Documente Academic
Documente Profesional
Documente Cultură
Sponsored by the
Switchgear Committee
IEEE
3 Park Avenue IEEE Std C37.63-2013
New York, NY 10016-5997 (Revision of
USA IEEE Std C37.63-2005)
26 April 2013
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
(Revision of
IEEE Std C37.63-2005)
Sponsor
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Abstract: Required definitions, ratings, procedures for performing design tests and production
tests, constructional requirements, and application considerations for overhead and pad-
mounted, dry-vault, and submersible automatic line sectionalizers for ac systems are specified.
Keywords: automatic line sectionalizers, cutout type, dry-vault, IEEE C37.63TM, pad-mounted,
sectionalizers, submersible
IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics
Engineers, Incorporated.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Notice and Disclaimer of Liability Concerning the Use of IEEE Documents: IEEE Standards documents are developed
within the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (IEEE-SA)
Standards Board. IEEE develops its standards through a consensus development process, approved by the American National
Standards Institute, which brings together volunteers representing varied viewpoints and interests to achieve the final product.
Volunteers are not necessarily members of the Institute and serve without compensation. While IEEE administers the process
and establishes rules to promote fairness in the consensus development process, IEEE does not independently evaluate, test, or
verify the accuracy of any of the information or the soundness of any judgments contained in its standards.
Use of an IEEE Standard is wholly voluntary. IEEE disclaims liability for any personal injury, property or other damage, of
any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the
publication, use of, or reliance upon any IEEE Standard document.
IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and expressly disclaims
any express or implied warranty, including any implied warranty of merchantability or fitness for a specific purpose, or that
the use of the material contained in its standards is free from patent infringement. IEEE Standards documents are supplied AS
IS.
The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or
provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a
standard is approved and issued is subject to change brought about through developments in the state of the art and comments
received from users of the standard. Every IEEE standard is subjected to review at least every ten years. When a document is
more than ten years old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of
some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the
latest edition of any IEEE standard.
In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on
behalf of, any person or entity. Nor is IEEE undertaking to perform any duty owed by any other person or entity to another.
Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of
reasonable care in any given circumstances or, as appropriate, seek the advice of a competent professional in determining the
appropriateness of a given IEEE standard.
Translations: The IEEE consensus development process involves the review of documents in English only. In the event that
an IEEE standard is translated, only the English version published by IEEE should be considered the approved IEEE standard.
Official Statements: A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board
Operations Manual shall not be considered the official position of IEEE or any of its committees and shall not be considered to
be, nor be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or educational courses, an individual
presenting information on IEEE standards shall make it clear that his or her views should be considered the personal views of
that individual rather than the formal position of IEEE.
Comments on Standards: Comments for revision of IEEE Standards documents are welcome from any interested party,
regardless of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertaining
to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text,
together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is
important to ensure that any responses to comments and questions also receive the concurrence of a balance of interests. For
this reason, IEEE and the members of its societies and Standards Coordinating Committees are not able to provide an instant
response to comments or questions except in those cases where the matter has previously been addressed. Any person who
would like to participate in evaluating comments or revisions to an IEEE standard is welcome to join the relevant IEEE
working group at http://standards.ieee.org/develop/wg/.
Photocopies: Authorization to photocopy portions of any individual standard for internal or personal use is granted by The
Institute of Electrical and Electronics Engineers, Inc., provided that the appropriate fee is paid to Copyright Clearance Center.
To arrange for payment of licensing fee, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive,
Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational
classroom use can also be obtained through the Copyright Clearance Center.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Notice to users
Copyrights
This document is copyrighted by the IEEE. It is made available for a wide variety of both public and
private uses. These include both use, by reference, in laws and regulations, and use in private self-
regulation, standardization, and the promotion of engineering practices and methods. By making this
document available for use and adoption by public authorities and private users, the IEEE does not waive
any rights in copyright to this document.
Errata
Errata, if any, for this and all other standards can be accessed at the following URL:
http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.
Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to
the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant
has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the
IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may
indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without
compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of
any unfair discrimination to applicants desiring to obtain such licenses.
iv
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting
inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or
conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing
agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that
determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely
their own responsibility. Further information may be obtained from the IEEE Standards Association.
v
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Participants
At the time this IEEE standard was completed, the C37.63 Sectionalizer Working Group had the following
membership:
The following members of the individual balloting committee voted on this standard. Balloters may have
voted for approval, disapproval, or abstention.
vi
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
When the IEEE-SA Standards Board approved this standard on 6 March 2013, it had the following
membership:
*Member Emeritus
Also included are the following nonvoting IEEE-SA Standards Board liaisons:
Don Messina
IEEE Standards Program Manager, Document Development
Erin Spiewak
IEEE Standards Program Manager, Technical Program Development
vii
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Introduction
This introduction is not part of IEEE Std C37.63-2013, IEEE Standard Requirements for Overhead, Pad-Mounted, Dry-
Vault, and Submersible Automatic Line Sectionalizers for Alternating Current Systems Up to 38 kV.
This standard has been revised and updated from the 2005 revision of IEEE Std C37.63. This revision
incorporates significant improvements that reflect the present state of the art in automatic line
sectionalizers. These improvements include changes and additions in the following areas:
The term sectionalizer has been restored to the definition in IEEE Std C37.100.
Replacing reference to IEEE Std 1247-1998 by adopting reference to IEEE Std C37.100.1 or
by incorporating specifications within this document.
Restricted fault-making current rating to devices that have independent manual operation, in 5.102.
General structure of the document has been made compatable with IEEE Std C37.100.1.
Revised limits of temperature and temperature rise to be consistent with common requirements
IEEE Std C37.100.1 and the circuit breaker standard, IEEE Std C37.04.
Partial discharge tests have been aligned with IEEE Std C37.60-2012 (IEEE/IEC dual logo).
viii
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
Contents
1. Overview .................................................................................................................................................... 1
1.1 Scope ................................................................................................................................................... 1
1.2 Purpose ................................................................................................................................................ 1
2. Normative references.................................................................................................................................. 2
3. Definitions .................................................................................................................................................. 3
5. Ratings........................................................................................................................................................ 4
5.1 Rating information............................................................................................................................... 4
5.2 Rated maximum voltage (V)................................................................................................................ 5
5.3 Rated insulation level .......................................................................................................................... 7
5.4 Rated power-frequency (f r ) ................................................................................................................. 7
5.5 Rated continuous (normal) current and temperature rise..................................................................... 7
5.6 Rated short-time withstand current (I k ) ............................................................................................... 7
5.7 Rated peak withstand current (I p ) ........................................................................................................ 7
5.8 Rated duration of short-circuit (t k ) ...................................................................................................... 7
5.9 Rated supply voltage of closing and opening devices and of auxiliary and control circuits (U a ) ....... 8
5.10 Rated supply frequency of closing and opening devices and of auxiliary circuits ............................ 8
5.11 Rated pressure of compressed gas supply for insulation and/or operation ........................................ 8
5.12 Rated filling levels for insulation and/or operation. .......................................................................... 8
5.101 Preferred minimum actuating current ratings (series coil sectionalizers) ........................................ 8
5.102 Preferred fault-making current rating .............................................................................................. 8
5.103 Rated load-switching current........................................................................................................... 9
5.104 Rated unloaded transformer switching current ................................................................................ 9
5.105 Preferred line charging and cable charging current ratings ............................................................. 9
ix
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
7. Design (type) tests .................................................................................................................................... 14
7.1 General conditions for tests ............................................................................................................... 14
7.2 Insulation (dielectric) tests................................................................................................................. 17
7.3 Radio influence voltage tests (RIV)................................................................................................... 19
7.4 Measurement of the resistance of circuits.......................................................................................... 19
7.5 Temperature rise test ......................................................................................................................... 20
7.6 Short-time withstand current and peak withstand current tests ......................................................... 21
7.7 Verification of the degrees of protection provided by enclosures ..................................................... 22
7.8 Tightness tests.................................................................................................................................... 22
7.9 Electromagnetic compatibility tests................................................................................................... 22
7.10 Additional tests on auxiliary and control circuits ............................................................................ 22
7.11 X-radiation test procedure for vacuum interrupters......................................................................... 22
7.101 Switching tests............................................................................................................................... 23
7.102 Fault-making tests.......................................................................................................................... 24
7.103 Condition of the sectionalizer after switching tests, short-time withstand current tests, and
fault-making current tests ............................................................................................................. 24
7.104 Mechanical operation tests ............................................................................................................ 25
7.105 Partial discharge tests .................................................................................................................... 26
7.106 Operating duty tests ....................................................................................................................... 27
7.107 Surge current testseries coil sectionalizers................................................................................. 29
7.108 Control electronic elements surge withstand capability tests ........................................................ 30
7.109 Minimum actuating current tests ................................................................................................... 30
7.110 Ice loading test............................................................................................................................... 30
x
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
IMPORTANT NOTICE: IEEE Standards documents are not intended to ensure safety, health, or
environmental protection, or ensure against interference with or from other devices or networks. Implementers
of IEEE Standards documents are responsible for determining and complying with all appropriate safety,
security, environmental, health, and interference protection practices and all applicable laws and regulations.
This IEEE document is made available for use subject to important notices and legal disclaimers.
These notices and disclaimers appear in all publications containing this document and may
be found under the heading Important Notice or Important Notices and Disclaimers
Concerning IEEE Documents. They can also be obtained on request from IEEE or viewed at
http://standards.ieee.org/IPR/disclaimers.html.
1. Overview
1.1 Scope
This standard applies to all overhead, pad-mounted, dry-vault, and submersible single-pole or multipole
alternating-current automatic line sectionalizers for rated maximum voltages above 1 kV and up to 38 kV.
Voltages above 38 kV shall be considered special applications.
In order to simplify the terminology in this standard, the term sectionalizer has been substituted for
automatic line sectionalizer wherever possible.
1.2 Purpose
The purpose of this standard is to describe the requirements for sectionalizers. Qualification to this standard
should give reasonable assurance to the user that equipment meeting the requirements of this standard will
perform in a satisfactory manner, provided that it has been properly selected for the intended application and
is installed in accordance with the manufacturers recommendations.
1
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
2. Normative references
The following referenced documents are indispensable for the application of this document (i.e., they must be
understood and used, so each referenced document is cited in text and its relationship to this document is
explained). For dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments or corrigenda) applies.
ANSI C37.85, American National Standard for SwitchgearAC High-Voltage Power Vacuum Interrupters
Safety Requirements for X-Radiation Limits. 1
IEC 60502, Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1 kV (Um =
1,2 kV) up to 30 kV (Um = 36 kV). 2
IEEE Std 386TM, IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems
Above 600 V.
IEEE Std 1247TM-2005, IEEE Standard for Interrupter Switches for Alternating Current, Rated Above 1000 V.
IEEE Std C37.09 TM-1999, IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a
Symmetrical Current Basis.
IEEE Std C37.42, IEEE Standard Specifications for High-Voltage (> 1000 V) Expulsion-Type Distribution-
Class Fuses, Fuse and Disconnecting Cutouts, Fuse Disconnecting Switches, and Fuse Links and Accessories
Used with These Devices.
IEEE/ISO/IEC Std C37.60-2012, High-Voltage Switchgear and ControlgearPart 111: Automatic Circuit
Reclosers and Fault Interrupters for Alternating Current Systems up to 38 kV.
IEEE Std C37.100.1-2007, IEEE Standard of Common Requirements for High Voltage Power Switchgear
Rated Above 1000 V.
IEEE Std C37.301, IEEE Standard for High-Voltage Switchgear (Above 1000 V) Tests TechniquesPartial
Discharge Measurements.
1
ANSI publications are available from the Sales Department, American National Standards Institute, 25 West 43rd Street, 4th Floor,
New York, NY 10036, USA (http://www.ansi.org/).
2
IEC publications are available from the Sales Department of the International Electrotechnical Commission, Case Postale 131, 3, rue
de Varemb, CH-1211, Genve 20, Switzerland/Suisse (http://www.iec.ch/). IEC publications are also available in the United States
from the Sales Department, American National Standards Institute, 25 West 43rd Street, 4th Floor, New York, NY 10036, USA
(http://www.ansi.org/).
3
IEEE publications are available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, P.O. Box 1331,
Piscataway, NJ 08855-1331, USA (http://standards.ieee.org/).
4
The IEEE standards or products referred to in this clause are trademarks of the Institute of Electrical and Electronics Engineers, Inc.
2
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
3. Definitions
For the purposes of this document, the following terms and definitions apply. The IEEE Standards Dictionary
Online should be consulted for terms not defined in this clause. 5
An asterisk (*) indicates that at the time this standard was approved, there were no corresponding definitions in
IEEE Std C37.100.
automatic line sectionalizer: A self-contained circuit-opening device that automatically opens the main electrical
circuit through it after sensing and responding to a predetermined number of successive main current impulses
equal to or greater than a predetermined magnitude. It opens while the main electrical circuit is de-energized. It
may also have provision to be manually operated to interrupt loads.
cutout type sectionalizers: An automatic line sectionalizer, typically single-phase, that is very similar in outward
appearance to a distribution open dropout type fuse cutout and is used in a distribution cutout fuse support
(mounting).*
NOTECutout type sectionalizers usually have ratings that are associated with the distribution cutout mounting in which they
are applied. 6
minimum actuating current: The minimum actuating current of sectionalizers is the minimum rms (root-mean-
square) current that actuates a counting operation or an automatic operation.*
non-sustained disruptive discharge (NSDD): Disruptive discharge associated with current interruption that does
not result in the resumption of power frequency current or, in the case of capacitive current interruption, does not
result in current in the main load circuit.
series coil sectionalizer: A sectionalizer in which main circuit current impulses above a specified value, flowing
through a solenoid or operating coil, provide the energy required to operate the counting mechanism.
5
IEEE Standards Dictionary Online subscription is available at:
http://www.ieee.org/portal/innovate/products/standard/standards_dictionary.html.
6
Notes in text, tables, and figures are given for information only and do not contain requirements needed to implement this standard.
3
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Subclause 2.1.2 of IEEE Std C37.100.1-2007 applies with the following addition.
i) Flooding
A Submersible Automatic Line Sectionalizer (subsurface or vault) that is installed in a below-grade enclosure
may be subject to occasional flooding to a depth not exceeding 3 m above the top of the switchgear.
j) Icing conditions
The ice coating shall be considered in the range from 1 mm up to, but not exceeding, 20 mm.
Subclause 2.2, and all of its subclauses, of IEEE Std C37.100.1-2007 apply.
5. Ratings
The list of ratings given in the first paragraph of Clause 4 of IEEE Std C37.100-2007.1 does not apply and is
replaced by the following list of ratings.
The following switching ratings are optional; they only apply to sectionalizers that are designed for the
respective switching ratings.
4
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
The rated maximum voltage indicates the upper limit of the highest voltage of systems for which the switchgear is
intended. The preferred values of rated maximum voltage are given in Table 1 and Table 2. Special ratings for
series coil sectionalizers are given in Annex B.
5
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Table 1 Preferred voltage ratings for sectionalizers (except those covered in Table 2)
Rated power-frequency Rated power-frequency
Line no. Rated maximum Rated lightning impulse
dry withstand voltage wet withstand voltage
(See Note 1) voltage (kV) withstand voltage (kV)
(kV) (kV)
(See Note 2)
(See Note 2) (See Note 2)
Col. 1 Col. 2 Col. 3 Col. 4 Col. 5
1 15.0 95 36 30
2 15.5 110 50 45
3 27.0 125 60 50
4 38.0 150 70 60
11 12.0 75 28 28
12 17.5 95 38 38
13 24.0 125 50 50
14 36.0 170 70 70
NOTE 1Lines 11 to 14 refer to distribution systems commonly found outside of North America; the test withstand
levels in column 3 and 4 were selected from Table 1a of IEC 62271-1-2007 [B2].
NOTE 2Cutout type sectionalizers usually have ratings that are associated with the distribution cutout mounting in
which they are applied. IEEE Std C37.42 gives preferred values for the distribution cutout fuse support.
NOTE 1 Lines 11 to 14 refer to distribution systems commonly found outside of North America; the test withstand
levels in column 3 and 4 were selected from Table 1a of IEC 62271-1-2007.
NOTE 2 The rated power-frequency dry withstand voltage for North America (line 1, line 3, and line 4) is reduced, as
compared to Table 1, to take into account the reduced withstand capability of some cable components (i.e., elbows, tee
connectors).
NOTE 3DC voltage testing of field-aged cables is not a recommended practice. Refer to IEEE Std 400.1 [B3] and
IEEE Std 400.2 [B4] for guidelines on testing of dielectric shielded cables. Refer also to IEEE Std 433 [B5] for
comparisons of some characteristics of high-voltage testing using 60 Hz ac, dc, and 0.1 Hz methods. The dc withstand
test requirement on the sectionalizer demonstrates its capability to withstand either dc or VLF testing of connected cables.
6
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
The preferred values of insulation level voltage are given in Table 1 and Table 2.
In these tables, the withstand voltage applies at the standardized reference atmosphere [temperature (20 C),
pressure (101.3 kPa), and humidity (11 g/m3)] specified in IEEE Std 4TM. Insulation withstand capability is
affected by altitude. For special service conditions, see 4.2.
Subclause 4.4.1 of IEEE Std C37.100.1-2007 applies with the following additions.
Series coil sectionalizers have special ratings determined by the series coil itself. The continuous current
and the load-switching current ratings of series coil sectionalizers are given in Annex B (see Table B.1
and Table B.2).
Preferred values for the rated short-time withstand currents for series coil sectionalizers are given in Table B.2.
Preferred values for the rated short-circuit withstand current of the main circuit of all other sectionalizers are as
follows: 1 kA, 1.25 kA, 2 kA, 4 kA, 6 kA, 8 kA, 10 kA, 12.5 kA, 16 kA, or 20 kA.
Subclause 4.6 of IEEE Std C37.100.1-2007 applies with the following modification.
The preferred peak withstand current levels for series coil sectionalizers are given in Table B.2.
7
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Sectionalizers shall also have a related, required capability for a 10 s short-time withstand current. The preferred
10 s short-circuit withstand current rating is 32.5% of the rated 1 s short-time withstand current rating.
NOTEThe 1 s and 10 s short-time withstand current tests provide two points on a damage curve to assist the
user in coordinating the device with upstream reclosers and downstream fuses and transformers. Refer to IEEE
Std C37.48.1 [B6] for additional information.
5.9 Rated supply voltage of closing and opening devices and of auxiliary and control
circuits (U a )
5.10 Rated supply frequency of closing and opening devices and of auxiliary circuits
5.11 Rated pressure of compressed gas supply for insulation and/or operation
For series coil sectionalizers, the preferred minimum actuating current ratings are given in Annex B.
For sectionalizers designed to have a fault-making rating, the preferred fault-making current is the power-
frequency, 1 s rated short-time withstand current, expressed in symmetrical rms amperes. The sectionalizer shall
have the related ability to make and carry an asymmetrical current with a peak current of 2.6 times the
symmetrical 1 s rated short-time withstand current, the circuit X/R being approximately 17 at 60 Hz.
Only sectionalizers having a closing speed that is independent of operating personnel can have a fault-making
current rating. Sectionalizers having a closing speed that is dependent on operating personnel may have a making
current capability, which indicates that successful circuit closing is dependent upon proper operation of the
device. See 6.10.
The fault-making current rating carries the requirement of a design verification test and the rating is assigned to
the sectionalizer on its nameplate. A making current capability is an asserted capability of the device by the
manufacturer under conditions specified by that manufacturer. A making current capability is not shown on the
nameplate.
8
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
The rated load-switching current is the maximum rms symmetrical power-frequency load current flowing in a
circuit that the sectionalizer shall be required to make and interrupt at its rated maximum voltage.
The rated unloaded transformer switching current is the maximum transformer exciting current that the switch
shall be required to make and interrupt at its rated maximum voltage. The current is expressed in rms symmetrical
amperes. Optionally, the rating may be expressed as the maximum transformer size associated with the exciting
current that can be switched.
NOTEThe making current may include a transient current several orders of magnitude larger than that of the
rated unloaded transformer switching current.
The preferred line charging and cable charging interrupting current ratings for sectionalizers having this
capability are as given in Table 3.
Table 3 Preferred line charging and cable charging switching current ratings
12.0 2 10
17.5 2 10
24.0 5 25
36.0 5 40
NOTEThe first three lines refer to voltages commonly specified in North America. The last
four lines refer to distribution systems commonly found outside of North America (see Note 1
of Table 1 and Table 2).
Subclause 5.1, and its subclauses, of IEEE Std C37.100.1-2007 apply with the following addition.
When oil is used as an insulating medium, provision shall be made to obtain a bottom oil sample.
9
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
A sectionalizer with a metal housing shall have provisions for the connection of a ground lead.
The grounding connector shall accommodate a ground conductor of a size adequate to conduct the rated 1 s short-
time withstand current of the sectionalizer.
Pad-mounted, dry-vault, and submersible sectionalizers shall have an additional grounding connection for each
three-phase set of cable entrances.
At the present time, there are no requirements defined for this subject.
At the present time, there are no requirements defined for this subject.
At the present time, there are no requirements defined for this subject.
At the present time, there are no requirements defined for this subject.
Subclause 5.10 of IEEE Std C37.100.1-2007 applies with the following additions.
10
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Series coil sectionalizers shall be provided with a separate nameplate that can be changed when the coil is
changed and is permanently marked with the following information:
Nameplates shall be securely fixed in position and visible from the normal operating position.
NOTE 1The abbreviation in column (2) may be used instead of the term in column (1). When the term in
column (1) is used, the word rated is not required.
NOTE 2SI metric units are preferred; alternate units in parentheses ( ) are acceptable alternates.
11
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Subclause 5.11 of IEEE Std C37.100.1-2007 applies with the following addition.
Interlocking devices may be specified for reasons of safety and/or convenience but are not covered by this
standard.
Subclause 5.12 of IEEE Std C37.100.1-2007 applies with the following addition.
If a position indicator is provided, the preferred colors are red to signify closed and green to signify open. If the
words OPEN or CLOSED are included on the indicator, they should be in contrasting colors.
When indicators are used on stored energy operating mechanisms, the following colors are preferred subject to
any local codes or indicator requirements:
a) Yellow background with the word charged in black letters for charged mechanism
b) White background with the word discharged in black letters for discharged mechanism
As an alternative, red letters on a white background for both indicators may be used.
6.101 Counters
If an operations counter is provided, it shall indicate the total number of tripping operations of the sectionalizer.
The counter shall be visible from the normal operating position.
6.102 Instruction
Instruction manuals for sectionalizers shall be supplied with the equipment. These may include directions for
inspection, storage, unpacking, assembling, and testing the sectionalizer. Additional information may be
contained in maintenance manuals and spare parts lists, which may be available from the manufacturer.
Operating instructions shall include sufficient information to avoid potentially hazardous conditions if a
sectionalizer is not rated for fault closing or load switching.
12
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
For connection of bare conductors, bushing terminals shall accommodate conductors of a size adequate to
conduct the rated continuous current of the sectionalizer without exceeding the appropriate temperature rise given
in 5.5.2.
For submersible sectionalizers, bushings shall accommodate cable terminations in accordance with
IEEE Std 386TM or IEC 60502, unless specified by the user.
Tanks, cabinets, and all appurtenances shall be made of corrosion-resistant material or provided with an impact
and corrosion-resistant finish. Equipment shall be suitable for storage in uncovered areas.
Lifting lugs shall be provided and positioned so that the equipment will remain level when lifted. The lugs shall
be designed and located to avoid interference between lifting slings and any attachments, such as bushings and
operating handles, and to avoid scratching or marring the finish during handling.
Pad-mounted enclosures shall meet the requirements of IEEE C57.12.28. Pad-mounted equipment shall be
constructed so that it can be lifted into place on the pad without disturbing the entrance cables.
Lifting provisions used on pad-mounted equipment shall be designed to not protrude above the top of the cabinet
and shall be recessed so that no part of the lifting provision protrudes past the vertical plane. Any lifting provision
not meeting the requirement listed above shall be removable after installation and reusable, should the equipment
need to be moved, repositioned, or replaced.
All cable terminating compartment access doors shall have padlocking provisions. Unless otherwise specified,
these access doors shall also have pentahead bolt securing features as shown in IEEE C57.12.28. Compartment
doors shall have a positive means of latching in the open position and to the extent practical should be large
enough to facilitate working in the equipment. Pad-mounted equipment enclosure coating systems shall meet the
requirements of IEEE C57.12.28.
Sectionalizers shall be provided with a manual operating means to both open and close the sectionalizer.
If a fault-making rating is assigned, the manual closing shall be independent operation, that is, independent of
operating personnel. If a fault-making rating is not assigned, the manual closing may be dependent operation. See
5.102.
13
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Manual control is defined as control in which the main devices under control, whether manually or power
operated, are controlled by an attendant. (Refer to IEEE Std C37.100.)
The design (type) tests are for the purpose of proving the characteristics of the sectionalizer, its operating device,
and auxiliary equipment.
When a manufacturer is requesting a certification or type test report, the manufacturer must submit to the testing
laboratory drawings and other data containing sufficient information to unambiguously identify by type the
essential details and parts of the automatic line sectionalizer presented for test.
The definition of an automatic line sectionalizer includes its automatic control. The manufacturer shall include in
the information provided to the testing laboratory sufficient information to identify the control used in the design
tests. Where appropriate, this information shall include model number, serial number, firmware revision, software
revision, and other appropriate control software information.
The definition of a cutout type sectionalizer includes a fuse type support. This support is integral to the dielectric
capability of the device. The manufacturer shall include in the information provided to the testing laboratory
sufficient information to identify the mounting or support used in the design tests. Where appropriate, this
information shall include make, model number, and rating.
The results of all design (type-tests) shall be recorded in design-test (type-test) reports containing sufficient data
to prove compliance with the ratings and the test clauses of the relevant standards and sufficient information shall
be included so that the essential parts of the automatic line sectionalizer can be identified.
The definition of an automatic line sectionalizer includes its automatic control. The control shall be considered an
essential part of the automatic line sectionalizer in the test report, including its model number, serial number,
firmware revision, software revision, and other appropriate control schemes.
The definition of a cutout type sectionalizer includes a fuse type support. This mounting or support shall be
considered an essential part of the cutout type sectionalizer and noted in the test report including its make, model
number, and rating.
14
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
A cutout mounted sectionalizer may require the temporary attachment of an auxiliary device to perform the
switching functions of a sectionalizer if such ratings are assigned. If such a device is required, it shall be
considered an essential part of the switchgear and noted in the test report including its make, model number, and
rating.
Tests to verify the ratings and performance requirements of all sectionalizer shall be in accordance with Table 5.
The sectionalizer shall be new and in good condition, and tests shall be applied before the device is put into
commercial use.
A resistance check shall be performed on the sectionalizer prior to any current or mechanical test, see 7.4. For
cutout mounted sectionalizers, the resistance check shall be measured between the top and bottom conductor
connectors of the cutout device.
The sectionalizer shall be mounted in a manner closely approximating the normal service conditions for which it
is designed. Sectionalizers intended for pole or frame mounting may be mounted at any convenient height above
ground. If the sectionalizer normally requires control apparatus, the control apparatus shall be connected during
the tests observing the following minimum requirements:
a) The control shall be mounted on the sectionalizer as intended by the manufacturers design or positioned
within 2 m of sectionalizer phase terminals under test, and
b) The sectionalizer shall be connected to the control apparatus with the manufacturers approved cable
whose length shall be the maximum allowed by the manufacturer except that it need not exceed 6 m.
If the control apparatus is intended by the manufacturer to always be integrally mounted to, or within, the
sectionalizer structure, it shall be considered in compliance with a) and b) above with a zero length control cable.
15
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Summary of test
Subclause
Type of test (see appropriate test specifications for Exceptions or conditions
no.
details of each test)
All parts of the sectionalizer, and control apparatus where used, that are normally grounded shall be grounded by
a lead attached to the ground terminal in a manner not to decrease the withstand voltage.
The frequency of the power supply voltage shall be the rated value 5%, except that tests at either 50 Hz or
60 Hz may be used to qualify for both rated power frequencies.
The sectionalizer shall perform satisfactorily over the full range of control voltages specified in 5.9. This
requirement shall be met by performing the standard operating duty as specified in 7.106.3. This requirement does
16
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
not apply to tests that do not include open or close operating duties, for example, dielectric withstand and
continuous current tests.
Subclause 6.2 of IEEE Std C37.100.1-2007 applies with the following additions.
The tests shall be performed with the test voltages given in Table 1 or Table 2 using the line number specified by
the manufacturer.
Rated insulation levels for cutout mounted sectionalizers are based in part on the rating of the fuse support or base
identified by the manufacturer in 7.1.2 and 7.1.3. Automatic line sectionalizer shall be capable of withstanding,
without damage to the automatic line sectionalizer and associated control apparatus, if any, the test voltages of 7.2
when tested in accordance with 7.1.
Insulation tests of automatic line sectionalizers shall be performed only when the automatic line sectionalizer is
completely isolated from all system voltages.
Subclause 6.2.2 of IEEE Std C37.100.1-2007 applies with the additions given in 7.2.6.1
Subclause 6.2.3 of IEEE Std C37.100.1-2007 applies with the following additions.
a) On overhead sectionalizer, electrical connections shall be made by means of bare wire, inserted in each
terminal. These bare wires shall project in such a manner as not to decrease the withstand value. Any
necessary bends may be made at the terminals. The test lead connections shall be made to the wires
projecting from the terminals. Terminals shall be representative of those used in service.
b) On pad-mounted, submersible, and dry-vault sectionalizers connections shall be made through a cable
termination similar to that for which the sectionalizers was designed. If terminations capable of meeting
the specified dielectric voltage are not available, other terminations (bushing or connectors, or both) may
be substituted for the purpose of performing these tests. Breakdown of the termination interface used for
the test connections does not constitute a failure of the entity. The termination interface may be replaced
and testing continued.
Subclause 6.2.4 of IEEE Std C37.100.1-2007 applies with the following addition.
Refer also to IEEE Std C37.100.1-2007, subclause 6.2.6.2 for vacuum interrupter based sectionalizers.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Subclause 6.2.5.1 of IEEE Std C37.100.1-2007 applies with the following addition.
Single-phase sectionalizers shall be tested for conditions 1, 4, and 7 of Table 9 of IEEE Std C37.100.1-2007. The
connections of the terminals for phases B and C are not applicable.
The tests shall be performed with the test voltages given in Table 1 or Table 2.
Subclause 6.2.6.1 of IEEE Std C37.100.1-2007 applies with the following addition.
a) Wet tests shall not apply to sectionalizers within weather-resistant enclosures or those utilizing
submersible cables or terminations.
b) IEEE values of rated maximum voltage, column 2 of Table 1 and Table 2 given in lines 1 through 4:
Power-frequency withstand test voltages shall be applied in accordance with IEEE Std 4, with a peak
value equal to 1.414 times the rated power-frequency withstand dry and wet test values given in columns
4 and 5 of Table 1 and Table 2. The test duration shall be 60 s for the dry test.
The preferred method for wet tests shall be the conventional procedure-practice in the US of IEEE Std 4
with a test duration of 10 s. The standard test procedure of IEEE Std 4 is allowed as an alternate.
NOTEFuture designs should standardize the wet test procedure by adopting the standard test procedure as
defined in IEEE Std 4.
c) IEC values of rated maximum voltage, column 2 of Table 1 and Table 2 given in lines 11 through 14:
Power-frequency withstand test voltages shall be applied in accordance with IEEE Std 4, with a peak
value equal to 1.414 times the rated power-frequency withstand dry and wet test values given in columns
4 and 5 of Table 1 and Table 2. The test duration shall be 60 s for the dry test.
For the IEC values of rated maximum voltage, the wet test method of test shall be the standard test
procedure of IEEE Std 4 with a test duration of 60 s.
WARNING
When performing tests involving open contacts in vacuum, adequate precautions such as shielding or distance
should be used to protect test personnel against the possibility of X-radiation occurrences due, for example, to
incorrect contact spacing or the application of voltages in excess of those specified. For appropriate shielding,
distances, and exposure limits, refer to ANSI C37.85.
18
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Subclause 6.2.6.2 of IEEE Std C37.100.1-2007 applies with the following addition.
The voltage levels shall be equal to or greater than those that are specified.
7.2.6.101.1 Application
A dc withstand voltage test is required on sectionalizers using pad-mounted, dry-vault, and submersible cable
connectors. This test is in addition to the power-frequency withstand test in 6.2.6.1 of IEEE Std C37.100.1-2007.
NOTEA dc withstand voltage test is required as the design test on the sectionalizer. It is included to verify that the
switchgear can withstand the same dc or very low frequency test voltages applied in the field to cables where the cables may
still be connected to the switchgear.
The test voltage applied shall be the value given in column 6 of Table 2.
The dc power source for the dc withstand test shall be capable of supplying a minimum of 10 mA before tripping
out on overload. The test shall be considered to have failed if there is:
The test shall be considered to have passed if the test device withstands the test voltage with a leakage current that
does not exceed 10 mA. Non-sustained disruptive discharges (NSDD) may occur and are allowed.
NOTEThese test criteria recognize the likelihood that a small leakage current may pass through an insulating medium or
across an insulating surface while still supporting the high dc voltage. This is particularly true of vacuum interrupters.
19
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Subclause 6.5.2 of IEEE Std C37.100.1-2007 applies with the following addition.
The following arrangement shall be allowed as an alternate to the arrangement of equipment specified in
subclause 6.5.2 of IEEE Std C37.100.1-2007 in which case the 5 K difference of temperature rise between the
terminals and the external connections shall not apply.
The sectionalizer shall have a conductor connected to each terminal having a minimum length of 1.2 m. For
sectionalizers with bushings designed for connection to bare copper conductors, use cables no larger than listed in
Table 6. For aluminum cables use Table 7. For sectionalizers designed for use with submersible or insulated
cables, the cables shall be chosen for the rated current and voltage of the sectionalizer. Refer to IEEE Std 386 for
guidance. The connection shall be made to the ends of these conductors.
Size of leads
Rated continuous
(normal) current (A)
AWG kcmil mm2
20
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
7.6.1 General
Main circuits and, where applicable, the grounding circuits of the switchgear shall be subjected to tests to prove
their ability to carry the rated peak withstand current and the rated short-time withstand current. The tests shall be
made at the rated frequency with a tolerance of 10% at any suitable voltage and starting at any convenient
ambient temperature.
If a family of sectionalizer ratings utilize the same design and components for the main current-carrying circuit,
the tests shall be made on the smallest and largest short-time withstand current rating assigned to the family.
NOTESome sectionalizer designs achieve different current ratings by a change in the sensing and control elements alone.
Subclause 6.6.2 of IEEE Std C37.100.1-2007 applies with the following modifications.
Sectionalizers shall carry the rated short-time currents as given in 5.6 and 5.8 or in Table B.2. The test is required
for only one counting operation at each test duration given in 5.8.
21
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
After the test, the switchgear shall not show significant deterioration, shall be capable of operating normally,
carrying its rated normal current continuously without exceeding the temperature rise limits specified in Table 3
of C37.100.1, and withstanding 80% of the rated dry power frequency withstand voltage specified under dielectric
tests.
If the mechanical switching device has a rated making and/or breaking capacity, then the condition of the contacts
shall not be such as to affect the performance materially at any making and/or breaking current up to its rated
value.
a) A no-load operation of the mechanical switching device shall be performed immediately after the test, and
the contacts shall open at the first attempt.
b) The resistance of the main circuit shall be measured according to 6.4.1 of C37.100.1. If the resistance has
increased by more than 200%, and if it is not possible to confirm the condition of the contacts by visual
inspection, it may be appropriate to perform an additional temperature rise test.
This standard does not cover specifications for degrees of protection provided by enclosures.
This standard does not cover any additional specifications for tests on auxiliary and control circuits.
22
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Switching tests are performed to determine the adequacy of the design of a particular type, style, or model of
switch or its component parts to meet its assigned switching abilities.
Switching ratings are optional ratings for sectionalizers covered by this standard; see Clause 5.
Subclause 8.3.1 of IEEE Std 1247-2005 applies with the following exceptions and modifications.
1) Load-switching tests are performed as part of the operating duty tests for load-interrupting
sectionalizers, see 7.106.
2) Loop-switching and 5% load-switching tests in Table 5 of IEEE Std 1247-2005 are not required.
d) Unit testing as described in 8.3.1.9 of IEEE Std 1247-2005, is not permitted.
Subclause 8.3.2.1 of IEEE Std 1247-2005 applies with the following modifications.
Load switching is not a required rating. Sectionalizers that are rated for load-switching operation shall have load-
switching tests performed as part of the operating duty tests specified in 7.106.
Subclause 8.3.2.3 of IEEE Std 1247-2005 applies with the following modifications.
Cable-charging switching is not a required rating. Sectionalizers that are rated for operation on grounded wye
cable circuits shall be capable of interrupting the charging current of unloaded lengths of single-phase shielded
cable. The purpose of this test is to demonstrate the capability of interrupting the capacitive switching current
rating of the sectionalizer.
Cable charging switching tests, if required, apply only for shielded cables (C1 = C0 in Figure 7 of IEEE Std 1247-
2005).
Subclause 8.3.2.5 of IEEE Std 1247-2005 applies with the following modifications.
Unloaded transformer switching is not a required rating. Sectionalizers that are rated for unloaded transformer
switching operation shall be tested with a current between 3% and 4% of continuous current rating of the
sectionalizer.
23
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
7.102.1 General
The fault-making current verification test is required on sectionalizers that have been assigned a fault-making
current rating. Sectionalizers that rely on dependent manual operation shall not be assigned a fault-making current
rating; see 5.102.
The test to prove the capability to meet the rated fault-making current as given in 5.6 and 5.102 shall be the
requirements in Table 8, duty 4. The sectionalizer shall pass a test with a peak current of 2.6 times the
symmetrical 1 second rated short-time withstand current, the circuit X/R being approximately 17 at 60 Hz. The
duration of the current flow shall be no less than 10 cycles. As stated in 7.106.1 and 7.106.3d), repeated tests may
be required to achieve the required peak current as it is not always possible to reach the peak current value due to
pre-arcing (see subclause 8.5 of IEEE Std 1247-2005). Determine the magnitude of current in accordance with
Clause 7 of IEEE Std C37.09-1999.
7.103 Condition of the sectionalizer after switching tests, short-time withstand current
tests, and fault-making current tests
During and following the specified tests, the condition of the sectionalizer shall be as follows:
a) Maintenance: During the test, the switch shall have functioned without failure and without maintenance or
replacement of parts.
b) Mechanical:
1) After performing the specified test duties, the mechanical function and the insulators of the used
switch shall be practically in the same condition as before the tests. Visual inspection of the used
switch after tests is usually sufficient for checking this requirement. The arcing contacts or any other
specified renewable parts may be worn. The quality of the oil, used for arc extinction in oil switches,
may be impaired and its quantity reduced from the normal level. There may be deposits on
insulators caused by the decomposition of the arc extinguishing medium.
2) The switch shall be capable of operating normally. Visual inspection and no-load operation of the
used switch after tests are usually sufficient for checking this requirement.
c) Electrical:
1) The switch shall be capable of carrying its rated continuous current without experiencing a thermal
run-away but not necessarily without exceeding rated temperature rise in the closed position. A
contact resistance check shall be made in accordance with 7.4 to determine the switchs current
carrying ability. The value of contact resistance shall be less than 200% of that before the test. If the
contact resistance is greater than 200% of that before the test, a continuous current test with no
thermal runaway shall be performed. Thermal runaway means that the temperature does not stabilize
and continues to increase as a trend.
2) The power-frequency dry withstand voltage of the used switch shall not be reduced below 80% of
the rated power-frequency dry withstand voltage by deterioration of insulating parts. A rated power-
frequency dry withstand voltage test shall be performed at 80% of the rated power frequency dry
withstand voltage to evaluate the insulating ability.
24
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
d) Unless the switching tests, short-time withstand current tests, and fault-making current tests have
consumed the life of the sectionalizer, as defined by the switch manufacturer, the sectionalizer shall be
capable of performing its rated switching duties. A suitable interrupting test shall be performed.
The sectionalizer shall meet the conditions of environment and mechanical duty when tested in accordance with
7.1 and the following subclauses.
The sectionalizer shall meet the requirements of the environmental and mechanical duties when the conditions of
7.1 are met and it is tested in accordance with the following subclauses.
The sectionalizer shall be subjected to 500 automatic lockout operations without maintenance. The interval
between operations shall be the shortest allowed by the rest time of the counting mechanism.
The condition of the sectionalizer after the mechanical duty test shall be in accordance with 7.104.3.
A sectionalizer shall be tested for proper operation and reset at the lowest temperature for which it is designed.
After the sectionalizer has come to a steady temperature, it shall be operated with the control set for 1, 2, and 3
shots to lockout. Heater performance shall be verified during this test.
The condition of the sectionalizer after the cold temperature test shall be in accordance with 7.104.3.
7.104.3 Condition of the sectionalizer after mechanical and cold temperature tests
During and after the tests, the sectionalizer shall be in such a condition that it is capable of operating normally,
carrying its rated normal current, and withstanding the voltage as defined below.
During the tests, the sectionalizer operates on command and does not operate without command;
During and after the tests, any distortion of mechanical parts is not such that it adversely affects the
operation of the sectionalizer or prevents the proper fitting of any replacement part;
The sectionalizer shall be capable of automatic and manual operation according to its design.
a) Resistance value according to 7.4 tshall not have increased by more than 50 % or 100 , whichever is
greater;
b) The sectionalizer shall be capable of passing a power-frequency withstand test. The withstand test voltage
shall be 80 % of the values shown in column 4 of Table 1 and Table 2.
For devices that have both interrupting and non-interrupting gaps, each gap shall be tested in its respective open
position. Gaps that may be open continuously must withstand 80% of the values shown in column 4 of Table 1
and Table 2. Gaps that may be exposed to voltage stresses for short durations significantly less than one minute
25
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
shall be capable of withstanding a voltage to be stated by the manufacturer but not less than the rated maximum
voltage of the device.
7.105.1 General
Partial discharge tests shall be performed on all sectionalizers that use a nonself-restoring dielectric as the
primary insulation (e.g., solid dielectric). For purposes of this clause, primary insulation shall be considered to be
the predominant insulation between phases and/or to ground (e.g., solid dielectric).
These tests shall be performed in accordance with IEEE Std C37.301. The minimum detection sensitivity for
which these tests are conducted shall be 10 pC.
The measuring voltage shall be as specified in 7.105.3. Sectionalizers having two or more voltage ratings shall be
measured on the basis of the highest voltage rating given on the nameplate.
Partial discharge limits are not defined for the general case. Partial discharge limits for the equipment under test
shall be declared by the manufacturer and serve as the guaranteed limit for the routine tests of all units of a similar
design. The actual test values of the type test shall be equal to or less than the manufacturers declared values.
NOTEThere is general agreement that partial discharge testing should be performed on all sectionalizers where the primary
insulating system may be subject to deterioration due to partial discharge. At a minimum, the data will help to monitor process
consistency by the producer and serviceability for the user. The following three reasons have been given for not setting partial
discharge test limits at this time: 1) there is not a sufficient body of evidence to establish a causeeffect relationship between
partial discharge and performance in distribution switchgear; 2) there is not an agreement as to what the limits should be; and
3) appropriate values will depend on the materials, design, and complexity of the equipment. Partial discharge limits at the test
voltage specified in 7.105.3 have been suggested in the 10 pC to 20 pC range for a phase or module tested alone. At the upper
end, a partial discharge limit of 100 pC has been recommended for a complete three-phase assembly. The 100 pC value is
consistent with the Canadian Standard CAN/CSA C22.2 No 31-10 [B1].
The surface of insulators should be clean and dry. The test object should also be at ambient temperature.
Mechanical, thermal, or electrical stressing before the test should be avoided.
The equipment and general method used in making partial discharge measurements tests shall be in accordance
with the recommendations of IEEE Std C37.301.
Tests shall be made with the sectionalizer or test module in the closed and open positions. All surfaces that are
normally grounded shall be grounded and all surfaces isolated that are normally isolated. The general test
procedure shall be as follows where:
Vr
Pre-stress voltage Vpre stress 1.3 1.5
3
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
The inception voltage V i is the lowest applied voltage at which the magnitude of a partial discharge (PD) pulse
quantity becomes equal to or exceeds 10 pC unless otherwise defined by the manufacturer specific to his
equipment.
The extinction voltage (Ve) is the highest applied voltage at which the magnitude of a chosen PD pulse quantity
becomes equal to, or less than, 10 pC unless otherwise defined by the manufacturer specific to his equipment.
a) Starting at a voltage level less than 60% of V pre-stress , raise the voltage up to or above V pre-stress ; note and
record the inception voltage (V i ).
b) Maintain the voltage at the pre-stress voltage level for 60 s.
c) Lower the voltage to the measuring voltage (V pd ). Maintain this voltage for 60 s and then note the partial
discharge level at the end of this period.
d) Note and record the extinction voltage (V e ). The extinction voltage may occur at a voltage level above or
below the measuring voltage. In any case, the extinction voltage level should be noted and recorded.
NOTEAn open gap in a vacuum interrupter may have field emission from rough spots on the cathode contact during partial
discharge tests. This emission is not likely to distort the test results at the voltage level specified above. However, even at this
voltage, and especially at higher voltage levels, field emission currents may lead to erroneous conclusions about the presence
of partial discharge in solid insulation parallel to the vacuum gap. Since field emission is only observed on a cathode, the
observation of asymmetrical results with respect to voltage polarity when a dc voltage is applied is then an indication of the
presence of field emission in a vacuum gap instead of a partial discharge in the parallel solid insulation.
7.106.1 General
The operating duty shall consist of the applicable tests specified in 7.106.2 made without maintenance, in the
order given in Table 8 and on the same test sample. However, if the 90% peak is not obtained on the first attempt
of test duty 4, the operating duty sequence may continue on to test duty 5 while a second sample is used to
complete the requirements of test duty 4.
The test samples shall be of the highest continuous current rating of a design. These tests shall prove conformance
with this standard for all lower current ratings of this design. This applies specifically to designs in which the
continuous current rating is dependent on a series coil rating and the current path is otherwise the same for all
current ratings of the design.
The complete operating duty for a sectionalizer design shall consist of each of the test duties in columns 5, 6, 7,
and 8 of Table 8 that are applicable for the design. The test procedures for each test duty shall be as specified in
columns 2, 3, and 4 of Table 8 and the provisions of 7.106.3.
27
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
a) Test duty 1 shall consist of five operations each at one- and two-shots to lockout and 10 operations at
three-shots to lockout.
b) Test duty 2 shall consist of the number of operations in column 2 such that 50% of the operations are
three-shot to lockout; remaining operations may be divided between one- and two-shot to lockout test
duties. Tests shall show that the isolating time from current cessation to sectionalizer contact parting does
not exceed 0.25 s. At least five operations shall be performed at both the maximum and the minimum
voltages given in 5.9. See 7.106.6
c) Test duty 3 should provide a sufficient time interval between non-automatic operations to prevent the
formation of excessive pressures. The power factor of the test circuit shall be as specified in 8.3.2.1 of
IEEE Std 1247-2005. At least five operations shall be performed at both the maximum and the minimum
voltages given in 5.9. See 7.106.6.
d) Test duty 4 shall consist of a sufficient number of non-automatic closing operations to obtain one
operation with 90% to 100% asymmetry. For three-phase sectionalizers, this test shall be made on a three-
phase basis.
e) Test duty 5 shall have a test circuit with a power factor as specified in 8.3.2.1 of IEEE Std 1247-2005.
Sectionalizers shall meet the automatic and non-automatic duties specified without emitting flame or oil.
The condition of the sectionalizer shall be as required in 7.103 with the exception condition 4 does not apply.
After the series of operations equivalent to the standard operating duty, it is not to be inferred that the
sectionalizer can again meet its rating without being inspected and, if necessary, repaired.
28
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
7.107.1 General
A series coil sectionalizer shall be capable of withstanding two current surges of 65 000 A crest having a 5 s
10 s wave shape.
If a coil bypass device is required, it shall be mounted in the sectionalizer in the same manner as furnished for
normal service. The leads from the high-current impulse generator shall be connected to the same terminals of the
sectionalizer.
Following this test, the sectionalizer shall be tested at the minimum actuating current for the design so as to cause
it to go through one automatic operation to lockout.
29
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
At the end of the test, the sectionalizer and the coil bypass device shall be in the following condition:
a) Mechanical. Substantially in the same mechanical condition as at the beginning except for minor arc scars
on any gap electrodes of the coil bypass device. There shall be no indication of external flashover of the
coil bypass device, from the terminals of the coil bypass device to any other parts of the sectionalizer or of
the series coil of the sectionalizer.
b) Electrical. With the coil bypass connected in its normal operating position, the sectionalizer shall be
capable of withstanding rated maximum voltage in the open position and, in the closed position, of
functioning correctly on overcurrent to go through its counting cycle to lockout at the minimum actuating
current for the design.
Control electronic elements supplied with sectionalizers shall withstand, without damage, voltage surges
originating in the low-voltage energy source, in the current or voltage transformers connected to the control
elements, or both, or in the control leads connecting the sectionalizer and the control elements. The surge
withstand capability tests shall be performed as given in 6.13 of IEEE Std C37.60-2003.
Sectionalizers shall meet the rated minimum actuating current within the specified limits of 10% when tested as
specified in 7.1, 7.109.1, and 7.109.2.
The tests shall be made on the smallest and largest actuating current rating or setting of the same design.
The sectionalizer shall be connected to a low-voltage power source of alternating current in series with a means
for increasing the current and of delivering successive current impulses to cause operation of the counting
mechanism.
The sectionalizer, set for one-shot lockout, shall be subjected to sufficient current impulses to verify that it does
not operate below 90% but does operate at 110% of minimum actuating current.
NOTE 2In this subclause, the abbreviation DUT (device under test) refers to the sectionalizer under test.
7.110.1 Introduction
Ice loading tests are design tests performed to determine the rated ice breaking ability of outdoor switching
equipment.
30
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
A procedure is described for producing clear ice coatings which compare with those encountered in nature so that
reproducible tests can be made. For severe ice conditions, a choice is provided between two classes of ice
thickness: 10 mm and 20 mm.
The procedure for producing controlled coatings of ice (comparable with those encountered in nature) is defined
in 7.110.4.5.1.
7.110.2 Applicability
The tests defined in 7.110 shall be performed if the manufacturer claims suitability of the sectionalizer for operation under
conditions where ice formation may exceed 1 mm. Ice loading tests are only required for sectionalizers that have external
moving parts not protected from ice formation that, if frozen in ice, would impair the automatic operation of the device.
NOTEThe cutout type sectionalizer is used in a distribution cutout fuse support. Consult the cutout type sectionalizer
manufacturer for applications under icing conditions.
a) Clear ice. Clear ice results from rain falling through air with a temperature between 0 C (+32 F) and
10 C (+14 F)
b) Rime ice. Rime ice is characterized by a white appearance from the air entrapped during ice formation,
forms from rain falling through air with a temperature below 10 C (+14 F), or from condensation of
atmospheric moisture on cold surfaces
The ice loading test shall be performed with clear ice, which represents the most difficult operating conditions.
Since these coatings may form during a period of rain with initial temperatures above freezing, moving parts may
be filled with water, which may subsequently freeze.
31
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
The type of laboratory must be stated in the test report. Three-pole, group-operated DUTs must be tested as
complete three-pole assemblies; however, single-pole operated DUTs may be tested as complete single-pole
assemblies.
External surfaces shall be free from all traces of oil or grease, since even a thin film of oil or grease will prevent
ice from adhering directly to the surface and will affect the test results.
The test for the ice breaking rating shall be performed for both making and breaking operations. The DUT shall
be tested with representative operating mechanism components, as required for a typical installation in the field.
Test bars, (metal rods or tubes) approximately 3 cm in diameter and 1m in length, shall be mounted at each end of
the test specimenwith their longitudinal axes horizontaland placed to receive the same general wetting as the
DUT. The number of test bars shall provide a fair evaluation of the ice thickness over all parts of the DUT, and in
no case shall less than one test bar per pole be used. Visual inspection of the ice build-up on the DUT shall be
consistent with the test bar measurements.
The thickness of the ice shall be determined on the top surface of the test bars by measurement of the depth of
saw cuts or drilled holes 15 cm (6 in) from each end of the test bar. The average of the ice thickness shall be equal
to or greater than the rated ice breaking ability of the DUT. No measurement shall be less than 83% of this rating.
The DUT shall be completely assembled in a chamber that can be cooled to a temperature of 10 C (+14 F).
The chamber shall be equipped with sprinklers to provide a fine water spray to the entire assembly with general
wetting from above.
The water used in the spray shall be cooled to a temperature between 0 C (32 F) and 3 C (37 F). During a 1 h
wetting period, the chamber ambient temperature shall be held between +5 C (+33 F) and +3 C (+37 F).
Following the 1 h spray period, the ambient temperature shall be lowered to the range of 7 C (+19 F) to 3 C
(+27 F). The spray shall be continued until the rated ice thickness is measured on the top surface of the test bars.
The ice coating shall then cure with the chamber ambient temperature in the range of 7 C (+19 F) to 3 C
(+27 F) for a minimum of 4 h after spray is discontinued. The DUT shall be operated following this curing
period.
Outdoor tests can be performed when the ambient temperature is between 3 C (+27 F) and 15 C (+5 F) and
the wind velocity is below 25 km/h (15 mph). The completely assembled DUT shall be tested in an area equipped
with adequate spray equipment to provide even coverage of the DUT.
32
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
With the ambient temperature above freezing, the DUT shall be given a 1 h wetting period, which will coat the
surface with a fine spray deposit. The wetting shall precede the spray for ice build-up by not more than 4 h.
To obtain uniform coverage, the spray equipment may require adjustment due to wind conditions, or the spray
may be interrupted frequently to permit ice formation. The spray procedure shall be continued until the rated ice
thickness is measured on the top surface of the test bars.
The ice coating shall cure for a minimum of 2 h prior to operation of the DUT. Further temperature decrease
during the curing period will not appreciably affect the test results. The operation test must be completed before
the temperature rises above 3 C (+27 F) and before the radiant heat of the sun changes the characteristics of
the ice.
DUTs shall be operated by automatic control or by a person using a standard operating device. Chopping on
opening (jerking back and forth on the manual operating mechanism) is not permitted on DUTs because these
switches are likely to be in a position to carry significant current when closed, and multiple unsuccessful attempts
at opening or closing are likely to result in significant current arcs being drawn in air.
Automatic power-operated DUTs shall perform successfully on the first power-operated opening or closing
attempt.
The ice test shall be completed when the DUT has been operated through the two separate sequences, a) and b), as
follows:
a) From its iced fully-open position to its fully-closed position, (with proper engagement of the contact
surfaces and proper engagement of any interrupter)
b) From its iced fully-closed position to its fully-open and locked out position (with proper operation of any
interrupter)
The equipment must sustain no damage that will interfere with normal operation. The order of operating
sequences is optional.
If so rated, the equipment shall be capable of circuit interruption during successful opening of the DUT.
Following the successful closing of an iced DUT, the equipment must be capable of any rated circuit interruption
during a subsequent opening operation. During the test, no damage shall be sustained that would impair the
current interruption or dielectric withstand capability. A physical examination of linkages, components, and
alignments shall be made to assure that proper interruption operation and sequencing has been preserved.
Further, following sequence b) above, the device must successfully go through a power frequency wet withstand
test to verify that the dielectric withstand performance has not been compromised. If there is doubt about the
successful performance of the DUT, a temperature rise test, a short-time withstand current test, or a power-
frequency withstand voltage test, as applicable, shall be conducted to verify acceptable performance.
33
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
8.1 General
The routine (production) tests are for the purpose of revealing faults in material or construction. The routine
(production) tests shall be made wherever reasonably practical at the manufacturers facility on each apparatus
manufactured, to ensure that the product is in accordance with the equipment on which the type tests have been
passed.
The routine (production) tests given in this standard comprise the following:
A short-duration power-frequency voltage shall be applied. The test shall be made according to IEEE Std 4 and
7.2, on the complete apparatus or on each separate complete pole, or on each transport unit. Equipment shall be in
new, clean, and dry condition.
The test voltage shall be that voltage specified in Table 1 or Table 2. The duration of the test may be reduced to
10 s if a voltage of 110% of that specified is used.
Control, secondary wiring, and accessory devices shall be checked to verify that all connections have been made
correctly. Devices and relays, if needed, shall be checked by actual operation where feasible. Those circuits for
which operation is not feasible shall be checked for continuity.
For sectionalizers that require the media to be contained within its enclosure to perform as designed, a tightness
test must be performed as described in a). For sectionalizers that are required to be submersible, the tightness test
must be performed as described in b).
a) Tests shall be performed at normal ambient air temperature with the assembly filled to correspond to the
manufacturers test practice. Sniffing type test equipment may be used.
b) A suitable leak test shall be performed on submersible sectionalizers to verify that they will operate under
service conditions as outlined in 4.1.2.
34
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Sectionalizers shall be subjected to the following calibration, where applicable, for conformance to published
operating characteristics. Calibration may be performed on the individual control elements sub-assembly prior to
final assembly on the sectionalizer. When the latter is done, the complete assembly shall be tested to assure that
the device will open the sectionalizer. The calibration may be performed in any order deemed appropriate by the
manufacturer.
Partial discharge tests shall be performed on all sectionalizers that use a non self-restoring dielectric as the
primary insulation. For purposes of this clause, primary insulation shall be considered to be the predominant
insulation between phases and/or to ground, (e.g., solid dielectric). Tests shall be performed as specified in 7.105
with the following exceptions:
35
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Annex A
(informative)
X/R ratios
A.1 General
A general understanding of circuit time constant () and X/R ratio and associated peak currents is necessary for
the proper design, testing, and application of switchgear. The mechanical stresses associated with fault withstand
2
or fault making, are in relation with the square of the peak current ( ipeak ) and the thermal stress associated with
pre-arcing or fault current interruption is a complex relation of the arc voltage, the arcing time and the total charge
(integral of the arcing current).
An electrical circuit may be defined by its main series components that are the inductance (L or X) (X = 2f r L)
and resistance. The circuit time constant () is defined by the ratio L/R, = L/R. The ratio X/R is frequency
dependent (i.e., a time constant of 45 ms will lead to an X/R ratio of 14 at 50 Hz and 17 at 60 Hz).
For a three-phase fault, the positive sequence components of the circuit shall be considered ( = L1/R1, X/R =
X1/R1). For a phase to ground fault, the positive and zero sequences components shall be considered as follows:
2 L1 L0 X 2 X1 X 0
or
2 R1 R0 R 2 R1 R0
where:
The maximum asymmetrical current occurs when the fault is initiated at zero voltage. Such a fault may be
associated with lightning flashover or with a switch or a breaker closing or reclosing on a faulted circuit or a
temporary ground. If a three-phase switching device is used, an asymmetrical fault current will occur in one of the
phases, the value of which will be between 87% and 100% of maximum asymmetrical current.
36
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
The instantaneous current of a single-phase circuit will be in accordance with Equation (A.1).
i(t ) 2 I sint sin e t / (A.1)
where:
The maximum asymmetry will occur when the fault is initiated at zero voltage ( = 0).
The peak of the asymmetrical current (ipeak) is the maximum of the Equation (A.1). The peak factor K is
ipeak/I.
Table A.1 is a tabulation of the peak factors for both 50 Hz and 60 Hz over a range of time constants.
37
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for
Alternating Current Systems Up to 38 kV
Annex B
(normative)
Series coil sectionalizers have been used globally for many years. Traditionally, series coil designs operate
in a current-sensing mode as opposed to a time-sensing or voltage-sensing mode.
The current ratings of series coil sectionalizers are determined by the series coil itself and by the rating of
the contacts. The preferred ratings of series coil sectionalizers, as established in earlier revisions of this standard,
are given in Table B.1 and Table B.2.
The rating of a series coil sectionalizer shall be as given in Table B.1 and Table B.2.
The preferred ratings unique to a series coil sectionalizer are given in Table B.1 and Table B.2. Any rating
not specifically listed in Table B.1 or Table B.2 shall be taken from the appropriate subclauses of Clause 5 of
this standard.
Table B.1Preferred ratings and performance characteristics for series coil automatic line
sectionalizers
Rate lightning Rated power-frequency
Rated impulse withstand voltage (kV) Currenta (A)
maximum withstand
Line no. Load current
voltage (kV) voltage (kV) 60 s dry 10 s wet Continuous switching
Col. 1 Col. 2 Col. 3 Col. 4 Col. 5 Col. 6 Col. 7
Single-phase sectionalizers
1 15.0 95 35 30 140 308
Three-phase sectionalizers
5 15.5 110 50 45 200 440
a
See Table B.2 for data on current ratings for all continuous current ratings.
38
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers
for Alternating Current Systems Up to 38 kV
39
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.63-2013
IEEE Standard for Requirements for Overhead, Pad-Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers
for Alternating Current Systems Up to 38 kV
Annex C
(informative)
Bibliography
7
CSA publications are available from the Canadian Standards Association (http://www.csa.ca/).
8
IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch/). IEC publications are also
available in the United States from the American National Standards Institute (http://www.ansi.org/).
9
The IEEE standards or products referred to in this clause are trademarks of The Institute of Electrical and Electronics Engineers, Inc.
10
This publication is available from The Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
40
Copyright 2013 IEEE. All rights reserved.
Authorized licensed use limited to: Univ Distrital Francisco Jose de Caldas. Downloaded on February 07,2017 at 02:57:54 UTC from IEEE Xplore. Restrictions apply.