Sunteți pe pagina 1din 1

FROM

GENERATOR

WEBSITE
N
L3
L2
L1

www.deepseaplc.com
P1

BATTERY +VE
(12 OR 24 VDC )
MIN 2 AMPS
MAX 20 AMP

S1
ANTI-SURGE FUSE

2
49
+VE

CT1
S2

BATTERY
CT2
-VE

1
L151 L251
50
P2
SECONDARY
UPTO32 AMPS REMOVE LINK FOR
FOR REMOTE EM STOP RS232
FUSE

51

CT3
L351
CTs MUST BE 5 AMP

GEN CURRENT
N52

3
CT4
53

BATTERY -VE
TO FUEL SOLENOID MAX 16AMP

4
52
FUEL

COM

5
TO CRANK SOLENOID MAX 16AMP CRANK

L1
45
LOW OIL PRESSURE

L2
OIL PRESSURE

57
46

ALL BATTERY NEGATIVES MUST BE CONNECTED TOGETHER


HIGH COOLANT TEMP

L3

GEN VOLTS
WATER TEMP

58
47
FUEL TEMP
FUEL

59
48

60
COMMON GROUND

2 AMP
FUSES
TO ENGINE EARTH

39
TO GEN SWITCHING
DSE5510

4
DEVICE CIRCUITRY

GEN
CLOSE
CHARGE ALT

9
OUTPUT
40
CHARGE ALTERNATOR
DIAGRAM.

USER CONFIGURATION INPUT 1

10
20

SCR
TO MAG PICK UP IF
USED
USER CONFIGURATION INPUT 2 SCREEN EARTHED AT

11
21

MPU
THIS END ONLY
DO NOT CONNECT

12
22
USER CONFIGURATION INPUT 3
SCREEN TO ENGINE

13
157
USER CONFIGURATION INPUT 4

P810
USER CONFIGURATION INPUT 5

14
37

9 INPUTS
MODULE 5510
5
OUTPUT

15
38
USER CONFIGURATION INPUT 6

16
USER CONFIGURATION INPUT 7

17
54
USER CONFIGURATION INPUT 8
3 or 4 POLE
or CONTACTOR

PLANT +VE
AUTOMATIC ACB

USER CONFIGURATION INPUT 9

18
55
AUTOMATIC MCCB

UNUSED

56
USER CONFIGURATION INPUT +VE OUTPUT

6
SCR
29
USER CONFIGURATION INPUT +VE OUTPUT

7
30

RS485

3 OUTPUTS
USER CONFIGURATION INPUT +VE OUTPUT

8
31
23
SCR
TO ENGINE ECU
SCREEN EARTHED AT

19
24

J1939
THIS END ONLY
CONECT SCREEN AT
DO NOT CONNECT

L
GENERATOR ONLY SCREEN TO ENGINE

25

B
O/P

32

TO
L1

33
41

GOVERNOR
GOVERNOR
L2
UNUSED

34
42

MSC
L3

BUS VOLTS

SCREEN EARTHED
B
O/P

AT THIS END ONLY


35
43

L
H
SCR

AVR

TO
AVR
A
N

36
44

28
27
26
CONECT SCREEN AT
GENERATOR ONLY
2 AMP
FUSES
N
L3
L2
L1

H(27) AND L(28)


MAX 250 METERS
TO LOAD

MSC CONNECTIONS

120 OHM SCREEN CABLE


TO OTHER 5510 AND 5560

THE FIRST AND LAST UNITS

120 OHM RESISTOR ACROSS


MSC MUST BE FITTED WITH A

S-ar putea să vă placă și