SOUTHERN REGIONAL LOAD DESPATCH CENTRE POWER SYSTEM OPERATION CORPORATION LTD NOVEMBER 2012 BANGALORE INDEX CHAPTER) Saale) PAGE NO 1 Introduction 1.2 2 Black start Facilities 34 3 System Restoration Approach 57 4 Southern region - Over view & Grid maps 8-16 5 Detailed Operational Procedure for AndhraPradesh 17-62 6 Detailed Operational Procedure for Karnataka 63-87 7 Detailed Operational Procedure for Tamil nadu 88-141 8 Detailed Operational Procedure for Kerala 142-165 List of Annexures EIN SM03 Nea aie IPAGE NO. 1 List of Power Stations With Black Start Facilityin S.R 166-167 List of Major Sub-Stations With Synchronising Facility in SR 168-171 im List of Railway Traction Stations IRATS Vv Mock Exercise Procedure For inter Regional HVDC Links 176-184 List of Exhibits FAs Nea aie IPAGE NO. ANDHRA PRADESH 1 Startup Power for AP Subsystem - 1: RYTPP, VIPS, %6 Srisailam & N’Sagar Complex (During Total / Partial 2 Startup Power for A.P Subsystem - 2: Ramagundam NTPC 38 (During Total Blackout) G15 stata PAGE NO 3 Schematic Diagram of Badravathi HVDC Back to Back 30 Station 4 Startup Power for A.P Subsystem - 2: Ramagundam NTPC 45 (During Partial Blackout) 5 Startup Power for A.P Subsystem ~ 3: KTPS, NTPC Simhadri 49 (During Partial Blackout) 6 Schematic Diagram of Gajuwakha HVDC Back to Back 54 Station 7 Supply Details for Railway Traction System in A.P 58-60 KARNATAKA Startup Power for Kamataka Subsystem ~ 1: Sharavathi, 8 Sharavathi Tail Race (STRP}, Jog, Varahi and Yelehanka 68 (Diesel). (During Total / Partial Blackout) Startup Power for Kamataka Subsystem ~ 2: RTPS,BTPS, 9 Nagjheri, Kadra, Kodasalli Kaiga, Tata & Jindal (Ouring 76 Total /Partial Blackout) 10 Supply Details for Railway Traction System in Karnataka 86 TAMIL NADU a Startup Power for TN Subsystem — 1: TTPS (During Total 101 Blackout) 12 __ Startup Power for TN Subsystem ~ 2: MTPS & NLC (During 112 Total / Partial Blackout) 43 Startup Power for TN Subsystem ~ 3: Chennai Area (During 131 Total / Partial Blackout) 14 Supply Details for Railway Traction System in Tamil Nadu: 137-138 KERALA 15 Startup Power for Kerala Subsystem ~ 1: North Kerala 148 (During Total / Partial Blackout) 16 Startup Power for Kerala Subsystem ~ 2: South Kerala 153 (During Total / Partial Blackout) Supply Details for Railway Traction System in Kerala 158-159 7 Grid Maps EXHIBIT Nea aie IPAGE NO. 1 Andhra Pradesh System 2 2 Karnataka System B 3 Kerala System 4 4 Tamil Nadu System 15 5 Southern Region 16 Mock Drill Schedule 1 Safa NAN 1 Andhra Pradesh System 62 2 Karnataka System 87 3 Kerala System 165 4 Tamil Nadu System 139 SRLOC Black Start Restoration Procedure 2013 1.0 INTRODUCTION 1.1 Inan integrated power system, disturbances of major / minor nature can occur under various contingencies. Such disturbances can result in collapse of a part of the system or sometimes entire system, requiring restoration of the affected system in the minimum possible time. In order to achieve the same, it is therefore necessary to have a well laid down restoration procedure under various conditions of partial black out and /or total black out of the system 1.2. Inthe event of a black out, the initial moments are extremely precious and it requires the right decision to be taken at first instance for speedy restoration of the system. Any lapse or delay in taking the right initial decision may prove to be very costly. Hence, it is of paramount importance that all the operating personnel of Load Despatch Centres and the officials involved in grid operation should be thoroughly conversant with the restoration procedure so as to minimise the time taken in restoration of the system after partial /total black out, Further during the Restoration process the system operators, Power station and Substation personnel must act in consonance to normalize the grid 13 SRLDC has been publishing the document on “Black Start Restoration Procedure in SR" from time to time viz. December 1999, January 2002, July 2004, July 2006, February 2009, February 2010 , February 2011 and January 2012, Asthe network is expanding, in line with clause 5.8 (a & b) of IEGC, this Procedure requires review and/or revision every year, based ‘on which the Mock drill of the procedure for different sub-systems shall be carried out by the constituents at least once every six months under intimation to SRLOC 14 SRLDC has suggested the changes vide Letter dated 15.10.12 and requested the feed back 1.5 Based on the details of new elements added during this year and the feedback received during Black start Workshop held at constituents premises & letter communication, the updated version of the “Black Start Restoration Procedure in SR ~ 2013" (BSRP ~ 2013) was approved by SRPC forum in the 7?" Operation Co-ordination Committee meeting held on 09.11.12 SRLDC 16 17 Black Start Restoration Procedure 2013 The procedures given in this document are general in nature and provide a guideline for the restoration team at the time of disturbance. Depending on the availability of transmission elements, generators and the category and extent of blackout, restoration on real time basis should adopt the best procedure suited for the situation. Based on this document, SR constituents are advised to prepare station wise detailed mock drill procedure/plan including switching instructions in their control centres, so that the operators will have further clarity to ensure faster restoration in case of contingencies. SRLDC Black Start Restoration Procedure 2013 2.0 BLACK START FACILITIES 2.1 Existing Black Start facilities : A list of generating stations with self-start facilities is enclosed as Annexure/. 2.2 Survival/Auxiliary power requirement: Survival power can be defined as the minimum power required for avoiding the damage to the equipment in case of supply failure and keep the equipment fit for reuse immediately. Under black start failure the survival / auxiliary power would consist of the following * Turbine emergency oil pump = Jacking oil pumps * Barring gear of the turbine * Lubricating oll pumps * Compressors for breaker operation + Emergency lighting = Battery chargers communication & telemetry system 2.3 Asageneral rule, the survival power requirement would be around 0.25-0.30% of the unit capacity. SINO, [Unit Capacity Survival power required 7 120 MW Unit 250-350 KW 2 IO MW unit 350-500 KW 3 500 MW Unit 1250-1500 KW 2.4 Start up power requirement: The start up power is the power required for the atxiliaries while the generating unit is restored. The requirement of start up power by various units is as follows: = Nuclear & Thermal = Hydro = Gas 7 to 8% of the unit capacity 0.5 to 1% of the unit capacity 1.5 to 2%of the unit capacity SRLDC 25 2.6 27 Black Start Restoration Procedure 2013 The startup power requirement for starting the thermal units is considerably high as the major auxiliaries like BFP, ID Fan, FD fan, CW pumps etc. are of bigger size and the starting torque is large. However, in case of hydro units, the requirement of start-up power is comparatively much lower because of relatively very few auxiliaries. The details of the DG Set installed in the generating stations for providing start up power is enclosed as Annexured. Synchronising facilities at power stations / Major sub-stations: In order to build up the system, the synchronizing facilities play a very important role. The different generating stations having synchronising facilities are indicated in Annexure-1 Similarly, major 220/230KV sub-stations where synchronising facilities are available are detailed atAnnexure-Il, All 400kV Stations in the Region have Synchronising facility Railway Traction Supply During the time of System Restoration (Black Start} due importance is required to be given to the traction load and the supply to the grid points feeding the Railway Traction Station is to be extended on priority. A List of Railway Traction Stations is given in Annexure il Mock Exercise Procedure Mock Exercise Procedure for availing start-up power through AC by-pass of Inter Regional HVDC Links is detailed in Annexure - IV. SRLOC Black Start Restoration Procedure 2013 3.0 SYSTEM RESTORATION APPROACH While Restoring the System the following specific points must be given due importance: 3.1 Systems with a fair dispersal of generating stations with Black Start facilities Those generating stations where black start facility are available should be started up and stable islands should be formed around these generating stations by connecting essential loads. These islands should be gradually interconnected at the earliest opportunity keeping into consideration the total load-generation balance. Care should be taken to add loads in steps keeping in view the load characteristics Le. variation of load with respect to voltage & frequency. 3.2. Systems with limited and /or distant Black Start facility Providing start up power for systems which have few generating stations with black start facilities or the start up power to be imported from neighboring regions at one or two points is a challenging job. This is mainly due to the distance between the source of startup power and the generators and while extending the startup power care should be taken to control the voltages at various intermediate points. This can be achieved by providing loads and adjusting the taps of the transformers at the intermediate stations. Sufficient attention has to be given for MVAR management and line loadings to prevent secondary collapse during restoration which will extend the restoration time. 3.3 Reactive Power Control: During initial stages of restoration process, itis of utmost importance to keep the system voltages within the allowable limit. This can be accomplished by Charging the shorter line first Switching off capacitor bank Taking bus reactors into service Charging transformers and taking Bus reactors into service wherever available Converting line reactors into Bus reactors wherever feasible. Operating generators at minimum voltage levels Changing transformer taps Energisation of fewer high voltage lines. 3.4 Load & Generation Balance: * Achieving load generation balance by restoring commensurate and essential loads only. * Restoring load in small steps keeping in view the load characteristics, * Paying special attention while restoring traction and other fluctuating loads. + If considered essential, then by by-passing the U/F relays initially, until sufficient loads are connected & frequency stabilizes. * Maintaining frequency close to 50 Hz. SRLDC 35 3.6 37 Black Start Restoration Procedure 2013 = Keeping Generating units on FGMO Priorities: * Provide backup survival/start up power to nuclear units. * Restore start up power supply to generating stations, critical sub-stations and load dispatch centres * Formation of self-sustaining Islands around the generating stations for which procedures should be laid down in advance. * Avoid paralleling islands through weak ties Communication & Co-ordination: * Ensuring reliable communication between LDC's, generating stations and major sub-stations. . Agreed back up procedures & delegation of control in the event of failure of communication facilities. Actions to be taken at Generating Stations and Substations: Each Substation/Generating Station should draw its own detailed procedure for the action to be taken in their stations during restoration . To avoid delay in restoration ensure the proper functioning of bus couplers, synchronising facility etc at regular intervals, * Ensure proper gas/air pressure in breakers and attend to minor leaks in time * Donotattempt charging the suspected element * Controlling high voltage during restoration to avoid damage to equipments * In case of low battery condition during restoration (due to weak battery/long duration outage of power supply}, to avoid excessive power drain, only the essential load/communication channels to be kept in service Detall procedure for such actions has to be prepared and kept handy — by the concerned substation/generating station Survival Power: Ensuring availability of backup power supplies such as batteries, battery chargers, diesel sets to ensure supply to essential loads like air compressor for operation of circuit breakers, DC system for communication systems etc SRLOC Black Start Restoration Procedure 2013 3.8 General Guidelines: While each disturbance would be different and may require a different plan, nevertheless it would be useful to formulate general guidelines for the benefit of the load despatchers. These may be described as below: a} The operator at generating stations and sub-stations should have the knowledge of pre identified synchronising locations and pre laid down synchronising procedures. b} Switching procedure should be clearly laid down and periodically reviewed. ©) The transformer taps should be checked for desired setting to minimise voltage difference. d) The sub-stations operators and load despatchers should make a check of the capacitor banks and reactors in servi switching operations for voltage control & accordingly should cary out the ) _Energising of high voltage lines and cables should be avoided until enough generating capacity is available. f) Provision of islanding schemes area-wise, power station wise, and Unit wise would enhance the ability to restore faster. These shouldbe fully exploited 4g) Startup power to nuclear plants should be extended fast as poisoning of the reactors would delay restoration of nuclear units. hy Guidelines for decision making should be clear and should be delegated to all the major sub-stations and generating stations under varied conditions. i) Imparting training & providing necessary documentation to the load despatchers Note: The Restoration Procedure and sequence as given in document gives the general guidelines for restoring the system. However, as the exact conditions in case of each disturbance may be different and vary, the officer building up the system may take the action best suited for speedy Restoration of the system in real time. SRLDC 4.0 41 Black Start Restoration Procedure 2013 SOUTHERN REGION OVERVIEW This chapter explains the broad guidelines for restoring the system during Blackouts Procedure is split up in to four sections covering each Geographical area as detailed below Geographical Systems Covered Section Covering the Area Procedure Andhra Andhra Pradesh and NTPC, 5 Pradesh Ramagundam Karnataka Karnataka and Kaiga APP 6 Tamilnadu Tamil Nadu, Pondy, NLC and MAPS 7 Kerala Kerala and Rajeev Gandhi CCPP & Each state has been divided in to Subsystems on the basis of the natural separation taking place during disturbances. Source for providing start up powers has been identified for each Subsystem both from within the Subsystem and also from outside the Subsystem for early Restoration of the power system The details of subsystems are: ANDHRAPRADESH Andhrapradesh has been divided into three subsystems as mentioned below: ‘SUB SYSTEM - 1: The sub-system 1 comprises of major thermal stations viz. VIPS, Lanco , RYTPS, SEPL & MEPL and the important load centers ike Hyderabad, Vijayawada, Kurnool, Machilipatnam & Nellore along with Black Start faciities at Srisailem & N’Sagar, Jurala (iF Water Available) Hydro stations SRLDC 4.2 43 Black Start Restoration Procedure 2013 ‘SUB SYSTEM — ; The sub-system 2 comprises of Ramagundam Thermal power station, Kakatiya and the important load centers like Ramagundam loads & Western Region with No Black Start facilities in the Sub system SUB SYSTEM - 3: The sub-system 3 comprises of major thermal stations viz, KTPS, Simhadhi, & Gas Stations viz Jegrupadu, VGTS, Spectrum, Gowthami, Konaseema, GMR Vemagiri,Jegrupadu Extn and 8SES and the important load centers like Vizag, Kakinada along with Black Start facilities at U’Sileru, L’Sleru Hydro stations Synchronisation of Sub Systems: Once the individual subsystems are built to a stable level, the systems are synchronized with each other. The synchronization of subsystems will be done at the generating stations, preferably KARNATAKA Karnataka has been divided into two subsystems as mentioned below: ‘SUB SYSTEM - Sharavathi Tail Race {STRP), Jog, Varahi and Yelehanka (Diesel), UPCL. It includes major and The sub-system 1 comprises of Major Hydro Stations Viz. Sharavathi, important load centre like Bangalore, Mysore, Hoody, Peenya & Mangalore etc SUB SYSTEM - 2: The sub-system 2 comprises of Major Thermal Stations Viz. Raichur & Bellary and Major Hydro Stations Viz. Nagjheri, Kadra, Kodasalli & Almatti and Kaiga (Nuclear), Tata (Diesel) & Jindal (Corex). It includes major and important load centre like Hubli, Belgaum & Gulbarga ete. TAMIL NADU ‘Tamilnadu has been divided into three subsystems as mentioned below: SUB SYSTEM — The sub-system 1 comprises of major thermal station viz. TIPS, Kudankulam Atomic Power Station, Hydro stations like Periyar, Suruliyar, Papanasam, Servalar etc, Madurai Power Corporation Pvt, Ltd,, (Diesel Power Generating station), PENNA Power (Gas Power Generating Station) Valuthur GTPP and wind generation spread SRLDC 44 45 Black Start Restoration Procedure 2013 over southern part of Tamilnadu. The important load centers in this sub system include Tuticorin, Nagercoil, Tirunelveli & Madurai. This sub system has process industries like Sterlite and Space research centre at Mahendragirietc., INS Kattabomman Naval Centre, SUB SYSTEM - 2: The sub-system 2 comprises of ISGS station NLC (TS4 Expn, TS-ll, TS- I(€xpni} and major thermal station viz. NLC TS-1, MTPS, Hydro stations like Kundah, Pykara, Moyar etc, Gas Power Generating Stations like PP Nallur, ABAN, Kuttalam, Kovilkalappal, Diesel generating station at Samalpatti etc., in the coastal area of Tamil Nadu and wind generation at Udumalpet area. The important load centers in this sub system include Coimbatore, Tiruppur, Salem, Tanjore, Trichy & Hosur. Important Loads such as Traction at Trichy Murugupatty -Ambigapuram and Ariyalur-Koothur in Trichy area: SUB SYSTEM - 3: The sub-system 3 comprises of ISGS Nuclear station MAPS, major thermal stations viz. North Chennai, Vallur, Ennore, GMR Vasavi, Basin Bridge Gas Power Generating Stations, HITECH and TCPL etc., The important load centers in this sub system include Chennai and Arni. KERALA Kerala has been divided into two subsystems as detailed below: ‘SUB SYSTEM - 1: The sub-system 1 comprises of Kozhikode Diese! Generating Power Station (KDPP) and Kuttiadi Hydro Power Station in the northern part of Kerala. It includes the load centre like Nallalam, Areakode (Kozhikode), Kasarkode, Taliparamba, Kannur, etc., SUB SYSTEM - 2: The sub-system 2 comprises of Major Hydro Stations Viz, Idukki, Lower Periyar, Sabirigiri and RGCCPP Kayankulam (Naptha / Gas). includes major and important load centres like Trivandrum, Kalamassery, Pallam etc,, PROCEDURE DETAILS Source of startup power in case of Total Blackout of the Region, Blackout of the entire state system and Blackout of the Subsystem alone. ‘* Identifying the loads for each Subsystem. 10 SRLDC 46 Black Start Restoration Procedure 2013 ‘Points of synchronisation with other Subsystems. * Actions to be taken by various Generating Stationsand Substations. The procedures given in this document are general in nature and provide a guideline for the Restoration team depending on the availability of Transmission Elements, Generators and the Type and the extend of Blackout Restoration Team, on Real Time basis, should adopt the best procedure suited for the situation Based on this document Constituents have to prepare Station wise detailed switching instructions so that the Operators will have clarity and Restoration will be faster. GENRAL PRE RESTORATION REQUIREMENTS Whenever there is a total Blackout in a state / region, to facilitate early building up of the stable subsystems, the constituents should keep the UFRs & FGMO in by-passed condition during the restoration process. Also all the filter banks / capacitor banks should be in switched off condition during the restoration process " SRLOC Black Start Restoration Procedure 2013 POWER MAP OF ANDHRA PRADESH ee "a f K 7 if iff g A sig. [onli coils g romp |earenanipet ww ff |. if 4 Sup m ane WH ( ptheay Vi lB a ee fe A emsnces/ [onl ASF | enter |) ee a — rover abou oma x4) reac me J LM i ‘some sucuenoe LN froin 98 r 3a { TAMIL NADU oT TO SCALE NOVeniper 2012 SRLOC Black Start Restoration Procedure 2013 POWER MAP OF KARNATAKA SRLOC Black Start Restoration Procedure 2013 POWER MAP OF KERALA \TpKONAIE venese\ nm en Fropcet =. tog 1 a y eA Rr < 4 % > yreuounaurer / Toren None ae \ 4 eww SUB SYSTEM ‘OENERATING STATIONS 70 THIRUNELVELL i sadn ie moe ronan SY SRLOC Black Start Restoration Procedure 2013 POWER MAP OF TAMIL NADU LO OF SP KON ~TARAMAN B76 LINE S LL0 OF SP KOI TARAMAN DL of ‘ ow SUB-SYSTEM-3 Tonciione 10) post A grauvancn _ fh reverent ae et mamcasousiiy / SUB- svSTeM Doncanl 1 @ NEVVELL TS EXPANSION ae i TexPansion crap Jo Chee cue XI ox unos (Sr Towanda Prrwshaun ee _ & oo so t sowie g {oon une cae 422 Sy, rommmgan — % “* oo Foal ortonne sera aio a iN ) al To NOT To SCALE SELES) BANGALORE SRLOC Black Start Restoration Procedure 2013 POWER MAP OF SOUTHERN REGION 7 NOT TO SCALE, SRLOC k Start Restoration Procedure 2013 5.0 RESTORATION OF AP SYSTEM 5.1 SYSTEM OVERVIEW AP system c ded in to three sub systems, which cai brought up independently and synchronized subsequently on he system develops in to larger sustainable islands. 5.2 MAJOR GENERATING STATIONS. Following are the Major Generating Stations in the AP System st STATION TYPE SECTOR| SUB |CAPACITY| BLACK START No system| inmw | FACILITY 1 [RSTPS Thermal | |SGS 2 2600 | Not Available 2 |vTPs Thermal | State 1 1760 | Not Available 3 | LANCO Gas State 1 352 Not 4 | BSEs State | 3 220 | Not Available 5 | JEGURUPADU Gas State 3 216 Not Available 6 | SPECTRUM Gas 3 208 Not Available 7 |vaTP-1 Gas | State | 3 100 | Not Available 8 |VGTP-Il Gas | State | 3 172 | Available 9 |KTPS Thermal | State | 3 1720 | Not Available O | LOWER S| Hydro State 3 460 Available 11 | UPPER SILER Hydro | state | 3 240 | Available 12 | JURALA Hydro State 1 234 Available 13 | SIMHADRI Thermal | State | 3 1500 | Not Available 14 | SRISAILAM LB Hydro State 1 900 Available 15 | N'SAGAR Hydro | State | 1 816 | Available W7 SRL 5.3 k Start Restoration Pro 16 | SRISAILAM RB Hydro | State 770 Available 7 |RYTPS Thermal | State 1 1050 | Not Av 8 | KAKATIYA Thermal | State 3 500 | Not 9 | VEMAGIRI Gas State 3 370 | Not 20 | LKPPL Gas IPP 3 366 | Not Available 21 | JEGRUPADU GAS PP 3 220 | Not Available 22 | GAUTHAM GAS IPP 3 464 | Not Available 23 | KONASEEMA GAS IPP 3 444 | Not Ave 24 | GMR BARGE GAS PP 3 237 Available 25 | SEPL THERMAL | [PP 1 300 | Not Available 25 | MEPL THERMAL | IPP 1 150 | Not LIST OF SUB-STATIONS WITH SYNCHRONISING FACILITY SYNCHRONISING SI.No. SUB STATION FACILITY YESINO T | 220KV Mydukur YES 2 220KV Kondapalli YES 3 | 220KV Gooty YES 4 | 220KV Nunna YES 5 | 220KV Garividi YES 6 | 220KV Markapur YES 7 | 220KV Ongole YES 8 | 220KV Somay YES 9 | 220KV Thal YES 10 | 220KV Mal YES 222 KV Shapurnagar YES 12 [222KV Dind YES 13 [220KV Miryalaguda YES Ire 2013 18 SRLDC 5.4 Black Start Restoration Procedure 2013 SI.No. | SUB STATION SYNCHRONISING FACILITY YES/NO 14 |220KV Budidampadu’ YES. 15 | 220KV Dichpalli YES 16 | 220KV Kalwakurthy YES 17 | 220KV Tadikonda YES. 18 [220KV Bommuru YES 19 | 220KV Nidadavole YES: 20 | 220KV Podili YES 21 | 220KV Chandrayanguita YES: 22 | 220 KV Bhongiri YES 23 | 220 KV Narketpalli YES 24 [220 KV SamarlakotalPeddpuram) YES: 22 | ALL AQ0KV Stations in AP YES. IMPORTANT CONNECTIONS OF AP SYSTEM 5.4.1 WITH OTHER REGION With Western Region: = HVDC Back to Back Station at Chandrapur (Bhadrawathi) with A/C by-pass arrangement and 400kV Chandrapur ~ Ramagundam D/C With Eastern Region: HVDC Back to Back Station at Gajuwaka with A/C by pass arrangement and 400kV Jeypore ~ Gajuwaka D/C 5.4.2 220kV Barasur ~ Lower Sileru and 220kV Balimela - Upper Sileru lines are not in use WITHIN THE REGION A. With Karnataka: a} 400kV 5/C Gooty - Somanahally b} 400kV S/C Gooty ~ Neelamangala ¢) 400kV D/C Gooty - Raichur d) 400kV S/C Mehaboobnagar ~ Raichur e) 400kV S/C Kadapa - Kolar 19 SRLDC 5.5 Black Start Restoration Procedure 2013 f) 220kV S/C Gooty ~ Regulapadu -Alipur (Bellary) 4) 220kV S/C Tandur - Sedam B. With Tamil Nadu a} AOOkY S/C Chittoor - Sriperumpudur b) 400kV D/C Nellore - Alamathy ©) 220kV S/C Sulurpet - Gummidipoondi d) 220KV S/C Chittoor - Thiruvalam ‘SUB SYSTEM DEMARCATION SUB SYSTEM - 1: The sub-system 1 comprises of major thermal stations viz. VIPS, Lanco, RYTPS, SEPL & MEPL and the important load centers like Hyderabad, Vijayawada, Kurnool, Machilipatnam & Nellore along with Black Start factities at Srisailm & N’Sagar, Jurala (iF Water Available) Hydro stations SUB SYSTEM - 2: The sub-system 2 comprises of Ramagundam Thermal power station, Kakatiya and the important load centers like Ramagundam loads & Western Region with No Black Start facilities in the Sub system, SUB SYSTEM - 3: The sub-system 3 comprises of major thermal stations viz. KTPS, Simhadri, & Gas Stations viz Jegrupadu, VGTS, Spectrum, Gowthami, Konaseema, GMR Vemagiri,Jegrupadu Extn and 8SES and the important load centers like Vizag, Kakinada along with Black Start facilities at U’Sileru, L’Sleru Hydro stations ‘Synchronisation of Sub Systems: Once the individual subsystems are built to a stable level, the systems are synchronized with each other. The synchronization of subsystems will be done at the generating stations, preferably. IMPORTANT Criteria for deciding Restoration approach in AP System. SURVIVAL of Ramagundam islanding scheme is the most important criteria in deciding Restoration approach of AP system during total black out condition. 20 k Start Restoration Procedure 2013 If the Ramagundam islanding scheme successfully survives, then it is practically NOT possible to connect with WR through AC by-pass at HVDC Badravathi. If the Ramagundam-Hyderabad Island of approximately 1800 MW acts (47.8 Hz with 200ms delay}, the System Operator has to restore the Island as quickly as possible as there are no hydro generators in this Island and Ramagundam units have limited bandwidth to flex generation as required by the loads. The System Operator at AP SLDC would endeavor to closely match loads to Ramagundam Generation at all times. The Restoration procedure would now focus onsynchronising this Island with N’Sagar-Srisailam island that may have to be built up from black start. In case rest of AP/SR survives the Ramagundam-Hyderabad Island can be quickly synchronised with rest of AP/SR system by flexing the generation at N’Sagara Srisailam complex. In case rest of AP/SR does not survive, N’Sagar- units would be self-started with minimum loads(KM Palli) and supply would be extended to Talapalli. Simultaneously units at Srisailam (RB) would be started up and synchronised with N’Sagar units. Loads would be extended by closing Srisailam-Mydukur line and afterwards extending the same to Cuddapah-Chinakampalli-Muddanur for starting up of units. Srisailam (LB) would be started up and power extended to Kurnool. Meanwhile the N'Sagar-Srisailam(RB) complex would extend supply to Kurnool and synchronise with Srisailam(LB) at Kurnool. After the island has reached 700-1000 MW, the 400 kV Talapalli-Hyderabad line would be usedto synchronise Ramagundam-Hyderabad island with Srisailam-N’Sagar island. The Kurnool-Hyderabad 400 kV would also be closed to strengthen the link. Only incase Ramagundam island failed to survive, it can be connected to WR through AC by-pass at Ramagundam for availing start-up power to NTPC Ramagundam. 2 SRLOC Black Start Restoration Procedure 2013 POWER MAP OF ANDHRA PRADESH cae : Se nO eee? nee ~~ INS ann ca, a I yed a pa ! spamit NADU . Seo. SRLDC, BANGALORE DT TO SCALE NOVEMBER 2012 22 SRLDC Black Start Restoration Procedure 2013 5.6RESTORATION OF SUB SYSTEM 1 The sub-system 1 comprises of major thermal stations viz, VIPS, LANCO, RYTPS, SEPL & MEPL and the important load centers like Hyderabad, Vijayawada, Kurnool, Machilipatnam & Nellore along with Black Start facilities at Srisailm & N’Sagar Hydro stations 5.6.1 AVAILING START-UP POWER This subsystem can avail start up power supply from the following sources A. During Total Regional Blackout and / or Total Blackout of AP system = Self-start N'Sagar and avail startup power from N’Sagar through 220kV N'sagar - Tallapalli to VIPS, VIPS U#7 & to Lanco via VTPS-Kondapalli- Lanco & to Lanco(ISGS) via VTPS-Nunna-Lanco4 = Self-start Srisailam RB and avail startup power from Srisailam RB through ‘Mydukur ~ Kadapa ~ Chinkampally - Muddanurto RYTPS, = Extend startup power from Srisailam RB to SEPL/ MEPL Srisailam RB - Markapur-Podili/Ongole -Nellore 220 - Nellore 400 - SEPL/MEPL = Synchronise 220kV Srisailam - N'Sagar . During Blackout of Sub system 1 alone = From KTPS through 220kV KTPS - Nunna - VIPS, VIPS U7 & & to Lanco via VTPS-Kondapalli-Lanco & to Lanco(ISGS) via VTPS-Nunna-Lanco4 = From Vijjeswaram/Shimadri through Bommur - Vijjeswaram stagel - Bhimadole- Nunna ~ VIPS & & to Lanco via VIPS-Kondapalli-Lanco & to LancofISGS) via VIPS-Nunna-Lanco4 = Self-starting of Hydro systems of Srisailam ~ N’Sagar and through 220kV N'Sagar ~ Srisailam RB - Mydukur - Kadapa ~ Chinkarpally ~ Muddanur to RYTPS = Extending startup power from Srisallam RB to SEPL’ MEPL Srisallam RB Markapur-Podili/Ongole Nellore 220 ~ Nellore 400~SEPL/MEPL = From TN System through 400kV Almatty ~ Nellore- SEPL/MEPL 23 SRLDC Black Start Restoration Procedure 2013 From TN System through 400kV Sriperumpudur ~ Chittoor - Kadapa & 220KV Kadapa - RYTPS From Karnataka System through 400kV Kolar ~ Kadapa & 220kV Kadapa — RYTPS From Karnataka System through 400kV RTPS - Mahboobnagar - N'Sagar Through 220kV Tandur - Sedam line Through 220kV Gooty -Regulapadu- Bellary (Alipur} line 5.6.2 RESTORATION OF THE SUBSYSTEM 1 DURING TOTAL BLACKOUT OF AP. ‘SYSTEM. This subsystem will be developed after availing statup power supply as mentioned in 5.6.1 (A). The restoration process is as follows: fa) (f) (g) Self-start one unit at N'Sagar with 90 MW generation while supplying loads at N'Sagar (60 MW) local loads and extend startup supply to VTS via 220kV S/C Talapalli line. Self-start one unit at Srisailam RB with local loads of 20 MW & Simultaneously, syncronise Srisailam-N Sagar. Extend supply to RYTPP via 220kV Mydukur (20MW) - Kadapa (30MW) - Chinkampally -Muddanur (30MW}. Simultaneously start two units at Srisailam RB and increase the generation to meet the loads Extend start up supply to VIPS Us? from VTS 220kV Extend supply to SEPL/MEPL via 220kV Markapur(10MW) - Podili/Ongole (IOMW) ~ 220kv Nellore (1OMW) - 400ky Nellore. Extend startup power to LANCO through 220kV VIS - Kondapalli line. Extend supply to Chandrayengutta via Dindi and supply to important loads at Hyderabad If Self-start of Srisailam LB is not available then Extend supply from Srisailam RB to 220kV { AP Carbide) Kurnool {100MW). via Somayajulapalli and Extend supply from Chandrayangutta to Mamidapally. 24 SRLDC ti) i) Black Start Restoration Procedure 2013 If self-start of Srisailam LB is available then Self-start Stisailam LB & extend to Kurnool 400 kV and supply important loads. Simultaneously charge 400 kV Srisailam-Mamidapally line and supply to importantloads at hyderabad. Self-Start Jurala (if water available) and extend to dindi via Mehboobnagar- Boothpur-Kalvakurthi for synchronization at dindi Extend startup power to LANCO (ISGS} through 220kV VTS - 220KV Nunna 400kv Nunna -line. Extend supply to Khamam from N’Sagar & Energise Khamam 400 KV. The subsystem 1 is developed by gradually increasing the generation in the subsystem and extending supply to loads of Podili, Tadikonda, Gunadala, Nunna, Hyderabad This subsystem 1 can be synchronised with subsystem 3 at KTS through 220kV D/C KTS-Khamam line. Subsequently 400 kV Nunna - Khammam, Nunna -Srisailam, Mamidapalli - Gheanaput, N’Sagar - Khammam would be taken up whenever voltage permits, Warangal 400 kV would be energized Sub System 2 & rest of A.P would be synchronized at Ramagundam through 400 kV Ramagundam - Warangal / Khammam line after matching the frequency of both subsystems. AP Hydro would be flexed to mi mize flow on Ramagundam - Chandrapur line & subsequently this would be tripped. 25 Black Start Restoration Procedure 2013 SRLDC and. jueuy weindewuiny cil [ ereavnava) wous | e825 H pppeoeus | wrvavnat | iwNwoua ‘p04 epeHl poieet— (EMBLAS SS wou) ‘Ayeyeuewos, 210pe FF gosue edepey IIMA I’VIS 4173S HS30Vud VUHONV uoReISanS ae wewioul "@. 2 ese 26 SRLDC Black Start Restoration Procedure 2013 5.6.3 ACTIONS TO BE TAKEN BY VARIOUS GENERATING STATIONS OF AP IN RESTORING SUBSYSTEM 1 DURING TOTAL REGIONAL BLACKOUT AND / OR BLACKOUT OF ENTIRE AP SYSTEM (a) AtN’SAGAR: = Ascertain the Total Blackout in AP System or Southern Region. = Open all the lines connected to N’Sagar, = Self-start one unit at N'Sagar with 90 MW generation while supplying loads at N'Sagar (60 MW) and extend startup supply to VTS via 220kV S/C Talapalli line "= Co-ordinate with Srisailam RBPH and synchronise N’Sagar - Srisailam RBPH lines with gradual increase of generation in line to connected loads in the part system = After stable operation of subsystem 1 with generation of N'Sagar, Srisailam, VTS and RYTPS and connected load and synchronization of Srisailam ~ Kurnool 400kV line, Synchronise the N’Sagar ~ Khammam 400kV line (b) At TALLAPALLY: * Keep 220KV Tallapally - VTS line in open condition = After getting energized the 220kV bus through N’Sagar ~ Tallapally line, extend supply to VIS by synchronizing 220kV Tallapally - VTS line = Connect the Loads at Tallapally area (o) AtVTS: = Ascertain the Total Blackout in AP System or Southern Region. = Openall the lines connected to VIS = After getting energized the 220KV bus at VTS through 220kV Tallapally-VI'S ling, extend the supply to unit auxiliary/station supply. = Extend startup power to VTS-VI via 220 kV = Charge 220kV VTS - Kondapally line and extend startup power to LANCO. 27 SRLDC Black Start Restoration Procedure 2013 = Charge 220kV VTS - Nunna line and extend startup power to LANCO(ISGS} via 400KV Nunna. = Charge 220kV VTS - Nunna- 8himadolu line and connect the loads as per the level of generation (d) At SRISAILAM RBPH: = Ascertain the Total Blackout in AP System or Southern Region. = Open all the lines connected to Srisallam RBPH = Self-start one unit of Srisailam RBPH with local loads of 20 MW and simultaneously Synchronise 220k Srisailam RBPH ~ N'Sagar = Extend supply to Mydukur through 220kV Srisailam RBPH -Mydukur line = Extend Supply to Dindi through 220kV Srisailam RBPH = Dindi line and request for connecting loads at Dindi = Extend supply to YG Palem through 220kV Srisailam RBPH ~ Dornala and request Dornala to connect loads = Extend supply to Podli through 220kV Srisailam RBPH ~ Podli line and request Podli to connect loads with gradual increa in generation. (e) At DINDI: = Ascertain the Total Blackout in AP System or Southern Region = Open all the lines connected to Dindi = Avail supply from Srisailam RBPH and charge the 220kV bus. = Extend supply to CH gutta in consultation with SLDC regarding Ramagundam island status = Avail supply from Kalwakurthy and synchronise (f) At CHANDRAYANGUTTA: = Ascertain the Total Blackout in AP System or Southern Region = Open all the lines connected to CH gutta in consultation with SLDC regarding status of Ramagundam island 28 SRLDC Black Start Restoration Procedure 2013 = Avail supply from Dindi and charge the 220kV bus. = Connect the local loads = Extend supply to Jublice Hills through 132kV line = Charge / Synchronise the Mamidipally 220kV line asper direction of SLOC (g) At SRISAILAM LBPH: = Ascertain the Total Blackout in AP System or Southern Region = Openall the lines connected to Srisailam LBPH © Self-start unit at Srisailam LBPH unit = Charge 400kV Srisailam LBPH ~ Karnool line and request to connect the local loads at Karnool = Start other units one by one with gradual increase in load at Kurnool and Voltage profile around 400kV. = Controlling the voltage at Srisailam LBPH around 4cOkV, charge 400kV Srisailam LBPH - Mamidipally line and request to connect the loads at Mamidipally in consultation with SLOC regarding Ramagundam island status. (h) At MAMIDIPALLY: = Ascertain the Total Blackout in AP System or Southern Region. = Openall the lines connected to Mamidipally = Avail supply through 400kY Srisailam LBPH ~ Mamidipally line or 220kV CH gutta ~ Mamidipally line in consultation with SLDC regarding Ramagundam island status. = Connect the local loads at Mamidipally = Charge / Synchronise the other line as per direction of SLO (i) At MYDUKUR: = Ascertain the Total Blackout in AP System or Southern Region = Openall the lines connected to Mydukur 29 SRLOC Black Start Restoration Procedure 2013 = Avail supply through Srisailam RBPH and energise the 220kKV bus at Mydukur, = Connect the local loads at Mydukur = Extend supply to Kadapa (j) At KADAPA (220kV): = Ascertain the Total Blackout in AP System or Southern Region Open all the lines connected to Kadapa Avail supply from Mydukur and energise the 220kV bus at Kadapa Connect the local loads at Kadapa = Extend supply to Chinakampalli (k) At CHINAKAMPALLI: = Ascertain the Total Blackout in AP System or Southern Region. * Openall the lines connected to Chinakampalli = Avail supply from Kadapa and energise the 220KV bus at Chinekampall = Connect the local loads at Chinakampalli = Extend supply to RYTPP = Charge / Synchronise Chinakampalli - Renigunta 220KV line (I) Action at RYTPP: = Openall the lines = Avail Start up supply from - Chinkampally ( NSagar / S'Sailem/ Kolar - Kadapa / $'P Budur- Chittor- Kadapa) or - Ananthpur ( Through Nelamangala / Hoody ~ Gooty 400kV Line } = Start the generation at RYTPP and Synchronise, = Extend supply to Yeraguntala and request for connecting local loads at Yeraguntala 30 SRLOC Black Start Restoration Procedure 2013 (m) AtPODLI: = Ascertain the Total Blackout in AP System or Southern Region = Open all the lines connected to Podli = Avail supply through Srisailam RBPH and energise the 220kV bus at Podli = Connect the local loads at Podli = Extend supply to Ongole for Traction Supply = Extend Supply to Nellore for Traction Supply (n) AtONGOLE: = Ascertain the Total Blackout in AP System or Southern Region = Openall the lines connected to Ongole = Avail supply from Podli and energise the 220kV busat Ongole. = Connect the Traction loads & local loads at Ongole = Charge / Synchronise 220kV Ongole - Nellore line in consultation with Nellore 220kV S/S (0) AtNELLORE: = Ascertain the Total Blackout in AP System or Southern Region = Openall the lines connected to Nellore = Avail supply from Podli / Ongole and energise the 200kV bus at Nellore. = Charge Nellore 400kV & Extend startup power to SEP/MEPL Connect the Traction loads & local loads at Nellore = Extend supply to Manubolu and Sullurpet = Charge / Synchronise 220kV Nellore ~ Manubolu line (p) AtRENIGUNTA: = Ascertain the Total Blackout in AP System or Southern Region. = Open all the lines connected to Renigunta 3 SRLDC Black Start Restoration Procedure 2013 = Avail supply from Manubolu / Chinakampalli and energise the 220kV bus at Renigunta * Connect the Traction loads & local loads at Renigunta = Extend supply to 220kV Chittor through 220kV Mahadeva Mangalam and request to connect local loads = Charge / Synchronise 220kV Nellore / Chinakampalli feeders as the case may be (q) At CHELLAKURTHY: (r) = Ascertain the Total Blackout in AP System or Southern Region Open all the lines connected to Chalakurthy Avail supply from N’Sagar and charge the 220kV bus, Connect the local loads Extend supply to Miryalguda & KM Palli At MIRYALGUDA: = Ascertain the Total Blackout in AP System or Southern Region = Open all the lines connected to Miryalguda = Avail supply from Chellakurthy and charge the 220kV bus. = Connect the local loads = Bxtend supply to Khammam 32 SRLOC Black Start Restoration Procedure 2013 (s) AtKHAMMAM: = Ascertain the Total Blackout in AP System or Southern Region. = Open all the lines connected to Khammam = Avail supply from Miryalguda and charge the 220kV bus. = Connect the local loads = Charge the 400 / 220kV ICT and energise the 400kV bus = Wait for the instruction of SLDC / RLDC for synchronizing the 400kV lines. (t) AtLanco(ISGs) : = Ascertain the Total Blackout in AP System or Southern Region = Open all the outgoing lines = Avail start up supply from Vijaywada 400k after getting clearance from RLDC (u) At SEPL/MEPL: = Ascertain the Total Blackout in AP System or Southern Region = Open all the outgoing lines = Avail start up supply from Nellore 400kV after getting clearance from RLOC 5.6.4 PROCEDURE FOR AVAILING STARTUP POWER DURING PARTIALBLACKOUT OF SUB-SYSTEM - 1 ALONE As already explained earlier in clause 5.6.1 (B), during the restoration of Subsystem 1 alone start up power can be availed from other subsystems through * From KTPS through 220kV KTPS ~ Nunna-VTPS. * From Vijjeswaram/Shimadri through Bommur - Vijjeswaram stagel — Bhimadole- VIPS. 33 SRLDC 5.7 Black Start Restoration Procedure 2013 + Self-starting of Hydro systems of Srisailam - N’Sagar and through 220kV N'Sagar ~ Srisailam RB - Mydukur ~ Kadapa ~ Chinkampally - Muddanur to RYTPS * From TN System through 400kV Sriperumpudur ~ Chittoor ~ Kadapa & 220kV Kadapa -RYTPS * From Karnataka System through 400kV Kolar ~ Kadapa & 220kV Kadapa ~ RYTPS "From Karnataka System through 400kV Neelamangala - Gooty / Sommanahally - Gooty & 220kV Gooty ~ Ananthapur~ Muddanur- RYTPS + Extending startup power from Srisailam RB to SEPL/ MEPL Srisailam RB - Markapur-Podili/Ongole -Nellore 220 ~ Nellore 400 - SEPL/MEPL + From TN System through 400kV Almatty ~ Nellore- SEPL/MEPL + From Srisailam & N’Sagar complexas explained in clause 5.6.1 (A) + After startup power is available for VIPS & RYTPS, further extend for restoration of this sub-system may be initiated as explained in 5.6.2 & 5.6.2.1 above RESTORATION OF SUB SYSTEM - 2 The sub-system 2 comprises of Ramagundam & Kakatiya Thermal power station and the important load centers like Ramagundam loads & Western Region with No Black Start facilities in the Sub system 5.7.1 AVAILING START-UP POWER Presently this subsystem has an islanding scheme for NTPC Ramagundam along with Hyderabad loads. Incase of survival of this subsystem in islanding mode, the island could not be connected to WR through AC by-pass at HVDC Badravathi as the frequency of WR and surviving island would be different and flexing generation J loads of the surviving island for matching to WR frequency may be very difficult and may lead to collapse. Also, attempt to avail support through Badrawathi HVDC Back-to-Back by synchronizing Ramagundam ~ Chandrapur lines, with out building the island to sufficiently large size, is not preferable due to low short circuit level at HVDC Badrawathi. Under such situation, the surviving island has to be 34 SRLDC Black Start Restoration Procedure 2013 synchronized with rest of AP at the earliest possible with increase in hydro generation along with matching loads in other subsystems of AP. Incase, the islanding scheme could not survivie, then, this subsystem can avail start up power supply from the following sources 35 SRLDC Black Start Restoration Procedure 2013 A. During Total Regional Blackout and / or Total Blackout of AP system From Western Region through HVDC Back to Back station at Bhadrawati (Chandrapur) with A/C bypass arrangement and 400kV Chandrapur- Ramagundam D/C. line From Subsystem 1 by availing self-starting facility of hydro units at N’sagar / Srisailam complex B. During Blackout of Sub system 2 alone From TPS through 220 kV KTPS - Khammam - Warangal-Nagaram- Malayalapalli-Ramagundam From 220Kv N’Sagar ~ Chellakurthi ~ Miryalguda ~ Khammam ~ Warangal ~ Ramagundam lines From KTPS Sth Stage through 220 kV KTPS- Budidampadu (Khammam 400 kV} 400 kV Khammam -Ramagundam line From VIPS through 220 KV VIPS-Nunna & 400 kV Vijayawada-Khammam-Ramagundam From Srisailam, N’sagar Hydro complex through 220 kV N’sagar - Tallapalli 400 kV N'sagar- Ramagunadam 5.7.2. RESTORATION OF THE SUBSYSTEM 2 DURING TOTAL BLACKOUT OF AP. ‘SYSTEM. This subsystem will be developed after availing startup power supply as mentioned in 5.7.1 (A). The restoration process is as follows: 1. Extend startup supply to Ramagundam & Kakatiya from Western region through Chandrapur A.C bypass link, following procedure asfollows {a}. Ensure that line breakers of 400 kV Ramagundam-Chandrapur lines | and II are opened at Ramagundam & Chandrapur end 36 SRLDC Black Start Restoration Procedure 2013 (b) Ensure that HVDC system is isolated from both West and South Bus. (c)_ Ensure that all filter |solators are opened. (d} Ensure that West Bus 2 is in energized condition (e) Close A/C bypass link isolators (f) Close breaker of Ramagundam line | or Il in consultation with Ramagundam. This would extend start up power to Ramagundam. (g)_ In case the bus voltage at Ramagundam is very high, request AP to avail some loads radially to control the voltage. {h) Extend startup supply to Kakatiya vie 400kv Ramagundam ~ Warrangal- Bhoopalpally alternately via 220kv Malayalapalli-220 kv Nagaram- 220 kv Warrangal -400kv Warrangal (i) Ramagundam would build up the generation gradually with load through ICTs at Ramagundam The subsystem 2 is developed by gradually increasing the generation in the Ramagundam and extending supply to loads of Ramagundam, Sub System 2 & rest of A.P would be synchronized at Ramagundam through 400 kV Ramagundam - Warangal / Khammam line after matching the frequency of both subsystems. AP Hydro would be flexed to mit ize flow below 20MW on Ramagundam - Chandrapur line & subsequently this would be tripped. 2. Incase of any difficulties in extending startup supply to Ramagundam from Western region through Chandrapur A.C bypass link, avail startup power from N'Sagar Complex through 400kV N’sagar - Hyderabad - Ramagundam lines along with loads at Hyderabad for controlling the voltage profile. 37 Black Start Restoration Procedure 2013 SRLDC Ape ssuswowpuss eis vas 01 vows Yy, ora0x3] WAVAVEQVHE —yolosu NUZLSaM POU PHEW (.NOOVIE W101) VALLVWH 3 NVONNOVIVA Z WALSAS-ENS VALLYMVM GNV WVONNOVINVa OdLN YO4 YIMOd dn Luvis LuVLS 4138 HSaqvud VUHGONY Black Start Restoration Procedure 2013 SRLDC envamovave TRVaNnOWNYH vo nasy 39 SRLDC Black Start Restoration Procedure 2013 5.7.3, ACTIONS TO BE TAKEN BY VARIOUS GENERATING STATIONS AND HVDC OF AP IN RESTORING SUBSYSTEM 2 DURING TOTAL REGIONAL BLACKOUT AND / OR BLACKOUT OF ENTIRE AP SYSTEM & NON-SURVIVAL OF RAMAGUNDAM ISLANDING SCHEME. (a) (b) {c) Actions by HVDC Bhadrawati Upon receipt of request from Ramagundam for providing start up power Bhadrawati will make the following arrangements to extend the start up power. = Ensure that line breakers of 400 kV Ramagundam-Chandrapur lines | and Il are opened at Ramagundam & Chandrapur ends = Ensure that HVDC system is isolated from both West and South Bus. = Ensure that all filter Isolators are opened = Ensure that West Bus 2 is in energized condition = Close A/C bypass link isolators = Close breaker of Ramagundam line | or Il in consultation with Ramagundam = This would extend start up power to Ramagundam STPS & Kakatiya Actions by RSTPS = Ensure all 400 kV line breakers open at Ramagundam end. = Avail start up supply from HVDC station at Bhadrawati through one of the circuits of 400kV Ramagundam-Chandrapur line for starting the unit. = In case the bus voltage at Ramagundam is very high, request AP to avail some loads radially to control the voltage = Extend start up supply to Kekatiye via Warrangal-Bhoopalpally = Ramagundam would build up the generation gradually with load through ICTs at Ramagundam Actions by KAKATIYA 40 SRLDC 5.7.4 Black Start Restoration Procedure 2013 = Open all 400 kV line breakers. = Avail start up supply from Ramagundam via 400kv Warangal in consultation with SLDC. = Kakatiya would build up the generation (d) Actions By APLD = Provide the loads for Ramagundam generators through ICTs at Ramagundam in coordination with RSTPS. * Loads to be regulated keeping in view the level of generation at Ramagundam and import constraints as per the directions of SRLOC Note: SRLDC/WALDC Control Room, Ramagundam and Bhadrawati HVDC stations shall endeavor to confirm the actions to be taken in the event of Total Black-out in the AP system. However, extension of WR power to Ramagundam shall be carried out at the request of Ramagundam without waiting for any code from SRLOC JWRLOC except that before extending the supply, Bhadrawati shall interact with Ramagundam and obtain clearance from Ramagundam for its readiness to avail the power supply. PROCEDURE FOR AVAILING STARTUP POWER SUPPLY FROM WITH IN AP SYSTEM In the event of difficulty in availing WR supply for any reason, the alternate source for availing start up power to Ramagundam & Kakatiya would be from N'sagar or Srisailam Hydel power stations In this case the following steps would be followed. (a) Supply from N'sagar or Stisailam power house would be extended to Tallapally. (b) 220 kV supply from Tallapally would be extended and stepped up to 400 kV by charging one of 220/400 kV 315 MVA transformers at 400 kV N’sagar sub station. (©) Before extending 400 kV supply fram N’sagar to Ramagundam, the voltage at N'sagar would be controlled by utilising bus reactor, line reactor provided at a SRLDC 5.7.5 Black Start Restoration Procedure 2013 both ends of 400 kV N'sagar-Ramagundam line and if required by varying ICT taps at N’sagar In case 400 kV voltage at N’sagar is not brought under control by using reactors and ICT taps at N’sagar, 400 kV supply from N’sagar should be extended to Hyderabad and voltage at Hyderabad could be controlled by connecting loads through ICT at Hyderabad. Supply to Ramagundam can be extended by charging one of the 400 kV lines from Hyderabad to Ramagundam and NTPC can avail start up power by charging Ramagundam bus Once Startup is given to Ramagundam, Then extend start up power from to Kakatiya as explained above SYNCHRONISING SUBSYSTEM - 2 (RAMAGUNDAM & KAKATIYA) WITH REST OF A.P AND OPENING OF AC BY-PASS LINK WITH WR ‘As the Subsystem 2 builds up it has to be synchronised with rest of AP at the earliest opportunity to increase the stability of the\ grid. This Subsystem can be synchronised with rest of AP by closing 400 kV Warangal / Khammam - Ramagundam line. Tying of subsystem to be done preferably at 400 KV level only. Once the Northern part of AP grid is adequately strengthened and stabilised, RLOC shall request WRLOC to withdraw the assistance from WR. The following steps shall then be taken to open out the AC bypass link at HVDC Bhadrawati, After the AP system develops into a stable island of about 2500 to 3000MW, AIC inter connection with WR will be opened out only after reducing the flow on the interconnection to a minimum value by adjusting the load generation balance in AP Subsystem Load in AP system would be regulated to bring down the flow on 400 kV Ramagundam-Chandrapur line as minimum as possible (10 to 20 MW) by regulating generation at N’sagar, Srisailam and Chandrapur (WR) NTPC would then manually open 400 kV Ramagundam-Chandrapur line to separate part SR system from WR system in consultation with SRLDC / Bhadrawati 42 SRLDC 5.7.6 Black Start Restoration Procedure 2013 Opening of A/C Bypass Link At Bhadrawati: + Bhadrawati shall obtain permission from WRLOC and SRLDC to open out the AIC bypass link, * Breaker controlling Ramagundam | and |i lines shall be opened. * Open breaker of MSEB-2 controlling West Bus-2, * Check that West Bus and South Bus is dead * Open A/C bypass link isolators = Prepare the HVDC station for operation in Back to Back Convertor mode and then await instructions and code exchange between WRLDC and SRLDC. PROCEDURE FOR AVAILING STARTUP POWER DURING PARTIAL BLACKOUT OF ‘SUB-SYSTEM - 2 In the event of Partial Black out in AP system and Subsystem 2 alone going into black out startup power for Subsystem 2 will be made available fram any one of the neighboring Subsystem in AP and the procedure is detailed below A. From KHAMMAM ® Charge 400 kV Ramagundam ~ Warangal / Khammam line at Warangal / Khammam * Charge 400 kV Switchyard at Ramagundam and avail start up power B. From WARANGAL * Charge 220 kV Warangal-Nagaram-Malayalpalli switching substation * Charge 220 kV Malayalpalli-Ramagundam line-1 or line-2 or line-3 = Charge 220 kV/400 kV Auto Transformer-3, 4 or 5 and avail start up power supply C. From N’SAGAR /SRISAILAM Hydro Complex 43 SRLOC Black Start Restoration Procedure 2013 * Procedure as detailed in section 5.7.4 In case of Sucessful Islanding of Ramagundam- Hyderabad Scheme Sub System 2 & rest of A.P would be synchronized at 400kV Ghanapur— N’Sagar at N’Sagar End and 400kV Ramagundam - Warrangal - Khamam at Ramagundamend. aa 2013 Black Start Restoration Procedure SRLDC er (Un0yOV1G TWHLAVa) VALLUNUN # S4LsuZNaISASENS VALLVMV & WVGNNOVNVE OdiN YOd HaMOd an Lavis AMVLS 4135 HS30Vad VUHONV SRLOC Black Start Restoration Procedure 2013 5.8 RESTORATION OF SUB SYSTEM 3 The sub-system 3 comprises of major thermal stations viz. KTPS, Simhadri & Gas Stations viz Jegrupadu, VGTS-2, Spectrum and BSES and the important load centers like Vizag, Kakinada along with Black Start facilities at U'Sileru, L’Sileru , Donkerai Hydro stations, Vijjeswaram stage gas Station. 5.8.1 AVAILING START-UP POWER To restore this Subsystem Startup power can be availed from the following: A. During Total Regional Blackout and / or Total Blackout of AP system = From Eastern Region through HVDC Back to Back station at Gazuwaka with AVC bypass arrangement and 400kV Gazuwaka - Jeypore D/C, line (First Option) * From Lower Sileru, Upper Sileru & Donkarai hydro units through © 220kV LSileru - Donkerai - U.Sileru — Pendurthy - Gazuwaka & 400kV Gazuwaka - Simhadri (Gazuwaka ~ Kalpakka - Simhadri line will be used as alternate path instead of Gazuwaka - Simhadri} © From Lower Sileru to KTPS © From Lower Sileru - 220KV KTPS ~ 220 KV Khammam-400kV Khamam — KTPS VI = From GMR Barge units through © From GMB Barge to PO Puram - BSES * From GMR Barge to Bommur - 220KV Vemagiri - 400kV Vemagir ~ Vemagiri gas complex B. During Blackout of Sub system 3 alone * From LSileru/U.Sileru / Donkarai as detailed in 5.8.1 (A) = From GMR Barge as detailed in 5.8.1 (Aj * From Subsystem 1 through 46 SRLDC Black Start Restoration Procedure 2013 © 220kV N'Sagar~ Chellakurthi- Miryalguda ~ Khammam lines © 220kV VTS -NUNNA- Bhimadole- Vijjeswaram stagel - Bommur — Peddapuram - Parwada -Gazuwaka & 400kV Gazuwaka-Kalpakka- Simhadri © 220KV VTS ~ KV Kota - Vijjeswaram stage2 ~ Bommur ~ Peddapuram — Parwada ~ Gazuwaka & 400k Gazuwaka - Kalpakka ~ Simhadri © 220kV Vijjeswaram stage1 - Bommur - L Siler ~ KTPS & KTPS VI 5.8.2 RESTORATION PROCESS FOR SUBSYSTEM 3 DURING TOTAL BLACKOUT OF AP SYSTEM 5.8.2.1 In case of total blackout of AP System a) d) The First option for Simhadri startup is through AC Bypass of Gazuwaka HVDC & Extending ER Supply to Simhadri. On exercising this option, Start-up supply to be extended to Vemagiri complex through Gajuwaka ~ Parwada — Peddapuram ~ Bommur 220kV lines or Gajuwaka ~ Pendurithi ~ U.Sileru ~ Donkarai ~ LSileru - Bommur 220kV lines. Subsequently, builtup an island with Simhadri, Vemagiri Complex & Sileru generation along with matching loads at Vizag, Pendurithi, Bommur etc to an extend of 1000M\Y ~ 1500MW. After building-up the island, flexing the Sileru hydro generaion, delink the island from N-EW grid at HVDC Gajuwaka by tripping the 400kV AC inter connector feeder to Gajuwaka ICT. Alternately, Self-start Lower Sileru and extend startup supply (20MW) to KTPS. through 220kV L Sileru - KTPS line Extend start up supply to KTPS VI from 220KV KTPS ~ 220 KV Khammam- 400k Khamam - KTPS VI as the first option. 400kY Ramagundam ~ 400kV Warrangal - 400kV Khammam ~ 400kV KTS VI will be second option if voltage permits Simultaneously startup Upper Sileru and extend 220ky supply to Gazuwaka via Donkarai - Upper Sileru - Pendurthi (SOMW} - Gazuwaka (20 MW) and further extend startup supply to Simhadri via Gazuwaka - Simhadri 400kV line. 47 SRLDC e) Oo} hp Black Start Restoration Procedure 2013 Simultaneously Donkarayi can be started Simultaneoulsy start up GMR Barge and extend start up supply to BSESivia PD Puram). Extend supply to Bommur from GMR Barge via PDPuram as the first aption and from Lower Sileru as the second option and both can be synchronized at Bommur Extend startup supply to Jegrupadu, VGTS-1 VGTS-2 & Spectrum (via Kakinada) From Bormmur extend supply to Gazuwaka (PG) via Kakinada / PDPuram and then to Simhadri (Option #3 for Simhadri startup) Extend Start Up supply to Vemagiri Gas Complex via Bommur - Vemagiri 220kv / 400 Kv. 48 Black Start Restoration Procedure 2013 SRLDC yeu aleweny 2o100h— aooze— peor uOReNL BP se9 sean ano. Apes SuswONPUKS veiguas 01 vonEs Yy ‘ana07] pawns oie auiseseuoy SLA epi f erepeung euunn npedrubar pez or ByenNz29 exemifzes) x aE (noyov1a TWLLwvd / W101 ONTING) MAVHWIS 3 1 Lois wevemsamin Pisani UM ‘Siw £WALSAS-ans Tas Lavis J1as HSaqved VaHGNY 4s SRLDC Black Start Restoration Procedure 2013 5.8.3 ACTIONS TO BE TAKEN BY VARIOUS GENERATING STATIONS AND SUB- STATIONS DURING TOTAL REGIONAL BLACKOUT AND / OR TOTAL BLACKOUT IN AP SUBSYSTEM - 3 fa) (b) {c) At LOWER SILERU * Ascertain the Total Blackout in AP System or Southern Region ® Open out all outgoing lines = Self-start the machine = Extend supply to KTPS ® Charge / Synchronise 220kV L Sileru ~ Donkarai line = Extend supply to Bommur through 220kV LSileru - Bommur line for connecting Traction loads at Bommur. * Incase any delay / difficulties in self-start L Sileru Units, first avail supply from Donkarai AtKTPS = Ascertain the Total Blackout in AP System or Southern Region * Follow the instructions of SLDC for any operation At DONKARAL * Ascertain the Total Blackout in AP System or Southern Region ® Open out all outgoing lines = Self-start the machine * Charge / synchronise 220kV Donkarai- U.Sileru line * Charge / Synchronise 220kV Donkarai- LSileru line * Incase any delay / difficulties in self-start Donkerai Units, first avail supply from U.Sileru / LSileru as the case may be and then proceed the steps above 50 SRLDC (d) Black Start Restoration Procedure 2013 At BOMMUR Bommur is @ very important substation from the point of Black Start Procedure since it connects to Subsystem 1 through Bommur ~ Vijeswaram stage2 - KV Kota ~ VTS. It also connects to all the gas stations of this Subsystem. Following are the actions to be taken at Bommur. Ascertain the Total Blackout in AP System or Southern Region (e) (f * Open out all outgoing lines = Avail supply from GMR Barge via PDPuram in consultation with APLD. = Incase any delay / difficulties in self-starting GMR Barge Units, first avail supply from Usileru / LSileru as the case may be and then proceed the steps below * Connect limited local loads = Extend startup power to Jegrupadu * Extend startup power to Spectrum through 220kV Bommur = Kakinada line * Extend startup power to BSES through 220kV Bommur - Peddapuram line = Charge / Synchronise 220kV Bommur - Vijeswaram stage ~ 2 line & Bommur = Vijeswaram stage - 1 line At VIUESWARAM STAGE -1 ® Ascertain the Total Blackout in AP System or Southern Region * Open out all outgoing lines * Avail Start Up supply from 8ommur. = Extend power supply to Bhimadole At UPPER SILERU- Ascertain the Total Blackout in AP System or Southern Region ® Open out all outgoing lines Self-start the machine Charge / synchronise 220kV Donkarai - U.sileru line st

S-ar putea să vă placă și