1. Scope

This specification covers accessories for power cable.

2. Reference Standards

IEC 62067 : Power cables with extruded insulation and their accessories for rated voltages above
150kV(Um=170kV)
up to 500kV(Um=550kV) Test methods and requirements

3. Construction and Material

Construction and dimensions of accessories are shown in the attached drawings.

4. Tests

The following tests shall be performed prior to shipment at manufactures work.

4.1 Routine tests

Appearance & Construction test.

4.2 Sample tests

Dimensions test (One Sample).

5. Packing

All accessories shall be covered with strong wooden box, and each wooden box shall be marked with particulars of
accessories, i.e. description, size, quantity, gross and net weights, etc.

6. Reference Drawings

Item No. Descriptions Drawing No.


1 LINK BOX FOR EARTHING (1-1 WAY) UEEBE1Q002
2 LINK BOX FOR EARTHING (3-1 WAY) UEEBE3Q002
3 LINK BOX WITH SVL (1-1 WAY) UEEBS1Q002
4 LINK BOX FOR CROSS-BONDING (3-1 WAY) UEEBX3Q001
5 LINK BOX FOR EARTHING WITH SVL (3-1 WAY) UEEBM3Q002
Ref. No. : LSPA13-S120
Rev. No. : 0
Page No. : 3 of 3

7. Storage instruction for cable accessories

7.1 General

All materials shall be stored in a dry warehouse protected from the sunrays. Cases must be laid on a flat without loads
over them. Room temperature shall be controlled less than 35 and humidity also shall be less controlled than 50%.

7.2 Guaranteed Period


For the other items which are not shown in the table below, two years shall be guaranteed unless it is explicitly stated.

7.2.1 Epoxy Resin Components


Epoxy resin components could absorb moisture if the components are exposed to air directly for long time;
an under vacuum heating treatment (90 for 48 hours) must be carried out before the installation of the component.
Even if the epoxy resin components are not exposed to air directly, vacuum heating treatment is recommended before
installation.

7.2.2 Rubber Components


Stress cone and joint sleeve components, which are rubber components as main insulators, shall be kept away
from direct sunrays. The direct sunrays affect the original nature of rubber.

7.3 Storage Time

Some components, in particular tapes and putties, could have a decay of physical characteristics due to storage time
and ambient temperature. Assuming the ambient temperature of the warehouse between 0 and 35 , the
following storage time could be guaranteed:

Material Usable period after date of production


Metal parts 5 years or more
Porcelain/Composite Insulator 5 years or more
Epoxy components 5 years
Silicone rubber sleeve 5 years
Heat shrinkable tubes 2 years
Stress relief cone (EPR/Silicone) 5 years
Gasket/O-ring 5 years
Tapes & Putties 2 years
Silicone grease 2 years
Insulating oil 2 years
Waterproof compound 3 years