AIR CONDITIONERS

MODEL

PUHY-RP-Y(S)JM-B
PURY-RP-YJM-B

DATA BOOK
REPLACE MULTI
1.OUTDOOR UNIT
Y SERIES ................................................................................................................. 1

R2 SERIES............................................................................................................. 61

2.CAPACITY TABLES (Indoor unit) ............................................................ 87

3.SYSTEM DESIGN
Y SERIES ............................................................................................................. 189

R2 SERIES........................................................................................................... 241

4.CONTROLLER ................................................................................................. 285


Y SERIES

OUTDOOR UNITS
I.Y SERIES

1. SPECIFICATIONS........................................................................................................................................... 2
2. EXTERNAL DIMENSIONS .............................................................................................................................. 15
3. CENTER OF GRAVITY ................................................................................................................................... 19
4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ 20
5. SOUND LEVELS ............................................................................................................................................. 21
6. CAPACITY TABLES ........................................................................................................................................ 25
6-1. Correction by temperature ....................................................................................................................... 25
6-2. Correction by total indoor......................................................................................................................... 39
6-3. Correction by refrigerant piping length..................................................................................................... 43
6-4. Correction at frost and defrost ................................................................................................................. 46
6-5. Operation temperature range .................................................................................................................. 47
7. OPTIONAL PARTS.......................................................................................................................................... 48
7-1. OUTDOOR TWINNING KIT..................................................................................................................... 48
8. UNIT SELECTION ........................................................................................................................................... 49
8-1. Indoor and outdoor unit selection ............................................................................................................ 49
8-2. Calculation samples................................................................................................................................. 51
8-3. Pipe diameter correction factor ................................................................................................................ 54

OUTDOOR UNITS 1
1. SPECIFICATIONS
I.YSPECIFICATIONS
1. SERIES

Model PUHY-RP200YJM-B(-BS) PUHY-RP250YJM-B(-BS)


Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 22.4 28.0
(Nominal) *1 kcal / h 19,300 24,100
*1 BTU / h 76,400 95,500
Power input kW 5.68 7.62
Current input A 9.5-9.1-8.7 12.8-12.2-11.7
COP kW / kW 3.94 3.67
Temp. range of Indoor W.B. 15.0~24.0C(59~75F) 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F) -5.0~43.0C(23~109F)
Heating capacity *2 kW 25.0 31.5
(Nominal) *2 kcal / h 21,500 27,100
*2 BTU / h 85,300 107,500
Power input kW 5.69 7.22
Current input A 9.6-9.1-8.7 12.1-11.5-11.1
COP kW / kW 4.39 4.36
Temp. range of Indoor D.B. 15.0~27.0C(59~81F) 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F) -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~17 P15~P250 / 1~21
Sound pressure level (measured in anechoic room) dB <A> 56 57
Refrigerant Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
piping diameter Gas pipe mm (in.) 28.58(1-1/8) Brazed 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit LEV and HIC circuit
Net weight kg (lbs) 230(508) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G725 KD94G725
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts
Header: CMY-Y104/108/1010-G Header: CMY-Y104/108/1010-G

Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

*The specification data is


subject to rounding variation.

OUTDOOR UNITS 2
1. SPECIFICATIONS
Model PUHY-RP300YJM-B(-BS) PUHY-RP350YJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 33.5 40.0
(Nominal) *1 kcal / h 28,800 34,400
*1 BTU / h 114,300 136,500
Power input kW 8.98 11.79
Current input A 15.1-14.4-13.8 19.9-18.9-18.2
COP kW / kW 3.73 3.39
Temp. range of Indoor W.B. 15.0~24.0C(59~75F) 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F) -5.0~43.0C(23~109F)
Heating capacity *2 kW 37.5 45.0
(Nominal) *2 kcal / h 32,300 38,700
*2 BTU / h 128,000 153,500
Power input kW 9.42 12.60
Current input A 15.9-15.1-14.5 21.2-20.2-19.4
COP kW / kW 3.98 3.57
Temp. range of Indoor D.B. 15.0~27.0C(59~81F) 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F) -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~26 P15~P250 / 1~30
Sound pressure level (measured in anechoic room) dB <A> 59 60
Refrigerant Liquid pipe mm (in.) 12.7(1/2) Brazed 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58(1-1/8) Brazed 34.93(1-3/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 9.9
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G725 KD94G725
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts
Header: CMY-Y104/108/1010-G Header: CMY-Y104/108/1010-G

Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).

*The specification data is


subject to rounding variation.

OUTDOOR UNITS 3
1. SPECIFICATIONS

Model PUHY-RP400YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 45.0
(Nominal) *1 kcal / h 38,700
*1 BTU / h 153,500
Power input kW 11.87
Current input A 20.0-19.0-18.3
COP kW / kW 3.79
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 50.0
(Nominal) *2 kcal / h 43,000
*2 BTU / h 170,600
Power input kW 11.38
Current input A 19.2-18.2-17.5
COP kW / kW 4.39
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 59
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP200YJM-B(-BS) PUHY-RP200YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 4.8
Case heater kW 0.035(240 V) 0.035(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 6.5kg (15lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 230(508) 230(508)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G726
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 4
1. SPECIFICATIONS
Model PUHY-RP450YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 50.0
(Nominal) *1 kcal / h 43,000
*1 BTU / h 170,600
Power input kW 13.77
Current input A 23.2-22.0-21.2
COP kW / kW 3.63
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 56.0
(Nominal) *2 kcal / h 48,200
*2 BTU / h 191,100
Power input kW 12.81
Current input A 21.6-20.5-19.8
COP kW / kW 4.37
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 59.5
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP200YJM-B(-BS) PUHY-RP250YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 230(508) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G726
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 5
1. SPECIFICATIONS
Model PUHY-RP500YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 56.0
(Nominal) *1 kcal / h 48,200
*1 BTU / h 191,100
Power input kW 15.68
Current input A 26.4-25.1-24.2
COP kW / kW 3.57
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 63.0
(Nominal) *2 kcal / h 54,200
*2 BTU / h 215,000
Power input kW 14.44
Current input A 24.3-23.1-22.3
COP kW / kW 4.36
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 60
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 6.8 6.8
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G726
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 6
1. SPECIFICATIONS
Model PUHY-RP550YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 63.0
(Nominal) *1 kcal / h 54,200
*1 BTU / h 215,000
Power input kW 17.50
Current input A 29.5-28.0-27.0
COP kW / kW 3.60
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 69.0
(Nominal) *2 kcal / h 59,300
*2 BTU / h 235,400
Power input kW 16.62
Current input A 28.0-26.6-25.6
COP kW / kW 4.15
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 61
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 6.8 8.2
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G726
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 7
1. SPECIFICATIONS
Model PUHY-RP600YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 69.0
(Nominal) *1 kcal / h 59,300
*1 BTU / h 235,400
Power input kW 18.59
Current input A 31.3-29.8-28.7
COP kW / kW 3.71
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 76.5
(Nominal) *2 kcal / h 65,800
*2 BTU / h 261,000
Power input kW 19.22
Current input A 32.4-30.8-29.7
COP kW / kW 3.98
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G726
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 8
1. SPECIFICATIONS
Model PUHY-RP650YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 73.0
(Nominal) *1 kcal / h 62,800
*1 BTU / h 249,100
Power input kW 21.09
Current input A 35.6-33.8-32.6
COP kW / kW 3.46
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 81.5
(Nominal) *2 kcal / h 70,100
*2 BTU / h 278,100
Power input kW 21.73
Current input A 36.6-34.8-33.5
COP kW / kW 3.75
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP300YJM-B(-BS) PUHY-RP350YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
L/s 3,083 3,083
cfm 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 9.9
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa High pressure sensor, High pressure switch at 4.15,3.3MPa
Protection devices High pressure protection
(601,479 psi) (601,479 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 28.58(1-1/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G726
Wiring KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 9
1. SPECIFICATIONS

Model PUHY-RP700YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 80.0
(Nominal) *1 kcal / h 68,800
*1 BTU / h 273,000
Power input kW 22.22
Current input A 37.5-35.6-34.3
COP kW / kW 3.60
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 88.0
(Nominal) *2 kcal / h 75,700
*2 BTU / h 300,300
Power input kW 20.13
Current input A 33.9-32.2-31.1
COP kW / kW 4.37
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 61.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP200YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC
Manufacture
CORPORATION CORPORATION CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 4.8 6.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/
in.
16 16 16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP. / FAN)
tection tection tection
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 230(508) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G727
Wiring KE94C490 KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) cfm =m3/min x 35.31
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) *The specification data is
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O). subject to rounding variation.

OUTDOOR UNITS 10
1. SPECIFICATIONS
Model PUHY-RP750YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 85.0
(Nominal) *1 kcal / h 73,100
*1 BTU / h 290,000
Power input kW 24.14
Current input A 40.7-38.7-37.3
COP kW / kW 3.52
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 95.0
(Nominal) *2 kcal / h 81,700
*2 BTU / h 324,100
Power input kW 21.78
Current input A 36.7-34.9-33.6
COP kW / kW 4.36
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC
Manufacture
CORPORATION CORPORATION CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 6.8 6.8 6.8
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/
in.
16 16 16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP. / FAN)
tection tection tection
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G727
Wiring KE94C490 KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) cfm =m3/min x 35.31
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) *The specification data is
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O). subject to rounding variation.

OUTDOOR UNITS 11
1. SPECIFICATIONS
Model PUHY-RP800YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 90.0
(Nominal) *1 kcal / h 77,400
*1 BTU / h 307,100
Power input kW 25.49
Current input A 43.0-40.8-39.4
COP kW / kW 3.53
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 100.0
(Nominal) *2 kcal / h 86,000
*2 BTU / h 341,200
Power input kW 23.75
Current input A 40.0-38.0-36.7
COP kW / kW 4.21
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC
Manufacture
CORPORATION CORPORATION CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 6.8 6.8 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/
in.
16 16 16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP. / FAN)
tection tection tection
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G727
Wiring KE94C490 KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) cfm =m3/min x 35.31
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) *The specification data is
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O). subject to rounding variation.

OUTDOOR UNITS 12
1. SPECIFICATIONS
Model PUHY-RP850YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 96.0
(Nominal) *1 kcal / h 82,600
*1 BTU / h 327,600
Power input kW 27.11
Current input A 45.7-43.4-41.9
COP kW / kW 3.54
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 108.0
(Nominal) *2 kcal / h 92,900
*2 BTU / h 368,500
Power input kW 26.47
Current input A 44.6-42.4-40.9
COP kW / kW 4.08
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 63.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC
Manufacture
CORPORATION CORPORATION CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 6.8 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/
in.
16 16 16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP. / FAN)
tection tection tection
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G727
Wiring KE94C490 KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) cfm =m3/min x 35.31
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) *The specification data is
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O). subject to rounding variation.

OUTDOOR UNITS 13
1. SPECIFICATIONS
Model PUHY-RP900YSJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 101.0
(Nominal) *1 kcal / h 86,900
*1 BTU / h 344,600
Power input kW 28.29
Current input A 47.7-45.3-43.7
COP kW / kW 3.57
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 113.0
(Nominal) *2 kcal / h 97,200
*2 BTU / h 385,600
Power input kW 28.39
Current input A 47.9-45.5-43.8
COP kW / kW 3.98
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC
Manufacture
CORPORATION CORPORATION CORPORATION
Starting method Inverter Inverter Inverter
Motor output kW 8.2 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/ 67-3/8(65 without legs) x 36-1/4 x 29-15/
in.
16 16 16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi) switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP. / FAN)
tection tection tection
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G727
Wiring KE94C490 KE94C490 KE94C490
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Header: CMY-Y104/108/1010-G
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes : Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) cfm =m3/min x 35.31
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) *The specification data is
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O). subject to rounding variation.

OUTDOOR UNITS 14
2. EXTERNAL DIMENSIONS

760
<Accessories>
Connecting pipe
<Gas> Elbow (ID25.4 OD25.4) RP200, RP250, RP300, RP350 1 pc.
Pipe (ID25.4 OD19.05) RP200 1 pc.
Pipe (ID25.4 OD22.2) RP250, RP300 1 pc.
920 Pipe (ID25.4 OD28.58) RP200, RP250, RP300, RP350 1 pc.
Discharge air Top view Pipe (ID25.4 OD34.93) RP350 1 pc.
<Liquid> Pipe (ID9.52 OD9.52) RP200, RP250, RP300 1 pc.
Pipe (ID9.52 OD12.7) RP200, RP250, RP300 1 pc.
Pipe (ID12.7 OD12.7) RP350 1 pc.

240
Pipe (ID12.7 OD15.88) RP350 1 pc.
Control box

Note1. Please refer to the next page for information


2. EXTERNAL DIMENSIONS

Intake Intake
air
regarding necessary spacing around the
Intake air
unit and foundation work.
air 2. The detachable leg can be removed at site.
Refrigerant service
valve <liquid> 3. At brazing of pipes, wrap the refrigerant service valve
Service

1650
PUHY-RP200, 250, 300, 350YJM-B(-BS)

with wet cloth and keep the temperature of

1710
panel
refrigerant service valve under 120C.

1410
Refrigerant service
valve <gas> 6
4 1
NO. Usage Specifications

72
Front through hole 102 72 Knockout hole
For pipes

54
B
Bottom through hole 150 92 Knockout hole

OUTDOOR UNITS
132 88
Front through hole 65 or 40 Knockout hole
For wires Front through hole 52 or 27 Knockout hole

90
60 60 204 98
3 Bottom through hole 52 Knockout hole
(60)

(60)
55 25 25 55 251 102 For transmission cables Front through hole 34 Knockout hole
760 Detachable leg
Front view
(front and back, 2 points)
Left side view Note 2*
221 150
Connecting pipe specifications 251 83 22-1420 Oval hole
Position dimensions 186
Connection specifications for
86
18

for the refrigerant 145


the refrigerant service valve *1
service valve
Model

C
131
Liquid Gas
Liquid Gas
A C B
92

28.58 Brazed
PUHY-RP200YJM-B(-BS) 12.7 Brazed 5
(19.05 Brazed) *2
142 145 (9.52 Brazed) *2 2 Refrigerant service
(760)

PUHY-RP250YJM-B(-BS) 28.58 Brazed Refrigerant service valve <gas>


172 valve <liquid>
724 (721~727)

PUHY-RP300YJM-B(-BS) 12.7 Brazed (22.2 Brazed) *2


(Mounting pitch)

15.88 Brazed 34.93 Brazed


PUHY-RP350YJM-B(-BS) 143 150
(12.7 Brazed) *2 (28.58 Brazed) *2
18

*1 Connect by using the connecting pipes (for bottom piping and front piping) 80 760 80
that are supplied. (Mounting pitch)
*2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units. Bottom view
Unit : mm

15
1. Required space around the unit In case of collective installation
When multiple units are installed adjacent to each other, secure enough space to allow
In case of single installation for air circulation and walkway between groups of units as shown in the figures below.
Secure enough space around the unit as shown in the figure below. At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
With a space of at least With a space of at least to the figures that are marked with an asterisk.
300 mm to the wall on 100 mm to the wall on If there is a wall at both the front and the rear of the unit, install up to six units
the back of the unit the back of the unit consecutively in the side direction and provide a space of 1000 mm or more as inlet space/
passage space for each six units.

100 min.*
Wall <H> Wall <H>

300 min.*
<To be left open>

100 min.*

300 min.*
Front
Front
Front

Front
Front
Wall <H>

Wall <H>

450 min.*
Front Front

450 min.*
<To be left open>
<To be left open>

<To be left open>


<To be left open>
15 min.* 15 min.* 50 min.* 50 min.* Wall <H> 30 min. Wall <H> 100 min.
2. EXTERNAL DIMENSIONS

450 min.* 450 min. 450 min. 100 min.*

450 min.*

450 min.*
<Top view> <Top view>
<Unit: mm> <To be left open>

When the height of the walls on the front, back or on the sides <H>
PUHY-RP200, 250, 300, 350YJM-B(-BS)

exceeds the wall height limit as defined below, add the height
Wall <H> Wall <H>
300 min.*
that exceeds the height limit <h> to the figures that are marked
300 min.*

with an asterisk.
Wall <H>

15 min.*

h
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from
the unit bottom

H
Front
Front
Front
Side: Up to the unit height Front

h
Front
900 min.
900 min.

Front

Unit height

OUTDOOR UNITS
500
<To be left open>
<To be left open>
<To be left open>

450 min. 450 min.

<Side view>
Wall <H> <To be left open>
1000 min.*
300 min.*

Corner of the
2. Foundation work installation leg 30 mm max. <Unit: mm>

Take into consideration the surface strength, water drainage route,


piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
M10 anchor bolt
Build the foundation in such way that the corner of the installation leg is <field supply required>
securely supported as shown in the right figure. (Fig.A, B)
Detachable leg
When using a rubber isolating cushion, please ensure it is large enough Fig.A (without detachable legs)
to cover the entire width of each of the unit's legs. Fixing plate
<field supply required> Fixing plate
The protrusion length of the anchor bolt must not exceed 30 mm. (Fig.A, B) <field supply required>
Use four fixing plates as shown in the right figure <field supply required>
Corner of the Fig.C (without detachable legs) Fig.D (with detachable legs)
when using post-installed anchor bolts. (Fig.C, D)
installation leg
30 mm max.

To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
Detachable leg
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked M10 anchor bolt
with the installation base. <field supply required>
Refer to the Installation Manual when installing units on an installation base.
Fig.B (with detachable legs)
Unit : mm

16
760 920 30 920
Discharge air
Outdoor unit 1 Outdoor unit 2
2. EXTERNAL DIMENSIONS

1650
1710
Intake
Intake Intake
air
air air
PUHY-RP400, 450, 500, 550, 600, 650YSJM-B(-BS)

OUTDOOR UNITS
e
Left side view c a
To indoor unit
Liquid Twinning pipe <optional parts>

(60)
Detachable leg f
d b
Note 2* To indoor unit
Twinning pipe connection size Gas Twinning pipe <optional parts>
Front view
Package unit name PUHY-RP400YSJM-B(-BS) PUHY-RP450YSJM-B(-BS) PUHY-RP500YSJM-B(-BS) PUHY-RP550YSJM-B(-BS) PUHY-RP600YSJM-B(-BS) PUHY-RP650YSJM-B(-BS)
Outdoor unit 1 PUHY-RP200YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP350YJM-B(-BS) Liquid Gas
Component unit name Unit model
Outdoor unit 2 PUHY-RP200YJM-B(-BS) PUHY-RP200YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS) c or e d or f
Outdoor Twinning Kit (optional parts) CMY-RP100VBK RP200 9.52 19.05
Liquid a 15.88 19.05 RP250 9.52 22.2
Indoor unit~Twinning pipe Twinning pipe~Outdoor unit
Gas b 34.93 41.28 RP300 12.7 22.2
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. RP350 12.7 28.58
2. The detachable leg can be removed at site.
3. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500 mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm

17
760 920 30 920 30 920

Discharge air
Outdoor unit 1 Outdoor unit 2 Outdoor unit 3

1650
1710
Intake Intake
2. EXTERNAL DIMENSIONS

Intake air air


air
PUHY-RP700, 750, 800, 850, 900YSJM-B(-BS)

OUTDOOR UNITS
g a
e c To indoor unit
Left side view
Liquid Twinning pipe 2

(60)
Liquid Twinning pipe 1
Detachable leg <optional parts> <optional parts>
j
Note 2* h d b To indoor unit
f
Gas Twinning pipe 1 Gas Twinning pipe 2
<optional parts> <optional parts>
Twinning pipe connection size
Package unit name PUHY-RP700YSJM-B(-BS) PUHY-RP750YSJM-B(-BS) PUHY-RP800YSJM-B(-BS) PUHY-RP850YSJM-B(-BS) PUHY-RP900YSJM-B(-BS)
Front view
Outdoor unit 1 PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS)
Component unit name Outdoor unit 2 PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS) PUHY-RP300YJM-B(-BS)
Outdoor unit 3 PUHY-RP200YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP250YJM-B(-BS) PUHY-RP300YJM-B(-BS)
Outdoor Twinning Kit (optional parts) CMY-RP200VBK Liquid Gas
Unit model
Liquid a 19.05 e or g or i f or h or j
Indoor unit~Twinning pipe 2
Gas b 41.28 RP200 9.52 19.05
Liquid c 19.05 Twinning pipe~Outdoor unit RP250 9.52 22.2
Twinning pipe 1~Twinning pipe 2
Gas d 34.93 RP300 12.7 22.2
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. The detachable leg can be removed at site.
3. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (sections "a" , "b" , "c" and "d" in the figure) must have at least 500 mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm

18
3. CENTER OF GRAVITY
3. CENTER OF GRAVITY

PUHY-RP200, RP250, RP300, RP350YJM-B(-BS)

920 760

Unit: mm
Model X Y Z
PUHY-RP200YJM-B(-BS) 330 337 550
1410
PUHY-RP250YJM-B(-BS) 325 342 550
PUHY-RP300YJM-B(-BS) 325 352 550
PUHY-RP350YJM-B(-BS) 325 352 550
Z

X Y

760 80 724

OUTDOOR UNITS 19
P 63H1 P 63H2

1 2 1 3
4. ELECTRICAL WIRING DIAGRAMS

21 1 3 12
FAN Board CN18V CN4 CN5 CNDC
blue red 4 1 3 pink 12 1 3 12 21 12 6
F01 CN21 3 5
DC700V blue 2 CNT01 CN801 CNT02 CN332 CN4 M
1 yellow blue CNLVA 4
3
4A T CPU power 2 LEV1
LED3: CPU in
4 operation 6 supply circuit 7 1
C631 5
C630 R630 IPM 5
1 CN22 4 5 CN2 6
Fan motor red 3 2 5
(Heat exchanger) CNVDC 2 72C 2 CN72 ZNR01 1 CNLVB 4 M
R631 1 6 1 red red 3
U U 2 LEV2a
7 2
M V 1 Power failure 1
3~ 4 CNAC2 detection circuit 6
1 LED1: Normal black
3 5
W operation CNLVC 4
CNINV M
LED2: Error 21S4b CN501 X01 red 3
1 2 LEV2b
1
C100 2 Control Board LED1
X02 6
SV1a 1 CN502 5
R1 R5 *5 CNLVD 4
DCL
M
black 3 blue 3 SLEV
CN503 2
red 1 2 X03 SWU2 SWU1 OFF ON OFF ON OFF ON OFF ON OFF ON 1
CH11 1 blue 1 1 1 1 1
3 72C 4 10's 1's
3 digit digit
red black CN504
21 3 1 21S4a X04
1 green 3
SC-P1 CN6 CN5V CN4 2
6 SC-P2 1 Unit address 10 10 10 10 10 1
CN5 yellow 6 CNTYP2
5 CN4 red 1 3 SW5 SW4 SW3 SW2 SW1
5 setting black
1 3 blue D1 LED1: Normal operation (lit)
CN2 3 R5 R4 *6 SV5b
/ Error(blink) 3 CN506 LED1
CN1 P FT-P Function
1 + 7 SV1b X05 Display
R6 4 1 setting Z25
C11 C1 5 setting CNTYP5 3
DSA N FT-N CN2 X06
1 6 green 1
Z5 2 12V CN51
Z4 RSH1 1 1 Z24
F1,F2,F3 + U - C30 C31 SV3 CN507 CNTYP4 2
AC250V U Noise + + 3 red *3 green 1
6.3A T DB1 C32 C33 3 3
F3 + + IPM X07 4 Compressor ON/OFF output 4
Filter C34 C35 1 1 5 CN213 3
TH6
F2 + + Error detection output
C36 C37 THHS CNTYP red 2 TH7
F1 C10 + + 6 1
Z1 Z2 Z3 F4 black
R30 R31 SC-V
PUHY-RP200, 250, 300, 350YJM-B(-BS)

U U U C3 C4 C5 C6 AC250V CN508 2
6.3A T SV9 TH3
C9 R32 R33 3 black
CN212 1
C2 C8 R34 R35 LED3: Lit when powered 2
SC-L1 SC-U SC-W X09 CN990 1 TH5
C7 red red 1
C1 SC-L2 3 1
4. ELECTRICAL WIRING DIAGRAMS

white white CN992 2 2 63HS2


yellow 1 3
R3 black black
3 1
R2 6
CN202 2 2 63LS
SC-L3 red 1 3
1 CT3 5
R1 LED2: CPU in operation 3 1
CN510 TB7 Power CN201 2 2 63HS1
3 CT12 CT22 SV8 yellow 1 3
L1 L2 L3 N CN3 selecting
green 1
CN1A 3 1 4 1 CN1B X14
connector
TB21 TB22 TB23 TB24
INV Board red white black
CN40
F01 1
AC250V 1 4 ON CN211 2 TH4
L 3.15A T blue red yellow red

OUTDOOR UNITS
CN3N CN3S CN3D CN102 CN41 CNS2 CNIT
CNAC 2 1 321 321 321 1234 1 4 12 12345
red OFF

*3
TB1
L1 L2 L3 N

red white black CN04


Power Source 1 3 red 4321 21 54321
V CN102 CNS2 CNIT
3N~ U W *1. Single-dotted lines indicate wiring yellow red
MS
50/60Hz 3~ not supplied with the unit. LED1: Power supply to
M-NET power
supply circuit Indoor/Outdoor transmission line
380/400/415V L1 L2 L3 N Motor *2. Dot-dash lines indicate the control TB3 TB7
(Compressor) M1 M2 M1 M2 S
box boundaries.
<Symbol explanation> TP1 TP2
*3. Refer to the Data book for connecting
Symbol Explanation Symbol Explanation M-NET Board
21S4a, b 4-way valve SV3 Solenoid Capacity control, Refrigerant
input/output signal connectors.
63H1 Pressure High pressure protection for the valve phase control in auto-cleaning *4. Daisy-chain terminals (TB3) on the
switch outdoor unit SV5b Outdoor unit heat exchanger outdoor units in the same refrigerant
63H2 Pressure protection for pre- capacity control
existing pipes SV8 Refrigerant charging port for
system together.
auto-charge
*4
63HS1 Pressure Discharge pressure *5. Faston terminals have a locking Indoor/Outdoor Central control
63HS2 sensor Middle pressure SV9 For opening/closing the bypass function. Make sure the terminals transmission transmission
63LS Low pressure circuit cable cable
72C Magnetic relay (inverter main circuit) TB1 Terminal Power supply are securely locked in place after
CT12, 22, 3 Current sensor (AC) TB3 block Indoor/Outdoor transmission insertion. Press the tab on the
CH11 Crankcase heater (for heating the compressor) cable terminals to remove them.
DCL DC reactor TB7 Central control transmission
SLEV Oil flow control cable *6. Control box houses high-voltage parts.
LEV1 Linear HIC bypass, Controls refrigerant TH3 Thermistor Pipe temperature Before inspecting the inside of the
expansion flow in HIC circuit TH4 Discharge pipe temperature
valve ACC inlet pipe temperature
control box, turn off the power, keep
LEV2a, b Pressure control, Refrigerant flow TH5
rate control TH6 Subcooled liquid refrigerant the unit off for at least 10 minutes,
SV1a Solenoid For opening/closing the bypass temperature and confirm that the voltage between
valve circuit under the O/S TH7 OA temperature
SV1b IPM temperature
FT-P and FT-N on INV Board has dropped
For opening/closing the bypass THHS
circuit Z24, 25 Function setting connector to DC20V or less.

20
5. SOUND LEVELS
5. SOUND LEVELS

Sound level of PUHY-RP300YJM-B(-BS)


Measurement condition 90
PUHY-RP200, 250, 300, 350YJM-B(-BS) Stand 50/60Hz

80 Low 50/60Hz

70

Octave band sound level (dB)


NC-70

60
NC-60
1m 50
NC-50

40
NC-40

30
Measurement NC-30
location
1m 20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 65.5 64.0 61.5 56.0 53.0 48.5 45.0 43.0 59.0
Low noise mode 50/60Hz 61.5 60.0 49.5 45.0 42.0 39.0 40.0 38.0 50.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-RP200YJM-B(-BS) Sound level of PUHY-RP350YJM-B(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz

70 70
Octave band sound level (dB)

Octave band sound level (dB)

NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 62.5 61.0 58.5 53.0 50.0 45.5 39.0 36.0 56.0 Standard 50/60Hz 62.0 65.0 63.0 57.0 53.5 49.0 48.0 42.0 60.0
Low noise mode 50/60Hz 56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0 Low noise mode 50/60Hz 62.0 54.0 48.5 46.0 41.5 40.0 41.5 39.5 50.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-RP250YJM-B(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz

70
Octave band sound level (dB)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 59.0 62.0 60.0 54.0 50.5 46.0 41.0 35.0 57.0
Low noise mode 50/60Hz 58.0 53.5 44.0 39.0 36.5 32.5 31.0 24.5 44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

OUTDOOR UNITS 21
5. SOUND LEVELS

Measurement condition Sound level of PUHY-RP500YSJM-B(-BS)


90
PUHY-RP400, 450, 500, 550, 600, 650YSJM-B(-BS) Stand 50/60Hz

80 Low 50/60Hz

70

Octave band sound level (dB)


NC-70

60
1m NC-60

50
NC-50

40
NC-40
Measurement
30
location NC-30
1m

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 62.0 65.0 63.0 57.0 53.5 49.0 44.0 38.0 60.0
Low noise mode 50/60Hz 61.0 56.5 47.0 42.0 39.5 35.5 34.0 27.5 47.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-RP400YSJM-B(-BS) Sound level of PUHY-RP550YSJM-B(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz

70 70
Octave band sound level (dB)

Octave band sound level (dB)

NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 65.5 64.0 61.5 56.0 53.0 48.5 42.0 39.0 59.0 Standard 50/60Hz 66.0 66.0 63.5 58.0 55.0 50.5 46.5 43.5 61.0
Low noise mode 50/60Hz 59.5 51.5 49.0 42.0 41.5 35.5 36.0 28.5 47.0 Low noise mode 50/60Hz 63.5 61.0 50.5 46.0 43.0 40.0 40.5 38.0 51.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-RP450YSJM-B(-BS) Sound level of PUHY-RP600YSJM-B(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz

70 70
Octave band sound level (dB)

Octave band sound level (dB)

NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 64.0 64.5 62.5 56.5 53.0 48.5 43.0 38.5 59.5 Standard 50/60Hz 68.5 67.0 64.5 59.0 56.0 51.5 48.0 46.0 62.0
Low noise mode 50/60Hz 60.5 54.5 48.0 42.0 40.5 35.5 35.0 28.0 47.0 Low noise mode 50/60Hz 64.5 63.0 52.5 48.0 45.0 42.0 43.0 41.0 53.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

OUTDOOR UNITS 22
5. SOUND LEVELS
Sound level of PUHY-RP650YSJM-B(-BS)
90
Stand 50/60Hz

80 Low 50/60Hz

70
Octave band sound level (dB)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 67.0 67.5 65.0 59.5 56.0 51.5 49.5 45.5 62.5
Low noise mode 50/60Hz 65.0 61.0 52.0 48.5 45.0 42.5 44.0 42.0 53.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

OUTDOOR UNITS 23
5. SOUND LEVELS

Sound level of PUHY-RP800YSJM-B(-BS)


Measurement condition
90
PUHY-RP700, 750, 800, 850, 900YSJM-B(-BS) Stand 50/60Hz

80 Low 50/60Hz

70

Octave band sound level (dB)


NC-70

60
NC-60
1m
50
NC-50

40
NC-40
Measurement
location 30

1m
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 67.0 67.5 65.5 59.5 56.0 51.5 47.5 44.0 62.5
Low noise mode 50/60Hz 65.0 62.0 52.0 47.0 44.0 41.0 41.0 38.5 52.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-RP700YSJM-B(-BS) Sound level of PUHY-RP850YSJM-B(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz

70 70
Octave band sound level (dB)

Octave band sound level (dB)

NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 65.5 66.5 64.5 58.5 55.0 50.5 45.5 40.0 61.5 Standard 50/60Hz 69.0 68.5 66.0 60.5 57.5 53.0 49.0 46.5 63.5
Low noise mode 50/60Hz 63.0 57.5 50.0 44.0 42.5 37.5 37.0 30.0 49.0 Low noise mode 50/60Hz 65.5 63.5 53.0 48.5 45.5 42.5 43.0 41.0 53.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-RP750YSJM-B(-BS) Sound level of PUHY-RP900YSJM-B(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz

70 70
Octave band sound level (dB)

Octave band sound level (dB)

NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 64.0 67.0 65.0 59.0 55.5 51.0 46.0 40.0 62.0 Standard 50/60Hz 70.5 69.0 66.5 61.0 58.0 53.5 50.0 48.0 64.0
Low noise mode 50/60Hz 63.5 59.0 49.5 44.5 41.5 37.5 36.0 29.5 49.0 Low noise mode 50/60Hz 66.5 65.0 54.5 50.0 47.0 44.0 45.0 43.0 55.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

OUTDOOR UNITS 24
6. CAPACITY TABLES
6-1. Correction by temperature
6. CAPACITY TABLES

CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values
and the ratios below, the capacity can be found for various temperatures.

PUHY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 22.4 28.0
Cooling 1.3
Capacity BTU/h 76,400 95,500
Input kW 5.68 7.62

Ratio of cooling capacity


1.2 24CWB
75FWB
1.1 22CWB
72FWB

1.0 20CWB
68FWB
18CWB
0.9 64FWB
16CWB
0.8 61FWB
15CWB
59FWB
0.7

0.6

24CWB
75FWB
22CWB
1.2 72FWB
20CWB
1.1 68FWB
18CWB
Ratio of power input

64FWB
1.0
16CWB
61FWB
0.9 15CWB
59FWB
0.8

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 25.0 31.5
Heating 1.3 15CDB
Capacity BTU/h 85,300 107,500 59FDB
Input kW 5.69 7.22 1.2
Ratio of heating capacity

1.1
20CDB
1.0 68FDB

0.9
25CDB
0.8 77FDB

0.7 27CDB
80FDB

0.6

0.5

0.4

1.4

1.3

1.2
Ratio of power input

1.1
15CDB
59FDB
1.0

0.9

0.8 20CDB
68FDB

0.7
25CDB
77FDB
0.6
27CDB
0.5 80FDB

0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 25
6. CAPACITY TABLES

PUHY- RP300YJM-B RP350YJM-B 1.4 Indoor Temperature


Nominal kW 33.5 40.0
Cooling 1.3
Capacity BTU/h 114,300 136,500
Input kW 8.98 11.79

Ratio of cooling capacity


1.2
24CWB
PUHY- RP400YSJM-B 1.1 75FWB
22CWB
Nominal kW 45.0 72FWB
Cooling 1.0
Capacity BTU/h 153,500 20CWB
68FWB
Input kW 11.87 0.9 18CWB
64FWB

0.8 16CWB
61FWB
15CWB
0.7 59FWB

0.6

24CWB
75FWB
1.2 22CWB
72FWB

1.1 20CWB
68FWB
Ratio of power input

18CWB
1.0 64FWB
16CWB
0.9 61FWB
15CWB
59FWB
0.8

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP300YJM-B RP350YJM-B 1.4 Indoor Temperature


Nominal kW 37.5 45.0
Heating 1.3
Capacity BTU/h 128,000 153,500
Input kW 9.42 12.60 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PUHY- RP400YSJM-B
20CDB
Nominal kW 50 1.0 68FDB
Heating
Capacity BTU/h 170,600 0.9
Input kW 11.38
0.8
25CDB
77FDB
0.7
27CDB
80FDB
0.6

0.5

0.4

1.4

1.3

1.2
Ratio of power input

1.1

1.0
15CDB
0.9 59FDB

0.8

0.7 20CDB
68FDB

0.6
25CDB
77FDB
0.5
27CDB
80FDB
0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 26
6. CAPACITY TABLES

PUHY- RP450YSJM-B RP500YSJM-B 1.4 Indoor Temperature


Nominal kW 50.0 56.0
Cooling 1.3
Capacity BTU/h 170,600 191,100
Input kW 13.77 15.68

Ratio of cooling capacity


1.2 24CWB
75FWB
22CWB
PUHY- RP550YSJM-B P600YSJM-B 1.1 72FWB
Nominal kW 63.0 69.0 20CWB
Cooling 1.0 68FWB
Capacity BTU/h 215,000 235,400 18CWB
Input 64FWB
kW 17.50 18.59 0.9
16CWB
61FWB
PUHY- RP650YSJM-B 0.8 15CWB
Nominal kW 73.0 59FWB
Cooling 0.7
Capacity BTU/h 249,100
Input kW 21.09 0.6

24CWB
1.2 75FWB
22CWB
1.1 72FWB
20CWB
Ratio of power input

68FWB
1.0
18CWB
64FWB
0.9 16CWB
61FWB
0.8 15CWB
59FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP450YSJM-B RP500YSJM-B 1.4 Indoor Temperature


Nominal kW 56.0 63.0
Heating 1.3
Capacity BTU/h 191,100 215,000
Input kW 12.81 14.44 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PUHY- RP550YSJM-B RP600YSJM-B
1.0 20CDB
Nominal kW 69.0 76.5 68FDB
Heating
Capacity BTU/h 235,400 261,000 0.9
Input kW 16.62 19.22
0.8 25CDB
77FDB

PUHY- RP650YSJM-B 0.7 27CDB


80FDB
Nominal kW 81.5
Heating 0.6
Capacity BTU/h 278,100
Input 0.5
kW 21.73
0.4

1.4

1.3

1.2
Ratio of power input

1.1
15CDB
1.0 59FDB

0.9

0.8 20CDB
68FDB

0.7
25CDB
77FDB
0.6
27CDB
0.5 80FDB

0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 27
6. CAPACITY TABLES

PUHY- RP700YSJM-B PR750YSJM-B 1.4 Indoor Temperature


Nominal kW 80.0 85.0
Cooling 1.3
Capacity BTU/h 273,000 290,000
Input kW 22.22 24.14

Ratio of cooling capacity


1.2
24CWB
PUHY- RP800YSJM-B 1.1 75FWB
22CWB
Nominal kW 90.0 72FWB
Cooling 1.0
Capacity BTU/h 307,100 20CWB
68FWB
Input kW 25.49 0.9 18CWB
64FWB

0.8 16CWB
61FWB
15CWB
0.7 59FWB

0.6

24CWB
1.2 75FWB
22CWB
1.1 72FWB
20CWB
Ratio of power input

68FWB
1.0
18CWB
64FWB
0.9 16CWB
61FWB
0.8 15CWB
59FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP700YSJM-B PR750YSJM-B 1.4 Indoor Temperature


Nominal kW 88.0 95.0
Heating 1.3 15CDB
Capacity BTU/h 300,300 324,100 59FDB
Input kW 20.13 21.78 1.2
Ratio of heating capacity

1.1
PUHY- RP800YSJM-B 20CDB
Nominal kW 100.0 1.0 68FDB
Heating
Capacity BTU/h 341,200 0.9
Input kW 23.75 25CDB
0.8 77FDB

0.7 27CDB
80FDB

0.6

0.5

0.4

1.4

1.3

1.2
Ratio of power input

1.1
15CDB
59FDB
1.0

0.9

0.8 20CDB
68FDB

0.7
25CDB
77FDB
0.6
27CDB
0.5 80FDB

0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 28
6. CAPACITY TABLES

PUHY- RP850YSJM-B RP900YSJM-B 1.4 Indoor Temperature


Nominal kW 96.0 101.0
Cooling 1.3
Capacity BTU/h 327,600 344,600
24CWB
Input kW 27.11 28.29

Ratio of cooling capacity


1.2 75FWB
22CWB
1.1 72FWB
20CWB
68FWB
1.0
18CWB
64FWB
0.9 16CWB
61FWB
0.8 15CWB
59FWB

0.7

0.6

24CWB
75FWB
22CWB
1.1 72FWB
20CWB
1.0 68FWB
18CWB
Ratio of power input

64FWB
0.9
16CWB
61FWB
0.8 15CWB
59FWB
0.7

0.6

0.5

0.4

0.3
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP850YSJM-B RP900YSJM-B 1.4 Indoor Temperature


Nominal kW 108.0 113.0
Heating 1.3
Capacity BTU/h 368,500 385,600
Input kW 26.47 28.39 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
20CDB
1.0 68FDB

0.9

0.8
25CDB
77FDB
0.7
27CDB
80FDB
0.6

0.5

0.4

1.4

1.3

1.2
Ratio of power input

1.1

1.0
15CDB
0.9 59FDB

0.8

0.7 20CDB
68FDB

0.6
25CDB
0.5 77FDB
27CDB
80FDB
0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 29
6. CAPACITY TABLES
Correction by temperature (COP Priority Mode)
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity val-
ues and the ratios below, the capacity can be found for various temperatures.
To select high heating performance mode, DipSW 3-7 must be set to OFF.

PUHY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 22.4 28.0
Cooling 1.3
Capacity BTU/h 76,400 95,500
Input kW 5.68 7.62

Ratio of cooling capacity


1.2 24CWB
75FWB
(There is no difference in cooling performance
1.1 22CWB
between Standard Mode and COP Priority Mode.) 72FWB

1.0 20CWB
68FWB
18CWB
0.9 64FWB
16CWB
0.8 61FWB
15CWB
59FWB
0.7

0.6

24CWB
75FWB
22CWB
1.2 72FWB
20CWB
1.1 68FWB
18CWB
Ratio of power input

64FWB
1.0
16CWB
61FWB
0.9 15CWB
59FWB
0.8

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 25.0 31.5
Heating 1.3 15CDB
Capacity BTU/h 85,300 107,500 59FDB
Input kW 5.69 7.22 1.2
Ratio of heating capacity

1.1
20CDB
68FDB
1.0

0.9
25CDB
0.8 77FDB
27CDB
0.7 80FDB

0.6

0.5

0.4

1.2

1.1
Ratio of power input

15CDB
1.0 59FDB

0.9

0.8 20CDB
68FDB
0.7
25CDB
0.6 77FDB

27CDB
0.5 80FDB

0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 30
6. CAPACITY TABLES

PUHY- RP300YJM-B RP350YJM-B 1.4 Indoor Temperature


Nominal kW 33.5 40.0
Cooling 1.3
Capacity BTU/h 114,300 136,500
Input kW 8.98 11.79

Ratio of cooling capacity


1.2
24CWB
PUHY- RP400YSJM-B 1.1 75FWB
22CWB
Nominal kW 45.0 72FWB
Cooling 1.0
Capacity BTU/h 153,500 20CWB
68FWB
Input kW 11.87 0.9 18CWB
64FWB
(There is no difference in cooling performance 0.8 16CWB
between Standard Mode and COP Priority Mode.) 61FWB
15CWB
0.7 59FWB

0.6

24CWB
75FWB
1.2 22CWB
72FWB

1.1 20CWB
68FWB
Ratio of power input

18CWB
1.0 64FWB
16CWB
0.9 61FWB
15CWB
59FWB
0.8

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP300YJM-B RP350YJM-B 1.4 Indoor Temperature


Nominal kW 37.5 45.0
Heating 1.3
Capacity BTU/h 128,000 153,500
Input kW 9.42 12.60 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PUHY- RP400YSJM-B
Nominal kW 20CDB
50 1.0 68FDB
Heating
Capacity BTU/h 170,600
0.9
Input kW 11.38
0.8
25CDB
77FDB
0.7
27CDB
80FDB
0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0
15CDB
0.9 59FDB

0.8

0.7 20CDB
68FDB

0.6
25CDB
0.5 77FDB
27CDB
0.4 80FDB

-20 -15 -10 -5 0 5 10 15 CWB


-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 31
6. CAPACITY TABLES

PUHY- RP450YSJM-B RP500YSJM-B 1.4 Indoor Temperature


Nominal kW 50.0 56.0
Cooling 1.3
Capacity BTU/h 170,600 191,100
Input kW 13.77 15.68

Ratio of cooling capacity


1.2 24CWB
75FWB
22CWB
PUHY- RP550YSJM-B P600YSJM-B 1.1 72FWB
Nominal kW 63.0 69.0 20CWB
Cooling 1.0 68FWB
Capacity BTU/h 215,000 235,400 18CWB
Input 64FWB
kW 17.50 18.59 0.9
16CWB
61FWB
PUHY- RP650YSJM-B 0.8 15CWB
Nominal kW 73.0 59FWB
Cooling 0.7
Capacity BTU/h 249,100
Input kW 21.09 0.6
(There is no difference in cooling performance
between Standard Mode and COP Priority Mode.)
24CWB
1.2 75FWB
22CWB
1.1 72FWB
20CWB
Ratio of power input

68FWB
1.0
18CWB
64FWB
0.9 16CWB
61FWB
0.8 15CWB
59FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP450YSJM-B RP500YSJM-B 1.4 Indoor Temperature


Nominal kW 56.0 63.0
Heating 1.3
Capacity BTU/h 191,100 215,000
Input kW 12.81 14.44 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PUHY- RP550YSJM-B RP600YSJM-B
Nominal kW 69.0 76.5 1.0 20CDB
68FDB
Heating
Capacity BTU/h 235,400 261,000
0.9
Input kW 16.62 19.22
25CDB
0.8 77FDB
PUHY- RP650YSJM-B 27CDB
0.7 80FDB
Nominal kW 81.5
Heating
Capacity BTU/h 278,100 0.6
Input kW 21.73 0.5

0.4

1.2

1.1
Ratio of power input

1.0
15CDB
59FDB
0.9

0.8 20CDB
68FDB
0.7
25CDB
0.6 77FDB

27CDB
0.5 80FDB

0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 32
6. CAPACITY TABLES

PUHY- RP700YSJM-B RP750YSJM-B 1.4 Indoor Temperature


Nominal kW 80.0 85.0
Cooling 1.3
Capacity BTU/h 273,000 290,000
Input kW 22.22 24.14

Ratio of cooling capacity


1.2
24CWB
75FWB
PUHY- RP800YSJM-B 1.1
22CWB
Nominal kW 90.0 72FWB
Cooling 1.0
Capacity BTU/h 307,100 20CWB
68FWB
Input kW 25.49 0.9 18CWB
64FWB
(There is no difference in cooling performance 0.8 16CWB
between Standard Mode and COP Priority Mode.) 61FWB
15CWB
0.7 59FWB

0.6

24CWB
1.2 75FWB
22CWB
1.1 72FWB
20CWB
Ratio of power input

68FWB
1.0
18CWB
64FWB
0.9 16CWB
61FWB
0.8 15CWB
59FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP700YSJM-B PR750YSJM-B 1.4 Indoor Temperature


Nominal kW 88.0 95.0
Heating 1.3
Capacity BTU/h 300,300 324,100
Input kW 20.13 21.78 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PUHY- RP800YSJM-B
Nominal kW 20CDB
100.0 1.0 68FDB
Heating
Capacity BTU/h 341,200
0.9
Input kW 23.75 25CDB
0.8 77FDB
27CDB
0.7 80FDB

0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0

0.9 15CDB
59FDB

0.8

0.7 20CDB
68FDB

0.6
25CDB
77FDB
0.5
27CDB
80FDB
0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 33
6. CAPACITY TABLES

PUHY- RP850YSJM-B RP900YSJM-B 1.4 Indoor Temperature


Nominal kW 96.0 101.0
Cooling 1.3
Capacity BTU/h 327,600 344,600
24CWB
Input kW 27.11 28.29

Ratio of cooling capacity


1.2 75FWB
22CWB
(There is no difference in cooling performance
1.1 72FWB
between Standard Mode and COP Priority Mode.)
20CWB
68FWB
1.0
18CWB
64FWB
0.9 16CWB
61FWB
0.8 15CWB
59FWB

0.7

0.6

24CWB
75FWB
22CWB
1.1 72FWB
20CWB
1.0 68FWB
18CWB
Ratio of power input

64FWB
0.9
16CWB
61FWB
0.8 15CWB
59FWB
0.7

0.6

0.5

0.4

0.3
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP850YSJM-B RP900YSJM-B 1.4 Indoor Temperature


Nominal kW 108.0 113.0
Heating 1.3
Capacity BTU/h 368,500 385,600
Input kW 26.47 28.39 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
20CDB
1.0 68FDB

0.9
25CDB
0.8 77FDB
27CDB
0.7 80FDB

0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0
15CDB
59FDB
0.9

0.8 20CDB
68FDB
0.7
25CDB
0.6 77FDB

27CDB
0.5 80FDB

0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 34
6. CAPACITY TABLES
Correction by temperature (Connection with PWFY-P100/200VM-E-AU (HEX unit))

PUHY- RP200YJM-B RP250YJM-B 1.5 HEX unit inlet-water temperature


Nominal kW 22.4 28.0
Cooling 1.4
Capacity BTU/h 76,400 95,500
Input kW 5.68 7.62 1.3

Ratio of cooling capacity


1.2

1.1
35C
1.0 95F
30C
86F
0.9
25C
77F
0.8
20C
68F
0.7 15C
59F
0.6 10C
50F
0.5

1.2 35C
95F
1.1 30C
Ratio of power input

86F

1.0 25C
77F
20C
0.9 68F
15C
0.8 59F
10C
0.7 50F

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP200YJM-B RP250YJM-B 1.4 HEX unit inlet-water temperature


Nominal kW 25.0 31.5
Heating 1.3
Capacity BTU/h 85,300 107,500
Input kW 5.69 7.22 1.2
Ratio of heating capacity

10C
50F
1.1 20C
68F
1.0 30C
86F

0.9 35C
95F

0.8 40C
104F
0.7

0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0
40C
104F
0.9
35C
95F
0.8
30C
86F
0.7
20C
68F
0.6
10C
50F
0.5

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 35
6. CAPACITY TABLES
PUHY- RP300YJM-B RP350YJM-B 1.5 HEX unit inlet-water temperature
Nominal kW 33.5 40.0
Cooling 1.4
Capacity BTU/h 114,300 136,500
Input kW 8.98 11.79 1.3

Ratio of cooling capacity


1.2
PUHY- RP400YSJM-B
Nominal kW 45.0 1.1
Cooling
Capacity BTU/h 153,500 35C
1.0 95F
Input kW 11.87 30C
86F
0.9
25C
77F
0.8
20C
68F
0.7 15C
59F
0.6 10C
50F
0.5

1.2 35C
95F
1.1 30C
Ratio of power input

86F

1.0 25C
77F
20C
0.9 68F
15C
0.8 59F
10C
0.7 50F

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP300YJM-B RP350YJM-B 1.4 HEX unit inlet-water temperature


Nominal kW 37.5 45.0
Heating 1.3
Capacity BTU/h 128,000 153,500
Input kW 9.42 12.60 1.2
Ratio of heating capacity

10C
50F
1.1 20C
PUHY- RP400YSJM-B 68F

Nominal kW 50 1.0 30C


Heating 86F
Capacity BTU/h 170,600 0.9 35C
95F
Input kW 11.38
0.8 40C
104F
0.7

0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0
40C
104F
0.9
35C
95F
0.8
30C
86F
0.7
20C
68F
0.6
10C
50F
0.5

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 36
6. CAPACITY TABLES
PUHY- RP450YSJM-B RP500YSJM-B 1.5 HEX unit inlet-water temperature
Nominal kW 50.0 56.0
Cooling 1.4
Capacity BTU/h 170,600 191,100
Input kW 13.77 15.68 1.3

Ratio of cooling capacity


1.2
PUHY- RP550YSJM-B RP600YSJM-B
Nominal kW 63.0 69.0 1.1
Cooling
Capacity BTU/h 215,000 235,400 35C
1.0 95F
Input kW 17.50 18.59 30C
86F
0.9
PUHY- RP650YSJM-B 25C
77F
Nominal kW 73.0 0.8
20C
Cooling 68F
Capacity BTU/h 249,100 0.7 15C
Input kW 21.09 59F
0.6 10C
50F
0.5

1.2 35C
95F
1.1 30C
Ratio of power input

86F

1.0 25C
77F
20C
0.9 68F
15C
0.8 59F
10C
0.7 50F

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP450YSJM-B RP500YSJM-B 1.4 HEX unit inlet-water temperature


Nominal kW 56.0 63.0
Heating 1.3
Capacity BTU/h 191,000 215,000
Input kW 12.81 14.44 1.2
Ratio of heating capacity

10C
50F
1.1 20C
PUHY- RP550YSJM-B RP600YSJM-B 68F
Nominal kW 69.0 76.5 1.0 30C
Heating 86F
Capacity BTU/h 235,400 261,000 0.9 35C
95F
Input kW 16.62 19.22
0.8 40C
104F
PUHY- RP650YSJM-B 0.7
Nominal kW 81.5
Heating 0.6
Capacity BTU/h 278,100
Input kW 21.73 0.5

0.4

1.2

1.1
Ratio of power input

1.0
40C
104F
0.9
35C
95F
0.8
30C
86F
0.7
20C
68F
0.6
10C
50F
0.5

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 37
6. CAPACITY TABLES
PUHY- RP700YSJM-B RP750YSJM-B 1.5 HEX unit inlet-water temperature
Nominal kW 80.0 85.0
Cooling 1.4
Capacity BTU/h 273,000 290,000
Input kW 22.22 24.14 1.3

Ratio of cooling capacity


1.2
PUHY- RP800YSJM-B RP850YSJM-B
Nominal kW 90.0 96.0 1.1
Cooling
Capacity BTU/h 307,100 327,600 35C
1.0 95F
Input kW 25.49 27.11 30C
86F
0.9
PUHY- RP900YSJM-B 25C
77F
Nominal kW 101.0 0.8
20C
Cooling 68F
Capacity BTU/h 344,600 0.7 15C
Input kW 28.29 59F
0.6 10C
50F
0.5

1.2 35C
95F
1.1 30C
Ratio of power input

86F

1.0 25C
77F
20C
0.9 68F
15C
0.8 59F
10C
0.7 50F

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PUHY- RP700YSJM-B RP750YSJM-B 1.4 HEX unit inlet-water temperature


Nominal kW 88.0 95.0
Heating 1.3
Capacity BTU/h 300,300 324,100
Input kW 20.13 21.78 1.2
Ratio of heating capacity

10C
50F
1.1 20C
PUHY- RP800YSJM-B RP850YSJM-B 68F
Nominal kW 100.0 108.0 1.0 30C
Heating 86F
Capacity BTU/h 341,200 368,500 0.9 35C
95F
Input kW 23.75 26.47
0.8 40C
104F
PUHY- RP900YSJM-B 0.7
Nominal kW 113.0
Heating 0.6
Capacity BTU/h 385,600
Input kW 28.39 0.5

0.4

1.2

1.1
Ratio of power input

1.0
40C
104F
0.9
35C
95F
0.8
30C
86F
0.7
20C
68F
0.6
10C
50F
0.5

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 38
6. CAPACITY TABLES
6-2. Correction by total indoor
CITY MULTI system have different capacities and inputs when many combinations of indoor units with different total capacities
are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity
for a particular application.

PUHY-RP200, 250YJM-B(-BS)

50.0

40.0
Capacity(kW)

30.0

20.0

10.0

10.0
Input(kW)

5.0

RP200 RP250
Cooling Cooling
Heating Heating
0.0
50 100 150 200 250 300 350
Total capacity of indoor units

PUHY-RP300, 350YJM-B(-BS)

50.0

40.0
Capacity(kW)

30.0

20.0

10.0

15.0

12.5

10.0
Input(kW)

7.5

5.0 RP300 RP350


Cooling Cooling
Heating Heating
2.5
100 200 300 400 500
Total capacity of indoor units

OUTDOOR UNITS 39
6. CAPACITY TABLES

PUHY-RP400, 450YSJM-B(-BS)

60.0

50.0
Capacity(kW)

40.0

30.0

20.0

10.0

15.0
Input(kW)

10.0

5.0
RP400 RP450
Cooling Cooling
Heating Heating
0.0
200 300 400 500 600
Total capacity of indoor units

PUHY-RP500, 550YSJM-B(-BS)

70.0

60.0
Capacity(kW)

50.0

40.0

30.0

20.0

15.0
Input(kW)

10.0

5.0
RP500 RP550
Cooling Cooling
Heating Heating
0.0
200 300 400 500 600 700 800
Total capacity of indoor units

OUTDOOR UNITS 40
6. CAPACITY TABLES

PUHY-RP600,650YSJM-B(-BS)

90.0

80.0
Capacity(kW)

70.0

60.0

50.0

40.0

30.0
Input(kW)

20.0

10.0
RP600 RP650
Cooling Cooling
Heating Heating
0.0
200 300 400 500 600 700 800 900
Total capacity of indoor units

PUHY-RP700,750YSJM-B(-BS)

120.0

100.0
Capacity(kW)

80.0

60.0

40.0

20.0

30.0
Input(kW)

20.0

10.0
RP700 RP750
Cooling Cooling
Heating Heating
0.0
300 400 500 600 700 800 900 1000
Total capacity of indoor units

OUTDOOR UNITS 41
6. CAPACITY TABLES

PUHY-RP800, 850YSJM-B(-BS)

120.0

100.0
Capacity(kW)

80.0

60.0

40.0

40.0

30.0
Input(kW)

20.0

10.0 RP800 RP850


Cooling Cooling
Heating Heating
0.0
400 500 600 700 800 900 1000 1100 1200
Total capacity of indoor units

PUHY-RP900YSJM-B(-BS)

140.0

120.0
Capacity(kW)

100.0

80.0

60.0

40.0

30.0
Input(kW)

20.0

10.0
RP900
Cooling
Heating
0.0
400 600 800 1000 1200 1400
Total capacity of indoor units

OUTDOOR UNITS 42
6. CAPACITY TABLES
6-3. Correction by refrigerant piping length
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
6-3-1 and 6-3-2, the capacity can be observed. 6-3-3 shows how to obtain the equivalent length of piping.

6-3-1. Cooling capacity correction


PUHY-RP200YJM-B(-BS) Total capacity of indoor unit PUHY-RP400YSJM-B(-BS) Total capacity of indoor unit
1 100 1 200
Cooling capacity correction factor

Cooling capacity correction factor


0.95 150 0.95 300

0.90 200 0.90


400
260 520
0.85 0.85

0.80 0.80

0.75 0.75

0.70 0.70
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP250YJM-B(-BS) Total capacity of indoor unit PUHY-RP450YSJM-B(-BS) Total capacity of indoor unit
1 125 1 225
188 338
Cooling capacity correction factor

Cooling capacity correction factor


0.95
0.95
250 450
0.90 325 585
0.90
0.85
0.85
0.80

0.75 0.80

0.70 0.75
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP300YJM-B(-BS) Total capacity of indoor unit PUHY-RP500YSJM-B(-BS) Total capacity of indoor unit
1 150 1 250
375
Cooling capacity correction factor

Cooling capacity correction factor

0.95 225 0.95


500
0.90 0.90 650
300
390
0.85 0.85

0.80 0.80

0.75 0.75

0.70 0.70
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP350YJM-B(-BS) Total capacity of indoor unit PUHY-RP550YSJM-B(-BS) Total capacity of indoor unit
1 175 1 275
263 413
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95
350 550
0.90 455 0.90 715

0.85 0.85

0.80 0.80

0.75 0.75

0.70 0.70
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140
Piping equivalent length (m) Piping equivalent length (m)

OUTDOOR UNITS 43
6. CAPACITY TABLES

PUHY-RP600YSJM-B(-BS) Total capacity of indoor unit PUHY-RP800YSJM-B(-BS) Total capacity of indoor unit
1 300 1 400,
450 600
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95
600 800
0.90 780 0.90 1040

0.85 0.85

0.80 0.80

0.75 0.75

0.70 0.70
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP650YSJM-B(-BS) Total capacity of indoor unit PUHY-RP850YSJM-B(-BS) Total capacity of indoor unit
1 325, 1 425
488 637
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95
650 850
0.90 845 0.90 1105

0.85 0.85

0.80 0.80

0.75 0.75

0.70 0.70
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP700YSJM-B(-BS) Total capacity of indoor unit PUHY-RP900YSJM-B(-BS) Total capacity of indoor unit
1 350, 1 450
525 675
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95
700 900
0.90 910 0.90 1170

0.85 0.85

0.80 0.80

0.75 0.75

0.70 0.70
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP750YSJM-B(-BS) Total capacity of indoor unit


1 375,
563
Cooling capacity correction factor

0.95
750
0.90 975

0.85

0.80

0.75

0.70
0 20 40 60 80 100 120
Piping equivalent length (m)

OUTDOOR UNITS 44
6. CAPACITY TABLES

6-3-2. Heating capacity correction


PUHY-RP200, 250YJM-B(-BS) PUHY-RP600, 650YSJM-B(-BS)
1.00 1.00
Heating capacity correction factor

Heating capacity correction factor


0.95 0.95

0.90 0.90
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP300, 350YJM-B(-BS) PUHY-RP700, 750, 800YSJM-B(-BS)


1.00 1.00
Heating capacity correction factor

Heating capacity correction factor


0.95 0.95

0.90 0.90
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-RP400, 450, 500, 550YSJM-B(-BS) PUHY-RP850, 900YSJM-B(-BS)


1.00 1.00
Heating capacity correction factor

Heating capacity correction factor

0.95 0.95

0.90 0.90
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

6-3-3. How to obtain the equivalent piping length


1. PUHY-RP200YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.35 x number of bent on the piping) [m]
2. PUHY-RP250, 300YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.42 x number of bent on the piping) [m]
3. PUHY-RP350YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.47 x number of bent on the piping) [m]
4. PUHY-RP400, 450, 500, 550, 600, 650YSJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]
5. PUHY-RP700, 750, 800YSJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.70 x number of bent on the piping) [m]
6. PUHY-RP850, 900YSJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.80 x number of bent on the piping) [m]

OUTDOOR UNITS 45
6. CAPACITY TABLES
6-4. Correction at frost and defrost
Due to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be
calculated by multiplying the correction factor shown in the table below.

Table of correction factor at frost and defrost


Outdoor inlet air temp. C 6 4 2 1 0 -2 -4 -6 -8 -10 -20
Outdoor inlet air temp. F 43 39 36 34 32 28 25 21 18 14 14
PUHY-RP200YJM-B(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP250YJM-B(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP300YJM-B(-BS) 1.00 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP350YJM-B(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP400YSJM-B(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP450YSJM-B(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP500YSJM-B(-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP550YSJM-B(-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP600YSJM-B(-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP650YSJM-B(-BS) 1.00 0.98 0.89 0.88 0.89 0.90 0.92 0.95 0.95 0.95 0.95
PUHY-RP700YSJM-B(-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP750YSJM-B(-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP800YSJM-B(-BS) 1.00 0.98 0.89 0.88 0.89 0.90 0.92 0.95 0.95 0.95 0.95
PUHY-RP850YSJM-B(-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP900YSJM-B(-BS) 1.00 0.98 0.89 0.88 0.89 0.90 0.92 0.95 0.95 0.95 0.95

OUTDOOR UNITS 46
6. CAPACITY TABLES
6-5. Operation temperature range

86 30

77 25
Indoor temperature

68 20

59 15

50 10

41 5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Outdoor temperature

86 30

77 25
Indoor temperature

68 20

59 15

50 10

41 5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Outdoor temperature

OUTDOOR UNITS 47
7. OPTIONAL PARTS
7-1. OUTDOOR TWINNING KIT
7. OPTIONAL PARTS

For PUHY-RP-YSJM, following optional Outdoor Twinning Kit is needed to use to combine to refrigerant flows of its PUHY-RP-
YJM. Details of selecting the proper kit should be referred to the System Design Section.

mm
CMY-RP100VBK
For Gas pipe: For Liquid pipe: <Deformed pipe(Accessory)>

666
OD 28.58 OD 28.58 ID 22.2
ID 28.58 OD 12.7 ID 9.52
600
Pipe cover
(Dot-dashed part) Pipe cover OD 12.7
ID 12.7
(Dot-dashed part) 49 62
Distributer OD 15.88
(2 pcs.) (2 pcs.)
OD 31.75 Distributer

162
OD 15.88 ID 19.05
OD 28.58 ID 25.4

98
ID 28.58 ID 12.7

ID 15.88 The straight part of pipe 85 62


ID 34.93 The straight part of pipe
Note 2 Note 2
OD 12.7 OD 28.58 ID 19.05 OD 34.93 ID 41.28
( 500 ) OD 28.58 ( 500 )
748
658
62 69
(2 pcs.)

ID:Inner Diameter OD:Outer Diameter

CMY-RP200VBK mm
For Gas pipe: For Liquid pipe: <Deformed pipe(Accessory)>
666
OD 28.58
ID 28.58
606 OD 15.88
Pipe cover
(Dot-dashed part) Pipe cover ID 15.88
(Dot-dashed part)
Distributer OD 19.05
OD 31.75
Distributer
162

ID 19.05 OD 22.2 ID 19.05

115
OD 12.7 ID 9.52
ID 34.93

The straight part of pipe 49 62


The straight part of pipe
ID 38.1 Note 2 (2 pcs.)
Note 2 ID 19.05
OD 15.88
( 500 ) OD 28.58
( 500 ) OD 25.4 ID 19.05
OD 15.88 ID 9.52

743 661
49 62

663 OD 25.4
ID 28.58
Pipe cover 600 OD 12.7 OD 38.1 ID 41.28
OD 25.4 ID 22.2
(Dot-dashed part) Pipe cover ID 12.7
(Dot-dashed part)
Distributer OD 15.88
OD 28.58
Distributer
162

62
ID 12.7 69
98

ID 28.58

The straight part of pipe OD 28.58 ID 22.2 OD 15.88 ID 12.7


The straight part of pipe
ID 34.93 Note 2
Note 2 ID 19.05
OD 12.7
( 500 ) OD 25.4
( 500 ) 62 49
(2 pcs.)
658
748

ID:Inner Diameter OD:Outer Diameter

Note 1. Reference the attitude angle of the branch pipe below the fig.
Distributer
15

The angle of the branch pipe is within 15 against the horizontal plane.
2. The length of the straight part of pipe connected in front of the twinning pipe must be 500mm or longer.
Removing, cutting and bending the twinning kit will cause damage the unit.
3. Pipe diameter is indicated by inside diameter.

OUTDOOR UNITS 48
8. UNIT SELECTION
8-1. Indoor and outdoor unit selection
8. UNIT SELECTION

(1) Selecting indoor units


1) Calculate the thermal road of each room.

2) Based on the thermal load corrected for indoor unit return air temperature, select appropriate indoor unit models.
Refer to the correction factor diagram for the outdoor unit whose capacity is the closest to the total thermal load of the
system (Qi). Refer to CAPACITY TABLES (Indoor unit) and 6. CAPACITY TABLES.

3) Calculate the total capacity of the indoor units in the system (N).

(2) Selecting outdoor units


1) Based on the total capacity of the indoor units (N), tentatively select the capacity of the outdoor unit (X).
The total capacity of the indoor units to be connected to a given outdoor unit (N) should not exceed the maximum
connectable capacity of the outdoor unit.

2) The tentatively selected standard capacity of the outdoor unit (X) will be defined as Qs.
* If the total capacity of the indoor units that are connected to a given outdoor unit exceeds 100% of the outdoor unit
capacity (X), refer to the outdoor unit partial load capacity table, find the capacity that corresponds to the total capacity
N, and use it as the standard outdoor unit capacity (Qs).

3) Obtain the maximum outdoor unit capacity (Qm) by multiplying Qs (standard outdoor unit capacity) by the following
correction factors: piping length, outside air temperature, and defrost (heating).
Find the piping length correction factor from the diagram that corresponds to the total indoor unit capacity (N).

Qm = Qs x Piping length correction factor x Outside air temperature correction factor


x Defrost correction factor (heating only) x Pipe diameter correction factor

Outside air temperature correction factor Refer to 6-1.


Piping length correction factor Refer to 6-3.
Defrost correction factor (heating only) Refer to 6-4.
Pipe diameter correction factor (applicable only if non-standard size pipes are connected) Refer to 8-3.

4) Make sure the maximum outdoor unit capacity Qm is equal to or greater than the total thermal load Qi.
If Qm is smaller than Qi, reconsider the outdoor unit capacity (X) so that Qm Qi will hold true.

5) After selecting indoor and outdoor units, calculate the apportioned indoor unit capacity, and make sure that the formula
"Thermal load Indoor unit capacity" will hold true for each room.
If the thermal load exceeds the indoor unit capacity in one or more rooms, increase the indoor unit size as long as doing so
will not exceed the maximum connectable capacity of the outdoor unit. Then, start over from step 1) above. If the
maximum connectable capacity is exceeded by increasing the indoor unit capacity, increase the outdoor capacity as well,
then start over from step 1) above.

Calculate the indoor/outdoor unit capacities and check for unit compatibility by
considering both the heating and the cooling loads. If the formula Qm Qi does not
hold true for either cooling or heating, reconsider the outdoor unit capacity (X).

OUTDOOR UNITS 49
8. UNIT SELECTION
(3) Obtaining the unit capacity
A. If the apportioned indoor unit capacity obtained in step 5) on the previous page is equal to or greater than the rated
indoor unit capacity, the following formula will be used to calculate the indoor unit capacity: "Rated capacity x return air
temperature correction factor x piping length correction factor (x pipe diameter correction factor)".

B. If the apportioned indoor unit capacity obtained in step 5) on the previous page is smaller than the rated indoor unit
capacity, the following formula will be used to calculate the indoor unit capacity: "Apportioned indoor unit capacity x
return air temperature correction factor."

* The standard outside air temperatures used to obtain the return air temperature correction factor is 35CDB for cooling
and 6CWB for heating.
* If non-standard size pipes are connected, use the pipe diameter correction factors for the main pipes, merge pipes, and
branch pipes.

(4) Notes
When deciding the outside air temperature to calculate unit capacity requirements, take into consideration the possible
temperature rise around the outdoor unit due to short-cycling. (When installing outdoor units collectively on the rooftop or if
outdoor units are surrounded by walls or other objects, it is recommended to set the outside temperature as 43C for
calculation.)

If you want to take sensible heat load into consideration, refer to the relevant catalogs for information on sensible heat
factor when selecting indoor units.

OUTDOOR UNITS 50
8. UNIT SELECTION
8-2. Calculation samples
(1) To connect indoor units using the standard pipes
Design conditions
<Cooling> Indoor design dry-bulb temperature: 26C/Indoor design wet-bulb temperature: 18.5C
Outdoor design dry-bulb temperature: 36C
Cooling load: 13.5 kW for each of the two rooms
<Heating> Indoor design dry-bulb temperature: 21C
Outdoor design wet-bulb temperature: 5C
Heating load: 14.5 kW for each of the two rooms
<Miscellaneous information>
Main piping: 28.58 x 45 m, Branch piping: 19.05 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
A. Calculating the cooling load
a) The thermal load (13.5 kW/room), indoor unit return air temperature correction factor, and piping length correction
factor are used to calculate the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively
selected. (Because the total thermal load is 27 kW, the air temperature correction diagram for the 250 model outdoor
unit will be used.)
b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected.
Based on the above, the standard capacity Qs will be 28 kW.
c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:
Outside air temperature 36CDB Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19C)
Piping length: 50 m Capacity correction factor: 0.97
If the standard capacity Qs is corrected for indoor/outside air temperatures and piping length, the maximum outdoor unit
capacity Qm can be obtained as follows: Qm = 28 x 0.99 x 0.97 = 26.8 kW.
The result shows that the thermal load Qi (27 kW) exceeds the unit capacity Qm, so a larger 300 model outdoor unit
needs to be selected.
d) For the 300 model units, the outside air temperature correction factor is 0.99. The piping length correction factor that
can be obtained from the diagram for the system whose total indoor unit capacity is 250 would be 0.96.
Because the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained
using the following formula: Qm = 33.5 x 0.99 x 0.96 = 31.8 kW. The result 31.8 kW is greater than the Qi (27 kW), so
the maximum capacity Qm meets the capacity requirement.
e) Compare the thermal loads on the indoor units, using the maximum outdoor unit capacity apportioned to each indoor
unit and taking the indoor unit return air temperature correction factors into consideration. The correction factor for the
return air temperature at 18.5CWB is 0.99 (at the standard outside dry-bulb temperature of 35C), and this value can
be plugged into the following formula to obtain the capacity.
32.1 kW x 125/250 x 0.99 = 15.8 kW
The result shows that the capacity (15.8 kW) is greater than the thermal load (13.5 kW), and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
B. Calculating the heating load
Next, you will calculate the heating load and unit capacity requirements, using the models that were selected in the
previous section.
a) The standard capacity (Qs) of the tentatively selected 300 model outdoor unit is 37.5 kW.
b) Use this value in the following formula to obtain the maximum outdoor unit capacity Qm as shown below:
Qm = 37.5 x 1.00 x 0.965 x 0.975 = 35.2 kW, (where the outside air temperature is 5CWB, capacity correction factor
is 1.00 (at the standard indoor dry-bulb temperature of 20C), defrost correction factor is 0.965, piping length is 50 m,
and capacity correction factor is 0.975).
The result shows that the Maximum outdoor unit capacity Qm (35.2 kW) exceeds the heating load Qi (29 kW).
c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 35.2 x 125/250 x 0.96 = 16.8 kW (where the indoor unit return air temperature correction factor at 21CDB is
0.96) (standard outside temperature at 6C). The result shows that the unit capacity (16.8 kW) exceeds the thermal
load for each room (14.5 kW).
Based on the above calculation, the following indoor and outdoor units can be selected.
Indoor units: 125 model x 2 units
Outdoor unit: RP300 model
C. Calculating the capacity requirement
a) The cooling capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 15.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (14.0 kW). The actual cooling capacity under the specified conditions is
calculated as follows: 14.0 x 0.99 x 0.97 = 13.4 kW (where the return air temperature correction factor at the standard
outside temperature of 35CDB is 0.99 and the piping length correction factor is 0.97).
b) The heating capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 16.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (16.0 kW). The actual heating capacity under the specified conditions is
calculated as follows: 16.0 x 0.95 x 0.975 = 14.8 kW (where the return air temperature correction factor at the standard
outside temperature of 6CWB is 0.95 and the piping length correction factor is 0.975).

OUTDOOR UNITS 51
8. UNIT SELECTION
(2) To connect indoor units using non-standard pipes
Design conditions
<Cooling> Indoor design dry-bulb temperature: 26C/Indoor design wet-bulb temperature: 18.5C
Outdoor design dry-bulb temperature: 36C
Cooling load: 13.5 kW for each of the two rooms
<Heating> Indoor design dry-bulb temperature: 21C
Outdoor design wet-bulb temperature: 5C
Heating load: 14.5 kW for each of the two rooms
<Miscellaneous information>
Main piping: 25.4 x 45 m, Branch piping: 15.88 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
A. Calculating the cooling load
a) The thermal load of 13 kW per room and the indoor unit return air temperature correction factor are used to calculate
the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively selected. (Because the total
thermal load is 26 kW, the air temperature correction diagram for the 250 model outdoor unit will be used.)

b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected.
Based on the above, the standard capacity Qs will be 28 kW.
c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:

Outside air temperature 36CDB Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19C)
Piping length: 50 m Capacity correction factor: 0.97
Main piping: 25.4 x 45 m Pipe diameter correction factor: 0.98
The standard capacity Qs is corrected for indoor/outside air temperatures, piping length, and pipe diameter to obtain the
maximum outdoor unit capacity Qm as follows: Qm = 28 x 0.99 x 0.97 x 0.98 = 26.3 kW. Because this value does not
meet the thermal load Qi (27 kW), a larger 300 model outdoor unit needs to be selected.

d) For the 300 model, the outside air temperature correction factor is 0.99, the pipe diameter correction factor for a 45 m
pipe with a diameter of 25.4 is 0.98, and the piping length correction factor is 0.96 (read from the diagram for the unit
whose total indoor unit capacity N is 250).
Where the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained as
follows: Qm = 33.5 x 0.99 x 0.98 x 0.96= 31.2 kW. This value is greater than the thermal load Qi (27 kW), and the
maximum capacity Qm satisfies the capacity requirements.

e) Compare the thermal loads on the indoor unit side, using the maximum outdoor unit capacity apportioned to each
indoor unit and taking the indoor unit return air condition correction factors into consideration. The correction factor for
the return air temperature at 18.5C is 0.99 (at the standard outside dry-bulb temperature of 35C), and the pipe
diameter correction factor for a 5 m pipe with a diameter of 15.88 connected to a 125-model unit is 0.99. These
values can be plugged into the following formula to obtain the capacity.
31.8 kW x 125/250 x 0.99 x 0.99=15.5 kW.
The result shows that the capacity (15.5 kW) is greater than the thermal load of 13.5 kW, and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
B. Calculating the heating load
Next, we will calculate the heating load, using the models that are selected based on the cooling load calculation.
a) The standard capacity Qs of the tentatively selected (during cooling load calculation) 300 model outdoor unit is 37.5
kW.
b) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 300 model outdoor units are as follows:
Outside air temperature 5CWB Capacity correction factor 1.00 (at the standard indoor dry-bulb temperature of 20C)
Defrost correction factor is 0.975
Piping length: 50 m Capacity correction factor: 0.975
Main piping: 25.4 x 45 m Pipe diameter correction factor: 0.98
The standard capacity Qs is corrected for indoor/outside air temperatures and piping length to obtain the maximum
outdoor unit capacity Qm as follows: Qm = 37.5 x 1.00 x 0.975 x 0.975 x 0.98 = 34.9 kW.
The result shows that the Maximum outdoor unit capacity Qm (34.9 kW) exceeds the heating load Qi (29 kW).
c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 34.9 x 125/250 x 0.96 x 0.99 = 16.5 kW (where the correction factor for the indoor unit return air temperature
of 21CDB is 0.96 (standard outside temperature at 6C), and the pipe diameter correction factor for a 5 m branch pipe
with a diameter of 15.88 connected to a 125 models is 0.99. The result shows that the unit capacity 16.5 kW exceeds
the thermal load for each room (14.5 kW).
Based on the above calculation, the following indoor and outdoor units can be selected.
Indoor units: 125 model x 2 units
Outdoor unit: RP300 model

OUTDOOR UNITS 52
8. UNIT SELECTION
<Capacity requirement calculation flow chart>

Obtain the thermal load (Qi).

Correct for the indoor unit return air temperature.

Determine the capacity for each indoor unit.

Calculate the total indoor unit capacity (N).

Select the outdoor unit capacity (X).

Correct the standard outdoor unit capacity (Qs)


for outside air temperature and piping length to
obtain the corrected capacity (Qm).

YES
Select the outdoor unit one rank higher
Thermal load Qi > Corrected capacity Qm
in capacity.

NO

Apportion the corrected outdoor unit capacity (Qm)


to each indoor unit.

Multiply the apportioned capacity by the indoor


unit temperature correction factor, and make sure it
is equal to or greater than the thermal load.

Finish
(calculations to be done for both cooling and heating)

OUTDOOR UNITS 53
8. UNIT SELECTION
8-3. Pipe diameter correction factor
8-3-1. Correction factors for the outdoor units and main pipe diameter
PUHY-RP200YJM-B PUHY-RP350YJM-B
1 1
Pipe diameter correction factor

Pipe diameter correction factor


28.58
25.4

0.90 22.2 0.90 25.4


19.05

0.80 0.80

0.70 0.70

0.60 0.60
0 20 40 60 80 100 0 20 40 60 80 100
Equivalent main piping length (m) Equivalent main piping length (m)

PUHY-RP250YJM-B PUHY-RP400YSJM-B
1 1
Pipe diameter correction factor

Pipe diameter correction factor


25.4
28.58

0.90 22.2 0.90

0.80 0.80

0.70 0.70

0.60 0.60
0 20 40 60 80 100 0 20 40 60 80 100
Equivalent main piping length (m) Equivalent main piping length (m)

PUHY-RP300YJM-B PUHY-RP450YSJM-B
1 1
Pipe diameter correction factor

Pipe diameter correction factor

25.4

0.90 0.90
28.58
22.2

0.80 0.80

0.70 0.70

0.60 0.60
0 20 40 60 80 100 0 20 40 60 80 100
Equivalent main piping length (m) Equivalent main piping length (m)

OUTDOOR UNITS 54
8. UNIT SELECTION

PUHY-RP500YSJM-B PUHY-RP650YSJM-B
1 1
Pipe diameter correction factor

Pipe diameter correction factor


34.93
0.90 0.90
28.58
28.58

0.80 0.80

0.70 0.70

0.60 0.60
0 20 40 60 80 100 0 20 40 60 80 100
Equivalent main piping length (m) Equivalent main piping length (m)

PUHY-RP550YSJM-B PUHY-RP700YSJM-B
1 1
Pipe diameter correction factor

Pipe diameter correction factor


0.90 0.90 34.93
28.58

0.80 0.80

0.70 0.70

0.60 0.60
0 20 40 60 80 100 0 20 40 60 80 100
Equivalent main piping length (m) Equivalent main piping length (m)

PUHY-RP600YSJM-B PUHY-RP750YSJM-B
1 1
Pipe diameter correction factor

Pipe diameter correction factor

0.90 0.90

34.93
28.58

0.80 0.80

0.70 0.70

0.60 0.60
0 20 40 60 80 100 0 20 40 60 80 100
Equivalent main piping length (m) Equivalent main piping length (m)

OUTDOOR UNITS 55
8. UNIT SELECTION

PUHY-RP800YSJM-B
1
Pipe diameter correction factor

0.90

34.93

0.80

0.70

0.60
0 20 40 60 80 100
Equivalent main piping length (m)

OUTDOOR UNITS 56
8. UNIT SELECTION

8-3-2. Correction factors for the indoor units and branch pipe diameter
P50 P250
1 1
Pipe diameter correction factor

Pipe diameter correction factor


25.4

12.7 22.2

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Branch piping length (m) Branch piping length (m)

P100, P125, P140


1
Pipe diameter correction factor

15.88

0.90

0.80
0 10 20 30 40
Branch piping length (m)

P200
1
Pipe diameter correction factor

22.2

19.05

0.90

0.80
0 10 20 30 40
Branch piping length (m)

OUTDOOR UNITS 57
8. UNIT SELECTION

8-3-3. Correction factors for the downstream indoor units and the pipes at the downstream of
the branch pipe
P81~P40 P331~P400
1 1
Pipe diameter correction factor

Pipe diameter correction factor


15.88
28.58

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Equivalent main piping length (m) Equivalent main piping length (m)

P161~P200 P401~P630
1 1
Pipe diameter correction factor

Pipe diameter correction factor


22.2
28.58
19.05

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Equivalent main piping length (m) Equivalent main piping length (m)

P201~P300 P631~P650
1 1
Pipe diameter correction factor

Pipe diameter correction factor

34.93
22.2
28.58

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Equivalent main piping length (m) Equivalent main piping length (m)

OUTDOOR UNITS 58
8. UNIT SELECTION

P651~P800
1
Pipe diameter correction factor

34.93

0.90

0.80
0 10 20 30 40
Equivalent main piping length (m)

OUTDOOR UNITS 59
OUTDOOR UNITS 60
R2 SERIES

OUTDOOR UNITS
I.R2 SERIES

1. SPECIFICATIONS........................................................................................................................................... 62
2. EXTERNAL DIMENSIONS .............................................................................................................................. 64
3. CENTER OF GRAVITY ................................................................................................................................... 66
4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ 67
5. SOUND LEVELS ............................................................................................................................................. 68
6. CAPACITY TABLES ........................................................................................................................................ 69
6-1. Correction by temperature ....................................................................................................................... 69
6-2. Correction by total indoor......................................................................................................................... 73
6-3. Correction by refrigerant piping length..................................................................................................... 74
6-4. Correction by port counts of the BC controller ......................................................................................... 76
6-5. Correction at frost and defrost ................................................................................................................. 76
6-6. Operation temperature range .................................................................................................................. 77
7. UNIT SELECTION ........................................................................................................................................... 78
7-1. Indoor and outdoor unit selection ............................................................................................................ 78
7-2. Calculation samples................................................................................................................................. 80
7-3. Pipe diameter correction factor ................................................................................................................ 83

OUTDOOR UNITS 61
1. SPECIFICATIONS
1. SPECIFICATIONS
I.R2 SERIES

Model PURY-RP200YJM-B(-BS) PURY-RP250YJM-B(-BS)


Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 22.4 28.0
(Nominal) *1 kcal / h 19,300 24,100
*1 BTU / h 76,400 95,500
Power input kW 4.95 6.82
Current input A 8.3-7.9-7.6 11.5-10.9-10.5
COP kW / kW 4.52 4.10
Temp. range of Indoor W.B. 15.0~24.0C(59~75F) 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F) -5.0~43.0C(23~109F)
Heating capacity *2 kW 25.0 31.5
(Nominal) *2 kcal / h 21,500 27,100
*2 BTU / h 85,300 107,500
Power input kW 5.50 7.22
Current input A 9.2-8.8-8.5 12.1-11.5-11.1
COP kW / kW 4.54 4.36
Temp. range of Indoor D.B. 15.0~27.0C(59~81F) 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F) -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~150 % of outdoor unit capacity 50~150 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~20 P15~P250 / 1~25
Sound pressure level (measured in anechoic room) dB <A> 56 57
Refrigerant High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed
piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 225 225
L/s 3,750 3,750
cfm 7,945 7,945
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 5.4 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension HxWxD mm 1,710(1,650 without legs) x 1,220 x 760 1,710(1,650 without legs) x 1,220 x 760
in. 67-3/8(65 without legs) x 48-1/16 x 29-15/16 67-3/8(65 without legs) x 48-1/16 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.6MPa High pressure sensor, High pressure switch at 4.15,3.6MPa
Protection devices High pressure protection
(601,522 psi) (601,522 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Discharge thermo protection, Over-current protection Discharge thermo protection, Over-current protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 11.8kg (27lbs) R410A x 11.8kg (27lbs)
Control Indoor LEV and BC controller Indoor LEV and BC controller
Net weight kg (lbs) 275(607) 290(640)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) - -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G728 KD94G728
Wiring KE94C491 KE94C491
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts Joint: CMY-R160-J1 Joint: CMY-R160-J1
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1 BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1 Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 62
1. SPECIFICATIONS
Model PURY-RP300YJM-B(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 33.5
(Nominal) *1 kcal / h 28,800
*1 BTU / h 114,300
Power input kW 8.35
Current input A 14.0-13.3-12.9
COP kW / kW 4.01
Temp. range of Indoor W.B. 15.0~24.0C(59~75F)
cooling Outdoor D.B. -5.0~43.0C(23~109F)
Heating capacity *2 kW 37.5
(Nominal) *2 kcal / h 32,300
*2 BTU / h 128,000
Power input kW 8.70
Current input A 14.6-13.9-13.4
COP kW / kW 4.31
Temp. range of Indoor D.B. 15.0~27.0C(59~81F)
heating Outdoor W.B. -20.0~15.5C(-4~60F)
Indoor unit Total capacity 50~150 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~30
Sound pressure level (measured in anechoic room) dB <A> 59
Refrigerant High pressure mm (in.) 19.05(3/4) Brazed
piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3 / min 225
L/s 3,750
cfm 7,945
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 7.8
Case heater kW 0.045(240 V)
Lubricant MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type)
<MUNSELL 5Y 8/1>
External dimension HxWxD mm 1,710(1,650 without legs) x 1,220 x 760
in. 67-3/8(65 without legs) x 48-1/16 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.6MPa
Protection devices High pressure protection
(601,522 psi)
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection
Compressor Discharge thermo protection, Over-current protection
Fan motor Thermal switch
Refrigerant Type x original charge R410A x 11.8kg (27lbs)
Control Indoor LEV and BC controller
Net weight kg (lbs) 290(640)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94G728
Wiring KE94C491
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-R160-J1
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-1) kcal =kW x 860
Indoor: 27CDB/19CWB (81FDB/66FWB), Outdoor: 35CDB (95FDB) BTU/h =kW x 3,412
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) cfm =m3/min x 35.31
Indoor: 20CDB (68FDB), Outdoor: 7CDB/6CWB (45FDB/43FWB) lbs =kg / 0.4536
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
*The specification data is
subject to rounding variation.

OUTDOOR UNITS 63
2. EXTERNAL DIMENSIONS

760
1220 <Accessories>
Connecting pipe
Discharge air Top view <Low pressure> Pipe (ID25.4 ID28.58) 1 pc.

240
Control box Note 1. Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.
2. The detachable leg can be removed at site.
2. EXTERNAL DIMENSIONS

Intake Intake 3. At brazing of pipes, wrap the refrigerant service


PURY-RP200, 250, 300YJM-B(-BS)

Intake air air valve with wet cloth and keep the temperature of
air refrigerant service valve under 120C.

Refrigerant service Service

1650
1710
valve <Low pressure> panel

1410
Refrigerant service
valve <High pressure>

4 7
5 1
NO. Usage Specifications
2

77
Front through hole 14077 Knockout hole

B
Front through hole

OUTDOOR UNITS
217
For pipes (Uses when twinning kit (optional 45 Knockout hole

146
parts) is mounted.)
Bottom through hole

90

54
15094 Knockout hole
60 60 235
Front through hole 65 or 40 Knockout hole
(60)

(60)
55 25 25 55 251 58 Detachable leg For wires Front through hole 52 or 27 Knockout hole
75 (front and back, 2 points) Bottom through hole 65 Knockout hole
760 271 140 Front view Note 2*
For transmission cables Front through hole 34 Knockout hole
Left side view 271 150
301 83 22-1420 Oval hole

145
Connecting pipe specifications 216

84
18

Position dimensions
Connection specifications for
for the refrigerant

131
145
the refrigerant service valve *1
service valve
Model High Low

94
pressure pressure High Low
pressure pressure 6 Refrigerant service
A B
valve <Low pressure>
(760)

3
PURY-RP200YJM-B(-BS) Refrigerant service
valve <High pressure>
724 (721~727)

PURY-RP250YJM-B(-BS) 261 263 19.05 Brazed 28.58 Brazed


(Mounting pitch)

PURY-RP300YJM-B(-BS)

*1. Connect by using the connecting pipes (for bottom piping and front piping)
80 1060 80
18

that are supplied.


(Mounting pitch)
Bottom view
Unit : mm

64
1. Required space around the unit In case of collective installation
When multiple units are installed adjacent to each other, secure enough space to allow
In case of single installation for air circulation and walkway between groups of units as shown in the figures below.
Secure enough space around the unit as shown in the figure below. At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
With a space of at least With a space of at least to the figures that are marked with an asterisk.
300 mm to the wall on 100 mm to the wall on If there is a wall at both the front and the rear of the unit, install up to six units
the back of the unit the back of the unit consecutively in the side direction and provide a space of 1000 mm or more as inlet space/
passage space for each six units.

100 min.*
300 min.*
Wall <H> <To be left open>

100 min.*
Wall <H>

300 min.*
Front
Front
Front

Front
Front
Wall <H>

Wall <H>

450 min.*
Front Front

450 min.*
<To be left open>
<To be left open>

<To be left open>


<To be left open>
15 min.* 15 min.* 50 min.* 50 min.* Wall <H> 30 min.
Wall <H> 100 min.
2. EXTERNAL DIMENSIONS

450 min.* 450 min. 450 min. 100 min.*

450 min.*

450 min.*
<Top view> <Top view>
PURY-RP200, 250, 300YJM-B(-BS)

<Unit: mm> <To be left open>

When the height of the walls on the front, back or on the sides <H>
exceeds the wall height limit as defined below, add the height Wall <H> 300 min.*
that exceeds the height limit <h> to the figures that are marked Wall <H>
300 min.*

with an asterisk.

15 min.*
Wall <H>

h
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from
the unit bottom

H
Front
Front
Front
Side: Up to the unit height Front

h
Front
900 min.
900 min.

Front

Unit height

OUTDOOR UNITS
500
<To be left open>
<To be left open>
<To be left open>

450 min. 450 min.

<Side view>
Wall <H> <To be left open>
1000 min.*
300 min.*

Corner of the
2. Foundation work installation leg <Unit: mm>
30 mm max.

Take into consideration the surface strength, water drainage route,


piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
M10 anchor bolt
Build the foundation in such way that the corner of the installation leg is <field supply required> Detachable leg
securely supported as shown in the right figure. (Fig.A, B)
When using a rubber isolating cushion, please ensure it is large enough Fig.A (without detachable legs) Fixing plate
<field supply required> Fixing plate
to cover the entire width of each of the unit's legs. <field supply required>
The protrusion length of the anchor bolt must not exceed 30 mm. (Fig.A, B)
Use four fixing plates as shown in the right figure <field supply required> Fig.C (without detachable legs) Fig.D (with detachable legs)
Corner of the
when using post-installed anchor bolts. (Fig.C, D) installation leg
30 mm max.

To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
Detachable leg
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked M10 anchor bolt
<field supply required>
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
Fig.B (with detachable legs)
Unit : mm

65
3. CENTER OF GRAVITY
3. CENTER OF GRAVITY

PURY-RP200, RP250, RP300YJM-B(-BS)

1220 760

Unit: mm
Model X Y Z
PURY-RP200YJM-B(-BS) 445 342 642
1470

PURY-RP250, 300YJM-B(-BS) 443 333 633


Z

X Y
60

1060 80 724

OUTDOOR UNITS 66
P 63H1 P 63H2

1 2 1 3
4. ELECTRICAL WIRING DIAGRAMS

21 1 3 12
FAN Board CN18V CN4 CN5 CNDC
blue red 4 1 3 12
CN21 3 pink 1 3 12 21 12
F01 blue 2
DC700V CNT01 CN801 CNT02 CN332 CN4
4A T 1 yellow blue
LED3: CPU in CPU power
4 operation 6 supply circuit 7
C631 5
C630 R630 IPM 5
1 CN22 4 5 CN2
Fan motor
CNVDC red 3 2
(Heat exchanger) 2 72C 2 CN72 ZNR01 1
R631 1 6 1 red
U 2 U
7 Power failure
M V 1
3~ 4 CNAC2 detection circuit
1 LED1: Normal black
W CNINV operation
LED2: Error

C100 2 Control Board LED1


CN502 X02 6
SV1a 5
R1 R5 1
*4 CNLVD 4 M
DCL 3 blue 3
black SLEV
CN503 2
red 1 2 CH11 X03 SWU2 SWU1 OFF ON OFF ON OFF ON OFF ON OFF ON 1
1 blue 1 1 1 1 1
3 72C 4 10's 1's
3 digit digit
red black CN504
21 3 1 21S4a X04
1 green
SC-P1 CN6 CN5V CN4 2
6 SC-P2 1 Unit address 10 10 10 10 10
CN5 yellow 6
5 CN4 red 1 3 5 setting SW5 SW4 SW3 SW2 SW1
1 3 blue D1 LED1: Normal operation (lit) 3
CN2 3 R5 R4 *5 SV5b CN506
/ Error (blink) 3 LED1 1
CN1 P FT-P Function CNTYP2
1 + 7 SV8 X05 Display black
R6 1
4 5 setting
C11 C1 setting
PURY-RP200, 250, 300YJM-B(-BS)

DSA N FT-N CN2 6 X06


1
Z5 2 5 12V CN51 Z25
Z4 RSH1 1 1 CNTYP5 3
F1,F2,F3 C30 C31 SV4a CN507
U Noise + U - + + 3 red *3 green 1
AC250V 3
6.3A T F3 DB1 C32 C33 3 X07 Z24
Filter + + IPM SV4b 1 4 Compressor ON/OFF output CNTYP4 2
C34 C35 1 5 green 1
F2 + +
C36 C37 CNTYP 6 X08 Error detection output
+ + THHS 4
Z1 Z2 Z3 F1 C10 F4 black 5 TH6
R30 R31 SC-V CN213 3
U U U C3 C4 C5 C6 AC250V CN508 red 2
6.3A T SV9 3 black 1 TH7
C9 R32 R33
C2 C8 R34 R35 SV2 X09 2
SC-L1 SC-U SC-W 1 CN212 1 TH3
4. ELECTRICAL WIRING DIAGRAMS

C7 red red
SC-L2 6 X10 LED3: Lit when powered
C1 2
white white 5 CN990 1 TH5
R3 SV4c CN509
black black 3 blue 3 1
CN992 2 2 63HS2
R2 SV4d X11 yellow 1 3
SC-L3 1
1 CT3 3 1
R1 X12 CN202 2 2 63LS
6
3 CT12 CT22 5
red 1 3
L1 L2 L3 N CN3 CN510
LED2: CPU in operation 3 1
SV5c TB7 Power 63HS1
green 3 yellow CN201 2 2
CN1A 3 1 4 1 CN1B selecting 1 3
INV Board red white black SV6 X13
TB21 TB22 TB23 TB24 1 connector
X14

OUTDOOR UNITS
CN40
F01
L AC250V 1 4 ON
3.15A T blue red yellow red 1 TH4
CN211 2
CN3N CN3S CN3D CN102 CN41 CNS2 CNIT
CNAC 2 1 321 321 321 1234 1 4 12 12345
red OFF

TB1 *3
L1 L2 L3 N

red white black


V
Power Source CN04
U W 1 3 red 4321 21 54321
3N~
MS CN102 CNS2 CNIT
3~ yellow red
50/60Hz
380/400/415V Motor LED1: Power supply to
L1 L2 L3 N M-NET power Indoor/Outdoor transmission line
(Compressor) *1. Single-dotted lines indicate wiring supply circuit
TB3 TB7
not supplied with the unit. M1 M2 M1 M2 S
<Symbol explanation> TP1 TP2
*2. Dot-dash lines indicate the control
Symbol Explanation Symbol Explanation box boundaries. M-NET Board
21S4a 4-way valve (Cooling/Heating switching) SV5c Solenoid Heat exchanger low pressure bypass
High pressure protection for the SV6 valve Middle pressure control
*3. Refer to the Data book for connecting
63H1 Pressure
switch outdoor unit SV8 Refrigerant charging port for input/output signal connectors.
63H2 Pressure protection for pre- auto-charge *4. Faston terminals have a locking
existing pipes SV9 For opening/closing the bypass
63HS1 Discharge pressure circuit
function. Make sure the terminals Central control
Pressure Indoor/Outdoor
63HS2 sensor Middle pressure TB1 Terminal Power supply are securely locked in place after transmission transmission
cable cable
63LS Low pressure TB3 block Indoor/Outdoor transmission insertion. Press the tab on the
72C Magnetic relay (inverter main circuit) cable
CT12, 22, 3 Current sensor (AC) TB7 Central control transmission
terminals to remove them.
CH11 Crankcase heater (for heating the compressor) cable *5. Control box houses high-voltage parts.
DCL DC reactor TH3 Thermistor Liquid pipe temperature Before inspecting the inside of the
SLEV Oil flow control TH4 Discharge pipe temperature
Solenoid For opening/closing the bypass TH5 ACC inlet pipe temperature control box, turn off the power, keep
SV1a
valve circuit under the O/S TH6 Heat exchanger inlet pipe the unit off for at least 10 minutes,
SV2 Discharge suction bypass temperature and confirm that the voltage between
SV4a, b, c, d Heat exchanger capacity control TH7 OA temperature
SV5b For opening/closing the bypass THHS IPM temperature FT-P and FT-N on INV Board has dropped
circuit Z24, 25 Function setting connector to DC20V or less.

67
5. SOUND LEVELS
5. SOUND LEVELS

Sound level of PURY-RP300YJM-B(-BS)


Measurement condition
90
PURY-RP200, 250, 300YJM-B(-BS) Stand 50/60Hz

80 Low 50/60Hz

70

Octave band sound level (dB)


NC-70

60
1m NC-60

50
NC-50

40
NC-40
Measurement
30
location NC-30
1m

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 65.0 63.5 61.0 56.0 53.0 48.5 45.0 42.5 59.0
Low noise mode 50/60Hz 61.0 59.5 49.0 44.5 41.5 38.5 39.5 37.5 50.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PURY-RP200YJM-B(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz

70
Octave band sound level (dB)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 62.5 61.0 58.5 53.0 50.0 45.5 39.0 36.0 56.0
Low noise mode 50/60Hz 56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PURY-RP250YJM-B(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz

70
Octave band sound level (dB)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 59.0 62.0 60.0 54.0 50.5 46.0 41.0 35.0 57.0
Low noise mode 50/60Hz 58.0 53.5 44.0 39.0 36.5 32.5 31.0 24.5 44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

OUTDOOR UNITS 68
6. CAPACITY TABLES
6-1. Correction by temperature
6. CAPACITY TABLES

CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values
and the ratios below, the capacity can be found for various temperatures.

PURY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 22.4 28.0
Cooling 1.3
Capacity BTU/h 76,400 95,500
Input kW 4.95 6.82

Ratio of cooling capacity


1.2
24CWB
75FWB
PURY- RP300YJM-B 1.1
22CWB
Nominal kW 33.5 72FWB
Cooling 1.0 20CWB
Capacity BTU/h 114,300 68FWB

Input kW 8.35 0.9 18CWB


64FWB
16CWB
0.8 61FWB
15CWB
0.7 59FWB

0.6

24CWB
75FWB
1.2
22CWB
72FWB
1.1 20CWB
68FWB
Ratio of power input

1.0 18CWB
64FWB
16CWB
0.9 61FWB
15CWB
0.8 59FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PURY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 25.0 31.5
Heating 1.3
Capacity BTU/h 85,300 107,500
Input kW 5.50 7.22 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PURY- RP300YJM-B 20CDB
1.0
Nominal kW 37.5 68FDB
Heating
Capacity BTU/h 128,000 0.9
Input kW 8.70 0.8
25CDB
77FDB
0.7
27CDB
80FDB
0.6

0.5

0.4

1.4

1.3

1.2
Ratio of power input

1.1

1.0
15CDB
0.9 59FDB

0.8

0.7 20CDB
68FDB

0.6
25CDB
77FDB
0.5
27CDB
80FDB
0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 69
6. CAPACITY TABLES
Correction by temperature (COP Priority Mode)
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity val-
ues and the ratios below, the capacity can be found for various temperatures.
To select high heating performance mode, DipSW 3-7 must be set to OFF.

PURY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 22.4 28.0
Cooling 1.3
Capacity BTU/h 76,400 95,500
Input kW 4.95 6.82

Ratio of cooling capacity


1.2
24CWB
75FWB
PURY- RP300YJM-B 1.1
22CWB
Nominal kW 33.5 72FWB
Cooling 1.0 20CWB
Capacity BTU/h 114,300 68FWB

Input kW 8.35 0.9 18CWB


64FWB

(There is no difference in cooling performance 0.8


16CWB
61FWB
between Standard Mode and COP Priority Mode.)
15CWB
0.7 59FWB

0.6

24CWB
75FWB
1.2
22CWB
72FWB
1.1 20CWB
68FWB
Ratio of power input

1.0 18CWB
64FWB
16CWB
0.9 61FWB
15CWB
0.8 59FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PURY- RP200YJM-B RP250YJM-B 1.4 Indoor Temperature


Nominal kW 25.0 31.5
Heating 1.3
Capacity BTU/h 85,300 107,500
Input kW 5.50 7.22 1.2
Ratio of heating capacity

15CDB
59FDB
1.1
PURY- RP300YJM-B
20CDB
Nominal kW 37.5 1.0 68FDB
Heating
Capacity BTU/h 128,000 0.9
Input kW 8.70
0.8
25CDB
77FDB
0.7
27CDB
80FDB
0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0
15CDB
0.9 59FDB

0.8
20CDB
0.7 68FDB

0.6 25CDB
77FDB
0.5
27CDB
80FDB
0.4
-20 -15 -10 -5 0 5 10 15 CWB
-4 5 14 23 32 41 50 59 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 70
6. CAPACITY TABLES
Correction by temperature (Connection with PWFY-P100/200VM-E-AU (HEX unit))

PURY- RP200YJM-B RP250YJM-B 1.5 HEX unit inlet-water temperature


Nominal kW 22.4 28.0
Cooling 1.4
Capacity BTU/h 76,400 95,500
Input kW 4.95 6.82 1.3

Ratio of cooling capacity


1.2
PURY- RP300YJM-B
Nominal kW 33.5 1.1
Cooling
Capacity BTU/h 114,300 35C
1.0 95F
Input kW 8.35 30C
86F
0.9
25C
77F
0.8
20C
68F
0.7 15C
59F
0.6 10C
50F
0.5

1.2 35C
95F
1.1 30C
Ratio of power input

86F

1.0 25C
77F
20C
0.9 68F
15C
0.8 59F
10C
0.7 50F

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 CDB
23 32 41 50 59 68 77 86 95 104 113 FDB
Ratio of cooling capacity and power input Outdoor Temperature

PURY- RP200YJM-B RP250YJM-B 1.4 HEX unit inlet-water temperature


Nominal kW 25.0 31.5
Heating 1.3
Capacity BTU/h 85,300 107,500
Input kW 5.50 7.22 1.2
Ratio of heating capacity

10C
50F
1.1 20C
PURY- RP300YJM-B 68F

Nominal kW 37.5 1.0 30C


Heating 86F
Capacity BTU/h 128,000 0.9 35C
95F
Input kW 8.70
0.8 40C
104F
0.7

0.6

0.5

0.4

1.2

1.1
Ratio of power input

1.0
40C
104F
0.9
35C
95F
0.8
30C
86F
0.7
20C
68F
0.6
10C
50F
0.5

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of heating capacity and power input Outdoor Temperature

OUTDOOR UNITS 71
6. CAPACITY TABLES
Correction by temperature (Connection with PWFY-P100VM-E-BU (Booster unit))

PURY- RP200YJM-B RP250YJM-B 1.4 Booster unit inlet-water temperature


Nominal kW 25.0 31.5
Heating 1.3 40C
Capacity BTU/h 85,300 107,500 104F

1.2 50C
Input kW 5.50 7.22

Ratio of heating capacity


122F
60C
1.1 140F
PURY- RP300YJM-B
65C
Nominal kW 37.5 1.0 149F
Heating
Capacity BTU/h 128,000 0.9 30C
86F
Input kW 8.70
0.8 20C
68F
0.7

0.6
10C
50F
0.5

0.4

1.2

1.1
Ratio of power input

40C
1.0 104F
50C
122F
0.9
30C
86F
0.8
60C
140F
0.7 65C
149F
0.6 20C
68F
0.5 10C
50F
0.4
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of heating capacity and power input Outdoor Temperature

1.1 Booster unit inlet-water temperature


65C
1.0 149F
60C
0.9
Ratio of booster unit input

140F

0.8 50C
122F

0.7
40C
0.6 104F

0.5 30C
86F
0.4
20C
68F
0.3
10C
50F
0.2
-20 -15 -10 -5 0 5 10 15 20 25 30 CWB
-4 5 14 23 32 41 50 59 68 77 86 FWB
Ratio of booster power input Outdoor Temperature

OUTDOOR UNITS 72
6. CAPACITY TABLES
6-2. Correction by total indoor
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following tables, the
maximum capacity can be observed so as to ensure the system having enough capacity to meet the conditions.

PURY-RP200, 250YJM-B(-BS)

35.0

30.0
Capacity(kW)

25.0

20.0

15.0

10.0
10.0

8.0
Input(kW)

6.0

4.0
RP200 RP250
Cooling Cooling
Heating Heating
2.0
100 200 300 400
Total capacity of indoor units

PURY-RP300YJM-B(-BS)

50.0

40.0
Capacity(kW)

30.0

20.0

10.0

12.0

10.0

8.0
Input(kW)

6.0

4.0
RP300
Cooling
Heating
2.0
100 200 300 400 500
Total capacity of indoor units

OUTDOOR UNITS 73
6. CAPACITY TABLES
6-3. Correction by refrigerant piping length
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
6-3-1 and 6-3-2, the capacity can be observed. 6-3-3 shows how to obtain the equivalent length of piping.

6-3-1. Cooling capacity correction


PURY-RP200YJM-B(-BS)
Total capacity of indoor unit
1 100
Cooling capacity correction factor

0.95 150

0.90
200
0.85 300
0.80
0.75

0.70

0.65
0 20 40 60 80 100 120
Piping equivalent length (m)

PURY-RP250YJM-B(-BS)
Total capacity of indoor unit
1 125
Cooling capacity correction factor

0.95 188

0.90
250
0.85 375
0.80
0.75

0.70

0.65
0 20 40 60 80 100 120
Piping equivalent length (m)

PURY-RP300YJM-B(-BS)
Total capacity of indoor unit
1 150
Cooling capacity correction factor

0.95 225

0.90
300
0.85 450
0.80
0.75

0.70

0.65
0 20 40 60 80 100 120
Piping equivalent length (m)

OUTDOOR UNITS 74
6. CAPACITY TABLES

6-3-2. Heating capacity correction


PURY-RP200YJM-B(-BS)

1.00
Heating capacity correction factor

0.95

0.90

0.85
0 20 40 60 80 100 120
Piping equivalent length (m)

PURY-RP250YJM-B(-BS)

1.00
Heating capacity correction factor

0.95

0.90

0.85
0 20 40 60 80 100 120
Piping equivalent length (m)

PURY-RP300YJM-B(-BS)

1.00
Heating capacity correction factor

0.95

0.90

0.85
0 20 40 60 80 100 120
Piping equivalent length (m)

OUTDOOR UNITS 75
6. CAPACITY TABLES

6-3-3. How to obtain the equivalent piping length


1. PURY-RP200YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.35 x number of bent on the piping) [m]
2. PURY-RP250, 300YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.42 x number of bent on the piping) [m]

6-4. Correction by port counts of the BC controller


Indoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller.
Indoor unit sizes from P100 to P140 should normally be connected to 2 ports on the BC controller (set BC controller DIP-SW 4-6
to its ON position).
In cases whereby indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller (set BC controller DIP-SW
4-6 to its OFF position), the cooling capacity of the indoor unit should be multiplied by a correction factor of 0.97.

6-5. Correction at frost and defrost


Due to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be
calculated by multiplying the correction factor shown in the table below.

Table of correction factor at frost and defrost


Outdoor inlet air temp. C 6 4 2 1 0 -2 -4 -6 -8 -10 -20
Outdoor inlet air temp. F 43 39 36 34 32 28 25 21 18 14 -4
PURY-RP200YJM-B(-BS) 1.00 0.95 0.84 0.83 0.83 0.87 0.90 0.95 0.95 0.95 0.95
PURY-RP250YJM-B(-BS) 1.00 0.95 0.84 0.83 0.83 0.87 0.90 0.95 0.95 0.95 0.95
PURY-RP300YJM-B(-BS) 1.00 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95

OUTDOOR UNITS 76
6. CAPACITY TABLES
6-6. Operation temperature range

86 30

77 25
Indoor temperature

68 20

59 15

50 10

41 5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Outdoor temperature

86 30

77 25
Indoor temperature

68 20

59 15

50 10

41 5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Outdoor temperature

Combination of cooling/heating operation (Cooling main or Heating main)

Indoor temperature
Outdoor temperature
Cooling Heating
-5 to 21 CDB (23 to 70 FDB) 15 to 27 CDB (59 to 81 FDB)
-6 to 15.5 CWB (21 to 60 FWB) 15 to 24 CWB (59 to 75 FWB)

OUTDOOR UNITS 77
7. UNIT SELECTION
7-1. Indoor and outdoor unit selection
7. UNIT SELECTION

(1) Selecting indoor units


1) Calculate the thermal road of each room.

2) Based on the thermal load corrected for indoor unit return air temperature, select appropriate indoor unit models.
Refer to the correction factor diagram for the outdoor unit whose capacity is the closest to the total thermal load of the
system (Qi). Refer to CAPACITY TABLES (Indoor unit) and 6. CAPACITY TABLES.

3) Calculate the total capacity of the indoor units in the system (N).

(2) Selecting outdoor units


1) Based on the total capacity of the indoor units (N), tentatively select the capacity of the outdoor unit (X).
The total capacity of the indoor units to be connected to a given outdoor unit (N) should not exceed the maximum
connectable capacity of the outdoor unit.

2) The tentatively selected standard capacity of the outdoor unit (X) will be defined as Qs.
* If the total capacity of the indoor units that are connected to a given outdoor unit exceeds 100% of the outdoor unit
capacity (X), refer to the outdoor unit partial load capacity table, find the capacity that corresponds to the total capacity
N, and use it as the standard outdoor unit capacity (Qs).

3) Obtain the maximum outdoor unit capacity (Qm) by multiplying Qs (standard outdoor unit capacity) by the following
correction factors: piping length, outside air temperature, and defrost (heating).
Find the piping length correction factor from the diagram that corresponds to the total indoor unit capacity (N).

Qm = Qs x Piping length correction factor x Outside air temperature correction factor


x Defrost correction factor (heating only) x Pipe diameter correction factor

Outside air temperature correction factor Refer to 6-1.


Piping length correction factor Refer to 6-3.
Defrost correction factor (heating only) Refer to 6-5.
Pipe diameter correction factor (applicable only if non-standard size pipes are connected) Refer to 7-3.

4) Make sure the maximum outdoor unit capacity Qm is equal to or greater than the total thermal load Qi.
If Qm is smaller than Qi, reconsider the outdoor unit capacity (X) so that Qm Qi will hold true.

5) After selecting indoor and outdoor units, calculate the apportioned indoor unit capacity, and make sure that the formula
"Thermal load Indoor unit capacity" will hold true for each room.
If the thermal load exceeds the indoor unit capacity in one or more rooms, increase the indoor unit size as long as doing so
will not exceed the maximum connectable capacity of the outdoor unit. Then, start over from step 1) above. If the
maximum connectable capacity is exceeded by increasing the indoor unit capacity, increase the outdoor capacity as well,
then start over from step 1) above.

Calculate the indoor/outdoor unit capacities and check for unit compatibility by
considering both the heating and the cooling loads. If the formula Qm Qi does not
hold true for either cooling or heating, reconsider the outdoor unit capacity (X).

OUTDOOR UNITS 78
7. UNIT SELECTION
(3) Obtaining the unit capacity
A. If the apportioned indoor unit capacity obtained in step 5) on the previous page is equal to or greater than the rated
indoor unit capacity, the following formula will be used to calculate the indoor unit capacity: "Rated capacity x return air
temperature correction factor x piping length correction factor (x pipe diameter correction factor)".

B. If the apportioned indoor unit capacity obtained in step 5) on the previous page is smaller than the rated indoor unit
capacity, the following formula will be used to calculate the indoor unit capacity: "Apportioned indoor unit capacity x
return air temperature correction factor."

* The standard outside air temperatures used to obtain the return air temperature correction factor is 35CDB for cooling
and 6CWB for heating.
* If non-standard size pipes are connected, use the pipe diameter correction factors for the main pipes, merge pipes, and
branch pipes.

(4) Notes
When deciding the outside air temperature to calculate unit capacity requirements, take into consideration the possible
temperature rise around the outdoor unit due to short-cycling. (When installing outdoor units collectively on the rooftop or if
outdoor units are surrounded by walls or other objects, it is recommended to set the outside temperature as 43C for
calculation.)

If you want to take sensible heat load into consideration, refer to the relevant catalogs for information on sensible heat
factor when selecting indoor units.

OUTDOOR UNITS 79
7. UNIT SELECTION
7-2. Calculation samples
(1) To connect indoor units using the standard pipes
Design conditions
<Cooling> Indoor design dry-bulb temperature: 26C/Indoor design wet-bulb temperature: 18.5C
Outdoor design dry-bulb temperature: 36C
Cooling load: 13.5 kW for each of the two rooms
<Heating> Indoor design dry-bulb temperature: 21C
Outdoor design wet-bulb temperature: 5C
Heating load: 14.5 kW for each of the two rooms
<Miscellaneous information>
Main piping: 28.58 x 45 m, Branch piping: 19.05 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
A. Calculating the cooling load
a) The thermal load (13.5 kW/room), indoor unit return air temperature correction factor, and piping length correction
factor are used to calculate the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively
selected. (Because the total thermal load is 27 kW, the air temperature correction diagram for the 250 model outdoor
unit will be used.)
b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected.
Based on the above, the standard capacity Qs will be 28 kW.
c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:
Outside air temperature 36CDB Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19C)
Piping length: 50 m Capacity correction factor: 0.97
If the standard capacity Qs is corrected for indoor/outside air temperatures and piping length, the maximum outdoor unit
capacity Qm can be obtained as follows: Qm = 28 x 0.99 x 0.97 = 26.8 kW.
The result shows that the thermal load Qi (27 kW) exceeds the unit capacity Qm, so a larger 300 model outdoor unit
needs to be selected.
d) For the 300 model units, the outside air temperature correction factor is 0.99. The piping length correction factor that
can be obtained from the diagram for the system whose total indoor unit capacity is 250 would be 0.96.
Because the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained
using the following formula: Qm = 33.5 x 0.99 x 0.96 = 31.8 kW. The result 31.8 kW is greater than the Qi (27 kW), so
the maximum capacity Qm meets the capacity requirement.
e) Compare the thermal loads on the indoor units, using the maximum outdoor unit capacity apportioned to each indoor
unit and taking the indoor unit return air temperature correction factors into consideration. The correction factor for the
return air temperature at 18.5CWB is 0.99 (at the standard outside dry-bulb temperature of 35C), and this value can
be plugged into the following formula to obtain the capacity.
32.1 kW x 125/250 x 0.99 = 15.8 kW
The result shows that the capacity (15.8 kW) is greater than the thermal load (13.5 kW), and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
B. Calculating the heating load
Next, you will calculate the heating load and unit capacity requirements, using the models that were selected in the
previous section.
a) The standard capacity (Qs) of the tentatively selected 300 model outdoor unit is 37.5 kW.
b) Use this value in the following formula to obtain the maximum outdoor unit capacity Qm as shown below:
Qm = 37.5 x 1.00 x 0.965 x 0.975 = 35.2 kW, (where the outside air temperature is 5CWB, capacity correction factor
is 1.00 (at the standard indoor dry-bulb temperature of 20C), defrost correction factor is 0.965, piping length is 50 m,
and capacity correction factor is 0.975).
The result shows that the Maximum outdoor unit capacity Qm (35.2 kW) exceeds the heating load Qi (29 kW).
c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 35.2 x 125/250 x 0.96 = 16.8 kW (where the indoor unit return air temperature correction factor at 21CDB is
0.96) (standard outside temperature at 6C). The result shows that the unit capacity (16.8 kW) exceeds the thermal
load for each room (14.5 kW).
Based on the above calculation, the following indoor and outdoor units can be selected.
Indoor units: 125 model x 2 units
Outdoor unit: RP300 model
C. Calculating the capacity requirement
a) The cooling capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 15.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (14.0 kW). The actual cooling capacity under the specified conditions is
calculated as follows: 14.0 x 0.99 x 0.97 = 13.4 kW (where the return air temperature correction factor at the standard
outside temperature of 35CDB is 0.99 and the piping length correction factor is 0.97).
b) The heating capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 16.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (16.0 kW). The actual heating capacity under the specified conditions is
calculated as follows: 16.0 x 0.95 x 0.975 = 14.8 kW (where the return air temperature correction factor at the standard
outside temperature of 6CWB is 0.95 and the piping length correction factor is 0.975).

OUTDOOR UNITS 80
7. UNIT SELECTION
(2) To connect indoor units using non-standard pipes
Design conditions
<Cooling> Indoor design dry-bulb temperature: 26C/Indoor design wet-bulb temperature: 18.5C
Outdoor design dry-bulb temperature: 36C
Cooling load: 13.5 kW for each of the two rooms
<Heating> Indoor design dry-bulb temperature: 21C
Outdoor design wet-bulb temperature: 5C
Heating load: 14.5 kW for each of the two rooms
<Miscellaneous information>
Main piping: 25.4 x 45 m, Branch piping: 15.88 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
A. Calculating the cooling load
a) The thermal load of 13 kW per room and the indoor unit return air temperature correction factor are used to calculate
the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively selected. (Because the total
thermal load is 26 kW, the air temperature correction diagram for the 250 model outdoor unit will be used.)

b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected.
Based on the above, the standard capacity Qs will be 28 kW.
c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:

Outside air temperature 36CDB Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19C)
Piping length: 50 m Capacity correction factor: 0.97
Main piping: 25.4 x 45 m Pipe diameter correction factor: 0.98
The standard capacity Qs is corrected for indoor/outside air temperatures, piping length, and pipe diameter to obtain the
maximum outdoor unit capacity Qm as follows: Qm = 28 x 0.99 x 0.97 x 0.98 = 26.3 kW. Because this value does not
meet the thermal load Qi (27 kW), a larger 300 model outdoor unit needs to be selected.

d) For the 300 model, the outside air temperature correction factor is 0.99, the pipe diameter correction factor for a 45 m
pipe with a diameter of 25.4 is 0.98, and the piping length correction factor is 0.96 (read from the diagram for the unit
whose total indoor unit capacity N is 250).
Where the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained as
follows: Qm = 33.5 x 0.99 x 0.98 x 0.96= 31.2 kW. This value is greater than the thermal load Qi (27 kW), and the
maximum capacity Qm satisfies the capacity requirements.

e) Compare the thermal loads on the indoor unit side, using the maximum outdoor unit capacity apportioned to each
indoor unit and taking the indoor unit return air condition correction factors into consideration. The correction factor for
the return air temperature at 18.5C is 0.99 (at the standard outside dry-bulb temperature of 35C), and the pipe
diameter correction factor for a 5 m pipe with a diameter of 15.88 connected to a 125-model unit is 0.99. These
values can be plugged into the following formula to obtain the capacity.
31.8 kW x 125/250 x 0.99 x 0.99=15.5 kW.
The result shows that the capacity (15.5 kW) is greater than the thermal load of 13.5 kW, and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
B. Calculating the heating load
Next, we will calculate the heating load, using the models that are selected based on the cooling load calculation.
a) The standard capacity Qs of the tentatively selected (during cooling load calculation) 300 model outdoor unit is 37.5
kW.
b) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 300 model outdoor units are as follows:
Outside air temperature 5CWB Capacity correction factor 1.00 (at the standard indoor dry-bulb temperature of 20C)
Defrost correction factor is 0.975
Piping length: 50 m Capacity correction factor: 0.975
Main piping: 25.4 x 45 m Pipe diameter correction factor: 0.98
The standard capacity Qs is corrected for indoor/outside air temperatures and piping length to obtain the maximum
outdoor unit capacity Qm as follows: Qm = 37.5 x 1.00 x 0.975 x 0.975 x 0.98 = 34.9 kW.
The result shows that the Maximum outdoor unit capacity Qm (34.9 kW) exceeds the heating load Qi (29 kW).
c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 34.9 x 125/250 x 0.96 x 0.99 = 16.5 kW (where the correction factor for the indoor unit return air temperature
of 21CDB is 0.96 (standard outside temperature at 6C), and the pipe diameter correction factor for a 5 m branch pipe
with a diameter of 15.88 connected to a 125 models is 0.99. The result shows that the unit capacity 16.5 kW exceeds
the thermal load for each room (14.5 kW).
Based on the above calculation, the following indoor and outdoor units can be selected.
Indoor units: 125 model x 2 units
Outdoor unit: RP300 model

OUTDOOR UNITS 81
7. UNIT SELECTION
<Capacity requirement calculation flow chart>

Obtain the thermal load (Qi).

Correct for the indoor unit return air temperature.

Determine the capacity for each indoor unit.

Calculate the total indoor unit capacity (N).

Select the outdoor unit capacity (X).

Correct the standard outdoor unit capacity (Qs)


for outside air temperature and piping length to
obtain the corrected capacity (Qm).

YES
Select the outdoor unit one rank higher
Thermal load Qi > Corrected capacity Qm
in capacity.

NO

Apportion the corrected outdoor unit capacity (Qm)


to each indoor unit.

Multiply the apportioned capacity by the indoor


unit temperature correction factor, and make sure it
is equal to or greater than the thermal load.

Finish
(calculations to be done for both cooling and heating)

OUTDOOR UNITS 82
7. UNIT SELECTION
7-3. Pipe diameter correction factor
7-3-1. Correction factors for the outdoor units and main pipe diameter
PURY-RP200YJM-B
1
Pipe diameter correction factor

25.4

0.90 22.2

19.05

0.80

0.70

0.60
0 20 40 60 80 100
Equivalent main piping length (m)

PURY-RP250YJM-B
1
Pipe diameter correction factor

25.4

0.90 22.2

0.80

0.70

0.60
0 20 40 60 80 100
Equivalent main piping length (m)

PURY-RP300YJM-B
1
Pipe diameter correction factor

25.4

0.90
22.2

0.80

0.70

0.60
0 20 40 60 80 100
Equivalent main piping length (m)

OUTDOOR UNITS 83
7. UNIT SELECTION

7-3-2. Correction factors for the indoor units and branch pipe diameter
P50 P250
1 1
Pipe diameter correction factor

Pipe diameter correction factor


25.4

12.7 22.2

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Branch piping length (m) Branch piping length (m)

P100, P125, P140


1
Pipe diameter correction factor

15.88

0.90

0.80
0 10 20 30 40
Branch piping length (m)

P200
1
Pipe diameter correction factor

22.2

19.05

0.90

0.80
0 10 20 30 40
Branch piping length (m)

OUTDOOR UNITS 84
7. UNIT SELECTION

7-3-3. Correction factors for the downstream indoor units and the pipes at the downstream of
the branch pipe
P81~P40 P331~P400
1 1
Pipe diameter correction factor

Pipe diameter correction factor


15.88
28.58

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Equivalent main piping length (m) Equivalent main piping length (m)

P161~P200 P401~P630
1 1
Pipe diameter correction factor

Pipe diameter correction factor


22.2
28.58
19.05

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Equivalent main piping length (m) Equivalent main piping length (m)

P201~P300 P631~P650
1 1
Pipe diameter correction factor

Pipe diameter correction factor

34.93
22.2
28.58

0.90 0.90

0.80 0.80
0 10 20 30 40 0 10 20 30 40
Equivalent main piping length (m) Equivalent main piping length (m)

OUTDOOR UNITS 85
7. UNIT SELECTION

P651~P800
1
Pipe diameter correction factor

34.93

0.90

0.80
0 10 20 30 40
Equivalent main piping length (m)

OUTDOOR UNITS 86
CAPACITY TABLES

Capacity Table
I.CAPACITY TABLES

1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)] ................................................................ 89


1-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 89
1-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 93
1-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 97
1-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 101
1-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 105
2. Cooling [Ceiling concealed (Middle static pressure type)] ............................................................................... 109
2-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 109
2-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 111
2-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 113
2-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 115
2-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 117
3. Cooling [Ceiling cassette (1-way flow type)] .................................................................................................... 119
3-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 119
3-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 120
3-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 121
3-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 122
3-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 123
4. Cooling [Ceiling cassette (2-way flow type)] .................................................................................................... 124
4-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 124
4-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 126
4-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 128
4-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 130
4-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 132
5. Cooling [Ceiling cassette (4-way flow type)] .................................................................................................... 134
5-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 134
5-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 136
5-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 138
5-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 140
5-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 142
6. Cooling [Ceiling suspended] ............................................................................................................................ 144
6-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 144
6-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 145
6-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 146
6-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 147
6-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 148
7. Cooling [Wall mounted].................................................................................................................................... 149
7-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 149
7-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 151
7-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 153
7-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 155
7-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 157
8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)].............................................................. 159
8-1. Cooling capacity with PUHY,PURY-RP200-250YJM .............................................................................. 159
8-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 162
8-3. Cooling capacity with PUHY-RP450-650YSJM ....................................................................................... 165
8-4. Cooling capacity with PUHY-RP700-800YSJM ....................................................................................... 168
8-5. Cooling capacity with PUHY-RP850-900YSJM ....................................................................................... 171
9. Heating [All indoor units].................................................................................................................................. 174
9-1. Heating capacity with PUHY,PURY-RP200-250YJM .............................................................................. 174
9-2. Heating capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM ...................................................... 175
9-3. Heating capacity with PUHY-RP450-650YSJM ....................................................................................... 176
9-4. Heating capacity with PUHY-RP700-800YSJM ....................................................................................... 177
9-5. Heating capacity with PUHY-RP850-900YSJM ....................................................................................... 178
9-6. Heating capacity with PUHY,PURY-RP200-250YJM "COP priority mode" ............................................. 179

INDOOR UNITS 87
CAPACITY TABLES
9-7. Heating capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM "COP priority mode" ..................... 180
9-8. Heating capacity with PUHY-RP450-650YSJM "COP priority mode" ...................................................... 181
9-9. Heating capacity with PUHY-RP700-800YSJM "COP priority mode" ...................................................... 182
9-10.Heating capacity with PUHY-RP850-900YSJM "COP priority mode"...................................................... 183
10. Cooling [Ceiling concealed (Fresh air intake)] ................................................................................................. 184
10-1.Cooling capacity....................................................................................................................................... 184
10-2.Outlet air temp. cooled............................................................................................................................. 185
11. Heating [Ceiling concealed (Fresh air intake)] ................................................................................................. 186
11-1.Heating capacity ...................................................................................................................................... 186
11-2.Outlet air temp. heated ............................................................................................................................ 187

INDOOR UNITS 88
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
1-1. Cooling capacity with PUHY,PURY-RP200-250YJM
1. Cooling [Ceiling
I.CAPACITY TABLESconcealed (Silent/Slim/High static pressure type)]

PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.5 5.0 3.5 5.3 3.5 5.7 3.4
22.5 4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.5 5.0 3.5 5.3 3.5 5.7 3.4
25.0 4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.5 5.0 3.5 5.3 3.5 5.6 3.4
27.5 4.3 3.2 4.4 3.3 4.6 3.3 4.8 3.5 4.9 3.5 5.2 3.4 5.5 3.4
40 30.0 4.2 3.2 4.3 3.3 4.6 3.3 4.7 3.5 4.8 3.4 5.1 3.4 5.4 3.3
(4.5) 32.5 4.1 3.2 4.2 3.3 4.5 3.2 4.6 3.4 4.7 3.4 5.0 3.3 5.3 3.3
35.0 4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.4 4.6 3.4 4.9 3.3 5.2 3.3
37.5 4.0 3.1 4.1 3.2 4.3 3.2 4.4 3.4 4.5 3.3 4.8 3.3 5.0 3.2
40.0 3.9 3.1 4.0 3.2 4.2 3.1 4.3 3.3 4.4 3.3 4.7 3.2 4.9 3.2
43.0 3.8 3.0 3.9 3.1 4.1 3.1 4.2 3.3 4.3 3.2 4.5 3.2 4.8 3.1
20.0 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.2 4.1 6.6 4.0 7.1 4.0
22.5 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.2 4.1 6.6 4.0 7.1 4.0
25.0 5.3 3.8 5.5 3.9 5.9 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
27.5 5.3 3.8 5.5 3.9 5.8 3.9 5.9 4.1 6.1 4.0 6.4 4.0 6.8 3.9
50 30.0 5.2 3.8 5.4 3.9 5.7 3.8 5.8 4.0 6.0 4.0 6.3 3.9 6.7 3.9
(5.6) 32.5 5.1 3.7 5.3 3.8 5.6 3.8 5.7 4.0 5.9 3.9 6.2 3.9 6.6 3.8
35.0 5.0 3.7 5.2 3.8 5.5 3.7 5.6 3.9 5.8 3.9 6.1 3.8 6.4 3.7
37.5 4.9 3.6 5.1 3.7 5.4 3.7 5.5 3.9 5.6 3.8 5.9 3.8 6.3 3.7
40.0 4.8 3.6 5.0 3.7 5.3 3.6 5.4 3.8 5.5 3.8 5.8 3.7 6.1 3.6
43.0 4.7 3.5 4.8 3.6 5.1 3.6 5.3 3.8 5.4 3.7 5.6 3.6 6.0 3.6
20.0 6.7 5.0 7.0 5.2 7.5 5.1 7.7 5.4 7.9 5.4 8.4 5.3 9.0 5.3
22.5 6.7 5.0 7.0 5.2 7.5 5.1 7.7 5.4 7.9 5.4 8.4 5.3 9.0 5.3
25.0 6.7 5.0 7.0 5.2 7.5 5.1 7.7 5.4 7.9 5.4 8.3 5.3 8.8 5.2
27.5 6.7 5.0 6.9 5.1 7.3 5.1 7.5 5.4 7.7 5.3 8.1 5.2 8.7 5.2
63 30.0 6.6 4.9 6.8 5.1 7.2 5.0 7.4 5.3 7.6 5.3 8.0 5.2 8.5 5.1
(7.1) 32.5 6.5 4.9 6.7 5.0 7.1 5.0 7.2 5.2 7.4 5.2 7.8 5.1 8.3 5.0
35.0 6.4 4.8 6.5 5.0 6.9 4.9 7.1 5.2 7.3 5.1 7.7 5.1 8.1 5.0
37.5 6.2 4.8 6.4 4.9 6.8 4.8 7.0 5.1 7.2 5.1 7.5 5.0 8.0 4.9
40.0 6.1 4.7 6.3 4.8 6.7 4.8 6.8 5.1 7.0 5.0 7.4 4.9 7.8 4.9
43.0 6.0 4.6 6.1 4.8 6.5 4.7 6.7 5.0 6.9 5.0 7.2 4.9 7.6 4.8
20.0 7.6 5.6 7.9 5.8 8.4 5.7 8.7 6.1 8.9 6.0 9.5 6.0 10.1 5.9
22.5 7.6 5.6 7.9 5.8 8.4 5.7 8.7 6.1 8.9 6.0 9.5 6.0 10.1 5.9
25.0 7.6 5.6 7.9 5.8 8.4 5.7 8.6 6.1 8.9 6.0 9.4 5.9 10.0 5.8
27.5 7.6 5.6 7.8 5.7 8.3 5.7 8.5 6.0 8.7 5.9 9.2 5.8 9.8 5.8
71 30.0 7.4 5.5 7.7 5.7 8.1 5.6 8.3 5.9 8.5 5.9 9.0 5.8 9.6 5.7
(8.0) 32.5 7.3 5.4 7.5 5.6 8.0 5.5 8.2 5.8 8.4 5.8 8.8 5.7 9.4 5.6
35.0 7.2 5.4 7.4 5.5 7.8 5.5 8.0 5.8 8.2 5.7 8.6 5.6 9.2 5.5
37.5 7.0 5.3 7.2 5.5 7.7 5.4 7.9 5.7 8.1 5.7 8.5 5.6 9.0 5.5
40.0 6.9 5.2 7.1 5.4 7.5 5.3 7.7 5.7 7.9 5.6 8.3 5.5 8.8 5.4
43.0 6.7 5.2 6.9 5.3 7.3 5.3 7.5 5.6 7.7 5.5 8.1 5.4 8.5 5.3
20.0 8.6 6.3 8.9 6.5 9.5 6.5 9.7 6.9 10.0 6.8 10.6 6.7 11.4 6.7
22.5 8.6 6.3 8.9 6.5 9.5 6.5 9.7 6.9 10.0 6.8 10.6 6.7 11.4 6.7
25.0 8.6 6.3 8.9 6.5 9.5 6.5 9.7 6.8 10.0 6.8 10.5 6.7 11.2 6.6
27.5 8.5 6.3 8.8 6.5 9.3 6.4 9.5 6.8 9.8 6.7 10.3 6.6 11.0 6.5
80 30.0 8.4 6.2 8.6 6.4 9.1 6.3 9.4 6.7 9.6 6.6 10.1 6.5 10.8 6.4
(9.0) 32.5 8.2 6.2 8.5 6.3 8.9 6.3 9.2 6.6 9.4 6.6 9.9 6.5 10.5 6.4
35.0 8.1 6.1 8.3 6.3 8.8 6.2 9.0 6.5 9.2 6.5 9.7 6.4 10.3 6.3
37.5 7.9 6.0 8.1 6.2 8.6 6.1 8.8 6.5 9.1 6.4 9.5 6.3 10.1 6.2
40.0 7.7 5.9 8.0 6.1 8.4 6.0 8.7 6.4 8.9 6.4 9.3 6.2 9.9 6.1
43.0 7.6 5.8 7.8 6.0 8.2 6.0 8.5 6.3 8.7 6.3 9.1 6.1 9.6 6.0
20.0 10.6 8.5 11.0 8.8 11.8 8.8 12.1 9.3 12.5 9.3 13.2 9.2 14.2 9.1
22.5 10.6 8.5 11.0 8.8 11.8 8.8 12.1 9.3 12.5 9.3 13.2 9.2 14.2 9.1
25.0 10.6 8.5 11.0 8.8 11.8 8.8 12.1 9.3 12.4 9.2 13.1 9.1 13.9 9.0
27.5 10.6 8.5 10.9 8.8 11.6 8.7 11.9 9.2 12.2 9.2 12.9 9.0 13.7 8.9
100 30.0 10.4 8.4 10.7 8.7 11.3 8.6 11.6 9.1 12.0 9.1 12.6 8.9 13.4 8.8
(11.2) 32.5 10.2 8.3 10.5 8.6 11.1 8.5 11.4 9.1 11.7 9.0 12.4 8.8 13.1 8.7
35.0 10.0 8.2 10.3 8.5 10.9 8.4 11.2 9.0 11.5 8.9 12.1 8.7 12.8 8.6
37.5 9.8 8.1 10.1 8.4 10.7 8.3 11.0 8.9 11.3 8.8 11.9 8.7 12.6 8.5
40.0 9.6 8.1 9.9 8.3 10.5 8.2 10.8 8.8 11.1 8.7 11.6 8.6 12.3 8.4
43.0 9.4 7.9 9.7 8.2 10.2 8.1 10.5 8.7 10.8 8.6 11.3 8.5 12.0 8.3
20.0 13.3 9.8 13.8 10.1 14.7 10.1 15.2 10.6 15.6 10.6 16.6 10.4 17.7 10.3
22.5 13.3 9.8 13.8 10.1 14.7 10.1 15.2 10.6 15.6 10.6 16.6 10.4 17.7 10.3
25.0 13.3 9.8 13.8 10.1 14.7 10.1 15.1 10.6 15.5 10.5 16.4 10.4 17.4 10.2
27.5 13.3 9.8 13.6 10.1 14.4 10.0 14.8 10.5 15.2 10.4 16.1 10.3 17.1 10.1
125 30.0 13.0 9.7 13.4 10.0 14.2 9.8 14.6 10.4 14.9 10.3 15.8 10.1 16.7 10.0
(14.0) 32.5 12.8 9.6 13.2 9.8 13.9 9.7 14.3 10.3 14.7 10.2 15.4 10.0 16.4 9.9
35.0 12.5 9.4 12.9 9.7 13.7 9.6 14.0 10.1 14.4 10.1 15.1 9.9 16.0 9.7
37.5 12.3 9.3 12.7 9.6 13.4 9.5 13.8 10.0 14.1 10.0 14.8 9.8 15.7 9.6
40.0 12.1 9.2 12.4 9.5 13.1 9.4 13.5 9.9 13.8 9.8 14.5 9.6 15.4 9.5
43.0 11.8 9.1 12.1 9.3 12.8 9.2 13.2 9.8 13.5 9.7 14.1 9.5 15.0 9.4
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 89
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 15.2 11.2 15.8 11.6 16.8 11.5 17.3 12.2 17.8 12.1 18.9 11.9 20.2 11.8
22.5 15.2 11.2 15.8 11.6 16.8 11.5 17.3 12.2 17.8 12.1 18.9 11.9 20.2 11.8
25.0 15.2 11.2 15.8 11.6 16.8 11.5 17.3 12.1 17.7 12.0 18.7 11.9 19.9 11.7
27.5 15.2 11.2 15.6 11.5 16.5 11.4 16.9 12.0 17.4 11.9 18.4 11.7 19.5 11.6
140 30.0 14.9 11.1 15.3 11.4 16.2 11.2 16.6 11.9 17.1 11.8 18.0 11.6 19.1 11.4
(16.0) 32.5 14.6 10.9 15.0 11.2 15.9 11.1 16.3 11.7 16.8 11.6 17.6 11.4 18.7 11.3
35.0 14.3 10.8 14.8 11.1 15.6 11.0 16.0 11.6 16.4 11.5 17.3 11.3 18.3 11.1
37.5 14.1 10.7 14.5 11.0 15.3 10.8 15.7 11.5 16.1 11.4 16.9 11.2 17.9 11.0
40.0 13.8 10.5 14.2 10.8 15.0 10.7 15.4 11.3 15.8 11.3 16.6 11.0 17.6 10.9
43.0 13.4 10.4 13.8 10.7 14.6 10.5 15.0 11.2 15.4 11.1 16.1 10.9 17.1 10.7
20.0 21.3 16.1 22.1 16.6 23.5 16.5 24.2 17.5 25.0 17.4 26.5 17.2 28.3 17.0
22.5 21.3 16.1 22.1 16.6 23.5 16.5 24.2 17.5 25.0 17.4 26.5 17.2 28.3 17.0
25.0 21.3 16.1 22.1 16.6 23.5 16.5 24.2 17.5 24.8 17.3 26.2 17.1 27.9 16.8
27.5 21.2 16.0 21.8 16.5 23.1 16.3 23.7 17.3 24.3 17.1 25.7 16.9 27.3 16.6
200 30.0 20.8 15.9 21.4 16.3 22.7 16.1 23.3 17.1 23.9 16.9 25.2 16.7 26.8 16.4
(22.4) 32.5 20.4 15.7 21.0 16.1 22.3 16.0 22.9 16.9 23.5 16.8 24.7 16.5 26.2 16.2
35.0 20.1 15.5 20.7 16.0 21.9 15.8 22.4 16.7 23.0 16.6 24.2 16.3 25.7 16.1
37.5 19.7 15.3 20.3 15.8 21.4 15.6 22.0 16.5 22.6 16.4 23.7 16.1 25.1 15.9
40.0 19.3 15.1 19.9 15.6 21.0 15.4 21.6 16.4 22.1 16.2 23.2 15.9 24.6 15.7
43.0 18.8 14.9 19.4 15.4 20.5 15.2 21.1 16.1 21.6 16.0 22.6 15.7 23.9 15.5
20.0 26.6 20.0 27.6 20.7 29.4 20.5 30.3 21.7 31.2 21.6 33.1 21.3 35.4 21.1
22.5 26.6 20.0 27.6 20.7 29.4 20.5 30.3 21.7 31.2 21.6 33.1 21.3 35.4 21.1
25.0 26.6 20.0 27.6 20.7 29.4 20.5 30.2 21.7 31.0 21.5 32.8 21.2 34.8 20.9
27.5 26.5 20.0 27.3 20.5 28.9 20.3 29.7 21.5 30.4 21.3 32.1 20.9 34.2 20.7
250 30.0 26.0 19.7 26.8 20.3 28.4 20.1 29.1 21.2 29.9 21.1 31.5 20.7 33.5 20.4
(28.0) 32.5 25.6 19.5 26.3 20.1 27.8 19.8 28.6 21.0 29.3 20.8 30.9 20.5 32.8 20.2
35.0 25.1 19.3 25.8 19.8 27.3 19.6 28.0 20.7 28.8 20.6 30.3 20.2 32.1 19.9
37.5 24.6 19.0 25.3 19.6 26.8 19.4 27.5 20.5 28.2 20.4 29.6 20.0 31.4 19.7
40.0 24.1 18.8 24.8 19.4 26.3 19.1 27.0 20.3 27.7 20.2 29.0 19.8 30.7 19.5
43.0 23.5 18.5 24.2 19.1 25.6 18.9 26.3 20.0 27.0 19.9 28.2 19.5 29.9 19.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 90
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMR-E-L/R CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.7 1.8
27.5 2.1 1.7 2.1 1.8 2.3 1.7 2.3 1.9 2.4 1.8 2.5 1.8 2.7 1.8
20 30.0 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.6 1.8
(2.2) 32.5 2.0 1.7 2.1 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
35.0 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
37.5 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.5 1.7
40.0 1.9 1.6 2.0 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.3 1.7 2.4 1.7
43.0 1.8 1.6 1.9 1.7 2.0 1.6 2.1 1.8 2.1 1.7 2.2 1.7 2.3 1.7
20.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
22.5 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
25.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
27.5 2.7 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.0 2.1 3.2 2.1 3.4 2.1
25 30.0 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.3 2.0
(2.8) 32.5 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 2.9 2.1 3.1 2.0 3.3 2.0
35.0 2.5 1.9 2.6 2.0 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0
37.5 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.8 2.0 3.0 2.0 3.1 2.0
40.0 2.4 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 1.9
43.0 2.4 1.8 2.4 1.9 2.6 1.9 2.6 2.0 2.7 2.0 2.8 1.9 3.0 1.9
20.0 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.6 2.6
22.5 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.6 2.6
25.0 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
27.5 3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.1 2.5 4.4 2.5
32 30.0 3.3 2.4 3.4 2.5 3.6 2.4 3.7 2.6 3.8 2.5 4.1 2.5 4.3 2.5
(3.6) 32.5 3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.2 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.4 4.1 2.4
37.5 3.2 2.3 3.3 2.4 3.4 2.3 3.5 2.5 3.6 2.4 3.8 2.4 4.0 2.4
40.0 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.7 2.4 3.9 2.3
43.0 3.0 2.2 3.1 2.3 3.3 2.3 3.4 2.4 3.5 2.4 3.6 2.3 3.8 2.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 91
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMS1(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
22.5 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
25.0 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
27.5 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.6
15 30.0 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.0 1.6
(1.7) 32.5 1.6 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
35.0 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5
37.5 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5
40.0 1.5 1.4 1.5 1.5 1.6 1.4 1.6 1.6 1.7 1.5 1.8 1.5 1.9 1.5
43.0 1.4 1.4 1.5 1.4 1.6 1.4 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.5
20.0 2.1 1.8 2.2 1.9 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
22.5 2.1 1.8 2.2 1.9 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
25.0 2.1 1.8 2.2 1.9 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.7 1.9
27.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.6 1.9
(2.2) 32.5 2.0 1.7 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.2 1.9 2.3 1.8 2.5 1.8
40.0 1.9 1.7 2.0 1.8 2.1 1.7 2.1 1.9 2.2 1.9 2.3 1.8 2.4 1.8
43.0 1.8 1.7 1.9 1.7 2.0 1.7 2.1 1.8 2.1 1.8 2.2 1.8 2.3 1.8
20.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.6 2.1 2.7 2.2 2.8 2.2 2.9 2.3 3.0 2.3 3.2 2.2 3.3 2.2
(2.8) 32.5 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 2.9 2.3 3.1 2.2 3.3 2.2
35.0 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.8 2.2 3.0 2.2 3.1 2.1
40.0 2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.1
43.0 2.4 2.0 2.4 2.1 2.6 2.0 2.6 2.2 2.7 2.2 2.8 2.1 3.0 2.1
20.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.6 2.7
22.5 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.6 2.7
25.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.2 2.7 4.5 2.7
27.5 3.4 2.6 3.5 2.7 3.7 2.6 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.6
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.5 3.3 2.6 3.5 2.5 3.6 2.7 3.7 2.7 3.9 2.6 4.1 2.6
37.5 3.2 2.5 3.3 2.5 3.4 2.5 3.5 2.7 3.6 2.6 3.8 2.6 4.0 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.5
43.0 3.0 2.4 3.1 2.5 3.3 2.4 3.4 2.6 3.5 2.6 3.6 2.5 3.8 2.5
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.7 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.7 3.3
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.6 3.3
27.5 4.3 3.1 4.4 3.2 4.6 3.2 4.8 3.4 4.9 3.3 5.2 3.3 5.5 3.2
40 30.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.3 4.8 3.3 5.1 3.2 5.4 3.2
(4.5) 32.5 4.1 3.1 4.2 3.1 4.5 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.3 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1
37.5 4.0 3.0 4.1 3.1 4.3 3.0 4.4 3.2 4.5 3.2 4.8 3.1 5.0 3.1
40.0 3.9 2.9 4.0 3.0 4.2 3.0 4.3 3.2 4.4 3.2 4.7 3.1 4.9 3.0
43.0 3.8 2.9 3.9 3.0 4.1 3.0 4.2 3.1 4.3 3.1 4.5 3.0 4.8 3.0
20.0 5.3 3.9 5.5 4.0 5.9 3.9 6.1 4.2 6.2 4.1 6.6 4.1 7.1 4.0
22.5 5.3 3.9 5.5 4.0 5.9 3.9 6.1 4.2 6.2 4.1 6.6 4.1 7.1 4.0
25.0 5.3 3.9 5.5 4.0 5.9 3.9 6.0 4.2 6.2 4.1 6.6 4.1 7.0 4.0
27.5 5.3 3.8 5.5 3.9 5.8 3.9 5.9 4.1 6.1 4.1 6.4 4.0 6.8 4.0
50 30.0 5.2 3.8 5.4 3.9 5.7 3.9 5.8 4.1 6.0 4.0 6.3 4.0 6.7 3.9
(5.6) 32.5 5.1 3.7 5.3 3.9 5.6 3.8 5.7 4.0 5.9 4.0 6.2 3.9 6.6 3.9
35.0 5.0 3.7 5.2 3.8 5.5 3.8 5.6 4.0 5.8 3.9 6.1 3.9 6.4 3.8
37.5 4.9 3.7 5.1 3.8 5.4 3.7 5.5 3.9 5.6 3.9 5.9 3.8 6.3 3.8
40.0 4.8 3.6 5.0 3.7 5.3 3.7 5.4 3.9 5.5 3.8 5.8 3.8 6.1 3.7
43.0 4.7 3.5 4.8 3.6 5.1 3.6 5.3 3.8 5.4 3.8 5.6 3.7 6.0 3.6
20.0 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.3 7.9 5.2 8.4 5.2 9.0 5.1
22.5 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.3 7.9 5.2 8.4 5.2 9.0 5.1
25.0 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.2 7.9 5.2 8.3 5.1 8.8 5.1
27.5 6.7 4.9 6.9 5.0 7.3 4.9 7.5 5.2 7.7 5.1 8.1 5.1 8.7 5.0
63 30.0 6.6 4.8 6.8 4.9 7.2 4.9 7.4 5.1 7.6 5.1 8.0 5.0 8.5 4.9
(7.1) 32.5 6.5 4.7 6.7 4.9 7.1 4.8 7.2 5.1 7.4 5.0 7.8 4.9 8.3 4.9
35.0 6.4 4.7 6.5 4.8 6.9 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.1 4.8
37.5 6.2 4.6 6.4 4.7 6.8 4.7 7.0 4.9 7.2 4.9 7.5 4.8 8.0 4.7
40.0 6.1 4.6 6.3 4.7 6.7 4.6 6.8 4.9 7.0 4.8 7.4 4.7 7.8 4.7
43.0 6.0 4.5 6.1 4.6 6.5 4.6 6.7 4.8 6.9 4.8 7.2 4.7 7.6 4.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 92
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
1-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.4 3.3 4.5 3.4 4.9 3.4 5.0 3.6 5.2 3.6 5.5 3.6 5.8 3.5
22.5 4.4 3.3 4.5 3.4 4.8 3.4 4.9 3.6 5.1 3.6 5.4 3.5 5.7 3.5
25.0 4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.5 5.0 3.5 5.3 3.5 5.6 3.4
27.5 4.2 3.2 4.3 3.3 4.6 3.3 4.8 3.5 4.9 3.5 5.2 3.4 5.5 3.4
40 30.0 4.1 3.2 4.2 3.3 4.5 3.2 4.7 3.5 4.8 3.4 5.1 3.4 5.4 3.3
(4.5) 32.5 4.1 3.2 4.2 3.2 4.4 3.2 4.6 3.4 4.7 3.4 5.0 3.4 5.3 3.3
35.0 4.0 3.1 4.1 3.2 4.3 3.2 4.5 3.4 4.6 3.4 4.9 3.3 5.2 3.3
37.5 3.9 3.1 4.0 3.2 4.2 3.1 4.4 3.3 4.5 3.3 4.8 3.3 5.1 3.2
40.0 3.9 3.1 3.9 3.1 4.2 3.1 4.3 3.3 4.4 3.3 4.7 3.2 5.0 3.2
43.0 3.8 3.0 3.8 3.1 4.0 3.0 4.2 3.3 4.3 3.2 4.6 3.2 4.8 3.1
20.0 5.4 3.9 5.6 4.0 6.1 4.0 6.3 4.2 6.5 4.2 6.9 4.1 7.3 4.1
22.5 5.4 3.9 5.6 4.0 6.0 3.9 6.2 4.2 6.3 4.1 6.7 4.1 7.1 4.0
25.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
27.5 5.3 3.8 5.4 3.9 5.7 3.8 5.9 4.1 6.1 4.0 6.5 4.0 6.9 3.9
50 30.0 5.2 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.7 3.9
(5.6) 32.5 5.1 3.7 5.2 3.8 5.5 3.7 5.7 3.9 5.9 3.9 6.2 3.9 6.6 3.8
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.7 3.9 6.1 3.8 6.5 3.8
37.5 4.9 3.6 5.0 3.7 5.3 3.6 5.5 3.8 5.6 3.8 6.0 3.8 6.3 3.7
40.0 4.8 3.6 4.9 3.6 5.2 3.6 5.3 3.8 5.5 3.8 5.8 3.7 6.2 3.7
43.0 4.7 3.5 4.7 3.5 5.0 3.5 5.2 3.7 5.4 3.7 5.7 3.7 6.0 3.6
20.0 6.9 5.1 7.1 5.2 7.7 5.2 7.9 5.5 8.2 5.5 8.7 5.5 9.2 5.4
22.5 6.9 5.1 7.1 5.2 7.6 5.2 7.8 5.5 8.0 5.5 8.5 5.4 9.1 5.3
25.0 6.8 5.0 7.0 5.2 7.4 5.1 7.7 5.4 7.9 5.4 8.4 5.3 8.9 5.2
27.5 6.7 5.0 6.8 5.1 7.3 5.1 7.5 5.4 7.7 5.3 8.2 5.3 8.7 5.2
63 30.0 6.5 4.9 6.7 5.0 7.1 5.0 7.4 5.3 7.6 5.3 8.1 5.2 8.5 5.1
(7.1) 32.5 6.4 4.9 6.6 5.0 7.0 4.9 7.2 5.2 7.4 5.2 7.9 5.1 8.4 5.1
35.0 6.3 4.8 6.4 4.9 6.8 4.9 7.1 5.2 7.3 5.1 7.7 5.1 8.2 5.0
37.5 6.2 4.7 6.3 4.8 6.7 4.8 6.9 5.1 7.1 5.1 7.6 5.0 8.0 4.9
40.0 6.1 4.7 6.2 4.8 6.6 4.7 6.8 5.0 7.0 5.0 7.4 4.9 7.8 4.9
43.0 6.0 4.6 6.0 4.7 6.4 4.7 6.6 5.0 6.8 4.9 7.2 4.9 7.6 4.8
20.0 7.8 5.7 8.0 5.9 8.6 5.9 8.9 6.2 9.2 6.2 9.8 6.1 10.4 6.0
22.5 7.7 5.7 8.0 5.8 8.5 5.8 8.8 6.1 9.1 6.1 9.6 6.0 10.2 5.9
25.0 7.6 5.6 7.8 5.8 8.4 5.7 8.6 6.1 8.9 6.0 9.4 5.9 10.0 5.9
27.5 7.5 5.5 7.7 5.7 8.2 5.6 8.5 6.0 8.7 5.9 9.3 5.9 9.8 5.8
71 30.0 7.4 5.5 7.5 5.6 8.0 5.6 8.3 5.9 8.6 5.9 9.1 5.8 9.6 5.7
(8.0) 32.5 7.3 5.4 7.4 5.5 7.9 5.5 8.1 5.8 8.4 5.8 8.9 5.7 9.4 5.6
35.0 7.1 5.4 7.2 5.5 7.7 5.4 8.0 5.8 8.2 5.7 8.7 5.7 9.2 5.6
37.5 7.0 5.3 7.1 5.4 7.5 5.4 7.8 5.7 8.0 5.7 8.5 5.6 9.0 5.5
40.0 6.9 5.2 6.9 5.3 7.4 5.3 7.6 5.6 7.9 5.6 8.3 5.5 8.8 5.4
43.0 6.7 5.2 6.8 5.2 7.2 5.2 7.4 5.5 7.7 5.5 8.1 5.4 8.6 5.4
20.0 8.7 6.4 9.0 6.6 9.7 6.6 10.1 7.0 10.4 7.0 11.0 6.9 11.7 6.8
22.5 8.7 6.4 9.0 6.6 9.6 6.6 9.9 6.9 10.2 6.9 10.8 6.8 11.5 6.7
25.0 8.6 6.3 8.8 6.5 9.4 6.5 9.7 6.8 10.0 6.8 10.6 6.7 11.3 6.6
27.5 8.4 6.3 8.6 6.4 9.2 6.4 9.5 6.8 9.8 6.7 10.4 6.6 11.0 6.5
80 30.0 8.3 6.2 8.5 6.4 9.0 6.3 9.3 6.7 9.6 6.7 10.2 6.6 10.8 6.5
(9.0) 32.5 8.2 6.1 8.3 6.3 8.9 6.2 9.1 6.6 9.4 6.6 10.0 6.5 10.6 6.4
35.0 8.0 6.1 8.1 6.2 8.7 6.1 9.0 6.5 9.2 6.5 9.8 6.4 10.4 6.3
37.5 7.9 6.0 8.0 6.1 8.5 6.1 8.8 6.4 9.0 6.4 9.6 6.3 10.2 6.2
40.0 7.7 5.9 7.8 6.0 8.3 6.0 8.6 6.4 8.8 6.3 9.4 6.2 9.9 6.2
43.0 7.6 5.9 7.6 5.9 8.1 5.9 8.4 6.3 8.6 6.2 9.1 6.2 9.7 6.1
20.0 10.9 8.6 11.3 8.9 12.1 8.9 12.5 9.5 12.9 9.5 13.7 9.3 14.5 9.2
22.5 10.8 8.6 11.2 8.9 11.9 8.8 12.3 9.4 12.7 9.4 13.5 9.3 14.3 9.1
25.0 10.7 8.5 11.0 8.8 11.7 8.7 12.1 9.3 12.5 9.3 13.2 9.2 14.0 9.0
27.5 10.5 8.5 10.8 8.7 11.5 8.6 11.8 9.2 12.2 9.2 13.0 9.1 13.7 8.9
100 30.0 10.3 8.4 10.6 8.6 11.2 8.5 11.6 9.1 12.0 9.1 12.7 9.0 13.5 8.8
(11.2) 32.5 10.2 8.3 10.3 8.5 11.0 8.4 11.4 9.0 11.7 9.0 12.4 8.9 13.2 8.7
35.0 10.0 8.2 10.1 8.4 10.8 8.4 11.2 9.0 11.5 8.9 12.2 8.8 12.9 8.7
37.5 9.8 8.1 9.9 8.3 10.6 8.3 10.9 8.8 11.2 8.8 11.9 8.7 12.6 8.6
40.0 9.6 8.0 9.7 8.2 10.3 8.2 10.7 8.8 11.0 8.7 11.7 8.6 12.4 8.5
43.0 9.4 8.0 9.5 8.1 10.1 8.1 10.4 8.6 10.7 8.6 11.4 8.5 12.1 8.4
20.0 13.6 10.0 14.1 10.3 15.1 10.3 15.7 10.9 16.2 10.8 17.2 10.7 18.2 10.5
22.5 13.6 10.0 14.0 10.2 14.9 10.2 15.4 10.7 15.9 10.7 16.8 10.6 17.8 10.4
25.0 13.3 9.8 13.7 10.1 14.6 10.0 15.1 10.6 15.6 10.6 16.5 10.4 17.5 10.3
27.5 13.1 9.7 13.5 10.0 14.3 9.9 14.8 10.5 15.3 10.4 16.2 10.3 17.2 10.1
125 30.0 12.9 9.6 13.2 9.9 14.1 9.8 14.5 10.4 15.0 10.3 15.9 10.2 16.8 10.0
(14.0) 32.5 12.7 9.5 12.9 9.7 13.8 9.7 14.2 10.2 14.7 10.2 15.6 10.1 16.5 9.9
35.0 12.5 9.4 12.7 9.6 13.5 9.5 14.0 10.1 14.4 10.1 15.2 9.9 16.2 9.8
37.5 12.3 9.3 12.4 9.5 13.2 9.4 13.6 10.0 14.1 9.9 14.9 9.8 15.8 9.7
40.0 12.0 9.2 12.2 9.4 12.9 9.3 13.3 9.9 13.8 9.8 14.6 9.7 15.5 9.5
43.0 11.8 9.1 11.8 9.2 12.6 9.1 13.0 9.7 13.4 9.7 14.2 9.5 15.1 9.4
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 93
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 15.5 11.4 16.1 11.7 17.3 11.7 17.9 12.4 18.5 12.4 19.6 12.2 20.8 12.0
22.5 15.5 11.4 16.0 11.7 17.0 11.6 17.6 12.3 18.1 12.2 19.2 12.1 20.4 11.9
25.0 15.3 11.3 15.7 11.6 16.7 11.5 17.3 12.1 17.8 12.1 18.9 11.9 20.0 11.7
27.5 15.0 11.1 15.4 11.4 16.4 11.3 16.9 12.0 17.4 11.9 18.5 11.8 19.6 11.6
140 30.0 14.8 11.0 15.1 11.3 16.1 11.2 16.6 11.8 17.1 11.8 18.1 11.6 19.2 11.5
(16.0) 32.5 14.5 10.9 14.8 11.1 15.7 11.0 16.3 11.7 16.8 11.6 17.8 11.5 18.8 11.3
35.0 14.3 10.8 14.5 11.0 15.4 10.9 16.0 11.6 16.4 11.5 17.4 11.4 18.5 11.2
37.5 14.0 10.6 14.2 10.8 15.1 10.7 15.6 11.4 16.1 11.4 17.0 11.2 18.1 11.0
40.0 13.8 10.5 13.9 10.7 14.8 10.6 15.2 11.3 15.7 11.2 16.7 11.1 17.7 10.9
43.0 13.5 10.4 13.5 10.5 14.4 10.4 14.8 11.1 15.3 11.0 16.3 10.9 17.2 10.7
20.0 21.8 16.3 22.5 16.8 24.2 16.8 25.0 17.8 25.9 17.8 27.5 17.5 29.1 17.3
22.5 21.7 16.3 22.4 16.8 23.8 16.6 24.6 17.7 25.4 17.6 26.9 17.3 28.6 17.1
25.0 21.4 16.1 21.9 16.6 23.4 16.4 24.2 17.5 24.9 17.4 26.4 17.1 28.0 16.9
27.5 21.0 15.9 21.5 16.4 22.9 16.2 23.7 17.3 24.4 17.2 25.9 16.9 27.5 16.7
200 30.0 20.7 15.8 21.1 16.2 22.5 16.0 23.2 17.1 23.9 17.0 25.4 16.7 26.9 16.5
(22.4) 32.5 20.3 15.6 20.7 16.0 22.0 15.8 22.8 16.9 23.5 16.8 24.9 16.6 26.4 16.3
35.0 20.0 15.4 20.3 15.8 21.6 15.7 22.4 16.7 23.0 16.6 24.4 16.4 25.8 16.1
37.5 19.6 15.3 19.9 15.6 21.1 15.5 21.8 16.5 22.5 16.4 23.9 16.2 25.3 15.9
40.0 19.3 15.1 19.4 15.4 20.7 15.3 21.3 16.3 22.0 16.2 23.4 16.0 24.8 15.7
43.0 18.9 14.9 18.9 15.2 20.1 15.0 20.8 16.0 21.4 16.0 22.8 15.8 24.1 15.5
20.0 27.2 20.3 28.1 20.9 30.3 20.9 31.3 22.2 32.3 22.1 34.3 21.8 36.4 21.5
22.5 27.1 20.3 28.0 20.8 29.8 20.7 30.8 21.9 31.7 21.8 33.7 21.5 35.7 21.2
25.0 26.7 20.0 27.4 20.6 29.2 20.4 30.2 21.7 31.1 21.6 33.0 21.3 35.0 21.0
27.5 26.3 19.8 26.9 20.3 28.7 20.2 29.6 21.4 30.5 21.3 32.4 21.1 34.3 20.7
250 30.0 25.8 19.6 26.4 20.1 28.1 19.9 29.0 21.2 29.9 21.1 31.8 20.8 33.7 20.5
(28.0) 32.5 25.4 19.4 25.9 19.9 27.5 19.7 28.4 20.9 29.3 20.8 31.1 20.6 33.0 20.2
35.0 25.0 19.2 25.3 19.6 27.0 19.4 28.0 20.7 28.7 20.6 30.5 20.3 32.3 20.0
37.5 24.5 19.0 24.8 19.4 26.4 19.2 27.3 20.4 28.1 20.3 29.8 20.1 31.6 19.8
40.0 24.1 18.8 24.3 19.1 25.9 19.0 26.7 20.2 27.5 20.1 29.2 19.8 30.9 19.5
43.0 23.6 18.5 23.7 18.8 25.2 18.7 26.0 19.9 26.8 19.8 28.4 19.6 30.1 19.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 94
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMR-E-L/R CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.8 2.4 1.8 2.5 1.9 2.5 1.9 2.7 1.9 2.9 1.9
22.5 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.9 2.8 1.8
25.0 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
27.5 2.1 1.7 2.1 1.8 2.3 1.7 2.3 1.9 2.4 1.9 2.5 1.8 2.7 1.8
20 30.0 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.6 1.8
(2.2) 32.5 2.0 1.7 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
35.0 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
37.5 1.9 1.6 2.0 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.5 1.7
40.0 1.9 1.6 1.9 1.7 2.0 1.6 2.1 1.8 2.2 1.8 2.3 1.7 2.4 1.7
43.0 1.9 1.6 1.9 1.6 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.7 2.4 1.7
20.0 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.2 3.6 2.1
22.5 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.1 3.6 2.1
25.0 2.7 2.0 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
27.5 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.1 3.4 2.1
25 30.0 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0
37.5 2.5 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
40.0 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 1.9
43.0 2.4 1.8 2.4 1.9 2.5 1.9 2.6 2.0 2.7 2.0 2.8 1.9 3.0 1.9
20.0 3.5 2.5 3.6 2.5 3.9 2.5 4.0 2.7 4.2 2.7 4.4 2.6 4.7 2.6
22.5 3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.7 4.1 2.6 4.3 2.6 4.6 2.6
25.0 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
27.5 3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.5 4.4 2.5
32 30.0 3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.6 3.8 2.5 4.1 2.5 4.3 2.5
(3.6) 32.5 3.3 2.4 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.2 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.3 3.6 2.5 3.7 2.5 3.9 2.4 4.2 2.4
37.5 3.2 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.8 2.4 4.1 2.4
40.0 3.1 2.3 3.1 2.3 3.3 2.3 3.4 2.4 3.5 2.4 3.8 2.4 4.0 2.3
43.0 3.0 2.2 3.0 2.3 3.2 2.2 3.3 2.4 3.4 2.4 3.7 2.3 3.9 2.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 95
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMS1(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.7 1.5 1.7 1.5 1.8 1.5 1.9 1.7 2.0 1.7 2.1 1.6 2.2 1.6
22.5 1.6 1.5 1.7 1.5 1.8 1.5 1.9 1.6 1.9 1.6 2.0 1.6 2.2 1.6
25.0 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
27.5 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
15 30.0 1.6 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.0 1.6
(1.7) 32.5 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
35.0 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.9 1.6 2.0 1.5
37.5 1.5 1.4 1.5 1.5 1.6 1.4 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5
40.0 1.5 1.4 1.5 1.4 1.6 1.4 1.6 1.6 1.7 1.5 1.8 1.5 1.9 1.5
43.0 1.4 1.4 1.4 1.4 1.5 1.4 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.5
20.0 2.1 1.8 2.2 1.9 2.4 1.9 2.5 2.0 2.5 2.0 2.7 2.0 2.9 1.9
22.5 2.1 1.8 2.2 1.9 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
25.0 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.4 2.0 2.6 1.9 2.8 1.9
27.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.6 1.9
(2.2) 32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8
37.5 1.9 1.7 2.0 1.8 2.1 1.7 2.1 1.9 2.2 1.9 2.3 1.8 2.5 1.8
40.0 1.9 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.2 1.8 2.3 1.8 2.4 1.8
43.0 1.9 1.7 1.9 1.7 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.8 2.4 1.8
20.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
22.5 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
25.0 2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.2 2.3 3.4 2.2
25 30.0 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.8 2.3 2.9 2.3 3.1 2.2 3.3 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.1
40.0 2.4 2.0 2.4 2.1 2.6 2.0 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.1
43.0 2.4 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.2 2.8 2.1 3.0 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.9 4.2 2.9 4.4 2.8 4.7 2.8
22.5 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.8 4.1 2.8 4.3 2.8 4.6 2.7
25.0 3.4 2.6 3.5 2.7 3.8 2.6 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
27.5 3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
32 30.0 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.7
(3.6) 32.5 3.3 2.5 3.3 2.6 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.7 4.2 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.7 2.7 3.9 2.6 4.2 2.6
37.5 3.2 2.5 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.8 2.6 4.1 2.6
40.0 3.1 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.5 2.6 3.8 2.6 4.0 2.5
43.0 3.0 2.4 3.0 2.4 3.2 2.4 3.3 2.6 3.4 2.6 3.7 2.5 3.9 2.5
20.0 4.4 3.2 4.5 3.3 4.9 3.3 5.0 3.5 5.2 3.5 5.5 3.4 5.8 3.4
22.5 4.4 3.2 4.5 3.3 4.8 3.3 4.9 3.4 5.1 3.4 5.4 3.4 5.7 3.3
25.0 4.3 3.2 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.6 3.3
27.5 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.1 4.2 3.2 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.3 5.4 3.2
(4.5) 32.5 4.1 3.0 4.2 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.3 3.2
35.0 4.0 3.0 4.1 3.1 4.3 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1
37.5 3.9 3.0 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.8 3.1 5.1 3.1
40.0 3.9 2.9 3.9 3.0 4.2 3.0 4.3 3.2 4.4 3.1 4.7 3.1 5.0 3.1
43.0 3.8 2.9 3.8 2.9 4.0 2.9 4.2 3.1 4.3 3.1 4.6 3.1 4.8 3.0
20.0 5.4 3.9 5.6 4.0 6.1 4.0 6.3 4.3 6.5 4.2 6.9 4.2 7.3 4.1
22.5 5.4 3.9 5.6 4.0 6.0 4.0 6.2 4.2 6.3 4.2 6.7 4.1 7.1 4.1
25.0 5.3 3.9 5.5 4.0 5.8 3.9 6.0 4.2 6.2 4.1 6.6 4.1 7.0 4.0
27.5 5.3 3.8 5.4 3.9 5.7 3.9 5.9 4.1 6.1 4.1 6.5 4.0 6.9 4.0
50 30.0 5.2 3.8 5.3 3.9 5.6 3.8 5.8 4.1 6.0 4.0 6.4 4.0 6.7 3.9
(5.6) 32.5 5.1 3.7 5.2 3.8 5.5 3.8 5.7 4.0 5.9 4.0 6.2 3.9 6.6 3.9
35.0 5.0 3.7 5.1 3.8 5.4 3.7 5.6 4.0 5.7 3.9 6.1 3.9 6.5 3.8
37.5 4.9 3.6 5.0 3.7 5.3 3.7 5.5 3.9 5.6 3.9 6.0 3.8 6.3 3.8
40.0 4.8 3.6 4.9 3.7 5.2 3.6 5.3 3.8 5.5 3.8 5.8 3.8 6.2 3.7
43.0 4.7 3.6 4.7 3.6 5.0 3.6 5.2 3.8 5.4 3.8 5.7 3.7 6.0 3.7
20.0 6.9 4.9 7.1 5.1 7.7 5.1 7.9 5.4 8.2 5.4 8.7 5.3 9.2 5.2
22.5 6.9 4.9 7.1 5.1 7.6 5.0 7.8 5.3 8.0 5.3 8.5 5.2 9.1 5.1
25.0 6.8 4.9 7.0 5.0 7.4 5.0 7.7 5.2 7.9 5.2 8.4 5.2 8.9 5.1
27.5 6.7 4.8 6.8 4.9 7.3 4.9 7.5 5.2 7.7 5.2 8.2 5.1 8.7 5.0
63 30.0 6.5 4.8 6.7 4.9 7.1 4.8 7.4 5.1 7.6 5.1 8.1 5.0 8.5 4.9
(7.1) 32.5 6.4 4.7 6.6 4.8 7.0 4.8 7.2 5.1 7.4 5.0 7.9 5.0 8.4 4.9
35.0 6.3 4.7 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.2 4.8
37.5 6.2 4.6 6.3 4.7 6.7 4.6 6.9 4.9 7.1 4.9 7.6 4.8 8.0 4.8
40.0 6.1 4.6 6.2 4.6 6.6 4.6 6.8 4.9 7.0 4.8 7.4 4.8 7.8 4.7
43.0 6.0 4.5 6.0 4.5 6.4 4.5 6.6 4.8 6.8 4.8 7.2 4.7 7.6 4.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 96
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
1-3. Cooling capacity with PUHY-RP450-650YSJM
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.2 4.4 3.3 4.7 3.3 4.8 3.5 5.0 3.5 5.3 3.5 5.7 3.4
22.5 4.2 3.2 4.3 3.3 4.6 3.3 4.8 3.5 4.9 3.5 5.3 3.5 5.6 3.4
25.0 4.2 3.2 4.3 3.3 4.6 3.3 4.7 3.5 4.9 3.5 5.2 3.4 5.6 3.4
27.5 4.1 3.2 4.2 3.3 4.5 3.3 4.7 3.5 4.8 3.5 5.2 3.4 5.5 3.4
40 30.0 4.1 3.2 4.2 3.2 4.5 3.2 4.6 3.4 4.8 3.4 5.1 3.4 5.5 3.4
(4.5) 32.5 4.0 3.1 4.1 3.2 4.4 3.2 4.6 3.4 4.7 3.4 5.1 3.4 5.4 3.3
35.0 4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.4 4.7 3.4 5.0 3.4 5.4 3.3
37.5 4.0 3.1 4.0 3.2 4.3 3.2 4.5 3.4 4.6 3.4 5.0 3.3 5.3 3.3
40.0 3.9 3.1 4.0 3.1 4.3 3.1 4.4 3.4 4.6 3.3 4.9 3.3 5.3 3.3
43.0 3.9 3.1 3.9 3.1 4.2 3.1 4.4 3.3 4.5 3.3 4.9 3.3 5.2 3.3
20.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
25.0 5.2 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.9 3.9
50 30.0 5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.7 5.5 3.7 5.7 4.0 5.9 3.9 6.3 3.9 6.7 3.9
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.7 3.8
37.5 4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.6 3.8
40.0 4.9 3.6 4.9 3.6 5.3 3.6 5.5 3.9 5.7 3.9 6.1 3.8 6.5 3.8
43.0 4.8 3.6 4.9 3.6 5.2 3.6 5.4 3.8 5.6 3.8 6.0 3.8 6.5 3.8
20.0 6.7 5.0 6.9 5.1 7.4 5.1 7.6 5.4 7.9 5.4 8.4 5.3 8.9 5.3
22.5 6.6 5.0 6.8 5.1 7.3 5.1 7.6 5.4 7.8 5.4 8.3 5.3 8.8 5.2
25.0 6.6 4.9 6.8 5.1 7.2 5.0 7.5 5.3 7.7 5.3 8.2 5.3 8.8 5.2
27.5 6.5 4.9 6.7 5.0 7.2 5.0 7.4 5.3 7.6 5.3 8.2 5.2 8.7 5.2
63 30.0 6.4 4.9 6.6 5.0 7.1 5.0 7.3 5.3 7.6 5.3 8.1 5.2 8.6 5.1
(7.1) 32.5 6.4 4.8 6.5 4.9 7.0 4.9 7.2 5.2 7.5 5.2 8.0 5.2 8.5 5.1
35.0 6.3 4.8 6.4 4.9 6.9 4.9 7.1 5.2 7.4 5.2 7.9 5.1 8.5 5.1
37.5 6.2 4.8 6.3 4.9 6.8 4.9 7.1 5.2 7.3 5.2 7.8 5.1 8.4 5.1
40.0 6.2 4.7 6.3 4.8 6.7 4.8 7.0 5.1 7.2 5.1 7.8 5.1 8.3 5.0
43.0 6.1 4.7 6.2 4.8 6.7 4.8 6.9 5.1 7.1 5.1 7.7 5.0 8.2 5.0
20.0 7.6 5.6 7.8 5.7 8.3 5.7 8.6 6.0 8.9 6.0 9.4 5.9 10.0 5.9
22.5 7.5 5.5 7.7 5.7 8.2 5.7 8.5 6.0 8.8 6.0 9.4 5.9 10.0 5.8
25.0 7.4 5.5 7.6 5.6 8.1 5.6 8.4 6.0 8.7 5.9 9.3 5.9 9.9 5.8
27.5 7.3 5.5 7.5 5.6 8.1 5.6 8.3 5.9 8.6 5.9 9.2 5.8 9.8 5.8
71 30.0 7.3 5.4 7.4 5.6 8.0 5.5 8.2 5.9 8.5 5.9 9.1 5.8 9.7 5.7
(8.0) 32.5 7.2 5.4 7.3 5.5 7.9 5.5 8.2 5.8 8.4 5.8 9.0 5.8 9.6 5.7
35.0 7.1 5.4 7.2 5.5 7.8 5.5 8.0 5.8 8.3 5.8 8.9 5.7 9.5 5.7
37.5 7.0 5.3 7.2 5.4 7.7 5.4 8.0 5.8 8.3 5.7 8.8 5.7 9.4 5.6
40.0 7.0 5.3 7.1 5.4 7.6 5.4 7.9 5.7 8.2 5.7 8.7 5.7 9.4 5.6
43.0 6.9 5.2 7.0 5.3 7.5 5.3 7.8 5.7 8.1 5.7 8.6 5.6 9.2 5.6
20.0 8.5 6.3 8.8 6.5 9.4 6.5 9.7 6.8 10.0 6.8 10.6 6.7 11.3 6.6
22.5 8.4 6.3 8.7 6.4 9.3 6.4 9.6 6.8 9.9 6.8 10.5 6.7 11.2 6.6
25.0 8.3 6.2 8.6 6.4 9.2 6.4 9.5 6.8 9.8 6.7 10.4 6.7 11.1 6.6
27.5 8.3 6.2 8.5 6.3 9.1 6.3 9.4 6.7 9.7 6.7 10.3 6.6 11.0 6.5
80 30.0 8.2 6.1 8.4 6.3 9.0 6.3 9.3 6.7 9.6 6.6 10.2 6.6 10.9 6.5
(9.0) 32.5 8.1 6.1 8.3 6.2 8.9 6.2 9.2 6.6 9.5 6.6 10.1 6.5 10.8 6.5
35.0 8.0 6.1 8.1 6.2 8.8 6.2 9.0 6.5 9.4 6.6 10.0 6.5 10.7 6.4
37.5 7.9 6.0 8.0 6.1 8.7 6.1 9.0 6.5 9.3 6.5 9.9 6.5 10.6 6.4
40.0 7.8 6.0 7.9 6.1 8.6 6.1 8.9 6.5 9.2 6.5 9.8 6.4 10.5 6.4
43.0 7.7 5.9 7.8 6.0 8.4 6.0 8.7 6.4 9.1 6.4 9.7 6.4 10.4 6.3
20.0 10.6 8.5 10.9 8.8 11.7 8.7 12.0 9.3 12.4 9.3 13.2 9.2 14.1 9.0
22.5 10.5 8.4 10.8 8.7 11.5 8.7 11.9 9.3 12.3 9.2 13.1 9.1 13.9 9.0
25.0 10.4 8.4 10.6 8.7 11.4 8.6 11.8 9.2 12.2 9.2 13.0 9.1 13.8 9.0
27.5 10.3 8.3 10.5 8.6 11.3 8.6 11.7 9.2 12.1 9.1 12.9 9.0 13.7 8.9
100 30.0 10.2 8.3 10.4 8.5 11.2 8.5 11.5 9.1 11.9 9.1 12.7 9.0 13.6 8.9
(11.2) 32.5 10.1 8.2 10.3 8.5 11.0 8.5 11.4 9.0 11.8 9.0 12.6 8.9 13.5 8.8
35.0 9.9 8.2 10.1 8.4 10.9 8.4 11.2 9.0 11.7 9.0 12.5 8.9 13.3 8.8
37.5 9.8 8.1 10.0 8.4 10.8 8.3 11.2 8.9 11.6 8.9 12.4 8.8 13.2 8.8
40.0 9.7 8.1 9.9 8.3 10.6 8.3 11.0 8.9 11.4 8.9 12.2 8.8 13.1 8.7
43.0 9.6 8.0 9.7 8.2 10.5 8.2 10.9 8.8 11.3 8.8 12.1 8.7 12.9 8.7
20.0 13.2 9.8 13.6 10.1 14.6 10.0 15.1 10.6 15.5 10.6 16.5 10.4 17.6 10.3
22.5 13.1 9.7 13.5 10.0 14.4 9.9 14.9 10.5 15.4 10.5 16.4 10.4 17.4 10.2
25.0 13.0 9.7 13.3 9.9 14.3 9.9 14.7 10.5 15.2 10.4 16.2 10.3 17.3 10.2
27.5 12.8 9.6 13.2 9.8 14.1 9.8 14.6 10.4 15.1 10.4 16.1 10.3 17.1 10.1
125 30.0 12.7 9.5 13.0 9.8 13.9 9.7 14.4 10.3 14.9 10.3 15.9 10.2 17.0 10.1
(14.0) 32.5 12.6 9.5 12.8 9.7 13.8 9.7 14.3 10.3 14.8 10.2 15.8 10.1 16.8 10.0
35.0 12.4 9.4 12.7 9.6 13.6 9.6 14.0 10.1 14.6 10.2 15.6 10.1 16.7 10.0
37.5 12.3 9.3 12.5 9.5 13.5 9.5 14.0 10.1 14.4 10.1 15.5 10.0 16.5 9.9
40.0 12.2 9.3 12.4 9.5 13.3 9.4 13.8 10.1 14.3 10.0 15.3 10.0 16.4 9.9
43.0 12.0 9.2 12.2 9.4 13.1 9.4 13.6 10.0 14.1 9.9 15.1 9.9 16.2 9.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 97
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 15.1 11.2 15.6 11.5 16.7 11.4 17.2 12.1 17.8 12.1 18.9 11.9 20.1 11.8
22.5 15.0 11.1 15.4 11.4 16.5 11.4 17.0 12.0 17.6 12.0 18.7 11.9 19.9 11.7
25.0 14.8 11.0 15.2 11.3 16.3 11.3 16.8 12.0 17.4 11.9 18.5 11.8 19.7 11.6
27.5 14.7 11.0 15.0 11.2 16.1 11.2 16.7 11.9 17.2 11.8 18.4 11.7 19.6 11.6
140 30.0 14.5 10.9 14.9 11.2 15.9 11.1 16.5 11.8 17.0 11.8 18.2 11.7 19.4 11.5
(16.0) 32.5 14.4 10.8 14.7 11.1 15.8 11.0 16.3 11.7 16.9 11.7 18.0 11.6 19.2 11.5
35.0 14.2 10.7 14.5 11.0 15.6 11.0 16.0 11.6 16.7 11.6 17.8 11.5 19.1 11.4
37.5 14.1 10.7 14.3 10.9 15.4 10.9 15.9 11.6 16.5 11.5 17.7 11.4 18.9 11.3
40.0 13.9 10.6 14.1 10.8 15.2 10.8 15.8 11.5 16.3 11.5 17.5 11.4 18.7 11.3
43.0 13.7 10.5 13.9 10.7 15.0 10.7 15.6 11.4 16.1 11.4 17.3 11.3 18.5 11.2
20.0 21.2 16.0 21.8 16.5 23.3 16.4 24.1 17.4 24.9 17.3 26.5 17.1 28.1 16.9
22.5 21.0 15.9 21.6 16.4 23.1 16.3 23.8 17.3 24.6 17.2 26.2 17.1 27.9 16.8
25.0 20.7 15.8 21.3 16.3 22.8 16.2 23.6 17.2 24.4 17.1 26.0 17.0 27.6 16.7
27.5 20.5 15.7 21.0 16.1 22.6 16.1 23.3 17.1 24.1 17.0 25.7 16.9 27.4 16.7
200 30.0 20.3 15.6 20.8 16.0 22.3 16.0 23.1 17.0 23.9 16.9 25.5 16.8 27.2 16.6
(22.4) 32.5 20.1 15.5 20.5 15.9 22.1 15.9 22.8 16.9 23.6 16.8 25.2 16.7 26.9 16.5
35.0 19.9 15.4 20.3 15.8 21.8 15.7 22.4 16.7 23.4 16.7 25.0 16.6 26.7 16.4
37.5 19.7 15.3 20.0 15.7 21.5 15.6 22.3 16.7 23.1 16.6 24.7 16.5 26.4 16.3
40.0 19.5 15.2 19.8 15.5 21.3 15.5 22.1 16.6 22.8 16.5 24.5 16.4 26.2 16.2
43.0 19.2 15.1 19.5 15.4 21.0 15.4 21.8 16.4 22.6 16.4 24.2 16.3 25.9 16.1
20.0 26.5 19.9 27.3 20.5 29.2 20.4 30.1 21.7 31.1 21.6 33.1 21.3 35.2 21.0
22.5 26.2 19.8 26.9 20.4 28.8 20.3 29.8 21.5 30.8 21.4 32.8 21.2 34.9 20.9
25.0 25.9 19.7 26.6 20.2 28.5 20.1 29.5 21.4 30.5 21.3 32.4 21.1 34.6 20.8
27.5 25.7 19.5 26.3 20.1 28.2 20.0 29.2 21.2 30.1 21.2 32.1 21.0 34.3 20.7
250 30.0 25.4 19.4 26.0 19.9 27.9 19.8 28.9 21.1 29.8 21.0 31.8 20.8 33.9 20.6
(28.0) 32.5 25.1 19.3 25.7 19.8 27.6 19.7 28.5 21.0 29.5 20.9 31.5 20.7 33.6 20.5
35.0 24.9 19.2 25.4 19.6 27.2 19.6 28.0 20.7 29.2 20.8 31.2 20.6 33.3 20.4
37.5 24.6 19.0 25.0 19.5 26.9 19.4 27.9 20.7 28.9 20.6 30.9 20.5 33.0 20.3
40.0 24.3 18.9 24.7 19.3 26.6 19.3 27.6 20.6 28.6 20.5 30.6 20.4 32.7 20.2
43.0 24.0 18.7 24.3 19.1 26.2 19.1 27.2 20.4 28.2 20.4 30.2 20.2 32.4 20.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 98
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMR-E-L/R CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.1 1.8 2.3 1.7 2.3 1.9 2.4 1.9 2.6 1.8 2.7 1.8
25.0 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.9 2.4 1.8 2.5 1.8 2.7 1.8
27.5 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
20 30.0 2.0 1.7 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.7 1.8
(2.2) 32.5 2.0 1.7 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
35.0 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
37.5 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
40.0 1.9 1.6 1.9 1.7 2.1 1.7 2.2 1.8 2.2 1.8 2.4 1.8 2.6 1.8
43.0 1.9 1.6 1.9 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.8 2.5 1.8
20.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
22.5 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
25.0 2.6 2.0 2.7 2.0 2.9 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.5 2.1
27.5 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.1
25 30.0 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
37.5 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.1 2.0 3.3 2.0
40.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
43.0 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
20.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.5 2.5
22.5 3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.5
25.0 3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.5 4.4 2.5
27.5 3.3 2.4 3.4 2.4 3.6 2.4 3.8 2.6 3.9 2.5 4.1 2.5 4.4 2.5
32 30.0 3.3 2.4 3.3 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.4 2.5
(3.6) 32.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.3 2.5
35.0 3.2 2.3 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.5 4.0 2.5 4.3 2.5
37.5 3.2 2.3 3.2 2.3 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.4
40.0 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.5 3.7 2.5 3.9 2.4 4.2 2.4
43.0 3.1 2.3 3.1 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.9 2.4 4.2 2.4
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 99
1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMS1(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
22.5 1.6 1.5 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
25.0 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.6
27.5 1.6 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.6
15 30.0 1.5 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.1 1.6
(1.7) 32.5 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
35.0 1.5 1.4 1.5 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
37.5 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
40.0 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.9 1.6 2.0 1.5
43.0 1.5 1.4 1.5 1.4 1.6 1.4 1.7 1.6 1.7 1.6 1.8 1.5 2.0 1.5
20.0 2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.4 2.0 2.6 1.9 2.8 1.9
22.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 2.0 2.4 1.9 2.6 1.9 2.7 1.9
25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.7 1.9
(2.2) 32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
40.0 1.9 1.7 1.9 1.8 2.1 1.7 2.2 1.9 2.2 1.9 2.4 1.9 2.6 1.8
43.0 1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.9 2.5 1.8
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.5 2.2
27.5 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
43.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
20.0 3.4 2.6 3.5 2.7 3.7 2.6 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.7
22.5 3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.8 4.0 2.8 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.7
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.8 2.7 4.0 2.7 4.3 2.6
37.5 3.2 2.5 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.7 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.3 3.3 5.6 3.3
25.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.9 3.3 5.2 3.3 5.6 3.3
27.5 4.1 3.1 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.1 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.3 5.1 3.3 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.7 3.3 5.0 3.2 5.4 3.2
37.5 4.0 3.0 4.0 3.1 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.2
40.0 3.9 3.0 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.2 5.3 3.2
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.9 3.2 5.2 3.1
20.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.1 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.1 7.0 4.0
25.0 5.2 3.8 5.3 3.9 5.7 3.9 5.9 4.1 6.1 4.1 6.5 4.0 6.9 4.0
27.5 5.1 3.8 5.3 3.9 5.6 3.8 5.8 4.1 6.0 4.0 6.4 4.0 6.9 4.0
50 30.0 5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.8 5.5 3.8 5.7 4.0 5.9 4.0 6.3 4.0 6.7 3.9
35.0 5.0 3.7 5.1 3.8 5.4 3.8 5.6 4.0 5.8 4.0 6.2 3.9 6.7 3.9
37.5 4.9 3.7 5.0 3.7 5.4 3.7 5.6 4.0 5.8 3.9 6.2 3.9 6.6 3.9
40.0 4.9 3.6 4.9 3.7 5.3 3.7 5.5 3.9 5.7 3.9 6.1 3.9 6.5 3.8
43.0 4.8 3.6 4.9 3.7 5.2 3.7 5.4 3.9 5.6 3.9 6.0 3.9 6.5 3.8
20.0 6.7 4.9 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.2 8.9 5.1
22.5 6.6 4.8 6.8 4.9 7.3 4.9 7.6 5.2 7.8 5.2 8.3 5.1 8.8 5.1
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.8 5.0
27.5 6.5 4.8 6.7 4.9 7.2 4.8 7.4 5.1 7.6 5.1 8.2 5.1 8.7 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.0 8.0 5.0 8.5 4.9
35.0 6.3 4.7 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 7.9 5.0 8.5 4.9
37.5 6.2 4.6 6.3 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 5.0 7.2 4.9 7.8 4.9 8.3 4.9
43.0 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.1 4.9 7.7 4.9 8.2 4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 100


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
1-4. Cooling capacity with PUHY-RP700-800YSJM
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.3 4.5 3.4 4.8 3.4 5.0 3.6 5.2 3.6 5.5 3.6 5.9 3.5
22.5 4.3 3.3 4.4 3.4 4.7 3.4 4.9 3.6 5.1 3.5 5.4 3.5 5.8 3.5
25.0 4.2 3.2 4.3 3.3 4.7 3.3 4.8 3.5 5.0 3.5 5.3 3.5 5.7 3.4
27.5 4.1 3.2 4.3 3.3 4.6 3.3 4.7 3.5 4.9 3.5 5.2 3.4 5.6 3.4
40 30.0 4.1 3.1 4.2 3.3 4.5 3.2 4.7 3.5 4.8 3.4 5.1 3.4 5.5 3.4
(4.5) 32.5 4.0 3.1 4.1 3.2 4.4 3.2 4.6 3.4 4.7 3.4 5.0 3.4 5.4 3.3
35.0 3.9 3.1 4.0 3.2 4.3 3.2 4.5 3.4 4.6 3.4 4.9 3.3 5.3 3.3
37.5 3.8 3.0 4.0 3.1 4.2 3.1 4.4 3.3 4.5 3.3 4.8 3.3 5.2 3.3
40.0 3.8 3.0 3.9 3.1 4.2 3.1 4.3 3.3 4.5 3.3 4.8 3.3 5.1 3.2
43.0 3.7 3.0 3.8 3.1 4.1 3.1 4.2 3.3 4.3 3.3 4.6 3.2 4.9 3.2
20.0 5.4 3.9 5.6 4.0 6.0 4.0 6.2 4.2 6.4 4.2 6.9 4.1 7.3 4.1
22.5 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.3 4.1 6.7 4.1 7.2 4.0
25.0 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
27.5 5.1 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
50 30.0 5.0 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.8 3.9
(5.6) 32.5 5.0 3.6 5.1 3.7 5.5 3.7 5.7 3.9 5.9 3.9 6.3 3.9 6.7 3.8
35.0 4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.8 6.5 3.8
37.5 4.8 3.5 4.9 3.6 5.3 3.6 5.5 3.8 5.7 3.8 6.0 3.8 6.4 3.7
40.0 4.7 3.5 4.8 3.6 5.2 3.6 5.4 3.8 5.5 3.8 5.9 3.8 6.3 3.7
43.0 4.6 3.4 4.7 3.5 5.1 3.5 5.2 3.7 5.4 3.7 5.8 3.7 6.1 3.6
20.0 6.9 5.1 7.1 5.2 7.6 5.2 7.9 5.5 8.2 5.5 8.7 5.5 9.3 5.4
22.5 6.7 5.0 7.0 5.2 7.5 5.2 7.8 5.5 8.0 5.4 8.6 5.4 9.1 5.3
25.0 6.6 5.0 6.9 5.1 7.4 5.1 7.6 5.4 7.9 5.4 8.4 5.3 8.9 5.3
27.5 6.5 4.9 6.7 5.0 7.2 5.0 7.5 5.3 7.7 5.3 8.3 5.3 8.8 5.2
63 30.0 6.4 4.8 6.6 5.0 7.1 5.0 7.3 5.3 7.6 5.3 8.1 5.2 8.6 5.1
(7.1) 32.5 6.3 4.8 6.5 4.9 7.0 4.9 7.2 5.2 7.5 5.2 7.9 5.2 8.5 5.1
35.0 6.2 4.7 6.4 4.9 6.8 4.9 7.1 5.2 7.3 5.1 7.8 5.1 8.3 5.0
37.5 6.1 4.7 6.2 4.8 6.7 4.8 6.9 5.1 7.2 5.1 7.6 5.0 8.1 5.0
40.0 5.9 4.6 6.1 4.8 6.6 4.7 6.8 5.1 7.0 5.0 7.5 5.0 8.0 4.9
43.0 5.8 4.5 6.0 4.7 6.4 4.7 6.6 5.0 6.9 5.0 7.3 4.9 7.8 4.9
20.0 7.7 5.7 8.0 5.8 8.6 5.8 8.9 6.2 9.2 6.1 9.8 6.1 10.4 6.0
22.5 7.6 5.6 7.9 5.8 8.4 5.8 8.7 6.1 9.0 6.1 9.6 6.0 10.3 5.9
25.0 7.5 5.5 7.7 5.7 8.3 5.7 8.6 6.0 8.9 6.0 9.5 6.0 10.1 5.9
27.5 7.3 5.5 7.6 5.6 8.1 5.6 8.4 6.0 8.7 5.9 9.3 5.9 9.9 5.8
71 30.0 7.2 5.4 7.4 5.6 8.0 5.6 8.3 5.9 8.6 5.9 9.1 5.8 9.7 5.7
(8.0) 32.5 7.1 5.3 7.3 5.5 7.8 5.5 8.1 5.8 8.4 5.8 9.0 5.8 9.5 5.7
35.0 6.9 5.3 7.2 5.4 7.7 5.4 8.0 5.8 8.2 5.7 8.8 5.7 9.3 5.6
37.5 6.8 5.2 7.0 5.4 7.5 5.4 7.8 5.7 8.1 5.7 8.6 5.6 9.2 5.5
40.0 6.7 5.1 6.9 5.3 7.4 5.3 7.7 5.6 7.9 5.6 8.4 5.6 9.0 5.5
43.0 6.5 5.1 6.7 5.2 7.2 5.2 7.5 5.6 7.7 5.5 8.2 5.5 8.8 5.4
20.0 8.7 6.4 9.0 6.6 9.7 6.6 10.0 7.0 10.3 7.0 11.0 6.9 11.7 6.8
22.5 8.5 6.3 8.9 6.5 9.5 6.5 9.8 6.9 10.2 6.9 10.8 6.8 11.5 6.7
25.0 8.4 6.3 8.7 6.5 9.3 6.4 9.7 6.8 10.0 6.8 10.6 6.7 11.3 6.6
27.5 8.3 6.2 8.5 6.4 9.2 6.4 9.5 6.8 9.8 6.7 10.5 6.7 11.1 6.6
80 30.0 8.1 6.1 8.4 6.3 9.0 6.3 9.3 6.7 9.6 6.7 10.3 6.6 10.9 6.5
(9.0) 32.5 8.0 6.0 8.2 6.2 8.8 6.2 9.1 6.6 9.4 6.6 10.1 6.5 10.7 6.4
35.0 7.8 6.0 8.1 6.2 8.7 6.1 9.0 6.5 9.3 6.5 9.9 6.4 10.5 6.4
37.5 7.7 5.9 7.9 6.1 8.5 6.1 8.8 6.5 9.1 6.4 9.7 6.4 10.3 6.3
40.0 7.5 5.8 7.7 6.0 8.3 6.0 8.6 6.4 8.9 6.4 9.5 6.3 10.1 6.2
43.0 7.4 5.7 7.6 5.9 8.1 5.9 8.4 6.3 8.7 6.3 9.3 6.2 9.9 6.1
20.0 10.8 8.6 11.2 8.9 12.0 8.9 12.5 9.5 12.9 9.4 13.7 9.3 14.6 9.2
22.5 10.6 8.5 11.0 8.8 11.8 8.8 12.2 9.4 12.6 9.4 13.5 9.3 14.4 9.1
25.0 10.5 8.4 10.8 8.7 11.6 8.7 12.0 9.3 12.4 9.3 13.3 9.2 14.1 9.1
27.5 10.3 8.3 10.6 8.6 11.4 8.6 11.8 9.2 12.2 9.2 13.0 9.1 13.8 9.0
100 30.0 10.1 8.3 10.4 8.6 11.2 8.5 11.6 9.1 12.0 9.1 12.8 9.0 13.6 8.9
(11.2) 32.5 9.9 8.2 10.2 8.5 11.0 8.4 11.4 9.0 11.8 9.0 12.5 8.9 13.3 8.8
35.0 9.7 8.1 10.0 8.4 10.8 8.3 11.2 9.0 11.5 8.9 12.3 8.8 13.1 8.7
37.5 9.5 8.0 9.8 8.3 10.6 8.3 10.9 8.9 11.3 8.8 12.1 8.7 12.8 8.6
40.0 9.4 7.9 9.6 8.2 10.4 8.2 10.7 8.8 11.1 8.7 11.8 8.7 12.6 8.5
43.0 9.2 7.8 9.4 8.1 10.1 8.1 10.5 8.7 10.8 8.6 11.5 8.6 12.3 8.4
20.0 13.5 9.9 14.0 10.3 15.0 10.2 15.6 10.8 16.1 10.8 17.2 10.7 18.3 10.5
22.5 13.3 9.8 13.8 10.1 14.8 10.1 15.3 10.7 15.8 10.7 16.9 10.6 17.9 10.4
25.0 13.1 9.7 13.5 10.0 14.5 10.0 15.0 10.6 15.5 10.6 16.6 10.4 17.6 10.3
27.5 12.8 9.6 13.3 9.9 14.3 9.9 14.8 10.5 15.3 10.4 16.3 10.3 17.3 10.2
125 30.0 12.6 9.5 13.0 9.8 14.0 9.7 14.5 10.4 15.0 10.3 16.0 10.2 17.0 10.1
(14.0) 32.5 12.4 9.4 12.8 9.7 13.7 9.6 14.2 10.2 14.7 10.2 15.7 10.1 16.7 10.0
35.0 12.2 9.3 12.5 9.5 13.5 9.5 14.0 10.1 14.4 10.1 15.4 10.0 16.4 9.9
37.5 11.9 9.1 12.3 9.4 13.2 9.4 13.7 10.0 14.1 10.0 15.1 9.9 16.0 9.7
40.0 11.7 9.0 12.1 9.3 12.9 9.3 13.4 9.9 13.9 9.9 14.8 9.8 15.7 9.6
43.0 11.4 8.9 11.8 9.2 12.6 9.1 13.1 9.7 13.5 9.7 14.4 9.6 15.4 9.5
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 101


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 15.5 11.4 16.0 11.7 17.2 11.7 17.8 12.4 18.4 12.3 19.6 12.2 20.9 12.1
22.5 15.2 11.2 15.7 11.6 16.9 11.6 17.5 12.2 18.1 12.2 19.3 12.1 20.5 11.9
25.0 14.9 11.1 15.5 11.4 16.6 11.4 17.2 12.1 17.8 12.1 18.9 11.9 20.1 11.8
27.5 14.7 11.0 15.2 11.3 16.3 11.3 16.9 12.0 17.4 11.9 18.6 11.8 19.8 11.7
140 30.0 14.4 10.8 14.9 11.2 16.0 11.1 16.6 11.8 17.1 11.8 18.3 11.7 19.4 11.5
(16.0) 32.5 14.2 10.7 14.6 11.0 15.7 11.0 16.2 11.7 16.8 11.7 17.9 11.5 19.1 11.4
35.0 13.9 10.6 14.3 10.9 15.4 10.9 16.0 11.6 16.5 11.5 17.6 11.4 18.7 11.3
37.5 13.6 10.5 14.1 10.8 15.1 10.7 15.6 11.4 16.2 11.4 17.2 11.3 18.3 11.1
40.0 13.4 10.3 13.8 10.6 14.8 10.6 15.3 11.3 15.8 11.3 16.9 11.2 18.0 11.0
43.0 13.1 10.2 13.4 10.5 14.4 10.5 14.9 11.1 15.5 11.1 16.5 11.0 17.6 10.9
20.0 21.6 16.3 22.4 16.8 24.1 16.7 24.9 17.8 25.7 17.7 27.5 17.5 29.2 17.3
22.5 21.3 16.1 22.0 16.6 23.6 16.6 24.5 17.6 25.3 17.5 27.0 17.4 28.7 17.1
25.0 20.9 15.9 21.6 16.4 23.2 16.4 24.0 17.4 24.9 17.3 26.5 17.2 28.2 16.9
27.5 20.5 15.7 21.3 16.2 22.8 16.2 23.6 17.2 24.4 17.2 26.0 17.0 27.7 16.8
200 30.0 20.2 15.5 20.9 16.1 22.4 16.0 23.2 17.0 24.0 17.0 25.6 16.8 27.2 16.6
(22.4) 32.5 19.8 15.4 20.5 15.9 22.0 15.8 22.7 16.9 23.5 16.8 25.1 16.6 26.7 16.4
35.0 19.5 15.2 20.1 15.7 21.5 15.6 22.4 16.7 23.1 16.6 24.6 16.4 26.2 16.2
37.5 19.1 15.0 19.7 15.5 21.1 15.5 21.9 16.5 22.6 16.4 24.1 16.3 25.7 16.1
40.0 18.7 14.9 19.3 15.3 20.7 15.3 21.4 16.3 22.2 16.2 23.7 16.1 25.2 15.9
43.0 18.3 14.6 18.8 15.1 20.2 15.1 20.9 16.1 21.6 16.0 23.1 15.9 24.6 15.7
20.0 27.0 20.2 28.0 20.9 30.1 20.8 31.1 22.1 32.2 22.0 34.3 21.8 36.5 21.5
22.5 26.6 20.0 27.5 20.7 29.6 20.6 30.6 21.9 31.6 21.8 33.7 21.6 35.9 21.3
25.0 26.1 19.8 27.1 20.4 29.0 20.4 30.0 21.6 31.1 21.5 33.1 21.3 35.2 21.1
27.5 25.7 19.5 26.6 20.2 28.5 20.1 29.5 21.4 30.5 21.3 32.5 21.1 34.6 20.8
250 30.0 25.2 19.3 26.1 19.9 28.0 19.9 29.0 21.2 29.9 21.1 31.9 20.9 34.0 20.6
(28.0) 32.5 24.8 19.1 25.6 19.7 27.5 19.7 28.4 20.9 29.4 20.9 31.4 20.6 33.4 20.4
35.0 24.3 18.9 25.1 19.5 26.9 19.4 28.0 20.7 28.8 20.6 30.8 20.4 32.7 20.2
37.5 23.9 18.7 24.6 19.3 26.4 19.2 27.3 20.5 28.3 20.4 30.2 20.2 32.1 19.9
40.0 23.4 18.5 24.1 19.0 25.9 19.0 26.8 20.2 27.7 20.2 29.6 20.0 31.5 19.7
43.0 22.9 18.2 23.5 18.8 25.3 18.7 26.2 20.0 27.0 19.9 28.9 19.7 30.7 19.5
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 102


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMR-E-L/R CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.8 2.4 1.8 2.4 1.9 2.5 1.9 2.7 1.9 2.9 1.9
22.5 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.9 2.8 1.8
25.0 2.1 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
27.5 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.9 2.4 1.9 2.6 1.8 2.7 1.8
20 30.0 2.0 1.7 2.0 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
(2.2) 32.5 1.9 1.6 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
35.0 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
37.5 1.9 1.6 1.9 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.8 2.5 1.7
40.0 1.8 1.6 1.9 1.7 2.0 1.6 2.1 1.8 2.2 1.8 2.3 1.7 2.5 1.7
43.0 1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.8 2.1 1.7 2.3 1.7 2.4 1.7
20.0 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.2 3.7 2.1
22.5 2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.2 3.2 2.2 3.4 2.1 3.6 2.1
25.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
27.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
25 30.0 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
35.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.1 2.0 3.3 2.0
37.5 2.4 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
40.0 2.3 1.8 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.0
43.0 2.3 1.8 2.4 1.9 2.5 1.9 2.6 2.0 2.7 2.0 2.9 2.0 3.1 1.9
20.0 3.5 2.5 3.6 2.5 3.9 2.5 4.0 2.7 4.1 2.7 4.4 2.6 4.7 2.6
22.5 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.1 2.6 4.3 2.6 4.6 2.6
25.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.5 2.5
27.5 3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.5 4.5 2.5
32 30.0 3.2 2.3 3.4 2.4 3.6 2.4 3.7 2.5 3.9 2.5 4.1 2.5 4.4 2.5
(3.6) 32.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.3 2.5
35.0 3.1 2.3 3.2 2.4 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.4
37.5 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.5 3.6 2.4 3.9 2.4 4.1 2.4
40.0 3.0 2.2 3.1 2.3 3.3 2.3 3.4 2.4 3.6 2.4 3.8 2.4 4.0 2.4
43.0 2.9 2.2 3.0 2.3 3.2 2.2 3.4 2.4 3.5 2.4 3.7 2.4 3.9 2.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 103


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMS1(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.5 1.7 1.5 1.8 1.5 1.9 1.7 2.0 1.6 2.1 1.6 2.2 1.6
22.5 1.6 1.5 1.7 1.5 1.8 1.5 1.9 1.6 1.9 1.6 2.0 1.6 2.2 1.6
25.0 1.6 1.5 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
27.5 1.6 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
15 30.0 1.5 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.1 1.6
(1.7) 32.5 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
35.0 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
37.5 1.4 1.4 1.5 1.5 1.6 1.4 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5
40.0 1.4 1.4 1.5 1.4 1.6 1.4 1.6 1.6 1.7 1.5 1.8 1.5 1.9 1.5
43.0 1.4 1.4 1.4 1.4 1.5 1.4 1.6 1.5 1.6 1.5 1.8 1.5 1.9 1.5
20.0 2.1 1.8 2.2 1.9 2.4 1.9 2.4 2.0 2.5 2.0 2.7 2.0 2.9 1.9
22.5 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
25.0 2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.4 2.0 2.6 1.9 2.8 1.9
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9 2.7 1.9
20 30.0 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
(2.2) 32.5 1.9 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
37.5 1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.9 2.5 1.8
40.0 1.8 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.2 1.9 2.3 1.8 2.5 1.8
43.0 1.8 1.6 1.8 1.7 2.0 1.7 2.1 1.8 2.1 1.8 2.3 1.8 2.4 1.8
20.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.7 2.3
22.5 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.3 3.4 2.3 3.6 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.3 2.9 2.3 3.1 2.2 3.3 2.2
35.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
40.0 2.3 2.0 2.4 2.1 2.6 2.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.1
43.0 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.2 2.9 2.1 3.1 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.9 4.1 2.8 4.4 2.8 4.7 2.8
22.5 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.1 2.8 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.7
27.5 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.5 2.7
32 30.0 3.2 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.7 4.3 2.6
35.0 3.1 2.4 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.6 4.2 2.6
37.5 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.6 3.9 2.6 4.1 2.6
40.0 3.0 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.6 4.0 2.6
43.0 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.6 3.5 2.6 3.7 2.6 3.9 2.5
20.0 4.3 3.2 4.5 3.3 4.8 3.3 5.0 3.5 5.2 3.5 5.5 3.4 5.9 3.4
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.1 3.4 5.4 3.4 5.8 3.3
25.0 4.2 3.1 4.3 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
27.5 4.1 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.9 3.3 5.2 3.3 5.6 3.3
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.3 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.4 3.2
35.0 3.9 3.0 4.0 3.1 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.3 3.2
37.5 3.8 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.8 3.2 5.2 3.1
40.0 3.8 2.9 3.9 3.0 4.2 3.0 4.3 3.2 4.5 3.2 4.8 3.1 5.1 3.1
43.0 3.7 2.9 3.8 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.6 3.1 4.9 3.0
20.0 5.4 3.9 5.6 4.0 6.0 4.0 6.2 4.2 6.4 4.2 6.9 4.2 7.3 4.1
22.5 5.3 3.9 5.5 4.0 5.9 4.0 6.1 4.2 6.3 4.2 6.7 4.1 7.2 4.1
25.0 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.1 7.0 4.0
27.5 5.1 3.8 5.3 3.9 5.7 3.9 5.9 4.1 6.1 4.1 6.5 4.0 6.9 4.0
50 30.0 5.0 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.8 5.5 3.8 5.7 4.0 5.9 4.0 6.3 3.9 6.7 3.9
35.0 4.9 3.6 5.0 3.7 5.4 3.7 5.6 4.0 5.8 3.9 6.2 3.9 6.5 3.8
37.5 4.8 3.6 4.9 3.7 5.3 3.7 5.5 3.9 5.7 3.9 6.0 3.9 6.4 3.8
40.0 4.7 3.5 4.8 3.6 5.2 3.6 5.4 3.9 5.5 3.8 5.9 3.8 6.3 3.8
43.0 4.6 3.5 4.7 3.6 5.1 3.6 5.2 3.8 5.4 3.8 5.8 3.8 6.1 3.7
20.0 6.9 4.9 7.1 5.1 7.6 5.1 7.9 5.4 8.2 5.3 8.7 5.3 9.3 5.2
22.5 6.7 4.9 7.0 5.0 7.5 5.0 7.8 5.3 8.0 5.3 8.6 5.2 9.1 5.2
25.0 6.6 4.8 6.9 5.0 7.4 4.9 7.6 5.2 7.9 5.2 8.4 5.2 8.9 5.1
27.5 6.5 4.8 6.7 4.9 7.2 4.9 7.5 5.2 7.7 5.2 8.3 5.1 8.8 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.3 4.6 6.5 4.8 7.0 4.8 7.2 5.0 7.5 5.0 7.9 5.0 8.5 4.9
35.0 6.2 4.6 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.3 4.9
37.5 6.1 4.5 6.2 4.7 6.7 4.6 6.9 4.9 7.2 4.9 7.6 4.9 8.1 4.8
40.0 5.9 4.5 6.1 4.6 6.6 4.6 6.8 4.9 7.0 4.9 7.5 4.8 8.0 4.7
43.0 5.8 4.4 6.0 4.5 6.4 4.5 6.6 4.8 6.9 4.8 7.3 4.7 7.8 4.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 104


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
1-5. Cooling capacity with PUHY-RP850-900YSJM
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.2 4.4 3.3 4.7 3.3 4.8 3.5 5.0 3.5 5.3 3.5 5.7 3.4
22.5 4.2 3.2 4.3 3.3 4.6 3.3 4.8 3.5 4.9 3.5 5.3 3.5 5.6 3.4
25.0 4.2 3.2 4.3 3.3 4.6 3.3 4.7 3.5 4.9 3.5 5.2 3.4 5.6 3.4
27.5 4.1 3.2 4.2 3.3 4.5 3.3 4.7 3.5 4.8 3.5 5.2 3.4 5.5 3.4
40 30.0 4.1 3.2 4.2 3.2 4.5 3.2 4.6 3.4 4.8 3.4 5.1 3.4 5.5 3.4
(4.5) 32.5 4.0 3.1 4.1 3.2 4.4 3.2 4.6 3.4 4.7 3.4 5.1 3.4 5.4 3.3
35.0 4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.4 4.7 3.4 5.0 3.4 5.4 3.3
37.5 4.0 3.1 4.0 3.2 4.3 3.2 4.5 3.4 4.6 3.4 5.0 3.3 5.3 3.3
40.0 3.9 3.1 4.0 3.1 4.3 3.1 4.4 3.4 4.6 3.3 4.9 3.3 5.3 3.3
43.0 3.9 3.1 3.9 3.1 4.2 3.1 4.4 3.3 4.5 3.3 4.9 3.3 5.2 3.3
20.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
25.0 5.2 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.9 3.9
50 30.0 5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.7 5.5 3.7 5.7 4.0 5.9 3.9 6.3 3.9 6.7 3.9
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.7 3.8
37.5 4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.6 3.8
40.0 4.9 3.6 4.9 3.6 5.3 3.6 5.5 3.9 5.7 3.9 6.1 3.8 6.5 3.8
43.0 4.8 3.6 4.9 3.6 5.2 3.6 5.4 3.8 5.6 3.8 6.0 3.8 6.5 3.8
20.0 6.7 5.0 6.9 5.1 7.4 5.1 7.6 5.4 7.9 5.4 8.4 5.3 8.9 5.3
22.5 6.6 5.0 6.8 5.1 7.3 5.1 7.6 5.4 7.8 5.4 8.3 5.3 8.8 5.2
25.0 6.6 4.9 6.8 5.1 7.2 5.0 7.5 5.3 7.7 5.3 8.2 5.3 8.8 5.2
27.5 6.5 4.9 6.7 5.0 7.2 5.0 7.4 5.3 7.6 5.3 8.2 5.2 8.7 5.2
63 30.0 6.4 4.9 6.6 5.0 7.1 5.0 7.3 5.3 7.6 5.3 8.1 5.2 8.6 5.1
(7.1) 32.5 6.4 4.8 6.5 4.9 7.0 4.9 7.2 5.2 7.5 5.2 8.0 5.2 8.5 5.1
35.0 6.3 4.8 6.4 4.9 6.9 4.9 7.1 5.2 7.4 5.2 7.9 5.1 8.5 5.1
37.5 6.2 4.8 6.3 4.9 6.8 4.9 7.1 5.2 7.3 5.2 7.8 5.1 8.4 5.1
40.0 6.2 4.7 6.3 4.8 6.7 4.8 7.0 5.1 7.2 5.1 7.8 5.1 8.3 5.0
43.0 6.1 4.7 6.2 4.8 6.7 4.8 6.9 5.1 7.1 5.1 7.7 5.0 8.2 5.0
20.0 7.6 5.6 7.8 5.7 8.3 5.7 8.6 6.0 8.9 6.0 9.4 5.9 10.0 5.9
22.5 7.5 5.5 7.7 5.7 8.2 5.7 8.5 6.0 8.8 6.0 9.4 5.9 10.0 5.8
25.0 7.4 5.5 7.6 5.6 8.1 5.6 8.4 6.0 8.7 5.9 9.3 5.9 9.9 5.8
27.5 7.3 5.5 7.5 5.6 8.1 5.6 8.3 5.9 8.6 5.9 9.2 5.8 9.8 5.8
71 30.0 7.3 5.4 7.4 5.6 8.0 5.5 8.2 5.9 8.5 5.9 9.1 5.8 9.7 5.7
(8.0) 32.5 7.2 5.4 7.3 5.5 7.9 5.5 8.2 5.8 8.4 5.8 9.0 5.8 9.6 5.7
35.0 7.1 5.4 7.2 5.5 7.8 5.5 8.0 5.8 8.3 5.8 8.9 5.7 9.5 5.7
37.5 7.0 5.3 7.2 5.4 7.7 5.4 8.0 5.8 8.3 5.7 8.8 5.7 9.4 5.6
40.0 7.0 5.3 7.1 5.4 7.6 5.4 7.9 5.7 8.2 5.7 8.7 5.7 9.4 5.6
43.0 6.9 5.2 7.0 5.3 7.5 5.3 7.8 5.7 8.1 5.7 8.6 5.6 9.2 5.6
20.0 8.5 6.3 8.8 6.5 9.4 6.5 9.7 6.8 10.0 6.8 10.6 6.7 11.3 6.6
22.5 8.4 6.3 8.7 6.4 9.3 6.4 9.6 6.8 9.9 6.8 10.5 6.7 11.2 6.6
25.0 8.3 6.2 8.6 6.4 9.2 6.4 9.5 6.8 9.8 6.7 10.4 6.7 11.1 6.6
27.5 8.3 6.2 8.5 6.3 9.1 6.3 9.4 6.7 9.7 6.7 10.3 6.6 11.0 6.5
80 30.0 8.2 6.1 8.4 6.3 9.0 6.3 9.3 6.7 9.6 6.6 10.2 6.6 10.9 6.5
(9.0) 32.5 8.1 6.1 8.3 6.2 8.9 6.2 9.2 6.6 9.5 6.6 10.1 6.5 10.8 6.5
35.0 8.0 6.1 8.1 6.2 8.8 6.2 9.0 6.5 9.4 6.6 10.0 6.5 10.7 6.4
37.5 7.9 6.0 8.0 6.1 8.7 6.1 9.0 6.5 9.3 6.5 9.9 6.5 10.6 6.4
40.0 7.8 6.0 7.9 6.1 8.6 6.1 8.9 6.5 9.2 6.5 9.8 6.4 10.5 6.4
43.0 7.7 5.9 7.8 6.0 8.4 6.0 8.7 6.4 9.1 6.4 9.7 6.4 10.4 6.3
20.0 10.6 8.5 10.9 8.8 11.7 8.7 12.0 9.3 12.4 9.3 13.2 9.2 14.1 9.0
22.5 10.5 8.4 10.8 8.7 11.5 8.7 11.9 9.3 12.3 9.2 13.1 9.1 13.9 9.0
25.0 10.4 8.4 10.6 8.7 11.4 8.6 11.8 9.2 12.2 9.2 13.0 9.1 13.8 9.0
27.5 10.3 8.3 10.5 8.6 11.3 8.6 11.7 9.2 12.1 9.1 12.9 9.0 13.7 8.9
100 30.0 10.2 8.3 10.4 8.5 11.2 8.5 11.5 9.1 11.9 9.1 12.7 9.0 13.6 8.9
(11.2) 32.5 10.1 8.2 10.3 8.5 11.0 8.5 11.4 9.0 11.8 9.0 12.6 8.9 13.5 8.8
35.0 9.9 8.2 10.1 8.4 10.9 8.4 11.2 9.0 11.7 9.0 12.5 8.9 13.3 8.8
37.5 9.8 8.1 10.0 8.4 10.8 8.3 11.2 8.9 11.6 8.9 12.4 8.8 13.2 8.8
40.0 9.7 8.1 9.9 8.3 10.6 8.3 11.0 8.9 11.4 8.9 12.2 8.8 13.1 8.7
43.0 9.6 8.0 9.7 8.2 10.5 8.2 10.9 8.8 11.3 8.8 12.1 8.7 12.9 8.7
20.0 13.2 9.8 13.6 10.1 14.6 10.0 15.1 10.6 15.5 10.6 16.5 10.4 17.6 10.3
22.5 13.1 9.7 13.5 10.0 14.4 9.9 14.9 10.5 15.4 10.5 16.4 10.4 17.4 10.2
25.0 13.0 9.7 13.3 9.9 14.3 9.9 14.7 10.5 15.2 10.4 16.2 10.3 17.3 10.2
27.5 12.8 9.6 13.2 9.8 14.1 9.8 14.6 10.4 15.1 10.4 16.1 10.3 17.1 10.1
125 30.0 12.7 9.5 13.0 9.8 13.9 9.7 14.4 10.3 14.9 10.3 15.9 10.2 17.0 10.1
(14.0) 32.5 12.6 9.5 12.8 9.7 13.8 9.7 14.3 10.3 14.8 10.2 15.8 10.1 16.8 10.0
35.0 12.4 9.4 12.7 9.6 13.6 9.6 14.0 10.1 14.6 10.2 15.6 10.1 16.7 10.0
37.5 12.3 9.3 12.5 9.5 13.5 9.5 14.0 10.1 14.4 10.1 15.5 10.0 16.5 9.9
40.0 12.2 9.3 12.4 9.5 13.3 9.4 13.8 10.1 14.3 10.0 15.3 10.0 16.4 9.9
43.0 12.0 9.2 12.2 9.4 13.1 9.4 13.6 10.0 14.1 9.9 15.1 9.9 16.2 9.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 105


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMH-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 15.1 11.2 15.6 11.5 16.7 11.4 17.2 12.1 17.8 12.1 18.9 11.9 20.1 11.8
22.5 15.0 11.1 15.4 11.4 16.5 11.4 17.0 12.0 17.6 12.0 18.7 11.9 19.9 11.7
25.0 14.8 11.0 15.2 11.3 16.3 11.3 16.8 12.0 17.4 11.9 18.5 11.8 19.7 11.6
27.5 14.7 11.0 15.0 11.2 16.1 11.2 16.7 11.9 17.2 11.8 18.4 11.7 19.6 11.6
140 30.0 14.5 10.9 14.9 11.2 15.9 11.1 16.5 11.8 17.0 11.8 18.2 11.7 19.4 11.5
(16.0) 32.5 14.4 10.8 14.7 11.1 15.8 11.0 16.3 11.7 16.9 11.7 18.0 11.6 19.2 11.5
35.0 14.2 10.7 14.5 11.0 15.6 11.0 16.0 11.6 16.7 11.6 17.8 11.5 19.1 11.4
37.5 14.1 10.7 14.3 10.9 15.4 10.9 15.9 11.6 16.5 11.5 17.7 11.4 18.9 11.3
40.0 13.9 10.6 14.1 10.8 15.2 10.8 15.8 11.5 16.3 11.5 17.5 11.4 18.7 11.3
43.0 13.7 10.5 13.9 10.7 15.0 10.7 15.6 11.4 16.1 11.4 17.3 11.3 18.5 11.2
20.0 21.2 16.0 21.8 16.5 23.3 16.4 24.1 17.4 24.9 17.3 26.5 17.1 28.1 16.9
22.5 21.0 15.9 21.6 16.4 23.1 16.3 23.8 17.3 24.6 17.2 26.2 17.1 27.9 16.8
25.0 20.7 15.8 21.3 16.3 22.8 16.2 23.6 17.2 24.4 17.1 26.0 17.0 27.6 16.7
27.5 20.5 15.7 21.0 16.1 22.6 16.1 23.3 17.1 24.1 17.0 25.7 16.9 27.4 16.7
200 30.0 20.3 15.6 20.8 16.0 22.3 16.0 23.1 17.0 23.9 16.9 25.5 16.8 27.2 16.6
(22.4) 32.5 20.1 15.5 20.5 15.9 22.1 15.9 22.8 16.9 23.6 16.8 25.2 16.7 26.9 16.5
35.0 19.9 15.4 20.3 15.8 21.8 15.7 22.4 16.7 23.4 16.7 25.0 16.6 26.7 16.4
37.5 19.7 15.3 20.0 15.7 21.5 15.6 22.3 16.7 23.1 16.6 24.7 16.5 26.4 16.3
40.0 19.5 15.2 19.8 15.5 21.3 15.5 22.1 16.6 22.8 16.5 24.5 16.4 26.2 16.2
43.0 19.2 15.1 19.5 15.4 21.0 15.4 21.8 16.4 22.6 16.4 24.2 16.3 25.9 16.1
20.0 26.5 19.9 27.3 20.5 29.2 20.4 30.1 21.7 31.1 21.6 33.1 21.3 35.2 21.0
22.5 26.2 19.8 26.9 20.4 28.8 20.3 29.8 21.5 30.8 21.4 32.8 21.2 34.9 20.9
25.0 25.9 19.7 26.6 20.2 28.5 20.1 29.5 21.4 30.5 21.3 32.4 21.1 34.6 20.8
27.5 25.7 19.5 26.3 20.1 28.2 20.0 29.2 21.2 30.1 21.2 32.1 21.0 34.3 20.7
250 30.0 25.4 19.4 26.0 19.9 27.9 19.8 28.9 21.1 29.8 21.0 31.8 20.8 33.9 20.6
(28.0) 32.5 25.1 19.3 25.7 19.8 27.6 19.7 28.5 21.0 29.5 20.9 31.5 20.7 33.6 20.5
35.0 24.9 19.2 25.4 19.6 27.2 19.6 28.0 20.7 29.2 20.8 31.2 20.6 33.3 20.4
37.5 24.6 19.0 25.0 19.5 26.9 19.4 27.9 20.7 28.9 20.6 30.9 20.5 33.0 20.3
40.0 24.3 18.9 24.7 19.3 26.6 19.3 27.6 20.6 28.6 20.5 30.6 20.4 32.7 20.2
43.0 24.0 18.7 24.3 19.1 26.2 19.1 27.2 20.4 28.2 20.4 30.2 20.2 32.4 20.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 106


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMR-E-L/R CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.1 1.8 2.3 1.7 2.3 1.9 2.4 1.9 2.6 1.8 2.7 1.8
25.0 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.9 2.4 1.8 2.5 1.8 2.7 1.8
27.5 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
20 30.0 2.0 1.7 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.7 1.8
(2.2) 32.5 2.0 1.7 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
35.0 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
37.5 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
40.0 1.9 1.6 1.9 1.7 2.1 1.7 2.2 1.8 2.2 1.8 2.4 1.8 2.6 1.8
43.0 1.9 1.6 1.9 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.8 2.5 1.8
20.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
22.5 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
25.0 2.6 2.0 2.7 2.0 2.9 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.5 2.1
27.5 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.1
25 30.0 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
37.5 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.1 2.0 3.3 2.0
40.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
43.0 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
20.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.5 2.5
22.5 3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.5
25.0 3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.5 4.4 2.5
27.5 3.3 2.4 3.4 2.4 3.6 2.4 3.8 2.6 3.9 2.5 4.1 2.5 4.4 2.5
32 30.0 3.3 2.4 3.3 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.4 2.5
(3.6) 32.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.3 2.5
35.0 3.2 2.3 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.5 4.0 2.5 4.3 2.5
37.5 3.2 2.3 3.2 2.3 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.4
40.0 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.5 3.7 2.5 3.9 2.4 4.2 2.4
43.0 3.1 2.3 3.1 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.9 2.4 4.2 2.4
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 107


1. Cooling [Ceiling concealed (Silent/Slim/High static pressure type)]
PEFY-P-VMS1(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
22.5 1.6 1.5 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
25.0 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.6
27.5 1.6 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.6
15 30.0 1.5 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.1 1.6
(1.7) 32.5 1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
35.0 1.5 1.4 1.5 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
37.5 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
40.0 1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.9 1.6 2.0 1.5
43.0 1.5 1.4 1.5 1.4 1.6 1.4 1.7 1.6 1.7 1.6 1.8 1.5 2.0 1.5
20.0 2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.4 2.0 2.6 1.9 2.8 1.9
22.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 2.0 2.4 1.9 2.6 1.9 2.7 1.9
25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.7 1.9
(2.2) 32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
40.0 1.9 1.7 1.9 1.8 2.1 1.7 2.2 1.9 2.2 1.9 2.4 1.9 2.6 1.8
43.0 1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.9 2.5 1.8
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.5 2.2
27.5 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
43.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
20.0 3.4 2.6 3.5 2.7 3.7 2.6 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.7
22.5 3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.8 4.0 2.8 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.7
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.8 2.7 4.0 2.7 4.3 2.6
37.5 3.2 2.5 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.7 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.3 3.3 5.6 3.3
25.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.9 3.3 5.2 3.3 5.6 3.3
27.5 4.1 3.1 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.1 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.3 5.1 3.3 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.7 3.3 5.0 3.2 5.4 3.2
37.5 4.0 3.0 4.0 3.1 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.2
40.0 3.9 3.0 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.2 5.3 3.2
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.9 3.2 5.2 3.1
20.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.1 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.1 7.0 4.0
25.0 5.2 3.8 5.3 3.9 5.7 3.9 5.9 4.1 6.1 4.1 6.5 4.0 6.9 4.0
27.5 5.1 3.8 5.3 3.9 5.6 3.8 5.8 4.1 6.0 4.0 6.4 4.0 6.9 4.0
50 30.0 5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.8 5.5 3.8 5.7 4.0 5.9 4.0 6.3 4.0 6.7 3.9
35.0 5.0 3.7 5.1 3.8 5.4 3.8 5.6 4.0 5.8 4.0 6.2 3.9 6.7 3.9
37.5 4.9 3.7 5.0 3.7 5.4 3.7 5.6 4.0 5.8 3.9 6.2 3.9 6.6 3.9
40.0 4.9 3.6 4.9 3.7 5.3 3.7 5.5 3.9 5.7 3.9 6.1 3.9 6.5 3.8
43.0 4.8 3.6 4.9 3.7 5.2 3.7 5.4 3.9 5.6 3.9 6.0 3.9 6.5 3.8
20.0 6.7 4.9 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.2 8.9 5.1
22.5 6.6 4.8 6.8 4.9 7.3 4.9 7.6 5.2 7.8 5.2 8.3 5.1 8.8 5.1
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.8 5.0
27.5 6.5 4.8 6.7 4.9 7.2 4.8 7.4 5.1 7.6 5.1 8.2 5.1 8.7 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.0 8.0 5.0 8.5 4.9
35.0 6.3 4.7 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 7.9 5.0 8.5 4.9
37.5 6.2 4.6 6.3 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 5.0 7.2 4.9 7.8 4.9 8.3 4.9
43.0 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.1 4.9 7.7 4.9 8.2 4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 108


2. Cooling [Ceiling concealed (Middle static pressure type)]
2-1. Cooling capacity with PUHY,PURY-RP200-250YJM
2. Cooling [Ceiling concealed (Middle static pressure type)]

PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.0 2.6 2.0 2.8 2.0
22.5 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.0 2.6 2.0 2.8 2.0
25.0 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.4 2.0 2.6 2.0 2.7 2.0
27.5 2.1 1.9 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.5 2.0 2.6 2.0
(2.2) 32.5 2.0 1.8 2.1 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
35.0 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9 2.5 1.9
37.5 1.9 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.2 2.0 2.3 1.9 2.5 1.9
40.0 1.9 1.8 2.0 1.8 2.1 1.8 2.1 2.0 2.2 1.9 2.3 1.9 2.4 1.9
43.0 1.8 1.7 1.9 1.8 2.0 1.8 2.1 1.9 2.1 1.9 2.2 1.9 2.3 1.9
20.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
22.5 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
25.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
27.5 2.7 2.1 2.7 2.2 2.9 2.1 3.0 2.3 3.0 2.2 3.2 2.2 3.4 2.2
25 30.0 2.6 2.1 2.7 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.3 2.2
(2.8) 32.5 2.6 2.0 2.6 2.1 2.8 2.1 2.9 2.2 2.9 2.2 3.1 2.2 3.3 2.1
35.0 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1 3.2 2.1
37.5 2.5 2.0 2.5 2.1 2.7 2.0 2.8 2.2 2.8 2.2 3.0 2.1 3.1 2.1
40.0 2.4 2.0 2.5 2.0 2.6 2.0 2.7 2.2 2.8 2.1 2.9 2.1 3.1 2.1
43.0 2.4 2.0 2.4 2.0 2.6 2.0 2.6 2.1 2.7 2.1 2.8 2.1 3.0 2.0
20.0 3.4 2.5 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.6 2.7
22.5 3.4 2.5 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.6 2.7
25.0 3.4 2.5 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.7 4.2 2.7 4.5 2.7
27.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.5 3.7 2.7 3.8 2.6 4.0 2.6 4.2 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
37.5 3.2 2.4 3.3 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.8 2.5 4.0 2.5
40.0 3.1 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.6 2.6 3.7 2.5 3.9 2.5
43.0 3.0 2.4 3.1 2.4 3.3 2.4 3.4 2.5 3.5 2.5 3.6 2.5 3.8 2.4
20.0 4.3 3.4 4.4 3.6 4.7 3.5 4.9 3.8 5.0 3.7 5.3 3.7 5.7 3.7
22.5 4.3 3.4 4.4 3.6 4.7 3.5 4.9 3.8 5.0 3.7 5.3 3.7 5.7 3.7
25.0 4.3 3.4 4.4 3.6 4.7 3.5 4.9 3.8 5.0 3.7 5.3 3.7 5.6 3.6
27.5 4.3 3.4 4.4 3.5 4.6 3.5 4.8 3.7 4.9 3.7 5.2 3.6 5.5 3.6
40 30.0 4.2 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.8 3.7 5.1 3.6 5.4 3.5
(4.5) 32.5 4.1 3.3 4.2 3.5 4.5 3.4 4.6 3.6 4.7 3.6 5.0 3.6 5.3 3.5
35.0 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5
37.5 4.0 3.3 4.1 3.4 4.3 3.3 4.4 3.6 4.5 3.5 4.8 3.5 5.0 3.4
40.0 3.9 3.2 4.0 3.4 4.2 3.3 4.3 3.5 4.4 3.5 4.7 3.4 4.9 3.4
43.0 3.8 3.2 3.9 3.3 4.1 3.3 4.2 3.5 4.3 3.5 4.5 3.4 4.8 3.4
20.0 5.3 4.2 5.5 4.4 5.9 4.3 6.1 4.6 6.2 4.6 6.6 4.5 7.1 4.5
22.5 5.3 4.2 5.5 4.4 5.9 4.3 6.1 4.6 6.2 4.6 6.6 4.5 7.1 4.5
25.0 5.3 4.2 5.5 4.4 5.9 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
27.5 5.3 4.2 5.5 4.3 5.8 4.3 5.9 4.6 6.1 4.5 6.4 4.5 6.8 4.4
50 30.0 5.2 4.2 5.4 4.3 5.7 4.3 5.8 4.5 6.0 4.5 6.3 4.4 6.7 4.4
(5.6) 32.5 5.1 4.1 5.3 4.3 5.6 4.2 5.7 4.5 5.9 4.4 6.2 4.4 6.6 4.3
35.0 5.0 4.1 5.2 4.2 5.5 4.2 5.6 4.4 5.8 4.4 6.1 4.3 6.4 4.3
37.5 4.9 4.0 5.1 4.2 5.4 4.1 5.5 4.4 5.6 4.4 5.9 4.3 6.3 4.2
40.0 4.8 4.0 5.0 4.1 5.3 4.1 5.4 4.3 5.5 4.3 5.8 4.2 6.1 4.2
43.0 4.7 3.9 4.8 4.1 5.1 4.0 5.3 4.3 5.4 4.3 5.6 4.2 6.0 4.1
20.0 6.7 5.2 7.0 5.4 7.5 5.4 7.7 5.7 7.9 5.7 8.4 5.6 9.0 5.5
22.5 6.7 5.2 7.0 5.4 7.5 5.4 7.7 5.7 7.9 5.7 8.4 5.6 9.0 5.5
25.0 6.7 5.2 7.0 5.4 7.5 5.4 7.7 5.7 7.9 5.6 8.3 5.6 8.8 5.5
27.5 6.7 5.2 6.9 5.4 7.3 5.3 7.5 5.6 7.7 5.6 8.1 5.5 8.7 5.4
63 30.0 6.6 5.2 6.8 5.3 7.2 5.3 7.4 5.6 7.6 5.5 8.0 5.4 8.5 5.4
(7.1) 32.5 6.5 5.1 6.7 5.3 7.1 5.2 7.2 5.5 7.4 5.5 7.8 5.4 8.3 5.3
35.0 6.4 5.0 6.5 5.2 6.9 5.1 7.1 5.5 7.3 5.4 7.7 5.3 8.1 5.2
37.5 6.2 5.0 6.4 5.1 6.8 5.1 7.0 5.4 7.2 5.4 7.5 5.3 8.0 5.2
40.0 6.1 4.9 6.3 5.1 6.7 5.0 6.8 5.3 7.0 5.3 7.4 5.2 7.8 5.1
43.0 6.0 4.9 6.1 5.0 6.5 5.0 6.7 5.3 6.9 5.2 7.2 5.1 7.6 5.1
20.0 7.6 5.7 7.9 5.9 8.4 5.8 8.7 6.2 8.9 6.1 9.5 6.1 10.1 6.0
22.5 7.6 5.7 7.9 5.9 8.4 5.8 8.7 6.2 8.9 6.1 9.5 6.1 10.1 6.0
25.0 7.6 5.7 7.9 5.9 8.4 5.8 8.6 6.2 8.9 6.1 9.4 6.0 10.0 5.9
27.5 7.6 5.7 7.8 5.8 8.3 5.8 8.5 6.1 8.7 6.0 9.2 6.0 9.8 5.9
71 30.0 7.4 5.6 7.7 5.8 8.1 5.7 8.3 6.0 8.5 6.0 9.0 5.9 9.6 5.8
(8.0) 32.5 7.3 5.5 7.5 5.7 8.0 5.6 8.2 6.0 8.4 5.9 8.8 5.8 9.4 5.7
35.0 7.2 5.5 7.4 5.6 7.8 5.6 8.0 5.9 8.2 5.9 8.6 5.7 9.2 5.7
37.5 7.0 5.4 7.2 5.6 7.7 5.5 7.9 5.8 8.1 5.8 8.5 5.7 9.0 5.6
40.0 6.9 5.3 7.1 5.5 7.5 5.4 7.7 5.8 7.9 5.7 8.3 5.6 8.8 5.5
43.0 6.7 5.3 6.9 5.4 7.3 5.4 7.5 5.7 7.7 5.7 8.1 5.5 8.5 5.4
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 109


2. Cooling [Ceiling concealed (Middle static pressure type)]
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.6 6.1 8.9 6.3 9.5 6.3 9.7 6.6 10.0 6.6 10.6 6.5 11.4 6.4
22.5 8.6 6.1 8.9 6.3 9.5 6.3 9.7 6.6 10.0 6.6 10.6 6.5 11.4 6.4
25.0 8.6 6.1 8.9 6.3 9.5 6.3 9.7 6.6 10.0 6.5 10.5 6.4 11.2 6.4
27.5 8.5 6.1 8.8 6.3 9.3 6.2 9.5 6.5 9.8 6.5 10.3 6.4 11.0 6.3
80 30.0 8.4 6.0 8.6 6.2 9.1 6.1 9.4 6.4 9.6 6.4 10.1 6.3 10.8 6.2
(9.0) 32.5 8.2 6.0 8.5 6.1 8.9 6.0 9.2 6.4 9.4 6.3 9.9 6.2 10.5 6.1
35.0 8.1 5.9 8.3 6.0 8.8 6.0 9.0 6.3 9.2 6.2 9.7 6.1 10.3 6.0
37.5 7.9 5.8 8.1 6.0 8.6 5.9 8.8 6.2 9.1 6.2 9.5 6.0 10.1 5.9
40.0 7.7 5.7 8.0 5.9 8.4 5.8 8.7 6.1 8.9 6.1 9.3 6.0 9.9 5.9
43.0 7.6 5.6 7.8 5.8 8.2 5.7 8.5 6.0 8.7 6.0 9.1 5.9 9.6 5.8
20.0 10.6 8.4 11.0 8.7 11.8 8.6 12.1 9.2 12.5 9.1 13.2 9.0 14.2 8.9
22.5 10.6 8.4 11.0 8.7 11.8 8.6 12.1 9.2 12.5 9.1 13.2 9.0 14.2 8.9
25.0 10.6 8.4 11.0 8.7 11.8 8.6 12.1 9.2 12.4 9.1 13.1 9.0 13.9 8.9
27.5 10.6 8.4 10.9 8.6 11.6 8.6 11.9 9.1 12.2 9.0 12.9 8.9 13.7 8.8
100 30.0 10.4 8.3 10.7 8.6 11.3 8.5 11.6 9.0 12.0 8.9 12.6 8.8 13.4 8.7
(11.2) 32.5 10.2 8.2 10.5 8.5 11.1 8.4 11.4 8.9 11.7 8.8 12.4 8.7 13.1 8.6
35.0 10.0 8.1 10.3 8.4 10.9 8.3 11.2 8.8 11.5 8.8 12.1 8.6 12.8 8.5
37.5 9.8 8.0 10.1 8.3 10.7 8.2 11.0 8.7 11.3 8.7 11.9 8.5 12.6 8.4
40.0 9.6 7.9 9.9 8.2 10.5 8.1 10.8 8.6 11.1 8.6 11.6 8.4 12.3 8.3
43.0 9.4 7.8 9.7 8.1 10.2 8.0 10.5 8.5 10.8 8.5 11.3 8.3 12.0 8.2
20.0 13.3 10.2 13.8 10.6 14.7 10.5 15.2 11.2 15.6 11.1 16.6 11.0 17.7 10.8
22.5 13.3 10.2 13.8 10.6 14.7 10.5 15.2 11.2 15.6 11.1 16.6 11.0 17.7 10.8
25.0 13.3 10.2 13.8 10.6 14.7 10.5 15.1 11.1 15.5 11.0 16.4 10.9 17.4 10.7
27.5 13.3 10.2 13.6 10.5 14.4 10.4 14.8 11.0 15.2 10.9 16.1 10.8 17.1 10.6
125 30.0 13.0 10.1 13.4 10.4 14.2 10.3 14.6 10.9 14.9 10.8 15.8 10.6 16.7 10.5
(14.0) 32.5 12.8 10.0 13.2 10.3 13.9 10.2 14.3 10.8 14.7 10.7 15.4 10.5 16.4 10.4
35.0 12.5 9.9 12.9 10.2 13.7 10.1 14.0 10.7 14.4 10.6 15.1 10.4 16.0 10.3
37.5 12.3 9.8 12.7 10.1 13.4 9.9 13.8 10.6 14.1 10.5 14.8 10.3 15.7 10.1
40.0 12.1 9.6 12.4 9.9 13.1 9.8 13.5 10.5 13.8 10.4 14.5 10.2 15.4 10.0
43.0 11.8 9.5 12.1 9.8 12.8 9.7 13.2 10.3 13.5 10.3 14.1 10.0 15.0 9.9
20.0 15.2 11.6 15.8 12.0 16.8 11.9 17.3 12.6 17.8 12.5 18.9 12.4 20.2 12.2
22.5 15.2 11.6 15.8 12.0 16.8 11.9 17.3 12.6 17.8 12.5 18.9 12.4 20.2 12.2
25.0 15.2 11.6 15.8 12.0 16.8 11.9 17.3 12.6 17.7 12.5 18.7 12.3 19.9 12.1
27.5 15.2 11.5 15.6 11.9 16.5 11.7 16.9 12.4 17.4 12.3 18.4 12.1 19.5 12.0
140 30.0 14.9 11.4 15.3 11.8 16.2 11.6 16.6 12.3 17.1 12.2 18.0 12.0 19.1 11.8
(16.0) 32.5 14.6 11.3 15.0 11.6 15.9 11.5 16.3 12.2 16.8 12.1 17.6 11.9 18.7 11.7
35.0 14.3 11.1 14.8 11.5 15.6 11.4 16.0 12.0 16.4 12.0 17.3 11.7 18.3 11.6
37.5 14.1 11.0 14.5 11.4 15.3 11.2 15.7 11.9 16.1 11.8 16.9 11.6 17.9 11.4
40.0 13.8 10.9 14.2 11.2 15.0 11.1 15.4 11.8 15.8 11.7 16.6 11.5 17.6 11.3
43.0 13.4 10.7 13.8 11.1 14.6 10.9 15.0 11.6 15.4 11.6 16.1 11.3 17.1 11.1
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 110


2. Cooling [Ceiling concealed (Middle static pressure type)]
2-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.2 2.0 2.4 1.9 2.5 2.1 2.5 2.1 2.7 2.1 2.9 2.0
22.5 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.1 2.6 2.0 2.8 2.0
25.0 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.4 2.0 2.6 2.0 2.8 2.0
27.5 2.1 1.8 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.0
(2.2) 32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
35.0 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.5 1.9
37.5 1.9 1.8 2.0 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.3 1.9 2.5 1.9
40.0 1.9 1.8 1.9 1.8 2.0 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 1.9
43.0 1.9 1.7 1.9 1.8 2.0 1.8 2.0 1.9 2.1 1.9 2.2 1.9 2.4 1.9
20.0 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.3 3.6 2.3
22.5 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.3 3.6 2.2
25.0 2.7 2.1 2.7 2.2 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
27.5 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.3 3.1 2.3 3.2 2.2 3.4 2.2
25 30.0 2.6 2.1 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.0 2.6 2.1 2.8 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.1
35.0 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.1
37.5 2.5 2.0 2.5 2.0 2.6 2.0 2.7 2.2 2.8 2.2 3.0 2.1 3.2 2.1
40.0 2.4 2.0 2.4 2.0 2.6 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1
43.0 2.4 2.0 2.4 2.0 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.1 3.0 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.8 4.2 2.8 4.4 2.8 4.7 2.7
22.5 3.5 2.6 3.6 2.7 3.8 2.6 4.0 2.8 4.1 2.8 4.3 2.7 4.6 2.7
25.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.7 4.2 2.7 4.5 2.7
27.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.6
32 30.0 3.3 2.5 3.4 2.6 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
(3.6) 32.5 3.3 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.6 4.0 2.6 4.2 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.2 2.5
37.5 3.2 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.6 2.6 3.8 2.6 4.1 2.5
40.0 3.1 2.4 3.1 2.4 3.3 2.4 3.4 2.6 3.5 2.6 3.8 2.5 4.0 2.5
43.0 3.0 2.4 3.0 2.4 3.2 2.4 3.3 2.5 3.4 2.5 3.7 2.5 3.9 2.4
20.0 4.4 3.5 4.5 3.6 4.9 3.6 5.0 3.8 5.2 3.8 5.5 3.8 5.8 3.7
22.5 4.4 3.5 4.5 3.6 4.8 3.6 4.9 3.8 5.1 3.8 5.4 3.7 5.7 3.7
25.0 4.3 3.4 4.4 3.5 4.7 3.5 4.9 3.8 5.0 3.7 5.3 3.7 5.6 3.6
27.5 4.2 3.4 4.3 3.5 4.6 3.5 4.8 3.7 4.9 3.7 5.2 3.6 5.5 3.6
40 30.0 4.1 3.4 4.2 3.5 4.5 3.4 4.7 3.7 4.8 3.7 5.1 3.6 5.4 3.6
(4.5) 32.5 4.1 3.3 4.2 3.4 4.4 3.4 4.6 3.6 4.7 3.6 5.0 3.6 5.3 3.5
35.0 4.0 3.3 4.1 3.4 4.3 3.4 4.5 3.6 4.6 3.6 4.9 3.5 5.2 3.5
37.5 3.9 3.3 4.0 3.4 4.2 3.3 4.4 3.6 4.5 3.5 4.8 3.5 5.1 3.4
40.0 3.9 3.2 3.9 3.3 4.2 3.3 4.3 3.5 4.4 3.5 4.7 3.5 5.0 3.4
43.0 3.8 3.2 3.8 3.3 4.0 3.2 4.2 3.5 4.3 3.5 4.6 3.4 4.8 3.4
20.0 5.4 4.3 5.6 4.4 6.1 4.4 6.3 4.7 6.5 4.7 6.9 4.6 7.3 4.6
22.5 5.4 4.3 5.6 4.4 6.0 4.4 6.2 4.7 6.3 4.6 6.7 4.6 7.1 4.5
25.0 5.3 4.2 5.5 4.4 5.8 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
27.5 5.3 4.2 5.4 4.3 5.7 4.3 5.9 4.6 6.1 4.5 6.5 4.5 6.9 4.4
50 30.0 5.2 4.1 5.3 4.3 5.6 4.2 5.8 4.5 6.0 4.5 6.4 4.4 6.7 4.4
(5.6) 32.5 5.1 4.1 5.2 4.2 5.5 4.2 5.7 4.5 5.9 4.4 6.2 4.4 6.6 4.3
35.0 5.0 4.1 5.1 4.2 5.4 4.1 5.6 4.4 5.7 4.4 6.1 4.3 6.5 4.3
37.5 4.9 4.0 5.0 4.1 5.3 4.1 5.5 4.4 5.6 4.4 6.0 4.3 6.3 4.2
40.0 4.8 4.0 4.9 4.1 5.2 4.0 5.3 4.3 5.5 4.3 5.8 4.3 6.2 4.2
43.0 4.7 3.9 4.7 4.0 5.0 4.0 5.2 4.3 5.4 4.2 5.7 4.2 6.0 4.1
20.0 6.9 5.3 7.1 5.5 7.7 5.5 7.9 5.8 8.2 5.8 8.7 5.7 9.2 5.6
22.5 6.9 5.3 7.1 5.4 7.6 5.4 7.8 5.8 8.0 5.7 8.5 5.7 9.1 5.6
25.0 6.8 5.2 7.0 5.4 7.4 5.3 7.7 5.7 7.9 5.7 8.4 5.6 8.9 5.5
27.5 6.7 5.2 6.8 5.3 7.3 5.3 7.5 5.6 7.7 5.6 8.2 5.5 8.7 5.4
63 30.0 6.5 5.1 6.7 5.3 7.1 5.2 7.4 5.6 7.6 5.5 8.1 5.5 8.5 5.4
(7.1) 32.5 6.4 5.1 6.6 5.2 7.0 5.2 7.2 5.5 7.4 5.5 7.9 5.4 8.4 5.3
35.0 6.3 5.0 6.4 5.1 6.8 5.1 7.1 5.5 7.3 5.4 7.7 5.3 8.2 5.3
37.5 6.2 5.0 6.3 5.1 6.7 5.0 6.9 5.4 7.1 5.4 7.6 5.3 8.0 5.2
40.0 6.1 4.9 6.2 5.0 6.6 5.0 6.8 5.3 7.0 5.3 7.4 5.2 7.8 5.1
43.0 6.0 4.9 6.0 4.9 6.4 4.9 6.6 5.2 6.8 5.2 7.2 5.2 7.6 5.1
20.0 7.8 5.8 8.0 6.0 8.6 5.9 8.9 6.3 9.2 6.3 9.8 6.2 10.4 6.1
22.5 7.7 5.8 8.0 5.9 8.5 5.9 8.8 6.2 9.1 6.2 9.6 6.1 10.2 6.0
25.0 7.6 5.7 7.8 5.9 8.4 5.8 8.6 6.2 8.9 6.1 9.4 6.1 10.0 6.0
27.5 7.5 5.6 7.7 5.8 8.2 5.7 8.5 6.1 8.7 6.1 9.3 6.0 9.8 5.9
71 30.0 7.4 5.6 7.5 5.7 8.0 5.7 8.3 6.0 8.6 6.0 9.1 5.9 9.6 5.8
(8.0) 32.5 7.3 5.5 7.4 5.6 7.9 5.6 8.1 5.9 8.4 5.9 8.9 5.8 9.4 5.8
35.0 7.1 5.5 7.2 5.6 7.7 5.5 8.0 5.9 8.2 5.8 8.7 5.8 9.2 5.7
37.5 7.0 5.4 7.1 5.5 7.5 5.5 7.8 5.8 8.0 5.8 8.5 5.7 9.0 5.6
40.0 6.9 5.3 6.9 5.4 7.4 5.4 7.6 5.7 7.9 5.7 8.3 5.6 8.8 5.6
43.0 6.7 5.3 6.8 5.4 7.2 5.3 7.4 5.7 7.7 5.6 8.1 5.6 8.6 5.5
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 111


2. Cooling [Ceiling concealed (Middle static pressure type)]
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.7 6.2 9.0 6.4 9.7 6.4 10.1 6.8 10.4 6.7 11.0 6.6 11.7 6.5
22.5 8.7 6.2 9.0 6.4 9.6 6.3 9.9 6.7 10.2 6.6 10.8 6.6 11.5 6.5
25.0 8.6 6.1 8.8 6.3 9.4 6.3 9.7 6.6 10.0 6.6 10.6 6.5 11.3 6.4
27.5 8.4 6.1 8.6 6.2 9.2 6.2 9.5 6.5 9.8 6.5 10.4 6.4 11.0 6.3
80 30.0 8.3 6.0 8.5 6.1 9.0 6.1 9.3 6.4 9.6 6.4 10.2 6.3 10.8 6.2
(9.0) 32.5 8.2 5.9 8.3 6.0 8.9 6.0 9.1 6.3 9.4 6.3 10.0 6.2 10.6 6.1
35.0 8.0 5.9 8.1 6.0 8.7 5.9 9.0 6.3 9.2 6.2 9.8 6.1 10.4 6.1
37.5 7.9 5.8 8.0 5.9 8.5 5.8 8.8 6.2 9.0 6.1 9.6 6.1 10.2 6.0
40.0 7.7 5.7 7.8 5.8 8.3 5.8 8.6 6.1 8.8 6.1 9.4 6.0 9.9 5.9
43.0 7.6 5.6 7.6 5.7 8.1 5.7 8.4 6.0 8.6 6.0 9.1 5.9 9.7 5.8
20.0 10.9 8.5 11.3 8.8 12.1 8.8 12.5 9.4 12.9 9.3 13.7 9.2 14.5 9.1
22.5 10.8 8.5 11.2 8.8 11.9 8.7 12.3 9.3 12.7 9.2 13.5 9.1 14.3 9.0
25.0 10.7 8.4 11.0 8.7 11.7 8.6 12.1 9.2 12.5 9.1 13.2 9.0 14.0 8.9
27.5 10.5 8.3 10.8 8.6 11.5 8.5 11.8 9.1 12.2 9.0 13.0 8.9 13.7 8.8
100 30.0 10.3 8.3 10.6 8.5 11.2 8.4 11.6 9.0 12.0 8.9 12.7 8.8 13.5 8.7
(11.2) 32.5 10.2 8.2 10.3 8.4 11.0 8.3 11.4 8.9 11.7 8.8 12.4 8.7 13.2 8.6
35.0 10.0 8.1 10.1 8.3 10.8 8.2 11.2 8.8 11.5 8.7 12.2 8.6 12.9 8.5
37.5 9.8 8.0 9.9 8.2 10.6 8.1 10.9 8.7 11.2 8.7 11.9 8.5 12.6 8.4
40.0 9.6 7.9 9.7 8.1 10.3 8.0 10.7 8.6 11.0 8.6 11.7 8.5 12.4 8.3
43.0 9.4 7.8 9.5 8.0 10.1 7.9 10.4 8.5 10.7 8.4 11.4 8.3 12.1 8.2
20.0 13.6 10.4 14.1 10.7 15.1 10.7 15.7 11.4 16.2 11.3 17.2 11.2 18.2 11.0
22.5 13.6 10.4 14.0 10.7 14.9 10.6 15.4 11.3 15.9 11.2 16.8 11.1 17.8 10.9
25.0 13.3 10.3 13.7 10.6 14.6 10.5 15.1 11.1 15.6 11.1 16.5 10.9 17.5 10.8
27.5 13.1 10.2 13.5 10.4 14.3 10.4 14.8 11.0 15.3 11.0 16.2 10.8 17.2 10.7
125 30.0 12.9 10.0 13.2 10.3 14.1 10.2 14.5 10.9 15.0 10.8 15.9 10.7 16.8 10.5
(14.0) 32.5 12.7 9.9 12.9 10.2 13.8 10.1 14.2 10.8 14.7 10.7 15.6 10.6 16.5 10.4
35.0 12.5 9.8 12.7 10.1 13.5 10.0 14.0 10.7 14.4 10.6 15.2 10.5 16.2 10.3
37.5 12.3 9.7 12.4 9.9 13.2 9.9 13.6 10.5 14.1 10.5 14.9 10.3 15.8 10.2
40.0 12.0 9.6 12.2 9.8 12.9 9.7 13.3 10.4 13.8 10.4 14.6 10.2 15.5 10.1
43.0 11.8 9.5 11.8 9.7 12.6 9.6 13.0 10.3 13.4 10.2 14.2 10.1 15.1 9.9
20.0 15.5 11.7 16.1 12.1 17.3 12.1 17.9 12.8 18.5 12.8 19.6 12.6 20.8 12.4
22.5 15.5 11.7 16.0 12.1 17.0 12.0 17.6 12.7 18.1 12.7 19.2 12.5 20.4 12.3
25.0 15.3 11.6 15.7 11.9 16.7 11.8 17.3 12.6 17.8 12.5 18.9 12.3 20.0 12.2
27.5 15.0 11.5 15.4 11.8 16.4 11.7 16.9 12.4 17.4 12.4 18.5 12.2 19.6 12.0
140 30.0 14.8 11.4 15.1 11.6 16.1 11.6 16.6 12.3 17.1 12.2 18.1 12.1 19.2 11.9
(16.0) 32.5 14.5 11.2 14.8 11.5 15.7 11.4 16.3 12.1 16.8 12.1 17.8 11.9 18.8 11.8
35.0 14.3 11.1 14.5 11.4 15.4 11.3 16.0 12.0 16.4 11.9 17.4 11.8 18.5 11.6
37.5 14.0 11.0 14.2 11.2 15.1 11.1 15.6 11.9 16.1 11.8 17.0 11.7 18.1 11.5
40.0 13.8 10.9 13.9 11.1 14.8 11.0 15.2 11.7 15.7 11.7 16.7 11.5 17.7 11.3
43.0 13.5 10.7 13.5 10.9 14.4 10.8 14.8 11.6 15.3 11.5 16.3 11.4 17.2 11.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 112


2. Cooling [Ceiling concealed (Middle static pressure type)]
2-3. Cooling capacity with PUHY-RP450-650YSJM
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.1 1.9 2.3 1.9 2.4 2.1 2.4 2.0 2.6 2.0 2.8 2.0
22.5 2.1 1.8 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.0 2.6 2.0 2.7 2.0
25.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.5 2.0 2.7 2.0
(2.2) 32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
35.0 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
37.5 1.9 1.8 2.0 1.8 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
40.0 1.9 1.8 1.9 1.8 2.1 1.8 2.2 2.0 2.2 2.0 2.4 2.0 2.6 1.9
43.0 1.9 1.8 1.9 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.4 1.9 2.5 1.9
20.0 2.6 2.1 2.7 2.2 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
22.5 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
25.0 2.6 2.1 2.7 2.1 2.9 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.5 2.2
27.5 2.6 2.1 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
25 30.0 2.5 2.0 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.0 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
35.0 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.0 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.1
40.0 2.4 2.0 2.5 2.0 2.7 2.0 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.1
43.0 2.4 2.0 2.4 2.0 2.6 2.0 2.7 2.2 2.8 2.2 3.0 2.1 3.2 2.1
20.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.5 2.7
22.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 4.0 2.7 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.6
27.5 3.3 2.5 3.4 2.6 3.6 2.5 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.3 2.5 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.4 2.6
(3.6) 32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.8 2.6 4.0 2.6 4.3 2.6
37.5 3.2 2.4 3.2 2.5 3.5 2.5 3.6 2.6 3.7 2.6 4.0 2.6 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.4 3.4 2.4 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.5
20.0 4.3 3.4 4.4 3.5 4.7 3.5 4.8 3.7 5.0 3.7 5.3 3.7 5.7 3.6
22.5 4.2 3.4 4.3 3.5 4.6 3.5 4.8 3.7 4.9 3.7 5.3 3.7 5.6 3.6
25.0 4.2 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.9 3.7 5.2 3.7 5.6 3.6
27.5 4.1 3.4 4.2 3.5 4.5 3.4 4.7 3.7 4.8 3.7 5.2 3.6 5.5 3.6
40 30.0 4.1 3.3 4.2 3.4 4.5 3.4 4.6 3.7 4.8 3.6 5.1 3.6 5.5 3.6
(4.5) 32.5 4.0 3.3 4.1 3.4 4.4 3.4 4.6 3.6 4.7 3.6 5.1 3.6 5.4 3.6
35.0 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.7 3.6 5.0 3.6 5.4 3.5
37.5 4.0 3.3 4.0 3.4 4.3 3.4 4.5 3.6 4.6 3.6 5.0 3.6 5.3 3.5
40.0 3.9 3.3 4.0 3.3 4.3 3.3 4.4 3.6 4.6 3.6 4.9 3.5 5.3 3.5
43.0 3.9 3.2 3.9 3.3 4.2 3.3 4.4 3.6 4.5 3.5 4.9 3.5 5.2 3.5
20.0 5.3 4.2 5.5 4.3 5.8 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
22.5 5.2 4.2 5.4 4.3 5.8 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
25.0 5.2 4.2 5.3 4.3 5.7 4.3 5.9 4.6 6.1 4.5 6.5 4.5 6.9 4.4
27.5 5.1 4.1 5.3 4.3 5.6 4.2 5.8 4.5 6.0 4.5 6.4 4.5 6.9 4.4
50 30.0 5.1 4.1 5.2 4.2 5.6 4.2 5.8 4.5 6.0 4.5 6.4 4.4 6.8 4.4
(5.6) 32.5 5.0 4.1 5.1 4.2 5.5 4.2 5.7 4.5 5.9 4.5 6.3 4.4 6.7 4.4
35.0 5.0 4.1 5.1 4.2 5.4 4.2 5.6 4.4 5.8 4.4 6.2 4.4 6.7 4.4
37.5 4.9 4.0 5.0 4.1 5.4 4.1 5.6 4.4 5.8 4.4 6.2 4.4 6.6 4.3
40.0 4.9 4.0 4.9 4.1 5.3 4.1 5.5 4.4 5.7 4.4 6.1 4.4 6.5 4.3
43.0 4.8 4.0 4.9 4.1 5.2 4.1 5.4 4.4 5.6 4.4 6.0 4.3 6.5 4.3
20.0 6.7 5.2 6.9 5.4 7.4 5.3 7.6 5.7 7.9 5.7 8.4 5.6 8.9 5.5
22.5 6.6 5.2 6.8 5.3 7.3 5.3 7.6 5.6 7.8 5.6 8.3 5.6 8.8 5.5
25.0 6.6 5.1 6.8 5.3 7.2 5.3 7.5 5.6 7.7 5.6 8.2 5.5 8.8 5.5
27.5 6.5 5.1 6.7 5.3 7.2 5.2 7.4 5.6 7.6 5.6 8.2 5.5 8.7 5.4
63 30.0 6.4 5.1 6.6 5.2 7.1 5.2 7.3 5.5 7.6 5.5 8.1 5.5 8.6 5.4
(7.1) 32.5 6.4 5.0 6.5 5.2 7.0 5.2 7.2 5.5 7.5 5.5 8.0 5.4 8.5 5.4
35.0 6.3 5.0 6.4 5.1 6.9 5.1 7.1 5.5 7.4 5.5 7.9 5.4 8.5 5.4
37.5 6.2 5.0 6.3 5.1 6.8 5.1 7.1 5.4 7.3 5.4 7.8 5.4 8.4 5.3
40.0 6.2 5.0 6.3 5.1 6.7 5.1 7.0 5.4 7.2 5.4 7.8 5.4 8.3 5.3
43.0 6.1 4.9 6.2 5.0 6.7 5.0 6.9 5.4 7.1 5.4 7.7 5.3 8.2 5.3
20.0 7.6 5.7 7.8 5.8 8.3 5.8 8.6 6.2 8.9 6.1 9.4 6.1 10.0 6.0
22.5 7.5 5.6 7.7 5.8 8.2 5.8 8.5 6.1 8.8 6.1 9.4 6.0 10.0 5.9
25.0 7.4 5.6 7.6 5.7 8.1 5.7 8.4 6.1 8.7 6.1 9.3 6.0 9.9 5.9
27.5 7.3 5.6 7.5 5.7 8.1 5.7 8.3 6.0 8.6 6.0 9.2 6.0 9.8 5.9
71 30.0 7.3 5.5 7.4 5.7 8.0 5.6 8.2 6.0 8.5 6.0 9.1 5.9 9.7 5.9
(8.0) 32.5 7.2 5.5 7.3 5.6 7.9 5.6 8.2 6.0 8.4 5.9 9.0 5.9 9.6 5.8
35.0 7.1 5.4 7.2 5.6 7.8 5.6 8.0 5.9 8.3 5.9 8.9 5.9 9.5 5.8
37.5 7.0 5.4 7.2 5.5 7.7 5.5 8.0 5.9 8.3 5.9 8.8 5.8 9.4 5.8
40.0 7.0 5.4 7.1 5.5 7.6 5.5 7.9 5.8 8.2 5.8 8.7 5.8 9.4 5.7
43.0 6.9 5.3 7.0 5.4 7.5 5.4 7.8 5.8 8.1 5.8 8.6 5.7 9.2 5.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 113


2. Cooling [Ceiling concealed (Middle static pressure type)]
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.5 6.1 8.8 6.3 9.4 6.2 9.7 6.6 10.0 6.6 10.6 6.5 11.3 6.4
22.5 8.4 6.1 8.7 6.2 9.3 6.2 9.6 6.5 9.9 6.5 10.5 6.4 11.2 6.4
25.0 8.3 6.0 8.6 6.2 9.2 6.1 9.5 6.5 9.8 6.5 10.4 6.4 11.1 6.3
27.5 8.3 6.0 8.5 6.1 9.1 6.1 9.4 6.4 9.7 6.4 10.3 6.4 11.0 6.3
80 30.0 8.2 5.9 8.4 6.1 9.0 6.1 9.3 6.4 9.6 6.4 10.2 6.3 10.9 6.2
(9.0) 32.5 8.1 5.9 8.3 6.0 8.9 6.0 9.2 6.4 9.5 6.3 10.1 6.3 10.8 6.2
35.0 8.0 5.8 8.1 6.0 8.8 6.0 9.0 6.3 9.4 6.3 10.0 6.2 10.7 6.2
37.5 7.9 5.8 8.0 5.9 8.7 5.9 9.0 6.3 9.3 6.2 9.9 6.2 10.6 6.1
40.0 7.8 5.8 7.9 5.9 8.6 5.9 8.9 6.2 9.2 6.2 9.8 6.2 10.5 6.1
43.0 7.7 5.7 7.8 5.8 8.4 5.8 8.7 6.2 9.1 6.2 9.7 6.1 10.4 6.1
20.0 10.6 8.4 10.9 8.6 11.7 8.6 12.0 9.2 12.4 9.1 13.2 9.0 14.1 8.9
22.5 10.5 8.3 10.8 8.6 11.5 8.5 11.9 9.1 12.3 9.1 13.1 9.0 13.9 8.9
25.0 10.4 8.3 10.6 8.5 11.4 8.5 11.8 9.1 12.2 9.0 13.0 8.9 13.8 8.8
27.5 10.3 8.2 10.5 8.5 11.3 8.4 11.7 9.0 12.1 9.0 12.9 8.9 13.7 8.8
100 30.0 10.2 8.2 10.4 8.4 11.2 8.4 11.5 9.0 11.9 8.9 12.7 8.8 13.6 8.7
(11.2) 32.5 10.1 8.1 10.3 8.4 11.0 8.3 11.4 8.9 11.8 8.9 12.6 8.8 13.5 8.7
35.0 9.9 8.1 10.1 8.3 10.9 8.3 11.2 8.8 11.7 8.8 12.5 8.7 13.3 8.7
37.5 9.8 8.0 10.0 8.2 10.8 8.2 11.2 8.8 11.6 8.8 12.4 8.7 13.2 8.6
40.0 9.7 8.0 9.9 8.2 10.6 8.2 11.0 8.7 11.4 8.7 12.2 8.7 13.1 8.6
43.0 9.6 7.9 9.7 8.1 10.5 8.1 10.9 8.7 11.3 8.7 12.1 8.6 12.9 8.5
20.0 13.2 10.2 13.6 10.5 14.6 10.5 15.1 11.1 15.5 11.1 16.5 10.9 17.6 10.8
22.5 13.1 10.1 13.5 10.4 14.4 10.4 14.9 11.1 15.4 11.0 16.4 10.9 17.4 10.7
25.0 13.0 10.1 13.3 10.4 14.3 10.3 14.7 11.0 15.2 10.9 16.2 10.8 17.3 10.7
27.5 12.8 10.0 13.2 10.3 14.1 10.2 14.6 10.9 15.1 10.9 16.1 10.8 17.1 10.6
125 30.0 12.7 9.9 13.0 10.2 13.9 10.2 14.4 10.9 14.9 10.8 15.9 10.7 17.0 10.6
(14.0) 32.5 12.6 9.9 12.8 10.1 13.8 10.1 14.3 10.8 14.8 10.7 15.8 10.7 16.8 10.5
35.0 12.4 9.8 12.7 10.1 13.6 10.0 14.0 10.7 14.6 10.7 15.6 10.6 16.7 10.5
37.5 12.3 9.8 12.5 10.0 13.5 10.0 14.0 10.7 14.4 10.6 15.5 10.5 16.5 10.4
40.0 12.2 9.7 12.4 9.9 13.3 9.9 13.8 10.6 14.3 10.6 15.3 10.5 16.4 10.4
43.0 12.0 9.6 12.2 9.8 13.1 9.8 13.6 10.5 14.1 10.5 15.1 10.4 16.2 10.3
20.0 15.1 11.5 15.6 11.9 16.7 11.8 17.2 12.6 17.8 12.5 18.9 12.4 20.1 12.2
22.5 15.0 11.5 15.4 11.8 16.5 11.7 17.0 12.5 17.6 12.4 18.7 12.3 19.9 12.1
25.0 14.8 11.4 15.2 11.7 16.3 11.7 16.8 12.4 17.4 12.3 18.5 12.2 19.7 12.1
27.5 14.7 11.3 15.0 11.6 16.1 11.6 16.7 12.3 17.2 12.3 18.4 12.2 19.6 12.0
140 30.0 14.5 11.2 14.9 11.5 15.9 11.5 16.5 12.2 17.0 12.2 18.2 12.1 19.4 11.9
(16.0) 32.5 14.4 11.2 14.7 11.5 15.8 11.4 16.3 12.2 16.9 12.1 18.0 12.0 19.2 11.9
35.0 14.2 11.1 14.5 11.4 15.6 11.3 16.0 12.0 16.7 12.1 17.8 12.0 19.1 11.8
37.5 14.1 11.0 14.3 11.3 15.4 11.3 15.9 12.0 16.5 12.0 17.7 11.9 18.9 11.8
40.0 13.9 10.9 14.1 11.2 15.2 11.2 15.8 11.9 16.3 11.9 17.5 11.8 18.7 11.7
43.0 13.7 10.9 13.9 11.1 15.0 11.1 15.6 11.9 16.1 11.8 17.3 11.7 18.5 11.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 114


2. Cooling [Ceiling concealed (Middle static pressure type)]
2-4. Cooling capacity with PUHY-RP700-800YSJM
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.2 1.9 2.4 1.9 2.4 2.1 2.5 2.1 2.7 2.1 2.9 2.0
22.5 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.1 2.6 2.0 2.8 2.0
25.0 2.1 1.8 2.1 1.9 2.3 1.9 2.4 2.1 2.4 2.0 2.6 2.0 2.8 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.6 2.0 2.7 2.0
20 30.0 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
(2.2) 32.5 1.9 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
35.0 1.9 1.8 2.0 1.8 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
37.5 1.9 1.8 1.9 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.4 1.9 2.5 1.9
40.0 1.8 1.7 1.9 1.8 2.0 1.8 2.1 2.0 2.2 1.9 2.3 1.9 2.5 1.9
43.0 1.8 1.7 1.8 1.8 2.0 1.8 2.1 1.9 2.1 1.9 2.3 1.9 2.4 1.9
20.0 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.3 3.7 2.3
22.5 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.3 3.6 2.2
25.0 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
27.5 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
25 30.0 2.5 2.0 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
35.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.1
37.5 2.4 2.0 2.5 2.0 2.6 2.0 2.7 2.2 2.8 2.2 3.0 2.1 3.2 2.1
40.0 2.3 1.9 2.4 2.0 2.6 2.0 2.7 2.1 2.8 2.1 3.0 2.1 3.1 2.1
43.0 2.3 1.9 2.4 2.0 2.5 2.0 2.6 2.1 2.7 2.1 2.9 2.1 3.1 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.8 4.1 2.8 4.4 2.8 4.7 2.7
22.5 3.4 2.5 3.5 2.6 3.8 2.6 3.9 2.8 4.1 2.8 4.3 2.7 4.6 2.7
25.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.5 2.7
27.5 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.5 2.6
32 30.0 3.2 2.5 3.4 2.5 3.6 2.5 3.7 2.7 3.9 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.3 2.6
35.0 3.1 2.4 3.2 2.5 3.5 2.5 3.6 2.6 3.7 2.6 4.0 2.6 4.2 2.6
37.5 3.1 2.4 3.2 2.4 3.4 2.4 3.5 2.6 3.6 2.6 3.9 2.6 4.1 2.5
40.0 3.0 2.3 3.1 2.4 3.3 2.4 3.4 2.6 3.6 2.6 3.8 2.5 4.0 2.5
43.0 2.9 2.3 3.0 2.4 3.2 2.4 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.5
20.0 4.3 3.5 4.5 3.6 4.8 3.6 5.0 3.8 5.2 3.8 5.5 3.8 5.9 3.7
22.5 4.3 3.4 4.4 3.6 4.7 3.5 4.9 3.8 5.1 3.8 5.4 3.7 5.8 3.7
25.0 4.2 3.4 4.3 3.5 4.7 3.5 4.8 3.7 5.0 3.7 5.3 3.7 5.7 3.6
27.5 4.1 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.9 3.7 5.2 3.7 5.6 3.6
40 30.0 4.1 3.3 4.2 3.4 4.5 3.4 4.7 3.7 4.8 3.7 5.1 3.6 5.5 3.6
(4.5) 32.5 4.0 3.3 4.1 3.4 4.4 3.4 4.6 3.6 4.7 3.6 5.0 3.6 5.4 3.5
35.0 3.9 3.3 4.0 3.4 4.3 3.4 4.5 3.6 4.6 3.6 4.9 3.6 5.3 3.5
37.5 3.8 3.2 4.0 3.3 4.2 3.3 4.4 3.6 4.5 3.6 4.8 3.5 5.2 3.5
40.0 3.8 3.2 3.9 3.3 4.2 3.3 4.3 3.5 4.5 3.5 4.8 3.5 5.1 3.4
43.0 3.7 3.2 3.8 3.3 4.1 3.2 4.2 3.5 4.3 3.5 4.6 3.4 4.9 3.4
20.0 5.4 4.3 5.6 4.4 6.0 4.4 6.2 4.7 6.4 4.7 6.9 4.6 7.3 4.6
22.5 5.3 4.2 5.5 4.4 5.9 4.4 6.1 4.6 6.3 4.6 6.7 4.6 7.2 4.5
25.0 5.2 4.2 5.4 4.3 5.8 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
27.5 5.1 4.1 5.3 4.3 5.7 4.3 5.9 4.6 6.1 4.5 6.5 4.5 6.9 4.4
50 30.0 5.0 4.1 5.2 4.2 5.6 4.2 5.8 4.5 6.0 4.5 6.4 4.5 6.8 4.4
(5.6) 32.5 5.0 4.0 5.1 4.2 5.5 4.2 5.7 4.5 5.9 4.5 6.3 4.4 6.7 4.4
35.0 4.9 4.0 5.0 4.1 5.4 4.1 5.6 4.4 5.8 4.4 6.2 4.4 6.5 4.3
37.5 4.8 4.0 4.9 4.1 5.3 4.1 5.5 4.4 5.7 4.4 6.0 4.3 6.4 4.3
40.0 4.7 3.9 4.8 4.1 5.2 4.0 5.4 4.3 5.5 4.3 5.9 4.3 6.3 4.2
43.0 4.6 3.9 4.7 4.0 5.1 4.0 5.2 4.3 5.4 4.3 5.8 4.2 6.1 4.2
20.0 6.9 5.3 7.1 5.5 7.6 5.4 7.9 5.8 8.2 5.8 8.7 5.7 9.3 5.6
22.5 6.7 5.2 7.0 5.4 7.5 5.4 7.8 5.7 8.0 5.7 8.6 5.7 9.1 5.6
25.0 6.6 5.2 6.9 5.3 7.4 5.3 7.6 5.7 7.9 5.7 8.4 5.6 8.9 5.5
27.5 6.5 5.1 6.7 5.3 7.2 5.3 7.5 5.6 7.7 5.6 8.3 5.5 8.8 5.5
63 30.0 6.4 5.1 6.6 5.2 7.1 5.2 7.3 5.6 7.6 5.5 8.1 5.5 8.6 5.4
(7.1) 32.5 6.3 5.0 6.5 5.2 7.0 5.2 7.2 5.5 7.5 5.5 7.9 5.4 8.5 5.4
35.0 6.2 4.9 6.4 5.1 6.8 5.1 7.1 5.5 7.3 5.4 7.8 5.4 8.3 5.3
37.5 6.1 4.9 6.2 5.1 6.7 5.0 6.9 5.4 7.2 5.4 7.6 5.3 8.1 5.2
40.0 5.9 4.8 6.1 5.0 6.6 5.0 6.8 5.3 7.0 5.3 7.5 5.3 8.0 5.2
43.0 5.8 4.8 6.0 4.9 6.4 4.9 6.6 5.3 6.9 5.2 7.3 5.2 7.8 5.1
20.0 7.7 5.8 8.0 5.9 8.6 5.9 8.9 6.3 9.2 6.3 9.8 6.2 10.4 6.1
22.5 7.6 5.7 7.9 5.9 8.4 5.9 8.7 6.2 9.0 6.2 9.6 6.1 10.3 6.1
25.0 7.5 5.6 7.7 5.8 8.3 5.8 8.6 6.1 8.9 6.1 9.5 6.1 10.1 6.0
27.5 7.3 5.6 7.6 5.7 8.1 5.7 8.4 6.1 8.7 6.1 9.3 6.0 9.9 5.9
71 30.0 7.2 5.5 7.4 5.7 8.0 5.7 8.3 6.0 8.6 6.0 9.1 5.9 9.7 5.9
(8.0) 32.5 7.1 5.4 7.3 5.6 7.8 5.6 8.1 5.9 8.4 5.9 9.0 5.9 9.5 5.8
35.0 6.9 5.4 7.2 5.5 7.7 5.5 8.0 5.9 8.2 5.9 8.8 5.8 9.3 5.7
37.5 6.8 5.3 7.0 5.5 7.5 5.5 7.8 5.8 8.1 5.8 8.6 5.7 9.2 5.7
40.0 6.7 5.2 6.9 5.4 7.4 5.4 7.7 5.8 7.9 5.7 8.4 5.7 9.0 5.6
43.0 6.5 5.2 6.7 5.3 7.2 5.3 7.5 5.7 7.7 5.7 8.2 5.6 8.8 5.5
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 115


2. Cooling [Ceiling concealed (Middle static pressure type)]
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.7 6.2 9.0 6.4 9.7 6.4 10.0 6.7 10.3 6.7 11.0 6.6 11.7 6.6
22.5 8.5 6.1 8.9 6.3 9.5 6.3 9.8 6.7 10.2 6.6 10.8 6.6 11.5 6.5
25.0 8.4 6.1 8.7 6.2 9.3 6.2 9.7 6.6 10.0 6.6 10.6 6.5 11.3 6.4
27.5 8.3 6.0 8.5 6.2 9.2 6.1 9.5 6.5 9.8 6.5 10.5 6.4 11.1 6.3
80 30.0 8.1 5.9 8.4 6.1 9.0 6.1 9.3 6.4 9.6 6.4 10.3 6.3 10.9 6.3
(9.0) 32.5 8.0 5.8 8.2 6.0 8.8 6.0 9.1 6.3 9.4 6.3 10.1 6.3 10.7 6.2
35.0 7.8 5.8 8.1 5.9 8.7 5.9 9.0 6.3 9.3 6.2 9.9 6.2 10.5 6.1
37.5 7.7 5.7 7.9 5.8 8.5 5.8 8.8 6.2 9.1 6.2 9.7 6.1 10.3 6.0
40.0 7.5 5.6 7.7 5.8 8.3 5.8 8.6 6.1 8.9 6.1 9.5 6.0 10.1 6.0
43.0 7.4 5.5 7.6 5.7 8.1 5.7 8.4 6.0 8.7 6.0 9.3 5.9 9.9 5.9
20.0 10.8 8.5 11.2 8.8 12.0 8.8 12.5 9.3 12.9 9.3 13.7 9.2 14.6 9.1
22.5 10.6 8.4 11.0 8.7 11.8 8.7 12.2 9.2 12.6 9.2 13.5 9.1 14.4 9.0
25.0 10.5 8.3 10.8 8.6 11.6 8.6 12.0 9.2 12.4 9.1 13.3 9.0 14.1 8.9
27.5 10.3 8.2 10.6 8.5 11.4 8.5 11.8 9.1 12.2 9.0 13.0 8.9 13.8 8.8
100 30.0 10.1 8.1 10.4 8.4 11.2 8.4 11.6 9.0 12.0 8.9 12.8 8.9 13.6 8.7
(11.2) 32.5 9.9 8.1 10.2 8.3 11.0 8.3 11.4 8.9 11.8 8.9 12.5 8.8 13.3 8.7
35.0 9.7 8.0 10.0 8.2 10.8 8.2 11.2 8.8 11.5 8.8 12.3 8.7 13.1 8.6
37.5 9.5 7.9 9.8 8.2 10.6 8.1 10.9 8.7 11.3 8.7 12.1 8.6 12.8 8.5
40.0 9.4 7.8 9.6 8.1 10.4 8.0 10.7 8.6 11.1 8.6 11.8 8.5 12.6 8.4
43.0 9.2 7.7 9.4 8.0 10.1 7.9 10.5 8.5 10.8 8.5 11.5 8.4 12.3 8.3
20.0 13.5 10.3 14.0 10.7 15.0 10.7 15.6 11.3 16.1 11.3 17.2 11.2 18.3 11.0
22.5 13.3 10.2 13.8 10.6 14.8 10.5 15.3 11.2 15.8 11.2 16.9 11.1 17.9 10.9
25.0 13.1 10.1 13.5 10.5 14.5 10.4 15.0 11.1 15.5 11.1 16.6 11.0 17.6 10.8
27.5 12.8 10.0 13.3 10.3 14.3 10.3 14.8 11.0 15.3 11.0 16.3 10.8 17.3 10.7
125 30.0 12.6 9.9 13.0 10.2 14.0 10.2 14.5 10.9 15.0 10.8 16.0 10.7 17.0 10.6
(14.0) 32.5 12.4 9.8 12.8 10.1 13.7 10.1 14.2 10.8 14.7 10.7 15.7 10.6 16.7 10.5
35.0 12.2 9.7 12.5 10.0 13.5 10.0 14.0 10.7 14.4 10.6 15.4 10.5 16.4 10.4
37.5 11.9 9.6 12.3 9.9 13.2 9.9 13.7 10.5 14.1 10.5 15.1 10.4 16.0 10.3
40.0 11.7 9.5 12.1 9.8 12.9 9.8 13.4 10.4 13.9 10.4 14.8 10.3 15.7 10.2
43.0 11.4 9.3 11.8 9.7 12.6 9.6 13.1 10.3 13.5 10.3 14.4 10.2 15.4 10.0
20.0 15.5 11.7 16.0 12.1 17.2 12.1 17.8 12.8 18.4 12.8 19.6 12.6 20.9 12.5
22.5 15.2 11.6 15.7 12.0 16.9 11.9 17.5 12.7 18.1 12.6 19.3 12.5 20.5 12.3
25.0 14.9 11.4 15.5 11.8 16.6 11.8 17.2 12.5 17.8 12.5 18.9 12.4 20.1 12.2
27.5 14.7 11.3 15.2 11.7 16.3 11.7 16.9 12.4 17.4 12.4 18.6 12.2 19.8 12.1
140 30.0 14.4 11.2 14.9 11.6 16.0 11.5 16.6 12.3 17.1 12.2 18.3 12.1 19.4 12.0
(16.0) 32.5 14.2 11.1 14.6 11.4 15.7 11.4 16.2 12.1 16.8 12.1 17.9 12.0 19.1 11.8
35.0 13.9 10.9 14.3 11.3 15.4 11.3 16.0 12.0 16.5 12.0 17.6 11.9 18.7 11.7
37.5 13.6 10.8 14.1 11.2 15.1 11.1 15.6 11.9 16.2 11.8 17.2 11.7 18.3 11.6
40.0 13.4 10.7 13.8 11.0 14.8 11.0 15.3 11.8 15.8 11.7 16.9 11.6 18.0 11.5
43.0 13.1 10.6 13.4 10.9 14.4 10.9 14.9 11.6 15.5 11.6 16.5 11.5 17.6 11.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 116


2. Cooling [Ceiling concealed (Middle static pressure type)]
2-5. Cooling capacity with PUHY-RP850-900YSJM
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.1 1.9 2.3 1.9 2.4 2.1 2.4 2.0 2.6 2.0 2.8 2.0
22.5 2.1 1.8 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.0 2.6 2.0 2.7 2.0
25.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.5 2.0 2.7 2.0
(2.2) 32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
35.0 2.0 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
37.5 1.9 1.8 2.0 1.8 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
40.0 1.9 1.8 1.9 1.8 2.1 1.8 2.2 2.0 2.2 2.0 2.4 2.0 2.6 1.9
43.0 1.9 1.8 1.9 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.4 1.9 2.5 1.9
20.0 2.6 2.1 2.7 2.2 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
22.5 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.3 3.1 2.3 3.3 2.2 3.5 2.2
25.0 2.6 2.1 2.7 2.1 2.9 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.5 2.2
27.5 2.6 2.1 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
25 30.0 2.5 2.0 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.0 2.6 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.2
35.0 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.0 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.1
40.0 2.4 2.0 2.5 2.0 2.7 2.0 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.1
43.0 2.4 2.0 2.4 2.0 2.6 2.0 2.7 2.2 2.8 2.2 3.0 2.1 3.2 2.1
20.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.5 2.7
22.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 4.0 2.7 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.6
27.5 3.3 2.5 3.4 2.6 3.6 2.5 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.3 2.5 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.4 2.6
(3.6) 32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.8 2.6 4.0 2.6 4.3 2.6
37.5 3.2 2.4 3.2 2.5 3.5 2.5 3.6 2.6 3.7 2.6 4.0 2.6 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.4 3.4 2.4 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.5
20.0 4.3 3.4 4.4 3.5 4.7 3.5 4.8 3.7 5.0 3.7 5.3 3.7 5.7 3.6
22.5 4.2 3.4 4.3 3.5 4.6 3.5 4.8 3.7 4.9 3.7 5.3 3.7 5.6 3.6
25.0 4.2 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.9 3.7 5.2 3.7 5.6 3.6
27.5 4.1 3.4 4.2 3.5 4.5 3.4 4.7 3.7 4.8 3.7 5.2 3.6 5.5 3.6
40 30.0 4.1 3.3 4.2 3.4 4.5 3.4 4.6 3.7 4.8 3.6 5.1 3.6 5.5 3.6
(4.5) 32.5 4.0 3.3 4.1 3.4 4.4 3.4 4.6 3.6 4.7 3.6 5.1 3.6 5.4 3.6
35.0 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.7 3.6 5.0 3.6 5.4 3.5
37.5 4.0 3.3 4.0 3.4 4.3 3.4 4.5 3.6 4.6 3.6 5.0 3.6 5.3 3.5
40.0 3.9 3.3 4.0 3.3 4.3 3.3 4.4 3.6 4.6 3.6 4.9 3.5 5.3 3.5
43.0 3.9 3.2 3.9 3.3 4.2 3.3 4.4 3.6 4.5 3.5 4.9 3.5 5.2 3.5
20.0 5.3 4.2 5.5 4.3 5.8 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
22.5 5.2 4.2 5.4 4.3 5.8 4.3 6.0 4.6 6.2 4.6 6.6 4.5 7.0 4.5
25.0 5.2 4.2 5.3 4.3 5.7 4.3 5.9 4.6 6.1 4.5 6.5 4.5 6.9 4.4
27.5 5.1 4.1 5.3 4.3 5.6 4.2 5.8 4.5 6.0 4.5 6.4 4.5 6.9 4.4
50 30.0 5.1 4.1 5.2 4.2 5.6 4.2 5.8 4.5 6.0 4.5 6.4 4.4 6.8 4.4
(5.6) 32.5 5.0 4.1 5.1 4.2 5.5 4.2 5.7 4.5 5.9 4.5 6.3 4.4 6.7 4.4
35.0 5.0 4.1 5.1 4.2 5.4 4.2 5.6 4.4 5.8 4.4 6.2 4.4 6.7 4.4
37.5 4.9 4.0 5.0 4.1 5.4 4.1 5.6 4.4 5.8 4.4 6.2 4.4 6.6 4.3
40.0 4.9 4.0 4.9 4.1 5.3 4.1 5.5 4.4 5.7 4.4 6.1 4.4 6.5 4.3
43.0 4.8 4.0 4.9 4.1 5.2 4.1 5.4 4.4 5.6 4.4 6.0 4.3 6.5 4.3
20.0 6.7 5.2 6.9 5.4 7.4 5.3 7.6 5.7 7.9 5.7 8.4 5.6 8.9 5.5
22.5 6.6 5.2 6.8 5.3 7.3 5.3 7.6 5.6 7.8 5.6 8.3 5.6 8.8 5.5
25.0 6.6 5.1 6.8 5.3 7.2 5.3 7.5 5.6 7.7 5.6 8.2 5.5 8.8 5.5
27.5 6.5 5.1 6.7 5.3 7.2 5.2 7.4 5.6 7.6 5.6 8.2 5.5 8.7 5.4
63 30.0 6.4 5.1 6.6 5.2 7.1 5.2 7.3 5.5 7.6 5.5 8.1 5.5 8.6 5.4
(7.1) 32.5 6.4 5.0 6.5 5.2 7.0 5.2 7.2 5.5 7.5 5.5 8.0 5.4 8.5 5.4
35.0 6.3 5.0 6.4 5.1 6.9 5.1 7.1 5.5 7.4 5.5 7.9 5.4 8.5 5.4
37.5 6.2 5.0 6.3 5.1 6.8 5.1 7.1 5.4 7.3 5.4 7.8 5.4 8.4 5.3
40.0 6.2 5.0 6.3 5.1 6.7 5.1 7.0 5.4 7.2 5.4 7.8 5.4 8.3 5.3
43.0 6.1 4.9 6.2 5.0 6.7 5.0 6.9 5.4 7.1 5.4 7.7 5.3 8.2 5.3
20.0 7.6 5.7 7.8 5.8 8.3 5.8 8.6 6.2 8.9 6.1 9.4 6.1 10.0 6.0
22.5 7.5 5.6 7.7 5.8 8.2 5.8 8.5 6.1 8.8 6.1 9.4 6.0 10.0 5.9
25.0 7.4 5.6 7.6 5.7 8.1 5.7 8.4 6.1 8.7 6.1 9.3 6.0 9.9 5.9
27.5 7.3 5.6 7.5 5.7 8.1 5.7 8.3 6.0 8.6 6.0 9.2 6.0 9.8 5.9
71 30.0 7.3 5.5 7.4 5.7 8.0 5.6 8.2 6.0 8.5 6.0 9.1 5.9 9.7 5.9
(8.0) 32.5 7.2 5.5 7.3 5.6 7.9 5.6 8.2 6.0 8.4 5.9 9.0 5.9 9.6 5.8
35.0 7.1 5.4 7.2 5.6 7.8 5.6 8.0 5.9 8.3 5.9 8.9 5.9 9.5 5.8
37.5 7.0 5.4 7.2 5.5 7.7 5.5 8.0 5.9 8.3 5.9 8.8 5.8 9.4 5.8
40.0 7.0 5.4 7.1 5.5 7.6 5.5 7.9 5.8 8.2 5.8 8.7 5.8 9.4 5.7
43.0 6.9 5.3 7.0 5.4 7.5 5.4 7.8 5.8 8.1 5.8 8.6 5.7 9.2 5.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 117


2. Cooling [Ceiling concealed (Middle static pressure type)]
PEFY-P-VMA(L)-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.5 6.1 8.8 6.3 9.4 6.2 9.7 6.6 10.0 6.6 10.6 6.5 11.3 6.4
22.5 8.4 6.1 8.7 6.2 9.3 6.2 9.6 6.5 9.9 6.5 10.5 6.4 11.2 6.4
25.0 8.3 6.0 8.6 6.2 9.2 6.1 9.5 6.5 9.8 6.5 10.4 6.4 11.1 6.3
27.5 8.3 6.0 8.5 6.1 9.1 6.1 9.4 6.4 9.7 6.4 10.3 6.4 11.0 6.3
80 30.0 8.2 5.9 8.4 6.1 9.0 6.1 9.3 6.4 9.6 6.4 10.2 6.3 10.9 6.2
(9.0) 32.5 8.1 5.9 8.3 6.0 8.9 6.0 9.2 6.4 9.5 6.3 10.1 6.3 10.8 6.2
35.0 8.0 5.8 8.1 6.0 8.8 6.0 9.0 6.3 9.4 6.3 10.0 6.2 10.7 6.2
37.5 7.9 5.8 8.0 5.9 8.7 5.9 9.0 6.3 9.3 6.2 9.9 6.2 10.6 6.1
40.0 7.8 5.8 7.9 5.9 8.6 5.9 8.9 6.2 9.2 6.2 9.8 6.2 10.5 6.1
43.0 7.7 5.7 7.8 5.8 8.4 5.8 8.7 6.2 9.1 6.2 9.7 6.1 10.4 6.1
20.0 10.6 8.4 10.9 8.6 11.7 8.6 12.0 9.2 12.4 9.1 13.2 9.0 14.1 8.9
22.5 10.5 8.3 10.8 8.6 11.5 8.5 11.9 9.1 12.3 9.1 13.1 9.0 13.9 8.9
25.0 10.4 8.3 10.6 8.5 11.4 8.5 11.8 9.1 12.2 9.0 13.0 8.9 13.8 8.8
27.5 10.3 8.2 10.5 8.5 11.3 8.4 11.7 9.0 12.1 9.0 12.9 8.9 13.7 8.8
100 30.0 10.2 8.2 10.4 8.4 11.2 8.4 11.5 9.0 11.9 8.9 12.7 8.8 13.6 8.7
(11.2) 32.5 10.1 8.1 10.3 8.4 11.0 8.3 11.4 8.9 11.8 8.9 12.6 8.8 13.5 8.7
35.0 9.9 8.1 10.1 8.3 10.9 8.3 11.2 8.8 11.7 8.8 12.5 8.7 13.3 8.7
37.5 9.8 8.0 10.0 8.2 10.8 8.2 11.2 8.8 11.6 8.8 12.4 8.7 13.2 8.6
40.0 9.7 8.0 9.9 8.2 10.6 8.2 11.0 8.7 11.4 8.7 12.2 8.7 13.1 8.6
43.0 9.6 7.9 9.7 8.1 10.5 8.1 10.9 8.7 11.3 8.7 12.1 8.6 12.9 8.5
20.0 13.2 10.2 13.6 10.5 14.6 10.5 15.1 11.1 15.5 11.1 16.5 10.9 17.6 10.8
22.5 13.1 10.1 13.5 10.4 14.4 10.4 14.9 11.1 15.4 11.0 16.4 10.9 17.4 10.7
25.0 13.0 10.1 13.3 10.4 14.3 10.3 14.7 11.0 15.2 10.9 16.2 10.8 17.3 10.7
27.5 12.8 10.0 13.2 10.3 14.1 10.2 14.6 10.9 15.1 10.9 16.1 10.8 17.1 10.6
125 30.0 12.7 9.9 13.0 10.2 13.9 10.2 14.4 10.9 14.9 10.8 15.9 10.7 17.0 10.6
(14.0) 32.5 12.6 9.9 12.8 10.1 13.8 10.1 14.3 10.8 14.8 10.7 15.8 10.7 16.8 10.5
35.0 12.4 9.8 12.7 10.1 13.6 10.0 14.0 10.7 14.6 10.7 15.6 10.6 16.7 10.5
37.5 12.3 9.8 12.5 10.0 13.5 10.0 14.0 10.7 14.4 10.6 15.5 10.5 16.5 10.4
40.0 12.2 9.7 12.4 9.9 13.3 9.9 13.8 10.6 14.3 10.6 15.3 10.5 16.4 10.4
43.0 12.0 9.6 12.2 9.8 13.1 9.8 13.6 10.5 14.1 10.5 15.1 10.4 16.2 10.3
20.0 15.1 11.5 15.6 11.9 16.7 11.8 17.2 12.6 17.8 12.5 18.9 12.4 20.1 12.2
22.5 15.0 11.5 15.4 11.8 16.5 11.7 17.0 12.5 17.6 12.4 18.7 12.3 19.9 12.1
25.0 14.8 11.4 15.2 11.7 16.3 11.7 16.8 12.4 17.4 12.3 18.5 12.2 19.7 12.1
27.5 14.7 11.3 15.0 11.6 16.1 11.6 16.7 12.3 17.2 12.3 18.4 12.2 19.6 12.0
140 30.0 14.5 11.2 14.9 11.5 15.9 11.5 16.5 12.2 17.0 12.2 18.2 12.1 19.4 11.9
(16.0) 32.5 14.4 11.2 14.7 11.5 15.8 11.4 16.3 12.2 16.9 12.1 18.0 12.0 19.2 11.9
35.0 14.2 11.1 14.5 11.4 15.6 11.3 16.0 12.0 16.7 12.1 17.8 12.0 19.1 11.8
37.5 14.1 11.0 14.3 11.3 15.4 11.3 15.9 12.0 16.5 12.0 17.7 11.9 18.9 11.8
40.0 13.9 10.9 14.1 11.2 15.2 11.2 15.8 11.9 16.3 11.9 17.5 11.8 18.7 11.7
43.0 13.7 10.9 13.9 11.1 15.0 11.1 15.6 11.9 16.1 11.8 17.3 11.7 18.5 11.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 118


3. Cooling [Ceiling cassette (1-way flow type)]
3-1. Cooling capacity with PUHY,PURY-RP200-250YJM
3. Cooling [Ceiling cassette (1-way flow type)]

PMFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.5 2.0 2.6 2.0 2.8 1.9
22.5 2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.5 2.0 2.6 2.0 2.8 1.9
25.0 2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.4 2.0 2.6 2.0 2.7 1.9
27.5 2.1 1.8 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.1 1.9 2.2 1.8 2.3 2.0 2.3 2.0 2.5 1.9 2.6 1.9
(2.2) 32.5 2.0 1.8 2.1 1.8 2.2 1.8 2.2 2.0 2.3 1.9 2.4 1.9 2.6 1.9
35.0 2.0 1.8 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.2 1.9 2.3 1.9 2.5 1.8
40.0 1.9 1.7 2.0 1.8 2.1 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 1.8
43.0 1.8 1.7 1.9 1.8 2.0 1.7 2.1 1.9 2.1 1.9 2.2 1.8 2.3 1.8
20.0 2.7 2.2 2.8 2.3 2.9 2.3 3.0 2.5 3.1 2.4 3.3 2.4 3.5 2.4
22.5 2.7 2.2 2.8 2.3 2.9 2.3 3.0 2.5 3.1 2.4 3.3 2.4 3.5 2.4
25.0 2.7 2.2 2.8 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
27.5 2.7 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.0 2.4 3.2 2.4 3.4 2.3
25 30.0 2.6 2.2 2.7 2.3 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.3 3.3 2.3
(2.8) 32.5 2.6 2.2 2.6 2.3 2.8 2.2 2.9 2.4 2.9 2.4 3.1 2.3 3.3 2.3
35.0 2.5 2.2 2.6 2.2 2.7 2.2 2.8 2.4 2.9 2.3 3.0 2.3 3.2 2.3
37.5 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.3 2.8 2.3 3.0 2.3 3.1 2.2
40.0 2.4 2.1 2.5 2.2 2.6 2.2 2.7 2.3 2.8 2.3 2.9 2.3 3.1 2.2
43.0 2.4 2.1 2.4 2.2 2.6 2.1 2.6 2.3 2.7 2.3 2.8 2.2 3.0 2.2
20.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.6 2.7
22.5 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.6 2.7
25.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.8 4.2 2.7 4.5 2.7
27.5 3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.6
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.7 2.6 3.9 2.6 4.1 2.6
37.5 3.2 2.4 3.3 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.8 2.6 4.0 2.5
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.7 2.5 3.9 2.5
43.0 3.0 2.4 3.1 2.4 3.3 2.4 3.4 2.6 3.5 2.5 3.6 2.5 3.8 2.5
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.7 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.7 3.3
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.6 3.3
27.5 4.3 3.1 4.4 3.2 4.6 3.2 4.8 3.4 4.9 3.3 5.2 3.3 5.5 3.2
40 30.0 4.2 3.1 4.3 3.2 4.6 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.4 3.2
(4.5) 32.5 4.1 3.1 4.2 3.1 4.5 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.3 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1
37.5 4.0 3.0 4.1 3.1 4.3 3.0 4.4 3.2 4.5 3.2 4.8 3.1 5.0 3.1
40.0 3.9 2.9 4.0 3.0 4.2 3.0 4.3 3.2 4.4 3.1 4.7 3.1 4.9 3.0
43.0 3.8 2.9 3.9 3.0 4.1 2.9 4.2 3.1 4.3 3.1 4.5 3.0 4.8 3.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 119


3. Cooling [Ceiling cassette (1-way flow type)]
3-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PMFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.2 1.9 2.4 1.9 2.5 2.0 2.5 2.0 2.7 2.0 2.9 2.0
22.5 2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.5 2.0 2.6 2.0 2.8 2.0
25.0 2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.4 2.0 2.6 2.0 2.8 1.9
27.5 2.1 1.8 2.1 1.9 2.3 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.6 1.9
(2.2) 32.5 2.0 1.8 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
35.0 2.0 1.8 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.5 1.9
40.0 1.9 1.7 1.9 1.8 2.0 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 1.8
43.0 1.9 1.7 1.9 1.7 2.0 1.7 2.0 1.9 2.1 1.9 2.2 1.8 2.4 1.8
20.0 2.7 2.2 2.8 2.3 3.0 2.3 3.1 2.5 3.2 2.5 3.4 2.4 3.6 2.4
22.5 2.7 2.2 2.8 2.3 3.0 2.3 3.1 2.5 3.2 2.5 3.4 2.4 3.6 2.4
25.0 2.7 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
27.5 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.2 2.4 3.4 2.3
25 30.0 2.6 2.2 2.6 2.3 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.3
(2.8) 32.5 2.5 2.2 2.6 2.2 2.8 2.2 2.8 2.4 2.9 2.4 3.1 2.3 3.3 2.3
35.0 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.4 2.9 2.3 3.0 2.3 3.2 2.3
37.5 2.5 2.1 2.5 2.2 2.6 2.2 2.7 2.3 2.8 2.3 3.0 2.3 3.2 2.3
40.0 2.4 2.1 2.4 2.2 2.6 2.1 2.7 2.3 2.8 2.3 2.9 2.3 3.1 2.2
43.0 2.4 2.1 2.4 2.1 2.5 2.1 2.6 2.3 2.7 2.3 2.8 2.2 3.0 2.2
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.8 4.2 2.8 4.4 2.8 4.7 2.8
22.5 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.8 4.1 2.8 4.3 2.8 4.6 2.7
25.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.8 4.2 2.7 4.5 2.7
27.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.7
32 30.0 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.6
(3.6) 32.5 3.3 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.7 2.6 3.9 2.6 4.2 2.6
37.5 3.2 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.8 2.6 4.1 2.5
40.0 3.1 2.4 3.1 2.5 3.3 2.4 3.4 2.6 3.5 2.6 3.8 2.5 4.0 2.5
43.0 3.0 2.4 3.0 2.4 3.2 2.4 3.3 2.5 3.4 2.5 3.7 2.5 3.9 2.5
20.0 4.4 3.2 4.5 3.3 4.9 3.3 5.0 3.5 5.2 3.5 5.5 3.4 5.8 3.4
22.5 4.4 3.2 4.5 3.3 4.8 3.3 4.9 3.4 5.1 3.4 5.4 3.4 5.7 3.3
25.0 4.3 3.2 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.6 3.3
27.5 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.1 4.2 3.2 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.3 5.4 3.2
(4.5) 32.5 4.1 3.0 4.2 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.3 3.2
35.0 4.0 3.0 4.1 3.1 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1
37.5 3.9 3.0 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.8 3.1 5.1 3.1
40.0 3.9 2.9 3.9 3.0 4.2 3.0 4.3 3.2 4.4 3.1 4.7 3.1 5.0 3.0
43.0 3.8 2.9 3.8 2.9 4.0 2.9 4.2 3.1 4.3 3.1 4.6 3.0 4.8 3.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 120


3. Cooling [Ceiling cassette (1-way flow type)]
3-3. Cooling capacity with PUHY-RP450-650YSJM
PMFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.1 1.9 2.3 1.9 2.4 2.0 2.4 2.0 2.6 2.0 2.8 1.9
22.5 2.1 1.8 2.1 1.9 2.3 1.8 2.3 2.0 2.4 2.0 2.6 2.0 2.7 1.9
25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
27.5 2.0 1.8 2.1 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.0 1.8 2.2 1.8 2.3 2.0 2.3 2.0 2.5 1.9 2.7 1.9
(2.2) 32.5 2.0 1.8 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
40.0 1.9 1.7 1.9 1.8 2.1 1.8 2.2 1.9 2.2 1.9 2.4 1.9 2.6 1.9
43.0 1.9 1.7 1.9 1.8 2.1 1.8 2.1 1.9 2.2 1.9 2.4 1.9 2.5 1.9
20.0 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
22.5 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
25.0 2.6 2.2 2.7 2.3 2.9 2.3 2.9 2.4 3.0 2.4 3.2 2.4 3.5 2.4
27.5 2.6 2.2 2.6 2.3 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.3
25 30.0 2.5 2.2 2.6 2.2 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.3
(2.8) 32.5 2.5 2.2 2.6 2.2 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.3 3.4 2.3
35.0 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.4 2.9 2.4 3.1 2.3 3.3 2.3
37.5 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.4 2.9 2.3 3.1 2.3 3.3 2.3
40.0 2.4 2.1 2.5 2.2 2.7 2.2 2.8 2.3 2.9 2.3 3.1 2.3 3.3 2.3
43.0 2.4 2.1 2.4 2.2 2.6 2.2 2.7 2.3 2.8 2.3 3.0 2.3 3.2 2.3
20.0 3.4 2.6 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.5 2.7
22.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.8 4.0 2.7 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.8 2.7 4.0 2.6 4.3 2.6
37.5 3.2 2.4 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.6 4.0 2.6 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.3 3.3 5.6 3.3
25.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.3
27.5 4.1 3.1 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.3 5.1 3.3 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.2
37.5 4.0 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.2
40.0 3.9 3.0 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.2 5.3 3.2
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.9 3.2 5.2 3.1
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 121


3. Cooling [Ceiling cassette (1-way flow type)]
3-4. Cooling capacity with PUHY-RP700-800YSJM
PMFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.2 1.9 2.4 1.9 2.4 2.0 2.5 2.0 2.7 2.0 2.9 2.0
22.5 2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.5 2.0 2.6 2.0 2.8 2.0
25.0 2.1 1.8 2.1 1.9 2.3 1.9 2.4 2.0 2.4 2.0 2.6 2.0 2.8 1.9
27.5 2.0 1.8 2.1 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.6 2.0 2.7 1.9
20 30.0 2.0 1.8 2.0 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
(2.2) 32.5 1.9 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
37.5 1.9 1.7 1.9 1.8 2.1 1.8 2.1 1.9 2.2 1.9 2.4 1.9 2.5 1.9
40.0 1.8 1.7 1.9 1.8 2.0 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.5 1.8
43.0 1.8 1.7 1.8 1.7 2.0 1.7 2.1 1.9 2.1 1.9 2.3 1.9 2.4 1.8
20.0 2.7 2.2 2.8 2.3 3.0 2.3 3.1 2.5 3.2 2.5 3.4 2.4 3.7 2.4
22.5 2.7 2.2 2.8 2.3 3.0 2.3 3.1 2.5 3.2 2.5 3.4 2.4 3.6 2.4
25.0 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
27.5 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
25 30.0 2.5 2.2 2.6 2.2 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.3
(2.8) 32.5 2.5 2.1 2.6 2.2 2.7 2.2 2.8 2.4 2.9 2.4 3.1 2.3 3.3 2.3
35.0 2.4 2.1 2.5 2.2 2.7 2.2 2.8 2.4 2.9 2.3 3.1 2.3 3.3 2.3
37.5 2.4 2.1 2.5 2.2 2.6 2.2 2.7 2.3 2.8 2.3 3.0 2.3 3.2 2.3
40.0 2.3 2.1 2.4 2.2 2.6 2.1 2.7 2.3 2.8 2.3 3.0 2.3 3.1 2.3
43.0 2.3 2.1 2.4 2.1 2.5 2.1 2.6 2.3 2.7 2.3 2.9 2.3 3.1 2.2
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.8 4.1 2.8 4.4 2.8 4.7 2.8
22.5 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.1 2.8 4.3 2.8 4.6 2.7
25.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.5 2.7
27.5 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.5 2.7
32 30.0 3.2 2.5 3.4 2.6 3.6 2.5 3.7 2.7 3.9 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.3 2.6
35.0 3.1 2.4 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.6 4.0 2.6 4.2 2.6
37.5 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.1 2.6
40.0 3.0 2.4 3.1 2.4 3.3 2.4 3.4 2.6 3.6 2.6 3.8 2.6 4.0 2.5
43.0 2.9 2.3 3.0 2.4 3.2 2.4 3.4 2.6 3.5 2.5 3.7 2.5 3.9 2.5
20.0 4.3 3.2 4.5 3.3 4.8 3.3 5.0 3.5 5.2 3.5 5.5 3.4 5.9 3.4
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.1 3.4 5.4 3.4 5.8 3.3
25.0 4.2 3.1 4.3 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
27.5 4.1 3.1 4.3 3.2 4.6 3.2 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.3
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.3 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.4 3.2
35.0 3.9 3.0 4.0 3.1 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.3 3.1
37.5 3.8 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.8 3.2 5.2 3.1
40.0 3.8 2.9 3.9 3.0 4.2 3.0 4.3 3.2 4.5 3.1 4.8 3.1 5.1 3.1
43.0 3.7 2.8 3.8 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.6 3.1 4.9 3.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 122


3. Cooling [Ceiling cassette (1-way flow type)]
3-5. Cooling capacity with PUHY-RP850-900YSJM
PMFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.1 1.9 2.3 1.9 2.4 2.0 2.4 2.0 2.6 2.0 2.8 1.9
22.5 2.1 1.8 2.1 1.9 2.3 1.8 2.3 2.0 2.4 2.0 2.6 2.0 2.7 1.9
25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
27.5 2.0 1.8 2.1 1.8 2.2 1.8 2.3 2.0 2.4 2.0 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.0 1.8 2.2 1.8 2.3 2.0 2.3 2.0 2.5 1.9 2.7 1.9
(2.2) 32.5 2.0 1.8 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
40.0 1.9 1.7 1.9 1.8 2.1 1.8 2.2 1.9 2.2 1.9 2.4 1.9 2.6 1.9
43.0 1.9 1.7 1.9 1.8 2.1 1.8 2.1 1.9 2.2 1.9 2.4 1.9 2.5 1.9
20.0 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
22.5 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.1 2.4 3.3 2.4 3.5 2.4
25.0 2.6 2.2 2.7 2.3 2.9 2.3 2.9 2.4 3.0 2.4 3.2 2.4 3.5 2.4
27.5 2.6 2.2 2.6 2.3 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.3
25 30.0 2.5 2.2 2.6 2.2 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.3
(2.8) 32.5 2.5 2.2 2.6 2.2 2.8 2.2 2.9 2.4 3.0 2.4 3.2 2.3 3.4 2.3
35.0 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.4 2.9 2.4 3.1 2.3 3.3 2.3
37.5 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.4 2.9 2.3 3.1 2.3 3.3 2.3
40.0 2.4 2.1 2.5 2.2 2.7 2.2 2.8 2.3 2.9 2.3 3.1 2.3 3.3 2.3
43.0 2.4 2.1 2.4 2.2 2.6 2.2 2.7 2.3 2.8 2.3 3.0 2.3 3.2 2.3
20.0 3.4 2.6 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.5 2.7
22.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.8 4.0 2.7 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.8 2.7 4.0 2.6 4.3 2.6
37.5 3.2 2.4 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.6 4.0 2.6 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.3 3.3 5.6 3.3
25.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.3
27.5 4.1 3.1 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.3 5.1 3.3 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.2
37.5 4.0 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.2
40.0 3.9 3.0 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.2 5.3 3.2
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.9 3.2 5.2 3.1
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 123


4. Cooling [Ceiling cassette (2-way flow type)]
4-1. Cooling capacity with PUHY,PURY-RP200-250YJM
4. Cooling [Ceiling cassette (2-way flow type)]

PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.1 2.6 2.0 2.8 2.0
22.5 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.1 2.6 2.0 2.8 2.0
25.0 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.4 2.1 2.6 2.0 2.7 2.0
27.5 2.1 1.9 2.1 1.9 2.3 1.9 2.3 2.1 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.5 2.0 2.6 2.0
(2.2) 32.5 2.0 1.8 2.1 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
35.0 2.0 1.8 2.0 1.9 2.1 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.5 1.9
37.5 1.9 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.2 2.0 2.3 1.9 2.5 1.9
40.0 1.9 1.8 2.0 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.3 1.9 2.4 1.9
43.0 1.8 1.8 1.9 1.8 2.0 1.8 2.1 2.0 2.1 1.9 2.2 1.9 2.3 1.9
20.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
27.5 2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.6 2.1 2.7 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.3 2.2
(2.8) 32.5 2.6 2.1 2.6 2.1 2.8 2.1 2.9 2.3 2.9 2.2 3.1 2.2 3.3 2.2
35.0 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.8 2.2 3.0 2.2 3.1 2.1
40.0 2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 2.9 2.1 3.1 2.1
43.0 2.4 2.0 2.4 2.1 2.6 2.0 2.6 2.2 2.7 2.2 2.8 2.1 3.0 2.1
20.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.6 2.7
22.5 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.8 4.3 2.7 4.6 2.7
25.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.7 4.2 2.7 4.5 2.7
27.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5
37.5 3.2 2.4 3.3 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.8 2.5 4.0 2.5
40.0 3.1 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.6 2.6 3.7 2.5 3.9 2.5
43.0 3.0 2.4 3.1 2.4 3.3 2.4 3.4 2.6 3.5 2.5 3.6 2.5 3.8 2.4
20.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.1 5.7 3.1
22.5 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.1 5.7 3.1
25.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.1 5.6 3.1
27.5 4.3 3.0 4.4 3.1 4.6 3.0 4.8 3.2 4.9 3.1 5.2 3.1 5.5 3.0
40 30.0 4.2 2.9 4.3 3.0 4.6 3.0 4.7 3.1 4.8 3.1 5.1 3.0 5.4 3.0
(4.5) 32.5 4.1 2.9 4.2 3.0 4.5 2.9 4.6 3.1 4.7 3.1 5.0 3.0 5.3 3.0
35.0 4.0 2.9 4.1 2.9 4.4 2.9 4.5 3.0 4.6 3.0 4.9 3.0 5.2 2.9
37.5 4.0 2.8 4.1 2.9 4.3 2.9 4.4 3.0 4.5 3.0 4.8 2.9 5.0 2.9
40.0 3.9 2.8 4.0 2.9 4.2 2.8 4.3 3.0 4.4 2.9 4.7 2.9 4.9 2.8
43.0 3.8 2.7 3.9 2.8 4.1 2.8 4.2 2.9 4.3 2.9 4.5 2.8 4.8 2.8
20.0 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.2 4.1 6.6 4.0 7.1 4.0
22.5 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.2 4.1 6.6 4.0 7.1 4.0
25.0 5.3 3.8 5.5 3.9 5.9 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 3.9
27.5 5.3 3.8 5.5 3.9 5.8 3.9 5.9 4.1 6.1 4.0 6.4 4.0 6.8 3.9
50 30.0 5.2 3.8 5.4 3.9 5.7 3.8 5.8 4.0 6.0 4.0 6.3 3.9 6.7 3.8
(5.6) 32.5 5.1 3.7 5.3 3.8 5.6 3.8 5.7 4.0 5.9 3.9 6.2 3.9 6.6 3.8
35.0 5.0 3.7 5.2 3.8 5.5 3.7 5.6 3.9 5.8 3.9 6.1 3.8 6.4 3.7
37.5 4.9 3.6 5.1 3.7 5.4 3.7 5.5 3.9 5.6 3.8 5.9 3.8 6.3 3.7
40.0 4.8 3.6 5.0 3.7 5.3 3.6 5.4 3.8 5.5 3.8 5.8 3.7 6.1 3.6
43.0 4.7 3.5 4.8 3.6 5.1 3.6 5.3 3.8 5.4 3.7 5.6 3.6 6.0 3.6
20.0 6.7 4.7 7.0 4.9 7.5 4.8 7.7 5.1 7.9 5.1 8.4 5.0 9.0 4.9
22.5 6.7 4.7 7.0 4.9 7.5 4.8 7.7 5.1 7.9 5.1 8.4 5.0 9.0 4.9
25.0 6.7 4.7 7.0 4.9 7.5 4.8 7.7 5.1 7.9 5.0 8.3 4.9 8.8 4.9
27.5 6.7 4.7 6.9 4.8 7.3 4.8 7.5 5.0 7.7 5.0 8.1 4.9 8.7 4.8
63 30.0 6.6 4.7 6.8 4.8 7.2 4.7 7.4 4.9 7.6 4.9 8.0 4.8 8.5 4.7
(7.1) 32.5 6.5 4.6 6.7 4.7 7.1 4.6 7.2 4.9 7.4 4.8 7.8 4.7 8.3 4.7
35.0 6.4 4.5 6.5 4.6 6.9 4.6 7.1 4.8 7.3 4.8 7.7 4.7 8.1 4.6
37.5 6.2 4.5 6.4 4.6 6.8 4.5 7.0 4.8 7.2 4.7 7.5 4.6 8.0 4.5
40.0 6.1 4.4 6.3 4.5 6.7 4.5 6.8 4.7 7.0 4.7 7.4 4.6 7.8 4.5
43.0 6.0 4.3 6.1 4.4 6.5 4.4 6.7 4.6 6.9 4.6 7.2 4.5 7.6 4.4
20.0 8.6 6.2 8.9 6.4 9.5 6.4 9.7 6.8 10.0 6.7 10.6 6.6 11.4 6.6
22.5 8.6 6.2 8.9 6.4 9.5 6.4 9.7 6.8 10.0 6.7 10.6 6.6 11.4 6.6
25.0 8.6 6.2 8.9 6.4 9.5 6.4 9.7 6.7 10.0 6.7 10.5 6.6 11.2 6.5
27.5 8.5 6.2 8.8 6.4 9.3 6.3 9.5 6.7 9.8 6.6 10.3 6.5 11.0 6.4
80 30.0 8.4 6.2 8.6 6.3 9.1 6.3 9.4 6.6 9.6 6.5 10.1 6.4 10.8 6.3
(9.0) 32.5 8.2 6.1 8.5 6.2 8.9 6.2 9.2 6.5 9.4 6.5 9.9 6.3 10.5 6.3
35.0 8.1 6.0 8.3 6.2 8.8 6.1 9.0 6.4 9.2 6.4 9.7 6.3 10.3 6.2
37.5 7.9 5.9 8.1 6.1 8.6 6.0 8.8 6.4 9.1 6.3 9.5 6.2 10.1 6.1
40.0 7.7 5.8 8.0 6.0 8.4 5.9 8.7 6.3 8.9 6.2 9.3 6.1 9.9 6.0
43.0 7.6 5.8 7.8 5.9 8.2 5.9 8.5 6.2 8.7 6.2 9.1 6.0 9.6 5.9
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 124


4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.6 7.7 11.0 7.9 11.8 7.9 12.1 8.3 12.5 8.2 13.2 8.1 14.2 8.0
22.5 10.6 7.7 11.0 7.9 11.8 7.9 12.1 8.3 12.5 8.2 13.2 8.1 14.2 8.0
25.0 10.6 7.7 11.0 7.9 11.8 7.9 12.1 8.3 12.4 8.2 13.1 8.1 13.9 8.0
27.5 10.6 7.7 10.9 7.9 11.6 7.8 11.9 8.2 12.2 8.1 12.9 8.0 13.7 7.9
100 30.0 10.4 7.6 10.7 7.8 11.3 7.7 11.6 8.1 12.0 8.0 12.6 7.9 13.4 7.8
(11.2) 32.5 10.2 7.5 10.5 7.7 11.1 7.6 11.4 8.0 11.7 7.9 12.4 7.8 13.1 7.7
35.0 10.0 7.4 10.3 7.6 10.9 7.5 11.2 7.9 11.5 7.8 12.1 7.7 12.8 7.6
37.5 9.8 7.3 10.1 7.5 10.7 7.4 11.0 7.8 11.3 7.7 11.9 7.6 12.6 7.5
40.0 9.6 7.2 9.9 7.4 10.5 7.3 10.8 7.7 11.1 7.6 11.6 7.5 12.3 7.4
43.0 9.4 7.1 9.7 7.3 10.2 7.2 10.5 7.6 10.8 7.5 11.3 7.4 12.0 7.2
20.0 13.3 9.8 13.8 10.1 14.7 10.0 15.2 10.6 15.6 10.5 16.6 10.4 17.7 10.2
22.5 13.3 9.8 13.8 10.1 14.7 10.0 15.2 10.6 15.6 10.5 16.6 10.4 17.7 10.2
25.0 13.3 9.8 13.8 10.1 14.7 10.0 15.1 10.5 15.5 10.4 16.4 10.3 17.4 10.1
27.5 13.3 9.7 13.6 10.0 14.4 9.9 14.8 10.4 15.2 10.3 16.1 10.2 17.1 10.0
125 30.0 13.0 9.6 13.4 9.9 14.2 9.8 14.6 10.3 14.9 10.2 15.8 10.0 16.7 9.9
(14.0) 32.5 12.8 9.5 13.2 9.8 13.9 9.6 14.3 10.2 14.7 10.1 15.4 9.9 16.4 9.8
35.0 12.5 9.4 12.9 9.6 13.7 9.5 14.0 10.1 14.4 10.0 15.1 9.8 16.0 9.7
37.5 12.3 9.3 12.7 9.5 13.4 9.4 13.8 9.9 14.1 9.9 14.8 9.7 15.7 9.5
40.0 12.1 9.1 12.4 9.4 13.1 9.3 13.5 9.8 13.8 9.7 14.5 9.6 15.4 9.4
43.0 11.8 9.0 12.1 9.3 12.8 9.1 13.2 9.7 13.5 9.6 14.1 9.4 15.0 9.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 125


4. Cooling [Ceiling cassette (2-way flow type)]
4-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.2 2.0 2.4 2.0 2.5 2.1 2.5 2.1 2.7 2.1 2.9 2.0
22.5 2.1 1.9 2.2 2.0 2.3 1.9 2.4 2.1 2.5 2.1 2.6 2.1 2.8 2.0
25.0 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.4 2.1 2.6 2.0 2.8 2.0
27.5 2.1 1.9 2.1 1.9 2.3 1.9 2.3 2.1 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.0
(2.2) 32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.6 2.0
35.0 2.0 1.8 2.0 1.9 2.1 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.5 1.9
37.5 1.9 1.8 2.0 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.3 1.9 2.5 1.9
40.0 1.9 1.8 1.9 1.8 2.0 1.8 2.1 2.0 2.2 2.0 2.3 1.9 2.4 1.9
43.0 1.9 1.8 1.9 1.8 2.0 1.8 2.0 1.9 2.1 1.9 2.2 1.9 2.4 1.9
20.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
22.5 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.3 3.4 2.3 3.6 2.3
25.0 2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.2 2.3 3.4 2.2
25 30.0 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.8 2.3 2.9 2.2 3.1 2.2 3.3 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.1
40.0 2.4 2.0 2.4 2.1 2.6 2.0 2.7 2.2 2.8 2.2 2.9 2.1 3.1 2.1
43.0 2.4 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.1 2.8 2.1 3.0 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.8 4.2 2.8 4.4 2.8 4.7 2.7
22.5 3.5 2.6 3.6 2.7 3.8 2.6 4.0 2.8 4.1 2.8 4.3 2.7 4.6 2.7
25.0 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.0 2.7 4.2 2.7 4.5 2.7
27.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.6
32 30.0 3.3 2.5 3.4 2.6 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
(3.6) 32.5 3.3 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.2 2.5
37.5 3.2 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.6 2.6 3.8 2.6 4.1 2.5
40.0 3.1 2.4 3.1 2.4 3.3 2.4 3.4 2.6 3.5 2.6 3.8 2.5 4.0 2.5
43.0 3.0 2.4 3.0 2.4 3.2 2.4 3.3 2.5 3.4 2.5 3.7 2.5 3.9 2.4
20.0 4.4 3.0 4.5 3.1 4.9 3.1 5.0 3.3 5.2 3.3 5.5 3.2 5.8 3.2
22.5 4.4 3.0 4.5 3.1 4.8 3.1 4.9 3.2 5.1 3.2 5.4 3.2 5.7 3.1
25.0 4.3 3.0 4.4 3.1 4.7 3.0 4.9 3.2 5.0 3.2 5.3 3.1 5.6 3.1
27.5 4.2 3.0 4.3 3.0 4.6 3.0 4.8 3.2 4.9 3.1 5.2 3.1 5.5 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.1 3.1 5.4 3.0
(4.5) 32.5 4.1 2.9 4.2 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.0 3.0 5.3 3.0
35.0 4.0 2.9 4.1 2.9 4.3 2.9 4.5 3.0 4.6 3.0 4.9 3.0 5.2 2.9
37.5 3.9 2.8 4.0 2.9 4.2 2.8 4.4 3.0 4.5 3.0 4.8 2.9 5.1 2.9
40.0 3.9 2.8 3.9 2.8 4.2 2.8 4.3 2.9 4.4 2.9 4.7 2.9 5.0 2.8
43.0 3.8 2.7 3.8 2.8 4.0 2.7 4.2 2.9 4.3 2.9 4.6 2.8 4.8 2.8
20.0 5.4 3.9 5.6 4.0 6.1 4.0 6.3 4.2 6.5 4.2 6.9 4.1 7.3 4.1
22.5 5.4 3.9 5.6 4.0 6.0 3.9 6.2 4.2 6.3 4.1 6.7 4.1 7.1 4.0
25.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
27.5 5.3 3.8 5.4 3.9 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
50 30.0 5.2 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.7 3.9
(5.6) 32.5 5.1 3.7 5.2 3.8 5.5 3.7 5.7 3.9 5.9 3.9 6.2 3.9 6.6 3.8
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.7 3.9 6.1 3.8 6.5 3.8
37.5 4.9 3.6 5.0 3.7 5.3 3.6 5.5 3.8 5.6 3.8 6.0 3.8 6.3 3.7
40.0 4.8 3.6 4.9 3.6 5.2 3.6 5.3 3.8 5.5 3.8 5.8 3.7 6.2 3.7
43.0 4.7 3.5 4.7 3.5 5.0 3.5 5.2 3.7 5.4 3.7 5.7 3.7 6.0 3.6
20.0 6.9 4.8 7.1 4.9 7.7 4.9 7.9 5.2 8.2 5.2 8.7 5.1 9.2 5.0
22.5 6.9 4.8 7.1 4.9 7.6 4.9 7.8 5.1 8.0 5.1 8.5 5.0 9.1 5.0
25.0 6.8 4.7 7.0 4.8 7.4 4.8 7.7 5.1 7.9 5.0 8.4 5.0 8.9 4.9
27.5 6.7 4.7 6.8 4.8 7.3 4.8 7.5 5.0 7.7 5.0 8.2 4.9 8.7 4.8
63 30.0 6.5 4.6 6.7 4.7 7.1 4.7 7.4 4.9 7.6 4.9 8.1 4.8 8.5 4.8
(7.1) 32.5 6.4 4.6 6.6 4.6 7.0 4.6 7.2 4.9 7.4 4.8 7.9 4.8 8.4 4.7
35.0 6.3 4.5 6.4 4.6 6.8 4.5 7.1 4.8 7.3 4.8 7.7 4.7 8.2 4.6
37.5 6.2 4.5 6.3 4.5 6.7 4.5 6.9 4.7 7.1 4.7 7.6 4.6 8.0 4.6
40.0 6.1 4.4 6.2 4.4 6.6 4.4 6.8 4.7 7.0 4.6 7.4 4.6 7.8 4.5
43.0 6.0 4.3 6.0 4.4 6.4 4.3 6.6 4.6 6.8 4.6 7.2 4.5 7.6 4.4
20.0 8.7 6.3 9.0 6.5 9.7 6.5 10.1 6.9 10.4 6.9 11.0 6.8 11.7 6.7
22.5 8.7 6.3 9.0 6.5 9.6 6.5 9.9 6.8 10.2 6.8 10.8 6.7 11.5 6.6
25.0 8.6 6.3 8.8 6.4 9.4 6.4 9.7 6.7 10.0 6.7 10.6 6.6 11.3 6.5
27.5 8.4 6.2 8.6 6.3 9.2 6.3 9.5 6.7 9.8 6.6 10.4 6.5 11.0 6.4
80 30.0 8.3 6.1 8.5 6.3 9.0 6.2 9.3 6.6 9.6 6.5 10.2 6.5 10.8 6.4
(9.0) 32.5 8.2 6.1 8.3 6.2 8.9 6.1 9.1 6.5 9.4 6.5 10.0 6.4 10.6 6.3
35.0 8.0 6.0 8.1 6.1 8.7 6.0 9.0 6.4 9.2 6.4 9.8 6.3 10.4 6.2
37.5 7.9 5.9 8.0 6.0 8.5 6.0 8.8 6.3 9.0 6.3 9.6 6.2 10.2 6.1
40.0 7.7 5.8 7.8 5.9 8.3 5.9 8.6 6.3 8.8 6.2 9.4 6.1 9.9 6.0
43.0 7.6 5.8 7.6 5.8 8.1 5.8 8.4 6.2 8.6 6.1 9.1 6.0 9.7 6.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 126


4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.9 7.8 11.3 8.0 12.1 8.0 12.5 8.5 12.9 8.4 13.7 8.3 14.5 8.2
22.5 10.8 7.8 11.2 8.0 11.9 7.9 12.3 8.4 12.7 8.3 13.5 8.2 14.3 8.1
25.0 10.7 7.7 11.0 7.9 11.7 7.8 12.1 8.3 12.5 8.2 13.2 8.1 14.0 8.0
27.5 10.5 7.6 10.8 7.8 11.5 7.7 11.8 8.2 12.2 8.1 13.0 8.0 13.7 7.9
100 30.0 10.3 7.5 10.6 7.7 11.2 7.6 11.6 8.1 12.0 8.0 12.7 7.9 13.5 7.8
(11.2) 32.5 10.2 7.4 10.3 7.6 11.0 7.5 11.4 8.0 11.7 7.9 12.4 7.8 13.2 7.7
35.0 10.0 7.3 10.1 7.5 10.8 7.4 11.2 7.9 11.5 7.8 12.2 7.7 12.9 7.6
37.5 9.8 7.3 9.9 7.4 10.6 7.3 10.9 7.7 11.2 7.7 11.9 7.6 12.6 7.5
40.0 9.6 7.2 9.7 7.3 10.3 7.2 10.7 7.6 11.0 7.6 11.7 7.5 12.4 7.4
43.0 9.4 7.1 9.5 7.1 10.1 7.1 10.4 7.5 10.7 7.5 11.4 7.4 12.1 7.3
20.0 13.6 9.9 14.1 10.2 15.1 10.2 15.7 10.8 16.2 10.7 17.2 10.6 18.2 10.4
22.5 13.6 9.9 14.0 10.2 14.9 10.1 15.4 10.7 15.9 10.6 16.8 10.5 17.8 10.3
25.0 13.3 9.8 13.7 10.0 14.6 10.0 15.1 10.5 15.6 10.5 16.5 10.3 17.5 10.2
27.5 13.1 9.7 13.5 9.9 14.3 9.8 14.8 10.4 15.3 10.3 16.2 10.2 17.2 10.1
125 30.0 12.9 9.6 13.2 9.8 14.1 9.7 14.5 10.3 15.0 10.2 15.9 10.1 16.8 9.9
(14.0) 32.5 12.7 9.4 12.9 9.6 13.8 9.6 14.2 10.1 14.7 10.1 15.6 10.0 16.5 9.8
35.0 12.5 9.3 12.7 9.5 13.5 9.4 14.0 10.1 14.4 10.0 15.2 9.8 16.2 9.7
37.5 12.3 9.2 12.4 9.4 13.2 9.3 13.6 9.9 14.1 9.8 14.9 9.7 15.8 9.6
40.0 12.0 9.1 12.2 9.3 12.9 9.2 13.3 9.8 13.8 9.7 14.6 9.6 15.5 9.4
43.0 11.8 9.0 11.8 9.1 12.6 9.0 13.0 9.6 13.4 9.6 14.2 9.5 15.1 9.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 127


4. Cooling [Ceiling cassette (2-way flow type)]
4-3. Cooling capacity with PUHY-RP450-650YSJM
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.1 1.9 2.3 1.9 2.4 2.1 2.4 2.1 2.6 2.0 2.8 2.0
22.5 2.1 1.9 2.1 1.9 2.3 1.9 2.3 2.1 2.4 2.0 2.6 2.0 2.7 2.0
25.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.5 2.0 2.7 2.0
(2.2) 32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
35.0 2.0 1.8 2.0 1.9 2.1 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
37.5 1.9 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.6 2.0
40.0 1.9 1.8 1.9 1.8 2.1 1.8 2.2 2.0 2.2 2.0 2.4 2.0 2.6 1.9
43.0 1.9 1.8 1.9 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.4 2.0 2.5 1.9
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
25.0 2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.5 2.2
27.5 2.6 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
35.0 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
43.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
20.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.5 2.7
22.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 4.0 2.7 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.5 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.3 2.5 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.8 2.6 4.0 2.6 4.3 2.6
37.5 3.2 2.4 3.2 2.5 3.5 2.5 3.6 2.6 3.7 2.6 4.0 2.6 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.4 3.4 2.4 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
20.0 4.3 3.0 4.4 3.1 4.7 3.0 4.8 3.2 5.0 3.2 5.3 3.1 5.7 3.1
22.5 4.2 3.0 4.3 3.0 4.6 3.0 4.8 3.2 4.9 3.2 5.3 3.1 5.6 3.1
25.0 4.2 2.9 4.3 3.0 4.6 3.0 4.7 3.1 4.9 3.1 5.2 3.1 5.6 3.1
27.5 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.2 3.1 5.5 3.0
40 30.0 4.1 2.9 4.2 2.9 4.5 2.9 4.6 3.1 4.8 3.1 5.1 3.1 5.5 3.0
(4.5) 32.5 4.0 2.9 4.1 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.1 3.0 5.4 3.0
35.0 4.0 2.8 4.1 2.9 4.4 2.9 4.5 3.0 4.7 3.0 5.0 3.0 5.4 3.0
37.5 4.0 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.6 3.0 5.0 3.0 5.3 3.0
40.0 3.9 2.8 4.0 2.8 4.3 2.8 4.4 3.0 4.6 3.0 4.9 3.0 5.3 3.0
43.0 3.9 2.8 3.9 2.8 4.2 2.8 4.4 3.0 4.5 3.0 4.9 3.0 5.2 2.9
20.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.0 6.6 4.0 7.0 4.0
25.0 5.2 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.9 3.9
50 30.0 5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.7 5.5 3.7 5.7 4.0 5.9 3.9 6.3 3.9 6.7 3.9
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.7 3.8
37.5 4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.6 3.8
40.0 4.9 3.6 4.9 3.6 5.3 3.6 5.5 3.9 5.7 3.9 6.1 3.8 6.5 3.8
43.0 4.8 3.5 4.9 3.6 5.2 3.6 5.4 3.8 5.6 3.8 6.0 3.8 6.5 3.8
20.0 6.7 4.7 6.9 4.8 7.4 4.8 7.6 5.1 7.9 5.0 8.4 5.0 8.9 4.9
22.5 6.6 4.7 6.8 4.8 7.3 4.8 7.6 5.0 7.8 5.0 8.3 4.9 8.8 4.9
25.0 6.6 4.6 6.8 4.7 7.2 4.7 7.5 5.0 7.7 5.0 8.2 4.9 8.8 4.9
27.5 6.5 4.6 6.7 4.7 7.2 4.7 7.4 4.9 7.6 4.9 8.2 4.9 8.7 4.8
63 30.0 6.4 4.6 6.6 4.7 7.1 4.7 7.3 4.9 7.6 4.9 8.1 4.8 8.6 4.8
(7.1) 32.5 6.4 4.5 6.5 4.6 7.0 4.6 7.2 4.9 7.5 4.9 8.0 4.8 8.5 4.8
35.0 6.3 4.5 6.4 4.6 6.9 4.6 7.1 4.8 7.4 4.8 7.9 4.8 8.5 4.7
37.5 6.2 4.5 6.3 4.5 6.8 4.5 7.1 4.8 7.3 4.8 7.8 4.8 8.4 4.7
40.0 6.2 4.4 6.3 4.5 6.7 4.5 7.0 4.8 7.2 4.8 7.8 4.7 8.3 4.7
43.0 6.1 4.4 6.2 4.5 6.7 4.5 6.9 4.7 7.1 4.7 7.7 4.7 8.2 4.6
20.0 8.5 6.2 8.8 6.4 9.4 6.4 9.7 6.7 10.0 6.7 10.6 6.6 11.3 6.5
22.5 8.4 6.2 8.7 6.3 9.3 6.3 9.6 6.7 9.9 6.7 10.5 6.6 11.2 6.5
25.0 8.3 6.1 8.6 6.3 9.2 6.3 9.5 6.6 9.8 6.6 10.4 6.5 11.1 6.5
27.5 8.3 6.1 8.5 6.2 9.1 6.2 9.4 6.6 9.7 6.6 10.3 6.5 11.0 6.4
80 30.0 8.2 6.1 8.4 6.2 9.0 6.2 9.3 6.6 9.6 6.5 10.2 6.5 10.9 6.4
(9.0) 32.5 8.1 6.0 8.3 6.1 8.9 6.1 9.2 6.5 9.5 6.5 10.1 6.4 10.8 6.4
35.0 8.0 6.0 8.1 6.1 8.8 6.1 9.0 6.4 9.4 6.4 10.0 6.4 10.7 6.3
37.5 7.9 5.9 8.0 6.1 8.7 6.0 9.0 6.4 9.3 6.4 9.9 6.4 10.6 6.3
40.0 7.8 5.9 7.9 6.0 8.6 6.0 8.9 6.4 9.2 6.4 9.8 6.3 10.5 6.3
43.0 7.7 5.8 7.8 5.9 8.4 5.9 8.7 6.3 9.1 6.3 9.7 6.3 10.4 6.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 128


4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.6 7.6 10.9 7.8 11.7 7.8 12.0 8.3 12.4 8.2 13.2 8.1 14.1 8.0
22.5 10.5 7.6 10.8 7.8 11.5 7.8 11.9 8.2 12.3 8.2 13.1 8.1 13.9 8.0
25.0 10.4 7.5 10.6 7.7 11.4 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
27.5 10.3 7.5 10.5 7.7 11.3 7.6 11.7 8.1 12.1 8.1 12.9 8.0 13.7 7.9
100 30.0 10.2 7.4 10.4 7.6 11.2 7.6 11.5 8.0 11.9 8.0 12.7 7.9 13.6 7.8
(11.2) 32.5 10.1 7.4 10.3 7.5 11.0 7.5 11.4 8.0 11.8 7.9 12.6 7.9 13.5 7.8
35.0 9.9 7.3 10.1 7.5 10.9 7.5 11.2 7.9 11.7 7.9 12.5 7.8 13.3 7.7
37.5 9.8 7.3 10.0 7.4 10.8 7.4 11.2 7.9 11.6 7.8 12.4 7.8 13.2 7.7
40.0 9.7 7.2 9.9 7.4 10.6 7.3 11.0 7.8 11.4 7.8 12.2 7.7 13.1 7.7
43.0 9.6 7.2 9.7 7.3 10.5 7.3 10.9 7.7 11.3 7.7 12.1 7.7 12.9 7.6
20.0 13.2 9.7 13.6 10.0 14.6 9.9 15.1 10.5 15.5 10.5 16.5 10.3 17.6 10.2
22.5 13.1 9.7 13.5 9.9 14.4 9.9 14.9 10.4 15.4 10.4 16.4 10.3 17.4 10.2
25.0 13.0 9.6 13.3 9.8 14.3 9.8 14.7 10.4 15.2 10.3 16.2 10.2 17.3 10.1
27.5 12.8 9.5 13.2 9.8 14.1 9.7 14.6 10.3 15.1 10.3 16.1 10.2 17.1 10.0
125 30.0 12.7 9.5 13.0 9.7 13.9 9.6 14.4 10.2 14.9 10.2 15.9 10.1 17.0 10.0
(14.0) 32.5 12.6 9.4 12.8 9.6 13.8 9.6 14.3 10.2 14.8 10.1 15.8 10.0 16.8 9.9
35.0 12.4 9.3 12.7 9.5 13.6 9.5 14.0 10.1 14.6 10.1 15.6 10.0 16.7 9.9
37.5 12.3 9.3 12.5 9.4 13.5 9.4 14.0 10.0 14.4 10.0 15.5 9.9 16.5 9.8
40.0 12.2 9.2 12.4 9.4 13.3 9.4 13.8 10.0 14.3 9.9 15.3 9.9 16.4 9.8
43.0 12.0 9.1 12.2 9.3 13.1 9.3 13.6 9.9 14.1 9.9 15.1 9.8 16.2 9.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 129


4. Cooling [Ceiling cassette (2-way flow type)]
4-4. Cooling capacity with PUHY-RP700-800YSJM
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.2 2.0 2.4 1.9 2.4 2.1 2.5 2.1 2.7 2.1 2.9 2.0
22.5 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.1 2.5 2.1 2.6 2.1 2.8 2.0
25.0 2.1 1.9 2.1 1.9 2.3 1.9 2.4 2.1 2.4 2.1 2.6 2.0 2.8 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.6 2.0 2.7 2.0
20 30.0 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
(2.2) 32.5 1.9 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
35.0 1.9 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.6 1.9
37.5 1.9 1.8 1.9 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.4 2.0 2.5 1.9
40.0 1.8 1.8 1.9 1.8 2.0 1.8 2.1 2.0 2.2 2.0 2.3 1.9 2.5 1.9
43.0 1.8 1.7 1.8 1.8 2.0 1.8 2.1 1.9 2.1 1.9 2.3 1.9 2.4 1.9
20.0 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.7 2.3
22.5 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.3 3.6 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.3 2.9 2.2 3.1 2.2 3.3 2.2
35.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
40.0 2.3 2.0 2.4 2.0 2.6 2.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.1
43.0 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.2 2.9 2.1 3.1 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.8 4.1 2.8 4.4 2.8 4.7 2.7
22.5 3.4 2.6 3.5 2.6 3.8 2.6 3.9 2.8 4.1 2.8 4.3 2.7 4.6 2.7
25.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.5 2.7
27.5 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.5 2.7
32 30.0 3.2 2.5 3.4 2.5 3.6 2.5 3.7 2.7 3.9 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.0 2.6 4.3 2.6
35.0 3.1 2.4 3.2 2.5 3.5 2.5 3.6 2.6 3.7 2.6 4.0 2.6 4.2 2.6
37.5 3.1 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.6 2.6 3.9 2.6 4.1 2.5
40.0 3.0 2.4 3.1 2.4 3.3 2.4 3.4 2.6 3.6 2.6 3.8 2.5 4.0 2.5
43.0 2.9 2.3 3.0 2.4 3.2 2.4 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.5
20.0 4.3 3.0 4.5 3.1 4.8 3.1 5.0 3.3 5.2 3.3 5.5 3.2 5.9 3.2
22.5 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.1 3.2 5.4 3.2 5.8 3.1
25.0 4.2 3.0 4.3 3.0 4.7 3.0 4.8 3.2 5.0 3.2 5.3 3.2 5.7 3.1
27.5 4.1 2.9 4.3 3.0 4.6 3.0 4.7 3.1 4.9 3.1 5.2 3.1 5.6 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 2.9 4.7 3.1 4.8 3.1 5.1 3.1 5.5 3.0
(4.5) 32.5 4.0 2.8 4.1 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.0 3.0 5.4 3.0
35.0 3.9 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.6 3.0 4.9 3.0 5.3 3.0
37.5 3.8 2.8 4.0 2.8 4.2 2.8 4.4 3.0 4.5 3.0 4.8 3.0 5.2 2.9
40.0 3.8 2.7 3.9 2.8 4.2 2.8 4.3 2.9 4.5 2.9 4.8 2.9 5.1 2.9
43.0 3.7 2.7 3.8 2.7 4.1 2.7 4.2 2.9 4.3 2.9 4.6 2.9 4.9 2.8
20.0 5.4 3.9 5.6 4.0 6.0 4.0 6.2 4.2 6.4 4.2 6.9 4.1 7.3 4.1
22.5 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.3 4.1 6.7 4.1 7.2 4.0
25.0 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
27.5 5.1 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
50 30.0 5.0 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.8 3.9
(5.6) 32.5 5.0 3.6 5.1 3.7 5.5 3.7 5.7 3.9 5.9 3.9 6.3 3.9 6.7 3.8
35.0 4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.8 6.5 3.8
37.5 4.8 3.5 4.9 3.6 5.3 3.6 5.5 3.8 5.7 3.8 6.0 3.8 6.4 3.7
40.0 4.7 3.5 4.8 3.6 5.2 3.6 5.4 3.8 5.5 3.8 5.9 3.7 6.3 3.7
43.0 4.6 3.4 4.7 3.5 5.1 3.5 5.2 3.7 5.4 3.7 5.8 3.7 6.1 3.6
20.0 6.9 4.8 7.1 4.9 7.6 4.9 7.9 5.2 8.2 5.2 8.7 5.1 9.3 5.0
22.5 6.7 4.7 7.0 4.9 7.5 4.9 7.8 5.1 8.0 5.1 8.6 5.0 9.1 5.0
25.0 6.6 4.7 6.9 4.8 7.4 4.8 7.6 5.1 7.9 5.0 8.4 5.0 8.9 4.9
27.5 6.5 4.6 6.7 4.7 7.2 4.7 7.5 5.0 7.7 5.0 8.3 4.9 8.8 4.9
63 30.0 6.4 4.5 6.6 4.7 7.1 4.7 7.3 4.9 7.6 4.9 8.1 4.9 8.6 4.8
(7.1) 32.5 6.3 4.5 6.5 4.6 7.0 4.6 7.2 4.9 7.5 4.8 7.9 4.8 8.5 4.7
35.0 6.2 4.4 6.4 4.5 6.8 4.5 7.1 4.8 7.3 4.8 7.8 4.7 8.3 4.7
37.5 6.1 4.4 6.2 4.5 6.7 4.5 6.9 4.7 7.2 4.7 7.6 4.7 8.1 4.6
40.0 5.9 4.3 6.1 4.4 6.6 4.4 6.8 4.7 7.0 4.7 7.5 4.6 8.0 4.6
43.0 5.8 4.2 6.0 4.3 6.4 4.3 6.6 4.6 6.9 4.6 7.3 4.5 7.8 4.5
20.0 8.7 6.3 9.0 6.5 9.7 6.5 10.0 6.9 10.3 6.9 11.0 6.8 11.7 6.7
22.5 8.5 6.2 8.9 6.4 9.5 6.4 9.8 6.8 10.2 6.8 10.8 6.7 11.5 6.6
25.0 8.4 6.2 8.7 6.4 9.3 6.3 9.7 6.7 10.0 6.7 10.6 6.6 11.3 6.5
27.5 8.3 6.1 8.5 6.3 9.2 6.3 9.5 6.6 9.8 6.6 10.5 6.6 11.1 6.5
80 30.0 8.1 6.0 8.4 6.2 9.0 6.2 9.3 6.6 9.6 6.5 10.3 6.5 10.9 6.4
(9.0) 32.5 8.0 6.0 8.2 6.1 8.8 6.1 9.1 6.5 9.4 6.5 10.1 6.4 10.7 6.3
35.0 7.8 5.9 8.1 6.1 8.7 6.0 9.0 6.4 9.3 6.4 9.9 6.3 10.5 6.2
37.5 7.7 5.8 7.9 6.0 8.5 6.0 8.8 6.3 9.1 6.3 9.7 6.3 10.3 6.2
40.0 7.5 5.7 7.7 5.9 8.3 5.9 8.6 6.3 8.9 6.2 9.5 6.2 10.1 6.1
43.0 7.4 5.7 7.6 5.8 8.1 5.8 8.4 6.2 8.7 6.2 9.3 6.1 9.9 6.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 130


4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.8 7.8 11.2 8.0 12.0 8.0 12.5 8.4 12.9 8.4 13.7 8.3 14.6 8.2
22.5 10.6 7.7 11.0 7.9 11.8 7.9 12.2 8.3 12.6 8.3 13.5 8.2 14.4 8.1
25.0 10.5 7.6 10.8 7.8 11.6 7.8 12.0 8.2 12.4 8.2 13.3 8.1 14.1 8.0
27.5 10.3 7.5 10.6 7.7 11.4 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
100 30.0 10.1 7.4 10.4 7.6 11.2 7.6 11.6 8.0 12.0 8.0 12.8 7.9 13.6 7.8
(11.2) 32.5 9.9 7.3 10.2 7.5 11.0 7.5 11.4 8.0 11.8 7.9 12.5 7.8 13.3 7.7
35.0 9.7 7.2 10.0 7.4 10.8 7.4 11.2 7.9 11.5 7.8 12.3 7.8 13.1 7.6
37.5 9.5 7.1 9.8 7.3 10.6 7.3 10.9 7.8 11.3 7.7 12.1 7.7 12.8 7.6
40.0 9.4 7.0 9.6 7.2 10.4 7.2 10.7 7.7 11.1 7.6 11.8 7.6 12.6 7.5
43.0 9.2 6.9 9.4 7.1 10.1 7.1 10.5 7.6 10.8 7.5 11.5 7.5 12.3 7.4
20.0 13.5 9.9 14.0 10.2 15.0 10.2 15.6 10.7 16.1 10.7 17.2 10.6 18.3 10.5
22.5 13.3 9.8 13.8 10.1 14.8 10.0 15.3 10.6 15.8 10.6 16.9 10.5 17.9 10.3
25.0 13.1 9.6 13.5 9.9 14.5 9.9 15.0 10.5 15.5 10.5 16.6 10.4 17.6 10.2
27.5 12.8 9.5 13.3 9.8 14.3 9.8 14.8 10.4 15.3 10.3 16.3 10.2 17.3 10.1
125 30.0 12.6 9.4 13.0 9.7 14.0 9.7 14.5 10.3 15.0 10.2 16.0 10.1 17.0 10.0
(14.0) 32.5 12.4 9.3 12.8 9.6 13.7 9.6 14.2 10.1 14.7 10.1 15.7 10.0 16.7 9.9
35.0 12.2 9.2 12.5 9.5 13.5 9.4 14.0 10.1 14.4 10.0 15.4 9.9 16.4 9.8
37.5 11.9 9.1 12.3 9.3 13.2 9.3 13.7 9.9 14.1 9.9 15.1 9.8 16.0 9.7
40.0 11.7 9.0 12.1 9.2 12.9 9.2 13.4 9.8 13.9 9.8 14.8 9.7 15.7 9.5
43.0 11.4 8.8 11.8 9.1 12.6 9.1 13.1 9.7 13.5 9.6 14.4 9.5 15.4 9.4
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 131


4. Cooling [Ceiling cassette (2-way flow type)]
4-5. Cooling capacity with PUHY-RP850-900YSJM
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.9 2.1 1.9 2.3 1.9 2.4 2.1 2.4 2.1 2.6 2.0 2.8 2.0
22.5 2.1 1.9 2.1 1.9 2.3 1.9 2.3 2.1 2.4 2.0 2.6 2.0 2.7 2.0
25.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.7 2.0
20 30.0 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.5 2.0 2.7 2.0
(2.2) 32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
35.0 2.0 1.8 2.0 1.9 2.1 1.9 2.2 2.0 2.3 2.0 2.5 2.0 2.6 2.0
37.5 1.9 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 2.0 2.6 2.0
40.0 1.9 1.8 1.9 1.8 2.1 1.8 2.2 2.0 2.2 2.0 2.4 2.0 2.6 1.9
43.0 1.9 1.8 1.9 1.8 2.1 1.8 2.1 2.0 2.2 2.0 2.4 2.0 2.5 1.9
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.2
25.0 2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.5 2.2
27.5 2.6 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
35.0 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
43.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
20.0 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.8 4.0 2.7 4.3 2.7 4.5 2.7
22.5 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.7 4.0 2.7 4.2 2.7 4.5 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.7 3.9 2.7 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.5 3.8 2.7 3.9 2.7 4.1 2.7 4.4 2.6
32 30.0 3.3 2.5 3.3 2.5 3.6 2.5 3.7 2.7 3.8 2.7 4.1 2.7 4.4 2.6
(3.6) 32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.7 2.7 3.8 2.7 4.1 2.6 4.3 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.6 2.6 3.8 2.6 4.0 2.6 4.3 2.6
37.5 3.2 2.4 3.2 2.5 3.5 2.5 3.6 2.6 3.7 2.6 4.0 2.6 4.2 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.6 3.9 2.6 4.2 2.6
43.0 3.1 2.4 3.1 2.4 3.4 2.4 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
20.0 4.3 3.0 4.4 3.1 4.7 3.0 4.8 3.2 5.0 3.2 5.3 3.1 5.7 3.1
22.5 4.2 3.0 4.3 3.0 4.6 3.0 4.8 3.2 4.9 3.2 5.3 3.1 5.6 3.1
25.0 4.2 2.9 4.3 3.0 4.6 3.0 4.7 3.1 4.9 3.1 5.2 3.1 5.6 3.1
27.5 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.2 3.1 5.5 3.0
40 30.0 4.1 2.9 4.2 2.9 4.5 2.9 4.6 3.1 4.8 3.1 5.1 3.1 5.5 3.0
(4.5) 32.5 4.0 2.9 4.1 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.1 3.0 5.4 3.0
35.0 4.0 2.8 4.1 2.9 4.4 2.9 4.5 3.0 4.7 3.0 5.0 3.0 5.4 3.0
37.5 4.0 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.6 3.0 5.0 3.0 5.3 3.0
40.0 3.9 2.8 4.0 2.8 4.3 2.8 4.4 3.0 4.6 3.0 4.9 3.0 5.3 3.0
43.0 3.9 2.8 3.9 2.8 4.2 2.8 4.4 3.0 4.5 3.0 4.9 3.0 5.2 2.9
20.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.0 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.0 4.1 6.2 4.0 6.6 4.0 7.0 4.0
25.0 5.2 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 4.0 6.9 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.9 3.9
50 30.0 5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.8 3.9
(5.6) 32.5 5.0 3.7 5.1 3.7 5.5 3.7 5.7 4.0 5.9 3.9 6.3 3.9 6.7 3.9
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.7 3.8
37.5 4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.9 6.6 3.8
40.0 4.9 3.6 4.9 3.6 5.3 3.6 5.5 3.9 5.7 3.9 6.1 3.8 6.5 3.8
43.0 4.8 3.5 4.9 3.6 5.2 3.6 5.4 3.8 5.6 3.8 6.0 3.8 6.5 3.8
20.0 6.7 4.7 6.9 4.8 7.4 4.8 7.6 5.1 7.9 5.0 8.4 5.0 8.9 4.9
22.5 6.6 4.7 6.8 4.8 7.3 4.8 7.6 5.0 7.8 5.0 8.3 4.9 8.8 4.9
25.0 6.6 4.6 6.8 4.7 7.2 4.7 7.5 5.0 7.7 5.0 8.2 4.9 8.8 4.9
27.5 6.5 4.6 6.7 4.7 7.2 4.7 7.4 4.9 7.6 4.9 8.2 4.9 8.7 4.8
63 30.0 6.4 4.6 6.6 4.7 7.1 4.7 7.3 4.9 7.6 4.9 8.1 4.8 8.6 4.8
(7.1) 32.5 6.4 4.5 6.5 4.6 7.0 4.6 7.2 4.9 7.5 4.9 8.0 4.8 8.5 4.8
35.0 6.3 4.5 6.4 4.6 6.9 4.6 7.1 4.8 7.4 4.8 7.9 4.8 8.5 4.7
37.5 6.2 4.5 6.3 4.5 6.8 4.5 7.1 4.8 7.3 4.8 7.8 4.8 8.4 4.7
40.0 6.2 4.4 6.3 4.5 6.7 4.5 7.0 4.8 7.2 4.8 7.8 4.7 8.3 4.7
43.0 6.1 4.4 6.2 4.5 6.7 4.5 6.9 4.7 7.1 4.7 7.7 4.7 8.2 4.6
20.0 8.5 6.2 8.8 6.4 9.4 6.4 9.7 6.7 10.0 6.7 10.6 6.6 11.3 6.5
22.5 8.4 6.2 8.7 6.3 9.3 6.3 9.6 6.7 9.9 6.7 10.5 6.6 11.2 6.5
25.0 8.3 6.1 8.6 6.3 9.2 6.3 9.5 6.6 9.8 6.6 10.4 6.5 11.1 6.5
27.5 8.3 6.1 8.5 6.2 9.1 6.2 9.4 6.6 9.7 6.6 10.3 6.5 11.0 6.4
80 30.0 8.2 6.1 8.4 6.2 9.0 6.2 9.3 6.6 9.6 6.5 10.2 6.5 10.9 6.4
(9.0) 32.5 8.1 6.0 8.3 6.1 8.9 6.1 9.2 6.5 9.5 6.5 10.1 6.4 10.8 6.4
35.0 8.0 6.0 8.1 6.1 8.8 6.1 9.0 6.4 9.4 6.4 10.0 6.4 10.7 6.3
37.5 7.9 5.9 8.0 6.1 8.7 6.0 9.0 6.4 9.3 6.4 9.9 6.4 10.6 6.3
40.0 7.8 5.9 7.9 6.0 8.6 6.0 8.9 6.4 9.2 6.4 9.8 6.3 10.5 6.3
43.0 7.7 5.8 7.8 5.9 8.4 5.9 8.7 6.3 9.1 6.3 9.7 6.3 10.4 6.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 132


4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.6 7.6 10.9 7.8 11.7 7.8 12.0 8.3 12.4 8.2 13.2 8.1 14.1 8.0
22.5 10.5 7.6 10.8 7.8 11.5 7.8 11.9 8.2 12.3 8.2 13.1 8.1 13.9 8.0
25.0 10.4 7.5 10.6 7.7 11.4 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
27.5 10.3 7.5 10.5 7.7 11.3 7.6 11.7 8.1 12.1 8.1 12.9 8.0 13.7 7.9
100 30.0 10.2 7.4 10.4 7.6 11.2 7.6 11.5 8.0 11.9 8.0 12.7 7.9 13.6 7.8
(11.2) 32.5 10.1 7.4 10.3 7.5 11.0 7.5 11.4 8.0 11.8 7.9 12.6 7.9 13.5 7.8
35.0 9.9 7.3 10.1 7.5 10.9 7.5 11.2 7.9 11.7 7.9 12.5 7.8 13.3 7.7
37.5 9.8 7.3 10.0 7.4 10.8 7.4 11.2 7.9 11.6 7.8 12.4 7.8 13.2 7.7
40.0 9.7 7.2 9.9 7.4 10.6 7.3 11.0 7.8 11.4 7.8 12.2 7.7 13.1 7.7
43.0 9.6 7.2 9.7 7.3 10.5 7.3 10.9 7.7 11.3 7.7 12.1 7.7 12.9 7.6
20.0 13.2 9.7 13.6 10.0 14.6 9.9 15.1 10.5 15.5 10.5 16.5 10.3 17.6 10.2
22.5 13.1 9.7 13.5 9.9 14.4 9.9 14.9 10.4 15.4 10.4 16.4 10.3 17.4 10.2
25.0 13.0 9.6 13.3 9.8 14.3 9.8 14.7 10.4 15.2 10.3 16.2 10.2 17.3 10.1
27.5 12.8 9.5 13.2 9.8 14.1 9.7 14.6 10.3 15.1 10.3 16.1 10.2 17.1 10.0
125 30.0 12.7 9.5 13.0 9.7 13.9 9.6 14.4 10.2 14.9 10.2 15.9 10.1 17.0 10.0
(14.0) 32.5 12.6 9.4 12.8 9.6 13.8 9.6 14.3 10.2 14.8 10.1 15.8 10.0 16.8 9.9
35.0 12.4 9.3 12.7 9.5 13.6 9.5 14.0 10.1 14.6 10.1 15.6 10.0 16.7 9.9
37.5 12.3 9.3 12.5 9.4 13.5 9.4 14.0 10.0 14.4 10.0 15.5 9.9 16.5 9.8
40.0 12.2 9.2 12.4 9.4 13.3 9.4 13.8 10.0 14.3 9.9 15.3 9.9 16.4 9.8
43.0 12.0 9.1 12.2 9.3 13.1 9.3 13.6 9.9 14.1 9.9 15.1 9.8 16.2 9.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 133


5. Cooling [Ceiling cassette (4-way flow type)]
5-1. Cooling capacity with PUHY,PURY-RP200-250YJM
5. Cooling [Ceiling cassette (4-way flow type)]

PLFY-P-VCM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
22.5 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
25.0 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.7 1.9
27.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.6 1.9
(2.2) 32.5 2.0 1.7 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.8 2.5 1.8
37.5 1.9 1.7 2.0 1.8 2.1 1.7 2.2 1.9 2.2 1.9 2.3 1.8 2.5 1.8
40.0 1.9 1.7 2.0 1.8 2.1 1.7 2.1 1.9 2.2 1.8 2.3 1.8 2.4 1.8
43.0 1.8 1.7 1.9 1.7 2.0 1.7 2.1 1.8 2.1 1.8 2.2 1.8 2.3 1.8
20.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.6 2.1 2.7 2.2 2.8 2.2 2.9 2.3 3.0 2.3 3.2 2.2 3.3 2.2
(2.8) 32.5 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 2.9 2.3 3.1 2.2 3.3 2.2
35.0 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.3 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.8 2.2 3.0 2.2 3.1 2.1
40.0 2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.1
43.0 2.4 2.0 2.4 2.1 2.6 2.0 2.6 2.2 2.7 2.2 2.8 2.1 3.0 2.1
20.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.6 2.8
22.5 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
27.5 3.4 2.6 3.5 2.7 3.7 2.6 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.6 3.4 2.6 3.6 2.6 3.7 2.8 3.8 2.7 4.1 2.7 4.3 2.7
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.2 2.6
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.7 2.7 3.9 2.6 4.1 2.6
37.5 3.2 2.5 3.3 2.6 3.4 2.5 3.5 2.7 3.6 2.7 3.8 2.6 4.0 2.6
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.6 3.7 2.6 3.9 2.5
43.0 3.0 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.5 2.6 3.6 2.5 3.8 2.5
20.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.3 5.0 3.3 5.3 3.2 5.7 3.2
22.5 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.3 5.0 3.3 5.3 3.2 5.7 3.2
25.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.3 5.0 3.2 5.3 3.2 5.6 3.2
27.5 4.3 3.0 4.4 3.1 4.6 3.1 4.8 3.2 4.9 3.2 5.2 3.2 5.5 3.1
40 30.0 4.2 3.0 4.3 3.1 4.6 3.0 4.7 3.2 4.8 3.2 5.1 3.1 5.4 3.1
(4.5) 32.5 4.1 3.0 4.2 3.0 4.5 3.0 4.6 3.2 4.7 3.1 5.0 3.1 5.3 3.0
35.0 4.0 2.9 4.1 3.0 4.4 3.0 4.5 3.1 4.6 3.1 4.9 3.0 5.2 3.0
37.5 4.0 2.9 4.1 3.0 4.3 2.9 4.4 3.1 4.5 3.1 4.8 3.0 5.0 2.9
40.0 3.9 2.8 4.0 2.9 4.2 2.9 4.3 3.0 4.4 3.0 4.7 3.0 4.9 2.9
43.0 3.8 2.8 3.9 2.9 4.1 2.8 4.2 3.0 4.3 3.0 4.5 2.9 4.8 2.9
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 134


5. Cooling [Ceiling cassette (4-way flow type)]
PLFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.4 2.8 3.5 2.9 3.8 2.9 3.9 3.1 4.0 3.1 4.3 3.1 4.6 3.0
22.5 3.4 2.8 3.5 2.9 3.8 2.9 3.9 3.1 4.0 3.1 4.3 3.1 4.6 3.0
25.0 3.4 2.8 3.5 2.9 3.8 2.9 3.9 3.1 4.0 3.1 4.2 3.0 4.5 3.0
27.5 3.4 2.8 3.5 2.9 3.7 2.9 3.8 3.1 3.9 3.1 4.1 3.0 4.4 3.0
32 30.0 3.3 2.8 3.4 2.9 3.6 2.9 3.7 3.1 3.8 3.0 4.1 3.0 4.3 3.0
(3.6) 32.5 3.3 2.8 3.4 2.9 3.6 2.8 3.7 3.0 3.8 3.0 4.0 3.0 4.2 2.9
35.0 3.2 2.7 3.3 2.8 3.5 2.8 3.6 3.0 3.7 3.0 3.9 2.9 4.1 2.9
37.5 3.2 2.7 3.3 2.8 3.4 2.8 3.5 3.0 3.6 3.0 3.8 2.9 4.0 2.9
40.0 3.1 2.7 3.2 2.8 3.4 2.8 3.5 3.0 3.6 2.9 3.7 2.9 3.9 2.8
43.0 3.0 2.7 3.1 2.8 3.3 2.7 3.4 2.9 3.5 2.9 3.6 2.8 3.8 2.8
20.0 4.3 3.5 4.4 3.6 4.7 3.6 4.9 3.8 5.0 3.8 5.3 3.7 5.7 3.7
22.5 4.3 3.5 4.4 3.6 4.7 3.6 4.9 3.8 5.0 3.8 5.3 3.7 5.7 3.7
25.0 4.3 3.5 4.4 3.6 4.7 3.6 4.9 3.8 5.0 3.8 5.3 3.7 5.6 3.6
27.5 4.3 3.4 4.4 3.6 4.6 3.5 4.8 3.7 4.9 3.7 5.2 3.7 5.5 3.6
40 30.0 4.2 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.8 3.7 5.1 3.6 5.4 3.6
(4.5) 32.5 4.1 3.4 4.2 3.5 4.5 3.4 4.6 3.7 4.7 3.6 5.0 3.6 5.3 3.5
35.0 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.6 3.6 4.9 3.6 5.2 3.5
37.5 4.0 3.3 4.1 3.4 4.3 3.4 4.4 3.6 4.5 3.6 4.8 3.5 5.0 3.5
40.0 3.9 3.3 4.0 3.4 4.2 3.3 4.3 3.6 4.4 3.5 4.7 3.5 4.9 3.4
43.0 3.8 3.2 3.9 3.3 4.1 3.3 4.2 3.5 4.3 3.5 4.5 3.4 4.8 3.4
20.0 5.3 4.0 5.5 4.1 5.9 4.1 6.1 4.3 6.2 4.3 6.6 4.3 7.1 4.2
22.5 5.3 4.0 5.5 4.1 5.9 4.1 6.1 4.3 6.2 4.3 6.6 4.3 7.1 4.2
25.0 5.3 4.0 5.5 4.1 5.9 4.1 6.0 4.3 6.2 4.3 6.6 4.2 7.0 4.2
27.5 5.3 4.0 5.5 4.1 5.8 4.0 5.9 4.3 6.1 4.2 6.4 4.2 6.8 4.1
50 30.0 5.2 3.9 5.4 4.0 5.7 4.0 5.8 4.2 6.0 4.2 6.3 4.1 6.7 4.1
(5.6) 32.5 5.1 3.9 5.3 4.0 5.6 4.0 5.7 4.2 5.9 4.2 6.2 4.1 6.6 4.0
35.0 5.0 3.8 5.2 4.0 5.5 3.9 5.6 4.1 5.8 4.1 6.1 4.0 6.4 4.0
37.5 4.9 3.8 5.1 3.9 5.4 3.9 5.5 4.1 5.6 4.1 5.9 4.0 6.3 3.9
40.0 4.8 3.7 5.0 3.9 5.3 3.8 5.4 4.1 5.5 4.0 5.8 3.9 6.1 3.9
43.0 4.7 3.7 4.8 3.8 5.1 3.8 5.3 4.0 5.4 4.0 5.6 3.9 6.0 3.8
20.0 6.7 4.9 7.0 5.1 7.5 5.0 7.7 5.3 7.9 5.3 8.4 5.2 9.0 5.2
22.5 6.7 4.9 7.0 5.1 7.5 5.0 7.7 5.3 7.9 5.3 8.4 5.2 9.0 5.2
25.0 6.7 4.9 7.0 5.1 7.5 5.0 7.7 5.3 7.9 5.3 8.3 5.2 8.8 5.1
27.5 6.7 4.9 6.9 5.0 7.3 5.0 7.5 5.2 7.7 5.2 8.1 5.1 8.7 5.0
63 30.0 6.6 4.8 6.8 5.0 7.2 4.9 7.4 5.2 7.6 5.1 8.0 5.0 8.5 5.0
(7.1) 32.5 6.5 4.8 6.7 4.9 7.1 4.8 7.2 5.1 7.4 5.1 7.8 5.0 8.3 4.9
35.0 6.4 4.7 6.5 4.8 6.9 4.8 7.1 5.0 7.3 5.0 7.7 4.9 8.1 4.8
37.5 6.2 4.7 6.4 4.8 6.8 4.7 7.0 5.0 7.2 5.0 7.5 4.9 8.0 4.8
40.0 6.1 4.6 6.3 4.7 6.7 4.7 6.8 4.9 7.0 4.9 7.4 4.8 7.8 4.7
43.0 6.0 4.5 6.1 4.7 6.5 4.6 6.7 4.9 6.9 4.8 7.2 4.7 7.6 4.7
20.0 8.6 6.1 8.9 6.3 9.5 6.3 9.7 6.6 10.0 6.6 10.6 6.5 11.4 6.4
22.5 8.6 6.1 8.9 6.3 9.5 6.3 9.7 6.6 10.0 6.6 10.6 6.5 11.4 6.4
25.0 8.6 6.1 8.9 6.3 9.5 6.3 9.7 6.6 10.0 6.5 10.5 6.4 11.2 6.3
27.5 8.5 6.1 8.8 6.3 9.3 6.2 9.5 6.5 9.8 6.4 10.3 6.3 11.0 6.2
80 30.0 8.4 6.0 8.6 6.2 9.1 6.1 9.4 6.4 9.6 6.4 10.1 6.3 10.8 6.2
(9.0) 32.5 8.2 5.9 8.5 6.1 8.9 6.0 9.2 6.3 9.4 6.3 9.9 6.2 10.5 6.1
35.0 8.1 5.9 8.3 6.0 8.8 5.9 9.0 6.3 9.2 6.2 9.7 6.1 10.3 6.0
37.5 7.9 5.8 8.1 5.9 8.6 5.9 8.8 6.2 9.1 6.1 9.5 6.0 10.1 5.9
40.0 7.7 5.7 8.0 5.9 8.4 5.8 8.7 6.1 8.9 6.1 9.3 5.9 9.9 5.8
43.0 7.6 5.6 7.8 5.8 8.2 5.7 8.5 6.0 8.7 6.0 9.1 5.8 9.6 5.7
20.0 10.6 7.6 11.0 7.9 11.8 7.8 12.1 8.2 12.5 8.2 13.2 8.1 14.2 8.0
22.5 10.6 7.6 11.0 7.9 11.8 7.8 12.1 8.2 12.5 8.2 13.2 8.1 14.2 8.0
25.0 10.6 7.6 11.0 7.9 11.8 7.8 12.1 8.2 12.4 8.2 13.1 8.0 13.9 7.9
27.5 10.6 7.6 10.9 7.8 11.6 7.7 11.9 8.1 12.2 8.1 12.9 7.9 13.7 7.8
100 30.0 10.4 7.5 10.7 7.7 11.3 7.6 11.6 8.0 12.0 8.0 12.6 7.8 13.4 7.7
(11.2) 32.5 10.2 7.4 10.5 7.6 11.1 7.5 11.4 7.9 11.7 7.9 12.4 7.7 13.1 7.6
35.0 10.0 7.3 10.3 7.5 10.9 7.4 11.2 7.8 11.5 7.8 12.1 7.6 12.8 7.5
37.5 9.8 7.2 10.1 7.4 10.7 7.3 11.0 7.7 11.3 7.7 11.9 7.5 12.6 7.4
40.0 9.6 7.1 9.9 7.3 10.5 7.3 10.8 7.7 11.1 7.6 11.6 7.4 12.3 7.3
43.0 9.4 7.0 9.7 7.2 10.2 7.1 10.5 7.5 10.8 7.5 11.3 7.3 12.0 7.2
20.0 13.3 9.3 13.8 9.6 14.7 9.5 15.2 10.0 15.6 9.9 16.6 9.8 17.7 9.7
22.5 13.3 9.3 13.8 9.6 14.7 9.5 15.2 10.0 15.6 9.9 16.6 9.8 17.7 9.7
25.0 13.3 9.3 13.8 9.6 14.7 9.5 15.1 10.0 15.5 9.9 16.4 9.7 17.4 9.6
27.5 13.3 9.3 13.6 9.5 14.4 9.4 14.8 9.9 15.2 9.8 16.1 9.6 17.1 9.5
125 30.0 13.0 9.2 13.4 9.4 14.2 9.3 14.6 9.7 14.9 9.6 15.8 9.5 16.7 9.3
(14.0) 32.5 12.8 9.0 13.2 9.3 13.9 9.2 14.3 9.6 14.7 9.5 15.4 9.3 16.4 9.2
35.0 12.5 8.9 12.9 9.1 13.7 9.0 14.0 9.5 14.4 9.4 15.1 9.2 16.0 9.1
37.5 12.3 8.8 12.7 9.0 13.4 8.9 13.8 9.4 14.1 9.3 14.8 9.1 15.7 8.9
40.0 12.1 8.7 12.4 8.9 13.1 8.8 13.5 9.2 13.8 9.2 14.5 9.0 15.4 8.8
43.0 11.8 8.5 12.1 8.7 12.8 8.6 13.2 9.1 13.5 9.0 14.1 8.8 15.0 8.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 135


5. Cooling [Ceiling cassette (4-way flow type)]
5-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PLFY-P-VCM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.2 1.9 2.4 1.9 2.5 2.0 2.5 2.0 2.7 2.0 2.9 1.9
22.5 2.1 1.8 2.2 1.9 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
25.0 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.8 1.9
27.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.6 1.9
(2.2) 32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8
37.5 1.9 1.7 2.0 1.8 2.1 1.7 2.1 1.9 2.2 1.9 2.3 1.8 2.5 1.8
40.0 1.9 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.2 1.8 2.3 1.8 2.4 1.8
43.0 1.9 1.7 1.9 1.7 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.8 2.4 1.8
20.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
22.5 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
25.0 2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.2 2.3 3.4 2.2
25 30.0 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.8 2.3 2.9 2.3 3.1 2.2 3.3 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.3 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
40.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.1
43.0 2.4 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.2 2.8 2.1 3.0 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.9 4.2 2.9 4.4 2.8 4.7 2.8
22.5 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.9 4.1 2.8 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
27.5 3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
32 30.0 3.3 2.6 3.4 2.6 3.6 2.6 3.7 2.8 3.8 2.7 4.1 2.7 4.3 2.7
(3.6) 32.5 3.3 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.2 2.6
35.0 3.2 2.5 3.3 2.6 3.5 2.5 3.6 2.7 3.7 2.7 3.9 2.7 4.2 2.6
37.5 3.2 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.8 2.6 4.1 2.6
40.0 3.1 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.5 2.6 3.8 2.6 4.0 2.6
43.0 3.0 2.4 3.0 2.5 3.2 2.4 3.3 2.6 3.4 2.6 3.7 2.6 3.9 2.5
20.0 4.4 3.1 4.5 3.2 4.9 3.2 5.0 3.4 5.2 3.3 5.5 3.3 5.8 3.2
22.5 4.4 3.1 4.5 3.2 4.8 3.1 4.9 3.3 5.1 3.3 5.4 3.3 5.7 3.2
25.0 4.3 3.1 4.4 3.1 4.7 3.1 4.9 3.3 5.0 3.3 5.3 3.2 5.6 3.2
27.5 4.2 3.0 4.3 3.1 4.6 3.1 4.8 3.2 4.9 3.2 5.2 3.2 5.5 3.1
40 30.0 4.1 3.0 4.2 3.0 4.5 3.0 4.7 3.2 4.8 3.2 5.1 3.1 5.4 3.1
(4.5) 32.5 4.1 2.9 4.2 3.0 4.4 3.0 4.6 3.1 4.7 3.1 5.0 3.1 5.3 3.0
35.0 4.0 2.9 4.1 3.0 4.3 2.9 4.5 3.1 4.6 3.1 4.9 3.0 5.2 3.0
37.5 3.9 2.9 4.0 2.9 4.2 2.9 4.4 3.1 4.5 3.0 4.8 3.0 5.1 3.0
40.0 3.9 2.8 3.9 2.9 4.2 2.9 4.3 3.0 4.4 3.0 4.7 3.0 5.0 2.9
43.0 3.8 2.8 3.8 2.8 4.0 2.8 4.2 3.0 4.3 3.0 4.6 2.9 4.8 2.9
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 136


5. Cooling [Ceiling cassette (4-way flow type)]
PLFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.5 2.9 3.6 3.0 3.9 3.0 4.0 3.2 4.2 3.2 4.4 3.1 4.7 3.1
22.5 3.5 2.9 3.6 3.0 3.8 2.9 4.0 3.1 4.1 3.1 4.3 3.1 4.6 3.0
25.0 3.4 2.8 3.5 2.9 3.8 2.9 3.9 3.1 4.0 3.1 4.2 3.1 4.5 3.0
27.5 3.4 2.8 3.5 2.9 3.7 2.9 3.8 3.1 3.9 3.1 4.2 3.0 4.4 3.0
32 30.0 3.3 2.8 3.4 2.9 3.6 2.9 3.7 3.1 3.8 3.0 4.1 3.0 4.3 3.0
(3.6) 32.5 3.3 2.8 3.3 2.8 3.5 2.8 3.7 3.0 3.8 3.0 4.0 3.0 4.2 2.9
35.0 3.2 2.7 3.3 2.8 3.5 2.8 3.6 3.0 3.7 3.0 3.9 2.9 4.2 2.9
37.5 3.2 2.7 3.2 2.8 3.4 2.8 3.5 3.0 3.6 3.0 3.8 2.9 4.1 2.9
40.0 3.1 2.7 3.1 2.8 3.3 2.7 3.4 2.9 3.5 2.9 3.8 2.9 4.0 2.8
43.0 3.0 2.7 3.0 2.7 3.2 2.7 3.3 2.9 3.4 2.9 3.7 2.9 3.9 2.8
20.0 4.4 3.5 4.5 3.6 4.9 3.6 5.0 3.9 5.2 3.8 5.5 3.8 5.8 3.7
22.5 4.4 3.5 4.5 3.6 4.8 3.6 4.9 3.8 5.1 3.8 5.4 3.8 5.7 3.7
25.0 4.3 3.5 4.4 3.6 4.7 3.5 4.9 3.8 5.0 3.8 5.3 3.7 5.6 3.7
27.5 4.2 3.4 4.3 3.5 4.6 3.5 4.8 3.7 4.9 3.7 5.2 3.7 5.5 3.6
40 30.0 4.1 3.4 4.2 3.5 4.5 3.5 4.7 3.7 4.8 3.7 5.1 3.6 5.4 3.6
(4.5) 32.5 4.1 3.4 4.2 3.5 4.4 3.4 4.6 3.7 4.7 3.6 5.0 3.6 5.3 3.5
35.0 4.0 3.3 4.1 3.4 4.3 3.4 4.5 3.6 4.6 3.6 4.9 3.6 5.2 3.5
37.5 3.9 3.3 4.0 3.4 4.2 3.3 4.4 3.6 4.5 3.6 4.8 3.5 5.1 3.5
40.0 3.9 3.3 3.9 3.3 4.2 3.3 4.3 3.6 4.4 3.5 4.7 3.5 5.0 3.4
43.0 3.8 3.2 3.8 3.3 4.0 3.3 4.2 3.5 4.3 3.5 4.6 3.4 4.8 3.4
20.0 5.4 4.0 5.6 4.2 6.1 4.2 6.3 4.4 6.5 4.4 6.9 4.3 7.3 4.3
22.5 5.4 4.0 5.6 4.2 6.0 4.1 6.2 4.4 6.3 4.4 6.7 4.3 7.1 4.2
25.0 5.3 4.0 5.5 4.1 5.8 4.1 6.0 4.3 6.2 4.3 6.6 4.2 7.0 4.2
27.5 5.3 4.0 5.4 4.1 5.7 4.0 5.9 4.3 6.1 4.3 6.5 4.2 6.9 4.1
50 30.0 5.2 3.9 5.3 4.0 5.6 4.0 5.8 4.2 6.0 4.2 6.4 4.1 6.7 4.1
(5.6) 32.5 5.1 3.9 5.2 4.0 5.5 3.9 5.7 4.2 5.9 4.2 6.2 4.1 6.6 4.0
35.0 5.0 3.8 5.1 3.9 5.4 3.9 5.6 4.1 5.7 4.1 6.1 4.1 6.5 4.0
37.5 4.9 3.8 5.0 3.9 5.3 3.8 5.5 4.1 5.6 4.1 6.0 4.0 6.3 3.9
40.0 4.8 3.7 4.9 3.8 5.2 3.8 5.3 4.0 5.5 4.0 5.8 4.0 6.2 3.9
43.0 4.7 3.7 4.7 3.8 5.0 3.7 5.2 4.0 5.4 3.9 5.7 3.9 6.0 3.8
20.0 6.9 5.0 7.1 5.1 7.7 5.1 7.9 5.4 8.2 5.4 8.7 5.3 9.2 5.2
22.5 6.9 5.0 7.1 5.1 7.6 5.1 7.8 5.4 8.0 5.3 8.5 5.3 9.1 5.2
25.0 6.8 4.9 7.0 5.0 7.4 5.0 7.7 5.3 7.9 5.3 8.4 5.2 8.9 5.1
27.5 6.7 4.9 6.8 5.0 7.3 4.9 7.5 5.2 7.7 5.2 8.2 5.1 8.7 5.1
63 30.0 6.5 4.8 6.7 4.9 7.1 4.9 7.4 5.2 7.6 5.1 8.1 5.1 8.5 5.0
(7.1) 32.5 6.4 4.8 6.6 4.9 7.0 4.8 7.2 5.1 7.4 5.1 7.9 5.0 8.4 4.9
35.0 6.3 4.7 6.4 4.8 6.8 4.8 7.1 5.0 7.3 5.0 7.7 4.9 8.2 4.9
37.5 6.2 4.6 6.3 4.7 6.7 4.7 6.9 5.0 7.1 4.9 7.6 4.9 8.0 4.8
40.0 6.1 4.6 6.2 4.7 6.6 4.6 6.8 4.9 7.0 4.9 7.4 4.8 7.8 4.7
43.0 6.0 4.5 6.0 4.6 6.4 4.5 6.6 4.8 6.8 4.8 7.2 4.7 7.6 4.7
20.0 8.7 6.2 9.0 6.4 9.7 6.4 10.1 6.7 10.4 6.7 11.0 6.6 11.7 6.5
22.5 8.7 6.2 9.0 6.4 9.6 6.3 9.9 6.7 10.2 6.6 10.8 6.5 11.5 6.4
25.0 8.6 6.1 8.8 6.3 9.4 6.2 9.7 6.6 10.0 6.5 10.6 6.5 11.3 6.4
27.5 8.4 6.1 8.6 6.2 9.2 6.1 9.5 6.5 9.8 6.5 10.4 6.4 11.0 6.3
80 30.0 8.3 6.0 8.5 6.1 9.0 6.1 9.3 6.4 9.6 6.4 10.2 6.3 10.8 6.2
(9.0) 32.5 8.2 5.9 8.3 6.0 8.9 6.0 9.1 6.3 9.4 6.3 10.0 6.2 10.6 6.1
35.0 8.0 5.8 8.1 5.9 8.7 5.9 9.0 6.3 9.2 6.2 9.8 6.1 10.4 6.0
37.5 7.9 5.8 8.0 5.9 8.5 5.8 8.8 6.2 9.0 6.1 9.6 6.0 10.2 5.9
40.0 7.7 5.7 7.8 5.8 8.3 5.7 8.6 6.1 8.8 6.0 9.4 6.0 9.9 5.9
43.0 7.6 5.6 7.6 5.7 8.1 5.6 8.4 6.0 8.6 5.9 9.1 5.9 9.7 5.8
20.0 10.9 7.8 11.3 8.0 12.1 8.0 12.5 8.4 12.9 8.4 13.7 8.3 14.5 8.2
22.5 10.8 7.8 11.2 8.0 11.9 7.9 12.3 8.3 12.7 8.3 13.5 8.2 14.3 8.1
25.0 10.7 7.7 11.0 7.9 11.7 7.8 12.1 8.2 12.5 8.2 13.2 8.1 14.0 8.0
27.5 10.5 7.6 10.8 7.7 11.5 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.7 7.9
100 30.0 10.3 7.5 10.6 7.6 11.2 7.6 11.6 8.0 12.0 8.0 12.7 7.9 13.5 7.8
(11.2) 32.5 10.2 7.4 10.3 7.5 11.0 7.5 11.4 7.9 11.7 7.9 12.4 7.8 13.2 7.6
35.0 10.0 7.3 10.1 7.4 10.8 7.4 11.2 7.8 11.5 7.8 12.2 7.7 12.9 7.5
37.5 9.8 7.2 9.9 7.3 10.6 7.3 10.9 7.7 11.2 7.7 11.9 7.6 12.6 7.5
40.0 9.6 7.1 9.7 7.2 10.3 7.2 10.7 7.6 11.0 7.6 11.7 7.5 12.4 7.4
43.0 9.4 7.0 9.5 7.1 10.1 7.1 10.4 7.5 10.7 7.4 11.4 7.4 12.1 7.2
20.0 13.6 9.5 14.1 9.7 15.1 9.7 15.7 10.2 16.2 10.2 17.2 10.1 18.2 9.9
22.5 13.6 9.5 14.0 9.7 14.9 9.6 15.4 10.1 15.9 10.1 16.8 9.9 17.8 9.8
25.0 13.3 9.3 13.7 9.5 14.6 9.5 15.1 10.0 15.6 9.9 16.5 9.8 17.5 9.6
27.5 13.1 9.2 13.5 9.4 14.3 9.4 14.8 9.8 15.3 9.8 16.2 9.7 17.2 9.5
125 30.0 12.9 9.1 13.2 9.3 14.1 9.2 14.5 9.7 15.0 9.7 15.9 9.5 16.8 9.4
(14.0) 32.5 12.7 9.0 12.9 9.1 13.8 9.1 14.2 9.6 14.7 9.5 15.6 9.4 16.5 9.2
35.0 12.5 8.9 12.7 9.0 13.5 8.9 14.0 9.5 14.4 9.4 15.2 9.3 16.2 9.1
37.5 12.3 8.8 12.4 8.9 13.2 8.8 13.6 9.3 14.1 9.3 14.9 9.1 15.8 9.0
40.0 12.0 8.7 12.2 8.8 12.9 8.7 13.3 9.2 13.8 9.1 14.6 9.0 15.5 8.9
43.0 11.8 8.5 11.8 8.6 12.6 8.5 13.0 9.0 13.4 9.0 14.2 8.8 15.1 8.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 137


5. Cooling [Ceiling cassette (4-way flow type)]
5-3. Cooling capacity with PUHY-RP450-650YSJM
PLFY-P-VCM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.8 1.9
22.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.6 1.9 2.7 1.9
25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.7 1.9
(2.2) 32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
40.0 1.9 1.7 1.9 1.7 2.1 1.7 2.2 1.9 2.2 1.9 2.4 1.9 2.6 1.8
43.0 1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.8 2.5 1.8
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.5 2.3
27.5 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.3 2.9 2.3 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
43.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
20.0 3.4 2.6 3.5 2.7 3.7 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.7
22.5 3.4 2.6 3.5 2.7 3.7 2.6 3.8 2.8 4.0 2.8 4.2 2.8 4.5 2.7
25.0 3.3 2.6 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.8 3.8 2.7 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.7
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.7 4.3 2.7
37.5 3.2 2.5 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.6
40.0 3.1 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.7 3.9 2.7 4.2 2.6
43.0 3.1 2.4 3.1 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.9 2.6 4.2 2.6
20.0 4.3 3.0 4.4 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.2 5.7 3.2
22.5 4.2 3.0 4.3 3.1 4.6 3.1 4.8 3.2 4.9 3.2 5.3 3.2 5.6 3.2
25.0 4.2 3.0 4.3 3.1 4.6 3.1 4.7 3.2 4.9 3.2 5.2 3.2 5.6 3.1
27.5 4.1 3.0 4.2 3.0 4.5 3.0 4.7 3.2 4.8 3.2 5.2 3.2 5.5 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 3.0 4.6 3.2 4.8 3.2 5.1 3.1 5.5 3.1
(4.5) 32.5 4.0 2.9 4.1 3.0 4.4 3.0 4.6 3.2 4.7 3.1 5.1 3.1 5.4 3.1
35.0 4.0 2.9 4.1 3.0 4.4 3.0 4.5 3.1 4.7 3.1 5.0 3.1 5.4 3.1
37.5 4.0 2.9 4.0 2.9 4.3 2.9 4.5 3.1 4.6 3.1 5.0 3.1 5.3 3.0
40.0 3.9 2.9 4.0 2.9 4.3 2.9 4.4 3.1 4.6 3.1 4.9 3.1 5.3 3.0
43.0 3.9 2.8 3.9 2.9 4.2 2.9 4.4 3.1 4.5 3.0 4.9 3.0 5.2 3.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 138


5. Cooling [Ceiling cassette (4-way flow type)]
PLFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.4 2.8 3.5 2.9 3.7 2.9 3.9 3.1 4.0 3.1 4.3 3.1 4.5 3.0
22.5 3.4 2.8 3.5 2.9 3.7 2.9 3.8 3.1 4.0 3.1 4.2 3.0 4.5 3.0
25.0 3.3 2.8 3.4 2.9 3.7 2.9 3.8 3.1 3.9 3.1 4.2 3.0 4.4 3.0
27.5 3.3 2.8 3.4 2.9 3.6 2.9 3.8 3.1 3.9 3.1 4.1 3.0 4.4 3.0
32 30.0 3.3 2.8 3.3 2.9 3.6 2.8 3.7 3.0 3.8 3.0 4.1 3.0 4.4 3.0
(3.6) 32.5 3.2 2.7 3.3 2.8 3.5 2.8 3.7 3.0 3.8 3.0 4.1 3.0 4.3 3.0
35.0 3.2 2.7 3.3 2.8 3.5 2.8 3.6 3.0 3.8 3.0 4.0 3.0 4.3 2.9
37.5 3.2 2.7 3.2 2.8 3.5 2.8 3.6 3.0 3.7 3.0 4.0 3.0 4.2 2.9
40.0 3.1 2.7 3.2 2.8 3.4 2.8 3.5 3.0 3.7 3.0 3.9 3.0 4.2 2.9
43.0 3.1 2.7 3.1 2.8 3.4 2.8 3.5 3.0 3.6 3.0 3.9 2.9 4.2 2.9
20.0 4.3 3.4 4.4 3.6 4.7 3.5 4.8 3.8 5.0 3.8 5.3 3.7 5.7 3.7
22.5 4.2 3.4 4.3 3.5 4.6 3.5 4.8 3.8 4.9 3.7 5.3 3.7 5.6 3.6
25.0 4.2 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.9 3.7 5.2 3.7 5.6 3.6
27.5 4.1 3.4 4.2 3.5 4.5 3.5 4.7 3.7 4.8 3.7 5.2 3.7 5.5 3.6
40 30.0 4.1 3.4 4.2 3.5 4.5 3.4 4.6 3.7 4.8 3.7 5.1 3.6 5.5 3.6
(4.5) 32.5 4.0 3.3 4.1 3.4 4.4 3.4 4.6 3.7 4.7 3.7 5.1 3.6 5.4 3.6
35.0 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.7 3.6 5.0 3.6 5.4 3.6
37.5 4.0 3.3 4.0 3.4 4.3 3.4 4.5 3.6 4.6 3.6 5.0 3.6 5.3 3.6
40.0 3.9 3.3 4.0 3.4 4.3 3.4 4.4 3.6 4.6 3.6 4.9 3.6 5.3 3.5
43.0 3.9 3.3 3.9 3.3 4.2 3.3 4.4 3.6 4.5 3.6 4.9 3.5 5.2 3.5
20.0 5.3 4.0 5.5 4.1 5.8 4.1 6.0 4.3 6.2 4.3 6.6 4.3 7.0 4.2
22.5 5.2 4.0 5.4 4.1 5.8 4.0 6.0 4.3 6.2 4.3 6.6 4.2 7.0 4.2
25.0 5.2 3.9 5.3 4.0 5.7 4.0 5.9 4.3 6.1 4.2 6.5 4.2 6.9 4.2
27.5 5.1 3.9 5.3 4.0 5.6 4.0 5.8 4.2 6.0 4.2 6.4 4.2 6.9 4.1
50 30.0 5.1 3.9 5.2 4.0 5.6 4.0 5.8 4.2 6.0 4.2 6.4 4.2 6.8 4.1
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.2 5.9 4.2 6.3 4.1 6.7 4.1
35.0 5.0 3.8 5.1 3.9 5.4 3.9 5.6 4.1 5.8 4.1 6.2 4.1 6.7 4.1
37.5 4.9 3.8 5.0 3.9 5.4 3.9 5.6 4.1 5.8 4.1 6.2 4.1 6.6 4.0
40.0 4.9 3.8 4.9 3.9 5.3 3.8 5.5 4.1 5.7 4.1 6.1 4.1 6.5 4.0
43.0 4.8 3.7 4.9 3.8 5.2 3.8 5.4 4.1 5.6 4.1 6.0 4.0 6.5 4.0
20.0 6.7 4.9 6.9 5.0 7.4 5.0 7.6 5.3 7.9 5.3 8.4 5.2 8.9 5.1
22.5 6.6 4.9 6.8 5.0 7.3 5.0 7.6 5.3 7.8 5.2 8.3 5.2 8.8 5.1
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.2 8.2 5.1 8.8 5.1
27.5 6.5 4.8 6.7 4.9 7.2 4.9 7.4 5.2 7.6 5.2 8.2 5.1 8.7 5.0
63 30.0 6.4 4.8 6.6 4.9 7.1 4.9 7.3 5.1 7.6 5.1 8.1 5.1 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.1 8.0 5.0 8.5 5.0
35.0 6.3 4.7 6.4 4.8 6.9 4.8 7.1 5.0 7.4 5.1 7.9 5.0 8.5 5.0
37.5 6.2 4.7 6.3 4.8 6.8 4.7 7.1 5.0 7.3 5.0 7.8 5.0 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 5.0 7.2 5.0 7.8 5.0 8.3 4.9
43.0 6.1 4.6 6.2 4.7 6.7 4.7 6.9 5.0 7.1 5.0 7.7 4.9 8.2 4.9
20.0 8.5 6.1 8.8 6.2 9.4 6.2 9.7 6.6 10.0 6.5 10.6 6.5 11.3 6.4
22.5 8.4 6.0 8.7 6.2 9.3 6.2 9.6 6.5 9.9 6.5 10.5 6.4 11.2 6.3
25.0 8.3 6.0 8.6 6.1 9.2 6.1 9.5 6.5 9.8 6.4 10.4 6.4 11.1 6.3
27.5 8.3 6.0 8.5 6.1 9.1 6.1 9.4 6.4 9.7 6.4 10.3 6.3 11.0 6.3
80 30.0 8.2 5.9 8.4 6.0 9.0 6.0 9.3 6.4 9.6 6.4 10.2 6.3 10.9 6.2
(9.0) 32.5 8.1 5.9 8.3 6.0 8.9 6.0 9.2 6.3 9.5 6.3 10.1 6.3 10.8 6.2
35.0 8.0 5.8 8.1 5.9 8.8 5.9 9.0 6.3 9.4 6.3 10.0 6.2 10.7 6.2
37.5 7.9 5.8 8.0 5.9 8.7 5.9 9.0 6.2 9.3 6.2 9.9 6.2 10.6 6.1
40.0 7.8 5.7 7.9 5.8 8.6 5.8 8.9 6.2 9.2 6.2 9.8 6.1 10.5 6.1
43.0 7.7 5.7 7.8 5.8 8.4 5.8 8.7 6.1 9.1 6.1 9.7 6.1 10.4 6.0
20.0 10.6 7.6 10.9 7.8 11.7 7.8 12.0 8.2 12.4 8.2 13.2 8.1 14.1 8.0
22.5 10.5 7.6 10.8 7.8 11.5 7.7 11.9 8.2 12.3 8.1 13.1 8.0 13.9 7.9
25.0 10.4 7.5 10.6 7.7 11.4 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
27.5 10.3 7.5 10.5 7.6 11.3 7.6 11.7 8.0 12.1 8.0 12.9 7.9 13.7 7.8
100 30.0 10.2 7.4 10.4 7.6 11.2 7.5 11.5 8.0 11.9 8.0 12.7 7.9 13.6 7.8
(11.2) 32.5 10.1 7.3 10.3 7.5 11.0 7.5 11.4 7.9 11.8 7.9 12.6 7.8 13.5 7.7
35.0 9.9 7.3 10.1 7.4 10.9 7.4 11.2 7.8 11.7 7.8 12.5 7.8 13.3 7.7
37.5 9.8 7.2 10.0 7.4 10.8 7.4 11.2 7.8 11.6 7.8 12.4 7.7 13.2 7.7
40.0 9.7 7.2 9.9 7.3 10.6 7.3 11.0 7.8 11.4 7.7 12.2 7.7 13.1 7.6
43.0 9.6 7.1 9.7 7.2 10.5 7.2 10.9 7.7 11.3 7.7 12.1 7.6 12.9 7.6
20.0 13.2 9.3 13.6 9.5 14.6 9.5 15.1 10.0 15.5 9.9 16.5 9.8 17.6 9.7
22.5 13.1 9.2 13.5 9.4 14.4 9.4 14.9 9.9 15.4 9.8 16.4 9.7 17.4 9.6
25.0 13.0 9.1 13.3 9.3 14.3 9.3 14.7 9.8 15.2 9.8 16.2 9.7 17.3 9.5
27.5 12.8 9.1 13.2 9.3 14.1 9.2 14.6 9.7 15.1 9.7 16.1 9.6 17.1 9.5
125 30.0 12.7 9.0 13.0 9.2 13.9 9.2 14.4 9.7 14.9 9.6 15.9 9.5 17.0 9.4
(14.0) 32.5 12.6 8.9 12.8 9.1 13.8 9.1 14.3 9.6 14.8 9.6 15.8 9.5 16.8 9.4
35.0 12.4 8.9 12.7 9.0 13.6 9.0 14.0 9.5 14.6 9.5 15.6 9.4 16.7 9.3
37.5 12.3 8.8 12.5 8.9 13.5 8.9 14.0 9.4 14.4 9.4 15.5 9.3 16.5 9.3
40.0 12.2 8.7 12.4 8.9 13.3 8.9 13.8 9.4 14.3 9.3 15.3 9.3 16.4 9.2
43.0 12.0 8.6 12.2 8.8 13.1 8.8 13.6 9.3 14.1 9.3 15.1 9.2 16.2 9.1
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 139


5. Cooling [Ceiling cassette (4-way flow type)]
5-4. Cooling capacity with PUHY-RP700-800YSJM
PLFY-P-VCM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.2 1.9 2.4 1.9 2.4 2.0 2.5 2.0 2.7 2.0 2.9 1.9
22.5 2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
25.0 2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.8 1.9
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9 2.7 1.9
20 30.0 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
(2.2) 32.5 1.9 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
37.5 1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.8 2.5 1.8
40.0 1.8 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.2 1.8 2.3 1.8 2.5 1.8
43.0 1.8 1.6 1.8 1.7 2.0 1.7 2.1 1.8 2.1 1.8 2.3 1.8 2.4 1.8
20.0 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.7 2.3
22.5 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.3 3.4 2.3 3.6 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
27.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.3 2.9 2.3 3.1 2.2 3.3 2.2
35.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.3 2.9 2.2 3.1 2.2 3.3 2.2
37.5 2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
40.0 2.3 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.1
43.0 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.2 2.9 2.1 3.1 2.1
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.9 4.1 2.9 4.4 2.8 4.7 2.8
22.5 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.1 2.8 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.7 3.7 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.7
27.5 3.3 2.5 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.8 4.5 2.7
32 30.0 3.2 2.5 3.4 2.6 3.6 2.6 3.7 2.8 3.9 2.7 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.3 2.7
35.0 3.1 2.5 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.6
37.5 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.9 2.6 4.1 2.6
40.0 3.0 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.6 4.0 2.6
43.0 2.9 2.4 3.0 2.4 3.2 2.4 3.4 2.6 3.5 2.6 3.7 2.6 3.9 2.5
20.0 4.3 3.1 4.5 3.2 4.8 3.2 5.0 3.3 5.2 3.3 5.5 3.3 5.9 3.3
22.5 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.3 5.1 3.3 5.4 3.3 5.8 3.2
25.0 4.2 3.0 4.3 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.2 5.7 3.2
27.5 4.1 3.0 4.3 3.1 4.6 3.0 4.7 3.2 4.9 3.2 5.2 3.2 5.6 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.2 4.8 3.2 5.1 3.1 5.5 3.1
(4.5) 32.5 4.0 2.9 4.1 3.0 4.4 3.0 4.6 3.1 4.7 3.1 5.0 3.1 5.4 3.1
35.0 3.9 2.9 4.0 2.9 4.3 2.9 4.5 3.1 4.6 3.1 4.9 3.1 5.3 3.0
37.5 3.8 2.8 4.0 2.9 4.2 2.9 4.4 3.1 4.5 3.1 4.8 3.0 5.2 3.0
40.0 3.8 2.8 3.9 2.9 4.2 2.9 4.3 3.0 4.5 3.0 4.8 3.0 5.1 2.9
43.0 3.7 2.7 3.8 2.8 4.1 2.8 4.2 3.0 4.3 3.0 4.6 2.9 4.9 2.9
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 140


5. Cooling [Ceiling cassette (4-way flow type)]
PLFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.5 2.9 3.6 3.0 3.9 3.0 4.0 3.2 4.1 3.2 4.4 3.1 4.7 3.1
22.5 3.4 2.8 3.5 2.9 3.8 2.9 3.9 3.1 4.1 3.1 4.3 3.1 4.6 3.1
25.0 3.4 2.8 3.5 2.9 3.7 2.9 3.9 3.1 4.0 3.1 4.3 3.1 4.5 3.0
27.5 3.3 2.8 3.4 2.9 3.7 2.9 3.8 3.1 3.9 3.1 4.2 3.0 4.5 3.0
32 30.0 3.2 2.8 3.4 2.9 3.6 2.8 3.7 3.1 3.9 3.0 4.1 3.0 4.4 3.0
(3.6) 32.5 3.2 2.7 3.3 2.8 3.5 2.8 3.7 3.0 3.8 3.0 4.0 3.0 4.3 2.9
35.0 3.1 2.7 3.2 2.8 3.5 2.8 3.6 3.0 3.7 3.0 4.0 3.0 4.2 2.9
37.5 3.1 2.7 3.2 2.8 3.4 2.8 3.5 3.0 3.6 3.0 3.9 2.9 4.1 2.9
40.0 3.0 2.6 3.1 2.7 3.3 2.7 3.4 2.9 3.6 2.9 3.8 2.9 4.0 2.9
43.0 2.9 2.6 3.0 2.7 3.2 2.7 3.4 2.9 3.5 2.9 3.7 2.9 3.9 2.8
20.0 4.3 3.5 4.5 3.6 4.8 3.6 5.0 3.8 5.2 3.8 5.5 3.8 5.9 3.7
22.5 4.3 3.5 4.4 3.6 4.7 3.6 4.9 3.8 5.1 3.8 5.4 3.8 5.8 3.7
25.0 4.2 3.4 4.3 3.5 4.7 3.5 4.8 3.8 5.0 3.8 5.3 3.7 5.7 3.7
27.5 4.1 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.9 3.7 5.2 3.7 5.6 3.6
40 30.0 4.1 3.3 4.2 3.5 4.5 3.5 4.7 3.7 4.8 3.7 5.1 3.6 5.5 3.6
(4.5) 32.5 4.0 3.3 4.1 3.4 4.4 3.4 4.6 3.7 4.7 3.6 5.0 3.6 5.4 3.6
35.0 3.9 3.3 4.0 3.4 4.3 3.4 4.5 3.6 4.6 3.6 4.9 3.6 5.3 3.5
37.5 3.8 3.2 4.0 3.4 4.2 3.3 4.4 3.6 4.5 3.6 4.8 3.5 5.2 3.5
40.0 3.8 3.2 3.9 3.3 4.2 3.3 4.3 3.6 4.5 3.5 4.8 3.5 5.1 3.5
43.0 3.7 3.2 3.8 3.3 4.1 3.3 4.2 3.5 4.3 3.5 4.6 3.5 4.9 3.4
20.0 5.4 4.0 5.6 4.2 6.0 4.2 6.2 4.4 6.4 4.4 6.9 4.3 7.3 4.3
22.5 5.3 4.0 5.5 4.1 5.9 4.1 6.1 4.4 6.3 4.3 6.7 4.3 7.2 4.2
25.0 5.2 3.9 5.4 4.1 5.8 4.1 6.0 4.3 6.2 4.3 6.6 4.3 7.0 4.2
27.5 5.1 3.9 5.3 4.0 5.7 4.0 5.9 4.3 6.1 4.3 6.5 4.2 6.9 4.2
50 30.0 5.0 3.9 5.2 4.0 5.6 4.0 5.8 4.2 6.0 4.2 6.4 4.2 6.8 4.1
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.2 5.9 4.2 6.3 4.1 6.7 4.1
35.0 4.9 3.8 5.0 3.9 5.4 3.9 5.6 4.1 5.8 4.1 6.2 4.1 6.5 4.0
37.5 4.8 3.7 4.9 3.8 5.3 3.8 5.5 4.1 5.7 4.1 6.0 4.0 6.4 4.0
40.0 4.7 3.7 4.8 3.8 5.2 3.8 5.4 4.0 5.5 4.0 5.9 4.0 6.3 3.9
43.0 4.6 3.6 4.7 3.7 5.1 3.7 5.2 4.0 5.4 4.0 5.8 3.9 6.1 3.9
20.0 6.9 5.0 7.1 5.1 7.6 5.1 7.9 5.4 8.2 5.4 8.7 5.3 9.3 5.3
22.5 6.7 4.9 7.0 5.1 7.5 5.0 7.8 5.3 8.0 5.3 8.6 5.3 9.1 5.2
25.0 6.6 4.9 6.9 5.0 7.4 5.0 7.6 5.3 7.9 5.3 8.4 5.2 8.9 5.1
27.5 6.5 4.8 6.7 4.9 7.2 4.9 7.5 5.2 7.7 5.2 8.3 5.1 8.8 5.1
63 30.0 6.4 4.7 6.6 4.9 7.1 4.9 7.3 5.2 7.6 5.1 8.1 5.1 8.6 5.0
(7.1) 32.5 6.3 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.1 7.9 5.0 8.5 5.0
35.0 6.2 4.6 6.4 4.8 6.8 4.7 7.1 5.0 7.3 5.0 7.8 5.0 8.3 4.9
37.5 6.1 4.6 6.2 4.7 6.7 4.7 6.9 5.0 7.2 5.0 7.6 4.9 8.1 4.8
40.0 5.9 4.5 6.1 4.6 6.6 4.6 6.8 4.9 7.0 4.9 7.5 4.9 8.0 4.8
43.0 5.8 4.4 6.0 4.6 6.4 4.6 6.6 4.8 6.9 4.8 7.3 4.8 7.8 4.7
20.0 8.7 6.2 9.0 6.4 9.7 6.4 10.0 6.7 10.3 6.7 11.0 6.6 11.7 6.5
22.5 8.5 6.1 8.9 6.3 9.5 6.3 9.8 6.6 10.2 6.6 10.8 6.5 11.5 6.5
25.0 8.4 6.0 8.7 6.2 9.3 6.2 9.7 6.6 10.0 6.5 10.6 6.5 11.3 6.4
27.5 8.3 6.0 8.5 6.1 9.2 6.1 9.5 6.5 9.8 6.5 10.5 6.4 11.1 6.3
80 30.0 8.1 5.9 8.4 6.1 9.0 6.0 9.3 6.4 9.6 6.4 10.3 6.3 10.9 6.2
(9.0) 32.5 8.0 5.8 8.2 6.0 8.8 6.0 9.1 6.3 9.4 6.3 10.1 6.2 10.7 6.2
35.0 7.8 5.7 8.1 5.9 8.7 5.9 9.0 6.3 9.3 6.2 9.9 6.2 10.5 6.1
37.5 7.7 5.7 7.9 5.8 8.5 5.8 8.8 6.2 9.1 6.1 9.7 6.1 10.3 6.0
40.0 7.5 5.6 7.7 5.7 8.3 5.7 8.6 6.1 8.9 6.1 9.5 6.0 10.1 5.9
43.0 7.4 5.5 7.6 5.7 8.1 5.6 8.4 6.0 8.7 6.0 9.3 5.9 9.9 5.8
20.0 10.8 7.7 11.2 8.0 12.0 8.0 12.5 8.4 12.9 8.4 13.7 8.3 14.6 8.2
22.5 10.6 7.6 11.0 7.9 11.8 7.9 12.2 8.3 12.6 8.3 13.5 8.2 14.4 8.1
25.0 10.5 7.6 10.8 7.8 11.6 7.8 12.0 8.2 12.4 8.2 13.3 8.1 14.1 8.0
27.5 10.3 7.5 10.6 7.7 11.4 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
100 30.0 10.1 7.4 10.4 7.6 11.2 7.6 11.6 8.0 12.0 8.0 12.8 7.9 13.6 7.8
(11.2) 32.5 9.9 7.3 10.2 7.5 11.0 7.5 11.4 7.9 11.8 7.9 12.5 7.8 13.3 7.7
35.0 9.7 7.2 10.0 7.4 10.8 7.4 11.2 7.8 11.5 7.8 12.3 7.7 13.1 7.6
37.5 9.5 7.1 9.8 7.3 10.6 7.3 10.9 7.7 11.3 7.7 12.1 7.6 12.8 7.5
40.0 9.4 7.0 9.6 7.2 10.4 7.2 10.7 7.6 11.1 7.6 11.8 7.5 12.6 7.4
43.0 9.2 6.9 9.4 7.1 10.1 7.1 10.5 7.5 10.8 7.5 11.5 7.4 12.3 7.3
20.0 13.5 9.4 14.0 9.7 15.0 9.7 15.6 10.2 16.1 10.2 17.2 10.1 18.3 9.9
22.5 13.3 9.3 13.8 9.6 14.8 9.6 15.3 10.1 15.8 10.0 16.9 9.9 17.9 9.8
25.0 13.1 9.2 13.5 9.5 14.5 9.4 15.0 9.9 15.5 9.9 16.6 9.8 17.6 9.7
27.5 12.8 9.1 13.3 9.3 14.3 9.3 14.8 9.8 15.3 9.8 16.3 9.7 17.3 9.6
125 30.0 12.6 9.0 13.0 9.2 14.0 9.2 14.5 9.7 15.0 9.7 16.0 9.6 17.0 9.4
(14.0) 32.5 12.4 8.8 12.8 9.1 13.7 9.1 14.2 9.6 14.7 9.5 15.7 9.4 16.7 9.3
35.0 12.2 8.7 12.5 8.9 13.5 8.9 14.0 9.5 14.4 9.4 15.4 9.3 16.4 9.2
37.5 11.9 8.6 12.3 8.8 13.2 8.8 13.7 9.3 14.1 9.3 15.1 9.2 16.0 9.1
40.0 11.7 8.5 12.1 8.7 12.9 8.7 13.4 9.2 13.9 9.2 14.8 9.1 15.7 9.0
43.0 11.4 8.3 11.8 8.6 12.6 8.5 13.1 9.0 13.5 9.0 14.4 8.9 15.4 8.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 141


5. Cooling [Ceiling cassette (4-way flow type)]
5-5. Cooling capacity with PUHY-RP850-900YSJM
PLFY-P-VCM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.8 1.9
22.5 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.6 1.9 2.7 1.9
25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
20 30.0 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.7 1.9
(2.2) 32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
35.0 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
40.0 1.9 1.7 1.9 1.7 2.1 1.7 2.2 1.9 2.2 1.9 2.4 1.9 2.6 1.8
43.0 1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.8 2.5 1.8
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
25.0 2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.5 2.3
27.5 2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
(2.8) 32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.2 3.4 2.2
35.0 2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.3 2.9 2.3 3.1 2.2 3.3 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
43.0 2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
20.0 3.4 2.6 3.5 2.7 3.7 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.7
22.5 3.4 2.6 3.5 2.7 3.7 2.6 3.8 2.8 4.0 2.8 4.2 2.8 4.5 2.7
25.0 3.3 2.6 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.8 3.8 2.7 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.1 2.7 4.3 2.7
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.7 4.3 2.7
37.5 3.2 2.5 3.2 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.6
40.0 3.1 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.7 3.9 2.7 4.2 2.6
43.0 3.1 2.4 3.1 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.9 2.6 4.2 2.6
20.0 4.3 3.0 4.4 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.2 5.7 3.2
22.5 4.2 3.0 4.3 3.1 4.6 3.1 4.8 3.2 4.9 3.2 5.3 3.2 5.6 3.2
25.0 4.2 3.0 4.3 3.1 4.6 3.1 4.7 3.2 4.9 3.2 5.2 3.2 5.6 3.1
27.5 4.1 3.0 4.2 3.0 4.5 3.0 4.7 3.2 4.8 3.2 5.2 3.2 5.5 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 3.0 4.6 3.2 4.8 3.2 5.1 3.1 5.5 3.1
(4.5) 32.5 4.0 2.9 4.1 3.0 4.4 3.0 4.6 3.2 4.7 3.1 5.1 3.1 5.4 3.1
35.0 4.0 2.9 4.1 3.0 4.4 3.0 4.5 3.1 4.7 3.1 5.0 3.1 5.4 3.1
37.5 4.0 2.9 4.0 2.9 4.3 2.9 4.5 3.1 4.6 3.1 5.0 3.1 5.3 3.0
40.0 3.9 2.9 4.0 2.9 4.3 2.9 4.4 3.1 4.6 3.1 4.9 3.1 5.3 3.0
43.0 3.9 2.8 3.9 2.9 4.2 2.9 4.4 3.1 4.5 3.0 4.9 3.0 5.2 3.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 142


5. Cooling [Ceiling cassette (4-way flow type)]
PLFY-P-VBM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.4 2.8 3.5 2.9 3.7 2.9 3.9 3.1 4.0 3.1 4.3 3.1 4.5 3.0
22.5 3.4 2.8 3.5 2.9 3.7 2.9 3.8 3.1 4.0 3.1 4.2 3.0 4.5 3.0
25.0 3.3 2.8 3.4 2.9 3.7 2.9 3.8 3.1 3.9 3.1 4.2 3.0 4.4 3.0
27.5 3.3 2.8 3.4 2.9 3.6 2.9 3.8 3.1 3.9 3.1 4.1 3.0 4.4 3.0
32 30.0 3.3 2.8 3.3 2.9 3.6 2.8 3.7 3.0 3.8 3.0 4.1 3.0 4.4 3.0
(3.6) 32.5 3.2 2.7 3.3 2.8 3.5 2.8 3.7 3.0 3.8 3.0 4.1 3.0 4.3 3.0
35.0 3.2 2.7 3.3 2.8 3.5 2.8 3.6 3.0 3.8 3.0 4.0 3.0 4.3 2.9
37.5 3.2 2.7 3.2 2.8 3.5 2.8 3.6 3.0 3.7 3.0 4.0 3.0 4.2 2.9
40.0 3.1 2.7 3.2 2.8 3.4 2.8 3.5 3.0 3.7 3.0 3.9 3.0 4.2 2.9
43.0 3.1 2.7 3.1 2.8 3.4 2.8 3.5 3.0 3.6 3.0 3.9 2.9 4.2 2.9
20.0 4.3 3.4 4.4 3.6 4.7 3.5 4.8 3.8 5.0 3.8 5.3 3.7 5.7 3.7
22.5 4.2 3.4 4.3 3.5 4.6 3.5 4.8 3.8 4.9 3.7 5.3 3.7 5.6 3.6
25.0 4.2 3.4 4.3 3.5 4.6 3.5 4.7 3.7 4.9 3.7 5.2 3.7 5.6 3.6
27.5 4.1 3.4 4.2 3.5 4.5 3.5 4.7 3.7 4.8 3.7 5.2 3.7 5.5 3.6
40 30.0 4.1 3.4 4.2 3.5 4.5 3.4 4.6 3.7 4.8 3.7 5.1 3.6 5.5 3.6
(4.5) 32.5 4.0 3.3 4.1 3.4 4.4 3.4 4.6 3.7 4.7 3.7 5.1 3.6 5.4 3.6
35.0 4.0 3.3 4.1 3.4 4.4 3.4 4.5 3.6 4.7 3.6 5.0 3.6 5.4 3.6
37.5 4.0 3.3 4.0 3.4 4.3 3.4 4.5 3.6 4.6 3.6 5.0 3.6 5.3 3.6
40.0 3.9 3.3 4.0 3.4 4.3 3.4 4.4 3.6 4.6 3.6 4.9 3.6 5.3 3.5
43.0 3.9 3.3 3.9 3.3 4.2 3.3 4.4 3.6 4.5 3.6 4.9 3.5 5.2 3.5
20.0 5.3 4.0 5.5 4.1 5.8 4.1 6.0 4.3 6.2 4.3 6.6 4.3 7.0 4.2
22.5 5.2 4.0 5.4 4.1 5.8 4.0 6.0 4.3 6.2 4.3 6.6 4.2 7.0 4.2
25.0 5.2 3.9 5.3 4.0 5.7 4.0 5.9 4.3 6.1 4.2 6.5 4.2 6.9 4.2
27.5 5.1 3.9 5.3 4.0 5.6 4.0 5.8 4.2 6.0 4.2 6.4 4.2 6.9 4.1
50 30.0 5.1 3.9 5.2 4.0 5.6 4.0 5.8 4.2 6.0 4.2 6.4 4.2 6.8 4.1
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.2 5.9 4.2 6.3 4.1 6.7 4.1
35.0 5.0 3.8 5.1 3.9 5.4 3.9 5.6 4.1 5.8 4.1 6.2 4.1 6.7 4.1
37.5 4.9 3.8 5.0 3.9 5.4 3.9 5.6 4.1 5.8 4.1 6.2 4.1 6.6 4.0
40.0 4.9 3.8 4.9 3.9 5.3 3.8 5.5 4.1 5.7 4.1 6.1 4.1 6.5 4.0
43.0 4.8 3.7 4.9 3.8 5.2 3.8 5.4 4.1 5.6 4.1 6.0 4.0 6.5 4.0
20.0 6.7 4.9 6.9 5.0 7.4 5.0 7.6 5.3 7.9 5.3 8.4 5.2 8.9 5.1
22.5 6.6 4.9 6.8 5.0 7.3 5.0 7.6 5.3 7.8 5.2 8.3 5.2 8.8 5.1
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.2 8.2 5.1 8.8 5.1
27.5 6.5 4.8 6.7 4.9 7.2 4.9 7.4 5.2 7.6 5.2 8.2 5.1 8.7 5.0
63 30.0 6.4 4.8 6.6 4.9 7.1 4.9 7.3 5.1 7.6 5.1 8.1 5.1 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.1 8.0 5.0 8.5 5.0
35.0 6.3 4.7 6.4 4.8 6.9 4.8 7.1 5.0 7.4 5.1 7.9 5.0 8.5 5.0
37.5 6.2 4.7 6.3 4.8 6.8 4.7 7.1 5.0 7.3 5.0 7.8 5.0 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 5.0 7.2 5.0 7.8 5.0 8.3 4.9
43.0 6.1 4.6 6.2 4.7 6.7 4.7 6.9 5.0 7.1 5.0 7.7 4.9 8.2 4.9
20.0 8.5 6.1 8.8 6.2 9.4 6.2 9.7 6.6 10.0 6.5 10.6 6.5 11.3 6.4
22.5 8.4 6.0 8.7 6.2 9.3 6.2 9.6 6.5 9.9 6.5 10.5 6.4 11.2 6.3
25.0 8.3 6.0 8.6 6.1 9.2 6.1 9.5 6.5 9.8 6.4 10.4 6.4 11.1 6.3
27.5 8.3 6.0 8.5 6.1 9.1 6.1 9.4 6.4 9.7 6.4 10.3 6.3 11.0 6.3
80 30.0 8.2 5.9 8.4 6.0 9.0 6.0 9.3 6.4 9.6 6.4 10.2 6.3 10.9 6.2
(9.0) 32.5 8.1 5.9 8.3 6.0 8.9 6.0 9.2 6.3 9.5 6.3 10.1 6.3 10.8 6.2
35.0 8.0 5.8 8.1 5.9 8.8 5.9 9.0 6.3 9.4 6.3 10.0 6.2 10.7 6.2
37.5 7.9 5.8 8.0 5.9 8.7 5.9 9.0 6.2 9.3 6.2 9.9 6.2 10.6 6.1
40.0 7.8 5.7 7.9 5.8 8.6 5.8 8.9 6.2 9.2 6.2 9.8 6.1 10.5 6.1
43.0 7.7 5.7 7.8 5.8 8.4 5.8 8.7 6.1 9.1 6.1 9.7 6.1 10.4 6.0
20.0 10.6 7.6 10.9 7.8 11.7 7.8 12.0 8.2 12.4 8.2 13.2 8.1 14.1 8.0
22.5 10.5 7.6 10.8 7.8 11.5 7.7 11.9 8.2 12.3 8.1 13.1 8.0 13.9 7.9
25.0 10.4 7.5 10.6 7.7 11.4 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
27.5 10.3 7.5 10.5 7.6 11.3 7.6 11.7 8.0 12.1 8.0 12.9 7.9 13.7 7.8
100 30.0 10.2 7.4 10.4 7.6 11.2 7.5 11.5 8.0 11.9 8.0 12.7 7.9 13.6 7.8
(11.2) 32.5 10.1 7.3 10.3 7.5 11.0 7.5 11.4 7.9 11.8 7.9 12.6 7.8 13.5 7.7
35.0 9.9 7.3 10.1 7.4 10.9 7.4 11.2 7.8 11.7 7.8 12.5 7.8 13.3 7.7
37.5 9.8 7.2 10.0 7.4 10.8 7.4 11.2 7.8 11.6 7.8 12.4 7.7 13.2 7.7
40.0 9.7 7.2 9.9 7.3 10.6 7.3 11.0 7.8 11.4 7.7 12.2 7.7 13.1 7.6
43.0 9.6 7.1 9.7 7.2 10.5 7.2 10.9 7.7 11.3 7.7 12.1 7.6 12.9 7.6
20.0 13.2 9.3 13.6 9.5 14.6 9.5 15.1 10.0 15.5 9.9 16.5 9.8 17.6 9.7
22.5 13.1 9.2 13.5 9.4 14.4 9.4 14.9 9.9 15.4 9.8 16.4 9.7 17.4 9.6
25.0 13.0 9.1 13.3 9.3 14.3 9.3 14.7 9.8 15.2 9.8 16.2 9.7 17.3 9.5
27.5 12.8 9.1 13.2 9.3 14.1 9.2 14.6 9.7 15.1 9.7 16.1 9.6 17.1 9.5
125 30.0 12.7 9.0 13.0 9.2 13.9 9.2 14.4 9.7 14.9 9.6 15.9 9.5 17.0 9.4
(14.0) 32.5 12.6 8.9 12.8 9.1 13.8 9.1 14.3 9.6 14.8 9.6 15.8 9.5 16.8 9.4
35.0 12.4 8.9 12.7 9.0 13.6 9.0 14.0 9.5 14.6 9.5 15.6 9.4 16.7 9.3
37.5 12.3 8.8 12.5 8.9 13.5 8.9 14.0 9.4 14.4 9.4 15.5 9.3 16.5 9.3
40.0 12.2 8.7 12.4 8.9 13.3 8.9 13.8 9.4 14.3 9.3 15.3 9.3 16.4 9.2
43.0 12.0 8.6 12.2 8.8 13.1 8.8 13.6 9.3 14.1 9.3 15.1 9.2 16.2 9.1
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 143


6. Cooling [Ceiling suspended]
6-1. Cooling capacity with PUHY,PURY-RP200-250YJM
6. Cooling [Ceiling suspended]

PCFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.3 5.0 3.3 5.3 3.3 5.7 3.2
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.3 5.0 3.3 5.3 3.3 5.7 3.2
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.3 5.0 3.3 5.3 3.2 5.6 3.2
27.5 4.3 3.1 4.4 3.1 4.6 3.1 4.8 3.3 4.9 3.2 5.2 3.2 5.5 3.1
40 30.0 4.2 3.0 4.3 3.1 4.6 3.1 4.7 3.2 4.8 3.2 5.1 3.2 5.4 3.1
(4.5) 32.5 4.1 3.0 4.2 3.1 4.5 3.0 4.6 3.2 4.7 3.2 5.0 3.1 5.3 3.1
35.0 4.0 3.0 4.1 3.0 4.4 3.0 4.5 3.2 4.6 3.1 4.9 3.1 5.2 3.0
37.5 4.0 2.9 4.1 3.0 4.3 3.0 4.4 3.1 4.5 3.1 4.8 3.0 5.0 3.0
40.0 3.9 2.9 4.0 3.0 4.2 2.9 4.3 3.1 4.4 3.1 4.7 3.0 4.9 2.9
43.0 3.8 2.8 3.9 2.9 4.1 2.9 4.2 3.0 4.3 3.0 4.5 2.9 4.8 2.9
20.0 6.7 4.8 7.0 4.9 7.5 4.9 7.7 5.2 7.9 5.1 8.4 5.1 9.0 5.0
22.5 6.7 4.8 7.0 4.9 7.5 4.9 7.7 5.2 7.9 5.1 8.4 5.1 9.0 5.0
25.0 6.7 4.8 7.0 4.9 7.5 4.9 7.7 5.1 7.9 5.1 8.3 5.0 8.8 5.0
27.5 6.7 4.8 6.9 4.9 7.3 4.8 7.5 5.1 7.7 5.0 8.1 5.0 8.7 4.9
63 30.0 6.6 4.7 6.8 4.8 7.2 4.8 7.4 5.0 7.6 5.0 8.0 4.9 8.5 4.8
(7.1) 32.5 6.5 4.7 6.7 4.8 7.1 4.7 7.2 5.0 7.4 4.9 7.8 4.8 8.3 4.8
35.0 6.4 4.6 6.5 4.7 6.9 4.7 7.1 4.9 7.3 4.9 7.7 4.8 8.1 4.7
37.5 6.2 4.5 6.4 4.6 6.8 4.6 7.0 4.8 7.2 4.8 7.5 4.7 8.0 4.6
40.0 6.1 4.5 6.3 4.6 6.7 4.5 6.8 4.8 7.0 4.7 7.4 4.6 7.8 4.6
43.0 6.0 4.4 6.1 4.5 6.5 4.5 6.7 4.7 6.9 4.7 7.2 4.6 7.6 4.5
20.0 10.6 7.4 11.0 7.6 11.8 7.6 12.1 8.0 12.5 7.9 13.2 7.8 14.2 7.8
22.5 10.6 7.4 11.0 7.6 11.8 7.6 12.1 8.0 12.5 7.9 13.2 7.8 14.2 7.8
25.0 10.6 7.4 11.0 7.6 11.8 7.6 12.1 8.0 12.4 7.9 13.1 7.8 13.9 7.7
27.5 10.6 7.4 10.9 7.6 11.6 7.5 11.9 7.9 12.2 7.8 12.9 7.7 13.7 7.6
100 30.0 10.4 7.3 10.7 7.5 11.3 7.4 11.6 7.8 12.0 7.7 12.6 7.6 13.4 7.4
(11.2) 32.5 10.2 7.2 10.5 7.4 11.1 7.3 11.4 7.7 11.7 7.6 12.4 7.5 13.1 7.3
35.0 10.0 7.1 10.3 7.3 10.9 7.2 11.2 7.5 11.5 7.5 12.1 7.3 12.8 7.2
37.5 9.8 7.0 10.1 7.2 10.7 7.1 11.0 7.5 11.3 7.4 11.9 7.2 12.6 7.1
40.0 9.6 6.9 9.9 7.1 10.5 7.0 10.8 7.4 11.1 7.3 11.6 7.1 12.3 7.0
43.0 9.4 6.8 9.7 7.0 10.2 6.9 10.5 7.2 10.8 7.2 11.3 7.0 12.0 6.9
20.0 13.3 9.2 13.8 9.5 14.7 9.5 15.2 9.9 15.6 9.9 16.6 9.7 17.7 9.6
22.5 13.3 9.2 13.8 9.5 14.7 9.5 15.2 9.9 15.6 9.9 16.6 9.7 17.7 9.6
25.0 13.3 9.2 13.8 9.5 14.7 9.5 15.1 9.9 15.5 9.8 16.4 9.7 17.4 9.5
27.5 13.3 9.2 13.6 9.4 14.4 9.3 14.8 9.8 15.2 9.7 16.1 9.5 17.1 9.4
125 30.0 13.0 9.1 13.4 9.3 14.2 9.2 14.6 9.6 14.9 9.6 15.8 9.4 16.7 9.3
(14.0) 32.5 12.8 9.0 13.2 9.2 13.9 9.1 14.3 9.5 14.7 9.4 15.4 9.3 16.4 9.1
35.0 12.5 8.8 12.9 9.1 13.7 8.9 14.0 9.4 14.4 9.3 15.1 9.1 16.0 9.0
37.5 12.3 8.7 12.7 8.9 13.4 8.8 13.8 9.3 14.1 9.2 14.8 9.0 15.7 8.9
40.0 12.1 8.6 12.4 8.8 13.1 8.7 13.5 9.1 13.8 9.1 14.5 8.9 15.4 8.7
43.0 11.8 8.4 12.1 8.7 12.8 8.5 13.2 9.0 13.5 8.9 14.1 8.7 15.0 8.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 144


6. Cooling [Ceiling suspended]
6-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PCFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.4 3.1 4.5 3.2 4.9 3.2 5.0 3.4 5.2 3.4 5.5 3.3 5.8 3.3
22.5 4.4 3.1 4.5 3.2 4.8 3.2 4.9 3.4 5.1 3.3 5.4 3.3 5.7 3.2
25.0 4.3 3.1 4.4 3.2 4.7 3.1 4.9 3.3 5.0 3.3 5.3 3.3 5.6 3.2
27.5 4.2 3.0 4.3 3.1 4.6 3.1 4.8 3.3 4.9 3.3 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.2 4.8 3.2 5.1 3.2 5.4 3.1
(4.5) 32.5 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.2 4.7 3.2 5.0 3.1 5.3 3.1
35.0 4.0 2.9 4.1 3.0 4.3 3.0 4.5 3.2 4.6 3.1 4.9 3.1 5.2 3.0
37.5 3.9 2.9 4.0 3.0 4.2 2.9 4.4 3.1 4.5 3.1 4.8 3.0 5.1 3.0
40.0 3.9 2.9 3.9 2.9 4.2 2.9 4.3 3.1 4.4 3.0 4.7 3.0 5.0 3.0
43.0 3.8 2.8 3.8 2.9 4.0 2.8 4.2 3.0 4.3 3.0 4.6 3.0 4.8 2.9
20.0 6.9 4.9 7.1 5.0 7.7 5.0 7.9 5.3 8.2 5.3 8.7 5.2 9.2 5.1
22.5 6.9 4.9 7.1 5.0 7.6 5.0 7.8 5.2 8.0 5.2 8.5 5.1 9.1 5.0
25.0 6.8 4.8 7.0 4.9 7.4 4.9 7.7 5.1 7.9 5.1 8.4 5.1 8.9 5.0
27.5 6.7 4.7 6.8 4.8 7.3 4.8 7.5 5.1 7.7 5.0 8.2 5.0 8.7 4.9
63 30.0 6.5 4.7 6.7 4.8 7.1 4.7 7.4 5.0 7.6 5.0 8.1 4.9 8.5 4.8
(7.1) 32.5 6.4 4.6 6.6 4.7 7.0 4.7 7.2 4.9 7.4 4.9 7.9 4.9 8.4 4.8
35.0 6.3 4.6 6.4 4.6 6.8 4.6 7.1 4.9 7.3 4.8 7.7 4.8 8.2 4.7
37.5 6.2 4.5 6.3 4.6 6.7 4.5 6.9 4.8 7.1 4.8 7.6 4.7 8.0 4.6
40.0 6.1 4.5 6.2 4.5 6.6 4.5 6.8 4.7 7.0 4.7 7.4 4.7 7.8 4.6
43.0 6.0 4.4 6.0 4.4 6.4 4.4 6.6 4.7 6.8 4.6 7.2 4.6 7.6 4.5
20.0 10.9 7.6 11.3 7.8 12.1 7.8 12.5 8.2 12.9 8.1 13.7 8.0 14.5 7.9
22.5 10.8 7.5 11.2 7.7 11.9 7.7 12.3 8.1 12.7 8.0 13.5 7.9 14.3 7.8
25.0 10.7 7.5 11.0 7.6 11.7 7.6 12.1 8.0 12.5 7.9 13.2 7.8 14.0 7.7
27.5 10.5 7.4 10.8 7.5 11.5 7.5 11.8 7.8 12.2 7.8 13.0 7.7 13.7 7.6
100 30.0 10.3 7.3 10.6 7.4 11.2 7.4 11.6 7.7 12.0 7.7 12.7 7.6 13.5 7.5
(11.2) 32.5 10.2 7.2 10.3 7.3 11.0 7.2 11.4 7.6 11.7 7.6 12.4 7.5 13.2 7.4
35.0 10.0 7.1 10.1 7.2 10.8 7.1 11.2 7.5 11.5 7.5 12.2 7.4 12.9 7.3
37.5 9.8 7.0 9.9 7.1 10.6 7.0 10.9 7.4 11.2 7.4 11.9 7.3 12.6 7.2
40.0 9.6 6.9 9.7 7.0 10.3 6.9 10.7 7.3 11.0 7.3 11.7 7.2 12.4 7.1
43.0 9.4 6.8 9.5 6.9 10.1 6.8 10.4 7.2 10.7 7.1 11.4 7.1 12.1 6.9
20.0 13.6 9.4 14.1 9.7 15.1 9.7 15.7 10.2 16.2 10.1 17.2 10.0 18.2 9.8
22.5 13.6 9.4 14.0 9.6 14.9 9.6 15.4 10.0 15.9 10.0 16.8 9.9 17.8 9.7
25.0 13.3 9.3 13.7 9.5 14.6 9.4 15.1 9.9 15.6 9.8 16.5 9.7 17.5 9.6
27.5 13.1 9.2 13.5 9.3 14.3 9.3 14.8 9.8 15.3 9.7 16.2 9.6 17.2 9.4
125 30.0 12.9 9.0 13.2 9.2 14.1 9.1 14.5 9.6 15.0 9.6 15.9 9.4 16.8 9.3
(14.0) 32.5 12.7 8.9 12.9 9.1 13.8 9.0 14.2 9.5 14.7 9.4 15.6 9.3 16.5 9.2
35.0 12.5 8.8 12.7 8.9 13.5 8.9 14.0 9.4 14.4 9.3 15.2 9.2 16.2 9.0
37.5 12.3 8.7 12.4 8.8 13.2 8.7 13.6 9.2 14.1 9.2 14.9 9.0 15.8 8.9
40.0 12.0 8.6 12.2 8.7 12.9 8.6 13.3 9.1 13.8 9.0 14.6 8.9 15.5 8.8
43.0 11.8 8.4 11.8 8.5 12.6 8.4 13.0 8.9 13.4 8.9 14.2 8.8 15.1 8.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 145


6. Cooling [Ceiling suspended]
6-3. Cooling capacity with PUHY-RP450-650YSJM
PCFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.1 4.4 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.3 5.7 3.2
22.5 4.2 3.0 4.3 3.1 4.6 3.1 4.8 3.3 4.9 3.3 5.3 3.2 5.6 3.2
25.0 4.2 3.0 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.2 5.2 3.2 5.6 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.2 4.8 3.2 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.0 4.5 3.0 4.6 3.2 4.8 3.2 5.1 3.2 5.5 3.1
(4.5) 32.5 4.0 3.0 4.1 3.0 4.4 3.0 4.6 3.2 4.7 3.2 5.1 3.2 5.4 3.1
35.0 4.0 2.9 4.1 3.0 4.4 3.0 4.5 3.2 4.7 3.2 5.0 3.1 5.4 3.1
37.5 4.0 2.9 4.0 3.0 4.3 3.0 4.5 3.1 4.6 3.1 5.0 3.1 5.3 3.1
40.0 3.9 2.9 4.0 2.9 4.3 2.9 4.4 3.1 4.6 3.1 4.9 3.1 5.3 3.1
43.0 3.9 2.9 3.9 2.9 4.2 2.9 4.4 3.1 4.5 3.1 4.9 3.1 5.2 3.0
20.0 6.7 4.8 6.9 4.9 7.4 4.9 7.6 5.1 7.9 5.1 8.4 5.1 8.9 5.0
22.5 6.6 4.7 6.8 4.9 7.3 4.8 7.6 5.1 7.8 5.1 8.3 5.0 8.8 5.0
25.0 6.6 4.7 6.8 4.8 7.2 4.8 7.5 5.1 7.7 5.0 8.2 5.0 8.8 4.9
27.5 6.5 4.7 6.7 4.8 7.2 4.8 7.4 5.0 7.6 5.0 8.2 5.0 8.7 4.9
63 30.0 6.4 4.6 6.6 4.7 7.1 4.7 7.3 5.0 7.6 5.0 8.1 4.9 8.6 4.9
(7.1) 32.5 6.4 4.6 6.5 4.7 7.0 4.7 7.2 4.9 7.5 4.9 8.0 4.9 8.5 4.8
35.0 6.3 4.6 6.4 4.6 6.9 4.6 7.1 4.9 7.4 4.9 7.9 4.9 8.5 4.8
37.5 6.2 4.5 6.3 4.6 6.8 4.6 7.1 4.9 7.3 4.9 7.8 4.8 8.4 4.8
40.0 6.2 4.5 6.3 4.6 6.7 4.6 7.0 4.8 7.2 4.8 7.8 4.8 8.3 4.8
43.0 6.1 4.5 6.2 4.5 6.7 4.5 6.9 4.8 7.1 4.8 7.7 4.8 8.2 4.7
20.0 10.6 7.4 10.9 7.6 11.7 7.6 12.0 7.9 12.4 7.9 13.2 7.8 14.1 7.7
22.5 10.5 7.3 10.8 7.5 11.5 7.5 11.9 7.9 12.3 7.8 13.1 7.8 13.9 7.7
25.0 10.4 7.3 10.6 7.5 11.4 7.4 11.8 7.8 12.2 7.8 13.0 7.7 13.8 7.6
27.5 10.3 7.2 10.5 7.4 11.3 7.4 11.7 7.8 12.1 7.7 12.9 7.7 13.7 7.6
100 30.0 10.2 7.2 10.4 7.3 11.2 7.3 11.5 7.7 11.9 7.7 12.7 7.6 13.6 7.5
(11.2) 32.5 10.1 7.1 10.3 7.3 11.0 7.2 11.4 7.6 11.8 7.6 12.6 7.6 13.5 7.5
35.0 9.9 7.1 10.1 7.2 10.9 7.2 11.2 7.5 11.7 7.6 12.5 7.5 13.3 7.4
37.5 9.8 7.0 10.0 7.1 10.8 7.1 11.2 7.5 11.6 7.5 12.4 7.5 13.2 7.4
40.0 9.7 7.0 9.9 7.1 10.6 7.1 11.0 7.5 11.4 7.5 12.2 7.4 13.1 7.3
43.0 9.6 6.9 9.7 7.0 10.5 7.0 10.9 7.4 11.3 7.4 12.1 7.3 12.9 7.3
20.0 13.2 9.2 13.6 9.4 14.6 9.4 15.1 9.9 15.5 9.8 16.5 9.7 17.6 9.6
22.5 13.1 9.1 13.5 9.3 14.4 9.3 14.9 9.8 15.4 9.8 16.4 9.7 17.4 9.5
25.0 13.0 9.1 13.3 9.3 14.3 9.2 14.7 9.7 15.2 9.7 16.2 9.6 17.3 9.5
27.5 12.8 9.0 13.2 9.2 14.1 9.2 14.6 9.6 15.1 9.6 16.1 9.5 17.1 9.4
125 30.0 12.7 8.9 13.0 9.1 13.9 9.1 14.4 9.6 14.9 9.5 15.9 9.5 17.0 9.3
(14.0) 32.5 12.6 8.9 12.8 9.0 13.8 9.0 14.3 9.5 14.8 9.5 15.8 9.4 16.8 9.3
35.0 12.4 8.8 12.7 8.9 13.6 8.9 14.0 9.4 14.6 9.4 15.6 9.3 16.7 9.2
37.5 12.3 8.7 12.5 8.9 13.5 8.9 14.0 9.4 14.4 9.3 15.5 9.3 16.5 9.2
40.0 12.2 8.6 12.4 8.8 13.3 8.8 13.8 9.3 14.3 9.3 15.3 9.2 16.4 9.1
43.0 12.0 8.6 12.2 8.7 13.1 8.7 13.6 9.2 14.1 9.2 15.1 9.1 16.2 9.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 146


6. Cooling [Ceiling suspended]
6-4. Cooling capacity with PUHY-RP700-800YSJM
PCFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.1 4.5 3.2 4.8 3.2 5.0 3.4 5.2 3.4 5.5 3.3 5.9 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.3 5.1 3.3 5.4 3.3 5.8 3.3
25.0 4.2 3.0 4.3 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.3 5.7 3.2
27.5 4.1 3.0 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.2 5.6 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.0 4.7 3.2 4.8 3.2 5.1 3.2 5.5 3.1
(4.5) 32.5 4.0 2.9 4.1 3.0 4.4 3.0 4.6 3.2 4.7 3.2 5.0 3.1 5.4 3.1
35.0 3.9 2.9 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.1 4.9 3.1 5.3 3.1
37.5 3.8 2.9 4.0 2.9 4.2 2.9 4.4 3.1 4.5 3.1 4.8 3.1 5.2 3.0
40.0 3.8 2.8 3.9 2.9 4.2 2.9 4.3 3.1 4.5 3.1 4.8 3.0 5.1 3.0
43.0 3.7 2.8 3.8 2.9 4.1 2.8 4.2 3.0 4.3 3.0 4.6 3.0 4.9 2.9
20.0 6.9 4.8 7.1 5.0 7.6 5.0 7.9 5.3 8.2 5.2 8.7 5.2 9.3 5.1
22.5 6.7 4.8 7.0 4.9 7.5 4.9 7.8 5.2 8.0 5.2 8.6 5.1 9.1 5.1
25.0 6.6 4.7 6.9 4.9 7.4 4.9 7.6 5.1 7.9 5.1 8.4 5.1 8.9 5.0
27.5 6.5 4.7 6.7 4.8 7.2 4.8 7.5 5.1 7.7 5.0 8.3 5.0 8.8 4.9
63 30.0 6.4 4.6 6.6 4.7 7.1 4.7 7.3 5.0 7.6 5.0 8.1 4.9 8.6 4.9
(7.1) 32.5 6.3 4.5 6.5 4.7 7.0 4.7 7.2 4.9 7.5 4.9 7.9 4.9 8.5 4.8
35.0 6.2 4.5 6.4 4.6 6.8 4.6 7.1 4.9 7.3 4.9 7.8 4.8 8.3 4.7
37.5 6.1 4.4 6.2 4.6 6.7 4.5 6.9 4.8 7.2 4.8 7.6 4.8 8.1 4.7
40.0 5.9 4.4 6.1 4.5 6.6 4.5 6.8 4.8 7.0 4.7 7.5 4.7 8.0 4.6
43.0 5.8 4.3 6.0 4.4 6.4 4.4 6.6 4.7 6.9 4.7 7.3 4.6 7.8 4.6
20.0 10.8 7.5 11.2 7.7 12.0 7.7 12.5 8.1 12.9 8.1 13.7 8.0 14.6 7.9
22.5 10.6 7.4 11.0 7.6 11.8 7.6 12.2 8.0 12.6 8.0 13.5 7.9 14.4 7.8
25.0 10.5 7.3 10.8 7.5 11.6 7.5 12.0 7.9 12.4 7.9 13.3 7.8 14.1 7.7
27.5 10.3 7.2 10.6 7.4 11.4 7.4 11.8 7.8 12.2 7.8 13.0 7.7 13.8 7.6
100 30.0 10.1 7.1 10.4 7.3 11.2 7.3 11.6 7.7 12.0 7.7 12.8 7.6 13.6 7.5
(11.2) 32.5 9.9 7.0 10.2 7.2 11.0 7.2 11.4 7.6 11.8 7.6 12.5 7.5 13.3 7.4
35.0 9.7 7.0 10.0 7.1 10.8 7.1 11.2 7.5 11.5 7.5 12.3 7.4 13.1 7.3
37.5 9.5 6.9 9.8 7.0 10.6 7.0 10.9 7.4 11.3 7.4 12.1 7.3 12.8 7.2
40.0 9.4 6.8 9.6 6.9 10.4 6.9 10.7 7.3 11.1 7.3 11.8 7.2 12.6 7.1
43.0 9.2 6.7 9.4 6.8 10.1 6.8 10.5 7.2 10.8 7.2 11.5 7.1 12.3 7.0
20.0 13.5 9.4 14.0 9.6 15.0 9.6 15.6 10.1 16.1 10.1 17.2 10.0 18.3 9.9
22.5 13.3 9.2 13.8 9.5 14.8 9.5 15.3 10.0 15.8 10.0 16.9 9.9 17.9 9.7
25.0 13.1 9.1 13.5 9.4 14.5 9.4 15.0 9.9 15.5 9.8 16.6 9.7 17.6 9.6
27.5 12.8 9.0 13.3 9.2 14.3 9.2 14.8 9.7 15.3 9.7 16.3 9.6 17.3 9.5
125 30.0 12.6 8.9 13.0 9.1 14.0 9.1 14.5 9.6 15.0 9.6 16.0 9.5 17.0 9.4
(14.0) 32.5 12.4 8.8 12.8 9.0 13.7 9.0 14.2 9.5 14.7 9.4 15.7 9.4 16.7 9.2
35.0 12.2 8.6 12.5 8.9 13.5 8.9 14.0 9.4 14.4 9.3 15.4 9.2 16.4 9.1
37.5 11.9 8.5 12.3 8.7 13.2 8.7 13.7 9.2 14.1 9.2 15.1 9.1 16.0 9.0
40.0 11.7 8.4 12.1 8.6 12.9 8.6 13.4 9.1 13.9 9.1 14.8 9.0 15.7 8.9
43.0 11.4 8.3 11.8 8.5 12.6 8.5 13.1 9.0 13.5 8.9 14.4 8.8 15.4 8.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 147


6. Cooling [Ceiling suspended]
6-5. Cooling capacity with PUHY-RP850-900YSJM
PCFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.3 3.1 4.4 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.3 5.7 3.2
22.5 4.2 3.0 4.3 3.1 4.6 3.1 4.8 3.3 4.9 3.3 5.3 3.2 5.6 3.2
25.0 4.2 3.0 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.2 5.2 3.2 5.6 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.2 4.8 3.2 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.0 4.5 3.0 4.6 3.2 4.8 3.2 5.1 3.2 5.5 3.1
(4.5) 32.5 4.0 3.0 4.1 3.0 4.4 3.0 4.6 3.2 4.7 3.2 5.1 3.2 5.4 3.1
35.0 4.0 2.9 4.1 3.0 4.4 3.0 4.5 3.2 4.7 3.2 5.0 3.1 5.4 3.1
37.5 4.0 2.9 4.0 3.0 4.3 3.0 4.5 3.1 4.6 3.1 5.0 3.1 5.3 3.1
40.0 3.9 2.9 4.0 2.9 4.3 2.9 4.4 3.1 4.6 3.1 4.9 3.1 5.3 3.1
43.0 3.9 2.9 3.9 2.9 4.2 2.9 4.4 3.1 4.5 3.1 4.9 3.1 5.2 3.0
20.0 6.7 4.8 6.9 4.9 7.4 4.9 7.6 5.1 7.9 5.1 8.4 5.1 8.9 5.0
22.5 6.6 4.7 6.8 4.9 7.3 4.8 7.6 5.1 7.8 5.1 8.3 5.0 8.8 5.0
25.0 6.6 4.7 6.8 4.8 7.2 4.8 7.5 5.1 7.7 5.0 8.2 5.0 8.8 4.9
27.5 6.5 4.7 6.7 4.8 7.2 4.8 7.4 5.0 7.6 5.0 8.2 5.0 8.7 4.9
63 30.0 6.4 4.6 6.6 4.7 7.1 4.7 7.3 5.0 7.6 5.0 8.1 4.9 8.6 4.9
(7.1) 32.5 6.4 4.6 6.5 4.7 7.0 4.7 7.2 4.9 7.5 4.9 8.0 4.9 8.5 4.8
35.0 6.3 4.6 6.4 4.6 6.9 4.6 7.1 4.9 7.4 4.9 7.9 4.9 8.5 4.8
37.5 6.2 4.5 6.3 4.6 6.8 4.6 7.1 4.9 7.3 4.9 7.8 4.8 8.4 4.8
40.0 6.2 4.5 6.3 4.6 6.7 4.6 7.0 4.8 7.2 4.8 7.8 4.8 8.3 4.8
43.0 6.1 4.5 6.2 4.5 6.7 4.5 6.9 4.8 7.1 4.8 7.7 4.8 8.2 4.7
20.0 10.6 7.4 10.9 7.6 11.7 7.6 12.0 7.9 12.4 7.9 13.2 7.8 14.1 7.7
22.5 10.5 7.3 10.8 7.5 11.5 7.5 11.9 7.9 12.3 7.8 13.1 7.8 13.9 7.7
25.0 10.4 7.3 10.6 7.5 11.4 7.4 11.8 7.8 12.2 7.8 13.0 7.7 13.8 7.6
27.5 10.3 7.2 10.5 7.4 11.3 7.4 11.7 7.8 12.1 7.7 12.9 7.7 13.7 7.6
100 30.0 10.2 7.2 10.4 7.3 11.2 7.3 11.5 7.7 11.9 7.7 12.7 7.6 13.6 7.5
(11.2) 32.5 10.1 7.1 10.3 7.3 11.0 7.2 11.4 7.6 11.8 7.6 12.6 7.6 13.5 7.5
35.0 9.9 7.1 10.1 7.2 10.9 7.2 11.2 7.5 11.7 7.6 12.5 7.5 13.3 7.4
37.5 9.8 7.0 10.0 7.1 10.8 7.1 11.2 7.5 11.6 7.5 12.4 7.5 13.2 7.4
40.0 9.7 7.0 9.9 7.1 10.6 7.1 11.0 7.5 11.4 7.5 12.2 7.4 13.1 7.3
43.0 9.6 6.9 9.7 7.0 10.5 7.0 10.9 7.4 11.3 7.4 12.1 7.3 12.9 7.3
20.0 13.2 9.2 13.6 9.4 14.6 9.4 15.1 9.9 15.5 9.8 16.5 9.7 17.6 9.6
22.5 13.1 9.1 13.5 9.3 14.4 9.3 14.9 9.8 15.4 9.8 16.4 9.7 17.4 9.5
25.0 13.0 9.1 13.3 9.3 14.3 9.2 14.7 9.7 15.2 9.7 16.2 9.6 17.3 9.5
27.5 12.8 9.0 13.2 9.2 14.1 9.2 14.6 9.6 15.1 9.6 16.1 9.5 17.1 9.4
125 30.0 12.7 8.9 13.0 9.1 13.9 9.1 14.4 9.6 14.9 9.5 15.9 9.5 17.0 9.3
(14.0) 32.5 12.6 8.9 12.8 9.0 13.8 9.0 14.3 9.5 14.8 9.5 15.8 9.4 16.8 9.3
35.0 12.4 8.8 12.7 8.9 13.6 8.9 14.0 9.4 14.6 9.4 15.6 9.3 16.7 9.2
37.5 12.3 8.7 12.5 8.9 13.5 8.9 14.0 9.4 14.4 9.3 15.5 9.3 16.5 9.2
40.0 12.2 8.6 12.4 8.8 13.3 8.8 13.8 9.3 14.3 9.3 15.3 9.2 16.4 9.1
43.0 12.0 8.6 12.2 8.7 13.1 8.7 13.6 9.2 14.1 9.2 15.1 9.1 16.2 9.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 148


7. Cooling [Wall mounted]
7-1. Cooling capacity with PUHY,PURY-RP200-250YJM
7. Cooling [Wall mounted]

PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.2
22.5 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.2
25.0 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.2
27.5 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 1.8 1.2 2.0 1.2 2.1 1.2
15 30.0 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2
(1.7) 32.5 1.6 1.1 1.6 1.2 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
35.0 1.5 1.1 1.6 1.1 1.7 1.1 1.7 1.2 1.7 1.2 1.8 1.2 1.9 1.1
37.5 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.8 1.1 1.9 1.1
40.0 1.5 1.1 1.5 1.1 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.1 1.9 1.1
43.0 1.4 1.1 1.5 1.1 1.6 1.1 1.6 1.1 1.6 1.1 1.7 1.1 1.8 1.1
20.0 2.1 1.5 2.2 1.5 2.3 1.5 2.4 1.6 2.5 1.6 2.6 1.6 2.8 1.6
22.5 2.1 1.5 2.2 1.5 2.3 1.5 2.4 1.6 2.5 1.6 2.6 1.6 2.8 1.6
25.0 2.1 1.5 2.2 1.5 2.3 1.5 2.4 1.6 2.4 1.6 2.6 1.6 2.7 1.5
27.5 2.1 1.5 2.1 1.5 2.3 1.5 2.3 1.6 2.4 1.6 2.5 1.5 2.7 1.5
20 30.0 2.0 1.5 2.1 1.5 2.2 1.5 2.3 1.6 2.3 1.5 2.5 1.5 2.6 1.5
(2.2) 32.5 2.0 1.4 2.1 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.4 1.5 2.6 1.5
35.0 2.0 1.4 2.0 1.5 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.5 2.5 1.5
37.5 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.2 1.5 2.3 1.5 2.5 1.4
40.0 1.9 1.4 2.0 1.4 2.1 1.4 2.1 1.5 2.2 1.5 2.3 1.4 2.4 1.4
43.0 1.8 1.4 1.9 1.4 2.0 1.4 2.1 1.5 2.1 1.4 2.2 1.4 2.3 1.4
20.0 2.7 1.9 2.8 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 2.0
22.5 2.7 1.9 2.8 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 2.0
25.0 2.7 1.9 2.8 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
27.5 2.7 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.0 2.0 3.2 1.9 3.4 1.9
25 30.0 2.6 1.8 2.7 1.9 2.8 1.9 2.9 2.0 3.0 1.9 3.2 1.9 3.3 1.9
(2.8) 32.5 2.6 1.8 2.6 1.9 2.8 1.8 2.9 1.9 2.9 1.9 3.1 1.9 3.3 1.9
35.0 2.5 1.8 2.6 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.0 1.9 3.2 1.8
37.5 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.8 1.9 3.0 1.8 3.1 1.8
40.0 2.4 1.7 2.5 1.8 2.6 1.8 2.7 1.9 2.8 1.8 2.9 1.8 3.1 1.8
43.0 2.4 1.7 2.4 1.8 2.6 1.7 2.6 1.8 2.7 1.8 2.8 1.8 3.0 1.7
20.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.6 2.8
22.5 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
27.5 3.4 2.6 3.5 2.7 3.7 2.7 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.6 3.4 2.7 3.6 2.6 3.7 2.8 3.8 2.8 4.1 2.7 4.3 2.7
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.8 3.8 2.7 4.0 2.7 4.2 2.6
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6
37.5 3.2 2.5 3.3 2.6 3.4 2.5 3.5 2.7 3.6 2.7 3.8 2.6 4.0 2.6
40.0 3.1 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.6 3.7 2.6 3.9 2.6
43.0 3.0 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.5 2.6 3.6 2.6 3.8 2.5
20.0 4.3 3.2 4.4 3.3 4.7 3.3 4.9 3.5 5.0 3.4 5.3 3.4 5.7 3.4
22.5 4.3 3.2 4.4 3.3 4.7 3.3 4.9 3.5 5.0 3.4 5.3 3.4 5.7 3.4
25.0 4.3 3.2 4.4 3.3 4.7 3.3 4.9 3.5 5.0 3.4 5.3 3.4 5.6 3.3
27.5 4.3 3.2 4.4 3.3 4.6 3.2 4.8 3.4 4.9 3.4 5.2 3.3 5.5 3.3
40 30.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.8 3.4 5.1 3.3 5.4 3.3
(4.5) 32.5 4.1 3.1 4.2 3.2 4.5 3.2 4.6 3.3 4.7 3.3 5.0 3.3 5.3 3.2
35.0 4.0 3.1 4.1 3.2 4.4 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.2
37.5 4.0 3.0 4.1 3.1 4.3 3.1 4.4 3.3 4.5 3.2 4.8 3.2 5.0 3.1
40.0 3.9 3.0 4.0 3.1 4.2 3.1 4.3 3.2 4.4 3.2 4.7 3.1 4.9 3.1
43.0 3.8 3.0 3.9 3.0 4.1 3.0 4.2 3.2 4.3 3.2 4.5 3.1 4.8 3.1
20.0 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.2 4.0 6.6 4.0 7.1 4.0
22.5 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.2 4.0 6.6 4.0 7.1 4.0
25.0 5.3 3.8 5.5 3.9 5.9 3.9 6.0 4.1 6.2 4.0 6.6 4.0 7.0 3.9
27.5 5.3 3.8 5.5 3.9 5.8 3.8 5.9 4.0 6.1 4.0 6.4 3.9 6.8 3.9
50 30.0 5.2 3.7 5.4 3.8 5.7 3.8 5.8 4.0 6.0 3.9 6.3 3.9 6.7 3.8
(5.6) 32.5 5.1 3.7 5.3 3.8 5.6 3.7 5.7 3.9 5.9 3.9 6.2 3.8 6.6 3.8
35.0 5.0 3.6 5.2 3.7 5.5 3.7 5.6 3.9 5.8 3.8 6.1 3.8 6.4 3.7
37.5 4.9 3.6 5.1 3.7 5.4 3.6 5.5 3.8 5.6 3.8 5.9 3.7 6.3 3.7
40.0 4.8 3.5 5.0 3.6 5.3 3.6 5.4 3.8 5.5 3.7 5.8 3.7 6.1 3.6
43.0 4.7 3.5 4.8 3.6 5.1 3.5 5.3 3.7 5.4 3.7 5.6 3.6 6.0 3.5
20.0 6.7 5.2 7.0 5.4 7.5 5.3 7.7 5.7 7.9 5.6 8.4 5.6 9.0 5.5
22.5 6.7 5.2 7.0 5.4 7.5 5.3 7.7 5.7 7.9 5.6 8.4 5.6 9.0 5.5
25.0 6.7 5.2 7.0 5.4 7.5 5.3 7.7 5.7 7.9 5.6 8.3 5.5 8.8 5.5
27.5 6.7 5.2 6.9 5.3 7.3 5.3 7.5 5.6 7.7 5.5 8.1 5.5 8.7 5.4
63 30.0 6.6 5.1 6.8 5.3 7.2 5.2 7.4 5.5 7.6 5.5 8.0 5.4 8.5 5.3
(7.1) 32.5 6.5 5.1 6.7 5.2 7.1 5.2 7.2 5.5 7.4 5.4 7.8 5.3 8.3 5.3
35.0 6.4 5.0 6.5 5.2 6.9 5.1 7.1 5.4 7.3 5.4 7.7 5.3 8.1 5.2
37.5 6.2 4.9 6.4 5.1 6.8 5.0 7.0 5.4 7.2 5.3 7.5 5.2 8.0 5.1
40.0 6.1 4.9 6.3 5.0 6.7 5.0 6.8 5.3 7.0 5.3 7.4 5.2 7.8 5.1
43.0 6.0 4.8 6.1 5.0 6.5 4.9 6.7 5.2 6.9 5.2 7.2 5.1 7.6 5.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 149


7. Cooling [Wall mounted]
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.6 7.6 11.0 7.9 11.8 7.8 12.1 8.2 12.5 8.2 13.2 8.1 14.2 8.0
22.5 10.6 7.6 11.0 7.9 11.8 7.8 12.1 8.2 12.5 8.2 13.2 8.1 14.2 8.0
25.0 10.6 7.6 11.0 7.9 11.8 7.8 12.1 8.2 12.4 8.1 13.1 8.0 13.9 7.9
27.5 10.6 7.6 10.9 7.8 11.6 7.7 11.9 8.1 12.2 8.0 12.9 7.9 13.7 7.8
100 30.0 10.4 7.5 10.7 7.7 11.3 7.6 11.6 8.0 12.0 7.9 12.6 7.8 13.4 7.7
(11.2) 32.5 10.2 7.4 10.5 7.6 11.1 7.5 11.4 7.9 11.7 7.9 12.4 7.7 13.1 7.6
35.0 10.0 7.3 10.3 7.5 10.9 7.4 11.2 7.8 11.5 7.8 12.1 7.6 12.8 7.5
37.5 9.8 7.2 10.1 7.4 10.7 7.3 11.0 7.7 11.3 7.7 11.9 7.5 12.6 7.4
40.0 9.6 7.1 9.9 7.3 10.5 7.2 10.8 7.6 11.1 7.6 11.6 7.4 12.3 7.3
43.0 9.4 7.0 9.7 7.2 10.2 7.1 10.5 7.5 10.8 7.5 11.3 7.3 12.0 7.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 150


7. Cooling [Wall mounted]
7-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.7 1.2 1.7 1.2 1.8 1.2 1.9 1.3 2.0 1.3 2.1 1.3 2.2 1.2
22.5 1.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 1.9 1.3 2.0 1.2 2.2 1.2
25.0 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.2
27.5 1.6 1.2 1.6 1.2 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.2
15 30.0 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2
(1.7) 32.5 1.5 1.1 1.6 1.1 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
35.0 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.9 1.2 2.0 1.2
37.5 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.8 1.2 1.9 1.1
40.0 1.5 1.1 1.5 1.1 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.1 1.9 1.1
43.0 1.4 1.1 1.4 1.1 1.5 1.1 1.6 1.1 1.6 1.1 1.7 1.1 1.8 1.1
20.0 2.1 1.5 2.2 1.6 2.4 1.6 2.5 1.6 2.5 1.6 2.7 1.6 2.9 1.6
22.5 2.1 1.5 2.2 1.5 2.3 1.5 2.4 1.6 2.5 1.6 2.6 1.6 2.8 1.6
25.0 2.1 1.5 2.2 1.5 2.3 1.5 2.4 1.6 2.4 1.6 2.6 1.6 2.8 1.5
27.5 2.1 1.5 2.1 1.5 2.3 1.5 2.3 1.6 2.4 1.6 2.5 1.5 2.7 1.5
20 30.0 2.0 1.5 2.1 1.5 2.2 1.5 2.3 1.6 2.4 1.5 2.5 1.5 2.6 1.5
(2.2) 32.5 2.0 1.4 2.0 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.4 1.5 2.6 1.5
35.0 2.0 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.5 2.5 1.5
37.5 1.9 1.4 2.0 1.4 2.1 1.4 2.1 1.5 2.2 1.5 2.3 1.5 2.5 1.4
40.0 1.9 1.4 1.9 1.4 2.0 1.4 2.1 1.5 2.2 1.5 2.3 1.4 2.4 1.4
43.0 1.9 1.4 1.9 1.4 2.0 1.4 2.0 1.4 2.1 1.4 2.2 1.4 2.4 1.4
20.0 2.7 1.9 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.0 3.6 2.0
22.5 2.7 1.9 2.8 1.9 3.0 1.9 3.1 2.0 3.2 2.0 3.4 2.0 3.6 2.0
25.0 2.7 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
27.5 2.6 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.2 1.9 3.4 1.9
25 30.0 2.6 1.8 2.6 1.9 2.8 1.9 2.9 2.0 3.0 1.9 3.2 1.9 3.4 1.9
(2.8) 32.5 2.5 1.8 2.6 1.8 2.8 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
35.0 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.0 1.9 3.2 1.8
37.5 2.5 1.8 2.5 1.8 2.6 1.8 2.7 1.9 2.8 1.9 3.0 1.8 3.2 1.8
40.0 2.4 1.7 2.4 1.8 2.6 1.7 2.7 1.8 2.8 1.8 2.9 1.8 3.1 1.8
43.0 2.4 1.7 2.4 1.7 2.5 1.7 2.6 1.8 2.7 1.8 2.8 1.8 3.0 1.8
20.0 3.5 2.7 3.6 2.7 3.9 2.7 4.0 2.9 4.2 2.9 4.4 2.9 4.7 2.8
22.5 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.9 4.1 2.9 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
27.5 3.4 2.6 3.5 2.7 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.8 4.4 2.7
32 30.0 3.3 2.6 3.4 2.6 3.6 2.6 3.7 2.8 3.8 2.8 4.1 2.7 4.3 2.7
(3.6) 32.5 3.3 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.2 2.7
35.0 3.2 2.5 3.3 2.6 3.5 2.5 3.6 2.7 3.7 2.7 3.9 2.7 4.2 2.6
37.5 3.2 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.8 2.6 4.1 2.6
40.0 3.1 2.5 3.1 2.5 3.3 2.5 3.4 2.7 3.5 2.6 3.8 2.6 4.0 2.6
43.0 3.0 2.4 3.0 2.5 3.2 2.4 3.3 2.6 3.4 2.6 3.7 2.6 3.9 2.5
20.0 4.4 3.2 4.5 3.3 4.9 3.3 5.0 3.5 5.2 3.5 5.5 3.5 5.8 3.4
22.5 4.4 3.2 4.5 3.3 4.8 3.3 4.9 3.5 5.1 3.5 5.4 3.4 5.7 3.4
25.0 4.3 3.2 4.4 3.3 4.7 3.3 4.9 3.5 5.0 3.4 5.3 3.4 5.6 3.3
27.5 4.2 3.2 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.2 3.4 5.5 3.3
40 30.0 4.1 3.1 4.2 3.2 4.5 3.2 4.7 3.4 4.8 3.4 5.1 3.3 5.4 3.3
(4.5) 32.5 4.1 3.1 4.2 3.2 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.3 5.3 3.2
35.0 4.0 3.1 4.1 3.1 4.3 3.1 4.5 3.3 4.6 3.3 4.9 3.2 5.2 3.2
37.5 3.9 3.0 4.0 3.1 4.2 3.1 4.4 3.3 4.5 3.2 4.8 3.2 5.1 3.2
40.0 3.9 3.0 3.9 3.0 4.2 3.0 4.3 3.2 4.4 3.2 4.7 3.2 5.0 3.1
43.0 3.8 3.0 3.8 3.0 4.0 3.0 4.2 3.2 4.3 3.2 4.6 3.1 4.8 3.1
20.0 5.4 3.8 5.6 4.0 6.1 4.0 6.3 4.2 6.5 4.2 6.9 4.1 7.3 4.0
22.5 5.4 3.8 5.6 3.9 6.0 3.9 6.2 4.1 6.3 4.1 6.7 4.0 7.1 4.0
25.0 5.3 3.8 5.5 3.9 5.8 3.9 6.0 4.1 6.2 4.0 6.6 4.0 7.0 3.9
27.5 5.3 3.7 5.4 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 3.9 6.9 3.9
50 30.0 5.2 3.7 5.3 3.8 5.6 3.7 5.8 4.0 6.0 3.9 6.4 3.9 6.7 3.8
(5.6) 32.5 5.1 3.7 5.2 3.7 5.5 3.7 5.7 3.9 5.9 3.9 6.2 3.8 6.6 3.8
35.0 5.0 3.6 5.1 3.7 5.4 3.6 5.6 3.9 5.7 3.8 6.1 3.8 6.5 3.7
37.5 4.9 3.6 5.0 3.6 5.3 3.6 5.5 3.8 5.6 3.8 6.0 3.7 6.3 3.7
40.0 4.8 3.5 4.9 3.6 5.2 3.5 5.3 3.7 5.5 3.7 5.8 3.7 6.2 3.6
43.0 4.7 3.5 4.7 3.5 5.0 3.5 5.2 3.7 5.4 3.7 5.7 3.6 6.0 3.6
20.0 6.9 5.3 7.1 5.4 7.7 5.4 7.9 5.8 8.2 5.7 8.7 5.7 9.2 5.6
22.5 6.9 5.3 7.1 5.4 7.6 5.4 7.8 5.7 8.0 5.7 8.5 5.6 9.1 5.5
25.0 6.8 5.2 7.0 5.4 7.4 5.3 7.7 5.7 7.9 5.6 8.4 5.6 8.9 5.5
27.5 6.7 5.2 6.8 5.3 7.3 5.3 7.5 5.6 7.7 5.6 8.2 5.5 8.7 5.4
63 30.0 6.5 5.1 6.7 5.2 7.1 5.2 7.4 5.5 7.6 5.5 8.1 5.4 8.5 5.3
(7.1) 32.5 6.4 5.0 6.6 5.2 7.0 5.1 7.2 5.5 7.4 5.4 7.9 5.4 8.4 5.3
35.0 6.3 5.0 6.4 5.1 6.8 5.1 7.1 5.4 7.3 5.4 7.7 5.3 8.2 5.2
37.5 6.2 4.9 6.3 5.0 6.7 5.0 6.9 5.3 7.1 5.3 7.6 5.2 8.0 5.2
40.0 6.1 4.9 6.2 5.0 6.6 4.9 6.8 5.3 7.0 5.3 7.4 5.2 7.8 5.1
43.0 6.0 4.8 6.0 4.9 6.4 4.9 6.6 5.2 6.8 5.2 7.2 5.1 7.6 5.0
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 151


7. Cooling [Wall mounted]
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.9 7.8 11.3 8.0 12.1 8.0 12.5 8.4 12.9 8.4 13.7 8.3 14.5 8.1
22.5 10.8 7.7 11.2 7.9 11.9 7.9 12.3 8.3 12.7 8.3 13.5 8.2 14.3 8.0
25.0 10.7 7.6 11.0 7.8 11.7 7.8 12.1 8.2 12.5 8.2 13.2 8.1 14.0 7.9
27.5 10.5 7.6 10.8 7.7 11.5 7.7 11.8 8.1 12.2 8.1 13.0 8.0 13.7 7.8
100 30.0 10.3 7.5 10.6 7.6 11.2 7.6 11.6 8.0 12.0 8.0 12.7 7.9 13.5 7.7
(11.2) 32.5 10.2 7.4 10.3 7.5 11.0 7.5 11.4 7.9 11.7 7.9 12.4 7.8 13.2 7.6
35.0 10.0 7.3 10.1 7.4 10.8 7.4 11.2 7.8 11.5 7.8 12.2 7.6 12.9 7.5
37.5 9.8 7.2 9.9 7.3 10.6 7.3 10.9 7.7 11.2 7.6 11.9 7.5 12.6 7.4
40.0 9.6 7.1 9.7 7.2 10.3 7.2 10.7 7.6 11.0 7.5 11.7 7.4 12.4 7.3
43.0 9.4 7.0 9.5 7.1 10.1 7.0 10.4 7.5 10.7 7.4 11.4 7.3 12.1 7.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 152


7. Cooling [Wall mounted]
7-3. Cooling capacity with PUHY-RP450-650YSJM
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.2
22.5 1.6 1.2 1.6 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.2
25.0 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 2.0 1.2 2.1 1.2
27.5 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 2.0 1.2 2.1 1.2
15 30.0 1.5 1.1 1.6 1.2 1.7 1.1 1.8 1.2 1.8 1.2 1.9 1.2 2.1 1.2
(1.7) 32.5 1.5 1.1 1.6 1.1 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
35.0 1.5 1.1 1.5 1.1 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
37.5 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
40.0 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.9 1.2 2.0 1.2
43.0 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.8 1.2 2.0 1.2
20.0 2.1 1.5 2.1 1.5 2.3 1.5 2.4 1.6 2.4 1.6 2.6 1.6 2.8 1.5
22.5 2.1 1.5 2.1 1.5 2.3 1.5 2.3 1.6 2.4 1.6 2.6 1.6 2.7 1.5
25.0 2.0 1.5 2.1 1.5 2.2 1.5 2.3 1.6 2.4 1.6 2.5 1.6 2.7 1.5
27.5 2.0 1.4 2.1 1.5 2.2 1.5 2.3 1.6 2.4 1.6 2.5 1.5 2.7 1.5
20 30.0 2.0 1.4 2.0 1.5 2.2 1.5 2.3 1.6 2.3 1.5 2.5 1.5 2.7 1.5
(2.2) 32.5 2.0 1.4 2.0 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.5 1.5 2.6 1.5
35.0 2.0 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.5 1.5 2.6 1.5
37.5 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.5 2.6 1.5
40.0 1.9 1.4 1.9 1.4 2.1 1.4 2.2 1.5 2.2 1.5 2.4 1.5 2.6 1.5
43.0 1.9 1.4 1.9 1.4 2.1 1.4 2.1 1.5 2.2 1.5 2.4 1.5 2.5 1.5
20.0 2.6 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
22.5 2.6 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
25.0 2.6 1.8 2.7 1.9 2.9 1.9 2.9 2.0 3.0 2.0 3.2 1.9 3.5 1.9
27.5 2.6 1.8 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 1.9 3.4 1.9
25 30.0 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.9 3.0 1.9 3.2 1.9 3.4 1.9
(2.8) 32.5 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.9 3.0 1.9 3.2 1.9 3.4 1.9
35.0 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
37.5 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
40.0 2.4 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
43.0 2.4 1.7 2.4 1.8 2.6 1.8 2.7 1.9 2.8 1.9 3.0 1.9 3.2 1.8
20.0 3.4 2.6 3.5 2.7 3.7 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.8
22.5 3.4 2.6 3.5 2.7 3.7 2.7 3.8 2.8 4.0 2.8 4.2 2.8 4.5 2.7
25.0 3.3 2.6 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.8 4.4 2.7
27.5 3.3 2.6 3.4 2.6 3.6 2.6 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.8 3.8 2.8 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.8 3.8 2.7 4.1 2.7 4.3 2.7
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.7 4.3 2.7
37.5 3.2 2.5 3.2 2.6 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.7
40.0 3.1 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.7 3.9 2.7 4.2 2.6
43.0 3.1 2.5 3.1 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.9 2.7 4.2 2.6
20.0 4.3 3.2 4.4 3.3 4.7 3.3 4.8 3.5 5.0 3.4 5.3 3.4 5.7 3.4
22.5 4.2 3.2 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.3 3.4 5.6 3.3
25.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.9 3.4 5.2 3.4 5.6 3.3
27.5 4.1 3.1 4.2 3.2 4.5 3.2 4.7 3.4 4.8 3.4 5.2 3.3 5.5 3.3
40 30.0 4.1 3.1 4.2 3.2 4.5 3.2 4.6 3.4 4.8 3.4 5.1 3.3 5.5 3.3
(4.5) 32.5 4.0 3.1 4.1 3.2 4.4 3.1 4.6 3.3 4.7 3.3 5.1 3.3 5.4 3.3
35.0 4.0 3.1 4.1 3.1 4.4 3.1 4.5 3.3 4.7 3.3 5.0 3.3 5.4 3.2
37.5 4.0 3.0 4.0 3.1 4.3 3.1 4.5 3.3 4.6 3.3 5.0 3.3 5.3 3.2
40.0 3.9 3.0 4.0 3.1 4.3 3.1 4.4 3.3 4.6 3.3 4.9 3.2 5.3 3.2
43.0 3.9 3.0 3.9 3.1 4.2 3.1 4.4 3.3 4.5 3.2 4.9 3.2 5.2 3.2
20.0 5.3 3.8 5.5 3.9 5.8 3.8 6.0 4.1 6.2 4.0 6.6 4.0 7.0 3.9
22.5 5.2 3.7 5.4 3.8 5.8 3.8 6.0 4.0 6.2 4.0 6.6 4.0 7.0 3.9
25.0 5.2 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 3.9 6.9 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.9 3.9
50 30.0 5.1 3.7 5.2 3.7 5.6 3.7 5.8 3.9 6.0 3.9 6.4 3.9 6.8 3.8
(5.6) 32.5 5.0 3.6 5.1 3.7 5.5 3.7 5.7 3.9 5.9 3.9 6.3 3.9 6.7 3.8
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.8 6.7 3.8
37.5 4.9 3.6 5.0 3.6 5.4 3.6 5.6 3.9 5.8 3.8 6.2 3.8 6.6 3.8
40.0 4.9 3.5 4.9 3.6 5.3 3.6 5.5 3.8 5.7 3.8 6.1 3.8 6.5 3.8
43.0 4.8 3.5 4.9 3.6 5.2 3.6 5.4 3.8 5.6 3.8 6.0 3.8 6.5 3.7
20.0 6.7 5.2 6.9 5.3 7.4 5.3 7.6 5.6 7.9 5.6 8.4 5.6 8.9 5.5
22.5 6.6 5.1 6.8 5.3 7.3 5.3 7.6 5.6 7.8 5.6 8.3 5.5 8.8 5.5
25.0 6.6 5.1 6.8 5.3 7.2 5.2 7.5 5.6 7.7 5.6 8.2 5.5 8.8 5.4
27.5 6.5 5.1 6.7 5.2 7.2 5.2 7.4 5.5 7.6 5.5 8.2 5.5 8.7 5.4
63 30.0 6.4 5.0 6.6 5.2 7.1 5.2 7.3 5.5 7.6 5.5 8.1 5.4 8.6 5.4
(7.1) 32.5 6.4 5.0 6.5 5.1 7.0 5.1 7.2 5.5 7.5 5.5 8.0 5.4 8.5 5.3
35.0 6.3 5.0 6.4 5.1 6.9 5.1 7.1 5.4 7.4 5.4 7.9 5.4 8.5 5.3
37.5 6.2 5.0 6.3 5.1 6.8 5.1 7.1 5.4 7.3 5.4 7.8 5.3 8.4 5.3
40.0 6.2 4.9 6.3 5.0 6.7 5.0 7.0 5.4 7.2 5.4 7.8 5.3 8.3 5.3
43.0 6.1 4.9 6.2 5.0 6.7 5.0 6.9 5.3 7.1 5.3 7.7 5.3 8.2 5.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 153


7. Cooling [Wall mounted]
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.6 7.6 10.9 7.8 11.7 7.8 12.0 8.2 12.4 8.2 13.2 8.1 14.1 8.0
22.5 10.5 7.5 10.8 7.7 11.5 7.7 11.9 8.1 12.3 8.1 13.1 8.0 13.9 7.9
25.0 10.4 7.5 10.6 7.7 11.4 7.6 11.8 8.1 12.2 8.0 13.0 8.0 13.8 7.9
27.5 10.3 7.4 10.5 7.6 11.3 7.6 11.7 8.0 12.1 8.0 12.9 7.9 13.7 7.8
100 30.0 10.2 7.4 10.4 7.5 11.2 7.5 11.5 8.0 11.9 7.9 12.7 7.9 13.6 7.8
(11.2) 32.5 10.1 7.3 10.3 7.5 11.0 7.5 11.4 7.9 11.8 7.9 12.6 7.8 13.5 7.7
35.0 9.9 7.3 10.1 7.4 10.9 7.4 11.2 7.8 11.7 7.8 12.5 7.8 13.3 7.7
37.5 9.8 7.2 10.0 7.4 10.8 7.4 11.2 7.8 11.6 7.8 12.4 7.7 13.2 7.6
40.0 9.7 7.2 9.9 7.3 10.6 7.3 11.0 7.7 11.4 7.7 12.2 7.7 13.1 7.6
43.0 9.6 7.1 9.7 7.2 10.5 7.2 10.9 7.7 11.3 7.7 12.1 7.6 12.9 7.5
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 154


7. Cooling [Wall mounted]
7-4. Cooling capacity with PUHY-RP700-800YSJM
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 2.0 1.3 2.1 1.3 2.2 1.2
22.5 1.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 1.9 1.3 2.0 1.2 2.2 1.2
25.0 1.6 1.1 1.6 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.2
27.5 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.2
15 30.0 1.5 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.1 1.2
(1.7) 32.5 1.5 1.1 1.6 1.1 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
35.0 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
37.5 1.4 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.8 1.2 1.9 1.1
40.0 1.4 1.1 1.5 1.1 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.1 1.9 1.1
43.0 1.4 1.1 1.4 1.1 1.5 1.1 1.6 1.1 1.6 1.1 1.8 1.1 1.9 1.1
20.0 2.1 1.5 2.2 1.6 2.4 1.5 2.4 1.6 2.5 1.6 2.7 1.6 2.9 1.6
22.5 2.1 1.5 2.2 1.5 2.3 1.5 2.4 1.6 2.5 1.6 2.6 1.6 2.8 1.6
25.0 2.1 1.5 2.1 1.5 2.3 1.5 2.4 1.6 2.4 1.6 2.6 1.6 2.8 1.6
27.5 2.0 1.5 2.1 1.5 2.2 1.5 2.3 1.6 2.4 1.6 2.6 1.6 2.7 1.5
20 30.0 2.0 1.4 2.0 1.5 2.2 1.5 2.3 1.6 2.4 1.5 2.5 1.5 2.7 1.5
(2.2) 32.5 1.9 1.4 2.0 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.5 1.5 2.6 1.5
35.0 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.5 2.6 1.5
37.5 1.9 1.4 1.9 1.4 2.1 1.4 2.1 1.5 2.2 1.5 2.4 1.5 2.5 1.5
40.0 1.8 1.4 1.9 1.4 2.0 1.4 2.1 1.5 2.2 1.5 2.3 1.5 2.5 1.4
43.0 1.8 1.3 1.8 1.4 2.0 1.4 2.1 1.5 2.1 1.5 2.3 1.4 2.4 1.4
20.0 2.7 1.9 2.8 2.0 3.0 1.9 3.1 2.1 3.2 2.0 3.4 2.0 3.7 2.0
22.5 2.7 1.9 2.8 1.9 3.0 1.9 3.1 2.0 3.2 2.0 3.4 2.0 3.6 2.0
25.0 2.6 1.8 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
27.5 2.6 1.8 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 1.9 3.5 1.9
25 30.0 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.9 3.0 1.9 3.2 1.9 3.4 1.9
(2.8) 32.5 2.5 1.8 2.6 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
35.0 2.4 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
37.5 2.4 1.7 2.5 1.8 2.6 1.8 2.7 1.9 2.8 1.9 3.0 1.9 3.2 1.8
40.0 2.3 1.7 2.4 1.8 2.6 1.7 2.7 1.9 2.8 1.8 3.0 1.8 3.1 1.8
43.0 2.3 1.7 2.4 1.7 2.5 1.7 2.6 1.8 2.7 1.8 2.9 1.8 3.1 1.8
20.0 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.9 4.1 2.9 4.4 2.9 4.7 2.8
22.5 3.4 2.6 3.5 2.7 3.8 2.7 3.9 2.9 4.1 2.9 4.3 2.8 4.6 2.8
25.0 3.4 2.6 3.5 2.7 3.7 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.8
27.5 3.3 2.6 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.8 4.5 2.7
32 30.0 3.2 2.5 3.4 2.6 3.6 2.6 3.7 2.8 3.9 2.8 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.3 2.7
35.0 3.1 2.5 3.2 2.6 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.6
37.5 3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.9 2.7 4.1 2.6
40.0 3.0 2.4 3.1 2.5 3.3 2.5 3.4 2.7 3.6 2.6 3.8 2.6 4.0 2.6
43.0 2.9 2.4 3.0 2.5 3.2 2.5 3.4 2.6 3.5 2.6 3.7 2.6 3.9 2.6
20.0 4.3 3.2 4.5 3.3 4.8 3.3 5.0 3.5 5.2 3.5 5.5 3.5 5.9 3.4
22.5 4.3 3.2 4.4 3.3 4.7 3.3 4.9 3.5 5.1 3.5 5.4 3.4 5.8 3.4
25.0 4.2 3.2 4.3 3.3 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.4 5.7 3.4
27.5 4.1 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.9 3.4 5.2 3.4 5.6 3.3
40 30.0 4.1 3.1 4.2 3.2 4.5 3.2 4.7 3.4 4.8 3.4 5.1 3.3 5.5 3.3
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.3 5.4 3.2
35.0 3.9 3.0 4.0 3.1 4.3 3.1 4.5 3.3 4.6 3.3 4.9 3.3 5.3 3.2
37.5 3.8 3.0 4.0 3.1 4.2 3.1 4.4 3.3 4.5 3.3 4.8 3.2 5.2 3.2
40.0 3.8 2.9 3.9 3.0 4.2 3.0 4.3 3.2 4.5 3.2 4.8 3.2 5.1 3.1
43.0 3.7 2.9 3.8 3.0 4.1 3.0 4.2 3.2 4.3 3.2 4.6 3.1 4.9 3.1
20.0 5.4 3.8 5.6 3.9 6.0 3.9 6.2 4.1 6.4 4.1 6.9 4.1 7.3 4.0
22.5 5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.1 6.3 4.1 6.7 4.0 7.2 4.0
25.0 5.2 3.7 5.4 3.8 5.8 3.8 6.0 4.0 6.2 4.0 6.6 4.0 7.0 3.9
27.5 5.1 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 3.9 6.9 3.9
50 30.0 5.0 3.6 5.2 3.7 5.6 3.7 5.8 4.0 6.0 3.9 6.4 3.9 6.8 3.8
(5.6) 32.5 5.0 3.6 5.1 3.7 5.5 3.7 5.7 3.9 5.9 3.9 6.3 3.9 6.7 3.8
35.0 4.9 3.5 5.0 3.6 5.4 3.6 5.6 3.9 5.8 3.8 6.2 3.8 6.5 3.8
37.5 4.8 3.5 4.9 3.6 5.3 3.6 5.5 3.8 5.7 3.8 6.0 3.8 6.4 3.7
40.0 4.7 3.5 4.8 3.6 5.2 3.5 5.4 3.8 5.5 3.7 5.9 3.7 6.3 3.7
43.0 4.6 3.4 4.7 3.5 5.1 3.5 5.2 3.7 5.4 3.7 5.8 3.7 6.1 3.6
20.0 6.9 5.2 7.1 5.4 7.6 5.4 7.9 5.8 8.2 5.7 8.7 5.7 9.3 5.6
22.5 6.7 5.2 7.0 5.4 7.5 5.4 7.8 5.7 8.0 5.7 8.6 5.6 9.1 5.5
25.0 6.6 5.1 6.9 5.3 7.4 5.3 7.6 5.6 7.9 5.6 8.4 5.6 8.9 5.5
27.5 6.5 5.1 6.7 5.3 7.2 5.2 7.5 5.6 7.7 5.6 8.3 5.5 8.8 5.4
63 30.0 6.4 5.0 6.6 5.2 7.1 5.2 7.3 5.5 7.6 5.5 8.1 5.4 8.6 5.4
(7.1) 32.5 6.3 5.0 6.5 5.1 7.0 5.1 7.2 5.5 7.5 5.4 7.9 5.4 8.5 5.3
35.0 6.2 4.9 6.4 5.1 6.8 5.1 7.1 5.4 7.3 5.4 7.8 5.3 8.3 5.3
37.5 6.1 4.9 6.2 5.0 6.7 5.0 6.9 5.3 7.2 5.3 7.6 5.3 8.1 5.2
40.0 5.9 4.8 6.1 5.0 6.6 4.9 6.8 5.3 7.0 5.3 7.5 5.2 8.0 5.2
43.0 5.8 4.7 6.0 4.9 6.4 4.9 6.6 5.2 6.9 5.2 7.3 5.2 7.8 5.1
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 155


7. Cooling [Wall mounted]
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.8 7.7 11.2 8.0 12.0 7.9 12.5 8.4 12.9 8.4 13.7 8.3 14.6 8.2
22.5 10.6 7.6 11.0 7.9 11.8 7.8 12.2 8.3 12.6 8.3 13.5 8.2 14.4 8.1
25.0 10.5 7.5 10.8 7.8 11.6 7.7 12.0 8.2 12.4 8.2 13.3 8.1 14.1 8.0
27.5 10.3 7.4 10.6 7.7 11.4 7.6 11.8 8.1 12.2 8.1 13.0 8.0 13.8 7.9
100 30.0 10.1 7.4 10.4 7.6 11.2 7.5 11.6 8.0 12.0 8.0 12.8 7.9 13.6 7.8
(11.2) 32.5 9.9 7.3 10.2 7.5 11.0 7.5 11.4 7.9 11.8 7.9 12.5 7.8 13.3 7.7
35.0 9.7 7.2 10.0 7.4 10.8 7.4 11.2 7.8 11.5 7.8 12.3 7.7 13.1 7.6
37.5 9.5 7.1 9.8 7.3 10.6 7.3 10.9 7.7 11.3 7.7 12.1 7.6 12.8 7.5
40.0 9.4 7.0 9.6 7.2 10.4 7.2 10.7 7.6 11.1 7.6 11.8 7.5 12.6 7.4
43.0 9.2 6.9 9.4 7.1 10.1 7.1 10.5 7.5 10.8 7.5 11.5 7.4 12.3 7.3
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 156


7. Cooling [Wall mounted]
7-5. Cooling capacity with PUHY-RP850-900YSJM
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.2
22.5 1.6 1.2 1.6 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.2
25.0 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 2.0 1.2 2.1 1.2
27.5 1.6 1.1 1.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 2.0 1.2 2.1 1.2
15 30.0 1.5 1.1 1.6 1.2 1.7 1.1 1.8 1.2 1.8 1.2 1.9 1.2 2.1 1.2
(1.7) 32.5 1.5 1.1 1.6 1.1 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
35.0 1.5 1.1 1.5 1.1 1.7 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
37.5 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.8 1.2 1.9 1.2 2.0 1.2
40.0 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.9 1.2 2.0 1.2
43.0 1.5 1.1 1.5 1.1 1.6 1.1 1.7 1.2 1.7 1.2 1.8 1.2 2.0 1.2
20.0 2.1 1.5 2.1 1.5 2.3 1.5 2.4 1.6 2.4 1.6 2.6 1.6 2.8 1.5
22.5 2.1 1.5 2.1 1.5 2.3 1.5 2.3 1.6 2.4 1.6 2.6 1.6 2.7 1.5
25.0 2.0 1.5 2.1 1.5 2.2 1.5 2.3 1.6 2.4 1.6 2.5 1.6 2.7 1.5
27.5 2.0 1.4 2.1 1.5 2.2 1.5 2.3 1.6 2.4 1.6 2.5 1.5 2.7 1.5
20 30.0 2.0 1.4 2.0 1.5 2.2 1.5 2.3 1.6 2.3 1.5 2.5 1.5 2.7 1.5
(2.2) 32.5 2.0 1.4 2.0 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.5 1.5 2.6 1.5
35.0 2.0 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.5 1.5 2.6 1.5
37.5 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.5 2.6 1.5
40.0 1.9 1.4 1.9 1.4 2.1 1.4 2.2 1.5 2.2 1.5 2.4 1.5 2.6 1.5
43.0 1.9 1.4 1.9 1.4 2.1 1.4 2.1 1.5 2.2 1.5 2.4 1.5 2.5 1.5
20.0 2.6 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
22.5 2.6 1.9 2.7 1.9 2.9 1.9 3.0 2.0 3.1 2.0 3.3 2.0 3.5 1.9
25.0 2.6 1.8 2.7 1.9 2.9 1.9 2.9 2.0 3.0 2.0 3.2 1.9 3.5 1.9
27.5 2.6 1.8 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 1.9 3.4 1.9
25 30.0 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.9 3.0 1.9 3.2 1.9 3.4 1.9
(2.8) 32.5 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.9 3.0 1.9 3.2 1.9 3.4 1.9
35.0 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
37.5 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
40.0 2.4 1.8 2.5 1.8 2.7 1.8 2.8 1.9 2.9 1.9 3.1 1.9 3.3 1.9
43.0 2.4 1.7 2.4 1.8 2.6 1.8 2.7 1.9 2.8 1.9 3.0 1.9 3.2 1.8
20.0 3.4 2.6 3.5 2.7 3.7 2.7 3.9 2.8 4.0 2.8 4.3 2.8 4.5 2.8
22.5 3.4 2.6 3.5 2.7 3.7 2.7 3.8 2.8 4.0 2.8 4.2 2.8 4.5 2.7
25.0 3.3 2.6 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.8 4.4 2.7
27.5 3.3 2.6 3.4 2.6 3.6 2.6 3.8 2.8 3.9 2.8 4.1 2.7 4.4 2.7
32 30.0 3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.8 3.8 2.8 4.1 2.7 4.4 2.7
(3.6) 32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.8 3.8 2.7 4.1 2.7 4.3 2.7
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.7 4.3 2.7
37.5 3.2 2.5 3.2 2.6 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.2 2.7
40.0 3.1 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.7 3.9 2.7 4.2 2.6
43.0 3.1 2.5 3.1 2.5 3.4 2.5 3.5 2.7 3.6 2.7 3.9 2.7 4.2 2.6
20.0 4.3 3.2 4.4 3.3 4.7 3.3 4.8 3.5 5.0 3.4 5.3 3.4 5.7 3.4
22.5 4.2 3.2 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.4 5.3 3.4 5.6 3.3
25.0 4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.4 4.9 3.4 5.2 3.4 5.6 3.3
27.5 4.1 3.1 4.2 3.2 4.5 3.2 4.7 3.4 4.8 3.4 5.2 3.3 5.5 3.3
40 30.0 4.1 3.1 4.2 3.2 4.5 3.2 4.6 3.4 4.8 3.4 5.1 3.3 5.5 3.3
(4.5) 32.5 4.0 3.1 4.1 3.2 4.4 3.1 4.6 3.3 4.7 3.3 5.1 3.3 5.4 3.3
35.0 4.0 3.1 4.1 3.1 4.4 3.1 4.5 3.3 4.7 3.3 5.0 3.3 5.4 3.2
37.5 4.0 3.0 4.0 3.1 4.3 3.1 4.5 3.3 4.6 3.3 5.0 3.3 5.3 3.2
40.0 3.9 3.0 4.0 3.1 4.3 3.1 4.4 3.3 4.6 3.3 4.9 3.2 5.3 3.2
43.0 3.9 3.0 3.9 3.1 4.2 3.1 4.4 3.3 4.5 3.2 4.9 3.2 5.2 3.2
20.0 5.3 3.8 5.5 3.9 5.8 3.8 6.0 4.1 6.2 4.0 6.6 4.0 7.0 3.9
22.5 5.2 3.7 5.4 3.8 5.8 3.8 6.0 4.0 6.2 4.0 6.6 4.0 7.0 3.9
25.0 5.2 3.7 5.3 3.8 5.7 3.8 5.9 4.0 6.1 4.0 6.5 3.9 6.9 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 3.9 6.9 3.9
50 30.0 5.1 3.7 5.2 3.7 5.6 3.7 5.8 3.9 6.0 3.9 6.4 3.9 6.8 3.8
(5.6) 32.5 5.0 3.6 5.1 3.7 5.5 3.7 5.7 3.9 5.9 3.9 6.3 3.9 6.7 3.8
35.0 5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.9 5.8 3.9 6.2 3.8 6.7 3.8
37.5 4.9 3.6 5.0 3.6 5.4 3.6 5.6 3.9 5.8 3.8 6.2 3.8 6.6 3.8
40.0 4.9 3.5 4.9 3.6 5.3 3.6 5.5 3.8 5.7 3.8 6.1 3.8 6.5 3.8
43.0 4.8 3.5 4.9 3.6 5.2 3.6 5.4 3.8 5.6 3.8 6.0 3.8 6.5 3.7
20.0 6.7 5.2 6.9 5.3 7.4 5.3 7.6 5.6 7.9 5.6 8.4 5.6 8.9 5.5
22.5 6.6 5.1 6.8 5.3 7.3 5.3 7.6 5.6 7.8 5.6 8.3 5.5 8.8 5.5
25.0 6.6 5.1 6.8 5.3 7.2 5.2 7.5 5.6 7.7 5.6 8.2 5.5 8.8 5.4
27.5 6.5 5.1 6.7 5.2 7.2 5.2 7.4 5.5 7.6 5.5 8.2 5.5 8.7 5.4
63 30.0 6.4 5.0 6.6 5.2 7.1 5.2 7.3 5.5 7.6 5.5 8.1 5.4 8.6 5.4
(7.1) 32.5 6.4 5.0 6.5 5.1 7.0 5.1 7.2 5.5 7.5 5.5 8.0 5.4 8.5 5.3
35.0 6.3 5.0 6.4 5.1 6.9 5.1 7.1 5.4 7.4 5.4 7.9 5.4 8.5 5.3
37.5 6.2 5.0 6.3 5.1 6.8 5.1 7.1 5.4 7.3 5.4 7.8 5.3 8.4 5.3
40.0 6.2 4.9 6.3 5.0 6.7 5.0 7.0 5.4 7.2 5.4 7.8 5.3 8.3 5.3
43.0 6.1 4.9 6.2 5.0 6.7 5.0 6.9 5.3 7.1 5.3 7.7 5.3 8.2 5.2
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 157


7. Cooling [Wall mounted]
PKFY-P-VBM-E,VHM-E,VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 10.6 7.6 10.9 7.8 11.7 7.8 12.0 8.2 12.4 8.2 13.2 8.1 14.1 8.0
22.5 10.5 7.5 10.8 7.7 11.5 7.7 11.9 8.1 12.3 8.1 13.1 8.0 13.9 7.9
25.0 10.4 7.5 10.6 7.7 11.4 7.6 11.8 8.1 12.2 8.0 13.0 8.0 13.8 7.9
27.5 10.3 7.4 10.5 7.6 11.3 7.6 11.7 8.0 12.1 8.0 12.9 7.9 13.7 7.8
100 30.0 10.2 7.4 10.4 7.5 11.2 7.5 11.5 8.0 11.9 7.9 12.7 7.9 13.6 7.8
(11.2) 32.5 10.1 7.3 10.3 7.5 11.0 7.5 11.4 7.9 11.8 7.9 12.6 7.8 13.5 7.7
35.0 9.9 7.3 10.1 7.4 10.9 7.4 11.2 7.8 11.7 7.8 12.5 7.8 13.3 7.7
37.5 9.8 7.2 10.0 7.4 10.8 7.4 11.2 7.8 11.6 7.8 12.4 7.7 13.2 7.6
40.0 9.7 7.2 9.9 7.3 10.6 7.3 11.0 7.7 11.4 7.7 12.2 7.7 13.1 7.6
43.0 9.6 7.1 9.7 7.2 10.5 7.2 10.9 7.7 11.3 7.7 12.1 7.6 12.9 7.5
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 158


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
8-1. Cooling capacity with PUHY,PURY-RP200-250YJM
8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]

PFFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.7 1.8
27.5 2.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.6 1.7
(2.2) 32.5 2.0 1.6 2.1 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.7 2.4 1.7 2.5 1.7
37.5 1.9 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.2 1.7 2.3 1.7 2.5 1.7
40.0 1.9 1.6 2.0 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7
43.0 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.7 2.1 1.7 2.2 1.7 2.3 1.6
20.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
22.5 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
25.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
27.5 2.7 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.0 2.1 3.2 2.1 3.4 2.1
25 30.0 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.3 2.0
(2.8) 32.5 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 2.9 2.1 3.1 2.0 3.3 2.0
35.0 2.5 1.9 2.6 2.0 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0
37.5 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.8 2.0 3.0 2.0 3.1 2.0
40.0 2.4 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 1.9
43.0 2.4 1.8 2.4 1.9 2.6 1.9 2.6 2.0 2.7 2.0 2.8 1.9 3.0 1.9
20.0 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.6 2.5
22.5 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.6 2.5
25.0 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.2 2.5 4.5 2.5
27.5 3.4 2.4 3.5 2.5 3.7 2.4 3.8 2.6 3.9 2.5 4.1 2.5 4.4 2.5
32 30.0 3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.3 2.4
(3.6) 32.5 3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.0 2.4 4.2 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.4 4.1 2.4
37.5 3.2 2.3 3.3 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3
40.0 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.7 2.3 3.9 2.3
43.0 3.0 2.2 3.1 2.3 3.3 2.3 3.4 2.4 3.5 2.4 3.6 2.3 3.8 2.3
20.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.2 5.7 3.1
22.5 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.2 5.7 3.1
25.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.1 5.6 3.1
27.5 4.3 3.0 4.4 3.1 4.6 3.0 4.8 3.2 4.9 3.1 5.2 3.1 5.5 3.0
40 30.0 4.2 2.9 4.3 3.0 4.6 3.0 4.7 3.1 4.8 3.1 5.1 3.0 5.4 3.0
(4.5) 32.5 4.1 2.9 4.2 3.0 4.5 2.9 4.6 3.1 4.7 3.1 5.0 3.0 5.3 3.0
35.0 4.0 2.9 4.1 2.9 4.4 2.9 4.5 3.0 4.6 3.0 4.9 3.0 5.2 2.9
37.5 4.0 2.8 4.1 2.9 4.3 2.9 4.4 3.0 4.5 3.0 4.8 2.9 5.0 2.9
40.0 3.9 2.8 4.0 2.9 4.2 2.8 4.3 3.0 4.4 2.9 4.7 2.9 4.9 2.8
43.0 3.8 2.7 3.9 2.8 4.1 2.8 4.2 2.9 4.3 2.9 4.5 2.8 4.8 2.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 159


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLEM-E,VLRM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.7 1.8
27.5 2.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.7 2.6 1.7
(2.2) 32.5 2.0 1.6 2.1 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.3 1.7 2.5 1.7
40.0 1.9 1.6 2.0 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.6
43.0 1.8 1.5 1.9 1.6 2.0 1.6 2.1 1.7 2.1 1.7 2.2 1.6 2.3 1.6
20.0 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
22.5 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
25.0 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
27.5 2.7 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.0 2.1 3.2 2.0 3.4 2.0
25 30.0 2.6 1.9 2.7 2.0 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.3 2.0
(2.8) 32.5 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 2.9 2.0 3.1 2.0 3.3 1.9
35.0 2.5 1.9 2.6 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.0 1.9 3.2 1.9
37.5 2.5 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.8 2.0 3.0 1.9 3.1 1.9
40.0 2.4 1.8 2.5 1.9 2.6 1.8 2.7 2.0 2.8 1.9 2.9 1.9 3.1 1.9
43.0 2.4 1.8 2.4 1.8 2.6 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.8
20.0 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.6 2.6
22.5 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.6 2.6
25.0 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.0 2.6 4.2 2.6 4.5 2.6
27.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.1 2.6 4.4 2.5
32 30.0 3.3 2.4 3.4 2.5 3.6 2.5 3.7 2.6 3.8 2.6 4.1 2.5 4.3 2.5
(3.6) 32.5 3.3 2.4 3.4 2.5 3.6 2.4 3.7 2.6 3.8 2.6 4.0 2.5 4.2 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.5 3.2 2.3 3.3 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.4
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.7 2.4 3.9 2.4
43.0 3.0 2.3 3.1 2.3 3.3 2.3 3.4 2.5 3.5 2.4 3.6 2.4 3.8 2.3
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.7 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.7 3.3
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.6 3.2
27.5 4.3 3.1 4.4 3.2 4.6 3.2 4.8 3.3 4.9 3.3 5.2 3.2 5.5 3.2
40 30.0 4.2 3.1 4.3 3.1 4.6 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.4 3.2
(4.5) 32.5 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.2 4.7 3.2 5.0 3.2 5.3 3.1
35.0 4.0 3.0 4.1 3.1 4.4 3.0 4.5 3.2 4.6 3.2 4.9 3.1 5.2 3.1
37.5 4.0 3.0 4.1 3.0 4.3 3.0 4.4 3.2 4.5 3.1 4.8 3.1 5.0 3.0
40.0 3.9 2.9 4.0 3.0 4.2 3.0 4.3 3.1 4.4 3.1 4.7 3.0 4.9 3.0
43.0 3.8 2.9 3.9 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.5 3.0 4.8 2.9
20.0 5.3 3.9 5.5 4.1 5.9 4.0 6.1 4.3 6.2 4.2 6.6 4.2 7.1 4.1
22.5 5.3 3.9 5.5 4.1 5.9 4.0 6.1 4.3 6.2 4.2 6.6 4.2 7.1 4.1
25.0 5.3 3.9 5.5 4.1 5.9 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
27.5 5.3 3.9 5.5 4.0 5.8 4.0 5.9 4.2 6.1 4.2 6.4 4.1 6.8 4.0
50 30.0 5.2 3.9 5.4 4.0 5.7 3.9 5.8 4.2 6.0 4.1 6.3 4.1 6.7 4.0
(5.6) 32.5 5.1 3.8 5.3 3.9 5.6 3.9 5.7 4.1 5.9 4.1 6.2 4.0 6.6 3.9
35.0 5.0 3.8 5.2 3.9 5.5 3.8 5.6 4.1 5.8 4.0 6.1 4.0 6.4 3.9
37.5 4.9 3.7 5.1 3.8 5.4 3.8 5.5 4.0 5.6 4.0 5.9 3.9 6.3 3.8
40.0 4.8 3.7 5.0 3.8 5.3 3.7 5.4 4.0 5.5 3.9 5.8 3.9 6.1 3.8
43.0 4.7 3.6 4.8 3.7 5.1 3.7 5.3 3.9 5.4 3.9 5.6 3.8 6.0 3.7
20.0 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.3 7.9 5.2 8.4 5.2 9.0 5.1
22.5 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.3 7.9 5.2 8.4 5.2 9.0 5.1
25.0 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.2 7.9 5.2 8.3 5.1 8.8 5.0
27.5 6.7 4.9 6.9 5.0 7.3 4.9 7.5 5.2 7.7 5.1 8.1 5.1 8.7 5.0
63 30.0 6.6 4.8 6.8 4.9 7.2 4.9 7.4 5.1 7.6 5.1 8.0 5.0 8.5 4.9
(7.1) 32.5 6.5 4.7 6.7 4.9 7.1 4.8 7.2 5.1 7.4 5.0 7.8 4.9 8.3 4.9
35.0 6.4 4.7 6.5 4.8 6.9 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.1 4.8
37.5 6.2 4.6 6.4 4.7 6.8 4.7 7.0 4.9 7.2 4.9 7.5 4.8 8.0 4.7
40.0 6.1 4.5 6.3 4.7 6.7 4.6 6.8 4.9 7.0 4.8 7.4 4.7 7.8 4.7
43.0 6.0 4.5 6.1 4.6 6.5 4.5 6.7 4.8 6.9 4.8 7.2 4.7 7.6 4.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 160


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLRMM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.7 1.8
27.5 2.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.7 2.6 1.7
(2.2) 32.5 2.0 1.6 2.1 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.3 1.7 2.5 1.7
40.0 1.9 1.6 2.0 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.6
43.0 1.8 1.5 1.9 1.6 2.0 1.6 2.1 1.7 2.1 1.7 2.2 1.6 2.3 1.6
20.0 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
22.5 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
25.0 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
27.5 2.7 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.0 2.1 3.2 2.0 3.4 2.0
25 30.0 2.6 1.9 2.7 2.0 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.3 2.0
(2.8) 32.5 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 2.9 2.0 3.1 2.0 3.3 1.9
35.0 2.5 1.9 2.6 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.0 1.9 3.2 1.9
37.5 2.5 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.8 2.0 3.0 1.9 3.1 1.9
40.0 2.4 1.8 2.5 1.9 2.6 1.8 2.7 2.0 2.8 1.9 2.9 1.9 3.1 1.9
43.0 2.4 1.8 2.4 1.8 2.6 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.8
20.0 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.6 2.6
22.5 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.6 2.6
25.0 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.0 2.6 4.2 2.6 4.5 2.6
27.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.1 2.6 4.4 2.5
32 30.0 3.3 2.4 3.4 2.5 3.6 2.5 3.7 2.6 3.8 2.6 4.1 2.5 4.3 2.5
(3.6) 32.5 3.3 2.4 3.4 2.5 3.6 2.4 3.7 2.6 3.8 2.6 4.0 2.5 4.2 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4
37.5 3.2 2.3 3.3 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.4
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.7 2.4 3.9 2.4
43.0 3.0 2.3 3.1 2.3 3.3 2.3 3.4 2.5 3.5 2.4 3.6 2.4 3.8 2.3
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.7 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.7 3.3
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.6 3.2
27.5 4.3 3.1 4.4 3.2 4.6 3.2 4.8 3.3 4.9 3.3 5.2 3.2 5.5 3.2
40 30.0 4.2 3.1 4.3 3.1 4.6 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.4 3.2
(4.5) 32.5 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.2 4.7 3.2 5.0 3.2 5.3 3.1
35.0 4.0 3.0 4.1 3.1 4.4 3.0 4.5 3.2 4.6 3.2 4.9 3.1 5.2 3.1
37.5 4.0 3.0 4.1 3.0 4.3 3.0 4.4 3.2 4.5 3.1 4.8 3.1 5.0 3.0
40.0 3.9 2.9 4.0 3.0 4.2 3.0 4.3 3.1 4.4 3.1 4.7 3.0 4.9 3.0
43.0 3.8 2.9 3.9 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.5 3.0 4.8 2.9
20.0 5.3 3.9 5.5 4.1 5.9 4.0 6.1 4.3 6.2 4.2 6.6 4.2 7.1 4.1
22.5 5.3 3.9 5.5 4.1 5.9 4.0 6.1 4.3 6.2 4.2 6.6 4.2 7.1 4.1
25.0 5.3 3.9 5.5 4.1 5.9 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
27.5 5.3 3.9 5.5 4.0 5.8 4.0 5.9 4.2 6.1 4.2 6.4 4.1 6.8 4.0
50 30.0 5.2 3.9 5.4 4.0 5.7 3.9 5.8 4.2 6.0 4.1 6.3 4.1 6.7 4.0
(5.6) 32.5 5.1 3.8 5.3 3.9 5.6 3.9 5.7 4.1 5.9 4.1 6.2 4.0 6.6 3.9
35.0 5.0 3.8 5.2 3.9 5.5 3.8 5.6 4.1 5.8 4.0 6.1 4.0 6.4 3.9
37.5 4.9 3.7 5.1 3.8 5.4 3.8 5.5 4.0 5.6 4.0 5.9 3.9 6.3 3.8
40.0 4.8 3.7 5.0 3.8 5.3 3.7 5.4 4.0 5.5 3.9 5.8 3.9 6.1 3.8
43.0 4.7 3.6 4.8 3.7 5.1 3.7 5.3 3.9 5.4 3.9 5.6 3.8 6.0 3.7
20.0 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.3 7.9 5.2 8.4 5.2 9.0 5.1
22.5 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.3 7.9 5.2 8.4 5.2 9.0 5.1
25.0 6.7 4.9 7.0 5.0 7.5 5.0 7.7 5.2 7.9 5.2 8.3 5.1 8.8 5.0
27.5 6.7 4.9 6.9 5.0 7.3 4.9 7.5 5.2 7.7 5.1 8.1 5.1 8.7 5.0
63 30.0 6.6 4.8 6.8 4.9 7.2 4.9 7.4 5.1 7.6 5.1 8.0 5.0 8.5 4.9
(7.1) 32.5 6.5 4.7 6.7 4.9 7.1 4.8 7.2 5.1 7.4 5.0 7.8 4.9 8.3 4.9
35.0 6.4 4.7 6.5 4.8 6.9 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.1 4.8
37.5 6.2 4.6 6.4 4.7 6.8 4.7 7.0 4.9 7.2 4.9 7.5 4.8 8.0 4.7
40.0 6.1 4.5 6.3 4.7 6.7 4.6 6.8 4.9 7.0 4.8 7.4 4.7 7.8 4.7
43.0 6.0 4.5 6.1 4.6 6.5 4.5 6.7 4.8 6.9 4.8 7.2 4.7 7.6 4.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 161


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
8-2. Cooling capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
PFFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.8 2.4 1.7 2.5 1.9 2.5 1.9 2.7 1.8 2.9 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
27.5 2.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
20 30.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.6 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.8 2.3 1.7 2.4 1.7 2.5 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.5 1.7
40.0 1.9 1.6 1.9 1.6 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7
43.0 1.9 1.6 1.9 1.6 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.7 2.4 1.6
20.0 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.2 3.6 2.1
22.5 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.1 3.6 2.1
25.0 2.7 2.0 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
27.5 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.1 3.4 2.1
25 30.0 2.6 2.0 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.0 2.0 3.2 2.0
37.5 2.5 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
40.0 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 1.9
43.0 2.4 1.8 2.4 1.9 2.5 1.9 2.6 2.0 2.7 2.0 2.8 1.9 3.0 1.9
20.0 3.5 2.5 3.6 2.5 3.9 2.5 4.0 2.7 4.2 2.7 4.4 2.6 4.7 2.6
22.5 3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.6 4.1 2.6 4.3 2.6 4.6 2.5
25.0 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
27.5 3.4 2.4 3.5 2.5 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.5 4.4 2.5
32 30.0 3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.3 2.4
(3.6) 32.5 3.3 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.2 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.3 3.6 2.5 3.7 2.5 3.9 2.4 4.2 2.4
37.5 3.2 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.8 2.4 4.1 2.3
40.0 3.1 2.3 3.1 2.3 3.3 2.3 3.4 2.4 3.5 2.4 3.8 2.4 4.0 2.3
43.0 3.0 2.2 3.0 2.2 3.2 2.2 3.3 2.4 3.4 2.3 3.7 2.3 3.9 2.3
20.0 4.4 3.0 4.5 3.1 4.9 3.1 5.0 3.3 5.2 3.3 5.5 3.2 5.8 3.2
22.5 4.4 3.0 4.5 3.1 4.8 3.1 4.9 3.3 5.1 3.2 5.4 3.2 5.7 3.1
25.0 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.0 3.2 5.3 3.1 5.6 3.1
27.5 4.2 3.0 4.3 3.0 4.6 3.0 4.8 3.2 4.9 3.1 5.2 3.1 5.5 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.1 3.1 5.4 3.0
(4.5) 32.5 4.1 2.9 4.2 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.0 3.0 5.3 3.0
35.0 4.0 2.9 4.1 2.9 4.3 2.9 4.5 3.0 4.6 3.0 4.9 3.0 5.2 2.9
37.5 3.9 2.8 4.0 2.9 4.2 2.8 4.4 3.0 4.5 3.0 4.8 2.9 5.1 2.9
40.0 3.9 2.8 3.9 2.8 4.2 2.8 4.3 2.9 4.4 2.9 4.7 2.9 5.0 2.8
43.0 3.8 2.7 3.8 2.8 4.0 2.7 4.2 2.9 4.3 2.9 4.6 2.8 4.8 2.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 162


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLEM-E,VLRM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.9 2.5 1.8 2.7 1.8 2.9 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
27.5 2.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.7 2.6 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.6 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.5 1.7
40.0 1.9 1.6 1.9 1.6 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.6
43.0 1.9 1.6 1.9 1.6 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.7 2.4 1.6
20.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.6 2.1
22.5 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.6 2.0
25.0 2.7 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
27.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.0 3.4 2.0
25 30.0 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 1.9 2.8 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.0 3.2 1.9
37.5 2.5 1.8 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
40.0 2.4 1.8 2.4 1.8 2.6 1.8 2.7 1.9 2.8 1.9 2.9 1.9 3.1 1.9
43.0 2.4 1.8 2.4 1.8 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.8
20.0 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.7 4.2 2.7 4.4 2.7 4.7 2.6
22.5 3.5 2.5 3.6 2.6 3.8 2.6 4.0 2.7 4.1 2.7 4.3 2.7 4.6 2.6
25.0 3.4 2.5 3.5 2.5 3.8 2.5 3.9 2.7 4.0 2.7 4.2 2.6 4.5 2.6
27.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.4 2.6
32 30.0 3.3 2.4 3.4 2.5 3.6 2.5 3.7 2.6 3.8 2.6 4.1 2.6 4.3 2.5
(3.6) 32.5 3.3 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.0 2.5 4.2 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.2 2.5
37.5 3.2 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.8 2.5 4.1 2.4
40.0 3.1 2.3 3.1 2.4 3.3 2.3 3.4 2.5 3.5 2.5 3.8 2.4 4.0 2.4
43.0 3.0 2.3 3.0 2.3 3.2 2.3 3.3 2.4 3.4 2.4 3.7 2.4 3.9 2.4
20.0 4.4 3.2 4.5 3.3 4.9 3.3 5.0 3.4 5.2 3.4 5.5 3.4 5.8 3.3
22.5 4.4 3.2 4.5 3.2 4.8 3.2 4.9 3.4 5.1 3.4 5.4 3.3 5.7 3.3
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.6 3.2
27.5 4.2 3.1 4.3 3.2 4.6 3.1 4.8 3.3 4.9 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.4 3.2
(4.5) 32.5 4.1 3.0 4.2 3.1 4.4 3.1 4.6 3.2 4.7 3.2 5.0 3.2 5.3 3.1
35.0 4.0 3.0 4.1 3.0 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.1 5.2 3.1
37.5 3.9 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.1 4.8 3.1 5.1 3.0
40.0 3.9 2.9 3.9 3.0 4.2 2.9 4.3 3.1 4.4 3.1 4.7 3.1 5.0 3.0
43.0 3.8 2.9 3.8 2.9 4.0 2.9 4.2 3.1 4.3 3.0 4.6 3.0 4.8 3.0
20.0 5.4 4.0 5.6 4.1 6.1 4.1 6.3 4.3 6.5 4.3 6.9 4.3 7.3 4.2
22.5 5.4 4.0 5.6 4.1 6.0 4.1 6.2 4.3 6.3 4.3 6.7 4.2 7.1 4.2
25.0 5.3 3.9 5.5 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
27.5 5.3 3.9 5.4 4.0 5.7 4.0 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
50 30.0 5.2 3.9 5.3 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.7 4.0
(5.6) 32.5 5.1 3.8 5.2 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.2 4.0 6.6 4.0
35.0 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.7 4.0 6.1 4.0 6.5 3.9
37.5 4.9 3.7 5.0 3.8 5.3 3.8 5.5 4.0 5.6 4.0 6.0 3.9 6.3 3.9
40.0 4.8 3.7 4.9 3.7 5.2 3.7 5.3 3.9 5.5 3.9 5.8 3.9 6.2 3.8
43.0 4.7 3.6 4.7 3.7 5.0 3.7 5.2 3.9 5.4 3.9 5.7 3.8 6.0 3.8
20.0 6.9 4.9 7.1 5.1 7.7 5.1 7.9 5.4 8.2 5.3 8.7 5.3 9.2 5.2
22.5 6.9 4.9 7.1 5.1 7.6 5.0 7.8 5.3 8.0 5.3 8.5 5.2 9.1 5.1
25.0 6.8 4.9 7.0 5.0 7.4 5.0 7.7 5.2 7.9 5.2 8.4 5.1 8.9 5.1
27.5 6.7 4.8 6.8 4.9 7.3 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.7 5.0
63 30.0 6.5 4.8 6.7 4.9 7.1 4.8 7.4 5.1 7.6 5.1 8.1 5.0 8.5 4.9
(7.1) 32.5 6.4 4.7 6.6 4.8 7.0 4.8 7.2 5.0 7.4 5.0 7.9 5.0 8.4 4.9
35.0 6.3 4.7 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.2 4.8
37.5 6.2 4.6 6.3 4.7 6.7 4.6 6.9 4.9 7.1 4.9 7.6 4.8 8.0 4.7
40.0 6.1 4.5 6.2 4.6 6.6 4.6 6.8 4.8 7.0 4.8 7.4 4.8 7.8 4.7
43.0 6.0 4.5 6.0 4.5 6.4 4.5 6.6 4.8 6.8 4.7 7.2 4.7 7.6 4.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 163


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLRMM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.9 2.5 1.8 2.7 1.8 2.9 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
27.5 2.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.7 2.6 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.6 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.5 1.7
40.0 1.9 1.6 1.9 1.6 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.6
43.0 1.9 1.6 1.9 1.6 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.7 2.4 1.6
20.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.6 2.1
22.5 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.6 2.0
25.0 2.7 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
27.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.0 3.4 2.0
25 30.0 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 1.9 2.8 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.0 2.0 3.2 1.9
37.5 2.5 1.8 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
40.0 2.4 1.8 2.4 1.8 2.6 1.8 2.7 1.9 2.8 1.9 2.9 1.9 3.1 1.9
43.0 2.4 1.8 2.4 1.8 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.8
20.0 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.7 4.2 2.7 4.4 2.7 4.7 2.6
22.5 3.5 2.5 3.6 2.6 3.8 2.6 4.0 2.7 4.1 2.7 4.3 2.7 4.6 2.6
25.0 3.4 2.5 3.5 2.5 3.8 2.5 3.9 2.7 4.0 2.7 4.2 2.6 4.5 2.6
27.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.4 2.6
32 30.0 3.3 2.4 3.4 2.5 3.6 2.5 3.7 2.6 3.8 2.6 4.1 2.6 4.3 2.5
(3.6) 32.5 3.3 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.0 2.5 4.2 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.2 2.5
37.5 3.2 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.8 2.5 4.1 2.4
40.0 3.1 2.3 3.1 2.4 3.3 2.3 3.4 2.5 3.5 2.5 3.8 2.4 4.0 2.4
43.0 3.0 2.3 3.0 2.3 3.2 2.3 3.3 2.4 3.4 2.4 3.7 2.4 3.9 2.4
20.0 4.4 3.2 4.5 3.3 4.9 3.3 5.0 3.4 5.2 3.4 5.5 3.4 5.8 3.3
22.5 4.4 3.2 4.5 3.2 4.8 3.2 4.9 3.4 5.1 3.4 5.4 3.3 5.7 3.3
25.0 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.3 5.3 3.3 5.6 3.2
27.5 4.2 3.1 4.3 3.2 4.6 3.1 4.8 3.3 4.9 3.3 5.2 3.3 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.4 3.2
(4.5) 32.5 4.1 3.0 4.2 3.1 4.4 3.1 4.6 3.2 4.7 3.2 5.0 3.2 5.3 3.1
35.0 4.0 3.0 4.1 3.0 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.1 5.2 3.1
37.5 3.9 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.1 4.8 3.1 5.1 3.0
40.0 3.9 2.9 3.9 3.0 4.2 2.9 4.3 3.1 4.4 3.1 4.7 3.1 5.0 3.0
43.0 3.8 2.9 3.8 2.9 4.0 2.9 4.2 3.1 4.3 3.0 4.6 3.0 4.8 3.0
20.0 5.4 4.0 5.6 4.1 6.1 4.1 6.3 4.3 6.5 4.3 6.9 4.3 7.3 4.2
22.5 5.4 4.0 5.6 4.1 6.0 4.1 6.2 4.3 6.3 4.3 6.7 4.2 7.1 4.2
25.0 5.3 3.9 5.5 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
27.5 5.3 3.9 5.4 4.0 5.7 4.0 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
50 30.0 5.2 3.9 5.3 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.7 4.0
(5.6) 32.5 5.1 3.8 5.2 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.2 4.0 6.6 4.0
35.0 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.7 4.0 6.1 4.0 6.5 3.9
37.5 4.9 3.7 5.0 3.8 5.3 3.8 5.5 4.0 5.6 4.0 6.0 3.9 6.3 3.9
40.0 4.8 3.7 4.9 3.7 5.2 3.7 5.3 3.9 5.5 3.9 5.8 3.9 6.2 3.8
43.0 4.7 3.6 4.7 3.7 5.0 3.7 5.2 3.9 5.4 3.9 5.7 3.8 6.0 3.8
20.0 6.9 4.9 7.1 5.1 7.7 5.1 7.9 5.4 8.2 5.3 8.7 5.3 9.2 5.2
22.5 6.9 4.9 7.1 5.1 7.6 5.0 7.8 5.3 8.0 5.3 8.5 5.2 9.1 5.1
25.0 6.8 4.9 7.0 5.0 7.4 5.0 7.7 5.2 7.9 5.2 8.4 5.1 8.9 5.1
27.5 6.7 4.8 6.8 4.9 7.3 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.7 5.0
63 30.0 6.5 4.8 6.7 4.9 7.1 4.8 7.4 5.1 7.6 5.1 8.1 5.0 8.5 4.9
(7.1) 32.5 6.4 4.7 6.6 4.8 7.0 4.8 7.2 5.0 7.4 5.0 7.9 5.0 8.4 4.9
35.0 6.3 4.7 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.2 4.8
37.5 6.2 4.6 6.3 4.7 6.7 4.6 6.9 4.9 7.1 4.9 7.6 4.8 8.0 4.7
40.0 6.1 4.5 6.2 4.6 6.6 4.6 6.8 4.8 7.0 4.8 7.4 4.8 7.8 4.7
43.0 6.0 4.5 6.0 4.5 6.4 4.5 6.6 4.8 6.8 4.7 7.2 4.7 7.6 4.6
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 164


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
8-3. Cooling capacity with PUHY-RP450-650YSJM
PFFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
25.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.7 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.7
35.0 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
40.0 1.9 1.6 1.9 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.4 1.7 2.6 1.7
43.0 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
20.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
22.5 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
25.0 2.6 2.0 2.7 2.0 2.9 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.5 2.1
27.5 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.1
25 30.0 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
37.5 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
40.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
43.0 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
20.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.5 2.5
22.5 3.4 2.4 3.5 2.5 3.7 2.4 3.8 2.6 4.0 2.6 4.2 2.5 4.5 2.5
25.0 3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.5 4.2 2.5 4.4 2.5
27.5 3.3 2.4 3.4 2.4 3.6 2.4 3.8 2.5 3.9 2.5 4.1 2.5 4.4 2.5
32 30.0 3.3 2.3 3.3 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.4 2.5
(3.6) 32.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.3 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.3 3.6 2.5 3.8 2.5 4.0 2.5 4.3 2.4
37.5 3.2 2.3 3.2 2.3 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.4 4.2 2.4
40.0 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.7 2.4 3.9 2.4 4.2 2.4
43.0 3.1 2.3 3.1 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.9 2.4 4.2 2.4
20.0 4.3 3.0 4.4 3.1 4.7 3.0 4.8 3.2 5.0 3.2 5.3 3.2 5.7 3.1
22.5 4.2 3.0 4.3 3.0 4.6 3.0 4.8 3.2 4.9 3.2 5.3 3.1 5.6 3.1
25.0 4.2 2.9 4.3 3.0 4.6 3.0 4.7 3.2 4.9 3.1 5.2 3.1 5.6 3.1
27.5 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.2 3.1 5.5 3.1
40 30.0 4.1 2.9 4.2 2.9 4.5 2.9 4.6 3.1 4.8 3.1 5.1 3.1 5.5 3.0
(4.5) 32.5 4.0 2.9 4.1 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.1 3.0 5.4 3.0
35.0 4.0 2.8 4.1 2.9 4.4 2.9 4.5 3.0 4.7 3.0 5.0 3.0 5.4 3.0
37.5 4.0 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.6 3.0 5.0 3.0 5.3 3.0
40.0 3.9 2.8 4.0 2.8 4.3 2.8 4.4 3.0 4.6 3.0 4.9 3.0 5.3 3.0
43.0 3.9 2.8 3.9 2.8 4.2 2.8 4.4 3.0 4.5 3.0 4.9 3.0 5.2 2.9
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 165


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLEM-E,VLRM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
25.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.7 2.7 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.5 1.7 2.6 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.6 1.7
40.0 1.9 1.6 1.9 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.4 1.7 2.6 1.7
43.0 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
20.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
22.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
25.0 2.6 1.9 2.7 2.0 2.9 1.9 2.9 2.1 3.0 2.1 3.2 2.0 3.5 2.0
27.5 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
25 30.0 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
37.5 2.5 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
40.0 2.4 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 1.9
43.0 2.4 1.8 2.4 1.8 2.6 1.8 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
20.0 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.5 2.6
22.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.6
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.4 2.6
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.8 2.6 3.9 2.6 4.1 2.6 4.4 2.5
32 30.0 3.3 2.4 3.3 2.5 3.6 2.4 3.7 2.6 3.8 2.6 4.1 2.6 4.4 2.5
(3.6) 32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.1 2.5 4.3 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.6 4.0 2.5 4.3 2.5
37.5 3.2 2.3 3.2 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.5
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.5 4.2 2.5
43.0 3.1 2.3 3.1 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.9 2.5 4.2 2.5
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.3 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.1 4.8 3.3 4.9 3.3 5.3 3.3 5.6 3.2
25.0 4.2 3.1 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.2 5.1 3.2 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.2 4.7 3.2 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.0 4.4 3.0 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.1
37.5 4.0 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.1
40.0 3.9 2.9 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.1 5.3 3.1
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.1 4.5 3.1 4.9 3.1 5.2 3.1
20.0 5.3 3.9 5.5 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
22.5 5.2 3.9 5.4 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
25.0 5.2 3.9 5.3 4.0 5.7 3.9 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
27.5 5.1 3.8 5.3 3.9 5.6 3.9 5.8 4.2 6.0 4.1 6.4 4.1 6.9 4.1
50 30.0 5.1 3.8 5.2 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.8 4.0
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.3 4.1 6.7 4.0
35.0 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.8 4.1 6.2 4.0 6.7 4.0
37.5 4.9 3.7 5.0 3.8 5.4 3.8 5.6 4.1 5.8 4.0 6.2 4.0 6.6 4.0
40.0 4.9 3.7 4.9 3.8 5.3 3.8 5.5 4.0 5.7 4.0 6.1 4.0 6.5 3.9
43.0 4.8 3.7 4.9 3.7 5.2 3.7 5.4 4.0 5.6 4.0 6.0 4.0 6.5 3.9
20.0 6.7 4.8 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.1 8.9 5.1
22.5 6.6 4.8 6.8 4.9 7.3 4.9 7.6 5.2 7.8 5.2 8.3 5.1 8.8 5.0
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.8 5.0
27.5 6.5 4.7 6.7 4.9 7.2 4.8 7.4 5.1 7.6 5.1 8.2 5.1 8.7 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.0 8.0 5.0 8.5 4.9
35.0 6.3 4.6 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 7.9 5.0 8.5 4.9
37.5 6.2 4.6 6.3 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 4.9 7.2 4.9 7.8 4.9 8.3 4.9
43.0 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.1 4.9 7.7 4.9 8.2 4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 166


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLRMM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
25.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.7 2.7 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.5 1.7 2.6 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.6 1.7
40.0 1.9 1.6 1.9 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.4 1.7 2.6 1.7
43.0 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
20.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
22.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
25.0 2.6 1.9 2.7 2.0 2.9 1.9 2.9 2.1 3.0 2.1 3.2 2.0 3.5 2.0
27.5 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
25 30.0 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
37.5 2.5 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
40.0 2.4 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 1.9
43.0 2.4 1.8 2.4 1.8 2.6 1.8 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
20.0 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.5 2.6
22.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.6
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.4 2.6
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.8 2.6 3.9 2.6 4.1 2.6 4.4 2.5
32 30.0 3.3 2.4 3.3 2.5 3.6 2.4 3.7 2.6 3.8 2.6 4.1 2.6 4.4 2.5
(3.6) 32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.1 2.5 4.3 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.6 4.0 2.5 4.3 2.5
37.5 3.2 2.3 3.2 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.5
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.5 4.2 2.5
43.0 3.1 2.3 3.1 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.9 2.5 4.2 2.5
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.3 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.1 4.8 3.3 4.9 3.3 5.3 3.3 5.6 3.2
25.0 4.2 3.1 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.2 5.1 3.2 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.2 4.7 3.2 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.0 4.4 3.0 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.1
37.5 4.0 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.1
40.0 3.9 2.9 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.1 5.3 3.1
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.1 4.5 3.1 4.9 3.1 5.2 3.1
20.0 5.3 3.9 5.5 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
22.5 5.2 3.9 5.4 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
25.0 5.2 3.9 5.3 4.0 5.7 3.9 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
27.5 5.1 3.8 5.3 3.9 5.6 3.9 5.8 4.2 6.0 4.1 6.4 4.1 6.9 4.1
50 30.0 5.1 3.8 5.2 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.8 4.0
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.3 4.1 6.7 4.0
35.0 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.8 4.1 6.2 4.0 6.7 4.0
37.5 4.9 3.7 5.0 3.8 5.4 3.8 5.6 4.1 5.8 4.0 6.2 4.0 6.6 4.0
40.0 4.9 3.7 4.9 3.8 5.3 3.8 5.5 4.0 5.7 4.0 6.1 4.0 6.5 3.9
43.0 4.8 3.7 4.9 3.7 5.2 3.7 5.4 4.0 5.6 4.0 6.0 4.0 6.5 3.9
20.0 6.7 4.8 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.1 8.9 5.1
22.5 6.6 4.8 6.8 4.9 7.3 4.9 7.6 5.2 7.8 5.2 8.3 5.1 8.8 5.0
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.8 5.0
27.5 6.5 4.7 6.7 4.9 7.2 4.8 7.4 5.1 7.6 5.1 8.2 5.1 8.7 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.0 8.0 5.0 8.5 4.9
35.0 6.3 4.6 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 7.9 5.0 8.5 4.9
37.5 6.2 4.6 6.3 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 4.9 7.2 4.9 7.8 4.9 8.3 4.9
43.0 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.1 4.9 7.7 4.9 8.2 4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 167


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
8-4. Cooling capacity with PUHY-RP700-800YSJM
PFFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.4 1.7 2.4 1.9 2.5 1.9 2.7 1.8 2.9 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
(2.2) 32.5 1.9 1.6 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.8 2.3 1.7 2.4 1.7 2.6 1.7
37.5 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
40.0 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.5 1.7
43.0 1.8 1.5 1.8 1.6 2.0 1.6 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.7
20.0 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.2 3.7 2.1
22.5 2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.2 3.2 2.2 3.4 2.1 3.6 2.1
25.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
27.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
25 30.0 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.1 2.9 2.1 3.1 2.1 3.3 2.0
35.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.1 2.0 3.3 2.0
37.5 2.4 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
40.0 2.3 1.8 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.0
43.0 2.3 1.8 2.4 1.9 2.5 1.9 2.6 2.0 2.7 2.0 2.9 2.0 3.1 1.9
20.0 3.5 2.5 3.6 2.5 3.9 2.5 4.0 2.7 4.1 2.6 4.4 2.6 4.7 2.6
22.5 3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.1 2.6 4.3 2.6 4.6 2.6
25.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.5 2.5
27.5 3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.5 4.5 2.5
32 30.0 3.2 2.3 3.4 2.4 3.6 2.4 3.7 2.5 3.9 2.5 4.1 2.5 4.4 2.5
(3.6) 32.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.3 2.4
35.0 3.1 2.3 3.2 2.3 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.4 4.2 2.4
37.5 3.1 2.2 3.2 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.9 2.4 4.1 2.4
40.0 3.0 2.2 3.1 2.3 3.3 2.3 3.4 2.4 3.6 2.4 3.8 2.4 4.0 2.3
43.0 2.9 2.2 3.0 2.2 3.2 2.2 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3
20.0 4.3 3.0 4.5 3.1 4.8 3.1 5.0 3.3 5.2 3.3 5.5 3.2 5.9 3.2
22.5 4.3 3.0 4.4 3.1 4.7 3.1 4.9 3.2 5.1 3.2 5.4 3.2 5.8 3.2
25.0 4.2 3.0 4.3 3.0 4.7 3.0 4.8 3.2 5.0 3.2 5.3 3.2 5.7 3.1
27.5 4.1 2.9 4.3 3.0 4.6 3.0 4.7 3.2 4.9 3.1 5.2 3.1 5.6 3.1
40 30.0 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.1 3.1 5.5 3.0
(4.5) 32.5 4.0 2.8 4.1 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.0 3.0 5.4 3.0
35.0 3.9 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.6 3.0 4.9 3.0 5.3 3.0
37.5 3.8 2.8 4.0 2.8 4.2 2.8 4.4 3.0 4.5 3.0 4.8 3.0 5.2 2.9
40.0 3.8 2.7 3.9 2.8 4.2 2.8 4.3 3.0 4.5 2.9 4.8 2.9 5.1 2.9
43.0 3.7 2.7 3.8 2.8 4.1 2.7 4.2 2.9 4.3 2.9 4.6 2.9 4.9 2.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 168


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLEM-E,VLRM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.4 1.7 2.4 1.8 2.5 1.8 2.7 1.8 2.9 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.6 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.7
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
(2.2) 32.5 1.9 1.6 2.0 1.6 2.2 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.6 1.7
37.5 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
40.0 1.8 1.5 1.9 1.6 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.5 1.7
43.0 1.8 1.5 1.8 1.6 2.0 1.6 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.6
20.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.7 2.1
22.5 2.7 1.9 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.6 2.1
25.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
27.5 2.6 1.9 2.7 2.0 2.9 1.9 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
25 30.0 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.8 2.6 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
35.0 2.4 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 1.9
37.5 2.4 1.8 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
40.0 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.9
43.0 2.3 1.8 2.4 1.8 2.5 1.8 2.6 1.9 2.7 1.9 2.9 1.9 3.1 1.9
20.0 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.7 4.1 2.7 4.4 2.7 4.7 2.7
22.5 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.1 2.7 4.3 2.7 4.6 2.6
25.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.5 2.6
27.5 3.3 2.4 3.4 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.5 2.6
32 30.0 3.2 2.4 3.4 2.5 3.6 2.5 3.7 2.6 3.9 2.6 4.1 2.6 4.4 2.5
(3.6) 32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.0 2.5 4.3 2.5
35.0 3.1 2.3 3.2 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.5
37.5 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.9 2.5 4.1 2.4
40.0 3.0 2.3 3.1 2.3 3.3 2.3 3.4 2.5 3.6 2.5 3.8 2.4 4.0 2.4
43.0 2.9 2.2 3.0 2.3 3.2 2.3 3.4 2.4 3.5 2.4 3.7 2.4 3.9 2.4
20.0 4.3 3.1 4.5 3.2 4.8 3.2 5.0 3.4 5.2 3.4 5.5 3.4 5.9 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.1 3.4 5.4 3.3 5.8 3.3
25.0 4.2 3.1 4.3 3.2 4.7 3.2 4.8 3.3 5.0 3.3 5.3 3.3 5.7 3.3
27.5 4.1 3.0 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.0 4.6 3.2 4.7 3.2 5.0 3.2 5.4 3.1
35.0 3.9 2.9 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.3 3.1
37.5 3.8 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.1 4.8 3.1 5.2 3.1
40.0 3.8 2.9 3.9 2.9 4.2 2.9 4.3 3.1 4.5 3.1 4.8 3.1 5.1 3.0
43.0 3.7 2.8 3.8 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.6 3.0 4.9 3.0
20.0 5.4 4.0 5.6 4.1 6.0 4.1 6.2 4.3 6.4 4.3 6.9 4.3 7.3 4.2
22.5 5.3 3.9 5.5 4.1 5.9 4.0 6.1 4.3 6.3 4.3 6.7 4.2 7.2 4.2
25.0 5.2 3.9 5.4 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
27.5 5.1 3.8 5.3 4.0 5.7 3.9 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
50 30.0 5.0 3.8 5.2 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.8 4.0
(5.6) 32.5 5.0 3.7 5.1 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.3 4.0 6.7 4.0
35.0 4.9 3.7 5.0 3.8 5.4 3.8 5.6 4.1 5.8 4.0 6.2 4.0 6.5 3.9
37.5 4.8 3.7 4.9 3.8 5.3 3.8 5.5 4.0 5.7 4.0 6.0 3.9 6.4 3.9
40.0 4.7 3.6 4.8 3.7 5.2 3.7 5.4 4.0 5.5 3.9 5.9 3.9 6.3 3.9
43.0 4.6 3.6 4.7 3.7 5.1 3.7 5.2 3.9 5.4 3.9 5.8 3.9 6.1 3.8
20.0 6.9 4.9 7.1 5.1 7.6 5.1 7.9 5.3 8.2 5.3 8.7 5.3 9.3 5.2
22.5 6.7 4.9 7.0 5.0 7.5 5.0 7.8 5.3 8.0 5.3 8.6 5.2 9.1 5.1
25.0 6.6 4.8 6.9 5.0 7.4 4.9 7.6 5.2 7.9 5.2 8.4 5.2 8.9 5.1
27.5 6.5 4.7 6.7 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.3 5.1 8.8 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.3 4.6 6.5 4.8 7.0 4.8 7.2 5.0 7.5 5.0 7.9 5.0 8.5 4.9
35.0 6.2 4.6 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.3 4.8
37.5 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.2 4.9 7.6 4.9 8.1 4.8
40.0 5.9 4.5 6.1 4.6 6.6 4.6 6.8 4.9 7.0 4.8 7.5 4.8 8.0 4.7
43.0 5.8 4.4 6.0 4.5 6.4 4.5 6.6 4.8 6.9 4.8 7.3 4.7 7.8 4.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 169


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLRMM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.2 1.7 2.4 1.7 2.4 1.8 2.5 1.8 2.7 1.8 2.9 1.8
22.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.8
25.0 2.1 1.6 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.7
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
(2.2) 32.5 1.9 1.6 2.0 1.6 2.2 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.6 1.7
37.5 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
40.0 1.8 1.5 1.9 1.6 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.5 1.7
43.0 1.8 1.5 1.8 1.6 2.0 1.6 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.6
20.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.7 2.1
22.5 2.7 1.9 2.8 2.0 3.0 2.0 3.1 2.1 3.2 2.1 3.4 2.1 3.6 2.1
25.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
27.5 2.6 1.9 2.7 2.0 2.9 1.9 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
25 30.0 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.8 2.6 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
35.0 2.4 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 1.9
37.5 2.4 1.8 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
40.0 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.9
43.0 2.3 1.8 2.4 1.8 2.5 1.8 2.6 1.9 2.7 1.9 2.9 1.9 3.1 1.9
20.0 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.7 4.1 2.7 4.4 2.7 4.7 2.7
22.5 3.4 2.5 3.5 2.6 3.8 2.5 3.9 2.7 4.1 2.7 4.3 2.7 4.6 2.6
25.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.5 2.6
27.5 3.3 2.4 3.4 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.5 2.6
32 30.0 3.2 2.4 3.4 2.5 3.6 2.5 3.7 2.6 3.9 2.6 4.1 2.6 4.4 2.5
(3.6) 32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.0 2.5 4.3 2.5
35.0 3.1 2.3 3.2 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.5
37.5 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.9 2.5 4.1 2.4
40.0 3.0 2.3 3.1 2.3 3.3 2.3 3.4 2.5 3.6 2.5 3.8 2.4 4.0 2.4
43.0 2.9 2.2 3.0 2.3 3.2 2.3 3.4 2.4 3.5 2.4 3.7 2.4 3.9 2.4
20.0 4.3 3.1 4.5 3.2 4.8 3.2 5.0 3.4 5.2 3.4 5.5 3.4 5.9 3.3
22.5 4.3 3.1 4.4 3.2 4.7 3.2 4.9 3.4 5.1 3.4 5.4 3.3 5.8 3.3
25.0 4.2 3.1 4.3 3.2 4.7 3.2 4.8 3.3 5.0 3.3 5.3 3.3 5.7 3.3
27.5 4.1 3.0 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.2 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.0 4.6 3.2 4.7 3.2 5.0 3.2 5.4 3.1
35.0 3.9 2.9 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.3 3.1
37.5 3.8 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.1 4.8 3.1 5.2 3.1
40.0 3.8 2.9 3.9 2.9 4.2 2.9 4.3 3.1 4.5 3.1 4.8 3.1 5.1 3.0
43.0 3.7 2.8 3.8 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.6 3.0 4.9 3.0
20.0 5.4 4.0 5.6 4.1 6.0 4.1 6.2 4.3 6.4 4.3 6.9 4.3 7.3 4.2
22.5 5.3 3.9 5.5 4.1 5.9 4.0 6.1 4.3 6.3 4.3 6.7 4.2 7.2 4.2
25.0 5.2 3.9 5.4 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
27.5 5.1 3.8 5.3 4.0 5.7 3.9 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
50 30.0 5.0 3.8 5.2 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.8 4.0
(5.6) 32.5 5.0 3.7 5.1 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.3 4.0 6.7 4.0
35.0 4.9 3.7 5.0 3.8 5.4 3.8 5.6 4.1 5.8 4.0 6.2 4.0 6.5 3.9
37.5 4.8 3.7 4.9 3.8 5.3 3.8 5.5 4.0 5.7 4.0 6.0 3.9 6.4 3.9
40.0 4.7 3.6 4.8 3.7 5.2 3.7 5.4 4.0 5.5 3.9 5.9 3.9 6.3 3.9
43.0 4.6 3.6 4.7 3.7 5.1 3.7 5.2 3.9 5.4 3.9 5.8 3.9 6.1 3.8
20.0 6.9 4.9 7.1 5.1 7.6 5.1 7.9 5.3 8.2 5.3 8.7 5.3 9.3 5.2
22.5 6.7 4.9 7.0 5.0 7.5 5.0 7.8 5.3 8.0 5.3 8.6 5.2 9.1 5.1
25.0 6.6 4.8 6.9 5.0 7.4 4.9 7.6 5.2 7.9 5.2 8.4 5.2 8.9 5.1
27.5 6.5 4.7 6.7 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.3 5.1 8.8 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.3 4.6 6.5 4.8 7.0 4.8 7.2 5.0 7.5 5.0 7.9 5.0 8.5 4.9
35.0 6.2 4.6 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.3 4.8
37.5 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.2 4.9 7.6 4.9 8.1 4.8
40.0 5.9 4.5 6.1 4.6 6.6 4.6 6.8 4.9 7.0 4.8 7.5 4.8 8.0 4.7
43.0 5.8 4.4 6.0 4.5 6.4 4.5 6.6 4.8 6.9 4.8 7.3 4.7 7.8 4.7
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 170


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
8-5. Cooling capacity with PUHY-RP850-900YSJM
PFFY-P-VKM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
25.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.7 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.7
35.0 2.0 1.6 2.0 1.7 2.1 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.8 2.3 1.8 2.4 1.7 2.6 1.7
40.0 1.9 1.6 1.9 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.4 1.7 2.6 1.7
43.0 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
20.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
22.5 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
25.0 2.6 2.0 2.7 2.0 2.9 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.5 2.1
27.5 2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.1
25 30.0 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
37.5 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
40.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
43.0 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
20.0 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.3 2.6 4.5 2.5
22.5 3.4 2.4 3.5 2.5 3.7 2.4 3.8 2.6 4.0 2.6 4.2 2.5 4.5 2.5
25.0 3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.5 4.2 2.5 4.4 2.5
27.5 3.3 2.4 3.4 2.4 3.6 2.4 3.8 2.5 3.9 2.5 4.1 2.5 4.4 2.5
32 30.0 3.3 2.3 3.3 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.4 2.5
(3.6) 32.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.1 2.5 4.3 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.3 3.6 2.5 3.8 2.5 4.0 2.5 4.3 2.4
37.5 3.2 2.3 3.2 2.3 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.4 4.2 2.4
40.0 3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.7 2.4 3.9 2.4 4.2 2.4
43.0 3.1 2.3 3.1 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.9 2.4 4.2 2.4
20.0 4.3 3.0 4.4 3.1 4.7 3.0 4.8 3.2 5.0 3.2 5.3 3.2 5.7 3.1
22.5 4.2 3.0 4.3 3.0 4.6 3.0 4.8 3.2 4.9 3.2 5.3 3.1 5.6 3.1
25.0 4.2 2.9 4.3 3.0 4.6 3.0 4.7 3.2 4.9 3.1 5.2 3.1 5.6 3.1
27.5 4.1 2.9 4.2 3.0 4.5 3.0 4.7 3.1 4.8 3.1 5.2 3.1 5.5 3.1
40 30.0 4.1 2.9 4.2 2.9 4.5 2.9 4.6 3.1 4.8 3.1 5.1 3.1 5.5 3.0
(4.5) 32.5 4.0 2.9 4.1 2.9 4.4 2.9 4.6 3.1 4.7 3.1 5.1 3.0 5.4 3.0
35.0 4.0 2.8 4.1 2.9 4.4 2.9 4.5 3.0 4.7 3.0 5.0 3.0 5.4 3.0
37.5 4.0 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.6 3.0 5.0 3.0 5.3 3.0
40.0 3.9 2.8 4.0 2.8 4.3 2.8 4.4 3.0 4.6 3.0 4.9 3.0 5.3 3.0
43.0 3.9 2.8 3.9 2.8 4.2 2.8 4.4 3.0 4.5 3.0 4.9 3.0 5.2 2.9
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 171


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLEM-E,VLRM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
25.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.7 2.7 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.5 1.7 2.6 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.6 1.7
40.0 1.9 1.6 1.9 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.4 1.7 2.6 1.7
43.0 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
20.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
22.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
25.0 2.6 1.9 2.7 2.0 2.9 1.9 2.9 2.1 3.0 2.1 3.2 2.0 3.5 2.0
27.5 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
25 30.0 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
37.5 2.5 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
40.0 2.4 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 1.9
43.0 2.4 1.8 2.4 1.8 2.6 1.8 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
20.0 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.5 2.6
22.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.6
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.4 2.6
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.8 2.6 3.9 2.6 4.1 2.6 4.4 2.5
32 30.0 3.3 2.4 3.3 2.5 3.6 2.4 3.7 2.6 3.8 2.6 4.1 2.6 4.4 2.5
(3.6) 32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.1 2.5 4.3 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.6 4.0 2.5 4.3 2.5
37.5 3.2 2.3 3.2 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.5
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.5 4.2 2.5
43.0 3.1 2.3 3.1 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.9 2.5 4.2 2.5
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.3 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.1 4.8 3.3 4.9 3.3 5.3 3.3 5.6 3.2
25.0 4.2 3.1 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.2 5.1 3.2 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.2 4.7 3.2 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.0 4.4 3.0 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.1
37.5 4.0 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.1
40.0 3.9 2.9 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.1 5.3 3.1
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.1 4.5 3.1 4.9 3.1 5.2 3.1
20.0 5.3 3.9 5.5 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
22.5 5.2 3.9 5.4 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
25.0 5.2 3.9 5.3 4.0 5.7 3.9 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
27.5 5.1 3.8 5.3 3.9 5.6 3.9 5.8 4.2 6.0 4.1 6.4 4.1 6.9 4.1
50 30.0 5.1 3.8 5.2 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.8 4.0
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.3 4.1 6.7 4.0
35.0 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.8 4.1 6.2 4.0 6.7 4.0
37.5 4.9 3.7 5.0 3.8 5.4 3.8 5.6 4.1 5.8 4.0 6.2 4.0 6.6 4.0
40.0 4.9 3.7 4.9 3.8 5.3 3.8 5.5 4.0 5.7 4.0 6.1 4.0 6.5 3.9
43.0 4.8 3.7 4.9 3.7 5.2 3.7 5.4 4.0 5.6 4.0 6.0 4.0 6.5 3.9
20.0 6.7 4.8 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.1 8.9 5.1
22.5 6.6 4.8 6.8 4.9 7.3 4.9 7.6 5.2 7.8 5.2 8.3 5.1 8.8 5.0
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.8 5.0
27.5 6.5 4.7 6.7 4.9 7.2 4.8 7.4 5.1 7.6 5.1 8.2 5.1 8.7 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.0 8.0 5.0 8.5 4.9
35.0 6.3 4.6 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 7.9 5.0 8.5 4.9
37.5 6.2 4.6 6.3 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 4.9 7.2 4.9 7.8 4.9 8.3 4.9
43.0 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.1 4.9 7.7 4.9 8.2 4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 172


8. Cooling [Floor standing (Exposed 2-way/Exposed/Concealed type)]
PFFY-P-VLRMM-E CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp.
size air temp. 21.5C D.B. 23C D.B. 25C D.B. 27C D.B. 28C D.B. 30C D.B. 32C D.B.
(Rated kW) 15C W.B. 16C W.B. 18C W.B. 19C W.B. 20C W.B. 22C W.B. 24C W.B.
C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.8
22.5 2.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8 2.4 1.8 2.6 1.8 2.7 1.8
25.0 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
27.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.7
20 30.0 2.0 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.7 2.7 1.7
(2.2) 32.5 2.0 1.6 2.0 1.7 2.2 1.6 2.2 1.8 2.3 1.8 2.5 1.7 2.6 1.7
35.0 2.0 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.5 1.7 2.6 1.7
37.5 1.9 1.6 2.0 1.6 2.1 1.6 2.2 1.7 2.3 1.7 2.4 1.7 2.6 1.7
40.0 1.9 1.6 1.9 1.6 2.1 1.6 2.2 1.7 2.2 1.7 2.4 1.7 2.6 1.7
43.0 1.9 1.6 1.9 1.6 2.1 1.6 2.1 1.7 2.2 1.7 2.4 1.7 2.5 1.7
20.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.0
22.5 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.0 3.5 2.0
25.0 2.6 1.9 2.7 2.0 2.9 1.9 2.9 2.1 3.0 2.1 3.2 2.0 3.5 2.0
27.5 2.6 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
25 30.0 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
(2.8) 32.5 2.5 1.9 2.6 1.9 2.8 1.9 2.9 2.0 3.0 2.0 3.2 2.0 3.4 2.0
35.0 2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
37.5 2.5 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 2.0
40.0 2.4 1.8 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.1 2.0 3.3 1.9
43.0 2.4 1.8 2.4 1.8 2.6 1.8 2.7 2.0 2.8 2.0 3.0 1.9 3.2 1.9
20.0 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.7 4.0 2.7 4.3 2.6 4.5 2.6
22.5 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.6
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.6 4.4 2.6
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.8 2.6 3.9 2.6 4.1 2.6 4.4 2.5
32 30.0 3.3 2.4 3.3 2.5 3.6 2.4 3.7 2.6 3.8 2.6 4.1 2.6 4.4 2.5
(3.6) 32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.6 3.8 2.6 4.1 2.5 4.3 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.6 4.0 2.5 4.3 2.5
37.5 3.2 2.3 3.2 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.5
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.5 4.2 2.5
43.0 3.1 2.3 3.1 2.4 3.4 2.4 3.5 2.5 3.6 2.5 3.9 2.5 4.2 2.5
20.0 4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.3 5.3 3.3 5.7 3.3
22.5 4.2 3.1 4.3 3.2 4.6 3.1 4.8 3.3 4.9 3.3 5.3 3.3 5.6 3.2
25.0 4.2 3.1 4.3 3.1 4.6 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.2 3.2 5.5 3.2
40 30.0 4.1 3.0 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.2 5.1 3.2 5.5 3.2
(4.5) 32.5 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.2 4.7 3.2 5.1 3.2 5.4 3.2
35.0 4.0 3.0 4.1 3.0 4.4 3.0 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.1
37.5 4.0 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.6 3.2 5.0 3.2 5.3 3.1
40.0 3.9 2.9 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 4.9 3.1 5.3 3.1
43.0 3.9 2.9 3.9 3.0 4.2 3.0 4.4 3.1 4.5 3.1 4.9 3.1 5.2 3.1
20.0 5.3 3.9 5.5 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
22.5 5.2 3.9 5.4 4.0 5.8 4.0 6.0 4.2 6.2 4.2 6.6 4.2 7.0 4.1
25.0 5.2 3.9 5.3 4.0 5.7 3.9 5.9 4.2 6.1 4.2 6.5 4.1 6.9 4.1
27.5 5.1 3.8 5.3 3.9 5.6 3.9 5.8 4.2 6.0 4.1 6.4 4.1 6.9 4.1
50 30.0 5.1 3.8 5.2 3.9 5.6 3.9 5.8 4.1 6.0 4.1 6.4 4.1 6.8 4.0
(5.6) 32.5 5.0 3.8 5.1 3.9 5.5 3.9 5.7 4.1 5.9 4.1 6.3 4.1 6.7 4.0
35.0 5.0 3.8 5.1 3.8 5.4 3.8 5.6 4.1 5.8 4.1 6.2 4.0 6.7 4.0
37.5 4.9 3.7 5.0 3.8 5.4 3.8 5.6 4.1 5.8 4.0 6.2 4.0 6.6 4.0
40.0 4.9 3.7 4.9 3.8 5.3 3.8 5.5 4.0 5.7 4.0 6.1 4.0 6.5 3.9
43.0 4.8 3.7 4.9 3.7 5.2 3.7 5.4 4.0 5.6 4.0 6.0 4.0 6.5 3.9
20.0 6.7 4.8 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.1 8.9 5.1
22.5 6.6 4.8 6.8 4.9 7.3 4.9 7.6 5.2 7.8 5.2 8.3 5.1 8.8 5.0
25.0 6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.1 8.2 5.1 8.8 5.0
27.5 6.5 4.7 6.7 4.9 7.2 4.8 7.4 5.1 7.6 5.1 8.2 5.1 8.7 5.0
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
(7.1) 32.5 6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.1 7.5 5.0 8.0 5.0 8.5 4.9
35.0 6.3 4.6 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 7.9 5.0 8.5 4.9
37.5 6.2 4.6 6.3 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.8 4.9 8.4 4.9
40.0 6.2 4.6 6.3 4.7 6.7 4.7 7.0 4.9 7.2 4.9 7.8 4.9 8.3 4.9
43.0 6.1 4.5 6.2 4.6 6.7 4.6 6.9 4.9 7.1 4.9 7.7 4.9 8.2 4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 173


9. Heating [All indoor units]
9-1. Heating capacity with PUHY,PURY-RP200-250YJM
9. Heating [All indoor units]

All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.3 1.3 1.3 1.3 -20.0 6.2 6.1 6.1 6.0
-15.0 1.4 1.4 1.4 1.3 -15.0 6.7 6.7 6.5 6.3
-10.0 1.6 1.6 1.5 1.3 -10.0 7.4 7.4 7.1 6.3
-5.0 1.8 1.8 1.5 1.3 -5.0 8.4 8.3 7.2 6.3
0.0 1.9 1.9 1.5 1.3 0.0 9.1 9.0 7.2 6.3
15 71
(1.9) 2.5 1.9 1.9 1.5 1.3 (9.0) 2.5 9.1 9.0 7.2 6.3
6.0 1.9 1.9 1.5 1.3 6.0 9.1 9.0 7.2 6.3
7.5 2.0 1.9 1.5 1.3 7.5 9.3 9.0 7.2 6.3
10.0 2.1 1.9 1.5 1.3 10.0 9.8 9.0 7.2 6.3
12.5 2.2 1.9 1.5 1.3 12.5 10.4 9.0 7.2 6.3
15.5 2.4 1.9 1.5 1.3 15.5 11.3 9.0 7.2 6.3
-20.0 1.7 1.7 1.7 1.7 -20.0 6.9 6.8 6.8 6.7
-15.0 1.9 1.9 1.8 1.7 -15.0 7.5 7.5 7.2 6.9
-10.0 2.1 2.0 2.0 1.8 -10.0 8.3 8.2 7.9 7.0
-5.0 2.3 2.3 2.0 1.8 -5.0 9.4 9.3 8.0 7.0
0.0 2.5 2.5 2.0 1.8 0.0 10.1 10.0 8.0 7.0
20 80
(2.5) 2.5 2.5 2.5 2.0 1.8 (10.0) 2.5 10.1 10.0 8.0 7.0
6.0 2.5 2.5 2.0 1.8 6.0 10.1 10.0 8.0 7.0
7.5 2.6 2.5 2.0 1.8 7.5 10.4 10.0 8.0 7.0
10.0 2.7 2.5 2.0 1.8 10.0 10.9 10.0 8.0 7.0
12.5 2.9 2.5 2.0 1.8 12.5 11.6 10.0 8.0 7.0
15.5 3.1 2.5 2.0 1.8 15.5 12.6 10.0 8.0 7.0
-20.0 2.2 2.2 2.2 2.1 -20.0 8.7 8.5 8.5 8.4
-15.0 2.4 2.4 2.3 2.2 -15.0 9.3 9.3 9.0 8.7
-10.0 2.6 2.6 2.5 2.2 -10.0 10.3 10.2 9.9 8.8
-5.0 3.0 3.0 2.6 2.2 -5.0 11.7 11.6 10.0 8.8
0.0 3.2 3.2 2.6 2.2 0.0 12.6 12.5 10.0 8.8
25 100
(3.2) 2.5 3.2 3.2 2.6 2.2 (12.5) 2.5 12.6 12.5 10.0 8.8
6.0 3.2 3.2 2.6 2.2 6.0 12.6 12.5 10.0 8.8
7.5 3.3 3.2 2.6 2.2 7.5 12.9 12.5 10.0 8.8
10.0 3.5 3.2 2.6 2.2 10.0 13.6 12.5 10.0 8.8
12.5 3.7 3.2 2.6 2.2 12.5 14.5 12.5 10.0 8.8
15.5 4.0 3.2 2.6 2.2 15.5 15.7 12.5 10.0 8.8
-20.0 2.8 2.7 2.7 2.7 -20.0 11.1 10.9 10.8 10.7
-15.0 3.0 3.0 2.9 2.8 -15.0 11.9 11.9 11.5 11.1
-10.0 3.3 3.3 3.2 2.8 -10.0 13.2 13.1 12.6 11.2
-5.0 3.7 3.7 3.2 2.8 -5.0 15.0 14.8 12.8 11.2
0.0 4.0 4.0 3.2 2.8 0.0 16.2 16.0 12.8 11.2
32 125
(4.0) 2.5 4.0 4.0 3.2 2.8 (16.0) 2.5 16.2 16.0 12.8 11.2
6.0 4.0 4.0 3.2 2.8 6.0 16.2 16.0 12.8 11.2
7.5 4.1 4.0 3.2 2.8 7.5 16.6 16.0 12.8 11.2
10.0 4.4 4.0 3.2 2.8 10.0 17.4 16.0 12.8 11.2
12.5 4.6 4.0 3.2 2.8 12.5 18.5 16.0 12.8 11.2
15.5 5.0 4.0 3.2 2.8 15.5 20.1 16.0 12.8 11.2
-20.0 3.5 3.4 3.4 3.3 -20.0 12.5 12.2 12.2 12.1
-15.0 3.7 3.7 3.6 3.5 -15.0 13.4 13.4 12.9 12.5
-10.0 4.1 4.1 3.9 3.5 -10.0 14.9 14.7 14.2 12.6
-5.0 4.7 4.6 4.0 3.5 -5.0 16.9 16.7 14.4 12.6
0.0 5.1 5.0 4.0 3.5 0.0 18.2 18.0 14.4 12.6
40 140
2.5 5.1 5.0 4.0 3.5 2.5 18.2 18.0 14.4 12.6
(5.0) (18.0)
6.0 5.1 5.0 4.0 3.5 6.0 18.2 18.0 14.4 12.6
7.5 5.2 5.0 4.0 3.5 7.5 18.6 18.0 14.4 12.6
10.0 5.5 5.0 4.0 3.5 10.0 19.6 18.0 14.4 12.6
12.5 5.8 5.0 4.0 3.5 12.5 20.9 18.0 14.4 12.6
15.5 6.3 5.0 4.0 3.5 15.5 22.6 18.0 14.4 12.6
-20.0 4.4 4.3 4.3 4.2 -20.0 17.3 17.0 16.9 16.7
-15.0 4.7 4.7 4.5 4.4 -15.0 18.6 18.6 18.0 17.4
-10.0 5.2 5.2 5.0 4.4 -10.0 20.7 20.5 19.7 17.5
-5.0 5.9 5.8 5.0 4.4 -5.0 23.4 23.1 20.0 17.5
0.0 6.4 6.3 5.0 4.4 0.0 25.3 25.0 20.0 17.5
50 200
(6.3) 2.5 6.4 6.3 5.0 4.4 (25.0) 2.5 25.3 25.0 20.0 17.5
6.0 6.4 6.3 5.0 4.4 6.0 25.3 25.0 20.0 17.5
7.5 6.5 6.3 5.0 4.4 7.5 25.9 25.0 20.0 17.5
10.0 6.9 6.3 5.0 4.4 10.0 27.3 25.0 20.0 17.5
12.5 7.3 6.3 5.0 4.4 12.5 29.0 25.0 20.0 17.5
15.5 7.9 6.3 5.0 4.4 15.5 31.4 25.0 20.0 17.5
-20.0 5.5 5.4 5.4 5.4 -20.0 21.8 21.4 21.3 21.1
-15.0 6.0 6.0 5.7 5.6 -15.0 23.5 23.5 22.6 21.9
-10.0 6.6 6.6 6.3 5.6 -10.0 26.1 25.8 24.9 22.1
-5.0 7.5 7.4 6.4 5.6 -5.0 29.5 29.1 25.2 22.1
0.0 8.1 8.0 6.4 5.6 0.0 31.8 31.5 25.2 22.1
63 250
(8.0) 2.5 8.1 8.0 6.4 5.6 (31.5) 2.5 31.8 31.5 25.2 22.1
6.0 8.1 8.0 6.4 5.6 6.0 31.8 31.5 25.2 22.1
7.5 8.3 8.0 6.4 5.6 7.5 32.6 31.5 25.2 22.1
10.0 8.7 8.0 6.4 5.6 10.0 34.3 31.5 25.2 22.1
12.5 9.3 8.0 6.4 5.6 12.5 36.5 31.5 25.2 22.1
15.5 10.1 8.0 6.4 5.6 15.5 39.6 31.5 25.2 22.1
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 174


9. Heating [All indoor units]
9-2. Heating capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.2 1.2 1.2 1.2 -20.0 5.8 5.8 5.8 5.6
-15.0 1.3 1.3 1.3 1.2 -15.0 6.3 6.3 6.2 5.8
-10.0 1.5 1.5 1.4 1.2 -10.0 6.9 6.9 6.7 5.8
-5.0 1.6 1.7 1.4 1.2 -5.0 7.8 7.8 6.7 5.8
0.0 1.8 1.8 1.4 1.2 0.0 8.8 8.8 6.7 5.8
15 71
(1.9) 2.5 1.9 1.9 1.4 1.2 (9.0) 2.5 9.0 9.0 6.7 5.8
6.0 1.9 1.9 1.4 1.2 6.0 9.2 9.0 6.7 5.8
7.5 2.0 1.9 1.4 1.2 7.5 9.5 9.0 6.7 5.8
10.0 2.1 1.9 1.4 1.2 10.0 9.9 9.0 6.7 5.8
12.5 2.2 1.9 1.4 1.2 12.5 10.3 9.0 6.7 5.8
15.5 2.2 1.9 1.4 1.2 15.5 10.3 9.0 6.7 5.8
-20.0 1.6 1.6 1.6 1.6 -20.0 6.4 6.5 6.4 6.2
-15.0 1.7 1.7 1.7 1.6 -15.0 7.0 7.0 6.9 6.4
-10.0 1.9 1.9 1.9 1.6 -10.0 7.7 7.7 7.5 6.4
-5.0 2.2 2.2 1.9 1.6 -5.0 8.7 8.7 7.5 6.4
0.0 2.4 2.4 1.9 1.6 0.0 9.7 9.7 7.5 6.4
20 80
(2.5) 2.5 2.5 2.5 1.9 1.6 (10.0) 2.5 10.0 10.0 7.5 6.4
6.0 2.6 2.5 1.9 1.6 6.0 10.2 10.0 7.5 6.4
7.5 2.6 2.5 1.9 1.6 7.5 10.5 10.0 7.5 6.4
10.0 2.8 2.5 1.9 1.6 10.0 11.1 10.0 7.5 6.4
12.5 2.9 2.5 1.9 1.6 12.5 11.5 10.0 7.5 6.4
15.5 2.9 2.5 1.9 1.6 15.5 11.5 10.0 7.5 6.4
-20.0 2.1 2.1 2.1 2.0 -20.0 8.0 8.1 8.0 7.8
-15.0 2.2 2.2 2.2 2.0 -15.0 8.7 8.7 8.6 8.0
-10.0 2.5 2.5 2.4 2.0 -10.0 9.6 9.6 9.3 8.0
-5.0 2.8 2.8 2.4 2.0 -5.0 10.8 10.9 9.3 8.0
0.0 3.1 3.1 2.4 2.0 0.0 12.2 12.2 9.3 8.0
25 100
(3.2) 2.5 3.2 3.2 2.4 2.0 (12.5) 2.5 12.5 12.5 9.3 8.0
6.0 3.3 3.2 2.4 2.0 6.0 12.8 12.5 9.3 8.0
7.5 3.4 3.2 2.4 2.0 7.5 13.2 12.5 9.3 8.0
10.0 3.5 3.2 2.4 2.0 10.0 13.8 12.5 9.3 8.0
12.5 3.7 3.2 2.4 2.0 12.5 14.3 12.5 9.3 8.0
15.5 3.7 3.2 2.4 2.0 15.5 14.3 12.5 9.3 8.0
-20.0 2.6 2.6 2.6 2.5 -20.0 10.3 10.3 10.3 9.9
-15.0 2.8 2.8 2.8 2.6 -15.0 11.1 11.2 11.1 10.2
-10.0 3.1 3.1 3.0 2.6 -10.0 12.3 12.3 11.9 10.2
-5.0 3.5 3.5 3.0 2.6 -5.0 13.9 13.9 11.9 10.2
0.0 3.9 3.9 3.0 2.6 0.0 15.6 15.6 11.9 10.2
32 125
(4.0) 2.5 4.0 4.0 3.0 2.6 (16.0) 2.5 16.0 16.0 11.9 10.2
6.0 4.1 4.0 3.0 2.6 6.0 16.4 16.0 11.9 10.2
7.5 4.2 4.0 3.0 2.6 7.5 16.9 16.0 11.9 10.2
10.0 4.4 4.0 3.0 2.6 10.0 17.7 16.0 11.9 10.2
12.5 4.6 4.0 3.0 2.6 12.5 18.3 16.0 11.9 10.2
15.5 4.6 4.0 3.0 2.6 15.5 18.3 16.0 11.9 10.2
-20.0 3.2 3.2 3.2 3.1 -20.0 11.5 11.6 11.5 11.2
-15.0 3.5 3.5 3.5 3.2 -15.0 12.5 12.6 12.5 11.5
-10.0 3.8 3.8 3.7 3.2 -10.0 13.8 13.8 13.4 11.5
-5.0 4.3 4.3 3.7 3.2 -5.0 15.6 15.6 13.4 11.5
0.0 4.9 4.9 3.7 3.2 0.0 17.5 17.5 13.4 11.5
40 140
2.5 5.0 5.0 3.7 3.2 2.5 18.0 18.0 13.4 11.5
(5.0) (18.0)
6.0 5.1 5.0 3.7 3.2 6.0 18.4 18.0 13.4 11.5
7.5 5.3 5.0 3.7 3.2 7.5 19.0 18.0 13.4 11.5
10.0 5.5 5.0 3.7 3.2 10.0 19.9 18.0 13.4 11.5
12.5 5.7 5.0 3.7 3.2 12.5 20.6 18.0 13.4 11.5
15.5 5.7 5.0 3.7 3.2 15.5 20.6 18.0 13.4 11.5
-20.0 4.0 4.1 4.0 3.9 -20.0 16.0 16.1 16.0 15.5
-15.0 4.4 4.4 4.4 4.0 -15.0 17.4 17.5 17.3 16.0
-10.0 4.8 4.8 4.7 4.0 -10.0 19.2 19.2 18.6 16.0
-5.0 5.5 5.5 4.7 4.0 -5.0 21.7 21.7 18.6 16.0
0.0 6.1 6.1 4.7 4.0 0.0 24.3 24.3 18.6 16.0
50 200
(6.3) 2.5 6.3 6.3 4.7 4.0 (25.0) 2.5 25.0 25.0 18.6 16.0
6.0 6.5 6.3 4.7 4.0 6.0 25.6 25.0 18.6 16.0
7.5 6.6 6.3 4.7 4.0 7.5 26.4 25.0 18.6 16.0
10.0 7.0 6.3 4.7 4.0 10.0 27.6 25.0 18.6 16.0
12.5 7.2 6.3 4.7 4.0 12.5 28.6 25.0 18.6 16.0
15.5 7.2 6.3 4.7 4.0 15.5 28.6 25.0 18.6 16.0
-20.0 5.1 5.2 5.1 5.0 -20.0 20.2 20.3 20.2 19.6
-15.0 5.6 5.6 5.5 5.1 -15.0 21.9 22.0 21.8 20.2
-10.0 6.1 6.2 6.0 5.1 -10.0 24.2 24.2 23.5 20.2
-5.0 6.9 7.0 6.0 5.1 -5.0 27.3 27.4 23.5 20.2
0.0 7.8 7.8 6.0 5.1 0.0 30.6 30.6 23.5 20.2
63 250
(8.0) 2.5 8.0 8.0 6.0 5.1 (31.5) 2.5 31.5 31.5 23.5 20.2
6.0 8.2 8.0 6.0 5.1 6.0 32.3 31.5 23.5 20.2
7.5 8.4 8.0 6.0 5.1 7.5 33.2 31.5 23.5 20.2
10.0 8.8 8.0 6.0 5.1 10.0 34.8 31.5 23.5 20.2
12.5 9.2 8.0 6.0 5.1 12.5 36.1 31.5 23.5 20.2
15.5 9.2 8.0 6.0 5.1 15.5 36.1 31.5 23.5 20.2
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 175


9. Heating [All indoor units]
9-3. Heating capacity with PUHY-RP450-650YSJM
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.2 1.1 1.2 1.1 -20.0 5.5 5.4 5.4 5.3
-15.0 1.3 1.3 1.2 1.2 -15.0 6.1 6.0 5.8 5.7
-10.0 1.4 1.4 1.3 1.3 -10.0 6.8 6.6 6.4 6.2
-5.0 1.6 1.6 1.5 1.3 -5.0 7.5 7.4 7.1 6.4
0.0 1.8 1.8 1.5 1.3 0.0 8.3 8.3 7.1 6.4
15 71
(1.9) 2.5 1.8 1.8 1.5 1.3 (9.0) 2.5 8.7 8.7 7.1 6.4
6.0 1.9 1.9 1.5 1.3 6.0 9.2 9.0 7.1 6.4
7.5 2.0 1.9 1.5 1.3 7.5 9.5 9.0 7.1 6.4
10.0 2.1 1.9 1.5 1.3 10.0 9.9 9.0 7.1 6.4
12.5 2.2 1.9 1.5 1.3 12.5 10.3 9.0 7.1 6.4
15.5 2.2 1.9 1.5 1.3 15.5 10.4 9.0 7.1 6.4
-20.0 1.5 1.5 1.5 1.5 -20.0 6.2 6.0 6.1 5.9
-15.0 1.7 1.7 1.6 1.6 -15.0 6.8 6.6 6.5 6.3
-10.0 1.9 1.8 1.8 1.7 -10.0 7.5 7.3 7.1 6.9
-5.0 2.1 2.1 2.0 1.8 -5.0 8.3 8.3 7.9 7.1
0.0 2.3 2.3 2.0 1.8 0.0 9.2 9.2 7.9 7.1
20 80
(2.5) 2.5 2.4 2.4 2.0 1.8 (10.0) 2.5 9.7 9.7 7.9 7.1
6.0 2.6 2.5 2.0 1.8 6.0 10.2 10.0 7.9 7.1
7.5 2.6 2.5 2.0 1.8 7.5 10.5 10.0 7.9 7.1
10.0 2.7 2.5 2.0 1.8 10.0 11.0 10.0 7.9 7.1
12.5 2.9 2.5 2.0 1.8 12.5 11.5 10.0 7.9 7.1
15.5 2.9 2.5 2.0 1.8 15.5 11.5 10.0 7.9 7.1
-20.0 2.0 1.9 1.9 1.9 -20.0 7.7 7.5 7.6 7.4
-15.0 2.2 2.1 2.1 2.0 -15.0 8.5 8.3 8.1 7.9
-10.0 2.4 2.3 2.3 2.2 -10.0 9.4 9.1 8.9 8.7
-5.0 2.7 2.6 2.5 2.3 -5.0 10.4 10.3 9.9 8.9
0.0 3.0 3.0 2.5 2.3 0.0 11.5 11.5 9.9 8.9
25 100
(3.2) 2.5 3.1 3.1 2.5 2.3 (12.5) 2.5 12.1 12.1 9.9 8.9
6.0 3.3 3.2 2.5 2.3 6.0 12.8 12.5 9.9 8.9
7.5 3.4 3.2 2.5 2.3 7.5 13.1 12.5 9.9 8.9
10.0 3.5 3.2 2.5 2.3 10.0 13.7 12.5 9.9 8.9
12.5 3.7 3.2 2.5 2.3 12.5 14.3 12.5 9.9 8.9
15.5 3.7 3.2 2.5 2.3 15.5 14.4 12.5 9.9 8.9
-20.0 2.5 2.4 2.4 2.4 -20.0 9.9 9.6 9.7 9.4
-15.0 2.7 2.7 2.6 2.5 -15.0 10.9 10.6 10.4 10.1
-10.0 3.0 2.9 2.8 2.8 -10.0 12.0 11.7 11.4 11.1
-5.0 3.3 3.3 3.2 2.8 -5.0 13.3 13.2 12.7 11.3
0.0 3.7 3.7 3.2 2.8 0.0 14.8 14.8 12.7 11.3
32 125
(4.0) 2.5 3.9 3.9 3.2 2.8 (16.0) 2.5 15.5 15.5 12.7 11.3
6.0 4.1 4.0 3.2 2.8 6.0 16.3 16.0 12.7 11.3
7.5 4.2 4.0 3.2 2.8 7.5 16.8 16.0 12.7 11.3
10.0 4.4 4.0 3.2 2.8 10.0 17.6 16.0 12.7 11.3
12.5 4.6 4.0 3.2 2.8 12.5 18.4 16.0 12.7 11.3
15.5 4.6 4.0 3.2 2.8 15.5 18.5 16.0 12.7 11.3
-20.0 3.1 3.0 3.0 2.9 -20.0 11.1 10.8 10.9 10.6
-15.0 3.4 3.3 3.2 3.1 -15.0 12.3 11.9 11.7 11.3
-10.0 3.8 3.6 3.6 3.5 -10.0 13.5 13.1 12.8 12.5
-5.0 4.2 4.1 4.0 3.5 -5.0 15.0 14.9 14.3 12.8
0.0 4.6 4.6 4.0 3.5 0.0 16.6 16.6 14.3 12.8
40 140
2.5 4.9 4.9 4.0 3.5 2.5 17.5 17.5 14.3 12.8
(5.0) (18.0)
6.0 5.1 5.0 4.0 3.5 6.0 18.4 18.0 14.3 12.8
7.5 5.3 5.0 4.0 3.5 7.5 18.9 18.0 14.3 12.8
10.0 5.5 5.0 4.0 3.5 10.0 19.8 18.0 14.3 12.8
12.5 5.7 5.0 4.0 3.5 12.5 20.7 18.0 14.3 12.8
15.5 5.8 5.0 4.0 3.5 15.5 20.8 18.0 14.3 12.8
-20.0 3.9 3.8 3.8 3.7 -20.0 15.4 15.0 15.1 14.7
-15.0 4.3 4.2 4.1 4.0 -15.0 17.1 16.6 16.2 15.7
-10.0 4.7 4.6 4.5 4.4 -10.0 18.8 18.2 17.8 17.3
-5.0 5.2 5.2 5.0 4.5 -5.0 20.8 20.6 19.8 17.7
0.0 5.8 5.8 5.0 4.5 0.0 23.1 23.0 19.8 17.7
50 200
(6.3) 2.5 6.1 6.1 5.0 4.5 (25.0) 2.5 24.3 24.3 19.8 17.7
6.0 6.4 6.3 5.0 4.5 6.0 25.5 25.0 19.8 17.7
7.5 6.6 6.3 5.0 4.5 7.5 26.3 25.0 19.8 17.7
10.0 6.9 6.3 5.0 4.5 10.0 27.4 25.0 19.8 17.7
12.5 7.2 6.3 5.0 4.5 12.5 28.7 25.0 19.8 17.7
15.5 7.3 6.3 5.0 4.5 15.5 28.9 25.0 19.8 17.7
-20.0 4.9 4.8 4.8 4.7 -20.0 19.4 18.9 19.1 18.6
-15.0 5.5 5.3 5.2 5.0 -15.0 21.5 20.9 20.4 19.8
-10.0 6.0 5.8 5.7 5.5 -10.0 23.6 23.0 22.4 21.8
-5.0 6.7 6.6 6.3 5.7 -5.0 26.2 26.0 24.9 22.3
0.0 7.4 7.4 6.3 5.7 0.0 29.1 29.0 25.0 22.3
63 250
(8.0) 2.5 7.8 7.8 6.3 5.7 (31.5) 2.5 30.6 30.6 25.0 22.3
6.0 8.2 8.0 6.3 5.7 6.0 32.2 31.5 25.0 22.3
7.5 8.4 8.0 6.3 5.7 7.5 33.1 31.5 25.0 22.3
10.0 8.8 8.0 6.3 5.7 10.0 34.6 31.5 25.0 22.3
12.5 9.2 8.0 6.3 5.7 12.5 36.1 31.5 25.0 22.3
15.5 9.2 8.0 6.3 5.7 15.5 36.4 31.5 25.0 22.3
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 176


9. Heating [All indoor units]
9-4. Heating capacity with PUHY-RP700-800YSJM
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.3 1.3 1.3 1.3 -20.0 6.2 6.2 6.1 6.0
-15.0 1.4 1.4 1.4 1.3 -15.0 6.8 6.8 6.5 6.3
-10.0 1.6 1.6 1.5 1.3 -10.0 7.5 7.4 7.2 6.3
-5.0 1.8 1.8 1.5 1.3 -5.0 8.5 8.4 7.2 6.3
0.0 1.9 1.9 1.5 1.3 0.0 9.1 9.0 7.2 6.3
15 71
(1.9) 2.5 1.9 1.9 1.5 1.3 (9.0) 2.5 9.1 9.0 7.2 6.3
6.0 1.9 1.9 1.5 1.3 6.0 9.1 9.0 7.2 6.3
7.5 2.0 1.9 1.5 1.3 7.5 9.3 9.0 7.2 6.3
10.0 2.1 1.9 1.5 1.3 10.0 9.8 9.0 7.2 6.3
12.5 2.2 1.9 1.5 1.3 12.5 10.4 9.0 7.2 6.3
15.5 2.4 1.9 1.5 1.3 15.5 11.3 9.0 7.2 6.3
-20.0 1.7 1.7 1.7 1.7 -20.0 6.9 6.9 6.8 6.7
-15.0 1.9 1.9 1.8 1.7 -15.0 7.6 7.5 7.3 6.9
-10.0 2.1 2.1 2.0 1.8 -10.0 8.3 8.3 8.0 7.0
-5.0 2.4 2.3 2.0 1.8 -5.0 9.4 9.3 8.0 7.0
0.0 2.5 2.5 2.0 1.8 0.0 10.1 10.0 8.0 7.0
20 80
(2.5) 2.5 2.5 2.5 2.0 1.8 (10.0) 2.5 10.1 10.0 8.0 7.0
6.0 2.5 2.5 2.0 1.8 6.0 10.1 10.0 8.0 7.0
7.5 2.6 2.5 2.0 1.8 7.5 10.4 10.0 8.0 7.0
10.0 2.7 2.5 2.0 1.8 10.0 10.9 10.0 8.0 7.0
12.5 2.9 2.5 2.0 1.8 12.5 11.6 10.0 8.0 7.0
15.5 3.1 2.5 2.0 1.8 15.5 12.6 10.0 8.0 7.0
-20.0 2.2 2.2 2.2 2.1 -20.0 8.7 8.6 8.5 8.4
-15.0 2.4 2.4 2.3 2.2 -15.0 9.4 9.4 9.1 8.7
-10.0 2.7 2.6 2.6 2.2 -10.0 10.4 10.3 10.0 8.8
-5.0 3.0 3.0 2.6 2.2 -5.0 11.8 11.7 10.0 8.8
0.0 3.2 3.2 2.6 2.2 0.0 12.6 12.5 10.0 8.8
25 100
(3.2) 2.5 3.2 3.2 2.6 2.2 (12.5) 2.5 12.6 12.5 10.0 8.8
6.0 3.2 3.2 2.6 2.2 6.0 12.6 12.5 10.0 8.8
7.5 3.3 3.2 2.6 2.2 7.5 12.9 12.5 10.0 8.8
10.0 3.5 3.2 2.6 2.2 10.0 13.6 12.5 10.0 8.8
12.5 3.7 3.2 2.6 2.2 12.5 14.5 12.5 10.0 8.8
15.5 4.0 3.2 2.6 2.2 15.5 15.7 12.5 10.0 8.8
-20.0 2.8 2.7 2.7 2.7 -20.0 11.1 11.0 10.9 10.7
-15.0 3.0 3.0 2.9 2.8 -15.0 12.1 12.0 11.6 11.1
-10.0 3.3 3.3 3.2 2.8 -10.0 13.3 13.2 12.8 11.2
-5.0 3.8 3.7 3.2 2.8 -5.0 15.1 14.9 12.8 11.2
0.0 4.0 4.0 3.2 2.8 0.0 16.2 16.0 12.8 11.2
32 125
(4.0) 2.5 4.0 4.0 3.2 2.8 (16.0) 2.5 16.2 16.0 12.8 11.2
6.0 4.0 4.0 3.2 2.8 6.0 16.2 16.0 12.8 11.2
7.5 4.1 4.0 3.2 2.8 7.5 16.6 16.0 12.8 11.2
10.0 4.4 4.0 3.2 2.8 10.0 17.4 16.0 12.8 11.2
12.5 4.6 4.0 3.2 2.8 12.5 18.5 16.0 12.8 11.2
15.5 5.0 4.0 3.2 2.8 15.5 20.1 16.0 12.8 11.2
-20.0 3.5 3.4 3.4 3.3 -20.0 12.5 12.3 12.3 12.1
-15.0 3.8 3.8 3.6 3.5 -15.0 13.6 13.5 13.1 12.5
-10.0 4.2 4.1 4.0 3.5 -10.0 15.0 14.9 14.4 12.6
-5.0 4.7 4.7 4.0 3.5 -5.0 17.0 16.8 14.4 12.6
0.0 5.1 5.0 4.0 3.5 0.0 18.2 18.0 14.4 12.6
40 140
2.5 5.1 5.0 4.0 3.5 2.5 18.2 18.0 14.4 12.6
(5.0) (18.0)
6.0 5.1 5.0 4.0 3.5 6.0 18.2 18.0 14.4 12.6
7.5 5.2 5.0 4.0 3.5 7.5 18.6 18.0 14.4 12.6
10.0 5.5 5.0 4.0 3.5 10.0 19.6 18.0 14.4 12.6
12.5 5.8 5.0 4.0 3.5 12.5 20.9 18.0 14.4 12.6
15.5 6.3 5.0 4.0 3.5 15.5 22.6 18.0 14.4 12.6
-20.0 4.4 4.3 4.3 4.2 -20.0 17.4 17.2 17.1 16.7
-15.0 4.8 4.7 4.6 4.4 -15.0 18.9 18.8 18.2 17.4
-10.0 5.2 5.2 5.0 4.4 -10.0 20.8 20.7 20.0 17.5
-5.0 5.9 5.9 5.0 4.4 -5.0 23.6 23.4 20.0 17.5
0.0 6.4 6.3 5.0 4.4 0.0 25.3 25.0 20.0 17.5
50 200
(6.3) 2.5 6.4 6.3 5.0 4.4 (25.0) 2.5 25.3 25.0 20.0 17.5
6.0 6.4 6.3 5.0 4.4 6.0 25.3 25.0 20.0 17.5
7.5 6.5 6.3 5.0 4.4 7.5 25.9 25.0 20.0 17.5
10.0 6.9 6.3 5.0 4.4 10.0 27.3 25.0 20.0 17.5
12.5 7.3 6.3 5.0 4.4 12.5 29.0 25.0 20.0 17.5
15.5 7.9 6.3 5.0 4.4 15.5 31.4 25.0 20.0 17.5
-20.0 5.6 5.5 5.5 5.4 -20.0 21.9 21.6 21.5 21.1
-15.0 6.0 6.0 5.8 5.6 -15.0 23.8 23.7 22.9 21.9
-10.0 6.7 6.6 6.4 5.6 -10.0 26.2 26.0 25.1 22.1
-5.0 7.5 7.5 6.4 5.6 -5.0 29.7 29.4 25.2 22.1
0.0 8.1 8.0 6.4 5.6 0.0 31.8 31.5 25.2 22.1
63 250
(8.0) 2.5 8.1 8.0 6.4 5.6 (31.5) 2.5 31.8 31.5 25.2 22.1
6.0 8.1 8.0 6.4 5.6 6.0 31.8 31.5 25.2 22.1
7.5 8.3 8.0 6.4 5.6 7.5 32.6 31.5 25.2 22.1
10.0 8.7 8.0 6.4 5.6 10.0 34.3 31.5 25.2 22.1
12.5 9.3 8.0 6.4 5.6 12.5 36.5 31.5 25.2 22.1
15.5 10.1 8.0 6.4 5.6 15.5 39.6 31.5 25.2 22.1
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 177


9. Heating [All indoor units]
9-5. Heating capacity with PUHY-RP850-900YSJM
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.2 1.2 1.2 1.2 -20.0 5.8 5.8 5.8 5.6
-15.0 1.3 1.3 1.3 1.2 -15.0 6.3 6.3 6.2 5.8
-10.0 1.5 1.5 1.4 1.2 -10.0 6.9 6.9 6.7 5.8
-5.0 1.6 1.7 1.4 1.2 -5.0 7.8 7.8 6.7 5.8
0.0 1.8 1.8 1.4 1.2 0.0 8.8 8.8 6.7 5.8
15 71
(1.9) 2.5 1.9 1.9 1.4 1.2 (9.0) 2.5 9.0 9.0 6.7 5.8
6.0 1.9 1.9 1.4 1.2 6.0 9.2 9.0 6.7 5.8
7.5 2.0 1.9 1.4 1.2 7.5 9.5 9.0 6.7 5.8
10.0 2.1 1.9 1.4 1.2 10.0 9.9 9.0 6.7 5.8
12.5 2.2 1.9 1.4 1.2 12.5 10.3 9.0 6.7 5.8
15.5 2.2 1.9 1.4 1.2 15.5 10.3 9.0 6.7 5.8
-20.0 1.6 1.6 1.6 1.6 -20.0 6.4 6.5 6.4 6.2
-15.0 1.7 1.7 1.7 1.6 -15.0 7.0 7.0 6.9 6.4
-10.0 1.9 1.9 1.9 1.6 -10.0 7.7 7.7 7.5 6.4
-5.0 2.2 2.2 1.9 1.6 -5.0 8.7 8.7 7.5 6.4
0.0 2.4 2.4 1.9 1.6 0.0 9.7 9.7 7.5 6.4
20 80
(2.5) 2.5 2.5 2.5 1.9 1.6 (10.0) 2.5 10.0 10.0 7.5 6.4
6.0 2.6 2.5 1.9 1.6 6.0 10.2 10.0 7.5 6.4
7.5 2.6 2.5 1.9 1.6 7.5 10.5 10.0 7.5 6.4
10.0 2.8 2.5 1.9 1.6 10.0 11.1 10.0 7.5 6.4
12.5 2.9 2.5 1.9 1.6 12.5 11.5 10.0 7.5 6.4
15.5 2.9 2.5 1.9 1.6 15.5 11.5 10.0 7.5 6.4
-20.0 2.1 2.1 2.1 2.0 -20.0 8.0 8.1 8.0 7.8
-15.0 2.2 2.2 2.2 2.0 -15.0 8.7 8.7 8.6 8.0
-10.0 2.5 2.5 2.4 2.0 -10.0 9.6 9.6 9.3 8.0
-5.0 2.8 2.8 2.4 2.0 -5.0 10.8 10.9 9.3 8.0
0.0 3.1 3.1 2.4 2.0 0.0 12.2 12.2 9.3 8.0
25 100
(3.2) 2.5 3.2 3.2 2.4 2.0 (12.5) 2.5 12.5 12.5 9.3 8.0
6.0 3.3 3.2 2.4 2.0 6.0 12.8 12.5 9.3 8.0
7.5 3.4 3.2 2.4 2.0 7.5 13.2 12.5 9.3 8.0
10.0 3.5 3.2 2.4 2.0 10.0 13.8 12.5 9.3 8.0
12.5 3.7 3.2 2.4 2.0 12.5 14.3 12.5 9.3 8.0
15.5 3.7 3.2 2.4 2.0 15.5 14.3 12.5 9.3 8.0
-20.0 2.6 2.6 2.6 2.5 -20.0 10.3 10.3 10.3 9.9
-15.0 2.8 2.8 2.8 2.6 -15.0 11.1 11.2 11.1 10.2
-10.0 3.1 3.1 3.0 2.6 -10.0 12.3 12.3 11.9 10.2
-5.0 3.5 3.5 3.0 2.6 -5.0 13.9 13.9 11.9 10.2
0.0 3.9 3.9 3.0 2.6 0.0 15.6 15.6 11.9 10.2
32 125
(4.0) 2.5 4.0 4.0 3.0 2.6 (16.0) 2.5 16.0 16.0 11.9 10.2
6.0 4.1 4.0 3.0 2.6 6.0 16.4 16.0 11.9 10.2
7.5 4.2 4.0 3.0 2.6 7.5 16.9 16.0 11.9 10.2
10.0 4.4 4.0 3.0 2.6 10.0 17.7 16.0 11.9 10.2
12.5 4.6 4.0 3.0 2.6 12.5 18.3 16.0 11.9 10.2
15.5 4.6 4.0 3.0 2.6 15.5 18.3 16.0 11.9 10.2
-20.0 3.2 3.2 3.2 3.1 -20.0 11.5 11.6 11.5 11.2
-15.0 3.5 3.5 3.5 3.2 -15.0 12.5 12.6 12.5 11.5
-10.0 3.8 3.8 3.7 3.2 -10.0 13.8 13.8 13.4 11.5
-5.0 4.3 4.3 3.7 3.2 -5.0 15.6 15.6 13.4 11.5
0.0 4.9 4.9 3.7 3.2 0.0 17.5 17.5 13.4 11.5
40 140
2.5 5.0 5.0 3.7 3.2 2.5 18.0 18.0 13.4 11.5
(5.0) (18.0)
6.0 5.1 5.0 3.7 3.2 6.0 18.4 18.0 13.4 11.5
7.5 5.3 5.0 3.7 3.2 7.5 19.0 18.0 13.4 11.5
10.0 5.5 5.0 3.7 3.2 10.0 19.9 18.0 13.4 11.5
12.5 5.7 5.0 3.7 3.2 12.5 20.6 18.0 13.4 11.5
15.5 5.7 5.0 3.7 3.2 15.5 20.6 18.0 13.4 11.5
-20.0 4.0 4.1 4.0 3.9 -20.0 16.0 16.1 16.0 15.5
-15.0 4.4 4.4 4.4 4.0 -15.0 17.4 17.5 17.3 16.0
-10.0 4.8 4.8 4.7 4.0 -10.0 19.2 19.2 18.6 16.0
-5.0 5.5 5.5 4.7 4.0 -5.0 21.7 21.7 18.6 16.0
0.0 6.1 6.1 4.7 4.0 0.0 24.3 24.3 18.6 16.0
50 200
(6.3) 2.5 6.3 6.3 4.7 4.0 (25.0) 2.5 25.0 25.0 18.6 16.0
6.0 6.5 6.3 4.7 4.0 6.0 25.6 25.0 18.6 16.0
7.5 6.6 6.3 4.7 4.0 7.5 26.4 25.0 18.6 16.0
10.0 7.0 6.3 4.7 4.0 10.0 27.6 25.0 18.6 16.0
12.5 7.2 6.3 4.7 4.0 12.5 28.6 25.0 18.6 16.0
15.5 7.2 6.3 4.7 4.0 15.5 28.6 25.0 18.6 16.0
-20.0 5.1 5.2 5.1 5.0 -20.0 20.2 20.3 20.2 19.6
-15.0 5.6 5.6 5.5 5.1 -15.0 21.9 22.0 21.8 20.2
-10.0 6.1 6.2 6.0 5.1 -10.0 24.2 24.2 23.5 20.2
-5.0 6.9 7.0 6.0 5.1 -5.0 27.3 27.4 23.5 20.2
0.0 7.8 7.8 6.0 5.1 0.0 30.6 30.6 23.5 20.2
63 250
(8.0) 2.5 8.0 8.0 6.0 5.1 (31.5) 2.5 31.5 31.5 23.5 20.2
6.0 8.2 8.0 6.0 5.1 6.0 32.3 31.5 23.5 20.2
7.5 8.4 8.0 6.0 5.1 7.5 33.2 31.5 23.5 20.2
10.0 8.8 8.0 6.0 5.1 10.0 34.8 31.5 23.5 20.2
12.5 9.2 8.0 6.0 5.1 12.5 36.1 31.5 23.5 20.2
15.5 9.2 8.0 6.0 5.1 15.5 36.1 31.5 23.5 20.2
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 178


9. Heating [All indoor units]
9-6. Heating capacity with PUHY,PURY-RP200-250YJM "COP priority mode"
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.0 1.0 1.0 0.9 -20.0 4.6 4.5 4.5 4.5
-15.0 1.2 1.2 1.1 1.1 -15.0 5.6 5.5 5.4 5.3
-10.0 1.4 1.4 1.3 1.3 -10.0 6.6 6.5 6.3 6.2
-5.0 1.6 1.6 1.5 1.3 -5.0 7.5 7.4 7.2 6.3
0.0 1.8 1.8 1.5 1.3 0.0 8.5 8.4 7.2 6.3
15 71
(1.9) 2.5 1.9 1.9 1.5 1.3 (9.0) 2.5 9.0 8.9 7.2 6.3
6.0 2.0 1.9 1.5 1.3 6.0 9.3 9.0 7.2 6.3
7.5 2.0 1.9 1.5 1.3 7.5 9.7 9.0 7.2 6.3
10.0 2.2 1.9 1.5 1.3 10.0 10.3 9.0 7.2 6.3
12.5 2.3 1.9 1.5 1.3 12.5 10.8 9.0 7.2 6.3
15.5 2.4 1.9 1.5 1.3 15.5 11.5 9.0 7.2 6.3
-20.0 1.3 1.3 1.3 1.2 -20.0 5.1 5.0 5.0 5.0
-15.0 1.6 1.5 1.5 1.5 -15.0 6.2 6.1 6.0 5.9
-10.0 1.8 1.8 1.7 1.7 -10.0 7.3 7.2 7.0 6.8
-5.0 2.1 2.1 2.0 1.8 -5.0 8.4 8.3 8.0 7.0
0.0 2.4 2.3 2.0 1.8 0.0 9.5 9.4 8.0 7.0
20 80
(2.5) 2.5 2.5 2.5 2.0 1.8 (10.0) 2.5 10.0 9.9 8.0 7.0
6.0 2.6 2.5 2.0 1.8 6.0 10.4 10.0 8.0 7.0
7.5 2.7 2.5 2.0 1.8 7.5 10.7 10.0 8.0 7.0
10.0 2.8 2.5 2.0 1.8 10.0 11.4 10.0 8.0 7.0
12.5 3.0 2.5 2.0 1.8 12.5 12.0 10.0 8.0 7.0
15.5 3.2 2.5 2.0 1.8 15.5 12.8 10.0 8.0 7.0
-20.0 1.6 1.6 1.6 1.6 -20.0 6.4 6.3 6.3 6.2
-15.0 2.0 2.0 1.9 1.9 -15.0 7.8 7.6 7.5 7.4
-10.0 2.3 2.3 2.2 2.2 -10.0 9.1 9.0 8.7 8.6
-5.0 2.7 2.6 2.6 2.2 -5.0 10.5 10.3 10.0 8.8
0.0 3.0 3.0 2.6 2.2 0.0 11.8 11.7 10.0 8.8
25 100
(3.2) 2.5 3.2 3.2 2.6 2.2 (12.5) 2.5 12.5 12.4 10.0 8.8
6.0 3.3 3.2 2.6 2.2 6.0 12.9 12.5 10.0 8.8
7.5 3.4 3.2 2.6 2.2 7.5 13.4 12.5 10.0 8.8
10.0 3.6 3.2 2.6 2.2 10.0 14.2 12.5 10.0 8.8
12.5 3.9 3.2 2.6 2.2 12.5 15.1 12.5 10.0 8.8
15.5 4.1 3.2 2.6 2.2 15.5 16.0 12.5 10.0 8.8
-20.0 2.0 2.0 2.0 2.0 -20.0 8.2 8.0 8.0 7.9
-15.0 2.5 2.4 2.4 2.4 -15.0 9.9 9.8 9.6 9.4
-10.0 2.9 2.9 2.8 2.7 -10.0 11.7 11.5 11.2 11.0
-5.0 3.3 3.3 3.2 2.8 -5.0 13.4 13.2 12.8 11.2
0.0 3.8 3.7 3.2 2.8 0.0 15.1 15.0 12.8 11.2
32 125
(4.0) 2.5 4.0 4.0 3.2 2.8 (16.0) 2.5 16.0 15.8 12.8 11.2
6.0 4.1 4.0 3.2 2.8 6.0 16.6 16.0 12.8 11.2
7.5 4.3 4.0 3.2 2.8 7.5 17.2 16.0 12.8 11.2
10.0 4.6 4.0 3.2 2.8 10.0 18.2 16.0 12.8 11.2
12.5 4.8 4.0 3.2 2.8 12.5 19.3 16.0 12.8 11.2
15.5 5.1 4.0 3.2 2.8 15.5 20.5 16.0 12.8 11.2
-20.0 2.6 2.5 2.5 2.5 -20.0 9.2 9.0 9.0 8.9
-15.0 3.1 3.1 3.0 3.0 -15.0 11.2 11.0 10.8 10.6
-10.0 3.6 3.6 3.5 3.4 -10.0 13.1 12.9 12.6 12.3
-5.0 4.2 4.1 4.0 3.5 -5.0 15.1 14.9 14.4 12.6
0.0 4.7 4.7 4.0 3.5 0.0 17.0 16.8 14.4 12.6
40 140
(5.0) 2.5 5.0 4.9 4.0 3.5 (18.0) 2.5 18.0 17.8 14.4 12.6
6.0 5.2 5.0 4.0 3.5 6.0 18.6 18.0 14.4 12.6
7.5 5.4 5.0 4.0 3.5 7.5 19.3 18.0 14.4 12.6
10.0 5.7 5.0 4.0 3.5 10.0 20.5 18.0 14.4 12.6
12.5 6.0 5.0 4.0 3.5 12.5 21.7 18.0 14.4 12.6
15.5 6.4 5.0 4.0 3.5 15.5 23.1 18.0 14.4 12.6
-20.0 3.2 3.2 3.2 3.1 -20.0 12.8 12.6 12.5 12.4
-15.0 3.9 3.8 3.8 3.7 -15.0 15.5 15.3 15.0 14.8
-10.0 4.6 4.5 4.4 4.3 -10.0 18.2 18.0 17.5 17.1
-5.0 5.3 5.2 5.0 4.4 -5.0 20.9 20.7 20.0 17.5
0.0 6.0 5.9 5.0 4.4 0.0 23.6 23.4 20.0 17.5
50 200
(6.3) 2.5 6.3 6.2 5.0 4.4 (25.0) 2.5 25.0 24.7 20.0 17.5
6.0 6.5 6.3 5.0 4.4 6.0 25.9 25.0 20.0 17.5
7.5 6.8 6.3 5.0 4.4 7.5 26.9 25.0 20.0 17.5
10.0 7.2 6.3 5.0 4.4 10.0 28.5 25.0 20.0 17.5
12.5 7.6 6.3 5.0 4.4 12.5 30.1 25.0 20.0 17.5
15.5 8.1 6.3 5.0 4.4 15.5 32.1 25.0 20.0 17.5
-20.0 4.1 4.0 4.0 4.0 -20.0 16.1 15.8 15.8 15.6
-15.0 5.0 4.9 4.8 4.7 -15.0 19.5 19.2 18.9 18.6
-10.0 5.8 5.7 5.6 5.5 -10.0 22.9 22.6 22.0 21.6
-5.0 6.7 6.6 6.4 5.6 -5.0 26.4 26.0 25.2 22.1
0.0 7.6 7.5 6.4 5.6 0.0 29.8 29.5 25.2 22.1
63 250
(8.0) 2.5 8.0 7.9 6.4 5.6 (31.5) 2.5 31.5 31.2 25.2 22.1
6.0 8.3 8.0 6.4 5.6 6.0 32.6 31.5 25.2 22.1
7.5 8.6 8.0 6.4 5.6 7.5 33.9 31.5 25.2 22.1
10.0 9.1 8.0 6.4 5.6 10.0 35.9 31.5 25.2 22.1
12.5 9.6 8.0 6.4 5.6 12.5 37.9 31.5 25.2 22.1
15.5 10.3 8.0 6.4 5.6 15.5 40.4 31.5 25.2 22.1
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 179


9. Heating [All indoor units]
9-7. Heating capacity with PUHY-RP300-400Y(S)JM,PURY-RP300YJM "COP priority
mode"
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 0.9 1.0 1.0 0.9 -20.0 4.5 4.5 4.6 4.4
-15.0 1.1 1.1 1.1 1.1 -15.0 5.4 5.4 5.4 5.2
-10.0 1.3 1.3 1.3 1.2 -10.0 6.3 6.2 6.2 5.8
-5.0 1.5 1.5 1.4 1.2 -5.0 7.2 7.1 6.7 5.8
0.0 1.7 1.7 1.4 1.2 0.0 8.1 8.0 6.7 5.8
15 71
(1.9) 2.5 1.8 1.8 1.4 1.2 (9.0) 2.5 8.6 8.4 6.7 5.8
6.0 1.9 1.9 1.4 1.2 6.0 9.2 9.0 6.7 5.8
7.5 2.0 1.9 1.4 1.2 7.5 9.5 9.0 6.7 5.8
10.0 2.1 1.9 1.4 1.2 10.0 9.9 9.0 6.7 5.8
12.5 2.2 1.9 1.4 1.2 12.5 10.3 9.0 6.7 5.8
15.5 2.2 1.9 1.4 1.2 15.5 10.3 9.0 6.7 5.8
-20.0 1.2 1.3 1.3 1.2 -20.0 5.0 5.0 5.1 4.9
-15.0 1.5 1.5 1.5 1.5 -15.0 6.0 6.0 6.0 5.8
-10.0 1.8 1.7 1.7 1.6 -10.0 7.0 6.9 6.8 6.4
-5.0 2.0 2.0 1.9 1.6 -5.0 8.0 7.9 7.4 6.4
0.0 2.3 2.2 1.9 1.6 0.0 9.0 8.9 7.5 6.4
20 80
(2.5) 2.5 2.4 2.3 1.9 1.6 (10.0) 2.5 9.5 9.3 7.5 6.4
6.0 2.6 2.5 1.9 1.6 6.0 10.2 10.0 7.5 6.4
7.5 2.6 2.5 1.9 1.6 7.5 10.5 10.0 7.5 6.4
10.0 2.8 2.5 1.9 1.6 10.0 11.0 10.0 7.5 6.4
12.5 2.9 2.5 1.9 1.6 12.5 11.5 10.0 7.5 6.4
15.5 2.9 2.5 1.9 1.6 15.5 11.5 10.0 7.5 6.4
-20.0 1.6 1.6 1.6 1.6 -20.0 6.2 6.3 6.4 6.1
-15.0 1.9 1.9 1.9 1.9 -15.0 7.5 7.5 7.5 7.3
-10.0 2.2 2.2 2.2 2.0 -10.0 8.8 8.7 8.6 8.0
-5.0 2.6 2.5 2.4 2.0 -5.0 10.0 9.9 9.3 8.0
0.0 2.9 2.8 2.4 2.0 0.0 11.3 11.1 9.3 8.0
25 100
(3.2) 2.5 3.1 3.0 2.4 2.0 (12.5) 2.5 11.9 11.7 9.3 8.0
6.0 3.3 3.2 2.4 2.0 6.0 12.8 12.5 9.3 8.0
7.5 3.4 3.2 2.4 2.0 7.5 13.2 12.5 9.3 8.0
10.0 3.5 3.2 2.4 2.0 10.0 13.8 12.5 9.3 8.0
12.5 3.7 3.2 2.4 2.0 12.5 14.3 12.5 9.3 8.0
15.5 3.7 3.2 2.4 2.0 15.5 14.3 12.5 9.3 8.0
-20.0 2.0 2.0 2.0 2.0 -20.0 8.0 8.0 8.2 7.8
-15.0 2.4 2.4 2.4 2.3 -15.0 9.6 9.6 9.6 9.3
-10.0 2.8 2.8 2.7 2.6 -10.0 11.2 11.1 10.9 10.2
-5.0 3.2 3.2 3.0 2.6 -5.0 12.8 12.6 11.9 10.2
0.0 3.6 3.5 3.0 2.6 0.0 14.4 14.2 11.9 10.2
32 125
(4.0) 2.5 3.8 3.7 3.0 2.6 (16.0) 2.5 15.3 14.9 11.9 10.2
6.0 4.1 4.0 3.0 2.6 6.0 16.4 16.0 11.9 10.2
7.5 4.2 4.0 3.0 2.6 7.5 16.9 16.0 11.9 10.2
10.0 4.4 4.0 3.0 2.6 10.0 17.7 16.0 11.9 10.2
12.5 4.6 4.0 3.0 2.6 12.5 18.3 16.0 11.9 10.2
15.5 4.6 4.0 3.0 2.6 15.5 18.3 16.0 12.0 10.2
-20.0 2.5 2.5 2.6 2.4 -20.0 9.0 9.1 9.2 8.8
-15.0 3.0 3.0 3.0 2.9 -15.0 10.8 10.8 10.8 10.5
-10.0 3.5 3.5 3.4 3.2 -10.0 12.6 12.5 12.3 11.5
-5.0 4.0 3.9 3.7 3.2 -5.0 14.4 14.2 13.4 11.5
0.0 4.5 4.4 3.7 3.2 0.0 16.3 15.9 13.4 11.5
40 140
(5.0) 2.5 4.8 4.7 3.7 3.2 (18.0) 2.5 17.2 16.8 13.4 11.5
6.0 5.1 5.0 3.7 3.2 6.0 18.4 18.0 13.4 11.5
7.5 5.3 5.0 3.7 3.2 7.5 19.0 18.0 13.4 11.5
10.0 5.5 5.0 3.7 3.2 10.0 19.9 18.0 13.4 11.5
12.5 5.7 5.0 3.7 3.2 12.5 20.6 18.0 13.4 11.5
15.5 5.7 5.0 3.7 3.2 15.5 20.6 18.0 13.4 11.5
-20.0 3.1 3.2 3.2 3.1 -20.0 12.5 12.6 12.8 12.2
-15.0 3.8 3.8 3.8 3.7 -15.0 15.0 15.0 15.0 14.6
-10.0 4.4 4.4 4.3 4.0 -10.0 17.5 17.4 17.1 16.0
-5.0 5.1 5.0 4.7 4.0 -5.0 20.0 19.7 18.6 16.0
0.0 5.7 5.6 4.7 4.0 0.0 22.6 22.1 18.6 16.0
50 200
(6.3) 2.5 6.0 5.9 4.7 4.0 (25.0) 2.5 23.8 23.3 18.6 16.0
6.0 6.5 6.3 4.7 4.0 6.0 25.6 25.0 18.6 16.0
7.5 6.6 6.3 4.7 4.0 7.5 26.4 25.0 18.7 16.0
10.0 7.0 6.3 4.7 4.0 10.0 27.6 25.0 18.7 16.0
12.5 7.2 6.3 4.7 4.0 12.5 28.6 25.0 18.7 16.0
15.5 7.2 6.3 4.7 4.0 15.5 28.6 25.0 18.7 16.0
-20.0 4.0 4.0 4.1 3.9 -20.0 15.7 15.8 16.1 15.4
-15.0 4.8 4.8 4.8 4.7 -15.0 18.9 18.9 18.8 18.4
-10.0 5.6 5.6 5.5 5.1 -10.0 22.1 21.9 21.5 20.2
-5.0 6.4 6.3 6.0 5.1 -5.0 25.3 24.9 23.5 20.2
0.0 7.2 7.1 6.0 5.1 0.0 28.4 27.9 23.5 20.2
63 250
(8.0) 2.5 7.6 7.5 6.0 5.1 (31.5) 2.5 30.0 29.4 23.5 20.2
6.0 8.2 8.0 6.0 5.1 6.0 32.3 31.5 23.5 20.2
7.5 8.4 8.0 6.0 5.1 7.5 33.2 31.5 23.5 20.2
10.0 8.8 8.0 6.0 5.1 10.0 34.8 31.5 23.5 20.2
12.5 9.2 8.0 6.0 5.1 12.5 36.1 31.5 23.5 20.2
15.5 9.2 8.0 6.0 5.1 15.5 36.1 31.5 23.5 20.2
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 180


9. Heating [All indoor units]
9-8. Heating capacity with PUHY-RP450-650YSJM "COP priority mode"
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.0 1.0 1.0 0.9 -20.0 4.8 4.6 4.6 4.5
-15.0 1.2 1.2 1.1 1.1 -15.0 5.6 5.5 5.3 5.2
-10.0 1.4 1.3 1.3 1.3 -10.0 6.5 6.4 6.1 6.0
-5.0 1.6 1.5 1.5 1.3 -5.0 7.4 7.2 6.9 6.4
0.0 1.7 1.7 1.5 1.3 0.0 8.2 8.1 7.1 6.4
15 71
(1.9) 2.5 1.8 1.8 1.5 1.3 (9.0) 2.5 8.7 8.5 7.1 6.4
6.0 2.0 1.9 1.5 1.3 6.0 9.3 9.0 7.1 6.4
7.5 2.0 1.9 1.5 1.3 7.5 9.5 9.0 7.1 6.4
10.0 2.1 1.9 1.5 1.3 10.0 10.0 9.0 7.1 6.4
12.5 2.2 1.9 1.5 1.3 12.5 10.4 9.0 7.1 6.4
15.5 2.2 1.9 1.5 1.3 15.5 10.4 9.0 7.1 6.4
-20.0 1.3 1.3 1.3 1.2 -20.0 5.3 5.1 5.1 5.0
-15.0 1.6 1.5 1.5 1.5 -15.0 6.3 6.1 5.9 5.8
-10.0 1.8 1.8 1.7 1.7 -10.0 7.2 7.1 6.8 6.6
-5.0 2.0 2.0 1.9 1.8 -5.0 8.2 8.0 7.7 7.1
0.0 2.3 2.2 2.0 1.8 0.0 9.1 9.0 7.9 7.1
20 80
(2.5) 2.5 2.4 2.4 2.0 1.8 (10.0) 2.5 9.6 9.5 7.9 7.1
6.0 2.6 2.5 2.0 1.8 6.0 10.3 10.0 7.9 7.1
7.5 2.6 2.5 2.0 1.8 7.5 10.6 10.0 7.9 7.1
10.0 2.8 2.5 2.0 1.8 10.0 11.1 10.0 7.9 7.1
12.5 2.9 2.5 2.0 1.8 12.5 11.5 10.0 7.9 7.1
15.5 2.9 2.5 2.0 1.8 15.5 11.6 10.0 7.9 7.1
-20.0 1.7 1.6 1.6 1.6 -20.0 6.6 6.4 6.4 6.2
-15.0 2.0 2.0 1.9 1.9 -15.0 7.8 7.6 7.4 7.3
-10.0 2.3 2.3 2.2 2.1 -10.0 9.0 8.8 8.5 8.3
-5.0 2.6 2.6 2.4 2.3 -5.0 10.2 10.0 9.6 8.9
0.0 2.9 2.9 2.5 2.3 0.0 11.4 11.2 9.9 8.9
25 100
(3.2) 2.5 3.1 3.0 2.5 2.3 (12.5) 2.5 12.0 11.8 9.9 8.9
6.0 3.3 3.2 2.5 2.3 6.0 12.9 12.5 9.9 8.9
7.5 3.4 3.2 2.5 2.3 7.5 13.2 12.5 9.9 8.9
10.0 3.5 3.2 2.5 2.3 10.0 13.8 12.5 9.9 8.9
12.5 3.7 3.2 2.5 2.3 12.5 14.4 12.5 9.9 8.9
15.5 3.7 3.2 2.5 2.3 15.5 14.5 12.5 9.9 8.9
-20.0 2.1 2.1 2.0 2.0 -20.0 8.5 8.2 8.1 8.0
-15.0 2.5 2.4 2.4 2.3 -15.0 10.0 9.8 9.5 9.3
-10.0 2.9 2.8 2.7 2.6 -10.0 11.5 11.3 10.9 10.6
-5.0 3.3 3.2 3.1 2.8 -5.0 13.1 12.8 12.2 11.3
0.0 3.7 3.6 3.2 2.8 0.0 14.6 14.4 12.7 11.3
32 125
(4.0) 2.5 3.8 3.8 3.2 2.8 (16.0) 2.5 15.4 15.1 12.7 11.3
6.0 4.1 4.0 3.2 2.8 6.0 16.5 16.0 12.7 11.3
7.5 4.2 4.0 3.2 2.8 7.5 16.9 16.0 12.7 11.3
10.0 4.4 4.0 3.2 2.8 10.0 17.7 16.0 12.7 11.3
12.5 4.6 4.0 3.2 2.8 12.5 18.5 16.0 12.7 11.3
15.5 4.6 4.0 3.2 2.8 15.5 18.5 16.0 12.7 11.3
-20.0 2.6 2.6 2.5 2.5 -20.0 9.5 9.3 9.1 9.0
-15.0 3.1 3.1 3.0 2.9 -15.0 11.3 11.0 10.7 10.4
-10.0 3.6 3.5 3.4 3.3 -10.0 13.0 12.7 12.2 11.9
-5.0 4.1 4.0 3.8 3.5 -5.0 14.7 14.4 13.8 12.8
0.0 4.6 4.5 4.0 3.5 0.0 16.4 16.1 14.3 12.8
40 140
(5.0) 2.5 4.8 4.7 4.0 3.5 (18.0) 2.5 17.3 17.0 14.3 12.8
6.0 5.1 5.0 4.0 3.5 6.0 18.5 18.0 14.3 12.8
7.5 5.3 5.0 4.0 3.5 7.5 19.0 18.0 14.3 12.8
10.0 5.5 5.0 4.0 3.5 10.0 19.9 18.0 14.3 12.8
12.5 5.8 5.0 4.0 3.5 12.5 20.8 18.0 14.3 12.8
15.5 5.8 5.0 4.0 3.5 15.5 20.8 18.0 14.3 12.8
-20.0 3.3 3.2 3.2 3.1 -20.0 13.2 12.9 12.7 12.5
-15.0 3.9 3.8 3.7 3.7 -15.0 15.6 15.3 14.9 14.5
-10.0 4.5 4.4 4.3 4.2 -10.0 18.0 17.6 17.0 16.5
-5.0 5.1 5.0 4.8 4.5 -5.0 20.4 20.0 19.1 17.7
0.0 5.8 5.7 5.0 4.5 0.0 22.8 22.4 19.8 17.7
50 200
(6.3) 2.5 6.1 6.0 5.0 4.5 (25.0) 2.5 24.0 23.6 19.8 17.7
6.0 6.5 6.3 5.0 4.5 6.0 25.7 25.0 19.8 17.7
7.5 6.7 6.3 5.0 4.5 7.5 26.4 25.0 19.8 17.7
10.0 7.0 6.3 5.0 4.5 10.0 27.6 25.0 19.8 17.7
12.5 7.3 6.3 5.0 4.5 12.5 28.9 25.0 19.8 17.7
15.5 7.3 6.3 5.0 4.5 15.5 28.9 25.0 19.8 17.7
-20.0 4.2 4.1 4.1 4.0 -20.0 16.7 16.2 16.0 15.7
-15.0 5.0 4.9 4.8 4.6 -15.0 19.7 19.2 18.7 18.3
-10.0 5.8 5.6 5.4 5.3 -10.0 22.7 22.2 21.4 20.8
-5.0 6.5 6.4 6.1 5.7 -5.0 25.7 25.2 24.1 22.3
0.0 7.3 7.2 6.3 5.7 0.0 28.8 28.3 25.0 22.3
63 250
(8.0) 2.5 7.7 7.6 6.3 5.7 (31.5) 2.5 30.3 29.8 25.0 22.3
6.0 8.2 8.0 6.3 5.7 6.0 32.4 31.5 25.0 22.3
7.5 8.5 8.0 6.3 5.7 7.5 33.3 31.5 25.0 22.3
10.0 8.8 8.0 6.3 5.7 10.0 34.8 31.5 25.0 22.3
12.5 9.2 8.0 6.3 5.7 12.5 36.4 31.5 25.0 22.3
15.5 9.3 8.0 6.3 5.7 15.5 36.5 31.5 24.9 22.3
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 181


9. Heating [All indoor units]
9-9. Heating capacity with PUHY-RP700-800YSJM "COP priority mode"
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.0 1.0 1.0 0.9 -20.0 4.6 4.5 4.5 4.4
-15.0 1.2 1.1 1.1 1.1 -15.0 5.5 5.4 5.3 5.2
-10.0 1.3 1.3 1.3 1.3 -10.0 6.4 6.3 6.1 6.0
-5.0 1.5 1.5 1.5 1.4 -5.0 7.3 7.1 6.9 6.6
0.0 1.7 1.7 1.5 1.4 0.0 8.2 8.0 7.1 6.6
15 71
(1.9) 2.5 1.8 1.8 1.5 1.4 (9.0) 2.5 8.6 8.4 7.1 6.6
6.0 1.9 1.9 1.5 1.4 6.0 9.2 9.0 7.1 6.6
7.5 2.0 1.9 1.5 1.4 7.5 9.5 9.0 7.1 6.6
10.0 2.1 1.9 1.5 1.4 10.0 9.9 9.0 7.1 6.6
12.5 2.2 1.9 1.5 1.4 12.5 10.4 9.0 7.1 6.6
15.5 2.2 1.9 1.5 1.4 15.5 10.4 9.0 7.1 6.6
-20.0 1.3 1.3 1.3 1.2 -20.0 5.1 5.0 5.0 4.9
-15.0 1.5 1.5 1.5 1.5 -15.0 6.1 6.0 5.9 5.8
-10.0 1.8 1.7 1.7 1.7 -10.0 7.1 7.0 6.8 6.7
-5.0 2.0 2.0 1.9 1.8 -5.0 8.1 7.9 7.7 7.3
0.0 2.3 2.2 2.0 1.8 0.0 9.1 8.9 7.9 7.3
20 80
(2.5) 2.5 2.4 2.3 2.0 1.8 (10.0) 2.5 9.6 9.4 7.9 7.3
6.0 2.6 2.5 2.0 1.8 6.0 10.3 10.0 7.9 7.3
7.5 2.6 2.5 2.0 1.8 7.5 10.6 10.0 7.9 7.3
10.0 2.8 2.5 2.0 1.8 10.0 11.1 10.0 7.9 7.3
12.5 2.9 2.5 2.0 1.8 12.5 11.5 10.0 7.9 7.3
15.5 2.9 2.5 2.0 1.8 15.5 11.6 10.0 7.9 7.3
-20.0 1.6 1.6 1.6 1.6 -20.0 6.4 6.3 6.3 6.2
-15.0 1.9 1.9 1.9 1.9 -15.0 7.6 7.5 7.4 7.3
-10.0 2.3 2.2 2.2 2.1 -10.0 8.9 8.7 8.5 8.3
-5.0 2.6 2.5 2.5 2.4 -5.0 10.1 9.9 9.6 9.2
0.0 2.9 2.8 2.5 2.4 0.0 11.3 11.1 9.9 9.2
25 100
(3.2) 2.5 3.1 3.0 2.5 2.4 (12.5) 2.5 12.0 11.7 9.9 9.2
6.0 3.3 3.2 2.5 2.3 6.0 12.8 12.5 9.9 9.2
7.5 3.4 3.2 2.5 2.3 7.5 13.2 12.5 9.9 9.2
10.0 3.5 3.2 2.5 2.3 10.0 13.8 12.5 9.9 9.2
12.5 3.7 3.2 2.5 2.3 12.5 14.4 12.5 9.9 9.2
15.5 3.7 3.2 2.5 2.3 15.5 14.4 12.5 9.9 9.2
-20.0 2.0 2.0 2.0 2.0 -20.0 8.2 8.0 8.1 7.9
-15.0 2.4 2.4 2.4 2.3 -15.0 9.7 9.6 9.5 9.3
-10.0 2.8 2.8 2.7 2.7 -10.0 11.3 11.1 10.9 10.7
-5.0 3.2 3.2 3.1 2.9 -5.0 12.9 12.7 12.3 11.8
0.0 3.6 3.6 3.2 2.9 0.0 14.5 14.2 12.7 11.8
32 125
(4.0) 2.5 3.8 3.8 3.2 2.9 (16.0) 2.5 15.3 15.0 12.7 11.8
6.0 4.1 4.0 3.2 2.9 6.0 16.4 16.0 12.7 11.7
7.5 4.2 4.0 3.2 2.9 7.5 16.9 16.0 12.7 11.7
10.0 4.4 4.0 3.2 2.9 10.0 17.7 16.0 12.7 11.7
12.5 4.6 4.0 3.2 2.9 12.5 18.4 16.0 12.7 11.7
15.5 4.6 4.0 3.2 2.9 15.5 18.5 16.0 12.7 11.7
-20.0 2.6 2.5 2.5 2.5 -20.0 9.2 9.1 9.1 8.9
-15.0 3.0 3.0 3.0 2.9 -15.0 11.0 10.8 10.7 10.4
-10.0 3.5 3.5 3.4 3.3 -10.0 12.7 12.5 12.2 12.0
-5.0 4.0 4.0 3.8 3.7 -5.0 14.5 14.3 13.8 13.2
0.0 4.5 4.5 4.0 3.7 0.0 16.3 16.0 14.3 13.2
40 140
(5.0) 2.5 4.8 4.7 4.0 3.7 (18.0) 2.5 17.2 16.9 14.3 13.2
6.0 5.1 5.0 4.0 3.7 6.0 18.5 18.0 14.3 13.2
7.5 5.3 5.0 4.0 3.7 7.5 19.0 18.0 14.3 13.2
10.0 5.5 5.0 4.0 3.7 10.0 19.9 18.0 14.3 13.2
12.5 5.8 5.0 4.0 3.7 12.5 20.7 18.0 14.3 13.2
15.5 5.8 5.0 4.0 3.7 15.5 20.8 18.0 14.3 13.2
-20.0 3.2 3.2 3.2 3.1 -20.0 12.8 12.6 12.6 12.4
-15.0 3.8 3.8 3.7 3.7 -15.0 15.2 15.0 14.8 14.5
-10.0 4.5 4.4 4.3 4.2 -10.0 17.7 17.4 17.0 16.6
-5.0 5.1 5.0 4.8 4.6 -5.0 20.2 19.8 19.2 18.4
0.0 5.7 5.6 5.0 4.6 0.0 22.7 22.3 19.8 18.4
50 200
(6.3) 2.5 6.0 5.9 5.0 4.6 (25.0) 2.5 23.9 23.5 19.8 18.4
6.0 6.5 6.3 5.0 4.6 6.0 25.6 25.0 19.8 18.4
7.5 6.7 6.3 5.0 4.6 7.5 26.4 25.0 19.8 18.4
10.0 7.0 6.3 5.0 4.6 10.0 27.6 25.0 19.8 18.4
12.5 7.3 6.3 5.0 4.6 12.5 28.8 25.0 19.8 18.4
15.5 7.3 6.3 5.0 4.6 15.5 28.9 25.0 19.8 18.3
-20.0 4.1 4.0 4.0 4.0 -20.0 16.1 15.8 15.9 15.6
-15.0 4.9 4.8 4.7 4.6 -15.0 19.2 18.9 18.6 18.3
-10.0 5.7 5.6 5.4 5.3 -10.0 22.3 21.9 21.4 21.0
-5.0 6.5 6.3 6.1 5.9 -5.0 25.4 25.0 24.2 23.1
0.0 7.3 7.1 6.3 5.9 0.0 28.6 28.0 25.0 23.1
63 250
(8.0) 2.5 7.7 7.5 6.3 5.9 (31.5) 2.5 30.1 29.6 25.0 23.1
6.0 8.2 8.0 6.3 5.9 6.0 32.3 31.5 25.0 23.1
7.5 8.4 8.0 6.3 5.9 7.5 33.3 31.5 25.0 23.1
10.0 8.8 8.0 6.3 5.9 10.0 34.8 31.5 25.0 23.1
12.5 9.2 8.0 6.3 5.9 12.5 36.3 31.5 25.0 23.1
15.5 9.2 8.0 6.3 5.9 15.5 36.4 31.5 25.0 23.1
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 182


9. Heating [All indoor units]
9-10. Heating capacity with PUHY-RP850-900YSJM "COP priority mode"
All Indoor units SHC:Sensible Heat Capacity(kW) All Indoor units SHC:Sensible Heat Capacity(kW)
Model Outdoor Indoor air temp. Model Outdoor Indoor air temp.
size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B. size air temp. 15C D.B. 20C D.B. 25C D.B. 27C D.B.
(Rated kW) C W.B. SHC SHC SHC SHC (Rated kW) C W.B. SHC SHC SHC SHC
-20.0 1.0 1.0 1.0 0.9 -20.0 4.8 4.6 4.6 4.5
-15.0 1.2 1.2 1.1 1.1 -15.0 5.6 5.5 5.3 5.2
-10.0 1.4 1.3 1.3 1.3 -10.0 6.5 6.4 6.1 6.0
-5.0 1.6 1.5 1.5 1.3 -5.0 7.4 7.2 6.9 6.4
0.0 1.7 1.7 1.5 1.3 0.0 8.2 8.1 7.1 6.4
15 71
(1.9) 2.5 1.8 1.8 1.5 1.3 (9.0) 2.5 8.7 8.5 7.1 6.4
6.0 2.0 1.9 1.5 1.3 6.0 9.3 9.0 7.1 6.4
7.5 2.0 1.9 1.5 1.3 7.5 9.5 9.0 7.1 6.4
10.0 2.1 1.9 1.5 1.3 10.0 10.0 9.0 7.1 6.4
12.5 2.2 1.9 1.5 1.3 12.5 10.4 9.0 7.1 6.4
15.5 2.2 1.9 1.5 1.3 15.5 10.4 9.0 7.1 6.4
-20.0 1.3 1.3 1.3 1.2 -20.0 5.3 5.1 5.1 5.0
-15.0 1.6 1.5 1.5 1.5 -15.0 6.3 6.1 5.9 5.8
-10.0 1.8 1.8 1.7 1.7 -10.0 7.2 7.1 6.8 6.6
-5.0 2.0 2.0 1.9 1.8 -5.0 8.2 8.0 7.7 7.1
0.0 2.3 2.2 2.0 1.8 0.0 9.1 9.0 7.9 7.1
20 80
(2.5) 2.5 2.4 2.4 2.0 1.8 (10.0) 2.5 9.6 9.5 7.9 7.1
6.0 2.6 2.5 2.0 1.8 6.0 10.3 10.0 7.9 7.1
7.5 2.6 2.5 2.0 1.8 7.5 10.6 10.0 7.9 7.1
10.0 2.8 2.5 2.0 1.8 10.0 11.1 10.0 7.9 7.1
12.5 2.9 2.5 2.0 1.8 12.5 11.5 10.0 7.9 7.1
15.5 2.9 2.5 2.0 1.8 15.5 11.6 10.0 7.9 7.1
-20.0 1.7 1.6 1.6 1.6 -20.0 6.6 6.4 6.4 6.2
-15.0 2.0 2.0 1.9 1.9 -15.0 7.8 7.6 7.4 7.3
-10.0 2.3 2.3 2.2 2.1 -10.0 9.0 8.8 8.5 8.3
-5.0 2.6 2.6 2.4 2.3 -5.0 10.2 10.0 9.6 8.9
0.0 2.9 2.9 2.5 2.3 0.0 11.4 11.2 9.9 8.9
25 100
(3.2) 2.5 3.1 3.0 2.5 2.3 (12.5) 2.5 12.0 11.8 9.9 8.9
6.0 3.3 3.2 2.5 2.3 6.0 12.9 12.5 9.9 8.9
7.5 3.4 3.2 2.5 2.3 7.5 13.2 12.5 9.9 8.9
10.0 3.5 3.2 2.5 2.3 10.0 13.8 12.5 9.9 8.9
12.5 3.7 3.2 2.5 2.3 12.5 14.4 12.5 9.9 8.9
15.5 3.7 3.2 2.5 2.3 15.5 14.5 12.5 9.9 8.9
-20.0 2.1 2.1 2.0 2.0 -20.0 8.5 8.2 8.1 8.0
-15.0 2.5 2.4 2.4 2.3 -15.0 10.0 9.8 9.5 9.3
-10.0 2.9 2.8 2.7 2.6 -10.0 11.5 11.3 10.9 10.6
-5.0 3.3 3.2 3.1 2.8 -5.0 13.1 12.8 12.2 11.3
0.0 3.7 3.6 3.2 2.8 0.0 14.6 14.4 12.7 11.3
32 125
(4.0) 2.5 3.8 3.8 3.2 2.8 (16.0) 2.5 15.4 15.1 12.7 11.3
6.0 4.1 4.0 3.2 2.8 6.0 16.5 16.0 12.7 11.3
7.5 4.2 4.0 3.2 2.8 7.5 16.9 16.0 12.7 11.3
10.0 4.4 4.0 3.2 2.8 10.0 17.7 16.0 12.7 11.3
12.5 4.6 4.0 3.2 2.8 12.5 18.5 16.0 12.7 11.3
15.5 4.6 4.0 3.2 2.8 15.5 18.5 16.0 12.7 11.3
-20.0 2.6 2.6 2.5 2.5 -20.0 9.5 9.3 9.1 9.0
-15.0 3.1 3.1 3.0 2.9 -15.0 11.3 11.0 10.7 10.4
-10.0 3.6 3.5 3.4 3.3 -10.0 13.0 12.7 12.2 11.9
-5.0 4.1 4.0 3.8 3.5 -5.0 14.7 14.4 13.8 12.8
0.0 4.6 4.5 4.0 3.5 0.0 16.4 16.1 14.3 12.8
40 140
(5.0) 2.5 4.8 4.7 4.0 3.5 (18.0) 2.5 17.3 17.0 14.3 12.8
6.0 5.1 5.0 4.0 3.5 6.0 18.5 18.0 14.3 12.8
7.5 5.3 5.0 4.0 3.5 7.5 19.0 18.0 14.3 12.8
10.0 5.5 5.0 4.0 3.5 10.0 19.9 18.0 14.3 12.8
12.5 5.8 5.0 4.0 3.5 12.5 20.8 18.0 14.3 12.8
15.5 5.8 5.0 4.0 3.5 15.5 20.8 18.0 14.3 12.8
-20.0 3.3 3.2 3.2 3.1 -20.0 13.2 12.9 12.7 12.5
-15.0 3.9 3.8 3.7 3.7 -15.0 15.6 15.3 14.9 14.5
-10.0 4.5 4.4 4.3 4.2 -10.0 18.0 17.6 17.0 16.5
-5.0 5.1 5.0 4.8 4.5 -5.0 20.4 20.0 19.1 17.7
0.0 5.8 5.7 5.0 4.5 0.0 22.8 22.4 19.8 17.7
50 200
(6.3) 2.5 6.1 6.0 5.0 4.5 (25.0) 2.5 24.0 23.6 19.8 17.7
6.0 6.5 6.3 5.0 4.5 6.0 25.7 25.0 19.8 17.7
7.5 6.7 6.3 5.0 4.5 7.5 26.4 25.0 19.8 17.7
10.0 7.0 6.3 5.0 4.5 10.0 27.6 25.0 19.8 17.7
12.5 7.3 6.3 5.0 4.5 12.5 28.9 25.0 19.8 17.7
15.5 7.3 6.3 5.0 4.5 15.5 28.9 25.0 19.8 17.7
-20.0 4.2 4.1 4.1 4.0 -20.0 16.7 16.2 16.0 15.7
-15.0 5.0 4.9 4.8 4.6 -15.0 19.7 19.2 18.7 18.3
-10.0 5.8 5.6 5.4 5.3 -10.0 22.7 22.2 21.4 20.8
-5.0 6.5 6.4 6.1 5.7 -5.0 25.7 25.2 24.1 22.3
0.0 7.3 7.2 6.3 5.7 0.0 28.8 28.3 25.0 22.3
63 250
(8.0) 2.5 7.7 7.6 6.3 5.7 (31.5) 2.5 30.3 29.8 25.0 22.3
6.0 8.2 8.0 6.3 5.7 6.0 32.4 31.5 25.0 22.3
7.5 8.5 8.0 6.3 5.7 7.5 33.3 31.5 25.0 22.3
10.0 8.8 8.0 6.3 5.7 10.0 34.8 31.5 25.0 22.3
12.5 9.2 8.0 6.3 5.7 12.5 36.4 31.5 25.0 22.3
15.5 9.3 8.0 6.3 5.7 15.5 36.5 31.5 24.9 22.3
kcal/h=kW x 860 , BTU/h = kW x 3,412 kcal/h=kW x 860 , BTU/h = kW x 3,412

INDOOR UNITS 183


10. Cooling [Ceiling concealed (Fresh air intake)]
10-1. Cooling capacity
10. Cooling [Ceiling concealed (Fresh air intake)]

PEFY-P80VMH-E-F CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)


Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
70 21 4.4 3.0 5.3 2.9 - - - - - - - - - - - - - -
73 23 4.4 3.4 5.3 3.3 6.5 3.0 - - - - - - - - - - - -
77 25 4.4 3.8 5.2 3.7 6.4 3.4 - - - - - - - - - - - -
81 27 - - 5.2 4.0 6.4 3.7 7.5 3.3 - - - - - - - - - -
84 29 - - - - 6.4 4.1 7.5 3.7 8.5 3.2 - - - - - - - -
88 31 - - - - 6.3 4.5 7.4 4.0 8.4 3.5 9.1 3.1 - - - - - -
91 33 - - - - - - 7.3 4.4 8.3 3.8 9.0 3.5 9.6 3.0 - - - -
95 35 - - - - - - 7.2 4.7 8.2 4.2 8.9 3.8 9.5 3.3 - - - -
99 37 - - - - - - - - 8.1 4.5 8.8 4.1 9.4 3.7 9.9 3.2 - -
104 40 - - - - - - - - 8.0 5.0 8.6 4.6 9.1 4.1 9.7 3.7 10.5 2.9

PEFY-P140VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
70 21 7.8 5.6 9.4 5.3 - - - - - - - - - - - - - -
73 23 7.8 6.3 9.3 6.0 11.5 5.4 - - - - - - - - - - - -
77 25 7.8 7.1 9.3 6.8 11.5 6.1 - - - - - - - - - - - -
81 27 - - 9.3 7.5 11.4 6.8 13.4 6.0 - - - - - - - - - -
84 29 - - - - 11.3 7.5 13.3 6.7 15.2 5.6 - - - - - - - -
88 31 - - - - 11.2 8.2 13.2 7.3 15.0 6.3 16.2 5.5 - - - - - -
91 33 - - - - - - 13.0 8.0 14.8 7.0 16.0 6.2 17.1 5.3 - - - -
95 35 - - - - - - 12.9 8.7 14.6 7.6 15.8 6.8 16.9 6.0 - - - -
99 37 - - - - - - - - 14.5 8.3 15.6 7.5 16.6 6.6 17.7 5.7 - -
104 40 - - - - - - - - 14.2 9.3 15.2 8.5 16.3 7.6 17.3 6.7 18.7 5.3

PEFY-P200VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
70 21 10.9 7.9 13.1 7.5 - - - - - - - - - - - - - -
73 23 11.0 9.0 13.1 8.5 16.1 7.6 - - - - - - - - - - - -
77 25 11.0 10.1 13.0 9.6 16.0 8.6 - - - - - - - - - - - -
81 27 - - 13.0 10.7 15.9 9.7 18.8 8.4 - - - - - - - - - -
84 29 - - - - 15.8 10.7 18.6 9.4 21.2 7.9 - - - - - - - -
88 31 - - - - 15.7 11.7 18.4 10.4 21.0 8.9 22.6 7.7 - - - - - -
91 33 - - - - - - 18.2 11.4 20.7 9.8 22.4 8.7 23.9 7.5 - - - -
95 35 - - - - - - 18.0 12.4 20.5 10.8 22.1 9.6 23.6 8.4 - - - -
99 37 - - - - - - - - 20.2 11.8 21.8 10.6 23.3 9.4 24.7 8.1 - -
104 40 - - - - - - - - 19.8 13.2 21.3 12.0 22.8 10.8 24.2 9.5 26.2 7.47

PEFY-P250VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
70 21 13.7 9.9 16.4 9.3 - - - - - - - - - - - - - -
73 23 13.7 11.3 16.3 10.7 20.2 9.5 - - - - - - - - - - - -
77 25 13.7 12.6 16.3 12.0 20.1 10.8 - - - - - - - - - - - -
81 27 - - 16.2 13.3 19.9 12.1 23.4 10.5 - - - - - - - - - -
84 29 - - - - 19.8 13.4 23.2 11.7 26.5 9.8 - - - - - - - -
88 31 - - - - 19.6 14.7 23.0 13.0 26.2 11.1 28.3 9.7 - - - - - -
91 33 - - - - - - 22.8 14.2 25.9 12.3 28.0 10.9 29.9 9.3 - - - -
95 35 - - - - - - 22.5 15.5 25.6 13.5 27.6 12.1 29.5 10.5 - - - -
99 37 - - - - - - - - 25.3 14.7 27.2 13.3 29.1 11.7 30.9 10.1 - -
104 40 - - - - - - - - 24.8 16.5 26.6 15.0 28.4 13.5 30.2 11.9 32.7 9.34
There are times when the cooling capacity is lowered to protect the compressor in cases where the outdoor air temperature exceeds 40C (104F)

INDOOR UNITS 184


10. Cooling [Ceiling concealed (Fresh air intake)]
10-2. Outlet air temp. cooled
PEFY-P80VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B.
70 21 5.1 5.0 5.6 5.6 - - - - - - - - - - - - - -
73 23 5.1 5.0 5.7 5.6 7.0 7.0 - - - - - - - - - - - -
77 25 5.1 5.0 5.7 5.7 7.1 7.1 - - - - - - - - - - - -
81 27 - - 5.8 5.7 7.2 7.2 9.2 9.2 - - - - - - - - - -
84 29 - - - - 7.4 7.3 9.4 9.4 12.0 12.0 - - - - - - - -
88 31 - - - - 7.5 7.4 9.6 9.6 12.2 12.2 14.2 14.2 - - - - - -
91 33 - - - - - - 9.8 9.7 12.4 12.4 14.4 14.4 16.6 16.6 - - - -
95 35 - - - - - - 10.0 9.9 12.6 12.6 14.6 14.6 16.8 16.8 - - - -
99 37 - - - - - - - - 12.8 12.8 14.9 14.8 17.1 17.1 19.5 19.5 - -
104 40 - - - - - - - - 13.2 13.1 15.3 15.2 17.5 17.4 19.9 19.8 23.7 23.7

PEFY-P140VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B.
70 21 6.3 6.3 7.1 7.0 - - - - - - - - - - - - - -
73 23 6.3 6.3 7.1 7.1 8.7 8.7 - - - - - - - - - - - -
77 25 6.4 6.3 7.2 7.1 8.8 8.8 - - - - - - - - - - - -
81 27 - - 7.2 7.1 8.9 8.9 11.1 11.1 - - - - - - - - - -
84 29 - - - - 9.0 9.0 11.2 11.2 13.9 13.9 - - - - - - - -
88 31 - - - - 9.1 9.0 11.4 11.3 14.0 14.0 16.1 16.1 - - - - - -
91 33 - - - - - - 11.5 11.5 14.2 14.2 16.2 16.2 18.4 18.4 - - - -
95 35 - - - - - - 11.7 11.6 14.4 14.4 16.4 16.4 18.6 18.6 - - - -
99 37 - - - - - - - - 14.6 14.5 16.7 16.6 18.8 18.8 21.2 21.1 - -
104 40 - - - - - - - - 14.9 14.8 17.0 16.9 19.2 19.1 21.5 21.5 25.2 25.2

PEFY-P200VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B.
70 21 7.6 7.2 8.3 8.2 - - - - - - - - - - - - - -
73 23 7.7 7.2 8.5 8.2 10.0 10.0 - - - - - - - - - - - -
77 25 7.8 7.2 8.6 8.2 10.3 10.1 - - - - - - - - - - - -
81 27 - - 8.8 8.2 10.5 10.1 12.5 12.4 - - - - - - - - - -
84 29 - - - - 10.7 10.2 12.8 12.6 15.3 15.3 - - - - - - - -
88 31 - - - - 10.9 10.3 13.0 12.7 15.6 15.4 17.5 17.5 - - - - - -
91 33 - - - - - - 13.3 12.8 15.9 15.6 17.7 17.6 19.8 19.8 - - - -
95 35 - - - - - - 13.6 12.9 16.1 15.7 18.1 17.8 20.1 20.0 - - - -
99 37 - - - - - - - - 16.4 15.9 18.4 17.9 20.4 20.1 22.6 22.4 - -
104 40 - - - - - - - - 16.9 16.1 18.8 18.2 20.9 20.4 23.1 22.7 26.5 26.3

PEFY-P250VMH-E-F
Outdoor 59F W.B. 63F W.B. 68FW.B. 73F W.B. 79F W.B. 82F W.B. 86F W.B. 90F W.B. 95F W.B.
air temp. 15C W.B. 17C W.B. 20C W.B. 23C W.B. 26C W.B. 28C W.B. 30C W.B. 32C W.B. 35C W.B.
F D.B. C D.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B. C D.B. C W.B.
70 21 7.6 7.2 8.3 8.2 - - - - - - - - - - - - - -
73 23 7.7 7.2 8.5 8.2 10.0 10.0 - - - - - - - - - - - -
77 25 7.8 7.2 8.6 8.2 10.3 10.1 - - - - - - - - - - - -
81 27 - - 8.8 8.2 10.5 10.1 12.5 12.4 - - - - - - - - - -
84 29 - - - - 10.7 10.2 12.8 12.6 15.3 15.3 - - - - - - - -
88 31 - - - - 10.9 10.3 13.0 12.7 15.6 15.4 17.5 17.5 - - - - - -
91 33 - - - - - - 13.3 12.8 15.9 15.6 17.7 17.6 19.8 19.8 - - - -
95 35 - - - - - - 13.6 12.9 16.1 15.7 18.1 17.8 20.1 20.0 - - - -
99 37 - - - - - - - - 16.4 15.9 18.4 17.9 20.4 20.1 22.6 22.4 - -
104 40 - - - - - - - - 16.9 16.1 18.8 18.2 20.9 20.4 23.1 22.7 26.5 26.3

INDOOR UNITS 185


11. Heating [Ceiling concealed (Fresh air intake)]
11-1. Heating capacity
11. Heating [Ceiling concealed (Fresh air intake)]

PEFY-P80VMH-E-F SHC:Sensible Heat Capacity(kW)


Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. SHC SHC SHC SHC SHC SHC SHC SHC SHC
18 -8 8.2 - - - - - - - -
27 -3 - 9.1 - - - - - - -
32 0 - - 8.5 - - - - - -
37 3 - - - 7.9 7.9 - - - -
45 7 - - - - 7.1 7.1 7.1 - -
52 11 - - - - - - 6.3 6.3 -
59 15 - - - - - - - 5.5 5.5
64 18 - - - - - - - 5.0 5.0
68 20 - - - - - - - - 4.6

PEFY-P140VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. SHC SHC SHC SHC SHC SHC SHC SHC SHC
18 -8 14.6 - - - - - - - -
27 -3 - 16.2 - - - - - - -
32 0 - - 15.1 - - - - - -
37 3 - - - 14.0 14.0 - - - -
45 7 - - - - 12.6 12.6 12.6 - -
52 11 - - - - - - 11.2 11.2 -
59 15 - - - - - - - 9.8 9.8
64 18 - - - - - - - 8.8 8.8
68 20 - - - - - - - - 8.1

PEFY-P200VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. SHC SHC SHC SHC SHC SHC SHC SHC SHC
18 -8 20.5 - - - - - - - -
27 -3 - 22.7 - - - - - - -
32 0 - - 21.2 - - - - - -
37 3 - - - 19.7 19.7 - - - -
45 7 - - - - 17.8 17.8 17.8 - -
52 11 - - - - - - 15.8 15.8 -
59 15 - - - - - - - 13.8 13.8
64 18 - - - - - - - 12.3 12.3
68 20 - - - - - - - - 11.4

PEFY-P250VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. SHC SHC SHC SHC SHC SHC SHC SHC SHC
18 -8 25.7 - - - - - - - -
27 -3 - 28.3 - - - - - - -
32 0 - - 26.5 - - - - - -
37 3 - - - 24.7 24.7 - - - -
45 7 - - - - 22.2 22.2 22.2 - -
52 11 - - - - - - 19.7 19.7 -
59 15 - - - - - - - 17.3 17.3
64 18 - - - - - - - 15.4 15.4
68 20 - - - - - - - - 14.2

INDOOR UNITS 186


11. Heating [Ceiling concealed (Fresh air intake)]
11-2. Outlet air temp. heated
PEFY-P80VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B.
18 -8 40.6 - - - - - - - -
27 -3 - 53.1 - - - - - - -
32 0 - - 51.9 - - - - - -
37 3 - - - 51.3 51.8 - - - -
45 7 - - - - 50.5 50.5 50.9 - -
52 11 - - - - - - 49.6 50.1 -
59 15 - - - - - - - 48.8 49.2
64 18 - - - - - - - 48.2 48.2
68 20 - - - - - - - - 47.8

PEFY-P140VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B.
18 -8 34.7 - - - - - - - -
27 -3 - 45.8 - - - - - - -
32 0 - - 45.6 - - - - - -
37 3 - - - 45.4 45.4 - - - -
45 7 - - - - 45.2 45.2 45.2 - -
52 11 - - - - - - 45.0 45.0 -
59 15 - - - - - - - 44.7 45.1
64 18 - - - - - - - 44.6 44.6
68 20 - - - - - - - - 44.4

PEFY-P200VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B.
18 -8 29.7 - - - - - - - -
27 -3 - 40.0 - - - - - - -
32 0 - - 40.3 - - - - - -
37 3 - - - 40.6 40.7 - - - -
45 7 - - - - 40.8 40.9 41.0 - -
52 11 - - - - - - 41.2 41.4 -
59 15 - - - - - - - 41.5 41.7
64 18 - - - - - - - 41.7 41.8
68 20 - - - - - - - - 41.9

PEFY-P250VMH-E-F
Outdoor 16F W.B. 23F W.B. 27F W.B. 32F W.B. 36F W.B. 39F W.B. 43F W.B. 50F W.B. 57F W.B.
air temp. -9C W.B. -5C W.B. -2.9C W.B. 0C W.B. 2C W.B. 4C W.B. 6C W.B. 10C W.B. 14C W.B.
F D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B. C D.B.
18 -8 29.7 - - - - - - - -
27 -3 - 40.0 - - - - - - -
32 0 - - 40.3 - - - - - -
37 3 - - - 40.6 40.7 - - - -
45 7 - - - - 40.8 40.9 41.0 - -
52 11 - - - - - - 41.2 41.4 -
59 15 - - - - - - - 41.5 41.7
64 18 - - - - - - - 41.6 41.8
68 20 - - - - - - - - 41.9

INDOOR UNITS 187


INDOOR UNITS 188
SYSTEM DESIGN Y SERIES

1. Electrical work.................................................................................................................................................. 190


1-1.General cautions ....................................................................................................................................... 190
1-2.Power supply for Indoor unit and Outdoor unit .......................................................................................... 191
1-3.Power cable specifications ........................................................................................................................ 196
1-4.Power supply examples............................................................................................................................. 197
2. M-NET control.................................................................................................................................................. 200
2-1.Transmission cable length limitation.......................................................................................................... 200
2-2.Transmission cable specifications ............................................................................................................. 201
2-3.System configuration restrictions............................................................................................................... 206
2-4.Address setting.......................................................................................................................................... 209
3. Piping Design................................................................................................................................................... 222
3-1.Piping Design ............................................................................................................................................ 222
3-2.Refrigerant charging calculation ................................................................................................................ 228
4. Outdoor Installation.......................................................................................................................................... 229
4-1.Requirement on installation site ................................................................................................................ 229
4-2.Spacing...................................................................................................................................................... 230
4-3.Piping direction .......................................................................................................................................... 232
4-4.Weather countermeasure .......................................................................................................................... 237
4-5.Caution on selecting outdoor units ............................................................................................................ 238
5. Caution for refrigerant leakage ........................................................................................................................ 239
5-1.Refrigerant property................................................................................................................................... 239
5-2.Confirm the Critical concentration and take countermeasure.................................................................... 239

SYSTEM DESIGN Y SERIES 189


1. Electrical work
1-1. General cautions
1. Electrical work
I.

Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in.] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 380~415V(220~240V) power source to terminal block of transmission cable. If connected,electrical parts
will be burnt out.
Use 2-core shield cable for transmission cable. If transmission cables of different systems are wired with the same
multiple-core cable, the resultant poor transmitting and receiving will cause erroneous operations.

Indoor unit Indoor unit


Outdoor Outdoor

OK NO
unit unit

2-core shield cable


Multiple-
core cable Remote
Remote controller
controller
BC controller BC controller

2-core shield cable

SYSTEM DESIGN 190


1. Electrical work
1-2. Power supply for Indoor unit and Outdoor unit
1-2-1. Electrical characteristics of Indoor unit
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps
IFM :Indoor Fan Motor Output : Fan motor rated output
Power supply IFM
PMFY-P-VBM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PMFY-P20VBM-E 0.25 0.028 0.20
PMFY-P25VBM-E 220-240V / 50Hz Max.: 264V 0.26 0.028 0.21
PMFY-P32VBM-E 220V / 60Hz Min.: 198V 0.26 0.028 0.21
PMFY-P40VBM-E 0.33 0.028 0.26

Power supply IFM


PLFY-P-VCM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PLFY-P20VCM-E 0.29 0.011 0.23
PLFY-P25VCM-E Max.: 264V 0.29 0.015 0.23
220-240V / 50Hz
PLFY-P32VCM-E Min.: 198V 0.35 0.020 0.28
PLFY-P40VCM-E 0.35 0.020 0.28

Power supply IFM


PLFY-P-VBM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PLFY-P32VBM-E 0.28 0.050 0.22
PLFY-P40VBM-E 0.36 0.050 0.29
PLFY-P50VBM-E 0.36 0.050 0.29
220-240V / 50Hz Max.: 264V
PLFY-P63VBM-E 0.45 0.050 0.36
220V / 60Hz Min.: 198V
PLFY-P80VBM-E 0.64 0.050 0.51
PLFY-P100VBM-E 1.25 0.120 1.00
PLFY-P125VBM-E 1.34 0.120 1.07

Power supply IFM


PLFY-P-VLMD-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PLFY-P20VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37
PLFY-P25VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37
PLFY-P32VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37
PLFY-P40VLMD-E 0.50 / 0.53 0.015 0.40 / 0.42
220-240V / 50Hz Max.: 264V
PLFY-P50VLMD-E 0.51 / 0.54 0.020 0.41 / 0.43
220-230V / 60Hz Min.: 198V
PLFY-P63VLMD-E 0.61 / 0.64 0.020 0.49 / 0.51
PLFY-P80VLMD-E 0.90 / 0.93 0.020 0.72 / 0.74
PLFY-P100VLMD-E 0.94 / 1.10 0.030 0.75 / 0.88
PLFY-P125VLMD-E 1.69 / 1.69 0.078x2 1.35 / 1.35

Power supply IFM


PEFY-P-VMR-E-L/R
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P20VMR-E-L/R 0.37 / 0.37 0.018 0.29 / 0.29
220-240V / 50Hz Max.: 264V
PEFY-P25VMR-E-L/R 0.37 / 0.37 0.018 0.29 / 0.29
220-230V / 60Hz Min.: 198V
PEFY-P32VMR-E-L/R 0.43 / 0.48 0.023 0.34 / 0.38

Power supply IFM


PEFY-P-VMS1-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P15VMS1-E 0.63 / 0.63 0.096 0.50 / 0.50
PEFY-P20VMS1-E 0.70 / 0.70 0.096 0.56 / 0.56
PEFY-P25VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60
220-240V / 50Hz Max.: 264V
PEFY-P32VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60
220-240V / 60Hz Min.: 198V
PEFY-P40VMS1-E 0.83 / 0.82 0.096 0.66 / 0.65
PEFY-P50VMS1-E 1.02 / 1.00 0.096 0.81 / 0.80
PEFY-P63VMS1-E 1.08 / 1.07 0.096 0.86 / 0.85

SYSTEM DESIGN 191


1. Electrical work

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps


IFM :Indoor Fan Motor Output : Fan motor rated output
Power supply IFM
PEFY-P-VMS1L-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P15VMS1L-E 0.46 / 0.46 0.096 0.37 / 0.37
PEFY-P20VMS1L-E 0.54 / 0.54 0.096 0.43 / 0.43
PEFY-P25VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47
220-240V / 50Hz Max.: 264V
PEFY-P32VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47
220-240V / 60Hz Min.: 198V
PEFY-P40VMS1L-E 0.68 / 0.68 0.096 0.54 / 0.54
PEFY-P50VMS1L-E 0.84 / 0.84 0.096 0.67 / 0.67
PEFY-P63VMS1L-E 0.91 / 0.91 0.096 0.73 / 0.73

Power supply IFM


PEFY-P-VMH-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P40VMH-E 1.21 / 1.61 0.08 0.97 / 1.29
PEFY-P50VMH-E 1.21 / 1.61 0.08 0.97 / 1.29
PEFY-P63VMH-E 1.49 / 1.95 0.12 1.19 / 1.56
PEFY-P71VMH-E 220-240V / 50Hz Max.: 264V 1.58 / 2.18 0.14 1.26 / 1.74
PEFY-P80VMH-E 220-240V / 60Hz Min.: 198V 1.85 / 2.40 0.18 1.48 / 1.92
PEFY-P100VMH-E 3.03 / 3.93 0.26 2.42 / 3.14
PEFY-P125VMH-E 3.03 / 3.93 0.26 2.42 / 3.14
PEFY-P140VMH-E 3.10 / 3.98 0.26 2.48 / 3.18
PEFY-P200VMH-E 380-415V / 50Hz Max.: 456V 2.03 / 2.33 0.76 1.62 / 1.86
PEFY-P250VMH-E 380-415V / 60Hz Min.: 342V 2.50 / 2.88 1.08 2.00 / 2.30

Power supply IFM


PEFY-P-VMA-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PEFY-P20VMA-E 1.03 0.085 0.82
PEFY-P25VMA-E 1.03 0.085 0.82
PEFY-P32VMA-E 1.18 0.085 0.95
PEFY-P40VMA-E 1.43 0.085 1.14
PEFY-P50VMA-E 1.54 0.085 1.23
220-240V / 50Hz Max.: 264V
PEFY-P63VMA-E 2.22 0.121 1.78
220-240V / 60Hz Min.: 198V
PEFY-P71VMA-E 2.46 0.121 1.97
PEFY-P80VMA-E 2.47 0.121 1.98
PEFY-P100VMA-E 3.30 0.244 2.64
PEFY-P125VMA-E 3.39 0.244 2.71
PEFY-P140VMA-E 3.29 0.244 2.63

Power supply IFM


PEFY-P-VMAL-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PEFY-P20VMAL-E 0.92 0.085 0.74
PEFY-P25VMAL-E 0.92 0.085 0.74
PEFY-P32VMAL-E 1.07 0.085 0.86
PEFY-P40VMAL-E 1.32 0.085 1.06
PEFY-P50VMAL-E 1.40 0.085 1.12
220-240V / 50Hz Max.: 264V
PEFY-P63VMAL-E 2.08 0.121 1.67
220-240V / 60Hz Min.: 198V
PEFY-P71VMAL-E 2.32 0.121 1.86
PEFY-P80VMAL-E 2.36 0.121 1.89
PEFY-P100VMAL-E 3.19 0.244 2.55
PEFY-P125VMAL-E 3.27 0.244 2.62
PEFY-P140VMAL-E 3.17 0.244 2.53

Power supply IFM


PEFY-P-VMH-E-F
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P80VMH-E-F 220-240V / 50Hz Max.: 264V 0.92 / 1.15 0.09 0.73 / 0.92
PEFY-P140VMH-E-F 208-230V / 60Hz Min.: 187V 1.58 / 1.84 0.14 1.26 / 1.47
PEFY-P200VMH-E-F 380-415V / 50Hz Max.: 456V 0.73 / 0.93 0.20 0.58 / 0.74
PEFY-P250VMH-E-F 380-415V / 60Hz Min.: 342V 0.85 / 1.08 0.23 0.68 / 0.86

SYSTEM DESIGN 192


1. Electrical work
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps
IFM :Indoor Fan Motor Output : Fan motor rated output

Power supply IFM


PKFY-P-VBM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PKFY-P15VBM-E 0.25 0.017 0.20
220-240V / 50Hz Max.: 264V
PKFY-P20VBM-E 0.25 0.017 0.20
220V / 60Hz Min.: 198V
PKFY-P25VBM-E 0.25 0.017 0.20

Power supply IFM


PKFY-P-VHM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PKFY-P32VHM-E 0.38 0.030 0.30
220-240V / 50Hz Max.: 264V
PKFY-P40VHM-E 0.38 0.030 0.30
220V / 60Hz Min.: 198V
PKFY-P50VHM-E 0.38 0.030 0.30

Power supply IFM


PKFY-P-VKM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PKFY-P63VKM-E 220-240V / 50Hz Max.: 264V 0.36 0.056 0.29
PKFY-P100VKM-E 220V / 60Hz Min.: 198V 0.63 0.056 0.50

Power supply IFM


PCFY-P-VKM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PCFY-P40VKM-E 0.35 0.090 0.28
PCFY-P63VKM-E 220-240V / 50Hz Max.: 264V 0.41 0.095 0.33
PCFY-P100VKM-E 220V / 60Hz Min.: 198V 0.81 0.160 0.65
PCFY-P125VKM-E 0.95 0.160 0.76

Power supply IFM


PFFY-P-VKM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PFFY-P20VKM-E 0.25 0.03x2 0.20
PFFY-P25VKM-E Max.: 264V 0.25 0.03x2 0.20
220-240V / 50Hz
PFFY-P32VKM-E Min.: 198V 0.25 0.03x2 0.20
PFFY-P40VKM-E 0.30 0.03x2 0.24

Power supply IFM


PFFY-P-VLEM-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PFFY-P20VLEM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P25VLEM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P32VLEM-E 220-240V / 50Hz Max.: 264V 0.36 / 0.38 0.018 0.29 / 0.30
PFFY-P40VLEM-E 208-230V / 60Hz Min.: 187V 0.40 / 0.41 0.030 0.32 / 0.33
PFFY-P50VLEM-E 0.50 / 0.51 0.035 0.40 / 0.41
PFFY-P63VLEM-E 0.58 / 0.59 0.050 0.46 / 0.47

SYSTEM DESIGN 193


1. Electrical work

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps


IFM :Indoor Fan Motor Output : Fan motor rated output
Power supply IFM
PFFY-P-VLRM-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PFFY-P20VLRM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P25VLRM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P32VLRM-E 220-240V / 50Hz Max.: 264V 0.36 / 0.38 0.018 0.29 / 0.30
PFFY-P40VLRM-E 208-230V / 60Hz Min.: 187V 0.40 / 0.41 0.030 0.32 / 0.33
PFFY-P50VLRM-E 0.50 / 0.51 0.035 0.40 / 0.41
PFFY-P63VLRM-E 0.58 / 0.59 0.050 0.46 / 0.47

Power supply IFM


PFFY-P-VLRMM-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PFFY-P20VLRMM-E 0.59 / 0.58 0.096 0.47 / 0.46
PFFY-P25VLRMM-E 0.59 / 0.58 0.096 0.47 / 0.46
PFFY-P32VLRMM-E Max.: 264V 0.69 / 0.69 0.096 0.55 / 0.55
220-240V / 50Hz
PFFY-P40VLRMM-E Min.: 198V 0.78 / 0.76 0.096 0.62 / 0.61
PFFY-P50VLRMM-E 0.80 / 0.79 0.096 0.64 / 0.63
PFFY-P63VLRMM-E 0.93 / 0.93 0.096 0.74 / 0.74

Power supply IFM


GUF-RDH3
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
GUF-50RD(H)3 220-240V / 50Hz Max.: 264V 1.85 / 1.85 0.081x2 1.48 / 1.48
GUF-100RD(H)3 220V / 60Hz Min.: 198V 3.49 / 3.49 0.16x2 2.79 / 2.79

SYSTEM DESIGN 194


1. Electrical work
1-2-2. Electrical characteristics of Outdoor unit
Units Power supply Compressor FAN RLA (A) (50 / 60Hz)
Model Unit Combination
Hz Volts Voltage range MCA(A) Output (kW) SC (A) Output (kW) Cooling Heating
PUHY-RP200YJM-B(-BS) - 13.5 4.8 0.92 9.5/9.1/8.7 9.6/9.1/8.7
PUHY-RP250YJM-B(-BS) - 18.3 6.8 0.92 12.8/12.2/11.7 12.1/11.5/11.1
PUHY-RP300YJM-B(-BS) - 21.5 8.2 0.92 15.1/14.4/13.8 15.9/15.1/14.5
PUHY-RP350YJM-B(-BS) - 28.4 9.9 0.92 19.9/18.9/18.2 21.2/20.2/19.4
PUHY-RP200YJM-B(-BS) 4.8 0.92
PUHY-RP400YSJM-B(-BS) 28.6 20.0/19.0/18.3 19.2/18.2/17.5
PUHY-RP200YJM-B(-BS) 4.8 0.92
PUHY-RP200YJM-B(-BS) 4.8 0.92
PUHY-RP450YSJM-B(-BS) 33.1 23.2/22.0/21.2 21.6/20.5/19.8
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP500YSJM-B(-BS) 37.7 26.4/25.1/24.2 24.3/23.1/22.3
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP550YSJM-B(-BS) 42.1 29.5/28.0/27.0 28.0/26.6/25.6
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP600YSJM-B(-BS) 44.7 31.3/29.8/28.7 32.4/30.8/29.7
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP650YSJM-B(-BS) 380 50.9 35.6/33.8/32.6 36.6/34.8/33.5
Max:456V
PUHY-RP350YJM-B(-BS) 50/60 400 9.9 8 0.92
Min:342V
415
PUHY-RP200YJM-B(-BS) 4.8 0.92
PUHY-RP700YSJM-B(-BS) PUHY-RP250YJM-B(-BS) 53.6 6.8 0.92 37.5/35.6/34.3 33.9/32.2/31.1
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP750YSJM-B(-BS) PUHY-RP250YJM-B(-BS) 58.2 6.8 0.92 40.7/38.7/37.3 36.7/34.9/33.6
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP800YSJM-B(-BS) PUHY-RP250YJM-B(-BS) 61.4 6.8 0.92 43.0/40.8/39.4 40.0/38.0/36.7
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP250YJM-B(-BS) 6.8 0.92
PUHY-RP850YSJM-B(-BS) PUHY-RP300YJM-B(-BS) 65.3 8.2 0.92 45.7/43.4/41.9 44.6/42.4/40.9
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP300YJM-B(-BS) 8.2 0.92
PUHY-RP900YSJM-B(-BS) PUHY-RP300YJM-B(-BS) 68.2 8.2 0.92 47.7/45.3/43.7 47.9/45.5/43.8
PUHY-RP300YJM-B(-BS) 8.2 0.92

SYSTEM DESIGN 195


1. Electrical work
1-3. Power cable specifications

Thickness of wire for main power supply, capacities of the switch and system impedance
Minimum wire thickness (mm2) Local swtich (A) Breaker for wiring Max. Permissive
Model Breaker for current leakage
Main cable Branch Ground Capacity Fuse (NFB) (A) System impedance

PUHY-RP200YJM-B 4 - 4 30A 100mA 0.1sec. or less 25 25 30 *1


PUHY-RP250YJM-B 4 - 4 30A 100mA 0.1sec. or less 25 25 30 *1
Outdoor unit
PUHY-RP300YJM-B 4 - 4 30A 100mA 0.1sec. or less 32 32 30 *1
PUHY-RP350YJM-B 6 - 6 40A 100mA 0.1sec. or less 40 40 40 0.26
F0 = 20 or less *2 1.5 1.5 1.5 20A current sensitivity *3 20 20 20 (apply to IEC61000-3-3)
Total operating
current of F0 = 30 or less *2 2.5 2.5 2.5 30A current sensitivity *3 30 30 30 (apply to IEC61000-3-3)
the indoor unit F0 = 40 or less *2 4.0 4.0 4.0 40A current sensitivity *3 40 40 40 (apply to IEC61000-3-3)
*1 Meets technical requirements of IEC61000-3-3

*2: Please take the larger of F1 or F2 as the value for F0.


F1 = Total operating maximum current of the indoor units 1.2 Indoor unit V1
Type A PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, 1.6
F2 = (V1 Quantity of Type A) + (V1 Quantity of Type B) + (V1 Quantity of Others)
PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM
Type B PEFY-VMA(L) 3.2
Others Other indoor unit 0

*3: Current sensitivity is calculated using the following formula.


G1 = (V2 Quantity of Type 1) + (V2 Quantity of Type 2) + (V2 Quantity of Others) + (V3 Wire length [km])

G1 Current sensitivity Indoor unit V2 Wire thickness (mm2) V3


30mA or less 30mA 0.1sec. or less Type 1 PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, 2.4
1.5 48
PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM
100mA or less 100mA 0.1sec. or less Type 2 PEFY-VMA(L) 1.6 2.5 56
Others Other indoor unit 0 4.0 66

1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop more
than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.

Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.
Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
Check the existing wires for damage to insulation by measuring the resistance between the lead and the ground with a 500V ohmmeter. If the insulation resistance is less than 100 M,
replace the wires.

This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the interface point (power service box) of
the user's supply.

The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2) at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to
a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).

Ssc(*2)
Model Ssc(MVA)
PUHY-RP200YJM 1.25
PUHY-RP250YJM 1.54
PUHY-RP300YJM 1.75
PUHY-RP350YJM 2.31

SYSTEM DESIGN 196


1. Electrical work
1-4. Power supply examples

The local standards and/or regulations is applicable at a higher priority.


1-4-1. PUHY-RP200-350YJM-B
Note:
<In the case a system controller is connected.> 1 The transmission cable is not-polarity double-wire.
Centralized control 2 Symbol means a screw terminal for wiring.
transmission cable 3 The shield wire of transmission cable should be connected to the grounding terminal at
Note12 >=1.25mm2 Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
SC Shield cable connected to the S terminal at Indoor unit or all shield wire should be connected together.
(CVVS, CPEVS The broken line at the scheme means shield wire.
MVVS) 4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
Connector shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
CN41 CN40 OU Note4 centralized control transmission cable. The shield wire of the centralized control
Note4 transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40.
To other OU 5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
LW TB1 TB3 TB7 is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) 0.75~1.25mm2 in thickness.
6 MA remote controller and ME remote controller should not be grouped together.
TB7 7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
Power supply (S) transmission cable to connect all the TB15 terminals of the Indoor units. It is called
3-phase 4-wire "Grouping".
380-400-415V 50/60Hz If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
Note10,13 address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
Note3 9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10 The critical current for choosing power source equipment is approximate
To *1 or *2 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
*1 13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.
(Using MA remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with MA R/C cable
the model of connected S S 0.3-1.25mm2
indoor units (Shield) (Shield)
(0.75~1.25mm2)
<=200m
Indoor-outdoor Transmission Note5, Note11
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with
the model of connected S S ME R/C cable
indoor units (Shield) (Shield) 0.3~1.25mm2
(0.75~1.25mm2)
Indoor-outdoor Transmission <=10m
transmission cable booster Note5, Note11
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker Minimum Wire thickness
*1, *2 BC OCP*3 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PUHY-RP200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4


LW Local switch PUHY-RP250YJM 30A 100mA 0.1sec. or less 25 25 30 4 4
BC Breaker capacity PUHY-RP300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector PUHY-RP350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6
WB Wiring breaker
NFB Non-fuse breaker *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).
OU Outdoor unit *2 Ground-fault interrupter should combine using of local switch or wiring breaker.
*3 It shows data for B-type fuse of the breaker for current leakage.
IU Indoor unit
SC System controller
MA R/C MA remote controller
ME R/C ME remote controller

SYSTEM DESIGN 197


1. Electrical work
The local standards and/or regulations is applicable at a higher priority.
1-4-2. PUHY-RP400-650YSJM-B
<In the case a system controller is connected.> Note:
1 The transmission cable is not-polarity double-wire.
Centralized control
transmission cable 2 Symbol means a screw terminal for wiring.
Note12 >=1.25mm2 3 The shield wire of transmission cable should be connected to the grounding terminal at
SC Shield cable Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
(CVVS, CPEVS connected to the S terminal at Indoor unit or all shield wire should be connected together.
MVVS) The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
Connector supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
CN41 CN40 OU Note4 OU shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
Note4 centralized control transmission cable. The shield wire of the centralized control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
To other OU CN40.
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
LW TB1 TB3 TB7 LW TB1 TB3 TB7 cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size
0.75~1.25mm2 in thickness.
TB7 TB7 6 MA remote controller and ME remote controller should not be grouped together.
Power supply (S) Power supply (S) 7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
3-phase 4-wire 3-phase 4-wire transmission cable to connect all the TB15 terminals of the Indoor units. It is called
380-400-415V 50/60Hz 380-400-415V 50/60Hz "Grouping".
Note10,13 Note10,13 If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
Note3 8 Indoor board consumes power from TB3. The power balance should be considered
Note3 according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
To *1 or *2 10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
*1 12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13. The phases of electricity power must be confirmed to be right used. Phase-reverse, or
(Using MA remote controller) phase-missing could break the controllers.
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with MA R/C cable
the model of connected S S 0.3-1.25mm2
indoor units (Shield) (Shield)
(0.75~1.25mm2)
<=200m
Indoor-outdoor Transmission Note5, Note11
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with
the model of connected S S ME R/C cable
indoor units (Shield) (Shield) 0.3~1.25mm2
(0.75~1.25mm2)
Indoor-outdoor Transmission <=10m
transmission cable booster Note5, Note11
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker Minimum Wire thickness
*1, *2 BC OCP*3 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PUHY-RP200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4


LW Local switch PUHY-RP250YJM 30A 100mA 0.1sec. or less 25 25 30 4 4
BC Breaker capacity PUHY-RP300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector PUHY-RP350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6
WB Wiring breaker
NFB Non-fuse breaker *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).
OU Outdoor unit *2 Ground-fault interrupter should combine using of local switch or wiring breaker.
IU Indoor unit *3 It shows data for B-type fuse of the breaker for current leakage.
SC System controller
MA R/C MA remote controller
ME R/C ME remote controller

SYSTEM DESIGN 198


1. Electrical work
The local standards and/or regulations is applicable at a higher priority.
1-4-3. PUHY-RP700-900YSJM-B
<In the case a system controller is connected.>
Centralized control Note:
Note12 transmission cable 1 The transmission cable is not-polarity double-wire.
SC >=1.25mm2 2 Symbol means a screw terminal for wiring.
Shield cable 3 The shield wire of transmission cable should be connected to the grounding terminal at
(CVVS, CPEVS Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
MVVS) connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
Connector outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
CN41 CN40 OU Note4
OU OU supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
Note4
shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
To other OU
centralized control transmission cable. The shield wire of the centralized control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
LW TB1 TB3 TB7 LW TB1 TB3 TB7 LW TB1 TB3 TB7 CN40.
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2)
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
TB7 TB7 TB7 R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
Power supply (S) Power supply (S) Power supply (S)
3-phase 4-wire 3-phase 4-wire 3-phase 4-wire cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
380-400-415V 50/60Hz 380-400-415V 50/60Hz 380-400-415V 50/60Hz is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size
Note10,13 Note10,13 Note10,13
0.75~1.25mm2 in thickness.
6 MA remote controller and ME remote controller should not be grouped together.
Note3 Note3 7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
Note3
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
To *1 or *2 to the booster.
10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
*1 11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
(Using MA remote controller) 13. The phases of electricity power must be confirmed to be right used. Phase-reverse, or
Connecting TB5 terminal. phase-missing could break the controllers.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with MA R/C cable
the model of connected S S 0.3-1.25mm2
indoor units (Shield) (Shield)
(0.75~1.25mm2)
<=200m
Indoor-outdoor Transmission Note5, Note11
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with
the model of connected S S ME R/C cable
indoor units (Shield) (Shield) 0.3~1.25mm2
(0.75~1.25mm2)
Indoor-outdoor Transmission <=10m
transmission cable booster Note5, Note11
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker Minimum Wire thickness
*1, *2 BC OCP*3 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PUHY-RP200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4


LW Local switch PUHY-RP250YJM 30A 100mA 0.1sec. or less 25 25 30 4 4
BC Breaker capacity PUHY-RP300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector PUHY-RP350YJM 40A 100mA 0.1sec. or less 40 40 40 6 6
WB Wiring breaker
NFB Non-fuse breaker *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).
OU Outdoor unit *2 Ground-fault interrupter should combine using of local switch or wiring breaker.
*3 It shows data for B-type fuse of the breaker for current leakage.
IU Indoor unit
SC System controller
MA R/C MA remote controller
ME R/C ME remote controller

SYSTEM DESIGN 199


2. M-NET control
2-1. Transmission cable length limitation
2. M-NET control

2-1-1. Using MA Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]

L8 L1

Group1 Group3 Group5


OS2 OS1 OC IC IC IC IC

(53) (52) (51) (01) (04) (05) (06)


TB3 TB3 TB3 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15
M1M2 M1M2 M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2

a2
TB7 TB7 TB7
M1M2 S M1M2 S M1M2 S

a1
a4

a1
A B A B A B

a2

a2

a3
Shielded wire
MA MA MA
L2

OC L3 L4
(54 ) IC IC IC

TB7
(02) (03) (07)
M1 M2 S
TB3 TB5 TB15 TB5 TB 15 TB5 TB15
M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
L6

Power Supply Unit

a1
PAC-SC51KUA
A BS
V+V-FG

A B
L7

AG-150A
n

MA

A B S V+V-FG

OC, OS1, OS2 : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller

2-1-2. Using ME Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <= 500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from ME to Indoor e1, e2+e3, e4 <=10m[32ft.]*1 0.3-1.25 mm2 [AWG22-16] *1
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]
*1. If the length from ME to Indoor exceed 10m, use 1.25 mm2 [AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.

L8 L1

Group1 Group3 Group5


OS2 OS1 OC IC IC IC IC

(53) (52) (51) (01) (04) (05) (06)


TB3 TB3 TB3 TB5 TB5 TB5 TB5
M1M2 M1M2 M1M2 M1M2 S M1M2 S M1M2 S M1M2 S

TB7 TB7 TB7


M1M2 S M1M2 S M1M2 S
e1

e2

e3

A B A B A B
Shielded wire (101) (105) (155)
ME ME ME
L2

OC L3 L4
(54 ) IC IC IC

TB7
(02) (03) (07)
M1 M2 S
TB3 TB5 TB5 TB5
M1M2 M1M2 S M1M2 S M1M2 S
L5
L6

Power Supply Unit


PAC-SC51KUA
e4

A B S
V+V-FG

A B
(103)
L7

AG-150A
n

ME

A B S V+V-FG

OC, OS1, OS2: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller

SYSTEM DESIGN 200


2. M-NET control
2-2. Transmission cable specifications
Transmission cables (Li) ME Remote controller cables MA Remote controller cables
Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable
CVVS, CPEVS or MVVS CVV
2 2
Cable size 0.3 1.25 [AWG22 16] 0.3 1.25 [AWG22 16]
More than 1.25 [AWG16] (0.75 1.25 2
[AWG18 16]) (0.75 1.25 2
[AWG18 16])
When 10m [32ft] is exceeded, use cables with
Remarks Max length : 200m [656ft]
the same specification as transmission cables.

Connected with simple remote controller. CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

Check the existing wires for damage to insulation by measuring the resistance between the lead and the ground with a 500V
ohmmeter. If the insulation resistance is less than 100 M, replace the wires.
Disconnect all controllers before measuring insulation resistance to avoid controller damage.

Note: Disconnect the system controller before starting a refrigerant oil recovery operation, if one is connected.
Reconnect the system controller after the completion of the refrigerant oil recovery operation.

SYSTEM DESIGN 201


2. M-NET control
2-2-1. Reusability check of the existing transmission lines for Replace Multi units
Use the flowcharts on the following pages to determine the reusability of the existing transmission lines.
Obtain the system configuration drawing, fill out the checklist, and make a decision based on them.

Existing transmission lines reusability checklist


Check items Findings Notes
1. Remote controller cable (MA remote controller)
(1) Length m
(2) Cable size mm2
(3) Number of cores Cores

(4) Cable type (shielded/unshielded) Shielded/Unshielded


2. Remote controller cable (ME remote controller)
(1) Length *1 m
(2) Cable size mm2
(3) Number of cores Cores

(4) Cable type (shielded/unshielded) Shielded/Unshielded


3. Remote controller cable (system controller)
(1) Length *1 m
(2) Cable size mm2
(3) Number of cores Cores

(4) Cable type (shielded/unshielded) Shielded/Unshielded


(5) System controller connection (Indoor unit Indoor/Centralized
system/centralized control system)
4. Indoor-outdoor transmission line
(1) Refrigerant system (Single/Multiple) Single/Multiple
(2) Length of transmission line to the farthest unit *1 m
(3) Cable size mm2
(4) Number of cores Cores

(5) Cable type (shielded/unshielded) Shielded/Unshielded


(6) Number of connected indoor units units

5. Centralized control transmission line


(1) Length of transmission line to the farthest unit *1 m
(2) Cable size mm2
(3) Number of cores Cores
(4) Cable type (shielded/unshielded) Shielded/Unshielded

6. Availability of system configuration drawing (Obtain one as Available/Not available


much as possible.)
7. Noise-related problems with the old units Available/Not available
(Write down the nature of the problem in the Notes column,
if any.)

8. Are there any high-frequency medical equipment in the adjacent Available/Not available
area that could cause noise-interference?
(Write down the specific nature of the concerns in the Notes
column, if any.)

*1: If the remote controller (ME/System controller) length exceeds 10 m, include the exceeded length in the calculation of the
transmission line length (indoor-outdoor transmission line/centralized control system).

SYSTEM DESIGN 202


2. M-NET control

Reusability of MA remote controller wiring Reusability of M-NET remote controller witing

Checking the Checking the


transmission cable transmission cable

NO Refer to Table A. NO Refer to Table A.


Is the 2-core cable used? Handle the non-using wiring as Is the 2-core cable used? Handle the non-using wiring as
shown in figure A. shown in figure A.

YES YES

NO NO If the wiring is more than 10m, include the


Is the wiring of Wiring for MA remote controller Is the wiring of exceeding length to the total wiring length.
less than 200m? must be under 200m. less than 10m? When 10m is exceeded, use cables with the
same specification as transmission cables.

YES YES

Go to "Reusability of Go to "Reusability of
Transmission line". Transmission line".

Reusability of System controller wiring Figure A. Non-using wiring


Side: A A
Close to power supply unit B shielded wire B
Checking the (Outdoor unit, Power supply unit)
transmission cable S S

A A
B Non-shielded wire B
NO S S
Refer to Table A.
Is the 2-core cable used? Handle the non-using wiring as Non using wiring on the power supply side (Outdoor unit, Power supply
shown in figure A.
unit) should be connected to the shield terminal. The non-using wiring on
the opposite side should be open and insulated.
YES

If the wiring is more than 10m, include the


exceeding length to the total wiring length.
When 10m is exceeded, use cables with the
same specification as transmission cables.

YES

Go to "Reusability of
Transmission line".

Table A

Transmission cables (Li) ME Remote controller cables MA Remote controller cables


Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable
CVVS, CPEVS or MVVS CVV
2 2
Cable size 0.3 1.25 [AWG22 16] 0.3 1.25 [AWG22 16]
More than 1.25 [AWG16] (0.75 1.25 2
[AWG18 16]) (0.75 1.25 2
[AWG18 16])
When 10m [32ft] is exceeded, use cables with
Remarks Max length : 200m [656ft]
the same specification as transmission cables.

Connected with simple remote controller. CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

SYSTEM DESIGN 203


2. M-NET control

Determining the reusability of the transmission line

Reusability of Transmission line

Checking the transmission cable

NO *1: When the remote controller cable (ME remote controller and system remote
Is there a ground fault
Fix the ground fault current. controller) exceeds 10m, use cables with the same specification as
current?
transmission cables (indoor/outdoor and centralized controller).

YES

Is the farthest NO Farthest transmission line of


transmission line less centralized controller must be less
than 200m? than 200m.

YES

Is the diameter of the


NO Check the number of indoor units,
Is the diameter of the current
NO Change the wiring to shielded wiring
farthest length of transmission line
transmission line more than and read the applicable diameter wiring thicker than the diameter with more than 1.25mm2.
1.25mm2? from the diagram B. read from diagram B?

YES YES

NO Refer to Table A.
Is the 2-core cable used? Handle the wiring that are not used
as shown in figure A.

YES

NO NO Farthest transmission line of


Is the system single Is the farthest transmission
centralized controller must be less
refrigerant system? line of centralized controller
less than 500m? than 500m.

YES YES

NO Is the diameter of
NO Check the farthest transmission line Is the diameter of the current
NO
Is the farthest transmission centralized transmission line length of centralized controller and wiring thicker than the
line of indoor/outdoor unit more than 1.25mm2?
read the applicable diameter. diameter read from chart A?
less than 120m? *1
YES YES
YES

Change the centralized transmission


NO line diameter to more than 1.25mm2.
Is the shielded wiring used? Please contact your local distributor
for more information.

YES
Chart A. Centralized transmission line applicable diameter
Shielded wiring should be connected
to the terminal at the power supply Length between power
unit side (outdoor unit).
supply unit to outdoor unit Wiring diameter
and system controller
Less than 200m More than 0.5mm2
Less than 130m More than 0.3mm2

Existing transmission line can


be reused.

Figure A. Non-using wiring

Side: A A
Close to power supply unit B shielded wire B
(Outdoor unit, Power supply unit)
S S

A A
B Non-shielded wire B
S S

Non using wiring on the power supply side (Outdoor unit, Power supply
unit) should be connected to the shield terminal. The non-using wiring on
the opposite side should be open and insulated.

Table A

Transmission cables (Li) ME Remote controller cables MA Remote controller cables


Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable
CVVS, CPEVS or MVVS CVV
2 2
Cable size 0.3 1.25 [AWG22 16] 0.3 1.25 [AWG22 16]
More than 1.25 [AWG16] (0.75 1.25 2
[AWG18 16]) (0.75 1.25 2
[AWG18 16])
When 10m [32ft] is exceeded, use cables with
Remarks Max length : 200m [656ft]
the same specification as transmission cables.

Connected with simple remote controller. CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

SYSTEM DESIGN 204


2. M-NET control

Diagram B Checking the cable size


MA remote controller
200

Length of transmission line to the farthest unit (m)


1.25mm2

150

0.75mm2

0.5mm2
100

0.3mm2

50

0
0 5 10 15 20 25 30 32
Number of indoor units

ME remote controller
200

1.25mm2
Length of transmission line to the farthest unit (m)

150

0.75mm2
0.5mm2

100

0.3mm2

50

0
0 5 10 15 20
Number of indoor units

SYSTEM DESIGN 205


2. M-NET control
2-3. System configuration restrictions
2-3-1. Common restrictions for the CITYMULTI system

For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
*OA processing unit GUF-RD(H) is considered as Indoor unit.
B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.)
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.

2-3-2. Ensuring proper communication power for M-NET


In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY, and OA processing unit
GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases,
Transmission booster should be used. Taking the power consumption of Indoor unit sized P20-P140 as 1, the equivalent
power consumption or supply of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption
Indoor, OA unit Indoor unit BC controller MA RC. LOSSNAY ME Remote Contr. Timers, System Contr. ON/OFF Contr. MN Converter
Sized P15-P140 Sized P200,P250 CMB PAR-30MAA PAR-F27MEA PAC-SC30GRA AT-50A PAC-YT40ANRA CMS CMS
GUF-50, 100 PAR-21MAA PAC-SE51CRA PAC-SF44SRA -MNF-B -MNG-E
PAC-YT51CRA(B) PZ-52SF-E PAC-YT34STA
PAR-FA32MA AG-150A
LGH-RX-E
PZ-60DR-E
1 7 2 0 1/4 1/2 4 1 1/2 2
*RC : Remote Controller
Table 2-3-2 The equivalent power supply
Transmission Booster Power supply unit Expansion controller BM ADAPTER System Controller Outdoor unit Outdoor unit
PAC-SF46EPA PAC-SC51KUA PAC-YG50ECA BAC-HD150 GB-50ADA Connector TB3 and TB7 total * Connector TB7 only
25 5 6 6 6 32 6
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32. Not
applicable to the PUMY model.
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the
air-conditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, OA process units and ME remote controller, Timers
and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sized
P200, 250 is counted as 7 Indoor units, but MA remote controller(s), LOSSNAY, PZ-60DR-E is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumption
reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA is used to supply power at TB7 side, count from
TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reaches
6, a PAC-SF46EPA should be set.
System example

TB7 TB3
UP

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

POWER RATING 220-240V:0.7A ~/N

50

WEIGHT 3.4kg

MADE IN JAPAN

01 02 Transmission
booster
(No.1)

ME remote ME remote
controller controller
TB7 TB3 N1 N2
Outdoor unit Transmission booster (No.1) should be used, Within N2, conditions 1,2 should be followed.
if the total quantity of Indoor units, OA process units and ME remote controllers 1.The total quantity of Indoor units, OA process units
reaches 40, (Indoor unit sized P200, 250 is counted as 7); and ME remote controller should not exceed 40.
or if the total equivalent transmission power consumption reaches 32. *Indoor unit sized P200, 250 is counted as 7 units.
2.The total equivalent transmission power consumption
UP
should not exceed 25.

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

220-240V:0.7A ~/N
POWER RATING
50

WEIGHT 3.4kg

MADE IN JAPAN

Transmission
LOSSNAY booster LOSSNAY
CENTRALIZED CONTROLLER AG-150A

unit PAC-SF46EPA unit


M-NET Centralized controller (No.2)
(AG-150A)
PZ-52SF-E PZ-52SF-E
24VDC
Power supply unit
PAC-SC51KUA N3 N4
Transmission booster (No.2) should be used, Within N4, the total equivalent transmission
if the total equivalent transmission power consumption reaches 5. power consumption should not exceed 25.

SYSTEM DESIGN 206


2. M-NET control
2-3-3. Ensuring proper power supply to System controller
The power to System controller (excluding LMAP02-E) is supplied via M-NET transmission line. M-NET transmission line
at TB7 side is called Centralized control transmission line while one at TB3 side is called Indoor-Outdoor transmission line.
There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.

2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB3.
If there is more than 1 Outdoor unit, it is necessary to Fig. 2-3-3-A M-NET transmission lines System controller
(excluding LMAP02-E)
replace power supply switch connector CN41 with CN40 Outdoor unit
(Indoor-Outdoor transmission lines)
Group Group
on one Outdoor unit. TB3
TB7
Replacement of
CN41 with CN40 Indoor unit

M-NET transmission lines


(transmission lines
for centralized controller) MA remote controller

Outdoor unit
Group Group
TB3
TB7
Use CN41
as it is. Indoor unit

ME remote controller

System
controller Maximum 3 System controllers can be connected to TB3.

2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB7
and receiving power from the Outdoor unit. Fig. 2-3-3-B M-NET transmission lines
It is necessary to replace power supply switch connector Outdoor unit
(Indoor-Outdoor transmission lines)
Group Group
CN41 with CN40 on one Outdoor unit. TB3
TB7
Replacement of
CN41 with CN40 Indoor unit

M-NET transmission lines


(transmission lines
for centralized controller) MA remote controller

Outdoor unit
Group Group
TB3
TB7
Use CN41
as it is. Indoor unit

ME remote controller

System
controller Maximum 3 System controllers can be connected to TB7.

2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
When using PAC-SC51KUA to supply transmission
Fig. 2-3-3-C
power, the power supply connector CN41 on the Outdoor M-NET transmission lines
(Indoor-Outdoor transmission lines)
units should be kept as it is. It is also a factory setting. Outdoor unit
Group Group

1 PAC-SC51KUA supports maximum 1 AG-150A unit TB7


TB3

due to the limited power 24VDC at its TB3. Use CN41


as it is. Indoor unit

However, 1 PAC-SC51KUA supplies transmission power M-NET transmission lines


(transmission lines
at its TB2 equal to 5 Indoor units, which is referable at for centralized controller) MA remote controller

Table 2-3-2. Outdoor unit


Group Group
If PZ-52SF-E, Timers, System controller, ON/OFF TB3
controller connected to TB7 consume transmission power TB7
Use CN41
Indoor unit
more than 5 (Indoor units), Transmission booster as it is.

PAC-SF46EPA is needed. PAC-SF46EPA supplies PAC-SC51KUA


ME remote controller
transmission power equal to 25 Indoor units.
System
controller

CAUTION
AG-150A*1 is recommended to connect to TB7 because it performs back-up to a number of data.
In an air conditioner system has more than 1 Outdoor units, AG-150A receiving transmission power through TB7 on one of the Outdoor units would have a
risk that the connected Outdoor unit failure would stop power supply to AG-150A, and disrupt the whole system.
When applying apportioned electric power function, AG-150A is necessary to connected to TB7 and has its own power supply unit PAC-SC51KUA.*2
*1: AG-150A is an example model of system controllers.
*2: Power supply unit PAC-SC51KUA is for AG-150A.

SYSTEM DESIGN 207


2. M-NET control

2-3-4. Power supply to LM adapter LMAP02-E


1-phase 220-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when connecting only the LMAP02-E. Yet, make sure to change
the power supply changeover connector CN41 to CN40 on the LM adapter.

2-3-5. Power supply to expansion controller


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary.
The expansion controller supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)

2-3-6. Power supply to BM ADAPTER


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.
Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.

2-3-7. Power supply to GB-50ADA


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary.
GB-50ADA supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)

SYSTEM DESIGN 208


2. M-NET control
2-4. Address setting

2-4-1. Switch operation

In order to constitute CITY MULTI in a complete system, switch Rotary switch


operation for setting the unit address No. and connection No. is Branch
required. No. setting Unit address No. setting

Address No. of outdoor unit, indoor unit and remote controller. F 0 12 9


01
9
01

BC E

3456

2 3

2 3
D
The address No. is set at the address setting board.

7 8

7 8
In the case of R2 system, it is necessary to set the same No. at the
789A 45 6 45 6
branch No. switch of indoor unit as that of the BC controller
connected. (When connecting two or more branches, use the lowest
branch No.)
Caution for switch operations
Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.

MA remote controller

When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
The factory setting is Main .

PAR-21MAA
The MA remote controller does not have the switches listed above.
Refer to the installation manual for the function setting.

PAC-YT51CRB
Setting the dip switches
There are switches on the front of the remote controller. Remote controller Main/Sub and other function settings
are performed using these switches. Ordinarily, only change the Main/Sub setting of SW1.
(The factory settings are all ON.)
SW No SW contents Main ON OFF Comment
Remote controller
1 Main Sub Set one of the two remote controllers at one group to Main
Main/Sub setting
Temperature display
2 Celsius Fahrenheit When the temperature is displayed in [Fahrenheit], set to No.
units setting
Cooling/heating dis- When you do not want to display Cooling and Heating in the
3 Yes No
play in AUTO mode Auto mode, set to No.

SYSTEM DESIGN 209


2. M-NET control

2-4-2. Rule of setting address

Unit Address setting Example Note


Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
9 0 1 9 0 1
If applicable, set the sub BC controllers in an PURY
Indoor unit 01 ~ 50

7 8

7 8
2 3

2 3
4 5 6 4 5 6
system in the following order:
10 1 (1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)

The smallest address of indoor unit in same refrigerant


system + 50
9 0 1 9 0 1 Assign sequential address numbers to the outdoor
Outdoor unit
7 8

7 8
2 3

2 3
51 ~ 99, 100 4 5 6 4 5 6 units in one refrigerant circuit system. OC, OS1 and
(Note1) OS2 are automatically detected. (Note 2)
10 1 Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The address of outdoor unit + 1
9 0 1 9 0 1
BC controller Please reset one of them to an address between 51
7 8

7 8
2 3

2 3

52 ~ 99, 100 and 99 when two addresses overlap.


(Main)
4 5 6 4 5 6
The address automatically becomes "100" if it is set
10 1
as "01~ 50"
9 0 1 9 0 1 Lowest address within the indoor units connected to
BC controller
7 8

7 8
2 3

2 3

52 ~ 99, 100 the BC controller (Sub) plus 50.


(Sub)
4 5 6 4 5 6

10 1
Local remote controller

0 1 0 1
ME, LOSSNAY 9 9

1 The smallest address of indoor unit in the group + 100


2 3

2 3
7 8

7 8

Remote controller 101 ~ 150 45 6 45 6

(Main) Fixed The place of "100" is fixed to "1"


10 1

ME, LOSSNAY 9
0 1
9
0 1 The address of main remote controller + 50
1
2 3

2 3
7 8

7 8

Remote controller 151 ~ 199, 200 45 6 45 6


The address automatically becomes "200" if it is set
(Sub) Fixed
10 1 as "00"
0 1 0 1

2
9 9
Group remote The smallest group No. to be managed + 200
2 3

2 3
7 8

7 8

controller 201 ~ 250 Fixed


45 6 45 6

10 1

0 1 0 1 0 1
9 9 9
System remote
2 3

2 3

2 3
7 8

7 8

7 8

000, 201 ~ 250


controller
45 6 45 6 45 6

100 10 1
0 1 0 1 0 1
9 9 9
The smallest group No. to be managed + 200
ON/OFF remote
2 3

2 3

2 3
7 8

7 8

7 8
System controller

000, 201 ~ 250 45 6 45 6 45 6


controller The smallest group No. to be managed is changeable.
100 10 1

AG-150A
GB-50ADA 000, 201 ~ 250 0,2 0~5 0~9
AT-50A
100 10 1

PAC-YG50ECA 000, 201 ~ 250 0,2 0~5 0~9 Settings are made on the initial screen of AG-150A.
100 10 1

BAC-HD150 000, 201 ~ 250 0,2 0~5 0~9 Settings are made with setting tool of BM ADAPTER.

100 10 1

9 0 1 9 0 1

2
7 8

7 8
2 3

2 3

LMAP02-E 201 ~ 250 4 5 6 4 5 6

Fixed
10 1

Note1: To set the address to "100", set it to "50"


Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.

SYSTEM DESIGN 210


2. M-NET control

2-4-3. System examples

Factory setting
Original switch setting of the outdoors, indoors, controllers, LMAP and BM ADAPTER at shipment is as follows.
Outdoor unit : Address: 00, CN41: U (Jumper), DipSW2-1: OFF
Indoor unit : Address: 00
ME remote controller : Address: 101
LMAP : Address: 247, CN41: U (Jumper), DipSW1-2: OFF
BM ADAPTER : Address: 00

Setting at the site


DipSW2-1(Outdoor) : When the System Controller is used, all the Dip SW2-1 at the outdoor units should be
set to "ON". * Dip SW2-1 remains OFF when only LMAP02-E is used.
DipSW1-2(LMAP) : When the LMAP is used together with System Controller, DipSW1-2 at the LMAP should be
set to "ON".
CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.

2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller


<Three outdoor units> <Two outdoor units> <One outdoor unit>
PUHY PUHY PUHY
OC OS1 OS2 OC OS1 OC
00 00 00 00 00 00
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4

Indoor unit
00 00 00 00 00
TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15

SRU 1*
MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)

1*
Wireless R/C
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. No address setting is needed.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".

SYSTEM DESIGN 211


2. M-NET control

2-4-3. System examples


2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller
<Three outdoor units> <Two outdoor units> <One outdoor unit>
PUHY PUHY PUHY
OC OS1 OS2 OC OS1 OC
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4

Indoor unit
01 02 03 04 05
TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15

201
SRU 1*
SC MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)

1*
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units and centralized controller.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".

SYSTEM DESIGN 212


2. M-NET control

2-4-3. System examples

2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring

PUHY PUHY PUHY


OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 91 92 98
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21

Indoor unit
01 02 03 30
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

TB2 Transmission Booster


PAC-SF46EPA
202 SRU *1
Power supply unit SC*3 MA R/C MA R/C MA R/C
(PAC-SC51KUA) *2 (Main) (Sub)

000 or 201 *1
SC*3 Wireless R/C

Group 31 Group 32 Group 33 Group 34 Group 35 Group 36

Indoor unit LOSSNAY LOSSNAY


41 42 43 45 46 47
TB5 TB15 TB5 TB5 TB5 TB15 TB5 TB15 TB5 TM4

203 SRU *1 142 143


SC *3 ME R/C PZ-52SF-E MA R/C MA R/C MA R/C PZ-60
(Main) (Sub) DR-E
*1
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24V DC should be used with the PAC-SC51KUA.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, LOSSNAY and system controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

SYSTEM DESIGN 213


2. M-NET control

2-4-3. System examples

2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller


<Three outdoor units> <Two outdoor units> <One outdoor unit>
PUHY PUHY PUHY
OC OS1 OS2 OC OS1 OC
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4

Indoor unit
01 02 03 04 05
TB5 TB5 TB5 TB5 TB5

101 102 104 105 155


ME R/C ME R/C ME R/C ME R/C ME R/C

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, system controller and ME remote controllers.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

2-4-3-5. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY


<Three outdoor units> <Two outdoor units> <One outdoor unit>
PUHY PUHY PUHY
OC OS1 OS2 OC OS1 OC
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4 Group 5 Group 6

Indoor unit LOSSNAY LOSSNAY


01 02 03 04 05 06
TB5 TB5 TB5 TB5 TB5 TB5 TM4

201 101 102 103 104 105 155


SC ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C PZ-60
DR-E

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, LOSSNAY centralized controller, ME remote controllers.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".

SYSTEM DESIGN 214


2. M-NET control

2-4-3. System examples

2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
PUHY PUHY PUHY
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 91 92 97
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21

Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

TB2 Transmission Booster


PAC-SF46EPA
202 101 102 130 180
Power supply unit SC *2 ME R/C ME R/C ME R/C ME R/C
(PAC-SC51KUA) *1

000 or 201

SC*2

Group 31 Group 32 Group 33 Group 34 Group 35 Group 36

Indoor unit LOSSNAY LOSSNAY


41 42 43 44 45 46
TB5 TB5 TB5 TB5 TB5 TB5 TM4

203 141 142 143 144 145 195


SC *2 ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C PZ-60
DR-E

*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24V DC should be used with the PAC-SC51KUA.
*2 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

SYSTEM DESIGN 215


2. M-NET control

2-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit


PUHY PUHY
OC OS OC
TB7 TB7 TB7
51 52 56
CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


OFF OFF OFF
TB3 TB3 TB3

Group 1 Group 2

01 02 03 04 05

101 105
ME R/C ME R/C

Group 4 Group 3

10 09 08 07 06

110 107
ME R/C ME R/C
NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

2-4-3-8. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, No Power sypply unit
PUHY PUHY
OC OS OC
TB7 TB7 TB7
51 52 56
CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2

01 02 03 04 05

201 101 105


SC ME R/C ME R/C

Group 4 Group 3

10 09 08 07 06

110 107
ME R/C ME R/C
NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

SYSTEM DESIGN 216


2. M-NET control

2-4-3-9. TG-2000A(*1)+AG-150A*2
AG-150A can control max. 50 indoor units;
TG-2000A can control max. 40 AG-150A;*3
TG-2000A can control max. 2000 indoor units.
AG-150A PUHY
OC
000
TB7
51
24VDC CN40 CN41

TB3 TB2
DipSW2-1
ON
Power supply unit TB3
(PAC-SC51KUA)
Group 1 Group 2 Group 40

Indoor unit
01 02 03 42
HUB
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *4 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)
PC with
*4
TG-2000A
Wireless R/C

LAN AG-150A
PUHY PUHY
000 OC OS OC
TB7 TB7 TB7
51 52 91
24VDC CN40 CN41 CN40 CN41 CN40 CN41
TB3 TB2
DipSW2-1 DipSW2-1 DipSW2-1
ON ON ON
Power supply unit TB3 TB3 TB3
(PAC-SC51KUA)

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34 Group 35


Interlocked
Indoor unit LOSSNAY LOSSNAY
41 42 43 44 45 46
TB5 TB5 TB5 TB5 TB5 TB5 TM4

141 142 144 145 195


PZ-60
ME R/C ME R/C ME R/C ME R/C ME R/C DR-E
It is planned that GB-50ADA will be supported on TG-2000A Ver. 6.3* or later.
*1 TG-2000A (Ver.5.5 or later) supports AG-150A (Ver.1 series).
TG-2000A (Ver. 6.1 or later) supports AG-150A (Ver. 2.1 or later) connected with the expansion controller (EC).
*2 AG-150A (Ver.1 series) does not support the expansion controller (EC).
*3 When AG-150A connected with the expansion controller (EC) is connected, the number of EC will be the maximum controllable number.
TG-2000A can control up to 40 EC or AG-150A without EC connection.
*4 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 217


2. M-NET control

2-4-3. System examples


2-4-3-10. AG-150A + PAC-YG50ECA (Expansion controller)
AG-150A can control max. 150 indoor units/ via expansion controllers.
AG-150A

24VDC
TB3
Power supply unit
(PAC-SC51KUA)
<Three outdoor units> <Two outdoor units> <One outdoor unit>
PAC-YG50ECA
PUHY PUHY PUHY
000 OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
CN40 CN41 51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40

Indoor unit
01 02 03 42
HUB
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *1 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)
PC with *1
Browser Wireless R/C

LAN
PAC-YG50ECA
000 PUHY PUHY PUHY
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
CN40 CN41
51 52 53 91 92 96
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


PAC-YG50ECA
ON ON ON ON ON ON
000 TB3 TB3 TB3 TB3 TB3 TB3

CN40 CN41 Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C
Group 31 Group 32 Group 33 Group 34 Group 35
Indoor unit LOSSNAY
41 42 43 44 45
TB5 TB5 TB5 TB5 TB5

141 142 143 144 145 195


ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C
NOTE
When connecting AG-150A to PAC-YG50ECA, TB2 for power supply unit does not need to be connected to AG-150A.
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 218


2. M-NET control

2-4-3. System examples

2-4-3-11. LMAP
LMAP can transmission for max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system
controller (SC).

LMAP can transmission for max.


LMAP(01) 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
identified by Neuron ID
<Three outdoor units> <Two outdoor units> <One outdoor unit>
247
(LONWORKs adapter) PUHY PUHY PUHY
CN40 CN41
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
DipSW1-2
OFF 51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40


Indoor unit
01 02 03 42
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15
AG-150A
Transmission Booster
SRU *1 PAC-SF46EPA
000
Power supply unit
(PAC-SC51KUA) MA R/C MA R/C MA R/C
(Main) (Sub)
TB3 24VDC
*1
TB2 Wireless R/C
LMAP(02)
identified by Neuron ID
LONWORKS

247
PUHY PUHY PUHY
CN40 CN41 OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
DipSW1-2 51 52 53 91 92 97
ON CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34 Group 35 Group 36


Indoor unit LOSSNAY LOSSNAY
41 42 43 44 45 46
PC TB5 TB5 TB5 TB5 TB5 TB5 TM4

LONWORKS card
141 142 143 144 145 195
LONWORKS card ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C PZ-60
DR-E
LONWORKS card For other equipments (Lighting, security, elevator etc.)
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 219


2. M-NET control

2-4-3. System examples

2-4-3-12. BM ADAPTER
BM ADAPTER can transmission for max. 50 indoor units;
Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected
without the power supply unit.

BM ADAPTER can transmission for max.


50 indoor units in single-refrigerant-system or multi-refrigerant-system.
BM ADAPTER(01)
<Three outdoor units> <Two outdoor units> <One outdoor unit>
000
HUB PUHY PUHY PUHY
CN40 CN41
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40


Indoor unit
01 02 03 42
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *1 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)

*1
Wireless R/C

BM ADAPTER(02)
BAC net

201
PUHY PUHY PUHY
CN40 CN41 OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 91 92 96
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34 Group 35


Indoor unit LOSSNAY
41 42 43 44 45
TB5 TB5 TB5 TB5 TB5

141 142 143 144 145 195


ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C
HUB
For other equipments (Lighting, security, elevator etc.)
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 220


2. M-NET control

2-4-3. System examples

2-4-3-13. BM ADAPTER+PAC-YG50ECA (Expansion controller)


BM ADAPTER(*1) can transmission for max. 150 indoor units/via expansion controllers (PAC-YG50ECA).

LAN1
BM ADAPTER PAC-YG50ECA*4
BACnet 000 <Three outdoor units> <Two outdoor units> <One outdoor unit>
CN40 CN41 PUHY PUHY PUHY
CN40 CN41
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
LAN2 51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40


Indoor unit
01 02 03 42
LAN TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *2 PAC-SF46EPA

HUB MA R/C MA R/C MA R/C


(Main) (Sub)

*2
Wireless R/C

PAC-YG50ECA*4
000
PUHY PUHY PUHY
CN40 CN41 OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 91 92 96
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41
PAC-YG50ECA *4
000 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1 DipSW2-1
CN40 CN41 ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
AG-150A *3 TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C
24VDC TB3
Group 31 Group 32 Group 33 Group 34 Group 35
Indoor unit LOSSNAY
Power supply unit
(PAC-SC51KUA) 41 42 43 44 45
TB5 TB5 TB5 TB5 TB5

141 142 143 144 145 195


ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C

NOTE
It is not necessary to connect the M-NET transmission line to the TB3 on BM ADAPTER. Leave the power
jumper of BM ADAPTER connected to CN41.
*1 BM ADAPTER (Ver.2.00 or later) supports the expansion controller.
*2 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*3 AG-150A (Ver.2.30 or later) supports the BM ADAPTER.
*4 PAC-YG50ECA (Ver.1.30 or later) supports the BM ADAPTER.

SYSTEM DESIGN 221


3. Piping Design
3-1. Piping Design
3. Piping Design

3-1-1. PUHY-RP200-350YJM-B

OU

Note 1. No Joint after Header; Piping direct to Indoor Unit from Header
Note 2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better.
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m) = Actual piping length + "M" x Quantity of bent.

Header
B
1st Joint
Capped
L1
H' (OU under IU)
H (OU above IU)

C
L2

D E a b c

Joint IU IU IU

d e f g

h1
IU IU IU IU

Fig. 3-1-1A Piping scheme IU : Indoor unit, OU : Outdoor unit

Table 3-1-1-1. Piping length (m) Table 3-1-1-2. Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor unit model M (m/bent)
Total piping length A+B+C+D+E+a+b+c+d+e+f+g 300 *1 PUHY-RP200YJM-B 0.35
Farthest IU from OU (L1) A+C+D+E+g / A+B+c 120 150 PUHY-RP250YJM-B 0.42
Farthest IU from first joint (L2) C+D+E+g / B+c 40 *2 PUHY-RP300YJM-B 0.42
Height between OU and IU (OU above IU) H 50 PUHY-RP350YJM-B 0.47
Height between OU and IU (OU under IU) H' 40
Height between IU and IU h1 15
OU: Outdoor Unit, IU: Indoor Unit

* 1 Do not exceed the amount of refrigerant to be charged written below.


PUHY-RP200-250YJM-B: 0.39 L0 + 0.29 L1 + 0.2 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 18
PUHY-RP300-350YJM-B: 0.39 L0 + 0.29 L1 + 0.2 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 25

L0: Total length of 22.2 liquid pipe (m)


L1: Total length of 19.05 liquid pipe (m)
L2: Total length of 15.88 liquid pipe (m)
L3: Total length of 12.7 liquid pipe (m)
L4: Total length of 9.52 liquid pipe (m)
L5: Total length of 6.35 liquid pipe (m)

* 2 When creating 1 system out of the pipework of 2 systems, (L1-L2) must be 40 m or less.

L1: Distance between system 1's original outdoor unit and system 1's original farthest indoor unit.
L2: Distance between system 2's original outdoor unit and system 2's original farthest indoor unit.
L1 L2

Table 3-1-1-3. Piping "A" size selection rule (mm) Table 3-1-1-4. R410A piping "B", "C", "D", "E" size selection rule (mm [in.])
Outdoor Pipe (Liquid) Pipe (Gas) Total down-stream Indoor capacity Pipe (Liquid) Pipe (Gas)
PUHY-RP200YJM-B 12.7 28.58 ~ P80 9.52 [3/8"] 15.88 [5/8"]
PUHY-RP250YJM-B 12.7 28.58 P81 ~ P160 12.7 [1/2"] 19.05 [3/4"]
PUHY-RP300YJM-B 12.7 28.58 P161 ~ P330 12.7 [1/2"] 25.4 [1"]
PUHY-RP350YJM-B 15.88 34.93 P331 ~ P630 15.88 [5/8"] 34.93 [1-3/8"]
P631 ~ 19.05 [3/4"] 41.28 [1-5/8"]

Table 3-1-1-5. Piping "a", "b", "c", "d", "e", "f", "g" size selection rule (mm [in.])
Indoor Unit size Pipe (Liquid) Pipe (Gas)
P20, P25, P32, P40 6.35 [1/4"] 12.70 [1/2"] Note 3. Indoor capacity is described as its model size.
For example, PEFY-P32VMM-E, its capacity is P32.
P50, P63, P71, P80 9.52 [3/8"] 15.88 [5/8"] Note 4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
P140 9.52 [3/8"] 19.05 [3/4"] For example, PEFY-P25VMM-E + PEFY-P32VMM-E: Total Indoor capacity = P25 + P32 = P57
Note 5. Piping size determined by the Total down-stream indoor capacity is NOT necessary
P200 12.7 [1/2"] 25.4 [1"] to be bigger than the up-stream one.
P250 12.7 [1/2"] 28.58 [1-1/8"] i.e. A >= B; A >= C >= D

SYSTEM DESIGN 222


3. Piping Design
3-1-2. PUHY-RP400-550YSJM-B

OU Note 1. No Joint after Header; Piping direct to Indoor Unit from Header
Note 2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better.
OU
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m) = Actual piping length + "M" x Quantity of bent.

Trap (gas

OK NG pipe only)

h2
2m To indoor unit 2 m max To indoor unit
Downward To indoor unit Upward To indoor unit
T incline incline
S
Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
Header
A B Capped
H' (OU under IU)
H (OU above IU)

1st Joint a b c
Outdoor Twinning Kit
CMY-RP100VBK IU IU IU
C L1
L2

D E

h1
d e f g
Joint
IU IU IU

IU
Fig. 3-1-1B Piping scheme IU : Indoor unit, OU : Outdoor unit

Table 3-1-2-1. Piping length (m) Table 3-1-2-2. Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor unit model M (m/bent)
Total piping length S+T+A+B+C+D+E+a+b+c+d+e+f+g 300 *1 PUHY-RP400YSJM-B 0.50
Distance between OU and OU S+T 10 PUHY-RP450YSJM-B 0.50
Height between OU and OU h2 0.1 PUHY-RP500YSJM-B 0.50
Farthest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 120 150 PUHY-RP550YSJM-B 0.50
Farthest IU from the first Joint (L2) C+D+E+g / B+c 40 *2
Height between OU and IU (OU above IU) H 50
Height between OU and IU (OU under IU) H' 40
Height between IU and IU h1 15
OU: Outdoor Unit, IU: Indoor Unit

* 1 Do not exceed the amount of refrigerant to be charged written below.


PUHY-RP400-550YSJM-B: 0.39 L0 + 0.29 L1 + 0.2 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 25

L0: Total length of 22.2 liquid pipe (m)


L1: Total length of 19.05 liquid pipe (m)
L2: Total length of 15.88 liquid pipe (m)
L3: Total length of 12.7 liquid pipe (m)
L4: Total length of 9.52 liquid pipe (m)
L5: Total length of 6.35 liquid pipe (m)

* 2 When creating 1 system out of the pipework of 2 systems, (L1-L2) must be 40 m or less.

L1: Distance between system 1's original outdoor unit and system 1's original farthest indoor unit.
L2: Distance between system 2's original outdoor unit and system 2's original farthest indoor unit.
L1 L2

Table 3-1-2-3. Piping "A" size selection rule (mm) Table 3-1-2-4. Piping "B", "C", "D", "E" size selection rule (mm [in.])
Outdoor Pipe (Liquid) Pipe (Gas) Total down-stream Indoor capacity Pipe (Liquid) Pipe (Gas)
PUHY-RP400YSJM-B 15.88 34.93 ~ P80 9.52 [3/8"] 15.88 [5/8"]
PUHY-RP450YSJM-B 15.88 34.93 P81 ~ P160 12.7 [1/2"] 19.05 [3/4"]
PUHY-RP500YSJM-B 15.88 34.93 P161 ~ P330 12.7 [1/2"] 25.4 [1"]
PUHY-RP550YSJM-B 15.88 34.93 P331 ~ P630 15.88 [5/8"] 34.93 [1-3/8"]
P631 ~ 19.05 [3/4"] 41.28 [1-5/8"]

Table 3-1-2-5. Piping "a", "b", "c", "d", "e", "f", "g" size selection rule (mm [in.])
Indoor Unit size Pipe (Liquid) Pipe (Gas)
P20, P25, P32, P40 6.35 [1/4"] 12.70 [1/2"] Note 3. Indoor capacity is described as its model size.
For example, PEFY-P32VMM-E, its capacity is P32.
P50, P63, P71, P80 9.52 [3/8"] 15.88 [5/8"] Note 4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
P140 9.52 [3/8"] 19.05 [3/4"] For example, PEFY-P25VMM-E + PEFY-P32VMM-E: Total Indoor capacity = P25 + P32 = P57
Note 5. Piping size determined by the Total down-stream indoor capacity is NOT necessary
P200 12.7 [1/2"] 25.4 [1"] to be bigger than the up-stream one.
P250 12.7 [1/2"] 28.58 [1-1/8"] i.e. A >= B; A >= C >= D

SYSTEM DESIGN 223


3. Piping Design

3-1-3. PUHY-RP600-650YSJM-B

OU Note 1. No Joint after Header; Piping direct to Indoor Unit from Header
Note 2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better.
OU
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m) = Actual piping length + "M" x Quantity of bent.

Trap (gas

OK NG pipe only)

h2
2m To indoor unit 2 m max To indoor unit
Downward To indoor unit Upward To indoor unit
T incline incline
S
Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
Header
A B Capped
H' (OU under IU)
H (OU above IU)

1st Joint a b c
Outdoor Twinning Kit
CMY-RP100VBK IU IU IU
C L1
L2

D E

h1
d e f g
Joint
IU IU IU

IU
Fig. 3-1-1C Piping scheme IU : Indoor unit, OU : Outdoor unit

Table 3-1-3-1. Piping length (m) Table 3-1-3-2. Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor unit model M (m/bent)
Total piping length S+T+A+B+C+D+E+a+b+c+d+e+f+g 250 *1 PUHY-RP600YSJM-B 0.50
Distance between OU and OU S+T 10 PUHY-RP650YSJM-B 0.50
Height between OU and OU h2 0.1
Farthest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 120 150
Farthest IU from the first Joint (L2) C+D+E+g / B+c 40 *2
Height between OU and IU (OU above IU) H 50
Height between OU and IU (OU under IU) H' 40
Height between IU and IU h1 15
OU: Outdoor Unit, IU: Indoor Unit

* 1 Do not exceed the amount of refrigerant to be charged written below.


PUHY-RP600-650YSJM-B: 0.39 L0 + 0.29 L1 + 0.2 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 25

L0: Total length of 22.2 liquid pipe (m)


L1: Total length of 19.05 liquid pipe (m)
L2: Total length of 15.88 liquid pipe (m)
L3: Total length of 12.7 liquid pipe (m)
L4: Total length of 9.52 liquid pipe (m)
L5: Total length of 6.35 liquid pipe (m)

* 2 When creating 1 system out of the pipework of 2 systems, (L1-L2) must be 40 m or less.

L1: Distance between system 1's original outdoor unit and system 1's original farthest indoor unit.
L2: Distance between system 2's original outdoor unit and system 2's original farthest indoor unit.
L1 L2

Table 3-1-3-3. Piping "A" size selection rule (mm) Table 3-1-3-4. Piping "B", "C", "D", "E" size selection rule (mm [in.])
Outdoor Pipe (Liquid) Pipe (Gas) Total down-stream Indoor capacity Pipe (Liquid) Pipe (Gas)
PUHY-RP600YSJM-B 19.05 34.93 ~ P80 9.52 [3/8"] 15.88 [5/8"]
PUHY-RP650YSJM-B 19.05 41.28 P81 ~ P160 12.7 [1/2"] 19.05 [3/4"]
P161 ~ P330 12.7 [1/2"] 25.4 [1"]
P331 ~ P630 15.88 [5/8"] 34.93 [1-3/8"]
P631 ~ 19.05 [3/4"] 41.28 [1-5/8"]

Table 3-1-3-5. Piping "a", "b", "c", "d", "e", "f", "g" size selection rule (mm [in.])
Indoor Unit size Pipe (Liquid) Pipe (Gas) Note 3. Indoor capacity is described as its model size.
P20, P25, P32, P40 6.35 [1/4"] 12.70 [1/2"] For example, PEFY-P32VMM-E, its capacity is P32.
Note 4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
P50, P63, P71, P80 9.52 [3/8"] 15.88 [5/8"] For example, PEFY-P25VMM-E + PEFY-P32VMM-E: Total Indoor capacity = P25 + P32 = P57
P140 9.52 [3/8"] 19.05 [3/4"] Note 5. Piping size determined by the Total down-stream indoor capacity is NOT necessary
to be bigger than the up-stream one.
P200 12.7 [1/2"] 25.4 [1"] i.e. A >= B; A >= C >= D
P250 12.7 [1/2"] 28.58 [1-1/8"]

SYSTEM DESIGN 224


3. Piping Design

3-1-4. PUHY-RP700-900YSJM-B

OU OU Note 1. No Joint after Header; Piping direct to Indoor Unit from Header
Note 2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better.
OU
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m) = Actual piping length + "M" x Quantity of bent.

Trap (gas

OK NG pipe only)

h2 M N
2m To indoor unit 2 m max To indoor unit
Downward To indoor unit Upward To indoor unit
incline incline
T
S Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
Header
1st Outdoor Capped
A B
Twinning Kit
H' (OU under IU)
H (OU above IU)

1st Joint a b
2nd Outdoor c
Twinning Kit
IU IU IU
C L1
L2

D E

h1
d e f g
Joint
IU IU IU

IU
Fig. 3-1-1D Piping scheme IU : Indoor unit, OU : Outdoor unit

Table 3-1-4-1. Piping length (m) Table 3-1-4-2. Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor unit model M (m/bent)
Total piping length S+T+M+N+A+B+C+D+E+a+b+c+d+e+f+g 250 *1 PUHY-RP700YSJM-B 0.70
Distance between OU and OU S+T+M+N 10 PUHY-RP750YSJM-B 0.70
Height between OU and OU h2 0.1 PUHY-RP800YSJM-B 0.70
Farthest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 120 150 PUHY-RP850YSJM-B 0.80
Farthest IU from the first Joint (L2) C+D+E+g / B+c 40 *2 PUHY-RP900YSJM-B 0.80
Height between OU and IU (OU above IU) H 50
Height between OU and IU (OU under IU) H' 40
Height between IU and IU h1 15
OU: Outdoor Unit, IU: Indoor Unit

* 1 Do not exceed the amount of refrigerant to be charged written below.


PUHY-RP700-900YSJM-B: 0.39 L0 + 0.29 L1 + 0.2 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 25

L0: Total length of 22.2 liquid pipe (m)


L1: Total length of 19.05 liquid pipe (m)
L2: Total length of 15.88 liquid pipe (m)
L3: Total length of 12.7 liquid pipe (m)
L4: Total length of 9.52 liquid pipe (m)
L5: Total length of 6.35 liquid pipe (m)

* 2 When creating 1 system out of the pipework of 2 systems, (L1-L2) must be 40 m or less.

L1: Distance between system 1's original outdoor unit and system 1's original farthest indoor unit.
L2: Distance between system 2's original outdoor unit and system 2's original farthest indoor unit.
L1 L2

Table 3-1-4-3. Piping "A" size selection rule (mm) Table 3-1-4-4. Piping "B", "C", "D", "E" size selection rule (mm [in.])
Outdoor Pipe (Liquid) Pipe (Gas) Total down-stream Indoor capacity Pipe (Liquid) Pipe (Gas)
PUHY-RP700YSJM-B 19.05 41.28 ~ P80 9.52 [3/8"] 15.88 [5/8"]
PUHY-RP750YSJM-B 19.05 41.28 P81 ~ P160 12.7 [1/2"] 19.05 [3/4"]
PUHY-RP800YSJM-B 19.05 41.28 P161 ~ P330 12.7 [1/2"] 25.4 [1"]
PUHY-RP850YSJM-B 19.05 41.28 P331 ~ P630 15.88 [5/8"] 34.93 [1-3/8"]
PUHY-RP900YSJM-B 19.05 41.28 P631 ~ 19.05 [3/4"] 41.28 [1-5/8"]
For Piping size "M", "N", "S", "T", please refer to specification of the Twining kit
CMY-RP200VBK at the Outdoor unit's external drawing.

Table 3-1-4-5. Piping "a", "b", "c", "d", "e", "f", "g" size selection rule (mm [in.])
Indoor Unit size Pipe (Liquid) Pipe (Gas) Note 3. Indoor capacity is described as its model size.
P20, P25, P32, P40 6.35 [1/4"] 12.70 [1/2"] For example, PEFY-P32VMM-E, its capacity is P32.
Note 4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
P50, P63, P71, P80 9.52 [3/8"] 15.88 [5/8"] For example, PEFY-P25VMM-E + PEFY-P32VMM-E: Total Indoor capacity = P25 + P32 = P57
P140 9.52 [3/8"] 19.05 [3/4"] Note 5. Piping size determined by the Total down-stream indoor capacity is NOT necessary
to be bigger than the up-stream one.
P200 12.7 [1/2"] 25.4 [1"] i.e. A >= B; A >= C >= D
P250 12.7 [1/2"] 28.58 [1-1/8"]

SYSTEM DESIGN 225


3. Piping Design
3-1-5. Pipe diameter compatibility table

Standard
Usable (Unit performance will be affected.)
Usable (Vertical separation between OU and IU to be 20 m or less)
Usable (Piping length limitation will apply.)
Usable (Refrigerant charge amount limit will apply.)
Not use

(1) Main pipe


Outdoor model 200 250 300 350 400 450 500 550 600 650 700
Liquid 9.52 (45m or shorter) (30m or shorter) (25m or shorter)
12.7
(65m or shorter) (50m or shorter) (40m or shorter) (35m or shorter) (30m or shorter)
15.88 (70m or shorter) (60m or shorter) (55m or shorter)
19.05
22.2
Gas 15.88
19.05
22.2
25.4
28.58
34.93
41.28
Outdoor model 750 800 850 900
Liquid 9.52

12.7

15.88 (50m or shorter) (45m or shorter) (40m or shorter) (35m or shorter)


19.05
22.2
Gas 15.88
19.05
22.2
25.4
28.58
34.93
41.28

(2) Indoor pipe


Indoor model 15 20 25 32 40 50 63 71 80 100 125
Liquid 6.35 (30m or shorter) (20m or shorter)
9.52
12.7
15.88
Gas 12.7
15.88
19.05
22.2
25.4
28.58
Indoor model 140 200 250
Liquid 6.35

9.52
(25m or shorter) (15m or shorter)
12.7
15.88
Gas 12.7
15.88
19.05
22.2
25.4
28.58

(3) Joint pipe


Indoor model -80 -140 -160 -200 -300 -330 -400 -630 -650 -800 801-
Liquid 9.52 (15m or shorter) (15m or shorter) (10m or shorter) (10m or shorter)
12.7 (30m or shorter)
15.88 (30m or shorter)
19.05
22.2
Gas 15.88
19.05
22.2
25.4
28.58
34.93
41.28
Note
1) The in the table indicates that the existing piping system can be reused if the total amount of refrigerant charge in the existing system is less than the specified amount calculated
by using the following formulas:
PUHY-RP200-250YJM-B : 0.39L0+0.29L1+0.2L2+0.12L3+0.06L4<18
PUHY-RP300-900YJM-B : 0.39L0+0.29L1+0.2L2+0.12L3+0.06L4<25
L0 : Total length of 22.2 liquid pipe(m)
L1 : Total length of 19.05 liquid pipe(m)
L2 : Total length of 15.88 liquid pipe(m)
L3 : Total length of 12.7 liquid pipe(m)
L4 : Total length of 9.52 liquid pipe(m)
L5 : Total length of 6.35 liquid pipe(m)

SYSTEM DESIGN 226


3. Piping Design
3-1-6. Flow chart to check if the existing piping can be reused

Start

Are the existing pipes still


Do you know what kind of Exisiting piping cannot be NO
NO connected with indoor units and the
refrigerant oil is used in the reused. Use new piping. outdoor units? (excluding sealed
existing system? branch pipes that are
not in use)
YES Please contact your local If the piping is left disconnected, there is a
distributor. possibility of contamination and corrosion YES
inside the pipe. Do not reuse such pipes.
Is the refrigerant oil SUNISO, MS, Is the existing unit
Barrel Freeze, HAB or Freol? Mitsubishi Electric unit?
NO NO

YES YES

Is the capacity of new


replacement unit the same as that
The vertical height NO of the existing unit?
difference needs to be 50m or
less between IU and OU (if OU is
below IU, 40m or less). And also, height YES
NO
difference between each IU is
15m or less.

Check the piping size and length.


YES Take the refrigerant oil recovery
procedures described in the Mineral
Oil Collection (Refrigerant Oil
Does the piping diameter
Recovery) Manual.
and piping length match
NO our guideline?

YES

Is the branch pipe shape T, Y NO


or header branching?

YES

NO Check the branch pipe type


and the reusability standards
to make a decision.
Please change to the specified
branch pipe.
YES

Do the existing NO
pipes hold enough
air tightness?

YES YES Did the existing unit before the NO


replacement operate without
any gas leak?
Please have air tight test on site.

YES NO
Is the piping air tight?

All branch pipes are connected NO Cut the branch pipe completely that are not
with the indoor units. in use, and seal it.

YES

NO
Is the piping correctly covered
with heat insulation material? Conduct heat insulation.

YES

Does the piping meet the


strength requirements?
NO (material,thickness,anti
corrosion)

YES

Use a new piping. The existing piping can be reused.

SYSTEM DESIGN 227


3. Piping Design
3-2. Refrigerant charging calculation
Sample connection (with 8 indoor units)
OU OU
OU Note 1. No Joint after Header; Piping direct to Indoor Unit from Header
Note 2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better.
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m) = Actual piping length + "M" x Quantity of bent.

Trap (gas

OK NG pipe only)

A B 2m To indoor unit 2 m max To indoor unit


D Downward To indoor unit Upward To indoor unit
incline incline

C Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.

Outdoor Twinning Kit


CMY-RP200VBK E F G I

a b c d
1st Joint

IU IU IU IU
1 : P250 2 : P200 3 : P80 4 : P71

J K M

e f g i

IU IU IU IU
5 : P140 6 : P125 7 : P63 8 : P25

Amount of refrigerant to be charged


Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant
for each pipe on site.
Record the size of each liquid pipe and the amount of refrigerant that was charged on the outdoor unit for future reference.

Calculating the amount of refrigerant to be charged


The amount of refrigerant to be charged is calculated with the size of the on-site-installed liquid pipes and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1 kg. (i.e., 16.08 kg = 16.1 kg)

<Amount of refrigerant to be charged>


Calculating the amount of refrigerant to be charged
Total length of 22.2 Total length of 19.05 Total length of 15.88 Total length of 12.7 Total length of 9.52 Total length of 6.35 Total capacity of connected Charged amount
liquid pipe x 0.39 liquid pipe x 0.29 liquid pipe x 0.2 liquid pipe x 0.12 liquid pipe x 0.06 liquid pipe x 0.024 indoor units

+ + + + + + ~80 2.0 kg
81~160 2.5 kg
(m) x 0.39 (kg/m) (m) x 0.29 (kg/m) (m) x 0.2 (kg/m) (m) x 0.12 (kg/m) (m) x 0.06 (kg/m) (m) x 0.024 (kg/m)
161~330 3.0 kg
331~390 3.5 kg

Amount of factory- Sample calculation 391~480


481~630
4.5 kg
5.0 kg
charged refrigerant 631~710 6.0 kg
Indoor 711~800 8.0 kg
Outdoor unit model Charged amount A: 9.52 3m 1: P200 a : 12.7 15 m 801~890 9.0 kg
RP200 6.5kg B: 12.70 2m 2: P200 b : 12.7 15 m 891~1070 10.0 kg
RP250 C: 19.05 2m 3: P80 c : 9.52 5m
1071~1170 12.0 kg
D: 15.88 1m 4: P71 d : 9.52 5m
RP300 9.0kg E: 19.05 10 m e : 9.52 5m
5: P125
RP350 F: 15.88 10 m 6: P125 f : 9.52 5m
G: 15.88 5m 7: P63 g : 9.52 5m
I: 12.7 5m 8: P25 i : 6.35 5m
J: 15.88 20 m
K: 12.7 5m
M: 12.7 5m

Total length for 19.05 C + E = 12


each pipe size: 15.88 D + F + G + J = 1 + 10 + 5 + 20 = 36 m
12.70 B + I + K + M + a + b = 2 + 5 + 5 + 5 + 15 + 15 = 47 m
9.52 A + c + d + e + f + g = 3 + 5 + 5 + 5 + 5 + 5 = 23 m
6.35 i=5m
This yields the following result: = 0.29 x 12 + 0.2 x 36 + 0.12 x 47 + 0.06 x 23 + 0.024 x 5 + 9
= 26.82 kg
= 26.9 kg

SYSTEM DESIGN 228


4. Outdoor Installation
4-1. Requirement on installation site
4. Outdoor Installation

1. No direct thermal radiation to the unit.


2. No possibility of annoying the neighbors by the sound of the unit.
Valves and refrigerant flow on the outdoor unit may generate noise.
3. Avoid the sites where strong winds blow.
4. With strength to bear the weight of the unit.
5. Drain flow from the unit is cared at heating mode.
6. Enough space for installation and service as shown at 4-2.
7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.
8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.

SYSTEM DESIGN 229


4. Outdoor Installation
4-2. Spacing

In case of single installation


Secure enough space around the unit as shown in the figure.
<A> : Top view A : Front C : Back
<B> : Side view B : Unit height D : Air outlet guide (Procured at the site)
<C> : When there is little space up to an obstruction

(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall

300*
[11-13/16]

A 450*
[17-23/32]

15* [19/32] 15* [19/32]


<A>
(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall

100*
[3-15/16]

A 450*
[17-23/32]

50* [1-31/32] 50* [1-31/32]


<A>
(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction
h
H

B
h

A
H
[19-11/16]
500

<B>
When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below,
add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.

<Wall height limit> Front: Up to the unit height


Back: Up to 500mm [19-11/16 in.] from the unit bottom
Side: Up to the unit height
If the unit cannot be kept clear of the wall, please change the direction of the air outlet of the unit to blow against the wall to avoid air short cycle.
(4) If there are obstacles at the upper part of the unit

1000
45 [39-3/8]
D
240
[9-15/32]

A C

(Unit : mm [in.])
<C>
50 [1-31/32]

SYSTEM DESIGN 230


4. Outdoor Installation

In case of collective installation and continuous installation


A : Front C : Wall height (H)
B : Must be open
When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and
passageways between groups of units as shown in the figures.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
an asterisk.
If there is a wall at both the front and the rear of the unit, install up to six units consecutively in the side direction and
provide a space of 1000mm or more as inlet space/passage space for each six units.

[11-13/16]

[11-13/16]
300*

300*
C C

B B
A

[35-7/16]
900
B A B
[17-23/32]
450*

C 30
[1-3/16]

[11-13/16] [11-13/16]
300*
C
[3-15/16]
100*

300*
C
B B
A
[17-23/32]
450*

C 100
[3-15/16]

900
[35-7/16]
A B

B 1000*
[39-3/8] B

A A A
C C

450* 450 450 100*


[17-23/32] [17-23/32] [17-23/32] [3-15/16]
B
15*

A A A

(Unit : mm [in.])
450 450
[17-23/32] [17-23/32]

SYSTEM DESIGN 231


4. Outdoor Installation
4-3. Piping direction

4-3-1. Lifting method

When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.
Support the unit at four points with two ropes, and avoid giving mechanical shock.
Suspension rope angle must be 40 or less, so as to avoid compressing fan guard.
Use two ropes, each at least 8m [26 ft.] in length
Use ropes strong enough to support the weight of the unit.
Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-
ed.)
Use protective pads to keep the ropes from scratching the panels on the unit.

(Unit : m [ft.])

8 [26] 40

8 [26]

CAUTION
Exercise caution when transporting products.

Products weighing more than 20 kg [45 LBS] should not be carried alone.
Do not carry the product by the PP bands.
To avoid the risk of injury, do not touch the heat exchanger fins.
Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.
When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.

SYSTEM DESIGN 232


4. Outdoor Installation

4-3-2. Installation

Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or
during an earthquake.
Install the unit on a durable base made of such materials as concrete or angle steel.
Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
noise from being transmitted from the unit through walls and floors.
When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.
Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16 in.].
This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.

WARNING

A : M10 anchor bolt procured at the site. Properly install the unit on a surface that can withstand the weight of
the unit. Unit installed on an unstable surface may fall and cause injury.
B : Corner is not seated.
C : Fixing bracket for hole-in anchor bolt
(3 locations to fix with screws). WARNING
D : Detachable leg Take appropriate safety measures against strong winds and earth-
quakes to prevent the unit from falling.
<Without detachable leg>
[1-3/16 in.]
30mm

Install the unit in such a


way that the corner of
the angle bracket at the
base of the unit shown B
in the figure is securely
supported. The brackets
A may bend if they are not
securely supported. C

<With detachable leg>


[1-3/16 in.]
30mm

Install the unit in such a


way that the corner of
D the angle bracket at the B
base of the unit shown
in the figure is securely
supported. The brackets
A may bend if they are not
securely supported. C D

Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor units
during operation.), piping route, and wiring route when performing foundation work.
4-3-3. Anchor bolt positions
Individual installation Collective installation (Unit : mm [in.])
7243 [(28-13/32~28-5/8)]

7243 [(28-13/32~28-5/8)]

30 [1-3/16] 30 [1-3/16]
A A 190 [7-1/2] A 190 [7-1/2] A
(For maintenance)
Leave a minimum of 30 mm [1-3/16 in.] between units.

PUHY RP200-RP350
A 7602 [29-15/16(29-27/32~30)]

SYSTEM DESIGN 233


4. Outdoor Installation

4-3-4. Installation

When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height.

RP200-RP350
(Unit : mm [in.])
221 150
[8-23/32] [5-29/32]
251 83 2X2-14X20 Oval hole
[9-29/32] [3-9/32]
145 [5-23/32]
86 [3-13/32]
131 [5-3/16]

[23/32]
186
18

[7-11/32]
A

[28-13/32~28-5/8]
(Mounting pitch)
(760 [29-15/16])
724(721 727)
92 [3-5/8]

Refrigerant service
valve <liquid>
Model
Refrigerant service
valve <gas> PUHY-RP200YJM-B(-BS)
PUHY-RP250YJM-B(-BS) 145 [5-23/32]
PUHY-RP300YJM-B(-BS)
[23/32]

80 760 [29-15/16] 80
18

[3-5/32] (Mounting pitch) [3-5/32]


PUHY-RP350YJM-B(-BS) 150 [5-29/32]
Bottom view

Installation base perpendicular to the units front panel

4-3-5. Refrigerant pipe routing

The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.

This unit allows two types of pipe routing:


Bottom piping
Front piping

CAUTION
To prevent small animals, water, and snow from
entering the unit and damage its parts, close the
gap around the edges of through holes for pipes
and wires with filler plates.
Filler plate Fill the gap at the site
(not supplied)

SYSTEM DESIGN 234


4. Outdoor Installation

4-3-6. Twinning on the outdoor unit side


The tilt angle of the twinning pipe
The tilt angle of the twinning pipe must be within 15 with the horizontal plane.
Tilting the twinning pipe more than specified will cause damage to the unit.
The length of the straight part of the pipe before the branching
For the twinning kit, always use the accessory piping parts. Note: See the following drawing for the fitting
The length of the straight part of pipe connected in front of the position of the twinning pipe.
Reducer
twinning pipe must be 500 mm [19 in.] or longer.
(Connect the field piping so that the length of the straight part

15
of pipe connected in front of the twinning pipe can be 500 mm
[19 in.] or longer.)
The tilt angle of the reducer should be
If the length is less than 500 mm [19 in.], it will cause damage
within 15with the horizontal plane.
to the unit.

The piping connection


When connecting the twinning kit to the outdoor unit, note the following:
If the length of piping from the twinning kit to the outdoor unit is more than 2 m [6 ft.],
install a trap within 2 m [6 ft.] from the outdoor unit. The height of the trap must be 200
mm [7 in.] or higher.

<2 m [6 ft.] or less>


<More than 2 m [6 ft.]>
Trap
(gas pipe only)

200 mm [7 in.]
To Indoor unit or over To Indoor unit To Indoor unit
2m
Less than 2 m [6 ft.]

When installing the twinning kit in a higher position than the outdoor unit base, make
sure that the twinning kit is installed in a position lower than 200 mm [7 in.] from the
outdoor unit base.

Outdoor unit 1 Outdoor unit 2


<PUHY-RP500YSJM-B>

Twinning pipe1
To Indoor unit

200 mm [7 in.]
or less

<PUHY-RP900YSJM-B>
Outdoor unit 1 Outdoor unit 2 Outdoor unit 3

Twinning pipe 1 Twinning pipe 2


To Indoor unit
200 mm [7 in.]
or less

SYSTEM DESIGN 235


4. Outdoor Installation

4-3-7. Twinning on the outdoor unit side


See the following drawing for connecting the pipes between the outdoor units.
<PUHY-RP500YSJM-B>

Field piping

Twinning kit
The Field piping
mus length o
t be f
500 the stra
mm ig
[19 i ht pipe
n.] o
r lon
ger

<PUHY-RP900YSJM-B>

Field piping

Twinning kit
Field piping
The
le Twinning kit
mus ngth of
t be t
500 he straig
mm ht pip
[19 i Field piping
n.] o e
r lon
ger The
le
mus ngth of
t be t
500 he straig
mm h
[19 i t pipe
n.] o
r lon
ger

CAUTION
The length of the straight pipe must be 500mm[19 in.] or longer.
If not, it may cause improper operation.

SYSTEM DESIGN 236


4. Outdoor Installation
4-4. Weather countermeasure

Snow hood
906 [35-11/16] 750 [29-17/32] Unit : mm[in]
800 [31-1/2]

(920 [36-1/4])
1324 [52-5/32]

(760) [29-15/16]
[3-13/32]
86
H

(See Note 1)

453 [17-27/32] 910 [35-27/32] 453 [17-27/32] 760 [29-15/16] 453 [17-27/32]

<Front view> <Side view>


Outlet Inlet

Note:
1.Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base shall
not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind slip
through the structure. (If frame base is too wide, snow will be accumulated on it.)
2.Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3.Build frame base at customer referring to this figure.
Material: Galvanized steel plate 1.2T [1/16 in T]
Painting: Overall painting with polyester powder
Color: Munsell 5Y8/1 (same as that of unit)
4.When the unit is used in a cold region and the heating operation is continuously performed for a long time when the outside air
temperature is below freezing, install a heater to the unit base or take other appropriate measures to prevent water from
freezing on the base.

Countermeasure to wind
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.

Wind

Install the outdoor unit where seasonal Install the outdoor unit to avoid having
winds do not blow directly against the seasonal winds against the front of air
unit, such as behind a building. outlet/inlet on the unit.

SYSTEM DESIGN 237


4. Outdoor Installation
4-5. Caution on selecting outdoor units

Consult your dealer when the following issues on Y system are the key concern.
Warm air may flow out from the indoor unit during heating Thermo-OFF.
Refrigerant flow sound may occur in the rooms with low background noise such as hotel rooms, hospital rooms, bedrooms, or
conference rooms.
To avoid the above issues on Y system, changing board settings on the indoor and outdoor units is required.
Ask AC&R Works for details.

SYSTEM DESIGN 238


5. Caution for refrigerant leakage
The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.
5. Caution for refrigerant leakage

The following standard may be applicable if no local regulation or standard is available.

5-1. Refrigerant property


R410A refrigerant is harmless and incombustible. The R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room
has possibility to lead to a hypoxia situation. Therefore, the Critial concentration specified below shall not be exceeded even if the leakage
happens.
Critical concentration
Critical concentration hereby is the refrigerant concentration in which no human body would be hurt if immediate measures can be taken
when refrigerant leakage happens.
Critical concentration of R410A: 0.30kg/m3
(The weight of refrigeration gas per 1 m3 air conditioning space.);
The Critical concentration is subject to ISO5149, EN378-1.
For the CITY MULTI system, the concentration of refrigerant leaked should not have a chance to exceed the Critical concentration in
any situntion.
5-2. Confirm the Critical concentration and take countermeasure
The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)
leaked into a room divided by its room capacity (V).It is referable to Fig.5-1.The refrigerant of Outdoor unit here includes its original
charge and additional charge at the site.
The additional charge is calculated according to 3-2 .Refrigerant charging calculation and shall not be over charged at the site.
Procedure 5-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take countermeasures against
a possible leakage.
Outdoor unit (No.1) Outdoor unit (No.1) Outdoor unit (No.2)

Flow of refrigerant Flow of refrigerant Flow of refrigerant

Indoor unit Indoor unit

Maximum refrigerant leakage concentration (Rmax) Maximum refrigerant leakage concentration (Rmax)
Rmax=Wmax / V (kg/m3) Rmax=Wmax / V (kg/m3) W1: Refrigerant weight of Outdoor unit No.1
where, Wmax=W1+W2 W2: Refrigerant weight of Outdoor unit No.2
Fig. 5-1 The maximum refrigerant leakage concentration
5-2-1.Find the room capacity (V),
If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space are
considered as one.The total space shall be added up.
5-2-2.Find the possible maximum leakage (Wmax) in the room.If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refriger-
ant of the Outdoor units.
5-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).
5-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3.
If no, then the CITY MULTI is safe against refrigerant leakage.
If yes, following countermeasure is recommended to do at site.
Countermeasure 1:Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.
e.g.make the upper and lower seams of door big enough.
Countermeasure 2:Smaller total charge (making Wmax smaller)
e.g.Avoid connecting more than 1 Outdoor unit to one room.
e.g.Using smaller model size but more Outdoor units.
e.g.Shorten the refrigerant piping as much as possible.
Countermeasure 3:Fresh air in from the ceiling (Ventilation)
As the density of the refrigerant is bigger than that of the air.Fresh air supply from the ceiling is better than air exhausting from the ceiling.
Fresh air supply solution refers to Fig.5-2~4.
Fresh air supply fan (always ON) Fresh air supply fan Refrigerant pipe (high pressure pipe)
Fresh air supply fan
Refrigerant pipe Refrigerant pipe
Refrigerant stop valve
to Outdoor unit to Outdoor unit
to Outdoor unit

Indoor unit Indoor unit


Indoor space Indoor space Indoor unit
Indoor space

(Floor) (Floor)
Opening (Floor)
Opening
Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).
[At 0.3m height from the floor]
[At 0.3m height from the floor]

Fig.5-2.Fresh air supply always ON Fig.5-3.Fresh air supply upon sensor action Fig.5-4.Fresh air supply and refrigerant
shut-off upon sensor action
Note 1.Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens.
Note 2.In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.
The piping should consider the extension due to the temperature variation.

SYSTEM DESIGN 239


SYSTEM DESIGN 240
SYSTEM DESIGN R2 SERIES

1. Electrical work.................................................................................................................................................. 242


1-1.General cautions ....................................................................................................................................... 242
1-2.Power supply for Indoor unit and Outdoor unit .......................................................................................... 243
1-3.Power cable specifications ........................................................................................................................ 247
1-4.Power supply examples............................................................................................................................. 248
2. M-NET control.................................................................................................................................................. 249
2-1.Transmission cable length limitation.......................................................................................................... 249
2-2.Transmission cable specifications ............................................................................................................. 250
2-3.System configuration restrictions............................................................................................................... 255
2-4.Address setting.......................................................................................................................................... 258
3. Piping Design................................................................................................................................................... 271
3-1.Piping Design ............................................................................................................................................ 271
3-2.Refrigerant charging calculation ................................................................................................................ 275
4. Outdoor Installation.......................................................................................................................................... 276
4-1.Requirement on installation site ................................................................................................................ 276
4-2.Spacing...................................................................................................................................................... 277
4-3.Piping direction .......................................................................................................................................... 279
4-4.Weather countermeasure .......................................................................................................................... 282
5. Caution for refrigerant leakage ........................................................................................................................ 283
5-1.Refrigerant property................................................................................................................................... 283
5-2.Confirm the Critical concentration and take countermeasure.................................................................... 283

SYSTEM DESIGN R2 SERIES 241


1. Electrical work
1-1. General cautions
1. Electrical work
I.

Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in.] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 380~415V(220~240V) power source to terminal block of transmission cable. If connected,electrical parts
will be burnt out.
Use 2-core shield cable for transmission cable. If transmission cables of different systems are wired with the same
multiple-core cable, the resultant poor transmitting and receiving will cause erroneous operations.

Indoor unit Indoor unit


Outdoor Outdoor

OK NO
unit unit

2-core shield cable


Multiple-
core cable Remote
Remote controller
controller
BC controller BC controller

2-core shield cable

SYSTEM DESIGN 242


1. Electrical work
1-2. Power supply for Indoor unit and Outdoor unit
1-2-1. Electrical characteristics of Indoor unit
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps
IFM :Indoor Fan Motor Output : Fan motor rated output
Power supply IFM
PMFY-P-VBM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PMFY-P20VBM-E 0.25 0.028 0.20
PMFY-P25VBM-E 220-240V / 50Hz Max.: 264V 0.26 0.028 0.21
PMFY-P32VBM-E 220V / 60Hz Min.: 198V 0.26 0.028 0.21
PMFY-P40VBM-E 0.33 0.028 0.26

Power supply IFM


PLFY-P-VCM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PLFY-P20VCM-E 0.29 0.011 0.23
PLFY-P25VCM-E Max.: 264V 0.29 0.015 0.23
220-240V / 50Hz
PLFY-P32VCM-E Min.: 198V 0.35 0.020 0.28
PLFY-P40VCM-E 0.35 0.020 0.28

Power supply IFM


PLFY-P-VBM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PLFY-P32VBM-E 0.28 0.050 0.22
PLFY-P40VBM-E 0.36 0.050 0.29
PLFY-P50VBM-E 0.36 0.050 0.29
220-240V / 50Hz Max.: 264V
PLFY-P63VBM-E 0.45 0.050 0.36
220V / 60Hz Min.: 198V
PLFY-P80VBM-E 0.64 0.050 0.51
PLFY-P100VBM-E 1.25 0.120 1.00
PLFY-P125VBM-E 1.34 0.120 1.07

Power supply IFM


PLFY-P-VLMD-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PLFY-P20VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37
PLFY-P25VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37
PLFY-P32VLMD-E 0.45 / 0.46 0.015 0.36 / 0.37
PLFY-P40VLMD-E 0.50 / 0.53 0.015 0.40 / 0.42
220-240V / 50Hz Max.: 264V
PLFY-P50VLMD-E 0.51 / 0.54 0.020 0.41 / 0.43
220-230V / 60Hz Min.: 198V
PLFY-P63VLMD-E 0.61 / 0.64 0.020 0.49 / 0.51
PLFY-P80VLMD-E 0.90 / 0.93 0.020 0.72 / 0.74
PLFY-P100VLMD-E 0.94 / 1.10 0.030 0.75 / 0.88
PLFY-P125VLMD-E 1.69 / 1.69 0.078x2 1.35 / 1.35

Power supply IFM


PEFY-P-VMR-E-L/R
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P20VMR-E-L/R 0.37 / 0.37 0.018 0.29 / 0.29
220-240V / 50Hz Max.: 264V
PEFY-P25VMR-E-L/R 0.37 / 0.37 0.018 0.29 / 0.29
220-230V / 60Hz Min.: 198V
PEFY-P32VMR-E-L/R 0.43 / 0.48 0.023 0.34 / 0.38

Power supply IFM


PEFY-P-VMS1-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P15VMS1-E 0.63 / 0.63 0.096 0.50 / 0.50
PEFY-P20VMS1-E 0.70 / 0.70 0.096 0.56 / 0.56
PEFY-P25VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60
220-240V / 50Hz Max.: 264V
PEFY-P32VMS1-E 0.75 / 0.75 0.096 0.60 / 0.60
220-240V / 60Hz Min.: 198V
PEFY-P40VMS1-E 0.83 / 0.82 0.096 0.66 / 0.65
PEFY-P50VMS1-E 1.02 / 1.00 0.096 0.81 / 0.80
PEFY-P63VMS1-E 1.08 / 1.07 0.096 0.86 / 0.85

SYSTEM DESIGN 243


1. Electrical work

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps


IFM :Indoor Fan Motor Output : Fan motor rated output
Power supply IFM
PEFY-P-VMS1L-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P15VMS1L-E 0.46 / 0.46 0.096 0.37 / 0.37
PEFY-P20VMS1L-E 0.54 / 0.54 0.096 0.43 / 0.43
PEFY-P25VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47
220-240V / 50Hz Max.: 264V
PEFY-P32VMS1L-E 0.59 / 0.59 0.096 0.47 / 0.47
220-240V / 60Hz Min.: 198V
PEFY-P40VMS1L-E 0.68 / 0.68 0.096 0.54 / 0.54
PEFY-P50VMS1L-E 0.84 / 0.84 0.096 0.67 / 0.67
PEFY-P63VMS1L-E 0.91 / 0.91 0.096 0.73 / 0.73

Power supply IFM


PEFY-P-VMH-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P40VMH-E 1.21 / 1.61 0.08 0.97 / 1.29
PEFY-P50VMH-E 1.21 / 1.61 0.08 0.97 / 1.29
PEFY-P63VMH-E 1.49 / 1.95 0.12 1.19 / 1.56
PEFY-P71VMH-E 220-240V / 50Hz Max.: 264V 1.58 / 2.18 0.14 1.26 / 1.74
PEFY-P80VMH-E 220-240V / 60Hz Min.: 198V 1.85 / 2.40 0.18 1.48 / 1.92
PEFY-P100VMH-E 3.03 / 3.93 0.26 2.42 / 3.14
PEFY-P125VMH-E 3.03 / 3.93 0.26 2.42 / 3.14
PEFY-P140VMH-E 3.10 / 3.98 0.26 2.48 / 3.18
PEFY-P200VMH-E 380-415V / 50Hz Max.: 456V 2.03 / 2.33 0.76 1.62 / 1.86
PEFY-P250VMH-E 380-415V / 60Hz Min.: 342V 2.50 / 2.88 1.08 2.00 / 2.30

Power supply IFM


PEFY-P-VMA-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PEFY-P20VMA-E 1.03 0.085 0.82
PEFY-P25VMA-E 1.03 0.085 0.82
PEFY-P32VMA-E 1.18 0.085 0.95
PEFY-P40VMA-E 1.43 0.085 1.14
PEFY-P50VMA-E 1.54 0.085 1.23
220-240V / 50Hz Max.: 264V
PEFY-P63VMA-E 2.22 0.121 1.78
220-240V / 60Hz Min.: 198V
PEFY-P71VMA-E 2.46 0.121 1.97
PEFY-P80VMA-E 2.47 0.121 1.98
PEFY-P100VMA-E 3.30 0.244 2.64
PEFY-P125VMA-E 3.39 0.244 2.71
PEFY-P140VMA-E 3.29 0.244 2.63

Power supply IFM


PEFY-P-VMAL-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PEFY-P20VMAL-E 0.92 0.085 0.74
PEFY-P25VMAL-E 0.92 0.085 0.74
PEFY-P32VMAL-E 1.07 0.085 0.86
PEFY-P40VMAL-E 1.32 0.085 1.06
PEFY-P50VMAL-E 1.40 0.085 1.12
220-240V / 50Hz Max.: 264V
PEFY-P63VMAL-E 2.08 0.121 1.67
220-240V / 60Hz Min.: 198V
PEFY-P71VMAL-E 2.32 0.121 1.86
PEFY-P80VMAL-E 2.36 0.121 1.89
PEFY-P100VMAL-E 3.19 0.244 2.55
PEFY-P125VMAL-E 3.27 0.244 2.62
PEFY-P140VMAL-E 3.17 0.244 2.53

Power supply IFM


PEFY-P-VMH-E-F
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PEFY-P80VMH-E-F 220-240V / 50Hz Max.: 264V 0.92 / 1.15 0.09 0.73 / 0.92
PEFY-P140VMH-E-F 208-230V / 60Hz Min.: 187V 1.58 / 1.84 0.14 1.26 / 1.47
PEFY-P200VMH-E-F 380-415V / 50Hz Max.: 456V 0.73 / 0.93 0.20 0.58 / 0.74
PEFY-P250VMH-E-F 380-415V / 60Hz Min.: 342V 0.85 / 1.08 0.23 0.68 / 0.86

SYSTEM DESIGN 244


1. Electrical work
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps
IFM :Indoor Fan Motor Output : Fan motor rated output

Power supply IFM


PKFY-P-VBM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PKFY-P15VBM-E 0.25 0.017 0.20
220-240V / 50Hz Max.: 264V
PKFY-P20VBM-E 0.25 0.017 0.20
220V / 60Hz Min.: 198V
PKFY-P25VBM-E 0.25 0.017 0.20

Power supply IFM


PKFY-P-VHM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PKFY-P32VHM-E 0.38 0.030 0.30
220-240V / 50Hz Max.: 264V
PKFY-P40VHM-E 0.38 0.030 0.30
220V / 60Hz Min.: 198V
PKFY-P50VHM-E 0.38 0.030 0.30

Power supply IFM


PKFY-P-VKM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PKFY-P63VKM-E 220-240V / 50Hz Max.: 264V 0.36 0.056 0.29
PKFY-P100VKM-E 220V / 60Hz Min.: 198V 0.63 0.056 0.50

Power supply IFM


PCFY-P-VKM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PCFY-P40VKM-E 0.35 0.090 0.28
PCFY-P63VKM-E 220-240V / 50Hz Max.: 264V 0.41 0.095 0.33
PCFY-P100VKM-E 220V / 60Hz Min.: 198V 0.81 0.160 0.65
PCFY-P125VKM-E 0.95 0.160 0.76

Power supply IFM


PFFY-P-VKM-E
Volts / Hz Range +-10% MCA(A) Output(kW) FLA(A)
PFFY-P20VKM-E 0.25 0.03x2 0.20
PFFY-P25VKM-E Max.: 264V 0.25 0.03x2 0.20
220-240V / 50Hz
PFFY-P32VKM-E Min.: 198V 0.25 0.03x2 0.20
PFFY-P40VKM-E 0.30 0.03x2 0.24

Power supply IFM


PFFY-P-VLEM-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PFFY-P20VLEM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P25VLEM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P32VLEM-E 220-240V / 50Hz Max.: 264V 0.36 / 0.38 0.018 0.29 / 0.30
PFFY-P40VLEM-E 208-230V / 60Hz Min.: 187V 0.40 / 0.41 0.030 0.32 / 0.33
PFFY-P50VLEM-E 0.50 / 0.51 0.035 0.40 / 0.41
PFFY-P63VLEM-E 0.58 / 0.59 0.050 0.46 / 0.47

SYSTEM DESIGN 245


1. Electrical work

Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps


IFM :Indoor Fan Motor Output : Fan motor rated output
Power supply IFM
PFFY-P-VLRM-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PFFY-P20VLRM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P25VLRM-E 0.24 / 0.31 0.015 0.19 / 0.25
PFFY-P32VLRM-E 220-240V / 50Hz Max.: 264V 0.36 / 0.38 0.018 0.29 / 0.30
PFFY-P40VLRM-E 208-230V / 60Hz Min.: 187V 0.40 / 0.41 0.030 0.32 / 0.33
PFFY-P50VLRM-E 0.50 / 0.51 0.035 0.40 / 0.41
PFFY-P63VLRM-E 0.58 / 0.59 0.050 0.46 / 0.47

Power supply IFM


PFFY-P-VLRMM-E
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
PFFY-P20VLRMM-E 0.59 / 0.58 0.096 0.47 / 0.46
PFFY-P25VLRMM-E 0.59 / 0.58 0.096 0.47 / 0.46
PFFY-P32VLRMM-E Max.: 264V 0.69 / 0.69 0.096 0.55 / 0.55
220-240V / 50Hz
PFFY-P40VLRMM-E Min.: 198V 0.78 / 0.76 0.096 0.62 / 0.61
PFFY-P50VLRMM-E 0.80 / 0.79 0.096 0.64 / 0.63
PFFY-P63VLRMM-E 0.93 / 0.93 0.096 0.74 / 0.74

Power supply IFM


GUF-RDH3
Volts / Hz Range +-10% MCA(A) (50 / 60Hz) Output(kW) FLA(A) (50 / 60Hz)
GUF-50RD(H)3 220-240V / 50Hz Max.: 264V 1.85 / 1.85 0.081x2 1.48 / 1.48
GUF-100RD(H)3 220V / 60Hz Min.: 198V 3.49 / 3.49 0.16x2 2.79 / 2.79

SYSTEM DESIGN 246


1. Electrical work
1-2-2. Electrical characteristics of Outdoor unit at cooling mode
Units Power supply Compressor FAN RLA (A) (50 / 60Hz)
Model Unit Combination
Hz Volts Voltage range MCA(A) Output (kW) SC (A) Output (kW) Cooling Heating
PURY-RP200YJM-B(-BS) - 11.8 5.4 0.92 8.3/7.9/7.6 9.2/8.8/8.5
380
Max : 456V
PURY-RP250YJM-B(-BS) - 50/60 400 16.4 6.8 8 0.92 11.5/10.9/10.5 12.1/11.5/11.1
Min : 342V
415
PURY-RP300YJM-B(-BS) - 20.0 7.8 0.92 14.0/13.3/12.9 14.6/13.9/13.4

1-3. Power cable specifications

Thickness of wire for main power supply, capacities of the switch and system impedance
Minimum wire thickness (mm2) Local swtich (A) Breaker for wiring Max. Permissive
Model Breaker for current leakage
Main cable Branch Ground Capacity Fuse (NFB) (A) System Impedance

PURY-RP200YJM-B 4 - 4 30A 100mA 0.1sec. or less 25 25 30 *1


Outdoor unit PURY-RP250YJM-B 4 - 4 30A 100mA 0.1sec. or less 25 25 30 *1
PURY-RP300YJM-B 4 - 4 30A 100mA 0.1sec. or less 32 32 30 *1
F0 = 20 or less *2 1.5 1.5 1.5 20A current sensitivity *3 20 20 20 (apply to IEC61000-3-3)
Total operating
current of F0 = 30 or less *2 2.5 2.5 2.5 30A current sensitivity *3 30 30 30 (apply to IEC61000-3-3)
the indoor unit F0 = 40 or less *2 4.0 4.0 4.0 40A current sensitivity *3 40 40 40 (apply to IEC61000-3-3)
*1: Meet technical requirements of IEC61000-3-3

*2: Please take the larger of F1 or F2 as the value for F0.


F1 = Total operating maximum current of the indoor units 1.2 Indoor unit V1
Type A PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, 1.6
F2 = (V1 Quantity of Type A) + (V1 Quantity of Type B) + (V1 Quantity of Others)
PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM
Type B PEFY-VMA(L) 3.2
Others Other indoor unit 0

*3: Current sensitivity is calculated using the following formula.


G1 = (V2 Quantity of Type 1) + (V2 Quantity of Type 2) + (V2 Quantity of Others) + (V3 Wire length [km])

G1 Current sensitivity Indoor unit V2 Wire thickness (mm2) V3


30mA or less 30mA 0.1sec. or less Type 1 PLFY-VBM, PMFY-VBM, PEFY-VMS1(L), PCFY-VKM, 2.4
1.5 48
PKFY-VHM, PKFY-VKM, PFFY-VKM, PFFY-VLRMM
100mA or less 100mA 0.1sec. or less Type 2 PEFY-VMA(L) 1.6 2.5 56
Others Other indoor unit 0 4.0 66

1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.

Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.
Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
Check the existing wires for damage to insulation by measuring the resistance between the lead and the ground with a 500V ohmmeter. If the insulation resistance is less than 100 M,re-
place the wires.

This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the interface point (power service box) of
the user's supply.

The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2) at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to
a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).

Ssc(*2)
Model Ssc(MVA)
PURY-RP200YJM 1.25
PURY-RP250YJM 1.36
PURY-RP300YJM 1.66

SYSTEM DESIGN 247


1. Electrical work
1-4. Power supply examples
1-4-1.PURY-RP200-300YJM-B
<In the case a system controller is connected.> Note:
Centralized control 1 The transmission cable is not-polarity double-wire.
transmission cable 2 Symbol means a screw terminal for wiring.
Note12 >=1.25mm2 3 The shield wire of transmission cable should be connected to the grounding terminal at
SC Shield cable Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
(CVVS, CPEVS connected to the S terminal at Indoor unit or all shield wire should be connected together.
MVVS) The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
Connector supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
CN41 CN40 OU Note4 shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
Note4 centralized control transmission cable. The shield wire of the centralized control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
To other OU CN40.
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
LW TB1 TB3 TB7 cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size
0.75~1.25mm2 in thickness.
TB7 6 MA remote controller and ME remote controller should not be grouped together.
Power supply (S) 7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
3-phase 4-wire transmission cable to connect all the TB15 terminals of the Indoor units. It is called
380-400-415V 50/60Hz "Grouping".
Note10,13 If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
Note3 according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
To *1 or *2 10 The critical current for choosing power source equipment is approximate
BC controller 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
*1 TB02 12 When System controller (SC) is connected to the system, turn the SW2-1 on.
(M1,M2) TB01 PE 13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
(Using MA remote controller) S L,N phase-missing could break the controllers.
Connecting TB5 terminal. (Shield)

LW Pull box
GFI WB
Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with the MA R/C cable
model of connected indoor S S 0.3-1.25mm2
units or BC controller (Shield) (Shield)
(0.75~1.25mm2)
<=200m
Indoor-outdoor Transmission Note5, Note11
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

BC controller
*2 TB02
(M1,M2) TB01 PE
(Using ME remote controller) S L,N
Connecting TB5 terminal. (Shield)

LW Pull box
GFI WB
Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with the
model of connected indoor S S ME R/C cable
units or BC controller (Shield) (Shield) 0.3~1.25mm2
(0.75~1.25mm2)
Indoor-outdoor Transmission <=10m
transmission cable booster Note5, Note11
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker Minimum Wire thickness
*1, *2 BKC OCP*3 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PURY-RP200YJM 30A 100mA 0.1sec. or less 25 25 30 4 4


LW Local switch PURY-RP250YJM 30A 100mA 0.1sec. or less 25 25 30 4 4
BKC Breaker capacity PURY-RP300YJM 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector
WB Wiring breaker *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-C series or equivalent).
NFB Non-fuse breaker *2 Ground-fault interrupter should combine using of local switch or wiring breaker.
*3 It shows data for B-type fuse of the breaker for current leakage.
OU Outdoor unit
IU Indoor unit
SC System controller
MA R/C MA remote controller
ME R/C ME remote controller

SYSTEM DESIGN 248


2. M-NET control
2-1. Transmission cable length limitation
2. M-NET control

2-1-1. Using MA Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]

L1

Group1 Group3 Group5


OC BC(Main) IC IC BC(Sub) IC IC

(51) (52) (01) (04) (55) (05) (06)


TB3 TB02 TB5 TB15 TB5 TB15 TB02 TB5 TB15 TB5 TB15
M1M2 M1M2 S M1M2 S 1 2 M1M2 S 1 2 M1M2 S M1M2 S 1 2 M1M2 S 1 2

a2
TB7
M1M2S

a1
a4

a1
A B A B A B

a2

a2

a3
Shielded wire
MA MA MA
L2

OC L3 L4
(54 ) BC(Main) IC IC BC(Sub) IC

TB7
(56) (02) (03) (57) (07)
M1 M2 S
TB3 TB02 TB5 TB15 TB5 TB 15 TB02 TB5 TB15
M1M2 M1M2 S M1M2 S 1 2 M1M2 S 1 2 M1M2 S M1M2 S 1 2
L6

Power Supply Unit

a1
PAC-SC51KUA
A B S
V+V-FG

A B
L7

AG-150A
n

MA

A B S V+V-FG

OC : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller

2-1-2. Using ME Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7, L3+L5 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from ME to Indoor e1, e2+e3, e4 <=10m[32ft.]*1 0.3-1.25 mm2 [AWG22-16] *1
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]
*1. If the length from ME to Indoor exceed 10m, use 1.25 mm2 [AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.

L1

Group1 Group3 Group5


OC BC(Main) IC IC BC(Sub) IC IC

(51) (52) (01) (04) (55) (05) (06)


TB3 TB02 TB5 TB5 TB02 TB5 TB5
M1M2 M1M2 S M1M2 S M1M2 S M1M2 S M1M2 S M1M2 S

TB7
M1M2 S
e2

e3

A B A B A B
Shielded wire (101) (105) (155)
ME ME ME
L2

OC L3 L4
(54 ) BC(Main) IC IC BC(Sub) IC

TB7
(56) (02) (03) (57) (07)
M1 M2 S
TB3 TB02 TB5 TB5 TB02 TB5
M1M2 M1M2 S M1M2 S M1M2 S M1M2 S M1M2 S
L5
L6

Power Supply Uni t


PAC-SC51KUA
e4

A B S
V+V-FG

A B
(103)
L7

AG-150A
n

ME

A B S V+V-FG

OC : Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller

SYSTEM DESIGN 249


2. M-NET control
2-2. Transmission cable specifications
Transmission cables (Li) ME Remote controller cables MA Remote controller cables
Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable
CVVS, CPEVS or MVVS CVV
2 2
Cable size 0.3 1.25 [AWG22 16] 0.3 1.25 [AWG22 16]
More than 1.25 [AWG16] (0.75 1.25 2
[AWG18 16]) (0.75 1.25 2
[AWG18 16])
When 10m [32ft] is exceeded, use cables with
Remarks Max length : 200m [656ft]
the same specification as transmission cables.

Connected with simple remote controller. CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

Check the existing wires for damage to insulation by measuring the resistance between the lead and the ground with a 500V
ohmmeter. If the insulation resistance is less than 100 M, replace the wires.
Disconnect all controllers before measuring insulation resistance to avoid controller damage.

Note: Disconnect the system controller before starting a refrigerant oil recovery operation, if one is connected.
Reconnect the system controller after the completion of the refrigerant oil recovery operation.

SYSTEM DESIGN 250


2. M-NET control
2-2-1. Reusability check of the existing transmission lines for Replace Multi units
Use the flowcharts on the following pages to determine the reusability of the existing transmission lines.
Obtain the system configuration drawing, fill out the checklist, and make a decision based on them.

Existing transmission lines reusability checklist


Check items Findings Notes
1. Remote controller cable (MA remote controller)
(1) Length m
(2) Cable size mm2
(3) Number of cores Cores

(4) Cable type (shielded/unshielded) Shielded/Unshielded


2. Remote controller cable (ME remote controller)
(1) Length *1 m
(2) Cable size mm2
(3) Number of cores Cores

(4) Cable type (shielded/unshielded) Shielded/Unshielded


3. Remote controller cable (system controller)
(1) Length *1 m
(2) Cable size mm2
(3) Number of cores Cores

(4) Cable type (shielded/unshielded) Shielded/Unshielded


(5) System controller connection (Indoor unit Indoor/Centralized
system/centralized control system)
4. Indoor-outdoor transmission line
(1) Refrigerant system (Single/Multiple) Single/Multiple
(2) Length of transmission line to the farthest unit *1 m
(3) Cable size mm2
(4) Number of cores Cores

(5) Cable type (shielded/unshielded) Shielded/Unshielded


(6) Number of connected indoor units units

5. Centralized control transmission line


(1) Length of transmission line to the farthest unit *1 m
(2) Cable size mm2
(3) Number of cores Cores
(4) Cable type (shielded/unshielded) Shielded/Unshielded

6. Availability of system configuration drawing (Obtain one as Available/Not available


much as possible.)
7. Noise-related problems with the old units Available/Not available
(Write down the nature of the problem in the Notes column,
if any.)

8. Are there any high-frequency medical equipment in the adjacent Available/Not available
area that could cause noise-interference?
(Write down the specific nature of the concerns in the Notes
column, if any.)

*1: If the remote controller (ME/System controller) length exceeds 10 m, include the exceeded length in the calculation of the
transmission line length (indoor-outdoor transmission line/centralized control system).

SYSTEM DESIGN 251


2. M-NET control

Reusability of MA remote controller wiring Reusability of M-NET remote controller witing

Checking the Checking the


transmission cable transmission cable

NO Refer to Table A. NO Refer to Table A.


Is the 2-core cable used? Handle the non-using wiring as Is the 2-core cable used? Handle the non-using wiring as
shown in figure A. shown in figure A.

YES YES

NO NO If the wiring is more than 10m, include the


Is the wiring of Wiring for MA remote controller Is the wiring of exceeding length to the total wiring length.
less than 200m? must be under 200m. less than 10m? When 10m is exceeded, use cables with the
same specification as transmission cables.

YES YES

Go to "Reusability of Go to "Reusability of
Transmission line". Transmission line".

Reusability of System controller wiring Figure A. Non-using wiring


Side: A A
Close to power supply unit B shielded wire B
Checking the (Outdoor unit, Power supply unit)
transmission cable S S

A A
B Non-shielded wire B
NO S S
Refer to Table A.
Is the 2-core cable used? Handle the non-using wiring as Non using wiring on the power supply side (Outdoor unit, Power supply
shown in figure A.
unit) should be connected to the shield terminal. The non-using wiring on
the opposite side should be open and insulated.
YES

If the wiring is more than 10m, include the


exceeding length to the total wiring length.
When 10m is exceeded, use cables with the
same specification as transmission cables.

YES

Go to "Reusability of
Transmission line".

Table A

Transmission cables (Li) ME Remote controller cables MA Remote controller cables


Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable
CVVS, CPEVS or MVVS CVV
2 2
Cable size 0.3 1.25 [AWG22 16] 0.3 1.25 [AWG22 16]
More than 1.25 [AWG16] (0.75 1.25 2
[AWG18 16]) (0.75 1.25 2
[AWG18 16])
When 10m [32ft] is exceeded, use cables with
Remarks Max length : 200m [656ft]
the same specification as transmission cables.

Connected with simple remote controller. CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

SYSTEM DESIGN 252


2. M-NET control

Determining the reusability of the transmission line

Reusability of Transmission line

Checking the transmission cable

NO *1: When the remote controller cable (ME remote controller and system remote
Is there a ground fault
Fix the ground fault current. controller) exceeds 10m, use cables with the same specification as
current?
transmission cables (indoor/outdoor and centralized controller).

YES

Is the farthest NO Farthest transmission line of


transmission line less centralized controller must be less
than 200m? than 200m.

YES

Is the diameter of the


NO Check the number of indoor units,
Is the diameter of the current
NO Change the wiring to shielded wiring
farthest length of transmission line
transmission line more than and read the applicable diameter wiring thicker than the diameter with more than 1.25mm2.
1.25mm2? from the diagram B. read from diagram B?

YES YES

NO Refer to Table A.
Is the 2-core cable used? Handle the wiring that are not used
as shown in figure A.

YES

NO NO Farthest transmission line of


Is the system single Is the farthest transmission
centralized controller must be less
refrigerant system? line of centralized controller
less than 500m? than 500m.

YES YES

NO Is the diameter of
NO Check the farthest transmission line Is the diameter of the current
NO
Is the farthest transmission centralized transmission line length of centralized controller and wiring thicker than the
line of indoor/outdoor unit more than 1.25mm2?
read the applicable diameter. diameter read from chart A?
less than 120m? *1
YES YES
YES

Change the centralized transmission


NO line diameter to more than 1.25mm2.
Is the shielded wiring used? Please contact your local distributor
for more information.

YES
Chart A. Centralized transmission line applicable diameter
Shielded wiring should be connected
to the terminal at the power supply Length between power
unit side (outdoor unit).
supply unit to outdoor unit Wiring diameter
and system controller
Less than 200m More than 0.5mm2
Less than 130m More than 0.3mm2

Existing transmission line can


be reused.

Figure A. Non-using wiring

Side: A A
Close to power supply unit B shielded wire B
(Outdoor unit, Power supply unit)
S S

A A
B Non-shielded wire B
S S

Non using wiring on the power supply side (Outdoor unit, Power supply
unit) should be connected to the shield terminal. The non-using wiring on
the opposite side should be open and insulated.

Table A

Transmission cables (Li) ME Remote controller cables MA Remote controller cables


Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable
CVVS, CPEVS or MVVS CVV
2 2
Cable size 0.3 1.25 [AWG22 16] 0.3 1.25 [AWG22 16]
More than 1.25 [AWG16] (0.75 1.25 2
[AWG18 16]) (0.75 1.25 2
[AWG18 16])
When 10m [32ft] is exceeded, use cables with
Remarks Max length : 200m [656ft]
the same specification as transmission cables.

Connected with simple remote controller. CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

SYSTEM DESIGN 253


2. M-NET control

Diagram B Checking the cable size


MA remote controller
200

Length of transmission line to the farthest unit (m)


1.25mm2

150

0.75mm2

0.5mm2
100

0.3mm2

50

0
0 5 10 15 20 25 30 32
Number of indoor units

ME remote controller
200

1.25mm2
Length of transmission line to the farthest unit (m)

150

0.75mm2
0.5mm2

100

0.3mm2

50

0
0 5 10 15 20
Number of indoor units

SYSTEM DESIGN 254


2. M-NET control
2-3. System configuration restrictions
2-3-1. Common restrictions for the CITYMULTI system

For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
*OA processing unit GUF-RD(H) is considered as Indoor unit.
B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.)
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.

2-3-2. Ensuring proper communication power for M-NET


In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY, and OA processing unit
GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases,
Transmission booster should be used. Taking the power consumption of Indoor unit sized P20-P140 as 1, the equivalent
power consumption or supply of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption
Indoor, OA unit Indoor unit BC controller MA RC. LOSSNAY ME Remote Contr. Timers, System Contr. ON/OFF Contr. MN Converter
Sized P15-P140 Sized P200,P250 CMB PAR-30MAA PAR-F27MEA PAC-SC30GRA AT-50A PAC-YT40ANRA CMS CMS
GUF-50, 100 PAR-21MAA PAC-SE51CRA PAC-SF44SRA -MNF-B -MNG-E
PAC-YT51CRA(B) PZ-52SF-E PAC-YT34STA
PAR-FA32MA AG-150A
LGH-RX-E
PZ-60DR-E
1 7 2 0 1/4 1/2 4 1 1/2 2
*RC : Remote Controller
Table 2-3-2 The equivalent power supply
Transmission Booster Power supply unit Expansion controller BM ADAPTER System Controller Outdoor unit Outdoor unit
PAC-SF46EPA PAC-SC51KUA PAC-YG50ECA BAC-HD150 GB-50ADA Connector TB3 and TB7 total * Connector TB7 only
25 5 6 6 6 32 6
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32. Not
applicable to the PUMY model.
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the
air-conditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, OA process units and ME remote controller, Timers
and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sized
P200, 250 is counted as 7 Indoor units, but MA remote controller(s), LOSSNAY, PZ-60DR-E is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumption
reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA is used to supply power at TB7 side, count from
TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reaches
6, a PAC-SF46EPA should be set.
System example

TB7 TB3
UP

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

POWER RATING 220-240V:0.7A ~/N

50

WEIGHT 3.4kg

MADE IN JAPAN

01 02 Transmission
booster
(No.1)

ME remote ME remote
controller controller
TB7 TB3 N1 N2
Outdoor unit Transmission booster (No.1) should be used, Within N2, conditions 1,2 should be followed.
if the total quantity of Indoor units, OA process units and ME remote controllers 1.The total quantity of Indoor units, OA process units
reaches 40, (Indoor unit sized P200, 250 is counted as 7); and ME remote controller should not exceed 40.
or if the total equivalent transmission power consumption reaches 32. *Indoor unit sized P200, 250 is counted as 7 units.
2.The total equivalent transmission power consumption
UP
should not exceed 25.

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

220-240V:0.7A ~/N
POWER RATING
50

WEIGHT 3.4kg

MADE IN JAPAN

Transmission
LOSSNAY booster LOSSNAY
CENTRALIZED CONTROLLER AG-150A

unit PAC-SF46EPA unit


M-NET Centralized controller (No.2)
(AG-150A)
PZ-52SF-E PZ-52SF-E
24VDC
Power supply unit
PAC-SC51KUA N3 N4
Transmission booster (No.2) should be used, Within N4, the total equivalent transmission
if the total equivalent transmission power consumption reaches 5. power consumption should not exceed 25.

SYSTEM DESIGN 255


2. M-NET control
2-3-3. Ensuring proper power supply to System controller
The power to System controller (excluding LMAP02-E) is supplied via M-NET transmission line. M-NET transmission line
at TB7 side is called Centralized control transmission line while one at TB3 side is called Indoor-Outdoor transmission line.
There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.

2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB3.
If there is more than 1 Outdoor unit, it is necessary to Fig. 2-3-3-A M-NET transmission lines System controller
(excluding LMAP02-E)
replace power supply switch connector CN41 with CN40 Outdoor unit
(Indoor-Outdoor transmission lines)
Group Group
on one Outdoor unit. TB3
TB7
Replacement of
CN41 with CN40 Indoor unit

M-NET transmission lines


(transmission lines
for centralized controller) MA remote controller

Outdoor unit
Group Group
TB3
TB7
Use CN41
as it is. Indoor unit

ME remote controller

System
controller Maximum 3 System controllers can be connected to TB3.

2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB7
and receiving power from the Outdoor unit. Fig. 2-3-3-B M-NET transmission lines
It is necessary to replace power supply switch connector Outdoor unit
(Indoor-Outdoor transmission lines)
Group Group
CN41 with CN40 on one Outdoor unit. TB3
TB7
Replacement of
CN41 with CN40 Indoor unit

M-NET transmission lines


(transmission lines
for centralized controller) MA remote controller

Outdoor unit
Group Group
TB3
TB7
Use CN41
as it is. Indoor unit

ME remote controller

System
controller Maximum 3 System controllers can be connected to TB7.

2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
When using PAC-SC51KUA to supply transmission
Fig. 2-3-3-C
power, the power supply connector CN41 on the Outdoor M-NET transmission lines
(Indoor-Outdoor transmission lines)
units should be kept as it is. It is also a factory setting. Outdoor unit
Group Group

1 PAC-SC51KUA supports maximum 1 AG-150A unit TB7


TB3

due to the limited power 24VDC at its TB3. Use CN41


as it is. Indoor unit

However, 1 PAC-SC51KUA supplies transmission power M-NET transmission lines


(transmission lines
at its TB2 equal to 5 Indoor units, which is referable at for centralized controller) MA remote controller

Table 2-3-2. Outdoor unit


Group Group
If PZ-52SF-E, Timers, System controller, ON/OFF TB3
controller connected to TB7 consume transmission power TB7
Use CN41
Indoor unit
more than 5 (Indoor units), Transmission booster as it is.

PAC-SF46EPA is needed. PAC-SF46EPA supplies PAC-SC51KUA


ME remote controller
transmission power equal to 25 Indoor units.
System
controller

CAUTION
AG-150A*1 is recommended to connect to TB7 because it performs back-up to a number of data.
In an air conditioner system has more than 1 Outdoor units, AG-150A receiving transmission power through TB7 on one of the Outdoor units would have a
risk that the connected Outdoor unit failure would stop power supply to AG-150A, and disrupt the whole system.
When applying apportioned electric power function, AG-150A is necessary to connected to TB7 and has its own power supply unit PAC-SC51KUA.*2
*1: AG-150A is an example model of system controllers.
*2: Power supply unit PAC-SC51KUA is for AG-150A.

SYSTEM DESIGN 256


2. M-NET control

2-3-4. Power supply to LM adapter LMAP02-E


1-phase 220-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when connecting only the LMAP02-E. Yet, make sure to change
the power supply changeover connector CN41 to CN40 on the LM adapter.

2-3-5. Power supply to expansion controller


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary.
The expansion controller supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)

2-3-6. Power supply to BM ADAPTER


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.
Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.

2-3-7. Power supply to GB-50ADA


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary.
GB-50ADA supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)

SYSTEM DESIGN 257


2. M-NET control
2-4. Address setting

2-4-1. Switch operation

In order to constitute CITY MULTI in a complete system, switch Rotary switch


operation for setting the unit address No. and connection No. is Branch
required. No. setting Unit address No. setting

Address No. of outdoor unit, indoor unit and remote controller. F 0 12 9


01
9
01

BC E

3456

2 3

2 3
D
The address No. is set at the address setting board.

7 8

7 8
In the case of R2 system, it is necessary to set the same No. at the
789A 45 6 45 6
branch No. switch of indoor unit as that of the BC controller
connected. (When connecting two or more branches, use the lowest
branch No.)
Caution for switch operations
Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.

MA remote controller

When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
The factory setting is Main .

PAR-21MAA
The MA remote controller does not have the switches listed above.
Refer to the installation manual for the function setting.

PAC-YT51CRB
Setting the dip switches
There are switches on the front of the remote controller. Remote controller Main/Sub and other function settings
are performed using these switches. Ordinarily, only change the Main/Sub setting of SW1.
(The factory settings are all ON.)
SW No SW contents Main ON OFF Comment
Remote controller
1 Main Sub Set one of the two remote controllers at one group to Main
Main/Sub setting
Temperature display
2 Celsius Fahrenheit When the temperature is displayed in [Fahrenheit], set to No.
units setting
Cooling/heating dis- When you do not want to display Cooling and Heating in the
3 Yes No
play in AUTO mode Auto mode, set to No.

SYSTEM DESIGN 258


2. M-NET control

2-4-2. Rule of setting address

Unit Address setting Example Note


Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
9 0 1 9 0 1
If applicable, set the sub BC controllers in an PURY
Indoor unit 01 ~ 50

7 8

7 8
2 3

2 3
4 5 6 4 5 6
system in the following order:
10 1 (1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)

The smallest address of indoor unit in same refrigerant


system + 50
9 0 1 9 0 1 Assign sequential address numbers to the outdoor
Outdoor unit

7 8

7 8
2 3

2 3
51 ~ 99, 100 4 5 6 4 5 6 units in one refrigerant circuit system. OC, OS1 and
(Note1) OS2 are automatically detected. (Note 2)
10 1 Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The address of outdoor unit + 1
9 0 1 9 0 1
BC controller Please reset one of them to an address between 51
7 8

7 8
2 3

52 ~ 99, 100 2 3 and 99 when two addresses overlap.


(Main)
4 5 6 4 5 6
The address automatically becomes "100" if it is set
10 1
as "01~ 50"
9 0 1 9 0 1 Lowest address within the indoor units connected to
BC controller
7 8

7 8
2 3

2 3

52 ~ 99, 100 the BC controller (Sub) plus 50.


(Sub)
4 5 6 4 5 6

10 1
Local remote controller

0 1 0 1
ME, LOSSNAY 9 9

1 The smallest address of indoor unit in the group + 100


2 3

2 3
7 8

7 8

Remote controller 101 ~ 150 45 6 45 6

(Main) Fixed The place of "100" is fixed to "1"


10 1

ME, LOSSNAY 9
0 1
9
0 1 The address of main remote controller + 50
1
2 3

2 3
7 8

7 8

Remote controller 151 ~ 199, 200 45 6 45 6


The address automatically becomes "200" if it is set
(Sub) Fixed
10 1 as "00"
0 1 0 1

2
9 9
Group remote The smallest group No. to be managed + 200
2 3

2 3
7 8

7 8

controller 201 ~ 250 Fixed


45 6 45 6

10 1

0 1 0 1 0 1
9 9 9
System remote
2 3

2 3

2 3
7 8

7 8

7 8

000, 201 ~ 250


controller
45 6 45 6 45 6

100 10 1
0 1 0 1 0 1
9 9 9
The smallest group No. to be managed + 200
ON/OFF remote
2 3

2 3

2 3
7 8

7 8

7 8
System controller

000, 201 ~ 250 45 6 45 6 45 6


controller The smallest group No. to be managed is changeable.
100 10 1

AG-150A
GB-50ADA 000, 201 ~ 250 0,2 0~5 0~9
AT-50A
100 10 1

PAC-YG50ECA 000, 201 ~ 250 0,2 0~5 0~9 Settings are made on the initial screen of AG-150A.
100 10 1

BAC-HD150 000, 201 ~ 250 0,2 0~5 0~9 Settings are made with setting tool of BM ADAPTER.

100 10 1

9 0 1 9 0 1

2
7 8

7 8
2 3

2 3

LMAP02-E 201 ~ 250 4 5 6 4 5 6

Fixed
10 1

Note1: To set the address to "100", set it to "50"


Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.

SYSTEM DESIGN 259


2. M-NET control

2-4-3. System examples


Factory setting
Original switch setting of the outdoors, indoors, controllers, LMAP and BM ADAPTER at shipment is as follows.
Outdoor unit : Address: 00, CN41: U (Jumper), DipSW2-1: OFF
Indoor unit : Address: 00
BC controller : Address: 00
ME remote controller : Address: 101
LMAP : Address: 247, CN41: U (Jumper), DipSW1-2: OFF
BM ADAPTER : Address: 00

Setting at the site


DipSW2-1(Outdoor) : When the System Controller is used, all the Dip SW2-1 at the outdoor units should be set to
"ON". * Dip SW2-1 remains OFF when only LMAP02-E is used.
DipSW4-6(BC controller) : Set DipSW 4-6 to ON at BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports.
It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DipSW 4-6 to OFF).
DipSW1-2(LMAP) : When the LMAP is used together with System Controller, DipSW1-2 at the LMAP
should be set to "ON".
CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.

2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller

PURY
OC
00
CN40 CN41

DipSW2-1
OFF
TB3

Group 1 Group 2 Group 3 Group 4

BC controller Indoor unit


00 00 00 00 00 00
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15

SRU 1*
MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)

1*
Wireless R/C
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
NOTE:
1. No address setting is needed.
2. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".
3. Indoor units should be set with a branch number.
4. Address setting is required if a sub BC controller is connected.

SYSTEM DESIGN 260


2. M-NET control

2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller

PURY
OC
51
CN40 CN41

DipSW2-1
ON
TB3

Group 1 Group 2 Group 3 Group 4

BC controller Indoor unit


52 01 02 03 04 05
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15

201 SRU 1*
MA R/C MA R/C MA R/C MA R/C
SC (Main) (Sub)

1*
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Address should be set to Indoor units and centralized controller.
2. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".
3. Indoor units should be set with a branch number.

SYSTEM DESIGN 261


2. M-NET control

2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/ TB3 side, Booster for long M-NET wiring

PURY PURY PURY


OC OC OC
TB7 TB7 TB7
51 91 98
CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2 Group 21

BC controller Indoor unit


52 01 02 03 30
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

TB2 Transmission Booster


PAC-SF46EPA
SRU *1
Power supply unit 202 MA R/C MA R/C MA R/C
(PAC-SC51KUA) (Main) (Sub)
*2 SC*3
*1
Wireless R/C
000 or 201

SC
Group 31 Group 32 Group 33 Group 34 Group 35 Group 36
BC controller BC controller
(Main) Indoor unit LOSSNAY (Sub1) LOSSNAY
92 41 42 43 95 45 46 47
TB02 TB5 TB15 TB5 TB5 TB5 TB15 TB5 TB15 TB5 TM4

SRU *1 142 143


ME R/C PZ-52SF-E MA R/C MA R/C MA R/C PZ-60
203 (Main) (Sub) DR-E
SC*3
*1
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24VDC should be used with the PAC-SC51KUA.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
NOTE:
1. Address should be set to Indoor units, LOSSNAY and system controller.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to
2-3 "System configuration restrictions".
3. Indoor units should be set with a branch number.
4. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor units that are
connected to each sub BC controller and 50.

SYSTEM DESIGN 262


2. M-NET control

2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller

PURY
OC
51
CN40 CN41

DipSW2-1
OFF
TB3

Group 1 Group 2 Group 3 Group 4

BC controller Indoor unit


52 01 02 03 04 05
TB02 TB5 TB5 TB5 TB5 TB5

101 102 104 105 155


ME R/C ME R/C ME R/C ME R/C ME R/C

NOTE:
1. Address should be set to Indoor units, system controller and ME remote controllers.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
3. Indoor units should be set with a branch number.

2-4-3-5. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY

PURY
OC
51
CN40 CN41

DipSW2-1
ON
TB3

Group 1 Group 2 Group 3 Group 4 Group 5 Group 6

BC controller Indoor unit LOSSNAY LOSSNAY


52 01 02 03 04 05 06
TB02 TB5 TB5 TB5 TB5 TB5 TB5 TM4

201
101 102 103 104 105 155
ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C PZ-60
SC DR-E

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.

NOTE:
1. Address should be set to Indoor units, LOSSNAY centralized controller, ME remote controllers.
2. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".
3. Indoor units should be set with a branch number.

SYSTEM DESIGN 263


2. M-NET control

2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
PURY PURY PURY
OC OC OC
TB7 TB7 TB7
51 91 97
CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2 Group 21


BC controller BC controller
(Main) Indoor unit (Sub)
52 01 02 03 80 30
TB02 TB5 TB5 TB5 TB02 TB2 TB3 TB5

TB2 Transmission Booster


101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C
Power supply unit
(PAC-SC51KUA)
*1 Group 31 Group 32 Group 33 Group 34 Group 35 Group 36
BC controller Indoor unit LOSSNAY LOSSNAY
92 41 42 43 44 45 46
000 or 201 TB02 TB5 TB5 TB5 TB5 TB5 TB5 TM4

SC
141 142 143 144 145 195 PZ-60
ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C DR-E

*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24VDC should be used with the PAC-SC51KUA.
NOTE:
1. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
2. Indoor units should be set with a branch number.
3. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.
When the address assigned to sub BC controller overlaps those of any other units including outdoor units (OC/OS) or main BC controller,
sub BC controller will be given priority to have the address.

2-4-3-7. Example : BC, BC sub NOTE


Indoor units should be set with a branch number.
PURY BC (main) address = O/U address + 1
OC BC (sub) address = Lowest address within the indoor units connected to the BC controller (sub) + 50
If applicable, set the sub BC controllers in an PURY system in the following order:
51 (1) Indoor unit to be connected to the BC controller (Main)
CN40 CN41 (2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
: M-NET wiring : Piping
DipSW2-1 52 54 57
OFF BC controllers BC controllers BC controllers
TB3 TB02 CMB-V-GA1(main) TB02 CMB-V-GB1(No.1 sub) TB02 CMB-V-GB1(No.2 sub)

01 02 03 04 05 06 07 08
TB5 TB5 TB5 TB5 TB5 TB5 TB5 TB5

101 104 106 107

Group 1 Group 2 Group 3 Group 4

SYSTEM DESIGN 264


2. M-NET control

2-4-3-8. ME remote controller, Multi-refrigerant-system, No Power supply unit


PURY PURY
OC OC
TB7 TB7
51 56
CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1
OFF OFF
TB3 TB3

Group 1 Group 2
BC controller
52 01 02 03 04 05
TB02

101 105
ME R/C ME R/C

Group 4 Group 3
BC controller
57 10 09 08 07 06
TB02

110 107
ME R/C ME R/C
NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

2-4-3-9. ME remote controller , Multi-refrigerant-system, System Controller at TB7 side, No Power sypply unit
PURY PURY
OC OC
TB7 TB7
51 56
CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1
ON ON
TB3 TB3

Group 1 Group 2
BC controller
52 01 02 03 04 05
TB02

201 101 105


SC ME R/C ME R/C

Group 4 Group 3
BC controller
57 10 09 08 07 06
TB02

110 107
ME R/C ME R/C
NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

SYSTEM DESIGN 265


2. M-NET control
2-4-3-10. TG-2000A(*1)+AG-150A(*2)
AG-150A can control max. 50 indoor units;
TG-2000A can control max. 40 AG-150A;*3
TG-2000A can control max. 2000 indoor units.

AG-150A PURY PURY


OC OC
000
TB7 TB7
24VDC 51 51
CN40 CN41 CN40 CN41
TB3 TB2

DipSW2-1 DipSW2-1
Power supply unit ON ON
(PAC-SC51KUA) TB3 TB3

Group 1 Group 2 Group 40

BC controller Indoor unit


52 01 02 03 42
HUB
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *4 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)
PC with *4
TG-2000A Wireless R/C

LAN AG-150A PURY PURY

000 OC OC
TB7 TB7
51 91
24VDC CN40 CN41 CN40 CN41
TB3 TB2
DipSW2-1 DipSW2-1
ON ON
Power supply unit TB3 TB3
(PAC-SC51KUA)

Group 1 Group 2 Group 21


BC controller Indoor unit
52 01 02 03 30
TB02 TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34


BC controller Interlocked BC controller
(Main) Indoor unit LOSSNAY (Sub)
92 41 42 43 94 44 45
TB02 TB5 TB5 TB5 TB02 TB5 TB5

141 142 144 145 195


ME R/C ME R/C ME R/C ME R/C ME R/C

It is planned that GB-50ADA will be supported on TG-2000A Ver. 6.3* or later.


*1 TG-2000A (Ver.5.5 or later) supports AG-150A (Ver.1series).
TG-2000A (Ver. 6.1 or later) supports AG-150A (Ver. 2.1 or later) connected with the expansion controller (EC).
*2 AG-150A (Ver.1series) does not support the expansion controller (EC).
*3 When AG-150A connected with the expansion controller (EC) is connected, the number of EC will be the maximum controllable number.
TG-2000A can control up to 40 EC or AG-150A without EC connection.
*4 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 266


2. M-NET control
2-4-3-11. AG-150A+PAC-YG50ECA (Expansion controller)
AG-150A can control max. 150 indoor units/ via expansion controllers.
AG-150A

24VDC
TB3

Power supply unit


PAC-YG50ECA (PAC-SC51KUA) PURY PURY
000
OC OC
TB7 TB7
CN41 CN40
51 51
CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1
ON ON
TB3 TB3

Group 1 Group 2 Group 40

BC controller Indoor unit


HUB
52 01 02 03 42
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *4 PAC-SF46EPA

MA R/C MA R/C MA R/C


PC with (Main) (Sub)
Browser *4
PAC-YG50ECA Wireless R/C
LAN 000 PURY PURY
OC OC
CN41 CN40 TB7 TB7
51 91
PAC-YG50ECA CN40 CN41 CN40 CN41

000
DipSW2-1 DipSW2-1
ON ON
CN41 CN40
TB3 TB3

Group 1 Group 2 Group 21


BC controller Indoor unit
52 01 02 03 30
TB02 TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34


BC controller Interlocked BC controller
(Main) Indoor unit LOSSNAY (Sub)
92 41 42 43 94 44 45
TB02 TB5 TB5 TB5 TB02 TB5 TB5

141 142 144 145 195


ME R/C ME R/C ME R/C ME R/C ME R/C

NOTE
When connecting AG-150A to PAC-YG50ECA, TB2 for power supply unit does not need to be connected to AG-150A.
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 AG-150A (Ver.1series) does not support the expansion controller (EC).

SYSTEM DESIGN 267


2. M-NET control

2-4-3-12. LMAP
LMAP can transmission for max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system
controller (SC).
LMAP can transmission for max.
LMAP(01) 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
identified by Neuron ID

247
(LONWORKS adapter) PURY PURY
CN40 CN41
OC OC
TB7 TB7
DipSW1-2
OFF 51 51
CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1
OFF OFF
TB3 TB3

Group 1 Group 2 Group 40


BC controller Indoor unit
52 01 02 03 42
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15
AG-150A
Transmission Booster
SRU *1 PAC-SF46EPA
000
Power supply unit
(PAC-SC51KUA) MA R/C MA R/C MA R/C
(Main) (Sub)
TB3 24VDC
*1
TB2 Wireless R/C
LMAP(02)
identified by Neuron ID
LONWORKS

247 PURY PURY PURY


CN40 CN41 OC OC OC
TB7 TB7 TB7
DipSW1-2 51 91 97
ON CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2 Group 21


BC controller BC controller
(Main) Indoor unit (Sub)
52 01 02 03 80 30
TB02 TB5 TB5 TB5 TB02 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34 Group 35 Group 36


BC controller BC controller
(Main) Indoor unit LOSSNAY (Sub) LOSSNAY
92 41 42 43 94 44 45 46
TB02 TB5 TB5 TB5 TB02 TB5 TB5 TB5 TM4

PC
141 142 143 144 145 195
LONWORKS card PZ-60
ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C DR-E

LONWORKS card

LONWORKS card For other equipments (Lighting, security, elevator etc.)


*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 268


2. M-NET control

2-4-3-13. BM ADAPTER
BM ADAPTER can transmission for max. 50 indoor units;
Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected
without the power supply unit.

BM ADAPTER can transmission for max.


50 indoor units in single-refrigerant-system or multi-refrigerant-system.
BM ADAPTER(01)
000
HUB PURY PURY
CN40 CN41
OC OC
TB7 TB7
51 51
CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1
OFF OFF
TB3 TB3

Group 1 Group 2 Group 40


BC controller Indoor unit
52 01 02 03 42
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *1 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)

*1
Wireless R/C

BM ADAPTER(02)
201
BAC net

PURY PURY PURY


CN40 CN41 OC OC OC
TB7 TB7 TB7
51 91 96
CN40 CN41 CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2 Group 21


BC controller BC controller
(Main) Indoor unit (Sub)
52 01 02 03 80 30
TB02 TB5 TB5 TB5 TB02 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34 Group 35


BC controller BC controller
(Main) Indoor unit LOSSNAY (Sub)
92 41 42 43 94 44 45
TB02 TB5 TB5 TB5 TB02 TB5 TB5

HUB
141 142 143 144 145 195
ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C

For other equipments (Lighting, security, elevator etc.)


*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

SYSTEM DESIGN 269


2. M-NET control

2-4-3-14. BM ADAPTER+PAC-YG50ECA (Expansion controller)


BM ADAPTER(*1) can transmission for max. 150 indoor units/via expansion controllers (PAC-YG50ECA).

LAN1
BM ADAPTER PAC-YG50ECA *4
BACnet 000
CN40 CN41 PURY PURY
CN40 CN41
OC OC
TB7 TB7
LAN2 51 51
CN40 CN41 CN40 CN41

DipSW2-1 DipSW2-1
OFF OFF
TB3 TB3

Group 1 Group 2 Group 40


BC controller Indoor unit
LAN 52 01 02 03 42
TB02 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *2 PAC-SF46EPA
HUB
MA R/C MA R/C MA R/C
PAC-YG50ECA *4 (Main) (Sub)
000 *2
CN40 CN41
Wireless R/C

PURY PURY PURY


OC OC OC
PAC-YG50ECA *4 TB7 TB7 TB7
000 51 91 96
CN40 CN41 CN40 CN41 CN40 CN41
CN40 CN41

DipSW2-1 DipSW2-1 DipSW2-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2 Group 21


BC controller BC controller
(Main) Indoor unit (Sub)
52 01 02 03 80 30
TB02 TB5 TB5 TB5 TB02 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C
AG-150A *3
Group 31 Group 32 Group 33 Group 34 Group 35
BC controller BC controller
(Main) Indoor unit LOSSNAY (Sub)
92 41 42 43 94 44 45
24VDC TB3 TB02 TB5 TB5 TB5 TB02 TB5 TB5

Power supply unit 141 142 143 144 145 195


(PAC-SC51KUA) ME R/C ME R/C PZ-52SF-E ME R/C ME R/C ME R/C

NOTE
It is not necessary to connect the M-NET transmission line to the TB3 on BM ADAPTER. Leave the power
jumper of BM ADAPTER connected to CN41.
*1 BM ADAPTER (Ver.2.00 or later) supports the expansion controller.
*2 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*3 AG-150A (Ver.2.30 or later) supports the BM ADAPTER.
*4 PAC-YG50ECA (Ver.1.30 or later) supports the BM ADAPTER.

SYSTEM DESIGN 270


3. Piping Design
3-1. Piping Design
3. Piping Design

3-1-1. IF 16 ports or less are in use, I.e., if only one BC controller is in use with no sub BC controller
Note1. No Header usable on PURY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ; Joint CMY-R160-J1 Liquid side
CMY-R160-J1
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; (Liquid side) 226

Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ; M
(M)3/8"(Brazing)
BC controller (N)9.52ID
Piping length needs to consider the actual length and equivalent length which bents are counted. (M)3/8"(Brazing)
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports. Joint CMY-R160-J1 Gas side
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF). S N 226
T
However, the cooling capacity decreases a little (For details, refer to the chapter OUTDOOR UNITS, CMY-R160-J1 (S)5/8"(Brazing)
IU (T)19.05ID
R2 SERIES, 6-4. Correction by port counts of the BC controller). (Gas side)
(S)5/8"(Brazing)
Note7. Individual indoor units grouped together to connect to the BC controller via one port cannot operate
individually in heating and cooling modes at the same time. I.e., they must all function in either heating
Fig. 3-1-1AA
Note8. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
or cooling together.
Note9. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.
For example, PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.
OU

A
For outodoor units equal to or larger than a size P400, on
the BC controller please ensure CMB-PV-GA1 is used.
H H'
BC controller IU
Reducer (P15~P50) Joint
d
(attached with BC controller)
h1 B h2
a Joint
(CMY-R160-J1)
b
c

IU IU IU
(P15-P80) (P100-250) Max.3 sets for 1 port.
Total capacity <= P80
Fig. 3-1-1A Piping scheme

Table 3-1-1-1. Piping length limitation (m) Table3-1-1-2. Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor Model M (m/bent)
Total piping length A+B+a+b+c+d 220 *1 PUHY-RP200YJM-B 0.35
Farthest IU from OU A+B+d 100 (90) *2 125 (115) PUHY-RP250YJM-B 0.42
Distance between OU and BC A 70 (60) *2 PUHY-RP300YJM-B 0.42
Farthest IU from BC controller B+d 30
Heignt between OU and IU (OU above IU) H 50
Heignt between OU and IU (OU under IU) H' 40
Height between IU and BC h1 15 (10) *3
Height between IU and IU h2 15 (10) *3
OU : Outdoor Unit ; IU : Indoor Unit
* 1 Do not exceed the amount of refrigerant to be charged written below. Table3-1-1-3. Piping "A"size selection rule (mm [in.])
PURY-RP200-300YJM-B : 0.16 L1 + 0.11 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 20 Outdoor Model Pipe(High pressure) Pipe(Low pressure)
RP200YJM 19.05 [3/4"] 28.58 [1-1/8"] *4
RP250YJM 19.05 [3/4"] 28.58 [1-1/8"]
L1: Total length of 19.05 high pressure pipe (m)
RP300YJM 19.05 [3/4"] 28.58 [1-1/8"]
L2: Total length of 15.88 high pressure pipe (m)
L3: Total length of 12.7 liquid pipe (m) Table3-1-1-4. Piping "B" size seleciton rule (mm [in.])
L4: Total length of 9.52 liquid pipe (m) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas)
L5: Total length of 6.35 liquid pipe (m) P80 or less 9.52 [3/8"] 15.88 [5/8"]
P81 or more 12.7 [1/2"] 19.05 [3/4"]
* 2 The value in ( ) in the table is applied when indoor total capacity exceeds 130% of
outdoor unit capacity.
* 3 Distance of indoor unit size P200, P250 from BC must be less than 10 m, if any. Table3-1-1-5. Piping "a", "b", "c", "d" size selection rule (mm [in.])
* 4 25.4 for R22 Indoor Unit size Pipe(Liquid) Pipe(Gas)
P15 to P40, GUF-50RD(H) 6.35 [1/4"] 12.70 [1/2"]
P50 to P80, GUF-100RD(H) 9.52 [3/8"] 15.88 [5/8"]
P100 to P140 9.52 [3/8"] 19.05 [3/4"]
P200 12.7 [1/2"] 25.4 [1"] or
28.58 [1-1/8"]
P250 12.7 [1/2"] 28.58 [1-1/8"]

SYSTEM DESIGN 271


3. Piping Design

3-1-2. IF more than 16 ports are in use, or if there is more than one BC controller in use for one outdoor unit
Note1. No Header usable on PURY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ;
Joint CMY-R160-J1 Liquid side
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ; CMY-R160-J1 226
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ; (Liquid side)
(M)3/8"(Brazing)
Piping length needs to consider the actual length and equivalent length which bents are counted. M BC controller
(N)9.52ID
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent. (M)3/8"(Brazing)
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports.
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF).
Joint CMY-R160-J1 Gas side
However, the cooling capacity decreases a little (For details, refer to the chapter OUTDOOR UNITS,
R2 SERIES, 6-4. Correction by port counts of the BC controller). S N 226
T
Note7. Individual indoor units grouped together to connect to the BC controller via one port cannot operate individually CMY-R160-J1 (S)5/8"(Brazing)
IU (T)19.05ID
in heating and cooling modes at the same time. I.e., they must all function in either heating or cooling together. (Gas side)
(S)5/8"(Brazing)
Note8. For sub BC controller CMB-P V-GB1 the connectable indoor unit capacities may sum to equal that of a
P350 unit or less. However, if two sub controllers are used the TOTAL sum of connectable units
connected to BOTH sub controllers must also not exceed that of a P350 unit.
Fig. 3-1-2AA
For sub BC controller CMB-P1016V-HB1 the connectable indoor unit capacities may sum to equal that
or a P350 unit or less. However, if two sub controllers are used the TOTAL sum of connectable units
connected to BOTH sub controllers must also not exceed that of a P450 unit.
Note9. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.
Note10. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.
For example, PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.

OU

IU
CMY-Y202-G2
CMY-Y102L-G2
e h1
A CMY-Y102S-G2
(Joint) D BC controller (Sub BC)

BC controller (Main BC) C h3


H H'
CMY-Y102S-G
Reducer (P15-P50) E BC controller (Sub BC)
(attached with BC controller)
(Joint) h2
B
h1 a CMY-R160-J1 b
c d
(Joint) f h1
IU IU
IU IU
(P15-P80) (P100-P250)
Max.3 sets for 1 port.
Total capacity < = P80
IU

Fig. 3-1-2B Piping scheme OU : Outdoor unit, IU : Indoor unit

Table 3-1-2-1. Piping length limitation (m) Table3-1-2-2. Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor Model M (m/bent)
Total piping length A+B+a+b+c+d 220 *1 PUHY-RP200YJM-B 0.35
Farthest IU from OU A+B+d 100 (90) *2 125 (115) PUHY-RP250YJM-B 0.42
Distance between OU and BC A 70 (60) *2 PUHY-RP300YJM-B 0.42
Farthest IU from BC controller B+d 30
Heignt between OU and IU (OU above IU) H 50
Heignt between OU and IU (OU under IU) H' 40
Height between IU and BC h1 15 (10) *3
Height between IU and IU h2 15 (10) *3
Height between BC(Main or Sub) and BC(Sub) h3 15 (10) *3
OU : Outdoor Unit ; IU : Indoor Unit
* 1 Do not exceed the amount of refrigerant to be charged written below. Table3-1-2-3. Piping "A"size selection rule (mm [in.])
PURY-RP200-300YJM-B : 0.16 L1 + 0.11 L2 + 0.12 L3 + 0.06 L4 + 0.024 L5 < 20 Outdoor Model Pipe(High pressure) Pipe(Low pressure)
RP200YJM 19.05 [3/4"] 28.58 [1-1/8"] *4
RP250YJM 19.05 [3/4"] 28.58 [1-1/8"]
L1: Total length of 19.05 high pressure pipe (m)
RP300YJM 19.05 [3/4"] 28.58 [1-1/8"]
L2: Total length of 15.88 high pressure pipe (m)
L3: Total length of 12.7 liquid pipe (m) Table3-1-2-4. Piping "B" size seleciton rule (mm [in.])
L4: Total length of 9.52 liquid pipe (m) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas)
L5: Total length of 6.35 liquid pipe (m) P80 or less 9.52 [3/8"] 15.88 [5/8"]
P81 or more 12.7 [1/2"] 19.05 [3/4"]
* 2 The value in ( ) in the table is applied when indoor total capacity exceeds 130% of
outdoor unit capacity. Table3-1-2-5. Piping "C", "D", "E" size selection rule (mm [in.])
* 3 Distance of indoor unit size P200, P250 from BC must be less than 10 m, if any. Total down-stream Indoor capacity Pipe(Lequid) Pipe(HP Gas) Pipe(LP Gas)
* 4 25.4 for R22 P200 or less 9.52 [3/8"] 15.88 [5/8"] 19.05 [3/4"]
P201 to P300 9.52 [3/8"] 19.05 [3/4"] 22.20 [7/8"]
P301 to P350 12.70 [1/2"] 19.05 [3/4"] 28.58 [1-1/8"]
P351 to P400 12.70 [1/2"] 22.20 [7/8"] 28.58 [1-1/8"]
HP : High pressure, LP:Low pressure

Table3-1-2-6. Piping "a", "b", "c", "d" size selection rule (mm [in.])
Indoor Unit size Pipe(Liquid) Pipe(Gas)
P15 to P40, GUF-50RD(H) 6.35 [1/4"] 12.70 [1/2"]
P50 to P80, GUF-100RD(H) 9.52 [3/8"] 15.88 [5/8"]
P100 to P140 9.52 [3/8"] 19.05 [3/4"]
P200 12.7 [1/2"] 25.4 [1"] or
28.58 [1-1/8"]
P250 12.7 [1/2"] 28.58 [1-1/8"]

SYSTEM DESIGN 272


3. Piping Design
3-1-3. Pipe diameter compatibility table

Standard
Usable (Unit performance will be affected.)
Usable (Vertical separation between OU and IU to be 20 m or less)
Usable (Piping length limitation will apply.)
Usable (Refrigerant charge amount limit will apply.)
Not use

(1) Main pipe


Outdoor model 200 250 300
Low pressure 15.88
19.05
22.2
25.4
28.58
34.93
41.28
High pressure 9.52
12.7
15.88
19.05

(2) Indoor pipe


Indoor model 15 20 25 32 40 50 63 71 80 100 125
Liquid 6.35 (30m or shorter) (20m or shorter)
9.52
12.7
19.05
Gas 12.7
15.88
19.05
22.2
25.4
28.58
Indoor model 140 200 250
Liquid 6.35

9.52
(25m or shorter) (15m or shorter)
12.7
19.05
Gas 12.7
15.88
19.05
22.2
25.4
28.58
Note
1) The in the table indicates that the existing piping system can be reused if the total amount of refrigerant charge in the existing system is less than the specified amount calculated
by using the following formulas:
0.16L1+0.11L2+0.12L3+0.06L4+0.024.<20
L1 : Total length of 19.05 high pressure pipe(m)
L2 : Total length of 15.88 high pressure pipe(m)
L3 : Total length of 12.7 liquid pipe(m)
L4 : Total length of 9.52 liquid pipe(m)
L5 : Total length of 6.35 liquid pipe(m)

SYSTEM DESIGN 273


3. Piping Design
3-1-4. Flow chart to check if the existing piping can be reused

Start

Are the existing pipes still


Do you know what kind of Exisiting piping cannot be NO
NO connected with indoor units and the
refrigerant oil is used in the reused. Use new piping. outdoor units? (excluding sealed
existing system? branch pipes that are
not in use)
YES Please contact your local If the piping is left disconnected, there is a
distributor. possibility of contamination and corrosion YES
inside the pipe. Do not reuse such pipes.
Is the refrigerant oil SUNISO, MS, Is the existing unit
Barrel Freeze, HAB or Freol? Mitsubishi Electric unit?
NO NO

YES YES

Is the capacity of new


replacement unit the same as that
The vertical height NO of the existing unit?
difference needs to be 50m or
less between IU and OU (if OU is
below IU, 40m or less). And also, height YES
NO
difference between each IU is
15m or less.

Check the piping size and length.


YES Take the refrigerant oil recovery
procedures described in the Mineral
Oil Collection (Refrigerant Oil
Does the piping diameter
Recovery) Manual.
and piping length match
NO our guideline?

YES

Is the branch pipe shape T, Y NO


or header branching?

YES

NO Check the branch pipe type


and the reusability standards
to make a decision.
Please change to the specified
branch pipe.
YES

Do the existing NO
pipes hold enough
air tightness?

YES YES Did the existing unit before the NO


replacement operate without
any gas leak?
Please have air tight test on site.

YES NO
Is the piping air tight?

All branch pipes are connected NO Cut the branch pipe completely that are not
with the indoor units. in use, and seal it.

YES

NO
Is the piping correctly covered
with heat insulation material? Conduct heat insulation.

YES

Does the piping meet the


strength requirements?
NO (material,thickness,anti
corrosion)

YES

Use a new piping. The existing piping can be reused.

SYSTEM DESIGN 274


3. Piping Design
3-2. Refrigerant charging calculation

Sample connection (with BC controller and 4 indoor units)

OU

A
For outodoor units equal to or larger than a size P400, on
the BC controller please ensure CMB-PV-GA1 is used.
H H'
BC controller IU
Reducer (P15~P50) Joint d
(attached with BC controller)
h1 B h2
a Joint
(CMY-R160-J1)
b
c

IU IU IU
(P15-P80) (P100-250) Max.3 sets for 1 port.
Total capacity <= P80

Amount of additional refrigerant to be charged


Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipes on site.
Record the size of each high pressure pipe and liquid pipe, and the amout of refrigerant that was charged on the outdoor unit for future reference.

Calculating the amount of additional refrigerant to be charged


The amount of refrigerant to be charged is calculated with the size of the on-site-installed hige pressure pipes and liquid pipes, and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1kg. (i.e., 16.08 kg = 16.1 kg)

<Amount of additional refrigerant to be charged>


Calculating the amount of additional refrigerant to be charged
High pressure High pressure
Liquid pipe size Liquid pipe size Liquid pipe size
Additional refrigerant pipe size pipe size
Total length of 12.7 Total length of 9.52 Total length of 6.35
charge = Total length of 19.05 + Total length of 15.88 + + +
x 0.12 x 0.06 x 0.024
x 0.16 x 0.11
(kg) (m) x 0.16(kg/m) (m) x 0.11(kg/m) (m) x 0.12(kg/m) (m) x 0.06(kg/m) (m) x 0.024(kg/m)

Charged amount per Total capacity


Total outdoor unit BC controller
BC controller Charged amount of connected Charged amount
Model (Sub) Total units
+ (Standard / Main) + + indoor units
RP200 2.0 kg 1 unit 1.0 kg -80 2.0 kg
RP250 2 units 2.0 kg 81 - 160 2.5 kg
3.0 kg
RP300 161 - 330 3.0 kg
331 - 390 3.5 kg
391 - 450 4.5 kg

Amount of factory charged refrigerant Sample calculation


Outdoor unit Indoor
Charged amount
Model A: 28.58 40m 1 : P80 a: 9.52 5m
RP200 B: 9.52 10m 2 : P125 b: 12.7 3m
RP250 11.8 kg 3 : P15 c: 6.35 2m
RP300 4 : P20 d: 6.35 3m

Total length for each pipe size : 15.88 A = 40m


12.70 b = 3m
9.52 B + a = 10 + 5 = 15 m
6.35 c+d=2+3=5m
Therefore, additional refrigerant charge = 0.11 x 40 + 0.12 x 3 + 0.06 x 15 + 0.024 x 5 + 2 + 3
= 10.78 kg
= 10.8 kg

SYSTEM DESIGN 275


4. Outdoor Installation
4-1. Requirement on installation site
4. Outdoor Installation

1. No direct thermal radiation to the unit.


2. No possibility of annoying the neighbors by the sound of the unit.
Valves and refrigerant flow on the outdoor unit may generate noise.
3. Avoid the sites where strong winds blow.
4. With strength to bear the weight of the unit.
5. Drain flow from the unit is cared at heating mode.
6. Enough space for installation and service as shown at 4-2.
7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.
8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.

SYSTEM DESIGN 276


4. Outdoor Installation
4-2. Spacing

In case of single installation


Secure enough space around the unit as shown in the figure.
<A> : Top view A : Front C : Back
<B> : Side view B : Unit height D : Air outlet guide (Procured at the site)
<C> : When there is little space up to an obstruction

(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall

300*
[11-13/16]

A 450*
[17-23/32]

15* [19/32] 15* [19/32]


<A>
(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall

100*
[3-15/16]

A 450*
[17-23/32]

50* [1-31/32] 50* [1-31/32]


<A>
(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction
h
H

B
h

A
H
[19-11/16]
500

<B>
When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below,
add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.

<Wall height limit> Front: Up to the unit height


Back: Up to 500mm [19-11/16 in.] from the unit bottom
Side: Up to the unit height
If the unit cannot be kept clear of the wall, please change the direction of the air outlet of the unit to blow against the wall to avoid air short cycle.
(4) If there are obstacles at the upper part of the unit

1000
45 [39-3/8]
D
240
[9-15/32]

A C

(Unit : mm [in.])
<C>
50 [1-31/32]

SYSTEM DESIGN 277


4. Outdoor Installation

In case of collective installation and continuous installation


A : Front C : Wall height (H)
B : Must be open
When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and
passageways between groups of units as shown in the figures.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
an asterisk.
If there is a wall at both the front and the rear of the unit, install up to six units consecutively in the side direction and
provide a space of 1000mm or more as inlet space/passage space for each six units.

[11-13/16]

[11-13/16]
300*

300*
C C

B B
A

[35-7/16]
900
B A B
[17-23/32]
450*

C 30
[1-3/16]

[11-13/16] [11-13/16]
300*
C
[3-15/16]
100*

300*
C
B B
A
[17-23/32]
450*

C 100
[3-15/16]

900
[35-7/16]
A B

B 1000*
[39-3/8] B

A A A
C C

450* 450 450 100*


[17-23/32] [17-23/32] [17-23/32] [3-15/16]
B
15*

A A A

(Unit : mm [in.])
450 450
[17-23/32] [17-23/32]

SYSTEM DESIGN 278


4. Outdoor Installation
4-3. Piping direction

4-3-1. Lifting method

When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.
Support the unit at four points with two ropes, and avoid giving mechanical shock.
Suspension rope angle must be 40 or less, so as to avoid compressing fan guard.
Use two ropes, each at least 8m [26 ft.] in length
Use ropes strong enough to support the weight of the unit.
Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-
ed.)
Use protective pads to keep the ropes from scratching the panels on the unit.

(Unit : m [ft.])

8m
40

8m

CAUTION
Exercise caution when transporting products.

Products weighing more than 20 kg [45 LBS] should not be carried alone.
Do not carry the product by the PP bands.
To avoid the risk of injury, do not touch the heat exchanger fins.
Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.
When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.

SYSTEM DESIGN 279


4. Outdoor Installation

4-3-2. Installation

Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or
during an earthquake.
Install the unit on a durable base made of such materials as concrete or angle steel.
Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
noise from being transmitted from the unit through walls and floors.
When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.
Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16 in.].
This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.

WARNING

A : M10 anchor bolt procured at the site. Properly install the unit on a surface that can withstand the weight of
the unit. Unit installed on an unstable surface may fall and cause injury.
B : Corner is not seated.
C : Fixing bracket for hole-in anchor bolt
(3 locations to fix with screws). WARNING
D : Detachable leg Take appropriate safety measures against strong winds and earth-
quakes to prevent the unit from falling.
<Without detachable leg>
[1-3/16 in.]
30mm

Install the unit in such a


way that the corner of
the angle bracket at the
base of the unit shown B
in the figure is securely
supported. The brackets
A may bend if they are not
securely supported. C

<With detachable leg>


[1-3/16 in.]
30mm

Install the unit in such a


way that the corner of
D the angle bracket at the B
base of the unit shown
in the figure is securely
supported. The brackets
A may bend if they are not
securely supported. C D

Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor units
during operation.), piping route, and wiring route when performing foundation work.
4-3-3. Anchor bolt positions
Individual installation Collective installation (Unit : mm [in.])
7243 [(28-13/32~28-5/8)]

7243 [(28-13/32~28-5/8)]

30 [1-3/16] 30 [1-3/16]
A A 190 [7-1/2] A 190 [7-1/2] A
(For maintenance)
Leave a minimum of 30 mm [1-3/16 in.] between units.

PURY RP200, 250, 300


A 10602 [41-3/4(41-21/32~41-13/16)]

SYSTEM DESIGN 280


4. Outdoor Installation

4-3-4. Installation

When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height.

RP200, 250, 300 (Unit : mm [in.])


271 150
[10-11/16] [5-29/32]
301 83 2X2-14X20 Oval hole
145 [5-23/32]
[11-7/8] [3-9/32]
145 [5-23/32]

84 [3-5/16]
131 [5-3/16]

[23/32]
216

18
[8-17/32]

[28-13/32~28-5/8]
(Mounting pitch)
(760 [29-15/16])
724(721 727)
94 [3-23/32]

Refrigerant service
valve <High pressure> Refrigerant service
valve <Low pressure>

80 1060 [41-3/4] 80
[23/32]

(Mounting pitch)
18

[3-5/32] [3-5/32]
Bottom view

Installation base parallel to the units front panel

4-3-5. Refrigerant pipe routing

The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.

This unit allows two types of pipe routing:


Bottom piping
Front piping

CAUTION
To prevent small animals, water, and snow from
entering the unit and damage its parts, close the
gap around the edges of through holes for pipes
Filler plate
Fill the gap at the site
and wires with filler plates.
(not supplied)

SYSTEM DESIGN 281


4. Outdoor Installation
4-4. Weather countermeasure
In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in normal
and good condition in winter time. Surround the units with snow nets or fences to protect them from snow. Even in the other areas,
full consideration is required for installation of unit in order to prevent abnormal operations caused by wind or snow. When rain
and snow directly fall on unit in the case of air-conditioning operations in 10 or less degrees centigrade outdoor air
(50 or less degrees fahrenheit outdoor air) , mount inlet and outlet ducts on unit for assuring stable operations.
Countermeasure to snow and wind
Prevention the Outdoor unit from wind and snow damages in cold or snowy areas, snow hood shown below is recommended
and helpful.
Snow hood
1206 [47-1/2]
750 [29-17/32]
800 [31-1/2]

(1220)[48-1/16]
1324 [52-5/32]

B (760)
[29-15/16]
[3-13/32]
86

B
B
H

453 453
[17-27/32] 1210 [47-21/32] [17-27/32] 453
760 [29-15/16] [17-27/32]
<Front view>
<Side view>
A Outlet B Inlet
Note:
1. Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base
shall not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind slip
through the structure. (If frame base is too wide, snow will be accumulated on it.)
2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3. Build frame base at customer referring to this figure.
Material : Galvanized steel plate 1.2T [1/16 in. T]
Painting : Overall painting with polyester powder
Color : Munsell 5Y8/1 (same as that of unit)
4. To install units side by side, install a filler plate between
the fan guard and the outlet-side snow food as shown in Figure A.
(The filler plate provided accommodates the installation pitch of between 30-80 mm [1-3/16~3-5/32 in.].)
5. When the unit is used in a cold region and the heating operation is continuously
performed for a long time when the outside air temperature is below freezing, install Figure A Filler plate
a heater to the unit base or take other appropriate measures to prevent water from freezing on the base.
Countermeasure to wind
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.
A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.
To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away
from the direction of the wind.

A Wind
A

Install the outdoor unit where seasonal Install the outdoor unit to avoid having
winds do not blow directly against the
A seasonal winds against the front of air
unit, such as behind a building. outlet/inlet on the unit.

SYSTEM DESIGN 282


5. Caution for refrigerant leakage
The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.
5. Caution for refrigerant leakage

The following standard may be applicable if no local regulation or standard is available.

5-1. Refrigerant property


R410A refrigerant is harmless and incombustible. The R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room
has possibility to lead to a hypoxia situation. Therefore, the Critial concentration specified below shall not be exceeded even if the leakage
happens.
Critical concentration
Critical concentration hereby is the refrigerant concentration in which no human body would be hurt if immediate measures can be taken
when refrigerant leakage happens.
Critical concentration of R410A: 0.30kg/m3
(The weight of refrigeration gas per 1 m3 air conditioning space.);
The Critical concentration is subject to ISO5149, EN378-1.
For the CITY MULTI system, the concentration of refrigerant leaked should not have a chance to exceed the Critical concentration in
any situntion.
5-2. Confirm the Critical concentration and take countermeasure
The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)
leaked into a room divided by its room capacity (V).It is referable to Fig.5-1.The refrigerant of Outdoor unit here includes its original
charge and additional charge at the site.
The additional charge is calculated according to 3-2 .Refrigerant charging calculation and shall not be over charged at the site.
Procedure 5-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take countermeasures against
a possible leakage.
Outdoor unit (No.1) Outdoor unit (No.1) Outdoor unit (No.2)

Flow of refrigerant Flow of refrigerant Flow of refrigerant

Indoor unit Indoor unit

Maximum refrigerant leakage concentration (Rmax) Maximum refrigerant leakage concentration (Rmax)
Rmax=Wmax / V (kg/m3) Rmax=Wmax / V (kg/m3) W1: Refrigerant weight of Outdoor unit No.1
where, Wmax=W1+W2 W2: Refrigerant weight of Outdoor unit No.2
Fig. 5-1 The maximum refrigerant leakage concentration
5-2-1.Find the room capacity (V),
If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space are
considered as one.The total space shall be added up.
5-2-2.Find the possible maximum leakage (Wmax) in the room.If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refriger-
ant of the Outdoor units.
5-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).
5-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3.
If no, then the CITY MULTI is safe against refrigerant leakage.
If yes, following countermeasure is recommended to do at site.
Countermeasure 1:Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.
e.g.make the upper and lower seams of door big enough.
Countermeasure 2:Smaller total charge (making Wmax smaller)
e.g.Avoid connecting more than 1 Outdoor unit to one room.
e.g.Using smaller model size but more Outdoor units.
e.g.Shorten the refrigerant piping as much as possible.
Countermeasure 3:Fresh air in from the ceiling (Ventilation)
As the density of the refrigerant is bigger than that of the air.Fresh air supply from the ceiling is better than air exhausting from the ceiling.
Fresh air supply solution refers to Fig.5-2~4.
Fresh air supply fan (always ON) Fresh air supply fan Refrigerant pipe (high pressure pipe)
Fresh air supply fan
Refrigerant pipe Refrigerant pipe
Refrigerant stop valve
to Outdoor unit to Outdoor unit
to Outdoor unit

Indoor unit Indoor unit


Indoor space Indoor space Indoor unit
Indoor space

(Floor) (Floor)
Opening (Floor)
Opening
Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).
[At 0.3m height from the floor]
[At 0.3m height from the floor]

Fig.5-2.Fresh air supply always ON Fig.5-3.Fresh air supply upon sensor action Fig.5-4.Fresh air supply and refrigerant
shut-off upon sensor action
Note 1.Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens.
Note 2.In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.
The piping should consider the extension due to the temperature variation.

SYSTEM DESIGN 283


SYSTEM DESIGN 284
CONTROLLER

1-1.System component ......................................................................................................................................... 286


1-2.Outdoor unit input/output connector ............................................................................................................... 288
1-3.Indoor unit "-E" type input/output connector.................................................................................................... 289

CONTROLLER 285
CONTROLLER
1-1. System component
1. System component
I.

CITY MULTI system can be monitored or controlled with signal to/from the outside as every control board of Indoor unit or Outdoor unit has input/output signal
connectors. Independent control to the individual Indoor or Outdoor can be carried out by using these connectors. Yet, for large-scale control, MELANS would be
much easier. When using input/output connectors, a dedicated adapter (optional part) and a relay circuit needed to be prepared by the site.
Following are some typical example.
Table 1-1. Control can be achieved by using Outdoor input/output connectors.
Using connector
Function Usage Signal Option
PUHY PURY
Demand Prohibiting cooling/heating operation (thermo OFF) by an external input to the CN3D CN3D Input Adapter for external
(level-signal)
outdoor unit. input
* It can be used as the demand control for each refrigerant system. (PAC-SC36NA-E)
Low noise mode Performs a low noise operation of the outdoor unit by an external input to the outdoor unit.
* It can be used as the low noise operation device for each refrigerant system.
Snow sensor signal input Forces the outdoor unit to perform a fan operation by receiving signals from the CN3S CN3S
snow sensor. *4
Auto-changeover Cooling/heating operation can be changed by an external input to the outdoor unit. CN3N -
Operation status of the How to extract signals from the outdoor unit. CN51 CN51 Output Adapter for external
compressor * It can be used as an operation status display device. (level-signal) output
Error status * It can be used for an interlock operation with external devices. (PAC-SC37SA-E)

*1 For details, refer to 1) through 4) shown below.


*2 Low noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of on-DEMAND are possible, using different
configurations of low noise mode input and DEMAND input settings.
When 2 or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible. When 3 outdoor units exist in one refrigerant circuit
system, 12 levels of on-DEMAND are possible.
*3 Low noise mode can be switched from ability main to low noise main with Dip SW5-5 on the outdoor unit. Dip SW5-5 OFF: ability main (ability main mode : The sound pressure level is
reduced by limiting the maximum fan frequency under the following condition. Cooling mode : outdoor temp. (TH6)< 30C Heating mode : outdoor temp. (TH6) > 3C), ON: low noise main.
*4 When multiple outdoor units exist in one refrigerant circuit system, settings on every outdoor unit (signal input) are required.
*5 For detailed drawing, refer to "1-2. Outdoor unit input/output connector".
1) Table 1-1-1 SW4-4: OFF (Compressor ON/OFF, Low noise mode)
CN3D 1-3P 2-level of on-Demand *6
Open 100%(No Demand)
Short-circuit 0%

CN3D 1-2P Low noise mode *7


Open OFF
Short-circuit ON
*6 When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON (4 levels or 8 levels or 12 levels of on- DEMAND), this function cannot be used.
*7 This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on the outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND) (*8)
CN3D 1-2P
CN3D 1-3P Open Short-circuit
Open 100% (No DEMAND) 75%
Short-circuit 0% 50%
Note the following steps to be taken when using STEP DEMAND. If the demand settings are switched in the wrong order listed as the
Example: When switching from 100% to 50% wrong example above, the unit may go into thermo OFF mode.
The percentage of the DEMAND listed in the table above is an
Steps in DEMAND <WRONG> 100% NO
0% 50%
approximate value based on the compressor volume and does not
level setting <CORRECT> 100% OK
75% 50% necessarily correspond with the capacity.
This function and the Low noise mode function cannot be used together.
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND) (*8,*9)
8 levels of on-DEMAND No.2 CN3D
1-2P Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit
Open Open 100% (No DEMAND) 50% 88% 75%
Short-circuit 50% 0% 38% 25%
Short-circuit Open 88% 38% 75% 63%
Short-circuit 75% 25% 63% 50%
4) When SW4-4 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND) (*9)
12 levels of No.2 CN3D 1-2P Open
on-DEMAND 1-3P Open Short-circuit
No.3 CN3D 1-2P Open Short-circuit Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit Open Short-circuit Open Short-circuit
Open Open 100% 67% 92% 84% 67% 34% 59% 50%
Short-circuit 67% 34% 59% 50% 34% 0% 25% 17%
Short-circuit Open 92% 59% 84% 75% 59% 25% 50% 42%
Short-circuit 84% 50% 75% 67% 50% 17% 42% 34%

12 levels of No.2 CN3D 1-2P Short-circuit


on-DEMAND 1-3P Open Short-circuit
No.3 CN3D 1-2P Open Short-circuit Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit Open Short-circuit Open Short-circuit
Open Open 92% 59% 84% 75% 84% 50% 75% 67%
Short-circuit 59% 25% 50% 42% 50% 17% 42% 34%
Short-circuit Open 84% 50% 75% 67% 75% 42% 67% 59%
Short-circuit 75% 42% 67% 59% 67% 34% 59% 50%
*8 Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*9 CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.

CONTROLLER 286
CONTROLLER

Table 1-2. Control can be achieved by using Indoor input/output connectors.


Function Usage Using connector Signal
Remote/Local switching *1 Indoor group can be controlled ON/OFF by an ON/OFF switching or contact input to CN32 Input
ON/OFF *2*3 the connector of the head Indoor in an Indoor group. (level-signal)
It can be interlocked with timer, door, window, or other equipment to "Force stopping"
ON/OFF *2*3 Indoor group can be controlled ON/OFF by an external pulse signal input to the CN51 Input
connector of the head Indoor in an Indoor group. (pulse-signal)
Demand Indoor group can be controlled ON/OFF by an ON/OFF switching or contact input to CN52 Input
the connector of every Indoor in an Indoor group. (pulse-signal)
Monitoring ON/OFF state Signal output from a head Indoor unit, presenting its Indoor group. CN51
Monitoring heating state It can be used for monitoring or interlock with other equipment purpose and so on. CN52 Output
Monitoring cooling/drying state CN52
Monitoring Error state Signal output from every Indoor unit, for monitoring Error or Thermo-off (fan) state. CN51 Output
Monitoring Thermo-OFF(fan) state It can be used for monitoring or interlock with other equipment purpose and so on. CN52
*1. When switching to Remote, control at Local remote controller will NOT be effective, but the "CENTRALLY CONTROLLED" is displayed.
*2. MA or ME remote controller is needed for this function.
*3. If using ON/OFF input function, Automatic-address-start-up can not be performed to start-up the system at commissioning.
*4. If CITY MULTI use GB-50A/AG-150A and PLC software to control the Indoor unit via its external input/output connectors, Dip Switch 1-9 and Dip Switch 1-10
should be set to ON.
In this case, the input/output connectors act as normal connectors, functions mentioned at Table 1-2 are no more available.
Details are available at the PLC software Instruction Manual.

Table 1-3. ON/OFF control to each Indoor unit (group) by using Dip Switch 9 and 10 (SW1-9, SW1-10) of the Indoor unit.
Function Operation on Indoor units Setting Dip Switch *1*4
1-9 1-10
Auto ON All indoor units will turn ON and automatically resume to its previous mode after 5 minutes from OFF ON
power recovery.
Auto recovery Indoor unit recovers to its previous state (ON/OFF, mode) after 5 minutes from power recovery. ON OFF
All OFF Forced stopping regardless of Indoor units' state. OFF OFF
*1. The Dip Switch setting should be carried out on every Indoor unit in the group.
*2. Outdoor unit's power supply should NOT be cut. Otherwise, power supply to case heater of the compressor would be cut too, which may cause damage to the
compressor.
*3. Above method can not be applied to the power ON/OFF of the drain pump and humidifier equipment.
*4. If CITY MULTI use GB-50A/AG-150A and PLC software to control the Indoor unit via its external input/output connectors, Dip Switch 1-9 and Dip Switch 1-10
should be set to ON.
In this case, the input/output connectors act as normal connectors, functions mentioned at Table 1-3 are no more available.

System example
Outdoor unit

Outdoor unit
power supply
Indoor unit

Indoor unit
power supply

Local
Switch remote
controller
Restart of the CITY MULTI needs to be careful. When no power supply to the outdoor unit, no power supply to the compressor case heater too. The compressor
needed to be warmed up before running. When using above functions, power supply to the outdoor unit should be ensured.

Table 1-4. How to use Remote/Local switching connector CN32


State Local remote controller display and operation CN32-SW-1 CN32-SW-2
for Local/Remote for Remote
control switching "ON/OFF" operation
Local remote controller control Operation is permitted OFF OFF
Remote STOP "CENTRALLY CONTROLLED" flashing, "ON/OFF" at local remote controller is not possible. ON OFF
Remote START "CENTRALLY CONTROLLED" flashing, "ON/OFF" at local remote controller is not possible. ON ON
* For details refer to CN32 in section 1-3. Indoor unit -E type input/output connector.

Table 1-5. Limitations to combining system controls


Control combining
Description Pulse ON/OFF Power ON/OFF Automatic recover
distant/local
1 Control combining distant/local CN32 - *1 *1 *1
2 Pulse ON/OFF CN51 - O O
3 HA ON/OFF(JEMA) CN51 O O
4 Power ON/OFF - -
5 Automatic recover - -
*1. Pulse ON/OFF, power ON/OFF and automatic recover can only be used when the remote/local setting CN32 is set to local.
Therefore, always avoid this function when combining control.

CONTROLLER 287
CONTROLLER
1-2. Outdoor unit input/output connector

1.Wiring should be covered by insulation tube with supplementary insulation.


Caution: 2.Use relays or switches with IEC or equivalent standard.
3.The electric strength between accessible parts and control circuit should have 2750V or more.

1-2-1. Output
State (CN51)
Distant control
board Relay circuit Adapter *1 Outdoor unit L1 : Outdoor unit error display lamp
L1 X control board L2 : Compressor operation lamp (compressor running state)
Lamp power source

Y X, Y : Relay (coil =<0.9W : 12VDC)


X Y 5 CN51
L2 4
*1. Optional part : PAC-SC37SA-E or field supply.
3

Preparations
in the field Maximum cable
length is 10m

1-2-2. Input
Y, R2 series
(1) Step demand and Low noise mode (CN3D) (2) Low noise mode (CN3D + DipSW4-4 OFF)
For details, refer to "Table 1-1". Outdoor unit
Outdoor unit Relay circuit Adapter *2 control board
Relay circuit Adapter *2 control board
CN3D
CN3D X 1
X 1 2
2
Y 3
3

Preparations
Preparations
in the field
in the field
Maximum cable
Maximum cable
length is 10m
length is 10m X : Relay Contact rating voltage >= 15VDC
X : Low noise mode or demand Contact rating current >= 0.1A
Y : Demand Minimum applicable load =< 1mA at DC
X,Y : Relay Contact rating voltage >= 15VDC *2. Optional part : PAC-SC36NA-E or field supply.
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC Low noise mode : The sound pressure level is reduced by controlling
*2. Optional part : PAC-SC36NA-E or field supply. the maximum fan frequency and compressor frequency.
-Note-
The sound pressure level can not be reduced, when neither
the fan frequency nor the compressor frequency are maximum.

(3) Autochangeover (CN3N) (R2 excluded) (4) Snow sensor (CN3S)


Relay circuit Adapter *2 Outdoor unit Outdoor unit
control board Relay circuit Adapter *2 control board
X 1 CN3N
CN3S
2 X 1
2
Y 3
3

Preparations
Preparations
Maximum cable in the field
in the field
length is 10m Maximum cable
X : Cooling / Heating length is 10m
Y : Validity / Invalidity of X X : Relay Contact rating voltage >= 15VDC
X,Y : Relay Contact rating voltage >= 15VDC Contact rating current >= 0.1A
Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
Minimum applicable load =< 1mA at DC *2. Optional part : PAC-SC36NA-E or field supply.
*2. Optional part : PAC-SC36NA-E or field supply. Snow sensor : The outdoor fan runs when X is closed
in stop mode or thermostat mode.
X
OFF ON
OFF Normal
Y
ON Cooling Heating

CONTROLLER 288
CONTROLLER
1-3. Indoor unit "-E" type input/output connector

1.Wiring should be covered by insulation tube with supplementary insulation.


Caution: 2.Use relays or switches with IEC or equivalent standard.
3.The electric strength between accessible parts and control circuit should have 2750V or more.

ON/OFF (Pulse) input specification


Item Description
Input signal Pulse sign (a connect)

Standard of pulse

200msec or more

Input Output

CN51 CN52
Distant control board Relay circuit Adapter 1 Distant control board Relay circuit Adapter 1 Indoor unit
Indoor unit
control board
control board 1
SW 1
Power supply Power supply
X L1 CN52
of relay X 2 CN51 of relay X Z Y X
2
L2
3 Y
3
L1
Y Z Y L3
4 Z 4
L2
Z 5

Maximum cable
Maximum cable length is 10m[32ft.]
L1 : Status lamp
SW : Distant ON/OFF switch length is 10m[32ft.] Fan motor output (SW1-5 OFF)
L1 : Status lamp Every time the SW is pushed Thermostat ON (SW1-5 ON)
L2 : Error lamp (the pulse is inputted), it L2 : Cooling/Dry status lamp
X : Relay (a point of contact, fixed DC1mA) reacts against ON/OFF. L3 : Heating status lamp
Y, Z : Relay Contact rating voltage >= 15VDC X, Y, Z : Relay (Coil with fixed 12VDC, a power consumption of 0.9W or less)
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC

CN32
Distant control board Relay circuit Adapter 2 Indoor unit
control board
1
Power supply Y
CN32
X
of relay
SW2 X 2

SW1 Y 3

Maximum cable
length is 10m[32ft.]
SW1 : Distant/Local switching SW2 is available when SW1
SW2 : ON/OFF switch is ON.
X, Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC

CN52
Distant control board Relay circuit Adapter 1 Indoor unit
control board

Power supply 1
CN52
of relay
X

SW1 X 5

Maximum cable
length is 10m[32ft.]
SW1 : Demand switch
X : Relay (coil <=0.9W,12VDC)

SW1 Indoor unit


ON Forced thermo-OFF
1. Optional part : PAC-SA88HA-E or field supply
OFF Normal running 2. Optional part : PAC-SE55RA-E or field supply

CONTROLLER 289
DATA BOOK PUHY-RP-Y(S)JM-B
PURY-RP-YJM-B

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

New publication effective Feb. 2011


MEE10K014 Specifications subject to change without notice