Documente Academic
Documente Profesional
Documente Cultură
cn
and harmonic power components of the load current while maintaining A Novel Technique for Measuring Grounding
the sinusoidal currents and unity power factor at the source side.
Simulation Results: A simulation example for the three-phase
Capacitance and Grounding Fault Resistance
four-wire SAPF connected to a nonlinear load supplied by an unbal- in Ineffectively Grounded Systems
anced source is used to verify the usefulness of the proposed method for
calculating SAPF reference compensating currents. Figures 2 - 4 illus-
trate the simulation results for the SAPF instantaneous reactive and XiangJun Zeng, Xianggen Yin, Deshu Chen
harmonic power compensation. Figure 2 shows waveforms of the Author Affiliation: Department of Electrical Power Engineering,
source voltage, source currents before and after compensation at each Huazhong University of Science and Technology, Wuhan, Hubei Prov-
phase. Figure 3 reveals the waveform of the SAPF reference compen- ince, China.
sating current at phase a. Figure 4 illustrates the waveforms of the in- Abstract: A principle for resonance measurement based on inject-
stantaneous and average active power supplied by the SAPF during ing resonant frequency signal is presented in this letter. The grounding
compensation. The waveforms in Figure 4 indicate that the average ac- capacitance of lines and equipment and the grounding fault resistance
tive power consumed by the load is completely supplied by the source, can be measured on-line in ineffectively grounded systems.
and the SAPF does not require the dc source to produce compensating Petersen-coil automatic tuning is implemented, and 100% stator
current. As illustrated in Figures 2 - 4, the SAPF is as expected to have a grounding fault protection for generator stator windings is also pro-
good performance based on the proposed method for generating refer- posed. The prototype for Petersen-coil tuning has been tested on net-
ence compensating currents. works for many years. In addition the new method for generator stator
Conclusions: The method proposed in this letter is useful for deter- grounding fault protection is verified by simulation.
mining the three-phase SAPF reference compensating currents in the Keywords: Distribution systems, Petersen-coil tuning, generator
a-b-c coordinate for reactive and harmonic power compensation of the protection
load. The SAPF compensation scheme based on the proposed method Introduction: Many medium voltage distribution networks are res-
is valid for both ideal and nonideal source voltages as well as load cur- onant earthed neutral systems [1]. In China, most distribution systems
rents in the three-phase system, where the sinusoidal source currents are isolated systems or resonant earthed neutral systems. To benefit
are maintained. Unlike the p-q theory-based methods that involve more from this resonant earthed neutral systems (arc self-extinguishes), reso-
complex design in SAPF control circuit due to coordinate transforma- nance tuning between Petersen-coil inductance and grounding capaci-
tions, the proposed method provides a simpler way to implement the tance of lines and equipment must be maintained on-line. The
SAPF controller. The new method is proved to be adequate for com- grounding capacitance varies with the networks topology that changes
pensation applications. in practical operation. Consequently, the grounding capacitance must
References: be measured on-line. The traditional way for measuring grounding ca-
[1] H. Akagi, Y. Kanazawa, and A. Nabae, Generalized theory of pacitance based on an analysis of neutral-to-earth voltage (that is, reso-
the instantaneous reactive power in three-phase circuits, in Proc. IEEJ nance curve) is the Petersen coil [1]. Another method based on
Int. Power Electronics Conf. (IPEC-Tokyo), 1983, pp. 1375-1386. injecting constant frequency current signal needs to measure ampli-
[2] W.M. Grady, M.J. Samotyj, and A.H. Noyola, Survey of active tudes and phases of the injected current, of neutral-to-ground voltage
power line conditioning methodologies, IEEE Trans. Power Delivery, and of their variation due to the injection with high accuracy [2].
vol. 5, pp. 1536-1542, July 1990. In generator units, while high grounding fault is taking place, the
[3] J.L. Willems, A new interpretation of the Akagi-Nabae power ground fault current is not larger than the capacitive current of genera-
components for nonsinusoidal three-phase situations, IEEE Trans. tor stator windings. Thus this ground fault is difficult to detect by the
Instrum. Meas., vol. 41, pp. 523-5297, Aug. 1992. traditional protection scheme based on the fundamental frequency zero
[4] F.Z. Peng and J.S. Lai, Generalized instantaneous reactive sequence voltage and the third-order harmonic zero sequence voltage
power theory for three-phase power systems, IEEE Trans. Instrum. [3], [4]. Another protection scheme based on injecting a subharmonic
Meas., vol. 45, pp. 293-297, Feb. 1996. frequency signal can improve sensitivity due to the high impedance
Copyright Statement: ISSN 0282-1724/01/$10.00 2001 IEEE. path of the generator and connected equipment capacitance at the low
Manuscript received 9 August 2000. This paper is published herein in frequency [5]. This still can not satisfy the requirement of large genera-
its entirety.
tor units, however (such as the hydro-generator of Three-Gorge Power Petersen-Coil Automatic Tuning: A variable frequency current
Station, which stator winding capacitance is about 6f ). signal is injected though the secondary side of zero sequence voltage
A novel method for resonance measurement based on injection res- transformer, which is contained in the Petersen coil, into the zero se-
onant frequency signal is presented in this letter. Grounding capaci- quence circuit (as in Figure 2). By changing the signal frequency and
tance can be simply calculated and grounding fault resistance can also looking for the resonance frequency of the system, the total grounding
be evaluated. Then, Petersen-coil tuning is implemented and 100% capacitance of lines and equipment can be calculated by (1). The total
stator high-impedance ground-fault protection for generator stator capacitive current is
windings can be realized.
The Principle of Resonance Measurement: The zero sequence
U
equivalent circuit for resonance measurement with injection signal in I C = 3 CU =
ineffectively grounding systems is shown in Figure 1, where Is is a 20 L
variable frequency constant current signal source, U s is the signal volt- (3)
age, R0 is the neutral point earthed resistance in high-resistance ground
systems or in resistor parallel with compensation equipment where is the system angular frequency and U is the phase voltage of
(Petersen-coil) grounding systems, I n is the current injection at the neu- system.
tral point (not including the current through R0 ), L is the neutral point The total inductive impedance of the Petersen coil will be adjusted
earthed inductance in reactance grounding systems or resistor in paral- to equal capacitive impedance on-line. When a distribution system has
lel with compensation equipment grounding systems, C is the total several Petersen coils, the grounding capacitance of the whole network
grounding capacitance of equipment and lines, and R f is the grounding can be calculated easily only by selecting one Petersen coil to inject sig-
fault resistance. By injecting a variable frequency signal, measuring nal current and then looking for the systems resonant frequency.
phase difference between the signal voltage (U s ) and the signal current Practical Experience with Petersen Coil Tuning: The prototype
(I s ), while the phase difference is about equal to zero (that is reso- for Petersen coil tuning is developed, which has been tested on net-
nance), this signal frequency is the resonance frequency of the system. works for several years. Some operational feedback has already been
The total capacitance to earth (C) can be calculated by received. The capacitive current of one 35 kV distribution network in
Minlou (Hunan province, China) was measured on 6 January 1997.
1 Each feeder was switched on or off, and the capacitive current was
C = L 2 tested (Table 1).
0
(1) From Table 1, we can find that the largest error is up to 0.6 A. It
maybe because the estimated value of the capacitive current is not ac-
where 0 is the resonance angular frequency. curate and that the magnetic curve of Petersen coil is nonlinear.
Injecting a signal with resonant angular frequency 0 during Stator Grounding Fault Protection: In subharmonic injection
grounding fault, the fault resistance R f can be calculated as protection schemes, the signal frequency is usually selected as 12.5 Hz,
20 Hz, etc. They can reduce the effect of grounding capacitance of
stator windings, but they are difficult to eliminate. In order to satisfy the
Us requirement of 100% stator high-impedance ground-fault protection
Rf = .
In for large generator units an inductance, which is connected in parallel
(2) with the resistor at the secondary side of neutral point grounding trans-