EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Verify and ensure the grounding for the installed AC outlets on the SAES-T-795,
A1
communications equipment rack is isolated from the equipment chassis. 4.4.2
Verify and ensure that the communication bonding conductor used for SAES-T-916,
A3 bonding & grounding the equipment racks is an insulated (green) no. 6 Illustration III,
AWG. pg.94
Verify and ensure that the equipment racks are self supporting, channel
A4 type, having standard 1-3/4"(4.45 cm) multiple vertical Pre-threaded EIA-310-D
mounting holes on front and rear prior the start of installation.
Verify and ensure that the panel horizontal mounting center is either 19" IFC drawings &
A5
or 23" and the racks height is as shown on the IFC drawings. Specification
Verify that the number of equipment racks installed is in accordance with IFC drawings &
A6
the Floor Diagram drawings. Specification
REMARKS:
REFERENCE DOCUMENTS:
1. EIA-310-D Standard
2. SAES-T-795, Communication Facility Grounding System dated 27 February, 2007
3. SAES-T-916, Telecommunications Building Cable Systems dated 7 February, 2007