Documente Academic
Documente Profesional
Documente Cultură
SERIES: EWYQ-BAWP
SERIES: EWYQ-BAWP_MAX
GENERAL CHARACTERISTICS
-Inverter chiller
-High efficiency with leader-of-class ESEER (up to 4.33)
-Minimal starting currents and short payback times
-No buffertank required for standard applications
-Daikin scroll compressor
-Large operation range (ambient temperature up to 43C)
-Digital remote controller
Page 1 of 4
Chiller selection software
DAIKIN CSS - Rev. 9.5
Printing date: 14/02/2017
GENERAL CHARACTERISTICS
-Inverter chiller
-High efficiency with leader-of-class ESEER (up to 4.33)
-Minimal starting currents and short payback times
-No buffertank required for standard applications
-Daikin scroll compressor
-Large operation range (ambient temperature up to 43C)
-Digital remote controller
Page 2 of 4
Chiller selection software
DAIKIN CSS - Rev. 9.5
Printing date: 14/02/2017
CASING
Colour * Daikin White Daikin White
Material * GPSS GPSS
DIMENSIONS
Height mm 1684 1684
Width mm 2980 2980
Length mm 780 780
WEIGHT
Unit Weight kg 730 730
Operating Weight kg 738 738
FAN
Type * Direct drive Direct drive
On/Off fans On/Off fans
Drive *
Air temperature C 35,0 35,0
COMPRESSOR
Type Hermetically sealed scroll Hermetically sealed scroll
compressor compressor
Quantity No. 6 6
SOUND LEVEL
Sound Power - Cooling*** dB(A) 83 83
REFRIGERANT CIRCUIT
Refrigerant type R410A R410A
Refrigerant charge kg 19 19
N. of circuits No. 1 1
PIPING CONNECTIONS
Evaporator water inlet/outlet 2" (female) 2" (female)
* IW: Ivory White - GPSS: Galvanized and Painted Steel Sheet - PHE: Plate Heat Exchanger - S&T: Single Pass Shell & Tube.* CC:
Closed Cell - HFP: High efficiency fin and tube type - DPT: Direct Propeller Type - DOL: Direct On Line - VFD: Inverter - BRS:
Brushless.** If red contact factory.***sound power level (@STD conditions) are mesuared in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units
Page 3 of 4
Chiller selection software
DAIKIN CSS - Rev. 9.5
Printing date: 14/02/2017
Fluid: Water
* Heating capacity, unit power input and COP are based on the following conditions: air exchanger 7,0 - 85%C; water exchanger
40,0/45,0, unit at full load operation;
ELECTRICAL SPECIFICATIONS
MODEL EWYQ064BAWP EWYQ064BAWP_MAX
POWER SUPPLY
Phases Nr 3 3
Frequency Hz 50 50
Voltage V 400 400
Voltage tolerance Minimum % -10 -10
Voltage tolerance Maximum % 10 10
COMPRESSORS
Phases Nr 3 3
Voltage V 400 400
Starting method ---
Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting
current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%.Nominal
current in cooling mode is referred to the following conditions: evaporator 12/7C; ambient 35C; compressors + fans
current.Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed
current.Maximum unit current for wires sizing is based on minimum allowed voltage.Maximum current for wires sizing:
(compressors full load ampere + fans current) x 1,1.(1) Running current based on the following conditions: evaporator
12,0/7,0C; ambient 35,0C;Fluid: Water
Page 4 of 4