Application Advisory
If you plan to make housing measurements for overall machine protection,
consider the usefulness of the measurement for each application. Most
common machine malfunctions (imbalance, misalignment, etc.) originate at
the rotor and cause an increase (or at least a change) in rotor vibration. For
any housing measurement to be effective for overall machine protection,
the machine must faithfully transmit a significant amount of rotor vibration
to the bearing housing or machine casing, or more specifically, to the
mounting location of the transducer. In addition, you should exercise care
in the physical installation of the transducer. Improper installation can
degrade the transducers performance, and/or generate signals that do not
represent actual machine vibration. Integration of the output to
displacement can make this worse. Exercise extreme caution if integrating
to displacement in any case.
Page 1 of 7
Maximum Cable
Specifications Length
Parameters are specified from +20 C to +30 C (+68 305 metres (1,000 feet) of cable,
F to +86 F) and at 100 Hz unless otherwise part number 02173006, with no
indicated. degradation of signal.
Note: Operation outside the specified limits may result in false Hazardous Area Approvals
readings or loss of machine monitoring.
Multiple approvals for hazardous areas certified by
Electrical Canadian Standards Association (CSA) in North
America and by LCIE in Europe.
Sensitivity
North America
3.94mV/mm/s (100 mV/in/s) 5%.
Ex ia IIC T4
Frequency AEx ia IIC T4
Response
Class I, Div 1, Groups A, B, C, D
4.5 Hz to 5 kHz (270 cpm to 300 Class II, Groups E, F, G
kcpm) 3.0 dB. Class III
6.0 Hz to 2.5 kHz (360 cpm to 150 when installed per dwg 167537
kcpm) 0.9 dB. T4 @ -40C Ta 100C
Ex nL IIC T4
Temperature
Sensitivity AEx nA IIC T4
Class I, Div 2, Groups A, B, C, D
-14% to +7.5% typical over the when installed per dwg 167537
operating temperature range.
T4 @ -40C Ta 100C
Velocity Range
European/ATEX
1270 mm/s (50 in/s) peak. II 1 G
Transverse Ex ia IIC T4 Ga
Sensitivity T4 @ -55C Ta 121C
Page 2 of 7
Environmental Limits Polarity
Diameter
Height
Case Material
Connector
Mounting
Torque
Page 3 of 7
Interconnect Cables 84661
AXX 2-conductor twisted, shielded 22
A: Cable length Option in feet AWG armored cable with 2-
socket moisture-resistant female
For the cables listed below, order connector at one end, terminal
in increments of 1.0 ft (305 mm). lugs at the other end.
Example: 0 9 = 9 ft Used with monitors. Not for use
with 21128 Velocity Transducer
1 2 = 12 ft
Housing.
Page 4 of 7
Used with 1/4 - 28 UNF mounting
Velocity Transducer Housing Assembly thread adapters.
21128-AXX-BXX
46122-01
A: Mounting Thread Option
01 Unthreaded Quick Connect for
02 3/4 - 14 NPT semi-permanent mounting of
03 1/2 - 14 NPT Velomitor Sensors. Used with
04 1/2 - 12 BSP 1/2 - 20 UNF mounting thread
adapters.
B: Cable Exit Fitting Option
89409-01
01 1/2 - 14 NPT plug
02 1/2 -14 NPT explosion-proof Individual 1/2 - 20 UNF
03 1/2 -14 NPT explosion-proof mounting adapter.
with cable gland seal
89410-01
Note: When using the 21128 housing,
cable part number 89477-AA is Individual M8 x 1 mounting
necessary to connect the adapter.
Velomitor Sensor to a monitor.
89411-01
Page 5 of 7
Graphs and Figures
63.2
(2.49)
4
3
Page 6 of 7
2
dB referenced to 100 Hz
-1
-2
1 10 100 1000 10000
Frequency (Hz)
Figure 2: Typical Amplitude Response
100
80
Phase Lag Angle (degrees)
60
40
20
-20
1 10 100 1000 10000
Frequency (Hz)
* Denotes trademarks of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Company.
Page 7 of 7