Documente Academic
Documente Profesional
Documente Cultură
Per-unit Quantities
The per-unit value of any quantity is defined as the ratio of the actual quantity to its
base expressed as a decimal. That is, a per-unit quantity = (Actual quantity) / (Base
quantity).
=
(Base voltage kVL x1000/ 3 ) 3Base voltage kVL
Base kVA 3ph
= [(Base voltage kVL)2] / [Base MVA3ph ]
b) The per unit impedances of machines of the same type and widely different
rating usually lie within a narrow range although the ohmic values differ
materially for machines of different ratings. For this reason when the
impedance is not known definitely, it is generally possible to select from
tabulated average values a per unit impedance which will be reasonably
correct. Experience in working with per unit values brings familiarity with the
proper values of per unit impedance for different types of apparatus.
1
d) The way in which transformers are connected in three-phase circuits does not
affect the per unit impedances of the equivalent circuit although the
transformer connection does determine the relation between the voltage bases
on the two sides of the transformer.
Solution:
[kV ( A)]2 MVA( B)
Z P.U . ( B) Z P.U . ( A)
[kV ( B)]2 MVA( A)
18 2 100
Z P.U . ( B) 0.25( )( ) 0.0405
20 2 500
2
diagram. It indicates by a single line and standard symbols how the transmission
lines and associated apparatus of an electric system are connected together. The
purpose of the one-line diagram is to supply in concise form the significant
information about the system.
The American National Standards Institute (ANSI) and the Institute of Electrical and
Electronics Engineers (IEEE) have published a set of standard symbols for electrical
diagrams. Figure 1 shows a few symbols which are commonly used.
In order to calculate the performance of a system under load conditions or upon the
occurrence of a fault, the one-line diagram is used to draw the single-phase or per-
phase equivalent circuit of the system. Figure 3 combines the equivalent circuits for
the various components shown in figure 2 to form the per-phase impedance diagram
of the system.
3
For a load study :
The lagging loads A and B are represented by resistance and inductive reactance
in series.
The impedance diagram does not include the current limiting impedances because
no current flows in the ground under balanced conditions.
Shunt admittance of a transformer is usually omitted as the shunt current is
usually insignificant compared with the full-load current.
If we decide to simplify our calculation of fault current by omitting all static loads, all
resistances, the shunt admittance of each transformer, and the capacitance of the
transmission line, the impedance diagram reduces to the per-phase reactance diagram
of figure 4. These simplifications apply to fault calculations only.