D E 7 8 This range is regarded as
Q the sum check target.
Computer side 05H 30H 30H 46H 46H 54H 54H 30H 30H 35H 41H 42H 43H 44H 45H 37H 38H
PLC side
S E
T 0 0 F F 0 5 A B C D E T A 3
X X G
02H 30H 30H 46H 46H 30H 35H 41H 42H 43H 44H 45H 03H 41H 33H

(FX2N-232IF)
Communication
Non-Protocol
Both data should be equivalent.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-85
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Computer Link 8.1 Checking FX PLC Version Applicability

8. Troubleshooting
This chapter explains troubleshooting.

8.1 Checking FX PLC Version Applicability


Verify that the FX PLC main unit is an applicable version.
For the version applicability check, refer to Section 1.3.

8.2 Checking Communication Status Based on LED Indication


Check the status of the "RD(RXD)" and "SD(TXD)" indicator LEDs provided in the optional equipment.

LED status
Operation status
RD(RXD) SD(TXD)
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received.
Off Off Data is not sent or received.
While computer link is executed normally, both LEDs flash brightly.
If they do not flash, check the wiring, station number settings and communication setting.

8.3 Checking Installation and Wiring

1. Mounting status
If the communication equipment is not securely connected to the PLC, communication is not possible.
For mounting method, refer to the respective communication equipment manual.

2. Power supply (for FX0N-485ADP)


The FX0N-485ADP requires a driving power supply. Verify that the power supply is provided correctly.

3. Wiring
Verify that the wiring to all communication equipment is correct. If the communication equipment is wired
incorrectly, communication is not possible.
For wiring method check, refer to Chapter 4.

8.4 Checking Sequence Program

1. Communication setting in the sequence program


Verify that the parallel link and N:N Network are not set. Verify that the communication format (D8120, D8400
and D8420) is set correctly. Communication is not possible if a communication port is set twice or more.
After changing any setting, make sure to reboot the PLCs power.

2. Communication setting using parameters


Verify that the communication settings using parameters is suitable to the purpose of use.
If the communication settings are not suitable to the purpose of use, communication will not function correctly.
After changing any setting, make sure to reboot the PLCs power.

3. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in computer link.
After changing the setting, make sure to reboot the PLC's power.

D-86
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Computer Link 8.4 Checking Sequence Program

A
4. Presence of VRRD and VRSC instructions

Common Items
1) Except FX3G, FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, reboot the PLCs power.
2) In FX3G PLC
- In the case of the 14 points and 24-point type
B

N:N Network
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, reboot the PLC's power.
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions. C
After deleting these instructions, reboot the PLC's power.

Parallel Link
3) In FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power. D

Computer Link
5. Presence of RS instruction (except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS instruction is not used in the program.
If this instruction is used, delete it, reboot the PLCs power.
6. Presence of RS and RS2 instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel. E
If these instructions are used for the same channel, delete them, reboot the PLCs power.

Communication
Inverter
7. Presence of EXTR instruction (in FX2N and FX2NC PLCs)
Verify that the EXTR instruction is not used in the program.
If this instruction is used, delete it, then reboot the PLCs power.

8. Presence of IVCK, IVDR, IVRD, IVWR, IVBWR*1, and IVMC instructions (in FX3S, FX3G, F
FX3GC, FX3U and FX3UC PLCs)

(RS/RS2 Instruction)
Communication
Non-Protocol
Verify that the IVCK, IVDR, IVRD, IVWR, IVBWR and IVMC instructions are not being used for the same
channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.
*1. Only available for FX3U and FX3UC PLCs.
9. Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
G

(FX2N-232IF)
Communication
Non-Protocol
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.

10.Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and
FX3UC PLCs)
Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the H
same channel.
Communication
Programming

If these instructions are used for the same channel, delete them, reboot the PLCs power.

I
Maintenance
Remote

Apx.A
models
Discontinued

D-87
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Computer Link 8.5 Checking Error Codes

8.5 Checking Error Codes

8.5.1 Error codes when NAK is sent


The table below shows error codes and contents of errors when NAK is sent in communication between the
computer and a PLC.
As an error code, a two-digit ASCII code (hexadecimal) within the range from 00H to FFH is sent.
When two or more errors occur at the same time, priority is given to the error code with the smallest number,
and the error code with the smallest number is sent.
When any error shown below occurs, the entire transfer sequence is initialized.

Error code list


Error code
Error item Contents of error Action
(hexadecimal)
Sum check error has occurred. Check the data sent from the computer
Sum check The sum check code included in the and the contents of the sum check.
02H
error received data is different from the sum Modify either one, and then execute
value calculated from the received data. communication again.
The communication protocol is
1) Check the contents of parameters
abnormal.
and the contents of control
A control procedure set using
procedure. Modify either contents,
parameters was ignored, and a different
and then execute communication
control procedure was adopted in
03H Protocol error again.
communication. Or the adopted control
2) Refer to the command list shown in
procedure was partially different from the
Chapter 7, modify the specified
preset control procedure. Or a command
command etc., and then execute
specified in the preset control procedure
communication again.
does not exist.
An error occurred in the character area
A, B or C. Or a specified command does 1) Check the contents of the character
not exist. areas A, B and C, modify the
contents if necessary, and then
1) The control procedure set using
execute communication again.
Character parameters is different.
06H 2) Refer to "2.2.2 Applicable device
area error 2) A specified device number does not
ranges", modify the number of
exist in the target PLC.
characters used to specify the device
3) A device number is not set with the
number, and then execute
specified number of characters (5 or
communication again.
7 characters).
Check the data to be written to the
Character ASCII code data to be written to a device
07H device, modify it if necessary, and then
error is not hexadecimal.
execute communication again.
Check the PLC number included in the
message, modify it if necessary, and
PLC number A station with the corresponding PLC
0AH then execute communication again.
error number does not exist.
The PLC number should be "FFH" in all
FX Series PLCs.
Check the PLC number included in the
message, modify it if necessary, and
PLC number A station with the corresponding PLC
10H then execute communication again.
error number does not exist.
The PLC number should be "FFH" in all
FX Series PLCs.
Remote control to set the RUN or STOP
mode is disabled.
Remote Set the PLC mode to RUN or STOP
18H The RUN or STOP mode is determined
control error using the forced RUN mode.
in the PLC hardware (by using the RUN/
STOP selector switch, etc.).

D-88
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Computer Link 8.5 Checking Error Codes

A
8.5.2 Error codes in PLC

Common Items
When an error is included in a message sent from the computer to a PLC, an error occurs in the PLC.
When such an error occurs, the serial communication error flag turns ON.
When PLCs other then FX3G, FX3GC, FX3U and FX3UC PLCs are used or when ch1 is used in an FX3G,
FX3GC, FX3U or FX3UC PLC, the special auxiliary relay M8063 turns ON as an error flag. When ch2 is used in
an FX3G, FX3GC, FX3U or FX3UC PLC, the special auxiliary relay M8438 turns ON as an error flag.
B

N:N Network
When a serial communication error occurs, the error code is stored in D8063 if M8063 turns ON, or stored in
D8438 if M8438 turns ON.
The error code list is shown below:

Device
Error
code
Error item Contents of error Action C

Parallel Link
Check the transfer specifications
Parity, overrun or
6301 The transfer data is abnormal. set using parameters, and
framing error
execute communication again.
When the station number was FF, Check the specified command,
6305 Command error any command other than "GW" modify it if necessary, and then
D8063
(ch1)
was received. execute communication again. D
The received message was The message is insufficient.

Computer Link
insufficient. Because normal Check the transfer program in the
6306 Monitoring timeout message was not received within computer, modify it if necessary,
the time-out time setting, the and then execute communication
transfer sequence was initialized. again.

3801
Parity, overrun or
The transfer data is abnormal.
Check the transfer specifications
set using parameters, and
E
framing error

Communication
Inverter
execute communication again.
When the station number was FF, Check the specified command,
3805 Command error any command other than "GW" modify it if necessary, and then
D8438
was received. execute communication again.
(ch2)
The received message was
insufficient. Because normal
The message is insufficient.
Check the transfer program in the
F

(RS/RS2 Instruction)
Communication
Non-Protocol
3806 Monitoring timeout message was not received within computer, modify it if necessary,
the time-out time setting the and then execute communication
transfer sequence was initialized. again.

Serial communication errors and serial communication error code are not cleared even when communication
is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
G

(FX2N-232IF)
Communication
Non-Protocol
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-89
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.1 Related Device List

9. Related Data

9.1 Related Device List

1. Bit devices
Device Name Description R/W
Turns ON when an error occurs in serial communication using
M8063 Serial communication error 1 R
ch 1.
M8120 Communication setting keep Keeps the communication setting status (for FX0N PLCs). R/W
Turns ON or OFF when the global command (GW) is received
M8126 Global function ON R
from the computer (for ch 1).
Remains ON while the on-demand function is being executed
*1 (for ch 1).
M8127 On-demand send processing R
ON: On-demand data is being sent.
OFF: Sending of on-demand data is completed.
Turns ON when an error is included in a specified value for
M8128 On-demand error flag R
data sending used in the on-demand function (for ch 1).
Specifies the unit (byte or word) of data handled in the on-
On-demand data byte/word demand function (for ch 1).
M8129 R/W
switch ON: Unit = Byte (8-bit)
OFF: Unit = Word (16-bit)
Turns ON or OFF when the global command (GW) is received
M8426 Global function ON R
from the computer (for ch 2).
Remains ON while the on-demand function is being executed
(for ch 2).
M8427 On-demand send processing R
ON: On-demand data is being sent.
OFF: Sending of on-demand data is completed.
Turns ON when an error is included in a specified value for
M8428 On-demand error flag R
data sending used in the on-demand function (for ch 2).
Specifies the data unit (byte or word) handled in the on-
On-demand data byte/word demand function (for ch 2).
M8429 R/W
switch ON: Unit = Byte (8-bit)
OFF: Unit = Word (16-bit)
Turns ON when an error occurs in serial communication using
M8438 Serial communication error 2 R
ch 2.
R: Read only
R/W: Read or Write
*1. FX0N, FX1S, FX1N and FX1NC PLCs do not support this device.

D-90
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.1 Related Device List

A
2. Word devices

Common Items
Device Name Description R/W
Serial communication error Stores the error code when an error occurs in serial
D8063 R
code 1 communication (for ch 1).
D8120 Communication format setting Sets the communication format (for ch 1). R/W
D8121 Station number settings Sets the station number in computer link (for ch 1). R/W B

N:N Network
On-demand data head device Sets the head data register device number containing the data
D8127 R/W
number specification to be sent using the on-demand function (for ch 1).
On-demand data quantity Sets the amount of data to be sent using the on-demand
D8128 R/W
specification function (for ch 1).
Sets the evaluation time for error when the receiving of data
D8129 Time-out time setting
from the computer is interrupted (for ch 1).
R/W C

Parallel Link
D8419 Operation mode display (ch 1) Stores the communication type being used (for ch 1). R
D8420 Communication format setting Sets the communication format (for ch 2). R/W
D8421 Station number settings Sets the station number in computer link (for ch 2). R/W
On-demand data head device Sets the head data register device number containing the data
D8427 R/W
number specification to be sent using the on-demand function (for ch 2).
On-demand data quantity Sets the amount of data to be sent using the on-demand
D
D8428 R/W

Computer Link
specification function (for ch 2).
Sets the evaluation time for error when the receiving of data
D8429 Time-out time setting R/W
from the computer is interrupted (for ch 2).
Serial communication error Stores the error code when an error occurs in serial
D8438 R
code 2 communication (for ch 2).
D8439 Operation mode display (ch 2) Stores the communication type being used (for ch 2). R E

Communication
Inverter
R: Read only
R/W: Read or Write

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-91
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.2 Details of Related Devices

9.2 Details of Related Devices


The devices described below are used for computer link.

9.2.1 Serial communication error [M8063 and M8438]


These devices turn ON when an error occurs during serial communication.
1. Detailed contents
These devices work as the serial communication error flags.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, M8063 turns ON.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, M8063 turns ON.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, M8438 turns ON.
When serial communication error flags turn ON, a corresponding error code is stored in D8063 and D8438.

2. Cautions on use
Serial communication errors code are not cleared even when communication is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

9.2.2 Communication setting keep [M8120]


Set this device to ON in a sequence program so that the communication setting is kept (for FX0N PLCs).
1. Detailed contents
In an FX0N PLC, set M8120 to ON in a sequence program so that the communication format setting and
station number settings are kept.
2. Cautions on use
In an FX0N PLC, the communication setting status is kept only when M8120 is set to ON.
In any PLC other than FX0N PLCs, setting of M8120 is not required.

9.2.3 Global function ON [M8126 and M8426]


These devices turn ON/OFF when the PLC receives the global command (GW) from personal computers.
1. Detailed contents
When the computer sends the global command, the global ON flag turns ON or OFF in all connected stations.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, M8126 turns ON or
OFF.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, M8126 turns ON or OFF.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, M8426 turns ON or OFF.
2. Cautions on use
The global ON flag turns OFF from ON when the PLC power is turned OFF or when the PLC mode is
changed to STOP.

9.2.4 On-demand send processing [M8127 and M8427]


These devices remain ON while the on-demand function is being executed.
1. Detailed contents
When a PLC gives data sending request using the on-demand function, the on-demand send processing flag
turns ON.
In FX2(FX), FX2C, FX2N, FX2NC and FX3S PLCs and in FX3G, FX3GC, FX3U and FX3UC PLCs using the
communication port ch1, M8127 turns ON/OFF.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, M8427 turns ON/OFF.
2. Cautions on use
Use these devices for interlock to prevent generation of two or more on-demand requests at the same time.

D-92
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.2 Details of Related Devices

A
9.2.5 On-demand error flag [M8128 and M8428]

Common Items
These devices turn ON when an error is included in a specified value for data sending used with the on-
demand function.

1. Detailed contents
When the amount of on-demand data is incorrect, the on-demand error flag turns ON.
B

N:N Network
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, M8128 turns ON.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, M8128 turns ON.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, M8428 turns ON.

2. Cautions on use
While the on-demand error flag is ON, data sending is disabled for the on-demand function. C
When sending data from a PLC using the on-demand function, set to OFF the on-demand error flag.

Parallel Link
9.2.6 On-demand data word/byte changeover [M8129 and M8429]
These devices specify the unit (word or byte) of on-demand data.

1. Detailed contents D
Use this device to specify the data unit sent using the on-demand function.

Computer Link
Set these devices to ON to specify "byte" (8-bit). Set these devices to OFF to specify "word" (16-bit).
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, use M8129.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, use M8129.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, use M8429.

2. Cautions on use E

Communication
Inverter
When the unit is set to "word", the amount of on-demand data units is equivalent to the number of data
registers for sending.
When the unit is set to "byte", two on-demand data units use one data register for sending.
Example: When the amount of on-demand data is "5", the amount of data registers for sending is "3".

9.2.7 Serial communication error code [D8063 and D8438] F

(RS/RS2 Instruction)
Communication
Non-Protocol
These devices store the error codes during serial communication.

1. Detailed contents
When the serial communication error flag (M8063 or M8438) turns ON, a corresponding error code is stored
in these devices.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, an error code is G
stored in D8063.

(FX2N-232IF)
Communication
Non-Protocol
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, an error code is stored in
D8063.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, an error code is stored in D8438.
The error code list is shown below:

Device
Error
Error item Contents of error
H
code
Communication
Programming

Parity, overrun or
6301 The transfer data is abnormal.
framing error
When the station number was FF, any command other than "GW"
D8063 6305 Command error
was received.
(ch1)
The received message was insufficient. Because normal message I
6306 Monitoring timeout was not received within the time-out time setting, the transfer
Maintenance
Remote

sequence was initialized.


Parity, overrun or
3801 The transfer data is abnormal.
framing error
When the station number was FF, any command other than "GW"
D8438 3805 Command error
(ch2)
was received. Apx.A
The received message was insufficient. Because normal message
models
Discontinued

3806 Monitoring timeout was not received within the time-out time setting, the transfer
sequence was initialized.

D-93
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.2 Details of Related Devices

2. Cautions on use
Error codes are not cleared even after communication recovers its normal status.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

9.2.8 Communication format setting [D8120 and D8420]


These devices set the serial communication format.

1. Detailed contents
These devices set the serial communication format. In FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC,
FX3U and FX3UC PLCs, the contents set in parameters are transferred to these devices when the power is
turned ON.
In FX2(FX), FX2C and FX0N PLCs, set the communication format using a sequence program, and then turn
ON the power.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using communication port ch1, use D8120.
Set the communication format using parameters when using the communication port ch2 in FX3G, FX3GC,
FX3U and FX3UC PLCs.
Use D8420 for confirmation.
The tables below show the setting details.
Contents of D8120
Contents
Bit No. Name
0 (bit = OFF) 1 (bit = ON)
b0 Data length 7-bit 8-bit
b2, b1
b1 (0, 0): Not provided
Parity
b2 (0, 1): Odd
(1, 1): Even
b3 Stop bit 1-bit 2-bit
b7, b6, b5, b4 b7, b6, b5, b4
b4 (0, 0, 1, 1): 300 (0, 1, 1, 1): 4800
b5 Baud rate (0, 1, 0, 0): 600 (1, 0, 0, 0): 9600
b6 (bps) (0, 1, 0, 1): 1200 (1, 0, 0, 1): 19200
b7
(0, 1, 1, 0): 2400 (1, 0, 1, 0): 38400*1
b8 Header Not provided Provided (D8124) Initial value: STX (02H)
b9 Terminator Not provided Provided (D8125) Initial value: ETX (03H)
Com- b11, b10
b10
Control line puter (0, 0): RS-485/RS-422 interface
b11
link (1, 0): RS-232C interface
b12 Not applicable
b13 Sum check Not added Added
b14 Protocol Not used Used
Control
b15 Format 1 Format 4
procedure

*1. This setting is available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

D-94
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.2 Details of Related Devices

A
Contents of D8420

Common Items
Contents
Bit No. Name
0 (bit = OFF) 1 (bit = ON)
b0 Data length 7-bit 8-bit
b2, b1
b1
Parity
(0, 0): Not provided B
b2 (0, 1): Odd

N:N Network
(1, 1): Even
b3 Stop bit 1-bit 2-bit
b7, b6, b5, b4 b7, b6, b5, b4
b4
(0, 0, 1, 1): 300 (0, 1, 1, 1): 4800
b5
b6
Baud rate
(bps)
(0, 1, 0, 0): 600 (1, 0, 0, 0): 9600 C
(0, 1, 0, 1): 1200 (1, 0, 0, 1): 19200
b7

Parallel Link
(0, 1, 1, 0): 2400 (1, 0, 1, 0): 38400
b8 Header Not provided Provided
b9 Terminator Not provided Provided
b10 Com- b12, b11, b10
b11
b12
Control line puter
link
(0, 0, 0): RS-485/RS-422 interface
(0, 1, 0): RS-232C interface
D

Computer Link
b13 Sum check Not added Added
b14 Protocol Not used Used
Control
b15 Format 1 Format 4
procedure

2. Cautions on use
E

Communication
Inverter
Do not use both the parameters and communication format setting devices (D8120 or D8420) at the same
time. If the communication format is set using both methods at the same time, priority is given to the setting
using parameters.
When setting the communication format device (D8120) in an FX0N PLC, set the communication setting
latched (battery backed) device (M8120) to ON.
When using computer link, make sure to set the header (b8) and terminator (b9) to "not provided". And set the F
protocol (b14) to "used".

(RS/RS2 Instruction)
Communication
Non-Protocol
If the communication format is set using the special data register, the setting becomes valid when the power
is turned ON after the setting is written to the special data register.

9.2.9 Station number settings [D8121 and D8421]


G
These devices set the station number in computer link.

(FX2N-232IF)
Communication
Non-Protocol
1. Detailed contents
Set the station number of each PLC used in computer link. The applicable setting range is from 0 to 15 (from
H00 to H0F).
In FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the contents set using
parameters are stored when the power is turned ON.
H
Communication
Programming

In FX2(FX), FX2C and FX0N PLCs, set the station number using a sequence program, and then turn ON the
power.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs and in FX3G, FX3GC, FX3U and FX3UC PLCs using
communication port ch1, use D8121.
Set the station number using parameters when using the communication port ch2 in FX3G, FX3GC, FX3U and
FX3UC PLCs. I
Use D8421 for confirmation.
Maintenance
Remote

2. Cautions on use
Do not use both the parameters and station number settings device (D8121) at the same time. If the station
number is set using both methods at the same time, priority is given to the setting using a parameter.
When setting the station number settings device (D8121) in an FX0N PLC, set the communication setting
latched (battery backed) device (M8120) to ON.
Apx.A
models
Discontinued

D-95
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.2 Details of Related Devices

9.2.10 On-demand data head device number specification [D8127 and D8427]
These devices set the head data register device number containing the data to be sent using the on-demand
function in a sequence program.

1. Detailed contents
These devices set the head data register device number containing the data to be sent using the on-demand
function.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs and in FX3G, FX3GC, FX3U and FX3UC PLCs using
the communication port, use D8127.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, use D8127.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, use D8427.
If there is an error in the set data, the on-demand error flag (M8128 or M8428) turns ON.

2. Cautions on use
When setting the on-demand data head device number specification device (D8127 or D8427), set the flag
using the pulse operation type.
While the on-demand send processing flag (M8127 or M8427) is ON, do not write data.

9.2.11 On-demand data quantity specification [D8128 and D8428]


These devices set the amount of data to be sent from a PLC using the on-demand function in a sequence
program.

1. Detailed contents
These devices set the amount of data to be sent using the on-demand function. Set the amount of data 64 or
less.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, use D8128.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, use D8128.
In FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch2, use D8428.
If an error is included in the set data, the on-demand error flag (M8128 or M8428) turns ON.

2. Cautions on use
When setting the on-demand data quantity specification device (D8128 or D8428), set the flag using the pulse
operation type.
While the on-demand send processing flag (M8127 or M8427) is ON, do not write data.

D-96
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.2 Details of Related Devices

A
9.2.12 Time-out time setting [D8129 and D8429]

Common Items
These devices set the evaluation time for error when receiving of data from the computer is interrupted.

1. Detailed contents
These devices set the error evaluation time in 10-ms units used when the receiving of data from the computer
is interrupted.
B

N:N Network
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, use D8129.
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, use D8129.
Set the time-out time setting using parameters when using the communication port ch2 in FX3G, FX3GC, FX3U
and FX3UC PLCs.
Use D8429 for confirmation.
The table below shows the setting range. C

Parallel Link
FX Series Setting range
FX0N, FX1S, FX1N, FX1NC 1 to 255 (10 to 2550 ms) (When "0" is set, it is handled as "100 ms".)
FX2(FX), FX2C, FX2N, FX2NC,
1 to 3276 (10 to 32760 ms) (When "0" is set, it is handled as "100 ms".)
FX3S, FX3G, FX3GC, FX3U, FX3UC

2. Cautions on use D
Do not set the time-out time setting parameter and the time-out time (D8129) at the same time. The priority is

Computer Link
given to the parameter setting.
When setting the time-out time setting device (D8129) in an FX0N PLC, set the communication setting latched
(battery backed) device (M8120) to ON.
Make sure that the time-out time setting is not shorter than the time required to receive one character at the
set baud rate. E

Communication
Inverter
9.2.13 Operation mode display [D8419 and D8439]
These devices store the communication type being used. (in the FX3S, FX3G, FX3GC, FX3U and FX3UC)

1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.

The table below shows the contents of the communication type codes.
Code
0 Programming communication
Description
G

(FX2N-232IF)
Communication
Non-Protocol
1 PP modem mode
2 Protocol dedicated to computer link
3 N:N Network
4 RS instruction
5 RS2 instruction H
Communication
Programming

6 Parallel link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication
10 CF-ADP I
11 ENET-ADP
Maintenance
Remote

12 Input/output expansion board is used.

Apx.A
models
Discontinued

D-97
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.3 Communication Setting Method Using Sequence Program

9.3 Communication Setting Method Using Sequence Program


When adjusting the communication setting using a sequence program, transfer values to D8120
(communication format), D8121 (station number settings) and D8129 (time-out time setting), and then turn
the power ON.
This section explains the communication setting method using a sequence program.

9.3.1 Setting procedure


Perform the following procedure to set the communication using a sequence program.

1 Creating a program using a programming tool


Create the program shown below using a programming tool.

M8000
M8120 This step is required only in FX0N PLC.

M8002
FNC 12 H6082 D8120 The communication format is set.
Initial pulse MOV

FNC 12 H0 D8121 The station number is set.


MOV

FNC 12 K1 D8129 The time-out time setting is set.


MOV

For details on these devices, refer to Section 9.2.

2 Writing the sequence program to the PLC


Transfer the created program to the PLC.

3 Setting the PLC mode to RUN


Set the PLC to RUN mode, and execute the program.

4 Turning the PLC power OFF and then ON


Turn OFF the PLC power, and then turn it to ON so that the communication setting becomes valid.

9.3.2 Caution on communication setting using sequence program

1) Do not set the communication using a sequence program and parameters at the same time.
If the communication is set using both methods at the same time, priority is given to the setting using
parameters.
2) Since the special data registers (D8120, D8121, D8129) is a battery backed area in the case of the FX2N,
FX2NC, FX3U and FX3UC series, a value cannot be normally saved when the battery is discharge (or after
a battery error occurs).
Therefore, keep in mind that a computer link setting may not be possible in this case.

D-98
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.4 ASCII Code Table

A
9.4 ASCII Code Table

Common Items
<ASCII code table (8-bit code expressed in hexadecimal)>
The ASCII codes A1H to DFH indicate Japanese characters.

N:N Network
C

Parallel Link
D

Computer Link
E

Communication
Inverter
*1. \ (ASCII CODE:5C) symbol is displayed as " " in Japanese.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

D-99
FX Series PLC User's Manual - Data Communication Edition 9 Related Data
Computer Link 9.4 ASCII Code Table

MEMO

D-100
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
E. Inverter Communication
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains "inverter communication" provided for the MELSEC-F FX Series Programmable
Maintenance
Remote

Controllers and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

E-1
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication

E-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Inverter Communication 1.1 Outline of System

Common Items
1. Outline
This chapter explains inverter communication. B

N:N Network
1.1 Outline of System
Inverter communication allows connection between an FX PLC and up to eight inverters to monitor operations
of inverters, give various commands to inverters and read and write inverter parameters through
communication via RS-485 .
C

Parallel Link
1) Mitsubishi general-purpose inverters FREQROL F800, A800, F700, A700, E700, D700, V500, F500,
A500, E500 and S500 (containing the communication type) Series can be linked.
(FX2N and FX2NC PLCs support only the A500, E500, and S500 (containing the communication function)
Series inverters.)
2) Inverter operations can be monitored, various command can be given to inverters, and parameters can
be read or written in inverters.
D

Computer Link
3) The total extension distance is 500m (1640' 5") maximum (for the system configured with 485ADP only).

Important points and reference


System chapter/paragraph

Up to eight inverters ....... Number of linked units E


500m (1640' 5") [50m (164' 0") when 485BD is included] ....... Total extension distance

Communication
Inverter
For the specifications,
FX PLC Inverter Inverter refer to Chapter 2.

....... To check available PLC


models, refer to Section 1.3.
F
......

(RS/RS2 Instruction)
Communication
Non-Protocol
For the communication
setting of inverters,
refer to Chapter 5.
+ + +
Communication
equipment
operating in
Built-in PU port
in accordance
Built-in PU port For selection,
in accordance ....... refer to Chapter 3.
G

(FX2N-232IF)
Communication
Non-Protocol
accordance with with RS-485 with RS-485
RS-485

....... For wiring,


refer to Chapter 4.
Master station Station No. 1 Station No. n
H
Point
Communication
Programming

Inverter operations, reading/writing parameters, and monitor output can be performed with the PLC function
by writing a prepared sequence program to the inverter.
The inverter PLC function differs from the inverter communication function.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Inverter Communication 1.2 Procedures Before Operation

1.2 Procedures Before Operation


The flow chart below shows the Inverter Communication setting and sequence programs creation procedures
up until data link:

Inverter Communication
Refer to Chapter 1

Outline Outline of system


Available PLC versions
Available programming tools
Refer to Chapter 2

Check communication specifications Communication specifications


Applicable inverters
Operation commands and parameters
Refer to Chapter 3
Execution time in inverter communication
Determine system configuration and selection System configuration
Select communication equipment

Refer to Chapter 4

Perform wiring Wiring procedure


Selection of cables and connection
equipment
Refer to Chapter 5 Wiring example
Set inverter communication Parameter communication

Programming tool
Refer to Chapter 6

Perform PLC communication setting


Connect PLC*1

Refer to Chapter 7, 9

Create programs Programs for FX2N, FX2NC Series


(Chapter 7)
Common items
Basic programs
Programs for FX3S, FX3G, FX3GC, FX3U,
FX3UC Series (Chapter 9)
Based on SD/RD lamp lighting status and Common items
contents of error check devices, verify that Basic programs
communication is being executed normally.
If there are problems, refer to the troubleshooting
(Chapter 11).

Refer to Chapter 8, 10

Practical program examples Program examples for FX2N, FX2NC Series


(Chapter 8)
Basic programs
Program examples for FX3S, FX3G, FX3GC, FX3U,
FX3UC Series (Chapter 10)
Basic programs
*1. For the programming tool to PLC connection procedure, refer to the "Programming Communication"
section in this manual or the respective programming tool manual.
For details on operation method, refer to the respective programming tool manual.

E-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Inverter Communication 1.3 Communication Type Applicability in PLC

A
1.3 Communication Type Applicability in PLC

Common Items
1.3.1 For applicable versions
The communication types are applicable for the following versions. B
: Applicable

N:N Network
: Not applicable
PLC Applicability Remarks
FX3UC Series *1
FX3U Series *1
F800, A800, F700, A700, E700, D700, V500, F500, A500,
C
FX3GC Series *1

Parallel Link
E500 and S500 Series inverters can be connected.
FX3G Series *1
FX3S Series *1
FX2NC Series *1 A500, E500 and S500 Series inverters can be
FX2N Series *1 connected. D

Computer Link
FX1NC Series Inverter communication is not provided.
FX1N Series Inverter communication is not provided.
FX1S Series Inverter communication is not provided.
FX0N Series Inverter communication is not provided.
FX0S Series Inverter communication is not provided. E
FX0 Series Inverter communication is not provided.

Communication
Inverter
FX2C Series Inverter communication is not provided.
FX2(FX) Series Inverter communication is not provided.
FX1 Series Inverter communication is not provided.

*1. The table below shows PLC versions applicable to each inverter. F

(RS/RS2 Instruction)
Communication
Non-Protocol
FREQROL-S500/ FREQROL-F500/ FREQROL-F700/ FREQROL-D700/ FREQROL-A800/
PLC
E500/A500 V500 A700 E700 F800
FX3UC Ver.1.00 or later Ver.2.20 or later Ver.2.32 or later Ver.3.11 or later
FX3U Ver.2.20 or later Ver.2.32 or later Ver.3.11 or later
FX3GC Ver.1.40 or later Ver.2.22 or later
G
FX3G Ver.1.10 or later Ver.2.22 or later

(FX2N-232IF)
Communication
Non-Protocol
FX3S Ver.1.00 or later Ver.1.10 or later
FX2N,
Ver.3.00 or later
FX2NC

1.3.2 Version check H


Communication
Programming

The PLC version can be checked by reading the last three digits of device D8001.
For a detailed description of the version check, refer to A. Common Items Section 4.2.

1.3.3 How to look at the manufacturer's serial number


I
The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT"
Maintenance
Remote

indicated on the front of the product.


For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Section 4.1.

Apx.A
models
Discontinued

E-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Inverter Communication 1.4 Programming Tool Applicability

1.4 Programming Tool Applicability

1.4.1 For applicable versions


The programming tool is applicable for each FX Series from the version shown:

1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
The IVMC instruction is supported in
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
Ver. 1.48A or later.
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later The IVMC instruction is not supported.
The IVMC instruction is supported in
FX-30P Ver. 1.00 or later
Ver. 1.20 or later.
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
The IVMC instruction is supported in
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
Ver. 1.62Q or later.
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later The IVMC instruction is not supported.
The IVMC instruction is supported in
FX-30P Ver. 1.00 or later
Ver. 1.50 or later.
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later -
The IVMC instruction is supported in
FX-30P Ver. 1.30 or later
Ver. 1.50 or later.
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW7 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.10 or later The versions shown on the left
FX-30P Ver. 1.00 or later supporting EXTR instruction
are applicable.
FX-20P-E(-SET0)
Ver. 4.10 or later
FX-20P-MFXD-E
FX-10P-E Ver. 4.10 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.30 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 6.30 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 6.30 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 6.30 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

E-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Inverter Communication 1.4 Programming Tool Applicability

A
2. Japanese versions

Common Items
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
The IVMC instruction is supported in
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
Ver. 1.45X or later.
B
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later The IVMC instruction is not supported.

N:N Network
The IVMC instruction is supported in
FX-30P Ver. 1.00 or later
Ver. 1.20 or later.
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC C
The IVMC instruction is supported in

Parallel Link
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
Ver. 1.56J or later.
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later The IVMC instruction is not supported.
The IVMC instruction is supported in
FX-30P Ver. 1.00 or later
Ver. 1.50 or later.

GOT1000 Series display units


Refer to manuals of GOT1000 Series display units for applicable D
models and versions supporting the list editor function.

Computer Link
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later -
The IVMC instruction is supported in
FX-30P Ver. 1.30 or later
Ver. 1.50 or later.
Refer to manuals of GOT1000 Series display units for applicable E
GOT1000 Series display units
models and versions supporting the list editor function.

Communication
Inverter
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later

GOT1000 Series display units


Refer to manuals of GOT1000 Series display units for applicable
models and versions supporting the list editor function.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW7 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.20 or later The versions shown on the left
FX-30P Ver. 1.00 or later supporting EXTR instruction G
are applicable.

(FX2N-232IF)
Communication
Non-Protocol
FX-20P(-SET0)
Ver. 5.10 or later
FX-20P-MFXD
FX-10P(-SET0) Ver. 4.10 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.30 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 6.30 or later) H
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 6.30 or later)
Communication
Programming

F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 6.30 or later)


Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

1.4.2 For non-applicable versions (setting an alternative model) I


Maintenance
Remote

In FX2N, FX2NC, FX3G, FX3U and FX3UC PLCs, it is not possible to create programs using programming tools
of inapplicable versions.
Select "FX3G" in model selection when creating programs using a programming tool whose version is not
applicable to the FX3S and FX3GC PLC.
Apx.A
Point
models
Discontinued

In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

E-7
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.1 Communication Specifications (Reference)

2. Specifications
This chapter explains the communication specifications and performance.

2.1 Communication Specifications (Reference)

Item Specifications Remarks


Number of connectable units 8 maximum
Transmission standard RS-485 standard
Distance varies depending
Maximum total extension 500 m (1640' 5") or less when 485ADP is used
on communication
distance 50 m (164' 0") or less when 485BD is used
equipment type.
Protocol type Inverter computer link Link startup mode
Control procedure Asynchronous system
Communication method Half-duplex, bidirectional communication
Baud rate 4800, 9600, 19200 or 38400*1 bps Any one can be selected.
ASCII
Start bit
Character Data bit 7-bit
format Parity bit Even
Stop bit 1-bit

*1. FX3U and FX3UC Series PLC Ver. 2.41 or later, and FX3S, FX3G, FX3GC Series PLC is applicable.

2.2 Connectable Mitsubishi General-purpose Inverters


Series Built-in PU connector FR-A5NR (option) Remarks
Only models containing the RS-485
FREQROL-S500
communication type can be connected.
FREQROL-E500
FREQROL-A500
FREQROL-F500 Only available for FX3S, FX3G, FX3GC, FX3U
FREQROL-V500 and FX3UC PLCs.
Series Built-in PU connector Built-in RS-485 terminal Remarks
FREQROL-A700
FREQROL-F700 Only available for FX3S, FX3G, FX3GC FX3U
FREQROL-A800 and FX3UC PLCs.
FREQROL-F800
Series Built-in PU connector FR-E7TR (option) Remarks
FREQROL-D700 Only available for FX3S, FX3G, FX3GC, FX3U
FREQROL-E700 and FX3UC PLCs.

E-8
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.3 Link Specifications

A
2.3 Link Specifications

Common Items
The tables below show applicable parameters and operation commands.

2.3.1 When monitoring inverter operations (PLC inverter)


B

N:N Network
Applicable inverter
Instruction code
Read contents F800, A800, F700,
(hexadecimal) V500, F500, A500 E500 S500
A700, E700, D700
H7B Operation mode
H6F
H70
Output frequency [number of rotations]
Output current








C

Parallel Link
H71 Output voltage
H72 Special monitor
H73 Special monitor selection number
H74 Alarm definition
H75 Alarm definition D

Computer Link
H76 Alarm definition
H77 Alarm definition
H79 Inverter status monitor (extended)
H7A Inverter status monitor
H6E Set frequency (EEPROM) E
H6D Set frequency (RAM)

Communication
Inverter
H7F Link parameter expansion setting
Refer to Subsection 9.4.2
H6C Second parameter changing

2.3.2 When controlling inverter operations (PLC inverter) F

(RS/RS2 Instruction)
Communication
Non-Protocol
Applicable inverter
Instruction code
Written contents F800, A800, F700,
(hexadecimal) V500 F500, A500 E500, S500
A700, E700, D700
HFB Operation mode
HF3 Special monitor selection number G
HF9 Run command (expansion)

(FX2N-232IF)
Communication
Non-Protocol
HFA Run command
HEE Set frequency (EEPROM)
HED Set frequency (RAM)
HFD
HF4
Inverter reset
Alarm definition all clear








H
Communication
Programming

HFC All parameter all clear


HFC User clear
HFF Link parameter expansion setting

2.3.3 Parameters (PLC inverter) I


Maintenance
Remote

For inverter parameters which can be changed (read and written), refer to "12. Related Detailed Data" later.

Apx.A
models
Discontinued

E-9
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.4 Execution Times in Inverter Communication Instructions

2.4 Execution Times in Inverter Communication Instructions

2.4.1 Outline
The period of time after one inverter communication instruction is driven until communication with the inverter
is completed (M8029 turns ON) is regarded as the required time for the inverter communication instruction as
shown in the figure below.
X0
SET M0

M0
Inverter communication instruction

M8029
RST M0

M0

M8029

Tinv
T1 T2 T3
First time sending/receiving Second time sending/receiving "n"th time sending/receiving
in a single instruction in a single instruction in a single instruction
Communication Communication
preparation termination
processing processing

T4 T5 T6[n]*1

Inverter T7[n]*1 T8[n]*1 T9[n]*1


waiting time

The request message


is being sent
Inverter data
check time
The response message
is being received
*1. The time required for the "n"th time sending/receiving in a single instruction.

E-10
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.4 Execution Times in Inverter Communication Instructions

A
Some inverter communication instructions execute several times of sending/receiving in a single instruction.

Common Items
The following table shows the number of times of sending/receiving in each communication instruction.
Inverter communication instruction Number of times of sending/receiving in per instruction
IVDR 1
IVCK 1
Change of the 2nd parameter is
B
2

N:N Network
unnecessary
IVRD
Change of the 2nd parameter is
3
necessary*2
Change of the 2nd parameter is
2
IVWR
unnecessary
Change of the 2nd parameter is
C
3

Parallel Link
necessary*2
Number of times of S2 2 + Number of parameters *2 requiring change of the
IVBWR
communication S2 2nd parameter
IVMC 1

*2. For parameters requiring change of the 2nd parameter, refer to section 9.10.
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-11
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.4 Execution Times in Inverter Communication Instructions

2.4.2 Calculation method


Calculate the required time "Tinv" for inverter communication instruction in units of "ms" as follows.
"INT(n)" in the calculation formula indicates an integer obtained by truncating decimal places of "n".

1. Length of 1 character
In inverter communication, the communication setting is as shown in following table.
The length of 1 character is as shown in the following calculation expression.
Length of 1 character = Start bit + Data length + Parity bit + Stop bit
= 10[bit]
Name Set value bit
Start bit - 1
Data length 7 7
Parity bit Even number 1
Stop bit 1 1
Total 10

2. Execution times in inverter communication instructions


Execution times in inverter communication instructions is as shown in the following calculation expression.
Tinv = T1 + T2 + T3
T1 = 1[ms]
T2 = {n(T4+T5)}+T6[n][ms]
Sending and
receiving T6[1]+T6[2]+T6[3]+
frequency

T3 = 1[ms]
Calculate "T4", "T5" and "T6 [n]" as shown in the following table.
Communication
Calculation method
time

= ( INT ( 15 ) + 1) Scan time


T4
Scan time
T5 = 1[ms]
For Scan time < T7[n]+T8[n]+T9[n]
T7[n]+T8[n]+T9[n]
= ( INT ( ) + 1) Scan time
Scan time
T6[n]
For Scan time T7[n]+T8[n]+T9[n]
T7[n]+T8[n]+T9[n]
= ( INT ( ) + 2) Scan time
Scan time

1 Number of sending and Length of


T7[n]+T9[n] ={( )( ) } 1000
Communication speed [bps] receiving characters*1 1 character

T8[n] = Data check time in inverters*4

E-12
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.4 Execution Times in Inverter Communication Instructions

A
*1. Refer to the following table for the number of sent/received characters.

Common Items
Inverter First Second Third
Parameter/
communication
instruction code Sending Receiving Total Sending Receiving Total Sending Receiving Total
instruction
Change of the 2nd
parameter is 11 4 15 9 11 20 - - - B
unnecessary.

N:N Network
IVRD
Change of the 2nd
parameter is 11 4 15 11 4 15 9 11 20
necessary.
HF3, HFA, HFF 11 4 15 - - - - - -
IVDR HFD 13 0 *3 13 - - - - - - C
Other than above 13 4 17 - - - - - -

Parallel Link
H73, H7A, H7F, H6C 9 9 18 - - - - - -
IVCK
Other than above 9 11 20 - - - - - -
Change of the 2nd
parameter is
unnecessary.
11 4 15 13 4 17 - - -
D
IVWR

Computer Link
Change of the 2nd
parameter is 11 4 15 11 4 15 13 4 17
necessary.
Change of the 2nd
parameter is 11 4 15 13 4 17 - - -
unnecessary. E
IVBWR*2
Change of the 2nd

Communication
Inverter
parameter is 11 4 15 11 4 15 13 4 17
necessary.
IVMC - 19 19 38 - - - - - -

*2. Indicates the number of sent/received characters required to write 1 parameter.


The IVBWR instruction executes parameter writing by the number of times of communication S2 .
F

(RS/RS2 Instruction)
Communication
Non-Protocol
*3. The inverter gives no response because the inverter is being reset.
The PLC waits for 2.2 s until reset of the inverter is completed, and then completes execution of the
inverter communication instruction.
*4. Refer to the following table for the data check time in inverters.
Make sure to refer to the manual of the inverter used, and confirm the data check time for the G
communication command used.

(FX2N-232IF)
Communication
Non-Protocol
Item Data check time
Various monitors, operation command, set frequency
<12ms
(RAM)
Parameters read/write, set frequency (EEPROM) <30ms
Parameter all clear/all clear <5s H
Communication
Programming

No response
(The PLC waits for 2.2 s until reset of the inverter is
Reset instruction
completed, and then completes execution of the
inverter communication instruction.)
The IVWR, IVRD and IVBWR instructions automatically change expansion parameters and the 2nd
parameter. I
The data check time for the last (2nd or 3rd) sending/receiving in the IVWR and IVRD instructions and
Maintenance
Remote

the data check time for the last sending/receiving of each parameter writing in the IVBWR instruction
correspond to parameter reading/writing (< 30 ms).
The data check time for sending and receiving (expansion parameter change and 2nd parameter
change) other than the above correspond to various monitors (< 12 ms).
Apx.A
models
Discontinued

E-13
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.4 Execution Times in Inverter Communication Instructions

2.4.3 Calculation example


This is a calculation example for the following communication settings and scan time when communicating
with an inverter.
Communication speed = 19200[bps]
Length of 1 character = 10[bit]
Scan time = 10[ms]

1. Calculation example 1
Calculation of required time when Pr. 3 is read by the IVRD instruction
Tinv = T1 + T2 + T3 = 114[ms]
T1 = 1[ms], T3 = 1[ms]
Calculate "T2" as follows because Pr.3 does not require change of the 2nd parameter.

T2 = 2(T4+T5) + T6[1] + T6[2] = 2(20+1) + 20 + 50 = 112[ms]


Sending and The first The second
receiving sending and sending and
frequency receiving receiving
T4 = ( INT( 15
10
) + 1 ) 10 = 20[ms]
T5 = 1[ms]
T7[1] + T8[1] + T9[1]
T6[1] = ( INT( 10
) + 1 ) 10 = ( INT( 19.8
10
) + 1 ) 10 = 20[ms]
T7[1] + T8[1] + T9[1] = 7.8 + 12 = 19.8[ms]
T7[1] + T9[1] = ( ( 1 ) (11+4) 10 ) 1000 = 7.8[ms]
19200
T8[1] = 12[ms]
T7[2] + T8[2] + T9[2]
T6[2] = ( INT( ) + 1 ) 10 = ( INT( 40.4
10
) + 1 ) 10 = 50[ms]
10
T7[2] + T8[2] + T9[2] = 10.4 + 30 = 40.4[ms]
T7[2] + T9[2] = ( ( 1 ) (9+11) 10 ) 1000 = 10.4[ms]
19200
T8[2] = 30[ms]
Tinv = T1 + T2 + T3 = 1+112+1 = 114[ms]

2. Calculation example 2
Calculation of required time when Pr.902 is read by the IVRD instruction
Tinv = T1 + T2 + T3 = 155[ms]
T1 = 1[ms], T3 = 1[ms]
Calculate "T2" as follows because Pr.902 requires change of the 2nd parameter.

T2 = 3(T4+T5) + T6[1] + T6[2] + T6[3] = 3(20+1) + 20 + 20 + 50 = 153[ms]


Sending and The first The second The third
receiving sending and sending and sending and
frequency receiving receiving receiving
T4 = ( INT( 15
10
) + 1 ) 10 = 20[ms]
T5 = 1[ms]
T7[1] + T8[1] + T9[1]
T6[1] = ( INT( 10
) + 1 ) 10 = ( INT( 19.8
10
) + 1 ) 10 = 20[ms]
T7[1] + T8[1] + T9[1] = 7.8 + 12 = 19.8[ms]
T7[1] + T9[1] = ( ( 1 ) (11+4) 10 ) 1000 = 7.8[ms]
19200
T8[1] = 12[ms]
T7[2] + T8[2] + T9[2]
T6[2] = ( INT( 10
) + 1 ) 10 = ( INT( 19.8
10
) + 1 ) 10 = 20[ms]
T7[2] + T8[2] + T9[2] = 7.8 + 12 = 19.8[ms]
T7[2] + T9[2] = ( ( 1 ) (11+4) 10 ) 1000 = 7.8[ms]
19200
T8[2] = 12[ms]
T7[3] + T8[3] + T9[3]
T6[3] = ( INT( 10
) + 1 ) 10 = ( INT( 40.4
10
) + 1 ) 10 = 50[ms]
T7[3] + T8[3] + T9[3] = 10.4 + 30 = 40.4[ms]
T7[3] + T9[3] = ( ( 1 ) (9+11) 10 ) 1000 = 10.4[ms]
19200
T8[3] = 30[ms]
Tinv = T1 + T2 + T3 = 1+153+1 = 155[ms]

E-14
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Inverter Communication 2.4 Execution Times in Inverter Communication Instructions

A
3. Calculation example 3

Common Items
Calculation of required time when Pr. 10 to Pr. 14 [ S2 = 5] are written by the IVBWR instruction
Tinv = T1 + T2 + T3 = 512[ms]
T1 = 1[ms], T3 = 1[ms]
Calculate "T2" as follows because Pr.10 to Pr. 14 do not require change of the 2nd parameter and the
time required for writing is same in each parameter. B

N:N Network
T2 = ( 2 (T4+T5) + T6[1]+T6[2] ) + ( 2 (T4+T5) + T6[3]+T6[4] ) +
Time required to write Pr. 10 Time required to write Pr. 11
= 5 ( 2 (T4+T5) + T6[1]+T6[2] ) = 5 ( 2 (20+1) + 20 + 40 ) = 510[ms]
S2
T4 = ( INT( 15
10
) + 1 ) 10 = 20[ms] C
T5 = 1[ms]

Parallel Link
T7[1] + T8[1] + T9[1]
T6[1] = ( INT( 10
) + 1 ) 10 = ( INT( 19.8
10
) + 1 ) 10 = 20[ms]
T7[1] + T8[1] + T9[1] = 7.8 + 12 = 19.8[ms]
T7[1] + T9[1] = ( ( 1 ) (11+4) 10 ) 1000 = 7.8[ms]
19200
T8[1] = 12[ms]
T7[2] + T8[2] + T9[2]
D
T6[2] = ( INT( ) + 1 ) 10 = ( INT( 38.9 ) + 1 ) 10 = 40[ms]

Computer Link
10 10
T7[2] + T8[2] + T9[2] = 8.9 + 30 = 38.9[ms]
T7[2] + T9[2] = ( ( 1 ) (13+4) 10 ) 1000 = 8.9[ms]
19200
T8[2] = 30[ms]
Tinv = T1 + T2 + T3 = 1+510+1 = 512[ms] E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-15
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.1 System Configuration

3. System Configuration and Selection


This chapter explains the system configuration and communication equipment selection operating in
accordance with RS-485 required by FX PLCs.

3.1 System Configuration


This section outlines the system configuration required to use inverter communication.
Connect (optional) equipment operating in accordance with RS-485 to the FX PLC main unit.

1 , 2 , 3 , 4 , 5 , 6 , 7 and 8 indicate the communication equipment combination patterns.


Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

1
This is the communication board 50 m
+ built into the PLC, reducing the
(164' 0")
installation area.

FX2N PLC
Communication board

Function extension memory cassette


(only for FX2N PLC)

2 Attach the special adapter


connection board to the main unit, 500 m
+ + and then attach the communication (1640' 5")
adapter to the left side of the main
unit.
FX2N PLC
Communication Special adapter
adapter connection board

Function extension memory cassette


(only for FX2N PLC)

3
+ Attach the communication adapter 500 m
to the left side of the main unit. (1640' 5")
FX2NC PLC
Communication adapter

Function extension memory board


(only for FX2NC PLC)

4 RD A

+
RD
RD B

SD A

SD SD B

SG

Communication board FX3U PLC


Because the communication board 50 m
can be built in to the PLC, the
installation area does not change (164' 0")
RD A

+
RD
RD B

SD A

SD SD B

SG

Communication board FX3UC-32MT-LT(-2)

E-16
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.1 System Configuration

Common Items
Communication equipment operating Total extension
in accordance with RS-485 FX PLC Important point in selection distance

5
+ +
B

N:N Network
Expansion FX3U PLC Attach the expansion board to the
Communication
adapter board main unit, and then attach the 500 m
communication adapter to the left (1640' 5")
side of the main unit.

+
+ C

Parallel Link
Communication Expansion FX3UC-32MT-LT(-2)
adapter board

6 D
Attach the communication adapter to 500 m

Computer Link
+ the left side of the main unit. (1640' 5")

Communication FX3GC, FX3UC(D, DS, DSS)


adapter
E

Communication
Inverter
Because the communication
7 board can be built in to the PLC, 50 m
+ the installation area does not (164' 0")
change.
Communication FX3S, FX3G PLC F
board

(RS/RS2 Instruction)
Communication
Non-Protocol
8 Attach the connector conversion adapter
to the main unit, and then attach the 500 m
+ + (1640' 5") G
communication adapter to the left side
of the main unit.

(FX2N-232IF)
Communication
Non-Protocol
Communication Connector FX3S, FX3G PLC
adapter conversion
adapter

H
Communication
Programming

For communication equipment combinations for each FX Series, refer to the next section.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-17
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.2 Applicable FX PLC and Communication Equipment

3.2 Applicable FX PLC and Communication Equipment


Select a (optional) communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the external dimensions are different between the units shown in "FX2NC-485ADP/
FX0N-485ADP". Select either one.
- In the table below, only the cable is different between the units shown in "FX3G-485-BD/FX3G-485-BD-
RJ". Select either one.
- Inverter communication is not provided for the FX1, FX2(FX), FX2C, FX0, FX0S, FX0N, FX1S, FX1N and
FX1NC PLCs.
Total
FX Series Communication equipment (option) extension Check
distance

50 m
(164' 0")

FX2N FX2N-485-BD

+
+ + 500 m
(1640' 5")
FX2N-ROM-E1
(Function extension FX2N-CNV-BD FX2NC-485ADP FX2N-CNV-BD FX0N-485ADP
memory cassette) (European terminal block) (Terminal block)

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3S
+ 500 m
(1640' 5")

FX3S-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

FX3G
(14-point, 24-point type) 500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

E-18
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.2 Applicable FX PLC and Communication Equipment

A
Total

Common Items
FX Series Communication equipment (option) extension Check
distance
When using channel 1 (ch 1)

N:N Network
50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch1 when connected to C
the option connector 1.

Parallel Link
500 m
(1640' 5") D

Computer Link
FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)

Communication
Inverter
FX3G
(40-point, 60-point type)
50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
F
The communication equipment works as ch2 when connected to

(RS/RS2 Instruction)
Communication
Non-Protocol
the option connector 2.

(FX2N-232IF)
Communication
Non-Protocol
500 m
(1640' 5")
FX3G-CNV-ADP FX3U- ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or H
FX3G-2EYT-BD is connected to the option connector 2.
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-19
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.2 Applicable FX PLC and Communication Equipment

Total
FX Series Communication equipment (option) extension Check
distance
When using channel 1 (ch 1)
ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)

ch1

+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


ch1 ch2

+
RD

FX3U SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
ch1 ch2

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

FX2NC
500 m
+ (1640' 5")

FX2NC-485ADP FX0N-485ADP
(European terminal block) (Terminal block)

FX2NC-ROM-CE1
(Function extension
memory board)

E-20
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.2 Applicable FX PLC and Communication Equipment

A
Total

Common Items
FX Series Communication equipment (option) extension Check
distance
When using channel 1 (ch 1)

ch1
B

N:N Network
500 m
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


C

Parallel Link
ch1 ch2
FX3GC

+ 500 m
(1640' 5") D

Computer Link
FX3U- ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
When using channel 1 (ch 1)

ch1
E

Communication
Inverter
500 m
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)
F
When using channel 2 (ch 2)

(RS/RS2 Instruction)
Communication
Non-Protocol
ch1 ch2
FX3UC
(D, DS, DSS)
+ 500 m G
(1640' 5")

(FX2N-232IF)
Communication
Non-Protocol
FX3U-ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-21
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Inverter Communication 3.2 Applicable FX PLC and Communication Equipment

Total
FX Series Communication equipment (option) extension Check
distance
When using channel 1 (ch 1)

ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)

ch1

+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)

ch1 ch2

+
RD

FX3UC-32MT-LT(-2) SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
ch1 ch2

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

E-22
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 3.2 Applicable FX PLC and Communication Equipment

Common Items
4. Wiring
This chapter explains the wiring. B

N:N Network
WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
C

Parallel Link
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.

WIRING PRECAUTIONS D

Computer Link
Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents
due to abnormal data written to the PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit or high-voltage lines. E
2) Ground the shield wire or shield of the shielded cable at one point on the PLC. However, do not use common

Communication
Inverter
grounding with heavy electrical systems.
Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual. F
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure

(RS/RS2 Instruction)
Communication
Non-Protocol
that the screwdriver does not touch the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual. G
- Twist the end of strand wire and make sure that there are no loose wires.

(FX2N-232IF)
Communication
Non-Protocol
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-23
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.1 Wiring Procedure

4.1 Wiring Procedure

1 Confirming the connection method


Confirm the inverter connection method.
For details, refer to Section 4.2.

2 Preparing for wiring


Prepare cables, distributors and terminal resistors required for wiring.
For connection cables, refer to Section 4.3.
For distributors, refer to Section 4.4.
For terminal resistors, refer to Section 4.5.

3 Turning OFF the PLC power


Before starting any wiring work, make sure that the PLC power is OFF.

4 Connecting the power supply (FX0N-485ADP only)


Connect the power supply to the 24V DC power terminal.

5 Wiring communication equipment


Connect communication equipment with communication port of inverters (PU port, built-in terminal
for RS-485, FR-A5NR, FR-7TR).
For details, refer to Section 4.8.

6 Connecting terminal resistors


Connect terminal resistors to the communication equipment of the PLC and the RDA-RDB signal
terminal in the last inverter.
For details, refer to Section 4.5.

7 Wiring a shielding wire (Class-D grounding)


When using a twisted pair cable, wire a shielding wire.
For details, refer to Section 4.6.

E-24
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.2 Selecting Cables and Connection Devices

A
4.2 Selecting Cables and Connection Devices

Common Items
When connecting equipment operating in accordance with RS-485, use the following connection method with
10BASE-T or shielded twisted pair cables.

Terminal resistor
B
PU connector Non-stranded cable

N:N Network
(10BASE-T cable for LAN) (Which is supplied with or built in the communication
(RJ45 connector) equipment for the FX PLC side, and should be arranged
by the user for the inverter side)

4.2.1 S500, E500, A500, F500, V500, D700 and E700 Series (PU connector)
C

Parallel Link
1. In the case of 1-to-1 connection
When a distributor is not used When a distributor is used

Terminal
Distributor
resistor D

Computer Link
*1 10BASE-T cable

10BASE-T cable RS-485 connector 10BASE-T cable


(PU connector)
Terminal resistor Terminal resistor
E
Use a distributor because a terminal resistor cannot
RS-485 connector

Communication
Inverter
be connected to the inverter.
(PU connector)

2. In the case of 1-to-N connection


When a distributor is used F

(RS/RS2 Instruction)
Communication
Non-Protocol
10BASE-T 10BASE-T Terminal
cable cable resistor
Distributor Distributor Distributor

10BASE-T cable 10BASE-T cable


G
*1
10BASE-T cable
10BASE-T cable

(FX2N-232IF)
Communication
Non-Protocol
Terminal resistor

RS-485 connector PU
connector
PU
connector H
Communication
Programming

*1. When using FX3G-485-BD-RJ, use the PU connector (RJ45 connector) for connection.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-25
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.2 Selecting Cables and Connection Devices

4.2.2 A500, F500 and V500 Series (FR-A5NR)

1. In the case of 1-to-1 connection


When a distributor is not used

FR-A5NR

Twisted pair cable Terminal


resistor

Terminal resistor

2. In the case of 1-to-N connection


When a distributor is not used

Twisted pair cable Twisted pair cable


Terminal
resistor

Twisted pair cable FR-A5NR FR-A5NR FR-A5NR


Terminal resistor

E-26
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.2 Selecting Cables and Connection Devices

A
4.2.3 F800, A800, F700 and A700 Series (built-in RS-485 terminal)

Common Items
1. In the case of 1-to-1 connection
Set the terminal resistor switch in the inverter to "100 ".

Built-in RS-485 B
terminal

N:N Network
Twisted pair cable
C

Parallel Link
2. In the case of 1-to-N connection
Set the terminal resistor switch in the last inverter to "100 ".

D
Twisted pair cable Twisted pair cable

Computer Link
Twisted pair cable
E

Communication
Inverter
Built-in Built-in Built-in
RS-485 RS-485 RS-485
terminal terminal terminal
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-27
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.2 Selecting Cables and Connection Devices

4.2.4 E700 Series (FR-E7TR)

1. In the case of 1-to-1 connection


When a distributor is not used

FR-E7TR

Twisted pair cable

Terminal resistor

2. In the case of 1-to-N connection


When a distributor is not used

Twisted pair cable Twisted pair cable

Twisted pair cable


FR-E7TR FR-E7TR FR-E7TR
Terminal resistor

E-28
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.3 Connection Cables

A
4.3 Connection Cables

Common Items
4.3.1 10BASE-T cable
10BASE-T cables used in LAN wiring for a personal computer can be connected. B

N:N Network
1. Selection procedure when purchasing
1) Cable type : 10BASE-T cable (Category 3 or 5)
2) Connection specifications : Straight type
3) Connector : RJ45 connector
C
2. Cautions on using commercial cables

Parallel Link
Pay attention to the following point when purchasing commercial cables.
5V DC is output to the PU connector in the inverters for supplying power to the PU.
It is necessary to cut pins No. 2 and 8 of commercial cables to prevent wiring to pins No. 2 and 8.
(It is recommended to use the distributor BMJ-8-28N).
D
4.3.2 Twisted pair cable (recommended)

Computer Link
The table below shows recommended model names and manufacturers of cables used in wiring.
Use commercial three-pair type twisted pair cables of 0.3 mm2 or more.

1. Recommended cable list E

Communication
Inverter
Manufacturer Model name Remarks
DPEV SB 0.3 3P Three-pair cable of 0.3 mm2
Sumitomo Electric Industries, Ltd.
DPEV SB 0.5 3P Three-pair cable of 0.5 mm2
The Furukawa Electric Co., Ltd. D-KPEV-SB 0.5 3P Three-pair cable of 0.5 mm2
F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Cable structural drawing (reference)

(FX2N-232IF)
Communication
Three-pair cable structural Non-Protocol
drawing example
H
3. Point of contact
Communication
Programming

For details on cables such as specifications and price, contact each cable manufacturer.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-29
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.3 Connection Cables

4.3.3 Connecting cables

1. European type terminal block


The FX3G-485-BD-RJ terminal block is used for grounding.
The other options use shielded twisted pair cables for connecting communication equipment operating in
accordance with RS-485.
The table below shows applicable cables and tightening torques.
Cable size when Cable size when Bar terminal with Tool size
Tightening
one cable is two cables are Insulating sleeve
torque A B
connected connected (cable size)
FX3U-485-BD
FX3G-485-BD AWG22 to Applicable 0.22 to 0.25
AWG22 0.4 (0.01") 2.5 (0.09")
FX3U-485ADP AWG20 (AWG22 to AWG20) Nm
(-MB)
FX3G-485-BD- 0.5 to 0.6
AWG20 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
RJ Nm
0.5 to 0.6
FX2N-485-BD AWG26 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
Nm
AWG26 to AWG26 to 0.4 to 0.5
FX2NC-485ADP Not applicable 0.6 (0.03") 3.5 (0.14")
AWG16 AWG20 Nm

Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
With regard to the cable end treatment, use a stranded cable or solid cable as it is, or use a bar terminal with
insulating sleeve.
FX3G-485-BD-RJ, FX2N-485-BD and FX2NC-485ADP cannot use a bar terminal with insulating sleeve.
When using a stranded cable or solid cable as it is
- Twist the end of a stranded cable so that wires do not get barbed.
- Do not plate the end of the cable.
FX3G-485-BD, FX3U-485-BD, FX3G-485-BD-RJ,
FX3U-485ADP(-MB) FX2N-485-BD FX2NC-485ADP

Approx. 9 mm Approx. 6 mm Approx. 8 mm


(0.35") (0.23") (0.31")

When using a bar terminal with insulating sleeve Insulating sleeve Contact area
Because it is difficult to insert a cable into an insulating sleeve (Crimp area)
depending on the thickness of the cable sheath, select the proper cable
according to the outline drawing. 8 mm (0.31")
<Reference> 2.6 mm
14 mm
(0.1")
Manufacturer Model name Caulking tool (0.55")

CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
(or CRIMPFOX 6T-F*2)

*1. Old model name : CRIMPFOX ZA 3


*2. Old model name : CRIMPFOX UD 6

E-30
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.4 Connection Devices (RJ45 Connector and Distributor)

A
Tool

Common Items
Select a
When tightening a terminal on the European terminal block, use a small screwdriver
with a
commercial straight shape screwdriver whose tip is shown in the figure to straight tip.
the right.

Note A
For size A and size B,
B
B
If the diameter of screwdriver grip is too small, tightening torque will not refer to the table above.

N:N Network
be able to be achieved. To achieve the appropriate tightening torque
shown in the previous page, use the following screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
<Reference>
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB)
C
Manufacturer Model name

Parallel Link
Phoenix Contact Co., Ltd. SZS 0.4 2.5

FX3G-485-BD-RJ, FX2N-485-BD, FX2NC-485ADP


Manufacturer Model name
Phoenix Contact Co., Ltd. SZF 1-0.6 3.5 D

Computer Link
2. Terminal block
In the FX0N-485ADP, the terminal screw size is "M3".
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 Nm.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions. E

Communication
Inverter
When wiring one cable to one terminal
Terminal Crimp
3.2(0.13") screw terminal
6.2mm(0.24")
or less
3.2(0.13")
F
6.2mm(0.24")

(RS/RS2 Instruction)
Communication
Non-Protocol
Terminal
or less

When wiring two cables to one terminal


3.2(0.13")
Terminal Crimp
G
6.2mm(0.24")

(FX2N-232IF)
Communication
Non-Protocol
or less screw terminal
6.3mm(0.25")
or more

3.2(0.13")
6.2mm(0.24")
or less
Terminal H
6.3mm(0.25")
Communication
Programming

or more

4.4 Connection Devices (RJ45 Connector and Distributor)


I
Prepare the following devices if necessary.
Maintenance
Remote

Product name Model name Manufacturer


RJ45 connector 5-554720-3 Tyco Electronics Japan G.K.
BMJ-8
BMJ-8-28N (No internal connection of the No. 2
Distributor HACHIKO ELECTRIC CO., LTD.
and 8 pin) Apx.A
(Do not use a plug with terminal resistor)
models
Discontinued

E-31
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.5 Connecting Terminal Resistors

4.5 Connecting Terminal Resistors


Connect a terminal resistor to both the communication equipment of the FX PLC and the RDA-RDB signal
terminal in the last inverter.
For details on connection, refer to each wiring diagram.

1. Terminal resistor types Brown Precision


Prepare the following two types of terminal resistors.
Among the terminal resistors supplied with the communication equipment,
select ones with the color codes shown to the right.
1) On the FX PLC side, use a terminal resistor of 110 , 1/2 W supplied 1 1 1 =110
together with the communication equipment operating in accordance with (101)
RS-485. Brown Black Brown Precision

2) On the inverter side (PU connector except FR-A5NR, FR-E7TR), use a


terminal resistor of 100 , 1/2 W (not supplied).
3) On the inverter side (FR-A5NR), use a terminal resistor chip (supplied 1 0 1 =100
together with the FR-A5NR). (101)
4) On the inverter side (FR-E7TR), use the terminal resistor switch.

2. Connecting a terminal resistor to the FX PLC


Connect a terminal resistor between the RDA and RDB terminals of the communication equipment.

3. When using the FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ or FX3U-485ADP(-MB)


The FX3G-485-BD, FX3U-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB) have built-in terminal resistors.
Set the terminal resistor selector switch accordingly.
FX3U-485-BD FX3U-485ADP(-MB)

Terminal 330
resistor Terminal
OPEN resistor selector
selector switch
switch 110

FX3G-485-BD
Remove the upper terminal block before changing over the switch in the FX3G-485-BD.

Removal: Loosen the terminal block mounting screws, and remove the terminal block.
Installation: Attach the terminal block, and tighten the terminal block mounting screws.
Tightening torque : 0.4 to 0.5 Nm
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do
so may cause equipment failures or malfunctions.
For installation and removal of the terminal block, use the
recommended tool shown below or a tool having straight tip (such as Select a
screwdriver) as shown in the right figure. screwdriver
with a
<Reference> straight tip.

Manufacturer Model name


Phoenix Contact Co., Ltd. SZS 0.4 2.5 0.4mm 2.5mm
(0.01") (0.09")

Terminal resistor
selector switch

Terminal block mounting screws

E-32
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.6 Wiring a Shielding Wire (Class-D grounding)

A
FX3G-485-BD-RJ

Common Items
Terminal resistor
selector switch B

N:N Network
4. Connecting a terminal resistor to the inverter
Communication may be affected by noise echo depending on the transmission speed and transmission C

Parallel Link
distance. When communication is hindered by noise echo, connect a terminal resistor to the inverter.
1) When the PU connector or RS-485 connector (S500 Series) is used
- Connect a terminal resistor between pin No. 3 (RDA) and pin No. 6 (RDB).
- Connect a distributor to the PU terminal because terminal resistors cannot be connected.
- Connect a terminal resistor only to the inverter located furthest away from the FX PLC. D
2) When the FR-A5NR is used in connection

Computer Link
- Connect a terminal resistor chip (which is supplied together with the FR-A5NR) between the RDB and
RDR terminals in the most distant inverter.
3) When the FR-E7TR is used in connection
A terminal resistor is built into the FR-E7TR. Set the terminal resistor switch in the E700 Series inverter
located at the end to "100". E

Communication
Inverter
Terminal
resistor
switch

(RS/RS2 Instruction)
Communication
Non-Protocol
4) When the inverter built-in RS-485 terminal is used
A terminal resistor is built into the RS-485 terminal. Set the terminal resistor switch in the F700/A700
Series inverter located at the end to "100".
G

(FX2N-232IF)
Communication
Non-Protocol
OPEN
Terminal
resistor
switch
100
H
Communication
Programming

4.6 Wiring a Shielding Wire (Class-D grounding)


Perform Class-D grounding only to one side of a cable according to the absence/presence of the grounding I
terminal.
Maintenance
Remote

For details on connection, refer to each wiring diagram.

1. When the FG terminal is provided in the communication equipment


Connect the FG terminal to the (grounding) terminal of the PLC requiring Class-D grounding.

2. When the FG terminal is not provided in the communication equipment


Apx.A
models
Discontinued

Perform Class-D grounding directly to the shielding wire of the cable.

E-33
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.7 Connector in Inverter

4.7 Connector in Inverter

1. In the case of PU port connector


Pin No. Signal name Remarks When seen from inverter front
8 P5S Not used (receptacle side)
7 SG
(8)
6 RDB
5 SDA
4 SDB (1)
3 RDA Modular jack
2 P5S Not used
1 SG

The pins Nos. 2 and 8 (P5S) are provided for the power supply of the operation panel or parameter unit.
Do not wire them into inverter communication.

2. In the case of computer link using the FR-A5NR


Attach the FR-5NR to an A500, F500 or V500 Series inverter.

Terminal
block
Screw size: SDA SDB RDA RDB RDR SG A B C
M3
Terminal
symbol

Connect them to PLC communication


equipment operating in accordance with
RS-485.
For details, refer to the instruction manual of the FR-A5NR.

3. In the case of computer link using the FR-E7TR


Attach the FR-E7TR to an E700 Series inverter.

Terminal block
Connect them to PLC
communication equipment
operating in accordance
with RS-485.

For details, refer to the instruction manual of the FR-E7TR.

E-34
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.7 Connector in Inverter

A
4. In the case of built-in RS-485 terminal

Common Items
F800, A800, F700 and A700 Series inverters are equipped with a built-in RS-485 terminal.

Terminal
symbol
B
Connect them to the communication equipment

N:N Network
operating in accordance with RS-485 of the PLC.
European
terminal block

For details, refer to the instruction respective inverter manual.


C

Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-35
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

4.8 Connection Diagram

4.8.1 For S500, E500, A500, F500 , V500 and D700 Series (PU connector)

1. When one inverter is connected

Terminal resistor: 110


FX3U-485-BD, FX3G-485-BD and
FX3U-485ADP(-MB):
Set the built-in selector switch.
FX2N-485-BD and FX2NC-485ADP:
FX3U-485-BD Connect a terminal resistor (supplied)
FX3G-485-BD between the RDA and RDB terminals.
FX2N-485-BD
FX2NC-485ADP Distributor
FX0N-485ADP FX3U-485ADP(-MB) Connect a terminal
RDA RDA 5 5 resistor of 100 , 1/2 W
RDB RDB 4 4 (not supplied).
SDA SDA 3 3
SDB SDB 6 6 When seen from inverter front
24V (receptacle side)
DC LINK SG 1 1
50mA SG 10BASE-T 54361
cable 8
24+
24G PU (RS-485) S S R R
FG connector DDDD S
A B A BG 1
Class-D grounding PLC Inverter
54361 Modular jack

FX3G-485-BD-RJ
FX3G-485-BD-RJ Distributor (BMJ-8-28N)
RDA 5 5 5 Connect a terminal resistor of
RDB 4 4 4 100 , 1/2 W (not supplied).
SDA 3 3 3
SDB 6 6 6
SG 1 1 1
2 2 2
Terminal
resistor 7 7 7
8 8 8
Connector metal frame 5 4 3 6 1 2 7 8

PU(RJ45) 5 4 3 6 1 2 7 8
(Terminal resistor connector
RDA
RDB
SDA
SDB

selector switch: 110)


SG

(Wiring circuit switch:


2 pair)
PLC Inverter

E-36
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

A
2. When two or more (up to eight) inverters are connected

Common Items
Terminal resistor: 110
FX3U-485-BD, FX3G-485-BD and
FX3U-485ADP(-MB): Connect a terminal resistor of
Set the built-in selector switch. 100 , 1/2 W (not supplied) to
FX2N-485-BD and FX2NC-485ADP: the most distant inverter.
FX3U-485-BD
FX3G-485-BD
Connect a terminal resistor (supplied)
between the RDA and RDB terminals.
B

N:N Network
FX2N-485-BD
FX2NC-485ADP Distributor Distributor Distributor
FX0N-485ADP FX3U-485ADP(-MB)
RDA RDA 5 5 5 5 5 5
RDB RDB 4 4 4 4 4 4
SDA SDA 3 3 3 3 3 3
SDB SDB 6 6 6 6 6 6 C
24V
LINK SG 1 1 1 1 1 1

Parallel Link
DC
50mA SG 10BASE-T 54361 54361 54361
cable
24+
24G PU (RS-485) S S R R S PU (RS-485) S S R R S PU (RS-485) S S R R S
FG connector D D D D G connector D D D D G connector D D D D G
ABAB ABAB ... ABAB
Class-D grounding PLC Inverter
54361
Inverter
54361
Inverter
54361 D

Computer Link
For the pin arrangement in the connector,
refer to the connection diagram for one inverter.

FX3G-485-BD-RJ
Connect a terminal resistor of
100 , 1/2 W (not supplied) to E
the most distant inverter.

Communication
Inverter
FX3G-485-BD-RJ Distributor (BMJ-8-28N) Distributor (BMJ-8-28N)
RDA 5 5 5 5 5
RDB 4 4 4 4 4
SDA 3 3 3 3 3 F
SDB 6 6 6 6 6

(RS/RS2 Instruction)
Communication
Non-Protocol
SG 1 1 1 1 1
2 2 2 2 2
Terminal
resistor 7 7 7 7 7
8 8 8 8 8
Connector metal frame 5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 G

(FX2N-232IF)
Communication
Non-Protocol
PU(RJ45) 5 4 3 6 1 2 7 8 PU(RJ45) 5 4 3 6 1 2 7 8
(Terminal resistor connector connector
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB

selector switch: 110)


SG

SG

(Wiring circuit switch:


2 pair)
H
Communication
Programming

PLC Inverter Inverter

I
Maintenance
Remote

Apx.A
models
Discontinued

E-37
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

4.8.2 For A500, F500 and V500 Series (FR-A5NR)

1. When one inverter is connected


Terminal resistor: 110
FX3U-485-BD, FX3G-485-BD and
FX3U-485ADP(-MB):
FX3U-485-BD Set the built-in selector switch.
FX3G-485-BD FX2N-485-BD and FX2NC-485ADP:
FX2N-485-BD Connect a terminal resistor (supplied)
FX2NC-485ADP between the RDA and RDB terminals.
FX0N-485ADP FX3U-485ADP(-MB)
RDA RDA Twisted pair cable
RDB RDB (0.3mm2or more)
SDA SDA
SDB SDB Connect the terminal resistor connection piece.
24V 0.3mm2 or more
DC LINK SG
50mA
SG Terminal
24+ arrangement
SS RRR
24G S DD DDD
G Terminal
AB A BR block
FG
FR-A5NR Screw size: SDA SDB RDA RDB RDR SG A B C

Class-D grounding PLC M3


Inverter
Terminal
symbol Connect them to the
communication unit of the PLC.

2. When two or more (up to eight) inverters are connected


Terminal resistor: 110
FX3U-485-BD, FX3G-485-BD and
FX3U-485ADP(-MB):
Set the built-in selector switch.
FX2N-485-BD and FX2NC-485ADP:
FX3U-485-BD Connect a terminal resistor (supplied)
FX3G-485-BD between the RDA and RDB terminals.
FX2N-485-BD Connect the terminal
FX2NC-485ADP Twisted pair cable resistor connection
FX0N-485ADP FX3U-485ADP(-MB) (0.3mm2 or more) piece to the inverter
RDA RDA located furthest
RDB RDB away from the PLC.
SDA SDA
SDB SDB
24V 0.3mm2 or more
DC LINK SG
50mA SG Class D Class D
grounding grounding
24+
SS RRR SS RRR SS RRR
24G S DD DDD S DD DDD S DD DDD
G AB G AB G AB
FG A BR ABR
.... ABR

PLC FR-A5NR FR-A5NR FR-A5NR


Class-D grounding Inverter Inverter Inverter

For the pin arrangement of the connector,


refer to the connection diagram above for one inverter.

E-38
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

A
4.8.3 For E700 Series (PU connector)

Common Items
1. When one inverter is connected (4-wire type)

Terminal resistor: 110


FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB): B
Set the built-in selector switch.

N:N Network
Distributor
Connect a terminal
resistor of 100 , 1/2 W
(not supplied).
C
When seen from inverter front

Parallel Link
(receptacle side)
10BASE-T
cable

PU (RS-485)
connector
PLC Inverter D
Modular jack

Computer Link
FX3G-485-BD-RJ
FX3G-485-BD-RJ Distributor (BMJ-8-28N)
RDA
RDB
5
4
5
4
5
4
Connect a terminal resistor of
100 , 1/2 W (not supplied).
E

Communication
Inverter
SDA 3 3 3
SDB 6 6 6
SG 1 1 1
2 2 2
Terminal
resistor 7 7 7
8 8 8 F
Connector metal frame

(RS/RS2 Instruction)
Communication
Non-Protocol
5 4 3 6 1 2 7 8

PU(RJ45) 5 4 3 6 1 2 7 8
connector
(Terminal resistor
G
RDA
RDB
SDA
SDB

selector switch: 110)


SG

(Wiring circuit switch:

(FX2N-232IF)
Communication
Non-Protocol
2 pair)
PLC Inverter

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-39
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

2. When two or more (up to eight) inverters are connected (4-wire type)
Terminal resistor: 110 Connect a terminal resistor of
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB): 100 , 1/2 W (not supplied) to
Set the built-in selector switch. the most distant inverter.

Distributor Distributor Distributor

10BASE-T
cable

PU (RS-485) PU (RS-485) PU (RS-485)


connector connector connector
PLC Inverter Inverter Inverter

For the pin arrangement in the connector,


refer to the connection diagram for one inverter.

FX3G-485-BD-RJ
Connect a terminal resistor of
100 , 1/2 W (not supplied) to
the most distant inverter.

FX3G-485-BD-RJ Distributor (BMJ-8-28N) Distributor (BMJ-8-28N)


RDA 5 5 5 5 5
RDB 4 4 4 4 4
SDA 3 3 3 3 3
SDB 6 6 6 6 6
SG 1 1 1 1 1
2 2 2 2 2
Terminal
resistor 7 7 7 7 7
8 8 8 8 8
Connector metal frame 5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8

PU(RJ45) 5 4 3 6 1 2 7 8 PU(RJ45) 5 4 3 6 1 2 7 8
(Terminal resistor connector connector
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB

selector switch: 110)


SG

SG

(Wiring circuit switch:


2 pair)
PLC Inverter Inverter

E-40
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

A
3. When one inverter is connected (2-wire type)

Common Items
Terminal resistor: 110
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):
Set the built-in selector switch.

Distributor
B
Connect a terminal

N:N Network
resistor of 100 , 1/2 W
(not supplied).

When seen from inverter front


(receptacle side)
10BASE-T C
cable

Parallel Link
PU (RS-485)
connector
PLC Inverter
Modular jack

D
FX3G-485-BD-RJ

Computer Link
FX3G-485-BD-RJ Distributor (BMJ-8-28N)
RDA 5 5 5 Connect a terminal resistor of
RDB 4 4 4 100 , 1/2 W (not supplied).
SDA
SDB
3
6
3
6
3
6
E

Communication
Inverter
SG 1 1 1
2 2 2
Terminal
resistor 7 7 7
8 8 8
Connector metal frame 5 4 3 6 1 2 7 8
F

(RS/RS2 Instruction)
Communication
Non-Protocol
PU(RJ45) 5 4 3 6 1 2 7 8
(Terminal resistor connector
RDA
RDB
SDA
SDB

selector switch: 110)


SG

(Wiring circuit switch:


1 pair) G
PLC

(FX2N-232IF)
Communication
Non-Protocol
Inverter

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-41
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

4. When two or more (up to eight) inverters are connected (2-wire type)
Terminal resistor: 110 Connect a terminal resistor of
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB): 100 , 1/2 W (not supplied) to
Set the built-in selector switch. the most distant inverter.

Distributor Distributor Distributor

10BASE-T
cable

PU (RS-485) PU (RS-485) PU (RS-485)


connector connector connector
PLC Inverter Inverter Inverter

For the pin arrangement in the connector,


refer to the connection diagram for one inverter.

FX3G-485-BD-RJ
Connect a terminal resistor of
100 , 1/2 W (not supplied) to
the most distant inverter.

FX3G-485-BD-RJ Distributor (BMJ-8-28N) Distributor (BMJ-8-28N)


RDA 5 5 5 5 5
RDB 4 4 4 4 4
SDA 3 3 3 3 3
SDB 6 6 6 6 6
SG 1 1 1 1 1
2 2 2 2 2
Terminal
resistor 7 7 7 7 7
8 8 8 8 8
Connector metal frame 5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8

PU(RJ45) 5 4 3 6 1 2 7 8 PU(RJ45) 5 4 3 6 1 2 7 8
(Terminal resistor connector connector
RDA
RDB

RDA
RDB

selector switch: 110)


SDA
SDB

SDA
SDB
SG

SG

(Wiring circuit switch:


1 pair)
PLC Inverter Inverter

E-42
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

A
4.8.4 For E700 Series (FR-E7TR)

Common Items
1. When one inverter is connected (4-wire type)

Terminal resistor: 110 B


FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):

N:N Network
Set the built-in selector switch.

Twisted pair cable


(0.3mm2 or more)
Set the terminal resistor
switch to the "100 " side. C
0.3mm2 or more

Parallel Link
Terminal
arrangement
Terminal
block
PLC
Inverter Connect them to PLC
communication unit.
D

Computer Link
2. When two or more (up to eight) inverters are connected (4-wire type)
E
Terminal resistor: 110

Communication
Inverter
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):
Set the built-in selector switch.
Set the terminal resistor
Twisted pair cable switch to "100 " in the inverter
(0.3mm2 or more) located furthest away from the PLC.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
0.3mm2 or more

Class D Class D
grounding grounding
G

(FX2N-232IF)
Communication
Non-Protocol
PLC
Inverter Inverter Inverter

For the pin arrangement of the connector,


refer to the connection diagram above for one inverter.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-43
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

When adopting branches, perform the wiring as shown below: (4-wire type)

When connecting a 100 terminal resistor, set the switch to the "100 " side.

For crossover wiring of a shielded cable using the terminal SG, set the
terminal 2/SG selector switch to the right side (ON) to change over the
terminal 2 to the terminal SG.
(By this setting, analog inputs to the terminal 2 become invalid.)

To next station inverter

PLC

E-44
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

A
3. When one inverter is connected (2-wire type)

Common Items
Terminal resistor: 110
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):
Set the built-in selector switch.

Twisted pair cable B


(0.3mm2 or more)

N:N Network
Set the terminal resistor switch to the
Crossover "100 " side.
0.3mm2 or more wiring

Terminal
arrangement C
Terminal

Parallel Link
block
PLC Connect them to PLC
Inverter
communication unit.

Computer Link
4. When two or more (up to eight) inverters are connected (2-wire type)
Terminal resistor: 110
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):
Set the built-in selector switch. Set the terminal resistor switch
to "100 " in the inverter located
Twisted pair cable
furthest away from the PLC. E

Communication
Inverter
(0.3mm2 or more)
Crossover Crossover Crossover
wiring wiring wiring

0.3mm2 or more

Class D
grounding
Class D
grounding
F

(RS/RS2 Instruction)
Communication
Non-Protocol
PLC
Inverter Inverter Inverter

For the pin arrangement of the connector,


refer to the connection diagram above for one inverter.
G

(FX2N-232IF)
Communication
Non-Protocol
When adopting branches, perform the wiring as shown below: (2-wire type)

When connecting a 100 terminal


resistor, set the switch to the "100 "
H
Communication
Programming

side.

For crossover wiring of a shielded cable using the


terminal SG, set the terminal 2/SG selector switch
to the right side (ON) to change over the terminal
2 to the terminal SG. I
(By this setting, analog inputs to the terminal 2
Maintenance
Remote

become invalid.)

To next station inverter


Apx.A
PLC
models
Discontinued

Perform crossover wiring.

E-45
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.8 Connection Diagram

4.8.5 For F800, A800, F700 and A700 Series (built-in RS-485 terminal)

1. When one inverter is connected

Terminal resistor: 110


- FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):
FX3U-485-BD Set the built-in selector switch.
FX3G-485-BD
FX3U-485ADP(-MB)
RDA Twisted pair cable
(0.3mm2 or more)
RDB
SDA
Set the terminal resistor switch to the
SDB "100" side.
SG 0.3mm2 or more

SS RR
S DD DD
G AB AB
11 11
PLC Class-D
grounding
Inverter

2. When two or more (up to eight) inverters are connected

Terminal resistor: 110


- FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB):
Set the built-in selector switch.
Set the terminal resistor switch
FX3U-485-BD to "100" in the inverter located
FX3G-485-BD Twisted pair cable furthest away from the PLC.
(0.3mm2 or more)
FX3U-485ADP(-MB)
RDA
RDB
SDA
SDB
0.3mm2 or more
SG
Class-D Class-D
grounding grounding
Class-D SS SS R R RR SS SS R R RR SS RR
grounding S D D DD D D DD S S DD D D D D DD S .... S DD DD
G BA BA B ABA G G BA BA BA BA G G BA BA
PLC 1122 1122 1122 1122 11 11

Inverter Inverter Inverter

When adopting branches, perform the wiring as shown below:

+ - + - RXD + - + - RXD
Connect them Connect them to
to SDA and RDA1 and RDB1 in
SDB in PLC. TXD + - + - TXD + - + - next inverter.
Connect them Connect them to
to RDA and SDA1 and SDB1 in
RDB in PLC. SG SG VCC SG SG VCC next inverter.
Connect it to Connect it to SG in
SG in PLC. next inverter.

E-46
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Inverter Communication 4.9 Grounding

A
4.8.6 Switching of 1 pair / 2 paired wiring (FX3G-485-BD-RJ)

Common Items
The FX3G-485-BD-RJ has a built-in wiring circuit switch.
Set the wiring circuit switch to 1 pair / 2 pair.

N:N Network
Wiring circuit
switch

Parallel Link
4.9 Grounding
Grounding should be performed as stated below.
D
The grounding resistance should be 100 or less.

Computer Link
Independent grounding should be performed for best results.
When independent grounding can not be performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the Hardware Edition of each series.

PLC Other PLC Other PLC Other E


equipment equipment equipment

Communication
Inverter
Independent grounding Shared grounding Common grounding
Best condition Good condition Not allowed

The grounding wire size should be AWG 14 (2 mm2) or larger.


F
The grounding point should be close to the PLC, and all grounding wires should be as short as possible.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-47
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.1 Communication Port and Applicable Parameters

5. Communication Setting in Inverter


Before connecting an inverter to a PLC, set parameters related to communication in the inverter parameter
unit (PU) in advance using the procedure described in this chapter.
If these parameters are overwritten from the PLC after the inverter is connected, communication will be
disabled.
If these parameters are changed by mistake, they should be set again.

5.1 Communication Port and Applicable Parameters


When connecting an inverter to a PLC, it is necessary to set parameters corresponding to the communication
port in advance.

S500 Series E500 Series A500, F500 and V500 Series


Remove the surface cover. Remove the operation panel. Remove the operation panel.
PU
connector

FR-A5NR

PU Remove the
connector surface cover
RS-485 port
(PU connector)

F700 and A700 Series E700 Series


Remove the surface cover. Open the PU connector cover. Remove the surface cover.

FR-E7TR
PU connector

RS-485 terminal
D700 Series F800, A800 Series
Remove the surface cover. Remove the surface cover.

RS-485
terminal

PU connector

E-48
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.1 Communication Port and Applicable Parameters

A
Inverter connection Parameters applicable in Reference

Common Items
Model Model classification
destination inverter section
S500 Series Only models with built-in RS-485 port RS-485 port Pr79, n1 to n12 5.2
E500 Series Models with built-in PU port PU port Pr79, Pr117 to Pr124 5.3
Models with built-in PU port PU port Pr79, Pr117 to Pr124 5.4
A500 Series
Option FR-A5NR computer link Pr79, Pr331 to Pr342 5.5
B

N:N Network
Models with built-in PU port PU port Pr79, Pr117 to Pr124 5.4
F500 Series
Option FR-A5NR computer link Pr79, Pr331 to Pr342 5.5
Models with built-in PU port PU port Pr79, Pr117 to Pr124 5.4
V500 Series
Option FR-A5NR computer link Pr79, Pr331 to Pr342 5.5

D700 Series Models having built-in PU port PU port


Pr79, Pr117 to Pr124,
5.6
C
Pr340, Pr549

Parallel Link
Models having built-in PU port PU port
Pr79, Pr117 to Pr124,
E700 Series FR-E7TR 5.6
Option Pr.340, Pr549
control terminal option
A700 Series Models with built-in RS-485 terminal RS-485 terminal Pr79, Pr331 to Pr342, Pr549 5.7
F700 Series Models with built-in RS-485 terminal RS-485 terminal Pr79, Pr331 to Pr342, Pr549 5.7 D

Computer Link
Pr79, Pr331 to Pr342, Pr549
PN000, PN001, PN030 to
A800 Series Models with built-in RS-485 terminal RS-485 terminal 5.8
PN038, PD000, PD001,
PD010, PD011
Pr79, Pr331 to Pr342, Pr549
F800 Series Models with built-in RS-485 terminal RS-485 terminal
PN000, PN001, PN030 to
5.8
E
PN038, PD000, PD001,

Communication
Inverter
PD010, PD011

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-49
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.2 S500 Series (When Connected to RS-485 Port)

5.2 S500 Series (When Connected to RS-485 Port)

5.2.1 Contents of parameter setting

1. Contents of communication setting (essential items)


The table below shows parameters which should be set in all cases.
Parameter No. Parameter item Set value Setting contents
n1 Communication station number 00 to 31 Up to eight inverters can be connected.
48 4800 bps
n2 Communication speed 96 9600 bps
192 19200 bps (standard)
n3 Stop bit length 10 Data length: 7-bit/Stop bit: 1-bit
n4 Parity check presence/absence 2 Even parity present
n7 Wait time setting --- Set with communication data
n11 CR/LF selection 1 With CR, without LF
External operation mode is selected when
Pr79 Operation mode selection 0
power is turned ON.
n10 Link start mode selection 1 Computer link operation
n6 Communication check time interval --- Communication check suspension

2. Parameters which should be adjusted between test operation and actual operation
Parameter No. Parameter item Set value Setting contents
Number of Set the value shown on the left during adjustment, and
n5 ---
communication retries set a value from 1 to 10 during operation.

3. Others (which should be set if necessary)


The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter No. Parameter item Set value Setting contents
0: Written to RAM and EEPROM
n12 EEPROM write selection 0 or 1
1: Written to RAM only. Not written to EEPROM
Operation command 0: PLC
n8 0 or 1
write 1: External
0: PLC
n9 Speed command write 0 or 1
1: External
0 or 0.1 to 0: Frequency display, setting
Pr37 Speed display*1 999 0.1 to 999: Machine speed at 60Hz.

*1. This inverter communication function cannot read or write Pr37.


Set Pr37 to "0" when setting or monitoring the frequency in the PLC.
If any value other than "0" is set and the instruction code HFF is set to "01", the frequency may not be
set or monitored normally.

E-50
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.2 S500 Series (When Connected to RS-485 Port)

A
5.2.2 Parameter setting method (reference)

Common Items
This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
RUN indicator
Lights or flashes during
operation.
B
3-digit monitor LED

N:N Network
Shows the frequency,
parameter number, etc.

MODE key
Setting dial Changes over the setting mode. C
Changes the set value of

Parallel Link
the frequency and SET key
parameters. Sets each setting.

The operating procedure example below shows a case in which the baud rate is set to 19,200 bps.
D
1 Confirming the RUN indicator and the operation mode

Computer Link
Confirm that the operation is stopped (that the RUN indicator is OFF).

2 Selecting the parameter setting mode


Press the MODE key, and select the parameter setting mode.
E

Communication
Inverter
Monitor/frequency setting mode Parameter setting mode

The last parameter read


is displayed.

F
3 Setting the set value of Pr. 30 to "1"

(RS/RS2 Instruction)
Communication
Non-Protocol
(This step is not necessary if Pr. 30 is already set to "1".)
1. Turn the setting dial to display "P30".

(FX2N-232IF)
Communication
Non-Protocol
2. Press the SET key to read the currently set value.

H
Communication
Programming

3. Turn the setting dial to change the set value to "1".

I
Maintenance
Remote

Press the SET key to set "1".

Apx.A
models
Discontinued

The set value and parameter number are displayed alternately.


When the set value and parameter number are displayed alternately, the setting is completed.

E-51
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.2 S500 Series (When Connected to RS-485 Port)

4 Setting the set value of "n2" to "192"


("192" indicates the baud rate of 19200 bps.)
Turn the setting dial to display "n2".

Press the SET key to read the currently set value.

Turn the setting dial to change the set value to "192".

Press the SET key to set "192".

The set value and parameter number are displayed alternately.


When the set value and parameter number are displayed alternately, the setting is completed.

5 Changing other parameters in the same way as step 4


For details on the parameters to be set, refer to Subsection 5.2.1.

E-52
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.3 E500 Series (When Connected to PU Port)

A
5.3 E500 Series (When Connected to PU Port)

Common Items
5.3.1 Contents of parameter setting

1. Contents of communication setting (essential items)


B

N:N Network
The table below shows parameters which should be set in all cases.
Parameter No. Parameter item Set value Setting contents
Pr117 Communication station number 00 to 31 Up to eight inverters can be connected.
48 4800 bps
Pr118 Communication speed 96 9600 bps C

Parallel Link
192 19200 bps (standard)
Pr119 Stop bit / Data length 10 Data length: 7-bit/Stop bit: 1-bit
Pr120 Parity check presence/absence 2 Even parity present
Pr123 Waiting time setting 9999 Set with communication data

Pr124
CRLF presence/absence
selection
1 With CR, without LF D

Computer Link
External operation mode is selected when power
Pr79 Operation mode selection 0
is turned ON.
Communication check time
Pr122 9999 Communication check suspension
interval

2. Parameters which should be adjusted between test operation and actual operation
E

Communication
Inverter
Parameter No. Parameter item Set value Setting contents
Number of Set the value shown on the left during adjustment, and
Pr121 9999
communication retries set a value from 1 to 10 during operation.

3. Others (which should be set if necessary)


The table below shows parameters to be considered when using various system configuration and inverters.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
For the method of use, refer to the respective inverter manual.
Parameter No. Parameter item Set value Setting contents
0 or 0.01 to 0: Frequency display, setting
Pr37 Speed display*1 9998 0.01 to 9998: Machine speed at 60Hz.
0 : The built-in frequency setting knob is valid. G
Frequency setting 1 : The built-in frequency setting knob is invalid.

(FX2N-232IF)
Communication
Non-Protocol
Pr146 0, 1, 9999
command selection*2 9999 : The built-in frequency setting knob is valid when
the frequency is set to "0 Hz" by the keys.
EEPROM write selection 0: EEPROM is written.
Pr342 0 or 1
(only in 400 V class) 1: RAM is written.

*1. This inverter communication function cannot read or write Pr37. H


Set Pr37 to "0" when setting or monitoring the frequency in the PLC.
Communication
Programming

If any value other than "0" is set to Pr37 and the instruction code HFF is set to "01", the frequency may
not be set or monitored normally (in the 400 V class).
(In the 200 V and 100 V classes, the frequency may not be set or monitored normally if any value
other than "0" is set to Pr37 without regard to the setting of the instruction code HFF.)
*2. When changing the frequency from the PLC, set "1" or "9999". I
Maintenance
Remote

Apx.A
models
Discontinued

E-53
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.3 E500 Series (When Connected to PU Port)

5.3.2 Parameter setting method (reference)


This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
When the cover is closed

When the cover is open

Display LED 4 digits Unit indicator


Displays the frequency, Operation status indication
parameter number, etc. The LEDs light and flash according
Setting key to the mode and operation status.
Sets each setting. UP/DOWN key
MODE key Change the set value of the
Changes over the mode. frequency and parameters.

The operating procedure example below shows a case in which the baud rate is set to 19200 bps.

1 Confirming the RUN indicator and the operation mode indicator


Confirm that the operation is stopped (that the RUN indicator is Off).

2 Selecting the parameter setting mode


Press the MODE key, and select the parameter setting mode.
Monitoring mode Frequency setting mode*1 Parameter setting mode

*1. The frequency setting mode is displayed only in the PU operation mode.

3 Reading the parameter (Pr. 118)


There are two methods to read the parameter number:
Method to read the parameter number using the UP and DOWN keys
Press the UP and DOWN keys, and display the parameter number to be read.

E-54
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.3 E500 Series (When Connected to PU Port)

A
Method to set each digit of the parameter number

Common Items
a) Press the SET key to flash the most significant digit. Set a numeric value using the UP and DOWN
keys.

N:N Network
b) Press the SET key to flash the middle digit. Set a numeric value using the UP and DOWN keys.

Parallel Link
c) Press the SET key to flash the least significant digit. Set a numeric value using the UP and DOWN
keys.
D

Computer Link
4 Setting the set value of Pr. 118 to "192" E

Communication
Inverter
("192" indicates the baud rate of 19200 bps.)
1. Press the SET key to read the currently set value. Change the set value using the UP and
DOWN keys.

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Press and hold the SET key for 1.5 seconds to set "192". G

(FX2N-232IF)
Communication
The set value and parameter number are displayed Non-Protocol
Press and hold it
for 1.5 sec.
alternately.
H
Communication
Programming

3. Press the SET key to display the next parameter.

I
The parameter number and set value are displayed
Maintenance
Remote

alternately

5 Change other parameters in the same way as step 3.


For details on parameters to be set, refer to Subsection 5.3.1.
Apx.A
models
Discontinued

E-55
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.4 V500, F500 and A500 Series (Connection to PU Port)

5.4 V500, F500 and A500 Series (Connection to PU Port)

5.4.1 Contents of parameter setting

1. Contents of communication setting (essential items)


The table below shows parameters which should be set in any case.
Parameter No. Parameter item Set value Setting contents
Pr117 Communication station number 00 to 31 Up to eight inverters can be connected.
48 4800 bps
Pr118 Communication speed 96 9600 bps
192 19200 bps (standard)
Pr119 Stop bit length/data length 10 Data length: 7-bit/Stop bit: 1-bit
Pr120 Parity check presence/absence 2 2: Even parity
Pr123 Waiting time setting 9999 Set in communication data
CRLF presence/absence
Pr124 1 CR: Provided, LF: Not provided
selection
External operation mode is selected when
Pr79 Operation mode selection 0
power is turned ON.
Pr122 Communication check time interval 9999 Communication check is stopped.

2. Parameters which should be adjusted between test operation and actual operation
Parameter No. Parameter item Set value Setting contents
Number of Set the value shown on the left during adjustment, and
Pr121 9999
communication retries set a value from 1 to 10 during operation.

3. Others (which should be set if necessary)


The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter No. Parameter item Set value Setting contents
0: EEPROM are written.
Pr342 EEPROM write selection 0 or 1
1: RAM is written.

E-56
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.4 V500, F500 and A500 Series (Connection to PU Port)

A
5.4.2 Parameter setting method (reference)

Common Items
This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.

N:N Network
Display LED4 digit
Displays the frequency,
parameter number, etc.
Operation status
indication
REV LED flashes during
reverse rotation. C
Mode key FWD LED flashes during

Parallel Link
Changes over the mode. forward rotation.

Set key UP.down key


Sets each setting. Change the set value of
the frequency and
parameters.
The operating procedure example below shows a case in which the baud rate is set to 19200 bps.
D

Computer Link
1 Confirming the RUN indicator and the operation mode indicator
Confirm that the operation is stopped (that both the REV and FWD indicators are Off).
E
2 Selecting the parameter setting mode

Communication
Inverter
Press the MODE key, and select the parameter setting mode.
Monitor mode Frequency setting mode*1 Parameter setting mode

(RS/RS2 Instruction)
Communication
Non-Protocol
*1. The frequency setting mode is displayed only during the PU operation mode.

3 Reading the parameter (Pr. 118) G

(FX2N-232IF)
Communication
Non-Protocol
There are two methods to read the parameter number:
Method to read the parameter number using the UP and DOWN keys
Press the UP and DOWN keys, and display the parameter number to be read.

H
Communication
Programming

Method to set each digit of the parameter number


a) Press the SET key to flash the most significant digit. Set a numeric value using the UP and DOWN I
keys.
Maintenance
Remote

Apx.A
models
Discontinued

E-57
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.4 V500, F500 and A500 Series (Connection to PU Port)

b) Press the SET key to flash the middle digit. Set a numeric value using the UP and DOWN keys.

c) Press the SET key to flash the least significant digit. Set a numeric value using the UP and DOWN
keys.

4 Setting the set value of Pr. 118 to "192"


("192" indicates the baud rate of 19200 bps.)
1. Press the SET key to read the currently set value. Change the set value using the UP and
DOWN keys.

2. Press and hold the SET key for 1.5 seconds to set "192".

Press and hold it


for 1.5 sec.
The set value and parameter number are displayed alternately.

3. Press the SET key to display the next parameter

The set value and parameter number are displayed alternately.

5 Changing other parameters in the same way as step 3


For details on the parameters to be set, refer to Subsection 5.4.1.

E-58
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.5 V500, F500 and A500 Series (Connection to FR-A5NR)

A
5.5 V500, F500 and A500 Series (Connection to FR-A5NR)

Common Items
5.5.1 Contents of parameter setting

1. Contents of communication setting (essential items)


B

N:N Network
The table below shows parameters which should be set in all cases.
Parameter No. Parameter item Set value Setting contents
Pr331 Communication station number 00 to 31 Up to eight inverters can be connected.
48 4800 bps
Pr332 Communication speed 96 9600 bps (standard) C

Parallel Link
192 19200 bps
Pr333 Stop bit / Data length 10 Data length: 7-bit/Stop bit: 1-bit
Pr334 Parity check presence/absence 2 2: Even parity
Pr337 Waiting time setting 9999 Set in communication data
Pr341 CR, LF presence/absence selection 1 CR: Provided, LF: Not provided D
External operation mode is selected when

Computer Link
Pr79 Operation mode selection 0
power is turned ON.
Pr340 Link startup mode selection 1 Computer link
Pr336 Communication check time interval 9999 Communication check is stopped.

2. Parameters which should be adjusted between test operation and actual operation E
Parameter No. Parameter item Set value Setting contents

Communication
Inverter
Number of communication Set the value shown on the left during adjustment,
Pr335 9999
retries and set a value from 1 to 10 during operation.

3. Others (which should be set if necessary)


The table below shows parameters to be considered when using various system configuration and inverters. F
For the method of use, refer to the respective inverter manual.

(RS/RS2 Instruction)
Communication
Non-Protocol
Parameter No. Parameter item Set value Setting contents
0: EEPROM is written.
Pr342 EEPROM write selection 0 or 1
1: RAM is written.
0: PLC
Pr338 Operation command right 0 or 1
1: Outside G

(FX2N-232IF)
Communication
Non-Protocol
0: PLC
Pr339 Speed command write 0 or 1
1: Outside

5.5.2 Parameter setting method (reference)


The parameter setting method is the same as that for the V500, F500 and A500 Series (connection to the PU port). H
For the parameter setting method, refer to Subsection 5.4.2.
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-59
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.6 E700, D700 Series (when PU port, FR-E7TR is connected)

5.6 E700, D700 Series (when PU port, FR-E7TR is connected)

5.6.1 Contents of parameter setting

1. Contents of communication setting (essential items)


The table below shows parameters which should be set in all cases.
Parameter No. Parameter item Set value Setting contents
Pr117 PU communication station number 00 to 31 Up to eight inverters can be connected.
48 4800 bps
96 9600 bps
Pr118 PU communication speed
192 19200 bps (standard)
384 38400 bps
Pr119 PU communication stop bit length 10 Data length: 7-bit/Stop bit: 1-bit
Pr120 PU communication parity check 2 2: Even parity
Pr123 PU communication waiting time setting 9999 Set in communication data
PU communication CR/LF presence/
Pr124 1 CR: Provided, LF: Not provided
absence selection
External operation mode is selected when
Pr79 Operation mode selection 0
power is turned ON.
Mitsubishi inverter (computer link
Pr549 Protocol selection 0
operation) protocol
1: Network operation mode
10: Network operation mode
Operation mode can be changed
Pr340 Communication startup mode selection 1 or 10
between the PU operation mode and
network operation mode from the
operation panel.

2. Parameters which should be adjusted between test operation and actual operation
Parameter No. Parameter item Set value Setting contents
Set the value shown on the left during
Pr121 Number of PU communication retries 9999 adjustment, and set a value from 1 to 10
during operation.
Set the value shown on the left during
adjustment, and set a proper value in
Pr122 PU communication check time interval 9999
accordance with the system specification
during operation.

Caution on setting the PU communication check time interval (Pr122)


Description Set value
During adjustment or when communication with the PLC is not executed periodically 9999
When communication with the PLC is not executed 0 (Initial Value)
Set the communication time in the following cases
When it is necessary to monitor absence of communication for a certain time and stop
the inverter in such a case while communication with the PLC is being executed 0.1 to 999.8 sec
When it is necessary to stop the motor at the point which the PLC mode is changed
from RUN to STOP

E-60
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.6 E700, D700 Series (when PU port, FR-E7TR is connected)

A
3. Others (which should be set if necessary)

Common Items
The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter No. Parameter item Set value Setting contents
0 or 0.01 0: Frequency display, setting
Pr37 Speed display*1 to 9998 0.01 to 9998: Machine speed at 60Hz. B

N:N Network
0: Built-in frequency setting potentiometer
valid
Pr146 Built-in potentiometer switching*2 0 or 1
1: Built-in frequency setting potentiometer
invalid
0: EEPROM is written.
Pr342 Communication EEPROM write selection 0 or 1
1: RAM is written. C

Parallel Link
*1. This inverter communication function cannot read or write Pr37.
Set Pr37 to "0" when setting or monitoring the frequency in the PLC.
If any value other than "0" is set to Pr37 and the instruction code HFF is set to "01", the frequency may
not be set or monitored normally.
*2. Set Pr146 to "1" when changing the frequency from the PLC.
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-61
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.6 E700, D700 Series (when PU port, FR-E7TR is connected)

5.6.2 Parameter setting method (reference)


This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
Operating status display
Monitor Lit or flicker during inverter operation
(4-digit LED)
Show the frequency,
parameter number, etc.
Setting dial
Used to change
the frequency setting
and parameter values. SET key
Determines each setting
MODE key
Used to change each setting mode
The operating procedure example below shows a case in which the baud rate is set to 19200 bps.

1 Confirming the RUN indicator and the operation mode indicator


Confirm that the operation is stopped (that the RUN indicator is off).

2 Selecting the parameter setting mode


Press the MODE key, and select the parameter setting mode.
Monitor/frequency
setting mode Parameter setting mode

The previously read parameter


is displayed.

3 Setting the parameter Pr. 160 to "0"


(This step is not required if Pr. 160 is already set to "0".)
1. Turn the setting dial until "Pr. 160" is displayed.

2. Press the SET key to read the current set value.

3. Turn the setting dial, and change the set value to "0".

E-62
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.6 E700, D700 Series (when PU port, FR-E7TR is connected)

A
Press the SET key to determine the set value.

Common Items
The set value and parameter number are displayed alternately. B
The set value and parameter number are displayed alternately, and the setting is completed.

N:N Network
4 Setting the parameter Pr. 118 to "192"
("192" indicates the baud rate of 19200 bps.)
Turn the setting dial until "Pr. 118" is displayed. C

Parallel Link
Press the SET key to read the current set value.
D

Computer Link
Turn the setting dial, and change the set value to "192". E

Communication
Inverter
F
Press the SET key to determine the set value.

(RS/RS2 Instruction)
Communication
Non-Protocol
The set value and parameter number are displayed alternately.
G

(FX2N-232IF)
Communication
Non-Protocol
The set value and parameter number are displayed alternately, and the setting is completed.

5 Changing other parameters in the same way as step 4


For details on the parameters to be set, refer to Subsection 5.6.1. H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-63
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)

5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)

5.7.1 Contents of parameter setting

1. Contents of communication setting (essential items)


The table below shows parameters which should be set in all cases.
Parameter No. Parameter item Set value Setting contents
Pr331 RS-485 communication station 00 to 31 Up to eight inverters can be connected.
48 4800 bps
96 9600 bps (standard)
Pr332 RS-485 communication speed
192 19200 bps
384 38400 bps
Pr333 RS-485 communication stop bit length 10 Data length: 7-bit/Stop bit: 1-bit
RS-485 communication parity check
Pr334 2 2: Even parity
selection
Pr337 RS-485 communication waiting time setting 9999 Set in communication data
Pr341 RS-485 communication CR/LF selection 1 CR: Provided, LF: Not provided
External operation mode is selected when
Pr79 Operation mode selection 0
power is turned ON.
Pr340 Communication startup mode selection 1 Computer link
Pr336 RS-485 communication check time interval 9999 Communication check is stopped.
Pr549 Protocol selection 0 Mitsubishi inverter (computer link) protocol

2. Parameters which should be adjusted between test operation and actual operation
Parameter No. Parameter item Set value Setting contents
RS-485 communication number Set the value shown on the left during adjustment, and
Pr335 9999
of retries set a value from 1 to 10 during operation.

3. Others (which should be set if necessary)


The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter No. Parameter item Set value Setting contents
0: EEPROM is written.
Pr342 Communication EEPROM write selection 0 or 1
1: RAM is written.
0: PLC
Pr338 Communication operation command source 0 or 1
1: Outside
0: PLC
Pr339 Communication operation command source 0 or 1
1: Outside

E-64
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)

A
5.7.2 Parameter setting method (reference)

Common Items
This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.

Monitor (4-digit LED)


Operation mode indicator B
NET: Lit to indicate network

N:N Network
shows the frequency, operation mode
parameter number, etc. Rotation direction indicator
FWD: Lit during forward rotation
REV: Lit during reverse rotation
Setting dial
Used to change the
MODE key
Changes over the mode.
C
frequency setting and

Parallel Link
parameter values.

SET key
Sets each setting.

The operating procedure example below shows a case in which the baud rate is set to 19200 bps. D
1

Computer Link
Confirming the RUN indicator and the operation mode indicator
Confirm that the operation is stopped (that the RUN indicator is off).

2 Selecting the parameter setting mode E

Communication
Inverter
Press the MODE key, and select the parameter setting mode.
Monitor/frequency
setting mode Parameter setting mode

The previously read parameter


is displayed.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
3 Setting the parameter Pr. 160 to "0"
(This step is not required if Pr. 160 is already set to "0".)
1. Turn the setting dial until "Pr. 160" is displayed. G

(FX2N-232IF)
Communication
Non-Protocol

2. Press the SET key to read the current set value. H


Communication
Programming

3. Turn the setting dial, and change the set value to "0". I
Maintenance
Remote

Apx.A
models
Discontinued

E-65
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)

Press the SET key to determine the set value.

The set value and parameter number are displayed alternately.

The set value and parameter number are displayed alternately, and the setting is completed.

4 Setting the parameter Pr. 332 to "192"


("192" indicates the baud rate of 19200 bps.)
Turn the setting dial until "Pr. 332" is displayed.

Press the SET key to read the current set value.

Turn the setting dial, and change the set value to "192".

Press the SET key to determine the set value.

The set value and parameter number are displayed alternately.

The set value and parameter number are displayed alternately, and the setting is completed.

5 Change other parameters in the same way as step 4


For details on the parameters to be set, refer to Subsection 5.7.1.

E-66
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)

A
5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)

Common Items
5.8.1 Contents of parameter setting

1. Contents of communication setting (essential items)


B

N:N Network
The table below shows parameters which should be set in all cases.
Parameter Parameter
Parameter item Set value Setting contents
No. group
Pr331 N030 RS-485 communication station 00 to 31 Up to eight inverters can be connected.
48 4800 bps C
96 9600 bps (standard)

Parallel Link
Pr332 N031 RS-485 communication speed
192 19200 bps
384 38400 bps
RS-485 communication stop bit length/
10 Data length: 7-bit/Stop bit: 1-bit
data length
Pr333
N032 RS-485 communication data length 1 Data length: 7 bits
D

Computer Link
N033 RS-485 communication stop bit length 0 Stop bit: 1 bit
RS-485 communication parity check
Pr334 N034 2 2: Even parity
selection
RS-485 communication waiting time
Pr337 N037 9999 Set in communication data

Pr341 N038
setting
RS-485 communication CR/LF selection 1 CR: Provided, LF: Not provided
E

Communication
Inverter
External operation mode is selected
Pr79 D000 Operation mode selection 0
when power is turned ON.
Pr340 D001 Communication startup mode selection 1 Computer link
Mitsubishi inverter (computer link)
Pr549 N000 Protocol selection 0
protocol F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Parameters which should be adjusted between test operation and actual operation
Parameter Parameter
Parameter item Set value Setting contents
No. group
Set the value shown on the left during
RS-485 communication number of
Pr335 N035
retries
9999 adjustment, and set a value from 1 to
10 during operation.
G

(FX2N-232IF)
Communication
Non-Protocol
Set the value shown on the left during
RS-485 communication check time adjustment, and set a value in
Pr336 N036 9999
interval accordance with the system
specification during operation.

3. Others (which should be set if necessary) H


The table below shows parameters to be considered when using various system configuration and inverters.
Communication
Programming

For the method of use, refer to the respective inverter manual.


Parameter Parameter
Parameter item Set value Setting contents
No. group
Communication EEPROM write 0: Write to EEPROM and RAM.
Pr342 N001
selection
0 or 1
1: Write to RAM only. I
Maintenance
Remote

Communication operation command 0: PLC


Pr338 D010 0 or 1
source 1: Outside
Communication operation command 0: PLC
Pr339 D011 0 or 1
source 1: Outside

Apx.A
models
Discontinued

E-67
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)

5.8.2 Parameter setting method (reference)


This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.

Hz
Monitor (5-digit LED)
shows the frequency,
Operation mode indicator PU MON IM parameter number, etc.
NET : Lit to indicate network EXT PRM PM
NET P.RUN
operation mode
Rotation direction key
MODE key MODE SET ESC FWD
Changes over the mode. FWD: Lit during forward rotation
REV : Lit during reverse rotation
REV
SET key
Sets each setting. PU Setting dial
EXT STOP
RESET Used to change the frequency
setting and parameter values.
FR-DU08

The operating procedure example below shows a case in which the baud rate is set to 19200 bps.

1 Confirming the RUN indicator and the operation mode indicator


Confirm that the operation is stopped (that the P.RUN indicator is off).

2 Selecting the parameter setting mode


Press the MODE key, and select the parameter setting mode.
Monitor/frequency
setting mode Parameter setting mode

The previously read parameter


is displayed.
MODE

3 Setting the parameter Pr. 160 to "0"


(This step is not required if Pr. 160 is already set to "0".)
1. Turn the setting dial until "Pr. 160" is displayed.

2. Press the SET key to read the current set value.

SET

3. Turn the setting dial, and change the set value to "0".

E-68
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in Inverter
Inverter Communication 5.9 Cautions on Setting

A
Press the SET key to determine the set value.

Common Items
SET
The set value and parameter number are displayed alternately. B
The set value and parameter number are displayed alternately, and the setting is completed.

N:N Network
4 Setting the parameter Pr. 332 to "192"
("192" indicates the baud rate of 19200 bps.)
Turn the setting dial until "Pr. 332" is displayed. C

Parallel Link
Press the SET key to read the current set value.
D

Computer Link
SET

Turn the setting dial, and change the set value to "192". E

Communication
Inverter
F
Press the SET key to determine the set value.

(RS/RS2 Instruction)
Communication
Non-Protocol
SET

The set value and parameter number are displayed alternately. G

(FX2N-232IF)
Communication
Non-Protocol
The set value and parameter number are displayed alternately, and the setting is completed.

5 Change other parameters in the same way as step 4


For details on the parameters to be set, refer to Subsection 5.8.1. H
Communication
Programming

5.9 Cautions on Setting

1. Setting of the "communication check time interval" and "RS-485 communication check time
interval" I
Maintenance
Remote

Description Set value


During adjustment or when communication with the PLC is not executed periodically Value shown in table
When communication with the PLC is not executed 0
Set the communication time in the following cases:
When it is necessary to monitor the absence of communication for a certain time and stop
the inverter in such a case while communication with the PLC is being executed 0.1 to 999.8 sec
Apx.A
models
Discontinued

When it is necessary to stop the motor at the point which the PLC mode is changed from
RUN to STOP

E-69
FX Series PLC User's Manual - Data Communication Edition 6 Communication Setting in FX Programmable Controller
Inverter Communication 6.1 Parameter Assigning Method

6. Communication Setting in FX Programmable Controller


This chapter explains the communication setting method for inverter communication.
Set non-protocol communication for inverter communication.

6.1 Parameter Assigning Method


Use parameters for communication setting in the FX PLC.

1. Parameter assigning method


Register the communication setting in the sequence programming software parameters, and transfer the
parameters to the PLC.

2. Setting flow

Transferred
PLC memory when
power is Inverter communication using
Setting window turned ON ch1
Parameter area
D8120 Communication format
Parameter
method
Program area

In FX3G, FX3GC, FX3U and FX3UC


Inverter communication using
ch2
D8420 Communication format

E-70
FX Series PLC User's Manual - Data Communication Edition 6 Communication Setting in FX Programmable Controller
Inverter Communication 6.2 Communication Setting Using Parameter Method (GX Works2)

A
6.2 Communication Setting Using Parameter Method (GX Works2)

Common Items
Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 6.3. B
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

N:N Network
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

6.2.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that GX Works2 is already
started up.
C

Parallel Link
1 Opening the parameter setting window
In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar.
D

Computer Link
E

Communication
Inverter
F
2 Setting the serial communication (parameters)

(RS/RS2 Instruction)
Communication
Non-Protocol
Click the [PLC System(2)] tab in the FX Parameter window.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-71
FX Series PLC User's Manual - Data Communication Edition 6 Communication Setting in FX Programmable Controller
Inverter Communication 6.2 Communication Setting Using Parameter Method (GX Works2)

3 Setting the serial communication (parameters)


Set the parameters as shown below:

[1]
[2]
[3] [5]

[4]

[1] Set the channel to be used. (This parameter can be set only in the FX3G, FX3GC, FX3U and
FX3UC PLCs.)
[2] Check the "Operate Communication Setting" box.
[3] Set "Protocol" to "Non-procedural", "Data Length" to "7Bit", "Parity" to "Even", and "Stop Bit" to
"1Bit".

[4] Set "Transmission Speed" to either "4800", "9600", "19200" or "38400*1", and make sure that
the set value here is the same as the set value in the inverters.
[5] Ignore these items.
*1. This transmission speed is supported only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCS.

Click [End].

4 Writing parameters and program to the PLC


Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
[Execute].

E-72
FX Series PLC User's Manual - Data Communication Edition 6 Communication Setting in FX Programmable Controller
Inverter Communication 6.3 Communication Setting Using Parameter Method (FXGP/WIN)

A
6.3 Communication Setting Using Parameter Method (FXGP/WIN)

Common Items
Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with FXGP/WIN. Ch2 cannot be set using FXGP/WIN.
For details on GX Works2 operating procedure, refer to section 6.2. B
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

N:N Network
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

6.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already
started up.
C

Parallel Link
1 Displaying serial setting (parameter)
Select [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of parameter setting.
D
1. When there are no parameter settings

Computer Link
There are no communication settings. Click the [Yes] button.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-73
FX Series PLC User's Manual - Data Communication Edition 6 Communication Setting in FX Programmable Controller
Inverter Communication 6.3 Communication Setting Using Parameter Method (FXGP/WIN)

2. When there are already parameter settings


The existing communication setting contents are displayed.

2 Adjusting serial setting (parameter)


Execute the communication setting as shown below.

[1]

[2]
[3]

[1] Set "Protocol" to "RS instruction", "Data bits" to "7", "Parity" to "Even", and "Stop bits" to "1".
[2] Set "Transfer speed [bps]" to either "4800", "9600" or "19200", and make sure that the set value
here is the same as the set value in the inverters.
[3] Ignore these items.

3 Writing a sequence program (parameters) to the PLC


Select [PLC] [Transfers] [Write] from the toolbar, and click [OK] button.

E-74
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.1 Checking Contents of Related Devices

Common Items
7. Creating Programs (FX2N, FX2NC)
This chapter explains how to create programs which change inverter parameters and give operation B
commands to inverters.

N:N Network
As explanation, a program example is shown for each applied instruction.

7.1 Checking Contents of Related Devices


The tables below show the devices used in inverter communication in FX2N and FX2NC PLCs.
C

Parallel Link
1. Bit devices
Device No. Name Description R/W
Turns ON when execution of EXTR instruction is completed, and remains
Instruction execution ON for 1 scan.
M8029
complete Turns ON also when execution of instruction is completed if M8156
R D
(communication error or parameter error) turns ON.

Computer Link
Extension ROM
M8104 Remains ON while an extension ROM cassette is attached. R
cassette check
M8154 Unused R
Communication port
M8155
busy
Remains ON while the communication port is used by an EXTR instruction. R E

Communication
Inverter
Communication error
M8156 Turns ON when a communication error is caused by an EXTR instruction. R
or parameter error
Communication error
M8157 Turns ON when a communication error occurs. R
latch*1

R: Read only (used as a contact in program) F


*1. Cleared when the PLC mode is changed from STOP to RUN.

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Word devices
Device No. Name Description R/W
Extension ROM
D8104
cassette type code
Stores the extension ROM cassette type code (value: K1). R G

(FX2N-232IF)
Communication
Non-Protocol
Extension ROM Stores the extension ROM cassette version.
D8105 R
cassette version (value: K100 = Ver. 1.00).
Inverter response
D8154 Sets the inverter response waiting time. R/W
waiting time
Step number of
D8155 instruction using
Stores the step number of the EXTR instruction using the communication
port.
R H
communication port
Communication
Programming

Stores an error code when a communication error is caused by an EXTR


D8156 Error code*1 instruction.
R

Error occurrence Stores the instruction step number in which a communication error has
D8157 R
step number latch*1 occurred. (Stores K-1 when no error has occurred.)
I
R: Read only
Maintenance
Remote

W: Write only
R/W: Read or Write
*1. Cleared when the PLC mode is changed from STOP to RUN.

Apx.A
models
Discontinued

E-75
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.2 Common Items in Inverter Communication Instructions

7.2 Common Items in Inverter Communication Instructions

7.2.1 Inverter communication types (EXTR K10 to K13)


An FX2N and FX2NC PLC and inverter execute communication using EXTR (FNC180) instruction.
EXTR instruction can be described in four types of methods, from "EXTR K10" to "EXTR K13", depending on
the data communication direction and parameter writing/reading direction.
S S1 S2 S3
FNC180 Function Inverter station Inverter Read/
EXTR number number instruction code Write

Only EXTR (16-bit type) is applicable. Read value storage


DEXTR (32-bit type), EXTRP (pulse type) destination or value written
and DEXTRP (32-bit pulse type) are not to inverter
applicable.

Function Detailed
Instruction Function Control direction
number (S) explanation
K10 Monitors inverter operations PLC inverter 7.3
K11 Controls inverter operations PLC inverter 7.4
EXTR(FNC180)
K12 Reads inverter parameters PLC inverter 7.5
K13 Writes inverter parameters PLC inverter 7.6

7.2.2 Function and operation

1. Communication start timing


At the rising edge (OFFON) of the drive condition, the PLC starts communication with an inverter.
Even if the drive condition turns OFF during communication with an inverter, the PLC executes
communication until the end.
When the drive condition is always ON, the PLC executes communication repeatedly.

2. Simultaneous driving of EXTR instructions and communication processing


1) Driving instructions at the same time
- Two or more EXTR functions (K10 to K13) can be programmed, and driven at the same time.
- When two or more instructions are driven at the same time during communication, the next EXTR
instruction in the program is executed after the current communication with an inverter is finished.
M8000
FNC180 (1)
EXTR
RUN M8155
monitor ONOFF

FNC180 M8155
(2) ONOFF
EXTR
M8155
ONOFF

FNC180 (3)
EXTR

E-76
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.2 Common Items in Inverter Communication Instructions

A
- The PLC waits for 15 ms after acquiring the communication port, and then starts communication using

Common Items
EXTR instructions. Even if the drive condition turns ON, the PLC does not start execution of the EXTR
instruction until the communication port busy flag M8155 turns OFF from ON if M8155 was set to ON by
another EXTR instruction.
The PLC frees the communication port, and then executes EXTR instructions driven in the next step and
so on.
B
M0

N:N Network
FNC180 ......[1]
EXTR

M1
FNC180 ......[2]
EXTR
C

Parallel Link
M0
*1 *2
EXTR
instruction [1]
(Communicating) D

Computer Link
15ms 15ms 15ms

M1
*2
EXTR
instruction [2] E
(Communicating)

Communication
Inverter
15ms 15ms
EXTR EXTR EXTR EXTR EXTR
M8155 instruction [1] instruction [2] instruction [1] instruction [2] instruction [1]

*1.
*3
The PLC does not execute the instruction even if M8155 is turned OFF because the drive contact is
*3
F

(RS/RS2 Instruction)
Communication
Non-Protocol
OFF.
*2. When two or more instructions are driven at the same time during communication, the next EXTR
instruction is executed after the current instruction is completed.
*3. M8155 remains OFF until the next EXTR instruction is driven after execution of the current EXTR
instruction is completed. G
2) Cautions on programming

(FX2N-232IF)
Communication
Non-Protocol
When the drive contact for another EXTR instruction is driven by a pulse signal during communication
with an inverter, the communication is not executed.
When communicating with inverters for two or more items, let the drive contact for the EXTR instruction
remain ON until sending is completed. After communication with all inverters is completed, set the drive
contact to OFF using the instruction execution complete flag M8029. H
Communication
Programming

X001
SET M0 Command is latched

M0 FNC180 Communication is

EXTR executed

M8029 I
RST M0 Command is reset
Maintenance
Remote

Instruction execution
complete

3. Communication complete flag (M8029)


When communication with an inverter is completed, the instruction execution complete flag M8029 turns ON,
and remains ON for 1 scan.
Apx.A
models
Discontinued

For details on using M8029 method, refer to program examples shown below.

E-77
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.2 Common Items in Inverter Communication Instructions

7.2.3 Instruction completion and error flag operation


When two or more EXTR instructions are programmed, the following flags turn ON or OFF according to the
execution result of each EXTR instruction.
For acquiring the result of each EXTR instruction, make sure to provide these flags just below each EXTR
instruction.
Device number Description
M8029 Instruction execution complete
M8156 Communication error or parameter error
D8156 Error code

1. Operation of M8029 (instruction execution complete flag)


M8029 (instruction execution complete flag) operates as shown below.
In the program below, M0 and M2 turn OFF and M1 turn ON when communication is completed.
Operation of
[1] EXTR instruction is not driven. instruction execution
M0 (OFF) complete flag
FNC180 M8029 : OFF
EXTR

[2] EXTR instruction is driven.


M1 (ON)
FNC180 M8029 : ON
EXTR

[3] EXTR instruction is not driven.


M2 (OFF)
FNC180 M8029 : OFF
EXTR

2. Operations of M8156 (error flag) and D8156 (error code)


M8156 (error flag) and D8156 (error code) operate as shown below.
In the program below, a communication error occurs in [1] and [3], and communication is completed normally
in [2].
Operation of Error code
[1] Communication error (no response from inverter) communication status
M8000 error flag
FNC180 D8156: K1
M8156 : ON Error code is
EXTR
RUN stored
monitor
[2] Normal communication
FNC180 D8156: K1
M8156 : OFF Error code is not
EXTR
changed

[3] Communication error (data range error)


FNC180 D8156: K268
M8156 : ON Error code is
EXTR
stored

E-78
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.2 Common Items in Inverter Communication Instructions

A
3. Program examples

Common Items
X000
SET M0
Start command
M0
FNC180
EXTR
B

N:N Network
M8156
SET M50 M50
Communication error Error in the 1st
M8029 instruction
FNC 12 D8156 D50 D50
MOV
Instruction
execution C
complete

Parallel Link
RST M0

X001

Start command
SET M1 D

Computer Link
M1
FNC180
EXTR

M8156
SET M51 M51
Communication error Error in the 2nd
instruction
E
M8029
FNC 12

Communication
Inverter
D8156 D51 D51
MOV
Instruction
execution
complete
RST M1

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-79
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.2 Common Items in Inverter Communication Instructions

7.2.4 Cautions on programming

1. Using the EXTR instruction together with another instruction


The EXTR instruction cannot be used together with the RS instruction.
The EXTR instruction cannot be used together with a EXTR K0 instruction.

2. When programming the EXTR instruction in a state of a STL instruction


Make sure to let the state relay remain ON until communication with an inverter is completed. If the state relay
is set to OFF during communication, the EXTR instruction is stopped in the middle of execution, and another
EXTR instruction cannot be started. Program a sequence while observing the following cautions
Add M8029 (instruction execution complete flag) ON condition to the state relay transfer condition, and
provide such an interlock that the state relay ON/OFF status does not change during communication with
an inverter.
If the state changes during communication, communication may not be performed normally.
When resetting many state relays all at once using ZRST (FNC 40) instruction, etc., make sure that the
M8155 (communication port busy) OFF condition is established.
X000
SET M0
Reset input
M0 M8155 FNC 40 S0 S999 State relays S0 to S999
Communication ZRST are reset all at once.
port busy
RST M0

3. Using the EXTR instruction in a program flow


The EXTR instruction cannot be used in the following program flows
Program flow disabling the EXTR instruction Remarks
Between CJ and P instructions Conditional jump
Between FOR and NEXT instructions Repeat
Between P and SRET instructions Subroutine
Between I and IRET instructions Interrupt routine

4. Caution on write during RUN


1) Condition in which the EXTR instruction can be written
While the PLC is in the STOP status, the EXTR instruction can be written during RUN.
2) Condition in which the EXTR instruction cannot be written
The EXTR instruction cannot be written during RUN.
If the EXTR instruction is written during RUN while communication or if the EXTR instruction is deleted in
RUN mode, communication may be disabled after that. (In such a case, set the PLC to STOP, and then to
RUN mode again to initialize the status.)

5. When using the E500 Series


Parameters Nos. 922 and 923 in the E500 Series cannot be used in inverter communication.

E-80
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.3 Inverter Operation Monitoring Instruction (PLCInverter) [EXTR K10]

A
7.3 Inverter Operation Monitoring Instruction (PLCInverter) [EXTR K10]

Common Items
EXTR K10 instruction reads the operation status of an inverter to the PLC.

7.3.1 Function and operation


B
When an "instruction code" specified for computer link operation in inverters is specified in EXTR instruction,

N:N Network
a value in the inverter is read to D .

1. Applicable devices
Bit device Word device Others
Operand System/ C
System/User Digit specification Index Constant Pointer
type User

Parallel Link
X Y M T C S KnX KnY KnM KnS T C D V Z Modification K H P
S
S1
S2 D

Computer Link
D

2. Program example
S S1 S2 D
M0
FNC180 K10 K6 H6F D100 E
EXTR

Communication
Inverter
Command
contact
Function number: K10 Read value storage destination
Inverter station number: 0 to 31 Inverter instruction code (hexadecimal)

7.3.2 Inverter instruction codes F

(RS/RS2 Instruction)
Communication
Non-Protocol
The table below shows inverter instruction codes which can be specified in S2 .
For the instruction codes, refer to the pages explaining computer link in detail in each inverter manual.
S2 Applicable inverter
Read contents
Inverter instruction
code (hexadecimal)
A500 E500 S500 G

(FX2N-232IF)
Communication
Non-Protocol
H7B Operation mode
H6F Output frequency [speed]
H70 Output current
H71 Output voltage
H72 Special monitor H
H73 Special monitor selection No.
Communication
Programming

H74 Alarm definition


H75 Alarm definition
H76 Alarm definition
H77
H7A
Alarm definition
Inverter status monitor






I
Maintenance
Remote

H6E Set frequency read (E2PROM)


H6D Set frequency read (RAM)
H7F Link parameter expansion setting These codes cannot be specified in S2 in
EXTR K10 instruction.
H6C Second parameter changing
They are automatically processed when a Apx.A
"second parameter specification code" is
models
Discontinued

specified in EXTR K12 instruction.

E-81
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.4 Inverter Operation Control Instruction (PLCInverter) [EXTR K11]

7.4 Inverter Operation Control Instruction (PLCInverter) [EXTR K11]


This instruction writes a control value required to operate an inverter from the PLC to the inverter.

7.4.1 Function and operation


When an "instruction code" specified for computer link operation in inverters is specified in EXTR instruction,
a value specified in S3 is written to the specified item in the inverter.

1. Applicable devices
Bit device Word device Others
Operand System/
System/User Digit specification Index Constant Pointer
type User
X Y M T C S KnX KnY KnM KnS T C D V Z Modification K H P
S
S1
S2
S3

2. Program example
S S1 S2 S3
M0
FNC180 K11 K6 HFA K2M50
EXTR
Command
contact
Function number: K11 Value written to inverter
Inverter station number: 0 to 31 Inverter instruction code (hexadecimal)

7.4.2 Inverter instruction codes

The table below shows inverter instruction codes which can be specified in S2 .
For the instruction codes, refer to the pages explaining computer link in detail in each inverter manual.
S2 Applicable inverter
Inverter instruction Read contents
A500 E500 S500
code (hexadecimal)
HFB Operation mode
HF3 Special monitor selection No.
HFA Run command
HEE Set frequency write (EEPROM)
HED Set frequency write (RAM)
HFD*1 Inverter reset
HF4 Alarm definition batch clear
HFC Parameter all clear
HFC User clear

*1. The instruction code "HFD (inverter reset)" does not request response from the inverter. Accordingly,
even if inverter reset is executed to a station number in which an inverter is not connected, error does
not occur.
It takes about 2.2 seconds to complete execution of inverter reset.

E-82
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.5 Inverter Parameter Reading Instruction (PLCInverter) [EXTR K12]

A
7.5 Inverter Parameter Reading Instruction (PLCInverter) [EXTR K12]

Common Items
This instruction reads a parameter of an inverter to the PLC.

7.5.1 Function and operation


B
When a parameter number of an inverter is specified in EXTR instruction, the value of the parameter in the

N:N Network
inverter is read to D .

1. Applicable devices
Bit device Word device Others
Operand System/ C
System/User Digit specification Index Constant Pointer
type User

Parallel Link
X Y M T C S KnX KnY KnM KnS T C D V Z Modification K H P
S
S1
S2 D

Computer Link
D

2. Program example
S S1 S2 D
M0
FNC180 K12 K6 K7 D150 E
EXTR

Communication
Inverter
Command
contact
Function number: K12 Read value storage destination
Inverter station number: 0 to 31 Inverter parameter number (decimal)

7.5.2 Inverter parameter number F

(RS/RS2 Instruction)
Communication
Non-Protocol
Refer to related data shown later.

7.5.3 Program example of "second parameter specification code"


In the program example shown below, the parameter number 201 (frequency: 201, time: 1201, motor rotation G
direction: 2201) is read from the A500 inverter whose station number is 6.

(FX2N-232IF)
Communication
Non-Protocol
Read devices: D100 = Motor rotation direction, D101 = Frequency, D102 = Time
X001
SET M0
Read
command
S S1 S2 S3 H
M0
Communication
Programming

FNC180 K12 K6 K2201 D100 Motor rotation directionD100


EXTR
Drive
contact
Function number Read value storage destination
Inverter station number: Inverter parameter number (decimal)
0 to 31 I
FNC180 FrequencyD101
Maintenance
Remote

K12 K6 K201 D101


EXTR

FNC180 TimeD102
K12 K6 K1201 D102
EXTR
The unit is specified by Pr. 200.
M8029 Apx.A
RST M0
models
Discontinued

Execution complete flag

E-83
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.6 Inverter Parameter Writing Instruction (PLCInverter) [EXTR K13]

7.6 Inverter Parameter Writing Instruction (PLCInverter) [EXTR K13]


This instruction writes a value from the PLC to a parameter in an inverter.

7.6.1 Function and operation

When a parameter number in an inverter is specified in EXTR instruction, the value of S3 is written to the
specified item in the inverter.

1. Applicable devices
Bit device Word device Others
Operand System/
System/User Digit specification Index Constant Pointer
type User
X Y M T C S KnX KnY KnM KnS T C D V Z Modification K H P
S
S1
S2
S3

2. Program example
S S1 S2 S3
M0
FNC180 K13 K6 K7 D160
EXTR
Command
contact
Function number: K13 Value written to inverter
Inverter station number: 0 to 31 Inverter parameter number (decimal)

7.6.2 Inverter parameter number


Refer to related data shown later.

7.6.3 Program example of "second parameter specification code"


In the program example shown below, data is written from the PLC to parameter number 201 (frequency:
201, time: 1201, motor rotation direction: 2201) in the A500 inverter.
X001
SET M0
Write
command
S S1 S2 S3
M0
FNC180 K13 K6 K2201 H1 Motor rotation direction: Forward
EXTR
Drive
contact Function
number: K13 Value written to inverter
Inverter station number: Inverter parameter number (decimal)
0 to 31
FNC180 K13 K6 K201 H14 Frequency: 20Hz
EXTR

FNC180 Time: 1:00


K13 K6 K1201 H100
EXTR
The unit is specified by Pr. 200.
M8029
RST M0
Execution complete flag

E-84
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.7 Second Parameter Specification Codes

A
7.7 Second Parameter Specification Codes

Common Items
When handling the following parameters in computer link operation, it is necessary to select second
parameters.
In EXTR K12 and EXTR K13 instructions, when a value shown in the tables below is set to S2 , the
extension parameter and second parameter are automatically overwritten, and the parameter values are then B
read or written.

N:N Network
7.7.1 S500 Series

1. Second parameter specification codes for parameter numbers C2 to C7


C
Second parameter specification code

Parallel Link
Parameter
Name [Value to be specified in S2 in EXTR instruction for
No.
parameter No. (decimal)]
C2 Frequency setting voltage bias frequency 902
C3 Frequency setting voltage bias 1902
C4 Frequency setting voltage gain 903 D

Computer Link
C5 Frequency setting current bias frequency 904
C6 Frequency setting current bias 1904
C7 Frequency setting current gain 905

7.7.2 E500 Series E

Communication
Inverter
1. Second parameter specification codes for parameter numbers 902 to 905
Second parameter specification code
[Value to be specified in S2 in EXTR instruction for
Parameter
No.
Name
Offset/Gain
parameter No. (decimal)]
Analog Terminal analog
F

(RS/RS2 Instruction)
Communication
Non-Protocol
(H00) (H01) value (H02)
902 Frequency setting voltage bias 902 1902 2902
903 Frequency setting voltage gain 903 1903 2903
904 Frequency setting current bias 904 1904 2904
905 Frequency setting current gain 905 1905 2905 G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-85
FX Series PLC User's Manual - Data Communication Edition 7 Creating Programs (FX2N, FX2NC)
Inverter Communication 7.7 Second Parameter Specification Codes

7.7.3 A500 Series

1. Second parameter specification codes for parameter numbers 201 to 230


Second parameter specification code
[Value to be specified in S2 in EXTR instruction for
Parameter
Name parameter No. (decimal)]
No.
Operation frequency Rotation direction
Time read/write
read/write write/read
201 Program set 1 201 1201 2201
202 Program set 1 202 1202 2202
203 Program set 1 203 1203 2203
204 Program set 1 204 1204 2204
205 Program set 1 205 1205 2205
206 Program set 1 206 1206 2206
207 Program set 1 207 1207 2207
208 Program set 1 208 1208 2208
209 Program set 1 209 1209 2209
210 Program set 1 210 1210 2210
211 Program set 2 211 1211 2211
212 Program set 2 212 1212 2212
213 Program set 2 213 1213 2213
214 Program set 2 214 1214 2214
215 Program set 2 215 1215 2215
216 Program set 2 216 1216 2216
217 Program set 2 217 1217 2217
218 Program set 2 218 1218 2218
219 Program set 2 219 1219 2219
220 Program set 2 220 1220 2220
221 Program set 3 221 1221 2221
222 Program set 3 222 1222 2222
223 Program set 3 223 1223 2223
224 Program set 3 224 1224 2224
225 Program set 3 225 1225 2225
226 Program set 3 226 1226 2226
227 Program set 3 227 1227 2227
228 Program set 3 228 1228 2228
229 Program set 3 229 1229 2229
230 Program set 3 230 1230 2230

2. Second parameter specification codes for parameter numbers 902 to 905


Second parameter specification code
[Value to be specified in S2 in EXTR instruction for
Parameter
Name parameter No. (decimal)]
No.
Offset/Gain Analog Terminal analog
(H00) (H01) value (H02)
902 Frequency setting voltage bias 902 1902 2902
903 Frequency setting voltage gain 903 1903 2903
904 Frequency setting current bias 904 1904 2904
905 Frequency setting current gain 905 1905 2905

E-86
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.1 Practical Example 1

Common Items
8. Practical Program Examples (FX2N, FX2NC)
This chapter explains practical programs for inverter communication. B

N:N Network
8.1 Practical Example 1
This fundamental program example monitors operations of an inverter, controls operations of an inverter and
writes parameters to an inverter.
C

Parallel Link
8.1.1 System configuration example
An FX PLC is connected to an inverter.
FX2N, FX2NC Inverter
D

Computer Link
System memory

Terminal resistor
Distributor
E

Communication
Inverter
8.1.2 Contents of operation
As an example of operation control, an inverter can be stopped (X000), rotated forward (X001) and rotated
reverse (X002).
By changing the contents of D10, the speed can be changed.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
The contents of D10 can be changed from a sequence program or display unit.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-87
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.1 Practical Example 1

8.1.3 Program example

1. Writing parameters to an inverter while the PLC is in RUN mode

M8002
SET M10
Initial pulse
The write
instruction
is driven
M10
FNC180 K11 K0 H0FD H9696 The inverter is reset
EXTR
Driving of
write
instruction

FNC180 K11 K0 H0FB H0*1 Computer link


EXTR operation is specified

FNC180 K13 K0 K1 K12000 The maximum frequency


EXTR is set to "120 Hz"

FNC180 K13 K0 K2 K500 The minimum frequency


EXTR is set to "5 Hz"

FNC180 K13 K0 K7 K10 The acceleration time


EXTR is set to "1 s"

FNC180 K13 K0 K8 K10 The deceleration time


EXTR is set to "1 s"

M8029
RST M10
Instruction execute
complete The write
instruction
is driven

*1. When using an E500 Series inverter, use "H2" to specify computer link operation.

2. Changing the speed using a sequence program

M8000 FNC 12 K6000 D10 "60 Hz" is written as


RUN MOV P the initial value at
monitor Operation startup
speed
M17 FNC 12 K4000 D10 The operation speed is
Command for MOV P written as "40 Hz"
switching to speed 1 Operation
speed
M18 FNC 12 K2000 D10 The operation speed is
Command for MOV P written as "20 Hz"
switching to speed 2 Operation
speed

FNC180 K11 K0 H0ED D10 The preset frequency


EXTR is written to the
Operation inverter
speed

E-88
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.1 Practical Example 1

A
3. Controlling operations of an inverter

Common Items
X000
SET M15 H0FA is set to "00H"
Operation stop
command input Operation
stop B
X001 X000 Operation stop is reset

N:N Network
RST M15 by input X001 or X002
Forward Operation stop
rotation command input Operation
command stop
input
X002

Reverse rotation
command input
C

Parallel Link
M15 X001 X002
M21 b1 of H0FA is set to ON
Operation Forward Reverse rotation
stop rotation command input Forward rotation
command command
input
X002 X001
M22 b2 of H0FA is set to ON
D

Computer Link
Reverse Forward rotation
rotation command input Reverse rotation
command command
input
M8000
FNC180 K11 K0 H0FA K2M20 Operation command is written
EXTR M27 to M20H0FA
RUN monitor
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-89
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.1 Practical Example 1

4. Monitoring operations of an inverter

M8000 FNC180 K10 K0 H07A K2M100 Inverter status is read


RUN EXTR H7AM107 to M100
monitor Inverter
running
M100
Y000
Inverter
running Indicator
lamp, etc.
M101
Y001
Forward
rotation Indicator
lamp, etc.
M102
Y002
Reverse
rotation Indicator
lamp, etc.
M103
Y003 Contents of status
Up to (according to
frequency Indicator necessity)
lamp, etc.
M104
Y004
Overload
is applied Indicator
lamp, etc.
M106
Y006
Frequency
is detected Indicator
lamp, etc.
M107
Y007
Alarm
occurrence Indicator
lamp, etc.

FNC180 K10 K0 H06F D50 Output frequency


EXTR monitor
Frequency
monitor
value

END

E-90
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.2 Practical Example 2

A
8.2 Practical Example 2

Common Items
This program executes the same control as practical example 1 shown above.

8.2.1 System configuration example


B
An FX PLC is connected to an inverter.

N:N Network
FX2N, FX2NC Inverter

C
System memory

Parallel Link
Terminal resistor
Distributor

8.2.2 Contents of operation D

Computer Link
The differences from practical example 1 are that the inverter status is not read while data is written to an
inverter, and that the contents to be written are detected and written to an inverter only when the contents to
be written are changed.
Because communication between the PLC and the inverter is minimum in this program, the communication
time is reduced and the response time is improved. E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-91
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.2 Practical Example 2

8.2.3 Program example

1. Writing parameters to an inverter while the PLC is in RUN mode


M8002
SET M10
Initial pulse
The write
instruction
is driven
M10
FNC180 K11 K0 H0FD H9696 The inverter is reset
EXTR
Driving of
write
instruction

FNC180 K11 K0 H0FB H0*1 Computer link


EXTR operation is specified

FNC180 The maximum


K13 K0 K1 K12000 frequency is set to
EXTR "120Hz"

FNC180 The minimum


K13 K0 K2 K500 frequency is set to
EXTR "5Hz"

FNC180 K13 K0 K7 K10 The acceleration time


EXTR is set to "1s"

FNC180 K13 K0 K8 K10 The deceleration time


EXTR is set to "1s"

M8029
RST M10
Instruction execute
complete The write
instruction
is driven

*1. When using an E500 Series inverter, use "H2" to specify computer link operation.

E-92
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.2 Practical Example 2

A
2. Changing the speed using a sequence program

Common Items
M8000
FNC 12 K6000 D10 "60 Hz" is written as
MOV P the initial value at
RUN
monitor Operation startup

M17
speed
B
FNC 12 K4000 D10

N:N Network
The operation speed is
MOV P written as "40 Hz"
Command for
switching to speed 1 Operation
speed
M18
FNC 12 K2000 D10 The operation speed is
MOV P
Command for
switching to speed 2 Operation
written as "20 Hz"
C
speed

Parallel Link
M8002
FNC 12 D10 D80
MOV
Initial pulse
Operation Operation Change in the
speed speed is operation speed
withdrawn (D10) is
FNC228
D10 D80 SET M11
detected D
LD<>

Computer Link
Operation Operation speed is The write
speed withdrawn instruction
is driven
M11
FNC180 K11 K0 H0ED D10 The preset frequency is
EXTR written to the inverter
The write
instruction
is driven
Operation
speed
E

Communication
Inverter
M8029
RST M11
Instruction execute
complete The write
instruction
is driven
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-93
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.2 Practical Example 2

3. Controlling operations of an inverter

X000
SET M15 H0FA is set to "00H"
Operation stop
command input Operation
stop
X001 X000
RST M15 Operation stop is reset
Forward Operation stop by input X001 or X002
rotation command input Operation
command stop
input
X002

Reverse rotation
command input

M15 X001 X002


M21 b1 of H0FA is set to ON
Operation Forward Reverse Forward
stop rotation rotation rotation
command command command
input input
X002 X001
M22 b2 of H0FA is set to ON
Reverse Forward Reverse
rotation rotation rotation
command command command
input input
M8002 FNC 12
MOV K2M20 D81
Initial pulse
Operation Changes in the
command is operation commands
withdrawn (M28 to M20) are
detected
FNC228
LD<> K2M20 D81 SET M12
Operation Driving of
command is write
withdrawn instruction
M12 FNC180 Operation commands
EXTR K11 K0 H0FA K2M20 are written
Driving of M27 to M20H0FA
write
instruction
M8029
RST M12
Instruction execute
complete Driving of
write
instruction

E-94
FX Series PLC User's Manual - Data Communication Edition 8 Practical Program Examples (FX2N, FX2NC)
Inverter Communication 8.2 Practical Example 2

A
4. Monitoring operations of an inverter

Common Items
M10 M11 M12
MC N0 M70 While data is not
Driving of Driving of Driving of written to an inverter,
write write write
instruction instruction instruction
the status is read.
B

N:N Network
N0 M70

M8000 FNC180 K10 K0 H07A K2M100


RUN
EXTR Inverter status is read.
H07AM107 to M100 C
monitor Inverter

Parallel Link
running
M100
Y000
Inverter
running Indicator
lamp, etc.
M101
Y001
D

Computer Link
Forward
rotation Indicator
lamp, etc.
M102
Y002
Reverse
rotation Indicator
lamp, etc. E

Communication
Inverter
M103
Y003 Contents of status
Up to (according to necessity)
frequency Indicator
lamp, etc.
M104

Overload
Y004
F
is applied Indicator

(RS/RS2 Instruction)
Communication
Non-Protocol
lamp, etc.
M106
Y006
Frequency
is detected Indicator
lamp, etc.
M107 G
Y007

(FX2N-232IF)
Communication
Non-Protocol
Alarm
occurrence Indicator
lamp, etc.

FNC180 K10 K0 H06F D50


EXTR Output frequency monitor
Frequency
monitor
H
value
Communication
Programming

MCR N0

END
I
Maintenance
Remote

Apx.A
models
Discontinued

E-95
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.1 Differences between FX2N, FX2NC and FX3S, FX3G, FX3GC, FX3U, FX3UC

9. Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)


This chapter explains how to create programs which change parameters of inverters and give operation
commands to inverters.
As explanation, a program example is shown for each applied instruction.

9.1 Differences between FX2N, FX2NC and FX3S, FX3G, FX3GC, FX3U, FX3UC
Instruction devices used in inverter communication are different between FX3S, FX3G, FX3GC, FX3U, FX3UC
PLCs and FX2N, FX2NC PLCs.
When using a program for FX2N, FX2NC PLCs in FX3S, FX3G, FX3GC, FX3U, FX3UC PLCs, change the devices
according to the tables below.
1. Inverter communication instructions
Function FX2N,FX2NC FX3S,FX3G,FX3GC,FX3U,FX3UC
Monitoring operation of an inverter EXTR(K10) IVCK
Controlling operation of an inverter EXTR(K11) IVDR
Reading parameters from an inverter EXTR(K12) IVRD
Writing parameters to an inverter EXTR(K13) IVWR
Writing parameters to an inverter all at once IVBWR*1
Controls operations and monitors operations of an inverter
IVMC
with a single command
*1. Only available for FX3U and FX3UC PLCs.
2. Related devices
1) Bit devices
FX3S,FX3G,FX3GC,FX3U,FX3UC
Function FX2N,FX2NC
ch1 ch2
Instruction execution complete M8029 M8029 M8029
Communication error
M8063*2 M8063*5 M8438*5
(shared by all communication)
Inverter communicating M8155 M8151 M8156
Inverter communication error M8156 M8152*3 M8157*3
Inverter communication error latch*3 M8157 M8153 M8158
IVBWR instruction error*4 M8154*3 M8159*3
*2. In the FX2N and FX2NC PLCs, M8063 does not turn ON when an inverter communication error occurs.
*3. Cleared when the PLC mode is changed from STOP to RUN.
*4. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.
*5. Cleared when PLC power supply is turned from OFF to ON.
2) Word devices
FX3S,FX3G,FX3GC,FX3U,FX3UC
Function FX2N,FX2NC
ch1 ch2
Error code (shared by all communication) D8063 D8063*6 D8438*6
Response wait time of inverter communication D8154 D8150*6 D8155*6
Step number of instruction during inverter communication D8155 D8151 D8156
Inverter communication error code*7 D8156 D8152 D8157
Inverter communication error occurrence step*7 D8157 D8153 D8158
IVBWR instruction error parameter number*7*8 D8154 D8159
Operation mode display D8419 D8439
*6. Cleared when PLC power supply is turned from OFF to ON.
*7. Cleared when the PLC mode is changed from STOP to RUN.
*8. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.

E-96
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.2 Contents of Related Devices

A
9.2 Contents of Related Devices

Common Items
The tables below show devices used for inverter communication in FX3S, FX3G, FX3GC, FX3U and FX3UC
PLCs.

1. Bit devices B
Device No.

N:N Network
Name Description R/W
ch1 ch2
Turns ON when execution of inverter communication
instruction is completed, and remains ON for 1 scan.
M8029 Instruction execution complete Turns ON also when execution of instruction is R
completed if inverter communication error flag C
(M8152 or M8157) turns ON.

Parallel Link
Turns ON when an error occurs in any type of
M8063 M8438 Serial communication error*1 R
communication.
Remains ON while inverter communication is being
M8151 M8156 Inverter communicating R
executed.

M8152 M8157 Inverter communication error*2


Turns ON when an error occurs during
R D
communication with an inverter.

Computer Link
Turns ON when an error occurs during
M8153 M8158 Inverter communication error latch*2 R
communication with an inverter.
Turns ON when an error is caused by IVBWR
M8154 M8159 IVBWR instruction error*2, *3 R
instruction.

R: Read only (used as a contact in program) E

Communication
Inverter
*1. Cleared when PLC power supply is turned from OFF to ON.
*2. Cleared when the PLC mode is changed from STOP to RUN.
*3. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.

2. Word devices F
Device No.

(RS/RS2 Instruction)
Communication
Non-Protocol
Name Description R/W
ch1 ch2
D8063 D8438 Error code for serial communication*4 Stores a communication error code. R
Inverter communication response Sets the response wait time of inverter
D8150 D8155 R/W
waiting time*4 communication.
G
Step number of instruction executing Stores the step number of an instruction during
D8151 D8156 R

(FX2N-232IF)
Communication
Non-Protocol
inverter communication inverter communication.
Error code for inverter
D8152 D8157 Stores an inverter communication error code. R
communication*5
Step where inverter communication Latches a step number in which inverter
D8153 D8158
error occurred*5 communication error has occurred.*7
R
H
Error parameter number of IVBWR Stores a parameter number in which an IVBWR
Communication
Programming

D8154 D8159 R
instruction*5*6 instruction error has occurred.
D8419 D8439 Operation mode display Stores the communication type being used. R

R: Read only
W: Write only I
R/W: Read or Write
Maintenance
Remote

*4. Cleared when PLC power supply is turned from OFF to ON.
*5. Cleared when the PLC mode is changed from STOP to RUN.
*6. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.
*7. Updated only for the first error occurrence, and not for the second error occurrence or later. Apx.A
models
Discontinued

E-97
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.3 Common Items in Inverter Communication Instructions

9.3 Common Items in Inverter Communication Instructions

9.3.1 Inverter communication types (IVCK to IVMC)


Execute inverter communication using the following applied instructions.
There are six types of applied instructions, "IVCK (FNC270) to IVMC (FNC275)", depending on the data
communication direction and parameter reading/writing direction.
S1 S2 S3 n
Inverter Inverter Inverter Read/ Used
communication station instruction
instruction number code Write channel

Only 16-bit type is applicable. K1:ch1


DIVCK (32-bit type), IVCKP K2:ch2
(pulse operation type) and Read value storage destination
DIVCKP (32-bit pulse operation or value written to inverter
type) are not applicable.

Detailed
Instruction Function Control direction
explanation
IVCK(FNC270) Monitors operations of an inverter. PLC inverter 9.4
IVDR(FNC271) Controls operations of an inverter. PLC inverter 9.5
IVRD(FNC272) Reads a parameter from an inverter. PLC inverter 9.6
IVWR(FNC273) Writes a parameter to an inverter. PLC inverter 9.7
*1 Writes parameters to an inverter all at once. PLC inverter 9.8
IVBWR(FNC274)
Controls operations and monitors operations of an
IVMC(FNC275) PLC inverter 9.9
inverter with a single command

*1. Only available for FX3U and FX3UC PLCs.

9.3.2 Function and operation

1. Communication start timing


At the rising edge (OFFON) of the drive condition, the PLC starts communication with an inverter.
Even if the drive condition turns OFF during communication with an inverter, the PLC executes
communication until the last instruction.
When the drive condition is always ON, the PLC executes communication repeatedly.

2. Simultaneous driving of instructions and communication processing


1) Driving instructions at the same time
- Two or more IVCK (FNC270) to IVMC (FNC275) instructions can be programmed, and driven at the
same time.
- When two or more instructions are driven at the same time in the channel used for communication, the
latter inverter communication instruction in the program is executed after the current communication
with the inverter has finished.
M8000
FNC273 (1)
IVWR
RUN M8151
monitor ONOFF

FNC271 (2)
IVDR
M8151
ONOFF

FNC270 (3)
IVCK

E-98
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.3 Common Items in Inverter Communication Instructions

A
- The PLC waits for 15 ms after acquiring the communication port, and then starts communication using

Common Items
inverter communication instructions. Even if the drive condition turns ON, the PLC does not start
execution of an inverter communication instruction until the communication port busy flag M8151 turns
OFF from ON, if M8151 is already set to ON by another inverter communication instruction.
The PLC frees the communication port, and then executes inverter communication instructions driven in
the next step and so on.
B
M0

N:N Network
FNC273
IVWR

M1
FNC270
IVCK
C

Parallel Link
M0
*1 *2
IVWR
instruction
(Communicating) D

Computer Link
15ms 15ms 15ms

M1
*2
IVCK
instruction E
(Communicating)

Communication
Inverter
15ms 15ms

M8151 IVWR IVCK IVWR IVCK IVWR


*3 *3 F
*1. The PLC does not execute the instruction even if M8151 is turned OFF because the drive contact is

(RS/RS2 Instruction)
Communication
Non-Protocol
OFF.
*2. When two or more instructions are driven at the same time during communication, the next inverter
communication instruction is executed after the current instruction is completed.
*3. M8151 remains OFF until the next inverter communication instruction is driven after execution of the
current inverter communication instruction is completed. G

(FX2N-232IF)
Communication
Non-Protocol
2) Cautions on programming
When communicating with inverters for two or more items, let the drive contact for inverter
communication instruction remain ON until sending is completed. After communication with all inverters is
completed, set the drive contact to OFF using the instruction execution complete flag M8029.
X001
SET M0 Command is H
latched
Communication
Programming

M0 FNC274 Communication is
IVCK executed
M8029 Command is
RST M0
Instruction execution
complete
reset
I
Maintenance
Remote

3. Communication complete flag (M8029)


When communication with an inverter is completed, the instruction execution complete flag M8029 turns ON,
and remains ON for 1 scan.
For the M8029 use method, refer to program examples shown below.
Apx.A
models
Discontinued

E-99
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.3 Common Items in Inverter Communication Instructions

9.3.3 Instruction completion and error flag operation


When two or more inverter communication instructions are programmed, the following flags turn ON or OFF
according to the execution result of each inverter communication instruction.
To acquire the result of each inverter communication instruction, make sure to provide these flags just below
each inverter communication instruction.
Device Device
number Description number Description
ch1 ch2 ch1 ch2
M8029 Instruction execution complete D8063 D8438 Serial communication error code
M8063 M8438 Serial communication error D8152 D8157 Inverter communication error code
M8152 M8157 Inverter communication error D8153 D8158 Step in which inverter communication error occurred
Inverter communication error
M8153 M8158 D8154 D8159 IVBWR error parameter number*1
latch
M8154 M8159 IVBWR instruction error*1

*1. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.

1. Operation of M8029 (instruction execution complete flag)


The operation of M8029 (instruction execution complete flag) represents the state in which the IVDR
instruction is completed while M0, M2 are off and M1 is ON.
Operation of
[1] IVWR instruction is not driven instruction execution
M0 (OFF) complete flag
FNC273 M8029 : OFF
IVWR

[2] IVDR instruction is driven


M1 (ON)
FNC271 M8029 : ON
IVDR

[3] IVCK instruction is not driven


M2 (OFF)
FNC270 M8029 : OFF
IVCK

2. Processing of communication errors


The following two types of processing are executed for communication errors.
The parity error/overrun error/framing error flags (shown in the upper column) turns ON when an error occurs
in any type of communication.
The error flag shown in the lower column turns ON when an error occurs during communication with an
inverter.
Bit device Word device
ch1 ch2 ch1 ch2 ch1 ch2 ch1 ch2 Description
M8063 M8438 M8152 M8157 M8153 M8159 D8063 D8438
ON OFF OFF 6301 3801 Parity error, overrun error or framing error
ON Any inverter communication error other than
ON ON 6320 3820
(only at first time) those above

When inverter communication error flag turns ON, the step number is stored in the inverter communication
error occurrence step device (D8153 or D8158).
Create the program shown below for each corresponding instruction to check the inverter communication
error code (stored in D8152 or D8157).

E-100
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.3 Common Items in Inverter Communication Instructions

A
3. Program example

Common Items
X000
SET M0
Start command
M0
FNC277
IVWR
K1
B

N:N Network
M8152
SET M50 M50
Communication error Instruction error is
M8029 checked
FNC 12 D8152 D50 D50
Instruction MOV
execution
complete C
RST M0

Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-101
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.3 Common Items in Inverter Communication Instructions

9.3.4 Cautions on programming

1. Using an inverter communication instruction together with another instruction


An inverter communication instruction using ch1 cannot be used together with a RS instruction.
An inverter communication instruction cannot be used together with a RS2 instruction if the RS2 instruction
uses the same channel.

2. When programming an inverter communication instruction in a state of a STL instruction


Make sure to let the state relay remain ON until communication with an inverter is completed. Program a
sequence while observing the following cautions
Add M8029 (instruction execution complete flag) ON condition to the state relay transfer condition, and
provide such interlock that the state relay ON/OFF status does not change during communication with an
inverter.
If the state changes during communication, communication may not be performed normally.
When resetting many state relays all at once using the ZRST (FNC 40) instruction, etc., make sure that the
M8151 or M8156 (communication port busy) condition is OFF.
X000
SET M0
Reset input
M0 M8151 FNC 40 S0 S999 State relays S0 to S999
Communication ZRST are reset all at once.
port busy
RST M0

3. Using an inverter communication instruction in a program flow


An inverter communication instruction cannot be used in the following program flows
Program flow disabling the inverter communication
Remarks
instruction
Between CJ and P instructions Conditional jump
Between FOR and NEXT instructions Repeat
Between P and SRET instructions Subroutine
Between I and IRET instructions Interrupt routine

4. Caution on writing during RUN


1) Condition in which inverter communication instruction can be written:
While the PLC is in the STOP status, inverter communication instruction can be written during RUN.
2) Condition in which inverter communication instruction cannot be written:
Inverter communication instruction cannot be written during RUN.
If an inverter communication instruction is written during RUN during communication or if an inverter
communication instruction is deleted while in RUN, communication may be disabled after that. (In such a
case, set the PLC to STOP, and then to RUN mode again to initialize the status.)

5. When using the E500 Series


Parameters Nos. 922 and 923 in the E500 Series cannot be used in inverter communication.

E-102
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.3 Common Items in Inverter Communication Instructions

A
6. Cautions when using the password function for inverter

Common Items
1) When a communication error occurs
When a communication error occurs in an inverter communication instruction, the FX PLC automatically
retries communication up to 3 times*1.
Hence, when a password disable error occurs in the inverter in which "display of the number of times of
password disable error"*2 is enabled using Pr297, please note that the number of times of password B
disable error displayed in accordance with the setting of Pr297 may not be the same as the actual

N:N Network
number of times of password input error as described below.
Do not execute automatic retry (re-driving of an inverter instruction) using a sequence program when
writing data to Pr297.

Cases in which a password reset error occurs in an inverter communication instruction, and the actual C
number of times of reset error in such cases

Parallel Link
- When a wrong password is written to Pr297 due to a password input error
When the writing instruction is executed once, a password reset error occurs 3 times.
- When the password cannot be written correctly to Pr297 due to noise, etc.
A password reset error occurs up to 3 times.
D
2) When registering the password

Computer Link
When registering the password in the inverter using an inverter communication instruction, write the
password to Pr297, read Pr297, and then confirm that registration of the password is completed
normally*3.
If writing of the password to Pr297 is not completed normally due to noise, etc., the FX PLC automatically
retries writing, and the registered password may be reset by the retry. E

Communication
Inverter
*1. The FX PLC executes the first communication, and then retries communication twice (3 time in total).
*2. When "display of the number of times of password disable error" is enabled using Pr297 and when a
password disable error occurs 5 times, the "reading/writing restriction" cannot be disabled even if the
right password is input. For recovery from this status, it is necessary to all-clear all parameters. F
*3. When the value given as a result of reading Pr297 is "0" to "4", registration of the password is

(RS/RS2 Instruction)
Communication
Non-Protocol
completed normally.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-103
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.4 Inverter Operation Monitoring Instruction (PLCInverter) [FNC270 / IVCK]

9.4 Inverter Operation Monitoring Instruction


(PLCInverter) [FNC270 / IVCK]
The IVCK instruction reads the operation status of an inverter to the PLC.

9.4.1 Function and operation


When an "instruction code" specified for computer link operation in the inverters is specified in the IVCK
(FNC270) instruction, a value in the inverter is read to D .
1. Applicable devices
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S1 1 2
S2 1 2
D 1 2
n
1: Only available for FX3G, FX3GC, FX3U and FX3UC PLCs.
2: Only available for FX3U and FX3UC PLCs.
2. Program example
S1 S2 D n
M0
FNC270 K6 H6F D100 K1
IVCK
Command
contact Communication channel K1:ch1
Read value storage destination K2:ch2
Inverter station number: 0 to 31 Inverter instruction code (hexadecimal)

9.4.2 Inverter instruction codes


The table below shows inverter instruction codes which can be specified in S2 . Any instruction codes not
shown in the table below may cause communication errors. Use only instruction codes shown below.
For the instruction codes, refer to the pages explaining computer link in detail in each inverter manual.
S2 Applicable inverter
Inverter Instruction Read contents F800, A800, F700,
V500 F500, A500 E500 S500
code (hexadecimal) A700, E700, D700
H7B Operation mode
H6F Output frequency [speed] *1
H70 Output current
H71 Output voltage
H72 Special monitor
H73 Special monitor selection No.
H74 Alarm definition
H75 Alarm definition
H76 Alarm definition
H77 Alarm definition
H79 Inverter status monitor (expansion)
H7A Inverter status monitor
H6E Set frequency read (E2PROM) *1
H6D Set frequency read (RAM) *1
H7F Link parameter expansion setting These codes cannot be specified in S2 of the IVCK
instruction. They are automatically processed when a
H6C Second parameter changing "second parameter specification code" is specified the
IVRD instruction.
*1. Please write "0" to instruction code HFF (Link parameter expansion setting) just before the IVCK
instruction when reading frequency.
When "0" is not written, reading of the frequency may not be executed normally.

E-104
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.5 Inverter Operation Control Instruction (PLCInverter) [FNC271 / IVDR]

A
9.5 Inverter Operation Control Instruction (PLCInverter) [FNC271 / IVDR]

Common Items
This instruction writes a control value required to operate an inverter from the PLC to the inverter.

9.5.1 Function and operation


B
When an "instruction code" specified for computer link operation in the inverters is specified in the IVDR

N:N Network
(FNC271) instruction, the value specified in S3 is written to the specified item of the inverter.
1. Applicable devices
Bit Devices Word Devices Others
Oper-
and System/User Digit Specification System/User
Special
Unit
Index
Con- Real Charac-
stant Number ter String
Pointer C
Type

Parallel Link
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S1 1 2
S2 1 2
S3 1 2
n
D

Computer Link
1: Only available for FX3G, FX3GC, FX3U and FX3UC PLCs.
2: Only available for FX3U and FX3UC PLCs.

2. Program example
S1 S2 S3 n
M0
FNC271 K6 HFA K2M50 K1
E
IVDR

Communication
Inverter
Command
contact Communication channel K1:ch1
Value written to inverter K2:ch2
Inverter station number: 0 to 31 Inverter instruction code (hexadecimal)

9.5.2 Inverter instruction codes


F

(RS/RS2 Instruction)
Communication
Non-Protocol
The table below shows inverter instruction codes which can be specified in S2 .
For the instruction codes, refer to the pages explaining computer link in detail in each inverter manual.
S2 Applicable inverter
Inverter Instruction
code (hexadecimal)
Write contents F800, A800, F700,
A700, E700, D700
V500 F500, A500 E500, S500 G

(FX2N-232IF)
Communication
Non-Protocol
HFB Operation mode
HF3 Special monitor selection No.
HF9 Run command (expansion)
HFA Run command
HEE Set frequency write (EEPROM) *3 H
HED Set frequency write (RAM) *3
Communication
Programming

HFD*1 Inverter reset*2


HF4 Alarm definition batch clear
HFC Parameter all clear
HFC
HFF
User clear
Link parameter expansion setting








I
Maintenance
Remote

*1. The instruction code "HFD (inverter reset)" does not request a response from the inverter.
Accordingly, even if inverter reset is executed to a station number at which an inverter is not
connected, error does not occur.
It takes about 2.2 seconds to complete execution of inverter reset.
*2. When resetting the inverter, please specify H9696 as the operand S3 of the IVDR instruction. Apx.A
Do not use H9966.
models
Discontinued

*3. Please write "0" to instruction code HFF (Link parameter expansion setting) just before the IVDR
instruction when writing frequency.
When "0" is not written, writing of the frequency may not be executed normally.

E-105
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.6 Inverter Parameter Reading (PLCInverter) [FNC272 / IVRD]

9.6 Inverter Parameter Reading (PLCInverter) [FNC272 / IVRD]


This instruction reads a parameter of an inverter to the PLC.

9.6.1 Function and operation


When a parameter number of an inverter is specified in IVRD (FNC272) instruction, the value of the
parameter is read to D .

1. Applicable devices
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S1 1 2
S2 1 2
D 1 2
n

1: Only available for FX3G, FX3GC, FX3U and FX3UC PLCs.


2: Only available for FX3U and FX3UC PLCs.

2. Program example
S1 S2 D n
M0
FNC272 K6 K7 D150 K1
IVRD
Command
contact Communication channel K1:ch1
Read value storage destination K2:ch2
Inverter station number: 0 to 31 Inverter parameter number (decimal)

9.6.2 Inverter instruction codes


Refer to related data shown later.

9.6.3 Program example of "second parameter specification code"


For second parameter specification code, refer to Section 9.9.
In the program example shown below, the parameters (frequency: 201, time: 1201, motor rotation direction:
2201) are read from the A500 inverter whose station number is 6.

E-106
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.6 Inverter Parameter Reading (PLCInverter) [FNC272 / IVRD]

A
Read devices: D100 = Motor rotation direction, D101 = Frequency, D102 = Time

Common Items
X001
SET M0
Read
command
S1 S2 D n
M0
FNC272
B
K6 K2201 D100 K1 Motor rotation directionD100

N:N Network
IVRD
Drive
contact Communication channel K1:ch1
Inverter station Read value storage destination
number: Inverter parameter number (decimal)
0 to 31
FNC272 K6 K201 D101 K1 FrequencyD101 C
IVRD

Parallel Link
FNC272 TimeD102
K6 K1201 D102 K1
IVRD
The unit is specified by Pr. 200.
M8029
RST M0 D
Execution

Computer Link
complete flag

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-107
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.7 Inverter Parameter Writing (PLCInverter) [FNC273 / IVWR]

9.7 Inverter Parameter Writing (PLCInverter) [FNC273 / IVWR]


This instruction writes a value from the PLC to a parameter in an inverter.

9.7.1 Function and operation

When a parameter number in an inverter is specified in IVWR (FNC273) instruction, the value of S3 is
written to the specified item in the inverter.

1. Applicable devices
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S1 1 2
S2 1 2
S3 1 2
n

1: Only available for FX3G, FX3GC, FX3U and FX3UC PLCs.


2: Only available for FX3U and FX3UC PLCs.

2. Program example
S1 S2 S3 n
M0
FNC273 K6 K7 D160 K1
IVWR
Command
contact Communication channel K1:ch1
Value written to inverter K2:ch2
Inverter station number: 0 to 31 Inverter parameter number (decimal)

9.7.2 Inverter instruction codes


Refer to related data shown later.

9.7.3 Program example of "second parameter specification code"


For second parameter specification code, refer to Section 9.9.
In the program example shown below, data is written from the PLC to the parameters (frequency: 201, time:
1201, motor rotation direction: 2201) in the A500 inverter.
X001
SET M0
Write
command
S1 S2 S3 n
M0
FNC273 K6 K2201 H1 K1 Motor rotation direction: Forward
IVWR
Drive
contact Communication channel K1:ch1
Inverter station Value written to inverter
number: 0 to 31 Inverter parameter number (decimal)

FNC273 K6 K201 H14 K1 Frequency: 20Hz


IVWR

FNC273 Time: 1:00


K6 K1201 H100 K1
IVWR
The unit is specified by Pr. 200.
M8029
RST M0
Execution complete flag

E-108
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.8 Inverter Parameter Batch Writing (PLCInverter) [FNC274 / IVBWR]

A
9.8 Inverter Parameter Batch Writing (PLCInverter) [FNC274 / IVBWR]

Common Items
This instruction writes values from the PLC to parameters in an inverter all at once.
The IVBWR instruction is supported only in FX3U and FX3UC PLCs.

9.8.1 Function and operation B

N:N Network
When a parameter number in an inverter is specified in the IVBWR (FNC274) instruction, the values of S3
and later are written to the specified items in the inverter all at once.

1. Applicable devices

Oper-
Bit Devices Word Devices Others C
Special Con- Real Charac-

Parallel Link
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S1
S2
D
S3

Computer Link
n

2. Program example
S1 S2 S3 n
E

Communication
Inverter
M0
FNC274 K6 K8 D200 K1
Command IVBWR
contact
Inverter station number: 0 to 31 Communication channel K1: ch1
Number of parameters to be written Head device of parameter K2: ch2
(decimal) table written to inverter
F
The following table shows values (two word devices/point) in a specified table which are written to a number

(RS/RS2 Instruction)
Communication
Non-Protocol
of consecutive parameters specified in S2 starting from a word device specified in S3 .

S3 D200 Parameter No. 1


S3 +1 D201 Value 1 written to parameter
S3 +2 D202 Parameter No. 2 G

(FX2N-232IF)
Communication
Non-Protocol
S3 +3 D203 Value 2 written to parameter
S2 2 = Number of occupied word devices
: : :
: : :
S3 +14 D214 Parameter No. 8
S3 +15 D215 Value 8 written to parameter H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-109
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.9 Controls Operations and Monitors Operations of an Inverter with a Single Command(PLCInverter)[FNC275 / IVMC]

9.9 Controls Operations and Monitors Operations of an Inverter


with a Single Command(PLCInverter)[FNC275 / IVMC]
This instruction writes 2 types of settings (operation command and set frequency) to the inverter, and reads 2
types of data (inverter status monitor, output frequency, etc.) from the inverter at the same time.
The following PLC versions support the IVMC instruction.
PLC Applicable version
FX3S Ver. 1.00 or later
FX3G, FX3GC Ver. 1.40 or later
FX3U, FX3UC Ver. 2.70 or later

9.9.1 Function and operation

1. Applicable devices
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S1 1 2
S2 1 2
S3 1 2
D 1 2
n

1: Only available for FX3G, FX3GC, FX3U and FX3UC PLCs.


2: Only available for FX3U and FX3UC PLCs.

2. Program example
S1 S2 S3 D n
M0
FNC275 K0 H0000 D10 D20 K1
Command IVMC
contact Channel to be used
Inverter station number (K1: ch1, K2: ch2)
(K0 to K31) Head device which stores values to be read
Multiple instructions for inverter: from the inverter
Send/receive data type specification
Head device which stores data to be written to the inverter

3. Send/receive data type S2


The table below shows valid send data 1 and 2 and receive data 1 and 2 specified by the send/receive data
type S2 .
S2 Send data Receive data
Send/receive (Write contents to Inverter) (Read contents from Inverter)
data type
(HEX) Data 1 ( S3 ) Data 2 ( S3 +1) Data 1 ( D ) Data 2 ( D +1)

H0000 Set frequency Output frequency (speed)


H0001 Run command (RAM) Inverter status monitor Special monitor
H0010 (expansion) Set frequency (expansion) Output frequency (speed)
H0011 (RAM, EEPROM) Special monitor

Caution

Number of occupied devices


Two devices are occupied respectively by S3 and D .
Make sure not to use those devices in another control.

E-110
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.9 Controls Operations and Monitors Operations of an Inverter with a Single Command(PLCInverter)[FNC275 / IVMC]

A
If a device number outside the range due to indexing, etc. is specified in D , the receive data from the

Common Items
inverter is not stored in D . However, values set in S3 and S3 +1 may be written to the inverter.
If any unspecified value is set in S2 , unexpected data may be written to and read from the inverter, and
values of D and D +1 may be updated.
IVMC instruction reads the inverter status at the time of communication with the inverter, and stores the
read status to D . Accordingly, the status written by the IVMC instruction can be read by a next or later
B

N:N Network
read instruction (IVCK or IVMC).

9.9.2 Applicable inverters


This instruction is applicable to the following inverters:
FREQROL-A800 (Applicable in all) C

Parallel Link
FREQROL-F800 (Applicable in all)
FREQROL-E700 (February 2009 and later)
FREQROL-D700 (Applicable in all)
For details, refer to the respective inverter manual.
D
9.9.3 Applicable programming tool

Computer Link
The following programming tools support this instruction.

1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
E

Communication
Inverter
GX Works2 SWDNC-GXW2-E Ver. 1.48A or later
-
FX-30P Ver. 1.20 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.62Q or later
-
FX-30P Ver. 1.50 or later F
FX3GC PLC

(RS/RS2 Instruction)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.50 or later
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
FX-30P Ver. 1.50 or later
- G

(FX2N-232IF)
Communication
Non-Protocol
2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2
FX-30P
SWDNC-GXW2-J Ver. 1.45X or later
Ver. 1.20 or later
- H
Communication
Programming

FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.56J or later
-
FX-30P Ver. 1.50 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
I
FX-30P Ver. 1.50 or later
Maintenance
Remote

FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later

Apx.A
models
Discontinued

E-111
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

9.10 Second Parameter Specification Codes


When handling the following parameters in computer link operation, it is necessary to select second
parameters.
In IVRD, IVWR, and IVBWR*1 instructions, when a value shown in the tables below is set in S2 ( S3 in
IVBWR*1 instruction), the extension parameter and second parameter are automatically overwritten, and
parameter values are either read or written.
*1. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.

9.10.1 S500 Series

1. Second parameter specification codes for parameter numbers C2 to C7


Second parameter specification code
Parameter
Name [(decimal) value to be specified in S2 in IVRD/IVWR
No.
instruction for parameter number]
Frequency setting voltage bias
C2 902
frequency
C3 Frequency setting voltage bias 1902
C4 Frequency setting voltage gain 903
Frequency setting current bias
C5 904
frequency
C6 Frequency setting current bias 1904
C7 Frequency setting current gain 905

9.10.2 E500 Series

1. Second parameter specification codes for parameter numbers 902 to 905


Second parameter specification code
[(decimal) value to be specified in S2 in IVRD/IVWR
Parameter
Name instruction for parameter number]
No.
Offset/Gain Analog Analog value of
(H00) (H01) terminal (H02)
902 Frequency setting voltage bias 902 1902 2902
903 Frequency setting voltage gain 903 1903 2903
904 Frequency setting current bias 904 1904 2904
905 Frequency setting current gain 905 1905 2905

E-112
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

A
9.10.3 A500 Series

Common Items
1. Second parameter specification codes for parameter numbers 201 to 230 and 902 to 905
Second parameter specification code

Parameter
Name
[(decimal) value to be specified in S2 in IVRD/IVWR
instruction for parameter number]
B
No.

N:N Network
Operation frequency Rotation direction
Time read/write
read/write write/read
201 Program set 1 201 1201 2201
202 Program set 1 202 1202 2202
203 Program set 1 203 1203 2203 C
204 Program set 1 204 1204 2204

Parallel Link
205 Program set 1 205 1205 2205
206 Program set 1 206 1206 2206
207 Program set 1 207 1207 2207
208 Program set 1 208 1208 2208 D
209 Program set 1 209 1209 2209

Computer Link
210 Program set 1 210 1210 2210
211 Program set 2 211 1211 2211
212 Program set 2 212 1212 2212
213 Program set 2 213 1213 2213
214 Program set 2 214 1214 2214
E

Communication
Inverter
215 Program set 2 215 1215 2215
216 Program set 2 216 1216 2216
217 Program set 2 217 1217 2217
218 Program set 2 218 1218 2218
219 Program set 2 219 1219 2219 F
220 Program set 2 220 1220 2220

(RS/RS2 Instruction)
Communication
Non-Protocol
221 Program set 3 221 1221 2221
222 Program set 3 222 1222 2222
223 Program set 3 223 1223 2223
224 Program set 3 224 1224 2224 G
225 Program set 3 225 1225 2225

(FX2N-232IF)
Communication
Non-Protocol
226 Program set 3 226 1226 2226
227 Program set 3 227 1227 2227
228 Program set 3 228 1228 2228
229 Program set 3 229 1229 2229
230 Program set 3 230 1230 2230
H
Communication
Programming

2. Second parameter specification codes for parameter numbers 902 to 905


Second parameter specification code
[(decimal) value to be specified in S2 in IVRD/IVWR
Parameter
No.
Name instruction for parameter number]
Offset/Gain Analog Analog value of
I
Maintenance
Remote

(H00) (H01) terminal (H02)


902 Frequency setting voltage bias 902 1902 2902
903 Frequency setting voltage gain 903 1903 2903
904 Frequency setting current bias 904 1904 2904
905 Frequency setting current gain 905 1905 2905 Apx.A
models
Discontinued

E-113
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

9.10.4 F500 Series

1. Second parameter specification codes for parameter numbers 902 to 905


Second parameter specification code
[(decimal) value to be specified in S2 in IVRD/
Parameter
Name IVWR instruction for parameter number]
No.
Offset/Gain Analog Analog value of
(H00) (H01) terminal (H02)
902 Frequency setting voltage bias 902 1902 2902
903 Frequency setting voltage gain 903 1903 2903
904 Frequency setting current bias 904 1904 2904
905 Frequency setting current gain 905 1905 2905

9.10.5 V500 Series

1. Second parameter specification codes for parameter numbers 902 to 905


Second parameter specification code
[(decimal) value to be specified in S2 in IVRD/
Parameter
Name IVWR instruction for parameter number]
No.
Offset/Gain Analog Analog value of
(H00) (H01) terminal (H02)
902 Speed setting No. 2 bias 902 1902 2902
903 Speed setting No. 2 gain 903 1903 2903
904 Torque command No. 3 bias 904 1904 2904
905 Torque command No. 3 gain 905 1905 2905
917 No.1 terminal bias (speed) 917 1917 2917
918 No.1 terminal gain (speed) 918 1918 2918
919 No.1 terminal bias (torque/magnetic flux) 919 1919 2919
920 No.1 terminal gain (torque/magnetic flux) 920 1920 2920

9.10.6 F700 Series

1. Second parameter specification codes for parameter numbers 125, 126, and C2 to C7
Second parameter specification code
Parameter
Name [(decimal) value to be specified in S2 in
No.
IVRD/IVWR instruction for parameter number]
C2 Terminal 2 frequency setting bias frequency 902
C3 Terminal 2 frequency setting bias 1902
125 Terminal 2 frequency setting gain frequency 903
C4 Terminal 2 frequency setting gain 1903
C5 Terminal 4 frequency setting bias frequency 904
C6 Terminal 4 frequency setting bias 1904
126 Terminal 4 frequency setting gain frequency 905
C7 Terminal 4 frequency setting gain 1905

E-114
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

A
9.10.7 A700 Series

Common Items
1. Second parameter specification codes for parameter numbers 125, 126, C2 to C7, C12 to
C19, and C38 to C41

Parameter
Name
Second parameter specification code B
No. [(decimal) value to be specified in S2 in

N:N Network
IVRD/IVWR instruction for parameter number]
C2 Terminal 2 frequency setting bias frequency 902
C3 Terminal 2 frequency setting bias 1902
125 Terminal 2 frequency setting gain frequency 903
C4 Terminal 2 frequency setting gain 1903 C

Parallel Link
C5 Terminal 4 frequency setting bias frequency 904
C6 Terminal 4 frequency setting bias 1904
126 Terminal 4 frequency setting gain frequency 905
C7 Terminal 4 frequency setting gain 1905
C12 Bias frequency (speed) for terminal No. 1 917 D
C13 Bias (speed) for terminal No. 1 1917

Computer Link
C14 Gain frequency (speed) for terminal No. 1 918
C15 Gain (speed) for terminal No. 1 1918
C16 Bias command (torque) for terminal No. 1 919
C17
C18
Bias (torque) for terminal No. 1
Gain command (torque) for terminal No. 1
1919
920
E

Communication
Inverter
C19 Gain (torque) for terminal No. 1 1920
C38 Bias command (torque) for terminal No. 4 932
C39 Bias (torque) for terminal No. 4 1932
C40 Gain command (torque) for terminal No. 4 933
C41 Gain (torque) for terminal No. 4 1933 F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-115
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

9.10.8 E700 and D700 Series

1. Second parameter specification codes for parameter numbers 125, 126, C2 to C7 and C22 to
C25
Second parameter specification code
Parameter
Name [(decimal) value to be specified in S2 in IVRD/
No.
IVWR instruction for parameter number]
C2 Terminal 2 frequency setting bias frequency 902
Terminal 2 frequency setting bias 1902
C3
Terminal 2 analog value 2902 (Only the IVRD instruction)
125 Terminal 2 frequency setting gain frequency 903
Terminal 2 frequency setting gain 1903
C4
Terminal 2 analog value 2903 (Only the IVRD instruction)
C5 Terminal 4 frequency setting bias frequency 904
Terminal 4 frequency setting bias 1904
C6
Terminal 4 analog value 2904 (Only the IVRD instruction)
126 Terminal 4 frequency setting gain frequency 905
Terminal 4 frequency setting gain 1905
C7
Terminal 4 analog value 2905 (Only the IVRD instruction)
Frequency setting voltage bias frequency (built-in
C22 922
potentiometer)
Frequency setting voltage bias
C23 1922
(built-in potentiometer)
Frequency setting voltage gain frequency (built-in
C24 923
potentiometer)
Frequency setting voltage gain (built-in
C25 1923
potentiometer)

E-116
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

A
9.10.9 F800 Series

Common Items
1. Second parameter specification codes for parameter numbers Pr125, Pr126, C2 to C19 and
C38 to C41

Parameter
Second parameter specification code B
Name [(decimal) value to be specified in S2 in IVRD/

N:N Network
No.
IVWR instruction for parameter number]
C2 Terminal 2 frequency setting bias frequency 902
C3 Terminal 2 frequency setting bias 1902
125 Terminal 2 frequency setting gain frequency 903
C4 Terminal 2 frequency setting gain 1903
C

Parallel Link
C5 Terminal 4 frequency setting bias frequency 904
C6 Terminal 4 frequency setting bias 1904
126 Terminal 4 frequency setting gain frequency 905
C7 Terminal 4 frequency setting gain 1905
C12 Terminal 1 bias frequency (speed) 917 D
C13 Terminal 1 bias (speed) 1917

Computer Link
C14 Terminal 1 gain frequency (speed) 918
C15 Terminal 1 gain (speed) 1918
C16 Terminal 1 bias command (torque) 919
C17 Terminal 1 bias (torque) 1919
E
C18 Terminal 1 gain command (torque) 920

Communication
Inverter
C19 Terminal 1 gain (torque) 1920
C8 Current output bias signal 930
C9 Current output bias current 1930
C10 Current output gain signal 931
C11 Current output gain current 1931
F

(RS/RS2 Instruction)
Communication
Non-Protocol
C38 Terminal 4 bias command (torque) 932
C39 Terminal 4 bias (torque) 1932
C40 Terminal 4 gain command (torque) 933
C41 Terminal 4 gain (torque) 1933
C42 PID display bias coefficient 934 G
C43 PID display bias analog value 1934

(FX2N-232IF)
Communication
Non-Protocol
C44 PID display gain coefficient 935
C45 PID display gain analog value 1935

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-117
FX Series PLC User's Manual - Data Communication Edition 9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 9.10 Second Parameter Specification Codes

9.10.10 A800 Series

1. Second parameter specification codes for parameter numbers Pr125, Pr126, C2 to C19 and
C38 to C41
Second parameter specification code
Parameter
Name [(decimal) value to be specified in S2 in IVRD/
No.
IVWR instruction for parameter number]
C2 Terminal 2 frequency setting bias frequency 902
C3 Terminal 2 frequency setting bias 1902
125 Terminal 2 frequency setting gain frequency 903
C4 Terminal 2 frequency setting gain 1903
C5 Terminal 4 frequency setting bias frequency 904
C6 Terminal 4 frequency setting bias 1904
126 Terminal 4 frequency setting gain frequency 905
C7 Terminal 4 frequency setting gain 1905
C12 Terminal 1 bias frequency (speed) 917
C13 Terminal 1 bias (speed) 1917
C14 Terminal 1 gain frequency (speed) 918
C15 Terminal 1 gain (speed) 1918
C16 Terminal 1 bias command (torque) 919
C17 Terminal 1 bias (torque) 1919
C18 Terminal 1 gain command (torque) 920
C19 Terminal 1 gain (torque) 1920
C8 Current output bias signal 930
C9 Current output bias current 1930
C10 Current output gain signal 931
C11 Current output gain current 1931
C38 Terminal 4 bias command (torque) 932
C39 Terminal 4 bias (torque) 1932
C40 Terminal 4 gain command (torque) 933
C41 Terminal 4 gain (torque) 1933
C42 PID display bias coefficient 934
C43 PID display bias analog value 1934
C44 PID display gain coefficient 935
C45 PID display gain analog value 1935

E-118
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.1 Practical Example 1

Common Items
10. Practical Program Examples
(FX3S, FX3G, FX3GC, FX3U, FX3UC)
B

N:N Network
This chapter explains practical programs for inverter communication.

10.1 Practical Example 1


This fundamental program example monitors operations of an inverter, controls operations of the inverter and C

Parallel Link
writes parameters to the inverter.
Programs can be made simpler and the communication time can be reduced by using the IVMC instruction as
long as the PLC and inverter support the IVMC instruction.
For details on PLC versions support the IVMC instruction, refer to section 9.9.
Refer to "9.9.2 Applicable inverters" for supported inverters.
D
10.1.1 System configuration example

Computer Link
An FX PLC (ch 1) is connected to an inverter.
FX3S, FX3G, FX3GC, FX3U, FX3UC Inverter

Communication
Inverter
Terminal resistor F

(RS/RS2 Instruction)
Communication
Non-Protocol
Distributor

10.1.2 Contents of operation


As an example of operation control, an inverter can be stopped (X000), rotated forward (X001) and rotated G
reverse (X002).

(FX2N-232IF)
Communication
Non-Protocol
By changing the contents of D10*1, the speed can be changed.
The contents of D10*1 can be changed from a sequence program or display unit.
*1. D11 when the IVMC instruction is used
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-119
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.1 Practical Example 1

10.1.3 Program example

1. Writing parameters to an inverter while the PLC is in RUN mode


M8002
SET M10
Initial pulse
The write
instruction is
driven
M10
FNC271 K0 H0FD H9696 K1 The inverter is reset
Driving of IVDR
write
instruction
FNC271 K0 H0FB H0*1 K1 Computer link
IVDR operation is
specified

FNC 12 K1 D200 The maximum


MOV P frequency (Pr. 1) is
specified

FNC 12 K12000 D201 The maximum


MOV P frequency (Pr. 1) is
set to "120 Hz"

FNC 12 K2 D202 The minimum


MOV P frequency (Pr. 2) is
specified

FNC 12 K500 D203 The minimum


MOV P frequency (Pr. 2) is
set to "5 Hz"

FNC 12 K7 D204 The acceleration time


MOV P (Pr. 7) is specified

FNC 12 K10 D205 The acceleration time


MOV P (Pr. 7) is set to "1 sec"

FNC 12 K8 D206 The deceleration time


MOV P (Pr. 8) is specified

FNC 12 K10 D207 The deceleration time


MOV P (Pr. 8) is set to "1 sec"

FNC274 K0 K4 D200 K1 The parameters are written


IVBWR*2 all at once
D200 to D207
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)
M8029
RST M10
Instruction execute
complete Driving of
write
instruction
*1. When using an E500 Series inverter, use "H2" to specify computer link operation.
*2. The FX3S, FX3G and FX3GC PLC does not support the IVBWR instruction. Use the IVWR instruction
instead.

E-120
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.1 Practical Example 1

A
2. Changing the speed using a sequence program

Common Items
When the IVMC instruction is not used

M8000
FNC 12 K6000 D10 "60 Hz" is written as
MOV P the initial value at
RUN
monitor Operation
startup B
speed

N:N Network
M17
FNC 12 K4000 D10 The operation speed
Command for MOV P "40 Hz" is written
switching to Operation
speed 1 speed
M18 C
FNC 12 K2000 D10 The operation speed

Parallel Link
Command for MOV P "20 Hz" is written
switching to Operation
speed 2 speed

FNC271 K0 H0ED D10 K1 The preset frequency*1 is


IVDR written to the inverter
D
Operation

Computer Link
speed

*1. For the V500 Series inverter, write "0" to instruction code HFF (Link parameter expansion setting) just
before writing the set frequency in the program.

When the IVMC instruction is used E

Communication
Inverter
M8000
FNC 12 K6000 D11 "60 Hz" is written as
MOV P the initial value at
RUN startup
monitor Operation
speed
M17
FNC 12 K4000 D11
F
The operation speed
MOV P

(RS/RS2 Instruction)
Communication
Non-Protocol
Command for "40 Hz" is written
switching to Operation
speed 1 speed
M18
FNC 12 K2000 D11 The operation speed
MOV P "20 Hz" is written
Command for
switching to Operation
G
speed 2 speed

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-121
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.1 Practical Example 1

3. Controlling operations of an inverter


When the IVMC instruction is not used
X000
SET M15 H0FA is set to "00H"
Operation stop
command input Operation
stop
X001 X000
RST M15 Operation stop is reset
Forward Operation stop by input X001 or X002
rotation command input Operation
command stop
input
X002

Reverse
rotation
command
input
M15 X001 X002
M21 b1 of H0FA is set to ON
Operation Forward Reverse
stop rotation rotation Forward rotation
command command command
input input
X002 X001
M22 b2 of H0FA is set to ON
Reverse Forward
rotation rotation Reverse rotation
command command command
input input
M8000
FNC271 Operation command is
K0 H0FA K2M20 K1 written
IVDR
RUN M27 to M20H0FA
monitor

When the IVMC instruction is used

X000
SET M15 H0F9 is set to "0000H"
Operation stop
command input Operation
stop
X001 X000
RST M15 Operation stop is reset
Forward Operation stop by input X001 or X002
rotation command input Operation
command stop
input
X002

Reverse
rotation
command
input
M15 X001 X002
M21 b1 of H0F9 is set to ON
Operation Forward Reverse
stop rotation rotation Forward rotation
command command command
input input
X002 X001
M22 b2 of H0F9 is set to ON
Reverse Forward
rotation rotation Reverse rotation
command command command
input input
M8000
FNC 12 The run command is set
K4M20 D10
MOV to the device for writing.
RUN
monitor Operation
command

E-122
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.1 Practical Example 1

A
4. Monitoring operations of an inverter

Common Items
When the IVMC instruction is not used
M8000 Inverter status is read
FNC270 K0 H079*1 K4M100 K1 H79M115 to M100
IVCK
RUN
monitor B

N:N Network
M100
Y000
Inverter is
operating Indicator
lamp, etc.

M101 C
Y001

Parallel Link
Forward
rotation Indicator
lamp, etc.

M102
Y002
Reverse
rotation Indicator D
lamp, etc.

Computer Link
M103
Y003 Contents of status
Up to (according to necessity)
frequency Indicator
lamp, etc.
M104
Y004
E

Communication
Inverter
Overload
is applied Indicator
lamp, etc.

M106
Y006
Frequency
is detected Indicator
lamp, etc.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
M107
Y007
Alarm
occurrence Indicator
lamp, etc.

FNC270 K0 H06F D50 K1 Output frequency


G
IVCK
monitor*2

(FX2N-232IF)
Communication
Non-Protocol
Frequency
monitor value

END

H
Communication
Programming

*1. S500, E500, A500, F500 and V500 Series inverters do not support the command code H79 (Inverter
status monitor (extended)). Use the command code H7A (Inverter status monitor).
*2. For the V500 Series inverter, write "0" to instruction code HFF (Link parameter expansion setting) just
before reading the output frequency monitor in the program.
I
Maintenance
Remote

Apx.A
models
Discontinued

E-123
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.1 Practical Example 1

When the IVMC instruction is used

M8000 The set frequency (RAM) and run command


FNC275 K0 H0000 D10 D20 K1 (expansion) are written.
IVMC The inverter status monitor (expansion) and
RUN
monitor output frequency (speed) are read.*1

FNC 12 The inverter status monitor (expansion) is


D20 K4M100
MOV stored in bit devices.

M100
Y000
Inverter is
operating Indicator
lamp, etc.

M101
Y001
Forward
rotation Indicator
lamp, etc.

M102
Y002
Reverse
rotation Indicator
lamp, etc.

M103
Y003 Contents of status
Up to (according to necessity)
frequency Indicator
lamp, etc.
M104
Y004
Overload
is applied Indicator
lamp, etc.

M106
Y006
Frequency
is detected Indicator
lamp, etc.

M107
Y007
Alarm
occurrence Indicator
lamp, etc.

FNC 12 D21 D50 Output frequency (speed)


MOV monitor

END

*1. The IVMC instruction reads the inverter status at the time of communication with the inverter, and
stores it in D .
Accordingly, the inverter status written by the IVMC instruction can be read when the next reading
instruction (IVCK, IVMC, etc.) is executed.

E-124
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

A
10.2 Practical Example 2

Common Items
This program executes the same control as practical example 1 shown earlier from one communication port
(ch1) to two inverters (Station number: 0 and 1).

10.2.1 System configuration example B

N:N Network
An FX PLC (ch1) is connected to two inverters (Station number: 0 and 1).
Inverter A Inverter B
FX3S, FX3G, FX3GC, FX3U, FX3UC (station number 0) (station number 1)

Parallel Link
Terminal resistor D

Computer Link
Distributor Distributor

10.2.2 Contents of operation


Differences from the practical example 1 are the following three points: E

Communication
Inverter
The PLC executes communication from one communication port to two inverters.
Status is not being read when a write to inverter command is given.
The PLC only writes when it detects that contents to be written have changed since last being written.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-125
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

10.2.3 Program example

1. Writing parameters to an inverter while the PLC is in RUN mode


M8002
FNC 40 M510 M607 Clearing devices backed up
ZRST against power interruption
Initial pulse
FNC 40 Clearing devices backed up
D510 D707
ZRST against power interruption

SET M10

The write
instruction
is driven
(station number 0)

SET M510

The write
instruction
is driven
*Inverter A (station number 0) (station number 1)

M10
FNC271 K0 H0FD H9696 K1 The inverter is reset
Driving of IVDR
(station number 0)
write Computer link operation
instruction FNC271 K0 H0FB H0*1 K1 is specified
(station IVDR
(station number 0)
number 0)
The maximum
FNC 12 K1 D200 frequency (Pr. 1) is
MOV P specified
(station number 0)

FNC 12 The maximum


K12000 D201 frequency (Pr. 1) is
MOV P set to "120 Hz"
(station number 0)

FNC 12 The minimum


K2 D202 frequency (Pr. 2) is
MOV P specified
(station number 0)
The minimum
FNC 12 K500 D203 frequency (Pr. 2) is
MOV P set to "5 Hz"
(station number 0)
FNC 12 The acceleration time
K7 D204 (Pr. 7) is specified
MOV P
(station number 0)
FNC 12 The acceleration time
K10 D205 (Pr. 7) is set to "1 sec"
MOV P
(station number 0)

FNC 12 The deceleration time


K8 D206 (Pr. 8) is specified
MOV P
(station number 0)
The deceleration time
FNC 12 K10 D207 (Pr. 8) is set to "1 sec"
MOV P
(station number 0)
FNC274 The parameters are written
K0 K4 D200 K1 all at once
IVBWR*2 D200 to D207
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)
M8029 (station number 0)
RST M10
Instruction execute
complete Driving of write
instruction
(station number 0)

E-126
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

Common Items
*Inverter B
(station number 1)

M510
FNC271 K1 H0FD H9696 K1 The inverter is reset B
Driving of IVDR
(station number 1)

N:N Network
write Computer link operation
instruction FNC271 K1 H0FB H0*1 K1 is specified
(station IVDR
(station number 1)
number 1)
The maximum
FNC 12 K1 D700
MOV P
frequency (Pr. 1) is
specified C
(station number 1)

Parallel Link
FNC 12 The maximum
K12000 D701 frequency (Pr. 1) is
MOV P set to "120 Hz"
(station number 1)

FNC 12
MOV P
K2 D702
The minimum
frequency (Pr. 2) is D
specified

Computer Link
(station number 1)
The minimum
FNC 12 K500 D703 frequency (Pr. 2) is
MOV P set to "5 Hz"
(station number 1)
FNC 12 K7 D704
The acceleration time
(Pr. 7) is specified
E
MOV P

Communication
Inverter
(station number 1)
FNC 12 The acceleration time
K10 D705 (Pr. 7) is set to "1 sec"
MOV P
(station number 1)
The deceleration time
FNC 12
MOV P
K8 D706 (Pr. 8) is specified
(station number 1)
F

(RS/RS2 Instruction)
Communication
Non-Protocol
The deceleration time
FNC 12 K10 D707 (Pr. 8) is set to "1 sec"
MOV P
(station number 1)
FNC274 The parameters are written
K1 K4 D700 K1 all at once
IVBWR*2 D700 to D707
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)
G

(FX2N-232IF)
Communication
Non-Protocol
M8029 (station number 1)
RST M510
Instruction execute
complete Driving of
write
instruction
(station
number 1)
H
Communication
Programming

*1. When using an E500 Series inverter, use "H2" to specify computer link operation.
*2. The FX3S, FX3G and FX3GC PLC does not support the IVBWR instruction. Use the IVWR instruction
instead.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-127
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

2. Changing the speed using a sequence program

*Inverter A
(station number 0)
M8000
FNC 12 K6000 D10 "60 Hz" is written as
MOV P the initial value at
RUN
monitor Operation startup.
speed
(station
number 0)
M17
FNC 12 K4000 D10 The operation speed is
MOV P written as "40 Hz"
Command for
switching to speed 1 Operation
(station number 0) speed
(station
number 0)
M18
FNC 12 K2000 D10 The operation speed is
MOV P written as "20 Hz"
Command for
switching to speed 2 Operation
(station number 0) speed
(station
number 0)
M8002
FNC 12 D10 D80
MOV
Initial pulse
Operation Operation
speed speed is
(station withdrawn
number 0) (station Change in the
number 0) operation speed
(D10) is
FNC228 detected
LD<> D10 D80 SET M11

Operation Operation speed The write


speed is withdrawn instruction
is driven
(station (station
(station
number 0) number 0)
number 0)

M11 The preset frequency*1


FNC271 K0 H0ED D10 K1
IVDR is written to the
The write inverter
instruction Operation
is driven speed
(station (station
number 0) number 0)
M8029
RST M11
Instruction execute
complete The write
instruction
is driven
(station
number 0)

*1. For the V500 Series inverter, write "0" to instruction code HFF (Link parameter expansion setting) just
before writing the set frequency in the program.

E-128
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

Common Items
*Inverter B
(station number 1)
M8000
FNC 12 K6000
RUN
MOV P
D510 "60 Hz" is written as
the initial value at B
monitor Operation startup.

N:N Network
speed
(station
number 1)
M517
FNC 12 K4000 D510 The operation speed is
MOV P written as "40 Hz"
Command for
switching to speed 1 Operation
speed
C
(station number 1)

Parallel Link
(station
number 1)
M518
FNC 12 K2000 D510 The operation speed is
MOV P written as "20 Hz"
Command for
switching to speed 2 Operation
(station number 1) speed
(station
D

Computer Link
number 1)
M8002
FNC 12 D510 D580
MOV
Initial pulse
Operation Operation
speed speed is
(station withdrawn
number 1) (station Change in the E
number 1) operation speed

Communication
Inverter
(D510) is
FNC228 detected
LD<> D510 D580 SET M511

Operation Operation speed The write


speed is withdrawn instruction
is driven
(station (station
number 1) number 1)
(station
number 1)
F

(RS/RS2 Instruction)
Communication
Non-Protocol
M11 The preset frequency*1
FNC271 K1 H0ED D510 K1
IVDR is written to the
The write inverter
instruction Operation
is driven speed
(station
number 1)
(station
number 1)
G

(FX2N-232IF)
Communication
Non-Protocol
M8029
RST M511
Instruction execute
complete The write
instruction
is driven
(station
number 1) H
Communication
Programming

*1. For the V500 Series inverter, write "0" to instruction code HFF (Link parameter expansion setting) just
before writing the set frequency in the program.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-129
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

3. Controlling operations of an inverter

* Inverter A
(station number 0)
X000
SET M15 H0FA is set to "00H"
Operation stop
command input Operation
stop
(station number 0) (station
number 0)
X001 X000
RST M15 Operation stop is reset
Forward Operation stop by input X001 or X002
rotation command input Operation
command (station number 0) stop
input (station
(station number 0)
number 0)
X002

Reverse rotation
command input
(station number 0)
M15 X001 X002
M21 b1 of H0FA is set to ON
Operation Forward Reverse
stop rotation rotation Forward rotation
(station command command command
number 0) input input (station number 0)
(station (station
number 0) number 0)
X002 X001
M22 b2 of H0FA is set to ON
Reverse Forward
rotation rotation Reverse rotation
command command command
input input (station number 0)
(station (station
number 0) number 0)
M8002 FNC 12
MOV K2M20 D81
Initial pulse Changes in the
Operation
operation
command is commands
withdrawn (M27 to M20) are
(station detected
number 0)
FNC228
LD<> K2M20 D81 SET M12
Operation Driving of
command is write
withdrawn instruction
(station (station
number 0) number 0)
M12 FNC271
IVDR K0 H0FA K2M20 K1 Operation commands
Driving of are written.
write M27 to M20H0FA
instruction
(station M8029
number 0) RST M12
Instruction execute
complete Driving of write
instruction
(station
number 0)

E-130
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

Common Items
* Inverter B
(station number 1)
X010
SET M515 H0FA is set to "00H"
Operation stop
(command input Operation
stop
B
station number 1)

N:N Network
(station
number 1)
X011 X010
RST M515 Operation stop is reset
Forward Operation stop by input X011 or X012
rotation command input Operation
stop
command (station number 1)
input
(station
(station
number 1)
C

Parallel Link
number 1)
X012

Reverse rotation
command input
(station number 1)
M515 X011 X012
M521 b1 of H0FA is set to ON
D
Forward Reverse

Computer Link
Operation
stop rotation rotation Forward rotation
(station command command command
number 1) input input (station number 1)
(station (station
number 1) number 1)
X012
Reverse
X011
Forward
M522 b2 of H0FA is set to ON E

Communication
Inverter
rotation rotation Reverse rotation
command command command
input input (station number 1)
(station (station
number 1) number 1)
M8002 FNC 12
MOV K2M520 D581
Initial pulse
Operation Changes in the
F
operation

(RS/RS2 Instruction)
Communication
Non-Protocol
command is commands
withdrawn (M527 to M520) are
(station detected
number 1)
FNC228
LD<> K2M520 D581 SET M512
Operation Driving of G
command is write

(FX2N-232IF)
Communication
Non-Protocol
withdrawn instruction
(station (station
number 1) number 1)
M512 FNC271
IVDR K1 H0FA K2M520 K1 Operation commands
Driving of
write
are written.
M527 to M520H0FA H
instruction
Communication
Programming

(station M8029
number 1) RST M512
Instruction execute
complete Driving of write
instruction
(station
number 1) I
Maintenance
Remote

Apx.A
models
Discontinued

E-131
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

4. Monitoring operations of an inverter

* Inverter A
(station number 0)

M10 M11 M12


MC N0 M70 While data is not
Driving of Driving of Driving of written to an inverter,
write write write the status is read
instruction instruction instruction
(station (station (station
number 0) number 0) number 0)

N0 M70

M8000 FNC270 K0 H079*1 K4M100 K1 Inverter status is read


IVCK
RUN (station number 0)
monitor Inverter is
operating H79M115 to M100
(station number 0)
M100
Y000
Inverter
running Indicator
(station number 0) lamp, etc.
M101
Y001
Forward
rotation Indicator
(station number 0) lamp, etc.
M102
Y002
Reverse
rotation Indicator
(station number 0) lamp, etc.
M103
Y003 Contents of status
Up to (according to necessity)
frequency Indicator
(station number 0) lamp, etc.
M104
Y004
Overload
is applied Indicator
(station number 0) lamp, etc.
M106
Y006
Frequency
is detected Indicator
(station number 0) lamp, etc.
M107
Y007
Alarm
occurrence Indicator
(station number 0) lamp, etc.

FNC270 K0 H06F D50 K1


IVCK Output frequency monitor *2
(station number 0)
Frequency
monitor value
(station number 0)

MCR N0

*1. S500, E500, A500, F500 and V500 Series inverters do not support the command code H79 (Inverter
status monitor (extended)). Use the command code H7A (Inverter status monitor).
*2. For the V500 Series inverter, write "0" to instruction code HFF (Link parameter expansion setting) just
before reading the output frequency monitor in the program.

E-132
FX Series PLC User's Manual - Data Communication Edition 10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Inverter Communication 10.2 Practical Example 2

Common Items
* Inverter B
(station number 1)

M510 M511 M512


MC N0 M570
Driving of
write
Driving of
write
Driving of
write
While data is not
written to an inverter,
the status is read
B

N:N Network
instruction instruction instruction
(station (station (station
number 1) number 1) number 1)

N0 M570

M8000 FNC270 K1 H079*1 K4M600 K1 Inverter status is read


C
IVCK

Parallel Link
RUN (station number 1)
monitor Inverter is
operating H79M615 to M600
(station number 1)
M600
Y010
Inverter
running
(station number 1)
Indicator
lamp, etc.
D

Computer Link
M601
Y011
Forward
rotation Indicator
(station number 1) lamp, etc.
M602

Reverse
Y012 E
rotation Indicator

Communication
Inverter
(station number 1) lamp, etc.
M603
Y013 Contents of status
Up to (according to necessity)
frequency Indicator
(station number 1)
M604
lamp, etc.
F
Y014

(RS/RS2 Instruction)
Communication
Non-Protocol
Overload
is applied Indicator
(station number 1) lamp, etc.
M606
Y016
Frequency
is detected
(station number 1)
Indicator
lamp, etc.
G

(FX2N-232IF)
Communication
Non-Protocol
M607
Y017
Alarm
occurrence Indicator
(station number 1) lamp, etc.

FNC270
IVCK K1 H06F D550 K1 Output frequency monitor *2 H
(station number 1)
Communication
Programming

Frequency
monitor value
(station number 1)

MCR N0

END
I
Maintenance
Remote

*1. S500, E500, A500, F500 and V500 Series inverters do not support the command code H79 (Inverter
status monitor (extended)). Use the command code H7A (Inverter status monitor).
*2. For the V500 Series inverter, write "0" to instruction code HFF (Link parameter expansion setting) just
before reading the output frequency monitor in the program.
Apx.A
models
Discontinued

E-133
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Inverter Communication 11.1 Checking FX PLC Version Applicability (FX2N and FX2NC Series)

11. Troubleshooting
This chapter explains troubleshooting and error codes.

11.1 Checking FX PLC Version Applicability (FX2N and FX2NC Series)


Verify that the FX PLC main unit is an applicable version for inverter communication.
For version applicability, refer to Section 1.3.

11.2 Checking Communication Status Based on LED Indication


Check the status of the "RD(RXD)" and "SD(TXD)" indicator LEDs provided in the optional equipment.

LED status
Operation status
RD SD
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received
Off Off Data is not sent nor received.

11.3 Checking Installation

1. Mounting status
If the communication equipment is not securely connected to the PLC, communication is not possible.
For mounting method, refer to the respective communication equipment manual.

2. Power supply (for FX0N-485ADP)


The FX0N-485ADP requires a driving power supply. Verify that the power supply is provided correctly.

3. Wiring
Verify that the wiring to all communication equipment is correct. If the communication equipment is wired
incorrectly, communication is not possible.
For wiring method check, refer to Chapter 4.

11.4 Checking Sequence Program

1. Communication setting in the sequence program


Verify that N:N Network (D8173 to D8180) and parallel link (M8070 and M8071) are not set.
After changing any setting, make sure to turn OFF the PLC power, and then turn the power ON again.

2. Communication setting using parameters


Verify that the communication settings using parameters are correct. If the contents of the parameters do not
agree, communication will not function correctly.
After changing any parameters, make sure to turn OFF the PLC power, and then turn the power ON again.

3. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in inverter
communication. After changing the setting, make sure to reboot the PLC's power.

E-134
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Inverter Communication 11.4 Checking Sequence Program

A
4. Presence of VRRD and VRSC instructions

Common Items
1) Except FX3G, FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
2) In FX3G PLC
- In the case of the 14 points and 24-point type B
Verify that the VRRD and VRSC instructions are not used in the program.

N:N Network
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions. C
After deleting these instructions, turn OFF the PLC power, and then turn the power ON again.

Parallel Link
3) In FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power. D

Computer Link
5. Presence of RS instruction (in FX2N and FX2NC PLCs)
Verify that the RS instruction is not used in the program.
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.

6. Presence of RS and RS2 instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel. E
If these instructions are used for the same channel, delete them, turn OFF the PLC power, and then turn the

Communication
Inverter
power ON again.

7. Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.
F
8. Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3UC PLCs)
Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the
same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.
G
11.4.1 Checking inverter operation status

(FX2N-232IF)
Communication
Non-Protocol
1. When the operation mode of an inverter is not changed over to computer link mode
1) Verify that the inverter is set to the external operation mode.
2) Verify that no signal is being input to the external terminals STF and STR. H
3) Verify that the correct operation mode changeover program is being executed.
Communication
Programming

2. When an inverter cannot be started even in computer link mode


1) Verify that the program for starting the inverter is executed correctly.
2) Verify that the operation command and speed command are set correctly.
3) Verify that the allowable communication time interval is set correctly. I
Maintenance
Remote

3. When an inverter is stopped by an alarm during operation due to defective communication


1) Verify that a communication cable is connected correctly between the PLC and the inverter.
(Check for poor contact or wire breakage.)
2) Verify that a sequence program is created so that communication is executed with each inverter within a
constant cycle. Set the communication check time interval to a large value, and check the communication Apx.A
status.
models
Discontinued

3) Verify that the allowable communication time interval is set correctly.


4) Verify that terminal resistors are wired correctly.

E-135
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Inverter Communication 11.5 Checking Absence/Presence of Errors

11.5 Checking Absence/Presence of Errors


Verify that the error flag is not ON.
If the error flag is ON, check the error code and take proper countermeasures.
For error codes, refer to the next page.

11.6 Error Codes


When a communication error occurs, the error flag turns ON, and the error code is stored in the data register.
For error codes, refer to the table below.

1. Error storing devices


FX Series Error flag Data register for storing error code
FX2N,FX2NC M8156 D8156
ch1 ch2 ch1 ch2
FX3S,FX3G,FX3GC,FX3U,FX3UC
M8152 M8157 D8152 D8157

2. Error code list


Error
Inverter
code Contents of error
operation
(DEC)
0 Normal end (No Errors)
1 Inverter did not give response.
2 Timeout error Sending from inverter was aborted midway.
3 Station number error Unspecified station gave response.
4 Sum check error The sum of data sent back by the inverter did not match.
In writing or reading a parameter, an improper parameter number
Parameter number was specified.
5
specification error At this time, error code (K6706) is set to D8067.
K6706: Out-of-range data value for operand in applied instruction.
Because the port is being used for another communication type, it
Communication port cannot be used for communication with the inverter.
6 occupied by another At this time, error code (K6762) is set to D8067.
communication type K6762: The port specified in inverter communication instruction is
being used by another communication type.
A value outside the allowable range is set to the station number.
Station number
7 At this time, error code (K6706) is set to D8067.
outside setting range
K6706: Out-of-range data value for operand in applied instruction.
Sending timeout
8 Sending to the inverter was not completed within the specified time.
error*1
9 Received data error*1 Wrong data was received from the inverter.
Inverter sent the error code H0.
256 Computer NAK error The number of retries exceeded the allowable number because of an
error in the transfer request data.
Inverter sent the error code H1. When errors
257 Parity error have occurred
The contents are different from the specified parity.
consecutively
Inverter sent the error code H2.
beyond the
258 Sum check error The sum check code in the computer is different from the sum value
allowable
calculated from the data received by the inverter.
number of
Inverter sent the error code H3. retries, inverter
Syntax error is included in the data received by the inverter, is brought to an
259 Protocol error
receiving of data was not completed within the specified time, or CR/ alarm stop.
LF does not agree with the parameters.
Inverter sent the error code H4.
260 Framing error
The stop bit length is different from the initial set value.

E-136
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Inverter Communication 11.6 Error Codes

A
Error

Common Items
Inverter
code Contents of error
operation
(DEC)
When errors
have occurred

Inverter sent the error code H5.


consecutively
beyond the
B

N:N Network
261 Overrun error Before receiving the completed data in the inverter, the computer allowable
sent the next set of data. number of
retries, inverter
is brought to an
alarm stop.

262 Undefined
Inverter sent the error code H6.

C
Not defined currently in inverter.

Parallel Link
Inverter does
not accept
Inverter sent the error code H7.
received data,
263 Character error An unused character (other than 0 to 9, A to F and control codes)
but is not
was received.
brought to an
alarm stop. D

Computer Link
Inverter sent the error code H8.
264 Undefined
Not defined currently in inverter.

Inverter sent the error code H9.
265 Undefined
Not defined currently in inverter.
Inverter sent the error code HA.
266 Mode error A parameter was written in a mode other than computer link mode, Inverter does E
or while the inverter was operating.

Communication
Inverter
not accept
Inverter sent the error code HB. Instruction code error. received data,
267 Instruction code error
Non-existing instruction code was specified. but is not
Inverter sent the error code HC. brought to an
268 Data range error In writing a parameter or operation frequency, data outside the alarm stop.
allowable range was specified. F
Inverter sent the error code HD.

(RS/RS2 Instruction)
Communication
Non-Protocol
269 Undefined
Not defined currently in inverter.
Inverter sent the error code HE.
270 Undefined
Not defined currently in inverter.
Inverter sent the error code HF.
271 Undefined
Not defined currently in inverter. G
*1. This error code is supported only in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-137
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Inverter Communication 11.6 Error Codes

3. IVMC instruction error codes


When errors occur in the send data of the IVMC instruction, the following error codes are stored.
It is recommended to check error codes in hexadecimal.
Refer to the error code list earlier in this section for other errors.
Error code
(HEX)
IVMC Send Send
instruction data2 data1 Contents of error Inverter operation
error error error
information information information
b15 to b8 b7 to b4 b3 to b0
No error has occurred in both send data 1 and
H00 H0 H0 send data 2.
Normal end
The inverter sent error code HA to send data 1 of
the IVMC instruction.
A parameter was written in a mode other than
HA
computer link mode or while the inverter was
operating. The inverter did not accept the The inverter accepts
received data, but was not stopped by alarm. data corresponding to
H0 send data 2, and is not
The inverter sent error code HB to send data 1 of
brought to an alarm
HB the IVMC instruction.
stop.
Non-existing instruction code was specified.
The inverter sent error code HC to send data 1 of
HC the IVMC instruction.
Data outside the allowable range was specified.
The inverter sent error code HA to send data 2 of
the IVMC instruction.
A parameter was written in a mode other than
H02 HA
computer link mode or while inverter was
operating. The inverter did not accept the The inverter accepts
received data, but was not stopped by alarm. data corresponding to
H0 send data 1, and is not
The inverter sent error code HB to send data 2 of
brought to an alarm
HB the IVMC instruction.
stop.
Non-existing instruction code was specified.
The inverter sent error code HC to send data 2 of
HC the IVMC instruction.
Data outside the allowable range was specified.
The inverter does not
The inverter sent error codes to both send data 1
accept data
and send data 2 of the IVMC instruction.
corresponding to send
HA to HC HA to HC Refer to the contents of the error of the
data 1 and 2, but is not
corresponding error codes of send data 1 and
brought to an alarm
send data 2 for details of error codes.
stop.

E-138
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.1 Related Device List (FX2N, FX2NC)

Common Items
12. Related Data
This chapter shows various technical information. B

N:N Network
12.1 Related Device List (FX2N, FX2NC)
The tables below show special auxiliary relays and special data registers used in inverter communication
(EXTR K10 to EXTR K13).
C
1. Bit devices

Parallel Link
Device No. Name Description R/W
Turns ON when execution of EXTR instruction is completed, and remains
Instruction execution ON for 1 scan.
M8029 R
complete Turns ON also when execution of instruction is completed if M8156
(communication error or parameter error) turns ON. D

Computer Link
Extension ROM
M8104 Remains ON while an extension ROM cassette is attached. R
cassette check
M8154 Unused R
Communication port
M8155 Remains ON while the communication port is used by an EXTR instruction. R
busy
Communication error
E
M8156 Turns ON when a communication error is caused by an EXTR instruction. R

Communication
Inverter
or parameter error
Communication error
M8157 Turns ON when a communication error is caused by an EXTR instruction. R
latch*1

R: Read only (used as a contact in program)


*1. Cleared when the PLC mode is changed from STOP to RUN. F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Word devices
Device No. Name Description R/W
Extension ROM
D8104 Stores the type code of an extension ROM cassette (value: K1). R
cassette type code
Extension ROM Stores the version of an extension ROM cassette
G
D8105 R

(FX2N-232IF)
Communication
Non-Protocol
cassette version (value: K100 = Ver. 1.00).
Inverter response
D8154 Sets the inverter response waiting time. R/W
waiting time
Step number of
D8155 instruction using the Stores the step number of EXTR instruction using the communication port. R
communication port H
Communication
Programming

Stores an error code when a communication error is caused by an EXTR


D8156 Error code*1 instruction.
R

Error occurrence Stores the instruction step number in which a communication error has
D8157 R
step number latch*1 occurred. (Stores K-1 when no error has occurred.)

R: Read only I
W: Write only
Maintenance
Remote

R/W: Read or Write


*1. Cleared when the PLC mode is changed from STOP to RUN.

Apx.A
models
Discontinued

E-139
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.2 Details of Related Devices (FX2N, FX2NC)

12.2 Details of Related Devices (FX2N, FX2NC)


The following devices are special devices used in inverter communication.

12.2.1 Instruction execution complete [M8029]


When execution of an inverter communication instruction is completed, this device turns ON.

1. Detailed contents
When execution of an inverter communication instruction is completed, M8029 turns ON, and remains ON for
1 scan.
When an error occurs in an inverter communication instruction, M8029 turns ON.

2. Cautions on use
M8029 is used as the execution complete flag for other instructions (such as positioning instructions).
When using M8029, provide the contact just under the instruction whose execution completion is to be
checked.

12.2.2 Extension ROM cassette check [M8104]


This device remains ON while an extension ROM cassette is attached.

1. Detailed contents
M8104 remains ON while an extension ROM cassette is attached.
- FX2N . . . . . . FX2N-ROM-E1
- FX2NC . . . . . FX2NC-ROM-CE1

2. Cautions on use
While M8104 is OFF, EXTR instructions cannot be used.

12.2.3 Communication port busy [M8155]


This device remains ON while the communication port is being used by an EXTR instruction.

1. Detailed contents
M8155 remains ON while communication with an inverter is executed by an EXTR instruction.
When M8155 turns ON, D8155 stores the step number of an instruction using the communication port.
While M8155 is ON, another EXTR instruction cannot be executed.

12.2.4 Communication error or parameter error [M8156]


This device turns ON when an error is caused in communication with an inverter by an EXTR instruction.

1. Detailed contents
M8156 turns ON when an error is caused in communication with an inverter by an EXTR instruction.
When M8156 turns ON, D8156 stores the error code.

2. Cautions on use
M8156 is set to OFF by an EXTR instruction located in the next step in the program.
When using M8156, provide it just under the EXTR instruction whose error is to be checked.

E-140
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.2 Details of Related Devices (FX2N, FX2NC)

A
12.2.5 Communication error latch [M8157]

Common Items
This device turns ON when the communication error flag M8156 turns ON.

1. Detailed contents
M8157 turns ON when a communication error occurs and M8156 turns ON.
When M8157 turns ON, D8157 stores the step number in which the error has occurred.
B

N:N Network
2. Cautions on use
M8157 remains ON until the PLC mode is changed from STOP to RUN.

12.2.6 Extension ROM cassette type code [D8104]


C
This device stores the type code of an extension ROM cassette.

Parallel Link
1. Detailed contents
While the following ROM is attached to an FX PLC, D8104 stores its model code.
- FX2N . . . . . . FX2N-ROM-E1 (model code: K1)
- FX2NC . . . . . FX2NC-ROM-CE1 (model code: K1) D

Computer Link
12.2.7 Extension ROM cassette version [D8105]
This device stores the version of an extension ROM cassette.

1. Detailed contents
While an extension ROM is attached, D8105 stores its version information (K100 = Ver. 1.00).
E

Communication
Inverter
12.2.8 Inverter response waiting time [D8154]
This device sets the response waiting time of an inverter.

1. Detailed contents F
D8154 sets the response waiting time of an inverter.

(RS/RS2 Instruction)
Communication
Non-Protocol
Set a value within the range from "1 to 32767" (unit: 100 ms) to D8154.
When "0" or a negative value is set, it is handled as "100 ms".

12.2.9 Step number of instruction using communication port [D8155]


G
This device stores the step number of an instruction occupying the communication port.

(FX2N-232IF)
Communication
Non-Protocol
1. Detailed contents
D8155 stores the step number of EXTR instruction using the communication port.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-141
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.2 Details of Related Devices (FX2N, FX2NC)

12.2.10 Error code [D8156]


This device stores the error code when an error is caused in communication with an inverter by an EXTR
instruction.

1. Detailed contents
D8156 stores one of the following error codes when an error is caused in communication with an inverter by
the EXTR instruction.
Error
code Contents of error Inverter operation
(DEC)
0 Normal end (no error)
1 Inverter did not give response.
Timeout error. This code interlocks with M8156. Sending from inverter was aborted
2
midway through.
3 An unspecified station gave response.
4 The sum of data sent back by the inverter did not match.
In writing or reading a parameter, an improper parameter number was specified. At
5
this time, the error code K6706 is set to D8067.
Because the port is being used for another communication, it cannot be used for
6
communication with the inverter. At this time, the error code K6762 is set to D8067.
A value outside the allowable range is set to the station number.
7
At this time, error code (K6706) is set to D8067.
Inverter sent the error code H0. Computer NAK error.
256 An error was included in the transfer request data from the computer beyond the
allowable number of retries.
Inverter sent the error code H1. Parity error.
257
The contents are different from the specified parity.
Inverter sent the error code H2. Sum check error. When errors have
258 The sum check code in the computer is different from the sum value calculated from occurred
the data received by inverter. consecutively beyond
Inverter sent the error code H3. Protocol error. the allowable number
Syntax error is included in the data received by the inverter, and the receiving of of retries, inverter is
259
data has not been completed within the specified time, or CR/LF does not agree brought to an alarm
with the parameters. stop.
Inverter sent the error code H4. Framing error.
260
The stop bit length is different from the initial set value.
Inverter sent the error code H5. Overrun error.
261 Before receiving the completed data in the inverter, the computer sent the next set
of data.
Inverter sent the error code H6.
262
Not defined currently in inverter.
Inverter sent the error code H7. Character error. Inverter does not
263
An unused character (other than 0 to 9, A to F and control codes) was received. accept the received
data, but is not
Inverter sent the error code H8. brought to an alarm
264
Not defined currently in inverter. stop.
Inverter sent the error code H9.
265
Not defined currently in inverter.

E-142
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.2 Details of Related Devices (FX2N, FX2NC)

A
Error

Common Items
code Contents of error Inverter operation
(DEC)
Inverter sent the error code HA. Mode error.
A parameter was written in a mode other than computer link mode, or while inverter
266
was operating. Inverter does not accept the received data, but is not stopped by Inverter does not
alarm.
B
accept the received

N:N Network
Inverter sent the error code HB. Instruction code error. data, but is not
267
Non-existing instruction code was specified. brought to an alarm
Inverter sent the error code HC. Data range error. stop.
268 In writing a parameter or operation frequency, data outside the allowable range was
specified. Inverter does not accept the received data, but is not stopped by alarm.
Inverter sent the error code HD.
C
269

Parallel Link
Not defined currently in inverter.
Inverter sent the error code HE.
270
Not defined currently in inverter.
Inverter sent the error code HF.
271
Not defined currently in inverter.
D

Computer Link
12.2.11 Error occurrence step number latch [D8157]
This device stores the step number in which the communication error has occurred.

1. Detailed contents E

Communication
Inverter
When M8157 turns ON, D8157 stores the step number in which communication error has occurred.
When errors have occurred in two or more instructions, D8157 holds the step number of the instruction in
which an error occurred first.
When no error has occurred, D8157 stores "-1".

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-143
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.3 Related Device List (FX3S, FX3G, FX3GC, FX3U, FX3UC)

12.3 Related Device List (FX3S, FX3G, FX3GC, FX3U, FX3UC)


The tables below show special auxiliary relays and special data registers used in inverter communication
(FNC270 (IVCK) to FNC275 (IVMC)).
The FX3G PLC (14-point, 24-point type) and FX3S PLC does not support ch2.

1. Bit devices
Device No.
Name Description R/W
ch1 ch2
Turns ON when the execution of inverter
communication instruction is completed, and remains
ON for 1 scan.
M8029 Instruction execution complete R
Turns ON also when the execution of instruction is
completed if inverter communication error flag
(M8152 or M8157) turns ON.
Turns ON when an error occurs in any type of
M8063 M8438 Serial communication error*1 R
communication.
Remains ON while inverter communication is being
M8151 M8156 Inverter communicating R
executed.
Turns ON when an error occurs during
M8152 M8157 Inverter communication error*2 R
communication with an inverter.
Turns ON when an error occurs during
M8153 M8158 Inverter communication error latch*2 R
communication with an inverter.
Turns ON when an error is caused by IVBWR
M8154 M8159 IVBWR instruction error*2, *3 R
instruction.

R: Read only (used as a contact in program)


*1. Cleared when PLC power supply is turned from OFF to ON.
*2. Cleared when the PLC mode is changed from STOP to RUN.
*3. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.

2. Word devices
Device No.
Name Description R/W
ch1 ch2
D8063 D8438 Error code for serial communication*4 Stores a communication error code. R
Inverter communication response Sets the response wait time of inverter
D8150 D8155 R/W
waiting time*4 communication.
Step number of instruction executing Stores the step number of an instruction executing
D8151 D8156 R
inverter communication inverter communication.
Error code for inverter
D8152 D8157 Stores an inverter communication error code. R
communication*5
Inverter communication error Latches a step number in which an inverter
D8153 D8158 R
occurring step latch*5 communication error has occurred.*7
Error parameter number of IVBWR Stores a parameter number in which an IVBWR
D8154 D8159 R
instruction*5*6 instruction error has occurred.
D8419 D8439 Operation mode display Stores the communication type being used. R

R: Read only
W: Write only
R/W: Read or Write
*4. Cleared when PLC power supply is turned from OFF to ON.
*5. Cleared when the PLC mode is changed from STOP to RUN.
*6. The IVBWR instruction is supported only in FX3U and FX3UC PLCs.
*7. Updated only for the first error occurrence, and not for the second error occurrence or later.

E-144
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

A
12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

Common Items
The following devices are special devices used in inverter communications.
The FX3G PLC (14-point, 24-point type) and FX3S PLC does not support ch2.

12.4.1 Instruction execution complete [M8029] B

N:N Network
When execution of an inverter communication instruction is completed, this device turns ON.

1. Detailed contents
When execution of an inverter communication instruction is completed, M8029 turns ON, and remains ON for
1 scan.
When an error occurs in an inverter communication instruction, M8029 turns ON, and remains ON for 1 scan
C

Parallel Link
in the same way.

2. Cautions on use
M8029 is used as the execution complete flag for other instructions (such as positioning instructions).
When using M8029, provide the contact just under the instruction whose execution completion is to be
checked. D

Computer Link
12.4.2 Serial communication error [M8063 and M8438]
These devices turn ON when an error occurs during communication with an inverter.

1. Detailed contents
M8063 or M8438 turns ON when a parity error, overrun error or framing error occurs during communication
E

Communication
Inverter
with inverters or when on inverter communication error occurs.
M8063 turns ON when an error occurs during communication using ch1. When M8063 turns ON, D8063
stores the error code.
M8438 turns ON when an error occurs during communication using ch2. When M8438 turns ON, D8438
stores the error code.
F
2. Cautions on use

(RS/RS2 Instruction)
Communication
Non-Protocol
Serial communication errors are not cleared even when communication is restored.
Clear them by turning off and on the PLC.

12.4.3 Inverter communication ON [M8151 and M8156]


G
These devices remain ON while the communication port is used by an inverter communication instruction.

(FX2N-232IF)
Communication
Non-Protocol
1. Detailed contents
M8151 or M8156 remains ON while communication with an inverter is executed by an inverter communication
instruction.
M8151 remains ON while communication port ch1 is used. While M8151 remains ON, D8151 stores the step
number of an instruction using the communication port. H
M8156 remains ON while communication port ch2 is used. While M8156 remains ON, D8156 stores the step
Communication
Programming

number of an instruction using the communication port.

2. Cautions on use
While M8151 or M8156 remains ON, another inverter communication instruction cannot be executed.
I
Maintenance
Remote

Apx.A
models
Discontinued

E-145
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

12.4.4 Inverter communication error [M8152, M8153, M8157 and M8158]


These devices turn ON when an error occurs in an inverter communication instruction.

1. Detailed contents
M8152 or M8157 turn ON when an error occurs in an inverter communication instruction.
M8152 turn ON when an error occurs during communication using communication port ch1. When M8152
turn ON, D8152 stores the error code and D8153 stores the error step number.
M8157 turn ON when an error occurs during communication using communication port ch2. When M8157
turn ON, D8157 stores the error code and D8158 stores the error step number.
To D8152, D8153, D8157 and D8158 are updated only for the first error occurrence, and not for the second
error occurrence or later.

2. Cautions on use
M8152 and M8157 do not turn OFF even if the communication recovers its normal status. Clear them by
switching the PLC mode from STOP to RUN.

12.4.5 IVBWR instruction error [M8154 and M8159] (only in FX3U and FX3UC PLCs)
These devices turn ON when an error occurs in IVBWR instruction.

1. Detailed contents
M8154 or M8159 turns ON when a parameter number of set value specified in IVBWR instruction is outside
the allowable range.
M8154 turns ON when an error occurs in IVBWR instruction using communication port ch1. When M8154
turns ON, D8154 stores the rejected parameter number.
M8159 turns ON when an error occurs in IVBWR instruction using the communication port ch2. When M8159
turns ON, D8159 stores the rejected parameter number.

2. Cautions on use
IVBWR instruction errors are not cleared even when communication is restored.
Clear them by turning off and on the PLC.

12.4.6 Serial communication error code [D8063 and D8438]


These devices store the error code when the serial communication error flag turns ON.

1. Detailed contents
When an error occurs in an inverter communication instruction, D8063 or D8438 stores one of the following
error codes.
Error code
ch1 ch2 Contents
D8063 D8438
6301 3801 Parity error, framing error or overrun error
6320 3820 Inverter communication error

2. Cautions on use
Serial communication error codes are not cleared even when communication is restored.
Clear them by switching the PLC mode from STOP to RUN.

12.4.7 Inverter response waiting time [D8150 and D8155]


These devices set the response waiting time of the inverter.

1. Detailed contents
Set the response waiting time of an inverter.
When using communication port ch1, set a value to D8150.
When using communication port ch2, set a value to D8155.
Set a value within the range from "1 to 32767" (unit: 100 ms).
If "0" or negative value is set, it is handled as "100 ms".

E-146
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

A
12.4.8 Step number of instruction using communication port [D8151 and D8156]

Common Items
These devices store the step number of the instruction occupying the communication port.

1. Detailed contents.
D8151 or D8156 stores the step number of the inverter communication instruction using the communication
port.
B

N:N Network
D8151 stores the step number using communication port ch1.
D8156 stores the step number using communication port ch2.

2. Cautions on use
A decimal value without sign is stored as the step number in D8151 and D8156.
C
12.4.9 Inverter communication error code [D8152 and D8157]

Parallel Link
These devices store an error code when a communication error is caused by an inverter communication
instruction.

1. Detailed contents
Special data registers shown below respectively store inverter communication errors, depending on each
D

Computer Link
communication port.
D8152 stores the error code of an error in communication using communication port ch1.
D8157 stores the error code of an error in communication using communication port ch2.

2. Error codes
The following error codes are stored.
E

Communication
Inverter
Error
code Contents of error Inverter operation
(DEC)
0 Normal end (no error)
1 Inverter did not give response. F
Timeout error. This code interlocks with M8156. Sending from inverter was

(RS/RS2 Instruction)
Communication
Non-Protocol
2
aborted midway through.
3 An unspecified station gave response.
4 The sum of data sent back by the inverter did not match.
In writing or reading a parameter, an improper parameter number was specified.
5
At this time, the error code K6706 is set to D8067. G

(FX2N-232IF)
Communication
Non-Protocol
Because the port is being used for another communication type, it cannot be
6 used for communication with the inverter. At this time, the error code K6762 is
set to D8067.
A value outside the allowable range is set to the station number.
7
At this time, error code (K6706) is set to D8067.
8 Sending to the inverter was not completed within the specified time. H
Communication
Programming

9 Wrong data was received from the inverter.

I
Maintenance
Remote

Apx.A
models
Discontinued

E-147
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

Error
code Contents of error Inverter operation
(DEC)
Inverter sent the error code H0. Computer NAK error.
256 An error was included in the transfer request data from the computer beyond the
allowable number of retries.
Inverter sent the error code H1. Parity error.
257
The contents are different from the specified parity.
Inverter sent the error code H2. Sum check error.
258 The sum check code in the computer is different from the sum value calculated When errors have
from the data received by the inverter. occurred consecutively
beyond the allowable
Inverter sent the error code H3. Protocol error. number of retries, inverter
Syntax error is included in the data received by the inverter, and the receiving of is brought to an alarm
259
data was not completed within the specified time, or CR/LF does not agree with stop.
the parameters.
Inverter sent the error code H4. Framing error.
260
The stop bit length is different from the initial set value.
Inverter sent the error code H5. Overrun error.
261 Before receiving the completed data in the inverter, the computer sent the next
set of data.
Inverter sent the error code H6.
262
Not defined currently in inverter.
Inverter does not accept
Inverter sent the error code H7. Character error. the received data, but is
263
An unused character (other than 0 to 9, A to F and control codes) is received. not brought to an alarm
stop.
Inverter sent the error code H8.
264
Not defined currently in inverter.

Inverter sent the error code H9.
265
Not defined currently in inverter.
Inverter sent the error code HA. Mode error.
A parameter was written in a mode other than computer link mode or while
266
inverter was operating. Inverter does not accept the received data, but is not
stopped by alarm. Inverter does not accept
Inverter sent the error code HB. Instruction code error. the received data, but is
267
Non-existing instruction code was specified. not brought to an alarm
Inverter sent the error code HC. Data range error. stop.
In writing a parameter or operation frequency, data outside the allowable range
268
was specified. Inverter does not accept the received data, but is not stopped by
alarm.
Inverter sent the error code HD.
269
Not defined currently in inverter.
Inverter sent the error code HE.
270
Not defined currently in inverter.
Inverter sent the error code HF.
271
Not defined currently in inverter.

E-148
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

A
3. IVMC instruction error codes

Common Items
When errors occur in the send data of the IVMC instruction, the following error codes are stored.
It is recommended to check error codes in hexadecimal.
Refer to the error code list earlier in this section for other errors.
Error code
(HEX) B

N:N Network
IVMC Send Send
instruction data2 data1 Contents of error Inverter operation
error error error
information information information
b15 to b8 b7 to b4 b3 to b0
No error has occurred in both send data 1 and C
H00 H0 H0 send data 2.

Parallel Link
Normal end
The inverter sent error code HA to send data 1 of
the IVMC instruction.
A parameter was written in a mode other than
HA
computer link mode or while the inverter was
operating. The inverter did not accept the The inverter accepts D
received data, but was not stopped by alarm. data corresponding to

Computer Link
H0 send data 2, and is not
The inverter sent error code HB to send data 1 of
brought to an alarm
HB the IVMC instruction.
stop.
Non-existing instruction code was specified.
The inverter sent error code HC to send data 1 of
HC the IVMC instruction. E
Data outside the allowable range was specified.

Communication
Inverter
The inverter sent error code HA to send data 2 of
the IVMC instruction.
A parameter was written in a mode other than
H02 HA
computer link mode or while inverter was
The inverter accepts
operating. The inverter did not accept the
received data, but was not stopped by alarm. data corresponding to F
H0 send data 1, and is not

(RS/RS2 Instruction)
Communication
Non-Protocol
The inverter sent error code HB to send data 2 of
brought to an alarm
HB the IVMC instruction.
stop.
Non-existing instruction code was specified.
The inverter sent error code HC to send data 2 of
HC the IVMC instruction.
Data outside the allowable range was specified. G
The inverter does not

(FX2N-232IF)
Communication
Non-Protocol
The inverter sent error codes to both send data 1
accept data
and send data 2 of the IVMC instruction.
corresponding to send
HA to HC HA to HC Refer to the contents of the error of the
data 1 and 2, but is not
corresponding error codes of send data 1 and
brought to an alarm
send data 2 for details of error codes.
stop.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-149
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)

12.4.10 Inverter communication error occurrence step [D8153 and D8158]


These devices store the step number in which an inverter communication error has occurred.
1. Detailed contents
D8153 or D8158 stores the step number of the instruction causing an inverter communication error.
D8153 stores the step number in which an error has occurred in communication using communication port
ch1.
D8158 stores the step number in which an error has occurred in communication using communication port
ch2.
When errors that occurred in two or more instructions, D8153 or D8158 holds the step number in which the
error occurred first.
When no error has occurred, D8153 or D8158 stores "-1".

2. Cautions on use
A decimal value without the sign is stored as the step number in D8153 and D8158.

12.4.11 IVBWR instruction error parameter number [D8154 and D8159]


(only in FX3U and FX3UC PLCs)
These devices store the parameter number in which an error has occurred when IVBWR instruction error flag
"M8154 or M8159" turns ON.

1. Detailed contents
D8154 or D8159 stores the parameter number which was not written by IVBWR instruction.
D8154 stores the parameter number which was not written in communication using communication port ch1.
D8159 stores the parameter number which was not written in communication using communication port ch2.
When errors that occurred in two or more IVBWR instructions, D8154 or D8159 holds the parameter number
in which the error occurred first.

12.4.12 Operation mode display [D8419 and D8439]


These devices store the communication type being used.

1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.

The table below shows the contents of the communication type codes.
Code Description
0 Programming communication
1 PP modem mode
2 Protocol dedicated to computer link
3 N:N Network
4 RS instruction
5 RS2 instruction
6 Parallel link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication
10 CF-ADP
11 ENET-ADP
12 Input/output expansion board is used.

E-150
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
12.5 FREQROL Inverter Parameter List

Common Items
This section shows the list of parameters provided in FREQROL F800, A800, F700, A700, E700, V500, F500,
A500, E500 and S500 Series inverters.
For details on each function, refer to the respective inverter manual.
B
12.5.1 Parameters in V500, F500, A500, E500, and S500 Series

N:N Network
The following parameters are provided in FREQROL inverters. (For details, make sure to refer to the
respective inverter manual.)
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Function
Pr
Name
Pr
Name
Pr
Name
Pr
Name
Pr
Name
C
No. No. No. No. No.

Parallel Link
Torque boost
0
(manual)
0 Torque boost 0 Torque boost*3 0 Torque boost*3 0 Torque boost*3

Maximum speed Maximum Maximum Maximum Maximum


1 1 1 1 1
(simple mode) frequency frequency frequency frequency

2
Minimum speed
(simple mode)
2
Minimum
frequency
2
Minimum
frequency
2
Minimum
frequency
2
Minimum
frequency
D

Computer Link
3 Base frequency 3 Base frequency 3 Base frequency 3 Base frequency*3 3 Base frequency*3
Multi-speed
Multi-speed Multi-speed Multi-speed Multi-speed
setting
4 4 setting 4 setting 4 setting 4 setting
(high speed)
(high speed) (high speed) (high speed) (high speed)
(simple mode)
Basic Multi-speed
Multi-speed Multi-speed Multi-speed Multi-speed
E
functions setting

Communication
Inverter
5 5 setting 5 setting 5 setting 5 setting
(middle speed)
(middle speed) (middle speed) (middle speed) (middle speed)
(simple mode)
Multi-speed
Multi-speed Multi-speed Multi-speed Multi-speed
setting
6 6 setting 6 setting 6 setting 6 setting
(low speed)
(simple mode)
(low speed) (low speed) (low speed) (low speed)
F
Acceleration time

(RS/RS2 Instruction)
Communication
Non-Protocol
7 7 Acceleration time 7 Acceleration time 7 Acceleration time 7 Acceleration time
(simple mode)
Deceleration time
8 8 Deceleration time 8 Deceleration time 8 Deceleration time 8 Deceleration time
(simple mode)
Electronic thermal Electronic thermal Electronic thermal Electronic thermal Electronic thermal
9 9 9 9 9
O/L relay O/L relay O/L relay O/L relay O/L relay
DC injection brake DC injection brake DC injection brake DC injection brake
G
DC injection brake
10 10 operation 10 operation 10 operation 10 operation

(FX2N-232IF)
Communication
Non-Protocol
operation speed
frequency frequency frequency frequency
DC injection brake DC injection brake DC injection brake DC injection brake DC injection brake
11 11 11 11 11
operation time operation time operation time operation time operation time

Standard DC injection brake DC injection brake DC injection brake DC injection brake DC injection brake
12 12 12 12 12
operation
13
voltage
Starting speed 13
voltage
Starting frequency 13
voltage
Starting frequency 13
voltage
Starting frequency 13
voltage
Starting frequency
H
functions
Communication
Programming

Load pattern Load pattern Load pattern Load pattern


14 14 14 14
selection selection*3 selection*3 selection*3
15 Jog speed setting 15 Jog frequency 15 Jog frequency 15 Jog frequency 15 Jog frequency
Jog acceleration/ Jog acceleration/ Jog acceleration/ Jog acceleration/ Jog acceleration/
16 16 16 16 16

Standard
deceleration time
MRS input
deceleration time
MRS input
deceleration time
MRS input
deceleration time deceleration time
RUN key rotation
I
17 17 17 17
Maintenance
Remote

operation selection selection selection direction selection


function High speed High speed
(V500 18 maximum 18 maximum
Series frequency frequency
operation
selection Base frequency Base frequency Base frequency Base frequency Base frequency
19 19 19 19 19
functions) voltage voltage voltage*3 voltage*3 voltage*3 Apx.A
models
Discontinued

E-151
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Acceleration/ Acceleration/ Acceleration/ Acceleration/
Acceleration/
deceleration deceleration deceleration deceleration
20 deceleration 20 20 20 20
reference reference reference reference
reference speed
frequency frequency frequency frequency
Acceleration/ Acceleration/ Acceleration/ Acceleration/
Stall preventing
21 deceleration time 21 deceleration time 21 deceleration time 21 deceleration time 21
function selection
increment increment increment increment
Torque restriction Stall prevention Stall prevention Stall prevention Stall prevention
22 22 22 22 22
level operation level operation level operation level operation level
Stall prevention Stall prevention Stall prevention Stall prevention
operation level operation level operation level operation level
23 compensation 23 compensation 23 compensation 23 compensation
factor at double factor at double factor at double factor at double
speed speed speed speed
Multi-speed Multi-speed Multi-speed Multi-speed Multi-speed
24 24 24 24 24
setting (speed 4) setting (speed 4) setting (speed 4) setting (speed 4) setting (speed 4)
Multi-speed Multi-speed Multi-speed Multi-speed Multi-speed
25 25 25 25 25
setting (speed 5) setting (speed 5) setting (speed 5) setting (speed 5) setting (speed 5)
Multi-speed Multi-speed Multi-speed Multi-speed Multi-speed
26 26 26 26 26
setting (speed 6) setting (speed 6) setting (speed 6) setting (speed 6) setting (speed 6)
Multi-speed Multi-speed Multi-speed Multi-speed Multi-speed
27 27 27 27 27
setting (speed 7) setting (speed 7) setting (speed 7) setting (speed 7) setting (speed 7)
Stall preventing
Multi-speed input Multi-speed input Multi-speed input operation
Standard 28 28 28 28
compensation compensation compensation reduction starting
operation frequency
function
(V500 Acceleration/ Acceleration/ Acceleration/ Acceleration/ Acceleration/
Series 29 deceleration 29 deceleration 29 deceleration 29 deceleration 29 deceleration
operation pattern pattern pattern pattern pattern
selection Extended
Regenerative Regenerative Regenerative Regenerative
functions) 30 30 30 30 30 function display
function selection function selection function selection function selection
selection
Frequency jump Frequency jump Frequency jump Frequency jump
31 Speed jump 1A 31 31 31 31
1A 1A 1A 1A
Frequency jump Frequency jump Frequency jump Frequency jump
32 Speed jump 1B 32 32 32 32
1B 1B 1B 1B
Frequency jump Frequency jump Frequency jump Frequency jump
33 Speed jump 2A 33 33 33 33
2A 2A 2A 2A
Frequency jump Frequency jump Frequency jump Frequency jump
34 Speed jump 2B 34 34 34 34
2B 2B 2B 2B
Frequency jump Frequency jump Frequency jump Frequency jump
35 Speed jump 3A 35 35 35 35
3A 3A 3A 3A
Frequency jump Frequency jump Frequency jump Frequency jump
36 Speed jump 3B 36 36 36 36
3B 3B 3B 3B
37 Speed display 37 Speed display 37 Speed display 37 Speed display*8 37 Speed display*8
Frequency setting
Automatic torque Frequency at 5V
38 38 38 voltage gain
boost (10V) input
frequency
Automatic torque Frequency setting
Frequency at
39 boost operation 39 39 current gain
20mA input
starting current frequency
Start-time ground
40 fault detection
selection
Up-to-speed Up-to-frequency Up-to-frequency Up-to-frequency Up-to-frequency
41 41 41 41 41
sensitivity sensitivity sensitivity sensitivity sensitivity
Output Output frequency Output frequency Output frequency Output frequency
42 Speed detection 42 42 42 42
terminal detection detection detection detection
functions Speed detection Output frequency Output frequency Output frequency Output frequency
43 for reverse 43 detection for 43 detection for 43 detection for 43 detection for
rotation reverse rotation reverse rotation reverse rotation reverse rotation

E-152
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Second Second Second Second Second
44 acceleration/ 44 acceleration/ 44 acceleration/ 44 acceleration/ 44 acceleration/
deceleration time
Second
deceleration time
Second
deceleration time
Second
deceleration time
Second
deceleration time
Second
B
45 45 45 45 45

N:N Network
deceleration time deceleration time deceleration time deceleration time deceleration time
Second torque Second torque Second torque Second torque
46 46 46 46
boost boost*3 boost*3 boost*3
Second V/F Second V/F Second V/F Second V/F
47 47 47 47
(base frequency) (base frequency)*3 (base frequency)*3 (base frequency)*3
Second
functions Second stall Second stall
C
Second electronic
48 prevention 48 prevention 48

Parallel Link
thermal O/L relay
operation current operation current
Second stall Second stall
prevention prevention
49 49
operation operation
frequency
Second output
frequency
Second output

D
Second speed

Computer Link
50 50 frequency 50 frequency
detection
detection detection
DU/PU main DU/PU main DU/PU main Operation panel/ Control panel
52 display data 52 display data 52 display data 52 PU main display 52 display data
selection selection selection data selection selection

53
PU level display
53
PU level display
53
PU level display
53
Frequency setting
operation
E
data selection data selection data selection

Communication
Inverter
selection
Display DA1 terminal FM terminal FM terminal FM terminal FM (AM) terminal
54 54 54 54 54
functions function selection function selection function selection function selection function selection
Frequency Frequency Frequency Frequency
Speed monitoring
55 55 monitoring 55 monitoring 55 monitoring 55 monitoring
reference
reference reference reference reference
F
Current Current Current Current Current

(RS/RS2 Instruction)
Communication
Non-Protocol
56 monitoring 56 monitoring 56 monitoring 56 monitoring 56 monitoring
reference reference reference reference reference
Restart coasting Restart coasting Restart coasting Restart coasting Restart coasting
57 57 57 57 57
time time time time time
Restart
Restart cushion Restart cushion Restart cushion Restart cushion Restart cushion
58
time
58
time
58
time
58
time
58
time G
Additional Remote setting Remote setting Remote setting Remote setting Remote setting

(FX2N-232IF)
Communication
Non-Protocol
59 59 59 59 59
function function selection function selection function selection function selection function selection
Shortest
Intelligent mode Intelligent mode Intelligent mode acceleration/
60 60 60 60
selection selection selection deceleration
mode

61
Reference I for
61
Reference I for
61 Reference current
H
intelligent mode intelligent mode
Communication
Programming

Reference I for Reference I for


Reference current
62 intelligent mode 62 intelligent mode 62
for acceleration
acceleration acceleration

Reference I for Reference I for
Operation Reference current
selecting
63 intelligent mode
deceleration
63 intelligent mode
deceleration
63
for deceleration I
functions
Maintenance
Remote

Starting frequency
64
for elevator mode
65 Retry selection 65 Retry selection 65 Retry selection 65 Retry selection 66 Retry selection
Stall prevention Stall prevention Stall prevention
operation level operation level operation level
66 66 66
reduction starting reduction starting reduction starting Apx.A
frequency frequency frequency
models
Discontinued

Number of retries Number of retries Number of retries Number of retries Number of retries
67 at alarm 67 at alarm 67 at alarm 67 at alarm 67 at alarm
occurrence occurrence occurrence occurrence occurrence

E-153
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
68 Retry waiting time 68 Retry waiting time 68 Retry waiting time 68 Retry waiting time 68 Retry waiting time
Retry count Retry count Retry count Retry count Retry count
69 69 69 69 69
display erasure display erasure display erase display erasure display erase
Special Special Special
70 regenerative 70 regenerative 70 regenerative
brake duty brake duty brake duty
71 Applied motor 71 Applied motor 71 Applied motor 71 Applied motor 71 Applied motor
PWM frequency
PWM frequency PWM frequency PWM frequency PWM frequency
72 selection 72 72 72 72
selection selection selection selection
(simple mode)
Speed setting 0 to 5V/0 to 10V 0 to 5V/0 to 10V 0 to 5V/0 to 10V 0 to 5V/0 to 10V
73 73 73 73 73
signal selection selection selection selection
Filter time Filter time Filter time Input filter time
Operation 74 74 74 74
constant constant constant constant
selecting
Reset selection/ Reset selection/ Reset selection/ Reset selection/
functions
disconnected PU disconnected PU disconnected PU disconnected PU Reset selection/
75 75 75 75 75
detection/PU stop detection/PU stop detection/PU stop detection/PU stop PU stop selection
selection selection selection selection
Alarm code output Alarm code output
76 76
selection selection
Parameter write
Parameter write Parameter write Parameter write Parameter write
77 disable selection 77 77 77 77
disable selection disable selection disable selection disable selection
(simple mode)
Reverse rotation Reverse rotation Reverse rotation Reverse rotation Reverse rotation
78 prevention 78 prevention 78 prevention 78 prevention 78 prevention
selection selection selection selection selection
Operation mode
Operation mode Operation mode Operation mode Operation mode
79 selection 79 79 79 79
selection selection selection selection
(simple mode)
80 Motor capacity 80 Motor capacity 80 Motor capacity
Number of motor Number of motor
81 81
poles poles
Motor excitation
Motor excitation Motor excitation
82 current 82 82
*1 current*5 current
(no load current)
Rated motor Rated motor Rated motor
83 83 83
voltage voltage voltage
Rated motor Rated motor Rated motor
84 84 84
frequency frequency frequency
Speed control
89
gain
Motor constant Motor constant Motor constant
Motor 90 90 90
R1*1 (R1)*5 (R1)
constant
Motor constant Motor constant
91 91
R2*1 (R2)*5
Motor constant Motor constant
92 92
L1*1 (L1)*5
Motor constant Motor constant
93 93
L2*1 (L2)*5
Motor constant Motor constant
94 94
X*1 (X)*5
Online auto tuning
Online auto tuning
95 selection 95
selection
(simple mode)
Auto tuning Auto tuning Auto tuning
96 96 96
setting/status setting/status setting/status

E-154
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
V/F 1 V/F 1
100 100
(first frequency) (first frequency)*3
V/F 1 V/F 1 B
101 (first frequency 101 (first frequency

N:N Network
voltage) voltage)*3
V/F 2 (second V/F 2 (second
102 102
frequency) frequency)*3
V/F 2 (second V/F 2 (second
103 frequency
voltage)
103 frequency
voltage)*3
C

Parallel Link
5-point V/F 3 V/F 3
104 104
flexible (third frequency) (third frequency)*3
V/F V/F 3 V/F 3
character- 105 (third frequency 105 (third frequency
istics voltage) voltage)*3
V/F 4 (fourth V/F 4 (fourth D
106 106
frequency) frequency)*3

Computer Link
V/F 4 V/F 4
107 (fourth frequency 107 (fourth frequency
voltage) voltage)*3
V/F 5 (fifth V/F 5 (fifth
108
frequency)
108
frequency)*3 E
V/F 5 V/F 5

Communication
Inverter
109 (fifth frequency 109 (fifth frequency
voltage) voltage)*3
Third acceleration Third acceleration
110 110
/deceleration time /deceleration time

111
Third deceleration
time
111
Third deceleration
time
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Third torque
112
boost*3
Third V/F (base
113
frequency)*3
Third
functions
Third stall
114 prevention

G
operation current

(FX2N-232IF)
Communication
Non-Protocol
Third stall
prevention
115
operation
frequency

116
Third speed
Third output
116 frequency
H
detection
detection
Communication
Programming

Communication Communication Communication Communication


117 117 117 117
station number station number station number station number
Communication Communication Communication Communication
118 118 118 118
speed speed speed speed

119
Stop bit length/
data length
119
Stop bit length/
data length
119
Stop bit length/
data length
119 Stop bit length I
Maintenance
Remote

Communi- Parity check Parity check Parity check Parity check


cation 120 presence/ 120 presence/ 120 presence/ 120 presence/
functions absence absence absence absence
Number of Number of Number of Number of
121 communication 121 communication 121 communication 121 communication
retries retries retries retries Apx.A
Communication Communication Communication Communication
models
Discontinued

122 check time 122 check time 122 check time 122 check time
interval interval interval interval

E-155
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Waiting time Waiting time Waiting time Waiting time
123 123 123 123
Communi- setting setting setting setting
cation CR and LF CR and LF CR and LF CR and LF
functions 124 presence/absence 124 presence/absence 124 presence/absence 124 presence/absence
selection selection selection selection
PID action PID action PID action PID action PID action
128 128 128 128 88
selection selection selection selection selection
PID proportional PID proportional PID proportional PID proportional PID proportional
129 129 129 129 89
band band band band band
130 PID integral time 130 PID integral time 130 PID integral time 130 PID integral time 90 PID integral time
PID 131 Maximum 131 Maximum 131 Maximum 131 Maximum 91 PID maximum
control 132 Minimum 132 Minimum 132 Minimum 132 Minimum 92 PID minimum
PID action set PID action set PID action set PID action set PID action set
133 point for PU 133 point for PU 133 point for PU 133 point for PU 93 point for PU
operation operation operation operation operation
PID differential PID differential PID differential PID differential PID differential
134 134 134 134 94
time time time time time
Commercial Commercial
power supply- power supply-
inverter switch- inverter switch-
135 135
over sequence over sequence
output terminal output terminal
selection selection
MC switch-over MC switch-over
Commer- 136 136
interlock time interlock time
cial power
137 Start waiting time 137 Start waiting time
supply-
Commercial Commercial
inverter
switch- power supply- power supply-
over 138 inverter switch- 138 inverter switch-
over selection at over selection at
alarm occurrence alarm occurrence
Automatic Automatic
inverter- inverter-
139 commercial power 139 commercial power
supply switch- supply switch-
over frequency over frequency
Backlash Backlash
Backlash acceleration acceleration
140 acceleration 140 stopping 140 stopping
stopping speed
frequency*2 frequency*2
Backlash Backlash Backlash
141 acceleration 141 acceleration 141 acceleration
stopping time stopping time*2 stopping time*2
Backlash
Backlash Backlash
Backlash deceleration deceleration
142 deceleration 142 stopping 142 stopping
stopping speed
frequency*2 frequency*2
Backlash Backlash Backlash
143 deceleration 143 deceleration 143 deceleration
stopping time stopping time*2 stopping time*2
Speed setting Speed setting Speed setting
144 144 144
switchover switchover switchover
Display
functions PU display PU display PU display PU display
n13 PU display
145 language 145 language 145 language 145 language
(145) language
selection selection selection selection

E-156
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Frequency setting
146 command

Stall prevention Stall prevention


selection
B
Additional

N:N Network
148 operation level at 148 operation level at
functions
0 V input 0 V input

Stall prevention Stall prevention
149 operation level at 149 operation level at
10 V input 10 V input

150
Output current
detection level
150
Output current
detection level
150
Output current
detection level
48
Output current
detection level
C

Parallel Link
Output current
Output current Output current Output current
151 151 151 49 detection signal
Current detection period detection period detection period
delay time
detection
Zero current Zero current Zero current Zero current Zero current
152 152 152 152 50
detection level detection level detection level detection level detection level

153
Zero current
153
Zero current
153
Zero current
153
Zero current
51
Zero current D
detection period detection period detection period detection period detection time

Computer Link
Voltage reduction Voltage reduction
selection during selection during
154 154
stall prevention stall prevention
operation operation
RT signal
155
RT activated
condition
155 activated E
Sub condition

Communication
Inverter

functions Stall prevention Stall prevention Stall prevention Stall prevention
156 operation 156 operation 156 operation 156 operation
selection selection selection selection
OL signal output OL signal output OL signal waiting
157 157 157
timer waiting time time
DA2 terminal AM terminal AM terminal
F
158 158 158

(RS/RS2 Instruction)
Communication
Non-Protocol
function selection function selection function selection
Extended function
Additional User group read User group read User group read
160 selection 160 160 160
function selection selection selection
(simple mode)
Automatic restart Automatic restart Automatic restart
after
162 instantaneous
after
162 instantaneous
after
162 instantaneous
G

(FX2N-232IF)
Communication
Non-Protocol
power failure power failure power failure
Restart
selection selection selection
after
instanta- First cushion time First cushion time First cushion time
163 163 163
neous for restart for restart for restart
power First cushion First cushion First cushion
164 164 164
failure voltage for restart voltage for restart voltage for restart
H
Restart stall Restart stall
Restart current
Communication
Programming

165 165 prevention 165 prevention


restriction level
operation level operation level
Watt-hour meter Watt-hour meter
Initial 170 170
clear clear
monitor
Actual operation Actual operation Actual operation Actual operation
value 171
hour meter clear
171
hour meter clear
171
hour meter clear
171
hour meter clear I
User group 1 User group 1 User group 1
Maintenance
Remote

173 173 173


registration registration registration
User group 1 User group 1 User group 1
174 174 174
User deletion deletion deletion

functions User group 2 User group 2 User group 2
175 175 175
registration registration registration
User group 2 User group 2 User group 2
Apx.A
176 176 176
models
Discontinued

deletion deletion deletion

E-157
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
DI1 terminal RL terminal RL terminal RL terminal RL terminal
180 180 180 180 60
function selection function selection function selection function selection function selection
DI2 terminal RM terminal RM terminal RM terminal RM terminal
181 181 181 181 61
function selection function selection function selection function selection function selection
DI3 terminal RH terminal RH terminal RH terminal RH terminal
182 182 182 182 62
function selection function selection function selection function selection function selection
DI4 terminal RT terminal RT terminal MRS terminal
183 183 183 183
function selection function selection function selection function selection
AU terminal AU terminal
184 184
function selection function selection

JOG terminal JOG terminal
185 185
function selection function selection
CS terminal CS terminal
Terminal 186 186
function selection function selection
assignment
functions STR terminal STR terminal
187 63
function selection function selection
DO1 terminal RUN terminal RUN terminal RUN terminal RUN terminal
190 190 190 190 64
function selection function selection function selection function selection function selection
DO2 terminal SU terminal SU terminal FU terminal
191 191 191 191
function selection function selection function selection function selection
DO3 terminal IPF terminal IPF terminal A/B/C terminal A/B/C terminal
192 192 192 192 65
function selection function selection function selection function selection function selection
OL terminal OL terminal
193 193
function selection function selection

FU terminal FU terminal
194 194
function selection function selection
A/B/C terminal A/B/C terminal A/B/C terminal
195 195 195
function selection function selection function selection
Additional User's initial value User's initial value
199 199
function setting setting
Programmed
200 operation minute/
second selection
201 Program set 1
202 Program set 1
203 Program set 1
204 Program set 1
205 Program set 1
206 Program set 1
207 Program set 1
208 Program set 1
209 Program set 1
210 Program set 1
Programmed
211 Program set 2
operation
212 Program set 2
213 Program set 2
214 Program set 2
215 Program set 2
216 Program set 2
217 Program set 2
218 Program set 2
219 Program set 2
220 Program set 2
221 Program set 3
222 Program set 3
223 Program set 3

E-158
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
224 Program set 3
225 Program set 3
226 Program set 3 B
Programmed 227 Program set 3

N:N Network

operation 228 Program set 3
229 Program set 3
230 Program set 3
231 Timer setting

232
Multi-speed
232
Multi-speed
232
Multi-speed
80
Multi-speed C
setting (speed 8) setting (speed 8) setting (speed 8) setting (speed 8)

Parallel Link
Multi-speed Multi-speed Multi-speed Multi-speed
233 233 233 81
setting (speed 9) setting (speed 9) setting (speed 9) setting (speed 9)
Multi-speed Multi-speed Multi-speed Multi-speed
234 234 234 82
setting (speed 10) setting (speed 10) setting (speed 10) setting (speed 10)

Multi- 235
Multi-speed
setting (speed 11)
235
Multi-speed
setting (speed 11)
235
Multi-speed
setting (speed 11)
83
Multi-speed
setting (speed 11)
D
speed

Computer Link
operation Multi-speed Multi-speed Multi-speed Multi-speed
236 236 236 84
setting (speed 12) setting (speed 12) setting (speed 12) setting (speed 12)
Multi-speed Multi-speed Multi-speed Multi-speed
237 237 237 85
setting (speed 13) setting (speed 13) setting (speed 13) setting (speed 13)
Multi-speed Multi-speed Multi-speed Multi-speed
238
setting (speed 14)
238
setting (speed 14)
238
setting (speed 14)
86
setting (speed 14) E
Multi-speed Multi-speed Multi-speed Multi-speed

Communication
Inverter
239 239 239 87
setting (speed 15) setting (speed 15) setting (speed 15) setting (speed 15)
240 Soft-PWM setting 240 Soft-PWM setting 240 Soft-PWM setting 240 Soft-PWM setting 70 Soft-PWM setting
Cooling fan Cooling fan Cooling fan Cooling fan Cooling fan
244 operation 244 operation 244 operation 244 operation 76 operation
selection selection selection selection selection
245 Rated motor slip 95 Rated motor slip F

(RS/RS2 Instruction)
Communication
Non-Protocol
Slip compensation Slip compensation
246 96
response time time constant
Sub Constant-output Constant-output
functions region slip region slip
247 97
compensation compensation
selection selection
Automatic torque
G

(FX2N-232IF)
Communication
Non-Protocol
98 boost selection
(motor capacity)
Earth (ground)
Motor primary
249 fault detection at 99
resistance
start*6
Stop H
selecting 250 Stop selection 250 Stop selection 250 Stop selection
Communication
Programming

function
Output phase Output phase Output phase Output phase
251 failure protection 251 failure protection 251 failure protection 251 failure protection
Additional selection selection selection selection
functions
252 Override bias 252 Override bias 252 Override bias
253 Override gain 253 Override gain 253 Override gain
I
Maintenance
Remote

Power failure stop Power failure stop


261 261
selection selection
Subtraction speed Subtraction
Power 262 at deceleration 262 frequency at
failure start deceleration start

stop
functions 263
Subtraction
starting speed
263
Subtraction
starting frequency
Apx.A
models
Discontinued

Power-failure Power-failure
264 264
deceleration time 1 deceleration time 1

E-159
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Power-failure Power-failure
265 265
Power deceleration time 2 deceleration time 2
failure Power-failure
Power-failure
stop deceleration time
functions 266 deceleration time 266
switchover
switchover speed
frequency
Stop-on-contact/
Function load torque high
270
selection speed frequency
control selection
High speed
271 setting maximum
current
High Middle speed
speed 272 setting minimum
current
frequency
control Current averaging
273
range
Current averaging
274
filter constant
Stop-on-contact
exciting current
275
low speed
Stop-on- multiplying factor

contact
Stop-on-contact
276 PWM carrier
frequency
Brake opening Brake opening
278 278
speed frequency*4
Brake opening Brake opening
279 279
current current*4
Brake opening Brake opening
280 current detection 280 current detection
time time*4
Brake operation Brake operation
281 281
Brake time at start time at start*4
sequence Brake operation Brake operation
function 282 282 *4
speed frequency
Brake operation Brake operation
283 283
time at stop time at stop*4
Deceleration Deceleration
284 detection function 284 detection function
selection selection*4
Overspeed
Overspeed
285 285 detection
detection speed
frequency
286 Droop gain 286 Droop gain
Droop filter Droop filter
Droop 287 287
constant constant
control
functions Droop function
288 activation
selection
BCD code input BCD code input
300 BCD input bias 300 300
bias bias
12-bit BCD code input BCD code input
digital 301 BCD input gain 301 301
gain gain
input
302 Binary input bias 302 Binary input bias 302 Binary input bias
303 Binary input gain 303 Binary input gain 303 Binary input gain

E-160
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Selection of Selection of
Digital input and
whether digital whether digital
analog

12-bit
304 compensation 304
input and analog
compensation
304
input and analog
compensation B
input enable/
input are enabled input are enabled

N:N Network
digital disable selection
input or disabled or disabled
Read timing Data read timing Data read timing
305 operation 305 signal on/off 305 signal on/off
selection selection selection

306
Analog output
signal selection
306
Analog output
signal selection
306
Analog output
signal selection
C

Parallel Link
Setting for zero Setting for zero Setting for zero
307 307 307
analog output analog output analog output
Setting for Setting for Setting for
308 maximum analog 308 maximum analog 308 maximum analog
output output output
Analog output
309 signal voltage/
Analog output
309 signal voltage/
Analog output
309 signal voltage/
D

Computer Link
current switchover current switchover current switchover
Analog meter Analog meter Analog meter
310 voltage output 310 voltage output 310 voltage output
Analog selection selection selection
output/ Setting for zero Setting for zero Setting for zero
digital
output
311 analog meter
voltage output
311 analog meter
voltage output
311 analog meter
voltage output

E

Communication
Inverter
Setting for Setting for Setting for
maximum analog maximum analog maximum analog
312 312 312
meter voltage meter voltage meter voltage
output output output
313 Y0 output selection 313 Y0 output selection 313 Y0 output selection
314 Y1 output selection 314 Y1 output selection 314 Y1 output selection F

(RS/RS2 Instruction)
Communication
Non-Protocol
315 Y2 output selection 315 Y2 output selection 315 Y2 output selection
316 Y3 output selection 316 Y3 output selection 316 Y3 output selection
317 Y4 output selection 317 Y4 output selection 317 Y4 output selection
318 Y5 output selection 318 Y5 output selection 318 Y5 output selection
319 Y6 output selection 319 Y6 output selection 319 Y6 output selection

320
RA1 output
320
RA1 output
320
RA1 output G
selection selection selection

(FX2N-232IF)
Communication
Non-Protocol
Relay RA2 output RA2 output RA2 output
321 321 321
output selection selection selection
RA3 output RA3 output RA3 output
322 322 322
selection selection selection
Digital
input
329
Digital input unit
selection
H
Communication
Programming

Relay RA output RA output RA output


330 330 330
output selection selection selection
Communication Inverter station Communication n1 Communication
331 331 331
station number number station number (331) station number
Computer 332 Communication Communication Communication n2 Communication
link speed
332
speed
332
speed (332) speed I
function Stop bit length/ Stop bit length/ Stop bit length/ n3 Stop bit length/
Maintenance
Remote

333 333 333


(S500 data length data length data length (333) data length

Series Parity check Parity check
communi- 334 presence/ Parity check yes/ Parity check yes/ n4
334 334 presence/
cation no no (334)
absence absence
parameter)
Number of Number of
335 communication 335
Communication
335
Communication n5
communication
Apx.A
retry count retry count (335)
retries retries
models
Discontinued

E-161
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Communication Communication Communication Communication
n6
336 check time 336 check time 336 check time check time
(336)
interval interval interval interval
Waiting time Waiting time Waiting time n7
337 337 337 Wait time setting
setting setting setting (337)
Computer
link Operation Operation Operation Operation n8 Operation
338 338 338 338
function command source command write command right command source (338) command write
(S500 Speed command Speed command Speed command Speed command n9 Speed command
339 339 339 339
Series source write write source (339) write
communi- Link startup mode Link startup mode Link startup mode Link startup mode n10 Link start mode
cation 340 340 340 340
selection selection selection selection (340) selection
parameter)
CR and LF
CR and LF yes/no CR and LF yes/no n11 CR and LF
341 presence/absence 341 341
selection selection (341) selection
selection
2 2 2 2 n12 E2PROM write
342 E PROM write 342 E PROM write 342 E PROM write 342 E PROM write
selection selection selection selection (342) selection
DeviceNet DeviceNet DeviceNet DeviceNet
345 address 345 address startup 345 address startup 345 address startup
(lower) data (lower byte) data (lower byte) data (lower byte)
DeviceNet baud DeviceNet baud DeviceNet baud
DeviceNet baud
346 346 rate startup data 346 rate startup data 346 rate startup data
DeviceNet rate (lower)
(lower byte) (lower byte) (lower byte)
communi-
cation DeviceNet DeviceNet DeviceNet
347 address 347 address startup 347 address startup
(higher) data (higher byte) data (higher byte)

DeviceNet baud DeviceNet baud
DeviceNet baud
348 348 rate startup data 348 rate startup data
rate (higher)
(higher byte) (higher byte)
Stop position Stop position
350 command 350 command
selection selection
Orientation Orientation
351 351
switchover speed switchover speed
352 Creep speed
Creep switch
353
position

Position loop
354 switchover
position
DC injection start
Orientation 355
position
control/
encoder Internal stop Internal stop
356 356
feedback position command position command
control/ 357 In-position zone 357 In-position zone
pulse train
Servo torque
input 358
selection
Orientation
Encoder rotation
359 encoder rotation 359
direction
direction
External position
12-bit data
360 command 360
selection
selection
361 Position shift 361 Position shift
Orientation
362 362 Position loop gain
position loop gain
Completion signal
363
output delay time

E-162
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Encoder stop
364
check time

365
Orientation
censored limit
B

N:N Network
Reconfirmation
366
time
Speed feedback
367
range
368 Feedback gain
Number of Number of C
369 orientation 369 orientation

Parallel Link
encoder pulse encoder pulse
Control mode
370
selection
Torque


371 characteristic
selection D

Computer Link
Speed control P
372
Orientation gain
control/ Speed control I
encoder 373
gain
feedback
control/ Over-speed Over-speed
374 374
pulse train detection level detection level E
input 375 Servo lock gain

Communication
Inverter
Disconnection
376
detection selection
Acceleration S Acceleration S
380 380
pattern 1 pattern 1

381
Deceleration S
pattern 1
381
Deceleration S
pattern 1 F

(RS/RS2 Instruction)
Communication
Non-Protocol
Acceleration S Acceleration S
382 382
pattern 2 pattern 2
Deceleration S Deceleration S
383 383
pattern 2 pattern 2
Input pulse Input pulse
384 division scaling
factor
384 division scaling
factor
G

(FX2N-232IF)
Communication
Non-Protocol
Speed for zero Frequency for
385 385
input pulse zero input pulse
Speed for Frequency for
386 maximum input 386 maximum input
pulse pulse
Initial Initial H
387 communication 387 communication
Communication
Programming

delay time delay time


Send time interval Send time interval
388 388
at hart beat at hart beat
Minimum sending Minimum sending
389 389
time at hart beat time at hart beat
LONWORKS
communication
% setting % setting I
390 reference 390 reference
Maintenance
Remote

frequency frequency
Receive time Receive time
391 interval at heart 391 interval at heart
beat beat
Event-driven Event-driven
392
detection width
392
detection width
Apx.A
models
Discontinued

E-163
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Orientation
393
selection
Number of
394 machine side gear
teeth
Number of motor
395
side gear teeth
Orientation
Orientation speed
selection 396
gain (P term)
Orientation speed
397
integral time
Orientation speed
398
gain (D term)
Orientation
399
deceleration ratio
DI11 terminal
400
function selection
DI12 terminal
401
function selection
DI13 terminal
402
function selection
DI14 terminal
403
function selection
Extension DI15 terminal
404
input function selection
DI16 terminal
405
function selection
High resolution
406 analog input
selection
Motor
407 temperature
detection filter
DO11 terminal
410
function selection
DO12 terminal
411
function selection
Extension
DO13 terminal
output 412
function selection
Encoder pulse
413 output division
ratio
Position
419 command source
selection
Command pulse
420 scaling factor
numerator
Command pulse
421 scaling factor
Positioning denominator
control
422 Position loop gain
Position feed
423
forward gain
Position
command
424 acceleration/
deceleration time
constant

E-164
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Position feed
425 forward command
filter
426 In-position width
B

N:N Network
Excessive level
427
Positioning error

control Command pulse
428
selection
Clear signal
429
selection C
Pulse monitor

Parallel Link
430
selection
Pulse train torque
432
Torque command bias

command Pulse train torque
433
command gain
434 IP address 1
D

Computer Link
435 IP address 2
436 IP address 3
437 IP address 4
438 Sub-net mask 1

Position
439 Sub-net mask 2
440 Sub-net mask 3
E
control

Communication
Inverter
441 Sub-net mask 4
442 Gateway address 1
443 Gateway address 2
444 Gateway address 3
445 Gateway address 4 F
446 Password

(RS/RS2 Instruction)
Communication
Non-Protocol
Digital torque
447
Torque command bias

command Digital torque
448
command gain

450
Second applied
motor G

(FX2N-232IF)
Communication
Non-Protocol
Second motor
451 control method
selection
Motor
Second electronic
constant 452
thermal O/L relay

453
Second motor
capacity
H
Communication
Programming

Number of second
454
motor poles
Digital position
control sudden
464
stop deceleration
time I
First position feed
Maintenance
Remote

465 amount lower 4


Position digits
control
First position feed
466 amount upper 4
digits
Second position Apx.A
467 feed amount
models
Discontinued

lower 4 digits

E-165
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Second position
468 feed amount
upper 4 digits
Third position
469 feed amount
lower 4 digits
Third position
470 feed amount
upper 4 digits
Fourth position
471 feed amount
lower 4 digits
Fourth position
472 feed amount
upper 4 digits
Fifth position feed
473 amount lower 4
digits
Fifth position feed
474 amount upper 4
digits
Sixth position feed
475 amount lower 4
digits
Sixth position feed
476 amount upper 4
digits
Seventh position
477 feed amount
Position lower 4 digits

control Seventh position
478 feed amount
upper 4 digits
Eighth position
479 feed amount
lower 4 digits
Eighth position
480 feed amount
upper 4 digits
Ninth position
481 feed amount
lower 4 digits
Ninth position
482 feed amount
upper 4 digits
Tenth position
483 feed amount
lower 4 digits
Tenth position
484 feed amount
upper 4 digits
Eleventh position
485 feed amount
lower 4 digits
Eleventh position
486 feed amount
upper 4 digits
Twelfth position
487 feed amount
lower 4 digits

E-166
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Twelfth position
488 feed amount
upper 4 digits
Thirteenth
B

N:N Network
position feed
489
amount lower 4
digits
Thirteenth
position feed
490
amount upper 4
digits
C

Parallel Link
Fourteenth
Position
position feed
control 491
amount lower 4
digits
Fourteenth
492
position feed
amount upper 4
D

Computer Link
digits
Fifteenth position
493 feed amount
lower 4 digits
Fifteenth position
494 feed amount
upper 4 digits
E

Communication
Inverter
Remote output
495
selection
Remote Remote output
496
output data 1
Remote output
497
data 2 F
Action selection at

(RS/RS2 Instruction)
Communication
Non-Protocol
SSCNET
499
communication
interruption
Communi- Communication Communication Communication
cation Auxiliary motor
500 error recognition 500 500 error recognition 500 error recognition
(F500
Series
waiting time
operation
waiting time waiting time

G
Communication Communication Communication

(FX2N-232IF)
Communication
Non-Protocol
Advanced Motor switch-over
PID control 501 error occurrence 501
selection
501 error occurrence 501 error occurrence
functions) count display count display count display
Stop mode Stop mode
Communication
selection at MC switching selection at
502 502 502 error-time stop 502
communication interlock time communication
error
mode selection
error H
Capacitor life
Communication
Programming

503 Start waiting time 503


timer
Auxiliary motor Capacitor life
504 connection-time 504 alarm output
deceleration time setting time
Capacitor
life
Auxiliary motor
505 disconnection-time I
acceleration time
Maintenance
Remote

(F500
Series Output stop
506
Advanced detection time
PID control Output stop
functions) 507
detection level
Output stop Apx.A
508 cancel process
models
Discontinued

value level
Auxiliary motor 1
509
starting frequency

E-167
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Auxiliary motor 2
510
starting frequency
Auxiliary motor 3
511
starting frequency
Auxiliary motor 1
Capacitor 512 stopping
life frequency
(F500 Auxiliary motor 2
Series 513 stopping
Advanced frequency
PID control Auxiliary motor 3
functions) 514 stopping
frequency
Auxiliary motor
515
start delay time
Auxiliary motor
516
start delay time
Restart
after
instanta- Restart
611
neous acceleration time
power
failure
Control system
800 selection
(simple mode)
Torque
801 characteristic
selection
Pre-excitation
802
selection
Constant output
region torque
803
characteristic
selection
Operation
selecting Torque command
804
function source selection
Torque command
805
source (RAM)
Torque command
806 source (RAM,
EEPROM)
Speed restriction
807
selection
Forward rotation
808
speed restriction
Reverse rotation
809
speed restriction
Torque restriction
810 input method
selection
Control Torque restriction
system 812 level
function (regeneration)
(A500
Series Torque restriction
vector 813 level (3rd
control) quadrant)
Torque restriction
814 level (4th
quadrant)

E-168
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Torque restriction
815
level 2
Acceleration
816 torque restriction
Acceleration
816 torque restriction
B

N:N Network
level level
Deceleration Deceleration
817 torque restriction 817 torque restriction
level level
Easy gain tuning
818
response level
setting (simple
C

Parallel Link
mode)
Easy gain tuning
819 selection (simple
mode)
Speed control P
820
gain 1 D
Speed control

Computer Link
821
integral time 1
Speed setting
822
filter 1
Speed detection
Control 823
filter 1
system
function
Torque control P E
824
gain 1

Communication
Inverter
(A500
Series Torque control
825
vector integral time 1
control) Torque setting
826
filter 1
827
Torque detection
filter 1
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Model speed
828
control gain
Speed control P
830
gain 2
Speed control
831
integral time 2 G
Speed setting

(FX2N-232IF)
Communication
Non-Protocol
832
filter 2
Speed detection
833
filter 2
Torque control P
834
gain 2
Torque control
H
835
Communication
Programming

integral time 2
Torque setting
836
filter 2
Torque detection
837
filter 2

840
Torque bias I
selection
Maintenance
Remote

841 Torque bias 1


Torque 842 Torque bias 2

biases 843 Torque bias 3
844 Torque bias filter

845
Torque bias Apx.A
operation time
models
Discontinued

E-169
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
Torque bias
846 balance
compensation
Fall-time torque
Torque 847
bias No. 3 bias
biases
Fall-time torque
848
bias No. 3 gain
Analog input
849
offset adjustment
Number of
851
encoder pulses
Encoder rotation
852
direction
854 Excitation ratio
Additional 859 Torque current

functions Notch filter
862
frequency
863 Notch filter depth
864 Torque detection
Low speed
865
detection
Torque monitoring
Display 866
reference
functions
867 DA1 output filter
Terminal
No. 1 terminal
assign-
868 function
ment
assignment
function
Speed deviation
870
level
Protection Speed deviation
871
functions time
873 Speed restriction
874 OLT level setting
Operation 875 Fault definition
selecting Thermal relay
functions 876
protector input
Speed feed
forward/model
877
adaptive speed
control selection
Speed feed
Control 878
forward filter
system
Speed feed
functions
879 forward torque
restriction
880 Load inertia ratio
Speed feed
881
forward gain
Maintenance
890
output setting time
Maintenance Maintenance
891
functions output timer
Maintenance
892
output signal clear

E-170
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series

Common Items
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
C1
DA1 terminal FM terminal FM terminal FM terminal FM (AM) terminal
900 900 900 900 (900
calibration calibration calibration calibration calibration

DA2 terminal AM terminal AM terminal


(901))
B
901 901 901

N:N Network
calibration calibration calibration
Frequency setting
C2
voltage bias
Speed setting No. Frequency setting Frequency setting Frequency setting (902) frequency
902 902 902 902
2 bias voltage bias voltage bias voltage bias
C3 Frequency setting
(902) voltage bias C
Speed setting No. Frequency setting Frequency setting Frequency setting C4 Frequency setting

Parallel Link
903 903 903 903
2 gain voltage gain voltage gain voltage gain (903) voltage gain
Frequency setting
C5
current bias
Torque command Frequency setting Frequency setting Frequency setting (904) frequency
904 904 904 904
No. 3 bias current bias current bias current bias
C6 Frequency setting
(904) current bias D
Torque command Frequency setting Frequency setting Frequency setting C7 Frequency setting

Computer Link
905 905 905 905
No. 3 gain current gain current gain current gain (905) current gain
Parameter set by
C8
manufacturer. Do
(269)
not set.

917
No. 1 terminal
bias (speed) E

Communication
Inverter
No. 1 terminal
918
Calibration gain (speed)
functions No. 1 terminal
919 bias (torque/
magnetic flux)
No. 1 terminal
920 gain (torque/
F

(RS/RS2 Instruction)
Communication
Non-Protocol
magnetic flux)
Built-in frequency
setting
922 potentiometer

bias*7

Built-in frequency

G
setting

(FX2N-232IF)
Communication
Non-Protocol
923 potentiometer

gain*7
Motor
temperature
925
detection
calibration H
No. 6 terminal
Communication
Programming

926
bias (speed)

No. 6 terminal
927
gain (speed)
No. 6 terminal
928
bias (torque)
No. 6 terminal
I
929
Maintenance
Remote

gain (torque)
n14 PU buzzer sound
990 PU buzzer control 990 PU buzzer control 990 PU Buzzer control 990 PU buzzer control
(990) control
PU contrast PU contrast PU contrast PU contrast n15 PU contrast
Additional 991 991 991 991
adjustment adjustment adjustment adjustment (991) adjustment
functions
n16
PU main display Apx.A
screen data
models
Discontinued

(992)
selection

E-171
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL V500 Series FREQROL F500 Series FREQROL A500 Series FREQROL E500 Series FREQROL S500 Series
Pr Pr Pr Pr Pr
Function Name Name Name Name Name
No. No. No. No. No.
PU disconnection
Additional n17
detection/PU
functions (993)
setting lock

The parameters Pr. 77 and Pr. 79 cannot be written in computer link operation using the FR-A5NR.
*1. Can be read or written when the parameter Pr. 77 is set to "801".
*2. Can be read or written when the parameter Pr. 29 is set to "3".
*3. Indicates a parameter whose setting is ignored when the advanced magnetic flux vector control mode
is selected.
*4. Can be set when the parameters Pr. 80 and Pr. 81 are not set to "9999" and the parameter Pr. 60 is
set to "7" or "8".
*5. Can be read or written when the parameters Pr. 80 and Pr. 81 are not set to "9999" and the parameter
Pr. 77 is set to "801".
*6. Can be set only in the 200 V/100 V class.
*7. Cannot be used in inverter communication.
*8. This inverter communication function cannot read or write Pr. 37.
Set Pr. 37 to "0" when setting or monitoring the frequency in the PLC.
If any value other than "0" is set to Pr. 37 and the instruction code HFF is set to "01", the frequency
may not be set or monitored normally (in the 400 V class of the E500 series and S500 series).
(In the 200 V and 100 V classes of the E500 series, the frequency may not be set or monitored
normally if any value other than "0" is set to Pr. 37 without regard to the setting of the instruction code
HFF.)

E-172
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
12.5.2 Parameters in F700, A700, E700 and D700 Series

Common Items
The following parameters are provided in the F700, A700, E700 and D700 Series inverters. (For details, make
sure to refer to the respective inverter manual.)

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series B
Pr Pr Pr Pr

N:N Network
Function Name Name Name Name
No. No. No. No.
0 Torque boost 0 Torque boost 0 Torque boost 0 Torque boost
1 Maximum frequency 1 Maximum frequency 1 Maximum frequency 1 Maximum frequency
2 Minimum frequency 2 Minimum frequency 2 Minimum frequency 2 Minimum frequency
3 Base frequency 3 Base frequency 3 Base frequency 3 Base frequency C
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting

Parallel Link
4 4 4 4
(high speed) (high speed) (high speed) (high speed)

Basic functions Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
5 5 5 5
(middle speed) (middle speed) (middle speed) (middle speed)
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
6 6 6 6

7
(low speed)
Acceleration time 7
(low speed)
Acceleration time 7
(low speed)
Acceleration time 7
(low speed)
Acceleration time
D

Computer Link
8 Deceleration time 8 Deceleration time 8 Deceleration time 8 Deceleration time
Electronic thermal Electronic thermal Electronic thermal Electronic thermal
9 9 9 9
O/L relay O/L relay O/L relay O/L relay
DC injection brake DC injection brake DC injection brake DC injection brake
10 10 10 10

DC injection
operation frequency
DC injection brake
operation frequency
DC injection brake
operation frequency
DC injection brake
operation frequency
DC injection brake
E
11 11 11 11

Communication
Inverter
brake operation time operation time operation time operation time
DC injection brake DC injection brake DC injection brake DC injection brake
12 12 12 12
operation voltage operation voltage operation voltage operation voltage
13 Starting frequency 13 Starting frequency 13 Starting frequency 13 Starting frequency
14 Load pattern selection 14 Load pattern selection 14 Load pattern selection 14 Load pattern selection
15 Jog frequency 15 Jog frequency 15 Jog frequency 15 Jog frequency
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Jog operation Jog acceleration/ Jog acceleration/ Jog acceleration/ Jog acceleration/
16 16 16 16
deceleration time deceleration time deceleration time deceleration time
17 MRS input selection 17 MRS input selection 17 MRS input selection 17 MRS input selection
High speed maximum High speed maximum High speed maximum High speed maximum
18 18 18 18
frequency frequency frequency frequency
19 Base frequency voltage 19 Base frequency voltage 19 Base frequency voltage 19 Base frequency voltage G

(FX2N-232IF)
Communication
Non-Protocol
Acceleration/ Acceleration/ Acceleration/ Acceleration/
20 deceleration reference 20 deceleration reference 20 deceleration reference 20 deceleration reference
Acceleration/ frequency frequency frequency frequency
deceleration
times Acceleration/ Acceleration/ Acceleration/
21 deceleration time 21 deceleration time 21 deceleration time
increments increments
Stall prevention
increments
H
Stall prevention Stall prevention Stall prevention
Communication
Programming

22 22 operation level 22 22
operation level operation level operation level
(torque limit level )
Stall prevention Stall prevention Stall prevention Stall prevention Stall prevention
operation level operation level operation level operation level
23 23 23 23
compensation factor at compensation factor at compensation factor at compensation factor at
double speed double speed double speed double speed I
Multi-speed setting Multi-speed setting Multi-speed setting Multi-speed setting
Maintenance
Remote

24 24 24 24
(speed 4) (speed 4) (speed 4) (speed 4)
Multi-speed setting Multi-speed setting Multi-speed setting Multi-speed setting
25 25 25 25
Multispeed (speed 5) (speed 5) (speed 5) (speed 5)
setting Multi-speed setting Multi-speed setting Multi-speed setting Multi-speed setting
26 26 26 26
(speed 6) (speed 6) (speed 6) (speed 6)
Multi-speed setting Multi-speed setting Multi-speed setting Multi-speed setting
Apx.A
27 27 27 27
models
Discontinued

(speed 7) (speed 7) (speed 7) (speed 7)


Multi-speed input Multi-speed input
28 28
compensation selection compensation selection

E-173
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Acceleration/ Acceleration/ Acceleration/ Acceleration/
29 deceleration pattern 29 deceleration pattern 29 deceleration pattern 29 deceleration pattern
selection selection selection selection
Regenerative function Regenerative function Regenerative function Regenerative function
30 30 30 30
selection selection selection selection
31 Frequency jump 1A 31 Frequency jump 1A 31 Frequency jump 1A 31 Frequency jump 1A
32 Frequency jump 1B 32 Frequency jump 1B 32 Frequency jump 1B 32 Frequency jump 1B
33 Frequency jump 2A 33 Frequency jump 2A 33 Frequency jump 2A 33 Frequency jump 2A
Frequency jump
34 Frequency jump 2B 34 Frequency jump 2B 34 Frequency jump 2B 34 Frequency jump 2B
35 Frequency jump 3A 35 Frequency jump 3A 35 Frequency jump 3A 35 Frequency jump 3A
36 Frequency jump 3B 36 Frequency jump 3B 36 Frequency jump 3B 36 Frequency jump 3B
37 Speed display 37 Speed display 37 Speed display*1 37 Speed display*1
RUN key rotation RUN key rotation
40 40
direction selection direction selection
Uptofrequency Up-to-frequency Up-to-frequency Up-to-frequency
41 41 41 41
sensitivity sensitivity sensitivity sensitivity
Output frequency Output frequency Output frequency Output frequency
Frequency 42 42 42 42
detection detection detection detection
detection
Output frequency Output frequency Output frequency Output frequency
43 detection for reverse 43 detection for reverse 43 detection for reverse 43 detection for reverse
rotation rotation rotation rotation
Second acceleration/ Second acceleration/ Second acceleration/ Second acceleration/
44 44 44 44
deceleration time deceleration time deceleration time deceleration time
Second deceleration Second deceleration Second deceleration Second deceleration
45 45 45 45
time time time time
46 Second torque boost 46 Second torque boost 46 Second torque boost 46 Second torque boost
Second V/F Second V/F Second V/F Second V/F
47 47 47 47
(base frequency) (base frequency) (base frequency) (base frequency)
Second
functions Second stall prevention Second stall prevention Second stall prevention Second stall prevention
48 48 48 48
operation current operation current operation current operation current
Second stall prevention Second stall prevention
49 49
operation frequency operation frequency

Second output Second output
50 50
frequency detection frequency detection
Second electronic Second electronic Second electronic Second electronic
51 51 51 51
thermal O/L relay thermal O/L relay thermal O/L relay thermal O/L relay
DU/PU main display DU/PU main display DU/PU main display DU/PU main display
52 52 52 52
data selection data selection data selection data selection
FM terminal function FM terminal function FM terminal function FM terminal function
54 54 54 54
Monitor selection selection selection selection
functions Frequency monitoring Frequency monitoring Frequency monitoring Frequency monitoring
55 55 55 55
reference reference reference reference
Current monitoring Current monitoring Current monitoring Current monitoring
56 56 56 56
reference reference reference reference

57 Restart coasting time 57 Restart coasting time 57 Restart coasting time 57 Restart coasting time
Automatic
restart functions
58 Restart cushion time 58 Restart cushion time 58 Restart cushion time 58 Restart cushion time

Remote function Remote function Remote function Remote function


59 59 59 59
selection selection selection selection
Energy saving control Energy saving control Energy saving control Energy saving control
60 60 60 60
selection selection selection selection

E-174
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
61 Reference current 61 Reference current
Reference value at Reference value at
Automatic
62
acceleration
62
acceleration B
acceleration Reference value at Reference value at

N:N Network
/deceleration 63 63
deceleration deceleration
Starting frequency for
64
elevator mode
65 Retry selection 65 Retry selection 65 Retry selection 65 Retry selection


Stall prevention
66 operation reduction
Stall prevention
66 operation reduction
Stall prevention
66 operation reduction
Stall prevention
66 operation reduction
C

Parallel Link
starting frequency starting frequency starting frequency starting frequency
Number of retries at Number of retries at Number of retries at Number of retries at
67 67 67 67
alarm occurrence alarm occurrence fault occurrence fault occurrence
Retry 68 Retry waiting time 68 Retry waiting time 68 Retry waiting time 68 Retry waiting time
Retry count display Retry count display Retry count display Retry count display
69
erase
69
erase
69
erase
69
erase D

Computer Link
Special regenerative Special regenerative Special regenerative Special regenerative
70 70 70 70
brake duty brake duty brake duty brake duty
71 Applied motor 71 Applied motor 71 Applied motor 71 Applied motor
PWM frequency PWM frequency PWM frequency PWM frequency
72 72 72 72
selection selection selection selection
73 Analog input selection 73 Analog input selection 73 Analog input selection 73 Analog input selection E
74 Input filter time constant 74 Input filter time constant 74 Input filter time constant 74 Input filter time constant

Communication
Inverter
Reset selection/ Reset selection/ Reset selection/ Reset selection/
disconnected PU disconnected PU disconnected PU disconnected PU
75 75 75 75
detection/PU stop detection/PU stop detection/PU stop detection/PU stop
selection selection selection selection

76
Alarm code output
selection
76
Alarm code output
selection
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Parameter write Parameter write Parameter write Parameter write
77 77 77 77
selection selection selection selection
Reverse rotation Reverse rotation Reverse rotation Reverse rotation
78 78 78 78
prevention selection prevention selection prevention selection prevention selection
Operation mode Operation mode Operation mode Operation mode
79
selection
79
selection
79
selection
79
selection G
Motor capacity

(FX2N-232IF)
Communication
Non-Protocol
80 (simple magnetic flux 80 Motor capacity 80 Motor capacity 80 Motor capacity
vector control)
81 Number of motor poles 81 Number of motor poles
Simple 82 Motor excitation current 82 Motor excitation current 82 Motor excitation current
magnetic
flux vector

83 Motor rated voltage 83 Motor rated voltage 83 Motor rated voltage H
control 84 Rated motor frequency 84 Rated motor frequency 84 Rated motor frequency
Communication
Programming

Speed control gain


Speed control gain
89 89 (advanced magnetic
(magnetic flux vector)
flux vector)
90 Motor constant (R1) 90 Motor constant (R1) 90 Motor constant (R1) 90 Motor constant (R1)
91 Motor constant (R2) 91 Motor constant (R2)
I
92 Motor constant (L1) 92 Motor constant (L1)
Maintenance
Remote

93 Motor constant (L2) 93 Motor constant (L2)



94 Motor constant (X) 94 Motor constant (X)
Online auto tuning
95
selection

96
Auto tuning setting/
96
Auto tuning setting/
96
Auto tuning setting/ Apx.A
status status status
models
Discontinued

E-175
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
100 V/F1 (first frequency) 100 V/F1(first frequency)
V/F1 (first frequency V/F1(first frequency
101 101
voltage) voltage)
V/F2 (second
102 102 V/F2(second frequency)
frequency)
V/F2 (second frequency V/F2(second frequency
103 103
voltage) voltage)
Adjustable 5 104 V/F3 (third frequency) 104 V/F3(third frequency)
points V/F V/F3 (third frequency V/F3(third frequency
105 105
voltage) voltage)
106 V/F4 (fourth frequency) 106 V/F4(fourth frequency)
V/F4 (fourth frequency V/F4(fourth frequency
107 107
voltage) voltage)
108 V/F5 (fifth frequency) 108 V/F5(fifth frequency)

V/F5 (fifth frequency V/F5(fifth frequency
109 109
voltage) voltage)
Third acceleration/
110
deceleration time
111 Third deceleration time
112 Third torque boost
Third V/F (base
113
Third frequency)

functions Third stall prevention
114
operation current
Third stall prevention
115
operation frequency
Third output frequency
116
detection
PU communication PU communication PU communication PU communication
117 117 117 117
station station number station number station number
PU communication PU communication PU communication PU communication
118 118 118 118
speed speed speed speed
PU communication stop PU communication stop PU communication stop PU communication stop
119 119 119 119
bit length. bit length bit length bit length
PU communication PU communication PU communication PU communication
120 120 120 120
parity check parity check parity check parity check
PU connector
communication 121 Number of PU 121
Number of PU
121
Number of PU
121
Number of PU
communication retries communication retries communication retries communication retries
PU communication PU communication PU communication PU communication
122 122 122 122
check time interval check time interval check time interval check time interval
PU communication PU communication PU communication PU communication
123 123 123 123
waiting time setting waiting time setting waiting time setting waiting time setting
PU communication CR/ PU communication CR/
PU communication PU communication
124 LF presence/absence 124 LF presence/absence 124 124
CR/LF selection CR/LF selection
selection selection
Terminal 2 frequency Terminal 2 frequency Terminal 2 frequency Terminal 2 frequency
125 125 125 125
setting gain frequency setting gain frequency setting gain frequency setting gain frequency
Terminal 4 frequency Terminal 4 frequency Terminal 4 frequency Terminal 4 frequency
126 126 126 126
setting gain frequency setting gain frequency setting gain frequency setting gain frequency

E-176
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
PID control automatic PID control automatic PID control automatic PID control automatic
127 127 127 127
switchover frequency switchover frequency switchover frequency switchover frequency
128 PID action selection 128 PID action selection 128 PID action selection 128 PID action selection B
129 PID proportional band 129 PID proportional band 129 PID proportional band 129 PID proportional band

N:N Network
PID operation 130 PID integral time 130 PID integral time 130 PID integral time 130 PID integral time
131 PID maximum 131 PID upper limit 131 PID upper limit 131 PID upper limit
132 PID minimum 132 PID lower limit 132 PID lower limit 132 PID lower limit
133 PID action set point 133 PID action set point 133 PID action set point 133 PID action set point
134 PID differential time 134 PID differential time 134 PID differential time 134 PID differential time C

Parallel Link
Commercial power-
supply switchover Electronic bypass
135 135
sequence output sequence selection
terminal selection
MC switchover interlock MC switchover interlock
136 136
Commercial
time
137 Waiting time at a start
time
137 Start waiting time
D
power

Computer Link
supply-inverter Commercial power-
switch-over supply operation Bypass selection at an
138 138
switchover selection at alarm
an alarm
Automatic switchover
139
frequency between
Automatic switchover
139 frequency from inverter E
inverter and commercial
to bypass operation

Communication
Inverter
power-supply operation
Backlash acceleration Backlash acceleration
140 140
stopping frequency stopping frequency
Backlash acceleration Backlash acceleration
141 141
stopping time stopping time
Backlash
measures Backlash deceleration Backlash deceleration
F
142 142
stopping frequency stopping frequency

(RS/RS2 Instruction)
Communication
Non-Protocol
Backlash deceleration Backlash deceleration
143 143
stopping time stopping time
Speed setting Speed setting
144 144
switchover switchover

PU 145
PU display language
145
PU display language
145
PU display language
145
PU display language G
selection selection selection selection

(FX2N-232IF)
Communication
Non-Protocol
Built-in potentiometer Built-in potentiometer
146 146
switching switching
Stall prevention level at Stall prevention level at
148 148
0V input. 0V input

149
Stall prevention level at
10V input.
149
Stall prevention level at
10V input
H
Communication
Programming

Output current detection Output current detection Output current detection Output current detection
150 150 150 150
Current level level level level
detection Output current detection Output current detection Output current detection Output current detection
151 151 151 151
signal delay time signal delay time signal delay time signal delay time
Zero current detection Zero current detection Zero current detection Zero current detection
152
level
152
level
152
level
152
level I
Zero current detection Zero current detection Zero current detection Zero current detection
Maintenance
Remote

153 153 153 153


time time time time
Voltage reduction Voltage reduction
154 selection during stall 154 selection during stall
prevention operation prevention operation

RT signal function
155
RT signal reflection time
155 validity condition
Apx.A
selection
selection
models
Discontinued

Stall prevention Stall prevention Stall prevention Stall prevention


156 156 156 156
operation selection operation selection operation selection operation selection

E-177
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
157 OL signal output timer 157 OL signal output timer 157 OL signal output timer 157 OL signal output timer
AM terminal function AM terminal function
158 158
selection selection
Automatic switchover
Automatic switchover
ON range
frequency range from
159 between commercial 159
bypass to inverter
powersupply and
operation
inverter operation
User group read User group read User group read Extended function
160 160 160 160
selection selection selection display selection
Frequency setting/key Frequency setting/key Frequency setting/key Frequency setting/key
161 161 161 161
lock operation selection lock operation selection lock operation selection lock operation selection
Automatic restart after Automatic restart after Automatic restart after Automatic restart after
162 instantaneous power 162 instantaneous power 162 instantaneous power 162 instantaneous power
failure selection failure selection failure selection failure selection
First cushion time for First cushion time for
163 163
Automatic restart restart

restart functions First cushion voltage for First cushion voltage for
164 164
restart restart
Stall prevention Stall prevention Stall prevention Stall prevention
165 operation level for 165 operation level for 165 operation level for 165 operation level for
restart restart restart restart
Output current detection Output current detection Output current detection
166 166 166
Current signal retention time signal retention time signal retention time

detection Output current detection Output current detection Output current detection
167 167 167
operation selection operation selection operation selection
Cumulative power
170 170 Watt-hour meter clear 170 Watt-hour meter clear 170 Watt-hour meter clear
Cumulative meter clear
monitor clear Operation hour meter Operation hour meter Operation hour meter Operation hour meter
171 171 171 171
clear clear clear clear
User group registered User group registered User group registered
172 172 172
display/batch clear display/batch clear display/batch clear
User group
173 User group registration 173 User group registration 173 User group registration
174 User group clear 174 User group clear 174 User group clear
STF terminal function STF terminal function STF terminal function STF terminal function
178 178 178 178
selection selection selection selection
STR terminal function STR terminal function STR terminal function STR terminal function
179 179 179 179
selection selection selection selection
RL terminal function RL terminal function RL terminal function RL terminal function
180 180 180 180
selection selection selection selection
RM terminal function RM terminal function RM terminal function RM terminal function
181 181 181 181
selection selection selection selection
RH terminal function RH terminal function RH terminal function RH terminal function
182 182 182 182
selection selection selection selection
RT terminal function RT terminal function MRS terminal function
Input terminal 183 183 183
selection selection selection
function
assignment AU terminal function AU terminal function RES terminal function
184 184 184
selection selection selection
JOG terminal function JOG terminal function
185 185
selection selection
CS terminal function CS terminal function
186 186
selection selection
MRS terminal function MRS terminal function
187 187
selection selection
STOP terminal function STOP terminal function
188 188
selection selection
RES terminal function RES terminal function
189 189
selection selection

E-178
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
RUN terminal function RUN terminal function RUN terminal function RUN terminal function
190 190 190 190
selection selection selection selection

191
SU terminal function
selection
191
SU terminal function
selection
191
FU terminal function
selection
B

N:N Network
IPF terminal function IPF terminal function A,B,C terminal function A,B,C terminal function
192 192 192 192
selection selection selection selection
Output terminal
OL terminal function OL terminal function
function 193 193
selection selection
assignment
194
FU terminal function
selection
194
FU terminal function
selection C

Parallel Link
ABC1 terminal function ABC1 terminal function
195 195
selection selection
ABC2 terminal function ABC2 terminal function
196 196
selection selection
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
232
(speed 8)
232
(speed 8)
232
(speed 8)
232
(speed 8) D
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting

Computer Link
233 233 233 233
(speed 9) (speed 9) (speed 9) (speed 9)
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
234 234 234 234
(speed 10) (speed 10) (speed 10) (speed 10)
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
235 235 235 235
Multispeed
setting
(speed 11)
Multispeed setting
(speed 11)
Multi-speed setting
(speed 11)
Multi-speed setting
(speed 11)
Multi-speed setting
E
236 236 236 236

Communication
Inverter
(speed 12) (speed 12) (speed 12) (speed 12)
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
237 237 237 237
(speed 13) (speed 13) (speed 13) (speed 13)
Multispeed setting Multi-speed setting Multi-speed setting Multi-speed setting
238 238 238 238
(speed 14) (speed 14) (speed 14) (speed 14)

239
Multispeed setting
239
Multi-speed setting
239
Multi-speed setting
239
Multi-speed setting F
(speed 15) (speed 15) (speed 15) (speed 15)

(RS/RS2 Instruction)
Communication
Non-Protocol
SoftPWM operation Soft-PWM operation Soft-PWM operation Soft-PWM operation
240 240 240 240
selection selection selection selection
Analog input display Analog input display Analog input display Analog input display
241 241 241 241
unit switchover unit switchover unit switchover unit switchover


Terminal 1 added
242 compensation amount
Terminal 1 added
242 compensation amount
G

(FX2N-232IF)
Communication
Non-Protocol
(terminal 2) (terminal 2)

Terminal 1 added Terminal 1 added
243 compensation amount 243 compensation amount
(terminal 4) (terminal 4)
Cooling fan operation Cooling fan operation Cooling fan operation Cooling fan operation
244
selection
244
selection
244
selection
244
selection H
245 Rated slip 245 Rated slip 245 Rated slip 245 Rated slip
Communication
Programming

Slip compensation time Slip compensation time Slip compensation time Slip compensation time
246 246 246 246
Slip constant constant constant constant
compensation Constant-power region Constant-power region Constant-power region Constant-power range
247 slip compensation 247 slip compensation 247 slip compensation 247 slip compensation
selection selection selection
Earth (ground) fault
selection
Earth (ground) fault
I
249 249
Maintenance
Remote

detection at start detection at start


250 Stop selection 250 Stop selection 250 Stop selection 250 Stop selection
Output phase failure Output phase failure Output phase loss Output phase loss
251 251 251 251
protection selection protection selection protection selection protection selection
Frequency 252 Override bias 252 Override bias
compensation Apx.A
function 253 Override gain 253 Override gain
models
Discontinued

E-179
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
255 Life alarm status display 255 Life alarm status display 255 Life alarm status display 255 Life alarm status display
Inrush current limit Inrush current limit Inrush current limit Inrush current limit
256 256 256 256
circuit life display circuit life display circuit life display circuit life display
Control circuit capacitor Control circuit capacitor Control circuit capacitor Control circuit capacitor
257 257 257 257
Life check life display life display life display life display
Main circuit capacitor Main circuit capacitor Main circuit capacitor Main circuit capacitor
258 258 258 258
life display life display life display life display
Main circuit capacitor Main circuit capacitor Main circuit capacitor Main circuit capacitor
259 259 259 259
life measuring life measuring life measuring life measuring
PWM frequency PWM frequency
260 260
automatic switchover automatic switchover
Power failure stop Power failure stop Power failure stop Power failure stop
261 261 261 261
selection selection selection selection
Subtracted frequency at Subtracted frequency at
262 262
deceleration start deceleration start
Subtraction starting Subtraction starting
263 263
frequency frequency
Power failure
stop Powerfailure Power-failure
264 264
deceleration time 1 deceleration time 1
Powerfailure Power-failure
265 265
deceleration time 2 deceleration time 2
Power failure Power failure
266 deceleration time 266 deceleration time
switchover frequency switchover frequency
Terminal 4 input Terminal 4 input Terminal 4 input Terminal 4 input
267 267 267 267
selection selection selection selection
Monitor decimal digits Monitor decimal digits Monitor decimal digits Monitor decimal digits
268 268 268 268
selection selection selection selection
Stop-on contact/load
torque high speed Stop-on contact control
270 270
frequency control selection
selection
High-speed setting
271
maximum current
Middle-speed setting
Load torque 272
minimum current
high speed fre-
quency control Current averaging
273
range
Current averaging filter
274
time constant
Stop-on contact
Stop-on contact
excitation current
275 excitation current low 275
Stop-on con- low speed multiplying
speed multiplying factor
tact control factor
PWM carrier frequency PWM carrier frequency
276 276
at stop-on contact at stop-on contact
Stall prevention
277 operation current
switchover

E-180
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Brake opening Brake opening
278 278
frequency frequency
279 Brake opening current 279 Brake opening current B
Brake opening current Brake opening current

N:N Network
280 280
detection time detection time
Brake operation time at Brake operation time at
281 281
start start
Brake Brake operation Brake operation
sequence 282 282
function
frequency
Brake operation time at
frequency
Brake operation time at
C
283 283

Parallel Link
stop stop
Deceleration detection
284
function selection
Overspeed detection
frequency (Speed
285
deviation excess
detection frequency)

D

Computer Link
286 Droop gain 286 Droop gain
Droop filter time Droop filter time
287 287
Droop control constant constant
Droop function
288


activation selection
291 Pulse train I/O selection

E

Communication
Inverter
Automatic acceleration/ Automatic acceleration/
292 292
deceleration deceleration
Acceleration/ Acceleration/
293 deceleration separate 293 deceleration separate
selection selection

294
UV avoidance voltage

F
gain

(RS/RS2 Instruction)
Communication
Non-Protocol
Magnitude of frequency Magnitude of frequency
295 295
change setting change setting
Password 296 Password lock level

function 297 Password lock/unlock
298 Frequency search gain 298 Frequency search gain G
Rotation direction Rotation direction Rotation direction Rotation direction

(FX2N-232IF)
Communication
Non-Protocol
299 detection selection at 299 detection selection at 299 detection selection at 299 detection selection at
restarting restarting restarting restarting
300 BCD input bias 300 BCD input bias
301 BCD input gain 301 BCD input gain
302 BIN input bias 302 BIN input bias H
303 BIN input gain 303 BIN input gain
Communication
Programming

Digital input
Digital input and analog Digital input and analog
304 input compensation 304 input compensation
enable/disable selection enable/disable selection
Read timing operation Read timing operation
305 305
selection selection
I
Maintenance
Remote

Apx.A
models
Discontinued

E-181
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Analog output signal Analog output signal
306 306
selection selection
Setting for zero analog Setting for zero analog
307 307
output output
Setting for maximum Setting for maximum
308 308
analog output analog output
Analog output signal Analog output signal
309 voltage/current 309 voltage/current
Analog output
switchover switchover
Analog meter voltage Analog meter voltage
310 310
output selection output selection
Setting for zero analog Setting for zero analog
311 311
meter voltage output meter voltage output
Setting for maximum Setting for maximum
312 analog meter voltage 312 analog meter voltage
output output

313 DO0 output selection 313 DO0 output selection
314 DO1 output selection 314 DO1 output selection
315 DO2 output selection 315 DO2 output selection
Digital output 316 DO3 output selection 316 DO3 output selection
317 DO4 output selection 317 DO4 output selection
318 DO5 output selection 318 DO5 output selection

319 DO6 output selection 319 DO6 output selection
320 RA1 output selection 320 RA1 output selection
Relay output 321 RA2 output selection 321 RA2 output selection
322 RA3 output selection 322 RA3 output selection
323 AM0 0V adjustment 323 AM0 0V adjustment
Analog output
324 AM1 0mA adjustment 324 AM1 0mA adjustment
Digital input unit Digital input unit
329 329
selection selection
RS-485 communication RS-485 communication
331 331
station station number
RS-485 communication RS-485 communication
332 332
speed speed
RS-485 communication RS-485 communication
333 333
stop bit length stop bit length
RS-485 RS-485 communication RS-485 communication
334 334
communication parity check selection parity check selection
RS-485 communication RS-485 communication
335 335
number of retries retry count
RS-485 communication RS-485 communication
336 336
check time interval check time interval
RS-485 communication RS-485 communication
337 337
waiting time setting waiting time setting

E-182
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Communication Communication Communication Communication
338 operation command 338 operation command 338 operation command 338 operation command
source
Communication speed
source
Communication speed
source
Communication speed
source
Communication speed
B
339 339 339 339

N:N Network
command source command source command source command source
Communication startup Communication startup Communication startup Communication startup
340 340 340 340
RS-485 mode selection mode selection mode selection mode selection
communication RS-485 communication RS-485 communication
341 341
CR/LF selection CR/LF selection
Communication Communication Communication Communication C
342 EEPROM write 342 EEPROM write 342 EEPROM write 342 EEPROM write

Parallel Link
selection selection selection selection
Communication error Communication error Communication error Communication error
343 343 343 343
count count count count
345 DeviceNet address
DeviceNet
346 DeviceNet baud rate
D
Communication reset

Computer Link
CCLink 349
selection
380 Acceleration S-pattern 1
Deceleration S-pattern
S-pattern 381
1
acceleration/
deceleration C 382 Acceleration S-pattern 2 E
Deceleration S-pattern
383

Communication
Inverter
2

Input pulse division
384
scaling factor
Frequency for 0 input
Pulse train input 385
pulse
Frequency for

F
386
maximum input pulse

(RS/RS2 Instruction)
Communication
Non-Protocol
Initial communication
387
delay time
Send time interval at
388
heart beat

389
Minimum sending time G
LONWORKS at heart beat

(FX2N-232IF)
Communication
Non-Protocol

communication % setting reference
390
frequency
Receive time interval at
391
heart beat

392
Event driven detection
width
H
Communication
Programming

450 Second applied motor 450 Second applied motor 450 Second applied motor
Second motor control
451
method selection
453 Second motor capacity

454
Number of second
motor poles I
Second motor
Maintenance
Remote

Second motor excitation


constants 455
current
Rated second motor
456
voltage
Rated second motor
457
frequency Apx.A
Second motor constant
models
Discontinued

458
(R1)

E-183
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Second motor constant
459
(R2)
Second motor constant
460
(L1)
Second motor Second motor constant
461
constants (L2)
Second motor constant
462
(X)
Second motor auto
463
tuning setting/status
Remote output Remote output Remote output Remote output
495 495 495 495
selection selection selection selection
Remote output
496 Remote output data 1 496 Remote output data 1 496 Remote output data 1 496 Remote output data 1
497 Remote output data 2 497 Remote output data 2 497 Remote output data 2
Communication error Communication error
500 500
execution waiting time execution waiting time

Communication error Communication error
Communication
501 occurrence count 501 occurrence count
error
display display
Stop mode selection at Stop mode selection at Stop mode selection at
502 502 502
communication error communication error communication error
503 Maintenance timer 503 Maintenance timer 503 Maintenance timer 503 Maintenance timer
Maintenance Maintenance timer Maintenance timer Maintenance timer Maintenance timer
504 504 504 504
alarm output set time alarm output set time alarm output set time alarm output set time
S-pattern time at a start
516
of acceleration
S-pattern time at a
517 completion of
S-pattern accel- acceleration
eration/deceler-
ation D S-pattern time at a start
518
of deceleration
S-pattern time at a
519 completion of
deceleration
Frequency command
541
sign selection (CC-Link)
Communication station Communication station
542 542
number (CCLink) number (CCLink)
CCLink
Baud rate selection
543 Baud rate (CCLink) 543
(CC-Link)
CC-Link extended CC-Link extended
544 544
setting setting
USB communication USB communication
547 547
station number station number
USB
USB communication USB communication
548 548
check time interval check time interval
549 Protocol selection 549 Protocol selection 549 Protocol selection 549 Protocol selection
NET mode operation NET mode operation NET mode operation
550 command source 550 command source 550 command source
Communication selection selection selection
PU mode operation PU mode operation PU mode operation PU mode operation
551 command source 551 command source 551 command source 551 command source
selection selection selection selection
555 Current average time 555 Current average time 555 Current average time 555 Current average time
Current 556 Data output mask time 556 Data output mask time 556 Data output mask time 556 Data output mask time
average Current average value Current average value Current average value Current average value
monitor 557 monitor signal output 557 monitor signal output 557 monitor signal output 557 monitor signal output
reference current reference current reference current reference current

E-184
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
PTC thermistor
561
protection level

563
Energization time
carrying-over times
563
Energization time
carrying-over times
563
Energization time
carrying-over times
563
Energization time
carrying-over times
B

N:N Network
Operating time Operating time Operating time Operating time
564 564 564 564
carryingover times carryingover times carryingover times carryingover times
Second
Second motor speed
motor 569
control gain
constants
571 Holding time at a start 571 Holding time at a start 571 Holding time at a start 571 Holding time at a start C

Parallel Link
Second motor online
574
auto tuning
Output interruption Output interruption Output interruption
575 575 575
detection time detection time detection time

Output interruption Output interruption Output interruption
PID control 576
detection level
576
detection level
576
detection level D
Output interruption Output interruption Output interruption

Computer Link
577 577 577
release level cancel level cancel level
Acceleration time at a Acceleration time at a Acceleration time at a Acceleration time at a
611 611 611 611
restart restart restart restart
Speed smoothing Speed smoothing
653 653
control
Regeneration
control
Regeneration
E

Communication
Inverter
665 avoidance frequency 665 avoidance frequency
gain gain
Tuning data unit
684
switchover
Control method Control method
800
selection
800
selection F
Constant power range

(RS/RS2 Instruction)
Communication
Non-Protocol
803 torque characteristic
selection
Torque command
Torque 804
source selection
command
805
Torque command value
(RAM) G

(FX2N-232IF)
Communication
Non-Protocol
Torque command value
806
(RAM,EEPROM)
807 Speed limit selection

Forward rotation speed
808
Speed limit limit

809
Reverse rotation speed H
limit
Communication
Programming

Torque limit input


810
method selection
Set resolution
811
switchover

812
Torque limit level
(regeneration)
I
Maintenance
Remote

Torque limit level


813
Torque limit (3rd quadrant)
Torque limit level
814
(4th quadrant)
815 Torque limit level 2
Torque limit level during
Apx.A
816
acceleration
models
Discontinued

Torque limit level during


817
deceleration

E-185
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Easy gain tuning
818
Easy gain response level setting
tuning Easy gain tuning
819
selection
820 Speed control P gain 1
Speed control integral
821
time 1
822 Speed setting filter 1
824 Torque control P gain 1
Torque control integral
825
time 1
826 Torque setting filter 1
827 Torque detection filter 1
Adjustment Model speed control
828
function gain

830 Speed control P gain 2
Speed control integral
831
time 2
832 Speed setting filter2
834 Torque control P gain 2

Torque control integral
835
time 2
836 Torque setting filter2
837 Torque detection filter 2
Analog input off set
849
adjustment
Control operation
850
selection
Terminal 4 function
858
assignment
859 Torque current 859 Torque current
Torque bias
Second motor torque
860
current
Notch filter time
862
constant
863 Notch filter depth
864 Torque detection

865 Low speed detection
Indication Torque monitoring
866
function reference
867 AM output filter 867 AM output filter
Terminal 1 function
868
assignment
Input phase failure Input phase failure Input phase loss Input phase loss
872 872 872 872
Protective protection selection protection selection protection selection protection selection
Functions 874 OLT level setting

875 Fault definition

E-186
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Speed feed forward
877 control/model adaptive
speed control selection
Speed feed forward
B
878

N:N Network
Control system filter

functions Speed feed forward
879
torque limit
880 Load inertia ratio

881
Speed feed forward
gain C

Parallel Link
Regeneration Regeneration Regeneration Regeneration
882 avoidance operation 882 avoidance operation 882 avoidance operation 882 avoidance operation
selection selection selection selection
Regeneration Regeneration Regeneration Regeneration
883 avoidance operation 883 avoidance operation 883 avoidance operation 883 avoidance operation

Regeneration
level
Regeneration
level
Regeneration
level level
D

Computer Link
avoidance avoidance at avoidance at
884 884
function deceleration detection deceleration detection
sensitivity sensitivity
Regeneration avoidance Regeneration avoidance Regeneration avoidance Regeneration avoidance
885 compensation 885 compensation 885 compensation 885 compensation
frequency limit value frequency limit value frequency limit value frequency limit value E
Regeneration Regeneration Regeneration Regeneration avoidance

Communication
Inverter
886 886 886 886
avoidance voltage gain avoidance voltage gain avoidance voltage gain voltage gain
888 Free parameter 1 888 Free parameter 1 888 Free parameter 1 888 Free parameter 1
Free parameter
889 Free parameter 2 889 Free parameter 2 889 Free parameter 2 889 Free parameter 2
Cumulative power Cumulative power Cumulative power
891 monitor digit shifted
times
891 monitor digit shifted
times
891 monitor digit shifted
times
F

(RS/RS2 Instruction)
Communication
Non-Protocol
892 Load factor 892 Load factor
Energy saving monitor Energy saving monitor
893 reference 893 reference
(motor capacity) (motor capacity)
Control selection during Control selection during

Energy saving
894 commercial power 894 commercial power- G
supply operation supply operation

(FX2N-232IF)
Communication
Non-Protocol
monitor
Power saving rate Power saving rate
895 895
reference value reference value
896 Power unit cost 896 Power unit cost
Power saving monitor Power saving monitor
897 897
average time
Power saving
average time
Power saving
H
898 898
Communication
Programming

cumulative monitor clear cumulative monitor clear


Operation time rate Operation time rate
899 899
(estimated value) (estimated value)

I
Maintenance
Remote

Apx.A
models
Discontinued

E-187
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
C0 C0 C0 C0
FM terminal calibration FM terminal calibration FM terminal calibration FM terminal calibration
(900) (900) (900) (900)
C1 C1
AM terminal calibration AM terminal calibration
(901) (901)
C2 Terminal 2 frequency C2 Terminal 2 frequency C2 Terminal 2 frequency C2 Terminal 2 frequency
(902) setting bias frequency (902) setting bias frequency (902) setting bias frequency (902) setting bias frequency
C3 Terminal 2 frequency C3 Terminal 2 frequency C3 Terminal 2 frequency C3 Terminal 2 frequency
(902) setting bias (902) setting bias (902) setting bias (902) setting bias
125 Terminal 2 frequency 125 Terminal 2 frequency 125 Terminal 2 frequency 125 Terminal 2 frequency
(903) setting gain frequency (903) setting gain frequency (903) setting gain frequency (903) setting gain frequency
C4 Terminal 2 frequency C4 Terminal 2 frequency C4 Terminal 2 frequency C4 Terminal 2 frequency
(903) setting gain (903) setting gain (903) setting gain (903) setting gain
C5 Terminal 4 frequency C5 Terminal 4 frequency C5 Terminal 4 frequency C5 Terminal 4 frequency
(904) setting bias frequency (904) setting bias frequency (904) setting bias frequency (904) setting bias frequency
C6 Terminal 4 frequency C6 Terminal 4 frequency C6 Terminal 4 frequency C6 Terminal 4 frequency
(904) setting bias (904) setting bias (904) setting bias (904) setting bias
126 Terminal 4 frequency 126 Terminal 4 frequency 126 Terminal 4 frequency 126 Terminal 4 frequency
(905) setting gain frequency (905) setting gain frequency (905) setting gain frequency (905) setting gain frequency
C7 Terminal 4 frequency C7 Terminal 4 frequency C7 Terminal 4 frequency C7 Terminal 4 frequency
(905) setting gain (905) setting gain (905) setting gain (905) setting gain
C12 Bias frequency (speed)
(917) for terminal No.1
C13 Bias (speed) for
Calibration (917) terminal No.1
parameters
C14 Gain frequency (speed)
(918) for terminal No.1
C15 Gain (speed) for
(918) terminal No.1

C16 Bias command (torque)
(919) for terminal No.1
C17 Bias (torque) for
(919) terminal No.1
C18 Gain command (torque)
(920) for terminal No.1
C19 Gain (torque) for
(920) terminal No.1
Frequency setting Frequency setting
C22 C22
voltage bias frequency voltage bias frequency
(922) (922)
(built-in potentiometer) (built-in potentiometer)
Frequency setting Frequency setting
C23 C23
voltage bias voltage bias
(922) (922)
(built-in potentiometer) (built-in potentiometer)

Frequency setting Frequency setting
C24 C24
voltage gain frequency voltage gain frequency
(923) (923)
(built-in potentiometer) (built-in potentiometer)
Frequency setting Frequency setting
C25 C25
voltage gain voltage gain
(923) (923)
(built-in potentiometer) (built-in potentiometer)

E-188
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F700 Series FREQROL A700 Series FREQROL E700 Series FREQROL D700 Series

Common Items
Pr Pr Pr Pr
Function Name Name Name Name
No. No. No. No.
Terminal 4 bias
C38
command
(932)
(torque/magnetic flux)
C39 Terminal 4 bias
B

N:N Network
Calibration (932) (torque/magnetic flux)

parameters Terminal 4 gain
C40
command
(933)
(torque/magnetic flux)
C41 Gain (torque) for
(933) terminal No.4 C
Parameter copy alarm

Parallel Link
989
release
990 PU buzzer control 990 PU buzzer control 990 PU buzzer control 990 PU buzzer control
PU
991 PU contrast adjustment 991 PU contrast adjustment 991 PU contrast adjustment 991 PU contrast adjustment

*1. This inverter communication function cannot read or write Pr. 37.
Set Pr. 37 to "0" when setting or monitoring the frequency in the PLC. D
If any value other than "0" is set and the instruction code HFF is set to "01", the frequency may not be

Computer Link
set or monitored normally.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

E-189
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

12.5.3 Parameters in F800 and A800 Series


The following parameters are provided in FREQROL inverters. Pr. No.1000 and later are not supported.
(For details, make sure to refer to the respective inverter manual.)
FREQROL F800 Series FREQROL A800 Series
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
0 G000 Torque boost 0 G000 Torque boost
1 H400 Maximum frequency 1 H400 Maximum frequency
2 H401 Minimum frequency 2 H401 Minimum frequency
3 G001 Base frequency 3 G001 Base frequency
4 D301 Multi-speed setting (high speed) 4 D301 Multi-speed setting (high speed)
Basic functions 5 D302 Multi-speed setting (middle speed) 5 D302 Multi-speed setting (middle speed)
6 D303 Multi-speed setting (low speed) 6 D303 Multi-speed setting (low speed)
7 F010 Acceleration time 7 F010 Acceleration time
8 F011 Deceleration time 8 F011 Deceleration time
H000 Electronic thermal O/L relay H000 Electronic thermal O/L relay
9 9
C103 Rated motor current C103 Rated motor current
DC injection brake operation DC injection brake operation
10 G100 10 G100
DC injection frequency frequency
brake 11 G101 DC injection brake operation time 11 G101 DC injection brake operation time
12 G110 DC injection brake operation voltage 12 G110 DC injection brake operation voltage
13 F102 Starting frequency 13 F102 Starting frequency
14 G003 Load pattern selection 14 G003 Load pattern selection
15 D200 Jog frequency 15 D200 Jog frequency
Jog operation
16 F002 Jog acceleration/deceleration time 16 F002 Jog acceleration/deceleration time
17 T720 MRS input selection 17 T720 MRS input selection
18 H402 High speed maximum frequency 18 H402 High speed maximum frequency
- 19 G002 Base frequency voltage 19 G002 Base frequency voltage
Acceleration/deceleration reference Acceleration/deceleration reference
Acceleration/ 20 F000 20 F000
frequency frequency
deceleration
times Acceleration/deceleration time Acceleration/deceleration time
21 F001 21 F001
increments increments
Stall prevention operation level
22 H500 Stall prevention operation level 22 H500
(Torque limit level)
Stall prevention Stall prevention operation level Stall prevention operation level
23 H610 compensation factor at double 23 H610 compensation factor at double
speed speed
24 D304 Multi-speed setting (4 speed) 24 D304 Multi-speed setting (4 speed)
Multi-speed 25 D305 Multi-speed setting (5 speed) 25 D305 Multi-speed setting (5 speed)
setting 26 D306 Multi-speed setting (6 speed) 26 D306 Multi-speed setting (6 speed)
27 D307 Multi-speed setting (7 speed) 27 D307 Multi-speed setting (7 speed)
Multi-speed input compensation Multi-speed input compensation
28 D300 28 D300
selection selection
Acceleration/deceleration pattern Acceleration/deceleration pattern
29 F100 29 F100
selection selection
30 E300 Regenerative function selection 30 E300 Regenerative function selection
31 H420 Frequency jump 1A 31 H420 Frequency jump 1A
32 H421 Frequency jump 1B 32 H421 Frequency jump 1B
33 H422 Frequency jump 2A 33 H422 Frequency jump 2A
Frequency jump
34 H423 Frequency jump 2B 34 H423 Frequency jump 2B
35 H424 Frequency jump 3A 35 H424 Frequency jump 3A
36 H425 Frequency jump 3B 36 H425 Frequency jump 3B

E-190
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
37 M000 Speed display 37 M000 Speed display
41 M441 Up-to-frequency sensitivity 41 M441 Up-to-frequency sensitivity
Frequency 42 M442 Output frequency detection 42 M442 Output frequency detection
B

N:N Network
detection Output frequency detection for Output frequency detection for
43 M443 43 M443
reverse rotation reverse rotation
Second acceleration/deceleration Second acceleration/deceleration
44 F020 44 F020
time time
45 F021 Second deceleration time 45 F021 Second deceleration time
C
46 G010 Second torque boost 46 G010 Second torque boost

Parallel Link
47 G011 Second V/F (base frequency) 47 G011 Second V/F (base frequency)
Second Second stall prevention operation Second stall prevention operation
48 H600 48 H600
functions level level
Second stall prevention operation Second stall prevention operation
49 H601 49 H601
frequency frequency D
50 M444 Second output frequency detection 50 M444 Second output frequency detection

Computer Link
H010 Second electronic thermal O/L relay H010 Second electronic thermal O/L relay
51 51
C203 Rated second motor current C203 Rated second motor current
Operation panel main monitor Operation panel main monitor
52 M100 52 M100
selection selection
Monitor 54 M300 FM/CA terminal function selection 54 M300 FM/CA terminal function selection E
functions

Communication
Inverter
55 M040 Frequency monitoring reference 55 M040 Frequency monitoring reference
56 M041 Current monitoring reference 56 M041 Current monitoring reference
Automatic 57 A702 Restart coasting time 57 A702 Restart coasting time
restart 58 A703 Restart cushion time 58 A703 Restart cushion time
59 F101 Remote function selection 59 F101 Remote function selection F
60 G030 Energy saving control selection 60 G030 Energy saving control selection

(RS/RS2 Instruction)
Communication
Non-Protocol
61 F510 Reference current
Automatic 62 F511 Reference value at acceleration
acceleration/
deceleration 63 F512 Reference value at deceleration
64 F520 Starting frequency for elevator mode
G
65 H300 Retry selection 65 H300 Retry selection

(FX2N-232IF)
Communication
Non-Protocol
Stall prevention operation reduction Stall prevention operation reduction
66 H611 66 H611
starting frequency starting frequency
67 H301 Number of retries at fault occurrence 67 H301 Number of retries at fault occurrence
Retry 68 H302 Retry waiting time 68 H302 Retry waiting time
69 H303 Retry count display erase 69 H303 Retry count display erase H
Communication
Programming

70 G107 Special regenerative brake duty


71 C100 Applied motor 71 C100 Applied motor
- 72 E600 PWM frequency selection 72 E600 PWM frequency selection
73 T000 Analog input selection 73 T000 Analog input selection
74 T002 Input filter time constant 74 T002 Input filter time constant I
Reset selection/disconnected PU Reset selection/disconnected PU
Maintenance
Remote


detection/PU stop selection detection/PU stop selection
E100 Reset selection E100 Reset selection
75 75
E101 Disconnected PU detection E101 Disconnected PU detection
E102 PU stop selection E102 PU stop selection
E107 Reset limit E107 Reset limit Apx.A
models
Discontinued

76 M510 Fault code output selection 76 M510 Fault code output selection
77 E400 Parameter write selection 77 E400 Parameter write selection

E-191
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
78 D020 Reverse rotation prevention selection 78 D020 Reverse rotation prevention selection
79 D000 Operation mode selection 79 D000 Operation mode selection
80 C101 Motor capacity 80 C101 Motor capacity
81 C102 Number of motor poles 81 C102 Number of motor poles
82 C125 Motor excitation current 82 C125 Motor excitation current
83 C104 Rated motor voltage 83 C104 Rated motor voltage
84 C105 Rated motor frequency 84 C105 Rated motor frequency
Speed control gain Speed control gain
89 G932 89 G932
(Advanced magnetic flux vector) (Advanced magnetic flux vector)
90 C120 Motor constant (R1) 90 C120 Motor constant (R1)
Motor constants
91 C121 Motor constant (R2) 91 C121 Motor constant (R2)
Motor constant (L1)/ Motor constant (L1)/
92 C122 92 C122
d-axis inductance (Ld) d-axis inductance (Ld)
Motor constant (L2)/ Motor constant (L2)/
93 C123 93 C123
q-axis inductance (Lq) q-axis inductance (Lq)
94 C124 Motor constant (X) 94 C124 Motor constant (X)
95 C111 Online auto tuning selection 95 C111 Online auto tuning selection
96 C110 Auto tuning setting/status 96 C110 Auto tuning setting/status
100 G040 V/F1 (first frequency) 100 G040 V/F1 (first frequency)
101 G041 V/F1 (first frequency voltage) 101 G041 V/F1 (first frequency voltage)
102 G042 V/F2 (second frequency) 102 G042 V/F2 (second frequency)
103 G043 V/F2 (second frequency voltage) 103 G043 V/F2 (second frequency voltage)
Adjustable 5 104 G044 V/F3 (third frequency) 104 G044 V/F3 (third frequency)
points V/F 105 G045 V/F3 (third frequency voltage) 105 G045 V/F3 (third frequency voltage)
106 G046 V/F4 (fourth frequency) 106 G046 V/F4 (fourth frequency)
107 G047 V/F4 (fourth frequency voltage) 107 G047 V/F4 (fourth frequency voltage)
108 G048 V/F5 (fifth frequency) 108 G048 V/F5 (fifth frequency)
109 G049 V/F5 (fifth frequency voltage) 109 G049 V/F5 (fifth frequency voltage)
110 F030 Third acceleration/deceleration time
111 F031 Check valve deceleration time 111 F031 Third deceleration time
112 G020 Third torque boost
113 G021 Third V/F (base frequency)
Third functions
114 H602 Third stall prevention operation level

Third stall prevention operation
115 H603
frequency
116 M445 Third output frequency detection
117 N020 PU communication station number 117 N020 PU communication station number
118 N021 PU communication speed 118 N021 PU communication speed
PU communication stop bit length/ PU communication stop bit length/

data length data length
119 119
N022 PU communication data length N022 PU communication data length
N023 PU communication stop bit length N023 PU communication stop bit length
PU connector
communication 120 N024 PU communication parity check 120 N024 PU communication parity check
121 N025 Number of PU communication retries 121 N025 Number of PU communication retries
PU communication check time PU communication check time
122 N026 122 N026
interval interval
PU communication waiting time PU communication waiting time
123 N027 123 N027
setting setting
124 N028 PU communication CR/LF selection 124 N028 PU communication CR/LF selection

E-192
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
Terminal 2 frequency setting gain Terminal 2 frequency setting gain
125 T022 125 T022
frequency frequency

126 T042
Terminal 4 frequency setting gain
126 T042
Terminal 4 frequency setting gain B
frequency frequency

N:N Network
PID control automatic switchover PID control automatic switchover
127 A612 127 A612
frequency frequency
128 A610 PID action selection 128 A610 PID action selection
129 A613 PID proportional band 129 A613 PID proportional band
PID operation 130 A614 PID integral time 130 A614 PID integral time
C

Parallel Link
131 A601 PID upper limit 131 A601 PID upper limit
132 A602 PID lower limit 132 A602 PID lower limit
133 A611 PID action set point 133 A611 PID action set point
134 A615 PID differential time 134 A615 PID differential time

135 A000
Electronic bypass sequence
135 A000
Electronic bypass sequence D
selection selection

Computer Link
136 A001 MC switchover interlock time 136 A001 MC switchover interlock time
Bypass 137 A002 Start waiting time 137 A002 Start waiting time
138 A003 Bypass selection at a fault 138 A003 Bypass selection at a fault

139 A004
Automatic switchover frequency
from inverter to bypass operation
139 A004
Automatic switchover frequency
from inverter to bypass operation E

Communication
Inverter
Backlash acceleration stopping Backlash acceleration stopping
140 F200 140 F200
frequency frequency
Backlash 141 F201 Backlash acceleration stopping time 141 F201 Backlash acceleration stopping time
measures Backlash deceleration stopping Backlash deceleration stopping
142 F202 142 F202

143 F203
frequency
Backlash deceleration stopping time 143 F203
frequency
Backlash deceleration stopping time
F

(RS/RS2 Instruction)
Communication
Non-Protocol
144 M002 Speed setting switchover 144 M002 Speed setting switchover
PU 145 E103 PU display language selection 145 E103 PU display language selection
Acceleration/deceleration time Acceleration/deceleration time
147 F022 147 F022
switching frequency switching frequency
148 H620 Stall prevention level at 0 V input 148 H620 Stall prevention level at 0 V input G
149 H621 Stall prevention level at 10 V input 149 H621 Stall prevention level at 10 V input

(FX2N-232IF)
Communication
Non-Protocol
150 M460 Output current detection level 150 M460 Output current detection level
Current
detection Output current detection signal Output current detection signal delay
151 M461 151 M461
delay time time
152 M462 Zero current detection level 152 M462 Zero current detection level
153 M463 Zero current detection time 153 M463 Zero current detection time
H
Communication
Programming

Voltage reduction selection during Voltage reduction selection during


154 H631 154 H631
stall prevention operation stall prevention operation
RT signal function validity condition RT signal function validity condition
155 T730 155 T730
selection selection


156
157
H501
M430
Stall prevention operation selection
OL signal output timer
156
157
H501
M430
Stall prevention operation selection
OL signal output timer
I
Maintenance
Remote

158 M301 AM terminal function selection 158 M301 AM terminal function selection
Automatic switchover frequency Automatic switchover frequency
159 A005 range from bypass to inverter 159 A005 range from bypass to inverter
operation operation
160 E440 User group read selection 160 E440 User group read selection Apx.A
Frequency setting/key lock Frequency setting/key lock operation
models
Discontinued

161 E200 161 E200


operation selection selection

E-193
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
Automatic restart after Automatic restart after
162 A700 instantaneous power failure 162 A700 instantaneous power failure
selection selection
Automatic 163 A704 First cushion time for restart 163 A704 First cushion time for restart
restart functions
164 A705 First cushion voltage for restart 164 A705 First cushion voltage for restart
Stall prevention operation level for Stall prevention operation level for
165 A710 165 A710
restart restart
Output current detection signal Output current detection signal
166 M433 166 M433
Current retention time retention time
detection Output current detection operation Output current detection operation
167 M464 167 M464
selection selection
Cumulative 170 M020 Watt-hour meter clear 170 M020 Watt-hour meter clear
monitor clear 171 M030 Operation hour meter clear 171 M030 Operation hour meter clear
User group registered display/batch User group registered display/batch
172 E441 172 E441
clear clear
User group
173 E442 User group registration 173 E442 User group registration
174 E443 User group clear 174 E443 User group clear
178 T700 STF terminal function selection 178 T700 STF terminal function selection
179 T701 STR terminal function selection 179 T701 STR terminal function selection
180 T702 RL terminal function selection 180 T702 RL terminal function selection
181 T703 RM terminal function selection 181 T703 RM terminal function selection
182 T704 RH terminal function selection 182 T704 RH terminal function selection
Input terminal 183 T705 RT terminal function selection 183 T705 RT terminal function selection
function
assignment 184 T706 AU terminal function selection 184 T706 AU terminal function selection
185 T707 JOG terminal function selection 185 T707 JOG terminal function selection
186 T708 CS terminal function selection 186 T708 CS terminal function selection
187 T709 MRS terminal function selection 187 T709 MRS terminal function selection
188 T710 STOP terminal function selection 188 T710 STOP terminal function selection
189 T711 RES terminal function selection 189 T711 RES terminal function selection
190 M400 RUN terminal function selection 190 M400 RUN terminal function selection
191 M401 SU terminal function selection 191 M401 SU terminal function selection
Output terminal 192 M402 IPF terminal function selection 192 M402 IPF terminal function selection
function 193 M403 OL terminal function selection 193 M403 OL terminal function selection
assignment 194 M404 FU terminal function selection 194 M404 FU terminal function selection
195 M405 ABC1 terminal function selection 195 M405 ABC1 terminal function selection
196 M406 ABC2 terminal function selection 196 M406 ABC2 terminal function selection
232 D308 Multi-speed setting (8 speed) 232 D308 Multi-speed setting (8 speed)
233 D309 Multi-speed setting (9 speed) 233 D309 Multi-speed setting (9 speed)
234 D310 Multi-speed setting (10 speed) 234 D310 Multi-speed setting (10 speed)
Multi-speed 235 D311 Multi-speed setting (11 speed) 235 D311 Multi-speed setting (11 speed)
setting 236 D312 Multi-speed setting (12 speed) 236 D312 Multi-speed setting (12 speed)
237 D313 Multi-speed setting (13 speed) 237 D313 Multi-speed setting (13 speed)
238 D314 Multi-speed setting (14 speed) 238 D314 Multi-speed setting (14 speed)
239 D315 Multi-speed setting (15 speed) 239 D315 Multi-speed setting (15 speed)
240 E601 Soft-PWM operation selection 240 E601 Soft-PWM operation selection
241 M043 Analog input display unit switchover 241 M043 Analog input display unit switchover
Terminal 1 added compensation Terminal 1 added compensation
242 T021 242 T021
amount (terminal 2) amount (terminal 2)

E-194
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
Terminal 1 added compensation Terminal 1 added compensation
243 T041 243 T041
amount (terminal 4) amount (terminal 4)
244 H100 Cooling fan operation selection 244 H100 Cooling fan operation selection B

N:N Network
245 G203 Rated slip 245 G203 Rated slip
Slip 246 G204 Slip compensation time constant 246 G204 Slip compensation time constant
compensation Constant-power range slip Constant-power range slip
247 G205 247 G205
compensation selection compensation selection
248 A006 Self power management selection 248 A006 Self power management selection
C
249 H101 Earth (ground) fault detection at start 249 H101 Earth (ground) fault detection at start

Parallel Link
250 G106 Stop selection 250 G106 Stop selection
251 H200 Output phase loss protection selection 251 H200 Output phase loss protection selection
Frequency 252 T050 Override bias 252 T050 Override bias
compensation
function 253 T051 Override gain 253 T051 Override gain
D
254 A007 Main circuit power OFF waiting time 254 A007 Main circuit power OFF waiting time

Computer Link
255 E700 Life alarm status display 255 E700 Life alarm status display
256 E701 Inrush current limit circuit life display 256 E701 Inrush current limit circuit life display
Life check 257 E702 Control circuit capacitor life display 257 E702 Control circuit capacitor life display
258
259
E703
E704
Main circuit capacitor life display
Main circuit capacitor life measuring
258
259
E703
E704
Main circuit capacitor life display
Main circuit capacitor life measuring
E

Communication
Inverter
260 E602 PWM frequency automatic switchover 260 E602 PWM frequency automatic switchover
261 A730 Power failure stop selection 261 A730 Power failure stop selection
Subtracted frequency at Subtracted frequency at
262 A731 262 A731
deceleration start deceleration start
Power failure 263 A732 Subtraction starting frequency 263 A732 Subtraction starting frequency F
stop 264 A733 Power-failure deceleration time 1 264 A733 Power-failure deceleration time 1

(RS/RS2 Instruction)
Communication
Non-Protocol
265 A734 Power-failure deceleration time 2 265 A734 Power-failure deceleration time 2
Power failure deceleration time Power failure deceleration time
266 A735 266 A735
switchover frequency switchover frequency
267 T001 Terminal 4 input selection 267 T001 Terminal 4 input selection
268 M022 Monitor decimal digits selection 268 M022 Monitor decimal digits selection
G

(FX2N-232IF)
Communication
Non-Protocol
Stop-on contact/load torque high-
270 A200
speed frequency control selection
271 A201 High-speed setting maximum current
Load torque
high speed 272 A202 Middle-speed setting minimum current

frequency
control
273 A203 Current averaging range H
274 A204 Current averaging filter time constant
Communication
Programming

Stop-on contact excitation current


275 A205
Stop-on contact low-speed multiplying factor

control PWM carrier frequency at stop-on
276 A206
contact
I
Maintenance
Remote

Apx.A
models
Discontinued

E-195
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
278 A100 Brake opening frequency
279 A101 Brake opening current
Brake opening current detection
280 A102
time
281 A103 Brake operation time at start
Brake sequence 282 A104 Brake operation frequency

function 283 A105 Brake operation time at stop
Deceleration detection function
284 A106
selection
A107 Overspeed detection frequency
285 Speed deviation excess detection
H416
frequency
286 G400 Droop gain
Droop control 287 G401 Droop filter time constant
288 G402 Droop function activation selection
289 M431 Inverter output terminal filter 289 M431 Inverter output terminal filter
290 M044 Monitor negative output selection 290 M044 Monitor negative output selection
291 D100 Pulse train I/O selection 291 D100 Pulse train I/O selection
A110
292 Automatic acceleration/deceleration
F500
Acceleration/deceleration separate
293 F513
selection
294 A785 UV avoidance voltage gain 294 A785 UV avoidance voltage gain
Frequency change increment Frequency change increment
295 E201 295 E201
amount setting amount setting
Password 296 E410 Password lock level 296 E410 Password lock level
function 297 E411 Password lock/unlock 297 E411 Password lock/unlock
298 A711 Frequency search gain 298 A711 Frequency search gain
Rotation direction detection Rotation direction detection
299 A701 299 A701
selection at restarting selection at restarting
313 M410 DO0 output selection
CC-Link IE 314 M411 DO1 output selection
315 M412 DO2 output selection
RS-485 communication station RS-485 communication station
331 N030 331 N030
number number
332 N031 RS-485 communication speed 332 N031 RS-485 communication speed
RS-485 communication stop bit RS-485 communication stop bit

length/data length length/data length
333 333
N032 PU communication data length N032 PU communication data length
N033 PU communication stop bit length N033 PU communication stop bit length
RS-485 communication parity RS-485 communication parity check
334 N034 334 N034
RS-485 check selection selection
communication 335 N035 RS-485 communication retry count 335 N035 RS-485 communication retry count
RS-485 communication check time RS-485 communication check time
336 N036 336 N036
interval interval
RS-485 communication waiting time RS-485 communication waiting time
337 N037 337 N037
setting setting
Communication operation Communication operation command
338 D010 338 D010
command source source
Communication speed command Communication speed command
339 D011 339 D011
source source

E-196
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
Communication startup mode Communication startup mode
340 D001 340 D001
selection selection

341 N038
RS-485 communication CR/LF
341 N038
RS-485 communication CR/LF B
RS-485 selection selection

N:N Network
communication
Communication EEPROM write Communication EEPROM write
342 N001 342 N001
selection selection
343 N080 Communication error count 343 N080 Communication error count
349 N010 Communication reset selection
350 A510 Stop position command selection
C

Parallel Link
351 A526 Orientation speed
352 A527 Creep speed
353 A528 Creep switchover position
354 A529 Position loop switchover position
355 A530 DC injection brake start position D

Computer Link
356 A531 Internal stop position command
357 A532 Orientation in-position zone
Orientation
358 A533 Servo torque selection
control
359 C141 Encoder rotation direction
360 A511 16-bit data selection E
361 A512 Position shift

Communication
Inverter
362 A520 Orientation position loop gain
363 A521 Completion signal output delay time
364 A522 Encoder stop check time
365 A523 Orientation limit
366 A524 Recheck time
F

(RS/RS2 Instruction)
Communication
Non-Protocol
367 G240 Speed feedback range
368 G241 Feedback gain
Encoder 369 C140 Number of encoder pulses
feedback 374 H800 Overspeed detection level 374 H800 Overspeed detection level

376 C148
Encoder signal loss detection G
enable/disable selection

(FX2N-232IF)
Communication
Non-Protocol
380 F300 Acceleration S-pattern 1
S-pattern 381 F301 Deceleration S-pattern 1
acceleration/
deceleration C 382 F302 Acceleration S-pattern 2

384 D101 Input pulse division scaling factor


383
384
F303
D101
Deceleration S-pattern 2
Input pulse division scaling factor
H
Communication
Programming

Pulse train input 385 D110 Frequency for zero input pulse 385 D110 Frequency for zero input pulse
386 D111 Frequency for maximum input pulse 386 D111 Frequency for maximum input pulse
390 N054 % setting reference frequency
393 A525 Orientation selection
394 A540 Number of machine side gear teeth I
Maintenance
Remote

395 A541 Number of motor side gear teeth


Orientation
396 A542 Orientation speed gain (P term)
control
397 A543 Orientation speed integral time
398 A544 Orientation speed gain (D term)
399 A545 Orientation deceleration ratio Apx.A
models
Discontinued

E-197
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
414 A800 PLC function operation selection 414 A800 PLC function operation selection
415 A801 Inverter operation lock mode setting 415 A801 Inverter operation lock mode setting
PLC function
416 A802 Pre-scale function selection 416 A802 Pre-scale function selection
417 A803 Pre-scale setting value 417 A803 Pre-scale setting value
419 B000 Position command source selection
Command pulse scaling factor
420 B001 numerator
(electronic gear numerator)
Command pulse multiplication
421 B002 denominator
(electronic gear denominator)
422 B003 Position control gain
423 B004 Position feed forward gain
Position control
Position command acceleration/
424 B005
deceleration time constant
425 B006 Position feed forward command filter
426 B007 In-position width
427 B008 Excessive level error
428 B009 Command pulse selection
429 B010 Clear signal selection
430 B011 Pulse monitor selection
434 N110 Network number (CC-Link IE)
CC-Link IE
435 N111 Station number (CC-Link IE)
446 B012 Model position control gain
450 C200 Second applied motor 450 C200 Second applied motor
Second motor control method
451 G300
selection
453 C201 Second motor capacity 453 C201 Second motor capacity
454 C202 Number of second motor poles 454 C202 Number of second motor poles
455 C225 Second motor excitation current 455 C225 Second motor excitation current
456 C204 Rated second motor voltage 456 C204 Rated second motor voltage
457 C205 Rated second motor frequency 457 C205 Rated second motor frequency
Second motor
constants 458 C220 Second motor constant (R1) 458 C220 Second motor constant (R1)
459 C221 Second motor constant (R2) 459 C221 Second motor constant (R2)
Second motor constant (L1)/ Second motor constant (L1)/
460 C222 460 C222
d-axis inductance (Ld) d-axis inductance (Ld)
Second motor constant (L2)/ Second motor constant (L2)/
461 C223 461 C223
q-axis inductance (Lq) q-axis inductance (Lq)
462 C224 Second motor constant (X) 462 C224 Second motor constant (X)
Second motor auto tuning setting/ Second motor auto tuning setting/
463 C210 463 C210
status status
Digital position control sudden stop
464 B020
deceleration time
465 B021 First target position lower 4 digits
466 B022 First target position upper 4 digits
Simple position 467 B023 Second target position lower 4 digits

control
468 B024 Second target position upper 4 digits
469 B025 Third target position lower 4 digits
470 B026 Third target position upper 4 digits
471 B027 Fourth target position lower 4 digits

E-198
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
472 B028 Fourth target position upper 4 digits
473 B029 Fifth target position lower 4 digits
474 B030 Fifth target position upper 4 digits
B

N:N Network
475 B031 Sixth target position lower 4 digits
476 B032 Sixth target position upper 4 digits
477 B033 Seventh target position lower 4 digits
478 B034 Seventh target position upper 4 digits
479 B035 Eighth target position lower 4 digits C

Parallel Link
480 B036 Eighth target position upper 4 digits
481 B037 Ninth target position lower 4 digits
482 B038 Ninth target position upper 4 digits
Simple position
483 B039 Tenth target position lower 4 digits
control
484 B040 Tenth target position upper 4 digits D
485 B041 Eleventh target position lower 4 digits

Computer Link
486 B042 Eleventh target position upper 4 digits
487 B043 Twelfth target position lower 4 digits
488 B044 Twelfth target position upper 4 digits
489 B045 Thirteenth target position lower 4 digits
490 B046 Thirteenth target position upper 4 digits
E

Communication
Inverter
491 B047 Fourteenth target position lower 4 digits
492 B048 Fourteenth target position upper 4 digits
493 B049 Fifteenth target position lower 4 digits
494 B050 Fifteenth target position upper 4 digits
495 M500 Remote output selection 495 M500 Remote output selection F

(RS/RS2 Instruction)
Communication
Non-Protocol
Remote output 496 M501 Remote output data 1 496 M501 Remote output data 1
497 M502 Remote output data 2 497 M502 Remote output data 2
498 A804 PLC function flash memory clear 498 A804 PLC function flash memory clear
Communication error execution
500 N011
waiting time
Communication error occurrence
G
501 N012

(FX2N-232IF)
Communication
Non-Protocol
count display
Stop mode selection at Stop mode selection at
502 N013 502 N013
communication error communication error
503 E710 Maintenance timer 1 503 E710 Maintenance timer 1
Maintenance
504 E711
Maintenance timer 1 warning output
set time
504 E711
Maintenance timer 1 warning output
set time
H
Communication
Programming

505 M001 Speed setting reference 505 M001 Speed setting reference
Emergency drive dedicated retry
514 H324
waiting time
Emergency drive dedicated retry
515 H322
count I
S-pattern time at a start of
Maintenance
Remote

516 F400
acceleration
S-pattern time at a completion of
S-pattern 517 F401
acceleration
acceleration/
deceleration D S-pattern time at a start of
518 F402
deceleration Apx.A
S-pattern time at a completion of
models
Discontinued

519 F403
deceleration
522 G105 Output stop frequency 522 G105 Output stop frequency

E-199
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
523 H320 Emergency drive mode selection
524 H321 Emergency drive running speed
MODBUS-RTU communication MODBUS-RTU communication
539 N002 539 N002
check time interval check time interval
541 N100 Frequency command sign selection
547 N040 USB communication station number 547 N040 USB communication station number
USB USB communication check time USB communication check time
548 N041 548 N041
interval interval
549 N000 Protocol selection 549 N000 Protocol selection
NET mode operation command NET mode operation command
550 D012 550 D012
Communication source selection source selection
PU mode operation command PU mode operation command
551 D013 551 D013
source selection source selection
552 H429 Frequency jump range 552 H429 Frequency jump range
553 A603 PID deviation limit 553 A603 PID deviation limit
PID control
554 A604 PID signal operation selection 554 A604 PID signal operation selection
555 E720 Current average time 555 E720 Current average time
Current average 556 E721 Data output mask time 556 E721 Data output mask time
value monitor Current average value monitor Current average value monitor
557 E722 557 E722
signal output reference current signal output reference current
560 A712 Second frequency search gain 560 A712 Second frequency search gain
561 H020 PTC thermistor protection level 561 H020 PTC thermistor protection level
563 M021 Energization time carrying-over times 563 M021 Energization time carrying-over times
564 M031 Operating time carrying-over times 564 M031 Operating time carrying-over times
Second motor
569 G942 Second motor speed control gain 569 G942 Second motor speed control gain
constants
Multiple rating 570 E301 Multiple rating setting 570 E301 Multiple rating setting
571 F103 Holding time at a start 571 F103 Holding time at a start
A680 A680
573 4 mA input check selection 573 4 mA input check selection
T052 T052
574 C211 Second motor online auto tuning 574 C211 Second motor online auto tuning
575 A621 Output interruption detection time 575 A621 Output interruption detection time
PID control 576 A622 Output interruption detection level 576 A622 Output interruption detection level
577 A623 Output interruption cancel level 577 A623 Output interruption cancel level
578 A400 Auxiliary motor operation selection
579 A401 Motor connection function selection
580 A402 MC switching interlock time
581 A403 Start waiting time
Auxiliary motor connection-time
582 A404
deceleration time
Auxiliary motor disconnection-time
583 A405
Pump function acceleration time
584 A406 Auxiliary motor 1 starting frequency

585 A407 Auxiliary motor 2 starting frequency
586 A408 Auxiliary motor 3 starting frequency
Auxiliary motor 1 stopping
587 A409
frequency
Auxiliary motor 2 stopping
588 A410
frequency

E-200
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
Auxiliary motor 3 stopping
589 A411
frequency
Pump function
590 A412 Auxiliary motor start detection time
B

N:N Network
591 A413 Auxiliary motor stop detection time
592 A300 Traverse function selection 592 A300 Traverse function selection
593 A301 Maximum amplitude amount 593 A301 Maximum amplitude amount
Amplitude compensation amount Amplitude compensation amount
594 A302 594 A302
Traverse
function
during deceleration during deceleration
C
Amplitude compensation amount Amplitude compensation amount
595 A303 595 A303

Parallel Link
during acceleration during acceleration
596 A304 Amplitude acceleration time 596 A304 Amplitude acceleration time
597 A305 Amplitude deceleration time 597 A305 Amplitude deceleration time
598 H102 Undervoltage level 598 H102 Undervoltage level
599 T721 X10 terminal input selection 599 T721 X10 terminal input selection D

Computer Link
First free thermal reduction First free thermal reduction
600 H001 600 H001
frequency 1 frequency 1
601 H002 First free thermal reduction ratio 1 601 H002 First free thermal reduction ratio 1
Electronic
First free thermal reduction First free thermal reduction
thermal O/L 602 H003 602 H003
frequency 2 frequency 2
relay
603 H004 First free thermal reduction ratio 2 603 H004 First free thermal reduction ratio 2 E

Communication
Inverter
First free thermal reduction First free thermal reduction
604 H005 604 H005
frequency 3 frequency 3
Power failure stop external signal Power failure stop external signal
606 T722 606 T722
input selection input selection
607 H006 Motor permissible load level
Second motor permissible load
607 H006 Motor permissible load level
F
608 H016 608 H016 Second motor permissible load level

(RS/RS2 Instruction)
Communication
Non-Protocol
level
PID set point/deviation input PID set point/deviation input
609 A624 609 A624
PID control selection selection
610 A625 PID measured value input selection 610 A625 PID measured value input selection
611 F003 Acceleration time at a restart 611 F003 Acceleration time at a restart G
Cumulative pulse clear signal

(FX2N-232IF)
Communication
Non-Protocol
635 M610
selection
Cumulative pulse division scaling
Cumulative 636 M611
factor
pulse monitor
Control terminal optionCumulative
637 M612
pulse division scaling factor
H
638 M613 Cumulative pulse storage
Communication
Programming

639 A108 Brake opening current selection


640 A109 Brake operation frequency selection
Second brake sequence operation
641 A130
selection
642 A120 Second brake opening frequency I
Maintenance
Remote

643 A121 Second brake opening current


Brake sequence
Second brake opening current
function 644 A122
detection time
645 A123 Second brake operation time at start
646 A124 Second brake operation frequency
Apx.A
647 A125 Second brake operation time at stop
models
Discontinued

Second deceleration detection


648 A126
function selection

E-201
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
Second brake opening current
650 A128
Brake sequence selection

function Second brake operation frequency
651 A129
selection
Speed 653 G410 Speed smoothing control 653 G410 Speed smoothing control
smoothing
control 654 G411 Speed smoothing cutoff frequency 654 G411 Speed smoothing cutoff frequency

655 M530 Analog remote output selection 655 M530 Analog remote output selection
656 M531 Analog remote output 1 656 M531 Analog remote output 1
Analog remote
657 M532 Analog remote output 2 657 M532 Analog remote output 2
output function
658 M533 Analog remote output 3 658 M533 Analog remote output 3
659 M534 Analog remote output 4 659 M534 Analog remote output 4
Increased magnetic excitation Increased magnetic excitation
Increased 660 G130 660 G130
deceleration operation selection deceleration operation selection
magnetic
661 G131 Magnetic excitation increase rate 661 G131 Magnetic excitation increase rate
excitation
deceleration Increased magnetic excitation Increased magnetic excitation
662 G132 662 G132
current level current level
Control circuit temperature signal Control circuit temperature signal
663 M060 663 M060
output level output level
Regeneration avoidance frequency Regeneration avoidance frequency
665 G125 665 G125
gain gain
668 A786 Power failure stop frequency gain 668 A786 Power failure stop frequency gain
SF-PR slip amount adjustment SF-PR slip amount adjustment
673 G060 673 G060
operation selection operation selection
674 G061 SF-PR slip amount adjustment gain 674 G061 SF-PR slip amount adjustment gain
679 G420 Second droop gain
680 G421 Second droop filter time constant
Second droop Second droop function activation
681 G422
control selection
682 G423 Second droop break point gain
683 G424 Second droop break point torque
684 C000 Tuning data unit switchover 684 C000 Tuning data unit switchover
686 E712 Maintenance timer 2 686 E712 Maintenance timer 2
Maintenance timer 2 warning output Maintenance timer 2 warning output
687 E713 687 E713
set time set time
Maintenance
688 E714 Maintenance timer 3 688 E714 Maintenance timer 3
Maintenance timer 3 warning output Maintenance timer 3 warning output
689 E715 689 E715
set time set time
690 H881 Deceleration check time
Second free thermal reduction Second free thermal reduction
692 H011 692 H011
frequency 1 frequency 1
693 H012 Second free thermal reduction ratio 1 693 H012 Second free thermal reduction ratio 1
Electronic
Second free thermal reduction Second free thermal reduction
thermal O/L 694 H013 694 H013
frequency 2 frequency 2
relay
695 H014 Second free thermal reduction ratio 2 695 H014 Second free thermal reduction ratio 2
Second free thermal reduction Second free thermal reduction
696 H015 696 H015
frequency 3 frequency 3
699 T740 Input terminal filter 699 T740 Input terminal filter

E-202
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
702 C106 Maximum motor frequency 702 C106 Maximum motor frequency
706 C130 Induced voltage constant (phi f) 706 C130 Induced voltage constant (phi f)
707 C107 Motor inertia (integer) 707 C107 Motor inertia (integer)
B

N:N Network
711 C131 Motor Ld decay ratio 711 C131 Motor Ld decay ratio
712 C132 Motor Lq decay ratio 712 C132 Motor Lq decay ratio
Motor constants Starting resistance tuning Starting resistance tuning
717 C182 717 C182
compensation compensation

721 C185
Starting magnetic pole position
721 C185
Starting magnetic pole position C
detection pulse width detection pulse width

Parallel Link
724 C108 Motor inertia (exponent) 724 C108 Motor inertia (exponent)
725 C133 Motor protection current level 725 C133 Motor protection current level
726 N050 Auto Baudrate/Max Master
727 N051 Max Info Frames
BACnet MS/TP Device instance number
D
protocol 728 N052

Computer Link
(Upper 3 digits)
Device instance number
729 N053
(Lower 4 digits)
Second motor induced voltage Second motor induced voltage
738 C230 738 C230
constant (phi f) constant (phi f)
739 C231 Second motor Ld decay ratio 739 C231 Second motor Ld decay ratio E

Communication
Inverter
740 C232 Second motor Lq decay ratio 740 C232 Second motor Lq decay ratio
Second starting resistance tuning Second starting resistance tuning
741 C282 741 C282
compensation compensation
Motor constants
Second motor magnetic pole Second motor magnetic pole
742 C285 742 C285

743 C206
detection pulse width
Second motor maximum frequency 743 C206
detection pulse width
Second motor maximum frequency
F

(RS/RS2 Instruction)
Communication
Non-Protocol
744 C207 Second motor inertia (integer) 744 C207 Second motor inertia (integer)
745 C208 Second motor inertia (exponent) 745 C208 Second motor inertia (exponent)
746 C233 Second motor protection current level 746 C233 Second motor protection current level
Second motor low-speed range
747 G350
torque characteristic selection G
753 A650 Second PID action selection 753 A650 Second PID action selection

(FX2N-232IF)
Communication
Non-Protocol
Second PID control automatic Second PID control automatic
754 A652 754 A652
switchover frequency switchover frequency
755 A651 Second PID action set point 755 A651 Second PID action set point
PID control
756 A653 Second PID proportional band 756 A653 Second PID proportional band
757 A654 Second PID integral time 757 A654 Second PID integral time
H
Communication
Programming

758 A655 Second PID differential time 758 A655 Second PID differential time
759 A600 PID unit selection 759 A600 PID unit selection
760 A616 Pre-charge fault selection 760 A616 Pre-charge fault selection
761 A617 Pre-charge ending level 761 A617 Pre-charge ending level
762 A618 Pre-charge ending time 762 A618 Pre-charge ending time I
763 A619 Pre-charge upper detection level 763 A619 Pre-charge upper detection level
Maintenance
Remote

764 A620 Pre-charge time limit 764 A620 Pre-charge time limit
PID pre-charge
function 765 A656 Second pre-charge fault selection 765 A656 Second pre-charge fault selection
766 A657 Second pre-charge ending level 766 A657 Second pre-charge ending level
767 A658 Second pre-charge ending time 767 A658 Second pre-charge ending time Apx.A
Second pre-charge upper detection Second pre-charge upper detection
models
Discontinued

768 A659 768 A659


level level
769 A660 Second pre-charge time limit 769 A660 Second pre-charge time limit

E-203
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
774 M101 Operation panel monitor selection 1 774 M101 Operation panel monitor selection 1
Monitor
775 M102 Operation panel monitor selection 2 775 M102 Operation panel monitor selection 2
functions
776 M103 Operation panel monitor selection 3 776 M103 Operation panel monitor selection 3
A681 4 mA input check operation A681 4 mA input check operation
777 777
T053 frequency T053 frequency
A682 A682
778 4 mA input check filter 778 4 mA input check filter
T054 T054
Operation frequency during Operation frequency during
779 N014 779 N014
communication error communication error
Low speed range torque
788 G250
characteristic selection
Acceleration time in low-speed Acceleration time in low-speed
791 F070 791 F070
range range
Deceleration time in low-speed Deceleration time in low-speed
792 F071 792 F071
range range
Pulse increment setting for output Pulse increment setting for output
799 M520 799 M520
power power
800 G200 Control method selection 800 G200 Control method selection
802 G102 Pre-excitation selection
Constant output range torque
803 G210
characteristic selection
Torque 804 D400 Torque command source selection

command 805 D401 Torque command value (RAM)
Torque command value
806 D402
(RAM,EEPROM)
807 H410 Speed limit selection
Forward rotation speed limit/
808 H411
Speed limit speed limit
Reverse rotation speed limit/
809 H412
reverse-side speed limit
810 H700 Torque limit input method selection
811 D030 Set resolution switchover
812 H701 Torque limit level (regeneration)
813 H702 Torque limit level (3rd quadrant)
Torque limit
814 H703 Torque limit level (4th quadrant)
815 H710 Torque limit level 2
816 H720 Torque limit level during acceleration
817 H721 Torque limit level during deceleration
Easy gain tuning response level
818 C112
Easy gain tuning setting
819 C113 Easy gain tuning selection
820 G211 Speed control P gain 1 820 G211 Speed control P gain 1
821 G212 Speed control integral time 1 821 G212 Speed control integral time 1
822 T003 Speed setting filter 1 822 T003 Speed setting filter 1
823 G215 Speed detection filter 1
Adjustment
function Torque control P gain 1 Torque control P gain 1
824 G213 824 G213
(current loop proportional gain) (current loop proportional gain)
Torque control integral time 1 Torque control integral time 1
825 G214 825 G214
(current loop integral time) (current loop integral time)
826 T004 Torque setting filter 1

E-204
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
827 G216 Torque detection filter 1 827 G216 Torque detection filter 1
828 G224 Model speed control gain
830 G311 Speed control P gain 2 830 G311 Speed control P gain 2
B

N:N Network
831 G312 Speed control integral time 2 831 G312 Speed control integral time 2
Adjustment 832 T005 Speed setting filter 2 832 T005 Speed setting filter 2
function 833 G315 Speed detection filter 2
834 G313 Torque control P gain 2 834 G313 Torque control P gain 2
835 G314 Torque control integral time 2 835 G314 Torque control integral time 2 C

Parallel Link
836 T006 Torque setting filter 2
837 G316 Torque detection filter 2 837 G316 Torque detection filter 2
840 G230 Torque bias selection
841 G231 Torque bias 1
842 G232 Torque bias 2 D
843 G233 Torque bias 3

Computer Link
Torque bias 844 G234 Torque bias filter
845 G235 Torque bias operation time
846 G236 Torque bias balance compensation
847 G237 Fall-time torque bias terminal 1 bias
848 G238 Fall-time torque bias terminal 1 gain
E

Communication
Inverter
849 T007 Analog input offset adjustment 849 T007 Analog input offset adjustment
850 G103 Brake operation selection
Control terminal option-Number of
851 C240
encoder pulses

852 C241
Control terminal option-Encoder F
rotation direction

(RS/RS2 Instruction)
Communication
Non-Protocol
853 H417 Speed deviation time
854 G217 Excitation ratio
Control terminal option-Signal loss
Additional 855 C248
detection enable/disable selection
function
858 T040 Terminal 4 function assignment 858 T040 Terminal 4 function assignment G

(FX2N-232IF)
Communication
Non-Protocol
Torque current/Rated PM motor Torque current/Rated PM motor
859 C126 859 C126
current current
Second motor torque current/Rated Second motor torque current/
860 C226 860 C226
PM motor current Rated PM motor current
862 C242 Encoder option selection
Control terminal option-Encoder H
863 M600
Communication
Programming

pulse division ratio


864 M470 Torque detection 864 M470 Torque detection
865 M446 Low speed detection
Indication
866 M042 Torque monitoring reference 866 M042 Torque monitoring reference
function
867 M321 AM output filter 867 M321 AM output filter
I
Maintenance
Remote

868 T010 Terminal 1 function assignment 868 T010 Terminal 1 function assignment
869 M334 Current output filter 869 M334 Current output filter
870 M440 Speed detection hysteresis 870 M440 Speed detection hysteresis
872 H201 Input phase loss protection selection 872 H201 Input phase loss protection selection
Protective 873 H415 Speed limit Apx.A
models
Discontinued

Functions 874 H730 OLT level setting 874 H730 OLT level setting
875 H030 Fault definition

E-205
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

FREQROL F800 Series FREQROL A800 Series


Pr Pr Pr Pr
Function Name Name
No. Group No. Group
876 H022 Thermal protector input
Speed feed forward control/model
877 G220
adaptive speed control selection
Control system 878 G221 Speed feed forward filter

functions 879 G222 Speed feed forward torque limit
880 C114 Load inertia ratio
881 G223 Speed feed forward gain
Regeneration avoidance operation Regeneration avoidance operation
882 G120 882 G120
selection selection
Regeneration avoidance operation Regeneration avoidance operation
883 G121 883 G121
Regeneration level level
avoidance Regeneration avoidance at Regeneration avoidance at
884 G122 884 G122
function deceleration detection sensitivity deceleration detection sensitivity
Regeneration avoidance Regeneration avoidance
885 G123 885 G123
compensation frequency limit value compensation frequency limit value
886 G124 Regeneration avoidance voltage gain 886 G124 Regeneration avoidance voltage gain
888 E420 Free parameter 1 888 E420 Free parameter 1
Free parameters
889 E421 Free parameter 2 889 E421 Free parameter 2
Cumulative power monitor digit Cumulative power monitor digit
891 M023 891 M023
shifted times shifted times
892 M200 Load factor 892 M200 Load factor
Energy saving monitor reference Energy saving monitor reference
893 M201 893 M201
(motor capacity) (motor capacity)
Control selection during commercial Control selection during commercial
894 M202 894 M202
Energy saving power-supply operation power-supply operation
monitor 895 M203 Power saving rate reference value 895 M203 Power saving rate reference value
896 M204 Power unit cost 896 M204 Power unit cost
897 M205 Power saving monitor average time 897 M205 Power saving monitor average time
Power saving cumulative monitor Power saving cumulative monitor
898 M206 898 M206
clear clear
Operation time rate Operation time rate
899 M207 899 M207
(estimated value) (estimated value)
C0 C0
M310 FM/CA terminal calibration M310 FM/CA terminal calibration
(900) (900)
C1 C1
M320 AM terminal calibration M320 AM terminal calibration
(901) (901)
C2 Terminal 2 frequency setting bias C2 Terminal 2 frequency setting bias
T200 T200
(902) frequency (902) frequency
C3 C3
T201 Terminal 2 frequency setting bias T201 Terminal 2 frequency setting bias
(902) (902)
125 Terminal 2 frequency setting gain 125 Terminal 2 frequency setting gain
T202 T202
Calibration (903) frequency (903) frequency
parameters C4 C4
T203 Terminal 2 frequency setting gain T203 Terminal 2 frequency setting gain
(903) (903)
C5 Terminal 4 frequency setting bias C5 Terminal 4 frequency setting bias
T400 T400
(904) frequency (904) frequency
C6 C6
T401 Terminal 4 frequency setting bias T401 Terminal 4 frequency setting bias
(904) (904)
126 Terminal 4 frequency setting gain 126 Terminal 4 frequency setting gain
T402 T402
(905) frequency (905) frequency
C7 C7
T403 Terminal 4 frequency setting gain T403 Terminal 4 frequency setting gain
(905) (905)

E-206
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

A
FREQROL F800 Series FREQROL A800 Series

Common Items
Pr Pr Pr Pr
Function Name Name
No. Group No. Group
C12 C12
T100 Terminal 1 bias frequency (speed) T100 Terminal 1 bias frequency (speed)
(917) (917)
C13
T101 Terminal 1 bias (speed)
C13
T101 Terminal 1 bias (speed)
B
(917) (917)

N:N Network
C14 C14
T102 Terminal 1 gain frequency (speed) T102 Terminal 1 gain frequency (speed)
(918) (918)
C15 C15
T103 Terminal 1 gain (speed) T103 Terminal 1 gain (speed)
(918) (918)
C16
T110 Terminal 1 bias command (torque)
C16
T110 Terminal 1 bias command (torque)
C
(919) (919)

Parallel Link
C17 C17
T111 Terminal 1 bias (torque) T111 Terminal 1 bias (torque)
(919) (919)
C18 C18
T112 Terminal 1 gain command (torque) T112 Terminal 1 gain command (torque)
(920) (920)
C19
T113 Terminal 1 gain (torque)
C19
T113 Terminal 1 gain (torque)
D
(920) (920)

Computer Link
C8 C8
M330 Current output bias signal M330 Current output bias signal
(930) (930)
C9 C9
M331 Current output bias current M331 Current output bias current
Calibration (930) (930)
parameters C10
M332 Current output gain signal
C10
M332 Current output gain signal
E
(931) (931)

Communication
Inverter
C11 C11
M333 Current output gain current M333 Current output gain current
(931) (931)
C38 C38
T410 Terminal 4 bias command (torque) T410 Terminal 4 bias command (torque)
(932) (932)
C39
T411 Terminal 4 bias (torque)
C39
T411 Terminal 4 bias (torque)
F
(932) (932)

(RS/RS2 Instruction)
Communication
Non-Protocol
C40 C40
T412 Terminal 4 gain command (torque) T412 Terminal 4 gain command (torque)
(933) (933)
C41 C41
T413 Terminal 4 gain (torque) T413 Terminal 4 gain (torque)
(933) (933)
C42
A630 PID display bias coefficient
C42
A630 PID display bias coefficient
G
(934) (934)

(FX2N-232IF)
Communication
Non-Protocol
C43 C43
A631 PID display bias analog value A631 PID display bias analog value
(934) (934)
C44 C44
A632 PID display gain coefficient A632 PID display gain coefficient
(935) (935)
C45
A633 PID display gain analog value
C45
A633 PID display gain analog value
H
(935) (935)
Communication
Programming

977 E302 Input voltage mode selection 977 E302 Input voltage mode selection
989 E490 Parameter copy alarm release 989 E490 Parameter copy alarm release
990 E104 PU buzzer control 990 E104 PU buzzer control
PU

Monitor
991 E105 PU contrast adjustment
Operation panel setting dial push
991 E105 PU contrast adjustment
Operation panel setting dial push
I
992 M104 992 M104
Maintenance
Remote

functions monitor selection monitor selection


994 G403 Droop break point gain
Droop control
995 G404 Droop break point torque
997 H103 Fault initiation 997 H103 Fault initiation
998 E430 PM parameter initialization 998 E430 PM parameter initialization Apx.A
999 E431 Automatic parameter setting 999 E431 Automatic parameter setting
models
Discontinued

E-207
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Inverter Communication 12.5 FREQROL Inverter Parameter List

12.5.4 Communication parameters


The table below shows the parameters corresponding to each communication port.
- The PU port is common in the V500, F500, A500, and E500 Series.
- In the E500 Series, only the PU port is provided.
- In the V500, F500, and A500 Series, communication parameters for the FR-A5NR computer link are
provided.
- In the S500 Series containing RS-485 communication, the following parameters are applicable.
- In the D700 and E700 Series, communication parameters for the PU port are provided.
- In the E700 Series, communication parameters for the FR-E7TR computer link can be used.
- In the F800, A800, F700, and A700 Series, communication parameters for the built-in RS-485 terminal
are provided.
FREQROL D700 FREQROL F800,
FREQROL V500, FREQROL S500
FREQROL V500, and E700 Series A800, F700
F500 and A500 Series (Built-in port
F500, A500 and E500 (PU port) and A700 Series
Funct Series (FR-A5NR in accordance with
Series (PU port) (FR-E7TR computer (Built-in RS-485
ion computer link) RS-485)
link) terminal)
Pr Pr Pr Pr Pr
Name Name Name Name Name
No. No. No. No. No.
RS-485
Communication Communication n1 Communication PU communication
117 331 117 331 communication
station number station number 331 station number station number
station
RS-485
Communication Communication n2 Communication PU communication
118 332 118 332 communication
speed speed 332 speed speed
speed
RS-485
Stop bit length/ Stop bit length/ n3 Stop bit length/ PU communication
119 333 119 333 communication stop
Data length Data length 333 Data length stop bit length
bit length
RS-485
Parity check Parity check n4 Parity check PU communication communication
120 334 120 334
presence/absence presence/absence 334 presence/absence parity check parity check
selection
Number of Number of Number of times of Number of PU RS-485
121 communication 335 communication n5 communication 121 communication 335 communication
335
retries retries retries retries number of retries
RS-485
Communication Communication n6 Communication PU communication
Com- 122 336 122 336 communication
check time interval check time interval 336 check time interval check time interval
muni- check time interval
cation RS-485
n7 PU communication
type 123 Waiting time setting 337 Waiting time setting 337 Waiting time setting 123 337 communication
waiting time setting
waiting time setting
Communication Communication
Operation n8 Operation
338 338 operation command 338 operation command
command right 338 command right
source source
Communication Communication
Speed command n9 Speed command
339 339 frequency 339 speed command
write 339 right
command source source
Communication Communication
Link startup mode n10 Link startup mode
340 340 startup mode 340 startup mode
selection 340 selection
selection selection
PU communication RS-485
CR, LF presence/ CR, LF presence/ n11 Absence/presence 124 CR/LF presence/
124 341 341 communication CR/
absence selection absence selection 341 of CR and LF
absence selection LF selection
Communication Communication
E2PROM write n12 E2PROM write
342 342 342 EEPROM write 342 EEPROM write
selection selection
selection selection
549 Protocol selection 549 Protocol selection

E-208
FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
F. Non-Protocol Communication (RS/RS2 Instruction)
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains "non-protocol communication" provided for the MELSEC-F FX Series Programmable
Maintenance
Remote

Controllers and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

F-1
FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)

F-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.1 Outline of System

Common Items
1. Outline
This chapter explains Non-protocol communication. B

N:N Network
1.1 Outline of System
Non-protocol communication exchanges non-protocol data using a printer, bar code reader, etc.
In FX Series PLCs, non-protocol communication is available using the RS and RS2 instructions.
The RS2 instruction is dedicated to the FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.
C

Parallel Link
In FX3G, FX3GC PLCs, the RS2 instruction allows communication using three channels at the same time.
In FX3U, FX3UC PLCs, the RS2 instruction allows communication using two channels at the same time.

1) Up to 4096 points of data can be sent, and up to 4096 points of data can be received. In the case of FX2N
and FX2NC PLCs, make sure that the total number of sent and received data is 8000 points or less.
2) Data transfer is enabled when the connected equipment supports non-protocol serial communication.
D

Computer Link
3) The applicable total extension distance is 15m (49' 2") maximum in accordance with RS-232C
communication, and 500m (1640' 5") maximum in accordance with RS-485 communication [50m (164' 0")
when 485BD connection is used].

1. RS instruction E

Communication
Inverter
FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs
Important points and reference
System chapter/section

RS-232C: 15 m (49' 2")/RS-485: 500 m (1640' 5")


[50 m (164' 0") when 485BD is used] ....... Total extension distance
For specifications,
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Printer or bar code reader FX PLC refer to Chapter 2.

....... To check applicable PLC


models, refer to Section 1.3.

+ G

(FX2N-232IF)
Communication
Non-Protocol
Communication
equipment operating ....... For selection, refer to
in accordance with Chapter 3.
RS-232C or
RS-485

....... For wiring, refer to


Chapter 4.
H
Transfer direction Word devices ....... The amount of send data or
Communication
Programming

receive data can be 4096


Bar code reader points maximum.
or printer 4096 points data For details, refer to Chapter 2.

In PLCs except for the FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the amount of send data or receive
data can be 256 points maximum. I
Maintenance
Remote

Apx.A
models
Discontinued

F-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.1 Outline of System

2. RS2 instruction
FX3S PLC
Important points and reference
System chapter/section

RS-232C: 15 m (49' 2")/RS-485: 500 m (1640' 5")


[50 m (164' 0") when 485BD is used] ....... Total extension distance
For specifications,
Printer or bar code reader FX3S PLC refer to Chapter 2.

....... To check applicable PLC


models, refer to Section 1.3.

+
Communication
equipment operating ....... For selection, refer to
in accordance with Chapter 3.
RS-232C or
RS-485

....... For wiring, refer to


Chapter 4.

Transfer direction Word devices ....... The amount of send data or


receive data can be 4096
Bar code reader points maximum.
or printer 4096 points data For details, refer to Chapter 2.

F-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.1 Outline of System

A
FX3G and FX3GC PLCs

Common Items
Important points and reference
System chapter/section

RS-232C: 15 m (49' 2")/RS-485: 500 m (1640' 5")


[50 m (164' 0") when 485BD is used] Total extension distance
For specifications,
B

N:N Network
refer to Chapter 2.
Bar code reader Printer FX3G, FX3GC PLC

To check applicable PLC


models, refer to Section 1.3.
C

Parallel Link
For selection, refer to
RS-422 Chapter 3.
ch0 Standard
built-in port + For wiring, refer to
RS-232C/RS-422 Chapter 4.
Converter D

Computer Link
Transfer Word devices The amount of send data or
direction receive data can be 4096
Bar code reader points maximum.
Printer 4096 points data For details, refer to Chapter 2.

Communication
Inverter
Communication For selection, refer to
ch1 Chapter 3.
equipment
operating in
accordance with For wiring, refer to
RS-232C Chapter 4.
or RS-485
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Transfer direction Word devices The amount of send data or
receive data can be 4096
Bar code reader points maximum.
Printer 4096 points data For details, refer to Chapter 2.

G
For selection, refer to

(FX2N-232IF)
Communication
Non-Protocol
ch2 Communication Chapter 3.
equipment
operating in For wiring, refer to
accordance with Chapter 4.
RS-232C
or RS-485
H
Word devices
Communication
Programming

Transfer direction The amount of send data or


receive data can be 4096
Bar code reader points maximum.
Printer 4096 points data For details, refer to Chapter 2.

I
Maintenance
Remote

Apx.A
models
Discontinued

F-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.1 Outline of System

FX3U and FX3UC PLCs


Important points and reference
System chapter/section
RS-232C: 15 m (49' 2")/RS-485: 500 m (1640' 5")
[50 m (164' 0") when 485BD is used] ....... Total extension distance
For specifications,
Bar code reader Printer FX3U/FX3UC PLC refer to Chapter 2.

....... To check applicable PLC


models, refer to Section 1.3.

+
For selection, refer to
....... Chapter 3.
Communication
ch1 equipment operating
in accordance with
RS-232C or
RS-485 ....... For wiring, refer to
Chapter 4.

Transfer direction Word devices

Bar code reader ....... The amount of send data or


4096 points data receive data can be 4096
Printer points maximum.
For details, refer to Chapter 2.

+
.......For selection, refer to
Communication Chapter 3.
ch2 equipment operating
in accordance with
RS-232C or
RS-485 For wiring, refer to
.......Chapter 4.

Transfer direction Word devices

Bar code reader ....... The amount of send data or


receive data can be 4096
Printer 4096 points data points maximum.
For details, refer to Chapter 2.

F-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.2 Procedures Before Operation

A
1.2 Procedures Before Operation

Common Items
The flow chart below shows the Non-Protocol Communication setting procedures up until data link:

Non-Protocol Communication

Refer to Chapter 1.
B

N:N Network
Outline Outline of system
Applicable PLC versions
Applicable programming tools
Refer to Chapter 2.

Check communication specifications Communication specifications C


Communication applicability

Parallel Link
Refer to Chapter 3.

Determine system configuration and selection System configuration


Select communication equipment
Refer to Chapter 4.
D

Computer Link
Perform wiring Wiring procedure
Wiring example

Programming tool E

Communication
Inverter
Connect PLC*1

Refer to Chapter 5.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Perform PLC communication setting PLC serial communication setting
Setting using parameters

Refer to Chapter 6 and 8.

Create programs RS/RS2 instruction program


G

(FX2N-232IF)
Communication
Non-Protocol
Detailed explanation of related devices
Operation of control line
Refer to Chapter 10. Basic program

Use RS/RS2 instruction and other communication


Communication changeover
types together
Setting using a sequence program H
Communication
Programming

Based on SD/RD lamp lighting status and


contents of error check devices, verify that
communication is being executed normally.
If there are problems, refer to the troubleshooting
(Chapter 11). I
Maintenance
Remote

Refer to Chapter 7 and 9.

Practical program examples Example of connection to a printer

*1 For the programming tool to PLC connection procedure, refer to the "Programming Communication" section in this
Apx.A
models
Discontinued

manual or the respective programming tool manual.


For details on operating procedures, refer to the respective programming tool manual.

F-7
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.3 Communication Type Applicability in PLC

1.3 Communication Type Applicability in PLC

1.3.1 Applicable versions


The communication types are applicable in the following versions.
: Applicable (If applicable versions of main units are limited, they are described inside ( ).)
: Not applicable
PLC Applicability (applicable version) Remarks
FX3UC Series Full-duplex communication/half-duplex communication
FX3U Series Full-duplex communication/half-duplex communication
FX3GC Series Full-duplex communication/half-duplex communication
FX3G Series Full-duplex communication/half-duplex communication
FX3S Series Full-duplex communication/half-duplex communication
FX2NC Series Full-duplex communication/half-duplex communication
Full-duplex communication (Ver. 2.00 or later)/half-duplex
FX2N Series (Ver. 1.06 or later)
communication
FX1NC Series Half-duplex communication
FX1N Series Half-duplex communication
FX1S Series Half-duplex communication
FX0N Series (Ver. 1.20 or later) Half-duplex communication
FX0S Series Non-protocol communication is not provided
FX0 Series Non-protocol communication is not provided
FX2C Series Half-duplex communication
FX2(FX) Series (Ver. 3.07 or later)*1 Half-duplex communication
FX1 Series Non-protocol communication is not provided

*1. Applicable in products manufactured in January, 1994 (manufacturers serial No.: 41****) and later.

1.3.2 Version check


The PLC version can be checked by reading the last three digits of device D8001.
For a detailed description of the version check, refer to A. Common Items Section 4.2.

1.3.3 How to look at the manufacturer's serial number


The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT"
indicated on the front of the product.
For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Section 4.1.

1.3.4 Products whose production was stopped


Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A.
To see the latest available products, refer to the general catalog.

F-8
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.4 Programming Tool Applicability

A
1.4 Programming Tool Applicability

Common Items
1.4.1 For applicable versions
The programming tool is applicable for each FX Series from the version shown.
B
1. English versions

N:N Network
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer
FX-30P
SWD5C(F)-GPPW-E Ver. 8.18U or later
Ver. 1.00 or later
-
C

Parallel Link
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later - D
FX-30P Ver. 1.00 or later

Computer Link
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
FX-30P Ver. 1.30 or later
- E

Communication
Inverter
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
F
GOT1000 Series display units

(RS/RS2 Instruction)
Communication
Non-Protocol
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later G
FX-30P Ver. 1.00 or later -

(FX2N-232IF)
Communication
Non-Protocol
FX-20P-E(-SET0)
Ver. 3.00 or later
FX-20P-MFXC-E
FX-10P-E Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later) H
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
Communication
Programming

F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)


F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX1S, FX1N and FX1NC PLCs I
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
Maintenance
Remote

GX Developer SWD5C(F)-GPPW-E SW5 A or later


FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
FX-20P-MFXD-E
Ver. 4.00 or later Apx.A
models
Discontinued

FX-10P-E Ver. 4.00 or later

F-9
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.4 Programming Tool Applicability

Product name Model name Applicable version Remarks


GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW2 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.00 or later
FX-PCS-KIT/98 SW1PC-FXGP/98(-3,-5) Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 4.00 or later
FX-PCS-KIT/V-3 SW1PC-FXGP/V3 Ver. 2.00 or later -
FX-A7PHP-KIT SW1RX-GPPFX Ver. 3.00 or later
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 4.00 or later
FX-20P-MFXC
FX-10P(-SET0) Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

F-10
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (RS/RS2 Instruction) 1.4 Programming Tool Applicability

A
Product name Model name Applicable version Remarks

Common Items
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later B
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 5.00 or later

N:N Network
-
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 5.00 or later
FX-20P-MFXD
FX-10P(-SET0)
GOT-F900 Series display units
Ver. 4.00 or later
C

Parallel Link
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. D

Computer Link
1.4.2 For non-applicable versions (setting an alternative model)
Even programming tool not applicable to a PLC can create programs when an alternative model is set.
In this case, however, programming is enabled only in the ranges provided for the alternative PLC model
such as instructions and program size. E

Communication
Inverter
Model to be programmed Model to be set Priority: High Low
FX3UC Series FX3UC FX2N FX2(FX)
FX3U Series FX3U, FX3UC FX2N FX2(FX)
FX1N*1 FX2N*1
FX3GC Series FX3G, FX3GC
F
FX3G Series FX3G FX1N*1 FX2N*1

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3S Series FX3S FX3G FX1N*1
FX2NC Series FX2NC, FX2N FX2(FX)
FX2N Series FX2N FX2(FX)
FX1NC Series FX1NC, FX1N FX2N FX2(FX) G
FX1N Series FX1N FX2N FX2(FX)

(FX2N-232IF)
Communication
Non-Protocol
FX1S Series FX1S FX2(FX)
FX0N Series FX0N FX2(FX)
FX0S Series FX0S FX2(FX)
FX0 Series FX0 FX2(FX) H
FX2C Series FX2C, FX2(FX) FX2(FX)
Communication
Programming

FX2(FX) Series FX2(FX)


FX1 Series FX1

*1. "FX2N" is selected when the FX-10P(-E) is used.


I
Point
Maintenance
Remote

In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

Apx.A
models
Discontinued

F-11
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Non-Protocol Communication (RS/RS2 Instruction) 2.1 Communication Specifications (Reference)

2. Specifications
This chapter explains the communication specifications and performance of non-protocol communication.

2.1 Communication Specifications (Reference)


Non-protocol communication is executed in the communication specifications shown in the table below.
Item Specifications Remarks
RS-485 or RS-422
Transmission standard RS-232C standard
standard
500 m (1640' 5") or less
FX3UC, FX3U, FX3GC,
Maximum FX3G, FX3S, FX2NC, when using 485ADP
total FX2N, FX1NC, FX1N,
50 m (164' 0") or less 15 m (49' 2") or less
extension FX1S, FX0N PLCs
distance when using 485BD
FX2(FX), FX2C PLCs
Protocol type
Control procedure Non-protocol communication
Half-duplex, bidirectional communication/ Method varies
Communication method
full-duplex, bidirectional communication depending on FX Series.
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200 or 38400*1 bps
Start bit
These items are set using
Character Data bit 7 or 8-bit parameters or using
format Parity bit None, odd or even D8120, D8370, D8400 or
D8420.
Stop bit 1 or 2-bit
Header Provided or not provided
Terminator Provided or not provided
Control line Provided or not provided
Sum check is provided
Sum check Provided or not provided
only with RS2 instruction.

*1. FX3U, FX3UC Series PLC Ver. 2.41 or later, and FX3S, FX3G, FX3GC Series PLCs is applicable.

F-12
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Non-Protocol Communication (RS/RS2 Instruction) 2.2 Data Communication Specifications

A
2.2 Data Communication Specifications

Common Items
2.2.1 Communication type applicability in PLC

1. Full-duplex communication B
: Applicable (If applicable versions of main units are limited, they are described inside ( ).)

N:N Network
: Not applicable
Applicability of communication in accordance Applicability of communication in accordance
PLC Series
with RS-485 (applicable version) with RS-232C (applicable version)
FX3UC Series
FX3U Series C

Parallel Link
FX3GC Series
FX3G Series
FX3S Series
FX2NC Series
FX2N Series (Ver. 2.00 or later) *1 (Ver. 2.00 or later) D
FX1NC Series

Computer Link
FX1N Series
FX1S Series
FX0N Series
FX0S Series
FX0 Series E

Communication
Inverter
FX2C Series
FX2(FX) Series
*1. Only the FX2N-485-BD is applicable.

2. Half-duplex communication
: Applicable (If applicable versions of main units are limited, they are described inside ( ).) F
: Not applicable

(RS/RS2 Instruction)
Communication
Non-Protocol
Applicability of communication in accordance Applicability of communication in accordance
PLC Series
with RS-485 (applicable version) with RS-232C (applicable version)
FX3UC Series
FX3U Series
FX3GC Series




G

(FX2N-232IF)
Communication
Non-Protocol
FX3G Series
FX3S Series
FX2NC Series
FX2N Series (Ver. 1.06 or later) (Ver. 1.06 or later)
FX1NC Series H
FX1N Series
Communication
Programming

FX1S Series
FX0N Series (Ver. 1.20 or later) (Ver. 1.20 or later)
FX0S Series
FX0 Series
FX2C Series
I
Maintenance
Remote

FX2(FX) Series (Ver. 3.00 or later)*2


*2. Communication is applicable in products manufactured in November, 1994 (manufacturers serial No.: 4Y****) and later.

Apx.A
models
Discontinued

F-13
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Non-Protocol Communication (RS/RS2 Instruction) 2.3 Number of Transfer Data

2.3 Number of Transfer Data


FX Series Number of send/receive data Remarks
FX3UC Series 0 to 4096 points
FX3U Series 0 to 4096 points
FX3GC Series 0 to 4096 points
FX3G Series 0 to 4096 points
FX3S Series 0 to 4096 points
FX2NC Series 0 to 4096 points The total number of sent and received data should be 8000
FX2N Series 0 to 4096 points points or less.
FX1NC Series 0 to 256 points
FX1N Series 0 to 256 points
FX1S Series 0 to 256 points
FX0N Series 0 to 256 points
FX0S Series
FX0 Series
FX2C Series 0 to 256 points
FX2(FX) Series 0 to 256 points

F-14
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.1 System Configuration

Common Items
3. System Configuration and Selection
This chapter explains the system configuration and communication equipment selection operating in B
accordance with RS-485 or RS-232 required by FX PLCs.

N:N Network
3.1 System Configuration
This section outlines the system configuration required to use non-protocol communication.
Connect (optional) equipment operating in accordance with RS-485 or RS-232C to the FX PLC main unit.
C

Parallel Link
1 , 2 , 3 , 4 and 5 indicate the communication equipment combination patterns.

Communication equipment operating Total extension


in accordance with RS-485 or FX PLC Important point in selection distance
RS-232C

1
D

Computer Link
Connect the RS-232C/RS-422
+ converter to the standard port (RS-422) RS-232: 15 m
built in the PLC. (49' 2")
RS-232C/RS-422
Converter

2 RS-485: 50 m
E
This is the communication board built

Communication
Inverter
(164' 0")
+ into the PLC, reducing the installation
RS-232C: 15 m
area.
(49' 2")

Communication
board
F
3

(RS/RS2 Instruction)
Communication
Non-Protocol
Attach the special adapter connection RS-485: 500 m
board to the main unit, and then (1640' 5")
+ + attach the communication adapter to RS-232C: 15 m
the left side of the main unit. (49' 2")

Communication Special adapter


adapter connection board
G

(FX2N-232IF)
Communication
Non-Protocol
4 Attach the connector conversion RS-485: 500 m
adapter to the main unit, and then (1640' 5")
+ + attach the communication adapter to RS-232C: 15 m
the left side of the main unit. (49' 2")
H
Communication
Programming

Communication Connector
adapter conversion adapter

5
RS-485: 500 m
+ Attach the communication adapter to (1640' 5")
the left side of the main unit. RS-232C: 15 m
(49' 2")
I
Maintenance
Remote

Communication
adapter

Apx.A
For communication equipment combinations for each FX Series, refer to the next page.
models
Discontinued

F-15
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

3.2 Applicable FX PLC and Communication Equipment


Select a communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the external dimensions are different between the units shown in "FX2NC-485ADP/
FX0N-485ADP". Select either one.
- In the table below, only the outside dimensions and D-SUB connector shape are different between units
shown in "FX2NC-232ADP/FX0N-232ADP". Select either one.
- In the table below, only the cable is different between the units shown in "FX3G-485-BD/FX3G-485-BD-
RJ". Select either one.
- Non-protocol communication is not provided for the FX1, FX0, FX0S PLCs.

3.2.1 For communication in accordance with RS-232C

Total extension
FX Series Communication equipment (option) Check
distance

15 m
(49' 2")

FX0N FX2NC-232ADP FX0N-232ADP


(9-pin D-Sub, male) (25-pin D-Sub, female)

15 m
(49' 2")
FX1N-232-BD
(9-pin D-Sub, male)

FX1S + + 15 m
(49' 2")

FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP


(9-pin D-Sub, male) (25-pin D-Sub, female)

15 m
(49' 2")
FX1N-232-BD
(9-pin D-Sub, male)

FX1N + + 15 m
(49' 2")

FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP


(9-pin D-Sub, male) (25-pin D-Sub, female)

F-16
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance

15 m
(49' 2") B

N:N Network
FX2N-232-BD
(9-pin D-Sub, male)

FX2N
+ + 15 m
(49' 2")
C

Parallel Link
FX2N-CNV-BD FX2NC-232ADP FX2N-CNV-BD FX0N-232ADP
(9-pin D-Sub, male) (25-pin D-Sub, female)

D
15 m

Computer Link
(49' 2")

FX3G-232-BD
(9-pin D-SUB, male)

E
FX3S
+

Communication
Inverter
15 m
(49' 2")

FX3S-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-SUB, male)
When using channel 0 (ch 0) F

(RS/RS2 Instruction)
Communication
Non-Protocol
15 m
FX3G
(49' 2")
Standard built-in
port
FX-232AW
FX-232AWC
G

(FX2N-232IF)
Communication
Non-Protocol
RS-422 FX-232AWC-H
(8-pin MINI-DIN)
When using channel 1 (ch 1)

H
15 m
Communication
Programming

(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)

FX3G I
(14-point, 24-point
Maintenance
Remote

type)
15 m
(49' 2")

FX3G-CNV-ADP FX3U-232ADP(-MB)
(9-Pin D-Sub, male)
Apx.A
models
Discontinued

F-17
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)
The communication equipment works as ch1 when connected to
the option connector 1.

ch1

15 m
(49' 2")

FX3G-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)

ch2
FX3G
(40-point, 60-point
type)
15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)
The communication equipment works as ch2 when connected to
the option connector 2.

ch1 ch2

15 m
(49' 2")
FX3G-CNV-ADP FX3U-ADP(-MB) FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.

F-18
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)

ch1

B
15 m
RD

N:N Network
(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)

ch1 C

Parallel Link
+ 15 m
(49' 2")

FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)
D

Computer Link
When using channel 2 (ch 2)

ch1 ch2

FX3U
RD

SD

+ E
15 m

Communication
Inverter
(49' 2")
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV)

When a FX3U-8AV-BD is used, it occupies one communication port


channel. F

(RS/RS2 Instruction)
Communication
Non-Protocol
ch1 ch2

+ + 15 m
(49' 2")
G

(FX2N-232IF)
Communication
Non-Protocol
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

H
Communication
Programming

15 m
(49' 2")

FX2NC-232ADP FX0N-232ADP
FX1NC (9-pin D-Sub, male) (25-pin D-Sub, female)
I
Maintenance
Remote

15 m
(49' 2")

FX2NC
FX2NC-232ADP FX0N-232ADP Apx.A
(9-pin D-Sub, male) (25-pin D-Sub, female)
models
Discontinued

F-19
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 0 (ch 0)

15 m
FX3GC
(49' 2")
Standard built-in FX-232AW
port FX-232AWC
RS-422 FX-232AWC-H
(8-pin MINI-DIN)
When using channel 1 (ch 1)
ch1

15 m
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)

ch1 ch2
FX3GC

+ 15 m
(49' 2")

FX3U-ADP(-MB) FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232 and 485).

When using channel 1 (ch 1)


ch1

15 m
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)


ch1 ch2

FX3UC
(D, DS, DSS)
+ 15 m
(49' 2")
FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

F-20
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

RD

15 m
B

N:N Network
(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)

ch1
C

Parallel Link
+ 15 m
(49' 2")

FX3U-CNV-BD FX3U-232ADP(-MB)

When using channel 2 (ch 2)


(9-pin D-Sub, male)
D

Computer Link
ch1 ch2

+
RD

FX3UC-32MT-LT SD

(-2) 15 m
(49' 2") E

Communication
Inverter
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV)
When a FX3U-8AV-BD is used, it occupies one communication port
channel.
ch1 ch2
F

(RS/RS2 Instruction)
Communication
Non-Protocol
+ + 15 m
(49' 2")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB),
FX3U-CF-ADP
(9-pin D-Sub, male)
G
When a FX3U-CF-ADP is used, it occupies one communication port

(FX2N-232IF)
Communication
Non-Protocol
channel.

15 m H
(49' 2")
Communication
Programming

FX-232ADP
FX2(FX) (25-pin D-Sub, female)

I
Maintenance
Remote

15 m
(49' 2")

FX-232ADP
FX2C (25-pin D-Sub, female) Apx.A
models
Discontinued

F-21
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

3.2.2 For communication in accordance with RS-485

Total extension
FX Series Communication equipment (option) Check
distance

500 m
(1640' 5")

FX0N FX2NC-485ADP FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0")
FX1N-485-BD
(European terminal block)

FX1S + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0")
FX1N-485-BD
(European terminal block)

FX1N + + 500 m
(1640' 5")

FX1N-CNV-BD FX2NC-485ADP FX1N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

50 m
(164' 0")

FX2N-485-BD

FX2N + + 500 m
(1640' 5")

FX2N-CNV-BD FX2NC-485ADP FX2N-CNV-BD FX0N-485ADP


(European terminal block) (Terminal block)

F-22
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance

50 m
(164' 0")
B

N:N Network
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

C
FX3S
+ 500 m

Parallel Link
(1640' 5")

FX3S-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)

Computer Link
50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)

E
FX3G

Communication
Inverter
(14-point, 24-point
type) 500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block) F

(RS/RS2 Instruction)
Communication
Non-Protocol
When using channel 1 (ch 1)

ch1 ch1

50 m G
(164' 0")

(FX2N-232IF)
Communication
Non-Protocol
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch1 when connected to
the option connector 1.
FX3G
(40-point, 60-point ch1 H
Communication
Programming

type)

500 m
(1640' 5")

FX3G-CNV-ADP FX3U-485ADP(-MB)
(European terminal block)
I
Maintenance
Remote

Apx.A
models
Discontinued

F-23
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)
ch2 ch2

50 m
(164' 0")
FX3G-485-BD FX3G-485-BD-RJ
(European terminal block) (RJ45 connector)
The communication equipment works as ch2 when connected to
the option connector 2.

ch1 ch2
FX3G
(40-point, 60-point
type)
500 m
(1640' 5")
FX3G-CNV-ADP FX3U-ADP(-MB) FX3U-485ADP(-MB)
(Where represents (European terminal block)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
When using channel 1 (ch 1)

ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)

ch1
FX3U

+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

F-24
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch1 ch2

B
+
RD

N:N Network
SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication C
port channel.

Parallel Link
ch1 ch2
FX3U

+ + 500 m D

Computer Link
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
E

Communication
Inverter
500 m
(1640' 5")

FX1NC FX2NC-485ADP
(European terminal block)
FX0N-485ADP
(Terminal block) F

(RS/RS2 Instruction)
Communication
Non-Protocol
500 m
(1640' 5")
G
FX2NC-485ADP FX0N-485ADP

(FX2N-232IF)
Communication
Non-Protocol
FX2NC (European terminal block) (Terminal block)

When using channel 1 (ch 1)


ch1

500 m
H
Communication
Programming

(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


I
ch1 ch2
Maintenance
Remote

FX3GC

+ 500 m
(1640' 5")

FX3U-ADP(-MB) FX3U-485ADP(-MB) Apx.A


(Where represents (European terminal block)
models
Discontinued

232 and 485).

F-25
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (RS/RS2 Instruction) 3.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

500 m
(1640' 5")

FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


ch1 ch2

FX3UC
(D, DS, DSS)
+ 500 m
(1640' 5")
FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.
When using channel 1 (ch 1)
ch1

RD A

50 m
RD

RD B

SD A

(164' 0")
SD SD B

SG

FX3U-485-BD
(European terminal block)

ch1

+ 500 m
(1640' 5")

FX3U-CNV-BD FX3U-485ADP(-MB)
(European terminal block)

When using channel 2 (ch 2)


ch1 ch2

FX3UC-32MT-LT
+
RD

(-2)
SD

500 m
(1640' 5")
FX3U--BD FX3U-485ADP(-MB)
(Where represents (European terminal block)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication
port channel.
ch1 ch2

+ + 500 m
(1640' 5")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-485ADP(-MB)
FX3U-485ADP(-MB), (European terminal block)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication
port channel.

F-26
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.1 Wiring Procedure

Common Items
4. Wiring
This chapter explains the wiring. B

N:N Network
WIRING PRECAUTIONS

Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
C

Parallel Link
operation after installation or wiring work.
Failure to do so may cause electric shock.

WIRING PRECAUTIONS
D

Computer Link
Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents
due to abnormal data written to the PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the PLC. However, do not use common E
grounding with heavy electrical systems.

Communication
Inverter
Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure F
that the screwdriver does not touch the partition part of the terminal block.

(RS/RS2 Instruction)
Communication
Non-Protocol
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires. G
- Do not solder-plate the electric wire ends.

(FX2N-232IF)
Communication
Non-Protocol
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.

4.1 Wiring Procedure H


Communication
Programming

1 Preparing for wiring


Prepare cables and terminal resistors required for wiring.
For details, refer to Section 4.2.

2 Turning OFF the PLC power I


Maintenance
Remote

Before starting any wiring work, make sure that the PLC power is OFF.
3 Connecting the power supply (FX0N-485ADP only)
Connect the power supply to the 24V DC power terminal.
4 Wiring communication equipment Apx.A
models
Discontinued

Connect communication equipment operating in accordance with RS-485 or RS-232C.


For details, refer to Section 4.3.

F-27
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.2 Selecting Cables and Terminal Resistors

4.2 Selecting Cables and Terminal Resistors


Select cables using the procedure described below.

4.2.1 When using ch0 in FX3G, FX3GC PLC

When using ch0 (standard port (RS-422)) in the FX3G, FX3GC PLC, use the following cables.
RS-232C
Connector Cable
external Cable combination
shape length
device
Standard built-in
port
(RS-422)

Prepared by user 5
FX-422CAB0 4 16.5m
9-pin D-Sub (15m (49'2") maximum) 8
(1.5m(4'11)) 2 ( 541"),
25-pin D-Sub Screw for securing connector FX-232AW 7
FX-232AWC 1 maximum
[M2.6 (metric screw thread)]
FX-232AWC-H 3 6
For the connection diagram of the cable prepared by the user, 8-pin D-Sub,
female
refer to Section 4.3.

4.2.2 Twisted pair cable


Use twisted pair cables for connecting communication equipment operating in accordance with RS-485.
The table below shows recommended model names and manufacturers of cables used for wiring.

1. Recommended cables

Manufacturer Model name Remarks


SPEV(SB)-0.2-2P Two-pair cable of 0.2 mm2
Mitsubishi Cable Industries, Ltd. SPEV(SB)-MPC-0.2 3P Three-pair cable of 0.2 mm2
SPEV(SB)-0.5-2P Two-pair cable of 0.5 mm2
KMPEV-SB CWS-178 0.2SQ 2P Two-pair cable of 0.2 mm2
Showa Holdings Co., Ltd.
KMPEV-SB CWS-178 0.5SQ 2P Two-pair cable of 0.5 mm2
DPEV SB 0.3 3P Three-pair cable of 0.3 mm2
Sumitomo Electric Industries, Ltd.
DPEV SB 0.5 3P Three-pair cable of 0.5 mm2
D-KPEV-SB 0.2 3P Three-pair cable of 0.2 mm2
The Furukawa Electric Co., Ltd.
D-KPEV-SB 0.5 3P Three-pair cable of 0.5 mm2
IPEV-SB 2P 0.3 mm2 Two-pair cable of 0.3 mm2
Fujikura Ltd.
IPEV-SB 2P 0.5 mm2 Two-pair cable of 0.5 mm2

2. Cable structural drawing (reference)


Pair
Shield

Two-pair cable structural


drawing example Three-pair cable structural
drawing example

F-28
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.2 Selecting Cables and Terminal Resistors

A
4.2.3 10BASE-T cable

Common Items
10BASE-T cables used in LAN wiring for a personal computer can be connected to FX3G-485-BD-RJ.

1. Selection procedure when purchasing


1) Cable type : 10BASE-T cable (Category 3 or higher) B
2) Connection specifications : Straight type

N:N Network
3) Connector : RJ45 connector (Connector with metal frame is used)

2. Cautions on using commercial cables


Pay attention to the following point when purchasing commercial cables.
Use shielded cables. Make sure to connect the shield to the metal frame of the connector, and perform C
class D grounding.

Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-29
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.2 Selecting Cables and Terminal Resistors

4.2.4 Connecting cables

1. European type terminal block


The FX3G-485-BD-RJ terminal block is used for grounding.
The other options use shielded twisted pair cables for connecting communication equipment operating in
accordance with RS-485.
The table below shows applicable cables and tightening torques.
Cable size when Cable size when Bar terminal with Tool size
Tightening
one cable is two cables are Insulating sleeve
torque A B
connected connected (cable size)
FX3U-485-BD
FX3G-485-BD AWG22 to Applicable 0.22 to 0.25
AWG22 0.4 (0.01") 2.5 (0.09")
FX3U-485ADP AWG20 (AWG22 to AWG20) Nm
(-MB)
FX3G-485-BD- 0.5 to 0.6
AWG20 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
RJ Nm
FX2N-485-BD 0.5 to 0.6
AWG26 to AWG16 Not applicable 0.6 (0.03") 3.5 (0.14")
FX1N-485-BD Nm
AWG26 to AWG26 to 0.4 to 0.5
FX2NC-485ADP Not applicable 0.6 (0.03") 3.5 (0.14")
AWG16 AWG20 Nm

Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
With regard to the cable end treatment, use a stranded cable or solid cable as it is, or use a bar terminal with
an insulating sleeve.
FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD and FX2NC-485ADP cannot use a bar terminal with insulating
sleeve.

When using a stranded cable or solid cable as it is


- Twist the end of a stranded cable so that wires do not get barbed.
- Do not plate the end of the cable.
FX3G-485-BD, FX3U-485-BD, FX3G-485-BD-RJ,
FX3U-485ADP(-MB) FX2N-485-BD, FX1N-485-BD FX2NC-485ADP

Approx. 9 mm Approx. 6 mm Approx. 8 mm


(0.35") (0.23") (0.31")

When using a bar terminal with an insulating sleeve Insulating sleeve Contact area
Because it is difficult to insert a cable into an insulating sleeve depending (Crimp area)
on the thickness of the cable sheath, select the proper cable according to
the outline drawing. 8 mm (0.31")
<Reference> 2.6 mm
14 mm
(0.1")
Manufacturer Model name Caulking tool (0.55")

CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
(or CRIMPFOX 6T-F*2)

*1. Old model name : CRIMPFOX ZA 3


*2. Old model name : CRIMPFOX UD 6

F-30
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.2 Selecting Cables and Terminal Resistors

A
Tool

Common Items
Select a
When tightening a terminal on the European terminal block, use a small screwdriver
with a
commercial straight shape screwdriver whose tip is shown in the figure to straight tip.
the right.

Note A B
For size A and size B,
B
If the diameter of screwdriver grip is too small, tightening torque will not refer to the table above.

N:N Network
be able to be achieved. To achieve the appropriate tightening torque
shown in the previous page, use the following screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
<Reference>
FX3U-485-BD, FX3G-485-BD, FX3U-485ADP(-MB) C
Manufacturer Model name

Parallel Link
Phoenix Contact Co., Ltd. SZS 0.4 2.5

FX3G-485-BD-RJ, FX2N-485-BD, FX1N-485-BD, FX2NC-485ADP


Manufacturer Model name
Phoenix Contact Co., Ltd. SZF 1-0.6 3.5 D

Computer Link
2. Terminal block
In the FX0N-485ADP and FX-485ADP, the terminal screw size is "M3".
Make sure to use a crimp-style terminal with the following sizes.
Make sure that the tightening torque is 0.5 to 0.8 Nm. E
Do not tighten terminal screws with a torque outside the above-mentioned range.

Communication
Inverter
Failure to do so may cause equipment failures or malfunctions.
When wiring one cable to one terminal
Terminal Crimp
screw terminal
6.2mm(0.24")
3.2(0.13")
F

(RS/RS2 Instruction)
Communication
Non-Protocol
or less
3.2(0.13")
6.2mm(0.24") Terminal
or less

When wiring two cables to one terminal


G

(FX2N-232IF)
Communication
Non-Protocol
3.2(0.13")
6.2mm(0.24") Terminal Crimp
or less screw terminal
6.3mm(0.25")
or more
H
3.2(0.13")
Communication
Programming

6.2mm(0.24") Terminal
or less 6.3mm(0.25")
or more

I
Maintenance
Remote

Apx.A
models
Discontinued

F-31
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.2 Selecting Cables and Terminal Resistors

4.2.5 Connecting terminal resistors


Make sure to provide a terminal resistor at the end of each line. Brown Precision
In the case of one-pair wiring, connect a terminal resistor between the RDA-RDB
signal terminals of the communication equipment.
In the case of two-pair wiring, connect a terminal resistor between the RDA-RDB
signal terminals and SDA-SDB terminal of in the communication equipment.
1 1 1 =110
1. Terminal resistor type (101)
In the case of one-pair wiring, use two terminal resistors of 110 , 1/2 W. Orange Brown Precision
In the case of two-pair wiring, use four terminal resistors of 330 , 1/4 W.
Among the terminal resistors supplied together with the communication
equipment, select ones with the color codes shown to the right.
2. When using the FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ or
3 3 1 =330
FX3U-485ADP(-MB) (101)
The FX3U-485-BD, FX3G-485-BD, FX3G-485-BD-RJ and FX3U-485ADP(-MB)
have built-in terminal resistors.
Set the terminal resistor selector switch accordingly.
FX3U-485-BD FX3U-485ADP(-MB)

Terminal
resistor 330
Terminal
selector OPEN resistor selector
switch
switch 110

FX3G-485-BD
Remove the upper terminal block before changing over the switch in the FX3G-485-BD.

Removal: Loosen the terminal block mounting screws, and remove the terminal block.
Installation: Attach the terminal block, and tighten the terminal block mounting screws.
Tightening torque: 0.4 to 0.5 Nm
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do
so may cause equipment failures or malfunctions.
For installation and removal of the terminal block, use the
recommended tool shown below or a tool having straight tip (such as Select a
screwdriver) as shown in the right figure. screwdriver
<Reference> with a
straight tip.
Manufacturer Model name
Phoenix Contact Co., Ltd. SZS 0.4 2.5
0.4mm 2.5mm
(0.01") (0.09")

Terminal resistor
selector switch

Terminal block mounting screws


FX3G-485-BD-RJ

Terminal resistor
selector switch

F-32
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.3 Connection Diagram

A
4.3 Connection Diagram

Common Items
4.3.1 Connector pin arrangement in communication equipment operating in accordance with
RS-232C

FX0N-232ADP, FX1N-232-BD, FX2N-232-BD


B

N:N Network
FX-232AW, FX2NC-232ADP, FX3U-232-BD
FX-232ADP
FX-232AWC, FX3G-232-BD, Signal
FX-232AWC-H FX3U-232ADP(-MB) Function
name
25-pin D-Sub (female) 25-pin D-Sub (female) 9-pin D-Sub (male)
connector connector connector
8 1*1 CD (DCD) Receive carrier detection C

Parallel Link
13 3 13 3 2 RD (RXD) Receive data input
25 25
2 2 5 3 SD (TXD) Send data output
9
20 20*2 4 ER (DTR) Data terminal ready
7 7 1 6
5 SG (GND) Signal ground D
6 6*2 6 DR (DSR) Data set ready

Computer Link
14 1 14 1
1 FG Frame ground
*1. The FX2NC-232ADP does not use the CD (DCD) signal.
*2. Only the FX0N-232ADP uses the ER (DTR) and DR (DSR) signals.
E
4.3.2 Wiring for communication in accordance with RS-232C

Communication
Inverter
Representative wiring examples are shown in this subsection. When pin numbers in the external equipment
are different, wire the pins as shown below.
1. When connected equipment has the terminal specifications
PLC
F

(RS/RS2 Instruction)
Communication
Non-Protocol
9-pin D-Sub (female) connector 25-pin D-Sub (male) connector External equipment operating in accordance with RS-232C
FX3U-232-BD CS, RS DR, ER
Name FX0N-232ADP
FX2N-232-BD FX2NC-
FX3G-232-BD FX-232AW FX-232ADP Name Name
232ADP 9-pin 25-pin 9-pin 25-pin
FX1N-232-BD FX-232AWC D-Sub D-Sub D-Sub D-Sub
FX3U-232ADP(-MB) FX-232AWC-H


FG

RD(RXD) 2 3
1 FG

RD(RXD) 2
1
3
FG

RD(RXD) 2
1
3
G

(FX2N-232IF)
Communication
Non-Protocol
SD(TXD) 3 2 SD(TXD) 3 2 SD(TXD) 3 2
ER(DTR) *2
4 20 RS(RTS) 7 4 ER(DTR) 4 20
*1
SG(GND) 5 7 SG(GND) 5 7 SG(GND) 5 7
DR(DSR)
*1
6 6
*2
CS(CTS) 8 5 DR(DSR) 6 6 H
Communication
Programming

*1. When the control line is not used, wiring is not required for this signal.
Because the interlink mode [provided only in FX2N, FX2NC, FX3S, FX3G(except ch0), FX3GC(except
ch0), FX3U and FX3UC PLCs] uses the control line, wiring is required for this signal.
*2. Only the FX0N-232ADP and FX-232ADP uses the ER (DTR) and DR (DSR) signals.
I
Maintenance
Remote

Apx.A
models
Discontinued

F-33
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.3 Connection Diagram

2. When connected equipment has the modem specifications


PLC
External equipment operating in accordance with RS-232C
9-pin D-Sub (female) connector 25-pin D-Sub (male) connector
CS, RS DR, ER
FX3U-232-BD FX0N-232ADP
Name FX3G-232-BD
FX2NC- FX-232AW Name 9-pin 25-pin Name 9-pin 25-pin
FX2N-232-BD 232ADP FX-232ADP
FX1N-232-BD FX-232AWC D-Sub D-Sub D-Sub D-Sub
FX3U-232ADP(-MB) FX-232AWC-H
FG 1 FG 1 FG 1
CD(DCD) 1 *1 8 CD(DCD) 1 8 CD(DCD) 1 8
RD(RXD) 2 3 RD(RXD) 2 3 RD(RXD) 2 3

SD(TXD) 3 2 SD(TXD) 3 2 SD(TXD) 3 2

ER(DTR) 4 20 *2 RS(RTS) 7 4 ER(DTR) 4 20

SG(GND) 5 7 SG(GND) 5 7 SG(GND) 5 7

DR(DSR) 6 6 *2 CS(CTS) 8 5 DR(DSR) 6 6

*1. The FX0N-232ADP, FX2NC-232ADP, FX-232AW, FX-232AWC and FX-232AWC-H do not use the CD
(DCD) signal.
*2. Only the FX0N-232ADP and FX-232ADP uses the ER (DTR) and DR (DSR) signals.

F-34
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.3 Connection Diagram

A
4.3.3 Wiring for communication in accordance with RS-485

Common Items
One-pair wiring and two-pair wiring (for RS-422) are applicable for communication in accordance with RS-
485. Perform proper wiring according to the external equipment.

1. One-pair wiring
Communication
B
equipment operating FX3U-485-BD,FX3G-485-BD,FX2N-485-BD

N:N Network
in accordance with RS-485 FX0N-485ADP FX1N-485-BD,FX3U-485ADP(-MB) FX2NC-485ADP
SDA SDA SDA SDA
(TXD+) (TXD+) (TXD+) (TXD+)

SDB SDB SDB SDB


Terminal
resistor:
110
(TXD-) (TXD-) (TXD-) (TXD-)
Terminal
resistor:
110
C

Parallel Link
RDA RDA RDA RDA
*3 *3
(RXD+) (RXD+) (RXD+) (RXD+)

RDB RDB RDB RDB


(RXD-) (RXD-) (RXD-) (RXD-)

LINK LINK
SG
D
SG SG

Computer Link
FG*2 SG
Class-D grounding Class-D grounding
(resistance: 100 or less) *1 (resistance: 100 or less) *1

*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to the FX2N-
485-BD, FX1N-485-BD, FX3G-485-BD, FX3U-485-BD, FX2NC-485ADP or FX3U-485ADP(-MB).
E

Communication
Inverter
*2. Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring Class-
D grounding.
*3. If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
*4. Make sure to provide a terminal resistor at the end of each line.
The FX3U-485-BD and FX3U-485ADP(-MB) have a built-in terminal resistor.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Set the terminal resistor selector switch accordingly.
The FX3G-485-BD, FX0N-485ADP, FX2NC-485ADP, FX2N-485-BD and FX1N-485-BD are supplied
together with terminal resistors.
When using the FX2N-485-BD, signal loop between the PLC and the external device occurs since the FX2N-
485-BD has a full-duplex interface.
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-35
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.3 Connection Diagram

FX3G-485-BD-RJ
Communication
equipment operating
in accordance
with RS-485 Distributor (BMJ-8) Distributor (BMJ-8) FX3G-485-BD-RJ
SDA
(TXD+) 5 5 5 5 5 RDA
Terminal SDB 4 4 4 4 4 RDB
resistor (TXD-) 3 3 3 3 3 SDA
110 RDA 6 6 6 6 6 SDB
*2
(RXD+) 1 1 1 1 1 SG
RDB 2 2 2 2 2
(RXD-) Terminal
7 7 7 7 7 resistor
LINK
SG 8 8 8 8 8 *2

5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Connector metal frame


*1
Class-D Class-D Class-D Class-D
grounding grounding grounding grounding
*1 *1 *1
*1
5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Class-D
Connector metal frame

Connector metal frame


grounding (Terminal resistor
selector switch:
110)*2
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB
SG

SG
FX3G-485-BD-RJ FX3G-485-BD-RJ
(Terminal resistor selector switch: Open) (Terminal resistor selector switch: Open)

*1. Use shielded cables, and make sure to perform class D grounding on the shield.
When using the terminal block to connect ground of FX3G-485-BD-RJ, wire the ground wire only to
either one of two poles of the terminal block.
*2. Make sure to provide a terminal resistor at the end of each line. Set the FX3G-485-BD-RJ terminal
resistor selector switch accordingly.
Prepare the following devices if necessary.
Product name Model name Manufacturer
RJ45 connector TM11AP-88P HIROSE ELECTRIC CO., LTD.
BMJ-8
Distributor BMJ-8-28N (No internal connection of the No. 2 and 8 pin) HACHIKO ELECTRIC CO., LTD.
(Do not use a plug with terminal resistor)

F-36
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.3 Connection Diagram

A
2. Two-pair wiring

Common Items
Communication
equipment operating
in accordance with FX3U-485-BD,FX3G-485-BD,FX2N-485-BD
RS-485/RS-422 FX0N-485ADP FX1N-485-BD,FX3U-485ADP(-MB) FX2NC-485ADP
SDA SDA SDA SDA
(TXD+) (TXD+) (TXD+) (TXD+) B

N:N Network
SDB SDB SDB SDB
*3 *3
(TXD-) (TXD-) (TXD-) (TXD-)

RDA RDA RDA RDA


(RXD+) (RXD+) (RXD+) (RXD+)

*3
RDB RDB RDB RDB
*3
C
(RXD-) (RXD-) (RXD-) (RXD-)

Parallel Link
Terminal Terminal
resistor: resistor:
330 LINK LINK 330
SG
2 SG SG 2

FG*2 SG
Class-D grounding
(resistance: 100 or less) *1
Class-D grounding
(resistance: 100 or less) *1 D

Computer Link
*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to the FX2N-
485-BD, FX1N-485-BD, FX3G-485-BD, FX3U-485-BD, FX2NC-485ADP or FX3U-485ADP(-MB).

*2. Make sure to connect the FG terminal to the (grounding) terminal in the PLC requiring Class-
D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly. E
*3. Make sure to provide a terminal resistor at the end of each line.

Communication
Inverter
The FX3G-485-BD, FX3U-485-BD and FX3U-485ADP(-MB) have a built-in terminal resistor.
Set the terminal resistor selector switch accordingly.
The FX0N-485ADP, FX2NC-485ADP, FX2N-485-BD and FX1N-485-BD are supplied together with
terminal resistors.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-37
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.3 Connection Diagram

FX3G-485-BD-RJ
Communication equipment
operating in accordance
with RS-485/RS-422
Distributor (BMJ-8) Distributor (BMJ-8) FX3G-485-BD-RJ
SDA
(TXD+) 5 5 5 5 5 RDA
SDB 4 4 4 4 4 RDB
*2
(TXD-) 3 3 3 3 3 SDA
RDA 6 6 6 6 6 SDB
(RXD+) 1 1 1 1 1 SG
*2 RDB 2 2 2 2 2 Terminal
Terminal (RXD-) resistor
7 7 7 7 7 *2
resistor LINK Terminal
SG 8 8 8 8 8 resistor
330
2 5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Connector metal frame
*1
Class-D Class-D Class-D Class-D
grounding grounding grounding grounding
*1 *1 *1 *1

5 4 3 6 1 2 7 8 5 4 3 6 1 2 7 8 Class-D
Connector metal frame

Connector metal frame


grounding (Terminal resistor
selector switch:
330)*2
RDA
RDB

RDA
RDB
SDA
SDB

SDA
SDB
SG

SG
FX3G-485-BD-RJ FX3G-485-BD-RJ
(Terminal resistor selector switch: Open) (Terminal resistor selector switch: Open)

*1. Use shielded cables, and make sure to perform class D grounding on the shield.
When using the terminal block to connect ground of FX3G-485-BD-RJ, wire the ground wire only to
either one of two poles of the terminal block.
*2. Make sure to provide a terminal resistor at the end of each line. Set the FX3G-485-BD-RJ terminal
resistor selector switch accordingly.
Prepare the following devices if necessary.
Product name Model name Manufacturer
RJ45 connector TM11AP-88P HIROSE ELECTRIC CO., LTD.
BMJ-8
Distributor BMJ-8-28N (No internal connection of the No. 2 and 8 pin) HACHIKO ELECTRIC CO., LTD.
(Do not use a plug with terminal resistor)

F-38
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (RS/RS2 Instruction) 4.4 Grounding

A
3. Switching of 1 pair / 2 paired wiring (FX3G-485-BD-RJ)

Common Items
The FX3G-485-BD-RJ has a built-in wiring circuit switch.
Set the wiring circuit switch to 1 pair / 2 pair.

B
Wiring circuit

N:N Network
switch

Parallel Link
4.4 Grounding
Grounding should be performed as stated below.
The grounding resistance should be 100 or less. D
Independent grounding should be performed for best results.

Computer Link
When independent grounding can not be performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the Hardware Edition of each series.

PLC Other
equipment PLC Other
equipment PLC Other
equipment E

Communication
Inverter
Independent grounding Shared grounding Common grounding
Best condition Good condition Not allowed

The grounding wire size should be AWG 14 (2 mm2) or larger.


The grounding point should be close to the PLC, and all grounding wires should be as short as possible. F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-39
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Non-Protocol Communication (RS/RS2 Instruction) 5.1 Communication Setting Method Mechanism

5. Communication Setting in FX Programmable Controller


This chapter explains the communication setting types and setting methods for non-protocol communication
using RS/RS2 instruction.

5.1 Communication Setting Method Mechanism


This section explains the communication setting method types and setting procedures in FX PLCs.

1. Setting method types


1) Specifying the setting using parameters:
Set the parameters by adjusting communication settings on the personal computer screen using the
sequence programming software, and transfer them to a PLC.
(This method using parameters is not available in FX2(FX), FX2C and FX0N PLCs.)
(This method using parameters is not available for ch0 in FX3G, FX3GC PLCs.)
2) Specifying the settings by writing data to special data registers:
Prepare a sequence program which sets the communication format and time-out time setting, and then
transfer the program to the PLC.
Caution
A PLC operates in the same way without regard to a selected method shown above. If both methods are
selected, priority is given to the method using parameters.

2. Communication setting method applicability in each FX Series


Specification using Specification by writing settings
FX Series
parameters data to special data registers
FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S,
(Recommended)
FX3G (ch1, ch2), FX3GC (ch1, ch2), FX3U, FX3UC
FX2(FX), FX2C, FX0N, FX3G (ch0), FX3GC (ch0)

3. Setting data flow


PLC memory Transferred
Setting window when power
is turned ON RS instruction
Parameter area
D8120 Communication format
Parameter D8129 Time-out time setting
method Program area
Written by In FX3S, FX3G, FX3GC,
[MOV H D8120] FX3U and FX3UC
[MOV K D8129]
program Ch0 is available only
ch0 RS2 instruction
D8370 Communication format in the FX3G, FX3GC PLC.
D8379 Time-out time setting The setting method
In FX3S, FX3G, FX3GC, Written by using parameters cannot
FX3U and FX3UC program ch1 RS2 instruction
be used for ch0.
Sequence Program [MOV H D8370] D8400 Communication format
program for method Only ch1 is available in
[MOV K D8379] Written by D8409 Time-out time setting the FX3S PLC.
set values
program ch2 RS2 instruction
[MOV H D8400]
[MOV K D8409] D8420 Communication format
Written by D8429 Time-out time setting
[MOV H D8420] program
[MOV K D8429] When both methods are selected at the same time, priority is
given to the contents set in the parameter method.

4. Time at which the settings become valid


1) When specifying the settings by parameters
When the PLC power is turned ON, the contents of parameters set on the parameter setting window
using sequence programming software are automatically transferred to D8120, D8129, D8400, D8409,
D8420 and D8429 in the PLC.
As soon as the parameters are transferred to the PLC, the settings become valid.
After the program parameters are transferred to the PLC, it is necessary to turn OFF the PLC power
once, and then turn it ON again.

F-40
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Non-Protocol Communication (RS/RS2 Instruction) 5.2 Communication Setting Using Parameter Method (GX Works2)

A
2) When specifying the settings by writing data to special data registers

Common Items
After writing a sequence program, set the PLC mode from STOP to RUN to write the preset data to
D8120, D8400, D8420 or D8370. After that, set the PLC mode to STOP once, and then set it to RUN
again. Or turn OFF the PLC power once, and then turn it ON again.
As soon as the PLC mode is set to RUN from STOP or the PLC power is turned ON from OFF, the
settings become valid.
If change of the setting becomes necessary while the RS or RS2 instruction is being driven, set the RS or
B

N:N Network
RS2 instruction to OFF, set D8120, D8400, D8420 and D8370 to "0", and then set a new value to them.

5.2 Communication Setting Using Parameter Method (GX Works2)


Communication settings may be changed via the parameter method with GX Works2, GX Developer, C
FXGP/WIN for Windows and FX-30P handy programming panel. It is not possible to set ch0 in FX3G and

Parallel Link
FX3GC PLCs using parameters. This section describes how to change parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 5.3.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.2.1 Operating procedure


D

Computer Link
This subsection explains the serial communication setting method. Suppose that GX Works2 is already
started up.

1 Opening the parameter setting window E


In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].

Communication
Inverter
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-41
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Non-Protocol Communication (RS/RS2 Instruction) 5.2 Communication Setting Using Parameter Method (GX Works2)

2 Setting the serial communication (parameters)


Click the [PLC System(2)] tab in the dialog box

3 Setting the serial communication (parameters)


Select a channel and check the "Operate Communication Setting" box, then adjust the parameters
for that channel.
Execute the setting according to the connected communication equipment.
Click [End].

Caution
When setting "H/W Type" to "RS485", check the "Control Line" box.

4 Writing parameters to the PLC


Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
[Execute].

F-42
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Non-Protocol Communication (RS/RS2 Instruction) 5.3 Communication Setting Using Parameter Method (FXGP/WIN)

A
5.3 Communication Setting Using Parameter Method (FXGP/WIN)

Common Items
Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. It is not possible to set ch0 in FX3G and
FX3GC PLCs using parameters. This section describes how to change parameters with FXGP/WIN.
Ch0, ch2 cannot be set using FXGP/WIN. B
For details on GX Works2 operating procedure, refer to section 5.2.

N:N Network
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already C

Parallel Link
started up.

1 Displaying serial setting (parameter)


Select [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of the parameter settings. D
1. When there is no parameter setting

Computer Link
There is no communication setting. Click the [Yes] button.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-43
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting in FX Programmable Controller
Non-Protocol Communication (RS/RS2 Instruction) 5.3 Communication Setting Using Parameter Method (FXGP/WIN)

2. When there are already parameter settings.


The existing communication setting contents are displayed.

2 Adjusting serial setting (parameter)


Execute the settings according to the connected communication equipment.

Caution
When setting "Hardware" to "RS-485", set "Control line" to "H/W mode".

3 Writing a sequence program (parameters) to the PLC


Select [PLC] [Transfers] [Write] from the toolbar, and click [OK] button.

F-44
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.1 Checking Contents of Related Devices

Common Items
6. Creating Programs (RS Instruction)
This chapter explains how to create programs for non-protocol communication using RS instruction and how B
such programs operate.

N:N Network
6.1 Checking Contents of Related Devices
The tables below show devices used in non-protocol communication using the RS instruction.
C
1. Bit devices

Parallel Link
Device Name Description R/W
This device turns ON when a communication error occurs.
Serial communication error
M8063 When this device (serial communication error) turns ON, D8063 R
(ch1)
stores the corresponding error code.
M8120 Communication setting keep This device keeps the communication setting status (for FX0N PLC). W D

Computer Link
M8121 Sending wait flag This device remains ON while the PLC is waiting to send. R
M8122 Sending request When this device is set to ON, the PLC starts to send. R/W
This device turns ON when receiving is completed.
M8123 Receiving complete flag While this device (receiving complete flag) is ON, the PLC cannot R/W
receive any data.
M8124 Carrier detection flag This device turns ON in synchronization with the CD signal. R
E

Communication
Inverter
This device turns ON when data receiving is suspended and the
M8129*1 Time-out check flag next set of data is not given within the time set by the timeout R/W
settings device (D8129).
This device sets the send/receive data bit length to 16-bit or 8-bit.
M8161 8-bit processing mode ON: 8-bit mode W
OFF: 16-bit mode F

(RS/RS2 Instruction)
Communication
Non-Protocol
R: Read only
W: Write only
R/W: Read or Write
*1. Not provided in FX2N PLC before Ver. 2.00, and FX2(FX), FX2C, FX0N PLCs.
2. Word devices G

(FX2N-232IF)
Communication
Non-Protocol
Device Name Description R/W
Error code number of serial When the serial communication error flag (M8063) turns ON, this
D8063 R/W
communication error device stores the corresponding error code.
D8120 Communication format setting This device sets the communication format. R/W

D8122
Remaining amount of data to
This device stores the amount of remaining data to be sent. R H
be sent
Communication
Programming

Amount of data already


D8123 This device stores the amount of received data. R
received
D8124 Header This device sets the header (initial value: STX (H02)). R/W
D8125 Terminator This device sets the terminator (initial value: ETX (H03)). R/W
D8129 *2 Time-out time setting This device sets the timeout time. R/W I
Maintenance
Remote

Communication parameter
D8405*3 display
This device stores communication parameters set in the PLC. R

D8419*3 Operation mode display This device stores the communication type being used. R

R: Read only
W: Write only Apx.A
R/W: Read or Write
models
Discontinued

*2. Not provided in FX2N PLC before Ver. 2.00, and FX2(FX), FX2C, FX0N PLCs.
*3. Provided only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

F-45
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.2 How to Use RS Instruction

6.2 How to Use RS Instruction


This section explains the function, operation and programming method of RS instruction.

1. Applicable devices
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S
m
D
n

: Applicable only in FX3G, FX3GC, FX3U, FX3UC PLCs.


m, n: 0 to 4096 points in FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs
(However, "m + n" should not be more than 8000 points in FX2N and FX2NC PLCs.)
0 to 256 points in FX2(FX), FX2C, FX0N, FX1S, FX1N and FX1NC PLCs

2. Program example
S m D n
M0
FNC 80 D100 D0 D200 D1
RS
Amount of received data: 0 to 4096 points
Head device storing send data (0 to 256 points in FX2(FX), FX2C, FX0N,
Number of send data: 0 to 4096 points FX1S, FX1N and FX1NC PLCs)
(0 to 256 points in FX2(FX), FX2C, FX0N, Head device storing receive data
FX1S, FX1N and FX1NC PLCs)

6.2.1 Applicable frames


Message frames used in communication can be selected by setting the communication format.
The table below shows the message frames applicable to the RS instruction.
Header: Not provided
1 Data
Terminator: Not provided
Header: Not provided
2 Data Terminator
Terminator: Provided
Header: Provided
3 Header Data
Terminator: Not provided
Header: Provided
4 Header Data Terminator
Terminator: Provided

1. Header
When "header provided" is selected in the communication format settings, the lowest-order byte of D8124 is
used.
When data is sent, the lowest-order byte of D8124 is added at the head of the specified send data to be sent.
When data is received, receiving begins when the data on lowest-order byte of D8124 is received.

2. Terminator
When "terminator provided" is selected in the communication format settings, the lowest-order byte of D8125
is used.
When data is sent, the lowest-order byte of D8125 is added at the end of the specified send data.
When data is received, receiving is completed*1 when the data on lowest-order byte of D8125 is received.
*1. Receiving is completed also when the amount of received data specified by the RS instruction is
received or when the receiving of data is suspended and the next set of data is not executed within the
timeout time set by D8129.

F-46
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.2 How to Use RS Instruction

A
6.2.2 Function and operation

Common Items
RS instruction specifies the head device storing the sent data sent from the PLC, amount of data, head device
storing the received data and the maximum allowable amount of received data.
Create a program as shown below.
Command B

N:N Network
M0
FNC 80 D100 D0 D200 D1
RS
When the command contact (M0) is set to ON, the PLC waits to send and receive.
For handling of sent and received data, refer to Subsection 6.2.3.

Sending command
(pulse operation type)
C

Parallel Link
M1
Send data is written.

When the sending command (M1) is set to ON, write the send data to D100 and so on
(as many devices as specified number).
Give the sending command of the pulse operation type. D
After writing the send data, set the sending request device (M8122) to send the data.

Computer Link
Sending
request
SET M8122

When sending is completed, the sending request device (M8122) is automatically reset.
Do not reset it in a sequence program.
E

Communication
Inverter
For operation when data is sent, refer to Subsection 6.2.4.
Receiving complete
M8123
Receive data is moved.

When the PLC receives data from the connected equipment, the receiving complete flag F
(M8123) turns ON.

(RS/RS2 Instruction)
Communication
Non-Protocol
When M8123 turns ON, move the received data stored in D200 to another storage area.
Receiving
complete
RST M8123

After moving the received data, reset the receiving complete flag (M8123).
While M8123 is ON, the PLC cannot receive the next set of data.
G

(FX2N-232IF)
Communication
Non-Protocol
For the operation when data is received, refer to Subsection 6.2.5.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-47
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.2 How to Use RS Instruction

6.2.3 Send/receive data and amount of data


RS instruction can handle sent and received data in two modes, 16-bit mode and 8-bit mode.
Data is handled as shown below in each mode. (In the examples shown below, "header provided" and
"terminator provided" are selected in the communication setting.)

1. Handling of 16-bit data (when M8161 is set to OFF)


OFF in RUN mode 16-bit data
OFF
Highest-order 8-bit Lowest-order 8-bit
M8000
M8161 16-bit mode 16-bit data is divided into lowest-order
8-bit and highest-order 8-bit when it is
sent or received.
S m D n
X010
FNC 80 D200 K 4 D500 K 10
RS

STX D200 lowest- D200 highest- D201 lowest- D201 highest- ETX
Send data order byte order byte order byte order byte
(PLC Header
external Terminator
equipment) Head address specified by S
Number of bytes to be sent specified by "m"

STX D500 lowest- D500 highest- D501 lowest- D501 highest- D502 lowest- D502 highest- ETX
Receive data order byte order byte order byte order byte order byte order byte
(external Header
equipment Terminator
Head address specified by D
PLC)

They cannot exceed the upper limit number of devices (bytes) to be


received by "n". When the PLC receives the terminator (ETX) or "n" data,
receiving is completed.

1) Send data and amount of remaining send data


lowest-order byte

lowest-order byte
highest-order byte

highest-order byte
D200

D201
D200

D201

Send data
STX

ETX

SD (TXD)

4
Amount of remaining 3
send data 2
1
D8122 0

2) Receive data and amount of data already received


lowest-order byte

lowest-order byte

lowest-order byte
highest-order byte

highest-order byte

highest-order byte
D500

D501

D502

Receive data
D500

D501

D502
STX

ETX

RD (RXD)
6 When the receiving
5
4 complete flag M8123
Amount of data 3 is reset, the amount of
already received 2 received data is reset
1
D8123 0 also.

Caution on other instructions using M8161


M8161 is shared by RS, ASCI, HEX, CCD, and CRC (provided only in FX3U and FX3UC PLCs) instructions.
If M8161 is changed during the sending/receiving operation of the RS instruction, the data may not be
received normally.

F-48
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.2 How to Use RS Instruction

A
2. Handling of 8-bit data (when M8161 is set to ON)

Common Items
M8000 16-bit data
M8161 8-bit mode
Ignored Lowest-order 8-bit
S m D n Highest-order 8-bits are ignored,
X010
FNC 80 D200 K 4 D500 K 10
and only the lowest-order 8-bits are
regarded as valid data.
B
RS

N:N Network
STX D200 lowest- D201 lowest- D202 lowest- D203 lowest- ETX
Send data order byte order byte order byte order byte
(PLC Header Terminator
external Head address specified by S
equipment)
Number of bytes to be sent specified by "m"
C

Parallel Link
STX D500 lowest- D501 lowest- D502 lowest- D503 lowest- D504 lowest- D505 lowest- ETX
Receive data order byte order byte order byte order byte order byte order byte
(external Header Terminator
equipment Head address specified by D
PLC)
D
They cannot exceed the upper limit number of devices (bytes) to be

Computer Link
received, specified by "n". When the PLC receives the terminator (ETX) or
"n" data, receiving is completed.

1) Send data and amount of remaining data


E
lowest-order byte

lowest-order byte

lowest-order byte

lowest-order byte

Communication
Inverter
D200

D201

D202

D203

Send data
STX

ETX

SD (TXD)

Amount of remaining
4
3
F
2

(RS/RS2 Instruction)
Communication
Non-Protocol
data 1
D8122 0

2) Receive data and amount of received data

G
lowest-order byte

lowest-order byte

lowest-order byte

lowest-order byte

lowest-order byte

lowest-order byte

(FX2N-232IF)
Communication
Non-Protocol
D500

D501

D502

D503

D504

D505
STX

ETX

Receive data
RD (RXD)
6
5 When the receiving
Amount of received 3
4 complete flag M8123
is reset, the amount of
H
2
Communication
Programming

data 1 received data is reset


D8123 0 also.

Caution on other instructions using M8161


M8161 is shared by RS, ASCI, HEX, CCD, and CRC (provided only in FX3U and FX3UC PLCs) instructions. I
If M8161 is changed during the sending/receiving operation of the RS instruction, the data may not be
Maintenance
Remote

received normally.

Apx.A
models
Discontinued

F-49
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.2 How to Use RS Instruction

6.2.4 Operation when data is sent


When the sending request flag (M8122) is set to ON while RS instruction is driven, the PLC sends the data
stored in the data registers S to ( S +m-1) specified by the RS instruction.
When sending of the data is complete, the sending request flag (M8122) is automatically set to OFF.

1. Time at which sending is started


When RS instruction is executed after the sending request flag (M8122) is set to ON, the PLC starts to send.
When sending begins, the PLC sends the data stored in the data registers specified by the RS instruction in
interrupt processing regardless of the operation cycle.

2. Time at which sending is completed


When all send data is sent, sending is completed.
(If the terminator is set, the terminator is included in the send data.)

3. Cautions on sending
When sending data, observe the following cautions
1) While the sending request flag (M8122) is ON, do not change the amount of send data or contents of
send data.
2) Do not set the sending request flag (M8122) to OFF in a sequence program.
If the send data is changed while the sending request flag (M8122) is ON or if the sending request flag
(M8122) is set to OFF in a sequence program, correct data will not be sent.

6.2.5 Operation when data is received


When RS instruction is executed, the PLC waits to receive. When the PLC receives data from the connected
equipment and receiving is completed, the receiving complete flag (M8123) is set to ON.
When the PLC receives data, it stores the received data to the data registers D to ( D +n-1) specified
by the RS instruction.
While the receiving complete flag (M8123) is ON, the PLC cannot receive new data.

1. Time at which receiving is started


When the PLC receives data while it is waiting to receive, it starts receiving data.
When receiving begins, the PLC stores the received data in interrupt processing regardless of the operation
cycle.
When the header (D8124) is specified in the communication format, however, the PLC starts receiving when
it receives the code set in the header. And the PLC stores the received data except the header.

2. Time at which receiving is completed


Receiving is completed in the following three conditions. When either condition is established, receiving is
completed.
1) When the PLC receives as much data as specified by the RS instruction
2) When "terminator provided" is selected in the communication format, and the PLC receives the code set
in the terminator (D8125)
3) When data receiving is suspended and the PLC does not receive the next set of data within the time set
in the time-out time setting device (D8129)
At this time, the time-out check flag (M8129) turns ON.
(The time-out check flag is not provided in FX2N PLC before Ver. 2.00, and FX2(FX), FX2C, FX0N PLCs.)

F-50
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.2 How to Use RS Instruction

A
3. Operation of the time-out check flag (which is not provided in FX2N PLC before Ver. 2.00,

Common Items
and FX2(FX), FX2C, FX0N PLCs)
When data receiving is suspended, counting of the timeout time is started immediately. If the PLC does not
receive the next set of data within the time-out time setting set by D8129, the time-out check flag (M8129) is
set to ON. At this time, the receiving complete flag (M8123) is set to ON also.
The time-out time setting (D8129) can be set to a value from 1 to 255 (10 ms to 2550 ms). B
Receive data is suspended.

N:N Network
Receiving
Data
D8129 Set to OFF in sequence program.
Timeout determination 10 ms
M8129 ON
Receiving complete
ON
C
M8123

Parallel Link
The time-out check flag (M8129) does not turn OFF automatically.
Set it to OFF in the sequence program. (When M8123 is set to OFF, M8129 is also set to OFF.)
Using this function, the PLC can receive data from equipment where the amount of send data varies without
the terminator.
D
4. When the control line is set to interlink mode

Computer Link
When interlink mode is selected as the communication format, the following sequence is adopted from the
start of receiving to completion:
1) When the amount of data already received becomes "number of bytes to be received -30", the control line
ER (DTR) turns OFF.
When the control line ER (DTR) turns OFF, the external equipment should suspend data sending.
After the control line ER (DTR) turns OFF, the PLC can receive up to 30 characters (bytes).
E

Communication
Inverter
2) When the external equipment suspends data sending, the PLC sets the time-out check flag (M8129) and
receiving complete flag (M8123) to ON after the time-out time setting (D8129).
Move the received data in a sequence program, and then set the receiving complete flag (M8123) and
time-out check flag (M8129) to OFF.
3) When the receiving complete flag (M8123) is set to OFF, the control line ER (DTR) turns ON. F
When the control line ER (DTR) turns ON, resume sending data from the external equipment.

(RS/RS2 Instruction)
Communication
Non-Protocol
4) Repeat steps 1) to 3) until data receiving is completed.

5. Cautions on receiving
When receiving data, observe the following cautions:
1) While the receiving complete flag (M8123) is ON, the PLC cannot receive the next set of data. G
When the receiving complete flag is set to OFF, the PLC waits to receive.

(FX2N-232IF)
Communication
Non-Protocol
2) If the RS instruction is driven while the amount of received data "n" is "0", the operation of the receiving
complete flag (M8123) varies depending on the PLC as follows:
FX1S, FX1N, FX1NC PLCs
The receiving complete flag (M8123) remains OFF even after the RS instruction is driven, but the PLC
does not wait to receive. H
FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U, FX3UC PLCs
Communication
Programming

The receiving complete flag (M8123) turns ON after the RS instruction is driven.
To make the PLC wait to receive, set the amount of received data "n" to "1" or more, and set the receiving
complete flag (M8123) to OFF from ON.

I
Maintenance
Remote

Apx.A
models
Discontinued

F-51
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.3 Operation of Control Line

6.3 Operation of Control Line

6.3.1 FX2N (before Ver. 2.00), FX2(FX), FX2C, FX0N, FX1S, FX1N and FX1NC PLCs
FX2N PLCs before Ver. 2.00, and FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC PLCs execute half-duplex,
bidirectional communication.
When the sending flag is set to ON during receiving, the sending wait flag M8121 turns ON. When the
receiving complete flag turns ON from OFF, the PLC starts to send.

1. When the control line is not provided


RS
instruction OFF ON
driving

SD (TXD) Message Message


Send data 1 3

Sending ON OFF
request
M8122
Sending wait OFF ON
flag
M8121 100 s or more*1

RD (RXD) Message Message


Receive data 2 3

Receiving OFF ON ON
complete
M8123 Receiving wait status
is started. Reset it in a sequence program.
While it remains ON, the PLC cannot receive the next set of data.

*1. Set it to 2 scan times or more in FX2(FX), FX2C, FX0N, FX1S, FX1N and FX1NC PLCs.

2. When the control line is in the standard mode


Use this mode when only sending or receiving.
1) When only sending is executed
RS
instruction OFF ON
driving

SD (TXD) Message Message Message


Send data 1 1 2

Sending OFF ON
request
M8122
ER (DTR) OFF ON

DR (DSR) OFF ON

F-52
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.3 Operation of Control Line

A
2) When only receiving is executed [The DR (DSR) signal is not used.]

Common Items
RS
instruction OFF ON
driving

RD (RXD) Message Message


Receive data 1 2 B

N:N Network
ER (DTR) OFF ON

Receiving
complete OFF ON ON
M8123
Reset it in a sequence program. While it remains ON, the PLC cannot receive
C

Parallel Link
the next set of data.

3. When the control line is in the modem mode


RS
instruction OFF ON
driving D

Computer Link
SD (TXD) Message Message
Send data 1 3

Sending
request OFF ON
M8122 E
Sending wait

Communication
Inverter
flag OFF ON
M8121
ER (DTR) OFF ON

RD (RXD)
Receive data
Message
2
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Receiving
complete OFF ON
M8123
Reset it in a sequence program.
While it remains ON, the PLC cannot
100 s
or receive the next set of data. G
more*1

(FX2N-232IF)
Communication
Non-Protocol
DR (DSR) OFF ON

*1. Set it to 2 scan times or more in FX2(FX), FX2C, FX0N, FX1S, FX1N and FX1NC PLCs.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-53
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.3 Operation of Control Line

6.3.2 FX2N (Ver. 2.00 or later), FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs
FX2N PLCs Ver. 2.00 or later, and FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs execute full-duplex,
bidirectional communication. When executing half-duplex, bidirectional communication, pay attention not to
set the sending request to ON while receiving. If the sending request is set to ON, the PLC starts to send. As
a result, the external equipment may not be able to receive data, and the sent and received data may be
destroyed.
In full-duplex, bidirectional communication, the sending wait flag M8121 does not turn ON.
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, however, the sending wait flag M8121 remains ON while the
DR (DSR) is OFF, the PLC waits to send, and the control line is in the standard mode or interlink mode.

1. Without control line


RS
instruction OFF ON
driving

SD (TXD) Message Message Message


Send data 1 3 5

Sending
request OFF ON
M8122
RD (RXD) Message Message 4
Receive data 2

Receiving
complete OFF ON ON
M8123
Receiving wait status is Reset it in a sequence program.
started. While it remains ON, the PLC cannot receive the next set of data.

2. When the control line is in the standard mode


Use this mode when only sending or receiving.
The control line and transfer sequence are equivalent to those in FX2N PLCs (before Ver. 2.00). Refer to
Subsection 6.3.1.

3. When the control line is in the modem mode


RS
instruction OFF ON
driving

SD (TXD) Message Message 4


Send data 1

Sending
request OFF ON
M8122
ER (DTR) OFF ON

RD (RXD) Message 2 Message 3


Receive data

Receiving
complete OFF ON ON
M8123
DR (DSR) OFF ON
Reset it in a sequence program.
While it remains ON, the PLC cannot receive the next set of data.

F-54
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.3 Operation of Control Line

A
4. When the control line is in the interlink mode

Common Items
RS
instruction OFF ON
driving

SD (TXD)
Send data
Message
2
Message
4
Message
4 B

N:N Network
Sending
request ON OFF
M8122
DR (DSR) OFF *1 ON *1 *1
Up to 30 characters can be C
received. *2

Parallel Link
RD (RXD) Message Message 3 Message
Receive data 1 3
Time-out
time setting
D8129 10 ms
Time-out D
check flag

Computer Link
M8129

Receiving
OFF ON ON ON
complete
M8123 E

Communication
Inverter
ER (DTR) ON OFF

Reset it in a sequence program.


While it remains ON, the PLC cannot receive the next set of data.
F
*1. On the external equipment side, set the DR (DSR) signal to ON when the external equipment is ready

(RS/RS2 Instruction)
Communication
Non-Protocol
to receive.
The FX2N, FX2NC, FX3S, FX3G, FX3GC, FX3U or FX3UC PLC sends the send data when both the DR
(DSR) signal and the sending request turn ON.
*2. In the interlink mode, the PLC sets ER (DTR) to OFF when the amount of data already received
becomes "Number of bytes to be received -30", and asks the external equipment to stop sending.
After that, the PLC can only receive up to 30 characters. In this case, temporarily stop sending, and
G

(FX2N-232IF)
Communication
Non-Protocol
then send the remaining data after the ER (DTR) signal turns ON again.
When sending is stopped, the PLC finishes receiving after the time-out time setting is reached.
When sending is not stopped, the PLC finishes receiving after it has received the final send data or 30
characters. Accordingly, make sure that the amount of received data is "30 + ".

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-55
FX Series PLC User's Manual - Data Communication Edition 6 Creating Programs (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 6.4 Important Points in Creating Programs

6.4 Important Points in Creating Programs


1) The RS instruction can be used as many times as necessary in a program, but make sure that only one
RS instruction is driven at a time.
For multiple RS instructions to be driven, make sure the OFF time is longer than one scan time.
2) In FX2(FX), FX2C, FX0N, FX1S, FX1N and FX1NC PLCs, make sure to provide an interval of two scan times
or more between completion of sending and the start of receiving or between completion of receiving and
the start of sending.
In FX2N PLCs before Ver. 2.00, provide an interval of 100 s or more.
In FX2N PLCs Ver. 2.00 or later, FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, this interval is not
necessary.
3) While a RS instruction is being driven, change of D8120 is prohibited.
To change D8120, set the RS instruction to OFF, set D8120 to "0", and then set a new value to D8120.
4) In the interlink mode, set the amount of received data n to "31" or more.
If it is set to "30" or less, the control line ER (DTR) is set to OFF as soon as the PLC receives data. As a
result, the received data may be partially skipped.
5) Do not use another instruction which uses the same communication port. If such an instruction is used,
communication may not function normally.
FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs: RS2 instruction, IVDR instruction, etc.
FX2N and FX2NC PLCs: EXTR instruction
6) When RS-485 communication is executed in FX3U and FX3UC PLCs, it may take 300 s until the PLC
starts receiving after it has completed sending.
Assure 300 s or more in counterpart equipment as the period from completion of receiving to start of
sending.

6.5 Communication Error


When a communication error occurs, the error flag M8063 turns ON and D8063 stores the error code.
Error code Description
6301 Parity error, overrun error or framing error
6302 Defective communication character
6304 Defective data format
6305 Defective command
6306 Monitoring time out

Confirm the contents in "Chapter 11. Troubleshooting".

F-56
FX Series PLC User's Manual - Data Communication Edition 7 Practical Program Example (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 7.1 Example of Printing Using RS Instruction (Using RS-232C Connection)

Common Items
7. Practical Program Example (RS Instruction)
B
7.1 Example of Printing Using RS Instruction (Using RS-232C Connection)

N:N Network
In this example, a printer with an RS-232C interface is connected to a PLC, and data sent from the PLC is
printed.

1. System configuration
C

Parallel Link
Sending
+
FX2N-232-BD FX2N Series

Use a communication cable suitable to the pin arrangement of the printer connector.
D

Computer Link
(For representative wiring, refer to Chapter 4.)

2. Communication format
Align the communication format in the PLC with that in the printer used.
(The table below shows the communication format in the main unit.)
Data length 8-bit
E

Communication
Inverter
Parity Even
Stop bit 2-bit
Baud rate 2400 bps
Header Not provided
Terminator Not provided F

(RS/RS2 Instruction)
Communication
Non-Protocol
Control line (hardware) Not provided
Communication method (protocol) Non-protocol method

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-57
FX Series PLC User's Manual - Data Communication Edition 7 Practical Program Example (RS Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 7.1 Example of Printing Using RS Instruction (Using RS-232C Connection)

3. Sequence program
M8000
M8161 8-bit data is handled.

M8000
M8120 The communication setting is kept.
(This step is required only in an FX0N PLC.)
M8002
MOV H006F D8120 The b15 b0
communication
format is set. 0000 0000 0110 1111
0 0 6 F

This step is not required when the


X000 communication parameters are
RS instruction already set.
RS D10 K11 D50 K0 is driven.

X001
PLS M0

M0
MOV H0074 D10

MOV H0065 D11



MOV H006E D17
Send data is written.

MOV H0065 D18

MOV H000D D19

MOV H000A D20

Sending request
SET M8122 is given.

END

4. Operation

Turn ON the power to the PLC and printer, set the PLC to RUN mode,
Power is turned
ON. and set the printer to online mode.
At this time, the communication format is set in the PLC.
X000.ON

RS instruction is X000 is set to ON to drive the RS instruction.


driven. At this time, send data is stored in 11 devices from D10 to D20.

X001.ON
Every time X001 is set to ON, the data stored in D10 to D20 is sent to
Data is sent.
the printer.
ASCII codes are used in this example.
(The sending complete flag is automatically reset.)

F-58
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.1 Checking Contents of Related Devices

Common Items
8. Creating Programs (RS2 Instruction)
This chapter explains how to create programs for non-protocol communication using RS2 instruction and how B
such programs operate.

N:N Network
The RS2 instruction is dedicated to the FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.
RS2 instruction has the following additional functions which are not provided in the RS instruction:
1) Up to 4 characters (bytes) can be specified as the header and terminator.
2) The sum check can be added automatically.
3) The communication port (channel) can be specified.
C

Parallel Link
8.1 Checking Contents of Related Devices
The tables below show devices used in non-protocol communication using RS2 instruction.
Available channels vary depending on the main unit. D
For details, refer to Section 3.2.

Computer Link
1. Bit devices
Device
Name Description R/W
ch0 ch1 ch2
This device turns ON when a communication error occurs. E
When this device (serial communication error) turns ON,

Communication
Inverter
M8062 M8063 M8438 Serial communication error R
D8062, D8063 or D8438 stores the corresponding error
code.
M8371 M8401 M8421 Sending wait flag This device remains ON while the PLC is waiting to send. R
M8372 M8402 M8422 Sending request When this device is set to ON, the PLC starts to send. R/W
This device turns ON when receiving is completed. F
M8373 M8403 M8423 Receiving complete flag While this device (receiving complete flag) is ON, the PLC R/W

(RS/RS2 Instruction)
Communication
Non-Protocol
cannot receive any receive data.
This device turns ON in synchronization with the CD
M8404 M8424 Carrier detection flag R
(DCD) signal.
This device turns ON in synchronization with the DR (DSR)
M8425 Data set ready (DSR) flag*1
M8405
signal.
R
G
This device turns ON when data receiving is suspended

(FX2N-232IF)
Communication
Non-Protocol
M8379 M8409 M8429 Time-out check flag and the next set of receive data is not given within the time R/W
set by the time-out time setting device.

R: Read only
W: Write only
R/W: Read or Write H
Communication
Programming

*1. FX3U, FX3UC PLCs Ver. 2.30 or later, and FX3S, FX3G, FX3GC PLCs is applicable.

I
Maintenance
Remote

Apx.A
models
Discontinued

F-59
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.1 Checking Contents of Related Devices

2. Word devices
Device
Name Description R/W
ch0 ch1 ch2
Serial
When the serial communication error flag turns ON, this device
D8062 D8063 D8438 communication R/W
stores the corresponding error code.
error code
Communication
D8370 D8400 D8420 This device sets the communication format. R/W
format setting
Amount of
D8372 D8402 D8422 remaining send This device stores the amount of remaining send data. R
data
Amount of data
D8373 D8403 D8423 This device stores the amount of data already received. R
already received
Communication
D8405 D8425 parameter This devices stores communication parameters set in the PLC. R
display
Time-out time
D8379 D8409 D8429 This device sets the timeout time. R/W
setting
These devices set the headers 1 to 4.
Header
Header 1 and 1 2 3 4 Data
D8380 D8410 D8430 R/W
header 2
Initial
Header ch0 ch1 ch2
value
D8380 D8410 D8430
H02
1 (lowest-order (lowest-order (lowest-order
(STX)
byte) byte) byte)
D8380 D8410 D8430
2 (highest-order (highest-order (highest-order H00
byte) byte) byte)
D8381 D8411 D8431
Header 3 and 3 (lowest-order (lowest-order (lowest-order H00
D8381 D8411 D8431 R/W
header 4 byte) byte) byte)
D8381 D8411 D8431
4 (highest-order (highest-order (highest-order H00
byte) byte) byte)

When "H00" is set to the header 1, headers are not provided.


The area before H00 (in 1-byte units) is used to set the headers.

F-60
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.1 Checking Contents of Related Devices

A
Device

Common Items
Name Description R/W
ch0 ch1 ch2
These devices set the terminators 1 to 4.
Terminator

D8382 D8412 D8432


Terminator 1 and
terminator 2
Data 1 2 3 4
R/W B

N:N Network
Termi- Initial
ch0 ch1 ch2
nator value
D8382 D8412 D8432
H03
1 (lowest-order (lowest-order (lowest-order
(ETX)
byte) byte) byte)
D8382 D8412 D8432 C
2 (highest-order (highest-order (highest-order H00

Parallel Link
byte) byte) byte)
D8383 D8413 D8433
3 (lowest-order (lowest-order (lowest-order H00
Terminator 3 and byte) byte) byte)
D8383 D8413 D8433 R/W
terminator 4
4
D8383
(highest-order
D8413
(highest-order
D8433
(highest-order H00 D
byte) byte) byte)

Computer Link
When "H00" is set to the terminator 1, terminators are not
provided.
The area before H00 (in 1-byte units) is used to set the
terminators.
Receiving sum
E
D8384 D8414 D8434 This device stores the received sum check value. R

Communication
Inverter
(receive data)
Receiving sum
This device stores the sum check value calculated from the
D8385 D8415 D8435 (calculation R
received data.
result)
D8386 D8416 D8436 Sending sum This device stores the sum check value added to the send data. R
Operation mode F
D8389 D8419 D8439 This device stores the current communication being executed. R
display

(RS/RS2 Instruction)
Communication
Non-Protocol
R: Read only
W: Write only
R/W: Read or Write

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-61
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

8.2 How to Use RS2 Instruction


This section explains the function, operation and programming method of the RS2 instruction.
Available channels vary depending on the main unit.
For details, refer to Section 3.2.

1. Applicable devices
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System/User Digit Specification System/User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
S
m
D
n
n1

: Only available for FX3G, FX3GC, FX3U and FX3UC PLCs.


m, n: 0 to 4096 points
n1: K0, K1 or K2

2. Program example
S m D n n1
M0
FNC 87 D100 D0 D200 D1 K1
RS2

Communication channel
Head device storing send
data K0: ch 0
K1: ch 1
Number of send data: 0 to K2: ch 2
4096
Amount of received data: 0 to 4096 points
Head device storing receive data

F-62
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

A
8.2.1 Applicable frames

Common Items
Message frames used in communication can be selected by setting the communication format.
The table below shows message frames applicable to the RS2 instruction.

1 Data
B

N:N Network
2 Data CR+LF

3 Data Terminator

4 Data Terminator CR+LF


C

Parallel Link
5 Data Terminator Sum check

6 Data Terminator Sum check CR+LF

7 Header Data
D

Computer Link
8 Header Data CR+LF

9 Header Data Terminator

10 Header Data Terminator CR+LF


E

Communication
Inverter
11 Header Data Terminator Sum check

12 Header Data Terminator Sum check CR+LF

1. Header F
When "header provided" is selected in the communication format settings, the values of D8380 and D8381

(RS/RS2 Instruction)
Communication
Non-Protocol
are used for ch0, and the values of D8410 and D8411 are used for ch1, and the values of D8430 and D8431
are used for ch2.
Up to four headers can be set.
Header Header 1 Header 2 Header 3 Header 4
ch0 D8380 (lowest-order byte) D8380 (highest-order byte) D8381 (lowest-order byte) D8381 (highest-order byte) G

(FX2N-232IF)
Communication
Non-Protocol
ch1 D8410 (lowest-order byte) D8410 (highest-order byte) D8411 (lowest-order byte) D8411 (highest-order byte)
ch2 D8430 (lowest-order byte) D8430 (highest-order byte D8431 (lowest-order byte) D8431 (highest-order byte)
When data is sent, the data set in the devices above is added at the head of the specified send data.
When data is received, receiving begins when the data set in the devices above is received continuously.
Even if "header provided" is selected, headers are not provided if header 1 is set to "00H". H
The area before 00H (in 1-byte units) is used to set the headers.
Communication
Programming

Caution
Set the header before driving the RS2 instruction. Do not change the setting while the RS2 instruction is
being driven.
I
Maintenance
Remote

Apx.A
models
Discontinued

F-63
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

2. Terminator
When "terminator provided" is selected in the communication format settings, the values of D8382 and D8383
are used for ch0, and the values of D8412 and D8413 are used for ch1, and the values of D8432 and D8433
are used for ch2.
Up to four terminators can be set.
Terminator Terminator 1 Terminator 2 Terminator 3 Terminator 4
ch0 D8382 (lowest-order byte) D8382 (highest-order byte) D8383 (lowest-order byte) D8383 (highest-order byte)
ch1 D8412 (lowest-order byte) D8412 (highest-order byte) D8413 (lowest-order byte) D8413 (highest-order byte)
ch2 D8432 (lowest-order byte) D8432 (highest-order byte) D8433 (lowest-order byte) D8433 (highest-order byte)
When data is sent, the data set in the devices above is added at the end of the specified send data.
When data is received, receiving is completed*1 when the data set in the devices above is received.
Even if "terminator provided" is selected, terminators are not provided if terminator 1 is set to "00H".
The area before 00H (in 1-byte units) is used to set the terminators.
Caution
Set the terminator before driving the RS2 instruction. Do not change the setting while the RS2 instruction is
being driven.

*1. Receiving is also completed when the amount of received data specified by the RS2 instruction is
finished receiving or when data receiving is suspended and the next set of data is not received within
the time-out time setting device (D8379, D8409 or D8429).

3. Sum check
When "sum check provided" is selected in the communication format setting, the sum check is executed for
the sent and received data.
When selecting "sum check provided", make sure to select "terminator provided".
When data is sent, the sum of "data" + "terminator" is calculated, and added to the send data.
When data is received, it is checked whether or not the received sum is equivalent to the sum calculated by
the PLC.
For details on sum check, refer to Subsection 8.2.6.

4. CR + LF
When "CR + LF provided" is selected in the communication format setting, the character code of "CR + LF" is
added at the end of the send data.
When data is received, receiving is completed when "CR + LF" is received continuously.
However, receiving is also completed when the specified amount of received data is received or when data
receiving is suspended and the next set of data is not received within the time-out time setting.
Make sure that "CR" is not included in the message.

F-64
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

A
8.2.2 Function and operation

Common Items
RS2 instruction specifies the head device storing the send data from the PLC, amount of data, head device
storing the received data and maximum allowable amount of received data.
Create a program as shown below.
Command B
M0

N:N Network
FNC 87 D100 D0 D200 K30 K1
RS2
When the command contact (M0) is set to ON, the PLC waits for sending and receiving.
Sending For handling of sent and received data, refer to Subsection 8.2.3.
command
(pulse operation
type)
C

Parallel Link
M1
Send data is written.

When the sending command (M1) is set to ON, write the send data to D100 and later (as many
devices as the specified amount). Give the sending command of the pulse operation type.
After writing the send data, set the sending request device (M8402) to send the data.
Sending
D

Computer Link
request

SET M8402

When sending is completed, the sending request device (M8402) is automatically reset. Do not reset
it in a sequence program.
For the operation when data is sent, refer to Subsection 8.2.4. E
Receiving

Communication
Inverter
complete
M8403
Receive data is moved.

When the PLC receives data from the connected equipment, the receiving complete flag (M8403)
turns ON.
When M8403 turns ON, move the received data stored in D200 to another storage area. F

(RS/RS2 Instruction)
Communication
Non-Protocol
Receiving
complete

RST M8403

After moving the received data, reset the receiving complete flag (M8403).
While M8403 is ON, the PLC cannot receive the next set of receive data.
For the operation when data is received, refer to Subsection 8.2.5.
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-65
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

8.2.3 Send/receive data and amount of data


RS2 instruction can handle send data and receive data while storing two characters in one data register.
M8000
FNC 87 D100 K4 D200 K20 K1
RS2

Communication format setting


Control line not provided
Headers provided [DLE + STX (D8410: 0210H D8411: 0000H)]
Terminators provided [DLE + ETX (D8412: 0310H D8413: 0000H)]
Sum check provided
CR + LF added

1. Send data and amount of remaining send data


Header Data area Terminator Sum data . . . . . The order is different
from the data area
DLE STX 31H 32H 33H 34H DLE ETX 44H 44H
D8410 D8410 D100 D100 D101 D101 D8412 D8412 Sum Sum CR LF
lowest highest lowest highest lowest highest lowest highest highest lowest
-order -order -order -order -order -order -order -order -order -order
Send data byte byte byte byte byte byte byte byte byte byte

M8402
Sending request

It is automatically reset
Set it in a program. 4 when sending is
3 completed
D8403 2
Amount of remaining 1
send data 0

D8416 00H 31H 63H 96H CAH DAH DDH


Sending sum

F-66
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

A
2. Receive data and amount of data already received

Common Items
Header Data area Terminator Sum data . . . . . The order is different
from the data area
DLE STX 35H 36H 37H 38H DLE ETX 45H 44H
D8410D8410 D200 D200 D201 D201 D202 D202 Sum Sum CR
lowest highest lowest highest lowest highest lowest highest highest lowest
LF
B
-order -order -order -order -order -order -order -order -order -order

N:N Network
Receive data byte byte byte byte byte byte byte byte byte byte

M8403
Receiving complete
C

Parallel Link
It is set when Reset it in a
receiving is program
It is cleared when completed
header is received.
It is cleared
when the
D

Computer Link
receiving
complete flag
is cleared
6
5
4
3 E
2

Communication
Inverter
D8403
Amount of data 1
already received 0 The calculation
result is converted
into ASCII codes,
and compared
F

(RS/RS2 Instruction)
Communication
Non-Protocol
D8415
Receiving sum 00H 35H 6BH A2H DAH EAH EDH 00H
(calculation result)

Caution
G

(FX2N-232IF)
Communication
Non-Protocol
The 8-bit mode is not applicable in RS2 instruction.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-67
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

8.2.4 Operation when data is sent


When the sending request flag is set to ON while RS2 instruction is driven, the PLC sends the data stored in
the specified data registers S to ( S +m-1).
When using communication port ch0, set M8372.
When using communication port ch1, set M8402.
When using communication port ch2, set M8422.
When sending of the data is completed, the sending request flag is automatically set to OFF.

1. Time at which sending is started


When RS2 instruction is executed after the sending request flag is set to ON, the PLC starts to send.
When sending is started, the PLC sends the data stored in the data registers specified by RS2 instruction in
interrupt processing regardless of the operation cycle.

2. Time at which sending is completed


When all send data*1 is sent, sending is completed.
*1. The "terminators", "sum check" and "CR + LF" set in the communication format are included also in
the send data.

3. Cautions on sending
When sending data, observe the following cautions
1) While the sending request flag is ON, do not change the amount of send data or the contents of the send
data.
2) Do not set the sending request flag to OFF in a sequence program.
If the send data is changed while the sending request flag is ON or if the sending request flag is set to
OFF in a sequence program, correct data is not sent.

8.2.5 Operation when data is received


When RS2 instruction is executed, the PLC waits to receive. When the PLC receives data from the connected
equipment and receiving is completed, the receiving complete flag is set to ON.
When communication port ch0 is used, M8373 turns ON.
When communication port ch1 is used, M8403 turns ON.
When communication port ch2 is used, M8423 turns ON.
When the PLC receives data, it stores the received data to the data registers D to ( D +n-1) specified
by the RS2 instruction.
While the receiving complete flag is ON, the PLC cannot receive new data.

1. Time at which receiving is started


When the PLC receives data while it is waiting to receive, it starts receiving data.
When receiving begins, the PLC stores the received data in interrupt processing regardless of the operation
cycle.
When the headers are specified in the communication format, however, the PLC starts receiving when it
continuously receives the codes set in the headers. The PLC stores the received data except the headers.

F-68
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

A
2. Time at which receiving is completed

Common Items
Receiving is completed in the following three conditions. When either condition is established, receiving is
completed.
1) When the PLC receives the amount of receive data specified by the RS2 instruction
2) When the "terminators", "sum check" and "CR + LF" set in the communication format are received normally.
.......... Data CR+LF
B

N:N Network
.......... Data Terminator

.......... Data Terminator CR+LF

.......... Data Terminator Sum check C

Parallel Link
.......... Data Terminator Sum check CR+LF

3) When data receiving is suspended and the PLC does not receive the next set of data within the time set
within the time-out time setting device (D8379, D8409 or D8429), the time-out check flag (M8379, M8409
or M8429) turns ON.
D
3. Operation of time-out check flag

Computer Link
When data receiving is suspended, if the PLC does not receive the next set of data within the preset time-out
time setting, the time-out check flag is set to ON.
At this time, the receiving complete flag is also set to ON.
The time-out judgment time can be set in the following range:
Setting range for ch0 and ch2: 1 to 3,276 (10 to 32,760 ms)
Setting range for ch1: 1 to 255 (10 to 2,550 ms)
E

Communication
Inverter
Name ch0 ch1 ch2
Time-out check flag M8379 M8409 M8429
Time-out time setting D8379 D8409 D8429

Receive data is suspended.


F

(RS/RS2 Instruction)
Communication
Non-Protocol
Receiving
Data
D8409 Set to OFF in sequence program.
Time-out check flag 10 ms
M8409 ON
Receiving complete
M8403 ON G

(FX2N-232IF)
Communication
Non-Protocol
The time-out check flag does not turn OFF automatically. Set it to OFF in the sequence program. (When the
receiving complete flag is set to OFF, the time-out check flag is also set to OFF.)
By using this function, the PLC can receive data from equipment where the amount of send data varies
without the terminator.

4. When the control line is set to the interlink mode


H
Communication
Programming

When the interlink mode is selected in the communication format, the following sequence is adopted from
start of receiving to completion of receiving:
1) When the amount of data already received becomes "preset amount of received data -30", the control line
ER (DTR) turns OFF.
When the control line ER (DTR) turns OFF, the external equipment should suspend data sending.
After the control line ER (DTR) turns OFF, the PLC can receive up to 30 characters (bytes).
I
Maintenance
Remote

2) When the external equipment suspends data sending, the PLC sets the time-out check flag and receiving
complete flag to ON after the preset time-out time setting.
Move the received data in a sequence program, and then set the receiving complete flag and time-out
check flag to OFF.
3) When the receiving complete flag is set to OFF, the control line ER (DTR) turns ON. Apx.A
When the control line ER (DTR) turns ON, restart data sending from the external equipment.
models
Discontinued

4) Repeat steps 1) to 3) until data receiving is completed.

F-69
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

5. Cautions on receiving
When receiving data, observe the following cautions
1) While the receiving complete flag is ON, the PLC cannot receive the next set of receive data.
When the receiving complete flag is set to OFF, the PLC waits to receive.
2) If the RS2 instruction is driven while the amount of received data "n" is "0", the receiving complete flag
(M8373, M8403, M8423) turns ON. To make the PLC wait to receive, set the amount of received data "n"
to "1" or more, and set the receiving complete flag (M8373, M8403, M8423) to OFF from ON.
3) Set the amount of received data to a value including "terminators", "sum check" and "CR+LF".
If the specified amount of received data is small, the serial communication error flag (M8062, M8063 or
M8438) turns ON.

F-70
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.2 How to Use RS2 Instruction

A
8.2.6 Sum check code

Common Items
The sum check code indicates a two-digit ASCII code converted from the lowest-order byte (8-bit) of the
result (sum) acquired by adding the sum check target data as hexadecimal data.
By setting a parameter, set whether or not the sum check code is added in the message.
When "sum check provided" is selected, the sum check code is added in the message during sending. B
During receiving, the sum check code is compared with the value calculated from the received data to

N:N Network
check the received data.
When "sum check not provided" is selected, the sum check code is not added, so the received data is not
checked either.
A calculation example of the sum check code is shown below.

Example: When the communication format (parameters) is set as follows


C

Parallel Link
- Control line not provided
- Headers provided [DLE+STX (D8410: 0210H, D8411: 0000H)]
- Terminators provided [DLE+ETX (D8412: 0310H, D8413: 0000H)]

In the case of send data


D
Header Data area Terminator . . . . . The order is

Computer Link
Sum data different from
the data area.
DLE STX 31H 32H 33H 34H DLE ETX 44H 44H
D8410 D8410 D100 D100 D101 D101 D8412 D8412 Sum Sum CR LF
lowest highest lowest highest lowest highest lowest highest highest lowest
Send data
-order -order
byte byte
-order -order -order -order
byte byte byte byte
-order -order -order
byte byte byte
-order
byte E

Communication
Inverter
Sum check code target
D100 lowest-order bits 31H
D100 highest-order byte 32H
D101 lowest-order byte 33H
D101 highest-order byte 34H Converted into ASCII codes
D8412 lowest-order byte 10H (DLE) F
D8412 highest-order byte 03H (ETX)

(RS/RS2 Instruction)
Communication
Non-Protocol
DDH

In the case of receive data

. . . . . The order is
Header Data area Terminator Sum data different from
the data area.
G

(FX2N-232IF)
Communication
Non-Protocol
45H 44H
DLE STX 35H 36H 37H 38H DLE ETX Sum Sum
D8410 D8410 D200 D200 D201 D201 D202 D202 D8414 D8414 CR LF
lowest highest lowest highest lowest highest lowest highest highest lowest
-order -order -order -order -order -order -order -order -order -order
Receive data byte byte byte byte byte byte byte byte byte byte
H
Sum check code target
Communication
Programming

D200 lowest-order bits 35H


D200 highest-order byte 36H
D201 lowest-order byte 37H
D201 highest-order byte 38H Compared
D202 lowest-order byte 10H
D202 highest-order byte 03H
EDH 4544H
Converted into ASCII codes
I
Maintenance
Remote

Apx.A
models
Discontinued

F-71
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.3 Operation of Control Line

8.3 Operation of Control Line


FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs execute full-duplex, bidirectional communication. When
executing half-duplex, bidirectional communication, pay attention not to set the sending request to ON while
receiving. If the sending request is set to ON, the PLC starts to send. As a result, the external equipment may
not be able to receive data, and the sent and received data may be destroyed.
In full-duplex, bidirectional communication, the sending wait flag M8371, M8401, and M8421 does not turn
ON.
However, the sending wait flag M8371, M8401, and M8421 remains ON while the DR (DSR) is OFF, the PLC
waits to send, and the control line is in the standard mode or interlink mode.

1. When the control line is not provided


RS2
instruction OFF ON
driving

SD (TXD) Message Message Message


Send data 1 3 5

Sending OFF ON
request
M8402
RD (RXD) Message Message 4
Receive data 2

Receiving OFF ON ON
complete
M8403
Receiving wait status Reset it in a sequence program.
is started. While it remains ON, the PLC cannot receive the next
set of data.

F-72
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.3 Operation of Control Line

A
2. When the control line is in the standard mode

Common Items
Use this mode when only sending or receiving.
1) When only sending is executed
RS2
instruction OFF ON
driving B

N:N Network
SD (TXD) Message Message Message
Send data 1 1 2

Sending OFF ON
request
M8402 C

Parallel Link
ER (DTR) OFF ON

DR (DSR) OFF ON

2) When only receiving is executed [The DR (DSR) signal is not used.]


D
RS2

Computer Link
instruction OFF ON
driving

RD (RXD) Message Message


Receive data 1 2
E

Communication
Inverter
ER (DTR) OFF ON

Receiving
complete OFF ON ON
M8403
Reset it in a sequence program.
While it remains ON, the PLC cannot receive the next set of data. F

(RS/RS2 Instruction)
Communication
Non-Protocol
3. When the control line is in the modem mode
RS2
instruction OFF ON
driving
G
SD (TXD) Message

(FX2N-232IF)
Communication
Non-Protocol
Message 4
Send data 1

Sending OFF ON
request
M8402
ER (DTR) OFF ON
H
Communication
Programming

RD (RXD) Message 2 Message 3


Receive data

Receiving
complete
OFF ON ON I
Maintenance
Remote

M8403
DR (DSR) OFF ON

Reset it in a sequence program.


While it remains ON, the PLC cannot receive the next set of data.
Apx.A
models
Discontinued

F-73
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.3 Operation of Control Line

4. When the control line is in the interlink mode


RS2
instruction OFF ON
driving

SD (TXD) Message Message Message


Send data 2 4 4

Sending
request ON OFF
M8402
DR (DSR) OFF *1 ON *1 *1
Up to 30 characters can be
received. *2

RD (RXD) Message Message 3 Message


Receive data 1 3
Time-out
time setting
D8409 10 ms
Time-out
check
flag M8409

Receiving
complete OFF ON ON ON
M8403
ER (DTR) ON OFF

Reset it in a sequence program.


While it remains ON, the PLC cannot receive the next set of data.

*1. On the external equipment side, set the DR (DSR) signal to ON when the external equipment is ready
to receive.
The FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs sends the send data when both the DR (DSR) signal
and the sending request turn ON.
*2. In the interlink mode, the PLC sets ER (DTR) to OFF when the amount of data already received
becomes "Number of bytes to be received -30", and asks the external equipment to stop sending.
After that, the PLC can only receive up to 30 characters. In this case, temporarily stop sending, and
then send the remaining data after the ER (DTR) signal turns ON again.
When sending is stopped, the PLC finishes receiving after the time-out time setting is reached.
When sending is not stopped, the PLC finishes receiving after it has received the final send data or 30
characters. Accordingly, make sure that the number of receive characters are "30 + ".

F-74
FX Series PLC User's Manual - Data Communication Edition 8 Creating Programs (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 8.4 Important Points in Creating Programs

A
8.4 Important Points in Creating Programs

Common Items
1) The RS2 instruction can be used as many times as necessary in a program, but make sure that only one
RS2 instruction is driven in each communication port at a time.
For multiple RS instructions to be driven, make sure the OFF time is longer than one scan time.
2) Do not use another instruction (such as a RS instruction or IVDR instruction) which uses the same B
communication port. If such an instruction is used, communication may not function normally.

N:N Network
3) While a RS2 instruction is being driven, change of D8370, D8400 or D8420 is prohibited.
To change D8370, D8400 or D8420, set the RS2 instruction to OFF, set D8400 or D8420 to "0", and then
set a new value to D8400 or D8420.
4) In the interlink mode, set the amount of received data "n" to "31" or more.
If it is set to "30" or less, the control line ER (DTR) is set to OFF as soon as the PLC receives data.
C

Parallel Link
5) FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs execute full-duplex, bidirectional communication. When
using half-duplex, bidirectional communication, pay attention not to turn ON the sending request flag
while receiving.
6) When using the header and terminator, set them before driving the RS2 instruction. Do not change the
setting while the RS2 instruction is being driven. D
7) When RS-485 communication is executed in FX3U and FX3UC PLCs, it may take 300 s until the PLC

Computer Link
starts receiving after it has completed sending.
Assure 300 s or more in counterpart equipment as the period from completion of receiving to start of
sending.

8.5 Communication Error E

Communication
Inverter
When a communication error occurs, the error flag M8062 turns ON during communication using ch0, the
error flag M8063 turns ON during communication using ch1, or the error flag M8438 turns ON during
communication using ch2. D8063 or D8438 stores the error code respectively.
Error code
D8062 (ch0) D8063 (ch1) D8438 (ch2)
Description F

(RS/RS2 Instruction)
Communication
Non-Protocol
6201 6301 3801 Parity error, overrun error or framing error
6202 6302 3802 Defective communication character
6203 6303 3803 Receive data sum mismatch
6204 6304 3804 Defective data format
6205 6305 3805 Defective command G

(FX2N-232IF)
Communication
Non-Protocol
6206 6306 3806 Monitoring timeout

Confirm the contents in "Chapter 11. Troubleshooting".

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-75
FX Series PLC User's Manual - Data Communication Edition 9 Practical Program Example (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 9.1 Example of Printing Using RS2 Instruction (Using RS-232C Connection)

9. Practical Program Example (RS2 Instruction)

9.1 Example of Printing Using RS2 Instruction (Using RS-232C Connection)


In this example, a printer with the RS-232C interface is connected to a PLC, and the data sent from the PLC
is printed.

1. System configuration
ch1

Sending
RD

SD

+
FX3U-232-BD FX3U Series

Use a communication cable suitable to the pin arrangement of the connector of the printer used.

Communication format
Align the communication format in the PLC with that in the printer used.
(The table below shows the communication format in the main unit.)
Data length 8-bit
Parity Even
Stop bit 2-bit
Baud rate 2400 bps
Header Not provided
Terminator Not provided
Control line (H/W) Standard/RS-232C, provided
Communication method (protocol) Non-protocol method
CR, LF Not provided

F-76
FX Series PLC User's Manual - Data Communication Edition 9 Practical Program Example (RS2 Instruction)
Non-Protocol Communication (RS/RS2 Instruction) 9.1 Example of Printing Using RS2 Instruction (Using RS-232C Connection)

A
2. Sequence program

Common Items
M8002
H006F D8400 The
MOV communication b15 b0
format is set.
0000 0000 0110 1111
0 0 6 F B

N:N Network
This step is not required when the
communication parameters are
X000 RS2 already set.
RS2 D10 K11 D50 K0 K1 instruction
is driven.

X001 C
PLS M0

Parallel Link
M0
MOV H6574 D10

H7473 D11
D
MOV

Computer Link
MOV H6C20 D12 Send data is written.

MOV H6E69 D13


E

Communication
Inverter
MOV H0D65 D14

MOV H000A D15 F

(RS/RS2 Instruction)
Communication
Non-Protocol
Sending request
SET M8402 is given.

END G

(FX2N-232IF)
Communication
Non-Protocol
3. Operation

Turn ON the power to the PLC and printer, set the PLC to RUN mode,
Power is turned
ON. and set the printer to the online mode.
At this time, the communication format is set in the PLC. H
Communication
Programming

X000.ON

RS2 instruction is X000 is set to ON to drive RS2 instruction.


driven. At this time, send data is stored in 6 devices from D10 to D15.

X001.ON
Every time X001 is set to ON, data stored in D10 to D20 is sent to the
I
Maintenance
Remote

Data is sent.
printer.
ASCII codes are used in this example.
(The sending complete flag is automatically reset.)

Apx.A
models
Discontinued

F-77
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.1 Other Communication Type Used Together

10. When Combined with Another Communication


This chapter explains how to use non-protocol communication (RS or RS2 instruction) together with another
communication type.

10.1 Other Communication Type Used Together


In FX PLCs, the following communication types can be changed over.
When changing over the communication types above, it is necessary to set the communication using a
sequence program.

Programming [1] Non-protocol communication


communication (RS/RS2 instruction)

[1] Applicable only in FX2N PLCs Ver. 2.01 or later, and FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

Computer link [2] Non-protocol communication


communication (RS/RS2 instruction)

[2] Applicable only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

The tables below show devices used in sequence programs.


1) RS instruction
Device Name Description
D8120 Communication format setting Sets the communication format.
Operation mode display
D8419 Allows the communication type being executed to be checked.
(in FX3S, FX3G, FX3GC, FX3U and FX3UC)

2) RS2 instruction
Available channels vary depending on the main unit.
For details, refer to Section 3.2.
Device
Name Description
ch0 ch1 ch2
D8370 D8400 D8420 Communication format setting Sets the communication format.
Allows the communication type being executed to be
D8389 D8419 D8439 Operation mode display
checked.

For the communication setting method, refer to Section 10.6.


For details on the operation mode display, refer to Subsection 11.4.1.

F-78
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.2 When Combined with Programming Communication

A
10.2 When Combined with Programming Communication

Common Items
In FX2N PLCs Ver. 2.01 or later, and FX2NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, non-protocol
communication in accordance with RS-232C using RS instruction can be changed over to the programming
communication for peripheral equipment.
B
10.2.1 For FX2N and FX2NC PLCs

N:N Network
In FX2N PLCs Ver. 2.01 or later, and FX2NC PLCs, non-protocol communication using RS instruction by way
of RS-232C port in the FX2N-232-BD (for FX2N PLCs), FX0N-232ADP or FX2NC-232ADP can be changed
over to the communication with a programming tool (programming communication) by the following methods.
If the external equipment executes another type of communication while the programming communication is
selected, the PLC sends back "NAK".
C

Parallel Link
1. When changing over using RUN mode and STOP mode
Set the communication format to one of the settings shown below to use non-protocol communication (in
accordance with RS-232C) using the RS instruction while in RUN mode and then use the programming
communication while in STOP mode.
Contents
D
Item

Computer Link
H0086 H0186 H0286 H0386
Data length 7-bit
Parity bit Even
Stop bit 1-bit
Baud rate (bps) 9600 bps E
Header Not provided Provided Not provided Provided

Communication
Inverter
Terminator Not provided Provided
Control line Not provided

2. When changing over using the RS instruction while in RUN mode


When changing over non-protocol communication using RS instruction to the programming communication F
while in RUN mode, set RS instruction to OFF, and then overwrite the communication format (D8120) to

(RS/RS2 Instruction)
Communication
Non-Protocol
"H0000".
Before starting up RS instruction again, make sure to properly overwrite the communication format (D8120)
used in the RS instruction.
X0
MOV P H0086 D8120 G

(FX2N-232IF)
Communication
Non-Protocol
RS D1 K1 D2 K1
X0
MOV P H0000 D8120

In this setting also, the communication mode can be changed over using RUN mode and STOP mode if the
condition shown in 1 above is satisfied.
H
Communication
Programming

3. Caution on using the RS instruction and programming communication together


Do not use the communication setting by parameters. Use the communication format device (D8120).

I
Maintenance
Remote

Apx.A
models
Discontinued

F-79
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.2 When Combined with Programming Communication

10.2.2 For FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs


In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, non-protocol communication using RS instruction can be
changed over to communication with a programming tool (programming communication) by the following
methods.
If the external equipment executes another type of communication while the programming communication is
selected, the PLC sends back "NAK".
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the communication type operating in the communication port
can be checked in the operation mode display device (D8419).

1. When changing over using RUN mode and STOP mode


Set the communication format as shown below to use non-protocol communication (in accordance with RS-
232C) using RS instruction while in RUN mode and then use the programming communication while in STOP
mode.
Make sure to set the communication format used in the RS instruction to D8120, and write it before executing
the RS instruction.
X0
MOV P H0086 D8120

RS D1 K1 D2 K1

2. When changing over using the RS instruction while in RUN mode


When changing over non-protocol communication using RS instruction to the programming communication
while in RUN mode, set RS instruction to OFF, and then overwrite the communication format (D8120) to
"H0000".
Before starting up RS instruction again, make sure to properly overwrite the communication format (D8120)
used in the RS instruction.
X0
MOV P H0086 D8120

RS D1 K1 D2 K1
X0
MOV P H0000 D8120

3. Caution on using the RS instruction and programming communication together


Do not use the communication setting by parameters. Use the communication format device (D8120).

F-80
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.3 When Combined with Computer Link Communication

A
10.3 When Combined with Computer Link Communication

Common Items
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, non-protocol communication (in accordance with RS-232C or
RS-485) using the RS instruction can be changed over to a protocol dedicated to computer link by the
following methods.
The protocol supported by the communication port can be checked in the operation mode display device B
(D8149).

N:N Network
1. When changing over using RUN mode and STOP mode
Set the communication format as shown below to use non-protocol communication (in accordance with RS-
232C or RS-485) using the RS instruction while in RUN mode and then use computer link while in STOP
mode.
Set computer link using parameters. C
Make sure to set the communication format used in the RS instruction to D8120, and write it before executing

Parallel Link
the RS instruction.
X0
MOV P H0086 D8120

RS D1 K1 D2 K1 D

Computer Link
2. When changing over using the RS instruction while in RUN mode
When changing over non-protocol communication using the RS instruction to computer link while in RUN
mode, set the RS instruction to OFF, and then overwrite the communication format (D8120) to "H0000".
Set computer link using parameters.
Before starting up the RS instruction again, make sure to properly overwrite the communication format E
(D8120) used in the RS instruction.

Communication
Inverter
X0
MOV P H0086 D8120

RS D1 K1 D2 K1
X0
MOV P H0000 D8120
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-81
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.4 When Combined with Programming Communication

10.4 When Combined with Programming Communication


In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, non-protocol communication using RS2 instruction can be
changed over to communication with a programming tool (programming communication) by the following
methods.
If the external equipment executes another type of communication while the programming communication is
selected, the PLC sends back "NAK".
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the communication type operating in the communication port
can be checked in the operation mode display devices (D8389, D8419 and D8439).

1. When changing over using RUN mode and STOP mode


Set the communication format as shown below to use non-protocol communication (in accordance with RS-
232C) using the RS2 instruction while in RUN mode and then use the programming communication while in
STOP mode.
Make sure to set the communication format used in the RS2 instruction to D8370, D8400 or D8420, and write
it before executing the RS2 instruction.
X0
MOV P H0086 D8400
Command
RS2 D1 K1 D2 K1 K1

2. When changing over using the RS2 instruction while in RUN mode
When changing over non-protocol communication using the RS2 instruction to the programming
communication while in RUN mode, set the RS2 instruction to OFF, and then overwrite the communication
format (D8370, D8400 or D8420) to "H0000".
Before starting up the RS2 instruction again, make sure to properly overwrite the communication format
(D8370, D8400 or D8420) used in the RS2 instruction.
X0
MOV P H0086 D8400

RS2 D1 K1 D2 K1 K1
X0
MOV P H0000 D8400

3. Caution on using the RS2 instruction and programming communication together


Do not use the communication setting by parameters. Use the communication format device (D8370, D8400
or D8420).

F-82
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.5 Using RS2 Instruction and Computer Link Communication Together

A
10.5 Using RS2 Instruction and Computer Link Communication Together

Common Items
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, non-protocol communication (in accordance with RS-232C or
RS-485) using RS2 instruction can be changed over to computer link by the following methods.
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the communication type operating in the communication port
can be checked in the operation mode display devices (D8389, D8419 and D8439). B

N:N Network
1. When changing over using RUN mode and STOP mode
Set the communication format as shown below to use non-protocol communication (in accordance with RS-
232C) using RS2 instruction while in RUN mode and then use a protocol for computer link while in STOP mode.
Set computer link using parameters.
Make sure to set the communication format used in the RS2 instruction to D8370, D8400 or D8420, and write
it before executing the RS2 instruction. C

Parallel Link
X0
MOV P H0086 D8400
Command
RS2 D1 K1 D2 K1 K1

Non-protocol communication (in accordance with RS-485) cannot be changed over to computer link using D
RUN mode and STOP mode.

Computer Link
When changing over non-protocol communication (in accordance with RS-485) to computer link, refer to
"2. When changing over using the RS2 instruction while in RUN mode" below.

2. When changing over using the RS2 instruction while in RUN mode
When changing over non-protocol communication using the RS2 instruction to computer link while in RUN
mode, set the RS2 instruction to OFF, and then overwrite the communication format (D8370, D8400 or E
D8420) to "H0000".

Communication
Inverter
Set computer link using parameters.
Before starting up the RS2 instruction again, make sure to properly overwrite the communication format
(D8370, D8400 or D8420) used in the RS2 instruction.
X0
MOV P H0086 D8400 F

(RS/RS2 Instruction)
Communication
Non-Protocol
RS2 D1 K1 D2 K1 K1
X0
MOV P H0000 D8400

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-83
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.6 Communication Setting Method Using Sequence Program

10.6 Communication Setting Method Using Sequence Program


In the setting method using a sequence program, transfer values to the communication format device (D8120,
D8400 or D8420).
This section explains related devices and the setting method using a sequence program.

10.6.1 Communication setting for RS instruction


The following device is used in the communication setting.

1. D8120 (communication format)


By setting values to D8120, the data length, parity, baud rate, etc. can be set.
The table below shows the contents of D8120.
Contents
Bit No. Name
0 (bit = OFF) 1 (bit = ON)
b0 Data length 7-bit 8-bit
b2, b1
b1 (0, 0): Not provided
Parity
b2 (0, 1): Odd
(1, 1): Even
b3 Stop bit 1-bit 2-bit
b7, b6, b5, b4 b7, b6, b5, b4
b4 (0, 0, 1, 1): 300 (0, 1, 1, 1): 4800
b5 Baud rate (0, 1, 0, 0): 600 (1, 0, 0, 0): 9600
b6 (bps) (0, 1, 0, 1): 1200 (1, 0, 0, 1): 19200
b7
(0, 1, 1, 0): 2400 (1, 0, 1, 0): 38400*1
b8 Header Not provided Provided (D8124) initial value: STX (02H)
b9 Terminator Not provided Provided (D8125) initial value: ETX (03H)
b11, b10
(0, 0): Not provided <RS-232C interface>
Non- (0, 1): Standard mode <RS-232C interface>
protocol (1, 0): Interlink mode <RS-232C interface>
commu- (FX2N PLCs Ver. 2.00 or later, and FX2NC, FX3S, FX3G, FX3GC,
b10 nication FX3U, FX3UC PLCs)
Control line
b11 (1, 1): Modem mode
<RS-232C interface, RS-485/RS-422 interface*2>
Com- b11, b10
puter (0, 0): RS-485/RS-422 interface
link (1, 0): RS-232C interface
b12 Not applicable
*3 Sum check Not added Added
b13
b14*3 Protocol Not used Used
*3 Control procedure Format 1 Format 4
b15

*1. This setting is available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.
*2. When using the RS-485/RS-422 interface, only FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G,
FX3GC, FX3U and FX3UC PLCs are applicable.
*3. Make sure to set as "0" when using non-protocol communication.

F-84
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.6 Communication Setting Method Using Sequence Program

A
To set the communication type, use the following program.

Common Items
M8002 Data length 7-bit
FNC 12 H0C86 D8120
MOV Parity Even
Initial pulse
Stop bit 1-bit
b15
D8120 = [ 0000 1100 1000
b0
0110 ]
Baud rate 9600 bps B
Protocol Non-protocol

N:N Network
0 C 8 6
Header Not provided
Terminator Not provided
Control line Modem mode

Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-85
FX Series PLC User's Manual - Data Communication Edition 10 When Combined with Another Communication
Non-Protocol Communication (RS/RS2 Instruction) 10.6 Communication Setting Method Using Sequence Program

10.6.2 Communication setting for RS2 instruction


The following devices are used in the communication setting.
When using communication port ch0, set D8370.
When using communication port ch1, set D8400.
When using communication port ch2, set D8420.

1. D8370, D8400 and D8420 (communication format)


By setting values to D8400 or D8420, the data length, parity, baud rate, etc. can be set.
The table below shows the contents of D8400 and D8420.
Contents
Bit No. Name
0 (bit = OFF) 1 (bit = ON)
b0 Data length 7-bit 8-bit
b2, b1
b1 (0, 0): Not provided
Parity
b2 (0, 1): Odd
(1, 1): Even
b3 Stop bit 1-bit 2-bit
b7, b6, b5, b4 b7, b6, b5, b4
b4
(0, 0, 1, 1): 300 (0, 1, 1, 1): 4800
b5 Baud rate
(0, 1, 0, 0): 600 (1, 0, 0, 0): 9600
b6 (bps)
(0, 1, 0, 1): 1200 (1, 0, 0, 1): 19200
b7
(0, 1, 1, 0): 2400 (1, 0, 1, 0): 38400
b8 Header Not provided Provided*1
b9 Terminator Not provided Provided*1
b12, b11, b10
Non- (0, 0, 0): Not provided <RS-232C interface>
b10 protocol (0, 0, 1): Standard mode <RS-232C interface>
b11 Control line commu- (0, 1, 0): Interlink mode <RS-232C interface>
b12 nication (0, 1, 1): Modem mode <RS-232C interface>
*2 (1, 1, 1): Communication in accordance with RS-485
<RS-485/RS-422 interface>
b13 Sum check Not added Added*4
b14*3 Protocol Not used Used
Control proce-
b15 CR, LF: Not used (Format 1) CR, LF: Used (Format 4)
dure (CR, LF)

*1. In RS2 instruction, up to four headers and up to four terminators can be set.
*2. The control line is not available in FX3G, FX3GC PLCs when ch0 is used. Set "(1, 1, 1)".
*3. Make sure to set as "0" when using non-protocol communication.
*4. When executing non-protocol communication using RS2 instruction, add the sum check code after the
terminators.
Make sure to set the terminators when adding the sum check code.

To set the communication type, use the following program.


M8002 Data length 7-bit
FNC 12 H1C86 D8400
Initial pulse MOV Parity Even
Stop bit 1-bit
b15 b0
D8120 = [ 0001 1100 1000 0110 ] Baud rate 9600 bps
1 C 8 6 Protocol Non-protocol
Header Not provided
Terminator Not provided
Communication in
Control line
accordance with RS-485

F-86
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Non-Protocol Communication (RS/RS2 Instruction) 11.1 Checking FX PLC Version Applicability

Common Items
11. Troubleshooting
This chapter explains troubleshooting and error codes. B

N:N Network
11.1 Checking FX PLC Version Applicability
Verify that the FX PLC main unit is an applicable version in non-protocol communication.
For version applicability, refer to Section 1.3.
C

Parallel Link
11.2 Checking Communication Status Based on LED Indication
Check the status of the "RD" and "SD" indicator LEDs provided in the optional equipment.
LED status
RD SD
Operation status D

Computer Link
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received
Off Off Data is not sent nor received.
E

Communication
Inverter
11.3 Checking Installation

1. Mounting status
If the communication equipment is not securely connected to the PLC, communication is not possible.
For mounting method, refer to the respective communication equipment manual. F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. Power supply (for FX0N-485ADP)
The FX0N-485ADP requires a driving power supply. Verify that the power supply is provided correctly.

3. Wiring
Verify that the wiring to an communication equipment is correct. If the communication equipment is wired
incorrectly, communication is not possible.
G

(FX2N-232IF)
Communication
Non-Protocol
For wiring method check, refer to Chapter 4.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-87
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Non-Protocol Communication (RS/RS2 Instruction) 11.4 Checking Sequence Program

11.4 Checking Sequence Program

1. Communication settings in a sequence program


Verify that N:N Network (D8176 to D8180) and parallel link (M8070 and M8071) are not set.
Verify that the communication format (D8120, D8370, D8400 or D8420) is set correctly. If a communication
port is set more than once, communication is not possible.

2. Communication settings using parameters


Verify that the communication settings using parameters are correct. If the contents of the settings do not
agree, communication will not function correctly.
After changing any settings, make sure to turn OFF the PLC power, and then turn the power ON again.

3. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in non-
protocol communication (RS/RS2 Instruction). After changing the setting, make sure to reboot the PLC's power.

4. Presence of VRRD and VRSC instructions


1) Except FX3G, FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
2) In FX3G PLC
- In the case of the 14 points and 24-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions.
After deleting these instructions, turn OFF the PLC power, and then turn the power ON again.
3) In FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power.

5. Presence of IVCK, IVDR, IVRD, IVWR, IVBWR*1, and IVMC instructions (in FX3S, FX3G,
FX3GC, FX3U and FX3UC PLCs)
Verify that the IVCK, IVDR, IVRD, IVWR, IVBWR and IVMC instructions are not being used for the same
channel.
If these instructions are used for the same channel, revise them, turn OFF the PLC power, and then turn the
power ON again.
*1. Only available for FX3U and FX3UC PLCs.

6. Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.

7. Presence of EXTR instruction (in FX2N and FX2NC PLCs)


Verify that the EXTR instruction is not used in the program.
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.

8. Presence of RS and RS2 instructions


Verify that two or more RS/RS2 instructions are not being driven for the same channel.
If two or more RS/RS2 instructions are driven, modify the program so that only one RS/RS2 instruction is
driven.

9. Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and
FX3UC PLCs)
Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the
same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.

F-88
FX Series PLC User's Manual - Data Communication Edition 11 Troubleshooting
Non-Protocol Communication (RS/RS2 Instruction) 11.5 Checking the Absence/Presence of Errors

A
11.4.1 Checking communication port settings (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)

Common Items
1. Checking the operation mode
In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, the communication port operation status can be checked.
D8389 stores the communication type code currently adopted in communication port ch0.
D8419 stores the communication type code currently adopted in communication port ch1. B
D8439 stores the communication type code currently adopted in communication port ch2.

N:N Network
The table below shows the contents of the communication type codes.
Code Description
0 Programming communication
1 PP modem mode
2
3
Protocol dedicated to computer link
N:N Network
C

Parallel Link
4 RS instruction
5 RS2 instruction
6 Parallel link
7 Inverter instruction
8
9
The variable analog potentiometer expansion board is used.
MODBUS communication
D

Computer Link
10 CF-ADP
11 ENET-ADP
12 Input/output expansion board is used.
If the operation mode is different, check the parameters and sequence programs.
E
11.5 Checking the Absence/Presence of Errors

Communication
Inverter
1. Checking for communication errors
When a communication error occurs, the serial communication error flag turns ON.
When the communication port ch0 is used in FX3G, FX3GC PLCs, M8062 turns ON.
In all PLCs except FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port, M8063 turns ON. F
For FX3G, FX3GC, FX3U and FX3UC PLCs using the communication port ch1, M8063 turns ON.

(RS/RS2 Instruction)
Communication
Non-Protocol
When communication port ch2 is used in FX3G, FX3GC, FX3U and FX3UC PLCs, M8438 turns ON.
When the serial communication error flag turns ON, D8062, D8063 or D8438 stores the corresponding error code.
Available channels vary depending on the main unit.
For details, refer to Section 3.2.
2. Checking the error code
When the serial communication error flag turns ON, a corresponding error code shown below is stored in G
D8063 or D8438.

(FX2N-232IF)
Communication
Non-Protocol
Error code
Contents of error
ch0 (D8062) ch1 (D8063) ch2 (D8438)
6201 6301 3801 Parity error, overrun error or framing error
6202 6302 3802 Defective communication character
6203 6303 3803 Communication data sum mismatch H
Communication
Programming

6204 6304 3804 Defective data format


6205 6305 3805 Defective command
6206 6306 3806 Monitoring timeout
6307 3807 Modem initialization error
6308 3808 N:N Network parameter error
6309 3809 N:N Network setting error
I
Maintenance
Remote

6312 3812 Parallel link parameter error


6313 3813 Parallel link sum error
6314 3814 Parallel link format error
6320 3820 Inverter communication error
6330 3830 Memory access error
6340 3840 Special adapter connection error
Apx.A
models
Discontinued

When an error code above is stored, check the following items:


Wiring
Parameter settings

F-89
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.1 Related Device List (RS Instruction)

12. Related Data

12.1 Related Device List (RS Instruction)

1. Bit devices
Device Name Description R/W
M8063 Serial communication error flag This device turns ON when a communication error occurs. R
M8120 Communication setting keep This device keeps the communication setting status (for FX0N PLC). W
M8121 Sending wait flag This device remains ON while the PLC is waiting to send. R
When this device is set to ON by SET instruction, the PLC starts
M8122 Sending request R/W
to send.
M8123 Receiving complete flag This device turns ON when receiving is completed. R/W
M8124 Carrier detection flag This device turns ON and OFF in synchronization with the CD signal. R
This device turns ON when data receiving is suspended and the
M8129*1 Time-out check flag next set of receive data is not given within the time set by the time- R/W
out time setting device (D8129).
M8161 8-bit processing mode This device sets the send/receive data to 16-bit data or 8-bit data. W

R: Read only
W: Write only
R/W: Read or Write
*1. Not provided in FX2N PLCs before Ver. 2.00, and FX2(FX), FX2C, FX0N PLCs.

2. Word devices
Device Name Description R/W
Error code number of serial When the serial communication error flag (M8063) turns ON, this
D8063 R/W
communication error device stores the corresponding error code.
D8120 Communication format setting This device sets the communication format. R/W
Remaining amount of data to
D8122 This device stores the amount of remaining send data. R
be sent
Amount of data already
D8123 This device stores the amount of data already received. R
received
D8124 Header This device sets the header (initial value: STX (H02)). R/W
D8125 Terminator This device sets the terminator (initial value: ETX (H03)). R/W
D8129*2 Time-out time setting This device sets the time-out time. R/W
*3 Communication parameter display This device stores communication parameters set in the PLC. R
D8405
*3 Operation mode display This device stores the communication type being used. R
D8419

R: Read only
W: Write only
R/W: Read or Write
*2. Not provided in FX2N PLCs before Ver. 2.00, and FX2(FX), FX2C, FX0N PLCs.
*3. Provided only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

F-90
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.2 Details of related devices (RS instruction)

A
12.2 Details of related devices (RS instruction)

Common Items
This section explains devices used during non-protocol communication.

12.2.1 Serial communication error [M8063]


B
This device turns ON when an error occurs during serial communication.

N:N Network
1. Detailed contents
This device works as the serial communication error flag.
When this device turns ON, a corresponding error code is stored in D8063.

2. Cautions on use C

Parallel Link
The serial communication error flag does not turn OFF even after communication recovers its normal status.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.

12.2.2 Communication setting keep [M8120] D

Computer Link
Set this device to ON in a sequence program so that the communication setting is kept (for FX0N PLCs).

1. Detailed contents
In FX0N PLCs, set M8120 to ON in a sequence program so that the communication format setting is kept.

2. Cautions on use
E

Communication
Inverter
In FX0N PLCs, the communication setting status is kept only when M8120 is set to ON.
In any PLC other than the FX0N PLCs, setting of M8120 is not required.

12.2.3 Sending wait flag [M8121]


This device remains ON while the PLC is waiting to send. F

(RS/RS2 Instruction)
Communication
Non-Protocol
1. Detailed contents
In full-duplex communication in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs
While the control line is set to the standard or interlink mode in a communication parameter, when the
control line DR (DSR) turns OFF while sending data, the PLC waits to send and M8121 turns ON.
In full-duplex communication in all PLCs except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs G
M8121 does not turn ON.

(FX2N-232IF)
Communication
Non-Protocol
In half-duplex communication
When the sending request device is set to ON while data is being received, the PLC waits to send and
M8121 turns ON.

12.2.4 Sending request [M8122] H


Communication
Programming

When this device is set to ON by the SET instruction, the PLC starts to send.

1. Detailed contents
When this device is set to ON by the SET instruction, the PLC starts to send. When sending is completed, this
device is automatically set to OFF. I
Maintenance
Remote

2. Cautions on use
When setting this device to ON, set the drive condition in the pulse type.
In FX2N PLCs before Ver. 2.00, and FX2(FX), FX2C, FX0N, FX1S, FX1N, FX1NC PLCs, note the following
contents:
While the PLC is receiving data, next data is sent after the receiving is finished. During this period, the Apx.A
sending wait flag remains ON.
models
Discontinued

From when the head data is received until the receiving complete flag turns ON, it is regarded as data is
being received. If a sending request is given while the head data is being received, data is confused.

F-91
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.2 Details of related devices (RS instruction)

12.2.5 Receiving complete flag [M8123]


This device turns ON when receiving is completed.

1. Detailed contents
This device turns ON when receiving is completed.
Receiving is completed in one of the following three conditions.
When the PLC receives the amount of receive data specified by RS instruction
When "terminator provided" is selected in the communication format, and the PLC receives the code set in
the terminator
When data receiving is suspended and the PLC does not receive the next set of data within the time set in
the time-out time setting device
When the receiving complete flag turns ON, transfer the received data to another storage destination, and
then set this flag to OFF.
When this flag is set to OFF, the PLC waits to receive.

2. Cautions on use
When RS instruction is driven while the amount of received data is set to "0", the PLC does not wait to
receive. In such a case, set the amount of received data to "1" or more, set the receiving complete flag to ON,
and then set it to OFF.

12.2.6 Carrier detection flag [M8124]


This device turns ON and OFF in synchronization with the CD (DCD) signal.

1. Detailed contents
The CD (DCD) signal (channel receiving carrier detection) turns ON when the modem line is established.
While the carrier detection flag is OFF, the dial number can be sent.
While the carrier detection flag is ON, data can be sent and received.

12.2.7 Time-out check flag [M8129]


This device turns ON when data receiving is suspended, and the next set of receive data is not given within
the time set by the time-out time setting device.

1. Detailed contents
This device turns ON when data receiving is suspended and the next set of receive data is not given within
the time set by the time-out time setting device. The receiving complete flag also turns ON.
The time-out check flag turns OFF when the PLC waits to receive.
Using this function, the PLC can receive data from equipment where the amount of send data varies without
the terminator.
Receive data is
Receiving suspended.
Data
D8129 Set to OFF in sequence program.
Time-out check flag 10 ms
M8129 ON
Receiving complete
M8123 ON

F-92
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.2 Details of related devices (RS instruction)

A
12.2.8 Serial communication error code [D8063]

Common Items
When a serial communication error occurs, this device stores the corresponding error code.

1. Detailed contents
When a serial communication error occurs, this device stores the corresponding error code shown below.
B
Error code Contents of error

N:N Network
6301 Parity error, overrun error or framing error
6302 Defective communication character
6303 Communication data sum mismatch
6304 Defective data format
6305 Defective command
C

Parallel Link
6306 Monitoring timeout
6307 Modem initialization error
6308 N:N Network parameter error
6309 N:N Network setting error
6312 Parallel link character error D
6313 Parallel link sum error

Computer Link
6314 Parallel link format error
6320 Inverter communication error
6321 MODBUS communication error
6330 Memory access error E
6340 Special adapter connection error

Communication
Inverter
2. Cautions on use
Serial communication error code are not cleared even when communication is restored.
Serial communication errors are cleared in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs when the power is
turned off and on.
Serial communication errors are cleared in other PLCs when the mode is switched from STOP to RUN.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-93
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.2 Details of related devices (RS instruction)

12.2.9 Communication format setting [D8120]


This device sets the communication format.

1. Detailed contents
This device can set the data length, parity, baud rate, etc.
The table below shows the contents of the communication format setting.
Contents
Bit No. Name
0 (bit = OFF) 1 (bit = ON)
b0 Data length 7-bit 8-bit
b2, b1
b1 (0, 0): Not provided
Parity
b2 (0, 1): Odd
(1, 1): Even
b3 Stop bit 1-bit 2-bit
b7, b6, b5, b4 b7, b6, b5, b4
b4 (0, 0, 1, 1): 300 (0, 1, 1, 1): 4800
b5 Baud rate (0, 1, 0, 0): 600 (1, 0, 0, 0): 9600
b6 (bps) (0, 1, 0, 1): 1200 (1, 0, 0, 1): 19200
b7
(0, 1, 1, 0): 2400 (1, 0, 1, 0): 38400*1
b8 Header Not provided Provided (D8124) Initial value: STX (02H)
b9 Terminator Not provided Provided (D8125) Initial value: ETX (03H)
b11, b10
(0, 0): Not provided <RS-232C interface>
Non- (0, 1): Standard mode <RS-232C interface>
protocol (1, 0): Interlink mode <RS-232C interface>
commu- (FX2N PLC Ver. 2.00 or later, and FX2NC, FX3S, FX3G, FX3GC,
b10 nication FX3U, FX3UC PLCs)
Control line
b11 (1, 1): Modem mode
<RS-232C interface, RS-485/RS-422 interface*2>
Com- b11, b10
puter (0, 0): RS-485/RS-422 interface
link (1, 0): RS-232C interface
b12 Not applicable
b13*3 Sum check Not added Added
b14*3 Protocol Not used Used

b15*3 Control procedure Format 1 Format 4

*1. This setting is available only in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.
*2. When using the RS-485/RS-422 interface, only FX0N, FX1S, FX1N, FX1NC, FX2N, FX2NC, FX3S, FX3G,
FX3GC, FX3U and FX3UC PLCs are applicable.
*3. Make sure to set as "0" when using non-protocol communication.

2. Cautions on use
In all PLCs except FX2(FX), FX2C and FX0N PLCs, the communication format can be set using
parameters.
Even if the communication format is changed while the RS instruction is being driven, it is not reflected.
When setting the communication format in FX0N PLCs, set the communication setting latched (battery
backed) device (M8120) to ON.

12.2.10 Remaining amount of data to be sent [D8122]


This device stores the amount of remaining send data.

1. Detailed contents
This device stores the amount of remaining send data in 8-bit (1 byte) units.
Only data in communication frames are regarded as targets of counting.

F-94
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.2 Details of related devices (RS instruction)

A
12.2.11 Amount of data already received [D8123]

Common Items
This device stores the amount of data already received.

1. Detailed contents.
This device stores the amount of data already received in 8-bit (1 byte) units.
B

N:N Network
12.2.12 Header [D8124]
This device sets the header.

1. Detailed contents
When "header provided" is selected in the communication format setting, the lowest-order byte of D8124 is C
used.

Parallel Link
When data is sent, the data in the lowest-order byte of D8124 is added at the head of the specified send data.
When data is received, receiving begins when the data in the lowest-order byte of D8124 is received.

12.2.13 Terminator [D8125]


D
This device sets the terminator.

Computer Link
1. Detailed contents
When "terminator provided" is selected in the communication format setting, the lowest-order byte of D8125
is used.
When data is sent, the lowest-order byte of D8125 is added at the end of the specified send data.
When data is received, receiving is completed when the data in the lowest-order byte of D8125 is received. E

Communication
Inverter
12.2.14 Time-out time setting time [D8129]
This device sets the time-out time setting.

1. Detailed contents F
This device sets the error evaluation time (in 10-ms units) used when receiving of data is interrupted.

(RS/RS2 Instruction)
Communication
Non-Protocol
The setting range is from 1 to 255 (10 ms to 2550 ms).
When "0" is set in D8129, the time-out time is set to 100 ms.

2. Cautions on use
In all PLCs except FX2(FX), FX2C and FX0N PLCs, the time-out time setting can be set using a parameter. G
Even if the time-out time setting is changed while the RS instruction is being driven, it is not reflected.

(FX2N-232IF)
Communication
Non-Protocol
After changing the setting, set the RS instruction to OFF and ON.
When setting the time-out time setting in FX0N PLCs, set the communication setting latched (battery
backed) device (M8120) to ON.

12.2.15 Communication parameter display [D8405] H


Communication
Programming

This device stores the communication parameters set in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

1. Detailed contents
When the PLC power is turned ON, D8405 stores the contents of the communication parameters.
The contents of the parameters are the same as those of the communication format setting device (D8120).
I
Maintenance
Remote

Apx.A
models
Discontinued

F-95
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.3 Related Devices (RS2 Instruction)

12.2.16 Operation mode display [D8419]


This device stores the communication type being used.

1. Detailed contents
This device stores the code of the communication type currently being used by the communication port.
The table below shows the contents of the codes.
Code Description
0 Programming communication
1 PP modem mode
2 Protocol dedicated to computer link
3 N:N Network
4 RS instruction
5 RS2 instruction
6 Parallel link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication
10 CF-ADP
11 ENET-ADP
12 Input/output expansion board is used.

2. Cautions on use
This device stores "4" while RS instruction is driven or when the RS instruction is not changed over to another
mode.

12.3 Related Devices (RS2 Instruction)


Available channels vary depending on the main unit.
For details, refer to Section 3.2.

1. Bit devices
Device
Name Description R/W
ch0 ch1 ch2
This device turns ON when a communication error occurs.
Serial
When this device (serial communication error) turns ON,
M8062 M8063 M8438 communication R
D8062, D8063 or D8438 stores the corresponding error
error
code.
M8371 M8401 M8421 Sending wait flag This device remains ON while the PLC is waiting to send. R
M8372 M8402 M8422 Sending request When this device is set to ON, the PLC starts to send. R/W
This device turns ON when receiving is completed.
Receiving complete
M8373 M8403 M8423 While this device (receiving complete flag) is ON, the PLC R/W
flag
cannot receive any receive data.
Carrier detection This device turns ON in synchronization with the CD (DCD)
M8404 M8424 R
flag signal.
Data set ready This device turns ON in synchronization with the DR (DSR)
M8405 M8425 R
(DSR) flag*1 signal.
This device turns ON when data receiving is suspended and
M8379 M8409 M8429 Time-out check flag the next set of receive data is not given within the time set by R/W
the time-out time setting device.
R: Read only
W: Write only
R/W: Read or Write
*1. FX3U, FX3UC PLCs Ver. 2.30 or later, and FX3S, FX3G, FX3GC PLCs is applicable.

F-96
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

A
2. Word devices

Common Items
Device
Name Description R/W
ch0 ch1 ch2
Serial
When the serial communication error flag turns ON, this device
D8062 D8063 D8438 communication error R
code
stores the corresponding error code.
B
Communication

N:N Network
D8370 D8400 D8420 This device sets the communication format. R/W
format setting
Amount of
D8372 D8402 D8422 This device stores the amount of remaining send data. R
remaining send data
Amount of data
D8373 D8403 D8423
already received
This device stores the amount of data already received. R
C
Communication

Parallel Link
D8405 D8425 This device stores communication parameters set in the PLC. R
parameter display
Time-out time
D8379 D8409 D8429 This device sets the timeout time. R/W
setting
Header 1 and
D8380 D8410 D8430 R/W
header 2
These devices set the headers 1 to 4. D
Header 3 and

Computer Link
D8381 D8411 D8431 R/W
header 4
Terminator 1 and
D8382 D8412 D8432 R/W
terminator 2
These devices set the terminators 1 to 4.
Terminator 3 and
D8383 D8413 D8433 R/W
terminator 4
E
Receiving sum
D8384 D8414 D8434 This device stores the received sum check value. R

Communication
Inverter
(receive data)
Receiving sum This device stores the sum check value calculated from the
D8385 D8415 D8435 R
(calculation result) received data.
This device stores the sum check value added to the send
D8386 D8416 D8436 Sending sum R

Operation mode
data.
F
D8389 D8419 D8439 This device stores the communication type being used. R

(RS/RS2 Instruction)
Communication
Non-Protocol
display
R: Read only
W: Write only
R/W: Read or Write
G
12.4 Details of Related Devices (RS2 Instruction)

(FX2N-232IF)
Communication
Non-Protocol
Available channels vary depending on the main unit.
For details, refer to Section 3.2.

12.4.1 Serial communication error [M8062, M8063 and M8438] H


Communication
Programming

These devices turn ON when an error occurs during serial communication.

1. Detailed contents
These devices work as serial communication error flags.
M8062 turns ON when an error occurs in serial communication using communication port ch0.
M8063 turns ON when an error occurs in serial communication using communication port ch1. I
M8438 turns ON when an error occurs in serial communication using communication port ch2.
Maintenance
Remote

When M8063 turns ON, a corresponding error code is stored in D8063.


When M8438 turns ON, a corresponding error code is stored in D8438.

2. Cautions on use
Serial communication errors are not cleared even when communication is restored.
Cleared when the power is turned off and on.
Apx.A
models
Discontinued

F-97
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

12.4.2 Sending wait flag [M8371, M8401 and M8421]


These devices remain ON while the PLC is waiting to send.

1. Detailed contents
M8371 remains ON while the PLC is waiting to send in communication using communication port ch0.
M8401 remains ON while the PLC is waiting to send in communication using communication port ch1.
M8421 remains ON while the PLC is waiting to send in communication using communication port ch2.
In full-duplex communication
While the control line is set to the standard or interlink mode in the communication parameter, when the
control line DR (DSR) turns OFF while sending data, the PLC waits to send and M8401 or M8421 turns
ON.
In half-duplex communication
When the sending request device is set to ON while data is being received, the PLC waits to send and
M8401 or M8421 turns ON.

12.4.3 Sending request [M8372, M8402 and M8422]


When these devices are set to ON by SET instruction, the PLC starts to send.

1. Detailed contents
When these devices are set to ON by SET instruction, the PLC starts to send. When sending is completed,
these devices are automatically set to OFF.
When communication port ch0 is used, M8372 is set.
When communication port ch1 is used, M8402 is set.
When communication port ch2 is used, M8422 is set.

2. Cautions on use
When setting these devices to ON, set the drive condition in the pulse type.

12.4.4 Receiving complete flag [M8373, M8403 and M8423]


These devices turn ON when receiving is completed.

1. Detailed contents
These devices turn ON when receiving is completed.
When communication port ch0 is used, M8373 is set.
When communication port ch1 is used, M8403 is set.
When communication port ch2 is used, M8423 is set.
Receiving is completed in one of the following three conditions.
When the PLC receives the amount of receive data specified by the RS2 instruction
When the terminators are set, and the PLC receives the code set by the terminator
When data receiving is suspended and the PLC does not receive the next set of data within the time set by
the time-out time setting device

When the receiving complete flag turns ON, transfer the received data to another storage destination, and
then set this flag to OFF.
When this flag is set to OFF, the PLC waits to receive.

2. Cautions on use
When the RS2 instruction is driven while the amount of received data is set to "0", the PLC does not wait to
receive. To make the PLC wait to receive it is necessary to set the amount of received data "n" to "1" or more
and set the receiving complete flag to OFF from ON.

F-98
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

A
12.4.5 Carrier detection flag [M8404 and M8424]

Common Items
These devices turn ON/OFF in synchronization with the CD (DCD) signal.

1. Detailed contents
The CD (DCD) signal (channel receiving carrier detection) turns ON when the modem line is established.
When communication port ch1 is used, M8404 turns ON/OFF.
B

N:N Network
When communication port ch2 is used, M8424 turns ON/OFF.
While the carrier detection flag is OFF, the dial number can be sent.
While the carrier detection flag is ON, data can be sent and received.

12.4.6 Data set ready (DSR) flag [M8405 and M8425]


C
These devices turn ON/OFF in synchronization with the DR (DSR) signal.

Parallel Link
1. Detailed contents
The state of DR (DSR) signal can be checked when executing RS2 instruction.
When communicating port ch1 is used, M8405 turns ON/OFF.
When communication port ch2 is used, M8425 turns ON/OFF.
The images of M8405 and M8425 are updated during END processing.
D

Computer Link
12.4.7 Time-out check flag [M8379, M8409 and M8429]
These devices turn ON when data receiving is suspended, and the next set of receive data is not given within
the time set by the time-out time setting device.
E
1. Detailed contents

Communication
Inverter
These devices turn ON when data receiving is suspended and the next set of receive data is not given within
the time set by the time-out time setting device. The receiving complete flag also turns ON.
When communication port ch0 is used, M8379 turns ON.
When communication port ch1 is used, M8409 turns ON.
When communication port ch2 is used, M8429 turns ON. F
The time-out check flag turns OFF when the PLC waits to receive.

(RS/RS2 Instruction)
Communication
Non-Protocol
Using this function, the PLC can receive data from equipment where the amount of send data varies without
the terminators.
Receive data is
Receiving suspended.
Data
Set to OFF in sequence program.
G
D8409

(FX2N-232IF)
Communication
Non-Protocol
Time-out check flag 10 ms
M8409 ON
Receiving complete
M8403 ON

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-99
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

12.4.8 Serial communication error code [D8062, D8063 and D8438]


When a serial communication error occurs, these devices store the corresponding error codes.

1. Detailed contents
When a serial communication error occurs, these devices store the corresponding error codes shown below.
When communication port ch0 is used, M8062 turns ON.
When communication port ch1 is used, M8063 turns ON.
When communication port ch2 is used, M8438 turns ON.
Error code
Contents of error
ch0 (D8062) ch1 (D8063) ch2 (D8438)
6201 6301 3801 Parity error, overrun error or framing error
6202 6302 3802 Incorrect communication character
6203 6303 3803 Communication data sum mismatch
6204 6304 3804 Incorrect data format
6205 6305 3805 Incorrect command
6206 6306 3806 Monitoring timeout
6307 3807 Modem initialization error
6308 3808 N:N Network parameter error
6309 3809 N:N Network setting error
6312 3812 Parallel link parameter error
6313 3813 Parallel link sum error
6314 3814 Parallel link format error
6320 3820 Inverter communication error
6321 3821 MODBUS communication error
6330 3830 Memory access error
6340 3840 Special adapter connection error

2. Cautions on use
Serial communication error codes are not cleared even when communication is restored.
Cleared when the power is turned off and on.

F-100
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

A
12.4.9 Communication format setting [D8370, D8400 and D8420]

Common Items
These devices set the communication format.

1. Detailed contents
These devices can set the data length, parity, baud rate, etc.
When communication port ch0 is used, D8370 sets the communication format.
B

N:N Network
When communication port ch1 is used, D8400 sets the communication format.
When communication port ch2 is used, D8420 sets the communication format.
The table below shows the contents of the communication format settings. Computer link setting is not
applicable for D8370, D8400.
Contents
Bit No. Name
0 (bit = OFF) 1 (bit = ON)
C

Parallel Link
b0 Data length 7-bit 8-bit
b2, b1
b1 (0, 0): Not provided
Parity
b2 (0, 1): Odd
(1, 1): Even
b3 Stop bit 1-bit 2-bit
D

Computer Link
b7, b6, b5, b4 b7, b6, b5, b4
b4
(0, 0, 1, 1): 300 (0, 1, 1, 1): 4800
b5 Baud rate
(0, 1, 0, 0): 600 (1, 0, 0, 0): 9600
b6 (bps)
(0, 1, 0, 1): 1200 (1, 0, 0, 1): 19200
b7
(0, 1, 1, 0): 2400 (1, 0, 1, 0): 38400
b8*1 Header Not provided Provided*2
E

Communication
Inverter
b9*1 Terminator Not provided Provided*2
b12, b11, b10
(0, 0, 0): Not provided <RS-232C interface>
Non-protocol (0, 0, 1): Standard mode <RS-232C interface>

b10
(0, 1, 0): Interlink mode <RS-232C interface>
communication*3 (0, 1, 1): Modem mode <RS-232C interface> F
b11 Control line (1, 1, 1): Communication in accordance with RS-485

(RS/RS2 Instruction)
Communication
Non-Protocol
b12 <RS-485/RS-422 interface>
b12, b11, b10
Computer link (0, 0, 0): RS-485/RS-422 interface
(0, 1, 0): RS-232C interface
b13 Sum check Not added Added*4 G

(FX2N-232IF)
Communication
Non-Protocol
b14*5 Protocol Not used Used
Non-protocol CR, LF: Not used Non-protocol CR, LF: Used
Control communication (Format 1) communication (Format 2)
b15 procedure
(CR, LF) CR, LF: Not used CR, LF: Used
Computer link Computer link
(Format 1) (Format 4)
H
*1. Make sure to set as "0" when using computer link.
Communication
Programming

*2. In RS2 instruction, up to four headers and up to four terminators can be set.
*3. The control line is not available in FX3G, FX3GC PLCs when ch0 is used. Set "(1, 1, 1)".
*4. When executing non-protocol communication using RS2 instruction, add the sum check after the
terminators.
Make sure to set the terminators when adding the sum check.
I
Maintenance
Remote

*5. Make sure to set as "0" when using non-protocol communication.

2. Cautions on use
In FX3S, FX3U and FX3UC PLCs, the communication format can be set using parameters.
Even if the communication format is changed while the RS2 instruction is being driven, it is not reflected. Apx.A
models
Discontinued

In FX3G and FX3GC PLCs, the communication format can be set only for ch1 and ch2 using parameters.

F-101
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

12.4.10 Amount of remaining send data [D8372, D8402 and D8422]


These devices store the amount of remaining send data.

1. Detailed contents
These devices store the amount of remaining send data in 8-bit (1 byte) units.
When communication port ch0 is used, D8372 stores the value.
When communication port ch1 is used, D8402 stores the value.
When communication port ch2 is used, D8422 stores the value.
Only data in communication frames are regarded as the targets of counting.

12.4.11 Amount of data already received [D8373, D8403 and D8423]


These devices store the amount of data already received.

1. Detailed contents.
These devices stores the amount of data already received in 8-bit (1 byte) units.
When communication port ch0 is used, D8373 stores the value.
When communication port ch1 is used, D8403 stores the value.
When communication port ch2 is used, D8423 stores the value.

12.4.12 Communication parameter display [D8405 and D8425]


These devices store the communication parameters set in the PLC.

1. Detailed contents
When the PLC power is turned ON, these devices store the contents of the communication parameters.
The setting contents are the same as those of the communication format setting device.
When communication port ch1 is used, D8405 stores the contents.
When communication port ch2 is used, D8425 stores the contents.

12.4.13 Time-out time setting [D8379, D8409 and D8429]


These devices set the time-out time setting.

1. Detailed contents
These devices set the error evaluation time (in 10 ms units) used when receiving of data is interrupted.
When communication port ch0 is used, D8379 sets the time.
When communication port ch1 is used, D8409 sets the time.
When communication port ch2 is used, D8429 stores the time.
Setting range for ch0 and ch2: 1 to 3,276 (10 to 32,760 ms)
Setting range for ch1: 1 to 255 (10 to 2,550 ms)
When "0" is set in these devices, the time-out time is set to 100 ms.

2. Cautions on use
Even if the time-out time setting is changed while the RS2 instruction is being driven, it is not reflected.
After changing the setting, set the RS2 instruction to OFF and ON.

F-102
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

A
12.4.14 Header [D8380, D8381, D8410, D8411, D8430 and D8431]

Common Items
These devices set the headers 1, 2, 3 and 4.

1. Detailed contents
When "header provided" is selected in the communication format setting, the headers are set in the sent and
received data.
B

N:N Network
Up to four headers can be set in each channel.
When communication port ch0 is used, D8380 and D8381 set the headers.
When communication port ch1 is used, D8410 and D8411 set the headers.
When communication port ch2 is used, D8430 and D8431 set the headers.
The headers are set in the following order.
Header Header 1 Header 2 Header 3 Header 4 C

Parallel Link
ch0 D8380 (lowest-order byte) D8380 (highest-order byte) D8381 (lowest-order byte) D8381 (highest-order byte)
ch1 D8410 (lowest-order byte) D8410 (highest-order byte) D8411 (lowest-order byte) D8411 (highest-order byte)
ch2 D8430 (lowest-order byte) D8430 (highest-order byte D8431 (lowest-order byte) D8431 (highest-order byte)
When data is sent, the data set in the headers is added at Header
the head of the specified send data.
1 2 3 4 Data
D
When data is received, receiving begins when the data set

Computer Link
in the headers is received.

2. Cautions on use
Even if "header provided" is selected, headers are not provided if header 1 is set to "H00".
The area before "H00" (in 1-byte units) is used to set the headers.
E

Communication
Inverter
12.4.15 Terminator [D8382, D8383, D8412, D8413, D8432 and D8433]
These devices set the terminators 1, 2, 3 and 4.

1. Detailed contents
When "terminator provided" is selected in the communication format setting, the terminators are set in the F
sent and received data.

(RS/RS2 Instruction)
Communication
Non-Protocol
Up to four terminators can be set in each channel.
When communication port ch0 is used, D8382 and D8383 set the terminators.
When communication port ch1 is used, D8412 and D8413 set the terminators.
When communication port ch2 is used, D8432 and D8433 set the terminators.
The terminators are set in the following order.
G
Terminator Terminator 1 Terminator 2 Terminator 3 Terminator 4

(FX2N-232IF)
Communication
Non-Protocol
ch0 D8382 (lowest-order byte) D8382(highest-order byte) D8383 (lowest-order byte) D8383 (highest-order byte)
ch1 D8412 (lowest-order byte) D8412(highest-order byte) D8413 (lowest-order byte) D8413 (highest-order byte)
ch2 D8432 (lowest-order byte) D8432 (highest-order byte) D8433 (lowest-order byte) D8433 (highest-order byte)
When data is sent, the data set in the terminators is added
at the end of the specified send data.
Terminator H
Data 1 2 3 4
Communication
Programming

When data is received, receiving is completed when the


data set in the terminators is received.

2. Cautions on use
Even if "terminator provided" is selected, terminators are not provided if terminator 1 is set to "H00".
The area before "H00" (in 1-byte units) is used to set the terminators. I
Maintenance
Remote

Apx.A
models
Discontinued

F-103
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

12.4.16 Receiving sum (receive data) [D8384, D8414 and D8434]


These devices store the received sum check value.

1. Detailed contents
When "sum check provided" is selected in the communication format setting, the sum check is executed for
the sent and received data.
These devices store the sum added to the received data sent from the external equipment.
When communication port ch0 is used, D8384 stores the receiving sum.
When communication port ch1 is used, D8414 stores the receiving sum.
When communication port ch2 is used, D8434 stores the receiving sum.

2. Cautions on use
When selecting "sum check provided", make sure to also select "terminator provided".

12.4.17 Receiving sum (calculation result) [D8385, D8415 and D8435]


These devices store the sum check value calculated using the received data.

1. Detailed contents
When "sum check provided" is selected in the communication format settings, the sum check is executed for
the sent and received data.
These devices store the sum calculated by the FX PLC from the data received sent from the external
equipment.
When communication port ch0 is used, D8385 stores the receiving sum.
When communication port ch1 is used, D8415 stores the receiving sum.
When communication port ch2 is used, D8435 stores the receiving sum.

2. Cautions on use
When selecting "sum check provided", make sure to also select "terminator provided".

12.4.18 Sending sum [D8386, D8416 and D8436]


These devices store the sum check value added to the send data.

1. Detailed contents
When "sum check provided" is selected in the communication format settings, the sum check is executed for
the sent and received data.
These devices store the sum calculated from the send data.
When communication port ch0 is used, D8386 stores the sending sum.
When communication port ch1 is used, D8416 stores the sending sum.
When communication port ch2 is used, D8436 stores the sending sum.

2. Cautions on use
When selecting "sum check provided", make sure to select "terminator provided".

F-104
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.4 Details of Related Devices (RS2 Instruction)

A
12.4.19 Operation mode display [D8389, D8419 and D8439]

Common Items
These devices store the communication type being used.

1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
When communication port ch0 is used, D8389 stores the communication type.
B

N:N Network
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.

The table below shows the contents of the communication type codes.
Code Description
0 Programming communication
C

Parallel Link
1 PP modem mode
2 Protocol dedicated to computer link
3 N:N Network
4 RS instruction
5 RS2 instruction D

Computer Link
6 Parallel link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication
10 CF-ADP E
11 ENET-ADP

Communication
Inverter
12 Input/output expansion board is used.

2. Cautions on use
These devices store "5" while RS2 instruction is being driven or when RS2 instruction is not changed over to
another mode. F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

F-105
FX Series PLC User's Manual - Data Communication Edition 12 Related Data
Non-Protocol Communication (RS/RS2 Instruction) 12.5 ASCII Code Table

12.5 ASCII Code Table


<ASCII code table (8-bit code expressed in hexadecimal)>
The ASCII codes A1H to DFH indicate Japanese characters.

*1. \ (ASCII CODE:5C) symbol is displayed as " " in Japanese.

F-106
FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (FX2N-232IF)

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
G. Non-Protocol Communication (FX2N-232IF)
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
This manual explains "non protocol communication" provided for the MELSEC-F FX Series Programmable I
Controllers using the FX2N-232IF and should be read and understood before attempting to install or use the
Maintenance
Remote

unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

G-1
FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (FX2N-232IF)

G-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (FX2N-232IF) 1.1 Features

Common Items
1. Outline
The communication special function block operating in accordance with RS-232C, FX2N-232IF (hereafter B
referred to as "232IF"), is connected to an FX2N, FX3U, FX2NC, or FX3UC PLC to exchange serial data in the

N:N Network
full-duplex method between equipment with RS-232C interfaces such as a personal computer, bar code
reader or printer.
For the contents of the hardware, refer to the "FX2N-232IF Hardware Manual".

1.1 Features C

Parallel Link
1. Two or more 232IF (operating in accordance with RS-232C) blocks can be connected.
Two or more RS-232C interface blocks can be connected to an FX PLC.
1) For FX2N, FX3U and FX3UC*1 PLCs
Up to eight blocks can be connected to one PLC. D

Computer Link
*1. Up to seven blocks can be connected to the FX3UC-32MT-LT(-2) PLC.
2) For FX2NC PLCs
Up to four blocks can be connected to one PLC.
2. Non-protocol communication
Communication is executed in the full-duplex, asynchronous system, non-protocol method. The communication E
format can be specified using the buffer memory (BFM).

Communication
Inverter
The FROM and TO instructions are applicable for the buffer memory.
(In FX3U and FX3UC PLCs, other instructions are also applicable.)
3. Send/receive data buffer of 512 bytes/256 words
The send data buffer and receive data buffer can store 512 bytes/256 words independently.
In the RS-232C interlink connection mode, the 232IF can receive data beyond 512 bytes/256 words. F

(RS/RS2 Instruction)
Communication
Non-Protocol
4. Built-in ASCII-Hexadecimal conversion function
By using this built-in conversion function, hexadecimal numeric values (0 to F) inside the send data buffer can
be converted into ASCII code when being sent, and received ASCII code can be converted into hexadecimal
values (0 to F) when being stored in the receive data buffer.

System Important points and reference


chapter/section
G

(FX2N-232IF)
Communication
Non-Protocol
FX PLC FX2N-232IF FX2N-232IF

To check connectable PLC models,


refer to Chapter 1.
H
Communication
Programming

For selection, refer to Chapter 3.

Printer

I
Maintenance
Remote

For wiring, refer to Chapter 4.

Bar code reader Apx.A


models
Discontinued

G-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (FX2N-232IF) 1.2 Procedures Before Operation

1.2 Procedures Before Operation


The flow chart below shows the Non-Protocol Communication (operating in accordance with 232IF) setting
procedures up until data link:

Non-Protocol Communication(232IF)

Refer to Chapter 1.

Outline Outline of system


Available PLC versions
Available programming tools
Refer to Chapter 2.

Check communication specifications Communication specifications

Refer to Chapter 3.

Determine system configuration and selection System configuration

Refer to Chapter 4.

Perform wiring Wiring procedure


Wiring example
Programming tool

Connect PLC*1

Refer to Chapter 5.

Create programs FROM/TO instruction


Buffer memory list
Control line operation

Based on SD/RD lamp lighting status and


contents of error check devices, verify that
communication is being executed normally.
If there are problems, refer to the troubleshooting
(Chapter 7).

Refer to Chapter 6.
ASCII code sending and receiving examples are
Practical program examples
described.

*1 For the programming tool to PLC connection procedure, refer to the "Programming Communication" section in this
manual or the respective programming tool manual.
For details on operating procedures, refer to the respective programming tool manual.

G-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (FX2N-232IF) 1.3 Communication Type Applicability in PLC

A
1.3 Communication Type Applicability in PLC

Common Items
1.3.1 Applicable versions
The communication types are applicable in the following versions. B

N:N Network
: Applicable (If applicable versions of main units are limited, they are described inside ( ).)
:Not applicable
PLC Applicability Remarks
FX3UC Series
FX3U Series C

Parallel Link
FX3GC Series 232IF is not connectable.
FX3G Series 232IF is not connectable.
FX3S Series 232IF is not connectable.
FX2NC Series
FX2N Series D
FX1NC Series 232IF is not connectable.

Computer Link
FX1N Series 232IF is not connectable.
FX1S Series 232IF is not connectable.
FX0N Series 232IF is not connectable.
FX0S Series 232IF is not connectable. E
FX0 Series 232IF is not connectable.

Communication
Inverter
FX2C Series 232IF is not connectable.
FX2(FX) Series 232IF is not connectable.
FX1 Series 232IF is not connectable.

(RS/RS2 Instruction)
Communication
Non-Protocol
1.3.2 Products whose production was stopped
Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A.
To see the latest available products, refer to the general catalog.
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (FX2N-232IF) 1.4 Programming Tool Applicability

1.4 Programming Tool Applicability

1.4.1 For applicable versions


The programming tool is applicable for each FX Series from the version shown:

1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 3.00 or later
FX-20P-MFXC-E
FX-10P-E Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

G-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Non-Protocol Communication (FX2N-232IF) 1.4 Programming Tool Applicability

A
2. Japanese versions

Common Items
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later - B
FX-30P Ver. 1.00 or later

N:N Network
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
C
GX Developer SWD5C(F)-GPPW-J SW2 A or later

Parallel Link
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.00 or later
FX-PCS-KIT/98 SW1PC-FXGP/98(-3,-5) Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 4.00 or later
-
FX-PCS-KIT/V-3
FX-A7PHP-KIT
SW1PC-FXGP/V3
SW1RX-GPPFX
Ver. 2.00 or later
Ver. 3.00 or later
D

Computer Link
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 4.00 or later
FX-20P-MFXC
FX-10P(-SET0) Ver. 3.00 or later
GOT-F900 Series display units E
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)

Communication
Inverter
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. F

(RS/RS2 Instruction)
Communication
Non-Protocol
1.4.2 For non-applicable versions (setting an alternative model)
Even programming tool not applicable to a PLC can create programs when an alternative model is set.
In this case, however, programming is enabled only in the ranges provided for the alternative PLC model
such as instructions and program size. G

(FX2N-232IF)
Communication
Non-Protocol
Model to be
Model to be set Priority: High Low
programmed
FX3UC Series FX3UC FX2N FX2(FX)
FX3U Series FX3U, FX3UC FX2N FX2(FX)
FX2NC Series FX2NC, FX2N FX2(FX) H
FX2N Series FX2N FX2(FX)
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-7
FX Series PLC User's Manual - Data Communication Edition 2 Specification
Non-Protocol Communication (FX2N-232IF) 2.1 Communication Specifications

2. Specification
This chapter explains the communication specifications.

2.1 Communication Specifications


Non-protocol communication type is used in the communication specifications shown in the table below.
Item Specifications Remarks
Transmission standard RS-232C standard
Maximum total extension distance 15 m (49' 2")
Protocol type Non-protocol communication
Communication method Full-duplex, asynchronous system
Baud rate 300/600/1200/2400/4800/9600/19200 bps
Start bit
Character Data bit 7-bit/8-bit
format Parity bit None, odd or even
Stop bit 1-bit/2-bit
Header Provided or not provided Up to four bytes can be
Terminator Provided or not provided specified.
Control line Provided or not provided
Sum check Provided or not provided

G-8
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (FX2N-232IF) 3.1 System Configuration

Common Items
3. System Configuration and Selection
This chapter explains the system configuration and selection of the FX PLC and 232IF. B

N:N Network
3.1 System Configuration
This section outlines the system configuration required to use the 232IF.
1 and 2 indicate the communication equipment combination patterns.
C
Total extension

Parallel Link
FX PLC FX2N-232IF Important point in selection distance

1
+ 15 m
POW
ER

Attach the 232IF to the right side of


SD
RD

the main unit. (49' 2")


FX2N Series
D

Computer Link
FX3U Series

2 Attach the connector conversion


interface to the right side of the main 15 m
POW
ER

+ +
SD
RD

unit, and then attach the 232IF to the


right side of the connector conversion
(49' 2") E
interface.

Communication
Inverter
FX2NC Series Connector
FX3UC Series conversion
interface

(RS/RS2 Instruction)
Communication
Non-Protocol
For communication equipment combinations for each FX Series, refer to the next section.

3.2 Applicable FX PLC and Communication Equipment


G
Select a 232IF combination, and put a check mark in the "Check" column.

(FX2N-232IF)
Communication
Non-Protocol
During selection, pay attention to the following:
The capacity of the 5V DC power supplied from the PLC is limited. The current consumption at 5V DC of
the 232IF is 40 mA. Make sure that total current consumption at 5V DC including other blocks does not
exceed the specified value.

FX Series Communication equipment (option) Total extension


Check
H
distance
Communication
Programming

POW
ER
SD
RD

15 m
(49' 2")
I
FX2N FX2N-232IF
Maintenance
Remote

(9-pin D-Sub, male)

POW
ER

+
SD
RD

15 m
(49' 2")
Apx.A
models
Discontinued

FX2NC-CNV-IF FX2N-232IF
FX2NC (9-pin D-Sub, male)

G-9
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (FX2N-232IF) 3.3 Connection to PLC

Total extension
FX Series Communication equipment (option) distance
Check

POW
ER
SD
RD

15 m
(49' 2")

FX3U FX2N-232IF
(9-pin D-Sub, male)

POW
ER

+
SD
RD

15 m
(49' 2")

FX2NC-CNV-IF FX2N-232IF
(9-pin D-Sub, male)

POW
ER

+
SD

FX3UC
RD

15 m
(49' 2")

FX3UC-1PS-5V FX2N-232IF
(9-pin D-Sub, male)

3.3 Connection to PLC


The 232IF can be directly connected to an FX PLC main unit or to the right side of another function block or
powered extension unit.
The unit number is assigned to each special unit/block in the order "No. 0, No. 1, No. 2 ..." from the unit/block
nearest to the main unit. (for FX3UC-32MT-LT(-2) PLC, the unit number is assigned in the order "No. 1, No. 2,
No. 3 ...".)
Up to eight 232IF units can be connected to an FX2N/FX3U/FX3UC*1 PLC, up to four 232IF units can be
connected to an FX2NC PLC.
*1. Up to seven 232IF units can be connected to an FX3UC-32MT-LT(-2) PLC.

1. For FX2N PLC

POW
ER POW
ER
SD SD
RD RD

FX2N-48MR FX2N-232IF FX2N-16EX FX2N-232IF


X000 to X027 Special block X030 to Special block
Y000 to Y027 No.0 X047 No.1

G-10
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Non-Protocol Communication (FX2N-232IF) 3.3 Connection to PLC

A
2. For FX3U PLC

Common Items
POW
ER POW
ER
SD SD
RD RD

N:N Network
FX3U-48MR/ES FX2N-232IF FX2N-16EX FX2N-232IF
X000 to X027 Special block X030 to Special block
Y000 to Y027 No.0 X047 No.1
C
3. For FX2NC PLC

Parallel Link
FX2NC-CNV-IF
Connector conversion interface

POW
ER
SD
POW
ER
SD
D

Computer Link
RD RD

FX2NC-16MT FX2N-232IF FX2N-16EX FX2N-232IF E


X000 to X007 Special block X010 to Special block

Communication
Inverter
Y000 to Y007 No.0 X027 No.1

4. For FX3UC(D, DS, DSS) PLC


FX2NC-CNV-IF
Connector conversion interface F

(RS/RS2 Instruction)
Communication
Non-Protocol
POW
ER POW
ER

SD SD
RD RD

(FX2N-232IF)
Communication
Non-Protocol
FX3UC-32MT/D FX2N-232IF FX2N-16EX FX2N-232IF
X000 to X017 Special block X020 to Special block
Y000 to Y017 No.0 X037 No.1

5. For FX3UC-32MT-LT(-2) PLC


H
Communication
Programming

FX2NC-CNV-IF
Connector conversion interface

I
POW
ER POW
ER

SD SD
RD RD
Maintenance
Remote

FX3UC-32MT-LT FX2N-232IF FX2N-16EX FX2N-232IF


X000 to X017 Special block X020 to Special block Apx.A
Y000 to Y017 No.1 X037 No.2
models
Discontinued

G-11
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (FX2N-232IF) 4.1 Pin Arrangement

4. Wiring
This chapter explains the wiring.

4.1 Pin Arrangement


The table below shows the pin arrangement of the 232IF.
Example of applicable connector: 17JE-13090-02 (D8C2) by DDK Ltd.

Signal Signal direction 232IF:


Pin No. Function
Pin name External equipment
1 CD(DCD) Carrier detection
5
9 Receive data
4 2 RD(RXD)
8 (with LED indicator)
3
7 Send data
2 3 SD(TXD)
6 (with LED indicator)
1 4 ER(DTR) Data terminal ready
5 SG(GND) Signal ground
6 DR(DSR) Data set ready
#4-40UNC
inch screw Sending request
7 RS(RTS)
(receiving enable)*1
8 CS(CTS) Sending enable
9 CI(RI) Calling indicator
*1.The signal inside ( ) is adopted in the interlink connection mode.

4.2 Connection to External Equipment with Terminal Specifications


(without Control Line)
BFM # 0 (communication format): b9 = 0, b8 = 0 (control line not provided)
PLC side RS-232C external equipment side

Name FX2N-232IF Name 9-pin D-Sub 25-pin D-Sub


SD(TXD) 3 SD(TXD) 3 2
RD(RXD) 2 RD(RXD) 2 3
SG(GND) 5 SG(GND) 5 7

G-12
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Non-Protocol Communication (FX2N-232IF) 4.3 Connection to External Equipment with Terminal Specifications (with Control Line)

A
4.3 Connection to External Equipment with Terminal Specifications

Common Items
(with Control Line)

4.3.1 Standard RS-232C mode


B
Cross cable, BFM #0 (communication format): b9 = 0, b8 = 1 (standard RS-232C mode)

N:N Network
PLC side RS-232C external equipment side When the FX2N-232IF receives the RS (request
to send) signal at its carrier to send (CS) pin, the
Name FX2N-232IF Name 9-pin D-Sub 25-pin D-Sub
FX2N-232IF transfers signals as if the external
SD(TXD) 3 SD(TXD) 3 2
RD(RXD) 2 RD(RXD) 2 3
equipment exists.
*1. It is not necessary to connect the CD signal if
C

Parallel Link
RS(RTS) 7 RS(RTS) 7 4 monitoring the CD signal is not required.
For the CD signal, the 232IF indicates only the
CS(CTS) 8 CS(CTS) 8 5
status.
CD(DCD) 1 *1 *1 CD(DCD) 1 8 *2. The 232IF indicates only the status.
ER(DTR) 4 ER(DTR) 4 20
DR(DSR) 6
*2 *2
DR(DSR) 6 6 D

Computer Link
SG(GND) 5 SG(GND) 5 7

4.3.2 Interlink connection mode


Interlink serial cross cable, BFM #0 (communication format): b9 = 1, b8 = 1 (RS-232C interlink connection mode) E

Communication
Inverter
PLC side RS-232C external equipment side In the interlink connection mode, the 232IF can
receive data larger than 512 bytes which is the
Name FX2N-232IF Name 9-pin D-Sub 25-pin D-Sub
upper limit of the received data buffer in the
SD(TXD) 3 SD(TXD) 3 2 232IF.
RD(RXD) 2 RD(RXD) 2 3 *1. In this mode, the request to send (RS) signal works
RS(RTS) 7 RS(RTS) 7 4 as the receiving enable signal for the 232IF.
When the 232IF receives data beyond the
F
*1 *1

(RS/RS2 Instruction)
Communication
Non-Protocol
CS(CTS) 8 CS(CTS) 8 5 maximum number of receivable bytes, it turns OFF
ER(DTR) 4 ER(DTR) 4 20 which works as the receive ready signal (RS signal)
*2 *2 to ask the external equipment to stop sending. At
DR(DSR) 6 DR(DSR) 6 6
this time, by withdrawing the data located in the
SG(GND) 5 SG(GND) 5 7 received data buffer using a sequence program,
the 232IF can receive remaining data.
*2. The 232IF indicates only the status.
G

(FX2N-232IF)
Communication
Non-Protocol
4.4 Connection to External Equipment with Modem Specifications
Straight cable, BFM #0 (communication format): b9 = 0, b8 = 1 (standard RS-232C mode) H
Communication
Programming

PLC side RS-232C external equipment side *1. It is not necessary to connect the CD signal if
monitoring the CD signal is not required.
Name FX2N-232IF Name 9-pin D-Sub 25-pin D-Sub For the CD signal, the 232IF indicates only the
SD(TXD) 3 SD(TXD) 3 2 status.
RD(RXD) 2 RD(RXD) 2 3 *2. The 232IF indicates only the status.
RS(RTS) 7 RS(RTS) 7 4 *3. It is not necessary to connect the CI signal if I
monitoring of the CI signal is not required. For the
8 8 5
Maintenance
Remote

CS(CTS) CS(CTS)
CI signal, the 232IF indicates only the status.
*1 *1
CD(DCD) 1 CD(DCD) 1 8
ER(DTR) 4 ER(DTR) 4 20
*2 *2
DR(DSR) 6 DR(DSR) 6 6
SG(GND) 5
*3 *3
SG(GND) 5 7 Apx.A
CI(RI) 9 CI(RI) 9 22
models
Discontinued

G-13
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.1 Outline of Communication between FX PLC and 232IF

5. Creating Programs
This chapter explains how to create programs for non-protocol communication type using the 232IF.

5.1 Outline of Communication between FX PLC and 232IF


An FX PLC and 232IF transfer data between each other through the buffer memory (BFM).

5.1.1 For FROM and TO instructions

FX2N/FX3U/FX2NC/FX3UC PLC FX2N - 232IF Communication equipment

Device memory Buffer memory

TO instruction Communication
format Printer
Data register Sending command
D**** Error reset

TO instruction
Internal relay Send data
M****

FROM instruction Receiving completed


status
Bar code reader

FROM instruction
Receive data

5.1.2 For direct specification of buffer memory (U\G)


FX3U and FX3UC PLCs allow not only FROM and TO instructions but also direct specification of the buffer
memory (U\G) using the MOV instruction, etc.
FX3U/FX3UC PLC FX2N - 232IF Communication equipment

Device Buffer memory

Arbitrary applied Communication


instruction format Printer
Sending command
Error reset
Direct specification
of buffer memory Arbitrary applied
instruction
Send data
U \G
Arbitrary applied
instruction Receiving completed
status
Bar code reader

Arbitrary applied
instruction
Receive data

G-14
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.2 FROM and TO Instructions

A
5.2 FROM and TO Instructions

Common Items
This section explains how to use FROM and TO instructions.

5.2.1 FROM instruction


B
FROM instruction reads data of the buffer memory in a special block.

N:N Network
1. Applicable devices
For FX2N /FX2NC PLCs
Bit Devices Word Devices Others
Operand
Type
System User Digit Specification System User Index Constant Pointer C
X Y M T C S KnX KnY KnM KnS T C D V Z Modify K H P

Parallel Link
m1
m2

D
n D

Computer Link
For FX3U/FX3UC PLCs
Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System User Digit Specification System User Index Pointer
Unit stant Number ter String
Type

m1
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V

Z Modify K H

E "" P
E

Communication
Inverter
m2

D
n

2. Function and operation F


1) 16-bit operation (FROM and FROMP)

(RS/RS2 Instruction)
Communication
Non-Protocol
Special function block (BFM) PLC (word device)
"n" 16-bit data starting from buffer memory (BFM) No. m2 inside the special function block No. m1 are
transferred (read) to "n" devices starting from D inside the PLC.
Command
FNC 78
FROM m1 m2 D n G

(FX2N-232IF)
Communication
Non-Protocol
Number of transfer points
n = 1 to 32767
Transfer destination (PLC)
Transfer source BFM #
(Special extension unit/block)
m2 = 0 to 32766
Unit No.
H
Communication
Programming

m1 = 0 to 7

2) 32-bit operation (DFROM and DFROMP)


Special function block (BFM) PLC (word device)
"n" 32-bit data starting from buffer memory (BFM) No. m2 inside the special function block No. m1 are
transferred (read) to "n" devices starting from [ D +1, D ] inside the PLC.
Command
I
FNC 78
Maintenance
Remote

m1 m2 D n
DFROM
Number of transfer points
n = 1 to 16383
Transfer destination (PLC)
Transfer source BFM #
(Special extension unit/block) Apx.A
m2 = 0 to 32765
models
Discontinued

Unit No.
m1 = 0 to 7

G-15
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.2 FROM and TO Instructions

5.2.2 TO instruction
TO instruction writes data to the buffer memory in a special function block.

1. Applicable devices
For FX2N /FX2NC PLCs
Bit Devices Word Devices Others
Operand
System User Digit Specification System User Index Constant Pointer
Type
X Y M T C S KnX KnY KnM KnS T C D V Z Modify K H P
m1
m2

S
n

For FX3U/FX3UC PLCs


Bit Devices Word Devices Others
Oper-
Special Con- Real Charac-
and System User Digit Specification System User Index Pointer
Unit stant Number ter String
Type
X Y M T C S D.b KnX KnY KnM KnS T C D R U\G V Z Modify K H E "" P
m1
m2

S
n

2. Function and operation


1) 16-bit operation (TO and TOP)
PLC (word device) Special function block (BFM)
"n" 16-bit data starting from S inside the PLC are transferred (written) to "n" buffer memories starting
from buffer memory No. m2 inside the special function block No. m1.
Command
FNC 79 m1 m2 S n
TO
Number of transfer points
n = 1 to 32767
Transfer source (PLC)
BFM # Transfer destination
(Special extension unit/block)
m2 = 0 to 32766
Unit No.
m1 = 0 to 7

2) 32-bit operation (DTO and DTOP)


PLC (word device) Special function block (BFM)
"n" 32-bit data starting from [ S +1, S ] inside the PLC are transferred (written) to "n" buffer
memories starting from the buffer memory No. m2 inside the special function block No. m1.
Command
FNC 79 m1 m2 S n
DTO
Number of transfer points
n = 1 to 16383
Transfer source (PLC)
BFM # Transfer destination
(Special extension unit/block)
m2 = 0 to 32765
Unit No.
m1 = 0 to 7

G-16
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.3 Direct Specification of Buffer Memory (U\G)

A
5.3 Direct Specification of Buffer Memory (U\G)

Common Items
In FX3U and FX3UC PLCs, one is able to directly specify buffer memories and read/write data from/to the
specified buffer memories even with instructions other than the FROM and TO.
1. How to specify a buffer memory directly
When directly specifying a buffer memory, put the following setting directly into the source or destination of
B

N:N Network
the command.

U\G
Specifies the block number Specifies the buffer memory number

Example 1: When reading data from buffer memory No. 4 in special function block No. 1, and
C

Parallel Link
transferring it to D0
In the case of FROM instruction
M8000
FNC 78 K1 K4 D0 K1
FROM
D

Computer Link
In the case of direct
specification
M8000
FNC 12 U1\G4 D0
MOV

Example 2: When writing the numeric value K1 to buffer memory No. 1000 in special function block E
No. 1 (pulse operation type)

Communication
Inverter
In the case of TO instruction
M1
FNC 79 K1 K1000 K1 K1
TO P
F
In the case of direct

(RS/RS2 Instruction)
Communication
Non-Protocol
specification
M1
FNC 12 K1 U1\G1000
MOV P

Example 3: When multiplying the value stored in buffer memory No. 1000 in special function block
No. 1 by the numeric value "K2", and writing the multiplication result to buffer memories
G

(FX2N-232IF)
Communication
Non-Protocol
Nos. 2000 and 2001 in special function block No. 2
When using the FROM and TO instructions
M0
FNC 78 K1 K1000 D0 K1
FROM
H
FNC 22
Communication
Programming

D0 K2 D1
MUL

FNC 79 K2 K2000 D1 K1
D TO
I
Maintenance
Remote

In the case of direct specification


M0
FNC 22 U1\G1000 K2 U2\G2000
MUL
Apx.A
Caution
models
Discontinued

The FX3UC-32MT-LT(-2) PLC main unit has a built-in CC-Link/LT master. When using special function blocks,
set the block numbers. starting from "1".

G-17
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

5.4 Buffer Memory (BFM)


This section explains the contents of the buffer memory (BFM).

5.4.1 Buffer memory list

BFM
Name Setting range Initial value R/W
No.
#0 Communication format 0087H W
#1 Command 0 W
1 to 512
(when data length is 16-bit)
1 to 256
#2 Maximum number of receivable bytes 0 W
(when data length is 8-bit)
"0" is handled as "512" or
"256"
1 to 32767 ( 10 ms)
#3 Receiving timeout time "0" is handled as "no timeout 0 W
time".
#4 Sending header (lowest-order 2 bytes) 4 bytes maximum, 0 (no header)
W
#5 Sending header (highest-order 2 bytes) 0 suppression 0
#6 Sending terminator (lowest-order 2 bytes) 4 bytes maximum, 0 (no terminator)
W
#7 Sending terminator (highest-order 2 bytes) 0 suppression 0
#8 Receiving header (lowest-order 2 bytes) 4 bytes maximum, 0 (no header)
W
#9 Receiving header (highest-order 2 bytes) 0 suppression 0
#10 Receiving terminator (lowest-order 2 bytes) 4 bytes maximum, 0 (no terminator)
W
#11 Receiving terminator (highest-order 2 bytes) 0 suppression 0
Receiving suspension waiting time
#12 0 to 32767( 10 ms) 0 W
(in interlink connection mode)
0 to 512
(when data length is 16-bit)
#13 Amount of remaining send data 0 R
0 to 256
(when data length is 8-bit)
#14 Amount of received data buffers 0 to 256+15*1 0 R
#15 Sending sum result 0 R
#16 Receiving sum result 0 R
#20 Time from CS ON to sending start 0 to 32,767( 10 ms) 0 W
Time from actual sending completion to RS
#21 0 to 32,767( 10 ms) 0 W
OFF (complete flag ON)
#28 Status 0 R
#29 Error code 0 R
#30 Model code K7030 R
0 to 512
(when data length is 16-bit)
#1000 Number of bytes to be sent 0 W
0 to 256
(when data length is 8-bit)
#1001
to Send data buffer 0 W
#1256
0 to 512+30*1
(when data length is 16-bit)
#2000 Number of received bytes 0 R
0 to 256+15*1
(when data length is 8-bit)
#2001
to Receive data buffer 0 R
#2256

G-18
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

A
BFM

Common Items
Name Setting range Initial value R/W
No.
#2257
Preliminary receive data buffer for interlink
to 0 R
connection mode
#2271

R: Read only B
W: Read or Write

N:N Network
*1. Provided for preliminary buffers for the interlink connection mode.

Caution
Buffer memories specified as "W: For write" can be read also. C
Do not use undefined buffer memory numbers in programs.

Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-19
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

5.4.2 Communication format <BFM #0>

Bit Contents 0 1 Initial value


b0 Data length 7-bit 8-bit 1 : 8-bit
(00) : Not provided
b1
Parity (01) : Odd (11) : Even
b2
(11) : Even
b3 Stop bit 1-bit 2-bit 0 : 1-bit
(0011) : 300
(0100) : 600
b4
(0101) : 1200
b5
Baud rate (bps) (0110) : 2400 (1000) : 9600 bps
b6
(0111) : 4800
b7
(1000) : 9600
(1001) : 19200
(00) : Not provided
b8
Control line (01) : Standard RS-232C (00) : Not provided
b9
(11) : RS-232C interlink mode
(00) : Both CR and LF are not added.
b10
CR and LF addition (01) : Only CR is added. (00) : Not provided
b11
(11) : Both CR and LF are added.
(00) : Both check sum and ASCII-hexadecimal
conversion are not provided.
(01) : Only ASCII-hexadecimal conversion is
b12 Absence/presence of check sum provided. (00) : Not provided
b13 and ASCII-Hexadecimal conversion
(10) : Only check sum is provided.
(11) : Both check sum and ASCII-hexadecimal
conversion are provided.
Send/receive data buffer data
b14 16-bit 8-bit 0 : 16-bit
length
b15 Undefined (cannot be used) 0 : Undefined

The communication format setting contents are determined when the sending/receiving enable command
(BFM #1, b0) turns ON.
Accordingly, it is necessary to transfer the communication format setting in advance using TO instruction
before setting the sending/receiving enable command to ON.
However, the sending header and sending terminator are determined when the sending command (BFM #1,
b1) turns ON. And the receiving header and receiving terminator are determined when the sending/receiving
enable command (BFM #1, b0) turns ON and the receiving complete flag reset command (BFM #1, b2) turns
ON. Accordingly, if only the header and terminator are changed in the middle of communication, such change
will become valid at the next sending/receiving operation, (so it is not necessary to turn OFF the sending/
receiving enable command).

Example of communication format setting (specified in hexadecimal constant)


When specifying the communication format as shown in the table below, use the following program.

Data length 8-bit M8002


FNC 79 K0 K0 H4063 K1
Parity Odd
TO
Stop bit 1-bit Initial pulse Block No. BFM # Set value Number of
Baud rate 2400 bps transfer
points
Control line Not provided
CR and LF Not added
b15 b12 b11 b8 b7 b4 b3 b0
Check sum Not provided BFM #0 0 1 0 0 0 0 0 0 0 1 1 0 0 0 1 1
ASCII-hexadecimal
Not provided 4 0 6 3
conversion
Buffer data length 8-bit (4063H)

G-20
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

A
1. Communication format

Common Items
[1] Data
Select the communication format to
be used to send and receive data in
the 232IF from the formats shown to Data Termi-
[2] nator
the right.
1) The header can be specified
B
[3] Data Termi- CR

N:N Network
before the data in the nator
communication format.
Data Termi- CR LF
2) In the communication format [1], [4] nator
hexadecimal (binary) values and
ASCII codes can be sent and
received.
[5] Header Data Termi-
nator
Sum C

Parallel Link
When using the communication
formats [2] to [9], make sure to use [6] Header Data Termi- Sum CR
ASCII codes as the sent and nator
received data.
The received data should not [7] Header Data Termi- Sum CR LF
include the header, terminator or
nator
D
CR. (In communication formats [4],

Computer Link
[8] Data CR
[7] and [9], the data area after "CR"
is not received.)
By specifying b13 and b12 of BFM [9] Data CR LF
#0, the ASCII-Hexadecimal
conversion function can be used
for communication.
E

Communication
Inverter
3) ASCII codes "01H" to "1FH" can be used as the head terminator.
4) In the RS-232C interlink connection mode, the communication formats [2] to [7] are valid.

2. b0 to b7 (data length, parity, stop bit and baud rate)


Align the setting of b0 to b7 with the communication specifications in the connected external equipment. F
3. b9 and b8 (control line)

(RS/RS2 Instruction)
Communication
Non-Protocol
1) When "control line not provided (b9 = 0, b8 = 0)" is specified, data is transferred using only the SD and
RD signals without using the control line.
2) When the "standard RS-232C mode (b9 = 0, b8 = 1)" is specified, use a cross cable to connect
equipment with the terminal specifications, and use a straight cable to connect equipment with the
modem specifications.
G

(FX2N-232IF)
Communication
Non-Protocol
3) When the "RS-232C interlink connection mode (b9 = 1, b8 = 1)" is specified, the sending request (RS)
signal works as the receiving enable signal for the 232IF. When the 232IF receives data beyond the
maximum number of receivable bytes (BFM #2), it turns OFF the receiving enable (RS) signal to ask the
external equipment to suspend sending.
At this time, by withdrawing the contents of the received data buffer to data registers in the PLC using a
sequence program, the 232IF can continuously receive the remaining data.
H
Communication
Programming

When this mode is specified, make sure to perform the interlink connection for RS-232C.
For the wiring of equipment according to each setting, refer to Chapter 4.
For the operation of the control line, refer to Section 5.5.

4. b11 and b10 (CR and LF addition)


The following specification methods are applicable: I
1) Both CR and LF are not added (b11 = 0, b10 = 0).
Maintenance
Remote

2) Only CR is added (b11 = 0, b10 = 1).


3) Both CR and LF are added (b11 = 1, b10 = 1).
For the CR/LF addition format, refer to the communication format list above.
Apx.A
models
Discontinued

G-21
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

5. b13 and b12 (absence/presence of check sum and ASCII-Hexadecimal conversion)


The following specification methods are applicable:
1) Neither the check sum nor ASCII-Hexadecimal conversion are provided (b13 = 0, b12 = 0).
2) Only the ASCII-Hexadecimal conversion is provided (b13 = 0, b12 = 1).
3) Only the check sum is provided (b13 = 1, b12 = 0).
4) Both the check sum and ASCII-Hexadecimal conversion are provided (b13 = 1, b12 = 1).
For the check sum addition format, refer to the communication format list above.

<ASCII-Hexadecimal conversion>
When "ASCII-Hexadecimal conversion provided" is specified, the hexadecimal numeric value data (0 to
F) inside the send data buffer (BFM #1001 to 1256) is converted into ASCII data before being sent. And
the received ASCII data is converted into the hexadecimal numeric value data (0 to F) before being
stored in the received data buffer (BFM #2001 to 2256).
The number of sent/received bytes at this time indicates the amount of hexadecimal data.

<Sending format during conversion from hexadecimal data into ASCII data>
Example: When the send data is "10ABH", the header is "STX" and the terminator is "ETX"

(Send data buffer BFM #1001)


b15 b0
0 0 0 1 0 0 0 0 1 0 1 0 1 0 1 1
1 0 A B

1 byte 1 byte
The number of sent bytes is "2".

Data is converted into ASCII data when


being sent.

S E
T T
A B 1 0
X X
02H 41H 42H 31H 30H 03H

<Receiving format in conversion from ASCII data into hexadecimal data>


Example: When the received data is "10ABH", the header is "STX" and the terminator is "ETX"

S E
T T
A B 1 0
X X
02H 41H 42H 31H 30H 03H

(Receive data buffer BFM #2001)


b15 b0
0 0 0 1 0 0 0 0 1 0 1 0 1 0 1 1
1 0 A B

1 byte 1 byte
The number of received bytes is "2".

G-22
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

A
6. b14 (send/receive data buffer data length)

Common Items
The data is handled as shown below according to the buffer data length.

1) 16-bit (b14 = 0)
Send/receive data buffer
16-bit data is divided into B
Highest-order 8 byte Lowest-order 8 byte lowest-order 8-bit and highest-

N:N Network
order 8-bit when being sent or
received.
Example of send data buffer
S BFM BFM BFM BFM E
T #1001
lowest-
#1001
highest-
#1002
lowest-
#1002 T
highest-
C
X order byte X

Parallel Link
order byte order byte order byte

2) 8-bit (b14 = 1)
Send/receive data buffer
D
Highest-order 8-bit are ignored.

Computer Link
Ignored Lowest-order 8 byte Only lowest-order 8-bit are sent
and received as valid data.

Example of send data buffer


S BFM BFM BFM BFM E
T #1001 #1002 #1003 #1004 T E
lowest- lowest- lowest- lowest-

Communication
Inverter
X order byte order byte order byte order byte X

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-23
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

5.4.3 Command <BFM #1>


BFM #1 gives the command for sending or receiving data or resetting the status information to the 232IF.
Bit Contents
b0 Sending/receiving enable (ER ON)
b1 Sending command
b2 Receiving complete flag reset command
b3 Error reset

1. b0 (sending/receiving enable)
While b0 is ON, the 232IF can send and receive data.
Because the contents of the following set items are determined at the rising edge of b0, transfer these values
in advance using the TO instruction before setting b0 to ON:
- BFM #0 (communication format)
- BFM #9 and 8 (receiving header)
- BFM #11 and 10 (receiving terminator)
At the rising edge of b0, the error occurrence status (BFM #28, b3) and error code (BFM #29) are cleared.

2. b1 (sending command)
At the rising edge of b1, the contents of the send data buffer (BFM #1001 to 1256) in the amount of bytes
specified (BFM #1000) are sent to the external equipment.
When sending is completed, the sending complete status (BFM #28, b0) is set to ON. When the next sending
command (b1) is given, the sending complete status (BFM #28, b0) is automatically set to OFF.
When the sending command is given, the contents of the following set items are determined:
- BFM #5 and 4 (sending header)
- BFM #7 and 6 (sending terminator)

3. b2 (receiving complete flag reset command)


When b2 is set to ON, the following items are cleared:
- BFM #28, b1 (receiving complete)
- BFM #2000 (number of received bytes)
- BFM #2001 to 2256 (receive data buffer)
After receiving is completed, it is necessary to clear the receiving complete status (BFM #28, b1) because the
232IF cannot receive next data while b1 of the BFM #28 remains ON.
When the receiving complete flag reset command is given, the contents of the following set items are
determined:
- BFM #9 and 8 (receiving header)
- BFM #11 and 10 (receiving terminator)
In the RS-232C interlink connection mode (BFM #0, b9 = 1, b8 =1), the receiving complete flag reset
command works as the receiving continue command for receiving data beyond the maximum number of
receivable bytes (BFM #2), and clears the following items:
- BFM #28, b4 (receiving suspended)
- BFM #2000 (number of received bytes)
- BFM #2001 to 2256 (receive data buffer)
- BFM #2257 to 2271 (preliminary receive data buffer)
The receiving enable (RS) signal is automatically set to ON.

4. b3 (error reset)
When b3 is set to ON, the contents of the error occurrence status (BFM #28, b3) and error code (BFM #29)
are cleared.

G-24
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

A
5.4.4 Maximum number of receivable bytes <BFM #2>

Common Items
Setting range: 1 to 512 bytes (when the buffer data length is 16-bit)
1 to 256 bytes (when the buffer data length is 8-bit)
"0" is handled as "512" or "256 bytes". The initial value is "0".
This bit specifies the maximum number of bytes which can be received by the 232IF.
When the 232IF receives the maximum number of receivable bytes, it sets the receiving complete flag (BFM
B

N:N Network
#28, b1) to ON.
If the receiving terminator (BFM #11 and 10) or receiving timeout time (BFM #3) are set, the 232IF recognizes
that receiving is completed even if the already received data does not reach the maximum number of
receivable bytes when either condition is satisfied.

5.4.5 Receiving timeout time <BFM #3> C

Parallel Link
Setting range: 1 to 32767 ( 10 ms)
"0" is regarded as no timeout time. The initial value is "0".
This bit specifies the waiting time limit for receive data.
When the 232IF does not receive the next set of data within the receiving timeout time after the receiving
edge of each data, the receiving timeout flag (BFM #28, b2) turns ON. At this time, the 232IF recognizes that D
receiving is completed, and sets the receiving complete flag (BFM #28, b1) to ON.

Computer Link
5.4.6 Sending header <BFM #5 (highest-order 2 bytes) and BFM #4 (lowest-order 2
bytes)>
Setting range: 4 bytes maximum, 0 suppression E
The initial value is "0" (no sending header).

Communication
Inverter
Up to four headers can be specified for the 232IF send data. When the number of headers is less than 4, "0"s
in upper positions are ignored (0 suppression) and are not transferred.

BFM #5 BFM #4
(highest-order 2 bytes) (lowest-order 2 bytes)
b15 b0 b15 b0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 F

(RS/RS2 Instruction)
Communication
Non-Protocol
0 0 0 0 0 0 0 2
Fourth Third Second First header
header header header Example:
02H (STX)
The transfer order is "fourth header third header second header first header" when four headers are
set. G

(FX2N-232IF)
Communication
Non-Protocol
5.4.7 Sending terminator <BFM #7 (highest-order 2 bytes) and BFM #6 (lowest-order 2
bytes)>
Setting range: 4 bytes maximum, 0 suppression
The initial value is "0" (no sending terminator). H
Up to four terminators can be specified for the 232IF send data. When the number of terminators is less than
Communication
Programming

4, "0"s in upper positions are ignored (0 suppression) and are not transferred.
For the terminator transferred first, specify ASCII code from "01H" to "1FH". (For other terminators after that,
any ASCII code other than "01H" to "1FH" can be specified.)
The register structure and transfer order are the same as those of the sending header described above.

5.4.8 Receiving header <BFM #9 (highest-order 2 bytes) and BFM #8 (lowest-order 2


I
Maintenance
Remote

bytes)>
Setting range: 4 bytes maximum, 0 suppression
The initial value is "0" (no sending header).
Up to four headers can be specified for the 232IF received data. When the number of headers is less than 4,
"0"s in upper positions are ignored (0 suppression) and are not transferred. Apx.A
The register structure and transfer order are the same as those of the sending header described above.
models
Discontinued

G-25
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

5.4.9 Receiving terminator <BFM #11 (highest-order 2 bytes) and BFM #10 (lowest-order 2
bytes)>
Setting range: 4 bytes maximum, 0 suppression
The initial value is "0" (no sending terminator).
Up to four terminators can be specified for the 232IF received data. When the number of terminators is less
than 4, "0"s in upper positions are ignored (0 suppression) and are not transferred.
For the terminator received first, specify an ASCII code from "01H" to "1FH". (For other terminators after that,
any ASCII code other than "01H" to "1FH" can be specified.)
The register structure and transfer order are the same as those of the sending header described above.

5.4.10 Receiving suspension waiting time <BFM #12>


Setting range: 0 to 32767 ( 10 ms)
The initial value is "0 ms".
When the 232IF receives data beyond the maximum number of receivable bytes (BFM #2) in the RS-232C
interlink connection mode (BFM #0, b9 = 1, b8 = 1), it sets the receiving enable (RS) signal to OFF to ask the
external equipment to suspend sending.
BFM #12 sets the time after the receiving enable (RS) signal is set to OFF until the receiving suspended
status bit (BFM #28, b4) is set to ON. Make sure that the time set by BFM #12 is longer than the time between
when the 232IF sets the receiving enable (RS) signal to OFF until the external equipment completely
suspends sending.
If the receiving suspended status bit (BFM #28, b4) is set to ON before the external equipment stops sending,
the 232IF cannot receive the remaining data any more.
Preliminary receive
542 data buffer
513 (BFM#2257 to #2271)
512
Number of
received bytes 0 Maximum number of
receivable bytes
BFM#2000 (BFM#2) Set the time at which sending
from the external equipment
Data receiving is completely suspended.
Receiving enable(RS) is suspended.

Receiving suspended
BFM#28 b4
Suspension waiting
time(BFM#12)
0 to 32767(10 ms)

5.4.11 Amount of remaining send data <BFM #13>


Stored value: 0 to 512 (when the buffer data length is 16-bit)
0 to 256 (when the buffer data length is 8-bit)
This buffer stores the value set in the number of bytes to be sent (BFM #1000) subtracted by the number of
already sent data.

5.4.12 Amount of received data buffers <BFM #14>

Stored value: 0 to 256+15 ("15" is provided for the preliminary receive data buffer.)
This buffer stores the amount of received data buffers which have already received data among the received
data buffers BFM #2001 to 2256 and preliminary receive data buffers for interlink connection mode BFM
#2257 to 2271.

G-26
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

A
5.4.13 Sending sum result <BFM #15>

Common Items
Initial value: 0
This buffer stores the value of the check sum added to the send data.
The sum check target range and check sum calculation method are as shown below.

Sum check target range and check sum calculation method B


(Example)

N:N Network
Header Terminator Check sum

S E
T
X
0 A 1 2 5 F
T
X
5 2 C

Parallel Link
02H 30H 41H 31H 32H 35H 46H 03H 35H 32H

Target range

30H+41H+31H+32H+35H+
46H+03H=152H
D

Computer Link
The sum of the data including the terminators but not the first header (first one byte only) is calculated, the
least significant byte of the calculation result is converted into ASCII code, and the data is sent and received.
The ASCII data is arranged in the order of "upper digit, lower digit".

5.4.14 Receiving sum result <BFM #16> E

Communication
Inverter
Initial value: 0
This buffer stores the sum check value of the received data.
If the check sum value added to the received data is different from the receiving sum result, "receiving sum
check error" occurs.
The sum check target range and check sum calculation method are the same as those shown in "5.4.13
Sending sum result" above. F

(RS/RS2 Instruction)
Communication
Non-Protocol
5.4.15 Time from CS ON to sending start <BFM #20>
Set value: 0 to 32767 ( 10 ms)
Initial value: 0 ms
This buffer sets the time between when the sending enable (CS) signal is set to ON until the 232IF actually G
starts to send.

(FX2N-232IF)
Communication
Non-Protocol
When "control line not provided" is specified, this buffer sets the time after the sending command is given until
sending starts.
Set proper time according to the modem, etc.

5.4.16 Time from actual sending completion to RS OFF <BFM #21> H


Communication
Programming

Set value: 0 to 32767 ( 10 ms)


Initial value: 0 ms
This buffer sets the time between when the 232IF completes sending until RS signal turns OFF and the
sending complete flag (BFM #28, b0) turns ON.
Set proper time according to the modem, etc.
I
Maintenance
Remote

Apx.A
models
Discontinued

G-27
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

5.4.17 Status <BFM #28>

Bit Contents Bit Contents


b0 Sending complete b8 RS(RTS)
b1 Receiving complete b9 ER(DTR)
b2 Receiving timeout b10 Undefined
b3 Error occurrence b11 Undefined
b4 Receiving suspended b12 DR(DSR)
b5 Undefined b13 CD(DCD)
b6 Sending b14 DS(CTS)
b7 Receiving b15 CI(RI)

This buffer stores the 232IF status and sending/receiving result as the status information. The PLC can read
this buffer using the FROM instruction.
1. b0 (sending complete)
When sending the specified amount of bytes (BFM #1000) is completed, the sending complete flag (b0) is set
to ON.
The sending complete flag (b0) is automatically set to OFF when the next sending command (BFM #1, b1) is
set to ON.
2. b1 (receiving complete)
When the maximum number of receivable bytes (BFM #2) are received, the receiving complete flag (b1) is set
to ON.
If the receiving terminator (BFM #11 and 10) or receiving timeout time (BFM #3) is set, the 232IF recognizes
that receiving is completed even if the already received data does not reach the maximum number of
received bytes when either condition is satisfied.
It is necessary to set this receiving complete flag to OFF in a sequence program. The 232IF is not ready to
receive the next set of data while this bit is ON. Use the receiving complete flag reset command (BFM #1, b2)
to set this bit to OFF.
3. b2 (receiving timeout)
When the receiving timeout time (BFM #3) is reached during receiving, the receiving timeout bit (b2) is set to
ON. And the receiving complete flag (b1) is also set to ON.
The receiving timeout status (b2) is set to OFF when the receiving complete flag reset command (BFM #1,
b2) is executed.
4. b3 (error occurrence)
When an error occurs during sending or receiving, the error occurrence status bit (b3) is set to ON and the
contents of the error are stored in the error code (BFM #29).
5. b4 (receiving suspended)
When the 232IF receives data beyond the maximum number of receivable bytes (BFM #2) in the RS-232C
interlink connection mode (BFM #0, b9 = 1, b8 = 1), it sets the receiving enable (RS) signal to OFF and asks
the external equipment to suspend sending. After the receiving suspension waiting time (BFM #12), the 232IF
sets the receiving suspended status bit (b4) to ON.
To receive data beyond the maximum number of receivable bytes (BFM #2) in the interlink connection mode,
it is necessary to monitor the rising edge of this receiving suspended status bit (b4) in the sequence program,
and withdraw the number of received bytes (BFM #2000) or amount of received data buffers (BFM #14) from
the received data buffer (BFM #2001 to 2271) to data registers inside the PLC.
6. b6 (sending)
This bit remains ON from when the sending command (BFM #1, b1) is given until the sending complete flag
(BFM #28, b0) is set to ON.
7. b7 (receiving)
This bit remains ON from when the head data is received until the receiving complete flag (BFM #28, b1) is
set to ON.
8. b8 (RS), b9 (ER), b12 (DR), b13 (CD), b14 (CS) and b15 (CI)
These bits indicate the operation status by their ON/OFF status.

G-28
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.4 Buffer Memory (BFM)

A
5.4.18 Error code <BFM #29>

Common Items
For the error codes, refer to Section 7.2.

5.4.19 Model code <BFM #30>


The model code of the 232IF is "K7030".
B

N:N Network
The model code is a specific code assigned to each special extension module. By reading the model code in
the PLC, the equipment type can be checked.

5.4.20 Number of bytes to be sent <BFM #1000>


Setting range: 0 to 512 bytes (when the buffer data length is 16-bit) C
0 to 256 bytes (when the buffer data length is 8-bit)

Parallel Link
This buffer specifies how many bytes should be sent among the 512 bytes/256 words in the 16-bit send data
buffer (BFM #1001 to 1256).

5.4.21 Send data buffer <BFM #1001 to 1256>


The send data buffer is a section of 16-bit buffers for storing the send data. The send data buffers can store
D

Computer Link
up to 512 bytes/256 words.

Structure of send/receive data buffer

Example: BFM #1001 (16-bit buffer)

b15
Highest-order byte Lowest-order byte
b0
E

Communication
Inverter
0 0 1 1 0 0 1 0 0 1 0 0 0 0 0 1
3 2 4 1
32H=2 41H=A

1 byte 1 byte
F
1 word

(RS/RS2 Instruction)
Communication
Non-Protocol
Values in the send data buffers and receive data buffers are handled as hexadecimal values.

5.4.22 Number of received bytes <BFM #2000>

Stored value: 0 to 512+30*1 bytes (when the buffer data length is 16-bit)
G

(FX2N-232IF)
Communication
Non-Protocol
0 to 256+15*1 bytes (when the buffer data length is 8-bit)
This buffer stores the number of bytes received from the external equipment. The value stored in this buffer is
cleared when the receiving complete flag reset command (BFM #1, b2) is given.
*1. "30" or "15" bytes are provided for the preliminary buffer in the interlink connection mode.

5.4.23 Receive data buffer <BFM #2001 to 2256>


H
Communication
Programming

The received data buffer is a section of 16-bit buffers for storing the data received from the external equipment.
The received data buffer can store up to 512 bytes/256 words.
The received data buffer structure is same as the send data buffer structure.
The contents of the received data buffer are cleared when the receiving complete flag reset command (BFM
#1, b2) is given. I
Maintenance
Remote

5.4.24 Preliminary receive data buffer for interlink connection mode <BFM #2257 to 2271>
The preliminary receive data buffer is provided for storing the data beyond 512 bytes in the interlink
connection mode. The preliminary receive data buffers are used to receive the data sent after the receiving
enable (RS) signal is set to OFF until the external equipment suspends sending. Apx.A
The contents of the preliminary receive data buffer are cleared when the receiving complete flag reset
models
Discontinued

command (BFM #1, b2) is given.

G-29
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.5 Operation of Control Line

5.5 Operation of Control Line

5.5.1 When control line is not provided [BFM #0, (b9, b8) = (0, 0)]

Sending/ OFF ON
Set this bit to OFF in the sequence
receiving enable program. While it remains ON,
(BFM#1 b0) the next data cannot be sent.
Sending OFF ON
command
(BFM#1 b1)
SD(TXD) Message 1 Message 4
Send data
Time set by BFM #20 Time set by BFM #20
multiplied by 10 ms
Sending OFF multiplied by 10 ms ON
complete
(BFM#28 b0)
RD(RXD) Message 2 Message 3
Receive data

Receiving OFF ON
complete Set this bit to OFF in the
(BFM#28 b1) sequence program.
While it remains ON, the
next receiving complete
flag reset command
Receiving OFF cannot be given.
complete flag ON
reset command The receiving waiting
status is started.
(BFM#1 b2)
After receiving is completed and the received Set this bit to OFF in the sequence program.
data is read, set the receiving complete flag While it remains ON, the next receiving
(BFM #28, b1) to OFF using the receiving complete flag reset command cannot be
complete flag reset command. given.

G-30
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.5 Operation of Control Line

A
5.5.2 When control line is in standard RS-232C mode [BFM #0, (b9, b8) = (0, 1)]

Common Items
Sending/receiving
enable OFF ON
(BFM#1 b0)

DR(DSR) OFF ON Set this bit to OFF in the sequence * Value set by BFM #21
B
program. While it remains ON, the multiplied by 10 ms

N:N Network
Sending next data cannot be sent.
command OFF ON
(BFM#1 b1) *

RS(RTS) OFF ON
C
CS(CTS) OFF ON

Parallel Link
SD(TXD) OFF
Send data Message 2 Message 4
Sending Time set by BFM #20 Time set by BFM #20
complete
(BFM#28 b0)
OFF multiplied by 10 ms multiplied by 10 ms
D

Computer Link
* Value set by BFM #21 *
RD(RXD) multiplied by 10 ms
Message 1 Message 3
Receive data

Receiving OFF ON
complete
(BFM#28 b1) Set this bit to OFF in the
sequence program.
While it remains ON, the next
E

Communication
Inverter
receiving complete flag reset
Receiving OFF command cannot be given.
complete flag The receiving waiting
reset command status is started.
(BFM#1 b2) After receiving is completed and the received Set this bit to OFF in the sequence program.
data is read, set the receiving complete flag While it remains ON, the next receiving
(BFM #28, b1) to OFF using the receiving complete flag reset command cannot be given.
complete flag reset command.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-31
FX Series PLC User's Manual - Data Communication Edition 5 Creating Programs
Non-Protocol Communication (FX2N-232IF) 5.5 Operation of Control Line

5.5.3 When control line is in RS-232C interlink mode [BFM #0, (b9, b8) = (1, 1)]

Sending/receiving
enable OFF ON
(BFM#1 b0)

OFF ON Set this bit to OFF in the


DR(DSR)
sequence program.
Sending While it remains ON, the
command OFF ON next data cannot be sent.
(BFM#1 b1)

OFF *1 *1
CS(CTS)
Time set by BFM #20
multiplied by 10 ms Message 4
SD(TXD) Message 2
Send data
Sending OFF ON
complete
(BFM#28 b0)
Time set by BFM
#21 multiplied by
RS(RTS) OFF ON 10 ms

Message 3
RD(RXD) Message 1
Receive data
Receiving Message 3
suspended OFF ON
(BFM#28 b4)

Time set by BFM #12


Receiving multiplied by 10 ms
complete OFF ON
(BFM#28 b1) Set this bit to OFF in the
sequence program. While
Receiving it remains ON, the next
complete flag receiving complete flag
reset command reset command cannot be
(BFM#1 b2) OFF given.

After receiving is completed and the received data is Set this bit to OFF in the sequence program.
read, set the receiving complete flag (BFM #28, b1) to While it remains ON, the next receiving
OFF using the receiving complete flag reset complete flag reset command cannot be given.
command.

*1. Make sure that the CS (CTS) signal turns ON in the 232IF while the external equipment is ready to
receive.
*2. When the amount of data already received exceeds the maximum number of receivable bytes
specified by BFM #2, the RS (RTS) signal turns OFF. Accordingly, sending is suspended from the
external equipment within 30 bytes when the send/receive data buffer data length is 16-bit (BFM #0,
b14= 0), or within 15 bytes when the send/receive data buffer data length is 8-bit (BFM #0, b14= 1).
If sending is not suspended, the 232IF cannot receive all sent data.
*3. Read the amount of received bytes (BFM #14) from the received data buffer (BFM #2001 to 2271) to
data registers in the PLC, and then set it to ON.

G-32
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.1 Example of Sending/Receiving 16-Bit Buffer Length Data

Common Items
6. Practical Program Examples
B
6.1 Example of Sending/Receiving 16-Bit Buffer Length Data

N:N Network
In this example, the 16-bit buffer length data is sent and received between the 232IF and equipment with the
terminal specifications. In this example, ASCII codes stored in the data registers D201 to D205 in the PLC are
sent to the external equipment, and the data received from the external equipment is stored to data registers
D301 to D304 in the PLC. C

Parallel Link
1. System configuration
POW
ER

SD
RD

+ Cross cable

D
FX3U Series FX2N-232IF Personal computer, etc.

Computer Link
2. Example of setting buffer memory
Suppose that each buffer memory not described here is set to the initial value.
1) Communication format <BFM #0> E

Communication
Inverter
Bit Contents Setting
b0 Data length (1) : 8-bit
b1
Parity (1,1) : Even
b2
b3 Stop bit (1) : 2-bit F

(RS/RS2 Instruction)
Communication
Non-Protocol
b4
b5
Baud rate (1001) : 19200 bps
b6
b7
b8
b9
Control line (00) : Not provided
G
b10

(FX2N-232IF)
Communication
Non-Protocol
CR and LF addition (00) : Not provided
b11
Absence/presence of check
b12
sum and ASCII-Hexadecimal (00) : Not provided
b13
conversion

b14
Send/receive data buffer data
(0) : 16-bit Item to specify 16-bit data
H
length
Communication
Programming

b15 Undefined

b15 b8 b7 b0
0 0 0 0 0 0 0 0 1 0 0 1 1 1 1 1
I
0 0 9 F (009FH)
Maintenance
Remote

2) Command <BFM #1>


M0 b0: Sending/receiving enable (ER ON)
M1 b1: Sending command
M2 b2: Receiving complete flag reset command Apx.A
M3 b3: Error reset
models
Discontinued

3) Maximum number of receivable bytes <BFM #2>


8 bytes

G-33
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.1 Example of Sending/Receiving 16-Bit Buffer Length Data

4) Header and terminator <BFM #4 to 11>


BFM #4 and 8 (sending header and receiving header): 02H (STX)
BFM #6 and 10 (sending terminator and receiving terminator): 03H (ETX)
5) Status <BFM #28>
b0 M10: Sending complete b8 M18: RS(RTS)
b1 M11: Receiving complete b9 M19: ER(DTR)
b2 M12: Receiving timeout b10 M20: Undefined
b3 M13: Error occurrence b11 M21: Undefined
b4 M14: Receiving suspended b12 M22: DR(DSR)
b5 M15: Undefined b13 M23: CD(DCD)
b6 M16: Sending b14 M24: CS(CTS)
b7 M17: Receiving b15 M25: CI(RI)
6) Number of bytes to be sent <BFM #1000>
9 bytes
7) Send data buffer <BFM #1001 and later>
The send data "Test data" in ASCII codes is provided to 9 bytes (as specified in BFM#1000).
2nd byte 1st byte
highest-order lowest-order
(BFM#1001) e (65H) T (54H)
4th byte 3rd byte
(BFM#1002) t (74H) s (73H)
6th byte 5th byte
(BFM#1003) d (64H) (20H)
8th byte Space
7th byte
(BFM#1004) t (74H) a (61H)
10th byte 9th byte
The 10th byte is not sent.
(BFM#1005) * * a (61H)

8) Receive data buffer <BFM #2001 and later>


Eight bytes specified by the maximum number of receivable bytes (BFM #2) are read to data registers
D301 to D304 in the PLC.

G-34
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.1 Example of Sending/Receiving 16-Bit Buffer Length Data

A
3. Operation chart

Common Items
BFM#1 b0
(M0) Sending/receiving
enable

(M1) BFM#1 b1
Sending command
98 7
B
BFM#13 65

N:N Network
Amount of remaining 432
send data 10

#1001 (highest-order byte)

#1002 (highest-order byte)

#1003 (highest-order byte)

#1004 (highest-order byte)


The sending complete flag is

#1001 (lowest-order byte)

#1002 (lowest-order byte)

#1003 (lowest-order byte)

#1004 (lowest-order byte)

#1005 (lowest-order byte)


Sending

set to OFF also by the next


sending command.

C
STX

ETX

STX

Parallel Link
BFM#1001 to #1256
Send data buffer

BFM#1000
(M10) BFM#28 b0 Number of bytes
Sending complete to be sent
D
BFM#14 4

Computer Link
Amount of received 3
2
data buffers 0 1
BFM#2000 78
56
Number of received
2 34
bytes 01
The contents of received data buffer are cleared also. When the receiving complete flag is not reset
E
#2001 (highest-order byte)

#2002 (highest-order byte)

#2003 (highest-order byte)

#2004 (highest-order byte)


#2001 (lowest-order byte)

#2002 (lowest-order byte)

#2003 (lowest-order byte)

#2004 (lowest-order byte)

Communication
Inverter
Receiving

STX

ETX

ETX
STX

BFM#2001 to #2256
Received data buffer
F
BFM#2

(RS/RS2 Instruction)
Communication
Non-Protocol
(M11) BFM#28 b1 Maximum number of
Receiving complete receivable bytes

(M2) BFM#1 b2
Receiving complete flag reset command

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-35
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.1 Example of Sending/Receiving 16-Bit Buffer Length Data

4. Sequence program example


M8002 FNC 79 K0 K0 H009F K1 The communication format is transferred.
TO (009FH BFM#0)
Initial pulse
Block No. BFM # Transfer Number of
source transfer points
FNC 79 The maximum number of receivable bytes is transferred.
K0 K2 K8 K1 (K 8 BFM#2)
TO

FNC 79 H02 Sending header


K0 K4 K1 (02H BFM#4)
TO (STX)

FNC 79 H03 Sending terminator


K0 K6 K1 (03H BFM#6)
TO (ETX)

FNC 79 H02 Receiving header


K0 K8 K1 (02H BFM#8)
TO (STX)

FNC 79 K0 K 10 H03 K1 Receiving terminator


TO (ETX) (03H BFM#10)
X000
PLS M1 Sending command
Sending command input
M1 FNC 12 Number of bytes to be sent
K9 D 200
MOV (K9 D200)

FNC 12 H6554 D 201 ( e T)


MOV

FNC 12 H7473 D 202 (t s)


MOV

FNC 12 H6420 D 203 (d ) Send data (9 bytes)


MOV "Test data"

NC 12 H7461 D 204 (t a)
MOV

FNC 12 H0061 D 205 ( a)


MOV
Blank

FNC 79 The number of bytes to be sent and send data are transferred.
K0 K1000 D200 K6 D200(K 9) BFM#1000
TO D201(e T) BFM#1001
D202(t s) BFM#1002
D203(d ) BFM#1003
D204(t a) BFM#1004
D205( a) BFM#1005
M8000 M8003
M0 Sending/receiving is enabled.
RUN monitor
FNC 78 The status is read.
K0 K 28 K4M10 K1 (BFM#28 b15 to b0 M25 to M10)
FROM
Block No. BFM # Transfer Number of
source transfer points
M10
Y0
Sending complete The status is monitored (if necessary).
M13
Y1
Error occurrence
X001
M3 The error is reset.
Error reset input
M11 FNC 78 The received data buffers are read.
K0 K2001 D301 K4 BFM#2001 D301
Receiving FROM
BFM#2002 D302
complete
BFM#2003 D303
BFM#2004 D304

Receiving complete
M2 flag reset command

M8000 FNC 79 The commands are transferred.


K0 K1 K1M0 K1 (M3 to M0 BFM#1 b3 to b0)
TO

G-36
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.2 Sending/Receiving 8-Bit Buffer Length Data

A
6.2 Sending/Receiving 8-Bit Buffer Length Data

Common Items
In this example, the 8-bit buffer length data is sent and received between the 232IF and equipment with the
terminal specifications. In this example, ASCII codes stored in the data registers D201 to D209 in the PLC are
sent to the external equipment, and the data received from the external equipment is stored to data registers
D301 to D308 in the PLC. B

N:N Network
1. System configuration

POW
ER

SD
RD

+ Cross cable
C
Personal computer, etc.

Parallel Link
FX3U Series FX2N-232IF

2. Example of setting buffer memory


Suppose that each buffer memory not described here is set to the initial value.
1) Communication format <BFM #0> D

Computer Link
Bit Contents Setting
b0 Data length (1) : 8-bit
b1
Parity (1,1) : Even
b2
b3 Stop bit (1) : 2-bit
E

Communication
Inverter
b4
b5
Baud rate (1001) : 19200 bps
b6
b7
b8
b9
Control line (00) : Not provided F

(RS/RS2 Instruction)
Communication
Non-Protocol
b10
CR and LF addition (00) : Not provided
b11
b12 Absence/presence of check sum and ASCII-
(00) : Not provided
b13 Hexadecimal conversion
b14 Send/receive data buffer data length (1) : 8-bit Item to specify 8-bit data G
b15 Undefined

(FX2N-232IF)
Communication
Non-Protocol
b15 b8 b7 b0
0 1 0 0 0 0 0 0 1 0 0 1 1 1 1 1
4 0 9 F (409FH) H
Communication
Programming

2) Command <BFM #1>


M0 b0: Sending/receiving enable (ER ON)
M1 b1: Sending command
M2 b2: Receiving complete flag reset command
M3 b3: Error reset
3) Maximum number of receivable bytes <BFM #2>
I
Maintenance
Remote

8 bytes
4) Header and terminator <BFM #4 to 11>
BFM #4 and 8 (sending header and receiving header): 02H (STX)
BFM #6 and 10 (sending terminator and receiving terminator): 03H (ETX)
Apx.A
models
Discontinued

G-37
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.2 Sending/Receiving 8-Bit Buffer Length Data

5) Status <BFM #28>


b0 M10: Sending complete b8 M18: RS(RTS)
b1 M11: Receiving complete b9 M19: ER(DTR)
b2 M12: Receiving timeout b10 M20: Undefined
b3 M13: Error occurrence b11 M21: Undefined
b4 M14: Receiving suspended b12 M22: DR(DSR)
b5 M15: Undefined b13 M23: CD(DCD)
b6 M16: Sending b14 M24: CS(CTS)
b7 M17: Receiving b15 M25: CI(RI)
6) Number of bytes to be sent <BFM #1000>
9 bytes
7) Send data buffer <BFM #1001 and later>
The send data "Test data" in ASCII code is provided to 9 bytes (as specified in BFM #1000).
highest-order lowest-order 1st byte 6th byte
(BFM#1001) Ignored T (54H) (BFM#1006) Ignored d (64H)

2nd byte 7th byte


(BFM#1002) Ignored e (65H) (BFM#1007) Ignored a (61H)

3rd byte 8th byte


(BFM#1003) Ignored s (73H) (BFM#1008) Ignored t (74H)

4th byte 9th byte


(BFM#1004) Ignored t (74H) (BFM#1009) Ignored a (61H)

5th byte
(BFM#1005) Ignored (20H)

Space

8) Receive data buffer <BFM #2001 and later>


Eight bytes specified by the maximum number of receivable bytes (BFM #2) are read to data registers
D301 to D308 in the PLC.

G-38
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.2 Sending/Receiving 8-Bit Buffer Length Data

A
3. Operation chart

Common Items
BFM#1 b0
(M0) Sending/receiving
enable

(M1) BFM#1 b1
Sending command
BFM#13 98 7
B
Amount of remaining 65

N:N Network
send data
432
10

#1001 (lowest-order byte)


#1002 (lowest-order byte)
#1003 (lowest-order byte)

#1005 (lowest-order byte)

#1007 (lowest-order byte)

#1009 (lowest-order byte)


#1004 (lowest-order byte)

#1006 (lowest-order byte)

#1008 (lowest-order byte)


The sending complete flag is
Sending

set to OFF also by the next


sending command.

C
STX

STX
ETX

Parallel Link
BFM#1001 to #1256
Send data buffer

BFM#1000
(M10) BFM#28 b0 Number of bytes
Sending complete to be sent

BFM#14
D
78
56

Computer Link
Amount of received 34
2
data buffers 01
BFM#2000 678
Number of received
2 345
bytes 01
The contents of received data buffer are cleared also. When the receiving complete flag is not reset
E
#2001 (lowest-order byte)
#2002 (lowest-order byte)
#2003 (lowest-order byte)
#2004 (lowest-order byte)
#2005 (lowest-order byte)
#2006 (lowest-order byte)
#2007 (lowest-order byte)
#2008 (lowest-order byte)

Communication
Inverter
Receiving

STX

ETX

STX

BFM#2001 to #2256 ETX


Received data buffer
F
BFM#2
(M11) BFM#28 b1

(RS/RS2 Instruction)
Communication
Non-Protocol
Maximum number of
Receiving complete receivable bytes

(M2) BFM#1 b2
Receiving complete flag reset command

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

G-39
FX Series PLC User's Manual - Data Communication Edition 6 Practical Program Examples
Non-Protocol Communication (FX2N-232IF) 6.2 Sending/Receiving 8-Bit Buffer Length Data

4. Program example
M8002
FNC 79 K0 K0 H409F K1 The communication format is transferred.
TO (409FH BFM#0)
Initial
pulse Block No. BFM # Transfer Number of
source transfer points
FNC 79 K0 K2 K8 K1 The maximum number of receivable bytes is transferred.
TO (K 8 BFM#2)

FNC 79 K0 K4 H02 K1 Sending header


TO (STX) (02H BFM#4)

FNC 79 K0 K6 H03 K1 Sending terminator


TO (ETX) (03H BFM#6)

FNC 79 K0 K8 H02 K1 Receiving header


TO (STX) (02H BFM#8)

FNC 79 K0 K 10 H03 K1 Receiving terminator


TO (ETX) (03H BFM#10)
X000
PLS M1 Sending command
Sending command input
M1 FNC 12 Number of bytes to be sent
K9 D 200
MOV (K9 D200)

FNC 12
H54 D 201 (T)
MOV
Program the steps for the remaining
data in the same way.
MOV H65 D202 ( e )
MOV H73 D203 ( s ) Send data (9 bytes)
MOV H74 D204 ( t ) "Test data"
MOV H20 D205 ( )
MOV H64 D206 ( d )
MOV H61 D207 ( a )
MOV H74 D208 ( t )
MOV H61 D209 ( a )

The number of bytes to be sent and send data are transferred.


FNC 79 K0 K1000 D200 K 10
TO D200(K 9) BFM#1000 D205( ) BFM#1005
D201( t ) BFM#1001 D206( d ) BFM#1006
D202( e ) BFM#1002 D207( a ) BFM#1007
D203( s ) BFM#1003 D208( t ) BFM#1008
D204( t ) BFM#1004 D209( a ) BFM#1009
M8000 M8003
M0 Sending/receiving is enabled.
RUN
monitor
FNC 78 K0 K 28 K4M10 K1 The status is read.
FROM (BFM#28 b15 to b0 M25 to M10)
Block No. BFM # Transfer Number of
source transfer points
M10
Y0
Sending complete The status is monitored (if necessary).
M13
Y1
Error occurrence
X001
M3 The error is reset.
Error reset input
M11 FNC 78 The received data buffers are read.
K0 K2001 D301 K8
FROM BFM#2001 D301 BFM#2005 D305
Receiving BFM#2002 D302 BFM#2006 D306
complete BFM#2003 D303 BFM#2007 D307
BFM#2004 D304 BFM#2008 D308

M2 Receiving complete
flag reset command
M8000
FNC 79 K0 K1 K1M0 K1 The commands are transferred.
TO (M3 to M0 BFM#1 b3 to b0)

G-40
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Non-Protocol Communication (FX2N-232IF) 7.1 Check Items

Common Items
7. Troubleshooting
B
7.1 Check Items

N:N Network
1) Check the POWER LED of the 232IF.
- While the POWER LED is ON, the drive power is being supplied normally.
- If the POWER LED is OFF, the drive power is not being supplied normally.
2) Verify that the power supply is correctly wired to terminals of the 232IF.
C

Parallel Link
3) Check the SD LED and RD LED of the 232IF.
- If the RD LED does not turn ON when the 232IF receives data or if the SD LED does not turn ON when
the 232IF sends data, check the connection and wiring.
- If the RD LED turns ON when the 232IF receives data or if the SD LED turn ON when the 232IF sends
data, the installation and wiring are normal. D
4) Verify that the communication setting (BFM #0) in the 232IF is aligned correctly with the communication

Computer Link
setting in the external equipment. If the communication setting is not aligned correctly, align it.
5) Check the timing at which data is sent and received. For example, when sending data, verify that the
external equipment is ready to receive.
6) When the terminator is not used, verify that the quantity of data to be sent matches the receivable data
quantity. If the quantity of send data may vary, use the terminator. E

Communication
Inverter
7) Verify that the external equipment is operating normally.
8) Verify that the adopted data format is uniform. If the data format is different, modify it.

7.2 Error Codes


F
When an error occurs while data is being sent or received, the 232IF sets bit 3 of the BFM #28 to ON,

(RS/RS2 Instruction)
Communication
Non-Protocol
and stores the corresponding error code to the BFM #29.
Code Contents Cause and countermeasures
0 No error

1
Receiving parity error, overrun
error or framing error
The communication format such as the baud rate does not agree.
The control timing does not agree.
G

(FX2N-232IF)
Communication
Non-Protocol
2 Undefined
3 Defective received character The received data is not ASCII code.
4 Receiving sum check error The sent sum does not agree with the received sum result (BFM #16).
Receive data buffer overflow The number of received bytes exceeds "512+30" bytes. Decrease the
5 (only in interlink connection maximum number of receivable bytes (BFM #2), and increase the pre- H
mode) liminary receive data buffer area.
Communication
Programming

6 Baud rate setting error Non-existing baud rate is specified.


7 Receiving CR error CR is not located in the specified position.
8 Receiving LF error LF is not located in the specified position.
Head sending/receiving
9
terminator setting error
The head terminator is something other than 01H to 1FH. I
Maintenance
Remote

The terminator is not located in the specified position. Or the terminator


10 Receiving terminator error
does not agree.
11 Undefined
12 Transmission order error The transmission order does not agree.

Apx.A
models
Discontinued

G-41
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Non-Protocol Communication (FX2N-232IF) 7.2 Error Codes

MEMO

G-42
FX Series PLC User's Manual - Data Communication Edition
Programming Communication

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
H. Programming Communication
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains "programming communication" provided for the MELSEC-F FX Series Programmable
Maintenance
Remote

Controllers and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

H-1
FX Series PLC User's Manual - Data Communication Edition
Programming Communication

H-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Programming Communication 1.1 Outline of System

Common Items
1. Outline
This chapter explains programming communication. B

N:N Network
1.1 Outline of System
Programming communication transfers programs and monitors devices when a PLC programming tool is
connected.
C
1) A PLC can be directly connected to the RS-232C port in a personal computer with one cable.

Parallel Link
2) Sequence programs can be transferred and devices can be monitored through the USB port in a personal
computer.
This function is not provided for the FX2(FX) and FX2C Series.
3) Sequence programs can be transferred and devices can be monitored through the Ethernet port in a
personal computer. D
This function is provided for the FX3S, FX3G, FX3GC, FX3U and FX3UC Series.

Computer Link
4) It is possible to monitor devices using one programming tool, and change programs using another
programming tool.
This function is not provided for the FX2(FX), FX2C and FX0N Series.
5) Two HMIs or one HMI and one programming tool can be connected at the same time.
This function is not provided in the FX2(FX), FX2C and FX0N Series. E

Communication
Inverter
Important points and reference
System chapter/section

FX PLC

For communication
equipment and PLC
........ applicability, refer to
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Chapter 1.

Communication Communication
Standard equipment Standard equipment Ethernet
built-in port operating in built-in port operating in For selection, refer to
adapter ........ Chapter 2.
(RS-422) accordance with (USB) accordance with
RS-422 USB
G

(FX2N-232IF)
Communication
Non-Protocol
For combinations of cables
and converters, refer to
........ Chapter 3.
Cable selection
RS-232C/RS-422 converter

For cable connection


diagrams, refer to Chapter 4.
H
Communication
Programming

RS-422 RS-232C USB USB USB Ethernet


I
Maintenance
Remote

Personal computer
Applicable software ........ For software and tools for
sequence programs, refer to
Peripheral
GX Works2
GX Developer
Chapter 1. Apx.A
equipment
FXGP/WIN
models
Discontinued

H-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Programming Communication 1.2 Procedures Before Operation

1.2 Procedures Before Operation


The flow chart below shows the programming communication setting procedures up until data link:

Sequence programming

Refer to Chapter 1

Outline Outline of system


Applicable PLC
Applicable programming tools
Refer to Chapter 2

Determine system configuration and selection System configuration


Standard built-in port (provided)
Selecting communication equipment operating
Refer to Chapter 3 in accordance with RS-422/RS-232C/USB/Ethernet
Cautions on configuration
Connection configuration Selecting connection cables
Selecting cable for each communication
Refer to Chapter 4 equipment

Connection cable connection Connection cable connection diagram

Programming tool

Connect PLC*1

Refer to Chapter 5
Perform PLC communication setting
(initialization). PLC serial communication setting
Communication setting is not necessary.
(Confirm that setting is provided.)
Refer to Chapter 6

Set personal computer connection. Setting connection of Windows software


Communication port for connecting
personal computer
Selecting the baud rate
Ethernet port setting
Communication test
Windows software (GX Works2, GX Developer)
Setting is not required in programming
Based on SD/RD lamp lighting status and tool.
contents of error check devices,verify that
communication is being executed normally. In added communication extension
equipment, standard built-in port is not
If there are problems, refer to the troubleshooting
provided.
(Chapter 7).

*1 For the programming tool to PLC connection procedure, refer to the Programming Communication section in this manual
or the respective programming tool manual.
For details on operation methods, refer to the respective programming tool manual.

H-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Programming Communication 1.3 Communication Type Applicability in PLC

A
1.3 Communication Type Applicability in PLC

Common Items
1.3.1 Applicable PLC
The table below shows communication ports applicable in each PLC. B
: Applicable (If applicable versions of main units are limited, they are described inside ( ).)

N:N Network
: Not applicable
Optional Optional Optional
Standard communication communication
Standard communication
built-in equipment equipment equipment
built-in
PLC
port in operating in
accordance accordance
operating in port in operating in
accordance accordance accordance
Ethernet
adapter
Remarks C
with

Parallel Link
with RS-422 with RS-232C with USB with USB
RS-422
(-BD) (-BD) (ADP) (-BD)*1

FX3UC(D, DS,
(Ver. 3.10
DSS) Series
or later)

D
FX3UC-32MT-

Computer Link
(Ver. 3.10
LT(-2)
or later)

FX3U Series (Ver. 3.10
or later)

E

Communication
Inverter
FX3GC Series (Ver. 2.00
or later

FX3G Series (Ver. 2.00
or later
FX3S Series *2 F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX2NC Series
FX2N Series
FX1NC Series
FX1N Series
FX1S Series G
FX0N Series

(FX2N-232IF)
Communication
Non-Protocol
FX0S Series The programming
communication
FX0 Series function is not available
FX2C Series for any optional

FX2(FX) Series
communication
equipment.
H
Communication
Programming

FX1 Series

*1. When using USB communication with a model that does not support USB communication equipment
(-BD), use the FX-USB-AW.
However, FX2(FX), FX2C and FX1 PLCs do not support the FX-USB-AW.
Use the built-in USB port in FX3S, FX3G, FX3GC PLCs. I
*2. The FX3U-ENET-ADP Ver. 1.20 or later is applicable to the FX3S PLC.
Maintenance
Remote

1.3.2 Products whose production was stopped


Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A. Apx.A
To see the latest available products, refer to the general catalog.
models
Discontinued

H-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Programming Communication 1.4 Programming Tool Applicability

1.4 Programming Tool Applicability

1.4.1 For applicable versions


The programming tool is applicable for each FX Series from the version shown:

1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
The setting of the FX3U-ENET-ADP is
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
supported in Ver. 1.73B or later.
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later
-
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC
The setting of the FX3U-ENET-ADP is
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
supported in Ver. 1.87R or later.
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later
-
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3GC PLC
The setting of the FX3U-ENET-ADP is
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
supported in Ver. 1.87R or later.
FX-30P Ver. 1.30 or later -
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 3.00 or later
FX-20P-MFXC-E
FX-10P-E Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E SW5 A or later
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later
FX-30P Ver. 1.00 or later -
FX-20P-E(-SET0)
Ver. 4.00 or later
FX-20P-MFXD-E
FX-10P-E Ver. 4.00 or later

H-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Programming Communication 1.4 Programming Tool Applicability

A
Product name Model name Applicable version Remarks

Common Items
GOT-F900 Series display units
F940WGOT-TWD-E F940WGOT-TWD-E (Ver. 1.00 or later)
F940GOT-*WD-E F940GOT-LWD-E, F940GOT-SWD-E (Ver. 1.00 or later)
F940GOT-*BD-H-E F940GOT-LBD-H-E, F940GOT-SBD-H-E (Ver. 1.00 or later)
F940GOT-*BD-RH-E F940GOT-LBD-RH-E, F940GOT-SBD-RH-E (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
B
GOT1000 Series display units

N:N Network
models and versions supporting the list editor function.

2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
The setting of the FX3U-ENET-ADP is C
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
supported in Ver. 1.90U or later.

Parallel Link
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later
-
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX3G PLC D
The setting of the FX3U-ENET-ADP is

Computer Link
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
supported in Ver. 1.90U or later.
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later
-
FX-30P Ver. 1.00 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function. E
FX3GC PLC

Communication
Inverter
The setting of the FX3U-ENET-ADP is
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
supported in Ver. 1.90U or later.
FX-30P Ver. 1.30 or later -
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units

FX3S PLC
models and versions supporting the list editor function.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
G

(FX2N-232IF)
Communication
Non-Protocol
GX Developer SWD5C(F)-GPPW-J SW2 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.00 or later
FX-PCS-KIT/98 SW1PC-FXGP/98(-3,-5) Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 4.00 or later
-
FX-PCS-KIT/V-3
FX-A7PHP-KIT
SW1PC-FXGP/V3
SW1RX-GPPFX
Ver. 2.00 or later
Ver. 3.00 or later
H
Communication
Programming

FX-30P Ver. 1.00 or later


FX-20P(-SET0)
Ver. 4.00 or later
FX-20P-MFXC
FX-10P(-SET0) Ver. 3.00 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later) I
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
Maintenance
Remote

F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)


F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.
Apx.A
models
Discontinued

H-7
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Programming Communication 1.4 Programming Tool Applicability

Product name Model name Applicable version Remarks


FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 5.00 or later
-
FX-30P Ver. 1.00 or later
FX-20P(-SET0)
Ver. 5.00 or later
FX-20P-MFXD
FX-10P(-SET0) Ver. 4.00 or later
GOT-F900 Series display units
F940WGOT-TWD F940WGOT-TWD (Ver. 1.00 or later)
F940GOT-*WD F940GOT-LWD, F940GOT-SWD (Ver. 1.00 or later)
F940GOT-*BD-H F940GOT-LBD-H, F940GOT-SBD-H (Ver. 1.00 or later)
F940GOT-*BD-RH F940GOT-LBD-RH, F940GOT-SBD-RH (Ver. 1.00 or later)
Refer to manuals of GOT1000 Series display units for applicable
GOT1000 Series display units
models and versions supporting the list editor function.

1.4.2 For non-applicable versions (setting an alternative model)


Even programming tool not applicable to a PLC can create programs when an alternative model is set.
In this case, however, programming is enabled only in the ranges provided for the alternative PLC model
such as instructions and program size.

Model to be programmed Model to be set Priority: High Low


FX3UC Series FX3UC FX2N FX2(FX)
FX3U Series FX3U, FX3UC FX2N FX2(FX)
FX3GC Series*1 FX3G, FX3GC FX1N*2 FX2N*2
FX3G Series*1 FX3G FX1N*2 FX2N*2
FX3S Series*1 FX3S FX3G FX1N*2
FX2NC Series FX2NC, FX2N FX2(FX)
FX2N Series FX2N FX2(FX)
FX1NC Series FX1NC, FX1N FX2N FX2(FX)
FX1N Series FX1N FX2N FX2(FX)
FX1S Series FX1S FX2(FX)
FX0N Series FX0N FX2(FX)
FX0S Series FX0S FX2(FX)
FX0 Series FX0 FX2(FX)
FX2C Series FX2C, FX2(FX) FX2(FX)
FX2(FX) Series FX2(FX) FX2(FX)
FX1 Series FX1

*1. When performing communication using the standard built-in USB port, use a programming tool whose
version supports the FX3G PLC.
*2. "FX2N" is selected when the FX-10P(-E) is used.

Point
In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

H-8
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.1 System Configuration

Common Items
2. System Configuration and Selection
This chapter explains the system configuration and selection of communication equipment operating in B
accordance with RS-422, RS-232C or USB and Ethernet adapter required by FX PLCs.

N:N Network
2.1 System Configuration
This section outlines the system configuration required to use programming communication.
Connect (optional) communication equipment operating in accordance with RS-422, RS-232C, USB or
C

Parallel Link
Ethernet adapter to a built-in port of the FX PLC or the FX PLC main unit.

2.1.1 For communication equipment operating in accordance with RS-422

Communication equipment operating


in accordance with RS-422
FX PLC Important point in selection Total extension
distance
D

Computer Link
1
The standard port built in a PLC is 30 m
Not used. (98' 5")
required
E

Communication
Inverter
2
This is the communication board 50 m
+ built into the PLC, reducing the
installation area. (164' 0")
Communication
board F

(RS/RS2 Instruction)
Communication
Non-Protocol
For communication equipment combinations for each FX Series, refer to the next section.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-9
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.1 System Configuration

2.1.2 For communication equipment operating in accordance with RS-232C


1 , 2 , 3 and 4 indicate the communication equipment combination patterns.

Communication equipment operating


FX PLC Important point in selection Total extension
in accordance with RS-232C distance

1
This is the communication board built 15 m
+ into the PLC, reducing the installation
(49' 2")
area.

Communication
board

2
Attach the special adapter expansion
board to the main unit, and then
15 m
+ + (49' 2")
attach the communication adapter to
the left side of the main unit.

Communication Special adapter


adapter expansion board

3
Attach the connector conversion adapter
+ + to the main unit, and then attach the 15 m
communication adapter to the left side (49' 2")
of the main unit.
Communication Connector
adapter conversion adapter

4
+ Attach the communication adapter to 15 m
the left side of the main unit. (49' 2")

Communication
adapter

For communication equipment combinations for each FX Series, refer to the next section.

2.1.3 For communication equipment operating in accordance with USB

Communication equipment operating


FX PLC Important point in selection Total extension
in accordance with USB distance

1
Not The standard port built in a PLC is 3m
+ used.
required (9' 10")

2
RD This is the communication board built 5m
+ into the PLC, reducing the installation
(16' 4")
SD

area.

Communication
board

For communication equipment combinations for each FX Series, refer to the next section.

H-10
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.1 System Configuration

A
2.1.4 For Ethernet adapter

Common Items
1 , 2 and 3 indicate the communication equipment combination patterns.

FX3U-ENET-ADP FX PLC Important point in selection Maximum


segment length*1
B
1 Attach the connector conversion

N:N Network
board to the main unit, and then 100 m
+ + attach the FX3U-ENET-ADP to (380' 1")
the left side of the main unit.

FX3U-ENET-ADP Connector
conversion board C

Parallel Link
2
Attach the connector conversion adapter
to the main unit, and then attach the 100 m
+ + FX3U-ENET-ADP to the left side (380' 1")
of the main unit.
D
FX3U-ENET-ADP Connector

Computer Link
conversion adapter

3
Attach the FX3U-ENET-ADP to 100 m
+ the left side of the main unit. (380' 1") E

Communication
Inverter
FX3U-ENET-ADP

For communication equipment combinations for each FX Series, refer to the next section. F

(RS/RS2 Instruction)
Communication
Non-Protocol
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-11
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

2.2 Applicable FX PLC and Communication Equipment


Select a communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the outside dimensions and D-SUB connector shape are different between units
shown in "FX2NC-232ADP/FX0N-232ADP". Select either one.
- Only one unit of communication equipment can be connected.
- In the FX0, FX0S and FX0N Series, only the standard built-in port (8-pin MINI-DIN) is provided.
- In the FX1, FX2(FX) and FX2C Series, only the standard built-in port (25-pin D-Sub type) is provided.
Total extension
FX Series Communication equipment (option) Check
distance

50 m
(164' 0")
FX1N-422-BD
(8-pin MINI-DIN)

15 m
(49' 2")
FX1S FX1N-232-BD
(9-pin D-Sub)
Standard built-in
port (8-pin MINI-
DIN)
+ + 15 m
(49' 2")

FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP


(9-pin D-Sub) (25-pin D-Sub)

50 m
(164' 0")
FX1N-422-BD
(8-pin MINI-DIN)

15 m
(49' 2")
FX1N FX1N-232-BD
(9-pin D-Sub)
Standard built-in
port (8-pin MINI-
DIN)
+ + 15 m
(49' 2")

FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP


(9-pin D-Sub) (25-pin D-Sub)

H-12
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance

50 m
(164' 0") B

N:N Network
FX2N-422-BD
(8-pin MINI-DIN)

15 m
(49' 2") C
FX2N

Parallel Link
FX2N-232-BD
(9-pin D-Sub)
Standard built-in
port (8-pin MINI-
DIN)

+ + 15 m D
(49' 2")

Computer Link
FX2N-CNV-BD FX2NC-232ADP FX2N-CNV-BD FX0N-232ADP
(9-pin D-Sub) (25-pin D-Sub)

E
50 m

Communication
Inverter
(164' 0")
FX3G-422-BD
(8-pin MINI-DIN)

(RS/RS2 Instruction)
Communication
Non-Protocol
15 m
(49' 2")

FX3G-232-BD
FX3S (9-pin D-SUB, male)

RS-422 Standard G
built-in port

(FX2N-232IF)
Communication
Non-Protocol
(8-pin MINI-DIN) 15 m
(49' 2")
USB Standard
built-in port FX3S-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-SUB, male)
(Mini-B)
H
Communication
Programming

Maximum
segment
length*1
100 m
FX3S-CNV-ADP FX3U-ENET-ADP
(RJ45 type modular jack)
(328' 1")
I
Maintenance
Remote

*1. Indicates the distance between the hub and a node.


The maximum distance varies depending on the Ethernet equipment used.

Apx.A
models
Discontinued

H-13
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance

50 m
(164' 0")
FX3G-422-BD
(8-pin MINI-DIN)

15 m
(49' 2")

FX3G FX3G-232-BD
(14-point,24-point (9-pin D-SUB, male)
type)

RS-422 Standard
built-in port 15 m
(8-pin MINI-DIN) (49' 2")

USB Standard FX3G-CNV-ADP FX3U-232ADP(-MB)


built-in port (9-pin D-sub, male)
(Mini-B)

Maximum
segment
length*1
100 m
FX3G-CNV-ADP FX3U-ENET-ADP (328' 1")
(RJ45 type modular jack)
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.

H-14
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

N:N Network
50 m
(164' 0")
FX3G-422-BD
(8-pin MINI-DIN)
The communication equipment works as ch1 when connected to
the option connector 1.
C
ch1

Parallel Link
15 m
FX3G (49' 2")
(40-point,60-point
type)
FX3G-232-BD
(9-pin D-Sub, male) D
The communication equipment works as ch1 when connected to

Computer Link
RS-422 Standard the option connector 1.
built-in port ch1
(8-pin MINI-DIN)

USB Standard
built-in port
15 m E
(49' 2")

Communication
Inverter
(Mini-B)

FX3G-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)

Maximum F
segment

(RS/RS2 Instruction)
Communication
Non-Protocol
length*1
100 m
FX3G-CNV-ADP FX3U-ENET-ADP (328' 1")
(RJ45 type modular jack)

*1. Indicates the distance between the hub and a node. G


The maximum distance varies depending on the Ethernet equipment used.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-15
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)
ch2

50 m
(164' 0")
FX3G-422-BD
(8-pin MINI-DIN)
The communication equipment works as ch2 when connected to
the option connector 2.
ch2

15 m
(49' 2")
FX3G-232-BD
(9-pin D-sub, male)
FX3G The communication equipment works as ch2 when connected to
(40-point,60-point the option connector 2.
type) ch1 ch2

RS-422 Standard
built-in port
(8-pin MINI-DIN)
15 m
USB Standard (49' 2")
built-in port FX3G-CNV-ADP FX3U-ADP(-MB) FX3U-232ADP(-MB)
(Where represents (9pin D-SUB, male)
(Mini-B)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.

ch1 ch2

+ + Maximum
segment
length*1
FX3G-CNV-ADP FX3U-ADP(-MB) FX3U-ENET-ADP
100 m
(When represents (RJ45 type modular jack) (328' 1")
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.

H-16
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

B
50 m

N:N Network
(164' 0")

FX3U-422-BD
(8-pin MINI-DIN)

ch1 C

Parallel Link
15 m
RD

(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)
D

Computer Link
ch1

5m
RD

FX3U SD

(16' 4")
Standard built-in
port (8-pin MINI- FX3U-USB-BD E
(USB Mini-B connector)

Communication
Inverter
DIN)
ch1

+ 15 m
(49' 2") F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)

ch1
Maximum
G
+
segment
length*1

(FX2N-232IF)
Communication
Non-Protocol
100 m
(328' 1")
FX3U-CNV-BD FX3U-ENET-ADP
(RJ45 type modular jack)
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-17
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch1 ch2

+
RD

SD

15 m
(49' 2")
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV).

When a FX3U-8AV-BD is used, it occupies one communication port


channel.

ch1 ch2

FX3U
+ + 15 m
(49' 2")
Standard built-in FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
port (8-pin MINI-
FX3U-CF-ADP
DIN)
When a FX3U-CF-ADP is used, it occupies one communication port
channel.
ch1 ch2

+ + Maximum
segment
length*1
100 m
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-ENET-ADP
FX3U-485ADP(-MB), (RJ45 type modular jack) (328' 1")
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

15 m
(49' 2")
FX1NC
Standard built-in FX2NC-232ADP FX0N-232ADP
port (8-pin MINI- (9-pin D-Sub) (25-pin D-Sub)
DIN)

15 m
(49' 2")
FX2NC
Standard built-in FX2NC-232ADP FX0N-232ADP
port (8-pin MINI- (9-pin D-Sub) (25-pin D-Sub)
DIN)
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.

H-18
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)

ch1

B
15 m

N:N Network
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2) C

Parallel Link
ch1 ch2

FX3GC

Standard built-in
+ 15 m
(49' 2")
port (8-pin MINI-
DIN) D
FX3U-ADP(-MB) FX3U-232ADP(-MB)

Computer Link
(Where represents (9-pin D-Sub, male)
USB Standard 232 and 485).
built-in port
(Mini-B) ch1 ch2

Maximum
E
+ segment

Communication
Inverter
length*1
100 m
FX3U-ADP(-MB) FX3U-ENET-ADP
(328' 1")
(Where represents (RJ45 type modular jack)
232 and 485).
*1. Indicates the distance between the hub and a node. F
The maximum distance varies depending on the Ethernet equipment used.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-19
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)

ch1

15 m
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)


ch1 ch2

+ 15 m
FX3UC (49' 2")
(D, DS, DSS) FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
Standard built-in FX3U-CF-ADP
port (8-pin MINI- When a FX3U-CF-ADP is used, it occupies one communication port
DIN) channel.
ch1 ch2

+ Maximum
segment
length*1
FX3U-232ADP(-MB), FX3U-ENET-ADP
100 m
FX3U-485ADP(-MB), (RJ45 type modular jack) (328' 1")
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.

H-20
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

B
50 m

N:N Network
(164' 0")

FX3U-422-BD
(8-pin MINI-DIN)

ch1 C

Parallel Link
15 m
RD

(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)
D

Computer Link
ch1

5m
RD

FX3UC-32MT-LT SD

(-2) (16' 4")

Standard built-in FX3U-USB-BD E


(USB Mini-B connector)

Communication
Inverter
port (8-pin MINI-
DIN)
ch1

+ 15 m
(49' 2") F

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)

ch1
Maximum
G
+
segment
length*1

(FX2N-232IF)
Communication
Non-Protocol
100 m
(328' 1")
FX3U-CNV-BD FX3U-ENET-ADP
(RJ45 type modular jack)
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-21
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.2 Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)

ch1 ch2

+
RD

SD

15 m
(49' 2")
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication port
channel.

ch1 ch2

+ Maximum
RD

SD

segment
length*1
100 m
FX3U--BD FX3U-ENET-ADP
(Where represents (RJ45 type modular jack) (328' 1")
232, 422, 485, USB and 8AV).
When a FX3U-8AV-BD is used, it occupies one communication port
FX3UC-32MT-LT channel.
(-2) ch1 ch2

Standard built-in
port (8-pin MINI-
DIN) + + 15 m
(49' 2")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.
ch1 ch2

+ + Maximum
segment
length*1
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-ENET-ADP 100 m
FX3U-485ADP(-MB), (RJ45 type modular jack) (328' 1")
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.
*1. Indicates the distance between the hub and a node.
The maximum distance varies depending on the Ethernet equipment used.

H-22
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.3 Caution on Selection

A
2.3 Caution on Selection

Common Items
Some caution should be observed when using a programming tool with optional FX PLC communication
equipment.
Consider the following contents during selection.
B
2.3.1 When using 422BD

N:N Network
1. Current consumption at 5V DC of the expansion board
When the 422BD is attached to a PLC, it consumes the following current:
1) For FX3U and FX3UC-32MT-LT(-2) PLCs C
The FX3U-422-BD consumes 20 mA at 5V DC from the FX3U/FX3UC-32MT-LT(-2) PLC.

Parallel Link
2) For FX2N PLCs
The FX2N-422-BD consumes 60 mA at 5V DC from the FX2N PLC.

2. Current consumption of the special extension equipment and peripheral equipment


Make sure that the current consumption at 5V DC including the 422BD described above, special extension
equipment, and peripheral equipment shown below does not exceed the power capacity at 5V DC in the
D

Computer Link
FX2N/FX3U/FX3UC PLC.
Current con-
Peripheral equipment Connection cable sumption at
5V DC*1
FX-30P 115 mA*2 E
FX-20P(-E) FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP 180 mA

Communication
Inverter
FX-10P(-E) 120 mA
<F2-232CAB (for 25-pin D-Sub), F2-232CAB-1 (for 9-pin D-Sub)
or F2-232CAB-2 (for 14-pin half-pitch)> 220 mA
+ FX-232AW(C) + FX-422CAB0
<F2-232CAB (for 25-pin D-Sub), F2-232CAB-1 (for 9-pin D-Sub) F
Personal computer or F2-232CAB-2 (for 14-pin half-pitch)> 120 mA

(RS/RS2 Instruction)
Communication
Non-Protocol
(for programming) + FX-232AWC-H + FX-422CAB0
USB cable
(for connecting personal computer: A plug)
15 mA
(for connecting FX-USB-AW: USB Mini-B plug)
+ FX-USB-AW
FX-10DU(-E) FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP 220 mA
G

(FX2N-232IF)
Communication
Non-Protocol
FX-20DU(-E) FX-20DU-CAB0 180 mA
FX-10DM(-E) FX-20P-CAB0 or FX-20P-CAB + FX-20P-CADP 220 mA
FX-25DU(-E), FX-30DU(-B)(-E), FX-50DU-CAB0(-1M, -10M, -20M, -30M) 0 mA
FX-40DU(-B)(-ES), FX-40DU-TK(B)(-E),
FX-40DU-CAB(-10M, -20M, -30M) + FX-422AW0 160 mA
FX-50DU-TK(S)(-E), and ET-50 Series
F940GOT-SWD(LWD)(-E),
H
Communication
Programming

F930GOT-BWD(-E), ET-940 Series FX-50DU-CAB0(-1M, -10M, -20M, -30M, L) 0 mA


F930GOT-BBD-K(-E), and F920GOT-BBD-K
F9GT-H(RH)CAB2-150 + F9GT-H(RH)CAB-3M(-10M) or F9GT-
F940 Handy GOT (RH type) 0 mA
HCAB-3M(-10M) + F9GT-HCNB + FX-50DU-CAB0(-1M)
F920GOT-BBD5-K
F920 Handy GOT RH type
FX-50DU-CAB0(-1M)
F9GT-HCAB2-150, F9GT-HCAB-3M(-10M)
220 mA
0 mA
I
Maintenance
Remote

GOT-A900 Series (CPU direct connection type) FX9GT-CAB0(-150,-10M) 0 mA


GOT1000 Series (CPU direct connection type) GT01-CR4-8P (Where represents 10, 30, 100, or 300.) 0 mA
GOT1000 Series
GT10-CR4-8P (Where represents 10, or 30.) 220 mA
(GT10 5V DC power supply type)

*1. The power consumption of the FX3U-422-BD and FX2N-422-BD is not included.
Apx.A
models
Discontinued

*2. When the intensity of the LCD backlight is set at the initial value 4.
If the LCD backlight is set at the maximum value 8, it is handled as "155mA".

H-23
FX Series PLC User's Manual - Data Communication Edition 2 System Configuration and Selection
Programming Communication 2.3 Caution on Selection

3. Connection of the FX-2PIF


The FX-2PIF cannot be connected to the 422BD.
Connect it to the standard port.

2.3.2 When using 232BD or 232ADP


When the 232BD or 232ADP is attached to a PLC, it consumes the current shown in the table below. Make
sure that the power capacity of 5V DC in the FX1NC, FX2N, FX2NC, FX3U and FX3UC PLCs is not exceeded.
: Applicable
: Not attachable
FX3UC FX3UC
Power consumption
Model name FX1NC FX2N FX2NC FX3U (D, DS, (LT,
at 5 VDC
DSS) LT(-2))
FX3U-232-BD 20 mA
FX2N-232-BD 20 mA
FX3U-232ADP(-MB) 30 mA
FX2NC-232ADP 100 mA
FX0N-232ADP 200 mA

2.3.3 Other cautions

1. For FX1S, FX1N, FX1NC and FX2N (whose version is before Ver. 2.00) PLCs
1) Verify that the communication format is in the initial status (D8120 = K0).
Check the communication parameters using the peripheral equipment.
If the communication is set so that non-protocol procedure (RS instruction) or a dedicated protocol is
used, clear the setting to "0" using the peripheral equipment.
2) If RS instruction is used in the program, delete it, turn OFF the PLC power, and then turn it ON again.

2. For FX2N (Ver. 2.00 or later) and FX2NC (versions earlier than Ver. 3.00) PLCs
1) Verify that the communication format is in the initial status (D8120 = K0).
Check the communication parameters using the peripheral equipment.
If the communication is set so that non-protocol procedure (RS instruction) or a dedicated protocol is
used, clear the setting to "0" using the peripheral equipment.
2) If RS instruction is used in the program, do not execute it. If it is executed, the PLC operates according to
RS instruction.

3. For FX2N (Ver. 3.00 or later) and FX2NC (Ver. 3.00 or later) PLCs
1) Verify that the communication format is in the initial status (D8120 = K0).
Check the communication parameters using the peripheral equipment.
If the communication is set so that non-protocol procedure (RS instruction) or a dedicated protocol is
used, clear the setting to "0" using the peripheral equipment.
2) If RS instruction is used in the program, do not execute it. If it is executed, the PLC operates according to
RS instruction.
3) If EXTR instruction is used in the program, delete it, turn OFF the PLC power, and then turn it ON again.

4. For FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs


1) Verify that the communication format for the communication port used in programming communication is
set correctly (D8370, D8120, D8400, D8420 = K0).
Check whether the communication parameters are set correctly using the peripheral equipment.
2) Verify that the RS or RS2 instructions are not executed in the program for the communication port used in
programming communication.
Do not execute RS and RS2 instructions.
3) If an inverter communication instruction is used in the program for the communication port used in
programming communication, delete it, turn OFF the PLC power, and then turn it ON again.

5. Connection of (5V power type) GOT unit


When using the (5V power type) GOT unit together with the FX3S, FX3G PLC, connect only one GOT unit to
either the standard built-in port (RS-422) or the FX3G-422-BD. It is not allowed to connect two GOT units to
the FX3S, FX3G PLC at the same time.

H-24
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.1 Connection Procedure

Common Items
3. Selecting Connection Cables
This chapter explains the connection cable selection method. B

N:N Network
3.1 Connection Procedure

1 Checking the connector shape C

Parallel Link
Check the shape (male or female, etc.) of the connector of the connected programming tool (such
as personal computer) and the shape of the connector of the PLC, and verify that connection is
possible.

2 Connecting the cable connector to the programming tool D

Computer Link
Check the shape of the cable connector for the programming tool, and connect the cable correctly.

3 Connecting the cable connector to the PLC


Check the cable connector for the PLC, and connect the cable correctly. The cable connector has
one of the following shapes:
E

Communication
Inverter
- 8-pin MINI-DIN, male
- 25-pin D-Sub, male
- 9-pin D-Sub, female
- USB Mini-B plug
- RJ45 type modular F

(RS/RS2 Instruction)
Communication
Non-Protocol
1. Selecting a connection cable
According to the combination of the connected programming tool and PLC (communication equipment),
select the proper cable.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-25
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.2 Connector Shape in Each Product

3.2 Connector Shape in Each Product

Model name (series) Connector shape Model name (series) Connector shape
PLC Handy programming panel

13 1 5
FX-10P(-E), 4 8
FX1, FX2(FX) and FX2C FX-10P-SET0(-E), 2
PLCs 25 14 1 7
FX-20P(-E),
25-pin D-Sub,
female
FX-20P-SET0(-E), 3 6
FX-30P 8-pin MINI-DIN,
5 female
FX0, FX0S, FX0N, FX1S, 4 8
Personal computer
FX1N, FX1NC, FX2N, 2
1 7
FX2NC, FX3S, FX3G, 5 1
FX3GC, FX3U and 3 6
FX3UC PLCs 8-pin MINI-DIN,
female 9 6
9-pin D-Sub,
male

FX3S, FX3G, FX3GC PLCs


USB Mini-B PC-AT compatible
connector
machine
USB A connector
PLC (communication equipment)

5
4 8
FX1N-422-BD
FX2N-422-BD 2
1 7
FX3G-422-BD 8 1
FX3U-422-BD 3 6 RJ45 type modular jack
8-pin MINI-DIN,
female 7 1

13 1
14 8
14-pin Half-
FX0N-232ADP pitch, female
25 14
25-pin D-Sub, PC-9800 Series (NEC)
female 13 1
FX1N-232-BD
5 1
FX2N-232-BD 25 14
FX3G-232-BD 25-pin D-Sub,
female
FX3U-232-BD 9 6
FX2NC-232ADP 9-pin D-Sub,
FX3U-232ADP(-MB) male

FX3U-USB-BD
USB Mini-B
connector

FX3U-ENET-ADP
8 1
RJ45 type modular jack

H-26
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.3 Combinations of Connection Cables

A
3.3 Combinations of Connection Cables

Common Items
3.3.1 Handy programming panel

Programming tool
Cable combination
PLC connector Cable B
connector shape shape length

N:N Network
Standard built-in port
FX1N-422-BD
FX2N-422-BD
FX3G-422-BD
RS-422 RS-422 FX3U-422-BD
5 1.5 m
C

Parallel Link
4 8 (4' 11")
FX-20P-CAB0 [1.5 m (4' 11")]
... sold separately 2
1 7

3 6
P/I

8-pin MINI-DIN,

FX-10P(-E)
female
D
Standard built-in port

Computer Link
FX-20P(-E)
RS-422 RS-422 5
5 4 8
4 8
2 1.8 m
2 1 7
1 7 FX-20P-CAB [1.5 m (4' 11")] FX-20P-CADP
(5' 10")
3 6
3 6
... supplied with [0.3 m (0' 11")] ...
sold separately
8-pin MINI-DIN,
E
8-pin MINI-DIN,

Communication
Inverter
female
female
Standard built-in port
RS-422 RS-422
13 1
1.5 m
(4' 11")
FX-20P-CAB [1.5 m (4' 11")]
... supplied with
25
25-pin D-Sub,
14
F
female

(RS/RS2 Instruction)
Communication
Non-Protocol
Standard built-in port
FX1N-422-BD
FX2N-422-BD
FX3G-422-BD
RS-422 RS-422 FX3U-422-BD G
5 1.5 m

(FX2N-232IF)
Communication
Non-Protocol
4 8 (4' 11")
FX-20P-CAB0 [1.5 m (4' 11")]
FX-10P-SET0(-E) ... supplied with 2
1 7
FX-20P-SET0(-E)
FX-30P 3 6
8-pin MINI-DIN,
5
4 8 female H
2 Standard built-in port
Communication
Programming

1 7 RS-422 RS-422
13 1
3 6 1.5 m
8-pin MINI-DIN,
25 14 (4' 11")
female FX-20P-CAB [1.5 m (4' 11")]
... sold separately 25-pin D-Sub,
female
I
Maintenance
Remote

Apx.A
models
Discontinued

H-27
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.3 Combinations of Connection Cables

3.3.2 Personal computer

Programming tool PLC connector Cable


Cable combination
connector shape shape length
Standard built-in
port
FX1N-422-BD
RS-232C RS-422 FX2N-422-BD
FX3G-422-BD
FX3U-422-BD
4.5 m
F2-232CAB-1 [3 m (9' 10")] 5
FX-422CAB0
4 8 (14' 9")
... sold separately [1.5 m (4' 11")] ...
FX-232AW
sold separately 2
FX-232AWC 7
FX-232AWC-H 1
3 6
8-pin MINI-DIN,
female

RS-232C RS-422 Standard built-in


PC-AT compatible
machine port
3.3 m
- DOS/V personal 13 1
F2-232CAB-1 [3 m (9' 10")] (10' 9")
computer FX-422CAB
... sold separately [0.3 m (0' 11")] 4.5 m
- Windows personal FX-232AW
FX-232AWC
... sold separately 25 14 (14' 9")
computer FX-422CAB-150 25-pin D-Sub,
FX-232AWC-H [1.5 m (4' 11")] female
... sold separately
5 1
FX1N-232-BD
FX2N-232-BD
9 6 FX3G-232-BD
9-pin D-Sub, FX3U-232-BD
male
RS-232C RS-232C FX2NC-232ADP
FX3U-232ADP 3m
(-MB) (9' 10")
FX-232CAB-1 [3 m (9' 10")]
... sold separately 5 1

9 6
9-pin D-Sub,
male

FX0N-232ADP
RS-232C RS-232C 13 1
3m
F2-232CAB-1 [3 m (9' 10")] 25 14 (9' 10")
... sold separately 25-pin D-Sub,
female

H-28
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.3 Combinations of Connection Cables

A
Programming tool PLC connector Cable

Common Items
Cable combination
connector shape shape length
Standard built-in
port
FX1N-422-BD
RS-422
USB FX2N-422-BD
FX3U-422-BD
B

N:N Network
5 3m
USB cable [3 m (9' 10")] 4 8 (9' 10")
... supplied with
2
1 7
FX-USB-AW
PC-AT compatible 3 6
machine 8-pin MINI-DIN,
female
C
- Windows personal

Parallel Link
computer FX3U-USB-BD
USB USB 3m
(9' 10")

USB cable [3 m (9' 10")] USB Mini-B


5m

USB A connector
... supplied with connector (16' 4")
Maxi-
D

Computer Link
mum

Standard built-in
USB USB port

GT09-C30USB-5P [3 m (9' 10")]... sold separately


3m E
USB Mini-B
(9' 10")

Communication
Inverter
To be purchased from Mitsubishi Electric System & Service
MR-3JUSBCBL3M [3m (9' 10")]...sold separately connector

PC-AT compatible Ethernet Ethernet


machine
FX3U-ENET-ADP F

(RS/RS2 Instruction)
Communication
Non-Protocol
Straight cable Hub Straight cable
-
A cross cable can also be used when using direct connection (simple 8 1
connection) between the personal computer and the Ethernet adapter. RJ45 type
8 1 modular jack
RJ45 type modular jack
Cross cable G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-29
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.3 Combinations of Connection Cables

Programming tool PLC connector Cable


Cable combination
connector shape shape length
Standard built-in
port
FX1N-422-BD
RS-232C RS-422 FX2N-422-BD
FX3G-422-BD
FX3U-422-BD
F2-232CAB-2 [3 m (9' 10")] 4.5 m
FX-422CAB0 5
... sold separately 4 8 (14' 9")
FX-232AW [1.5 m (4' 11")] ...
sold separately
FX-232AWC 2
1 7
FX-232AWC-H
3 6
8-pin MINI-DIN,
female

RS-232C RS-422 Standard built-in


PC-9800 Series port
3.3 m
(NEC) 13 1
F2-232CAB-2 [3 m (9' 10")]
FX-422CAB
(10' 9")
- Notebook type ... sold separately 4.5 m
FX-232AW [0.3 m (0' 11")]
personal computer ... sold separately 25 14 (14' 9")
FX-232AWC
FX-422CAB-150 25-pin D-Sub,
FX-232AWC-H [1.5 m (4' 11")] female
7 1 ... sold separately

FX1N-232-BD
14 8 FX2N-232-BD
14-pin Half- FX3G-232-BD
pitch, female
FX3U-232-BD
RS-232C RS-232C FX2NC-232ADP
FX3U-232ADP 3m
(-MB) (9' 10")
FX-232CAB-2 [3 m (9' 10")]
... sold separately 5 1

9 6
9-pin D-Sub,
male

FX0N-232ADP
RS-232C RS-232C 13 1
3m
25 14 (9' 10")
F2-232CAB-2 [3 m (9' 10")]
... sold separately 25-pin D-Sub,
female

H-30
FX Series PLC User's Manual - Data Communication Edition 3 Selecting Connection Cables
Programming Communication 3.3 Combinations of Connection Cables

A
Programming tool PLC connector Cable

Common Items
Cable combination
connector shape shape length
Standard built-in
port
FX1N-422-BD
RS-232C RS-422 FX2N-422-BD
FX3G-422-BD
B

N:N Network
FX3U-422-BD
4.5 m
F2-232CAB [3 m (9' 10")] 5
FX-422CAB0 4 8 (14' 9")
... sold separately [1.5 m (4' 11")] ...
FX-232AW 2
sold separately 7
FX-232AWC 1
FX-232AWC-H
3 6 C
8-pin MINI-DIN,

Parallel Link
female

RS-232C RS-422 Standard built-in


PC-9800 Series port
3.3 m
(NEC)
- Desktop type
F2-232CAB [3 m (9' 10")]
FX-422CAB
13 1
(10' 9") D
... sold separately [0.3 m (0' 11")] 4.5 m

Computer Link
personal computer FX-232AW 25 14
FX-232AWC
... sold separately (14' 9")
FX-422CAB-150 25-pin D-Sub,
FX-232AWC-H [1.5 m (4' 11")] female
13 1 ... sold separately

FX1N-232-BD
25 14
25-pin D-Sub,
FX2N-232-BD E
female FX3G-232-BD

Communication
Inverter
FX3U-232-BD
RS-232C RS-232C FX2NC-232ADP
FX3U-232ADP 3m
(-MB) (9' 10")
F2-232CAB-1 [3 m (9' 10")]
5 1
... sold separately
F

(RS/RS2 Instruction)
Communication
Non-Protocol
9 6
9-pin D-Sub,
male

FX0N-232ADP
RS-232C RS-232C 13 1
3m G
(9' 10")

(FX2N-232IF)
Communication
Non-Protocol
F2-232CAB [3 m (9' 10")] 25 14
... sold separately 25-pin D-Sub,
female

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-31
FX Series PLC User's Manual - Data Communication Edition 4 Connection Cables and Interfaces
Programming Communication 4.1 Simplified Tables

4. Connection Cables and Interfaces

4.1 Simplified Tables

4.1.1 Cable connector shape correspondence table


From the shape of connectors at both ends of a cable, the cable model name can be known.
A Side B Side

B Side 3
4 6 1 5 1 13 13 1
1
2 7
6 9 14 25 25 14
8 USB Mini-B plug
5 9-pin D-Sub, 25-pin D-Sub, 25-pin D-Sub,
8-pin MINI-DIN, female male female
A Side
male

3
4 6
1 FX-20P-CAB
2 7 FX-20P-CAB0 FX-20P-CADP
FX-422CAB0
8
5
8-pin MINI-DIN,
male

FX-USB-AW

USB Mini-B (converter)
connector

USB cable
Provided as an
accessory of FX-
USB-AW and
USB A plug FX3U-USB-BD
GT09-C30USB-5P
MR-J3USBCBL3M

1 5

FX-232CAB-1 F2-232CAB-1
6 9
9-pin D-Sub,
female

1 7

FX-232CAB-2 F2-232CAB-2
8 14
14-pin Half-
pitch, male

1 13

F2-232CAB-1 F2-232CAB
14 25
25-pin D-Sub,
male

H-32
FX Series PLC User's Manual - Data Communication Edition 4 Connection Cables and Interfaces
Programming Communication 4.1 Simplified Tables

A
4.1.2 Cable combination simplified table

Common Items
From the shape of the programming tool connector and PLC connector, combinations of the cable, converter
and communication equipment can be checked.
Interface RS-422 RS-232C USB Ethernet
FX0,FX0S, B
FX0N,FX1S,

N:N Network
FX1N,FX1NC,
FX1,FX2(FX), FX3S, FX3G,
Standard port FX2N,FX2NC,
FX2C,A,QnA FX3GC
FX3S,FX3G,
FX3GC,FX3U,
FX3UC
FX1N-232-BD
C

Parallel Link
FX1N-422-BD FX2N-232-BD
FX3G-232-BD
Communication FX2N-422-BD
FX3U-232-BD FX0N-232ADP FX3U-USB-BD FX3U-ENET-ADP
equipment FX3G-422-BD
FX2NC-232ADP
FX3U-422-BD FX3U-232ADP
(-MB)
Connector in PLC D

Computer Link
5
4 8 13 1 5 1 13 1
2
1 7
25 14 9 6 25 14 USB Mini-B 8 1
3 6
8-pin MINI-DIN,
25-pin D-Sub,
female
9-pin D-Sub,
male
25-pin D-Sub,
female
connector RJ45 type
modular jack
E
female

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-33
FX Series PLC User's Manual - Data Communication Edition 4 Connection Cables and Interfaces
Programming Communication 4.1 Simplified Tables

Interface RS-422 RS-232C USB Ethernet

5 FX-20P-CAB0
4 8
2 or
1 7 FX-20P-CAB
3 6 FX-20P-CAB
+
8-pin MINI-DIN,
female FX-20P-CADP

FX-USB-AW*1 USB cable (included)


+ GT09-C30USB-5P*2

USB cable or
USB A connector (included) MR-J3USBCBL3M*2

F2-232CAB-1
F2-232CAB-1 +
5 1 + FX-232AW
FX-232AW FX-232AWC
FX-232AWC FX-232AWC-H FX-232CAB-1 F2-232CAB-1
9 6 FX-232AWC-H +
Connector in programming tool

9-pin D-Sub,
male + FX-422CAB
FX-422CAB0 or
FX-422CAB-150
F2-232CAB-2
F2-232CAB-2 +
7 1 + FX-232AW
FX-232AW FX-232AWC
FX-232AWC FX-232AWC-H FX-232CAB-2 F2-232CAB-2
14 8 +
FX-232AWC-H
14-pin Half-
pitch, female + FX-422CAB
FX-422CAB0 or
FX-422CAB-150
F2-232CAB
F2-232CAB +
13 1 + FX-232AW
FX-232AW FX-232AWC
FX-232AWC FX-232AWC-H F2-232CAB-1 F2-232CAB
25 14
FX-232AWC-H +
25-pin D-Sub,
female + FX-422CAB
FX-422CAB0 or
FX-422CAB-150

Cable
conforming to
Ethernet
8 1 standard
RJ45 type practice
modular jack

*1. FX3S, FX3G, FX3GC PLC is not applicable.


*2. For the standard built-in port (USB) in the FX3S, FX3G, FX3GC PLC, use the GT09-C30USB-5P or MR-
J3USBCBL3M.

H-34
FX Series PLC User's Manual - Data Communication Edition 4 Connection Cables and Interfaces
Programming Communication 4.2 Cable Connection Diagrams

A
4.2 Cable Connection Diagrams

Common Items
This section explains cable connection diagrams required for connection.

4.2.1 Personal computer connection cable - No. A


B
: Female type : Male type The connector shape indicates the engagement surface.

N:N Network
No. Cable model name Application Connection diagram Application

RS-232C Personal computer 1 1 Communication port


connection connector 2 2 connector
1 13 3 3 1 13
A-1 F2-232CAB 5
6
5
6
C

Parallel Link
14 25 7 7 14 25
25-pin D-Sub, male 20 20 25-pin D-SUB, male

RS-232C 1 4
Personal computer 5
connection connector Communication port
2 2 connector
5 1 3 3 1 13
Commercial cable*1
A-2 Reverse (cross) type 4
5
6
7
D

Computer Link
9 6 6 20 14 25
9-pin D-Sub, female 7 8 25-pin D-Sub, male
8 1
*1 Interlink supporting cables are not applicable. SHELL SHELL

RS-232C Personal computer 1 Shield Communication port


connection connector
1
connector
13 2
3
2
3
5 1 E
A-3 F2-232CAB-1 5

Communication
Inverter
8
6 4
14 25 9 6
7 5
25-pin D-Sub, male 20 9-pin D-Sub, female
6

RS-232C 1 2
Personal computer 2 20 Communication port
connection
1
connector
7
4
9 3
1
connector
13 F
A-4 F2-232CAB-2

(RS/RS2 Instruction)
Communication
Non-Protocol
11 5
6
8 14 14 7 14 25
14-pin Half-pitch 12 25-pin D-Sub, male
13

RS-232C Personal computer Communication port


connection
5
connector
1
2
3
2
3 5
connector
1
G
6 6
A-5 FX-232CAB-1

(FX2N-232IF)
Communication
Non-Protocol
8 8
5 5
9 6 4 4 9 6
9-pin D-Sub, female 9-pin D-Sub, female

RS-232C 1 7
Personal computer
connection
5
connector
1
2
8
3 Communication port
connector
H
3 2
Commercial cable*1
Communication
Programming

4 6 5 1
A-6 Reverse (cross) type 5 5
9 6 6 4
9-pin D-Sub, female 7 1 9 6
8 9-pin D-Sub, female
*1 Interlink supporting cables are not applicable. Frame Frame

RS-232C 1 3
I
Personal computer 2 Communication port
Maintenance
Remote

connection 4
connector 4 connector
1 7 9 2 5 1
A-7 FX-232CAB-2 11 6
8
8 14 14 5 9 6
14-pin Half-pitch 12 9-pin D-Sub, female
13 Apx.A
models
Discontinued

H-35
FX Series PLC User's Manual - Data Communication Edition 4 Connection Cables and Interfaces
Programming Communication 4.2 Cable Connection Diagrams

: Female type : Male type The connector shape indicates the engagement surface.

No. Cable model name Application Connection diagram Application

RS-232C 1 3
connection Personal computer 2 4
connector 3 7 Communication port
1 7 8 connector
Commercial cable*1 4 1 5 1
Reverse (cross) type 10
A-8 8 14 9 2
14-pin Half-pitch 11 6 9 6
12 5 9-pin D-Sub, female
13
14
*1 Interlink supporting cables are not applicable. FG FG

RS-422 2 2
connection Converter 3 7
FX-232AW,FX-232AWC, 7 3 3
FX-232AWC-H 12 5 4
1 13 6
FX-422CAB0 15 1
1
16 4 7
A-9 20 6 2
14 25 8 8
24
25-pin D-Sub, male 5 5
8 8-pin MINI-DIN, male
21
18
25

RS-422 1 1
connection Converter 2 2
FX-232AW,FX-232AWC, 3 3
FX-232AWC-H 4 4
FX-422CAB [0.3 m (0' 11")] 1 13 1 13
5 5
FX-422CAB-150 [1.5 m (4' 11")] 7 7
8 8
14 25 12 12 14 25
A-10 25-pin D-Sub, male 13 13 25-pin D-Sub, male
15 15
16 16
17 17
18 18
20 20
21 21
24 24
25 25

H-36
FX Series PLC User's Manual - Data Communication Edition 4 Connection Cables and Interfaces
Programming Communication 4.2 Cable Connection Diagrams

A
4.2.2 Connector conversion cable (commercial product) - No. B

Common Items
: Female type : Male type The connector shape indicates the engagement surface.

No. Cable model name Application Connection diagram Application

RS-232C
connection
1
2
8
3 B
3 2

N:N Network
5 1 1 13
4 20
Connector conversion 5 7
B-1 cable (normal type) 6
6
9 6 7 4 14 25
9-pin D-Sub, female 8 5 25-pin D-Sub, male
9 22
FG FG C
RS-232C 12 1

Parallel Link
connection 13 14
9 2
1 3
10 4
4 5
1 7 2 6 1 13
Connector conversion
B-2 cable (normal type) 14
7
11
D
13

Computer Link
8 14 14 25
3 8
14-pin Half-pitch 25-pin D-Sub, male
6 15
5 17
11 20
7 22
8 24
SHELL SHELL E

Communication
Inverter
RS-422 2 2
connection 3 7
7 3 3
12 5 4
1 13 6
FX-20P-CADP 15 1
1
B-3 16 4 7
14 25
20
24
6
8
2
8 F
25-pin D-Sub, female 5 5

(RS/RS2 Instruction)
Communication
Non-Protocol
8 8-pin MINI-DIN, male
21
18

4.2.3 FX-10P/FX-20P/FX-30P connection cable - No. C G

(FX2N-232IF)
Communication
Non-Protocol
: Female type : Male type The connector shape indicates the engagement surface.

No. Cable model name Application Connection diagram Application


Communication port
RS-422 Programming tool connector
connection 3 1 1
4
6
2
3
2
3
3
4
6
H
C-1 FX-20P-CAB0 1 4 4
Communication
Programming

1
7 5 5 7
2 2
6 6
8 8
5 7 7 5
8-pin MINI-DIN, male 8 8
8-pin MINI-DIN, male

RS-422
connection
2 2 I
Programming tool 3 7
Maintenance
Remote

3 7 3 1 13
4 5 12
6 1 15
1 4 16
C-2 2
7
6 20
14 25
FX-20P-CAB 25-pin D-Sub, male
8 8 24
5
8-pin MINI-DIN, male
4
8
Apx.A
models
Discontinued

21
13
17

H-37
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
Programming Communication 5.1 Check Procedure

5. Communication Setting (Initialization) in FX


Programmable Controller
This chapter explains the communication setting method for executing programming communication using
optional communication equipment operating in accordance with RS-422, RS-232C or USB.
For program communication settings in the FX3U-ENET-ADP, refer to the FX3U-ENET-ADP User's Manual.
The setting described here is not required when the standard built-in port*1 is used.
When using this communication function in an FX1S, FX1N, FX1NC, FX2N or FX2NC PLC, check D8120 using
the following procedure.
When using this communication function in ch1 in an FX3S, FX3G, FX3GC, FX3U or FX3UC PLC, check D8120
and D8400 using the following procedure.
When using this communication function in ch2 in an FX3G, FX3GC, FX3U or FX3UC PLC, check D8420 using
the following procedure.
*1. When using the standard built-in port for non-protocol communication (RS2 instruction) in an FX3G or
FX3GC PLC, connect the programming software to the standard built-in USB port.

5.1 Check Procedure

1 Monitoring D8120 (D8400, D8420)


Turn ON the PLC power while it is in STOP mode, and monitor D8120 (D8400, D8420).
1. When the value of D8120 (D8400, D8420) is "0"
The communication setting is not provided.
2. When the value of D8120 (D8400, D8420) is any value other than "0"
The communication setting is provided.

2 Checking absence/presence of the parameter setting


Check absence/presence using GX Works2, GX Developer, FXGP/WIN or FX-30P.
1) GX Works2 operating procedure (For details, refer to Section 5.2.)
2) FXGP/WIN operating procedure (For details, refer to Section 5.3.)
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

3 Checking absence/presence of sequence program setting


Check whether or not a write instruction is programmed for D8120 (D8400, D8420).
1. When such an instruction is programmed
Program example: (for D8120)
Change the program as shown below, and then change the PLC mode from STOP to RUN.
M8002 FNC 12
MOV H23F6 D8120 Program example
Initial pulse
The value varies depending on
the communication setting.

M8002 FNC 12
MOV H0000 D8120 Changed program
Initial pulse

2. When such an instruction is not programmed


Proceed to the next step.

4 Monitor D8120 (D8400, D8420) again, and confirming that its value is "0"

H-38
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
Programming Communication 5.2 Communication Setting Using Parameter Method (GX Works2)

A
5.2 Communication Setting Using Parameter Method (GX Works2)

Common Items
Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with GX Works2.
For details on FXGP/WIN operating procedure, refer to section 5.3. B
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

N:N Network
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.
For details on FX3U-ENET-ADP, refer to FX3U-ENET-ADP User's Manual.

5.2.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that GX Works2 is already C
started up.

Parallel Link
1 Opening the parameter setting window
In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar.
D

Computer Link
E

Communication
Inverter
2 Setting the serial communication (parameters) F

(RS/RS2 Instruction)
Communication
Non-Protocol
Click the [PLC System(2)] tab on the dialog box.
Select a channel to be used, and make sure that the "Operate Communication Setting" box is
cleared.
If a check mark is there, clear it.
Click [End]. G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

3 Writing parameters and program to the PLC Apx.A


models
Discontinued

Select [Online] [Write to PLC] from the menu bar, click [Parameter + Program], and then click
[Execute].

H-39
FX Series PLC User's Manual - Data Communication Edition 5 Communication Setting (Initialization) in FX Programmable Controller
Programming Communication 5.3 Communication Setting Using Parameter Method (FXGP/WIN)

5.3 Communication Setting Using Parameter Method (FXGP/WIN)


Communication settings may be changed via the parameter method with GX Works2, GX Developer,
FXGP/WIN for Windows and FX-30P handy programming panel. This section describes how to change
parameters with FXGP/WIN. FXGP/WIN cannot set ch2.
For details on GX Works2 operating procedure, refer to section 5.2.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.
For details on FX-30P operating procedure, refer to FX-30P Operation Manual.

5.3.1 Operating procedure


This subsection explains the serial communication setting method. Suppose that FXGP/WIN is already
started up.

1 Adjusting serial setting (parameter)


Select [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of parameter settings.

1. When there are no parameter settings


The dialog box shown below appears to indicate that there are no communication settings.
Click the [No] button.
In this case, the next step is not required.

2. When there are already parameter settings


The dialog box shown below appears to indicate that there are communication settings.
Click the [Clear] button to delete the communication settings from parameters.
Transfer parameters to the PLC using the following step.

2 Writing a sequence program (parameters) to the PLC


Select [PLC] [Transfers] [Write] from the toolbar, and click [OK] button.

H-40
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.1 Connection Setting (GX Works2)

Common Items
6. Connection Setting for Personal Computer
This chapter explains the setting method for connecting a personal computer and a PLC. B
GX Works2, GX Developer and FXGP/WIN for Windows, are applicable. The setting method is different in the

N:N Network
software packages.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

6.1 Connection Setting (GX Works2)


C

Parallel Link
GX Works2, Windows software for personal computers, has the following items to be set. Set each item
according to the connection status.
RS-232C, USB, Ethernet
Communication port
Transmission speed D

Computer Link
This setting is required to use the transparent function in the GOT (described later).
Communication time check
Number of retries

Each set item can be checked and changed on the Transfer Setup dialog box.
This section explains the setting using communication in accordance with RS-232C and USB. For connection
E

Communication
Inverter
and setting of the FX3U-ENET-ADP, refer to the FX3U-ENET-ADP User's Manual.

In the project view area of the navigation window, double-click [Connection Destination View] [Connection
destination data name] to display the dialog box shown below.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Point
Apx.A
In GX Works2, [Transfer Setup] can be selected even while the monitor function window is open.
models
Discontinued

H-41
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.1 Connection Setting (GX Works2)

6.1.1 Setting RS-232C or USB, communication port, and transmission speed


The setting procedures for RS-232C/USB, communication port and transmission speed are described below:
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

1 Displaying the "PC side I/F Serial Setting" window.


Double-click the "Serial" icon on the Transfer Setup dialog box. The window below appears.

2 Selecting "RS-232C" or "USB"


1. Connection for selecting "RS-232C (include FX-USB-AW/FX3U-USB-BD)"
Connect the PLC to the RS-232C port in the personal computer.
Connect the PLC to the USB port in the personal computer using the FX-USB-AW or FX3U-USB-BD.

2. Connection for selecting "USB"


Connect the PLC to the USB port in the personal computer using the transparent function at the USB port
in the GOT1000 Series.
Connect the standard USB port of the PLC to the USB port of the personal computer. (FX3S, FX3G, FX3GC)

Caution
For achieving communication using the standard built-in USB port, installation of the USB driver is required.
For the USB driver installation method and procedure, refer to the following manual.
For details on GX Works2 operating procedure, refer to GX Works2 Version 1 Operating Manual
(Common).
For details on GX Developer operating procedure, refer to GX Developer Operating Manual
(Startup).

H-42
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.1 Connection Setting (GX Works2)

A
3

Common Items
Setting the communication port and transmission speed (when "RS-232C" is
selected in the step 2)
Set these items according to the connection status.
COM port: Select the communication port in the personal computer to be used (among B
COM1 to COM63).

N:N Network
Transmission speed:Set the communication speed with the FX PLC.
The applicable transmission speed varies depending on each FX PLC. Refer
to the table below.
Communication
FX1
FX2(FX), FX0,
FX0N FX1S
FX1N, FX2N,
FX3S*1
FX3G, FX3U, C
speed FX2C FX0S FX1NC FX2NC FX3GC*1 FX3UC*2

Parallel Link
9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
115.2 kbps






D

Computer Link
*1. For achieving communication at 38.4, 57.6, or 115.2 kbps in an FX3S, FX3G and FX3GC PLC, the
FX-232AWC-H is required.
*2. For achieving communication at 38.4, 57.6, or 115.2 kbps in an FX3U and FX3UC PLC, the
FX-232AWC-H, FX-USB-AW, or FX3U-USB-BD is required.
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-43
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.1 Connection Setting (GX Works2)

6.1.2 Setting for using GOT transparent function


Arrange the setting in accordance with the connection status of the used equipment. This subsection explains
the setting when the GOT and PLC are directly connected (by serial connection).
For the GX Developer operation procedures, refer to the GX Developer Operating Manual.

[Transparent function of the GOT1000 Series]


The following setting is required when connecting the FX3S/FX3G/FX3GC/FX3U/FX3UC PLC using the
transparent function of the GOT1000 Series.
If the following setting is not provided, a communication error will occur.

1 Displaying the "PLC side I/F Detailed Setting of GOT" window

Double-click GOT on the Transfer Setup dialog box to display the window shown below.

2 Setting the CPU unit


Set "PLC Mode" to "FXCPU", and select "via GOT(direct coupled) transparent mode".

[Transparent function of the GOT-F900 Series]


The following setting is required when connecting the FX3S/FX3G/FX3GC/FX3U/FX3UC PLC using the
transparent function of the GOT-F900 Series.

1 Displaying the "PLC side I/F Detailed Setting of GOT" window

Double-click GOT on the Transfer Setup dialog box to display the window shown below.

2 Setting the CPU unit


Set "PLC Mode" to "FXCPU", and select "via GOT(direct coupled) transparent mode".
Check "via GOT-F900 transparent mode". However, it cannot be checked if "USB" is selected on the "PC side
I/F Serial Setting" window.

H-44
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.1 Connection Setting (GX Works2)

A
6.1.3 Setting communication time check and number of retries

Common Items
The setting procedure for the communication time check and number of retries is described below:
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

1 Displaying the communication time check/number of retries setting window


B
Double-click the "No Specification" icon on the Transfer Setup dialog box. The window

N:N Network
below appears.

Parallel Link
2 Setting the communication time check and number of retries
Check at communication time: Set the time for evaluating error (1 to 9999 sec). If data from the D
PLC is not received within this time, it is regarded as error.

Computer Link
Initial value: 5 sec
Retry times:Set the number of retries to be executed when a communication error has occurred (0
to 5).
Initial value: 0
Set the items above if necessary. E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

H-45
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.2 Connection Setting (FXGP/WIN)

6.2 Connection Setting (FXGP/WIN)


FXGP/WIN, Windows software for personal computers, has the following set items. Set each item according
to the connection status.
Communication port
Transmission speed

6.2.1 Setting communication port and transmission speed


The setting procedure for the communication port and transmission speed is described below:

1 Displaying the communication port/transmission speed setting window


Select [PLC] [Ports] from the toolbar. The window below appears.

2 Setting the communication port and transmission speed


Set these items according to the connection status.
Ports: Select the communication port in the personal computer to be used (among COM1 to
COM9).
Transfer speed:Set the communication speed with the FX PLC.
The applicable transmission speed varies depending on the FX Series. Refer to
the table below.
Communication FX2(FX), FX0, FX1N, FX2N, FX3G, FX3U,
FX1 FX0N FX1S FX3S*1
speed FX2C FX0S FX1NC FX2NC FX3GC FX3UC*2
*1

9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
115.2 kbps

*1. The FX3S, FX3G and FX3GC Series cannot be selected. Select the FX1N Series, and then create the
program.
*2. The FX3U and FX3UC Series cannot be selected. Select the FX2N Series, and then create the
program.

H-46
FX Series PLC User's Manual - Data Communication Edition 6 Connection Setting for Personal Computer
Programming Communication 6.3 Communication Test (GX Works2)

A
6.3 Communication Test (GX Works2)

Common Items
GX Works2, Windows software for personal computers, has a function to test communication with PLC.
Execute the communication test using the following procedure:
This section explains the method using GX Works2.
B
1 In the project view area of the navigation window, double-click [Connection

N:N Network
Destination View] [Connection destination data name].
The window below appears.

Parallel Link
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
Caution
In GX Works2, [Transfer Setup] can be selected even while the monitor function window is open.

2 Executing the communication test


G

(FX2N-232IF)
Communication
Non-Protocol
Click [Connection test] button to execute the communication test.

OK NG
H
Communication
Programming

I
Maintenance
Remote

The communication test Verify that the connection method is correct:


finished normally - Port (COM) number in the personal computer
- Cable configuration
Apx.A
models
Discontinued

Click [OK] button.

H-47
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Programming Communication 7.1 Checking PLC Version Applicability

7. Troubleshooting
This chapter explains troubleshooting.

7.1 Checking PLC Version Applicability


When executing programming communication using an FX PLC and communication equipment operating in
accordance with RS-422 or RS-232C, verify that the FX PLC is an applicable version.
For the version applicability check, refer to Section 1.3.

7.2 Checking Programming Tool Applicability


Verify that the programming tool version is applicable for programming communication.
For the version applicability check, refer to Section 1.4.

7.3 Checking Communication Status Based on LED Indication


Check the status of the "RXD (RD)" and "TXD (SD)" indicator LEDs provided in the optional equipment.
LED status
Operation status
RXD (RD) TXD (SD)
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received
Off Off Data is not sent nor received.

7.4 Checking Installation

1. Mounting status
If the communication equipment is not securely connected to the PLC, communication is not possible.
For the mounting method, refer to the respective communication equipment manual.

7.5 Checking Parameters in PLC

1. Checking the communication setting


Verify that non-protocol communication or computer link communication is not set in the parameters of the FX
PLC. If such communication is already set, programming communication with optional communication
equipment cannot be used.
For the setting of parameters in the PLC, refer to Chapter 5.

7.6 Checking Sequence Program

1. Checking the contents of the communication setting


Verify that no communication format (D8120, D8400 and D8420, N:N Network: D8173 to D8180, and Parallel
Link: M8070 and M8071) is being used in the sequence program.
If any communication format is being used in the sequence program, communication will not function
correctly.

H-48
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Programming Communication 7.6 Checking Sequence Program

A
2. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)

Common Items
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in
programming communication.
After changing the setting, make sure to reboot the PLC's power.

3. Presence of VRRD and VRSC instructions


B
1) Except FX3G, FX3U and FX3UC PLCs

N:N Network
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
2) In FX3G PLC
- In the case of the 14 points and 24-point type
Verify that the VRRD and VRSC instructions are not used in the program. C
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.

Parallel Link
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions.
After deleting these instructions, turn OFF the PLC power, and then turn the power ON again.
D
3) In FX3U and FX3UC PLCs

Computer Link
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power.

4. Presence of RS instruction (except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs) E
Verify that the RS instruction is not used in the program.

Communication
Inverter
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.

5. Presence of RS and RS2 instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel.
If these instructions are used for the same channel, revise them, turn OFF the PLC power, and then turn the
power ON again.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
6. Presence of EXTR instruction (in FX2N and FX2NC PLCs)
Verify that the EXTR instruction is not used in the program.
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.

7. Presence of IVCK, IVDR, IVRD, IVWR, IVBWR*1, and IVMC instructions (in FX3S, FX3G, G
FX3GC, FX3U and FX3UC PLCs)

(FX2N-232IF)
Communication
Non-Protocol
Verify that the IVCK, IVDR, IVRD, IVWR, IVBWR and IVMC instructions are not being used for the same
channel.
If these instructions are used for the same channel, revise them, turn OFF the PLC power, and then turn the
power ON again.
*1. Only available for FX3U and FX3UC PLCs. H
Communication
Programming

8. Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.

9. Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and
FX3UC PLCs) I
Maintenance
Remote

Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the
same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.

Apx.A
models
Discontinued

H-49
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Programming Communication 7.7 Checking Programming Tool Setting

7.7 Checking Programming Tool Setting


Verify that the setting contents in the programming tool are correct.

1. Checking the communication port


Verify that the communication port is set correctly.

2. Checking the transmission speed


Verify that the transmission speed is set correctly.
For the programming tool setting, refer to Chapter 6.

7.8 Checking Absence/Presence of Errors

1. Checking M8062 (except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
When a communication error occurs in the standard built-in port, M8062 turns ON and D8062 stores the
corresponding error code.

2. Checking the error code (D8062)


D8062 stores either of the following error codes:
Error code Contents of error
*1 Parity error, overrun error or framing error
6201
6202 Defective communication character
D8062 6203 Communication data sum mismatch
6204 Defective data format
6205 Defective command

3. Checking M8063 and M8438


When a communication errors occur in optional communication equipment, M8063 turns ON and D8063
stores the corresponding error code during communication using ch1, and M8438 turns ON and D8438 stores
the corresponding error code during communication using ch2.

H-50
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Programming Communication 7.9 Operation mode display [D8419 and D8439] (FX3S, FX3G, FX3GC, FX3U, FX3UC)

A
4. Checking the error code

Common Items
D8063 and D8438 store either of the following error codes:
Error code
Contents of error
D8063 (ch1) D8438 (ch2)
6301*1
6302
3801
3802
Parity error, overrun error or framing error
Defective communication character
B

N:N Network
6303 3803 Communication data sum mismatch
6304 3804 Defective data format
6305 3805 Defective command
6306 3806 Monitoring timeout
6307 3807 Modem initialization error C
6308 3808 N:N Network parameter error

Parallel Link
6309 3809 N:N Network setting error
6312 3812 Parallel link parameter error
6313 3813 Parallel link sum error
6314 3814 Parallel link format error
6320 3820 Inverter communication error D
6321 3821 MODBUS communication error

Computer Link
6330 3830 Memory access error
6340 3840 Special adapter connection error

*1. In the FX1N, FX1NC, FX2N and FX2NC Series, a communication error may occur during automatic
alignment of the transmission speed when programming communication is executed while the
transmission speed of the peripheral equipment is set to 19.2 kbps because the transmission speed at
E

Communication
Inverter
power ON is set to 9.6 kbps in the main unit.
Accordingly, when a communication error occurs at start of communication and problems are expected
if the error flag (special auxiliary relay) remains ON, clear the error flag for the corresponding channel.
When problems are expected if the error flag turns ON, execute programming communication after
setting the transmission speed of the peripheral equipment to 9.6 kbps at power ON of the PLC.
In other series, the error flag for the corresponding channel does not turn ON even if the transmission F
speed is automatically aligned.

(RS/RS2 Instruction)
Communication
Non-Protocol
(The error code is stored in the special data register for the corresponding channel.)

7.9 Operation mode display [D8419 and D8439] (FX3S, FX3G, FX3GC, FX3U, FX3UC)
These devices store the communication type being used. G

(FX2N-232IF)
Communication
Non-Protocol
1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.

The table below shows the contents of the communication type codes.
H
Communication
Programming

Code Description
0 Programming communication
1 PP modem mode
2 Protocol dedicated to computer link
3 N:N Network I
4 RS instruction
Maintenance
Remote

5 RS2 instruction
6 Parallel link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication Apx.A
10 CF-ADP
models
Discontinued

11 ENET-ADP
12 Input/output expansion board is used.

H-51
FX Series PLC User's Manual - Data Communication Edition 7 Troubleshooting
Programming Communication 7.9 Operation mode display [D8419 and D8439] (FX3S, FX3G, FX3GC, FX3U, FX3UC)

MEMO

H-52
FX Series PLC User's Manual - Data Communication Edition
Remote Maintenance

Common Items
B

N:N Network
FX Series Programmable Controllers
User's Manual [Data Communication Edition] C

Parallel Link
I. Remote Maintenance
D

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Foreword
I
This manual explains "remote maintenance" provided for the MELSEC-F FX Series Programmable
Maintenance
Remote

Controllers and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent Apx.A
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
models
Discontinued

rights which may occur as a result of using the contents noted in this manual.

2005 MITSUBISHI ELECTRIC CORPORATION

I-1
FX Series PLC User's Manual - Data Communication Edition
Remote Maintenance

I-2
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.1 Outline of System

Common Items
1. Outline
This chapter explains remote maintenance. B

N:N Network
1.1 Outline of System
Remote maintenance performs program transfer and device monitoring using Windows programming
software with a PLC connected to the telephone line by way of a modem. C

Parallel Link
1.1.1 Maintenance for programs in PLC

1) Sequence programs can be changed by transferring and writing programs during RUN.
2) Maintenance can be performed by device monitoring, PLC diagnosis, forced ON/OFF and changing set
values and current values. D
3) A line can be established from a personal computer to a modem connected to a PLC.

Computer Link
Important points and reference
System chapter/section

FX PLC E

Communication
Inverter
For the sequence For the PLC model
programming software, refer ........ ...... applicability, refer to
to Chapter 3. Chapter 2.
Personal
computer Communication
equipment
operating in
For selection, refer to
...... Chapter 3. F
accordance with

(RS/RS2 Instruction)
Communication
Non-Protocol
RS-232C

Commercial communication product For wiring, refer to


.............. Chapter 4.

General telephone line Setting the modem


G
..............

(FX2N-232IF)
Communication
Non-Protocol
For the personal computer
side, refer to Chapter 6.
Modem Modem For the PLC side, refer to
Chapter 5.

H
Communication
Programming

Cellular Cellular
Modem phone phone Modem

I
Maintenance
Remote

.............. For the remote maintenance


Personal software, refer to Chapter 3.
computer
Remotely accesses the PLC. Applicable software
GX Works2
GX Developer
FX-PCS/WIN Apx.A
models
Discontinued

I-3
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.1 Outline of System

1.1.2 File transfer between personal computers (supported only by FXGP/WIN)


This manual does not describe the operating procedure for this function, but the modem setting contents and
setting procedure in personal computers can be used as reference.
For the detailed explanation of this function, refer to the "FX-PCS/WIN SOFTWARE MANUAL".

1) Transferring sequence program files between personal computers

Important points and reference


System chapter/section

...... For the remote maintenance


software, refer to Chapter 3.
Personal
computer Applicable software
FX-PCS/WIN
It accesses a personal
computer (FXGP/WIN) in the
remote mode.

Commercial communication product For wiring, refer to


.............. Chapter 4.

General telephone line .............. Setting in the modem


For the personal computer
side, refer to Chapter 6.
Modem Modem

Cellular Cellular
Modem phone phone Modem

.............. For the remote maintenance


Personal software, refer to Chapter 3.
computer
Applicable software
Remotely accesses the FX-PCS/WIN
personal computer
(FXGP/WIN).

I-4
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.2 Procedures Before Operation

A
1.2 Procedures Before Operation

Common Items
The flow chart below shows the remote maintenance setting procedures up until communication:

Remote maintenance B

N:N Network
Refer to Chapter 1

Outline Outline of system


Applicable PLC versions
Applicable programming tools
Refer to Chapter 2 Software for remote access C
Check communication specifications Communication specifications

Parallel Link
Refer to Chapter 3

Determine system configuration and selection System configuration


Selecting communication equipment D
Applicable modem list

Computer Link
Refer to Chapter 4

Perform wiring Wiring procedure


Cables supplied with modem

Programming tool
E

Communication
Inverter
Connect PLC*1

F
Refer to Chapter 5

(RS/RS2 Instruction)
Communication
Non-Protocol
PLC communication setting
Set modem on PLC side Confirming that communication setting is
not provided
Setting modem
Setting modem connected to PLC
Refer to Chapter 6
(programs and parameters) G
Set modem on personal computer

(FX2N-232IF)
Communication
Non-Protocol
Setting modem
(remote access) side Setting modem connected to personal
computer
Turn ON power Refer to Chapter 7

Connect line Connection through telephone line


H
Communication
Programming

Based on SD/RD lamp lighting status and


contents of error check devices, verify that
communication is being executed normally.
If there are problems, refer to the troubleshooting
(Chapter 8).
I
Maintenance
Remote

*1 For the programming tool to PLC connection procedure, refer to the "Programming Communication" section in this
manual or the respective programming tool manual.
For details on operating procedures, refer to the respective programming tool manual.

Apx.A
models
Discontinued

I-5
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.3 Communication Type Applicability in PLC

1.3 Communication Type Applicability in PLC

1.3.1 Applicable versions


The communication types are applicable in the following versions.
: Applicable : Not applicable
PLC Applicability Remarks
FX3UC Series
FX3U Series
FX3GC Series
FX3G Series
FX3S Series
FX2NC Series
FX2N Series ME3314 (OMRON) is applicable to Ver. 2.01 and later.
FX1NC Series
FX1N Series
FX1S Series
FX0N Series This function is not available
FX0S Series This function is not available
FX0 Series This function is not available
FX2C Series This function is not available
FX2(FX) Series This function is not available
FX1 Series This function is not available

1.3.2 Version check


The PLC version can be checked by reading the last three digits of device D8001.
For a detailed description of the version check, refer to A. Common Items Section 4.2.

1.3.3 Products whose production was stopped


Production was stopped for some models of MELSEC-F Series PLCs and programming tools described in
this manual. For models whose production was stopped, refer to Appendix A.
To see the latest available products, refer to the general catalog.

I-6
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.4 Programming Tool Applicability

A
1.4 Programming Tool Applicability

Common Items
1.4.1 Programming tool for setting modem connected to PLC
The tables below show programming tools applicable for modem setting using parameters and sequence B
programs.

N:N Network
For programming software on remote maintenance, refer to Subsection 1.4.2

For applicable versions


The programming tool is applicable for each FX Series from the version shown:

1. English versions
C

Parallel Link
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.13P or later
FX-30P Ver. 1.00 or later D
FX3G PLC

Computer Link
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later E
-

Communication
Inverter
FX-30P Ver. 1.30 or later
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
F

(RS/RS2 Instruction)
Communication
Non-Protocol
GX Developer SWD5C(F)-GPPW-E SW2 A or later
-
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later
FX-30P Ver. 1.00 or later
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later G
GX Developer SWD5C(F)-GPPW-E SW5 A or later

(FX2N-232IF)
Communication
Non-Protocol
-
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later
FX-30P Ver. 1.00 or later

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-7
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.4 Programming Tool Applicability

2. Japanese versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW2 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.10 or later
FX-PCS-KIT/98 SW1PC-FXGP/98(-3,-5) Ver. 4.00 or later
-
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 4.00 or later
FX-PCS-KIT/V-3 SW1PC-FXGP/V3 Ver. 2.00 or later
FX-A7PHP-KIT SW1RX-GPPFX Ver. 3.00 or later
FX-30P Ver. 1.00 or later
FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later -
FX-PCS/98-3 SW1PC-FXGP/98-3 Ver. 5.00 or later
FX-30P Ver. 1.00 or later

I-8
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.4 Programming Tool Applicability

A
In the case of non-applicable versions (setting an alternative model)

Common Items
For FX1S, FX2N and FX2NC PLCs, it is not possible to create programs using programming tools of
inapplicable versions.
For FX1N, FX1NC, FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs of the following versions, it is possible to create
programs by setting an alternative model. In this case, however, created programs are limited to the function
range (such as instructions and program size) supported by the selected alternative model.
Any programming tool not shown below is not applicable.
B

N:N Network
1. English versions
Product name Version allowing Setting an
Model to be
(Model name is shown setting of alternative alternative Remarks
programmed
below.)
GX Developer
model model
C
SW2 A or later*1 The PP modem mode (ch1) and

Parallel Link
FX3U, FX3UC SWD5C(F)-GPPW-E
FX2N PP modem mode (ch2) cannot be
Series FX-PCS/WIN-E
Ver. 1.00 or later set.
SW0PC-FXGP/WIN-E
GX Works2
Ver. 1.64S or later FX3G
SWDNC-GXW2-E
FX3G, FX3GC GX Developer D
Series SWD5C(F)-GPPW-E SW2 A or later*2 The PP modem mode (ch1) and

Computer Link
FX1N*3 PP modem mode (ch2) cannot be
FX-PCS/WIN-E set.
Ver. 1.00 or later
SW0PC-FXGP/WIN-E
GX Works2
Ver. 1.08J or later
SWDNC-GXW2-E
FX3G
GX Developer
Ver. 8.72A or later E
SWD5C(F)-GPPW-E

Communication
Inverter
FX3S Series
GX Developer
SWD5C(F)-GPPW-E SW2 A or later*2
The PP modem mode (ch1)
FX1N*3 cannot be set.
FX-PCS/WIN-E
Ver. 1.00 or later
SW0PC-FXGP/WIN-E
GX Developer
FX1N, FX1NC SWD5C(F)-GPPW-E
SW2 A or later*4 F
FX2N

(RS/RS2 Instruction)
Communication
Non-Protocol
Series FX-PCS/WIN-E
Ver. 1.00 or later
SW0PC-FXGP/WIN-E

*1. An alternative model can be set in GX Developer SW2 A to Ver. 8.18U.


*2. An alternative model can be set in GX Developer SW2 A to Ver. 8.72A.
*3. Select "FX2N" in model selection when "FX1N" is not supported. G

(FX2N-232IF)
Communication
Non-Protocol
*4. An alternative model can be set in GX Developer SW2 A to SW5 A.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-9
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.4 Programming Tool Applicability

2. Japanese versions
Product name Version allowing Setting an
Model to be
(Model name is shown setting of alternative alternative Remarks
programmed
below.) model model
GX Developer
SWD5C(F)-GPPW-J SW2 A or later*1
FX-PCS/WIN
Ver. 2.10 or later
SW0PC-FXGP/WIN
FX-PCS-KIT/98
Ver. 4.00 or later The PP modem mode (ch1) and
FX3U, FX3UC SW1PC-FXGP/98(-3,-5)
FX2N PP modem mode (ch2) cannot be
Series FX-PCS/98-3
Ver. 4.00 or later set.
SW1PC-FXGP/98-3
FX-PCS-KIT/V-3
Ver. 2.00 or later
SW1PC-FXGP/V3
FX-A7PHP-KIT
Ver. 3.00 or later
SW1RX-GPPFX
GX Works2
Ver. 1.64S or later FX3G
SWDNC-GXW2-J
GX Developer
SWD5C(F)-GPPW-J SW2 A or later*2
FX-PCS/WIN
Ver. 2.10 or later
SW0PC-FXGP/WIN
FX3G, FX3GC FX-PCS-KIT/98
Ver. 4.00 or later The PP modem mode (ch1) and
Series SW1PC-FXGP/98(-3,-5)
FX1N*3 PP modem mode (ch2) cannot be
FX-PCS/98-3
Ver. 4.00 or later set.
SW1PC-FXGP/98-3
FX-PCS-KIT/V-3
Ver. 2.00 or later
SW1PC-FXGP/V3
FX-A7PHP-KIT
Ver. 3.00 or later
SW1RX-GPPFX
GX Works2
Ver. 1.07H or later
SWDNC-GXW2-J
FX3G
GX Developer
Ver. 8.72A or later
SWD5C(F)-GPPW-J
FX3S Series
GX Developer
SWD5C(F)-GPPW-J SW2 A or later*2
The PP modem mode (ch1)
FX1N*3 cannot be set.
FX-PCS/WIN
Ver. 3.00 or later
SW0PC-FXGP/WIN
GX Developer
SWD5C(F)-GPPW-J SW2 A or later*4
FX-PCS/WIN
Ver. 2.10 or later
SW0PC-FXGP/WIN
FX-PCS-KIT/98
Ver. 4.00 or later
FX1N, FX1NC SW1PC-FXGP/98(-3,-5)
FX2N
Series FX-PCS/98-3
Ver. 4.00 or later
SW1PC-FXGP/98-3
FX-PCS-KIT/V-3
Ver. 2.00 or later
SW1PC-FXGP/V3
FX-A7PHP-KIT
Ver. 3.00 or later
SW1RX-GPPFX
*1. An alternative model can be set in GX Developer SW2 A to Ver. 8.13P.
*2. An alternative model can be set in GX Developer SW2 A to Ver. 8.72A.
*3. Select "FX2N" in model selection when "FX1N" is not supported.
*4. An alternative model can be set in GX Developer SW2 A to SW5 A.

Point
In the FX3S PLC, set the memory capacity for PLC parameters to 4,000 steps or less.

I-10
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.4 Programming Tool Applicability

A
1.4.2 Programming software for remote maintenance

Common Items
The table below shows programming software for the personal computer which uses remote access.
For the applicability of programming tools for setting the modem, refer to Subsection 1.4.1.

In the case of applicable versions B


The programming software is applicable from the following versions:

N:N Network
1. English versions
Product name Model name Applicable version Remarks
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.64S or later
- C
GX Developer SWD5C(F)-GPPW-E Ver. 8.18U or later

Parallel Link
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.64S or later
-
GX Developer SWD5C(F)-GPPW-E Ver. 8.72A or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later - D
FX3S PLC

Computer Link
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.64S or later
GX Developer SWD5C(F)-GPPW-E SW2 A or later -
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 1.00 or later E
FX1S, FX1N and FX1NC PLCs

Communication
Inverter
GX Works2 SWDNC-GXW2-E Ver. 1.64S or later
GX Developer SWD5C(F)-GPPW-E SW5 A or later -
FX-PCS/WIN-E SW0PC-FXGP/WIN-E Ver. 3.00 or later

2. Japanese versions F
Product name Model name Applicable version Remarks

(RS/RS2 Instruction)
Communication
Non-Protocol
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.64S or later -
When connecting the programming
software to a PLC in which the PP
GX Developer SWD5C(F)-GPPW-J Ver. 8.13P or later modem mode (ch1) or PP modem G
mode (ch2) is set, use Ver. 8.18U or

(FX2N-232IF)
Communication
Non-Protocol
later.
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.64S or later
-
GX Developer SWD5C(F)-GPPW-J Ver. 8.72A or later
FX3GC PLC H
Communication
Programming

GX Works2 SWDNC-GXW2-J Ver. 1.77F or later -


FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later -
FX2N and FX2NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.64S or later I
GX Developer SWD5C(F)-GPPW-J SW2 A or later -
Maintenance
Remote

FX-PCS/WIN SW0PC-FXGP/WIN Ver. 2.10 or later


FX1S, FX1N and FX1NC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.64S or later
GX Developer SWD5C(F)-GPPW-J SW5 A or later -
Apx.A
FX-PCS/WIN SW0PC-FXGP/WIN Ver. 4.00 or later
models
Discontinued

I-11
FX Series PLC User's Manual - Data Communication Edition 1 Outline
Remote Maintenance 1.4 Programming Tool Applicability

In the case of non-applicable versions


A non-applicable programming software version cannot offer remote maintenance.
If your programming software is a non-applicable version, upgrade versions.
To upgrade versions, contact your dealer.

1.4.3 Cautions on using FXGP/WIN

1. The remote maintenance function cannot be used when FXGP/WIN is used in the following
versions of Windows:
- Windows NT 4.0
- Windows 2000
- Windows XP

2. For FX3U and FX3UC Series


The models "FX3U" and "FX3UC" cannot be selected.
"FX2N" can be selected and set as the alternative model.
However, FXGP/WIN cannot be connected to a PLC in which the PP modem mode is set.

3. For FX3S, FX3G and FX3GC Series


The models "FX3S", "FX3G" and "FX3GC" cannot be selected.
"FX1N" can be selected and set as the alternative model.
However, FXGP/WIN cannot be connected to a PLC in which the PP modem mode is set.

I-12
FX Series PLC User's Manual - Data Communication Edition 2 Specifications
Remote Maintenance 2.1 Communication Specifications (Reference)

Common Items
2. Specifications
This chapter explains the communication specifications and performance. B

N:N Network
2.1 Communication Specifications (Reference)
Communication is executed according to the (fixed) specifications shown in the table below. Specification
items such as baud rate cannot be changed.
Only modems supporting the communication specifications below can be used.
C

Parallel Link
Item Modem mode Remarks
Transmission standard RS-232C standard
Maximum total extension distance 15 m (49' 2") or less
Protocol type Modem mode
Communication method Half-duplex, asynchronous system D

Computer Link
Modem PLC
Baud rate 9600 bps Modem Personal
computer
Start bit 1-bit
When PP modem mode
Data bit 7-bit 8-bit (ch1) or PP modem E
Character mode (ch2) is set, "Data

Communication
Inverter
format bit: 8-bit" and "Parity bit:
Parity bit Even Not provided Not provided" are set
automatically.
Stop bit 1-bit
Header
Fixed
F
Terminator

(RS/RS2 Instruction)
Communication
Non-Protocol
Control line Not provided
Sum check Fixed
Applicable PLC
FX3UC Series
G
FX3U Series

(FX2N-232IF)
Communication
Non-Protocol
FX3GC Series
FX3G Series
FX3S Series
FX2NC Series H
FX2N Series
Communication
Programming

FX1NC Series
FX1N Series
FX1S Series
I
Maintenance
Remote

Apx.A
models
Discontinued

I-13
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.1 System Configuration

3. System Configuration and Selection


This chapter explains the configuration of communication equipment operating in accordance with RS-232C
and selection of the system required by FX PLCs.

3.1 System Configuration


This section outlines the system configuration required to use remote maintenance.
Connect (optional) equipment operating in accordance with RS-232C to the FX PLC main unit.

1 , 2 , 3 and 4 indicate the communication equipment combination patterns.

Communication equipment operating


FX PLC Important point in selection Total extension
in accordance with RS-232C distance

1
This is the communication board built 15 m
+ into the PLC, reducing the installation
(49' 2")
area.

Communication
board

2
Attach the special adapter expansion
board to the main unit, and then
15 m
+ + (49' 2")
attach the communication adapter to
the left side of the main unit.

Communication Special adapter


adapter expansion board

3 Attach the connector conversion


adapter to the main unit, and then 15 m
+ + attach the communication adapter to (49' 2")
the left side of the main unit.

Communication Connector
adapter conversion adapter

+ Attach the communication adapter to 15 m


the left side of the main unit. (49' 2")
The total extension distance should
conform to the modem specifications in
Communication both cases in which a cable supplied with
adapter
the modem is used and which another
prepared cable is used.

For communication equipment combinations for each FX Series, refer to the next page.

I-14
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.2 Setting Applicable FX PLC and Communication Equipment

A
3.2 Setting Applicable FX PLC and Communication Equipment

Common Items
Select a communication equipment combination, and put a check mark in the "Check" column.
During selection, pay attention to the following:
- In the table below, only the outside dimensions and D-SUB connector shape are different between units
shown in "FX2NC-232ADP/FX0N-232ADP". Select either one. B
- Remote maintenance is not provided for the FX1, FX2(FX), FX2C, FX0, FX0S and FX0N PLCs.

N:N Network
Total extension
FX Series Communication equipment (option) Check
distance

15 m C
(49' 2")

Parallel Link
FX1N-232-BD
(9-pin D-Sub)

+ + 15 m D
FX1S
(49' 2")

Computer Link
FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP
(9-pin D-Sub) (25-pin D-Sub)

15 m E
(49' 2")

Communication
Inverter
FX1N-232-BD
(9-pin D-Sub)

FX1N + + 15 m F
(49' 2")

(RS/RS2 Instruction)
Communication
Non-Protocol
FX1N-CNV-BD FX2NC-232ADP FX1N-CNV-BD FX0N-232ADP
(9-pin D-Sub) (25-pin D-Sub)

G
15 m

(FX2N-232IF)
Communication
Non-Protocol
(49' 2")
FX2N-232-BD
(9-pin D-Sub)

H
FX2N + +
Communication
Programming

15 m
(49' 2")

FX2N-CNV-BD FX2NC-232ADP FX2N-CNV-BD FX0N-232ADP


(9-pin D-Sub) (25-pin D-Sub)

I
Maintenance
Remote

Apx.A
models
Discontinued

I-15
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.2 Setting Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance

15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)

FX3S
15 m
(49' 2")

FX3S-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)

15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)

FX3G
(14-point,24-point
type) 15 m
(49' 2")

FX3G-CNV-ADP FX3U-232ADP(-MB)
(9-pin D-Sub, male)
When using channel 1 (ch 1)
ch1

15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)
The communication equipment works as ch1 when connected to
the option connector 1.
FX3G
(40-point,60-point ch1
type)

15 m
(49' 2")

FX3G-CNV-ADP FX3U-232ADP(-MB)
(9pin D-SUB, male)

I-16
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.2 Setting Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)*1

ch2

N:N Network
15 m
(49' 2")
FX3G-232-BD
(9-pin D-Sub, male)
The communication equipment works as ch2 when connected to
the option connector 2.
C

Parallel Link
ch1 ch2
FX3G
(40-point,60-point
type)

15 m
(49' 2")
D

Computer Link
FX3G-CNV-ADP FX3U-ADP(-MB) FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232 and 485).
Ch2 is not available when the FX3G-8AV-BD, FX3G-4EX-BD or
FX3G-2EYT-BD is connected to the option connector 2.
When using channel 1 (ch 1) E

Communication
Inverter
ch1

15 m
RD

(49' 2")
SD

FX3U-232-BD
F

(RS/RS2 Instruction)
Communication
Non-Protocol
(9-pin D-Sub, male)

ch1
FX3U

+ 15 m
(49' 2") G

(FX2N-232IF)
Communication
Non-Protocol
FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)

*1. When using ch2 in an FX3G PLC, it can be set only in the PP modem mode (ch2).

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-17
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.2 Setting Applicable FX PLC and Communication Equipment

Total extension
FX Series Communication equipment (option) Check
distance
When using channel 2 (ch 2)*1

ch1 ch2

+
RD

SD

15 m
(49' 2")
FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV)
When a FX3U-8AV-BD is used, it occupies one communication port
channel.

ch1 ch2
FX3U

+ + 15 m
(49' 2")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port
channel.

15 m
(49' 2")

FX2NC-232ADP FX0N-232ADP
FX1NC (9-pin D-Sub) (25-pin D-Sub)

15 m
(49' 2")

FX2NC-232ADP FX0N-232ADP
FX2NC (9-pin D-Sub) (25-pin D-Sub)
When using channel 1 (ch 1)
ch1

15 m
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)*2


ch1 ch2
FX3GC

+ 15 m
(49' 2")

FX3U-ADP(-MB) FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232 and 485).
*1. When using ch2 in an FX3U PLC, it can be set only in the PP modem mode (ch2).
*2. When using ch2 in an FX3GC PLC, it can be set only in the PP modem mode (ch2).

I-18
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.2 Setting Applicable FX PLC and Communication Equipment

A
Total extension

Common Items
FX Series Communication equipment (option) Check
distance
When using channel 1 (ch 1)
ch1

15 m
B

N:N Network
(49' 2")

FX3U-232ADP(-MB)
(9-pin D-Sub, male)

When using channel 2 (ch 2)*1


ch1 ch2
C

Parallel Link
FX3UC

+
(D, DS, DSS)
15 m
(49' 2")
FX3U-232ADP(-MB),
FX3U-485ADP(-MB),
FX3U-232ADP(-MB)
(9-pin D-Sub, male)
D

Computer Link
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port channel.
When using channel 1 (ch 1)
ch1

E
15 m
RD

Communication
Inverter
(49' 2")
SD

FX3U-232-BD
(9-pin D-Sub, male)

ch1
F

(RS/RS2 Instruction)
Communication
Non-Protocol
+ 15 m
(49' 2")

FX3U-CNV-BD FX3U-232ADP(-MB)
(9-pin D-Sub, male)
G
When using channel 2 (ch 2)*1

(FX2N-232IF)
Communication
Non-Protocol
ch1 ch2

FX3UC-32MT-LT
+
RD

(-2)
15 m
SD

(49' 2") H
Communication
Programming

FX3U--BD FX3U-232ADP(-MB)
(Where represents (9-pin D-Sub, male)
232, 422, 485, USB and 8AV)
When a FX3U-8AV-BD is used, it occupies one communication port channel.
ch1 ch2
I
+ +
Maintenance
Remote

15 m
(49' 2")
FX3U-CNV-BD FX3U-232ADP(-MB), FX3U-232ADP(-MB)
FX3U-485ADP(-MB), (9-pin D-Sub, male)
FX3U-CF-ADP
When a FX3U-CF-ADP is used, it occupies one communication port channel.
Apx.A
models
Discontinued

*1. When using ch2 in an FX3UC PLC, it can be set only in the PP modem mode (ch2).

I-19
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.3 Selecting Modem

3.3 Selecting Modem


In FX PLCs, the modems PV-AF288 (manufactured by AIWA CO., LTD.) and ME3314B (manufactured by
OMRON Corporation) are applicable.
When "user registration mode", "PP modem mode (ch1)", or "PP modem mode (ch2)" is selected in the
modem initialization setting in an FX PLC, other modems are also applicable.
The tables below show the communication specifications in the "user registration mode", "PP modem mode
(ch1)", and "PP modem mode (ch2)". Select a modem supporting the communication specifications shown
below.

1. User registration mode


Item Contents
Communication method Half-duplex, asynchronous system
Baud rate 9600 bps
Start bit 1-bit
Data bit 7-bit
Parity bit Even
Stop bit 1-bit
Control line Not provided

If the modem used does not support the communication specifications shown above, communication is not
possible.

2. PP modem mode (ch1) and PP modem mode (ch2)


Item Contents
Communication method Half-duplex, asynchronous system
Baud rate 9600 bps
Start bit 1-bit
Data bit 8-bit
Parity bit Not provided
Stop bit 1-bit
Control line Not provided

If the modem used does not support the communication specifications shown above, communication is not
possible.

I-20
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.3 Selecting Modem

A
3.3.1 List of modems whose operations are confirmed

Common Items
The tables below show already tested modems and their associated AT command.
1. Modem on the PLC side
The PLC has a command to initialize the PV-AF288 (manufactured by AIWA CO., LTD.) and ME3314B
(manufactured by OMRON Corporation). This command can be used only by setting parameters using the GX B
Works2, GX Developer or FXGP/WIN software.

N:N Network
For other modems, input and set the AT command shown below in ASCII code to a data register (D1000 and
later usually, and D200 or later in the FX1S PLC).
For the setting procedure, refer to Chapter 5.
AT command setting for modem
Manufacturer
on PLC side

Modem
GX Works2 GX Developer
(SWDNC (SWD5C FX-PCS/WIN
AT command Remarks C
model name

Parallel Link
-GXW2) -GPPW)
Manufactured by I-O DATA DEVICE, INC.
Input AT command shown
DFML-560ER ATE0Q1S0=2&D0&K0&W0&Y0%C3
on right
DFML-K56F*1 Input AT command shown on right ATE0Q1S0=2&D0&K0&W0&Y0\Q0%C3
Manufactured by AIWA CO., LTD.
D

Computer Link
PV-AF288*1 Select AIWA modem (PV-AF288) ATE0S0=2Q1&D0&M5\Q0\J0&W
PV-BF5606*1 Input AT command shown on right ATE0S0=2&D0Q1&K0&W
Manufactured by OMRON Corporation
In FX2N PLC, Ver. 2.01
ME3314B*1 Select OMRON modem (ME3314B) ATE0S0=2Q1&D0&H0&R1S15=8&W
and later are applicable.
Modem version: F/W
E
ME5614E*1

Communication
Inverter
Input AT command shown on right ATE0S0=2&D0Q1&K0&W Ver. 2.300
ME5614E2*1
Modem version: F/W
ME5614D*1 Input AT command shown on right ATE0S0=2&D0Q1&K0&W
Ver. 2.300
*1. Production is finished as of August, 2010.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-21
FX Series PLC User's Manual - Data Communication Edition 3 System Configuration and Selection
Remote Maintenance 3.3 Selecting Modem

2. Modem on the personal computer side for remote access


The table below shows modems whose operations are already confirmed. Input and set the AT command shown
below using a programming tool in the personal computer on the remote access side.
FXGP/WIN has a command to initialize the PV-AF288, PV-AF3360 (manufactured by AIWA CO., LTD.), ME3314B,
ME5614D, ME5614E and ME5614E2*2 (manufactured by OMRON Corporation). This command can be used only
by setting a parameter.
For the setting procedure, refer to Chapter 6.
Manufacturer AT command setting for modem on personal computer side for remote access
GX Works2 GX Developer Remarks
Modem
(SWDNC (SWD5C FX-PCS/WIN
model name
-GXW2) -GPPW)
Manufactured by I-O DATA DEVICE, INC.
DFML-560ER AT&C1E0Q0S0=2&K0&D0
Manufactured by AIWA CO., LTD.
Select this model (AT command is shown for reference)
PV-AF288*1
ATE0S0=2Q0V1&M4\J0\Q0
Select this model (AT command is shown for reference)
PV-AF3360*1
ATE0S0=2Q0V1S15=8&H0&R1
Select this model (AT command is shown for reference)
PV-BF5606*1 ATE0S0=2&K0&D0 ATE0S0=2&K0
Manufactured by OMRON Corporation
Select this model (AT command is shown for reference)
ME3314B*1
ATE0S0=2Q0V1S15=8&H0&R1
Modem version: F/W
ME5614E*1 Select this model (AT command is shown for reference) Ver. 2.300
ATE0S0=2&K0&D0
ME5614E2 ATE0S0=2&K0W0
*1*2
Select this model (AT command is shown for reference) Modem version: F/W
ME5614D*1 ATE0S0=2&K0&D0
ATE0S0=2&K0W0 Ver. 2.300
*1. Production is finished as of August, 2010.
*2. When used the FXGP/WIN, select the model "ME5614E".

I-22
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Remote Maintenance 4.1 Wiring Procedure

Common Items
4. Wiring
This chapter explains the wiring. B

N:N Network
4.1 Wiring Procedure

1 Turning OFF the PLC power C


Before starting any wiring work, make sure that the PLC power is OFF.

Parallel Link
2 Checking the connector shape
When a cable is included with the modem, check the shape of the RS-232C connector in the
personal computer to be connected, the shape of the connector in the communication equipment D
operating in accordance with RS-232C for the PLC, and male or female type.

Computer Link
3 Connecting the RS-232C ports in the modem and the PLC with a cable
Check the shape of the connector (number of pins) in the communication equipment operating in
accordance with RS-232C to be connected to the PLC. Each cable has either connector shape:
- 9-pin D-Sub, female
E

Communication
Inverter
- 25-pin D-Sub, male

4 Connecting the personal computer and the modem with a cable for remote access
Check the shape of the RS-232C connector (number of pins) on the personal computer for remote access.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-23
FX Series PLC User's Manual - Data Communication Edition 4 Wiring
Remote Maintenance 4.2 Connection Diagram

4.2 Connection Diagram

1. To connect the modem, use a cable included with the modem or cable described in the
modem manual.
Remote access

Line
general telephone
Cable line, etc. Cable

Modem Modem
Personal computer PLC

2. The table below shows the pin arrangement in the communication equipment operating in
accordance with RS-232C for the FX PLC.
FX1N-232-BD, FX2N-232-BD, FX2NC-232ADP,
FX0N-232ADP FX3G-232-BD, FX3U-232-BD, Signal
Function
FX3U-232ADP(-MB) name
25-pin D-Sub, female 9-pin D-Sub, male
1*1 CD Receiving carrier detection
25 13
3 2 RD (RXD) Receive data input
5 9
2 3 SD (TXD) Send data output

20 6 4 ER (DTR) Data terminal ready


1
7 5 SG (GND) Signal ground
14 1
6 6 DR (DSR) Data set ready

*1. The FX2NC-232ADP does not use the CD signal.

I-24
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

Common Items
5. How to Setup Modems on the PLC Side
This chapter explains how to set parameters for initialization using the AT command and set the B
communication specifications including the transmission speed for a modem connected to the PLC.

N:N Network
The setting method using GX Works2 and the setting method using FXGP/WIN are explained.
For applicable programming tools, refer to Subsection 1.4.2.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

5.1 Setting Using GX Works2 C

Parallel Link
This section explains the modem initialization setting and communication setting methods. Suppose that GX
Works2 is already started up.
Screens for the FX3U PLC are shown as examples.

5.1.1 Setting communication by way of RS-232C port D

Computer Link
It is not necessary to set the serial communication with a modem.
However, it is necessary to verify that another communication type is not used and whether the
communication setting is correct using the following procedure.
In FX PLCs, the communication setting can be executed using either of the following two methods:
1) Writing the value "0" to the data register D8120 using a sequence program E
If another communication type is already set for another application, delete the sequence program which

Communication
Inverter
writes a value to D8120.
When setting remote maintenance to ch1 in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLC, write the value "0" to
the data register D8120, D8400.
When setting remote maintenance to ch2 in an FX3G/FX3GC/FX3U/FX3UC PLC, write the value "0" to the
data register D8420.
F
2) Setting parameters using a sequence programming tool

(RS/RS2 Instruction)
Communication
Non-Protocol
By using the following procedure, verify that another communication type is not set.

1 Opening the PLC parameter setting window


In the project view area of the navigation window, double-click [Parameter] [PLC Parameter]. G
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from

(FX2N-232IF)
Communication
Non-Protocol
the menu bar.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-25
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

2 Checking the serial communication (parameter) setting


Click the [PLC System(2)] tab on the dialog box.
Make sure that the "Operate Communication Setting" box is cleared, and click the [End] button.
If a check mark is there, clear it, and then click the [End] button.

I-26
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

A
5.1.2 Modem initialization setting using parameter method

Common Items
This subsection explains how to select the AT command for initialization registered in the PLC and how to set
the AT command for an unregistered modem.

1 Opening the PLC parameter setting window B

N:N Network
In the project view area of the navigation window, double-click [Parameter] [PLC Parameter].
If the navigation window is not displayed, select [View] [Docking Window] [Navigation] from
the menu bar.

Parallel Link
D

Computer Link
2 Selecting the modem initialization method
Click the [PLC System(1)] tab on the dialog box. E
Select a modem to be connected in "MODEM Initialized", and click the [End] button.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-27
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

Modem model
Set item Description Manufacturer
name
Select this item when remote maintenance is
None
not used.
Select this item when the modem to be used Unregistered
User Register Mode
is not registered. modem

AIWA(PV-AF288) PV-AF288 AIWA CO., LTD.


Select the corresponding item when either
modem is to be used. OMRON
OMRON(ME3314B) ME3314B
Corporation
Select this item when the modem to be used
Unregistered
PP Modem Mode (CH1)*1 satisfying the PP modem mode specifications
modem

is not registered.
Select this item when remote maintenance is Unregistered
PP Modem Mode (CH2)*2 executed in ch2. modem

*1. When an FX3S, FX3G, FX3GC, FX3U and FX3UC PLC is used
*2. When an FX3G, FX3GC, FX3U and FX3UC PLC is used

3 Setting the AT command for the unregistered modem


When "User Register Mode", "PP Modem Mode (CH1)", or "PP Modem Mode (CH2)" is selected in
"MODEM Initialized", the AT command setting is required. For the AT command setting method for
unregistered modems, refer to Subsection 5.1.3.
The AT command setting is not required when "AIWA[PV-AF288]" or "OMRON(ME3314B)" is
selected.

4 Writing the parameter and program to the PLC


Select [Online] [Write to PLC] from the menu bar.
Click [Parameter] [PLC Parameter/Network Parameter] in the project tree.
When the AT command is set for an unregistered modem, next put a check mark next to "Device
Memory" "MAIN".
After placing the check mark, click the [Execute] button to write the contents to the FX PLC.

I-28
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

A
5.1.3 Setting AT command for unregistered modem

Common Items
Only when "MODEM Initialized" is set to "User Register Mode", "PP Modem Mode (CH1)", or "PP Modem
Mode (CH2)", execute the following setting.
(The modem initialization setting depends on the setting contents of the [PLC System(1)] tab displayed
when [Parameter] [PLC Parameter] is selected.)
B
1 Display a device memory

N:N Network
In the project view area of the navigation window, double-click [Device Memory] [Device
memory data name].

Parallel Link
D

Computer Link
E

Communication
Inverter
Caution F
In GX Developer, select "Device memory" in the project tree, right-click it to display the submenu, and select

(RS/RS2 Instruction)
Communication
Non-Protocol
"New".
Click the [OK] button on the New dialog box, and click the [Yes] button.

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-29
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

2 Displaying the device list


Select "Input Device" on the Edit menu to display the Input Device dialog box.

Set "Device", "Range", "Display Mode" and "Register", and click [OK].

The device (data register) number to be set varies depending on the PLC as shown below:
PLC Device range
FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U and FX3UC PLC D1000 to D1059
FX1S and FX3S PLC D200 to D255

I-30
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

A
3

Common Items
Inputting the AT command
Input the AT command to D1000 (D200 For FX1S and FX3S PLCs) and later. Input one character to
one word.
Click the data register to be input, and select "Paste Text" on the edit menu to display the Paste
Text dialog box. B

N:N Network
Input one (half-width) character, and click the [OK] button.

Parallel Link
D

Computer Link
E

Communication
Inverter
1. AT command structure
For initializing a modem, use the AT command developed by Hayes.
The Hayes AT command is generally expressed in the following format:
F

(RS/RS2 Instruction)
Communication
Non-Protocol
A T Command + Parameter Command + Parameter Command + Parameter CR LF

1 2 ...... n

For details on the AT command, refer to the manual of the modem to be used. G

(FX2N-232IF)
Communication
Non-Protocol
2. Input example of the AT command for initialization, Example: ATE0S0 = 2Q1&D0&M4\Q0\J0&W
Hexadecimal Hexadecimal
Data register No. ASCII code Data register No. ASCII code
value value
D1000 A 41 D1013 & 26
D1001 T 54 D1014 M 4D H
D1002 E 45 D1015 4 34
Communication
Programming

D1003 0 30 D1016 \ 5C
D1004 S 53 D1017 Q 51
D1005 0 30 D1018 0 30
D1006 = 3D D1019 \ 5C
I
D1007 2 32 D1020 J 4A
Maintenance
Remote

D1008 Q 51 D1021 0 30
D1009 1 31 D1022 & 26
D1010 & 26 D1023 W 57
D1011 D 44 D1024 CR 0D
D1012 0 30 D1025 LF 0A
Apx.A
models
Discontinued

I-31
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.1 Setting Using GX Works2

4 Inputting "CR" and "LF"


It is necessary to input "CR" and "LF" at the end of the AT command.
Input "0D" and "0A" (hexadecimal values) to data registers respectively.

If "CR (0DH)" and "LF (0AH)" are not input at the end of the AT command, remote maintenance is
not possible.

I-32
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.2 Setting Using FXGP/WIN

A
5.2 Setting Using FXGP/WIN

Common Items
This section explains the modem initialization setting and communication setting methods.

5.2.1 Setting communication by way of RS-232C port


B
It is not necessary to set the serial communication with a modem.

N:N Network
However, it is necessary to verify that another communication type is not used and whether the
communication setting is correct using the following procedure.

In FX PLCs, the communication setting can be executed using either of the following two methods:
1) Writing the value "0" to the data register D8120 using a sequence program C
If another communication type is already set for another application, delete the sequence program which

Parallel Link
writes a value to D8120.
2) Setting parameters using a sequence programming tool
By using the following procedure, verify that the communication setting is not provided.

1 Checking the serial setting (parameter) D

Computer Link
Select [Option] [Serial setting (parameter)] from the toolbar.
The following dialog box appears according to absence/presence of parameter setting.

1. When there is no parameter setting


The dialog box shown below appears to indicate that there is no communication setting. E
Click the [No] button.

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. When there are already parameter settings
The dialog box shown below appears to indicate that the communication setting is being used.
Click the [Clear] button.
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-33
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.2 Setting Using FXGP/WIN

5.2.2 Modem initialization setting using parameter method


This subsection explains how to select the AT command for initialization registered in advance in the PLC and
how to set the AT command for an unregistered modem.

1 Setting the PLC mode


Click [Option] [PLCs mode setting] from the toolbar.

2 Selecting the modem initialization method


Select a modem to be connected in "Modem initialize", and click the [OK] button.

Modem model
Set item Description Manufacturer
name
Select this item when remote maintenance is
None
not used.
Select this item when the modem to be used Unregistered
User entry mode
is not registered. modem

AIWA(PV-AF288) PV-AF288 AIWA CO., LTD.


Select corresponding item when either
modem is to be used. OMRON
OMRON(ME3314B) ME3314B
Corporation

3 Setting the AT command for an unregistered modem


When "User entry mode" is selected in "Modem initialize", the AT command setting is required.
For the AT command setting method for unregistered modems, refer to Subsection 5.2.3.
The AT command setting is not required when "AIWA(PV-AF288)" or "OMRON(ME3314B)" is
selected.

4 Writing the program to the PLC


Click [PLC] [Transfers] [Write] from the toolbar to display the "Program write" dialog box.
Select "All range", and click the [OK] button.

When the AT command is set for an unregistered modem, transfer the register also.
Click [PLC] [Register data transfers] [Write] from the toolbar to display the Write dialog box.
Place a check mark () next to "Data register", and click the [OK] button.

I-34
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.2 Setting Using FXGP/WIN

A
5.2.3 Setting AT command for unregistered modem

Common Items
Only when "User entry mode" is selected in "Modem initialize", execute the following setting.
(The modem initialization setting depends on the setting contents of the window displayed when [Option]
[PLCs mode setting] is selected from the toolbar.)
B
1 Displaying the device list

N:N Network
Select [View] [Register view] from the toolbar.

Parallel Link
D

Computer Link
2 Executing the display setting
Select the set items as shown in the table below, and click the [OK] button.
E
Item Contents of setting

Communication
Inverter
Display form Line
Data size 16bit

(RS/RS2 Instruction)
Communication
Non-Protocol
The device (data register) number to be set varies depending on the PLC as shown below:
G
PLC Device range

(FX2N-232IF)
Communication
Non-Protocol
FX1N/FX1NC/FX2N/FX2NC/FX3G/FX3GC/FX3U/FX3UC PLC D1000 to D1059
FX1S/FX3S PLC D200 to D255

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-35
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.2 Setting Using FXGP/WIN

3 Inputting the AT command


Input the AT command to the "ASCII" column of D1000 and later. Input one (half-width) character to
one word.

Make sure to input "CR (0DH)" and "LF (0AH)" at the end of the AT command. If they are not input,
remote maintenance is not possible.
The "CR" and "LF" input method is explained in the next step.

1. AT command structure
For initializing a modem, use the AT command developed by Hayes.
The Hayes AT command is generally expressed in the following format:

A T Command + Parameter Command + Parameter Command + Parameter CR LF

1 2 ...... n

For details on the AT command, refer to the manual of the modem to be used.

2. Input example of the AT command for initialization, Example: ATE0S0 = 2Q1&D0&M4\Q0\J0&W


Hexadecimal Hexadecimal
Data register No. ASCII code Data register No. ASCII code
value value
D1000 A 41 D1013 & 26
D1001 T 54 D1014 M 4D
D1002 E 45 D1015 4 34
D1003 0 30 D1016 \ 5C
D1004 S 53 D1017 Q 51
D1005 0 30 D1018 0 30
D1006 = 3D D1019 \ 5C
D1007 2 32 D1020 J 4A
D1008 Q 51 D1021 0 30
D1009 1 31 D1022 & 26
D1010 & 26 D1023 W 57
D1011 D 44 D1024 CR 0D
D1012 0 30 D1025 LF 0A

I-36
FX Series PLC User's Manual - Data Communication Edition 5 How to Setup Modems on the PLC Side
Remote Maintenance 5.3 Cautions on Use

A
4

Common Items
Inputting "CR" and "LF"
It is necessary to input "CR" and "LF" at the end of the AT command.
Input "000D" and "000A" (hexadecimal values) to data registers respectively.
B

N:N Network
C

Parallel Link
D

Computer Link
E

Communication
Inverter
If "CR (0DH)" and "LF (0AH)" are not input at the end of the AT command, remote maintenance is
disabled.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
5.3 Cautions on Use

1. Cautions on inputting the AT command for initialization to the PLC


1) The AT command finishes sending when "0" (hexadecimal value) is read.
G

(FX2N-232IF)
Communication
Non-Protocol
2) When creating a sequence program, make sure that the input area for the modem initialization command
is different from the data register area used by general sequence programs.
3) Make sure to input "CR (0DH)" and "LF (0AH)" at the end of the AT command. If they are not input,
remote maintenance is disabled.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-37
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.1 Setting Using GX Works2

6. How to Setup Modems on the PC Side for Remote


Access
This chapter explains how to set a modem connected to the personal computer for remote access.
The setting method using GX Works2 and the setting method using FXGP/WIN are explained respectively.
For applicable programming tools, refer to Subsection 1.4.2.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual.

Remote access side PLC side

Line
general telephone
Cable line, etc. Cable

Modem Modem
Personal computer PLC

This chapter explains the setting procedure The setting procedure for this side is
for this side. explained in Chapter 5.

6.1 Setting Using GX Works2


This section explains the line connection setting method using GX Works2.

6.1.1 Registering AT command for connected modem


This subsection explains how to register the AT command for initializing a modem connected to the personal
computer.

1 Setting the AT command


Select [Tools] [Set TEL Data/Connect via Modem] [AT Command Registration] from the menu
bar to display the following dialog box.

I-38
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.1 Setting Using GX Works2

A
2

Common Items
Registering the AT command for the connected modem
Select "Modem at MELSOFT Application Side" in the project tree, and click the [New AT
Command] button.
Input "Title" and "AT Command", and click the [OK] button.
- Input a name easy to understand such as the modem model name to "Title". B
- Input "AT Command" while referring to the description below.

N:N Network
C

Parallel Link
D

Computer Link
E

Communication
Inverter
1. In the case of a modem whose operation is confirmed
For such a modem, input the following AT command.
Modem model
Modem manufacturer name AT command set value Remarks
name
I-O DATA DEVICE, INC. DFML-560ER AT&C1E0Q0S0=2&K0&D0
F

(RS/RS2 Instruction)
Communication
Non-Protocol
AIWA CO., LTD. PV-BF5606 ATE0S0=2&K0&D0
ME5614E Modem version: F/W Ver. 2.300
OMRON Corporation ATE0S0=2&K0&D0
ME5614E2
OMRON Corporation ME5614D ATE0S0=2&K0&D0 Modem version: F/W Ver. 2.300

2. In the case of any other modem (whose operation is not confirmed)


G

(FX2N-232IF)
Communication
Non-Protocol
Click the [Help of AT Command] button.
Refer to the contents of the help and the manual of the connected modem, create the AT command.
3. Contents of help for the AT command
The table below shows the contents of description about [Help of AT Command]. H
Setting example: AT&C1Q0V1\N3&D0&K0
Communication
Programming

AT command Description
AT&Cn Set the mode in which the CD signal is set to ON when the carrier from the counterpart is received.
ATQn Set the AT command so that the result code for the AT command is sent back.
ATVn Set the AT command so that the response to the AT command is given in a character string.
The MNP automatic selection mode is recommended.
I
Maintenance
Remote

When the MNP block size is a set item, "128 bytes maximum per block" is general.
AT\Nn
When the MNP automatic selection mode cannot be specified, specify the direct mode in the
asynchronous communication mode.
AT&Dn Set the ER signal to "normally ON".
AT&Kn (AT&Hn&In&Rn) Set "no flow control".
When a converter is used, set "no dial tone". Apx.A
AT&Xn
It is not necessary to set this item when a converter is not used.
models
Discontinued

I-39
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.1 Setting Using GX Works2

6.1.2 Creating telephone directory (if necessary)


This subsection explains the method to register the telephone number of the counterpart (line connected to
the modem of the desired PLC).

1 Displaying the telephone directory dialog box


Select [Tools] [Set TEL Data/Connect via Modem] [Phone Book] from the menu bar to display
the following dialog box.

2 Creating the group name


Click the [New Group] button to display the Group Setting dialog box.
Input a group name (example: A Corporation) to which the telephone numbers belong, and click
the [OK] button.

I-40
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.1 Setting Using GX Works2

A
3

Common Items
Selecting a group name to which the counterpart telephone number will be
registered
Click and select an already created group name (example: A Corporation).
Click the [New Phone Number] button.
B

N:N Network
C

Parallel Link
D

Computer Link
4 Inputting the name, telephone number, etc. E

Communication
Inverter
Input required items, and click [OK] button.
If there is another counterpart to be registered, repeat from step 2 above.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
For details, refer to GX Works2 Version 1 Operating Manual (Common). Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-41
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.2 Setting Using FXGP/WIN

6.2 Setting Using FXGP/WIN


This section explains the line connection method using FXGP/WIN.

6.2.1 Registering AT command for connected modem


This subsection explains how to register the AT command for initializing a modem connected to the personal
computer for remote access.

1 Setting the AT command


Select [Remote] [Environment] [Modem] from the toolbar to display the following dialog box.

Registered modems are displayed.

2 Registering the AT command for the connected modem


1. When the connected modem is shown in the list
Select the modem model name, and click the [OK] button.
Proceed to step 4.

2. When the connected modem is not shown in the list


It is necessary to create the AT command for the modem, and register it.
Proceed to step 3.

I-42
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.2 Setting Using FXGP/WIN

A
3

Common Items
Newly creating the AT command for the modem
Click the [New Entry] button.
Input "Name" and "Initial Setup String", and then click the [OK] button.
- To "Name", input a name easy to understand such as the modem model name.
- To "Initial Setup String", input proper contents while referring to the description below.
B

N:N Network
C

Parallel Link
Input the AT command while referring to the description below.

1. In the case of a modem whose operation is confirmed


For a modem whose operation is confirmed, input the following AT command:
D

Computer Link
Modem Modem model
AT command set value
manufacturer name
AIWA CO., LTD. PV-AF288 ATE0S0=2Q0V1&M4\J0\Q0
AIWA CO., LTD. PV-AF3360 ATE0S0=2Q0V1S15=8&H0&R1
AIWA CO., LTD. PV-BF5606 ATE0S0=2&K E
OMRON Corporation ME3314B ATE0S0=2Q0V1S15=8&H0&R1

Communication
Inverter
OMRON Corporation ME5614E ATE0S0=2&K0W0
OMRON Corporation *1 ATE0S0=2&K0W0
ME5614E2
OMRON Corporation ME5614D ATE0S0=2&K0W0

*1. When used the FXGP/WIN, select the model "ME5614E". F

(RS/RS2 Instruction)
Communication
Non-Protocol
2. AT command structure
For initializing a modem, use the AT command developed by Hayes.
The Hayes AT command is generally expressed in the following format:

A T Command + Parameter Command + Parameter Command + Parameter CR LF


G

(FX2N-232IF)
Communication
Non-Protocol
1 2 ...... n

For details on the AT command, refer to the manual of the modem to be used.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-43
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.2 Setting Using FXGP/WIN

3. Setting contents of the AT command


When the PLC power is turned ON, the PLC sends the AT command to the modem to initialize the modem.
For reference, the table below shows the set items and setting contents of the AT commands for modems
which are registered in advance in FXGP/WIN.
The set items and setting contents may vary depending on each modem. For actual setting contents, refer to
the manual of the modem to be used.
Set item PV-AF288 (AIWA) PV-AF3360 (AIWA) ME3314B (OMRON)
ATE0S0=2Q0V1&M4\J0\Q0 ATE0S0=2Q0V1&M4\J0\Q0 ATE0S0=2Q0V1S15=8&H0&R1
Command echo E0 (not provided) E0 (not provided) E0 (not provided)
Number of times of calling
S0 = 2 (twice) S0 = 2 (twice) S0 = 2 (twice)
in automatic receiving
Result code display Q0 (provided) Q0 (provided) Q0 (provided)
Result code format V1 (character, word) V1 (character, word) V1 (character, word)
Communication mode &M4 (MNP automatic) &M4 (MNP automatic) S15 = 8 (V. 42 bis)
Terminal speed fixing
\J0 (fixed) \J0 (fixed)
mode
Send data flow control &H0 (not provided)
Terminal flow control
\Q0 (not provided) \Q0 (not provided) &R1 (not provided)
method
Initialization to values set
&F (FXGP/WIN sends "AT&F", and then sends the AT command above.)
in factory before delivery

4 Displaying the selected modem


Verify that the desired modem is set, and click the [OK] button.

On this window, a newly registered modem is selected.

I-44
FX Series PLC User's Manual - Data Communication Edition 6 How to Setup Modems on the PC Side for Remote Access
Remote Maintenance 6.2 Setting Using FXGP/WIN

A
6.2.2 Registering line connection destination

Common Items
This subsection explains how to register the telephone number of the line connection destination (line
connected to the modem of the desired PLC).

1 Displaying the line connection dialog box B

N:N Network
Select [Remote] [Connect] [to PLC] from the toolbar to display the following dialog box.

Parallel Link
D

Computer Link
2 Inputting the telephone number of the line connection destination E

Communication
Inverter
Click the [New Entry] button.
When the following dialog box appears, input the counterpart "Name" and "Phone".

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol
3 Registering the line connection destination
After inputting the telephone number, click the [OK] button to register it.
H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

For details on set items, refer to the manual of FXGP/WIN.

I-45
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.1 Preparing for Connection of PLC

7. Connecting Line
This chapter explains the line connection procedure for remote maintenance.

7.1 Preparing for Connection of PLC


For remote maintenance, it is necessary to properly establish the modem-to-PLC connection.
Set the PLC using the following procedure.

1 Setting initialization for the modem on the PLC side


Set the AT command for the modem to be connected to the PLC.
For details, refer to Chapter 6.

2 Turning OFF the PLC power


After inputting the AT command to the PLC, turn OFF the PLC power.

3 Connecting the modem


Connect the communication equipment of the PLC to the modem.
For details, refer to Chapter 4.

4 Turning ON the modem power


Turn ON the modem power connected to the PLC.

5 Turning ON the PLC power


After turning ON the power to the modem, turn ON the PLC power.
When the PLC power is turned ON, the TXD (SD) and RXD (RD) LEDs light instantaneously in the
optional communication equipment operating in accordance with RS-232C, and the AT command
is sent to the modem.
If these LEDs do not light, refer "Chapter 8. Troubleshooting".

I-46
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

A
7.2 Line Connection Procedure

Common Items
This section explains the procedure to connect a personal computer to a PLC using a telephone line. The
connection procedure varies depending on the software used. Connect a telephone line suitable to the
software used.
For details on GX Developer operating procedure, refer to GX Developer Operating Manual. B

N:N Network
7.2.1 For GX Works2
This subsection explains the line connection procedure using GX Works2. Prepare for connection of the PLC,
connect a modem to the communication port in the personal computer, and start up GX Works2.
C
1 Setting the line connection

Parallel Link
Select [Tools] [Set TEL Data/Connect via Modem] [Line Connection] from the menu bar to
display the following dialog box.

D
The line connection status is displayed.

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
2 Setting the connection method G
Select "Auto".

(FX2N-232IF)
Communication
Non-Protocol
3 Setting the line
Set each item as follows:
H
1. Line type
Communication
Programming

Set the type of line connected to the modem.


- In the case of general telephone, select the contracted line type (tone, pulse or ISDN).
- In the case of cellular phone, select "Tone".

2. Outside line I
Maintenance
Remote

Set this item if necessary for making phone calls to outside lines.

3. Port
Select the communication port number in the personal computer connected to the modem.
Apx.A
models
Discontinued

I-47
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

4 Setting the connection destination


Set the telephone number of the counterpart (line number of the modem connected to the desired
PLC).
When a telephone number has been set in advance in the telephone directory, it can be set using
the [Browse] button.
For details on the telephone directory, refer to Subsection 6.1.2.

5 Setting the AT command


Set the AT command for the modem connected to the personal computer. When the AT command
has been registered in advance, it can be set using the [Browse] button.
For details on the AT command registration, refer to Subsection 6.1.1.

6 Placing a check mark () next to "Record the logging data"


Put a check mark here when storing the log at the line connection to a file.
The log at the line connection is recorded in the following log file:

1. For GX Works2
Storage destination
- For Windows 2000 and Windows XP
User folder\Application Data\MITSUBISHI\MELSOFT\TEL\Log
- For Windows Vista, Windows 7, Windows 8, Windows 8.1 and Windows 10
User folder\AppData\Roaming\MITSUBISHI\MELSOFT\TEL\Log
Log file name: year, month, day.dat (example: 130206.dat)

2. For GX Developer
Storage destination: GX Developer installation destination\log (default: Melsec\Gppw\log)
Log file name: Date.log (example: 130206.log)

7 Setting others
When "PP Modem Mode (CH1)" or "PP Modem Mode (CH2)" is selected in "Init modem", place a
check mark () next to "User mode (8bits NP)".

8 Connecting the line


Click the [Connect] button to display the following dialog box.
Click the [Yes] button to execute line connection and make a call from the modem connected to the
personal computer.

I-48
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

A
9

Common Items
Checking the line connection status
1. When the line is connected
When the line is connected, the connection status shown below is displayed on the Line Connection dialog
box.
B

N:N Network
When connection is completed, the following dialog box appears to indicate the telephone number of the
connection destination and the communication speed. C

Parallel Link
D

Computer Link
Confirm the contents, and click the [OK] button to close the dialog box.
Proceed to step 10.
E
2. When the line cannot be connected

Communication
Inverter
When the line cannot be connected, the following figure is displayed on the Line Connection dialog box.
(Example: When no response is given by the modem connected to the personal computer)

(RS/RS2 Instruction)
Communication
Non-Protocol
And the following dialog box appears.

(FX2N-232IF)
Communication
Non-Protocol
Click the [OK] button to display the Options dialog box.

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

Change the waiting time and number of retries, and then click the [OK] button to close the dialog box.
Check the telephone number and AT command, and then execute connection again.
If line connection is disabled, refer to "Chapter 8. Troubleshooting".

I-49
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

10 Executing remote maintenance


Read and write sequence programs, and monitor devices.

11 Disconnecting the line


To disconnect the line, select [Tools] [Set TEL Data/Connect via Modem] [Line Disconnection]
from the menu bar.
When the following dialog box appears, click the [Yes] button to disconnect the line.

When line disconnection is finished, the following dialog box appears to indicate the connection
destination telephone number and line use time.

Click the [OK] button to close the dialog box.

I-50
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

A
7.2.2 For FXGP/WIN

Common Items
This subsection explains the line connection procedure using FXGP/WIN. Prepare for connection of the PLC,
connect a modem to the communication port in the personal computer, and then start up FXGP/WIN.

1 Setting the modem to be used B

N:N Network
Select [Remote] [Environment] [Modem] from the toolbar to display the following dialog box.

Parallel Link
D

Computer Link
Select the modem to be used, and click the [OK] button.
If the modem to be used is not displayed, click the [New Entry] button, and register the AT
E

Communication
Inverter
command for the modem.
For details on AT command registration, refer to Subsection 6.2.1.

2 Connecting the connection destination


Select [Remote] [Connect] [to PLC] from the toolbar to display the following dialog box.
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

Select the connection destination, and click the [OK] button.


If the connection destination is not displayed, click the [New Entry] button, and register the I
connection destination.
Maintenance
Remote

For details on connection destination registration, refer to Subsection 6.2.2.


Proceed to step 4.

When directly setting a telephone number, click the [Manual] button.


Proceed to the next step.
Apx.A
models
Discontinued

I-51
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

3 Executing manual connection


Click the [Manual] button to display the following dialog box.

Set "Name" and "Phone", and click the [OK] button.

4 Checking the line connection status


When the [OK] button is clicked, the following dialog box appears.

Click the [Yes] button to display the message box "Executing!" and make a call from the modem
connected to the personal computer.

5 Checking the line connection status


1. When the line is connected
When connection is completed, the message box "Executing!" is closed, and the line connection time is
displayed on the title bar as shown below:

Proceed to step 6.

2. When the line cannot be connected


When the line cannot be connected, the message box "Executing!" is closed, and the following dialog box
appears.

Click the [OK] button to close the dialog box.


Check the telephone number and AT command, and then execute connection again.
If line connection is disabled, refer to "Chapter 8. Troubleshooting".

I-52
FX Series PLC User's Manual - Data Communication Edition 7 Connecting Line
Remote Maintenance 7.2 Line Connection Procedure

A
6

Common Items
Executing remote maintenance
Read and write sequence programs, and monitor devices.

7 Disconnecting the line B


To disconnect the line, select [Remote] [Disconnect] from the toolbar.

N:N Network
When the following dialog box appears, click the [Yes] button to disconnect the line.

Parallel Link
When the line is disconnected, the line connection time on the title bar disappears.

Computer Link
E

Communication
Inverter
F

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-53
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Remote Maintenance 8.1 Checking FX PLC Applicability

8. Troubleshooting
This chapter explains troubleshooting.

8.1 Checking FX PLC Applicability


Verify that the FX PLC main unit version is applicable to remote maintenance.
For the version applicability check, refer to Section 1.3.

8.2 Checking Programming Tool Applicability


Verify that the programming tool version is applicable to remote maintenance.
For the version applicability check, refer to Section 1.4.
The remote maintenance function cannot be used when FXGP/WIN is used in the following versions of
Windows:
- Windows NT 4.0
- Windows 2000
- Windows XP

8.3 Checking Communication Status Based on LED Indication


Check the status of the "RXD (RD)" and "TXD (SD)" indicator LEDs provided in the optional equipment
LED status
Operation status
RXD (RD) TXD (SD)
Flashing Flashing Data is being sent or received.
Flashing Off Data is received, but is not sent.
Off Flashing Data is sent, but is not received
Off Off Data is not sent nor received.

When the power is turned ON, the FX PLC transfers the AT command to the connected modem. At this time,
the "RXD (RD)" and "TXD (SD)" indicator LEDs in the communication equipment light instantaneously.
If modem initialization is not set in parameters in the FX PLC, however, these LEDs do not light.
If the wiring and/or modem specifications are different, these LEDs flash several times, but the FX PLC does
not transfer the AT command.

8.4 Checking Installation

1. Mounting status
If the communication equipment is not securely connected to the PLC, communication is not possible.
For the mounting method, refer to the respective communication equipment manual.

I-54
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Remote Maintenance 8.5 Checking Modem Specifications

A
8.5 Checking Modem Specifications

Common Items
In a modem in which the following communication specifications are not applicable, remote maintenance can
be used.
Check the modem specifications.

1. In the case of user registration mode


B

N:N Network
Item Contents
Communication method Half-duplex, asynchronous system
Baud rate 9600 bps
Start bit 1-bit
Data bit 7-bit
C

Parallel Link
Parity bit Even
Stop bit 1-bit
Control line Not provided

2. PP modem mode (ch1) and PP modem mode (ch2) D


Item Contents

Computer Link
Communication method Half-duplex, asynchronous system
Baud rate 9600 bps
Start bit 1-bit
Data bit
Parity bit
8-bit
Not provided
E

Communication
Inverter
Stop bit 1-bit
Control line Not provided

8.6 Checking Setting in PLC F

(RS/RS2 Instruction)
Communication
Non-Protocol
Check the parameters, AT command and sequence programs in the PLC.
After changing any parameters, make sure to turn OFF the PLC power, and then turn it ON again.

8.6.1 Checking parameters in PLC


G
1. Checking the communication setting

(FX2N-232IF)
Communication
Non-Protocol
Verify that non-protocol communication, computer link communication, etc. are not set in the parameters of
the FX PLC. If such communication is already set, remote maintenance cannot be used.

2. Checking the modem initialization setting


Verify that the modem initialization is selected correctly in parameters in the FX PLC.
If the modem initialization is not set correctly, normal communication is not possible.
H
Communication
Programming

For the parameter settings of the PLC, refer to Chapter 5.

I
Maintenance
Remote

Apx.A
models
Discontinued

I-55
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Remote Maintenance 8.6 Checking Setting in PLC

8.6.2 Checking AT command setting


The AT command is required when "user registration mode", "PP modem mode (ch 1)" or "PP modem mode
(ch 2)" is selected in the modem initialization setting. When such a mode is set, check the following contents.

1. Checking data registers


The head device number and device range of data registers used for setting the AT command vary
depending on the FX Series.
Check the data register numbers in which the AT command is set.
PLC Device range
FX1N, FX1NC, FX2N, FX2NC, FX3G, FX3GC, FX3U and FX3UC PLC D1000 to D1059
FX1S and FX3S PLC D200 to D255

Use consecutive data registers from the head device number. If a numeric value is not set in a data register,
the data registers after it are not transferred.

2. Checking the contents of the AT command


If the contents of the AT command are not correct, remote maintenance cannot be used.
Verify that the setting contents are correct.
As reference, the table below shows the set items and their contents of the AT commands already registered
in PLCs.
PV-AF288 (AIWA) ME3314B (OMRON)
Set item
ATE0S0 = 2Q1&D0&M5\Q0\J0&W ATE0S0 = 2Q1&D0&H0&R1S15=8&W
Command echo E0 (not provided) E0 (not provided)
Number of times of calling in
S0 = 2 (twice) S0 = 2 (twice)
automatic receiving
Result code display Q1 (not provided) Q1 (not provided)
DTR control &D (normally ON) &D (normally ON)
Communication mode &M5 (V. 42 bis) S15 = 8 (V. 42 bis)
Terminal flow control method \Q0 (not provided) &R1 (not provided)
Send data flow control &H0 (not provided)
Terminal speed fixing mode \J0 (fixed)
Writing to nonvolatile memory &W &W

3. Checking "CR (H0D)" and "LF (H0A)"


Make sure to input "CR (H0D)" and "LF (H0A)" at the end of the AT command. If they are not input, the AT
command cannot be transferred.
For the AT command setting for the PLC, refer to Chapter 5.

I-56
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Remote Maintenance 8.6 Checking Setting in PLC

A
8.6.3 Checking sequence program

Common Items
1. Checking the contents of the communication setting
Verify that no communication format (D8120, D8400, D8420), N:N Network: D8176 to D8180, and Parallel
Link: M8070 and M8071) is being used in the sequence program.
If any communication format is being used in the sequence program, communication will not function B
correctly.

N:N Network
2. Ethernet port setting (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the same channel is not used in the Ethernet port setting. Do not set the channel used in remote
maintenance.
After changing the setting, make sure to reboot the PLC's power.
C
3. Presence of VRRD and VRSC instructions

Parallel Link
1) Except FX3G, FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
2) In FX3G PLC
- In the case of the 14 points and 24-point type
D

Computer Link
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions. E
After deleting these instructions, turn OFF the PLC power, and then turn the power ON again.

Communication
Inverter
3) In FX3U and FX3UC PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power.
F
4. Presence of RS instruction (except FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)

(RS/RS2 Instruction)
Communication
Non-Protocol
Verify that the RS instruction is not used in the program.
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.

5. Presence of RS and RS2 instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel.
If these instructions are used for the same channel, revise them, turn OFF the PLC power, and then turn the
G

(FX2N-232IF)
Communication
Non-Protocol
power ON again.
6. Presence of EXTR instruction (in FX2N and FX2NC PLCs)
Verify that the EXTR instruction is not used in the program.
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.

7. Presence of IVCK, IVDR, IVRD, IVWR, IVBWR*1, and IVMC instructions (in FX3S, FX3G,
H
Communication
Programming

FX3GC, FX3U and FX3UC PLCs)


Verify that the IVCK, IVDR, IVRD, IVWR, IVBWR and IVMC instructions are not being used for the same
channel.
If these instructions are used for the same channel, revise them, turn OFF the PLC power, and then turn the
power ON again.
*1. Only available for FX3U and FX3UC PLCs.
I
Maintenance
Remote

8. Presence of ADPRW instructions (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs)
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLCs power.

9. Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX3U and Apx.A
FX3UC PLCs)
models
Discontinued

Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the
same channel.
If these instructions are used for the same channel, delete them, reboot the PLCs power.

I-57
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Remote Maintenance 8.7 Checking Programming Tool Setting

8.7 Checking Programming Tool Setting


Verify that the setting contents in the programming tool are correct.

1. Checking the telephone number


Verify that the telephone number of the connection destination is set correctly.

2. Checking the AT command setting


Verify that the AT command is set correctly for the registered modem.

3. Checking the communication port


Verify that the communication port connected to the modem is set correctly.
For the programming tool setting, refer to Chapter 6.

8.8 Checking Absence/Presence of Errors


In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, an error occurs when modem initialization is not possible.
Verify that an error has not occurred.

1. Checking M8063
When a communication error occurs, M8063 turns ON and D8063 stores the corresponding error code.

2. Checking the error code


D8063 stores one of the following error codes:
Error code Contents of error
6301 Parity error, overrun error or framing error
6302 Defective communication character
6303 Communication data sum mismatch
6304 Defective data format
6305 Defective command
6306 Monitoring timeout
6307 Modem initialization error
6308 N:N Network parameter error
D8063
6309 N:N Network setting error
6312 Parallel link character error
6313 Parallel link sum error
6314 Parallel link format error
6320 Inverter communication error
6321 MODBUS communication error
6330 Memory access error
6340 Special adapter connection error

When modem initialization is disabled, D8063 stores the error code 6307.
If D8063 stores any error code shown above, check the following items:
Wiring
Modem specifications

I-58
FX Series PLC User's Manual - Data Communication Edition 8 Troubleshooting
Remote Maintenance 8.9 Operation mode display [D8419 and D8439] (FX3S, FX3G, FX3GC, FX3U, FX3UC)

A
8.9 Operation mode display [D8419 and D8439]

Common Items
(FX3S, FX3G, FX3GC, FX3U, FX3UC)
These devices store the communication type being used.

1. Detailed contents B
These devices store the code of the communication type currently being used in the communication port.

N:N Network
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.

The table below shows the contents of the communication type codes.
Code Description C

Parallel Link
0 Programming communication
1 PP modem mode
2 Protocol dedicated to computer link
3 N:N Network
4 RS instruction D
5 RS2 instruction

Computer Link
6 Parallel link
7 Inverter instruction
8 Variable analog potentiometer expansion board is used.
9 MODBUS communication
10 CF-ADP
E

Communication
Inverter
11 ENET-ADP
12 Input/output expansion board is used.

(RS/RS2 Instruction)
Communication
Non-Protocol
G

(FX2N-232IF)
Communication
Non-Protocol

H
Communication
Programming

I
Maintenance
Remote

Apx.A
models
Discontinued

I-59
FX Series PLC User's Manual - Data Communication Edition 9 Related Information
Remote Maintenance 9.1 ASCII Code Table

9. Related Information

9.1 ASCII Code Table

1. ASCII code table (7-bit code expressed in hexadecimal)


Hexadecimal 0 1 2 3 4 5 6 7
0 DLE SP 0 @ P p


1 SOH DC1 ! 1 A Q a q
2 STX DC2 2 B R b r
3 ETX DC3 # 3 C S c s
4 EOT DC4 $ 4 D T d t
5 ENQ NAK % 5 E U e u
6 ACK SYN & 6 F V f v
7 BEL ETB 7 G W g w
8 BS CAN ( 8 H X h x
9 HT EM ) 9 I Y i y
A LF SUB * : J Z j z
B VT ESC + ; K [ k {
C FF FS , < L \*1 l
D CR GS = M ] m }
E SO RS . > N n ~
F SI US / ? O _ o DEL

*1. \ (ASCII CODE:5C) symbol is displayed as " " in Japanese.

2. Examples of ASCII codes


ASCII ASCII ASCII ASCII
Decimal Alphabet Alphabet Code
(hexadecimal) (hexadecimal) (hexadecimal) (hexadecimal)
0 30 A 41 N 4E STX 02
1 31 B 42 O 4F ETX 03
2 32 C 43 P 50 LF 0A
3 33 D 44 Q 51 CR 0D
4 34 E 45 R 52
5 35 F 46 S 53
6 36 G 47 T 54
7 37 H 48 U 55
8 38 I 49 V 56
9 39 J 4A W 57
K 4B K 58
L 4C Y 59
M 4D Z 5A

ASCII
Symbol
(hexadecimal)
# 23
& 26
= 3D
\*1 5C

*1. \ (ASCII CODE:5C) symbol is displayed as " " in Japanese.

I-60
FX Series PLC User's Manual - Data Communication Edition Appendix A: Discontinued models
Discontinued models

Common Items
Appendix A: Discontinued models
The table below shows discontinued models of MELSEC-F Series PLCs and programming tools described in B
this manual.

N:N Network
Discontinued model Production stop date Repair acceptance period
FX1 June 30, 2002 Until June 30, 2009
FX2(FX) June 30, 2002 Until June 30, 2009
FX2C June 30, 2002 Until June 30, 2009 C
FX0 June 30, 2002 Until June 30, 2009

Parallel Link
FX0S January 31, 2006 Until January 31, 2013
FX0N January 31, 2006 Until January 31, 2013
FX2N September 30, 2012 Until September 30, 2019
FX2NC September 30, 2012 Until September 30, 2019
FX1S December 31, 2015 Until December 31, 2022
D

Computer Link
FX1N December 31, 2015 Until December 31, 2022
FX1NC December 31, 2015 Until December 31, 2022
FX1N-CNV-BD December 31, 2015 Until December 31, 2022
FX1N-232-BD December 31, 2015 Until December 31, 2022
FX1N-422-BD December 31, 2015 Until December 31, 2022 E
FX1N-485-BD December 31, 2015 Until December 31, 2022

Communication
Inverter
FX2N-CNV-BD December 31, 2015 Until December 31, 2022
FX2N-232-BD December 31, 2015 Until December 31, 2022
FX2N-422-BD December 31, 2015 Until December 31, 2022
FX2N-485-BD December 31, 2015 Until December 31, 2022 F
FX-232ADP June 30, 2002 Until June 30, 2009

(RS/RS2 Instruction)
Communication
Non-Protocol
FX-485ADP June 30, 2002 Until June 30, 2009
FX2-40AW June 30, 2002 Until June 30, 2009
FX2-40AP June 30, 2002 Until June 30, 2009
FX0N-485ADP January 31, 2006 Until January 31, 2013
FX0N-232ADP January 31, 2006 Until January 31, 2013
G

(FX2N-232IF)
Communication
Non-Protocol
FX2NC-232ADP December 31, 2015 Until December 31, 2022
FX2NC-485ADP December 31, 2015 Until December 31, 2022
FX-232AW September 30, 2004 Until September 30, 2011
FX-232AWC June 30, 2004 Until June 30, 2011
FX-232DOPA April 30, 2006 Until April 30, 2013 H
FX3U-232ADP September 30, 2013 Until September 30, 2020
Communication
Programming

FX3U-485ADP September 30, 2013 Until September 30, 2020


FX2N-16LNK-M September 30, 2012 Until September 30, 2019
FX2N-16CCL-M September 30, 2012 Until September 30, 2019
FX-2PIF June 30, 2008 Until June 30, 2015 I
FX-PCS/WIN(-E) March 31, 2013
Maintenance
Remote

FX-10P-E June 30, 2008 Until June 30, 2015


FX-10P-SET0 June 30, 2008 Until June 30, 2015
FX-20P(-E)-SET0 December 31, 2012 Until December 31, 2019
FX-10DU(-E) December 31, 2012 Until December 31, 2019
FX-20DU(-E) June 30, 2008 Until June 30, 2015
Apx.A
models
Discontinued

FX-20DU-CAB0 June 30, 2008 Until June 30, 2015


FX-25DU September 30, 2002 Until September 30, 2009

Apx.-1
FX Series PLC User's Manual - Data Communication Edition Appendix A: Discontinued models
Discontinued models

Discontinued model Production stop date Repair acceptance period


FX-30DU(-B) September 30, 2002 Until September 30, 2009
FX-40DU(-B) September 30, 2002 Until September 30, 2009
FX-40DU-TK(B) September 30, 2002 Until September 30, 2009
FX-50DU-TK(S) September 30, 2002 Until September 30, 2009

Apx.-2
Common Items N:N Network Parallel Link Computer Link Inverter Non-Protocol Non-Protocol Programming Remote Discontinued

Apx.A
E

I
A

H
F

Communication Communication Communication Communication Maintenance models


(RS/RS2 Instruction) (FX2N-232IF)
Appendix A: Discontinued models

Apx.-3
MEMO
FX Series PLC User's Manual - Data Communication Edition
Discontinued models
FX Series PLC User's Manual - Data Communication Edition Warranty

Warranty
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range 2. Onerous repair term after discontinuation of
If any faults or defects (hereinafter "Failure") found to be production
the responsibility of Mitsubishi occurs during use of the (1) Mitsubishi shall accept onerous product repairs for
product within the gratis warranty term, the product shall be seven (7) years after production of the product is
repaired at no cost via the sales representative or discontinued.
Mitsubishi Service Company. However, if repairs are Discontinuation of production shall be notified with
required onsite at domestic or overseas location, expenses Mitsubishi Technical Bulletins, etc.
to send an engineer will be solely at the customer's (2) Product supply (including repair parts) is not available
discretion. Mitsubishi shall not be held responsible for any after production is discontinued.
re-commissioning, maintenance, or testing on-site that 3. Overseas service
involves replacement of the failed module. Overseas, repairs shall be accepted by Mitsubishi's local
overseas FA Center. Note that the repair conditions at
[Gratis Warranty Term]
each FA Center may differ.
The gratis warranty term of the product shall be for one
year after the date of purchase or delivery to a designated 4. Exclusion of loss in opportunity and secondary
place. Note that after manufacture and shipment from loss from warranty liability
Mitsubishi, the maximum distribution period shall be six (6) Regardless of the gratis warranty term, Mitsubishi shall not
months, and the longest gratis warranty term after be liable for compensation to:
manufacturing shall be eighteen (18) months. The gratis (1) Damages caused by any cause found not to be the
warranty term of repair parts shall not exceed the gratis responsibility of Mitsubishi.
warranty term before repairs. (2) Loss in opportunity, lost profits incurred to the user by
Failures of Mitsubishi products.
[Gratis Warranty Range]
(3) Special damages and secondary damages whether
(1) The range shall be limited to normal use within the foreseeable or not, compensation for accidents, and
usage state, usage methods and usage environment, compensation for damages to products other than
etc., which follow the conditions and precautions, etc., Mitsubishi products.
given in the instruction manual, user's manual and (4) Replacement by the user, maintenance of on-site
caution labels on the product. equipment, start-up test run and other tasks.
(2) Even within the gratis warranty term, repairs shall be 5. Changes in product specifications
charged for in the following cases. The specifications given in the catalogs, manuals or
1. Failure occurring from inappropriate storage or technical documents are subject to change without prior
handling, carelessness or negligence by the user. notice.
Failure caused by the user's hardware or software 6. Product application
design. (1) In using the Mitsubishi MELSEC programmable logic
2. Failure caused by unapproved modifications, etc., controller, the usage conditions shall be that the
to the product by the user. application will not lead to a major accident even if any
3. When the Mitsubishi product is assembled into a problem or fault should occur in the programmable
user's device, Failure that could have been logic controller device, and that backup and fail-safe
avoided if functions or structures, judged as functions are systematically provided outside of the
necessary in the legal safety measures the user's device for any problem or fault.
device is subject to or as necessary by industry (2) The Mitsubishi programmable logic controller has been
standards, had been provided. designed and manufactured for applications in general
4. Failure that could have been avoided if industries, etc. Thus, applications in which the public
consumable parts (battery, backlight, fuse, etc.) could be affected such as in nuclear power plants and
designated in the instruction manual had been other power plants operated by respective power
correctly serviced or replaced. companies, and applications in which a special quality
5. Relay failure or output contact failure caused by assurance system is required, such as for Railway
usage beyond the specified Life of contact companies or Public service purposes shall be
(cycles). excluded from the programmable logic controller
6. Failure caused by external irresistible forces such applications.
as fires or abnormal voltages, and failure caused In addition, applications in which human life or property
by force majeure such as earthquakes, lightning, that could be greatly affected, such as in aircraft,
wind and water damage. medical applications, incineration and fuel devices,
7. Failure caused by reasons unpredictable by manned transportation, equipment for recreation and
scientific technology standards at time of shipment amusement, and safety devices, shall also be
from Mitsubishi. excluded from the programmable logic controller range
8. Any other failure found not to be the responsibility of applications.
of Mitsubishi or that admitted not to be so by the However, in certain cases, some applications may be
user. possible, providing the user consults their local
Mitsubishi representative outlining the special
requirements of the project, and providing that all
parties concerned agree to the special circumstances,
solely at the users discretion.

i
FX Series PLC User's Manual - Data Communication Edition Revised History

Revised History
Date Revision Description
7/2005 A First Edition
2/2006 B The status of the DR (DSR) signal is made checkable when RS2 (serial data
transfer 2) is in operation.
Parameters in A700 Series are added.
Clerical error is modified
11/2007 C FX3UC(D,DSS) Series are added.
FX3U-232ADP-MB, FX3U-485ADP-MB are added.
Inverter E700 Series are added. (FX3U, FX3UC Series corresponding)
Discontinued models are added. (Appendix A)
The addition and the change of other coverage.
Clerical error is modified.
11/2008 D FX3G Series are added.
Inverter E700 Series option FR-E7TR are added.
Inverter D700 Series are added. (FX3G, FX3U, FX3UC Series corresponding)
Discontinued models are added. (Appendix A)
Clerical error is modified.
6/2009 E FX-30P are added.
Caution on using CF card special adapter is added.
Explanation corrections for manufacture's serial number.
The addition and the change of other coverage.
Clerical error is modified.
11/2009 F The baud rate of the RS instruction/RS2 instruction/inverter communication/
computer link of the FX3U and FX3UC Series corresponds to "38400bps".
The addition and the change of other coverage.
Clerical error is modified.
8/2010 G Inverter multi command (FNC275 IVMC) are added.
FX3UC(DS) Series are added.
Caution on using VRRD and VRSC command is added. (FX3U, FX3UC Series
corresponding)
GX Works2 are added.
Explanation corrections for manufacturer's serial number and lot number.
The addition and the change of other coverage.
Clerical error is modified.
7/2011 H FX3G Series supports the IVMC instruction.
Cautions on setting up the N:N Network added.
The addition and the change of other coverage.
Clerical error is modified.
2/2012 J FX3GC Series are added.
FX3U-16CCL-M is added to system configurations.
The addition and the change of other coverage.
Clerical error is modified.
5/2013 K FX3S Series are added.
FX3U-ENET-ADP is added to system configurations.
Description of the programming tool is changed accompanied by change of the
programming tool from GX Developer to GX Works2.
Discontinued models are added.
The addition and the change of other coverage.
Clerical error is modified.

ii
FX Series PLC User's Manual - Data Communication Edition Revised History

Date Revision Description


9/2013 L FX3G-485-BD-RJ is added to system configurations.
Discontinued models are added.
The addition and the change of other coverage.
Clerical error is modified.
4/2015 M A part of the cover design is changed.
7/2016 N Inverter F800, A800 Series are added.
(FX3S, FX3G, FX3GC, FX3U, FX3UC Series corresponding)
FX3U-128ASL-M is added to system configurations.
Discontinued models are added.
The change of warranty coverage.
Clerical error is modified.

iii
FX SERIES PROGRAMMABLE CONTROLLERS

USER'S MANUAL

Data Communication Edition

HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

MODEL FX-U-COMMU-E
MODEL CODE 09R715

JY997D16901N Effective July 2016


(MEE) Specifications are subject to change without notice.

S-ar putea să vă placă și