Documente Academic
Documente Profesional
Documente Cultură
AbstractThe neutral-point balancing of 3L-NPC con- asymmetrical loads, tolerances of the capacitors, etc.
verter has been studied in many works in the past. There are several methods to balance the neutral-point of
However, all state-of-the-art methods have in common that the dc-link [7], [8], [9], [10]. These methods mainly de-
the information of the energy-flow direction is needed. pend on the modulation scheme and require the detection
Recently, Direct Dead-time Control (DDTC) has been
of the energy-flow direction. A new balancing method for
presented which controls the converter dead-times to
balance the dc-link independent from the energy-flow di-
three-phase 3L-NPC VSC, which is independent from
rection. This paper presents an experimental investigation the energy-flow direction and the applied modulation
of DDTC for different load conditions and control schemes. scheme, was presented in [5]. This method only needs
the capacitor voltages to balance the split dc-link of the
3L-NPC VSC.
I. I NTRODUCTION
This paper presents a summary of DDTC for the bal-
Multilevel inverters have become the dominant so- ancing of the split dc-link of 3L-NPC VSC. Moreover, it
lution for high power electrical drives [1], [2], [3], presents a 600 V, 3 kW test bench for the experimentally
[4]. Moreover, the three-phase, three-level neutral-point- verification of the method and experimentally studies
clamped voltage-source converter (3L-NPC VSC) is one the performance of the proposed method for diverse
of the most used converters for medium voltage drives implementations on a low cost FPGA.
[3], [2], [1], [5]. This topology has been successfully
transferred to low voltage high power applications [6], II. BASICS OF DDTC
becoming a serious competitor of the well established DDTC uses the semiconductor dead-times influence
two-level voltage-source converter (2L VSC). The 3L- on the neutral-point voltage to control its deviations
NPC VSC features following advantages: [5]. The method models the neutral-point voltage as a
lower switching and total losses for fs 3 . . . 5 kHz function of the neutral-point current. Assuming equal
[3], [2], capacitances in the upper and lower part of the dc-link,
lower harmonics and improved THD and WTHD
[3], [2], dvC1 dvC2
iM = C (1)
lower expense of filters to meet standards and grid dt dt
requirements [3], [2], dvM
iM = C , (2)
higher maximum switching frequency at given in- dt
stalled switch power [3], [2],
follows where vM is the neutral-point voltage. To de-
reduced insulation stress due to halved voltage step
scribe iM , a single phase of the 3L-NPC VSC and its
magnitudes [3], [2].
switching-states (qx = [1, 0, 1]) are examined as shown
One of the challenges of the 3L-NPC VSC is the in Fig. 1 . The neutral-point-current for one phase-leg can
balancing of the split dc-link. The reasons for the dc-link be described by
imbalance are diverse e.g. differences in IGBT switching
behavior, different timing of the gate-signals, dead times, iM x0 = Ix (1 |qx |) (3)
D6 T3 D3 D6 T3 D3 D6 T3 D3 VDC2 V Controller
- Limit
VDC2 VDC2 VDC2
TD24 TD2 , TD4
T4 D4 T4 D4 T4 D4
410
Table I
3L-NPC VSC TEST- BENCH PARAMETERS
Device Value
Voltage-source EA-PS 8720-15 Vmax = 720 V,
Pmax = 3 kW
DC-link capacitance C = 4 mF
(one half)
3L-NPC VSC Semikron Mini 3L VDC,max = 800 V,
Sout,max = 50 kVA
Load-inductance L = 4 mH, IL = 16 A
Load-resistance R = 15 , IR = 10 A
Output freuqency fo = [0 . . . 200 Hz]
Carrier frequency fc = 5 kHz
a) Complete test-bench
L iload R
v out
1
I load R
= , (6)
V out L
1 + (s + j)
R
where I load is the space-vector of the grid current,
V out the space-vector of the converter output voltage in
the Laplace domain, R the load resistance, L the load
inductance and the rotation speed of the synchronous
d) Load-resistance d-q-frame respectively.
Figure 4. Photos of 3L-NPC VSC test-bench
411
The complex part of the transfer function shows a 20
cross coupling between the d- and the q-current which 10
can be decoupled by a feed forward in the current
vM /V
0
controller [12]. 10
For the tuning of the PI-current regulator the delay of 20
the computation has to be considered. With symmetrical
sampling the total delay is 1.5Tsw , where Tsw is the 20
ia /A
first order delay element in the transfer function. The 0
20
1.5 2 2.5 3
1 t/s
I load 1 R
= . (7) a) DDTC with two-position controller
V out 1 + s 32 Tsw 1 + s L
R 20
vM /V
optimum [13]. The resulting transfer function of the PI- 0
controller is 10
20
1 + sT1 20
R(s) = with (8)
sT0 10
L
ia /A
0
T1 = , (9)
R 10
13
T0 = 2 Tsw . (10) 20
R2 3.6 3.4 3.2 3 2.8 2.6 2.4 2.2 2
t/s
B. Results
b) DDTC with PI controller
The DDTC can be realized with different controllers.
Figure 6. Neutral-point voltage and phase-current for RL-load at
The results shown in this paper were realized with a PI- Ia = 8 A and VDC = 600 V with DDTC and different controllers
controller and a two-position controller. The tests were
done with an L-load and an RL-load at a phase-current
of Ia = 8 A, a dc-link voltage of VDC = 600 V and an is sufficient to balance the dc-link. Further, it can be
output-frequency of fo = 50 Hz. The dc-balancing was seen that DDTC does not affect the current control .
deactivated until the neutral-point voltage reached the
start value vms = 20 V. Then, DDTC was reactivated to V. C ONCLUSION
observe the dynamic balancing behaviour. Fig. 6 shows This paper presented an experimental verification of
the experimental results for RL-load. The results for L- a new dc-balancing scheme, Direct Dead-time Control.
load are shown in Fig. 7 . It can be seen that DDTC Therefore, a test-bench was built. It consists of a 3L-
is able to balance the dc-link of a 3L-NPC for any NPC VSC which is fed by a DC voltage-source. On
load-angle without any information about the energy- the AC-side an RL-load was used to realise different
flow direction. This makes it possible to balance the load conditions. The current control, which was realised
dc-link for a load-angle of = 90 which is hard to in dSpace, calculates the reference values for the three
realize with state-of-the-art voltage balancing methods. phase-voltages. These were passed on to an FPGA which
Depending on the chosen controller and settings, there realized modulation and dc-balancing. The experimental
are differences in the dynamic and the control deviation. results show that DDTC is able to balance the dc-link.
Due to the high capacitance of the dc-link, the control The verification was done for different load-angles and
deviation of the two-position controller is negligible. controllers. DDTC is therefore a powerful and simple
The PI controller needs longer to settle the steady state. way to balance the dc-link of a 3L-NPC VSC without
The results show that with both controller and for all the need of energy-flow directions and independend from
investigated loads, the achieved dynamic and accuracy the chosen modulation scheme.
412
20
[6] M. Sprenger, R. Alvarez, I. Staudt, and S. Bernet, Character-
ization of a new 1.2 kv igbt 3l-npc phase-leg module for low
10
voltage applications, in Power Electronics and Applications
vM /V
0
Transactions on, vol. 49, no. 1, pp. 138 148, jan.-feb. 2013.
10 [11] M. Kazmierkowski and L. Malesani, Current control tech-
20 niques for three-phase voltage-source pwm converters: a sur-
vey, Industrial Electronics, IEEE Transactions on, vol. 45,
20 no. 5, pp. 691703, 1998.
[12] K. Dai, P. Liu, Y. Kang, and J. Chen, Decoupling current con-
10
trol for voltage source converter in synchronous roating frame,
ia /A
R EFERENCES
[1] D. Krug, S. Bernet, and S. Dieckerhoff, Comparison of state-
of-the-art voltage source converter topologies for medium volt-
age applications, in Industry Applications Conference, 2003.
38th IAS Annual Meeting. Conference Record of the, vol. 1,
oct. 2003, pp. 168 175 vol.1.
[2] R. Teichmann, M. Malinowski, and S. Bernet, Evaluation
of three-level rectifiers for low-voltage utility applications,
Industrial Electronics, IEEE Transactions on, vol. 52, no. 2,
pp. 471 481, april 2005.
[3] R. Teichmann and S. Bernet, A comparison of three-level
converters versus two-level converters for low-voltage drives,
traction, and utility applications, Industry Applications, IEEE
Transactions on, vol. 41, no. 3, pp. 855 865, may-june 2005.
[4] J. Rodriguez, S. Bernet, B. Wu, J. Pontt, and S. Kouro, Multi-
level voltage-source-converter topologies for industrial medium-
voltage drives, Industrial Electronics, IEEE Transactions on,
vol. 54, no. 6, pp. 2930 2945, dec. 2007.
[5] M. Sprenger, R. Alvarez, and S. Bernet, Direct dead-time
control - a novel dc-link neutral-point balancing method for
the three-level neutral-point-clamped voltage source inverter,
in Energy Conversion Congress and Exposition (ECCE), 2012
IEEE, sept. 2012, pp. 1157 1163.
413