Sunteți pe pagina 1din 2

Technical Datasheet Offer number: 27099587 Attachment

________________________________________________________________________________
Siemens H-Pos: 300; 3EP6 132-3PJ41-2DR1-Z X07 D91 X81
System Information
Nominal System Voltage (Un) 132 kV
Highest Voltage of Equipment (Um) 145 kV
Basic Insulation Level (BIL) 650 kV
Maximum altitude of installation (a.s.l.) 1000 m
Neutral system earthing solid
Power Frequency 50 Hz
Ambient temperature range -40 ... 55 C
Electrical data
Applied Standard IEC 60099-4
Rated voltage (Ur) 132 kV
Maximum continuous operating voltage (Uc / MCOV) 106 kV
Nominal discharge current (In, 8/20 s) 20 kA
Line discharge class 4
Long duration impulse current withstand (2 ms) 1 600 A
High current impulse withstand (4/10 s) 100 kA
Rated short circuit current (0,2 s) 65,0 kA
Maximum residual voltage at :
20 kA 1/2 s 413 kV
5 kA 8/20 s 297 kV
10 kA 8/20 s 316 kV
20 kA 8/20 s 347 kV
40 kA 8/20 s 379 kV
500 A 30/60 s 256 kV
1 kA 30/60 s 262 kV
2 kA 30/60 s 275 kV
Temporary overvoltage for 1 s 142 kV
Temporary overvoltage for 10 s 132 kV
Energy discharge capability - thermal 10,0 kJ/kVr
Energy discharge capability - impulse 6,50 kJ/kVr
Power Frequency withstand voltage (1min, wet) 452 kV
Lightning Impulse withstand voltage (1,2/50 s) 1 116 kV
Mechanical data
Height (H) 2 189 mm
Minimum creepage distance 7 668 mm
Number of units 1
Weight (G) 227 kg
Color of housing brown
Specified long-term load SLL (Fstat) 3280 N
Specified short-term load SSL (Fdyn) 8220 N
Drawing number E T HP AR 27099587.0300
Accessories
Line terminal Bolt 30 x 80 mm, A2
Ground terminal Insulated, 240x240 mm
Accessory 1 Earth lead 0,45 m / 35 mm

Accessory 2 3EX6031 Line clamp DIN/NEMA


Accessory 6 The Arrester Condition Monitor (ACM) in the advanced version reveals the
arrester conditions by indicating the following operating parameters:

- Total leakage current (peak value) in turns with


- Number of (surge) impulses,
- Resistive (leakage) current visualized by a "traffic light" system.

The "traffic light" visualisation of the resistive current is based on a


3rd-harmonic-evaluation of the leakage current considering the specific

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 5/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
surge arrester configuarion. Moreover, with a harmonic compensation in
the system voltage and considering the influence of the temperature of
the measurement the resistive current value is rectified.

General technical data:

- Measuring frequency range: 50 or 60 Hz


- Ambient temperature range: -40C to +60C

- Power supply: Solar panel


- Unlimited application field: latitude < 60
- Operational readiness after deep discharge of the solar battery: <(>
<<)> 2
days, placed in direct sunlight < 3 hours

Leakage current measurement:


- Measuring range of total leakage current (peak level): 0,15...15 mA
- Measuring range of resistive leakage current (peak level): 25...5000
A

Impulse current measurement:


- Counting threshold: > 50 A
- Surge counting time resolution: 2 Impulse per second
- Measuring range:
- High current (4/10 s): 1...100 kA
- Lightning impulse current (8/20 s): 1...40 kA
- Switching impulse current (30/60 s): 0,25...3 kA
- Long-duration current (T=500...5000 s): 0,2...2,1 kA

The included license key (arrester specific) enables the user to access
the following features, using the free of charge software and a
PC/laptop:
- Leakage current measurement (Itotal und Ires) daily for trend
analysis,
- Detailed Surge data history: date, time, surge current peak value,
equivalent of surge energy.

Memory capacity:
- Detailed surge data history: 448 entries
- Trend analysis data: 2000 (> 5 years)

Sensor/Transceiver data communication:


- Frequency: 2,4 GHz
- Transmitting power: <3 dBm
- Operating range:
- horizontal: up to 50 m
- vertical: up to 50 m

To establish a wireless remote connection between laptop and ACM one


USB-wireless module (3EX5 086) will be needed and has to be ordered
seperately.

AL: N
ECCN: N

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 6/8