Sunteți pe pagina 1din 4

S.No.

Particulars Unit Quantity


Process Details (E-1421 - Ist Stage Cooler of PAC)
1 Fluid
(a) Shell-side medium Air
(b) Tube-side medium Water
2 Number of Passes
(a) Shell-side No. 1
(b) Tube-side No. 4
3 Flow (Total)
(a) Shell-side * Kg/hr 89568 24.88 kg/s
(b) Tube-side Kg/hr 311000 86.39 kg/s
(c) condensate (shell side) Kg/hr 1375 0.382 kg/s
4 Op. Temperature (in/out)
(a) Shell-side o
C 138.6 / 41.5
(b) Tube-side o
C 33.5 / 43.5
5 Op. Pressure
(a) Shell-side Kg/cm2 1.2
(b) Tube-side Kg/cm2 3.5
6 Design Temperature
(a) Shell-side o
C 170
(b) Tube-side o
C 70
7 Design Pressure
(a) Shell-side Kg/cm2 7
(b) Tube-side Kg/cm2 7
8 Corrosion Allowance (CS Parts)
(a) Shell-side inch 3
(b) Tube-side inch 3
9 Process Specific Heat - -
10 Pressure Drop , max. allowable/calculated
(a) Shell-side Kg/cm2 0.036
(b) Tube-side Kg/cm 2
0.7/0.695
11 Process Density - -
12 Effective Surface Area m2 1920
13 Heat Load/Heat Duty MMCal/hr 3.108
Mechanical Details (E-1421 - Ist Stage Cooler of PAC)
14 Shell ID mm 2000
15 Tube Details
(a) Numbers - 994
(b) ID/OD mm 15 / 18
(c) Length mm 4300
(d) Pitch Arrangement - Triangular
(e) Thickness mm 1.5
(f) Pitch Spacing mm 32.5
16 Baffle (Type) Silicon Rubber
(a) Spacing mm 520
(b) Cut % -
no. of baffles 4
17 Metallurgy
(a) Shell-side - SS
(b) Tube-side - SA 516 Gr. 70
18 Mean Temp. Difference o
C 34.15
19 Calc. Outside Surface/unit m2 1780
20 Installed outside surface/unit m2 1920
21 Vapour
(a) Shell-side o
C 50.4
(b) Tube-side o
C
22 Fouling Coefficient
(a) Shell-side m2 oC h/KCal 0.0002
(b) Tube-side m C h/KCal
2 o
0.0006
23 Demister Type Wire Mesh pad
24 Efficeincy (for droplets >20 % 95
(a) Water velocity through tubes = 1.95 m/s
* = Comp. 1st Suction: Pressure/Temp./RH/Dry Air Flow = 0.94 Bar /35 oC /100% /66387 Nm3
Other Details
25 Supplier - GEA
26 Purchase Order No. - 514
27 Remarks - Tubes (Al Fins)
24.88 kg/s
86.39 kg/s
0.382 kg/s

S-ar putea să vă placă și