EP-MS-P4/S3-050
Specification for
XLPE Insulated Pilot Cables
Document Control
Department Document Type Document Title
Material EP-MS-P4/S3-50
EP Specification Specification for
Standards XLPE Insulated Pilot Cables
Issue Approval
Prepared By Approved By
Signature: Signature:
Issue Record
Issue No. Date Reason for re-issuing Document
When this document is approved for publishing on the intranet, a copy of its Document Control page should be sent to
the QA section who is custodian of KM quality management system.
1.0 SCOPE
2.0 REFERENCES
The cables shall be inconformity with IEC 60502 Part 1, and subsequent amendments,
except as may be otherwise stated, and of the following generic types.
3.0 GENERAL
The details given in this specification are based on international standards and
KAHRAMAA requirements in general and for the guideline to the manufacturers. The
parameters given herewith are minimum requirements, however, manufacturer shall
confirm in all aspects to supply of best design, selection of high quality material and
good workmanship in the manufacturing for the safe and accurate installation and
continuous smooth operation throughout the life of the material stipulated herein.
KAHRAMAA reserve the right to reject any material if found not as per International
standards mentioned hereto and KAHRAMAA requirements.
Manufacturer may offer any better product up and above the specified one herein,
however, KAHRAMAA reserves the right to accept or not.
All cables covered under this Specification should be designed for continuous operation
life for not less than 30 years under the climatic conditions specified herein.
6.1 Conductors:
Stranded, annealed copper conductor, circular in shape in accordance
with IEC 60228.
6.5 Inner Covering and Fillers: The inner covering shall be extruded. The material
to be used shall meet the operating temperature and design temperature
conditions and of a thickness in accordance with IEC 60502 and compatible with
insulating material. The material should be fire retardant and comprises of anti
Issue : 1 03-05-2010 unclassified Page 4 of 8
Specification for XLPE Insulated Pilot Cables EP-MS-P4/S3-050
aging components. The cores shall be laid up with non-hygroscopic fillers and
bound with a closed helix of polymer tape of material appropriate to the cable
temperature. There should not be any gap between cores and maintain the
perfect round shape of overall cable.
6.6 Armour: The armour shall comprise a single layer of galvanized steel wire of
diameter appropriate to IEC 60502. The armour shall be embedded in, and
covered by a material suitable to prevent the flow of water transversely and
longitudinally. The material shall be chemically inactive with the components
with which it is in contact, both with and without the presence of water. It shall
also remain substantially solid at the working temperature of the adjoining
components.
6.7 Oversheath: PVC extruded directly over the armour and water inhibitor (water
blocking tape). The material should be fire retardant, UV resistance, anti aging
components and high resistant to soil. It shall be type ST2 in accordance with
IEC 60502 and IEC 60332-1. Thickness shall be in compliance with the above
standard. The over sheath shall be colored in BLACK, and shall be embossed
with the legend:
- KAHRAMAA
- CABLE RATING
- CABLE SIZE & NUMBER OF CORES
- STANDARD NO.
- YEAR OF MANUFACTURE
- NAME OF MANUFACTURER
- RUNNING SERIAL NUMBER (at interval of 1 meter)
7.0 TESTS:
This relates to type tests and tests to be carried out during or after manufacture of the
specified cables. In addition to the type tests conducted in accordance with the
requirements of IEC 60502-Part 1. Copy of type test reports issued from reputed
independent laboratories need to be submitted.
The following tests shall be carried out on each manufactured length of cable, or sample
length as instructed by KAHRA MAA. The tests shall be as outlined in IEC 60502- Part
1, IEC 60228 and BSI BS EN 60811.
A. Routine Tests:
Routine tests are to be carried out each and every drum manufactured.
One set of routine test reports of each drum shall be fixed with the drum
in a strong water-proof envelope. The following routine tests are to be
carried out.
B. Sample Tests:
Sample tests are to be carried out on 10 % drums of each lot. Samples to
be taken from both sides of the entire length of the drum. One set of
sample test reports of shall be submitted to KAHRAMAA for review and
approval. The following sample tests are to be carried out. One set of
sample test report (wherever applicable) shall be fixed with the drum
along with routine test report.
Issue : 1 03-05-2010 unclassified Page 5 of 8
Specification for XLPE Insulated Pilot Cables EP-MS-P4/S3-050
1. Conductor Examination.
2. Check of Dimensions as per IEC 60811-1-1
3. Hot Set Test.
C. Type Tests:
Manufacturer shall carry out type tests to IEC 60502 on the cable and
issue certificates confirming that the cable has conformed.
In general, following test to be carried out at International Reputed
Independent Laboratory in accordance with IEC 60502- Part -1 and IEC
60228.
- Manufacturer's name
- Drum number/year & month of manufacture of cable
- Size, number of cores and voltage of cable, including the
designation "Cross Linked Polyethylene (XLPE)".
9.2 For every subsequent lot, the manufacturer is obliged to inform Kahramaa, at
least 20 days before dispatch, and obtain clearance for dispatch. KM Engineers
have the option of inspecting & witnessing all factory acceptance tests, including
routine tests, at manufacturers factory premises for each lot.
9.4 Type tests are to be carried out on Samples, essentially of same design and
ratings, as being offered. Manufacturer is obliged to provide details of test
procedures being followed, to the KM inspection team before commencing
factory accepting tests.
9.5 Each Lot needs to be subjected to all routine tests & sample tests at factory
before delivery. Further, each drum may be subjected to inspection on receiving
them at DOHA to verify its healthiness and its conformity with the guaranteed
design data.
9.6 All tests should be performed in accordance with the latest issue of relevant IEC
standards.
9.7 Three sets (copies) of routine tests, sample tests & FAT reports to be prepared.
One set to be attached with the drum, in a strong water-proof envelope. Second
copy to be sent along with delivery note. Third copy to be sent to the end-user
department.
9.8 FAT report shall include copy of quality control report containing list of check
points verified/inspected at factory against each drum. Each delivery note shall
include the details of serial number and month/year of production of each
drum.
9.9 Both the manufacturing date (i.e. month/year) and shipment date should be
marked on each drum, and the time difference between these two dates should
not be more than 6-months.
10.1 An illustrated drawing showing the cable cross section design, all components,
dimensions of each layer and data sheets.
10.2 A specific compliance (clause by clause up to sub clause level), statement of
conformity with the specification, else details of non-conformity.
10.3 Details of the method of protection against water ingress at armour level.
Permissible fault ratings of the conductors and the armour.
10.4 Type Test Report from International recognized Independent Laboratory. The
report must be not older than 10 years.
10.5 Complete product catalogue with all ratings, characteristics & recommended
installation procedure.
11.0 GUARANTEE
Supplied material shall be guaranteed against any defect for 5 (five) years from the date
of delivery or 3 (three) years from the date of installation whichever comes first.
The Tenderers are required to attach a separate deviation list to their Technical Offer
and include it in the Technical Package if the offered equipments do not meet the
requirements of any clause of the Specification.
Offers without any deviation list attached to the Technical Offer and included in the
Technical Package shall mean that the offer meets the requirements of the
Specifications on all the clauses.
Offers with deviations listed out shall mean that the offer meets the requirements of the
Specification on all the other clauses not included in the deviation list.