1 Railway Power Supply Systems DC Electrification Systems Control Center
Rectifier Transformer Supervisory Control And Data Acquisition (SCADA)
Traction Rectifier
Regenerative Inverter
Rail transport has been evaluated as an environment-friendly transportation system, helping to solve environmental DC Switchgear
Protection Relay
pollution, energy resources shortage, and chronic traffic congestion problems in developing countries. HSVCB
Since Toshiba started manufacturing traction motor and propulsion systems in 1899, we have made continuous Package-Type DC Substation
SCiB Traction Energy Storage System
technological innovations which led to the creation of new transportation systems, including power supply
systems. We have now expanded our business to supply advanced technologies on a global scale.
In the pursuit of technological innovation, global environmental issues are important, and demand is high for the
creation of a new product value aimed at reducing environmental impact while ensuring safety and comfort.
We offer products and systems to support your organizations activities aimed at protecting the environment,
thus contributing to the creation of a sustainable, eco-friendly society.
1 2
2 System Integration
Route map Timetable Our long histor y of engineering
Toshiba has been continuously striving to provide customers with advanced, optimal solutions. We are able railway system projects has given
us extensive expertise in designing
to provide not only the latest environmentally-friendly products from all over the world but also consulting
railway power supply systems. Our in-
services like energy simulation and construction works as well. house simulator is able to calculate
various railway system conditions
w i t h re m a r k a b l e a c c u r a c y. O u r
Substation experienced engineers are also there
Voltage to provide consultation and offer
customer-oriented solutions.
Current
Power
Train
Engineering
Toshiba is able to supply transmission and distribution products from
our bases all over the world, using our worldwide distributors to offer
customer-oriented solutions at a competitive price.
Construction
Procurement
& Manufacturing
Solid Insulated Switchgear Vegetable Oil Transformer SCiB Traction Energy Storage System
Having started in the transportation business in 1899, Toshiba has extensive experience in offering innovative railway system products. For In addition to supplying products, Toshiba also provides customers with FTK solutions. One representative example of our FTK comma the
power supply systems, our current products such as the Solid Insulated Switchgear, Vegetable Oil Transformer and SCiB Traction Energy Taiwan High Speed Railway, wherein Toshiba built and supplied essential products for railway electrification.
Storage System, are environment friendly solutions which contribute to a more sustainable environment.
3 4
3 Transmission Systems
3-1 Gas Insulated Switchgear (GIS)
Railway Power Supply equipment must be highly reliable and safe. In addition, today's equipment must The Gas Insulated Switchgear (GIS) is an integrated switchgear which uses SF6 insulation gas. It is used mainly in 72.5kV or higher
also be economically efficient to accommodate installation in limited space and in a short period of time. systems. Toshiba has a long history for developing and manufacturing GIS.
Therefore, Toshiba developed the highly reliable SF6 Gas Insulated Switchgear (GIS) which can simplify site
work and reduce land footprint by up to 92%. For the main transformer, Toshiba offers a non-flammable
Gas Insulated Transformer (GIT)
for a more compact substation
solution. As for Toshibas product
l i n e - u p fo r m i d d l e vo l t a g e
switchgears, we developed the
Cubicle t ype G as I nsulated
Switchgear (C-GIS) and SF6 gas
free Solid Insulated Switchgear
(SIS).
Ratings
P6 Features
P11
Transmission Systems Rated Voltage [kV] 72.5 ~ 252 Rated Voltage [kV] 36 / 72
Rated Interrupting Current [kA] 25 ~ 63 Rated Bus Current [A] 1200
Rated Lightning Impulse Withstand Voltage [kV] 325 ~ 1050
Rated
Compact Design
Breaking Current [kA] 16 / 25
Can be installed in indoor and underground substations
Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 Lightning Impulse [kV] 200 / 350
Typical space for AIS+OIT Rated Gas Pressure 0.7(GCB) / 0.7(GIS)
Rated Withstand Voltage
Outdoor Compatibility Power Frequency [kV] 70 / 140
2,236m2 Applicable Standards JEC / IEC Rated Gas Pressure
Protection against[MPa G]
pollution 0.05 (at 20C)
OIT
Safe Operation
Electrified parts are enclosed in the earthed tank
P11
P7
52m Rated
LowVoltage
Maintenance
[kV] 36
GSR GSM / GSP GSPF Rated Current [A] 1200
OIT Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 Between Main Circuit and Earth 200
Lightning
Method of Operation Hydraulic Motor Spring Motor Spring Rated Impulse [kV] Between Main Circuit Terminals 250
Safe Withstand
Tank Dead Tank Live Tank Power Between Main Circuit and Earth 70 1min.
Using safe material Voltage
Lighting (LTO) Frequency [kV] Between Main Circuit Terminals 100 10min.
Rated 900 / 1050 350 / 400 / 750 650
Impulse [kV]
Low Temperature High Effective
Withstand
Application Feeding System for High Speed Railway GIT Auxiliary Power DC 110V,
5 T-type Bushing Busbar 6 Battery
Lead Storage
Supply Unit AC 105V / 210V
ES EVT Rated Voltage [kV] 220 / 25x 2 ; 161 / 60x 2 ; 132 / 27.5x 2
TT Cooling Type ONAN / ONAF / OFAF
DS
Rated Power [MVA] 84 / 60
ES DS
VCB Overload 200% 5mins
P13
VCB CHD Connection Scott
3-3 Gas Circuit Breaker (GCB) 3-5 Solid Insulated Switchgear (SIS)
Gas Mineral Oil
Toshiba supplies many
Liquid Silicone
types of Gas Circuit
Vegetable Oil
Breakers (GCB) for 72kV or higher voltage.
Epoxy Resin Toshiba developed Solid Insulated Switchgear (SIS), which utilizes high-performance epoxy resin independently developed
Applicable for up to 6MW Rectier as insulating material for SIS. Our epoxy resin provides a remarkable improvement in strength, flexibility, heat-resistance
OIT
77kV 35kV and dielectric strength. By using this material for switchgear insulation, we are able to reduce the size while maintaining the
Applicable for DC600V / 750V / 1500V / 3000V equipments high reliability. Installation space required for the 72/82kV SIS is smaller than our conventional 72kV air-insulated
JEC / IEC switchgear. For the 24/36kV SIS, the new Balanced Magnetic Actuator (BMA) for
P6 the VCB is utilized which further reduces the size
P11
52m and weight of the SIS without compromising its performance.
Rated Voltage [kV] 72.5 ~ 252 Rated Voltage [kV] 36 / 72
OIT
Rated Interrupting Current [kA] 25 ~ 63 Rated Bus Current [A] 1200
Rated Lightning Impulse Withstand Voltage [kV] 325 ~ 1050 Rated Breaking Current [kA] Busbar 16 / 25
self cooling VDS
P6 P11 Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 LightningSafe
Impulse [kV] 200 / 350
P14 Rated Withstand Voltage Using safe material
Rated Gas Pressure 0.7(GCB) / 0.7(GIS) Operation Power Frequency
(LTO) [kV] 70 / 140
1500V / 3000V Rated Voltage [kV] 72.5 ~ 252 Rated Voltage [kV] 36 / 72 Mechanism
Applicable Standards JEC / IEC Rated Gas Pressure
Low Temperature [MPaG] 0.05 (at 20C)
High Effective
Rated Interrupting Current [kA] 25 ~ 63 Rated Bus Current [A] 1200 Cooling and Insulating Method Gas Mineral Oil Liquid Silicone Vegetable Oil Epoxy Resin
Operation Capacity
Rated Lightning Impulse Withstand Voltage [kV] 325 ~ 1050 Rated Breaking Current [kA] AIS 16 / 25 Rated Power Protection
Applicable for up to 6MW Usable
Rectier
in extremely Attractive features are realized by High amount of actual
Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 Lightning Impulse [kV] 200 / 350 Relay cold enviroments usable energy over
Rated Withstand Voltage Primary 77kVP11 Titanate
using Lithium 35kV OxideVD
Rated Voltage (-30C) wide range of SOC
Rated Gas Pressure 0.7(GCB) / 0.7(GIS) Power Frequency [kV] 70 / 140 P7 (LTO) in its anode
Secondary Applicable for DC600V / 750V / 1500V / 3000V
Applicable Standards JEC / IEC Rated Gas Pressure [MPaG] 0.05 (at 20C) Rated Voltage [kV] 36
Applicable Standard GSR GSM / GSP GSPF JEC / IEC ES
Rated Current [A] 1200
240kV GCB 72kV GCB 145kV 3-Phase GCB VCB
Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 Lightning Between Main Circuit and Earth 200
Rated
P11 P14 Method of Operation Hydraulic Motor Spring Motor Spring Impulse [kV] Between Main Circuit Terminals 250
Ratings
P7
16m Tank Dead Tank Live Tank
Voltage
Rapid
Withstand
Power
Recharging
Main Cable
Between Main Circuit and Earth 70 &1min.
Input Output
High
Rated Voltage [kV] 36 Cooling Method Lighting Vertical heat-pipe self cooling
GSR GSM / GSP GSPF Features Good Breaking
Rated Current [A] 1200
Ability Rated
Rated Power Impulse [kV]~ 6 MW
900 / 1050 350 / 400 / 750 650
Frequency [kV]
Recharges Between Main Circuit
CT Terminals 100 10min.
Usable with
43m Withstand in approx. 6 minutes high current
Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 Rated Short Time Withstand
Easy Installation
Lightning Between Main Circuit and Earth 200 Rated Voltage
Voltage Power 200-265-200(1min)/
DC 600V / 750V / 1500V / 3000V
140 / 160 / 325 275 Current [kA]
12.5 Long
2sec.Life
Method of Operation Hydraulic Motor Spring Motor Spring Rated Impulse [kV] Between Main Circuit Terminals 250 Frequency [kV] 250-330-250(1min)
Applicable Standard JEC / IEC GIT Over 6,000 charge-
Tank Dead Tank Live Tank
Withstand
Voltage
Low NoiseBetween Main Circuit and Earth 70 1min.
Power Applicable Standards JEC / IEC 24kV SIS Switching Lifetime
Mechanical 200,000 times
discharge cycles
1,000kWcontinuous rating GIS Electrical 100,000 times
g Inverter mode Lighting Frequency [kV] Between Main Circuit Terminals 100 10min.
Rated
3,000kW1minute or 4,500kW-30seconds 900 / 1050 350 / 400 / 750 650
Impulse [kV]
Withstand Rated Short Time Withstand
nverter mode 1,000kWcontinuous rating
Voltageonly Power 200-265-200(1min)/ 12.5 2sec.
140 / 160 / 325 275 Current [kA] 11m
Frequency [kV] 250-330-250(1min) GIT
ol mode (Make a selection for your operation ) Applicable Standards JEC / IEC Switching Lifetime
Mechanical 200,000 times Ratings
P8
Electrical 100,000 times P17
rol: To 6 or 8 output regulation
voltage control Rated Voltage [kV] 24 36 40.5 72 84 Features SF6 gas-less due to epoxy-
Rated Voltage [V] DC 750 , 1500
Rated Lightning Impulse [kV] 125 170 185 350 400
Rated Current [A]
resin coating
3000 , 4000
Withstand
allel * 6Arm * 2Bridge
800 / 1250
160 Rated Breaking Capacity
Compact Design
[kA] 50 (at 3106A / sec), 100 (at 1010 6A / sec)
Rated Short Time Current [kA] 50-1sec , 100-1sec
Outdoor Compatibility
24 36 40.5 72 84 Applicable Standard JIS (To be developed for IEC)
Rated Voltage [V] DC 750 , 1500
pure water (natural cooling type) Rated Lightning Impulse [kV] 125 170 185 350 400
Rated Current [A] 3000 , 4000
Rated Short Time Withstand
Current [kA]
25 / 31.5 1,000kWcontinuous rating Safe Operation
0W * 2,200D * 2,900H Withstand
The Cubicle Type Gas Insulated Switchgear (C-GIS) is an integrated switchgear which uses SF6 Regenerating Inverter mode
Power Frequency [kV] 50 70 95 140 160 Capacity 3,000kW1minute or 4,500kW-30seconds
of Inverter-800W * 1,000D * 2,300H
Voltage Rated Breaking Capacity [kA]
insulation gas. It is used mainly in 36kV to 84kV systems. Toshiba spent many years developing
50 (at 3106A / sec), 100 (at 1010 6A / sec) Applicable Standard JEC / IEC / GB Low Maintenance
630 / 1250 / 1250 / Rated Short Time Current [kA] 50-1sec , 100-1sec Powering Converter mode 1,000kWcontinuous rating only
2,800W * 2,000D * 2,500H and manufacturing
Rated Current [A] high quality C-GIS. Vacuum2000
circuit800
breakers
/ 1250 (VCB) are used for the C-GIS.
2000 Applicable Standard JIS (To be T-type Bushing
developed for IEC) Busbar
1,500VDC
P17 High Reliability
Rated Short Time Withstand ES EVT Output control mode (Make a selection for your operation ) Specifications Applicable equipments
25 / 31.5 Rated Input Voltage
Current [kA] -1) Load control: To 6 or 8 output regulation
DS TT
Applicable Standard JEC / IEC / GB -2) Constant voltage control MV Switchgear Unit 7.2 / 24 / 36kV Air Insulated type or
ES DS Solid Insulated type
P17 P13 P8
Rated Output Voltage
VCB 1,200VAC
36 40.5 72 84 VCB Eco-Friendly
CHD
Main Circuit Configuration
Design
1Series * 2Parallel * 6Arm * 2Bridge Safe Design
12-Pulse Rectifier Unit Up to 2,000kW
TR : Epoxy Resin Molded Dry
/ Liquid Silicone
[kV] 170 185 350 400 Specifications Applicable equipments Double bridge parallel configuration by Transformer SR : Heat-pipe Self-cooling
ES
Device IGBT (3,300V-1,200A) / MG1200FXF1US53(P)
kV] 70 95 140 160 MV Switchgear Unit 7.2 / 24 / 36kV Air Insulated
CHD type or P10
The Greenhouse Eect DC Switchgear Unit DC 600V, DC1500V HSCB or HSVCB
630, 1250, 2500 630, 1250, 2000 800, 1250 800, 1250 Solid Insulated type
ESResin Molded Dry
Sun
Device Cooling System
Application
Heat-pipe in pure water (natural cooling type)
Feeding System
Inverter-2,700W for High
* 2,200D
C-GIS
Speed
* 2,900H Railway Auxiliary Power DC 110V, Lead Storage Battery
25, 31.5 25, 31.5 20, 25, 31.5 20, 25, 31.5 TR : Epoxy Supply Unit AC 105V / 210V
JEC / IEC 12-Pulse Rectifier Unit Up to 2,000kW / Liquid
DS Silicone Rated Voltage
Dimension CT [kV] 220Panel
Control / 25xof2 Inverter-800W
; 161 / 60x 2 ; 132 / 27.5x*22,300H
* 1,000D
SR : Heat-pipe Self-cooling Cooling Type ONAN / ONAF /*OFAF
ES DC Reacrtor-2,800W 2,000D * 2,500H
P10 DC Switchgear Unit DC 600V, DC1500V HSCB orCT
HSVCB Rated Power [MVA] 84 / 60
Overload 200% 5mins Atmo
Application Feeding System for High Speed Railway
72kV C-GIS
Auxiliary Power
Cross-section
Supply Unit
DC 110V,
AC 105V / 210V
Lead Storage Battery
Connection Scott Green sph P13 Zero SF6 5kg 0kg
Rated Voltage [kV] 220 / 25x 2 ; 161 / 60x 2 ; 132 / 27.5x 2 h ous er
Cooling Type ONAN / ONAF / OFAF
P7 Applicable Standard JEC / IEC e Ga
e Half Weight
21F 1,900kg
Distance 850kg
Protection
51F Overcurrent Protection
Ratings
P7
Rated Power [MVA] 84 / 60 Rated Voltage [kV] 36 se 40.5 72 Half Components
Protection Function 84 2500pcs 1200pcs
s 27F Voltage Protection
27.5
Overload
Rated Voltage [kV]
200% 5mins
36 40.5 72 84 Features
P13 21F
Compact Design 50F
Rated Withstand Voltage
Lightning Impulse [kV] 170 185 350 37% Less Volume
79
4002.7m3 1.7m3
Automatic Reclose
Connection Scott P10 Power Frequency [kV] 70 95 140 160
Rated
1250 Applicable
Lightning Impulse [kV]
Withstand Standard JEC / IEC
170 185 350 400 Outdoor
21FCompatibility
Distance Protection Rated Current [A] Earth
630, 1250, 2500 630, 1250, 2000 800, 1250 800, 1250
e [kV] 250 Voltage Power Frequency [kV] 70 95 140 160 51F Overcurrent Protection Example
Rated Short Time ofWithstand
Roof-delta Connection
Current [kA] Transformer 25, 31.5 25, 31.5 20, 25, 31.5 (Comparing with
20, 25, 31.5 products at 24kV)
[kV] 95 630 / 630 /
Safe
Protection Function Operation
27F Voltage Protection UtilityStandards Feeding System for High Speed Railway SIS BusbarJEC
Compartment
TOSHIBA
800 / 800 / Applicable / IEC
Rated Current [A] 1250 / 1250 /
25
P10 2500 2000
1250 1250 Low Maintenance
79 Automatic Reclose SFRated
6 gasVoltage [kV]
is evaluated as the 220kV
most/ potent
60kV2 greenhouse gas and it SIS has an "Internal arc-free" feature which promotes safe
Cooling Type ONAN
poses negative effects in the environment. As part of Toshibas operation. Busbar and devices in each phase of the main
Rated Short Time Withstand
Current [kA]
25 /
31.5
25 /
31.5
20 / 25 / 20 / 25 /
31.5 31.5
Easy Withstand Voltage Test Ratedfor
drive Power development of60more eco-friendly products, Toshiba
the[MVA] circuit P10
are completely insulated with earthed layer of
Example of Roof-delta Connection Transformer
Overload a new material which
introduced 300%possesses
2min high dielectric strength. Toshiba'sRated
unique epoxy
[kV] resin mold 27.5
coating.
Applicable Standards JEC / IEC
Utility Feeding System for High Speed Railway Voltage
Connection Roof-delta
7 Rated Voltage [kV] 220kV / 60kV2 Rated Lightning 200 (to earth and across open8 contacts)
Applicable Standard JEC / IEC P7Withstand Impulse [kV] 220 (across isolating distance)
Cooling Type ONAN P12
Voltage
Rated Power [MVA] 60 P10 Rated (Line to [kV] Power
Voltage 95 36
(to earth40.5
and across72open contacts)
Rated Voltage [kV] 27.5 84
Overload 300% 2min Earth) Frequency [kV] 110 (across isolating distance)
Rated Voltage [kV] 27.5 Rated Lightning Impulse [kV] 170 185 350 400
Rated Current [A]
P10 1250
Connection Roof-delta Withstand
Rated Current [A] 1250
Rated Lightning 200 (to earth and across open contacts) Lightning Impulse [kV] 250 Voltage Power Frequency [kV] 70 95 140 160
Applicable Standard JEC / IEC Withstand Impulse [kV] 220 (across isolating distance) Rated Rated
Withstand Voltage
Voltage [kV] 55 / 27.5 Rated Short Time Withstand
Rated Gas Pressure
Withstand 0.7(GCB) / 0.7(GIS) Rated S
Voltage Power 200-265-200(1min)/
Applicable Standards 140 / 160JEC
/ 325
/ IEC 275 Current
Rated G
Frequency [kV] 250-330-250(1min)
P8Applicable Standards JEC / IEC Switchi
P17
P11
Rated Voltage [kV]
P7 24 36 40.5 72 84
Rated V
Rated Lightning Impulse [kV] 125 170 185 350 400 Rated V
Withstand GSR GSM / GSP GSPF Rated C
P8Voltage Rated C
Power Frequency [kV] 50 70 95 140 160 Rated B
Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 P17
4
Rated S
AC Electrification Systems
Method of Operation 630 / 1250
Hydraulic / 1250
Motor Spring/ Motor Spring Rated
Rated Voltage
Rated Current [kV]
[A] 24 200036 40.5 800 / 1250
72 84
2000 Withsta
Applica
Rated V
Tank Dead Tank Live Tank
Rated Lightning
Rated Short Time Impulse [kV] 125
Withstand 170 185 350 400 Voltage
AC Traction Transformer
25 / 31.5 Rated C
Current [kA]Lighting
Withstand
P11 P15 Rated 900 / 1050 350 / 400 / 750 650
4-1
Voltage Impulse
Power[kV]
Frequency [kV] 50 70 95 140 160 Rated B
Withstand
Applicable Standard JEC / IEC / GB Rated S
Voltage Power 200-265-200(1min)/
630 / 1250 / / 160
1250 / Rated S
Rated Current [A] 140 / 325 275
800 / 1250 Current
Frequency [kV] 250-330-250(1min)2000 2000 Applica
P17
Toshiba provides a highly-reliable and modernized AC electrification system which consists of elements Applicable Standards JEC / IEC Switchi
AC feeding power for rolling stock is single-phase power. The ACRated Short substation
feeding Time Withstand should therefore convert 25 / the
31.5 commercial
Current [kA]
such as large capacity of traction transformers, single phase circuit breakers, surge arrestors, and AC 3-phase into AC single-phase. However in this case, it will cause three phase voltage unbalance at the primary side.The Scott-
Applicable Standard JEC / IEC / GB
Power Source
connection and the Roof-delta connection transformer below are used for the AC traction transformer which can reduce the MV Sw
changeover switches. Our products are designed with thesubstation
substation advance technology based on our long history
3-phase voltage unbalance induced in the primary side. P17
of development. It contributes to a safe, stable and cost-minimized system operation for a long term. P8
12-Puls
P17
Sectioning Post Transformer Rated Voltage [kV] 24 36 40.5 72 84
Ratings
P10
Rated Lightning Impulse [kV] 125 170 185 350 400
MV SwiV
Rated
DC Swi
VS-A VS-B Withstand Rated C
Application Power Frequency [kV] Feeding50System70 for High Auxilia
Voltage 95Speed140Railway160 Rated B
IGBT Supply
12-Puls
Rated Voltage [kV] 220 / 25x 2 ; 161 / 60x 2 ; 132 / 27.5x 2
Features Toshiba can supply various types of transformers and propose the most suitable type of Regenerative
Inverter
Escalator
Rated CurrentLighting
[A]
630 / 1250 / 1250 /
800 / 1250
Rated S
transformer according to customer specification such as voltage, capacity, loss, installation Cooling Type ONAN / ONAF2000/ OFAF 2000 Applica
P10 DC Swi
condition, etc. Traction Substation
Rated
Rated Power
Short
Passenger
[MVA]
Time
Station Withstand
Facility
84 / 60
25 / 31.5
Current
Overload [kA] 200% 5mins Auxiliar
Application Feeding System for High Speed Railway P13
The changeover switches are used for the phase break point of high speed railway system. Applicable
Connection
Rated Standard
Voltage [kV] Scott
220 JEC2/ ;IEC
/ 25x 2 ; 161 / 60x 132/ GB
/ 27.5x 2
Supply
Our product is designed for long time operation under the harsh conditions of high voltages Applicable
Cooling Standard
Type JEC / IEC
ONAN / ONAF / OFAF
P17
and repeating surges. Rated Power [MVA] 84 / 60 Protect
The control and relay panels supplied by Toshiba are designed with the advance digital Overload 200% 5mins
P13
Decelerating / Regeneration by Brake Accelerating
Connection / Powering Scott
technologies. They integrate all required functions such as protection, control and monitoring by P10 MV Swi
the intelligent digital relays, PLCs and the LAN connection network. Applicable Standard JEC / IEC
Scott Connection Transformer
Example of Roof-delta Connection Transformer Protect
12-Puls
Utility Feeding System for High Speed Railway
P9 Ratings
Rated Voltage [kV]
P10
P10 220kV / 60kV2
DC Swi
TOSHIBA's POWER SUPPLY SYSTEMS for AC Feeding Substation Cooling Type ONAN
Auxiliar
Application
Example of Roof-delta
Rated Power [MVA] Feeding
Connection
60 System for High Speed Railway
Transformer P10
Supply
Rated
Overload
Utility Voltage [kV] 220
300% / 25x
Feeding 2min2 ; 161 for
System / 60x 2 ; 132
High / 27.5x
Speed 2
Railway
Rated V
Cooling
Connection
Rated Type [kV]
Voltage ONAN // 60kV2
Roof-delta
220kV ONAF / OFAF
P13 Rated Power
Applicable
Cooling Type [MVA]
Standard 84
JEC/ /60
ONAN IEC
Rated
Withsta
Overload
Rated Power [MVA] 200% 5mins
60 Voltage
P10
P13
Connection Scott 2min (Line to
Overload 300%
TO POWER COMPANY 3 phase NETWORK Earth)V
Rated
Applicable Standard
Connection JEC / IEC
Roof-delta
P10 Rated C
Rated
Applicable Standard JEC / IEC Protect
Withsta
Power Company 161kV 3 Rated Voltage [kV] 55 / 27.5 Rated S
Voltage
Curren
Type ONAN (Line to
27S1,27G1 27S2,27G2 Traction Transformer P10 Applica
Self Capacity [MVA] 4 / 5 / 7.5 / 10 Earth)
(Scott Connection) Rated
Roof-delta Connection Transformer P10
Power Line Capacity [MVA] Rated C
51S1,51G1 51S2,51G2 Example of Roof-delta 8 / 10 Transformer
Connection / 15 / 20
Overload
Rated Voltage [kV] 300%
55 2min
/ 27.5 Rated S
Utility Feeding System for High Speed Railway Current
Solid Insulated Type
Short Voltage
Circuit Intensity Can withstand thermally and mechanically
ONAN
Rated [kV] 220kV
for 25 /or60kV2
Auto-transformer
Switchgear 35 times of the rated current Applica
87T1,51T1,50GT1 87T2,51T2,50GT2 Rated Type Self Capacity [MVA] 4 / 5 / 7.5 / 10
4-2
51GT1 51GT2 Cooling
Applicable Standard ONAN
JEC / IEC
Power Line Capacity [MVA] 8 / 10 / 15 / 20
SF6 -Gas Insulated Rated Power [MVA] 60 P10
Switchgear (GIS) Overload
Overload 300%2min
300% 2min
Mtr1 Mtr2
Can withstand thermally and mechanically Rated V
Short
The Auto-transformer is used for the AT Feeding System (25kV 2) Circuit
Connection
which Intensitycatenary Roof-delta
reduces voltage drops
51B1M 51B1T 51B2M 51B2T
for 25 or 35 times and
of theelectro-magnetic
rated current Rated
Applicablethe
interference. It should be designed with low impedance and to withstand Standard JEC /current.
high short circuit IEC Withsta
50OT1T 50OT1M 50OT2T 50OT2T Applicable Standard JEC / IEC
Voltage
OT1 OT2
(Line to
51OT1 51OT2T Earth)
Ratings
P10 Rated C
Rated Voltage [kV] 55 / 27.5 Rated S
Current
Type ONAN
27.5kV VWA-Type Applica
21F41,50F41 21F11,50F11 21F13,50F13 21F12,50F12 21F14,50F14
Vacuum Switch Rated Self Capacity [MVA] 4 / 5 / 7.5 / 10
Power Line Capacity [MVA] 8 / 10 / 15 / 20
Overload 300% 2min
AT41 AT11 AT13 AT12 AT14
27F41M 27F11 27F13 27F12 27F14
Short Circuit Intensity Can withstand thermally and mechanically
for 25 or 35 times of the rated current
27F41W VS-A VS-B VS-A VS-B
Applicable Standard JEC / IEC
5
VS (Vacuum Switch)
Frequently Changeover
Capability
(over 200,000 times)
Control & Relay
Panel Overview
Auto-transformer
9 10
P11
P14
72.5 ~ 252
25 ~ 63
Feeding Circuit Breaker / Switchgear
Rated Voltage [kV]
Rated Bus Current [A]
36 / 72
1200 Cooling and Insulating Method Gas Mineral Oil
Feeding Circuit Breaker / Switchgear
Liquid Silicone Vegetable Oil Epoxy Resin
] 325 ~ 1050
140 ~ 460 4-3 (Solid Insulated Switchgear)
Rated Breaking Current [kA]
1700
Rated Voltage [V] DC 750 , 1500
170 185 350 400 Applicable Standards
Rated Current [A] 3000 , 4000
JEC / IEC P6 Lifetime
Switching
Mechanical
VCB 200,000 times
Ratings (C-GIS)
P11
1,000kWcontinuous rating
Electrical 100,000Inverter
Regenerating times mode P14
70 95 140 160 Rated Breaking Capacity [kA] 50 (at 310 A / sec), 100 (at 1010 A / sec)
6 6 Capacity
Rated Voltage [kV] 72.5 ~ 252
3,000kW1minute or 4,500kW-30seconds
Rated Voltage [kV] 36 / 72 Features Compact Design
250 / 1250 / Rated Short Time Current [kA] 50-1sec , 100-1sec Powering Converter mode 1,000kWcontinuous rating only
0 2000
800 / 1250 Rated Interrupting Current [kA] 25 ~ 63
CT
Rated Bus Current [A] 1200 Cooling and
Outdoor Compatibility Gas
Insulating Method Mineral Oi
Applicable Standard JIS (To be developed for IEC) Rated Lightning Impulse Withstand
1,500VDC Voltage [kV] 325 ~ 1050 Rated Breaking Current [kA] 16 / 25
P8 Rated Power A
25 / 31.5 RatedRated
P17 Input Voltage OutputVoltage
Power Frequency Withstand control [kV]
mode (Make 140 a selection
~ 460 for your operation ) P15 Lightning Impulse [kV] 200 / 350 Safe Operation
Primary
-1) Load control: To 6 or 8 output regulation Rated Withstand Voltage
Rated Gas Pressure 0.7(GCB) / 0.7(GIS) Power Frequency [kV] 70 / 140 Rated Voltage
JEC / IEC / GB Rated Voltage [kV] 24 36 40.5 15
00
72 84
Rated Voltage [V] Standards
-2) Constant voltage control
DC 750 , 1500 Low Maintenance
Secondary Appli
Applicable JEC / IEC Rated Gas Pressure [MPaG] 0.05 (at 20C) Applicable Standard
Rated Lightning Impulse [kV] 125 170 185 350 400 RatedCurrent
Output[A]Voltage 1,200VAC 1,000kWcontinuous rating
Rated 3000 , 4000
P17 Withstand 600 Regenerating Inverter mode
Voltage Power Frequency [kV] 50 70 95 140 160 Rated Capacity [kA] 50 1Series
(at 310*6A2Parallel * 6Arm
/ sec), 100 * 2Bridge
(at 1010 6A / sec) Capacity 3,000kW1minute or 4,500kW-30seconds
Main Breaking
Circuit Configuration
Specifications Applicable equipments Double bridge parallel configuration by Transformer P11 Powering Converter mode 1,000kWcontinuous ratingP14
only
630 / 1250 / 1250 / Rated Short Time Current [kA] 50-1sec , 100-1sec
Rated Current [A] SIS 800 / 1250 Device
P7 IGBT (3,300V-1,200A)
27.5kV
MV Switchgear Unit 7.2 / 24 / 36kV 2000
Air Insulated 2000
type or Cross Section Applicable Standard Side
JISView
(To be developed for/ IEC)
MG1200FXF1US53(P)
Solid Insulated type Device Cooling System Heat-pipe in pure water (natural cooling type) Rated Voltage [kV] 361,500VDC Cooling Method Vertical heat-pipe self cooling
Rated Short Time Withstand GSR GSM / GSP GSPF Output control mode (Make a selection for your operation )
25 / 31.5 Rated Current
Rated Input Voltage
[A] 1200 Rated Power
Current [kA] TR : Epoxy Resin Molded Dry Inverter-2,700W * 2,200D * 2,900H -1) Load control: To 6 or 8 output regulation ~ 6 MW
HSCB or HSVCB
Method of Operation
P17 Tank
Hydraulic
Dead Tank
Motor Spring Motor Spring
DC Reacrtor-2,800W * 2,000D * 2,500H
Live Tank 4-5 Rated
Withstand
Impulse [kV]
Rated Output Voltage
Voltage Power
Between Main Circuit Terminals 250
1,200VAC
Between Main Circuit and Earth 70 1min.
1Series * 2Parallel * 6Arm * 2Bridge
Applicable Standard JEC / IEC
se
s
21F 50F Features Colored LCD Touch Screen
P11
Power supply ranges 100 - 250Vdc
Sectioning Post Transformer for Human Interface
IEC60870-5-103 / Inputs / outputs Digital input 18*
P14
VS-A VS-B
Earth
0 etc.
72.5 ~ 252 Rated Voltage [kV]
Digital output 18*
36 / 72 Redundant System
25 ~ 63 Rated Bus Current [A] 1200 IGBT
panese / Portuguese
] 325 ~ 1050 Rated Breaking Current [kA]
Analog input 4*
16 / 25
Cooling and Insulating Method Gas Mineral Oil Liquid Silicone Vegetable Oil Epoxy Resin Regenerative
Inverter
Self-monitoring
Escalator and Self-
Lighting
Rated Power Applicable for up to 6MW Rectier
140 ~ 460
Communication ModbusImpulse
Lightning / IEC61850
[kV]/ IEC60870-5-103
200 / 350 / Primary 77kV 35kV
diagnosis Function
protocol & Interface
Rated Withstand Voltage Web browser DNP3.0 etc. Traction Substation Passenger Station Facility
0.7(GCB) / 0.7(GIS) Power Frequency [kV] 70 / 140 Rated Voltage
tection Changeover Switch[MPaG] Relay W205D187.8H255.9
Changeover0.05
Switch in Cubicle
Secondary
Application of Changeover Switch
Applicable for DC600V / 750V / 1500V / 3000V Alarms and Commands
JEC / IEC Rated Gas Pressure
Dimensions (at 20C)
e of rise protection MIMIC W149D 23.8H278.5 Applicable Standard JEC / IEC Logs Function
t protection (4 stages) LCD language English / Chinese / Japanese / Portuguese
erload protection (3 stages) Ratings
P11
Measuring Data (voltage,
*Maximum value P14
e protection (2 stages) current, power, power factor
Rated Voltage [kV] 36 FeaturesCooling Method
High Voltage Withstand Decelerating / Regeneration by Brake Accelerating / Powering
ge protection (2 stages) I Current surge protection Vertical heat-pipe self cooling etc.)
GSM / GSP
osing function
GSPF Rated Current [A] 1200
di / dt Current rate of rise protection
Rated PowerCapability ~ 6 MW
72 / 84 / 168 145
Lightning Between
50 Main Circuitprotection
Overcurrent and Earth (4
200
stages) In order to withstand
Rated Voltage the excessive
DC 600V voltage
/ 750V / 1500V / 3000V Connection with Remote
Motor Spring Motor Spring Protection Function
Rated at the phase break point, two vacuum
Impulse [kV]
Control Center (SCADA)
1700
Between
49 Main Circuit
Thermal Terminals
overload 250(2 stages)
protection Applicable Standard JEC / IEC
n* Withstand interrupters are provided in series for the
Tank Live Tank
SWGR, CB) Voltage Power Between
59 Main Circuitprotection
Overvoltage and Earth (3
70stages)
1min. P9
switch.
Frequency [kV] Between Main Circuit Terminals
n 350 / 400 / 750
fuction 650 27 Undervoltage protection100 10min.
(3 stages)
Rated Short Time Withstand Multi-shots
Long Life Operation
edance 12.5 2sec. auto-reclosing function 21F 50F
140 / 160 / 325 275 Current [kA] Aiming for long life operation, a simple
Line test Function
Controll Function electro-magnetic operation mechanism is
n JEC / IEC Switching Lifetime
Mechanical
Interbreaking200,000 times
Function** used. Control/Relay Panel P13
Electrical
Controlling100,000 times
Function(SWGR, CB)
ng 15
00
Metering Function I, V, +Wh, -Wh, Impedance
TO POWER COMPANY 3 phase NETWORK
CB state condition
600
Trip circuit supervision Substation Monitoring System
Power Company 161kV 3
P15
P17 Trip counter monitoring
Monitoring Function This Control/Relay Panel for AC Receiving Substations is installed with G2 Relay and monitoring system that utilizes DMS (Digital
36 40.5 72 84 CB operate time
4-7
170 185 350 400 I alarm
Rated Current [A] 3000 , 4000 1,000kWcontinuous rating
waveform collection, transmission functions and a user-friendly LCD interface.
Self supervision 51S1,51G1 Regenerating Inverter mode
51S2,51G2
n 70
the substations
95 are required.
140 160 Rated Breaking Capacity [kA] 50 (at 3106A / sec), 100 (at 1010 6A / sec) Capacity 3,000kW1minute or 4,500kW-30seconds
System monitoring results such as daily and monthly energy status reports and fault history can be displayed through its
Event records Powering Converter mode 1,000kWcontinuous rating only LCD.
250 / 1250 / Rated Short Time Current [kA] 50-1sec , 100-1sec large
800 / 1250 Record Function Fault records relay provides mainly 2
0 2000 Toshibas AC feeding
Applicable Standard protection
JIS (To be developed for IEC) 21F 87T1,51T1,50GT1 50F 87T2,51T2,50GT2 21F 50F
Disturbancevent records Load current with 51GT1 51GT2 1,500VDC Load current with
25 / 31.5
protection functions called Distance Relay (21F), and Thyristor Controlled
Rated InputCarsVoltage Output control mode (Make a selection for your operation ) Thyristor Controlled Cars
Instantaneous Overcurrent Relay
*Communication line (50F).
betweenIfthe
failure is detected,
substation is requieredit -1) Load control: To 6 or 8 output regulation
m)
m)
Angle
Angle
Mtr1 Mtr2
10 nt
10 nt
-2) Constant voltage control
ce rre
ce rre
JEC / IEC / GB
oh
oh
will isolate failure circuit quickly. X X
tan Cu
tan Cu
GPS
g Line
g Line
sis ult
sis ult
X1 Antennae X1
Rated
51B1MOutput Voltage
51B1T 51B2M 1,200VAC
51B2T
Re Fa
Re Fa
Zone1 Zone1
P17
ult um
ult um
Feedin
Feedin
50OT1T 50OT1M 50OT2T 50OT2T
Detected
1Series Rise Current(Ifv)
* 2Parallel * 6Arm * 2Bridge Detected Rise Current
(Fa inim
(Fa inim
Main
When aCircuit Configuration Remote Terminal Unit
OT1 X2 train
Double bridge parallelOT2
on 50F
configuration by Transformer
X2 When a train on 50F
Specifications Applicable equipments
M
M
Zone2 comes, Ifv=(If 2+IL 22If Zone2 comes, Ifv=(If 2+IL 22If
impedance ILcoslf~IL) impedance ILcoslf~IL)
Air Insulated type or
51OT1
Device
zone changes IGBT (3,300V-1,200A) 51OT2T
/ MG1200FXF1US53(P) zone changes
If
If
urrent Control/Status Signal Curren
MV Switchgear Unit 7.2 / 24 / 36kV um Load
C
um Load
Ratings
P13
Solid Insulated type Device Cooling System IL
Maxim in pure water (natural cooling type)
Heat-pipe Control Display Current Input
DMS SW-HUB PC
IL
Maxim
Power Source
Features For better environmental friendliness, a liquid silicone transformer or vegetable oil transformer can
be used for the rectifier transformer.
Heat pipe Rectifier has a very high thermal efficiency and can be installed outdoors. Gas Insulated Transformer Liquid Silicone Transformer Epoxy Resin Molded Dry Transformer
Transformer High Speed Vacuum Circuit Breaker (HSVCB) has high reliability, safety and can reduce
maintenance
Regenerative Inverter is a good energy saving solution for the efficient use of regenerative braking Features Nonflammable SF6 Gas Insulated
IGBT
Regenerative power from Escalator
rolling stocks.
Lighting Transformer is suitable for indoor use.
Inverter
SCiB Traction Energy Storage System is an energy saving solution which is not only useful Noncombustible liquid silicone
Traction Substationfor storage of Passenger Station Facility
regenerative energy but also for promoting power peak cut, feeder voltage transformer and vegetable
compensation and emergency power supply. oil transformer are friendly to
environment.
Package Type Substation saves space and construction works.
Vegetable Oil Transformer
P6 P11
P14
TOSHIBA's POWER SUPPLY SYSTEMS
Decelerating / Regeneration by Brake
Rated Voltage [kV]
for DC Feeding Substation Rated Voltage [kV]
Accelerating / Powering
72.5 ~ 252 36 / 72 Ratings
Rated Interrupting Current [kA] 25 ~ 63 Rated Bus Current [A] 1200 Cooling and Insulating Method Gas Mineral Oil Liquid Silicone Vegetable Oil Epoxy Resin
Rated Lightning Impulse Withstand Voltage [kV] 325 ~ 1050 Rated Breaking Current [kA] 16 / 25 Rated Power Applicable for up to 6MW Rectier
Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 Lightning Impulse [kV] 200 / 350
Rated Withstand Voltage Primary 77kV 35kV
Rated Gas Pressure 0.7(GCB) / 0.7(GIS) Power Frequency [kV] 70 / 140 Rated Voltage
Secondary Applicable for DC600V / 750V / 1500V / 3000V
Applicable Standards JEC / IEC Rated Gas Pressure [MPaG] 0.05 (at 20C) Applicable Standard JEC / IEC
Regenerative Inverter Heat-pipe cooled Silicon Rectifier SF6 -Gas Insulated Switchgear(GIS) P11 P14
P6 P11
P7
P13 Power Transformer SF6 -Gas Insulated P14
Traction Rectifier
Rated(Oil
Voltage [kV]
immersed) 36
Transformer Cooling Method Vertical heat-pipe self cooling
Rated Voltage [kV] 72.5 ~ 252 Rated Voltage [kV] 36 / 72
5-2
GSR GSM / GSP GSPF Rated Current [A] 1200
Rated Interrupting Current [kA] 25 ~ 63 Rated Bus Current [A] 1200 Rated Power ~ 6 MW
Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 Between Main Circuit and Earth 200 Cooling and Insulating Method Gas Mineral Oil Liquid Silicone Vegetable Oil Epoxy Resin
TO POWER
Rated Lightning Impulse COMPANY 3 phase
Withstand Voltage [kV]NETWORK 325 ~ 1050 Rated Breaking Lightning
Current [kA] 16 / 25 Rated Voltage DC 600V / 750V / 1500V / 3000V
Method of Operation Hydraulic Motor Spring Motor Spring Rated Impulse [kV] Between Main Circuit Terminals 250 Rated Power Applicable for up to 6MW Rectier
Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 Withstand Lightning Impulse [kV] 200 / 350 Applicable Standard JEC / IEC
Tank Dead Tank Live Tank Rated Withstand Voltage Primary 77kV 35kV
Rated Gas Pressure 0.7(GCB) / 0.7(GIS) Voltage Power Between Main Circuit and Earth 70 1min.
Power Frequency [kV] 70 / 140 Toshiba has a long history of manufacturing rectifiers
Rated Voltage (diode, thyristor, and IGBT type). Our current Rectifier has a heat pipe cooling
Lighting Frequency [kV] Between Main Circuit Terminals 100 10min. Secondary Applicable for DC600V / 750V / 1500V / 3000V
Rated
Applicable Standards
Impulse [kV]
900 / 1050 350 / 400 / 750
JEC / IEC 650 Rated Gas Pressure [MPaG] 0.05 (at 20C) system using high purity water. It is suitable for repeated overload current and has large cooling capacity and it can be installed outdoor.
Withstand Applicable Standard JEC / IEC
Rated Short Time Withstand 12.5 2sec.
Voltage Power 200-265-200(1min)/
140 / 160 / 325 275 Current [kA] Traction Energy Storage System (TESS)
Frequency [kV] 250-330-250(1min)
Applicable Standards JEC / IEC P11
Switching Lifetime
Mechanical 200,000 times Ratings
P14
P7 Electrical 100,000 times
Rated Voltage [kV] 36 Cooling Method Vertical heat-pipe self cooling
GSR GSM / GSP GSPF
P14~
Rated Current [A] 1200 Rated Power 6 MW
Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 Lightning Between Main Circuit and Earth 200 Rated Voltage DC 600V / 750V / 1500V / 3000V
P8Method of Operation Hydraulic Motor Spring Motor Spring Rated Impulse [kV] Between Main Circuit Terminals 250
Withstand Applicable Standard JEC / IEC
Tank Dead Tank Live Tank P17 P15
Voltage Cubicle type SFBetween
Power 6 -Gas Insulated
Main Circuit and Earth 70 1min.
Rated Voltage [kV]
Lighting 24 36 40.5 72 84 Switchgear(C-GIS)
Frequency [kV] Between Main Circuit Terminals 100 10min.
Rated 900 / 1050 350 / 400 / 750 650 Rated Voltage [V] DC 750 , 1500
Rated Impulse [kV]
Withstand Lightning Impulse [kV] 125 170 185 350 400 Heat 1,000kWcontinuous rating
Current
Rated Short [A] Withstand
Time 3000, 2sec.
4000
Withstand Power
Voltage 200-265-200(1min)/
140
12.5 Theory of Heat Pipe Cooling
Regenerating Inverter mode Radiation
70 / 16095
/ 325 140 275160
Condensation
Power Frequency
Voltage Frequency [kV] 50 Current [kA]
Rated Breaking Capacity [kA] 50 (at 3106A / sec), 100 (at 1010 6A / sec) Capacity 3,000kW1minute or 4,500kW-30seconds
[kV] 250-330-250(1min) Fin
Applicable Standards JEC/ / IEC
630 / 1250 1250 / Rated Short
Switching Time Current [kA] Mechanical
Lifetime
200,000 times
50-1sec , 100-1sec Powering Converter mode 1,000kWcontinuous rating only
Rated Current [A] 800 / 1250 Heat radiation
2000 2000 Applicable Standard Electrical
JIS (To be100,000 times
developed for IEC) => condensation 1,500VDC
Condensation
Rated Short Time Withstand Output control mode (Make a selection for your operation )
25 / 31.5 Rated Input Voltage Maintenance Ene
Current [kA] Heat convection by -1) Load control: To 6 or 8 output regulation PC Manage
-2) Constant voltage control
Vapor Flow
Applicable Standard JEC / IEC / GB Solid Insulated 24kV Metal-clad pressure difference
P8
Liquid Flow
Liquid Flow
Switchgear(SIS) Switchgear P15
P17 Rated Output Voltage 1,200VAC
P17 Pressure rise by
Rated Voltage [kV] 24 36 40.5 72 84 evaporation 1Series * 2Parallel * 6Arm * 2Bridge
Rated Voltage [V] DC 750 , 1500 Main Circuit Configuration
Specifications Applicable equipments Double bridge parallel configuration by Transformer
Evaporate
Rated Lightning Impulse [kV] 125 170 185 350 400 1,000kWcontinuous rating
Rated Current [A] 3000 , 4000 Device IGBT (3,300V-1,200A) / MG1200FXF1US53(P) System LAN-A(HUB)
Withstand MV Switchgear Unit Air Insulated type or Regenerating Inverter mode
7.2 / 24 / 36kV Capacity Coolant evaporation by
Voltage Power Frequency [kV] 50 70 95 140 160 Rated Breaking Capacity [kA] 50 (at 3106A / sec),
Solid100 (at 1010
Insulated 6A / sec)
type Device Cooling System
heat Heat-pipe in pure water (natural cooling3,000kW1minute
type) or 4,500kW-30seconds
System LAN-B(HUB)
Rated Short Time Current [kA] 50-1sec , 100-1sec Powering Converter mode 1,000kWcontinuous rating only
Evaporation
630 / 1250 / 1250 / TR : Epoxy Resin Molded Dry Inverter-2,700W * 2,200D * 2,900H
Rated Current [A] 800 / 1250 High Purity
2000 2000 Applicable Standard JIS (To be developed/ for IEC)Silicone Dimension Coolant and element
Heat
12-Pulse Rectifier Unit Up to 2,000kW Liquid Control Panel
1,500VDC of Inverter-800W * 1,000D * 2,300H
Water
SR : Heat-pipe Self-cooling heat exchange Base Clock Main S
Rated Short Time Withstand Output control mode*(Make
DC Reacrtor-2,800W 2,000Da *selection
2,500H for your operation )
25 / 31.5 Rated Input Voltage
Current [kA] -1) Load control: To 6 or 8 output regulation
P10 DC Switchgear Unit DC 600V, DC1500V HSCB or HSVCB
Applicable -2) Constant voltage control
MV/LV Metal-clad SF6Standard
-Gas Insulated JEC / IEC / GB
Liquid Silicone Transformer DC Switchgear DC Switchgear (HSVCB)
Switchgear Application
Transformer Feeding System for High Speed Railway Auxiliary Power DC 110V,
Supply Unit AC 105V / 210V
Lead Storage Battery Rated Output Voltage 1,200VAC Principle of Heat-pipe Self Cooling Heat-pipe Rectifier
Rated Voltage [kV] 220 / 25x 2 ; 161 / 60x 2 ; 132 / 27.5x 2 P17
15 P7
Main Circuit Configuration
1Series * 2Parallel * 6Arm * 2Bridge 16 PS LAN-A(HUB)
Cooling Type ONAN / ONAF / OFAF Specifications Applicable equipments Double bridge parallel configuration by Transformer
Rated Power [MVA] 84 / 60 Rated Voltage [kV]
Device 36
IGBT (3,300V-1,200A) / MG1200FXF1US53(P) 40.5 72 84 PS LAN-B(HUB)
MV Switchgear Unit 7.2 / 24 / 36kV Air Insulated type or
Overload 200% 5mins Solid Insulated type Device Cooling System Lightning Impulse
Heat-pipe [kV] water (natural
in pure 170cooling type) 185 350 400
P13 Rated Withstand Voltage
Connection Scott PowerInverter-2,700W
Frequency [kV]* 2,200D * 2,900H70 95 140 160
TR : Epoxy Resin Molded Dry
Applicable Standard JEC / IEC 12-Pulse Rectifier Unit Up21F
to 2,000kW Distance Protection
/ Liquid Silicone Rated Current [A]
Dimension 630, 1250,
Control Panel of Inverter-800W 2500* 2,300H 630, 1250, 2000
* 1,000D 800, 1250 800, 1250
PC Metering
Management PC Function I, V, W, +Wh, -Wh, Impedance (Monochrome) (Color)
Record Function
Event records
Fault records 5-4 Protection Relay (GRX-200 Series)
Disturbancevent records
PS LAN-A(HUB)
Based on a strong experience and know-how on the supply of highly quality DC High Speed Circuit Breakers and
*Communication lineDC Switchgears
between the substation is requiered
PS LAN-B(HUB)
since theDS1970s, Toshiba
Negative Incoming developed
Feeder the HS5 DC
with
Feeder Panel Variations
DS Switchgear
with bypasswith
DS our own
with DS DC Protection
and bypass Bypass HSCB Relay which satisfies current global
Ratings
P18
Bypass Bus
GRX200 GRX200
RTUP13
Bypass Bus
GRX200
20
DC
SAR GRX200
DC
SAR GRX200
DC Protection
79
Relay
Automatic Reclose
di / dt Current rate of rise protection
Rated Withstand Voltage 50 Over current protection (4 stages)
Power Frequency [kV] 9.2 User-friendly
50F Instantaneous Overcurrent Protection 49 Thermal overload protection (3 stages)
Applicable Standard JIS / IEC Protection
Human Interface
Multi-shots auto-reclosing function 32 Reverse Overcurrent protection (4 stages)
P16 Control Function Inter breaking function * 64 Grounding overvoltage protection (2 stages) GRX-200 Relay
Controlling function (SWGR, CB) 59 Over voltage protection (2 stages)
Typical Configuration Metering Function I, V, W, +Wh, Impedance 27 Under voltage protection (2 stages)
Event records Multi-shots auto-reclosing function
Feeder Panel Variations Monitoring Function FaultToshibas
records DC Switchgear Line test function
Negative DS Incoming Feeder with DS with bypass DS with DS and bypass Bypass HSCB
Main Bus Main Bus Main Bus Main Bus Main Bus
can berecords
Disturbance configured into Control Inter breaking function *
various
CB and common panel
DS status
DS DS Line
test
HSCB Line
test
HSCB Line
test
HSCB Line
test
HSCB Line
test
HSCB
configurations such as
Controlling function (SWGR, CB) Features Compact Design
Device Device Device Device Device CB and DS response monitoring Section compensation function
HSCB
R R R R
Record Function R
Trip feeder panels with DS,
circuit supervision Colored LCD Touch Screen for
Metering I, V, W, +Wh, -Wh, Impedance
Trip bypass DS, DS and
counter monitoring bypassby breaking level
categorized Human Interface
GRX200
GRX200
GRX200 GRX200 GRX200 GRX200 GRX200 Event records
Bypass Bus Bypass Bus
GRX200
and bypass HSCB.
Self-supervision Record Fault records Flexible Installation (The touch panel
GRX200 DS
DS DS DS
M M M M
Disturbance records and the main unit are separate.)
Bypass Bus
CB and DS status
U> 64
Main Bus
DS DS DS DS
Wide Range of Communication
CB and DS response monitoring
Protocol Supported
DC DC DC DC
N
SAR GRX200 SAR GRX200 SAR GRX200 SAR GRX200
Monitoring Trip circuit supervision
Trip counter monitoring categorized by breaking level Various Protection Elements
Self-supervision
Front View Side View of Feeder Panel
* Communication lines between the substations are required.
Negative Incoming Feeder1 Feeder2 Feeder3 Feeder4 Standby
4400
Feeder Relay Mimic
Back View
This protection relay can generate, monitor and record wave forms during
failure occurences. Through this, detailed fault analysis can be performed.
LINE TEST DEVICE LINE TEST DEVICE LINE TEST DEVICE LINE TEST DEVICE LINE TEST DEVICE
*1 *2 *1 *2 *1 *2 *1 *2 *1 *2
89FZ1
DS M
89FZ1 89FZ2 89FZ3 89FZ4 HCT
4000A DS DS DS DS
M M M M
4000A 4000A 4000A 4000A HCT
SR(N) DCVT
*1 *1 *1 *1 *1
DS-1 DS-1 DS-1 DS-1
Condensation
Fin
Heat radiation
=> condensation
Liquid Crystal Displays
Condensation
Maintenance Energy Printer Printer
Heat convection by PC Management PC (Monochrome) (Color)
Vapor Flow
pressure difference
Liquid Flow
Liquid Flow
RGB Matrix Switch
Pressure rise by
evaporation Other Video Sources
Evaporate
P6 P11
System LAN-A(HUB)
P14
High Speed Vacuum Circuit Breaker (HSVCB) Traction Energy Storage System with SCiB
Coolant evaporation by
Rated Voltage [kV] heat 72.5 ~ 252 Rated Voltage [kV] 36 / 72
5-5 5-7
System LAN-B(HUB)
Evaporation
Rated Interrupting Current [kA] 25 ~High
63 Purity Rated Bus Current [A] 1200 Cooling and Insulating Method Gas
Visual Signal
Mineral Oil Liquid Silicone Vegetable Oil Epoxy Resin
Coolant and element
Heat
Rated Lightning Impulse Withstand Voltage [kV] 325 ~Water
1050 Rated Breaking Current [kA] 16 / 25 Rated
Total Monitoring PCs Operator Console 1 Operator Console 2
Applicable for up to 6MW Rectier
Operator Console 3
heat exchange Base Clock Main Server A Power
Main Server B Main Server C
Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 Lightning Impulse [kV] 200 / 350
Toshiba has developed the innovative HSVCB. The HSVCB consists of theWithstand
Rated VCB, Capacitor,
Voltage Control and Protection units. The aerial arc Primary 77kV 35kV
Rated Gas Pressure 0.7(GCB) / 0.7(GIS) Power Frequency [kV] 70 / 140
chute and the contactor for the conventional HSCB are not used for the HSVCB. It contributes to safe operation and easy maintenance.
Rated Voltage System
Secondary Overview Applicable for DC600V / 750V / 1500V / 3000V
Applicable Standards JEC / IEC Rated Gas Pressure [MPaG] 0.05 (at 20C) Battery(SCiB)
Applicable Standard JEC / IEC
Toshiba developed Traction Energy Storage System (TESS)
Capacitor Unit
PS LAN-A(HUB)
with SCiB, an energy saving solution with Toshibas own
P11 Features P14 battery technology of high quality. TESS efficiently charges
P7 PS LAN-B(HUB) Converter
Control and Protection Unit Rated Voltage [kV] 36
and discharges surplus regenerative energy to/from
Cooling Method Vertical heat-pipe self cooling
GSR GSM / GSP GSPF Rated Current [A] 1200
SCiB. TESS is installedMTU with Toshibas
MTU patented advance Back Up Console
Rated Power
Rated Voltage [kV] 240 / 300 72 / 84 / 168 145 Safe OperationBetween Main Circuit and Earth 200 ~ 6 MW
V-SOC (Voltage-State-of-Charge) control system which
Lightning Rated Voltage DC 600V / 750V / 1500V / 3000V
Method of Operation Hydraulic Motor Spring Motor Spring Rated No Impulse
arc occurs during current breaking due to VCB application.
[kV] Between Main Circuit Terminals 250 allows flexible control of charge-discharge
Power Supply System LAN characteristics RTU
Withstand Applicable Standard JEC / IEC
Tank Dead Tank Live Tank in accordance to the batterys State-of-Charge (SOC). This
Voltage Low Noise Between Main Circuit and Earth 70 1min.
Power
Lighting RTU allows
RTU significant increase in battery lifetime. This system
RTU is
Frequency [kV] Between Main Circuit Terminals 100 10min.
Rated 900 / 1050 350 / 400 / 750 650 VCB application allows low noise.
Impulse [kV] useful not only for energy saving, but for various purposes
Substations
Withstand
Voltage Power 200-265-200(1min)/
P17
VCB Unit Rated Short Time Withstand 12.5 2sec. such as regenerated energy absorption, peak cut, feeder
DC Breaker TESS
Frequency [kV] 250-330-250(1min)
140 / 160 / 325 275 Low Maintenance
Current [kA]
Mechanical voltage compensation and emergency power supply.
Applicable Standards JEC / IEC Maintenance is free from
Switching Lifetime aerial arc200,000 times
chute and the contactor.
Outline of HSVCB Electrical 100,000 times
External Interface
DC-BUS
Converter Battery Panel
Receiving
1800W2380D2300H 600W650D2100H8 panels
P16
Open Command
Detecting
P8 Overcurrent
Control and Ratings
P17 P15
HCT Protection Unit
P6Rated Voltage [kV] 24 36 40.5 (HSTC)
72 84 P11
Rated Voltage [V] DC 750 , 1500 P14
Rated Lightning Impulse [kV]
Sub 125 170 185 350 400 1,000kWcontinuous rating
Feeder Panel Variations
Rated Voltage [kV] 72.5 ~ 252 Turn on the Rated Voltage
Rated Current [kV]
[A] 3000 , 4000 36 / 72
Withstand Valve Negative DS Incoming Regenerating
Feeder Inverter
with DSmode with bypass DS with DS and bypass Bypass HSCB
PowerCurrent
Frequency Open
70 Both25 Thyristor Switch Capacity 3,000kW1minute or 4,500kW-30seconds
Voltage
Rated Interrupting [kA] [kV]
close 50 95~ 63 140 160 Rated Bus
Rated Breaking Capacity
Current [A] [kA] 50 (at 3106A / sec), 100 (at 1010
1200 6A / sec)
Ratings
Main Bus Main Bus Main Bus Main Bus Main Bus
Valves Cooling and Insulating Method Gas Mineral Oil Liquid Silicone Vegetable Oil Epoxy Resin
Rated Lightning Impulse Withstand Rated Breaking
Rated Short Time Current
Current [kA] 50-1sec , 100-1sec
[kA] 16 / 25 Powering Converter mode 1,000kWcontinuous rating only
Rated Current [A] openVoltage
630 [kV]
/ 1250 / 1250 325 ~ / 1050
800 / 1250 Rated Power
DS DS
test
Line HSCB Line
test
HSCB Line
test
HSCB
Applicable
Line
test for up to
HSCB
test 6MW Rectier
Line HSCB
2000 2000
Capacitor Charger
Rated Power Frequency Withstand Voltage [kV] 140 ~ 460 Applicable Standard JIS (To Impulse
Lightning be developed
[kV] for IEC)
200 / 350 Device Device Device Device Device
500kW~2000kW
Rated Withstand Voltage Primary 1,500VDC 77kV R Rated Power 35kV
/ 31.5 - / 0.7(GIS)
HSCB
R R R R
Rated Gas
Rated Short Time Withstand
Pressure Main 70 / 140 Rated Voltage Output control mode (Make a selection for your operation )
250.7(GCB) Power Frequency [kV] Rated Input Voltage Secondary Applicable for DC600V / 750VBattery / 1500VCapacity/ 3000V 200kWh~800kWh
Current [kA]
Applicable Standards
Valve
close JEC / IEC+ Rated Gas Pressure [MPaG] 0.05 (at 20C)
DC-1)Breaker
Load control: To 6 or 8 output Control regulation Panel 1500V(950V~2000V)
JEC / IEC Rated Voltage for Feeder side
GRX200
When control and protection unit detects the over current or receives open command 600W1700D2100H2 panels 500W600D2100H2 Bypass Bus panels Bypass Bus
open Rated Voltage for Battery side
GRX200 600V(500V~713V)
from external devices, the both valves trip and the thyristor switch of capacitor unit is GRX200
Rated Output Voltage 1,200VAC
DS
M M
DS
M
DS
M
DS
VCB Unit P17the current of capacitor unit is in the opposite direction of the load/fault
turned on. Since Load 1p.u.(1min.) 0.5p.u.(4min.) or 0.5p.u.
BypassPattern
Thyristor Capacitor P11 P14 1Series * 2Parallel * 6Arm * 2Bridge Bus
continuous
current, the zero-cross point of DC current can be achieved. Therefore, the DC load/fault Main
U> Circuit64 Configuration
P7 Switch Unit Specifications Applicable equipments Double bridge parallel
DS DS
configuration DS
by Transformer DS
current can be broken with high reliability and safety. Main Bus
Rated Voltage [kV] 36 Cooling
DC DC DC DC
Package-Type DC Substation
P10
Rated 900 / 1050 350 / 400 / 750 650 DC Switchgear Unit DC 600V, DC1500V HSCB or HSVCB
Impulse [kV]
5-6
Withstand Rated Short Time Withstand
Voltage
ApplicationPower 200-265-200(1min)/
Feeding System140 for/High Auxiliary[kA]
Power 12.5 2sec.
DC 110V,
160 /Speed
325 Railway275 Current Lead Storage Battery
Frequency [kV] 250-330-250(1min) Supply Unit AC 105V / 210V
Rated Voltage [kV] 220 / 25x 2 ; 161 / 60x 2 ; 132 / 27.5x 2 Mechanical 200,000 times
Applicable Standards JEC / IEC P7
Cooling Type ONAN / ONAF / OFAF Switching Lifetime
Toshiba has developed the compact Package-Type DC Electrical 100,000
Substation. It is suitable for small-capacity times and temporary
substations
Rated Power [MVA] 84 / 60
substations during rehabilitation work, and it reduces substation space.
Rated Voltage [kV] SCiB 36 40.5 72 84
Overload 200% 5mins Lightning Impulse [kV] 170 185 350 400
P13 Rated Withstand Voltage
Connection Scott SCiB Power
is a rechargeable
Frequency [kV]battery which
70uses Lithium Titanate
95 140 Attractive features 160
are realized
P8
Applicable Standard JECVIEW
FRONT / IEC 21F Distance Protection Rated Current [A] Oxide (LTO). Its features include
P15
safety,
630, 1250, 2500long life, rapid
630, 1250, 2000 800, 1250 by using Lithium
800,Titanate
1250
P17
51F Overcurrent Protection charging,
Rated Short Time Withstand high
Current [kA] power output performance,
25, 31.5 and good 25, 31.5 20, 25, 31.5 Oxide (LTO) 20,
in its
25,anode
31.5
Rated Voltage [kV] 24 36 40.5 72 84 Protection Function
Rated
Features
Rated Voltage [V] Compactness Voltage Protection
27FDC 750 , 1500 Applicable Standardscryogenic operation. JEC / IEC
Lightning Impulse [kV] 125 170 185 350 400 79 3000 , 4000
Automatic Reclose 1,000kWcontinuous rating
Rated Current [A]
Withstand Regenerating Inverter mode
P10
Voltage Power Frequency [kV] 50 70 95 140 160 Flexible
Rated Breaking Capacity [kA]
Layout
50 (at 310 A / sec), 100 (at 1010 A / sec)
6 6 Capacity 3,000kW1minute or 4,500kW-30seconds
Powering Converter mode 1,000kWcontinuous rating only * Results of cell level tests under certain conditions.
Example of Roof-delta 630 / 1250 / 1250 /
Connection Transformer Rated Short Time Current[kA]
Short Construction
50-1sec , 100-1sec Period Not a guaranteed performance.
Rated Current [A] 800 / 1250
2000 2000
Utility Feeding System for High Speed Railway
Applicable Standard JIS (To be developed for IEC)
System 1,500VDC
Design
Rated Short Time Withstand DC Output control mode (Make a selection for your operation )
Rated Voltage 25 / 31.5 Rated Input Voltage
Current [kA] [kV] 220kV / 60kV2 switchgear -1) Load control: To 6 or 8 output regulation
DC auxiliary In the introduction of TESS in a railway system,
-2) Constant voltage control P7
Cooling Type
Applicable Standard ONAN JEC / IEC / GB (Negative P12
Power it is important to do an accurate and reliable
Rated Power [MVA] 60 panel) P10
Overload 300% 2min
Ratings
P17
Rated
Rated Output [kV] simulation1,200VAC
VoltageVoltage of the traction power27.5 system during Rated Voltage [kV] 36 40.5 72 84
Rated Lightning Impulse [kV]
Rated Voltage [kV] 27.5 Rated Current [A] the design1Series
Main Circuit Configuration stage.* 2Parallel * 6Arm *1250
2Bridge 170 185 350 400
Connection Roof-delta Specifications Applicable equipments Double bridge parallel configuration by Transformer Withstand
Rated Lightning 200 (to earth and across open contacts) Lightning Impulse [kV] 250 Voltage Power Frequency [kV] 70 95 140 160
Applicable Standard JEC / IEC Withstand Impulse [kV] 220 (across isolating distance)type or Rated Withstand Voltage
Device IGBT (3,300V-1,200A) / MG1200FXF1US53(P)
MV Switchgear Unit 7.2 / 24 / 36kV Air Insulated ToshibaPower
has many experience
Frequency [kV] and
95 consultation
Voltage 630 / 630 / 800 / 800 /
Solid Insulated type Device Cooling System Heat-pipe in pure water (natural cooling type) Rated Current [A]
(Line to Power 95 (to earth and across open contacts) know-how
Rated Short Time Withstand Currentfor[kA]
such energy simulation
25 required 1250 / 1250 / 1250 1250
Earth) Frequency [kV] 110 (across isolating distance)
TR : Epoxy Resin Molded Dry Inverter-2,700W * 2,200D * 2,900H 2500 2000
in designing a highly efficient total energy
/ Liquid Silicone Dimension Rated Short Time Withstand 25 / 25 / 20 / 25 / 20 / 25 /
P10 12-Pulse
Rated Current [A] Unit Up to 2,000kW
Rectifier 1250 Control Panel of Inverter-800W * 1,000D * 2,300H
saving solution for the customer.
SR : Heat-pipe Self-cooling Current [kA] 31.5 31.5 31.5 31.5
DC Reacrtor-2,800W * 2,000D * 2,500H
Rated Voltage [kV]Auxiliary
P10 AC
55 /switchgear
27.5
Rectifier DC switchgear
Rated Short Time Withstand 31.5 This simulation leads to a more suitable design of Applicable Standards JEC / IEC
(Power DC Switchgear
Current [kA] Unit DC 600V, DC1500V HSCB or HSVCB
Type Power Supply ONANReceiving equipment (Feeder panel) the TESS in terms of efficiency and cost as well.
panel panel) Auxiliary
ApplicablePower
Standard DC 110V,
Application
Self Capacity [MVA] Feeding System
4 / 5 / 7.5 / 10 for High Speed Railway IEC Lead Storage Battery
Rated Supply Unit AC 105V / 210V
Rated
PowerVoltage
Line [kV]
Capacity [MVA] 220 / 152 Outline
/ 25x
8 / 10 /; 161 of Package-Type
20 / 60x 2 ; 132 / 27.5x DC
2 Substation
P7
1
19 Cooling Type
Overload ONAN
300% /2min
ONAF / OFAF 20
Rated Power [MVA] 84 / 60
Can withstand thermally and mechanically Rated Voltage [kV] 36 40.5 72 84
Short Circuit Intensity
Overload for 255mins
200% or 35 times of the rated current Lightning Impulse [kV] 170 185 350 400
P13 Rated Withstand Voltage
Applicable Standard
Connection JEC / IEC
Scott Power Frequency [kV] 70 95 140 160
Applicable Standard JEC / IEC 21F Distance Protection Rated Current [A] 630, 1250, 2500 630, 1250, 2000 800, 1250 800, 1250
51F Overcurrent Protection Rated Short Time Withstand Current [kA] 25, 31.5 25, 31.5 20, 25, 31.5 20, 25, 31.5
Protection Function
6 Power SCADA
5-8 Regenerative Inverter
The regenerative inverter is P15
an ideal solution for regenerative braking power from rolling stocks. It converts the DC regenerative
power back to AC power and supplies it to the auxiliary system for passenger stations. Toshiba supplies the IGBT inverters with Overview Features
heat pipe cooling systems.
pressure difference
imes
Liquid Flow
Liquid Flow
Water Total Monitoring PCs Operator Console 1 Operator Console 2 Operator Console 3
heat exchange Base Clock Main Server A Main Server B Main Server C
1,000kWcontinuous rating
Regenerating Inverter mode
00 (at 1010 6A / sec) Capacity 3,000kW1minute or 4,500kW-30seconds
Powering Converter mode 1,000kWcontinuous rating only
for IEC) 1,500VDC
Rated Input Voltage Output control mode (Make a selection for your operation ) PS LAN-A(HUB)
-1) Load control: To 6 or 8 output regulation
-2) Constant voltage control PS LAN-B(HUB)
OIT
52m
OIT
Safe
Using safe material
(LTO)
Regenerative Inverter System Traction Energy Storage System with SCiB Low Temperature High Effective
Operation Capacity
Regenerative DC power from an electronic train converted to AC Regenerative DC power AIS
can now be stored in Toshibas Traction Energy Storage Super Charge Ion Battery (SCiB) Usable in extremely Attractive features are realized by High amount of actual
power via a Regenerative Power Inverter. The AC power is then System which utilizes high performance SCiB batteries. It is controlled cold enviroments usable energy over
using Lithium Titanate Oxide
supplied to nearby passenger stations for auxiliary power (e.g. using a special control system with Toshibas own propriety technology that SCiB is a rechargeable battery. (-30C)
(LTO) in its anode
wide range of SOC
Lighting, Escalators, etc.) promotes batteries longer lifetime. With the use of this equipment, each By using unique oxide materials, SCiB holds high resistance toward
substation can not only thermal runaway resulting from short circuiting caused by physical
save regenerative power stress. SCiB also has good characteristics such as, long life with small
but it can also help promote capacity loss even after 6,000 full charge-discharge cycles, rapid
power peak cut, compensate charging capability with ability to charge 80% of the capacity in as fast Rapid High
voltage unbalance and be 16m as approx. 6 minutes. High power output with performance equivalent Recharging Input & Output
used as emergency power to that of an EDLC (Electric Double-Layer Capacitors), and good Recharges Usable with
in approx. 6 minutes high current
system.43m cryogenic performance with ability to function even at -30C.
Long Life
GIT Over 6,000 charge-
Regenerative discharge cycles
GIS * Results of cell level tests under certain
Inverter SCiB Battery Panel conditions. Not a guaranteed
23 24
11m
GIT
Global Network
Global operations; Japan Global operations; Asia
X Sales / Engineering / Rep Office 1 Head Office (Tokyo, Japan) X Sales / Engineering / Rep Office 32 (TIPL) Toshiba India Private Ltd.
7
Y Production Factory Corporate Staff Y Production Factory
Sales 33 (TAPL) Toshiba Asia Pacific Pte., Ltd. (Singapore)
Engineering
8 34 (TAPL) Toshiba Asia Pacific Pte., Ltd. (Bangkok)
Japan 2 Smart Community Center [Kawasaki, Japan]
Corporate Staff 35 (TAPL) Toshiba Asia Pacific Pte., Ltd. (Kuala Lumpur)
Sales 32 40 38
9 6 Engineering 37 36 (TAPL) Toshiba Asia Pacific Pte., Ltd. (Jakarta)
4 1 India, South East Asia
10 3 2 3 Hamakawasaki Operations 34 37 (TAPL) Toshiba Asia Pacific Pte., Ltd. (Manila)
13 12 11 5 Transformers
14 35 39
7 Hokkaido Branch Switchgears 38 (TTDV) Toshiba Transmission & Distribution Vietnam
Surge Arresters 33 Protection Relays
8 Tohoku Branch On Line Monitoring Systems Substation Automation Systems
36
9 Hokuriku Branch
4 Fuchu Complex 39 (TTDA) Toshiba Transmission
10 Chubu Branch Protection System & Distribution Systems Asia Sdn. Bhd.
11 Kansai Branch Substation Automation System Medium Voltage Switchgears
System Solution vacuum Circuit Breakers
12 Shikoku Branch Medium Voltage Switchgears Ring Main Units, Compact Substations,
EPC of T&D Systems
13 Chugoku Branch 5 Mie Operations
14 Kyushu Branch Distribution Transformers 40 (TTDI) Toshiba Transmission & Distribution Systems India
Power Transformers EHV, UV, Transformers
Protection Equipment Medium Voltage Switchgears
Power Distribution Equipment
6 Kitashiba Electric Co., Ltd.
Distribution Transformers
Power Transformers
X Sales / Engineering / Rep Office 15 (TBV) Toshiba Baiyun Vacuum Interrupters (Jinzhou) Co., Ltd. X Sales / Engineering / Rep Office 41 (TIL) Toshiba International (Europe) Ltd. (Durham)
16 23 15 Vacuum Circuit Breakers
Y Production Factory Y Production Factory
China 17 18
42 (TTDE) Toshiba Transmission & Distribution Europe
16 (ETA) EPRI Toshiba Arrester Co., Ltd. 46 EPC of substations
20 19 Surge Arresters (~1,100kV) EPC of PV plants
41
21 17 (PTC) Henan Pinggao Toshiba High-Voltage Switchgear Co., Ltd. 42 43 (JHB) Toshiba Johannesburg Rep. Office
22
High Voltage Switchgears (110~1,100kV)
44 EMEA and Russia 44 (TTDG) Toshiba T&D Systems Gulf SPC. (Abu Dhabi)
18 (CTC) Changzhou Toshiba Transformer Co., Ltd. 45
Large Capacity Transformers (~1,100kV) 45 (TTDG) Toshiba T&D Systems Gulf SPC. (Bahrain)
19 (CTS) Changzhou Toshiba Shuidian Transformer Co., Ltd. 46 (TCIS) Toshiba CIS LLC (Moscow)
Distribution Transformers
X Sales / Engineering / Rep Office 24 (TIC-US) Toshiba International Corp. (Houston) X Sales / Engineering / Rep Office 47 (TIC AUS) Toshiba Intl Corp. (Sydney)
Y Production Factory Headquarters Y Production Factory
Power conditioner, Battery Energy Storage 48 (TIC AUS) Toshiba Intl Corp. (Brisbane)
25 (TIC-US) Toshiba Intl Corp. (Denver) 49 (TIC AUS) Toshiba Intl Corp. (Melbourne)
26 (TIC-US) Toshiba Intl Corp. (San Francisco) Oceania 48 50 (TIC AUS) Toshiba Intl Corp. (Perth)
25 26