I. INTRODUCTION
1 87 ,5
1 00
1 00
p c.
p c.
6 .25 0,00
The model determines the number of I/O points needed Often in making such comparisons there are
and calculates material costs involved. Also the cable compromises to be made, as rarely in practice are there
types and cable lengths are calculated including the cable only benefits and no dis-advantages in choosing one
material and installation costs. solution over the other.
For the intelligent MCC the cost savings are related to: The main driver in choosing between the technologies
- no need for DCS I/O is which approach gives an lower overall cost to the
- no need for conventional wiring project? Often this is influenced by the ability to allow
process engineering and electrical design to overlap and
thereby contribute to reducing or at least holding the
project duration. Benefits of early completion or achieving
planned completion dates can be very, very large and far
outweigh the difference in equipment costs.
VI. INTELLIGENT MCC, FUTURE DEVELOPMENTS VII. CONCLUSIONS, ARE THE BENEFITS OF IMCS
REALIZED IN PRACTICE?
Compartment temperature measurement (i.s.o. IR
scanning) In practice we have seen a strong tendency for more
Communications suitable for safety bus (no ESD and more MCCs to be specified with intelligent devices.
relays needed). This implies a need to comply with There is a greater amount of data requested to be made
additional requirements to achieve a suitable SIL available to DCS or SCADA systems. Whether this is as a
rating. Will users be happy to discard hard wiring result of a real need or merely response of designers to
for emergency stop signals? the capability being available is not wholly clear.
Make re-start schemes work reliably. Currently
settings are not recorded (communicate them and Intelligent MCCs offer lower installation costs when a
make the scheme visible). When restarting relays reasonable of MCC information has to be communicated
are used they can have unrevealed failures (they with the Process Control system.
are not telling that they are fault) Intelligent MCCs offer a high degree of flexibility with
Eliminate interposing relays regard to information available to be communicated now
Reduce amount of wiring (e.g. communication over or in the future. If certain functionality is not needed today
mains power or auxiliary power supplies) but needs to be added in the future most intelligent MCCs
Better Data management. Record settings in the can handle this without major changes.
field. Make it visible what changes have been
made in the field compared to released settings Also important for low maintenance costs is the lifetime
(approved by site management). of the Intelligent MCCs. Software and electronics tend to
Allow web browser functionality : no special change with a more rapid pace than the MCC main
software is needed on your PC. Just hook-up the components. In the past, suppliers of intelligent devices
laptop using an Ethernet or USB connection. have not given backward compatibility and upgrade paths
sufficient thought. Users are now being faced with
Allow next to local monitoring / parameter setting
complete system replacements and major upgrade costs
optionally for remote monitoring / parameter setting
after only 12-15 years of operation
through Internet.
Allow for integration of normal (low cost) multi-
It has been an article of faith in the past by many users
meters with the IMCS
that smart devices were the way to go in the future.
Event recording on functional unit level for use However Intelligent Motor controls have not yet fully
within Sequence of Event Recording (requires time delivered on their promise.
synchronisation) Areas for improvement are:
Wireless communications? Security is a big issue! Emergency stop signals are still hard wired
Reliability is a big issue in high EMC environments. meaning not all cost savings are realized,
Thermal overload should reset automatically. Trip Setting up the devices requires significantly
history should be available. more effort than for conventional devices and
How to deal with emergency stops and safety the number of settings creates issues in storing
switches (interlocks). the data,
In substations with both MV and LV MCCs or Differences in the version of the firmware used in
switchboards different standards exist for the devices creates problems for users where
communication protocols for MV and LV they have nominally identical devices bought at
equipment. different times,
Is IEC 61850 the way to go for communication Lifetime of the units is often short compared to
between MCC starter devices and the outside users expectations and upgrade paths are not
world so that there is a single protocol used? clearly thought through
Even where it is accepted that different protocols
Bespoke communication solutions are used
are needed due to differing requirements between
rather than true standards so interoperability is
of IMCS and MV Intelligent Electrical Devices
only achieved with considerable effort
should a common highway such as Industrial
Ethernet be adopted?
Is the profile LowVoltageSwitchGear as defined
by Profibus User Organisation the best standard
for motor starter communication, with regard to the
data organisation and content?
VIII. REFERENCES
IX. VITA
Authors:
Hans Meulenbroek