MODELS CGL, CG,


CNC, CWHV3 AND CWHV4
SINGLE PHASE SIMPLEX AND
DUPLEX CONTROL PANELS
For 25 HP Single Phase Submersible Grinder Pumps
and 15 HP Single Phase Submersible Solids Handling Pumps

WWW.FEMYERS.COM
SINGLE PHASE SIMPLEX AND DUPLEX CONTROL PANELS

MYERS MODELS CGL, CG, CNC, CWHV3 & CWHV4


Single Phase Simplex and Duplex Control Panels


Advantages by Design
Myers has re-engineered the control panel line for improved durability, reliability and
economy. CAD flexibility enhances our response time to help us better meet your
control panel requirements. Contact your Myers distributor or the Myers Ohio sales
office at 419-289-1144 for more details.

Quality electrical components assure reliable,


automatic pump operation
IEC horsepower-rated motor contactors rated at over 1 million cycles. Simplex

CG, CNC, CWHV3/4 have 1 pole ambient-compensated


bi-metal overload relay.
CGL has Klixon overload.
Designed for use with standard mercury float switches.
Uses three for simplex (off-on-alarm), four for duplex (off-on-override-alarm).
Solid state alternating relay (on duplex only) to equalize pump wear.
Override relay to start second pump if first one fails for any reason.

Corrosion resistant for long life Duplex


Weathertight NEMA 4X fiberglass enclosures with aluminum back panels.

Meets NEC and UL (508) standards for safety


UL-approved panel designs (label installed only on request).
Individual pump circuit breakers.
Separate control and alarm fuses.

2
SINGLE PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Standard Panel Features for CG, CNC,


CWHV3 AND CWHV4
A. Corrosion-resistant Enclosure P
NEMA 4X fiberglass (outdoor). Simplex

B. Aluminum Back Panel Full Inner Door Front View


S A
X
C. IEC Motor Starter(s) Q W

1-pole bi-metal overload relay E


R
(not on CWHV3). F
G

D. IEC Motor Contactor(s) H


(CWHV3 only)
D
E. Control Circuit Fuse J K
I
1 amp.
B
F.
L
Alarm Circuit Fuse N O N

G. Start Winding Relay(s)


H. Starting Capacitor(s) Duplex
P

A
I. Running Capacitor(s) Full Inner Door Front View
S
B
W
J. Hand-Off-Auto Switch I
X
Momentary in-hand. G G R R
I
K. Alarm Test Switch H

L. Pump Run Light


J L L J
C C
H
Amber. M M
K E F
M. Seal Leak Light V
T T U
Red (not on CWHV3).

N. Terminal Blocks O
N N N N
O

O. Ground Lug(s)
P. Flashing Alarm Light
Mounted on top of enclosure (red).
U. Override Relay
Q. Full Inner Door In event of first pump failure (duplex only).

R. Pump Circuit Breaker(s) V. Alternator Relay


Lock-out tab. Solid state (duplex only).

S. Solid State Flasher W. Incoming Power Terminal Blocks


T. Overload Reset Button X. Control Circuit Circuit Breaker
(Not on CWHV3)

WWW.FEMYERS.COM 3
SINGLE PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Standard Panel Features for CGL

A. Corrosion-resistant Enclosure
NEMA 4X fiberglass (outdoor). Simplex P

B. Aluminum Back Panel Q A

C. IEC Motor Contactor(s) D B


G
Silver cadmium oxide contacts.

D. Pump Circuit Breakers K

E. Control Circuit Fuse H


J
1 amp. L
C
F.
M
Alarm Circuit Fuse I
1 amp.

G. Start Winding Relay(s) E F N O

H. Starting Capacitor(s)
I. Running Capacitor(s)
J. Hand-Off-Auto Switch
Momentary in-hand. Duplex P
A
K. Klixon Overload
Q

L. Pump Run Light D D


G G
B
Amber.

M. Seal Leak Light H H

Red (only on units with detector).


C C I I
N. Terminal Blocks K K

O. Ground Lug(s) E
S R
J J
F L L
P. Flashing Alarm Light M M
Mounted on top of enclosure (red). N N
O O

Q. Solid State Flasher


R. Override Relay
In event of first pump failure (duplex only).

S. Alternator Relay
Solid state (duplex only).

4
SINGLE PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Panel Dimensions and Optional Features

F Optional Panel Features


Elapsed time meter
Alarm bell or horn
Alarm bell or horn with silence switch
Auxiliary alarm contacts

A D
Condensation heater
Convenience outlet
Intrinsically safe relays
Lightning arrestor
Full inner door (CGL only)
E C Cycle counter
B
115 or 24 volt control circuit transformer
Transfer switch/generator receptacle
Lag pump delay circuitry (duplex only)
Enclosure Dimensions Low level cut-off and alarm
Panel CGL CG, CNC,CWHHV CGL CG, CNC, CWHV Low voltage circuitry
Simplex 1 ph. Simplex 1 ph. Duplex 1 ph. Duplex 1 ph.
Material Fiberglass Fiberglass Fiberglass Fiberglass
A 15-1/2 17-1/2 19-5/8 19-5/8
B 13-3/8 15-7/16 17-1/2 17-1/2
C 7-3/4 7-11/16 10-5/8 10-5/8
D 14-5/8 16-3/4 18-7/8 18-7/8 Other options also available,
E 10 12 12 12 consult factory for applications.
F 5/16 5/16 5/16 5/16 NOTE: Some options may increase enclosure size.

WWW.FEMYERS.COM 5
SINGLE PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Control Panel Selection

Simplex Selection Chart Duplex Selection Chart

Catalog Number Encl. HP Volt Used with Pumps Catalog Number Encl. HP Volt Used with Pumps
CGL-O1SW NEMA 4X 2 208 WGL20-01 or WGL20-01(LD) CGL-O1DW NEMA 4X 2 208 WGL20-01 or WGL20-01(LD)
CGL-21SW NEMA 4X 2 230 WGL20-21 CGL-21DW NEMA 4X 2 230 WGL20-21
CGL(LD)-21SW NEMA 4X 2 230 WGL20-21 (LD) CGL(LD)-21DW NEMA 4X 2 230 WGL20-21 (LD)
CG-20-21SW NEMA 4X 2 230 WG20-21 CG-20-21DW NEMA 4X 2 230 WG20-21
CG-30-21SW NEMA 4X 3 230 WG30-21, WG50H-21, 3RH50M2-21 CG-30-21DW NEMA 4X 3 230 WG30-21, WG50H-21, 3RH50M2-21
CG-30H-21SW NEMA 4X 3 230 WG30H-21, 3RH30M2-21 CG-30H-21DW NEMA 4X 3 230 WG30H-21, 3RH30M2-21
CG-50-21SW NEMA 4X 5 230 WG50-21 CG-50-21DW NEMA 4X 5 230 WG50-21
CNC-10-21SW NEMA 4X 1 230 4V10M6-21 CNC-10-21DW NEMA 4X 1 230 4V10M6-21
CNC-15-21SW NEMA 4X 1-1/2 230 4V15M6-21 CNC-15-21DW NEMA 4X 1-1/2 230 4V15M6-21
CNC-20-21SW NEMA 4X 23 230 4V20M6-21, 4V30M6-21 CNC-20-21DW NEMA 4X 23 230 4V20M6-21, 4V30M6-21
CNC-30-21SW NEMA 4X 3 230 4V30M4-21, 4R30M4-21 CNC-30-21DW NEMA 4X 3 230 4V30M4-21, 4R30M4-21
CNC-50-21SW NEMA 4X 5 230 4V50M4-21, 4R50M4-21 CNC-50-21DW NEMA 4X 5 230 4V50M4-21, 4R50M4-21
CWHV3-15-21SW NEMA 4X 11-1/2 230 3WHV10M4-21, 3WHV15M4-21 CWHV3-15-21DW NEMA 4X 11-1/2 230 3WHV10M4-21, 3WHV15M4-21
CWHV3-20-21SW NEMA 4X 2 230 3WHV20M4-21 CWHV3-20-21DW NEMA 4X 2 230 3WHV20M4-21
CWHV3-30-21SW NEMA 4X 3 230 3WHV30M4-21 CWHV3-30-21DW NEMA 4X 3 230 3WHV30M4-21
CWHV3-50-21SW NEMA 4X 5 230 3WHV50M4-21 CWHV3-50-21DW NEMA 4X 5 230 3WHV50M4-21
CWHV4-30-21SW NEMA 4X 3 230 4WHV30M4-21 CWHV4-30-21DW NEMA 4X 3 230 4WHV30M4-21
CWHV4-50-21SW NEMA 4X 5 230 4WHV50M4-21 CWHV4-50-21DW NEMA 4X 5 230 4WHV50M4-21

6
SINGLE PHASE SIMPLEX AND DUPLEX CONTROL PANELS

Contact Myers for All of Your


Engineered Wastewater Systems
Grinder Pumps
2 HP through 15 HP models with lifts to 260 feet
and flows to 190 GPM
Complete turnkey systems or applications
engineered to specifications
Computer system design and selection
programs available
Hazardous location construction available

SOLIDS HANDLING Pumps


3" through 12" discharges with 2" to 5.25"
solids handling capabilities
1 HP through 125 HP models
Lifts to 280 feet and flows to 8000 GPM
Computer system design and selection
programs available
Hazardous location construction available

Self-Priming Pumps
Pump sizes 3", 4", 6", 8" and 10" suction and discharge
2.5" through 3.5" solids handling capabilities
1 HP through 100 HP models
Lifts to 25 feet
Flows 50 GPM to 2800 GPM
Computer system design and selection programs available

Custom Controls
Each unit is custom-built and tested
An extensive range of capabilities and features

WWW.FEMYERS.COM 7
740 EAST 9TH STREET, 269 TRILLIUM DRIVE, KITCHENER,
ASHLAND, OHIO 44805 ONTARIO, CANADA N2G 4W5
WWW.FEMYERS.COM WWW.FEMYERS.COM
Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
K3214 01/11/13 2013 Pentair Ltd. All Rights Reserved.