MODEL PA1/PA3/SA1/SA2/SA3/SA5/SB/SB2/SB3/SB4

SB5/SB6/SB7/SC/SC3/SC4/NB/NB2/NB6

LADDER LANGUAGE

PROGRAMMING MANUAL

B-61863E/14
No part of this manual may be reproduced in any form.
All specifications and designs are subject to change without notice.

The export of this product is subject to the authorization of the government of the country
from where the product is exported.

In this manual we have tried as much as possible to describe all the various matters.
However, we cannot describe all the matters which must not be done, or which cannot be
done, because there are so many possibilities.
Therefore, matters which are not especially described as possible in this manual should be
regarded as impossible.
B61863E/14 DEFINITION OF WARNING, CAUTION, AND NOTE

DEFINITION OF WARNING, CAUTION, AND NOTE

This manual includes safety precautions for protecting the user and preventing damage to the
machine. Precautions are classified into Warning and Caution according to their bearing on safety.
Also, supplementary information is described as a Note. Read the Warning, Caution, and Note
thoroughly before attempting to use the machine.

WARNING

Applied when there is a danger of the user being injured or when there is a danger of both the user
being injured and the equipment being damaged if the approved procedure is not observed.

CAUTION

Applied when there is a danger of the equipment being damaged, if the approved procedure is not
observed.

NOTE

The Note is used to indicate supplementary information other than Warning and Caution.

` Read this manual carefully, and store it in a safe place.

s1
B61863E/14 PREFACE

PREFACE

This programming manual describes the method of generating


ladder sequence programs for PMC.
It also describes the operation methods of CRT/MDI and
SYSTEM P series for sequence programming.
Renaming of PMC This manual presents programming descriptions for the PMC
Models models listed in the following table. Note that some models have
been renamed; in the product name column, the old names are
enclosed in parentheses, while the new names appear above the
old names. However, the previous specifications are still applied
to the renamed models. Thus, when using the renamed models,
users should:
Read the old names shown in this manual as the new names.
Read the old names appearing on the units as the new names.

Applicable models The models covered by this manual, and their abbreviations are :

Product Name Abbreviations Applicable CNC


FANUC PMCMODEL PA1 PMCPA1 FANUC Power MateMODEL D
FANUC Series 21MODEL A

FANUC PMCMODEL PA3 PMCPA3 FANUC Power MateMODEL D/F/H


FANUC Series 21MODEL A

FANUC PMCMODEL SA1 (Note 1) PMCSA1 FANUC Series 18MODEL A/B


(Old Name : FANUC PMCMODEL RA1) (PMCRA1) FANUC Series 20MODEL A
FANUC Series 21MODEL B
FANUC Series 20iMODEL A
FANUC Series 0iMODEL A
FANUC Series 21iMODEL A/B
Loader control function (Note 2)

FANUC PMCMODEL SA2 (Note 1) PMCSA2 FANUC Series 18MODEL A


(Old Name : FANUC PMCMODEL RA2) (PMCRA2)

FANUC PMCMODEL SA3 (Note 1) PMCSA3 FANUC Series 18MODEL A


(Old Name : FANUC PMCMODEL RA3) (PMCRA3) FANUC Series 20MODEL A
FANUC Series 21MODEL B
FANUC Series 0iMODEL A

FANUC PMCMODEL SA5 (Note 1) PMCSA5 FANUC Series 21iMODEL A


(Old Name : FANUC PMCMODEL RA5) (PMCRA5)

FANUC PMCMODEL SB (Note 1) PMCSB FANUC Series 16MODEL A


(Old Name : FANUC PMCMODEL RB) (PMCRB)
FANUC PMCMODEL SB2 (Note 1) PMCSB2
(Old Name : FANUC PMCMODEL RB2) (PMCRB2)

FANUC PMCMODEL SB3 (Note 1) PMCSB3 FANUC Series 16MODEL A/B


(Old Name : FANUC PMCMODEL RB3) (PMCRB3) FANUC Series 18MODEL B

p1
PREFACE B61863E/14

Product Name Abbreviations Applicable CNC


FANUC PMCMODEL SB4 (Note 1) PMCSB4 FANUC Series 16MODEL B
(Old Name : FANUC PMCMODEL RB4) (PMCRB4) FANUC Series 18MODEL B

FANUC PMCMODEL SB5 (Note 1) PMCSB5 FANUC Series 16MODEL C


(Old Name : FANUC PMCMODEL RB5) (PMCRB5) FANUC Series 18MODEL C
FANUC Series 16iMODEL A
FANUC Series 18iMODEL A
FANUC Power Mate iMODEL D/H

FANUC PMCMODEL SB6 (Note 1) PMCSB6 FANUC Series 16MODEL C


(Old Name : FANUC PMCMODEL RB6) (PMCRB6) FANUC Series 18MODEL C
FANUC Series 16iMODEL A
FANUC Series 18iMODEL A
FANUC Series 21iMODEL A
FANUC Power Mate iMODEL D/H

FANUC PMCMODEL SB7 PMCSB7 FANUC Series 16iMODEL B


FANUC Series 18iMODEL B
FANUC Series 21iMODEL B

FANUC PMCMODEL SC (Note 1) PMCSC FANUC Series 16MODEL A


(Old Name : FANUC PMCMODEL RC) (PMCRC)

FANUC PMCMODEL SC3 (Note 1) PMCSC3 FANUC Series 16MODEL A/B/C


(Old Name : FANUC PMCMODEL RC3) (PMCRC3) FANUC Series 18MODEL B/C

FANUC PMCMODEL SC4 (Note 1) PMCSC4 FANUC Series 16MODEL B/C


(Old Name : FANUC PMCMODEL RC4) (PMCRC4) FANUC Series 18MODEL B/C

FANUC PMCMODEL NB PMCNB FANUC Series 15MODEL B

FANUC PMCMODEL NB2 PMCNB2

FANUC PMCMODEL NB6 PMCNB6 FANUC Series 15iMODEL A

NOTE
1 These models have been renamed; in the product name
column, the old names are enclosed in parentheses, while
the new names appear above the old names. However, the
previous specifications are still applied to the renamed
models.
Thus, when using the renamed models, users should :
Read the old names shown in this manual as the new
names.
Read the old names appearing on the units as the new
names.
2 PMCSA1 is applied to the loader control side of a CNC
having the loader control function.
The CNC models having the loader control function are as
follows :
FANUC Series 16MODEL A/B/C
FANUC Series 18MODEL A/B/C
FANUC Series 21MODEL B
FANUC Series 16i/18i/21iMODEL A/B

p2
B61863E/14 PREFACE

Other manuals However, it does not include all items required for sequence
programming. For those required for sequence programming
refer to the following manuals.

Name of manual Reference items Application


FANUC Power Mate-MODEL D/F Interface between PMC and CNC PMC-PA1
CONNECTION MANUAL (B-62833EN) PMC-PA3
FANUC Power Mate-MODEL H Interface between PMC and CNC PMC-PA3
CONNECTION MANUAL (B62683EN)
FANUC Power Mate i-MODEL D/H Interface between PMC and CNC PMC-SB5
CONNECTION MANUAL (FUNCTION) (B63733EN1) PMC-SB6
FANUC Series 16/18 Interface between PMC and CNC PMC-SA1
CONNECTION MANUAL (B-61803E) PMC-SA2
PMC-SA3
PMC-SB
PMC-SB2
PMC-SB3
PMC-SC
PMC-SC3
FANUC Series 16/18/160/180-MODEL B Interface between PMC and CNC PMC-SB3
CONNECTION MANUAL (FUNCTION) (B-62443E-1) PMC-SB4
PMC-SC3
PMC-SC4
FANUC Series 16/18/160/180-MODEL C Interface between PMC and CNC PMC-SB5
CONNECTION MANUAL (FUNCTION) (B-62753EN-1) PMC-SB6
PMC-SC3
PMC-SC4
FANUC Series 16i/18i/21i/160i/180i/210iMODEL A Interface between PMC and CNC PMC-SA1
CONNECTION MANUAL (FUNCTION) (B-63003EN-1) PMC-SA5
PMC-SB5
PMC-SB6
FANUC Series 16i/18i/21i/160i/180i/210iMODEL B Interface between PMC and CNC PMC-SB7
CONNECTION MANUAL (FUNCTION) (B-63523EN-1)
FANUC Series 20FA/TA Interface between PMC and CNC PMC-SA1
CONNECTION MANUAL (B62173E) PMC-SA3
FANUC Series 21/210MODEL B Interface between PMC and CNC PMC-SA1
CONNECTION MANUAL (FUNCTION) (B62703EN1) PMC-SA3
FANUC Series 15-MODEL B Interface between PMC and CNC PMC-NB
BMI INTERFACE PMC-NB2
CONNECTION MANUAL (B-62073E-1)
FANUC Series 15i/150i-MODEL A Interface between PMC and CNC PMC-NB6
CONNECTION MANUAL (FUNCTION) (B63323EN1)
FANUC PMC C language programming PMC-SC
C LANGUAGE PROGRAMMING MANUAL PMC-SC3
(B-61863E-1) PMC-SC4
PMC-NB
PMC-NB2

Other application The models covered for reference by this manual, and their
model names abbreviations are:

Product name Abbreviation CNC for


FANUC PMC-MODEL P PMC-P FANUC Power Mate-MODEL C

FANUC PMC-MODEL NA PMC-NA FANUC Series 15-MODEL B

p3
B61863E/14 Table of Contents
DEFINITION OF WARNING, CAUTION, AND NOTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . s1

PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pI

I. PMC SEQUENCE PROGRAM


1. SEQUENCE PROGRAM CREATING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 SPECIFICATION OF PMCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 SUMMARY OF SPECIFICATION OF LADDER PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1.3 WHAT IS A SEQUENCE PROGRAM? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1.4 CREATION OF INTERFACE SPECIFICATIONS (STEPS 1 TO 3) . . . . . . . . . . . . . . . . . . . . . . . . . 37
1.5 CREATION OF LADDER DIAGRAM (STEP 4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1.6 CODING (STEP 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1.7 SEQUENCE PROGRAM ENTRY (STEPS 6, 7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1.8 SEQUENCE PROGRAM CHECK AND WRITE INTO ROM (STEPS 8 TO 11) . . . . . . . . . . . . . . 39
1.9 STORAGE AND CONTROL OF SEQUENCE PROGRAM (STEPS 12 TO 14) . . . . . . . . . . . . . . . 40

2. SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.1 EXECUTION PROCEDURE OF SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2.2 REPETITIVE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.3 PRIORITY OF EXECUTION (1ST LEVEL, 2ND LEVEL AND 3RD LEVEL) . . . . . . . . . . . . . . . 44
2.4 SEQUENCE PROGRAM STRUCTURING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
2.5 PROCESSING I/O SIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.5.1 Input Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
2.5.2 Output Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
2.5.3 I/O Signals to CNC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
2.5.4 Difference of Status of Signals between 1st Level and 2nd Level . . . . . . . . . . . . . . . . . . . . . . . 53
2.6 INTERLOCKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
2.7 SEQUENCE PROGRAM PROCESSING TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2.8 SEQUENCE PROGRAM MEMORY CAPACITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

3. ADDRESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
3.1 ADDRESSES BETWEEN PMC AND CNC (PMCNC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
3.2 ADDRESSES BETWEEN PMC AND MACHINE TOOL (PMCMT) . . . . . . . . . . . . . . . . . . . . . . 75
3.2.1 Addresses Between PMC and Machine Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
3.2.2 Assignment of I/O Module Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
3.2.3 I/O Link Connection Unit Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
3.2.4 I/O Unit MODEL B Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
3.2.5 Power Mate Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
3.2.6 FS16iLA Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
3.2.7 Distribution I/O Connection I/O Module and Distribution I/O Operators Panel
I/O Module Assignment Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
3.3 INTERNAL RELAY ADDRESSES (R) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
3.3.1 Area Managed by the System Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

c1
Table of contents B61863E/14

3.4 ADDRESSES FOR MESSAGE SELECTION DISPLAYED ON CRT (A) . . . . . . . . . . . . . . . . . . . 102


3.5 ADDRESS OF COUNTER (C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
3.6 ADDRESS OF KEEP RELAY AND NONVOLATILE MEMORY CONTROL (K) . . . . . . . . . . . . 106
3.7 ADDRESS OF DATA TABLE (D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
3.8 TIMER ADDRESSES (T) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
3.9 LABEL ADDRESSES (JMPB, JMPC, LBL) (L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
3.10 SUBPROGRAM NUMBERS (CALL, CALLU, SP) (P) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

4. PMC BASIC INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114


4.1 DETAILS OF BASIC INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
4.1.1 RD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
4.1.2 RD. NOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
4.1.3 WRT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
4.1.4 WRT. NOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
4.1.5 AND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
4.1.6 AND. NOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
4.1.7 OR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
4.1.8 OR. NOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
4.1.9 RD. STK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
4.1.10 RD. NOT. STK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
4.1.11 AND. STK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
4.1.12 OR. STK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
4.1.13 SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
4.1.14 RST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

5. FUNCTIONAL INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130


5.1 END1 (1ST LEVEL SEQUENCE PROGRAM END) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
5.2 END2 (2ND LEVEL SEQUENCE PROGRAM END) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
5.3 END3 (END OF 3RD LEVEL SEQUENCE) (PMCSC/SC3/SC4/NB/NB2/NB6/NB7 ONLY) . . 159
5.4 TMR (TIMER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
5.5 TMRB (FIXED TIMER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
5.6 TMRC (TIMER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
5.7 DEC (DECODE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
5.8 DECB (BINARY DECODING) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
5.9 CTR (COUNTER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
5.10 CTRB (Fixed counter) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
5.11 CTRC (COUNTER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
5.12 ROT (ROTATION CONTROL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
5.13 ROTB (BINARY ROTATION CONTROL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
5.14 COD (CODE CONVERSION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
5.15 CODB (BINARY CODE CONVERSION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
5.16 MOVE (LOGICAL PRODUCT TRANSFER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
5.17 MOVOR (DATA TRANSFER AFTER LOGICAL SUM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
5.18 COM (COMMON LINE CONTROL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
5.19 COME (COMMON LINE CONTROL END) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
5.20 JMP (JUMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
5.21 JMPE (JUMP END) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209

c2
B61863E/14 Table of contents

5.22 PARI (PARITY CHECK) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210


5.23 DCNV (DATA CONVERSION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
5.24 DCNVB (EXTENDED DATA CONVERSION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
5.25 COMP (COMPARISON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
5.26 COMPB (COMPARISON BETWEEN BINARY DATA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
5.27 COIN (COINCIDENCE CHECK) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
5.28 SFT (SHIFT REGISTER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
5.29 DSCH (DATA SEARCH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
5.30 DSCHB (BINARY DATA SEARCH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
5.31 XMOV (INDEXED DATA TRANSFER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
5.32 XMOVB (BINARY INDEX MODIFIER DATA TRANSFER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
5.33 ADD (ADDITION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
5.34 ADDB (BINARY ADDITION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
5.35 SUB (SUBTRACTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
5.36 SUBB (BINARY SUBTRACTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
5.37 MUL (MULTIPLICATION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
5.38 MULB (BINARY MULTIPLICATION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
5.39 DIV (DIVISION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
5.40 DIVB (BINARY DIVISION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
5.41 NUME (DEFINITION OF CONSTANT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
5.42 NUMEB (DEFINITION OF BINARY CONSTANTS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
5.43 DISP (MESSAGE DISPLAY) (PMCSB/SB2/SB3/SB4/SB5/SB6/SC/SC3/SC4 ONLY) . . . . . . . . 258
5.44 DISPB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
5.45 EXIN (EXTERNAL DATA INPUT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
5.46 WINDR (READING CNC WINDOW DATA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
5.47 WINDW (WRITING CNC WINDOW DATA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
5.48 ARBITRARY FUNCTIONAL INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
5.49 MMCWR (READING MMC WINDOW DATA) (OTHER THAN PMCPA1/PA3) . . . . . . . . . . . 297
5.50 MMCWW (WRITING MMC WINDOW DATA) (OTHER THAN PMCPA1/PA3) . . . . . . . . . . . 299
5.51 MOVB (TRANSFER OF 1 BYTE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
5.52 MOVW (TRANSFER OF 2 BYTES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
5.53 MOVN (TRANSFER OF AN ARBITRARY NUMBER OF BYTES) . . . . . . . . . . . . . . . . . . . . . . . 303
5.54 MOVD (TRANSFER OF 4 BYTES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
5.55 DIFU (RISING EDGE DETECTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
5.56 DIFD (FALLING EDGE DETECTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
5.57 EOR (EXCLUSIVE OR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
5.58 LOGICAL AND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
5.59 LOGICAL OR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
5.60 NOT (LOGICAL NOT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
5.61 MMC3 R (MMCIII WINDOW DATA READ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
5.62 MMC3W (MMCIII WINDOW DATA WRITE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
5.63 SPCNT (SPINDLE CONTROL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
5.64 END (END OF A LADDER PROGRAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
5.65 CALL (CONDITIONAL SUBPROGRAM CALL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
5.66 CALLU (UNCONDITIONAL SUBPROGRAM CALL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
5.67 SP (SUBPROGRAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
5.68 SPE (END OF A SUBPROGRAM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333

c3
Table of contents B61863E/14

5.69 JMPB (LABEL JUMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334


5.70 JMPC (LABEL JUMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
5.71 LBL (LABEL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
5.72 AXCTL (AXIS CONTROL BY PMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
5.73 PSGNL (POSITION SIGNAL OUTPUT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
5.74 PSGN2 (POSITION SIGNAL OUTPUT 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
5.75 NOP (NO OPERATION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351

6. NONVOLATILE MEMORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353


6.1 TIMER, COUNTER, KEEP RELAY, NONVOLATILE MEMORY CONTROL, DATA TABLE . 354
6.2 READING AND WRITING OF NONVOLATILE MEMORY DATA . . . . . . . . . . . . . . . . . . . . . . . 356
6.3 PMC DATA TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357

7. LADDER DIAGRAM FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 362


7.1 ADDRESSES, SIGNAL NAMES, COMMENTS, AND LINE NUMBERS . . . . . . . . . . . . . . . . . . 363
7.1.1 Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
7.1.2 Signal Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
7.1.3 Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
7.1.4 Line Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
7.2 SYMBOLS USED IN THE LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
7.3 LADDER DIAGRAM FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366
7.4 INFINITE NUMBER OF RELAY CONTACTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 367

8. MISCELLANEOUS ITEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368

9. SEQUENCE PROGRAM STRUCTURING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369


9.1 EXAMPLES OF STRUCTURED PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
9.1.1 Implementation Techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
9.1.2 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371
9.1.3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
9.2 SUBPROGRAMMING AND NESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
9.2.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
9.2.2 Execution Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
9.2.3 Creating a Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
9.3 CAUTIONS FOR SUBROUTINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378

10. JMP INSTRUCTIONS WITH LABEL SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . 380


10.1 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
10.2 RESTRICTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385

11. INTERRUPTTYPE PMC FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391


11.1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
11.2 SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
11.3 INTERRUPT PROCESSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394
11.3.1 Interrupt Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394

c4
B61863E/14 Table of contents

11.3.2 Input/Output Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395


11.3.3 Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
11.3.4 Execution Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
11.3.5 Interrupt Enable/Disable/Clear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
11.3.6 Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
11.4 SEQUENCE PROGRAM EXAMPLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400

II. PMC OPERATION (CRT/MDI)


1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
1.1 FOR MDI UNITS OTHER THAN STANDARD MDI UNITS
(FOR FS20 PMCSA1 AND SA3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
1.2 AUTOMATIC OPERATION WHEN THE POWER IS TURNED ON . . . . . . . . . . . . . . . . . . . . . . 412
1.3 CLEARING THE SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
1.4 LOADING THE STANDARD LADDER (FOR Power MateD/F PMCPA1 AND PA3) . . . . . . . 413
1.5 FS15i PMCNB6 OPERATING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
1.6 FS16i/18i/21iB PMCSA1/SB7 OPERATING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
1.7 LADDER PASSWORD FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
1.8 PMC OPERATION FOR LOADER CONTROL FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417

2. PMC MENU SELECTION PROCEDURE BY SOFTKEY . . . . . . . . . . . . . . . . . . . . . . . . 418

3. PMC I/O SIGNAL DISPLAY AND INTERNAL RELAY DISPLAY (PMCDGN) . . . . . . 424
3.1 DISPLAYING TITLE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
3.2 DISPLAY OF SIGNAL STATUS (STATUS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
3.3 ALARM SCREEN (ALARM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 428
3.4 TRACE FUNCTION (TRACE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
3.4.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
3.4.2 Parameter Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
3.4.3 Starting or Stopping the Trace Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
3.4.4 Trace Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
3.4.5 Automatic Tracing Function at Power on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
3.5 DISPLAYING THE CONTENTS OF MEMORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
3.5.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
3.5.2 Function for Storing Data in Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
3.6 FUNCTION FOR DISPLAYING SIGNAL WAVEFORMS (ANALYS) . . . . . . . . . . . . . . . . . . . . . 434
3.6.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
3.6.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
3.6.3 Parameter Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
3.6.4 Signal Diagnosis Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
3.6.5 Reading Signals Automatically at Power on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
3.7 DISPLAYING THE RUNNING STATE OF A USER TASK (USRDGN) . . . . . . . . . . . . . . . . . . . . 440
3.8 DISPLAYING AND SETTING THE CONFIGURATION STATUS OF I/O
DEVICES (IOCHK) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
3.8.1 I/O Link Connecting Check Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
3.8.2 I/O LinkII Parameter Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446

c5
Table of contents B61863E/14

3.9 FORCED INPUT/OUTPUT FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449


3.9.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
3.9.2 Setting/Operation for Enabling Forced Input/Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
3.9.3 Screen Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454
3.9.4 Modifying the Values of Signals by Forced Input/Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
3.9.5 Setting/Clearing OVERRIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458

4. PMC PARAMETERS SETTING AND DISPLAY (PMCPRM) . . . . . . . . . . . . . . . . . . . . . 460


4.1 OUTLINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
4.2 INPUT PMC PARAMETERS FROM MDI PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
4.2.1 Multiple Data Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
4.3 SETTING AND DISPLAY SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
4.3.1 Timer Screen (TIMER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
4.3.2 Counter Screen (COUNTR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464
4.3.3 Keep Relay (KEEPRL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464
4.3.4 Data Table (DATA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470
4.4 SETTING SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472
4.4.1 Other Setting Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475
4.5 NOTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 478

5. PMC LADDER DIAGRAM DISPLAY (PMCLAD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479


5.1 LADDER DIAGRAM DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 480
5.2 DUMP DISPLAY ON LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481
5.3 PARAMETER DISPLAY ON LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 482
5.3.1 The Value of Functional Instruction Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 483
5.4 SYMBOL AND COMMENT DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485
5.5 SEARCH OF SPECIFIED RELAY COIL POINTS IN LADDER DIAGRAM . . . . . . . . . . . . . . . . 486
5.6 STOP OF LADDER DIAGRAM DISPLAY BY TRIGGER OF SIGNAL . . . . . . . . . . . . . . . . . . . . 487
5.7 DIVIDING DISPLAY OF LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 489
5.8 ONLINE EDIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490

6. USER PMC SCREEN (PMCMDI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 492


6.1 FOR THE FS16 (PMCSC OR PMCSC3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
6.2 FOR THE FS15 (PMCNB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493

III. PMC PROGRAMMER (CRT/MDI)


1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
1.1 ABOUT THE FS15i PMCNB6 PROGRAMMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 498
1.2 ABOUT THE FS16i/18i/21iB PMCSA1/SB7 PROGRAMMER . . . . . . . . . . . . . . . . . . . . . . . . . 498

2. COMPONENT UNITS AND CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499


2.1 COMPONENT UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
2.2 CONNECTING COMPONENT UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505

c6
B61863E/14 Table of contents

3. SELECTION OF PROGRAMMER MENUS BY SOFTKEYS . . . . . . . . . . . . . . . . . . . . . 506

4. SPECIFYING AND DISPLAYING SYSTEM PARAMETERS (SYSPRM) . . . . . . . . . . . 508

5. EDITING OF SEQUENCE PROGRAM (EDIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515


5.1 SPECIFYING AND DISPLAYING TITLE DATA (TITLE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
5.1.1 Entering Title Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
5.1.2 Deleting Title Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
5.1.3 Editing Character Strings of Title Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 517
5.2 SEQUENCE PROGRAM GENERATION (LADDER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 519
5.2.1 Sequence Program Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
5.2.2 Alteration of Sequence Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524
5.2.3 Insert of Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524
5.2.4 Delete of Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 527
5.2.5 Search of Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
5.2.6 Copying the Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
5.2.7 Moving the Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 531
5.2.8 Editing Symbol Data and Comment at Once . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532
5.2.9 Address Change of Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532
5.3 I/O UNIT ADDRESS SETTING (MODULE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 534
5.4 SYMBOL DATA SETTING (SYMBOL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 537
5.4.1 Symbol Data and Comment Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 538
5.4.2 Symbol Data Search (SRCH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 538
5.4.3 Delete of Symbol Data and Comment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 538
5.4.4 Editing Character Strings of Symbol Data and Comment Data . . . . . . . . . . . . . . . . . . . . . . . . 539
5.4.5 Function for Editing Symbol Data and Comment Data at One Time . . . . . . . . . . . . . . . . . . . 539
5.4.6 Function of Copying Symbol and Comment Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 540
5.5 MESSAGE DATA SETTING (MESSAGE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 541
5.5.1 Message Data Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542
5.5.2 Searching for an Address (SRCH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542
5.5.3 Editing a Character String in Message Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542
5.5.4 Input with a Katakana Identification Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
5.5.5 Copying Message Data (COPY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
5.5.6 Inputting a Multibyte Character (D.CHAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
5.5.7 Displaying Input Code (DSPMOD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
5.6 CLEARING THE SEQUENCE PROGRAM AND CONDENSATION OF
THE SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544
5.6.1 Clearing the Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544
5.6.2 Compress the Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545
5.6.3 Clearing the PMC Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545
5.7 CROSS REFERENCE DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 546
5.7.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 546
5.7.2 Parameter Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547

6. EXECUTION OF A SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 551


6.1 START AND STOP OF A SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552

c7
Table of contents B61863E/14

6.2 STARTING THE SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553


6.3 FORCIBLY STOPPING THE SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553

7. WRITING, READING, AND VERIFYING THE SEQUENCE PROGRAM


AND PMC PARAMETER DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554
7.1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 555
7.1.1 C Input/Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 556
7.2 SET ITEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 557
7.3 OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559
7.3.1 Transfer to and from a FANUC LADDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559
7.3.2 Transfer to and from a FANUC FD Cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559
7.3.3 Storage to Flash ROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561
7.3.4 Storage to a Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563
7.3.5 Data Input to and Output from other Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 569
7.3.6 Setting the Transfer Speed ([SPEED] Soft Key) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 570
7.3.7 Transfer to and from a ROM WRITER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571
7.3.8 Notes on Using an MDI Keyboard without Cursor Keys
(when using the FS20 PMCMODEL SA1/SA3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 572
7.4 I/O ERROR MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 573
7.5 SEQUENCE PROGRAM COPY FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
7.5.1 Copy Title Data [CPYTTL] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
7.5.2 Copy a Ladder Program [CPYLAD] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
7.5.3 Copy Symbol Data and Comment Data [CPYSYM] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
7.5.4 Copy Message Data [CPYMSG] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
7.5.5 Copy the Sequence Programs [CPYALL] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576
7.5.6 Copy I/O Module Data [CPYMDL] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576
7.6 RESTRICTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576

8. FUNCTIONS FOR DISPLAYING MEMORY AREAS AND DEBUGGING


THE PROGRAM (MONIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 577
8.1 DISPLAYING THE GDT (GLOBAL DESCRIPTOR TABLE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 578
8.1.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 578
8.1.2 Descriptions of Displayed Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 580
8.2 DISPLAYING THE MEMORY ALLOCATION INFORMATION OF A USER
PROGRAM CODED IN C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 581
8.2.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 581
8.2.2 Displayed Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 583
8.3 DEBUGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 584
8.3.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 584
8.3.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 584
8.3.3 Parameter Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 585
8.3.4 Screen for Displaying Traced Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
8.3.5 Enabling Automatic Debugging at Poweron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
8.3.6 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
8.4 LADDER DEBUGGING FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 589
8.4.1 Screen of Ladder Debugging Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 589
8.4.2 Soft Key Menu of Ladder Debugging Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590

c8
B61863E/14 Table of contents

8.4.3 Step Operation [STEP] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 591


8.4.4 Stop Function of Break with Condition [BRKCTL] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 592
8.5 ONLINE FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 594
8.5.1 Online Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 595
8.5.2 Setting of online connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 595
8.5.3 Online Function by Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 599
8.5.4 Communication Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602
8.5.5 About Connection Log of Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603

9. ERROR MESSAGES (FOR EDIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605

10. ERROR MESSAGES (FOR I/O) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607

11. PMC PROGRAMMER (DPL/MDI) (ONLY FOR THE Power Mate) . . . . . . . . . . . . . . 608
11.1 SELECTING THE PMC PROGRAMMER MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 610
11.2 SETTING AND DISPLAYING SYSTEM PARAMETERS (SYSTEM PARAM) . . . . . . . . . . . . . . 611
11.3 EDITING THE SEQUENCE PROGRAM (EDIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612
11.4 EDITING LADDER MNEMONICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 613
11.4.1 Starting Ladder Mnemonics Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 613
11.4.2 Confirming the Ladder Mnemonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 614
11.4.3 Modifying the Ladder Mnemonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 616
11.4.4 Ending Ladder Mnemonics Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 618
11.5 STARTING AND STOPPING THE SEQUENCE PROGRAM (RUN/STOP) . . . . . . . . . . . . . . . . . 619
11.6 ERROR MESSAGES (FOR LADDER MNEMONICS EDITING) . . . . . . . . . . . . . . . . . . . . . . . . . 620
11.7 STORING THE SEQUENCE PROGRAM INTO FLASH EEPROM (I/O)
(ONLY FOR THE Power MateH AND Power Mate iD/H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 621
11.8 ERROR DETAILS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 622
11.9 INPUT/OUTPUT LADDER/PMCPARAMETER BY MDI/DPL . . . . . . . . . . . . . . . . . . . . . . . . . . 623
11.9.1 Input/Output Method to Office Programmer (Pg Mate/Mark II) (Fixed 9600bit/Sec.) . . . . . 623
11.9.2 Input/Output Method to FANUC FLOPPY CASSETTE (Fixed 4800bit/Sec.) . . . . . . . . . . . . 623
11.10 ONLINE DEBUGGING FUNCTION (ONLY FOR Power MateD/H and Power Mate iD/H) . 624
11.10.1 Starting and Stopping the Online Debugging Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 624
11.11 ERROR LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 626

IV. PMCNB6 MANIPULATION


1. OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 629

2. SOFT KEYBASED PMC MENU SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . 630


2.1 PMC BASIC MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 631
2.2 PMC SCREEN TRANSITION AND RELATED SOFT KEYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 633

3. DISPLAYING PMC INPUT/OUTPUT SIGNALS AND


INTERNAL RELAY (PMCDGN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 635
3.1 TITLE DATA DISPLAY (TITLE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 636

c9
Table of contents B61863E/14

3.2 TITLE DATA EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 637


3.3 SIGNAL STATUS DISPLAY (STATUS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 638
3.4 ALARM SCREEN (ALARM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 639
3.5 TRACE SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 640
3.5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 640
3.5.2 Setting of Trace Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 641
3.5.3 Execution of Trace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 647
3.5.4 Operation after Execution of Trace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 648
3.5.5 Comparison With the Function of FS15B (PMCNB/NB2) . . . . . . . . . . . . . . . . . . . . . . . . . 650
3.6 I/O LINK MONITOR AND ALLOCATION OF I/O UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 654
3.6.1 I/O Link Monitor screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 655
3.6.2 I/O Unit Allocation Viewer screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 657
3.6.3 I/O Unit Allocation Editor screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 658

4. PMC DATA SETTING AND DISPLAY (PMCPRM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 662


4.1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 663
4.2 METHOD FOR ENTERING PMC PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 664
4.3 CONTINUOUS DATA ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 665
4.4 TIMER SCREEN (TIMER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 666
4.5 COUNTER SCREEN (COUNTR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 667
4.6 KEEP RELAY SCREEN (KEEPRL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 668
4.7 DATA TABLE (DATA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 670

5. SETTING MENU (SETING) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 672


5.1 SCREEN FOR DISPLAYING GENERAL SETTINGS (GENERAL) . . . . . . . . . . . . . . . . . . . . . . . 673
5.2 SCREEN FOR DISPLAYING THE SETTING DATA RELATED TO
EDITING AND DEBUGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 674
5.3 SCREEN FOR SETTING/DISPLAYING ONLINE MONITOR PARAMETERS (ONLINE) . . . . . 675
5.4 SCREEN FOR DISPLAYING SETTING DATA RELATED TO C LANGUAGE FUNCTION . . . 677

6. LADDER DIAGRAM MONITOR AND EDITOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 678


6.1 LADDER DIAGRAM MONITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 681
6.1.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 682
6.1.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 684
6.1.3 Functional Instruction Data Table Viewer Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 688
6.1.4 Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 691
6.1.5 Display Format for Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 698
6.1.6 Functional Instructions of Special Monitor for Mat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 701
6.2 LADDER DIAGRAM EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702
6.2.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 704
6.2.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 705
6.2.3 Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 710
6.2.4 Error Messages and Their Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 715
6.2.5 How to Correct LADDER Program that Never Stops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 720
6.3 NET EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 721
6.3.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 722
6.3.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 723

c10
B61863E/14 Table of contents

6.3.3 Functional Instruction List Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 727


6.3.4 Functional Instruction Data Table Editor Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 728
6.3.5 Error Messages and Their Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 732
6.3.6 Structure of Valid Net . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 734
6.4 PROGRAM LIST VIEWER SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 735
6.4.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 736
6.4.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 739
6.4.3 Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 740
6.5 PROGRAM LIST EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 742
6.5.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 743
6.5.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 745
6.5.3 Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 746
6.6 COLLECTIVE MONITOR FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 747
6.6.1 Structures of Collective Monitor Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 748
6.6.2 Operations of Collective Monitor Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 749
6.6.3 How to Pick Up a Ladder Diagram Net . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750

7. PASSWORD PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 752


7.1 SPECIFICATIONS OF PASSWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 753
7.2 PASSWORD AND SWITCHING SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 754
7.2.1 Using One of RPassword and RWPassword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 754
7.2.2 Using Both of RPassword and RWPassword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 755

8. WRITING, READING, AND COMPARING SEQUENCE PROGRAMS


AND PMC PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 756
8.1 I/O SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 757
8.2 OUTPUTTING TO AND INPUTTING FROM MEMORY CARDS . . . . . . . . . . . . . . . . . . . . . . . . 760
8.3 MEMORY CARD LIST SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 764
8.4 OUTPUTTING TO AND INPUTTING FROM FLASH ROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 766
8.5 OUTPUTTING TO AND INPUTTING FROM FLOPPY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 769
8.6 FLOPPY LIST SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 773
8.7 OUTPUTTING TO AND INPUTTING FROM OTHER INPUT/OUTPUT DEVICES . . . . . . . . . 774
8.8 PORT SETTING SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 777
8.9 I/O SCREEN ERROR MESSAGES (PMCNB6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 779

9. STARTING AND STOPPING SEQUENCE PROGRAMS . . . . . . . . . . . . . . . . . . . . . . . . 783

V. FS16i/18i/21iB PMCSA1/SB7 MANIPULATION


1. SCREEN OPERATION FOR PMCSA1/SB7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 787
1.1 SCREEN OPERATION FOR PMCSA1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 788
1.1.1 Structure of Software Key in PMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 788
1.1.2 Addition of System Keep Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 788
1.2 SCREEN OPERATION FOR PMCSB7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 789
1.2.1 Structure of Software Key in PMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 789

c11
Table of contents B61863E/14

1.2.2 Expansion of Symbol Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 790


1.2.3 Addition of System Keep Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 790

2. SETTING FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 791


2.1 SWITCHING SCREENS FOR SETTING PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 792
2.2 SETTING SCREEN OF GENERAL FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 793
2.3 CAUTION SCREEN OF THE SETTING PARAMETER FOR THE SELECTABLE
I/O LINK ASSIGNMENT FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 795
2.4 SETTING PARAMETER SCREEN FOR THE SELECTABLE I/O LINK
ASSIGNMENT FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 796
2.5 PROGRAMMER PROTECTION FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 797
2.5.1 PROGRAMMER ENABLE (PMCSB7: K900.1, PMCSA1: K17.1) . . . . . . . . . . . . . . . . . . 798
2.5.2 HIDE PMC PROGRAM (PMCSB7: K900.0, PMCSA1: K17.0) . . . . . . . . . . . . . . . . . . . . . 798
2.5.3 EDIT ENABLE (PMCSB7: K901.6, PMCSA1: K18.6) . . . . . . . . . . . . . . . . . . . . . . . . . . . 799
2.5.4 ALLOW PMC STOP (PMCSB7: K902.2, PMCSA1: K19.2) . . . . . . . . . . . . . . . . . . . . . . . 799
2.5.5 RAM WRITE ENABLE (PMCSB7: K900.4, PMCSA1: K17.4) . . . . . . . . . . . . . . . . . . . . . 800
2.5.6 DATA TBL CNTL SCREEN (PMCSB7: K900.7, PMCSA1: K17.7) . . . . . . . . . . . . . . . . . 800
2.5.7 IO GROUP SELECTION (K906.1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800
2.6 EXAMPLE FOR SETTING PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 801

3. LADDER DIAGRAM MONITOR (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 803


3.1 LADDER DIAGRAM MONITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 805
3.1.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 806
3.1.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 808
3.1.3 Setting the Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 812
3.1.4 Display Format for Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 818
3.2 FUNCTIONAL INSTRUCTION DATA TABLE VIEWER SCREEN . . . . . . . . . . . . . . . . . . . . . . . 821
3.2.1 Screen Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 822
3.2.2 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 822
3.3 PROGRAM LIST VIEWER SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 824
3.3.1 Detail Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 824
3.3.2 Brief Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 826
3.3.3 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 827
3.3.4 Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 828

4. COLLECTIVE MONITOR FUNCTION (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 831


4.1 CALLING SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 832
4.2 SCREEN CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 833
4.3 SCREEN OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 834
4.4 ALARM MESSAGE AND COUNTERMEASURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 837

5. LADDER DIAGRAM EDITOR FUNCTION (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . 838


5.1 LADDER DIAGRAM EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 839
5.2 SCREEN CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 840
5.3 SCREEN OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 841
5.4 SETTING SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 844

c12
B61863E/14 Table of contents

5.5 NET EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 846


5.5.1 Screen Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 846
5.5.2 Screen Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 847
5.6 STRUCTURE OF VALID NET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 852
5.7 FUNCTIONAL INSTRUCTION LIST SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 853
5.8 FUNCTIONAL INSTRUCTION DATA TABLE EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . 854
5.9 PROGRAM LIST EDITOR SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 855
5.9.1 Screen Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 856
5.9.2 Setting Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 857
5.10 ALARM MESSAGE AND COUNTERMEASURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 858

6. SIGNAL TRACE FUNCTION (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 864


6.1 SIGNAL TRACE SCREEN (INITIAL SCREEN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 865
6.2 SETTING OF TRACE PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 866
6.3 SETTING OF SAMPLING ADDRESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 868
6.4 EXECUTION OF TRACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 870
6.5 OPERATION AFTER EXECUTION OF TRACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 871
6.6 AUTOMATIC START OF TRACE SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 874

7. SELECTABLE I/O LINK ASSIGNMENT FUNCTION (PMCSB7) . . . . . . . . . . . . . . . . 875


7.1 OUTLINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 876
7.2 EXAMPLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 879
7.3 NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 883

8. SYSTEM PARAMETER (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 884

9. I/O LINK CONNECTING CHECK SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 886

10. ONLINE FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 887


10.1 ONLINE SETTING SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 888
10.2 SETTING OF ONLINE CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 889
10.2.1 How to Set at PMC Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 889
10.2.2 Setting of Online Connection by NC Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 890
10.3 ONLINE FUNCTION BY ETHERNET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 891
10.3.1 Setting of Ethernet Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 891
10.3.2 Starting online communication by offline programmer (Ethernet connection) . . . . . . . . . . . . 892
10.4 COMMUNICATION STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 895
10.5 ABOUT CONNECTION LOG OF ETHERNET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 897

VI. STEP SEQUENCE FUNCTION


1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 901
1.1 STEP SEQUENCE METHOD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 902
1.2 GRAPHICAL SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 905

c13
Table of contents B61863E/14

1.3 PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 906

2. STEP SEQUENCE BASICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 908


2.1 TERMINOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 909
2.2 EXECUTION OF STEP SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 918

3. CONFIGURATION AND OPERATION OF STEPSEQUENCE PROGRAMS . . . . . . 922


3.1 STEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 923
3.2 INITIAL STEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 925
3.3 TRANSITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 926
3.4 DIVERGENCE OF SELECTIVE SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 927
3.5 CONVERGENCE OF SELECTIVE SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 927
3.6 DIVERGENCE OF SIMULTANEOUS SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 928
3.7 CONVERGENCE OF SIMULTANEOUS SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 929
3.8 JUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 930
3.9 LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 930
3.10 BLOCK STEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 931
3.11 INITIAL BLOCK STEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 932
3.12 END OF BLOCK STEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 932

4. EXTENDED LADDER INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 933


4.1 FUNCTIONAL INSTRUCTION TRSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 934
4.2 PMC ADDRESS (S ADDRESS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 934

5. SPECIFICATION OF STEP SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 935


5.1 SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 936
5.2 GENERAL RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 937
5.3 EXCLUSIVE CONTROL FOR FUNCTIONAL INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 943

6. CRT/MDI OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 946


6.1 DISPLAYING OF SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 947
6.1.1 Program Configuration List (Main Screen) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 947
6.1.2 Step Sequence Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 948
6.1.3 Ladder Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 950
6.2 TIMER SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 953
6.2.1 Time Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 953
6.2.2 Monitoring Elapsed Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 954
6.3 MONITOR TIME SCREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 955
6.4 EDITING FUNCTION OF LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 957
6.4.1 Program Configuration List (Main Screen) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 957
6.4.2 Step Sequence Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 958
6.4.3 Ladder Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 960
6.5 CORRESPONDING FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 962
6.6 COMPATIBILITY OF LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 963

c14
B61863E/14 Table of contents

VII. PMC PROGRAMMER (SYSTEM P series)


1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 967

2. FUNCTIONS OF PROCESSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 968

3. COMPONENT UNITS AND CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 970


3.1 COMPONENT UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 971
3.2 CONNECTIONS OF UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 972
3.3 KEYBOARD OF SYSTEM P SERIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 975
3.3.1 LOAD Key (System Program Loading Key) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 976
3.3.2 F Keys (F1 to F0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 976
3.3.3 R Keys (R0 to R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 977
3.3.4 Data Keys and Screen Scroll Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 978
3.4 SETTING OF I/O DEVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 979

4. OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 981
4.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 982
4.2 PREPARATION BEFORE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 984
4.2.1 System Floppy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 984
4.2.2 Limitations with the SYSTEM P Mate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 984
4.2.3 Loading of Floppy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 984
4.2.4 FANUC LADDER System Floppy Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 985
4.2.5 Programmer Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 986
4.2.6 Parameter Setting and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 987
4.3 PROGRAM EDITING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 990
4.3.1 Data Display and Setting (Title, Symbol, Ladder Program, Comment,
Message, I/O Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 990
4.3.2 Programming from Keyboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 996
4.3.3 Alter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 997
4.3.4 Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000
4.3.5 Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1001
4.3.6 Location Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1001
4.3.7 Display of Ladder Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1003
4.3.8 Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1004
4.3.9 Editing end . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1004
4.4 INPUT OF PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1005
4.4.1 Source Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1005
4.4.2 ROM Format Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1007
4.5 OUTPUT OF PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1010
4.5.1 Source Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1010
4.5.2 Paper Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1013
4.5.3 ROM Format Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1014
4.6 COLLATION OF PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1017
4.6.1 Collation of Source Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1017
4.6.2 ROM Format Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1017

c15
Table of contents B61863E/14

4.7 DELETION OF PROGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1018


4.8 SPECIAL USES OF THE R3 KEY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1019
4.9 DIRECT EDITING BY LADDER DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1020
4.9.1 Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1020
4.9.2 Limitations in SYSTEM P Mate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1020
4.9.3 Selection of Program Menu by Soft Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1020
4.9.4 Sequence Program Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1022
4.9.5 Substitution of Sequence Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1025
4.9.6 Additions to Sequence Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1025
4.9.7 Deleting a Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1028
4.9.8 Searching a Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1029
4.9.9 Copying a Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1031
4.9.10 Moving a Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1032
4.9.11 Symbol Data Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1033
4.9.12 Compressed Input by [COMAND] Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1034
4.9.13 Ending Edit of a Sequence Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1034
4.10 INPUT/OUTPUT OF LADDER PROGRAM WITH PG AND FLOPPY
CASSETTE/FA CARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1035
4.10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1035
4.10.2 Setting I/O Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1035
4.10.3 Program Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1035
4.10.4 Program Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1036
4.10.5 Program Collation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1037

5. FILE EDITING FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1038


5.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1039
5.2 CONFIGURATION OF COMMAND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1042
5.3 FDLIST COMMAND FILE ATTRIBUTE DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1043
5.4 RENAME COMMAND FILE ATTRIBUTE CHANGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1044
5.5 SCRATCH COMMAND DELETION OF FILES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1045
5.6 CONDENSE COMMAND RELEASE OF DELETED AREA . . . . . . . . . . . . . . . . . . . . . . . . . 1045
5.7 REMOVE COMMAND FILE COPY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1046

APPENDIX
A. ERROR CODES LIST (FOR FANUC LADDER PG) . . . . . . . . . . . . . . . . . . . . . . . . . . 1051

B. WINDOW FUNCTION DESCRIPTION (PMCPA1/PA3/


SA1/SA2/SA3/SA5/SB/SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) . . . . . . . . . . . . 1054
B.1 FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1055
B.2 LOWSPEED RESPONSE AND HIGHSPEED RESPONSE OF WINDOW FUNCTION . . . . 1055
B.3 LIST OF WINDOW FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1056
B.4 FORMATS AND DETAILS OF CONTROL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1059
B.4.1 Reading CNC System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1060
B.4.2 Reading a Tool Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1062

c16
B61863E/14 Table of contents

B.4.3 Writing a Tool Offset (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1064


B.4.4 Reading a Workpiece Origin Offset Value (not Supported by the Power MateD or F) . . . 1066
B.4.5 Writing a Workpiece Origin Offset Value (:Lowspeed Response)
(not Supported by the Power MateD or F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
B.4.6 Reading a Parameter (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1070
B.4.7 Writing a Parameter (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1072
B.4.8 Reading Setting Data (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1074
B.4.9 Writing Setting Data (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1076
B.4.10 Reading a Custom Macro Variable (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . 1078
B.4.11 Writing a Custom Macro Variable (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . 1081
B.4.12 Reading the CNC Alarm Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1083
B.4.13 Reading the Current Program Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1088
B.4.14 Reading the Current Sequence Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1090
B.4.15 Reading the Actual Velocity of Controlled Axes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1092
B.4.16 Reading the Absolute Position (Absolute Coordinates) of Controlled Axes . . . . . . . . . . . . . 1094
B.4.17 Reading the Machine Position (Machine Coordinates) of Controlled Axes . . . . . . . . . . . . . 1096
B.4.18 Reading a Skip Position (Stop Position of Skip Operation (G31)) of Controlled Axes . . . . 1098
B.4.19 Reading the Servo Delay for Controlled Axes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100
B.4.20 Reading the Acceleration/Deceleration Delay on Controlled Axes . . . . . . . . . . . . . . . . . . . . 1102
B.4.21 Reading Modal Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1104
B.4.22 Reading Diagnosis Data (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1109
B.4.23 Reading A/D Conversion Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1111
B.4.24 Reading Tool Life Management Data (Tool Group No.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1115
B.4.25 Reading Tool Life Management Data (Number of Tool Groups) . . . . . . . . . . . . . . . . . . . . . 1117
B.4.26 Reading Tool Life Management Data (Number of Tools) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1119
B.4.27 Reading Tool Life Management Data (Tool Life)
(not Supported by the Power Mate D, F, or Series 21TA) . . . . . . . . . . . . . . . . . . . . . . . . . 1121
B.4.28 Reading Tool Life Management Data (Tool Life Counter) . . . . . . . . . . . . . . . . . . . . . . . . . . 1123
B.4.29 Reading Tool Life Management Data (Tool Length Compensation No. (1): Tool No.) . . . . 1125
B.4.30 Reading Tool Life Management Data (Tool Length Compensation
No. (2): Tool Order No.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1127
B.4.31 Reading Tool Life Management Data (Cutter Compensation No. (1): Tool No.) . . . . . . . . . 1129
B.4.32 Reading Tool Life Management Data (Cutter Compensation No. (2): Tool Order No.) . . . . 1131
B.4.33 Reading Tool Life Management Data (Tool Information (1) : Tool No.) . . . . . . . . . . . . . . . 1133
B.4.34 Reading Tool Life Management Data (Tool Information (2): Tool Order No.) . . . . . . . . . . . 1135
B.4.35 Reading Tool Life Management Data (Tool No.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1137
B.4.36 Reading the Actual Spindle Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1139
B.4.37 Entering Data on the Program Check Screen (:Lowspeed Response)
(not available for Power MateD/F, Series 21TA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1141
B.4.38 Reading Clock Data (Date and Time) (not available for Power MateF) . . . . . . . . . . . . . . . 1143
B.4.39 Entering Torque Limit Data for the Digital Servo Motor (:Lowspeed Response) . . . . . . 1145
B.4.40 Reading Load Information of the Spindle Motor (Serial Interface) . . . . . . . . . . . . . . . . . . . . 1147
B.4.41 Reading a Parameter (not available for Power MateD/F, Series 21TA) . . . . . . . . . . . . . . 1150
B.4.42 Reading Set Data (not available for Power MateD/F, Series 21TA) . . . . . . . . . . . . . . . . . 1151
B.4.43 Reading Diagnosis Data (not available for Power MateD/F, Series 21TA) . . . . . . . . . . . . 1152
B.4.44 Reading a Character String of the CNC Program Being Executed in the Buffer . . . . . . . . . 1153
B.4.45 Reading the Relative Position on a Controlled Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1155
B.4.46 Reading the Remaining Travel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1157

c17
Table of contents B61863E/14

B.4.47 Reading CNC Status Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1159


B.4.48 Reading Value of the Pcode Macro Variable (:Lowspeed Response) . . . . . . . . . . . . . . . 1161
B.4.49 Writing Value of the Pcode Macro Variable (:Lowspeed Response) . . . . . . . . . . . . . . . . 1163
B.4.50 Reading the Tool Life Management Data (Tool Life Counter Type) . . . . . . . . . . . . . . . . . . . 1165
B.4.51 Registering the Tool Life Management Data (Tool Group) (:Lowspeed Response) . . . . . 1167
B.4.52 Writing the Tool Life Management Data (Tool Life) (:Lowspeed Response) . . . . . . . . . 1169
B.4.53 Writing the Tool Life Management Data (Tool Life Counter) (:Lowspeed Response) . . 1171
B.4.54 Writing the Tool Life Management Data (Tool Life Counter Type)
(:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1173
B.4.55 Writing the Tool Life Management Data
(Tool Length Offset Number (1) : Tool Number) (:Lowspeed Response) . . . . . . . . . . . . 1175
B.4.56 Writing the Tool Life Management Data (Tool Length Offset Number (2) :
Tool Operation Sequence Number) (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . 1177
B.4.57 Writing the Tool Life Management Data (Cutter Compensation Number (1) :
Tool Number) (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1179
B.4.58 Writing the Tool Life Management Data (Cutter Compensation Number (2) :
Tool Operation Sequence Number) (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . 1181
B.4.59 Writing the Tool Life Management Data
(Tool Condition (1) : Tool Number) (:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . 1183
B.4.60 Writing the Tool Management Data
(Tool Condition (2) : Tool Operation Sequence Number) (:Lowspeed Response) . . . . . . 1185
B.4.61 Writing the Tool Life Management Data (Tool Number) (:Lowspeed Response) . . . . . . 1187
B.4.62 Reading the Estimate Disturbance Torque Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1189
B.4.63 Reading the Current Program Number (8digit Program Numbers)
(not available for Power MateD/F, Series 21TA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1193
B.4.64 Reading Tool Life Management Data (Tool Group Number) . . . . . . . . . . . . . . . . . . . . . . . . 1195
B.4.65 Reading Tool Life Management Data (Tool Length Offset Number 1) . . . . . . . . . . . . . . . . . 1197
B.4.66 Reading Tool Life Management Data (Tool Diameter Offset Number 1) . . . . . . . . . . . . . . . 1199
B.4.67 Reading Tool Life Management Data (Tool Information 1) . . . . . . . . . . . . . . . . . . . . . . . . . 1201
B.4.68 Writing (Registering) Tool Life Management Data (Tool Group Number)
(:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1203
B.4.69 Writing Tool Life Management Data (Tool Length Offset Number 1)
(:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1206
B.4.70 Writing Tool Life Management Data (Tool Radius Offset Number 1)
(:Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1208
B.4.71 Writing Tool Life Management Data (Tool Information 1) (:Lowspeed Response) . . . . . 1210
B.4.72 Reading Actual Spindle Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1213
B.4.73 Reading Fine Torque Sensing Data (Statistical Calculation Results) . . . . . . . . . . . . . . . . . . 1217
B.4.74 Reading Fine Torque Sensing Data (Store Data) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1219
B.4.75 Specifying the Number of the Program for I/O Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1227
B.4.76 Preset of relative coordinate (:Lowspeed response)
(not available for Power Mate and Series 21TA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1229
B.4.77 Deleting the Tool life Management Data (Tool group) (:Lowspeed response) . . . . . . . . . 1232
B.4.78 Deleting the Tool life Management Data (Tool data) (:Lowspeed response) . . . . . . . . . . 1234
B.4.79 Deleting the Tool life Management Data (Tool life counter and Tool condition)
(:Lowspeed response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1236
B.4.80 Writing the Tool life Management Data (Arbitrary group number)
(:Lowspeed response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1238
B.4.81 Writing the Tool life Management Data (Remaining tool life) (:Lowspeed response) . . . 1240
B.4.82 Reading the Current Screen Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1242

c18
B61863E/14 Table of contents

B.4.83 Reading Detailed Alarm Information (:Lowspeed type) . . . . . . . . . . . . . . . . . . . . . . . . . . 1245

C. WINDOW FUNCTION DESCRIPTION (PMCNB/NB2/NB6) . . . . . . . . . . . . . . . . . . . 1249


C.1 FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1250
C.2 LOWSPEED RESPONSE AND HIGHSPEED RESPONSE OF WINDOW FUNCTION . . . . 1251
C.2.1 Functional Instruction WINDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1252
C.2.2 Functional Instruction WINDW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1254
C.3 FORMAT AND DETAILS OF THE CONTROL DATA OF
THE WINDR FUNCTIONAL INSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1256
C.3.1 Reading a Tool Offset (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1256
C.3.2 Reading a Workpiece Origin Offset Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1258
C.3.3 Reading a Parameter (Setting Data) (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . 1259
C.3.4 Reading a Custom Macro Variable (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . 1260
C.3.5 Reading the CNC Alarm Status (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1261
C.3.6 Reading the Current Program Number (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . 1262
C.3.7 Reading the Current Sequence Number (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . 1263
C.3.8 Reading the Actual Velocity of Controlled Axes (Lowspeed Response) . . . . . . . . . . . . . . . 1264
C.3.9 Reading the Absolute Position on a Controlled Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1264
C.3.10 Reading the Machine Position (Machine Coordinates) of Controlled Axes . . . . . . . . . . . . . 1266
C.3.11 Reading a Skip Position (Stop Position of Skip Operation (G31)) of Controlled Axes
(Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1267
C.3.12 Reading the Servo Delay for Controlled Axes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1268
C.3.13 Reading the Acceleration/Deceleration Delay on Controlled Axes . . . . . . . . . . . . . . . . . . . . 1268
C.3.14 Reading Modal Data (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1269
C.3.15 Reading Diagnosis Data (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1275
C.3.16 Reading A/D Conversion Data for the Feed Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1276
C.3.17 Reading the Tool Life Management Data (Tool Group Number) (Lowspeed Response) . . 1278
C.3.18 Reading the Tool Life Management Data (Number of Tool Groups)
(Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1279
C.3.19 Reading Tool Life Management Data (Number of Tools) (Lowspeed Response) . . . . . . . . 1279
C.3.20 Reading Tool Life Management Data (Tool Life) (Lowspeed response) . . . . . . . . . . . . . . 1280
C.3.21 Reading Tool Life Management Data (Tool Life Counter) (Lowspeed Response) . . . . . . . 1280
C.3.22 Reading Tool Life Management Data (Tool Life Counter Type) (Lowspeed Response) . . 1281
C.3.23 Reading Tool Life Management Data (Tool Length Compensation No.1)
(Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1282
C.3.24 Reading Tool Life Management Data (Tool Length Compensation No.2)
(Lowspeed response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1283
C.3.25 Reading Tool Life Management Data (Cutter Compensation No.1)
(Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1284
C.3.26 Reading Tool Life Management Data (Cutter Compensation No.2)
(Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1285
C.3.27 Reading Tool Life Management Data (Tool Information 1) (Lowspeed Response) . . . . . . 1286
C.3.28 Reading Tool Life Management Data (Tool Information 2) (Lowspeed Response) . . . . . . 1287
C.3.29 Reading Tool Life Management Data (Tool Number) (Lowspeed Response) . . . . . . . . . . . 1287
C.3.30 Reading Clock Data (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1288
C.3.31 Reading the Relative Position on a Controlled Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1289
C.3.32 Reading the Remaining Travel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1290
C.3.33 Reading an Estimate Disturbance Torque Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1291

c19
Table of contents B61863E/14

C.3.34
Reading the Machining Time (Lowspeed Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1292
C.3.35
Reading the Load Current (A/D Conversion Data) for the Spindle Motor . . . . . . . . . . . . . . 1293
C.3.36
Reading the Tool Offset Data According to the Specified Tool Number . . . . . . . . . . . . . . . 1294
C.3.37
Reading Tool Life Management Data (Tool Group Numbers) (Lowspeed Type) . . . . . . . . 1295
C.3.38
Reading Tool Life Management Data (Tool Length Compensation Number 1)
(Lowspeed Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1296
C.3.39 Reading Tool Life Management Data (Cutter Compensation Number 1)
(Lowspeed Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1297
C.3.40 Reading Tool Life Management Data (Tool Information 1) (Lowspeed Type) . . . . . . . . . . 1298
C.3.41 Reading Real Parameters (Lowspeed Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1299
C.3.42 Reading the actual Machine Position (Machine Coordinates) of Controlled Axes. . . . . . . . 1300
C.3.43 Reading Fine Torque Sensing Data (Statistical Calculation Results). . . . . . . . . . . . . . . . . . . 1301
C.3.44 Reading Fine Torque Sensing Data (Store Data) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1302
C.3.45 Reading detailed information of CNC alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1306
C.4 FORMAT AND DETAILS OF THE CONTROL DATA OF THE
WINDW FUNCTIONAL INSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1309
C.4.1 Writing a Tool Offset Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1310
C.4.2 Writing a Parameter (Setting Data) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1311
C.4.3 Writing a Custom Macro Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1312
C.4.4 Writing a Data on the Program Check Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1313
C.4.5 Writing the Torque Limit Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1314
C.4.6 Writing the Tool Life Management Data (Tool Group Number) . . . . . . . . . . . . . . . . . . . . . . 1315
C.4.7 Writing the Tool Life Management Data (Tool Life) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1315
C.4.8 Writing the Tool Life Management Data (Tool Life Counter) . . . . . . . . . . . . . . . . . . . . . . . . 1316
C.4.9 Writing the Tool Life Management Data (Tool Life Counter Type) . . . . . . . . . . . . . . . . . . . 1316
C.4.10 Writing the Tool Life Management Data (Tool Length Compensation Number 1) . . . . . . . . 1317
C.4.11 Writing the Tool Life Management Data (Tool Length Compensation Number 2) . . . . . . . . 1317
C.4.12 Writing the Tool Life Management Data (Cutter Compensation Number 1) . . . . . . . . . . . . 1318
C.4.13 Writing the Tool Life Management Data (Cutter Compensation Number 2) . . . . . . . . . . . . 1318
C.4.14 Writing the Tool Life Management Data (Tool Information 1) . . . . . . . . . . . . . . . . . . . . . . . 1319
C.4.15 Writing the Tool Life Management Data (Tool Information 2) . . . . . . . . . . . . . . . . . . . . . . . 1319
C.4.16 Writing the Tool Life Management Data (Tool Number) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1320
C.4.17 Writing the Tool Offset Data According to the Specified Tool Number . . . . . . . . . . . . . . . . 1321
C.4.18 Writing the Superposition Move Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1322
C.4.19 Writing the Feedrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1324
C.4.20 Writing Tool Life Management Data (Tool Group Numbers) . . . . . . . . . . . . . . . . . . . . . . . . 1325
C.4.21 Writing Tool Life Management Data (Tool Length Compensation Number 1) . . . . . . . . . . . 1326
C.4.22 Writing Tool Life Management Data (Cutter Compensation Number 1) . . . . . . . . . . . . . . . 1327
C.4.23 Writing Tool Life Management Data (Tool Information 1) . . . . . . . . . . . . . . . . . . . . . . . . . . 1328
C.4.24 Writing Real Parameters (Lowspeed Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1329

D. WINDOW FUNCTION DESCRIPTION (FS16/16iLA) . . . . . . . . . . . . . . . . . . . . . . . . . 1330


D.1 OUTLINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1331
D.2 FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1332
D.2.1 Transfer Between Data Area and Nonvolatile Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1332
D.2.2 Reading of the Comment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1336
D.2.3 Reading and Writing the Laser Command Data and Laser Setting Data . . . . . . . . . . . . . . . . 1337

E. WINDOW FUNCTION DESCRIPTION (FS16W) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1340


E.1 READING THE WIRE DIAMETER OFFSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1341

c20
B61863E/14 Table of contents

E.2 WRITING THE WIRE DIAMETER OFFSET (:LOWSPEED RESPONSE) . . . . . . . . . . . . . . 1343


E.3 READING THE PARAMETER (:LOWSPEED RESPONSE) . . . . . . . . . . . . . . . . . . . . . . . . . . 1345
E.4 WRITING THE PARAMETER (:LOWSPEED RESPONSE) . . . . . . . . . . . . . . . . . . . . . . . . . . 1347
E.5 READING SETTING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1352
E.6 WRITING SETTING DATA (LOWSPEED TYPE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1353
E.7 READING THE CNC ALARM STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1356
E.8 READING MODEL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1357
E.9 READING MACHINING DISTANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1361
E.10 READING THE MEASURED POINT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1362
E.11 WRITING THE MEASURED POINT (:LOWSPEED RESPONSE) . . . . . . . . . . . . . . . . . . . . 1364

F. WINDOW FUNCTION DESCRIPTION (FS16PA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1365


F.1 READING OF TOOL SETTING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1366
F.1.1 Data Number, Data Attribute, Data Length, Data Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1368
F.2 WRITING OF TOOL SETTING DATA (LOWSPEED RESPONSE) . . . . . . . . . . . . . . . . . . . . . 1370
F.3 READING TOOL SETTING DATA BY SPECIFYING TOOL NUMBER . . . . . . . . . . . . . . . . . . 1372
F.4 OTHER WINDOW FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1374

G. SIGNAL ADDRESS CONVERSION (FROM THE PMCMODEL


L/M TO THE PMCMODEL SB/SC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1375
G.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1376
G.2 FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1376
G.3 CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1376
G.4 MODIFYING THE CONVERTED SEQUENCE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1377
G.4.1 Modification Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1377

H. CONNECTING THE OPERATORS PANEL FOR FS 0 WITH FS16,


FS18, FS21, OR Power Mate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1378
H.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1379
H.2 CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1382
H.2.1 Connecting the I/O Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1382
H.2.2 Connecting the I/O Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1382
H.3 SIGNALS FOR CONNECTING THE OPERATORS PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . 1383
H.3.1 Emergency Stop Signal (*ESP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1383
H.3.2 Override Signals (*OV1 to *OV8) and Program Protect Key Signal (KEY) . . . . . . . . . . . . 1383
H.3.3 Key Switch Signals (Xn, Xn+2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1383
H.3.4 LED Signals (Ym) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1384
H.4 SPECIFYING ADDRESSES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1386
H.4.1 Parameter Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1386
H.4.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1386

I. EDITING FOR Power MateMODEL D (PMCPA1/PA3) . . . . . . . . . . . . . . . . . . . . . . . 1388


I.1 OUTLINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1389
I.2 COMPATIBILITY WITH CNC BASIC SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1389
I.3 PMC PROGRAMMER (CRT/MDI OR PDP/MDI) [LADDER EDITING FUNCTION] . . . . . . . 1390
I.3.1 Component Units and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1390

c21
Table of contents B61863E/14

I.3.1.1 Component units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1391


I.3.1.2 Connection of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1392
I.3.1.3 Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1392
I.3.2 Specification and Display of System Parameters (SYSPRM) . . . . . . . . . . . . . . . . . . . . . . . . 1393
I.3.3 Condense . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1393
I.4 SYSTEM DIAGRAM OF SOFT KEY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1395

J. APPLICABLE FANUC LADDER EDITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1396


J.1 FANUC LADDER, FANUC LADDERII, FANUC LADDERIII,
LADDER EDITING PACKAGES FANUC LADDERIII (IBM PC/AT)
A08B9210J505, LADDER EDITING PACKAGE (WINDOUS) (IBM PC/AT)
A08B9210J511) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1397
J.2 FANUC LADDER (SYSTEM P SERIES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1399

K. LEVEL UP OF INPUT/OUTPUT FUNCTION WITH MEMORY CARD . . . . . . . . . . . . 1401


K.1 OUTLINE OF LEVELED UP CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1402
K.2 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1403
K.2.1 CNC Offline Programmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1403
K.2.2 Offline Programmer CNC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1405
K.2.3 Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1406
K.3 NB/NB2 DATA COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1408
K.3.1 Data Transfer Between NB (4047 Series) and FANUC LADDER . . . . . . . . . . . . . . . . . . . . 1408
K.3.2 Data Transfer Between NB/NB2 (4048 Series) and FANUC LADDER . . . . . . . . . . . . . . . . 1408
K.3.3 Data Transfer Between NB (4047 Series) and NB (4048 Series) . . . . . . . . . . . . . . . . . . . . . 1409

L. MIGRATION OF LADDER PROGRAMS BETWEEN DIFFERENT MODELS . . . . . 1410


L.1 MIGRATION OF LADDER PROGRAMS FROM Power MateD/H TO Power Mate iD/H . . . 1411
L.2 MIGRATION FROM THE PMCNB/NB2 TO THE PMCNB6 . . . . . . . . . . . . . . . . . . . . . . . . . . 1413
L.3 MIGRATION FROM THE PMCSA5/SB5/SB6 TO THE PMCSB7 . . . . . . . . . . . . . . . . . . . . . . 1414
L.3.1 Addition of System Parameter Ladder Execution Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1415
L.4 MIGRATION FROM THE SERIES 0 AND SERIES 21B TO SERIES 0i . . . . . . . . . . . . . . . . . . 1416
L.4.1 Compatible With Series 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1416
L.4.2 Compatibility With Series 21MODEL B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1420
L.4.3 Limited Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1420

M. ALARM MESSAGE LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1421


M.1 ALARM MESSAGE (PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/SB2/SB3/SB4/SB5/
SB6/SC/SC3/SC4/NB/NB2/NB6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1422
M.2 ALARM MESSAGE (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1429
M.3 SYSTEM ALARM MESSAGES (PMCSC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1434
M.4 SYSTEM ALARM MESSAGES (C LANGUAGE FUNCTION FOR PMCNB/NB2/NB6) . . . . 1436
M.5 SYSTEM ALARM MESSAGES (PMCSB5/SB6/NB6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1437
M.6 PMC SYSTEM ALARM MESSAGES (PMCSB7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1439

N. EXAMPLE OF STEP SEQUENCE PROGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1441

O. STEP SEQUENCE CORRESPONDED C LANGUAGE . . . . . . . . . . . . . . . . . . . . . . . . 1445


O.1 WHILE STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1446

c22
B61863E/14 Table of contents

O.2 DOWHILE STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1448


O.3 FOR STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1450
O.4 IF ELSE STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1452
O.5 SWITCH STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1454

P. CHINESE CHARACTER CODE, HIRAGANA CODE, AND SPECIAL


CODE LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1457

c23
I. PMC SEQUENCE PROGRAM
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

1 SEQUENCE PROGRAM CREATING PROCEDURE

The procedure for creating the sequence program when the CNC machine
tool is controlled by use of the PMC is shown in Fig. 1.
Proceed according to the flow shown in Fig. 1.
The procedure is briefly explained below.

Start of control system


development

Decide the control object (machine, CNC)

Decide the specifications of control


operations
D Calculate the number of DI/DO points
D Estimate the control scale

Create the interface specifications


DI/DO terminal allocation

Create the ladder diagram


Create the addrss table

Entry method of the


sequence program

Key-in
Offline programmer
Specification of the
programmer

NC Enter the sequence program with the offline


programmer key

Store the sequence program into the PMC


RAM board by using the keys of the In necessary correct with the offline
CRT/MDI programmer key 5

If necessary correct with the keys of the When the debugging connect the offline
CRT/MDI programmer to CNC and transfer the
sequence program to Debugging RAM

No
Is there a simulator?

Yes

Debug the sequence program with the


simulator 6

Yes
Should the program be
corrected?
No

Fig. 1 Sequence program creating procedure (1/2)

3
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

Correct with Perform system operation


Debugging RAM 7
the keys of the
CRT/MDI

Yes Should the program


be corrected?

Write into the ROM using the


ROM writer 8

Perform system operation 9

Yes Should the program


be corrected?

No
10
Store the sequence program:
(1) Store in the disk of the offline
programmer
(2) Store in ROM

Output the ladder diagram of the


sequence program to the printer 11

Make sure that the maintenance


drawing is attached to the machine 12

End

Fig. 1 Sequence program creating procedure (2/2)

4
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

1.1 Table 1.1 shows the specification of PMCs.


Note that the program size, processing speed, available function
SPECIFICATION OF commands, internal addresses, and nonvolatile memory addresses of
PMCs some PMCs are different from those of other PMCs.

Table 1.1 PMC specifications (1)


Type of PMC
Specification PMC-PA1 PMC-PA3
of PMC
Program method language Ladder Ladder
Number of ladder level 2 2
1st level execution period 8 ms 8 ms
Mean processing time of 4. 5 * 0. 15
basic command (s/ step) (s/ step)
Program capacity
D Ladder (step) (Note 1,3) Approx. 3, 000 Approx. 5, 000
Approx. 12,000
(Only for Power
Mate D/H) D Power Mate D Data size of each modules
D Symbol, Comment (Note 2,3) 1 to 128KB 1 to 128KB
D Message (Note 3) 0.1 to 64KB 0.1 to 64KB Program size
MEMORY- Total
D Language only capacity
MODULE OnePath TwoPath
Command Basic command 12 kinds 14 kinds control control
Function command 47 kinds 64 kinds
Internal relay (R) 1100 byte 1118 byte A 256KB 62KB 24KB
Message request (A) 25 byte 25 byte
Keepmemory B 512KB 128KB 64KB
D Variable timer (T) 80 byte 80 byte
D Counter (C) 80 byte 80 byte
C 768KB 128KB 128KB
D Keep relay (K) 20 byte 20 byte
D Data table (D) 1860 byte 1860 byte
It is impossible that make the data more than the total
Subprogram (P) 512 programs capacity of each modules.
Label (L) 9999 labels
Fixed timer Timer No. 100 Timer No. 100 D Power Mate F
devices specified devices specified
Program size
I/O
D I/O Link (Note 4) (I) 1024 points max. 1024 points max.
(Master) (O) 1024 points max. 1024 points max. 64KB
D I/O Link (Note 7) (I) 64 points max. 64 points max.
(Slave) (O) 64 points max. 64 points max. D Power Mate H
D I/O card (I) 32 points max. 32 points max.
(O) 24 points max. 24 points max. Program size
Sequence program
SRAM SRAM
(Note 5) 128KB

5
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 The size of a symbol and that of a comment are fixed to 1KB.
The size of a message is fixed to 0.1KB.
The maximum size of a symbol and that of a comment are 64KB each.
3 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
4 I/O Link Master function is not available in the Power MateMODEL F.
5 FLASH ROM is used in the Power MateMODEL H.
6 As values indicated with an asterisk (*) in the table, former versions of the programming manual
and catalogs have listed the mean processing time of basic commands, but this manual lists
the execution time for one step. The actual ladder program execution performance (speed) of
each PMC has not been changed.
7 Up to 256/256 points of Input/Output points are available or I/O Link (Slave) in the Power
MateMODEL D/H.

6
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (2)

Type of PMC
PMCSA1 PMCSA2 PMCSA3
Specification
of PMC
Program method language Ladder Ladder Ladder
Number of ladder level 2 2 2
1st level execution period 8 ms 8 ms 8 ms
Mean processing time of basic 5.0 1.5 * 0. 15
command (s/ step) (s/ step) (s/ step)
Program capacity
D Ladder (step) (Note 1,3) Approx. 3, 000 Approx. 3, 000 Approx. 3, 000
Approx. 5, 000 Approx. 5, 000 Approx. 5, 000
Approx. 8, 000 Approx. 8, 000
Approx.12, 000 Approx.12, 000
D Symbol, Comment 1 to 128KB 1 to 128KB 1 to 128KB
(Note 2,3)
D Message (Note 3) 0. 1 to 64KB 0. 1 to 64KB 0. 1 to 64KB
D Language only
Command Basic command 12 kinds 12 kinds 14 kinds
Functioncommand 49 kinds 48 kinds 66 kinds
1100 byte 1118 byte 1118 byte
Internal relay (R) 25 byte 25 byte 25 byte
Message request (A)
Keepmemory 80 byte 80 byte 80 byte
D Variable timer (T)
80 byte 80 byte 80 byte
D Counter (C)
20 byte 20 byte 20 byte
D Keep relay (K)
D Data table (D) 1860 byte 1860 byte 1860 byte
Subprogram (P) 512 programs
Label (L) 9999 labels
Fixed timer Timer No. 100 Timer No. 100 Timer No. 100
devices specified devices specified devices specified
I/O
D I/O link (I) 1024 points max. 1024 points max. 1024 points max.
(O) 1024 points max. 1024 points max. 1024 points max.
D I/O card (I) 156 points max. 156 points max. 156 points max.
(O) 120 points max. 120 points max. 120 points max.
Sequence program EPROM EPROM EPROM
1Mbit1 (128KB) 1Mbit1 (128KB) 1Mbit1 (128KB)
(Note 4) (Note 4)

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 The size of a symbol and that of a comment are fixed to 32KB.
The size of a message is fixed to 2.1KB.
The maximum size of a symbol and that of a comment are 64KB each.
3 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
4 FLASH ROM is used in the FANUC Series 20.
5 As values indicated with an asterisk (*) in the table, former versions of the programming manual
and catalogs have listed the mean processing time of basic commands, but this manual lists
the execution time for one step. The actual ladder program execution performance (speed) of
each PMC has not been changed.
6 Application PMC for FANUC Series 16MODEL A loader control function is PMCSA1.

7
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

Table 1.1 PMC specifications (3)

Type of PMC
Specification PMCSB1 PMCSB2 PMCSB3
of PMC
Program method language Ladder Ladder Ladder
Number of ladder level 2 2 2
1st level excution period 8 ms 8 ms 8 ms
Mean processing time of basic 1.0 1.0 * 0. 15
command (s/ step) (s/ step) (s/ step)
Program capacity
D Ladder (step) (Note 1,3,4) Approx. 5, 000 Approx. 5, 000 Approx. 5, 000
Approx. 8, 000 Approx. 8, 000 Approx. 8, 000
Approx.12, 000 Approx.12, 000 Approx.12, 000
Approx.16, 000 Approx.16, 000 Approx.16, 000
Approx.24, 000 Approx.24, 000
D Symbol, Comment 1 to 128KB 1 to 128KB 1 to 128KB
(Note 2,4)
D Message (Note 4) 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB
D Language only
Command Basic command 12 kinds 12 kinds 14 kinds
Functioncommand 49 kinds 49 kinds 68 kinds
Internal relay (R) 1100 byte 1118 byte 1618 byte
Message request (A) 25 byte 25 byte 25 byte
Keepmemory
D Variable timer (T)
D Counter (C) 80 byte 80 byte 80 byte
D Keep relay (K) 80 byte 80 byte 80 byte
D Data table(D) (D) 20 byte 20 byte 20 byte
Subprogram (P) 1860 byte 1860 byte 3000 byte
Label (L)
Fixed timer 512 programs
9999 labels
Timer No. 100 Timer No. 100 Timer No. 100
devices specified devices specified devices specified

I/O
D I/O link (I) 1024 points max. 1024 points max. 1024 points max.
(O) 1024 points max. 1024 points max. 1024 points max.
D I/O card (I) 156 points max. 156 points max. 156 points max.
(Note 5) (O) 120 points max. 120 points max. 120 points max.
Sequence program EPROM EPROM EPROM
1Mbit1 (128KB) 1Mbit1 (128KB) 1Mbit1 (128KB)
ROM MODULE ROM MODULE
256KB (Note 3) 256KB (Note 3)

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 The size of a symbol and that of a comment are fixed to 32KB.
The size of a message is fixed to 2.1KB.
The maximum size of a symbol and that of a comment are 64KB each.
3 When the number of steps of the PMC-SB2, SB3 ladder program is approx. 24,000, the
capacity of the ROM module must be 256KB.
4 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
5 As values indicated with an asterisk (*) in the table, former versions of the programming manual
and catalogs have listed the mean processing time of basic commands, but this manual lists
the execution time for one step. The actual ladder program execution performance (speed) of
each PMC has not been changed.

8
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (4)

Type of PMC
Specification PMCSC PMCSC3 PMCNB
of PMC

Program method language Ladder Ladder Ladder


C-language C-language C-language

Number of ladder level 3 3 3

1st level execution period 8 ms 8 ms 8 ms

Mean processing time of basic 0.15 0.15 0.15


command (s/ step) (s/ step) (s/ step)

Program capacity
D Ladder (step) (Note 1,3) Approx. 16,000 Approx. 16,000 Approx. 8,000
Approx. 24,000 Approx. 24,000 Approx. 16,000
(Note 4)
Approx. 24,000
(Note 4)
D Symbol, Comment 1 to 128KB 1 to 128KB 1 to 128KB
(Note 2,3)
D Message (Note 3) 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB
D Language only 896KB max. 896KB max. 896KB max.

Command Basic command 12 kinds 14 kinds 14 kinds


Functioncommand 51 kinds 68 kinds 68 kinds

Internal relay (R) 1600 byte 1618 byte 1618 byte


Message request (A) 25 byte 25 byte 25 byte
Keepmemor
D Variable timer (T) 80 byte 80 byte 80 byte
D Counter (C) 80 byte 80 byte 80 byte
D Keep relay (K) 20 byte 20 byte 20 byte
D Data table (D) 3000 byte 3000 byte 3000 byte
Subprogram (P) 512 programs 512 programs
Label (L) 9999 labels 9999 labels
Fixed timer Timer No. 100 Timer No. 100 Timer No. 100
devices specified devices specified devices specified

I/O
D I/O link (I) 1024 points max. 1024 points max. 1024 points max.
(O) 1024 points max. 1024 points max. 1024 points max.
D I/O card (I) 156 points max. 156 points max.
(O) 120 points max. 120 points max.

Sequence program ROM MODULE ROM MODULE Flash ROM


128KB (16,000 128KB (16,000 64KB
steps option) steps option) (8,000 steps)
256KB (24,000 256KB (24,000 128KB
steps option) steps option) (16,000 steps)
512KB (24,000 512KB (24,000 256KB
steps option) steps option) (24,000 steps)
1MB (24,000 1MB (24,000 512KB
steps option) steps option) (24,000 steps)
1MB
(24,000 steps)

9
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with
basic instructions. The use of functional instructions may
vary the number of ladder steps.
2 The size of a symbol and that of a comment of PMC-SC/SC3
are fixed 32KB. The size of message of PMC-SC/SC3 is
fixed 2.1KB. The size of a symbol and that of a comment
of PMC-NB are fixed 28KB. The size of message of
PMC-NB is fixed 2.1KB. The maximum size of a symbol and
that of a comment are 64KB each.
3 These have no limit of size for each. However, the total size
of sequence program (the sum total of ladder,
symbols/comments, messages, etc.) never exceed the
storage size of sequence program. The size of them
influences the capacity of others.
4 When the number of steps of the PMC-NB ladder program
is not less than 8,000, the OPTION DRAM is required.
(A02B-0162-J151, J152)

10
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (5)

Series 18
Series 16MODEL B/Series 18MODEL B
Model MODEL B
PMCSB3 PMCSC3 PMCSB4 PMCSC4 PMCSA1

Programming method Ladder


Ladder Ladder
Ladder Clanguage Ladder
language Clanguage Step sequence
Step sequece

Number of ladder level 2 3 2 3 2


Level-1 Cycle Time 8 ms 8 ms 8 ms 8 ms 8 ms
Basic Instruction Execution Time * 0.1 0.1 * 0.1 0.1 5.0
(s/ step) (s/ step) (s/ step) (s/ step) (s/ step)

Program capacity
D Ladder (step) (Note 1,3) Approx. 5, 000 Approx. 5, 000 Approx. 3, 000
Approx. 8, 000 Approx. 8, 000 Approx. 5, 000
Approx.12, 000 Approx.12, 000
Approx.16, 000 Approx.16, 000 Approx.16, 000 Approx.16, 000
Approx.24, 000 Approx.24, 000 Approx.24, 000 Approx.24, 000
D Symbol/Comment (Note 2,3) 1 to 128KB 1 to 128KB 1 to 128KB 1 to 128KB 1 to 128KB
D Message (Note 3)
D Language only 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB
max. 896KB max. 896KB

Instruction (Basic) 14 kinds 14 kinds 14 kinds 14 kinds 12 kinds


(Functional) 67 kinds 69 kinds 67 kinds 69 kinds 49 kinds

Internal relay (R) 1618 byte 1618 byte 3200 byte 3200 byte 1100 byte
Message request (A) 25 byte 25 byte 125 byte 125 byte 25 byte
Non-volatile
D Var. Timer (T) 80 byte 80 byte 300 byte 300 byte 80 byte
D Counter (C) 80 byte 80 byte 200 byte 200 byte 80 byte
D Keep relay (K) 20 byte 20 byte 50 byte 50 byte 20 byte
D Data table (D) 3000 byte 3000 byte 8000 byte 8000 byte 1860 byte
Subprogram (P) 512 programs 512 programs 2000 programs 2000 programs
Label (L) 9999 labels 9999 labels 9999 labels 9999 labels
Fixed timer Timer No. 100 Timer No. 100 Timer No. 100 Timer No. 100 Timer No. 100
devices specified devices specified devices specified devices specified devices specified

Input/output
D I/O link (I) Max. 1024 points max. 1024 points max. 1024 points max. 1024 points max. 1024 points max.
(O) Max. 1024 points max. 1024 points max. 1024 points max. 1024 points max. 1024 points max.
D I/O card (I) Max. 312 points max. 312 points max. 312 points max. 312 points max. 312 points max.
(Note 4) (O) Max. 240 points max. 240 points max. 240 points max. 240 points max. 240 points max.
Sequence program Flash ROM Flash ROM Flash ROM Flash ROM Flash ROM
storage media 128KB (16,000 128KB (16,000 128KB (16,000 128KB (16,000 128KB
steps option or steps option) steps option or steps option)
less) 256KB (24,000 less) 256KB (24,000
256KB (24,000 steps option) 256KB (24,000 steps option)
steps option) 512KB (24,000 steps option) 512KB (24,000
steps option) steps option)
1MB (24,000 1MB (24,000
steps option) steps option)

11
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 The size of a symbol and that of a comment are fixed 32KB. The size of message is fixed 2.1KB.
The maximum size of a symbol and that of a comment are 64KB each.
3 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
4 That is the maximum number when 2 I/O cards (with 156 inputs/120 outputs) are used.
5 As values indicated with an asterisk (*) in the table, former versions of the programming manual
and catalogs have listed the mean processing time of basic commands, but this manual lists
the execution time for one step. The actual ladder program execution performance (speed) of
each PMC has not been changed.
6 Application PMC for FANUC Series 16MODEL B loader control function is PMCSA1.

12
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (6)

Series 16MODEL C/Series 18MODEL C


Model
PMCSB5 PMCSC3 PMCSB6 PMCSC4

Programming method Ladder


Ladder Ladder
Ladder Clanguage
language Clanguage Step sequence
Step sequece

Number of ladder level 2 3 2 3

Level-1 Cycle Time 8 ms 8 ms 8 ms 8 ms

Basic Instruction Execution Time * 0.1 0.1 * 0.1 0.1


(s/ step) (s/ step) (s/ step) (s/ step)

Program capacity
D Ladder (step) (Note 1,3) Approx. 3, 000 Approx. 3, 000
Approx. 5, 000 Approx. 5, 000
Approx. 8, 000 Approx. 8, 000
Approx.12, 000 Approx.12, 000
Approx.16, 000 Approx.16, 000 Approx.16, 000 Approx.16, 000
Approx.24, 000 Approx.24, 000 Approx.24, 000 Approx.24, 000
Approx.32, 000 Approx.32, 000
D Symbol/Comment (Note 2,3) 1 to 128KB 1 to 128KB 1 to 128KB 1 to 128KB
D Message (Note 3) 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB 0.1 to 64KB
D Language only max. 896KB max. 896KB

Instruction (Basic) 14 kinds 14 kinds 14 kinds 14 kinds


(Functional) 67 kinds 69 kinds 67 kinds 69 kinds

Internal relay (R) 1618 byte 1618 byte 3200 byte 3200 byte
Message request (A) 25 byte 25 byte 125 byte 125 byte
Non-volatile
D Var. Timer (T) 80 byte 80 byte 300 byte 300 byte
D Counter (C) 80 byte 80 byte 200 byte 200 byte
D Keep relay (K) 20 byte 20 byte 50 byte 50 byte
D Data table (D) 3000 byte 3000 byte 8000 byte 8000 byte
Subprogram (P) 512 programs 512 programs 2000 programs 2000 programs
Label (L) 9999 labels 9999 labels 9999 labels 9999 labels
Fixed timer Timer No. 100 Timer No. 100 Timer No. 100 Timer No. 100
devices specified devices specified devices specified devices specified

Input/output
D I/O link (I) Max. 1024 points max. 1024 points max. 1024 points max. 1024 points max.
(O) Max. 1024 points max. 1024 points max. 1024 points max. 1024 points max.
D I/O card (I) Max. 312 points max. 312 points max. 312 points max. 312 points max.
(Note 4) (O) Max. 240 points max. 240 points max. 240 points max. 240 points max.

Sequence program Flash ROM Flash ROM Flash ROM Flash ROM
storage media 128KB (16,000 128KB (16,000 steps 128KB (16,000 128KB (16,000 steps
steps option or less) option) steps option or less) option)
256KB (24,000 steps 256KB (24,000 steps 256KB (24,000 steps 256KB (24,000 steps
option) option) option) option)
512KB (24,000 steps 512KB (24,000 steps
option) option)
1MB (24,000 steps 1MB (24,000 steps
option) option)

13
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 The size of a symbol and that of a comment are fixed 32KB. The size of message is fixed 2.1KB.
The maximum size of a symbol and that of a comment are 64KB each.
3 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
4 That is the maximum number when 2 I/O cards (with 156 inputs/120 outputs) are used.
5 Application PMC for FANUC Series 16MODEL C loader control function is PMCSA1.

14
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (7)

Series 21MODEL B/
Model Series 210MODEL B
PMCSA1 PMCSA3
Programming method
Ladder Ladder
language

Number of ladder level 2 2

1st level excution period 8 ms 8 ms

Mean processing time of basic command 5.0 * 0.15


(s/ step) (s/ step)

Program capacity
D Ladder (step) (Note 1,4) Approx. 3, 000 Approx. 3, 000
Approx. 5, 000 Approx. 5, 000
Approx. 8, 000
Approx.12, 000
Approx.16, 000
D Symbol/Comment (Note 2,4) 1 to 128KB 1 to 128KB
(Note 4)
D Message 0.1 to 64KB 0.1 to 64KB
D Language only

Command Basic command 12 kinds 14 kinds


Functioncommand 49 kinds 66 kinds

Internal relay (R) 1100 byte 1118 byte


Message request (A) 25 byte 25 byte
Keepmemory
D Variable timer (T) 80 byte 80 byte
D Counter (C) 80 byte 80 byte
D Keep relay (K) 20 byte 20 byte
D Data table (D) 1860 byte 1860 byte
Subprogram (P) 512 programs
Label (L) 9999 labels
Fixed timer Timer No. 100 Timer No. 100
devices specified devices specified

I/O
D I/O link (I) 1024 points max. 1024 points max.
(O) 1024 points max. 1024 points max.
D I/O card (I) 96 points max. 96 points max.
(O) 72 points max. 72 points max.
(Note 5) (Note 5)

Sequence program Flash ROM Flash ROM


128KB (Note 3) 128KB (Note 5)

15
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with
basic instructions. The use of functional instructions may
vary the number of ladder steps.
2 The size of a symbol and that of a comment are fixed 32KB.
The size of message is fixed 2.1KB. The maximum size of
a symbol and that of a comment are 64KB each.
3 When extended memory is not specified in the 4082 series
(ordering drawing No.: A02B0210H020 or
A02B0210H022), the program capacity is 64KB.
4 These have no limit of size for each. However, the total size
of sequence program (the sum total of ladder,
symbols/comments, messages, etc.) never exceed the
storage size of sequence program. The size of them
influences the capacity of others.
5 Output points of I/O card in 4082 series are following ;
PMCSA1 : 64points, PMCSA3 : 64points
6 As values indicated with an asterisk (*) in the table, former
versions of the programming manual and brochure have
listed the mean processing time of basic commands, but this
manual lists the execution time for one step. The actual
ladder program execution performance (speed) of each
PMC has not been changed.
7 Application PMC for FANUC Series 21B loader control
function is PMCSA1.

16
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (8)

FANUC Series 16i/160i/18i/180i


Model PMCSA5 PMCSB5 PMCSB6
(Loader control)
Programmingmethod Ladder Ladder Ladder step sequence

Number of ladder levels 2 2 2

Firstlevel execution period 8 ms 8 ms 8 ms

Basic instruction processing time 5.0 sec/step 0.085 sec/step 0.085 sec/step

Program capacity
D Ladder (step) (Note 1,2) About 3,000 About 3,000 About 3,000
About 5,000 About 5,000 About 5,000
About 8,000 About 8,000 About 8,000
About 12,000 About 12,000 About 12,000
About 16,000 About 16,000
About 24,000 About 24,000
About 32,000
D Symbol & Comment (Note 2) 1KB to 128KB 1KB to 128KB 1KB to 128KB
D Message (Note 2) 0.1KB to 64KB 0.1KB to 64KB 0.1KB to 64KB

Instruction (Basic instruction) 12 14 14


(Functional instruction) 48 66 67

Internal relay (R) 1100 bytes 1618 bytes 3200 bytes


Message request (A) 25 bytes (200 points) 25 bytes (200 points) 125 bytes (1000 points)
Nonvolatile memory
D Variable timer (T) 80 bytes (40 each) 80 bytes (40 each) 300 bytes (150 each)
D Counter (C) 80 bytes (20 each) 80 bytes (20 each) 200 bytes (50 each)
D Keep replay (K) 20 bytes 20 bytes 50 bytes
D Data table (D) 1,860 bytes 3,000 bytes 8,000 bytes
Subprogram (P) 512 each 2000 each
Label (L) 9999 each 9999 each
Fixed timer 100 each 100 each 100 each
(Timer number specification)

I/O
D I/O link (Input) 1024 points maximum 1024 points maximum 2048 points maximum
(Note 4) (Note 5)
(Output) 1024 points maximum 1024 points maximum 2048 points maximum
(Note 5)

Sequence program storage media Flash ROM Flash ROM Flash ROM
128KB 128KB (16,000 128KB (16,000
steps option or less) steps option or less)
256KB (24,000 256KB (24,000
steps option or less) steps option)
384KB(32,000/40,000
steps option)

17
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
3 The PMCSA1 can be used with the loader control function of the FANUC Series
16i/18i/21i/160i/180i/210i.
4 For I/O of the FANUC Series 16i/18i/21i/160i/180i/210i, only the I/O link is used.
5 1024 points maximum (channel 1)+1024 points maximum (channel 2)= 2048 points maximum.
You can use the I/O Link channel 2 only when CNC hardware support the I/O Link 2channel
and optional I/O Link expansion is provided with CNC.

18
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (9)

FANUC Series
FANUC Series 21i/210i
21i/210i
Model
PMCSA1 PMCSA5 PMCSA5 PMCSB6
(Loader control)
Ladder
Programmingmethod Ladder Ladder Ladder
Step sequence

Number of ladder levels 2 2 2 2

Firstlevel execution period 8 ms 8 ms 8 ms 8 ms

Basic instruction 5.0 sec/ step 5.0 sec/ step 0.085 sec/ step 0.085 sec/ step
processing time

Program capacity About 3,000 About 3,000 About 3,000 About 3,000
D Ladder (step) About 5,000 About 5,000 About 5,000 About 5,000
(Note 1,2) About 8,000 About 8,000 About 8,000
About 12,000 About 12,000 About 12,000
About 16,000 About 16,000
About 24,000
About 32,000
D Symbol & Comment 1KB to 128KB 1KB to 128KB 1KB to 128KB 1KB to 128KB
(Note 2)
D Message (Note 2) 0.1KB to 64KB 0.1KB to 64KB 0.1KB to 64KB 0.1KB to 64KB

Instruction
(Basic instruction) 12 12 14 14
(Functional instruction) 49 49 66 67

Internal relay (R) 1100 bytes 1100 bytes 1118 bytes 3200 bytes
Message request (A) 25 bytes (200 points) 25 bytes (200 points) 25 bytes (200 points) 125 bytes (1000 points)
Nonvolatile memory
D Variable timer (T) 80 bytes (40 each) 80 bytes (40 each) 80 bytes (40 each) 300 bytes (150 each)
D Counter (C) 80 bytes (20 each) 80 bytes (20 each) 80 bytes (20 each) 200 bytes (50 each)
D Keep replay (K) 20 bytes 20 bytes 20 bytes 50 bytes
D Data table (D) 1860 bytes 1,860 bytes 1860 bytes 8,000 bytes
Subprogram (P) 512 each 2000 each
Label (L) 9999 each 9999 each
Fixed timer 100 each 100 each 100 each 100 each
(Timer number
specification)

I/O
D I/O link (Input) 1024 points maximum 1024 points maximum 1024 points maximum 2048 points maximum
(Note 4) (Note 5)
(Output) 1024 points maximum 1024 points maximum 1024 points maximum 2048 points maximum
(Note 5)

Sequence program storage Flash ROM Flash ROM Flash ROM Flash ROM
media 128KB 128KB 128KB 128KB (16,000
steps option or less)
256KB (24,000
steps option)
384KB(32,000/40,000
steps option)

19
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
3 The PMCSA1 can be used with the loader control function of the FANUC Series
16i/18i/21i/160i/180i/210i.
4 For I/O of the FANUC Series 16i/18i/21i/160i/180i/210i, only the I/O link is used.
5 1024 points maximum (channel 1)+1024 points maximum (channel 2)= 2048 points maximum.
You can use the I/O Link channel 2 only when CNC hardware support the I/O Link 2channel
and optional I/O Link expansion is provided with CNC.

20
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (10)

FUNAC Power Mate iMODEL D/H


Model
PMCSB5 PMCSB6
Programmingmethod Ladder Ladder step sequence
Number of ladder levels 2 2
Level1 cycle time 8 ms 8 ms
Basic instruction execution time 0.085 0.085
( sec/step) ( sec/step)
Program capacity
D Ladder (step) (Note 1,2) Approx. 5,000 Approx. 5,000
Approx. 12,000 Approx. 12,000
Approx. 16,000 Approx. 16,000
Approx. 24,000 Approx. 24,000
Approx. 32,000

D Symbol/Comment (Note 2) 1 to 128KB 1 to 128KB


D Message (Note 2) 0.1 to 64KB 0.1 to 64KB
Instruction (Basic) 14 kinds 14 kinds
(Functional) 67 kinds 67 kinds

Internal relay (R) 1618 bytes 3200 bytes


Message request (A) 25 bytes (200 points) 125 bytes (200 points)
Nonvolatile
D Var.timer (T) 80 bytes (40 points) 300 bytes (150 points)
D Counter (C) 80 bytes (20 points) 200 bytes (50 points)
D Keep replay (K) 20 bytes 50 bytes
D Data table (D) 3000 bytes 8000 bytes
Subprogram (P) 512 programs 2000 programs
Label (L) 9999 labels 9999 labels
Fixed timer Timer No.100 Timer No.100
devices specified devices specified
Input/Output
D I/O Link (I) Max. 1024 points max. 1024 points max.
(master) (O) Max. 1024 points max. 1024 points max.
D I/O Link (I) Max. 256 points max. 256 points max.
(slave) (O) Max. 256 points max. 256 points max.
D Builtin I/O (I) Max. 32 points max. 32 points max.
(O) Max. 24 points max. 24 points max.
Sequence program storage media Flash ROM Flash ROM
128KB (16,000 128KB (16,000
steps option or less) steps option or less)
256KB (24,000 256KB (24,000
steps option) steps option)
384KB (32,000
steps option)

NOTE
1 This is the number of ladder steps for the program only with
basic instructions. The use of functional instructions may
vary the number of ladder steps.
2 These have no limit of size for each. However, the total size
of sequence program (the sum total of ladder, symbols/
comments, messages, etc.) never exceed the storage size
of sequence program. The size of them influences the
capacity of others.

21
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

Table 1.1 PMC specifications (11)

Series 15MODEL B
Model PMCNB PMCNB2
(4048 Series)
Programmingmethod language Ladder Ladder
Clanguage Clanguage
Step sequence
Number of ladder level 3 3
Level1 Cycle Time 8 ms 8 ms
Basic instruction 0.1 0.1
Execution Time (s/step) (s/step)
Program capacity Approx. 8,000 Approx. 8,000
S Ladder(step) (Note 1,2) Approx.16,000 Approx.16,000
Approx.24,000 Approx.24,000
S Symbol/Comment 1 to 128KB 1 to 128KB
(Note 2)
S Message (Note 2) 0.1 to 64KB 0.1 to 64KB

S Language only max. 896KB max. 896KB

Instruction (Basic) 14 kinds 14 kinds


(Function) 69 kinds 69 kinds
Internal relay (R) 1618 bytes 3200 bytes
Message request (A) 25 bytes 125 bytes
Nonvolatile
S Var.Timer (T) 80 bytes 300 bytes

S Counter (C) 80 bytes 200 bytes

S Keep relay (K) 20 bytes 50 bytes

S Data table (D) 3000 bytes 8000 bytes

Subprogram (P) 512 programs 2000 programs

Label (L) 9999 labels 9999 labels

Fixed timer Max 100 timers Max 100 timers


specified by specified by
timer No. timer No.
Input/output
S I/O link (I) max 1024 points. max 1024 points.
(O) max 1024 points. max 1024 points.
S I/O card (I)
(O)
Sequence program Flash ROM Flash ROM
storage media 64 KB (8,000 64 KB (8,000
steps) steps)
128 KB (16,000 128 KB (16,000
steps) steps)
256 KB (24,000 256 KB (24,000
steps) steps)
512 KB (24,000 512 KB (24,000
steps) steps)
1 MB (24,000 1 MB (24,000
steps) steps)

22
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

NOTE
1 This is the number of ladder steps for the program only with
basic instructions. The use of functional instructions may
vary the number of ladder steps.
2 These have no limit of size for each. However, the total size
of sequence program (the sum total of ladder, symbols/
comments, messages, etc.) never exceed the storage size
of sequence program. The size of them influences the
capacity of others.
3 Please refer to (4) for PMCNB(4047 Series).
The abovementioned table is a value for PMCNB/NB2
(4048 Series).

23
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

Table 1.1 PMC specifications (12)

FANUC Series 15i


Model
PMCNB6
Programmingmethod Ladder
step sequence (optional)
Number of ladder levels 3
Firstlevel execution period 8 ms
Basic instruction processing time 0.085 sec/step
Program capacity
S Ladder (step) (Note 1,2) About 32,000 maximum
S Symbol/comment(Note 2) 1 to 128KB
S Message (Note 2) 0.1 to 64KB
Instruction (Basic instruction) 14
(Functional instruction) 64
Internal relay (R) 3200 byte
Message request (A) 125 bytes (1000 points)
Nonvolatile memory
S Variable timer (T) 300 bytes (150 points)
S Counter (C) 200 bytes (50 points)
S Keep relay (K) 50 byte
S Data table (D) 8000 byte
Subprogram (P) 2000 each
Label (L) 9999 each
Fixed timer 100 each (timer number specification)
I/O
S I/O link (Input) 1024 points maximum
(Note 3) (Output) 1024 points maximum
Sequence program storage media Flash ROM
128KB (16,000steps option or less)
256KB (24,000 steps)
384KB (32,000steps option)

NOTE
1 This is the number of ladder steps for the program only with
basic instructions. The use of functional instructions may
vary the number of ladder steps.
2 These have no limit of size for each. However, the total size
of sequence program (the sum total of ladder,
symbols/comments, messages, etc.) never exceed the
storage size of sequence program. The size of them
influences the capacity of others.
3 The one and only I/O of the FANUC Series 15i is the I/O
Link.

24
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (13)

Series 21iB Series 16i/18i/21iB


Model PMCSA1 PMCSA1 PMCSB7
(Loader control)
Programmingmethod Ladder Ladder Ladder Clanguage
Number of ladder levels 2 2 3
Firstlevel execution period 8 ms 8 ms 8 ms
Basic instruction processing time 5.0 sec/step 5.0 sec/step 0.033 sec/step
Program capacity
S Ladder (step) (Note 1,2) About 3,000 About 3,000 About 3,000
About 5,000 About 5,000 About 5,000
About 8,000 About 8,000
About 12,000 About 12,000
About 16,000
About 24,000
About 32,000
About 40,000
About 48,000
About 64,000
S Symbol & comment (Note 2) 1 to 128KB 1 to 128KB 1KB or more
S Message (Note 2) 0.1 to 64KB 0.1 to 64KB 8KB or more
Instruction (Basic instruction) 12 12 14
(Functionalinstruction) 48 48 69
Internal Relay (R) 1100 bytes 1,100 byte 8,500 byte
Extra Relay (E) 8,000 byte
Message Request (A) 200 points (25 byte) 200 points (25 byte) 2,000 points (500 byte,
2 bit/point)
Nonvolatile Memory
S Data Tables (D) 1,860 byte 1,860 byte 10,000 byte
S Variable Timers (T) 80 bytes (20 each) 40 points (80 byte) 250 points (1,000 byte,
4 byte/point)
S Fixed Timers 20 bytes 100 points 500 points (Timer number
specify)
S Counters (C) 1860 bytes 20 points (80 byte) 100 points (400 byte,
4 byte/point)
Fixed Counters (C) 100 points (200 byte,
2 byte/point)
S Keep Relays (K) 20 byte 120 byte
Subprograms (P) 100 each 2000
Labels (L) 9999
I/O I/O link
S Input 1024 points maximum 1024 points maximum 2048 points maximum (Note 3)
S Output 1024 points maximum 1024 points maximum 2048 points maximum (Note 3)
Sequence program storage media Flash ROM Flash ROM Flash ROM
128KB 128KB 128KB (16,000steps option or
less)
256KB (24,000steps option)
384KB(32,000/40,000steps
option)
512KB (48,000steps option)
768KB (64,000steps option)

25
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
3 Maximum of basic input/output points are 1024/1024 points. I/O Link expansion option extends
the maximum to 2048/2048 points.

26
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.1 PMC specifications (14)

Series 0iA
Model
PMCSA1 PMCSA3
Programmingmethod Ladder Ladder
Number of ladder levels 2 2
Level1 cycle time 8 ms 8 ms
Basic instruction execution time 5.0 sec/step 0.15 sec/step
Program capacity
S Ladder (step) (Note 1) Approx. 3,000 Approx. 3,000
Approx. 5,000 Approx. 5,000
Approx. 8,000
Approx. 12,000
Approx. 16,000
S Symbol/Comment (Note 2,3) 1 to 128KB 1 to 128KB
S Message (Note 2,3) 0.1 to 64KB 0.1 to 64KB
Instruction (Basic) 12 kinds 14 kinds
(Functional) 49 kinds 66 kinds
Internal relay (R) 1100 bytes 1118 bytes
Message request (A) 25 bytes (200 points) 25 bytes (200 points)
Nonvolatile
S Var.timer (T) 80 bytes (40 each) 80 bytes (40 each)
S Counter (C) 80 bytes (20 each) 80 bytes (20 each)
S Keep replay (K) 20 bytes 20 bytes
S Data table (D) 1860 bytes 1860 bytes
Subprogram (P) 512 programs
Label (L) 9999 labels
Fixed timer Timer No.100 devices specified Timer No.100 devices specified
Input/Output
S I/O Link (I) Max. 1024 points maximum 1024 points maximum
(master) (O) Max. 1024 points maximum 1024 points maximum
S Builtin I/O (I) Max. 96 points max. 96 points max.
(O) Max. 64 points max. 64 points max.
Flash ROM Flash ROM
128KB 128KB

NOTE
1 This is the number of ladder steps for the program only with basic instructions. The use of
functional instructions may vary the number of ladder steps.
2 These have no limit of size for each. However, the total size of sequence program (the sum total
of ladder, symbols/comments, messages, etc.) never exceed the storage size of sequence
program. The size of them influences the capacity of others.
3 The size of a symbol and that of a comment are fixed 32KB. The size of message is fixed 2.1KB.
The maximum size of a symbol and that of a comment are 64KB each.

27
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

1.2
SUMMARY OF
SPECIFICATION OF
LADDER PROGRAM Table 1.2 Summary of specification of ladder program (1)

Model PMCPA1 PMCPA3 PMCP


PMC Interfaces between the PMC and CNC Compatible Incompatible
address (F and G) (Note 2)

Interfaces between the PMC and Compatible Incompatible


machine (X and Y) (Note 2)

Others (R, A, C, K, D, T) Compatible Incompatible

Ladder ROM format (object) Incompatible (Note 1)


program
compatibility Source format (mnemonic) Compatible Incompatible
(Note 2)

System Divided system Not provided (Note 3) Provided

Undivided system Provided Not provided

Basic commands Compatible

Function DISP (SUB49) Not provided (Note 4) Provided


commands
COM Coil count specification Not provided (Note 5) Provided
(SUB9)
COME (SUB29) specification Provided

JMP Coil count specification Not provided (Note 5) Provided


(SUB10)
JMPE (SUB30) specification Provided

NOTE
1 The same ROM cannot be shared by different models. The
ROM must be rewritten using the offline programmer.
2 It is possible that convert the signal address by the
operation of SIGNAL ADDRESS CONVERSION
(APPENDIX G).
3 The setting item of system parameter IGNORE DEVIDE
CODE is not provided.
4 Use the DISPB (SUB41) command instead.
5 The range of the COM (SUB9) and JMP (SUB10)
commands cannot be specified with the number of coils.
Specify the range with the COME (SUB29) and JMPE
(SUB30) commands. If specify the number of coils, no error
messages will be displayed while editing, but ALARM093
will be displayed when send the data to RAM.

28
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.2 Summary of specification of ladder program (2)

PMC
PMC SB3/ PMC
PMC PMC PMC PMC PMC
Model SA3/ SB4/ SC3/
SA1 SA2 SB SB2 SC
SA5 SB5/ SC4
SB6
PMC address Interfaces between the PMC and CNC (F and
Compatible (Note 8)
G)
Interfaces between the PMC and machine (X
Compatible
and Y)
Subprogram, label (P and L) Not
Not provided Provided Not provided Provided Provided
provided
Others (R, A, C, K, D, T) Compatible (Note 1)
Ladder ROM format (object) Incompatible (Note 2)
program
compatibility Source format (mnemonic) Compatible (Note 3)

System Divided system


Not provided (Note 4) Provided
Not provided
Provided
Not
(Note 4) provided
Undivided system Provided
Structuring Sub program
Unusable Usable Unusable Usable
Un-
Usable
usable
Basic commands Compatible
Function END3 (SUB48) Not provided Provided
commands DISP (SUB49) Not provided (Note 5) Provided
COM Coil count specification Not
Not provided
(SUB9) Not provided (Note 6) Provided Provided provided
(Note 6)
(Note 6)
COME (SUB29) specification Provided
JMP Coil count specification Not
Not provided
(SUB10) Not provided (Note 6) Provided Provided provided
(Note 6)
(Note 6)
JMPE (SUB30) specification Provided
FNC9X (SUB9X) Not provided Provided
MMCWR (SUB98), MMCWW (SUB99)
Provided (Note 7) Provided
MMC3R (SUB88), MMC3W (SUB89) (Note 7)
MOVB (SUB43), MOVW (SUB44) , Not
MOVN (SUB45)
Not provided Provided Not provided Provided
provided
Provided

DIFU (SUB57), DIFD (SUB58) Not


Not provided Provided Not provided Provided
provided
Provided

AND (SUB60), OR (SUB61) Not


NOT (SUB62), EOR (SUB59)
Not provided Provided Not provided Provided
provided
Provided

Function Commands for subprogram


command END (SUB64) , Not
Not provided Provided Not provided Provided
provided
Provided
(for structured CALL (SUB65), CALLU (SUB66) ,
programming) SP (SUB71), SPE (SUB72)
Extended jump command
Not
JMPB (SUB68), JMPC (SUB73) Not provided Provided Not provided Provided
provided
Provided
LBL (SUB69)

29
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 The internal relay and the data table in nonvolatile memory
for the PMC-SB3, SC, SC3 are extended, compared with
those for other models.
2 The same ROM cannot be shared by different models. The
ROM must be rewritten using the offline programmer.
However, the ROM for the PMCSA2 can be used for the
PMCSA3 and the ROM for the PMCSB2 can be used for
the PMCSB3.
3 The program can be converted by reinputting it after it is
output in a source format.
4 The setting item of system parameter IGNORE DEVIDE
CODE is not provided.
5 Use the DISPB (SUB41) command instead.
6 The range of the COM (SUB9) and JMP (SUB10)
commands cannot be specified with the number of coils.
Specify the range with the COME (SUB29) and JMPE
(SUB30) commands.
7 For the FS18A (PMCSA1/SA2/SA3), only the MMCIII can
be used. For the FS18B, the MMCIII and MMCIV can be
used.
For the FS21B (PMCSA1/SA3), the MMCIV can be used.
For the FS16i/18i/21i, the MMCIV can be used.
For the FS16C/18C, the MMCIV can be used.
8 In the PMCSB4, SB6, and SC4, interface extension is
made. The extended portion of the interface is not
compatible with other PMCs.

30
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.2 Summary of specification of ladder program (3)

Model PMC PMC PMC


NA NB NB2
Series (4046) (4047) (4048)
(4048)
PMC address Interfaces between the PMC and CNC (F and G) Incompatible

Interfaces between the PMC and machine Compatible


(X and Y)
Subprogram, label (P and L) Not
Provided
provided

Others (R, A, C, K, D, T) Compatible (Note 1)

Ladder ROM format (object) Incompatible (Note 2)


program
compatibility Source format (mnemonic) Compatible (Note 3)

System Divided system Provided Not provided

Undivided system Not Provided


provided

Structuring Subprogram Usable Unusable

Step sequence Unusable Usable

Basic commands Compatible

Function END3 (SUB48) Provided


commands
DISP (SUB49) Provided Not provided

COM Coil count spesification Provided Not provided


(SUB9)
COME (SUB29) specification Provided

JMP Coil count specification Provided Not provided


(SUB10)
JMPE (SUB30) specification Provided

FNC9X (SUB9X) Provided

LIBRY (SUB60), LEND (SUB61) Provided Not provided

MMCWR (SUB98), MMCWW (SUB99)


MMC3R (SUB88), MMC3W (SUB89)
MOVB (SUB43), MOVW (SUB44)
Not
MOVN (SUB45) provided
Provided
DIFU (SUB57), DIFD (SUB58)
AND (SUB60), OR (SUB61)
NOT (SUB62), EOR (SUB59)
Function S Command for subprogram
command END (SUB64) , CALL (SUB65) , CALLU Not
Provided
(for structured (SUB66) , provided
programming) SP (SUB71) , SPE (SUB72)
S Extended jump command Not
Provided
JMPB (SUB68) , JMPC (SUB73) , LBL (SUB69) provided

NOTE
1 Management of internal relay address and that of datatable
are different between the PMCNB/NB2 and the PMCNA.
2 The same ROM cannot be shared by different models.
The ROM must be rewritten using the offline programmer.
3 The data can be converted by outputting in the source
format and then inputting again.
Moreover, a part of functional instruction is not compatible
between PMCNB/NB2 and PMCNA.

31
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

Table 1.2 Ladder Compatibility (4)

FANUC Series 15B FANUC Series 15i


Model
PMCNB PMCNB2 PMCNB6
PMC address PMCCNC interface (F, G) Compatible(NOTE 1)
PMCmachine interface (X, Y) Compatible
Area used by management software (K) K17 to K19 K900 to K909
Ladder ROM format (object) Not compatible Compatible(NOTE 2)
compatibility
Source format (mnemonic) Compatible
Basic instruction Compatible
Functional FNC9X(SUB9X) Yes No
instruction MMC3R(SUB88)
MMC3W(SUB89)
MMCWR(SUB98)
MMCWW(SUB99)

User program (C) Yes Yes(NOTE 3)


User program (step sequence) No Yes Yes (optional)
Sequence program automatic operation K17#2=1 K900#2=1 K900#2=0

NOTE
1 Compatibility is not maintained for the interface unique to
the Series 15i.
2 The PMCNB6 of the Series 15i is highly compatible with
the PMCNB2 of the Series 15B. The PMCNB2 and
PMCNB6 differ from each other in:
(1)Execution timedependent ladder
As instruction execution becomes faster, the following
changes may occur in the execution timing:
S Change in the execution cycle of the second ladder
level
S Change in timing for the secondlevel split and
firstlevel execution
S Change in timing for ladder execution and I/O transfer
(2)Window functions
The functional instructions that can be used vary
between the PMCNB2 and PMCNB6. See Chapter 5,
PMC Functional Instructions in Part I, PMC Sequence
Program.
(3)Screen manipulation
The operating procedure for the PMC screen for the
PMCNB6 of the 15i varies slightly from that for the
PMCNB2 of the 15B.
See Chapter 7, PMCNB6 Screen Manipulation, in
Part II, PMC Manipulation.
(4)Step sequence
For the PMCNB6, the step sequence is optional.
3 The C option is necessary.

32
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

Table 1.2 Ladder Compatibility (5)

16i/18i/21iA 16i/18i/21iB
Model
SA5 SB5 SB6 SB7
PMC address PMCCNC interface (F, G) F0 to F255 Expanded to F0 Expanded to F0
G0 to G255 to F511 and G0 to F767 and G0
to G511 to G767
PMCmachine interface (X, Y) X0 to X127 X200 to X327 Compatible
Y0 to Y127 and Y200 to
Y327 are added.
Area used by management software (K) K17 to K19 Changed to Expanded to
K900 to K909 K900 to K919
Basic instruction Compatible
Function END3 No Yes
instruction CTRB (additional)
MOVD
DISP Yes No

The above table lists the differences to be noted on upward conversion to


the PMCSB5, PMCSB6, or PMCSB7. Simple conversion in the
reverse direction cannot be performed generally because functions such
as the PMC address ranges are limited.

33
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

CAUTION
1 The above table does not contain simple addition of reserved areas for PMC addresses that
are not used by the ladder.
2 Execution timedependent ladder
As instruction execution becomes faster, the following changes may occur in the execution
timing:
S Change in the execution cycle of the second ladder level
S Change in timing for the secondlevel split and firstlevel execution
S Change in timing for ladder execution and I/O transfer
A ladder which can be operated on the 16i/18i/21iA must also be checked for operation on
the 16i/18i/21iB system.
3 Changes in memory capacities required for a sequence program (PMCSB7)
As described in Section 2.8, the memory capacities required for the system and
symbol/comment data have been changed. As a result, the capacity of flash ROM is increased
as compared with the PMCSA5/SB5/SB6, even for the same source program. If a created
sequence program exceeds the capacity of flash ROM, add the step count option or delete
unnecessary symbols and comments.
4 Screen display and operation
The PMCSB7 has much the same screen display/operation system as the
PMCSA5/SB5/SB6. Some operations for the PMCSA5/SB5/SB6 have been modified to
improve operability and functionality, however. The same goes for the PMCSA1. For details,
see Chapter 1, SCREEN OPERATION FOR PMCSA1/SB7 in Part V.
5 PMC parameter input/output (PMCSB7)
With increase in size of a PMC parameter (T, C, K, and D areas), the data format used for
inputting PMC parameters from a memory card or floppy disk (FANUC Handy File) or outputting
them to it on the PMC I/O screen has been extended.
S PMC parameters output by the PMCSA5/SB5/SB6 can be read by the PMCSB7.
S PMC parameters output by the PMCSB7 cannot be read by the PMCSA5/SB5/SB6.
An extension relay (E area) has been added as a PMC address. A PMC parameter input or
output by the PMCSB7 contains the E area. If a PMC parameter output by the PMCSB7 is
read, the E area is initialized to the status when the PMC parameter is output.

34
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

1.3 This is paragraph outlines functions of a sequence program before


explaining the programming work.
WHAT IS A
SEQUENCE A sequence program is a program for sequence control of machine tools
and other systems.
PROGRAM?
A program is defined as a processing procedure to enable CPU to execute
arithmetic processing.
This program is converted into a format (machine language instructions)
to enable CPU to execute decoding and arithmetic processing, and stored
into the RAM or ROM memory.
The CPU reads out instructions of the program stored into the memory
at high speed every instruction, and executes the program by arithmetic
operation.
The programming of a sequence program begins with the production of
a ladder diagram which serves as a processing procedure for arithmetic
processing by CPU.
This ladder program is produced using PMC instructions.
After producing the ladder diagram, the processing sequence of this
ladder diagram is converted into machine language instructions, and
stored into the memory (program input).
Conversion into the machine language instructions and storage into the
memory are done by the PMC programmer. The PMC programmer is a
function to produce a program.
The sequence program being stored into the memory is sequentially read
out into the PMCs CPU every instruction at high speed and executed.
Fig. 1.3 shows this relation.
The CPU reads out input circuit signals of address X0.0 by RD X0.0
instruction, and sets them into an operation register. Then, the CPU
executes AND operation with internal relay states at address R10.0
according to the AND R10.1 instruction, and sets these results into the
operation register.
The CPU executes instructions at high speed and outputs arithmetic
results to the address Y0.0 output circuit.

35
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

PMC (Programmable Machine Controller)

CPU

Sequence program memory


A B D W RD X0.0
Sequence
AND R10.1
X0.0 R10.1 R20.3 Y0.0 program input
C OR X6.1
AND.NOT R20.3
X6.1
WRT Y0.0

Controlled system, such as machine


tools and other systems
Input circuit
X0.0
X6.1

Output circuit
Y0.0

Internal relay (RAM)


R10.1
R20.3

Fig. 1.3 Execution of sequence program by PMC

36
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

1.4 After deciding the control object specifications and calculating the
number of input/output signal points, create the interface specifications.
CREATION OF Use the input/output signal interface tables in the CONNECTING
INTERFACE MANUAL for the creation of the interface specifications. Enter the signal
SPECIFICATIONS names (within six characters) in the input/output signal interface table
according to the type of the connected signals. For the input/output
(STEPS 1 TO 3)
signals, see CONNECTION MANUAL.

1.5 Express the control operations decided by step 2 by use of the ladder
diagram (relay circuit diagram). For the functions of the timer, counter,
CREATION OF etc. which cannot be expressed with the relay symbols (i.e. the functional
LADDER DIAGRAM instructions), express them with the symbols assigned to the functional
(STEP 4) instructions.
In the offline programmer and built-in editing function, the sequence
program can be entered in the ladder diagram format from the keys of the
CRT/MDI panel or from the keys of the keyboard of the SYSTEM P
series.
Also, the entered sequence program can be output to the printer in the
ladder diagram format using the SYSTEM P series.
Therefore, entry can be performed while the ladder diagram is created on
the CRT screen at the time of sequence program entry. Thus no ladder
diagram may be prepared in advance.
However, in order to shorten the time occupied by the equipment for the
creation of the sequence program or to efficiently create the sequence
program, it is recommended to prepare the ladder diagram in advance.
The ladder diagram is used as a maintenance diagram by the personnel in
charge of maintenance in FANUC, the machine tool builder and end user
in the world. Therefore, the ladder diagram must be easy to understand.
Signal names (max. six characters) can be entered to the input/output
signals, comments (max. 30 characters) can be entered to the relay coil,
and comments (max. 30 characters) can be entered to the input/output
signals of the address tables at the time of entry of the sequence program.
Be sure to enter understandable signal names and comments as much as
possible.

37
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

1.6 In the coding, the contents of control expressed in the ladder diagram are
converted into PMC instructions. In the case of using the offline
CODING (STEP 5) programmer or ladder diagram editting, since sequence program entry can
be performed in the simple ladder diagram format, it is normally
unnecessary to perform coding.
Coding is necessary only when the sequence program is punched on a
paper tape and entered from the paper tape.
Examples of the ladder diagram and the coding are shown in Fig. 1.6.

FIN
MF MF SF TF
Miscellaneous
function
F7.0 F 7.0 F 7.2 F 7.3 finish signal
SF G4.3

F7.2
TF MFIN SFIN TFIN

F7.3 R211.7 R211.5 R211.6

Address number,
Step number Instruction Remark
bit number
850 RD F7.0 MF
851 OR F7.2 SF
852 OR F7.3 TF
853 RD.NOT.STK F7.0 MF
854 OR R211.7 MFIN
856 AND.STK
857 RD.NOT.STK F7.2 SF
858 OR R211.5 SFIN
859 AND.STK
860 RD.NOT.STK F7.3 TF
861 OR R211.6 TFIN
862 AND.STK
863 WRT G4.3 FIN

Fig. 1.6

38
1. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM CREATING PROCEDURE

1.7 The sequence program can be entered in five ways as follows:


SEQUENCE (1) Entry with CRT/MDI keys
PROGRAM ENTRY The sequence program is entered in the ladder diagram format by
pressing the keys of the CRT/MDI.
(STEPS 6, 7)
(2) Entry with keys of SYSTEM P series keyboard
The sequence program is entered in the mnemonic symbol by
pressing the keys of SYSTEM P series keyboard.
(3) Entry from PPR of SYSTEM P series
The sequence program punched on a paper tape is read out of the PPR
and stored in the memory of the SYSTEM P series.
(4) Entry form floppy disk of SYSTEM P series
This method is used when a completed sequence program is slightly
changed. The sequence program written in the floppy disk is stored
in the memory of SYSTEM P series.
(5) Entry form ROM Writer
This method is used when a completed sequence program is slightly
changed. The sequence program written in the ROM is stored from
the PMC Writer or FA Writer into P-G or Debugging RAM.

1.8 Check the sequence program and write it into the ROM after check is over.
The sequence program can be checked in two ways.
SEQUENCE
PROGRAM CHECK (1) Check by simulator
Instead of the machine, connect a simulator (consisting of lamps and
AND WRITE INTO switches). Instead of using input signals from the machine, enter
ROM (STEPS 8 TO 11) signals by turning on and off the switches according to the machine
movement. Check the output signals on the basis of the activation
of the lamps.
(2) Check by system operation
Perform checks by connecting the machine. Since it sometimes
happens that unexpected operations may be executed depending on
a sequence program, arrange for safety before starting operations.
(3) Writing into ROM
When check of the sequence program is over, write the sequence
program into the ROM. The ROMs to be used are as follows. Then,
the ROM into the CNC unit, and deliver it as a regular product to an
end user. Writing of the sequence program into the ROM,
maintenance and control thereof shall be performed by the machine
tool builder. For this purpose, FANUC provides the PMC Writer or
FA Writer as the ROM writer and the ROM or the ROM module that
is the PC board on which a ROM chip is mounted. Be sure to use
these devices for entering a sequence program in ROMs.

39
1. SEQUENCE PROGRAM
CREATING PROCEDURE PMC SEQUENCE PROGRAM B61863E/14

1.9 (1) Storage and control of sequence program


After debugging, the sequence program should be stored and
STORAGE AND controlled by the machine tool builder. It can be stored in the
CONTROL OF following ways:
SEQUENCE (a) Storing in ROM
PROGRAM The sequence program can be stored in the ROM. For control,
(STEPS 12 TO 14) enter the drawing number, edition number, etc. of the machine
tool builder into the label provided in the ROM, and attach it to
the ROM for control. The same control is necessary for the ROM
for product.
(b) Storing in floppy disk
The sequence program can be stored in the floppy disk with
offline programmer. Many programs can be stored in one floppy
disk.
(c) Storing in paper tape
The sequence program can be stored in the form of a paper tape.
(d) Storing in FANUC floppy disk cassette
The sequence program can be stored in floppy disk cassette.
(2) Compiling and control of maintenance drawing
The sequence program can be output to the printer in the ladder
diagram format using the offline programmer or built-in editing
function. Be sure to attach the ladder diagram to the machine as a
maintenance drawing together with the machine tool magnetic
circuit diagrams, etc.

40
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

2 SEQUENCE PROGRAM

Since PMC sequence control handled by software and operates on


principles different from a general relay circuit, the sequence control
method must be fully understood in order to design the PMC sequence.

41
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

2.1 In a general relay sequence circuit, each relay operates at approximately


the same time. In the figure below for example, when relay A operates,
EXECUTION the relay D and E operate at approximately the same time. (When both
PROCEDURE OF contacts B and C are off.) In PMC sequence control, each relay of the
SEQUENCE circuit operates sequentially. When relay A operates, relay D operates,
then relay E (see Fig. 2.1 (a)). Thus each relay operates in sequence which
PROGRAM
can be written as a ladder diagram. (programmed sequence)
A B
D

A C
E

Fig. 2.1 (a) Circuit examples


Although the PMC sequential operation is performed at high speed, the
speed will change with the order to be executed.
Fig. 2.1 (b) (A) and (B) illustrate operations varying from the relay circuit
to PMC program.
(P.B)
A C
B

A
C

(A)

(P.B)
A
C

A C
B

(B)

Fig. 2.1 (b) Circuit examples


(1) Relay circuit
Operations are the same in both Fig. 2.1 (b) (A) and (B). Turning on
A (P.B) causes current to flow to coils B and C, which turns on B and
C. When C turns on, B turns off.
(2) PMC program
In Fig. 2.1 (b) (A), as in the relay circuit, turning on A (P.B) turns on
B and C, and after one cycle of the PMC sequence, turns off B. But
in Fig. 2.1 (b) (B), turning on A (P.B) turns on C, but does not turn
on B.

42
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

2.2 The sequence program is executed from the beginning of coding to the
end of coding of the ladder diagram in the sequence written. When the
REPETITIVE sequence program ends, the program starts over from the beginning. This
OPERATION is called repetitive operation.
The execution time from the beginning to the end of the ladder diagram
is called the sequence processing time, which varies according to the
control scale (the number of steps) and the size of the 1st level sequence.
The shorter the process time is, the better the signal response becomes.

43
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

2.3 A sequence program consists of three parts: 1st level sequence, 2nd level
sequence and 3rd level sequence. The 3rd level sequence part is added
PRIORITY OF to the models usable the 3rd level sequence. (see Fig. 2.3 (a)).
EXECUTION Sequence program
(1ST LEVEL, 2ND
1st level sequence part Specifies the end of the
LEVEL AND 3RD SUB 1
1st level sequence part.
LEVEL) Division 1

Division 2
2nd level sequence part

SUB 2 Division n

3rd level sequence part Specifies the end of the


SUB 48 2nd level sequence part.

(Only the models usable the 3rd level sequence)


Specifies the end of the 3rd level sequence part.

Fig. 2.3 (a) Construction of sequence program


The 1st level sequence part operates every 8 ms (highspeed sequential
operation).
If the 1st level sequence part is long, the total operating time, including
the 2nd level sequence part, is extended. Therefore the 1st level sequence
part must be programmed to be processed in as short time as possible.
The 2nd level sequence part operates every 8n ms. Here n is a dividing
number for the 2nd level sequence part. The 2nd level sequence part is
divided automatically when the sequence program is transferred to the
RAM for debugging in the CNC unit or it is written on ROM after the
program is created. The time for one cycle of the sequence program is
then displayed on the offline programmer screen.
The 3rd level sequence part operates during idle time of PMC.
(1) Division of the 2nd level sequence part
The 2nd level sequence part must be divided in order to execute the
1st level sequence part. For example a sequence program is executed
in the following sequence when the dividing number is n. (See Fig.
2.3 (b), 2.3 (c) )
After the last 2nd level sequence part (division n) is executed, the
sequence program is executed again from the beginning. Thus, when
the dividing number is n, the cycle of execution is 8mms (8msn).
The 1st level sequence operates every 8 msec, and the 2nd level
sequence every 8n msec. If the steps of the 1st level sequence is
increased, the steps of the 2nd level sequence operating within 8 msec
becomes less, thereby increasing the dividing number and making
the processing time longer. Therefore, it is desirable to program so
as to reduce the 1st level sequence to a minimum.
In the, PMCSA1, SA2, SB and SB2, 1.25 ms of 8 ms is assigned
to execution of the 1st and 2nd level sequences. The remaining time
is assigned to NC processing.
In the PMCSC, 5 ms of 8 ms is assigned to execution of the 1st and
2nd level sequences. The standard setting value is 5 ms when system
parameter LADDER EXEC = 100%. The remaining time is assigned
to execution of the 3rd level sequence and the program.

44
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

8ms 8ms 8ms

1st level 1.25ms 1.25ms 1.25ms

Division 1 Division 2 Division n Division 1


2nd level

NC processing

Fig. 2.3 (b) Sequence in which the Sequence Program Is Executed (PMCSA1, SA2, SB and SB2)

8ms 8ms 8ms

1st level 5ms 5ms 5ms

2nd level Division 1 Division 2 Division n Division 1

3rd level, program execution,


and displaying the PMC screen

Fig. 2.3 (c) Sequence in which the Sequence Program Is Executed (PMCSC)
(2) 1st level sequence part
Only shortwidth pulse signals are processed. These signals include
emergency stop, overtravel of each axis, reference point return
deceleration, external deceleration, skip, measuring position arrival
and feed hold signals.
(3) 3rd level sequence
The purpose of the 3rd level sequence is to execute such programs
as display processing or control status monitor having no direct
relation to the machine control (operator message, alarm display,
etc.), to lighten the load of the 2nd level program having a direct
relation to the machine control by transferring former programs to the
3rd level, and to shorten the PMC execution time (cycle time).
For PMCRC, when 3rd level program is not used, command SUB
48 (END3) following SUB 2 instruction.
(4) Divided system and undivided system
There is a model can use the divided system and undivided system
among the PMCs. In the divided system, a ladder program is divided
before being executed if all ladder program run regardless of the
sequence state (see Fig. 2.3 (d)).
For an actual ladder program, not all ladder program run. The PMC
cannot therefore be used effectively.
The PMC can execute the ladder program in the system for terminating
one cycle of the program using the time to execute the actual ladder
program (undivide system) as well as in the divided system.
The time required for the one cycle can be reduced by the effective
use of jump instructions in the ladder program.
Since the sequence using many functional instructions requires a lot
of processing time, the undivided system should be specified so that
the PMC is used more effectively (see Fig. 2.3 (e)).
To operate the PMC in the undivided system, set system parameter
IGNORE DIVIDE CODE to YES.
The PMC model usable only the undivided system, does not have
setting system parameter IGNORE DIVIDE CODE. It is always

45
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

operated under the undivided system.


A
Functional
instruction

B
Functional
instruction

C
Functional
instruction

The ladder program is divided if all functional instructions are


executed regardless of execution of an actual ladder program.

Fig. 2.3 (d) Divisions in the divided system

A
Functional
instruction

B
Functional
instruction

C
Functional
instruction

Execution of an actual ladder program when A = 0, B = 1, and C = 0.

Fig. 2.3 (e) Execution of a ladder program


(a) Example of effective use of the undivided system
Example 1)
Many M codes are usually used. Since more than one M code
is not used in the same block, the decoded M code is divided
into several parts. Machine instructions are used as these
decoded parts.
The M code is divided into M codes having two digits such
as M21, M22, M24, M28, and so on.
Example 2)
To reduce the number of ROM types using the same ladder
program for multiple machines, a PMC parameter must be
specified so that any of the following ladder program run.

Ladder A (Ladder common to all machines)

(Selected by a PMC parameter)

(Ladders dedicated
Ladder B1 Ladder B2 Ladder B3 to each machine)

Fig. 2.3 (f)

46
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

(5) Construction of sequence program in the case of using Subprogram.

1st level sequence part

END1 (SUB 1)

2nd level sequence part

END2 (SUB 2)

3rd level sequence part


(Only about the PMC
model usable the 3rd
level sequence)
END3 (SUB 48)

SP
D Sub program must be written between 2nd
D level program and 3rd level program.

SPE

SP

Sub program

SPE

SP

SPE

End of sequence program END D The end of sequence program is expressed


D by END command.

Fig. 2.3 (g)

47
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

2.4 : Can be used


SEQUENCE : Cannot be used

PROGRAM PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6


STRUCTURING
With the conventional PMC, a ladder program is described sequentially.
By employing a ladder language that allows structured programming, the
following benefits are derived:
D A program can be understood and developed easily.
D A program error can be found easily.
D When an operation error occurs, the cause can be found easily.
Three major structured programming capabilities are supported.
(1) Subprogramming
A subprogram can consist of a ladder sequence as the processing unit.

Job A D D D f

FUNC D D D f
Job B
D
D
D

(2) Nesting
Ladder subprograms created in (1) above are combined to structure
a ladder sequence.
Main Program Sub Program1 Sub Program2

Job A Job A1 Job A11

D
D
Job B D Job A12

Job An

48
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

(3) Conditional branch


The main program loops and checks whether conditions are satisfied.
If a condition is satisfied, the corresponding subprogram is executed.
If the condition is not satisfied, the subprogram is skipped.
Main Program Sub Program1

PROCESS11 PROCESS11
STATE1 PROCESS1

PROCESS12
STATE2 PROCESS2

D PROCESS13
D
D

For details, see Chapter 9.

49
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

2.5 Input signals (M function, T function, etc.) from the CNC and those (cycle
start, feed hold, etc.) from the machine tool are sent to the PMC.
PROCESSING I/O
SIGNALS Signals for the CNC (cycle start, feed hold, etc.) and those for the machine
tool (tunret rotation, spindle stop, etc.) are output from the PMC.
Fig. 2.4 shows the relationship between these signals and the PMC.
Input signals are entered in the input memory of PMC and output signals
are issued from PMC.
As shown in Fig. 2.5, the input signals are synchronized only in the 2nd
level sequence part.

CNC PMC
Input memory of CNC Sequence program

Input signals from 1st level


CNC sequence part

Transmitted at the
start of 2nd level 2nd level synchronous
input signal memory

Input signals from


CNC
Transmitted every 8 ms

Input signals from 2nd level


machine tool
sequence part

Output memory of CNC

Output signals to
CNC

MT
Output signalmemory

Output signals to Output signals to the


machine tool machine

Input signal memory

Input signals from Input signals from 3rd level


machine tool machine sequence part
(Only PMCSC)
Transmitted
every 2 ms

Fig. 2.5 PMC I/O signals

50
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

2.5.1 (1) Input memory of CNC


Input Signal The input signals from CNC are loaded in memory of CNC and are
Processing transferred to the PMC at intervals of 8 ms.
Since the 1st level and the 3rd level sequence part directly refer to
these signals and process operations, these signals do not
synchronize with input signals from the CNC.
See item 2.5.3.
(2) Input signals from machine tool (DI/DO card)
Input signals from the machine tool are transferred to the input signal
memory from the input circuit (DI/DO card). 1st level and 3rd level
sequence part directly processes by reading signals loaded in the
input signal memory.
(3) Input signal memory
The input signal memory stores signals transferred from the machine
tool at intervals of 2 ms period.
The PMC 1st level sequence part and 3rd level sequence part are used
to read and process signals stored in this memory.
In this case, state of signals set in the input signal memory
synchronizes with that of 1st level sequence part but not with that of
3rd level sequence part.
See item 2.5.3.
(4) 2nd level synchronous input signal memory
The 2nd level synchronous input signal memory stores signals
processed by the 2nd level sequence section.
State of the signals set in this memory synchronizes with that of the
2nd level sequence part.
Input signal memory and input signals from the CNC are transferred
to the 2nd level synchronous input signal memory only at the
beginning of execution of the 2nd level sequence section. Therefore,
the status of the 2nd level synchronous input signal memory does not
change from the beginning to end of the execution of the 2nd level
sequence part.
Programmer function makes the processing so that the 1st level
sequence section and 3rd level sequence section use the input signal
memory and input signals from the CNC side and the 2nd level
sequence section uses the 2nd level synchronous input signal
memory.

2.5.2 (1) CNC output memory


Output Signal The output signals are transferred from the PMC to the CNC output
Processing memory at intervals of 8 ms.
(2) Output signals to machine tool (DI/DO card)
Output signals to the machine tool are transferred from the PMC
output signal memory to the machine tool.
(3) Output signal memory
The output signal memory is set by the PMC sequence program.
Signals stored in this memory are transferred to the machine side at
a 2 ms period.

51
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

NOTE
The status of the CNC input memory, input signals from
machine, CNC output memory and output signals to
machine can be checked by using the PC selfdiagnosis
function.
The selfdiagnosis number specified is the address number
used by the sequence program.

2.5.3 Signals input from the CNC are transferred to the PMC at intervals of 8
I/O Signals to CNC ms.
Signals output to the CNC are transferred from the PMC at intervals of
8 ms.
PMC I/O signals are generally transferred at intervals of 8 ms.
In this case, note that state of the input signals from the CNC does not
synchronize with that of the 1st level sequence program and the 2nd level
sequence program. By this reason, if an input signal from the CNC may
change while execution of the 1st level sequence program, for example,
some trouble may occur like example in Fig. 2.5.3 (a).
To avoid such trouble, write the state of signal TF in an internal relay at
the start of the 1st level sequence, then the 1st level sequence program
shall refer to the internal relay as signal TF. See Fig. 2.5.3 (b).
TF W1

TF W2

END 1

If after TF=0 is load, signal state changes to TF=1,


state of W1=1 and W2=1 may momentary occur

Fig. 2.5.3 (a)

TF TFM

TFM W1

TFM W2

END 1

Make signal TF synchronized one, and state of


W1=1 and W2=1 may not occur.

Fig. 2.5.3 (b)

52
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

2.5.4 The status of the same input signal may be different in the 1st level and
Difference of Status of 2nd level sequences. That is, at 1st level, processing is performed using
input signal memory and at 2nd level, processing is performed using the
Signals between 1st 2nd level synchronous input signal memory. Therefore, it is possible for
Level and 2nd Level a 2nd level input signal to delay by a cycle of 2nd level sequence execution
at the worst, compared with a 1st level input signal.
This must be kept in mind when writing the sequence program.
A.M ON (short time width pulse signal)
Signal statesO B OFF
C OF

Differences drawn in Fig. 2.5.4 (a) and Fig. 2.5.4 (b) when the 1st level
sequence has been executed are as follows:
(a) Fig. 2.5.4 (a)
W2 may not be 1 even when W1=1. (Because the A.M signal may
be different at the 1st and 2nd levels.)
(b) Fig. 2.5.4 (b)
If W1=1, W2=1.
When performing the sequence shown in Fig. 2.5.4 (a), proceed
as follows:
At 1st level, perform a highspeed sequence when the A.M signal
changes (operating).
At 2nd level, perform sequence processing when the A.M signal
does not change (stopped).

A.M B A.M B

W1 W1

1st Level

END 1 END 1

A.M C W1 C

2nd Level W2 W2

Fig. 2.5.4 (a) Fig. 2.5.4 (b)

53
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

2.6 Interlocking is externally important in sequence control safety.


Interlocking with the sequence program is necessary. However,
INTERLOCKING interlocking with the end of the electric circuit in the machine tool
magnetics cabinet must not be forgotten. Even though logically
interlocked with the sequence program (software), the interlock will not
work when trouble occurs in the hardware used to execute the sequence
program. Therefore, always provide an interlock inside the machine tool
magnetics cabinet panel to ensure operator safety and to protect the
machine from damage.

54
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

2.7 The exact sequence processing time is displayed on the CRT screen when
the sequence programs have been completed. The time is 2nd level
SEQUENCE sequence division number n x 8 ms.
PROGRAM This section explains how to estimate processing times that are important
PROCESSING TIME in sequence control when the ladder diagram, the basis of sequence
program control, is almost complete.
(1) Processing time calculation units
Sequence processing time estimation is based on the basic
instructions (AND, OR, etc.). The execution time for a functional
instruction is given in the execution constant column of the
Functional Instruction Table. Converted to a basic instruction; that
is the number of basic instructions that a functional instruction is
equivalent to.
Processing time is determined for the above using the equation in
item below.
(2) Processing time estimation equation
The number of division (n) in the 2nd level sequence is determined
and the processing time is calculated using the following equations:
Sequence processing time =
n (number of division) 8 msec
(LT) sec
n= +1
(ET)sec (HT)sec
(n is an integer, fractions are omitted)
(a) (HT) is the execution time for the 1st level sequence section.
(HT)={(number of steps in basic instruction)+(sum of functional
instruction execution time constants) 10} (IT) sec
Execution time constant for END.1 (206) must be included in HT.
(b) (LT) is the execution time for the 2nd level sequence section.
(LT)={(number of steps in basic instruction)+(sum of functional
instruction execution time constants) 10} (IT) sec
END.2 execution time (127) must be included.
(c) (ET) is the execution time assigned to the 1st and 2nd level parts
out of 8 ms.
For PMCSB
(ET) = 1.25 ms = 1250s
For PMCSC (standard setting when LADDER EXEC = 100%)
(ET) = 5 ms = 5000s
(d) IT) is the execution constant for calculating the processing time.
The value is as follows:
(IT) = 0.15s

55
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

(3) Processing time calculation example


(a) 1st level sequence
Basic instruction: 100 steps
Functional instruction:
CTR: 2 times,
COMPB: 2 times
CTR execution time constant: 26
COMPB execution time constant: 24
END.1 execution time constant: 206
HT={100+(26 2+24 2+206) 10} 0.15 =474 sec
(b) 2nd level sequence
Basic instruction: 6,000 steps
Functional instruction:
TMR: 35 times,
DECB: 25 times,
ROTB: 2 times
TMR execution time constant: 23
DECB execution time constant: 20
ROTB execution time constant: 33
END.2 execution time constant: 32
LT={6,000+(23 35+20 25+33 2+32) 10} 0.15=3004.5msec
(c) Determination of the number of divisions (n)
3004.5 sec
n= +1 = 4.87
1250sec 474 sec

(d) Processing time calculation


Sequence processing time=4 (number of division) 8 msec=32
msec

NOTE
For the PMCSB/SC, see the execution time constant of
each function instruction in Table 5 (b) in Section I5, PMC
FUNCTION INSTRUCTIONS.

56
B61863E/14 PMC SEQUENCE PROGRAM 2. SEQUENCE PROGRAM

2.8 The following tables list memory capacities required for a sequence
program. Create a sequence program so that the total capacity of these
SEQUENCE items does not exceed the sequence program memory capacity.
PROGRAM MEMORY
CAPACITY
Table 2.8 (a) PMCSB7

Memory capacity
Type Item
(Note 1)

Ladder (Note 2) Basic instruction 4 bytes

Functional instruction 4 bytes

Functional instruction parameter 4 bytes

Symbol/comment One symbol or comment 24 bytes


(Note 2)
One halfwidth character in a comment 1 byte (Note 3)

Message (Note 2) One halfwidth alphanumeric character in 1 byte (Note 4)


a message

Others System used area About 15K bytes

Table 2.8 (b) PMCSB4/SB6/SC4/NB2/NB6

Memory capacity
Type Item
(Note 1)

Ladder (Note 2) Basic instruction 4 bytes

Functional instruction 4 bytes

Functional instruction parameter 4 bytes

Symbol/comment One symbol or comment 12 bytes


(Note 2)
One halfwidth character in a comment 1 byte

Message (Note 2) One halfwidth alphanumeric character in 1 byte (Note 4)


a message

Others System used area About 4K bytes

Table 2.8 (c) PMCSB6 (I/O links expanded)

Memory capacity
Type Item
(Note 1)

Ladder (Note 2) Basic instruction 4 bytes

Functional instruction 4 bytes

Functional instruction parameter 4 bytes

Symbol/comment One symbol or comment 12 bytes


(Note 2)
One halfwidth character in a comment 1 byte

Message (Note 2) One halfwidth alphanumeric character in 1 byte (Note 4)


a message

Others System used area About 9.5K bytes

57
2. SEQUENCE PROGRAM PMC SEQUENCE PROGRAM B61863E/14

Table 2.8 (d) PMCSA1/SA3/SA5/SB/SB2/SB3/SB5/SC/SC3/PA1/PA3/NB

Memory capacity
Type Item
(Note 1)

Ladder (Note 2) Basic instruction 4 bytes

Functional instruction 4 bytes

Functional instruction parameter 4 bytes

Symbol/comment One symbol or comment 10 bytes


(Note 2)
One halfwidth character in a comment 1 byte

Message (Note 2) One halfwidth alphanumeric character in 1 byte (Note 4)


a message

Others System used area About 2K bytes

NOTE
1 The total capacity of a sequence program (including all
items such as ladder, symbols/comments, and messages)
cannot exceed the capacity of the sequence program
storage memory. If the ladder, symbol/comment, or
message area is large, the size of another area may be
limited.
2 The PMC programmer may adjust arrangement of the areas
in the sequence program memory to improve processing
efficiency. As a result, up to 1K (1024) bytes may be added
to the total capacity of each type of data.
3 A fullwidth character requires double the capacity.
4 For each of halfwidth katakana characters and special
characters, and fullwidth hiragana characters, kanji
characters, and special characters, a capacity of 1 byte is
required per digit of the notation (including characters
preceding and following the character such as @) by
character code input. For details of notation by character
code input, refer to the paragraph describing DISPB in
Chapter 5, FUNCTIONAL INSTRUCTIONS.

58
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

3 ADDRESS

An address shows a signal location. Addresses include input/output


signals with respect to the machine, the input/output signals with respect
to the CNC, the internal relays, the counters, the keep relays (PMC
parameters), and data table. Each address consists of an address number
(for every 8 signals) and a bit number (0 to 7). Enter the symbol table
showing the relationship between the signal names and the addresses into
the programmer by using the keys of the CRT/MDI or the keys of the
keyboard of the offline programmer as in the case of the sequence
program.
For programming, see Chapter III, IV and V.
(1) Addresses related to PMC
Four types of addresses as shown in Fig. 3 are necessary for creation
of the PMC sequence program.

Internal relay

Machine
Note) CNC (MT)
signal PMC signal

Nonvolatile memory
(1) Counter
(2) Keep relay
(3) Data table
(4) Variable Timer

Fig. 3 Addresses related to PMC

(a) The input/output signals with respect to the PMC, which are
indicated by the solid lines, are transferred via the receiver and the
driver of the I/O board.
(b) The input/output signals with respect to the PMC, which are
indicated by the broken lines, are transferred only in the memory
such as the RAM.
All of these signals can be displayed on the CRT/MDI panel.
(2) Address regulations
The address comprises the address number and the bit number in the
format as shown below.

59
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

X 127. 7

Bit number (0 to 7)
Address number (within four numerics after alphabet)

An alphabet must be specified at the beginning of the address number


to indicate the type of the signal as shown in Table 3. When
specifying the address in the byte unit by the functional instruction,
specify X127. In this case, . and the bit number are not necessary.

Table 3 Alphabetic characters in address numbers (1)

Model
Character Signal description Power Mate - D Power Mate- F Power Mate- H
PMC PA1 PMC- PA3 PMC- PA3 PMC- PA3
X Signal from the machine to the X0 to X127 X1000 to X1005 X0 to X127
PMC (MT to PMC) (I/O Link Master) X1020 to X1027 (I/O Link Master)
X1000 to X1003 (Slave) X1000 to X1003
(Builtin l/O Card) (Builtin I/O Card)
X1020 to X1051 X1020 to X1051
(I/O Link Slave) (I/O Link Slave)
Y Signal from the PMC to the Y0 to Y127 Y1000 to Y1003 Y0 to Y127
machine (PMC to MT) (I/O Link Master) Y1020 to Y1027 (I/O Link Master)
(Caution 3) Y1000 to Y1002 (Slave) Y1000 to Y1002
(Builtin I/ O Card) (Builtin l/O Card)
Y1020 to Y1051 Y1020 to Y1051
(I/O Link Slave) (I/O Link Slave)
F Signal from the NC to the PMC F0 to F255 F0 to F255 F0 to F255
(NC to PMC) F1000 to F1255
(Dual path control)
G Signal from the PMC to the NC G0 to G255 G0 to G255 G0 to G255
(PMC to NC) G1000 to G1255
(Dual path control)
R Internal relay (Caution 1) R0 to R999 R0 to R999 R0 to R999 R0 to R999
R9000 to R9000 to R9000 to R9117 R9000 to R9117
R9099 R9117
A Message request signal A0 to A24 A0 to A24 A0 to A24
C Counter C0 to C79 C0 to C79 C0 to C79
K Keep relay (Caution 2) K0 to K19 K0 to K19 K0 to K19
T Variable timer T0 to T79 T0 to T79 T0 to T79
D Data table D0 to D1859 D0 to D1859 D0 to D1859
L Label Number L1 to L9999 L1 to L9999 L1 to L9999
P Subprogram Number P1 to P512 P1 to P512 P1 to P512

CAUTION
1 R9000 to R9117 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.
2 K17 to K19 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.
3 I/O Link Master function is not available in the Power
MateMODEL F.
You cannot use the address X0127 and Y0127.

60
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic characters in address numbers (2)

Model
Character Signal description FS20A FS18A
PMC-SA1 PMC-SA3 PMC-SA1 PMC-SA2 PMC-SA3
X Signal from the machine to the X0 to X127 X0 to X127
PMC (MT to PMC) X1000 to X1013 (Caution 1) X1000 to X1019
Y Ssignal from the PMC to the Y0 to Y127 Y0 to Y127
machine (PMC to MT) Y1000 to Y1013 (Caution 1) Y1000 to Y1014
F Signal from the NC to the PMC F0 to F255 F0 to F255
(NC to PMC) F1000 to F125 F1000 to F1255
G Signal from the PMC to the NC G0 to G255 G0 to G255
(PMC to NC) G1000 to G1255 G1000 to G1255
R Internal relay (Caution 2) R0 to R999 R0 to R999 R0 to R999 R0 to R999
R9000 to R9099 R9000 to R9117 R9000 to R9099 R9000 to R9117
A Message request signal A0 to A24 A0 to A24
C Counter C0 to C79 C0 to C79
K Keep relay (Caution 3) K0 to K19 K0 to K19
D Data table D0 to D1859 D0 to D1859
T Variable timer T0 to T79 T0 to T79
L Label number L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P512

CAUTION
1 X1000 to X1007 and Y1000 to Y1007 are configured as a
matrix.
2 R9000 to R9117 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.
3 K17 to K19 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.

61
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3 Alphabetic characters in address numbers (3)

Chara Model
Signal description
cter PMC-SB PMC-SB2 PMC-SB3 PMC-SC PMC-SC3 PMC-NB
X Signal from the machine to the X0 to X127 X0 to X127
PMC (MT to PMC) X1000 to X1039
Y Signal from the PMC to the Y0 to Y127 Y0 to Y127
machine (PMC to MT) Y1000 to Y1029
F Signal from the NC to the PMC F0 to F255 F0 to F319
(NC to PMC) F1000 to F1255
G Signal from the PMC to the NC G0 to G255 G0 to G511
(PMC to NC) G1000 to G1255
R Internal relay (Caution 1) R0 to R999 R0 to R999 R0 to R1499 R0 to R1499 R0 to R1499 R0 to R1499
R9000 to R9000 to R9000 to R9000 to R9000 to R9000 to
R9099 R9117 R9117 R9099 R9117 R9117
A Message request signal A0 to A24
C Counter C0 to C79
K Keep relay (Caution 2) K0 to K19
D Data table D0 to D1859 D0 to D2999
T Variable timer T0 to T79
L Label number L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P512

CAUTION
1 R9000 to R9117 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.
2 K17 to K19 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.

62
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic characters in address numbers (4)

Model
Signal descrip- Series
Character Series 16-MODEL B/Series 18-MODEL B
tion 18-MODEL B
PMC-SB3 PMC-SC3 PMC-SB4 PMC-SC4 PMC-SA1
X Signal from the X0 to X127 X0 to X127
machine to the PMC X1000 to X1019 X1000 to X1019
(MT to PMC) X1020 to X1039 X1020 to X1039
Y Signal from the PMC Y0 to Y127 Y0 to Y127
to the machine (PMC Y1000 to Y1014 Y1000 to Y1014
to MT) Y1020 to Y1034 Y1020 to Y1034
F Signal from the NC to F0 to F255 F0 to F255 F0 to F511 F0 to F511 F0 to F255
the PMC (NC to F1000 to F1255 F1000 to F1255 F1000 to F1511 F1000 to F1511 F1000 to F1255
PMC) F2000 to F2511 F2000 to F2511
G Signal from the PMC G0 to G255 G0 to G255 G0 to G511 G0 to G511 G0 to G255
to the NC (PMC to G1000 to G1255 G1000 to G1255 G1000 to G1511 G1000 to G1511 G1000 to G1255
NC) G2000 to G2511 G2000 to G2511
R Internal relay R0 to R1499 R0 to R1499 R0 to R2999 R0 to R2999 R0 to R999
R9000 to R9117 R9000 to R9117 R9000 to R9199 R9000 to R9199 R9000 to R9099
A Message request A0 to A24 A0 to A24 A0 to A124 A0 to A124 A0 to A24
signal
C Counter C0 to C79 C0 to C79 C0 to C199 C0 to C199 C0 to C79
K Keep relay K0 to K19 K0 to K19 K0 to K39 K0 to K39 K0 to K19
K900 to K909 K900 to K909
T Data table T0 to T79 T0 to T79 T0 to T299 T0 to T299 T0 to T79
D Variable timer D0 to D2999 D0 to D2999 D0 to D7999 D0 to D7999 D0 to D1859
L Label number L1 to L9999 L1 to L9999 L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P512 P1 to P2000 P1 to P2000

63
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3 Alphabetic characters in address numbers (5)

Model
Character Signal description Series 16-MODEL C/Series 18-MODEL C
PMC-SB5 PMC-SC3 PMC-SB6 PMC-SC4
X Signal from the machine to the PMC (MT to X0 to X127
PMC) X1000 to X1019
X1020 to X1039
Y Signal from the PMC to the machine (PMC Y0 to Y127
to MT) Y1000 to Y1014
Y1020 to Y1034
F Signal from the NC to the PMC (NC to F0 to F255 F0 to F255 F0 to F511 F0 to F511
PMC) F1000 to F1255 F1000 to F1255 F1000 to F1511 F1000 to F1511
F2000 to F2511 F2000 to F2511
G Signal from the PMC to the NC (PMC to G0 to G255 G0 to G255 G0 to G511 G0 to G511
NC) G1000 to G1255 G1000 to G1255 G1000 to G1511 G1000 to G1511
G2000 to G2511 G2000 to G2511
R Internal relay R0 to R1499 R0 to R1499 R0 to R2999 R0 to R2999
R9000 to R9117 R9000 to R9117 R9000 to R9199 R9000 to R9199
A Message request signal A0 to A24 A0 to A24 A0 to A124 A0 to A124
C Counter C0 to C79 C0 to C79 C0 to C199 C0 to C199
K Keep relay K0 to K19 K0 to K19 K0 to K39 K0 to K39
K900 to K909 K900 to K909
T Data table T0 to T79 T0 to T79 T0 to T299 T0 to T299
D Variable timer D0 to D2999 D0 to D2999 D0 to D7999 D0 to D7999
L Label number L1 to L9999 L1 to L9999 L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P512 P1 to P2000 P1 to P2000

64
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic characters in address numbers (6)

Model
Character Signal description Series 21/210-MODEL B
PMC-SA1 PMC-SA3
X Signal from the machine to the X0 to X127
PMC (MT to PMC) X1000 to X1011
Y Signal from the PMC to the Y0 to Y127
machine (PMC to MT) Y1000 to Y1008 (Note)
F Signal from the NC to the PMC F0 to F255
(NC to PMC) F1000 to F1255
G Signal from the PMC to the NC G0 to G255
(PMC to NC) G1000 to G1255
R Internal relay R0 to R1999 R0 to R1499
R9000 to R9099 R9000 to R9117
A Message request signal A0 to A24
C Counter C0 to C79
K Keep relay K0 to K19
D Data table D0 to D1859
T Variable timer T0 to T79
L Label number L1 to L9999
P Subprogram number P1 to P512

NOTE
The Y addresses for the 4082 series are Y0 to Y127 and
Y1000 to Y1007.

65
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3 Alphabetic characters in address numbers (7)

Model
Sym-
Type of signal FANUC Series 16i/160i/18i/180iA
bol
PMCSB5 PMCSB6
X Signal from the machine to PMC X0 to X127 X0 to X127
(MT PMC) (Note 1) X200 to X327 (Note 2)
(Note 1)
Y Signal from the PMC to machine Y0 to Y127 Y0 to Y127
(PMC MT) (Note 1) Y200 to Y327 (Note 2)
(Note 1)
F Signal from the NC to PMC F0 to F255 F0 to F511
(NC PMC) F1000 to F1255 F1000 to F1511
F2000 to F2511
G Signal from the PMC to NC G0 to G255 G0 to G511
(PMC NC) G1000 to G1255 G1000 to G1511
G2000 to G2511
R Internal relay R0 to R1499 R0 to R2999
R9000 to R9117 R9000 to R9199
A Message request signal A0 to A24 A0 to A124
C Counter C0 to C79 C0 to C199
K Keep relay K0 to K19 K0 to K39
K900 to K909
D Variable timer T0 to T79 T0 to T299
T Data table D0 to D2999 D0 to D7999
L Label number L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P2000

NOTE
1 The addresses (X1000 and up, Y1000 and up) cannot be assigned for I/O. Never use X1000
and up, or Y1000 and up.
2 I/O of the I/O Link channel 2 can be assigned to the addresses (X200 to X327, Y200 to Y327).
You can use the I/O Link channel 2 only when CNC hardware support the I/O Link 2channel
and optional I/O Link expansion is provided with CNC. And to assign to these areas, it is
necessary to use programming software that supports the I/O Link expansion.

66
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic characters in address numbers (8)

Model
Sym-
Type of signal FANUC Series 21i/210iA
bol
PMCSA1 PMCSA5 PMCSB6
X Signal from the machine to PMC X0 to X127 (Note 1) X0 to X127 (Note 1)
(MT PMC) X200 to X327 (Note 2)

Y Signal from the PMC to machine Y0 to Y127 (Note 1) Y0 to Y127 (Note 1)


(PMC MT) Y200 to Y327 (Note 2)

F Signal from the NC to PMC F0 to F255 F0 to F511


(NC PMC) F1000 to F1255 F1000 to F1511
F2000 to F2511
G Signal from the PMC to NC G0 to G255 G0 to G511
(PMC NC) G1000 to G1255 G1000 to G1511
G2000 to G2511
R Internal relay R0 to R999 R0 to R999 R0 to R2999
R9000 to R9099 R9000 to R9117 R9000 to R9199
A Message request signal A0 to A24 A0 to A124
C Counter C0 to C79 C0 to C199
K Keep relay K0 to K19 K0 to K39
K900 to K909
D Variable timer T0 to T79 T0 to T299
T Data table D0 to D1859 D0 to D7999
L Label number L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P2000

NOTE
1 The addresses (X1000 and up, Y1000 and up) cannot be assigned for I/O. Never use X1000
and up, or Y1000 and up.
2 I/O of the I/O Link channel 2 can be assigned to the addresses (X200 to X327, Y200 to Y327).
You can use the I/O Link channel 2 only when CNC hardware supports the I/O Link 2channel
and optional I/O Link expansion is provided with CNC. And to assign to these areas, it is
necessary to use programming software that supports the I/O Link expansion.

67
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3 Alphabetic characters in address numbers (9)

Model
Sym-
Signal description FANUC Power Mate iMODEL D/H
bol
PMCSB5 PMCSB6
X Input signal from the machine to the X0 to X127 (I/O Link Master) X0 to X127 (I/O Link Master)
PMC (MT to PMC) X1000 to X1003 (Builtin I/O) X1000 to X1003 (Builtin I/O)
X1020 to X1051 (I/O Link Slave) X1020 to X1051 (I/O Link Slave)
Y Output signal from the PMC to the Y0 to Y127 (I/O Link Master) Y0 to Y127 (I/O Link Master)
machine (PMC to MT) Y1000 to Y1003 (Builtin I/O) Y1000 to Y1003 (Builtin I/O)
Y1020 to Y1051 (I/O Link Slave) Y1020 to Y1051 (I/O Link Slave)
F Input signal from the NC to the PMC F0 to F255 F0 to F511
(NC to PMC) F1000 to F1255 F1000 to F1511
F2000 to F2511
G Output signal from the PMC to the G0 to G255 G0 to G511
NC (PMC to NC) G1000 to G1255 G1000 to G1511
G2000 to G2511
R Internal relay R0 to R1499 R0 to R2999
R9000 to R9117 R9000 to R9199
A Message request signal A0 to A24 A0 to A124
C Counter C0 to C79 C0 to C199
K Keep relay K0 to K19 K0 to K39
K900 to K909
T Variable timer T0 to T79 T0 to T299
D Data table D0 to D2999 D0 to D7999
L Label number L1 to L9999 L1 to L9999
P Subprogram number P1 to P512 P1 to P2000

68
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic characters in address numbers (10)

Model
Series 15-MODEL B
Character Signal description
PMC-NB
PMC-NB2
(4048)
X Input signal from the machine to X0 to X127
the PMC (MT to PMC)
Y Output signal from the PMC to Y0 to Y127
the machine (PMC to MT)
F Input signal from the NC to the F0 to F319
PMC (NC to PMC)
G Output signal from the PMC to the G0 to G511
NC (PMC to NC)
R Internal relay R0 to R1499 R0 to R1499
R9000 to R9099 R9000 to R9117
A Message request signal A0 to A24 A0 to A124
C Counter (Nonvolatile memory) C0 to C79 C0 to C199
K Keep relay (Nonvolatile memory) K0 to K19 K0 to K39
K900 to K909
D Data table (Nonvolatile memory) D0 to D2999 D0 to D7999
T Variable timer T0 to T79 T0 to T299
(Nonvolatile memory)
L Label number L1 to L9999
P Subprogram number P1 to P512 P1 to P2000

CAUTION
1 R9000 to R9199 are areas reserved for the PMC system
program;
these areas cannot be used for output by a sequence
program.
2 K17 to K19 or K900 to K909 are areas reserved for the PMC
system program;
these areas cannot be used for output by a sequence
program.
3 Please refer to (3) PMCNB(Series 4047).

69
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3 Alphabetic Characters for PMC Address Number (11)

Model
Character Signal description FANUC Series 15i
PMCNB6
X Input signal from machine to PMC X0 to X127
(MTPMC)
Y Output signal from PMC to machine Y0 to Y127
(PMCMT)
F Input signal from the NC to PMC F0 to F511
(NCPMC)
G Output signal from the PMC to NC G0 to G511
(PMCNC)
R Internal relay R0 to R2999
R9000 to R9199
A Message request signal A0 to A124
C Counter C0 to C199
K Keep relay K0 to K39
K900 to K909
T Variable timer T0 to T299
D Data table D0 to D7999
L Label number L1 to L9999
P Subprogram number P1 to P2000

70
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic Characters for PMC Address Number (12)

Control type
Address Type of signal Series 16i/18i/21iB
PMCSA1 PMCSB7
X Input signal from machine tool to X0 to X127 X0 to X127
PMC (MTPMC) X200 to X327*1
X1000 to X1127*2
Y Output signal from PMC to Y0 to Y127 Y0 to Y127
machine tool (PMCMT) Y200 to Y327*1
Y1000 to Y1127*2
F Input signal from NC to PMC F0 to F255 F0 to F767*3
(NCPMC) F1000 to F1767*4
F2000 to F2767*4
F3000 to F3767*5
G Output signal from PMC to NC G0 to G255 G0 to G767*3
(PMCNC) G1000 to G1767*4
G2000 to G2767*4
G3000 to G3767*5
R Internal relay R0 to R999 R0 to R7999
R0 to R9099 R9000 to R9499*6
E Extra relay*7 E0 to E7999
A Message request A0 to A24 A0 to A249
Message display state*8 A9000 to A9249
C Counter C0 to C79 C0 to C399
C5000 to C5199*9
K Keep relay K0 to K19 K0 to K99
K900 to K919*10
T Variable timer T0 to T79 T0 to T499
T9000 to T9499*11
D Date table D0 to D1859 D0 to D9999
L Label number L1 to L9999
P Subprogram number P1 to P2000

71
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

CAUTION
1 These addresses are used for channel 2 of I/O Link. I/O link
expansion option is necessary.
2 This area is reserved for PMC. I/O can not be assigned in
it.
Dont use it in sequence program.
3 This area contains PMC reserve. Actual available
addresses depend on the configuration of CNC system.
4 This area is used for multi path system. It contains PMC
reserve. Actual available addresses depend on the
configuration of CNC system.
5 This area is for PMC reserve. Dont use it in sequence
program.
6 This area is used for PMC system software as special relay.
Please use these according to the explanation of each
address.
7 This area can be used equally as internal relay(R).
These relays (E) are nonvolatile type. However, these can
be input/output to/from memory card, etc, as PMC
parameter.
8 These addresses are message display state signals that
have onetoone correspondence to message display
request signal. It is impossible to write into these addresses.
9 This area is used for counter instruction (CTRB) that
requires preset value as fixed number.
10 This area is used for PMC control software. Please use
these signals according to each explanation.
11 This area is for PMC reserve. Dont use it in sequence
program.

72
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3 Alphabetic Characters for PMC Address Number (12)

FANUC Series 0i
Character Signal description
PMCSA1 PMCSA3
X Signal from machine to PMC X0 to X127
(MTPMC) X1000 to X1011

Y Signal from PMC to machine Y0 to Y127


(PMCMT) Y1000 to Y1008
F Signal from NC to PMC F0 to F255
(NCPMC) F1000 to F1255
G Signal from PMC to NC G0 to G255
(PMCNC) G1000 to G1255
R Internal relay R0 to R999 R0 to R999
R9000 to R9099 R9000 to R9117
A Message request signal A0 to A24
C Counter C0 to C79
K Keep relay K0 to K19
T Variable timer T0 to T79
D Data table D0 to D1859
L Label number L1 to L9999
P Subprogram number P1 to P512

73
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.1 Addresses of the interfaces are outlined below. For details, see
CONNECTING MANUAL of Series 16.
ADDRESSES
BETWEEN PMC AND (1) Basic machine interface
CNC (PMCNC) (a) PMCzCNC related signals
The addresses for Series 15 are from F0 to F511, for the others are
from F0 to F255.
For details of the signals, see CONNECTING MANUAL of
CNC.
(b) PMC!CNC related signals
The addresses for Series 15 are from G0 to G511, for the others
are from G0 to G255.
For details of the signals, see CONNECTING MANUAL of
CNC.

74
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

3.2
ADDRESSES
BETWEEN PMC AND
MACHINE TOOL
(PMCMT)

3.2.1 (1) When the FANUC I/O Link is used


Addresses Between (a) PMC MT
PMC and Machine Tool Addresses of channel 1 are from X0 to X127.
Addresses of channel 2 are from X200 to X327. (PMCSB6/SB7
for Series 16i /160i /18i /180i /21i /210i)
(b) PMC MT
Addresses of channel 1 are from Y0 to Y127.
Addresses of channel 2 are from Y200 to Y327. (PMCSB6/SB7
for Series 16i /160i /18i /180i /21i /210i)
Up to 1024 input and 1024 output points can be assigned to any
address of each channel within the above range in byte units.
(2) When the builtin I/O card is used (except Series 15)
(a) PMC MT
Addresses are from X1000 to X1019.
(b) PMC MT
Addresses are from X1000 to X1014.
The addresses in the above range are always specified. They cannot
therefore be changed when the I/O points are assigned to them.
(3) NC signals whose addresses are fixed and that are input from the
machine tool
Be sure to assign the following signals to be input from the machine tool
to the specified addresses because the NC unit refers to the following
fixed addresses during processing.

NOTE
If both I/O Link and builtin I/O card are provided, the
address of the I/O card is valid.
(Except Series 15)

75
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3.2.1 (a) Input signals whose addresses are fixed (Series 16/Series 18)

Address
Signal Symbol When the I/O Link When the builtin
is used I/O card is used
T Signal indicating that Xaxis measurement position is reached XAE X4.0 X1004.0
system
Signal indicating that Zaxis measurement position is reached ZAE X4.1 X1004.1
Function B for directly entering the measurement value of tool +MIT1 X4.2 X1004.2
compensation in the positive X direction
Function B for directly entering the measurement value of tool MIT1 X4.3 X1004.3
compensation in the negative X direction
Function B for directly entering the measurement value of tool +MIT2 X4.4 X1004.4
compensation in the positive Z direction
Function B for directly entering the measurement value of tool MIT2 X4.5 X1004.5
compensation in the negative Z direction
M Signal indicating that Xaxis measurement position is reached XAE X4.0 X1004.0
system
Signal indicating that Yaxis measurement position is reached YAE X4.1 X1004.1
Signal indicating that Zaxis measurement position is reached ZAE X4.2 X1004.2
Common Skip signal SKIP X4.7 X1004.7
Emergency stop signal *ESP X8.4 X1008.4
Deceleration signal for 1st axis reference position return *DEC1 X9.0 X1009.0
Deceleration signal for 2nd axis reference position return *DEC2 X9.1 X1009.1
Deceleration signal for 3rd axis reference position return *DEC3 X9.2 X1009.2
Deceleration signal for 4th axis reference position return *DEC4 X9.3 X1009.3
Deceleration signal for 5th axis reference position return *DEC5 X9.4 X1009.4
Deceleration signal for 6th axis reference position return *DEC6 X9.5 X1009.5
Deceleration signal for 7th axis reference position return *DEC7 X9.6 X1009.6
Deceleration signal for 8th axis reference position return *DEC8 X9.7 X1009.7

If the NC is a TT system, the signals for tool post 2 listed in Table 3.2.1
(b) are always assigned to the following addresses.
In addition, the system does not have the signals for tool post 1, DEC5
to DEC8 (X9.4 to X9.7).

Table 3.2.1 (b) Input signals whose addresses are fixed (TT) (Series 16/Series 18)

Address
Signal Symbol When the I/O Link is When the builtin
used I/O card is used
TT Signal indicating that Xaxis measurement position is reached XAE X13.0 X1013.0
system
Signal indicating that Zaxis measurement position is reached ZAE X13.1 X1013.1
Function B for directly entering the measurement value of tool +MIT1 X13.2 X1013.2
compensation in the positive X direction
Function B for directly entering the measurement value of tool MIT1 X13.3 X1013.3
compensation in the negative X direction
Function B for directly entering the measurement value of tool +MIT2 X13.4 X1013.4
compensation in the positive Z direction
Function B for directly entering the measurement value of tool MIT2 X13.5 X1013.5
compensation in the negative Z direction
Skip signal SKIP X13.7 X1013.7
Deceleration signal for 1st axis reference position return *DEC1 X7.0 X1007.0
Deceleration signal for 2nd axis reference position return *DEC2 X7.1 X1007.1
Deceleration signal for 3rd axis reference position return *DEC3 X7.2 X1007.2
Deceleration signal for 4th axis reference position return *DEC4 X7.3 X1007.3

76
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Table 3.2.1 (c) Input signals whose addresses are fixed (Series 15)

Emergency Skip signal Measurement position reached signal


Type of I/O unit
stop address address AE1 (XAE) AE2 (ZAE)
Connection unit X6.4 X11.6 X8.3 X8.4
I/O unit X6.4 X11.6 X8.3 X8.4

3.2.2 The sequence program addresses of each module should be decided by the
machine tool builder. These decided addresses are set to the programmer
Assignment of I/O
memory by using programmer.
Module Addresses
The address information being set to the programmer is written together
with a sequence program into ROM when a sequence program is written
into ROM. No I/O address is changeable in the written stage of the
address information into ROM. These addresses are determined by the
connecting position (group number and base number) of the I/O base unit,
each module position (slot number) mounted inside the I/O base unit and
each module name.
Fig. 3.2.2 (a) and Fig. 3.2.2 (b) indicate the configuration of the I/O base
unit.
For the specifications and details of connections of the I/O interface
module, I/O module, CPU module, and other modules, see Connection
Manual of each CNC.

PMC

I/O control Group


unit I/O Unit I/O Unit
#0

AIF01A AIF01B

Base#0 Base#1

Fig. 3.2.2 (a)

77
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

PMC

I/O control Group


unit I/O Unit I/O Unit
#0

AIF01A AIF01B

Base#0 Base#1

Group
I/O Unit I/O Unit
#1

AIF01A AIF01B

Base#0 Base#1

Power Group
Mate #2
Base#0

Connection unit Group


#3
Base#0

Possible to connect max. 16 groups


Max. 2 Base/Group
Max. 10 Slot/Base

Fig. 3.2.2 (b)


(1) Group No.
Up to two I/O units can be connected using the additional I/O
interface module AIF01B, based on I/O interface AIF01A. Up to two
I/O units extended from AIF01A are called a group. When only one
interface module is not enough to accommodate the required I/O
modules, or when multiple I/O units are separately located remote
from the machine, connect the first AIF01A and the second AIF01A
with the cable. Up to 16 groups of I/O units can be connected.
(2) Base No.
In one group, there are 2 max. I/O base units. The I/O unit with the
I/O interface module IF01A is assigned to base No. 0 and another is
assigned to base No.1.
(3) Slot No.
A maximum of 5 or 10 I/O modules can be mounted on the I/O base
unit ABU05A, ABU10A, respectively. The module mounting
position on the I/O base unit is expressed with slot Nos. In each base
unit, the mounting position of the I/O interface module is assigned
to slot No. 0, and slot No. 1, 2, 3 ... are assigned in order from the left.
In the case of I/O base unit (BU10B) for 10 slots, slot No. 1, 2 follow
slot No. 8. The last slot No. 1, 2 are assigned for the next base
address. Each module can be mounted on an arbitrary slot. It is
possible to mount modules by skipping some slots.

78
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

(4) Module name


For module names, see Table 3.2.2 (a) to (c).
An actual module name begins with A. When specifying a module,
omit the first letter A from the module name.
Example) When specifying module AID16D, enter ID16D.

Table 3.2.2 (a) Input modules


Number Indica-
Input Module name Rated Rated cur-
Polarity Response time of input Terminal tion
format (Actual module name) voltage rent
points by LED
Noninsulat ID32A Not
24VDC 7.5mA Both 20 ms max. 32 Connector
ion DC input (AID32A) provided
ID32B Not
24VDC 7.5mA Both 2 ms max. 32 Connector
(AID32B) provided
Insulation ID16C
24VDC 7.5mA NEG 20 ms max. 16 Terminal board Provided
DC input (AID32C)
ID16D
24VDC 7.5mA POS 20 ms max. 16 Terminal board Provided
(AID32D)
ID32E Not
24VDC 7.5mA Both 20 ms max. 32 Connector
(AID32E) provided
ID32F Not
24VDC 7.5mA Both 2 ms max. 32 Connector
(AID32F) provided
Noninsulat IA16G 100 to 14.5mA ON : 20ms max
16 Terminal board Provided
ion DC input (AIAHG) 120VAC (AC120V) OFF : 45ms max

Polarity NEG : 0 V common (current output)


POS : 24 V common (current output)

Table 3.2.2 (b) Output modules


Number Number
Output Module name Rated Rated Indication
Polarity of of points/ Terminal Fuse
format (Actual module name) voltage current by LED
points common
Insulation OD08C 12 to 24 Terminal
2A NEG 8 8 Provided Provided
DC output (AOD08C) VDC board
OD08D Terminal
2A POS 8 8 Provided Provided
(AOD08D) board
OD16C Terminal Not
0.5A NEG 16 8 Provided
(AOD16C) board provided
OD16D Terminal Not
0.5A POS 16 8 Provided
(AOD16D) board provided
OD32C Not
0.3A NEG 32 8 Connector Not provided
(AOD32C) provided
OD32D Not
0.3A POS 32 8 Connector Not provided
(AOD32D) provided
AC output OA05E 100 to Terminal
2A 5 1 Provided Provided
(AOA05E) 240 VAC board
OA08E Terminal
1A 8 4 Provided Provided
(AOA08E) board
OA12E 100 to Terminal
0.5A 12 6 Provided Provided
(AOR12G) 120 VAC board
Relay OR08G 250 VAC/ Terminal Not
4A 8 1 Provided
output (AOR08G) 30 VDC board provided
max.
OR16G Terminal Not
2A 16 4 Provided
(AOR16G) board provided

Polarity NEG : 0 V common (current output)


POS : 24 V common (current output)

79
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Table 3.2.2 (c) Other modules

Module name Occupied


Name Specifications
(actual module name) address
FANUC CNC SYSTEM FS04A Input: 4 bytes FANUC Series 0C
FANUC Power Mate Output: 4 bytes (with FANUC I/O Link supported)
FANUC Power MateMODEL
FS08A Input: 8 bytes
A/B/C/D/E/F/H
Output: 8 bytes
OC02I Input: 16 bytes FANUC Power MateMODEL D/H
OC02O Output: 16 bytes
OC03I Input: 32 bytes
OC03O Output: 32 bytes
Analog input module AD04A Input: 8 bytes
(AAD04A)
Analog output module DA02A Output: 4 bytes
(ADA02A)
Connection unit (one piece) CN01I Input: 12 bytes
Connection unit (two pieces) CN01O Output: 8 bytes
Connection unit (one piece) CN02I Input: 24 bytes
Connection unit (two pieces) CN02O Output: 16 bytes
Operators panel connection unit I/O card E OC01I Input: 12 bytes Ordering information:
A16B22000660 (sink type)
OC01O Output: 8 bytes A16B22010730 (source type)

Operators panel connection unit I/O card D /8 Input: 8 bytes Ordering information:
A16B22000661 (sink type)
/4 Output: 4 bytes A16B22010731 (source type)

Machine operators panel interface unit OC02I Input: 16 bytes


OC02O Output: 16 bytes
OC03I Input: 32 bytes
OC03O Output: 32 bytes
I/O Link connection unit /V Input: V bytes Specify the same value (1 to 8) as the
Output: V bytes number of input or output bytes in V.
OC02I Input: 16 bytes
OC02O Output: 16 bytes
OC03I Input: 32 bytes
OC03O Input: 32 bytes
Area for the I/O Unit MODEL B #V Input: V bytes Specify 1 to 10 bytes in V.
Output: V bytes
## Input: 4 bytes Specify an area for reading information
about whether the power of each unit in the
I/O Unit MODEL B is on.
Special modules /V Input: V bytes Specify the same value (1 to 8) as the
Special modules, which are not listed in Output: V bytes number of input or output bytes in V.
Tables 3.2.2 (a) to (c)
OC02I Input: 16 bytes Used when the number of input or output
bytes is 9 to 16.
OC02O Output: 16 bytes
OC03I Input: 32 bytes Used when the number of input or output
bytes is 17 to 32.
OC03O Output: 32 bytes

80
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Module name Occupied


Name Specifications
(actual module name) address
Distribution I/O connector panel I/O CM03I (/3) Input 3 bytes Basic unit only
modules(NOTES 3, 4)
CM06I (/6) Input 6 bytes Expansion unit 1 is used.
CM09I Input 9 bytes Expansion unit 2 is used.
CM12I (OC01I) Input 12 bytes Expansion unit 3 is used.
CM13I Input 13 bytes The first MPG unit is used.
CM14I Input 14 bytes The second MPG unit is used.
CM15I Input 15 bytes The third MPG unit is used.
CM16I (OC02I) Input 16 bytes DO alarm detection is used.
CM02O (/2) Output 2 bytes Basic unit only
CM04O (/4) Output 4 bytes Expansion unit 1 is used.
CM06O (/6) Output 6 bytes Expansion unit 2 is used.
CM08O (/8) Output 8 bytes Expansion unit 3 is used.
Distribution I/O operators panel I/O CM06I (/6) Input 6 bytes
modules(NOTES 3, 4)
CM13I Input 13 bytes The first MPG unit is used.
CM14I Input 14 bytes The second MPG unit is used.
CM15I Input 15 bytes The third MPG unit is used.
CM16I (OC02I) Input 16 bytes DO alarm detection is used.
CM04O (/4) Output 4 bytes
CM08O (/8) Output 8 bytes
External I/O card A, D for Power Mate /6 Input 6 bytes
/4 Output 4 bytes
External I/O card B, E for Power Mate OC01I Input 12 bytes
OC01O Output 8 bytes

81
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 See Section 3.2.3, I/O Link connection unit assignment
method, for how to assign the I/O Link connection unit.
2 See Section 3.2.4, I/O Link MODEL B assignment
method, for how to assign the I/O Link MODEL B.
3 See Section 3.2.7, Distribution panel I/O connection panel
I/O module and distribution I/O operators panel I/O module
assignment method, for how to assign the connection
panel I/O module and operators panel I/O module.
4 If the version of the programming system (FANUC
LADDER, FANUC LADDERII) is too old to match a module
above, use the compatible module indicated in
parentheses. When a compatible module having the same
number of points is not available, use a compatible module
having a greater number of points.
5 On the PMCSB6/SB7 for Series 16i/18i/21i/160i/180i/
210i, when programming software supports the I/O Link
expansion, up to 16 groups of I/O Module can be assigned
to the I/O Link channel 2 area. To link the I/O Link channel
2 actually, the option of the I/O Link expansion is necessary.

CAUTION
For I/O Unit MODEL A, to use 3, 5, 6, or 7 bytes for
assignment, change the module name as follows.
Do not use 10241, /3, /5, /6, or /7 for the module name.
Module name
Before change After change
10241 /4
/3 /4
/5 /8
/6 /8
/7 /8

82
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

(5) How to set address to each module


The character and the mount position of each module is now decided
with the group number, base number, slot number, and module name,
so the address of each module can now be decided, corresponding
these data and the input/output addresses. After display the I/O unit
address screen as shown below on the programmers CRT, set
necessary data on the screen, Then the module address is now
assigned. The occupying DI/DO points (bytes) of each module are
stored in the programmer, so just assign the address of the head byte
of each module, and the addresses of the other bytes in the module
are automatically assigned by the programmer.
For instance, when the module ID32A is assigned address X5 as in
Fig. 3.2.2 (c), the necessary 4 bytes are automatically secured. For
details on operation, see Chapters III, IV, Programmer. The
input/output addresses of each module can be freely decided in this
method at the machine tool builder, so the address can be decided
when making the ladder diagram, as long as it does not duplicate with
the addresses of each module.

ADDRESS GROUP BASE SLOT NAME

X000
X001
X002
X003
X004
X005 0 0 5 ID32A
X006 0 0 5 ID32A
Automatical X007 0 0 5 ID32A
set X008 0 0 5 ID32A
X009

Fig. 3.2.2 (c) I/O unit address screen

NOTE
When assigning Connection unit 1, Connection unit 2 or
Connection unit for operators panel, set base number to 0
and slot number to 1.

83
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

(6) Notes when setting addresses

(a) The head bytes of the analog input module (AD04A) and analog
output module (DA02A) must be assigned to even number addresses
of input address (XVVV), and output address (YVVV) each.
When reading the A/Dconverted digital value from the input
address (XVVV) or when writing the D/Aconverting value to the
output address (YVVV), readout and writein must always be
done in word (16 bits) units.

ADDRESS GROUP BASE SLOT NAME

X000 0 0 1 ID16C
X001 0 0 1 ID16C
X002 0 0 2 ID16D
X003 0 0 2 ID16D
X004 1 0 1 IA16G
X005 1 0 1 IA16G
X006 1 0 2 IA16G
X007 1 0 2 IA16G
X008 2 0 1 ID16D
X009 2 a 0 1 ID16D

Fig. 3.2.2 (d)

3.2.3 Concept:
I/O Link Connection In conventional data transfer, when data is to be transferred between CNC
Unit Assignment A and CNC B, the I/O units indicated by (a) (figure below) must be
connected with each other. (In this case, data can be transferred using any
I/O unit.)

CNC A I/ O Unit I/ O Unit CNC B


Model A Model A

(a)
I/ O Unit
Model A
$ I/ O Unit
Model A

I/ O Unit I/ O Unit
Model A Model A

The I/O link connection unit replaces these I/O units, thus eliminating the
need to connect them with, for example, cables.

84
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

CNC A I/ O Unit I/ O Unit CNC B


Model A Model A

This portion is replaced by an I/O link


connection unit.
(a)
I/ O Unit
Model A $ I/ O Unit
Model A

I/ O Unit I/ O Unit
Model A Model A

Consequently, when the I/O link connection unit is used, the connections
become as shown below.

CNC A I/ O Unit I/ O Unit CNC B


Model A Model A

I/O Link
connection unit

I/ O Unit I/ O Unit
Model A Model A

Method of assignment: The assignment data depends on what type of I/O unit is to be replaced
with an I/O link connection unit.
Occupied
Input unit name at the time of assignment Output unit name at the time of assignment
address
1 to 8 / V (V represents a number from 1 to 8.) / V (V represents a number from 1 to 8.)
16 OC02I OC02O
32 OC03I OC03O

Setting: When a connection unit that occupies 16byte addresses is attached to the
input side in GROUP = 1, enter 1.0.1.OC02I.

NOTE
On the PMCSB6/SB7 for Series 16i/18i/21i/160i/180i/
210i, when programming software supports the I/O Link
expansion, I/O Link connection unit can be assigned to the
I/O Link channel 2 area. To link the I/O Link channel 2
actually, the option of the I/O Link expansion is necessary.

85
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.2.4 D Related hardware publications:


I/O Unit MODEL B FANUC I/O UnitMODEL B Connection and Maintenance Manual
(B62163E)
Assignment
I/O Unit MODEL Bs can be used together with a Power Mate operator
panel interface unit, connection unit, and I/O Unit MODEL As.
In this case, the I/O Unit MODEL Bs occupy one group; that is, no other
type of unit can be present in that group.
An example of connection is shown below.

I/ O LINK
MASTER

[GROUP] =0
Power Mate

[BASE] =0, [SLOT] =1


[GROUP] =1

Operators panel
interface unit

[BASE] =0, [SLOT] =1


[GROUP] =2

SLOT No. SLOT No.

I/O Unit A I/O Unit A


[GROUP] =3

[BASE] =0 [BASE] =1

I/O unit model B


interface unit
I/O unit model B I/O unit model B
DI/DO unit DI/DO unit
(Unit No.=1) (Unit No.=20)

[BASE] =0, [SLOT] =1 [BASE] =0, [SLOT] =20

I/O unit model B I/O unit model B


DI/DO unit DI/DO unit
(Unit No.=5) (Unit No.=10)

[BASE] =0, [SLOT] =5 [BASE] =0, [SLOT] =10

I/O unit model B I/O unit model B


DI/DO unit DI/DO unit
(Unit No.=30) (Unit No.=9)

[BASE] =0, [SLOT] =30 [BASE] =0, [SLOT] =9

86
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Method of assignment: Specify a group number in [GROUP]. Always specify 0 in [BASE].


Specify the unit number of an I/O unit model B in [SLOT]. But when you
assign the poweron/off intormation, specify 0 in [SLOT].
The data specified by [SLOT] and [NAME] is as follows:
[SLOT] = 0, 1, ...30:
Unit number (1 to 30) of an I/O unit model B DI/DO unit
[NAME]: Addresses occupied by an I/O unit model B
Input/output size of ([base unit] Assigned
Occupied address
+ [extended unit]) name
1 byte #1 Input/output: 1 byte
2 bytes #2 Input/output: 2 bytes
3 bytes #3 Input/output: 3 bytes
4 bytes #4 Input/output: 4 bytes
6 bytes #6 Input/output: 6 bytes
8 bytes #8 Input/output: 8 bytes
10 bytes #10 Input/output: 10 bytes
Poweron/off information ## Input: 4 bytes

Setting: When an I/O unit model B assigned unit number 10 and occupying an area
of 3 bytes is attached to the input with GROUP = 1, enter 1.0.10.#3.

NOTE
On the PMCSB6/SB7 for Series 16i/18i/21i/160i/180i/
210i, when programming software supports the I/O Link
expansion, I/O UnitMODEL B can be assigned to the I/O
Link channel 2 area. But total number of groups of channel
1 and channel 2 of I/O Unit MODEL B available at the same
time is up to 8 when I/O device is connected to channel 2.
To link the I/O Link channel 2 actually, the option of the I/O
Link expansion is necessary.

3.2.5 When a Power MateD/H or Power Mate iD/H is used as I/O Link slave,
it need to be assigned on the I/O Link master side.
Power Mate On the I/O link slave side, fixed addresses are used, so that no address
Assignment needs to be assigned. (See Table 3 for the addresses used.)
An example of connection is shown below.

I/ O LINK
MASTER

[GROUP] =0
Operators panel
interface unit

[BASE] =0, [SLOT] =1


[GROUP] =1

Power Mate

[BASE] =0, [SLOT] =1

87
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Method of assignment: Specify a group number in [GROUP].


Always specify 0 in [BASE].
Always specify 1 in [SLOT].
The data specified by [NAME] is as follows:
I/O points Input unit name at the Output unit name at the
(input/output) time of assignment time of assignment
32/32 FS04A FS04A
64/64 FS08A FS08A
128/128 OC02I OC02O
256/256 OC03I OC03O

Setting: When a Power MateD of 256/256 points is connected with group 1, input
the undermentioned assignment data.
Input side : 1.0.1.OC03I
Output side : 1.0.1.OC03O

NOTE
On the PMCSB6/SB7 for Series 16i/18i/21i/160i/180i/
210i, when programming software supports the I/O Link
expansion, Power MateD/H or Power Mate iD/H can be
assigned to the I/O Link channel 2 area. To link the I/O Link
channel 2 actually, the option of the I/O Link expansion is
necessary.

3.2.6 On the FS16iLA, the laser oscillator is connected as part of the I/O Link.
FS16iLA Assignment 3 groups (DI/DO=256/256 points) are used for the laser oscillator
interface. 13 groups, 768/768 points (X0 to X95, Y0 to Y95) of the I/O
Link channel 1 can be used for the ladder diagram. 16 groups, 1024/1024
points (X200 to X327, Y200 to Y327) of the I/O Link channel 2 can be
used for the ladder diagram. For details on the laser oscillator connection,
see the FS16i Series CONNECTION MANUAL (B63003EN), FANUC
I/O Link connection.

Connection Example

FS16iLA

I/ O LINK
MASTER

Max. 13 groups

X0 to X95
Operators panel I/O module Y0 to Y95

Max. 3 groups

Laser oscillator

88
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Method of Assignment Specify 0 to 12 in [GROUP].


For details on how to assign [BASE] and [SLOT], see 3.2.2 Assignment
of I/O Module Addresses.

CAUTION
1 Addresses X96 to X127 and Y96 to Y127 cannot be used
in ladder diagrams.
2 When addresses X96 to X127 and Y96 to Y127 are
assigned, I/O points are not linked.
3 Connect the laser group to the end of the I/O link.
4 The I/O Link restart function cannot be used.
5 The OVERRIDE mode of the forced I/O function cannot be
used.
6 PMCSB5 does not support a laser.

3.2.7 To assign connection panel I/O and operators panel I/O modules to the
Distribution I/O I/O Link, set the group number with an I/O Link serial number (use a
smaller number toward the I/O Link master CNC, like 0, 1, and 2). Also,
Connection I/O Module set the base number and slot number to 0 and 1, respectively. If a
and Distribution I/O combination of the basic module and expansion modules is used as the
Operators Panel I/O connection panel I/O module, assign all the modules in one I/O Link
Module Assignment group as one unit. Unlike the I/O Unit MODELA, it is unnecessary to
Methods specify a slot number. An assignment example is shown below.

Assignment example
Example

CNC

JD1A

72 input points (16 generalpurpose points + 56 matrix points) and


56 output points (X4 and higher, Y0 and higher)
Operators panel I/O
module MPG
A20B20020470
JD1B
JD1A
MPG

96 input points and 64 output points (X20 and higher, Y10 and higher)
Connection Expansion Expansion Expansion
panel I/O module 1 module 2 module 3
basic module
JD1B
JD1A

24 input points and 16 output points (X100 and higher, Y100 and higher)
Connection
panel I/O
basic module
JD1B
JD1A

89
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Group Base Slot Name

X004 0 0 1 CM14I

X020 1 0 1 CM12I

X100 2 0 1 CM03I

Y000 0 0 1 CM08O

Y010 1 0 1 CM08O

Y100 2 0 1 CM02O

Assignment name To assign the connection panel I/O and operators panel I/O modules for
the I/O Link, it is necessary to use programming software that supports
these modules. If the programming software does not support the
modules, use compatible names for assignment described later.

Connection panel I/O Refer to the following manuals for an explanation of how the connection
panel I/O module signals are mapped:
D FANUC Series 16i/18i Connection Manual (Hardware)
B63003EN
D FANUC Series 21i Connection Manual (Hardware) B63083EN
D FANUC Series 15i Connection Manual (Hardware) B63323EN
D FANUC Power Mate i Connection Manual (Hardware) B63173EN
The assignment that is made for different configurations (such as basic
module configuration and combination basic/expansion module
configuration) is explained below.

CAUTION
Expansion modules must be connected in ascending order
with respect to the module number (1, 2, then 3). An
expansion module number cannot be skipped.

Basic module Expansion Expansion


module 1 module 2
JD1B
JD1A

It is impossible to assign expansion module 2 without


expansion module 1, which will be installed later, as shown
above.

(1) Basic module only

24 input points and 16 output points

Basic module

JD1B
JD1A

90
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM03I and output Y = CM02O
D One manual pulse generator:
Input X = CM13I and output Y = CM02O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM02O no matter how
many manual pulse generators are used
(2) Basic module + expansion module 1

48 input points and 32 output points

Basic module Expansion


module 1
JD1B
JD1A

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM06I and output Y = CM04O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM04O no matter how
many manual pulse generators are used
(3) Basic module + expansion module 1 + expansion module 2

72 input points and 48 output points

Basic module Expansion Expansion


module 1 module 2
JD1B
JD1A

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM09I and output Y = CM06O
D One manual pulse generator:
Input X = CM13I and output Y = CM06O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM06O no matter how
many manual pulse generators are used
(4) Basic module + expansion module 1 + expansion module 2 +
expansion module 3

96 input points and 64 output points

Basic module Expansion Expansion Expansion


module 1 module 2 module 3
JD1B
JD1A

91
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM12I and output Y = CM08O
D One manual pulse generator:
Input X = CM13I and output Y = CM08O
D Two manual pulse generators:
Input X = CM14I and output Y = CM08O
D Three manual pulse generators:
Input X = CM15I and output Y = CM08O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM08O no matter how
many manual pulse generators are used

Operators panel I/O Refer to the following manuals for an explanation how the operators
module panel I/O module signals are mapped:
D FANUC Series 16i/18i Connection Manual (Hardware)
B63003EN
D FANUC Series 21i Connection Manual (Hardware) B63083EN
D FANUC Series 15i Connection Manual (Hardware) B63323EN
D FANUC Power Mate i D/H Connection Manual (Hardware)
B63173EN
(1) Operators panel I/O module
(A20B20020470 supporting matrix inputs)

16 generalpurpose input points + 56 matrix input points


56 matrix output points

Operators panel I/O


module
JD1B
JD1A

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM12I and output Y = CM08O
D One manual pulse generator:
Input X = CM13I and output Y = CM08O
D Two manual pulse generators:
Input X = CM14I and output Y = CM08O
D Three manual pulse generators:
Input X = CM15I and output Y = CM08O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM08O no matter how
many manual pulse generators are used
(2) Operators panel I/O modules
(A20B20020520 and A20B20020521)

92
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

48 input points
32 output points

Operators panel I/O


module
JD1B
JD1A

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM06I and output Y = CM04O
D One manual pulse generator:
Input X = CM13I and output Y = CM04O
D Two manual pulse generators:
Input X = CM14I and output Y = CM04O
D Three manual pulse generators:
Input X = CM15I and output Y = CM04O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM04O no matter how
many manual pulse generators are used
(3) Distribution I/O machine operators panels (A20B80010721,
A20B80010720, and A20B80010210)

8 override (and other) signal input points + 24 generalpurpose input points + 64


matrix input points
64 output matrix points

Operators panel I/O


module
JD1B
JD1A

(a) If DO alarm detection is not used


D No manual pulse generator:
Input X = CM12I and output Y = CM08O
D One manual pulse generator:
Input X = CM13I and output Y = CM08O
D Two manual pulse generators:
Input X = CM14I and output Y = CM08O
D Three manual pulse generators:
Input X = CM15I and output Y = CM08O
(b) If DO alarm detection is used
D Input X = CM16I and output Y = CM08O no matter how
many manual pulse generators are used

93
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Compatible names for If your programming unit does not support the connection I/O or
assignment operators panel I/O module, use the following compatible names for I/O
Link assignment.
Assignment name Compatible name

CM03I /3

CM06I /6

CM09I OC01I

CM12I OC01I

CM13I OC02I

CM14I OC02I

CM15I OC02I

CM16I OC02I

CM02O /2

CM04O /4

CM06O /6

CM08O /8

NOTE
On the PMCSB6/SB7 for Series 16i/18i/21i/160i/180i/
210i, when programming software supports the I/O Link
expansion, I/O Connection, I/O Module and Operators
Panel I/O Module can be assigned to the I/O Link channel
2 area. But Manual Pulse Generator can not be assigned to
channel 2 area.

94
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

3.3 In each model, the following signals (bytes) can be used as internal relays.
This area is cleared to zero when the power is turned on.
INTERNAL RELAY
ADDRESSES (R)
Model PA1 PA3

Number of 1100 1118


bytes

Model SA1 SA2 SA3/SA5

Number of
1100 1118 1118
bytes

Model SB SB2 SB3/SB5 SB4/SB6 SB7

Number of
1100 1118 1618 3200 8500
bytes

Model SC SC3 SC4

Number of
bytes 1600 1618 3200

Model NB NB2 NB6

Number of
bytes 1618 3200 3200

95
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

Address number
7 6 5 4 3 2 1 0

R0 PMCPA1 PMCSB3 PMCSB4 PMCSB7


PMCPA3 PMCSB5 PMCSB6
R1 PMCSA1 PMCSC PMCSC4
PMCSA2 PMCSC3 PMCNB2
PMCSA3 PMCNB PMCNB6
PMCSA5
PMCSB
PMCSB2

R999



R1499


R2999
.
.

R7999

R9099 PMCPA1 PMCPA3 PMCSB4 PMCSB7


PMCSA1 PMCSA2 PMCSB6
PMCSB PMCSA3 PMCSC4
PMCSC PMCSA5 PMCNB2
PMCSB2 PMCNB6
PMCSB3
R9099 PMCSB5
PMCSC3
PMCNB


R9117


R9199
.
.


R9499

96
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

3.3.1 (1) R9000 (Operation output register for the ADDB, SUBB, MULB,
Area Managed by the DIVB, and COMPB functional instructions)
System Program 7 6 5 4 3 2 1 0
R9000

The result is 0.
The result is a negative
value.
The result overflows.

(2) R9000 (Error output for the EXIN, WINDR, WINDW, MMCWR,
MMCWW, MMC3R, and MMC3W functional instructions)
7 6 5 4 3 2 1 0
R9000

The instruction ended


in error.

(3) R9002 to R9005 (Operation output registers for the DIVB functional
instruction)
The data remaining after the DIVB functional instruction is executed
is output.
(4) R9010 to R9027 (Interface area for the FNC9x functional
instruction) (PMCSC only)
The area is provided as an interface between the FNC9x functional
instruction to be executed and a desired function.
7 6 5 4 3 2 1 0

R9010 Contents of the command to


97 96 95 94 93 92 91 90 be executed
R9011 Data output when the
97 96 95 94 93 92 91 90 processing is completed
R9012

R9013 Addresses of the control data for SUB90


R9014

R9015
Addresses of the control data for SUB91

R9026
Addresses of the control data for SUB97
R9027

97
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

(5) R9100 to R9117 (Interface area for the FNC9x functional


instruction) (PMCSC3/SC4/NB/NB2 only)
The area is provided as an interface between the FNC9x functional
instruction to be executed and a desired function.
7 6 5 4 3 2 1 0
Contents of the command
R9100 97 96 95 94 93 92 91 90 to be executed

R9101 Data output when the


97 96 95 94 93 92 91 90 processing is completed
R9102

R9103 Addresses of the control data for SUB90

R9104

R9105
Addresses of the control data for SUB91

R9116
Addresses of the control data for SUB97
R9117

(6) R9091 (System timer)


4 signals can be used as system timer.
The specifications of every signal are as following.
7 6 5 4 3 2 1 0
R9091

always OFF
always ON

Cyclic signal of 200 ms


(104 ms ON, 96 ms OFF)

Cyclic signal of 1 second.


(504 ms ON, 496 ms OFF)

CAUTION
In the beginning, every signal is OFF.
The signals of R9091.0 and R9091.1 are always set at the
beginning of 1st level in every cycle.
Every pulse signal (ONOFF) includes 8 ms errors.

98
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

R9091. 5

104ms 96ms

200ms

R9091. 6

504ms 496ms

1 second

(7) RUN to STOP Transition Signal, STOP to RUN Transition Signal


and RUN Status Signal (PMCSB7)
(a) Overview
(i) RUN to STOP transition signal and STOP to RUN
transition signal
The RUN to STOP transition signal and the STOP to RUN
transition signal for LADDER program execution are to
handle these events in a LADDER program.
(ii) RUN status signal
RUN status signal is to notify the status of LADDER and
PMC C program execution to other systems or programs, such
a network board, C executor program, FOCAS1 Ethernet or
HSSB library etc.
(b) Address
7 6 5 4 3 2 1 0
R9015

R9015.0:STOP to RUN
transition signal
(LADDER program use only)

R9015.1:RUN to STOP
transition signal
(LADDER program use only)

7 6 5 4 3 2 1 0
R9091

R9091.2:RUN status signal


0 : LADDER is stopping.
1 : LADDER is running.

99
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

(c) Behavior

LADDER execution RUN


STOP

R9015.0 1
STOP to RUN signal 0

R9015.1 1
RUN to STOP signal 0

R9091.2 1
RUN status signal 0

One Scan
of LADDER

(i) STOP to RUN transition signal (R9015.0)


When a STOP to RUN event is detected on system software,
this signal will be turned on during the 1st scan of LADDER
program after LADDER started. This signal has individual
status corresponding the scan of each LADDER execution
level like R9000. This signal is completely turned on during
whole of the 1st scan in any execution level of LADDER
program.
When does a STOP to RUN event happen?
LADDER starting at every power on cycle
pressing a RUN softkey on a PMC screen
RUN commanded by FANUC LADDERIII or
LADDER EDITING PACKAGE
Referring this signal in a LADDER program, you can recognize
and handle a STOP to RUN transition event. You can program
a preprocessing for LADDER execution.

NOTE
This signal is available only in LADDER program. Dont refer
this signal on other systems or programs, such a network
board, C executor program, FOCAS1 Ethernet or HSSB
liberally etc. because this signal has individual status in
each LADDER execution.

(ii) RUN to STOP transition signal (R9015.1)


When a RUN to STOP event is detected on system software, this
signal will be turned off during the last scan of LADDER
program before LADDER stopped. This signal has individual
status corresponding the scan of each LADDER execution level
like R9000. This signal is completely turned off during the last
scan before any execution level of LADDER program stops.
When does a RUN to STOP event happen?
pressing a STOP softkey on a PMC screen
STOP commanded by FANUC LADDERIII or
LADDER EDITING PACKAGE

100
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

pressing a EDIT>IOMDL softkey on a PMC screen


pressing a EDIT>MESAGE softkey on a PMC
screen
pressing a EDIT>SYMBOL softkey on a PMC
screen
pressing a EDIT>CLEAR softkey on a PMC screen
pressing a SYSPRM softkey on a PMC screen
storing a LADDER or PMC C language program to PMC
on PMC I/O screen
storing a LADDER program to PMC using FANUC
LADDERIII or LADDER EDITING PACKAGE
Referring this signal in a LADDER program, you can recognize
and handle a RUN to STOP transition event. You can program
a postprocessing for LADDER execution (i.e. preprocessing
for stopping of LADDER execution). For example, set or reset
any appropriate signals into certain condition for the safety.

NOTE
1 This signal is available only in LADDER program. Dont refer
this signal on other systems or programs, such a network
board, C executor program, FOCAS1 Ethernet or HSSB
liberally etc. because this signal has individual status in
each LADDER execution level.
2 You can not handle this event using this signal at a power off
sequence and system alarm of CNC in which the execution
of LADDER and I/O scanning are completely shut down.

(iii) RUN status signal (R9091.2)


Referring this signal on other systems or programs, such a
network board, C executor program, FOCAS1 Ethernet or
HSSB liberally etc. you can know the status of LADDER and
PMC C language program execution.
(d) Example of use
(i) Calling a subprogram at RUN to STOP condition.
R9015.1

SUB65 Pxxxx
CALL

(ii) Forcing off a specified output signal programmed in 1st level


at RUN to STOP transition.

Input R9015.1 Output

101
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.4 This area is used as message display request. In each model, the following
number of messages can be used. Where Number of Messages =
ADDRESSES FOR Number of Bytes  8
MESSAGE This area is cleared to zero when the power is turned on. For information
SELECTION about using the message, see the subsection 5.43.
DISPLAYED ON CRT
(A) Model PA1 PA3

Number of bytes 25 25

Number of messages 200 200

Model SA1 SA2 SA3/


SA5

Number of bytes 25 25 25

Number of messages 200 200 200

SB3/ SB4/
Model SB SB2 SB7
SB5 SB6

Number of bytes 25 25 25 125 500

Number of messages 200 200 200 1000 2000

Model SC SC3 SC4

Number of bytes 25 25 125

Number of messages 200 200 1000

Model NB NB2 NB6

Number of bytes 25 125 125

Number of messages 200 1000 1000

102
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Address number

7 6 5 4 3 2 1 0

A0 PMCPA1 PMCSB4 PMCSB7


PMCPA3 PMCSB6
PMCSA1 PMCSC4
A1 PMCSA2 PMCNB2
PMCSA3 PMCNB6
PMCSA5
PMCSB
PMCSB2
PMCSB3
PMCSB5
PMCSC
PMCSC3
PMCNB

A24

A124

A249

Fig. 3.4 Address of message display reguest

103
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.5 This area is used as counters. In each model, the following number of
counters can be used. Where Number of Counters = Number of Bytes
ADDRESS OF /4
COUNTER (C) Since this area is nonvolatile, the contents of the memory do not disappear
even when the power is turned off.

Model PA1 PA3

Number of bytes 80 80

Number of counters 20 20

SA3/
Model SA1 SA2 SA5

Number of bytes 80 80 80

Number of counters 20 20 20

SB3/ SB4/ SB7


Model SB SB2
SB5 SB6

Number of bytes 80 80 80 200 400

Number of counters 20 20 20 50 100

Model SC SC3 SC4

Number of bytes 80 80 200

Number of counters 20 20 50

Model NB NB2 NB6

Number of bytes 80 200 200

Number of counters 20 50 50

104
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Address number

7 6 5 4 3 2 1 0

PMCPA1 PMCSB4 PMCSB7


C0 Preset value
PMCPA3 PMCSB6

C1 PMCSA1 PMCSC4
Counter PMCSA2 PMCNB2
No. 1 PMCSA3 PMCNB6
C2 current value
PMCSA5
C3 PMCSB
PMCSB2
PMCSB3
PMCSB5
PMCSC
PMCSC3
C76 Preset value PMCNB

C77 Counter
No. 20
C78 current value

C79

C196 Preset value

C197 Counter
No. 50
C198 current value

C199

C396 Preset value

C397 Counter
No. 100
C398 current value

C399

Fig. 3.5 Address of Counter

105
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.6 The area is used as keep relays and PMC parameters. In each model, the
following number of bytes can be used. Since this area is nonvolatile, the
ADDRESS OF KEEP contents of the memory do not disappear even when the power is turned
RELAY AND off.
NONVOLATILE
MEMORY CONTROL Model PA1 PA3
(K)
Number of bytes 20 20
Nonvolatile memory
control address K16 K16

PMC control software K17 K17


parameter to to
K19 K19

SA3/
Model SA1 SA2 SA5

Number of bytes 20 20 20
Nonvolatile memory
control address K16 K16 K16

PMC control software K17 K17 K17


parameter to to to
K19 K19 K19

SB3/ SB4/ SB7


Model SB SB2
SB5 SB6

Number of bytes 20 20 20 50 120


Nonvolatile memory
control address K16 K16 K16 K16 K16

PMC control software K17 K17 K17 K900 K900


parameter to to to to to
K19 K19 K19 K909 K919

Model SC SC3 SC4

Number of bytes 20 20 50
Nonvolatile memory
control address K16 K16 K16

PMC control software K17 K17 K900


parameter to to to
K19 K19 K909

Model NB NB2 NB6

Number of bytes 20 50 50

Nonvolatile memory K16 K16 K16


control address
PMC control software K17 K900 K900
parameter to to to
K19 K909 K909

106
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Address number

7 6 5 4 3 2 1 0
K0
PMCPA1 PMCSB4 PMCSB7
PMCPA3 PMCSB6
PMCSA1 PMCSC4
K1 PMCSA2 PMCNB2
PMCSA3 PMCNB6
PMCSA5
PMCSB
PMCSB2
PMCSB3
PMCSB5
PMCSC
PMCSC3
PMCNB

K19

K39

K99

K900
PMCSB4 PMCSB7
PMCSB6
PMCSC4
PMCNB2
PMCNB6

K909

K919

Fig. 3.6 Address of keep relay and nonvolative memory control


For the information about using Nonvolatile memory control, see the
section 6.1.
PMC control software parameter area is used by PMC control software.
For more information about PMC control software parameter, see the
section II 4.3.

107
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.7 Data table is the area of nonvolatile memory. In each model, the following
number of bytes can be used.
ADDRESS OF DATA
TABLE (D)
Model PA1 PA3

Number of bytes 1860 1860

SA3/
Model SA1 SA2
SA5
Number of bytes 1860 1860 1860

SB3/ SB4/
Model SB SB2 SB7
SB5 SB6
Number of bytes 1860 1860 3000 8000 10000

Model SC SC3 SC4

Number of bytes 3000 3000 8000

Model NB NB2 NB6

Number of bytes 3000 8000 8000

108
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Address number

7 6 5 4 3 2 1 0

D0 PMCPA1 PMCSB3 PMCSB4 PMCSB7


PMCPA3 PMCSB5 PMCSB6
D1 PMCSA1 PMCSC PMCSC4
PMCSA2 PMCSC3 PMCNB2
PMCSA3 PMCNB PMCNB6
PMCSA5
PMCSB
PMCSB2
D1859

D2999

D7999

D9999

Fig. 3.7 Address of data table

109
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.8 This area is used by TMR instruction as variable timers. In each model,
the following number of timers can be used. Where Number of timers
TIMER ADDRESSES = Number of Bytes / 2
(T) Since this area is nonvolatile, the contents of the memory do not disappear
even when the power is turned off.

Model PA1 PA3

Number of bytes 80 80

Number of timers 40 40

SA3/
Model SA1 SA2 SA5

Number of bytes 80 80 80

Number of timers 40 40 40

SB3/ SB4
Model SB SB2 SB7
SB5 SB6

Number of bytes 80 80 80 300 500

Number of timers 40 40 40 150 250

Model SC SC3 SC4

Number of bytes 80 80 300

Number of timers 40 40 150

Model NB NB2 NB6

Number of bytes 80 300 300

Number of timers 40 150 150

110
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

Address number

7 6 5 4 3 2 1 0

Timer PMCPA1 PMCSB4 PMCSB7


T0
No. 1 PMCPA3 PMCSB6
T1 PMCSA1 PMCSC4
PMCSA2 PMCNB2
Timer PMCSA3 PMCNB6
T2
No. 2 PMCSA5
T3 PMCSB
PMCSB2
PMCSB3
PMCSB5
PMCSC
PMCSC3
Timer PMCNB
T78
No. 40
T79

Timer
T298
No. 150
T299

Timer
T498
No. 250
T499

Fig. 3.8 Timer address

111
3. ADDRESS PMC SEQUENCE PROGRAM B61863E/14

3.9 Label addresses are used to specify jump destination labels (positions in
a sequence program) in the JMPB and JMPC instructions. The same label
LABEL ADDRESSES number can appear in different LBL instructions in the same sequence
(JMPB, JMPC, LBL) program as long as it is unique in the program unit (main program,
(L) subprogram). In each model, the following number of label can be used.

Model PA1 PA3

Number of labels 9999

SA3/
Model SA1 SA2 SA5

Number of labels 9999

SB3/ SB4/
Model SB SB2 SB5 SB6 SB7

Number of labels 9999 9999 9999

Model SC SC3 SC4

Number of labels 9999 9999

Model NB/ NB6


NB2
Number of labels 9999 9999

112
B61863E/14 PMC SEQUENCE PROGRAM 3. ADDRESS

3.10 Subprogram numbers are used to specify jump destination subprogram


labels in the CALL and CALLU instructions. Subprogram number must
SUBPROGRAM be unique in the entire sequence program. In each model, the following
NUMBERS (CALL, number of subprograms can be used.
CALLU, SP) (P)
Model PA1 PA3

Number of subprograms 512

SA3/
Model SA1 SA2 SA5

Number of subprograms 512

SB3/ SB3/
Model SB SB2 SB5 SB6 SB7

Number of subprograms 512 2000 2000

Model SC SC3 SC4

Number of subprograms 512 2000

Model NB NB2 NB6

Number of subprograms 512 2000 2000

113
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4 PMC BASIC INSTRUCTIONS

Designing a sequence program begins with writing a ladder diagram. The


ladder diagram is written using relay contact symbols and functional
instruction code. (These will be described later.) Logic written in the
ladder diagram is entered as a sequence program in the Programmer.
There are two sequence program entry methods. One is the entry method
with the mnemonic language (PMC instructions such as RD, AND and
OR). The other is the relay symbol method ( , and ) in which the
sequence program is entered by using the relay contact symbols and the
functional instruction symbols of the ladder diagram. When the relay
symbol method is used, the ladder diagram format can be used and
programming can be performed without understanding the PMC
instructions (basic instructions such as RD, AND and OR).
Actually, however, the sequence program entered by the relay symbol
method is also internally converted into the instruction corresponding to
the PMC instruction. When the sequence program is punched on a paper
tape and then entered to the programmer, programming must be
performed with the PMC instructions.
Also, the meanings of the functional instructions described later must be
understood fully. See Subsection 4.1 and Section 5.
On how to enter the sequence program into the programmer by using the
PMC instructions and relay symbols, see Chapter III or V.
The following should be noted first before reading the explanation on
PMC instructions.
This manual describes the entry method using mnemonic language.
(1) Signal address
Relay coils and contacts written in a ladder diagram are each given
an address, represented with an address number and a bit number.
(See Fig. 4 (a)) It is possible for the head zero. For details of address,
see Section 3.

Signal name
Relay name

A B
RO
X8.1 R12.6
C R9.0

Y20.4 Bit number

Address number

Fig. 4 (a) Address of signal

114
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

(2) Type
There are two types of PMC instructions, basic and functional.
(a) Basic instruction
Basic instructions are most often used when designing sequence
programs. They perform onebit operations, such as AND, or
OR. There are 12 types.
(b) Functional instruction
Functional instructions ease programming of machine
movements that are difficult to program with basic instructions.
Refer to Chapter V about the type of functional instruction.
(3) Storage of logical operation results
A register is provided for storing the intermediate results of a logical
operation during operation of a sequence program. This register
consists of 9 bits. (See Fig. 4 (b) ) .

Stack register (which temporarily stores the inter- The result of an operation
mediate result of an operation) currently being executed
enters here.

ST8 ST7 ST6 ST5 ST4 ST3 ST2 ST1 ST0

Fig. 4 (b)
Execution of an instruction (RD.STK or the like) to temporarily store the
intermediate results of an operation as in the above figure, shifts left and
stacks the status stored so far; conversely, execution (AND.STK or the
like) to retrieve a stacked signal shifts it right. The signal stacked last is
retrieved first.
Refer to explanations of each instruction for concrete applications and
operations.

115
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1 The type of instructions and contents of processing are listed in the Table
4.1 (a).
DETAILS OF BASIC
INSTRUCTIONS Information format 1:
This is used when writing instructions on a coding sheet, punching out
them on a paper tape or displayed on the CRT/MDI or offline programmer.
Information format 2:
This is used when inputting instructions through programmer.
This format is to simplify an input operation.
RN, for instance, means RD.NOT and represents an input operation using
both keys, R and N.
Details of each basic instruction will be given here.

Table 4.1 (a) Basic instruction and processing

Instruction
No. Format 1 Format 2 Contents of processing
(coding) (keys of FANUC LADDER)
1 RD R Reads the status of a specified signal and sets it in ST0.

2 RD.NOT RN Inverts the logical status of a specified signal, reads and sets it in ST0.

3 WRT W Outputs the results of logical operations (status of ST0) to a specified


address.

4 WRT.NOT WN Inverts the results of logical operations (status of ST0) and outputs it to a
specified address.

5 AND A Induces a logical product.

6 AND.NOT AN Inverts the status of a specified signal and induces a logical product.

7 OR O Induces a logical sum.

8 OR.NOT ON Inverts the status of a specified signal and induces a logical sum.

9 RD.STK RS Shifts the stack register left one bit, read and sets the status of a specified
signal in ST0.

10 RD.NOT.STK RNS Shifts the stack register left one bit reads the inveried logical status of a
specified signal, and sets it in ST0.

11 AND.STK AS Sets the logical product of ST0 and ST1, and shifts the stack register right
one bit.

12 OR.STK OS Sets the logical sum of ST0 and ST1, and shifts the stack register right by one
bit.

13 SET SET Calculates the logical OR of the contents of ST0 and the status of the signal
at the specified address and outputs the result to the specified address.

14 RST RST Calculates the logical AND of the inverted contents of ST0 and the specified
address and outputs the result to the address.

116
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

Basic instructions available on each models are as shown in the Table


4.1 (b).

Table 4.1 (b) Basic instruction

Model
PMC- PMC- PMC- PMC- PMC- PMC- PMC- PMC- PMC-
PA1 PA3 SA1/ SB/ SC SA3/ SB3/ SC3/ NB/
No. Instruction SA2 SB2 SA5 SB4/ SC4 NB2/
SB5/ NB6
SB6/
SB7
1 RD f f f f f f f f f

2 RD.NOT f f f f f f f f f

3 WRT f f f f f f f f f

4 WRT.NOT f f f f f f f f f

5 AND f f f f f f f f f

6 AND.NOT f f f f f f f f f

7 OR f f f f f f f f f

8 OR.NOT f f f f f f f f f

9 RD.STK f f f f f f f f f

10 RD.NOT.STK f f f f f f f f f

11 AND.STK f f f f f f f f f

12 OR.STK f f f f f f f f f

13 SET f f f f f

14 RST f f f f f

: Cannot be used f : Can be used

NOTE
SET/RST are not available on PMCSA3 for Series 20.

117
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1.1 (1) Format


RD (Address)

Bit number

Address number

(2) Reads the status (1 or 0) of a signal at a specified address and sets it


in ST0.
(3) Is used when beginning coding with contact A ( ). See the ladder
diagram of Fig. 4.1.1 and entries in the coding sheet of Table 4.1.1
for an example of using the RD instruction.
(4) The signal read by the RD instruction may be any signal entered as
the logical condition for one coil (output).

A B C
W1

X10.1 X2.0 R2.1 R200.0

D G

W2
X5.1 R5.4 R200.1
E

Y5.2
F

Y5.3

Fig. 4.1.1 Ladder diagram

Table 4.1.1 Coding for Fig. 4.1.1

Coding sheet Status of operating result


Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD X10 . 1 A A
2 AND X2 . 0 B A.B
3 AND . NOT R2 . 1 C A.B.C
4 WRT R200 . 0 W1 output A.B.C
5 RD X5 . 1 D D
6 OR . NOT Y5 . 2 E D+E
7 OR Y5 . 3 F D+E+F
8 AND R5 . 4 G (D+E+F)@G
9 WRT R200 . 1 W2 output (D+E+F)@G
10

118
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

4.1.2 (1) Format


RD. NOT (Address)

Bit number

Address number

(2) Inverts the status of a signal at a specified address and set it in ST0.
(3) Is used when beginning coding with contact B ( ). See the ladder
diagram of Fig. 4.1.2 and entries in the coding sheet of Table 4.1.2
for an example of using the RD.NOT instruction.
(4) The signal read by the RD.NOT instruction may be any contact B
entered as the logical condition of one coil.

A B C
W1

R1.1 F2.2 F3.3 R210.1

D G

W2
G5.1 R10.5
E R210.2

X4.2
F

Y10.7

Fig. 4.1.2 Ladder diagram

Table 4.1.2 Coding for Fig. 4.1.2

Coding sheet Status of operating result


Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD. NOT R1 . 1 A A
2 AND . NOT F2 . 2 B A.B
3 AND . NOT F3 . 3 C A@B@C
4 WRT R210 . 1 W1 output A@B@C
5 RD. NOT G5 . 1 D D
6 OR . NOT X4 . 2 E D+E
7 OR Y10 . 7 F D+E+F
8 AND R10 . 5 G (D+E+F)@G
9 WRT R210 . 2 W2 output (D+E+F)@G

119
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1.3 (1) Format


WRT (Address)

Bit number

Address number

(2) Outputs the results of logical operations, that is, the status of ST0 to
a specified address.
(3) The results of one logical operation can also be output to two or more
addresses. How to use the WRT instruction in this case is shown in
Fig. 4.1.3 and Table 4.1.3.

A C

W1
R220.1 G2.2 Y11.1
B
W2
X4.2
Y14.6

Fig. 4.1.3 Ladder diagram

Table 4.1.3 Coding for Fig. 4.1.3

Coding sheet Status of operating result


Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD R220 . 1 A A
2 OR X4 . 2 B A+B
3 AND G2 . 2 C (A+B)@C
4 WRT Y11 . 1 W1 output (A+B)@C
5 WRT Y14 . 6 W2 output (A+B)@C

120
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

4.1.4 (1) Format


WRT. NOT (Address)

Bit number

Address number

(2) Inverts the results of logical operations, that is, the status of ST0 and
outputs it to a specified address. Fig. 4.1.4 and Table 4.1.4 show an
example on using the WRT.NOT instruction.

A C

W1
R220.1 G2.2 Y11.1
B
W2
X4.2 Y14.6

Fig. 4.1.4 Ladder diagram

Table 4.1.4 Coding for Fig. 4.1.4


Coding sheet Status of operating result
Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD R220 . 1 A A
2 OR X4 . 2 B A+B
3 AND G2 . 2 C (A+B) C
4 WRT Y11 . 1 W1 output (A+B) C
5 WRT. NOT Y14 . 6 W2 output (A+B) C

121
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1.5 (1) Format


AND (Address)

Bit number

Address number

(2) Induces a logical product.


(3) See Fig. 4.1.1 and Table 4.1.1 for an example of using the AND
instruction.

4.1.6 (1) Format


AND. NOT (Address)

Bit number

Address number

(2) Inverts the status of a signal at a specified address and induces a


logical product.
(3) See Fig. 4.1.1 and Table 4.1.1 for an example of using the AND.NOT
instruction.

4.1.7 (1) Format


OR (Address)

Bit number

Address number

(2) Induces a logical sum.


(3) See Fig. 4.1.1 and Table 4.1.1 for an example of using the OR
instruction.

4.1.8 (1) Format


OR. NOT (Address)

Bit number

Address number

(2) Inverts the status of a signal at a specified address and induces a


logical sum.
(3) See Fig. 4.1.1 and Table 4.1.1 for an example of using the OR.NOT
instruction.

122
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

4.1.9 (1) Format


RD. STK (Address)

Bit number

Address number

(2) Stacks the intermediate results of a logical operations. After shifting


the stack register left one bit, sets a signal at a specified address to
ST0.
(3) Is used when the signal to be specified is contact A ( ).
(4) See Fig. 4.1.9 and Table 4.1.9 for an example of using the RD.STK
instruction.

A B
W1
X1.1 Y1.2 Y15.0
C D

X1.3 Y1.4
E F

R2.1 R3.5

Fig. 4.1.9 Ladder diagram

Table 4.1.9 Coding for Fig. 4.1.9

Coding sheet Status of operating result


Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD X1 . 1 A A
2 AND Y1 . 2 B A@B
3 RD. STK X1 . 3 C A@B C
4 AND Y1 . 4 D A@B C@D
5 OR. STK A@B+C@D
6 RD. STK R2 . 1 E A@B+C@D E
7 AND R3 . 5 F A@B+C@D E@F
8 OR.STK A@B+C@D+E@F
9 WRT Y15 . 0 W1 output A@B+C@D+E@F
10

123
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1.10 (1) Format


RD. NOT. STK (Address)

Bit number

Address number

(2) Stacks the intermediate results of a logical operations. Shifts the


stack register left one bit, inverts the status of a signal at a specified
address and sets it in ST0.
(3) Is used when the signal to be specified is contact B ( ).
(4) See Fig. 4.1.10 and Table 4.1.10 for an example of using the
RD.NOT.STK instruction.

A B E F
W1
X1.0 X1.1 Y1.2 Y1.3 Y15.7
C D G H

R1.4 R1.5 X1.6 Y1.7

Fig. 4.1.10 Ladder diagram

Table 4.1.10 Coding for Fig. 4.1.10


Coding sheet Status of operating result
Step Address
Instruction Bit No. Remarks ST2 ST1 ST0
Number No.
1 RD X1 . 0 A A
2 AND. NOT X1 . 1 B A@B
3 RD.NOT.STK R1 . 4 C A@B C
4 AND. NOT R1 . 5 D A@B C@D
5 OR. STK A@B+C@D
6 RD. STK Y1 . 2 E A@B+C@D E
7 AND Y1 . 3 F A@B+C@D E@F
8 RD.STK X1 . 6 G A@B+C@D E@F G
9 AND. NOT Y1 . 7 H A@B+C@D E@F G@H
10 OR. STK A@B+C@D E@F+G@H
11 AND. STK (A@B+C@D)@(E@F+G@H)
12 WRT Y15 . 7 W1 output (A@B+C@D)@(E@F+G@H)
13
14

124
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

4.1.11 (1) Format


AND. STK (Address)

Bit number

Address number

(2) Induces a logical product from the operation results in ST0 and ST1,
sets the result in ST1, and shifts the stack register right one bit.
(3) See Fig. 4.1.10 and Table 4.1.10 for an example of using the
AND.STK instruction.

4.1.12 (1) Format


OR. STK (Address)

Bit number

Address number

(2) Induces a logical sum from the operation results in ST0 and in ST1,
sets the result in ST1, and shifts the stack register right one bit.
(3) See Fig. 4.1.9 and Table 4.1.9 or Fig. 4.1.10 and Table 4.1.10 for
examples of using the OR.STK instruction.

NOTE
In Table 4.1.9 putting OR.STK at step 5 between steps 7
and 8 brings about the same result. But it is recommended
to code as shown in Table 4.1.9, because coding OR.STK
or AND.STK in succession is prone to cause an error.

125
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1.13 (1) Format


SET (Address)

Bit No.

Address No.

(2) Logical sum of the logical operation result ST0 with the content of
the specified address is outputted to the same address.
(3) Refer to the figure below for an example of using the SET instruction.

A C
(S)
R0.0 Y0.0

X0.0

Fig. 4.1.13 Ladder diagram

Table 4.1.13 Coding for Fig. 4.1.13


Coding sheet Status of operating result
Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD R0 . 0 A A C
2 OR X0 . 0 B A+B C
Y0.0
3 SET Y0 . 0 (A+B) +C
output

126
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

(4) Remarks
The use of the PMCPA3, SA2, SA3, SB2, SB3, and SC3 is
restricted as follows:
(a) Restriction of using
Do not use SET/RST like the following example 1, use them
alone like the following example 2.

R0.0 Y0.0 R0.0 Y0.0

(S) (S)

X0.0 Y0.1 X0.0

f
R0.0 Y0.1
D
D f
D
D
D X0.0
D
D
D

END2 END2

Example 1 Example 2

D The relation between COM and COME.


The operation of SET/RST in the section of COM/COME is as
follows.
COM condition ON (ACT=1) : It operates usually.
COM condition OFF (ACT=0) : SET does not operate.

127
4. PMC BASIC INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

4.1.14 (1) Format


RST (Address)

Bit No.

Address No.

(2) Logical product of inverted logical operation result ST0 with the
content of the specified address is outputted to the same address.
(3) Refer to the figure below for an example of using the RST
instruction.

A C

(R)
R0.0 Y0.0

X0.0

Fig. 4.1.14 Ladder diagram

Table 4.1.14 Coding for Fig. 4.1.14


Coding sheet Status of operating result
Step
Instruction Address No. Bit No. Remarks ST2 ST1 ST0
Number
1 RD R0 . 0 A A C
2 OR X0 . 0 B A+B C
Y0.0
3 SET Y0 . 0 (A+B) +C
output

128
B61863E/14 PMC SEQUENCE PROGRAM 4. PMC BASIC INSTRUCTIONS

(4) Remarks
The use of the PMCPA3, SA2, SA3, SB2, SB3, and SC3 is
restricted as follows:
(a) Restriction of using
Do not use SET/RST like the following example 1, use them
alone like the following example 2.
R0.0 Y0.0 R0.0 Y0.0

(S) (S)

X0.0 Y0.1 X0.0

f
.
R0.0 Y0.1
.
f
.
X0.0
. .

. .

END2 END2

Example 1 Example 2

D The relation between COM and COME.


The operation of SET/RST in the section of COM/COME is as
follows.
COM condition ON (ACT=1) : It operates usually.
COM condition OFF (ACT=0) : RST does not operate.

129
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5 FUNCTIONAL INSTRUCTIONS

In preparing a sequence program, some functions such as the function for


controlling rotation via the shorter path, are difficult to program with
basic instructions, which perform only onebit logical operations.
Therefore, functional instructions are available to facilitate
programming. See Table 5 (a).
Table 5 (a) Types and processing of functional instructions (1)

Instruction Model
Format 2 Processing
Format 1 Format 3 PMC PMC
(paper tape
(Ladder) (program input) PA1 PA3
punch program)
END1 SUB1 S1 End of a firstlevel ladder program f f

END2 SUB2 S2 End of a secondlevel ladder program f f

END3 SUB48 S48 End of a thirdlevel ladder program

TMR TMR S3 or TMR Timer processing f f

TMRB SUB24 S24 Fixed timer processing f f

TMRC SUB54 S54 Timer processing f f

DEC DEC S4 or DEC Decoding f f

DECB SUB25 S25 Binary decoding f f

CTR SUB5 S5 Counter processing f f

CTRC SUB55 S55 Counter processing f f

ROT SUB6 S6 Rotation control f f

ROTB SUB26 S26 Binary rotation control f f

COD SUB7 S7 Code conversion f f

CODB SUB27 S27 Binary code conversion f f

MOVE SUB8 S8 Data transfer after logical AND f f

MOVOR SUB28 S28 Data transfer after logical OR f f

MOVB SUB43 S43 Transfer of 1 byte f

MOVW SUB44 S44 Transfer of 2 bytes f

MOVN SUB45 S45 Transfer of an arbitrary number of bytes f

COM SUB9 S9 Common line control f f

: Cannot be used f : Can be used

130
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and processing of functional instructions (2)

Instruction Model
Format 2 Processing
Format 1 Format 3 PMC PMC
(paper tape
(Ladder) (program input) PA1 PA3
punch program)
COME SUB29 S29 End of common line control f f

JMP SUB10 S10 Jump f f

JMPE SUB30 S30 End of a jump f f

JMPB SUB68 S68 Label jump 1 f

JMPC SUB73 S73 Label jump 2 f

LBL SUB69 S69 Label f

PARI SUB11 S11 Parity check f f

DCNV SUB14 S14 Data conversion f f

DCNVB SUB31 S31 Extended data conversion f f

COMP SUB15 S15 Comparison f f

COMPB SUB32 S32 Binary comparison f f

COIN SUB16 S16 Coincidence check f f

SFT SUB33 S33 Shift register f f

DSCH SUB17 S17 Data search f f

DSCHB SUB34 S34 Binary data search f f

XMOV SUB18 S18 Indexed data transfer f f

XMOVB SUB35 S35 Binary indexed data transfer f f

ADD SUB19 S19 Addition f f

ADDB SUB36 S36 Binary addition f f

SUB SUB20 S20 Subtraction f f

SUBB SUB37 S37 Binary subtraction f f

MUL SUB21 S21 Multiplication f f

MULB SUB38 S38 Binary multiplication f f

DIV SUB22 S22 Division f f

DIVB SUB39 S39 Binary division f f

NUME SUB23 S23 Constant definition f f

NUMEB SUB40 S40 Binary constant definition f f

DISP SUB49 S49 Message display

DISPB SUB41 S41 Extended message display f f

EXIN SUB42 S42 External data input f f

WINDR SUB51 S51 Window data read f f

WINDW SUB52 S52 Window data write f f

: Cannot be used f : Can be used

131
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and processing of functional instructions (3)

Instruction Model
Format 2 Processing
Format 1 Format 3 PMC PMC
(paper tape
(Ladder) (program input) PA1 PA3
punch program)
PSGNL SUB50 S50 Position signal output f f

PSGN2 SUB63 S63 Position signal output 2 f f

DIFU SUB57 S57 Rising edge detection f

DIFD SUB58 S58 Falling edge detection f

EOR SUB59 S59 Exclusive OR f

AND SUB60 S60 Logical AND f

OR SUB61 S61 Logical OR f

NOT SUB62 S62 Logical NOT f

END SUB64 S64 End of a subprogram f

CALL SUB65 S65 Conditional subprogram call f

CALLU SUB66 S66 Unconditional subprogram call f

SP SUB71 S71 Subprogram f

SPE SUB72 S72 End of a subprogram f

AXCTL SUB53 S53 PMC axes control f f

NOP SUB70 S70 No operation n

: Cannot be used f : Can be used n : Can be used (with some restrictions)

132
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and processing of functional instructions (4)

Model
Instruc- SUB
Processing PMC PMC PMC PMC PMC PMC PMC PMC
PMC
PMC
tion number NB/
SA1 SA2 SA3 SB SB2 SB3 SC SC3 NB6
NB2

END1 1 End of a firstlevel ladder program f f f f f f f f f f

END2 2 End of a secondlevel ladder program f f f f f f f f f f

END3 48 End of a thirdlevel ladder program f f f f

TMR 3 Timer processing f f f f f f f f f f

TMRB 24 Fixed timer processing f f f f f f f f f f

TMRC 54 Timer processing f f f f f f f f f f

DEC 4 Decoding f f f f f f f f f f

DECB 25 Binary decoding f f f f f f f f f f

CTR 5 Counter processing f f f f f f f f f f

CTRC 55 Counter processing f f f f f f f f f f

ROT 6 Rotation control f f f f f f f f f f

ROTB 26 Binary rotation control f f f f f f f f f f

COD 7 Code conversion f f f f f f f f f f

CODB 27 Binary code conversion f f f f f f f f f f

MOVE 8 Data transfer after Logical AND f f f f f f f f f f

MOVOR 28 Data transfer after logical OR f f f f f f f f f f

MOVB 43 Transfer of 1 byte f f f f f

MOVW 44 Transfer of 2 bytes f f f f f

MOVN 45 Transfer of an arbitrary number of bytes f f f f f

COM 9 Common line control f f f f f f f f f f

COME 29 End of common line control f f f f f f f f f f

JMP 10 Jump f f f f f f f f f f

JMPE 30 End of a jump f f f f f f f f f f

JMPB 68 Label jump 1 f f f f f

JMPC 73 Label jump 2 f f f f f

LBL 69 Label f f f f f

PARI 11 Parity check f f f f f f f f f f

DCNV 14 Data conversion f f f f f f f f f f

DCNVB 31 Binary data conversion f f f f f f f f f f

COMP 15 Comparison f f f f f f f f f f

COMPB 32 Binary comparison f f f f f f f f f f

COIN 16 Coincidence check f f f f f f f f f f

SFT 33 Shift register f f f f f f f f f f

DSCH 17 Data search f f f f f f f f f f

DSCHB 34 Binary data search f f f f f f f f f f

: Cannot be used f : Can be used

133
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and processing of functional instructions (5)

Model
Instruc- SUB
Processing PMC PMC PMC PMC PMC PMC PMC PMC
PMC
PMC
tion number NB/
SA1 SA2 SA3 SB SB2 SB3 SC SC3 NB6
NB2

XMOV 18 Indexed data transfer f f f f f f f f f f

XMOVB 35 Binary indexed data transfer f f f f f f f f f f

ADD 19 Addition f f f f f f f f f f

ADDB 36 Binary addition f f f f f f f f f f

SUB 20 Subtraction f f f f f f f f f f

SUBB 37 Binary subtraction f f f f f f f f f f

MUL 21 Multiplication f f f f f f f f f f

MULB 38 Binary multiplication f f f f f f f f f f

DIV 22 Division f f f f f f f f f f

DIVB 39 Binary division f f f f f f f f f f

NUME 23 Constant definition f f f f f f f f f f

NUMEB 40 Binary constant definition f f f f f f f f f f

DISP 49 Message display f f f f f

DISPB 41 Extended message display f f f f f f f f f f

EXIN 42 External data input f f f f f f f f f f

SPCNT 46 Spindle control f f

WINDR 51 NC window data read f f f f f f f f f f

WINDW 52 NC window data write f f f f f f f f f f

FNC9X 9X Arbitrary functional instruction (X = 0 to 7) f f

MMC3R 88 MMC3 window data read f f f f f f f f f

MMC3W 89 MMC3 window data write f f f f f f f f f

MMCWR 98 MMC window data read f f f f f f f f f f

MMCWW 99 MMC window data write f f f f f f f f f f

DIFU 57 Rising edge detection f f f f f

DIFD 58 Falling edge detection f f f f f

EOR 59 Exclusive OR f f f f f

AND 60 Logical AND f f f f f

OR 61 Logical OR f f f f f

NOT 62 Logical NOT f f f f f

END 64 End of a subprogram f f f f f

CALL 65 Conditional subprogram call f f f f f

CALLU 66 Unconditional subprogram call f f f f f

SP 71 Subprogram f f f f f

SPE 72 End of a subprogram f f f f f

134
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Model
Instruc- SUB
Processing PMC PMC PMC PMC PMC PMC PMC PMC
PMC
PMC
tion number NB/
SA1 SA2 SA3 SB SB2 SB3 SC SC3 NB6
NB2

AXCTL 53 PMC axes control f f f f f f f f

NOP 70 No operation n f

: Cannot be used f : Can be used n : Can be used (with some restrictions)

135
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and processing of functional instructions (6)


Model
SUB Series 16/18-MODEL Series 18-
Name Processing Series 16/18-MODEL B
number B/C MODEL B
PMC-SB3 PMC-SB4 PMC-SC3 PMC-SC4 PMC-SA1
END1 1 First level program end f f f f f
END2 2 Second level program end f f f f f
END3 48 Third level program end f f
TMR 3 Timer processing f f f f f
TMRB 24 Fixed timer processing f f f f f
TMRC 54 Timer processing f f f f f
DEC 4 Decoding f f f f f
DECB 25 Binary decoding f f f f f
CTR 5 Counter processing f f f f f
CTRC 55 Counter processing f f f f f
ROT 6 Rotation control f f f f f
ROTB 26 Binary rotation control f f f f f
COD 7 Code conversion f f f f f
CODB 27 Binary code conversion f f f f f
MOVE 8 ANDed data transfer f f f f f
MOVOR 28 ORed data transfer f f f f f
MOVB 43 Byte data transfer f f f f
MOVW 44 Word data transfer f f f f
MOVN 45 Block data transfer f f f f
COM 9 Common line control f f f f f
COME 29 Common line control end f f f f f
JMP 10 Jump f f f f f
JMPE 30 Jump end f f f f f
JMPB 68 Label jump 1 f f f f
JMPC 73 Label jump 2 f f f f
LBL 69 Label f f f f
PARI 11 Parity check f f f f f
DCNV 14 Data conversion f f f f f
DCNVB 31 Extended data conversion f f f f f
COMP 15 Comparison f f f f f
COMPB 32 Binary comparison f f f f f
COIN 16 Coincidence check f f f f f
SFT 33 Shift register f f f f f
DSCH 17 Data search f f f f f
DSCHB 34 Binary data search f f f f f
XMOV 18 Indexed data transfer f f f f f
XMOVB 35 Binary indexed data transfer f f f f f
ADD 19 Addition f f f f f
: Cannot be used f : Can be used

136
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and processing of functional instructions (7)


Model
SUB Series 16/18-MODEL Series 18-
Name Processing Series 16/18-MODEL B
number B/C MODEL B
PMC-SB3 PMC-SB4 PMC-SC3 PMC-SC4 PMC-SA1
ADDB 36 Binary Addition f f f f f
SUB 20 Subtraction f f f f f
SUBB 37 Binary subtraction f f f f f
MUL 21 Multiplication f f f f f
MULB 38 Binary multiplication f f f f f
DIV 22 Division f f f f f
DIVB 39 Binary division f f f f f
NUME 23 Definition of constant f f f f f
NUMEB 40 Definition of binary constant f f f f f
DISP 49 Message display n n n n
DISPB 41 Extended message display f f f f f
EXIN 42 External data input f f f f f
AXCTL 53 PMC axis control f f f f f
WINDR 51 Window data read f f f f f
WINDW 52 Window data write f f f f f
FNC9X 9X Arbitrary functional ins. f f
MMC3R 88 MMC3 window data read f f f f f
MMC3W 89 MMC3 window data write f f f f f
MMCWR 98 MMC2 window data read f f f f f
MMCWW 99 MMC2 window data write f f f f f
DIFU 57 Rising edge detection f f f f
DIFD 58 Falling edge detection f f f f
EOR 59 Exclusive OR f f f f
AND 60 Logical production f f f f
OR 61 Logical Add f f f f
NOT 62 Logical Negation f f f f
END 64 End of subprograms f f f f
CALL 65 Conditional subprogram call f f f f
CALLU 66 Unconditional subprogram call f f f f
SP 71 Subprogram f f f f
SPE 72 End of a subprogram f f f f
NOP 70 No operation n n n

: Cannot be used f : Can be used n : Can be used (with some restrictions)

CAUTION
On the PMCSB3/SB4/SC3/SC4, DISP is provided only for the compatibility with Series 16/18 MODEL
A. On the Series 16/18 MODEL B, it is recommended to use DISPB instead of DISP because some
extended functions such as high speed display and display of double sized character are available only
with DISPB. On the Series 16/18 MODEL B, if both DISP and DISPB are used in the same sequence
program, double sized character can not be displayed by DISPB.

137
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and processing of functional instructions (8)


Model
SUB
Name Processing Series 16-MODEL C/Series 18-MODEL C
number
PMC-SB5 PMC-SB6
END1 1 First level program end f f
END2 2 Second level program end f f
END3 48 Third level program end
TMR 3 Timer processing f f
TMRB 24 Fixed timer processing f f
TMRC 54 Timer processing f f
DEC 4 Decoding f f
DECB 25 Binary decoding f f
CTR 5 Counter processing f f
CTRC 55 Counter processing f f
ROT 6 Rotation control f f
ROTB 26 Binary rotation control f f
COD 7 Code conversion f f
CODB 27 Binary code conversion f f
MOVE 8 ANDed data transfer f f
MOVOR 28 ORed data transfer f f
MOVB 43 Byte data transfer f f
MOVW 44 Word data transfer f f
MOVN 45 Block data transfer f f
COM 9 Common line control f f
COME 29 Common line control end f f
JMP 10 Jump f f
JMPE 30 Jump end f f
JMPB 68 Label jump 1 f f
JMPC 73 Label jump 2 f f
LBL 69 Label f f
PARI 11 Parity check f f
DCNV 14 Data conversion f f
DCNVB 31 Extended data conversion f f
COMP 15 Comparison f f
COMPB 32 Binary comparison f f
COIN 16 Coincidence check f f
SFT 33 Shift register f f
DSCH 17 Data search f f
DSCHB 34 Binary data search f f
XMOV 18 Indexed data transfer f f
XMOVB 35 Binary indexed data transfer f f
ADD 19 Addition f f
: Cannot be used f : Can be used

138
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and processing of functional instructions (9)


Model
SUB
Name Processing Series 16-MODEL C/Series 18-MODEL C
number
PMC-SB5 PMC-SB6
ADDB 36 Binary Addition f f
SUB 20 Subtraction f f
SUBB 37 Binary subtraction f f
MUL 21 Multiplication f f
MULB 38 Binary multiplication f f
DIV 22 Division f f
DIVB 39 Binary division f f
NUME 23 Definition of constant f f
NUMEB 40 Definition of binary constant f f
DISP 49 Message display (Caution) n n
DISPB 41 Extended message display f f
EXIN 42 External data input f f
AXCTL 53 PMC axis control f f
WINDR 51 Window data read f f
WINDW 52 Window data write f f
FNC9X 9X Arbitrary functional ins.
MMC3R 88 MMC3 window data read f f
MMC3W 89 MMC3 window data write f f
MMCWR 98 MMC2 window data read f f
MMCWW 99 MMC2 window data write f f
DIFU 57 Rising edge detection f f
DIFD 58 Falling edge detection f f
EOR 59 Exclusive OR f f
AND 60 Logical production f f
OR 61 Logical Add f f
NOT 62 Logical Negation f f
END 64 End of subprograms f f
CALL 65 Conditional subprogram call f f
CALLU 66 Unconditional subprogram call f f
SP 71 Subprogram f f
SPE 72 End of a subprogram f f
NOP 70 No operation n n
: Cannot be used f : Can be used n : Can be used (with some restrictions)

CAUTION
On the PMCSB5/SB6, DISP is provided only for the compatibility with Series 16 MODEL A/B. On the
Series 16/18 MODEL C, it is recommended to use DISPB instead of DISP because some extended
functions such as high speed display and display of double sized character are available only with DISPB.
On the Series 16/18 MODEL C, if both DISP and DISPB are used in the same sequence program, double
sized character can not be displayed by DISPB.

139
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and processing of functional instructions (10)


Model
SUB Series 21-MODEL B
Name Processing
number Series 0i-MODEL A
PMC-SA1 PMC-SA3
END1 1 First level program end f f
END2 2 Second level program end f f
END3 48 Third level program end
TMR 3 Timer processing f f
TMRB 24 Fixed timer processing f f
TMRC 54 Timer processing f f
DEC 4 Decoding f f
DECB 25 Binary decoding f f
CTR 5 Counter processing f f
CTRC 55 Counter processing f f
ROT 6 Rotation control f f
ROTB 26 Binary rotation control f f
COD 7 Code conversion f f
CODB 27 Binary code conversion f f
MOVE 8 ANDed data transfer f f
MOVOR 28 ORed data transfer f f
MOVB 43 Byte data transfer f
MOVW 44 Word data transfer f
MOVN 45 Block data transfer f
COM 9 Common line control f f
COME 29 Common line control end f f
JMP 10 Jump f f
JMPE 30 Jump end f f
JMPB 68 Label jump 1 f
JMPC 73 Label jump 2 f
LBL 69 Label f
PARI 11 Parity check f f
DCNV 14 Data conversion f f
DCNVB 31 Extended data conversion f f
COMP 15 Comparison f f
COMPB 32 Binary comparison f f
COIN 16 Coincidence check f f
SFT 33 Shift register f f
DSCH 17 Data search f f
DSCHB 34 Binary data search f f
XMOV 18 Indexed data transfer f f
XMOVB 35 Binary indexed data transfer f f
ADD 19 Addition f f
: Cannot be used f : Can be used

140
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and processing of functional instructions (11)


Model
SUB Series 21-MODEL B
Name Processing
number Series 0i-MODEL A
PMC-SA1 PMC-SA3
ADDB 36 Binary Addition f f
SUB 20 Subtraction f f
SUBB 37 Binary subtraction f f
MUL 21 Multiplication f f
MULB 38 Binary multiplication f f
DIV 22 Division f f
DIVB 39 Binary division f f
NUME 23 Definition of constant f f
NUMEB 40 Definition of binary constant f f
DISP 49 Message display
DISPB 41 Extended message display f f
EXIN 42 External data input f f
AXCTL 53 PMC axis control f f
WINDR 51 Window data read f f
WINDW 52 Window data write f f
FNC9X 9X Arbitrary functional ins.
MMC3R 88 MMC3 window data read f f
MMC3W 89 MMC3 window data write f f
MMCWR 98 MMC2 window data read f f
MMCWW 99 MMC2 window data write f f
DIFU 57 Rising edge detection f
DIFD 58 Falling edge detection f
EOR 59 Exclusive OR f
AND 60 Logical production f
OR 61 Logical Add f
NOT 62 Logical Negation f
END 64 End of subprograms f
CALL 65 Conditional subprogram call f
CALLU 66 Unconditional subprogram call f
SP 71 Subprogram f
SPE 72 End of a subprogram f
NOP 70 No operation
: Cannot be used f : Can be used

141
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and Processing of Functional Instructions (6) Part 1

Model
SUB
Name Processing Series 16i MODEL A/Series 18i MODEL A
number
PMCSB5 PMCSB6
END1 1 First level program end f f
END2 2 Second level program end f f
END3 48 Third level program end
TMR 3 Timer processing f f
TMRB 24 Fixed timer processing f f
TMRC 54 Timer processing f f
DEC 4 Decoding f f
DECB 25 Binary decoding f f
CTR 5 Counter processing f f
CTRC 55 Counter processing f f
ROT 6 Rotation control f f
ROTB 26 Binary rotation control f f
COD 7 Code conversion f f
CODB 27 Binary code conversion f f
MOVE 8 ANDed data transfer f f
MOVOR 28 ORed data transfer f f
MOVB 43 Transfer of one byte f f
MOVW 44 Transfer of two bytes f f
MOVN 45 Transfer of arbitrary bytes f f
COM 9 Common line control f f
COME 29 Common line control end f f
JMP 10 Jump f f
JMPE 30 Jump end f f
JMPB 68 Label jump 1 f f
JMPC 73 Label jump 2 f f
LBL 69 Label specification f f
PARI 11 Parity check f f
DCNV 14 Data conversion f f
DCNVB 31 Binary data conversion f f
COMP 15 Comparison f f
COMPB 32 Binary comparison f f
COIN 16 Coincidence check f f
SFT 33 Shift register f f
DSCH 17 Data search f f
DSCHB 34 Binary data search f f
XMOV 18 Indexed data transfer f f
XMOVB 35 Binary indexed data transfer f f
ADD 19 BCD addition f f

: Cannot be used f : Can be used

142
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and Processing of Functional Instructions (6) Part 2

Model
SUB
Name Processing Series 16i MODEL A/Series 18i MODEL A
number
PMCSB5 PMCSB6
ADDB 36 Binary addition f f
SUB 20 BCD subtraction f f
SUBB 37 Binary subtraction f f
MUL 21 BCD multiplication f f
MULB 38 Binary multiplication f f
DIV 22 BCD division f f
DIVB 39 Binary division f f
NUME 23 Definition of constant f f
NUMEB 40 Definition of binary constant f f
DISP 49 Message display (Caution) n n
DISPB 41 Extended message display f f
EXIN 42 External data input f f
AXCTL 53 PMC axis control f f
WINDR 51 Window data read f f
WINDW 52 Window data write f f
FNC9X 9X Arbitrary functional instruction
MMC3R 88 MMC3 window data read
MMC3W 89 MMC3 window data write
MMCWR 98 MMC2 window data read f f
MMCWW 99 MMC2 window data write f f
DIFU 57 Rising edge detection f f
DIFD 58 Falling edge detection f f
EOR 59 Exclusive OR f f
AND 60 Logical product f f
OR 61 Logical add f f
NOT 62 Logical negation f f
END 64 End of subprograms f f
CALL 65 Conditional subprogram call f f
CALLU 66 Unconditional subprogram call f f
SP 71 Subprogram f f
SPE 72 End of a subprogram f f
NOP 70 No operation f f

: Cannot be used f : Can be used n : Can be used (with some restrictions)

143
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

CAUTION
With PMCSB5/SB6 of the Series 16i/18i MODEL A, the DISP instruction can be used only to ensure
compatibility with the Series 16 MODEL A/B.
With the Series 16i/18i MODEL A, FANUC recommends the use of the DISPB instruction that provides
extended functions such as highspeed display and kanji character display.
With the Series 16i/18i MODEL A, if both the DISP instruction and DISPB instruction are used in the same
sequence program, the kanji display function of the DISPB instruction cannot be used.

144
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and Processing of Functional Instructions (7) Part 1

Model
SUB
Name Processing Series 21i MODEL A
number
PMCSA1 PMCSA5
END1 1 First level program end f f
END2 2 Second level program end f f
END3 48 Third level program end
TMR 3 Timer processing f f
TMRB 24 Fixed timer processing f f
TMRC 54 Timer processing f f
DEC 4 Decoding f f
DECB 25 Binary decoding f f
CTR 5 Counter processing f f
CTRC 55 Counter processing f f
ROT 6 Rotation control f f
ROTB 26 Binary rotation control f f
COD 7 Code conversion f f
CODB 27 Binary code conversion f f
MOVE 8 ANDed data transfer f f
MOVOR 28 ORed data transfer f f
MOVB 43 Transfer of one byte f
MOVW 44 Transfer of two bytes f
MOVN 45 Transfer of arbitrary bytes f
COM 9 Common line control f f
COME 29 Common line control end f f
JMP 10 Jump f f
JMPE 30 Jump end f f
JMPB 68 Label jump 1 f
JMPC 73 Label jump 2 f
LBL 69 Label specification f
PARI 11 Parity check f f
DCNV 14 Data conversion f f
DCNVB 31 Binary data conversion f f
COMP 15 Comparison f f
COMPB 32 Binary comparison f f
COIN 16 Coincidence check f f
SFT 33 Shift register f f
DSCH 17 Data search f f
DSCHB 34 Binary data search f f
XMOV 18 Indexed data transfer f f
XMOVB 35 Binary indexed data transfer f f
ADD 19 BCD addition f f

: Cannot be used f : Can be used

145
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and Processing of Functional Instructions (7) Part 2

Model
SUB
Name Processing Series 21i MODEL A
number
PMCSA1 PMCSA5
ADDB 36 Binary addition f f
SUB 20 BCD subtraction f f
SUBB 37 Binary subtraction f f

MUL 21 BCD multiplication f f


MULB 38 Binary multiplication f f

DIV 22 BCD division f f


DIVB 39 Binary division f f

NUME 23 Definition of constant f f


NUMEB 40 Definition of binary constant f f

DISP 49 Message display


DISPB 41 Extended message display f f
EXIN 42 External data input f f

AXCTL 53 PMC axis control f f


WINDR 51 Window data read f f

WINDW 52 Window data write f f


FNC9X 9X Arbitrary functional instruction

MMC3R 88 MMC3 window data read


MMC3W 89 MMC3 window data write

MMCWR 98 MMC2 window data read f f


MMCWW 99 MMC2 window data write f f
DIFU 57 Rising edge detection f

DIFD 58 Falling edge detection f


EOR 59 Exclusive OR f

AND 60 Logical product f


OR 61 Logical add f

NOT 62 Logical negation f


END 64 End of subprograms f

CALL 65 Conditional subprogram call f


CALLU 66 Unconditional subprogram call f
SP 71 Subprogram f

SPE 72 End of a subprogram f


NOP 70 No operation f f

: Cannot be used f : Can be used

146
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and Processing of Functional Instructions (8) Part 1

Model
Com-
SUB Series 16i /18i /21i
mand Description Series 21iMODEL B
Name Number MODEL B
PMCSA1 PMCSB7
END1 1 1st Level program end f f
END2 2 2nd Level program end f f
END3 48 3rd Level program end f
TMR 3 Timer f f
TMRB 24 Fixed timer f f*2
TMRC 54 Timer f f*2
DEC 4 Decode f f
DECB 25 Binary decode f f
CTR 5 Counter f f
CTRB 56 Fixed counter f*1
CTRC 55 Counter f f
ROT 6 Rotational control f f
ROTB 26 Binary rotational control f f
COD 7 Code conversion f f
CODB 27 Binary code conversion f f
MOVE 8 Move ANDed data f f
MOVOR 28 Move ORed data f f
MOVB 43 Move 1 byte f
MOVW 44 Move 2 bytes (Word) f
MOVD 47 Move 4 bytes (Double word) f*1
MOVN 45 Move arbitrary bytes f
COM 9 Common line control f f
COME 29 Common line control end f f
JMP 10 Jump f f
JMPE 30 Jump end f f
JMPB 68 Label jump 1 f
JMPC 73 Label jump 2 f
LBL 69 Label f
PARI 11 Parity check f f
DCNV 14 Data convert f f
DCNVB 31 Binary data convert f f
COMP 15 Comparison f f
COMPB 32 Binary comparison f f
COIN 16 Coincidence check f f
SFT 33 Shift register f f
DSCH 17 Data search f f
DSCHB 34 Binary data search f f

: Not available f : Available

147
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5 (a) Types and Processing of Functional Instructions (8) Part 2

Model
Com-
SUB Series 16i /18i /21i
mand Description Series 21iMODEL B
Name Number MODEL B
PMCSA1 PMCSB7
XMOV 18 Indexed data transfer f f
XMOVB 35 Binary indexed data transfer f f
ADD 19 Addition f f

ADDB 36 Binary addition f f


SUB 20 Subtraction f f

SUBB 37 Binary Subtraction f f


MUL 21 Multiplication f f

MULB 38 Binary Multiplication f f


DIV 22 Division f f

DIVB 39 Binary division f f


NUME 23 Define constant f f
NUMEB 40 Define binary constant f f

DISP 49 Display message *3


DISPB 41 Display message f f*2

EXIN 42 External data input f f


SPCNT 46 Spindle control *3

AXCTL 53 PMC axis control f f


WINDR 51 CNC window data read f f

WINDW 52 CNC window data write f f


FNC9X 9X Arbitrary functional instruction (X=0 to 7) f*4
MMC3R 88 MMC3 window data read *3

MMC3W 89 MMC3 window data write *3


MMCWR 98 MMC window data read f f

MMCWW 99 MMC window data write f f


PSGNL 50 Position signal output *3

PSGN2 63 Position signal output 2 *3


DIFU 57 Rising edge detection f

DIFD 58 Falling edge detection f


EOR 59 Exclusive OR f
AND 60 Logical AND f

OR 61 Logical OR f
NOT 62 Logical NOT f

END 64 End of ladder program f


CALL 65 Conditional subprogram call f

CALLU 66 Unconditional subprogram call f


SP 71 Subprogram f

: Not available f : Available

148
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (a) Types and Processing of Functional Instructions (8) Part 3

Model
Com-
SUB Series 16i /18i /21i
mand Description Series 21iMODEL B
Name Number MODEL B
PMCSA1 PMCSB7
SPE 72 End of subprogram f
NOP 70 No operation (Net comment) f f

: Not available f : Available

NOTE
1 These are new functions that are added to PMCSB7.
2 These specifications are improved for PMCSB7.
3 These are ignored like NOP if these are programmed in ladder. Therefore, you can use these
functions to keep compatibility of your ladder program for several machines. You must certainly
keep ACT=0 in case of some functions that need ACT input.
4 This is effective when you use PMC C language option.

149
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

The execution time constant is a ratio of the execution time of a functional


instruction to the execution time of 10 basic instruction steps (1.5 s).
Execution time constants are used when a ladder program is executed in
the separate mode.

Table 5 (b) Execution Time Constants of Functional Instructions (1)

Instruc- SUB Model


Processing
tion Number PMCSB PMCSC
END1 1 End of a firstlevel ladder program 171 1033

END2 2 End of a secondlevel ladder program 26 45

END3 48 End of a thirdlevel ladder program - 0

TMR 3 Timer processing 19 33

TMRB 24 Fixed timer processing 19 34

TMRC 54 Timer processing 17 29

DEC 4 Decoding 21 28

DECB 25 Binary decoding 16 23

CTR 5 Counter processing 21 35

CTRC 55 Counter processing 18 26

ROT 6 Rotation control 37 53

ROTB 26 Binary rotation control 27 39

COD 7 Code conversion 20 29

CODB 27 Binary code conversion 19 29

MOVE 8 Data transfer after Logical AND 19 27

MOVOR 28 Data transfer after logical OR 13 19

COM 9 Common line control 11 14

COME 29 End of common line control 0.1 0.1

JMP 10 Jump 12 16

JMPE 30 End of a jump 9 11

PARI 11 Parity check 13 19

DCNV 14 Data conversion 25 37

DCNVB 31 Binary data conversion 132 233

COMP 15 Comparison 22 36

COMPB 32 Binary comparison 20 31

COIN 16 Coincidence check 21 36

SFT 33 Shift register 15 22

DSCH 17 Data search 237 287

DSCHB 34 Binary data search 351 596

XMOV 18 Indexed data transfer 26 38

XMOVB 35 Binary indexed data transfer 27 37

150
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (b) Execution Time Constants of Functional Instructions (2)

Instruc- SUB Model


Processing
tion Number PMCSB PMCSC
ADD 19 Addition 22 33

ADDB 36 Binary addition 25 39

SUB 20 Subtraction 21 32

SUBB 37 Binary subtraction 25 39

MUL 21 Multiplication 42 63

MULB 38 Binary multiplication 28 45

DIV 22 Division 44 66

DIVB 39 Binary division 33 53

NUME 23 Constant definition 18 25

NUMEB 40 Binary constant definition 13 20

DISP 49 Message display 51 93

DISPB 41 Extended message display 177 297

EXIN 42 External data input 29 49

WINDR 51 NC window data read 101 293

WINDW 52 NC window data write 101 293

FNC9X 9X Arbitrary functional instruction (X=0 to 7) - 21

MMC3R 88 MMC3 window data read 342 375

MMC3W 89 MMC3 window data write 385 421

MMCWR 98 MMC window data read 100 293

MMCWW 99 MMC window data write 100 293

151
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Execution time constant: This constant represents how many times the execution time of a
functional instruction corresponds to the execution time of 10 basic
instructions (about 1.5s) . The execution time of a basic instruction is
about 0.15 s.
The general format and restrictions common to each functional
instruction are given below, details on each instructions will follow later.
Refer to this paragraph without fail, since it covers the provisions on using
a functional instruction and other important items.
(1) Format
Since the functional instructions cannot be represented with relay
symbols, the format shown in Fig. 5 (a) must be used. The format
includes control conditions, an instruction, parameters, W1, R9000
to R9005 (Functional instruction operation result register).

Control conditions
Parameter (Note)
A B
(3)
I
n
L0 L1 s
C D t
(2) r Para
(2) (3) (4)

u meter
R 2.4 R 3.1 c
t (1) W1
RST
(1) i
o R 10.1
n
R 5.7
ACT
(0)
(E1)
R 7.1

7 6 5 4 3 2 1 0
R9000

R9001

R9002

R9003

R9004

R9005

Fig. 5 (a) Function instruction format

152
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5 (c) Coding of function instruction

Coding sheet Status of operating result


Step Address
Instruction Bit No. Remarks ST3 ST2 ST1 ST0
Number No.
1 RD R1 . 0 A A
2 AND R1 . 1 B A@B
3 RD. STK R2 . 4 C A@B C
4 AND. NOT R3 . 1 D A@B C@D
5 RD. STK R5 . 7 RST A@B C@D RST
6 RD. STK R7 . 1 ACT A@B C@D RST ACT
7 SUB ff Instruction A@B C@D RST ACT
8 (PRM) (Note 2) ffff Parameter 1 A@B C@D RST ACT
9 (PRM) ffff Parameter 2 A@B C@D RST ACT
10 (PRM) ffff Parameter 3 A@B C@D RST ACT
11 (PRM) ffff Parameter 4 A@B C@D RST ACT
12 WRT R10 . 1 W1 output A@B C@D RST W1

NOTE
1 Numbers in parentheses under control conditions indicate
the position of the stored register.
2 (PRM) of steps 8 to 11 under Instruction means that P must
be input when a parameter is input from the programmer,
and PRM is not required to be input when a parameter is
input from a paper tape.

(2) Control condition


The number and meaning of control conditions vary with each
functional instruction. The control conditions are entered in the stick
register as shown in Table 5 (b). The sequence is fixed and cannot
be changed or omitted.

CAUTION
For the functional instructions, with a RST as a control
condition, the RST has the highest priority. Accordingly
when RST=1, the RST processing is done even when
ACT=0.

(3) Instruction
The types of instructions are shown in Table 5 (a). The Programmer
has exclusive keys for functional instructions TMR and DEC. They
are input by T and D keys, respectively. The other functional
instructions are given by S key and a following number. When
instructions are input by relay symbols, software keys are used to
input them. Refer to chapter III or V for details.
(4) Parameter
Unlike basic instructions, functional instructions can handle numeric
values. Thus the reference data or addresses containing data are
entered under Parameter. The number and meaning vary with each
functional instruction. The P key is used to enter parameters in the
Programmer.

153
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(5) W1
The operation results of a functional instruction, when represented with
one bit of 1 or 0, is output to W1 whose address can be determined freely
by the programmer. Its meaning varies with each functional instruction.
Note that some functional instructions have no W1.
(6) Data to be processed
Data handled by functional instructions are of binary coded decimal
(BCD) code and binary code.
In the conventional PMCs, the numeric data is processed mainly
based on the BCD code. However, in the PMCSB/SC, it is
recommended to handle all pieces of numeric data with the binary
code. The reasons for this are:
(a) In the Series 16, the numeric data (M, S, T, B code) between the
CNC and the PMC should be of the binary code.
(b) Numeric data on which the CPU performs processing must be in
binary format. When numeric data is always processed in binary
format, therefore, neither BCDtobinary nor binarytoBCD
conversion is necessary, thus enabling faster PMC processing.
(c) When the data is of the binary code, the range of the numeric data
processable becomes wide. Also, negative numeric data can be
processed easily, and the arithmetic operation functions are
strengthened. The binary numeric data is handled, as a rule, on
the basis of 1 byte (128 to+127), 2 bytes (32768 to +32767),
and 4 bytes (99999999 to +99999999).
(d) When various numeric data items are entered or displayed using
the keys on the CRT/MDI panel, all the numeric data items in
binary are conveniently specified or displayed in decimal.
Therefore, no problem arises, though the data stored in the
internal memory is of the binary code. Pay attention to this only
when referring to the memory by the sequence program. See (7).
In the functional instructions, binary data is mainly handled.
(7) Example of numeric data
(a) BCD code data
The basic data handled with the BCD code is of 1 byte (0 to 99)
or 2 bytes (0 to 9999). The BCD 4digit data is entered into two
bytes of continuous addresses as shown below.
Example: When BCD data 1234 is stored to addresses R250
and R251.
7 6 5 4 3 2 1 0

R250 0 0 1 1 0 1 0 0

3 4

7 6 5 4 3 2 1 0

R251 0 0 0 1 0 0 1 0

1 2
Specify smaller address R250 by a functional instruction.
(Note) The low order digits are entered to the smaller address.

154
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(b) Binary code data


The basic data handled with the binary code is of 1 byte (128 to
+127), 2 bytes (32,768 to +32,767) and 4 bytes (99,999,999 to
+99,999,999). The data is stored at addresses R200, R201, R202
and R203 as shown below.

1 byte data (128 to +127) Example: 1 byte data

7 6 5 4 3 2 1 0
R200 " 26 25 24 23 22 21 20 7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 1 (+1)
0 : Positive
1 : Negative

2 byte data (32,768 to + 32,767) 1 1 1 1 1 1 1 1 (1)


7 6 5 4 3 2 1 0
R200 27 26 25 24 23 22 21 20

0 1 1 1 1 1 1 1 (+127)
R201 " 214 213 212 211 210 29 28

4 byte data (99999999 to +99999999) 1 0 0 0 0 0 0 1 (127)

7 6 5 4 3 2 1 0
R200 27 26 25 24 23 22 21 20

R201 215 214 213 212 211 210 29 28

R202 223 222 221 220 219 218 217 216

R203 " 230 229 228 227 226 225 224

By a functional instruction, specify smaller address R200.


A negative value is set by the twos complement code.

(8) Addresses of numerical data handled in the function instructions


When numerical data handled in the function instructions are 2 bytes
or 4 bytes, addresses of numerical data specified by parameters of
function instructions are better to take even numbers.
The use of even addresses slightly reduces the execution time of
functional instructions.
These parameters of the functional instructions mainly handling
binary data are marked with an asterisk as follows.

155
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

* When 2byte or 4byte data is handled, assigning even addresses to addresses marked with *
reduces the time required to execute functional instructions.

A + B = C Error output

RST
ADDB
* * *
ffff ffff ffff ffff
W1
ACT Address Address Address for
Specifying for an for an outputting
(SUB36)
a format augend addend the sum

Fig. 5 (b)
In even addresses, the number after R is even with internal relays, and
the number after D is even in data tables.
(9) Functional instruction calculation result register (R9000 to R9005)
(See Fig. 5 (c))
The result of calculation of the functional instruction is set in the
register.
This register is used commonly to the functional instructions.
Therefore, refer to the information in the register immediately after the
functional instruction is executed. Otherwise, the previous information
disappears when the next functional instruction is executed.
The calculation information in the register cannot be transferred
between different levels of the sequence program. For example, it is
impossible to read the set information by referring to registers
R9000s by the 2nd level program. When the subtraction instruction
(SUBB) is executed by the 1st level program.
The calculation information set in the register is guaranteed up to the
point just before the functional instruction for setting the next
calculation information is executed between the same level of
programs. The calculation information set in this register differs
according to the functional instruction. It can be read out by the
sequence program, but cannot be written.
7 6 5 4 3 2 1 0
R9000

R9001

R9002

R9003

R9004

R9005

Fig. 5 (c)
This register is a 6 byte register (R9000 to R9005), and the data of
1 bit unit or 1 byte unit can be referred to.
When reading the data of bit 1 of R9000, specify RD R9000.1.

156
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.1
END1 (1ST LEVEL
SEQUENCE
PROGRAM END)

5.1.1 Must be specifies once in a sequence program, either at the end of the 1st
Function level sequence, or at the beginning of the 2nd level sequence when there
is no 1st level sequence.

5.1.2 Fig. 5.1.2 shows the format of END.1 and Table 5.1.2 shows the coding.
Format

END1
(SUB 1)

Fig. 5.1.2 Format of END.1

Table 5.1.2 Coding of END.1


Coding sheet
Step Address Bit
Instruction Remarks
Number Number Number
SUB 1 End of 1st level

157
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.2
END2 (2ND LEVEL
SEQUENCE
PROGRAM END)

5.2.1 Specify at the end of the 2nd level sequence.


Function

5.2.2 Fig.5.2.2 shows the expression format and Table 5.2.2 shows the coding
Format format.

END2
(SUB 2)

Fig. 5.2.2 Format of END.2

Table 5.2.2 Coding of END.2


Coding sheet
Step Address Bit
Instruction Remarks
Number Number Number
SUB 2 2nd level sequence program end

158
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.3
END3 (END OF 3RD
LEVEL SEQUENCE)
(PMCSC/SC3/SC4/
NB/NB2/NB6/NB7
ONLY)
5.3.1 Specify this command at the end of the 3rd level sequence program, i.e.
it indicates the end of the sequence program. If there is no 3rd level
Function
sequence program, specify this command immediately after END.2
command.

5.3.2 Fig.5.3.2 shows description format and Table 5.3.2 shows coding format.
Format

END3
(SUB 48)

Fig. 5.3.2 END.3 description format

Table 5.3.2 END.3 coding format


Coding sheet
Step Address Bit
Instruction Remarks
Number Number Number
SUB 48 End of 3rd level program

159
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.4
TMR (TIMER)

5.4.1 This is an ondelay timer.


Function

5.4.2 Fig.5.4.4 (a) shows description format and Table 5.4.4 shows coding
Format format.

5.4.3 ACT=0: Turns off the timer relay (TMff).


Control Condition ACT=1: Initiates the timer.

5.4.4 When the time preset is reached with ACT=1 as shown in Fig.5.4.4 (b),
Timer Relay (TMff) the timer relay turns on. The address of the timer relay is determined by
designer.
Timer relay

ACT

TMR ff TMff

fff.f
fff.f

Timer number
Control condition Instruction

Fig. 5.4.4 (a) Format of TMR


Table 5.4.4 Coding of TMR

Step Address Bit


Instruction Remarks
Number Number Number
1 RD ffff. f ACT
2 TMR ff
3 WRT fff. f TMff

ACT
TMff
T
T indicates the time set in this timer
command.

Fig. 5.4.4 (b) Operation of the timer

160
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.4.5 The timer can be set via the CRT/MDI unit of the CNC (See Chapter II).
Setting Timers The setting time is every 48 ms for timer number 1 to 8 and every 8 ms
for timer number 9 to 40. A time less than 48 ms is discarded for timer
number 1 to 8. The time set by timers 9 to 40 is every 8 ms. Any
remainder is discarded. For example, if 38 ms is set, the remainder 6
(38=8 4+6) is discarded, and only 32 ms is actually set.

Model PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4

Type of timer

48 ms timer 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8
number

8 ms timer number 9 to 40 9 to 40 9 to 40 9 to 40 9 to 40 9 to 40 9 to 40 9 to 40 9 to 40 9 to 150

Model SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

Type of timer

48 ms timer 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8 1 to 8
number

8 ms timer number 9 to 40 9 to 150 9 to 250 9 to 40 9 to 40 9 to 150 9 to 40 9 to 150 9 to 150

5.4.6
Timer Accuracy

Type of timer Setting time Error

48 ms timer 48 ms to 1572.8 s 0 to +48 ms

8 ms timer 8 ms to 262.1 s 0 to +8 ms

Variation in time is caused only by operation time of the Timer


Instruction. For example, when a timer instruction is used in the 2nd level
sequence part, the variation does not include the delay time (Max. 2nd
level sequence one cycle time) until the sequence actuates after the set
time is reached.

5.4.7 Set the timer number.


Parameter
WARNING
If the timer number is duplicated, or falls outside the valid
range, the operation will be unpredictable.

161
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.5
TMRB (FIXED TIMER)

5.5.1 This timer is used as a fixed ondelay timer. The variable timer in section
Function 5.4 sets time of the timer into the nonvolatile memory, and can be reset
via the CRT/MDI when necessary.
Time present in this fixed timer is written to the ROM together with the
sequence program, so the timer time once set cannot be changed unless
the whole ROM is exchanged.

5.5.2 The format is expressed as follows (Fig.5.5.2).


Format

Timer relay

ACT TMRB fff f f


TMB
(SUB24) Timer Preset fff
number time

Fig. 5.5.2 Format of TMRB

5.5.3 ACT=0: Turns off timer relay


Control Conditions (TMBfff).
ACT=1: Start timer.

5.5.4 As shown in Fig.5.5.4, timer relay is set ON after certain time preset in
Timer Relay the parameter of this instruction pasts after ACT=1.
The designer will decide the address of the internal relay in the timer relay.
(TMBfff)
ACT
TMB
T
T indicates the time set in this timer
command.

Fig. 5.5.4 Timer operation

5.5.5 (a) Timer number


Sets timer number (1 to 100) of the fixed timers.
Parameter
For the PMCSB7, set a number between 1 and 500.

WARNING
If the same timer number is used more than once or if a timer
number out of the valid range is used, operation is
unpredictable.

162
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(b) Preset time is 8 to 262,136 ms.


Processing is done every 8 ms in this fixed timer.
The preset time is therefore integral times of 8 ms and the odds are
omitted.
For example, when set 38 ms, 38=8 4+6, the odd 6 is omitted, and
the preset time becomes 32 ms.
The range of the preset time is 8 to 262,136 ms.
For the PMCSB7, preset time is 1 to 32,760,000 msec (about 546
minutes).

5.5.6 Time varies 0 to level 1 sweep interval from the setting time.
Precision of the Timer The varing time in this timer is caused only the error occurred when the
timer instruction performs operation process.
Error caused by sequence program processing time (time of 1 cycle of the
second level), etc. are not included.

163
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.6
TMRC (TIMER)

5.6.1 This is the ondelay timer.


A timer setting time is set at an arbitrary address. The selection of an
Function
address determines whether the timer is a variable timer or fixed timer.
No limit is imposed on the number of timers provided areas can be
allocated.

5.6.2 Fig.5.6.2 and Table 5.6.2 show the expression format and the coding
Format format, respectively.

TMRC f ffff ffff


ACT
TM
Time set Time ff
Timer time resister
(SUB54) accuracy address address

Fig. 5.6.2 TMRC expression format

Table 5.6.2 TMRC coding format

Step Address Bit


Instruction Remarks
Number Number Number
1 RD ffff. f
2 SUB 54 TMRC command
3 (PRM) f Timer accuracy
4 (PRM) fff Timer set time address
5 (PRM) ffff Timer register address
6 WRT ffff. f TMff

5.6.3 ACT=0 : Turns off the timer relay


(TMff).
Control Condition
ACT=1 : Starts the timer.

5.6.4
Timer Accuracy Timer precision Setting value Setting time Error
8 ms 0 1 to 262,136 1 to +8 ms
48 ms 1 1 to 1,572,816 1 to +48 ms
1 s (Note) 2 1 to 32,767 1 to +1 s
10 s (Note) 3 1 to 327,670 1 to +10 s
1 m (Note) 4 1 to 32,767 1 to +1 m

NOTE
This function is usable only with the following models:
FS16C/18C PMCSB5/SB6
FS16i/18i PMCSB5/SB6
FS21i PMCSA5

164
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

For PMCSB7 :
Timer accuracy Setting number The range of setting time (Note) Margin of error
8msec 0 8msec to about 262.1sec 0 to + Level 1 Sweep Interval
48msec 1 48msec to about 26.2 min 0 to + Level 1 Sweep Interval
1sec 2 1sec to about 546 min 0 to + Level 1 Sweep Interval
10sec 3 10sec to about 91 h 0 to + Level 1 Sweep Interval
1min 4 1min to about 546 h 0 to +1sec
1msec 5 1msec to about 32.7 sec 0 to + Level 1 Sweep Interval
10msec 6 10msec to about 327.7 sec 0 to + Level 1 Sweep Interval
100msec 7 100msec to about 54.6 min 0 to + Level 1 Sweep Interval

NOTE
The range of the value is 0 to 32767.

5.6.5 Sets the first address of the timer set time field.
The continuous 2byte memory space is required for the timer set time
Timer Set Time
field.
Address Field D is normally used as this field.

Timer set time + 0


TIME
Timer set time + 1

Time : Timer set time


(1 to 32,767)

The timer set time is converted into the binary value in 8 ms (48 ms) units.
The timer set time is shown as follows:
8 ms 8 to 262,136 ms
48 ms 48 to 1,572,816 ms
1s 1 to 32,767s
10 s 1 to 327,670s
1m 1 to 32,767m

5.6.6 Set the start address of a timer register area.


Timer Register A timer register area must be allocated to a continuous fourbyte memory
area starting from the set address. Normally, the R area is used as a timer
Address register area. This area should be used by the PMC system, and therefore
should not be used by the sequence program.

Timer register + 0

Timer register + 1
Timer register
Timer register + 2

Timer register + 3

165
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.6.7 As shown in Fig. 5.6.7, after ACT is set to 1, the timer relay is turned on
Timer Relay (TMff) once the time specified in this command has elapsed.

ACT
TM ff
T
T indicates the time set in this timer
command.

Fig. 5.6.7 Timer operation

166
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.7
DEC (DECODE)

5.7.1 Outputs 1 when the twodigit BCD code signal is equal to a specified
Function number, and 0 when not. Is used mainly to decode M or T function.

5.7.2 Fig.5.7.2 and Table 5.7.2 show the expression format and Table 5.7.2
Format show the coding format.

Decoding result output


ACT

DEC ffff ffff W1

fff. f fff. f

Decode ff ff
Control condition Instruction
instruction Number of digits
instruction
Address of decode signal Number of digits instruction

Fig. 5.7.2 Format of DEC

Table 5.7.2 Coding of DEC

Step Address Bit


Instruction Remarks
Number Number Number
1 RD fff. f ACT
2 DEC ffff
3 (PRM) ffff
4 WRT fff. f W1, Decoding result output

5.7.3 ACT=0 : Turns the decoding result output off (W1).


ACT=1 : Performs decoding.
Control Condition
When the specified number is equal to the code signal, W1=1;
when not, W1=0.

5.7.4 Specify the address containing twodigit BCD code signals.


Code Signal Address

167
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.7.5 There are two paths, the number and the number of digits.
Decode Specification Decode specification

f f f f

Number of digits specification

Number specification

(i) Number:
Specify the decode number.
Must always be decoded in two digits.
(ii) Number of digits:
01 : The highorder digit of two decimal digits is set to 0 and
only the loworder digit is decoded.
10 : The loworder digit is set to 0 and only the highorder digit
is decoded.
11 : Two decimal digits are decoded.

5.7.6 W1 is 1 when the status of the code signal at a specified address is equal
W1 to a specified number, 0 when not. The address of W1 is determined by
designer.
(Decoding Result
Output)

DEC R200 3011 W1


R100.0 R103.1 R228.1

Fig. 5.7.6 Ladder diagram using the DEC instruction

Table 5.7.6 Coding for Fig.5.7.6


Coding sheet

Step Address Bit


Instruction Remarks
Number Number Number
1 RD R100.0
2 AND R103.1
3 DEC R200
4 (PRM) 3011
5 WRT R228 . 1

168
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.8
DECB (BINARY
DECODING)

5.8.1 DECB decodes one, two, or fourbyte binary code data. When one of the
Function specified eight consecutive numbers matches the code data, a logical high
value (value 1) is set in the output data bit which corresponds to the
specified number. When these numbers do not match, a logical low value
(value 0) is set.
Use this instruction for decoding data of the M or T function.
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i/Power Mate i and
PMCSA5 for Series 21i/210i, the setting of the format specification
parameter is extended. With this setting, DECB can decode multiple
(8 n) bytes.
For the details of the setting of a format specification parameter, refer to
5.8.4 Parameters.

5.8.2
Format

DECB ffff Decode result output


ffff 7 6 5 4 3 2 1 0
Code
data
(SUB 25) Decode designating
number +0
1, 2 or 4byte
binary code data Decode designating
+1
number

Decode designating +7
number
Decode designating numbers
Eight numbers, each of which is added by 0, 1, 2, . . . , and 7 to the specified number
are decoded.
When number 62 is specified, for example, eight numbers of 62 to 69 are decoded.
If code data is 62, 0 bit of output data is turned on; if 69, 7th bit is turned on.

Fig. 5.8.2 (a) Function of DECB (basic specification)

169
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

DECB ffff Decode result output


ffff 7 6 5 4 3 2 1 0
Code
data
(SUB 25) Decode designating
number +0

15 14 13 12 11 10 9 8
1, 2 or 4byte
binary code data Decode designating
number +8

8n1 8(n1)

Decode designating
number +(8n1)

Decode designating numbers


8n numbers, each of which is added by 0, 1, 2, . . . , and (8n1) to the specified
number are decoded. (n is set by the format specification parmeter)
When number 62 is specified, for example, 8n numbers of 62 to 62+8n1 are
decoded.
If code data is 62, 0 bit of output data+0 is turned on; if 77, 7th bit of output data+1 is
turned on.

Fig. 5.8.2 (b) Function of DECB (extended specification)


(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i, PMCSA5 for Series 21i/210i,
and PMCNB6 for Series 15i)

Fig.5.8.2 (c), (d) show the expression format.

*
ACT DECB f ffff ffff ffff
ffff

(SUB 25) Format Code Decode Decode


specifi data designa result
cation address tion output
address

Fig. 5.8.2 (c) Expression format of DECB (basic specification)

*
ACT DECB ffff ffff ffff ffff
ffff

(SUB 25) Format Code Decode Decode


specifi data designa result
cation address tion output
address

Fig. 5.8.2 (d) Expression format of DECB (extended specification)


(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i, PMCSA5/SB6/SB7 for Series 21i/210i,
and PMCNB6 for Series 15i)

170
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.8.3 (a) Command (ACT)


Control Conditions ACT=0 : Resets all the output data bits.
ACT=1 : Decodes data.
Results of processing is set in the output data address.

5.8.4 (a) Format specification


Set the size of code data to the 1st digit of the parameter.
Parameters
0001 : Code data is in binary format of 1 byte length
0002 : Code data is in binary format of 2 byte length
0004 : Code data is in binary format of 4 byte length
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i
and PMCSA5 for Series 21i/210i, when setting format specification
in the following extended format, DECB can decode multiple (8 n)
bytes by 1 instruction.
0nn1 : In case of decoding multiple (8 nn) bytes and code
data is binary format of 1 byte length
0nn2 : In case of decoding multiple (8 nn) bytes and code
data is binary format of 2 byte length
0nn4 : In case of decoding multiple (8 nn) bytes and code
data is binary format of 4 byte length
The nn is the numerical value from 02 to 99. When setting 00 or 01,
it works for decoding 8 numbers.

Format specification (extended specification) :


0 n n x

The byte length setting of code data


1 : 1 byte length
2 : 2 byte length
4 : 4 byte length
The multiple decoding number setting
0001 :
It decodes 8 continuous numbers.
The decode result output address needs a memory of 1 byte length.
0299 :
It decodes multiple (8 nn) continuous numbers.
The decode result output address needs a memory of nn bytes length.

(b) Code data address


specifies an address at which code data is stored.
(c) Number specification decode designation
Specifies the first of the 8 continuous numbers to be decoded.
(d) Decode result address
Specifies an address where the decoded result shall be output.
A onebyte area is necessary in the memory for the output.
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i
and PMCNB6 for Series 15i, when executing this instruction in
extended specification, the area of setting by the format specification
for the nn bytes is necessary.

171
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.9
CTR (COUNTER)

5.9.1 CTR is used as a counter. Counters are used for various purposes for NC
Function Machine tools.
Numerical data such as preset values and count values can be used with
either BCD format or binary format by a system parameter.

WARNING
When a incollect BCD data was set to a BCD type counter,
the morement of CTR cannot be sured.
If changing the counter type, be sure to reconfigure the
counter data.

This counter has the following functions to meet various applications.


(a) Preset counter
Outputs a signal when the preset count is reached. The number can
be preset from the CRT/MDI panel, or set in the sequence program.
(b) Ring counter
Upon reaching the preset count, returns to the initial value by issuing
another count signal.
(c) Up/down counter
The count can be either up or down.
(d) Selection of initial value
Selects the initial value as either 0 or 1.
A combination of the preceding functions results in the ring counter
below.

8 1
7 2

6 3
5 4

Presetting : 8
Initial value : 1

Such a counter permits the position of a rotor to be memorized.

172
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.9.2 Fig.5.9.2 show the expression format and Table 5.9.2 show the coding
Format format.

CN0

fff. f CTR ffff


(SUB 5)
UPDOWN Count up output

fff. f
W1
RST
fff. f
fff. f
ACT

fff. f Counter number

Instruction (SUB 5)
Control condition

Fig. 5.9.2 Format of CRT instruction

Table 5.9.2 Coding for Fig.5.9.2

Coding sheet Memory status of control condition


Step Address
Instruction Bit No. Remarks ST3 ST2 ST1 ST0
Number No.
1 RD fff . f CN0 CN0
2 RD. STK fff . f UPDOWN CN0 UPDOWN
3 RD. STK fff . f RST CN0 UPDOWN RST
4 RD. STK fff . f ACT CN0 UPDOWN RST ACT
5 SUB 5 CTR instruction CN0 UPDOWN RST ACT
6 (PRM) ff Counter number CN0 UPDOWN RST ACT
7 WRT fff . f W1 output number CN0 UPDOWN RST W1

173
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.9.3 (a) Specify the initial value. (CN0)


Control Conditions CN0=0: Begins the value of the counter with 0.
0, 1, 2, 3 n.
CN0=1: Begins the value of the counter with 1 (0 is not used).
1, 2, 3 n.
(b) Specify up or down counter.
UPDOWN=0:
Up counter. The counter begins with 0 when CN0=0;
1 when 1.
UPDOWN=1:
Down counter. The counter begins with the preset value.
(c) Reset (RST)
RST=0: Releases reset.
RST=1: Enables reset.
W1 becomes 0. The integrated value is reset to the initial value.

NOTE
Set RST to 1, only when reset is required.

(d) Count signal (ACT)


1

Count Count

0: Counter does not operate. W1 does not change.


ACT
1: Count is made by catching the rise of ACT.

5.9.4
Counter Number

Model PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4

Counter number 1 to 20 1 to 20 1 to 20 1 to 20 1 to 20 1 to 20 1 to 20 1 to 20 1 to 20 1 to 50

Model SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

Counter number 1 to 20 1 to 50 1 to 100 1 to 20 1 to 20 1 to 50 1 to 20 1 to 50 1 to 50

The preset value and cumulative value that can be set are as follows:
Binary counter: 0 to 32767
BCD counter: 0 to 9999

WARNING
If the counter number is duplicated, or falls outside the valid
range, the operation will be unpredictable.

174
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.9.5 When the count is up to a preset value, W1=1. The address of W1 can be
Countup Output (W1) determined arbitrarily.
When the counter reaches the set value, W1 is set to 1.
When the counter reaches 0 or 1, W1 is set to 1.

5.9.6 [Example 1]
As a preset counter (See Fig.5.9.6 (a))
Examples of Using the
The number of workpieces to be machined is counted. When the number
Counter reaches the preset count, a signal is output.
D L1 is a circuit to make logic 1.
D Since the count ranges from 0 to 9999, contact B of L1 is used for
making CN0=0.
D Since it is to be up counter, contract B of L1 is used make
UPDOWN=0.
D The reset signal of the counter uses input signal CRST.M from the
machine tool.
D The count signal is M30X, which was decoded from the CNC
output M code. M30X contains contact B of CUP to prevent
counting past the preset value, as long as reset is not enabled after
countup.

L1

L1
R200.1
L1 R200.1

R200.1
L1
(3) (1)
(CN0)
R200.1
L1
(2)
(UPDOWN) CTR 0001
(SUB 5)
R200.1
CUP Count up output
CRST.M
(1)
(RST) Y6.1
X36.0
CUP M30X
(0)
(ACT)
Y6.1 R200.3

Fig. 5.9.6 (a) Ladder diagram for the counter, example 1

175
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

[Example 2]
Use of the counter to store the position of a rotor. (See Fig.5.9.6 (b))

L1
1
R200.1
R200.1
L1

R200.1
L1
(3)
(CN0)
R200.1
REV
(2)
(UPDOWN)
CTR 0002
R200.1
L1 (SUB 5)
(1)
(RST) R200.0
R200.1
POS
(0)
(ACT)
X36.0

Fig. 5.9.6 (b) Ladder diagram for the counter, example 2


4
3 5

2
6

1 7

12 8

11 9
10

Fixed position for indexing

Fig. 5.9.6 (c) Indexing for a rotor


Fig.5.9.6 (b) shows a ladder diagram for a counter to store the position of
a rotor of Fig.5.9.6 (c).
(1) Control conditions
(a) Count start number
When a 12angle rotor shown in Fig.5.9.6 (c) is used, the count
starting number is 1. Contact A of L1 is used for making CN0=1.
(b) Specify up and down
The signal REV changes according to the then direction of
rotation. It becomes 0 for forward rotation and 1 for reverse
rotation. Thus, the counter is an up counter for forward rotation
and a down counter for reverse rotation.
(c) Reset
In this example, since W1 is not used, RST=0, and contact B of
L1 is used.

176
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(d) Count signal


The count signal POS turns on and off 12 times each time the rotor
rotates once.
(2) Counter number and W1
In this example, the second counter is used. The result of W1 is not
used, but its address must be determined.
(3) Operation
(a) Setting the preset value
Since the rotor to be controlled is 12angle as shown in Fig.5.9.6
(c), 12 must be preset in the counter. It is set from the CRT/MDI
panel.
(b) Setting the current value
When the power is turned on, the position of the rotor must be
equated with the count on the counter. The count is set via the
CRT/MDI panel. Once a current value is set, then correct current
positions will be loaded to the counter every time.
(c) The POS signal turns on and off each time the rotor rotates.
The number of times of the POS signal turns on and off is counted
by the counter, as below.
1, 2, 3, . . . 11, 12, 1, 2, . . .
for forward rotation
1, 12, 11, . . . 3, 2, 1, 12 . . .
for reverse rotation

177
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.10 PMCSB7
CTRB (FIXED O
COUNTER)

5.10.1 CTRB is used as a counter. Numerical data such as preset values and count
Functions values can be used with binary format. This counter has the following
functions to meet various applications.
(a) Preset counter
Preset the count value. If the count reaches this preset value, outputs
to show that.
(b) Ring counter
This is the ring counter which is reset to the initial value when the
count signal is input after the count reaches the preset value.
(c) Up/down counter
This is the reversible counter to be used as both up counter and down
counter.
(d) Selection of initial value
Either 0 or 1 can be selected as the initial value.

5.10.2 Fig.5.10.2 and Table 5.10.2 show the expression format and the cording
Format format, respectively.

CN0

UPDOWN
OOOO.O
CTRB O....O
Counter
(SUB56) Preset Value
Number W1
RST

ACT

Fig. 5.10.2 CTRB expression format

178
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5.10.2 CTRB cording format

Step Address Bit


Instruction Remarks
number number number
1 RD OOOO.O CN0
2 RD.STK OOOO.O UPDOWN
3 RD.STK OOOO.O RST
4 RD.STK OOOO.O ACT
5 SUB 56 CTRB command
6 (PRM) OOO Counter Number
7 (PRM) O...O Preset Value
8 WRT OOOO.O W1

5.10.3 (a) Specifying the initial value (CN0)


Control Condition CN0=0 : The counter value starts with 0. 0,1,2,3,.......,,n
CN0=1 : The counter value starts with 1. 1,2,3,4.........,n
(b) Specifying up or down (UPDOWN)
UPDOWN=0 : Up counter
The initial value is 0 when CN0=0 or 1 when CN0=1.
UPDOWN=1 : Down counter
The initial value is the preset value.
(c) Reset (RST)
RST=0 : Cancels reset.
RST=1 : Resets. W1 is reset to 0. The accumulated value is reset
to the initial value.
(d) Count signal (ACT)
ACT=0 : The counter does not operated. W1 does not change.
ACT=1 : The counter operates at the rise of this signal.
(3) Counter number
Set 1 to 100 as counter number.
(4) Preset value
Following value can be set as preset value.
Binary counter: 0 to 32767
*CTRB is always binary counter. System parameter is ineffective.
(5) Countup output (W1)
When the counter value reaches the preset value, W1 is set to 1. The
W1 address can be specified arbitrarily.
(6) Accumulate value
The address C5000 are used for accumulate value of the CTRB. One
value has 2 bytes.
Counter number 1 corresponds to C5000 and number 2 corresponds
to C5002.

179
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.11
CTRC (COUNTER)

5.11.1 The numeral data of this counter are all binary. This counter has the
following functions and can be used according to the application:
Functions
(a) Preset counter
Preset the count value and if the count reaches this preset value,
outputs to show that.
(b) Ring counter
This is the ring counter which is reset to the initial value when the
count signal is input after the count reaches the preset value.
(c) Up/down counter
This is the reversible counter to be used as both the up counter and
down counter.
(d) Selection of the initial value
Either 0 or 1 can be selected as the initial value.

5.11.2 Fig.5.11.2 and Table 5.11.2 show the expression format and the coding
format, respectively.
Format

CN0
CTRC ffff ffff

UPDOWN
SUB 55

Counter Counter
RST preset value register W1
address address

ACT

Fig. 5.11.2 CTRC expression format

Table 5.11.2 CRTC coding format

Step Address Bit


Instruction Remarks
Number Number Number
1 RD ffff. f CN0
2 RD.STK ffff. f UPDOWN
3 RD.STK ffff. f RST
4 RD.STK ffff. f ACT
5 SUB 55 CRTC command
6 (PRM) ffff Counter preset address
7 (PRM) ffff Counter register address
8 WRT ffff. f W1

180
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.11.3 (a) Specifying the initial value (CN0)


Control Conditions CN0=0 : The count value starts with 0. 0, 1, 2, 3, . . . n
CN0=1 : The count value starts with 1. 1, 2, 3, . . . n
(b) Specifying up or down count (UPDOWN)
UPDOWN=0:
Up counter.
The initial value is 0 when CN0=0 or 1 when CN0=1.
UPDOWN=1:
Down counter. The initial value is the preset value.
(c) Reset (RST)
RST=0 : Reset cancelled.
RST=1 : Reset. W1 is reset to 0. The accumulated value is
reset to the initial value.
(d) Count signal (ACT)
ACT=0 : The counter does not operate. W1 does not change.
ACT=1 : The counter operates at the rise of this signal.

5.11.4 The first address of the counter preset value field is set.
Counter Preset Value The continuous 2byte memory space from the first address is required
for this field. Field D is normally used.
Address

Counter preset value+0


CTR: Preset value
CTR
(0 to 32,767)
Counter preset value+1

The counter preset value is binary. Therefore, it ranges from 0 to 32767.

5.11.5 The first address of the counter register field is set.


Counter Register The continuous 4byte memory space from the first address is required
for this field. Field D is normally used.
Address
NOTE
When field R is specified as the counter register address,
the counter starts with count value 0 after powered on.

181
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.11.6 If the count value reaches the preset value, W1 is set to 1.


Countup Output (W1) The W1 address can be determined freely.

Counter register +0
CTR Count value
Counter register +1

Counter register +2
WORK WORK : Unusable
Counter register +3

182
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.12
ROT (ROTATION
CONTROL)

5.12.1 Controls rotors, such as the tool post, ATC, rotary table, etc., and is used
Function for the following functions.
(a) Selection of the rotation direction via the shorter path
(b) Calculation of the number of steps between the current position and
the goal position
(c) Calculation of the position one position before the goal or of the
number of steps up to one position before the goal

5.12.2 Fig.5.12.2 shows the expression format and Table 5.12.2 shows the
Format coding format.

RN0
(5) (1) (2) (3) (4)

ffff. f
BYT
(4)

ffff. f
DIR Rotating direction
(3) output
ROT
ffff. f (SUB 6) ffff ffff ffff ffff W1
POS
(2) ffff. f

ffff. f
INC
(1)

ffff. f
ACT
(0)

ffff. f
Calculating result output address
Goal position address

Control condition Current position address


Instruction
Rotor indexing address

Fig. 5.12.2 ROT instruction format

183
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5.12.2 Coding for Fig.5.12.2


Coding sheet Status of operating result
Step Instruc- Address
Bit No. Remarks ST5 ST4 ST3 ST2 ST1 ST0
Number tion No.
1 RD ffff . f RN0 RN0
2 RD. STK ffff . f BYT RN0 BYT
3 RD. STK ffff . f DIR RN0 BYT DIR
4 RD. STK ffff . f POS RN0 BYT DIR POS
5 RD. STK ffff . f INC RN0 BYT DIR POS INC
6 RD. STK ffff . f ACT RN0 BYT DIR POS INC ACT
7 SUB 6 ROT RN0 BYT DIR POS INC ACT
8 (PRM) ffff Rotor indexing number RN0 BYT DIR POS INC ACT
9 (PRM) ffff Current position RN0 BYT DIR POS INC ACT
10 (PRM) ffff Goal position address RN0 BYT DIR POS INC ACT
11 (PRM) ffff Calculating result output address RN0 BYT DIR POS INC ACT
12 WRT fff . f RN0 BYT DIR POS INC W1
13
14
15

5.12.3 (a) Specify the starting number of the rotor.


RN0=0 : Begins the number of the position of the rotor with 0.
Control Conditions
RN0=1 : Begins the number of the position of the rotor with 1.
(b) Specify the number of digits of the process data (position data).
BYT=0 : BCD two digits
BYT=1 : BCD four digits
(c) Select the rotation direction via the shorter path or not.
DIR=0 : No direction is selected. The direction of rotation is
only forward.
DIR=1 : Selected. See (8) for details on the rotation direction.
(d) Specify the operating conditions.
POS=0 : Calculates the goal position.
POS=1 : Calculates the position one position before the goal
position.
(e) Specify the position or the number of steps.
INC=0 : Calculates the number of the position. If the position
one position before the goal position is to be calculated,
specify INC=0 and POS=1
INC=1 : Calculates the number of steps. If the difference
between the current position and the goal position is to
be calculated, specify INC=1 and POS=0.
(f) Execution command
ACT=0 : The ROT instruction is not executed. W1 does not
change.
ACT=1 : Executed. Normally, set ACT=0. If the operation
results are required, set ACT=1.

184
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.12.4 Specify the rotor indexing number.


Rotor Indexing Number

5.12.5 Specify the address storing the current position.


Current Position
Address

5.12.6 Specify the address storing the goal position (or command value), for
Goal Position Address example the address storing the CNC output T code.

5.12.7 Calculate the number of steps for the rotor to rotate, the number of steps
Operation Result up to the position one position before, or the position before the goal.
When the calculating result is to be used, always check that ACT=1.
Output Address

5.12.8 The direction of rotation for control of rotation via the shorter path is
Rotating Direction output to W1. When W1=0, the direction is forward (FOR) when 1,
reverse (REV). The definition of FOR and REV is shown in Fig.5.12.8.
Output (W1) If the number given to the rotor is ascending, the rotation is FOR; if
descending, REV. The address of W1 can be determined arbitrarily.
When, however, the result of W1 is to be used, always check that ACT=1.

An example of a 12position rotor


(a) (b)
1 1
12 2 2 12

11 3
3 11
FOR REV REV FOR

10 4 4 10

9 5 5 9

8 6 6 8
7 7

Indexing fixed position Indexing fixed position

Fig. 5.12.8 Rotation direction

185
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.13
ROTB
(BINARY ROTATION
CONTROL)

5.13.1 This instruction is used to control rotating elements including the tool
Function post, ATC (Automatic Tool Changer), rotary table, etc. In the ROT
command (5.12) a parameter indicating the number of rotating element
indexing positions is a fixed data in programming. For ROTB, however,
you can specify an address for the number of rotating element index
positions, allowing change even after programming. The data handled are
all in the binary format. Otherwise, ROTB is coded in the same way as
ROT.

5.13.2 Fig.5.13.2 shows the expression format of ROTB


Format

RN0

* * * *

DIR

POS
ROTB f ffff ffff ffff ffff
W1

INC

(SUB 26) Format Rotating Current Target Arithm


specific element position position etic
ACT ation indexed address address result
position output
address address

Fig. 5.13.2 Expression format of ROTB

5.13.3 The control conditions do not differ basically from those for ROT
Control Conditions command described in section 5.12. However, BYT has been eliminated
from ROTB (it forms part of the ROTB parameters).
For the reset, see ROT.

186
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.13.4 (a) Format


Parameters Specifies data length (1, 2, or 4 bytes). Use the first digit of the
parameter to specify the number of bytes.
1 : 1 byte
2 : 2 bytes
4 : 4 bytes
All numerical data (number of indexed positions for the rotating
elements, current address, etc.) are in the binary format.
Therefore, they require the memory space specified by data length.
(b) Rotating element indexed position address
Specifies the address containing the number of rotary element
positions to be indexed.
(c) Other parameters
For the functions and use of the other parameters, see Section 5.12.

5.13.5 See Section 5.12.


Output for Rotational
Direction (W1)

5.13.6 Fig. 5.13 (b) illustrates a ladder diagram for a 12position rotor to be
controlled for rotation via the shorter path and for deceleration at the
Example of Using the
position one position before the goal.
ROTB Instruction
D The goal position is specified with CNC 32B of binary code (address
F26 to F29).
D The current position is entered with the binary code signal (address
X41) from the machine tool.
D The result of calculating the position one position before the goal is
output to address R230 (work area).
D Operation starts with the output TF (address F7.3) from the CNC.
D The coincidence check instruction (COIN) is used to detect the
deceleration and stop positions.

187
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

A
A Logic 1
R0228.0 R0228.0
A

R0228.0
A (4)
ROTB 4 D0000 X0041 F0026 R0230
(SUB 26) CR Shorter
R0228.0 CCW path or not
A R0228.1
(3) Refer Rotor Current Goal Calcula
ence indexing position position tion
R0228.0 data number address address result
format output
A address
(2)

R0228.0
A (1)

R0228.0
CWM CCWM
TF (0)

F0007.3 Y0005.6 Y0005.6

TF (0) COMPB 1004 R0230 X0041


(SUB 32) Refer Refer Compari
F0007.3 ence ence son
data data data
TF format address
Deceleration
TDEC position
detection
R9000.0 F0007.3 R0228.2
TDEC TF
DECM Deceleration
command
R0228.2 F0007.3 Y0005.5
TCOMPB DECM

R0228.3 Y0005.5
TF (0)
COMPB 1004 F0026 X0041
(SUB 32) Refer Refer Compari
F0007.3 ence ence son
data data data
TF format address Goal position
TCO (stop position)
MPB detection
R9000.0 F0007.3 R0228.3
CRCCW TCOMPB
TF
CWM Forward
rotation
F0007.3 R0228.1 R0228.3 Y0005.6 command
TF CRCCW TCOMPB
CCWM Reverse
rotation
F0007.3 R0228.1 R0228.3 Y0005.6 command

Fig. 5.13.6 Example of a ladder diagram for the ROTB instruction

188
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.14
COD
(CODE CONVERSION)

5.14.1 Converts BCD codes into an arbitrary two or fourdigits BCD numbers.
Function For code conversion shown in Fig.5.14.1 the conversion input data
address, conversion table, and convert data output address must be
provided.
Set a table address, in which the data to be retrieved from the conversion
table is contained, to conversion table input data address in a twodigits
BCD number. The conversion table is entered in sequence with the
numbers to be retrieved in the two or fourdigits number. The contents
of the conversion table of the number entered in the conversion input data
address is output to the convert data output address. As shown in
Fig.5.14.1, when 3 is entered in the conversion input data address, the
contents 137 located at 3 in the conversion table is output to the convert
data output address.

Table internal address Conversion table

Conversion input 0
data address 3
1


ffff
Specifies table internal 2


number (BCD twodigits).
3 137


Convert data
output address
ffff
Data of the specified table internal address is
output to this address.
n

Fig. 5.14.1 Code conversion diagram

189
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.14.2 Fig.5.14.2 shows the format for the COD instruction and Table 5.14.2
Format shows the coding format.

BYT

ffff. f
COD Error output
RST
(SUB 7) ffff ffff ffff
W1
ffff. f
ACT

ffff. f Converted data output


address
Conversion input data address
Size of table data
Control condition Instruction

Conversion data table

Table address Convert data

1 f f f f
2 f f f f
3 f f f f
4 f f f f

Fig. 5.14.2 COD instruction

Table 5.14.2 Coding for Fig.5.14.2

Coding sheet Memory status of control condition


Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RST BYT RST
3 RD. STK fff . f ACT BYT RST ACT
4 SUB 7 COD instruction

5 (PRM) ffff Size of table data (1)

6 (PRM) ffff Conversion input data address (2)

7 (PRM) ffff Convert data output address (3)

8 (PRM) ffff Convert data at table address 0 (4)

9 (PRM) ffff Convert data at table address 1 (5)

10 : : :

11 WRT fff . f Error output W1

190
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.14.3 (a) Specify the data size.


Control Conditions BYT=0 : Specifies that the conversion table data is to be BCD
two digits.
BYT=1 : Specifies that the conversion table data is to be BCD
four digits.
(b) Error output reset
RST=0 : Disable reset
RST=1 : Sets error output W1 to 0 (resets).
(c) Execution command
ACT=0 : The COD instruction is not executed. W1 does not
change.
ACT=1 : Executed.

5.14.4 A conversion table data address from 0 to 99 can be specified.


Size of Table Data Specify n+1 as the size of table when n is the last table internal number.

5.14.5 The conversion table address includes a table address in which converted
Conversion Input Data data is loaded. Data in the conversion table can be retrieved by specifying
a conversion table address.
Address One byte (BCD 2digit) is required for this conversion input data address.

5.14.6 The convert data output address is the address where the data stored in the
Convert Data Output table is to be output. The convert data BCD two digits in size, requires
only a 1byte memory at the convert data output address.
Address Convert data BCD four digits in size, requires a 2byte memory at the
convert data output address.

5.14.7 If an error occurs in the conversion input address during execution of the
COD instruction, W1=1 to indicate an error.
Error Output (W1)
For example, W1=1 results if a number exceeding the table size specified
in the sequence program is specified as the conversion input address.
When W1=1, it is desirable to effect an appropriate interlock, such as
having the error lamp on the machine tool operators panel light or
stopping axis feed.

5.14.8 The size of the conversion data table is from 00 to 99.


Conversion Data Table The conversion data can be either BCD two digits or four digits, which
is specified depends on the control conditions

191
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.15
CODB (BINARY
CODE CONVERSION)

5.15.1 This instruction converts data in binary format to an optional binary


Function format 1byte, 2byte, or 4byte data.
Conversion input data address, conversion table, and conversion data
output address are necessary for data conversion; as shown in Fig.5.15.1.
Compared to the 5.14 COD Function Instruction, this CODB function
instruction handles numerical data 1, 2 and 4byte length binary format
data, and the conversion table can be extended to maximum 256.

Table address Conversion table

Conversion
2 0
data address
ffff


Specify table address 1
here.(binaryformat1 byte)


2
(Note 1) This table data is binary


format 2byte data.


3
Conversion data


(Note 2) Conversion table is written
output address 1250
in the ROM together
ffff
Data stored in the specified together with the program,
table address is output to because it is defined in the
this address sequence program.

n
n : max. 255

Fig. 5.15.1 Code conversion diagram

5.15.2 Fig.5.15.2 shows the expression format of CODB.


Format

RST *
Error output
CODB f fff ffff ffff

W1
ACT (SUB 27) Format Number Conversi Conversi
designa of on input on data
tion conver data output
sion address address
table
data

Fig. 5.15.2 Expression format of CODB

192
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.15.3 (a) Reset (RST)


Control Conditions RST=0 : Do not reset.
RST=1 : Reset error output W1 (W1=0).
(b) Activate command (ACT)
ACT=0 : Do not execute CODB instruction
ACT=1 : Execute CODB instruction.

5.15.4 (a) Format designation


Parameters Designates binary numerical size in the conversion table.
1 : Numerical data is binary 1byte data.
2 : Numerical data is binary 2byte data.
4 : Numerical data is binary 4byte data.
(b) Number of conversion table data
Designates size of conversion table. 256 (0 to 255) data can be made.
(c) Conversion input data address
Data in the conversion data table can be taken out by specifying the
table number. The address specifying the table number is called
conversion input data address, and 1byte memory is required from
the specified address.
(d) Conversion data output address
Address to output data stored in the specified table number is called
conversion data output address.
Memory of the byte length specified in the format designation is
necessary from the specified address.

5.15.5 Size of the conversion data table is maximum 256 (from 0 to 255).
This conversion data table is programmed between the parameter
Conversion Data Table
conversion data output address of this instruction and the error output
(W1).

5.15.6 If there are any abnormality when executing the CODB instruction,
Error Output (W1) W1=1 and error will be output.

193
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.16
MOVE
(LOGICAL PRODUCT
TRANSFER)

5.16.1 ANDs logical multiplication data and input data, and outputs the results
Function to a specified address. Can also be used to remove unnecessary bits from
an eightbit signal in a specific address, etc.
(Logical multiplication data) (Input data) to a specified address
The input data is one byte (eight bits).
7 6 5 4 3 2 1 0
Input data 0 0 0 0 0 0 0 0

Logical f f f f f f f f
multiplicationdata
Loworder fourbit logical
multiplication data
Highorder fourbit
logical multiplication data

5.16.2 Fig.5.16.2 shows the expression format and Table 5.16.2 shows the
Format coding format.

ACT
MOVE (1) (2) (3) (4)
(SUB 8) ffff ffff ffff ffff
ffff. f

Output address

Control condition Input data address


Loworder 4bit logical multiplication data

Highorder 4bit logical multiplication data

Fig. 5.16.2 Move instruction format


Table 5.16.2 Coding for Fig.5.16.2

Coding sheet Memory status of control condition


Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f ACT ACT
2 SUB 8 MOVE instruction
3 (PRM) ffff Highorder 4bit logical
multiplication data (1)
4 (PRM) ffff Loworder 4bit logical
multiplication data (2)
5 (PRM) ffff Input data address (3)
6 (PRM) ffff Output data address (4)

194
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.16.3 ACT=0 : Move instruction not executed.


Execution Command ACT=1 : Executed.

5.16.4 If a code signal and another signal coexist at address X35 for an input
Example of Using the signal from the machine tool, to compare the code signal and a code signal
at another address, the rest of signals in address X35 becomes an obstacle.
MOVE Instruction Thus, the MOVE instruction can be used to output only the code signal
at address X35 address R210.

7 6 5 4 3 2 1 0
Address X35

Code signal

Another signa

Logical multiplication data 0 0 0 1 1 1 1 1

Loworder fourbit logical multiplication data

Highorder fourbit logical multiplication data

Address R210 0 0 0

Code signal

A MOVE (1) (2) (3) (4)


(SUB 8) 0001 1111 X035 R210
R228.1

Fig. 5.16.4 MOVE instruction ladder diagram

195
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.17
MOVOR
(DATA TRANSFER
AFTER LOGICAL
SUM)

5.17.1 This instruction ORs the input data and the logical sum data and
transfers the result to the destination.
Function
Input data Logical sum data
OR

Output data

5.17.2 Fig.5.17.2 shows the expression format of MOVOR.


Format

MOVOR ffff ffff ffff


ACT

(SUB 28) Input data Logical Output


address sum data address
address

Fig. 5.17.2 Expression format of MOVOR

5.17.3 (a) Command (ACT)


Control Conditions ACT=0: Do not execute MOVOR.
ACT=1: Execute MOVOR.

5.17.4 (a) Input data address


Parameters Specifies the address for the input data.
(b) Logical sum data address
Specifies the address of the logical sum data with which to OR the
transferred data.
(c) Output address
This is the address to contain the logical sum obtained. It is also
possible to obtain the logical sum (OR) of the input and the logical
sum data and output the result in the logical sum data address. For
this, you must set the logical sum data address for the output address.

196
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.18
COM (COMMON LINE
CONTROL)
5.18.1
: Can be used
COM (Common Line
: Cannot be used
Control) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f

This function can be used for specifying the number of coils only on the
PMCSB/SC. On other PMCs, specify 0 for the number of coils and use
the common line control end instruction to use this function. For how to
use the instruction, see Subsection 5.18.4.

5.18.1.1 The specified number of coils or the coils in a region up to the common
Function line control end instruction (COME) are turned off. (See Fig.5.18.1.1)
Relay number specification is set when a numeric other than zero is
specified in a parameter for the number of turned off coils.
Specification of the region up to the common line control end instruction
is set when zero is specified for the number of turned off coils.
When the common line control end instruction is programmed in the relay
number specification, error is indicated when programming is completed.

ACT COM ffff

Number of
SUB 9
turnedoff
coils

0 to 9999
0 : Region specification
Other than 0 : Numeric specification

COME
Effective only when the number of
SUB 29 turnedoff coils is set to zero.

Fig. 5.18.1.1 Function of COM

197
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.18.1.2 Fig.5.18.1.2 (a) shows the expression format of COM


Format

COM ffff

SUB 9 Number of
turnedoff
coils

Fig. 5.18.1.2 (a) Expression format of COM

ACT COM 2

(a)

A B
W1
ACT=1
11.0 11.1
(b) C

W2
D

(a) When COM ACT=1, execution


B F G begins with the step after COM.
(b) When COM ACT=0, coil W1 and coil
W3 W2 are turned OFF unconditionally,
ACT=0 and execution begins with the next
step after W2.

Fig. 5.18.1.2 (b) Ladder diagram for the COM instruction

5.18.2 ACT=0 : The specified number of coils or the coils within the region
specified are unconditionally turned off (set to 0).
Control Conditions
ACT=1 : No processing is performed.
Processing is performed from the step next to the COM instruction.

198
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.18.3 (a) Number of turnedoff coils


Parameter Specify 0 to 9999.
0 : Region specification
Other than 0: Coil number specification

ACT A B
W1

ACT C
W2

E F G
W3

Fig. 5.18.3 (a) Relay circuit example

CAUTION
1 A functional instruction in a range specified by COM executes processing,
regardless of COM ACT. However, if COM ACT=0, the coil of the execution result becomes 0.
2 Another COM instruction cannot be specified in the range specified by the COM instruction.
3 If COM ACT=0, the coil written in by a WRT. NOT instruction in a range specified by COM
becomes 1 unconditionally.
4 The number of coils cannot be specified in PMCSA2, or PMCSB2. Assume the number of
coils to be 0 and specify the region with the common line control end (COME) command.

ACT
COM 3

A B
W1 Regardless of the ACT condition of the
COM instruction, if ACT1=1, the input
data of MOVE function is transferred to
Highord Loworde Input Output the output address
ACT1 er 4bit r 4bit data address
MOVE logical logical address
multiplicat multiplicat
ion data ion data

D Reference Comparis
data on data
COIN (address) (address) W2 When ACT=0 in the COM instruction,
ACT2 W2=0 unconditionally.

E
W3

Fig. 5.18.3 (b)

199
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.18.4
: Can be used
COM (Common Line
: Cannot be used
Control) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f f f f f f f

5.18.5 The COM instruction controls the coils in a range up to a common line
Function control end instruction (COME). (See Fig.5.18.5) Specify 0 as the
number of coils, and specify a range to be controlled using the common
line end instruction.
When the common line end instruction is not specified, the message COM
FUNCTION MISSING is displayed.
ACT

COM 0

SUB 9

Valid range of
the COM
f instruction

COME

SUB 29

Fig. 5.18.5 Function of COM

5.18.6 Fig.5.18.6 shows the expression format of the functional instruction


COM.
Format
ACT
COM 0

SUB 9

Fig. 5.18.6 Expression Format of COM

200
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.18.7 ACT = 0 : The coils in the specified range are unconditionally turned
Control Conditions off (set to 0).
ACT = 1 : The same operation as when COM is not used is performed.

5.18.8 (a) Specify 0. (Range specification only)


Parameters
NOTE
1 COM instruction operation
Suppose the following Ladder diagram including a COM
instruction exists:

ACT
COM 0

SUB 9

ON OUT1

OFF OUT2

Then, for the coil OUTx, this Ladder diagram has the same
effect as the following Ladder diagram:
ON ACT OUT1

OFF ACT OUT2

So, the functional instructions in the range specified with a


COM instruction are processed, regardless of the setting of
ACT of the COM instruction. Note, however, that the coil for
the execution of a functional instruction is unconditionally
set to 0 when COM ACT = 0.
2 In the range specified with a COM instruction, no additional
COM instruction can be specified.
3 As explained in the figures in Note 1, the coil for WRT.NOT
in the range specified with a COM instruction is
unconditionally set to 1 when COM ACT = 0.

201
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.18.9 Do not create a program in which a combination of JMP and JMPE


Caution instructions is used to cause a jump to and from a sequence between the
COM and COME instructions; the ladder sequence may not be able to
operate normally after the jump.

JMP instruction
COM instruction

Prohib-
ited
JMP instruction
COM instruction

Prohib-
COME instruction ited
JMPE instruction

COME instruction

JMPE instruction

202
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.19
COME (COMMON
LINE CONTROL END)

5.19.1 This instruction indicates the division in the region specification of the
Function common line control instruction (COM).
This instruction cannot be used alone. It must he used together with the
COM instruction.

5.19.2 Fig.5.19.2 shows the expression format of COME


Format
COME

SUB 29

Fig. 5.19.2 Expression format of COME

203
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.20
JMP (JUMP)

5.20.1
: Can be used
JMP (Jump)
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f

This function can be used for specifying the number of coils only on the
PMCSB/SC. On other PMCs, specify 0 for the number of coils and use
the jump end instruction to use this function. For how to use the
instruction, see Subsection 5.20.7.

5.20.2 This instruction jumps the specified number of coils or the logic
Function instructions (including the functional instructions) contained within the
region up to the jump end instruction (JMPE).
Coil number specification is set when a numeral other than zero is
specified in the parameter for the number of coils.
Specification of the region up to the jump end instruction is set when zero
is set for the number of coils. Nesting of jump instructions is not allowed.

ACT JMP ffff

SUB 10 Number
of jumped
coils

0 to 9999
0 : Region specification
Other tha 0 : Coil number specification

JMPE
Effective only when the number of
SUB 30 jumped coils is set to zero.

Fig. 5.20.2

204
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.20.3
Format
ACT JMP ffff

Number
SUB 10 of jumped
coils

5.20.4 ACT=0 : Nojump.Processing begins with the step after the JMP instruction.
ACT=1 : The logic instructions contained within the specified number of
Control Conditions
coils or the specified region are jumped. Processing is performed
from the next step.

5.20.5 (a) Number of jumped coils


Parameter Specify 0 to 9999.
0 : Region specification jump
Other than 0 : Coil number specification jump
When the jump end instruction is programmed in the coil number
specification, error is indicated when programming is completed.
Table 5.20.5 JMP instruction coding
Step Instruc- Address Bit Remarks
Number tion Number Number
1 RD fff. f ACT
2 SUB 10 JMP instruction
3 (PRM) ffff Number of coils to be jumped

NOTE
The number of coils can be specified only for the
PMCSB/SC. Assume the number of coils to be 0 and specify
the region with the jump end (JMPE) command.

205
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.20.6 Fig.5.20.6 shows a ladder diagram for the JMP instruction. When
Operation ACT=0, the next step to the JMP instruction is executed. When ACT=1,
logical operations are skipped according to the specified number of coils.
Note that, when ACT=1, even if signal A changes from 1 to 0 or vice versa
as shown in Fig.5.20.6, W1 remains in a status before ACT=1. Similarly,
W2 remains unchanged, even if signals B, C, and D change. If a sequence
is executed in ladder split mode, even the use of the JMP instruction does
not reduce the execution time of the sequence (see Section I.2.3,
Processing Priority).

ACT
JMP
2
(SUB 10)

A
W1
ACT=0
10.1 20.1
B
W2
C

E F
W3
ACT=1

Fig. 5.20.6 Ladder diagram for the JMP instruction

206
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.20.7
: Can be used
JMP (Jump)
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f f f f f f f

5.20.7.1 The JMP instruction causes a departure from the normal sequence to
Function executing instructions. When a JMP instruction is specified, processing
jumps to a jump and instruction (JMPE) without executing the logical
instructions (including functional instructions) in the range delimited by
a jump end instruction (JMPE). (See Fig.5.20.7.1) Specify 0 as the
number of coils, and specify a range to be skipped using the jump end
instruction.
When the jump end instruction is not specified, the message JUMP
FUNCTION MISSING is displayed.
ACT
JMP 0

SUB 10

Valid range of the


f
JMP instruction

JMPE

SUB 30

Fig. 5.20.7.1 Function of JMP

5.20.7.2 Fig.5.20.7.2 shows the expression format of the functional instruction


Format JMP.

ACT
JMP 0

SUB 10

Fig. 5.20.7.2 Expression format of JMP

207
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.20.7.3 ACT=1 : The logical instructions (including functional instructions) in


Control Conditions the specified range are skipped; program execution proceeds to
the next step.
ACT=0 : The same operation as when JMP is not used is performed.

5.20.7.4 (a) Specify 0. (Range specification only)


Parameters
NOTE
JMP instruction operation
When ACT = 1, processing jumps to a jump end instruction
(JMPE); the logical instructions (including functional
instructions) in the specified jump range are not executed.
When the Ladder program is executed in the nonseparate
mode, this instruction can reduce the Ladder execution
period (scan time).

5.20.8 Do not create a program in which a combination of JMP and JMPE


Caution instructions is used to cause a jump to and from a sequence between the
COM and COME instructions; the ladder sequence may not be able to
operate normally after the jump.

JMP instruction
COM instruction

Prohib- JMP instruction


COM instruction ited

COME instruction
JMPE instruction Prohib-
ited

COME instruction

JMPE instruction

208
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.21
JMPE (JUMP END)

5.21.1 This instruction indicates the division in the region specification of the
Function jump instruction (JMP).
It cannot be used alone. It must be used together with the JMP instruction.

5.21.2
Format
JMPE

SUB 30

209
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.22
PARI
(PARITY CHECK)

5.22.1 Checks the parity of code signals, and outputs an error if an abnormality
Function is detected. Secifies either an even or oddparity check. Only onebyte
(eight bits) of data can be checked.

5.22.2 Fig.5.22.2 shows the expression format and Table 5.22.2 shows the
Format coding format.

O.E (2)

ffff. f Error output


PARI
RST (1)
(SUB 11) ffff W1

ffff. f
ffff. f
ACT (0)

ffff. f

Check data address


Control condition Instruction

Fig. 5.22.2 PARI instruction format

Table 5.22.2 PARI instruction coding


Coding sheet Memory status of control condition
Step Addres
Number Instruction s No. Bit No. Remarks ST3 ST2 ST1 ST0

1 RD fff. f ACT O.E


2 RD. STK fff. f ACT O.E RST
3 RD. STK fff. f ACT O.E RST ACT
4 SUB 11 PARI instruction
5 (PRM) ffff Check data address
6 ffff. f Error output W1

210
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.22.3 (a) Specify even or odd.


Control Conditions O.E=0 : Evenparity check
O.E=1 : Oddparity check
(b) Reset
RST=0 : Disables reset.
RST=1 : Sets error output W1 to 0. That is, when a parity error
occurs, setting RST to 1 results in resetting.
(c) Execution command
ACT=0 : Parity checks are not performed. W1 does not alter.
ACT=1 : Executes the PARI instruction, performing a parity
check.

5.22.4 If the results of executing the PARI instruction is abnormal, W1=1 and
Error Output (W1) an error is posted. The W1 address can be determined arbitrarily.

5.22.5 Fig.5.22.5 shows oddparity checking of a code signal entered at address


Example of Using the X036.
PARI Instruction

7 6 5 4 3 2 1 0
Address X036 0

6bit code signal


Oddparity bit

A
A
R228.0
A R228.0

R228.0
A (2)

R228.0
PARI
ERST.M
(1)
(SUB 11) X036 ERR
X32.7

TF (0)

F7.3

Fig. 5.22.5 Ladder diagram for the PARI instruction

NOTE
For bits 0 to 7, bits other than those for the parity check must
be 0.

211
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.23
DCNV
(DATA CONVERSION)

5.23.1 Converts binarycode into BCDcode and vice versa.


Function

5.23.2 Fig.5.23.2 shows the expression format and Table 5.23.2 shows the
Format coding format.

BYT (3)
(1) (1)
fff. f DCNV

CNV (2)
(SUB 14) ffff ffff

fff. f Error output


RST (1)
W1
fff. f
fff. f
ACT (0)

fff. f
Conversion result output address
Instruction Input data address
Control condition

Fig. 5.23.2 DCNV instruction format

Table 5.23.2 DCNV instruction coding

Coding sheet Memory status of control condition


Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD f fff . f BYT BYT
2 RD. STK fff . f CNV BYT CNV
3 RD. STK fff . f RST BYT CNV RST
4 RD. STK fff . f ACT BYT CNV RST ACT
5 SUB 14 DCNV instruction

6 (PRM) ffff (1) Input data address

7 (PRM) ffff (2) Conversionresult output address

8 WRT fff . f W1 error output W1

212
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.23.3 (a) Specify data size.


Control Conditions BYT=0 : Process data in length of one byte (8 bits)
BYT=1 : Process data in length of two byte (16 bits)
(b) Specify the type of conversion
CNV=0 : Converts binarycode into BCDcode.
CNV=1 : Converts BCDcode into binarycode.
(c) Reset
RST=0 : Disables reset.
RST=1 : Resets error output W1. That is, setting RST to 1 when
W1, makes W1=0.
(d) Execution command
ACT=0 : Data is not converted. W1 does not alter.
ACT=1 : Data is converted.

5.23.4 W1=0 : Normal


Error Output (W1) W1=1 : Conversion error
W1=1 if the input data which should be BCD data, is binary
data, or if the data size (byte length) specified in advance is
exceeded when converting binary data into BCD data.

213
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.24
DCNVB (EXTENDED
DATA CONVERSION)

5.24.1 This instruction converts 1, 2, and 4byte binary code into BCD code or
Function vice versa. To execute this instruction, you must preserve the necessary
number of bytes in the memory for the conversion result output data.

5.24.2 Fig.5.24.2 shows the expression format of DCNVB


Format
SIN
* *

CNV

DCNVB f ffff ffff


W1
RST
(SUB 31)

Format Input data Convers


specifica address ion result
ACT tion
output
address

Fig. 5.24.2 Expression format of DCNVB

5.24.3 (a) Sign of the data to be converted (SIN)


Control Conditions This parameter is significant only when you are converting BCD data
into binary coded data. It gives the sign of the BCD data.
Note that though it is insignificant when you are converting binary
into BCD data, you cannot omit it.
SIN=0 : Data (BCD code) to be input is positive.
SIN=1 : Data (BCD code) to be input is negative.
(b) Type of conversion (CNV)
CNV=0 : Convert binary data into BCD data
CNV=1 : Convert BCD data into binary data.
(c) Reset (RST)
RST=0 : Release reset
RST=1 : Reset error output W1. In other words, set W1=0.
(d) Execution command (ACT)
ACT=0 : Data is not converted. The value of W1 remains unchanged.
ACT=1 : Data is converted.

214
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.24.4 (a) Format specification


Parameters Specify data length (1,2, or 4 bytes).
Use the first digit of the parameter to specify byte length.
1 : one byte
2 : two bytes
4 : four bytes
(b) Input data address
Specify the address containing the input data address.
(c) Address for the conversion result output
Specify the address to output the data converted to BCD or binary
format.

5.24.5 W1=0 : Correct conversion


Error Output (W1) W1=1 : Abnormally
(The data to be converted is specified as BCD data but is found to be
binary data, or the specified number of bytes cannot contain (and hence
an overflow occurs) the BCD data into which a binary data is converted.)

5.24.6 This register is set with data on operation. If register bit 1 is on, they
Operation Output signify the following.
For the positive/negative signs when binary data is converted into BCD
Register (R9000) data, see R9000.

7 6 5 4 3 2 1 0

R9000

Negative

Overflow
(data exceeds the number of bytes specified)

215
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.25
COMP
(COMPARISON)

5.25.1 Compares input and comparison values.


Function

5.25.2 Fig.5.25.2 shows the expression format and Table 5.25.2 shows the
Format coding format.

BYT COMP
f ffff ffff
(SUB 15) Comparison
fff.f result output
W1
ACT
ffff.f
fff.f

Instruction Comparison value


Control condition Input value

Input data format


(constant or address)

Fig. 5.25.2 COMP instruction format

Table 5.25.2 COMP instruction coding


Coding sheet Memory status of control condition
Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f ACT BYT ACT
3 SUB 15 COMP instruction
4 (PRM) f Input data format
5 (PRM) ffff Input data
6 (PRM) ffff Comparison data address
7 WRT fff . f W1: Comparison result output W1

216
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.25.3 (a) Specify the data size.


Control Conditions BYT=0 : Process data (input value and comparison value) is BCD
two digits long.
BYT=1 : Process data (input value and comparison value) is four
digits long.
(b) Execution command
ACT=0 : The COMP instruction is not executed. W1 does not alter.
ACT=1 : The COMP instruction is executed and the result is output
to W1.

5.25.4 0 : Specifies input data with a constant.


1 : Specifies input data with an address
Input Data Format
Not specify input data directly, but specify an address storing input
data.

5.25.5 The input data can be specified as either a constant or the address storing
it. The selection is made by a parameter of format specification.
Input Data

5.25.6 Specifies the address storing the comparison data.


Comparison Data
Address

5.25.7 W1=0 : Input data > Comparison data


W1=1 : Input data x Comparison data
Comparison Result
Output

217
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.26
COMPB
(COMPARISON
BETWEEN BINARY
DATA)

5.26.1 This instruction compares 1, 2, and 4byte binary data with one another.
Function Results of comparison are set in the operation output register (R9000).
Sufficient number of bytes are necessary in the memory to hold the input
data and comparison data.

5.26.2 Fig.5.26.2 shows the expression format of COMPB.


Format

* *

ACT COMPB ffff ffff ffff

Format Input data Address of


SUB 32 specifi (address) data to be
cation compared

Fig. 5.26.2 Expression format of COMPB

5.26.3 (a) Command (ACT)


Control Conditions ACT=0 : Do not execute COMPB.
ACT=1 : Execute COMPB.

5.26.4 (a) Format specification


Parameters Specify data length (1,2, or 4 bytes) and format for the input data
(constants data or address data).

0 0

Specification of data length


1 : 1 byte length data
2 : 2 byte length data
Specification of format 4 : 4 byte length data
0 : Constants
1 : Address

(b) Input data (address)


Format for the input data is determined by the specification in a).
(c) Address of data to be compared
Indicates the address in which the comparison data is stored.

218
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.26.5 The data involved in the operation are set in this register. This register is
Operation Output set with data on operation. If register bit 1 is on, they indicate the
following:
Register (R9000)
7 6 5 4 3 2 1 0

R9000

Zero (input data=data compared)

Negative (input data<data compared)

Overflow

219
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.27
COIN (COINCIDENCE
CHECK)

5.27.1 Checks whether the input value and comparison value coincide.
Function This instruction is available with BCD data.

5.27.2 Fig.5.27.2 shows the expression format and Table 5.27.2 shows the
Format coding format.

BYT (1) COIN (1) (2) (3)


Result
fff.f W1
(SUB 16) f ffff ffff Output
ACT (0)
ffff.f
fff.f

Comparison value
Instruction Input value
Control conditions address

Input value format (constant or address)

Fig. 5.27.2 COIN instruction format

Table 5.27.2 COIN instruction coding


Coding sheet Memory status of control condition
Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f ACT BYT ACT
3 SUB 16 COIN instruction
4 (PRM) f Reference value format
5 (PRM) ffff Reference value
6 (PRM) ffff Comparison value address
7 WRT fff . f W1: Checking result output W1

220
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.27.3 (a) Specify the data size.


Control Conditions BYT=0 : Process data (input value, and comparison values).
Each BCD is two digits long.
BYT=1 : Each BCD four digits long.
(b) Execution command
ACT=0 : The COIN instruction is not executed. W1 does not
change.
ACT=1 : The COIN instruction is executed and the results is output
to W1.

5.27.4 0 : Specifies input data as a constant.


1 : Specifies input data as an address.
Input Data Format.

5.27.5 The input data can be specified as either a constant or an address storing
Input Data it. The selection is made by a parameter of format designation.

5.27.6 Specifies the address storing the comparison data.


Comparison Data
Address

5.27.7 W1=0 : Input data 0 Comparison data


Comparison Result W1=1 : Input data = Comparison data
Output

221
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.28
SFT
(SHIFT REGISTER)

5.28.1 This instruction shifts 2byte (16bit) data by a bit to the left or right.
Note that W1=1 when data 1 is shifted from the left extremity (bit 15)
Function
in left shift or from the right extremity (bit 0) in right shift.

5.28.2
Format
DIR
SFT *

CONT ffff

RST Address of W1
shift data

ACT
(SUB 33)

5.28.3 (a) Shift direction specification (DIR)


DIR=0 : Left shift
Control Conditions
DIR=1 : Right shift
(b) Condition specification (CONT)
CONT=0:
On 1 bit shifts by one bit in the specified direction.
The condition of an adjacent bit (eighter right or left adjacent bit
according to the specification of shift direction DIR) is set to the
original bit position of the on 1 bit.
Also, 0 is set to bit 0 after shifting in the left direction or set to hit
15 after shifting in the right direction.
In case of leftward shift;

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Left shift

Bit shifts leftward every bit

Shift out at bit 15


Zero is set to bit 0.

CONT=1:
Shift is the same as above, but 1s are set to shifted bits.

222
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Left shift
0 0 0 0 0 0 1 1 1 1 0 0 1 1 0 0

Each bit shifts leftward. Status 1 remains unchanged

(c) Reset (RST)


The shifted out data (W1=1) is reset (W1=0).
RST=0 : W1 is not reset.
RST=1 : W1 is reset (W1=0).
(d) Actuation signal (ACT)
Shift processing is done when ACT=1. For shifting one bit only,
execute an instruction when ACT=1, and then, set ACT to 0
(ACT=0).

5.28.4 (a) Shift data addresses


Parameters Sets shift data addresses. These designated addresses require a
continuous 2byte memory for shift data.
Bit numbers are represented by bit 0 to 15 as shown below. When
addresses are designated for programming, an address number is
attached every 8 bits, and the designable bit numbers are 0 to 7.

7 6 5 4 3 2 1 0
Designated address

15 14 13 12 11 10 9 8

Designated address +1

5.28.5 W1=0 : 1 was not shifted out because of the shift operation.
Shifted Out W1=1 : 1 was shifted out because of the shift operation.

223
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.29
DSCH
(DATA SEARCH)

5.29.1 DSCH is only valid for data tables (see section 6.3) which can be used by
Function the PMC. DSCH searches the data table for a specified data, outputs an
address storing it counting from the beginning of the data table. If the data
cannot be found, an output is made accordingly.
Table internal number Data table
0

1
Search data
2
100 100

Search data result output

Fig. 5.29.1

NOTE
Parameter of this functional instruction and the data table
heading address specified here are table internal number 0.
The table internal number specified here, however, is
different from that mentioned in 6.3.

5.29.2 Fig.5.29.2 shows the expression format and Table 5.29.2 shows the
Format coding format.

BYT (2)
DSCH (1) (2) (3) (4)
ffff.f Search data
RST (1) ffff ffff ffff ffff presence/absence
W1 output address
ffff.f (SUB 17)
ffff.f
ACT (0)

ffff.f
Instruction
Search result output address
Control condition Search data address

Data table heading address

Number of data of the data table (Table capacity)

Fig. 5.29.2 DSCH instruction format

224
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Table 5.29.2 DSCH instruction coding


Coding sheet Memory status of control condition
Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RST BYT RST
3 RD. STK fff . f ACT BYT RST ACT
4 SUB 17 DSCH instruction
5 (PRM) ffff Number of data of the data table
6 (PRM) ffff Data table heading address
7 (PRM) ffff Search data address
8 (PRM) ffff Search result output address
9 WRT fff . f Search data presence/absence output adress W1

5.29.3 (a) Specify data size.


BYT=0 : Data stored in the data table, BCD two digits long.
Control Conditions
BYT=1 : Data stored in the data table, BCD four digits long.
(b) Reset
RST=0 : Release reset
RST=1 : Enables a reset, that is, sets W1 to 0.
(c) Execution command
ACT=0 : The DSCH instruction is not executed. W1 does not change.
ACT=1 : The DSCH is executed, and the table internal number
storing the desired data is output., If the data cannot be
found, W1=1.

5.29.4 Specifies the size of the data table. If the beginning of the data table is 0
Number Of Data of the and the end is n, n+1 is set as the number of data of the data table.
Data Table

5.29.5 Addresses that can be used in a data table are fixed. When preparing a data
Data Table Head table, the addresses to be used must be determined beforehand, specify the
head address of a data table here.
Address

5.29.6 Indicates the address of the data to be searched.


Search Data Address

225
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.29.7 If the data being searched for is found, the internal number of the table
Search Result Output storing the data is output to this field. This address field is called a search
result output address field.
Address The search result output address field requires memory whose size is the
number of bytes conforming to the size of the data specified by BYT.

5.29.8 W1=0 : The data to be searched exists.


W1=1 : The data to be searched does not exist.
Search Data
Presence/Absence
Output

226
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.30
DSCHB (BINARY
DATA SEARCH)

5.30.1 Alike the DSCH instruction of Section 5.29, this function instruction
Function instructs data search in the data table.
There are two differences; the numerical data handled in this instruction
are all in binary format; and number of data (table capacity) in the data
table can be specified by specifying the address, thus allowing change in
table capacity even after writing the sequence program in the ROM.

Table number Data table


0
Search data
1
100 100
2
3
Search result output
2

Fig. 5.30.1

5.30.2
Format

RST DSCHB
* * * * Search result
f ffff ffff ffff ffff
(SUB 34) W1
Storage Data table Search Output
address of head data address of
ACT number of address address search
Format data in result
designa data table
tion

Fig. 5.30.2

227
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.30.3 (a) R eset (RST)


Control Conditions RST=0 : Release reset
RST=1 : Reset. W1=0.
(b) Activation command
ACT=0 : Do not execute DSCHB instruction. W1 does not change.
ACT=1 : Execute DSCHB instruction. If the search data is found,
table number where the data is stored will be output. If the
search data is not found, W1 becomes 1.

5.30.4 (a) Format designation


Parameter Specifies data length. Specify byte length in the first digit of the
parameter.
1 : 1byte long data
2 : 2byte long data
4 : 4byte long data
(b) Storage address of number of data in data table
Specifies address in which number of data in the data table is set.
This address requires memory of number of byte according to the
format designation.
Number of data in the table is n+1 (headnumber in the table is 0 and
the last number is n).
(c) Data table head address
Sets head address of data table.
(d) Search data address
Address in which search data is set.
(e) Search result output address
After searching, if search data is found, the table number where the
data is stored will be output. The searched table number is output in
this search result output address. This address requires memory of
number of byte according to the format designation.

5.30.5 W1=0 : Search data found.


W1=1 : Search data not found.
Search Result (W1)

228
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.31
XMOV (INDEXED
DATA TRANSFER)

5.31.1 Reads or rewrites the contents of the data table. Like the DSCH
Function instruction, XMOV is only valid for data tables which can be used by the
PMC.

NOTE
The data table heading address specified here is table
internal number 0. The table internal number specified here,
however, is different from that mentioned in 6.3.

Data table
Table internal number
0


Input or output data
1 3
2

Table internal storing


2
input or output data

n
1 Read out data from the data table.
2 Write data in the data table.

Fig. 5.31.1 Reading and writing of data

5.31.2 Fig.5.31.2 shows the expression format and Table 5.31.2 shows the
Format coding format.

BYT (3)
(1) (2) (3) (4)
ffff.f XMOV
RW (2)
ffff ffff ffff ffff
ffff.f Error output
RST (1) (SUB 18)
W1
ffff.f
ACT (0) ffff.f

ffff.f
Instruction Address storing tabel internal number
Address storing input/output data
Control condition Data table heading address
Number of data of the data table (Table capacity)

Fig. 5.31.2 XMOV instruction format

229
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5.31.2 XMOV instruction coding


Coding sheet Memory status of control conditions
Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RW BYT RW
3 RD. STK fff . f RST BYT RW RST
4 RD. STK fff . f ACT BYT RW RST ACT
5 SUB 18 XMOV instruction
6 (PRM) ffff Number of data of the data table
7 (PRM) ffff Data table heading address
8 (PRM) ffff Address storing input/output data
9 (PRM) ffff Address storing table internal number
10 WRT fff . f Error output W1

5.31.3 (a) Specify the number of digits of data.


BYT=0 : Data stored in the data table, BCD in two digits long.
Control Conditions
BYT=1 : Data stored in the data table, BCD in four digits long.
(b) Specify read or write
RW=0 : Data is read from the data table.
RW=1 : Data is write in the data table.
(c) Reset
RST=0 : Release reset.
RST=1 : Enables reset, that is, sets W1 to 0.
(d) Execution command
ACT=0 : The XMOV instruction is not executed. W1 does not
change.
ACT=1 : The XMOV instruction is executed.

5.31.4 Specifies the size of the data table. If the beginning of the data table is 0
Number of Data Of the and the end is n, n+1 is set as the number of data of the data table.
Data Table

5.31.5 Address that can be used in a data table are fixed. When preparing a data
Data Table Head table, the addresses to be used must be determined beforehand, and the
head address placed in that data table .
Address

5.31.6 The input/output data storage address is the address storing the specified
Address Storing data, and is external to the data table. The contents of the data table is read
or rewritten.
Input/Output Data

230
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.31.7 The table internal number storage address is the address storing the table
Address Storing the internal number of the data to be read or rewritten.
This address requires memory specified by the formaat designation
Table Internal Number (BYT).

5.31.8 W1=0 : There is no error.


W1=1 : There is an error.
Error Output
An error occurs if a table internal number exceeding the
previously programmed number of the data table is specified.

231
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.32
XMOVB (BINARY
INDEX MODIFIER
DATA TRANSFER)

5.32.1 Alike the XMOV instruction of Section 5.31, this function instruction
Function instructs reading and rewriting of data in the data.
There are two differences; the numerical data handled in this instruction
are all in binary format; and number of data (table capacity) in the data
table can be specified by specifying the address, thus allowing change in
table capacity even after writing the sequence program in the ROM.
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i/Power Mate i,
PMCSA5 for Series 21i/210i, and PMCNB6 for Series 15i the setting
of the format specification parameter is extended. With this setting,
XMOVB can read/write the multiple data in 1 instruction. For the details
of the setting of a format specification parameter, refer to 5.32.4
Parameters.
(a) Read data from data table

The number of data table elements : M (It specifies the storage address of number
of data table elements)

DT[0] D I 3 S B

DT[1] A Index:I Input/Output data:S

DT[2]

DT[3] B

DT[4]

DT[5] C

DT[M1]

Data table:DT

The operation of the instruction :


DT[I] S

Fig. 5.32.1 (a) Read data from data table (basic specification)

232
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

The number of data table elements : M (It specifies the storage address of number
of data table elements)
The number of index array elements : N (It specifies the format specification)

DT[0] D I[0] 1 S[0] A

DT[1] A I[1] 3 S[1] B

DT[2] I[2] 5 S[2] C

DT[3] B I[3] 0 S[3] D

DT[4]
I[N1] S[N1]
DT[5] C
Index Input/Output
array:I data array:S
DT[M1]

Data table:DT

The operation of the instruction :


DT[I[n]] S[n] (n=0,1,2, . . . ,N1)

Fig. 5.32.1 (b) Read data from data table (expended specification)
(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i,
PMCSA5/SB6/SB7 for Series 21i/210i, and PMCNB6 for Series 15i)
(b) Write data to data table

The number of data table elements : M (It specifies the storage address of number
of data table elements)

S B I 3 DT[0]

Input/Output data:S Index:I DT[1]

DT[2]

DT[3] B

DT[4]

DT[5]

DT[M1]

Data table:DT

The operation of the instruction :


S DT[I]

Fig. 5.32.1 (c) Write data to data table (basic specification)

233
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

The number of data table elements : M (It specifies the storage address of number
of data table elements)
The number of index array elements : N (It specifies the format specification)

S[0] A I[0] 1 DT[0] D

S[1] B I[1] 3 DT[1] A

S[2] C I[2] 5 DT[2]

S[3] D I[3] 0 DT[3] B

DT[4]
S[N1] I[N1]
DT[5] C
Input/Output Index
data array:S array:I
DT[M1]

Data table:DT

The operation of the instruction :


S[n] DT[I[n]] (n=0,1,2, . . . ,N1)

Fig. 5.32.1 (d) Write data to data table (expended specification)


(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i,
PMCSA5/SB6/SB7 for Series 21i/210i, and PMCNB6 for Series 15i)

5.32.2
Format

RW

XMOVB f ffff ffff ffff ffff


RST Storage Data I/O data Table
address table storage number
of W1
head address storage
Format number address address
ACT of data
designa in data
(SUB 35) tion table
DT[ ] S I

Fig. 5.32.2 (a) XMOVB instruction format

RW

XMOVB ffff ffff ffff ffff ffff


RST Storage Data I/O data Table
address table storage number
of W1
head address storage
Format number address address
ACT of data
designa in data
(SUB 35) tion table
DT[ ] S[ ] I[ ]

Fig. 5.32.2 (b) XMOVB (expended specification)


(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i, PMCSA5 for Series 21i/210i,
and PMCNB6 for Series 15i)

234
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.32.3 (a) Read, write designation (RW)


Control Conditions RW=0 : Read data from data table.
RW=1 : Write data to data table.
(b) Reset (RST)
RST=0 : Reset release.
RST=1 : Reset. W1=0.
(c) Activation command (ACT)
ACT=0: Do not execute XMOVB instruction.
There is no change in W1.
ACT=1: Execute XMOVB instruction.

5.32.4 (a) Format designation


Specifies data length. Specify byte length in the first digit of the
Parameters
parameter.
0001 :1byte long data
0002 :2byte long data
0004 :4byte long data

In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i/Power Mate i,


PMCSA5/SB6/SB7 for Series 21i/210i, and PMCNB6 for Series
15i when setting format specification in the following extended
format, XMOVB can read/write multiple data in data table in 1
instruction. Specifies data length (1, 2, or 4) to the 1st digit as
abovementioned. Specifies the number of the index array elements
to the 2nd and 3rd digit. Specifies 0 to the 4th digit.
0nn1 : In case of reading/writing multiple (nn) data in data
table by 1 byte length
0nn2 : In case of reading/writing multiple (nn) data in data
table by 2 byte length
0nn4 : In case of reading/writing multiple (nn) data in data
table by 4 byte length

The nn is the numerical value from 02 to 99. When setting 00 or 01,


it works as the basic specification in which one data transfer is
performed by one instruction.

Format specification (extended specification) :


0 n n x

The byte length setting


1 : 1 byte length
2 : 2 byte length
4 : 4 byte length
The number of the index array elements
0001 :
It works as the basic specification.
0299 :
Read/Write multiple (nn) data from/to data table.

235
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(b) Storage address of number of data table elements


Set to the memory at the byte length which set the number of the data
table elements in (a) Format specification and set the address to this
parameter. The effective range of number of data table elements is
as follows with the byte length which set in (a) Format
specification.
1 byte length : 1 to 255
2 byte length : 1 to 32767
(Actually, set a value below the size of the D area.)
4 byte length : 1 to 99999999
(Actually, set a value below the size of the D area.)
(c) Data table head address
Sets head address in the data table.
The memory of (byte length) (number of data table elements)
which was set in (a) Format specification and (b) Storage address
of number of data table elements is necessary.
(d) Input/Output data storage address
In case of the reading, set the address of the memory which stores a
reading result. In case of the writing, set the address of the memory
which stores a writing result. The memory with the byte length
which set in (a) Format specification is necessary.
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i,
PMCSA5/SB6/SB7 for Series 21i/210i, and PMCNB6 for Series
15i when setting format specification in the extended format, set the
head address of the array. (In case of the reading, set the head address
of the array in which a reading result is stored. In case of the writing,
set the head address of the array in which a writing result is stored.)
The memory of (byte length) (number of index array elements)
which was set in (a) Format specification is necessary.
(e) Index storage address
Set the address of the memory in which an index value is stored. The
memory with the byte length set in (a) Format specification is
necessary. The effective range of number of data in index is as
follows according to the byte length set in (A) Format
specification.
Actually, set the value which is smaller than the value to set in (b)
Storage address of number of data table elements to the index.
When setting an index value above the value to set in (b) Storage
address of number of data table elements, it causes an error output
W1=1 in instruction execution.
1 byte length : 0 to 254
2 byte length : 0 to 32766
4 byte length : 0 to 99999998
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i,
PMCSA5/SB6/SB7 for Series 21i/210i, and PMCNB6 for Series
15i when setting format specification in the extended format, set an
address at the head of the array in which an index value is stored. The
memory of (byte length) (number of data in index array) which
was set in (a) Format specification is necessary.

236
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.32.5 W1=0 : No error


Error Output (W1) W1=1 : Error found. In the case where the index value set in (e) Index
storage address exceeds the value set in (b) Storage address
of number of data table elements, it becomes W1=1. The
reading or writing of the data table isnt executed.
In PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power
Mate i, PMCSA5/SB6/SB7 for Series 21i/210i, and
PMCNB6 for Series 15i when setting format specification in
the extended format, in the case the value set in (b) Storage
address of number of data table elements, it becomes W1=1.
The reading or writing of a data table is executed for the normal
index values but not executed as for the wrong index values.

5.32.6 (a) Read data from data table (extended specification)


Example for Extended
Specification
The number of data table elements : R0=9
The number of index array elements : 4

RW=0

XMOVB 0041 R0 R100 R200 D0


RST=0
W1

ACT=1

R100 D D0 2 R200 A

R101 D1 5 R201 B

R102 A D2 8 R202 C

R103 D3 0 R203 D

R104 Index array Input/Output


data array
R105 B

R106

R107

R108 C

Data table
The operation of the instruction :
(1) R102 R200
(2) R105 R201
(3) R108 R202
(4) R100 R203

Fig.5.32.6 (a) Example for XMOVB (extended specification)


(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i, PMCSA5/SB6/SB7 for Series 21i/210i,
and PMCNB6 for Series 15i)

237
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(b) Write data to data table (extended specification)

The number of data table elements : R0=9


The number of index array elements : 4

RW=1

XMOVB 0041 R0 R200 R100 D0


RST=0
W1

ACT=1

R100 A D0 2 R200 D

R101 B D1 5 R201

R102 C D2 8 R202 A

R103 D D3 0 R203

Input/Output Index array R204


data array
R205 B

R206

R207

R208 C

Data table

The operation of the instruction :


(1) R100 R202
(2) R101 R205
(3) R102 R208
(4) R103 R200

Fig. 5.32.6 (b) Example for XMOVB (extended specification)


(only for PMCSB5/SB6/SB7 for Series 16i/160i/18i/180i Power Mate i and PMCSA5/SB6/SB7 for Series 21i/210i)

238
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.33
ADD (ADDITION)

5.33.1 Adds BCD twoor fourdigit data.


Function

5.33.2 Fig.5.33.2 shows the expression format and Table 5.33.2 shows the
Format coding format.

A + B = C
BYT (2)
ADD (1) (2) (3) (4)
ffff.f
Error output
RST (1) f ffff ffff ffff W1
ffff.f (SUB 19)
ACT fff.f
(0)

ffff.f
Instruction
Sum output address

Control conditions Addend


Summand address

Format of addend (Constant or address)

Fig. 5.33.2 ADD instruction format


Table 5.33.2 DSCH instruction coding
Coding sheet Memory status of control conditions
Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RST BYT RST
3 RD. STK fff . f ACT BYT RST ACT
4 SUB 19 ADD instruction
5 (PRM) f Addend format
6 (PRM) ffff Summand address
7 (PRM) ffff Addend (address)
8 (PRM) ffff Sum output address
9 WRT fff . f Error output W1

239
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.33.3 (a) Specify the number of digits of data.


Control Conditions BYT=0 : Data is BCD two digits long.
BYT=1 : Data is BCD four digits long.
(b) Reset
RST=0 : Release reset.
RST=1 : Resets error output W1, that is, sets W1 to 0.
(c) Execution command
ACT=0 : The ADD instruction is not executed.
ACT=1 : The ADD instruction is executed.

5.33.4 0 : Specifies addend with a constant.


1 : Specifies addend with an address.
Data Format of Addend

5.33.5 Set the address storing the summand.


Summand Address

5.33.6 Addressing of the addend depends on 5.32.4.


Addend (Address)

5.33.7 Set the address to which the sum is to be output.


Sum Output Address

5.33.8 If the sum exceeds the data size specified in 5.32.3a), W1=1 is set to
Error Output indicate an error.

240
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.34
ADDB
(BINARY ADDITION)

5.34.1 This instruction performs binary addition between 1, 2, and 4byte


Function data. In the operation result register (R9000), operating data is set besides
the numerical data representing the operation results. The required
number of bytes is necessary to store each augend, the added, and the
operation output data.

5.34.2
Format

A + B = C Error output
RST
ADDB * * *
ffff ffff ffff ffff
W1
ACT
Format Augend Addend Result
(SUB 36) specifi address address or (sum)
cation constant address

5.34.3 (a) Reset (RST)


RST=0 : Release reset
Control Conditions
RST=1 : Resets error output W1. In other words, makes W1=0.
(b) Command (ACT)
ACT=0 : Do not execute ADDB. W1 does not change now.
ACT=1 : Execute ADDB.

241
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.34.4 (a) Format specification


Parameters Specifies data length (1,2, and 4 bytes) and the format for the addend
(constant or address).

0 0

Data length specification


1 : 1 byte length data
2 : 2 bytes length data
4 : 4 bytes length data

Format specification
0 : Constant data
1 : Address data

(b) Augend address


Address containing the augend.
(c) Addend data (address)
Specification in (a) determines the format of the addend.
(d) Result output address
Specifies the address to contain the result of operation.

5.34.5 W1=0 : Operation correct


Error Output (W1) W1=1 : Operation incorrect
W1 goes on (W1=1) if the result of addition exceeds the specified data
length.

5.34.6 This register is set with data on operation. If register bit is on, they signify
Operation Output the following operation data:
Register (R9000) 7 6 5 4 3 2 1 0

R9000

Zero

Negative

Overflow

242
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.35
SUB (SUBTRACTION)

5.35.1 Subtracts BCD twoor fourdigit data.


Function

5.35.2 Fig.5.35.2 shows the expression format and Table 5.35.2 shows the
Format coding format.

BYT (2)
SUB (1)
ffff.f Error output
RST (1)
f ffff ffff ffff W1
ffff.f (SUB 20)
ffff.f
ACT (0)

ffff.f
Instruction Difference output address

Control condition Subtrahend (address or constant)


Subtrahend (data address)

Minuend data format

Fig. 5.35.2 SUB Instruction format

Table 5.35.2 SUB instruction format


Coding sheet Memory status of control conditions
Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RST BYT RST
3 RD. STK fff . f ACT BYT RST ACT
4 SUB 20 SUB instruction
5 (PRM) ffff Data format of subtrahend
6 (PRM) ffff Minuend address
7 (PRM) ffff Subtrahend (address)
8 (PRM) ffff Difference output address
9 WRT fff . f Error output W1

243
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.35.3 (a) Specification of the number of digits of data.


Control Conditions BYT=0 : Data BCD two digits long
BYT=1 : Data BCD four digits long

5.35.4 RST=0 : Release reset.


RST=1 : Resets error output W1, that is, sets W1 to 0.
Reset

5.35.5 ACT=0 : The SUB instruction is not executed. W1 does not change.
ACT=1 : The SUB instruction is executed.
Execution Command

5.35.6 0 : Specifies subtrahend with a constant.


Data Format of 1 : Specifies subtrahend with an address.
Subtrahend

5.35.7 Set the address storing the minuend.


Minuend Address

5.35.8 Addressing of the subtrahend depends on 5.35.6.


Subtrahend (Address)

5.35.9 Sets the address to which the difference is output.


Difference Output
Address

5.35.10 W1 is set 1 to indicate an error if the difference is negative.


Error Output

244
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.36
SUBB (BINARY
SUBTRACTION)

5.36.1 This instruction subtracts one data from another, both data being in the
Function binary format of 1, 2 or 4 bytes.
In the operation result register (R9000), operation data is set besides the
numerical data representing the operation. A required number of bytes is
necessary to store the subtrahend, minuend, and the result (difference).

5.36.2
Format

A B = C Error output
RST
SUBB * * *
ffff ffff ffff ffff

ACT W1
Format Menuend Subtrahend Differenc
address addressor e output
(SUB 37) specifi
constant address
cation

5.36.3 (a) Reset (RST)


RST=0 : Release reset
Control Conditions
RST=1 : Resets error output W1. (Set W1 to 0.)
(b) Command (ACT)
ACT=0 : Do not execute SUBB. W1 does not change now.
ACT=1 : Execute SUBB.

245
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.36.4 (a) Format specification


Parameters Specifies data length (1, 2, and 4 bytes) and the format for the
subtrahend (constant or address).

0 0

Data length specification


1 : 1 byte length data
2 : 2 bytes length data
4 : 4 bytes length data
Format specification
0 : Constant data
1 : Address data

(b) Minuend address


Address containing the minuend.
(c) Minuend data (address)
Specification in (a) determines the format of the minuend.
(d) Result output address
Specifies the address to contain the result of operation.

5.36.5 W1=0 : Operation correct


Error Output (W1) W1=1 : Operation incorrect
W1 goes on (W1=1) if the result of subtraction exceeds the specified data
length.

5.36.6 This register is set with data on operation. If register bit is on, they signify
Operation Output the following operation data:
Register (R9000) 7 6 5 4 3 2 1 0

R9000

Zero

Negative
Overflow

246
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.37
MUL
(MULTIPLICATION)

5.37.1 Multiplies BCD twoor fourdigit data. The product must also be BCD
Function twoor fourdigit data.

5.37.2 Fig.5.37.2 shows the expression format and Table 5.37.2 shows the
Format coding format.

A B = C
BYT (2)
MUL (1) (2) (3) (4)
fff.f Error output
RST (1) f ffff ffff ffff W1
fff.f (SUB 21)
(0) ffff.f
ACT

fff.f
Instruction
Product output address

Control conditions Multiplier (address or constant)


Multiplicand address

Data format of multiplier (constant or address)

Fig. 5.37.2 MUL instruction format

Table 5.37.2 MUL instruction coding

Coding sheet Memory status of control conditions


Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RST BYT RST
3 RD. STK fff . f ACT BYT RST ACT
4 SUB 21 MUL instruction
5 (PRM) ffff Data format of multiplier
6 (PRM) ffff Multiplicand address
7 (PRM) ffff Multiplier (address)
8 (PRM) ffff Product output address
9 WRT fff . f Error output W1

247
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.37.3 (a) Specify the number of digits of data.


Control Conditions BYT=0 : Data is BCD two digits long.
BYT=1 : Data is BCD four digits long.
(b) Reset
RST=0 : Releases reset.
RST=1 : Resets error output W1, that is, sets W1 to 0.
(c) Execution command
ACT=0 : The MUL instruction is not executed. W1 does not
change.
ACT=1 : The MUL instruction is executed.

5.37.4 0 : Specifies multiplier with a constant.


1 : Specifies multiplier with an address.
Data Format of
Multiplier

5.37.5 Sets the address storing the multiplicand.


Multiplicand Address

5.37.6 Addressing of the multiplier depends on 4).


Multiplier (Address)

5.37.7 Set the address to which the product is output.


Product Output
Address

5.37.8 W1=1 is set to indicate an error if the product exceeds the size specified
Error Output in 5.37.3a).

248
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.38
MULB (BINARY
MULTIPLICATION)

5.38.1 This instruction multiplies 1, 2, and 4byte binary data items. In the
Function operation result register (R9000), operation data is set besides the
numerical data representing the operation.
A required number of bytes is necessary to store multiplicand, multiplier,
and the result (product).

5.38.2
Format

A B = C Error output
RST
MULB * * *
ffff ffff ffff ffff

ACT W1
Format Multipli Multiplier Product
(SUB 38) specifi cand address or output
cation address constant address

5.38.3 (a) Reset (RST)


RST=0 : Release reset
Control Conditions
RST=1 : Resets error output W1. In other words, makes W1=0.
(b) Command (ACT)
ACT=0: Do not execute MULB. W1 does not change now.
ACT=1: Execute MULB.

249
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.38.4 (a) Format specification


Parameters Specifies data length (1, 2, and 4 bytes) and the format for the
multiplier (constant or address).

0 0

Data length specification


1 : 1 byte length data
2 : 2 bytes length data
4 : 4 bytes length data

Format specification
0 : Constant data
1 : Address data

(b) Multiplicand address


Address containing the multiplicand.
(c) Multiplier data (address or constant)
Specification in (a) determines the format of the multiplier.
(d) Result output address
Specifies the address to contain the result of operation.

5.38.5 W1=0 : Operation correct


Error Output (W1) W1=1 : Operation incorrect
W1 goes on (W1=1) if the result of multiplication exceeds the specified
data length.

5.38.6 This register is set with data on operation. If register bit is on, they signify
Operation Output the following operation data:
Register (R9000) 7 6 5 4 3 2 1 0
R9000

Zero

Negative

Overflow

250
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.39
DIV (DIVISION)

5.39.1 Divides BCD twoor fourdigit data. Remainders are discarded.


Function

5.39.2 Fig.5.39.2 shows the expression format and Table 5.39.2 shows the
Format coding format.

BYT (2)
DIV (1) (2) (3) (4)
ffff.f Error output
RST (1)
f ffff ffff ffff W1
ffff.f (SUB 22)
(0) fff.f
ACT

ffff.f
Instruction
Quotient output address

Control conditions Divisor (address or constant)


Dividend address

Data format of divider

Fig. 5.39.2 DIV instruction format

Table 5.39.2 DIV instruction coding

Coding sheet Memory status of control conditions


Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f RST BYT RST
3 RD. STK fff . f ACT BYT RST ACT
4 SUB 22 DIV instruction
5 (PRM) ffff Data format of divider
6 (PRM) ffff Dividend address
7 (PRM) ffff Divider (address)
8 (PRM) ffff Quatient output address
9 WRT fff . f Error output W1

251
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.39.3 (a) Specify the number of digits of data.


Control Conditions BYT=0 : Data is BCD two digits long.
BYT=1 : Data is BCD four digits long.
(b) Reset
RST=0 : Releases reset.
RST=1 : Resets error output W1, that is, sets W1 to 0.
(c) Execution command
ACT=0 : The DIV instruction is not executed. W1 does not change.
ACT=1 : The DIV instruction is executed.

5.39.4 0 : Specifies divisor data by constant.


1 : Specifies divisor data by address.
Divisor Data Format
Designation

5.39.5 Sets the address storing the dividend.


Dividend Address

5.39.6 Addressing of the divisor depends on 5.39.4.


Divisor (Address)

5.39.7 Sets the address to which the quotient is output.


Quotient Output
Address

5.39.8 W1=1 is set to indicate an error if the divider is 0.


Error Output

252
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.40
DIVB (BINARY
DIVISION)

5.40.1 This instruction divides binary data items 1, 2, and 4 byte in length. In the
Function operation result register (R9000), operation data is set and remainder is
set to R9002 and following addresses.
A required number of bytes is necessary to store the dividend, divisor, and
the result (quotient).

5.40.2
Format

A / B = C Error data
RST
* * *
DIVB ffff ffff ffff ffff

Divisor W1
ACT
Format Dividend (address) Quotient
SUB 39 specifi address or address
cation constant

5.40.3 (a) Reset (RST)


RST=0 : Release reset
Control Conditions
RST=1 : Resets error output W1. In other words, makes W1=0.
(b) Command (ACT)
ACT=0 : Do not execute DIVB. W1 does not change now.
ACT=1 : Execute DIVB.

253
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.40.4 (a) Format specification


Parameters Specifies data length (1, 2, and 4 bytes) and the format for the divisor
(constant or address).

0 0

Data length specification


1 : 1 byte length data
2 : 2 bytes length data
4 : 4 bytes length data
Format specification
0 : Constant data
1 : Address data

(b) Dividend address


Address containing the dividend
(c) Divisor data (address)
Specification in (a) determines the format of the divisor.
(d) Result output address
Specified the address to contain the result of operation.

5.40.5 W1=0 : Operation correct


Error Putput (W1) W1=1 : Operation incorrect
W1 goes on (W1=1) if the divisor is 0.

5.40.6 This register is set with data on operation. If register bit is on, they signify
Operation Output the following operation data:
Register (R9000) 7 6 5 4 3 2 1 0
R9000

Zero

Negative

5.40.7 Depending on its length, the remainder is stored in one or more of


Remainder Output registers R9002 to R9005.
Address

254
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.41
NUME (DEFINITION
OF CONSTANT)

5.41.1 Defines constants, when required. In this case, constants are defined with
this instructions.
Function

5.41.2 Fig.5.41.2 shows the expression format and Table 5.41.2 shows the
Format coding format.

BYT (1) (2)


(1) NUME

fff.f ffff ffff


ACT (0)
(SUB 23)
fff.f

Instruction Constant Constant outputaddress


Control condition

Fig. 5.41.2 NUME instruction format


Table 5.41.2 NUME instruction coding

Coding sheet Memory status of control conditions


Step Instruc- Address
Bit No. Remarks ST3 ST2 ST1 ST0
Number tion No.
1 RD fff . f BYT BYT
2 RD. STK fff . f ACT BYT ACT
3 SUB 23 NUME instruction

4 (PRM) ffff Constant

5 (PRM) ffff Constant output address

5.41.3 (a) Specify the number of digits of a constant.


BYT=0 : Constant is BCD two digits long.
Control Conditions
BYT=1 : Constant is BCD four digits long.
(b) Execution command
ACT=0 : The NUME instruction is not executed.
ACT=1 : The NUME instruction is executed.

5.41.4 Sets the constant as the number of digits specified in Item (a) in Subsec.
Constant 5.41.3.

5.41.5 Sets the address to which the constant defined in Subsec. 5.41.4 is output.
Constant Output
Address

255
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.42
NUMEB (DEFINITION
OF BINARY
CONSTANTS)

5.42.1 This instruction defines 1, 2, or 4bytes long binary constant. Data


Function entered in decimal during programming is converted into binary data
during program execution. The binary data is stored in the specified
memory address(es).
In PMCSA5/SB5/SB6/SB7 for Series 16i/160i/18i/180i/21i/210i,
Power Mate i and PMCNB6 for Series 15i/150i, the setting of the format
specification parameter is extended. With this setting, NUMEB can store
multiple data by 1 instruction. This extended specification is effective
when initializing a large memory area with value. For the details of the
setting of a format specification parameter, refer to 5.41.4 Parameters.

5.42.2
Format

NUMEB
ACT
f ffff ffff

Format Constant
(SUB 40) specifi Constant output
cation address

Fig. 5.42.2 (a) NUMBER instruction format

NUMEB
ACT
ffff ffff ffff

Format Constant
(SUB 40) specifi Constant output
cation address

Fig. 5.42.2 (b) Expression format of NUMEB (extended specification)


(only for PMCSA5/SB5/SB6/SB7 for Series 16i/160i/18i/180i /21i/210i
Power Mate i and PMCNB6 for Series 15i/150i)

5.42.3 (a) Command (ACT)


ACT= 0 : Do not execute NUMEB.
Control Conditions
ACT= 1 : Execute NUMEB.

256
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.42.4 (a) Format specification


Parameters Specifies data length (1, 2, or 4 bytes).
Use the first parameter digit to specify byte length:
0001 : Binary data of 1 byte length
0002 : Binary data of 2 byte length
0004 : Binary data of 4 byte length
In PMCSA5/SB5/SB6/SB7 for Series 16i/160i/18i/180i/21i/210i
Power Mate i and PMCNB6 for Series 15i/150i, when setting
format specification in the following extended format, NUMEB can
store multiple data by 1 instruction.
Specify data length (1, 2, or 4) to the 1st digit as abovementioned.
Specify the number of the array in which is a constant to the 2nd and
3rd digit is defines.
Specify 0 to the 4th digit.
0nn1 : In case of defining multiple (nn) data by 1 byte length
0nn2 : In case of defining multiple (nn) data by 2 byte length
0nn4 : In case of defining multiple (nn) data by 4 byte length
The nn is the numerical value from 02 to 99. When setting 00 or 01,
it works as the basic specification that works for one data.

Format specification (extended specification) :


0 n n x

The byte length setting of constant


1 : 1 byte length
2 : 2 byte length
4 : 4 byte length
Number of data in the array
0001 :
It defines constant at 1 memory.
0299 :
It defines constants at multiple (nn) memory.

(b) Constant
Defined constants in decimal format. Set a constant data within the
effective range for the byte length which is set in (a) Format
specification.
(c) Constant output address
Specifies the address of the area for output of the binary data. The
memory of the number of bytes which is set in (a) Format
specification is necessary.
In PMCSA5/SB5/SB6/SB7 for Series 16i/160i/18i/180i/21i/210i
Power Mate i and PMCNB6 for Series 15i/150i, when setting
format specification in the extended format, it is necessary to reserve
memory of (byte length) (number of array elements which define
constant) which was set in (a) Format specification.

257
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.43
DISP (MESSAGE
DISPLAY)
(PMCSB/SB2/SB3/
SB4/SB5/SB6/SC/
SC3/SC4 ONLY)

5.43.1 DISP is used to display messages on the CRT screen, CNC of which enters
alarm status. Message data to be displayed is specified after the
Function
parameters of the functional instruction. One DISP functional instruction
can define up to 16 types of message. Display is performed by setting the
control condition ACT to 1. In order to display and then clear a message,
set the displayrequest bit corresponding to the message data number to
1 and 0, respectively.
Up to one alarm message (message data putting the CNC in alarm status)
can be displayed on one screen. When one message is cleared, a message
is displayed. Similarly, each time one of the message is displayed. One
operator message (message data not putting the CNC in alarm status) can
be displayed on a screen. When an operator message is cleared in a state
when four operator messages are displayed, the subsequent operator
message is displayed.

5.43.2 Fig.5.43.2 shows the instruction format and Table 5.43.2 shows the
Format coding format.

258
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(1) (2) (3) Process end


DISP
ACT
(SUB 49) ffff ffff ffff W1

fff. f

Message control address


Control condition
Number of data of one message data
Instruction
Total sum of data of message data

Message data

Message number
1

Message data 1
Message characters

m
Message number
1

Message data 2
Message characters

Message number
1

Message data n
Message characters

1 x n x 16

Fig. 5.43.2 DISP instruction format

259
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Table 5.43.2 DISP instruction coding

Coding sheet Memory status of control


conditions
Step Instruc- Address
Bit No. Remarks ST2 ST1 ST0
Number tion No.
RD fff . f ACT ACT
SUB 49 DISP ACT
(PRM) ffff Total sum of data of message data
(PRM) ffff Number of data of one message item
(PRM) ffff Message control address
(PRM) ffff Message number
(PRM) ffff 2
(PRM) ffff 3
: : : Message characters
: : :
(PRM) ffff m
(PRM) ffff Message number
(PRM) ffff 2
(PRM) ffff 3
: : : Message characters
: : :
(PRM) ffff m
: : :
: : :
(PRM) ffff Message number
(PRM) ffff 2
(PRM) ffff 3
: : : Message characters
: : :
(PRM) ffff m
WRT ffff Process end (W1) W1

260
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.43.3 ACT=0: Nothing is processed. W1 does not change.


Control Condition ACT=1: The specified message data is displayed or cleared.
ACT must remain 1 until processing end is reported by W1.

5.43.4 (a) Total sum of message data of data:


Parameters m n
(b) Number of data of one massage data:
m Note)
(c) Message control address: Specifies the address of the RAM of
internal relay area (see 5.43.7 for details).

NOTE
The number of data used by each message data item, m,
must be the same. Since 00 is ignored, it can be set for
unnecessary data. For example, for particular messages
with a different number of displayed characters, set 00 so
that the number of data, m, are the same.

261
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.43.5 (a) Message number:


Message Data The specified number produces an appropriate event as follows.
1000 to 1999 (alarm message):
The CNC is put in alarm status and the number and following data
are displayed. The maximum number of the displayed characters
is up to 32, except for the message number. When an alarm status
occurs, the operation being executed stops. To release the alarm
status, set the displayrequest bit (see Fig.5.43.7) to 0.
2000 to 2099 (operator message):
The CNC is not put in alarm status and the number and following
data are displayed. The maximum number of the displayed
characters is 255, except for the message number.
2100 to 2999 (operator message):
The CNC is not put in alarm status and the number is not displayed.
Only the following data (up to 255 characters) is displayed.
50005999 (alarm messages on path 2):
Path 2 is placed in the alarm state. A displayed message number is
a specified number from which 4000 is subtracted. The number of
displayed characters excluding this number is 32 or less. If the
alarm state arises during axis movement, a gradual stop occurs. The
alarm state can be released by setting the display request bit to 0.
70007999 (alarm messages on path 3):
Path 3 is placed in the alarm state. The displayed message number
is a specified number from which 6000 is subtracted. The number
of displayed characters excluding this number is 32 or less. If the
alarm state arises during axis movement, a gradual stop occurs. The
alarm state can be released by setting the display request bit to 0.

NOTE
If all characters in the operator message are kana
characters, up to 254 kana characters are displayed.

(b) Message character


An alphanumeric character is specified with a twodigit decimal
(two characters per step). Table 5.43.6 shows the correspondence
between characters and specified numbers.
The above message data is always specified because it is written on
ROM. The message data cannot therefore be changed as desired.
However, arbitrary numeric data of up to four BCD digits can be
displayed according to the specified variable data. The spindle tool
number which changes whenever ACT tools are changed and the
number of the tool at the toolchange position can be displayed, for
example. For specifying variable data, see 5.42.10 below.

262
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.43.6 W1=0 : Processing ends. Normally, W1=0. If W1=0 after W1=1,


Error Output (W1) processing ends.
W1=1 : In process. W1=1 when ACT=1.

Table 5.43.6 Correspondince between characters and specified numbers


Specified Corresponding Specified Corresponding Specified Corresponding Specified Corresponding
number character number character number character number character
32 (space) 64 160 192
33 65 161 193
34 66 162 194
35 67 163 195
36 68 164 196
37 69 165 197
38 70 166 198
39 71 167 199
40 72 168 200
41 73 169 201
42 74 170 202
43 75 171 203
44 76 172 204
45 77 173 205
46 78 174 206
47 79 175 207
48 80 176 208
49 81 177 209
50 82 178 210
51 83 179 211
52 84 180 212
53 85 181 213
54 86 182 214
55 87 183 215
56 88 184 216
57 89 185 217
58 90 186 218
59 91 187 219
60 92 188 220
61 93 189 221
62 94 190 222
63 95 191 223
*1) minus *2) Under bar *3) Long bar

263
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.43.7 The parameters and message data used by this functional instruction are
Parameters and as follows.
Message Data
SUB49
Total sum of data of message data
Parameter Number of data of one message item
R200 Message control address
(Specify a message to be displayed, using an address of RAM in the internal relay area is
taken to here, R200 is taken.)

Message 1
data Message data 2 is displayed on the CRT screen

Message RAM 7 6 5 4 3 2 1 0
data 2
address
R200 0 0 0 0 0 0 1 0
Display request
Message R201 0 0 0 0 0 0 0 0
data 3
R202 0 0 0 0 0 0 1 0
Display state
R203 0 0 0 0 0 0 0 0

Two bytes of R200 and R201, the address specified in the message control address and
that address plus +1, (display request), are required to specify a message to be displayed.
Even if the number of message data items is small, two bytes are always required. 0 is set to
unnecessary data. 0 is set automatically when the CNC is powered on.
Two bytes of R202 and R203, the specified address plus +2 and the same address plus +3,
(displayed state), show the message displayed on the CRT screen.
Message
n When there is more than one display request, only a prescribed number of message are
data
displayed on the CRT screen. Actually displayed messages are known by the displayed
state. The displayed state is set automatically in the two bytes of the displayed state and can
be referred to by the sequence program. Those bytes must not be written in.

One DISP functional instruction requires the four consecutive bytes


following the address specified in the above message control address
in order to check the display request and displayed status.
When messages are displayed or cleared, message data 1 to n (n x
16) and displayrequest bits correspond to each other as shown in
Fig.5.43.7.
To display and clear a message data item, set the corresponding bit
to 1 and 0, respectively, and the control condition ACT to 1.
If the sequence program checks messages displayed on the screen,
message data 1 to n and displayrequest bits correspond to each other
as shown in Fig.5.43.7.
Message data for which 1 is set among the 16 displayed status bits,
is the message data currently being displayed.

264
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Note) 7 6 5 4 3 2 1 0
Message Message Message Message Message Message Message Message
Specified
data data data data data data data data
address
Display 8 7 6 5 4 3 2 1
request Message Message Message Message Message Message Message Message
Specified
data data data data data data data data
address
16 15 14 13 12 11 10 9
Message Message Message Message Message Message Message Message
Specified
data data data data data data data data
address +2
Display 8 7 6 5 4 3 2 1
state Message Message Message Message Message Message Message Message
Specified
data data data data data data data data
address +3
16 15 14 13 12 11 10 9

Fig. 5.43.7 Correspondence between message data and display request/displayed status

NOTE
Specified address means an address specified in the
message control address of a DISP instruction parameter.

5.43.8 (a) CNC external data input function


Remarks on Using the The DISP instruction displays messages using external data input
DISP Instruction function or external message display, which involves external
worknumber search, external tool offset, external work coordinate
system shift, etc. as well as message display. The DISP instruction
cannot display messages when any of these functions is being
executed. To check this, EPCA (any address in internal relay area)
and EPCB (any address in control relay area) are used as interlock
signal. The sequence program sets EPCA to 1 while the message is
displayed, and to 0 upon competion of processing. The sequence
program sets EPCB to 1 while any function other than the above is
being processed, and to 0 upon completion of processing.
When EPCB = 1, messages must not be displayed (DISP ACT must
not be 1). Set ACT to 1 after making sure that EPCB = 0.
When the function other than message display is executed, execute
after making sure that EPCA = 0. DISP instruction and external data
input function (external tool offset, external work number search)
must be programmed in the same sequence level.
(b) External data input function address
During DISP instruction execution (EPCA = 1), the PMC CNC
interface of the external data input function must not be used for
processing of external tool offset, external worknumber search or
external work coordinate system shifting. If EPCA = 1, use the JUMP
instruction, for example, to skip writing data, so that nothing is
written in the interface.

265
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(c) ACT and W1 of the DISP instruction


(a) Timing of ACT ON
If EPCB = 0, ACT may be set to 1 with any timing. For instance,
when all displayrequest bits are off or when the status displayed
on the screen and the display requests are the same, that is, when
there are no new display requests, even if ACT = 1, the DISP
instruction processes nothing and the operation terminates (W1
= 0).
Even if another displayrequest bit is set on and ACT is set to 1
with a prescribed number of messages (four alarm messages or
one operator messages) displayed on the screen, no message is
displayed for that request, but W1 = 0 after W1 = 1 and W1 = 1
again during execution of the next cycle. In other words, W1 only
changes back and forth between 1 and 0.
(b) Using two or more DISP instructions
If EPCB = 0, ACT of each DISP instruction may be turned on
simultaneously. Until the DISP instruction whose ACT was set
to 1 earlier, has been completed (W1 = 0), executing of the next
DISP instruction is kept waiting. W1 of the DISP instruction kept
waiting remains 0 at this time. Consequently, no messages more
than those specified number are displayed, as discussed in 5.42.1.
From (a) and (b) above, set ACT to 1 whenever EPCB = 0. Do not
set ACT to 1 when EPCB = 1.

266
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.43.9 (a) Display three types of messages with the following conditions.
Examples of Using The SPER = 1 and SPINDLE ALARM (Message data 1)
ATCER = 1 and ACT ALARM (Message data 2)
DISP Instruction WORK = 1 and WORK SET UP (Message data 3)

[Message data specified]


7 6 5 4 3 2 1 0

AddressR220 0 0 0 0 0 MSI AL2 AL1


Display request
R221 0 0 0 0 0 0 0 0

R222 0 0 0 0 0
Display state
SPER R223 0 0 0 0 0 0 0 0
AL1

R220.0
ATCER D SPINDLE ALARM Message data 1 : AL1
AL2 D ATC ALARM Message data 2 : AL2
D WORK SET UP Message data 3 : MS1
R220.1
WORK
MS1

R220.2

EPCB
ACT Whenever EPCB=0, ACT=1

R201.2

DISP Total One Control Messa


sum messag ge
ACT
SUB of es 10 addres
W1 When ACT=1, promptly R1=1, display being begun.
49 message
s
R201.2 s When display is completed, automatically W1=0.
R220
30 R201.3

1 1010 SPINDLE ALARM


2 1020 ATC ALARM
3 2100 WORK SET UP

W1
EP Interlock signal for external data input function
R201.3 CA
R295.0

267
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Step Instruc-
Number tion Address No. Bit No. Remarks ST2 ST1 ST0

RD R201.2 ACT
SUB 49
(PRM) 30 Total sum of data of message data
(PRM) 10 Number of data of one message
(PRM) R220 Message control address
(PRM)
(PRM) 1010 Message No.
8380 SP
7378 IN
6876 DL
6932 E_ Message data 1
6576 AL (10 data m=10)
6582 AR
7700 M
(Note1)
0000
0000
1020 Message No.
6584 AT
6732 C_
6576 AL
Message data 2
6582 AR
(10 data m=10)
7700 M
0000
0000
0000
0000
2100 Message No.
8779 W0
8275 RK
3200 _
Message data 3
0192
(10 data m=10)
0222
0221
0196
0222
(PRM) 0216
ACT
WRT R201.3 Process end (W1) W1
RD R201.3 W1
WRT R295.0 W1

Fig. 5.43.9 (a)

NOTE
1 00 is ignored data.
2 Display example (The following is displayed on the screen in message data 1).
1010 SPINDLE ALARM

268
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(b) Using three DISP instructions and one external tool offset

EPCB
ACT Set ACT to 1 whenever no external tool offset is
being precessed (EPCB=0)

DISP
ACT
W1 1st DISP instruction

DISP
ACT
W2 2nd DISP instruction

DISP
ACT
W3 3rd DISP instruction

W1
EP
CA Use as external tool offset interlock.
W2 EPCA=1 during execution of each DISP
instruction. When EPCA=0, see (8), (iii)
W3

ACT
JMP n Use a JMP instruction, for example, so that no
Jump
external data input interface (addresses) may be
DISP instruction (EPCA=1).

W3

Processing W3
of
external tool offset
Writing into external data input interface

En
External tool
offset start EPCA
condition EP
Always turn EPCB off on completion of external tool
CB
External tool EPCB offset. completion is when processing has been
offset end exactly completed and NC signal REND=0.
condition

Fig. 5.43.9 (b)

269
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.43.10 Conform to the following instruction format. Variable data, i.e., any
Variable Data Display numeric value of up to four BCD digits, can be displayed.
by Specifying Variable
Data SUB49 Instruction format

ffff Total number of steps in message data

ffff Number of steps in one message data item

ffff Message control address


ffff Message number

Message characters

ffff
990m Variable data specification
VVVV Variable data address
ffff Message number

Message characters

ffff
ffff Message number
990m Variable data specification
VVVV Variable data address

Message characters
990m Variable data specification
VVVV Variable data address

NOTE
1 One step is used at variable data specification 990m.
2 The number of steps is the same for each message data
item. The number of characters to be displayed varies
according to the value specified for m.
3 Multiple variable data items can be used in one message
data item.

(1) Specifying variable data


990m

Specifies the number of digits in the variable data.


(1xmx4)

Variable data

270
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(2) Variable data address


VVVV: Address of the area in which variable data is stored
(3) Variable data
Specify variable data consisting of up to four BCD digits (the number
of digits specified for m) to be displayed at the address specified by
the variable data address using the sequence program.
For example, variable data 1234 is specified at variable data address
R300 in BCD as shown below:
AddressR300 0011 0100

R301 0001 0010

(4) Example
To display TOOL NO 123
SUB49
0007 Total number of steps in message data
0007 Number of steps in one message data item
R300 Message control address
2100 Message number
8479 TO
7396 OL
3278 N
7932 O
9903 Variable data specification
R350 Variable data address

AddressR350 0011 0100

R351 0001 0010

271
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.44
DISPB

5.44.1 This instruction displays messages on the CNC screen. You can also
Function specify the message number to generate an alarm in the CNC. This
instruction supports special functions (numerical data display and kanji
character display) in addition to the same basic functions as those of the
message display instruction (DISP), described in Section 5.43.
However, it performs a special additional function, namely, it displays
numerical data.
You can program up to 2000 messages. You must use the special message
addresses in your program (see Chapter 3, Address) to simplify use of
the messages. The following are the features of this function.
(a) In the program you define the total number of messages by using
DISPB, and set ACT=1.It does not matter if ACT is already set at 1.
If, however, ACT = 0, DISPB will not process the messages at all.
When ACT = 1, messages are displayed according to the contents of
the message display request memory (addresses A) and the message
data table.
When multiple messages are requested simultaneously, all the
messages may not be displayed. The display of messages depends on
the number of messages which can be displayed in CNC screen.
In PMCSB7, the status of the messages which is displayed actually
in CNC screen is shown in the message display status memory.
Relation between the message display request memory address and
the message data table appears in Table 5.44.1(a).
Message data table
Message display request memory (RAM) Number of message data table (written in ROM)
Address
7 6 5 4 3 2 1 0 (Messagedata corresponding
A0 A0.0 to address A0.0)
A1
(Messagedata corresponding
A2
A0.1 to address A0.1)

(Maximum) A2
(Messagedata corresponding
(Maximum) A24.7
to address A24.7)

Fig. 5.44.1(a) Message display request memory and message data table

272
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Message display request memory Message data table

7 6 5 4 3 2 1 0 A000.0 (Message data corresponding


A0 0 0 0 0 0 0 1 1 to address A000.0)
A1 0 0 0 0 0 0 0 0 A000.1 (Message data corresponding
A2 0 0 0 0 0 0 0 0 to address A000.1)
|
| ================================
|
=============================
A249 1 0 0 0 0 0 0 0
A249.7
(Message data corresponding
to address A249.7)

Message display status memory

7 6 5 4 3 2 1 0 NC message screen
A9000 0 0 0 0 0 0 1 1 xxxx:(Message of A000.0)
A9001 0 0 0 0 0 0 0 0 yyyy:(Message of A000.1)
A9002 0 0 0 0 0 0 0 0
zzzz:(Message of A249.7)
|
| XXXXXXXXXXXXXXXXXXX
|

A9249 1 0 0 0 0 0 0 0 [ ][ ][ ][ ][ ]

Fig. 5.44.1(b) Message display request memory, message display status memory and Message data table in
PMCSB7

(i) Message display request memory (RAM)


The message display request memory consists bits at A addresses
on each PMC model. One bit corresponds to one type of message
data.
If you want to display a message on the CRT screen, set the
corresponding display request memory 1. Set 0 to erase the
message of CNC screen.
(ii) Message display status memory (PMCSB7)
This memory locates at the address A9000 to A9249 and has
2000bits. Each bit corresponds to a message. While displaying a
message in CNC screen, the corresponding bit is set to 1. The
ladder can not write on this memory.
(iii) Message data table
This table stores messages corresponding to the message display
request bits. The table is stored in the EPROM together with the
sequence program. Message data table numbers correspond to the
message display request memory addresses.
The message data table capacity is prepared by the maximum
capacity of a message, or, 255 characters (255 bytes). Produce a
message data within this capacity.
A character prepared in CRT/MDI key consists of one byte, and
4 bytes are necessary for a message number (consisting of 4
characters) in the next item. A character not covered by the

273
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

CRT/MDI keys requires two bytes (a halfwidth kana character)


or four bytes (a kanji character or other fullwidth character). For
details, see Section 5.44.6.
(iv) Message number
This message number consisting of 4 digits must always be
defined at the start of each message data. The CRT display is as
specified below by this message number.
D FS16M/T, FS18M/T, FS15B, FS15i, FS20, Power
MateD (single path control), Power MateF and Power
MateH
Message CNC Display contents
number screen
1000 to 1999 Alarm message Alarm message
screen D CNC is turned to alarm state.
2000 to 2099 Operator Operator message
message screen
2100 to 2999 Operator message (without message number)
D Only message data, no message number, is
displayed.

D FS16TT and FS18TT


Message CNC Display contents
number screen
1000 to 1999 Alarm message Alarm message
screen (The 1st D The 1st tool post side of CNC is turned to alarm
tool post side) state.
2000 to 2099 Operator Operator message
message screen
2100 to 2999 Operator message (without message number)
5000 to 5999 Alarm message Alarm message
screen (The 2nd D The 2nd tool post side of CNC is turned to alarm
tool post side) state.
D The displayed message number is a value by
witch 4000 is subtracted from specified number.

D For 3path control


Message CNC Display contents
number screen
1000 to 1999 Alarm screen Alarm message
(on path 1) D Path 1 is placed in the alarm state.
2000 to 2099 Operator Operator message
2100 to 2999 message screen Operator message (with no message number)
5000 to 5999 Alarm screen Alarm message
(on path 2) D Path 2 is placed in the alarm state.
D The displayed message number is a specified
number from which 4000 is subtracted.
7000 to 7999 Alarm screen Alarm message
(on path 3) D Path 3 is placed in the alarm state.
D The displayed message number is a specified
number from which 6000 is subtracted.

274
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

D Power MateD (dual path control)


Message CNC Display contents
number screen
1000 to 1999 Alarm message Alarm message
screen (The 1st D The 1st path side of CNC is turned to alarm state.
path side)
2000 to 2099 Operator Operator message
message screen
2100 to 2999 (The 1st path Operator message (without message number)
side)

5000 to 5999 Alarm message Alarm message


screen (The 2nd D The 2nd path side of CNC is turned to alarm state.
path side) D The displayed message number is a value by
witch 4000 is subtracted from specified number.
6000 to 6099 Operator Operator message
message screen D The displayed message number is a value by
(The 2nd path witch 4000 is subtracted from specified number.
side)
6100 to 6999 Operator message (without message number)

Moreover, the DPL/ MDI display with Power Mate is as specified


below by this message number.

D Power MateD (single path control), Power MateF and


Power MateH
Message CNC Display contents
number screen
1000 to 1999 Alarm message Message number
screen D CNC is turned to alarm state.
D Only message number, no message data, is
displayed.
2000 to 2099 Operator Operator message
message screen D Only message data, no message number, is
2100 to 2999 displayed.

D Power MateD (dual path control)


Message CNC Display contents
number screen
1000 to 1999 Alarm message Message number
screen (The 1st D The 1st path side of CNC is turned to alarm state.
path side) D Only message number, no message data, is
displayed.
2000 to 2099 Operator Operator message
message screen D Only message data, no message number, is
2100 to 2999 (The 1st path displayed.
side)

5000 to 5999 Alarm message Message number


screen (The 2nd D The 2nd path side of CNC is turned to alarm state.
path side) D Only message number, no message data, is
displayed.
D The displayed message number is a value by
witch 4000 is subtracted from specified number.
6000 to 6099 Operator Operator message
message screen D Only message data, no message number, is
6100 to 6999 (The 2nd path displayed.
side)

275
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

NOTE
1 The number of message number which you can display at
the same time to the alarm screen on DPL/MDI is up to 3.
2 The number of character which you can display to the
operator message screen on DPL/MDI is up to 32
characters. The message data since the 33rd character is
not displayed.
3 A ~ character (code A0H) is displayed as space character
to the screen on DPL/MDI.
4 The DPL/MDI cannot display kanji (doublebyte) characters.
5 In the FS15i, each alarm message must consist of up to 30
characters.

(b) You need not use numerical codes for message data input. Instead, when
programming, directly key in the characters making up the messages
(from the CRT/MDI keyboard). For the characters that CRT/MDI does
not provide for, you must enter these characters by numerical data with
special symbols @. For details, refer to Subsec. 5.44.6).
(c) Use external data input command (described later) where you must
combine the DISPB instruction with external data input function (for
external tool compensation, external workpiece No. search, etc.).
Such use of the DISPB instruction does not affect the interface of
external data input function though the common interface is used
between DISPB instruction and external data input function.
(d) If you write the message data items in the ROM after programming,
you cannot change them any more (they will become fixed data
items). However, you can still change and display only the numerical
data forming part of the messages if you specify addresses storing the
numerical data as the message data and assign the required numerical
data in these addresses through sequence program.
Use of this function makes it possible for you to display frequently
varying numerical data (such as tool number etc.) during automatic
operations.
(e) A message is displayed on the CNC alarm message/operator message
screen.
When using the DISPB instruction, you must satisfy the following
conditions:
To use DISPB, the optional External Data Input function or External
Message Display is necessary for CNC.

5.44.2
Format
DISPB fff

ACT

(SUB 41) Number of


message

276
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.44.3 ACT=0 : Do not display messages on the CRT.


Conditions ACT=1 : Display the messages on the CRT.

5.44.4 (a) Number of messages


Parameters Specifies the total number of messages (up to 200).

Function PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

Number of 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to 1 to
messages 200 200 200 200 200 200 200 200 200 200 200 1000 2000 200 200 1000 200 1000 1000

5.44.5 To change the numerical data contained within the messages, enter in the
messages the number of digits making up the data and the memory
Numerical Data Display
address to contain the data. To differentiate between the numerical data
from the other message data, write it within [ ] in the message.
Since the brackets, [ ], are used to contain numerical data, they are not
themselves treated as symbols to be included in the messages.
(a) Numerical data format
[Ibid, ffff]

Memory address that the numerical data is stored


The address must be of binary format.

Set the bid data after character I:


b : Number of bytes (1, 2, or 4)
i : Number of digits in the integer part (0 to 8)
d : Number of digits in the fractional part (0 to 8)

NOTE
1 Sum of integer part digits and fractional part digits must be
within 8.
2 Blank is displayed for digits exceeding 8 digits.
3 Do not use any space between the brackets, [ ].

(b) Example
The following message includes 3 digits tool number at the spindle
and the offset data (f.ff) for this tool. And these data are
contained in memory address of 2bytes:
SPINDLE TOOL No. = [I230, VVVV]
OFFSET DATA = [I212, nnnn]

277
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.44.6 Message characters not covered by the CRT/MDI keys (kanji and
Defining Characters halfwidth kana characters) can be input as follows:
not found in the (a) Halfwidth kana characters
CRT/MDI (i) Data format
Numerical code enclosed by @ and @
(ii) Input method
Enter the numerical codes corresponding to the characters to be
input, by referring to the character code table (Table 5.44.6).
Each character requires two bytes. Characters covered by the
CRT/MDI keys can also be input in this way.
(iii) Example
To input ATC? OK when characters A, T, C, O, and
K are registered in the CRT/MDI unit, enter the following:

NOTE
Spaces are used between each numerical code in example
to understand easily, but do not use them actually.

(b) Kanji (fullwidth) characters


: Can be used
: Cannot be used
Power FS20 FS21B FS0i FS21i FS18A FS16A FS16B FS16C FS16i FS15B FS15i
Mate FS21A FS18B FS18C FS18i

PA1 SA1 SA1 SA1 SA1 SA1 SA2 SB SB2 SC SB3 SC3 SB5 SC3 SB5 NB NB2 NB6
PA3 SA3 SA3 SA3 SA5 SA3 SB3 SC3 SB4 SC4 SB6 SC4 SB6
SB7

f f f f f f f f f f f f

NOTE
1 The PMCSA1 for the FS18A can be used when the PMC management software series is
4071.
2 The PMCSB for the FS16A can be used when the PMC management software series is
4063.
3 The PMCSC/SC3 for the FS16A cannot be used depending on the series and edition of the
CNC software.
4 For the FS16A, set the following CNC parameter:
No. 6300 bit 6 = 0: Kanji characters are used for the DISPB instruction (default).
1: Kanji characters are not used for the DISPB instruction.
When kanji characters are used, the DISP instruction cannot be used.
5 On the CNC, the external data input option or external message option must be selected.

(i) Data format


Numerical code enclosed by @02 and 01@
(ii) Input method
Enter the numerical codes corresponding to the characters to be
input, by referring to the kanji, hiragana, and special code table
in Appendix P. Each character requires four bytes.

278
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(iii) Example
To input ATC? OK when characters A, T, C, O, and K are
registered in the CRT/MDI unit, enter the following:
4434 3A3A 01

NOTE
1 To define @, enter @40...@, where 40 is the code
corresponding to @40 . . . . . @
Code for @
2 To renew the message line displayed on the CRT/MDI
screen, input as:@ OA @ at the end of the data.
3 When using numerical codes, @ code occupies 1 byte, and
space code occupies 2 bytes. (Space code = 20, 2 and 0
occupies 1 byte each).
4 The following control codes are used: 02: 2byte code (kanji
and hiragana characters) 01: 1byte code (alphanumeric
and halfwidth kana characters) Do not specify 02 or 01
between @02 and 01@, as follows. The characters may not
be correctly displayed. @02 ... 02 ... 01@ @02 ... 01 ...
01@
5 Spaces are used between each numerical code in example
to understand easily, but do not use them actually.

Table 5.44.6 Character code table

2 3 4 5 A B C D
0 (Space) 0 @ P ~ _ *3)
1 ! 1 A Q
2 # 2 B R
3 # 3 C S
4 $ 4 D T
5 % 5 E U
6 & 6 F V
7 7 G W
8 ( 8 H X
9 ) 9 I Y
A * : J Z
B + ; K [
C , < L
D *1) = M ]
E > N
F / ? O __ *2)
*1) Minus, *2) Under bar, *3) Long bar *4) Dakuten *5) Handakuten

279
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.44.7 See I9.3 for details.


Notes when this
Functional Instruction
is Used in Subroutine

5.44.8
Foreign Language
Display
Power Mate/ FS20/ FS18A FS16A FS16B FS16C FS21i FS16i FS15B FS15i
FS21A FS21B FS18B FS18C FS18i

PA1 SA1 SA1, SA2 SB, SB2, SB3 SB3 SB4 SB5 SB6 SA1 SB5 SB6 NB NB6
PA3 SA3 SA3 SC, SC3 SC3 SC4 SC3 SC4 SA5 SB7 NB2

f f f

(a) General
In the message data areas corresponding to contiguous message
display request memory locations, message data can be displayed in
any of several languages.
The language in which a message is displayed is selected by shifting
the message display request bit according to the address bit shift
amount set in setting parameter 2.

A0.0 Language 1 When A0.0 is turned on after setting the message


A0.1 Language 2 display request bit shift amount to 2, the message
display request bit is shifted by 2 bits to display
A0.2 Language 3 language 3.
A0.3 Language 4
A0.4 Language 5

The parameters set on the setting parameter 2 screen are listed below.
See II4.4.1 for details.
D MESSAGE SHIFT VALUE
Message display request bit shift amount
D MESSAGE SHIFT START ADDRESS
Start bit address of the message display request bit area to be
shifted
(b) Examples
Example 1:
Message data in any of four languages is set starting at A0.0 in
the order of Japanese, English, Italian, German, Japanese and so
on. The Italian message data is displayed.
Set the parameters as follows:
MESSAGE SHIFT VALUE : 2
MESSAGE SHIFT START ADDRESS : A0.0
(MESSAGE SHIFT VALUE =
0:Japanese/1:English/2:Italian/3:German)
Manipulate A0.0, A0.4, A1.0, A1.4, and so forth with the ladder.

280
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Message table
A0.0 Japanese 1
When A0.0 is turned on, Italian 1 is
A0.1 English 1 displayed. (The message data is
A0.2 Italian 1 shifted by 2 bits).
A0.3 German 1
A0.4 Japanese 2
When A0.4 is turned on, Italian 2 is
A0.5 English 2 displayed. (The message data is
A0.6 Italian 2 shifted by 2 bits).

A0.7 German 2
; :
Am.n :

Example 2:
As common alarm messages, English message data is displayed
with A0.0 through A9.7. Operator messages are set starting at
A10.0 in the order of Japanese, English, Italian, German and so
on, and German message data is displayed.
Set the parameters as follows:
MESSAGE SHIFT VALUE : 3
MESSAGE SHIFT START ADDRESS : A10.0
(MESSAGE SHIFT VALUE =
0:Japanese/1:English/2:Italian/3:German)
Manipulate A10.0, A10.4, A11.0, A11.4, and so forth with the
ladder.
When any of A0.0 to A9.7 is turned on, the message
corresponding to the bit is displayed.

Message table
A0.0 English A (ALARM)
A0.1 English B (ALARM) When A0.1 is turned on, Eng-
lish B is displayed.
A0.2 English C (ALARM)

A10.0 Japanese 1 (OPE) When A10.0 is turned on, Ger-


man 1 is displayed. (The mes-
A10.1 English 1 (OPE) sage data is shifted by 3 bits).
A10.2 Italian 1 (OPE)
A10.3 German 1 (OPE)
A10.4 Japanese 2 (OPE) When A10.4 is turned on, Ger-
A10.5 English 2 (OPE) man 2 is displayed. (The mes-
sage data is shifted by 3 bits).
A10.6 Italian 2 (OPE)
A10.7 German 2 (OPE)

: :
: :
A m.n :

281
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Example 3:
As common alarm messages, English message data is displayed
with A0.0 through A9.7. Operator messages are set starting at
A10.0 in the order of Japanese, English, Italian, German and so
on, with 40 successive messages assigned to each language. For
these messages, German message data is displayed.
Set the parameters as follows:
MESSAGE SHIFT VALUE : 120 (40 x 3)
MESSAGE SHIFT START ADDRESS : A10.0
(MESSAGE SHIFT VALUE =
0:Japanese/40:English/80:Italian/120:German)
Manipulate A10.0 through A14.7 with the ladder.
When any of A0.0 to A9.7 is turned on, the message
corresponding to the bit is displayed.

Message table

A0.0 English A (ALARM)


A0.1 English B (ALARM) When A0.1 is turned on, Eng-
A0.2 English C (ALARM) lish B is displayed.

When A10.0 is turned on, Ger-


A10.0 Japanese 1 (OPE)
man 1 is displayed.
A10.1 Japanese 2 (OPE)
When A10.1 is turned on, Ger-
man 2 is displayed.
A15.0 English 1 (OPE)
(The message data is shifted by
A15.1 English 2 (OPE) 120 bits).

A20.0 Italian 1 (OPE)


A20.1 Italian 2 (OPE)

A25.0 German 1 (OPE)


A25.1 German 2 (OPE)

: :
Am.n :

(c) Notes
The same message number should be assigned to a message in each
language that has the same meaning.
Message table
A0.0 1000 English A (ALARM)
A0.1 1001 English B (ALARM)

A10.0 1000 Japanese 1 (OPE)


A10.1 1001 Japanese 2 (OPE)

282
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.45
EXIN (EXTERNAL
DATA INPUT)

5.45.1 This instruction is used for external data (external tool compensation,
Function external message function, external program number search, external
workpiece coordinates shift, etc.) input. You must use this instruction
when combining the message display instruction (DISP, DISPB) with the
external data input function. If you are not used DISP or DISPB, you need
not use this instruction either. Instead, use the external data input interface
from PMC to NC directly in your program.
The DISPB instruction uses the interface from PMC to NC provided by
the external data input function during display. The DISP instruction
prevents the interface signal transferred from the PMC to NC from being
changed due to external cutter compensation or others.
You can use the EXIN instruction only when the PMCNC interface is
of BMI (Basic Machine Interface) and optional external data input
function is provided with NC.
An 4byte control data as described below is required for external data
input function (option).
In PMCSA5/SB5/SB6/SB7, the expended specification that needs 6
bytes of control data is supported. With this setting, the extended
operation can use ED16 to ED31 signals (for program number O8 digits
etc.). To use the extended specification, it is necessary to set to NC
parameter 6300#7 (EEXIN)=1.
D NC parameter
(FS16i/18i/21i) #7 #6 #5 #4 #3 #2 #1 #0
6300 EEXIN

data format : bit type


EEXIN : EXIN function of PMC
0 : basic specification
1 : extended specification

NOTE
To use program number O8 digits, the option with program
number O8 digits and NC parameter 6300#7 (EEXIN)=1 are
necessary.

283
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.45.2
Format
ACT
EXIN ffff
W1
(SUB 42)
Control data
address

Fig. 5.45.2 EXIN instruction format

5.45.3 ACT=0 : Do not process external data input/output.


ACT=1 : Process external data input/output.
Control Conditions
ACT is to be maintained 1 till the end of external data input/output. After
external data input, reset ACT (W1 = 1).

5.45.4 (a) Control data (except PMCNB/NB2/NB6)


Parameter The control data needs 4 continuous bytes from the specification
address. The path is specified to the 1st byte. The addresses G0 to
G2 of the interface from PMC to NC are specified by after 3 bytes.
For 2nd path, the addresses G1000 to G1002 are specified. Fot 3rd
path, the addresses G2000 to G2002 are specified. (Be sure to set the
strobe signal (ESTB) to ON.)
In PMCSA5/SB5/SB6/SB7, in case of the extended specification
(program number O8 digits etc.), a control data is extended. In this
case, the control data address needs 6 continuous bytes from the
specified address. THe path is specified in the 1st byte. The
addresses G0 to G2 and G210 to G211 of the interface from PMC to
NC are specified in later 5 bytes. For 2nd path, the addresses G1000
to G1002 and G1210 to G1211 are specified. For 3rd path, the
addresses G2000 to G2002 and G2210 to G2111 are specified. (Be
sure to set the strobe signal (ESTB) to ON.)
Basic specification Extended specification
(program number O8 digits etc.)
CTL+0 CTL+0
HEAD NO. HEAD NO.
+1 +1
ED0 to ED7 ED0 to ED7
+2 +2
ED8 to ED15 ED8 to ED15
+3 +3
EA0 to EA6, ESTB ED16 to ED23
+4 +4
ED24 to ED31
+5
EA0 to EA6, ESTB
+6

284
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

[For single path control]


CTL+0 : 0
CTL+1 to CTL+3 : Data to be specified for G0 to G2
In case of the extended specification (program number O8 digits
etc.), it sets CTL+1 to CTL+5 as follows.
CTL+1 to CTL+2 : Data to be specified for G0 to G1
CTL+3 to CTL+4 : Data to be specified for G210 to G211
CTL+5 : Data to be specified for G2
[For multi path control]
(i) 1st path
CTL+0 : 0
CTL+1 to CTL+3 : Data to be specified for G0 to G2
In case of the extended specification (program number O8 digits
etc.), it sets CTL+1 to CTL+5 as follows.
CTL+1 to CTL+2 : Data to be specified for G0 to G1
CTL+3 to CTL+4 : Data to be specified for G210 to G211
CTL+5 : Data to be specified for G2
(ii) 2nd path
CTL+0 : 2
CTL+1 to CTL+3 : Data to be specified for G1000 to G1002
In case of the extended specification (program number O8 digits
etc.), it sets CTL+1 to CTL+5 as follows.
CTL+1 to CTL+2 : Data to be specified for G1000 to G1001
CTL+3 to CTL+4 : Data to be specified for G1210 to G1211
CTL+5 : Data to be specified for G1002
(iii) 3rd path
CTL+0 : 3
CTL+1 to CTL+3 : Data to be specified for G2000 to G2002
In case of the extended specification (program number O8 digits
etc.), it sets CTL+1 to CTL+5 as follows.
CTL+1 to CTL+2 : Data to be specified for G2000 to G2001
CTL+3 to CTL+4 : Data to be specified for G2210 to G2211
CTL+5 : Data to be specified for G2002

NOTE
Refer to the Series 16 or 18 Connection Manual for
detailed data to be specified concerning external data input.

(b) Control data (PMCNB/NB2/NB6)


When the external input function is used.
A consecutive area in eight bytes is necessary as the control data.
In 15 M/ T, set command data in this CTL+0 +7 by the same data
form as G32 39 of BMI interface.
In 15 TT, set command data in this CTL+0 +7 by the same data
form as G112 119 of BMI interface.

285
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

CTL+0
EISTB, EOREND etc.
+1
EIA0 to EIA7
+2
EID32 to EID39
+3
EID40 to EID47
+4
EID0 to EID7
+5
EID8 to EID15
+6
EID16 to EID23
+7
EID25 to EID31

When the external output function is used.


A consecutive area in 16 bytes is necessary as the control data.
In 15M/T, set command data in first CTL+0 +7 by the same data
form as G3239 of BMI interface. The data output from NC is written
in CTL+8 +15 in the same data form as BMI interface F3239.
In 15TT, set command data in first CTL+0 +7 by the same data form
as G112119 of BMI interface. The data output from NC is written in
CTL+8 +15 in the same data form as BMI interface F112119.

CTL+0 to to
EISTB, EOREND etc CTL+8
+1 EOSTB, EIREND etc
EIA0 to EIA7 +9
+2 EOA0 to EOA7
EID32 to EID39 +10
+3 EOD32 to EOD39
EID40 to EID47 +11
+4 EOD40 to EOD47
EID0 to EID7 +12
+5 EOD0 to EOD7
EID8 to EID15 +13
+6 EOD8 to EOD15
EID16 to EID23 +14
+7 EOD16 to EOD23
EID25 to EID31 +15
EOD25 to EOD31
to to

NOTE
Refer to the following manuals in detail of BMI interface.
FANUC Series 15MODEL B Connection Manual (BMI
interface)
FANUC Series 15i/150iMODEL A Connection Manual
(Function)

286
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.45.5 This indicates end of transfer of external data. This transfer end condition
End of Transfer (W1) shows the end of a series of external data input sequence. This functional
instruction executes a series of transfer sequence, and finally sets ESTB
= 0 in the PMC NC interface. As a result, W1 is set to 1 (W1 = 1) after
confirming that EREND = 0.
When W1 = 1, transfer of data is over. Reset ACT now.

CAUTION
1 The EXIN command cannot input multiple external data items
at the same time. Be sure to issue the next EXIN command
(ACT = 1) after external data transfer ends (W1 = 1).
2 Be sure to specify an interlock when the external data input function
is used by commands other than the function commands, DISP,
DISPB, and EXIN.

5.45.6 If any of the following errors occurs during external data input, the bit in
the operation output register is set. In this case, external data transfer ends
Operation Output
(W1 = 1).
Register
7 6 5 4 3 2 1 0
R9000

EXIN error

(Description of errors)
D When the EXIN command (ACT = 1) is started, the strobe signal
(ESTB) or EREND signal is already on. The external data may be
input by commands other than the function commands, DISP,
DISPB, and EXIN.
D An invalid head number was specified for 16TT or 18TT. (Data
other than 0 to 2 was specified.)
D The specification of HEAD.NO is incorrect.
(Data other than 0 to 3 is set for 3path control.)

5.45.7 See I9.3 for details.


Notes when this
Functional Instruction
is Used in Subroutine

287
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.46
WINDR (READING
CNC WINDOW DATA)

5.46.1 This function reads various data items via the window between the PMC
Function and the CNC.
The WINDR is classified into two types. One type completes reading
a data during one scan time. Another type completes reading a data during
a few scan time. The former is called the function of a highspeed
response and the latter is called the function of a lowspeed response.

5.46.2
Format

ACT W1

WINDR Control
data
(SUB 51) address

Fig. 5.46.2

5.46.3 ACT=0 : The WINDR function is not executed.


Control Condition ACT=1 :The WINDR function is executed. Using the function of a
highspeed response, it is possible to read the data continuously
by always keeping ACT on. However, using the function of a
lowspeed response, as soon as reading a data is completed,
reset ACT once (ACT=0).

5.46.4 (a) Control data address


Parameter The PMC byte address is used to specify the area where control data
is stored.

288
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.46.5
Control Data CTL+0 Function code * Set the control data area by sequence
program before executing the WINDR
+2 Completion code or WINDW.
+4 Data length

+6 Data number

+8 Data attribute
* Only the size of the read data is
+10 Read data necessary for the data area below to to
CTL+10 usually.

+n

See Appendixies B to F WINDOW FUNCTION DESCRIPTION.

CAUTION
1 In the functional instructions WINDR and WINDW, the
control data area may be temporarily rewritten. Therefore,
set the control data area by sequence program before the
WINDR or WINDW is executed even when you specify
the none volatile memory area like D address for the
control data area. Because, when the power supply is
turned off during the control data is rewritten, this rewritten
data may be memorized in a none volatile memory.
Therefore, note that the WINDR or WINDW might be
executed with the wrong control data when the power
supply is turned on next if the control data area is not set by
sequence program.
2 Set the control data in the same program level as the
WINDR or WINDW is executed. If you set the control data
in the different program level, note that the WINDR or
WINDW might not be executed correctly, because the
control data is rewritten during the execution of WINDR or
WINDW.
3 In the diagnosis screen, it might be seen that the value of
control data is changing. This is not abnormal. Because the
display processing and the execution processing of a
sequence program are asynchronously executed.
Therefore, the value when the control data is rewritten
(abovementioned) is occasionally displayed. Even in this
case, the WINDR or WINDW is executed correctly.

289
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.46.6 W1=0 : W1 is usually reset. The W1=0 indicates that the WINDR
Reading Completion is not executed or the WINDR being executed now.
W1=1 : W1 is set when the reading a data is completed by the reading
(W1) command (ACT=1). If the function of a lowspeed response is
used, as soon as reading a data is completed, reset ACT
(ACT=0).

5.46.7 If an error occurs during execution of the WINDR or WINDW, the


bit in the operation output register is set. At the same time, the reading
Operation Output
completion is set (W1=1). Details of the error are output to the completion
register code (CTL+2) in the control data area. See Appendixies B to F WINDOW
FUNCTION DESCRIPTION.

7 6 5 4 3 2 1 0
R9000

WINDR error

5.46.8 When you use the function of a lowspeed response, there are a few
Notes when this limitation. Refer to I9.3 NOTE FOR SUBROUTINES WHEN YOU
USE SUBROUTINES When you use the function of a highspeed
Functional Instruction response, there is no limitation.
is Used in Subroutine

290
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.47
WINDW (WRITING
CNC WINDOW DATA)

5.47.1 This function writes various data items via the window between the PMC
Function and the CNC.

5.47.2
Format

ACT W1

WINDW Control
data
(SUB 52) address

Fig. 5.47.2

5.47.3 ACT=0 : The WINDW function is not executed.


Control Condition ACT=1 :The WINDW function is executed. As soon as writing a data is
completed, reset ACT once (ACT=0).

5.47.4 (a) Control data address


Parameter The PMC byte address is used to specify the area where control data
is stored.

291
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.47.5
Control Data * Set the control data area by sequence
CTL+0 Function code
program before executing the
+2 Completion code WINDR or WINDW.

+4 Data length

+6 Data number

+8 Data attribute

+10 Writing data

+42

See Appendixies B to F WINDOW FUNCTION DESCRIPTION.

CAUTION
1 In the functional instructions WINDR and WINDW, the
control data area may be temporarily rewritten. Therefore,
set the control data area by sequence program before the
WINDR or WINDW is executed even when you specify
the none volatile memory area like D address for the
control data area. Because, when the power supply is
turned off during the control data is rewritten, this rewritten
data may be memorized in a none volatile memory.
Therefore, note that the WINDR or WINDW might be
executed with the wrong control data when the power
supply is turned on next if the control data area is not set by
sequence program.
2 Set the control data in the same program level as the
WINDR or WINDW is executed. If you set the control data
in the different program level, note that the WINDR or
WINDW might not be executed correctly, because the
control data is rewritten during the execution of WINDR or
WINDW.
3 In the diagnosis screen, it might be seen that the value of
control data is changing. This is not abnormal. Because the
display processing and the execution processing of a
sequence program are asynchronously executed.
Therefore, the value when the control data is rewritten
(abovementioned) is occasionally displayed. Even in this
case, the WINDR or WINDW is executed correctly.

292
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.47.6 W1=0 : W1 is usually reset. The W1=0 indicates that the


Writing Completion WINDW is not executed or the WINDW being executed
now.
(W1) W1=1 : W1 is set when the writing a data is completed by the writing
command (ACT=1). As soon as writing a data is completed,
reset ACT (ACT=0).

5.47.7 If an error occurs during execution of the WINDR or WINDW, the


bit in the operation output register is set. At the same time, the writing
Operation Output
completion is set (W1=1). Details of the error are output to the completion
Register code (CTL+2) in the control data area. See Appendixies B to F WINDOW
FUNCTION DESCRIPTION.

7 6 5 4 3 2 1 0

R9000

WINDW error

5.47.8 When you use the function of a lowspeed response, there are a few
Notes when this limitation. Refer to I9.3 NOTE FOR SUBROUTINES WHEN YOU
USE SUBROUTINES
Functional Instruction
is Used in Subroutine

293
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.48
ARBITRARY
FUNCTIONAL
INSTRUCTIONS

5.48.1
FNC 90 to 97
(Arbitrary Functional
Instructions) (Only for
PMCRC/RC3/NB/NB2)

5.48.1.1 These functional instructions (SUB90 to SUB97) are used to execute the
Function arbitrary functional instructions. These instructions consist of the
addresses specifying the start condition, process end output, and control
condition.

5.48.1.2 Fig.5.48.1.2 shows the notation format. Table 5.48.1.2 shows the coding
Format format.

ACT SUB90 ffffffff


W1

FNC 90 Control data


address

Fig. 5.48.1.2 FUNC 90 notation format

Table 5.48.1.2 FUNC 90 coding format

Step Com- Address


Bit No. Remarks
number mand No.
1 RD ffff. f ACT
2 SUB 90 FUNC90 command
3 (PRM) ffff Control data address
4 WRT ffff. f W1

5.48.1.3 (a) Execution command (ACT)


Control Condition This is used as the start condition of an arbitrary functional
instruction.

5.48.1.4 (a) Control data address


Parameter Specifies the first address in the control data area.

294
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.48.1.5 Set the control data to be used by an arbitrary functional instruction.


Control Data If the control data is determined as follows, for example, the person who
created the ladder program determines a control address to set the control
data using the ladder program.

Control data 7 2 1 0
addres
CTL + 0 CNO UPDOWN RST

CTL + 1

CTL + 2
Counter number
CTL + 3

5.48.1.6 This is used as the process end output of an arbitrary functional


Process End Output instruction.
(W1)
NOTE
If this functional instruction is displayed by the PCLAD
display function, an arbitrary functional instruction is
displayed as SUB9X, FNC99X.

295
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.48.2
Creating an Arbitrary
Function

5.48.2.1 (a) Execution command (ACT)


Arbitrary Functional The contents of the execution command can be referenced by bit 1
at R9010.
Instruction and Interface
(b) Control data address
The address where the control data is stored can be referenced in the
byte address format at R9012 or later.
(c) Process end output (W1)
The data output when the process terminates can be referenced by bit
1 at R9011.

5.48.2.2
Use of the R Field
Execution command data
R9010 97 96 95 94 93 92 91 90

R9011 97 96 95 94 93 92 91 90 Process end output data

R9012 Control data address of SUB90 Byte address

R9014 Control data address of SUB91

R9026 Control data address of SUB97

5.48.2.3 Reference the start condition (ACT) of the arbitrary function by bit 1 at
Creating an Arbitrary R9010. Reference the address at which the control data is stored in the
byte address format by the fields at R9012 and later. Set the end signal
Function
(W1) of an arbitrary function in bit 1 at R9011. For example, to execute
the arbitrary function using SUB90, reference the start condition by
R9010.0. Reference the control data address in the byte address format
by R9012. Set the end signal at R9011.0.

296
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.49
MMCWR (READING
MMC WINDOW DATA)
(OTHER THAN
PMCPA1/PA3)

5.49.1 This command reads up to 32 bytes of data via the window between PMC
and MMC. The data can be determined as required between the PMC
Function
ladder program and MMC application program.

5.49.2
Format

MMCWR ffff ffff


ACT
Input data Input data W1
length address
(SUB98) address

Fig. 5.49.2 MMCWR instrument format


Table 5.49.2 MMCWR coding format coding sheet

Step Com- Address


number mand No. Bit No. Remarks

1 RD fff. f ACT
2 SUB 98
3 (PRM) ffff Input data length address
4 (PRM) ffff. Input data address
5 WRT fff. f W1, processing completion

5.49.3 ACT=0 : The MMCWR function is not executed.


Control Condition ACT=1 : The MMCWR function is executed. Hold ACT = 1 until
processing is completed and specify ACT = 0 immediately after
processing is completed (W1 = 1).

5.49.4 (a) Input data length address (two bytes)


Parameters Specifies the length of input data transferred from MMC. When
transfer is completed, the length of data actually transferred is stored.
The maximum data length is 32 bytes.
(b) Input data address
Specifies the area containing data transferred from MMC. An area
large enough for the specified input data length is required.

297
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.49.5 W1=0 : This value is usually set. W1 = 1 indicates that processing is


Processing Completion completed. As soon as processing is completed, specify
ACT=0.
(W1) W1=1 : This value is set when data transfer from MMC is completed or
if an error occurs.

5.49.6 If an MMC window transfer error occurs, the bit in the operation output
register is set to indicate the error. If an error occurs, the transferred data
Operation Output
is not stored in the input data area.
Register
7 6 5 4 3 2 1 0

R9000

MMCWR error

5.49.7 The completion status information is specified in R9002 and R9003. The
completion codes and contents, W1, and error bits are as follows:
Completion Status
11 Initialization at MMC is not completed.
Information (W1 = 0, R9000#0 = 0)
10 Processing is in progress (W1 = 0, R9000#0 = 0)
0 Processing is completed.(W1 = 1, R9000#0 = 0)
2 Data length error (W1 = 1, R9000#0 = 1)
(0, a negative value, or a value exceeding 33 bytes was specified
for the data length. The length of data actually transferred
exceeded the specified value.)
6 MMC is not provided (W1 = 1, R9000#0 = 1)

5.49.8 Refer to Sec. I9.3.


Notes when this
Functional Instruction
is Used in Subroutine

298
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.50
MMCWW (WRITING
MMC WINDOW DATA)
(OTHER THAN
PMCPA1/PA3)

5.50.1 This command writes data containing up to 32 bytes via the window
Function between PMC and MMC. The data can be determined as required
between the PMC ladder program and MMC application program.

5.50.2
Format

MMCWW ffff ffff


ACT
Output data Output data W1
length address
(SUB99) address

Fig. 5.50.2 MMCWW instruction format

Table 5.50.2 MMCWW coding format coding sheet

Step Com- Address


number mand No. Bit No. Remarks

1 RD fff. f ACT
2 SUB 99
3 (PRM) ffff Output data length address
4 (PRM) ffff. Output data address
5 WRT fff. f W1, processing completion

5.50.3 ACT=0 : The MMCWW function is not executed.


Control Condition ACT=1 : The MMCWW function is executed. Hold ACT = 1 until
processing is completed and specify ACT = 0 immediately after
processing is completed.

5.50.4 (a) Output data length address (two bytes)


Parameters Specifies the length of output data transferred to MMC. The maximum
data length is 32 bytes.
(b) Output data address
Specifies the area storing data to be transferred to MMC. An area
large enough for the specified output data length is required.

299
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.50.5 W1=0 : This value is usually set. W1 = 1 indicates that processing is


Processing Completion completed. As soon as processing is completed, specify
ACT=0.
(W1) W1=1 : This value is set when data transfer to MMC is completed or if
an error occurs.

5.50.6 If an MMC window transfer error occurs, the bit in the operation output
register is set to indicate the error. If an error occurs, the transferred data
Operation Output
is not transferred to MMC.
Register
7 6 5 4 3 2 1 0

R9000

MMCWW error

5.50.7 The completion status information is specified in R9002 and R9003. The
completion codes and contents, W1, and error bits are as follows:
Completion Status
11 Initialization at MMC is not completed.(W1 = 0, R9000#0 = 0)
Information 10 Processing is in progress.(W1 = 0, R9000#0 = 0)
0 Processing is completed. (W1 = 1, R9000#0 = 0)
2 Data length error (W1 = 1, R9000#0 = 1)
(0, a negative value, or a value exceeding 33 bytes was specified
for the data length.)
6 MMC is not provided. (W1 = 1, R9000#0 = 1)

5.50.8 Refer to Sec. I9.3.


Notes when this
Functional Instruction
is Used in Subroutine

300
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.51 f : Can be used


: Cannot be used
MOVB (TRANSFER PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

OF 1 BYTE) f f f f f f f f f f f f f

5.51.1 The MOVB instruction transfers 1byte data from a specified source
address to a specified destination address.
Function

5.51.2
Format ACT
MOVB Transfer Transfer
source destinatio
address n address
SUB 43

Fig. 5.51.2 MOVB instruction format

5.51.3 (a) Execution specification


ACT=0 : No data is transferred.
Control Conditions
ACT=1 : Onebyte data is transferred.

301
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.52 f : Can be used


: Cannot be used
MOVW (TRANSFER PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

OF 2 BYTES) f f f f f f f f f f f f f

5.52.1 The MOVW instruction transfers 2byte data from a specified source
address to a specified destination address.
Function

5.52.2
Format ACT
MOVW Transfer Transfer
source destinatio
address n address
SUB 44

Fig. 5.52.2 MOVB instruction format

5.52.3 (a) Execution specification


ACT=0 : No data is transferred.
Control Conditions
ACT=1 : Twobyte data is transferred.

302
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.53 f : Can be used


: Cannot be used
MOVN (TRANSFER PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

OF AN ARBITRARY f f f f f f f f f f f f f

NUMBER OF BYTES)

5.53.1 The MOVN instruction transfers data consisting of an arbitrary number


of bytes from a specified source address to a specified destination address.
Function

5.53.2
Format ACT
MOVN Number of Transfer Transfer
bytes to be source destinatio
transferred address n address
SUB 45

5.53.3 (a) Execution specification


Control Conditions ACT=0 : No data is transferred.
ACT=1 : A specified number of bytes are transferred.

5.53.4 (a) Number of bytes to be transferred


Specify the number of bytes to be transferred. An odd number can
Parameters
also be specified. A number from 1 to 9999 can be specified.

NOTE
With the PMCPA3/SA3/SB3/SB4/SC3/SC4/NB/NB2, a
value from 1 to 200 must be set as the number of transferred
bytes.

303
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.54 f : Can be used


: Cannot be used
MOVD (TRANSFER PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

OF 4 BYTES) f

5.54.1 The MOVD instruction transfers 4 bytes data from a specified source
address to a specified destination address.
Function

5.54.2
Format
ACT Transfer Transfer
MOVD
source destination
SUB47
address address

5.54.3 ACT=0: No data is transferred.


Control Conditions ACT=1: A specified number of bytes are transferred.

304
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.55 f : Can be used


: Cannot be used
DIFU (RISING EDGE PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

DETECTION) f f f f f f f f f f f f f

5.55.1 The DIFU instruction sets the output signal to 1 for one scanning cycle
Function on a rising edge of the input signal.

5.55.2
Format ACT OUT
DIFU Rising f
edge
SUB 57 number

5.55.3 (a) Input signal


Control Conditions On a rising edge (01) of the input signal, the output signal is set to
1.
(b) Output signal
The output signal level remains at 1 for one scanning cycle of the
ladder level where this functional instruction is operating.

5.55.4 (a) Rising edge number


Parameters Model PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2

Rising edge _ 1 to _ _ 1 to 1 to _ _ 1 to 1 to 1 to 1 to 1 to _ 1 to 1 to 1 to 1 to
number 256 256 256 256 500 256 500 1000 256 500 256 500

WARNING
If the same number is used for another DIFU instruction or
a DIFD instruction (described later) in one Ladder diagram,
operation is not guaranteed.

5.55.5
Operation 1 2 3 4 Execution period

ACT

OUT

305
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.56 f : Can be used


: Cannot be used
DIFD (FALLING EDGE PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

DETECTION) f f f f f f f f f f f f f

5.56.1 The DIFD instruction set the output signal to 1 for one scanning period
Function on a falling edge of the input signal.

5.56.2
Format ACT OUT
DIFD Falling f
edge
SUB 58 number

5.56.3 (a) Input signal


On a falling edge(10)of the input signal, the output signal is set to 1.
Control Conditions
(b) Output signal
The output signal level remains at 1 for one scanning period of the
ladder level where this functional instruction is operating.

5.56.4 (a) Falling edge number


Parameters Model PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2

Falling edge _ 1 to _ _ 1 to 1 to _ _ 1 to 1 to 1 to 1 to 1 to _ 1 to 1 to 1 to 1 to
number 256 256 256 256 500 256 500 1000 256 500 256 500

WARNING
If the same number is used for another DIFD instruction or
a DIFU instruction (described above) in one ladder diagram,
operation is not guaranteed.

5.56.5
Operation 1 2 3 4 Execution period

ACT

OUT

306
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.57 f : Can be used


: Cannot be used
EOR PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

(EXCLUSIVE OR) f f f f f f f f f f f f f

5.57.1 The EOR instruction exclusiveORs the contents of address A with a


constant (or the contents of address B), and stores the result at address C.
Function

5.57.2
Format ACT
EOR Format Address Constant or Address
specification A address B C
SUB 59

5.57.3 (a) Input signal


Control Conditions ACT=0 : The EOR instruction is not executed.
ACT=1 : The EOR instruction is executed.

5.57.4 (a) Format specification


Parameters Specify a data length (1, 2, or 4 bytes), and an input data format
(constant or address specification).

Data length specification


Format specification 1 : 1 byte
0 : Constant 2 : 2 bytes
1 : Address specification 4 : 4 bytes

(b) Address A
Input data to be exclusiveORed. The data that is held starting at this
address and has the data length specified in format specification is
treated as input data.
(c) Constant or address B
Input data to be exclusiveORed with. When address specification
is selected in format specification, the data that is held starting at this
address and has the data length specified in format specification is
treated as input data.
(d) Address C
Address used to store the result of an exclusive OR operation. The
result of an exclusive OR operation is stored starting at this address,
and has the data length specified in format specification.

307
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.57.5 When address A and address B hold the following data:


Operation
Address A 1 1 1 0 0 0 1 1

Address B 0 1 0 1 0 1 0 1

The result of the exclusive OR operation is as follows:

Address C 1 0 1 1 0 1 1 0

308
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.58 f : Can be used


: Cannot be used
LOGICAL AND PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.58.1 The AND instruction ANDs the contents of address A with a constant (or
Function the contents of address B), and stores the result at address C.

5.58.2
Format ACT
AND Format Address Constant Address
specification A or C
SUB 60 address B

5.58.3 (a) Input signal


ACT=0 : The AND instruction is not executed.
Control Conditions
ACT=1 : The AND instruction is executed.

5.58.4 (a) Format specification


Specify a data length (1, 2, or 4 bytes), and an input data format
Parameters
(constant or address specification).

Data length specification


Format specification 1 : 1 byte
0 : Constant 2 : 2 bytes
1 : Address specification 4 : 4 bytes

(b) Address A
Input data to be ANDed. The data that is held starting at this address
and has the data length specified in format specification is treated as
input data.
(c) Constant or address B
Input data to be ANDed with. When address specification is selected
in format specification, the data that is held starting at this address
and has the data length specified in format specification is treated as
input data.
(d) Address C
Address used to store the result of an AND operation. The result of
an AND operation is stored starting at this address, and has the data
length specified in format specification.

309
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.58.5 When address A and address B hold the following data:


Operation
Address A 1 1 1 0 0 0 1 1

Address B 0 1 0 1 0 1 0 1

The result of the AND operation is as follows:

Address C 0 1 0 0 0 0 1 0

310
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.59 f : Can be used


: Cannot be used
LOGICAL OR PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.59.1 The OR instruction ORs the contents of address A with a constant (or the
Function contents of address B), and stores the result at address C.

5.59.2
Format ACT
OR Format Address Constant Address
specification or
A C
address
SUB 61 B

5.59.3 (a) Input signal


ACT=0 : The OR instruction is not executed.
Control Conditions
ACT=1 : The OR instruction is executed.

5.59.4 (a) Format specification


Parameters Specify a data length (1, 2, or 4 bytes), and an input data format
(constant or address specification).

Data length specification


Format specification 1 : 1 byte
0: Constant 2 : 2 bytes
1 : Address specification 4 : 4 bytes

(b) Address A
Input data to be ORed. The data that is held starting at this address
and has the data length specified in format specification is treated as
input data.
(c) Constant or address B
Input data to be ORed with. When address specification is selected
in format specification, the data that is held starting at this address
and has the data length specified in format specification is treated as
input data.
(d) Address C
Address used to store the result of an OR operation. The result of an
OR operation is stored starting at this address, and has the data length
specified in format specification.

311
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.59.5 When address A and address B hold the following data:


Operation
Address A 1 1 1 0 0 0 1 1

Address B 0 1 0 1 0 1 0 1

The result of the OR operation is as follows:

Address C 1 1 1 1 0 1 1 1

312
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.60 f : Can be used


: Cannot be used
NOT (LOGICAL NOT) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.60.1 The NOT instruction inverts each bit of the contents of address A, and
stores the result at address B.
Function

5.60.2
Format ACT
NOT Format Address Address B
specification
A
SUB 62

5.60.3 (a) Input signal


ACT=0 : The NOT instruction is not executed.
Control Conditions
ACT=1 : The NOT instruction is executed.

5.60.4 (a) Format specification


Specify a data length (1, 2, or 4 bytes).
Parameters

Data length specification


1 : 1 byte
2 : 2 bytes
4 : 4 bytes

(b) Address A
Input data to be inverted bit by bit. The data that is held starting at
this address and has the data length specified in format specification
is treated as input data.
(c) Address B
Address used to output the result of a NOT operation. The result of
a NOT operation is stored starting at this address, and has the data
length specified in format specification.

313
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.60.5 When address A holds the following data:


Operation
Address A 1 1 1 0 0 0 1 1

The result of the NOT operation is as follows:

Address B 0 0 0 1 1 1 0 0

314
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.61 f : Can be used


: Can be used (with some restrictions)
MMC3 R : Cannot be used

(MMCIII WINDOW PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

DATA READ) f f f f f f f f f f f f

NOTE
This functional instruction cannot be used with SA1 of the
Series 16i/18i/21iMODEL A/B and Series 15i.

5.61.1 The MMC3R instruction reads MMCIII application data via a


PMCMMC window. Which buffer in the MMCIII is to be read can be
Function
specified. The contents of read data can be freely determined by a PMC
Ladder program and MMCIII application program.

CNC Buffer 1
PMC PMC data Buffer 1 MMCIII
Offset

Data length

Buffer n
n = maximum of 10

5.61.2
Format

ACT W1
MMC3R Buffer Offset from Data length Input data f
specification the beginning
SUB 88 of the buffer

5.61.3 ACT=0 : The MMC3R instruction is not executed.


ACT=1 : Data is read.
Control Conditions
(ACT)

315
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.61.4 (a) Address for storing buffer specifications (2 bytes)


Parameters A buffer from which data is to be read is specified. Up to 10 buffers
can be specified. Specify the address where the buffer specification
is held.

NOTE
For the method of buffer registration, refer to the relevant
MMCIII manual.

(b) Address for storing an offset from the beginning of a buffer (2 bytes)
An offset from the beginning of a read buffer is specified. Specify
the address where the offset is held.
(c) Data length storage address (2 bytes)
The length of data to be read from the MMCIII is specified. Specify
the address where the length of data is held. The maximum allowable
data length is 256 bytes.
(d) Input data storage address
Specify the address where data to be read from the MMCIII is
stored. A contiguous area not smaller than the length of data
specified in c) above is required.

5.61.5 W1=0 :When ACT = 0, W1 = 0 is set. If W1 = 0 is set when ACT = 1,


it indicates that read processing is in progress.
Processing Completion
W1=1 :Indicates that read processing has terminated. Whether read
(W1)
processing has terminated normally or abnormally can be
checked with the state of R9000 described below.

5.61.6 When W1 indicates the termination of read processing, a termination state


is set.
Operation Output
Register 7 6 5 4 3 2 1 0

R9000

MMC3R error

MMC3R=0 : Normal termination


MMC3R=1 : Abnormal termination

5.61.7 When ACT = 1, completion status information is set in the operation


register R9002.
Completion Status
Information 11 : MMC initialization not completed (W1=0, R9000#0=0)
0 : Normal termination (W1=1, R9000#0=0)
2 : Data length error (W1=1, R9000#0=1)
The specified length of data is 0, negative data is specified, or
the maximum allowable data length is exceeded.
6 : The MMCIII is not attached. (W1=1, R9000#0=1)
3 : Buffer specification error (W1=1, R9000#0=1)

316
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.61.8 Refer to Sec. I9.3.


Notes when this
Functional Instruction
is Used in Subroutine

317
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.62 f : Can be used


: Can be used (with some restrictions)
MMC3W : Cannot be used

(MMCIII WINDOW PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

DATA WRITE) f f f f f f f f f f f

NOTE
This functional instruction cannot be used with SA1 of the
Series 16i/18i/21iMODEL A/B and Series 15i.

5.62.1 The MMC3W instruction writes data to MMCIII application data via a
PMCMMC window. Which buffer in the MMCIII is to be written to
Function
can be specified. The contents of write data can be freely determined by
a PMC Ladder program and MMCIII application program.

CNC Buffer 1
PMC PMC data Buffer 1 MMC III
Offset

Data length

Buffer n
n = maximum of 10

5.62.2
Format

ACT W1
MMC3W Buffer Offset from Data length Input data f
specification the
SUB 89 beginning of
the buffer

5.62.3 ACT=0 : The MMC3W instruction is not executed.


Control Conditions ACT=1 : Data is written.
(ACT)

318
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.62.4 (a) Address for storing buffer specifications (2 bytes)


Parameters A buffer to which data is to be written is specified. Up to 10 buffers
can be specified. Specify the address where the buffer specification
is held.

NOTE
For the method of buffer registration, refer to the relevant
MMCIII manual.

(b) Address for storing an offset from the beginning of a buffer (2 bytes)
An offset from the beginning of a write buffer is specified. Specify
the address where the offset is held.
(c) Data length storage address (2 bytes)
The length of data to be written to the MMCIII is specified. Specify
the address where the length of data is held. The maximum allowable
data length is 256 bytes.
(d) Output data storage address
Specify the address where data to be written to the MMCIII is
stored. A contiguous area not smaller than the length of data
specified in c) above is required.

5.62.5 W1=0 :When ACT = 0, W1 = 0 is set. If W1 = 0 is set when ACT = 1,


Processing Completion it indicates that write processing is in progress.
(W1) W1=1 :Indicates that write processing has terminated. Whether write
processing has terminated normally or abnormally can be
checked with the state of R9000 described below.

5.62.6 When W1 indicates the termination of write processing, a termination


state is set.
Operation Output
Register 7 6 5 4 3 2 1 0

R9000

MMC3R error

MMC3W=0 : Normal termination


MMC3W=1 : MMC3R = 1: Abnormal termination

319
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.62.7 When ACT = 1, completion status information is set in the operation


Completion Status register R9002.
Information 11 : MMC initialization not completed (W1=0, R9000#0=0)
0 : Normal termination (W1=1, R9000#0=0)
2 : Data length error (W1=1, R9000#0=1)
The specified length of data is 0, negative data is specified, or
the maximum allowable data length is exceeded.
6 : The MMCIII is not attached. (W1=1, R9000#0=1)
3 : Buffer specification error (W1=1, R9000#0=1)

5.62.8 Refer to Sec. I9.3.


Notes when this
Functional Instruction
is Used in Subroutine

320
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.63 f : Can be used


: Cannot be used
SPCNT PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6
(SPINDLE CONTROL) f f f

5.63.1 SPCNT performs the following processing using spindle speed data
(32bit binary data) that is input from the NC or some other device to the
Function
PMC:
(a) Gear selection (Up to four gears from GR1 to GR4 can be used.)
(b) Calculating a spindle motor rotation command (13bit binary data)
when automatic gear selection is enabled
(c) Calculating a spindle motor rotation command (13bit binary data)
when direct gear selection is enabled
(d) Calculating a spindle motor rotation command when a spindle
override is specified
(e) Clamping the spindle motor speed to an upper or lower limit
As shown in Fig.5.63.1, a spindle motor rotation command is
calculated from the spindle speed data. The maximum value (8191)
of the spindle motor command is equivalent to an analog voltage at
10V.

NOTE
The motor speed is clamped after spindle override is
specified.

Spindle motor rotation command (13bit binary data)

Maximum motor speed (8191)


Upper limit at which the motor
speed is clamped
GR1 GR2 GR3 GR4

Lower limit at which the motor Spindle speed


speed is clamped (min1)
Maximum Maximum Maximum Maximum spindle
spindle speed spindle speed spindle speed for speed for GR4
for GR1 for GR2 GR3

Fig. 5.63.1 Spindle Speeds and Corresponding Spindle Motor Rotation Commands

The spindle motor rotation command is calculated as 13bit binary


data. If the spindle amplifier is a D/A converter provided in the
machine and can only handle 12bit binary data, for example, the
calculated spindle motor rotation command must be halved before
being output (shifted right one bit position in a shift register).

321
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(i) Spindle control with automatic gear selection


This functional instruction uses spindle speed data (32bit binary
data) and the maximum spindle speeds set in parameters GR1 to
GR4 of this functional instruction to select a gear, calculate the
spindle motor rotation command for that selected gear, and output
the result to the control data address.
Based on this output information, the sequence program must
perform gear switching as necessary and output the rotation
command to the spindle motor.

Spindle control
Information of GR1 to GR2


Spindle speed
SPCNT
Spindle motor
rotation
command

(ii) Spindle control with direct gear selection


When direct gear selection is set, this functional instruction does
not perform gear selection. A gear to be used is selected by the
sequence program. The target gear must be set at the control data
address, which is a parameter of this functional instruction, using
the sequence program.
According to the set gear, the functional instruction calculates and
outputs a spindle motor rotation command. In this case, the
spindle motor rotation command has a linear relationship with the
spindle speed. The line for the selected gear is assumed to extend
to its lower limit (indicated by a dotted line). See Fig.5.63.1.
Spindle control
Information of GR1 to GR2


Spindle speed
SPCNT Spindle motor
rotation
command

The spindle motor speed can be clamped at the upper and lower
limits also with direct gear specification. When the CNC
performs constant surface speed control, spindle control with
direct gear specification is generally performed.

322
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.63.2
Format

CIRC
* * *
SPCNT ffff ffff ffff
OVRD

(SUB46) Spindle speed data Spindle control Control data


ACT
address parameter address address

5.63.3 (a) Direct gear specification (CIRC)


CIRC=0 : Disables direct gear specification.
Control Conditions
(Enables automatic gear selection.)
CIRC=1 : Enables direct gear specification.
(b) Override specification (OVRD)
OVRD=0 : Disables the override function
OVRD=1 : Enables the override function.
(c) Instruction execution specification (ACT)
ACT=0 : The SPCNT instruction is not executed.
ACT=1 : The SPCNT instruction is executed.

5.63.4 (a) Spindle speed data address


Parameters Specifies an evennumbered address at which the spindle speed data
(32bit binary data) is stored.
(b) Spindle control parameter address
Specifies an evennumbered address at which the parameters for
spindle control are stored. Binary data is set in contiguous 24byte
memory locations starting at the specified address.

Spindle control parameter +0


Lower spindle motor speed limit data
Spindle control parameter +4
Upper spindle motor speed limit data
Spindle control parameter +8
Maximum spindle speed for gear 1
Spindle control parameter +12
Maximum spindle speed for gear 2
Spindle control parameter +16
Maximum spindle speed for gear 3
Spindle control parameter +20
Maximum spindle speed for gear 4
Spindle control parameter +24

323
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(i) Lower spindle motor speed limit data


Sets the lower spindle motor speed limit obtained from the
following expression:
Minimum speed (rpm) specified for
Lower spindle motor the spindle motor
speed limit data = 8191
Maximum speed (rpm) obtainable by the
spindle motor

A value from 0 to 8191 can be specified as the lower speed limit


data. The maximum spindle motor speed is achieved when 10 V
is applied to the motor.
(ii) Upper spindle motor speed limit data
Sets the upper spindle motor speed limit obtained from the
following expression:
Maximum speed (rpm) specified for
Upper spindle motor the spindle motor
speed limit data = 8191
Maximum speed (rpm) obtainable by
the spindle motor

(iii) Maximum spindle speed for GR1


Sets a maximum spindle speed (min1) for GR1. The maximum
spindle speed must be set in this parameter even when GR1 gear
is not provided. The maximum spindle speed is the speed of the
spindle when the motor operates at its maximum speed.
(iv) Maximum spindle speed for GR2
Sets a maximum spindle speed (min1) for GR2. When GR2 is
not provided, this parameter must be set to 0.
(v) Maximum spindle speed for GR3
Sets a maximum spindle speed (min1) for GR3. When GR3 is
not provided, this parameter must be set to 0.
(vi) Maximum spindle speed for GR4
Sets a maximum spindle speed (min1) for GR4. When GR4 is
not provided, this parameter must be set to 0.
(c) Control data address
Contiguous 4byte memory locations starting at the evennumbered
address specified in the control data address parameter must be
specified.

7 6 5 4 3 2 1 0

Specified address+0 R08 R07 R06 R05 R04 R03 R02 R01
Spindle motor
Specified address+1 R13 R12 R11 R10 R09 rotation command

Specified address+2 GR4 GR3 GR2 GR1 } Spindle gear


} selection
Specified address+3 SOV128 SOV64 SOV32 SOV16 SOV8 SOV4 SOV2 SOV1 } Spindle override

(i) Spindle gear selection


7 6 5 4 3 2 1 0
GR4 GR3 GR2 GR1

[For automatic gear selection]


This functional instruction finds an appropriate gear using the
spindle speed data and the maximum spindle speed for each
gear, then outputs the result to GR1 to GR4.

324
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

[For direct gear selection]


The sequence program sets the gear to be used in GR1 to GR4.
This functional instruction calculates the spindle motor rotation
commands for all speeds from the upper motor speed limit to the
lower speed limit (extended portion indicated by dotted line). See
Fig. 5.63.1.
(ii) Spindle motor rotation command
7 6 5 4 3 2 1 0
R08 R07 R06 R05 R04 R03 R02 R01
R13 R12 R11 R10 R09

The spindle motor rotation command (13bit binary data)


calculated by this functional instruction is set at these control data
addresses. This instruction specifies a spindle motor rotation
command with a spindle override applied.
(iii) Spindle override
7 6 5 4 3 2 1 0
SOV128 SOV64 SOV32 SOV16 SOV8 SOV4 SOV2 SOV1

The sequence program must set a spindle override in binary. A


spindle override from 0% to 255% can be set in binary.

5.63.5 Spindle control is primarily used to control the spindle speed during
normal cutting. It can, however, also be used to:
Use of Spindle Control
(a) Rotate the spindle motor at a specific speed when the gear is switched
The sequence program can output appropriate 13bit binary data as
a spindle motor rotation command to rotate the spindle motor at a
specific speed, without using this functional instruction.
(b) Rotate the spindle at a specific speed during spindle orientation
This is enabled by specifying appropriate spindle speed data in the
functional instruction (SPCNT). During spindle orientation, the
spindle is rotated at the specified orientation spindle speed with the
currently selected gear (gear selection is not performed). Gear
selection is disabled by setting CIRC to 1 (direct gear specification).

Spindle control
Spindle
speed data Spindle speed data
Information of
GR1 to GR2
sent from
the NC, etc.


Orientation SPCNT
spindle

speed data

Spindle motor
rotation command

325
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

(c) Control the spindle in a tapping cycle


In a tapping cycle, spindle rotation is reversed at the bottom of a hole.
Using the HIGH gear to reverse the rotation requires a lower analog
voltage than using the LOW gear. So, using the HIGH gear reduces
the machining time.
To widen the usable range of the HIGH gear, set CIRC to 1 to disable
automatic gear selection.
(d) Clamp the spindle speed
When the BMI interface is used between the NC and PMC, spindle
should be controlled by the PMC (sequence program), as described
in the BMI manual.
Clamping the spindle speed is one of the spindle control operations.
The spindle control functional instruction SPCNT (SUB46) can be
used to clamp the spindle speed. The clamping method is outlined
below. For precise control, conform to the specifications of the
machine supplied by the machine tool builder.


Spindle control Spindle motor
Spindle
speed data
GR1 to GR4 rotation command




Spindle
speed limit
data
Spindle motor
limit value

(e) Example
Suppose that the parameters are set as follows:
Minimum speed specified for the spindle motor = 1000 min1
Maximum speed specified for the spindle motor = 35000 min1
Maximum speed obtainable by the spindle motor = 40000 min1
(Maximum speed when 10 V is applied to the spindle motor)
Maximum speed for gear 1 = 25000 min1
Maximum speed for gear 2 = 40000 min1
Maximum speed for gear 3 = 6000 min1
Maximum speed for gear 4 = 100000 min1
Spindle speed data addresses = F10 to F11 (RO0 to RO15)
The specified spindle speed signal is used.
(For details, refer to the BMI connection manual.)
Spindle control parameter addresses = D10 to D33
Control data addresses = R0 to R3

326
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

(1) Create a functional instruction.

R9091.1 MOVW

F10 R10
SUB44

R9091.1
NUMEB
2 0 R12
SUB40

CIRC
SPCNT R10 D10 R0

OVRD
SUB46

ACT

(2) Set the spindle speed data


Copy the spindle speed data (RO0 to RO15) to spindle speed data
addres specified at the first porameter of SPCNT.

R10 RO0 to 7 Copy from F10


RO8 to 15 Copy from F11
0 Clear by 0
0 Clear by 0

(3) Set the spindle control parameters.


The lower spindle motor speed limit data and the upper spindle
motor speed limit data are obtained as follows (see i) and ii) of b)
in 4)):
Lower spindle motor 1000
speed limit data = 8191 = 204 (min1)
40000

Upper spindle motor 35000


speed limit data = 8191 = 7167 (min1)
40000

327
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

Then, the spindle control parameters are set as follows:

D10 toD13 204 Lower spindle motor speed limit data


D14 to D17 7167 Upper spindle motor speed limit data
D18 to D21 25000 Maximum spindle speed for gear 1
D22 to D25 40000 Maximum spindle speed for gear 2
D26 to D29 60000 Maximum spindle speed for gear 3
D30 to D33 100000 Maximum spindle speed for gear 4

(4) Calculate the spindle motor rotation command for the spindle
speed

Maximum motor speed (8191)


Lower limit at which the motor
speed is clamped
(7167) GR1 GR2 GR3 GR4

Spindle speed
Lower limit at which the motor
speed is clamped (min1)
Maximum Maximum Maximum spindle Maximum spindle
(204)
spindle speed spindle speed speed for GR3 speed for GR4
for GR1 (25000) for GR2 (60000) (100000)
(40000)

From the above graph, the following table can be obtained:

Table 5.63.5 Maximum and Minimum spindle speeds for each gear

Minimum spindle speed Maximum spindle speed


(min1) (min1)
GR1 625 21877
GR2 21878 35004
GR3 35005 52506
GR4 52507 87499
(When CIRC = 0, OVRD = 0)

Thus, if the spindle speed data is 55000 (min1), when the spindle
override is not applied (OVRD = 0) and the direct gear
specification is not set (CIRC = 0), the spindle motor rotation
command and the spindle gear to be used are obtained as follows:

R0 to R1 Spindlemotor rotation command


4505
R2 8 (GR4) Spindle gear selection

328
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.64 f : Can be used


: Cannot be used
END (END OF A PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

LADDER PROGRAM) f f f f f f f f f f f f f

5.64.1 The END functional instruction designates the end of a ladder program.
END must be placed at the end of the ladder program.
Function

5.64.2
Format
END

SUB 64

329
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.65 f : Can be used


: Cannot be used
CALL (CONDITIONAL PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

SUBPROGRAM f f f f f f f f f f f f f

CALL)

5.65.1 The CALL functional instruction calls a subprogram. When a


subprogram number is specified in CALL, a jump occurs to the
Function
subprogram if a condition is satisfied.

5.65.2
Format ACT
CALL Subprogram
number
SUB 65

5.65.3 (a) Input signal


Control Conditions ACT=0 : The CALL instruction is not executed.
ACT=1 : The CALL instruction is executed.

5.65.4 (a) Subprogram number


Parameters Specifies the subprogram number of a subprogram to be called. The
subprogram number must be specified in the P address form. A
number from P1 to P512 can be specified.
Example : To call subprogram 1

ACT
CALL P1

SUB 65

CAUTION
Be careful when using the CALL instruction with the COM,
COME, JMP, or JMPE functional instruction. For details,
see Chapter 9 in Part I.

330
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.66 f : Can be used


: Cannot be used
CALLU PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

(UNCONDITIONAL f f f f f f f f f f f f f

SUBPROGRAM
CALL)

5.66.1 The CALLU functional instruction calls a subprogram. When a


Function subprogram number is specified, a jump occurs to the subprogram.

5.66.2
Format
CALLU Subprogram
number
SUB 66

5.66.3 (a) Subprogram number


Parameters Specifies the subprogram number of a subprogram to be called. The
subprogram number must be specified in the P address form. A
number from P1 to P512 can be specified.
Example : To call subprogram 1

CALLU P1

SUB 66

331
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.67 f : Can be used


: Cannot be used
SP (SUBPROGRAM) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.67.1 The SP functional instruction is used to create a subprogram. A


subprogram number is specified as a subprogram name. SP is used with
Function
the SPE functional instruction (mentioned later) to specify the
subprogram range.

5.67.2
Format
SP Subprogram
number
SUB 71

5.67.3 (a) Subprogram number


Specifies the subprogram number of a subprogram to be coded
Parameters
following this instruction. The subprogram number must be
specified in the P address form. A number from P1 to P512 can be
specified. The specified subprogram number must be unique within
the sequence program.
Function PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

Subprogram P1 to P1 to P1 to P1 to P1 to P1 to P1 to P1 to P1 to P1 to P1 to P1 to P1 to
number P512 P512 P512 P512 P2000 P512 P2000 P2000 P512 P2000 P512 P2000 P2000

Example: When the subprogram number is set to 1

SP P1

SUB 71

332
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.68 f : Can be used


: Cannot be used
SPE (END OF A
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6
SUBPROGRAM) f f f f f f f f f f f f f

5.68.1 The SPE functional instruction is used to create a subprogram. SPE is


Function used with the SP functional instruction. It specifies the range of a
subprogram. When this functional instruction has been executed, control
is returned to the functional instruction that called the subprogram.

5.68.2
Format
SPE

SUB 72

333
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.69 f : Can be used


: Cannot be used
JMPB (LABEL JUMP) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.69.1 The JMPB functional instruction transfers control to a Ladder immediately


after the label set in a Ladder program. The jump instruction can transfer
Function
control freely before and after the instruction within the program unit (main
program or subprogram) in which the instruction is coded. (See the
description of the LBL functional instruction, which is be explained later.)
As compared with the conventional JMP functional instruction, JMPB
has the following additional functions:
D More than one jump instruction can be coded for the same label.
D Jump instructions can be nested.
Ladder program
Program unit Program unit
LBL AA
LBL AA

JMPB BB

JMPB AA
JMPB AA

JMPB AA LBL BB

5.69.2
Format ACT
JMPB Specification
of the jump
destination
SUB 68 label

5.69.3 ACT=0 : The next instruction after the JMPB instruction is executed.
Control Conditions ACT=1 : Control is transferred to the Ladder immediately after the
specified label.
(ACT)

5.69.4 (a) Label specification


Parameters Specifies the label of the jump destination. The label number must
be specified in the L address form. A value from L1 to L9999 can
be specified.

CAUTION
1 For the specifications of this instruction, see Chapter 10 in
Part I.
2 When this instruction is used to jump back to a previous
instruction, care must be taken not to cause an infinite loop.

334
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.70 f : Can be used


: Cannot be used
JMPC (LABEL JUMP) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.70.1 The JMPC functional instruction returns control from a subprogram to the
main program. Be sure to code the destination label in the main program.
Function
The specifications of this JMPC functional instruction are the same as
those of the JMPC functional instruction, except that JMPC always
returns control to the main program.
D More than one jump instruction can be coded for the same label.
Ladder program
Main Main
program program
LBL AA
LBL AA

LBL BB

Subprogram Subprogram

JMPC AA JMPC AA

JMPC AA JMPC BB

5.70.2
Format ACT
JMPC Specification
of the jump
destination
SUB 73 label

5.70.3 ACT=0 : The instruction after the JMPC instruction is executed.


Control Conditions ACT=1 : Control is transferred to the Ladder after the specified label.
(ACT)

5.70.4 (a) Label specification


Parameters Specifies the label of the jump destination. The label number must
be specified in the L address form. A number from L1 to L9999 can
be specified.

CAUTION
1 For the specifications of this instruction, see Chapter 10 in
Part I.
2 When this instruction is used to jump back to a previous
instruction, care must be taken not to cause an infinite loop.

335
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.71 f : Can be used


: Cannot be used
LBL (LABEL) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

5.71.1 The LBL functional instruction specifies a label in a Ladder program. It


specifies the jump destination for the JMPB and JMPC functional
Function
instructions. (See the explanation of the JMPB and JMPC functional
instructions.)

Ladder program

LBL AA
LBL AA

JMPB BB

JMPB AA
JMPC AA

JMPC AA LBL BB

5.71.2
Format
LBL Label
specification
SUB 69

5.71.3 (a) Label specification


Specifies the jump destination for the JMPB and JMPC functional
Parameters
instructions. The label number must be specified in the L address
form. A label number from L1 to L9999 can be specified. A label
number can be used more than once as long as it is used in a different
program unit (main program, subprogram).

NOTE
For the use of this instruction, see Chapter 10 of Part I.

336
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.72 f : Available
: Unavailable
AXCTL (AXIS PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

CONTROL BY PMC) f f f f f f f f f f f f f f f f

NOTE
1 Option for Axis control by PMC function is required.
2 This functional instruction can not be used on the CNC that
does not have option for Axis control by PMC.

5.72.1 This function simplifies the handshake of DI/DO signal for the axis
Function control by PMC.

5.72.2
Format
RST W1
AXCTL ffff ffff f
Group No. Axis control
ACT (SUB 53) of DI/DO signal data address

Fig. 5.72.2 AXCTL instruction format

Table 5.72.2 AXCTL instruction coding


Step Instruc- Address Bit
Number tion Number Number Remarks

1 RD ffff. f RST
2 RD. STK ffff. f ACT
3 SUB 53 AXCTL command
4 (PRM) ffff Number of DI/DO signal
5 (PRM) ffff Axis control data address
6 WRT ffff. f W1, processing completion

5.72.3 ACT=0 : The AXCTL function is not executed.


If RST is 1, PMC axis control instruction reset processing is performed.
Control Condition
If a modification is made to a ladder program with RST set to 1, the
AXCTL instruction cannot sometimes be executed successively when the
ladder program is executed again.
When modifying a ladder program, set RST and ACT to 0.
ACT=1 : The AXCTL function is executed.
ACT is to be maintained 1 till the end of AXCTL processing.
And reset ACT immediately after the processing is complete
(W1 = 1).
RST=0 : Release reset.
RST=1 : Set the reset signal (ECLRx) to 1. All the buffered commands
are invalidated and the command being executed is stopped.
Set RST at the same time as the reset of CNC when CNC
becomes the state of alarm.

337
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

NOTE
When RST and ACT become 1 at the same time, RST is
prior to ACT.

5.72.4 (a) Group number of DI/DO signal


Parameters Specify the DI/DO signal group by the number.
1 : group A(G142 to G149, F130 to F132)
2 : group B(G154 to G161, F133 to F135)
3 : group C(G166 to G173, F136 to F138)
; Cannot be used on Power MateD/F
4 : group D(G178 to G185, F139 to F141)
; Cannot be used on Power MateD/F
5 : group E (G226 to G233, F228 to F230)
; Can be used only on Power MateH
6 : group F (G238 to G245, F231 to F233)
; Can be used only on Power MateH
Add 1000 to the above number as follows if you use HEAD2 of
FS16/18TT or 2nd path side of Power MatwD.
1001 : group A (G1142 to G1149, F1130 to F1132)
1002 : group B (G1154 to G1161, F1133 to F1135)
1003 : group C (G1166 to G1173, F1136 to F1138)
; Cannot be used on Power Mate
1004 : group D (G1178 to G1185, F1139 to F1141)
; Cannot be used on Power Mate
When 3rd path side is used with the Series 16i/18i, the following
addresses are used for DI/DO signals:
2001 : Group A (G2142 to G2149, F2130 to F2132)
2002 : Group B (G2154 to G2161, F2133 to F2135)
2003 : Group C (G2166 to G2173, F2136 to F2138)
2004 : Group D (G2178 to G2185, F2139 to F2141)
(b) Group number of DI/DO signal for PMiD/H
1 : Group A(G142 to G149, F130 to F132)
2 : Group B (G154 to G161, F133 to F135)
3 : Group C (G166 to G173, F136 to F138)
4 : Group D(G178 to G185, F139 to F141)
5 : Group E (G464 to G471, F500 to F502)
6 : Group F (G476 to G483, F503 to F505)
7 : Group G(G488 to G495, F506 to F508)
8 : Group H(G500 to G507, F509 to F511)
For 2nd path side of PMiD/H
1001 : Group A (G1142 to G1149, F1130 to F1132)
1002 : Group B (G1154 to G1161, F1133 to F1135)
1003 : Group C (G1166 to G1173, F1136 to F1138)
1004 : Group D (G1178 to G1185, F1139 to F1141)
1005 : Group E (G1464 to G1471, F1500 to F1502)
1006 : Group F (G1476 to G1483, F1503 to F1505)
1007 : Group G (G1488 to G1495, F1506 to F1508)
1008 : Group H (G1500 to G1507, F1509 to F1511)

338
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

NOTE
With the PMCSB5 (RB5), group E and subsequent groups
cannot be used. The SB6 (RB6) is required to use these
groups.

(c) Axis control data address


Select the addresses of the locations that contain PMC axis control
data.

+0 FANUC reserved Specify 0.

1 Control command Specify the command to set EC0xEC6x.

2 Command data 1 Specify the data to set EIF0xEIF15x.

4 Command data 2 Specify the data to set EID0xEID31x.

6
(x=A / B / C / D)
7

The following functions are available.


Operation Control Command data 1 Command data 2
Rapid traverse 00H Feedrate Total travel amount

Need not to set if CNC


PRM. 8002#0 = 0.
Cutting feed 01H Feedrate (Note 1) Total travel amount
(feed per min.)
Cutting feed (Note 2) 02H Feedrate per Total travel amount
(feed per revolution) revolution
Skip 03H Feedrate Total travel amount
(feed per min.) (Note 2)
Dwell 04H not used Dwell time
Reference pos. return 05H not used not used
Continuous feed (Note 3) 06H Feedrate Feed direction
(Note 4)
1st ref. pos. return 07H Feed rate
2nd ref. pos. return 08H
3rd ref. pos. return 09H Need not to set if CNC not used
4th ref. pos. return 0AH PRM. 8002#0 = 0.
(Note 2)
External pulse 0BH Pulse weighting
synchronization 0DH not used
(Note 2) 0EH
(Note 3) 0FH (Only M series)
Speed command 10H Feedrate not used
(Note 2)
(Note 5)
(Note 6)
Machine coordinate 20H Feedrate Position of machine
positioning. coordinate.
(Rapid traverse) Need not to set if CNC (absolute)
(Note 2) PRM. 8002#0 = 0.
(Note 6)

339
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

CAUTION
1 When you specify 0 for feedrate, CNC does not work.
Please release this state by RST = 1.
2 It is not available in PMCMODEL PA1/PA3.
3 When you end a continuous feed or external pulse
synchronization, set RST to 1. And, continuous feed cant
be used with buffering inhibits signal = 1. You must set the
signal to 0.
4 Specify the direction by most significant bit of command
data 2.
5 Command control axis must be specified to rotary axis by
setting parameter ROTx (No. 1006#0) to 0.
6 Not applicable to the Power Mate.
However this function applicables to the Power Mate i.
7 For details such as the range of command data, please refer
to the connecting manual for each CNC models.

CAUTION
The above table is not uptodate. For the latest
information, refer to the descriptions about PMC axis control
in the CNC Connection Manual (Functions).

Example 1) In case of cutting feed (feed per min.)

+0 0H Not used (Specify 0).

1 01H Command code for cutting feed. (feed per min.)

2 Feedrate unit : mm/min.

4 Total travel amount

5 unit : 0.001mm

6
(x=A / B / C / D)
7

340
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

Example 2) In case of machine coordinate positioning.

+0 0H Not used (Specify 0).

1 Command code for machine coordinate


20H positioning.

2 0
or In case of CNC PRM8002#0= 0 not used.
Feedrate =1 Feedrate.
3

(Absolute)
4 Position in machine
coordinate system
5

CAUTION
It is necessary to set the CNC parameters relating to the axis
movement.

5.72.5 W1=0 : It is 0 usually. W1=1 indicates that AXCTL instruction is


completed.
End of Command (W1)
Specify ACT=0 immediately after processing is completed.
(W1=1).
W1=1 : It will become 1 when the command of the axis control by PMC
is buffered on CNC (when EMBUFx=0) or when axis
movement is completed (when EMBUFx=1).

5.72.6 When error occurs by processing the axis control by PMC, the bit of the
Operation Output operation output register will be set. At the same time, processing is over.
Register (R9000) 7 6 5 4 3 2 1 0

R9000

Group number of DI/DO


signal specification error.

NOTE
1 W1 becomes 1 regardless of the state of ACT.
2 It is not related to the state of the alarm signal (EIALx).

341
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.72.7 (1) The following signals cannot be operated from this function.
Remarks Please operate by LADDER.
D Axis control stop signal
ESTPx (G142#5, G154#5, G166#5, G178#5)
D Servooff signal
ESOFx (G142#4, G154#4, G166#4, G178#4)
D Block stop signal
ESBKx (G142#3, G154#3, G166#3, G178#3)
D Block stop inhibit signal
EMSBKx (G143#7, G155#7, G167#7, G179#7)
D Controlled axis selection signal
EAX1EAX8 (G136#0 to #7)
D Override signal *FV0E*FV7E (G151#0 to #7)
D Override cancel signal OVCE (G150#5)
D Rapid traverse override signal
ROV2E, ROV1E (G150#1, #0)
D Dry run signal DRNE (G150#7)
D Manual rapid traverse RTE (G150#7)
selection signal
D Skip signal SKIP/ESKIP (X4#7, #6)
D Buffering inhibit signal
EMBUFx (G142#2, G154#2, G166/#2, G178#2)
(x=A/B/C/D)

WARNING
Movement cannot be sured when controlled axis selection
signal (EAXx) is changed in the state of ACT=1.

(2) Buffering inhibit signal (EMBUFx)


0 : The commands are buffered on the CNC.
Even if one command is being executed, the CNC accepts the next
command as long as there is vacancy in the buffer on CNC.
W1 will become 1 when the command of the axis control by PMC
is buffered on CNC.
1 : Prohibits the buffering on CNC.
W1 will become 1 when the movement of the instructed axis
control by PMC is completed.

342
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.73 f : Can be used


: Usable in some
PSGNL (POSITION CNC models
SIGNAL OUTPUT) : Cannot be used

PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB5 SB6 SB7 SC SC3 NB NB2 NB6
SB4 SC4
f f

NOTE
The PMCSB5/SB6 can be used only in the Power Mate
iD/H.

5.73.1 This function outputs a signal that indicates the are in which the current
position in the mechanical coordinate system is located. The area is
Function
specified by parameter.

5.73.2
Format

ACT PSGNL ffff ffff


Area division Current position

(SUB 50) specification area output


data address address

Fig. 5.73.2 PSGNL instruction format

5.73.3 (a) Execution specification (ACT)


ACT=0 : The PSGNL instruction is not executed.
Control Condition
ACT=1 : The PSGNLnstruction is executed.

343
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.73.4 (a) Area division specification data address


Parameters Set the top address of area division specification data 29 bytes of
continuous memory are necessary in nonvolatile memory area for
area division specification data.

Area division
(1 : 1st Axis, 2 : 2nd Axis,...)
specification data Axis No.
+0 or
Path No. (1 : 1st Path1st Axis
(1byte) 2 :2nd Path1st Axis)

+1
I
(4bytes)

+5
II
(4bytes)

+9
III
(4bytes)

Area division
+13 specification data
IV
(4bytes)

+17
V
(4bytes)

+21
VI
(4bytes)

+25
VII
(4bytes)

+29

D In case of axisNo. specification


Please set axisNo. to select. (1 byte data of binary format)
(Example) Axis No.=1 : For machine coordinates of the 1st axis
Axis No.=2 : For machine coordinates of the 2nd axis
D In case of path specification (Power MateMODEL D dual path
control)
Please set pathNo. of axis to select. (1 byte data of binary format)
(Example)
Path spec.=1: For machine coordinates of the 1st axis on the 1st path)
Path spec.=2: For machine coordinates of the 1st axis on the 2nd path)
Each area division specification data (I, II, III, ...., VII) is 4bytes
binary format data. (Scale is 0.001mm or 0.001inch)

344
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

<Example of area division>

I II III IV V VI VII
(1) (2) (3) (4) (5) (6) (7) (8)
)
Total stroke area

As shown in the above diagram, check can be performed for the 8


areas (1) to (8) by dividing the total stroke area by 7 division points.

NOTE
1 Please set the division points data in ascending order (I <
II < .....<VI < VII). If they are not in ascending order, the
sequence program cannot operate normally.
2 Even if you need division points only under 7, you must set
the division specification data for7.

(b) Current position area output address


The address which is output the divided area that the currrent position
in the machine coordinates system located.
Cureent position
7 6 5 4 3 2 1 0
area output address (1) (2) (3) (4) (5) (6) (7) (8)

Corresponding bit is set to 1 indicates the area in which the current


position in the machine coordinates system is located.
(Example)
Bit 0 becomes 1 if the current position in the machine coordinate
system is greater than VII. Bit 1 becomes 1 if the current position
in the machine coordinate system is greater than VI but not greater
than VII.

5.73.5 If an error occurs in position signal output processing, the corresponding


Operation Output bit of the operation output register is set.
Register (R9000) 7 6 5 4 3 2 1 0

R9000

Axis number or path


specification error

345
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.73.6 This example illustrates how to output the position signal of the current
Example of Using position of the first axis of path 1 in the machine coordinate system (the
area split specification data and current position area output addresses are
Position Signals set to D0321 and R1000, respectively).

ACT PSGNL D0321 R1000

(SUB 50)

Decimal

D0321 1

D0322 300000

D0326 200000

D0330 100000

D0334 0

D0338 100000

D0342 200000

D0346 300000

If ACT = 1 for the above ladder and area split specification data, the
current specification area output (R1000) is as follows:
D R1000.0=1: The current position in the machine coordinate system is
greater than 300.000 mm.
D R1000.1=1: The current position in the machine coordinate system is
greater than 200.000 mm but not greater than 300.000 mm.
D R1000.2=1: The current position in the machine coordinate system is
greater than 100.000 mm but not greater than 200.000 mm.
D R1000.3=1: The current position in the machine coordinate system is
greater than 0 mm but not greater than 100.000 mm.
D R1000.4=1: The current position in the machine coordinate system is
greater than 100.000 mm but not greater than 0 mm.
D R1000.5=1: The current position in the machine coordinate system is
greater than 200.00 mm but not greater than 100.000
mm.
D R1000.6=1: The current position in the machine coordinate system is
greater than 300.000 mm but not greater than 200.000
mm.
D R1000.7=1: The current position in the machine coordinate system is
not greater than 300.000 mm.

346
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.74 f : Can be used


: Usable in some
PSGN2 (POSITION CNC models
: Cannot be used
SIGNAL OUTPUT 2) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB5 SB6 SB7 SC SC3 NB NB2 NB6
SB4 SC4
f f

NOTE
The PMCSB5/SB6 can be used only in the Power Mate
iD/H.

5.74.1 Turn W1=1 which th ecurrent position in the machine coordinates system
Function is in the area specifified by parameters.

5.74.2
Format
ACT PSGN2 ffff W1
Control data f
(SUB 63) address

Fig. 5.74.2 PSGN2 instruction format

5.74.3 (a) Execution specification (ACT)


ACT=0 : The PSGN2 instruction is not executed.
Control Condition
ACT=1 : The PSGN2 instruction is executed.

347
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.74.4 (a) Control data address


Parameters Please set the top address of control data.
For the area specification data, 9bytes of continuous memory area in
the nonvolatile memory is necessary.
Control data+0
Axis No. (1 : 1st Axis, 2 : 2nd Axis,...)
(basic
or
specification)
Path No.
(1 : 1st Path1st Axis
(1byte) 2 :2nd Path1st Axis)

+1
Boundary Point 1
(4bytes)

+5
Boundary Point 2
(4bytes)

+9

D In case of axisNo. specification


Please set axisNo. to select. (1 byte data of binary format)
(Example) Axis No.=1 : For machine coordinates of the 1st axis
Axis No.=2 : For machine coordinates of the 2nd axis
D In case of path specification (Power MateMODEL D two path
control)
Please set pathNo. of axis to select. (1 byte data of binary format)
In the PMCSB5/SB6 for the Power Mate i, control data can be used
under the following expanded specification. Generally, use of the
expanded specification offers faster operation. So it is recommended
that the expanded specification be used.
The control data requires 12 consecutive bytes in nonvolatile
memory.
Control data + 0
(expanded Fixed to 0
(2bytes)
specification)

(0 = path 1, 2 = path 2, ...)


+2
Path specification
(1byte)

+3 (1 = first axis, 2 = second axis, ...)


Axis number
(1byte)

+4
Boundary point 1
(4bytes)

+8
Boundary point 2
(4bytes)

+12

348
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

D Path specification
A path is specified. (Onebyte data in binary form)
(Example) Path specification = 0: Path 1 is specified.
Path specification = 2: Path 2 is specified.
Path specification = 3: Path 3 is specified.
D Axis number specification
An axis number is specified. (Binary onebyte data)
(Example) Axis number = 1: The machine coordinates for the first
axis are specified.
Axis number = 2: The machine coordinates for the second
axis are specified.
(Boundary points <1> and <2> are binary fourbyte data. Their unit
of measurement is 0.001 mm or 0.001 inch.

CAUTION
Data for both boundary points <1> and <2> must be
specified in ascending order (boundary point 1 x boundary
point 2).

<Example of area division>

1
W1 0

Boundary Point < 1 > Boundary Point < 2 >


Note) Includes
+ F : Boundary Point <1><2>.
F F
Total stroke area

5.74.5 W1=0 : The current position in the machine coordinates system is


outside of the area specified by parameters.
Current Position Area
W1=1 : The current position n the machine coordinates system is inside
Output (W1) of the area specified by parameters.

5.74.6 If an error occurs in position signal output processing, the corresponding


Operation Output bit of the operation output register is set.
In this case, W1 = 0.
Register (R9000)
7 6 5 4 3 2 1 0

R9000

Axis number or path


specification error

349
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.74.7 D This example illustrates how to output the position signal for the
Example of Using current position of the second axis of path 1 in the machine coordinate
system if it is the position between 100.000 mm and 200.000 mm.
Position Signals (The control data address is set to D0320.)

(Basic specification)

ACT PSGN2 D0320 W1


f
(SUB 63)

Binary Decimal
D0320 00000010 ( 2)
D0321 01100000 (100000)
D0322 01111001
D0323 11111110
D0324 11111111
D0325 01000000 ( 200000)
D0326 00001101
D0327 00000011
D0328 00000000

(Basic specification)

ACT PSGN2 D0320 W1


f
(SUB 63)

Binary Decimal
D0320 00000000 0
D0321 00000000
D0322 00000000 0
D0323 00000010 2
D0324 01100000 100000
D0325 01111001
D0326 11111110
D0327 11111111
D0328 01000000
D0329 00001101 200000
D0330 00000011
D0331 00000000

If ACT = 1 for the above ladder and control data, W1 = 1 when:


100.000 x current position (second axis) in the machine coordinate
system x 200.000 mm

350
B61863E/14 PMC SEQUENCE PROGRAM 5. FUNCTIONAL INSTRUCTIONS

5.75 f : Can be used


: Can be used depending of the version of software
NOP (NO : Cannot be used

OPERATION) PMD/H PA1 PA3



FS16/18A SA1 SA2 SA3 SB SB2 SB3 SC SC3

FS16/18B SA1 SB3 SB4



FS16/18 B/C SC3 SC4

FS16/18C SA1 SB5 SB6

FS20 SA1 SA3

FS21B SA1 SA3

FS0i SA1 SA3

FS16i/18i/21i SA1 SA5 SB5 SB6 SB7


PMi
f f f f f
FS15B NB NB2

FS15i NB6
f

351
5. FUNCTIONAL INSTRUCTIONS PMC SEQUENCE PROGRAM B61863E/14

5.75.1 During creation of a ladder program using the offline programmer, if the
Function program is compiled with specifying the setting with which a net
comment or form feed code is used and the point of the net comment is
output, position information of the net comment or form feed code is
output as the NOP instruction. This instruction performs no operation
during execution of the ladder.

CAUTION
1 Do not move or delete the NOP instruction using the builtin edit function. During
decompilation, position information of net comments and form feed are lost.
2 For the model which does not support this instruction, always compile a program without
specifying the setting with which the net comment pointers are output. If the NOP instruction
is executed on a model which does not support the instruction, a system error may occur.
Set the following items on the programmer compiler option screen as shown below:
FANUC LADDERII Select [None] for [Net Comment].
FANUC LADDERIII Uncheck [Output Net Comment Pointers].
3 This instruction can be used on the following models on which the listed version or later of
software is installed:
PMD/H PMCPA1 4074/01 to, 4078/06 to
(Cannot be used on series 4075)
FS16B/18B PMCSB3/SB4 4066/08 to
Edit card 4073/06 to
FS16C/18C PMCSA1/SB5/SB6 4067/09 to
Edit card 4090/04 to
FS16B/18B/16C/18C PMCSC3/SC4 4068/08 to
FS15B PMCNB/NB2 4048/06 to, 4049/01 to
(Cannot be used on series 4075)

352
B61863E/14 PMC SEQUENCE PROGRAM 6. NONVOLATILE MEMORY

6 NONVOLATILE MEMORY

353
6. NONVOLATILE MEMORY PMC SEQUENCE PROGRAM B61863E/14

6.1 Nonvolatile memory is considered nonvolatile if its contents are not


erased when the power is turned off.
TIMER, COUNTER,
KEEP RELAY, (1) Used for the timer
NONVOLATILE Time can be set and displayed from the CRT/MDI panel. The set time
can be read or written by a sequence program instruction.
MEMORY CONTROL,
DATA TABLE (2) Used for the counter
This area is used to store the preset and cumulative values of the
counter. Values can be set and displayed from the CRT/MDI panel.
These values can be read and written by a sequence program
instruction. Refer to section 3.5 for details of addresses.
The data format is two bytes of BCD or binary, and the higher-order
digits are entered at the smaller address.
Whether counter is processed by BCD format or binary format is
selected by a system parameter.

Example) PMC counter addresses are C0 and C1 and the set value
is 1578.

BCD code (1578)

7 6 5 4 3 2 1 0
C0 0 1 1 1 1 0 0 0

7 8

7 6 5 4 3 2 1 0
C1 0 0 0 1 0 1 0 1

1 5

Binary code (1578)


7 6 5 4 3 2 1 0
C0 0 0 1 0 1 0 1 0

27 26 25 24 23 22 21 20

7 6 5 4 3 2 1 0
C1 0 0 0 0 0 1 1 0

215 214 213 212 211 210 29 28

To change low-order digits of the set value by a sequence program


instruction with 1 byte processing, specify C0 as the output address
of the functional instruction parameters to enter new data.

(3) Keep relay


This memory is used as parameters, keep relays, etc. for sequence
control. Setting and display are possible from the CRT/MDI panel
and sequence program instructions can be used for reading and
writing. Since data set or displayed from the CRT/MDI panel is
binary eight bits, each of the eight digits of data is set or displayed
as 0 or 1.

354
B61863E/14 PMC SEQUENCE PROGRAM 6. NONVOLATILE MEMORY

(4) Nonvolatile memory control (MWRTF, MWRTF2) (Address K16)


This memory is used when the position of a moving part of the
machine tool, such as a lathe turret, is stored in code (BCD, etc.) and
to maintain it while power is off.
#7 #6 #5 #4 #3 #2 #1 #0
K16 MWRTF2 MWRTF

Setting and display are possible from the CRT/MDI panel, and
sequence program instructions can be used for reading and writing.
If, for example, power is turned off for some reason during rotation
of the turret, the turret stops and a difference between the contents of
the memory storing the position and the actual position of the turret
occurs. When power is turned on again, the machine tool will be out
of sequence. To prevent this, use the nonvolatile memory control, and
a sequence program as follows.
(a) Set MWRTF in nonvolatile memory control to 1 before starting
the turret.
(b) Start the turret.
(c) Set MWRTF to 0 after the turret stops.
(d) MWRTF remains 1 if power is turned off between a) and c).
(e) When power is turned on again, automatically MWRTF2 = 1 and
an error is reported to the sequence program. Thus, the sequence
program processes (a) to (d), check for the error of MWRTF2, and
outputs an alarm when MWRTF2 = 1 (error).
(f) In response, the operator should set MWRTF and MWRTF2 to 0
from the CRT/MDI panel.
(g) Resume operation after the contents of the memory and the turret
position are aligned.
(5) Data table
A sizable amount of numeric data (data table) can be used for
sequence control by the PMC. See section 6.3 for details.

355
6. NONVOLATILE MEMORY PMC SEQUENCE PROGRAM B61863E/14

6.2 All the nonvolatile memory data can be read and written by the sequence
program. The memory read and written by the PMC sequence program
READING AND is actually not a nonvolatile memory, but a nonvolatile memory image
WRITING OF (RAM) storing the same data as the nonvolatile memory. When the power
NONVOLATILE supply is turned off, the data in the nonvolatile memory image disappears.
Immediately after the power is turned on, the nonvolatile memory data is
MEMORY DATA
automatically transferred to the nonvolatile memory image. Before the
power is turned off, the data is correctly restored.
When the nonvolatile memory image is rewritten by the sequence
program, the data is automatically transferred to the CMOS or bubble
memory.
When the sequence program rewrite nonvolatile memory image of area,
the rewritten data is automatically transferred to the nonvolatile memory.
Rewriting of nonvolatile memory can also be done by rewriting optional
addresses of the nonvolatile memory image in an optional timing. The
changed data will be automatically transferred to the nonvolatile memory.
Therefore, there is not special processing necessary when the sequence
program writes or reads nonvolatile memory. It will only take some time
to write in the nonvolatile memory (512 ms).

356
B61863E/14 PMC SEQUENCE PROGRAM 6. NONVOLATILE MEMORY

6.3 (1) Introduction


PMC DATA TABLE PMC sequence control sometimes requires a sizable amount of
numeric data (herein after referred to as data table. If contents of such
data table are free to set or to read, they can be used as various PMC
sequence control data, such as tool numbers of tools on the ATC
magazine.
Each table size can be set optionally in the memory for data table, and
1-, 2-, or 4-byte binary or BCD format data can be used per each table,
thus consigning a simple-to-use table.
Data in the data table can be set in the nonvolatile memory or
displayed via the CRT/MDI panel.
Data set in the data table can also be easily read or written by the
sequence program using function instructions as data search
(DSCHB), or index modification data transfer (XMOVB).

NOTE
For details of the usable range, see I3.

(2) Configuration of the PMC data table and notes on programming


(a) Configuration of the data table
PMC data table consists of table control data and data table. Table
control data control the size and data format (BCD or binary) of
the tables.
This table control data must first be set from CRT/MDI before
preparing data table. In the sequence program, the table control
data cannot be read or written. When the contents of the
nonvolatile memory are read or written using the Floppy Cassette,
the table control data is read or written together. Fig 6.3 (a) is a
general configuration of the data table, and Fig 6.3 (b) is a detailed
configuration of the data table. Also refer to 3.7 for data table
configuration.
(b) Data table head address
If the data table starts from an odd address, for example, when a
data table is created with an odd number of one-byte data, the
DSCHB instruction operates slower than when the data table
starts from an even address. It is recommended that the starting
address of a data table be an even number.

357
6. NONVOLATILE MEMORY PMC SEQUENCE PROGRAM B61863E/14

Table control data


Data table number

D0
D1
Basic data table
(1860 bytes or 3000 bytes)

Data table

D1859
or
D2999

Fig. 6.3 (a) General configuration of data table

358
B61863E/14 PMC SEQUENCE PROGRAM 6. NONVOLATILE MEMORY

Number of
tables

Table parameter

Table 1 Data type


control data
Number of data

Data table head address

Table parameter

Table 2 Data type


control data
Number of data Table control data

Data table head address

Table parameter

Table n Data type


control data
Number of data

Address No. Data table head address


D0 Table number
0 Data
D1
1 Data table 1
D2 :
n1
Table number
0
1
2 Data
3 Data table 2
: Data table
:
n2

Table number

Table number
0 Data
1 Data table n
:
np

(Note)
n1, n2, and np are the last table number
of each data table.

Fig. 6.3 (b) Detailed configuration of data table

359
6. NONVOLATILE MEMORY PMC SEQUENCE PROGRAM B61863E/14

(3) Table control data


The table control data controls a data table
If the table control data is not properly set, a data table described in
Item (4) cannot be properly created.
Referring to the description in Item (3), set the table control data, then
create a data table.
(a) Number of groups of tables
Specify the number of groups of data tables in binary.
(b) Control data for table groups 1 to n
Each data table has table control data consisting of the starting
address of the table, table parameters, data type, and the number
of data items.
(i) Starting address of the table
Specify the starting address of the table from D0 to D1859
or D0 to D2999.
(ii) Table parameter
#7 #6 #5 #4 #3 #2 #1 #0
MASK COD

0 : A data table is specified in binary.


COD
1 : A data table is specified in BCD.

0 : The contents of the data table are not protected.
MASK
1 : The contents of the data table are protected.

(iii) Data type


Specify the length of data in the data table.
0 : One byte
1 : Two bytes
2 : Four bytes
(iv) Number of data items
Specify the number of data items used in the data table.
(4) Data table
Data table can be created within the range of the memory (D address)
for the data table and separated some groups. This number of groups
is decided with the number of tables of table control data.
The maximum of the number of table groups.
Except PMCNB max 100 tables
PMCNB max 50 tables

360
B61863E/14 PMC SEQUENCE PROGRAM 6. NONVOLATILE MEMORY

Table number

0
1

2
Table 1 (1-byte data)
3

Table 2 (2-byte data)

Each data table can be used in 1, 2 or 4 byte data. Table parameter


of table control data decides whether to use 1 or 2 byte data.
Therefore, 1 table number is taken for a 1-byte data when table data
is 1 byte; 2 byte data when table data is 2 bytes.
(5) Entering data in a data table
Specify a location number in the data table from the CRT/MDI panel,
then enter the data. A number for each location in the table is defined
for each data table group.

NOTE
Reading and Writing of the data table are available from the
sequence program.

361
7. LADDER DIAGRAM FORMAT PMC SEQUENCE PROGRAM B61863E/14

7 LADDER DIAGRAM FORMAT

A designer examines and checks the ladder diagram in the process of


design. However, it should be noted that other persons (maintenance
servicemen, for example) read the ladder diagram far longer than the
designer.
Accordingly, the ladder diagram must be written to be easily understood
by all persons.
For this purpose, applicable symbols, writing method, and other methods
are specified as detailed below.

362
B61863E/14 PMC SEQUENCE PROGRAM 7. LADDER DIAGRAM FORMAT

7.1 Addresses, signal names, comments, and line numbers must be inserted
into a ladder diagram to enable all users to easily read the ladder diagram.
ADDRESSES,
SIGNAL NAMES,
COMMENTS, AND
LINE NUMBERS

7.1.1 Each address consists of an address number and a bit number, and it is
represented as follows.
Addresses

Bit number (0 to 7)

Address number
(A numeric of 4 digits or less after an alphabetic character)

An alphabetic character is prefixed to the start of each address number to


represent the kinds of signals as shown in Table 7.1.1.

Table 7.1.1 Alphabetic symbols of address numbers

Symbol Type of signal


X Input signal entered from machine tool to PMC (MTPMC)
Y Output signal sent from PMC to machine tool (PMCMT)
F Input signal entered from CNC to PMC (CNCPMC)
G Output signal sent from PMC to CNC (PMCCNC)
R Internal relay
A Message display request
C Counter
K Keep relay
D Data table
T Variable Timer
L Label number
P subprogram number

363
7. LADDER DIAGRAM FORMAT PMC SEQUENCE PROGRAM B61863E/14

7.1.2 Suitable symbols shall be attached to I/O signals as signal names


Signal Names according to the following procedure.
(1) The names of all signals containing CNC signals and machine tool
signals are represented within 6 characters.
Alphanumeric characters and special symbols described in this
manual are all employable.
(2) For CNCPMC signal names, signal names shown in the PMC
address table are employable as they are.
(3) CNC signals to be entered from the machine tool and CNC signals
to be sent to the machine tool are identified from each other by
prefixing X or Y to the start of these CNCPMC signal names,
respectively. A single block input signal is represented as XSRK by
prefixing X, while a start lamp output signal is represented as YSTL
by prefixing Y, for example. However, when X or Y is prefixed to the
start of an CNCPMC signal name, certain signal names exceed 6
characters. In such a case, omit the last character from such a signal
name (*SECLPX*SECL)

7.1.3 A comment of within 30 characters can be inserted to a relay coil in a


Comments sequence program and each symbol in a symbol table.
When relay coils are output signals to the machine tool, insert a detailed
description of the signal to all relay coils as the comment to be inserted
to the relay coil. Also insert a detailed description of the signal when other
auxiliary relays are significant in sequence control.
Be sure to insert detailed descriptions of machine toolrelated input
signals, in particular, as comments in symbol tables.
Detailed comments are necessary as it is difficult to guess the meanings
of signals specific to the machine tool by judging the symbol name alone.

7.1.4 A line number should be attached to each line of the ladder diagram. For
Line Numbers details, refer to Sec. 7.3.

364
B61863E/14 PMC SEQUENCE PROGRAM 7. LADDER DIAGRAM FORMAT

7.2
Symbol Description
SYMBOLS USED IN
These are the contacts of relays in the PMC, and
THE LADDER A contact
are used for other input from the machine side
DIAGRAM and CNC
B contact

These are input signals from the CNC.


A contact

B contact

These are input signals from the machine side


A contact (including the built-in manual control panel).

B contact

These are timer contacts in the PMC


A contact

B contact

This is a relay coil whose contact is used only in


the PMC.

This is a relay coil whose contact is output to


CNC.

This is a relay coil whose contact is output to the


machine side.

This is the coil of a timer in the PMC.

This is a PMC fucnctional instruction. The actual


form varies depending on the instruction.

NOTE
If the coil is represented by or , the relay is within the
PMC, and the contact uses or .

365
7. LADDER DIAGRAM FORMAT PMC SEQUENCE PROGRAM B61863E/14

7.3 (1) Format


The size should be A3 or A4 (JIS standard).
LADDER DIAGRAM
(2) Columns are used for wiring.
FORMAT

3A
3B
Line number

3P

Spindle control

(3) Divide the circuits into several functions. And program the same
function in a single program.
Example) Mode control.spindle control, turret control, APC control.
(4) Assign a line number to each line as follows:

Line symbol (A to Z)

Page number (1 to 999)

(5) Write a relay contact with a signal name of the relay coil, line number
and address.
Signal name

Address
Line number

(6) For complicated timing, timing chart should be on the same page of
the ladder diagram.
(7) The meaning of the code numbers for the S, T, and M functions
should be listed on the ladder diagram.
(8) The 1st level sequence part should be written at the beginning of the
ladder diagram.
(9) The following data should be written on the first page of the ladder
diagram:
(i) The sequence program design number
Machine tool builder shall assign design numbers of sequence
program and ROMs and manage them.
(ii) Description of symbol
(iii) Setting table of timer, counter, and PMC parameters and meaning
of them.
(iv) Description of functional instruction.
(10) Easy-to-understand name should be assigned.

366
B61863E/14 PMC SEQUENCE PROGRAM 7. LADDER DIAGRAM FORMAT

7.4 A general relay sequence circuit has a finite number of contacts, so several
relays use one contact in common so as to reduce the number of contacts
INFINITE NUMBER used as much as possible.
OF RELAY
CONTACTS

R1

R2

The PMC is considered to have an infinite number of relay contact and


is written as in the figure below.

A
R1

A B

R2

367
8. MISCELLANEOUS ITEM PMC SEQUENCE PROGRAM B61863E/14

8 MISCELLANEOUS ITEM

To create a ladder program related to the axis-control function by the


PMC, refer to the subsection, Axis-control function by the PMC, in the
Connecting Manual.

368
9. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM STRUCTURING

9 SEQUENCE PROGRAM STRUCTURING

f : Can be used
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

With the conventional PMC, a Ladder program is described sequentially.


By employing a Ladder language that allows structured programming, the
following benefits are derived:
D A program can be understood and developed easily.
D A program error can be found easily.
D When an operation error occurs, the cause can be found easily.

369
9. SEQUENCE PROGRAM
STRUCTURING PMC SEQUENCE PROGRAM B61863E/14

9.1
EXAMPLES OF
STRUCTURED
PROGRAMMING

9.1.1 Three major structured programming capabilities are supported.


Implementation (1) Subprogramming
Techniques A subprogram can consist of a Ladder sequence as the processing
units.

Job A f

FUNC f
Job B


(2) Nesting
Ladder subprograms created in 1 above are combined to structure a
Ladder sequence.
Main Program Sub Program1 Sub Program2

Job A Job A1 Job A11

D
D
Job B D Job A12

Job An

(3) Conditional branch


The main program loops and check whether conditions are satisfied.
If a condition is satisfied, the corresponding subprogram is executed.
If the condition is not satisfied, the subprogram is skipped.

Main Program Sub Program

PROCESS11 PROCESS11
STATE1 PROCESS1

PROCESS12
STATE2 PROCESS2

PROCESS13

370
9. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM STRUCTURING

9.1.2 (1) Example


Applications Suppose that there are four major jobs.

If Y0 is 1, a request to machine a workpiece is assumed, and


A processing is performed (with a condition).
A : 1 Pick up a workpiece from a pallet. (A1)
2 Machine the workpiece. (A2)
3 Return the workpiece to the pallet. (A3)
B
B : 4 Move the pallet.

(2) Program structure


Sub Program P1 Sub Program P2 Sub Program P3 Sub Program P4

A A1 A1 A2

B A2 Sub Program P5 Sub Program P6

A3 B
A3

(3) Program description


Main Program

END1

Y0
CALL MAIN Machine a workpiece.

END2

Sub Program P1 (=MAIN)

SP MAIN


CALL A Machine a workpiece.


CALL B Move a pallet.

SPE

371
9. SEQUENCE PROGRAM
STRUCTURING PMC SEQUENCE PROGRAM B61863E/14

Sub Program P2 (=A)

SP A


CALLU A1 Pick up a workpiece from a pallet.


CALLU A2 Machine the workpiece.


CALLU A3 Return the workpiece to the pallet.

SPE

Sub Program P3 (=A1)

SP A1


Pick up a workpiece
from a pallet. Ladder coding

SPE

Sub Program P4 (=A2)

SP A2


Machine the workpiece. Ladder coding

SPE

Sub Program P5 (=A3)

SP A3


Return the workpiece to Ladder coding
the pallet.
SPE

372
9. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM STRUCTURING

Sub Program P6 (=B)

SP B


Move the pallet. Ladder coding

SPE

9.1.3 (1) Main program


Specifications The main program is the Ladder program consisting of the first- and
second-level Ladder programs. One, but only one, main program can
be created. A subprogram cannot be called from the first-level
Ladder program. Any number of subprograms however, can be
called from the second-level Ladder program. The functional
instructions JMP and COM must be completed within each main
program or subprogram.
(2) Subprogram
A subprogram is a program called by the second-level Ladder
program. It is a program unit starting with the functional instruction
SP and ending with the functional instruction SPE. Up to 512
subprograms can be created for one PMC.
(3) Nesting
A subprogram can call another subprogram. The maximum nesting
depth is eight levels. Recursive calls are not allowed.

373
9. SEQUENCE PROGRAM
STRUCTURING PMC SEQUENCE PROGRAM B61863E/14

9.2
SUBPROGRAMMING
AND NESTING

9.2.1 Conditional JUMP (or unconditional JUMP) is coded in the main


Function program, and the name of a subprogram to be executed is specified. In
the subprogram, the name of the subprogram and a Ladder sequence to
be executed are coded.
When a subprogram is named Pn (program name), and this name is
specified in conditional JUMP, the subprogram is executed by calling it.
A symbol and comment can be added to Pn to assign a subroutine name.
In the example shown in Fig. 9.2.1, the main program calls three
subprograms. These calls are all conditional calls. Subprogram P1 is
named SUBPRO. It calls subprogram PROCS1 unconditionally.
Main Program Sub Program P1 (=SUBPRO)

END1 SP SUBPRO

f
CALL SUBPRO
CALLU PROCS1

CALL P2 f

CALL P3
ADD 0001 f
B 0001
END2 F10

R200

SPE

Fig. 9.2.1 Example of subprogramming and nesting

374
9. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM STRUCTURING

9.2.2 The main program is always active. Subprograms on the other hand, are
Execution Method active only when called by another program.
In the following example, subprogram SUBPRO is called by signal A.

Main Program Sub Program


f
SP SUBPRO
END1
f
A
CALL SUBPRO

END2 SPE

Program cycle

Signal A

Main program

a b c d a
Subprogram

Management
program

Flow of execution
a : Functional instruction CALL calls a subprogram in order to
transfer control to the subprogram.
b : When the end of the subprogram is reached, control is returned to
the main program.
c : When the end of the main program is reached, the management
program performs Ladder program postprocessing.

375
9. SEQUENCE PROGRAM
STRUCTURING PMC SEQUENCE PROGRAM B61863E/14

9.2.3 Create subprograms in the same way as the first-, second-, and third-level
Creating a Program Ladder programs.
Example of creation

END1
A

CALL SUBPRO

END2

SP SUBPRO

SPE

SP P20

SPE

END Must create

376
9. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM STRUCTURING

Inhibit items
(1) Subprograms are nested.

SP SUBPRO

SPE

SPE

(2) A subprogram is created within the first-, second-, or third-level


Ladder program.

END1

SP SUBPRO

END2

377
9. SEQUENCE PROGRAM
STRUCTURING PMC SEQUENCE PROGRAM B61863E/14

9.3 a) DISPB
CAUTIONS FOR b) EXIN
SUBROUTINES c) WINDR (only low-speed response)
d) WINDW (only low-speed response)
e) MMCWR
f) MMCWW
g) MMC3R
h) MMC3W
When you use the above-mentioned functional instructions, ACT=1 must
be held until the transfer completion information(W1) becomes 1.
Therefore, be careful of the following when using those instructions in
subprograms.
D Do not stop calling the subprogram at the state which has not been
completed yet, that is executed still while using the instructions in the
subprogram.
(In other words, do not set the ACT of the CALL instruction to 0)
If you do it the function of the instructions after that is not
guaranteed.
D Call the subprogram from other subprograms at the state which has
not been completed yet while using the instructions in the
subprogram.
The movement of the above-mentioned functional instruction
after that is not guaranteed so that the last functional instruction
may be processing the instruction.
Then, when the subprogram, in which the above-mentioned functional
instruction is used, is called from two or more places, it is necessary to
control the subprogram exclusively. The case of the WINDR instruction
(low-speed response) is given as an example here.

378
9. SEQUENCE PROGRAM
B61863E/14 PMC SEQUENCE PROGRAM STRUCTURING

Example)
When subprogram is called from two places. (The WINDR
instruction is used)

Main program Subprogram 1 Subprogram 2

C2
JMPB L4 SP S-PRO1 SP S-PRO2

C1 B A B
DATA1 SET JMPB L1 WINDR DATA

C1 ON A
CALL S-PRO1 SPE
A
A C1 CALL S-PRO2

B
C2
JMPB L2
C1
JMPB L3
LBL L1

LBL L4 ON A

C2
DATA2 SET CALLU S-PRO2

C2
CALL S-PRO1 LBL L2

A C2
SPE
C1

LBL L3

Description)
Subprogram 1 controls ACT(A)and W1(B)of WINDR (subprogram 2).
By A controlled in subprogram 1, the main program decides which
relay (C1,C2) to be effective.
When the WINDR instruction is completed, the following data will
be set and the other CALL instruction is started.
It keeps working in this way.

379
10. JMP INSTRUCTIONS WITH
LABEL SPECIFICATION PMC SEQUENCE PROGRAM B61863E/14

10 JMP INSTRUCTIONS WITH LABEL SPECIFICATION

f : Can be used
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6

f f f f f f f f f f f f f

380
10. JMP INSTRUCTIONS WITH
B61863E/14 PMC SEQUENCE PROGRAM LABEL SPECIFICATION

10.1 (1) Relationship between JMPB/JMPC and LBL


(Forward and backward jumps to the same label are possible.)
SPECIFICATIONS
JMPB A f : Possible

LBL A

f f

JMPB A

JMPC A

CAUTION
The specifications allow backward jumps. A backward
jump, however, may result in an infinite loop or cause the
execution time of the first-level Ladder program to exceed
1.5 ms (or 5 ms). Create a program carefully so an infinite
loop does not occur.

381
10. JMP INSTRUCTIONS WITH
LABEL SPECIFICATION PMC SEQUENCE PROGRAM B61863E/14

(2) Same label


(A label can be used more than once as long as it is unique within the
main program or each subprogram.)

LBL A

First level LBL B

END1

Second level
LBL C

END2

SP A SP A

LBL C

SPE

SP B

SP B

LBL B

SPE

CAUTION
As mentioned in (8) of Section 10.2, the same label must not
exist in the first- and second-level Ladder programs.

(3) Number of labels


First-and second-level Ladder programs : Up to 256 labels
Subprogram : Up to 256 labels for each subprogram
Label number : L1 to L9999

382
10. JMP INSTRUCTIONS WITH
B61863E/14 PMC SEQUENCE PROGRAM LABEL SPECIFICATION

(4) Relationship between JMP/JMPE and JMPB/JMPC


(JMPB and JMPC can be used with JMP and JMPE freely.)

JMPB A
f : Possible

JMPE f

LBL A

JMPB D
f
JMPB B

JMP f

LBL B

JMPB C
f
LBL C

JMPE

LBL D

(5) Relationship between CALL/CALLU and JMPB/JMPC


(JMPB and JMPC can be used with CALL and CALLU freely.)

JMPB C f : Possible
f
JMPB A
f
CALL

LBL A

JMPB B
f

CALLU

LBL B

LBL C

383
10. JMP INSTRUCTIONS WITH
LABEL SPECIFICATION PMC SEQUENCE PROGRAM B61863E/14

(6) Position of JMPC


(JMPC coded between COM and COME can cause a jump.)

LBL A f : Possible

f
Second level

END2

SP B

SP A COM

JMPC A

COME

SPE

384
10. JMP INSTRUCTIONS WITH
B61863E/14 PMC SEQUENCE PROGRAM LABEL SPECIFICATION

10.2 (1) Jump destination of JMPB (1)


(A jump over END1 or END2 is inhibited.)
RESTRICTIONS
f : Possible
LBL A
: Impossible

JMPB B
f

First level LBL B

JMPB C

END1

Second level LBL C

JMPB A

END2

(2) Jump destination of JMPB (2)


(A jump must be performed within a subprogram.)

f : Possible
JMPB A : Impossible
f
LBL A
SP A
JMPB B

SPE

SP B
SP B

LBL B

SPE

385
10. JMP INSTRUCTIONS WITH
LABEL SPECIFICATION PMC SEQUENCE PROGRAM B61863E/14

(3) Jump destination of JMPB (3)


(A jump over COM or COME is inhibited.)

JMPB A f : Possible
: Impossible

COME

LBL A

JMPB D

f
JMPB B

COM

LBL B

JMPB C
f
LBL C

COME

LBL D

386
10. JMP INSTRUCTIONS WITH
B61863E/14 PMC SEQUENCE PROGRAM LABEL SPECIFICATION

(4) Jump destination of JMPC (1)


(A jump to the first-level Ladder program is inhibited.)

f : Possible
LBL A : Impossible

First level

END1

Second level
LBL B
f

END2

SP A

SP A

JMPC B

JMPC A

SPE

387
10. JMP INSTRUCTIONS WITH
LABEL SPECIFICATION PMC SEQUENCE PROGRAM B61863E/14

(5) Jump destination of JMPC (2)


(A jump to a label between COM and COME is inhibited.)

: Impossible
COM

LBL A
Second level

COME

END2

SP A
SP A

JMPC A

SPE

(6) Jump destination of JMPC (3)


(Control must not be returned to a label that appears earlier than the
instruction that has called the subprogram.)
: Impossible

LBL A

Second level

CALL A

END2

SP A
SP A

JMPC A

SPE

CAUTION
Although Ladder diagrams can be edited, editing a Ladder
diagram may cause an infinite loop. So, be careful not to
program such processing.

388
10. JMP INSTRUCTIONS WITH
B61863E/14 PMC SEQUENCE PROGRAM LABEL SPECIFICATION

(7) LBL for JMPB (1)


(There is no LBL in the same subprogram.)

LBL A

Second level

END2

SP A
SP A

JMPB A

SPE

(8) LBL for JMPB (2)


(The same LBL is found in the first- and second-level Ladder
programs.)

JMPB A

First level
LBL A

END1

Second level

LBL A

END

389
10. JMP INSTRUCTIONS WITH
LABEL SPECIFICATION PMC SEQUENCE PROGRAM B61863E/14

(9) LBL for JMPC


(There is no LBL in the second-level Ladder program.)

LBL A
Second level

END2

SP A
SP A

JMPC B

SPE

390
11. INTERRUPTTYPE
B61863E/14 PMC SEQUENCE PROGRAM PMC FUNCTION

11 INTERRUPTTYPE PMC FUNCTION

NOTE
This function is available only in the PMCSB5/SB6 for the
Power Mate iH. It requires the interrupttype PMC option.

391
11. INTERRUPTTYPE
PMC FUNCTION PMC SEQUENCE PROGRAM B61863E/14

11.1 This function enables the discontinuation of the current sequence


program (secondlevel sequence section) and the execution of another
OVERVIEW sequence program (conventional firstlevel sequence section) when
urgent execution of the latter sequence program becomes necessary.
The interrupt program is called for execution on the rising and/or falling
edges of an interrupt input (one of eight points X1003.0 to X1003.7).

[Conventional] [Interrupt]
8ms

Interrupt input signal


(X1003)

Interrupt
First level

Second level Second level

System processing System processing

Fig. 11.1 Sequence program execution order

392
11. INTERRUPTTYPE
B61863E/14 PMC SEQUENCE PROGRAM PMC FUNCTION

11.2 The following NC parameters specify the conditions for the interrupt
input signals.
SETTING
D NC parameters (bit type)

#7 #6 #5 #4 #3 #2 #1 #0
8731 EPMC7 EPMC6 EPMC5 EPMC4 EPMC3 EPMC2 EPMC1 EPMC0

EPMCn Whether to use bit n of X1003 as an interrupttype PMC


0 : Not used.
1 : Used.

#7 #6 #5 #4 #3 #2 #1 #0
8732 UPEG7 UPEG6 UPEG5 UPEG4 UPEG3 UPEG2 UPEG1 UPEG0

UPEGn Whether to use the interrupttype PMC on the rising edge of a signal
defined by bit n of X1003
0 : Not used.
1 : Used.

#7 #6 #5 #4 #3 #2 #1 #0
8733 DWEG7 DWEG6 DWEG5 DWEG4 DWEG3 DWEG2 DWEG1 DWEG0

DEWGn Whether to use the interrupttype PMC on the falling edge of a signal
defined by bit n of X1003
0 : Not used.
1 : Used.
(Example) The following settings specify that the rising edge of bit 0
of X1003, the falling edge of bit 1 of X1003, and both the
rising and falling edges of bit 7 of X1003 be used as
conditions for interrupt program execution.

#7 #6 #5 #4 #3 #2 #1 #0
8731 1 0 0 0 0 0 1 1

#7 #6 #5 #4 #3 #2 #1 #0
8732 1 0 0 0 0 0 0 1

#7 #6 #5 #4 #3 #2 #1 #0
8733 1 0 0 0 0 0 1 0

393
11. INTERRUPTTYPE
PMC FUNCTION PMC SEQUENCE PROGRAM B61863E/14

11.3
INTERRUPT
PROCESSING

11.3.1 This function uses a conventional firstlevel sequence section as an


Interrupt Program interrupt program.
Only one interrupt program is supported. More than one interrupt input
condition (up to 8 points from bit 0 to bit 7 of X1003) can be specified
as the conditions for executing the interrupt program. In this case, if any
one condition is satisfied, the interrupt program is executed. To define a
different process in the interrupt program for each interrupt input signal,
create the interrupt program by referencing Section 11.4, Sequence
Program Examples.

[Conventionally] [With interrupt used]

Run at 8ms intervals Run on interrupt input


Firstlevel Interrupt program
sequence section

END1(SUB1) END1(SUB1)

Run at 8 x nms intervals Run at 8 x nms intervals


Secondlevel (nonsplit method) Secondlevel (nonsplit method)
sequence section sequence section

END2(SUB2) END2(SUB2)

SP(SUB71) SP(SUB71)

Subprogram Subprogram

SPE(SUB72) SPE(SUB72)

END(SUB64) END(SUB64)

Fig. 11.3.1 Sequence program configuration

394
11. INTERRUPTTYPE
B61863E/14 PMC SEQUENCE PROGRAM PMC FUNCTION

11.3.2 Input/output signals (F, G, X, Y addresses) between the NC and machine


Input/Output Signal are processed asynchronously except for builtin I/O units (X1000 to
X1003, X1007, Y1000 to Y1002). (Usually, processing for NC <> PMC
Processing (F/G), Link master (X0 to X127), and I/O Link slave (X1020 to X1051,
Y1020 to Y1051) is performed at 8, 2, or 8ms intervals, respectively.)
When an interrupttype PMC is used, input signals (X1000 to X1003,
X1007) from a builtin I/O unit are read immediately before the interrupt
program is executed. Output signals (Y1000 to Y1002) to a builtin I/O
unit are written immediately after the interrupt program is executed.
Builtin I/O signals are processed at 8ms intervals even when the
interrupt program is not executed.
The same signal is read from both X1007 and X1003, but signal changes
in X1007 can be read faster. Therefore, ladder programs should use
X1007 rather than X1003 when referencing an input signal.
To enable the interrupt program to judge interrupt input trigger
conditions, the interrupt request status (which of the signals defined by
bit 0 to bit 7 of X1003 causes the interrupt) is output to an internal relay
(R9021).
D Interrupt relay R9021 (interrupt request status)
#7 #6 #5 #4 #3 #2 #1 #0
R9021

This relay indicates the status of an interrupt request corresponding to


each interrupt input signal (bit 0 to bit 7 of X1003).
When a bit is set to 1, it indicates that the corresponding signal is
requesting an interrupt.

11.3.3 The interrupt program is executed within 0.5 ms (software response time)
after an interrupt input signal is received. If there is an interruptinhibited
Response Time
interval, the execution of the interrupt program is deferred by the
corresponding time. If another interrupt input signal is received when the
interrupt program is already running, the newly received signal is kept
waiting until the current execution ends.

395
11. INTERRUPTTYPE
PMC FUNCTION PMC SEQUENCE PROGRAM B61863E/14

11.3.4 The execution time of the interrupt program must be within about 6 ms,
Execution Time even in the worst case.
If an interrupt program whose execution time is longer than 6 ms is
executed, or if too many interrupt requests are made, a PMC alarm (WN08
INTERRUPT LADDER TIME OVER) is issued.
The maximum execution time of the interrupt program can be checked
using the internal relay (R9022 to R9023).
D Internal relay R9022 to R9023 (interrupt program maximum
execution time)
R9022 Interrupt ladder program maximum execution time [10 s]

This data is the maximum allowable execution time for the interrupt
ladder program. (0 to 655,350 s)
D PMC alarm message (alarm screen)
Alarm message Meaning and response

WN08 INTERRUPT The execution time of the interrupt ladder has ex-
LADDAR TIME OVER ceeded the allowable value (about 6 ms). The
interrupt program is too large, or too many inter-
rupt requests were issued. So, the second level of
the ladder has operated.
(Response) Make the interrupt program smaller,
or reduce the number of interrupt requests.

CAUTION
Check the execution time of the interrupt program with the
internal relay mentioned above, and change the program to
keep the regular interrupt program execution time within 2
ms.

11.3.5 The WINDW machine instruction (with function code 10000) is used to
enable, disable, and clear (that is, nullify all internally stored requests for)
Interrupt
interrupts in the secondlevel program.
Enable/Disable/Clear If an interrupt request arises when an interrupt has been disabled, interrupt
program execution is deferred until an interrupt is enabled.
The secondlevel program is initially in an interrupt disabled state. Any
interrupt request is rejected before the NC preparation completed signal
MA (F1.7) is input. To enable immediately when the power is applied,
execute the WINDW machine instruction (with function code 10000),
using the preparation completed signal MA (F1.7) signal. (See Section
11.4, Sequence Program Examples.)
D Window function (with function code 10000 for enabling, disabling,
and clearing interrupts)
[Description of data]
Interrupttype PMC interrupts are enabled, disabled, and cleared.

396
11. INTERRUPTTYPE
B61863E/14 PMC SEQUENCE PROGRAM PMC FUNCTION

[Input data structure]

Top address+0
(Function code)

10000

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)

+6
(Data number)
N N=1 to 3
(N = data specification) 1: Enable interrupts. (All conditions)
2: Disable interrupts. (All conditions)
3: Clear interrupts. (All conditions)
+8
(Data attribute)

(Need not be set)

+10

[Completion code types]


0: Interrupt setting has been completed normally.
3: The specified data number is incorrect. (Data other than 1, 2, or 3 was
specified.)
6: The interrupttype PMC option is not available. Alternatively,
conditions for setting the interrupt input signals specified in the
relevant NC parameters are incorrect.
[Output data structure]

Top address+0
(Function code)

10000

+2
(Completion code)
?
(See the above descriptions
about the completion codes.)
+4
(Data length)
?
(Data at input)

+6
(Data number)
N
(Data at input)

+8
(Data attribute)
?
(Data at input)

+10

397
11. INTERRUPTTYPE
PMC FUNCTION PMC SEQUENCE PROGRAM B61863E/14

11.3.6 Machine instructions not usable in the interrupt program


Cautions (1) TMR (timer), TMRB (fixed timer), and TMRC (timer)
The least input increment for the timer values is 8 ms, so it may not
be possible to measure time accurately.
(2) CTR (counter), CTRC (counter), DIFU (rising edge detection), DIFD
(falling edge detection)
Because the rising or falling signal edge is handled, it is necessary to
execute the interrupt program twice in order to check for signal
changes. Furthermore, the DIFU and DIFD outputs are held to 1 until
the interrupt program is executed again.
(3) DISPB (message display), EXIN (external data input), lowspeed
WINDR/WINDW (NC window data read/write), and AXCTL (PMC
axis control)
It takes at least two cycles (one cycle = 8 ms) to complete the execution
of each of these instructions. In addition, the execution of the EXIN,
lowspeed WINDR/WINDW, and AXCTL instructions involve
exclusive control. If the interrupt program is terminated before
completion, these instructions are disabled in the secondlevel
sequence program.
(4) CALL (conditional subprogram call) and CALLU (unconditional
subprogram call)
These instructions are unusable, in the same way as the conventional
firstlevel program.

398
11. INTERRUPTTYPE
B61863E/14 PMC SEQUENCE PROGRAM PMC FUNCTION

Continuous interrupt processing


After the interrupt program has been started by a certain interrupt signal,
if another interrupt signal occurs, it is processed after the current interrupt
processing is completed.
(Example) Rising edges of bits 0 and 1 of X1003

Interrupt input signal


(X1003.0)

Interrupt input signal


(X1003.1)

Executed later

Interrupt program

Fig. 11.3.6 (a) Continuous interrupt operations triggered


by different signals

After the interrupt program has been started by a certain interrupt signal,
if the same interrupt signal occurs again, it is ignored.
(Example) Rising edge of bit 0 of X1003

Interrupt input signal


(X1003.0)

Interrupt program This interrupt


request is
ignored.

Fig. 11.3.6 (b) Continuous interrupt operations triggered


by the same signal

If both the rising and falling edges of a certain interrupt input signal are
specified for interrupt, the falling (rising) edge is ignored if it is detected
during the interrupt program execution requested on the rising (falling)
edge. So, it is necessary to complete the interrupt program execution
before the interrupt input signal changes.

399
11. INTERRUPTTYPE
PMC FUNCTION PMC SEQUENCE PROGRAM B61863E/14

11.4 (1) Interrupt program that handles interrupt requests separately


Use of R9021 together with a label jump enables processing interrupt
SEQUENCE requests separately as shown below.
PROGRAM
EXAMPLES
R9021.0 JMPB L0001
SUB68

Sequence program triggered by interrupt


input signal bit 0 of X1003.0
(executed only when bit 0 of R9021.0 = 1)

LBL L0001
SUB69

R9021.1 JMPB L0002


SUB68

Sequence program triggered by interrupt


input signal bit 1 of X1003.1
(executed only when bit 1 of R9021.1 = 1)

LBL L0002
SUB69

END1
SUB1

400
11. INTERRUPTTYPE
B61863E/14 PMC SEQUENCE PROGRAM PMC FUNCTION

(2) Enabling interrupts immediately when the power is applied

MA(F1.7) DIFU 1 R0.0


MA
SUB57
signal
rising

R0.0 NUMEB 2
SUB40 10000
R100

R0.0 NUMEB 2
SUB40 1
R106

R0.0 R1.0
WINDW R100
Interrupt
SUB52
enable

END2
SUB2

401
11. INTERRUPTTYPE
PMC FUNCTION PMC SEQUENCE PROGRAM B61863E/14

(3) Specifying an interruptdisabled interval

R9091.1 NUMEB 2
SUB40 10000
R100

R9091.1 NUMEB 2
SUB40 1
R106

R9091.1 NUMEB 2
SUB40 10000
R200

R9091.1 NUMEB 2
SUB40 2
R206

R9091.1 R2.0
WINDW R200
Interrupt
SUB52
disable

Interruptdisabledinterval

R9091.1 R1.0
WINDW R100
SUB52 Interrupt
enable

END2
SUB2

402
II. PMC OPERATION (CRT/MDI)
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

1 GENERAL

The following PMC data can be set and displayed by using the CRT/MDI
panel.
1) PMC I/O signal display and internal relay display (PMCDGN)
PMCDGN has following screens.
a) Title data display
b) Status screen
c) Alarm screen
d) Trace function
e) Memory display
f) Signal Wareform display function
g) User task execution status display function
2) PMC data setting and display (PMCPRM)
The following PMC data are provided.
a) Timer
b) Counter
c) Keep relay
d) Data table
3) Display of sequence program ladder diagram (PMCLAD)
4) PMC screen (PMCMDI) for the user
Press the function key <CUSTOM> on the CRT/MDI panel first.

NOTE
This function key is effective when a user program exists in
the PMCRC.

Switch the NC and PMC menus as described below.


NC screen to PMC screen
Press the SYSTEM function key on the CRT/MDI panel. Selecting the
PMC soft key displays the PMC basic menu.
PMC screen to NC screen
D Pressing the RETURN key (the leftmost key) on the PMC basic
menu screen changes the menu to the NC soft key menu.
D Selecting a function key on the PMC screen changes the screen to the
corresponding NC screen.
Figs. 1 a) to 1 l) show the standard CRT/MDI panels.

NOTE
A key in < > is a function key on the CRT/MDI panel. A key
in [ ] is a soft key described below.

405
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

a) 9 small monochrome/color CRT/MDI panel for 16TA/18TA


(Horizontal type)

Function keys Address/numeric keys

SHIFT key
Cancel key
INPUT key

Edit keys

HELP key
RESET key

Soft keys Page keys


Cursor control keys

b) 9 monochrome/color CRT/MDI panel for 16TA/18TA


(Horizontal type)

RESET key
HELP key Address/numeric keys

Edit keys

Cancel key

INPUT key

Soft keys Page keys Function keys


Power on/off buttom SHIFT key Cursor control keys

406
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

c) 10 color LCD/MDI panel for 16TA/18TA (Horizontal type)

Function keys Address/numeric keys

Cancel key
SHIFT key
INPUT key

HELP key
RESET key

Page keys Edit keys


Soft keys
Power on/off buttom Cursor control keys

d) 10 color LCD/MDI panel for 16TA/18TA (Vertical type)

Power on/off buttom

Soft keys

RESET key Function keys

HELP key Edit keys

Cursor control keys


SHIFT key

Address/numeric keys Page keys


INPUT key
Cancel key

407
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

e) 14 color CRT/MDI panel for 16TA/18TA (Horizontal type)

RESET key
Address/numeric keys HELP key

SHIFT key

Edit keys

INPUT key
Cancel key
Function keys

Cursor control keys

Power on/off buttom Page keys


Soft keys

f) 14 color CRT/MDI panel for 16TA/18TA (Vertical type)

Soft keys

RESET key
Function keys
HELP key Edit keys
Cursor control keys

Address/numeric keys Page keys


Power on/off buttom INPUT key
SHIFT key Cancel key

408
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

g) 9 small monochrome/color CRT/MDI panel for


16MA/18MA (Horizontal type)

Function keys Address/numeric keys

SHIFT key
Cancel keys
INPUT key

Edit keys

HELP key
RESET key

Page keys
Soft keys
Cursor control keys

h) 9 monochrome/color CRT/MDI panel for 16MA/18MA


(Horizontal type)

RESET key
HELP key Address/numeric keys

Edit keys

Cancel key

INPUT key

SHIFT key Cursor control keys


Power on/off buttom Soft keys Function keys
Page keys

409
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

i) 10 color LDC/MDI panel for 16MA/18MA (Horizontal type)

Function keys Address/numeric keys

Cancel key
SHIFT key
INPUT key

HELP key
RESET key

Page keys Edit keys


Soft keys
Cursor control keys
Power on/off buttom

j) 10 color LCD/MDI panel for 16MA/18MA (Vertical type)

Power on/off buttom

Soft keys

RESET key Function keys

HELP key Edit keys

Cursor control keys


SHIFT key

Address/numeric keys Page keys


INPUT key
Cancel keys

410
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

k) 14 color CRT/MDI panel for 16MA/18MA (Horizontal type)

RESET key
Address/numeric keys HELP key

SHIFT key

Edit keys

INPUT key
Cancel key
Function keys

Cursor control keys

Power on/off buttom Page keys


Soft keys

l) 14 color CRT/MDI panel for 16MA/18MA (Vertical type)

Soft keys

RESET key
Function keys

HELP key Edit keys

Cursor control keys

Address/numeric keys Page keys


Power on/off buttom
INPUT key
SHIFT key Cancel key

411
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

1.1 Note the followings when you input PMCaddress on the original MDI
boards made by MTBs without using Standard MDI Unit supplied by
FOR MDI UNITS FANUC.
OTHER THAN
(1) If the MDI has the keys to input PMCaddress (X, Y, F, G, R, A, C,
STANDARD MDI K, D, T), You can operate as same as FANUC Seires 18
UNITS (FOR FS20 (PMCSA1/SA3).
PMCSA1 AND SA3) (2) If MDI does not have those keys, input PMCaddress as follows.
When inputting PMCaddress (in PCLAD, STATUS and so on), you
can substitute number keys (0 to 9) and a hyphen key () for
PMCaddress capital keys (X, Y, F, G, etc.). PMCaddress capital
keys are corresponding to the number keys as follows.
PMCaddress keys G F Y X A R T K C D
number keys 0 1 2 3 4 5 6 7 8 9

(Example) If you want to input X0.0 [SRCH] , input 30.0 [SRCH] .

1.2 When a valid sequence program is contained in the PMC, automatic


operation can be started immediately after poweron by keep relay
AUTOMATIC setting. This eliminates the need to display the PMC screen and run a
OPERATION WHEN sequence program each time the power is turned on. The keep relay
THE POWER IS setting method depends on the PMC model. See Section 4.3.3.
TURNED ON

1.3 When the power for the CNC is turned on for the first time, a RAM
PARITY or NMI alarm may occur in the PMC. This is caused by invalid
CLEARING THE data in the sequence program storage area in the PMC. The sequence
SEQUENCE program must be cleared to prevent this.
PROGRAM The automatic operation (see 1.2 above) can also be stopped by clearing
the sequence program in the PMC.
The sequence program can be cleared in either of the following two ways:
1. Turn on the power while pressing X and O.
2. Turn on the power, display the PMC screen, and use the programmer
function of the PMC (EDIT/CLEAR).

NOTE
In case of loader control function, turn on the power while
pressing X and 5.

412
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

1.4 The PMCPA1 and PA3 contained in the Power Mate have a sequence
program called the standard ladder in their ROM to operate the Power
LOADING THE Mate without creating a sequence program.
STANDARD LADDER
Operation)
(FOR Power MateD/F
Parameter in the Power Mate
PMCPA1 AND PA3)
#7 #6 #5 #4 #3 #2 #1 #0
8703 FLA

#0 (FLA) = 0 : The FANUC standard ladder is not used.


1 : The FANUC standard ladder is used.
(1) Set bit 0 (FLA) of NC parameter 8703 to 1.
This generates alarm 000 (poweroff request) in the Power Mate.
(2) Turn off the power, then turn it on again.
If the PMC contains a sequence program (PMC alarm ER22
PROGRAM NOTHING does not occur), turn on the power while
clearing the sequence program (pressing X and O).
(3) The FANUC standard ladder is loaded.

CAUTION
If the sequence program is not cleared in the PMC, the
FANUC standard ladder is not loaded. The existing
sequence program remains.

1.5 See Part IV, PMCNB6 Manipulation for an explanation of how to


operate the FS15i PMCNB6.
FS15i PMCNB6
OPERATING
PROCEDURE

1.6 See Part V, PMCSA1/SB7 Manipulation for an explanation of how to


operate the FS16i/18i/21iB PMCSA1/SB7.
FS16i/18i/21iB
PMCSA1/SB7
OPERATING
PROCEDURE

413
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

1.7 A password can be specified for a ladder program. Specified passwords


are stored as sequence program data. A ladder program for which the
LADDER PASSWORD password has been specified cannot be displayed or edited.
FUNCTION Symbols, comments and messages, however, can be displayed and edited
whether a password is specified or not.
(1) Applicable model
PMCSA1/SA5/SB5/SB6 for Series 16i/18i/21iA
PMCSA1/SB3/SB4/SC3/SC4 for Series 16/18MODEL B
PMCSB5/SB6 for Series 16/18MODEL C
PMCSA1/SA3 for Series 21/210MODEL B
PMCNB/NB2 for Series 15MODEL B
(The 4047 series is not supported.)
PMCPA3 for Power MateH
(2) Types of passwords
A password consists of up to eight alphanumeric characters. The
following two types of passwords are used.
Display permissible : R password (READ)
Display and editing permissible : RW password (READ+WRITE)

Table 1.7 (a) Screens requiring password release and corresponding


password types
Selected screen (soft key) Password
PMCLAD READ
ONLEDT READ+WRITE
M.SRCH (display) READ
M.SRCH (input) READ+WRITE
LADDER READ+WRITE
CLRLAD READ+WRITE
CLRALL READ+WRITE
DBGLAD READ
ONLEDT READ+WRITE

Table 1.7 (b) Screens requiring password release and corresponding


password types (DPL/MDI)
Selected screen Password
LADDER READ+WRITE

414
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

NOTE
1 See the following items for the selected screens listed in
Table 1.7 (a).
PMCLAD : 5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) in Part II
M.SRCH : 3.5 Display the Contents of Memory
(M.SRCH) in Part II
LADDER : 5.2 Sequence program generation
(LADDER) in Part III
CLRLAD : 5.6.1 Clear the sequence program in Part
III
CLRALL : 5.6.1 Clear the sequence program in Part
III
DBGLAD : 8.4 Ladder Debug Function in Part III
ONLEDT : 5.8 Online Editing in Part II
8.4.2 Soft key menu for ladder debug
function in Part III
2 For an explanation of the selection screen of Table 1.7 (b),
see the following section:
LADDER: III 11.4 Ladder Mnemonic Editing
3 With DPL/MDI of the Power Mate, the use of the following
characters only is supported for clearing passwords:
Alphabetic characters : D, F, G, K, P, T, X, Y
Numeric characters : 0, 1, 2, 3, 4, 5, 6, 7, 8, 9
If a character other than those listed above is used for a
password, the password cannot be cleared using the
DPL/MDI.

(3) Setting a password


Set a password for a ladder program on the editing/password screen
on FANUC LADDER (for personal computers).
(4) Releasing password protection
A ladder program for which the password has been specified cannot
be displayed or edited until the password is input correctly. Once
password protection is released, the protection remains being
released until the power is turned off then on again.
(a) When operation which requires releasing the password
protection is performed, the system displays either of the
following messages to require the protection to be released,
depending on the type of password.
KEY IN PASSWORD(R) READ PASSWORD
KEY IN PASSWORD(R/W) READ+WRITE
PASSWORD
(b) Enter the password and press the [INPUT] key.
*The entered password is not displayed. (Echo back is not
performed.)

415
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

(c) When the password is correctly specified, the protection is


released and the corresponding operation becomes available. See
Table 1.6 (a). If the password is incorrectly specified, the
message FALSE PASSWORD is displayed.

NOTE
The sequence program is cleared by turning on the power
with the X and O keys being held down, whether password
protection is specified or not.

(5) Special password


: Usable
: See Note.
n : Not usable
Power FS20/ FS18A FS16A FS16B FS16C FS21i FS16i FS15B
Mate/ FS21B FS18B FS18C FS18i
FS21A

PA1 RA1 SA1, SA2 SB, SB2, SB3 SB3 SB4 SB5 SB6 SC4 SA1 SB5 SB6 NB NB2
PA3 RA3 SA3 SC, SC3 SC3 SC4 SC3 SA5

n f n f f

NOTE
Usable editions
PMCSB4 : Series 4066 Edition 08 or later
PMCSC4 : Series 4068 Edition 07 or later
Edit card : Series 4073 Edition 06 or later

When a password beginning with the character # is set for RW


password, the subprogram after P1500 can be edited in spite of the
protection by this password.

LADDER <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP


P1500 ( ) USER PROGRAM NO.1

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P1500 V P1501 V]P1502

example 1)
When the cursor is positioned to the subprogram P1500 and [ZOOM]
key is pressed, this subprogram P1500 can be edited in spite of the
protection by the password.
example2)
When the cursor is positioned to the subprogram P1 and [ZOOM] key
is pressed, if the protection by the password is not released, the
message KEY IN PASSWORD(R/W) is displayed and this
subprogram can be edited by inputting a correct password.

416
B61863E/14 PMC OPERATION (CRT/MDI) 1. GENERAL

1.8 Note the following when PMC of loader control function is operated.
PMC OPERATION D Operate PMC after switching to the screen for the loader control. (The
control of the main and the loader changes by pushing the SHIFT key
FOR LOADER and the HELP key at the same time.)
CONTROL FUNCTION D Connector JD5A of main board is used when communicating with
RS232C.
D When ladder data is input and output to the memory card on the PMC
I/O screen or an edit card is used,the edit card or the memory card is
installed at connector CNMC of the loader board.
D Connector JD1A of loader board is used when using I/O Link function.

417
2. PMC MENU SELECTION
PROCEDURE BY SOFTKEY PMC OPERATION (CRT/MDI) B61863E/14

2 PMC MENU SELECTION PROCEDURE BY SOFTKEY

Pressing the function key <SYSTEM> of CRT/MDI and the PMC soft
key changes the screen to the PMC basic screen. The soft keys are
displayed at the bottom of the screen.
1) PMC basic menu
If the control provides a builtin programmer function, a programmer
basic menu is selected by depressing the next key. The PMC basic
menu and programmer basic menu are alternately selected from each
other by depressing the next key.
For programmer basic menus and operation, see Chapter III PMC
PROGRAMMER.

NOTE
1 In the following description, the relation between soft keys and menu is described based on the
9 CRT/MDI panel. The 10, 14 CRT/MDI panel is provided with 10 soft keys which are those
of the 9 CRT/MDI panel, and thus, it displays many menus as compared with the 9 CRT/MDI
panel.
2 The following operations are necessary for using the builtin programmer function:
Model Operation
PMCSA1/SA2/SA3/SB/SB2/SB3 Mount the editing module.
(FS16/18MODEL A),
PMCSA1(FS16MODEL A loader control) (A02B0120CC160)
PMCPA1/PA3 (Power MateD/H), Mount an editing card.
PMCSA1/SB3/SB4 (FS16/18MODEL B),
PMCSB5/SB6 (FS16/18MODEL C),
PMCSA1/SA5/SB5/SB6
(16i/18i/21iMODEL A),
PMCSA1/SA3 (FS20, FS21/210B),
PMCSA1
(FS16MODEL B/C, 16i/18i/21iMODEL A,
FS21B loadercontrol function)
PMCSC/SC3(FS16/18MODELA), The function is already contained.
PMCSC3/SC4(FS16/18MODELB/C),
PMCNB/NB2(FS15B)
Common to all the models listed above Set bit 1 of K17 to 1.

The FS18MODEL A contains the PMCSA1,SA2,or SA3. The series number is 4070.
The FS20 contains the PMCSA1 or SA3. The series number is 4080.
The FS21/210B contains PMCSA1 or SA3. The series number is 4084.
The FS21B(with loader control) contains PMCSA1. The series number is 4086.

418
2. PMC MENU SELECTION
B61863E/14 PMC OPERATION (CRT/MDI) PROCEDURE BY SOFTKEY

2) Keys on CRT/MDI panel


The following keys are related to PMC operation on CRT/MDI panel.
a) <SYSTEM> key
Selects from CNC menu to PMC basic menu.
b) <PAGE> key
Screen page return key.
c) <PAGE> key
Screen page advance key.

PMC DIAGNOSIS FUNCTIONS MONIT RUN

SELECT ONE OF FOLLOWING SOFT KEYS

PMCLAD : DYNAMIC LADDER DISPLAY


PMCDGN : DIAGNOSIS FUNCTION
PMCPRM : PARAMETER(T/C/K/D)
RUN/STOP: RUN/STOP SEQUENCE PROGRAM
EDIT : EDIT SEQUENCE PROGRAM
Builtin programmer func-
tion I/O : I/O SEQUENCE PROGRAM
SYSPRM : SYSTEM PARAMETER
MONIT : PMC MONITOR

[PMCLAD] [PMCDGN] [PMCPRM] [ ] [ ]

Fig. 2 PMC basic menu screen (9CRT)

NOTE
Without builtin programmer function of PMCSA1, SA2,
SA3, SB, SB2, SB3, SB4, SB5, or SB6 there are
only RUN/STOP and I/O functions.

d) <> key
Cursor shift (upward) key.
e) <> key
Cursor shift (downward) key.
f) <> key
Cursor shift (leftward) key. Search function with this key is
provided in PMCLAD EDIT, LADDER (See chapter II.5 and
Chapter III.5.25 for details).
g) <> key
Cursor shift (rightward) key. Search function with this key is
provided in PMCLAD EDIT, LADDER (See chapter II.5 and
Chapter III.5.25 for details).
h) Soft key
These keys show operating functions corresponding to individual
operations when various PMC operations are done. The soft key
functions change (key menus are selected) according to
operations.

419
2. PMC MENU SELECTION
PROCEDURE BY SOFTKEY PMC OPERATION (CRT/MDI) B61863E/14

i) Next key
This key is used for extending menus of soft keys. By pressing
this key, a menu changes, and by pressing it again, the menu is
reset as before.
j) Return key
Various PMC operations are conducted by pressing soft keys
related to menus.
The menus sequentially change when pressing corresponding
soft key. Use this return key to reset a menu to the original one.
3) Status display
The alarm status and the name of the sequence program storage that
is currently effective are displayed on all the PMC menus.
In addition, PMCSC/SC3/SC4/NB display the states while the
debugging function is used.

Data entry >


Status display DBG RAM ALM
Soft key display [ ] [ ] [ ] [ ] [ ]

D ALM : An alarm occurred in the PMC (For details, see


Section 3.3.)
D RAM : The currently effective sequence program storage
is a RAM module.
D ROM : The currently effective sequence program storage
is a ROM module.
D EPROM: Currently effective sequence program storage is
EPROM. (EPROM for PMCSA1, PMCSA2,
PMCSB, and PMCSB2)
D DBG : A break issued by the debugging function of
PMCSC/SC3/SC4/NB in effective.
D BRK : The break issued by the debugging function of
PMCSC/SC3/SC4/NB has terminated.

420
2. PMC MENU SELECTION
B61863E/14 PMC OPERATION (CRT/MDI) PROCEDURE BY SOFTKEY

4) Relation between PMC menus and soft keys


There are 2 types, A and B, in the series of CNC.
ATYPE

RUN or STOP EDIT I/O SYSPRM MONIT

Chapter II.5 Chapter II.3 Chapter II.4 NEXT

PMCLAD PMCDGN PMCPRM

RET RET RET

TOP TITLE TIMER

BOTTOM STATUS COUNTR

SRCH ALARM KEEPRL

W SRCH TRACE DATA

N SRCH

NEXT NEXT

F SRCH M. SRCH*1

ANALYS*2

USRDGN*3

ADRESS
(SYMBOL)

NOTE
The soft keys indicated by *1, *2, *3 are supported only for
certain models. See the conditions in the description of
each relevant function.

421
2. PMC MENU SELECTION
PROCEDURE BY SOFTKEY PMC OPERATION (CRT/MDI) B61863E/14

BTYPE

RUN or STOP EDIT I/O SYSPRM MONIT

Chapter II.5 Chapter II.3 Chapter II.4 NEXT

PMCLAD PMCDGN PMCPRM

RET RET RET

SEARCH TITLE TIMER

ADRESS STATUS COUNTR


(SYMBOL)
TRIGER ALARM KEEPRL

WINDOW TRACE DATA

SETING

NEXT NEXT

DUMP M. SRCH*1

DPARA ANALYS*2

USRDGN*3

ONLEDT

IOCHK*4

NOTE
The soft keys indicated by *1, *2, *3 are supported only for
certain models. See the conditions in the description of
each relevant function.

The softkey s type for the series of CNC.


CNC type Power Mate FS20 FS18 FS16 FS15B
PMC type PA1 PA3 SA1 SA3 SA1 SA2 SA3 SB SB2 SB3 SC SC3 NB NB2
Softkey type A A A A AB A B AB A B AB AB B B

Type A or B is selected depending on the Series of PMC control software.


Series of PMC control software and type of softkey are related as follows.
Type A Type B
FS16A 4061 4063
FS18A 4070 4071

422
2. PMC MENU SELECTION
B61863E/14 PMC OPERATION (CRT/MDI) PROCEDURE BY SOFTKEY

(Reference) Series of PMC control software is displayed on the


[PMCDGN] and [TITLE] screen as shown below.

PMC CONTROL PROGRAM


SERIES : 4063 EDITION : 08

Series of PMC control software

423
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3 PMC I/O SIGNAL DISPLAY AND INTERNAL RELAY


DISPLAY (PMCDGN)

PMC I/O signals, internal relays, and other PMC diagnosis are displayed
on the screen by depressing soft key [PMCDGN].

PMCLAD PMCDGN PMCPRM

RET

TITLE STATUS ALARM TRACE

NEXT

M.SRCH ANALYS USRDGN IOCHK

424
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.1 Title Data refers to the title of the sequence program created by the
machine tool builder.
DISPLAYING TITLE
DATA They consist of the following ten items :
Machine tool builder name (32 characters)
Machine tool name (32 characters)
NC and PMC types (32 characters)
Sequence program number (4 characters)
Version (2 characters)
Sequence program drawing number (32 characters)
Date when the sequence program was created (16 characters)
Sequence program programmer (32 characters)
ROM programmer (32 characters)
Comment (32 characters)
In addition to the title display :
1) Series and version of the PMC control software.
2) Type of the PMC.
3) For Editing module or Editing card, the series and version.
4) Memory areas used for each sequence data, and execution time of
ladder program.
5) Type of PMC control module and PMC sequence program.
6) For the non-dividing system, the present, maximum and minimum
values for the execution time of ladder program.

NOTE
When a C board is installed in the Series 16i/18i, the title
data for C can be displayed. With the arrow keys [] and
[], the user can switch the display between the ladder title
and C title data.

To display the previous or next screen on the 9 CRT/MDI, use the


<PAGE > or <PAGE > key.

PMC TITLE DATA #1 MONIT RUN


PMC PROGRAM NO. : 1234
EDITION NO. : 12
PMC CONTROL PROGRAM
SERIES : 4063 EDITION : 08
(SERIES : 4065 EDITION : 08)
PMC TYPE CONTROL : RB3 PROGRAM : RB3
MEMORY USED : 007.8 KB
LADDER : 007.0 KB
SYMBOL : 000.0 KB
MESSAGE : 000.8 KB
SCAN TIME : 008 MS
SCAN MAX : 016 MS MIN : 008 MS

[TITLE ] [STATUS ] [ALARM ] [TRACE ] [ ]

Fig. 3.1 (a) Title data 1

425
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

PMC TITLE DATA #2 MONIT RUN

MACHINE TOOL BUILDER NAME :


f f

MACHINE TOOL NAME :


f f

CNC & PMC TYPE NAME :


f f

PROGRAM DRAWING NO. :


f f

[TITLE ] [STATUS ] [ALARM ] [TRACE ] [ ]

Fig. 3.1 (b) Title data 2

PMC TITLE DATA #3 MONIT RUN

DATE OF PROGRAMING :
f f

PROGRAM DESIGNED BY :
f f

ROM WRITTEN BY :
f f

REMARKS :
f f

[TITLE ] [STATUS ] [ALARM ] [TRACE ] [ ]

Fig. 3.1 (c) Title data 3

426
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.2 The contents at all addresses (X, Y, F, G, R, A, C, K, D, T, M, N)


disignated in programs can be displayed on the CRT screen. This display
DISPLAY OF SIGNAL is all done by 0 and 1 bit patterns, and symbol data is displayed
STATUS (STATUS) together at address bits where symbol data are difined.

TITLE STATUS ALARM TRACE

RET
SEARCH NEXT

M.SRCH ANALYS USRDGN I/O CHK

1 Depress [STATUS] soft key. The CRT screen changes as shown in


Fig. 3.2, and the soft key menu is changed.
2 Depress [SEARCH] key after keying in an address to be displayed.
3 A continuous 8 byte data is displayed by a bit pattern from the
designated address in the top stage of the CRT screen.
4 Depress [SEARCH] key or page key to display another address.

PMC SIGNAL STATUS MONIT RUN

ADDRESS 7 6 5 4 3 2 1 0
EXDAT1 ED7 ED6 ED5 ED4 ED3 ED2 ED1 ED0
G0000 0 0 0 0 0 0 0 0
EXDAT2 ED15 ED14 ED13 ED12 ED11 ED10 ED9 ED8
G0001 0 0 0 0 0 0 0 0
ESTB EA6 EA5 EA4 EA3 EA2 EA1 EA0
G0002 0 0 0 0 0 0 0 0
ERDRQ EOREND
G0003 0 0 0 0 0 0 0 0
MFIN5 MFIN4 MFIN3 MFIN2 MFIN1
G0004 0 0 0 0 0 0 0 0
BFIN AFL TFIN SFIN EFIND MFIN
G0005 0 0 0 0 0 0 0 0
DLK OVC *ABSM BRN SRN
G0004 0 0 0 0 0 0 0 0
RLSOT EXLM2 *FLWP ST STLK RVS
G0007 0 0 0 0 0 0 0 0

[SEARCH] [ ] [ ] [ ] [ ] [ ]

Fig. 3.2 Status display of PMC I/O signals and internal relays

427
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.3 If an alarm is issued in the PMC, pressing the PMC soft key displays the
alarm message as shown in Fig. 3.3. ALM blinks at the lower right corner
ALARM SCREEN of the screen.
(ALARM) If a fatal error occurs, a sequence program does not start.

PMC ALARM MESSAGE MONIT STOP

ER00 PROGRAM DATA ERROR (ROM)

ALM

[TITLE ] [STATUS] [ALARM ] [TRACE ] [ ]

Fig. 3.3 Alarm screen


For displayed messages, see the appendix, Alarm Message List.

428
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.4 This function checks the signal history which cannot be checked in the
status display. Using one- or two-byte addressing, the function records
TRACE FUNCTION a state when the signal changes. In two-byte addressing, discontinuous
(TRACE) addresses can be set.

3.4.1 Pressing the [TRACE] key on the PMCDGN screen displays the trace
Operation screen when signals are being read. When signals are not being read, the
parameter setting screen for reading signals is displayed. After displaying
either screen, pressing the [TRCPRM] key on the trace screen displays the
parameter setting screen and pressing the [T.DISP] key on the parameter
setting screen displays the trace screen.

TITLE STATUS ALARM TRACE

RET
T.DISP EXEC NEXT

or or
TRCPRM STOP

M.SRCH ANALYS USRDGN

3.4.2 Data to be used for reading signals needs to be specified to check the
Parameter Setting signal history.
Screen 1) Parameters
TRACE MODE : Sets a mode used for reading signals
0 : 1-byte data
1 : 2-byte data (discontinuous addresses can be
specified)
2 : Word data (with continuous addresses)
ADDRESS TYPE : Sets addresses used
0 : PMC address
1 : Physical address
ADDRESS : Sets addresses at which a signal is traced
MASK DATA : Sets a masked bit or bits (signals can be read with
unnecessary bits masked)
Range : 00 to FF
The above trace parameters are retained if the power is turned off.

429
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.4.3 EXEC : Starts reading signals


Starting or Stopping
the Trace Function NOTE
1 Pressing the [EXEC] key again clears the results of the
previous trace.
If the trace parameters are not set correctly, the trace is not
performed.
When signals are being sampled using the function for
displaying signal waveforms, the trace is not performed.
2 The result data of the trace is stored latest 256-byte. If the
power is turned off, the results of the trace are cleared.
3 Signals R9000 to R9007 cannot be traced.
4 A signal is traced at intervals of 8 ms. If the signal changes
within 8 ms, the changed signal state cannot be traced.
5 When the trace address type is specified as a physical
address, specify an effective memory address. If an
ineffective address is specified to execute the trace, a
system error may occur.

STOP : Stops reading signals.

PMC SIGNAL TRACE MONIT RUN

TRACE MODE : 1
(0:1BYTE/1:2BYTE/2:WORD)
1ST TRACE ADDRESS CONDITION
ADDRESS TYPE : 1 (0:PMC /1:PHY)
ADDRESS : FFE480
MASK DATA : 11
2ND TRACE ADDRESS CONDITION
ADDRESS TYPE : 0 (0:PMC /1:PHY)
ADDRESS : Y0
MASK DATA : FF

[T.DISP] [ EXEC ] [ ] [ ] [ ]

Fig. 3.4.3 Trace parameter setting screen

430
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.4.4 Signal history can be checked using data specified on the parameter
Trace Screen setting screen. The result of the latest trace is displayed at the cursor
position. The cursor moves on the screen as the results of the trace are
obtained. If the cursor moves off the screen, the results of the trace can
be followed by pressing the page key to display the subsequent screen.

PMC SIGNAL TRACE MONIT RUN

1ST ADDRESS = X0000 (FF) 2ND ADDRESS = Y0000 (FF)


NO. 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
0000 . . . . . . . . . . . . . . . .
0001 . . . . . . . . . . . . . . . .
0002 . . . . . . . . . . . . . . . .
0003 . . . . . . . . . . . . . . . .
0004 . . . . . . . . . . . . . . . .
0005 . . . . . . . . . . . . . . . .
0006 . . . . . . . . . . . . . . . .
0007 . . . . . . . . . . . . . . . .
0008 . . . . . . . . . . . . . . . .
0009 . . . . . . . . . . . . . . . .
0010 . . . . . . . . . . . . . . . .
0011 . . . . . . . . . . . . . . . .
0012 . . . . . . . . . . . . . . . .
0013 . . . . . . . . . . . . . . . .
0014 . . . . . . . . . . . . . . . .
0015 . . . . . . . . . . . . . . . .

[TRCPRM ] [ STOP ] [ ] [ ] [ ]

EXEC

Fig. 3.4.4 Trace screen

3.4.5 Trace operation can be started automatically, immediately after


poweron, by setting trace parameters beforehand and by setting the keep
Automatic Tracing
relay to start the trace function automatically upon poweron. The keep
Function at Power on relay setting method depends on the PMC model. See Section 4.3.3.

431
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.5
DISPLAYING THE : Standard
: optional
CONTENTS OF : cannot be used
MEMORY n : Can be used for the 4084 series.
Power FS21i FS16A
Power FS20/ FS16A/B FS16C FS16B/C
Mate- FS21B FS18A FS18B FS16A FS16i FS16A /B/C FS15B
Mate-H FS21A FS18B FS18C FS18B/C
D/F FS18i FS18B/C

PA1 PA3 PA3 SA1 SA3 SA1 SA3 SA1 SA2 SA3 SA1 SB SB2 SB3 SB4 SB5 SB6 SA1 SA5 SB5 SB6 SC SC3 SC4 NB NB2

n n

D The ladder editing module is required for the PMCSB/SB2/SB3 of the


Series 16 MODEL A and for the PMCSA1/SA2/SA3 of the Series
18MODEL A.
D This function is provided as a standard function with
PMCSA1/SB3/SB4/SB5/SB6/SC3/SC4 of the Series
16/18MODEL B/C, and PMCSA1/SA3 of the Series 21/210MB.

3.5.1 1) Pressing the [M.SRCH] soft key changes the screen to that shown in
Fig. 3.5.2. The displayed soft keys also change.
Operation
2) Enter a physical address in hexadecimal from which the contents of
the memory are to be displayed. Then pressing the [SEARCH] key
displays 256 bytes of stored data starting from the specified address.
Example) Entering 100000, then pressing the [SEARCH] key
displays the contents of the memory starting from
100000H.
3) An address can be changed using the <PAGE > or <PAGE > key.
4) Pressing either the [BYTE], [WORD], or [D.WORD] soft key
displays data of the corresponding type.

CAUTION
If an address at which the memory is not used is specified,
a system error occurs. Be sure to specify the correct
address.

432
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.5.2 To store data in memory, set bit 4 of keep relay K17 to 1, move the cursor
Function for Storing to a position at which the address of the data to be changed in RAM is
displayed, and enter data in units of data type in hexadecimal.
Data in Memory
Example) Entering 0F41, then pressing the [INPUT] key stores 0F41
at the address specified by the cursor.

WARNING
Some values cause a system error.

PMC CONTENTS OF MEMORY MONIT RUN

100000 0000 0000 0000 0000 0000 0000 0000 0000 ................
100010 4142 4344 4546 4748 494A 4B4C 4D4E 4F50 ABCDEFGHIJKLMNOP
100020 2020 2020 2020 2020 2020 2020 2020 2020
100030 5152 5354 5556 5758 595A 2020 2020 2020 QRSTUVWXYZ

100040 0000 0000 0000 0000 0000 0000 0000 0000 ................
100050 0000 0000 0000 0000 0000 0000 0000 0000 ................
100060 0000 0000 0000 0000 0000 0000 0000 0000 ................
100070 0000 0000 0000 0000 0000 0000 0000 0000 ................
100080 4641 4E55 4320 434F 2E2C 5444 0000 0000 FANUC CO.LTD....
100090 0000 0000 0000 0000 0000 0000 0000 0000 ................
1000A0 0000 0000 0000 0000 0000 0000 0000 0000 ................
1000B0 0000 0000 0000 0000 0000 0000 0000 0000 ................

1000C0 0000 0000 0000 0000 0000 0000 0000 0000 ................
1000D0 0000 0000 0000 0000 0000 0000 0000 0000 ................
1000E0 0000 0000 0000 0000 0000 0000 0000 0000 ................
1000F0 0000 0000 0000 0000 0000 0000 0000 0000

>

[ SEARCH ] [ INPUT ] [ ] [ ] [ ]

Fig. 3.5.2 Memory display

433
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.6
FUNCTION FOR
DISPLAYING SIGNAL : Standard
: optional
WAVEFORMS : cannot be used
(ANALYS) n : Can be used for the 4084 series.
Power Power FS20/ FS21B FS18A FS18B FS16A FS16A/B FS16C FS21i FS16A FS16A FS16B/C FS15B
MateD/F MateH FS21A FS18B FS18C FS16i /B/C FS18B/C
FS18B/C
FS18i
PA1 PA3 PA3 SA1 SA3 SA1 SA3 SA1 SA2 SA3 SA1 SB SB2 SB3 SB4 SB5 SB6 SA1 SA5 SB5 SB6 SC SC3 SC4 NB NB2

n n

D The ladder edit module is required with PMCSB/SB2/SB3 of the


Series 16MODEL A, and PMCSA2/SA3 of the Series 18MODEL
A.
D The ladder edit card is required with PMCRA1/RB3/RB4 of the Series
16/18MODEL B, PMCSA1/SB5/SB6 of the Series 16/18MODEL
C, PMCSA1/SA3 of the Series 21/210MODEL B, and PMCPA3 of
the Power MateMODELH.
D Work RAM is required with PMCSC/SC3 of the Series 16MODEL
A.
D This function is provided as a standard function with PMCSC3/SC4
of the Series 16/18MODEL B/C.
D The ladder edit card is required with PMCSA5/SB5/SB6 of the Series
16i/18i/21iMODEL A.

3.6.1 1) Maximum number of signals traced at the same time: 16


Specifications 2) Maximum sampling period: 10 s
3) Sampling interval: 8 ms

3.6.2 Pressing the [ANALYS] key on the PMCDGN screen displays the
Operation parameter screen for diagnosing signals. Pressing the [SCOPE] soft key
on the parameter screen displays the screen showing signal diagnosis. To
return to the parameter screen, press the [SGNPRM] soft key.

434
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

TITLE STATUS ALARM TRACE


NEXT

M.SRCH ANALYS USRDGN

RET SCOPE DELETE INIT ADRESS


or
SYMBOL

SGNPRM START T.SRCH ADRESS


or
SYMBOL NEXT

EXCHG SCALE

SELECT CANCEL

RET

TO CANCEL

EXEC CANCEL

3.6.3 To trace the state of a signal, the trace conditions need to be specified on
Parameter Screen the parameter screen. In a 9 screen, a trace address can be specified by
pressing the <PAGE > key. (See Fig. 3.4.4.)
1) Setting parameters
Move the cursor to a parameter to be specified. Enter a value and
press the [INPUT] key. To delete the value of the parameter, move
the cursor to the parameter, then press the [DELETE] soft key.
a) SAMPLING TIME
Specify the maximum trace time in the range of 1 to 10 s.
b) TRIGGER ADDRESS
Specify a trigger address from which the tracing starts on the
PMC address. A symbol name can be used.
c) CONDITION
Specify the conditions at which the tracing starts.
0 : When the [START] key is pressed
1 : When the [START] key is pressed and the trigger address
signal rises
2 : When the [START] key is pressed and the trigger address
signal falls

NOTE
Conditions 1 and 2 are effective when a trigger address is
specified.

435
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

d) TRIGGER MODE
Sampled data for up to 10 seconds is stored in the trace buffer.
A signal is stored in the buffer within 8 ms.
This parameter specifies the starting and end points for obtaining
data.
0 : AFTER
In this mode, signal states are obtained in the period specified
in parameter SAMPLING TIME from the time when the
trigger conditions are satisfied.
1 : ABOUT
In this mode, signal states are obtained in the period specified
in the parameter SAMPLING TIME with the time at the
middle when the trigger conditions are satisfied.
2 : BEFORE
In this mode, signal states are obtained in the period specified
in parameter SAMPLING TIME before the trigger
conditions are satisfied.
3 : ONLY
In this mode, the signal states are obtained only when the
trigger conditions are satisfied.

NOTE
Trigger mode 1 and 2 are effective when condition 1 or 2 is
set.

e) SIGNAL ADDRESS
Specify up to 16 addresses at which the tracing is performed with
PMC addresses or symbol names.
2) Initializing signal diagnosis data
Pressing the [INIT] soft key on the parameter screen initializes
parameter data and trace data.
3) Displaying symbols for trigger addresses and trace addresses
Pressing the [ADRESS] soft key displays trigger and trace addresses
for which symbols are defined and the key changes to the [SYMBOL]
key. Pressing the [SYMBOL] key displays the symbols for trigger
and trace addresses and the key changes to the [ADRESS] key.

436
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

PMC SIGNAL PARAMETER MONIT RUN

SAMPLING TIME : 10(1-10SEC)

TRIGGER ADDRESS : *ESP

CONDITION : 1
(0:START 1:TRIGGER-ON 2:TRIGGER-OFF)

TRIGGER MODE : 1
(0:AFTER 1:ABOUT 2:BEFORE 3:ONLY)

>

[SCOPE ] [DELETE] [INIT ] [ADRESS] [ ]

ADRESS/SYMBOL

Fig. 3.6.3 (a) Parameter setting screen 1

PMC SIGNAL PARAMETER MONIT RUN

SIGNAL ADDRESS

1 : ED0 9 : X0000.0
2 : ED1 10 : X0000.1
3 : ED2 11 : X0000.2
4 : ED3 12 : X0000.3
5 : ED4 13 : X0000.4
6 : ED5 14 : X0000.5
7 : ED6 15 : X0000.6
8 : ED7 16 : X0000.7

>

[SCOPE ] [DELETE] [INIT ] [ADRESS] [ ]

ADRESS/SYMBOL

Fig. 3.6.3 (b) Parameter setting screen 2

437
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.6.4 After parameters are specified on the parameter screen, select the signal
Signal Diagnosis diagnosis screen.
Screen Pressing the [START] soft key starts to trace the specified signal.
While the signals are traced, EXECUTING is displayed. When the
tracing is finished, the period in which the specified signal was traced is
displayed on the screen.
When the optional graphic function is provided, the waveform is
displayed by using the graphic function.
When the function is not provided, waveform is displayed with J
indicating the signal is on and _ indicating the signal off.
In the ONLY mode, even when the optional graphic function is
provided,J and _ is used to display the waveform as shown in Fig.
3.6.4.
1) Starting or stopping the data sampling
Pressing the [START] key starts sampling. Pressing the [STOP] key
stops sampling and the sampled data is displayed.
2) Displaying traced data by specifying a period
Enter a period in ms in which traced data is to be displayed. Pressing
the [T.SRCH] key displays the traced data.
Example) Entering 800, then pressing the [T.SRCH] key displays the
waveform from 512 ms to 1024 ms.
3) Displaying symbols for trigger and trace addresses
When symbols are defined for trigger and trace addresses, the
symbols and addresses are displayed
4) Exchanging positions at which traced data is displayed
Pressing the [EXCHG] key moves the cursor to the first traced
address. Position the cursor to the trace address to be exchanged,
using the <> or <> key, then press the [SELECT] key. Next,
position the cursor to the trace address with which the selected trace
address is to be exchanged, then press the [TO] key. Finally, press the
[EXEC] key. The trace data is exchanged.
During the above operation, all other soft keys are disabled until the
[EXEC] key has been pressed. To cancel the exchange, press the
[CANCEL] key.
5) Changing the time division (This function is available when the
graphic function is used.)
When displaying the signal waveform, the time division can be
changed.
Setting 8 . . . . . . 8 ms/divisions
16 . . . . . 16 ms/divisions
32 . . . . . 32 ms/divisions
Pressing only the [SCALE] key increments the minimum scale from
8 to 32 ms, as follows:
6) Shifting traced data upward or downward
Pressing the <PAGE > key shifts traced data upward. Pressing the
<PAGE > key shifts traced data downward.
7) Shifting traced data left or right

438
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

Pressing the key shifts traced data to the left. Pressing the
key shifts traced data to the right.

PMC SIGNAL ANALYSIS(SCOPE) MONIT RUN


SAMPLING TIME : 10 CONDITION : 1
TRIGGER ADDRESS:*ESP TRIGGER MODE: 1

ED0
ED1
ED2
ED3
ED4
ED3

-256 0(MSEC)

[SGNPRM] [START ] [T.SRCH ] [ADRESS ] [ ]


START/STOP ADRESS/SYMBOL

Fig. 3.6.4 Screen displaying signal diagnosis

3.6.5 Since parameter and sampling data is stored in nonvolatile memory, data
Reading Signals is retained when the power is turned off.
Data sampling can be started automatically, immediately after poweron,
Automatically at Power by setting sampling parameters and setting the keep relay beforehand.
on The keep relay setting method depends on the PMC model. See Section
4.3.3.

439
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.7 Pressing the [USRDGN] key dynamically displays the running states of
user tasks (including the third level of a ladder program) in the PMC (Fig.
DISPLAYING THE 3.7).
RUNNING STATE OF
: Can be used
A USER TASK : Cannot be used
(USRDGN) PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SC SC3 SC4 NB NB2


(Note)

Work RAM is necessary (A02B-0120-H987 for the PMC-SC and


PMC-SC3 and A02B-0162-J151 or A02B-0162-J152 for the PMC-NB).
For details, refer to the PMC-SC/SC3/SC4/NB Programming Manual
(C language) (B-61863E-1).

NOTE
C language board is required.

PMC MONIT USER TASK #1 MONIT RUN

ID NAME LV STATUS WAIT-INF WAIT-ID


LAD3 10 READY
10 TASK_O1 @ 10 ACTIVE
11 TASK_O2 # 11 READY
12 TASK_O3 12 WAIT TIM
13 TASK_O4 13 WAIT EVT.O 1
14 TASK_O5 14 WAIT EVT.A 3
15 TASK_O6 15 WAIT PKT 2340
16 TASK_O7 STOP
17 TASK8 17 READY

>

[ ][ ][ ][ ][ ]

Fig. 3.7 Screen displaying the running states of user tasks

[Displayed items]

ID NAME LV STATUS WAIT-INF WAIT-ID


11 TASK1 # 13 WAIT EVT.O 10

ID for wait information


Wait information
Running state
Task level
Operation
Task name
Task ID

440
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

1) Operation
Code Description
# RS-232C being used
@ NC command edit being used

2) Running state
Code Description
ACTIVE Running
READY Ready
WAIT Waiting
STOP Task stopped
ERROR The system deleted the task because the task had called library that
is not supported.

3) Wait information
Code Description
TIM Waiting for time-out
EVT.A Waiting for AND condition of event flags
EVT.O Waiting for OR condition of event flags
SEM Waiting for semaphore
MBX.R Waiting for READ of the mail box
MBX.W Waiting for WRITE of the mail box
PKT Waiting for a packet to be received
PCMDI Waiting for the PCMDI command to be issued

441
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.8 Check kind of I/O modules connected to I/O Link.


Set communication parameters of I/O LinkII, PROFIBUSDP,
DISPLAYING AND DeviceNet, FLnet.
SETTING THE : Supprted
CONFIGURATION : Not supported

STATUS OF I/O Power


Mate
Power
MateH
Power
Matei
FS21
TA/TB
FS20 FS16/
18A
FS16/
18B
FS16/
18C
FS21B FS16i/
18i/21i
FS15B

D/F/G
DEVICES (IOCHK)

In case of FS16 / 18B / FS21B / Power MateH:

TITLE STATUS ALARM TRACE

NEXT

M.SRCH ANALYS (USRDGN) IOCHK

RET

IOLNK IOLNK2

In case of FS16C / 18C:

TITLE STATUS ALARM TRACE

NEXT

M.SRCH ANALYS (USRDGN) IOCHK

RET

IOLNK IOLNK2 PROFI

In case of FS16i / 18i / 21i/ Power Mate i:

TITLE STATUS ALARM TRACE

NEXT

M.SRCH ANALYS (USRDGN) IOCHK

RET

IOLNK IOLNK2 PROFI FLNET


or
D=NET

442
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

PMC I/O CHECK

SELECT ONE OF FOLLOWING SOFT KEYS

IOLNK : I/O LINK CHECK


IOLNK2 : I/O LINKII SETTING
PROFI : PROFIBUS PARAMETER
D_NET : DEVICENET PARAMETER
FLNET : FLNET SETTING

Fig. 3.8 Menu of I/O check screen


There are following sub screens under the I/O Check screen.
Softkeys are displayed when each function can be used.
Please refer to the manual about requirement of the functions and detail
of the sub screens.
Softkey : Name of sub screen
[IOLNK ] : I/O Link Connecting Check screen
[IOLNK2] : I/O LinkII Parameter Setting screen
.....FANUC I/O LinkII CONNECTING MANUAL
.....(B62714EN)
[PROFI] : PROFIBUSDP Parameter Setting screen
.....FANUC PROFIBUSDP Board OPERATORS
.....MANUAL (B62924EN)
[D_NET] : DeviceNet Parameter Setting screen
.....FANUC DeviceNet Board OPERATORS MANUAL
.....(B63404EN)
[FLNET] : FLnet Parameter Setting screen
.....FANUC FLnet Board OPERATORS MANUAL
.....(B63434EN)
In case of FS15B:

TITLE STATUS ALARM TRACE

NEXT

M.SRCH ANALYS USRDGN IOCHK

Only I/O Link Connecting Check screen is supported.


When [IOCHK]key is pressed, I/O Link Connecting Check screen
isdisplayed directly.

443
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.8.1 The I/O Link connecting check screen displays the types and ID codes of
I/O Link Connecting the connected I/O devices for each group. When I/O device is not
connected, NO I/O DEVICE is displayed.
Check Screen If there is a problem of input or output signals for I/O devices, check
connection of I/O Link by referring to this screen.
(1) When CNC hardware dose not support the I/O Link expansion
function.

PMC I/O LINK(1/1)


CHANNEL 1
GROUP ID KIND OF UNIT

00 80 CONNECTION UNIT
01 82 OPERATOR PANEL
02 84 I/O UNIT MODEL A
03 96 CONNECTION UNIT
04 4A POWER MATE

Fig. 3.8.1 (a) Example of the I/O Link screen

Table 3.8.1 I/O devices and ID codes

Displayed I/O device name ID Actual I/O device


CONNECTION UNIT 80 Connection unit
OPERATOR PANEL 82 Operators panel connection unit
I/O-B3 83 Expanded I/O B3
I/O UNIT MODEL A 84 to 87 I/O Unit MODEL A
I/O UNIT MODEL B 9D to 9E I/O Unit MODEL B
POWER MATE 4A Power Mate
FANUC SERVO AMPLIFIER UNIT
series (I/O Link OPTION)
CONNECTION UNIT 96 I/O Link connection unit
I/O MODULE A9 to AA Distributed I/O
OTHER UNIT Other than above

The screen displayed like fig.3.8.1 (a) means that the I/O devices are
composed like following fig.3.8.1 (b).

444
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

CNC Connection Group 0


Unit

Operators
Panel Connec- Group 1
tion Unit

I/O
Group 2
Unit MODEL A

I/O Link
Connection Group 3
Unit

Power Mate
Group 4

Fig. 3.8.1 (b) I/O Link configuration


(2) When CNC hardware supports the I/O Link expansion function.

PMC I/O LINK(1/1)


CHANNEL 1 CHANNEL 2
GROUP ID KIND OF UNIT GROUP ID KIND OF UNIT

00 80 CONNECTION UNIT 00 80 I/O UNIT


MODEL A
01 82 OPERATOR PANEL 01 82 POWER MATE
02 84 I/O UNIT MODEL A 02 84 POWER MATE
03 96 CONNECTION UNIT
04 4A POWER MATE

Fig. 3.8.1 (c) Example of the I/O Link connecting check screen
When the screen is displayed like fig.3.8.1(c), the I/O devices are
composed like following fig.3.8.1 (d)

445
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

Channel 2
CNC
Connection Group 0 I/O
Channel 1 Unit Unit MODEL A

Operators Power Mate


Panel Connec- Group 1
tion Unit

I/O Power Mate


Group 2
Unit MODEL A

I/O Link
Connection Group 3
Unit

Power Mate
Group 4

Fig. 3.8.1 (d) I/O Link configuration

When PMC model is not PMCSB6 for Series 16i /160i /18i /180i /21i /
210i or optional I/O Link expansion is not provided with CNC, NOT
SUPPORTED is displayed on CHANNEL 2.

3.8.2 In case of using the I/O LinkII function, set the following I/O LinkII
I/O LinkII Parameter parameter on this screen. Depending on the kind of I/O LinkII interface
board, master/slave screen is displayed automatically.
Setting Screen Please refer to
FANUC I/O LinkII Operators Manual (B62714EN)
about details of I/O LinkII and each parameter.
(1) Set parameters.
Move the cursor to the parameter by using the cursor key.
Type the data and press the soft key[INPUT] or MDI key<INPUT>.
The set parameter is saved to the I/O LinkII board when the data is
input.
(2) Change channel.
Change the channel by the soft key [PRV.CH],[NXT.CH]. These keys
are not displayed when the single channel is used.
(3) Delete parameter.
Move the cursor to the parameter by using the cursor key.
Press the soft key[DELETE].
(4) Delete all parameters.
Press the soft key[DELALL].
Press the soft key[EXEC] to delete all parameters.
Press the soft key[CANCEL] to cancel the deletion.
(5) Change page.
This screen is composed of two pages when the 9 inch CRT is used.
Change the page by using (PAGE) key of MDI.

446
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

(6) Restart I/O LinkII


Press the soft key [START] to restart I/O LinkII after editing the
parameter.
When the restart is completed normally, LINK STARTED is
displayed.
If the restart fails, START ERROR is displayed. In this case, check
the parameter that is set.
Example of parameter setting of master.

PMC I/O LINKII CH 1 (1/2)

GENERAL:
MAX SLAVE NO. = 03 (131)
SCAN TIME = 0100 (19999)*2MSEC
STATUS ADDRESS = R0500
DI/DO SETTING:
DI/DO MAP MODE = 1 (1,2)
DI/DO DATA SIZE = 16 (064)
DO ADDRESS = R0100
DI ADDRESS = R0150

[INPUT ] [DELETE ] [DELALL] [PRV.CH] [NXT.CH]

PMC I/O LINKII CH 1 (2/2)

MESSAGE I/O SETTING:


MESSAGE SIZE = 032 (0128)
OUTPUT ADDRESS = R0200
INPUT ADDRESS = R0250
STATUS:
REFRESH TIME = 40 MSEC
I/O LINKII = 6546/01 (MASTER)

[INPUT ] [DELETE ] [DELALL] [PRV.CH] [NXT.CH]

Fig. 3.8.2 (a) Example of the I/O LinkII screen.(master)

447
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

Example of parameter setting of slave.

PMC I/O LINKII CH 1 (1/2)

GENERAL:
MAX SLAVE NO. = 03 (131)
STATION NO. = 02 (131)
STATUS ADDRESS = R0900
DI/DO SETTING:
DI/DO MAP MODE = 0 (0,2)
DI/DO DATA SIZE = 16 (064)
DO ADDRESS = R0000
DI ADDRESS = R0032

[INPUT ] [DELETE ] [DELALL] [PRV.CH] [NXT.CH]

PMC I/O LINKII CH 1 (2/2)

MESSAGE I/O SETTING:


MESSAGE SIZE = 032 (0128)
OUTPUT ADDRESS = R0256
INPUT ADDRESS = R0296
STATUS:
I/O LINKII = 6545/01 (SLAVE )

[INPUT ] [DELETE ] [DELALL] [PRV.CH] [NXT.CH]

Fig. 3.8.2 (b) Example of the I/O LinkII screen.(slave)

448
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.9
FORCED
INPUT/OUTPUT
: Usable
FUNCTION
n: See Note.
: Not usable

Power Power FS20/ FS18A FS16A FS16B FS16C FS21i FS16i FS15B
Mate Mate iD/H FS21A FS18B FS18C FS18i

PA1 SB5 SA1 SA1, SA2 SB, SB2, SB3 SB3 SB4 SB5 SB6 SA5 SB5 SB6 NB
PA3 SB6 SA3 SA3 SC, SC3 SC3 SC4 SC3 SC4 NB2

n n n n

NOTE
With the FS16i/18i/21i, the edit card or C board are
required.
With the Power Mate iD/H, the edit card is required.
With SA1 of the FS16i/18i/21i, only FORCING mode is
valid.

3.9.1 This function can forcibly enter a value for the signal of an arbitrary PMC
Overview address. With this function, for example, an X value can be forcibly
entered to enable sequence program debugging without using a machine,
and a Y value can be forcibly entered to enable the signal wiring on the
machine to be checked efficiently without using a sequence program.
This function is added to the status display function.

(1) Input mode


Two input modes are available. The user can choose between the two
modes, depending on the application.
(a) FORCING mode
This mode is applicable to all addresses. When input/output scan
is performed by a sequence program, however, a signal modified
by the forced input/output function is overwritten, and the result
of modification made by the forced input/output function is lost.

Machine I/O address


Overwrite X, Y

Overwrite

Overwrite G, F, R, T, K, C, D. .
Ladder

449
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

Example 1:
In this example, the forced input/output function is applied to R0
in the ladder program below.

X0.0
MOVE 1111
1111
K0
R0

a. The initial signal states are as follows:


X0.0 = off, K0 = 55H, R0 = 00H
b. FFH is forcibly entered to R0.
X0.0 = off, K0 = 55H, R0 = FFH
c. When X0.0 is turned on, R0 assumes the result of output by
the sequence program as follows:
X0.0 = on, K0 = 55H, R0 = 55H
Example 2:
In this example, the forced input/output function is applied to X0
in a configuration where the I/O UNITMODEL A is connected
to X0 over an I/O link.
The input value from the I/O UNITMODEL A is transferred to
X0 at certain intervals. So, even if the value of X0 is forcibly
modified, X0 is overwritten in the next cycle. Thus, the value of
X0 is restored to the value input from the I/O UNITMODEL A.

I/O UNITMODEL A NC

X0 = FFH X0 = FFH

The value of X0 is forcibly X0 = 00H


modified to 00H.

In the next cycle, the value of X0 is restored to that


entered from the I/O UNITMODEL A.

I/O UNITMODEL A NC

X0 = FFH X0 = FFH

Cyclical transfer may also be performed for addresses that are not
assigned. So, use the forced input/output function for X in
FORCING mode to debug a sequence program when no machine
is connected or assigned. Use the OVERRIDE mode to debug a
sequence program in the case of I/O connection.

450
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

(b) OVERRIDE mode


That state in which values modified by the forced input/output
function cannot be overwritten by a sequence program or
machine signal is referred to as OVERRIDE mode. In
OVERRIDE mode, OVERRIDE can be set for arbitrary X and Y
signals.
FORCING is applied to those X and Y addresses where
OVERRIDE is not set, and also to addresses other than the X and
Y addresses.

Machine I/O address


Overwrite disabled X, Y
(OVERRIDE)
Overwrite disabled

Overwrite
X, Y
Ladder (NOT OVERRIDE)
G, F, R, T, K, C, D. .

Example:
In this example, the forced input/output function is applied to X0
in a configuration where the I/O UNITMODEL A is connected
to X0 with an I/O link.

I/O UNITMODEL A NC

X0 = FFH X0 = FFH

OVERRIDE is set for X0.

A value transferred from the I/O


UNITMODEL A is invalidated.

I/O UNITMODEL A X NC

X0 = FFH X0 = FFH

Value 00H is forcibly entered to X0.

I/O UNITMODEL A X NC

X0 = FFH X0 = 00H

Thus, the forced input/output function for X addresses in


OVERRIDE mode can be used to debug a sequence program
while a machine is connected.
When a Y address is placed in the OVERRIDE state, a value that
has been forcibly modified by the forced input/output function is
output to the machine.

451
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

CAUTION
1 In OVERRIDE mode, input/output signals are updated at
8ms intervals in sync with the first ladder level. When an
I/O link is used which is usually updated at 2ms intervals,
an input/output signal timing delay occurs. For this reason,
note that a sequence that depends on input/output signal
timing may perform an unpredictable operation.
2 Note that, when OVERRIDE mode is set, the interval of the
second level may be extended slightly.
3 Even if OVERRIDE is set for a Y address, the resultant value
of a ladder operation before being modified by the forced
input/output function is displayed as the coil on/off value in
ladder dynamic display.
A value, after being modified by the forced input/output
function, is output to the machine. So, note that the on/off
indication in ladder dynamic display does not match a value
output to the machine.
Example:
In this example, the forced input/output function is used
for Y0.0 in the ladder below in a configuration where the
I/O UNITMODEL A is connected to Y0 with an I/O link.
Before OVERRIDE setting, the on/off indication in
dynamic display matches a value output to the I/O
UNITMODEL A as shown below.

X0.0 Y0.0
I/O UNITMODEL A NC

Y0.0 = off (Off) (Off)


(Dynamic display)

If 1 is entered forcibly after setting OVERRIDE for Y0.0,


the value modified by the forced input/output function is
output to the I/O UNITMODEL A as shown below.
X0.0 Y0.0
I/O UNITMODEL A NC

Y0.0 = on (Off) (Off)


(Dynamic display)

452
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.9.2 Use the procedures below to set the input/output modes.


Setting/Operation for (1) Operation for enabling FORCING mode
Enabling Forced Use the procedure below.
Input/Output (a) Mount an edit card or C board.
(b) Turn on the power.
(c) Set the PROGRAM ENABLE (bit 1 of K17 or bit 1 of K900)
setting parameter to YES.
(2) Operation for enabling OVERRIDE mode
Use the procedure below.
(a) Mount an edit card or C board.
(b) Turn on the power.
(c) Set the PROGRAM ENABLE (bit 1 of K17 or bit 1 of K900)
setting parameter to YES.
(d) Set the OVERRIDE ENABLE setting parameter (OVERRIDE)
to YES.
(e) Turn the power off, then back on.

WARNING
Special care must be exercised when modifying a signal
with the forced input/output function. If the forced
input/output function is used incorrectly, the operation of the
machine may be unpredictable. Never use this function
when persons are near the machine.

CAUTION
1 When shipping a machine, disable this function.
2 This function is disabled by extracting the edit card or setting
the PROGRAM ENABLE setting parameter to NO.
3 The setting of OVERRIDE is not maintained when the
power is turned off. When the power is turned on again, the
setting of OVERRIDE is cleared for all X and Y addresses.

453
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.9.3 (1) Soft keys


Screen Display
TITLE STATUS ALARM TRACE

SEARCH FORCE

SEARCH ON OFF STATUS

OVRSET OVRRST INIT

EXEC CANCEL

(2) Details of the soft keys


(a) [SEARCH]
Searches for an address to be displayed.
(b) [ON] (Note 1)
Forcibly changes the value of a signal to 1.
(c) [OFF] (Note 1)
Forcibly changes the value of a signal to 0.
(d) [FORCE]/[STATUS] (Note 1)
Switches between the status display screen and forced
input/output screen.
(e) [OVRSET] (Note 2)
Sets OVERRIDE for a signal.
(f) [OVRRST] (Note 2)
Clears an OVERRIDE setting for a signal.
(g) [INIT] (Note 2)
Clears OVERRIDE for all the X and Y areas.

NOTE
1 The soft key is enabled in FORCING mode.
2 The soft key is enabled in OVERRIDE mode.

454
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

(3) Forced input/output screens


FORCING Mode Status Screen

PMC SIGNAL STATUS MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0
X0001 0 0 0 0 0 0 0 1
X0002 0 0 0 0 0 0 1 0
X0003 0 0 0 0 0 1 0 0
X0004 0 0 0 0 1 0 0 0
X0005 0 0 0 1 0 0 0 0
X0006 0 0 1 0 0 0 0 0
X0007 0 1 0 0 0 0 0 0

[SEARCH] [ ] [ ] [ ] [ FORCE ]

FORCING Mode Setting Screen

PMC SIGNAL FORCING MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0
X0001 0 0 0 0 0 0 0 1
X0002 0 0 0 0 0 0 1 0
X0003 0 0 0 0 0 1 0 0
X0004 0 0 0 0 1 0 0 0
X0005 0 0 0 1 0 0 0 0
X0006 0 0 1 0 0 0 0 0
X0007 0 1 0 0 0 0 0 0

[SEARCH] [ ON ] [ OFF ] [ ] [STATUS]

455
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

OVERRIDE Mode Status Screen

PMC SIGNAL STATUS OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0
X0001 0 0 0 0 0 0 0 >1
X0002 0 0 0 0 0 0 >1 0
X0003 0 0 0 0 0 >1 0 0
X0004 0 0 0 0 >1 0 0 0
X0005 0 0 0 >1 0 0 0 0
X0006 0 0 >1 0 0 0 0 0
X0007 0 >1 0 0 0 0 0 0

[SEARCH] [ ] [ ] [ ] [ FORCE ]

OVERRIDE Mode Setting Screen

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0
X0001 0 0 0 0 0 0 0 0>1
X0002 0 0 0 0 0 0 1>1 0
X0003 0 0 0 0 0 1>1 0 0
X0004 0 0 0 0 0>1 0 0 0
X0005 0 0 0 0>1 0 0 0 0
X0006 0 0 0>1 0 0 0 0 0
X0007 0 1>1 0 0 0 0 0 0

[SEARCH] [ ON ] [ OFF ] [ ] [STATUS]

[OVRSET] [ OVRRST ] [ ] [ INIT ] [ ]

456
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

3.9.4 The method described below applies to both FORCING and OVERRIDE
Modifying the Values of modes.
Signals by Forced (1) Modifying signal values on a bitbybit basis
Input/Output Position the cursor to a desired input bit, then enter a desired value
by using one of the following three methods:
(a) Enter 1, then press the INPUT key or the [ON] soft key.
The signal is forcibly turned on.
(b) Enter 0, then press the INPUT key or the [OFF] soft key.
The signal is forcibly turned off.
(c) Press the INPUT key.
The on/off state of the signal is reversed.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0

(2) Modifying signal values on a bytebybyte basis


Move the cursor to a desired input byte, then enter a desired value by
using one of the following three methods:
(a) Enter a binary number of no more than 8 digits, then press the
INPUT key. (If an entered number is shorter than 8 digits, the
number is entered starting from bit 0.)
Example: When 100 is entered, the number is entered at the
following bit positions:
Bit No. 76543210
00000100
(b) Press the [ON] soft key.
All bits of the specified byte are set to 1.
(c) Press the [OFF] soft key.
All bits of the specified byte are set to 0.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0

457
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
(PMCDGN) PMC OPERATION (CRT/MDI) B61863E/14

3.9.5 (1) Setting OVERRIDE


OVERRIDE can be set as described below.
Setting/Clearing By using the [OVRSET] soft key, place the desired bit/byte in the
OVERRIDE OVERRIDE state.
(a) Setting OVERRIDE on a bitbybit basis
Move the cursor to the desired bit, then press the [OVRSET] soft
key.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0

Then, the display changes as shown below.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0> 0 0 0

(b) Setting OVERRIDE on a bytebybyte basis


Position the cursor to the desired byte, then press the [OVRSET]
soft key.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 0 0 0

Then, the display changes as shown below.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0>0 0>0 0>0 0>0 0>0 0>0 0>0 0>0

When OVERRIDE is set, the signal resumes the state existing


before OVERRIDE setting. When OVERRIDE is set for a pulse
signal, for example, the signal state existing when the [OVRSET]
soft key is pressed is overridden.
Each bit for which OVERRIDE is set has > added in the status
display.
In OVERRIDE mode, those signal states that are not in the
OVERRIDE state are also displayed.
For an X signal:
(Input signal from the machine) 0 > 1 (input signal to the
ladder)
For a Y signal
(Output signal from the ladder) 0 > 1 (output signal to the
machine)

458
3. PMC I/O SIGNAL DISPLAY AND
INTERNAL RELAY DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCDGN)

(2) Clearing OVERRIDE


By using the [OVRRST] soft key, clear the OVERRIDE state of the
desired bit/byte.
This operation returns the state of a signal to the state existing before
OVERRIDE setting.
(a) Clearing OVERRIDE on a bitbybit basis
Position the cursor to the desired bit, then press the [OVRRST]
soft key.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 1> 0 0 0

Then, the display changes as shown below.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 0 0 0 0 0 1 0 0

(b) Clearing OVERRIDE on a bytebybyte basis


Position the cursor to the desired byte, then press the [OVRRST]
soft key.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 1>0 0>1 1>0 0>0 1>0 1>1 1>0 0>1

Then, the display changes as shown below.

PMC SIGNAL FORCING OVERRIDE MONIT RUN

NO. 7 6 5 4 3 2 1 0
X0000 1 0 1 0 1 1 1 0

(c) Clearing OVERRIDE for all X and Y areas


Press the [INIT] soft key. Then, the message CLEAR
OVERRIDES OK? is displayed.
By using the soft key [EXEC]/[CANCEL], execute or cancel the
clearing of OVERRIDE.

459
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

4 PMC PARAMETERS SETTING AND DISPLAY (PMCPRM)

460
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

4.1 Parameters of TIMER, COUNTER, KEEP RELAY and DATA TABLE,


which are nonvolatile, are set and displayed with CRT/MDI panel.
OUTLINE To use this function, press the soft key [PMCPRM] of PMC basic menu
screen.

NOTE
The address and contents of the nonvolatile memory are
described in 3.5 to 3.8 of I3. ADDRESS and I6.
NONVOLATILE MEMORY.

461
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

4.2 1 Place the sequence program in the STOP state.


INPUT PMC 2 When the sequence program is in the RUN state, perform the setting
PARAMETERS FROM below.
MDI PANEL (1) Set NC to MDI mode or Emergency Stop status.
(2) Set PWE of NC setting screen or Program Protect
Signal(KEY4) to 1. (See the following table.)
PWE KEY4
TIMER

COUNTER : Alternative
KEEP RELAY

DATA TABLE : Alternative

3 Press the following soft keys to select the screens.


[TIMER ] : TIMER screen
[COUNTR] : COUNTER screen
[KEEPRL] : KEEP RELAY screen
[ DATA ] : DATA TABLE screen
4 By using cursor keys, move cursor to the position for setting value.
5 Press the INPUT key after typing the value.
6 Set PWE or KEY4 to 0 after setting value.

4.2.1 1 This function is effective on the screen of TIMER, COUNTER,


KEEP RELAY, and DATA TABLE.
Multiple Data Input
2 Up to 10 data can be inputted at once.
3 The cursor is moved to the final data position of inputted data.
(1) Input method
D ; (EOB) is used for separating data.
Press the INPUT key after typing 100; 200; 300.
D ; = is used for inputting the same value as preceding data.
Press the INPUT key after typing 100; =; =; 200; =, and it
becomes 100, 100, 100, 200, 200.
D ; ; is used for skipping an input address.
Press the INPUT key after typing 100; ; 100.
The second data is not inputted.

462
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

4.3
SETTING AND
DISPLAY SCREEN

4.3.1 The TIMER times of the functional instruction TMR(SUB 3) are set and
Timer Screen (TIMER) displayed on this screen.

Page No.(Change pages with the page keys.)


The TIMER No.s used by TIMER instruction
The addresses refered by sequence program

PMC PRM (TIMER) #001 MONIT RUN

NO. ADDRESS DATA NO. ADDRESS DATA TIMER times(See the following table.)
01 T00 2016 11 T20 1000
TIMER Minimum Maximum
02 T02 48 12 T22 8
No.s time time
03 T04 960 13 T24 0
04 T06 1008 14 T26 32 1 to 8 48 (ms) 1572.8 (s)
05 T08 0 15 T28 0
06 T10 0 16 T30 0
07 T12 96 17 T32 2000 9 to 40 or
9 to 150
08 T14 0 18 T34 0 (*1) 8 (ms) 262.136 (s)
09 T16 8 19 T36 8
10 T18 16 20 T38 10000
*1 The usable numbers vary from one model to
another. For details, see Section 5.4 in Part I.
[TIMER ] [COUNTR ] [KEEPRL ] [ DATA ] [ ]

463
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

4.3.2 The maximum(PRESET) values and CURRENT values of the functional


Counter Screen instruction CTR(SUB 5) are set and displayed on this screen.
(COUNTR)
The COUNTER No.s used by CTR instruction
The addresses refered by sequence program
Page No.(Change pages with the page keys.)
The maximum(PRESET) values of COUNTER
(The minimum values are specified in CTR instruction.)

PMC PRM (COUNTER) #001 MONIT RUN

NO. ADDRESS PRESET CURRENT The CURRENT values of COUNTER


01 C00 4 1
02 C04 4 2
03 C08 4 3
04 C12 5 4
05 C16 4 5
06 C20 545 6
07 C24 5 3 09999 in BCD(032767 in Binary) can be set as
08 C28 6 2 the PRESET and CURRENT values.
09 C32 6 1
10 C36 6 4

[TIMER ] [COUNTR ] [KEEPRL ] [ DATA ] [ ]

4.3.3 The KEEP RELAYs and the Data for Controlling nonvolatile memory are
set and displayed on this screen.
Keep Relay (KEEPRL)

PMC PRM (KEEP RELAY) MONIT RUN


The address used by sequence program
NO. ADDRESS DATA NO. ADDRESS DATA
01 K00 00000000 11 K10 00000000
02 K01 00000000 12 K11 00000000
03 K02 00000000 13 K12 00000000
04 K03 00000000 14 K13 00000000
05 K04 00000000 15 K14 00000000
06 K05 00000000 16 K15 00000000
07 K06 00000000 17 K16 00000000
08 K07 00000000 18 K17 00000110
09 K08 00000000 19 K18 00000000
10 K09 00000000 20 K19 00000000
J : This area is reserved for special use. (Note)

[TIMER ] [COUNTR ] [KEEPRL ] [ DATA ] [ ]

464
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

NOTE
1 The Data for Controlling Nonvolatile Memory(K16)
Refer to I6.1(4)Nonvolatile Memory Control.
2 The Data for PMC Management Software(K17,18,19)
Be careful of using the following KEEP RELAYs, because
they are used by PMC Management Software.

The Data for PMC Management Software


Model PA1 PA3
PMC control software data 1 K17 K17
PMC control software data 2 K18 K18
Reserved K19 K19

Model SA1 SA2


PMC control software data 1 K17 K17
PMC control software data 2 K18 K18
Reserved K19 K19

Model SB SB2
PMC control software data 1 K17 K17
PMC control software data 2 K18 K18
Reserved K19 K19

SA3/ SB3/ SB4/


Model
SA5 SB5 SB6
PMC control software data 1 K17 K17 K900
PMC control software data 2 K18 K18 K901
PMC control software data 3 K19 K19 K902
Reserved K903
to
K909

Model SC SC3 SC4


PMC control software data 1 K17 K17 K900
PMC control software data 2 K18 K18 K901
PMC control software data 3 K19 K19 K902
Reserved K903
to
K909

Model NB NB2
PMC control software data 1 K17 K900
PMC control software data 2 K18 K901
PMC control software data 3 K19 K902
Reserved K903
to
K909

PMC control software data 1 (K17 or K900)


#7 #6 #5 #4 #3 #2 #1 #0
K17
or DTBLDSP ANASTAT TRCSTART MEMINP SELCTMDL AUTORUN PRGRAM LADMASK
K900

465
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

#7 DTBLDSP 0 : The PMC parameter data table control screen is


displayed.
1 : The PMC parameter data table control screen is
not displayed.
#6 ANASTAT 0 : In the function for displaying signal waveforms,
sampling starts when the [START] soft key is pressed.
1 : In the function for displaying signal waveforms,
sampling starts automatically when the power is
turned on.
* This bit is effective only for applicable models specified in 3.6,
Function for Displaying Signal Waveforms (ANALYS), in Part
II.
#5 TRCSTAT 0 : In the signal trace function, tracing starts when
the [EXEC] soft key is pressed.
1 : In the signal trace function, tracing starts
automatically when the power is turned on.
#4 MEMINP 0 : Data cannot be entered in the memory content
display function.
1 : Data can be entered in the memory content
display function.
* This bit is effective only for applicable models specified in 3.5,
Display the Contents of Memory (M.SRCH), in Part II.

#3 SELCTMDL 0 : The sequence program stored in ROM (EPROM)


is enabled.
1 : The sequence program stored in the RAM
module or ROM module (only for
PMCSB2/SB3) is enabled.
* This bit enables either the EPROM module or ROM/RAM
module when both modules are provided. It is effective for the
PMCSA1, SA2, SA3, SB, SB2, and SB3. (It is not effective for
the Series 20 or Series 16/18 MODELB.)

#2 AUTORUN 0 : In RAM operation, a sequence program is not


executed when the power is turned on.
1 : In RAM operation, a sequence program is
executed automatically when the power is turned
on (as in ROM operation).
* For the PMC of the Series 16/18 MODELB/C, Series
16i/18i/21iMODEL A, and Power Mate iD/H this bit has the
following meanings.

0 : The sequence program is executed automatically


when the power is turned on.
1 : The sequence program is executed when the
[RUN] soft key is pressed.
#1 PRGRAM 0 : The builtin programmer function is not
operated.
(The programmer menu is not displayed, either.)
1 : The builtin programmer function is operated.
(The programmer menu is displayed.)

466
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

WARNING
Set this bit to 0 before shipment from the factory.
If the bit setting is left as 0, the operator may stop execution
of the ladder diagram by mistake, and cause an accident.

#0 LADMASK 0 : Ladder dynamic display (PCLAD) is performed.


1 : Ladder dynamic display (PCLAD) is not
performed.

PMC control software data 2 (K18 or K901)


#7 #6 #5 #4 #3 #2 #1 #0
K18
or IGNDINT CHKPRTY CALCPRTY TRNSRAM TRGSTAT DBGSTAT IGNKEY
K901

#7 IGNDINT 0 : When the screen is switched to the PCMMDI


screen, the CRT is initialized.
1 : When the screen is switched to the PCMMDI
screen, the CRT is not initialized.
* The flag is used to determine whether PMC control software
initializes the CRT when the screen is switched to the PCMMDI
screen. Design application software sot that the CRT is initialized
when this flag is on.
#5 CHKPRTY 0 : The parity check is performed for the system
ROM and program ROM/RAM.
1 : The parity check is not performed for the system
ROM and program ROM/RAM.
#4 CALCPRTY 0 : The builtin programmer function performs
RAM parity calculation.
1 : The builtin programmer function does not
performs RAM parity calculation.
#3 TRNSRAM 0 : A ladder program is not automatically sent to the
backup RAM after online editing is completed.
1 : A ladder program is automatically sent to the
backup RAM after online editing is completed.
#2 TRGSTAT 0 : The trigger stop function does not automatically
start when the power is turned on.
1 : The trigger stop function automatically starts
when the power is turned on.
#1 DBGSTAT 0 : In the C language debug function, the break
processing does not automatically start when the
power is turned on.
1 : In the C language debug function, the break
processing automatically starts when the power is
turned on.
* This flag is effective for the PMCSC/SC3/SC4.
#0 IGNKEY 0 : Function keys are enabled when the user program
displays the user screen.
1 : Function keys are disabled when the user
program displays the user screen.

467
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

* This flag is effective for the PMCSC/SC3/SC4/NB/NB2, When


this bit is set to 1 in the user screen, the screen cannot be switched
to the NC screen using the function keys. For this reason, a
program that always sets this bit to 0 or that changes the screen
to the NC screen is required.
* Be sure to set this flag to 1 when the CNC screen display function
is used to display the user menu on an open CNC.
PMC control software data 3 (K19 or K902)
K19 #7 #6 #5 #4 #3 #2 #1 #0
or LCDMONO CREJECT FROM
K902
WRT

#3 LCDMONO 0 : Ladderrelated display is brightnessadjusted


when a monochrome LCD is used with the VGA
setting.
1 : Ladderrelated display is not
brightnessadjusted but is displayed in reverse
video when a monochrome LCD is used with the
VGA setting.
#1 CREJECT 0 : A Clanguage program is activated.
1 : A Clanguage program is forcibly not activated.
* The flag is effective for the PMCRC/RC3/RC4.
#0 FROMWRT 0 : The program is not automatically written to
FROM.
1 : After a lodder program on C program has been
edited, the program is automatically written to
FROM.

CAUTION
Be sure to set bits not used in the PMC control software data
to 0.

In case of PMCPA1/PA3
on Power Mate #7 #6 #5 #4 #3 #2 #1 #0
K17 DTBLDSP ANASTAT TRCSTART MEMINP AUTORUN PRGRAM LADMASK

#7 DTBLDSP 0 : The PMC parameter data table control screen is


displayed.
1 : The PMC parameter data table control screen is
not displayed.
#6 ANASTAT 0 : Sampling is started with the signal waveform
display function by using the execution soft key.
1 : Sampling is started with the signal waveform
display function, automatically after the power is
turned on.
(This setting cannot be used with the Power
MateD/F.)
#5 TRCSTAT 0 : Trace operation is started with the signal trace
function by using the trace execution soft key.
1 : Trace operation is started with the signal trace
function, automatically after the power is turned
on.

468
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

#4 MEMINP 0 : Data cannot be entered with the memory contents


display function.
1 : Data can be entered with the memory contents
display function.
(This setting cannot be used with the Power
MateD/F.)
#2 AUTORUN 0 : The sequence program is executed automatically
after the power is turned on.
(This setting cannot be used with the Power
MateD/F. Set to 0.)
1 : The sequence program is executed by using the
sequence program execution soft key.
#1 PRGRAM 0 : The builtin programmer function is not
operated. (The programmer menu is not
displayed either.)
1 : The builtin programmer function is operated.
(The programmer menu is displayed.)
#0 LADMASK 0 : Ladder dynamic display (PMCLAD) is
performed.
1 : Ladder dynamic display (PMCLAD) is not
performed.

#7 #6 #5 #4 #3 #2 #1 #0
K18 CHKPRTY CALCPRTY TRANSRAM TRGSTAT

#5 CHKPRTY 0 : System ROM and program ROM/RAM parity


checks are performed.
1 : System ROM and program ROM/RAM parity
checks are not performed.
#4 CALCPRTY 0 : A RAM parity calculation is performed with the
builtin programmer function.
1 : A RAM parity calculation is not performed with
the builtin programmer function.
#3 TRNSRAM 0 : Upon the completion of online editing, the ladder
program is not automatically transferred to RAM
for editing.
1 : Upon the completion of online editing, the ladder
program is automatically transferred to RAM for
editing. (This setting cannot be used with the
Power MateD/F.)
#2 TRGSTAT 0 : When the power is turned on, the trigger stop
function is not started automatically.
1 : When the power is turned on, the trigger stop
function is started automatically.
(This setting cannot be used with the Power
MateD/F.)

#7 #6 #5 #4 #3 #2 #1 #0
K19 FROMWRT

469
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

#0 FROMWRT 0 : After a ladder is edited, the ladder is not


automatically written to FROM.
1 : After a ladder is edited, the ladder is
automatically written to FROM.
(This setting cannot be used with the Power
MateD/F.)

CAUTION
The unused area of the data for the PMC management
software must always be set to 0.

4.3.4 DATA TABLE consists of two screens, that is, Data Table Controlling
Data Table (DATA) Data screen and Data Table screen.
(1) Data Table Controlling Data Screen
Data Table Controlling Data Screen for controlling Data Table is
displayed by pressing the soft key [DATA].
Group No.s
The top address of Data Table
Table Parameters(Note)
Page No. (Change pages with the page keys)
Data length
(0:1byte, 1:2bytes, 2:4bytes)
PMC DATA TBL CONTROL #001 MONIT RUN

GROUP TABLE COUNT = 16 The number of group of Data Table

NO. ADDRESS PARAMETER TYPE NO. OF DATA The data numbers of each Data Table
001 D0000 00000000 0 20
002 D0020 00000010 0 81
003 D0101 00000001 1 100
004 D0301 00000000 2 50
005 D0501 00000011 0 5
006 D0506 00000000 0 10
007 D0506 00000000 1 10 * You can set the same address in other groups.
008 D0506 00000000 2 10

You can initialize the Data Table setting data. The


[G.DATA] [G.CONT] [NO.SRH] [ ] [ INIT ] initial data is as follows.

PMC DATA TBL CONTROL #001 MONIT RUN

GROUP TABLE COUNT = 1

NO. ADDRESS PARAMETER TYPE NO. OF DATA


001 D0000 00000000 0 1860

002 * 3000:PMCSB3/SB5
/SC/SC3/NB
* 8000:PMCSB4/SB6/NB2
Press this key after typing the group No., and the cursor is moved to the group.
Press this key after typing the number of group, and the Group Table Count is set.
You can change the screen to Data Table.

470
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

NOTE
Table Parameter
#7 #6 #5 #4 #3 #2 #1 #0

0 : Binary
1 : BCD

0 : Available to input
1 : Unavailable to input (Protection mode)

0 : Binary of BCD (The bit 0 is valid


1 : Hexadecimal (The bit 0 is invalid.)

(2) Data Table Screen


If the Data Table Controlling Data is set, Data Table Screen is
displayed by pressing the soft key [G.DATA].
Group No.s

Page No.
(Change pages with the page keys)
PMC PRM (DATA) 001/001 MONIT RUN

NO. ADDRESS DATA The address used by sequence program


001 D0000 10
002 D0001 48
003 D0002 5
004 D0003 64
005 D0004 0
006 D0005 0
007 D0006 48
008 D0007 10
009 D0008 1
010 D0009 1

[C.DATA] [GSRCH] [SEARCH] [ ] [ ]

Press this key after typing the address (ex.D8;D can be omitted), and the cursor
is moved to the address in the current group.

If you search the Data Table in the other group, press this key after typing the
group No., and the cursor is moved to the top of the address in the specified
group.

You can change the screen to Data Table Controlling Data.

471
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

4.4 Part of KEEP RELAY parameters can be set on SETTING Screen.


SETTING SCREEN : Can be used
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SC SC3 SC4 NB NB2

NOTE
: Can be used for the specific series of CNC.
(Series 16 : B005/11 to, B105/08 to, B305/04 to, B009/03
to, All serieses of MODEL C)
(Series 18 : BD03/12 to, BE03/09 to, BG23/03 to,
BG03/06 to, BD09/02 to, BE09/14 to, All serieses of
MODEL C)
PMCPA3 can be used only with Power MateH.

D The display items are different according to the type of CNC.


D The parameter is set by a soft key or the <INPUT> key with 0 or 1.
D Once an item has been set, the cursor moves to the next item.
[PMCSA1/SA3/SB/SB3/SB4 on SETTING screen]

PMC PRM (SETTING) MONIT RUN

PROGRAMMER ENABLE = 0(0:NO 1:YES) (K17. 1)


LADDER START (RAM) = 0(0:MANUAL 1:AUTO) (K17. 2)
SELECT ROM/RAM = 0(0:ROM 1:RAM) (K17. 3)
SIGNAL TRACE START = 0(0:MANUAL 1:AUTO) (K17. 5)
DATA TBL CNTL SCREEN = 0(0:YES 1:NO) (K17. 7)
SIGNAL TRIGGER START = 0(0:MANUAL 1:AUTO) (K18. 2)
TRANS LADDER(ONLEDT) = 0(0:MANUAL 1: AUTO) (K18. 3)

[ NO ] [ YES ] [ ] [ ] [ ]

* The bracketed addresses show the related KEEP RELAYs.

472
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

[PMCSC/SC3/SC4 on SETTING screen]

PMC PRM (SETTING) MONIT RUN

PROGRAMMER ENABLE = 0(0:NO 1:YES) (K17. 1)


LADDER START (RAM) = 0(0:MANUAL 1:AUTO) (K17. 2)
RAM WRITE ENABLE = 0(0:NO 1:YES) (K17. 4)
SIGNAL TRACE START = 0(0:MANUAL 1:AUTO) (K17. 5)
SIGNAL ANALYS START = 0(0:MANUAL 1:AUTO) (K17. 6)
DATA TBL CNTL SCREEN = 0(0:YES 1:NO) (K17. 7)
FUNC KEY INP(CUSTOM) = 0(0:AVAL 1:IGNORE) (K18. 0)
DEBUG FUNC START = 0(0:MANUAL 1:AUTO) (K18. 1)
SIGNAL TRIGGER START = 0(0:MANUAL 1:AUTO) (K18. 2)
TRANS LADDER (ONLEDT)= 0(0:MANUAL 1:AUTO) (K18. 3)
INITPMCMDI SCREEN = 0(0:YES 1:NO) (K18. 7)

[ NO ] [ YES ] [ ] [ ] [ ]

* The bracketed addresses show the related KEEP RELAYs.


[PMCPA3 on SETTING screen]

PMC PRM (SETTING) MONIT RUN

PROGRAMMER ENABLE = 0(0:NO 1:YES) (K17. 1)


LADDER START = 0(0:AUTO 1:MANUAL) (K17. 2)
RAM WRITE ENABLE = 0(0:NO 1:YES) (K17. 4)
SIGNAL TRACE START = 0(0:MANUAL 1:AUTO) (K17. 5)
DATA TBL CNTL SCREEN = 0(0:YES 1:NO) (K17. 7)
SIGNAL TRIGGER START = 0(0:MANUAL 1:AUTO) (K18. 2)

[ NO ] [ YES ] [ ] [ ] [ ]

* The bracketed address show the related KEEP RELAYs

473
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

[PMCNB/NB2 on SETTING screen]

PMC PRM (SETTING) MONIT RUN


NB NB2
PROGRAMMER ENABLE = 0 (0:NO 1:YES) (K17. 1, K900.1)
AUTOMATIC LADDER START = 0 (0:MANUAL 1:AUTO) (K17. 2, K900.2)
RAM WRITE ENABLE IN [M.SRC] = 0 (0:NO 1:YES) (K17. 4, K900.4)
SIGNAL TRACE START = 0 (0:MANUAL 1:AUTO) (K17. 5, K900.5)
SIGNAL ANALYSIS START = 0 (0:MANUAL 1:AUTO) (K17. 6, K900.6)
DATA TABLE CONTROL SCREEN = 0 (0:YES 1:NO) (K17. 7, K900.7)
NC/PC KEY EFFECTIVE = 0 (0:AVAL 1:IGNORE) (K18. 0, K901.0)
DEBUG FUNCTION START = 0 (0:MANUAL 1:AUTO)
(K18. 1, K901.1)
SIGNAL TRIGGER START = 0 (0:MANUAL 1:AUTO)
TRANSFER LADDER (ONLINEEDIT) = 0 (0:MANUAL 1:AUTO) (K18. 2, K901.2)
INITIALIZE PMCMDI SCREEN = 0 (0:YES 1:NO) (K18. 3, K901.3)
WRITE TO FROM (EDIT) = 0 (0:NO 1:YES) (K18. 7, K901.7)
REJECT LANGUAGE = 0 (0:NO 1:YES) (K19. 0, K902.0)
SIGNAL ANALYSIS DISPLAY MODE = 0 (0:GRAPHIC 1:TEXT) (K19. 1, K902.1)
SPECIFY NC WINDOW FORMAT = 0 (0:AUTO 1:MANUAL)
NC WINDOW FORMAT (TOOL DATA) = 0 (0:EXPAND 1:STANDARD)

[ NO ] [ YES ] [ ] [ ] [ ]

* The bracketed addresses show the related KEEP RELAYs.


SIGNAL TRIGGER ENABLE
Displayed in case of PMCNB(4047).
Stop function of ladder diagram display by trigger of signal is set.
The trigger stop function can be used by selecting YES ,and turning
off and on the power.
WRITE TO FROM (EDIT)
Setting to write the LADDER data in FROM, when the edit of
LADDER ends.
When you select YES and then get out of the EDIT screen, a
message confirming if you write to FROM is displayed.
REJECT LANGUAGE
It is setting of the start of the program of C language.
When YES is selected, the program of C language is not started.
SIGNAL ANALYSIS DISPLAY MODE
The display form in the signal waveform display function is set.
The display form can be selected.
Select TEXT and it is displayed by the character.
Select GRAPHIC and it is displayed by the line.
SPECIFY NC WINDOW FORMAT
The form in functional instruction WINDR and WINDW are set.
When AUTO is selected, the format is automatically distinguished
by the state of bit 4 of NC parameter 7401.
When MANUAL is selected, the format is selected by NC
WINDOW FORMAT (TOOL DATA).

474
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

NC WINDOW FORMAT (TOOL DATA)


The format in functional instruction WINDR and WINDW are set.
When MANUAL is selected by SPECIFY NC WINDOW
FORMAT, this item is effective.
The window instruction of a new format can be used by selecting
EXPAND.
(The same meaning as bit 4 of NC parameter 7401 is 1.)
An old window instruction can be used by selecting STANDARD
(The same meaning as bit 4 of NC parameter 7401 is 0.)
GRAY SCALE DISPLAY
This parameter sets the ladderrelated display method when a
monochrome LCD is used. When you find the screen display on the
monochrome LCD not easy to view, change this parameter setting.
When USE is selected, the difference in brightness is used for screen
display.
When UNUSED is selected, reverse video is used for screen display.
NOTE
A change made to this parameter does not become valid
until the power is turned on next. After the setting of this
parameter has been changed, the power must be turned off
then back on for the setting to become effective.

4.4.1 Enable or disable the following function and mode:


Other Setting Screens D Multilanguage display function
D OVERRIDE mode of the forced input/output function
(1) Setting screen display
Each setting screen can be displayed by pressing the [NEXT] or
[PREV] soft key on the setting parameter screen.

[ YES ] [ NO ] [ ] [ PREV ] [ NEXT ]

Setting parameter

[ INPUT ] [ ] [ ] [ PREV ] [ NEXT ]

Setting parameter
(multilanguagedisplay function)

[ YES ] [ NO ] [ ] [ PREV ] [ NEXT ]

Setting parameter (OVERRIDE mode


of the forced input/output function)

475
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

Each setting parameter can be set when the respective conditions are
satisfied.
(a) Multilanguage display function
D The PROGRAM ENABLE setting parameter is set to YES
(bit 1 of K17 or bit 1 of K900 is set to 1).
D The PMC model is SB6.
(b) OVERRIDE mode of the forced input/output function
D The PROGRAM ENABLE setting parameter is set to YES
(bit 1 of K17 or bit 1 of K900 is set to 1)
D The PMC model is SA5, SB5, or SB6.
D The editing function is provided.
(2) Setting operations
(a) Setting the Multilanguage display function
Position the cursor to the each setting item with the arrow keys,
enter the desired data, then press the [INPUT] soft key.

PMC PRM (MESSAGE SHIFT) MONIT RUN

MESSAGE SHIFT VALUE = 0


MESSAGE SHIFT START ADDRESS = A0000.0

[INPUT] [ ] [ ] [ PREV ] [ NEXT ]

(i) Parameters
D MESSAGE SHIFT VALUE
Enter a desired message display request bit shift amount.
A value from 0 to 999 can be entered. The initially displayed
value is 0.
Entered data is maintained even after the power is turned off.
D MESSAGE SHIFT START ADDRESS
Enter a shift start bit address in the message display request
bit area.
An address A value can be entered. The initially displayed
value is A0.0.
Entered data is maintained even after the power is turned off.

NOTE
Data entered for MESSAGE SHIFT START ADDRESS is
valid only when a value other than 0 is entered for
MESSAGE SHIFT VALUE.

476
4. PMC PARAMETERS SETTING AND
B61863E/14 PMC OPERATION (CRT/MDI) DISPLAY (PMCPRM)

(b) OVERRIDE mode of the forced input/output function


D Set OVERRIDE mode by using the soft key or by entering
0 or 1 followed by the <INPUT> key.

PMC PRM (OVERRIDE) MONIT RUN

OVERRIDE ENABLE = 0 (0:NO 1:YES)

[ NO ] [ YES ] [ ] [ PREV ] [ NEXT ]

OVERRIDE ENABLE 0 : OVERRIDE mode is disabled.


1 : OVERRIDE mode is enabled.

CAUTION
If the setting of this parameter is modified, the new setting
becomes effective when the power is next turned on. After
this parameter has been modified, the power must be
turned off then back on.

477
4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM) PMC OPERATION (CRT/MDI) B61863E/14

4.5 If you make a keyboard without cursor keys, you must move cursor by
searching the address or so. In case of TIMER,COUNTER and KEEP
NOTE RELAY, press the soft key [TIMER],[COUNTR] or [KEEPRL] after
typing the address(Ex.1,2).
In case of Data Table Controlling Data, press the soft key [DATA](or
[NO.SRH] if Data Table screen has already been displayed) after typing
the group No.(Ex.3). In case of the Data Table, press the soft key
[SEARCH] after typing the address in the Data Table screen which
contains the address you want to search(Ex.4).
Ex.1) In case of setting the TIMER NO.11(ADDRESS T20)
1 Press the soft key [TIMER] after typing T20(or T21;T can be
omitted.).
2 Press the INPUT key after typing the value.
Ex.2) In case of setting PRESET and CURRENT values of the
COUNTER NO.02(ADDRESS C04)
1 PRESET Press the soft key [COUNTER] after typing C4 (or
C5;C can be omitted).
CURRENT Press the soft key [COUNTER] after typing
C6 (or C7;C can be omitted).
2 Press the INPUT key after typing the value.

CAUTION
It is not the number(NO.) but the address(ADDRESS) that
you type in searching.

Ex.3) In case of the ADDRESS,PARAMETER,TYPE and NO. OF


DATA of the Data Table Controlling Data NO.002.
1 Press the soft key [NO.SRH] after typing 2, and the cursor is
moved to the ADDRESS position.
2 Press the INPUT key after typing the ADDRESS(ex.D20;D must
not be omitted), and the cursor is automatically moved to the next
position(PARAMETER). The cursor is moved only by pressing
the INPUT key.
3 In the same way, set the PARAMETER,TYPE and NO. OF
DATA. If you finish setting the NO. OF DATA, the cursor is
moved to the position(ADDRESS) in the same line.
Ex.4) In case of setting D22 in the Data Table of the group 2
1 Press the soft key [G.DATA] on the Data Table Controlling Data
screen, and the Data Table screen is displayed.
2 Press the soft key [GSRCH] after typing 2 on the Data Table
screen, and the Data Table of the group 2 is displayed.
3 Press the soft key [SEARCH] after typing D22(D can be omitted).
4 Press the INPUT key after typing the value.

478
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

5 PMC LADDER DIAGRAM DISPLAY (PMCLAD)

Displaying the PMC ladder diagram on CRT/MDI panel is available.


This ladder diagram display function offers functions effectively used for
locating troubles in addition to the simple ladder diagram display.
The following functions are done using the soft keys.
(1) Search and display of optional relay coil on ladder diagrams.

(2) Ladder diagram dynamic display.


(3) Stop of ladder diagram display by trigger of signal (on or off).
(4) Screen-dividing display.
(5) Monitor display of signal condition.
(6) Monitor display of parameter in functional instructions.
(7) ON LINE edit.
For this operation, depress [PMCLAD] soft key of PMC basic menu to
bring the following menu.
ATYPE

PMCLAD PMCDGN PMCPRM

RET

TOP BOTTOM SRCH W-SRCH N-SRCH

Sec. 5.5 Sec. 5.5 Sec. 5.5 Sec. 5.5 Sec.5.5 NEXT

F-SRCH ADRESS
(SYMBOL)
Sec. 5.5 Sec. 5.4

BTYPE

PMCLAD PMCDGN PMCPRM

RET

SEARCH ADRESS TRIGER WINDOW


(SYMBOL)

Sec. 5.5 Sec. 5.4 Sec. 5.6 Sec. 5.7 NEXT

DUMP DPARA ONLEDT


(NDPARA)

Sec. 5.2 Sec. 5.3 Sec. 5.8

479
5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) PMC OPERATION (CRT/MDI) B61863E/14

5.1 The following functions can be done the ladder diagram display screen.
LADDER DIAGRAM (a) Specified relay coil of ladder diagrams can be searched and
displayed.
DISPLAY
(b) Ladder diagram dynamic display.
The logical on-off states during a sequence program execution are
displayed on a ladder diagram by changing the brightness in case
of a monochrome CRT or by changing colors in case of a color
CRT.
(1) Ladder diagram display
Press [PMCLAD] soft key, then the ladder diagram will be displayed.
Eight relay contacts and relay coils in total are displayed in the
horizontal direction of the CRT screen.
If the number of relay contacts exceed the above value, they are
displayed in 2 or more lines.

Signal name
(Within 6 characters) LADDER MONIT RUN
Address or
symbol name
MA SPDALM X2.4 MACHINE Comments
READY (within 30
characters)
MACHINE
ALARM

9 lines

[SEARCH] [ADRESS ] [TRIGER] [WINDOW] [ ]

[ DUMP ] [ DPARA ] [ ] [ONLEDT] [ ]

Fig. 5.1 Ladder diagram display

NOTE
When online communication is being performed with USE
selected on the online setting screen (see Section III8.5),
pressing the [PMCLAD] soft key displays the message
REJECT (ONLINE MONITOR ACTIVE), disabling access
to the display. In such a case, select NOT USED on the
online setting screen, and stop online communication on
the PC side.

480
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

5.2 Ladder diagram and signal status dump can be displayed together.
DUMP DISPLAY ON The dump is displayed over 2 lines at the last line of ladder diagram by
LADDER DIAGRAM pressing the [DUMP] soft key.
PAGE keys or [SEARCH] soft key is used for changing of PMC
address.

LADDER *TITLE DATA REMARKS 32 BYTES * NET 00001-00004 MONIT RUN

X1000.0 X1000.0
X1000.1 X1000.2 X1000.1
X1000.3

X1001.0 ACT SUB 3 0002 X1001.0


TMR

X1001.1 X1001.2 X1001.1

X1001.3

ADDRESS DUMP
G0000 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .......
G0016 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .......

[ BYTE ] [ WORD ] [ D.WORD ] [ ] [ ]

The [DUMP] soft key has the following functions.


(1) [BYTE] : Byte type display (1 BYTE)
G0000 00 14 00 00 01 00 00 00 00 00 00 00 00 00 00 00
G0016 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
(2) [WORD] : Word type display (2 BYTE)
G0000 1400 0000 0001 0000 0000 0000 0000 0000
G0016 0000 0000 0000 0000 0000 0000 0000 0000
(3) [D.WORD] : Long word type display (4 BYTE)
G0000 00001400 00000001 00000000 00000000
G0016 00000000 00000000 00000000 00000000

481
5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) PMC OPERATION (CRT/MDI) B61863E/14

5.3 The value of parameter of a functional instruction is displayed in the


functional instruction of a ladder diagram.
PARAMETER
DISPLAY ON
LADDER *TITLE DATA REMARKS 32 BYTES * NET 00001-00004 MONIT RUN
LADDER DIAGRAM
X1000.0 X1000.0
X1000.0 RST X1000.3
ABSDE ACT
SUB36 2
ADDB
D0000
[ 0](Content of D0)
1
D0000
[ 0]

[ DUMP ] [ DPARA ] [ ] [ ONLEDT ] [ ]


(NDPARA)

The function of the soft key is as follows :


(1) [DPARA] : The value of parameter is displayed in functional
instruction.
(2) [NDPARA] : The value of parameter is not displayed in functional
instruction.

482
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

5.3.1
The Value of
Functional Instruction
Parameter Data length of instruction
Functional Data parameter (1: byte, 2: word, 4: d. word) Displaying
No.
instruction no. s form
1 2 3 4 5 6
1 END1 0
2 END2 0
3 TMR (NOTE3) 2 4 4 Binary
4 DEC 1 1 BCD
5 CTR (NOTE4) 2 2 2 Binary
6 ROT 3 2 2 2 BCD
7 COD 2 1 2 BCD
8 MOVE 2 1 1 HEX
9 COM 0
10 JMP 0
11 PARI 1 1
12
13
14 DCNV 2 2 2 (Note 1)
15 COMP 2 2 2 BCD
16 COIN 2 2 2 BCD
17 DSCH 3 2 2 2 BCD
18 XMOV 3 2 2 2 BCD
19 ADD 3 2 2 2 BCD
20 SUB 3 2 2 2 BCD
21 MUL 3 2 2 2 BCD
22 DIV 3 2 2 2 BCD
23 NUME 1 2 BCD
24 TMRB (NOTE3) 1 4 Binary
25 DECB 2 1/2/4 1
26 ROTB 4 1/2/4 1/2/4 1/2/4 1/2/4 Binary
27 CODB 2 1 1/2/4
28 MOVOR 3 1 1 1 HEX
29 COME 0
30 JMPE 0
31 DCNVB 2 1/2/4 1/2/4 (Note1)
32 COMPB 2 1/2/4 1/2/4 Binary
33 SFT 1 HEX
34 DSCHB 4 1/2/4 1/2/4 1/2/4 1/2/4 Binary
35 XMOVB 4 1/2/4 1/2/4 1/2/4 1/2/4 Binary
36 ADDB 3 1/2/4 1/2/4 1/2/4 Binary
37 SUBB 3 1/2/4 1/2/4 1/2/4 Binary
38 MULB 3 1/2/4 1/2/4 1/2/4 Binary
39 DIVB 3 1/2/4 1/2/4 1/2/4 Binary
40 NUMEB 1 1/2/4 Binary
41 DISPB 0
42 EXIN 1 4 HEX
43 MOVB 2 1 1 Binary
44 MOVW 2 2 2 Binary
45 MOVN 2 4 4 Binary
46
47
48 END3 0
49 DISP 1 4 HEX
50 PSGNL 2 1 1 HEX
51 WINDR 1 2 Binary
52 WINDW 1 2 Binary
53 AXCTL 1 4 HEX
54 TMRC (NOTE3) 2 4 4 Binary

483
5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) PMC OPERATION (CRT/MDI) B61863E/14

Data length of instruction


Functional Data parameter (1: byte, 2: word, 4: d. word) Displaying
No.
instruction no. s form
1 2 3 4 5 6
55 CTRC (NOTE4) 2 2 2 Binary
56
57 DIFU 0
58 DIFD 0
59 EOR 3 1/2/4 1/2/4 1/2/4 HEX
60 AND 3 1/2/4 1/2/4 1/2/4 HEX
61 OR 3 1/2/4 1/2/4 1/2/4 HEX
62 NOT 2 1/2/4 1/2/4 HEX
63 PSGN2 1 1 HEX
64 END 0
65 CALL 0
66 CALLU 0
67
68 JMPB 0
69 LBL 0
70
71 SP 0
72 SPE 0
73 JMPC 0
74
Y Y
Y Y
87
88 MMC3R 4 2 2 2 2 Unsign
89 MMC3W 4 2 2 2 2 Unsign
90 FNC90 1 2 Binary
91 FNC91 1 2 Binary
92 FNC92 1 2 Binary
93 FNC93 1 2 Binary
94 FNC94 1 2 Binary
95 FNC95 1 2 Binary
96 FNC96 1 2 Binary
97 FNC97 1 2 Binary
98 MMCWR 2 2 2 Unsign
99 MMCWW 2 2 2 Unsign

NOTE
1 The data length of BCD is displayed for 1 is 2-figures, 2 is
4-figures.
2 The value of parameter is not displayed in this instruction.
3 The timer is displayed the content of timer number (3: TMR,
24: TMRB, 54: TMRC).
4 The counter is displayed the content of counter number (5:
CTR, 55: CTRC).

484
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

5.4 If symbol data and comments are defined to the PMC address, a comment
is displayed for symbol display and relay coil.
SYMBOL AND
COMMENT DISPLAY By pressing soft key [ADRESS], the symbol displayed relay is
address-displayed.
By pressing soft key [SYMBOL], the symbol displayed relay is
symbol-displayed.
(See III. PMC programer, 5. 4 Symbol data setting)

LADDER MONIT RUN


Signal name
Address or
symbol name MA SPDALM X2.4 MACHINE Comments
mments READY
MACHINE
ALARM

[ SEARCH ] [ ADRESS ] [ TRIGER ] [ WINDOW ] [ ]


(SYMBOL)

The function of the soft key [ADRESS] is as follows.


(1) [ADRESS] : is used to display the address name.
(2) [SYMBOL] : is used to display the symbol name.

485
5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) PMC OPERATION (CRT/MDI) B61863E/14

5.5 Specified relay coil points of ladder diagrams can be displayed on the
screen.
SEARCH OF
SPECIFIED RELAY For this operation, press [SEARCH] soft key to bring the following menu.
COIL POINTS IN
LADDER DIAGRAM SEARCH ADRESS TRIGER WINDOW

RET

TOP BOTTOM SRCH W- SRCH N- SRCH

NEXT

F- SRCH

The function of the soft key [SEARCH] is as follows :


(1) [TOP] : Displays the first NET of the ladder from the
beginning of the screen.
(2) [BOTTOM] : Displays the last NET of the ladder from the
beginning of the screen.
(3) [SRCH] : When the address and bit number or symbol name to
be searched are typed in and the [SRCH] key is
pressed, the specified address or symbol is searched
from the top of the current screen. If the specified
relay cannot be found until the last NET of the ladder,
the relay are searched again from the first ladder until
the NET where they started being searched.
(4) [W-SRCH] : This is used for searching a relay coil. Press
[W-SRCH] soft key after keying in an address and bit
number or symbol name. If the same address and bit
number or the same symbol name is detected, the
screen containing it will be displayed.
(5) [N-SRCH] : Displays the ladder with the specified NET number
from the beginning of the screen. Moreover, when
pressing the [N-SRCH] key without keying the NET
number, the display is scrolled down by one NET.
(6) [F-SRCH] : When the functional instruction name or functional
instruction number is typed in and the [F-SRCH] key
is pressed, the functional instruction is searched.

486
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

5.6
STOP OF LADDER : Can be used
: Cannot be us
DIAGRAM DISPLAY PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SC SC3 SC4 NB NB2
BY TRIGGER OF
SIGNAL
NOTE
: Can be used for the specific series of CNC
(Series 16 : B005/11 to, B105/08 to, B305/04 to, B009/03
to, All serieses of MODEL C)
(Series 18 : BD03/12 to, BE03/09 to, BG23/03 to,
BG03/06 to, BD09/02 to, BE09/14 to, All serieses of
MODEL C)
PMCPA3 can be used only with Power MateH.

The ladder display can be stopped by manual operation or trigger of


signal.
The former ladder diagram display renews signal status every moment.
But by using this function, all the ladder diagram at the specified moment
can be checked.
The stop conditions as a trigger are specified by rising or falling edge
detection of the designated signal.
* Display of setting trigger
The setting address, condition and counter are displayed at the title
line.

MODE : ON : X0000.0 : 0 : 0001

COUNT: Trigger checking number (default 1)

POINT : Trigger checking point (default 0)


0 the top of the 1st level
1 after END1 execution
2 after END2 execution
3 after END3 execution

ADR : Trigger setting address

ON : Rising edge detection (TRGON) ,


OFF : Falling edge detection (TRGOFF)

* Setting form adr ; p1 ; p2 + [TRGON/TRGOFF] soft key

NOTE
; = EOB

adr (trigger address) ; p1 (trigger point) ; p2 (trigger checking number


(1 to 65535))

487
5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) PMC OPERATION (CRT/MDI) B61863E/14

* Because parameters are stored in the nonvolatile memory, they are


not lost even if the power is turned off.
When bit 2 of keep relay K18 is set to 1 after parameters for sampling
are specified, the trigger function automatically starts when the power
is turned on.
For this operation, press [TRIGER] soft key to bring the following menu.

SEARCH ADRESS TRIGER WINDOW

RET

TRGON TRGOFF START


(STOP)
NEXT

DUMP DPARA TRGSRC INIT


(NDPARA)

The function of the soft key is as follows :


(1) [TRGON] : Trigger is set on condition that the ladder status stops
when the status of designated signal is rising.
(2) [TRGOFF] : Trigger is set on condition that the ladder status stops
when the status of designated signal is falling.
(3) [START] : Change start/stop of trigger execution. While this
function is executing, TRG is blinking.
(4) [TRGSRC] : Search and blink the instruction stopped by trigger.
(5) [INIT] : The setting of trigger is initialized.

488
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

5.7 This function is used for dividing display of ladder diagram.


DIVIDING DISPLAY The maximum number of division is 6.
OF LADDER
LADDER *TITLE DATA REMARKS 32 BYTES * NET 00001-00004 MONIT RUN
DIAGRAM
*NET NO. 00001 00001
X1000.1 X1000.1 X1000.1 X1000.1 X1000.1 X1000.2 Y1000.0

*ESP SMBL X100.0 X100.0 X100.0

*NET NO. 00001 00001


X1000.0 X1000.1 X1000.2 Y1000.1

X1000.0 X1000.1 X1000.2 Y1000.2

ESP SMBL

ADDRESS DUMP
G0000 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .............
G0016 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .............
G0032 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .............
G0048 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .............
G0064 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .............

[DIVIDE ] [ CANCEL ] [ DELETE ] [SELECFT ] [ WIDTH ]

Fig. 5.7 Dividing display of ladder diagram

NOTE
For DUMP display, dump screen is displayed at the last part
of screen.

For this operation, press [WINDOW] soft key to bring the following
menu.

SEARCH ADRESS TRIGER WINDOW

RET

DIVIDE CANCEL DELETE SELECT WIDTH

The function of the soft key is as follows :


(1) [DIVIDE] : The screen will be divided.
The dividing display of ladder diagram can be
displayed for the designated NET number.
(NET number + [DIVIDE] )
(2) [CANCEL] : The dividing display of ladder diagram display ends.
(The screen returns to normal display.)
(3) [DELETE] : The screen division subject to operation is ended.
(4) [SELECT] : Change the screen subject to division operation.
The screen in operation is displayed by purple title
line, another screen is displayed by blue title line.
In monochrome CRT, the screen is displayed by
changing brightness.

489
5. PMC LADDER DIAGRAM DISPLAY
(PMCLAD) PMC OPERATION (CRT/MDI) B61863E/14

(5) [WIDTH] : Change the width of division by using [EXPAND] or


[SHRINK] soft key.
(6) [EXPAND] : The divided screen is expanded.
(7) [SHRINK] : The divided screen is shrank.

5.8
ONLINE EDIT : Can be used
: Option
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SC SC3 SC4 NB NB2

NOTE
: Can be used for the specific series of CNC
(Series 16 : B005/11 to, B105/08 to, B305/04 to, B009/03
to, All serieses of model C)
(Series 18 : BD03/12 to, BE03/09 to, BG23/03 to,
BG03/06, BD09/02 to, BE09/14 to, All serieses of model
C)
PMCSA3 is usable only with the Power MateH.

For the PMC MODEL PA, SA series and SB series, the editing card
(module) is necessary.
When bit 1 in the keep relay K17 is 1, this function is available and
[ONLEDT] soft key is displayed.
When the ladder program is executing, a part of the ladder program can
be changed.
D Change the type of contact (A contact, B contact)
D Change address of contact and coil.
D Change address parameter of functional instruction.
This function dont change the size.
(Cannot be Addition, deletion and changable data size)
When bit 3 of keep relay K18 is set to 1, the results of online editing are
automatically reflected on the ladder program for editing. When bit 3 of
keep relay K18 is set to 0, reflect the results of online editing on the ladder
program for editing, using the COPY function for the I/O screen.
Otherwise, the results of editing will be lost upon poweroff. For the
Moreover, when the CNC being used is the Series 15MODEL B, Series
16/18MODEL B/C, Series 21/210MODEL B, Series
16i/18i/21iMODEL A, or Power MateMODEL H, write to flash ROM.
How to store the results of editing

PMC other than NB Press the COPY key on the I/O screen.
NB Without DRAM Write the program into FROM.
With DRAM Press the COPY key on the I/O screen. Write the
program into FROM.

490
5. PMC LADDER DIAGRAM DISPLAY
B61863E/14 PMC OPERATION (CRT/MDI) (PMCLAD)

Operation
Press the [ONLEDT] soft key to enable the editing of a ladder
program. The editing procedure is the same as that using the
programmer function, described in Part III.

491
6. USER PMC SCREEN (PMCMDI) PMC OPERATION (CRT/MDI) B61863E/14

6 USER PMC SCREEN (PMCMDI)

492
B61863E/14 PMC OPERATION (CRT/MDI) 6. USER PMC SCREEN (PMCMDI)

6.1 This user PMC screen is open to users, and it employs function key
<CUSTOM>. It is applicable only when C language programming has
FOR THE FS16 been made. For details, see the PMCSC/SC3/SC4/NB programming
(PMCSC OR manual for C language (B61863E1).
PMCSC3)
NOTE
Pressing the <CUSTOM> key several times changes the
screen to the PMCMDI screen. Because the <CUSTOM>
key is also used to execute other functions.

6.2 This user PMC screen is open to users. To display this screen, display the
PMC screen and press the OTHERS key or call the plpcmdi function in
FOR THE FS15 C language. It is applicable only when the program has been written in
(PMCNB) C language. For details, see the PMCSC/SC3/SC4/NB programming
manual for C language (B61863E1).

493
III. PMC PROGRAMMER
(CRT/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) 1. GENERAL

1 GENERAL

This PMC programmer is used to set PMC system parameters and also
generate and execute sequence programs by using soft keys on the
CRT/MDI panel. For this operation, the PMC debugging RAM must be
mounted in the CNC in advance.
For the CRT/MDI panel keys, refer to PMC operation in PARTII, Chapter
1 and 2.
1) Setting and display of PMC system parameters (SYSPRM)
The following system parameters are available.
a) Selection of counter data types (BCD or binary)
b) Selection of division/nondivision of ladder program (only
PMCSC)
c) Parameters for executing C language programs (only for
PMCSC)
2) Editing of sequence programs (EDIT)
The following editing functions are provided.
a) Clear of memory
b) Title data input
c) Input, insert, search, and delete of sequence programs by ladder
diagram format
d) Input, insert, delete, and search of symbol data
e) Address setting to each module when I/0 unit is used
f) Message data input
3) Execution of sequence programs (RUN/STOP)
The following function is provided to execute sequence programs
a) Sequence program start and stop
4) To write, verify, and read of sequence programs and PMC data, and
to write and read of I/0 sequence programs, followings are provided.
a) Input/output of sequence programs to and from FANUC floppy
disk cassette
b) Input/output of sequence programs to and from debugging RAM
c) Input/output of sequence programs to and from ROM
d) Input/output of PMC parameter data to and from FANUC FD
cassette
5) Displaying the contents of memory for the user C program and
debugging the user C program (MONIT)
a) Displaying the GDT map of the user C program
b) Displaying memory information for the user C program
c) Debugging the user C program

497
1. GENERAL PMC OPERATION (CRT/MDI) B61863E/14

1.1 See Part IV, PMCNB6 Manupiration Screen for an explanation of the
FS15i PMCNB6.
ABOUT THE FS15i
PMCNB6
PROGRAMMER

1.2 See Part V, PMCSA1/SB7 Manupiration Screen for an explanation of


the FS16i/18i/21i PMCSA1/SB7.
ABOUT THE
FS16i/18i/21iB
PMCSA1/SB7
PROGRAMMER

498
2. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) CONNECTIONS

2 COMPONENT UNITS AND CONNECTIONS

This section describes only the 16/18MODEL A. For other models,


refer to the order list and the connection manual for each model.
The units required for generating a sequence program and connection
methods are described below.

499
2. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (CRT/MDI) B61863E/14

2.1 1) PCB and module for PMC


COMPONENT UNITS This is PCB and module for PMC. The type of board is as follows;
a) Series 16
i) PMCSB (Main CPU board)
D PMC control (A20B29000560, 0143)
D Debugging control (A20B29000530)
D PMC user ROM
D Editing module (A02B0120C160)
ii) PMCRC (Option 3 board)
D PMC control module
A20B29000390
(When using language programs, work RAM is required.)
A20B29000391
A20B29000143
b) Series 18
i) PMCSA1/SA2 (Main CPU board)
D PMC control module (A20B29000142) for PMCSA1
(A20B29000920) for PMCSA2
D Debugging RAM module (A20B29000530) Common
D PMC user ROM with
PMCSB
D Editing module (A02B01200160)

500
2. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) CONNECTIONS

Configuration of the main CPU board (Series 16)

Connector Connector
Drawing number : A16B22000900 name name Application

LED
PMCR
B CPU CRT JA1 CRT video signal
ROM MDI JA2 MDI keyboard
13 R2321 JD5A RS232C serial port
R2322 JD5B RS232C serial port
MPG JA3 Manual pulse generator
Module IOLINK JD1A FANUC I/O LINK
SPDL1 JA7A Serial spindle
1 2 3 4 5 6 7 8 AOUT1 JA8A Analog output
APCBAT JA4A APC battery

AMP1 JV1 1st axis servo amplifier


AMP2 JV2 2nd axis servo amplifier
AMP3 JV3 3rd axis servo amplifier
AMP4 JV4 4th axis servo amplifier
ENC1 JF1 1st axis pulse coder
CNA ENC2 JF2 2nd axis pulse coder
ENC3 JF3 3rd axis pulse coder
Fbus
backplane 9 10 11 12 ENC4 JF4 4th axis pulse coder
connector SCALE1 JF21 1st axis scale
SERVO SCALE2 JF22 2nd axis scale
ROM
SCALE3 JF23 3rd axis scale
SCALE4 JF24 4th axis scale

Fig. 2.1 (a) Layout of parts on Main CPU board (Series 16)

Table 2.1 (a) Modules of Main CPU board (Series 16)

No. Module Drawing number Functional outline


1 ROM module A20B29000290 to 0293 ROM for CAP I or macros
2 ROM module A20B29000290 to 0292 ROM for the CNC system
3 SRAM module A20B29000530 RAM for debugging the PMCSB
4 SRAM module A20B29000530,0531 RAM for part programs and parameters
A20B29000540,0541
5 PMC control module A20B29000560 (For PMCSB) PMC operation control
A20B29000143 (For PMCSC)
6 CRT control module A20B29000150 to 0152 CRT display control
7 System control module A20B29000101 to 0103 Clear, battery backup, spindle control, etc.
8 I/O interface module A20B29000110 MDI, MPG, RS232C, etc.
9 Servo control module A20B29000160 Digital servo control of the 3rd and 4th axes
10 Servo control module A20B29000160 Digital servo control of the 1st and 2nd axes
11 Servo interface module A20B29000370,0380 3rd/4th axis amplifier/pulse coder interface
12 Servo interface module A20B29000370,0380 1st/2nd axis amplifier/pulse coder interface

501
2. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (CRT/MDI) B61863E/14

Configuration of the option 3 board (Series 16)

Drawing number : A16B22000940 (PMCRC+CAP II)


A16B22000941 (only for PMCRC) Connector Connector
A16B22000943 (only for CAP II) Name Name Application

LED

Module

1 2 3 4 5 6

IOLINK JD1A2 FANUC I/O LINK

CNA
7 8 9
Fbus
backplane CPU
connector

Fig. 2.1 (b) Layout of Parts on Option 3 Board (Series 16)

Table 2.1 (b) Modules of Option 3 Board (Series 16)

No. Module Drawing number Functional outline


1 ROM module A20B29000290 to 0293 User ROM for PMCSC (Mount the RAM module
during debugging.)
2 ROM module A20B29000292 System ROM for PMCSC
3 DRAM module A20B29000553 Work RAM for PMCSC
4 PMC control module A20B29000560 PMC operation control and I/O Link control
5 PMC CPU module A20B29000390 For ladder capacity 24000 steps or C language
A20B29000391 Other than the above

502
2. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) CONNECTIONS

Configuration of the Main CPU Board (Series 18)


Connector Connector
Drawing number : A16B22010080 Name No. Description

LED

PMCRA1/RA2 CRT JA1 CRT video signal


ROM MDI JA2 MDI keyboard
16 R2321 JD5A RS232C serial port
R2322 JD5B RS232C serial port
MPG JA3 Manual pulse generator
Module IOLINK JD1A FANUC I/O LINK
SPDL1 JA7A Serial spindle
1 2 3 4 5 6 7 8 AOUT1 JA8A Analog output
APCBAT JA4A Battery for use with the APC

AMP1 JV1 Axis 1 servo amplifier


AMP2 JV2 Axis 2 servo amplifier
AMP3 JV3 Axis 3 servo amplifier
AMP4 JV4 Axis 4 servo amplifier
ENC1 JF1 Axis 1 pulse coder
CNA ENC2 JF2 Axis 2 pulse coder
ENC3 JF3 Axis 3 pulse coder
FBUS ENC4 JF4 Axis 4 pulse coder
back plane 9 10 11 12 13 14 15
SCALE1 JF21 Axis 1 scale
connector
SCALE2 JF22 Axis 2 scale
SCALE3 JF23 Axis 3 scale
SCALE4 JF24 Axis 4 scale

Fig. 2.1 (c) Parts layout for the main CPU board (Series 18)

Table 2.1 (c) Module list for the main CPU board (Series 18)

No. Module name Drawing no. Function outline


1 ROM module A20B29000290 to 0293 ROM for macros or CAP 1
2 ROM module A20B29000290 to 0292 ROM for the CNC system
3 SRAM module A20B29000530 RAM for PMCSA1/SA2 debug
4 SRAM module A20B29000530,0531 RAM for parameters and tape memory
A20B29000540,0541
5 PMC control module A20B29000142 (PMCSA1) PMC operation control
A20B29000920 (PMCSA2)
6 Main CPU module A20B29000930 FS18 Main processor
7 System control module A20B29000900 to 0902 Clear, battery backup, spindle control, servo/graphics
software flash ROM
8 I/O interface module A20B29000110 MDI, MPG, RS232C
9 Graphics control module A20B29000310 Graphics display control
10 Graphics CPU module A20B29000590 Graphics control CPU
11 CRT control module A20B29000154 to 0156 CRT display control
12 Servo control module A20B29000160 Digital servo control for axes 3 and 4
13 Servo control module A20B29000160 Digital servo control for axes 1 and 2
14 Servo interface module A20B29000380 Amplifier, pulse coder, and interface for axes 3 and 4
15 Servo interface module A20B29000380 Amplifier, pulse coder, and interface for axes 1 and 2

503
2. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (CRT/MDI) B61863E/14

2) Debugging RAM
This is used for debugging sequence programs. Since this debugging
RAM memory is backed up by the battery, the memory data contents
are not erased even when turning off the power supply.

CAUTION
If a RAM parity error occurs or when power is first turned on
after installation, the RAM for debugging must be cleared.

(Procedure)
Turn on power to the CNC while pressing the X and O keys
simultaneously. The contents of the RAM for debugging are then
cleared.
3) Editing module
This is a builtin programmer for PMCSA1, PMCSA2, SA3,
PMCSB, PMCSB2, or SB3 that enables editing sequence
programs.
4) ROM
After debugging, write a sequence program into ROM.
5) ROM WRITER
This unit is used for writing or reading out a sequence program to
ROM.
6) Offline programmer
This is used to transfer a sequence program.
By connecting the Offline programmer to PMCSA1, SA2, SB,
SB2, SB3, SC, or SC3, the storage of sequence programs in the
floppy, and the output of a sequence program into printer can be done.

504
2. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) CONNECTIONS

2.2 (1) Connecting the debugging RAM module


CONNECTING a) PMCSB, SB2 and SB3 : Connect the module to portion 3
shown in Fig. 2.1 (a).
COMPONENT UNITS
b) PMCSC and PMCSC3 : Connect the module to portion 1
shown in Fig. 2.1 (b).
c) PMCSA1, SA2 and SA3 : Connect the module to portion 3
shown in Fig. 2.1 (c).
(2) Connecting the editing module for PMCSA1, SA2, SA3, SB,
SB2 and SB3 Connect the module to portion 3 shown in Fig. 2.1
(a).
(3) Connecting ROM
a) PMCSB, SB2 and SB3 : Connect EPROM to portion 13
shown in Fig. 2.1 (a).
b) PMCSC and PMCSC3 : Connect the ROM module to
portion 1 shown in Fig. 2.1 (b).
c) PMCSA1, SA2 and SA3 : Connect EPROM to portion 16
shown in Fig. 2.1 (c).
: Enabled
: Enabled depending on the option
: Disabled
SA1 SA2 SA3 SB SB2 SB3 SC SC3
RAM module
Editing module
EPROM
ROM module

NOTE
1 When 24,000 optional PMCSB2 and PMCSB3 ladder
steps are available, 256K bytes of the ROM module can be
used. In this case, connect the ROM module to portion 3
shown in Fig. 2.1 (a).
2 Either a RAM module, editing module, or ROM module can
be connected to each board of PMCSA1, SA2, SA3,
SB, SB2 and SB3.
3 Either a RAM module or ROM module can be connected to
each board of PMCSC and PMCSC3.

(4) Connecting the offline programmer


Connect the offline programmer to the reader/punch interface on the
CNC. There are several connectors for the reader/punch interface on
the CNC. The connector to be used is specified during I/O processing
for the PMC. For details, see Section 7.

505
3. SELECTION OF PROGRAMMER
MENUS BY SOFTKEYS PMC PROGRAMMER (CRT/MDI) B61863E/14

3 SELECTION OF PROGRAMMER MENUS BY SOFTKEYS

To operate the PMC programmer, set bit 1 in K17 of the keep relay area
for PMC parameters to 1, enabling the programmer basic menu to be
displayed. To display the programmer basic menu, press <SYSTEM>
and [PMC] soft key on the MDI keyboard then, press the [NEXT] key.
The programmer basic menu is displayed at the lower part of the CRT
screen to signify the keys as shown in the following figure.
(1) Programmer basic menu
The programmer basic menu and PMC basic menu are selected to
each other alternately by pressing the [NEXT] key. For the PMC basic
menu and operation, see PMC operation in Chapter II.

NOTE
In the following description, the relation between soft keys
and menus is described based on 9inch CRT/MDI panel.
The 14inch CRT/MDI panel is different from the 9inch
CRT/MDI panel about the number of soft keys. Five soft
keys are mounted on the 9inch CRT/MDI panel, while ten
soft keys are mounted on the 14inch CRT/MDI panel.

RESET key
HELP key Address/numeric keys

Edit keys

Cancel key

INPUT keys

SHIFT key Cursor control keys


Power on/off buttom Soft keys Function keys
Page keys

506
3. SELECTION OF PROGRAMMER
B61863E/14 PMC PROGRAMMER (CRT/MDI) MENUS BY SOFTKEYS

(2) Relation between programmer menus and soft keys


The relation between programmer menus and soft keys are different
according to each function as shown in the following figure. These
menus are selected by pressing related keys. For the menu contents,
see the description given later. Refer to this figure for operation.

PMCLAD PMCDGN PMCPRM

Chapter III.6 Chapter III.5 Chapter III.7 Chapter III.4 NEXT

RUN or STOP EDIT I/O SYSPRM MONIT

RET RET RET RET

TITLE DBGLAD**

LADDER

SYMBOL GDT*

MESAGE USRMEM*

DEBUG*

NEXT

MODULE

CROSS

CLEAR

NOTE
1 Mark * is valid for PMCSC/SC3/SC4/NB function.
2 Mark ** is valid for PMCSA3/SB3 with Editing module or
PMCSC/SC3 function.

507
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
(SYSPRM) PMC PROGRAMMER (CRT/MDI) B61863E/14

4 SPECIFYING AND DISPLAYING SYSTEM PARAMETERS


(SYSPRM)

Display the system parameter screen by pressing soft key [SYSPRM] on


the basic programmer menu. Move the cursor to necessary system
parameters and specify them according to the menu displayed on the
screen. When this function is selected, if the sequence program is in
operation, the PMC management software automatically stops this
function.
(1) COUNTER DATA Specifies whether the counter value is used in binary or BCD by
TYPE functional instruction CTR.

CAUTION
After changing a counter data type, set up the counter value
again.

(2) LADDER EXEC Specifies the increment or decrement of processing time of the 1st and 2nd
(valid for PMC level parts of the ladder program in the range of 1% to 150%. This
SC/SC3/SC4/NB/NB2) increases or decreases the scanning time of the ladder program. This
parameter influences the processing time of the 3rd level part of the ladder
program and the language program.
If 100% is specified, the time of 5 ms for an 8 ms cycle is used to process
the 1st and 2nd level parts of the ladder program. The remaining 3 ms is
used to process the 3rd level part of the ladder program, language
program, and PMC screen display.
If 120% is specified, the time of 6 ms is used to process the 1st and 2nd
level parts of the ladder program. This reduces the scanning time of the
ladder program, thus enabling the ladder program to be executed at high
speed. Note that the processing time required for the 3rd level part of the
ladder program, language program, and PMC screen display is
substantially reduced. If the undivided system is specified too, this
parameter is validated.
If a value less than 40% is specified, 40% is assumed. If a value greater than
120% is specified, 120% is assumed.
The processing time of the 1st and 2nd parts of the ladder program is
obtained by the following formula:
Processing time of the 1st and
(LADDER EXEC)
2nd parts of the ladder program=5 msec
100
The processing time of the 3rd level part of the ladder program, language
program, and PMC screen display
= 8 ms (processing time of the 1st and 2nd level parts of the ladder
program)

508
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
B61863E/14 PMC PROGRAMMER (CRT/MDI) (SYSPRM)

100% 120%
8 msec 8 msec
1st and 2nd level 1st and 2nd level
parts of the ladder parts of the ladder
program program
5 ms
6 ms

Others Others
3 ms
2 ms

(3) LANGUAGE EXEC Specifies the division ratio of execution for PMC screen display and
RATIO (valid for language program.
PMCSC/SC3/SC4/NB/ (0 to 99%)
NB2) Since the execution priority of PMC screen display is higher than
language program tasks, it is usually hard for the tasks to execute
processing while displaying PMC screen. Then this parameter can be
used to set the division ratio for each. Cyclic processing of language
program is therefore possible during PMC screen display. Only language
program tasks are running if PMC screen is not displayed.
(4) IGNORE DIVID CODE Specifies whether the ladder program is executed in the divided system
(valid for PMCSB (IGNORE DIVID CODE = NO) or in the undivided system.
andRC)

(5) LANGUAGE ORIGIN Specifies the first address of the link control statement data in the
(valid for PMCSC/ language program.
SC3/SC4/NB/NB2) Be sure to specify 0 when the language program is not stored.
LANGUAGE AREA and SIZE indicate the area where the language
program is stored. Store the language program in the specified area.
When the language program is stored, the Language Origin is
automatically set by moving the cursor to this item and pressing
[ORIGIN] soft key.
(6) MAX LADDER Specify the maximum size of the ladder program. This parameter can be
AREA SIZE used to increase or decrease the size of the work area used by language
(valid for PMCSC/ programs. The setting of the parameter takes effect only after power is
SC3/NB) turned on. When the setting is to be changed, therefore, power must be
turned off.
For details, see the FANUC PMCMODEL SC/SC3/SC4/NB
PROGRAMMING MANUAL C LANGUAGE (B61863E1). The
default is the size in kilobytes resulting from conversion of the ladder step
option.
(7) FS0 OPERATOR Specifies whether the Series 0 operators panel is connected. When YES
PANEL is selected, specify the actual addresses of DI and DO connected to the
operators panel, the address of the key image transferred from the
operators panel, and the address of the LED image to be transferred to
the operators panel.
(a) KEY DI ADDRESS
Specify a PMC address representing the first address of the external
DI actually connected (X0 to X127, X200 to X327, or X1000 to
X1019).

509
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
(SYSPRM) PMC PROGRAMMER (CRT/MDI) B61863E/14

(b) LED DO ADDRESS


Specify a PMC address representing the first address of the external
DO actually connected (Y0 to Y127, Y200 to Y327, or Y1000 to
Y1014).
(c) KEY BIT IMAGE ADDRESS
Specify a PMC address representing the first address of the key
image to be referenced by the user program. Usually specify an
arbitrary internal relay (R) area.
(d) LED BIT IMAGE ADDRESS
Specify a PMC address representing the first address of the key
image to be generated by the user program. Usually specify an
arbitrary internal relay (R) area.
(8) STEP SEQUENCE When creating new programs with the builtin editing function, set this
parameter first, then execute CLEAR ALL or perform clear operation
(turn on power while holding down X and O) at power on.
When selecting the step sequence method: STEP SEQUENCE = YES
When selecting the ladder method: STEP SEQUENCE = NO
(9) I/O Link 2 CHANNEL When creating a new program for assignment of the I/O Link channel 2
(PMCSB6 for Series with the builtin editing function, set this parameter first, then execute
16i/18i/21i/160i/180i/ CLEAR ALL or perform clear operation (turn on power while holding
210i) down X and O) at power on.
When assigning the I/O Link channel 2
(Note1): I/O LINK 2 CHANNEL = YES
When assigning only the I/O Link channel 1
(Note2): I/O LINK 2 CHANNEL = NO

510
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
B61863E/14 PMC PROGRAMMER (CRT/MDI) (SYSPRM)

NOTE
1. PMC model for FANUC LADDERII /Ladder Editing
Package is PMCSB6 (IO2) or PMCSB6 (STEP SEQ,
IO2)(case of using the step sequence method).
2. PMC model of FANUC LADDERII /Ladder Editing Package
is PMCSB6 or PMCSB6 (STEP SEQ)(case of using the
step sequence method).
3. When assigning the I/O Link channel 2, capacity of the
memory used by system increases maximum 5376 bytes
compared to the case of not assigning the I/O Link channel
2. Please adjust the volume of Ladder, symbol, comment,
and message, in order to reduce the sequence program
size to fit for the ROM capacity.
4. FANUC LADDERII /Ladder Editing Package is used when
converting sequence program for 1 channel (PMCSB6 or
PMCSB6 (STEP SEQ)) into sequence program for
expansion (PMCSB6 (IO2) or PMCSB6 (STEP SEQ,
IO2)). Please refer to FANUC LADDERII OPERATORS
MANUAL (B66184EN/02) APPENDIX 3.3 Convert The
PMC Type of Sequence Program and FANUC OPEN CNC
LADDER EDITING PACKAGE OPERATORS MANUAL
(B62884EN/016) APPENDIX D.3 CONVERT THE PMC
TYPE OF SEQUENCE PROGRAM.

PMC SYSTEM PARAMETER


COUNTER DATA TYPE = BINARY/BCD

FS0 OPERATOR PANEL = YES/NO

KEY DI ADDRESS = X100

LED DO ADDRESS = Y100

KEY BIT IMAGE ADDRESS = R900

LED BIT IMAGE ADDRESS = R910


>

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. 4(a) PMCSA series system parameter screen

511
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
(SYSPRM) PMC PROGRAMMER (CRT/MDI) B61863E/14

PMC SYSTEM PARAMETER

COUNTER DATA TYPE = BINARY/BCD

IGNORE DIVIDE CODE = NO/YES

>

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. 4(b) PMCSB series system parameter screen (1st page)

PMC SYSTEM PARAMETER MONIT STOP

COUNTER DATA TYPE = BINARY /BCD

LADDER EXEC = 100% (1150)

LANGUAGE EXEC RATIO = 50% (099)

IGNORE DIVIDE CODE = NO/YES

LANGUAGE ORIGIN = 841000H


(LANGUAGE AREA = 840000H,SIZE = 768KB)
MAX LADDER AREA SIZE = 90KB (196)

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. 4(c) PMC SC, SC3 or NB system parameter screen (1st page)

512
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
B61863E/14 PMC PROGRAMMER (CRT/MDI) (SYSPRM)

PMC SYSTEM PARAMETER (1/2) MONIT STOP

COUNTER DATA TYPE = BINARY/BCD

IGNORE DIVIDE CODE = YES/NO

>

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. 4(d) PMCSB4/SB6/SC4 system parameter screen (1st page)

PMC SYSTEM PARAMETER (1/2) MONIT STOP

COUNTER DATA TYPE = BINARY/BCD

LADDER EXEC = % (1150)

LANGUAGE EXEC RATIO = % (099)

LANGUAGE ORIGIN = H
(LANGUAGE AREA = H, SIZE = KB)

STEP SEQUENCE = YES/NO


>

[ BINARY ] [ BCD ] [ ] [ ] [ ]

Fig. 4(e) PMCSC4/NB2 system parameter screen (1 st page)

Press the [NEXT] key to select the following screen for PMCSB series,
PMCSC series, and PMCNB :

513
4. SPECIFYING AND DISPLAYING
SYSTEM PARAMETERS
(SYSPRM) PMC PROGRAMMER (CRT/MDI) B61863E/14

PMC SYSTEM PARAMETER (2/2) MONIT STOP

FS0 OPERATOR PANEL = YES/NO

KEY DI ADDRESS = X100

LED DO ADDRESS = Y100

KEY BIT IMAGE ADDRESS = R900

LED BIT IMAGE ADDRESS = R910

>

[ YES ] [ NO ] [ ] [ ] [ ]

Fig. 4(f) PMCSB series, PMCSC series, or PMCNB system parameter


screen (2nd page)

PMC SYSTEM PARAMETER (1/2) MONIT STOP

COUNTER DATA TYPE = BINARY/BCD

STEP SEQUENCE = YES/NO

I/O LINK 2 CHANNEL = YES/NO

>

[ YES ] [ NO ] [ ] [ ] [ ]

Fig. 4(g) PMCSB6 system parameter screen (1st page)

514
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5 EDITING OF SEQUENCE PROGRAM (EDIT)

Press soft key [EDIT] of the programmer basic menu to bring the
following menu. For setting the CLEAR or I/O unit address, press the
[NEXT] key to bring another menu.
Each menu of [EDIT] can be selected by EDIT key, or menu of other EDIT
can be selected by each EDIT menu. When this function is selected, if the
sequence program is in operation, the PMC management software
automatically stops this function.
(Operation)
Perform each operation by pressing necessary menu soft keys. Press
[RETURN] key for resetting to the programmer basic menu.

RUN EDIT I/O SYSPRM MONIT


(STOP)
RET

TITLE LADDER SYMBOL MESAGE

III.5.1 III.5.2 III.5.4 III.5.5 NEXT

MODULE CROSS CLEAR

III.5.3 III.5.7 III.5.6

PMC EDITION MENU MONIT STOP

SELECT ONE OF FOLLOWING SOFT KEYS

TITLE : TITLE DATA


LADDER : LADDER DIAGRAM
SYMBOL : SYMBOL & COMMENT DATA
MESAGE : MESSAGE DATA
MODULE : I/O MODULE DATA
CLEAR : CLEAR DATA
CROSS : CROSS REFERENCE

[TITLE ] [LADDER] [MESAGE] [ ] [ ]

[MODULE] [ ] [CROSS ] [ ] [CLEAR ]

Fig. 5 Editing basic menu

515
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.1 The title data refers to the title of the sequence program created by the
machine tool builder. The data consists of the following ten items:
SPECIFYING AND
DISPLAYING TITLE D Machine tool builder name (32 characters)
DATA (TITLE) D Machine tool name (32 characters)
D NC and PMC types (32 characters)
D Sequence program number (16 characters)
D Version (4 characters)
D Sequence program drawing number (32 characters)
D Date of sequence program creation (16 characters)
D Sequence program programmer (32 characters)
D ROM programmer (32 characters)
D Comment (32 characters)
The title for the 9 CRT consists of three screens. The screens are changed
by pressing <PAGE> or <PAGE> .

RUN EDIT I/O SYSPRM MONIT

RETURN

TITLE LADDER SYMBOL MESAGE

RETURN

INSERT DELETE LADDER C LANG

NOTE
When a C language board is installed in the Series 16i/18i,
the title data for C can be edited. With the soft key
[LADDER], the display can be switched to the ladder title
data. With the soft key [C LANG], the display can be
switched to the C title data.

5.1.1 (1) Move the cursor to the desired title data item. Use the cursor keys [],
[], [], [] to move the cursor.
Entering Title Data
(2) Press the address key and numeric keys to enter the title data, and
press the <INPUT> key.

5.1.2 (1) Move the cursor to the desired title data item. Use the cursor keys [],
[], [], [] to move the cursor.
Deleting Title Data
(2) After keying in the title data by pressing the desired address keys and
numeric keys, press the <INPUT> key.

516
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.1.3 When the length of the cursor is the same as the maximum number of
Editing Character characters, pressing the [INSERT] key enables the operator to edit
character strings. Then, the length of the cursor is changed to that of one
Strings of Title Data character.
(1) Move the cursor to the desired insertion position with the cursor keys
and enter a character string. Then, the character string is inserted.
(2) Pressing the [DELETE] key deletes the character at the cursor.

PMC TITLE DATA #1 MONIT RUN

PMC PROGRAM NO. : 1234


EDITION NO. : 12

PMC CONTROL PROGRAM


SERIES : 4061 EDITION : 01

MEMORY USED : 44.0KB


LADDER : 32.0KB
SYMBOL : 10.2KB
MESSAGE : 01.8KB
SCAN TIME : 048 MSEC

[INSERT] [DELETE] [ ] [ ] [ ]

Fig. 5.1.3 (a) Title edit screen 1

PMC TITLE DATA #2 MONIT RUN

MACHINE TOOL BUILDER NAME :


f f

MACHINE TOOL NAME :


f f

CNC & PMC TYPE NAME :


f f

PROGRAM DRAWING NO. :


f f

[INSERT] [DELETE] [ ] [ ] [ ]

Fig. 5.1.3 (b) Title edit screen 2

517
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

PMC TITLE DATA #3 MONIT RUN

DATE OF PROGRAMING :
f f

PROGRAM DESIGNED BY :
f f

ROM WRITTEN BY :
f f

REMARKS :
f f

[INSERT] [DELETE] [ ] [ ] [ ]

Fig. 5.1.3 (c) Title edit screen 3

518
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.2 Input, insert, delete, and search a sequence program as described below.
The relation between these functions and soft keys is as shown below.
SEQUENCE
PROGRAM
GENERATION RUN EDIT I/O SYSPRM MONIT
(STOP)
(LADDER)
RET

TITLE LADDER SYMBOL MESAGE

RET

yj jy yj jy j yyj FUNCTN

NEXT

COMAND

NEXT

y(S)yj
III 5.3 y(R)yj III 5.7

RET

INSNET DELNET INSERT ADRESS SEARCH

NEXT

COPY MOVE CHANGE

Fig. 5.2 Sequence program generation softkeys

NOTE
y(S)yjand y(R)yj are valid for PMCPA3, SA3,
SB3, SB4, SC3, SC4, and NB.

Each of EDIT LADDER software functional instruction keys can be


selected by the [COMAND] key. Type in one of the following character
strings and press software key [COMAND]. The character string within
parentheses [ ] can be omitted. n after the character string indicates
that a value can be input. For example, if the [COMMAND] key is pressed
after D2 is typed in, the operation can be performed in the same manner
when the <DELNET> key is pressed after 2 is typed in.

I[NSERT] D[ELNET][n] n:value


A[DRESS] SY[MBOL]
S[EARCH] C[OPY][n]
M[OVE][n]
Generate and search a program by pressing soft keys of the above menu.

519
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

NOTE
Soft keys ( [ ] or [ ])([ ] or [ ] ) are used for producing
or deleting an upper left vertical line or upper right vertical line on
the ladder diagram. The solid line display vertical line indicates the
production, while the dotted line display vertical line shows the
deletion. Which one is available is determined by the ladder
diagrams and cursor positions.

When the cursor is set to this position, the upper right vertical line is not produced yet,
and the menu becomes [ ]

When the cursor is set to this position, the upper right vertical line is already produced,
and the menu becomes [ ]

5.2.1 Press soft key [LADDER] for inputting a sequence program. The soft key
Sequence Program menu changes as shown in Fig. 5.2.
Input If a sequence program is not input yet, the right and left vertical lines only
of the ladder diagram are displayed on CRT/MDI.
Start inputting a program with this screen condition. If a previous
program remains unerased from RAM module for debug, clear it
according to the instruction in 5.6 before starting the program input.
Input a ladder diagram by moving the cursor to the desired input position
by using the cursor key.
The following description shows an example of the input of a program of
the basic instruction and a program of the functional instruction.
(1) In case of basic instruction program input;

R0.1 R10.2 R1.7 R20.2

X2.4

The contacts and coils inputtable in one line are as specified below.
9inch CRT/MDI
10inch CRT/MDI 7 contact + relay coil
14inch CRT/MDI
They cannot be input into one line more than specified. If they exceed the specified
range, provide a dummy relay coil halfway.

520
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

1 Press soft key [ ] after moving the cursor to the start


position.
Symbol [ ] is input to the cursor position and
HORIZONTAL LINE ILLEGAL is displayed at the lower
right part of the CRT screen. This is a caution message to
show that the ladder diagram horizontal line is not entered
yet. Input address and bit data next.
2 Press <INPUT> key after inputting R0.1 by using address
key and numeric keys. The address is set on the contact, and
cursor shifts rightward.
3 Input A contact with address R10.2 by the above method 1,
2.
(Note) The order of processes 1 and 2 are interchangeable.
4 Input B contact R1.7
Press soft key [ ], input address R1.7, and then, press
<INPUT> key.
The address is set on the B contact and the cursor shifts
rightward.
5 Press soft key [ ]with the cursor kept as it is.
A right horizontal line is automatically drawn, and a relay
coil symbol is entered near the right vertical line.
6 Press <INPUT> key after inputting.
The cursor automatically shifts to the input start position of
the next line.
7 Input the OR condition next,
Press soft key [ ], input address X2.4 and then, press
INPUT key. The address is set on the B contact and the cursor
shifts rightward.
8 Press NEXT key, since the soft key of the right horizontal line
of OR is necessary.
9 Press soft key [ ] to input a horizontal line.
When inputting the horizontal bar key ([ ], [ ]), key
in a numerical value and press this bar key, and then the
horizontal line for the frequency will be drawn. However, this
horizontal line will not be drawn over the LINE.
10 Press soft key [ ], and input necessary upper right vertical
line or OR.

521
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

CAUTION
1 When the ladder program displayed on the screen is incomplete (when, for example, addresses
have not been entered) or erroneous, the screen cannot be scrolled even when a page key is
pressed. Before attempting to scroll the screen, therefore, ensure that the ladder program is
complete and errorfree.
However, be careful since the program net (a block corresponding to a range from RD to WRT
Instruction) containing an error is deleted when the screen is switched to an CNC screen.
2 7 contacts + a coil are specified to be inputtable per line from CRT/MDI, any more contacts
exceeding the specified value are not inputtable.
However, this limitation is not applicable to mnemonic sequence programs generated by Offline
programmer. When a sequence program, transferred from the offline programmer to the PMC,
exceeds the length which can be displayed on a single line, the program is displayed using two
or more lines, linked with a continuation symbol. This continuation symbol is not erasable
usually, except when all programs from RD instruction to WRT instruction are erased.
3 If the power is turned off while a ladder program is being displayed in edit mode, that ladder
program will be lost. Always save the program and exit the editing screen before turning off
the power.
4 The termination processing of the ladder (JMP, COM, and other processing) is done when the
EDIT screen is switched to another screen by pressing RET key, it takes several tens second
until the screen is switched completely, if the ladder is large.
5 In the Series 15MODEL B, Series 16/18MODEL B/C, and Series 16i/18i/21iMODEL A CNC
that use Flash Memory, the program is not automatically written into Flash Memory once editing
ends. After editing, perform the processing for writing to Flash Memory (see 7.3.3, FROM in
Chapter 7 of Part III). Otherwise, the editing results will be lost when the power is turned off.
6 When the user presses the RET key to switch from the edit screen to another screen, the
parameters of functional instructions TMR, TMRB, CRT, DIFU, and DIFD are checked for a
parameter number range error and duplicate parameter number in the ladder termination
processing. If a range error is found, the editing cannot be terminated. If the use of a duplicate
parameter number is found, the guidance message is displayed.

(2) In case of functional instruction program input;


For inputting a functional instruction, press [FUNCTN] soft key, and
then, input instruction symbol of the functional Instruction and SUB
number.
A function command can be input by pressing the [FUNCTN] key
after keying the Function Command No. When pressing the
[FUNCTN] key without keying in the Function Command No., the
function command table is displayed. Key in Function Command No.
and press [INPUT] key.
If you dont keep the instruction symbol and SUB number into mind,
you can display a functional instruction table covering the
correspondence between instruction on symbols and SUB numbers
automatically by inputting a wrong instruction symbol or a wrong SUB
number and then pressing the soft key [FUNCTN] key or by pressing
soft key [FUNCTN] key only without inputting any other key.
If an aimed functional instruction is not found in the displayed
functional instruction table, press [NEXT] key or [PAGE] key to
brings its subsequent table.
Press [FUNCTN] key when resetting the functional instruction table
to the original ladder diagram.

522
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

Functional
instruction table

When a wrong functional


instruction is entered or
[FUNCTN] key only is
pressed;
FUNCTN

[NEXT] key (to display the subsequent


functional instruction table)

Functional instruction generation soft key


(Press this key again when resetting the functional instruction
table to the original ladder diagram)

NOTE
If the system is left undone without inputting any data after
pressing soft key [FUNCTN], the other soft keys are not
employable. In such a case, press [FUNCTN] key again.

DECB

SUB 25 Format Code Specifi Output


specifi- data cation data
cation address number address

Input functional instruction parameters in the vertical direction


as shown in the following figure when inputting functional
instructions from CRT/MDI panel.

DECB
SUB 25 CRT/MDI
ACT Format specification

Code data address



Specification number
Output data address

1 Input a control condition.


Press soft key [ ], input the address and bit data, and
then, press <INPUT> key. The cursor shifts rightward.
2 Input an instruction.
Press soft key [FUNCTN], input SUB number 25, and then,
press <INPUT> key. A functional instruction diagram
appears as shown in the above figure.
3 Input an instruction parameter.
Input the first parameter, format specification, and then, press
<INPUT> key. The cursor automatically lowers downward.
Input three residual parameters in order.

523
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.2.2 The method of altering a generated sequence program is the same as


Alteration of Sequence described in 5.2.1. Move the cursor to the program part to be altered and
input change data.
Programs

5.2.3
Insert of Sequence
Program
yj jy yj jy j yyj FUNCTN

INSNET DELNET ADRESS SEARCH

RETURN

INSNET INSLIN INSELM

A sequence program is inserted in four ways on the ladder diagram as


described below.
(1) To insert a relay contacts in the horizontal direction.

Simple horizontal insert

Insert

Move the cursor to the position where a sequence program is to be


inserted, and input the program by the method specified in 5.2.1.
When a vertical line is to be deleted
for the insert operation ;

Insert



Cursor

1 Set the cursor to the above position.


2 Press soft key [ ] for erasing the upper left vertical line. The
upper left vertical line to the cursor disappears.
3 Press soft key [ ] to produce a upper right vertical line to
the cursor, then, press soft key [ ]. Both vertical line
and horizontal line are produced.

524
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

4 Shift the cursor to a line of contact insert position.


5 Press soft key [ ] to add contacts.
(2) For inserting vertical line;

Insert

For inserting a vertical line as shown in the above figure, the inserting
area is required, correspondingly. In order to produce the area, shift
the entire part after the part to be inserted by one line by moving the
cursor to the ladder diagram within the dotted line range (an optional
part is allowable) and then pressing soft key [INSNET] (see Fig. 5.2).
The lower ladder diagram shifts downward by one line, each time the
[INSNET] key is pressed to produce the area to which a line is to be
inserted.
If a surplus insert area remains unused after the insert processing ends
(if an area corresponding to 3 lines has been reserved when two lines
have been inserted, for example), the area may be left as it is. No
problem arises.
1 Move the cursor to the ladder diagram bounded by a dotted
line.
2 Press soft key [INSNET].
The lower ladder diagram shifts downward by one line.
3 Pressing [INSNET] key without keying in numeric values
will cause one line to be inserted.
4 Pressing [INSNET] key with keying in numeric values will
cause the line to be inserted the number of numeric values
input.
5 After setting the cursor to a position where the contacts is to
be inserted, press soft key [ ]. After setting address data,
press [INPUT] key. The cursor shifts rightward.
6 Press soft key [ ] to produce an OR circuit.
(3) Inserting the 1 NET sequence program lines
Space lines are inserted one by one.
1 Type in the number of lines to be inserted and press the
[INSLIN] key. The lines corresponding to the input number
are inserted. (If the number of lines to be inserted is not typed
in but the [INSLIN] key is pressed, one line is inserted.)

525
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

Cursor

If the [INSLIN] key is pressed when the cursor is in the


position specified as shown in the above figure on the left, the
line is inserted as shown in the above figure on the right.
(4) Inserting the 1 NET sequence program elements
Elements can be inserted one by one.
1 Type in the number of elements to be inserted and press the
[INSELM] key. The elements corresponding to the input
number are inserted. If the number of elements prefixed by
character A is typed in and the [INSELM] key is pressed,
the elements are inserted after the cursor.
(If the number of elements to be inserted is not typed in but
the [INSELM] key is pressed, one element is inserted.)

Cursor

When the [INSELM] key is pressed when the cursor is


positioned as shown in the above figure on the left, the
element is inserted as shown in the above figure on the right.

Cursor

If A is typed in when the cursor is positioned as shown in


the above figure on the left and the [INSELEM] key is
pressed, the element is inserted as shown in the above figure
on the right.

526
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.2.4 (1) Delete a part of sequence program by using three kinds of soft keys
after setting the cursor to the portion from which the sequence
Delete of Sequence program is to be deleted.
Program [ ] : Delete of horizontal lines, relay contacts, relay coils, etc.
[ ] : Delete of upper left vertical line to the cursor
[ ] : Delete of upper right vertical line to the cursor
(2) Delete a net of the sequence program (the part from the RD instruction
to the WRT instruction) with the [DELNET] key.
(3) Deleting NETs one by one

yj jy yj jy j yyj FUNCTN

INSNET DELNET ADRESS SEARCH

RETURN

EXEC CANCEL SEARCH CDOWN CUP

1 Deletion
Move the cursor to the NET to be deleted and press the
[DELETE] key. The NET to be deleted brightly displayed on
the screen.
2 Deleting multiple NETs
Move the cursor with the cursor DOWN key, [CDOWN]
key, or [SEACH] key to blink the NETs to be deleted. Type
in a value and press the [CDOWN] key to move the cursor
the number of times specified by this value.
3 Execution Press the [EXEC] key.
Cancel Press the [CANCEL] key.
4 If the NET to be deleted is already known, move the cursor
to the first NET, type in the number of NETs, and press the
[DELNET] key to omit steps 1 and 2.

527
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

X 2.0 R20.1 Y 1.2 R6.4

R0.5 For searching the same address as specified


here, set the cursor to this position, and press
soft key [SRCH].
R20.1
R0.5 X 4.2

R21.0 Y 2.0

R20.1 R2.2

R0.4
The same address is searched, and the cursor shifts
to this position.
R10.5
R0.5

5.2.5 Search a sequence program by using the following soft keys. For the
following soft keys, see Fig. 5.2.
Search of Sequence
Program
yj jy yj jy j yyj FUNCTN

INSNET DELNET ADRESS SEARCH

RETURN

TOP BOTTOM SRCH WSRCH NSRCH

NEXT

FSRCH CDOWN CUP

(1) Soft key [TOP]


When this key is pressed, the start of the sequence program is
displayed on the screen and the cursor shifts to this start position.
(2) Soft key [BOTTOM]
When this key is pressed, the last of the sequence program is
displayed on the screen, and the cursor shifts to this position.
(3) Soft key [SRCH]
This key is used to search a specified address. It searches the specified
address from the program of the cursor part to the last program of this
screen, and displays the address on the screen.

528
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

a) Method of specifying the address by the cursor


Set the cursor to the relay contact part of the address to be
searched and press soft key [SRCH].
The system searches the same address as the address specified by
the cursor from the cursor program on the presently displayed
screen to the end of the program (SUB 48).
When the same address is found, the program part is displayed
on the screen, and the cursor shifts to the address part. If the same
address is not found as a result of this search, an error is displayed.
b) Method of specifying the address by inputting it
Input an address to be searched by using address and numeric
keys and press soft key [SRCH]. The same address as specified
is searched from the program of the cursor part on the presently
displayed screen to the last of the program (SUB 48).
When the same address is found, the program part is displayed
on the screen, and the cursor shifts to the address part.
If the same address is not found as a result of this search, an error
is displayed.
(4) Soft key [WSRCH]
This key specified an address of the relay coil to be searched, and
searches the relay coil of the specified address from the program at
the cursor part to the end of the program (SUB 48) on this screen.
Then, it displays the relay coil on the screen.
Two methods are available to specify the address of the relay coil to
be searched.
a) Method of specifying the address by cursor
Set the cursor to the relay contact of the relay coil to be searched,
and press soft key [WSRCH].
The corresponding relay coil is searched from the program of the
cursor part to the end of the program (SUB 48).
When the relay coil is found, the program part is displayed on the
screen, and the cursor shifts to the relay coil.
If no corresponding relay coil is found as a result of search, an
error occurs.
b) Method of specifying the address by inputting it
Input the address of the relay coil to be searched by both address
and numeric keys, and then, press soft key [WSRCH].
The specified address relay coil is searched from the program of
the cursor part on the presently displayed screen to the end of
program (SUB 48).
When the specified address relay coil is found, the program part
is displayed on the screen, and the cursor shifts to the relay coil.
If no relay coil is found as a result of search, an error is displayed.
(5) Soft key [NSRCH]
Display the ladder with the specified NET number from the top of the
screen.
If the number is not typed in but the [NSRCH] key is pressed, the
display is scrolled down by one NET.

529
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

(6) Soft key [FSRCH]


Type in the functional instruction number and press the [FSRCH]
key to start searching the functional instruction. When the [FSRCH]
key is pressed during execution of a functional instruction, the
functional instruction with the same number as this instruction is
searched.
(7) Searching with cursor keys (<>, <>, <>, <>)
D Type in the address or symbol and press the cursor key to start
searching the address. When the key is pressed, the operation
is performed in the same manner when the [SRCH] key is pressed.
D Type in NET NO. and press the cursor key to start searching the NET
NO.
D Type in the functional instruction name or functional instruction
number with S and press the cursor key to start searching the
functional instruction.
Example) Type in END1 or S1 and press the cursor key to
search functional instruction END1.

5.2.6 The sequence program with multiple NETs can be copied in NETs.
Specify the NET to be copied and the copy position with the cursor. The
Copying the Sequence
number of copies can be also specified.
Program
yj jy yj jy j yyj FUNCTN

COPY MOVE

RETURN

UNTIL CANCEL SEARCH CDOWN CUP

TO CANCEL SEARCH CDOWN CUP

1 Copying
Move the cursor to the NET to be copied and press the [COPY] key.
The NET to be copied blinks on the screen.
2 Copying multiple NETs
Move the cursor with the cursor UP/DOWN key, [CUP] key,
[CDOWN] key, or [SEARCH] key to blink the NETs to be copied.
Type in a value and press [CUP] or [CDOWN] key to scroll up or
down the screen by the number of times specified by this value.
3 Setting the NET to be copied
Press the [UNTIL] key.
4 Specifying the copying address
Press the [TO] key to start copying a NET. The NET is copied into
the position above the cursor. If the number of copies is typed in
before the [TO] key is pressed, the NET is copied the specified
number of times.

530
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5 If the cursor is moved to the first NET and the number of NETs is
typed in when the NETs to be copied are known, steps 1 through 3
can be omitted by pressing the [COPY] key.

NOTE
An error NET cannot be copied.

5.2.7 The sequence program with multiple NETs can be moved in NETs.
Specify the NET to be moved and the move position with the cursor. The
Moving the Sequence
number of times of moving NETs can be also specified.
Program
yj jy yj jy j yyj FUNCTN

COPY MOVE

RETURN

UNTIL CANCEL SEARCH CDOWN CUP

TO CANCEL SEARCH CDOWN CUP

1 Moving
Move the cursor to the NET to be copied and press the [MOVE] key.
The NET to be moved blinks on the screen.
2 Moving multiple NETs
Moving the cursor with the cursor UP/DOWN key, [CUP] key,
[CDOWN] key, or [SEARCH] key to blink the NETs to be moved.
Type in a value and press [CUP] or [CDOWN] key to scroll up or
down the screen by the number of times specified by this value.
3 Setting the NET to be moved
Press the [UNTIL] key.
4 Specifying the copying address
Press the [TO] key to start copying a NET.
The NET is moved to the position above the cursor.
5 If the cursor is moved to the first NET and the number of NETs is
typed in when the NETs to be moved are known, steps 1 through 3
can be omitted by pressing the [MOVE] key.

NOTE
An error NET cannot be copied.

531
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.2.8 While editing a sequence program, symbol data and comment can be
Editing Symbol Data edited.
and Comment at Once (1) The symbol data and comment assigned to undefined address can be
edited.
a) Move the cursor to the position where a contact or coil is to be
inputted.
b) Enter an address, enter the symbol and comment enclosed in
characters other than alphanumeric characters, then press the soft
key of [contact or coil].
(Example) When the contact X8.4 is assigned the symbol
*ESP and the comment EMERGENCY STOP.
Operation : Depress [contact] soft key after
entering X8.4/ *ESP/EMERGENCY STOP/.
(2) The symbol data and comment assigned to the address already
defined can be edited.
a) Move the cursor on the address part where symbol data or
comment will be edited.
b) Enter the symbol and comment enclosed in characters other than
alphanumeric characters, then press the <INPUT> key.
(Example) When the contact X8.4 is assigned the symbol
*ESP and the comment EMERGENCY STOP.
Operation : Depress the <INPUT> key after
entering /*ESP/ EMERGENCY
STOP/.
(3) The symbol data and comment only can be edited by the similar
operation to the above (1) and (2).
a) For entering X8.4/*ESP/ or /*ESP/ with the INPUT key,
the symbol data only can be edited.
b) For entering X8.4//EMERGENCY STOP/ or
//EMERGENCY STOP/ with the INPUT key, the comment
only can be edited.

5.2.9 The address in a sequence program can be replaced with another address
Address Change of by the procedure below.
Sequence Program
COPY MOVE CHANGE

OADR CANCEL

NADR CANCEL

EXEC CANCEL SEARCH C CUP


DOWN

532
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

(1) Changing the address while checking it one by one


a) Press the [CHANGE] key.
b) Input the original address and press the [OADR] key.
c) Input the new address and press the [NADR] key.
d) Press the [EXEC] key for executing the change. After
completion, the cursor will shift downward to the nearest address
to be changed.
If the [EXEC] key is pressed again at the point, the address
change can be continued.
(2) Changing the address within the specified range
a) Press the [CHANGE] key, and move the cursor to the address to
be changed.
b) Input the original address and press the [OADR] key.
c) Input the new address and press the [NADR] key.
d) The specified range will be brightened by using the [CDOWN]
or [CUP] key.
All the addresses within the specified range can be changed.
e) Press the [EXEC] key for executing the change.
(3) Address designation by a wild card
The address to be changed can be designated by using the * code
as a wild card.
(Example) X*.0 means X0000.0, X0001.0, . . . . , X9999.0.
X0000.* means X0000.0, . . . . , X0000.7.
X* means X0000, X0001, . . . . , X9999.
The wild card can be used for both of the original address (OADR)
and new adress (NADR).
The following are examples by wild card.
a) X0.* to D100.*
X0000.0 D0100.0
X0000.1 D0100.1
:
X0000.7 D0100.7
b) X*.0 to X*.7
X0000.0 X0000.7
X0001.0 X0001.7
:
X9999.0 X9999.7
[Limit items]
D The address of data part in Functional instruction DISP
cannot be changed.
D If the original address (OADR) and new address (NADR) are
different in address name and the byte part of new address
(NADR) is specified by a wild card, the change can not be
done.
Example) D1234.0 X*.7, D* X*

533
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.3 Set and delet the address of each module in I/O unit as follows. The
relation between these functions and soft keys is as shown in the
I/O UNIT ADDRESS following figure.
SETTING (MODULE)
RUN EDIT I/O SYSPRM MONIT

RETURN

TITLE LADDER SYMBOL MESAGE

NEXT

SYSPRM MODULE

RETURN

INPUT SEARCH DELETE PRV.CH NXT.CH

(Note 1) (Note 1)
NEXT

IOSTRT

(Note 1)These soft keys are available, when editing sequence program
is allowed to assign to the I/O Link channel 2.

Fig. 5.3 Address setting for I/O unit


(1) Address setting for each module
1 Press the soft key [MODULE].
The following module address setting screen is displayed.
2 Move the cursor to the address to be set, and input data in the
order of GROUP, BASE, SLOT, and NAME and press
INPUT key. Input a dot (.) as a delimiter of each data.
Example) When setting the AID16A module with group = 0,
base = 0, and slot = 5
0. 0. 5. ID16A
Table 3.2.2 in Section I3.2 lists the necessary names for the
NAME column.
3 Set all data of the module employed to aimed addresses by
using the cursor key and page key.

534
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

PMC I/O MODULE

ADDRESS GROUP BASE SLOT NAME ADDRESS GROUP BASE SLOT NAME
X000 2 0 2 ID16C Y000 3 0 1 #1 I/O Unit
X001 2 0 2 ID16C Y001 3 0 5 #1 MODEL B
X002 3 0 9 #2 Y002
X003 3 0 9 #2 Y003
X004 3 0 30 #2 Y004 2 0 1 OD16C I/O Unit
X005 3 0 30 #2 Y005 2 0 1 OD16C MODEL A
X006 3 0 10 #2 Y006 2 1 1 OD32D
X007 3 0 10 #2 Y007 2 1 1 OD32D
X008 3 0 20 #2 Y008 2 1 1 OD32D
X009 3 0 20 #2 Y009 2 1 1 OD32D
X010 3 0 0 ## Y010 2 0 3 OD16C
X011 3 0 0 ## Y011 2 0 3 OD16C
X012 3 0 0 ## Y012
X013 3 0 0 ## Y013
X014 0 0 1 FS04A Y014 0 0 1 FS04A
Power
Mate
GROUP.BASE.SLOT.NAME =
>2.0.4.OD08C

CAUTION
I/O module data items are made valid in the poweron
sequence. When changing settings, be sure to turn off the
power and turn it on to validate the settings.
However, the power need not be turned off and on again to
validate settings when the programmer function version
displays the soft key IOSTRT, (described later (item 4).
Press the IOSTRT key after changing data.

(2) Delete of address


A preset address of each module can be deleted as follows:
1 Move the cursor to the address to be deleted, and press soft
key [DELET] (see Fig. 5.3).
2 The preset address data are deleted.
(3) Soft key [SEARCH]
Searches the typein address.
1 Type in the address to be searched and press the [SEARCH]
key.
2 The typedin address starts being displayed from the top of
the screen.
(4) Validate the assignment data.
I/O module data is validated when the power is turned on. If I/O
module data is changed without changing the configuration of the I/O
devices, the new I/O module data is validated when the IOSTRT key
is pressed.
The conditions where the IOSTRT key is displayed depend on the
version of the programmer function.
(5) Soft key [PRV.CH] or [NXT.CH]
1 It is available to assign the I/O Link expansion. This soft key
is to change the I/O Link channel.

535
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

(6) Error and warning messages issued during the editing of assignment
data
No. Error or warning message Description
1 ERR : GROUP NO. (015) The group number must be from 0 to 15.
2 ERR : BASE NO. (03) The base number must be from 0 to 3.
3 WARN : BASE NO. MUST BE 0 The base number must be 0 for the I/O UnitB. It is forcibly set to 0.
4 ERR : SLOT NO. (110) The slot number must be from 1 to 10 for the I/O UnitA.
5 ERR : SLOT NO. (0, 130) The slot number must be from 0 to 30 for the I/O UnitB.
6 ERR : SLOT NO. MUST BE 0 The slot number must be 0 to set the poweron/off information for the I/O UnitB.
7 ERR : ILLEGAL NAME An invalid or unsupported assignment name has been entered. Enter a correct name.
8 INPUT INVALID An invalid character string has been entered. Reenter with a correct format.
9 INPOSSIBLE WRITE An attempt has been made to edit ROM data. ROM data cannot be edited.
10 ERR : ADDRESS ALREADY ASSIGNED The specified address is already assigned. Assign another address or retry after
deleting the existing data.
11 ERR : ADDRESS OVER An address exceeds the upper limit (X127, Y127). Check the addresses used for the
unit to be set.
12 ERR : SLOT ALREADEY DEFINED The specified slot is already assigned. Check the existing data.
13 WARN : SLOT ALREADY DEFINED The specified slot is already assigned. Check the existing data.
14 ERR : UNIT TYPE MISMATCH (IN OR OUT) An X address cannot be assigned to an output module. A Y address cannot be
assigned to an input module.
15 ERR : UNIT TYPE MISMATCH (MODEL) I/O UnitA and I/O UnitB are assigned in the same group. I/O UnitA and I/O UnitB
cannot exist in the same group.

536
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.4 A signal name (within 6 alphanumeric characters) can be attached to I/O


signals and internal relays employed in sequence programs.
SYMBOL DATA
SETTING (SYMBOL) Also, a comment (within 30 alphanumeric characters) can be attached to
the relay coils in addition to the symbol name.
Symbol data and comment are displayed together with a ladder diagram
on the CRT/MDI screen as follows.

Signal name
(within 6
characters)
MA SPDALM X2.4 R2.2 Y4.3 ATCALM R100.1 MRDY
MACHINE Comment
READY within 30
APCALM R5.4 MALM characters

MACHINE
10 lines ALARM

Addresses are
issued for those
items for which
symbols are not R120.1 TIND D20.7 R52.1
defined.
APC

If symbol data and comment are defined in signal addresses of the


program, the signal name and comment are displayed as Shown in the
above figure.
If neither symbol data nor comment is defined at an address, the address
is displayed as it is.
A maximum of 64 KBytes can be used for the ladder, symbol, comment,
and data. After the program is initialized, the capacity of the symbol area
and that of the comment area are usually 32KB (28KB for PMCNB)
each. When additional data is entered causing the total amount of data in
either area to exceed 32KB (28KB for PMCNB), the area is
automatically extended in 1KB units.

STOP EDIT I/O SYSPRM MONIT

RETURN

TITLE LADDER SYMBOL MESAGE

RETURN

INPMOD DELETE SEARCH COPY

Fig. 5.4(a) Setting and display of symbol data

537
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

When soft key [SYMBOL] is pressed, the following screen is displayed,


and the soft key operation is done hereafter.

SYMBOL & COMMENT 001


ADDRESS SYMBOL COMMENT
*---------* *------*-------*--------------*

Fig. 5.4(b) Symbol data screen

5.4.1 Refer to Fig. 5.4 (a) and Fig. 5.4 (b). Input symbol data and comment on
the screen shown in Fig. 5.4 (b).
Symbol Data and
1 Press <INPUT> key after inputting an address where a symbol and
Comment Input
a comment are to be set.
The input address is set to the ADDRESS column of Fig. 5.4 (b), and
the cursor shifts to the address. The input addresses are arrange and
set in the alphabetic sequence, and they can be inserted halfway.
2 For setting a symbol, shift the cursor rightward by using the cursor
key.
3 After setting symbol data (within 6 alphanumeric characters), press
INPUT key.
The symbol data are set in the SYMBOL column of Fig. 5.4 (b), and
the cursor shifts to the COMMENT column.
4 For inputting a comment, set comment data (within 30 alphanumeric
characters), and press INPUT key.
Comment data are set to the COMMENT column in Fig. 5.4 (b).
Repeat steps 1 to 4 hereafter.

5.4.2 Display the screen shown in Fig. 5.4 (b) and search symbol data
Symbol Data Search (1) After setting an address or symbol data to be searched, press soft key
[SRCH].
(SRCH)
Specified address or symbol data is searched and displayed on the
screen.
The cursor shifts to the corresponding address part.

5.4.3 Move the cursor to the address to be deleted in the ADDRESS column of
Fig. 5.4 (b), and press soft key [DELETE].
Delete of Symbol Data
and Comment

538
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.4.4 The edit modes can be changed by pressing the [INPMOD] soft key as
Editing Character follows:
Strings of Symbol Data Character string edit status
and Comment Data Maximum Insertion mode Replacement
character input (INSERT) mode (ALTER)

INSERT is displayed on the screen in the insertion mode. ALTER


is displayed on the screen in the replacement mode.
D When the <INPUT> key is pressed
(1) In the character string edit status
Insertion mode : The entered character is inserted at the cursor.
If the [INPUT] key is pressed after no
character is entered, one space is inserted.
Replacement mode : The character at the cursor is replaced with
the entered character. If the [INPUT] key
is pressed after no character is entered, the
character at the cursor is replaced with one
space.
(2) When the length of the cursor is the same as the number of
characters that can be entered.
The original character string are replaced with the entered
characters.
D When the <DELETE> key is pressed
(1) In the character string edit status
Insertion mode : The character at the cursor is deleted.
Replacement mode : The character at the cursor is replaced with
a space.
(2) When the length of the cursor is the same as the number of
characters that can be entered
The character string at the cursor is deleted.

5.4.5 An address, symbol, and comment can be entered at one time.


Function for Editing (1) Editing the symbol and comment assigned to address not defined
Symbol Data and Enter an address, enter the symbol and comment enclosed in
Comment Data at One characters other than alphanumeric characters, then press the
<INPUT> key.
Time
The cursor may be located anywhere. A comment can be omitted.
Example) G0.4 / *EMG / EMERGENCYSW/ <INPUT> key
Address Symbol Comment
(2) Editing the symbol and comment assigned to address already defined
Move the cursor to the desired line of the address whose symbol and
comment are to be edited.
Next, enter the symbol and comment enclosed in characters other than
alphanumeric characters.
Then, press the <INPUT> key. A comment can be omitted.

539
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.4.6 Copy the specified data to reedit and register it.


Function of Copying
Symbol and Comment INPMOD DELETE SEARCH COPY

Data
RETURN

SYMBOL ALL CANCEL

UNTIL CANCEL

EXEC INPMOD DELETE CANCEL

(1) Press the [COPY] soft key.


(2) Select data to be copied with the corresponding soft key.
[ALL] : The address, symbol data, and comment data are copied.
[SYMBOL] : The address and symbol data are copied.
When either of the above soft keys is pressed, the line at the cursor
is specified as the beginning of the range of the data to be copied.
(3) Specify the range with the [] and [] cursor keys.
D A range of more than 15 lines cannot be specified. Up to 15 lines can
be displayed on one screen.
D A range cannot be specified at a position above the cursor position.
When the copy range of the data is specified, the data is displayed
differently.
(4) Press the [UNTIL] soft key to determine the copy range.
(5) Edit the address and symbol data according to the procedure
described in Sections 5.4.1 and 5.4.4.
(6) When updating the data is completed, press the [EXEC] soft key to
register the copied data.

540
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.5 Message data are used for PMC functional instruction DISPB (SUB 41).
MESSAGE DATA The setting and display methods are as shown below.
SETTING (MESSAGE)
RUN EDIT I/O SYSPRM MONIT
(STOP)
RET

TITLE LADDER SYMBOL MESAGE

RET

INPMOD DELETE SRCH COPY DSPMOD

NEXT

ETC D.CHAR

Fig. 5.5 (a)


When soft key MESAGE is pressed, the next screen is displayed, and
setting operation can be done hereafter.

MESSAGE 001
NO. MESSAGE
A 00.0
A 00.1

A 01.1

Fig. 5.5 (b) Message data screen


After initialization, the capacity of the message area is approx. 2.1KB.
When additional data is entered causing the total amount of data in the
area to exceed 2.1KB, the message area is automatically extended in 1KB
units to a maximum of 64KB.

541
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.5.1 Refer to Fig. 5.5 (a) and Fig. 5.5 (b). Display the screen shown in Fig. 5.5
Message Data Input (b).
1 Display a number to set a message data by using PAGE key.
2 Shift the cursor to this number by the cursor key.
3 After setting message data, press INPUT key.
If the message data has already been entered, it is deleted and the set
data is entered.
Repeat steps 1 to 3 hereafter.

5.5.2 (1) Specify an address to be searched for, and press the [SRCH] soft key.
Searching for an Then, the specified address is searched for and displayed on the
screen.
Address (SRCH)

5.5.3 Edit modes can be changed by pressing the [INPMOD] soft key as
Editing a Character follows:
String in Message Data Character string edit status

Maximum char- Insertion input Replacement input


acter input (32 (INSERT) (ALTER)
characters)

The edit mode is changed every time the [INPMOD] soft key is pressed.
[INSERT] is displayed on the screen in the insertion mode.
[ALTER] is displayed on the screen in the replacement mode.
D When the <INPUT> key is pressed
(1) In the character string edit status
Insertion mode : The entered character is inserted at the cursor.
Replacement mode : The character at the cursor is replaced with
the entered character.
(2) When the maximum number of characters are entered
The original character string at the cursor is replaced with the
entered characters.
D When the <DELETE> key is pressed
(1) In the character string edit status
Insertion mode : The character at the cursor is deleted.
Replacement mode : The character at the cursor is replaced with
a space.
(2) When the maximum number of characters are entered
The character string at the cursor is deleted.
(3) When the cursor is located at the address field
The entire message data specified at the address is deleted.

542
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.5.4 If no @ key on the MDI key, pressing the [ETC] soft key enables the
Input with a Katakana operator to enter the data enclosed between at signs (@).
Identification Code When the soft key is pressed, ETC CODE is displayed on the screen.

5.5.5 Move the cursor to the message number to be copied and press the
[COPY] key.
Copying Message Data
(COPY) Then press the [EXEC] key after moving the cursor to the message
number in which it is copied.

5.5.6 The input mode becomes multibyte character by pressing the [D.CHAR]
Inputting a Multibyte key.
Character (D.CHAR) (@02, 01@ are added to input data automatically.)
For example, 4873 [INPUT] is processed as @02487301@.

5.5.7 The ASCII code enclosed with @ characters is displayed in the form of
Displaying Input Code screen display by pressing the [DSPMOD] key.
(DSPMOD) Example) Katakana : @B6C532@ is displayed.
Multibyte character :
@0248733E6F44643B5F01@100
is displayed.

543
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.6
CLEARING THE
RUN EDIT I/O SYSPRM
SEQUENCE (STOP)
PROGRAM AND RET
CONDENSATION OF
TITLE LADDER SYMBOL MESAGE
THE SEQUENCE
PROGRAM RET NEXT

MODULE CROSS CLEAR

CLRTTL CLRLAD CLRSYM CLRMSG CLRLNG

NEXT

CLRALL CLRMDL CONDNS CLRPRM CLREXT

CLRTMR CLRCNT CLRKPR CLRDT

NEXT

CLRALL

5.6.1 Clears each data in the sequence program


Clearing the Sequence The function of the key is as follows:
Program (1) [CLRTTL] : Clears the title data.
(2) [CLRLAD] : Clears the ladder program.
(3) [CLRSYM] : Clears the symbol and comment data.
If the extend symbol and comment data is cleared,
the field is restored to the original size.
(4) [CLRMSG] : Clears the message data.
If the extend message data is cleared, the field is
restored tothe original size.
(5) [CLRLNG] : The C language area is cleared. Clear the C language
area before transferring a C program. When a C
language board is installed in the Series 16i/18i, this
item is displayed.
(6) [CLRALL] : Clear all data described in the above (1) to (4). Clear
also the C language programs for models which
create C language programs, such as models
PMCSC, SC3, SC4, NB, and NB2.
Press this soft key when the message PLEASE
CLEAR ALL is displayed.
(7) [CLRMDL] : Clears the I/O module data.

544
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

(8) [CONDNS] : Compress the sequence program in 1KB units.


The detail will be explained chapter 5.6.2.
(9) [CLRPRM] : Clears each parameter data.
The detail will be explained chapter 5.6.3.
(10) [CLREXT] : Clears the expand nonvolatile memory (valid for
PMCSC/SC3/SC4/NB/NB2)

CAUTION
When using a system that incorporates flash ROM, clear the
flash ROM before writing to it. If the power is turned on again
without performing this operation, sequence program data
is not cleared.

5.6.2 Compresses the sequence program in 1KB units.


Compress the (1) [CONDNS] : Compresses the unused area in the message, symbol,
Sequence Program or comment area in the sequence program in 1KB
units when the capacity of the unused area extends
1KB. The unused area, which is the size less than
1KB, will not be compressed.

5.6.3 Clears each PMC parameter.


Clearing the PMC The function of the key is as follows:
Parameter (1) [CLRTMR] : Clears timer data.
(2) [CLRCNT] : Clears counter data.
(3) [CLRKPR] : Clears keep relay data.
(4) [CLRDT] : Clears data table.
(5) [CLRALL] : Clear all data described in the above (1) to (4).

CAUTION
These functions require the same condition as PMC data
setting in operation For [CLRALL], all conditions are
required. See Chapter II.4. PMC PARAMETER SETTING
AND DISPLAY

545
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

5.7 The cross reference is displayed for PMC address and functional
instruction used in a sequence program.
CROSS REFERENCE
DISPLAY Cross reference display has the following functions.
(1) Display NET number by specifying the PMC address.
(2) Display the address list by specifying PMC address name (G, F, Y,
).
(3) Display a functional instruction list.
(4) Display NET number by specifying the functional instruction
number.

5.7.1 Pressing the [CROSS] key displays the cross reference screen for setting
parameters.
Operation
Press soft key [CRSREF] in the parameter setting screen for displaying
the cross reference of address and functional instruction in use. Press soft
key [CRSPRM] to return to the parameter setting screen from cross
reference display.

RUN EDIT I/O SYSPRM MONIT


(STOP)
RET

TITLE LADDER SYMBOL MESAGE

NEXT

MODULE CROSS CLEAR

RET

CRSREF INPUT INIT

CRSPRM

546
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

5.7.2 To display cross reference, the address and reference type need to be
Parameter Setting specified on the parameter screen.
Screen
Display the reference of 1. In SELECT CROSS TYPE, input 1.
addresses which are 2. In 1: REFERENCE ADDRESS, input addresses which should be
used. displayed. (maximum number of input: 8)
3. Press [CRSREF] key.
The address, symbol, relay and the NET number will be displayed as
shown in Fig. 5.7.2 (b).

PMC CROSS REFERENCE


SELECT CROSS TYPE = 1
( 1:ADDRESS 2:ADRS KIND 3:FUNCTION.NO )
1:REFERENCE ADDRESS
1 = X0000.0 5 =
2 = 6 =
3 = 7 =
4 = 8 =
2:ADRS KIND =
( G /F /Y /X /A /R /K /C /D /P /L )
3:FUNCTION.NO = ( ALL=0 )

[CRSREF] [INPUT ] [ ] [ INIT ] [ ]

Fig. 5.7.2 (a) Cross reference setting (TYPE1)

PMC CROSS REFERENCE

X0000.0 ABCDE
: 1 2
( ) : 4 32

[CRSPRM] [ ] [ ] [ ] [ ]

Fig. 5.7.2 (b) Cross reference display (TYPE1)

547
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

Display the reference of 1. In SELECT CROSS TYPE, input 2.


each address name 2. In 2: ADRS KIND, input the address name.
3. Press [CRSREF] key.
The bit/byte addresses and the related symbol in the sequence
program will be displayed as shown in Fig.5.7.2 (d).

PMC CROSS REFERENCE


SELECT CROSS TYPE = 2
( 1:ADDRESS 2:ADRS KIND 3:FUNCTION.NO )
1:REFERENCE ADDRESS
1 = X0000.0 5 =
2 = 6 =
3 = 7 =
4 = 8 =
2:ADRS KIND = X
( G /F /Y /X /A /R /K /C /D /P /L )
3:FUNCTION.NO = ( ALL=0 )

[CRSREF] [INPUT ] [ ] [ INIT ] [ ]

Fig. 5.7.2 (c) Cross reference setting (TYPE2)

PMC CROSS REFERENCE

HEAD CHARACTER = X

USED ADDRESS = X0000.0


SYMBOL NAME = ABCDE

X0000
SYMBOL NOTHING

[CRSPRM] [ ] [ ] [ ] [ ]

Fig. 5.7.2 (d) Cross reference display (TYPE2)

548
5. EDITING OF SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM (EDIT)

Display a functional 1. In SELECT CROSS TYPE, input 3.


instruction list in use 2. In 3: FUNCTION. NO, input 0.
3. Press [CRSREF] key.
The functional instruction name and the functional instruction
number in the sequence program will be displayed as shown in
Fig.5.7.2 (f).

PMC CROSS REFERENCE


SELECT CROSS TYPE = 3
( 1:ADDRESS 2:ADRS KIND 3:FUNCTION.NO )
1:REFERENCE ADDRESS
1 = X0000.0 5 =
2 = 6 =
3 = 7 =
4 = 8 =
2:ADRS KIND =
( G /F /Y /X /A /R /K /C /D /P /L )
3:FUNCTION.NO = ( ALL=0 )

[CRSREF] [INPUT ] [ ] [ INIT ] [ ]

Fig. 5.7.2 (e) Cross reference setting (TYPE3)

PMC CROSS REFERENCE

FUNCTION NAME END1( 1) END2( 2)


COD( 7)

[CRSPRM] [ ] [ ] [ ] [ ]

Fig. 5.7.2 (f) Cross reference display (TYPE3)

549
5. EDITING OF SEQUENCE
PROGRAM (EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

Display the reference of 1. In SELECT CROSS TYPE, input 3.


functional instruction 2. In 3: FUNCTION. NO, input the functional instruction number.
(FUNCTION. NO =
number of the functional 3. Press [CRSREF] key.
instruction) The functional instruction name, functional instruction number and
NET number in the sequence program will be displayed as shown in
Fig.5.7.2 (g).

PMC CROSS REFERENCE

FUNCTION NO. = 7
FUNCTION NAME = COD
USED NET NO. = 6 14

[CRSPRM] [ ] [ ] [ ] [ ]

Fig. 5.7.2 (g) Displaying of cross reference (TYPE3)

550
6. EXECUTION OF A SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM

6 EXECUTION OF A SEQUENCE PROGRAM

551
6. EXECUTION OF A SEQUENCE
PROGRAM PMC PROGRAMMER (CRT/MDI) B61863E/14

6.1 Start and Stop of a sequence program are described as follows.


START AND STOP OF
PMCLAD PMCDCN PMCPPM
A SEQUENCE
PROGRAM RETURN

RUN EDIT I/O SYSPRM MONIT


or STOP

Fig. 6.1 The sequence program execution software key


An operable sequence program is usually automatically started when
power is turned on if the program is stored in ROM. However, the
program is not started if it is stored in RAM.
(1) Start of a sequence program (RUN)
When a sequence program is at the stopped state, pressing the [RUN]
key causes the sequence program to run displaying the software key
as [STOP].
The ladder program starts from the beginning. However, whether
Clanguage programs start from the beginning depends on the
function selected in advance.
a) When a Clanguage program starts from the beginning
Functions selected in advance: Ladder editing, reading the
system parameter, reading a sequence program using
input/output processing
b) When a Clanguage program does not start from the beginning
but restarts from the next step after stopping
Function selected in advance: Functions other than the function
in item (a)

NOTE
Both ladder and Clanguage programs start from the
beginning immediately after the power is turned on.

(2) Stop of a sequence program (STOP)


When a sequence program is at the run state, pressing the [STOP] key
causes the sequence program to stop displaying the software key as
[RUN].

552
6. EXECUTION OF A SEQUENCE
B61863E/14 PMC PROGRAMMER (CRT/MDI) PROGRAM

6.2 The sequence program can be automatically started immediately after


poweron, when bit 2 of keep relay K17 (PMC parameter) is set to 1.
STARTING THE
SEQUENCE NOTE
PROGRAM For the Series 16/18MODEL B/C, Series
16i/18i/21i/15iMODEL A, automatic start is specified
when bit 2 of K17 is set to 0.

6.3 To forcibly stop starting the sequence program in ROM or RAM, at


poweron, turn on the power by pressing the [Z] key while pressing the
FORCIBLY [CAN] key. (Except for PMCNB/NB2)
STOPPING THE
This method is effective for locating the error when a system error occurs
SEQUENCE after power is turned on and when the error may be caused by the sequence
PROGRAM program.
Never perform this operation in a normal state.

WARNING
In normal operation, do not use the Z + CAN keys to stop the
sequence program forcibly.

553
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

7 WRITING, READING, AND VERIFYING THE SEQUENCE


PROGRAM AND PMC PARAMETER DATA

When the [I/O] key is pressed, the sequence program and PMC data are
written, read, or collated for the specified device. Operations are
performed with cursor keys and soft keys.

RUN EDIT I/O SYSPRM

RETURN

EXEC CANCEL (NO.)

554
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.1 When the [I/O] key is pressed, the sequence program and PMC data are
written, read, or collated for the specified device. Operations are
OVERVIEW performed with cursor keys and soft keys.

RUN EDIT I/O SYSPRM

RETURN

EXEC CANCEL (NO.)

NEXT

SPEED

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1

DEVICE = HOST

DATA KIND =
(ALL:LADDER + LANGUAGE)
FUNCTION =

>
ALM
[ EXEC ] [CANCEL] [ HOST ] [FDCAS ] [FROM ]

[Case of FS16/18]

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1

DEVICE = HOST

DATA KIND =

FUNCTION =

>

[ EXEC ] [CANCEL] [ HOST ] [FDCAS ] [ROMWRT]

[ ] [OTHERS] [SPEED ] [ ] [ COPY ]

555
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

CAUTION
The sequence program can be output while the ladder is
being executed, but the output speed is low. When the
sequence program is input while the ladder is being
executed, the execution of the ladder is automatically
stopped.

7.1.1 Conventionally, C programs have been managed together with ladder


programs. For this reason, when only a ladder program is to be modified
C Input/Output
as shown in Fig. 7.1.1 (a), the program linked with a C program needs to
be replaced.
With the FANUC Series 16i/18i/160i/180i, ladder programs and C
programs are managed separately. So, each program can be edited and
replaced independently of the other programs as shown in Fig. 7.1.1 (b).

NC

Ladder Download Ladder


+ Upload
C +
C

Download
C

Fig. 7.1.1 (a) Ladder and C structure for FANUC Series 16B/16C

NC

Ladder Download Ladder


Upload

C Download C
Upload

Fig. 7.1.1 (b) Ladder and C structure for FANUC Series 16i/18i/160i/180i

556
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.2 (1) CHANNEL


SET ITEMS Specify which connector the reader/punch interface (such as
RS232C) is connected to. CHANNEL must be set when HOST,
FDCAS, or OTHERS is selected for DEVICE.
(2) DEVICE
Select the device with which the PMC inputs or outputs data, using
soft keys.
Soft key Description
HOST Transfers data with a FANUC LADDER (PG, PG Mate, or personal
computer).
(See Subsection 7.3.1 for details.)
FDCAS Transfers data with a FANUC FD cassette.
(See Subsection 7.3.2 for details.)
FROM Transfers data with flash EEPROM. This is where the sequence program is
stored.
(See Subsection 7.3.3 for details.)
MCARD Transfers data with a memory card.
(See Subsection 7.3.4 or details.)
OTHERS Transfers data with other input/output devices.
(See Subsection 7.3.5 for details.)
SPEED Used to set transfer conditions when RS232C is used.
(See Subsection 7.3.6 for details.)
ROMWRT Transfers data with a ROM WRITER.
(See Subsection 7.3.7 for details)

NOTE
Some functions cannot be used with some PMC models.
See Section 7.3.

(3) DATA KIND


Select the type of output data using soft keys. DATA KIND must be
set when FDCAS, MCARD, or OTHERS is selected for DEVICE.
DATA KIND CONTENTS
ALL Output the data of sequence program and C program
LADDER Output the data of sequence program
(Ladder, Symbol, Comment, Message, etc.)
PARAM Output PMC Parameters
(Note 1) (TIMER, COUNTER, KEEP RELAY, DATA TABLE, etc.)
CLANG Outputs a C program.
(Note 2)

NOTE
1 The conditions of outputting PMC parameters
1) When sequence program is stopped
You can input/output them.
2) When sequence program is executed
You must satisfy the following conditions.
Output (WRITE) Set NC to EDIT mode.
Input (READ) . . . Set NC to Emergency Stop status,
and, set PWE of NC parameters to 1.
2 When a C language board is installed in the Series 16i/18i,
the item of CLANG is displayed, and C program output is
enabled.

557
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

(4) FUNCTION
Select the direction of data transfer between the PMC and
input/output device.
Item Description
WRITE Outputs data from the PMC to an input/output device.
READ Inputs data from an input/output device to the PMC.
COMPARE Collates data in the PMC and an input/output device.
(Note) PMC data cannot be collated.
DELETE Deletes a file in FDCAS or MCARD.
LIST Lists the files in FDCAS or MCARD.
BLANK Performs blank check for FROM.
ERASE Clears the data in FROM.
FORMAT Initializes MCARD (clears all data).

(5) FILE NO.


FILE NO. is displayed when FDCAS or MCARD is selected for
DEVICE. Specify the file number or file name for WRITE, READ,
COMPARE, or DELETE processing. Note the following restrictions
on the file name when FDCAS or MCARD is selected for DEVICE:
FDCAS (FANUC FD MCARD (MEMORY
CASSETTE) CARD)
Number of characters Up to 17 characters following @ Up to 8 characters following @
in the file name or #. The file is written after the or #(*1).
existing files.
When the same name An error occurs. Delete the The new file is written over the
as an existing file is existing file and reoutput the existing file (the contents of the
specified new file. existing file are lost).
When 1 is specified The file is written after the The system names the file and
for the file name existing files. writes it(*2).
When 0 is specified for The file is written and all the The system names the file and
the file name existing files are deleted. writes it(*2).

NOTE
1 Name the file in the MSDOS format (up to eight characters
for the file name with up to three characters for the
extension).
Example) FILE NO. = @12345678.123
FILE NO. = @LADDER.EXE
2 If the file name is not specified, the system names the file
as follows:
The model name is
DATA KIND File name
PMCNB for the
ALL modelname.ALL
PMCNB and PMCSA
LADDER modelname.LAD
for the PMCSA1 or
PARAM modelname.PRM PMCSA3.

558
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.3
OPERATIONS

7.3.1 (a) Setting the channel


Transfer to and from a Move the cursor to CHANNEL = . Check that an RS232C cable
is connected to the main board. Enter the number (1 or 2)
FANUC LADDER corresponding to the connector. The correspondence between the
connector and CHANNEL is as follows:
CHANNEL = 1 : JD5A (main board)
CHANNEL = 2 : JD5B (main board)
(b) Setting the transfer conditions
Press the [SPEED] soft key and set each condition. See Subsection
7.3.6 for details.
(c) Writing, reading, or collating the sequence program
Item Operation
DEVICE Press the [HOST] soft key.
Press the [EXEC] soft key and to make the NC ready for operation.

Select necessary items on a FANUC LADDER and start transfer.

NOTE
1 WRITE, READ, or COMPARE is automatically switched by
operation on a FANUC LADDER.
2 This operation can not be used with PMCSB7.

7.3.2 Reads or writes the sequence program, Pascal or C programs, or PMC


Transfer to and from a data.
FANUC FD Cassette PMC I/O PROGRAM MONIT STOP

CHANNEL = 1

DEVICE = FDCAS

DATA KIND = ALL


(ALL:LADDER + LANGUAGE)
FUNCTION = WRITE

FILE NO. = 1
(1:ADD,0:INIT,OR @ NAME)
>
ALM
[ EXEC ] [CANCEL] [ HOST ] [FDCAS ] [FROM ]

(a) Setting the channel


Enter the number of the channel used at CHANNEL = . See (a) in
Subsection 7.3.1 for details.

559
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

(b) Setting the transfer conditions


Press the [SPEED] soft key and set each condition. See Subsection
7.3.6 for details.
(c) Writing a file
Item Operation
DEVICE Press the [FDCAS] soft key.
FUNCTION Press the [WRITE] soft key.
DATA KIND Select the type of data to be output (see (3) in Section 7.2).
FILE NO. Name the file within 17 characters. 1 is displayed if no name is entered
(see (5) in Section 7.2).

Press the [EXEC] soft key to start outputting the file.


(d) Reading a file
Item Operation
DEVICE Press the [FDCAS] soft key.
FUNCTION Press the [READ] soft key.
FILE NO. Enter the number or name of the file to be input.

Press the [EXEC] soft key to start inputting the file.


(e) Collating a file
Item Operation
DEVICE Press the [FDCAS] soft key.
FUNCTION Press the [COMPAR] soft key.
FILE NO. Enter the number or name of the file to be collated.

Press the [EXEC] soft key to start collating the file.

Note
PMC data cannot be collated. The data the file is to be
collated with depends on the file.

(f) Deleting a file


Item Operation
DEVICE Press the [FDCAS] soft key.
FUNCTION Press the [DELETE] soft key.
FILE NO. Enter the number or name of the file to be deleted.

Press the [EXEC] soft key to start deleting the file.


(g) Listing the files
Item Operation
DEVICE Press the [FDCAS] soft key.
FUNCTION Press the [LIST] soft key.

Press the [EXEC] soft key to start listing the files.

560
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.3.3
Storage to Flash ROM : Supported
: Not supported
FS21i
Power Power MateH FS21/ FS16B FS16C
FS18 FS16A FS16i FS15B
MateD/F/G FS20 210MB FS18B FS18C
FS18i

Formerly, a RAM module or ROM module was necessary for storing


programs. Using Flash Memory, however, programs can be ROMstored
on the PMC board.

CAUTION
1 If the power is turned off without performing the writing
operation, the updated sequence program is not stored.
2 The CNC must be placed in the emergency stop state when
data is read from or written to Flash Memory.
3 Even if the sequence program is cleared with the X and O
keys at poweron, the contents of Flash Memory are not
cleared. Therefore, when the power is turned on again, the
sequence program in Flash Memory is read. To clear the
contents of Flash Memory, write Flash Memory after
clearing the sequence program with X and O.

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1

DEVICE = FROM

DATA KIND =
(ALL:LADDER + LANGUAGE)
FUNCTION = WRITE

RAM SIZE = A ( MAX SIZE = B )


PROGRAM ALREADY EXISTS (EXEC?)
>
ALM
[ EXEC ] [CANCEL] [ HOST ] [FDCAS ] [FROM ]

(a) Writing data to Flash Memory


Item Operation
DEVICE Press the [FROM] soft key.
FUNCTION Press the [WRITE] soft key.

Press the [EXEC] soft key to start outputting data.

561
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

CAUTION
1 Operation in PMCNB
(a)If data is stored in Flash Memory, a message is displayed
to confirm writing.
(b)RAM SIZE indicates the size of the sequence program.
MAX SIZE indicates the size of the ROM option in the
PMC.
A: 64K bytes, B: 128K bytes, C: 256K bytes,
D: 512K bytes, E: 1M bytes
2 When a C board is installed in the Series 16i/18i, ladder
programs and C programs must be written into Flash
Memory separately.
(a)When a ladder program is written into Flash Memory,
select [LADDER] from the DATA KIND item.
When a C program is written into Flash Memory, select
[CLANG] from the DATA KIND item.
(b)Select [WRITE] from the FUNCTION item.
(c) Press the [EXEC] soft key to start writing to Flash
Memory.

(b) Reading data from Flash Memory


Item Operation
DEVICE Press the [FROM] soft key.
FUNCTION Press the [READ] soft key.

Press the [EXEC] soft key to start inputting data.


(c) Comparing data in Flash Memory
Item Operation
DEVICE Press the [FROM] soft key.
FUNCTION Press the [COMPAR] soft key.

Press the [EXEC] soft key to start comparing data.


(d) Checking if data is stored in Flash Memory
Item Operation
DEVICE Press the [FROM] soft key.
FUNCTION Press the [BLANK] soft key.

Press the [EXEC] soft key to check if data is stored in Flash Memory.

CAUTION
Operation in PMCNB
When data is stored in Flash Memory : BLANK ERROR is
displayed.
When no data is stored in Flash Memory : BLANK
COMPLETE is displayed.

562
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

(e) Deleting data in Flash Memory


Item Operation
DEVICE Press the [FROM] soft key.
FUNCTION Press the [ERASE] soft key.

Press the [EXEC] soft key to start deleting data.

NOTE
In FS16B/18B, [READ], [COMPAR], [BLANK] and [ERASE]
functions are unavailable.

7.3.4
Storage to a Memory : Supported
: Not supported
Card
FS21i
Power Power MateH FS21/ FS16B FS16C
FS18 FS16A FS16i FS15B
MateD/F/G FS20 210MB FS18B FS18C
FS18i

NOTE
This function is not supported on DPL/MDI of Power
MateH.

Sequence programs and data are input from or output to a memory card
as described below. The memory card to which data is input from or
output to can directly send or receive data to or from the programming unit
(FANUC LADDER).
The supported function and the kind of memory card is shown as below.
Any kind of card has to be conformed to TYPE 1 to 2 of PCMCIA (The
Personal Computer Memory Card International Association ) 2.0 (or
later) or TYPE 1 to 2 of JEIDA (Japanese Electronics Development
Association) 4.0 (or later) . And the format is based on MSDOS FAT file
system.

NOTE
With the Power MateH, FS20, FS21/210MB, FS16A,
FS18A, FS16B, FS18B, FS16C, FS18C, and FS15B,
cards having a capacity of more than 32M bytes cannot be
used.

563
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

The case of FS20,FS18B,FS16B FS18C, FS16C PMC


: Supported
: Not supported
Flash Memory
SRAM Card ATA Card
Card
Read of a file
Format of a card
Write of a file
Delete of a file
List of a file

The case of FS15B(PMCNB)


: Supported
: Not supported
Flash Memory Card
SRAM Card Supported Unsupported ATA Card
Card Card
Read of a file
Format of a card
Write of a file
Delete of a file
List of a file

The case of FS16i, FS18i, FS21i


: Supported
: Not supported
Flash Memory Card
SRAM Card Supported Unsupported ATA Card
Card Card
Read of a file
Format of a card
Write of a file
Delete of a file
List of a file

(1) Flash memory card writing


The following kinds of flash memory card are supported.
S Intel Series 2 Flash Memory Cards (or compatible cards)
Attribute memory is needed for any card.
Files can be written on the card that is formatted by MSDOS. But
there are following limitations.
S It is impossible to alter a file that is already written.
S A card that is formatted by Flash File System can not be used.
(Neither Read nor List)
S The data can not be written in the last 128Kbyte of the card. So,
available size of a card is (Card_size 128Kbyte). Please refer to
the following figure.

564
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

Before Writing

FileA

FileB

FileC

Add
FileD

128Kbyte

After writing

FileA

FileB

FileC

FileD

128Kbyte

CLOSE ERROR is displayed and FileD cannot be saved.


In the part of the ,the data of FileD is written. But read and
list functions are not available for FileD.
After this operation, any file cannot be written to this card.
There are following limitations due to the system that formats the
flash memory card.

565
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

(a) When the card formatted and written files by FANUC products
is used by other systems.
Ramuzou CardPro
Note1) Note2)
Read of a file
Add of file Not supported function
List of file

NOTE
1 Ramuzou is a memory card reader/writer that is made by
ADTEK SYSTEM SCIENCE.
2 CardPro is a memory card reader/writer that is made by
Data I/O.

(b) When the card formatted and written files by other system is used
by FANUC products.
CardPro
Ramuzou
Note3)
Read of a file
Add of file
List of file

NOTE
If you use the CardPro to format a flash memory card, type
the following command.
CPFORMAT drivename: /F:FLASHFAT /NOCIS

566
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

(2) Operation
The operation is almost the same as Subsection 7.3.2 except that steps
(a) and (b) are not necessary for a memory card.

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1

DEVICE = MCARD

DATA KIND = PARAM


(ALL:LADDER + LANGUAGE)
FUNCTION = WRITE

FILE NO. = 1
(1:ADD, 0:INIT, OR@ NAME)
>
ALM
[MCARD] [OTHER] [ ] [ ] [ ]

(a) Formatting the memory card


Item Operation
DEVICE Press the [MCARD] soft key.
FUNCTION Press the [FORMAT] soft key.

Press the [EXEC] soft key to start formatting.


(b) Writing a file
Item Operation
DEVICE Press the [MCARD] soft key.
FUNCTION Press the [WRITE] soft key.
DATA KIND Select the type of data to be output.
(See (3) in Section 7.2)
FILE NO. Name the file within 8 characters. 1 is displayed if no name is entered.
(See (5) in Section 7.2)

Press the [EXEC] soft key to start outputting the file.


If the file name is not specified, the system names the file as follows:

DATA KIND File name The model name is PMCNB


for the PMCNB and PMCRA
ALL modelname.ALL
for the PMCRA1 or RA3.
LADDER modelname.LAD
PARAM modelname.PRM

(c) Reading a file


Item Operation
DEVICE Press the [MCARD] soft key.
FUNCTION Press the [READ] soft key.
FILE NO. Enter the number or name of the file to be input.

Press the [EXEC] soft key to start inputting the file.

567
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

(d) Collating a file


Item Operation
DEVICE Press the [MCARD] soft key.
FUNCTION Press the [COMPAR] soft key.
FILE NO. Enter the number or name of the file to be collated.

Press the [EXEC] soft key to start collating the file.

CAUTION
PMC data cannot be collated.

(e) Deleting a file


Item Operation
DEVICE Press the [MCARD] soft key.
FUNCTION Press the [DELETE] soft key.
FILE NO. Enter the number or name of the file to be deleted.

Press the [EXEC] soft key to start deleting the file.


(f) Listing the files
Item Operation
DEVICE Press the [MCARD] soft key.
FUNCTION Press the [LIST] soft key.

Press the [EXEC] soft key to start listing the files.

568
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.3.5
Data Input to and : Supported
Output from other : Not supported

Devices Power
FS20
FS21/
FS18 FS16 FS18B FS16B
FS16C
FS21i
FS16i FS15B
Mate 210MB FS18C
FS18i

Reads or writes the sequence program, Pascal or C programs, or PMC


data.

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1

DEVICE = OTHERS

DATA KIND = ALL


(ALL:LADDER + LANGUAGE)
FUNCTION = WRITE

>
ALM
[MCARD] [OTHERS] [SPEED ] [ ] [ ]

(a) Setting the channel


Enter the number of the channel used at CHANNEL = . See (a) in
Subsection 7.3.1 for details.
(b) Setting the transfer conditions
Press the [SPEED] soft key and set each condition. See Subsection
7.3.6 for details.
(c) Outputting data (PMC to input/output device)
Item Operation
DEVICE Press the [OTHERS] soft key.
FUNCTION Press the [WRITE] soft key.
DATA KIND Select the type of data to be output (see (3) in Section 7.2).
Set the input/output device so that it is ready to accept data (wait state).

Press the [EXEC] soft key to start outputting data.


(d) Inputting data (input/output device to PMC)
Item Operation
DEVICE Press the [OTHERS] soft key.
FUNCTION Press the [READ] soft key.
Press the [EXEC] soft key and wait until data input finishes.

The input/output device starts outputting data.

569
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

CAUTION
If DATA ERROR is displayed when a C program is written
with the Series 16i/18i, perform the following:
1 Clear the C language area by pressing soft keys [EDIT],
[CLEAR], [CLRLNG], then [EXEC].
2 Read the C program again.
3 On the system parameter screen, set LANGUAGE
ORIGIN.
4 Write the C program into flash ROM.

(e) Collating data


Item Operation
DEVICE Press the [OTHERS] soft key.
FUNCTION Press the [COMPAR] soft key.
Press the [EXEC] soft key and wait until data collation finishes.

The input/output device starts outputting data.

NOTE
PMC data cannot be collated. The data the file is to be
collated with depends on the file.

7.3.6
Setting the Transfer : Supported
: Not supported
Speed ([SPEED] Soft FS21i
Power FS21/ FS16C
Key) Mate
FS20
210MB
FS18 FS16 FS18B FS16B
FS18C
FS16i FS15B
FS18i

PMC SPEED OTHERS MONIT STOP


BAUD RATE = 3
(0:1200,1:2400,2:4800,3:9600,4:19200)

PARITY BIT = 0
(0:NONE,1:ODD,2:EVEN)

STOP BIT = 1
(0:1BIT,1:2BIT)

WRITE CODE = 1
(0:ASCII,1:ISO)
>
ALM
[INPUT ] [ ] [ ] [ ] [ INIT ]

570
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

The items shown above must be set when RS232C is used for
communication. Move the cursor to each item and enter a number.
Pressing the [INIT] soft key sets each item to the initial value. WRITE
CODE = is displayed only when OTHERS is selected for DEVICE.
The table below lists the setting for communication with a FANUC
LADDER.
Setting on the
Setting on the PMC
Item personal
(SPEED screen)
computer
Baud rate (bps) 9600 BAUD RATE = 3 (9600bps)
Character length 8 bits
Parity check No parity PARITY BIT = 0 (NONE)
Number of stop bits 2 bits STOP BIT = 1 (2BIT)
X parameter None

7.3.7
Transfer to and from a : Supported
ROM WRITER : Not supported
FS21i
Power FS21/ FS16C
FS20 FS18 FS16 FS18B FS16B FS16i FS15B
Mate 210MB FS18C
FS18i

Reads or writes the sequence program, Pascal or C programs, or PMC


data.
This function is valid for the builtin programer function.
(a) Writing a file
Item Operation
DEVICE Press the [ROMWRT] soft key.
FUNCTION Press the [WRITE] soft key.

Press the [EXEC] soft key to start outputting the data.


(b) Reading a file
Item Operation
DEVICE Press the [ROMWRT] soft key.
FUNCTION Press the [READ] soft key.

Press the [EXEC] soft key to start inputting the data.


(c) Collating a file
Item Operation
DEVICE Press the [ROMWRT] soft key.
FUNCTION Press the [COMPAR] soft key.

Press the [EXEC] soft key to start collating the data.

571
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

7.3.8 When the machine tool builder creates a MDI keyboard which has no
Notes on Using an MDI cursor keys on the PMCMODEL SA1/SA3 of the FS 20, note the
following methods of operation. Ladder diagrams cannot be edited using
Keyboard without the ladderdiagramedit memory card.
Cursor Keys
On each setting screen, when an item is specified, the cursor automatically
(when using the FS20
moves to the next item to be specified. When the item at the cursor need
PMCMODEL SA1/SA3) not be modified, specify the same value again. When the item at the
bottom of the screen has been specified, the cursor automatically moves
to the item at the top of the screen (CHANNEL setting). When the return
key (leftmost soft key) is pressed to exit from the I/O screen, the cursor
automatically moves to the top of the screen. Examples of setting items
are shown below.
Example 1) When a ladder program is output to an offline programmer
(such as the PG or a personal computer)
1 CHANNEL setting : Enter the desired channel number,
then press the <INPUT> key or
[(NO.)] key. To use the current value,
just press the <INPUT> key or
[(NO.)] key.
2 DEVICE setting : Press the [HOST] key. The cursor
returns to the CHANNEL setting
position to enable CHANNEL
setting.
Example 2) When a ladder program is written into an FROM
1 CHANNEL setting : No specification required. To move
the cursor, perform the operation
described in 1 of Example 1.
2 DEVICE setting : Press the [FROM] key.
3 FUNCTION setting : No specification required. To change
the CHANNEL setting, press the
[WRITE] key to return the cursor to
the CHANNEL setting position.
Example 3) When a ladder program or a PMC parameter is read from or
written into an FDCAS (MCARD)
1 CHANNEL setting : See 1 of Example 1 (or 1 of Example
2).
2 DEVICE setting : Press the [FDCAS] ([MCARD]) key.
3 DATA KIND setting: Press the [LADDER] key for ladder
operation. Press the [PARAM] key
for PMCparameter operation.
4 FUNCTION setting : Press the [READ]/[WRITE] key.
5 FILE NO. setting : Enter the desired file number or file
name, then press the <INPUT> key or
[EXEC] key. When the current value
is used, just press the <INPUT> key.
The cursor automatically returns to
the CHANNEL setting position. The
setting can be modified.
In each example, pressing the [EXEC] key after setting data executes the
corresponding processing.

572
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.4
I/O ERROR
MESSAGES
Message CONTENTS OPERATION
PROGRAM ALREADY EXISTS A program is already stored in the FLASH ROM (during blank check).
PROGRAM ALREADY EXISTS (EXEC ?) A program is already stored in the FLASH ROM (during writing or deleting data).
Action) Press the EXEC key again when the message is displayed. Data is then written
or deleted.
PROGRAM NOTHING No program is in the FLASH ROM.
ERASE ERROR The FLASH ROM is faulty and must be replaced. Consult your FANUC service office.
F
L WRITE ERROR
S
H READ ERROR
ANOTHER USED The FLASH ROM is being used by a device other than the PMC.
R
O MUST BE IN EMG STOP NOT EMG STOP The CNC is not in the emergency stop state.
M
NO OPTION There is no ROM cassette option.
SIZE ERROR The size of the program exceeds the FLASH ROM size (during writing of the sequence
program).
Action) Use the CONDENSEM function (EDIT/CLEAR screen). If the error persists, the
FLASH ROM size must be increased.
The size of the program exceeds the RAM size (during reading of the sequence program).
Action) The RAM size must be increased.
I/O OPEN ERROR nn nn = 1: The RS232C interface is being used by a device other than the PMC.
Action) Check if another device is using the RS232C interface.
Check that, on the online setting screen (Section 8.5.1 in Part III), NOT USE is
set for the RS232C item.
nn = 6: There is no RS232C option.
nn = 20: The RS232C interface is connected incorrectly.
Action) Check that the connection and the setting, such as channel and baud rate, are
H correct.
O
S I/O WRITE ERROR nn nn = 20: The RS232C interface is connected incorrectly.
T Action) Check that the connection and the setting, such as channel and baud rate, are
. correct.
F nn = 22: Communication cannot be performed normally.
D Action) Check if a cable is disconnected.
C
A I/O READ ERROR nn nn = 20: The RS232C interface is connected incorrectly.
S Action) Check that the connection and the setting, such as channel and baud rate, are
. correct.
O nn = 22: Communication cannot be performed normally.
T Action) Check if a cable is disconnected.
H ADDRESS IS OUT OF RANGE (xxxxxx) Data other than that stored in the PMC debugging RAM area has been transferred.
E xxxxxx: Transfer address
R
S DATA ERROR Invalid data was read.
Action) Check the cable and setting (SPEED).
When a C program is read into the Series 16i/18i:
Action) Clear the C language area by pressing soft keys [EDIT], [CLEAR], [CLRLNG],
then [EXEC].
PROGRAM DATA ERROR Data output contains an error
Action) On the alarm screen, check the details of the alarm.

573
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

Message CONTENTS OPERATION


CREATE ERROR The file name is invalid.
Action) Name the file is the MSDOS format (see(5) of Section 7.2).
NO MORE SPACE The memory card capacity is insufficient.
WRITE ERROR Action) Replace the memory card or delete unnecessary files and retry.
NOT READY The memory card is not mounted.
Action) Confirm if the memory card is mounted correctly.
MOUNT ERROR The memory card is not formatted.
Action) Format the memory card (see (a) of Subsection 7.3.4).
WRITE PROTECT The memory card is protected.
Action) Remove the protection of the memory card.
BATTERY ALARM The battery of the memory card is not enough.
M Action) Exchange the battery of the memory card.
E
M FILE NOT FOUND Specified file number or file name is not found.
O Action) Confirm the file number or the file name by LIST.
R DELETE ERROR The file cannot be deleted.
Y Action) Change the attribute of the file.
C PROGRAM ALREADY EXISTS The file name already exists.
A Action) Change to other file name.
R
D I/O WRITE ERROR nn nn=30 : The memory card is not mounted.
I/O READ ERROR nn Action) Confirm if the memory card is mounted correctly.
I/O COMPARE ERROR nn nn=31 : The data cannot be written to the memory card.
I/O DELETE ERROR nn Action) Remove the protection of the memory card.
I/O LIST ERROR nn Exchange the memory card for the SRAM card.
I/O FORMAT ERROR nn nn=32 : The battery of the memory card is not enough.
Action) Exchange the battery of the memory card.
nn=102: The memory card capacity is insufficient.
Action) Replace the memory card or delete unnecessary files and retry.
nn=135: The memory card is not formatted.
nn=105: ditto
Action) Format the memory card.
nn=114: Specified file is not found.
Action) Confirm the file number or the file name by LIST.
nn=115: Specified file is protected.
Action) Confirm the attribute of the file.

R SIZE OVER WRITE The ROM size is smaller than the program size.
O Response) Increase the ROM size.
M

W
R ROM WRITER ERROR nnnnn An error has occurred in the ROM writer.
I Response) Refer to the ROM Writer Operators Manual.
T
E
R
COMPARE ERR XXXXXX = AA:BB The data between DEVICE and PMC is different.
CONT?(Y/N) XXXXXX : Address
aa : The data in PMC
bb : The data in DEVICE
C Action) If you continue it, press Y key.
o Otherwise, press N key.
m DATA ERROR Invalid data was read.
m Action) Check the cable and setting (SPEED).
o When a C program is read into the Series 16i/18i:
n Action) Clear the C language area by pressing soft keys [EDIT], [CLEAR], [CLRLNG],
then [EXEC].
PROGRAM DATA ERROR Data output contains an error.
Action) On the alarm screen, check the details of the alarm.

574
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
B61863E/14 PMC PROGRAMMER (CRT/MDI) PMC PARAMETER DATA

7.5 The data items of the sequence program stored in EPROM can be copied
into the debugging RAM module for PMCSA1, PMCSA2, PMCSB,
SEQUENCE and PMCSB2.
PROGRAM COPY
The following shows the relationship between the function and soft keys.
FUNCTION
RUN EDIT I/O SYSPRM MONIT

RETURN

EXEC CANCEL (NO.)

NEXT

ROM COPY

CPYTTL CPYLAD CPYSYM CPYMSG

NEXT

CPYALL CPYMDL

7.5.1 Copies title data.


Copy Title Data
[CPYTTL]

7.5.2 Copies a ladder program.


Copy a Ladder
Program [CPYLAD]

7.5.3 Copies symbol data and comment data.


Copy Symbol Data and
Comment Data
[CPYSYM]

7.5.4 Copies message data.


Copy Message Data
[CPYMSG]

575
7. WRITING, READING, AND VERIFYING
THE SEQUENCE PROGRAM AND
PMC PARAMETER DATA PMC PROGRAMMER (CRT/MDI) B61863E/14

7.5.5 Copies all the sequence programs into the debugging RAM.
Copy the Sequence
Programs [CPYALL]

7.5.6 Copies I/O module data.


Copy I/O Module Data
[CPYMDL] CAUTION
If the I/O module data is different from the currently selected
data during copying in Subsection 7.5.5 or 7.5.6, turn off the
power and restart the system.

7.6 Two channels cannot be used for the reader/punch interface at the same
time. Before performing these I/O operations, be sure to terminate the
RESTRICTIONS system other than the PMC and processing through the reader/punch
interface in the PMC program.

576
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8 FUNCTIONS FOR DISPLAYING MEMORY AREAS AND


DEBUGGING THE PROGRAM (MONIT)

Press the [MONIT] soft key on the basic programmer menu to display the
basic monitor menu shown in Fig. 8. Pressing an appropriate soft key
enables the user to display memory areas used for a user program written
in the C language or to debug a program.
f : Can be used
: Cannot be used
: Can be used (with some restrictious)
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SC SC3 SC4 NB NB2

Work RAM is necessary (A02B0120H987 for the PMCSC, SC3, and


SC4 and A02B0162J151 or A02B0162J152 for the PMCNB and
NB2).
These functions facilitate debugging a user program created by the
machine tool builder in the C language. If the settings are erroneous, a
system error may occur or the system may be shut down. Specify the
settings correctly.
For details of operation, refer to the PMCSC/SC3/SC4/NB/NB2
Programming Manual (C language) (B61863E1).
The following figure shows the soft key related to these functions.

RUN EDIT I/O SYSPRM MONIT


(STOP)
RET

DBGLAD GDT USRMEM DEBUG

III 8.4 III 8.1 III 8.2 III 8.3

PMC MONITOR MENU MONIT STOP

SELECT ONE OF FOLLOWING SOFT KEYS

DBGLAD : DEBUG LADDER DIAGRAM


GDT : DESCRIPTOR TABLE MAP
USRMEM : USER MEMORY INFORMATION
DEBUG : DEBUG FUNCTION

[DBGLAD] [ ONLINE ] [ GDT ] [USRMEM] [DEBUG ]

Fig. 8 Basic monitor menu

577
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.1 Information of a User Program Coded in C


DISPLAYING THE GDT Nos. 32 to 95 defined in a user program can be displayed.
GDT (GLOBAL The specified GDTs can also be dumped.
DESCRIPTOR TABLE) The following figure shows the soft keys related to this function.

GDT USRMEM DEBUG

RET

NO.SRH M.DUMP

RET

SEARCH INPUT

NEXT

BYTE WORD D.WORD

8.1.1 (1) Press the [GDT] soft key to display the user GDT information shown
in Fig. 8.1.1 (a).
Operation
(2) Use the [NO. SRH] key to search for the GDT table with a desired
number.
(3) Press the [M. DUMP] key to dump the data of the GDT number which
is displayed at the top.
(4) Press the [NEXT] key on the memory dump screen.
Pressing the [BYTE] key displays the data in units of bytes.
Pressing the [WORD] key displays the data in units of words, where
one word equals two bytes. Pressing the [D. WORD] key displays
the data in units of double words, or four bytes.
See Fig. 8.1.1 (b).
(5) When bit 4 of keep relay K17 is set to 1, the contents of RAM can be
changed in units of the specified length on the memory dump screen
by moving the cursor to the data to be changed.

WARNING
Depending on the settings, a user program may operate
erroneously, causing a system error. Be sure to specify the
correct settings.

578
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

PMC DESCRIPTOR TABLE(GDT) MONIT RUN

NO. ACCESS USE BASE LIMIT


032 RW 16 0016000AH 0000056FH
033 RW 16 0016005AH 0000023FH
034 RW 16 00160300H 00000040H
035 RW 16 00160340H 00000234H
036 ER 16 00823000H 00000058H
037 ER 16 0084FB7CH 0000070AH
038 NULL DESCRIPTOR
039 ER 16 0084FF88H 0000292FH
040 RW 16 00160A6CH 0000005AH
041 RW 16 00160600H 00000402H
>

[NO.SRH] [ ] [ ] [M.DUMP] [ ]

Fig. 8.1.1(a) User GDT information

PMC DESCRIPTOR TABLE(GDT) MONIT RUN

NO. ACCESS USE BASE LIMIT


032 RW 16 0016000AH 0000056FH
033 RW 16 0016005AH 0000023FH
Y Y
[NO.SRH] [ ] [ ] [M.DUMP] [ ]

PMC MEMORY DUMP(GDT NO.032) MONIT RUN

103:0000 0000 0000 0000 0000 0000 ......


103:0010 0000 0000 0000 0000 0000 ......
103:0020 0000 0000 0000 0000 0000 .....
Dumped
information of
GDT NO.32

Fig. 8.1.1(b) Memory dump

579
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.1.2
Descriptions of
Displayed Items

NO. ACCESS USE BASE LIMIT


32 ER 16 00862340H 0000523FH

Segment limit

Segment base

Segment type

Segment attribute

GDT NO.

(1) Access attribute of a segment


Code Description
RO Readonly data segment
RW Read/write data segment
ROD Readonly downwardexpansion data segment
RWD Read/write downwardexpansion data segment
EO Executeonly code segment
ER Execute/read code segment

(2) Segment type


Code Description
16 16bit segment
32 32bit segment

NOTE
A user program created with the IC286 compiler is
segmented in 16bit units.

(3) Undefined segment


NULL DESCRIPTOR is displayed for an undefined segment.

580
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.2 The segment information of the following areas defined by a user program
for each task can be displayed and the contents of the areas can be dumped.
DISPLAYING THE
MEMORY D Data area
ALLOCATION D Stack area
INFORMATION OF A D Common memory area
USER PROGRAM The PMC management software dynamically allocates the areas
mentioned above at locations which are different from those defined by
CODED IN C. the user program.
The system allocates the data area at activation. When the system is not
activated after the user program has been loaded, the data area is located
at the address defined by the user program. Be sure to refer to the area after
the system starts.
The following figure shows the soft keys related to this function.

GDT USRMEM DEBUG

RET

TASK.D TASK.S COM.D M.DUMP

RET

SEARCH INPUT

NEXT

BYTE WORD D.WORD

8.2.1 (1) Press the [USRMEM] soft key. Depending on which soft key is
pressed next (see below), the task memory information of a user
Operation program is displayed on the screen as shown in Fig. 8.2.1 (a) to (c).
Soft keys
[TASK. D] : Displays the information of allocating task data.
[TASK. S] : Displays the information of allocating task stacks.
[COM.D] : Displays the information of common memory
allocation.
(2) A task data area and stack area are displayed for each task ID. The
information for all the common memory defined by user link control
statements is displayed.
(3) Pressing the [M. DUMP] key on each allocation information screen
enables the contents of the memory related to the item which is
displayed at the top to be dumped.
(4) Operation on the memory dump screen is the same as that described
in Section 8.1.
(5) When bit 4 of keep relay K17 is set to 1, the contents of RAM can be
changed in units of the specified length on the memory dump screen
by moving the cursor to the data to be changed.

581
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

CAUTION
Depending on the settings, a user program may operate
erroneously, causing a system error. Be sure to specify the
correct settings.

PMC USER MEMORY(TASK DATA) MONIT RUN

ID NAME GDT BASE LIMIT


10 TASKO01 039 00160050H 00010100H
11 TASKO02 040 00160060H 00004100H
12 TASKO03 041 00160070H 00005100H
13 TASKO04 042 00160080H 00000160H
14 TASKO05 043 00160210H 00000170H
15 TASKO06 044 00160110H 00000110H

>

[TASK.D] [TASK.S] [COM.D ] [M.DUMP] [ ]

Fig. 8.2.1(a) Information of a task data area

PMC USER MEMORY(TASK STACK) MONIT RUN

ID NAME GDT BASE LIMIT


10 TASKO01 239 00161050H 00010100H
11 TASKO02 240 00161060H 00004100H
12 TASKO03 241 00161070H 00005100H
13 TASKO04 242 00161080H 00000160H
14 TASKO05 243 00161210H 00000170H
15 TASKO06 244 00161110H 00000110H

>

[TASK.D] [TASK.S] [COM.D ] [M.DUMP] [ ]

Fig. 8.2.1(b) Information of a task stack area

582
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

PMC USER MEMORY(COMMON DATA) MONIT RUN

NO. GDT BASE LIMIT


01 042 00162010H 00000100H
02 045 00162020H 000A0100H
03 047 00162030H 0000D000H
04 048 00162040H 0000A100H

>

[TASK.D] [TASK.S] [COM.D ] [M.DUMP] [ ]

Fig. 8.2.1(c) Information of a common memory data area

8.2.2 (1) Items displayed for a task data area and stack area
Displayed Items

ID NAME GDT BASE LIMIT


10 TASK001 032 00160010H 00000100H

Segment limit

Segment base

GDT No.

Task name

Task ID

(2) Items displayed for a common memory area

NO GDT BASE LIMIT


01 032 00160010H 00000100H

Segment limit

Segment base

GDT NO.

Common memory No.

583
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.3 There are two ways to check if a user program operates as intended. One
is to execute the program while displaying the sequence on an external
DEBUGGING unit such as a display monitor. The other is to execute the program to a
specified point (breakpoint), and check if the internal data items such as
program work areas are correct.
This PMC debugging function checks programs using breakpoints.

8.3.1 (1) Number of breakpoints: Up to 4


Specifications (2) Number of portions to be traced: 8
(3) Capacity of memory used for storing traced data: Up to 256 bytes,
up to 32 bytes for each traced portion

8.3.2 Press the [DEBUG] soft key to display the parameter screen for
Operation debugging. Pressing the [D.DUMP] key on the parameter screen displays
the contents of the CPU registers and specified internal data items at the
breakpoint.
To return from the data display screen to the parameter screen, press the
[D.PRM] soft key.
After the parameters are set, but before the program is interrupted, DBG
blinks at the bottom right of the PMC screen. The breakpoint numbers
BP1 to BP4 are also displayed at the bottom of the debug function screen.
When the program is interrupted at a breakpoint, BRK blinks at the
bottom right of the PMC screen. At this time, the breakpoint number,
from BP1 to BP4, is displayed in reverse at the bottom of the debug
function screen.
The following figure shows soft keys related to this function.

GDT USRMEM DEBUG

RET

D.DUMP BRK.NO EXEC INIT

RET

D.PRM BRK.NO

584
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.3.3 When the debug function is used, it is necessary to set the break conditions
Parameter Screen on the parameter screen. When using a 9 screen, press the <PAGE> key
to set a trace data area for a breakpoint.
(1) Setting parameters
(a) BREAK SEG.ADR
Specify the effective address of the breakpoint using a segment
address. When data is accessed, specify the break address using
a segment address.
Use a key, such as EOB, to delimit a segment and an offset. Do
not use alphanumeric keys.

NOTE
In data access, an even boundary or 4byte boundary is
assumed according to the type of ACCESS LENGTH,
described later.
Example)
When the break address is GDT.NO = 32,
OFFSETADDRESS = 101, specify 103; 101, obtained using
the following formula:
32 (GDT.NO) x 8 + 3 = 259 = 103 (Hex)
S When ACCESS LENGTH = WORD is specified with
BREAK SEG.ADR = 103; 101
An access to 103; 100101 causes a break.
S When ACCESS LENGTH = D.WORD is specified with
BREAK SEG.ADR = 103; 101
An access to 103; 100103 causes a break.

(b) BREAK COND.


Specify a break condition.
0 (EXEC) : A program is interrupted at the specified
effective address.
1 (WRITE) : A program is interrupted when it writes
data to the specified address.
2 (READ/WRITE) : A program is interrupted when it writes
data to or read data from the specified
address.
(c) ACCESS LENGTH
Specify the address type of a breakpoint.
0 (BYTE) : An address is specified in units of bytes for
read/write operation at the specified address
and for when a program is interrupted at the
specified effective address.
1 (WORD) : An address is specified in units of words for
read/write operation at the specified address.
2 (D.WORD) : An address is specified in units of two words
for read/write operation at the specified
address.
(d) PASS COUNT
Specify the number of times a break condition is satisfied before
the program is interrupted, in the range of 1 to 65535.

585
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

(e) TASK ID
Specify the task ID of a program. This parameter is convenient
for identifying the program when it is to be interrupted at a
breakpoint located in a function called from multiple tasks or is
located in common memory.
(f) TASK STATUS
Specify how to handle the task when a program is interrupted.
0 (PASS) : The task continues after the program is
interrupted.
1 (STOP) : The user task stops when the program is
interrupted. The ladder program does not stop.

CAUTION
To restart the user program, press the [STOP] key to stop
the sequence program and then press the [RUN] key to start
the program on the basic menu using the RUN/STOP
function.

(g) BREAK AVAIL.


Specify whether the parameters for each breakpoint are valid or
invalid.
(h) NO. TRACE ADR.
Using segment addresses, specify up to eight addresses from
which data is traced when a program is interrupted at a
breakpoint. Up to 32 bytes are stored for each address.
Use a key, such as EOB, to delimit a segment and an offset. Do
not use alphanumeric keys.
To initialize these addresses only, enter 0; 0.

CAUTION
If the addresses are specified erroneously, the following two
items, TYPE and LENGTH, cannot be specified.

(i) TYPE
Specify an address type with which traced data is displayed.
0 (BYTE) : Data is displayed in units of bytes.
1 (WORD) : Data is displayed in units of words.
2 (D.WORD) : Data is displayed in units of double words.
(j) LENGTH
Specify the length of traced data to be displayed.
(2) Starting processing for a breakpoint
When the parameters for each breakpoint are correctly specified,
press the [EXEC] soft key on the parameter screen to start the
processing for the currently selected breakpoint. The breakpoint
number, from BP1 to BP4, is displayed at the bottom of the screen.
(3) Initializing data used for debugging
To initialize the parameters and memory used for storing traced data,
press the [INIT] soft key on the parameter screen. The parameter and
memory for the currently selected breakpoint are then initialized.

586
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

(4) Changing a breakpoint


Up to four breakpoints can be specified. For each breakpoint,
parameters are specified and traced data is stored. To select a desired
breakpoint, press the [BRK.NO] soft key on the parameter screen.
The breakpoint is selected in the order of BP1, BP2, BP3, and BP4.

PMC DEBUG (PARAM) MONIT RUN

BREAK POINT NO.1

BREAK SEG.ADR = 0000:00000000


BREAK COND. = 0 ( 0:E 1:W 2:RW )
ACCESS LENGTH = 0 ( 0:B 1:W 3:D )
PASS COUNT = 32767
TASK ID = 1 ( 0:ALL / 1025 )
TASK STATUS = 0 ( 0:PASS 1:STOP )
BREAK AVAIL. = 0 ( 0:NO 1:YES )

>

[D.DUMP] [BRK.NO] [ EXEC ] [ INIT ] [ ]

Fig. 8.3.3 (a) Screen for specifying a break condition

PMC DEBUG (PARAM) MONIT RUN

BREAK POINT NO.1


NO. DUMP ADR. TYPE LENGTH
(0:B/1:W/2:D) (32BYTE)
01 0000:00000000 0 10
02 0000:00000000 1 9
03 0000:00000000 2 8
04 0000:00000000 0 7
05 0000:00000000 1 6
06 0000:00000000 2 5
07 0000:00000000 0 4
08 0000:00000000 1 3
>

[D.DUMP] [BRK.NO] [ EXEC ] [ INIT ] [ ]

Fig. 8.3.3 (b) Screen for specifying data to be traced

587
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.3.4 When a program is interrupted under the break condition specified on the
Screen for Displaying parameter screen, BRK blinks at the bottom right of the PMC screen. The
breakpoint number at which the program has been interrupted is displayed
Traced Data in reverse at the bottom of the debug function screen.
To display the traced data, press the [D.DUMP] soft key on the parameter
screen, then press the [BRK.NO] key to select the screen for displaying
the traced data corresponding to the breakpoint.
The following items are displayed.
(1) REGISTER
Displays the contents of the CPU registers.
(2) MEMORY
Displays the contents of memory at addresses of the traced data
specified on the parameter screen.
When the contents are displayed on multiple pages, scroll the screen,
if necessary, using the <PAGE>, <PAGE>, <>, or, <> key.

PMC DEBUG (DUMP) MONIT RUN


BREAK POINT NO.1(0000:00000000)
REGISTER
EAX=00000000 EBX=00000000 ECX=00000000
EDX=00000000 ESI=00000000 EDI=00000000
EBP=00000000 ESP=00000000 IEP=00000000
DS=0000 ES=0000 FS=0000 GS=0000
SS=0000 CS=0000 EFLAGS=00000000
CONTENS OF MEMORY
01 0000:00000000 00000000 00000000
02 0000:00000000 00000000 00000000
03 0000:00000000 00 00 00 00 00 00 00 00
04 0000:00000000 0000 0000 0000 0000
>

[D.PRM ] [BRK.NO] [ ] [ ] [ ]

Fig. 8.3.4 Screen for displaying traced data

8.3.5 As parameters used for debugging and traces data are stored in the
retained memory, they are not lost when the power is turned off.
Enabling Automatic
Debugging at When bit 1 of keep relay K18 is set to 1 after break condition parameters
Poweron are correctly specified, debugging is automatically enabled when the
power is turned on.

8.3.6 (1) Specify a break address (BREAK SEG.ADR) in the area used by the
user program.
Notes
If a break address is specified in the area which is used by the PMC
management software, the system may hang up.
(2) Debug function is incorporated in the CPU, reduces the CPU speed.
Do not use the function during normal system operation.

588
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.4
LADDER : Can be used
: Cannot be used
DEBUGGING : To use this function, a ladder editing module is required
FUNCTION PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2

NOTE
PMCPA3 is usable with the Power MateH.

Using this function, Step Operations and Stop Operations listed below are
possible. Step Operations are to execute ladder by specified step (single
instruction, single net, and specified block). Stop Operations are to stop
the execution of ladder when specified condition becomes true.
(1) Step Operation to execute one instruction from current position.
(2) Step Operation to execute one net (one circuit) from current position.
(3) Step Operation to execute from current position to specified contact
or coil instruction.
(4) Stop Operation to execute from the first step and stop the execution
at specified contact or coil instruction.
(5) Stop Operation to stop the execution of ladder by a trigger of signal
condition. (Optionally, a trigger counter can be specified.)
(6) Stop Operation to stop the execution of ladder after executing one
scan. (Optionally, a scan counter can be specified.)

8.4.1
Screen of Ladder
Debugging Function LADDER *TITLE DATA REMARKS 32 BYTES * NET 0000100004 MONIT RUN

X1000.0 Y1000.0
X1000.1 Y1000.1
ABSDE
SUB36 2
X1000.0 RST ADDB Y1000.3
D0000
[ 0]
FGHI ACT 1
D0000
[ 0]

X1000.0 Y1000.5

ACC=1 STK=0000 0011 OF=0 SF=1 ZF=1

[SEARCH ] [ STEP ] [ BRKCTL ] [ ] [ DUMP ]

[ RUN ] [ ADRESS ] [ DPARA ] [ONLEDT ] [ RESET ]

Fig. 8.4.1 Screen of ladder debugging function

589
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.4.2 For this operation, press [DBGLAD] soft key to bring the following
Soft Key Menu of menu.
Ladder Debugging
Function DBGLAD ONLINE GDT USRMEM DEBUG

RET

SEARCH STEP BRKCTL DUMP

Subsec. 8.4.3 Subsec. 8.4.3 NEXT

RUN ADRESS DPARA ONLEDT RESET


(STOP) (SYMBOL) (NDPARA)

The function of the soft key is as follows.


(1) [SEARCH] : is used to specify several types of search functions.
(2) [STEP] : is used to specify several types of Step Functions.
This function can not be used when the ladder
program is being executed.
(3) [BRKCTL] : is used to specify Stop Functions.
This function is to stop the execution of ladder when
specified condition becomes true. This function can
not be used when the ladder program is being
executed.
(4) [DUMP] : is used to display the contents of PMC address in the
2 lines at the bottom of CRT where the last NET is
normally displayed.
(5) [RUN] : is used to switch the monitor mode from STOP to
RUN, or vice versa.
(6) [ADRESS] : is used to switch the symbol display mode from
SYMBOL to ADDRESS, or vice versa.
(7) [DPARA] : is used to switch the mode for displaying the
contents of functional instruction parameters from
NDPARA (No Display Parameter) mode to DPARA
(Display Parameter) mode, or vice versa.
(8) [ONLEDT] : is used to edit the ladder program without stopping
the execution. Editing is limited within the
operations which do not change the size of ladder.
(9) [RESET] : is used to initialize the Step Function and Stop
Function.

NOTE
See Chapter II. 5.3 and 5.4 for details of (7) or (8).

590
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.4.3 Using this function, Step Operations such as single step, single net, and
Step Operation [STEP] block steps until specified instruction are possible.
[Function]
(1) Step Operation to execute one instruction from current position.
(2) Step Operation to execute one net (one circuit) from current position.
(3) Step operation to execute from current position to specified contact
or coil instruction.
[Displaying of Step] See Fig. 8.4.1
ACC=1 STK=0000 0011 OF=0 SF=0 ZF=1
ACC : result of operation
STK : contents of stack (1 byte)
OF : overflow (0=NO, 1=YES)
SF : sign (0=NO, 1=YES)
ZF : zero (0=NO, 1=YES)
For this operation, press [STEP] soft key to bring the following menu.

SEARCH STEP BRKCTL DUMP

RET

ELMMNT NETMNT BLOCK B.SRCH TRNS.B

SEARCH START

The function of the soft key is as follows.


(1) [STEP] : A blinking cursor shows the current position at
which the execution is stopped. y moving the cursor,
a position at which the execution is to be stopped can
be specified.
(2) [ELMMNT] : is used to execute one instruction from current
position.
(3) [NETMNT] : is used to execute one net from current position.
(4) [BLOCK] : is used to execute from current position to specified
instruction. If specified instruction is not executed
because it is skipped by conditional JMP or CALL
instructions, the execution will stop at the END
instruction, END1 (SUB 1), END2 (SUB 2), or
END3 (SUB 48), of the current level.
(5) [B.SRCH] : is used to search the instruction at which the
execution is currently stopped.
(6) [TRNS.B] : is used to transfer the current status of input signals
to the synchronous buffer so that succeeding
instructions could operate on refreshed inputs when
the execution is continued from current position.
(For more about the synchronous buffer, see Chapter
I.2.5 Processing I/O Signal)

591
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

CAUTION
Normally, transferring to the synchronous buffer is
automatically performed at the beginning of the 2nd level
ladder.

8.4.4 Using this function, the execution of the ladder can be stopped when
specified condition becomes true. Then, the signal condition can be
Stop Function of Break
checked.
with Condition
[BRKCTL] [Function]
(1) Stop operation to execute from the first step and then to stop at
specified contact or coil instruction. (Optionally, a trigger counter
can be specified to stop after the instruction is executed specified
times.)
(2) Stop operation to stop the execution of ladder when a trigger
condition specified by signal becomes true. (Optionally, a trigger
counter can be specified to stop after the trigger becomes true
specified times.)
(3) Stop operation to stop the execution of ladder after executing a scan.
(Optionally, a scan counter can be specified to stop after executing
specified times of scans.) The execution is started by pressing
[START] key.
[Displaying of specified trigger]

MODE :ON :X0000. 0 : 0 : 0000/12345

COUNT : trigger counter


(present counter/specified counter)
POINT : trigger point at which the trigger
condition is checked (default is 0)
0 the top of the 1st level seq
1 after END1
2 after END2
3 after END3
ADR : specified trigger address

ON : signal turn on (TRGON), OFF : turn off

[Displaying of specified scan]

SCAN COUNT : 00000/00003

counter of scan (present counter/specified counter)

592
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

SEARCH STEP BRKCTL DUMP

RET

TRIGER SCAN INIT START


(STOP)

TRGON TRGOFF

The function of [BRKCTL] soft key is as follows.


(1) [TRIGER] : is used to specify the trigger condition by signal.
Trigger condition has to be specified according to the
following syntax. And then, the execution is started by
pressing [START] key.
ADR ; PONIT (03) ; COUNT +
[TRGON/ TRGOFF]
ADR : specified trigger address
POINT : trigger point at which the trigger condition
is checked (default is 0)
0 the top of the 1st level sequence
1 after END1
2 after END2
3 after END3
COUNT : counter of checked trigger (default is 1)
(1 to 65535)
(2) [TRGON] : is used to specify turn on trigger to stop the execution
when the signal is transitioned from off to on status.
(3) [TRGOFF] : is used to specify turn off trigger to stop the
execution when the signal is transitioned from on to off
status.
(4) [DUMP] : is used to display the contents of PMC address in the
2 lines at the bottom of CRT where the last NET is
normally displayed.
(5) [SCAN] : is used to specify a stop function by scan counter. To
specify a scan counter, input as follows.
counter + [SCAN]. (counter: 1 to 65535)
When the counter is not specified, it is recognized as
1.
After specifying the scan counter, the execution is
started by pressing [START] key.
(6) [INIT] : is used to initialize the stop function with break
condition.
(7) [START] : is used to start the execution after specifying the
condition to stop.

593
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.5
f : Usable
ONLINE FUNCTION : See Note
: Not usable
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SC SC3 SC4 NB NB2

NOTE
1 PMCPA3 is usable with the Power MateD/H.
2 PMCSA1 is usable with the loader control function of the
Series 21i.
3 PMCSA3 is usable with the FANUC NC Board.
4 If the system is set up to use the online function, that line
is occupied, and cannot be used with other input/output
functions. To use the line with other input/output functions,
set up the system so as not to use the online function.
If the system is set up to use the online function, the
following functions cannot be used:
D [PMCLAD], [I/O], [EDIT], [SYSPRM], [TRACE],
[ANALYS], [USRDGN], [DGNLAD], [GDT], [USRMEM]

With the online function of the FANUC LADDERII or ladder editing


package, the following can be performed using the personal computer:
D Ladder monitor display
D Online ladder editing (This cannot be used with the PMCSA1.)
D PMC parameter display and editing
D Signal state monitor display and modifications
D Input/output to and from the PMC (loading from the PMC, storing to
the PMC)
D Writing to flash ROM
Before this online function can be used, communication conditions must
be set in the PMC built into the CNC.

594
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.5.1
Online Setting Screen

Fig. 8.5.1 Online monitor setting screen


Meanings of Soft key
EMG ST : Terminates communication forcibly. Use this key if
communication becomes abnormal and the connection
cannot be terminated normally.
INIT : Initializes the parameters to their default values.

NOTE
1 In case of configuration of CNC with which neither Ethernet
nor HSSB is available, the item of HIGH SPEED I/F is not
displayed.
2 In case of display which has 5+2 soft key, two pages are
used for this setting screen.
Switch the page by <Page Up> or <Page Down> key.

8.5.2 To communicate with FANUC LADDERII, FANUC LADDERIII or


Setting of online Ladder Editing Package, you need to put the PMC system in waiting
situation of the connection. There are two ways for setting this, setting at
connection PMC screen and setting in NC parameter. Also, there are three connection
types, for example Ethernet, RS232C or HSSB.

595
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.5.2.1 To display the soft key [MONIT] in the PMC main menu screen, set
How to set at PMC PROGRAMMER
ENABLE to YES in the setting screen. When pushing the soft key
Screen
[MONIT]>[ONLINE], the online setting screen is displayed. (Fig.
8.5.1)
1. Case of connection by RS232C (FANUC LADDERII, FANUC
LADDERIII)
(1) Check that NOT USE is selected at the RS232C item.
(2) Set the parameter of CHANNEL and BAUD RATE.
(3) Move the cursor to the RS232C item with Up or Down Cursor
key.
(4) Select USE with Left or Right Cursor key.
2. Case of connection by Ethernet (FANUC LADDERIII, Ladder
Editing Package)
(1) Move the cursor to the HIGH SPEED I/F item with Up or Down
Cursor key.
(2) Select USE with Left or Right Cursor key.
3. Case of connection by HSSB (Ladder Editing Package)
(1) Move the cursor to the HIGH SPEED I/F item with Up or Down
Cursor key.
(2) Select USE with Left or Right Cursor key.

NOTE
1 When both RS232C = USE and HIGH SPEED I/F =
USE are selected, the PMC system will communicate with
the application which is connected at first. If PMC system is
already connecting with an application, it can not connect
with other applications.
2 When you use the online function by Ethernet, the setting
of Ethernet parameters at CNC is necessary in advance.
3 Loader control function can not connect with FANUC
LADDERIII or Ladder Editing Package by Ethernet.

596
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.5.2.2 (1) Display the No.24 of NC parameter.


How to set at NC (2) To connect by Ethernet or HSSB, input 0, 11 or 12.
parameter To connect by RS232C, input 1, 2, 11 or 12.
Contents of NC parameter No.24.

NC parameter Setting of the PMC online monitor screen


No.24 RS232C HIGH SPEED I/F Meanings
The item of RS232C is changed to NOT USE.
0 NOT USE USE
The item of HIGH SPEED I/F is changed to USE.

The item of CHANNEL is set 1 and the item of RS232C is


1 USE (Channel 1) NOT USE changed to USE.
The item of HIGH SPEED I/F is changed to NOT USE.

The item of CHANNEL is set 2 and the item of RS232C is


2 USE (Channel 2) NOT USE changed to USE.
The item of HIGH SPEED I/F is changed to NOT USE.

The item of CHANNEL is set 1 and the item of RS232C and


11 USE (Channel 1) USE
HIGH SPEED I/F are changed to USE.

The item of CHANNEL is set 2 and the item of RS232C and


12 USE (Channel 2) USE
HIGH SPEED I/F are changed to USE.

3 to 10
(Reserved) (Reserved) Dont use this setting.
13 to 254

Terminates communication forcibly.It is the same effect as soft key


255 NOT USE NOT USE
[EMG ST].

NOTE
1 If the value of No.24 in NC parameter is changed, the setting
of the online monitor screen of PMC is automatically
changed too. This NC parameter is made effective
immediately after changing setting of the parameter.
2 Even if the setting of the online monitor screen of PMC is
changed, the value of No.24 in NC parameter is not
changed

597
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.5.2.3 (1) Display the No.101 of NC parameter.


How to set at NC (2) To connect by RS232C, input 1 to No.101#6.
parameter (Power
MateD/H) #7 #6 #5 #4 #3 #2 #1 #0
0101 1

#6 0 : Online monitor driver is not used.


1 : Online monitor driver is used.

NOTE
1 In case of Power MateD 2 pathcontrol, only a parameter
for 1 path is available.
2 The online monitor driver occupies the line while it is
operating. In this state, other input/output functions cannot
use the line. For other input/output functions to use the line,
it is necessary to display the abovementioned parameter
and stop the online monitor driver.
3 While the online monitor driver is operating, the following
functions cannot be used.
D [PMCLAD], [I/O], [EDIT], [SYSPRM] on CRT/MDI
D [EDIT], [SYSTEM PARAM], [I/O] on DPL/MDI
4 In case of operating NC, the screen display of NC (Position,
etc.) might be slow when using input/output functions (Load
program, Store program, etc.). There is no problem in the
operation of NC. It is recommended to use input/output
functions while NC is not operating.
5 When the screen made by C language executor is
displayed, the communication may be slow down. It is
recommended to use input/output functions after moving to
other screens (Position, etc).

598
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

8.5.3
Online Function by
Ethernet

8.5.3.1 When you try to connect FANUC LADDERIII or Ladder Editing


Setting of Ethernet Package (Window version) with CNC by Ethernet, it is necessary to set
some Ethernet parameters. The setting of Ethernet parameters can be set
parameters
in the following Ethernet parameter screen of CNC. Please refer to
FANUC Ethernet Board/DATA SERVER Board OPERATORS
MANUAL (B63354EN) about the detail of the setting screen and
setting parameters. The setting item necessary for Ethernet connection for
PMC online function is as follows.
IP ADDRESS (Set the IP address of CNC. 192.168.0.1
etc.)
SUBNET MASK (Set the mask address of the IP address.
255.255.255.0 etc.)
ROUTER IP ADDRESS (If you use the router, set the Router IP
Address.)
PORT NUMBER (TCP) (8193 etc.)

599
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.5.3.2 The procedures for online connection with PMC and the offline
Starting online programmer (FANUC LADDERIII, Ladder Editing Package for
windows) by Ethernet are as follows.
communication by
(Example: FANUC LADDERIII)
offline programmer
(Ethernet connection) (1) Start up FANUC LADDERIII, and click the [Communication] on
[Tool] menu.

(2) Select the [Network Address] tab and push the <Add Host> button.
Input the IP Address and Port No. inputted by 8.5.3.1 Setting of
Ethernet parameters.

600
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

(3) Select the [Setting] tab, and add the IP Address to Use device.

(4) Push the <Connect> button for start of the communication.


Ladder Editing Package can be connected by the same operation too.
Refer to FANUC LADDERIII OPERATORS
MANUAL(B66234EN) as for the detail of operation of FANUC
LADDERIII. Refer to LADDER EDITING PACKAGE (Windows)
OPERATORS MANUAL (B63484EN) as for the detail operation of
Ladder Editing Package.

CAUTION
1 When one of the following screens is displayed at PMC, the
online communication can not be used. Change to other
screens from the following screens, and use the online
function.
[PMCLAD], [I/O], [EDIT], [SYSPRM], [TRACE], [USRDGN],
[DBGLAD], [GDT], [USRMEM]
2 When the online function is used with RS232C, the
selected channel is occupied by the PMC system. To use
other input/output functions with RS232C, specify other
channel setting than the one used by online function.
3 Loader control function can not connect with FANUC
LADDERIII or Ladder Editing Package by Ethernet.

601
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

8.5.4 The communication status of RS232C and HIGH SPEED I/F are
Communication Status displayed at the online monitor screen during the online communication.

Fig. 8.5.4 Online monitor setting screen

USE TIME : The maximum time in the communication processing is dis-


played.

RS232C : The communication condition of RS232C is displayed.

HIGH SPEED I/F : The communication condition of HIGH SPEED I/F is dis-
played.
ETHER_BOARD : Displayed during the communication with Ethernet board.
The IP address of the communication partner is displayed.
HSSB : Displayed during the communication with HSSB.

The display messages and the meanings are shown in the table of below.
Displayed messages Meanings

INACTIVE The communication is inactive.

STOPPING The communication is being stopped.(Wait for the


termination of communication)

STARTING The communication is being started.(Wait for the


termination of communication over another commu-
nication path)

STANDBY The communication is active and in standby mode.

CONNECTED The communication is active and being connected.

NO OPTION The port can be not opened because there is not


option of RS232C.

BAD PARAMETER Invalid open parameters are specified.

TIMEOUT ERROR A timeout has occurred and communication is


aborted.

602
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
B61863E/14 PMC PROGRAMMER (CRT/MDI) THE PROGRAM (MONIT)

Displayed messages Meanings

TIMEOUT(K) ERROR A timeout has occurred and communication is


aborted.

BCC ERROR A Block Check Code (packet parity) error has oc-
curred.

PARITY ERROR A parity error has occurred.

OVERRUN ERROR A reception overrun has occurred and the commu-


nication can not recover.

SEQUENCE ERROR Packets are out of sequence.(Incorrect procedure)

DATA ERROR Incorrect packets have been received through retry


process.

QUEUE OVERFLOW The transmit/receive queue has overflowed.

DISCONNECTED Communication has been terminated successfully.

NO CONNECTION The cable is disconnected.

8.5.5 If any errors have occurred during Ethernet connection, the contents of the
About Connection Log errors are displayed at ETHLOG screen of CNC. Refer to this screen
when the communication does not start.
of Ethernet

603
8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

Connection Log Meanings and countermeasures

SnpErr:PDU=m,n,[x] date time An error has occurred during the online communication.
m, n : Online communication information that is internal information of a system.
SnpErr:PDU=n,[x] date time
x : Error information
SnpErr:TaskTimeOut[x] date time 6001 PMC does not support the Ethernet.Confirm the Series/Edition of PMC
software.
6003 Unsupported command data was received.Confirm the Series/Edition of
Ethernet board software.
6004 There was an error in command dataConfirm the Series/Edition of
Ethernet board software.
6005 PMC does not receive command data.Confirm the communication sta-
tus at the online setting screen of PMC.
6010 PMC does not receive command data.Confirm if HIGH SPEED
I/F=USE is selected and other application is not connected at the online
setting screen of PMC.
6011 Timeout error occurred at PMC.Increase the value of Time Out in
[Network Address] of [Communication] menu for FANUC LADDERIII or
Ladder Editing Package.
6012 PMC does not receive command data because it is busy for proces-
sing.Confirm the communication status at the online setting screen of
PMC.
6013 Timeout error occurred at PMCIncrease the value of Time Out in
[Network Address] of [Communication] menu for FANUC LADDERIII or
Ladder Editing Package.
6101 PMC received an unsupported function code.Confirm the Series/Edition
of PMC software.
date : The date when the error occurred.
Ex.) 0126 means January 26th.
time : The time when the error occurred.
Ex.) 1623 means 4:23 PM.

604
9. ERROR MESSAGES
B61863E/14 PMC PROGRAMMER (CRT/MDI) (FOR EDIT)

9 ERROR MESSAGES (FOR EDIT)

Error messages (For EDIT 1)

Message Contents and solution


ADDRESS BIT NOTHING The address of the relay/coil is not set.
FUNCTION NOT FOUND There is no functional instruction of the input number.
COM FUNCTION MISSING The functional instruction COM(SUB9) is not correctly dealt with.
Correspondence of COM and COME(SUB29) is incorrect.
Or, the number of coil controlled by COM is specified by the model which the number
cannot be specified.(It is possible to specify the number of coil only on PMCRB/RC.)
EDIT BUFFER OVER There is no empty area of the buffer for the editing.
(solution) Please reduce NET under editing.
END FUNCTION MISSING Functional instruction END1, END2, END3 and END do not exist
Or, there are error net in END1, END2, END3, END.
Or, order of END1, END2, END3, and END is not correct.
ERROR NET FOUND There is an error net.
ILLEGAL FUNCTION NO. The wrong number of the functional instruction is searched.
FUNCTION LINE ILLEGAL The functional instruction is not correctly connected.
HORIZONTAL LINE ILLEGAL The horizontal line of the net is not connected.
ILLEGAL NET CLEARED Because the power had been turn off while editing LADDER, some net under editing was cleared.
ILLEGAL OPERATION Operation is not correct.
The value is not specified and only INPUT key was pushed.
The address data is not correctly inputted.
Because the space to display the instruction on screen is not enough, the functional instruction
cannot be made.
SYMBOL UNDEFINED The symbol which was inputted is not defined.
INPUT INVALID There is an incorrect input data.
Nonnumerical value was inputted with COPY,INSLIN,CUP, CDOWN etc.
The input address was specified for write coil.
An illegal character was specified for the data table.
NET TOO LARGE The input net is larger than the editing buffer.
(solution) Please reduce the net under editing.
JUMP FUNCTION MISSING The functional instruction JMP(SUB10) is not correctly dealt with.
Correspondence of JMP and JMPE(SUB30) is incorrect.
The number of coil to jump is specified by the model which the number of coil cannot specified.
(It is possible to specify the coil number only on PMCSB/SC.)
LADDER BROKEN LADDER is broken.
LADDER ILLEGAL There is an incorrect LADDER.
IMPOSSIBLE WRITE You try to edit sequence program on the ROM.
OBJECT BUFFER OVER The sequence program area was filled.
(solution) Please reduce the LADDER.
PARAMETER NOTHING There is no parameter of the functional instruction.
PLEASE COMPLETE NET The error net was found in LADDER.
(solution) After correcting the error net, please continue operating.
PLEASE KEY IN SUB NO. Please input the number of the functional instruction.
(solution) If you do not input the functional instruction, please push soft key FUNC again.
PROGRAM MODULE NOTHING You tried to edit though there was neither RAM for debugging nor ROM for sequence program.
RELAY COIL FORBIT There is an unnecessary relay or coil.
RELAY OR COIL NOTHING The relay or the coil does not suffice.
PLEASE CLEAR ALL It is impossible to recover the sequence program.
(solution) Please clear the all data.

605
9. ERROR MESSAGES
(FOR EDIT) PMC PROGRAMMER (CRT/MDI) B61863E/14

Error messages (For EDIT 2)

Message Contents and solution


SYMBOL DATA DUPLICATE The same symbol name is defined in other place.
COMMENT DATA OVERFLOW The comment data area was filled.
(solution) Please reduce the number of the comment.
SYMBOL DATA OVERFLOW The symbol data area was filled.
(solution) Please reduce the number of the symbol.
VERTICAL LINE ILLEGAL There is an incorrect vertical line of the net.
MESSAGE DATA OVERFLOW The message data area was filled.
(solution) Please reduce the number of the message.
1ST LEVEL EXECUTE TIME OVER The 1st level of LADDER is too large to complete execution in time.
(solution) Please reduce the 1st level of LADDER.
PARA NO.RANGE ERR : A parameter number used for a functional instruction falls outside the allowable range.
functionalinstructionname (solution) Change the parameter number to a value within the allowable range.
PARA NO.DUPLICATE : A parameter number used for a functional instruction is specified more than once.
functionalinstructionname (solution) Change the number to a number that has not yet been used if duplicate execution causes
EXIT ? an error.

Error messages (during automatic FROM writing after ladder editing)

Message Contents and solution


PROGRAM ALREADY EXISTS A program already exists in flash ROM. (Upon BLANK execution)
PROGRAM ALREADY EXISTS A program already exists in flash ROM.
(EXEC?) (Action) While the message is being displayed, press the EXEC key again to execute
WRITE or ERASE. (Upon WRITE or ERASE execution)
PROGRAM NOTHING No program exists in flash ROM.
ERASE ERROR Flash ROM has failed and requires replacement. Contact a FANUC service
FROM WRITE ERROR 13 representative.
FROM WRITE ERROR 28
WRITE ERROR
FROM WRITE ERROR 12
FROM WRITE ERROR 29
READ ERROR
ANOTHER USED A unit other than the PMC is using the flash ROM.
FROM WRITE ERROR 9
FROM WRITE ERROR 36
MUST BE IN EMG STOP The CNC is not in emergency stop mode.
NOT EMG STOP
FROM WRITE ERROR 10
FROM WRITE ERROR 37
NO OPTION The ROM cassette option is not provided.
SIZE ERROR The size of a sequence program is larger than that of the flash ROM. (Upon WRITE
IMPOSSIBLE WRITE (SIZE OVER) execution)
NO SPACE (Action) Try the CONDENSE function (on the EDIT/CLEAR screen). If the problem
FROM WRITE ERROR 1 persists, increase the flash ROM size.
FROM WRITE ERROR 15 The size of a sequence program to be read is larger than that of RAM. (Upon READ
FROM WRITE ERROR 35 execution)
(Action) Increase the RAM size.

606
B61863E/14 PMC PROGRAMMER (CRT/MDI) 10. ERROR MESSAGES (FOR I/O)

10 ERROR MESSAGES (FOR I/O)

Error messages (For I/O 2)


Message Contents and solution
I/O OPEN ERROR nn An error occurs when the reader/puncher interface was started.
nn = 1 Because the interface is used with NC etc., the interface is not able to be opened by PMC
side.
(solution) After other functions finishes using the line, please execute again.
6 There is no option for the interface.
20 The interface cannot be opened.
(solution) Please confirm the connection of the cable. Please confirm setting of the
baud rate etc.
I/O WRITE ERROR nn An output error occurred in the reader/puncher interface.
nn = 20 The state of the interface is not correct.
(solution) Please confirm the connection of the cable. Please confirm setting the baud
rate etc.
22 Opponent side is not ready to receive.
(solution) Please confirm the power supply on the opponent side. Or, please initialize the
interface.
I/O READ ERROR nn An input error occurred in the reader/puncher interface.
nn = 20 The state of the interface is not correct.
(solution) Please confirm the connection of the cable. Please confirm setting the baud
rate etc.
21 The data is not sent from the opponent side.
(solution) Please confirm the power supply on the opponent side.
I/O LIST ERROR nn An error occurred in directory read processing from FD Cassette.
nn = 20 The state of the interface is not correct.
(solution) Please confirm the connection of the cable. Please confirm setting of the baud
rate etc.
COMPARE ERR xxxxxx = aa:bb A compare error occurred.
CONT?(Y/N) xxxxxx : The Address where the compare error occurred.
aa : The data on PMC side
bb : The data on device side
Enter Y to continue processing.
ADDRESS IS OUT OF The data transferred to the address out of the PMC debugging RAM area.
RANGE(xxxxxx) xxxxxx : Transferred address.
(solution) Please confirm the address of the transferring data.
LADDER : Please confirm the model setting.
C language : Please confirm setting the address in the link control statement and build file.
ROM WRITER ERROR nnnnnn An error occurred in the ROM writer.

607
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11 PMC PROGRAMMER (DPL/MDI)


(ONLY FOR THE Power Mate)

The DPL/MDI panel is used to set PMC system parameters and create and
execute the sequence program.
(1) Setting and displaying PMC system parameters (SYSTEM PARAM)
The type of counter data (BCD or binary) can be selected.
(2) Editing the sequence program (EDIT)
The sequence program can be edited (input, addition, search, and
deletion) by using the ladder mnemonics display.
(3) Executing the sequence program (RUN/STOP)
The execution of the sequence program can be started and
stopped.
(4) Storing the sequence program into flash EEPROM (I/O)
The sequence program can be stored into flash EEPROM (only
for the Power MateH and Power Mate iD/H).
The DPL/MDI panel is shown below.

X
O N G AXIS
DGNOS
PARAM POS
Y K/A G X

F M S T OPR
ALARM PRGRM
F RD WRT NOT

H # / EOB &@ MENU


SUB OR AND STK NO. VAR

P
7 8 9 P I READ INSRT

Q
4 5 6 T/C J WRITE DELET

R
1 2 3 D/R K
ALTER

0 /+ & CAN INPUT

Fig. 11 DPL/MDI panel for Power Mate

608
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

NOTE
1 With the PMC programmer (DPL/MDI) function, the
characters indicated at the lowerleft part of each key are
used.
2 When the <D/R> key is pressed once, the lefthand
character is valid. When the <D/R> key is pressed twice, the
righthand character is valid.
Example : When the <D/R> key is pressed once, D is keyed
in. When the <D/R> key is pressed twice, R is keyed in.
When a password is cleared, however, only the characters
on the left side are valid.

The screen configuration for the PMC programmer (DPL/MDI) function


is as follows:

PMC programmer menu Sequence program start and stop


<INPUT>or<READ>
PMC PRG MENU 1/3 LADDER RUN/STOP
>RUN/STOP MONITOR (STOP)
<CAN>or<WRITE>

<> <>

<INPUT> PMC editing menu <INPUT> Editing ladder mnemonics


or<READ> or<READ>
PMC PRG MENU 2/3 PMC EDIT 1/1 N0001
>EDIT >LADDER RD X0000.0
<CAN>or <CAN>or
<WRITE> <WRITE>

<> <>

<INPUT> Setting and displaying PMC system parameters


or<READ>
PMC PRG MENU 3/3 CTR TYPE=BCD
>SYSTEM PARAM (BINARY=0/BCD=1)
<CAN>or
<WRITE>
The Power MaterH supports the following screen:
<> <>
Screen for storing the sequence
<INPUT> program into flash ROM
or<WRITE>
PMC PRG MENU 4/4 DEVICE=FROM
>I/O >WRITE Y/N[YES]
<CAN>

609
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.1 To operate the PMC programmer, set K17#1 of the keep relay area for
PMC parameters to 1, then press the <PRGRM> key two times on the
SELECTING THE DPL/MDI (press the <PRGRM> key further when the program screen is
PMC PROGRAMMER selected), thus causing the PMC programmer menu to be displayed.
MENU
Program screen PMC programmer menu screen

<O0001> N010!G90 PMC PRG MENU 1/3


G01 G43 X10 ; <PRGRM> >RUN/STOP

Can be switched only when K17#1 = 1.

To return to the CNC screen, press the <POS>, <PRGRM>, <VAR>,


<DGNOS/PARAM>, or <ALARM> key.

<POS> Current
Position screen
<PRGRM>
Program screen

<PRGRM>
PMC programmer screen (K17#1=1)
(PMC programmer menu)
(PMC editing menu) <ALARM>
Alarm/Message screen
<DGNOS/
PARAM>
Parameter/Diagnostic screen

<VAR>
Offset/Setting/Macro
Variable screen

The following keys on the DPL/MDI panel are used for PMC operation:
1 <POS>, <PRGRM>, <VAR>, <DGNOS/PARAM>, <ALARM> key
Returns to the CNC screen.
2 <> key
Shifts the cursor upward.
3 <> key
Shifts the cursor downward.
4 <INPUT>, <READ> key
Selects a function when the PMC programmer menu or PMC editing
menu is displayed.
5 <CAN>, <WRITE> key
Returns to the previous menu from the PMC programmer menu or
PMC editing menu.

610
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

11.2 Selecting SYSTEM PARAM on the PMC programmer menu displays the
system parameter screen. If the sequence program is running, selecting
SETTING AND this function automatically stops the program.
DISPLAYING SYSTEM
1 Display the PMC programmer menu.
PARAMETERS
2 Display the SYSTEM PARAM item by pressing the <> or <> key.
(SYSTEM PARAM)
PMC PRG MENU 3/3
>SYSTEM PARAM

3 Press the <INPUT> or <READ> key. The system parameter screen


appears.

CTR TYPE = BIN


(BINARY=0/BCD=1)

4 The current counter data type is displayed on the screen.


(a) Specify the type of the counter value to be used for the CTR
functional instruction, as binary or BCD (enter <0> for binary or
<1> for BCD).
(b) Press the <INPUT> key.
The counter data type is set.
5 Pressing the <CAN> or <WRITE> key displays the PMC
programmer menu.

CAUTION
If the PMC parameter keep relay K19#0 is set to 1, the
screen for writing a sequence program into Flash Memory
is displayed upon the completion of editing. (This is
applicable to the Power MateH and Power Mate iD/H
only).

DEVICE=FROM
>WRITE Y/N [YES]

Write a sequence program into Flash Memory as explained


in Section 11.7.

611
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.3 Selecting EDIT on the PMC programmer menu displays the editing
menu.
EDITING THE
SEQUENCE 1 Display the PMC programmer menu.
PROGRAM (EDIT) 2 Display the EDIT item by pressing the <> or <> key.

PMC PRG MENU 2/3


>EDIT

3 Press the <INPUT> or <READ> key. The PMC editing menu


appears.

PMC EDIT 1/1


>LADDER

To end editing and display the PMC programmer menu, press the <CAN>
or <WRITE> key.

612
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

11.4
EDITING LADDER
MNEMONICS

11.4.1 When ladder mnemonic editing (LADDER) is selected from the PMC
Starting Ladder edit menu, the ladder mnemonic edit screen is displayed.
When this function is selected, the sequence program stops.
Mnemonics Editing
1 Display the PMC edit menu screen.
2 Display the LADDER item by pressing the <> or <> key.

PMC EDIT 1/1


>LADDER

3 Press the <INPUT> or <READ> key.


When a password is set for the ladder: Proceed to step 4.
When no password is set for the ladder: Proceed to step 6.
4 If a password is set, a password clear request is displayed.

PASSWORD (R/W)

NOTE
For a ladder for which a password has been set, the ladder
mnemonic editing function cannot be started unless the
correct password is entered. Once the password is cleared,
the password remains cleared until the power is turned off
then back on.

5 Enter the password, then press the <INPUT> key.

NOTE
The entered password is not displayed (not echoed back on
the screen).

If the entered password is incorrect, the following error message is


displayed.

FALSE PASSWORD

If the <INPUT> key is pressed at this time, the screen display returns
to the password clear request screen.
If the <CAN> key is pressed at this time, the screen display returns
to the PMC edit menu.
If the entered password is correct, the password is cleared.

613
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

6 A sequence program is displayed.


Step number

> N0001
RD X0000.0

Instruction

11.4.2 1 Cursor scroll (scroll per step)


Pressing the <> cursor key displays the instruction one step before
Confirming the Ladder
that currently displayed. Pressing the <> cursor key displays the
Mnemonics instruction one step after that currently displayed.
2 Specifying the step number
Entering <NO.>, <step number>, then <INPUT> displays the
instruction having the entered step number.
(The <> cursor key can be used instead of the <INPUT> key.)
(Example) <NO.>, <123>, <>

N0123
SUB 50 PSGNL

3 Relay search
Entering <address number> then <> searches for the relay
including the entered address.
(Example) <X0.2>, <>

N0105
AND X0000.2

4 Relay coil search


Entering <WRT>, <address number>, then <> searches for the
relay coil including the entered address.
(Example) <WRT>, <Y33.5>, <>
N0187
WRT. NOT Y0033.5

5 Functional instruction search


Entering <SUB>, <functional instruction number>, then <>
searches for the entered functional instruction.
(Example) <SUB>, <50>, <>

N0123
SUB 50 PSGNL

614
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

NOTE
1 Relay search, relay coil search, and functional instruction
search are started from the current screen. If the relay, relay
coil, or instruction is not found by the end of the ladder
program, search is performed from the beginning of the
ladder program to the step at which search was started. If
still not found, NOT FOUND is displayed.
N0105 NOT FOUND
AND X0000.2

2 Display of some instructions may differ from that for FANUC


LADDER.
PG, personalcomputer FANUC LADDER Ladder mnemonics editing
(a) RD.NOT.STK RD.N.STK

(b) TMR timernumber SUB 03 TMR


P001 timernumber

(c) DEC codesignaladdress SUB 04 DEC


(PRM) decodeinstruction P001 codesignaladdress
P002 decodeinstruction

The above also applies when modifying the ladder


mnemonics.

615
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.4.3 1 Changing an instruction


Modifying the Ladder (a) Display the instruction to be changed.
Mnemonics (b) Enter a new instruction.
(c) Press the <ALTER> key.
(Example) <OR>, <Y32.4>, <ALTER>

N1234
AND R0123.4

Before change

N1234
OR Y0032.4

After change

CAUTION
If changing the instruction causes the memory capacity to
be exceeded, the <ALTER> key is ignored without changing
the instruction.

2 Deleting an instruction
(a) Display the instruction to be deleted.
(b) Press the <DELET> key.
The instruction is deleted and the next instruction is displayed.
3 Inserting an instruction
(a) Display the instruction after which an instruction is to be inserted.
(b) Enter the instruction to be inserted.
(c) Press the <INSRT> key.
(Example) <AND>, <STK>, <INSRT>

N1234
AND R0123.4

Before insertion

N1234
AND.STK

After insertion

NOTE
If inserting the instruction causes the memory capacity to be
exceeded, the <INSRT> key is ignored without inserting the
instruction.

4 Deleting the ladder program


(a) Enter <9999>.
(b) Press the <DELET> key.
The whole ladder program is deleted.

616
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

NOTE
In editing the functional instruction TMR, TMRB, CTR,
DIFU, DIFD, the range and the multiple use of parameters
are checked.
When the parameter is out of range error, it can not be
inputted. When parameter is multiple use error, the error
message is displayed on the screen.
(Example) Error message of multiple use.

N00010 TMR (DUP)


P001 50

617
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.4.4 1 Press the <CAN> or <WRITE> key.


Ending Ladder 2 EXECUTING is displayed.
Mnemonics Editing
N0001
EXECUTING

3 The PMC editing menu appears.

NOTE
1 If the sequence program contains an error, the PMC editing
menu is not displayed but an error message appears on the
screen.
(Example) Error message
END FUNCTION
MISSING

Pressing the <> or <> cursor key displays the ladder


mnemonics editing screen.
2 Pressing the <POS>, <PRGRM>, <VAR>,
<DGNOS/PARAM>, or <ALARM> key during the editing of
the sequence program displays the CNC screen by forcibly
terminating editing even if the program contains an error.
3 When K19#0 of the keep relay area for PMC parameter is
set to 1, the screen for storing the sequence program into
flash EEPROM is displayed after ladder editing. (Only for
Power MateH, Power Mate iD/H)
DEVICE=FROM
>WRITE Y/N [YES]

Please refer to the item 11.4 and storing the sequence


program into flash EEPROM.
4 When parameter is multiple use error, the error message is
displayed on the screen.
(Example) Error message

FUNC. PARAM NO.


DUPLICATE

Pressing the <> or <> cursor key displays the ladder


mnemonics editing screen. Pressing <CAN> or <WRITE>
key again displays the PMC programmer menu.

618
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

11.5 Selecting RUN/STOP on the PMC programmer menu displays the


sequence program start/stop screen.
STARTING AND
STOPPING THE 1 Display the PMC programmer menu.
SEQUENCE 2 Display the RUN/STOP item by pressing the <> or <> key.
PROGRAM PMC PRG MENU 1/3
(RUN/STOP) >RUN/STOP

3 Press the <INPUT> or <READ> key. The sequence program


start/stop screen appears.

LADDER RUN/STOP
MONITOR [RUN]

4 The current execution state of the sequence program is displayed on


the screen.
Pressing the <> or <> key switches the state between running and
stopped.
5 Pressing the <CAN> or <WRITE> key displays the PMC
programmer menu.

CAUTION
When the sequence program cannot be started(RUN), the
alarm of PMC occurred. Please confirm the alarm status
referring to 11.11 Error List.

619
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.6
Displayed error message Error description (operator action)
ERROR MESSAGES 1 COIL NOTHING No coil is specified for a functional instruction
(FOR LADDER using a coil.

MNEMONICS 2 COM FUNCTION MISSING The use of the COM (SUB9) functional
instruction is incorrect.
EDITING) 3 END FUNCTION MISSING The END1 or END2 functional instruction is
missing (or ERROR NET).
4 JUMP FUNCTION MISSING The use of the JMP (SUB10) functional
instruction is incorrect.
5 LADDER BROKEN The ladder program is corrupted.
6 OBJECT BUFFER OVER The user program RAM is full.
(Note) (Perform condensation or reduce the
size of the ladder program.)
7 PLEASE CLEAR ALL The sequence program has become unrecov-
erable due to poweroff during editing.
8 1ST LEVEL EXEC TIME OVER The ladder first level is too great.
9 FUNC, PARAM NO. OUT OF There is out of range error in the parameter of
RANGE functional instruction TMR, TMRB, CTR,
DIFU, DIFD. It is displayed when mnemonics
editing is finished.
10 FUNC. PARAM NO. DUPLICATE There is multiple use error in the parameter of
functional instruction TMR, TMRB, CTR,
DIFU, DIFD. It is displayed when mnemonics
editing is finished.
11 Nxxxxx yyyy (RNG) There is out of range error in the parameter of
P0001 nnn functional instruction TMR, TMRB, CTR,
DIFU, DIFD.
xxxxx : Step number
yyyy : Functional instruction
nnn : Parameter
12 Nxxxxx yyyy (DUP) There is multiple use error in the parameter of
P0001 nnn functional instruction TMR, TMRB, CTR,
DIFU, DIFD.
xxxxx : Step number
yyyy : Functional instruction
nnn : Parameter

620
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

11.7 Selecting I/O on the PMC programmer menu displays the screen for
storing the sequence program into flash EEPROM. Before attempting to
STORING THE store the sequence program into flash EEPROM, place the CNC in the
SEQUENCE emergency stop state.
PROGRAM INTO (1) Display the PMC programmer menu.
FLASH EEPROM (I/O) (2) Display the I/O item by pressing the <> or <> key.
(ONLY FOR THE
Power MateH AND PMC PRG MENU 4/4
>I/O
Power Mate iD/H)
(3) Press the <INPUT> or <WRITE> key. The sequence program
storage screen appears. Pressing the <> or <> key switches display
between [YES] and [NO].
<>
DEVICE=FROM DEVICE=FROM
>WRITE!Y/N[YES] >WRITE!Y/N[NO ]
<>

(4) When [NO] is displayed, pressing the <INPUT> key displays the
sequence program storage screen. When [YES] is displayed, pressing
the <INPUT> key starts writing the sequence program into flash
EEPROM.
EXECUTING is displayed during writing.

WRITE TO FROM EXECUTING BLINKS.


EXECUTING

Once the sequence program has been written normally,


COMPLETE is displayed.

WRITE TO FROM
COMPLETE

NOTE
If an error occurs, an error message appears on the screen.

Example Example error message

NOT EMG STOP

To return to the sequence program storage screen, press the <> or


<> key.
(5) Pressing the <CAN> key displays the PMC programmer menu.

621
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.8 The table below lists the details of the errors which may occur during
storage into Flash ROM using the DPL/MDI (only for the Power MateH
ERROR DETAILS and Power Mate iD/H).
Error message Description
PROGRAM DATA The ladder data in RAM is invalid. Alternatively,
ERROR there is no RAM or ROM.
SIZE ERROR The program exceeds the maximum size which can
be written into FROM.
NOT EMG STOP The CNC is not in the emergency stop state.
OPEN ERROR The OPEN processing has failed.
ERASE ERROR The ERASE processing has failed.
The FROM cannot be erased. Alternatively, the
FROM is defective.
WRITE ERROR The WRITE processing has failed.
The FROM cannot be written. Alternatively, the
FROM is defective.

622
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

11.9
INPUT/OUTPUT
LADDER/
PMCPARAMETER
BY MDI/DPL

11.9.1 D Method of Inputting/Outputting Ladder


Input/Output Method to (1) Select Diagnose screen by key in <DGNOS> key.
Office Programmer (2) Key in <READ>key or <WRITE> key.
(Pg Mate/Mark II) (3) Turn on <F8> key from the office programmer menu screen, and
(Fixed 9600bit/Sec.) key in menu number 5<NL> or 3<NL>.

11.9.2 D Method of Inputting Ladder and PMCParameter.


Input/Output Method to (1) Select Diagnose screen by key in <DGNOS>key.
FANUC FLOPPY (2) Key in <NO.>key and optionally key in [File No.].
CASSETTE (3) Key in <READ>key.
(Fixed 4800bit/Sec.)
CAUTION
In case of input PMCParameter, it is necessary to set
following conditions.
(a)Emergency stop condition, and NCParameter PWE=1.
(b)Stop condition the Ladder program.

D Method of Outoutting Ladder.


(1) Select Diagnose screen by key in <DGNOS>key.
(2) Key in <NO.>key and optionally key in [Files No.].
(3) Key in <WRITE>.

D Method of Outputting PMCPatameter.


(1) Select PMC STATUS screen by key in <DIGNOS>key.
(2) Key in <No.> key and optionally key in [File No.].
(3) Key in <WRITE>.

CAUTION
In case of output PMCParameter, it is necessary to set
following condition.
(a)Edit mode.
(b)Stop condition the Ladder program.

623
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.10 The online debugging function enables the monitoring and modification
of ladder programs and signal status on personal computers screen using
ONLINE a personal computer connected to the Power Mate through an RS232C
DEBUGGING cable.
FUNCTION
(ONLY FOR Power CAUTION
MateD/H and Power The additional option of the Ladder Online debugging
function is necessary to use the online debugging function
Mate iD/H)
on PMCPA3 for Power MateD.

FANUC FANUC LADDERII is necessary to use the online debugging


function. (This software is a programming system for developing
FANUC PMC sequence programs which operate on IBM PC/AT and
compatible computers.)

Software name Specification Personal computer


FANUC LADDERII A08B9201J503 IBM PC/AT and compatible

In this section, only the parameter of online monitor driver for Power
MateH and attention in use is described. Other points(connection of
cable with personal computer, details of the operation, etc.) are described
in the following manual.

Name of Manual Spec.No. Reference Items


FANUC LADDERII OPERATORS MANUAL B66184EN Online function

11.10.1 When using the online debugging function to connect a personal


Starting and Stopping computer to the PMC, first start the driver that provides the
communication function of the PMC.
the Online Debugging When starting or stopping the driver, it is necessary to set either of the
Function following parameters.
D Parameter screen for online monitor(dPARAMETERS FOR ONLINE
MONITORc)
Pressing the [MONIT] then [ONLINE] soft keys on the PMC menu
screen causes the online monitor parameter screen to appear.
ParameterdRS232Cc = dUSEc : Online monitor driver is used.
dNOT USEc: Online monitor driver is not
used.

CAUTION
The CRT/MDI is necessary when the parameter is set on the
PARAMETERS FOR ONLINE MONITOR screen.

624
11. PMC PROGRAMMER (DPL/MDI)
B61863E/14 PMC PROGRAMMER (CRT/MDI) (ONLY FOR THE Power Mate)

D Parameter in the Power MateH (No.0101#6)

#7 #6 #5 #4 #3 #2 #1 #0
0101

#6 = 0 : Online monitor driver is not used.


1 : Online monitor driver is used.

NOTE
In case of Power MateD Dual path control, only the
parameter of first path side is effective.

When either of the following conditions consists, the online monitor


driver is started.
DParameter RS232C is USE
DBit 6 of parameter No.0101 is 1

CAUTION
1 The online monitor driver occupies the line while it is
operating.
In this state, other input/output functions cannot use the
line.
If other input/output functions use the line, it is necessary to
display the abovementioned parameter and stop the
online monitor driver.
2 While the online monitor driver is operating, the following
functions cannot be used.
D[PMCLAD], [I/O], [EDIT], [SYSPRM] on CRT/MDI
D[EDIT], [SYSTEM PARAM], [I/O] on DPL/MDI
3 In case of operating NC, the screen display of NC(Position,
etc.) might be slow when using input/output functions(Load
from PMC, Store to PMC, etc.). There is no problem in the
operation of NC. It is recommended to using input/output
functions while NC is not operating.
4 When the screen made by C language executor is
displayed, the communication speed decreases. It is
recommended to use input/output functions after moving to
other screens(Position, etc.).

625
11. PMC PROGRAMMER (DPL/MDI)
(ONLY FOR THE Power Mate) PMC PROGRAMMER (CRT/MDI) B61863E/14

11.11 If in alarm is issued in the PMC, the alarn message is displayed on the
CRT (PMC ALARM MESSAGE screeen). But in case of DPL/MDI, it
ERROR LIST is displayed only by Rrelay status (ON or Off).
Refer to the APPENDIX L.ALARM MESSAGE LIST for more
information.
(1) Error ststus at power on or PROGRAM DOWN LOAD.

7 6 5 4 3 2 1 0

R9044

1 ER01 PROGRAM DATA ERROR (RAM)

3 ER03 PROGRAM SIZE ERROR (OPTION)

4 ER04 LADDER OBJECT TYPE ERROR

7 ER07 NO OPTION (LADDER STEP)

7 6 5 4 3 2 1 0

R9046

0 ER16 RAM CHECK ERROR (PROGRAM RAM)

1 ER17 PROGRAM PARITY

2 ER18 PROGRAM DATA ERROR BY I/O

3 ER19 LADDER DATA ERROR

4 ER20 SYMBOL/COMMENT DATA ERROR

5 ER21 MESSAGE DATA ERROR

6 ER22 PROGRAM NOTHING

7 ER23 PLEASE TURN OFF POWER

626
IV. PMCNB6 MANIPULATION
B61863E/14 PMCNB6 MANIPULATION 1. OVERVIEW

1 OVERVIEW

In the NC system, clicking the [PMC] soft key on the [SYSTEM] menu
enables the setting and display of data related to the PMC. The following
screens are used to specify and display the PMCrelated data.
(1) Ladder diagram display and editing (PMCLAD)
(2) Displaying PMC input/output signals and internal relay (PMCDGN)
(a) Title data screen
(b) Status screen
(c) Alarm screen
(d) Trace screen
(e) I/O Link monitor screen
(3) PMC data setting and display (PMCPRM)
(f) Timer
(g) Counter
(h) Keep relay
(i) Data table
(4) Specifying PMC setting data (SETING)
(j) General setting data
(k) Setting data related to editing and debugging
(l) Online monitor parameter
(5) Writing, reading, and collating sequence programs and PMC
parameters (I/O)

629
2. SOFT KEYBASED PMC MENU
SELECTION PROCEDURE PMCNB6 MANIPULATION B61863E/14

2 SOFT KEYBASED PMC MENU SELECTION PROCEDURE

While the <SYSTEM> function key on the LCD/MDI is held down,


clicking the [PMC] soft key displays the following PMC basic menu.

630
2. SOFT KEYBASED PMC MENU
B61863E/14 PMCNB6 MANIPULATION SELECTION PROCEDURE

2.1
PMC BASIC MENU

(1) Title line


This line displays the title of each PMC system screen.
It also displays the status of the PMC system at the righthand end.
RUN STOP . . . . Whether the sequence program is running is
indicated. [RUN] means that the sequence
program is running. [STOP] means that the
sequence program is at a halt.
ALM . . . . . . . . . This character string appears if a PMC alarm has
occurred.
(2) Status line
This line displays NC information. The display is the same as that on
the NC system screen.
(3) Keyin buffer
This area displays the data that was typed in.
(4) Soft key
The soft key field consists of a soft key at both ends and ten soft keys
in between. The leftend key has the following meaning:
Return key . . Clicking this key returns you to the previous
screen.
If the builtin debug function is disabled (bit 1 of K900 = 0), the basic
menu appears as follows:

631
2. SOFT KEYBASED PMC MENU
SELECTION PROCEDURE PMCNB6 MANIPULATION B61863E/14

632
2. SOFT KEYBASED PMC MENU
B61863E/14 PMCNB6 MANIPULATION SELECTION PROCEDURE

2.2
PMC SCREEN
TRANSITION AND
RELATED SOFT
KEYS

633
2. SOFT KEYBASED PMC MENU
SELECTION PROCEDURE PMCNB6 MANIPULATION B61863E/14

NC system screen

PMC

<

PMC basic menu screen

PMCLAD Ladder diagram display/editing screen

<
TITLE Title screen

PMCDGN STATUS Status screen

<
ALARM Alarm screen

TRACE Trace screen

I/O Link connection display


I/O LINK screen

TIMER Timer screen

PMCPRM Counter screen


COUNTR
<
KEEPRL Keep relay screen

DATA Data table screen

Setting menu screen


SETING

< GENERAL General setting data

EDIT/
DEBUG Data related to editing and debugging

ONLINE Online parameter setting

I/O I/O screen


<

RUN
Program restart function

or

STOP

634
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3 DISPLAYING PMC INPUT/OUTPUT SIGNALS AND


INTERNAL RELAY (PMCDGN)

635
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

3.1 The title data corresponds to the title of a sequence program. It consists
of the following items:
TITLE DATA DISPLAY
(TITLE)

D Machine tool builder name (32 characters)


D Machine name (32 characters)
D NC/PMC type (32 characters)
D Sequence program number (4 characters)
D Edition (2 characters)
D Sequence program drawing (32 characters)
D Sequence program creation date (16 characters)
D Sequence program creator name (32 characters)
D ROM writer operator name (32 characters)
D Comment (32 characters)
In addition, the following data is displayed:
D PMC basic software series and edition
D Amount of memory occupied by each set of sequence data
D PMC basic software type and sequence program PMC type
D Current, maximum, and minimum execution time of the ladder
program
When the [EDIT] soft key is pressed, the Title Editor Screen appears.

NOTE
1 When PROGRAMMER ENABLE is set to YES on the
GENERAL screen of Setting screen, the [EDIT] soft key
appears on the Title Data Display screen.
2 If the [EDIT] soft key is pressed while Online function is
being executed, the ONLINE MONITOR IS ACTIVE
message is displayed and the Title Editor screen does not
appear.

636
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.2 When the [EDIT] soft key is pressed on the Title Data Display screen, the
Title Data Editor screen appears.
TITLE DATA EDITOR
SCREEN

On this screen, you can edit the following ten items.


D Machine tool builder name (32 characters)
D Machine name (32 characters)
D NC/PMC type (32 characters)
D Sequence program number (4 characters)
D Edition (2 characters)
D Sequence program drawing (32 characters)
D Sequence program creation date (16 characters)
D Sequence program creator name (32 characters)
D ROM writer operator name (32 characters)
D Comment (32 characters)
Move the cursor to the item and input the comment. If you initialize the
item on the cursor, press the [DELETE] soft key.
If you do not save the edited data into Flash ROM, edited data is cleared
by power OFF.
When finishing the edit, the following message is displayed to confirm
to write to Flash ROM.
DO YOU WANT TO WRITE PROGRAM INTO FLASH ROM?
The following soft key is displayed. YES soft key saves the data. NO
soft key does not save the data.

Pressing these soft keys causes a return to Title Data Display screen.

NOTE
When WRITE TO FROM (EDIT) is set to YES on the
EDIT/DEBUG screen of Setting screen, saving operation
into Flash ROM is enabled.

637
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

3.3 This screen displays the contents at all the addresses (X, Y, F, G, R, A, C,
T, K, D, M, and N) specified in programs. Each content display is a string
SIGNAL STATUS of 0 and 1 with a hexadecimal indication at the right end.
DISPLAY (STATUS)

Operating procedure
(1) Click the [STATUS] soft key. The screen shown above appears.
(2) Specify the desired address by keying it in, then click the [SEARCH]
soft key.
(3) A sequence of data starting at the specified address is displayed as a
bit pattern.
(4) To specify another address for display, click a cursor key, page key, or
the [SEARCH] soft key.

638
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.4 If an alarm condition occurs in the PMC, clicking the [PMC] soft key from
the NC system displays the following alarm message instead of the PMC
ALARM SCREEN basic menu. The soft keys displayed on this screen remain the same as
(ALARM) on the PMC basic module screen. In addition, character string ALM
appears on the title line.
If the alarm condition is fatal, no sequence program will be executed.

For an explanation of the alarm messages displayed on this screen, see


APPENDIX M, ALARM MESSAGE LIST.

639
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

3.5
TRACE SCREEN

3.5.1 On the trace screen, you can trace specified signals. The result of the trace
Overview is displayed as the time chart of signals.
There are two tracing modes. One is the Time Cycle mode that samples
the state of the signals at every specified cycle time. The other is the
Signal Transition mode that samples the status of the signals when the
signals that are watched at every specified time are changed.
Pushing [TRACE] soft key displays the following screen.

To execute tracing, setting of the trace parameter is necessary. Pushing the


[SETING] soft key displays Parameter Setting screen. The trace
function is able to run automatically by the setting on PMC Setting
screen when the power is switched on. In this case, setting of the trace
parameter is necessary in advance.

NOTE
As for the setting of automatic running for the trace function,
please refer to II 7.5.1 Screen for Displaying General
Settings (GENERAL)

640
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.5.2 Pushing the [SETING] soft key displays the Parameter Setting screen.
Setting of Trace The following is the screen example of the trace execution by TIME
CYCLE mode.
Parameter

Parameter Setting has two screens. The page number is displayed on


up right of the screen. The page key changes these screens.
Pushing [<] soft key displays PMC Signal Trace screen.
The following is the screen example of the trace execution by SIGNAL
TRANSITION mode.

641
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

D SAMPLING MODE
Determines the sampling mode. Select one by cursor key or soft key.
Soft keys display when the cursor is put on SAMPLING
MODE.

Explanation:
TIME CYCLE Samples at every specified cycle time.
SIGNAL TRANSITION Samples when the signal changes.
INIT Initializes all the settings. (This soft key
is always displayed in page 1.)
D SAMPLING RESOLUTION
The resolution of sampling is inputted. The default value is the
minimum resolution (8msec). The range of the value is from 8msec to
1000msec. Inputted value is rounded down to the multiple of 8msec.
D SAMPLING TIME
This parameter is displayed when TIME CYCLE is set on
SAMPLING MODE. The execution time of trace is inputted. The
value of SAMPLING SESOLUTION or the number of specified
signal address changes the range of the value that is able to input. The
range is displayed on the right of the edit box.
D SAMPLING FRAME
This parameter is displayed when SIGNAL TRANSITION is set on
SAMPLING MODE. The number of sampling is inputted. The
value of SAMPLING SESOLUTION or the number of specified
signal addresses changes the range of the value that is able to input.
The range is displayed on the right of the edit box.
D STOP CONDITION
Determines the condition to stop the trace. Select one by cursor key
or soft key.
Soft keys display when the cursor is put on STOP
CONDITION.

Explanation:
NONE Does not stop the tracing automatically.
BUFFER FULL Stops the tracing when the buffer becomes full.
TRIGGER Stops the tracing by trigger
D STOP CONDITION TRIGGER ADDRESS
When TRIGGER is set on STOP CONDITION, this parameter is
enabled. Input signal address or symbol name as stop trigger.
Only bit address or corresponding symbols can be inputted. Byte
address cannot be inputted.
Soft keys display when the cursor is put on STOP CONDITION
TRIGGER ADDRESS.

642
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

Explanation:
DELETE Clears the value in the edit box.
SYMBOL Changes the address display to the symbol name
display and changes the soft key to [ADDRESS].
After that, following soft keys are displayed.

ADDRESS Changes the symbol name display to the address


display and changes the soft key to [SYMBOL].
D STOP CONDITION TRIGGER MODE
When TRIGGER is set on STOP CONDITION, this parameter is
enabled. Input trigger mode when the trace is stopped. Select one by
cursor key or soft key.
Soft keys display when the cursor is put on STOP CONDITION
TRIGGER MODE.

Explanation:

RISING EDGE Stops the tracing automatically by rising up of


the trigger signal.
FALLING EDGE Stops the tracing automatically by falling
down of the trigger signal.
BOTH EDGE Stops the tracing automatically by rising up or
falling down of the trigger signal.
D STOP CONDITION TRIGGER POSITION
When TRIGGER is set on STOP CONDITION, this parameter is
enabled. Input the ratio of the sampling time or number which
specifies the position where specified trigger condition is on.
If you would like to examine the transitions of the signal before the
trigger condition, you should set a big value in this parameter. If you
would like to examine the transitions of the signal after the trigger
condition, you should set a small value in this parameter.
Example: The case that sampling time is 10 second and trigger
position is set as 10%.

Trigger position

1sec 9sec

1 0 9 (SEC)

The graph is displayed on the right of the edit box. The edge of the left
hand is as 0% and the edge of the right hand is as 100%. The position
indicated by the input value is displayed as a gauge.
D SAMPLING CONDITION
When SIGNAL TRANSITION is set on TRACE MODE, this
parameter is enabled. Select one by cursor key or soft key.

643
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

Soft keys display when the cursor is put on SAMPLING


CONDITION.

Explanation:
TRIGGER Samples the status of specified signals when
the specified sampling condition is on.
ANY CHANGE Samples the status of specified signals when
the signals change
The address of the signals that should be sampled is set on Parameter
Setting screen page2.
D SAMPLING CONDITION TRIGGER ADDRESS
When SIGNAL TRANSITION is set on TRACE MODE, and
TRIGGER is set on SAMPLING CONDITION, this parameter is
enabled. Input signal address or symbol name as sampling trigger.
Only bit address or corresponding symbol can be inputted. Byte
address cannot be inputted.
Soft keys display when the cursor is put on SAMPLING
CONDITION TRIGGER ADDRESS.

The contents of the soft keys are same as STOP CONDITION


TRIGGER ADDRESS.
D SAMPLING CONDITION TRIGGER MODE
When SIGNAL TRANSITION is set on TRACE MODE, and
TRIGGER is set on SAMPLING CONDITION, this parameter is
enabled. Input trigger mode that determines the condition of specified
trigger.
Soft keys display when the cursor is put on SAMPLING
CONDITION TRIGGER MODE.

Explanation:
RISING EDGE Samples the status of specified signals by
rising up of the trigger signal.
FALLING EDGE Samples the status of specified signals by
falling down of the trigger signal.
BOTH EDGE Samples the status of specified signals by
rising up or falling down of the trigger signal.
ON Samples the status of specified signals during
the trigger signal is on.
OFF Samples the status of specified signals during
the trigger signal is off.

644
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

D SAMPLING ADDRESS
In page 2 of Parameter Setting screen, you can set the addresses or
symbols that should be sampled.

Move the cursor into edit box and input PMC signal address or
symbol.
In case of inputting discrete bit addresses, any bit address can be
inputted. Moreover, when you input byte address, all bits of the
address (bit0bit7) are set automatically.
Maximum 32 points of signal address can be inputted. Increasing the
number of the signal address changes the capacity of SAMPLING
TIME or SAMPLING FRAME in page1. If the capacity is
changed, the warning message is displayed.
Example of warning message:
In case of TIME CYCLE mode
SAMPLING TIME IS REDUCED TO n SEC.
In case of SIGNAL TRANSITION mode
SAMPLING FRAME IS REDUCED TO n COUNT.
The n means the maximum value that is able to input.
Explanation of the soft keys:
DELETE Clears the value of the edit box on the cursor.
SYMBOL Changes the address display to the symbol
display. However, display of the address that is
not defined the symbol does not change. This
soft key also changes to ADDRESS. The
following soft keys are displayed.
MOVE UP Exchanges the signal indicated the cursor for
the signal above one line.
MOVE DOWN Exchanges the signal indicated the cursor for
the signal below one line.
DELETE ALL Clears all of the value of the edit box.

645
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

ADDRESS Changes the symbol display into the address


display and changes the soft key to
SYMBOL.
D TRIGGER SETTING OF THE SAMPLING SIGNALS
When SIGNAL TRANSITION is set on TRACE MODE and
ANY CHANGE is set on SAMPLING CONDITION, the check
boxes on the right of the sampling address or symbols are displayed
as follows. Check the signals that should trigger the sampling in the
setting signals.

Pushing [TRIGGER ON] soft key sets the trigger on. Pushing
[TRIGGER OFF] soft key sets the trigger off. The default setting is
trigger on for all signals. The contents of other soft keys are same as
SAMPLING ADDRESS.

646
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.5.3 On trace screen, pushing [START] soft key starts the execution of trace
Execution of Trace after you set the trace parameter correctly. The following is the screen
example of the trace execution by TIME CYCLE mode.

The result of trace is immediately displayed during execution of the trace.


When the stop condition that is set in parameter setting screen is satisfied
the execution is finished. Pushing [STOP] soft key aborts the execution.
The following is the screen example of the trace execution by SIGNAL
TRANSITION mode.

In SIGNAL TRANSITION mode, graphic display is not refreshed until


any signal for sampling trigger changes.

647
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

3.5.4 When the execution is finished, the result of trace is displayed. The
Operation after following is the screen example of trace by TIME CYCLE mode.
Execution of Trace

The cursor indicating current position is initially displayed on the original


point (0 point).
The position of the cursor is displayed in CURSOR POSITION in the
upper of the screen. The cursor can move horizontally.
The following is the screen example of trace by SIGNAL
TRANSITION mode.

After the execution, following operation is enabled.

648
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

(1) SCROLL OF SCREEN


Using cursor up/down key and page up/down key enables the vertical
scroll for the specified signal. Using cursor right/left key, [NEXT>>]
soft key and [PREV<<] soft key enables the horizontal scroll of the
graph.
(2) AUTOMATIC CALCULATION OF THE SELECTED RANGE
Pushing [POS MARK] soft key marks the current position and
displays the mark cursor. If the mark cursor duplicates with the current
position cursor, the current position cursor has priority of display. The
MARK POSITION that shows the position of the mark cursor and
SELECT RANGE that shows the range between the mark cursor
and the current position cursor are displayed in the upper of screen.
Moving the current position cursor changes these values. Pushing
[POS MARK] again releases the select range mode.

(3) ZOOM IN/ZOOM OUT OF WAVEFORM


Pushing [ZOOM IN] soft key magnifies the display of chart. Pushing
[ZOOM OUT] soft key reduces the display of chart. Pushing these soft
keys also change the scale value of the graduation on the graph. When
trace is just finished, the default zooming level was the most magnified
level. In [ZOOM OUT] mode, gray box is displayed as following
screen example when the transitions of signal cannot be expressed
accurately enough. The limitation of [ZOOM OUT] displays all of
result of the trace in one page.

649
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

(4) EXCHANGE OF SAMPLING SIGNAL


Pushing [MOVE UP] soft key exchanges the signal indicated by the
signal cursor for the signal one line above. Pushing [MOVE DOWN]
soft key exchanges the signal indicated by the signal cursor for the
signal one line below. The result of the operation is cancelled by the
execution of trace or putting the power off. When you would like to
preserve the order of displayed signals against the executing or
powering off, please change the order on SAMPLING ADDRESS
screen.

3.5.5 The trace function for PMCNB6 is different from the trace function,
Comparison With the [PMCDGN] [TRACE], or the analysis function, [PMCDGN]
[ANALYS], for PMCNB/NB2 in the specification of display and setting
Function of FS15B parameter.
(PMCNB/NB2) However, you can get the same result of the trace as PMCNB/NB2 by
parameter setting.
The way of setting of the parameters to get the same result of the trace as
PMCNB/NB2 is described as follows.

650
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

(1) Setting equivalent to the [TRACE] screen for PMCNB/NB2


The parameters in page 1

By setting SAMPLING MODE = SIGNAL TRANSITION,


sampling equivalent to [TRACE] function of PMCNB/NB2 is
performed.
Furthermore, enhancements on PMCNB6 are the ability to change
the sampling cycle time and the capacity of sampling data by setting
RESOLUTION and FRAME parameters. In addition, the result
of sampling is displayed in easy to understand format of time chart.
The parameters in page 2

651
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

If you input signals from bit0 to bit7 into SAMPLING ADDRESS,


this setting is equivalent to input of the byte address for
PMCNB/NB2. The trigger setting of the sampling signals is
equivalent to the set of mask data (MASK DATA) for
PMCNB/NB2.
(2) Setting equivalent to none trigger start of the [ANALYS] screen for
PMCNB/NB2 (CONDITION = 0 and TRIGGER MODE = 0)

(3) Setting equivalent to TRIGGER MODE = 0:AFTER,


1:ABOUT, 2:BEFORE of the [ANALYS] screen for
PMCNB/NB2

The value of TRIGGER POSITION is equivalent to AFTER,


ABOUT, BEFORE for PMCNB/NB2. The value 0 means
AFTER. The value 100 means BEFORE. The value from 1
to 99 means ABOUT.

652
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

The point of the enhancement is the ability to adjust the ratio of data
before and after the trigger position.
(4) Setting equivalent to TRIGGER MODE = 3:ONLY of the
[ANALYS] screen for PMCNB/NB2

The example samples the signals specified in page 2 when the


sampling condition specified in SAMPLING CONDITION is on.

653
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

3.6 The I/O Link Monitor screen and the I/O Unit Allocation screens are for
checking I/O Link connection and for allocating I/O Unit.
I/O LINK MONITOR
AND ALLOCATION D I/O Link Monitor screen: I/O Units connected via I/O Link are
displayed in order of Group number.
OF I/O UNIT D I/O Unit Allocation viewer screen: I/O Units Allocation to X and Y
addresses are displayed.
D I/O Unit Allocation Editor screen: I/O Units can be allocated to X and
Y addresses.
Change of screens

NOTE
Soft key [EDIT] appears only when programmer function is
enabled by setting PROGRAMMER ENABLE to YES at
GENERAL screen of PMC Settings. While Online Monitor
function is active, you can not reach I/O Unit Allocation
Editor screen. To use I/O Unit Allocation Editor function, you
have to disable Online Monitor function at PMC Setting
screen by choosing NOT USE for RS232C and
FBUS settings.

654
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.6.1 I/O Link Monitor screen shows the types and the ID codes of I/O Units
I/O Link Monitor screen that are connected to I/O Link in order of Group number.
You can confirm the connection of I/O Units type at this screen.
Call this screen by pressing of soft key [I/O LINK] in PMCDGN.

Table 3.6.1. Displayed type and true type of I/O Units

Displayed I/O Unit ID True I/O Unit

CONNECTION UNIT 80 Connection Unit

OPERATOR PANEL Connection Unit for Operators


82
Panel

I/OB3 83 I/O B3

IO UNITMODEL B 84, I/O UnitMODEL A


86,
87

PLC SERIES 9030 PLC SERIES 9030


45

POWER MATE / IO LINK BETA 4A Power Mate or I/O Link Beta

SERIES 0 50 Series 0

OPERATOR IF BOARD (MPG1) Machine Operators Panel Inter-


53
face

LINK CONNECTION UNIT 96 I/O Link Connecting Unit

I/O UNITMODEL B I/O UnitMODEL B


9E

655
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

Displayed I/O Unit ID True I/O Unit

RJ MATE 61 RJ Mate

CONNECTOR PANEL MODULE A9 I/O module for connector panel

OPERATOR PANEL A1 AA I/O module for operators panel

OPERATOR I/F BOARD (MPG3) 6B Operator Interface(with MPG)

LOADER I/O AF I/O Board for Loader

ROBOCUT DIF B0 DIF Board for ROBOCUT

ROBOCUT MIF B1 MIF Board for ROBOCUT

I/O CARD B2 I/O board

ROBOSHOT I/O CARD A B3 I/O for ROBOSHOT

LOADER I/O (MATRIX) B4 I/O Board for Loader(Matrix)

PROCESS I/O FA B5 Process I/O for RJ3

PROCESS IO 89 Process I/O for RX

I/O LINK ADAPTER 8B I/O Link adapter

ROBOT CONTROLLER 52 Controller for RX

PLC SERIES 90 54 PLC SERIES 90

OPERATOR PANEL 95 I/O for Series 0

LASER OSCILLATOR 97 Laser Oscillator

FIXED I/O TYPE A 98 I/O for Robot Type A

FIXED I/O TYPE B 99 I/O for Robot Type B

ASI CONVERTER 77 ASi Converter

OPERATOER PANEL B I/O Module(for Operator Panel


A8
48/32)

MACHINE OPERATOER PANEL I/O Module(for Machine Operator


A8
A Panel of 0 Type)

CONNECTION UNIT C1 (MPG) A8 Connection Unit C1(with MPG)

MACHINE OPERATOER PANEL I/O Module (for Machine Operator


A8
B Panel )

I/O MODULE WITH LCD A8 LCD display embedded I/O

UNKNOWN UNIT Unsupported I/O Unit

CAUTION
I/O Units not for Series FS15i are written in Table 7.8.1.

656
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.6.2 I/O Link Allocation Viewer screen shows I/O Units allocation to X and
I/O Unit Allocation Y addresses.
You can confirm the allocation of I/O Units at this screen.
Viewer screen Call this screen by pressing of soft key [I/O LINK] [I/O MODULE]
in PMCDGN.

657
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

3.6.3 Allocate I/O Units to X and Y addresses at I/O Unit Allocation Editor
I/O Unit Allocation screen.
Call this screen by pressing soft key [I/O LINK] [I/O MODULE]
Editor screen [EDIT] in PMCDGN.

3.6.3.1 Soft Keys in I/O Unit Allocation Editor screen


Operations

(1) Allocation I/O Units to X and Y addresses


(1.1)Set the cursor at address to which you will allocate new I/O Unit.
(1.2)Type Group. Base. Slot. Name and press INPUT key.
Ex) In case you allocate Group=1, Base=0, Slot=5,
Name=ID16A to X10, set the cursor at X10 and 1.0.5.
ID16C INPUT

658
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

NOTE
As to the allocation name of I/O Unit, please refer to FANUC
PMC Programming Manual (LADDER Language) Chapter
I, 3.2 Table3.2.2

(1.3)The I/O Unit is allocated to address of the cursor position for the
I/O Unit size.
In case of above example (1.2), I/O Unit is allocated at X10 and
X11 like as follows.

659
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN) PMCNB6 MANIPULATION B61863E/14

CAUTION
1 Turn off and on the power after you store the Ladder to Flash
ROM in order to make the allocation effective.
2 The Ladder program is not stopped automatically when you
open I/O Unit Allocation Viewer screen or Editor screen.

(2) Delete allocation


(2.1)Set the cursor at allocation of which you will delete and press soft
key [DELETE].
(2.2)The allocation is deleted.
(3) Delete all allocation
(3.1)Press the right end soft key.
(3.2)Press soft key [CLEAR ALL].
(3.3)ARE YOU SURE TO DELETE ALL ALLOCATION DATA?
is displayed.
(3.4)Press soft key [YES].
(3.5)Allocation of X and Y are all deleted.

660
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
B61863E/14 PMCNB6 MANIPULATION (PMCDGN)

3.6.3.2
Error Message Error message Meaning and solution

Meaning:
GROUP NUMBER Too large Group number is input.
IS TOO LARGE Solution:
Input Group Number below 16.

Meaning:
Too large Base number is input.
BASE NUMBER IS
TOO LARGE Solution:
I/O UnitB (##,#1#10): Input Base number 0
Other I/O Unit: Input 0 or 1.

Meaning:
Too large Slot number is input.
SLOT NUMBER IS
TOO LARGE Solution:
I/O UnitB: Input Slot number below 31
Other I/O Unit: Input Slot number below 11

Meaning:
Too small Slot number is input.
SLOT NUMBER IS
TOO SMALL Solution:
I/O UnitB: Input Slot number 0 or above
Other I/O Unit: Input Slot number above 0

Meaning:
I/O Unit for X is allocated to Y address or I/O Unit for Y
I/O UNIT NAME is allocated to X address.
MISMATCH
Solution:
Confirm the I/O Unit Name and the address

Meaning:
I/O Unit name is not correct.
ILLEGAL I/O UNIT
NAME Solution:
Input correct name described at Chapter I.3.2 Table
3.2.2.

Meaning:
There is no enough space for the size of I/O Unit you
will allocate.
Meaning:
NOT ENOUGH This message is displayed also in case you will allo-
SPACE cate to the address in which other I/O Unit has been
allocated.
Solution:
ReInput the allocation after you delete the allocation
under the cursor and make space.

661
4. PMC DATA SETTING AND
DISPLAY (PMCPRM) PMCNB6 MANIPULATION B61863E/14

4 PMC DATA SETTING AND DISPLAY (PMCPRM)

662
4. PMC DATA SETTING AND
B61863E/14 PMCNB6 MANIPULATION DISPLAY (PMCPRM)

4.1 This screen enables the entry and display of parameters for the timers,
counters, keep relay, and data tables, which are held in nonvolatile
OVERVIEW memory. To use this procedure, first click the [PMCPRM] soft key on the
PMC basic module.

663
4. PMC DATA SETTING AND
DISPLAY (PMCPRM) PMCNB6 MANIPULATION B61863E/14

4.2 Usually, no data can be entered for PMC parameters because they are
protected. The following two methods can be used to make it possible to
METHOD FOR enter data for them.
ENTERING PMC D If the sequence program is running (RUN state) (usually, this method
PARAMETERS should be used when the machine is operating.)
i) Place the NC in MDI mode or bring it to an emergency stop.
ii) Set PWE on the NC setting screen to 1 (see the following table).
iii) Alternatively, set the program protect signal (KEY4) to 1 (only if
counters or data tables are involved).
iv) The parameters are released from protection; so data can be entered
for them (see the following table).
PWE KEY4
Timer f
Counter f f
Keep relay f
Data table f f

v) After entering data for the parameters, return PWE or the KEY4
signal to the previous state.
D If the sequence program can be stopped (STOP state), for example,
while it is being debugged
i) Stop the sequence program.
ii) The parameter protection is released; so data can be entered for
them.

WARNING
If a sequence program is stopped while the machine is
operating, the machine may behave unexpectedly. Before
stopping the sequence program, make sure that nobody is
near the machine and that the tool cannot interfere with the
workpiece or machine. Incorrect operation of the machine
presents an extreme risk of death or serious injury to the
user. Damage the tool, workpiece, and/or the machine is
also likely.

An attempt to enter data for protected parameters causes the error


message WRITE PROTECT to be displayed.

664
4. PMC DATA SETTING AND
B61863E/14 PMCNB6 MANIPULATION DISPLAY (PMCPRM)

4.3 It is possible to enter data continuously on each of the timer, counter, keep
relay, and data table screens. After continuous data entry, the cursor
CONTINUOUS DATA appears at the bottom of the most recently entered data.
ENTRY D Entry
(1) Use ; (EOB) as a data delimiter.
(Example) 100;200;300; + INPUT key
(2) Use ;= to enter the same value as the previous data.
(Example) Entering 100;=;=;200;= + INPUT key causes the
following data to be entered: 100,100,100,200,200
(3) Use ;; to skip an address for entry.
(Example) Entering 100;;200; + INPUT key causes the
second data item to be skipped from entry.

665
4. PMC DATA SETTING AND
DISPLAY (PMCPRM) PMCNB6 MANIPULATION B61863E/14

4.4 This screen is used to set and display the timer values for the machine
instruction timers (SUB3).
TIMER SCREEN
(TIMER)

Table contents
D NO.: Counter number specified for a machine instruction
counter
D ADDRESS: Address referenced by a sequence program
D DATA: Timer value
Timer number Minimum timer value Maximum timer value
that can be specified that can be specified

1 to 8 48ms 1572.8 s

9 to 150 8ms 262.1 s

666
4. PMC DATA SETTING AND
B61863E/14 PMCNB6 MANIPULATION DISPLAY (PMCPRM)

4.5 This screen is used to set and display the maximum and minimum counter
values for machine instruction counters (SUB5).
COUNTER SCREEN
(COUNTR)

Table contents
D NO.: Counter number specified for a machine instruction
counter
D ADDRESS: Address referenced by a sequence program
D PRESET: Maximum counter value (a minimum counter value is
specified by a counter instruction)
D CURRENT: Current counter value
Counter types and maximum values
Counter type PRESET maximum value CURRENT maximum value

BINARY 32767 32767

BCD 9999 9999

667
4. PMC DATA SETTING AND
DISPLAY (PMCPRM) PMCNB6 MANIPULATION B61863E/14

4.6 This screen is used for setting and displaying the Keep Relays.
KEEP RELAY
SCREEN (KEEPRL)

Contents of the table


D ADDRESS: Address refered by sequence Program
D 07 Contents of each bit
D HEX: Value of the byte data by hexadecimal nortatin
Since Keep Relay is nonvolatile memory, the contents are not lost even
if you turn off the power .
Keep Relay area consists of parts as follows.
User area K0 K39

Special use area (Note) K900 K909

CAUTION
Do not use the Special use area , because the relays in this
area are reserved for PMC system software use, and they
affect behavior of the PMC software. Set 0 to any relays
that are not mentioned below, to prevent unexpected
behavior of PMC.

668
4. PMC DATA SETTING AND
B61863E/14 PMCNB6 MANIPULATION DISPLAY (PMCPRM)

(1) Special use area ( K900 K909)


PMC type PMCNB6

Special use area 1 K900

Reserved K901 K909

#7 #6 #5 #4 #3 #2 #1 #0
K900 DTBL DSP MEMINP AUTORUN PRGRAM LADMASK

#7 DTBLDSP 0 : The Data Table Controlling Data screen is displayed.


1 : The Data Table Controlling Data screen is not displayed.
#4 MEMINP 0 : The status of signals is not allowed to be modified.
1 : The status of signals is allowed to be modified.
This setting is effective for the following screens.
Embedded PMC:
* LADDER Diagram Monitor screen (Forced I/O function)
FANUC LADDERII and Ladder Editting Package
* Signal Status Screen (Online function)
#2 AUTORUN 0 : Sequence program starts automatically at power on.
1 : Sequence program starts by pressing of soft key [RUN]
#1 PRGRAM 0 : Embedded debug function is unavilable.
1 : Embedded debug function is avilable.
This setting is effective for the following screens and functions
Embedded PMC:
* LADDER Diagram Editor screen, I/O Unit Allocation Editor screen
* I/O screen
FANUC LADDERII and Ladder Editting Package
* Ladder transfer function
* Ladder Editor Screen (Online function)
#0 LADMASK 0 : Ladder diagram is displayed.
1 : Ladder diagram is not displayed.
This setting is effective for the following screens and functions
Embedded PMC:
* LADDER Diagram Editor screen, I/O Unit Allocation Editor screen
* I/O screen
FANUC LADDERII and Ladder Editting Package
* Ladder transfer function
* Ladder Editor Screen (Online function)

CAUTION
Set always 0 to any other relays in Special us area than
mentioned above, to prevent unexpected behavior of PMC.

669
4. PMC DATA SETTING AND
DISPLAY (PMCPRM) PMCNB6 MANIPULATION B61863E/14

4.7 There are two data table types (data table control data table and data table).
DATA TABLE (DATA) (1) Data table control data screen (C.DATA)
Clicking the [DATA] soft key displays the data table control data
setting screen for data table management.

Table contents
D GROUP TABLE COUNT:Number of data items in the data table
D NO.: Group number
D ADDRESS: Data table start address (the same address can be
specified for different groups.)
D PARAMETER: Table parameter(NOTE)
D TYPE: Data length (0 = 1 byte, 1 = 2 bytes, 2 = 4 bytes)
D DATA: Number of data items in each data table
Soft key definitions
[G.DATA]: Clicking this soft key switches to the screen for setting
and displaying the data in the data table.
[G.CONT]: After the number of groups is entered, clicking this soft
key asserts the number of groups for the data table.
[NO.SRH]: After a group number is entered, clicking this soft key
moves the cursor to the specified group.
[INIT]: Clicking this soft key initializes the data table.
* The initial data is as follows:
NO. ADDRESS PARAMETER TYPE DATA
001 D0000 00000000 0 8000

670
4. PMC DATA SETTING AND
B61863E/14 PMCNB6 MANIPULATION DISPLAY (PMCPRM)

NOTE
The meanings of the table parameters are as follows:
#7 #6 #5 #4 #3 #2 #1 #0

0: Binary format
1: BCD format
0: Input protection disabled
1: Input protection enabled
0: Binary or BCD format (with bit 0 valid)
1: Hexadecimal format (with bit 0 invalid)

(2) Data table screen


If the data table control data is specified, clicking the [G.DATA] soft
key on the data table control data screen displays the data table setting
screen.

Table contents
D NO.
D ADDRESS: Address used by the sequence program
D DATA
Soft key definitions
[C.DATA]: Clicking this soft key switches to the data table control
data screen.
[GSRCH]: After the entry of a group number for a data table to be
searched in another group, clicking this key moves the
cursor to the beginning of that group.
[SEARCH]: After the entry of an address, clicking this key moves the
cursor to the specified address within the currently
selected group. When entering the address, the D can
be omitted from the beginning of the address. After
entering 101 for example, clicking this key moves the
cursor to data using D101.

671
5. SETTING MENU (SETING) PMCNB6 MANIPULATION B61863E/14

5 SETTING MENU (SETING)

Clicking the [SETING] soft key on the PMC basic module screen displays
the following setting menu screen.

Menu contents
1. GENERAL: Screen for displaying general setting data
2. EDIT/DEBUG: Screen for displaying setting data related to
editing and debugging
3. ONLINE: Screen for displaying the communication
settings for the onlinefunction. (It is
displayed by setting PROGRAMMER
ENABLE to YES on the GENERAL
screen.)
4. C LANGUAGE: Screen for displaying setting data related to C
Language function.
Clicking the soft keys explained above displays the respective setting
screens.
Some of the settings on this screen are saved to the keep relay. It is
possible to prevent changes to that part of the settings on this setting
screen, using a sequence program for writing to the keep relay.

672
B61863E/14 PMCNB6 MANIPULATION 5. SETTING MENU (SETING)

5.1 Clicking the [GENERAL] soft key displays the following screen.
SCREEN FOR
DISPLAYING
GENERAL SETTINGS
(GENERAL)

D PROGRAMMER ENABLE
YES: The builtin debug function is used.
NO: The builtin debug function is not used.
D AUTOMATIC LADDER START
AUTO: The sequence program is executed automatically when
the power is switched on.
MANUAL: The sequence program is executed by clicking the
sequence program execution soft key.
D SIGNAL STATUS WRITE ENABLE
YES: The online function can be used to enter data on the signal status
screen.
NO: The online function is prevented from entering data on the
signal status screen.
D DATA TABLE CONTROL SCREEN
YES: The PMC parameter data table control screen is displayed.
NO: The PMC parameter data table control screen is not displayed.
D SIGNAL TRACE START
AUTO: Trace function is executed automatically when the power
is switched on.
MANUAL: Trace function is executed by operating soft key.

673
5. SETTING MENU (SETING) PMCNB6 MANIPULATION B61863E/14

5.2
SCREEN FOR
DISPLAYING THE
SETTING DATA
RELATED TO
EDITING AND
DEBUGGING

D WRITE TO FROM (EDIT)


YES: The ladder program is automatically written to FROM after
editing.
NO: The ladder program is not automatically written to FROM
after editing.

674
B61863E/14 PMCNB6 MANIPULATION 5. SETTING MENU (SETING)

5.3 If PROGRAMMER ENABLE is set to YES on the GENERAL screen,


the [ONLINE] soft key appears on the setting menu screen. Clicking this
SCREEN FOR soft key displays the following screen.
SETTING/DISPLAYIN
G ONLINE MONITOR
PARAMETERS
(ONLINE)

Menu descriptions
D CPU ID
The CPU ID value is displayed. The value can also be entered here,
but its entry is usually not necessary.
D RS232C (prompt)
USE: An RS232C port can be connected to FANUC
LADDERII.
NOT USE: No RS232C port is used.
Note) If no RS232C is to be connected to FANUC LADDERII,
select NOT USE.
D CHANNEL
A channel number to be used is displayed. The number can also be
entered.
D BAUD RATE
300: A baud rate of 300 is specified.
600: A baud rate of 600 is specified.
900: A baud rate of 900 is specified.
1200: A baud rate of 1200 is specified.
2400: A baud rate of 2400 is specified.
4800: A baud rate of 4800 is specified.
9600: A baud rate of 9600 is specified.
19200: A baud rate of 19200 is specified.
D PARITY
NONE: No parity is specified.
ODD: Odd parity is specified.
EVEN: Even parity is specified.

675
5. SETTING MENU (SETING) PMCNB6 MANIPULATION B61863E/14

D STOP BIT
1 BIT: The number of stop bits is set to 1.
2 BITS: The number of stop bits is set to 2.
D TIMER 1
The value in communication parameter timer 1 is displayed. The value
can also be entered, but its specification is usually not necessary.
D TIMER 2
The value in communication parameter timer 2 is displayed. The value
can also be entered, but its specification is usually not necessary.
D TIMER 3
The value in communication parameter timer 3 is displayed. The value
can also be entered, but its specification is usually not necessary.
D MAX PACKET SIZE
The maximum packet size for the communication parameter is
displayed. The size can also be entered, but its specification is usually
not necessary.
D RS232C (status display)
The status of an RS232C port is displayed.
INACTIVE: No RS232C port is in use.
STOPPING: An RS232C port is closed.
STARTING: An RS232C port is open.
STANDBY: An RS232C port is waiting to be connected to
FANUC LADDERII.
CONNECTED: An RS232C port has been connected to FANUC
LADDERII.
If the ladder editing package is included in the system configuration, the
FBUS prompt menu appears above the RS232C status display menu,
and the FBUS status display menu appears below the RS232C status
display menu.
D FBUS (prompt)
USE: An FBUS port can be connected to the ladder editing
package.
NOT USE: No FBUS port will be connected to the ladder editing
package.
D FBUS (status display)
The status of an FBUS port is displayed.
INACTIVE: No FBUS port is in use.
STOPPING: An FBUS port is closed.
STARTING: An FBUS port is open.
STANDBY: An FBUS port is waiting to be connected to
FANUC LADDERII.
CONNECTED: An FBUS port has been connected to FANUC
LADDERII.
Soft key descriptions
[EMGSTOP]: Clicking this key causes communication to be
terminated. It is used if it is impossible to terminate a
connection due to abnormal communication.
[INIT]: Clicking this key initializes the parameter settings.

676
B61863E/14 PMCNB6 MANIPULATION 5. SETTING MENU (SETING)

5.4
SCREEN FOR
DISPLAYING
SETTING DATA
RELATED TO C
LANGUAGE
FUNCTION

D FUNCTION KEY EFFECTIVE


YES: Function keys are enabled when the user program displays the
user screen.
NO: Function keys are disabled when the user program displays the
user screen.
D INITIALIZE PMCMDI SCREEN
YES: When the screen is switched to the PMCMDI screen, the display
screen is initialized.
NO: When the screen is switched to the PMCMDI screen, the display
screen is not initialized.
D REJECT LANGUAGE
YES: The program of C language is not activated.
NO: The program of C language is activated.

677
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6 LADDER DIAGRAM MONITOR AND EDITOR

The LADDER Diagram Monitor screen displays the LADDER Diagram


with the status of the signals in the diagram. You can watch how the
LADDER Program works at this LADDER Diagram Monitor screen.
The LADDER Diagram Editor screen allows you to change the LADDER
Diagram, adding relays and functional instructions, and change the action
of LADDER Diagram.
Press soft key [PMCLAD] at PMC Main Menu to reach the LADDER
Diagram Monitor/Editor screen.

NOTE
You can hide [PMCLAD] soft key at PMC Main Menu by
setting the keep relay of K900.0 to 1.

LADDER Diagram Monitor/Editor function consists of following


screens.
LADDER Diagram Monitor screen (LADDER Diagram
Monitor screen)
Displays LADDER Diagram and the current status of relays and
others.
LADDER Diagram Editor screen
Edits LADDER Diagram by the net.
Net Editor screen
Edits the structure of a net in LADDER Diagram

678
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

Program List Viewer screen


Chooses the subprogram to be displayed at LADDER Diagram
Monitor screen.
Program List Editor screen
Edits LADDER Diagram by the subprogram. Also chooses the
subprogram to be displayed at LADDER Diagram Editor screen.
These screens can be reached as described bellow.

679
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

NOTE
1 When [PMCLAD] soft key is pressed at first time after CNC
power cycle, Program List Viewer screen is displayed. Then
use [ZOOM] soft key to select subprogram to reach
LADDER Diagram Monitor screen, and the subprogram that
you have selected appears on the screen. Once you
choose subprogram, pressing [PMCLAD] soft key will
directly reach LADDER Diagram Monitor screen. Changing
LADDER program by I/O function will make the Program List
screen appear at [PMCLAD] soft key again. See Program
List screen for more detail. (404A/04 does not have
Program List Viewer screen. LADDER Diagram Monitor
screen can be reached directly from PMC Main Menu
always.)
2 404A/04 can not display LADDER program that is protected
by Password function. To view a protected LADDER
program, you need FANUC LADDERII, LADDER Editing
Package, or upgrade version to 404A/05 or later. 404A/05
or later will ask for password when necessary.
3 [EDIT] soft key in LADDER Diagram Monitor screen
appears only when Programmer function is enabled: to
enable Programmer function, set PROGRAMMER
ENABLE to YES at GENERAL screen of PMC Settings.
While Online Monitor function is active, you can not reach
LADDER Diagram Editor screen. To use LADDER Diagram
Editor function, you have to disable Online Monitor function
at PMC Setting screen: choose NOT USE.

680
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.1 LADDER Diagram Monitor screen shows the on/off status of contacts
and coils, and the contents of address specified for parameter of functional
LADDER DIAGRAM instructions. You can investigate how the LADDER program is working
MONITOR SCREEN by this monitor screen.
You can use following operation at this screen, including Forced I/O
function (Forcing mode), by which you can force the relay or the address
parameters of functional instructions to a new status or value.
D Switch subprogram to show [LIST]
D Search for address or others [SEARCH MENU]
D Show data table of functional instructions [DATA TABLE]
D Go to LADDER Diagram Editor screen [EDIT]
D Forced I/O function (Forcing mode) number + INPUT key

681
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.1.1
Screen Structures Title information (REMARKS) Current subprogram Current position Range to search

Area for LADDER Diagram

Key input line Message line Additional information line

(a) Screen Structure


1. Title information (REMARKS) of the LADDER Program, the
current subprogram, and the current position information of the
Diagram displayed in this screen, are displayed above the
LADDER Diagram.
When you select a subprogram to be displayed, range for search
function is indicated at right of the top line as LOCAL or
GLOBAL. In case of LOCAL, the range for search function
is restricted within the current subprogram. In case of
GLOBAL, on the other hand, search function searches whole
of LADDER program, and switch current subprogram
automatically according to the result of searching.
2. In the additional information line near the bottom of the screen,
the following information of the address under the cursor when
the cursor is shown.
D Net number of the net with the cursor
D Address and its symbol and comment information
D Current value
3. In the message line, error messages or inquiry messages will be
displayed depending on the situation.
4. In the area for LADDER Diagram, 8 or 9 relays side by side, and
10 relays in vertical can be displayed at maximum.
(b) LADDER Diagram
1. The Functional Instruction occupies less space than the Diagram
of PMCNB/NB2 for FS15B. And some names of control
conditions are shortened as follows:
UPDOWN UPD CTR (SUB5), CTRC (SUB55)
CONT CNT SFT (SUB33)
CIRC CIR SPCNT (SUB46)
OVRD OVD SPCNT (SUB46)

682
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

2. Nets wider than the screen width are displayed as Continuous


Net using continuous marks (>A1>).
Same continuous marks mean they are connected with each other.

(c) Monitor
1. Contacts and coils are displayed in different colors according to
the status of the signal. The status of power flow is not displayed.
2. The contents of address parameters of functional instructions are
not shown in default setting. With the extended functional
instruction format, you can see the contents of the parameters.
See Setting Screen for the detail.
(d) Displaying Symbols and Comments
1. If an address has a symbol name assigned, the symbol name will
be displayed instead of the address itself at default setting. You
can force not to show symbol by setting. See Setting Screen
for the detail.
2. If the address used with coil has a comment string assigned, the
comment strings will be displayed at the right margin beside the
coil. You can use this margin area to display an additional relay
instead of the comment string by setting: at this setting, one more
relay can be displayed in each diagram line. See Setting Screen
for the detail.

683
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.1.2
Operations Soft keys of LADDER Diagram Monitor screen on PMCNB6

Main soft keys of LADDER Diagram Monitor screen

Program List LADDER Diagram Editor Screen Settings

Display Data Table Switches to Collective


Monitor screen

Search soft keys


Search Write Coil Pick up a Ladder Search next
Diagram net

Search Functional
Instruction Switch range
Jump to
Top/Bottom Search Address or Net Search previous

(a) Operation with Softkeys


1. [LIST] Go to Program List Viewer screen
Goes to Program List Viewer screen to choose subprogram to be
displayed at LADDER Diagram Monitor screen.
2. [SEARCH MENU] Search & Jump
Change soft keys to Search soft keys. Use Return key [<] to
return to the Main soft keys.
Search soft keys consists of followings:
D [TOP BOTTOM] Jump to Top/Bottom
Jumps to the top of LADDER Program. If the top is
displayed already, then jump to the bottom.
D [SEARCH] Search Address/Net
Searches the PMC address or the net according to the
preceding string. You can specify both of bit address and byte
address.
When digits are entered, the digits are supposed to be a net
number and the screen will jump to the net of the net number.
When a string other than digits is entered, the string is
examined as a symbol for some PMC address at first. If the
string matches a symbol, then the address that the symbol
means will be searched for.
If no symbol matches the string, then the string is examined
as PMC address at next. If the string indicates correct PMC
address, then the address will be searched for.
When cursor is hidden, the net that has the specified net
number or contains the specified address will be shown at the
top of the screen.
When cursor is shown, the cursor moves to the relay or the
parameter to show the found address directly.
D [WRITE SEARCH] Search Write Coil
Searches for the write coils with the address that entered
string means. Any contacts with the address are ignored.
D [FUNC SEARCH] Search Functional Instruction
Searches for the functional instructions by its SUB number
or its mnemonic name such as TMR or END2.

684
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

D [PICKUP] Picking up ladder nets.


Picks up ladder nets with coil which you want to monitor, on
Collective Monitor screen. When picks up is complete, the
mark displayed to the top of net..
D [PREV] Search previous
Repeats to search the same thing backward (upward).
D [NEXT] Search next
Repeats to search the same thing forward (downward).
D [GLOBAL] / [LOCAL] Change range for searching
Changes the range for searching between GLOBAL and
LOCAL; GOBAL means whole of program, and LOCAL
means within the displaying subprogram. Current range for
searching is indicated at right of the information line at top
of screen.
3. [DATA TABLE] Go to Functional Instruction Data Table Viewer
screen
Goes to Functional Instruction Data Table Viewer screen to
examine contents of Data Table of functional instructions such as
COD (SUB 7) and CODB (SUB 27), which have Data Table in
themselves. This soft key appears only when the cursor is on a
functional instruction that has Data Table.
4. [EDIT] Go to LADDER Diagram Editor screen
Goes to LADDER Diagram Editor screen. This soft key appears
only when Programmer function1 is enabled. And activating
Online Monitor function2 disables this soft key.
5. [SWITCH] Switches to Collective Monitor screen.
Switches to Collective Monitor screen.
6. [SCREEN SETING] Screen settings
Goes to setting screen for LADDER Diagram Monitor screen.
You can change various settings for LADDER Diagram Monitor
screen at the screen. Use Return key [<] to return to LADDER
Diagram Monitor screen. See Settings for LADDER Diagram
Monitor section for the detail.
(b) Other operations
1. Cursor move keys, Page change keys
With cursor hidden, you can move diagram in the screen by
up/down Cursor move keys and Page change keys.
Function of Cursor keys when cursor is hidden

With cursor displayed, you can move the cursor by all cursor
move keys and Page change keys. When cursor is placed on some
relay or some address parameter of a functional instruction, the
information about the address under cursor is displayed at
Additional Information Line.

685
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

1 To enable Programmer function, go to GENERAL screen of PMC


Settings, and choose YES at item PROGRAMMER ENABLE.
2 To deactivate Online Monitor function, go to ONLIEN screen of
PMC Settings, and choose NOT USE at settings of RS232C and
FBUS (if appears).
2. number + INPUT key
When cursor is shown, you can force the value of the address
under cursor by entering new value as number + INPUT key.
In this screen, Forced I/O function is limited only to Forcing
mode. This Forced I/O function asks you to confirm your
intention before it takes effect. Once it is confirmed that you
actually want to change value by this function, you can change
the value of the same relay or parameter without further
confirmation. However, after you move cursor or you operate
other functions, you will be asked when you use the Forced I/O
function again.

WARNING
1 You have to pay special attention to use Forced I/O function
to change status of signals. Inappropriate use of Forced I/O
function may cause unexpected reaction of machine. You
have to make it sure that nobody is near the machine
when you use this function.
2 As you use Forcing mode of Forced I/O function to change
status of signal, however, the signal may look proof against
Forced I/O function, because LADDER program or I/O
device writes into the signal repeatedly. In this case, even
if the signal looks unchanged, actual signal may be
changed in very short moment. You should be careful for
the reaction of machine to such signal changes.

NOTE
1 Forced I/O function is enabled when SIGNAL STATUS
WRITE ENABLE setting is set to YES in GENERAL
screen of PMC Settings. If the setting is NO, INPUT key
will be just ignored.
2 Parameters of timer functional instructions, TMR, TMRB,
and TMRC, which have special monitor formats, are not
supported by Forced I/O function.

(c) Notes for Search function


1. The string followed by [SEARCH] is treated as symbol first. In
case that the symbol D0 is assigned to the bit address R0.0,
the operation D0 + [SEARCH] will search the bit address
R0.0, instead of byte address D0.3
2. To search the symbol that consists of only digit characters, which
will usually be treated as net number, you can use leading space
to specify explicitly the string is symbol. For example, while
123 + [SEARCH] will search the 123rd net from top of the
LADDER, _123 + [SEARCH] (_ is space) will search
address with symbol 123.

686
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

3 In this case, you can still search the byte address D0 by entering
D00. The excess 0 avoids the conflict with the symbol D0.
3. When the range for searching is GLOBAL, and the target is found
in other than displaying subprogram, the screen will automatically
switch to the subprogram to which the found target belongs.
Searching GLOBAL net number that current subprogram does not
contain, for example, the subprogram that contains the net of the net
number will appear in the screen, displaying the net.
(d) Shortcuts
1. Right/left cursor move keys that are following some string means
searching forward/backward. You can use following strings for
this search operation:
D Digits for net number
D 1 for top, 0 for bottom
D S + digits, for Functional instructions
D Other string for symbol or bit/byte address
D Leading space always makes the string treated as a symbol
or address.
Example: _123+[SEARCH] (_ means space) will search
the symbol 123 instead of the 123rd net.
2. When cursor is hidden, left/right cursor move keys without string
act just like [PREV]/[NEXT] soft keys.
3. String followed by [SEARCH MENU] soft key in PMCLAD
Main soft keys starts searching directly. In this case, [SEARCH
MENU] soft key acts just like right cursor move key.
4. [SEARCH] soft key in Search soft keys without string searches
the address or the functional instruction under cursor forward. If
cursor is hidden, or cursor is placed neither on a relay nor on a
functional instruction, this operation just repeats the last
successful search forward, just like [NEXT] soft key.
5. [WRITE SEARCH] soft key without string searches forward a
write coil of the same address with relay under cursor. If cursor
is hidden, or cursor is not placed on a relay, this operation will
search a write coil of the bit address that is searched at last
successful search. If the last search was not made with bit
address, the last entered string for searching is used to determine
what bit address is to be searched for a write coil.
6. [FUNC SEARCH] soft key without string searches forward the
same functional instruction with one under cursor. If cursor is
hidden, or cursor is not placed on a functional instruction, this
operation will search a functional instruction that is searched at
last successful search. If the last search was not made for
functional instruction, the last entered string for searching is used
to determine what functional instruction is to be searched.
7. [LIST] soft key following string that indicates subprogram,
switches subprogram on LADDER Diagram Monitor screen.
Examples for strings to specify subprogram are following:
L1 Level 1
P10, 10 Subprogram P10
0(zero), G Whole of LADDER program (Global)

687
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.1.3 Functional Instruction Data Table Viewer screen shows the contents of
Functional Instruction data table that belongs to some functional instructions.
To reach this screen, at LADDER Diagram Monitor screen, press [DATA
Data Table Viewer TABLE] soft key that is displayed when the cursor is on the following
Screen functional instructions which have a data table.
D Functional Instruction COD (SUB7)
D Functional Instruction CODB (SUB27)
Following operations are available at this screen.
D Search for data table number. [SEARCH NUMBER]
D Search for data value. [SEARCH VALUE]
D Change the displaying data digits. [BCD2],[BCD4]
(These soft keys can be operated
only at Functional Instruction
Data Table Viewer screen of
Functional Instruction COD.)

Functional Instruction Data Table Viewer screen of Functional


Instruction COD.

688
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

(1) Screen Structures

1. The functional instruction name, the number of data table, data


length and data type are displayed above the Data Table.
2. In the message line, error messages or inquiry messages will be
displayed depending on the situation.
3. In case of functional instruction COD, the data of 6 lines and 14
columns can be displayed in the area for Data table.
In case of functional instruction CODB, the data of 4 lines and
14 columns can be displayed in the area for Data table.
(2) Operations
Soft keys of Functional Instruction Data Table Viewer screen of
functional insturction COD.

Softkeys of Functional Instruction Data Table Viewer screen of


functional insturction CODB.

1. [SEARCH NUMBER] Search for data table number


Searches the data table number which you specified.
Then the cursor is displayed on the data of the target number.
And the cursor is disappeared when you operate something.

689
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

2. [SEARCH VALUE] Search for data value


Searches the data value which you specified.
Then the cursor is displayed on the target data.
And the cursor is disappeared when you operate something.
3. [BCD2] Display BCD2 digits
Changes the display data type to 2 digits of BCD. This operation
only switches the display data type. So it does never edit the data
on memory.
4. [BCD4] Display BCD4 digits
Changes the display data type to 4 digits of BCD. This operation
only switches the display data type. So it does never edit the data
on memory.
5. Cursor move keys, Page change keys
You can scroll screen by right/left cursor move keys and Page
change keys.

690
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.1.4
Setting Screen

1st page of setting screen

(a) Setting items


LADDER Diagram Monitor Setting screen contains the setting items
below:
D ADDRESS NOTATION
Determines whether the bit and byte addresses in the LADDER
Diagram are displayed as corresponding symbols, or the
addresses themselves.
SYMBOL (default)
Addresses that have a symbol are displayed by the symbols.
Addresses without symbols are displayed by the addresses
themselves.
ADDRESS
All addresses are displayed as the addresses themselves even
if they have a symbol.
D FUNCTION STYLE
Change the shape of functional instructions. There are three
options as below. You have to choose other than COMPACT
to show the current values of address parameters of functional
instructions.
COMPACT (default)
Occupies least space in diagram. Monitors of current values
of address parameters are omitted.
WIDE
Extends the box horizontally to reserve spaces for the
monitors of current values of address parameters. The box
becomes wider than COMPACT.

691
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

TALL
Extends the box vertically to reserve spaces for the monitors
of current values of address parameters. The box becomes
taller than COMPACT.
Display styles of functional instructions

The displays of current values of address parameters change their


format according to each parameter. Refer to the table in
Display Format for Parameters for detail.
When you place the cursor on an address parameter, its current
value is displayed in the Additional Information Line in both
formats of binary decimal, and BCD (or hexadecimal binary).
D RELAY COMMENT
Set the style of relay comment. These are three options as below.
When you display relay comment, less ladder diagram nets are
shown.
NONE (default)
Relay comments are not displayed.
1 LINE
Relay comments are displayed in one line. Up to 15
characters can be displayed. Characters after 16th character
will not be displayed. Width of a relay with comment of more
than 7 characters will be extended.
2 LINE
Relay comments are displayed in two lines. Up to 30
characters can be displayed. Width of a relay with comment
of more than 7 characters will be extended.
Display styles of relay comment

NONE

1 LINE

2 LINE

692
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

D SHOW COIL COMMENT


Determines whether to show coil comments.
YES (default)
Right margin of 2 lines of 15 characters is reserved for
display of coil comments.
NO
Right margin is used to extend diagram by one more relay,
instead of showing coil comment. The screen position bar is
also displayed at the right edge of the screen in this option.
Show Coil comment setting

D SHOW CURSOR
Determines whether to show cursor.
YES
Cursor is displayed. Cursor move keys will move the cursor.
When the cursor is placed on bit or byte addresses, the
information of the address is displayed at Additional
Information Line. When you search something with the
cursor displayed, the cursor goes directly where it is found.
This option is recommended for search operation with
LADDER program that contains many large nets.
NO (default)
Cursor is not displayed. Up/down cursor move keys will
scroll the contents of screen directly. When you search
something with the cursor hidden, the net, which contains it,
will appear at the top of the screen.
D SUBPROGRAM NET NUMBER
Determines whether a net number is counted as LOCAL
starting from the top of current subprogram, or is counted as
GLOBAL starting from the top of whole program. This setting
also affects the expression of net number at searching nets by
number.
LOCAL
Net number starts from 1 at top of current subprogram. Net
number is defined only within current subprogram. The net
number information at upper right of the screen is displayed
in the format displaying range / nets in subprogram NET.
GLOBAL (default)
Net number starts from 1 at top of Level 1 program. Net
number is defined identically at whole of program. The net
number information at upper right of the screen is displayed
in the format displaying range / subprogram range NET.

693
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

Definition of Net number

D WRAP SEARCH ENABLED


Allows search process to wrap from top/bottom to bottom/top to
continue to search.
YES (default)
Downward search will continue to search from top of
LADDER when reaches to bottom. Upward search will also
continue to search from bottom when reaches to top.
NO
Search process will fail when reached top or bottom, and
displays an error message at Message Line.

Wrap search

694
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

D DIAGRAM APPEARANCE SETTING


Changes the appearance of LADDER diagram. Lines, relays, and
functional instructions that constitute LADDER diagram can be
changed in the colors and the shapes. Samples of Off Contact,
On Contact, Monitor of Parameter in functional instruction
are displayed at right side. These samples change their
appearance according to the following current settings.
For the color setting, LADDER diagram is categorized into these
three parts, and you can specify their colors independently.
BOLD DIAGRAM
Sets thickness of diagram lines. This setting also affects
shapes of relays.
YES (default)
Diagram is drawn with thick lines. Relays are drawn in more
distinct shapes. You have to choose this option to make
following VARIABLE RELAY SYMBOL setting
effective.
NO
Diagram is drawn with thin lines. Relays are drawn in
smaller shapes.

Bold Diagram setting

695
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

NOTE
The setting BOLD DIAGRAM requires Character
registration function of CNC software, which is supported
by Series F002 version 03 or later. If CNC software does not
support it, diagram is always displayed with thin lines.

VARIABLE RELAY SYMBOL


Determines whether to change the shapes of relays according to
their on/off status, or to fix their shapes. This setting is effective
only when the setting BOLD DIAGRAM is set to YES.
YES
Shapes of relays change according to their on/off status. This
option is effective only when the setting BOLD
DIAGRAM is set to YES. If it is set to NO, shapes of
relays will not change regardless of this setting.
NO (default)
Shapes of relays will not change.
Change of relay shapes at on/off status

NOTE
The setting VARIABLE RELAY SYMBOL requires
Character registration function of CNC software, which is
supported by Series F002 version 03 or later. If CNC
software does not support it, shapes of relay will not change
according to their status.

ADDRESS COLOR
ADDRESS BACKGROUND
Colors for the relay address are set. You can specify these colors
by entering color number, or by moving right and left cursor. 16
colors (from No.0 to No.15) are available. Foreground color
should be different from background one.
DIAGRAM COLOR
DIAGRAM BACKGROUND
General color and its background color for LADDER Diagram.
You can specify these colors by entering color number, or by
using right and left cursor move keys to change the color number.
You can use 16 numbers from 0 to 15; however, some different
number may correspond to the same color. You can not specify
the same number to the foreground and the background colors.

696
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

ACTIVE RELAY COLOR


ACTIVE RELAY BACKGROUND
Color setting for the active relay. When a contact allows power
flow, and when a coil receives power, they are active and are
displayed with this color setting. When contacts and coils are not
active, they are displayed with general color. You can specify
these colors in the same manner as color setting of DIAGRAM
COLOR and DIAGRAM BACKGROUND.
PARAMETER COLOR
PARAMETER BACKGROUND
Color setting for the monitor of functional instruction
parameters. They are displayed when functional instructions are
displayed in the shape other than COMPACT. You can specify
these colors in the same manner as color setting of DIAGRAM
COLOR and DIAGRAM BACKGROUND.
COMMENT COLOR
COMMENT BACKGROUND
Colors for the relay comment are set. You can specify these
colors by entering color number, or by moving right and left
cursor. 16 colors (from No.0 to No.15) are available. Foreground
color should be different from background one.
(b) Soft keys
LADDER Diagram Monitor Setting screen has the soft keys of options
and following:
D [INIT] Initialize all settings
All settings will be initialized to the default values.

697
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.1.5 The following table shows all monitor formats for each parameter of each
Display Format for functional instruction.
Parameters NOTE
1 Variable in Monitor Format field means that this
parameter changes its size according to the other
parameter. Refer to the descriptions for each functional
instruction for detail.
2 Functional instruction with * mark has Data table.

No. Name Parameter Monitor Format No. Name Parameter Monitor Format
1 END1 18 XMOV 1 constant
2 END2 2 4digits BCD
3 TMR 1 special 3 4digits BCD
4 DEC 1 2digits BCD 4 4digits BCD
2 constant 19 ADD 1 constant
5 CTR 1 special 2 4digits BCD
6 ROT 1 constant 3 4digits BCD
2 4digits BCD 4 4digits BCD
3 4digits BCD 20 SUB 1 constant
4 4digits BCD 2 4digits BCD
7 COD * 1 constant 3 4digits BCD
2 2DIGITS BCD 4 4digits BCD
3 4digits BCD 21 MUL 1 constant
8 MOVE 1 constant 2 4digits BCD
2 constant 3 4digits BCD
3 2digits HEX 4 4digits BCD
4 2digits HEX 22 DIV 1 constant
9 COM 1 constant 2 4digits BCD
10 JMP 1 constant 3 4digits BCD
11 PARI 1 1byte binary 4 4digits BCD
14 DCNV 1 no monitor 23 NUME 1 constant
2 no monitor 2 4digits BCD
15 COMP 1 constant 24 TMRB 1 constant
2 4digits BCD 2 special
3 4digits BCD 25 DECB 1 constant
16 COIN 1 constant 2 variable binary
2 4digits BCD 3 constant
3 4digits BCD 4 2digits HEX
17 DSCH 1 constant 26 ROTB 1 constant
2 4digits BCD 2 variable binary
3 4digits BCD 3 variable binary
4 4digits BCD 4 variable binary
5 variable binary

698
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

No. Name Parameter Monitor Format No. Name Parameter Monitor Format
27 CODB * 1 constant 40 NUMEB 1 constant
2 constant 2 constant
3 1byte binary 3 variable binary
4 variable binary 41 DISPB 1 constant
28 MOVOR 1 2digits HEX 42 EXIN 1 8digits HEX
2 2digits HEX 43 MOVB 1 1byte binary
3 2digits HEX 2 1byte binary
29 COME 44 MOVW 1 2bytes binary
30 JMPE 2 2bytes binary
31 DCNVB 1 constant 45 MOVN 1 constant
2 no monitor 2 4bytes binary
3 no monitor 3 4bytes binary
32 COMPB 1 constant 46 SPCNT 1 4bytes binary
2 constant or 2 no monitor
variable binary 3 8digits HEX
3 variable binary 48 END3
33 SFT 1 4digits HEX 51 WINDR 1 2bytes binary
34 DSCHB 1 constant 52 WINDW 1 2bytes binary
2 variable binary 53 AXCTL 1 constant
3 variable binary 2 8digits HEX
4 variable binary 54 TMRC 1 constant
5 variable binary 2 special
35 XMOVB 1 constant 3 special
2 variable binary 55 CTRC 1 2bytes binary
3 variable binary 2 2bytes binary
4 variable binary 57 DIFU 1 constant
5 variable binary 58 DIFD 1 constant
36 ADDB 1 constant 59 EOR 1 constant
2 variable binary 2 variable HEX
3 constant or 3 constant or
variable binary variable HEX
4 variable binary 4 variable HEX
37 SUBB 1 constant 60 AND 1 constant
2 variable binary 2 variable HEX
3 constant or 3 constant or
variable binary variable HEX
4 variable binary 4 variable HEX
38 MULB 1 constant 61 OR 1 constant
2 variable binary 2 variable HEX
3 constant or 3 constant or
variable binary variable HEX
4 variable binary 4 variable HEX
39 DIVB 1 constant 62 NOT 1 constant
2 variable binary 2 variable HEX
3 constant or 3 variable HEX
variable binary 64 END
4 variable binary 65 CALL 1 no monitor

699
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

No. Name Parameter Monitor Format


66 CALLU 1 no monitor
68 JMPB 1 no monitor
69 LBL 1 no monitor
70 NOP 1 constant
71 SP 1 no monitor
72 SPE
73 JMPC 1 no monitor

700
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.1.6
Functional Instructions
of Special Monitor
forMat

TMR Displays in Current/Preset format by seconds


Displays in Current/Preset format by BCD or binary according to the Counter Type setting in LADDER
CTR
Program.
TMRB Displays current value by seconds (Preset value is displayed by milliseconds)
The 2nd parameter shows preset value, and the 3rd parameter shows current value as their monitor
displays.
These two monitor displays changes their format according to the 1st parameter as below:
1st Parameter Precision Display Format
0 8 ms by second
TMRC
1 48 ms by second
2 1 second HH:MM:SS
3 10 second HH:MM:SS
4 1 minute HH:MM

701
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.2 At LADDER Diagram Editor screen you can edit LADDER program to
change its behavior.
LADDER DIAGRAM To reach LADDER Diagram Editor screen, press [EDIT] soft key at
EDITOR SCREEN LADDER Diagram Monitor screen.
Following operations are available at LADDER Diagram Editor screen.
For more detail of these operations, refer to the descriptions of each key
to operate.

D Delete by net [DELETE]


D Move by net [CUT] & [PASTE]
D Copy by net [COPY] & [PASTE]
D Change address of bit address + INPUT key
contacts and coils
D Change parameters of number or byte address + INPUT
functional instructions key
D Add new net [NEW NET]
D Change construction of net [ZOOM]
D Make changes effective [UPDATE]
D Abandon changes [RESTORE]

You can modify LADDER even while the LADDER is running. At


modifying running LADDER, the modified LADDER will not run just
after each operation to modify it. PMC system preserves the LADDER
at the point of entering LADDER Diagram Editor screen, and the
preserved LADDER will continue to run while editing operation. When
exiting LADDER Diagram Editor screen, or pressing [UPDATE] soft
key, the modified LADDER starts to run and the modifications take
effects.

702
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

NOTE
1 [EDIT] soft key in LADDER Diagram Monitor screen
appears only when Programmer function is enabled. To
enable Programmer function, set PROGRAMMER
ENABLE to YES at GENERAL screen of PMC Settings.
While Online Monitor function is active, you can not reach
LADDER Diagram Editor screen. To use LADDER Diagram
Editor function, you have to disable Online Monitor function
at PMC Setting screen: choose NOT USE.
2 To edit LADDER protected by password, you have to unlock
the protection first. Enter password + INPUT key to unlock
it when password is requested.

703
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.2.1
Screen Structures

(a) Screen Structure


1. It is basically same with LADDER Diagram Monitor screen,
except that no monitor displays of relays and parameters of
functional instructions are displayed.
2. At right side of LADDER Diagram area, a position bar is always
displayed, which indicates screen position within current
subprogram: in LADDER Diagram Monitor screen, this position
bar is exclusively displayed with comments of write coil.
Sometimes, this position bar hides a part of write coil comments.
(b) LADDER Diagram
1. Style of LADDER Diagram is basically same with LADDER
Diagram Monitor screen, except that functional instructions are
drawn always in COMPACT format that has no monitor
displays.
2. Cursor is shown always. And the net, which will be an object of
following editing operations, is emphasized in screen.

704
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.2.2
Operations

(a) Operation with Softkeys


1. [LIST] Go to Program List Editor screen
Goes to Program List Editor screen to choose which subprogram
to be edited at LADDER Diagram Editor screen. The Program
List Editor screen can also edit subprograms; remove some
subprograms, or add new one.
2. [SEARCH MENU] Search & Jump
Change soft keys to Search soft keys. Use Return key [<] to
return to the Main soft keys.
Search soft keys are quite same with ones of LADDER
Diagram Monitor screen. See descriptions of search functions of
LADDER Diagram Monitor screen.
3. [ZOOM] Change construction of net
Goes to Net Editor screen to modify structure of the selected net.
For detail of editing operation at Net Editor screen, see
descriptions of Net Editor screen.
4. [NEW NET] Add new net
Create and add new net to cursor position. Pressing this soft key
reaches Net Editor screen, so that new net is constructed.
For detail of editing operation at Net Editor screen, see
descriptions of Net Editor screen.
5. [UPDATE] Make changes effective
Updates running LADDER program to currently edited
LADDER program, so that the all modifications will take effects,
and remains Editor screen. If it succeeds to update running
LADDER, edited LADDER starts to run.
Before updating LADDER program, edited LADDER program
is checked. If some problem is found, a message is displayed, and
updating process aborts. At some kind of error, cursor jumps
where the error is detected.

705
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

WARNING
You have to pay special attention to modify running
LADDER program. If you modify LADDER program in
wrong way, or update LADDER program with the machine
in improper status, it may cause unexpected reaction of the
machine. You have to make it sure that modifications you
make on LADDER program is appropriate, machine is in
proper status, and nobody is near the machine, when you
update LADDER program.

CAUTION
At updating LADDER program, it may take rather long time
to complete updating process in some cases according to
the activity of LADDER program. If it takes too long time, or
never complete at updating process, cancel updating
process and correct LADDER program, following
instructions in section 7.6.2.5 How to correct LADDER
program that never stops.

6. [SELECT NET] Select multiple nets


Selects multiple nets for following operations such as
[DELETE].
Pressing [SELECT NET] soft key leads to a mode to select one
or more nets for following editing operation. Use cursor move
keys and search functions to select nets, as you like. Being in
mode to select nets is indicated by dented [SELECT NET] soft
key, and the information of selected nets is shown in additional
information line at near bottom of screen.
7. [DELETE] Delete net
Deletes selected nets. The nets deleted by [DELETE] soft key are
lost. If you [DELETE] wrong nets, you have to abandon the all
modifications you have made, and restore LADDER program to
the original one before editing operation.
8. [CUT] Cut nets
Cuts selected nets. The cut nets are preserved in Paste Buffer, and
disappear from diagram. The contents of Paste Buffer before
[CUT] operation are lost.
[CUT] and [PASTE] soft keys are used to move nets.
The Paste Buffer can contain approx. 8000 steps maximum, and
[CUT] may fail to cut nets of over 8000 steps.

706
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

9. [COPY] Copy nets


Copy selected nets into Paste Buffer. No change on diagram will
be made. The contents of Paste Buffer before [COPY] operation
are lost.
[COPY] and [PASTE] soft keys are used to copy nets.
The Paste Buffer can contain approx. 8000 steps maximum, and
[COPY] may fail to copy nets of over 8000 steps.

10. [PASTE] Paste nets


Pastes nets at cursor position, which were stored into Paste Buffer
by [CUT] or [COPY] soft key.

Pressing [PASTE] soft key while selecting nets using [SELECT


NET] soft key, alters the selected nets with the nets in Paste
Buffer.

707
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

Pasting nets using [PASTE] soft key will not remove contents of
Paste Buffer. The contents of Paste Buffer will remain until
turning CNC power off.
11. [RESTORE] Abandon changes
Abandons all changes, and restores LADDER program to the one
at entering LADDER Diagram Editor screen, or last updated one
using [UPDATE] soft key. This soft key is useful when you make
wrong modifications and hard to recover from them.
12. [SCREEN SETING] Screen settings
Goes to setting screen for LADDER Diagram Editor screen. You
can change various settings for LADDER Diagram Editor screen
at the screen. Use Return key [<] to return to LADDER Diagram
Editor screen. See Settings for LADDER Diagram Editor
section for the detail.
13. [RUN] / [STOP] Run and stop LADDER program
Controls LADDER program execution. [RUN] soft key makes
LADDER run, and [STOP] soft key makes LADDER stop. Both
soft keys will confirm your intention. When you are sure to run
or stop LADDER program, press [YES] to take an action.

WARNING
1 You have to pay special attention to run/stop LADDER
program. Running/stopping LADDER program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. You have to make it sure
that machine is in proper status, and nobody is near the
machine when you run/stop LADDER program.
2 At stopping LADDER program, it may take rather long time
to complete to stop it in some cases according to the activity
of LADDER program. If LADDER takes too long time to
stop, or never stop, correct LADDER program, following
instructions in section 7.6.2.5 How to correct LADDER
program that never stops.

14. [<] Exit Editor


Updates running LADDER program to edited LADDER
program, so that the all modifications will take effects, and exits
Editor screen. If it succeeds to update running LADDER, edited
LADDER starts to run.
Before updating LADDER program, edited LADDER program

708
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

is checked. If some problem is found, a message is displayed,


updating process aborts and you can not exit this screen. At some
kind of error, cursor jumps where the error is detected.
The function keys such as SYSTEM key will not work when the
LADDER Diagram Editor screen is active.

WARNING
1 You have to pay special attention to modify running
LADDER program. If you modify LADDER program in
wrong way, or update LADDER program with the machine
in improper status, may cause unexpected reaction of the
machine. You have to make it sure that modifications you
make on LADDER program is appropriate, machine is
in proper status, and nobody is near the machine, when
you update LADDER program.
2 At updating LADDER program, it may take rather long time
to complete updating process in some cases according to
the activity of LADDER program. If it takes too long time, or
never complete at updating process, cancel updating
process and correct LADDER program, following
instructions in section 7.6.2.5 How to correct LADDER
program that never stops.

(b) Other operations


1. Cursor move keys, Page change keys
Cursor move keys and Page change keys move cursor on screen.
When cursor is placed on some relay or some address parameter
of a functional instruction, the information about the address
under cursor is displayed at Additional Information Line.
2. bit address + INPUT key
Changes bit address of relay under cursor.
3. number or byte address + INPUT key
Changes parameter of functional instructions under cursor.
But, there are some parameters that can not change by this
operation. If you see a message that means that this parameter can
not be changed, use Net Editor screen to change the parameter.
(c) Shortcuts
1. Same shortcut search operations with LADDER Diagram
Monitor screen are available. For their detail, see descriptions
about Shortcut operations of LADDER Diagram Monitor screen.
2. Same shortcut operations using [LIST] soft key with LADDER
Diagram Monitor screen are available.

709
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.2.3
Setting Screen

(a) Setting items


LADDER Diagram Editor Setting screen contains the setting items
below:
D ADDRESS NOTATION
Determines whether the bit and byte addresses in the LADDER
Diagram are displayed as corresponding symbols, or the
addresses themselves.
SYMBOL (default)
Addresses that have a symbol are displayed by the symbols.
Addresses without symbols are displayed by the addresses
themselves.
ADDRESS
All addresses are displayed as the addresses themselves even
if they have a symbol.
D RELAY COMMENT
Set the style of relay comment. These are three options as below.
When you display relay comment, less ladder diagram nets are
shown.
NONE (default)
Relay comments are not displayed.
1 LINE
Relay comments are displayed in one line. Up to 15
characters can be displayed. Characters after 16th character
will not be displayed. Width of a relay with comment of more
than 7 characters will be extended.
2 LINE
Relay comments are displayed in two lines. Up to 30
characters can be displayed. Width of a relay with comment
of more than 7 characters will be extended.

710
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

Display style of relay comment

NONE

1 LINE

2 LINE

D SHOW COIL COMMENT


Determines whether to show coil comments. Unlike LADDER
Diagram Monitor screen, the screen position gauge is always
displayed at the right edge of the screen.
YES (default)
Right margin of 2 lines of 15 characters is reserved for
display of coil comments.
NO
Right margin is used to extend diagram by one more relay,
instead of showing coil comment.

D SUBPROGRAM NET NUMBER

Determines whether a net number is counted as LOCAL starting


from the top of current subprogram, or is counted as GLOBAL
starting from the top of whole program. This setting also affects the
expression of net number at searching nets by number.
LOCAL
Net number starts from 1 at top of current subprogram. Net
number is defined only within current subprogram. The net
number information at upper right of the screen is displayed in the
format displaying range / nets in subprogram NET.
GLOBAL (default)
Net number starts from 1 at top of Level 1 program. Net number
is defined identically at whole of program. The net number
information at upper right of the screen is displayed in the format
displaying range / subprogram range NET.

711
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

D WRAP SEARCH ENABLED


Allows search process to wrap from top/bottom to bottom/top to
continue to search.
YES (default)
Downward search will continue to search from top of LADDER
when reaches to bottom. Upward search will also continue to
search from bottom when reaches to top.
NO
Search process will fail when reached top or bottom, and displays
an error message at Message Line.

D FORCE POSTPROCESS AFTER EDIT


Decides whether the postprocessing after editing LADDER
program, which makes LADDER program ready to run, will be
always done, or will be done only when LADDER program is
actually modified, at exiting LADDER Diagram Editor screen.
YES (default)
The postprocessing will be always done at exiting LADDER
Diagram Editor screen. Even at exiting Editor screen just after
entering it, LADDER structure will be checked because of the
postprocessing.
NO
The postprocessing will be done only after LADDER program
is actually modified. Before any modification on LADDER
program is done, you can always exit Editor screen without any
errors, even if the LADDER program has an error originally and
can not be executed.

712
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

D DIAGRAM APPEARANCE SETTING


Changes the appearance of LADDER diagram. Lines, relays, and
functional instructions that constitute LADDER diagram can be
changed in the colors and the shapes. Samples of Normal net,
Selected net, Protected net are displayed at right side. These
samples change their appearance according to the following current
settings.
For the color setting, LADDER diagram is categorized into these
three parts, and you can specify their colors independently, by
entering color number, or by using right and left cursor move keys to
change the color number. You can use 16 numbers from 0 to 15;
however, some different number may correspond to the same color.
You can not specify the same number to the foreground and the
background colors of a part.
BOLD DIAGRAM
Sets thickness of diagram lines. This setting also affects shapes
of relays.
YES (default)
Diagram is drawn with thick lines. Relays are drawn in more
distinct shapes. You have to choose this option to make
following VARIABLE RELAY SYMBOL setting
effective.
NO
Diagram is drawn with thin lines. Relays are drawn in
smaller shapes.

713
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

NOTE
The setting BOLD DIAGRAM requires Character
registration function of CNC software, which is supported
by Series F002 version 03 or later. If CNC software does not
support it, diagram is always displayed with thin lines.

ADDRESS COLOR
ADDRESS BACKGROUND
Colors for the relay address are set. You can specify these colors
by entering color number, or by moving right and left cursor. 16
colors (from No.0 to No.15) are available. Foreground color
should be different from background one.
DIAGRAM COLOR
DIAGRAM BACKGROUND
General color and its background color for LADDER Diagram.
SELECTED NET COLOR
SELECTED NET BACKGROUND
Color setting for the selected net. The nets that will be object of
following editing operation are displayed with this color setting.
PROTECTED NET COLOR
PROTECTED NET BACKGROUND
Color setting for the nets protected from editing operations. The
protected nets can not be selected as object of editing operations.
The nets with following functional instructions are protected
from deleting and creating when a subprogram (not whole
program) is chosen to edit.
END1 END3 SP
END2 END SPE
COMMENT COLOR
COMMENT BACKGROUND
Colors for the relay comment are set. You can specify these
colors by entering color number, or by moving right and left
cursor. 16 colors (from No.0 to No.15) are available. Foreground
color should be different from background one.
(b) Soft keys
LADDER Diagram Editor Setting screen has the soft keys of options
and following:
D [INIT] Initialize all settings
All settings will be initialized to the default values.

714
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.2.4 Pressing Return key [<] or [UPDATE] soft key will analyze edited
Error Messages and LADDER program and try to generate executable objects. If some error
is found at analyzing phase, you will see error message on screen, and
Their Solutions according to kind of error, cursor may jump to the place where the error
is found.
Following table shows error messages expected at LADDER analysis and
their meanings and solutions.
Error message Meaning and solution

Meaning:
CALL/CALLU is used in wrong place.
CALL/CALLU IN
BAD LEVEL. Solution:
CALL/CALLU must be used in Level 2 or in subpro-
grams. Do not use any other places.

Meaning:
COME is found between JMP and JMPE, and COM
and corresponding COME have different JMP/JMPE
status.
COME IN JMP. Solution:
COME and corresponding COM must have same
JMP/JMPE status. Review COM range and JMP
range, to adjust not to overlap with each other: it is
possible that one range includes the other completely.

Meaning:
There is no COM that corresponds to this COME.
COME WITHOUT
COM. Solution:
If COM is missing, add it in proper position. If the
COME is unnecessary, remove it.

DUPLICATE Meaning:
END1. Multiple END1, END2, or END3 are found.
DUPLICATE Solution:
END2. Remove extra END1, END2, or END3.
DUPLICATE
END3.

Meaning:
Same Laddress is used in plural LBLs.
DUPLICATE LBL. Solution:
If some of these LBLs are unnecessary, remove them.
If all of these LBLs is necessary, assign other Lad-
dresses to them to make all LBLs unique.

Meaning:
Same Paddress is used in plural SPs.
DUPLICATE P AD- Solution:
DRESS. If some of these SPs are unnecessary, remove them.
If all of these SPs is necessary, assign other Pad-
dresses to them to make all SPs unique.

715
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

Error message Meaning and solution

Meaning:
Plural TMRs, CTRs, TMRBs, DIFUs, or DIFDs have
DUPLICATE TMR the same number as their parameter.
NUMBER.(WARN- This is warning.
ING)
DUPLICATE CTR Solution:
NUMBER.(WARN- If some of them are unnecessary, remove them. If all
ING) of them are necessary, assign other number to pa-
DUPLICATE rameter of them to make them unique.
TMRB NUM- If two or more instructions with same parameter
BER.(WARNING) number will never be active simultaneously at one
DUPLICATE DIFU/ time, the LADDER program has a possibility to work
DIFD NUM- correctly, however, it is recommended from safety
BER.(WARNING) and maintenance points of view, that all these
instructions should have different parameter num-
ber with each other.

Meaning:
END IN COM. END, END1, END2, or END3 is found between COM
END1 IN COM. and COME.
END2 IN COM. Solution:
END3 IN COM. If COME is missing, add it in proper position. If COM
is unnecessary, remove it.

Meaning:
END IN JMP. END, END1, END2, or END3 is found between JMP
END1 IN JMP. and JMPE.
END2 IN JMP. Solution:
END3 IN JMP. If JMPE is missing, add it in proper position. If JMP is
unnecessary, remove it.

Meaning:
END is found between SP and SPE.
END IN SP. Solution:
If SPE is missing, add it in proper position. If END is
in wrong place, move it to proper position.

GARBAGE AFTER Meaning:


END. There are some nets after END, END2, or END3,
GARBAGE AFTER which will not be executed.
END2. Solution:
GARBAGE AFTER Remove unnecessary nets, and move necessary nets
END3. to proper position so that they will be executed.

ILLEGAL TMR Meaning:


NUMBER. TMR, CTR, TMRB, DIFU, or DIFD has parameter
ILLEGAL CTR number that is out of range.
NUMBER. Solution:
ILLEGAL TMRB If unnecessary, remove it. Assign correct number not
NUMBER. to exceed the maximum number defined by each
ILLEGAL DIFU/ PMC model.
DIFD NUMBER.

716
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

Error message Meaning and solution

Meaning:
JMP and corresponding JMPE have different COM/
COME status.
JMP/JMPE TO Solution:
BAD COM LEVEL. JMP and corresponding JMPE must have same
COM/COME status. Review JMP range and COM
range, to adjust not to overlap with each other: it is
possible that one range includes the other completely.

Meaning:
JMP and its destination differ in COM/COME status.
JMPB OVER COM Solution:
BORDER. JMPB and its destination must have same COM/
COME status. Review range of JMPB and COM
range, to adjust not to overlap with each other: it is
possible that one range includes the other completely.

Meaning:
JMPB jumps to different program level.
JMPB OVER LEV- Solution:
EL. JMPB can only jump to the same program level, or
within a subprogram. If the JMPB is unnecessary,
remove it. If LBL for the JMPB is missing, add it in
proper position. If it should be JMPC, correct it.

Meaning:
JMPC is used in other than subprogram.
JMPC IN BAD Solution:
LEVEL. JMPC is used to jump from a subprogram to level 2.
If the JMPC is unnecessary, remove it. If it should be
JMPB or JMP, correct it.

Meaning:
JMPC jumps to LBL between COM and COME.
Solution:
JMPC INTO COM. LBL for JMPC must be located out of any COM and
COME pair. If the JMPC is unnecessary, remove it. If
the LBL is located wrong, move it to correct position.
If the Laddress of JMPC is wrong, correct it.

Meaning:
JMPE is found between COM and COME, and JMP
and corresponding JMPE have different COM/COME
status.
JMPE IN COM. Solution:
JMPE and corresponding JMP must have same
COM/COME status. Review JMP range and COM
range, to adjust not to overlap with each other: it is
possible that one range includes the other completely.

Meaning:
There is no JMP that corresponds to this JMPE.
JMPE WITHOUT
JMP. Solution:
If JMP is missing, add it in proper position. If the
JMPE is unnecessary, remove it.

717
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

Error message Meaning and solution

Meaning:
LADDER PRO- LADDER program may be broken by some reason.
GRAM IS BRO- Solution:
KEN. This LADDER program must be all cleared once, and
remake LADDER program.

Meaning:
Can not find proper LBL for JMPB.
LBL FOR JMPB
NOT FOUND. Solution:
If JMPB is unnecessary, remove it. If LBL is missing,
add it in proper position.

Meaning:
Destination of JMPC is not level 2.
Solution:
LBL FOR JMPC IN JMPC is used to jump from a subprogram to level 2.
BAD LEVEL If the JMPC is unnecessary, remove it. If another LBL
of same Laddress that the JMPC is intended to jump
exists in the subprogram, assign different Laddress
to these two LBLs. If it should be JMPB or JMP, cor-
rect it.

Meaning:
Can not find proper LBL for JMPC.
LBL FOR JMPC Solution:
NOT FOUND. If JMPC is unnecessary, remove it. If LBL is missing,
add it in proper position: JMPC jumps into level 2. If it
should be JMPB or JMP, correct it.

Meaning:
There is no COME that corresponds to this COM.
MISSING COME
FOR THIS COM. Solution:
If COME is missing, add it in proper position. If COM
is unnecessary, remove it.

Meaning:
There is no JMPE that corresponds to this JMP.
MISSING JMPE
FOR THIS JMP. Solution:
If JMPE is missing, add it in proper position. If JMP is
unnecessary, remove it.

Meaning:
There is no SPE that corresponds to this SP.
MISSING SPE
FOR THIS SP. Solution:
If SPE is missing, add it in proper position. If SP is
unnecessary, remove it.

NO END. Meaning:
NO END1. END, END1, END2, or END3 is not found.
NO END2. Solution:
NO END3. Add END, END1, END2, or END3 in proper position.

Meaning:
Subprogram that is called by CALL/CALLU is not
NO SUCH SUB- found.
PROGRAM. Solution:
If it calls wrong subprogram, correct it. If the subpro-
gram is missing, create it.

718
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

Error message Meaning and solution

Meaning:
Write coil is necessary, but is not found.
NO WRITE COIL.
Solution:
Add proper write coil.

Meaning:
SP is found in wrong place.
SP IN BAD LEV-
EL. Solution:
SP can be used at top of a subprogram. Correct it so
that no SP exists in other place.

Meaning:
SP is found in level 3.
SP IN LEVEL3. Solution:
If END3 is located wrong, move it to correct position.
If the SP is unnecessary, remove it.

Meaning:
SP or SPE is found between COM and COME.
SP/SPE IN COM. Solution:
If COME is missing, add it in proper position. If the
COM is unnecessary, remove it.

Meaning:
SP or SPE is found between JMP and JMPE.
SP/SPE IN JMP. Solution:
If JMPE is missing, add it in proper position. If the
JMP is unnecessary, remove it.

Meaning:
There is no SP that corresponds to this SPE.
SPE WITHOUT
SP. Solution:
If SP is missing, add it in proper position. If the SPE is
unnecessary, remove it.

Meaning:
There are too many LBLs.
TOO MANY LBL. Solution:
Remove unnecessary LBLs. If this error still occurs,
adjust the construction of program to use less LBLs.

Meaning:
Unsupported instruction for this PMC model is found.
UNAVAILABLE Solution:
INSTRUCTION. Confirm that this LADDER program is correct one. If
this program is correct one, all these unsupported
instructions have to be removed.

719
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.2.5 If the following functional instructions are used with their ACT
How to Correct conditions (or RST conditions) are kept ON improperly, an attempt to
stop LADDER may take much time, or may not stop it actually.
LADDER Program that
Never Stops D WINDR / WINDW
In case of window function of highspeed response, this will not
cause the problem even if its ACT is stuck to ON.
D EXIN
D AXCTL
This will cause the problem also when RST condition is stuck to
ON.
D JMPB
When it jumps to the LBL before JMPB itself.
D JMPC
When it jumps to the LBL which leads to reach the same JMPC
again.
When LADDER can not stop, any operation to modify LADDER
program may take much time to complete, or may not complete.
Processes such as followings will be affected by this problem:
1. Stop LADDER program by [STOP] soft key.
2. Read new LADDER program from memory card or other devices
at I/O screen while current LADDER program is running.
3. Update running LADDER program at LADDER Diagram Editor
screen, by exiting the screen with return key [<], or by [UPDATE]
soft key.
To avoid this problem, find abovementioned functional instructions
whose ACT condition (or RST condition) is kept ON, and follow
instructions below to correct LADDER program to use these functional
instructions properly:
1. Confirm that machine is in safe condition, and then turn off
CNCs power.
2. Turn on CNCs power, with CAN and Z keys keeping held
down until CNCs finishes starting up completely, not to run
LADDER program automatically.
3. Go to LADDER Diagram Editor screen, find the instruction that
cause the trouble, modify logic around the instruction, so that
ACT condition (or RST condition) will once turn OFF after every
time the process of the instruction completes. In case that JMPB
or JMPC repeats same process, examine the condition to jump,
and reconstruct the structure of LADDER if necessary.
4. Write LADDER program into flash ROM at I/O screen.
5. Run LADDER program.
If the problem still remains after correction, there may be another
functional instruction that causes the trouble in the same way. Repeat
finding and correcting them in the same way, until the trouble is resolved.

720
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.3 At Net Editor screen, you can create new net, and modify existing net.
When [ZOOM] soft key is used to reach Net Editor screen, this screen is
Net Editor Screen in Modify Mode to modify existing net. When [NEW NET] soft key
is used, this screen is in New Mode to create new net from nothing.
Following operations are available at this screen:
D Place new contacts and coils bit address + [ ], [ ], etc.
D Change type of contacts and coils [ ], [ ], etc.
D Place new functional instructions [FUNC]
D Change type of functional instructions [FUNC]
D Erase contacts, coils, and functional instructions [ ]
D Draw/erase connecting lines [ ], [ ], [ ]
D Edit data table of functional instructions [DATA TABLE]
D Insert line/column [INSERT LINE], [INSERT COLUMN],
[APPEND COLUMN]
D Change address of contacts and coils bit address + INPUT key
D Change parameters of functional instructions number or byte
address + INPUT key
D Abandon modifications [RESTORE]

721
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.3.1
Screen Structures

(a) Screen structure


1. It is basically same with LADDER Diagram Editor screen, except
that only one net is in this screen, and that position bar at right
edge of screen does not appear at this screen.
2. Current edit mode is indicated at right of the top line as NEW
MODE or MODFY MODE. When [ZOOM] soft key at
LADDER Editor screen is used to reach Net Editor screen, the
screen is in Modify mode, and when [NEW NET] soft key is used,
it is in New mode.
3. Current net number is displayed at right of the top line. The net
number is same with the net number in previous LADDER
Diagram Editor screen.
4. Net Editor screen expands image of net horizontally for a wider
net according to its width, while LADDER Diagram
Monitor/Editor screen folds nets wider than screen width. When
net width is expanded over screen width, attempt to move cursor
out of screen will scroll net image to the direction.
The net of maximum size occupies area of 1024 elements, but
actually available area may be little less for internal use according
to the internal condition: element means the space that is
occupied by single relay.

722
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.3.2
Operations

(a) Operation with Softkeys


1. [ ],[ ],[ ],[ ],[ S
],[ R
]
Place relays (contacts and coils), or change type of existing
relays.
When one of these relay soft keys is pressed at cursor on blank
place, new relay of the soft key is placed under the cursor. When
the soft key follows a string that means a bit address, the bit
address is assigned to the newly placed relay. If no bit address
is given, last entered bit address is automatically used for the new
relay. If no bit address has been entered yet, the new relay will
have no address assigned to it. Contacts can be placed at other
than rightmost column, and coils can be placed at rightmost
column only.
Moving cursor onto an existing relay, pressing a relay soft key of
different type changes the type of relay under the cursor. But,
changing coil to contact, and changing contact to coil are
forbidden.

2. [FUNC] Enter and change functional instruction


Places functional instruction, or changes type of existing
functional instruction.
When [FUNC] soft key is pressed at cursor on blank place, new
functional instruction will be placed under the cursor: list of
available functional instructions is displayed, then choose type of
functional instruction to be entered. When [FUNC] soft key
follows a string that means number or name of a functional
instruction, the specified functional instruction is entered
directly, without the list screen.
Moving cursor onto an existing functional instruction, pressing
[FUNC] soft key changes the type of functional instruction under
the cursor.
3. [ ] Draw horizontal connection

723
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

Draws horizontal connection line. Or alters an existing relay to


horizontal line.
4. [ ] Erase relays and functional instructions
Erases relays and functional instructions under cursor.
5. [ ],[ ] Draw and erase vertical connection
Draw vertical connection line upward from right or left edge of
relay or horizontal line under cursor. Or erase existing vertical
lines.
If the relay or line under the cursor has no vertical line upward,
these soft keys have solid arrows, and indicate that pressing them
means drawing lines. On the other hand, if a vertical line already
exists under the cursor, arrows in these soft keys become pale
([ ], [ ]), and indicate that pressing them means
erasing lines.

6. [NEXT NET] Go to next net


Finishes editing current net, and goes to next net.
If [ZOOM] soft key at LADDER Diagram Editor screen is used
to reach Net Editor screen, [NEXT NET] will finish modifying
current net, and the next net will be an object of further editing
operation.
Action of [NEXT NET] soft key in Modify mode (modifying an existing net)

If [NEW NET] soft key at LADDER Diagram Editor screen is


used to reach Net Editor screen, [NEXT NET] will finish creating
current net, insert it into the LADDER program, and start with
blank to create another new net to be inserted next to the current
net.
Action of [NEXT NET] soft key in Modify mode (modifying an existing net)

724
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

7. [DATA TABLE] Edit data table


Reaches Functional Instruction Data Table Editor screen to edit
data table of functional instruction under cursor. This soft key
appears only when cursor is on a functional instruction that has
data table with it.
For detail of editing operation of data table, see descriptions of
Functional Instruction Data Table Editor screen.
8. [RESTORE] Abandon changes
Abandons all changes, and restores net to the one at starting
editing this net. If [NEW NET] soft key at LADDER Diagram
Editor screen is used to reach Net Editor screen, it will be back
to blank net, and if [ZOOM] soft key is used, it will be back to
the old net before modifications in this screen.
9. [INSERT LINE] Insert line
Inserts one blank line at cursor position. Diagram elements at or
below vertical cursor position will be shifted downward by one
line. Inserting line at middle of functional instruction box will
expand the box vertically to make a space between the input
conditions.

10. [INSERT COLUMN] Insert column


Inserts one blank column at cursor position. Diagram elements
at or on right of horizontal cursor position will be shifted to right
by one column. And if there is no room to shift the elements, a
new column is added and the Diagram area will be expanded to
right.

725
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

11. [APPEND COLUMN] Append column


Inserts one blank column at right of cursor position. Diagram
elements on right of horizontal cursor position will be shifted to
right by one column. And if necessary, net will be expanded to
right.

12. [<] Exit editor screen


Analyzes current editing net, and store it into LADDER program.
If some error is found in the net, it still remains Net Editor screen,
and an error message will be displayed. According to a kind of
error, cursor may indicate where the error is detected.
(b) Other operations
1. Cursor move keys, Page change keys
Cursor move keys and Page change keys move cursor on screen.
Net Editor screen expands image of net horizontally for a wider
net according to its width, while LADDER Diagram
Monitor/Editor screen folds nets wider than screen width. When
net width is expanded over screen width, attempt to move cursor
out of screen will scroll net image to the direction.
The net of maximum size occupies area of 1024 elements, but
actually available area may be little less for internal use according
to the internal condition: element means the space that is
occupied by single relay.
2. bit address + INPUT key
Changes bit address of relay under cursor.
3. number / byte address + INPUT key
Changes parameter of functional instructions under cursor.

726
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.3.3 Pressing [FUNC] soft key at Net Editor screen reaches Functional
Functional Instruction Instruction List screen at which you choose a functional instruction to be
entered from list of all available functional instructions.
List Screen

Operations at this screen are below:


(a) Operation with Softkeys
1. [SELECT] Select a functional instruction
Selects a functional instruction. The functional instruction under
cursor at that time is chosen, and entered into the editing net.
2. [SORT NUMBER], [SORT NAME] Rearrange functional
instructions list
Rearrange functional instructions list in two ways. [SORT
NUMBER] soft key arranges the list in numerical order with their
identifying numbers, on the other hand, [SORT NAME] soft key
arranges it in alphabetical order with their names. At beginning,
the list is arranged in alphabetical order.
3. [<] Quit selecting
Quits selecting functional instruction, and return to Net Editor
screen.
(b) Other operations
1. Cursor move keys
Cursor move keys move cursor on screen. According to the
cursor position, the functional instruction to be selected changes.
2. INPUT key
Act just like [SELECT] soft key.
(c) Shortcuts
1. [SELECT] soft key and INPUT key following number or name
of a functional instruction will select the specified functional
instruction directly, instead of the one under cursor.
2. When [FUNC] soft key in Net editor screen is pressed following
a string that means number or name of a functional instruction,
the specified functional instruction is entered directly, without
displaying Functional Instruction List screen.

727
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.3.4 At Functional Instruction Data Table Editor screen, you can edit the
Functional Instruction contents of data table that belongs to some functional instructions.
To reach this screen, at Net Editor screen, press [DATA TABLE] soft key
Data Table Editor that is displayed when the cursor is on the following functional
Screen instructions which have a data table.
D Functional Instruction COD (SUB7)
D Functional Instruction CODB (SUB27)
Following edit operations are available at this screen.
D Change the data table value. number + INPUT key
D Change the data length. [BYTE], [WORD], [D.WORD]
(These soft keys can be operated
only at Functional Instruction
Data Table Editor screen of
Functional Instruction CODB.)
D Change the number of data. [COUNT]
D Initialize all of data [INIT]

Functional Instruction Data Table Editor screen of Functional


Instruction CODB.

728
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

(1) Screen Structures

(a) Screen Structure


It is same with Functional Instruction Data Table Viewer screen.
(b) Display data
The cursor is shown always. You can edit the data that is pointed
by the cursor.
(2) Operations
Soft keys of Functional Instruction Data Table Editor screen of
functional instruction COD.

Soft keys of Functional Instruction Data Table Editor screen of


functional instruction CODB.

1. [SEARCH NUMBER] Search for data table number


Searches the data table number which you specified.
2. [SEARCH VALUE] Search for data value
Searches the data value which you specified.

729
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

3. [BCD2] Display BCD2 digits


Changes the display data type to 2 digits of BCD. This operation
only switches the display data type. So it does never edit the data
on memory.
4. [BCD4] Display BCD4 digits
Changes the display data type to 4 digits of BCD. This operation
only switches the display data type. So it does never edit the data
on memory.

NOTE
In the functional instruction COD (SUB7), the data type of
the data table can dynamically be changed either BCD2 or
BCD4 by BYT which is one of input condition. So the data
type of the data table is decided when the functional
instruction COD is executed. Decide the display data digit
according to the status of BYT by pressing either [BCD2]
soft key or [BCD4] soft key.
After turning the power on, the default displaying data type
is BCD4 digits. But if you change data type by pressing
[BCD2] soft key or [BCD4] soft key, the data type is kept until
you change again.
The data table of functional instruction COD is stored in the
memory as BCD4 digits type.
If you change the data type from BCD4 digits to BCD2 digits,
the data is displayed without higher 2digits. But the data
of higher 2digits is kept in the memory. So you return the
data type from BCD2 digits to BCD4 digits, the former BCD4
digits is recovered.
The input range of the data obeys the current data type.

5. [BYTE] Change to the BYTE length


Changes data length to 1 byte. If overflowed data is found, the
cursor points it, and this operation aborts. Then, correct it and
press [BYTE] soft key again.
6. [WORD] Change to the 2 BYTE length
Changes data length to 2 byte. If overflowed data is found, the
cursor points it, and this operation aborts. Then, correct it and
press [WORD] soft key again.
7. [WORD] Change to the 4 BYTE length
Changes data length to 4 byte.

NOTE
On functional instruction CODB, the data type is decided by
the first parameter of it.
So, if you change data type, the first parameter is changed
too.
When you added functional instruction CODB to ladder
program, the default data type is BYTE.

730
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

8. [COUNT] Change the number of data


Changes the number of data. If you expanded the number of data,
0 is set to expanded data as default.

NOTE
In case of functional instruction COD, the number of data is
decided by the first parameter of it.
In case of functional instruction CODB, the number of data
is decided by the second parameter of it.
If you change the number of data, these parameters are
changed too.

9. [INIT] Initialize all of data


Initializes all of data to 0. The number of data is not changed.
10. Cursor move keys, Page change keys
You can move the cursor by all cursor move keys and Page change
keys.
11. number + INPUT key
Changes the data that is pointed by the cursor.
The input range of the data obeys the data length and the display
data type.
Ex.) The case of functional instruction COD and displaying
BCD2 digits
The available data range: 0 to 99
Ex.) The case of functional instruction CODB and length of 2
BYTE
The available data range: 32768 to 32767
And you can input multiple numbers by the following methods.
(1) ;(EOB) is used for separating data.
(Ex.) Press the INPUT key after typing 100;200;300;
(2) ;= is used for inputting the same value as preceding data.
(Ex.) Press the INPUT key after typing 100;=;=;200;=,
and it becomes 100,100,100,200,200.
(3) ;; is used for skipping an input address.
(Ex.) Press the INPUT key after typing 100;;100. The
second data is not inputted.

731
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.3.5 Return key [<] or [NEXT NET] soft key analyzes current editing net, and
Error Messages and produce executable object of the net: new object of LADDER program is
not yet effective at this time. If some error is found through the analysis,
Their Solutions an error message is displayed, and cursor may indicate where the error is
detected, according to type of error.
Following table shows error messages expected at net analysis and their
meanings and solutions.
Error message Meaning and solution

Meaning:
When a net contains more than one coil, the coils
ALL COIL MUST should not have any contact beside them that affects
HAVE SAME IN- only one of the coils.
PUT Solution:
Left terminals of all coils in a net must be connected to
same input point.

Meaning:
Coil is located in bad position.
BAD COIL LOCA- Solution:
TION Coil can be located only at rightmost column. Any coil
located at other place must be erased once, and
place necessary coils in correct place.

Meaning:
Some condition input of functional instruction is not
connected correctly.
Solution:
BAD CONDITION Check the connection of all condition inputs of the
functional instruction. Especially for functional instruc-
tion that has more than one condition input, check if
connections to condition inputs interfere with each
other.

Meaning:
FUNCTION AF- Functional instruction is used in output section of net:
TER DI- refer to next section for detail.
VERGENCE IS Solution:
FORBIDDEN Functional instruction can not be used in output sec-
tion of net. If necessary, divide the net into plural nets.

Meaning:
Net is too complicated to analyze.
NET IS TOO COM- Solution:
PLICATED Examine every connection, and find unnecessarily
bending connection, or coils that are connected to
different point.

Meaning:
There is signal connected to nowhere.
NO CONNECTION Solution:
Find gap that is expected to be connected, and cor-
rect the connection.

732
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

Error message Meaning and solution

Meaning:
No signal is provided for logical operation.
NO INPUT FOR Solution:
OPERATION Coil without input, or coil connected to output of func-
tional instruction that has no output, causes this error.
If coil is not necessary, remove it. If necessary,
connect it to meaningful input.

Meaning:
No logical operation with functional instruction output
OPERATION AF- is permitted, except write coils.
TER FUNCTION Solution:
IS FORBIDDEN Output of functional instruction can not be connected
to a contact, nor to conjunction with other signal that
will be implemented by logicalor operation.

Meaning:
Relay with blank address, or blank parameter of func-
PARAMETER IS tional instruction, is found.
NOT SUPPLIED Solution:
Enter all of the relay addresses, and parameters of
functional instructions.

Meaning:
Some contacts are connected with short circuit.
SHORT CIRCUIT Solution:
Find contact with terminals connected by short circuit,
and correct connections.

Meaning:
TOO MANY Too many functional instructions are in one net.
FUNCTIONS IN Solution:
NET Only one functional instruction is allowed to constitute
a net. If necessary, divide the net into plural nets.

Meaning:
WRITE COIL EX- Write coil is expected, but not found.
PECTED Solution:
Add proper write coil to the net.

733
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.3.6 Valid net for PMCNB6 must have following structure:


Structure of Valid Net

Input section consists of contacts and functional instruction, and the


result of operations of input section is led to Convergence point. After
the convergence point, there is Output section that consists of coils
only. The Convergence point is the nearest point to right power line,
where all connections join with each other to gather into single
connection.

Input section contains at least one relay or functional instruction,


however, output section may contain nothing.

Valid net for PMCNB6 is also restricted in following rules:


D Only one functional instruction is available for a net.
D Functional instruction can be placed only at last (rightmost) of input
section.
D Only coils can be contained in output section.

734
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.4 Program List Viewer screen shows the list of subprogram of the Ladder.
You can select one subprogram then the content of program is displayed.
PROGRAM LIST This screen also shows the detail information (program type, symbol
VIEWER SCREEN name, comment, program size, program net count, the start net number
in all of the program and protect condition) for subprogram.
To reach this screen, at LADDER Diagram Monitor screen, press [LIST]
soft key.
Following operations are available at this screen.
D Show the content of selected program. [ZOOM]
(Go to LADDER Diagram Monitor screen)
D Search for program. [SEARCH]
D Go to Program List Setting screen. [LIST SETING]

Program List Viewer screen (Detail)

You can select Detail viewer format or Brief viewer format on Program
List Viewer screen.
The default viewer format is Detail viewer format.
See Setting screen for Program List Viewer screen section for more
detail.

735
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.4.1
Screen Structures (1) Program List Viewer screen (Detail)
Program List Viewer screen (Detail) shows the detail information that
are program size, program net count and so on for program.

(a) Screen Structure


1. The title information (REMARKS) of the Ladder Program and
the total program count are displayed above the Program List.
2. In the message line, error messages or inquiry messages will be
displayed depending on the situation.
3. In the area for Program List, 14 data can be displayed at
maximum.
(b) Area of Program List
1. The icon L means program type of Ladder. It is displayed in
the L/S field for each program.

NOTE
Displaying L requires Character registration function of
CNC software, which is supported by Series F002 version
03 or later. If CNC software does not support it, Ladder
program type is always displayed L.

2. Program name is displayed in the PROG NO. field for each


program.
There are three kinds of program names.
PROGRAM : It means the whole program.
LEVELn (n=1,2,3) : It means the Ladder level 1, 2 and 3.
Pm (m=1 to 2000) : It means subprogram.
3. The symbol is displayed in the SYMBOL field for each
program.
If no symbol is set into the subprogram, the SYMBOL field
will be blank.

736
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

4. The comment is displayed in the COMMENT field for each


program.
If no comment is set into the subprogram, the COMMENT
field will be blank.
5. The program size is displayed in the SIZE (BYTE) field for
each program.
If the program size is not over 1024 byte, the unit is shown in byte.
If it is over 1024 byte, the unit is shown in kilo (1024) byte with
K.
Ex.) The case that program size is not over 1024 byte.
1023 bytes : 1023 is shown.
Ex.) The case that program size is over 1024 byte.
20000 bytes : 19.5K is shown.
6. In the NET COUNT field for each program, total number of
nets in the program and first net number of the program in the
whole Ladder program are displayed as follows.
Total number of nets in the program* / First global net number
of the program in the whole Ladder program*
* Maximum is 99,999.
7. The status of protection is displayed in the P field for each
program.
Following icons mean the status of protection.
(Lock) : Monitoring and editing program are
disabled.
(Magnifying glass) : Monitoring program is enabled.
Editing program is disabled.
(Pencil) : Monitoring and editing program are
enabled.

NOTE
The displaying icons requires Character registration
function of CNC software, which is supported by Series
F002 version 03 or later. If CNC software does not support
it, the statuses of protection are displayed as follows.
P : Monitoring and editing program are disabled.
R : Monitoring program is enabled.
Editing program is disabled.
Space : Monitoring and editing program are enabled.

(2) Program List Viewer screen (Brief)


Program List Viewer screen (Brief) shows less information than
Program List Viewer screen (Detail), to increase the number of items.
The program type, the status of protection and the name or symbol are
displayed for each program.
The detail information of program that is pointed by the cursor is
displayed on additional information line.

737
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

(a) Screen Structure


1. The title information (REMARKS) of the Ladder Program and
the total program count are displayed above the Program List.
2. In the message line, error messages or inquiry messages will be
displayed depending on the situation.
3. In additional information line near the bottom of the screen, the
following information is displayed for the program under the
cursor.
D program name
D symbol, comment
D program size
D total number of nets
D First global net number of the program in the whole Ladder
program.
4. In the Program List area, the programs 14 lines and 5 columns can
be displayed in maximum.
(b) Area of Program List
The following items are displayed in Program List area of Program
List Viewer screen.
The meanings of these items are the same as the items of Program List
Viewer screen (Detail).
D Program type.
D Status of protection
D Program name or symbol. (See Screen Setting for Program List
Viewer screen section for selecting this item.)

738
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.4.2
Operations

(a) Operation with Softkeys


1. [ZOOM] Display the contents of program
Goes to LADDER Diagram Monitor screen. If you press
[ZOOM] soft key without strings, the program under the cursor
is displayed at LADDER Diagram Monitor screen.
If you entered program name (See (c) 1. for detail) or symbol
before pressing [ZOOM] soft key, the program according to the
preceding string is searched and the program is displayed at
LADDER Diagram Monitor screen.
But, when the selected program is protected to monitor, you have
to unlock the protection.
2. [SEARCH] Search for program
Searches the program. If you entered program name (See (c) 1.
for detail) or symbol and press [SEARCH] soft key, the program
according to the preceding string is searched, the cursor points the
program.
3. [LIST SETING] Screen Settings
Goes to setting screen for Program List Viewer screen. You can
change various settings for Program List Viewer screen at the
screen. Use Return key [<] to return to Program List Viewer
screen. See Settings for Program List Viewer screen section for
the detail.
(b) Other operations
1. Cursor move keys, Page change keys
You can move cursor by all cursor move keys and Page change
keys.
And if you entered program name (See (c) 1. for detail) or symbol
and press Right cursor move key, the program according to the
preceding string is searched, the cursor points the program.
2. INPUT key
You can operate same as [ZOOM] soft key.
(c) Note of searching operations
1. When program is searched by program name, the strings that
show each program are as follows.
PROGRAM : 0(Zero) or G
LEVEL1, 2, 3 : L + Number
Ex.) L1, L01, etc
Pn : Number or P + Number
Ex.) 1, P1, P01
2. Search function by [SEARCH] soft key or Right cursor move key
tries to suppose the given word as an item to be searched in
following order.
(i) The string for PROGRAM or LEVEL : 0(Zero), G,
L + Number
The number for subprogram : Number
(ii) Symbol
(iii) The string for subprogram : P + Number

739
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.4.3
Setting Screen

(a) Setting items


Program List Viewer/Editor screen contains the setting items below:
D VIEW FORMAT
Determines whether the list data in the Program List
Viewer/Editor screen are displayed as detail format, or brief
format themselves.
DETAIL (default)
The Program List Viewer/Editor screen shows Detail
information for each program.
The items of detail information are program type, program
name, symbol, comment, program size, program net count
and status of protection.
BRIEF
The Program List Viewer/Editor screen shows less
information than DETAIL, to increase the number of items.
The program type, the status of protection and the name or
symbol are displayed for each program.
The detail information of program that is pointed by the
cursor is displayed on additional information line.
D ADDRESS NOTATION
Determines whether the programs in the Program List
Viewer/Editor screen are displayed as corresponding symbols, or
the addresses themselves.
SYMBOL (default)
Addresses that have a symbol are displayed by the symbols.
Addresses without symbols are displayed by the addresses
themselves.
ADDRESS
All addresses are displayed as the addresses themselves even
if they have a symbol.

740
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

D SORT BY
Determines whether the programs in the Program List
Viewer/Editor screen are displayed in order of program number,
or symbol name themselves. And When ADDRESS NOTAION
is SYMBOL, this determination is enabled. So if ADDRESS
NOTAION is ADDRESS, the programs are always displayed in
order of program number.
PROGRAM NUMBER (default)
The programs are displayed in order of program number.
SYMBOL
Programs that have a symbol are displayed in order of the
symbol name. Programs without symbols are displayed in
order of program number after programs with the symbols.
PROGRAM, LEVEL1, LEVEL2, and LEVEL3 are out of
target of sort.
D PROTECTED PROGRAM
Determines whether protected programs in the Program List
Viewer/Editor screen are displayed or not. On each screen, the
protected program means as follows.
On Program List Viewer screen : the program is protected to
monitor.
On Program List Editor screen : the program is protected to
edit.
SHOW (default)
The protected programs are displayed in the Program List
Viewer/Editor screen.
HIDE
The protected programs are not displayed in the Program List
Viewer/Editor screen.
D FRAME NET IN SUBPROGRAM MODE
Frame net means functional instruction END1, 2 and 3 on
LEVEL 1,2,3, and functional instruction SP and SPE on
subprogram.
It determines whether the frame net in the LADDER Diagram
Monitor/Editor screen are displayed or not, when you selected the
program and press [ZOOM] soft key in the Program List
Viewer/Editor screen.
SHOW (default)
The frame net is displayed in the LADDER Diagram
Monitor/Editor screen.
HIDE
The frame net is not displayed in the LADDER Diagram
Monitor/Editor screen.

741
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.5 At Program List Editor screen you can create new program and delete a
program in addition to the function of Program List Viewer screen.
PROGRAM LIST To reach this screen, press [LIST] soft key at LADDER Diagram Editor
EDITOR SCREEN screen.
Following operations are available at Program List Editor screen. For
more detail of these operations, refer to the descriptions of each key to
operate.
D Create new program [NEW]
D Delete a program [DELETE]

Program List Editor screen (Datail)

You can select Detail viewer format or Brief viewer format on Program
List Editor screen.
The default viewer format is Detail viewer format.
See Setting screen for Program List Viewer screen section for more
detail.

742
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.5.1
Screen Structures (1) Program List Editor screen(Detail)
Program List Editor screen (Detail) shows the detail information that
are program size, program net count and so on for program.

(a) (a) Screen Structure


It is basically same with Program List Viewer screen (Detail).
(b) (b) Area of Program List
It is basically same with Program List Viewer screen (Detail).

743
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

(2) Program List Editor screen (Brief)


Program List Viewer screen (Brief) shows less information than
Program List Viewer screen (Detail), to increase the number of items.
The program type, the status of protection and the name or symbol are
displayed for each program.
The detail information of program that is pointed by the cursor is
displayed on additional information line.

(a) Screen Structure


It is basically same with Program List Viewer screen (Brief).
(b) Area of Program List
It is basically same with Program List Viewer screen (Brief).

744
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.5.2
Operations

(a) Operation with Softkeys


1. [ZOOM] Display the contents of program
Goes to LADDER Diagram Editor screen. The operation is
basically same with Program List Viewer screen. See
Operations for Program List Viewer screen section for the
detail.
2. [SEARCH] Search for program
The operation is basically same with Program List Viewer screen.
See Operations for Program List Viewer screen section for the
detail.
3. [LIST SETING] Screen Settings
The operation is basically same with Program List Viewer screen.
See Operations for Program List Viewer screen section for the
detail.
4. [NEW] Create new program
If you entered program name (See Note of searching operations
for Program List Viewer screen section for the detail) or symbol
and press [NEW] soft key, the program will be checked its
existence. If such program is not found, new program will be
created. The created program is inserted automatically into the
program list and the cursor points it.
The following ladder nets are created automatically according to
the type of created program by this operation.
LEVEL1 : Functional instruction END1
LEVEL2 : Functional instruction END2
LEVEL3 : Functional instruction END3
Subprogram : Functional instruction SP, SPE
If the status of protection of the program is enabled to edit, this
operation is available.
5. [DELETE] Delete a program
Deletes a program. If you entered no strings and press [DELETE]
soft key, the program under the cursor is deleted. If you entered
program name (See Note of searching operations for Program
List Viewer screen section for the detail) or symbol and press
[DELETE] soft key, the program will be checked its existence,
and will be deleted if such program is found.
But, PROGRAM, LEVEL1 and LEVEL2 should always exist on
program list.
If you delete these programs, the contents of program are
abandoned. But these programs do not disappear on program list.
If the status of protection of the program is enabled to edit, this
operation is available.

745
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.5.3 Screen settings of Program List Editor screen are basically same with
Setting Screen them of Program List Viewer screen. See Screen settings for Program
List Viewer screen section for the detail.

746
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.6 On Collective Monitor screen, only the necessary ladder nets can be
displayed by specifying ladder nets.
COLLECTIVE Collective Monitor screen displayed by pressing soft key [ZOOM] after
MONITOR FUNCTION moving the cursor to COLLECT program position on Program List
Viewer screen, or Press soft key [SWITCH] on Ladder Diagram Monitor
screen.

Program List Viewer screen

Ladder Diagram Monitor screen

747
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

6.6.1
Structures of Title information(REMARKS) Collective monitor mode Number of picked up nets

Collective Monitor
Screen

Area for LADDER Diagram

Key input line Message line Additional information line

(a) Screen Structure


1. It is basically the same as LADDER Diagram Monitor screen.
2. COLLECTIVE MONITOR displayed in the area for the current
subprogram above the screen means that this screen is the
Collective Monitor screen.
(b) LADDER Diagram
1. Any ladder diagram is not displayed first. Ladder nets selected by
the operation of a coil search and picking up nets, is added.
2. 128 nets or less of ladder net can be displayed on Collective
Monitor screen. When adding more new nets, most recently added
128 nets are displayed.

748
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

6.6.2
Operations of
Soft keys of Collective Monitor screen of PMCNB6
Collective Monitor
Main soft keys of Collective Monitor screen
Screen Initialization of Collective
Program List Jump to the ladder diagram net Monitor screen

Pick up a ladder Switches to Ladder Delete a net Display data table Screen setting
diagram net Diagram Monitor screen

(a) Operations using the soft keys


1. [LIST] Calling Program List Viewer screen.
Calls Program List Viewer screen. On Program List Viewer screen,
you can switch subprograms to be displayed on Ladder Diagram
Viewer screen.
2. [PICKUP] Picking up ladder nets.
Picks up ladder nets with coil which you want to monitor, on
Collective Monitor screen. About how to pick up refer to 7.6.6.3
How to pick up a ladder diagram net.
3. [JUMP] Jump to a ladder net.
On Ladder Diagram Monitor screen, search the ladder net at a
cursor position on Collective Monitor screen and jumps to the
ladder net. This soft key appears by setting SHOW CURSOR
to YES on the setting screen.
4. [SWITCH] Switches to Ladder Diagram Monitor screen.
Switches to Ladder Diagram Monitor screen.
5. [ERASE] Quits to dislpay a ladder diagram net on the screen. (1
net)
Quits to dislpay a ladder diagram net (only 1 net) whch is picked
up on Collective Monitor screen. This soft key appears by setting
SHOW CURSOR to YES on the setting screen.
6. [ERASE ALL] Quits to dislpay a ladder diagram net on the screen.
(all nets)
Quits to dislpay ladder diagram nets (all net) whch is picked up on
Collective Monitor screen.
7. [DATA TABLE] Go to Functional Instruction Data Table Viewer
screen.
Goes to Functional Instruction Data Table Viewer screen to
examine contents of Data Table of functional instructions such as
COD (SUB 7) and CODB (SUB 27), which have Data Table in
themselves. This soft key appears only when the cursor is on a
functional instruction that has Data Table.
8. [SCREEN SETING] Screen settings.
Calling the setting screen for Collective Monitor screen. You can
chenged each settings of a ladder diagram display. Return to
Collective Monitor screen when press the return key [<].

749
6. LADDER DIAGRAM MONITOR
AND EDITOR PMCNB6 MANIPULATION B61863E/14

(b) Other Operations


1. Cursor move keys, Page change keys
Cursor move keys and Page change keys move cursor on screen.
When cursor is placed on some relay or some address parameter of
a functional instruction, the information about the address under
cursor is displayed at Additional Information Line.

6.6.3 The operation for picking up ladder nets which you want to monitor on
How to Pick Up a Collective Monitor screen is as follows.
Ladder Diagram Net (1) Specification of ladder nets on Collective Monitor screen
a) Specify the address by key input
1. Enter the address which you want to monitor. (ex. Y0.0)
2. Press [PICKUP] soft key.
3. The net with the coil, which you specified by 1, is picked up
to the top of screen.
b) Specification of address from the ladder net on the Collective
Monitor screen
1. Move the cursor to a relay on the ladder net which uses address
that you want to monitor. (ex. Y19.3)
2. Press [PICKUP] soft key.
3. The net with the coil, which uses the address that you specified
by 1, is picked up to the top of screen and the cursor moves
to the specified coil position.

Collective Monitor screen (specification of ladder net on the screen)

750
6. LADDER DIAGRAM MONITOR
B61863E/14 PMCNB6 MANIPULATION AND EDITOR

1. Move the cursor to a relay on the ladder net which uses address that
you want to monitor. (ex. R0.5)
2. Press [SEARCH MENU] soft key.
3. Switches Softleys display. And then, press [PICKUP] soft key.
4. The mark is displayed to the left of net. When you switshed to
Collective Monitor screen, the net with the coil, which uses the address
that you specified by 1, is picked up to the top of screen.

Ladder Diagram Monitor screen (picked up of ladder net on the screen)

Collective Monitor screen (specification of ladder net on the Ladder Diagram


Monitor screen)

751
7. PASSWORD PROTECTION PMCNB6 MANIPULATION B61863E/14

7 PASSWORD PROTECTION

The password function protects the LADDER Diagram Monitor screen


and the LADDER Diagram Editor screen. If the password function is
enabled, it is impossible to display or edit the ladder program. The
protection was unlocked when entering the password, which is set on
FANUC LADDERII or LADDER Editing Package.

752
B61863E/14 PMCNB6 MANIPULATION 7. PASSWORD PROTECTION

7.1
SPECIFICATIONS OF (a) Password type
PASSWORD There are two password types.
One is the Rpassword to protect against reading. Another is the
RWpassword to protect against reading and writing.
(b) Available characters for password
The string that satisfies following condition can be set as the
password.
D The string length is less than 8 characters.
D Only capital letters and numerals.
(c) Screens protected by password
The following screen is protected by the password.
D Ladder diagram monitor screen
D Ladder diagram editor screen
(d) Indicator of protection status
The status of protected program is displayed in the Program List
Viewer screen and the Program List Editor screen. See program list
screen (detail) for Program List Viewer screen section for more
detail.
(e) How to unlock password protection
Before a screen protected by the password is displayed, the password
is inquired. The password is able to be unlocked when the strings of
password are entered.

NOTE
1 Once the password has been unlocked, the system never
inquires the password except turning the power on again or
replacing the ladder program by I/O function.
2 404A/04 can not display LADDER program that is protected
by Password function. To view a protected LADDER
program, you need FANUC LADDERII, LADDER Editing
Package, or upgrade version to 404A/05 or later. 404A/05
or later will ask for password when necessary.
3 When turning the power on pressing both X key and O
key, the ladder program will be cleared regardless of
password protection.

753
7. PASSWORD PROTECTION PMCNB6 MANIPULATION B61863E/14

7.2
PASSWORD AND
SWITCHING SCREEN

7.2.1 The LADDER Diagram Monitor screen and the Ladder Diagram Editor
Using One of screen are protected by the password.
RPassword and
RWPassword

NOTE
When [PMCLAD] soft key is pressed at first time after CNC
power cycle, Program List Viewer screen is displayed. Then
use [ZOOM] soft key to select subprogram to reach the
LADDER Diagram Monitor screen. The message ENTER
PASSWORD TO READ is displayed and the password is
inquired. If you enter Rpassword or RWpassword, the
subprogram that you have selected appears on the screen.
Once you choose subprogram, pressing [PMCLAD] soft key
will directly reach the LADDER Diagram Monitor screen.

754
B61863E/14 PMCNB6 MANIPULATION 7. PASSWORD PROTECTION

7.2.2 The LADDER Diagram Monitor screen and the LADDER Diagram
Using Both of Display screen are protected by the following password.
RPassword and D The LADDER Diagram Monitor screen: Rpassword or
RWPassword RWpassword
D The LADDER Diagram Display screen: RWpassword

NOTE
1 When [PMCLAD] soft key is pressed at first time after CNC
power cycle, Program List Viewer screen is displayed. Then
use [ZOOM] soft key to select subprogram to reach the
LADDER Diagram Monitor screen. The message ENTER
PASSWORD TO READ is displayed and the password is
inquired. If you enter Rpassword or RWpassword, the
subprogram that you have selected appears on the screen.
Once you choose subprogram, pressing [PMCLAD] soft key
will directly reach the LADDER Diagram Monitor screen.
2 When [EDIT] soft key is pressed in the LADDER Diagram
Monitor screen, the message ENTER PASSWORD TO
WRITE is displayed and the password is inquired. If you
enter RWpassword, the LADDEER Diagram Editor screen
is displayed. However, if you have already entered
RWpassword in program list viewer screen, the password
is never inquired in the LADDER Diagram Monitor screen.

755
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

8 WRITING, READING, AND COMPARING SEQUENCE


PROGRAMS AND PMC PARAMETERS

756
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

8.1 When the [I/O] soft key on the PMC main menu is pressed, the following
screen appears.
I/O SCREEN

On this screen, sequence programs and PMC parameters can be written


to the specified device, read from the device, and compared. The question
selection cursor, which moves vertically from one question to another, is
displayed, as is the option selection cursor, which moves horizontally
from one option to another. The displayed soft keys differ depending on
the position of the question selection cursor.
The following types of devices can be used for input/output. The desired
device type can be selected by positioning the question selection cursor
to DEVIDE and either moving the option selection cursor to that type
or selecting the soft key corresponding the type.
MEMORY CARD Data can be output to and input from a memory
card.
FLASH ROM Data can be output to and input from frash
ROM.
FLOPPY Data can be output to and input from handy
files or floppy cassettes.
OTHERS Data can be output to and input from other
input/output devices.
When you read a file from an I/O device, one of following messages
appears and whether to operate the important thing is confirmed.
Sequence program:
THE FILE CONTAINS LADDER PROGRAM. PROCEED TO
READ IT?
C language program:
THE FILE CONTAINS C LANGUAGE PROGRAM. PROCEED
TO READ IT?
PMC parameters:
THE FILE CONTAINS PMC PARAMETER. PROCEED TO
READ IT?

757
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

Other:
UNKNOWN FILE FORMAT
When you proceed to read a sequence program or a C language program,
the ladder program stops automatically. When you proceed to read PMC
parameters, new PMC parameters will be stored even if the ladder
program is running.

WARNING
1 If a Ladder program or a C language program is input while
a Ladder program is being executed, the execution of the
Ladder program and the C language program stop
automatically. You have to pay special attention to stop
Ladder program. Stopping Ladder program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. You have to make it sure
that machine is in proper status, and nobody is near the
machine when you stop Ladder program.
2 At stopping Ladder program, it may take rather long time to
completely stop it in some cases according to the activity of
Ladder program. If Ladder takes too long time to stop, or
never stop, correct Ladder program, following instructions
in section II. PMC OPERATION (CRT/MDI) 7.6.2.5 How to
correct LADDER program that never stops.
3 If the PMC parameters are input while a Ladder program is
being executed, You have to special attention to input it.
Because changed PMC parameters, may cause
unexpected effect to Ladder. You have to make it sure that
PMC parameters are not effect to Ladder when you input
PMC parameters.

758
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

In STATUS in the lower part of the screen, a detailed explanation of


execution and the execution status are displayed. During write, read, and
comparison, the size of the data already transferred is indicated as the
execution (intermediate) result.
The following gives a display example shown when PMC parameters are
written to a memory card:

NOTE
1 The [I/O] soft key is displayed by setting bit 1 of keep relay
K900 to 1.
2 For an explanation of error messages on I/O screen, see
section 12.1.9, I/O screen Error Messages.

759
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

8.2
OUTPUTTING TO
AND INPUTTING
FROM MEMORY
CARDS

When MEMORY CARD is selected for DEVICE, output to and input


from memory cards are enabled.
D FUNCTION
A data I/O command appears. Select FUNCTION with the item select
cursor, then select an item by moving the content select soft key
horizontally or pressing an appropriate soft key.
Soft keys displayed when the question selection cursor is positioned to
FUNCTION

Explanation of options
WRITE: Outputs data from the PMC to a memory card.
(Programs in C cannot be output.)
READ: Inputs data from a memory card to the PMC.
COMPARE: Compares the sequence programs on the PMC with those
on a memory card.
(Programs in C cannot be compared.)
DELETE: Deletes files from a memory card.
(Files on a flash card cannot be deleted.)
FORMAT: Formats a memory card.

CAUTION
When FORMAT is selected and executed, all data in the
memory card is lost. Be careful when executing this
function.

760
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

When you read a file from a memory card, one of following messages
appears and whether to operate the important thing is confirmed.
Sequence program:
THE FILE CONTAINS LADDER PROGRAM. PROCEED TO
READ IT?
C language program:
THE FILE CONTAINS C LANGUAGE PROGRAM. PROCEED
TO READ IT?
PMC parameters:
THE FILE CONTAINS PMC PARAMETER. PROCEED TO
READ IT?
Other:
UNKNOWN FILE FORMAT
When you proceed to read a sequence program or a C language program,
the ladder program stops automatically. When you proceed to read PMC
parameters, new PMC parameters will be stored even if the ladder
program is running.

WARNING
1 If a Ladder program or a C language program is input while
a Ladder program is being executed, the execution of the
Ladder program and the C language program stop
automatically. You have to pay special attention to stop
Ladder program. Stopping Ladder program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. You have to make it sure
that machine is in proper status, and nobody is near the
machine when you stop Ladder program.
2 At stopping Ladder program, it may take rather long time to
completely stop it in some cases according to the activity of
Ladder program. If Ladder takes too long time to stop, or
never stop, correct Ladder program, following instructions
in section II. PMC OPERATION (CRT/MDI) 7.6.2.5 How to
correct LADDER program that never stops.
3 If the PMC parameters are input while a Ladder program is
being executed, You have to special attention to input it.
Because changed PMC parameters, may cause
unexpected effect to Ladder. You have to make it sure that
PMC parameters are not effect to Ladder when you input
PMC parameters.
4 Set bit 1 of keep relay K900 to 0 when the machine tool is
shipped.

761
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

D KIND OF DATA
KIND OF DATA is displayed only when WRITE is selected for
FUNCTION.
Set the type of data to be output by moving the cursor horizontally to
that type or by clicking the corresponding soft key.
Soft keys displayed when the question selection cursor is positioned to
KIND OF DATA

Explanation of options
LADDER: Outputs sequence programs only.
PARAMETER: Outputs PMC parameters.
D FILE NO.
FILE NO. is displayed only when READ, COMPARE, or
DELETE is selected for FUNCTION.
Enter the file number in the edit box.
D FILE NAME
FILE NAME is displayed when WRITE, READ, COMPARE,
or DELETE is selected for FUNCTION.
Enter the file name in the edit box.
When READ, COMPARE, or DELETE is selected for
FUNCTION, the file name corresponding to the file number entered
in FILE NO. is displayed automatically.
The file name must be in MSDOS format: a file name of up to eight
characters followed by an extension of up to three characters.
When WRITE is selected for FUNCTION and the file name is not
entered, the following names are automatically assumed.
DATA KIND File name

LADDER PMCBN6.LAD

PARAM PMCNB6.PRM

CAUTION
When both FILE NO. and FILE NAME are displayed at
the same time, and a value is entered for FILE NO. and
another file name is entered in FILE NAME, the value
entered in FILE NO. is erased and the file name entered
in FILE NAME becomes effective.

762
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

Explanation of soft keys


[EXEC]: Executes the function selected for FUNCTION.
During execution, the soft key disappears and the
[CANCEL] soft key appears to the right of the key.
[CANCEL]: Cancels the execution of the function. When the function
terminates normally, the soft key disappears.
[LIST]: Replaces the current display with the memory card list
screen. See Section 12.1.3, Memory Card List Screen
for details.
The PMCNB6 supports the following memory cards:
: Supported
: Not supported
Flash Memory Card
SRAM Card Supported Unsupported ATA Card
Card Card
Read of a file
Format of a card
Write of a file
Delete of a file
List of a file

NOTE
For an explanation of supported flash memory cards, see
(1) Writing to flash memory cards in Section III.7.3.4.

763
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

8.3 When MEMORY CARD is selected in DEVICE, pressing the [LIST] soft
key displays the following screen:
MEMORY CARD LIST
SCREEN

If a memory card holding files is in the slot, the contents of the memory
card are displayed as shown in the above.

NOTE
Up to 128 files can be displayed on this screen. When 129
or more files are saved in the memory card, the 129th and
subsequent files are ignored.

When a file is selected on this screen, the screen display can be returned
to the previous screen. To select a file, place the cursor at the name of the
file, then press either the [SELECT] soft key or the INPUT key. After the
key entry, the screen display switches to the previous screen
automatically. In this case, the cursor is positioned at READ on the
FUNCTION menu, and the number and name of the file selected on the
list screen are indicated in the FILE NO. and FILE NAME fields,
respectively. A display example is shown below.

764
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

To return the screen display to the previous screen without selecting a file,
press the return key.
When the memory card is replaced with another card while the list screen
is being displayed, the displayed information is not updated
automatically. In this case, press the [REFRESH] soft key. The contents
of the new memory card are then displayed.
Explanation of soft keys
[SELECT]: Selects a file, and returns the screen display to the
previous screen.
[REFRESH]: Redisplays the contents of the memory card.

765
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

8.4
OUTPUTTING TO
AND INPUTTING
FROM FLASH ROM

When FLASH ROM is selected for DEVICE, output to and input from
flash ROM are enabled.

NOTE
The above screen is displayed when the C language board
is installed. When the C language board is not installed,
only LADDER is indicated on the menu of the KIND OF
DATA.

D FUNCTION
The available data input/output commands are displayed. Select the
desired command by moving the cursor horizontally to that command
or select it with the corresponding soft key.
Soft keys displayed when the cursor is positioned to FUNCTION

Explanation of options
WRITE: Outputs sequence programs from the PMC to flash
ROM.
READ: Inputs sequence programs from flash ROM to the PMC.
COMPARE: Compares the sequence programs on the PMC with those
on flash ROM.
When you read a file from a flash ROM, one of following messages
appears and whether to operate the important thing is confirmed.
Sequence program:
THE FILE CONTAINS LADDER PROGRAM. PROCEED TO
READ IT?

766
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

C language program:
THE FILE CONTAINS C LANGUAGE PROGRAM. PROCEED
TO READ IT?
PMC parameters:
THE FILE CONTAINS PMC PARAMETER. PROCEED TO
READ IT?
Other:
UNKNOWN FILE FORMAT
When you proceed to read a sequence program or a C language program,
the ladder program stops automatically. When you proceed to read PMC
parameters, new PMC parameters will be stored even if the ladder
program is running.

WARNING
1 If a Ladder program or a C language program is input while
a Ladder program is being executed, the execution of the
Ladder program and the C language program stop
automatically. You have to pay special attention to stop
Ladder program. Stopping Ladder program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. You have to make it sure
that machine is in proper status, and nobody is near the
machine when you stop Ladder program.
2 At stopping Ladder program, it may take rather long time to
completely stop it in some cases according to the activity of
Ladder program. If Ladder takes too long time to stop, or
never stop, correct Ladder program, following instructions
in section II. PMC OPERATION (CRT/MDI) 7.6.2.5 How to
correct LADDER program that never stops.
3 Set bit 1 of keep relay K900 to 0 when the machine tool is
shipped.

D KIND OF DATA
Displayed only when WRITE is selected in FUNCTION. Set the type
of the data you want to output by moving the cursor horizontally or by
using a soft key. C LANGUAGE appears only when the C language
board is installed.
Soft keys displayed when the item select cursor is placed at KIND OF
DATA

Explanation
LADDER: Outputs sequence programs only.
C LANGUAGE: Outputs programs in C.
Explanation of soft keys
[EXEC]: Executes the function selected for FUNCTION.
During execution, the soft key disappears and the
[CANCEL] soft key appears to the right of the key.

767
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

NOTE
When a program is written, it may take much time to initialize
the flash ROM. During initialization, INITIALIZING FLASH
ROM appears in the STATUS field in the lower part of the
screen.

768
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

8.5
OUTPUTTING TO
AND INPUTTING
FROM FLOPPY

When FLOPPY is selected for DEVICE, output to and input from


floppy cassette or handy file that is connected via RS232C are enabled.
D FUNCTION
The available data input/output commands are displayed. Select the
desired command by moving the cursor horizontally to that command
or select it with the corresponding soft key.
Soft keys displayed when the question selection cursor is
positioned to FUNCTION

Explanation of options
WRITE Outputs data from the PMC to a floppy disk or handy
file.
READ Inputs data from a floppy disk or handy file to the
PMC.
COMPARE Compares the sequence program on the PMC with
those on a floppy disk or handy file.
DELETE Delete a file from a floppy disk or handy file.
DELETE ALL Deletes all files from a floppy disk or handy file.

CAUTION
DELETE ALL command is not use for following floppy
cassette.
FLOPPY CASSETTE ADAPTER A13B0131B001

When you read a file from a floppy cassete or a handy file, one of
following messages appears and whether to operate the important thing
is confirmed.

769
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

Sequence program:
THE FILE CONTAINS LADDER PROGRAM. PROCEED TO
READ IT?
C language program:
THE FILE CONTAINS C LANGUAGE PROGRAM. PROCEED
TO READ IT?
PMC parameters:
THE FILE CONTAINS PMC PARAMETER. PROCEED TO
READ IT?
Other:
UNKNOWN FILE FORMAT
When you proceed to read a sequence program or a C language program,
the ladder program stops automatically. When you proceed to read PMC
parameters, new PMC parameters will be stored even if the ladder
program is running.

WARNING
1 If a Ladder program or a C language program is input while
a Ladder program is being executed, the execution of the
Ladder program and the C language program stop
automatically. You have to pay special attention to stop
Ladder program. Stopping Ladder program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. You have to make it sure
that machine is in proper status, and nobody is near the
machine when you stop Ladder program.
2 At stopping Ladder program, it may take rather long time to
completely stop it in some cases according to the activity of
Ladder program. If Ladder takes too long time to stop, or
never stop, correct Ladder program, following instructions
in section II. PMC OPERATION (CRT/MDI) 7.6.2.5 How to
correct LADDER program that never stops.
3 If the PMC parameters are input while a Ladder program is
being executed, You have to special attention to input it.
Because changed PMC parameters, may cause
unexpected effect to Ladder. You have to make it sure that
PMC parameters are not effect to Ladder when you input
PMC parameters.
4 Set bit 1 of keep relay K900 to 0 when the machine tool is
shipped.

770
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

D KIND OF DATA
KIND OF DATA is displayed only when WRITE is selected for
FUNCTION.
Set the type of data to be output by moving the cursor horizontally to
that command or select it with the corresponding soft key.
Soft keys displayed when the question selection cursor is
positioned to KIND OF DATA

Explanation of options
LADDER Outputs sequence program.
PARAMETER Outputs PMC parameters.
D FILE NO.
FILE NO. is displayed only when READ, COMPARE, or
DELETE is selected for FUNCTION.
Enter the file number in the edit box.
D FILE NANE
FILE NAME is displayed when WRITE, READ,
COMPARE, or DELETE is selected for FUNCTION.
Enter the file name in the edit box.
When READ, COMPARE, or DELETE is selected for
FUNCTION, the file name corresponding to the file number entered
in FILE NO. is displayed automatically.
When you output to or input from floppy disk formatted in DOS
format, the file name must be in MSDOS format: a file name of up
to eight characters followed by an extension of up to three characters.
When you output to or input from floppy disk formatted in FANUC
format, a file name of up to 17 characters will be input.
When WRITE is selected for FUNCTION and the file name is not
entered, the following names are automatically assumed.
DATA KIND File name

LADDER PMCNB6.LAD

PARAM PMCNB6.PRM

CAUTION
1 When both FILE NO. and FILE NAME are displayed at
the same time, and a value is entered for FILE NO. and
another file name is entered in FILE NAME, the value
entered in FILE NO. is erased and the file name entered
in FILE NAME becomes effective.
2 Specifying the same name as that of an existing file results
in an error.

771
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

Explanation of soft keys


[EXEC] Executes the function selected for FUNCTION.
During execution, the soft key disappears and the
[CANCEL] soft key appears to the right of the key.
[CANCEL] Cancels the execution of the function. When the
function terminates normally, the soft key
disappears.
[LIST] Replaces the current display with the Floppy list
screen. See Section 12.1.6, Floppy List Screen
for details.
[PORT SETING] Replaces the current display with the screen for
setting communication parameters. See Section
12.1.8, Port Setting Screen for details.

772
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

8.6 When FLOPPY is selected for DEVICE, pressing the [LIST] soft key
display the following screen.
FLOPPY LIST
SCREEN

The contents of the floppy cassettes or the handy files are displayed. When
a file is selected on this screen, the screen display can be returned to the
previous screen. To select the file, place the cursor at the name of the file,
then press either the [SELECT] soft key or the INPUT key. After the key
entry, the screen display switches to the previous screen automatically. In
this case, the cursor is positioned at READ on the FUNCTION menu,
and the number and name of the file selected on the list screen are
indicated in the FILE NO. and FILE NAME fields, respectively.
To return the screen display to the previous screen without selecting a file,
press the return key.
When the floppy cassette or the handy file is replaced with another one
while the list screen is being displayed, the displayed information is not
updated automatically. In this case, press the [REFRESH] soft key. The
contents are then displayed.

NOTE
Up to 128 files can be displayed on this screen. When 129
or more files are saved, the 129th and subsequent files are
ignored.

Explanation of soft keys


[SELECT] Selects a file, and returns the screen display to the
previous screen.
[REFRESH]Redisplays the contents of floppy cassette or handy file.

773
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

8.7
OUTPUTTING TO
AND INPUTTING
FROM OTHER
INPUT/OUTPUT
DEVICES

When OTHERS is selected for DEVICE, output to and input from


other input/output devices are enabled.
D FUNCTION
The available data input/output commands are displayed. Select the
desired command by moving the cursor horizontally to that command
or select it with the corresponding soft key.
Soft keys displayed when the question selection cursor is
positioned to FUNCTION

Explanation of options
WRITE Outputs data from the PMC to other input/output device.
READ Inputs data from other input/output device to the PMC.
COMPARE Compares the sequence program on the PMC with those
on other input/output device.
When you read a file from a I/O device, one of following messages
appears and whether to operate the important thing is confirmed.
Sequence program:
THE FILE CONTAINS LADDER PROGRAM. PROCEED TO
READ IT?
C language program:
THE FILE CONTAINS C LANGUAGE PROGRAM. PROCEED
TO READ IT?
PMC parameters:
THE FILE CONTAINS PMC PARAMETER. PROCEED TO
READ IT?
Other:
UNKNOWN FILE FORMAT

774
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

When you proceed to read a sequence program or a C language program,


the ladder program stops automatically. When you proceed to read PMC
parameters, new PMC parameters will be stored even if the ladder
program is running.

WARNING
1 If a Ladder program or a C language program is input while
a Ladder program is being executed, the execution of the
Ladder program and the C language program stop
automatically. You have to pay special attention to stop
Ladder program. Stopping Ladder program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. You have to make it sure
that machine is in proper status, and nobody is near the
machine when you stop Ladder program.
2 At stopping Ladder program, it may take rather long time to
completely stop it in some cases according to the activity of
Ladder program. If Ladder takes too long time to stop, or
never stop, correct Ladder program, following instructions
in section II. PMC OPERATION (CRT/MDI) 7.6.2.5 How to
correct LADDER program that never stops.
3 If the PMC parameters are input while a Ladder program is
being executed, You have to special attention to input it.
Because changed PMC parameters, may cause
unexpected effect to Ladder. You have to make it sure that
PMC parameters are not effect to Ladder when you input
PMC parameters.
4 Set bit 1 of keep relay K900 to 0 when the machine tool is
shipped.

775
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

D KIND OF DATA
KIND OF DATA is displayed only when WRITE is selected for
FUNCTION.
Set the type of data to be output by moving the cursor horizontally to
that command or select it with the corresponding soft key.
Soft keys displayed when the question selection cursor is
positioned to KIND OF DATA

Explanation of options
LADDER Outputs sequence program.
PARAMETER Outputs PMC parameters.
Explanation of soft keys
[EXEC] Executes the function selected for FUNCTION.
During execution, the soft key disappears and the
[CANCEL] soft key appears to the right of the key.
[CANCEL] Cancels the execution of the function. When the
function terminates normally, the soft key
disappears.
[PORT SETING] Replaces the current display with the screen for
setting communication parameters. See Section
12.1.8, Port Setting Screen for details.

776
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

8.8 When FLOPPY or OTHERS is selected for DEVICE, the [PORT


SETING] soft key is displayed. When the key is pressed, the following
PORT SETTING screen appears. The following gives a display example shown when
SCREEN OTHERS is selected for DEVICE.

This screen allows the setting of the communication data required for
communication using the RS232C. Communication data can be set for
each of the two types of devices independently of the other.
Selected device type is displayed to DEVICE menu on screen.
Explanation of each question
D CHANNEL
Check that an RS232C cable is connected to the main board of the
control unit. Directly enter the number corresponding to the connected
connector.
1 .......... JD5A
2 .......... JD5B
D BAUDRATE
1200: Sets the baud rate to 1200.
2400: Sets the baud rate to 2400.
4800: Sets the baud rate to 4800.
9600: Sets the baud rate to 9600.
19200: Sets the baud rate to 19200.
D STOP BIT
1 BIT: Sets the number of stop bits to 1.
2 BIT: Sets the number of stop bits to 2.
D WRITE CODE
WRITE CODE is displayed when OTHERS is selected for
DEVICE.
ASCII: Sets the output code to ASCII.
ISO: Sets the output code to ISO.

777
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

NOTE
Parity is always NONE.

Explanation of soft keys


[INIT] Sets all the parameters to their initial values.
Initial values

DEVICE = FLOPPY DEVICE = OTHERS

CHANNEL 1 1

BAUD RATE 4800 4800

STOP BIT 2 BITS 2 BITS

WRITE CODE (None) ISO

778
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

8.9 The error messages that may appear on the I/O screen and their meanings
and actions are listed below.
I/O SCREEN ERROR
MESSAGES D Error messages displayed during memory card I/O operation
(PMCNB6) Displayed error
Meaning and action
message

MEMORYCARD IS NOT No memory card is installed.


READY Action: Check whether a memory card is installed.

MEMORYCARD IS There is no available space in the memory card.


FULL Action: Delete files to create available space.

The memory card is writeprotected.


MEMORYCARD IS
WRITE PROTECTED Action: Release the write protection of the
memory card.

MEMORYCARD IS NOT The memory card cannot be recognized.


FORMATTED Action: Format the memory card.

There are too many files.


TOO MANY FILES IN
MEMORYCARD Action: Delete unnecessary files to reduce the
number of files.

The specified file cannot be found.


FILE NOT FOUND Action: On the list screen, check the file name or
file number.

Write to the specified file is not permitted.


FILE IS READONLY
Action: Check the attributes of the file.

The file name is illegal.


FILE NAME IS INVALID
Action: Specify the file name in MSDOS form.

The memory card cannot be formatted.


CAN NOT FORMAT Action: The NC cannot format this memory card.
MEMORYCARD Use another unit such as a personal com-
puter to format the memory card.

This memory card is not supported.


UNSUPPORTED
MEMORYCARD Action: Replace the memory card with another
one.

An error occurred when a file was deleted from the


CAN NOT DELETE FILE memory card.
Action: Check the attributes of the file.

The battery of the memory card has become


MEMORYCARD weak.
BATTERY ALARM
Action: Replace the battery of the memory card.

THIS FILE NAME IS The file name is already used.


ALREADY USED Action: Change the file name to another one.

The memory card cannot be accessed.


MEMORYCARD
ACCESS ERROR Action: Replace the memory card with another
one.

DIFFERENCE FOUND File comparison detected a mismatch.

779
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

Displayed error
Meaning and action
message

MEMORYCARD IS Another PMC user is using the memory card.


LOCKED BY OTHER Action: Wait until the PMC user completes proces-
FUNCTION sing, then retry.

An attempt was made to read a file, but its ROM


MEMORY CARD data ID was illegal.
HEADER ROM DATA ID
IS ILLEGAL Action: This file cannot be read. Check the type
of the file.

An attempt was made to read a file, but its ROM


FLASH ROM HEADER data ID was illegal.
ROM DATA ID IS
ILLEGAL Action: This file cannot be read. Check the type
of the file.

COMPARE OF C The compare function for programs in C is not


LANGUAGE PROGRAM supported.
IS NOT SUPPORTED

The file number cannot be selected.


FILE NUMBER CAN Action: If the file does not exist, the key entry is
NOT SELECTED invalid. If this error occurs even when the
cursor is placed at a file name, contact the
FANUC service center.

The entered file number is not present. The en-


THE FILE NUMBER tered number exceeds the total number of files.
DOES NOT EXIST Action: Check the total number of files on the list
screen.

A value up to 128 can be entered as the file num-


FILE NUMBER IS ber.
RESTRICTED TO 128
Action: Enter a numeric value not exceeding 128.

An error due to an internal factor occurred. Details


INTERNAL ERROR on the error are displayed in parentheses.
(xxxxxxxxxx) Action: Contact the FANUC service center, and
report the displayed message correctly.

D Error messages displayed during flash ROM I/O operation

Displayed error
Meaning and action
message

The system is not in the emergency stop state.


NOT IN EMG STOP
MODE Action: Place the system in the emergency stop
state.

INVALID LADDER The transfer program is illegal.


PROGRAM Action: Check the program.
INVALID C LANGUAGE
PROGRAM

DIFFERENCE FOUND A file comparison detected a mismatch.

FLASH ROM IS Another PMC user is using the flash ROM.


LOCKED BY OTHER Action: Wait until the PMC user completes proces-
FUNCTION. sing, then retry.

780
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
B61863E/14 PMCNB6 MANIPULATION PMC PARAMETERS

Displayed error
Meaning and action
message

The C language board cannot be recognized.


C LANGUAGE BOARD
IS NOT IMPLEMENTED Action: Check whether the C language board is
installed.

An error due to an internal factor occurred. Details


INTERNAL ERROR on the error are displayed in parentheses.
(xxxxxxxxxx) Action: Contact the FANUC service center, and
report the displayed message correctly.

D Error messages displayed during floppy cassettes, handy files or other


input/output devices I/O operation.

Displayed error
Meaning and action
message

Specified file is not PMC parameter format.


BAD PMC PARAMETER
FORMAT Action: Specify file of PMC parameter format, or
check the contents of the file.

Specified file is not handy file format.


BAD HANDY FILE
FORMAT Action: Specify file of handy file format, or check
the contents of the file.

Can not recognize the format of specified file.


UNKNOWN FILE Action: Specify file of recognizable format such
FORMAT as PMC parameter format, or check the
contents of the file.

Need file name or file number to identify file to


FILE NAME OR FILE read, compare, or delete.
NUMBER IS REQUIRED Action: Specify file name or file number for the
operation.

Communication with the I/O device has been time-


out.
COMMUNICATION
TIMEOUT Action: Check the communication parameters
such as baud rate, and retry to communi-
cate.

Any I/O device is not connected, or some error has


occurred in it.
I/O DEVICE IS NOT Action: Check the power of I/O device is ON.
ATTACHED OR IN Check the I/O device is connected.
ERROR STATUS Check the cable that connects I/O de-
vice with PMC is correct one.
If some error has occurred in I/O de-
vice, solve it.

RECEIVED BAD DATA: Invalid data has been received.


CHECK THE Action: Check the PMCs communication param-
COMMUNICATION eters such as baud rate match the ones of
PARAMETERS I/O device.

Too many data have received at once.


RECEIVED DATA HAS
OVERRUN Action: Check the communication parameters
about flow control.

781
8. WRITING, READING, AND COMPARING
SEQUENCE PROGRAMS AND
PMC PARAMETERS PMCNB6 MANIPULATION B61863E/14

Displayed error
Meaning and action
message

Others function is using this channel.


OTHERS FUNCTION IS
USING THIS CHANNEL Action: Use the other channel, or stop the func-
tion.

Setting parameters of communication are not cor-


BAD COMMUNICATION rect.
PARAMETER Action: Check the communication parameters
such as baud rate.

Others function such us FANUC LADDERII is


OTHER FUNCTION IS using I/O function.
USING I/O Action: Wait until function that using I/O function
do finish, or stop the function.

Can not input/output of sequence program, be-


cause Online function is using sequence pro-
SEQUENCE PROGRAM gram.
IS IN USE BY ONLINE Action: Wait until Online function, do finish the
FUNCTION using I/O function. In general, both of I/O
function and Online function should not
be used at the same time.

782
9. STARTING AND STOPPING
B61863E/14 PMCNB6 MANIPULATION SEQUENCE PROGRAMS

9 STARTING AND STOPPING SEQUENCE PROGRAMS

(1) Starting a sequence program (RUN)


When a program is stopped, clicking the [RUN] soft key causes the
program to start and the status line display to change to PMC RUN.
The sequence program starts from the beginning. The soft key
changes to [STOP].
(2) Stopping a sequence program (STOP)
When a program is executed, clicking the [STOP] soft key causes the
program to stop and the status line display to change to PMC STOP.
The soft key changes to [RUN].

WARNING
If the sequence program is stopped while the machine is
operating, the machine may behave in an unexpected way.
Before stopping the sequence program, ensure that there
are no people near the machine and that the tool cannot
collide with the workpiece or machine.
Otherwise, there is an extreme risk of death or serious
injury, as well as the likelihood of the tool, workpiece, and
machine being damaged.

(3) Automatic operation of a sequence program


When AUTOMATIC LADDER START is set to AUTO (bit 2 of the
keep relay K900 = 0) on the setting screen, a sequence program can be
executed automatically when the power is turned on.

783
V. FS16i/18i/21iB
PMCSA1/SB7
MANIPULATION
1. SCREEN OPERATION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FOR PMCSA1/SB7

1 SCREEN OPERATION FOR PMCSA1/SB7

787
1. SCREEN OPERATION
FOR PMCSA1/SB7 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

1.1 The following points are changed for improvement of operation and
feature for PMCSA1.
SCREEN OPERATION
D Edit functions which is embedded in PMC control software
FOR PMCSA1
D Reinforcement of programmer protection function

1.1.1 When pressing softkey [PMC] in CNC system menu screen, PMC main
Structure of Software menu appears. The following is the summary of PMC screen tree. The
shaded part is the improved screen for PMCSA1.
Key in PMC

[PMC] [PMCLAD] LADDER DIAGRAM MONITOR


[PMCDGN] [TITLE] TITLE DATA
[STATUS] SIGNAL STATUS
[ALARM] ALARM
[TRACE] SIGNAL TRACE
[IOCHK] I/O LINK CONNECTING CHECK
[PMCPRM] [TIMER] TIMER
[COUNTR] COUNTER
[KEEPRL] KEEP RELAY
[DATA] [G.DATA] DATA TABLE
[SETING] SETTING
[RUN]/[STOP] START AND STOP OF SEQUENCE PROGRAM
[EDIT] [TITLE] TITLE DATA EDITOR
[LADDER] LADDER DIAGRAM EDITOR
[SYMBOL] SYMBOL DATA EDITOR
[MESAGE] MESSAGE DATA EDITOR
[MODULE] I/O UNIT ADDRESS SETTING
[CROSS] CROSS REFERENCE
[CLEAR] CLEARING SEQUENCE PROGRAM
[I/O] INPUT AND OUTPUT OF SEQUENCE
PROGRAM AND PMC PARAMETER
[SYSPRM] SYSTEM PARAMETER
[MONIT] [ONLINE] ONLINE SETTING

1.1.2 The following system keep relays are added.


Addition of System Item Meaning PMCSA1
Keep Relays EDIT ENABLE Allows editing the ladder program. K18.6
ALLOW PMC STOP Allows start /stop of ladder program. K19.2
Please refer to 5. SETTING FUNCTION for detail.

788
1. SCREEN OPERATION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FOR PMCSA1/SB7

1.2 The following points are changed for improvement of operation and
feature for PMCSB7.
SCREEN OPERATION
D Edit functions which is embedded in PMC control software
FOR PMCSB7
D Display in Japanese
D Ladder monitor/editing screen
D Integration of Signal waveforms(ANALYS) and trace(TRACE)
D Extension of symbol data to 16 characters
D Reinforcement of programmer protection function

1.2.1 When pressing softkey [PMC] in CNC system menu screen, PMC main
Structure of Software menu appears. The following is the summary of PMC screen tree. The
shaded parts are the improved screens for PMCSB7.
Key in PMC

[PMC] [PMCLAD] [EDIT] LADDER DIAGRAM MONITOR


Refer to chapter 6
COLLECTIVE MONITOR FUNCTION
Refer to chapter 7
LADDER DIAGRAM EDITOR
Refer to chapter 8
[PMCDGN] [TITLE] TITLE DATA
[STATUS] SIGNAL STATUS
[ALARM] ALARM
[TRACE] SIGNAL TRACE Refer to chapter 9
[IOCHK] I/O LINK CONNECTING CHECK
[PMCPRM] [TIMER] TIMER
[COUNTR] COUNTER
[KEEPRL] KEEP RELAY
[DATA] [G.DATA] DATA TABLE
[SETING] SETTING SCREEN Refer to chapter 5
[RUN]/[STOP] START AND STOP OF SEQUENCE PROGRAM
[EDIT] [TITLE] TITLE DATA EDITOR
[LADDER] LADDER DIAGRAM EDITOR
[SYMBOL] SYMBOL DATA EDITOR
[MESAGE] MESSAGE DATA EDITOR
[MODULE] I/O UNIT ADDRESS SETTING
[CROSS] CROSS REFERENCE
[CLEAR] CLEARING SEQUENCE PROGRAM
[I/O] INPUT AND OUTPUT OF SEQUENCE
PROGRAM AND PMC PARAMETER
[SYSPRM] SYSTEM PARAMETER
[MONIT] [ONLINE] ONLINE SETTING

789
1. SCREEN OPERATION
FOR PMCSA1/SB7 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

1.2.2 In symbol/comment display/editing screen, you can edit maximum 16


Expansion of Symbol characters of symbols. Other screens which shows the symbols can
display and handle the symbols up to following character length.
Size
Max. display
Screens Search length Remark
character length
Symbol/comment editing 16char. 16 char.
Ladder monitor/editing 7char. 16 char. 16 characters display is available in additional in-
formation line
Program list 6 char. 16 char.
Signal status 7 char. 16 char.
Cross reference 7 char. 16 characters display is available in specifying ad-
dress (type 1) screen
Trace 7 char. 16 char. 9 characters display is available in setting screen
The symbol characters exceeding the displaying field are omitted in each
screen. Search function fully compares 16 characters in all screens which
have search function.

1.2.3 The following system keep relays are added.


Addition of System Item Meaning PMCSB7
Keep Relays EDIT ENABLE Allows editing the ladder program. K901.6
ALLOW PMC STOP Allows start /stop of ladder program. K902.2
TRACE START Starts the tracing automatically after K906.5
power turns on
Please refer to 2. SETTING FUNCTION for detail.

790
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 2. SETTING FUNCTION

2 SETTING FUNCTION

791
2. SETTING FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

2.1 There are following setting parameter screens on PMCSB7.


SWITCHING D Setting screen for general functions (See V2.2 for details.)
SCREENS FOR D Setting screen for multilanguage display function (See II4.4.1 for
details.)
SETTING
D Setting screen for selectable I/O link assignment function (See V2.4
PARAMETERS for details.)
D Setting screen for OVERRIDE mode of the forced input/output
function (See II4.4.1 for details.)
The flow of switching above setting screens is as following chart. Each
setting except multilanguage display function can be also set on System
Keep Relay screen. Setting screen of multilanguage display function,
selectable I/O link assignment function and OVERRIDE mode of the
forced input/output function and System Keep Relay screen can be
protected by programmer protection function.

PMC main menu

[PMCPRM] [KEEPRL]

[SETING]
Keep Relay
[<] (K0K99)
General function
Page Down The screen protection

The screen protection [NEXT]


[PREV] Keep Relay
(K900K919)

Multilanguage Display Function

The screen protection


[NEXT]
[PREV] [PREV]

Selectable I/O Link Assignment


Selectable I/O Link Assignment Function
Function caution screen
EFFECTIVE GROUP SELECTION
[YES]
The screen protection [NEXT]
[PREV]
[NEXT]
OVERRIDE mode of
the forced input/output function

792
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 2. SETTING FUNCTION

2.2
SETTING SCREEN
OF GENERAL
FUNCTION

Setting screen for PMCSB7


D TRACE START(PMCSB7:K906.5)
MANUAL (0): Executes the tracing with [EXEC] softkey.
AUTO (1): Starts the tracing automatically after the power turns
on.
D EDIT ENABLE(PMCSB7:K901.6, PMCSA1:K18.6)
NO (0): Prevents editing of the sequence program.
YES (1): Allows editing of the sequence program.

NOTE
This setting effects some PMC functions.
Please refer to 2.5 Programmer protection function

D WRITE TO FROM(PMCSB7:K902.0, PMCSA1:K19.0)


NO (0): Does not write to flash ROM automatically after editing of
sequence program.
YES (1): Writes to flash ROM automatically after editing of sequence
program.
D RAM WRITE ENABLE(PMCSB7:K900.4, PMCSA1:K17.4)
NO (0): Prevents forcing function.
YES (1): Allows forcing function.

NOTE
This setting effects some PMC functions.
Please refer to 2.5 Programmer protection function

793
2. SETTING FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

D DATA TBL CNTL SCREEN(PMCSB7:K900.7, PMCSA1:K17.7)


YES (0): Displays PMC parameter data table control screen.
NO (1): Does not displays PMC parameter data table control screen.
D HIDE PMC PROGRAM(PMCSB7:K900.0, PMCSA1:K17.0)
NO (0): Allows sequence program display.
YES (1): Prevents sequence program display.

NOTE
This setting effects some PMC functions.
Please refer to 2.5 Programmer protection function

D IO GROUP SELECTION (PMCSB7:K906.1)


HIDE (0) : The selectable I/O link assignment function screen is
not displayed.
SHOW (1) : The selectable I/O link assignment function screen is
displayed.
D LADDER START(PMCSB7:K900.2, PMCSA1:K17.2)
AUTO (0): Executes the sequence program automatically after
the power turns on.
MANUAL(1): Executes the sequence program by [RUN] softkey.
D ALLOW PMC STOP(PMCSB7:K902.2, PMCSA1:K19.2)
NO (0): Prevents run/stop operation of the sequence program.
YES (1): Allows run/stop operation of the sequence program.

NOTE
This setting effects some PMC functions.
Please refer to 2.5 Programmer protection function

D PROGRAMMER ENABLE(PMCSB7:K900.1, PMCSA1:K17.1)


NO (0): Disables embedded programmer function.
YES (1): Enables embedded programmer function.

NOTE
This setting effects some PMC functions.
Please refer to 2.5 Programmer protection function

794
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 2. SETTING FUNCTION

2.3 This caution screen is displayed for the operators attention when the
operator is going to switch to the setting parameter screen for the
CAUTION SCREEN selectable I/O link assignment function.
OF THE SETTING
PARAMETER FOR
THE SELECTABLE
I/O LINK
ASSIGNMENT
FUNCTION

The caution screen of the setting parameter for the selectable I/O link
assignment function
[YES]: This softkey switches to the setting parameter screen for the
selectable I/O link assignment function.
[PREV]: This softkey switches to the previous setting parameter screen.
[NEXT]: This softkey switches to the next setting parameter screen.

WARNING
If you modify this setting parameter without care, the I/O
assignment data may not match I/O devices and turning on
the power may result in unexpected malfunctions of
machine. So, it is required that the operator of this function
should be an expert who fully understands the sequence
program and the operation of PMC. It is also strongly
recommended to the developer of machine that this setting
screen should be protected from careless use by ordinary
operators after the machine is shipped into the field.

795
2. SETTING FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

2.4 You can set the group of optional I/O device that is connected with each
machines.
SETTING
PARAMETER
SCREEN FOR THE
SELECTABLE I/O
LINK ASSIGNMENT
FUNCTION

The setting parameter screen for the selectable I/O link assignment
function
EFFECTIVE GROUP SELECTION (channel 1: K910K911, channel2:
K912K913)
You can select effective I/O group in I/O link assignment data.
1 : I/O group is effective.
0 : I/O group is no effective.

The * mark means that the group is set as the basic part by the
parameter BASIC GROUP COUNT on the system parameter screen.
The value can not be set into this parts.

796
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 2. SETTING FUNCTION

2.5
PROGRAMMER
CAUTION
PROTECTION This section contains important information for developers
FUNCTION of application system controlled by PMC. Improperly
implemented application system may increase possibility of
defects in its safety. Careful examinations and
considerations on using and implementing with the
functions explained especially in this section are strongly
required.

PMC system provides various embedded programmer functions such as


edit, diagnosis and debugging which help the programming and
debugging of sequence program. To use these functions which may even
disable safety mechanism realized by sequence program, it is required
that the operator of these functions should be an expert who fully
understands the sequence program and the operation of PMC. It is also
strongly recommended to the developer of machine that these functions
should be protected from careless use by ordinary operators after the
machine is shipped into the field. Furthermore, if these functions partly
need to be used in the field for any purpose such as the maintenance or
adjustment, the developer of the machine should implement any means
to enable these functions after forcing the machine in safe mode or should
let the operator know and strictly follow proper procedure to ensure the
safety.
The setting parameters described in this section are provided for the
developer of machine to be able to properly program the sequence or
control the parameters for necessary conditions on which the operator is
allowed to use PMC programmer functions safely by eliminating careless
operation which may cause stopping the ladder, changing sequence
program or changing important setting data.
These parameters can be set on the setting screen or in some system keep
relays (:PMCSB7: K900 to 919,PMCSA1: K17 to 19).

797
2. SETTING FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

2.5.1 If you set PROGRAMMER ENABLE to YES, it enables the


PROGRAMMER following functions as a supervisor mode.
ENABLE (PMCSB7: Ladder editing screen
Title data editing screen
K900.1, PMCSA1: Symbol/comment data editing screen
K17.1) Message data editing screen
I/O unit address setting screen
Cross reference screen
Clear of sequence program
Clear of PMC parameter
Start/stop of ladder
Forcing function
Override function*1
Setting of multilanguage message display function
I/O screen
System parameter screen
Online setting screen
Setting screen for the I/O link assignment data selection function
Setting screen for keep relay K900 or after

NOTE
The override function also requires the setting of
OVERRIDE ENABLE in the setting parameters.

CAUTION
Set this setting to NO(0) before shipment of the machine.
If this setting is left as YES(1), the operator may stop
execution of the ladder program by mistake. If you want to
protect this setting, please make a sequence that always
writes 0 in this bit by your ladder. Or please control the
machine to force to translate into safety state by sequence
program using the way described in 3.3 when the ladder
stops.

2.5.2 If you set HIDE PMC PROGRAM to YES, it disables the following
functions which have the sequence program display.
HIDE PMC PROGRAM
(PMCSB7: K900.0, Ladder monitor screen
Ladder editing screen
PMCSA1: K17.0) Title data editing screen
Symbol/comment data editing screen
Message data editing screen
I/O unit address setting screen
Cross reference screen
Clear of sequence program
Clear of PMC parameter
System parameter screen

798
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 2. SETTING FUNCTION

NOTE
Even if this parameter is set to YES, these functions do not
be hidden except for Ladder monitor/editing screen if
PROGRAMMER ENABLE is set to YES.

2.5.3 If you set EDIT ENABLE to YES, it enables the following functions
EDIT ENABLE which can edit the program.
(PMCSB7: K901.6, Ladder editing screen*1
PMCSA1: K18.6) Title data editing screen*1
Symbol/comment data editing screen*1*2
Message data editing screen*1*2
I/O unit address setting screen*1*2
Cross reference screen*1
Clear of sequence program*1*2
Clear of PMC parameter*1*2
Setting of multilanguage message display function
System parameter screen*1
Setting screen for keep relay K900 or after

NOTE
1 Even if this parameter is set to YES, these functions which
have program display are invalid if HIDE PMC PROGRAM
is set to YES.
2 These screens with stop of ladder program require below
setting ALLOW PMC STOP.

CAUTION
Set this setting to NO(0) before shipment of the machine
if you want to prohibit operator form editing the program. If
you want to protect this setting, please make a sequence
that always writes 0 in this bit by your ladder.

2.5.4 If you set ALLOW PMC STOP to YES, it enables the following
ALLOW PMC STOP functions which require stop/start of ladder program. *1
(PMCSB7: K902.2, Symbol/comment data editing screen*2
PMCSA1: K19.2) Message data editing screen*2
I/O unit address setting screen*2
Clear of sequence program*2
Clear of PMC parameter*2
Start/stop of ladder
System parameter screen*2

799
2. SETTING FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

NOTE
1 Even if this parameter is set to YES, these functions which
have program display are invalid if HIDE PMC PROGRAM
is set to YES.
2 These editing screens require above setting EDIT
ENABLE.

CAUTION
Set this setting to NO(0) before shipment of the machine.
If this setting is left as YES(1), the operator may stop
execution of the ladder program by mistake. If you want to
protect this setting, please make a sequence that always
writes 0 in this bit by your ladder. Or please control the
machine to force to translate into safety state by sequence
program using the way described in 3.3 when the ladder
stops.

2.5.5 If you set RAM WRITE ENABLE to YES, it enables both the forcing
function and the override function.
RAM WRITE ENABLE
(PMCSB7: K900.4,
PMCSA1: K17.4) NOTE
The override function also requires the setting of
OVERRIDE ENABLE in the setting parameters.

2.5.6 If you set DATA TBL CNTL SCREEN to NO, the data table control
DATA TBL CNTL screen does not be displayed.
SCREEN (PMCSB7:
K900.7, PMCSA1:
K17.7)

2.5.7 If you set IO GROUP SELECTION to SHOW, the setting screen for
the selectable I/O link assignment function is enabled.
IO GROUP SELECTION
(K906.1)

800
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 2. SETTING FUNCTION

2.6 i) If you want to prohibit completely operator from accessing the


sequence program;
EXAMPLE FOR
D PROGRAMMER ENABLE
SETTING (PMCSB7: K900.1, PMCSA1: K17.1) NO
PARAMETERS D HIDE PMC PROGRAM
(PMCSB7: K900.0, PMCSA1: K17.0) YES
D EDIT ENABLE
(PMCSB7: K901.6, PMCSA1: K18.6) NO
D ALLOW PMC STOP
(PMCSB7: K902.2, PMCSA1: K19.2) NO
ii) If you want to allow operator only monitoring the sequence program;
D PROGRAMMER ENABLE
(PMCSB7: K900.1, PMCSA1: K17.1) NO
D HIDE PMC PROGRAM
(PMCSB7: K900.0, PMCSA1: K17.0) NO
D EDIT ENABLE
(PMCSB7: K901.6, PMCSA1: K18.6) NO
D ALLOW PMC STOP
(PMCSB7:K 902.2, PMCSA1: K19.2) NO

NOTE
Please use the password function of sequence program for
particular operator. Please refer to FANUC LADDERIII
operators manual B66234EN 5.4 PROTECING LADDER
PROGRAMS BY PASSWORD

iii) If you want to allow operator monitoring and editing the sequence
program;
D PROGRAMMER ENABLE
(PMCSB7: K900.1, PMCSA1: K17.1) NO
D HIDE PMC PROGRAM
(PMCSB7: K900.0, PMCSA1: K17.0) NO
D EDIT ENABLE
(PMCSB7: K901.6, PMCSA1: K18.6) YES
D ALLOW PMC STOP
(PMCSB7: K902.2, PMCSA1: K19.2) NO

NOTE
Please use the password function of sequence program for
particular operator. Please refer to FANUC LADDERIII
operators manual B66234EN 5.4 PROTECING LADDER
PROGRAMS BY PASSWORD.

iv) If you want to allow operator monitoring and editing the sequence
program which requires stop of ladder;
D PROGRAMMER ENABLE
(PMCSB7: K900.1, PMCSA1: K17.1) NO

801
2. SETTING FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

D HIDE PMC PROGRAM


(PMCSB7: K900.0, PMCSA1: K17.0) NO
D EDIT ENABLE
(PMCSB7: K901.6, PMCSA1: K18.6) YES
D ALLOW PMC STOP
(PMCSB7: K902.2, PMCSA1: K19.2) YES

NOTE
Please use the password function of sequence program for
particular operator. Please refer to FANUC LADDERIII
operators manual B66234EN 5.4 PROTECING LADDER
PROGRAMS BY PASSWORD.

WARNING
If a sequence program is stopped while the machine is
operating, the machine may behave unexpectedly. Before
stopping the sequence program, make sure that nobody is
near the machine and that the tool cannot interfere with the
workpiece or machine. Incorrect operation of the machine
presents an extreme risk of death or serious injury to the
user. Damage the tool, workpiece, and/or the machine is
also likely.

v) The case that operator who familiar with the machine and the ladder
sequence operate all the PMC programmer functions;
D PROGRAMMER ENABLE
(PMCSB7: K900.1, PMCSA1: K17.1) YES
D HIDE PMC PROGRAM
(PMCSB7: K900.0, PMCSA1: K17.0) NO

WARNING
If a sequence program is stopped while the machine is
operating, the machine may behave unexpectedly. Before
stopping the sequence program, make sure that nobody is
near the machine and that the tool cannot interfere with the
workpiece or machine. Incorrect operation of the machine
presents an extreme risk of death or serious injury to the
user. Damage the tool, workpiece, and/or the machine is
also likely.

802
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

3 LADDER DIAGRAM MONITOR (PMCSB7)

Pressing soft key [PMCLAD] displays the sequence program


dynamically. On the screen, you can monitor the LADDER Program
works.
The LADDER Diagram Editor screen allows you changing the LADDER
Diagram, adding relays and functional instructions, and changing the
action of LADDER Diagram.
LADDER Diagram Monitor/Editor function consists of following
screens.
a) LADDER Diagram Monitor screen
Displays LADDER Diagram and the current status of relays and
others.
b) Collective Monitor screen
Displays only selected ladder diagram and the current status of relays
and others.
c) LADDER Diagram Editor screen
Edits LADDER Diagram by the net.
d) Net Editor screen
Edits the structure of a net in LADDER Diagram
e) PMC Functional Instruction Data Table Viewer screen
Refers the contents of a data table of functional instruction.
f) PMC Functional Instruction Data Table Editor screen
Edits the contents of a data table of functional instruction.
g) Program List Viewer screen
Chooses the subprogram to be displayed at LADDER Diagram
Monitor screen.
h) Program List Editor screen
Edits LADDER Diagram by the subprogram. Also chooses the
subprogram to be displayed at LADDER Diagram Editor screen.

NOTE
You can hide [PMCLAD] soft key at PMC Main Menu by
setting the keep relay of K900.0 to 1.

803
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

These screens can be reached as described bellow.

PMC Main Menu

[<] [PMCLAD]

Program List NOTE 1


Monitor
Viewer screen
Function
[LIST] [ZOOM] [LIST] [ZOOM]

[SWITCH]

Ladder Diagram Collective Monitor


Monitor screen [SWITCH] screen

[<] [EDIT]
[LIST]
Program List
Editor Ladder Diagram Editor screen
Function Editor screen
[ZOOM], [<]
[<] [CREATE], [MODIFY]

Net Editor screen

Fig. 3 Relation of screen

NOTE
1 When [PMCLAD] soft key is pressed, the screen which was displayed last time among Ladder
Diagram Monitor screen, Collective Monitor screen and Program List Viewer screen is
displayed. When [PMCLAD] soft key is pressed at first time after CNC power is on, Program
List Viewer screen is displayed. Changing the ladder program by I/O function will also make
Program List Viewer screen appears at [PMCLAD] soft key again. See Program List Viewer
screen for more detail.
2 [EDIT] soft key in Ladder Diagram Monitor screen appears only when Programmer function is
enabled. To enable Programmer function, set PROGRAMMER ENABLE to YES at
GENERAL screen of PMC Settings or set keep relay K900.1 to 1. Or, set EDIT ENABLE to
YES or set K901.6 to 1. While Online Monitor function is active, you can not reach Ladder
Diagram Editor screen. To use Ladder Diagram Editor function, you have to disable Online
Monitor function at RS232C and FBUS on PARAMETERS FOR ONLINE MONITOR:
choose NOT USE.

804
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

3.1 LADDER Diagram Monitor screen shows the on/off status of contacts
and coils, and the contents of address specified for parameter of functional
LADDER DIAGRAM instructions.
MONITOR SCREEN Press the [PMCLAD] soft key on the PMC main menu to call the ladder
diagram screen. You can use following operation at this screen, including
Forced I/O function (Forcing mode), by which you can force the relay
or the address parameters of functional instructions to a new status or
value.
D Switch subprogram to show [LIST]
D Search for address or others [SEARCH]
D Show data table of functional instructions [TABLE]
D Go to LADDER Diagram Editor screen [EDIT]
D Calling collective monitor screen [SWITCH]
D Forced I/O function (Forcing mode) number + INPUT key

805
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

3.1.1
Screen Structures Title information (REMARKS) Current subprogram Current position Range to search

Area for LADDER Diagram

Message line Key input line Additional information line

(a) Screen Structure


1 Title information (REMARKS) of the LADDER program, the
current subprogram, and the current position information of the
Diagram displayed in this screen, are displayed above the
LADDER Diagram.
When you select a subprogram to be displayed, range for search
function is indicated at right of the top line as LOCAL or
GLOBAL. In case of LOCAL, the range for search function
is restricted within the current subprogram. In case of GLOBAL,
on the other hand, search function searches whole of LADDER
program, and switch current subprogram automatically according
to the result of searching.
2 In the additional information line near the bottom of the screen, the
following information of the address under the cursor when the
cursor is shown.
D Net number of the net with the cursor
D Address and its symbol and comment information
D Current value
3 In the message line, error messages or inquiry messages will be
displayed depending on the situation.
4 In the ladder diagram display area, relays can be displayed in one
of the following patterns: 9 by 8, 9 by 9, 8 by 6, 9 by 6, 8 by 5, and
9 by 5 (numberofrelaysinrow by numberofrelaysin
column). For details, see Setting the screen.
5 A gage is displayed at the righthand side of the screen. This gage
indicates the current display position relative to the entire ladder
program.

806
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

(b) LADDER Diagram


1 Nets wider than the screen width are displayed as Continuous
Net using continuous marks (>A1>). Same continuous marks
mean they are connected with each other.

(c) Monitor
1 Contacts and coils are displayed in different colors according to the
status of the signal. The status of power flow is not displayed.
2 The contents of address parameters of functional instructions are
not shown in default setting. With the extended functional
instruction format, you can see the contents of the parameters. See
Setting Screen for the detail.
(d) Displaying Symbols and Comments
1 Above each of contacts and coils, the address is displayed. For an
address assigned a symbol, you can specify that the symbol is
displayed instead of the address. You can also specify that the
symbol is displayed in color. For details, see Setting the screen.
2 When a comment is set for the address of a contact, it is displayed
below the contact. You can specify the display format of the
comment. You can also specify that the comment is displayed in
color. For details, see Setting the screen.
3 When a comment is set for the address of a coil, it is displayed in
the right margin of the screen in the wraparound mode. You can
specify that this area is used to display a relay instead of a comment
(to increase the number of relays that can be displayed in a row).
You can also specify that the comment is displayed in color. For
details, see Setting the screen.

807
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

3.1.2
Operations
Soft keys of LADDER Diagram Monitor screen on PMCSB7
Main soft keys of LADDER
Diagram Monitor screen
Program List LADDER Diagram Editor Screen Settings

Display Data Table Collective Monitor Function

Search soft keys Search Write Coil Pick UP Search next

Search Functional Switch range


Jump to Instruction Search previous
Top/Bottom
Search Address or Net

(a) Operation with Softkeys


1 [LIST] Go to Program List Viewer screen
Goes to Program List Viewer screen to choose subprogram to be
displayed at LADDER Diagram Monitor screen.
2 [SEARCH] Search & Jump
Change soft keys to Search soft keys. Use Return key [<] to
return to the Main soft keys. Search soft keys consists of
followings:
D [TOPBTM] Jump to Top/Bottom
Jumps to the top of LADDER Program. If the top is displayed
already, then jump to the bottom.
D [SEARCH] Search Address/Net
Searches the PMC address or the net according to the preceding
string. You can specify both of bit address and byte address.
When digits are entered, the digits are supposed to be a net
number and the screen will jump to the net of the net number.
When a string other than digits is entered, the string is examined
as a symbol for some PMC address at first. If the string matches
a symbol, then the address that the symbol means will be
searched for.
If no symbol matches the string, then the string is examined as
PMC address at next. If the string indicates correct PMC
address, then the address will be searched for.
When cursor is hidden, the net that has the specified net number
or contains the specified address will be shown at the top of the
screen.
When cursor is shown, the cursor moves to the relay or the
parameter to show the found address directly.
D [WSRCH] Search Write Coil
Searches for the write coils with the address that entered string
means. Any contacts with the address are ignored.

808
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

D [FSRCH] Search Functional Instruction


Searches for the functional instructions by its SUB number or
its mnemonic name such as TMR or END2.
D [PICKUP] Taking of ladder net into collective monitor screen
The ladder net which executes the monitor is taken into the
collective monitor screen.
D [PREV] Search previous
Repeats to search the same thing backward (upward).
D [NEXT] Search next
Repeats to search the same thing forward (downward).
D [GLOBAL] / [LOCAL] Change range for searching
Changes the range for searching between GLOBAL and
LOCAL; GOBAL means whole of program, and LOCAL
means within the displaying subprogram. Current range for
searching is indicated at right of the information line at top of
screen.
3 [TABLE] Go to Functional Instruction Data Table Viewer screen
Goes to Functional Instruction Data Table Viewer screen to
examine contents of Data Table of functional instructions such as
COD (SUB 7) and CODB (SUB 27), which have Data Table in
themselves. This soft key appears only when the cursor is on a
functional instruction that has Data Table.
4 [EDIT] Go to LADDER Diagram Editor screen
Goes to LADDER Diagram Editor screen. This soft key appears
only when Programmer function1 is enabled. And activating
Online Monitor function2 disables this soft key.

NOTE
1 To enable Programmer function, go to GENERAL screen of
PMC Settings, and choose YES at item PROGRAMMER
ENABLE.
2 To deactivate Online Monitor function, go to ONLIEN screen
of PMC Settings, and choose NOT USE at settings of
RS232C and FBUS (if appears).

5 [SWITCH] Calling collective monitor screen


The screen display is switched into the Collective Monitor screen.
6 [SETING] Screen settings
Goes to setting screen for LADDER Diagram Monitor screen. You
can change various settings for LADDER Diagram Monitor screen
at the screen. Use Return key [<] to return to LADDER Diagram
Monitor screen. See Settings for LADDER Diagram Monitor
section for the detail.
(b) Other operations
1 Cursor move keys, Page change keys
With cursor hidden, you can move diagram in the screen by
up/down Cursor move keys and Page change keys.

809
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Operations of the cursor movement keys when the cursor is not displayed


PAGE
Scrolling
Upward search

PAGE
Downward search

With cursor displayed, you can move the cursor by all cursor move
keys and Page change keys. When cursor is placed on some relay
or some address parameter of a functional instruction, the
information about the address under cursor is displayed at
Additional Information Line.
2 number + INPUT key
When cursor is shown, you can force the value of the address under
cursor by entering new value as number + INPUT key. In this
screen, Forced I/O function is limited only to Forcing mode. This
Forced I/O function asks you to confirm your intention before it
takes effect. Once it is confirmed that you actually want to change
value by this function, you can change the value of the same relay
or parameter without further confirmation. However, after you
move cursor or you operate other functions, you will be asked when
you use the Forced I/O function again.

WARNING
1 You have to pay special attention to use Forced I/O function
to change status of signals. Inappropriate use of Forced I/O
function may cause unexpected reaction of machine. You
have to make it sure that nobody is near the machine when
you use this function.
2 As you use Forcing mode of Forced I/O function to change
status of signal, however, the signal may look proof against
Forced I/O function, because LADDER program or I/O
device writes into the signal repeatedly. In this case, even
if the signal looks unchanged, actual signal may be
changed in very short moment. You should be careful for
the reaction of machine to such signal changes.

810
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

NOTE
1 Forced I/O function is enabled when RAM WRITE ENABLE
setting is set to YES in GENERAL screen of PMC Settings.
If the setting is NO, INPUT key will be just ignored.
2 Parameters of timer functional instructions, TMR, TMRB,
and TMRC, which have special monitor formats, are not
supported by Forced I/O function.

(c) Notes for Search function


1 The string followed by [SEARCH] is treated as symbol first. In
case that the symbol D0 is assigned to the bit address R0.0, the
operation D0 + [SEARCH] will search the bit address R0.0,
instead of byte address D0.3
2 To search the symbol that consists of only digit characters, which
will usually be treated as net number, you can use leading space to
specify explicitly the string is symbol. For example, while 123
+ [SEARCH] will search the 123rd net from top of the LADDER,
_123 + [SEARCH] (_ is space) will search address with
symbol 123.
3 When the range for searching is GLOBAL, and the target is found
in other than displaying subprogram, the screen will automatically
switch to the subprogram to which the found target belongs.
Searching GLOBAL net number that current subprogram does not
contain, for example, the subprogram that contains the net of the
net number will appear in the screen, displaying the net.
(d) Shortcuts
1 Right/left cursor move keys that are following some string means
searching forward/backward. You can use following strings for
this search operation:
D Digits for net number
D 1 for top, 0 for bottom
D S + digits, for Functional instructions
D Other string for symbol or bit/byte address
D Leading space always makes the string treated as a symbol or
address.
Example: _123+[SEARCH] (_ means space) will search
the symbol 123 instead of the 123rd net.
2 When cursor is hidden, left/right cursor move keys without string
act just like [PREV]/[NEXT] soft keys.
3 String followed by [SEARCH] soft key in PMCLAD Main soft
keys starts searching directly. In this case, [SEARCH] soft key
acts just like right cursor move key.
4 [SEARCH] soft key in Search soft keys without string searches
the address or the functional instruction under cursor forward. If
cursor is hidden, or cursor is placed neither on a relay nor on a
functional instruction, this operation just repeats the last successful
search forward, just like [NEXT] soft key.

811
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5 [WSRCH] soft key without string searches forward a write coil


of the same address with relay under cursor. If cursor is hidden, or
cursor is not placed on a relay, this operation will search a write coil
of the bit address that is searched at last successful search. If the
last search was not made with bit address, the last entered string for
searching is used to determine what bit address is to be searched for
a write coil.
6 [FSRCH] soft key without string searches forward the same
functional instruction with one under cursor. If cursor is hidden,
or cursor is not placed on a functional instruction, this operation
will search a functional instruction that is searched at last
successful search. If the last search was not made for functional
instruction, the last entered string for searching is used to determine
what functional instruction is to be searched.
7 [LIST] soft key following string that indicates subprogram,
switches subprogram on LADDER Diagram Monitor screen.
Examples for strings to specify subprogram are following:
L1 Level 1
P10, 10 Subprogram P10
0(zero), G Whole of LADDER program (Global)

3.1.3
Setting the Screen

(a) Setting items


LADDER Diagram Monitor Setting screen contains the setting items
below:
D ADDRESS NOTATION
Determines whether the bit and byte addresses in the LADDER
Diagram are displayed as corresponding symbols, or the addresses
themselves.

812
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

SYMBOL
Addresses that have a symbol are displayed by the symbols.
Addresses without symbols are displayed by the addresses
themselves.
ADDRESS (default)
All addresses are displayed as the addresses themselves even if
they have a symbol.
D FUNCTION STYLE
Change the shape of functional instructions. There are three
options as below. You have to choose other than COMPACT to
show the current values of address parameters of functional
instructions.
COMPACT
Occupies least space in diagram. Monitors of current values of
address parameters are omitted.
WIDE (default)
Extends the box horizontally to reserve spaces for the monitors
of current values of address parameters. The box becomes
wider than COMPACT.
TALL
Extends the box vertically to reserve spaces for the monitors of
current values of address parameters. The box becomes taller
than COMPACT.
Display styles of functional instructions

ACT
SUB 4 R0110
CMPACT
DEC 0

ACT
SUB 4 R0110 = 00
WIDE
DEC 0

ACT
SUB 4 R0110
TALL
DEC = 00
0

The displays of current values of address parameters change their


format according to each parameter. Refer to the table in Display
Format for Parameters for detail.
When you place the cursor on an address parameter, its current
value is displayed in the Additional Information Line in both
formats of binary decimal, and BCD (or hexadecimal binary).

813
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

D SHOW COMMENT OF CONTACT


Changes the display format of the comment displayed under each
contact.
NONE
Displays no comment under each contact. In this mode, more
contacts (8 by 9 or 9 by 9 (numberofcontactsinrow by
numberofcontactsincolumn)) can be displayed on the
screen by the space for the comment.
1 LINE
Displays the comment in 1 line of 15 halfsize characters (in 1
line of 7 Japaneselanguage characters) under each contact. The
width of each contact and the number of contacts that can be
displayed on the screen vary depending on the number of
characters in each comment. The number of contacts that can be
displayed on the screen is from 4 by 6 to 9 by 6
(numberofcontactsinrow by numberofcontactsin
column).
2 LINES (default)
Displays the comment in 2 lines of 15 halfsize characters each
(in 2 lines of 7 Japaneselanguage characters each) under each
contact. The width of each contact, the number of lines for each
comment, and the number of contacts that can be displayed on
the screen vary depending on the number of characters in each
comment. The number of contacts that can be displayed on the
screen is from 4 by 5 to 9 by 5 (numberofcontactsinrow by
numberofcontactsincolumn).
Comment display formats

814
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

D SHOW COMMENT OF COIL


Determines whether to show coil comments.
YES (default)
Right margin of 14 characters is reserved for display of coil
comments. You can set
NO
Right margin is used to extend diagram by one more relay,
instead of showing coil comment. The screen position bar is
also displayed at the right edge of the screen in this option.
Show Coil comment setting

YES NO

D SHOW CURSOR
Determines whether to show cursor.
YES (default)
Cursor is displayed. Cursor move keys will move the cursor.
When the cursor is placed on bit or byte addresses, the
information of the address is displayed at Additional
Information Line. When you search something with the cursor
displayed, the cursor goes directly where it is found. This
option is recommended for search operation with LADDER
program that contains many large nets.
NO
Cursor is not displayed. Up/down cursor move keys will scroll
the contents of screen directly. When you search something
with the cursor hidden, the net, which contains it, will appear
at the top of the screen.
D DIAGRAM APPEARANCE SETTING
Shows how the ladder diagram is displayed. You can set the colors
of the lines, relays, symbols, comments, and function command
parameters that are components of the ladder diagram. At right, the
monitor display of a symbol, OFF contact, ON contact, function
command parameter, and comment appears as an example. The
display of this example is changed according to the settings.
For colors, you can set the display color for each of the five types
of components of the ladder diagram.
ADDRESS COLOR
Sets the color of symbols and addresses. Enter a number or
increase or decrease the number using the left and right arrow
keys. You can specify one of 14 numbers from 0 to 13.

815
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

DIAGRAM COLOR
Sets the color of the entire ladder diagram. Set the color in the
same way as for symbol color.
ACTIVE RELAY COLOR
Sets the color of relays in the on state. The color of the relays
in the off state is the same as for the ladder diagram. Set the color
in the same way as for Symbol color.
PARAMETER COLOR
Sets the color of the monitor display of function command
parameters. The monitor display appears only when a value
other than Compact is set for Function command display
form. Set the color in the same way as for Symbol color.
COMMENT COLOR
Sets the color of comments. Set the color in the same way as for
Symbol color.
D SUBPROGRAM NET NUMBER
Determines whether a net number is counted as LOCAL starting
from the top of current subprogram, or is counted as GLOBAL
starting from the top of whole program. This setting also affects
the expression of net number at searching nets by number.
LOCAL
Net number starts from 1 at top of current subprogram. Net
number is defined only within current subprogram. The net
number information at upper right of the screen is displayed in
the format displaying range / nets in subprogram NET.
GLOBAL (default)
Net number starts from 1 at top of Level 1 program. Net number
is defined identically at whole of program. The net number
information at upper right of the screen is displayed in the
format displaying range / subprogram range NET.
Definition of Net number

LOCAL GLOBAL
1 1
2 2
3 3
|
48
49
50

Current 1 Current 51
| |
Subprogram Subprogram
19 69
1 70
|
98

D WRAP SEARCH ENABLED


Allows search process to wrap from top/bottom to bottom/top to
continue to search.

816
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

YES (default)
Downward search will continue to search from top of LADDER
when reaches to bottom. Upward search will also continue to
search from bottom when reaches to top.
NO
Search process will fail when reached top or bottom, and
displays an error message at Message Line.
Wrap search

YES NO
Not found

[PREV] [NEXT] [PREV] [NEXT]

Not found

(b) Soft keys


LADDER Diagram Monitor Setting screen has the soft keys of options
and following:
D [INIT] Initialize all settings
All settings will be initialized to the default values.

817
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

3.1.4 The following table shows all monitor formats for each parameter of each
Display Format for functional instruction.
Parameters
NOTE
1 Variable in Monitor Format field means that this parameter
changes its size according to the other parameter. Refer to
the descriptions for each functional instruction for detail.
2 Functional instruction with * mark has Data table.

No. Name Parameter Monitor Format No. Name Parameter Monitor Format
1 END1 18 XMOV 1 Constant
2 END2 2 4digits BCD
3 TMR 1 Special 3 4digits BCD
4 DEC 1 2digits BCD 4 4digits BCD
2 Constant 19 ADD 1 Constant
5 CTR 1 Special 2 4digits BCD
6 ROT 1 Constant 3 4digits BCD
2 4digits BCD 4 4digits BCD
3 4digits BCD 20 SUB 1 Constant
4 4digits BCD 2 4digits BCD
7 COD * 1 Constant 3 4digits BCD
2 2DIGITS BCD 4 4digits BCD
3 4digits BCD 21 MUL 1 Constant
8 MOVE 1 Constant 2 4digits BCD
2 Constant 3 4digits BCD
3 2digits HEX 4 4digits BCD
4 2digits HEX 22 DIV 1 Constant
9 COM 1 Constant 2 4digits BCD
10 JMP 1 Constant 3 4digits BCD
11 PARI 1 1byte binary 4 4digits BCD
14 DCNV 1 No monitor 23 NUME 1 Constant
2 No monitor 2 4digits BCD
15 COMP 1 Constant 24 TMRB 1 Special
2 4digits BCD 2 Constant
3 4digits BCD 25 DECB 1 Constant
16 COIN 1 Constant 2 Variable binary
2 4digits BCD 3 Constant
3 4digits BCD 4 2digits HEX
17 DSCH 1 Constant 26 ROTB 1 Constant
2 4digits BCD 2 Variable binary
3 4digits BCD 3 Variable binary
4 4digits BCD 4 Variable binary
5 Variable binary

818
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

No. Name Parameter Monitor Format No. Name Parameter Monitor Format
27 CODB * 1 Constant 40 NUMEB 1 Constant
2 Constant 2 Constant
3 1byte binary 3 Variable binary
4 Variable binary 41 DISPB* 1 Constant
28 MOVOR 1 2digits HEX 42 EXIN* 1 8digits HEX
2 2digits HEX 43 MOVB 1 1byte binary
3 2digits HEX 2 1byte binary
29 COME 44 MOVW 1 2bytes binary
30 JMPE 2 2bytes binary
31 DCNVB 1 Constant 45 MOVN 1 Constant
2 No monitor 2 4bytes binary
3 No monitor 3 4bytes binary
32 COMPB 1 Constant 47 MOVD 1 4bytes binary
2 Constant or 2 4bytes binary
Variable binary 48 END3
3 Variable binary 51 WINDR 1 2bytes binary
33 SFT 1 4digits HEX 52 WINDW 1 2bytes binary
34 DSCHB 1 Constant 53 AXCTL 1 Constant
2 Variable binary 2 8digits HEX
3 Variable binary 54 TMRC 1 Constant
4 Variable binary 2 Special
5 Variable binary 3 Special
35 XMOVB 1 Constant 55 CTRC 1 2bytes binary
2 Variable binary 2 2bytes binary
3 Variable binary 56 CTRB 1 Constant
4 Variable binary 2 Special
5 Variable binary 58 DIFD 1 Constant
36 ADDB 1 Constant 59 EOR 1 Constant
2 Variable binary 2 Variable HEX
3 Constant or 3 Constant or
Variable binary Variable HEX
4 Variable binary 4 Variable HEX
37 SUBB 1 Constant 60 AND 1 Constant
2 Variable binary 2 Variable HEX
3 Constant or 3 Constant or
Variable binary Variable HEX
4 Variable binary 4 Variable HEX
38 MULB 1 Constant 61 OR 1 Constant
2 Variable binary 2 Variable HEX
3 Constant or 3 Constant or
Variable binary Variable HEX
4 Variable binary 4 Variable HEX
39 DIVB 1 Constant 62 NOT 1 Constant
2 Variable binary 2 Variable HEX
3 Constant or 3 Variable HEX
Variable binary 64 END
4 Variable binary 65 CALL 1 No monitor

819
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

No. Name Parameter Monitor Format


66 CALLU 1 No monitor
68 JMPB 1 No monitor
69 LBL 1 No monitor
70 NOP 1 Constant
71 SP 1 No monitor
72 SPE
73 JMPC 1 No monitor

Functional Instructions of Special monitor format

TMR Displays in Current/Preset format by seconds


Displays in Current/Preset format by BCD or binary according to the Counter Type setting in LADDER
CTR
Program.
TMRB Displays current value by seconds (Preset value is displayed by milliseconds)
The 2nd parameter shows preset value, and the 3rd parameter shows current value as their monitor
displays.
These two monitor displays changes their format according to the 1st parameter as below:
1st Parameter Precision Display Format
0 8 ms by seconds
1 48 ms by seconds

TMRC 2 1 second HH:MM:SS


3 10 seconds HH:MM:SS
4 1 minute HH:MM:ss
5 1 ms by seconds
6 10 ms by seconds
7 100 ms by seconds

CTR Displays setting value with binary format.

820
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

3.2 Functional Instruction Data Table Viewer screen shows the contents of
data table that belongs to some functional instructions.
FUNCTIONAL To reach this screen, at LADDER Diagram Monitor screen, press
INSTRUCTION DATA [TABLE] soft key that is displayed when the cursor is on the following
TABLE VIEWER functional instructions which have a data table.
SCREEN D Functional Instruction COD (SUB7)
D Functional Instruction CODB (SUB27)
Following operations are available at this screen.
D Search for data table number. [NO.SRCH]
D Search for data value. [V.SRCH]
D Change the displaying data digits. [BCD2],[BCD4]
(These soft keys can be operated only at Functional Instruction
Data Table Viewer screen of Functional Instruction COD.)

Functional Instruction Data Table Viewer screen of Functional


Instruction COD.

821
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

3.2.1
Screen Structures

Functional instruction Number of data Data length Data type
name

Area for Data Table

Message line Key input line

1 The functional instruction name, the number of data table, data length
and data types are displayed above the Data Table.
2 In the message line, error messages or inquiry messages will be
displayed depending on the situation.
3 In case of functional instruction COD, the data of 6 lines and 14
columns can be displayed in the area for Data table.
In case of functional instruction CODB, the data of 4 lines and 14
columns can be displayed in the area for Data table.

3.2.2
Operations Soft keys of Functional Instruction Data Table Viewer screen of functional instruction COD.

Search for Display Display BCD4


Search for data
data value BCD2 digits
table number

Soft keys of Functional Instruction Data Table Viewer screen of functional instruction CODB.

Search for data Search for


table number data value

822
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

1 [NO.SRCH] Search for data table number


Searches the data table number which you specified.
Then the cursor is displayed on the data of the target number.
And the cursor is disappeared when you operate something.
2 [V.SRCH] Search for data value
Searches the data value which you specified.
Then the cursor is displayed on the target data.
And the cursor is disappeared when you operate something.
3 [BCD2] Display BCD2 digits
Changes the display data type to 2 digits of BCD. This operation only
switches the display data type. So it does never edit the data on
memory.
4 [BCD4] Display BCD4 digits
Changes the display data type to 4 digits of BCD. This operation only
switches the display data type. So it does never edit the data on
memory.
5 Cursor move keys, Page change keys
You can scroll screen by right/left cursor move keys and Page change
keys.

823
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

3.3
PROGRAM LIST
VIEWER SCREEN
3.3.1 Program List Viewer screen (Detail) shows the detail information that are
Detail Screen program size, program net count and so on for program.

Title information
(REMARKS) Total program count

Program of operation target

Message line Key input line Area for Program List

(a) Screen Structure


1. The title information (REMARKS) of the Ladder Program and the
total program count are displayed above the Program List.

2. In the message line, error messages or inquiry messages will be


displayed depending on the situation.
3. In the area for Program List, 14 data can be displayed at maximum.
(b) Area of Program List
1. The L means program type of Ladder. It is displayed in the L/S
field for each program.
2. Program name is displayed in the PROG NO. field for each
program.
There are three kinds of program names.
COLLECT : It means the collective program.
GLOBAL : It means the whole program.
LEVELn (n=1,2,3) : It means the Ladder level 1, 2 and 3.
Pm (m=1 to 2000) : It means subprogram.
3. The symbol is displayed in the SYMBOL field for each program.
If no symbol is set into the subprogram, the SYMBOL field will
be blank.

824
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

4. The comment is displayed in the COMMENT field for each


program.
If no comment is set into the subprogram, the COMMENT field
will be blank.
5. The program size is displayed in the SIZE (BYTE) field for each
program.
If the program size is not over 1024 byte, the unit is shown in byte.
If it is over 1024 byte, the unit is shown in kilo (1024) byte with
K.
Ex.) The case that program size is not over 1024 byte.
1023 bytes : 1023 is shown.
Ex.) The case that program size is over 1024 byte.
20000 bytes : 19.5K is shown.
6. In the NET COUNT field for each program, total number of nets
in the program and first net number of the program in the whole
Ladder program are displayed as follows.
Total number of nets in the program* / First global net number of
the program in the whole Ladder program*
* Maximum is 99,999.
7. The status of protection is displayed in the P field for each
program.
Following icons mean the status of protection.
P : Monitoring and editing program are disabled.
R : Monitoring program is enabled. Editing program is
disabled.
(Blank) : Monitoring and editing program are enabled.

825
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

3.3.2 Program List Viewer screen (Brief) shows less information than Program
Brief Screen List Viewer screen (Detail), to increase the number of items. The program
type, the status of protection and the name or symbol are displayed for
each program.
Title information
Program of operation target Total program count
(REMARKS)

Area for Program List

Message line Key input line Additional information line

The detail information of program that is pointed by the cursor is


displayed on additional information line.
(a) Screen Structure
1. The title information (REMARKS) of the Ladder Program and the
total program count are displayed above the Program List.
2. In the message line, error messages or inquiry messages will be
displayed depending on the situation.
3. In additional information line near the bottom of the screen, the
following information is displayed for the program under the
cursor.
D program name
D symbol, comment
D program size
D total number of nets
D First global net number of the program in the whole Ladder
program.
4. In the Program List area, the programs 14 lines and 5 columns
can be displayed in maximum.
(b) Area of Program List
The following items are displayed in Program List area of Program
List Viewer screen.
The meanings of these items are the same as the items of Program List
Viewer screen (Detail).

826
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

D Program type.
D Status of protection
D Program name or symbol. (See Screen Setting for Program List
Viewer screen section for selecting this item.)

3.3.3
Operations Soft key of Program List viewer screen
Search for program

Display the contents of program Screen Settings

(a) Operation with Softkeys


1 [ZOOM] Display the contents of program
Goes to LADDER Diagram Monitor screen. If you press [ZOOM]
soft key without strings, the program under the cursor is displayed
at LADDER Diagram Monitor screen.
If you entered program name (See (c) 1. for detail) or symbol before
pressing [ZOOM] soft key, the program according to the preceding
string is searched and the program is displayed at LADDER
Diagram Monitor screen.
But, when the selected program is protected to monitor, you have
to unlock the protection.
2 [SEARCH] Search for program
Searches the program. If you entered program name (See (c) 1. for
detail) or symbol and press [SEARCH] soft key, the program
according to the preceding string is searched, the cursor points the
program.
3 [SETING] Screen Settings
Goes to setting screen for Program List Viewer screen. You can
change various settings for Program List Viewer screen at the
screen. Use Return key [<] to return to Program List Viewer screen.
See Settings for Program List Viewer screen section for the
detail.
(b) Other operations
1 Cursor move keys, Page change keys
You can move cursor by all cursor move keys and Page change
keys.
And if you entered program name (See (c) 1. for detail) or symbol
and press Right cursor move key, the program according to the
preceding string is searched, the cursor points the program.
2 INPUT key
You can operate same as [ZOOM] soft key.

827
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

(c) Note of searching operations


1 When program is searched by program name, the strings that show
each program are as follows.
GLOBAL : 0(Zero) or G
LEVEL1, 2, 3 : L + Number Ex.) L1, L01, etc
Pn : Number or P + Number Ex.) 1, P1, P01
2 Search function by [SEARCH] soft key or Right cursor move key
tries to suppose the given word as an item to be searched in
following order.
(i) The string for GLOBAL or LEVEL : 0(Zero), G, L +
Number
The number for subprogram : Number
(ii) Symbol
(iii) The string for subprogram : P + Number

3.3.4
Setting Screen

(a) Setting items


Program List Viewer/Editor screen contains the setting items below:
D VIEW FORMAT
Determines whether the list data in the Program List Viewer/Editor
screen are displayed as detail format, or brief format themselves.
DETAIL (default)
The Program List Viewer/Editor screen shows Detail
information for each program.
The items of detail information are program type, program
name, symbol, comment, program size, program net count and
status of protection.

828
3. LADDER DIAGRAM
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION MONITOR (PMCSB7)

BRIEF
The Program List Viewer/Editor screen shows less information
than DETAIL, to increase the number of items. The program
type, the status of protection and the name or symbol are
displayed for each program.
The detail information of program that is pointed by the cursor
is displayed on additional information line.
D ADDRESS NOTATION
Determines whether the programs in the Program List
Viewer/Editor screen are displayed as corresponding symbols, or
the addresses themselves.
SYMBOL
Addresses that have a symbol are displayed by the symbols.
Addresses without symbols are displayed by the addresses
themselves.
ADDRESS (default)
All addresses are displayed as the addresses themselves even if
they have a symbol.
D SORT BY
Determines whether the programs in the Program List
Viewer/Editor screen are displayed in order of program number, or
symbol name themselves. And When ADDRESS NOTAION is
SYMBOL, this determination is enabled. So if ADDRESS
NOTAION is ADDRESS, the programs are always displayed in
order of program number.
PROGRAM NUMBER (default)
The programs are displayed in order of program number.
SYMBOL
Programs that have a symbol are displayed in order of the
symbol name. Programs without symbols are displayed in order
of program number after programs with the symbols.
GLOBAL, LEVEL1, LEVEL2, LEVEL3 are out of target of
sort.
D PROTECTED PROGRAM
Determines whether protected programs in the Program List
Viewer/Editor screen are displayed or not. On each screen, the
protected program means as follows.
On Program List Viewer screen : the program is protected to
monitor.
On Program List Editor screen: the program is protected to edit.
SHOW (default)
The protected programs are displayed in the Program List
Viewer/Editor screen.
HIDE
The protected programs are not displayed in the Program List
Viewer/Editor screen.

829
3. LADDER DIAGRAM
MONITOR (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

D FRAME NET IN SUBPROGRAM MODE


Frame net means functional instruction END1, 2 and 3 on LEVEL
1,2,3, and functional instruction SP and SPE on subprogram.
It determines whether the frame net in the LADDER Diagram
Monitor/Editor screen are displayed or not, when you selected the
program and press [ZOOM] soft key in the Program List
Viewer/Editor screen.
SHOW (default)
The frame net is displayed in the LADDER Diagram
Monitor/Editor screen.
HIDE
The frame net is not displayed in the LADDER Diagram
Monitor/Editor screen.

830
4. COLLECTIVE MONITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

4 COLLECTIVE MONITOR FUNCTION (PMCSB7)

On Collective Monitor screen, a monitor of the necessary ladder nets can


be displayed by specifying ladder nets.

831
4. COLLECTIVE MONITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

4.1 The calling operation of Collective Monitor screen is as follows.


CALLING SCREEN (1) Calling from Program List Viewer screen
Press soft key [ZOOM] after moving the cursor to COLLECT
program position on Program List Viewer screen.

Fig. 4.1(a) Program List Viewer screen


(2) Calling from Ladder Diagram Monitor screen
Press [SWITCH] soft key on Ladder Diagram Monitor screen.

Fig. 4.1(b) Ladder Diagram Monitor screen

832
4. COLLECTIVE MONITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

4.2 Collective Monitor screen is as follows. Any ladder diagram is not


displayed first. Ladder nets selected by the operation of a coil search and
SCREEN picking up nets is added. 128 nets or less of ladder net can be added on
CONFIGURATION Collective Monitor screen. When adding more new nets, most recently
added 128 nets are displayed.

Fig. 4.2 Collective Monitor screen (Initial screen)

833
4. COLLECTIVE MONITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

4.3
SCREEN
Collective Monitor screen
OPERATIONS
Program List Viewer Jump to the ladder diagram net Initialization of Collective Monitor screen

Pick up a ladder diagram net Switches to Ladder Delete a net Screen setting
Diagram Monitor screen.

Fig. 4.3(a) Soft key of the Collective Monitor screen


(a) Operations using the soft keys
1. [LIST] Calling Program List Viewer screen
Calls Program List Viewer screen. On Program List Viewer screen,
you can switch subprograms to be displayed on Ladder Diagram
Viewer screen.
2. [PICKUP] Picking up ladder nets.
Picks up ladder nets with coil which you want to monitor, on
Collective Monitor screen.
3. [JUMP] Jump to a ladder net.
On Ladder Diagram Monitor screen, search the ladder net at a
cursor position on Collective Monitor screen and jumps to the
ladder net.
4. [SWITCH] Switches to Ladder Diagram Monitor screen.
Switches to Ladder Diagram Monitor screen.
5. [ERASE] Quits to display a ladder diagram net on the screen. (1
net)
Quits to display a ladder diagram net (only 1 net) which is picked
up on Collective Monitor screen.
6. [ERSALL] Quits to display a ladder diagram net on the screen. (all
nets)
Quits to display ladder diagram nets (all net) which is picked up on
Collective Monitor screen.
7. [SETING] Screen settings
Calling the setting screen for Collective Monitor screen. You can
change each settings of a ladder diagram display. Return to
Collective Monitor screen when press the return key [<].
D Specification of monitored ladder diagram
The operation for picking up ladder nets which you want to monitor
on Collective Monitor screen is as follows.
1. Specification of ladder nets on Collective Monitor screen
Specify the address by key input
Pick up ladder nets by inputting the address used with the coil.
Specify the address from ladder diagram net on Collective
Monitor screen
Specify any relay by cursor on the ladder diagram net which is
picked up already. The net, which uses the relay which you
specified for coil, is picked up.

834
4. COLLECTIVE MONITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

2. Specify the ladder net on Ladder Diagram Monitor screen


Specify a ladder diagram net on Ladder Diagram Monitor screen
and the net is picked up on Collective Monitor screen.
D Pick up a ladder net on Collective Monitor screen
You can pick up a ladder net on Collective Monitor screen. The
operation for picking up ladder nets is as follows.
a) Specification of address
1. Enter the address which you want to monitor. (Ex. R14.7)
2. Press [PICKUP] soft key.
3. The net with the coil, which you specified by 1, is picked up to
the top of screen.
b) Specification of address from the ladder net on the screen
1. Move the cursor to a relay on the ladder net which uses address
that you want to monitor.
2. Press [PICKUP] soft key.
3. The net with the coil, which uses the address that you specified
by 1, is picked up to the top of screen and the cursor moves to
the specified coil position.

Fig. 4.3(b) Collective Monitor screen


D Pick up a ladder net on Ladder Diagram Viewer screen
You can pick up a ladder net on Ladder Diagram Viewer screen. The
operation for picking up ladder nets is as follows.
1. Press [SEARCH] soft key on Ladder Diagram Viewer screen. Then
soft keys for search are displayed.
2. Move the cursor to any ladder nets which you want to pick up.
3. Press [PICKUP] soft key and the net, which is specified by 2, is
picked up to a top of Collective Monitor screen.
4. As for the ladder net which is picked up to Collective Monitor
screen, F mark is displayed at the left side of the selected net.

835
4. COLLECTIVE MONITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Fig. 4.3(c) Ladder Diagram Viewer screen (Soft key for search)

836
4. COLLECTIVE MONITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

4.4
ALARM MESSAGE
AND
COUNTERMEASURE
Message that may be displayed during Collective Monitor function
Alarm number Faulty location/corrective action Contents

THE ADDRESS IS NOT FOUND Specify the address used with write Specified address was not used for the
coil write coil.

SYMBOL UNDEFINED Specify the defined symbol or address. Specified symbol was not defined.

WRITE COIL NEEDS BIT ADDRESS Specify the bit address The byte address was specified when
specifying the address used with write
coil.

SOME NETS ARE DISCARDED Not all the nets of picking up object All nets were not picked up because
can be picked up. Select the net of there were the nets of picking up ob-
picking up on Ladder Diagram Viewer ject more than 128 nets.
screen and pick up the net manually.

837
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5 LADDER DIAGRAM EDITOR FUNCTION (PMCSB7)

838
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

5.1 In Ladder Diagram Editor screen you can edit Ladder program to change
its behavior. To reach Ladder Diagram Editor screen, press [EDIT] soft
LADDER DIAGRAM key at Ladder Diagram Monitor screen. Following operations are
EDITOR SCREEN available at Ladder Diagram Editor screen.
Delete by net [DELETE]
Move by net [CUT] & [PASTE]
Copy by net [COPY] & [PASTE]
Change address of contacts and coils bit address + INPUT key
Change parameters of functional instructions
number or byte address+ INPUT key
Add new net [CREATE]
Change construction of net [MODIFY]
Make changes effective [UPDATE]
Abandon changes [RESTORE]

Fig. 5.1 Ladder Diagram Editor screen

NOTE
1 You can edit a ladder regardless of whether the ladder is
running/stopping. But, when you are going to execute the
edited ladder, it is necessary to update the ladder. By exiting
Ladder Editor screen, or pressing [UPDATE] soft key, update
the edited ladder. As for the protection of the editing operation,
please refer to 5.3 Example for setting parameters.
2 If the power is turned off before the edited sequence program
is written to flash ROM, the result of the edit is erased.Use the
input/output screen to write the sequence program to flash
ROM. When K902#0 is set to 1, a confirmation message
appears at the termination of editing, asking whether to write
the sequence program to flash ROM.

839
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.2
SCREEN Title information(REMARKS) Displayed subprogram Display position information

CONFIGURATION

Cursor
Display position

Ladder diagram display area

Message display line Key input line Additional information display line

Fig. 5.2 Ladder Diagram Editor screen


(a) Screen configuration
It is the basically same as Ladder diagram Monitor screen, except that
no monitor displays of relays and parameters of functional instructions
are displayed.
(b) Ladder diagram display
1. Style of a ladder diagram is basically the same as Ladder diagram
Monitor screen, except that functional instructions are drawn
always in COMPACT format that has no monitor displays.
2. Cursor is shown always. And the net, which will be an object of
following editing operations, is emphasized in screen.

840
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

5.3
SCREEN
Soft keys on the Ladder Diagram Editor screen
OPERATIONS
Program List Add new net Make changes effective
Cut net Paste net

Change to search soft keys Edit net Select multiple nets Delete net Copy net

Abandon changes RUN/STOP a sequence program

Setting screen

Fig. 5.3 Soft keys on Ladder Diagram Editor screen


(a) Operations using the soft keys
1. [LIST] Call Program List Editor screen
Calls Program List Editor screen. On Program List Editor screen,
you can select a subprogram to be edited on Ladder Diagram Editor
screen.
2. [SEARCH] Search and jump menu
Switches to the search soft keys. To return to the main soft keys,
press the Return key [<]. The search soft keys are quite same with
ones of Ladder diagram Monitor screen.
3. [MODIFY] Call Net Editor screen
Calls Net Editor screen to modify structure of the selected net.
4. [CREATE] Create new net
Create and add new net to cursor position. Pressing this soft key
reaches Net Editor screen, so that new net is constructed.
5. [UPDATE] Make changes effective
Updates running the ladder program to currently edited ladder
program, so that the all modifications will take effects, and remains
Editor screen. If it succeeds to update running ladder, edited ladder
starts to run.

WARNING
You have to pay special attention to modify running ladder
program. If you modify the ladder program in wrong way, or
update the ladder program with the machine in improper
status, it may cause unexpected reaction of the machine.
You have to make it sure that modifications you make on
the ladder program is appropriate, machine is in proper
status, and nobody is near the machine, when you update
the ladder program.

841
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

6. [SELECT] Select multiple nets


Selects multiple nets for following operations such as [DELETE],
[CUT], [COPY]. Pressing [SELECT] soft key leads to a mode to
select one or more nets for following editing operation. Use cursor
move keys and search functions to select nets, as you like. Being
in mode to select nets is indicated by dented [SELECT] soft key,
and the information of selected nets is shown in additional
information line at near bottom of screen.
7. [DELETE] Delete net
Deletes selected nets. The nets deleted by [DELETE] soft key are
lost. If you delete wrong nets by [DELETE], you have to abandon
the all modifications you have made, and restore the ladder
program to the original one before editing operation.
8. [CUT] Cut nets
Cuts selected nets. The cut nets are preserved in Paste Buffer, and
disappear from diagram. The contents of the Paste Buffer before
[CUT] operation are lost. [CUT] and [PASTE] soft keys are used
to move nets.
9. [COPY] Copy nets
Copy selected nets into the Paste Buffer. No change on diagram
will be made. The contents of the Paste Buffer before [COPY]
operation are lost. [COPY] and [PASTE] soft keys are used to copy
nets.
10.[PASTE] Paste nets
Pastes nets at cursor position, which were stored into the Paste
Buffer by [CUT] or [COPY] soft key. Pressing [PASTE] soft key
while selecting nets using [SELECT] soft key alters the selected
nets with the nets in the Paste Buffer. The contents of the Paste
Buffer will remain until turning CNC power off.
11.[RESTORE] Abandon changes
Abandons all changes, and restores the ladder program to the one
at entering Ladder Diagram Editor screen, or last updated one using
[UPDATE] soft key. This soft key is useful when you make wrong
modifications and hard to recover from them.
12.[SETING] Screen settings
Calls setting screen for Ladder Diagram Editor screen. You can
change various settings for Ladder Diagram Editor screen at the
screen. Use the Return key [<] to return to Ladder Diagram Editor
screen.
13.[RUN]/[STOP] Run and stop the ladder program
Controls the ladder program execution. [RUN] soft key makes the
ladder run and [STOP] soft key makes the ladder stop. Both soft
keys will confirm your intention. When you are sure to run or stop
the ladder program, press [YES] to take an action.

842
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

WARNING
You have to pay special attention to run/stop the ladder
program. Running/stopping the ladder program in a wrong
timing, or with machine in improper status, may cause
unexpected reaction of machine. At stopping the ladder
program, a safety mechanism and watch by the ladder
program is not operated. You have to make it sure that
machine is in proper status, and nobody is near the
machine when you run/stop the ladder program.

14.[<] Exit Editor


Updates running the ladder program to edited ladder program, so
that the all modifications will take effects, and exits Editor screen.
When Ladder Diagram Editor screen is active and the function keys
such as <SYS> key will not work, the data under edit is deleted.

WARNING
You have to pay special attention to modify running the
ladder program. If you modify the ladder program in wrong
way, or update the ladder program with the machine in
improper status, it may cause unexpected reaction of the
machine. You have to make it sure that modifications you
make on the ladder program is appropriate, machine is in
proper status, and nobody is near the machine, when you
update the ladder program.

(b) Operations using other keys


1. Cursor move keys, Page change keys
Cursor move keys and Page change keys move cursor on screen.
When cursor is placed on some relay or some address parameter of
a functional instruction, the information about the address under
cursor is displayed at Additional Information Line.
2. bit address + ENTER key
Changes bit address of relay under cursor.
3. number or byte address + ENTER key
Changes parameter of functional instructions under cursor. But,
there are some parameters that can not change by this operation. If
you see a message that means that this parameter can not be
changed, use Net Editor screen to change the parameter.
(c) Shortcut operations
1. Same shortcut search operations with Ladder Diagram Monitor
screen are available. For their detail, see descriptions about
Shortcut operations of Ladder Diagram Monitor screen.
2. Same shortcut operations using [LIST] soft key with Ladder
Diagram Monitor screen are available.

843
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.4
SETTING SCREEN

Fig. 5.4 Ladder Diagram Editor Setting screen


(a) Settings
There are the following settings on Ladder Diagram Editor Setting
screen:
ADDRESS NOTATION Default: ADDRESS
Specifies whether to display each bit and byte address in the ladder
diagram with the symbol or address.
SHOW COMMENT OF CONTACT Default: 2 LINE
Changes the display format of the comment displayed under each
contact.
SHOW COMMENT OF COIL Default: YES
Specifies whether to display the comment of each coil.
DIAGRAM APPEARANCE SETTING
Changes the color for ladder diagram. You can set the colors of a
line, relays and etc. that are components of the ladder diagram.
ADDRESS COLOR Default: Green (1)
DIAGRAM COLOR Default: Black (6)
SELECTED NET COLOR Default: Yellow (2)
PROTECTED NET COLOR Default: Light blue (5)
COMMENT COLOR Default: Light blue (5)
SUBPROGRAM NET NUMBER Default: GLOBAL
Specifies whether to display the LOCAL numbers, which are
assigned to the nets only in the subprogram, or GLOBAL
numbers, which are assigned to the whole ladder program when a
subprogram is displayed. The setting also affects the expression of
net number information at searching nets by number.
WRAP SEARCH ENABLED Default: YES
Specifies whether to return to the beginning of the ladder program
and continue search operation when the search operation reaches
the end of the ladder program.

844
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

FORCE POSTPROCESS AFTER EDIT Default: NO


Decides whether the postprocessing after editing ladder program,
which makes ladder program ready to run, will be always done, or
will be done only when ladder program is actually modified, at
exiting Ladder Diagram Editor screen.
(b) Soft keys
The following soft key is available on the Ladder Diagram Editor
Setting screen.
[INIT] Initializing all settings
All settings will be initialized to the default values.

845
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.5 In Net Editor screen, you can create new net, and modify existing net.
NET EDITOR 1. Modifying existing netWhen [MODIFY] soft key is used to reach Net
Editor screen, this screen is in MODIFY MODE to modify existing
SCREEN net.
2. Creating new net When [CREATE] soft key is used to reach Net
Editor screen, this screen is in CREATRE MODE to create new net
from nothing.
Following operations are available at this screen:
Place new contacts and coils bit address+ [ ], [ ], etc.
Change type of contacts and coils [ ], [ ], etc.
Place new functional instructions [FUNC]
Change type of functional instructions [FUNC]
Erase contacts, coils, and functional instructions
[ ]
Draw/erase connecting lines [ ], [ ], [ ]
Edit data table of functional instructions [TABLE]
Insert line/column [INSLIN],[INSCLM],[APPCLM]
Change address of contacts and coils bit address + INPUT key
Change parameters of functional instructions
number or byte address+ INPUT key
Abandon modifications [RESTOR]

5.5.1
Screen Configuration Displayed subprogram Display position information Edit mode

Cursor

Ladder diagram display area

Message display line Key input line Additional information display line

Fig. 5.5.1 Configuration of Net Editor screen


(a) Screen configuration
1. It is basically same with Ladder diagram Editor screen, except that
only one net is in this screen, and that position bar at right edge of
screen does not appear at this screen.

846
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

2. Current edit mode is indicated at right of the top line as CREATE


MODE or MODIFY MODE. When [MODIFY] soft key at Ladder
Diagram Editor screen is used to reach Net Editor screen, the screen
is in Modify mode, and when [CREATE] soft key is used, it is in Create
mode.
3. Current net number is displayed at right of the top line. The net number
is same with the net number in previous Ladder Diagram Editor
screen.
4. Net Editor screen expands image of net horizontally for a wider net
according to its width, while Ladder Diagram Monitor/Editor screen
folds nets wider than screen width. When net width is expanded over
screen width, attempt to move cursor out of screen will scroll net
image to the direction. The net of maximum size occupies area of 1024
elements, but actually available area may be little less for internal use
according to the internal condition: element means the space that is
occupied by single relay.

5.5.2
Screen Operations Soft keys on the Net Editor screen

Functional Left vertical Go to


A contact Normal coil instructions next net
connection

B contact Inverted coil Horizontal


connection Delete Right vertical
connection

Set coil Edit Data table Insert line Append column

Reset coil Abandon changes Insert column

Fig. 5.5.2(a) Soft keys on the Net Editor screen

847
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

(a) Screen configuration


1. [ ], [ ], [ ], [ ], [ s ], [ R ], Enter
and change relay
Place relays (contacts and coils), or change type of existing relays.
When one of these relay soft keys is pressed at cursor on blank
place, new relay of the soft key is placed under the cursor. When
the soft key follows a string that means a bit address, the bit address
is assigned to the newly placed relay. If no bit address is given, last
entered bit address is automatically used for the new relay. If no bit
address has been entered yet, the new relay will have no address
assigned to it. Contacts can be placed at other than rightmost
column, and coils can be placed at rightmost column only. Moving
cursor onto an existing relay, pressing a relay soft key of different
type changes the type of relay under the cursor. But, changing coil
to contact, and changing contact to coil are forbidden. It is basically
same with Ladder diagram Editor screen, except that only one net.

Sample of contacts and coils

2. [FUNC] Enter and change functional instruction


Places functional instruction, or changes type of existing
functional instruction. When [FUNC] soft key is pressed at cursor
on blank place, new functional instruction will be placed under the
cursor. List of available functional instructions is displayed, then
choose type of functional instruction to be entered. When [FUNC]
soft key follows a string that means number or name of a functional
instruction is entered directly, without the list screen. Moving
cursor onto an existing functional instruction, pressing [FUNC]
soft key changes the type of functional instruction under the cursor.
3. [ ]Draw horizontal connection
Draws horizontal connection line. Or alters an existing relay to
horizontal line.
4. [ ]Erase relays and functional instructions
Erases relays and functional instructions under cursor.
5. [ ], [ ]Draw and erase vertical connection
Draw vertical connection line upward from right or left edge of
relay or horizontal line under cursor. Or erase existing vertical
lines. If the relay or line under the cursor has no vertical line
upward, these soft keys have solid arrows, and indicate that
pressing them means drawing lines. On the other hand, if a vertical
line already exists under the cursor, arrows in these soft keys
become pale ([ ], [ ]), and indicate that pressing them
means erasing lines.

848
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

[ ]

[ ]

Drawing and erasing vertical connection line


6. [NXTNET] Go to next net
Finishes editing current net, and goes to next net. If [MODIFY] soft
key at Ladder Diagram Editor screen is used to reach Net Editor
screen, [NXTNET] will finish modifying current net, and the next
net will be an object of further editing operation.

Net 1 Editing Net 1 Editing


Net 2 Net 2a
Net 2a Net 3a
Net 3 [NXTNET] Net 3
[MODIFY] Net 4 Net 4

: :
: :

Action of [NXTNET] soft key in Modify mode (modifying an existing net)


If [NXTNET] soft key at Ladder Diagram Editor screen is used to
reach Net Editor screen, [NXTNET] will finish creating current
net, insert it into the ladder program, and start with blank to create
another new net to be inserted next to the current net.

Net 1 Editing Net 1


Net 2 Net 2 Editing
Net A
Net 3 [NXTNET] Net A
Net B
[CREATE] Net 4 Net 3
Net 4
:
: :

Action of [NXTNET] soft key in Create mode (creating new net)


7. [TABLE] Edit data table
Reaches Functional Instruction Data Table Editor screen to edit
data table of functional instruction under cursor. This soft key
appears only when cursor is a functional instruction that has data
table with it. For detail of editing operation of data table, see
descriptions of Functional Instruction Data Table Editor screen.

849
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

8. [RESTOR] Abandon changes


Abandons all changes, and restores net to the one at starting editing
this net. If [CREATE] soft key at Ladder Diagram Editor screen is
used to reach Net Editor screen, it will be back to blank net, and if
[MODIFY] soft key is used, it will be back to the old net before
modifications in this screen.
9. [INSLIN] Insert line
Inserts one blank line at cursor position. Diagram elements at or
below vertical cursor position will be shifted downward by one
line. Inserting line at middle of functional instruction box will
expand the box vertically to make a space between the input
conditions.

[INSLIN]

Fig. 5.5.2(b) Action of inserting line


10.[INSCLM] Insert column
Inserts one blank column at cursor position. Diagram elements at
or on right of horizontal cursor position will be shifted to right by
one column. And if there is no room to shift the elements, a new
column is added and the Diagram area will be expanded to right.

[INSCLM]

Action of inserting column

850
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

11.[APPCLM] Append column


Inserts one blank column at right of cursor position. Diagram
elements on right of horizontal cursor position will be shifted to
right by one column. And if necessary, net will be expanded to
right.

[APPCLM]

Action of appending column


12.[<] Exit editor screen
Analyzes current editing net, and store it into the ladder program.
If some error is found in the net, it still remains Net Editor screen,
and an error message will be displayed. According to a kind of
error, cursor may indicate where the error is detected.
(b) Operations using other keys
1. Cursor move keys, Page change keys
Cursor move keys and Page change keys move cursor on screen.
Net Editor screen expands image of net horizontally for a wider net
according to its width, while Ladder Diagram Monitor/Editor
screen folds nets wider than screen width. When net width is
expanded over screen width, attempt to move cursor out of screen
will scroll net image to the direction. The net of maximum size
occupies area of 1024 elements, but actually available area may be
little less for internal use according to the internal condition:
element means the space that is occupied by single relay.
2. bit address + INPUT key
Changes bit address of relay under cursor.
3. number / byte address + INPUT key
Changes parameter of functional instructions under cursor.

851
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.6 Valid net must have following structure:


STRUCTURE OF
VALID NET Convergence point

Input section Output


section

Structure of valid net


Input section consists of contacts and functional instruction, and the
result of operations of input section is led to Convergence point. After
the convergence point, there is Output section that consists of coils
only. The Convergence point is the nearest point to right power line,
where all connections join with each other to gather into single
connection.

Input section Convergence point Output section

Sample of valid net


Input section consists at least one relay or functional instruction, however,
output section may contain nothing.

Example of net with no output section


Valid net is also restricted in following rules:
Only one function instruction is available for a net.
Functional instruction can be placed only at last (rightmost) of input
section.
Only coils can be contained in output section.

852
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

5.7 Pressing [FUNC] soft key at Net Editor screen reaches Functional
Instruction List screen at which you choose a functional instruction to be
FUNCTIONAL entered from list of all available functional instructions.
INSTRUCTION LIST
SCREEN

Fig. 5.7 Functional Instruction List screen


Operations at this screen are below:
(a) Operations using the soft keys
1. [SELECT] Select a functional instruction
Selects a functional instruction. The function instruction under
cursor at that time is chosen, and entered into the editing net.
2. [NUMBER], [NAME] Rearrange functional instructions list
Rearrange functional instructions list in two ways. [NUMBER]
soft key arranges the list in numerical order with their identifying
numbers, on the other hand, [NAME] soft key arrange it in
alphabetical order with their names. At beginning, the list is
arranged in alphabetical order.
3. [<] Quit selecting
Quits selecting functional instruction, and return to Net Editor
screen.

853
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.8 At Functional Instruction Data Table Editor screen, you can edit the
contents of data table that belongs to some functional instructions. To
FUNCTIONAL reach this screen, at Net Editor screen, press [TABLE] soft key that is
INSTRUCTION DATA displayed when the cursor is on the following functional instructions
TABLE EDITOR which have a data table.
SCREEN Functional Instruction COD (SUB7)
Functional Instruction CODB (SUB27)
(Function instruction DISP(SUB49) is not be able to use)
Following edit operations are available at this screen.
Change the data table value. number + ENTER key
Change the data length. [BYTE], [WORD], [D.WORD]
(These soft keys can be operated only at Functional Instruction Data
Table Editor screen of Functional Instruction CODB.)
Change the number of data [COUNT]
Initialize all of data [INIT]

Fig. 5.8 Functional Instruction Data Table Editor screen

854
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

5.9 At Program List Editor screen you can create new program and delete a
program in addition to the function of Program List Viewer screen. To
PROGRAM LIST reach this screen, press [LIST] soft key at Ladder Diagram Editor screen.
EDITOR SCREEN Following operations are available at Program List Editor screen. For
more detail of these operations, refer to the descriptions of each key to
operate.
Create new program [NEW]
Delete a program [DELETE]

Fig. 5.9(a) Program List Editor screen (Detail)


You can select Detail viewer format or Brief viewer format on Program
List Editor screen. The default viewer format is Detail viewer format.

Fig. 5.9(b) Program List Editor screen (Brief)

855
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.9.1
Screen Operations Display the contents of program Screen Settings Delete a program

Search for program Add new program

Fig. 5.9.1 Soft keys of Program List Editor screen


(a) Operations using the soft keys
1. [ZOOM] Display the contents of program
Goes to Ladder Diagram Editor screen.
2. [SEARCH] Search for program
Searches for a program. Pressing [SEARCH] soft key after
entering a program name or symbol name searches for program
corresponding to the input character string and moves the cursor to
the program.
3. [SETING] Screen settings
Calling the screen for setting of Program List Editor screen. You
can change various settings for Program List Editor screen. To
return to Program List Editor screen, press the return key [<].
4. [NEW] Create new program
If you entered program name or symbol and press [NEW] soft key,
the program will be checked its existence. If such program is not
found, new program will be created. The created program is
inserted automatically into the program list and the cursor points
it. The following ladder nets are created automatically according
to the type of created program by this operation.
LEVEL1 : Functional instruction END1
LEVEL2 : Functional instruction END2
LEVEL3 : Functional instruction END3
Subprogram : Functional instruction SP, SPE
If the status of protection of the program is enabled to edit, this
operation is available.
5. [DELETE] Delete a program
Deletes a program. If you entered no strings and press [DELETE]
soft key, the program under the cursor is deleted. If you entered
program name or symbol and press [DELETE] soft key, the
program will be checked its existence, and will be deleted if such
program is found.
But, GLOBAL, LEVEL1 and LEVEL2 should always exist on
program list. If you delete these programs, the contents of program
are abandoned. But these programs do not disappear on program
list. If the status of protection of the program is enabled to edit, this
operation is available.

856
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

5.9.2
Setting Screen

Fig. 5.9.2 Program List Editor (Setting) screen


(a) Settings
There are the following settings on Program List Editor (Setting)
screen:
VIEW FORMAT Default : DETAIL
Specifies whether to display Program List Editor screen in
DETAIL or BRIEF mode.
ADDRESS NOTATION Default : ADDRESS
Specifies whether to display each subprogram on Program List
Editor screen with the address or symbol.
SORT BY Default : PROGRAM NUMBER
Specifies whether to display each subprograms on Program List
Editor screen in order of program numbers or symbols. When
ADDRESS NOTATION is SYMBOL, programs without symbols
are displayed in order of program number after programs with the
symbols. GLOBAL, LEVEL1, LEVEL2, LEVEL3 are out of
target of sort.
PROTECTED PROGRAM Default : SHOW
Specifies whether to display protected programs. The protected
program for this setting means programs which cannot be edited on
Program List Editor screen.
FRAME NET IN SUBPROGRAM MODE Default : SHOW
Frame net means functional instruction END1, 2 and 3 on
LEVEL1, 2, 3, and functional instruction SP and SPE on
subprogram. This setting specifies whether to display these frame
nets when the contents of a program are displayed by pressing
[ZOOM] soft key on Program List Editor screen.

857
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

5.10
ALARM MESSAGE
AND
COUNTERMEASURE
Messages that may be displayed during PMC program editing
Alarm number Faulty location/corrective action Contents

OVERLAPPED COM If COME is missing, add it in proper There is no COME that corresponds to
position. If the COM is unnecessary, this COM.
remove it.

END IN COM If COME is missing, add it in proper END,END1,END2, or END3 is found


END1 IN COM position. If COM is unnecessary, re- between COM and COME.
END2 IN COM move it.

JMPE IN COM JMPE and corresponding JMP must JMPE is found between COM and
have same COM/COME status. Re- COME, and JMP and corresponding
view JMP range and COM range, to JMPE have different COM/COME sta-
adjust not to overlap with each other: it tus.
is possible that one range includes the
other completely.

SP/SPE IN COM If COME is missing, add it in proper SP or SPE is found between COM and
position. If the COM is unnecessary, COME.
remove it.

COME WITHOUT COM If COM is missing, add it in proper There is no COM that corresponds to
position. If the COME is unnecessary, this COME.
remove it.

DUPLICATE CTR NUMBER If some of them are unnecessary, re- Plural CTRs have the same number as
(WARNING) move them. If all of them are neces- their parameter. (This is warning.)
sary, assign other number to parame-
ter of them to make them unique. (If
two or more instructions with same pa-
rameter number will never be active
simultaneously at one time, the Ladder
program has a possibility to work cor-
rectly, however, it is recommended
from safety and maintenance points of
view, that all these instructions should
have different parameter number with
each other.)

ILLEGAL CTR NUMBER If unnecessary, remove it. Assign cor- CTR has parameter number that is out
rect number not to exceed the maxi- of range.
mum number defined by each PMC
model.

858
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

Alarm number Faulty location/corrective action Contents

DUPLICATE DIFU/DIFD NUMBER If some of them are unnecessary, re- Plural DIFUs or DIFDs have the same
(WARNING) move them. If all of them are neces- number as their parameter. (This is
sary, assign other number to parame- warning.)
ter of them to make them unique. (If
two or more instructions with same pa-
rameter number will never be active
simultaneously at one time, the Ladder
program has a possibility to work cor-
rectly, however, it is recommended
from safety and maintenance points of
view, that all these instructions should
have different parameter number with
each other.)

ILLEGAL DIFU/DIFD NUMBER If unnecessary, remove it. Assign cor- DIFU or DIFD has parameter number
rect number not to exceed the maxi- that is out of range.
mum number defined by each PMC
model.

NO END Add END, END1, END2 or END3 in END, END1, END2 or END3 is not
NO END1 proper position. found.
NO END2
NO END3

DUPLICATE END1 Remove extra END1, END2 or END3. Multiple END1, END2 or END3 are
DUPLICATE END2 found.
DUPLICATE END3

GARBAGE AFTER END Remove unnecessary nets, and move There are some nets after END, END2
GARBAGE AFTER END2 necessary nets to proper position so or END3, which will not be executed.
GARBAGE AFTER END3 that they will be executed.

OVERLAPPED JMP If JMPE is missing, add it in proper There is no JMPE that corresponds to
position. If the JMP is unnecessary, this JMP.
remove it.

JMP/JMPE TO BAD COM LEVEL JMP and corresponding JMPE must JMP and corresponding JMPE have
have same COM/COME status. Re- different COM/COME status.
view JMP range and COM range, to
adjust not to overlap with each other: it
is possible that one range includes the
other completely.

COME IN JMP COME and corresponding COM must COME is found between JMP and
have same JMP/JMPE status. Review JMPE, and COM and corresponding
COM range and JMP range, to adjust COME have different JMP/JMPE sta-
not to overlap with each other: it is tus.
possible that one range includes the
other completely.

END IN JMP If JMPE is missing, add it in proper END,END1,END2, or END3 is found


END1 IN JMP position. If JMP is unnecessary, re- between JMP and JMPE.
END2 IN JMP move it.
END3 IN JMP

SP/SPE IN JMP If JMPE is missing, add it in proper SP or SPE is found between JMP and
position. If the JMP is unnecessary, JMPE.
remove it.

859
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Alarm number Faulty location/corrective action Contents

JMPB OVER COM BORDER JMPB and its destination must have JMPB and its destination differ in
same COM/COME status. Review COM/COME status.
range of JMPB and COM range, to ad-
just not to overlap with each other: it is
possible that one range includes the
other completely.

JMPB OVER LEVEL JMPB can only jump to the same pro- JMPB jumps to different program level.
gram level, or within a subprogram. If
the JMPB is unnecessary, remove it. If
LBL for the JMPB is missing, add it in
proper position. If it should be JMPC,
correct it.

LBL FOR JMPB NOT FOUND If JMPB is unnecessary, remove it. If Can not find proper LBL for JMPB.
LBL is missing, add it in proper posi-
tion.

JMPC IN BAD LEVEL JMPC is used to jump from a subpro- JMPC is used in other than subpro-
gram to level 2. If the JMPC is unnec- gram.
essary, remove it. If it should be JMPB
or JMP, correct it.

LBL FOR JMPC NOT FOUND If JMPC is unnecessary, remove it. If Can not find proper LBL for JMPC.
LBL is missing, add it in proper posi-
tion: JMPC jumps into level 2. If it
should be JMPB or JMP, correct it.

LBL FOR JMPC IN BAD LEVEL JMPC is used to jump from a subpro- Destination of JMPC is not level 2.
gram to level 2. If the JMPC is unnec-
essary, remove it. If another LBL of
same Laddress that the JMPC is in-
tended to jump exists in the subpro-
gram, assign different Laddress to
these two LBLs. If it should be JMPB
or JMP, correct it.

JMPC INTO COM LBL for JMPC must be located out of JMPC jumps to LBL between COM
any COM and COME pair. If the JMPC and COME.
is unnecessary, remove it. If the LBL is
located wrong, move it to correct posi-
tion. If the Laddress of JMPC is
wrong, correct it.

JMPE WITHOUT JMP If JMP is missing, add it in proper posi- There is no JMP that corresponds to
tion. If the JMPE is unnecessary, re- this JMPE.
move it.

TOO MANY LBL Remove unnecessary LBLs. If this er- There are too many LBLs.
ror still occurs, adjust the construction
of program to use less LBLs.

DUPLICATE LBL If some of these LBLs are unneces- Same Laddress is used in plural
sary, remove them. If all of these LBLs LBLs.
is necessary, assign other Laddress-
es to them to make all LBLs unique.

OVERLAPPED SP If SP is missing, add it in proper posi- There is no SP that corresponds to


tion. If the SPE is unnecessary, re- this SPE.
move it.

860
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

Alarm number Faulty location/corrective action Contents

SPE WITHOUT SP If SP is missing, add it in proper posi- There is no SP that corresponds to


tion. If the SPE is unnecessary, re- this SPE.
move it.

END IN SP If SPE is missing, add it in proper posi- END is found between SP and SPE.
tion. If END is in wrong place, move it
to proper position.

DUPLICATE P ADDRESS If some of these SPs are unnecessary, Same Paddress is used in plural
remove them. If all of these SPs is SPs.
necessary, assign other Paddresses
to them to make all SPs unique.

DUPLICATE TMRB NUMBER If some of them are unnecessary, re- Plural TMRBs have the same number
(WARNING) move them. If all of them are neces- as their parameter. (This is warning.)
sary, assign other number to parame-
ter of them to make them unique. (If
two or more instructions with same pa-
rameter number will never be active
simultaneously at one time, the Ladder
program has a possibility to work cor-
rectly, however, it is recommended
from safety and maintenance points of
view, that all these instructions should
have different parameter number with
each other.)

ILLEGAL TMRB NUMBER If unnecessary, remove it. Assign cor- TMRB has parameter number that is
rect number not to exceed the maxi- out of range.
mum number defined by each PMC
model

DUPLICATE TMR NUMBER If some of them are unnecessary, re- Plural TMRs have the same number
(WARNING) move them. If all of them are neces- as their parameter. (This is warning.)
sary, assign other number to parame-
ter of them to make them unique. (If
two or more instructions with same pa-
rameter number will never be active
simultaneously at one time, the Ladder
program has a possibility to work cor-
rectly, however, it is recommended
from safety and maintenance points of
view, that all these instructions should
have different parameter number with
each other.)

ILLEGAL TMR NUMBER If unnecessary, remove it. Assign cor- TMR has parameter number that is out
rect number not to exceed the maxi- of range.
mum number defined by each PMC
model.

NO SUCH SUBPROGRAM If it calls wrong subprogram, correct it. Subprogram that is called by CALL/
If the subprogram is missing, create it. CALLU is not found.

UNAVAILABLE INSTRUCTION Confirm that this ladder program is cor- Unsupported instruction for this PMC
rect one. If this program is correct one, model is found.
all these unsupported instructions
have to be removed.

SP IN BAD LEVEL SP can be used at top of a subpro- SP is found in wrong place.


gram. Correct it so that no SP exists in
other place.

861
5. LADDER DIAGRAM EDITOR
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Alarm number Faulty location/corrective action Contents

LADDER PROGRAM IS BROKEN This ladder program must be all Ladder program may be broken by
cleared once, and remake ladder pro- some reason.
gram.

NO WRITE COIL Add proper write coil. Write coil is necessary, but is not
found.

CALL/CALLU IN BAD LEVEL CALL/CALLU must be used in Level 2 CALL/CALLU is used in wrong place.
or in subprograms. Do not use any
other places.

SP IN LEVEL3 If END3 is located wrong, move it to SP is found in level 3.


correct position. If the SP is unneces-
sary, remove it.

Messages that may be displayed during net editing on PMC program editor screen
Alarm number Faulty location/corrective action Contents

TOO MANY FUNCTIONAL Only one functional instruction is al- Too many functional instructions are in
INSTRUCTIONS IN ONE NET lowed to constitute a net. If necessary, one net.
divide the net into plural nets.

TOO LARGE NET Divide the net into plural nets so that Net is too large. When a net is con-
step number in a net may become verted into the object, the net exceeds
small. 256 steps.

NO INPUT FOR OPERATION Coil without input, or coil connected to No signal is provided for logical opera-
output of functional instruction that has tion.
no output, causes this error. If coil is
not necessary, remove it. If necessary,
connect it to meaningful input.

OPERATION AFTER FUNCTION IS Output of functional instruction can not No logical operation with functional
FORBIDDEN be connected to a contact, nor to con- instruction output is permitted, except
junction with other signal that will be write coils.
implemented by logicalor operation.

WRITE COIL IS EXPECTED Add proper write coil to the net. Write coil is expected, but not found.

BAD COIL LOCATION Coil can be located only at rightmost Coil is located in bad position.
column. Any coil located at other place
must be erased once, and place nec-
essary coils in correct place.

SHORT CIRCUIT Find contact with terminals connected Some contacts are connected with
by short circuit, and correct connec- short circuit.
tions.

FUNCTION AFTER DIVERGENCE IS Functional instruction can not be used Functional instruction is used in output
FORBIDDEN in output section of net. If necessary, section of net.
divide the net into plural nets.

ALL COIL MUST HAVE SAME INPUT Left terminals of all coils in a net must When a net contains more than one
be connected to same input point. coil, the coils should not have any con-
tact beside them affects only of the
coils.

862
5. LADDER DIAGRAM EDITOR
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

Alarm number Faulty location/corrective action Contents

BAD CONDITION INPUT Check the connection of all condition Some condition input of functional
inputs of the functional instruction. Es- instruction is not connected correctly.
pecially for functional instruction that
has more than one condition input,
check if connections to condition in-
puts interfere with each other.

NO CONNECTION Find gap that is expected to be con- There is signal connected to nowhere.
nected, and correct the connection.

NET IS TOO COMPLICATED Examine every connection, and find Net is too complicated to analyze.
unnecessarily bending connection, or
coils that are connected to different
point.

PARAMETER IS NOT SUPPLIED Enter all of the relay addresses, and Relay with blank address, or blank pa-
parameters of functional instructions. rameter of functional instruction, is
found.

863
6. SIGNAL TRACE
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

6 SIGNAL TRACE FUNCTION (PMCSB7)

he signal trace function for PMCSB7 has both the signal wave form
display function and the signal trace function for PMCSA5/SB5/SB6
and has improved specification and operation.
PMCSA5/SB5/SB6 PMCSB7

Used condition The signal wave form display function Basic function as PMC control soft-
is provided in the ladder editing card. ware

Trace points 16 points 32 points

Sampling resolution 8ms (Fixed) 8ms to 1sec (Variable)

Maximum sampling time 10sec. (Fixed) Sampling time is expanded according


to number of trace points and resolu-
tion.
Ex.)
98sec. when 16 points and 8ms reso-
lution (Variable)
100 minutes when 32 points and 1
sec. resolution.

Display of trace result Sampling graph does not be displayed Sampling graph is displayed dynami-
dynamically in signal wave form dis- cally during the execution of trace.
play function.

On/off status of each bit is displayed in


signal trace function

On the trace screen, you can trace specified signals. The result of the trace
is displayed as the time chart of signals. There are two tracing modes.
Time Cycle mode: Samples the state of the signals at every
specified cycle time.
(Same specification as the signal wave
form display for PMCSA5/SB5/SB6)
Signal Transition mode: Samples the status of the signals when
the signals that are watched at every
specified time are changed.
(Same specification as the trace function
for PMCSA5/SB5/SB6)

864
6. SIGNAL TRACE
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

6.1 Pushing the [TRACE] soft key on PMC Diagnosis screen displays the
Signal Trace screen.
SIGNAL TRACE
SCREEN (INITIAL
SCREEN)

Signal Trace screen (Initial screen)

865
6. SIGNAL TRACE
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

6.2 Pushing the [SETING] soft key on the Signal Trace screen displays the
Parameter Setting screen. Parameter Setting has two screens. The
SETTING OF TRACE page key changes these screens.
PARAMETER

Setting screen of Trace Parameter (Page 1)


a) SAMPLING/ MODE
Determines the sampling mode.
TIME CYCLE: Samples at every specified cycle time.
SIGNAL TRANSITION: Samples when the signal changes.
b) SAMPLING/ RESOLUTION
The resolution of sampling is inputted. The default value is the
minimum resolution (8msec). The range of the value is from 8msec to
1000msec. Inputted value is rounded down to the multiple of 8msec.
c) SAMPLING/ TIME
This parameter is displayed when TIME CYCLE is set on
SAMPLING MODE. The execution time of trace is inputted. The
value of SAMPLING RESOLUTION or the number of specified
signal address changes the range of the value that is able to input. The
range is displayed on the right side.
d) SAMPLING/ FRAME
This parameter is displayed when SIGNAL TRANSITION is set on
SAMPLING MODE. The number of sampling is inputted. The value
of SAMPLING RESOLUTION or the number of specified signal
addresses changes the range of the value that is able to input. The range
is displayed on the right side.
e) STOP CONDITION
Determines the condition to stop the trace.
NONE: Does not stop the tracing automatically.
BUFFER FULL: Stops the tracing when the buffer becomes full.
TRIGGER: Stops the tracing by trigger.
f) STOP CONDITION/ TRIGGER/ ADDRESS
When TRIGGER is set on STOP CONDITION, this parameter is
enabled. Input signal address or symbol name as stop trigger.

866
6. SIGNAL TRACE
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

g) STOP CONDITION/ TRIGGER/ MODE


When TRIGGER is set on STOP CONDITION, this parameter is
enabled. Determine the trigger mode when the trace is stopped.
RISING EDGE: Stops the tracing automatically by rising up of
the trigger signal.
FALLING EDGE: Stops the tracing automatically by falling
down of the trigger signal.
BOTH EDGE: Stops the tracing automatically by rising up or
falling down of the trigger signal.
h) STOP CONDITION/ TRIGGER/ POSITION
When TRIGGER is set on STOP CONDITION, this parameter is
enabled. Input the ratio of the sampling time or number which
specifies the position where specified trigger condition is on. If you
would like to examine the transitions of the signal before the trigger
condition, you should set a big value in this parameter. If you would
like to examine the transitions of the signal after the trigger condition,
you should set a small value in this parameter.
Example: The case that sampling time is 10 second and trigger
position is set as 10%.
Trigger position

1sec 9sec

1 0 9 (SEC)

i) SAMPLING CONDITION
When SIGNAL TRANSITION is set on TRACE MODE, this
parameter is enabled. Determine the sampling condition.
TRIGGER: Samples the status of specified signals when
the specified sampling condition is on.
ANY CHANGE: Samples the status of specified signals when
the signals change.
j) SAMPLING CONDITION/ TRIGGER/ ADDRESS
When SIGNAL TRANSITION is set on TRACE MODE, and
TRIGGER is set on SAMPLING CONDITION, this parameter is
enabled. Input signal address or symbol name as sampling trigger.
k) SAMPLING CONDITION/ TRIGGER/ MODE
When SIGNAL TRANSITION is set on TRACE MODE, and
TRIGGER is set on SAMPLING CONDITION, this parameter is
enabled. Input trigger mode that determines the condition of specified
trigger.
RISING EDGE: Samples the status of specified signals by
rising up of the trigger signal.
FALLING EDGE: Samples the status of specified signals by
falling down of the trigger signal.
BOTH EDGE: Samples the status of specified signals by
rising up or falling down of the trigger signal.
ON: Samples the status of specified signals during
the trigger signal is on.
OFF: Samples the status of specified signals during
the trigger signal is off.

867
6. SIGNAL TRACE
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

6.3 a) Setting addresses


In page 2 of Parameter Setting screen, you can set the addresses or
SETTING OF symbols that should be sampled.
SAMPLING
ADDRESS

Setting screen of Trace Parameter (Page 2)


In case of inputting discrete bit addresses, any bit address can be inputted.
Moreover, when you input byte address, all bits of the address (bit0bit7)
are set automatically. Maximum 32 points of signal address can be
inputted.

NOTE
Increasing the number of the signal address changes the
capacity of
SAMPLING TIME or SAMPLING FRAME in page 1. If the
capacity
is changed, the following warning message is displayed.
(The n on the message means the maximum value that is
able to input.)
a) In case of TIME CYCLE mode
SAMPLING TIME IS REDUCED TO n SEC.
b) In case of SIGNAL TRANSITION mode

b) Soft keys
Soft keys on the Setting screen of sampling address are as follows
DELETE: Clears the value of the edit box on the cursor.
SYMBOL: Changes the address display to the symbol display.
However, display of the address that is not defined the
symbol does not change. This soft key also changes
to ADDRESS. The following soft keys are
displayed.
MV.UP: Exchanges the signal indicated the cursor for the
signal above one line.

868
6. SIGNAL TRACE
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

MV.DWN: Exchanges the signal indicated the cursor for the


signal below one line.
DELALL: Clears all of the value of the edit box.
c) Trigger setting
When SIGNAL TRANSITION is set on TRACE MODE and
ANY CHANGE is set on SAMPLING CONDITION, it can be set
whether to use the setting address as the signals that should trigger the
sampling in the setting signals. As for the signal address where the
trigger was set, F is displayed right. Soft keys on the Trigger setting
screen are as follows
TRGON: Sets the Trigger on.
TRGOFF: Sets the Trigger off.
The default setting is trigger on for all signals.

869
6. SIGNAL TRACE
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

6.4 On trace screen, pushing [START] soft key starts the execution of trace
after you set the trace parameter correctly. The followings are the screen
EXECUTION OF examples of the trace execution by TIME CYCLE mode and SIGNAL
TRACE TRANSITION mode

Execution of Trace screen (TIME CYCLE mode)

Execution of Trace screen (SIGNAL TRANSITION mode)


The result of trace is immediately displayed during execution of the trace.
When the stop conditions that is set in parameter setting screen is satisfied
the execution is finished. Pushing [STOP] soft key aborts the execution.
In SIGNAL TRANSITION mode, graphic display is not refreshed until
any signal for sampling trigger changes.

870
6. SIGNAL TRACE
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

6.5 When the execution is finished, the result of trace is displayed. The
followings are the screen examples of trace by TIME CYCLE and
OPERATION AFTER SIGNAL TRANSITION mode.
EXECUTION OF
TRACE

Result of Trace screen (TIME CYCLE mode)

Result of Trace screen (SIGNAL TRANSITION mode)


The cursor indicating current position is initially displayed on the original
point (0 point). The position of the cursor is displayed in CURSOR
POSITION in the upper of the screen. The cursor can move horizontally.
After the execution, following operation is enabled.
a) Scroll of screen
Cursor up/down key and Page up/down key
Enables the vertical scroll for the specified signal
Cursor right/left key, [NEXT>>] soft key and [PREV<<] soft key
Enables the horizontal scroll of the graph.

871
6. SIGNAL TRACE
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

b) Automatic calculation of the selected range


Pushing [MARK] soft key marks the current position and displays the
mark cursor. If the mark cursor duplicates with the current position
cursor, the current position cursor has priority of display. The MARK
POSITION that shows the position of the mark cursor and RANGE
that shows the range between the mark cursor and the current position
cursor are displayed in the upper of screen. Moving the current
position cursor changes these values. Pushing [MARK] again releases
the select range mode.

Result of Trace screen (Mark cursor display)


c) Zoom in/Zoom out of waveform
Pushing [Z.IN] soft key magnifies the display of chart. Pushing
[Z.OUT] soft key reduces the display of chart. Pushing these soft keys
also change the scale value of the graduation on the graph. When trace
is just finished, the default zooming level was the most magnified
level. In [Z.OUT] mode, X is displayed as following screen example
when the transitions of signal cannot be expressed accurately enough.
The limitation of [Z.OUT] displays all of result of the trace in one
page.

872
6. SIGNAL TRACE
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION FUNCTION (PMCSB7)

Result of Trace screen (Zoom out display)


d) Exchange of sampling signal
Pushing [MV.UP] soft key exchanges the signal indicated by the signal
cursor for the signal one line above. Pushing [MV.DWN] soft key
exchanges the signal indicated by the signal cursor for the signal one
line below. The result of the operation is cancelled by the execution of
trace or putting the power off. When you would like to preserve the
order of displayed signals against the executing or powering off,
please change the order on SAMPLING ADDRESS screen.

873
6. SIGNAL TRACE
FUNCTION (PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

6.6 Trace execution is automatically started after poweron by setting a PMC


parameter.
AUTOMATIC START
OF TRACE SETTING
#7 #6 #5 #4 #3 #2 #1 #0
K906

#5 0 : Starts trace execution when soft key [EXEC] is pressed.


1 : Automatically starts trace execution after poweron
This PMC parameter is set by the following item on the Setting screen of
PMC Parameter.
SIGNAL TRACE START = 0 (0: MANUAL 1: AUTO)

874
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION (PMCSB7)

7 SELECTABLE I/O LINK ASSIGNMENT FUNCTION


(PMCSB7)

875
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
(PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

7.1 This function enables the common use of a sequence program for several
machines which have different I/O device configuration with each other,
OUTLINE by setting the parameter to enable/disable each group in I/O link
assignment data.

Machine A Machine B
I/O devices I/O devices

CNC Power Connection CNC Power I/O


Mate Unit Mate Unit

I/O link assignment data I/O link assignment data


X0 0.0.1 FS08A (Power Mate) X0 0.0.1 FS08A (Power Mate)
X8 1.0.1 OC02I (Connection Unit) X24 1.0.1 I D32E (I/O Unit)

The I/O link assignment data of both the machine


A and the machine B are merged.
Off line programmer
I/O link assignment data
X0 0.0.1 FS08A (Power Mate)
X8 1.0.1 OC02I (Connection Unit)


X24 2.0.1 ID32E (I/O Unit)


Make ROM format file with I/O link assignment data that is used in both the machine A



and the machine B.


CNC
A sequence program issentto CNC.

Set effective I/O groups on parameter.

Power Mate Enable Power Mate Enable


Connection Unit Enable Connection Unit Disable
I/O Unit Disable I/O Unit Enable

Machine A : I/O devices Machine B : I/O devices

CNC Power Connection CNC Power I/O


Mate Unit Mate Unit

876
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION (PMCSB7)

The I/O devices that are used in all machines can be set as basic part of
configuration that is always effective.

Basic part

Machine A : I/O devices Machine B : I/O devices

CNC Power Connection CNC Power I/O


Mate Unit Mate Unit

The I/O link assignment data of the machine A and


the machine Bare merged.


Off line programmer


I/O link assignment data


X0 0.0.1 FS08A (Power Mate) Basic part (always connected)


X8 1.0.1 OC02I (Connection Unit) Optional group by parameter



X24 2.0.1 ID32E (I/O Unit) Optional group by parameter


Determine the basic part and the optional part of I/O link assignment data.




CNC

Set effective I/O group on parameter.


The sequence program issent to CNC

Power Mate Basic Power Mate Basic


Connection Unit Enable Connection Unit Disable
I/O Unit Disable I/O Unit Enable

Machine A : I/O devices Machine B : I/O devices

CNC Power Connection CNC Power I/O


Mate Unit Mate Unit

NOTE
When you set a basic part, you have to assign devices of
basic part continuously from group 0. And the basic part is
connected with the top of the link.

877
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
(PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Basic part Optional part

CNC Power Connection I/O OK


Mate Unit Unit

CNC Power Connection I/O NG


Mate Unit Unit

Optional part
Basic part

This function requires setting the following parameters. These parameters


can be set for each channel. See V8 and V2.4 for details.

1) ENABLE SELECTION:
Enables/Disables this function in the system parameter.
2) BASIC GROUP COUNT:
Sets the counts of group in basic part in the system parameter.
(This part must be assigned continuously from group 0.) The basic
groups in I/O link assignment data are always effective on all
machine configurations.
3) EFFECTIVE GROUP SELECTION:
Sets the group of optional I/O device that is connected with each
machine in the setting parameter. This parameter doesnt affect the
basic part.

NOTE
I/O Link expansion option is necessary to use channel 2 of
I/O Link.

878
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION (PMCSB7)

7.2 There are three machines which have different configurations of I/O
devices, each other.
EXAMPLE
D Configuration A
A machine which has a distribution I/O machine operators panel and
a connection panel I/O connected with channel 1 of NC.
Channel 1

CNC Distribution I/O machine Connection panel I/O


operators panel
Group 0 Group 1

Channel 2
No connection
D Configuration B
A machine which has a distribution I/O machine operators panel and
a Power Mate connected with channel 1 of NC.
Channel 1

CNC Distribution I/O machine Connection panel I/O


operators panel
Group 0 Group 1

Channel 2
No connection
D Configuration C
A machine which has the configuration A on channel 1 and two beta
amplifiers on channel 2.
Channel 1

CNC Distribution I/O machine Connection panel I/O


operators panel
Group 0 Group 1

Channel 2

CNC Beta amp. Beta amp.

Group 0 Group 1

These machines can use a common sequence program which has I/O link
assignment data that includes all I/O device configurations. The contents
of parameters for each I/O device configuration are as shown in next page.

879
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
(PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

(1) The contents of I/O link assignment data in sequence program


Channel 1

Address Group Base Slot Name I/O Device


X0000 0 0 1 CM12I Distribution I/O machine
operators panel
: : : : : :
X0020 1 0 1 CM03I Connection panel I/O
: : : : : :
X0030 2 0 1 FS08A Power Mate
: : : : : :

Channel 2

Address Group Base Slot Name I/O Device


X0200 0 0 1 OC02I Beta amp.
: : : : : :
X0220 1 0 1 OC02I Beta amp.
: : : : : :

(2) The contents of parameter


D Configuration A
i) System parameter
1CH ENABLE SELECTION = YES
BASIC GROUP COUNT = 1
2CH ENABLE SELECTION = YES
BASIC GROUP COUNT = 0
ii) Setting parameter
Group NO. : 00 01 02 03 04 05 06 07
(CH1) * 1 0 0 0 0 0 0
08 09 10 11 12 13 14 15
0 0 0 0 0 0 0 0
Group NO. : 00 01 02 03 04 05 06 07
(CH2) 0 0 0 0 0 0 0 0
08 09 10 11 12 13 14 15
0 0 0 0 0 0 0 0

880
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION (PMCSB7)

D Configuration B
i) System parameter
1CH ENABLE SELECTION = YES
BASIC GROUP COUNT = 1
2CH ENABLE SELECTION = YES
BASIC GROUP COUNT = 0
ii) Setting parameter
Group NO. : 00 01 02 03 04 05 06 07
(CH1) * 0 1 0 0 0 0 0
08 09 10 11 12 13 14 15
0 0 0 0 0 0 0 0
Group NO. : 00 01 02 03 04 05 06 07
(CH2) 0 0 0 0 0 0 0 0
08 09 10 11 12 13 14 15
0 0 0 0 0 0 0 0
D Configuration C
i) System parameter
1CH ENABLE SELECTION = YES
BASIC GROUP COUNT = 1
2CH ENABLE SELECTION = YES
BASIC GROUP COUNT = 0
ii) Setting parameter
Group NO. : 00 01 02 03 04 05 06 07
(CH1) * 1 0 0 0 0 0 0
08 09 10 11 12 13 14 15
0 0 0 0 0 0 0 0
Group NO. : 00 01 02 03 04 05 06 07
(CH2) 1 1 0 0 0 0 0 0
08 09 10 11 12 13 14 15
0 0 0 0 0 0 0 0
(3) The actual contents of I/O link assignment data modified by the
parameter
D Configuration A
Channel 1

Address Group Base Slot Name I/O Device


X0000 0 0 1 CM12I Distribution I/O machine
operators panel
: : : : : :
X0020 1 0 1 CM03I Connection panel I/O
: : : : : :

Channel 2
No connection

881
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
(PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

D Configuration B
Channel 1

Address Group Base Slot Name I/O Device


X0000 0 0 1 CM12I Distribution I/O machine
operators panel
: : : : : :
X0030 1 0 1 FS08A Power Mate
: : : : : :

Channel 2
No connection

D Configuration C
Channel 1

Address Group Base Slot Name I/O Device


X0000 0 0 1 CM12I Distribution I/O machine
operators panel
: : : : : :
X0020 1 0 1 CM03I Connection panel I/O
: : : : : :

Channel 2

Address Group Base Slot Name I/O Device


X0200 0 0 1 OC02I Beta amp.
: : : : : :
X0220 1 0 1 OC02I Beta amp.
: : : : : :

882
7. SELECTABLE I/O LINK
ASSIGNMENT FUNCTION
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION (PMCSB7)

7.3 1) If PMCparameters are cleared, cycling the power of CNC links only
the basic part.
NOTES
2) After selecting the assignment data, the I/O devices are linked with
shifted group number of effective I/O link assignment data.
You can check the result of connection by 5. I/O Link Connecting
Check Screen.

I/O link assignment data

Before selection After selection

Group 0 Effective Group 0

Group 1 Not effective Group 1

Group 2 Effective Group 2

Group 3 Not effective

Group 4 Effective

3) You can not exchange the order of the I/O group number.

WARNING
1) If a sequence program in which ENABLE SELECTION is
set to YES is executed with the PMC control software that
is not applied to this function, ENABLE SELECTION is
ignored and all I/O link assignment data are effective.
2)The [IOSTRT] key on I/O unit address setting screen has
been removed because improper use of this key may
increase mistake of setting the I/O assignment data which
causes wrong linking of the I/O devices and it may result in
unexpected malfunctions of machine. If you want to have
the machine linked with I/O devices under the selected I/O
link assignment data, you have to turn off and on power after
the confirmation of the correct connection of the I/O devices.
3) If a sequence program in which the system parameter for
this function is set is decompiled and compiled on the
FANUC LADDERIII or Ladder Editing Package that does
not support this function, the system parameter for this
function is initialized and all of I/O link assignment data
becomes effective. Please set the system parameters
again, when writing the sequence program into the CNC.

883
8. SYSTEM PARAMETER
(PMCSB7) FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

8 SYSTEM PARAMETER (PMCSB7)

System parameter screen


(1) ENABLE SELECTION
This parameter enables or disables Selectable I/O link assignment
function.
This parameter is set by softkey [NO] or [YES ].
NO: Dont use Selectable I/O link assignment function.
YES: Use Selectable I/O link assignment function.
The default setting is [NO].
If the parameters of both channel 1 and channel 2 are [NO], the setting
screen for this function explained on 3.22 Setting parameter is not
displayed.

WARNING
According to actually connected I/O devices, please set the
setting parameter(K910K913 described in 3.2.2) correctly
to enable this function.

884
8. SYSTEM PARAMETER
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION (PMCSB7)

(2) BASIC GROUP COUNT


This parameter determines the number of groups in the basic part of
the I/O link assignment data. You can set the group count for basic part
by entering (016) followed by softkey[INPUT]. The default is 0.
Example:
3: basic part 02 group
optional part 315 group

NOTE
For other system parameters, see Chapter 4 in Part III.

885
9. I/O LINK CONNECTING
CHECK SCREEN FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

9 I/O LINK CONNECTING CHECK SCREEN

The I/O Link connecting check screen displays the types and ID codes of
the connected I/O devices for each group. When I/O device is not
connected, any I/O device is not displayed. If there is a problem of input
or output signals for I/O devices, check the connection of I/O Link by
referring to this screen.

Available channel mark

I/O Link Connecting Check Screen


Available channel mark :
If channel is available, an * mark is displayed. The status in this
example screen shows that the channel 2 is not available.

NOTE
1 I/O Link expansion option is necessary to use the channel
2 of I/O Link.
2 For I/O devices and ID codes, sample I/O link
configurations, and an example of the I/O link connecting
check screen, see Subsection 3.8.1 in Part II.

886
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 10. ONLINE FUNCTION

10 ONLINE FUNCTION

There is the following function in the online function of FANUC


LADDERII, FANUC LADDERIII or Ladder Editing Package.
Ladder monitor display
Online ladder editing
PMC parameter display and editing
Signal state monitor display and modifications
Input/output to and from the PMC (loading from the PMC, storing to
the PMC)
Writing to flash ROM
When you use the online function, the setting of communication
condition is necessary in advance.

CAUTION
1 When one of the following screens is displayed at PMC, the
online communication can not be used. Change to other
screens from the following screens, and use the online
function.
[PMCLAD], [I/O], [EDIT], [SYSPRM], [TRACE], [USRDGN],
[DBGLAD], [GDT], [USRMEM]
Also, you can not use the above screens at PMC during the
online communication.
2 When the online function is used with RS232C, the
selected channel is occupied by the PMC system. To use
other input/output functions with RS232C, specify other
channel setting than the one used by online function.
3 Loader control function can not connect with FANUC
LADDERIII or Ladder Editing Package by Ethernet.

887
10. ONLINE FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

10.1
ONLINE SETTING
SCREEN

Fig. 10.1 Online monitor setting screen


Meanings of Soft key
EMG ST: Terminates communication forcibly. Use this key if
communication becomes abnormal and the connection
cannot be terminated normally.
INIT: Initializes the parameters to their default values.

NOTE
1 In case of configuration of CNC with which neither Ethernet
nor HSSB is available, the item of HIGH SPEED I/F is not
displayed.
2 In case of display which has 5+2 soft key, two pages are
used for this setting screen.
Switch the page by < Page Up > or <Page Down> key.

888
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 10. ONLINE FUNCTION

10.2 To communicate with FANUC LADDERII, FANUC LADDERIII or


Ladder Editing Package, you need to put the PMC system in waiting
SETTING OF ONLINE situation of the connection. There are two ways for setting this, setting at
CONNECTION PMC screen and setting in NC parameter. Also, there are three connection
types, for example Ethernet, RS232C or HSSB.

10.2.1 To display the soft key [MONIT] in the PMC main menu screen, set
PROGRAMMER
How to Set at PMC
ENABLE to YES in the setting screen. When pushing the soft key
Screen [MONIT][ONLINE], the online setting screen is displayed. (Fig. 7.1)
1. Case of connection by RS232C (FANUC LADDERII, FANUC
LADDERIII)
(1) Check that NOT USE is selected at the RS232C item.
(2) Set the parameter of CHANNEL and BAUD RATE.
(3) Move the cursor to the RS232C item with Up or Down Cursor
key.
(4) Select USE with Left or Right Cursor key.
2. Case of connection by Ethernet (FANUC LADDERIII, Ladder
Editing Package)
(1) Move the cursor to the HIGH SPEED I/F item with Up or Down
Cursor key.
(2) Select USE with Left or Right Cursor key.
3. Case of connection by HSSB (Ladder Editing Package)
(1) Move the cursor to the HIGH SPEED I/F item with Up or Down
Cursor key.
(2) Select USE with Left or Right Cursor key.

NOTE
1. When both RS232C = USE and HIGH SPEED I/F =
USE are selected, the PMC system will communicate with
the application which is connected at first. If PMC system is
already connecting with an application, it can not connect
with other applications.
2 When you use the online function by Ethernet, the setting
of Ethernet parameters at CNC is necessary in advance.
3 Loader control function can not connect with FANUC
LADDERIII or Ladder Editing Package by Ethernet.

889
10. ONLINE FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

10.2.2 You can enable and disable the online connection for Ethernet, HSSB and
Setting of Online RS232C by NC parameter No.24 without setting on the PMC online
monitor setting screen. This NC parameter is made effective immediately
Connection by NC after setting the parameter.
Parameter If the value of this parameter is changed, the item RS232Cand HIGH
SPEED I/F in the online monitor screen are automatically changed too.
Please refer to following table.
Contents of NC parameter No.24.
Each item of the online monitor
NC parameter screen after setting
Meanings
No.24
RS232C HIGH SPEED I/F
0 The settings on the online monitor setting screen are effec- This does not affect RS232C and
tive. HIGH SPEED I/F.
1 Enables Channel 1 of RS232C and disables HIGH USE (Channel 1) NOT USE
SPEED I/F.
2 Enables Channel 2 of RS232C and disables HIGH USE (Channel 2) NOT USE
SPEED I/F.
10 Disables RS232C and enables HIGH SPEED I/F. NOT USE USE
11 Enables Channel 1 of RS232C and HIGH SPEED I/F. USE (Channel 1) USE
12 Enables Channel 2 of RS232C and HIGH SPEED I/F. USE (Channel 2) USE
3 to 10 3 to 1013 to 254 Reserve (Dont use this setting.) (Reserved) (Reserved)
13 to 254
255 Terminates communication forcibly.It is the same effect as NOT USE NOT USE
soft key [EMG ST].
How to set the parameter
(1) Display the No.24 of NC parameter.
(2) To connect by Ethernet or HSSB, input 10, 11 or 12.
To connect by RS232C, input 1, 2, 11 or 12.

NOTE
1 Even if the setting of the online monitor screen of PMC is
changed, the value of No.24 in NC parameter is not
changed.
2 When you use the ladder editing package on the open CNC
or you use the FANUC LADDERIII to edit the ladder and
do not use the ladder monitor and the ladder editor on CNC
screen, the setting of this parameter should be used

890
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 10. ONLINE FUNCTION

10.3
ONLINE FUNCTION
BY ETHERNET

10.3.1 When you try to connect FANUC LADDERIII or Ladder Editing


Setting of Ethernet Package (Window version) with CNC by Ethernet, it is necessary to set
some Ethernet parameters. The setting of Ethernet parameters can be set
Parameters in the following Ethernet parameter screen of CNC. Please refer to
FANUC Ethernet Board/DATA SERVER Board OPERATORS
MANUAL (B63354EN) about the detail of the setting screen and
setting parameters. The setting item necessary for Ethernet connection for
PMC online function is as follows.
IP ADDRESS (Set the IP address of CNC. 192.168.0.1
etc.)
SUBNET MASK (Set the mask address of the IP address.
255.255.255.0 etc.)
ROUTER IP ADDRESS (If you use the router, set the Router IP
Address.)
PORT NUMBER (TCP) (8193 etc.)

Fig. 10.3.1(a) Ethernet Board

Fig. 10.3.1(b) Embedded Ethernet

891
10. ONLINE FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Fig. 10.3.1(c) Ethernet Card (PCMCIA)

10.3.2 The procedures for online connection with PMC and the offline
Starting online programmer (FANUC LADDERIII, Ladder Editing Package for
windows) by Ethernet are as follows.
communication by (Example: FANUC LADDERIII)
offline programmer
(1) Start up FANUC LADDERIII, and click the [Communication] on
(Ethernet connection) [Tool] menu.

(2) Select the [Network Address] tab and push the <Add Host> button.
Input the IP Address and Port No. inputted by 7.3.1 Setting of
Ethernet parameters.

892
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 10. ONLINE FUNCTION

(3) Select the [Setting] tab, and add the IP Address to Use device.

(4) Push the <Connect> button for start of the communication.

893
10. ONLINE FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Ladder Editing Package can be connected by the same operation too.


Refer to FANUC LADDERIII OPERATORS
MANUAL(B66234EN) as for the detail of operation of FANUC
LADDERIII. Refer to LADDER EDITING PACKAGE (Windows)
OPERATORS MANUAL (B63484EN) as for the detail operation of
Ladder Editing Package.

NOTE
1 When one of the following screens is displayed at PMC, the
online communication can not be used. Change to other
screens from the following screens, and use the online
function.
[PMCLAD], [I/O], [EDIT], [SYSPRM], [TRACE], [USRDGN],
[DBGLAD], [GDT], [USRMEM].
2 When the online function is used with RS232C, the
selected channel is occupied by the PMC system. To use
other input/output functions with RS232C, specify other
channel setting than the one used by online function.
3 Loader control function can not connect with FANUC
LADDERIII or Ladder Editing Package by Ethernet.

894
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 10. ONLINE FUNCTION

10.4 The communication status of RS232C and HIGH SPEED I/F are
displayed at the online monitor screen during the online communication.
COMMUNICATION
STATUS

Fig. 10.4 Online monitor setting screen


USE TIME: The maximum time in the communication processing is displayed.
RS232C: The communication condition of RS232C is displayed.
HIGH SPEED I/F: The communication condition of HIGH SPEED I/F is displayed.
ETHER_BOARD: Displayed during the communication with Ethernet board.The IP address of the commu-
nication partner is displayed.
EMB_ ETHERNET: Displayed during the communication with embedded Ethernet.The IP address of the
communication partner is displayed.
HSSB: Displayed during the communication with HSSB.

895
10. ONLINE FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

The display messages and the meanings are shown in the table of below.
Displayed messages Meanings
INACTIVE The communication is inactive.
STOPPING The communication is being stopped.(Wait for
the termination of communication)
STARTING The communication is being started.(Wait for the
termination of communication over another com-
munication path)
STANDBY The communication is active and in standby
mode.
CONNECTED The communication is active and being con-
nected.
NO OPTION The port can be not opened because there is not
option of RS232C.
BAD PARAMETER Invalid open parameters are specified.
TIMEOUT ERROR A timeout has occurred and communication is
aborted.
TIMEOUT(K) ERROR A timeout has occurred and communication is
aborted.
BCC ERROR A Block Check Code (packet parity) error has
occurred.
PARITY ERROR A parity error has occurred.
OVERRUN ERROR A reception overrun has occurred and the com-
munication can not recover.
SEQUENCE ERROR Packets are out of sequence.(Incorrect proce-
dure)
DATA ERROR Incorrect packets have been received through
retry process.
QUEUE OVERFLOW The transmit/receive queue has overflowed.
DISCONNECTED Communication has been terminated success-
fully.
NO CONNECTION The cable is disconnected.

896
B61863E/14 FS16i/18i/21iB PMCSA1/SB7 MANIPULATION 10. ONLINE FUNCTION

10.5 If any errors have occurred during Ethernet connection, the contents of the
errors are displayed at ETHLOG screen of CNC. Refer to this screen
ABOUT when the communication does not start.
CONNECTION LOG
OF ETHERNET

Fig. 10.5(a) The Log screen of embedded Ethernet

Fig. 10.5(b) The Log screen of Ethernet

897
10. ONLINE FUNCTION FS16i/18i/21iB PMCSA1/SB7 MANIPULATION B61863E/14

Connection Log Meanings and countermeasures


SnpErr:PDU=m,n,[x] date time An error has occurred during the online communication.
m, n : Online communication information that is internal information of a system.
SnpErr:PDU=n,[x] date time
x : Error information
SnpErr:TaskTimeOut[x] date time 6001 PMC does not support the Ethernet.Confirm the Series/Edition of PMC
software.
6003 Unsupported command data was received.Confirm the Series/Edition of
Ethernet board software.
6004 There was an error in command dataConfirm the Series/Edition of Ether-
net board software.
6005 PMC does not receive command data.Confirm the communication status
at the online setting screen of PMC.
6010 PMC does not receive command data.Confirm if HIGH SPEED I/F=USE
is selected and other application is not connected at the online setting
screen of PMC.
6011 Timeout error occurred at PMC.Increase the value of Time Out in [Net-
work Address] of [Communication] menu for FANUC LADDERIII or
Ladder Editing Package.
6012 PMC does not receive command data because it is busy for proces-
sing.Confirm the communication status at the online setting screen of
PMC.
6013 Timeout error occurred at PMCIncrease the value of Time Out in [Net-
work Address] of [Communication] menu for FANUC LADDERIII or
Ladder Editing Package.
6101 PMC received an unsupported function code.Confirm the Series/Edition
of PMC software.
date time: The time when the error occurred.
Ex.) 0323 means March 23rd.
1858 means 6:58 PM.
21161714 means 21st 4:17PM 14 seconds.

898
VI. STEP SEQUENCE
FUNCTION
B61863E/14 STEP SEQUENCE FUNCTION 1. GENERAL

1 GENERAL

901
1. GENERAL STEP SEQUENCE FUNCTION B61863E/14

1.1 The ladder method is most often used for programming the sequence
control governed by a programmable controller. This method, shown in
STEP SEQUENCE Fig.1.1(a) , was derived from relay-panel control circuits. Since it has
METHOD been in use for years, many sequence control engineers are already
familiar with it. This method is also used in PMC sequence
programming.

Fig. 1.1 (a) Ladder method


The greater the number of functions implemented by the PMC for a CNC
system, the larger and the more complicated the sequence program
becomes. A large-scale system requires a larger program and a greater
number of processes, making it hard for the ladder method to control the
overall process. This is because the ladder method does not describe the
order of control. While the ladder method is suitable for describing partial
control, it is hard to apply it to the description of the flow of control
overall.
To overcome this problem, structured programming has been introduced
into sequence control. A PMC that supports the subprogram function
enables the use of modular programs. As shown in Fig.1.1(b), a
large-scale program is divided into subprograms for each function,
simplifying the unit of processing. Since the programmer determines
how to divide the main program into subprograms and the control flow
used to call the subprograms, however, the programs are not necessarily
easy-to-understand by other programmers.

CALL
CALL

Subprogram
Subprogram

Fig. 1.1 (b) Module method

902
B61863E/14 STEP SEQUENCE FUNCTION 1. GENERAL

Given these conditions, a step sequence method has been created to


describe programs structurally. It is well-suited to the control of entire
processes and provides an easy-to-understand visualized flow of the
process. The step sequence programming features the direct
representation of the control flow on a flow chart, as shown in Fig.1.1(c).
Each block of processing is described as a subprogram, using the ladder
method. The entire program is then created by combining these
subprograms.

Step 1

Transition

Step 2

Subprogram of ladder diagram

Drawing flow

Fig. 1.1(c) Step sequence method


The step sequence method has the following features:
(1) Increased programming efficiency
D Since the flow of processes can be programmed directly, simple,
correct programming is enabled, reducing the time required for
programming.
D Even for complicated control, programming proceeds from the main
flow to detailed flow in each process, creating a structured, top-down
program, which is easy-to-understand by persons other than the
original creator.
D Structured modules can be used again easily.
(2) Easy debugging and maintenance
D Graphical display enables the operator to easily understand the
execution state of a program visually.
D Erroneous steps in a program can be found easily.
D A part of a program can be easily modified.
(3) High-speed program
D Since only the subprograms required for a certain process are
executed, the cycle time is reduced.
(4) Transition from ladder programs
D Since steps and transitions consist of conventional ladder programs,
conventional ladder programs can be converted to new step sequence
programs, without discarding ladder-program resources.
In step sequence programming, a sequence control program is divided
into two types of subprograms, steps and transitions. Steps describe
processes. Transitions connect steps and determine whether the transition
conditions from one step to another evaluate true. As shown in Fig.1.1(d),
a step sequence program is described using graphical symbols.

903
1. GENERAL STEP SEQUENCE FUNCTION B61863E/14

[ ] Step A Starts execution. Waits for machining request.


(Process 1)

Transition B Machining request?


When machining is requested
Step C Holds a workpiece on the pallet.
(Process 2)
Transition D Loading completed?
Once loading has been completed
Step E Machines the workpiece. (Process 3)

Transition F Machiningcompleted?
Once machining has been completed
Step G Unloads the workpiece to the pallet.
(Process 4)
Transition H Unloadingcompleted?
Once unloading has been completed
Step I Moves the pallet. (Process 5)

Fig. 1.1 (d) Example of machining the workpiece


As shown in this example, the program flow from process 1 through
process 5 is expressed visually. Detailed programs related to the
movements performed aspart of each process, and the signals used for
determining whether transition conditions for proceeding to the next step
are satisfied, are not described here. To program complicated control
flows, many other functions are supported, such as divergence, jump, and
nesting functions. The details of these functions are described later.
Step sequence programming is suitable for creating programs which
control processes sequentially. Programs used for controlling a unit
which operates according to a certain sequence, such as a loader, ATC, and
other peripheral units, are best suited to step sequence programming. For
programs which control units with no particular sequence, such as that of
the operators panel which is always monitoring the emergency stop
signal or mode signals, however, are not well-suited to step sequence
programming. The PMC supports the advantages of both methods, ladder
and step sequence programming, by calling subprograms written
according to a step sequence and those written as a ladder, from the main
program.

904
B61863E/14 STEP SEQUENCE FUNCTION 1. GENERAL

1.2 This manual uses the graphical symbols listed in Table 1.2 to describe step
sequence flowcharts. Depending on the character font being used, the
GRAPHICAL actually displayed symbols may differ slightly from those listed here.
SYMBOLS These graphical symbols are described in the subsequent chapters.

Table 1.2 List of graphical symbols

Display
Display of FANUC LADDER
Contents programming of
manual CNC Device
Personal
Computer
Step
Sn Sn Sn

Initial
Step [ ] Sn [ ] Sn [ ] Sn

Transition
Pn Pn Pn

Divergence of
Selective
Sequence

Convergence
of
Selective
Sequence

Divergence of
Simultaneous
Sequence

Convergence
of
Simultaneous
Sequence

Jump
Ln > Ln > Ln
Label
Ln < Ln < Ln

Block Step
] Sn ] Sn ] Sn

Initial
Block Step [ ] Sn [ ] Sn
[ ] Sn

End of
Block Step

905
1. GENERAL STEP SEQUENCE FUNCTION B61863E/14

1.3 Follow the procedure below to create a step sequence program. Use a
personal computer on which the FANUC LADDER software package is
PROGRAMMING installed to code (edit) a program. Use a CNC to execute, debug and
correct the ladder subprogram.
(1) Create step sequence program (editing)
(2) Create a subprogram of ladder diagram (editing)
(3) Compile
(4) Transfer to the CNC device (with the memory card or RS232C)
(5) Write to the FlashROM
(6) Execute
(7) Diagnosis and debugging
(8) Correct a subprogram of ladder diagram (editing)

RS232C
Personal CNC device
Computer
PMC- SB4/SB6/
Memory SC4/NB2
card
FANUC LADDER
(5) Write to the FlashROM
software (4) Transfer to the FlashROM
CNC device

(1) Create Step Sequence program (6) Execute


(editing) (7) Diagnosis and debugging
(2) Create a subprogram of ladder (8) Correct a subprogram of ladder diagram (editing)
diagram (editing)
(3) Compile

Fig. 1.3 Programming to create a program


Table1.3 lists the step sequence functions supported by a personal
computer (on which the FANUC LADDER software package is
installed) and CNC.

906
B61863E/14 STEP SEQUENCE FUNCTION 1. GENERAL

Table 1.3 Step sequence functions

: usable
Personal computer
PMC-SB4/
Functions SB6 PMC-SC4 PMC-NB2 FANUC FANUC FANUC
LADDER LADDER II LADDER III
Display and edit of a program
 Display of subprogram list
 Create a new subprogram
 Delete a subprogram
 Edit a subprogram of Step Sequence form
 Edit a subprogram of ladder diagram
 Compile
 Decompile

Input and output


 Input and output with a memory card
 Input and output with RS232C
 Write to a FlashROM

Execution of program
 execution of a ladder diagram
 execution of Step Sequence program

Diagnosis and debugging (note1)


 Diagnosis of Step Sequence program
 Diagnosis of a ladder diagram
 Set and display a monitoring timer

NOTE
While step sequence functions are being used, some of the
diagnosis and debug functions supported by the ladder
method cannot be used. For details, see 6.4 (Support
Functions).

907
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

2 STEP SEQUENCE BASICS

908
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

2.1 A step sequence program is created using a variety of graphical symbols,


as shown in Fig. 2.1 (a). The main terms used in the step sequence are
TERMINOLOGY described below.

(Block)
[ ] S1 (Initial Step)

P100 (Transition)

S2 (Step)

P101 (Transition)

L1 (Label)
S3

(Divergence of Selective Sequence)

(Divergence of
Simultaneous
Sequence)

(Convergence of
Simultaneous
Sequence)

(Convergence of Selective Sequence)

] S10 (Block Step)

L1 (Jump)

Fig. 2.1 (a) Step sequence elements

909
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

(1) Step

Sn
(Pm)

A step indicates a process, which is the basic processing unit in a step


sequence program. In a step, specify the S address (Sn), which is a
step number, and P address (Pm), which indicates a subprogram
(action program) specifying the details of processing in each step.
(2) Step state transition
When a step sequence program is executed, the process proceeds as
program processing advances, the state of each step changs
accordingly. Each step can assume any of the logical states listed in
Table 2.1, its state changes as shown in Fig. 2.1 (b). Activation refers
to the changing of a step from the inactive state to the active state.
Inactivation refers to the changing of a step from the active state to
the inactive state.

Table 2.1 Step state

State Processing Display


Active Execution Activated step.
The action program (subprogram) is being Sn
executed.

Inactive Transition Transition from execution to halt.


to halt The action program (subprogram) is executed
once only, then the step automatically transits to
halt.
Sn
Halt Not activated state.
The action program (subprogram) has not yet
been executed.

Inactivate (halt status)

Activate (active status)

Inactivate (transition to halt)

Fig. 2.1 (b) Step state transition

910
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

(3) Transition

Pn

A transition denotes the transition conditions. When these evaluate


true, the step of the corresponding state changes from the inactive to
active state or vice the reverse. Specify the P address (Pn), which
indicates a subprogram describing the transition conditions in detail.
As shown in Fig. 2.1 (c), step S2 changes its state from inactive to
active when the conditions described in transition P10 evaluate true,
while step S2 changes its state from active to inactive when the
conditions described in transition P20 evaluate true.

Executing step1 Executing step2 Executing step3

S1 (step 1) S1 (step1) S1 (step1)

P10 (Condition P10 P10


is true)
S2 (step2) S2 (step2) S2 (step2)

P20 P20 (Condition P20


is true)

S3 (step3) S3 (step3) S3 (step3)

Fig. 2.1 (c) Transition of step state by the transition


Note that the step immediately before a transition must be active in
order to switch the next step from inactive to active when the
conditions specified in the transition evaluate true. As shown in
Fig. 2.1 (d), step S3 does not change to the active state, even when
transition P20 evaluates true, if step S1 is active and step S2 is
inactive. An active state passes from a certain step to the next step
when the corresponding transition conditions evaluate true, the
execution of the step sequence program advancing one step.

Executing step1 Executing step1

S1 (step1) S1 (step1)

P10 P10

S2 (step2) S2 (step2)

P20 (Condition P20


is true)
S3 (step3) S3 (step3)

Fig. 2.1 (d) Transition of step state by transition

911
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

(4) Initial Step

[ ] Sn
(Pm)

While a normal step can be activated by a transition, the initial step


is activated automatically when execution of the program starts, as
shown in Fig. 2.1 (e).

Stopping program (STOP) Executing program (RUN)

[ ] S1 (step1) [ ] S1 (step1)

P10 P10

S2 (step2) S2 (step2)

P20 P20

S3 (step3) S3 (step3)

Fig. 2.1 (e) Activate of initial step


Although the initial step, which is usually executed first, is often
placed at the top of a program, it can also be specified at some point
within a program. It is always activated first. After being deactivated
once, it can be subsequently be activated again. In this case, it acts
in the same way as a normal step.

912
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

(5) Divergence and Convergence of Selective Sequence


To describe a complicated sequence, selective sequences can be used.
A selective sequence offers multiple choices, from among which the
condition becomes true first activates the corresponding step, as
shown in Fig. 2.1 (f). The divergent paths join to generate the mai
sequence.

S1
(Divergence of selective sequence)
P21 P22 P23
S21 S22 S23

(Convergence of selective sequence)

When transition P21 When transition P22


evaluates true evaluates true

S1 S2

(true) (true)
S21 S22 S23 S21 S22 S23

Fig. 2.1 (f) Selective sequence

913
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

(6) Divergence and Convergence of Simultaneous Sequence


A Simultaneous sequence can be used to execute multiple processes
simultaneously. In a Simultaneous sequence, as shown in Fig. 2.1 (g),
one transition activates multiple steps. The activated multiple steps
are executed independently. Once all steps along the multiple paths
have been completed, the divergent paths join to generate the main
sequence.

S1
P10
(Divergence of
simultaneous
sequence)
S21 S22 S23

S31 S32 S33

(Convergence of
simultaneous
sequence)
S4

When transition P10


evaluates true

S1
P10 (true)

S21 S22 S23

S31 S32 S33

S4

Fig. 2.1(g) Simultaneous sequence

914
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

(7) Jump and Label


The jump function is used to describe a nonserial sequence, such as
a repeated loop. As shown in Fig. 2.1 (h), when a jump designation
is activated, the sequence jumps to the step having the corresponding
jump destination label, after which that step is activated. To specify
a label number, the L address is used in the same way as a jump
instruction in ladder programming. A jump can be made to a previous
or subsequent step.

Executing step3 Executing step1

L1 L1 (Label)
S1 (step1) S1 (step1)

P10 P10

S2 (step2) S2 (step2)

P20 P20

S3 (step3) S3 (step3)

P30 (Condition P30


is true)

L1 (Jump) L1

Fig. 2.1 (h) Jump and Label


(8) Block
A block refers to a group of consecutive steps and transitions. A block
can be a step sequence program. The more complicated the sequence
becomes, the larger and more complex the block is. A program can
be divided into multiple blocks in the same way as for subprograms
in ladder programming, based on the concept of modular
programming. Each block is identified by a P address, which
corresponds to the subprogram number in ladder programming.
A block is executed as the main program in a step sequence, or called
from another step sequence program as a subprogram.

Block (P1) Block (P2)

[ ] [ ]

Fig. 2.1 (i) Block

915
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

(9) Calling block


To execute a block as the main program in a step sequence, call the
block with the CALLU (SUB 66) or CALL (SUB65) instruction in
the same way as for ladder subprogram calling from the second level
ladder program.

Ladder (Second level) Block2 (P2)

[ ]

CALLU P2

CALLU P3

Block3 (P3)

[ ]

Fig. 2.1 (j) Calling block

(10) Block step (calling step sequence program)

] Sn
(Pm)

To call a block from the step sequence program as a subprogram,


specify a block step in the step sequence program which calls the
block, as shown in Fig. 2.1 (k). This is called bloc nesting.

Block (P1) Block (P2)

[ ] S1 [ ] S231

S232
S21 S22 ] S23
(P2) S233

S3

Fig. 2.1 (k) Block nesting

The program shown in Fig. 2.1 (k) is equivalent to in Fig. 2.1 (l).
which does not use a block step.

916
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

Block (P1)

[ ] S1

S21 S22 S231

S232

S233

S3

Fig. 2.1 (l) Program without block step


(11)End of block step

Use an end block step to terminate nestedblockstep calling and to


return to the calling sequence.

917
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

2.2
EXECUTION OF STEP
SEQUENCE
Editing Compile Executing
(source program) (ROM format program)

First level
(Ladder diagram)

END1 (SUB 1) function

Second level
(Ladder diagram) CALL
CALL
END2 (SUB 2) function

Third level
(Ladder diagram)

END3 (SUB 48) function

Subprogram P1
(Ladder diagram)

[ ] Subprogram P2
(Step sequence)

Subprogram P3
(Ladder diagram)

[ ] Subprogram P4
(Step Sequence)

S
S
Subprogram Pn

END (SUB 64) function

Fig. 2.2 (a) Structure of program

918
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

In the step sequence method, a program is created (edited) in units of


subprograms. The edited source program is compiled andconverted to an
executable ROMformat program, thenlinked, as shown in Fig. 2.2 (a).
A ROMformat program is a kind of a modular program, created using
conventional subprograms. A step sequence block is also a type of a
subprogram. Step sequence blocks are linked to the end of the first level
to third level ladder programs, together with other ladder subprograms.
In the same way as in the ladder method, a program is activated at certain
intervals, namely every 8 ms, as shown in Fig. 2.2 (b). The first level and
second level ladders are executed for a certain period (T ms), then the third
level ladder is executed for the remaining time. The period in which the
first level and second level ladders are executed varies with the PMC
model and the setting of the system parameter (LADDER EXEC).
Whether the third level ladder can be used depends on the PMC model.

tn8 tn+0 tn+8 tn+16

8msec 8msec 8msec

T msec T msec T msec

First level

Second level

division division finished

Third level
(depends on
the PMC model)

Fig. 2.2 (b) Execution of program cyclically


After the first level ladder has been executed, the second level ladder i
executed for the remaining time. If the second level ladder cannot be fully
executed within one execution period, it is suspended partway, with the
remainder being executed in the nextperiod. This type of execution is
called divided execution. Where the second level ladder is divided varies
with the execution time of the first level ladder and that of the executed
instructions of the second level ladder. Divided execution is divided into
two types, divided system and undivided system. In the divided system,
the position where the second level ladder is divided is determined in
advance, a divided instruction code being inserted at that position. In the
undivided system, in contrast, where the second level ladder is divided is
not determined in advance, the ladder being automatically divided upon
the determined period elapsing. A PMC which allows step sequence
programming executes the second level ladder in undivided system.

919
2. STEP SEQUENCE BASICS STEP SEQUENCE FUNCTION B61863E/14

In divided execution, the second level ladder is executed at an interval that


is a multiple of 8 ms (e. g., 8, 16, 24 ms). Input signals referenced in the
second level ladder, such as addresses X and F, are refreshed in
synchronization with the execution period for the second level ladder, so
that they do not change during the execution.
All subprograms, created using either the ladder or step sequence method,
are called from the second level ladder. Hence, the execution time of the
second level ladder includes those of ladder subprograms, step sequence
programs (blocks), steps, and transitions. Since only the activated step
and the transition which checks the transition condition from the step to
the next step are executed in a step sequence program, the second level
ladder is executed much more frequently than may be expected from the
total number of steps.

LEVEL1 (Ladder diagram)

LEVEL2 (Ladder diagram)

CALLU P2

R0. 0
CALL P1

LEVEL3 (Ladder diagram)

P1 (Ladder diagram)

P2 (Step sequence)
L1
[ ] S1 (P3)

P4

S2 (P5)

P6
L1

P3 (Ladder diagram)

P4 (Ladder diagram)

Fig. 2.2 (c) Execution of step sequence

920
B61863E/14 STEP SEQUENCE FUNCTION 2. STEP SEQUENCE BASICS

In the step sequence program shown in Fig. 2.2 (c), when step S1 is
activated, subprograms are executed according to the timing illustrated in
Fig. 2.2 (d).

8msec

T msec

First level LEVEL1

Second level LEVEL2

Subprogram
P2 P1

Step
P3 P4

Transition

Third level LEVEL3

Fig. 2.2 (d) Timing of execution of step sequenceprogram


In this case, step sequence program P2, step P3, transition P4, and ladder
subprogram P1 are executed. Step P5 and transition P6 are not executed.

921
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
PROGRAMS STEP SEQUENCE FUNCTION B61863E/14

3 CONFIGURATION AND OPERATION OF


STEPSEQUENCE PROGRAMS

922
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
B61863E/14 STEP SEQUENCE FUNCTION PROGRAMS

3.1 A step is a unit of processing in a program.


STEP [Display]

Sn
(Pm)

[Contents]
D Define a step number (Sn), necessary for controlling execution, and
subprogram number (Pm) specifying actua processing, for a step.
D Assign a step number to a step.
D The same step number cannot be used twice in a program.
D A step has three logical states: the execution, transition to halt, and
halt states. The execution state is also called the active state. The
transition to halt and halt states are collectively called the inactive
state.
Sn.0
State Contents of operation Display
NOTE)
Activate Execution Activated step.
The action program (subprogram) is Sn 1
being executed.

Inactivate Transition to Transition from execution to halt.


halt The action program (subprogram) is
Sn 0
executed once only, then the step
automatically transits to halt.
Stop Not activated state.
The action program (subprogram) 0
has not yet been executed. Sn

NOTE
Refer to VI4.2 PMC ADDRESS (S ADDRESS)

Example) State transition of Step B

Transition A
Inactivate (halt state)

Step B
Transition A

Activate (execution state)


Transition C
Transition C

Inactivate (transition to halt)

(Execute one time)

923
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
PROGRAMS STEP SEQUENCE FUNCTION B61863E/14

[Example]
After the M7 code is decoded, control is transferred to the next step using
a DEC functional instruction.

S1
(P1) Subprogram P1
MF R0.0
DEC F0 f
F7.0
711

P101 Subprogram P101


R0.0
TRSET

924
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
B61863E/14 STEP SEQUENCE FUNCTION PROGRAMS

3.2 An initial step is automatically activated when execution of the program


starts. Once it has been activated, it operates in the same way as a normal
INITIAL STEP step. The program can be returned to this step through other steps.
[Display]

[ ] Sn
(Pm)

[Contents]
D Define a step number (Sn), necessary for controlling execution, and
subprogram number (Pm) specifying the actual processing, for an
initial step.
D All initial steps are activated when the other steps are not activated.
D Each block must contain at least one initial step. No limit is applied
to the number of initial steps contained in a block.
D A block having no initial step cannot be executed if called.
D Assign a step number to an initial step.
D The same step number cannot be used more than once in a program.
D In parallel branch, one initial step is required for each path. (See
example 2.)
[Example1]

L1
[ ] S1 When a program is executed, step P1, specified by
an initial step, is activated first.
P101

S2 Initial step S1 is executed in the same way as normal


step once S1 has been executed.
P102

L1

925
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
PROGRAMS STEP SEQUENCE FUNCTION B61863E/14

Example2

L1
When a program is executed, steps S3 and
S1 S4, specified by an initial step, are activated
first.
P101

Once steps S3 and S4 have been


[ ] S3 executed, initial steps S3 and S4 are
S2
executed in thesame way as normal
step when the program starts from step S1.
P102 P103

[ ] S4 S5

P110

L1

3.3 A transition specifies the conditions governing the transition from the
step to the next step.
TRANSITION
[Display]

Pn

[Contents]
D Only one transition is required between steps.
D Transition between steps is performed as described below.

S1 While S1 is activate, only S1 and P101 are


executed.
Other steps and transition are not executed.
P101 When the transition P102 evaluates true unles S2
is not being executed, the state is ignored.
S2

When the transition P101 evaluates true, control


P102 passes fro S1 to S2. In this case, when the condition
i true, S1 is terminated regardless of the state of S1,
and S2 is activated.

D When a signal is set to 1 in a transition, it remains the state even if


the control is transferred to the subsequentstep. To set the signal to
0, use another subprogram to do so.
[Example]
Refer an example described on the Step function (3.1).

926
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
B61863E/14 STEP SEQUENCE FUNCTION PROGRAMS

3.4 A selective sequence branches to two or more sequences. When the


transition evaluates true, the corresponding step is activated.
DIVERGENCE OF
SELECTIVE [Display]
SEQUENCE

[Contents]
D Transitions are placed after a divergence of selective sequence.
D The step connected to the transition for which the conditions are true
is first activated.
D When the conditions for any transition are true simultaneously, the
leftmost step is activated.
D A selective sequence can create up to 16 paths.
[Example]

[ ] S1
When the conditions for P101 are
satisfied earlier than those of P102,
P100 P101 step S3 is activated.

S2 S3

3.5 It combines two or more divergent paths to the main sequence.


CONVERGENCE OF [Display]
SELECTIVE
SEQUENCE

[Contents]
The number of divergent paths must match that of the convergent
paths.
[Example]

S2 S3 While step S3 is executed, the transition


P103 evaluates true, thus step S4 is
activated.
P102 P103

S4

927
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
PROGRAMS STEP SEQUENCE FUNCTION B61863E/14

3.6 A simultaneous sequence branches to two or more sequences, and all


steps are activated simultaneously.
DIVERGENCE OF
SIMULTANEOUS [Display]
SEQUENCE

[Contents]
D A transition must be placed before a divergence of simultaneous
sequence.
D All branched steps are activated simultaneously, then executed.
D A simultaneous sequence can create up to 16 paths.
[Example]

[ ] S1
When the transition P101 evaluates true,
P101 step S2 and S3 are activated simultaneously.

S2 S3

928
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
B61863E/14 STEP SEQUENCE FUNCTION PROGRAMS

3.7 It combines two or more divergent paths to the main sequence.


CONVERGENCE OF [Display]
SIMULTANEOUS
SEQUENCE

[Contents]
D A convergence of simultaneous sequence is processed as follows.

S10 S20 When the transition P120 evaluates


true, step S10 and S20 are terminated
and step S21 is activated.

P120

S21

D Wait processing is processed as follows.


case1 )

S10 S15 When the transition P109 evaluates true


unless both of step S11 and S16 are active,
control does not pass to step S20.
P110 P115
When the transition P109 evaluates true
while both of S11 and S16 are active, S11
S11 S16 and S16 are terminated and S20 is
activated. In the case, P109 provides the
termination conditions for both S11 and S16.

P109

S20

case2 )

S11 S16 To specify the termination conditions for


S11 and S16 separately, place the condi-
tions in P111 and P116 and specify two
P111 P116 dummy steps, S12 and S17, as shown
A dummy step also requires a step number
S12 S17 and subprogram number. Alsospecify a
(dummy) (dummy) dummy transition condition, which becomes
always true, in P110.

P110

S20

929
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
PROGRAMS STEP SEQUENCE FUNCTION B61863E/14

3.8 A jump controls the execution of steps nonsequentially, together with a


transition.
JUMP
[Display]

Ln

[Contents]
D Specify a jump destination label (Ln).
D The step to which control is transferred (jumped) is activated.
D The jump destination must be within the same program.
D A jump cannot be performed from outside a simultaneous sequence
to within the simultaneous sequence, or from within a simultaneous
sequence to outside.
D A jump cannot be performed between parallelbranched paths.
[Example]

L1
[ ] S1
When steps S4 and S5 ar
P101 executed and the transition P110
evaluates true, the program is
repeated from initial step S1.

S2 S3

P102 P103

S4 S5

P110

L1

3.9 A label specifies the jump destination.


LABEL [Display]

Ln

[Contents]
Specify the jump destination label (Ln).
[Example]
Refer to an example described on the jump function (3.8).

930
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
B61863E/14 STEP SEQUENCE FUNCTION PROGRAMS

3.10 A block step specifies the step sequence subprogram to be executed.


BLOCK STEP [Display]

] Sn
(Pm)

[Contents]
Define a step number (Sn), which controls the execution of a bloc
step, and a subprogram (Pm) specifying the actual process, for a
block step.

CAUTION
 Assign a step number to a block step.
 The same step number cannot be used twice in a program.
 A transition must be placed after a block step.
Example)
S1 S1

P101 P101

] S2
(P2) P2
S20 S20
equal
P120 P120

S21 S21

P121 P121

P102

S3 S3

 Transition P102 cannot be omitted due to the syntax of the step sequence method. Specify
a dummy transition, which becomes always true, for transition P102.
 Transition P121 must specify the transition condition for the termination of the step S21.
 When the conditions of transitions P102 and P121 are switched, step S21 will not be correctly
executed.

931
3. CONFIGURATION AND OPERATION
OF STEPSEQUENCE
PROGRAMS STEP SEQUENCE FUNCTION B61863E/14

3.11 This is an initial step on the block step.


INITIAL BLOCK STEP [Display]

[ ] Sn
(Pm)

[Contents]
D Define a step number (Sn), necessary for controlling execution, and
subprogram number (Pm)specifying the actual processing, for an
initial step.
D This step has the same function and graphical symbol asan initial
step.

3.12 This terminates a block step.


END OF BLOCK [Display]
STEP

[Contents]
D Use this step to terminate a block step.
D Each block requires at least one end block step. No limit is applied
to the number of end block steps.
[Example]

[ ] S1

P100 P103

S2

P102

932
4. EXTENDED LADDER
B61863E/14 STEP SEQUENCE FUNCTION INSTRUCTIONS

4 EXTENDED LADDER INSTRUCTIONS

To enable the specification of steps and transitions, the components of a


step sequence program, by means of the ladder method, the following
signals and functional instructions are provided. These signals and
instructions can only be used in subprograms in which step sequence step
and transitions are specified.

933
4. EXTENDED LADDER
INSTRUCTIONS STEP SEQUENCE FUNCTION B61863E/14

4.1 [Function]
FUNCTIONAL D This instruction describes that the conditions for a transition have
been true.
INSTRUCTION TRSET D This instruction is used in a subprogram which is called from a
transition.
[Format]

ACT

TRSET
(SUB122)

4.2 [Contens]
PMC ADDRESS D This address is used to read the logical state of a specified step.
(S ADDRESS) 0 : Transition to halt state, or halt state
1 : Execution state
D This address is used for creating a program in which detailed
transitions of the execution states between steps are considered.
Specify the number of the step to be read.
Example) To reference the state of the step S100
S100. 0
D This address allows any subprogram to reference the state of any step.
D Data cannot be written into state signal Sn. 0.
D A ladder can be configured for the TRSET transition instruction
using state signal Sn. 0. Referencing state signal Sn. 0, however,
adversely affects the portability and comprehensibility. Use this
feature sparingly.
[Example]
This address is used to reference the activation states of steps in a step
in which this address has been specified, and performs complicated
wait processing in a program including a simultaneous sequence.

In case of starting the executing of


S2 and S6 synchronously:

S1 S4

P1 P4 Sub program
S5.0
S2 S5 TRSET

P2 P1

S3 S6

934
5. SPECIFICATION OF STEP
B61863E/14 STEP SEQUENCE FUNCTION SEQUENCE

5 SPECIFICATION OF STEP SEQUENCE

935
5. SPECIFICATION OF STEP
SEQUENCE STEP SEQUENCE FUNCTION B61863E/14

5.1
SPECIFICATION Contents/Kind of PMC PMCRB4/RB6/RC4/NB2
Number of subprogram Up to 2000 (P1 to P2000)
Number of step Up to 1000 (S1 to S1000)
Number of label Up to 9999 (L1 to L9999)
Number of jump in block Up to 256
Nesting depth of block step Up to 8 levels
Size of block 64 lines 32 columns
Number of paths Up to 16 paths

@@@@
@@@@
@@@@

Up to 16 paths

@@@@
@@@@

Up to 16 paths

936
5. SPECIFICATION OF STEP
B61863E/14 STEP SEQUENCE FUNCTION SEQUENCE

5.2 D One transition must exist between step and step.


GENERAL RULES
S1 S1
(P10) (P10) sub prog
Correct
CALL P10
P1 or S1
CALL P11
S2 S2
(P11) (P11)
The step S1 calls
to subprogram P10, P11.

D The transition shall never be repeated even at the point of the divergence
and the convergence.

S1 S1

Correct
P1

P2 P10 P1 P10

S3 S10 S3 S10

S2 S10 S2 P10

Correct
P2 P11 P2 P11

P12

S12 S12

937
5. SPECIFICATION OF STEP
SEQUENCE STEP SEQUENCE FUNCTION B61863E/14

D When a simultaneous sequence is specified in another simultaneous


sequence, one convergence must not be used for each sequence.

S1 S2 S1 S2

P2 P2

S3 S4 S3 S4

Correct

P1 P3

S5 S5 (dumy)

P1

S6

D When a selective sequence is specified in a simultaneous sequence,


dummy steps must be required both after the divergence and before
convergence.

S1 P2 P4 S1 S2 (dummy)

S2 S3
P2 P4
P3 P5
S3 S4

Correct P3 P5

P1
S5 (dummy)
S4

P1

S6

938
5. SPECIFICATION OF STEP
B61863E/14 STEP SEQUENCE FUNCTION SEQUENCE

D In case of branching again immediately after the convergence, a


step/transition is required between the divergence and convergence.

S1 S2 S1 S2
Correct

P2 P10 P100 (dummy)


S100 (dummy)
S3 S10

P1 P10

S3 S10

S2 S10 S2 S10

Correct
P2 P11 P2 P11

S12 S13 S100 (dummy)


P100 (dummy )

S12 S13

D Immediately after the block step, a dummy transition which is always


true is needed.

S10
[ ] S100
P10 When block step S11 is used,
P100 transition P11 and P101 cannot
] S11 be omitted
S101
P11 note) P11 is a dummy transition.
The transition condition of
P101 P11 must always be true.
S12

939
5. SPECIFICATION OF STEP
SEQUENCE STEP SEQUENCE FUNCTION B61863E/14

D The divergence must be terminated with the same type of convergence.

P2 P4 Correct P2 P4

S2 S3 S2 S3

P3 P5 P3 P5

P2 P2

Correct

S2 S3 S2 S3

P3
P3

D The number of convergences must match that of divergences.

P1 P2 P1 P2

S2 S3 L1 Correct S2 S3 L1

P3 P3

S4 S4

D The number of convergences must match that of divergences, even at


the end of a block step.

P1 P2 P1 P2

S2 S2

P3 Correct P3

940
5. SPECIFICATION OF STEP
B61863E/14 STEP SEQUENCE FUNCTION SEQUENCE

D It is not possible to jump to the other subprogram.

Subprogram P1
Subprogram P2
S10
S100
P10
P100
L1
S101
S11 S20
P101
P11 P20
S102
S12 L1

D It is not possible to jump from a simultaneous sequence to another


simultaneous sequence.
S1

P1

S2 S10

P2 P10

S3 L1

P3
L1
S4

941
5. SPECIFICATION OF STEP
SEQUENCE STEP SEQUENCE FUNCTION B61863E/14

D It is not allowed to jump from inside of the simultaneous sequence to


outside.

L1
S1

P1

S2 S10 S20

P2 P10 P20

S3 S11 L1

942
5. SPECIFICATION OF STEP
B61863E/14 STEP SEQUENCE FUNCTION SEQUENCE

5.3 The use of the following functional instructions is restricted in steps and
transitions.
EXCLUSIVE
CONTROL FOR Group Description
Functional
instructions
FUNCTIONAL
A The instructions operate when a signal changes CTR (SUB5)
INSTRUCTIONS Con Multiple functional instructions having the same
CTRC (SUB60)
TMR (SUB3)
dition number are used. TMRB (SUB24)
TMRC (SUB54)
Prob Not activated. DIFU (SUB57)
lem Correct operation cannot be guaranteed. DIFD (SUB58)
B Restriction due to the interface. WINDR (SUB51)
WINDW (SUB52)
Con Data is input or output by using two subprograms. DISP (SUB49)
dition DISPB (SUB41)
Prob Invalid return value. EXIN (SUB40)
lem Not terminated. AXCTL (SUB53)

(1) Functional instructions of group A


Since these functional instructions operate when the corresponding
signals change, they may not operate correctly when called from
multiplesteps.
Example)
While multiple CTR functional instructions are used, when
control passes from S1 to S2 with ACT of CTR not set to off, CTR
is not counted when called from step S2.

S1 Subprogram P100
(P100) R0.0
CTR 1 ( )
P1

S2
(P100)

X1.0

Subprogram P1
X1.0
TRSET

943
5. SPECIFICATION OF STEP
SEQUENCE STEP SEQUENCE FUNCTION B61863E/14

Correct program
Divide the subprogram so that ACT of CTR is called after it is set to
off.

S1 Subprogram P100
(P100)
R0.0
CTR 1 ( )
P101

S2
(P102)

X1.0
P103

S3
(P100)
Subprogram P101
X1.0
P101 TRSET

S4
(P102)
Subprogram P102
R0.0
P103 CTR 1 ( )

R9091.0

Subprogram P103
R9091.1
TRSET

(2) Functional instructions of group B


While an instruction is being executed through the interface with the
NC, other same instructions cannot be executed. PMC control
software does not receive the process when the instruction is not at
a same position (net).
If ACT is set to on and off in different instructions (or subprograms),
these processes are not terminated.

NOTE
In the window instructions (WINDR and WINDW),
lowspeedtype is included the functional instructions of
group B.

944
5. SPECIFICATION OF STEP
B61863E/14 STEP SEQUENCE FUNCTION SEQUENCE

Example)

S1 Subprogram P100
(P100) R9091.1 R0.0
P1 WINDR R10 ( )

S2
(P101) Subprogram P1
R0.0
TRSET

Subprogram P101
R9091.0 R0.0
WINDR R10 ( )

Correct program
Correct the program so that ACT is set to on and off within one
subprogram.

S1 Subprogram P100
(P100) R9091.1
R0.0
P1 ( )

S2 CALLU P2
(P101)

Subprogram P1
R0.0
TRSET

Subprogram P101
R9091.0 R0.0
( )

CALLU P2

Subprogram P2
R0.1 R0.0
WINDR R10 ( )

945
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

6 CRT/MDI OPERATION

The following operations are supported to enable the diagnosis and


debugging of a step sequence program.
(1) Displaying the sequence diagram
(2) Displaying the run time of the step sequence program
(3) Monitoring the run time of the step sequence program

946
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

6.1 The diagnosis and debugging of a step sequence program have four
screens.
DISPLAYING OF
SEQUENCE (1) Program configuration list (main screen)
PROGRAM (2) Step sequence screen
(3) List screen
(4) Ladder screen

6.1.1 Press the [STPSEQ] key and display the program configuration list.
Program Configuration
List (Main Screen) STPSEQ <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN
P0001 ( ) SUB PROGRAM NO.1

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P0101 V P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ TIME ] [ PADRS ] [ ZOOM ]

Items displayed on the screen


Display Contents Display by [ZOOM] key
LEVEL1 Ladder first level Ladder diagram
LEVEL2 Ladder second level Ladder diagram
LEVEL3 Ladder third level note1) Ladder diagram
V Pxxx Subprogram Ladder diagram
V] Pxxx Subprogram Step sequence diagram

Pxxx indicates a subprogram number.

NOTE
The third level ladder can be omitted.

[ZOOM] key
To display the contents of a program, position the cursor to the
program number and press the [ZOOM] key. The step sequence
diagram (Fig. 6.1.2 (b)) or ladder diagram (Fig. 6.1.3 (c) is
automatically displayed according to the type of the program.
[TIME] key
Press the [TIME] key to display the time display screen (Fig. 6.2.1)
and time monitor screen (Fig. 6.3).
[PADRS/PSYMB] key
Displays the addresses specified to subprograms, using addresses or
symbols, if symbols have been assigned. When the [PADRS] key
ispressed, the addresses are displayed. When the [PSYMB] key is
pressed, the symbols are displayed.

947
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

6.1.2 (1) Position the cursor to a program indicated by V], then press the
[ZOOM] key.
Step Sequence Screen
STPSEQ <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN
P0407 (MAIN ) STEP SEQUENCE NO.1

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P0101 V P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ TIME ] [ PADRS ] [ ZOOM ]

Fig. 6.1.2 (a) Program configuration list (main screen)


Example)
When the cursor is positioned to V] P0407 and press the [ZOOM]
key, the subprogram P407 isdisplayed.
(2) Displayed Step Sequence
Activated steps are indicated by red V (highlighted V on a
monochrome display). (In this manual, activated steps are indicated
by H.)

PCLAD <<STPSEQ>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN


S0001 P0001(ROTATE) ROTATE THE WORK TIP P0407 1 1
< L1
[ ] S1
P1

< L4
] S2 S10 S20 S30

P2 P10 P13 P20 P30


< L2
S3 S11 S13 S21 S31

P3 P11 P14 P21 P23 P31


S4 S14 S23 > L2
P15 P22 S32

S15 S24

[ MAIN ] [ CHANGE ] [ TIME ] [ PADRS ] [ ZOOM ]

Fig. 6.1.2 (b) Step sequence screen

948
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

Meaning of display
Display Contents Display by [ZOOM] key
[V] Sxxx Initial step Ladder diagram
V Sxxx Step Ladder diagram
V] Sxxx Block step Step sequence diagram
+ Pxxx Transition Ladder diagram
Selective sequence Cannot zoom.
Simultaneous sequence Cannot zoom.

L2 Jump Cannot zoom.

L2 Label Cannot zoom.

Pxxx means the subprogram number.


[ZOOM] key
To display the contents of a program, position the cursor to the
program number and press the [ZOOM] key. The step sequence
diagram (Fig.6.1.2 (b)) or ladder diagram (Fig.6.1.3 (c)) is
automatically displayed according to the type of the program.
[MAIN] key
Press the [MAIN] key to return to the program configuration list.
[CHANGE] key
Press the [CHANGE] key to list the subprograms referenced in the
step sequence program.
[TIME] key
Press the [TIME] key to display the time display screen (Fig. 6.2.1).
[PADRS/PSYMB/SADRS/SSYMB] key
Displays the addresses specified with steps and transitions, using
addresses or symbols, if symbols have been assigned. And the display
of steps is changed to display the S addresses or P addresses.
Press the [PADRS] key to display the addresses of P addresses.
Press the [PSYMB] key to display the symbols of P addresses.
Press the [SADRS] key to display the addresses of S addresses.
Press the [SSYMB] key to display the symbols of S addresses.
(3) Displaying the list screen
While the step sequence screen is displayed and press the [CHANGE]
key, a list screen of the subprograms referenced in this step sequence
program is displayed.

PCLAD <<LIST>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN


S0001 P0001 (ROTATE) ROTATE THE WORK TIP
V] P0001 V] P0002 V] P0004 V] P0005 V] P0006 V] P0007

V P0008 V P0009 V P0014 V P0015 V P0016 V P0017


V P0021 V P0022 V P0024 V P0025 V P0026 V]P0027


V P0101 V]P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ ] [ ] [ ZOOM ]

[ MAIN ] [ CHANGE ] [ ] [ ] [ ]

949
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

[ZOOM] soft ke
To display a program, position the cursor to the program number and
press the [ZOOM] key. The step sequence screen (Fig. 6.1.2 (b)) or
ladder screen (Fig. 6.1.3 (c)) is automatically displayed according to
the type of the program.
[MAIN] key
Press the [MAIN] key to return to the program configuration list.
[TIME] key
Press the [TIME] key to display the time display screen (Fig. 6.2.1).
[PADRS/PSYMB] key
Displays the addresses specified to subprograms, using addresses or
symbols, if symbols have been assigned. When the [PADRS] key
is pressed, the addresses are displayed. When the [PSYMB] key is
pressed, the symbols are displayed.
[CHANGE] key
Press the [CHANGE] key to return to the step sequence diagram.

6.1.3 (1) Position the cursor to a program indicated by V, then press the
[ZOOM] key.
Ladder Screen
STPSEQ <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P0101 V]P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ TIME ] [ PADRS ] [ ZOOM ]

Fig. 6.1.3 (a) Program configuration list (main screen)


Example)
When the cursor is positioned to LEVEL1, press the[ZOOM]
key, the first level ladder is displayed.

PCLAD <<STPSEQ>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN


S0001 P0001 (ROTATE) ROTATE THE WORK TIP P0100 4 2
< L1
[ ] S1
P1

< L4
] S10 S20 S30
S2
P2 P10 P13 P20 P30
< L2
S3 S11 S13 S21 S31

[ MAIN ] [ CHANGE ] [ TIME ] [ PADRS ] [ ZOOM ]

Fig. 6.1.3 (b) Step Sequence screen

950
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

Example)
When the cursor is positioned to P2, press the [ZOOM] key,
subprogram P2 is displayed.
(2) Ladder Screen
The signals currently set to on are displayed in white (highlighted on
a monochrome display).

LADDER * STEP SEQUENCE DEMO PROGRAM * NET 00310033 MONIT RUN

R9091.1
MOVN 20
D10
R10
FIN
FIN
/ WINDR R10 ( )

FIN
MOVN 20
R10
SUB 45 D10

END1

SUB 1

[ SEARCH ] [ ADRESS ] [ TRIGER ] [ WINDOW ] [ ]

[ DUMP ] [ DPARA ] [ ] [ ONLEDT ] [ ]

Fig. 6.1.3 (c) Ladder screen


[SEARCH] key
Used for search within a subprogram.

SEARCH ADRESS TRIGER WINDOW

RET

TOP BOTTOM SRCH WSRCH N SRCH

NEXT

FSRCH

[TOP] key
Displays the top of a subprogram.
[BOTTOM] key
Displays the bottom of a subprogram.
[SRCH] key
Searches for the specified address.

951
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

[WSRCH] key
Displays the ladder in which the specified address is used as a coil
address.
[NSRCH] key
Displays the ladder having the specified net number, at the top of
the screen.
[FSRCH] key
Displays the specified functional instruction, at the to of the
screen.
[ADRESS/SYMBOL] key
Displays the addresses specified with relays and coils, using
addresses or symbols, if symbols have been assigned. When the
[ADRESS] key is pressed, the addresses are displayed. When the
[SYMBOL] key is pressed, the symbols are displayed.
[TRIGER] key
With a manual operation or a signal trigger function, a renewal
screen of a ladder monitoring function is stopped. By this
function, the signal status when one signal is changed is certainly
checked.
[WINDOW] key
Splits the screen into two sections, allowing the display of two
ladder positions in a subprogram.
[DUMP] key
Displays the contents of addresses at the bottom of the screen.
[DPARA] key
Displays the data specified with functional instructions.
[ONLEDT] key
While a sequence program is executing, a part of the ladder
diagram can be changed.

952
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

6.2 The elapsed time of a step sequence program is displayed.


TIMER SCREEN

6.2.1
Time Screen
STPSEQ <<STATUS>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN

STEP NO. STATUS ELAPSE MONITOR STEP NO. STATUS.


S0001( ) EXEC 1000000 T(1) OVER S0010(TILE ) EXEC
S0002( ) EXEC 100 T(3) S0011( )
S0003( ) EXEC 10000 T(4) S0012( )
S0004( ) 1000000 S0013( )

[ UP ] [ DOWN ] [ SEARCH ] [ RESET ] [ MONIT ]

Fig. 6.2.1 Time screen


Meaning of display
Display Contents
STEP NO. Step number
S0001 : Step number (123456) : symbol display
STATUS Step state
EXEC : Active space : Inactive
ELAPSE Actual elapsed time (per msec)
The time is increasing during active state.
MONITOR Monitor time
T (1) : monitoring time number
OVER : An elapsed time is over monitoring time

[UP] [DOWN] key


Scrolls the screen up or down, in units of pages, to display the
operation time of other steps. Acts in the same way as the page up
or down key.
[MONIT] key
Displays the screen used for setting the timer to monitor the operation
time. (See 6.3)
[SEARCH] key
Search and display the specified step number.
example) Display the S100 address.
Key in 100 and press the [SEARCH] key.
[RESET] key
For all of monitoring steps, the error status which occurred by the
monitoring function is canceled.
To cancel the status per steps, press the [DELETE] key on the monitor
time screen. (Please refer to 6.3 Monitor Time Screen below)

953
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

6.2.2 When an activated state remains set for longer than the specified time,
Monitoring Elapsed the state may be determined as being erroneous. The elapsed time can be
specified for up to eight steps.
Time
When an activated state remains set for longer than the specified time,
(1) OVER is displayed at the corresponding step number on the
STPSEQ/TIME screen.
(2) Execution of the ladder continues.
(3) The bit of address R9118 which corresponds with the step number is
set to
1. The processes for the error status can be program by the ladder
diagram. And the following message is displayed on the
PMC/ALARM screen.
ER48 STEP SEQUENCE TIME OVER (xxH)
xx displays the content of address R9118 in hexadecimal code.
Time Corresponding Time Corresponding
Number Address Number Address
1 R9118.0 5 R9118.4
2 R9188.1 6 R9118.5
3 R9188.2 7 R9188.6
4 R9188.3 8 R9188.7

954
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

6.3 Operation time limits can be specified for a step sequence program. Up
to eight steps can be monitored.
MONITOR TIME
SCREEN
STPSEQ<<MONITOR>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT RUN

NO. STEP NO. ELAPSE MONITOR


T(1) S0001( ) 1000000 2000
T(2) S0010(MOVE ) 100 1000
T(3) S0002( ) 100 2000
T(4) S0003( ) 10000 20000
T(5)
T(6)
T(7)
T(8)

[ DELETE ] [ ] [ ] [ ] [ ]

Fig. 6.3 monitor time screen


Meaning of display
Display Meaning
NO. Monitor time number
T (1) : means monitor time 1.
STEP NO. Step number
S0001 : Step number (123456) : symbol display
ELAPSE Actual elapsed time (per msec)
The time is increasing during active state.
MONITOR Monitor time (per msec)

[DELETE] key
Delete the definition of monitor time.
Operation
Definition of monitor
(1) Position the cursor at the input position and input a step
(or symbol).

NO. STEP NO. ELAPSE MONITOR


T(1) S0001( ) 1000000 2000
T(2) S0010(MOVE )

Key in MOVE and push [INPUT] key.


(2) Position the cursor at the input position and define a monitor
time.

NO. STEP NO. ELAPSE MONITOR


T(1) S0001( ) 1000000 2000
T(2) S0010(MOVE ) 1000 100

Keyin 100 and push [INPUT] key.

955
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

Deletion of monitor
Position the cursor at the deletion and press [DELETE] key.

NO. STEP NO. ELAPSE MONITOR


T(1) S0001( ) 1000000 2000
T(2) S0010(MOVE ) 100 1000

Alteration of monitor
Position the cursor at the alteration position and input again.

NO. STEP NO. ELAPSE MONITOR


T(1) S0001( ) 1000000 2000
T(2) S0100( ) 2000 1000

Key in S100 and push <INPUT> key.

956
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

6.4 The display and editing of a step sequence program per subprogram
aresupported.
EDITING FUNCTION A step sequence program is allowed to be displayed and a ladder diagram
OF LADDER is allowed to be displayed and edited.
DIAGRAM

6.4.1 Press the [EDIT] and [LADDER] key and display the program
Program Configuration configuration list.
List (Main Screen)
STPSEQ <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP
P0001 ( ) SUB PROGRAM NO.1

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P0101 V P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ ] [ PADRS ] [ ZOOM ]

Items displayed on the screen


Display Contents Display by [ZOOM] key
LEVEL1 Ladder first level Ladder diagram
LEVEL2 Ladder second level Ladder diagram
LEVEL3 Ladder third level (Note) Ladder diagram
V Pxxx Subprogram Ladder diagram
V] Pxxx Subprogram Step sequence diagram

Pxxx indicates a subprogram number.

NOTE
The third level ladder can be omitted.

[ZOOM] key
To display the contents of a program, position the cursor to the
program number and press the [ZOOM] key. The step sequence
diagram (Fig. 6.4.2 (b)) or ladder diagram (Fig. 6.4.3 (c)) is
automatically displayed according to the type of the program.
[PADRS/PSYMB] key
Displays the addresses specified to subprograms, using addresses or
symbols, if symbols have been assigned. When the [PADRS] key
is pressed, the addresses are displayed. When the [PSYMB] key is
pressed, the symbols are displayed.

957
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

6.4.2 (1) Position the cursor to a program indicated by j], then press the
[ZOOM] key.
Step Sequence Screen
LADDER <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP
P0407 ( ) STEP SEQUENCE NO.1

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P0101 V P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ TIME ] [ PADRS ] [ ZOOM ]

Fig. 6.4.2 (a) Program configuration list (main screen)


Example)
When the cursor is positioned to j] P0407 and press the
[ZOOM] key , the subprogram P407 is displayed.
(2) Displayed Step Sequence
Activated steps are indicated by red j (highlighted j on a
monochrome display). (In this manual, activated steps are indicated
by J.)

LADDER <<STPSEQ>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP


S0001 P0001(ROTATE) ROTATE THE WORK TIP P0407 1 1
< L1
[ ] S1
P1

< L4
] S2 S10 S20 S30

P2 P10 P13 P20 P30


< L2
S3 S11 S13 S21 S31

P3 P11 P14 P21 P23 P31


S4 S14 S23 > L2
P15 P22 S32

S15 S24

[ MAIN ] [ CHANGE ] [ ] [ PADRS ] [ ZOOM ]

Fig. 6.4.2 (b) Step sequence screen

958
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

Meaning of display
Display Contents Display by [ZOOM] key
[V] Sxxx Initial step Ladder diagram
V Sxxx Step Ladder diagram
V] Sxxx Block step Step sequence diagram
+ Pxxx Transition Ladder diagram
Selective sequence Cannot zoom.
Simultaneous sequence Cannot zoom.

L2 Jump Cannot zoom.

L2 Label Cannot zoom.

Pxxx means the subprogram number.


[ZOOM] key
To display the contents of a program, position the cursor to the
program number and press the [ZOOM] key. The step sequence
diagram (Fig. 6.4.2 (b)) or ladder diagram (Fig. 6.4.3 (c)) is
automatically displayed according to the type of the program.
[MAIN] key
Press the [MAIN] key to return to the program configuration list.
[CHANGE] key
Press the [CHANGE] key to list the subprograms referenced in
the step sequence program.
[PADRS/PSYMB/SADRS/SSYMB] key
Displays the addresses specified with steps and transitions, using
addresses or symbols, if symbols have been assigned.
And the display of steps is changed to display the S addresses or
P addresses.
Press the [PADRS] key to display the addresses of P addresses.
Press the [PSYMB] key to display the symbols of P addresses.
Press the [SADRS] key to display the addresses of S addresses.
Press the [SSYMB] key to display the symbols of S addresses.
(3) Displaying the list screen
While the step sequence screen is displayed and press the [CHANGE]
key, a list screen of the subprograms referenced in this step sequence
program is displayed.

LADDER <<LIST>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP


S0001 P0001 (ROTATE) ROTATE THE WORK TIP
V] P0001 V] P0002 V] P0004 V] P0005 V] P0006 V] P0007

V P0008 V P0009 V P0014 V P0015 V P0016 V P0017


V P0021 V P0022 V P0024 V P0025 V P0026 V]P0027


V P0101 V P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ CHANGE ] [ ] [ PADRS ] [ ZOOM ]

[ZOOM] soft key


To display a program, position the cursor to the program number
and press the [ZOOM] key. The step sequence screen (Fig. 6.4.2
(b)) or ladder screen (Fig. 6.4.3 (c)) is automatically displayed
according to the type of the program.

959
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

[MAIN] key
Press the [MAIN] key to return to the program configuration list.
[CHANGE] key
Press the [CHANGE] key to return to the step sequence diagram.
[PADRS/PSYMB] key
Displays the addresses specified to subprograms, using addresses
or symbols, if symbols have been assigned. When the [PADRS]
key is pressed, the addresses are displayed. When the [PSYMB]
key is pressed, the symbols are displayed.

6.4.3 (1) Position the cursor to a program indicated by j, then press the
[ZOOM] key.
Ladder Screen

LADDER <<MAIN>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP

LEVEL1 LEVEL2 LEVEL3


V P0001 V P0002 V P0004 V P0005 V P0006 V P0007
V P0008 V P0009 V P0014 V P0015 V P0016 V P0017
V P0021 V P0022 V P0024 V P0025 V P0026 V] P0027


V P0101 V P0202 V]P0304 V]P0405 V]P0406 V]P0407

[ UP ] [ DOWN ] [ ] [ PADRS ] [ ZOOM ]

Fig. 6.4.3 (a) Program configuration list (main screen)

Example)
When the cursor is positioned to LEVEL1, press the [ZOOM] key, the
first level ladder is displayed.

LADDER <<STPSEQ>> PROGRAM:(STEP SEQUENCE DEMO PROGRAM) MONIT STOP


S0001 P0001 (ROTATE) ROTATE THE WORK TIP P0100 4 2
< L1
[ ] S1
P1

< L4
] S10 S20 S30
S2
P2 P10 P13 P20 P30
< L2
S3 S11 S13 S21 S31

[ MAIN ] [ CHANGE ] [ ] [ PADRS ] [ ZOOM ]

Fig. 6.4.3 (b) Step Sequence screen

Example)
When the cursor is positioned to P2, press the [ZOOM] key, the
subprogram P2 is displayed.

960
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

(2) Ladder Screen

LADDER NET 00310033 MONIT STOP

R9091.1
MOVN 20
D10
R10
FIN
FIN
/ WINDR R10 ( )

FIN
MOVN 20
R10
SUB 45 D10

END1

SUB 1

Fig. 6.4.3 (c) Ladder screen


Please refer to the following section about the operations of editing a
ladder diagram.
III PMC PROGRAMMER(CRT/MDI) 5.2 Sequence
Program Generation(LADDER)

961
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

6.5 The following ladder diagnosis and debugging functions can be used
together with the step sequence functions.
CORRESPONDING
FUNCTION : can be used
: can be used on condition
: cannot be used
Functions PMCSB4/ PMCSC4 PMCNB2
SB6
PMC Ladder diagram display (PMCLAD)
PMC I/O signal display (PMCDGN)
Title screen (TITLE)
Signal status screen (STATUS)
Alarm screen (ALARM)
Trace screen (TRACE)
Contents of Memory (MEMORY)
Signal Waveforms screen (ANALYS) NOTE1
Running State of a User Task (USRDGN)
PMC Parameters screen (PMCPRM)
Timer screen (TIMER)
Counter screen (COUNTR)
Keep relay screen (KEEPRL)
Data table screen (DATA)
Simple setting screen (SETING)
Step Sequence screen (STPSEQ)
Displaying Step Sequence screen
Displaying Ladder screen
SEARCH
Display address and symbol
Trigger function (TRIGER)
Divided screen function (WINDOW)
Contents of memory (DUMP)
Contents of parameter (DPARA)
online editting (ONLEDT)
Time screen (TIME)
Monitor time screen (MONIT)
Execute or stop the sequence program (RUN)
Edit function (EDIT) NOTE1
Title screen (TITLE)
Ladder diagram (LADDER)
Symbol screen (SYMBOL)
Message screen (MESAGE)
Definition of I/O (MODULE)
Cross reference (CROSS)
Memory clear (CLEAR)
Input and output
FANUC LADDER (HOST)
Floppy cassette (FDCAS)
FlashROM (FROM)
Memory card (MCARD) NOTE2
Other I/O device (OTHERS)
System Parameter (SYSPRM) NOTE1
Debug function (MONIT) NOTE1
Ladder debug function (DBGLAD)
Descriptor table screen (GDT)
User memory screen (USRMEM)
User program debug function (DEBUG)

NOTE
1 An Editor card is needed.
2 It is possible to use while an Editor card is not mounted.
(Can be used with the 16i/18i/21i.)

962
B61863E/14 STEP SEQUENCE FUNCTION 6. CRT/MDI OPERATION

6.6 The PMCSB4, SB6, SC4 and NB2 can be used with either the ladder
method or step sequence method. When a step sequence program is
COMPATIBILITY OF transferred to the old version of the PMC, ER08 OBJECT UNMATCH
LADDER DIAGRAM is displayed on the PMC/ALARM screen.
The model setting of FANUC LADDER determines whether the ladder
or step sequence method is used. The STEP SEQUENCE item has been
added to the system parameter screen for future expansion. Specify the
parameter according to the model setting of FANUC LADDER.
To create a program with the builtin edit function, after the parameter has
been set execute CLEAR ALL. Alternatively, while holding down X
and O key, turn the power off and on.
When the step sequence method is used: STEP SEQUENCE = YES.
When the ladder method is used: STEP SEQUENCE = NO.

PMC SYSTEM PARAMETER (1/2) MONIT STOP

COUNTER DATA TYPE = BINARY / BCD

STEP SEQUENCE = YES / NO

>

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. 6.6 (a) PMCSB4/SB6 system parameter screen (first page)

PMC SYSTEM PARAMETER (2/2) MONIT STOP

FS0 OPERATOR PANEL = YES / NO

KEY DI ADDRESS =

LED DO ADDRESS =

KEY BIT IMAGE ADDRESS =

LED BIT IMAGE ADDRESS =

>

[ YES ] [ NO ] [ ] [ ] [ ]

Fig. 6.6 (b) PMCSB4/SB6 system parameter screen (second page)

963
6. CRT/MDI OPERATION STEP SEQUENCE FUNCTION B61863E/14

PMC SYSTEM PARAMETER (1/2) MONIT STOP

COUNTER DATA TYPE = BINARY / BCD

LADDER EXEC = % (1150)

LANGUAGE EXEC RATIO = % (099)

LANGUAGE ORIGIN = H
(LANGUAGE AREA = H, SIZE = KB)

STEP SEQUENCE = YES / NO

>

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. 6.6 (c) PMCSC4/NB2 system parameter screen (first page)

PMC SYSTEM PARAMETER (2/2) MONIT STOP

FS0 OPERATOR PANEL = YES / NO

KEY DI ADDRESS =

LED DO ADDRESS =

KEY BIT IMAGE ADDRESS =

LED BIT IMAGE ADDRESS =

>

[ YES ] [ NO ] [ ] [ ] [ ]

Fig. 6.6 (d) PMCSC4/NB2 system parameter screen (second page)

964
VII. PMC PROGRAMMER
(SYSTEM P series)
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 1. GENERAL

1 GENERAL

The FANUC LADDER system can easily prepare sequence programs,


symbol data, titles, and message of PMCSB and PMCSC, and also
easily define addresses of the modules to be installed in an I/O unit by
using SYSTEM P series.
Major functions of this FANUC LADDER are as described below.
(1) Input, display and editing of sequence programs
(2) Transfer of sequence programs (including write into EPROM for
PMC or ROM module.)
(3) Collation of sequence programs
(4) Program error display
The SYSTEM P series is used in the stage of preparing a sequence
program only and separated from PMC after the sequence program has
been completed. The SYSTEM P series can be connected to PMC only
when the PMC is operated with the RAM card and cannot be connected
when PMC is operated with a EPROM for PMC or ROM module.

series 16/18/20/21
Machine tool
/Power MateD

PMC card DI/DO card

System floppy loading

FANUC LADDER Paper tape input/output


PMCSA1/SA2 PPR
SYSTEM P series List output
(FANUC LADDER)
PMC EPROM for PMC
WRITER input/output
FANUC LADDER
PMCSB/SC or

FA EPROM for PMC


WRITER input/output

ROM for PMC


moduleinput/output

Floppy PRINTER
input/output
Sequence program figure output

Fig. 1

967
2. FUNCTIONS OF
PROCESSING PMC PROGRAMMER (SYSTEM P series) B61863E/14

2 FUNCTIONS OF PROCESSING

(1) Input of sequence programs


Input sequence programs using the following units when sequence
programs are loaded into the memory of the SYSTEM P series.
a) SYSTEM P series keyboard
b) PPR tape reader (paper tape)
c) Floppy
d) PMC memory
e) EPROM for PMC or ROM module
(2) Sequence program display
Sequence programs can be displayed on the 12 graphic display of
SYSTEM P series as follows.
a) Sequence programs can be displayed using mnemonic symbols.
b) Sequence programs can also be displayed in the ladder diagram
format.
(3) Editing of sequence programs
A sequence program can be edited by using the SYSTEM P series
keyboard in the following three ways.
a) Alteration
b) Insertion
c) Deletion
(4) Transfer of sequence programs
Sequence programs can be transferred as follows.
a) From SYSTEM P series memory to PMC memory
b) From PMC memory to SYSTEM P series memory
c) From SYSTEM P series memory to floppy
d) From floppy to SYSTEM P series memory
e) From SYSTEM P series memory to EPROM or ROM module for
PMC (Write into EPROM for PMC or ROM module)
f) From EPROM for PMC or ROM module to SYSTEM P series
memory
(5) Collation of sequence programs
Sequence programs can be checked by collating them between the
following memories.
a) SYSTEM P series memory PMC memory
b) SYSTEM P series memory floppy
c) SYSTEM P series memory EPROM for PMC or ROM module
d) SYSTEM P series memory paper tape

968
2. FUNCTIONS OF
B61863E/14 PMC PROGRAMMER (SYSTEM P series) PROCESSING

(6) Hard copy


a) Since FANUC PPR is connectable to SYSTEM P series, the
paper tape output and list output (mnemonic symbol) are
obtainable.
b) A ladder diagram can be printed out.
(7) Program error display
Sequence program errors are displayed on the screen of the SYSTEM
P series.
Error codes are displayed at the lower right of the screen as
ALARM=XXX.
Refer to list of error codes in Appendix.

969
3. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (SYSTEM P series) B61863E/14

3 COMPONENT UNITS AND CONNECTIONS

970
3. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (SYSTEM P series) CONNECTIONS

3.1 (1) SYSTEM P series


COMPONENT UNITS This system serves as a programmer to generate and edit sequence
programs.
(2) Series 16
This system transfers a generated sequence program to CNC.
(3) FANUC PPR
This PPR inputs/outputs a sequence program by using a paper tape,
and also output a source list to the printer.
(4) FANUC printer
This printer prints out the sequence program.
(5) FANUC PMC writer
This unit is used for writing a sequence program to the EPROM for
PMC or ROM module when the sequence program has been
completed.
(6) FANUC FA Writer
This unit is used for writing data to the EPROM or ROM module for
the PMC after a sequence program has been created.

971
3. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (SYSTEM P series) B61863E/14

3.2 For details of the connections of SYSTEM P series unit power supply,
PPR, and other units as well as their operation, refer to the following
CONNECTIONS OF operators manuals.
UNITS
SYSTEM PG Mark II: B66014E
SYSTEM PG Mate: B66003E
This chapter mainly describes the connections between SYSTEM P series
and I/O devices.

Fig. 3.2 (a) External view of SYSTEM P Mark II

972
3. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (SYSTEM P series) CONNECTIONS

Fig. 3.2 (b) External view of SYSTEM P Mate

Since a volatile RAM is employed as the SYSTEM P series memory, all


programs (FANUC LADDER system programs and sequence program)
being loaded into memory are operation should be started with the input
of FANUC LADDER system programs (called system loading).
If the SYSTEM P series power supply is turned off halfway in the curse
of inputting a sequence program from the keyboard, the sequence
program must be stored in advance, and this FANUC LADDER provides
an output function to a floppy for this purpose.

973
3. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (SYSTEM P series) B61863E/14

FANUC ROM WRITER (FANUC PMC WRITER)

Adaptor for
ROM modules

(FANUC FA WRITER)

Rear panel of the SYSTEM P EPROM for


Mark II Adaptor for the PMC
1Mbit EPROMs

CN2 CN1
EPROM for the PMC CN4 CN3

Adaptor for 40pin


ROMs
FANUC PPR
1 Tape input
ROM module
PMCSA1/SA2/SB/SC 2 Tape printout
for the PMC
3 List output

FANUC PRINTER

Prints sequence program


figures.

Fig. 3.2 (c) Connection of SYSTEM P series with each unit

(1) Connect FANUC PPR to connector CN1.


(2) Connect FANUC PMC writer or FANUC FA writer to connector
CN2.
(3) Connect FANUC printer to connector CN3.
(4) Connect connector CN4 to PMCSA1/SA2/SB/SB2/SC. It is
connected to a channel preset by a PMC I/O.
For details, refer to Setting and display of I/O in PMC programmer
(CRT/MDI) in III.
Connector JD5A on MAIN PCB 1 CHANNEL
Connector JD5B on MAIN PCB 2 CHANNEL

974
3. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (SYSTEM P series) CONNECTIONS

3.3 Figs. 3.3(a) (b) show the panel of the SYSTEM P series keyboard.
KEYBOARD OF It is not necessary to memorize the meanings of keys on the keyboard.
SYSTEM P SERIES Descriptions of these keys and menus are displayed on the SYSTEM P
series screen by operation, and you can easily operate the SYSTEM P
series board while monitoring the SYSTEM P series screen.
In this chapter, you should understand an outline of functions of these
keys.

Soft keys

Function keys

Function keys
Numeric keypad

Standard keyboard

Fig. 3.3 (a) Panel of the SYSTEM P Mark II key board

Function keys

Data input keys

Fig. 3.3 (b) Panel of the SYSTEM P Mate key board

975
3. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (SYSTEM P series) B61863E/14

3.3.1 This key is used to load the FANUC LADDER system program into the
LOAD Key (System SYSTEM P series memory through a floppy disk at the first time after
turning on power.
Program Loading Key)

3.3.2 F key is used to select an I/O device among I/O devices connected at that
F Keys (F1 to F0) time.
These F keys are provided with an LED. When depressing a key, the LED
lights, and when depressing the key once more, the LED goes out. The
lighting condition of of this LED indicates that an I/O has been
designated. No I/O device is operable when its corresponding LED is not
lighting.
The correspondence between F keys and I/O devices is as shown below.
(I) shows an input, while (O) shows an output.
(1) <F1> key: FANUC PPR paper tape reader (I)
(2) <F2> key: Floppy disk input (I)
(3) <F3> key: Not used
(4) <F4> key: Display of ladder diagram on SYSTEM P series screen
(O)
(5) <F5> key: FANUC PPR printer (O)
(6) <F6> key: FANUC PPR paper tape puncher (O)
(7) <F7> key: Floppy disk output (O)
(8) <F8> key: PMCPA1/PA2/SA1/SA2/SB/SB2/SC (I/O)
(9) <F9> key: FANUC PMC writer, FANUC FA writer (I/O)
(10) <F10> key: FANUC printer (O)
(The ladder diagram is printed on the printer.)
(11) <F13> key: FANUC Floppy Cassette/FANUC FA Card adapter (I)
(12) <F14> key: FANUC Floppy Cassette/FANUC FA Card adapter
(O)
Combination of F key and menu number of FANUC LADDER decided
which function is to be executed.

976
3. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (SYSTEM P series) CONNECTIONS

3.3.3 Four R keys <R0> to <R3> are provided. The meaning of these keys differ
R Keys (R0 to R3) according to the screen conditions at their operating time, even in case of
the same key.
(1) R key menu screen
This screen is obtained just after loading a FANUC LADDER system
program (1/2) or when pressing <NL> key only in a menu screen.
Refer to Fig. 4.2.2.
<R0> FANUC ladder start.
. A menu screen appears.
<R1> Editing a ladder diagram starts.
<R2> Not used in FANUC ladder. (Not accepted when pressing
these keys)
<R3> Request key (see 4.8)
Press NL keys, if a wrong key was pressed by mistake. The screen is
reset to the condition before pressing the wrong R key.
(2) Other than R key menu screen
<R0> This key operation is accepted when EDIT is displayed at the
lower left part of the screen (called EDIT screen hereafter)
during sequence program editing. The screen is switched to
the sequence program, symbol, message, I/O module, and
title, each time this R key is pressed.
<R1> 1 When this key is pressed during printing of a ladder
diagram on an external printer, the printer stops every page
to be ready for key entry.
2 When this key is pressed during data transfer between
SYSTEM P series and PMCSB/SC, data transfer is
stopped.
3 The signal display in a sequence program is alternately
selected to symbols and addresses, each time this R1 is
pressed during the display of the sequence program on the
screen.
<R2> Data on the last page are displayed, each time this key is
pressed on the EDIT screen.
<R3> 1 Data on the next page are displayed, each time this key is
pressed on the EDIT screen.
2 Transfer is aborted when this key is pressed during ROM
data transfer between SYSTEM P series and
PMCWRITER or floppy.

977
3. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (SYSTEM P series) B61863E/14

3.3.4 Data keys are used to enter data. To switch the output of such keys
Data Keys and Screen between the upper character and lowercharacter, use the [SHIFT] key or
[LOCK] key. Pressing the [SHIFT] key together with an arbitrary key
Scroll Key changes the output of the arbitrary key to the upper character, and pressing
the [LOCK] key changes the output of all keys to upper character. To
release the upper character mode, press the [LOCK] key again.
Special keys are described below.
(1) <NL> key
Data entry from the SYSTEM P series keyboard are input into
SYSTEM P series by depressing <NL> key.
Two <NL> keys are located on the keyboard for easily operation.
(2) <CAN> key
Data being entered from the keyboard are cancelled.
(3) BS key
Data being entered from the keyboard are sequentially deleted
leftward, each time this key is depressed.
(4) Arrow keys <> <> <> <>
These keys are accepted only when a ladder diagram is being
displayed on the screen, and used for scrolling the ladder diagram.

NOTE
None of [INS] [DEL] [CHG] [AUX] keys and K key is employable
in the FANUC LADDER.

978
3. COMPONENT UNITS AND
B61863E/14 PMC PROGRAMMER (SYSTEM P series) CONNECTIONS

3.4 (1) SYSTEM P series Mate


SETTING OF I/O An initial I/O device setting of FANUC LADDER for SYSTEM P
series Mate is as follows.
DEVICE
Table 3.4(a) FANUC LADDER (Mate) of table

Channel I/O device F key


CN1 PMCRAM F8
CN2 PMC WRITER F9
FA WRITER
CN3 External printer F10

Alter the setting of the I/O device by undermentioned IO command


when using FANUC PPR.

(Setting method of IO i) Press the R3 key in the menu screen of R keys.


command) REQUEST = is displayed in the left bottom of screen and
becomes the state which can be typed in.
ii) Type in IO PPR, CN1 <NL>.
PPR is allocated to channel 1.
iii) Type in as follows when channel 1 allocation is returned to
PMCRAM.
IO, NC, CN1, F8, BR10 <NL>
(2) SYSTEM P Mark II
The initial setting of I/O devices of FANUC LADDER for the
SYSTEM P Mark II is as follows.

Table 3.4(b) FANUC LADDER (Mark II)

Channel I/O device F key


CN1 FANUC PPR F1, F5, F6
CN2 PMC WRITER F9
FA WRITER
CN3 External printer F10
CN4 PMCRAM F8

(3) When a FANUC Floppy Cassette or FANUC FA Card adapter is used,


change the setting of the I/O device by executing the following I/O
command:
i) Press the [R3] key on the menu screen for the [R] keys.
Then REQUEST = appears at the lower left of the screen allowing
data to be entered.
ii) Type IO BCA, CN2, F13, F14, then press the <NL> key. The
FANUC Floppy Cassette or FA Card adapter is allocated to
channel 2.
iii) To initialize the setting of channel 2 again, type IO AUX, CN2,
F9, then press the <NL> key.
(4) Setting of the ROM writer
The PMCSA1, SA2 or SB uses one of 1MB EPROM (27C1024).
The PMCSC uses one of ROM module (128KB, 256KB, or
512KB).

979
3. COMPONENT UNITS AND
CONNECTIONS PMC PROGRAMMER (SYSTEM P series) B61863E/14

For this reason, when the PMCSA1, SA2 or SB is used, both the
FA Writer and PMC Writer can be used. When the PMCSC is used,
only the FA Writer is available.
When the PMCSA1, SA2 or SB is used, the ROM writer used can
be selected on the REQUEST screen as follows.
1 On the REQUEST screen, enter WRITER then press the <NL> key.
2 The following message appears. To select the FA Writer, enter 0
or press the <NL> key. To select the PMC Writer, enter 1.
SET KIND OF ROM WRITER (0:FA WRITER, 1:PMC
WRITER)
WRITER=
The current setting of the ROM writer can be checked on the system
parameter screen.
(1) PMC Writer
The PMC Writer is required when the PMCSA1, SA2, SB or
SB2 is available. To use a 1MB EPROM (27C1024), the 1M
EPROM adapter (A13B0147B001) is required. Set the
EPROM select switch to the 271024 position before using the 1M
EPROM adapter.
(2) FA Writer
When the FA Writer is used with the PMCSA1, SA2 or SB,
the EPROM adapter (1MB) for the FA Writer is required. When
the FA writer is used with the PMCRC, the ROM module
adapter is required.

980
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4 OPERATION

981
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.1 Various operations of FANUC ladder are done onthe specified screen.
GENERAL Fig. 4.1 shows the relation between various operations and corresponding
screens.

Power on SYSTEM P series power on

SYSTEM P Visual identification characters

FANUC ladder system floppy loading


FANUC ladder
system loading

Visual identification characters


FANUC ladder
R key menu screen
R0, R1, R2, R3

Keyin NL Keyin R3 Keyin R0 Keyin R1 Keyin R2


Ladder diagram
REQUEST= Parameter screen Unused
direct editing

Keyin NL 00 or NL keyin

Menu screen

01 keyin 02 keyin 03 keyin 04 keyin 05 keyin 06 keyin 07 keyin 08 keyin 09 keyin 10 keyin

Edit Source ROM Source ROM Source ROM Unused Clear Parame-
screen program program program program program program screen ter set-
input input output output verify verify ting
screen screen screen screen screen screen screen
(PTR, (FD, (PTP, FD, (FD, (PTR, (FD,
FD, KB) RAM PRT) RAM FD) RAM
cassette) cassette) cassette)

E NL keyin

00 or NL keyin after
E NL keyin when an alarm occurred or when parameter setting.
processing was aborted halfway.
Automatic return when processing has been
terminated normally.

Fig. 4.1 (a) Relation between various operations and screens

982
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

START

SYSTEM P power
on

Load system floppy


Set necessary system parameters.

Sequence program input, title,


symbol, comment, message
I/O module

Editing

Debug using PMCRAM

NO
Is dedug
completed?

YES

Write a sequence program into


EPROM for PMC or ROM
module

SYSTEM P series
power off

Operate the system after loading


EPROM for PMC or ROM module
to CNC

END

Fig. 4.1 (b) Outline of operation

983
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.2
PREPARATION
BEFORE OPERATION

4.2.1 The system floppy disk contains the system of FANUC LADDER for
System Floppy PMCSA1/SA2/SB/SB2/SC.

4.2.2 To apply the FANUC LADDER system for PMCSA1/SA2/SB/SB2/SC


Limitations with the to the SYSTEM P Mate will overlay each of the following functions.
SYSTEM P Mate D The function to display the ladder diagram on the screen and output it
on an external printer, which is operated using the menu numbers 03 and
F4 or 04 to F10.
D The function to input/output the ROM formatted program and make its
comparison, which is operated combining the menu numbers 03, 05 or
07 and F2, F7, F8, F9, F13 or F14.
D Ladder diagram direct editing, which is operated by pressing <R1> key
on the R key menu screen and executing ladder diagram direct editing.
The SYSTEM P Mate has less memory than the SYSTEM P Mark II and
cannot load the system program on the system floppy disk at a time. The
remainder left unloaded will be loaded automatically when each of the
functions above is used. However, only in the case the system floppy disk
has not been installed into the drive, the message MOUNT SYSTEM
FLOPPY DISK is displayed as follows:
SET SYSTEM FD & KEY I OK OR NO
FDD =OK ODRIVEJ (VOL =01)
FDD =
Install the system floppy disk into the drive #0 or #1 and key in OK 0
or OK 1. If the system floppy disk is installed into the drive #0, it is
possible to key in only OK without specifying the drive number.

4.2.3 FANUC LADDER system programs are loaded into the floppy. Also,
Loading of Floppy sequence programs can be written from SYSTEM P series into the floppy
or input from the floppy.
The loading method of the floppy is described in detail in the operators
manual for SYSTEM P series.
The following describes the loading direction of the floppy.
Loading direction of floppy

984
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

Drive No. 0

Drive No. 1

CRT

Fig. 4.2.3 Loading direction of floppy

4.2.4 (1) Turn on the SYSTEM P series power supply.


FANUC LADDER (2) Set the system floppy or prepared exclusive system floppy into the
System Floppy floppy disk.
Loading (3) Continue depressing <LOAD> key for 2 to 3 seconds on the
keyboard.
(4) The system loading is started. After this system loading, FANUC
LADDER is displayed on the CRT screen and R key menu also
appears.
This R key menu screen is shown in Fig. 4.2.6.
After this screen is displayed, take out system floppy or exclusive
system floppy.

Fig. 4.2.4 R key menu screen

985
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.2.5 A programmer menu screen (hereinafter called menu screen) is displayed


Programmer Menu by pressing <R0> key from the R key menu screen. Key in a menu number
to be executed Fig. 4.2.5 shows the menu screen.
Screen
The parameter setting screen is displayed by pressing <R0> key just after
loading the 1/2 system floppy.
Set parameters as required, referring to 4.2.6.
Proceed to the menu screen by pressing <NL> key.
Parameters are displayable and settable from the menu screen, too.
Programmer menu screen (The programmer menu and function keys are
displayed.)
The following figure shows the screen to be displayed when the
programmer key (R0) is pressed.
The programmer menu, function keys with I/O indication, and statuses
are displayed on this screen.

SET I/O KEY & KEY IN ONE OF THE FOLLOWING NO.S WHICH YOU WANT.

NO. ITEMS
01 EDIT LADDER PROGRAM.
02 INPUT LADDER PROGRAM FROM PTR OR FD.
03 INPUT ROM DATA FROM FD, PMCRAM OR ROM.
04 OUTPUT LADDER PROGRAM TO PTP. FD OR PRINTER.
05 OUTPUT ROM DATA TO FD, PMCRAM OR ROM.
06 COMPARE LADDER PROGRAM WITH PTR OR FD.
07 COMPARE ROM DATA WITH FD, PMCRAM OR ROM.
Capacity of area
08 (UNUSED) used for symbols
09 CLEAR OF TITLE, SYMBOL, LADDER OR MESSAGE DATA. and comment data

10 PARAMETER SET. A period of the


00 END EDIT & DISPLAY. sequence program

F1 : PTR (I) . F4 : GRP (O) SYMBOL =00.0KB SCAN TIME=OOOMS Capacity of a


ladder program
F2 : FD (I) . F10 : FPRT (O) LADDER =00.0KB
F5 : PRT (O) MESSAGE=00.0KB Capacity of
message data
F6 : PTP (O) ROM MODULE=A
The number of the
F7 : FD (O) END SEQ.NO=00000 last step in the
F8 : PMC (I/O) ERR SEQ.NO=00000 sequence program

F9 : ROM (I/O) ERR BLOCK =00000 ALARM=00 The number of a


step at which an
error occurred
The number of an
error occurred
NO. =
The number of
blocks in which an
error was detected
Enter a menu number.

Fig. 4.2.5 Programmer menu screen

986
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.2.6 Set parameters before inputting a sequence program without fail. Set
Parameter Setting and necessary parameters by changing from the menu screen to the parameter
setting screen (Fig.4.2.6), provided that the parameter setting screen is
Display automatically displayed just after loading the system floppy.
(Operation in step 1 is not required in the procedure below.)
1 Key in menu number 10 <NL> from the menu screen.
Turn off all F keys. The screen is switched, and the parameter setting
screen shown in Fig. 4.2.6 is displayed.
The initial value of each parameter is as shown in Fig. 4.2.6.

KEY IN ONE OF THE FOLLOWING NO.S WHICH YOU WANT TO SET PARA,S.

NO. ITEMS CURRENT PARAMETERS

01 (UNUSED) ;
02 COUNTER DATA TYPE ; BINARY
03 OPERATOR PANEL ; NO
KEY/LED ADDRESS ; /
KEY/LED BIT IMAGE ADRS. ; /
04 PMC TYPE ; PMCRC
05 LANGUAGE ORIGIN ; 000000H
06 (UNUSED) ;
07 LADDER EXEC. ; 100% (1150%)
08 (UNUSED) ;
09 IGNORE DIVIDE CODE ; NO
10 (UNUSED) ;
00 NOTHING TO SET
; ROM WRITER=FA WRITER
NO.=

Fig. 4.2.6 Parameter setting screen (PMCRC)

2 Key in 00 <NL> to proceed to the menu screen, if displayed


parameters are employed as they are.
3 Set parameters according to the following procedure when it is
necessary to change the displayed parameters.
No operation is required for an item in which no change is required.
a) Set a counter data type. The initial value is set to the binary
format.
1 Key in 02 <NL>
2 Select a binary or BCD notation, and key in the
corresponding number @@<NL>.
b) OPERATOR PANEL
Specifies whether the operators panel is used.
The initial value is already set to NO (unused).
1 Enter 03 and press the <NL> key.
2 The following message appears at the lower left of the screen.
EXAMPLE 0:NO, 1:YES
OP PANEL=
3 To disable the operators panel, enter 0 and press the <NL>
key. To enable the operators panel, enter 1 and press the
<NL> key.

987
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4 Selecting YES in step 3 displays the following message:


SET KEY/LED ADDRESS (KEY ADRS, LED ADRS.)
ADDR=
5 Enter a Yaddress to specify the KEY address and a
Yaddress to specify the LED address. For example, enter
X0,Y0 and press the <NL> key.
6 Entering data as shown above displays the following
message:
SET KEY/LED IMAGE ADDRESS (KEY ADRS, LED
ADRS.)
ADDR=
7 Enter addresses other than X and Faddresses. For
example, enter R0,R10 and press the <NL> key.
c) Select the type of PMC.
The initial value has been set to the PMCSB or SA1.
1 Type 04 and press the <NL> key.
2 The following message appears at the lower left of the screen:
EXAMPLE 0:PMCSB, 1:PMCSC
PMC TYPE=
or
EXAMPLE 0:PMCSA1, 1:PMCSA2
PMC TYPE=
3 To select the PMCSB or SA1, enter 0 and press the <NL>
key. To select the PMCSC or SA2, enter 1 and press the
<NL> key.
4 When the type of PMC is changed, all data items including
ladder data are cleared. The following message is displayed
for confirmation:
CLEAR ALL DATA TO CHANGE PMC TYPE (0:NO,
1:YES)
CLEAR/KEEP=
5 To cancel changing the type of the PMC, enter 0 and press the
<NL> key. To change the type of the PMC, enter 1 and press
the <NL> key.
d) LANGUAGE ORIGN (for PMCSC only)
The initial value is already set to 0.
1 Enter 05 and press the <NL> key.
2 Enter @@@@@@ (hexadecimal) and press the <NL> key
to specify the first address of the TCB in a C program.
e) LADDER EXEC (only for PMCSC)
The parameter value for LADDER EXEC is fixed to 100% for the
PMCRB. For the PMCRC, the parameter value can be set as
follows.
1 key in 07 <NL>.
2 Key in @@@ <NL> by numeric characters within a range
of 1% to 150%.
After setting, key in @@ <NL> or <NL> to set the menu screen.
This parameter is not supported for PMCSA1, PMCSA2,
PMCSB or PMCSB2.

988
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

f) IGNORE DIVIDE CODE (only for PMCSB/SC)


It is possible to select whether to execute a ladder program by
dividing it into smaller units or without dividing it.
This parameter can be specified as follows for PMCSB and
PMCSC:
1 Enter 09 and press the <NL> key.
2 To execute the ladder program by dividing it into smaller
units, enter 0 and press the <NL> key. To execute it without
dividing it, enter 1 and press the <NL> key.
This parameter is not supported for PMCSA1 or PMCSA2.
The ladder program is always executed without being divided.

989
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.3
PROGRAM EDITING

4.3.1 Display the EDIT screen by keying in 1 <NL> from the menu screen.
Data Display and Press <R0> by necessary times until a desired screen appears from the title
to I/O module. The screen is switched in the sequence shown in Fig.
Setting (Title, Symbol, 4.3.1, each time <R0> key is pressed.
Ladder Program,
Comment, Message, Individual screens are reset to the menu screen by E <NL>. In this
paragraph, only the input and editing operation of each data from the
I/O Module)
keyboard is described.
For the I/O operations using a paper tape or a floppy, see 4.4 and 4.5.
(1) Title data (title data list screen).
Set the following data on sequence program as a comment.

Menu screen Key in 1 NL

EDIT screen
Ladder program list R0
screen
R0

Symbol & comment list


Title data list screen
screen

R0
R0
I/O module data list Message data list
screen screen
R0

Fig. 4.3.1 (a) Switching sequence of data display screen

*** TITLE DATA LIST ***


01 MACHINE TOOL BUILDER NAME
02 MACHINE TOOL NAME
03 PMC & NC NAME FANUC PMCMODEL RB & F16MA
04 PMC PROGRAM NO.
05 EDITION NO.
06 PROGRAM DRAWING NO.
07 DATE OF PROGRAMMING
08 PROGRAM DESIGNED BY
09 ROM WRITTEN BY
10 REMARKS

PMC CONTROL PROGRAM SERIES : 4061 EDITION : 01

MEMORY USED : 00.0 KBYTE SCAN TIME : 008 MSEC

0003 ALTERED
EDIT

Fig. 4.3.1 (b) Title data list screen

990
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

a) MACHINE TOOL BUILDER NAME


Set the machine tool builder name (max. 32 characters).
Key in A1 @@@..........@@@ NL.

Machine tool builder name to be set


Example) A1 ***MACHINE(LTD) NL
b) MACHINE TOOL NAME
Set the machine tool name (max. 32 characters).
Key in A2 @@@..........@@@ NL.

Machine tool name to be set


Example) A2 ***MACHINE NL
c) CNC & PMC NAME
Set the CNC and PMC name (max. 32 characters).
Key in A3 @@@..........@@@ NL.

NC and PMC name to be set


Example) A3 F16MA.&.PMCN NL
d) PMC PROGRAM NO.
Set the sequence program number (max. 4 characters).
Key in A4 @@@@ NL.

Number to be set
Example) A4 0001 NL
e) EDITION NO.
Set the edition number (max. 2 characters).
Key in A5 @@ NL.

Edition number to be set


Example) A5 G NL
f) PROGRAM DRAWING NO.
Set the sequence program drawing number (max. 32 characters).
Key in A6 @@@...........@@@ NL.

Drawing number to be set


Example) A6 00010002000A NL
g) DATE OF PROGRAMMING
Set the sequence programming date (max. 16 characters).
Key in A7 @@..........@@ NL.

Date to be set
Example) A7 1990.10.23 NL

991
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

h) PROGRAM DESIGNED BY
Set the sequence program designer name (max. 32 characters).
Key in A8 @@@..........@@@ NL.

Name to be set
Example) A8 MR.***&MISS *** NL
i) ROM WRITTEN BY
Set the name of the programmer who wrote a program into ROM
cassette (max. 32 characters).
Key in A9 @@@..........@@@ NL.

Name to be set
Example) A9 MR.***&MISS *** NL
j) REMARKS
Set remarks (memo) (max. 32 characters).
Key in A10 @@..........@@ NL.

Remarks to be set
Example) A10 MEMOCOMMENT NL
Set title data about all items in the above format for both entry and
alteration.
All characters are settable so long as they can be keyed in from
the SYSTEM P series keyboard. Set easytounderstand data
about individual items.
(2) Symbol and comment data (SYMBOL & COMMENT LIST screen).
A symbol means a signal name to be attached to each PMC I/O signal.
The comment data is a comment statement of the signal name.
The symbol is optionally settable within maximum 6 characters,
while the comment data are optionally settable within maximum 30
characters.
a) Input from keyboard (Insert)
Key in G0.1 SYMNAM COMMENT NL.

Comment data
Symbol name
Address

Mode selection(IS..., AS...) and line selection (I..., A...) need not
be specified when symbols or comment data are input or edited.
Also addresses (G, F, X, Y,...) can be entered in any sequence.
b) Alter
The operation is completely the same as that described in 2) a).
c) Insert
The operation is completely the same as that described in 2) a).

992
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

d) Delete
i) Delete every line
Key in D@@@ NL.

Line number to be deleted


ii) Sequential delete
Key in D@@@@,@@@ NL.
Delete end line number
Delete start line number
e) Search
i) Search by line number
Key in L@@@@ NL.

Line number to be searched


ii) Search by symbol name
Key in L@@@@ SYMNAM NL.
Symbol name to be searched
Line number with which the search is to
be started
iii) Address search
Key in L@@@@ F0.1 NL.
Address to be searched
Line number with which the search is to
be started
(3) Message data (MESSAGE DATA LIST screen)
Message data are alarm and operator message data to be displayed by
using functional instruction DISPB (SUB 41).

***MESSAGE DATA LIST***


0001 A00.0 012345689XY Message data
0002 ABCD
Line number 0003
0004
0005
0006
0007
0008
0009 A00.1

Address

EDIT =

Fig. 4.3.1 (c) Message data list screen


Maximum 255 characters are entered to one address as message data.
Input message data every maximum 32 characters/line by dividing
them into 8 lines.

993
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

a) Input and alter from keyboard


Set message data in the alter format for both entry and alter. All
characters are settable so long as they can be keyed in from the
SYSTEM P series keyboard.
Key in message data every line in the following format.
A @@@ MESSAGEDATA1 NL.
Message data (maximum 32 characters)
Line number (maximum 3 digits)

A means alter.
b) Delete
Delete message data every line in the following format.
Key in D@@@ NL.

Line number to be deleted


c) Search
Search message data by address.
A@@.@ NL

Address of message data to be searched


(4) I/O module data (I/O MODULE DATA LIST screen)
I/O module data are used for determining addresses in a sequence
program of each I/O module.

***I/O MODULE DATA LIST***


ADDRESS GROUP BASE SLOT NAME
X000
X001
X002
X003



Fig. 4.3.1 (d) I/O module data list screen


a) Input and alter from keyboard
Set I/O module data in the following format when inputting or
altering them from the keyboard.
Key in I/O module data in the format of:
@@@ @ @ @@ @@@@@ NL
I/O module name
(maximum 5 digits)
Slot number (maximum 2 digits within
a range of 1 to 10)
Base number (1 digit within a range of 0 to 3)
Group number (1 digit within a range of 0 to 15)
Address (input X0, Y0, ...)

994
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

b) Delete
Delete I/O module data every address by specifying it as follows:
Key in @@@@ NL.
Address of I/O module data to be deleted
(input X0, Y0, ...)

CAUTION
1 If the same slot number is specified when the group and base numbers are equal to each
other, alarm No. 88 occurs.
2 If an output module is specified at an input address or an input module is specified at an
output address, alarm No. 87 occurs.
3 If a module is set doubly to a preset address, alarm No. 81 occurs.
Example) When two IO modules, b are set as shown in the following figure;

address group base slot name

a.

X000 2 0 1 FS08A
X001 2 0 1 FS08A
If an attempt is made to set a module to X014 like c., alarm No. 88 oc-
X002 2 0 1 FS08A
curs due to the reason in 1).
X003 2 0 1 FS08A
X004 2 0 1 FS08A
X005 2 0 1 FS08A
d.
X006 2 0 1 FS08A If an attempt is made to set an output module to X006 like d., alarm
No. 87 occurs due to the reason in 2).
X007 2 0 1 FS08A

X008 b.

X009 2 1 8 ID16C
X010 2 1 8 ID16C

X011 If an attempt is made to set input module ID32B to X006 like d., alarm
No. 81 occurs due to the reason in 3). In this case, this input module
X012 must be set after deleting a. and b. modules once.

X013
X014 c.
2 1 8 ID16C
X015 2 1 8 ID16C

The module names (FS08A, CT01A, etc.) used for input and output in common are out of the objects
of check in 1) and 2).

995
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.3.2 Input a sequence program from the keyboard.


Programming from Set the EDIT screen (LADDER PROGRAM LIST screen).
Keyboard Press menu number 1 <NL> on the menu screen, or press <R0> key on
the symbol or I/O module screen. Turn off all F keys at this time.
Key in IS0 <NL> (Insert Succession) to set the sequential insert mode,
and then, input a sequence program.
*IS MODE* is displayed at the lower right part of the screen. key in
desired instructions sequentially in the following format.

(Key in sequence) 1 IS0 <NL> (Sequential input start command)


*IS MODE* is displayed at the lower right part of the screen.
2 R X0.1 <NL>
3 W R1.1 <NL>
4 IE <NL> (Sequential input end command)
*IS MODE* display disappears from the lower right part of the
screen.

NOTE
1 Instructions to be keyed in are entered by abbreviated
symbols as shown above for the purpose of preventing a
keyin failure and improving the operability by reducing the
number of keyin times. It is also allowable to input these
instructions by using their full names, like RD X0.1 <NL>.
Table 4.3.2 shows the correspondence between
abbreviated symbols and full names.
2 No severe format checking is performed for mnemonic
program. For example, the following program may be
correct with mnemonic programming.
However this program cannot be displayed as ladder
diagram nor printed out on the printer.

Usually do not program as shown below:

Wrong program

996
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

Table 4.3.2 Keyboard input format and screen display format

Input format from keyboard Display format on screen


(Simple symbol) (Full name)
R X0. 1 RD X0. 1
RN X0. 2 RD. NOT X0. 2
RNS X0. 3 RD.NOT.STK X0. 3
W R0. 4 WRT R0. 4
WN R0. 5 WRT.NOT R0.5
O Y1. 0 OR Y1. 0
ON Y1. 1 OR.NOT Y1.1
OS OR. STK
AG2. 0 AND G2. 0
AN G2. 1 AND.NOT G2. 1
AS AND. STK
T 5 TMR 5
D F0 DEC F0
S 5 SUB 5
P 1234 (Parameter)

4.3.3 Correct a generated sequence program by alter operation.


Alter Set the EDIT screen (LADDER PROGRAM LIST screen) first and
display the generated source program. Turn off all F keys at this time.
a) Alter every instruction
Key in A@@@@@ R X0.1 NL
Instruction to be altered
Line number of the instruction to be altered
(maximum 5 digits)
A means alter.
b) Sequential alter
i) Key in AS@@@@@ NL (Alter Succession) to set the
sequential alter mode.
@@@@@: Line number to be sequentially altered (maximum
5 digits) AS MODE is displayed at the lower right part of the
screen.
ii) Instructions are sequentially altered starting with the Line
specified by @@@@@, each time the keyin operation is done
in the R X0.1 <NL> format.
iii) After sequential alter, key in AE <NL> (Alter End).
Example) Example of sequential alter of sequence program
For altering all step numbers 20 to 23;
(Key in sequence)
1 AS20 <NL> (Sequential alter start
command)
*AS MODE* is displayed at the
lower right part of screen.
00020 RD Y0.1 2 R Y0.1 <NL>

997
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

00021 WRT R0.1 3 W R0.1 <NL>


00022 RD F1.1 4 R Y1.2 <NL>
00023 WRT R1.1 5 W R1.2 <NL>
6 AE <NL> (Sequential alter end
command)
*AS MODE* display disappears
from the lower right part of the
screen.
c) Wiring change function
All of address used in Ladder Program is changed to a new
address independently of a command. Only bit address can be
changed.
Type in CA Address 1 Address 2 <NL>
(Symbol can not be changed)
A new address
A previous address to be changed
Abbreviation of CHANGE ALL
Example) CA R0.1 R1.2 <NL>
All R0.1 used in Ladder Program is changed
to R1.2.

CAUTION
If an address is specified which can not be changed to a new
address, an alarm 09 occurs when the specified line will be
changed. In that case, previous lines correctly changed to
that line can be acceptable.

998
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

00001 SUB1 00001 SUB1


00002 RD X0.1 00002 RD X1.7
00003 WRT R1.3 00003 WRT R1.2
00004 RD R1.2 00004 RD R1.2
00005 WRT R1.3 00005 WRT R1.3
00006 RD X0.1 00006 RD X1.7
00007 WRT R1.4 00007 WRT R1.4
00008 RD R1.3 00008 RD R1.2
00009 SUB 8 00009 SUB 8
00010 1111 00010 1111
00011 1111 00011 1111
00012 X0 00012 X0
This does not apply to byte address.
00013 R2 00013 R2
00014 SUB 2 00014 SUB 2
00015 SUB 48 00015 SUB 48

CA X0.1 X1.7 NL
EDIT= _ EDIT= _
Normal end of changing.
i. ii. iii.
00001 SUB1 00001 SUB1 00001 SUB1
00002 RD X0.1 00002 RD X0.1 00002 RD R1.2
00003 WRT R1.5 00003 WRT R1.5 00003 WRT R1.5
00004 RD R1.2 00004 RD X0.1 00004 RD R1.2
00005 WRT R1.3 00005 WRT R1.3 00005 WRT R1.3
00006 RD X0.1 00006 RD X0.1 00006 RD R1.2
00007 WRT R1.2 00007 WRTR1.2 00007 WRT R1.2
00008 RD R1.2 00008 RD R1.2 00008 RD R1.2
00009 SUB 8 00009 SUB 8 00009 SUB 8
00010 1111 00010 1111 00010 1111
00011 1111 00011 1111 00011 1111
00012 R1 00012 R1 00012 R1
00013 R2 00013 R2 00013 R2
00014 SUB 2 00014 SUB 2 00014 SUB 2
00015 SUB 48 00015 SUB 48 00015 SUB 48

EDIT= _ EDIT= _ EDIT= _

Abnormal end of Normal end of


changing. changing?
1 CA R1.2 X0.1 NL Alarm No. 09 2 CA X0.1 R1.2 NL

As shown above, an alarm No. 09 occurs when a ladder program i is


changed by an operation of 1 and a ladder program ii will be produced.

999
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

Then, it may be impossible to return a ladder program ii to a ladder


program i by an operation 2.
(Special use of wiring All address used in ladder program of specified line number of
change function) subsequent, is changed a new address independently of a command.
Only bit address can be changed.
Operate carefully with enough recognition of above.
C@@@@@ Address 1 Address 2 NL
(Symbol cannot be changed)
A new address
A previous address to be changed
Change start line number

Example) C7 R0.1 R1.2 <NL>


All R0.1 used in ladder program of 7th line or
subsequent, are changed to R1.2.

4.3.4 Insert a new program to the generated sequence program.


Insert Set the EDIT screen (LADDER PROGRAM LIST screen) first.
a) Insert every instruction

Key in I@@@@@ R X0.1 NL.


Instruction to be inserted
Line number just before the instruction to be
inserted (maximum 5 digits)
I means insert.

b) Sequential insert
i) Key in IS@@@@@ <NL> (Insert Succession) to set the
sequential insert mode, and *IS MODE* is displayed at the lower
right part of the screen.
@@@@@:Line number just before the instruction to be inserted
(maximum 5 digits)
ii) Instructions are sequentially inserted starting with the line next
to the line specified by @@@@@, each time the keyin
operation is done in the R X0.1 NL format.
iii) After sequential insert, key in IE <NL> (Insert End).
Example) Sequential insert of a sequence program
For inserting multiple instructions after step number
20
(Key in sequence)
1 IS20 <NL> (Sequential insert start
command)
*IS MODE* is displayed at the
lower right part of screen.

1000
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

00020 RD Y200.0 2 R.S R200.1 <NL>


00021 WRT R300.7 3 R.S R200.2 <NL>
4 R 5 <NL>
5 P 9 <NL>
6 IE <NL> (Sequential insert end
command)
*IS MODE* display disappears
from the lower right part of the
screen.

4.3.5 i) Delete every instruction


Delete Key in D@@@@@ NL.
Line number to be deleted
(maximum 5 digits)
D means delete.
ii) Sequential delete
Key in D@@@@@,@@@@@ NL.
Line number to complete delete
(maximum 5 digits)
Line number to start delete

4.3.6 Search a sequence number by a line number or instruction


Location Search i) Search by line number
Key in L@@@@@ NL.
Line number to be searched
(maximum 5 digits)
L means location search.
ii) Search by instruction (Search by address)
Key in L@@@@@ R X0.1 NL.
Instruction to be searched
Line number with which the search is to be started

CAUTION
Input data after changing the symbol display into address
display by passing R1 key, if the address of the instruction
to be searched is defined by a symbol and displayed by the
symbol.

1001
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

iii) Search by instruction (Search by symbol)


Key in L@@@@@ R ACT NL.
Instruction to be searched
(ACT: Symbol name)
Line number with which the search is to be started

CAUTION
This search applies to such a case as the address of the
instruction to be searched is defined by a symbol and the
symbol is displayed.

iv) Search by the bit address or its symbol name


The specified address (only bit address) or its symbol name is
searched from the specified line number independently of a
command.
Type in L@@@@ ????? NL.
Bit address or its symbol name
Search start line number

Example) L1 R1.0 NL
Start searching bit address R1.0 from 1st line.
L7 SMB NL
Start searching symbol name SM BL defined at
bit address from 7th line.
v) Continuous search
A specified command, address (only bit address) or its symbol name
is searched from 2nd line displayed on the screen.
Type in L ????? NL.
Command, bit address or its symbol name
to be searched
Type in F NL.
FIND: Search the same command, bit address or its
symbol name as that searched just before,
from 2nd line displayed on the screen.

Example) L R R0.1 <NL>


Search the command RD R0.1 from 2nd line
displayed on the screen.
L R0.1 <NL>
Search the bit address R0.1 from 2nd line displayed
on the screen.
L SYMBOL <NL>
Search the symbol name SYMBOL defined at bit
address from 2nd line displayed on the screen.

1002
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.3.7 The ladder diagram can be displayed on the programmer function EDIT
Display of Ladder screen.
Diagram Set the screen to EDIT screen (LADDER PROGRAM LIST)
a) Turn on F4 key.
b) Depress <NL> key
The ladder diagram is displayed on the screen.
For displaying the sequence program in the mnemonic format from
the ladder diagram, turn off F4 key, and depress <NL> key.
The ladder diagram at an optional point can be displayed by the step
number search or instruction search method.
If a ladder diagram cannot be displayed on one screen, it can be
displayed by scrolling it leftward, rightward, upward, and downward
as shown in the following table.
c) Edition during LADDER diagram display
Sequence programs can be edited even on the LADDER diagram
screen display, (This function is convenience when sequence
programs are edited with seeing LADDER diagram print out list.)
From EDIT= in the LADDER diagram screen display, sequence
programs can be edited by the same operation as in editing programs
in the LADDER PROGRAM LIST screen.

Scroll direction Key

Left (Left ladder on screen is NL


displayed.) 4 *** LADDER DIAGRAM ***

Right (Right ladder on screen is 6 NL


displayed.) X0.0 X0.1 Y 0.0

X1.0 X1.1 Y 0.1
Upper (Upper ladder on the NL
screen is displayed.) 8

Lower (Lower ladder on the 2 NL


screen is displayed.) TMR 1
X2.0 R 40.7
Upper half page X2.1
R2 NL
EDIT=
Lower half page
R2 NL

Fig. 4.3.7 Ladder diagram display screen

1003
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

Example)

* LADDER DIAGRAM *

1 From EDIT= IN the left figure, key in as follows.


ISO NL
END1 R X1.0 NL
W Y1.0 NL
IE NL

Y0.0
X0.0 2 Press R0 key to display the LADDER PROGRAM
LIST screen.
Two lines RDX1.0 AND WRT Y1.0 are added before
SUB1 (END1).
END2

~ ~
3 When the LADDER diagram is displayed again, the
diagram after adding the above two lines is displayed.
EDIT=

4.3.8 Editing command explanation screen can be displayed from Ladder


Help Screen program edition screen. (LADDER PROGRAM LIST or LADDER
DIAGRAM)
key in H <NL> to display the following screen.

*** HELP LIST ***


(@@@@@=SEQUENCE NO.)
<INSERT>
I@@@@@ OPERATION CODE : INSERT
IS@@@@@ : INSERT SUCCESSION START
IE : INSERT SUCCESSION END
<ALTER>
A@@@@@ OPERATION CODE : ALTER
AS@@@@@ : ALTER SUCCESSION START
AE : ALTER SUCCESSION END
<DELETE>
D@@@@(,@@@@@) : DELETE (SUCCESSION END)
<LOCATION SEACH>
L@@@@@ : SEQUENCE NO. SEARCH
L@@@@@ OPERATION CODE : OPERATION CODE SEARCH
L@@@@@ <ADDRESS OR SYMBOL> : ADDRESS OR SYMBOL SEARCH
L OPERATION CODE : SEARCH FROM DISPLAY 2ND LINE
L <ADDRESS OR SYMBOL> : SEARCH FROM DISPLAY 2ND LINE
F : FIND FROM DISPLAY 2ND LINE
<CHANGE ALL ADDRESS>
CA ADDRESS1 ADDRESS2 :CHANGE ALL ADDRESS1 TO ADDRESS2

Key in <NL> to return it to ladder program editing screen.

4.3.9 Key is E <NL> (End) after editing a sequence program, and the EDIT
Editing end screen is reset to the menu screen.

1004
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.4
INPUT OF PROGRAM

4.4.1 Read source programs (parameters, titles,


Source Program symbols, ladders, messages, and I/O modules) from an input unit
designated by an F key on the menu screen, and load them into SYSTEM
P series memory.
(1) Paper tape format of source programs
Paper tape format of source programs is of ISO code. No EIA code
paper tape can be used.
a) Parameter date

Feed % @0 CR % CR Feed

b) Title date

Feed % @1 CR 1 MACHINE TOOL CR % CR Feed

c) Symbol date

Feed % @2 CR F0.1 SYMBOL COMMENT CR % CR Feed

d) Ladder program

Feed % @3 CR RD X0.1 CR WRT WORK01 CR % CR Feed

e) Message date

Feed % @4 CR A0.0 MESSAGE = 1 CR A24.7 MESSAGE = 24 CR %


WRT WORK01 CR

CR ~ Feed

f) I/O module date

Feed % @5 CR X 0 0 0 5 ID32C CR % CR Feed

1005
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

(2) Input method from PPR reader


1 Turn on F1 key.
2 Key in menu number 2 <NL>.
3 The screen is switched, and the entry of a source program is
started.
4 After the source program has been normally entered, the screen
is automatically reset to the programmer menu screen. If an error
was detected during entry, PART is displayed on the lower left
part of the screen. Check error contents, and key in E NL. The
screen is reset to the programmer menu screen.
(3) Entry method from floppy
1 Turn on F2 key.
2 Key in menu number 2 <NL>.
3 The following message is displayed at the lower part of the screen.
SET FD & KEY IN OK KILL OR NO
FD0=OK <DRIVE> <@NAME OR : NUMBER>
FD0=
Fig. 4.4.1 shows the menu screen in the floppy entry mode.
[Screen when source programs are input form floppy]

SET I/O KEY & KEY IN ONE OF THE FOLLOWING NO.S WHICH YOU WANT.

NO.ITEMS
01 EDIT LADDER PROGRAM.
02 INPUT LADDER PROGRAM FROM PTR OR FD.
03 INPUT ROM DATA FROM FD. PMCRAM OR ROM.
04 OUTPUT LADDER PROGRAM TO PTP. FD OR PRINTER.
05 OUTPUT ROM DATA TO FD. PMCRAM OR ROM.
06 COMPARE LADDER PROGRAM WITH PTR OR FD.
07 COMPARE ROM DATA WITH FD. PMCRAM OR ROM.
08 (UNUSED)
09 CLEAR OF TITLE. SYMBOL. LADDER OR MESSAGE DATA.
10 PARAMETER SET.
00 END EDIT & DISPLAY.
F1 : PTR (I) . F4 : GRP (O) SYMBOL =00.0KB SCAN TIMEOO8MS
F2 : FD (I) . F10 : EPRT (O) LADDER =00.0KB
F5 : PRT (O) MESSAGE=00.0KB
F6 : PTP (O)
F7 : FD (O) END SEQ.NO=00000
F8 : PMC (I/O) ERR SEQ.NO=00000
F9 : ROM (I/O) ERR BLOCK =00000
SET FD & KEY IN OK KILL OR NO
FD0 = OK @FILE NAME
<DRIVE><@NAME OR NUMBER>
NO.=
Example

Key in file names to be input from floppy as shown in the example.

Fig. 4.4.1 Floppy input menu screen


4 Insert the floppy into the disk, and enter the following data.
Characters in < > need not be keyed in.
OK @LADDER1 NL
File name (provisional file name)
5 The screen is switched, and the entry of source programs is started
from the floppy.

1006
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

6 The following procedure is the same as in 4.4.1 2) 4.


7 A file name is inputtable up to maximum 17 characters. All
characters on the SYSTEM P series keyboard are employable for
this entry. The kinds of capitals are not limited.
@ (at mark) shows a file name input identifier. Key in it just before
the file name as shown in example $$ without fail.

CAUTION
If sequence program instructions are sequentially entered
while a sequence program is loaded in the SYSTEM P
series memory, the instructions are entered into the
SYSTEM P series memory following the previously loaded
program. Clear SYSTEM P series memory, if a new program
is entered from the floppy. (see 4.7)
The SYSTEM P series memory is cleared by turning off the
SYSTEM P series power supply.

4.4.2 (1) Transfer of sequence program from the PMCSA1/SA2/SB/SC


ROM Format Program The created sequence program is transferred from the
PMCSA1/SA2/SB/SC.
First, connect the SYSTEM P Series and the CNC with a
Reader/Puncher interface cable. (Refer to Appendix 1 for details of
the cable.) For the method and location of connection, refer to the
section 3.2 Configuration devices and their connection. In the
following procedure, operations 1 to 6 are NC side operations.
The keys enclosed in [ ] are soft keys.
1 Pressing soft keys [SYSTEM] and [PMC] displays the PMC
screen. Steps 2 to 4 below must be performed when [I/O] is not
displayed on the PMC screen. For a 9inch CRT, press soft key
[NEXT] to check that [I/O] is not on the screen.
2 Pressing soft keys [PMCPRM] and [KEEPRL] on the PMC
screen displays the keep relay setting screen.
3 Set K17.1 to 1 on the keep relay setting screen.
4 Pressing soft key [RETURN] displays the PMC screen.
5 On the PMC screen, pressing soft key [I/O] displays the I/O
screen. For a 9inch CRT, press soft key [NEXT] before pressing
soft key [I/O].
6 Pressing soft key [EXEC] on the I/O screen puts the system in the
EXECUTING state.
7 Turn on the F8 key on the SYSTEM P series menu screen. (Turn
on the F12 key at the same time when the Clanguage program
is included.)
8 If the menu number 3 [NL] is keyed in, the message shown
below will be displayed. PMCSA1/SA2/SB/SC is not
displayed. Key in the type of ROM module to be used from now
on. (Refer to Note 1 when selecting ROM module B, C or D.)

1007
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

SELECT THE TYPE OF ROM MODULE ACCORDING


TO THE FOLLOWING NO.
ROM MODULE 0:A 1:B, 2:C, 3:D
NO.=
By means of the abovedescribed operations, the program
transfer is started. The transfer screen is displayed on the
SYSTEM P Series screen and the transfer counter counts. The
screen returns to the menu screen after the end of transfer.
(2) Input from a floppy disk
1 Turn on the F2 key. (Turn on the F12 key at the same time when
the C language program is included.)
2 If the menu number 3 [NL] is keyed in, the message shown
below will be displayed. PMCSA1/SA2/SB/SC is not
displayed. Key in the type of ROM module to be used from now
on. (Refer to Note 1 when selecting ROM module B, C or D.)
SELECT THE TYPE OF ROM MODULE ACCORDING
TO THE FOLLOWING NO.
ROM MODULE 0:A 1:B, 2:C, 3:D
NO.=
3 The following message is displayed at the lower left part of the
screen.
SET FD & KEY IN OK,KILL OR NO
FD=OK <@FILE NAME>
FD0=OK <DRIVE><@NAME OR : NUMBER>
FD0=
4 Insert the floppy into the disk and enter the following data
5 OK @LADDER2 [NL]
File name
6 The screen is switched and the ROM format program is started
from the floppy disk.
7 After reading is ended, the screen is automatically changed to the
program menu screen if no problem occurs. When an error is
detected during reading, PART = is displayed on the left lower
part of the screen. Check the error and key in E [NL] to return
the screen to the program menu screen.
(3) Method of inputting from the FA writer and PMC writer
1 Check the setting of the ROM writer. (See Section 3.4, Setting
of I/O Device.)
2 Put the FA Writer in the REMOTE mode by the
[REMOTE/LOCAL] key before using it.
3 Turn on the F9 key. (Turn on the F12 key at the same time when
the C language program is included.)
4 If the menu number 3 <NL> is keyed in, the message shown
below will be displayed. PMCSA1/SA2/SB/SC is not
displayed. Key in the type of ROM module to be used from now
on. (Refer to Note 1 when selecting ROM module B, C or D.)
SELECT THE TYPE OF ROM MODULE ACCORDING
TO THE FOLLOWING NO.
ROM MODULE 0:A 1:B, 2:C, 3:D
NO.=

1008
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

5 The screen is switched and the message shown below is


displayed.
SET EPROM OR ROM MODULE & KEY IN OK OR
NO
KEY IN=
6 Check the above message. For the PMCSA1/SA2/SB, insert the
EPROM for the PMC into the FA Writer or PMC Writer. For the
PMCRC, insert the ROM module for the PMC into the FA
Writer or PMC Writer. Note, however, that ROM modules are not
available with the PMC Writer.
7 Key in OK <NL> or NO <NL>.
When OK <NL> is keyed in, the sequence program written into
the EPROM and ROM module for PMC is entered into PG
memory.
The screen returns to the menu screen if it ends with no problems
occurring.
When NO <NL> is keyed in, the screen returns to the menu
screen.

CAUTION
When using the SYSTEM P Mate, if ROM module B, C or
D is selected, overlay occurs. When cassette B or C is
selected, set the work floppy disk for external memory in
drive 1.

1009
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.5
OUTPUT OF
PROGRAM

4.5.1 By selecting 04 <NL> (OUTPUT LADDER PROGRAM) from menu


no.4, the following detail menu is displayed.
Source Program

SET I/O KEY & KEY IN ONE OF THE FOLLOWING NO.S WHICH YOU WANT.

NO. ITEMS
01 OUTPUT ALL DATA.
02 OUTPUT SYSTEM PARAMETER.
03 OUTPUT TITLE DATA
04 OUTPUT SYMBOL DATA.
05 OUTPUT MESSAGE DATA.
06 OUTPUT I/O MODUL DATA.
07 OUTPUT LADDER PROGRAM (MNEMONIC).
08 OUTPUT LADDER DIAGRAM (ONLY FANUC PRINTER).
09 OUTPUT CROSS REFERENCE (SEQUENCE NO.)
00 END
F5 : PRT (O) , F10 : FANUC PRINTER (O)
F6 : PTP (O) , F13 : CROSS REFERENCE (NO.8)
F7 : FD (O)

NO. =

Select a desired data and device from the above details menu screen by
combining the menu numbers and F keys.
(1) OUTPUT ALL DATA
All data of system parameters, titles, symbols, messages, I/O
modules and ladder programs (source format) are output to a device
specified by an F key.
Turn on an F key corresponding to the device to be output, and key
in detail menu number 01 <NL>.
If F10 key is turned on, all data are output to the FANUC printer
(external printer) and the ladder diagram is output last. If F13 key is
turned on furthermore, the ladder diagram is output with a cross
reference.
(2) OUTPUT SYSTEM PARAMETER
System parameter data are output to a device specified by an F key.
Turn on an F key corresponding to the device to be output, and key
in detail menu number 02 <NL>.
(3) OUTPUT TITLE, DATA
Title data are output to device specified by an F key.
Turn on an F key corresponding to a device to be output, and key in
detail menu No. 03 <NL>.
(4) OUTPUT SYMBOL DATA
Symbol data are output to device specified by an F key.
Turn on an F key corresponding to a device to be output and key in
detail menu number 04 <NL>.
The screen is switched and the following display appears.
OUTPUT = L@@@@ (,@@@@)
OUTPUT =_
Specify the output range by line numbers as follows.

1010
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

Example)
Key in L1, 100 NL
Output end liner number (If this parameter is
omitted, data are output to the last one.)
Output start line number
(5) OUTPUT MESSAGE DATA
Message data are output to a device specified by an F key.
Turn on an F key corresponding to a device to be output, and key in
detail menu number 05 <NL>.
The screen is switched and the following display appears.
OUTPUT = A@@.@ (,@@.@)
OUTPUT =_
Specify the output range by addresses as follows.
Example)
Key in A1.0,10.1
Output end address (If this parameter is
omitted, data are output to the last one.)
Output start address
(6) OUTPUT I/O MODULE DATA
I/O module data are output to a device specified by an F key.
Turn on an F key corresponding to a device to be output, and key in
detail menu number 06 <NL>.
(7) OUTPUT LADDER PROGRAM (MNEMONIC)
Ladder program (source format) data are output to a device specified
by an F key.
Turn on an F key corresponding to a device to be output, and key in
detail menu number 07 <NL>.
The screen is switched and the following display appears.
OUTPUT = L@@@@ (,@@@@)
OUTPUT =_
Specify the output range by line numbers as follows.
Example)
Key in L1,100 NL
Output end line number (If this parameter is
omitted, data are output to the last one.)
Output start line number
(8) OUTPUT LADDER DIAGRAM (ONLY FANUC PRINTER)
A ladder diagram is output to the FANUC printer (external printer).
Key in detail menu number 08 <NL>, and then, turn on F10 key.
Turn on F13 key furthermore, if it is desired to output the ladder
diagram with a cross reference.
The screen is switched and the following display appears.
OUTPUT = L@@@@ (,@@@@)
OUTPUT =_
Specify the output range by line numbers as follows.
(Partial output is also possible.)

1011
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

Example)
Key in L1,100 <NL>
Output end line number (If this parameter is
omitted, data are output to the last one.)
Output start line number

ITEMS

* ALL ADDRESS ALL


* HEAD CHARACTER G
* ADDRESS G14.6
* ADDRESS TO ADDRESS G14.6,R142.5
* ADDRESS TO END G14.6END

* END ; PUSH NL KEY

ADDR=

CAUTION
D It takes time more or less from the end of operation on end
to the start of printer operation when outputting the
LADDER diagram with cross reference. (EXECUTING is
displayed on the screen.)
This time depends upon the size and complexity of
sequence programs. The cross reference is displayed by
the page number and the line number of the LADDER
diagram every contact.
See Appendix printout example.
D If R1 key is pressed when each data is being output to the
FANUC printer (External printer), the output is cancelled.

(9) OUTPUT CROSS REFERENCE (SEQUENCE NO)


Addresses (symbols, comments) are printed with cross reference
Nos. by FANUC external PRINTER.
These Nos. correspond to the Mnemonic format list (screen) or
Ladder diagram (RD command line number).
Key in above detailed memo No. 09 <NL> and turn F10 key on. The
screen changes to display the key in example and ADDR= as below.
Key in addresses to be output according to examples.
Key in example Address to be output
ALL ALL <NL> All addresses (G,F,Y,X,A,R,T,K,C,D
in order)
Address initial R <NL> All address with the specified initial
Bit address X1.0<NL> Only bit address specified address
Byte address R58 <NL> Bit 0 7 of specified
Address range specification F8.0, X7.2<NL> Specified addresses in order of
G,F,Y,X,A,R,T,K, C,D
X0.2END<NL> All address after specified address

1012
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

*** CROSS REFERENCE LIST ***


PAGE=1
ADDRESS SYMBOL COMMENT DATA

G0000.0 *IT
653
G0000.1 *CST
653
G0000.4 *ESP
22 568 901 912 1177 1189 1288 2800
G0000.5 *SP
45 2802
G0000.7 ERS
3435 3512
G0001.0 *AIT
656

NOTE
1 When the same address performs double writing,*
MULTIPLE COIL USED * is displayed.
2 If the F10 key is set to OFF and output performed, the cross
reference table is displayed on the screen.

4.5.2 A 12inch chart is also applicable to the FANUC printer (external


printer).
Paper Command
(The standard chart size is 11 inches.) Enter the command for changing
the chart by the following operation.
(1) Press [R3] key from the R key menu screen.
(2) REQUEST= is displayed at the lower left part of the screen.
(3) Key in PAPER <NL>.
(4) The following message is displayed at the lower left part of the screen.
KEY IN NUMBER OF PAPER LENGTH
EXAMPLE 11INCH;0,12INCH;1.
LINE NUM.=
(5) Key in 0 <NL> for 11inch chart, or 1 <NL> for 12inch chart.

1013
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.5.3 (1) Transfer of sequence program into PMCSA1/SA2/SB/SC


ROM Format Program A generated sequence program is transferred into
PMCSA1/SA2/SB/SC.
Connect SYSTEM P series to CNC by using a Reader/Puncher
interface cable. (For this cable, see Appendix 1.) for the connection
method and places, see Section 3.2.
Steps 1 to 6 show the operation on the CNC side.
1 Pressing soft keys <SYSTEM> and [PMC] displays the PMC
screen. Steps 2 to 4 below must be performed when [I/O] is not
displayed on the PMC screen. For a 9inch CRT, press soft key
[NEXT] to check that [I/O] is not on the screen.
2 Pressing soft keys [PMCPRM] and [KEEPRL] on the PMC
screen displays the keep relay setting screen.
3 Set K17.1 to 1 on the keep relay setting screen.
4 Pressing soft key [RETURN] displays the PMC screen.
5 On the PMC screen, pressing soft key [I/O] displays the I/O
screen. For a 9inch CRT, press soft key [NEXT] before pressing
soft key [I/O].
6 Pressing soft key [EXEC] on the I/O screen puts the system in the
EXECUTING state.
7 Turn on F8 key from the SYSTEM P series menu screen. (Also
turn on F12 key when the C language program is included.)
8 Key in menu number 5 <NL>.
Now, the program transfer is started.
In SYSTEM P series, the transfer screen is displayed and the
transfer counter is counted up. After transfer, the screen is reset
to menu screen. In CNC screen, the COUNTER display is
counted up.
*Procedure when a i) When an alarm 31 occurs on SYSTEM P series screen;
program cannot be Cause 1 : Reader/Puncher interface cable is defective.
transferred from Remedy : Use the specified cable.
SYSTEM P series to RAM Cause 2 : Reader/Puncher interface connector is not
connected to correct channel SYSTEM P series.
of PMC Remedy : Connect the connector correctly.
ii) When the transfer counter of SYSTEM P series screen is
counted up and normally terminated, but data are not
transferred to the PMC RAM correctly;
Cause 1 : Reader/Puncher interface connector is not
connected to CNC.
Remedy : Connect it correctly.
Cause 2 : CNC screen is not set to I/O of PMC screen.
Remedy : Set the I/O screen by the soft key.
Cause 3 : An error occurs in ACI channel due to a certain
cause.
Remedy : Turn off the power supply once, and turn it on
again.

1014
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

(2) Output method to floppy


1 Turn on F7 key. (Also turn on F12 key when the C language
program is included.)
2 Set the floppy to the disk.
3 Key in menu number 5 <NL>.
4 The screen is switched and the following message is displayed:
SET FD & KEY IN OK,KILL OR NO.
FD0= OK <INT OR ADD><P OR NP,></DATE,>
<DRIVE>@NAME
FD0 =
When loading data starting with the start of the floppy, specify
INT. When loading data after the loaded files, specify ADD. After
outputting all data, the screen is reset to the program menu screen.
The menu screen is also reset by keying in NO <NL>.
(3) Method of outputting data to FA writer or PMC writer (EPROM for
PMC/ROM module write)
1 Check the setting of the ROM writer. (See Section 3.4, Setting
of I/O Device.)
2 Put the FA writer in the REMOTE mode by the
[REMOTE/LOCAL] key before using it.
3 Turn on F9 key. (Turn on F12 key when the C language program
is included.)
4 Key in menu number 5 NL.
5 The screen is switched to the title screen, and the following
message is displayed.
SET EPROM OR ROM MODULE & KEY IN OK OR
NO.
KEY IN =
Check the above message. For the PMCSA1/SA2/SB, insert the
EPROM for the PMC into the FA Writer or PMC Writer. For the
PMCRC, insert the ROM module for the PMC into the FA
Writer or PMC Writer. Note, however, that ROM modules are not
available with the PMC Writer.
6 Key in OK <NL> or NO <NL>.
When OK <NL> is keyed in, data are output from the SYSTEM
P series memory to the EPROM for PMC or ROM module.
After normal end, the screen is reset to the menu screen.

1015
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

*** TRANSFER ROM DATA TO PMC WRITER ***

01 MACHINE TOOL BUILDER NAME


02 MACHINE TOOL NAME
03 PMC & NC NAME
04 PMC PROGRAM NO
05 EDITION NO
06 PROGRAM DRAWING NO
07 DATE OF PROGRAMING
08 PROGRAM DESIGNED BY
09 ROM WRITTEN BY
10 REMARKS

PMC CONTROL PROGRAM SERIES : 4061 EDITION :01

MEMORY USED : 00.0 KBYT SCAN TIME : 008 MSEC

SET EPROM OR ROM MODULE & KEY IN OK OR NO


KEY IN =

*** TRANSFER ROM DATA TO PMC WRITER ***

01 MACHINE TOOL BUILDER NAME


02 MACHINE TOOL NAME
03 PMC & NC NAME
04 PMC PROGRAM NO
05 EDITION NO
06 PROGRAM DRAWING NO
07 DATE OF PROGRAMING
08 PROGRAM DESIGNED BY
09 ROM WRITTEN BY
10 REMARKS

PMC CONTROL PROGRAM SERIES : 4061 EDITION :01


MEMORY USED : 00.0 KBYT SCAN TIME : 008 MSEC
Display mode
BLANK : Blank check
MODE=BLANK PROGRAM : Write
ROML=10 ROMH=EF MEM FF AD=000000 VERIFY : Compare
ALARM=083

OUTPUT= Error number

Enter E NL, and restart from menu.

1016
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.6
COLLATION OF
PROGRAM

4.6.1 Enter source programs from the designated input unit, and compare them.
The operation method is the same as source program entry, except that 6
Collation of Source
shall be designated as the menu number.
Programs
(1) Comparison with PTR
1 Turn on F1 key.
2 Key in menu number 6 NL.
(2) Comparison with FD
1 Turn on F2 key.
2 Key in menu number 6 <NL>.
3 The screen is switched, and the following message is displayed.
SET FD & KEY IN OK, KILL OR NO,
FD0=OK<DRIVE> <@NAME OR : NUMBER>
FD0=
Specify the file name to be compared.
After normal end, the screen is automatically reset to the menu screen.
Also, this menu screen is reset by keying in KILL

4.6.2 Compare ROM format program by reading it from the specified input
device. The operation method is the same as in ROM format program
ROM Format Program
input, except that menu number 7 is specified.
(1) Comparison with FD
1 Turn on F2 key.
2 Key in menu number 7 <NL>.
3 The following operation is the same as in 4.6.1 2) 3 and later.
(2) Comparison with PMCRAM
Display the I/O of PMC screen on the CRT/MDI before executing the
following operation.
1 Turn on F8 key.
2 Key in menu number 7 <NL>.
Note when comparing PG and PMCRAM : The comparison
between PG and PMCRAM should be performed immediately
after the data transfer. (When the comparison is made after the output
of ROM format data, the parity portion of data may become error.)
(3) Comparison with EPROM for PMC and ROM module
1 Turn on F9 key.
2 Key in menu number 7 <NL>.
The screen is switched, and the comparison of ROM program is
started. After normal end, the screen is automatically reset to the
menu screen.

1017
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.7 Delete ladder programs, symbols, message, titles, and I/O module data
being loaded into SYSTEM P series memory according to the following
DELETION OF procedure.
PROGRAMS
1 Put the screen to menu screen.
2 Key in menu No. 9 <NL>.
3 The screen is switched, and the following message is displayed at the
lower left part of the screen. See Fig. 4.7.
KEY IN 1,2,3,4 OR 5 OR NO
CLEAR/KEEP =
4 Key in data number of the data to be deleted or key in NO <NL>,
if it is not desired to delete any data. After processing, the screen is
automatically reset to the programmer menu screen.

KEY IN ONE OF THE FOLLOWING NO.S WHICH YOU WANT TO CLEAR DATA

NO. ITEMS
01 TITLE DATA
02 SYMBOL DATA
03 LADDER DATA
04 MESSAGE DATA
05 I/O MODULE DATA
06 ALL DATA CLEAR

KEY IN 1. 2. 3. 4. 5 OR 6 OR NO
CLEAR/KEEP =

Fig. 4.7 Delection of sepuence programs


Example)
i) When all title data are to be deleted;
Key in 1 <NL>.
ii) When all symbol data are to be deleted;
Key in 2 <NL>.
iii) When all ladder programs are to be deleted;
Key in 3 <NL>.
iv) When all message data are to be deleted;
Key in 4 <NL>.
v) When I/O module data are to be deleted;
Key in 5 <NL>.
vi) When all titles, symbols, ladders, messages and I/O module data
are to be deleted;
Key in 6 <NL>.
vii) When no data are to be deleted;
Key in NO <NL>.

1018
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.8 Key in <NL> alone at the menu screen to display the R key menu screen.
Key in R3 at the R screen, and the display REQUEST= will appear at
SPECIAL USES OF bottom left of the screen, making key inputs possible. Key in <NL> on
THE R3 KEY this screen to return to the R key menu screen.
R3 executes a large number of processings. For the FANUC LADDER
system, however, note the following two points:
(1) Floppy file name output
1 Press R3 key at the R key menu screen.
2 This will change the screen contents, displaying REQUEST= at
its left bottom.
3 Key in FDLIST <NL>.
4 The file name will appear on the CRT display. To print out the file
name, turn on the F5 (printer) key in advance.
(2) Change of I/O devices (for output to a printer other than that of PPR)
1 Key in IO PRT, CN3, F5 <NL> while the screen displays
REQUEST=. When the F5 key has been turned on in advance,
the data is printed on the printer connected to connector CN3 on
the SYSTEM P series rear side.

1019
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.9
DIRECT EDITING BY
LADDER DIAGRAM

4.9.1 Using the PG Mate/Mark II software keys (in the case of PG Mate, the
Outline F keys), sequence program creation and editing can be performed directly
by the ladder diagram.
In the following explanation, [PG Mate] is called [Mate] and [PG Mark
II] is called [Mark II].
When it is possible to use this function, in the R key menu screen
R1: EDIT
is displayed. (In systems where [UNUSED] is displayed, it cannot be
used.)
The following items are present in the edit function.
D Ladder diagram direct editing by software key and cursor (input,
addition, deletion and substitution)
D Copying, moving and deletion of multiple lines of the ladder
D Optional relay and coil reference
D Comment display on ladder diagram

4.9.2 (1) This function operates only when the PG Mate main unit is version
04 and later. (When the power supply is turned on, it is displayed in
Limitations in SYSTEM the lower right part of the initial screen.)
P Mate (2) The function keys <F keys> are used instead of the soft keys (PG
Mark II). In the description that follows, an explanation for the soft
keys (PG Mark II) is given. When PG Mate is used, operate with
the function keys. At this time, in order to make the F key respond
and display the screen bottom line, the F key lamp illuminates to
correspond to those items displayed with shaded characters on the
screen.

4.9.3 The program menu appears in order to operate this function.


Selection of Program The program menu is displayed when the <R1> key is pressed from the
Menu by Soft Keys R menu screen. The program menu is displayed above the soft keys (in
the case of PG Mate, the function keys) as shown in the screen below,
and gives significance to the keys.
(1) Keyboard
Refer to Section 3.3 SYSTEM P keyboard.
(2) Relationship betweeen program menus and soft keys
The relationship between the program menus and the soft keys is
shown in the following for each function. These menus are changed
by pressing the related keys. For menu contents, refer to the
explanations described later. Utilize this figure when operating.

1020
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

R0 : PROGRAMMER
R1 : EDIT
R2 : UNUSED
R3 : REQUEST
Press the <R1> key

R keys menu screen

FUNCTN or or COMAND

[ COMAND ]

[ COMAND ]

INSNET DELNET INSERT ADRESS SEARCH COPY MOVE

1 2 3 4 5

1 [ DELNET ]

EXEC CANCEL SEARCH CDOWN CUP

2 [ INSERT ]

INSNET INSLIN INSELM

3 [ ADRESS ]

INSNET DELNET INSERT SYMBOL SEARCH COPY MOVE

4 [ SEARCH ]

TOP BOTTOM SRCH WSRCH NSRCH FSRCH CDOWN CUP

5 [ COPY/MOVE ]

UNTIL CANCEL SEARCH CDOWN CUP

TO CANCEL SEARCH CDOWN CUP

1021
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.9.4 In order to input the sequence program, press the <R1> key from the R
Sequence Program key menu. The soft key menu program is displayed, and in the case that
the sequence program has not yet been input, only the left and right
Input vertical lines of the ladder diagram are displayed on the screen.
Start inputting a program with the screen in this state.
Input a ladder diagram program by moving the cursor to the desired input
position using the cursor key.
The following description shows an example of the input of a program of
basic instruction and a program of functional instruction.
(1) Basic instruction program input

R0.1 R10.2 R1.7 R20.2

X2.4

1 Press the soft key [ ] after moving the cursor to the start
position.
Symbol [ ] is input at the cursor position and
HORIZONTAL LINE ILLEGAL is displayed at the lower right
part of the screen. This is a cautionary message which shows that
the ladder diagram horizontal line is not yet completely created.
Input the continuation address and bit data.
2 Press the <NL> key after inputting R0.1 using the keyboard. The
address is set on the contact and the cursor shifts rightward.
3 Input A contact with address R10.2 by the above methods 1 and
2.
4 Input B contact R1.7.
Press the soft key [ ], input address R1.7, and then press the
<NL> key. The address is set on the B contact and the cursor shifts
rightward.
5 Press software key [ ] with the cursor position unchanged.
A right horizontal line is automatically drawn, and a relay coil
symbol is entered near the right vertical line.
6 Press the <NL> key after inputting address R20.2.
The cursor automatically shifts to the input start position of the
next line.
7 Next, input the OR condition.
Press the soft key [ ], input address X2.4, and then press
the <NL> key. The address is set on the B contact and the cursor
shifts rightward.

1022
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

8 Press the soft key [ ] to input a horizontal line


When inputting the horizontal bar key [ ], by keying in a
numerical value and pressing this bar key, a horizontal line for the
frequency will be drawn. However, this horizontal line will not
be drawn over the LINE.
9 Because the upper right line OR is necessary, press the soft key
[ ] and input the upper right vertical line to end.

NOTE
1 When the ladder program displayed on the screen is incomplete (when, for example, addresses
have not been entered) or erroneous, the screen cannot be scrolled even when a page key is
pressed. Before attempting to scroll the screen, therefore, ensure that the ladder program is
complete and errorfree.
2 Since 8 contacts + coil are specified to be inputtable per line from the screen, any more contacts
in excess of this amount cannot be input. However, this restriction does not apply to a sequence
program created with mnemonic format.
When a sequence program, transferred from the offline programmer to the PMC, exceeds the
length which can be displayed on a single line, the program is displayed using two or more lines,
linked with a continuation symbol.
This continuation symbol is not erasable by software key [].
3 Below is shown an example with an error net, or part of it, erased with no error display.

1 Case of multiple nets on 1 LINE

Net is repeated

Downward from the net is erased

2 Case of multiple WRT results in 1 NET difference as shown in the diagram below.

Section C is erased

1023
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

NOTE
3 Case of exceeding the highest rank WRT in 1 NET
B

A C

Section B is erased

(2) Case of functional instruction program input


To input a functional instruction, input the soft key [FUNCTN], and
then input the functional instruction name or SUB number.
Further, when inputting a functional instruction, after keying in the
functional instruction number, it does not matter if the [FUNCTN]
key is pressed.
When you can not remember the instruction name or SUB number,
the functional instruction table corresponding to the instruction
symbol and SUB number can be displayed on the screen.
The functional instruction table is automatically displayed after
inputting an incorrect instruction name or SUB number and then
pressing the [FUNCTN] key, or by pressing the [FUNCTN] key only
without inputting any other key.
In order to return from the functional instruction table to the original
ladder diagram, press the [FUNCTN] key.

ACT MOVE (1) (2) (3) (4)

(SUB 8)

Control condition Output address

Input address
Low rank 4 bit logic data

High rank 4 bit logic data

When inputting a functional instruction with this function, the functional


instruction parameters are input vertically as shown in the diagram below.

MOVE
(1)
(SUB 8) (2)

(3)
(4)

1024
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

1 Input a control condition.


Press soft key [ ], input the address and bit data, and then
press the <NL> key. The cursor shifts rightward.
2 Input an instruction
Press the soft key [FUNCTN], input SUB number 8, and then
press the <NL> key. A functional instruction diagram appears as
shown in the above figure.
3 Input an instruction parameter
Input the high rank 4 bit logic data of the first parameter, and then
press the <NL> key. The cursor automatically lowers
downwards. Input the three residual parameters in order.

4.9.5 The method of substituting a created sequence program is the same as that
described earlier in Section 4.9.4.
Substitution of
Sequence Programs Move the cursor to the program part you want to alter and input the change
data.

4.9.6 From the soft key program menu, press the soft key [COMAND] and
operate with the soft keys shown below.
Additions to Sequence
Programs When you want to end the program menu shown below, press the soft key
at the extreme left.

INSNET DELNET INSERT ADRESS SEARCH COPY MOVE

INSNET INSLIN INSELM

A sequence program is added in four ways on the ladder diagram as


described below.
(1) Case of adding a relay contact in the horizontal direction

When the addition is horizontal

Case of adding

Move the cursor to the position where you want to add, and input te
program by the method described in Section 4.9.4.

1025
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

When a vertical line influences the addition


Case of adding


Cursor

1 Move the cursor to the above position.


2 Press the soft key [ ] in order to erase the upper left vertical line.
The upper left line, vertical to the cursor disappears.
3 Press the soft key [ ] in order to produce an upper right line
vertical to the cursor. Then, press the soft key [ ]. Both
vertical and horizontal lines are created.
4 Shift the cursor to a line of contact addition position.
5 Press the soft key [ ] to add contacts.
(2) Adding a vertical line
For adding a vertical line as shown in the above diagram, the area to
be added is required. In order to produce this area, shift the entire part
after the part to be added by one line by moving the cursor to the
ladder diagram within the dotted line range (an optional part is
allowable) and then pressing the soft key [INSNET].
The lower ladder diagram shifts downward by one line, each time the
[INSNET] key is pressed thereby producing the area to which a line
is to be added.
If a surplus addition area remains unused after the addition processing
ends (for example, if an area corresponding to 3 lines has been
reserved when two lines have been added), there is no problem if the
area is left remaining.

Addition

1 Move the cursor to the ladder diagram bounded by a dotted line.


2 Press the soft key [INSNET].
3 Pressing the [INSNET] key without keying in numeric values will
cause one line to be inserted.

1026
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4 Pressing the [INSNET] key with keying in numeric values will


cause the line to be inserted the number of times specified by the
numeric value input.
5 After setting the cursor to a position to which you want to add,
press the soft key [ ]. After setting address data, press the
<NL> key. The cursor shifts rightward.
6 Press the shift key [ ] to create an OR circuit.
(3) Inserting the 1 NET sequence program LINE.
Space lines are inserted in units of 1 LINE.
1 Key in the number of lines you want to insert and press the
[INSLIN] key. The inputted number of lines will be inserted. (If
the number of lines to be inserted is not keyed in, but the
[INSLIN] key is pressed, one line will be inserted.)

a


Crusor


b

If the [INSLIN] key is pressed with the cursor in the above
position, the state shown in the diagram on the right will occur.
(4) Inserting the 1 NET sequence program elements
Elements are inserted in 1 element units.
1 Key in the number of elements you want to insert and press the
[INSELM] key. The inputted number of elements will be
inserted. If a number of elements prefixed by the character A
are keyed in and the [INSELM] key is pressed, the elements are
inserted after the cursor.
(If the number of elements to be inserted is not keyed in, but the
[INSELM] key is pressed, one element is inserted.)


a

Cursor

b


1027
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

If the [INSELM] key is pressed with the cursor in the position on


the left, the state shown in the diagram on the right will occur.


a

Cursor


b

If the character A is keyed in and the [INSELM] key is pressed
with the cursor in the position on the left, the state shown in the
diagram on the right will occur.

4.9.7 (1) For deleting part of a program, use the following three kinds of soft
keys and delete after setting the cursor to the unnecessary part.
Deleting a Sequence
[ ] : Deletion of horizontal lines, relay contacts coils, etc.
Program
[ ] : Deletion of upper left vertical line to the cursor
[ ] : Deletion of upper right vertical line to the cursor
(2) For the deletion of a program net (part corresponding to the section
from RD instruction to WRT instruction), use the [DELNET] key.
(3) Deleting multiple NETs in NET units

INSNET DELNET INSERT ADRESS SEARCH COPY MOVE

EXEC CANCEL SEARCH CDOWN CUP

1 Deletion
Move the cursor to the NET you want to delete and press the
[DELETE] key. The net you want to delete will be displayed in
red. (In the case of Mate, in reversal display.)
2 Deleting multiple nets
Move the cursor with the cursor DOWN key, [CDOWN] key, or
[SEARCH] key to display in red the NET you want to delete. (In
the case of Mate, in reversal display.) Further, key in a numerical
value and press the [CDOWN] key to move the cursor the
number of times specified by this value.
3 Execution . . . . . . Press the [EXEC] key
Cancellation . . . . Press the [CANCEL] key
4 If you already know the NET you want to delete, move the cursor
to the first NET, key in the number of NETs, and press the
[DELNET] key to omit steps 1 and 2.

1028
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.9.8 Search a sequence program by using the following soft keys.


Searching a Sequence (1) Soft key [TOP]
Program When this key is pressed, the start of the sequence program is
desplayed on the screen and the cursor also sifts to the program start
position.
(2) Soft key [BOTTOM]
When this key is pressed, the last of the sequence program is
displayed on the screen and the cursor also shifts to this program end
position.
(3) Soft key [SRCH]
In this search, you specify an address you want to search and it
searches the specified address from the program of the cursor part on
this screen to the last part of the program and displays the address on
the screen. There are two methods to specify the address you want
to search.
(a) Method of specifying the address by the cursor
Set the cursor to the relay contact part of the address you want to
search and press the soft key [SRCH].
The system searches the same address as the address specified by
the cursor from the cursor part of the program currently displayed
on the screen to the end of the program.
When the same address is found, the program part is displayed
on the screen, and the cursor shifts to that address part. If the same
address is not found as a result of this search, the cursor remains
in the same position.
When finishing, press the soft key on the extreme left.
(b) Method of specifying the address by input
Input the address you want to searcch by using address and
numeric keys, then press the soft key [SRCH].
The same address as specified is searched from the program of the
cursor part currently displayed on the screen to the last part of the
program.
When the same address is found, the program part is displayed
on the screen, and the cursor shifts to that address part.
If the same address is not found as a result of this search, an error
is displayed.
(4) Soft key [WSRCH]
This key specifies an address of the relay coil to be searched, and then
searches the relay coil of the specified address from the program at
the cursor part to the end of the program on this screen. Then, it
displays the relay coil on the screen.
Two methods are available to specify the address of the relay coil to
be searched.
(a) Method of specifying the address by cursor
Set the cursor to the relay contact of the relay coil to be searched,
and press the soft key [WSRCH].
The corresponding relay coil is searched from the program of the
cursor part to the end of the program.
When the relay coil is found, the program part is displayed on the
screen, and the cursor shifts to the relay coil.

1029
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

If no corresponding relay coil is found as a result of the search,


an error occurs.

INSNET DELNET INSERT ADRESS SEARCH COPY MOVE

TOP BOTTOM SRCH WSRCH NSRCH FSRCH CDOWN CUP

Y1.2


X2.0 R20.1 R6.4

R0.5
When you want to search the same
R5.0 X4.2 R20.2 address as specified here. Set the
cursor to this position and press the soft
key [SRCH].
R21.0 Y2.0


R20.1 R2.2


R0.4
The same address is searched and
the cursor shifts to this position.
R0.5 R10.5

(b) Method of specifying the address by input


Input the address of the relay coil to be searched by both address
and numeric keys, and then press the soft key [WSRCH].
The specified address relay coil is searched from the program of
the cursor part currently displayed on the screen to the end of the
program.
When the specified address relay coil is found, the program part
is displayed on the screen, and the cursor shifts to the relay coil.
If no relay coil is found as a result of the search, an error occurs.
(5) Soft key [NSRCH]
This displays the ladder with the specified NET number from the top
of the screen. If the number is not keyed in, but the [NSRCH] key
is pressed, the display is scrolled down by one NET.
(6) Soft key [SSRCH]
Key in the functional instruction name or number and press the
[SSRCH] key to start searching the functional instruction. When the
[SSRCH] key is pressed during execution of a functional
instruction, the functional instruction with the same number as this
instruction is searched.
(7) Searching with cursor keys (<> , <> )
D Key in the address or symbol and press the cursor to start searching
the NET No.
D Key in the NET NO. and press the cursor key to start searchng the
NET NO.

1030
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

D Key in the functional instruction name or functional instruction


number starting with S and press the cursor key to start searching
the functional instruction.
Example) Key in END1 or S1 and press the cursor to search
functional instruction END1.

4.9.9 The sequence program with multiple NETs is copied in units of NETs.
Specify the NET to be copied and specify the copy position with the
Copying a Sequence
cursor. When copying, the number of copies can also be specified.
Program
1 Copying
Move the cursor to the NET you want to copy and press the [COPY]
key. The NET you want to copy will be displayed in yellow (in the
case of Mate, in reversal display).
2 Copying multiple NETs
Move the cursor with the cursor UP/DOWN key, [CUP] key,
[CDOWN] key, or [SEARCH] key to display in yellow the NET to
be copied. (In the case of Mate, in reversal display.) Further, if you
in a numerical value and press the [CUP] or [CDOWN] key, you
can scroll up or down the screen by the number of times specified by
this value.
3 Setting the NET to be copied
Press the [UNTIL] key.
4 Specifying the copying address
Copying is performed by the [TO] key. At this time, the NET is
copied in the direction above the cursor. If the number of copies is
keyed in before the [TO] key is pressed, the NET is copied that
specified number of times.
5 Further, if the NET you want to copy is already known, if the cursor
is moved to the first NET and the number of NETs is keyed in, then
by pressing the [COPY] key, steps 1 to 3 can be omitted.

INSNET DELNET INSERT ADRESS SEARCH COPY MOVE

UNTIL CANCEL SEARCH CDOWN CUP

TO CANCEL SEARCH CDOWN CUP

CAUTION
An error NET cannot be copied.

1031
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.9.10 A sequence program with multiple NETS is moved in units of NETs.


Moving a Sequence Specify the NET to be moved and specify the move position with the
cursor. When moving, the number of moves can also be specified.
Program
1 Moving
Move the cursor to the NET you want to move and press the [MOVE]
key. The NET you want to move will be displayed in yellow. (In the
case of Mate, in reversal display.)
2 Moving multiple NETs
Move the cursor with the cursor UP/DOWN key, [CUP] key,
[CDOWN] key, or [SEARCH] key to display in yellow the NET to
be moved. (In the case of Mate, in reversal display.) Further, if you
key in a numerical value and press the [CUP] or [CDOWN] key,
you can scroll up or down the screen by the number of times specified
by this value.
3 Setting the NET to be moved
Press the [UNTIL] key.
4 Specifying the moving address
Moving is performed by the [TO] key. At this time, the NET is
moved in the direction above the cursor.
5 Further, if the NET you want to move is already known, if the cursor
is moved to the first NET and the number of NETs is keyed in, then
by pressing the [MOVE] key, steps 13 can be omitted.

INSNET DELNET INSERT ADRESS SEARCH COPY MOVE

UNTIL CANCEL SEARCH CDOWN CUP

TO CANCEL SEARCH CDOWN CUP

CAUTION
An error NET cannot be moved.

1032
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.9.11 (1) Symbol and comment data display


Symbol Data Display Symbol data and comment are displayed together with a ladder
diagram on the screen as follows.
When symbol data and comment are defined in signal addresses in the
program, the signal name and comment are displayed as shown in the
above diagram.
When converting the symbol and address display, press the shift key
[ADRESS or SYMBOL].
(2) Symbol input and search in the sequence program
When symbol data is defined in signal addresses in the sequence
program, input and reference can be performed by the symbols.
(Address and symbol are only different in operation.)
If neither symbol data nor comment is defined at an address, the
address is displayed as it is.

Signal name
(within 6
characters)

Comment
MA SPDALM X2.4 R2.2 Y4.3 ATCALM R100.1 MRDY (within 30
MACHINE characters)
READY
APCALM R5.4 MALM
MACHINE
ALARM

10 lines

R120.1 TIND D20.7 R52.1

APC

Signal name An address is displayed if a symbol is


(within 6 characters) not defined.

1033
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

4.9.12 The main function of each soft key can be directly selected from the
Compressed Input by [COMAND] key.
[COMAND] Key After keying in the characters shown below, press the [COMAND] key.
[ ] shows parts that can be omitted. Further, the n appearing after the
characters signifies that it is also posssible to input a numerical value. For
example, after keying in D2, pressing the [COMAND] key results in the
same operation as keying in 2 and pressing the [DELNET] key.
I [NSERT]
D [ELNET] [n ]
A [DRESS]
SY [MBOL]
S [EARCH]
C [OPY] [n ]
M [OVE] [n ]
n :numerical value
The creation and search of programs is performed by pressing the
software keys of the above menu.

NOTE
The software keys [ or ] and [ or ] are used to
create or delete the upper left vertical line or the upper right
vertical line on the ladder diagram. The solid line display of
the vertical line indicates creation; the dotted line display of
the vertical line indicates deletion. As to which menu will
appear above the software keys, is decided by the ladder
diagram form and the cursor position.

4.9.13 In the program menu shown below, press the extreme left software key.
Ending Edit of a
Sequence Program

FUNCTN or or COMAND

CAUTION
When an error NET exists, ERROR NET NO. is displayed
and you cannot end the edit. End after correcting the
erroneous NET.

1034
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.10
INPUT/OUTPUT OF
LADDER PROGRAM
WITH PG AND
FLOPPY
CASSETTE/FA CARD

4.10.1 The ladder program can be stored in or fetched out of a floppy cassette/FA
General card by connecting PG and floppy cassette adapter/FA card adapter by
using this function enables reading the program stored in a floppy
cassette/FA card by using PMC RAM into PG or reading the program
stored in a floppy cassette/FA card by using PG into PMC RAM. The
usable adapters are as follows:
D FANUC cassette adapter 3 (A13B0131B001)/cassette F1
(A87L00010038)
D FANUC floppy cassette adapter (A13B0150B001)/floppy cassette
(A87L00010039)
D FA card adapter (A13B0148B001)/FA card (A87B00010108)

4.10.2 When using the FANUC floppy cassette adapter/FA card adapter, change
Setting I/O Commands the settings of the input/output devices by the following IO commands.
1 Press the R3 key on the R key menu screen. REQUEST= is
displayed lower left on the screen, and keying in is permitted.
2 Key in IO BCA, CN2, F13, F14 [NL]. The floppy cassette
adapter/FA card adapter is assigned to channel 2.
3 To return the assignment to channel 2 to PMC WRITER, key in IO
AUX, CN2, F9 [NL].

4.10.3 1 Turn on F13 key.


Program Input (Turn on F12 too, when C language program is included.)
2 Key in the menu No. 3 [NL].
3 (For PMCSC only) Enter the type of a ROM module to be used.
(See the following note for selecting ROM module B or C.)
SELECT THE TYPE OF ROM MODULE ACCORDING TO THE
FOLLOWING NO.
ROM MODULE 0:A, 1:B, 2:C
No. =
4 The message is displayed lower left on the screen.
SET BC & KEY IN OK OR NO
BC = OK <FILE NO. OR NEXT>
BC =
5 Set the floppy cassette/FA card in the adapter, and enter the following
data.

1035
4. OPERATION PMC PROGRAMMER (SYSTEM P series) B61863E/14

6 OK 1 [NL] (specify file No.) or OK NEXT [NL] (read the next


file).
7 The screen changes, and reading the program from the floppy
cassette/FA card starts.
8 When the program reading ends normally, the screen will
automatically return to the programmer menu. If any error is detected
during the program reading, PART= is displayed lower left on the
screen. Check the error contents, and key in E [NL]. The screen
will return to the programmer menu.

CAUTION
When ROM module B or C is selected during use of
SYSTEM P Mate, the program is overlaid. In this case,
insert the work floppy disk for the external memory into drive
1.

4.10.4 1 Turn on F14 key.


Program Output (Turn on F12 too, when C language program is included.)
2 Key in the menu No. 5 [NL].
3 The message is displayed lower left on the screen.
SET BC & KEY IN OK OR NO
BC = OK <INT OR ADD OR FILE NO.>
BC =
4 Set the floppy cassette/FA card in the adapter, and enter the following
data.
5 OK INT [NL] (write at the floppy head),
OK ADD [NL] (write in the next file) or OK1 [NL] (specify file
No.).

CAUTION
When specifying file number, put the numbers in the
ascending order. If the file No. located at the middle of a
floppy disk is specified, the files after that will be deleted.

6 The screen changes, and writing the program into the floppy
cassette/FA card starts.
7 When the program writing ends normally, the screen will
automatically return to the programmer menu. If any error is detected
during the program reading, PART= is displayed lower left on the
screen. Check the error contents, and key in E [NL]. The screen
will return to the programmer menu.

1036
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 4. OPERATION

4.10.5 1 Turn on F13 key.


Program Collation (Turn on F12 too, when C language program is included.)
2 Key in the menu No. 7 [NL].
3 The following operations are the same as those after 3 in Program
input.

CAUTION
For the program which is output from PMCSA1/SA2/SB/SC
RAM board to the floppy cassette/FA card by specifying
LADDER of ALL, there is no problem in the input/collation. It
is impossible to make input/collation for the program which is
output by specifying PARAM.

1037
5. FILE EDITING FUNCTION PMC PROGRAMMER (SYSTEM P series) B61863E/14

5 FILE EDITING FUNCTION

1038
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 5. FILE EDITING FUNCTION

5.1 This function edits floppy disk data in the unit of file. When key in only
<NL> the menu screen of R key appears key in R3 key on the R key menu.
GENERAL REQUEST= will be displayed on the left below part of the screen to
show a keyin enable condition.

NOTE
The format for file designation is as follows:
[drive No.] @ file name
: file No.

The file attributes are as shown below.


(1) File number
(2) File name
(3) File creation date
(4) Identification of protection file (protect)
(5) File size
(6) Multivolume number
These file attributes are attached when writing data into floppy disk.
When writing, the next floppy disk set request message is displayed, so
specify date and protection file.

File editing command table


Name of Contents inputted from keyboard
Contents of jobs command (NL key is inputted at the end of a
(Instruction) command)
Display of file name, or file FDLIST FDLI [D, [P,] [S,] [F,]
size [L,] File designation

Change of file name, date, RENAME P ] [,/date]


etc. RENA file designation [,
[,@ new file name] NP

Deletion of file SCRATCH SCRA file designation


File area condensation CONDENSE COND [drive No.]
Copy of file REMOVE M
(This command is REMO [ ,] [file designation]
A
effective for SYSTEM P INT
series with 2floppy disk [, ] [, P ] [,/date]
ADD NP
unit.)
[,@ new. file name]

Set FD, and key in OK, KILL, or NO.


FD=OK <INT or ADD,> <P or NP,> </data>
<drive> <@name>
FD=_

1039
5. FILE EDITING FUNCTION PMC PROGRAMMER (SYSTEM P series) B61863E/14

Set the floppy disk and key in as follows.


OK INT. P , [/date] [drive] [@ file name]
ADD NP
NO
KILL

When reading, the following floppy set request message is displayed.


Set FD, and key in OK, KILL, or NO.
FD=OK <drive.> <@name or : nember>
FD=_

Set floppy disk and key in as follows.


OK [drive number] @ file name
: file number
NO
KILL

In file editing function, the above floppy disk set request message key
input parameter can also be used. Now, parameter used in common here
here has the following meaning. Specify OK, NO, KILL and instruct
the answer to the set request.
OK . . . . After instructing execution of read and write, specify
parameter.
NO . . . . Cancel read/write to floppy only.
KILL . . Cancel the specified process.
Parameters instructing details of read and write is as follows.

1040
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 5. FILE EDITING FUNCTION

Parameter Function Notes


INT When writing, write from the head of When omitted, it is regarded as
the floppy ADD. If INT is specified to
protection file, an error generaters.
ADD When writing, add after exising fie
P Prepare as protection file When omitted, it is regarded as NP.
Ready files can be changed by
NP Prepare as ordinary file RENAME command.
Date Specify file preparation date with 6 Blank when omitted.
numbers
Drive number Specify drive number 0 or 1 set with When omitted, it is regarded as 0.
read/write floppy disk. See Note).
0 ; Upper unit
1; Lower unit
@ File name Specify file name (Max. 17 Always specify when writing.
characters). When reading, the first When reading, if omitted, the file is
name corresponding to the valid.
specified names is vallid.
; File number When reading, specify the With the FDLIST command, file
necessary file number after the :. number and file name list can be
displayed.

CAUTION
When specifying drive number and file name or file number,
specify without separating, as follows.
Example) 0 @ ABC or 1 : 5

When displaying set request message, drive number is decided by the


system, and FD0= or FD1= is displayed, instead of the FD=
message, to check the drive (unit) to be used. If a drive number is specified
then, it will be ignored. (FD0 shows drive 0, and FD1, drive 1).

1041
5. FILE EDITING FUNCTION PMC PROGRAMMER (SYSTEM P series) B61863E/14

5.2 (1) General form of command


CONFIGURATION OF Operation Space Operand
COMMAND Command name or its _ List of one or more parameters delimited
abbreviated form by delimiter symbol , (comma).
(4 leading characters)

A command name consists of plural alphabetic characters, and it can


be abbreviated by four leading characters.
An operand consists of parameters peculiar to commands and
parameters specified in floppy disk mounting request message.
(2) Execution of operands and commands
If operands are fully designated, a command is executed without
displaying any floppy disk mounting request message.
However, a certain command may require many parameters. If these
parameters cannot be recalled, specify the command name only.
Necessary parameters are indicated in the floppy disk mounting
request message. Accordingly, parameters can be input from the
keyboard according to this display. The message may be displayed
twice separately according to commands. (Old and new names are
requested separately in RENAME command, for example.)

1042
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 5. FILE EDITING FUNCTION

5.3 This command displays the attributes of files in the floppy disk, such as
file name, file size, etc.
FDLIST COMMAND
FILE ATTRIBUTE a) Input format
DISPLAY [D,] [P,] [S,] [F,]
FDLIST
[L,]

@ file name
[Drive No.]
: file No.

b) Operand
D: Display of file creation date consisting of 6 characters
P: Identification display of protection files
S: Display of file size
F: Display of size of unoccupied area
L: Executes all display by parameters D, P, S, F.
@ file name Displays a file having the designated
file name or designated
: file No. file number only. If this designation
is omitted, all files are treated as
processing objects.

c) This command displays the information (attributes) on the floppy


disk files.
If no attribute to be displayed is designated, the file number, file
name, and multivolume number only are displayed. The following
example shows the display of all information (L designation)
NO. FILE NAME V. DATE SIZE P.
001 DATA1 830928 72 P
002 DATA2 831028 60
003 DATA3 831028 8 P
**** DELETED FILE **** 10
005 DATA4 901022 10 P
006 DATA5 901022 5
FILE USED AREA = 155
DELETED FILE AREA = 10
FREE AREA = 1019

NOTE
The numeric characters shown in SIZE, FILE USED AREA,
DELETED FILE AREA, and FREE AREA are displayed
assuming that 256 characters are 1.

1043
5. FILE EDITING FUNCTION PMC PROGRAMMER (SYSTEM P series) B61863E/14

5.4 This command designates a change of the file name, file creation date, and
the designation of protection file.
RENAME COMMAND
FILE ATTRIBUTE a) Input format
CHANGE @ file name P
RENAME [drive No.] [,/date] [@ new file name]
: file No. NP

Designation of file to be changed Designation of file to be changed


b) Function
File attributes are renewed when they are designated by operand
parameters. Attributes which are not designated are stored as they
are. Protection files can be cancelled, but neither dates nor file names
are changeable. The designation of protection files must be cancelled
once before changing their attributes.
If all operands are omitted, the system displays an input message to
request the designation of a file to be changed. When the file to be
changed is designated by keying operation, a message is displayed
to input attributes of the file to be changed by keying operation.
Designate new data.
If the file to be changed only is designated together with the
command, the system asks the file attributes to be changed.
(RENAME: 5 <NL>, for example)
Old attributes (B) and new attributes (A) are displayed by executing
this command as shown below, for example.
Example)
RENAME :3, @ NEWNAME <F11>NL>
RENA : 3,@NEWNAME
NO. FILE NAME V. DATE P.
B: 003 DATA3 901020
A: 003 NEWNAME 901020

1044
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 5. FILE EDITING FUNCTION

5.5 This command deletes files of floppy disk.


SCRATCH COMMAND a) Input format
DELETION OF @ file name
SCRATCH [drive No.]
FILES : file No.

b) Function
This command deletes the designated file. Even if the file name is
displayed by FDLIST, the file name is not displayed any longer. The
area occupied by the deleted file must be released by CONDENSE
command before writing new data into the area.

5.6 This command releases the deleted file area to be employable.


CONDENSE a) Input format
COMMAND CONDENSE [drive No.]
RELEASE OF b) Function
DELETED AREA The area occupied by the file deleted by SCRATCH command cannot
be employed for writing new data under that condition. By executing
this command, all unemployable areas can be released. Since it
takes time to execute this command, it is recommended to arrange
these areas when there are many files to be deleted and the residual
capacity of the floppy disk is small.

1045
5. FILE EDITING FUNCTION PMC PROGRAMMER (SYSTEM P series) B61863E/14

5.7 This command copies files to another floppy disk by using two floppy
disk units.
REMOVE COMMAND
a) Input format
FILE COPY
M input drive @ file name INT , P , [/date] , @ new file
REMOVE A, No. file No. ADD NP name

Input designation Output designation


Designation of
copying method
b) Operand
No. M,A designation:
Specified file is copied with specified file attributes.
M (manual):
Copies designated files one by one.
Floppy disk mounting request message is displayed every file to ask
if the file is to be copied or not. If input file is not designated, all files
becomes the object to be copied.
If new file name is not designated, input file name is produced.
Accordingly, the output designation of REMOVE command is
meaningless, because the request for output designation is performed
every file.
i) When a file name is designated as an input;
All coincident files having the designated length are treated as
processing objects. If @A is designated, for example, all files
starting with A are asked.
ii) When a file number is designated as an input;
Files from a file having the designated file number to the last file
are treated as processing objects.
A (auto):
All files conforming to the designated conditions are copied. The
output designation file name is meaningless. However, P, NP and /
date are designated to all copied files with new attributes.
i)
If the file name or file number is not designated by input
designation, all files of the input floppy disk are copied.
ii) If the file name or file number is designated in input designation,
processing is done in the same way as in M designation.
c) Function
This command copies floppy disk files to another floppy disk. Files
are output to a floppy disk opposite to the drive number (0, if omitted)
designated by input designation. These files are copied by the
following three methods.
i) Copy of one file only (Neither M nor A is designated.)
(Ex. 1) REMOVE : 3,P, @ NEW <NL>
In this example, the input/output designations are as
follows; Input designation : 3rd file of drive No.0 floppy
disk

1046
B61863E/14 PMC PROGRAMMER (SYSTEM P series) 5. FILE EDITING FUNCTION

Output designation : File name is NEW, drive No.1


floppy disk with protection
ii) The system asks every file to check if the file is to be copied or
not. (M designation)
(Ex. 2) REMOVE M,1 @ A <NL>
In this example, the system asks to copy or not every file
with file name starting with A of drive No.1 floppy
disk.
A change of attributes such as file name, date, and file
protection can be designated.
iii) All designated files are copied. (A designation)
(Ex. 3) REMOVE A,: 3, INT,/830920 <NL>
In this example, files with file name starting with A
and with file No.3 and later of drive No.0 floppy disk are
copied to drive No.1 floppy disk from the head of it with
designated date 830930. The copied file names cannot
be changed in this method.
When this command is executed, input file attributed (I) and output
file attributes (O) are displayed. The next display example shows the
execution of REMOVE A, 1 @TO, INT, P <NL>.
NO. FILE NAME V.DATE P.
I:001 T01 ZX 1. 100/40 830920
O:001 T01 ZX 1. 100/40 830920 P
I:002 T02 ZX 1. 150/50 830920
O:002 T02 ZX 1. 150/50 830920 P
I:003 T04 ZX 1. 100/50 830920
O:003 T04 ZX 1. 100/50 830920 P
I:004 T05 ZX 1. 20/50 830920
O:004 T05 ZX 1. 20/50 830920 P
If REMOVE command is only designated, key in operands according
to the request message. The following are general designation format
for file copy.
i) Without M, A designation (One file is copied.)
0 @ file name INT P
REMOVE , ,
1 : file No. ADD NP

[,/ date] [, @ new file name] <NL>


ii) With M designation (request message is displayed for each
objected file.)
0 @ file name
REMOVE M,
1 : file No

iii) With A designation (All subjected files are copied.)


0 @ file name INT P
REMOVE , ,
1 : file No. ADD NP

[,/ date] <NL>

1047
APPENDIX
A. ERROR CODES LIST
B61863E/14 APPENDIX (FOR FANUC LADDER PG)

A ERROR CODES LIST (FOR FANUC LADDER PG)

Error codes Details of errors


01 Sequence program area over
02 No. of divisions has exceeded 99.
03 High level program time over
05 An error block was detected.
07 No designated step number is found.
08 An undefined instruction was specified.
09 An undefined address was specified.
10 Parameter data error
11 An address was employed in OR.STK and AND.STK.
12 An unemployable subroutine number was specified.
13 An unemployable timer number was specified.
14 A comparison error occurred.
15 A jump instruction was specified, exceeding END1 and END2.
16 A common instruction was specified, exceeding END1 and END2.
17 An instruction format error
18 An attempt was made to delete a parameter.
19 An attempt was made to add a parameter.
20 An erroneous system parameter data
21 A parameter was specified in a mode other than subroutine mode.
24 END2 is not specified.
25 WRT instruction is not specified in WRT instruction subroutine.
27 END1 is not specified.
29 A data sent from PMCSB/SC is in error.
30 R1 key is pressed during data transmission between SYSTEM P series and PMCSB/SC.
31 Input/output unit error
32 Read error
33 Hardware error of floppy disk
34 No designated file name is found.
41 An error occurred when inputting ROM data from ROM writer.
43 An error occurred when writing ROM data into ROM writer.
44 An error is deleted during comparison between SYSTEM P seriesmemory data and floppy data.
45 An error occurred when comparing ROM data with ROM writer data.
46 Key input data over
47 No designated symbol name is found.
48 A numeric value was directly specified to address parameters.
49 Counter number error
50 Decode functional instruction error
51 Symbol name (max. 6 characters) over

1051
A. ERROR CODES LIST
(FOR FANUC LADDER PG) APPENDIX B61863E/14

Error codes Details of errors


52 Input data error
53 Comment data are in error.
54 Symbol table over
55 Comment data area over
56 Designated symbol name is already employed.
57 Symbol table sequence is in error.
58 Designated symbol name is not found.
59 END1 was detected in COM mode.
60 END1 was detected in JMP mode.
61 END2 was detected in COM mode.
62 END2 was detected in JMP mode.
63 END 3 was detected in COM mode.
64 END 3 was detected in JMP mode.
65 END 3 is not specified.
66 COM functional instruction was specified in COM mode.
67 JMP functional instruction was specified in JMP mode.
68 Message address error
69 Message data area over
70 Message data error
71 No symbol table is prepared.
72 NC model error in title
73 Title number error
74 Title data error
75 I/O port address error
76 Group number error
77 Base number error
78 Slot number error
79 I/O module name error
80 I/O port data are not prepared yet.
81 I/O port data were doubly specified.
82 Specified symbol or address is missing.
83 An invalid unit is loaded in the ROM WRITER or the specification of ROM WRITER does not meet the
unit.
84 ROM module type is different from the specified one.
87 Output (or input) module was specified as an input (or output) address.
88 The same slot number was specified in the same group and the same base number.
89 The model of PMC is different.
93 The number of coils is specified by the COM or JMP command. (This causes an error for PMCSA1
and PMCSA2.)
150 Parity error of transfer data (check the cable.)
151 Excessive or insufficient data to be transferred (Check the cable.)
152 An EPROM or ROM module is not inserted in the ROM writer, or specification of the ROM writer is
invalid.
153 Blank check error (Ultraviolet ray is not sufficiently irradiated or the EPROM, ROM module is defective.)

1052
A. ERROR CODES LIST
B61863E/14 APPENDIX (FOR FANUC LADDER PG)

Error codes Details of errors


154 Write error (EPROM or ROM module is defective.)
155 Verifyerror (EPROM or ROM module is defective.)
156 Data output level error (EPROM or ROM module is defective.)
157 Timer test error is ROM writer (ROM writer is defective.)
158 I/O test error in ROM write (ROM writer is defective.)
159 A/D converter test error in ROM writer (ROM writer is defective.)
160 Power test error in ROM writer (ROM writer is defective.)
161 Power (VPP) is defective (EPROM, ROM module or ROM writer is defective.)
162 Power supply (VCC) is defective (EPROM, ROM module or ROM writer is defective.)
163 ROM test error in ROM writer (ROM writer is defective.)
164 RAM test error in ROM writer (ROM writer is defective.)
170 An initialization error in the external memory floppy disk.
171 The inputted ROM format data is greater than the specified cassette type.
The PASCAL origin of the inputted PASCAL load module is unsuitable.
172 The specified ROM format data cannot be edited with the PG Mate.
Outputting data in the ROM format is possible, however.

1053
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B WINDOW FUNCTION DESCRIPTION (PMCPA1/PA3/


SA1/SA2/SA3/SA5/SB/SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

1054
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.1 This window function is a functional instruction by which the data on the
CNC is read or is written.
FUNCTION

B.2 In the way to process, there are window function high speed and one
processed at low speed.
LOWSPEED
RESPONSE AND In case of a lowspeed response, The data is read or written by the control
between CNC and PMC
HIGHSPEED
RESPONSE OF Therefore, it is necessary to ACT=1 of the window instrucion must be
held until the transfer completion information (W1) becomes 1
WINDOW FUNCTION (interlock).
In a highspeed response, it is not necessity for take the interlock because
the data is directly read.

CAUTION
The window instruction of a lowspeed response is
controlled exclusively with the other window instructions of
lowspeed response.
Therefore, when the data is read or written continuously, it
is necessary to clear ACT of the functional instruction once
when the completion information (W1) become 1.
It does not work about ACT=1 of the other window
instructions of lowspeed response such as W1=1 and
ACT=1 of the window instruction of a lowspeed response.
The window instruction of a highspeed response is not
exclusively controlled like a lowspeed response.
Therefore, when the data is read or written continuously,
yow need not make ACT=0.
The scan number of times to complete the processing is
summarized on the following table.

TYPE SCAN TIMES UNTIL PROCESSING ENDS


LOW TWO SCAN TIMES OR MORE(This depends on the state of CNC)
HIGH 1SCAN TIME

CAUTION
Enter the desired function code (to which 1000 is added
when data of the second tool post (HEAD2) is read or written
in the TT series, or when data of the second path is read or
written in twopath control of the Power MateD.
To perform path 3 read/write operation in 3path control,
enter a function code + 2000.

1055
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.3
LIST OF WINDOW
FUNCTIONS
Number Description Function code R/W
1 Read CNC system information 0 R
2 Read the tool offset 13 R
3 Write a tool offset :Lowspeed response 14 W
4 Read the work origin offset *PM :Lowspeed response 15 R
5 Write work origin offset *PM :Lowspeed response 16 W
6 Read parameters *SB56 :Lowspeed response 17 R
7 Write parameters :Lowspeed response 18 W
8 Read setting data *SB56 :Lowspeed response 19 R
9 Write setting data :Lowspeed response 20 W
10 Read custom macro variables *SB56 :Lowspeed response 21 R
11 Write custom macro variables :Lowspeed response 22 W
12 Read the CNC alarm state 23, 186 (*8) R
13 Read the current program number 24 R
14 Read the current sequence number 25 R
15 Read an actual velocity for controlled axes 26 R
16 Read an absolute position (absolute coordinate value) on controlled axes 27 R
17 Read a machine position (machine coordinate value) on controlled axes 28 R
18 Read a skip operation (G31) stop position (coordinate value) on controlled axes 29 R
19 Read a servo delay amount 30 R
20 Read acceleration/deceleration delay amount on controlled axes 31 R
21 Read modal data 32 R
22 Read diagnosis data *SB56 :Lowspeed response 33 R
23 Read a feed motor load current value (A/D conversion data) 34 R
24 Reading tool life management data (tool group No.) *PM *21T *TM 38 R
25 Reading tool life management data (number of tool group s) *PM *21T *TM 39 R
26 Reading tool life management data (number of tools) *PM *21T *TM 40 R
27 Reading tool life management data (usable life of tool) *PM *21T *TM 41 R
28 Reading tool life management data (tool usage counter) *PM *21T *TM 42 R
Reading tool life management data (tool length compensation No. (1): Tool No.)
29 43 R
*PM *21T *TM
Reading tool life management data (tool length compensation No. (2):
30 44 R
Tool order No.) *PM *21T *TM
Reading tool life management data (cutter compensation No. (1): Tool No.)
31 45 R
*PM *21T *TM
Reading tool life management data (cutter compensation No. (2): Tool order No.)
32 46 R
*PM *21T *TM
Reading tool life management data (tool information (1): Tool No.)
33 47 R
*PM *21T *TM
Reading tool life management data (tool information (2): Tool order No.)
34 48 R
*PM *21T *TM
35 Reading tool life management data (tool No.) *PM *21T *TM 49 R
36 Reading the actual spindle speed 50 R

1056
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

Number Description Function code R/W


Entering data on the program check screen :lowspeed response
37 150 W
*PM *21T
38 Reading clock data (date and time) 151 R
39 Writing torque limit data for the digital servo motor :lowspeed response 152 W
40 Reading load information of the spindle motor (serial interface) 153 R
41 Reading a parameter *PM *21T 154 R
42 Reading setting data *PM *21T 155 R
43 Reading diagnosis data *PM *21T 156 R
44 Reading a character string of the CNC program being executed in the buffer *C 157 R
45 Reading the relative position of a controlled axis 74 R
46 Reading the remaining travel 75 R
47 Reading CNC status information 76 R
Reading value of the P code macro variable
48 59 R
*SB56 :lowspeed response *TM
49 Writing value of the P code macro variable :lowspeed response *TM 60 W
50 Reading the Tool life management data (Tool life counter type) 160 R
Registering the Tool life management data (Tool group)
51 163 W
:lowspeed response *TM
52 Writing the Tool life management data (Tool life) :lowspeed response *TM 164 W
Writing the Tool life management data (Tool life counter)
53 165 W
:lowspeed response *TM
Writing the Tool life management data (Tool life counter type)
54 166 W
:lowspeed response *TM
Writing the Tool life management data (Tool length offset number (1): Tool number)
55 167 W
:lowspeed response *TM
Writing the Tool life management data (Tool length offset number (2): Tool opera-
56 168 W
tion sequence number) :lowspeed response *TM
Writing the Tool life management data (Cutter compensation number (1):
57 169 W
Tool number) :lowspeed response *TM
Writing the Tool life management data (Cutter compensation number (2):
58 170 W
Tool operation sequence number) :lowspeed response *TM
Writing the Tool life management data (Tool condition (1): Tool number)
59 171 W
:lowspeed response *TM
Writing the Tool management data (Tool condition (2):
60 172 W
Tooloperation sequence number) :lowspeed response *TM
61 Writing the Tool life management data (Tool number) :lowspeed response *TM 173 W
62 Reading the Estimate disturbance torque data 211 R
63 Reading the current program number (8digit program numbers) *PM *21T 90 R
Writing (registering) tool life management data (tool group number)
64 200 R
*PM *21T *TM
65 Reading tool life management data (tool length offset number 1) *PM *21T *TM 227 R
Reading tool life management data (tool diameter offset number 1)
66 228 R
*PM *21T *TM
67 Reading tool life management data (tool information 1) *PM *21T *TM 201 R
Writing tool life management data (tool group number)
68 202 R
:lowspeed response *TM
Writing tool life management data (tool length offset number 1)
69 229 W
:lowspeed response *TM

1057
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

Number Description Function code R/W


Writing tool life management data (tool radius offset number 1)
70 230 W
:lowspeed response *TM
71 Writing tool life management data (tool information 1) :lowspeed response *TM 231 W
72 Reading actual spindle speeds 138 R
73 Reading fine torque sensing data (statistical calculation results) 226 R
74 Reading fine torque sensing data (store data) 232 R
75 Specification of the number of the program for I/O Link 194 W
76 Presetting the relative coordinate :lowspeed response 249 W
77 Deleting the Tool life Management Data (Tool group) :lowspeed response *TM 324 W
78 Deleting the Tool life Management Data (Tool data) :lowspeed response *TM 325 W
Clearing the Tool life Management Data (Tool life counter and Tool condition)
79 326 W
:lowspeed response *TM
Writing the Tool life Management Data (Arbitrary group number)
80 327 W
:lowspeed response *TM
Writing the Tool life Management Data (Remaining tool life)
81 328 W
:lowspeed response *TM
82 Reading the current screen number 120(*8) R
83 Reading detailed alarm information :lowspeed response 186(*8) R

*1 Function codes that have R in the R/W column are window read functions specifiable with the WINDR function command. Function
codes that have W in the R/W column are window write functions specifiable with the WINDW function command.
*2 For window functions mark with Lowspeed response, reading and writing parameters, setting data, diagnostic data and so on starts
after the PMC receives the response for request of reading and writing from the CNC. On the contrary, the other window functions can
read or write data at once in response to the request from PMC.
*3 Functions marked with *PM are not provided for the Power MateD or F.
*4 Functions marked with *21T are not provided for the Series 21T.
*5 Functions marked with *SB5/6 support highspeed window response for the SB5/SB6.
*6 Functions marked with *C are not provided for the SB5/SB6/SB7.
*7 Functions marked with *TM are restricted on CNC for the compound machining function.
1. Function can not be used.
2. Function can not be used in the T mode.
Refer to each window function for details.
*8 This function code is supported only by the Power Mate iD/H.

1058
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4 (1) In the explanation of the window functions, minuses () in the data
structure fields indicate that input data need not be set in these fields
FORMATS AND or that output data in these fields is not significant.
DETAILS OF
(2) All data is in binary unless otherwise specified.
CONTROL DATA
(3) All data block lengths and data lengths are indicated in bytes.
(4) Output data is valid only when window processing terminates
normally.
(5) Output data always includes one of the following completion codes.
Note, however, that all of the completion codes listed are not always
provided for each function.

Completion code Meaning


0 Normal termination
1 Error (invalid function code)
2 Error (invalid data block length)
3 Error (invalid data number)
4 Error (invalid data attribute)
5 Error (invalid data)
6 Error (necessary option missing)
7 Error (writeprotected)

Input and output control data has the following structure.


Top address +0
Function code

2
Completion code

4
Data length (M) These data set as input data are
(Byte length of data area) remain unchanged in the output
6 data.
Data number

8
Data attribute

10
Data area *Data length
Depends on the function.
X X

1059
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.1 [Description]
Reading CNC System System information peculiar to the CNC can be read. Such system
Information information includes the series name of the CNC (16 as series name, for
example), the machine type applied to the CNC, such s a machining center
(M) and a lathe (T), the series code and version of the ROM containing
the CNC system software, and the number of controlled axes.

[Input data structure]

Top address + 0
(Function code)
0

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

(Data number)
0

(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : CNC system information has been read normally.

1060
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
0

2
(Completion code)
0
(Always terminates normally.)

4
(Data length)
14

6
(Data number)

8
(Data attribute)

Value

10 ASCII characters
CNC series name (2 bytes) (16)

12 ASCII characters
Machine type M/T/TT (2 bytes)
( M, T. TT, . . . )

14 ROM series of CNC system ASCII characters


software(4 bytes) (B 0 0 0 1, . . . )

18 ROM version of CNC system ASCII characters


software(4 bytes) (0 0 0 1, 0 0 0 2, , . . )

22 ASCII characters
Number of controlled axes (2 bytes)
( 2, 3, 4, . . . )

NOTE
1 Data is stored from the upper digit in each lower byte.
2 In the Power MateD and F, the data corresponding to the
CNC series name and machine type are left as spaces.
3 In twopath control of the Power MateD, the data for the
first path is the same as that for the second path.

1061
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.2 [Description]
Reading a Tool Offset A tool offset value recorded in the CNC can be read.
Wear offset data, geometry offset data, cutter compensation data, and tool
length offset data can be read as a tool offset.

[Input data structure]

Top address + 0
(Function code)
13

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N = offset number)

8
(Data attribute)
M
(M = offset type)

10
(Data area)

(Need not be set)

X X

42

(a) Offset types (for machining centers, Power MateD, F)

Cutter Tool length If the type of tool offset need not be


specified, enter 0.
Wear 0 2
Figure 1 3

NOTE
In the Power MateD and F, read tool offsets without
specifying the classification (i.e. cutter compensation, tool
length, tool wear, and tool geometry).

(b) Offset types (for lathes)

X axis Z axis Tool tip R Virtual tool tip Y axis


Wear 0 2 4 6 8
Figure 1 3 5 7 9

1062
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The tool offset has been read normally.
3 : The offset number specified for reading is invalid. (This
completion code is returned when the specified offset number data
is not from 1 to the maximum number of offsets.)
4 : There are mistakes in the data attribute that specifies the type of
the offset to be read.
6 : For the offset number specified for reading, an additional tool
offset number option is required, but it is missing.
The offset number is not available for Power MateD/F.

[Output data structure]

Top address + 0
(Function code)
13

2
(Completion code)
?
(See the explanation of the completion codes.)

4
(Data length)
L (Normally set to 4)
(L: Byte length of offset value)

6
(Data number)
N
(N = offset number)

8
(Data attribute)
M
(M = offset type),, Value

10 Tool offset value Signed binary (A negative value is


represented in 2s complement.)
Upper 3 bytes are always 0 for virtual
tool tip

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.002 0.0002
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1063
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.3 [Description]
Writing a Tool Offset The tool offset value can be directly written into the CNC.
(:Lowspeed Wear offset data, geometry offset data, cutter compensation data, and tool
Response) length offset data can be written as a tool offset.

[Input data structure]

Top address + 0
(Function code)
14

2
(Completion code)

(Need not to be set)

4
(Data length)
4

6
(Data number)
N
(N = offset number)

8
(Data attribute)
M
(M = offset type) Value
10
Tool offset value Signed binary (A negative value is
represented in 2s complement.)
Upper 3 bytes are always 0 for virtual
tool tip

(a) Offset types (for machining centers, Power MateD, F)

Cutter Tool length If the type of tool offset need not be


specified, enter 0.
Wear 0 2
Figure 1 3

NOTE
In the Power MateD and F, write tool offsets without
specifying the classification (i.e. cutter compensation, tool
length, tool wear, and tool geometry).

(b) Offset types (for lathes)

X axis Z axis Tool tip R Virtual tool tip Y axis


Wear 0 2 4 6 8
Figure 1 3 5 7 9

1064
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

Input data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

[Completion codes]
0 : The tool offset has been written normally.
2 : The data byte length for the tool offset specified for writing is
invalid. (It is not set to 4.)
3 : The offset number specified for writing is invalid. (This
completion code is returned when the specified offset number data
is not from 1 to the maximum number of offsets.)
4 : There are mistakes in the data attribute that specifies the type of
the offset to be written.
6 : For the offset number specified for writing, the additional tool
offset number option is required, but it is missing.
The specified offset number is out of range. (Power MateD, F)

[Output data structure]

Top address + 0
(Function code)
14

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L: Input data)

6
(Data number)
N
(N = Input data)
8
(Data attribute)
M
(Input data) Value
10
Signed binary (A negative value is
Tool offset value: Input data represented in 2s complement.)

1065
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.4 [Description]
Reading a Workpiece The workpiece origin offset recorded in the CNC can be read.
Origin Offset Value A workpiece origin offset is provided for each controlled axis (the first
(not Supported by the axis to the eighth axis) in the CNC. Either the workpiece origin offset for
Power MateD or F) a specific axis can be read, or the workpiece origin offsets for all axes can
be read at one time. If the additional axis option is not provided, however,
the workpiece origin offset for the additional axis cannot be read.

[Input data structure]

Top address + 0
(Function code)
15

2
(Completion code)

(Need not be set)

4
(Data length) N = 0: External workpiece origin offset
N = 1: G54
(Need not be set)

6 N = 6: G59
(Data number) With addition of workpiece coordinate system pair
N N=7 : G54.1 P1
(N = 0 to 6)

8 N=306 : G54.1 P300
(Data attribute)
M M = 1 to n: Workpiece origin offset number of a
(M = 1 to n or 1) specific axis. n is the axis number.
10
(Data area) M = 1: Read for all axes

(Need not be set)

X X

42

1066
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The workpiece origin offset has been read normally.
3 : The specified data number is invalid because the number is not
from 0 to 6.
4 : The specified data attribute is invalid because the attribute data is
neither 1 nor a value from 1 to n (n is the number of axes).
Alternatively, the specified axis number is greater than the number
of controlled axes.
6 : There is no workpiece coordinate shift option added.

[Output data structure]

Top address + 0
(Function code)
15

2
(Completion code)
?
(See the explanation of
the completion codes.)
4 L = 4: The workpiece origin offset value for
(Data length)
L a specific axis is read.
(L: Byte length of the workpiece
origin offset value) L = 4*n: Workpiece origin offsets for all axes are
6 read.
(Data number)
N
(N = Input data)
8
(Data attribute)
M
(M = Input data) Value
10
Signed binary number (A negative value
Workpiece origin offset value is represented in 2s complement.)

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1067
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.5 [Description]
Writing a Workpiece Data can be written directly as a workpiece origin offset value in the CNC.
Origin Offset Value A workpiece origin offset is provided for each controlled axis (the first
(:Lowspeed axis to the eighth axis) in the CNC. Either the workpiece origin offset
Response) value for a specific axis can be written, or the workpiece origin offset
(not Supported by the values for all axes can be written at one time. If the additional axis option
Power MateD or F) is not provided, however, the workpiece origin offset value for the
additional axis cannot be written.

[Input data structure]

Top address + 0
(Function code) L = 4 : Workpiece origin offset value for a specific
16 axis is written.

L = 4*n
2
(Completion code) Workpiece origin offset values for all axes
are written.
(Need not be set) N = 0: External workpiece origin offset
N = 1: G54
4
(Data length)
L
(L: Byte length of the workpiece N = 6: G59
origin offset value) With the option of adding Workpiece coordinate systems
6 N=7: G54.1P1
(Data number)
N
(N = Offset group number) N=306: G54.1P300
M = 1 to n: Workpiece origin offset number of a
8 specific axis. n is the axis number.
(Data attribute) M = 1: Write for all axes
M
(M = Axis number) Value

10 Signed binary (A negative value is


Workpiece origin offset value represented in 2s complement.)

Input data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1068
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The workpiece origin offset has been written normally.
2 : The specified data length is invalid.
3 : The data number is invalid because the specified number is not
from 0 to 6.
4 : The specified data attribute is invalid because the attribute data is
neither 1 nor a value from 1 to n (n is the number of axes).
Alternatively, the specified axis number is greater than the number
of controlled axes.
6 : There is no workpiece coordinate shift option added.

[Output data structure]

Top address + 0
(Function code)
16

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L: Input data)

6
(Data number)
N
(N = Input data)
8
(Data attribute)
M
(M = Input data) Value

10 Signed binary number (A negative value


Workpiece origin offset value is represented in 2s complement.)

1069
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.6 [Description]
Reading a Parameter Parameter data in the CNC can be read.
(:Lowspeed There are four types of parameters in the CNC: Bit parameters having a
Response) definite meaning for each bit, byte parameters holding 1byte data, word
parameters holding 2byte data, and double word parameters holding
4byte data. Therefore, the length of the read data varies according to the
parameter number specified.
Note that bit parameters cannot be read in bit units. The eight bits (one
byte) for a parameter number must be read at a time.
For axis parameters, data for a specific axis can be read, or data for all axes
can be read at a time.
Specify pitch error compensation data in data Nos. 10000 to 11023 (1024
points in total).
For details of parameter data, refer to the Operators manual of the CNC.

[Input data structure]

Top address + 0
(Function code)
17

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N = parameter number)

8 M = 0: No axis
(Data attribute)
M M = 1 to n: A specific axis
(M = Axis number)
M = 1: All axes
10
(Data area)
When all axes are specified by spindle parameters
(Need not be set) (parameters 4000 to 4799), only two axes are specified.

X X

42

1070
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Parameter data has been read normally.
3 : The parameter number specified for reading is invalid.
4 : The specified data attribute is invalid because it is neither 0, 1,
nor a value 1 to n (n is the number of axes).
6 : Although a certain option, such as the pitch error compensation
option, is required for the data of the parameter number specified
for reading, it is not provided.
[Output data structure]

Top address + 0
(Function code)
17

2 (Completion code) When no axis or one axis is specified


? L = 1: Bit or byte parameter
(See the explanation of L = 2: Word parameter
the completion codes.) L = 4: Double word parameter
4
(Data length)
L
When all axes are specified
(L = 1, 2, 4, 1*n, 2*n, 4*n)
L = 1*n : Bit or byte parameter
6 L = 2*n: Word parameter
(Data number) L = 4*n: Double word parameter
N
(N = Input data)
8
(Data attribute)
M
(M = Input data) Value

10 Parameter data Parameterdependentform

CAUTION
For the SB5/SB6/SB7, macro executor parameters 9000 to
9011 cannot be read.

1071
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.7 [Description]
Writing a Parameter Data can be written in a parameter in the CNC.
(:Lowspeed There are four types of parameters in the CNC: Bit parameters having a
Response) definite meaning for each bit, byte parameters holding 1byte data, word
parameters holding 2byte data, and double word parameters holding
4byte data. Therefore, the length of the written data varies according to
the parameter specified.
Note that bit parameters cannot be written in bit units. The eight bits (one
byte) for the parameter number must be written at a time. This means that
when a bit needs to be written, the whole data for the corresponding
parameter number shall be read first, modify the target bit in the read data,
then the data shall be rewritten.
For axis parameters, data for a specific axis can be read, or data for all axes
can be read at a time.
For details of parameter data, refer to the Operators manual of the CNC.
Some parameters cause a P/S alarm 000 when data is written. (The power
must be turned off before continuing operation.)
[Input data structure]

Top address + 0
(Function code)
18

2 When no axis or one axis is specified


(Completion code) L = 1: Bit or byte parameter
L = 2: Word parameter
(Need not be set.) L = 4: Double word parameter
4
(Data length)
L When all axes are specified
(L = 1, 2, 4, 1*n, 2*n, 4*n)
L = 1*n: Bit or byte parameter
6 L = 2*n: Word parameter
(Data number) L = 4*n: Double word parameter
N
(N = parameter number)
8 M = 0: No axis
(Data attribute) M = 1 to n: A specific axis
M M = 1: All axes
(M = Axis number)
When all axes are specified by spindle parame-
ters (parameters 4000 to 4799), only two axes
are specified.

Value

10 Parameter data Parameterdependentform

1072
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Parameter data has been written normally.
2 : The data byte length of the parameter specified for writing is
invalid.
3 : The parameter number specified for writing is invalid.
4 : The specified data attribute is invalid because it is neither 0, 1,
nor a value from 1 to n (n is the number of axes).
6 : Although a certain option, such as the pitch error compensation
option, is required for the data of the parameter number specified
for writing, it is not provided.
[Output data structure]

Top address + 0
(Function code)
18

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = Input data)

6
(Data number)
N
(N = Input data)
8
(Data attribute)
M
(M = Input data) Value

10 Parameter data: Input data Parameterdependentform

CAUTION
Parameters may not become effective immediately
depending on the parameter numbers.

1073
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.8 [Description]
Reading Setting Data The CNC setting data can be read.
(:Lowspeed There are four types of setting data in the CNC: Bit setting data having
Response) a definite meaning for each bit, byte setting data stored in bytes, word
setting data stored in 2byte units, and doubleword setting data stored
in 4byte units. Therefore, the length of the read data varies according
to the setting data specified.
Note that bit setting data cannot be read in bit units. The eight bits (one
byte) for the setting data number must be read at a time.
For axis parameters, data for a specific axis can be read, or data for all axes
can be read at a time.
For details of setting data, refer to the Operators manual of the CNC.
[Input data structure]

Top address + 0
(Function code)
19

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N = Setting data number)

8 M=0: No axis
(Data attribute)
M M = 1 to n: A specific axis
(M = Axis number)
M = 1: All axes
10
(Data area)

(Need not be set)

X X

42

1074
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Setting data has been read normally.
3 : The setting number specified for reading is invalid.
4 : The specified data attribute is invalid because it is neither 0, 1,
nor a value from 1 to n (n is the number of axes).

[Output data structure]

Top address + 0
(Function code)
19

2 (Completion code) When no axis or one axis is specified


? L = 1: Bit or byte parameter
(See the explanation of L = 2: Word parameter
the completion codes.) L = 4: Double word parameter
4
(Data length)
L
When all axes are specified
(L = 1, 2, 4, 1*n, 2*n, 4*n)
L = 1*n: Bit or byte parameter
6 L = 2*n: Word parameter
(Data number) L = 4*n: Double word parameter
N
(N = Input data)
8
(Data attribute)
M
(M = Input data) Value
10
Setting data Parameterdependentform

1075
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.9 [Description]
Writing Setting Data Data can be written as setting data in the CNC.
(:Lowspeed For details of setting data, refer to the Operators manual of the CNC.
Response)
[Input data structure]

Top address + 0
(Function code)
20

2 When no axis or one axis is specified


(Completion code) L = 1: Bit or byte parameter
L = 2: Word parameter
(Need not be set.) L = 4: Double word parameter
4
(Data length)
L When all axes are specified
(L = 1, 2, 4, 1*n, 2*n, 4*n)
L = 1*n: Bit or byte parameter
6 L = 2*n: Word parameter
(Data number) L = 4*n: Double word parameter
N
(N = Setting data number)
8 M = 0: No axis
(Data attribute)
M M = 1 to n: A specific axis
(M = Axis number)
M = 1: All axes

Value

10 Setting data Setting datadependent form

1076
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Setting data has been written normally.
2 : The byte length of the setting data specified for writing is invalid.
3 : The setting data number specified for writing is invalid.
4 : The specified data attribute is invalid because it is neither 0, 1,
nor a value from 1 to n (n is the number of axes).
5 : Data exceeding the allowable range was specified as setting data
to be written. For example, when data outside the range from 0
to 3 is specified as the setting data to be written for I/O data, this
completion code is returned.

[Output data structure]

Top address + 0
(Function code)
20

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(N = Input data)

6
(Data number)
N
(N = Input data)
8
(Data attribute)
M
(M = Input data) Value

10 Setting data: Input data Setting datadependent form

1077
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.10 [Description]
Reading a Custom A custom macro variable in the CNC can be read.
Macro Variable Custom macro variables may or may not be read depending on the
variable type.
(:Lowspeed
(1) Local variables
Response)
Local variables (#1 to #33) cannot be read.
(2) Common variables
Common variables (#100 to #149 and #500 to #531) can be read in
floatingpoint representation. When the option to add common
variables is provided, however, common variables range from #100
to #199 and #500 to #999.
NOTE
1 Power MateD (twopath control), Power MateF: #100 to
199, #500 to 699.
Memory module A of onepath control: #100 to #149, #500
to #531.
Memory module B/C of onepath control: #100 to #199,
#500 to #699.
2 On the Power Mate iMODEL D/H, common variables #100
to #199 and #500 to #699 can be read and written.
Set the variable number within these ranges as the data
number of the input data, and read and write custom macro
variables.

(3) System variables


System variables (#1000 and up) can be read in floatingpoint
representation.
For details of the custom macro variables, refer to the Operators
Manual for the CNC.

CAUTION
For the SB5/SB6/SB7, system variables cannot be read.

1078
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Input data structure]


Top address + 0
(Function code)
21

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N = Custom macro variable number)
8
(Data attribute)
M
(M: Number of decimal places)

10
(Data area)

(Need not be set)
X X
42

[Completion codes]
0 : The custom macro variable has been read normally.
3 : The number of a custom macro variable that cannot be read was
specified as the data number. Only common variables can be read
as custom macro variables by this library command.
5 : The custom macro variable is not within the range from
0.0000001 to 99999999.
6 : The custom macro option is not provided.
The specified variable number is out of range. ( Power MateD,
F)

1079
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address + 0
(Function code)
21

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length) L = 6: Custom macro B
L The mantissa of a floating
(L: Byte length of custom macro point number is indicated in 4
variable data) bytes, and the exponent is
6 indicated in 2 bytes.
(Data number)
M = 0: The number of decimal
N
places is not specified.
(N = Input data)
M = 1x nx 7:
8 The number of decimal places is specified. n
(Data attribute) stands for the number of decimal places.
M
(M: Number of decimal places) Value

10 Custom macro variable data (4 bytes) Signed binary


Mantissa (custom macro B) (A negative value is represented in 2s
complement.)

14 Custom macro variable data (2 bytes)


Exponent (custom macro B): The num- Signed binary
ber of decimal digits 0 to 8 (no negative values)

1080
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.11 [Description]
Writing a Custom Data can be written in a custom macro variable in the CNC.
Macro Variable For details of common variables, refer to the Operators manual of the
(:Lowspeed CNC.
Response)
[Input data structure]

Top address + 0
(Function code)
22

2
(Completion code)

(Need not be set)

4
(Data length)
L L = 6: Custom macro B
(L: Byte length of custom The mantissa of a floatingpoint
macro variable data) number is indicated in 4 bytes,
6 and the exponent is indicated in
(Data number) 2 bytes.
N
(N = Custom macro variable number)

8
(Data attribute)
0
Value

10 Custom macro variable data (4 bytes) Signed binary


Mantissa (custom macro B) (A negative value is represented in 2s
complement.)

14 Custom macro variable data (2 bytes) Signed binary


Exponent (custom macro B): The num- (A negative value is represented in 2s
ber of decimal digits complement.)

1081
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The custom macro variable has been written normally.
2 : The specified data length is invalid because it is not 6.
3 : A custom macro variable number that cannot be written as the data
number was specified.
6 : The custom macro option has not been provided.
The specified variable number is out of range. (Power MateD, F)

[Output data structure]

Top address + 0
(Function code)
22

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L: Input data)

6
(Data number)
N
(N = Input data)

8
(Data attribute)

(Need not be set) Value

10 Custom macro variable data: Input data Signed binary


Mantissa (custom macro B) (A negative value is represented in 2s
complement.)

14 Custom macro variable data: Input data


Exponent (custom macro B): The num- Signed binary
ber of decimal digits

1082
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.12
Reading the CNC
Alarm Status

B.4.12.1 [Description]
Except Power When the CNC is in the alarm status, the alarm status data can be read.
MateD/F/H The following alarm status data can be read:
(1) First byte of alarm status data

7 6 5 4 3 2 1 0

PS1
PS2
PS3
PS
OTS
OH
SV
MALM

PS1 : P/S alarm 100 (PWE (parameter write enable) is set to 1.)
PS2 : P/S alarm 000 (Turn off the power before continuing operation.
Some parameters activate this alarm status when they are
written.)
PS3 : P/S alarm 101 (The part program recording area is disordered.
This alarm is activated when the power to the CNC is turned off
during part program editing or reading of a machining program.
To release the alarm, then press the RESET key while holding
down the PROG key.)
PS : A P/S alarm other than the above alarm is generated
OTS : Stroke limit alarm
OH : Overheat alarm
SV : Servo alarm
MALM: Memory alarm

1083
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

(2) Second byte of alarm status data

7 6 5 4 3 2 1 0

APAL
SPA
(Not used)
(Not used)
(Not used)
(Not used)
(Not used)
(Not used)

APAL: APC alarm


SPA : Spindle alarm

[Input data structure]

Top address + 0
(Function code)
23

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

1084
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.12.2 (1) Overview


For Power MateD/F/H PMC application programs can read CNC alarm information.
(Lowspeed type) (2) Alarm information
1) Alarm status
Information concerning the alarm type
2) Detailed alarm
Information concerning the alarm number and axis information
(3) Input data configuration

Top address+0 +2 +4 +6 +8 +10


Function Completion Data Data Data Data
code code length number attribute area

Function code : 23 (fixed)


Completion code : No specification required.
Data length : No specification required.
Data number : Number of alarms which can be stored. (Up to 30).
If 31 or more are specified, the value is assumed to
be 30.
Data area : No specification required.
Data attribute : 0: Alarm status information
Other than 0 : Detailed alarm information,
indicated in twobyte bittype data
described below (multiple bits can
be specified.)

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit

Bit 0 : P/S alarm 100 (PS1)


(PWE, parameter write enable, is set to 1.)
Bit 1 : P/S alarm 000 (PS2)
(Turn off the power. Writing data into certain parameters may
cause this alarm.)
Bit 2 : P/S alarm 101 (PS3)
(Part program storage has been disrupted. This alarm is issued
when the CNC is turned off during tape editing or machining
program reading. To release this alarm, press the RESET key
while holding down the PROG key.)
Bit 3 : A P/S alarm (PS) other than those described above has been
issued. (Up to 255)
Bit 4 : Stroke limit alarm (OTS)
Bit 5 : Overheat alarm (OH)

1085
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

Bit 6 : Servo alarm (SV)


Bit 7 : Not used
Bit 8 : APC alarm (APAL)
Bit 9 : Spindle alarm (SPA)
Bit 10 : P/S alarm 5000 or greater (PS_2)
Bit 11 to Bit 15 : Not used
(4) Output data configuration

Top address+0 +2 +4 +6 +8 +10


Function Completion Data Data Data Data
code code length number attribute area

Function code : 23 (fixed)


Completion code : Always 0.
Data length : 2 when the input data attribute is set to 0 and no
alarm is issued.
2 + 4*n when the input data attribute is set to other
than 0 (n stands for the number of alarms issued).
Data number : Same as that for the input data.
Data attribute : Same as that for the input data.
Data area : Twobyte bittype data when the input data
attribute is set to 0 (each bit indicates the same
information as that for the input data).
(2 + 4*n)byte data, described below, for all alarm
states specified in the input data attribute when the
input data attribute is other than 0.

2byte 2byte 2byte 4byte 4byte

Axis information Alarm number



7 6 5 4 3 2 1 0

n 15 14 13 12 11 10 9 8

Bit 0 = 1 : When an alarm is issued


for the first axis

Bit 1 = 1 : When an alarm is issued
for the second axis
Bits 2 to 15 are always set to 0.


Number First alarm Second nth
of alarms alarm alarm
(n: Number of alarms issued)

(5) Completion code


0 : CNC alarm status has been read normally.

1086
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : This alarm status in the CNC has been read normally.

[Output data structure]


Top address + 0
(Function code)
23

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
2

6
(Data number)

8
(Data attribute)

Value

10 CNC alarm status data 2 byte bit data. For the meanings of the
bits, see [Description] in this section.

1087
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.13 [Description]
Reading the Current The program number of a machining program being executed or selected
Program Number on the CNC can be read.
When a subprogram is executed on the CNC, the program number of the
main program can also be read. Note that the program number that can be
read is the first program number (first loop main program).
This function accepts only 4digit program numbers. When the
specification supports 8digit program numbers, specify function code
90 to read 8digit program numbers.
[Input data structure]

Top address + 0
(Function code)
24

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

(Data number)
0

(Data attribute)
0

10
(Data area)

(Need not be set)

42

[Completion codes]
0 : The program number of the currently executing program was read
successfully.
6: The program number is an 8digit program number. (Use function
code 90.)

1088
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
24

2
(Completion code)
?
(See the explanation above.)
4
(Data length)
4

6
(Data number)

8
(Data attribute)
Value

10 Current program number: ON Unsigned binary, 2 bytes long

12 Program number of main program:


OMN

(a) Current program number (ON)


The program number of the program being executed is set.
(b) Program number of main program (OMN)
When the currently executing program is a subprogram, the program
number of its main program (first loop main program) is set, When
the currently executing program is not a subprogram, 0 is set.

1089
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.14 [Description]
Reading the Current The sequence number of a machining program being executed on the
Sequence Number CNC can be read. If sequence numbers are not assigned to all blocks of
the machining program, the sequence number of the most recently
executed block is read.

[Input data structure]

Top address + 0
(Function code)
25

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

1090
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The current sequence number has been read normally.

[Output data structure]

Top address + 0
(Function code)
25

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L Note that the data length must be set to 4
(L = 4) bytes even though the current program
number is 2 bytes long (the sequence
6 number is indicated by 5 digits).

(Data number)

8
(Data attribute)
Value

10
Current sequence number Unsigned binary

1091
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.15 [Description]
Reading the Actual The actual velocity of a movement on CNCcontrolled axes can be read.
Velocity of Controlled Note that the read speed is the composite velocity for the controlled axes.
Axes When movement involves only the basic three axes, the X, Y, and Z axes,
the composite velocity equals the actual velocity. When movement,
however, involves the fourth axis, such as a rotation axis or a parallel axis,
as well as some of the basic three axes, the composite velocity for all the
relevant axes does not equal the actual velocity.

[Input data structure]

Top address + 0
(Function code)
26

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

1092
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The actual velocity for the controlled axes has been read normally.
[Output data structure]

Top address + 0
(Function code)
26

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = 4)
6
(Data number)

8
(Data attribute)

Value

10 Actual velocity for controlled axes Unsigned binary


<Data increments>
SInput in mm
1 mm/min
SInput in inches
0.01 inch/min.

1093
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.16 [Description]
Reading the Absolute The absolute coordinates of the CNCcontrolled axes for movement can
Position (Absolute be read. The absolute coordinates indicate those after cutter
Coordinates) of compensation or tool length compensation.
Controlled Axes
[Input data structure]

Top address + 0
(Function code)
27

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8 M = 1 to n: Absolute coordinate of a specific


(Data attribute) axis. n is the axis number.
M
(M = Axis number)
M = 1: Coordinates of all axes
10
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : The absolute coordinates of the controlled axes have been read
normally.
4 : Data specified as the data attribute is invalid because it is neither
1 nor a value from 1 to n (n is the number of axes). Alternatively,
the specified axis number is greater than the number of controlled
axes.

1094
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
27

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = 4*n, n is the number of
axes specified.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value

10 Absolute coordinate of the controlled Signed binary


axis specified (4 bytes) (A negative value is represented in 2s
complement.)

When the number of controlled axes is 4

Value

10 Absolute coordinate of the first axis Signed binary


(4 bytes) (A negative value is represented in 2s
complement.)
14 Absolute coordinate of the second axis
(4 bytes)

18 Absolute coordinate of the third axis


(4 bytes)

22 Absolute coordinate of the fourth axis


(4 bytes)

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1095
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.17 [Description]
Reading the Machine The machine coordinates of CNCcontrolled axes for movement can be
Position (Machine read. The read value equals the machine coordinate indicated on the
Coordinates) of current position display screen displayed in the CNC. (This screen can
be displayed by pressing the function button POS.)
Controlled Axes
[Input data structure]
Top address + 0
(Function code)
28

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8 M = 1 to n: Machine coordinate of a specific


(Data attribute) axis. n is the axis number.
M
(M = Axis number)
M = 1: Coordinates of all axes
10
(Data area)

(Need not be set)

X X

42

CAUTION
When an inch machine is used in metric input, or when a
millimeter machine is used in inch input, the machine
position that is read with bit 0 of parameter No. 3104 set to
1 differs from the value indicated by the CNC. In this case,
therefore, the value read through the ladder must be
calculated (converted).

[Completion codes]
0 : The machine coordinates of the controlled axes have been read
normally.
4 : Data specified as the data attribute is invalid because it is neither
1 nor a value from 1 to n (n is the number of axes). Alternatively,
the specified axis number is greater than the number of the
controlled axes.

1096
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
28

2
(Completion code)
?
(See the explanation of
the completion codes.)
4 (Data length)
L
(L = 4*n, n is the number of
axes specified.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value

10 Machine coordinate of the controlled Signed binary


axis specified (4 bytes) (A negative value is represented
in 2s complement.)

When the number of controlled axes is 4

Value

10 Machine coordinate of the first axis Signed binary


(4 bytes) (A negative value is represented
in 2s complement.)
14 Machine coordinate of the second axis
(4 bytes)

18 Machine coordinate of the third axis


(4 bytes)

22 Machine coordinate of the fourth axis


(4 bytes)

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1097
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.18 [Description]
Reading a Skip When a block of the skip operation (G31) is executed by the CNC and the
Position (Stop Position skip signal goes on to stop the machine, the absolute coordinates of the
of Skip Operation stop position on the axes of movement can be read.
(G31)) of Controlled
Axes [Input data structure]

Top address + 0
(Function code)
29

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8 M = 1 to n: Skip coordinate on a specific axis.


(Data attribute) n is the axis number.
M
(M = Axis number)
M = 1: Coordinates on all axes
10
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : The coordinates of the skip stop position for the controlled axes
have been read normally.
4 : Data specified for the data attribute is invalid because it is neither
1 nor a value from 1 to n (n is the number of axes). Alternatively,
the specified axis number is greater than the number of controlled
axes.

1098
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
29

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = 4*n, n is the number of
axes specified.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value

10 Skip coordinate of the controlled axis Signed binary


specified(4 bytes) (A negative value is represented in 2s
complement.)

When the number of controlled axes is 4

Value

10 Skip coordinate of the second axis Signed binary


(4 bytes) (A negative value is represented in 2s
complement.)
14 Skip coordinate of the third axis
(4 bytes)

18 Skip coordinate of the fourth axis


(4 bytes)

22 Skip coordinate of the first axis


(4 bytes)

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1099
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.19 [Description]
Reading the Servo The servo delay, which is the difference between the specified coordinates
Delay for Controlled of CNCcontrolled axes and the actual servo position, can be read.
Axes
[Input data structure]

Top address + 0
(Function code)
30

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8 M = 1 to n: Servo delay for a specific axis


(Data attribute)
M
(M = Axis number)
M = 1: Servo delay for all axes
10
(Data area)

(Need not be set)

X X

42

1100
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The servo delay for the controlled axes have been read normally.
4 : The data specified as the data attribute is invalid because it is
neither 1 nor a value from 1 to n (n is the number of axes).
Alternatively, the specified axis number is greater than the number
of controlled axes.

[Output data structure]

Top address + 0
(Function code)
30

2
(Completion code)
?
(See the explanation of
the completion codes.)
4 (Data length)
L
(L = 4*n, n is the number of
axes specified.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value

10 Servo delay for the controlled axis spe- Signed binary


cified (4 bytes) (A negative value is represented in 2s
complement.)

When the number of controlled axes is 4

Value

10 Servo delay for the first axis (4 bytes) Signed binary


(A negative value is represented in 2s
complement.)
14 Servo delay for the second axis
(4 bytes)

18 Servo delay for the third axis (4 bytes)

22 Servo delay for the fourth axis


(4 bytes)

1101
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.20 [Description]
Reading the The acceleration/deceleration delay, which is the difference between the
Acceleration/ coordinates of controlled axes programmed in the CNC and the position
Deceleration Delay on after acceleration/deceleration is performed, can be read.
Controlled Axes
[Input data structure]

Top address + 0
(Function code)
31

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8 M = 1 to n: Acceleration/deceleration delay for a


(Data attribute) specific axis
M
(M = Axis number)
M = 1: Acceleration/deceleration delay for all
10 axes
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : The acceleration/deceleration delay for the control axis has been
read normally.
4 : The data specified as the data attribute is invalid because it is
neither 1 nor a value from 1 to n (n is the number of axes).
Alternatively, the specified axis number is greater than the number
of controlled axes.

1102
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
31

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = 4*n, n is the number of
axes specified.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value

10 Acceleration/deceleration delay for the Signed binary


controlled axis specified (4 bytes) (A negative value is represented in 2s
complement.)

When the number of controlled axes is 4

10 Acceleration/deceleration delay for the Signed binary


first axis (4 bytes) (A negative value is represented in 2s
complement.)
14 Acceleration/deceleration delay for the
second axis (4 bytes)

18 Acceleration/deceleration delay for the


third axis (4 bytes)

22 Acceleration/deceleration delay for the


fourth axis (4 bytes)

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1103
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.21 [Description]
Reading Modal Data Modal information can be read from the CNC.
(1) Format and types of modal data for the G function
Data corresponding to the specified identification code is read and
stored in the data area. Whether the data is specified in the block
specified in the attribute of the data is determined by the value at the
most significant bit.

7 6 5 4 3 2 1 0

S Code in a group 1byte

1byte

0: Not specified in the block


1: Specified in the block

NOTE
G codes for machining centers are also used for the Power
MateD and F except those marked with *. G codes marked
with ** are not provided for the Power MateF.

(1/2)
Data type Data Data type Data
Identificati G code for machining Code in a G code for lathe (T, G) Code in a
on code center (M) group A series B series C series group
G00 0 G00 G00 G00 0
G01 1 G01 G01 G01 1
::G02 2 G02 G02 G02 2
::G03 3 G03 G03 G03 3
:G33 4 G32 G33 G33 4
G33 8
G34 G34 G34 9
0
G90 G77 G20 5
G92 G78 G21 6
G94 G79 G24 7
G71 G71 G72 10
G G G
G72 G72 G73 11
series series series
G73 G73 G74 only
12
only only
G74 G74 G75 13
G17 0 G96 G96 G96 1
1 G18 8 G97 G97 G97 0
G19 4
G90 0 G90 G90 0
2
G91 1 G91 G91 1
G68 G68 G68 1
3
G69 G69 G69 0
G94 0 G98 G94 G94 0
4
G95 1 G99 G95 G95 1
G20 0 G20 G20 G70 0
5
G21 1 G21 G21 G71 1

1104
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

(2/2)
Data type Data Data type Data
Identificati G code for machining Code in a G code for lathe (T, G) Code in a
on code center (M) group A series B series C series group
:G40 0 G40 G40 G40 0
6 :G41 1 G41 G41 G41 1
:G42 2 G42 G42 G42 2
G43 1 G25 G25 G25 0
7 G44 2 G26 G26 G26 1
G49 0
G73 10 G22 G22 G22 1
G74 11 G23 G23 G23 0
G76 12
G80 0
G81 1
G82 2
8 G83 3
G84 4
G85 5
G86 6
G87 7
G88 8
G89 9
:G98 0 G80 G80 G80 0
:G99 1 G83 G83 G83 1
G84 G84 G84 2
9 G85 G85 G85 3
G87 G87 G87 5
G88 G88 G88 6
G89 G89 G89 7
:G50 0 G98 G98 0
10
:G51 1 G99 G99 1
G66 1 G66 G66 G66 1
11
G67 0 G67 G67 G67 0
:G54 0 G54 G54 G54 0
:G55 1 G55 G55 G55 1
:G56 2 G56 G56 G56 2
13
:G57 3 G57 G57 G57 3
:G58 4 G58 G58 G58 4
:G59 5 G59 G59 G59 5
:G61 1
:G62 2
14
:G63 3
:G64 0
:G68 1
15
:G69 0
:G15 0
16
:G16 1
G40.1 1
17 G41.1 2
G42.1 0
G25 0
18
G26 1
G50.2 G50.2 G50.2 0
19
G51.2 G51.2 G51.2 1
G13.1 0 G13.1 G13.1 G13.1 0
20
G12.1 1 G12.1 G12.1 G12.1 1

1105
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

(2) Format and types of modal data for other than the G function

Data 4 bytes

FLAG1 1 byte

FLAG2 1 byte

7 6 5 4 3 2 1 0
Number of input digits

0: Positive
1: Negative
0: A decimal point not specified
1: A decimal point specified
0: Not specified in the current block
1: Specified in the current block

Number of decimal places

The specification of whether a decimal point is specified or not, in FLAG1,


and the specification of the number of decimal places, in FLAG2, are valid
only for F code. Even if a decimal point is not specified, the number of deci-
mal places may not be 0.
Note) As the numbers of input digits, M, S, T, and B, in a command address, the allow-
able numbers of digits that are specified for the appropriate parameters are returned.
M: Allowable number of digits of M code No. 3030
S: Allowable number of digits of S code No. 3031
T: Allowable number of digits of T code No. 3032
B: Allowable number of digits of B code No. 3033

Data type
Identification code Specified address
2 Enter identification codes
100 to 126 at one time.
100 B (second auxiliary function)
101 D
102 E (reserved)
103 F
104 H
105 L
106 M
107 S
108 T
109 R
110 P
111 Q
112 A
113 C
114 I
115 J
116 K
117 N
118 O
119 U
120 V
121 W
122 X
123 Y
124 Z
125 M2
126 M3

1106
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

CAUTION
The Power MateD/F is not provided with the second
auxiliary function.

[Input data structure]

Top address + 0
(Function code)
32

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6 N = 0 to : See the identification codes of list


(Data number) of data explained above.
N N = 1: All data for G function
(N: Data type)
N = 2: All data for other than G function
8
(Data attribute)
M M=0: Current block
(M: Specified block )

10 M=1: Next block


(Data area)
M=2: Block after the next block
(Need not be set)

X X

20

When all data items are specified to be read, the data items are all output
simultaneously in the order specified in the above data table.

1107
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Modal information has been read normally.
3 : Invalid data is specified as the data number.
4 : Invalid data is specified as the data attribute.
[Output data structure]

Top address + 0
(Function code)
32
(See the explanation above

2
(Completion code)
?
(See the explanation of
the completion codes.)
4 L=2 : G function
(Data length)
L L = 2*n : All data for G function
(L = 2, 6, 2*n, 6*m)
L=6: Other than G function
6
(Data number) L = 6*m : All data for other than G function
N (n: Number of groups for the G function)
(N: Input data) (m: Number of types other than for the G function)
8
(Data attribute)
M
(M: Input data) Value

10 Modal data for G function (2 bytes) See the data format for the G function.
The upper byte must always be set to 0.

Or

8
(Data attribute)
M
(M: Input data) Value

10 Data part of modal data for other than See the data format for other than the
G function(4 bytes) G function.

Flag part of modal data for other than See the flag format of the data for other
14 than the G function. The upper byte
G function(2 bytes)
must always be set to 0.

When all data items are specified to be read, the data items are all output
simultaneously in the order specified in the above data table.

1108
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.22 [Description]
Reading Diagnosis The information displayed on the diagnosis data screen in the CNC can
Data (:Lowspeed be read.
Response)
[Input data structure]

Top address + 0
(Function code)
33

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Diagnosis No.)

8 M=0: No axis
(Data attribute)
M M = 1 to n: One axis
(M: Axis number)
M = 1: All axes
10
(Data area)

(Need not be set)

1109
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Diagnosis data has been read from the CNC normally.
3 : The specified diagnosis data number is invalid.
4 : The data specified as the data attribute is invalid because it is
neither 0, 1, nor a value from 1 to n (n is the number of axes).
6 : An option required for reading the specified diagnosis data, such
as the remote buffer option, is not provided.

[Output data structure]

Top address + 0
(Function code)
33

2
(Completion code)
?
(See the explanation of When no axis or one axis is specified
the completion codes.) L = 1 : Bit or byte parameter
4 L = 2: Word parameter
(Data length) L = 4: Double Word parameter
L
(L = 1, 2, 4, 1*n, 2*n, 4*n)
When all axes are specified
6 L = 1*n Bit or byte parameter
(Data number) L = 2*n: Word parameter
N L = 4*n: Double word parameter
(N: Input data)

8
(Data attribute)
M
(M: Input data) Value

10 Diagnosis data Datadependentform

1110
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.23 [Description]
Reading A/D The digital value converted from the load current of the CNCcontrolled
Conversion Data axis can be read. The input data from the generalpurpose analog input
can also be read.

[Input data structure]

Top address + 0
(Function code)
34

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Type of analog voltage)

8
(Data attribute)
M
(M 1 to 8: Axis specification)
10
(Data area)

(Need not be set)

(a) Type of analog voltage (data number)

N Type of analog voltage


0 Generalpurpose analog voltage information
(for four channels)
2 Load information for the CNCcontrolled axes

CAUTION
Only onepath control of the Power Mate MODELD is
provided with one channel of generalpurpose analog
voltage information.

1111
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

(b) Specifying a CNCcontrolled axis (data attribute)


Specify a CNCcontrolled axis for which the voltage conversion
data for the load current is to be read. Data must be specified
according to the following table (Valid with the FS16A/18A and
FS16B (interface type A)):

Specification of CNC controlledaxis


Specified data Connector in the CNC
1 JV1 (MAIN BOARD)
2 JV2 (MAIN BOARD)
3 JV3 (MAIN BOARD)
4 JV4 (MAIN BOARD)
5 JV5 (OPTION BOARD)
6 JV6 (OPTION BOARD)
7 JV7 (OPTION BOARD)
8 JV8 (OPTION BOARD)

CAUTION
For generalpurpose analog input
Other than the i series
The OPTION2 board is required. Analog input is performed
through the analog signal interface. For details, refer to the
description of the analog signal interface in the connection
manual (hardware).
i series
Generalpurpose analog input is not supported. Use the
I/O Link analog input module.

[Completion codes]
0 : A/D conversion data has been read normally.
3 : The data specified for the data number is invalid.
4 : The data specified for the data attribute is invalid, or the specified
axis number is greater than the number of controlled axes.
6 : No analog input module is connected.

1112
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address + 0
(Function code)
34

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
2

6
(Data number)
N
(Input data)

8
(Data attribute)
M
(Input data) Value

10 A/D conversion data (2 bytes) Binary number from 0 to 255


AD
For general purpose analog

10 A/D conversion data (2 bytes) Binary number from 0 to "6554


AD
For CNC controlled axis
load information

(a) A/D conversion data (AD) of CNC controlled axis load information
The load current for the specified CNC controlled axis is converted
into analog voltage, the input to the A/D converter to output a digital
data.
The value actually set in the AD field is obtained from the following
formula:

(AD) N + Load current [A


6554 peak]

AD = A/D conversion data [Value read by the window function (")]


N = Nominal current limit for the amplifier corresponding to the motor
For the nominal current limits, see the table below or the
descriptions of the control motor.

(b) A/D conversion data (A/D) for generalpurpose analog voltage


information
In A/D conversion data (A/D), 0 corresponds to 10V, 128
corresponds to 0V, 255 corresponds to +10V, and other values
correspond in a direct proportion to these values.

(AD * 128) N + Load current [A


128 peak]

AD = A/D conversion data [Value read by the window function (")]


N = Nominal current limit for the amplifier corresponding to the motor
For the nominal current limits, see the table below or the descrip-
tions of the control motor.

1113
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

Servo amplifier module Applicable motor model Nominal current limit

Model Connected axis

SVM112 12Ap
SVM212/12 L and M axes
SVM212/20 L axis 0.5/3000
SVM212/40 L axis 1/3000
SVM312/12/12 L, M, and N axes 2/2000
SVM312/12/20 L and M axes 2/3000
SVM312/20/20 L axis
SVM312/12/40 L and M axes
SVM312/20/40 L axis

SVM120 20Ap
SVM212/20 M axis
SVM220/20 L and M axes C3/2000
SVM220/40 L axis C6/2000
SVM312/12/20 N axis C12/2000
SVM312/20/20 M and N axes
SVM320/20/20 L, M, and N axes
SVM312/20/40 M axis
SVM320/20/40 L and M axes

SVM140S 3/3000 40Ap


6/2000
M3/3000
L3/3000

SVM212/40 M axis 3/3000 40Ap


SVM220/40 M axis 6/2000
SVM240/40 M axis 12/2000
SVM312/12/40 N axis M3/3000
SVM312/20/40 N axis L3/3000
SVM320/20/40 N axis C22/1500

SVM140L 3/3000 40Ap


SVM240/80 L axis 6/2000
12/2000
22/1500
M3/3000
L3/3000
C22/1500

SVM180 6/3000 80Ap


SVM240/80 L axis 12/3000
SVM280/80 L and M axes 22/2000
30/1200
M6/3000
M9/3000
L6/3000
L9/3000

SVM1130 30/2000 130Ap


40/2000
22/3000
30/3000
40/2000 (with a fan)
L25/3000
L50/2000

NOTE
1 The current limits (peak values) are standard values. The operation value variation due to a
circuit constant is about +10%.
2 SVM1130 requires forced air cooling when the 22/3000, 30/3000, 40/2000 (with a fan),
L25/3000, or L50/2000 is driven. At this time, the rated output current is 51.0 Arms.

1114
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.24 [Description]
Reading Tool Life By specifying a tool No., the No. of the tool group to which the specified
Management Data tool belongs can be read from tool life management data.
(Tool Group No.)

[Input data structure]

Top address + 0
(Function code)
38

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute)
M
(M : Tool No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for the tool No., the No. of the tool group
currently used is read. In this case, if a tool group No. has
not been specified since the power to the CNC was turned
on, 0 is output.
If the same tool belongs to two or more tool groups, the Nos.
of all tool groups to which the tool belongs are displayed.

1115
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool group No. has been read normally.
4 : The value specified for the data attribute is invalid.
5 : The specified tool No. was not found.
6 : The tool life management option has not been added.

[Output data structure]

Top address + 0
(Function code)
38

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L L = 4 to 4 n
(L = 4 n) n is the number of tool groups to
which the specified tool belongs.
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value

10 Tool group No. (4 bytes) Unsigned binary

When the specified tool belongs to two or more tool groups

10 Tool group No. (4 bytes) Unsigned binary

14 Tool group No. (4 bytes)

18 Tool group No. (4 bytes)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1116
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.25 [Description]
Reading Tool Life The number of tool groups in tool life management data can be read.
Management Data The number of tool groups that can be registered varies depending on the
(Number of Tool setting of parameter 6800 of the CNC, as indicated in the following table.
Groups)
Parameter 6800
Number of tools
The numbers in parentheses apply when the additional
GS2 GS1 option is used
M series T series
0 0 1 to 16 (1 to 64) 1 to 16 (1 to 16)
0 1 1 to 32 (1 to 128) 1 to 32 (1 to 32)
1 0 1 to 64 (1 to 256) 1 to 64 (1 to 64)
1 1 1 to 128 (1 to 512) 1 to 16 (1 to 128)
M series: For Machining Centers T series: For Lathes

[Input data structure]

Top address + 0
(Function code)
39

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

1117
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The number of tool group Nos. has been read normally.
6 : The tool life management option has not been added.

[Output data structure]

Top address + 0
(Function code)
39

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)

8
(Data attribute)

Value

10 Number of tool groups (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1118
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.26 [Description]
Reading Tool Life By specifying a tool group No., the number of tools that belong to the tool
Management Data group can be read from tool life management data.
(Number of Tools) The number of tools that can be registered varies depending on the setting
of parameter 6800 of the CNC, as indicated in the following table.

Parameter 6800
Number of tools
The numbers in parentheses apply when the additional
GS2 GS1 option is used
M series T series
0 0 1 to 16 (1 to 64) 1 to 16 (1 to 16)
0 1 1 to 32 (1 to 128) 1 to 32 (1 to 32)
1 0 1 to 64 (1 to 256) 1 to 64 (1 to 64)
1 1 1 to 128 (1 to 512) 1 to 16 (1 to 128)
M series: For Machining Centers T series: For Lathes

[Input data structure]

Top address + 0
(Function code)
40

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

1119
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

CAUTION
If 0 is specified for the tool group No., the number of tools
that belong to the tool group currently used is read. In this
case, if a tool group No. has not been specified since the
power to the CNC was turned on, 0 is output.

[Completion codes]
0 : The number of tools has been read normally.
3 : The specified tool group No. is invalid.
6 : The tool life management option has not been added.

[Output data structure]

Top address + 0
(Function code)
40

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)

Value

10 Number of tools (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1120
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.27 [Description]
Reading Tool Life By specifying a tool group No., the life of tools belonging to the tool
Management Data group can be read from tool life management data.
(Tool Life) Whether to display the tool life in minutes or the number of cycles is
(not Supported by the selected by bit 2 of parameter 6800 (LTM) for the CNC.
Power Mate D, F, or
Series 21TA) [Input data structure]

Top address + 0
(Function code)
41

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for the tool group No., the tool life of the tool
group currently used is read. In this case, if a tool group No.
has not been specified since the power to the CNC was
turned on, 0 is output.

1121
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool life has been read normally.
3 : The specified tool group No. is invalid.
6 : The tool life management option has not been added.

[Output data structure]

Top address + 0
(Function code)
41

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)

Value

Tool life (4 bytes) Unsigned binary


10
Unit: Time (minutes) or
number of cycles

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1122
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.28 [Description]
Reading Tool Life By specifying a tool group No., the tool life counter for the specified tool
Management Data group can be read from tool life management data.
(Tool Life Counter)

[Input data structure]

Top address + 0
(Function code)
42

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)

8
(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for the tool group No., the tool life counter
for the tool group currently used is read. In this case, if a tool
group No. has not been specified since the power to the
CNC was turned on, 0 is output.

1123
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool life has been read normally.
3 : The specified tool group No. is invalid.
6 : The tool life management option has not been added.

[Output data structure]

Top address + 0
(Function code)
42

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)

Value

Tool life counter (4 bytes) Unsigned binary


10
Unit: Time (minutes) or
number of cycles

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1124
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.29 [Description]
Reading Tool Life By specifying a tool group No. and a tool No., the tool length
Management Data compensation No. for the specified tool can be read from tool life
(Tool Length management data. This function is available only with the M series
CNCs.
Compensation No. (1):
Tool No.)

[Input data structure]

Top address + 0
(Function code)
43

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)

8
(Data attribute)
M
(M: Tool No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for both the tool group No. and tool No., the
Nos. of the tool group and tool currently used are read. In
this case, if a tool group No. has not been specified since
the power to the CNC was turned on, 0 is output.
For the T series CNCs, 0 is always output.

1125
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool length compensation No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool No. is invalid.
5 : The specified tool No. was not found in the specified tool group.
6 : The tool life management option has not been added.

[Output data structure]

Top address + 0
(Function code)
43

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value

10 Tool length compensation No. (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1126
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.30 [Description]
Reading Tool Life By specifying a tool group No. and tool order No., the tool length
Management Data compensation No. for the specified tool can be read from tool life
(Tool Length management data. This function is available only with the M series CNCs.
Compensation No. (2):
Tool Order No.)

[Input data structure]


Top address + 0

(Function code)
44

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)
8
(Data attribute)
M
(M: Tool order No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for the tool group No., the No. of the tool
group currently used is read. In this case, if a tool group No.
has not been specified since the power to the CNC was
turned on, 0 is output.
When 0 is specified for the tool order No., if the specified tool
group has been used, the tool currently used is read. In this
case, if the specified tool group has not been used, the first
tool in the group is read.
For the T series CNCs, 0 is always output.

1127
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool length compensation No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool order is invalid.
5: The tool having the specified tool order is not registered in the
specified tool group.
6 : The tool life management option has not been added.

[Output data structure]


Top address + 0
(Function code)
44

2 (Completion code)
?
(See the explanation of
the completion codes.)
4

(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Tool length compensation No. (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1128
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.31 [Description]
Reading Tool Life By specifying a tool group No. and a tool No., the cutter compensation
Management Data No. for the specified tool can be read from tool life management data.
(Cutter Compensation This function is available only with the M series CNCs.
No. (1): Tool No.)

[Input data structure]


Top address + 0

(Function code)
45

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)
8
(Data attribute)
M
(M : Tool No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for both tool group No. and tool No., the Nos.
of the tool group and tool currently used are read. If a tool
group No. has not been specified since the power to the
CNC was turned on, 0 is output.
For the T series CNCs, 0 is always read.

1129
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The cutter compensation No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool No. is invalid.
5 : The specified tool No. was not found in the specified tool group.
6 : The tool life management option has not been added.

[Output data structure]


Top address + 0
(Function code)
45

2 (Completion code)
?
(See the explanation of
the completion codes.)
4

(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Cutter compensation No. (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1130
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.32 [Description]
Reading Tool Life By specifying a tool group No. and a tool order No., the cutter compensation
Management Data No. for the specified tool can be read from tool life management data. This
(Cutter Compensation function is available only with the M series CNCs.
No. (2): Tool Order No.)

[Input data structure]


Top address + 0

(Function code)
46

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)
8
(Data attribute)
M
(M: Tool order No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for the tool group No., the No. of the tool
group currently used is referenced. In this case, if a tool
group No. has not been specified since the power to the
CNC was turned on, 0 is output.
When 0 is specified for the tool order No., if the specified tool
group has been used, the tool currently used is read. In this
case, if the specified tool group has not been used, the first
tool in the group is referred to.
For the T series CNCs, 0 is always output.

1131
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The cutter compensation No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool order No. is invalid.
5: The tool having the specified tool order is not registered in the
specified tool group.
6 : The tool life management option has not been added.

[Output data structure]


Top address + 0
(Function code)
46

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Cutter compensation No. (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1132
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.33 [Description]
Reading Tool Life By specifying a tool group No. and a tool No., the information for the
Management Data specified tool can be read from tool life management data.
(Tool Information (1) :
Tool No.)

[Input data structure]


Top address + 0

(Function code)
47

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)
8
(Data attribute)
M
(M: Tool No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for both tool group No. and tool No., the Nos.
of the tool group and tool currently used are referenced.
If neither a tool group No. nor a tool No. has been specified
since the power to the CNC was turned on, 0 is output.

1133
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool group No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool No. is invalid.
5 : The specified tool No. was not found in the specified tool group.
6 : The tool life management option has not been added.

[Output data structure]


Top address + 0
(Function code)
47

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Number of tools (4 bytes) 0: See Note) on the previous page.
1: The tool is registered.
2: The tool has reached the end of its life.
3: The tool was skipped.
The three highorder bytes are fixed to 0.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1134
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.34 [Description]
Reading Tool Life By specifying a tool group No. and a tool order No., the information for
Management Data the specified tool can be read from tool life management data.
(Tool Information (2):
Tool Order No.)

[Input data structure]

Top address + 0
(Function code)
48

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)
8
(Data attribute)
M
(M: Tool order No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
If 0 is specified for the tool group No., the No. of the tool
group currently used is read. If a tool group No. has not
been specified since the power to the CNC was turned on,
0 is output.
When 0 is specified for the tool order No., if the specified tool
group has ever been used, the tool currently used is read.
In this case, if the specified tool group has not been used,
the first tool in the group is referred to.

1135
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool group No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool order No. is invalid.
5: The tool having the specified tool order is not registered in the
specified tool group.
6 : The tool life management option has not been added.

[Output data structure]


Top address + 0
(Function code)
48

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Tool information (4 bytes) 0: See Note) on the previous page.
1: The tool is registered.
2: The tool has reached the end of its life.
3: The tool was skipped.
The three highorder bytes are fixed to 0.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1136
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.35 [Description]
Reading Tool Life By specifying a tool group No. and a tool order No., the No. of the
Management Data corresponding tool can be read from tool life management data.
(Tool No.)

[Input data structure]


Top address + 0

(Function code)
49

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Tool group No.)
8
(Data attribute)
M
(M: Tool order No.)

10
(Data area)

(Need not be set)

X X

42

CAUTION
When 0 is specified for the tool group No., the tool group
currently used is referenced. If neither a tool group No. nor
a tool No. has been specified since the power to the CNC
was turned on, however, 0 is output for the tool group No.
When 0 is specified for the tool order No., if the specified tool
group has been used, the tool currently used is referred to.
If the specified tool group has not been used, the first tool
in the group is referenced.

1137
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool No. has been read normally.
3 : The specified tool group No. is invalid.
4 : The specified tool order No. is invalid.
6 : The tool life management option has not been added.

[Output data structure]


Top address + 0
(Function code)
49

2
(Completion code)
?
(See the explanation of
the completion codes.)
4

(Data length)
4

6
(Data number)
N
(N: Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Tool No. (4 bytes) Unsigned binary

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1138
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.36 [Description]
Reading the Actual The actual speed of the spindle can be read from the CNC.
Spindle Speed
[Input data structure]
Top address + 0

(Function code)
50

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

(Data number)
0

(Data attribute)
0

10
(Data area)

(Need not be set)

X X

42

1139
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The actual speed of the spindle has been read normally.
[Output data structure]
Top address + 0
(Function code)
50

2 (Completion code)
?
(See the explanation of
the completion codes.)
4

(Data length)
4

(Data number)

(Data attribute)
Value
10
Actual spindle speed Unsigned binary
<Data unit>
min1

1140
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.37 [Description]
Entering Data on the On the program check screen of the CNC, data can be entered for the
Program Check Screen spindle tool No. (HD.T) and the next tool No. (NX.T). This function is
(:Lowspeed available only with the M series CNCs.
Response) This function is effective only when bit 2 of parameter 3108 is 1.
(not available for
Power MateD/F,
Series 21TA) [Input data structure]
Top address + 0
(Function code)
150

2
(Completion code)

(Need not be set)

(Data length)
4

6
(Data number) N = 0 : Spindle tool No. (8 digits)
N
(N = 0, 1)
N = 1 : Next tool No. (8 digits)
8

(Data attribute)
0 Value
10
Data for the spindle tool No. Unsigned binary
(4 bytes)
or data for the next tool No.
(4 bytes)

1141
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Data has been entered on the program check screen normally.
2 : The data length in bytes is invalid.
3 : The data No. is invalid.

[Output data structure]


Top address + 0
(Function code)
150

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
4
(Input data)
6
(Data number) N = 0 : Spindle tool No. (8 digits)
N
(Input data)
N = 1 : Next tool No. (8 digits)
8
(Data attribute)

(Input data) Value
10
Data for the spindle tool No. Unsigned binary
(4 bytes)
or data for the next tool No.
(4 bytes)

1142
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.38 [Description]
Reading Clock Data The current date (year, month, day) and time (hours, minutes, seconds)
(Date and Time) can be read from the clock built into the CNC.
(not available for
Power MateF) [Input data structure]
Top address + 0
(Function code)
151

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)
6 N = 1: Reads current date and time.
(Data number)
N N = 0: Reads current date.
(N = 0, 1)
8 N = 1: Reads current time.

(Data attribute)
0

10
(Data area)

(Need not be set)

[Completion codes]
0 : Data of the clock built into the CNC has been read normally.
3 : A value other than 0, 1, and 1 was specified for the data No.

1143
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]


Top address + 0
(Function code)
151

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
6/12

6
(Data number)
N
(Input data)
8
(Data attribute)

(Input data) Value
10
Current date (year) or time (hours) Unsigned binary

12
Current date (month) or time (minutes)

14
Current date (day) or time (seconds)

When both the current date and current time are specified to be read by entering [1] for the data No.


(Input data) Value
10
Current date (year) Unsigned binary
12
Current date (month)
14
Current date (day)
16
Current time (hours)
18
Current time (minutes)
20
Current time (seconds)

[Example] September 10th, 1990 [Example] 23:59:59


(hours:minutes:seconds)
Data area Data area
1990 23
+2 +2
9 59
+4 +4
10 59

1144
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.39 [Description]
Entering Torque Limit Torque limit values for the digital servo motor can be entered.
Data for the Digital
Servo Motor
(:Lowspeed
Response) [Input data structure]
Top address + 0
(Function code)
152

2
(Completion code)

(Need not be set)

(Data length)
2

6
(Data number)
0

8
(Data attribute)
M M = 1 to n: Axis No.
(M: 1 to n)

Value
10
Torque limit data Unsigned binary
(1 byte) <Unit: %>
The highorder byte is always set to 0. Values from 0 to 255 correspond to 0%
to 100%.

[Example] To specify a torque limit of 50%, enter 128.

1145
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Torque limit data has been entered normally.
4 : The specified data attribute is invalid. That is, a value other than
1 to n (number of axes) was specified, or the specified axis No. was
greater than the number of controlled axes.

[Output data structure]


Top address + 0
(Function code)
152

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
2
(Input data)
6
(Data number)

(Input data)
8
(Data attribute)
M
(M: Input data) Value
10
Torque limit data (1 byte): Input data Unsigned binary
The highorder byte is always set to 0. <Unit: %>
Values from 0 to 255 correspond to 0%
to 100%.

1146
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.40 [Description]
Reading Load Load information of the serial spindle can be read.
Information of the The equation to normalize the load information is shown below
Spindle Motor (Serial
Load (%) + L l
Interface) 32767
L: Data read from the window
: The percentage of the maximum output of the motor to the
continuous rated output of the motor (When the maximum output
is 180% and the continuous rated output is 100%, the percentage
is 180.)

CAUTION
is equal to the value of parameter No. 4127.

[Input data structure]


Top address + 0

(Function code)
153

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N N= 0: Read the load of the No.1 spindle.
(Need not be set) 1: Read the load of the No.2 spindle.
2: Read the load of the No.3 spindle.
8 3: Read the load of the No.4 spindle.
1: Read the loads of the No.1 and No.2 spindles.
(Data attribute) 2: Read the loads of the No.1 to No.3 spindles.
0 3: Read the loads of the No.1 to No.4 spindles.
10
(Data area)

(Need not be set)

X X

42

1147
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Load information of the serial spindle has been read normally.

[Output data structure]


Top address + 0
(Function code)
153

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
L = 2: Specifies the first axis.
(Data length)
L
(L = 2, 4)
L = 4: Specifies all axes.
6 N= 0: Read the load of the No.1 spindle.
(Data number) 1: Read the load of the No.2 spindle.
N 2: Read the load of the No.3 spindle.
(N: Input data) 3: Read the load of the No.4 spindle.
1: Read the loads of the No.1 and No.2 spindles.
8 2: Read the loads of the No.1 to No.3 spindles.
3: Read the loads of the No.1 to No.4 spindles.
(Data attribute)
Value
10
Load information of the serial spindle Unsigned binary, 2 bytes long
(first or second axis)

When two axes are specified

(Data attribute)
Value
10
First axis in the load information of the Unsigned binary, 2 bytes long
serial spindle
12
Second axis in the load information of
the serial spindle

1148
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

When three axes are specified

(Data attribute)
Value
10
First axis in the load information of the Unsigned binary, 2 bytes long
serial spindle
12
Second axis in the load information of
the serial spindle
14
Third axis in the load information of the
serial spindle

When four axes are specified

(Data attribute)
Value
10
First axis in the load information of the Unsigned binary, 2 bytes long
serial spindle
12
Second axis in the load information of
the serial spindle
14
Third axis in the load information of the
serial spindle
16
Fourth axis in the load information of
the serial spindle

1149
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.41 [Description]
Reading a Parameter Parameter data in the CNC can be read directly from the CNC via the
(not available for FANUC bus.
Power MateD/F, This function is basically the same as the function described in Section
Series 21TA) B.4.6 Reading a Parameter, except that the function code is 154 and
some of the completion codes are different.

[Input data structure]


Top address + 0

(Function code)
154

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Parameter No.)

8 M=0 : No axis
(Data attribute)
M M = 1 to n : Specific axis
(M: 0, 1 to n, or 1)

10 M = 1 : All axes
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : Parameter data has been read normally.
3 : The parameter No. specified to be read is invalid.
4 : A value other than 0, 1, and 1 to n (number of axes) was specified
for the data attribute.
6 : An option required for setting the parameter to be read, such as the
error compensation option, is not provided.

1150
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.42 [Description]
Reading Set Data Set data stored in the CNC can be read directly from the CNC via the
(not available for FANUC bus.
Power MateD/F, This function is basically the same as the function described in Section
Series 21TA) B.4.8 Reading Set Data, except that the function code is 155 and some
of the completion codes are different.

[Input data structure]


Top address + 0

(Function code)
155

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Setting data No.)

8 M=0 : No axis
(Data attribute)
M M = 1 to n : Specific axis
(M: 0, 1 to n, or 1)

10 M = 1 : All axes
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : Set data has been read normally.
3 : The set data No. specified to be read is invalid.
4 : A value other than 0, 1, and 1 to n (number of axes) was specified
for the data attribute.

1151
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.43 [Description]
Reading Diagnosis Data displayed on the diagnosis data screen of the CNC can be read
Data (not available for directly from the CNC via the FANUC bus.
Power MateD/F, This function is basically the same as the function described in Section
Series 21TA) B.4.22 Reading Diagnosis Data, except that the function code is 156
and some of the completion codes are different.

[Input data structure]


Top address + 0

(Function code)
156

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N: Diagnosis No.)

8 M=0 : No axis
(Data attribute)
M M = 1 to n : Specific axis
(M: Axis number)

10 M = 1 : All axes
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : Diagnosis data has been read normally from the CNC.
3 : The diagnosis No. specified to be read is invalid.
4 : A value other than 0, 1, and 1 to n (number of axes) was specified
for the data attribute.
6 : An option required for using the diagnosis data to be read, such
as the remote buffer option, is not provided.

1152
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.44 [Description]
Reading a Character In a machining program being executed on the CNC, the block currently
String of the CNC executed, the next block, and the next block but one can be read in the
Program Being CNC program format. That is, these blocks can be read in the form of a
Executed in the Buffer character string of ASCII codes. This function is available only with the
M series CNCs.
Comments in a block can also be read.
The maximum number of characters in a character string is fixed to 64.

[Input data structure]

Top address + 0

(Function code)
157

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)

(Need not be set)

8 M=0 : Current block


(Data attribute)
M M = 1 to n : Next block
(M: Specified block)

10 M = 1 : Next block but one


(Data area)

(Need not be set)

X X

74

NOTE
1 When data specified by the NC is a macro statement, the
character string cannot be read correctly.
2 When data attribute M is set to 2, the next block but one can
be read only when the next block is an instruction for tool
diameter compensation C.

1153
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The character string of the CNC program being executed in the
buffer has been read normally.
4 : The value specified for the data attribute is invalid.

[Output data structure]


Top address + 0
(Function code)
157

2
(Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length) 64 characters
64

(Data number)

8
(Data attribute)
M
(M: Specified block)
10
NC command data for the first character ASCII code
RC(1) If a block consists of less than 64
characters, the remaining bytes are
11 NC command data for the second filled with 20H (space).
character
RC(2)

X X X
X X X

73
NC command data for the 64th character
RC(64)

1154
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.45 [Description]
Reading the Relative The relative coordinates of the machine moving along an axis controlled
Position on a by the CNC can be read.
Controlled Axis
[Input data structure]
Top address + 0

(Function code)
74

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute) M = 1 to n : Reads the relative coordinates of
M each axis. n is an axis No.
(M: Axis number)
M = 1 : Reads the relative coordinates of
10 all axes.
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : The relative coordinates on the controlled axis have been read
normally.
4 : The specified data attribute is invalid. That is, a value other than
1 and 1 to n (number of axes) was specified, or the specified axis
No. was greater than the number of controlled axes.

1155
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]


Top address + 0
(Function code)
74

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = 4*n. n is the number of
specified axes.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value
10
Relative coordinates on the specified Signed binary
controlled axis (4 bytes) (A negative value is represented in 2s
complement.)

When the number of controlled axes is 4

Value
10
Relative coordinates on the first axis Signed binary
(4 bytes) (A negative value is represented in 2s
complement.)
14
Relative coordinates on the second
axis (4 bytes)
18
Relative coordinates on the third axis
(4 bytes)
22
Relative coordinates on the fourth axis
(4 bytes)

Output data unit


Input system Increment system ISB Increment system ISC
mm, deg system 0.001 0.0001
inch system 0.0001 0.00001
0.001 0.0001
mm, deg system
0.001 0.0001
0.0001 0.00001
inch system
0.0001 0.00001

Double values can be read for a machining center system or when radius
specification is used for the relevant axis of a lathe system.

1156
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.46 [Description]
Reading the Remaining The remaining travel of the machine along an axis controlled by the CNC
Travel can be read. The read value equals the remaining travel indicated on the
current position display screen on the CNC. (This screen can be called
by pressing the function button POS.)

[Input data structure]


Top address + 0

(Function code)
75

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute) M = 1 to n: Reads the remaining travel along
M each axis. n is an axis No.
(M: Axis number)
M = 1 : Reads the remaining travel along all
10 axes.
(Data area)

(Need not be set)

X X

42

[Completion codes]
0 : The remaining travel along the controlled axis has beenread
normally.
4 : The specified data attribute is invalid. That is, a value other than
1 and 1 to n (number of axes) was specified, or the specified axis
No. was greater than the number of controlled axes.

1157
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address + 0
(Function code)
75

2 (Completion code)
?
(See the explanation of
the completion codes.)
4
(Data length)
L
(L = 4*n. n is the number of
specified axes.)
6
(Data number)

8
(Data attribute)
M
(M: Input data) Value
10
Remaining travel along the specified Signed binary
controlled axis (4 bytes) (A negative value is represented in 2s
complement.)

When the number of controlled axes is 4

Value
10
Remaining travel along the first axis Signed binary
(4 bytes) (A negative value is represented in 2s
complement.)
14
Remaining travel along the second
axis (4 bytes)
18
Remaining travel along the third axis
(4 bytes)
22
Remaining travel along the fourth axis
(4 bytes)

Output data unit


Increment Increment
Input system
system ISB system ISC
Machining center mm, deg
0.001 0.0001
system system
Power MateD, F inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.0005 0.00005
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.00005 0.000005
specification

1158
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.47 [Description]
Reading CNC Status Status information (status indication on the screen) can be read from the
Information CNC.
The types of status information that can be read are as follows.
(1) Indication of which mode is selected, automatic or manual
(2) Status of automatic operation
(3) Status of movement along the axis and dwelling
(4) Status of M, S, T, and B functions
(5) Statuses of emergency stop and the reset signal
(6) Alarm status
(7) Status of program edit
(Indication)

13 (5)
EMG
(1) (2) (3) (4) (6) (7)
14 EDIT STOP MTN FIN ALM 16:52:13 READ 14

15 (Soft key indication) 15


00 05 10 15 20 25 30 35

[Input data structure]


Top address + 0

(Function code)
76

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
0

8
(Data attribute)
0

10

(Data area)
X X
(Need not be set)

42

1159
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : CNC status information has been read normally.
[Output data structure]
Top address + 0
(Function code)
76

2
(Completion code)
?
(See the explanation of
the completion codes.)
4

(Data length)
14

6
(Data number)

(Input data)

8
(Data attribute)

(Input data) Value
10
Indication of which mode is currently 0 : MDI
selected, automatic or manual 1 : MEMory
(2 bytes) 2 : **** (Other states)
3 : EDIT
4 : HaNDle
5 : JOG
6 : Teach in JOG
7 : Teach in HND
8 : INC. feed
9 : REFerence
10: ReMoTe
12
Status of automatic operation (2 bytes) 0 : **** (Reset states)
1 : STOP
2 : HOLD
3 : STaRT
14 Status of movement along the axis or 0 : *** (Other states)
dwelling (2 bytes) 1 : MoTioN
2 : DWell

16 Status of M, S, T, and B functions 0 : *** (Other states)


(2 bytes) 1 : FIN
18 Status of emergency stop (2 bytes) 0 : (Releases the emergency stop state)
1 : EMerGency
2 : RESET
(The reset signal is on.)
20 Alarm status (2 bytes) 0 : *** (Other states)
1 : ALarM
2 : BATtery low
22
Status of program edit (2 bytes) 0 : ******* (Non editing)
1 : EDIT
2 : SeaRCH
3 : OUTPUT
4 : INPUT
5 : COMPARE
6 : LabelSKip
7 : OFST
8 : WSFT
9 : ReSTaRt

1160
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.48 [Description]
Reading Value of the This function gets the value of variable for Macrocompiler (Pcode
Pcode Macro Variable macro variable) of specified number.
(:Lowspeed The extended Pcode macro variable is not able to be read.
Response)
[Input data structure]
Top address + 0

(Function code)
59

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)
+6
(Data number)
N
(Pcode macro variable number)

+ 10
(Data attribute)
0

+ 12
(Data area)

(Need not be set)

+ 18

CAUTION
The Data number occupies 4 bytes instead of 2 bytes of
usual data structure.

1161
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to read the value of Pcode macro variable.
3 : The Pcode macro variable specified by Data number is not able
to be read.
5 : The value of the Pcode macro variable is out of range
("0.0000001 "99999999).
6 : No option, or no Macro ROM module.
[Output data structure]
Top address + 0
(Function code)
59

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
6

+6
(Data number)
N
(Same as input data)

+ 10
(Data attribute)

(Same as input data) Value
+ 12
Value of Pcode macro variable Signed binary
(4bytes) (Minus number is represented by 2s
complemental)

+ 16 Figures after decimal point of the value Signed binary


(2bytes) (Minus number is represented by 2s
complemental)

1162
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.49 [Description]
Writing Value of the This function stores the value into the variable for Macrocompiler
Pcode Macro Variable (Pcode macro variable) of specified number.
(:Lowspeed The extended Pcode macro variable is not able to be written into.
Response)
[Input data structure]
Top address + 0
(Function code)
60

+2
(Completion code)

(Need not be set)

+4
(Data length)
6

+6
(Data number)
N
(Pcode macro variable number)

+ 10
(Data attribute)
0 Value
+ 12
Value of Pcode macro variable Signed binary
(4bytes) (Minus number is represented by 2s
complemental)

+ 16
Figures after decimal point of the value Signed binary
(2bytes) (Minus number is represented by 2s
complemental)

CAUTION
The data number occupies 4 bytes instead of 2 bytes of
usual data structure.

1163
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to store the value into Pcode macro variable.
2 : The data length has illegal data (is not 6).
3 : The Pcode macro variable specified by Data number is not able
to be written.
6 : No option, or no Macro ROM module.

[Output data structure]


Top address + 0

(Function code)
60

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
6
(Same as input data)

+6
(Data number)
N
(Same as input data)

+ 10
(Data attribute)

(Same as input data)

+ 12
Value of Pcode macro variable
(4bytes)

+ 16
Figures after decimal point of the value
(2bytes)

1164
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.50 [Description]
Reading the Tool Life This function gets the Tool life counter type of specified tool group in the
Management Data Tool life management data. (M series only)
(Tool Life Counter
Type)

[Input data structure]


Top address + 0

(Function code)
160

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)
+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
0

+ 10
(Data area)

(Need not be set)

+ 12

CAUTION
About Tool group number (in Data number)
0 as Tool group number indicates the Tool group currently
used.
When Tool group has never specified since poweron, 0
of Tool group number results 0 as counter type.
0 of counter type will be returned on T series.

1165
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to read the Tool life counter type.
3 : The Tool group number is out of range from 0 to 512, or exceeds
the maximum number of registered Tool group.
6 : No option for Tool life management.
[Output data structure]
Top address + 0
(Function code)
160

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
2

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)

(Same as input data) Value
+ 10
Tool life counter type (2bytes) 0 : No counter type
1 : Frequency
2 : Real time (in minutes)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1166
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.51 [Description]
Registering the Tool This function registers the Tool group in Tool life management data, with
Life Management Data Tool number, length of life and Tool life counter type. On T series, the
(Tool Group) Tool life counter type will be specified by the NC parameter LTM
(No.6800#2), and this function cannot set/change the counter type.
(:Lowspeed
Response)

[Input data structure]


Top address + 0
(Function code)
163

+2
(Completion code)

(Need not be set)
+4
(Data length)
8
+6
(Data number)
0

+8
(Data attribute)
M
(M = Tool number) Value
+ 10
Tool group number Unsigned binary
(2bytes) 1512
+ 12
Tool life counter type 1 : Frequency
(2bytes) 2 : Real time in minutes
+ 14
Tool life (4bytes) Unsigned binary
19999 (Frequency)
14300 (Real time in minutes: 1count/4sNote)
11090 (Real time in minutes: 1count/1sNote)

NOTE
The tool life count is changed by parameter 6801#5.
6801#5 = 0 : the life is counted every 4seconds.
6801#5 = 1 : the life is counted every 1second.

[Completion codes]
0 : Success to register the Tool group.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool number in Data attribute has wrong value.
5 : The length of Tool life in Data area is out of range. The Tool life
counter type does not match on T series.
6 : No option for Tool life management.

1167
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]


Top address + 0

(Function code)
163

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
8
(Same as input data)

+6
(Data number)

(Same as input data)

+8
(Data attribute)
M
(Same as input data)
+ 10
Tool group number (2bytes)
(Same as input data)

+ 12
Tool life counter type (2bytes)
(Same as input data)

+ 14
Length of Tool life (4bytes)
(Same as input data)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1168
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.52 [Description]
Writing the Tool Life This function sets the length of Tool life of the specified Tool group in the
Management Data Tool life management data.
(Tool Life)
(:Lowspeed
Response)
[Input data structure]

Top address + 0
(Function code)
164

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
0
Value
+10
Unsigned binary
19999 (Frequency)
14300 (Real time in minutes: 1count/4sNote)
Tool life (4bytes) 11090 (Real time in minutes: 1count/1sNote)
Case of Tool life management data B
1999999 (Frequency)
1100000 (Real time in minutes)

NOTE
The tool life count is changed by parameter 6801#5.
6801#5 = 0 : the life is counted every 4seconds.
6801#5 = 1 : the life is counted every 1second.

1169
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the length of Tool life.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
5 : The length of Tool life is out of range.
6 : No option for Tool life management.
13 : The data of the currently selected tool group or the next tool group
cannot be rewritten. An attempt was made to rewrite the data of
the currently selected tool group or the next group.
[Output data structure]

Top address +0
(Function code)
164

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)

(Same as input data)

+10
Length of Tool life (4bytes)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1170
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.53 [Description]
Writing the Tool Life This function sets the Tool life counter in the specified Tool group in the
Management Data Tool life management data.
(Tool Life Counter)
(:Lowspeed
Response)
[Input data structure]

Top address + 0
(Function code)
165

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8

(Data attribute)
0 Value
+10
Tool life counter (4bytes) Unsigned binary
19999 (Frequency)
14300 (Real time in minutes: 1count/4sNote)
11090 (Real time in minutes: 1count/1sNote)
Case of Tool life management data B
1999999 (Frequency)
1100000 (Real time in minutes)

NOTE
The tool life count is changed by parameter 6801#5.
6801#5 = 0 : the life is counted every 4seconds.
6801#5 = 1 : the life is counted every 1second.

1171
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Tool life counter.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
5 : The value for Tool life counter is out of range.
6 : No option for Tool life management.
[Output data structure]

Top address + 0
(Function code)
165

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)

(Same as input data)

+10
Length of Tool life (4bytes)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1172
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.54 [Description]
Writing the Tool Life This function sets the Tool life counter type of specified Tool group in the
Management Data Tool life management data. (M series only)
(Tool Life Counter
Type) (:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
166

+2
(Completion code)

(Need not be set)

+4

(Data length)
2

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
0
Value
+10
Tool life counter type (2bytes) 1 : Frequency
2 : Real time in minutes

1173
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Tool life counter type.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
5 : The value for Tool life counter type is wrong.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
166

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
2
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)

(Same as input data)

+10
Tool life counter type (2bytes)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1174
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.55 [Description]
Writing the Tool Life This function sets the Tool length offset number of the specified Tool
Management Data group in the Tool life management data. (M series only)
(Tool Length Offset
Number (1) : Tool
Number) (:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
167

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool number) Value
+10
Tool length offset number (4bytes) Unsigned binary
1255

1175
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Tool length offset number.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool number in Data attribute has wrong value.
5 : The Tool number is not found in the Tool group.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
167

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Tool length offset number (4bytes)

CAUTION
The effective value for Tool length offset number depends
on Tool compensation number available on NC.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1176
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.56 [Description]
Writing the Tool Life This function sets the Tool length offset number of the Tool of the
Management Data specified Tool operation sequence number in the Tool life management
(Tool Length Offset data. (M series only)
Number (2) : Tool
Operation Sequence
Number) (:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
168

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool operation sequence number) Value
+10
Tool length offset number (4bytes) Unsigned binary
1255

1177
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Tool length offset number.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool operation sequence number is wrong.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
168

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Tool length offset number (4bytes)

CAUTION
The effective value for Tool length offset number depends
on Tool compensation number available on NC.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1178
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.57 [Description]
Writing the Tool Life This function sets the Cutter compensation number of the specified Tool
Management Data group in the Tool life management data. (M series only)
(Cutter Compensation
Number (1) : Tool
Number) (:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
169

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool number) Value
+10
Cutter compensation number (4bytes) Unsigned binary
1255

1179
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Cutter compensation number.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool number in Data attribute has wrong value.
5 : The Tool number is not found in the Tool group.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
169

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Cutter compensation number (4bytes)

CAUTION
The effective value for Cutter compensation number
depends on Tool compensation number available on NC.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1180
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.58 [Description]
Writing the Tool Life This function sets the Cutter compensation number of the Tool of the
Management Data specified Tool operation sequence number in the Tool life management
(Cutter Compensation data. (M series only)
Number (2) : Tool
Operation Sequence
Number) (:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
170

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool operation sequence number) Value
+10
Cutter compensation number (4bytes) Unsigned binary
1255

1181
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Cutter compensation number.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool operation sequence number is wrong.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
170

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Cutter compensation number (4bytes)

CAUTION
The effective value for Cutter compensation number
depends on Tool compensation number available on NC.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1182
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.59 [Description]
Writing the Tool Life This function sets the Tool condition of the specified Tool group in the
Management Data Tool life management data.(M series only)
(Tool Condition (1) :
Tool Number)
(:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
171

+2
(Completion code)

(Need not be set)

+4

(Data length)
2

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool number) Value
+10
Tool condition (2bytes) 1 : Tool state clear
2 : Tool state skip

1183
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Tool condition.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool number in Data attribute has wrong value.
5 : The Tool number is not found in the Tool group.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
171

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
2
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Tool condition (2bytes)

This function changes Tool condition as below.


command before call after call

skip (#) usable ( )


clear skip (#) in use (@)
consumed (*) usable ( )

unused ( ) skip (#)


skip in use (@) skip (#)
consumed (*) skip (*)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1184
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.60 [Description]
Writing the Tool This function sets the Tool condition of the Tool of the specified Tool
Management Data operation sequence number in the Tool life management data.
(Tool Condition (2) :
Tool Operation
Sequence Number)
(:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
172

+2
(Completion code)

(Need not be set)

+4

(Data length)
2

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool operation sequence number) Value
+10
Tool condition (2bytes) 1 : Tool state clear
2 : Tool state skip

1185
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to set the Tool condition.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool operation sequence number is wrong.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
172

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
2
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Tool condition (2bytes)

This function changes Tool condition as shown in B.4.59.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1186
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.61 [Description]
Writing the Tool Life This function registers a tool to the specified Tool group in the Tool life
Management Data management data.
(Tool Number)
(:Lowspeed
Response)

[Input data structure]

Top address + 0
(Function code)
173

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N = Tool group number)

+8
(Data attribute)
M
(M = Tool operation sequence number) Value
+10
Tool number (4bytes) Unsigned binary
19999

1187
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Success to register the Tool number.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
4 : The Tool operation sequence number is wrong.
6 : No option for Tool life management.

[Output data structure]

Top address + 0
(Function code)
173

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)

+6
(Data number)
N
(Same as input data)

+8
(Data attribute)
M
(Same as input data)

+10
Tool number (4bytes)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function.

1188
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.62
Reading the Estimate Power
FS20 FS18 FS16
Mate
Disturbance Torque

Data
: The support is decided by CNC series
: No support

CAUTION
The abnormal load detection function option is required.
For detailed settings of parameters and so forth, refer to the
description of abnormal load detection in the connection
manual (functions).

(1) servo axis


[Description ]
The load torques except a necessary torque for acceleration/ deceleration
of the digital servo axis are read.

[Input data structure]

Top address + 0

(Function code)
211
+2
(Completion code)

(Need not to be set)
+4
(Data length)

(Need not to be set)
+6

(Data number)
0

+8
(Data attribute) M=1 to n : Estimate disturbance torque data
M for specific axis. n is the axis
(M=1 to n or 1) number.
+10
M= 1 : Estimate disturbance torque data
(Data area)
for all axes.

(Need not to be set)
+12

1189
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The estimate disturbance torque data have been read normally.
4 : The data specified as the data attribute is invalid because it is
neither 1 nor a value from 1 to n (n is the number of axes).
Alternatively, the specified axis number is greater than the number
of controlled axes.
[Output data structure]

Top address + 0
(Function code)
211

+2
(Completion code)
?
(See the explanation of the
completion codes. )
+4
(Data length)
L
(L=2 n, n is the number
of axes specified. )
+6
(Data number)
0

+8
(Data attribute)
M
(M : Input data) Value
+10
Estimate disturbance torque data for- (A negative value is represented in 2s
the controlled axis specified complement. )
(2 bytes)
+12

When the number of controlled axes is 4

Value
+10 Estimate disturbance torque
data forfirst axis Signed binary
(2 bytes) (A negative value is represented in 2s
complement. )
+12 Estimate disturbance torque
data forsecond axis
(2 bytes)
+14 Estimate disturbance torque
data forthird axis
(2 bytes)
+16 Estimate disturbance torque
data forfourth axis
(2 bytes)
+18

1190
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

(2) spindle axis


[Description]
The load torques except a necessary torque for acceleration/ deceleration
of the serial spindle axis are read.

[Input data structure]

Top address + 0

(Function code)
211
+2
(Completion code)

(Need not to be set)
+4
(Data length)

(Need not to be set)
+6

(Data number)
1 M= 1 to n: Read the load of each spindle.
(n is the spindle number.)
+8 1: Read the loads of the No.1 and No.2 spindles.
(Data attribute) 2: Read the loads of the No.1 to No.3 spindles.
M 3: Read the loads of the No.1 to No.4 spindles.
(M=1 to n or 1)
+10
(Data area)

(Need not to be set)
+12

1191
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The estimate disturbance torque data have been read normally.
4 : The data specified as the data attribute is invalid because it is neither
1 nor a value from 1 to n (n is the number of axes) . Alternatively,
the specified axis number is greater than the number of controlled
axes.
[Output data structure]
Top address + 0
(Function code)
211

+2
(Completion code)
?
(See the explanation of
the completion codes. )
+4
(Data length)
L
(L=2 n, n is the number
of axes specified. )
+6

(Data number)
1
+8
(Data attribute)
M
(M : Input data) Value
+10
Estimate disturbance torque Signed binary
data forthe controlled axis specified (A negative value is represented in 2s
(2 bytes) complement. )
+12

When the number of controlled axes is 2

Value

+10 Estimate disturbance torque Signed binary


data for first axis (2 bytes) (A negative value is represented in 2s
complement. )
+8+(2 n) Estimate disturbance torque
data forsecond axis (2 bytes)

[supporting soft]
CNC : B005 SERIES Edition K or later
B105 SERIES Edition H or later
B205 SERIES Edition H or later
BD03 SERIES Edition L or later
BE03 SERIES Edition I or later
BF03 SERIES Edition I or later
SERVO : 9060 SERIES Edition J or later
SPINDLE : 9A50 SERIES Edition Q or later
* Some of the series not listed above are supported by the first edition.

1192
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.63 [Description]
Reading the Current This function reads CNC program numbers extended to 8 digits from the
Program Number usual 4 digits.
(8digit Program Basically, this function is the same as function number 24 excluding the
different data length of function code 90.
Numbers)
(not available for
Power MateD/F,
Series 21TA)
[Input data structure]

Top address 0
(Function code)
90

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

(Data number)
0

(Data attribute)
0

10
(Data area)

(Need not be set)

18

[Completion codes]
1 : The read command of the currently executing program could not
be executed. That is, the same command could not be executed as
the data of the program number was being updated on the CNC.
0 : The program number of the currently executing program has been
read normally.

1193
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address 0
(Function code)
200

2
(Completion code)
?
(See the explanation of the completion
codes, above.)
4
(Data length)
8

6
(Data number)

8
(Data attribute)

Value
10
Number of the program currently being Unsigned binary format, 4byte length
executed
ON
14
Program number of the main program
ON

18

(a) Number of the program currently being executed (ON)


The program number of the program currently being executed is set.
(b) Program number of the main program (OFF)
If the program currently being executed is a subprogram, the program
number of its main program is set.
If the program currently being executed is not a subprogram, 0 is set.

1194
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.64 [Description]
Reading Tool Life This function reads the tool group number to which the tool number is
Management Data currently registered.
(Tool Group Number)

[Input data structure]

Top address 0
(Function code)
200

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

(Data number)
0

8
(Data attribute)
M
(M=Tool number)

12
(Data area)

(Need not be set)

16

NOTE
When the tool number is set to 0, the tool group number
of the currently used tool is read.
If a tool group number is not specified after the power is
turned ON, tool group number 0 is read. Also, if a tool
number is registered to two or more tool group numbers, the
tool group numbers of all tool groups to which the tool
number is registered are read.

1195
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool group number was read successfully.
4 : The tool number in Data Attribute has a wrong value.
5 : The tool number is not registered.
6 : The tool life management option has not been added on.

[Output data structure]

Top address 0
(Function code)
200

2
(Completion code)
?
(See the explanation above.)
4
(Data length)
L L=4 to 4 x n
(L=4 n) n is the number of tool group numbers
6 when multiple groups is specified.

(Data number)

8
(Data attribute)
M
(M: entered data) Value
12
Unsigned binary
Tool group number
(4 bytes)
16

Or, when the tool number is registered to multiple groups

Value

12 Tool group number Unsigned binary


(4 bytes)

16 Tool group number


(4 bytes)

20 Tool group number


(4 bytes)

24

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1196
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.65 [Description]
Reading Tool Life This function reads the tool length offset number according to the
Management Data specified tool group number and tool number. (M series only)
(Tool Length Offset
Number 1)

[Input data structure]

Top address 0
(Function code)
227

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N=Tool group number)

8
(Data attribute)
M
(M=Tool number)

12
(Data area)

(Need not be set)

16

CAUTION
When the tool group number and tool number are set to 0,
the currently used tool group and tool number are
referenced.
If a tool group number is not specified after the power is
turned ON, tool group number 0 is read.
0 is always read on the T series.

1197
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool length offset number was read successfully.
3 : The specified tool group number is incorrect.
4 : The specified tool number is incorrect.
5 : The specified tool number is not registered to the specified tool
group.
6 : The tool life management option has not been added on.

[Output data structure]

Top address 0
(Function code)
227

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
4

6
(Data number)
N
(N: entered data)

8
(Data attribute)
M
(M: entered data) Value
12
Unsigned binary
Tool offset number
(4 bytes)

16

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1198
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.66 [Description]
Reading Tool Life This function reads the tool radius offset number according to the
Management Data specified tool group number and tool number. (M series only)
(Tool Diameter Offset
Number 1)

[Input data structure]

Top address 0
(Function code)
228

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N=Tool group number)

8
(Data attribute)
M
(M=Tool number)

12
((Data area))

(Need not be set)

16

CAUTION
When the tool group number and tool number are set to 0,
the currently used tool group and tool number are
referenced.
If a tool group number is not specified after the power is
turned ON, tool group number 0 is read.
0 is always read on the T series.

1199
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool radius offset number was read successfully.
3 : The specified tool group number is incorrect.
4 : The specified tool number is incorrect.
5 : The specified tool number is not registered to the specified tool
group.
6 : The tool life management option has not been added on.

[Output data structure]

Top address 0
(Function code)
228

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
4

6
(Data number)
N
(N: entered data)

8
(Data attribute)
M
(M: entered data) Value
12
Unsigned binary
Tool offset number
(4 bytes)

16

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1200
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.67 [Description]
Reading Tool Life This function reads the tool information (status) according to the specified
Management Data tool group number and tool number.
(Tool Information 1)

[Input data structure]

Top address 0
(Function code)
201

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N=Tool group number)

8
(Data attribute)
M
(M=Tool number)

12
((Data area))

(Need not be set)

16

CAUTION
When the tool group number and tool number are set to 0,
the currently used tool group and tool number are
referenced.
If a tool group number is not specified after the power is
turned ON, tool group number 0 is read.

1201
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool information was read successfully.
3 : The specified tool group number is incorrect.
4 : The specified tool number is incorrect.
5 : The specified tool number is not registered to the specified tool
group.
6 : The tool life management option has not been added on.

[Output data structure]

Top address 0
(Function code)
201

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
4

6
(Data number)
N
(N: entered data)

8
(Data attribute)
M
(M: entered data) Value
12
0: See Note in previous item/
Tool offset number 1: Tool is registered.
(4 bytes) 2: End of tool life.
3: Tool skipped
All above three bytes must be 0.
16

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1202
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.68 [Description]
Writing (Registering) This function registers the tool group number to tool life management
Tool Life Management data. Set the tool number, life value and life counter type to the specified
Data (Tool Group tool group. On the T series, since the life counter type is specified by CNC
parameter LTM (No. 6800#2), it cannot be set nor changed here.
Number) (:Lowspeed
Response)
[Input data structure]

Top address +0
(Function code)
202

+2
(Completion code)

(Need not be set)

+4
(Data length)
8

+6
(Data number)
0

+8

(Data attribute)
M
(M=Tool number)

Value
+12
Unsigned binary
Tool group number 1512
(2 bytes)

+14
Tool life counter type 1: Frequency
(2 bytes) 2: Real time in minutes

+16
Unsigned binary
Tool life 19999 (Frequency)
(4 bytes) 14300 (Real time in minutes: 1count/4sNote)
11090 (Real time in minutes: 1count/1sNote)
Tool life management data B
1999999 (Frequency)
1100000 (Real time in minutes)

NOTE
The tool life count is changed by parameter 6801#5.
6801#5 = 0 : the life is counted every 4seconds.
6801#5 = 1 : the life is counted every 1second.

1203
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : The tool length was registered successfully.
3 : The tool group number exceeded the range 1 to 512 or maximum
number of registered groups.
4 : The tool number in Data Attribute has a wrong value.
5 : The tool life value is outofrange. On the T series, the tool life
counter type is different.
6 : The tool life management option has not been added on.

[Output data structure]


Top address 0
(Function code)
202

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
8
(Entered data)

6
(Data number)

(Entered data)

(Data attribute)
M
(Entered data)

12
Tool group number
(2 bytes)
(Entered data)

14
Tool life counter type
(2 bytes)
(Entered data)

16
Tool life value
(4 bytes)
(Entered data)

20

1204
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1205
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.69 [Description]
Writing Tool Life This function sets the tool length offset number of a specified tool group
Management Data in the tool life management data. (M series only)
(Tool Length Offset
Number 1)
(:Lowspeed
Response)

[Input data structure]

Top address 0
(Function code)
229

2
(Completion code)

(Need not be set)

4
(Data length)
4

6
(Data number)
N
(N=Tool group number)
8

(Data attribute)
M
(M=Tool number)

Value
12
Unsigned binary
Tool length offset number 1 to 255
(4 bytes)

16

1206
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The tool length offset number was written successfully.
3 : The tool group number exceeded the range 1 to 512 or maximum
number of registered groups.
4 : The specified tool number is incorrect.
5 : The specified tool number is not registered to the specified tool
group.
6 : The tool life management option has not been added on.
[Output data structure]
Top address 0
(Function code)
229

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
4
(Entered data)

6
(Data number)
N
(Entered data)

(Data attribute)
M
(Entered data)

12
Tool length offset number
(4 bytes)

16

CAUTION
The tool length offset number that can be actually specified
is reliant on the tool offsets available on the NC.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1207
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.70 [Description]
Writing Tool Life This function sets the tool radius offset number of a tool belonging to a
Management Data specified tool group in the tool life management data. (M series only)
(Tool Radius Offset
Number 1)
(:Lowspeed
Response)

[Input data structure]

Top address 0
(Function code)
230

2
(Completion code)

(Need not be set)

4
(Data length)
4

6
(Data number)
N
(N=Tool group number)
8

(Data attribute)
M
(M=Tool number)

Value
12
Unsigned binary
Tool length offset number 1 to 255
(4 bytes)

16

1208
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : The tool radius offset number was written successfully.
3 : The tool group number exceeded the range 1 to 512 or maximum
number of registered groups.
4 : The specified tool number is incorrect.
5 : The specified tool number is not registered to the specified tool
group.
6 : The tool life management option has not been added on.

[Output data structure]


Top address 0
(Function code)
230

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
4
(Entered data)

6
(Data number)
N
(Entered data)

(Data attribute)
M
(Entered data)

12
Tool length offset number
(4 bytes)

16

CAUTION
The tool length offset number that can be actually specified
is reliant on the tool offsets available on the NC.

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1209
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.71 [Description]
Writing Tool Life This function sets the tool information of a tool belonging to a specified
Management Data tool group in the tool life management data. (M series only)
(Tool Information 1)
(:Lowspeed
Response)

[Input data structure]

Top address 0
(Function code)
231

2
(Completion code)

(Need not be set)

4
(Data length)
2

6
(Data number)
N
(N=Tool group number)
8

(Data attribute)
M
(M=Tool number)

Value
12
1: Clears tool status.
Tool group number 2: Skips tool status.
(2 bytes)

14

1210
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]

0 : The tool information was written successfully.

3 : The tool group number exceeded the range 1 to 512 or maximum


number of registered groups.

4 : The specified tool number is incorrect.

5 : The specified tool number is not registered to the specified tool


group.

6 : The tool life management option has not been added on.

[Output data structure]

Top address 0
(Function code)
231

2
(Completion code)
?
(See the explanation above.)

4
(Data length)
2
(Entered data)

6
(Data number)
N
(Entered data)

(Data attribute)
M
(Entered data)

12
Tool length offset number
(2 bytes)

14

The following table shows how the tool status changes before and after
this function is specified.

command Precommand Status Postcommand Status

skip (#) unused ( )


clear skip (#) in use (@)
used (*) unused ( )

unused ( ) skip (#)


skip in use (@) skip (#)
used (*) skip (*)

1211
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

NOTE
1 This cannot be used with those models that do not have the
tool life management function.
2 Tool life management data is not applied to the T mode of
the compound machining function. And compound
machining function is not applied to the function of tool life
management data B.

1212
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.72 (1) Actual spindle speed


Reading Actual Spindle [Description]
Speeds This function reads the actual speed of the No.1 to No.4 serial spindles.

[Input data structure]

Top address +0
(Function code)
138

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)

+6
(Data number)
0

+8
(Data attribute) M=1 to n : Read spindles on each axis.
M (n is the spindle number.)
(M=Spindle number)
1 : Read spindles on No.1 and No.2 axes
+10 2 : Read spindles on No.1 to No.3 axes
(Data area) 3 : Read spindles on No.1 to No.4 axes

(Need not be set)

[Completion codes]
0: The actual spindle speed was read successfully.
4: The spindle speed in Data Attribute has wrong values, that is ,
a value outside of the range 1 to (n1) or 1 to n (n: number of
spindles).

1213
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address +0
(Function code)
138

+2
(Completion code)
?
(See the explanation above.)
+4
(Data length)
L
(L=4 n)
+6

(Data number)

+8
(Data attribute)
M
(Entered data) Value
+10
Actual speed of specified spindle Signed binary
<data unit>
rpm
+14

Or, 4 controlled axes:

Value
+10
Actual speed of No.1 spindle Signed binary
<Data unit>
rpm
+14
Actual speed of No.2 spindle

+18
Actual speed of No.3 spindle

+22
Actual speed of No.4 spindle

+26

1214
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

(2) Position coderless actual spindle speed


[Description]
This function reads the actual spindle speed (position coderless actual
spindle speed) obtained by calculating the spindle motor speed of the
No.1 to No.4 serial spindles.

[Input data structure]

Top address +0
(Function code)
138

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)

+6
(Data number)
0

+8
(Data attribute) M=11 to (10+n) : Read spindles on each axis.
M (n is the spindle number.)
(M=Spindle number)
11 : Read spindles on No.1 and No.2 axes
+10 12 : Read spindles on No.1 to No.3 axes
(Data area) 13 : Read spindles on No.1 to No.4 axes

(Need not be set)

+12

[Completion codes]
0 : The actual spindle speed was read successfully.
4 : The spindle speed in Data Attribute has wrong values, that is ,
a value outside of the range 11 to (9+1) or 11 to (10+n) (n:
number of spindles).

1215
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address +0
(Function code)
138

+2
(Completion code)
?
(See the explanation above.)
+4
(Data length)
L
(L=4 n)
+6

(Data number)

+8
(Data attribute)
M
(Entered data) Value
+10
Position coderless actual spindle Signed binary
speed <data unit>
min1
+14

Or, 4 controlled axes:

Value
+10
Position coderless actual No.1 Signed binary
spindle speed <Data unit>
min1
+14
Position coderless actual No.2
spindle speed
+18
Position coderless actual No.3
spindle speed
+22
Position coderless actual No.4
spindle speed
+26

1216
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.73 [Description]
Reading Fine Torque This function reads the statistical calculation results (average value,
Sensing Data maximum value, distribution) in the fine torque sensing function.
(Statistical Calculation
Results) [Input data structure]

Top address +0
(Function code)
226

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)

+6
(Data number)
N
(N=Axis number)

+8
(Data attribute) M=1 to n : Read spindles on each axis.
0 (n is the spindle number.)

+10 1 : Read all axes


(Data area)

(Need not be set)

[Completion codes]
0 : The statistical calculation results were read successfully.
3 : The fine torque sensing data in Data Attribute has a wrong value,
that is, a value outside of the range 1 or 1 to n (n: number of
spindles).
6 : The fine torque sensing option has not been added on.

1217
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address +0
(Function code)
226

+2
(Completion code)
?
(See the above explanation.)
+4
(Data length)
L
(L=6 n)
+6

(Data number)

+8
(Data attribute)
M
(Entered data) Value
+10
Signed binary
Average value of target axis

+12

Maximum value of target axis

+14

Distribution of target axis

+16

Or, 4 controlled axes:

Value
+10
Average value of target axis 1 Signed binary
(Output only for number of axes
+12
Maximum value of target axis 1 specified to parameter Nos. 6390
to 6363)
+14
Distribution of target axis 1
+16
Average value of target axis 2
+18
Maximum value of target axis 2
+20
Distribution of target axis 2

:
+32
Average value of target axis 4
+34

1218
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.74 (1) Store counter


Reading Fine Torque [Description]
Sensing Data This function reads the number of stored torque data items.
(Store Data)
[Input data structure]

Top address +0
(Function code)
232

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)

+6

(Data number)
0

+8
(Data attribute) M= 0 : Latest data counter
M = 1 : Sample data counter
(M=Tool number)

+10
(Data area)

(Need not be set)

[Completion codes]
0 : The store counter was read successfully.
3 : Incorrect data number, that is, a value other than 0 is specified.
4 : The fine torque sensing data in Data Attribute has wrong values,
that is, a value other than 01.
6 : The fine torque sensing option has not been added on.

1219
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address +0
(Function code)
232

+2
(Completion code)
?
(See the explanation above.)

+4
(Data length)
4

+6
(Data number)
0
(Entered data)

+8
(Data attribute)
M
(Entered data) Value
+10
Unsigned binary
Store counter value

+14

1220
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

(2) Stored torque data (latest data)


[Description]
This function reads the latest stored data among stored torque data.

[Input data structure]

Top address +0
(Function code)
232

+2
(Completion code)

(Need not be set)

+4
(Data length)

(Need not be set)

+6
(Data number) N : Number of axis to be read + 100
N
(N=11 to (10+N))
+8
(Data attribute) M =0 : Latest data
M =1 : Sample data
(M=Data type)

+10
(Data area)

(Need not be set)

[Completion codes]
0: The stored torque data (latest data) was read successfully.
3: Incorrect data number, that is, a value other than 11 to (10+n) (n:
number of spindles) is specified.
4: The fine torque sensing data in Data Attribute has a wrong value,
that is, a value other than 0 or 1.
6: The fine torque sensing option has not been added on.

1221
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address +0
(Function code)
232

+2
(Completion code)
?
(See the explanation above.)

+4
(Data length)
L
Entered data
+6
(Data number)
N
(Entered data)

+8
(Data attribute)
M
(Entered data) Value
+10
Signed binary
Latest stored data

+12

NOTE
1 When data has not been stored, data is not output, and processing ends successfully with L
set to 0.
2 When sample data is selected by data attribute, the sample data corresponding to the latest
stored data is output.
Example) When 10000 sample data items (data numbers 0 to 9999) and latest data items
5000 (data numbers 0 to 4999) are stored, data number 4999 in the latest data is
output when data attribute M is set to 0, and data number 4999 in the sample data
is output when data attribute M is set to 1.
3 When sample data is selected by data attribute, and there is no sample data corresponding to
the latest stored data, data is not output, and processing ends successfully with L set to 0.
Example) When 5000 sample data items (data numbers 0 to 4999) and 10000 latest data
items (data numbers 0 to 9999) are stored, data is not output, and processing ends
successfully with L set to 0 when data attribute M is set to 1.

1222
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

(3) Stored torque data (any data)


[Description]
This function reads the arbitrary data among stored torque data.

[Input data structure]

Top address +0
(Function code)
232

+2
(Completion code)

(Need not be set)

+4
(Data length)
6

+6
(Data number) N: Number of axis to be read
N
(N=1 to n)
+8
(Data attribute) M =0 : Latest data
M =1 : Sample data
(M=Data type)

+10

Data number n

+14

Number of data items I

+16

Data of number n

+18

Data of number n+1

+20
:
:

1223
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

NOTE
The valid range of data number n is calculated as follows:
0 v n v (524288 1 1
a b)1
where,
1: Number of target axes 1
a= 2: Number of target axes 2
4: Number of target axes 3 and 4
b= 1: Sample data store function OFF
2: Sample data store function ON
The valid range of number of data items I is calculated as
follows:
1vlv20

[Completion codes]
0 : The stored torque data (any data) was read successfully.
2 : Incorrect data length, that is, a value other than 6 is specified.
3 : Incorrect data number, that is, a value other than 11 to (10+n) (n:
number of spindles) is specified.
4 : The fine torque sensing data in Data Attribute has a wrong value,
that is, a value other than 0 or 1.
5 : Incorrect data area is specified. See Note for details of value
ranges.
6 : The fine torque sensing option has not been added on.

1224
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address +0
(Function code)
232

+2
(Completion code)
?
(See the above explanation.)
+4
(Data length)
L
(L=6 + number of data items I 2)
+6
(Data number)
N
(Entered data)
+8
(Data attribute)
M
(Entered data) Value
+10
Signed binary
Data number n
(Entered data)
+14

Number of data items I


(Entered data)
+16

Distribution of target axes

+18
Number n data
+20
Number n+1 data
+22
Number n+2 data
+24
:

Number n+I1 data

1225
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

NOTE
1 When the number of actually stored data items is exceeded
even though data number n is in the valid range, data is not
output and processing ends successfully by number of data
items I set to 0.
Example) When the number of target axes is 2, and the
sample data store function is enabled
(parameter No.6350#2=1), data numbers 0 to
13107 are valid. However, if an attempt is made
to read (example (1) in figure below) data from
data number n = 131020 when the number of
actually stored data items is 131000 (data
numbers 0 to 130999), data is not output, and
the number of data items I becomes 0.
2 When data number n is within the number of actually stored
data items, and (n+I 1) exceeds the number of actually
stored data items, data of the stored data items is output,
and processing ends successfully. In this case, number of
data items I is updated to the number of data items that was
output.
Example) If an attempt is made to read (example (2) in
figure below) number of data items I (120) from
data number 130900 under the same
conditions as in the example above, the data of
data numbers 130900 to 130999 is output, and
number of data items I becomes 100.
Also, if an attempt is made to read (example (3)
in figure below) number of data items I (120)
from data number 130999 under the same
conditions as in the example above, the data of
data numbers 130990 to 130999 is output, and
number of data items becomes 10.

Data Number Valid Range

Range of actually stored data

Data range about to be read (1)


Data range about to be read (2)
Data range about to be read (1)

1226
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.75 [Explanation of data]


Specifying the Number Specify the number of the program to be input/output using the data
of the Program for I/O input/output function with I/O Link.
Link [Input data structure]

Top address +0
(Function code)
194

+2
(Completion code)

(Need not be set.)

+4
(Data length)
2

+6
(Data number)
0

+8
(Data attribute)
0
Value
+10
Signed binary format
Program number

+12

[Completion codes]
0 : The specification of the program number terminated normally.
5 : Invalid data was specified for the program number, i.e., the data
falls outside the range of 1 to 9999 or is not 9999.

1227
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Output data structure]

Top address +0
(Function code)
194

+2
(Completion code)
?
(See the explanation of completion
codes, above.)
+4
(Data length)
2
(Data at input time)
+6
(Data number)
0
(Data at input time)
+8
(Data attribute)
0
(Data at input time) Value
+10
Signed binary format
Program number
(Data at input time)

+12

CAUTION
For details of this function, see the section on data
input/output functions using I/O Link in the CNC
Connection Manual (Functions).

1228
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.76 [Description]
Preset of relative The preset data is set to the relative coordinate controlled by CNC. If 0
coordinate is set as preset data it becomes to origin.
(:Lowspeed But it is impossible to write the value of preset data to the transferring
axis. In the case of the preset of relative coordinate of all axes is executed
response)
by using this function, if only one axis is transferring, the preset of relative
(not available for coordinate cannot be executed, neither.
Power Mate and Series
[Input data structure]
21TA)
Case of writing data on each axis.

Top address +0
(Function code)
249

+2
(Completion code)

(Need not be set.)

+4
(Data length)
4

+6
(Data number)
0
Value
+8
M=1 to n: Write data on each
(Data attribute) (n is the axis number)
M
(M: Input data)
+10
Signed binary
Value of relative coordinate for the (A negative value is represented in 2s
controlled axis specified (4bytes) complement)

+12

Input data unit


Increment Increment
Input system
system ISB system ISC
mm, deg
Machining center 0.001 0.0001
system
system
inch system 0.0001 0.00001
Radius
0.001 0.0001
specification mm, deg
Diameter system
0.001 0.0001
Lathe specification
system Radius
0.0001 0.00001
specification
inch system
Diameter
0.0001 0.00001
specification

1229
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

Case of writing data on all axes (controlled axes are 4).

Top address +0
(Function code)
249

+2
(Completion code)

(Need not be set.)

+4
(Data length)
16

+6
(Data number)
0
Value
+8
1 must be set
(Data attribute)
M
(M=1)
+10
Signed binary
Value of relative coordinate for the first (A negative value is represented in 2s
axis (4bytes) complement)

+12
Value of relative coordinate for the se-
cond axis (4bytes)

+14
Value of relative coordinate for the third
axis (4bytes)

+18
Value of relative coordinate for the
fourth axis (4bytes)

+22

[Completion codes]
0 : Success to set the value of relative coordinate.
4 : Data specified for the data attribute is invalid because it is neither
1 nor a value from 1 to n(n is the number of axes). Alternatively,
the specified axis number is greater than the number of controlled
axes.
5 : Relative coordinate is out of range.
13 : Axis is moving now.

1230
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Output data structure]

Top address +0
(Function code)
249

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
L
(Same as input data)
+6
(Data number)
0
(Same as input data)
+8
(Data attribute)
M
(M: Input data)

+10
Value of relative coordinate
(4*n bytes)

1231
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.77 (Not available for Power Mate, Series 21TA)


Deleting the Tool life [Description]
Management Data The function deletes the specified Tool group in the Tool life management
(Tool group) data. In short, it makes the condition that Tool group is not registered.
(:Lowspeed
response)
[Input data structure]

Top address +0
(Function code)
324

+2
(Completion code)

(Need not be set)

+4

(Data length)
0

+6
(Data number)
N
(N=Tool group number)
+8

(Data attribute)
0

+10

1232
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Success to delete the Tool group number.
3 : The Tool group number is out of range from 1 to 512,or exceeds
the maximum number of registered Tool group.
6 : No option for Tool life management.

[Output data structure]

Top address +0
(Function code)
324

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
0
(Same as input data)
+6
(Data number)
N
(Same as input data)
+8
(Data attribute)
0
(Same as input data)

+10

NOTE
1 Those models that do not provide the tool life management
function cannot be used.
2 The turning mode of the complex machining function does
not support tool life management data.

1233
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.78
Deleting the Tool life [Description]
Management Data The function deletes the Tool data of the Tool of the specified Tool
(Tool data) operation sequence number in the Tool life management data. (M series
(:Lowspeed only)
response)

[Input data structure]

Top address +0
(Function code)
325

+2
(Completion code)

(Need not be set)

+4

(Data length)
0

+6
(Data number)
N
(N=Tool group number)
+8
(Data attribute)
M
(M=Tool operation sequence number)
+10

1234
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Success to delete the Tool group number.
3 : The Tool group number is out of range from 1 to 512,or exceeds
the maximum number of registered Tool group.
4 : The Tool operation sequence number is wrong.
6 : No option for Tool life management.

[Output data structure]

Top address +0
(Function code)
325

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
0
(Same as input data)
+6
(Data number)
N
(Same as input data)
+8
(Data attribute)
M
(Same as input data)

+10

NOTE
1 Those models that do not provide the tool life management
function cannot be used.
2 The turning mode of the complex machining function does
not support tool life management data.

1235
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.79
Deleting the Tool life [Description]
Management Data The function clears the Tool life counter and all Tool condition of the
(Tool life counter and specified Tool group in the Tool life management data.
Tool condition)
(:Lowspeed
response) [Input data structure]

Top address +0
(Function code)
326

+2
(Completion code)

(Need not be set)

+4

(Data length)
0

+6
(Data number)
N
(N=Tool group number)
+8

(Data attribute)
0

+10

1236
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Success to clear the Tool life counter and the Tool condition.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
6 : No option for Tool life management.

[Output data structure]

Top address +0
(Function code)
326

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
0
(Same as input data)
+6
(Data number)
N
(Same as input data)
+8
(Data attribute)
0
(Same as input data)

+10

NOTE
1 Those models that do not provide the tool life management
function cannot be used.
2 The turning mode of the complex machining function does
not support tool life management data.

1237
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.80
Writing the Tool life [Description]
Management Data This function sets Arbitrary group number of the specified Tool group in
(Arbitrary group the Tool life management data.
number) (:Lowspeed
response)
[Input data structure]

Top address +0
(Function code)
327

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N=Tool group number)
+8
(Data attribute)
0

+10
Arbitrary group number
(4bytes)

NOTE
Writing the Tool life Management Data (Arbitrary group
number) is available for Tool life management data B

1238
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Success to set the Arbitrary group number.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
5 : Arbitrary group number is out of range.
6 : No option for Tool life management.

[Output data structure]

Top address +0
(Function code)
327

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)
+6
(Data number)
N
(Same as input data)
+8
(Data attribute)
0
(Same as input data)

+10
Arbitrary group number
(4bytes)

NOTE
1 Those models that do not provide the tool life management
function cannot be used.
2 The turning mode of the complex machining function does
not support tool life management data.
The complex machining function does not support the tool
life management B function.

1239
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.81 (Not available for Power Mate, Series 21TA)


Writing the Tool life [Description]
Management Data This function sets the length of Remaining Tool life of the specified Tool
(Remaining tool life) group in the Tool life management data.
(:Lowspeed
response)
[Input data structure]

Top address +0
(Function code)
328

+2
(Completion code)

(Need not be set)

+4

(Data length)
4

+6
(Data number)
N
(N=Tool group number)
+8

(Data attribute)
0

+10

Remaining tool life


(4bytes)

NOTE
Writing the Tool life Management Data (Remaining tool life)
is available for Tool life management data B

1240
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Success to set the length of Remaining tool life.
3 : The Tool group number is out of range from 1 to 512, or exceeds
the maximum number of registered Tool group.
5 : Remaining tool life is out of range.
6 : No option for Tool life management.

[Output data structure]

Top address +0
(Function code)
328

+2
(Completion code)
?
(See the explanation above)

+4
(Data length)
4
(Same as input data)
+6
(Data number)
N
(Same as input data)
+8
(Data attribute)
0
(Same as input data)

+10
Renaububg tiik kufe
(4bytes)

NOTE
1 Those models that do not provide the tool life management
function cannot be used.
2 The turning mode of the complex machining function does
not support tool life management data.
The complex machining function does not support the tool
life management B function.

1241
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

B.4.82
Reading the Current [Description]
Screen Number The current screen number to display can be read.
[Input data structure]

Top address + 0

(Function code)
120
+2
(Completion code)

(Need not to be set)
+4
(Data length)

(Need not to be set)
+6
(Data number)

(Need not to be set)
+8
(Data attribute)

(Need not to be set)
+10

(Data area)

+12
(Need not to be set)

1242
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

[Completion codes]
0 : Reading the current screen number has been read normally.
1 : This function can not be used because series and edition of CNC
or PMC system software is not corresponded.
[Output data structure]

Top address +0
(Function code)
120

+2
(Completion code)
?
(See the explanation of the
completion code)
+4
(Data length)
4

+6
(Data number)

(Same as input data)
+8
(Data attribute)

(Same as input data)

+10
(Data area)
Screen number (Small classification)
(Refer to Table 1)
+12
(Data area)
Screen number (Large classification)
(Refer to Table 1)

NOTE
This function is used for Power Mate iD/H only.

1243
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[The screen number of Power Mate iD/H ]


Table B.4.82

Large classification Small classification


00 POSITION 00 ABSOLUTE
01 RELATIVE
02 ALL
03 HANDLE INTERRUPT
04 OPERATING MONITOR
05 C Executor
01 PROGRAM 00 MDI PROGRAM
01 PROGRAM
02 LIBRARY
03 CURRENT BLOCK
04 NEXT BLOCK
05 PROGRAM CHECK
07 FLOPPY DIRECTORY
0d C Executor
02 OFFSET 00 OFFSET
01 SETTING PARAMETER
03 MACRO VARIABLE
04 MENU
05 OPERATORS PANEL
0a C Executor
03 SYSTEM 00 PARAMETER
01 DIAGNOSE
02 PMC
03 SYSTEM
04 MEMORY
06 SERVO SETTING
07 SPINDLE SETTING
0b OPERATION HISTORY
0c ALL I/O
13 PERIODICAL MAINTENANCE DISP.
14 MAINTENANCE INFORMATION DISP.
18 FSSB SETTING DISPLAY
19 C Executor
04 MESSAGE 00 ALARM
01 EXTERNAL MESSAGE
02 ALARM HISTORY
0a C Executor
05 USER 01 MACRO1
02 MACRO2
03 MACRO3

1244
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

B.4.83
Reading Detailed [Description]
Alarm Information If the CNC is in the alarm status, the details can be read. Detailed
(:Lowspeed type) information includes the following:
(a) Alarm status information
Information of the type of alarm which occurs
(b) Detailed alarm information
Axis information of the alarm which occurs and alarm number
information
(1) Reading alarm status information
[Input data structure]

Top address + 0

(Function code)
186
+2
(Completion code)

(Need not to be set)
+4
(Data length)

(Need not to be set)
+6

(Data number)
0
+8

(Data attribute)
0

+10
(Data area)

(Need not to be set)
+12

1245
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Reading the CNC alarm status has terminated normally.
[Output data structure]

Top address +0
(Function code)
186

+2
(Completion code)

(See the explanation of the
completion code)
+4
(Data length)
2

+6
(Data number)
0
(Same as input data)
+8
(Data attribute)
0
(Same as input data)

+10
Alarm status information
(See below.)

+12

Alarm status information

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 bit

Bit 0: P/S alarm 100 (PS1)


(The alarm write enable setting PWE is set to 1.)
Bit 1: P/S alarm 000 (PS2)
(Turn the power off once. A written parameter may cause
this alarm.)
Bit 2: P/S alarm 101 (PS3)
(The part program storage area is disordered. If the power
to the CNC is turned off during part program editing or
machining program reading, this alarm occurs. To release
this alarm, press the RESET key while holding the PROG
key down.)
Bit 3: A P/S alarm other than the above occurs. (PS) (Up to 255)
Bit 4: Stroke limit alarm (OTS)
Bit 5: Overheat alarm (OH)
Bit 6: Servo alarm (SV)
Bit 7: Not used
Bit 8: APC alarm (APAL)
Bit 9: Spindle alarm (SPA)
Bit 10: P/S alarm having a number 5000 or after (PS_2)
Bits 11 to 15: Not used

1246
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
B61863E/14 APPENDIX SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4)

(2) Reading detailed alarm information


[Input data structure]

Top address + 0

(Function code)
186
+2
(Completion code)

(Need not to be set)
+4
(Data length)

(Need not to be set)
+6
M: 130
(Data number) Number of stored alarms
M
+8 N: Detailed alarm information request bits
(For the meaning of each bit, see Alarm
(Data attribute)
status information.
N

+10
(Data area)

(Need not to be set)
+12

1247
B. WINDOW FUNCTION DESCRIPTION
(PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/SB6/SB7/SC/SC3/SC4) APPENDIX B61863E/14

[Completion codes]
0 : Reading the CNC alarm status has terminated normally.
[Output data structure]

Top address +0
(Function code)
186
+2
(Completion code)

(See the explanation of the
completion code)
+4
(Date length)
2+4n
(n : Number of alarms)

+6
(Data number)
M
(Same as input data)
+8
(Data attribute)
N
(Same as Input data)
Explanation of the value
+10
Number of alarms 2byte unsigned binary data

+12
Axis information 2byte bit data (see below.)
(first alarm)
+14
Alarm number 2byte unsigned binary data
(first alarm)
+16
Axis information
(second alarm)
+18
Alarm number
(second alarm)

X X
+8+4 n
Axis information
(nth alarm)
+10+4 n
Alarm number
(nth alarm)
+12+4 n

D Axis information
For an axistype alarm, the bit indicating the corresponding axis
number is on.
(When an alarm occurs on axis 1, bit 0 is 1.)
For a nonaxistype alarm, the bit is 0.

1248
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C WINDOW FUNCTION DESCRIPTION (PMCNB/NB2/NB6)

1249
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.1 This window function is a functional instruction by which the data on the
CNC is read or is written.
FUNCTION
Option (FS15B : A02B0162J917, FS15i : A02B0261J950) of NC
window is necessary.

1250
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.2 In the way to process, there are window function high speed and one
processed at low speed.
LOWSPEED
RESPONSE AND In case of a lowspeed response, The data is read or written by the control
between CNC and PMC.
HIGHSPEED
Therefore, it is necessary to ACT=1 of the window instrucion must be
RESPONSE OF held until the transfer completion information (W1) becomes 1
WINDOW FUNCTION (interlock).
In a highspeed response, it is not necessity for take the interlock because
the data is directly read.
To read tool offset data, tool life management data, and the processing
time, the FS15B requires the installation of the NC window B option
(A02B0162J984), in addition to the NC window option.

CAUTION
1 The window instruction of a lowspeed response is controlled exclusively with the other window
instructions of lowspeed response.
Therefore, when the data is read or written continuously, it is necessary to clear ACT of the
functional instruction once when the completion information (W1) become 1.
It does not work about ACT=1 of the other window instructions of lowspeed response such
as W1=1 and ACT=1 of the window instruction of a lowspeed response.
The window instruction of a highspeed response is not exclusively controlled like a lowspeed
response. Therefore, when the data is read or written continuously, yow need not make ACT=0.
The scan number of times to complete the processing is summarized on the following table.
TYPE SCAN TIMES UNTIL PROCESSING ENDS
LOW TWO SCAN TIMES OR MORE (This depends on the state of CNC)
HIGH 1SCAN TIME

(Only FS15B)
2 There is a version which does not support in the reading or writing of the window data by a new
format.
ROM VERSION CONTENT
4047 AE It does not support a new format.
Please use #4 of NC parameter 7401 as 0.
F It supports a new form.
When the window function of a new format is used, please set #4 of NC parameter 7401 as 1.
4078 A

Function that is effected by #4 of NC parameter 7401.


CONTENT
FUNCTION
7401#4
Tool life management 0 The data of tool life management for 128 sets of tools can be read and written.
data
1 The data of tool life management for 512 sets of tools can be read and written.
Tool offset data 0 This function can not be used.
according to the
specified tool number 1 The tool offset data can be read and written.

3 Functions except the abovementioned are not related to #4 of NC parameter 7401.


If there is no option of the corresponding function, window instructions can not be used.

1251
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.2.1
Functional Instruction
WINDR

0
CTL0 Function code
2
Completion code
4
Data length
6
CTL1 Data number
8
CTL2 Axis specification
10
DATA Data area * Data length Depends on the function
X X

part1
Type of Type of control data Data
Data type processing length
CTL0 CTL1 CTL2
Tool offset data (low) 13 Offset number Offset format 4 byte
Work origin offset (high) 15 0 Axis number 4 byte
Parameter data (low) 17 Parameter number Axis number 4 byte
Setting data
Custom macro variables (low) 21 Custom macro number 0 6 byte
CNC alarm state (low) 23 0 0 2 byte
Current program number (low) 24 0 0 6 byte
Current sequence number (low) 25 0 0 6 byte
Actual velocity for controlled axes (low) 26 0 0 4 byte
Absolute position on controlled axes (high) 27 0 Axis number 4 byte
Machine position on controlled axes (high) 28 0 Axis number 4 byte
Skip operation stop position on (low) 29 0 Axis number 4 byte
controlled axes
Servo delay amount on controlled (high) 30 0 Axis number 4 byte
axes
Acceleration/deceleration delay (high) 31 0 Axis number 4 byte
amount on controlled axes
Modal data (G function) (low) 32 Data type Specified block 2 byte
(other than G function) 6 byte
Diagnosis data (low) 33 Diagnosis number 0 2 byte
Feed motor load current value (high) 34 200 Axis number 2 byte
Generalpurpose analog input (high) 34 0 Axis number 2 byte

1252
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

part2
Type of Type of control data Data
Data type processing length
CTL0 CTL1 CTL2
Tool life management data
Tool group No. (low) 38 0 Tool No. 4 byte
Number of tool groups (low) 39 Tool group No. 0 4 byte
Number of tools (low) 40 Tool group No. 0 4 byte
Tool life (low) 41 Tool group No. 0 4 byte
Tool life counter (low) 42 Tool group No. 0 4 byte
Tool life counter type (low) 160 Tool group No. 0 4 byte
Tool length compensation No.1 (low) 43 Tool group No. Tool No. 4 byte
Tool length compensation No.2 (low) 44 Tool group No. Tool order number 4 byte
Cutter compensation No.1 (low) 45 Tool group No. Tool No. 4 byte
Cutter compensation No.2 (low) 46 Tool group No. Tool order number 4 byte
Tool information 1 (low) 47 Tool group No. Tool No. 4 byte
Tool information 2 (low) 48 Tool group No. Tool order number 4 byte
Tool No. (low) 49 Tool group No. Tool order number 4 byte
Clock data (low) 151 Data format 0 6 byte
Relative position of controlled axes (high) 74 0 Axis number 4 byte
Remaining travel of controlled axes (high) 75 0 Axis number 4 byte
Estimate disturbance torque data of a (high) 211 0 Axis number 2 byte
digital
Estimate disturbance torque data of a (high) 211 1 Axis number 2 byte
serial spindle
Machining time (low) 178 Program number 1 6 byte
Load information of the spindle motor (high) 153 0 Axis number 2 byte
Tool offset data according to the (low) 213 Data format Tool number 4 byte
specified tool number
Tool life management data (Note)
Tool group number (low) 200 0 Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Tool length compensation number 1 (low) 227 Tool group number Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Cutter compensation number 1 (low) 228 Tool group number Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Tool information 1 (low) 201 Tool group number Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Real parameter data (Note) (low) 321 Parameter number Axis number 4 bytes
(4 bytes)
Actual machine position on controlled (high) 329 0 Axis number 4 bytes
axes (Note)
Reading Fine Torque Sensing Data (low) 226 Data number Axis number 4 bytes
(Statistical Calculation Results).
(Note)
Reading Fine Torque Sensing Data (low) 232 Data attribute Axis number 4 bytes
(Store Data). (Note)
Reading detailed information of CNC (low) 330 Alarm type Alarm count 8 bytes
alarm. (Note)

NOTE
This function is supported only by the FS15iA
(PMCNB6).

1253
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.2.2
Functional Instruction
WINDW

0
CTL0 Function code
2
Completion code
4
Data length
6
CTL1 Data number
8
CTL2 Axis specification
10
DATA Data area * Data length Depends on the function
Y Y

part1
Type of Type of control data Data
Data type processing length
CTL0 CTL1 CTL2
Tool offset data (low) 14 Offset number Offset format 4 byte
Parameter data (low) 18 Parameter number Axis number 4 byte
Setting data
Custom macro variables (low) 22 Custom macro number 0 6 byte
Data on the program check screen
Spindle tool number (low) 150 Data type 0 2 byte
Number of the tool to be used
next (low) 150 201 0 2 byte
Torque limit override (low) 152 0 Axis number 2 byte
Tool life management data
Number of tool groups (low) 163 0 Tool No. 4 byte
Tool life (low) 164 Tool group No. 0 4 byte
Tool life counter (low) 165 Tool group No. 0 4 byte
Tool life counter type (low) 166 Tool group No. 0 4 byte
Tool length compensation No.1 (low) 167 Tool group No. Tool No. 4 byte
Tool length compensation No.2 (low) 168 Tool group No. Tool order number 4 byte
Cutter compensation No.1 (low) 169 Tool group No. Tool No. 4 byte
Cutter compensation No.2 (low) 170 Tool group No. Tool order number 4 byte
Tool information 1 (low) 171 Tool group No. Tool No. 4 byte
Tool information 2 (low) 172 Tool group No. Tool order number 4 byte
Tool No. (low) 173 Tool group No. Tool order number 4 byte
Tool offset data according to the
specified tool number (low) 214 Data format Tool number 4 byte
Superposition move command 215 0 0 6 byte
(for three axes) (high)
Superposition move command 215 Axis specification mode Axis number 8 byte
(for four axes) (high)
Feedrate (high) 216 0 0 6 byte

1254
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

part2
Type of Type of control data Data
Data type processing length
CTL0 CTL1 CTL2
Tool life management data (Note)
Tool group number (low) 202 0 Tool number (4 bytes) 6 bytes
(supporting 8digit tool numbers)
Tool length compensation number 1 (low) 229 Tool group number Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Cutter compensation number 1 (low) 230 Tool group number Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Tool information 1 (low) 231 Tool group number Tool number (4 bytes) 4 bytes
(supporting 8digit tool numbers)
Real parameter data (Note) (low) 323 Parameter number Axis number 4 bytes
(4 bytes)

NOTE
This function is supported only by the FS15iA
(PMCNB6).

1255
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3 (1) See the description of the window function. The data item marked
with a dash () in the description of the data structure need not be
FORMAT AND entered.
DETAILS OF THE (2) The length of all data blocks and data items is represented in bytes.
CONTROL DATA OF (3) The read data becomes valid only when the instruction terminates
THE WINDR normally.
FUNCTIONAL Completion
Meaning
code
INSTRUCTION
10 The window instruction is being processed. Hold ACT until W1
is set to 1.
0 The instruction terminated normally.
1 An error occurred. The corresponding function number is not
found.
2 An error occurred. Possible causes include the following:
Wrong data is found in the CTL area. The NC does not have the
corresponding function.
3 An error occurred. The specified axis is not provided.
5 An error occurred. It is a mistake of data form. Though the
function supports only a new format, a old format is specified.

C.3.1
Reading a Tool Offset [Description]
(Lowspeed Response) The tool offset value (tool compensation) is read from the CNC.
Set data Read data
0 0
Function code Function code
13 13
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Offset number Offset number

8 8
Offset format Offset format

10 10
Data area Tool offset value
(4 byte) (4 byte)

14 14

1256
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

(Note 1) Offset format


M series (machining center system) T series (lathe system)

Data type Format Offset number Data type Format Offset number
(CTL+2, 3) (CTL+2, 3)

Tool compensation A Tool compensation A


Compensation 1 Offset number Compensation along 1 Offset number
the Xaxis
Tool compensation B Compensation along 2 Offset number
Geometry 1 Offset number the Zaxis
compensation Tooltip radius com- 3 Offset number
Wear 1 Offset number pensation
compensation +1000 Compensation along 4 Offset number
the Yaxis
Tool compensation C Compensation re- 5 Offset number
Tool length lated to the position Offset number
Geometry 1 Offset number of the virtual tool
compensation
Wear 1 Offset number Tool compensation B
compensation +1000 Geometry
Cutter compensation
Geometry 2 Offset number Compensation 1 Offset number
compensation along the Xaxis
Wear 2 Offset number Compensation 2 Offset number
compensation +1000 along the Zaxis
Tooltip radius 3 Offset number
compensation
Compensation 4 Offset number
along the Yaxis
Wear
compensation
Compensation 1 Offset number
along the Xaxis +1000
Compensation 2 Offset number
along the Zaxis +1000
Tooltip radius 3 Offset number
compensation +1000
Compensation 4 Offset number
along the Yaxis +1000
Compensation 5 Offset number
related to the
position of the
virtual tool

1257
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.2 [Description]
Reading a Workpiece The offset from the workpiece reference point of the current coordinate
Origin Offset Value system (including a shared offset) of the CNC is read.
The offset from the workpiece reference point for each axis can be read
individually. The offset from the workpiece reference point for an
additional axis can be read only when the additional axis is provided.
Set data Read data
0 0
Function code Function code
15 15
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Axis number Axis number

10 10
Data area Workpiece origin
(4 byte) offset value
(4 byte)

14 14

1258
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.3
Reading a Parameter
(Setting Data) [Description]
(Lowspeed Response) A parameter of the CNC is read.

Set data Read data


0 0
Function code Function code
17 17
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Parameter number Parameter number

8 0 : No axis 8
Data attribute Data attribute

10 1 to n : A specified axis 10
Data area Parameter data
(4 byte) (4 byte)

14 14
(Note) Format of parameter data
If the data is one byte long, it is set in the
DATA+0 area.
10
DATA+0
11
DATA+1
12
DATA+2
13
DATA+3
14

NOTE
A real parameter cannot be read using function code 17.
Read a parameter using:
D Real parameter: Function code 321
D Integer or bit parameter: Function code 17

1259
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.4 [Description]
Reading a Custom A custom macro variable is read from the CNC.
Macro Variable
(Lowspeed Response) NOTE
The position of the decimal point must be specified
beforehand.

Set data Read data


0 0
Function code Function code
21 21
2 2
Completion code Completion code

4 4
Data length Data length
6
6 6
Custom macro Custom macro
variable number variable number
8 8
Data attribute Data attribute
0
10 10
Data area Custom macro
(4 byte) variable value
(4 byte)

14 Position of 14 Position of
decimal point decimal point
(2 byte) (2 byte)
16 16

NOTE
In the case of reading a Custom Macro Variable of upper
100000.
Please input 10 to Data attribute, and input last four digits
of variable number to Custom macro variable number.

Examples The relationship between the read value and the stored variable is:
(Read value) =
(Custom macro variable in the NC) 10(Position of decimal point)
Read value Custom macro Position of
variable in the NC decimal point
1 0
12 1. 234 1
123 2
1234 3
12340 4

1260
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.5
Reading the CNC
Alarm Status [Description]
(Lowspeed Response) If the CNC is in the alarm state, the details of the alarm are read.

Set data Read data


0 0
Function code Function code
23 23
2 2
Completion code Completion code

4 4
Data length Data length
2
6 6
Data number Data number
0
8 8
Data attribute Data attribute
0
10 10
Data area ALARM 1
(2 byte) 11
ALARM 2
12 12

The following alarm states can be read:

ALARM 1 Data format ALARM 2 Data format


7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

#0 : Background P/S alarm #0 : External alarm message


#1 : Foreground P/S alarm #1 : Not defined
#2 : Overheat #2 : P/S alarm preventing the processing
#3 : SubCPU error from continuing (serious alarm)
#4 : Excessive synchronization error #3 : Not defined
#5 : Parameter enable switch enabled #4 : Servo alarm
#6 : Overtravel #5 : I/O error
#7 : PC error #6 : Parameter input requiring the power to be turned off
#7 : System error

1261
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.6
Reading the Current
Program Number [Description]
(Lowspeed Response) The number of a running machining program is read from the CNC.

Set data Read data


0 0
Function code Function code
24 24
2 2
Completion code Completion code

4 4
Data length Data length
6
6 6
Data number Data number
0
8 8
Data attribute Data attribute
0
10 10
Data area Program number
(6 byte)

14
FLAG 1
15
FLAG 2
16 16

FLAG 1 Data format FLAG 2 Data format


7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

#0 to 3 : Number of decimal places #3 : Whether at least one address in the range


#4 : Whether a decimal point is provided of D to the second miscellaneous
(0: Not provided, 1: Provided) function is specified after the NC is reset
#5 : Positive or negative (0: Not specified, 1: Specified)
(0: Positive, 1: Negative) #7 : Whether the read data is specified in the
#6 : Whether only one digit is provided current block of the part program
(0: Not only one, 1: Only one) (0: Not specified, 1: Specified)
#7 : Not defined Other bits are not defined.

1262
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.7 [Description]
Reading the Current The sequence number of the running machining program is read from the
Sequence Number CNC. If the blocks of the running machining program have no sequence
(Lowspeed Response) numbers, the sequence number of the block most recently executed is
read.

Set data Read data


0 0
Function code Function code
25 25
2 2
Completion code Completion code

4 4
Data length Data length
6
6 6
Data number Data number
0
8 8
Data attribute Data attribute
0
10 10
Data area Sequence number
(6 byte) (4 byte)

14
FLAG 1
15
FLAG 2
16 16

FLAG 1 Data format FLAG 2 Data format


7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

#0 to 3 : Number of decimal places #3 : Whether at least one address in the


#4 : Whether the decimal point is provided range of D to the second miscellaneous
(0: Not provided, 1: Provided) function is specified after the NC is reset
#5 : Positive or negative (0: Not specified, 1: Specified)
(0: Positive, 1: Negative) #7 : Whether the read data is specified in the
#6 : Whether only one digit is provided current block of the part program
(0: Not only one, 1: Only one) (0: Not specified, 1: Specified)Other bits
#7 : Not defined are not defined.

1263
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.8 [Description]
Reading the Actual The actual speed of the feed axes controlled by the CNC is read.
Velocity of Controlled The composite speed of the controlled axes is read. If the X, Y, and
Axes Zaxes, the basic three axes, are controlled as feed axes, the composite
(Lowspeed Response) speed of the three axes is read.
Set data Read data
0 0
Function code Function code
26 26
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Data attribute Data attribute
0
10 10
Data area Feedrate
(4 byte) (4 byte)

14 14

C.3.9
Reading the Absolute [Description]
Position on a The absolute position (absolute coordinates) on a feed axis controlled by
Controlled Axis the CNC is read.
Set data Read data
0 0
Function code Function code
27 27
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Axis number Axis number
0
10 10
Data area Absolute position
(4 byte) (4 byte)

14 14

1264
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

Data specification
Kind of data Data specification
Current position 1) Indicates the current position in the workpiece coordinate system.
The current position is calculated by the following simple expression.
The read current position is stored in the 4byte area of DATA+0 to DATA+3.
Current position = machine coordinate value workpiece offset value
The workpiece offset value can be obtained by summing up the folloing offset.
(1) External workpiece origin offset
(2) Workpiece origin offset (G54 to G59,G54.1Pp)
(3) Workpiece coordinate system (G92)
(4) Local coordinate system (G52)

Local coordinate system (G52)

Workpiece origin offset (G54 or after)

External workpiece origin offset

Workpiece coordinate system (G92)

x
Origin of the machine coordinate system

2) Read value is determined as follows:


(1) For the machining center system or when the radius is specified for the axis of the lathe systm.
The data shows double of the present position with the least input increment as a unit.
(2) When the diameter is specified for the lathe system
The data shows the present position with the least input increment.
(3) When the input unit is multiplied by 10
The data shows twentytimes the present position (radius programming) or tentimes the
present position (diameter programming) with the last command increment as a unit.
3) The present position of a moving axis can be read whenever the function instruction is executed.

1265
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.10
Reading the Machine
Position (Machine [Description]
Coordinates) of The machine position (machine coordinates) on a feed axis controlled by
Controlled Axes the CNC is read.
Set data Read data
0 0
Function code Function code
28 28
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Data attribute Data attribute

10 10
Data area Feedrate
(4 byte) (4 byte)

14 14

1) Read value is determined as follows:


(1) For the machining center system or when the radius is specified
for the axis of the lathe systm.
The data shows double of the present position with the least
input increment as a unit.
(2) When the diameter is specified for the lathe system
The data shows the present position with the least input
increment.
(3) When the input unit is multiplied by 10
The data shows twentytimes the present position (radius
programming) or tentimes the present position (diameter
programming) with the last command increment as a unit.
2) The present position of a moving axis can be read whenever the
function instruction is executed.

1266
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.11
Reading a Skip
Position (Stop Position
of Skip Operation
(G31)) of Controlled
[Description]
Axes
(Lowspeed Response) The absolute coordinates of the skip position specified in the CNC are
read.
Set data Read data
0 0
Function code Function code
29 29
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Axis number Axis number

10 10
Data area Skip position
(4 byte) (4 byte)

14 14

1) Read value is determined as follows:


(1) For the machining center system or when the radius is specified
for the axis of the lathe systm.
The data shows double of the present position with the least
input increment as a unit.
(2) When the diameter is specified for the lathe system
The data shows the present position with the least input
increment.
(3) When the input unit is multiplied by 10
The data shows twentytimes the present position (radius
programming) or tentimes the present position (diameter
programming) with the last command increment as a unit.
2) Once the skip signal has been input to the NC, movement along the
relevant axis is stopped then, after the elapse of the servo delay, the
absolute position can be read.

1267
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.12
Reading the Servo [Description]
Delay for Controlled A servo delay, which is the difference between the specified position on
Axes a controlled axis and the actual servo position, is read from the CNC.
Set data Read data
0 0
Function code Function code
30 30
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Data attribute Data attribute

10 10
Data area Servo delay
(4 byte) (4 byte)

14 14

C.3.13
Reading the [Description]
Acceleration/ An acceleration/deceleration delay, which is the difference between the
Deceleration Delay on programmed position on a controlled axis and the actual position after the
Controlled Axes acceleration or deceleration, is read from the CNC.
Set data Read data
0 0
Function code Function code
31 31
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Axis number Axis number

10 10
Data area Acceleration/
(4 byte) deceleration delay
(4 byte)

14 14

1268
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.14 [Description]
Reading Modal Data The continuousstate data is read from the CNC.
(Lowspeed Response) The continuousstate data can be broadly classified into two types: Data
of the preparatory function and data of other functions. When CTL2
(specified block) is set to 0, the continuousstate data of the previous
block is read. When CTL2 is set to 2, the continuousstate data of the next
block is read.
(1) Continuousstate data of the preparatory function
Set data Read data
0 0
Function code Function code
32 32
2 2
Completion code Completion code

4 4
Data length Data length
2
6 6
Data type 0 : Each data for G function Data type

8 0 : Previous block 8
Specified block Specified block
1 : Current block
10 10
Data area
2 : Next block Modal data
(2 byte)
12 12

(Note) Format of the continuousstate data


7 6 5 4 3 2 1 0
DATA+0

#0 to #6 : Continuousstate data
#7 : Specified block
1= Current block
0= Previous block

1269
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

(2) Continuousstate data of a function other than the preparatory


function
The following eleven data items of an NC part program can be read:
addresses D, E, H, L, M, N, O, S, T, and F, and second miscellaneous
function.

Set data Read data


0 0
Function code Function code
32 32
2 2
Completion code Completion code

4 4
Data length Data length
6
6 6
Data type 24 : All data for G function Data type

8 0 : Previous block 8
Specified block Specified block
1 : Current block
10 10
Data area 2 : Next block Modal data
(6 byte) (4 byte)

14
FLAG 1
15
FLAG 2
16 16

FLAG 1 Data format FLAG 2 Data format


7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

#0 3 : Number of decimal places #3 : Whether at least one address in the


#4 : Whether the decimal point is provided range of D to the second miscellaneous
(0: Not provided, 1: Provided) function is specified after the NC is reset
#5 : Positive or negative (0: Not specified, 1: Specified)
(0: Positive, 1: Negative) #7 : Whether the read data is specified in the
#6 : Whether only one digit is provided current block of the part program
(0: Not only one, 1: Only one) (0: Not specified, 1: Specified)
#7 : Not defined Other bits are not defined.

1270
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

(3) Data specification


Kind of data Data specification
Modal data 1) Modal data of G function
The relationship between the numbers specified in the CTL1 (kinds of data), modal data codes is shown below. Into
CTL2 (the specified block), specify 0 (previous data), 1 (present date), or 2 (next data) in accordance with the
necessary modal data.
The G code for the lathe system is expressed with the G code system B. Refer to the table indicating the G function
system. For example, the G32 of the G code system A corresponds to the G33 of the G code system B. As a result,
the code fetched in the DATA + 0 is 4.

G code for lathe


Specified number in G code for machining Code fetched in
system
CTL1 (kinds of data) center system DATA + 0
(G code system B)
00 G00 G00 0
G01 G01 1
G02 G02 2
G03 G03 3
G33 G33 4
G77 8
G78 9
G79 10
01 G17 G97 0
G18 G96 1
G19 2
02 G90 G90 1
G91 G91 0
03 G22 G22 0
G23 G23 1
04 G93 2
G94 G94 0
G95 G95 1
05 G20 G20 1
G21 G21 0
06 G40 G40 0
G41 G41 1
G42 G42 2
07 G43 1
G44 2
G49 0
08 G80 G80 0
G81 G81 1
G82 G82 2
G83 G83 3
G84 G84 4
G85 G85 5
G86 G86 6
G87 G87 7
G88 G88 8
G89 G89 9
G73 G83.1 10
G74 G84.1 11
G76 G86.1 12
09 G98 G98 0
G99 G99 1
10 G50 0
G51 1

1271
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

Kind of data Data specification


Modal data
G code for lathe
Specified number in G code for machining Code fetched in
system
CTL1 (kinds of data) center system DATA + 0
(G code system B)
11 G66 G66 1
G67 G66 0
G66.1 G66.1 2
12 G96 G68 1
G97 G69 0
13 G54 G54 0
G55 G55 1
G56 G56 2
G57 G57 3
G58 G58 4
G59 G59 5
14 G61 G61 1
G62 2
G63 3
G64 G64 0
15 G69 G17 0
G68 G18 1
G19 2
16 G15 0
G16 1
17 G50.1 G50.1 0
G51.1 G51.1 1

1272
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

Kind of data Data specification


Modal data
Table 1 of G code system for a lathe system
G code system *1)
Function
A B C
G00 G00 G00 Positioning
G01 G01 G01 Linear interpolation
G02 G02 G02 Circular interpolation CW
G03 G03 G03 Circular interpolation CCW
G04 G04 G04 Dwell
G07 G07 G07 Hypotherical axis interpolation
G09 G09 G09 Exact stop
G10 G10 G10 Data setting
G10.1 G10.1 G10.1 PC data setting
G11 G11 G11 Data setting mode cancel
G17 G17 G17 XpYp plane selection Xp: X axis or its parallel axis
G18 G18 G18 ZpXp plane selection Yp: Y axix or its parallel axis
G19 G19 G19 YpZp plane selection Zp: Z axis or its parallel axis
G20 G20 G70 Inch input
G21 G21 G71 Metric input
G22 G22 G22 Stored stroke check on
G23 G23 G23 Stored stroke check off
G27 G27 G27 Reference point return check
G28 G28 G28 Reference point return
G29 G29 G29 Return from reference point
G30 G30 G30 Return to 2nd, 3rd, 4th reference point
G31 G31 G31 Skip function
G32 G32 G32 Thread cutting
G34 G34 G34 Variable lead thread cutting
G35 G35 G35 Circular thread cutting CW
G36 G36 G36 Circular thread cutting CCW or automatic tool
compensation (X axis)
G37 G37 G37 Automatic tool compensation #1 or automatic tool
compensation (Z axis)
G37.1 G37.1 G37.1 Automatic tool compensation #1
G37.2 G37.2 G37.2 Automatic tool compensation #2
G37.3 G37.3 G37.3 Automatic tool compensation #3
G40 G40 G40 Tool nose radius compensation cancel
G41 G41 G41 Tool nose radius compensation left
G42 G42 G42 Tool nose radius compensation right
G50 G92 G92 Work coordinates change/maximum spindle spped
setting
G50.1 G50.1 G50.1 Programmable mirror image cancel
G51.1 G51.1 G51.1 Programmable mirror image
G52 G52 G52 Local coordinate system setting
G53 G53 G53 Machine coordinate system selection
G54 G54 G54 Work coordinate system 1 selection
G55 G55 G55 Work coordinate system 2 selection
G56 G56 G56 Work coordinate system 3 selection
G57 G57 G57 Work coordinate system 4 selection
G58 G58 G58 Work coordinate system 5 selection
G59 G59 G59 Work coordinate system 6 selection
G61 G61 G61 Exact stop mode
G62 G62 G62 Automatic corner override
G64 G64 G64 Cutting mode
G65 G65 G65 Macro call
G66 G66 G66 Macro modal call A
G66.1 G66.1 G66.1 Macro modal call B
G67 G67 G67 Macro modal call A/B cancel
G68 G68 G68 Mirror image for double currets on
G69 G69 G69 Mirror image for double currets cancel
G70 G70 G72 Finishing cycle
G71 G71 G73 Stock removal in turning

1273
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

Kind of data Data specification


Modal data Table 2 of G code system for a lathe system
G code system *1)
Function
A B C
G72 G72 G74 Stock removal in facing
G73 G73 G75 Pattern repeating
G74 G74 G76 Peck drilling Z axis
G75 G75 G77 Grooving in X axis
G76 G76 G78 Threading cycle
G80 G80 G80 Canned cycle for drilling cancel
G81 G81 G81 Drilling cycle, spot boring
G82 G82 G82 Drilling cycle, counter boring
G83 G83 G83 Peck drilling cycle
G83.1 G83.1 G83.1 Peck drilling cycle
G84 G84 G84 Tapping cycle
G84.1 G84.1 G84.1 Counter tapping cycle
G85 G85 G85 Boring cycle
G86 G86 G86 Boring cycle
G86.1 G86.1 G86.1 Fine boring cycle
G87 G87 G87 Back boring cycle
G88 G88 G88 Boring cycle
G89 G89 G89 Boring cycle
G90 G77 G20 Outting cycle A
G92 G78 G21 Thread cutting cycle
G94 G79 G24 Outting cycle B
G96 G96 G96 Constant surface speed control
G97 G97 G97 Constant surface speed control
G98 G94 G94 Feed per minute
G99 G95 G95 Feed per revolution
G90 G90 Absolute command
G91 G91 Incremental command
G98 G98 Canned cycle initial level return
G99 G99 Canned cycle R point level return

*1) G code system A/B can be selected by parameter setting (basic function).
Gcode sytem C is optinal function. However, when this option is selected, G code system A/B
is selectable.

2) Modal data other than the G function

Modal data other than CTL1 (kinds of data)


Field from which to
the G function For machining For turning fetch data
(address in the part program) system system
D 24
E 25 24
H 26 25
L 27 26
M 28 27
N 29 28 DATA+0 to DATA+5
O 30 29
S 31 30
T 32 31
F 33 32
Second auxiliary function 34 33

1274
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.15
Reading Diagnosis
Data [Description]
(Lowspeed Response) The data on the diagnostic data screen of the CNC is read.
Set data Read data
0 0
Function code Function code
33 33
2 2
Completion code Completion code

4 4
Data length Data length
2
6 6
Diagnosis number Diagnosis number

8 8
Data attribute Data attribute
0 0
10 10
Data area Diagnosis data
(2 byte) (2 byte)

12 12

NOTE
1 The valid range of diagnosis numbers is 0 to 103 and 200
to 303. (FS15B)
For the FS15i, the valid range of numbers is 1000 and
above. (FS15iA)
2 Only integer values can be read as diagnosis data.
(FS15iA)
3 For the FS15i, axis data can be read by specifying an axis
number for the data attribute.

1275
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.16 [Description]
Reading A/D 1. The load current for an axis controlled by the CNC is converted to
Conversion Data for adigital value and the digital value is read.
the Feed Motor 2. The analog data input to the CNC is converted to a digital value by
the A/D converter and the digital value is read.

Set data Read data


0 0
Function code Function code
34 34
2 2
Completion code Completion code

4 4
Data length Data length
2
6 6
Data number Data number

8 8
Axis number Axis number

10 10
Data area A/D conversion data
(2 byte) (2 byte)

12 12

An analog voltage ranging from 10V to +10V is input to the A/D


converter of the NC. The voltage is converted to a digital value ranging
form 0 to +255 and transferred by the window function to the PMC. This
value is called the A/D conversion data.
The digital value is proportional to the analog voltage: 0 corresponds to
10V, 128 corresponds to 0V, and 255 corresponds to +10V.
Type of analog voltage input Data number Axis number
Generalpurpose analog input 0 1
2
3
4
5
6
Analog input of a voltage caluculated 200 1
from the load current for the axis con- 2
trolled by the NC 3
(AC servo motor only) 4
5
6
7
8
9
10
11
12
13
14
15

Method of calculation of the load current of controlled axis from the read
A/D conversion data is as follows.

1276
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

a) In the case of peak current [Aop] of load current is calculated.


(READ DATA) * 128
LOAD CURRENT[Aop] + [Aop]
(COEFFICIENT)
b) In the case of ratings currents [Arms] of load current are calculated.
(READ DATA) * 128
LOAD CURRENT[Arms] + [Arms]
(COEFFICIENT) 2
c) In the case of percent (rate) is calculated.
LOAD CURRENT[Aop]
rate of load[%] + 100[%]
PEAK CURRENT OF SERVO MOTOR
COEFFICIENT:
It decides depending on the capacity of the amplifier to be used.
PEAK CURRENT OF SERVO MOTOR :
It dicides with the servo motor.

Examples When the AC motor model 30s is used and the read A/D conversion
data is 150, method of calculating each load current.
The following is understood from manual of the servo.
AC motor model Ratings currents(Arms)
30S 16

Moreover, the amplifier of 80A is used for the motor of 30S.


The coefficient is calculated.
The coefficient is a value by which the peak current of amplifier is
converted by 128.
COEFFICIENT + 128 + 128 + 1.6
PEAK CURRENT VALUE OF AMPLIFIER 80
The peak current of the servo motor is calculated.
PEAK CURRENT[Aop]+ (ratings currents) 2

+ 16 2 + 22.62742

8 23 [Aop]
Since the rade A/D conversion data is 150, the peak current, the ratings
currents and the rate of the load can be calculated.
a) Peak current[Aop] of load current
(READ DATA) * 128
LOAD CURRENT[Aop] + + 150 * 128
(COEFFICIENT) 1.6
+ 13.75 [Aop]
b) Ratings currents[Arms] of load current
(READ DATA) * 128
RATINGS CURRENTS[Arms] + + 150 * 128
(COEFFICIENT) 2 1.6 2
+ 9.72 [Arms]
c) PERCENT(RATE)
LOAD CURRENT[Aop]
RATE OF LOAD[%]+ 100
PEAK CURRENT OF SERVO MOTOR

+ 13.75 100 + 59.8 [%]


23

1277
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

[Hardware]
When general analog input data is read, one of the following hardware
items is required:
1 SubCPU board
2 Analog I/O module on the additional axis board
For details of the relationship between input numbers and connectors,
refer to the connection manual. When an NC controlled axis load current
is read, the hardware described above is not required.
[NC parameters]
When this function is used, the NC parameters listed below need to be set.
For details, refer to the parameter descriptions.
1 Bit 6 of parameter No. 1810 = 0 (A/D conversion is performed.)
2 Bit 0 of parameter No. 1811 = 1 (A/D conversion data is output in
highspeed mode.)

C.3.17
Reading the Tool Life
Management Data [Description]
(Tool Group Number) The number of the tool group in which the tool number is cataloged is
(Lowspeed Response) read.
Set data Read data
0 0
Function code Function code
38 38
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Tool No. Tool No.

10 10
Data area Tool group No.
(4 byte) (4 byte)

14 14

NOTE
The data can be read only when the tool life management
data function is provided.

1278
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.18
Reading the Tool Life
Management Data
(Number of Tool [Description]
Groups) The number of tool groups contained in the tool life management data is
(Lowspeed Response) read.

Set data Read data


0 0
Function code Function code
39 39
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Data attribute Data attribute
0
10 10
Data area Number of tool
(4 byte) groups
(4 byte)

14 14

C.3.19
Reading Tool Life
Management Data
(Number of Tools) [Description]
(Lowspeed Response) The number of tools cataloged in the specified tool group is read.

Set data Read data


0 0
Function code Function code
40 40
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Data attribute Data attribute
0
10 10
Data area Number of tools
(4 byte) (4 byte)

14 14

1279
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.20
Reading Tool Life
Management Data
(Tool Life) [Description]
(Lowspeed response) The tool life of the specified tool group is read.

Set data Read data


0 0
Function code Function code
41 41
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Data attribute Data attribute
0
10 10
Data area Tool life
(4 byte) (4 byte)

14 14

C.3.21
Reading Tool Life
Management Data
(Tool Life Counter) [Description]
(Lowspeed Response) The tool life counter of the specified tool group is read.

Set data Read data


0 0
Function code Function code
42 42
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Data attribute Data attribute
0
10 10
Data area Tool life counter
(4 byte) (4 byte)

14 14

1280
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.22
Reading Tool Life
Management Data (Tool
Life Counter Type) [Description]
(Lowspeed Response) The tool life counter type of the specified tool group is read.

Set data Read data


0 0
Function code Function code
160 160
2 2
Completion code Completion code

4 4
Data length Data length

6 6
Tool group No. Tool group No.

8 8
Data attribute Data attribute
0
10 10
Data area Tool life counter type
(4 byte) (4 byte)

14 14

Tool life counter type


1 : The tool life counter indicates the number of times the tool has been used.
2 : The tool life counter indicates the period of time the tool has been used.

1281
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.23
Reading Tool Life
Management Data
(Tool Length [Description]
Compensation No.1) A tool length compensation number is read according to the specified tool
(Lowspeed Response) group number and tool number.

Set data Read data


0 0
Function code Function code
43 43
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool No. Tool No.

10 10
Data area Tool length compensa-
(4 byte) tion No.
(4 byte)

14 14

If nothing is specified after the H code, the NC transfers 255 (FFH).

1282
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.24
Reading Tool Life
Management Data
(Tool Length [Description]
Compensation No.2) A tool length compensation number is read according to the specified tool
(Lowspeed response) group number and tool order number.

Set data Read data


0 0
Function code Function code
44 44
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool order number Tool order number

10 10
Data area Tool length
(4 byte) compensation No.
(4 byte)

14 14

If nothing is specified after the H code, the NC transfers 255 (FFH).

1283
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.25
Reading Tool Life
Management Data
(Cutter Compensation [Description]
No.1) A cutter compensation number is read according to the specified tool
(Lowspeed Response) group number and tool number.

Set data Read data


0 0
Function code Function code
45 45
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool No. Tool No.

10 10
Data area Cutter
(4 byte) compensation No.
(4 byte)

14 14

If nothing is specified after the D code, the NC transfers 255 (FFH).

1284
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.26
Reading Tool Life
Management Data
(Cutter Compensation [Description]
No.2) A cutter compensation number is read according to the specified tool
(Lowspeed Response) group number and tool order number.

Set data Read data


0 0
Function code Function code
46 46
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool order number Tool order number

10 10
Data area Cutter
(4 byte) compensation No.
(4 byte)

14 14

If nothing is specified after the D code, the NC transfers 255 (FFH).

1285
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.27
Reading Tool Life
Management Data [Description]
(Tool Information 1) The tool information (status) is read according to the specified tool group
(Lowspeed Response) number and tool number.

Set data Read data


0 0
Function code Function code
47 47
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool No. Tool No.

10 10
Data area Tool information
(4 byte) (4 byte)

14 14

Tool information
1 : The tool is cataloged.
2 : The tool life has expired.
3 : The tool was skipped.

1286
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.28
Reading Tool Life
Management Data [Description]
(Tool Information 2) The tool information (status) is read according to the specified tool group
(Lowspeed Response) number and tool order number.

Set data Read data


0 0
Function code Function code
48 48
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool order number Tool order number

10 10
Data area Tool information
(4 byte) (4 byte)

14 14

Tool information
See the description in Section C.3.27.

C.3.29
Reading Tool Life
Management Data [Description]
(Tool Number) A tool number is read according to the specified tool group number and
(Lowspeed Response) tool order number.

Set data Read data


0 0
Function code Function code
49 49
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Tool group No. Tool group No.

8 8
Tool order number Tool order number

10 10
Data area Tool No.
(4 byte) (4 byte)

14 14

1287
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.30 [Description]
Reading Clock Data The current data (year, month, day) and current time (hours, minutes,
(Lowspeed Response) seconds) can be read from the clock built into the CNC.

Set data Read data


0 0
Function code Function code
151 151
2 2
Completion code Completion code

4 4
Data length Data length
6
6 0 : Current data 6
Data format Data format

8 1 : Current time 8
Data attribute Data attribute
0
10 10
Data area Clock data
(6 byte) (6 byte)

16 16

(Note) Format of clock data


The data is binary.
Current date
DATA+ 0
Years (Example: 1992)
+2
Months (Example: 12)
+4
Days (Example: 16)
+6
Current time
DATA+ 0
Hours (Example: 23)
+2
Minutes (Example: 59)
+4
Seconds (Example: 59)
+6

1288
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.31
Reading the Relative [Description]
Position on a The relative position (relative coordinates) on a feed axis controlled by
Controlled Axis the CNC is read.

Set data Read data


0 0
Function code Function code
74 74
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Axis number Axis number

10 10
Data area Relative position
(4 byte) (4 byte)

14 14

1) The unit of the read value is determined as follows:


(1) For the machining center system or when the radius is specified
for the axis of the lathe systm.
The data shows double of the present position with the least
input increment as a unit.
(2) When the diameter is specified for the lathe system
The data shows the present position with the least input
increment.
(3) When the input unit is multiplied by 10
The data shows twentytimes the present position (radius
programming) or tentimes the present position (diameter
programming) with the last command increment as a unit.
2) The present position of a moving axis can be read whenever the
function instruction is executed.

1289
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.32 [Description]
Reading the Remaining The remaining traveling distance on a feed axis controlled by the CNC is
Travel read.

Set data Read data


0 0
Function code Function code
75 75
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0
8 8
Axis number Axis number

10 10
Data area Remaining travel
(4 byte) (4 byte)

14 14

1290
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.33 [Description]
Reading an Estimate 1) The load torques except a necessary torque for acceleration/
Disturbance Torque deceleration of the torques of the servo axis are read.
Data 2) The load torques except a necessary torque for acceleration/
deceleration of the torques of the serial spindle axis are read.

Set data Read data


0 0
Function code Function code
211 211
2 2
Completion code Completion code

4 4
Data length Data length
2
6 6
Data number 0: Estimate disturbance
Data number
0 or 1 torque data of a digital
servo
8 8
Axis number 1: Estimate disturbance Axis number
(1 to n) torque data of a serial (1 to n)
spindle
10 10 Estimate disturbance
Data area
torque
(2 byte)
(2 byte)
12 12

Kind of data Data specification


Estimate disturbance torque data Please refer to FANUC AC SERVO AMPLIFIER AMINTENANCE MANUAL
of a digital servo (B65005E) for correspondence of the load torque with the value of the read data.
Estimate disteurbance torque data Please refer to FANUC AC SPINDLE SERVO UNIT (SERIAL INTERFACE) MAINTE-
of a serial spindle NANCE MANUAL (B65045E) for correspondence of the load torque with the value of
the read data.
The load torque of the spindle is understood from the undermentioned calculation type.

Load torque + The read data Maximum output torque of spindle


16384

* For an explanation of the CNC parameters, refer to the CNC


Parameter Description.

1291
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.34
Reading the Machining
Time [Description]
(Lowspeed Response) The machining time currently specified for a program is read.

Set data Read data


0 0
Function code Function code
178 178
2 2
Completion code Completion code

4 4
Data length Data length
6
6 6
Program number Program number

8 8
Data attribute Data attribute
1 1
10 10
Data area Machining time
(6 byte) (6 byte)

16 16

1292
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.35
Reading the Load [Description]
Current (A/D The load current for the spindle (spindle motor) is converted to a digital
Conversion Data) for value and the digital value is read. (See Section 3.16, Reading the Load
the Spindle Motor Current (A/D Conversion Data) for the Feed Motor.)

Set data Read data


0 0
Function code Function code
153 153
2 2
Completion code Completion code

4 4
Data length Data length
2
6 6
Data number Data number
0
8 The 15B supports 8
Axis number two spindles, while Axis number
(1 to n) the 15iA supports (1 to n)
10 four spindles. 10
Data area A/D conversion data
(2 byte) (2 byte)
12 12

[Hardware]
When general analog input data is read, one of the following hardware
items is required:
1 SubCPU board
2 Analog I/O module on the additional axis board
With a serial spindle, however, the hardware described above is not
required if CNC software of mass production version IV or later is used.
For the relationship between input numbers and connectors, refer to the
connection manual.
[NC parameters]
When this function is used, the NC parameters listed below must be set.
For details, refer to the parameter descriptions.
1 Bit 6 of parameter No. 1810 = 0 (A/D conversion is performed.)
2 Bit 0 of parameter No. 1811 = 1
(A/D conversion data is output in highspeed mode.)

1293
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.36
Reading the Tool Offset
Data According to the [Description]
Specified Tool Number The tool number is spedified and the tool offset data is read.

Set data Read data


0 0
Function code Function code
213 213
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data format Data format

8 8
Tool number Tool number

10 10
Data area offset data
(4 byte) (4 byte)

16 16

The data form Tool number


Kind of the data to be read
CTL1 CTL2
Tool number 01 Tool display number
Pot number 10 Tool No.
Pot number 11 Tool display number
Tool length compensation value 20 Tool No.
Tool length compensation value 21 Tool display number
Cutter compensation value 30 Tool No.
Cutter compensation value 31 Tool display number

NOTE
Please use the bit 4 of NC parameter as 1.
When the completion code 5 is returned, change the
format of the window in the SETTING Screen.
(REFERENCE:chapter II 4.4 SETTING Screen)

1294
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.37 [Explanation of data]


Reading Tool Life The tool group number in which a tool number is registered is read.
Management Data Note that the tool number area is four bytes in length so that a tool number
(Tool Group Numbers) of up to eight digits can be specified.
(Lowspeed Type)
[Input data structure]

Settings After reading


0 0
Function code Function code
200 200
+2 +2
Completion code Completion code

+4 +4
Data length Data length
4
+6 +6
Data format Data format
0
+8 +8

Tool number Tool number


+10 +10

+12 +12
Data area Tool group number
+14 (4 byte) +14 (4 byte)

+16 +16

1295
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.38 [Explanation of data]


Reading Tool Life The tool length compensation number corresponding to the specified tool
Management Data group number and tool number is read.
(Tool Length Note that the tool number area is four bytes in length so that a tool number
of up to eight digits can be specified.
Compensation Number
1) (Lowspeed Type)
[Input data structure]

Settings After reading


0 0
Function code Function code
227 227
+2 +2
Completion code Completion code

+4 +4
Data length Data length
4
+6 +6
Tool group number Tool group number

+8 +8

Tool number Tool number


+10 +10

+12 +12
Data area Tool length
compensation number
+14 (4 byte) +14 (4 byte)

+16 +16

1296
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.39 [Explanation of data]


Reading Tool Life The cutter compensation number corresponding to the specified tool
Management Data group number and tool number is read.
(Cutter Compensation Note that the tool number area is four bytes in length so that a tool number
of up to eight digits can be specified.
Number 1)
(Lowspeed Type)
[Input data structure]

Settings After reading


0 0
Function code Function code
228 228
+2 +2
Completion code Completion code

+4 +4
Data length Data length
4
+6 +6
Tool group number Tool group number

+8 +8

Tool number Tool number


+10 +10

+12 +12
Data area Cutter compensation
number
+14 (4 byte) +14 (4 byte)

+16 +16

1297
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.40 [Explanation of data]


Reading Tool Life The tool information (state) corresponding to the specified tool group
Management Data number and tool number is read.
(Tool Information 1) Note that the tool number area is four bytes in length so that a tool number
of up to eight digits can be specified.
(Lowspeed Type)
[Input data structure]

Settings After reading


0 0
Function code Function code
201 201
+2 +2
Completion code Completion code

+4 +4
Data length Data length
4
+6 +6
Tool group number Tool group number

+8 +8

Tool number Tool number


+10 +10

+12 +12
Data area Tool length
compensation number
+14 (4 byte) +14 (4 byte)

+16 +16

Explanation of tool information


1 : The tool is registered.
2 : The tool has expired.
3 : The tool has been skipped.

1298
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.41
Reading Real [Explanation of data]
Parameters Real parameters are read from the CNC.
(Lowspeed Type)
[Input data structure]

Settings After reading


0 0
Function code Function code
321 321
+2 +2
Completion code Completion code

+4 +4
Data length Data length
4
+6 +6

Parameter number Parameter number


+8 +8

+10 0: no axis +10


Data attribute 1 to n: Data attribute
axis specified
+12 +12
Decimal point position Decimal point position

+14 +14
Data area Parameter value
+16 +16
(4 byte) (4 byte)

+18 +18

NOTE
An integer or bit parameter cannot be read using function
code 321.
Read a parameter using:
D Real parameter: Function code 321
D Integer or bit parameter: Function code 17

Example) The value of a readout parameter is as follows:


(Value of a readout parameter) =
(value of the parameter on the NC)
10(specified decimal point position)
Parameter value Value on the NC Decimal point position

1 0
12 1
123 1.123 2
1234 3
12340 4

1299
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.42
Reading the actual [Description]
Machine Position
The machine position (machine coordinates) on a feed axis controlled by
(Machine Coordinates) the CNC can be read.
of Controlled Axes. The machine position value includes the servo delay and the acceleration
/ deceleration delay.
So, this value might be not corresponding to the machine position value
on the position screen in the CNC.(This screen can be displayed by
pressing the function button POS.)
[Structure]

Input data Output data


0 0
Function code Function code
329 329
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data number Data number
0 0
8 Data attribute 8 Data attribute
M M
(M=Axis number) (M=Axis number)
10 10
Data area Data area
(4 byte)
(4 byte)

14 14

The unit of the output value is determined as follows:


(1) The case of radius programming axis.
The output data shows twice value of the present position with the
least input increment.
(2) The case of diameter programming axis.
The output data shows a value of the present position with the least
input increment.
(3) The case that the least input increment is set to tentimes value as
large as the least command increment.
The output data shows twentytimes value of the present position
(radius programming) or tentimes value of the present position
(diameter programming) with the least command increment.

NOTE
1 This function is provided by the FS15iA (PMCNB6) only.
2 To use this function, please set NC parameter 1013#7 to 1.
This parameter should be set only for necessary axes
because this parameter increases the load of CNC CPU.

1300
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.3.43
Reading Fine Torque [Description]
Sensing Data
This function reads the statistical calculation results (average value,
(Statistical Calculation
maximum value and distribution) in the fine torque sensing function.
Results).
[Structure]

Set data Read data


0 0
Function code Function code
226 226
2 2
Completion code Completion code

4 4
Data length Data length
6 Axis count
6 6
Data number Data number

8 8
Axis number Axis number
1: Read all axes
10 n: Read one axis 10
Data area
In case that Axis number is set to n
10
Average value of
target axis
12
Maximum value of
target axis
14
Distribution of
target axis
16
In case that Axis number is set to 1:
10
Average value of
target axis 1
12
Maximum value of
target axis 1
14
Distribution of
target axis 1
16
Average value of
target axis 2
18
Maximum value of
target axis 2
20
Output only for number of axes specified to Distribution of
parameter NO.4670 to 4673. target axis 2
22
:

NOTE
This function is provided by the FS15iA (PMCNB6) only.

1301
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.44 (1) Store Counter


Reading Fine Torque [Description]
Sensing Data (Store This function reads the number of stored torque data items. (Store
Data) Counter)
[Structure]

Set data Read data


0 0
Function code Function code
232 232
2 2
Completion code Completion code

4 4
Data length Data length
4
6 6
Data attribute Data attribute

8 8
Axis number Axis number
0 0: Newest data counter 0
10 1: Sample data counter 10
Data area Store counter value

14

NOTE
This function is provided by the FS15iA (PMCNB6) only.

1302
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

(2) Stored torque data (newest data)


[Description]
This function reads the newest stored data among stored torque data
[Structure]

Set data Read data


0 0
Function code Function code
232 232
2 2
Completion code Completion code

4 4
Data length Data length
2 or 0
6 6
Data attribute 10: Newest data counter Data attribute
11: Sample data counter
8 8
Axis number Axis number
N N
10 10
Data area Newest stored data

12

NOTE
1 When no data is stored, 0 is read as data length and no
data is read. The function completes normally.
2 When data attribute is set to 11, the sample data whose
number is same as the last number of newest data is read.
Ex.) In case that 10000 sample data items (the data number
from 0 to 9999) and newest data items 5000 (the data
number from 0 to 4999) are stored, newest data which
number is 4999 is read when data attribute is set to
10. And sample data which number is 4999 is read
when data attribute is set to 11.
3 When data attribute is set to 11 and no sample data whose
number is same as the last number of newest data is stored,
0 is read as data length and no data is read. The function
completes normally.
Ex.) In case that 5000 sample data items (the data number
from 0 to 4999) and newest data items 10000 (the data
number from 0 to 9999) are stored, no data is read, and
the function completes normally when data attribute is
set to 11.

1303
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

(3) Stored torque data (any data)


[Description]
This function reads the newest stored data among stored torque data
[Structure]

Set data Read data


0 0
Function code Function code
232 232
2 2
Completion code Completion code

4 4
Data length Data length
2 or 0
6 6
Data attribute 20: Newest data counter Data attribute
21: Sample data counter
8 8
Axis number Axis number
N N
10 10
Data number Data number
m m
14 14
Number of data items Number of data items
n n
16 16
Number m data

18
Number m+1 data

20
Number m+2 data

22
:

24
Number m+n1 data

26

1304
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

NOTE
1. The valid area of data number m is as follows:
0 m (524288 1/a 1/b) 1
1 : the number of the axes for Fine Torque Sensing is 1
for a = 2 : the number of the axes for Fine Torque Sensing is 2
4 : the number of the axes for Fine Torque Sensing is 3 or 4
1 : sample data saving function is disabled
b=
2 : sample data saving function is enabled
The valid area of the number of data n is as follows:
1 n 120
2. When data number m which is in the valid range exceeds the number of actually stored data
items, 0 is read as data length and no data is read. The function completes normally.
Ex.) In case that the number of target axes is 2 and the sample data store function is enabled,
the data numbers are valid in the range between 0 and 13107. However, if an attempt is
made to read data from data number m 131020 when the number of actually stored data
items is 131000 (the data number from 0 to 130999), 0 is read as data length and no data
is read. The function completes normally.
(Example 1 in figure below)
3. When data number m is within the number of actually stored data items, and the number
m+n1 exceeds the number of actually stored data items, data of the stored data items is read.
The function completes normally.
In this case, double of the number of read data items is read as data length.
Ex.) If an attempt is made to read number of data items n 120 from data number m 130900
under the same conditions as in the example above, the data number from 130900 to
130999 is read and 200 is read as data length.
(Example 2 in figure below)
Also if an attempt is made to read number of data items n 120 from data number m
130990 under the same conditions as in the example above, the data number from 130990
to 130999 is read, and 20is read as data length.
(Example 3 in figure below)

Data number vallid range


Range of actually stored data

Specified range (Ex. 1)

Reading range
Specified range (Ex. 2)

Reading range
Specified range (Ex. 3)

0 131000 131071

1305
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.3.45
Reading detailed [Description]
information of CNC This function reads detailed information of CNC alarm.
alarm. The detailed information of CNC alarm is as follows.
D axis number
D alarm type
D alarm number
[Structure]

Set data Read data


0 0
Function code Function code
330 330
2 2
Completion code Completion code

4 4
Data length Data length
8n+2
6 6
Number of alarm Number of alarm
1 to 30 1 to 30
8 8
Alarm type 1 : All alarm types Alarm type
1 to 20 0 to 20 : Alarm type
10 10
Data area Alarm information

(n = read number of alarm.)

NOTE
This function is provided by the FS15iA (PMCNB6) only.

[Alarm type]
Following is a correspondence table of the alarm type and the alarm type
number.
Alarm type Alarm type Alarm type
Alarm type Alarm type Alarm type
number number number
0 BG alarm 10 SR alarm 20 SP alarm
1 PS alarm 11
2 OH alarm 12 SV alarm
3 13 IO alarm
4 SN alarm 14 PW alarm
5 SW alarm 15 SY alarm
6 OT alarm 16
7 PC alarm 17
8 EX alarm 18
9 19 MC alarm

1306
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

[Structure of detailed alarm information]

2 byte 4 byte 2 byte 2 byte 8 byte 8 byte

Number Axis information Alarm Alarm


of read type number .....
alarm 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8
23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24
0 : Not axis type. .....
bit0=1 : An alarm is issued for
the first axis.
bit1=1 : An alarm is issued for
the second axis.
: :

.....
First alarm Second nth
alarm alarm

[Example]
NC alarm : OT alarm NO.6 (An alarm is issued for the 1st axis.)
: SV alarm NO.10,11 (Alarms are issued for the 3rd axis.)
: Ex alarm NO.5 (Not axis type)
When these alarms are issued, the read data is as follows.
1. In case that the SV alarm is read.

Set data Read data


0 0
Function code 330 Function code 330
2 2
Completion code Completion code 0
4 4
Data length Data length 18
6 6
Number of alarm 10 Number of alarm 10
8 8
Alarm type 12 Alarm type 12
10 10
Number of read alarms 2
12
Axis information 1 4
16
Alarm type 1 12
18
Alarm number 1 10
20
Axis information 2 4
24
Alarm type 2 12
26
Alarm number 2 11
28

1307
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

2. In case that all alarms are read.

Set data Read data


0 0
Function code 330 Function code 330
2 2
Completion code Completion code 0
4 4
Data length Data length 34
6 6
Number of alarm 10 Number of alarm 10
8 8
Alarm type 1 Alarm type 1
10 10
Number of read alarms 4
12
Axis information 1 1
16
Alarm type 1 6
18
Alarm number 1 6
20
Axis information 2 4
24
Alarm type 2 12
26
Alarm number 2 10
28
Axis information 3 4
32
Alarm type 3 12
34
Alarm number 3 11
36
Axis information 4 0
40
Alarm type 4 8
42
Alarm number 4 5
44

1308
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4 (1) See the description of the window function. The data item marked
with a dash () in the description of the data structure need not be
FORMAT AND entered.
DETAILS OF THE When output, the data item has no meaning.
CONTROL DATA OF (2) The length of all data blocks and data items is represented in bytes.
THE WINDW (3) The output data becomes valid only when the instruction terminates
FUNCTIONAL normally.
INSTRUCTION Completion code Description
10 The window instruction is being processed. Hold ACT
until W1 is set to 1.
0 The instruction terminated normally.
1 An error occurred. The corresponding function number is
not found.
2 An error occurred. Possible causes include the following:
Wrong data is found in the CTL area. The NC does not
have the corresponding function.
3 An error occurred. The specified axis is not provided.
5 An error occurred. it is a mistake of data form. Though the
function supports only a new format, a old format is speci-
fied.

1309
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.1 [Description]
Writing a Tool Offset The data is directly written into the tool offset value (tool compensation)
Data area of the CNC.
Set data
0
Function code
14
2
Completion code

4
Data length
4
6
Offset number

8
Offset format

10
Tool offset value
(4 byte)

14
(Note 1) Offset format
M system (machining center system) T system (lathe system)

Data type Format Offset number Data type Format Offset number
(CTL+2, 3) (CTL+2, 3)

Tool compensation A Tool compensation A


Compensation 1 Offset number Compensation along the 1 Offset number
Xaxis
Tool compensation B Compensation along the 2 Offset number
Geometry 1 Offset number Zaxis
compensation Tooltip radius compensation 3 Offset number
Wear 1 Offset number Compensation along the 4 Offset number
compensation +1000 Yaxis
Compensation related to the posi- 5 Offset number
tion of the virtual tool Offset number
Tool compensation C
Tool length
Geometry 1 Offset number Tool compensation B
compensation Geometry compensation
Wear 1 Offset number Compensation along the Xaxis 1 Offset number
compensation +1000 Compensation along the Zaxis 2 Offset number
Tooltip radius compensation 3 Offset number
Cutter Compensation along the Yaxis 4 Offset number
Geometry 2 Offset number Wear compensation
compensation Compensation along the Xaxis 1 Offset number
Wear 2 Offset number +1000
compensation +1000 Compensation along the Zaxis 2 Offset number
+1000
Tooltip radius compensation 3 Offset number
+1000
Compensation along the Yaxis 4 Offset number
+1000
Compensation related to the 5 Offset number
position of the virtual tool

1310
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.2 [Description]
Writing a Parameter The data is written into the parameter area of the CNC.
(Setting Data) The parameters of the CNC are classified into four types according to the
smallest unit that has a meaning. Bit parameter: Each bit has a meaning.
Byte parameter: Each byte has a meaning. Word parameter: Each set of
two bytes has a meaning. Double word parameter: Each set of four bytes
has a meaning.
Each bit of a bit parameter cannot be written individually. The eight bits
(one byte) of the parameter must be written at a time. To change a bit of
a bit parameter, read the entire parameter, change the desired bit, then
write the entire parameter.
Set data
0
Function code
18
2
Completion code

4
Data length
4
6
Parameter number

8 0 : No axis
Data attribute

10 1 to n : A specified axis
Parameter data
(4 byte)

14
(Note 1) Format of parameter data
If the data is one byte long, it is set in the DATA+0 area.

10
DATA+0
11
DATA+1
12
DATA+2
13
DATA+3
14

NOTE
For the PMCNB6, realtype parameters cannot be written,
causing a CTL ERROR to occur.

1311
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.3
Writing a Custom [Description]
Macro Variable The data is written into the custom macro variable area of the CNC.
Set data
0
Function code
22
2
Completion code

4
Data length
6
6
Custom macro
number
8
Data attribute
0
10
Custom macro
variable value
(4 byte)
14 Position of
decimal point
(2 byte)
16

(Note 1) In the case of writing a Custom Macro Variable of


upper than 100000.
Please input 10 to Data attribute, and input last
four digits of variable number to Custom macro
variable number.

(Note 2) Specification of the position of the decimal point


7 6 5 4 3 2 1 0
DATA+4

#0 to #3 : Set number of digit beelow decimal point.


#4 to #7 : Set to 0.

Examples (Value written in the NC) +


(value of custom macro variable)
10 (Positon of decimal point)
Value in the NC Custom macro variable value Position of
decimal point
1234. 000 0
123. 400 1234 1
12. 340 2
1. 124 3
0. 1234 4

1312
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.4 [Description]
Writing a Data on the The data to be displayed on the program check screen of the CNC is
Program Check Screen rewritten.
Set data
0
Function code
150
2
Completion code

4
Data length
2, 4
6
Data type

8
Data attribute
0
10
Data on the program
check screen
(2 byte)
12

Data length Data Attrib


Data type
15B 15i type ute
M code which is being executed (1 to 5) 2 2 1 to 5 0
Spindle speed range 2 2 100 0
Spindle tool number 2 2, 4 200 0
Number of the tool to be used next 2 2, 4 201 0

NOTE
1 As much program check screen data as the amount
specified with the data length can be written.
2 When the 15i is used, the spindle tool number and the next
machining tool number can each be written into a 2 or
4byte area.

1313
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.5
Writing the Torque [Description]
Limit Override The torque limit override of the specified feed axis is rewritten.
Set data
0
Function code
152
2
Completion code

4
Data length
2
6
Data type
0
8
Axis number
Value
10 Unsigned binary <Unit: %>
Torque limit override The values from 0 to 255 correspond to
0% to 100%.
12

[Example]
If the torque limit override is 50%, please set to 128.

NOTE
This window is valid for parameters set on the CNC.
Parameter 1802#4 0: Fixed to override 100%
1: This window enabled.

1314
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.6
Writing the Tool Life [Description]
Management Data The tool number and the tool life value are written into the specified tool
(Tool Group Number) group.

Set data
0
Function code
163
2 Data type Specification
Completion code
Number of Register the tool group.
tool groups Set group number, tool life value, and tool life counter for
4 transmission data.
Data length
4 7 6 5 4 3 2 1 0
DATA+0 Group number
6
Data number Life counter type
DATA+1 DATA+1 BIT 7
0
8 DATA+2
Tool life value
Tool No. DATA+3

10 Group number 1 to 512


Tool life value 1 to 9999 (Specified number of time)
Tool group No.
1 to 4300 (Specified time)
(4 byte) Tool life counter type ( DATA+1 BIT 7)
12 0: Number of time
Tool life value 1: Time (minute)
14

C.4.7
Writing the Tool Life
Management Data [Description]
(Tool Life) The data is written into the tool life value area of the specified tool group.
Set data
0
Function code
164
2
Completion code

4
Data length
4
6
Tool group No.

8
Data attribute
0
10
Tool life
(4 byte)

14

1315
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.8
Writing the Tool Life [Description]
Management Data The data is written into the tool life counter area of the specified tool
(Tool Life Counter) group.

Set data
0
Function code
165
2
Completion code

4
Data length
4
6
Tool group No.

8
Data attribute
0
10
Tool life counter
(4 byte)

14

C.4.9
Writing the Tool Life [Description]
Management Data The data is written into the tool life counter type area of the specified tool
(Tool Life Counter Type) group.

Set data
0
Function code
166
2
Completion code

4
Data length
4
6
Tool group No.

8
Data attribute
0
10
Tool life counter type
(4 byte)

14

Tool life counter type


1 : The tool life counter indicates the number of times the tool has been used.
2 : The tool life counter indicates the period of time the tool has been used.

1316
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.10
Writing the Tool Life
Management Data (Tool [Description]
Length Compensation The data is written into the tool length compensation number area
Number 1) specified by the tool group number and tool number.

Set data
0
Function code
167
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool No.

10
Tool length
compensation No.
(4 byte)

14

C.4.11
Writing the Tool Life
Management Data (Tool [Description]
Length Compensation The data is written into the tool length compensation number area
Number 2) specified by the tool group number and tool order number.

Set data
0
Function code
168
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool order number

10
Tool length
compensation No.
(4 byte)

14

1317
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.12
Writing the Tool Life
Management Data [Description]
(Cutter Compensation The data is written into the cutter compensation number area specified by
Number 1) the tool group number and tool number.

Set data
0
Function code
169
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool No.

10
Cutter
compensation No.
(4 byte)

14

C.4.13
Writing the Tool Life
Management Data [Description]
(Cutter Compensation The data is written into the cutter compensation number area specified by
Number 2) the tool group number and tool order number.

Set data
0
Function code
170
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool order number

10
Cutter
compensation No.
(4 byte)

14

1318
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.14
Writing the Tool Life [Description]
Management Data The data is written into the tool information (status) area specified by the
(Tool Information 1) tool group number and tool number.

Set data
0
Function code
171
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool No.

10
Tool information
(4 byte)

14

Tool information
1 : The tool is cataloged.
2 : The tool life has expired.
3 : The tool was skipped.

C.4.15
Writing the Tool Life [Description]
Management Data The data is written into the tool information (status) area specified by the
(Tool Information 2) tool group number and tool order number.

Set data
0
Function code
172
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool order number

10
Tool information
(4 byte)

14

1319
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.16
Writing the Tool Life [Description]
Management Data A tool number is written into (added to) the area specified by the tool
(Tool Number) group number and tool order number.
Set data
0
Function code
173
2
Completion code

4
Data length
4
6
Tool group No.

8
Tool order number

10
Tool No.
(4 byte)

14

1320
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.17
Writing the Tool Offset
Data According to the [Description]
Specified Tool Number The tool number is specified and the tool offset data is written.
Set data
0
Function code
214
2
Completion code

4
Data length
4
6
Data format

8
Tool number

12
offset data
(4 byte)

16

The data form Tool number


Kind of the data to be written
CTL1 CTL2
Change of Tool number 00 Tool No.
Change of Tool number 01 Tool display number
Pot number 10 Tool No.
Pot number 11 Tool display number
Tool length compensation value 20 Tool No.
Tool length compensation value 21 Tool display number
Cutter compensation value 30 Tool No.
Cutter compensation value 31 Tool display number
Addition of Tool number 40 Tool No.
Addition of Tool number 41 Tool display number

NOTE
(Only Series 15B)
Please use the bit 4 of NC parameter as 1.
When the completion code 5 is returned, change the
format of the window in the SETTING Screen.
(REFERENCE : chapter II 4.4 SETTING Screen)

1321
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.18
Writing the [Description]
Superposition Move After the axes for manual handle feed are selected in the manual handle
Command feed mode, the traveling distances (number of pulses) corresponding to
three manual pulse generators are written. The set value ranges from 256
to +256.
The specified number of pulses is assumed to be the number of pulses
entered from the manual pulse generator. The speed is calculated as
follows: (specified number of pulses) (magnification) 62.5
(pulses/second) The data in parameters 1413 and 1414 of the CNC is
valid for this function.
(1) For three axes
Set data
0
Function code
215
2
Completion code

4
Data length
6
6
Data number
0
8
Data attribute
0
10
Superposition
move command
(6 byte)

16

(Note 1) Format of superposition move command

DATA+0
First manual pulse generator
DATA+2
Second manual pulse generator
DATA+4
Third manual pulse generator
DATA+6

The data for using the fourth manual pulse generator is as shown on the
next page.

1322
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

(2) For four axes

Set data
0
Function code
215
2
Completion code

4
Data length
8
6
Axis specification
mode
8
Axis number

10
Superposition
move command
(8 byte)

18

Axis specification mode


7 6 5 4 3 2 1 0

#0 : Mode selection (0: The BMI signal is selected. 1: An axis number is selected.)

Axis number
7 6 5 4 3 2 1 0
CTL+8 CTL+8, #0 to #3: Axis number of the first pulse generator (P1)
P2 P1 CTL+8, #4 to #7: Axis number of the second pulse generator (P2)
CTL+9 CTL+9, #0 to #3: Axis number of the third pulse generator (P3)
P4 P3
CTL+9, #4 to #7: Axis number of the fourth pulse generator (P4)

(Note 1) Format of superposition move command


DATA+0
First manual pulse generator
DATA+2
Second manual pulse generator
DATA+4
Third manual pulse generator
DATA+6
Fourth manual pulse generator
DATA+8

1323
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.19 [Description]
Writing the Feedrate Feedrate writing can be specified only in the feedperminute mode. The
velocity command is specified with F 10d. A flag is provided to
validate either the command of the PMC or the feedrate of the CNC. After
the flag is set, the velocity command specified in the NC is invalidated.
To validate the feedrate of the NC, set the flag to 0.
Set data
0
Function code
216
2
Completion code

4
Data length
6
6
Data number
0
8
Data attribute
0
10
Feedrate
(6 byte)

16

(Note 1) Format of feedrate


7 6 5 4 3 2 1 0
DATA+0 Flag for validating the velocity command
: Bit 2 of DATA+0
DATA+2 (0: The NC is valid.
Feedrate, F 1: The PMC is valid.)
DATA+4 Exponent Feedrate, F : DATA+2 and DATA+3
of feedrate, d Exponent of feedrate, d : DATA+4 and DATA+5
DATA+6

NOTE
With the FS15iA (PMCNB6), this function is of the
lowspeed type. Therefore, this function need not be
interlocked with other windows.

1324
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.20 [Explanation of data]


Writing Tool Life A tool number and a tool life value are written to a specified tool number.
Management Data Note that the tool number area is four bytes in length so that a tool number
(Tool Group Numbers) of up to eight digits can be specified.
[Input data structure]

Settings
0
Function code
202
+2
Completion code
Data type Data specifications
+4 Tool group number The tool group is registered. As transfer data, the group
Data length number, life value, and life counter type are set.
6
7 6 5 4 3 2 1 0
+6
Data number DATA+0 Group number +
0 life counter type
DATA+1
+8 (DATA+1 BIT7 7)
DATA+2
Tool number DATA+3
+10 Life values
DATA+4
+12 DATA+5
Tool group number
+14 (6 byte)
Tool life value Group number 1 to
Life value 1 to 99999999 (if a count is specified)
+16 1 to 59940 (if a time is specified)
Life counter type (DATA+BIT 7)
+18 0 : Count
1 : Time (in minutes)

NOTE
This function is provided by the FS15iA (PMCNB6) only.

1325
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.21 [Explanation of data]


Writing Tool Life Data is written to the tool length compensation number specified by a tool
Management Data (Tool group number and a tool number.
Length Compensation Note that the tool number area is four bytes in length so that a tool number
of up to eight digits can be specified.
Number 1)
[Input data structure]
Settings
0
Function code
229
+2
Completion code

+4
Data length
4
+6
Tool group number

+8
Tool number
+10

+12
Tool length
+14 compensation number
(4 byte)
+16

NOTE
This function is provided by the FS15iA (PMCNB6) only.

1326
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.22 [Explanation of data]


Writing Tool Life Data is written to the cutter compensation number specified by a tool
Management Data group number and a tool number.
(Cutter Compensation Note that the tool number area is four bytes in length so that a tool number
of up to eight digits can be specified.
Number 1)
[Input data structure]
Settings
0
Function code
230
+2
Completion code

+4
Data length
4
+6
Tool group number

+8
Tool number
+10

+12
Cutter compensation
+14 number
(4 byte)
+16

NOTE
This function is provided by the FS15iA (PMCNB6) only.

1327
C. WINDOW FUNCTION DESCRIPTION
(PMCNB/NB2/NB6) APPENDIX B61863E/14

C.4.23 [Explanation of data]


Writing Tool Life Data is written to the tool information (state) specified by a tool group
Management Data number and a tool number.
(Tool Information 1) Note that the tool number area is four bytes in length so that a tool number
of up to eight digits can be specified.
[Input data structure]
Settings
0
Function code
231
+2
Completion code

+4
Data length
4
+6
Tool group number

+8
Tool number
+10

+12
Tool information
+14
(4 byte)
+16

Explanation of tool information


1 : The tool is registered.
2 : The tool has expired.
3 : The tool has been skipped.

NOTE
This function is provided by the FS15iA (PMCNB6) only.

1328
C. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (PMCNB/NB2/NB6)

C.4.24
Writing Real [Explanation of data]
Parameters Real parameters are written to the CNC.
(Lowspeed Type)
[Input data structure]
Settings
0
Function code
323
+2
Completion code

+4
Data length
6
+6
Parameter number
+8

+10
Data attribute 0: no axis
1 to n: axis specified
+12
Decimal point position

+14
Data area
+16
(4 byte)
+18

NOTE
Integer parameters cannot be written.

Example)
(Parameter variable value)
(Value to be set on the NC) =
10(specified decimal point position)
Value to be set on Custom macro Decimal point position
the NC variable value

1234.000 1234 0
123.400 1
12.640 2
1.234 3
0.1234 4

1329
D. WINDOW FUNCTION DESCRIPTION
(FS16/16iLA) APPENDIX B61863E/14

D WINDOW FUNCTION DESCRIPTION (FS16/16iLA)

1330
D. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16/16iLA)

D.1 The following function is added to PMCCNC window function for


FS16LA.
OUTLINE
(1) Transferring a processing condition file in nonvolatile memory to
data area in CNC memory, and vice versa.
(2) Reading a comment command in a part program.
(3) Reading data commanded to laser oscillator
The following functions are added to the PMCCNC window function on
the FS16iLA:
(1) Reading of comments
Comments specified within programs can be read.
(2) Laser command value data and laser setting data can be read and
written, and command value data to the laser oscillator can be read.

CAUTION
Data transfer of machining condition files between data
areas is not possible by ladder diagrams on the FS16iLA.

1331
D. WINDOW FUNCTION DESCRIPTION
(FS16/16iLA) APPENDIX B61863E/14

D.2
FUNCTION

D.2.1 (1) Transfer from data area to nonvolatile memory. (% lowspeed


type)
Transfer Between Data
Area and Nonvolatile
Memory [Contents of data]
The data can be transferred from the data area in CNC to PMC
nonvolatile memory by PMCRC application.
Setting the original data set or group in data attribute M.
Setting the written address of nonvolatile memory for the offset address
from the top address in address N.
Setting the total byte No. of written data set in address L.
Setting the forward structure of data set in data.
And the data can be transferred set or group from data area to nonvolatile
memory.

[Structure of input data]

Top address + 0 The following End Code is output at reading end.

(Function code) 0 : normal end


183 3 : The incorrect data is set in Address.
4 : The incorrect data is set in Data attribute.
2
(End Code)

(No need to set)

4 L = Set the total byte No. of the data structure


(Data length) for 1 set in nonvolatile memory.
L This data must be set in case of transferring
the data group.
(Noneed to set in case of transferring the set)
6
(Address) N = Set the forward address by the offset from
N the top address of nonvolatile memory.

8
M = Set the kind of data set or group to transfer
(Data attribute)
M 110 : Set of processing data
101103 : Set of piercing d data
10 201205 : Set of edge process data
(Data) 1000 : Group of processing data
1001 : Group of piercing data
1002 : Group of edge process data

Structure of data set


Set the correspondence of 1 set of data item in
data area and data item in nonvolatile memory
by relative address for nonvolatile memory.
(See note for details.)

1332
D. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16/16iLA)

(2) Transfer from nonvolatile memory to data area (% lowspeed type)

[Contents of data]
The data can be transferred from the processing condition file registered
in nonvolatile memory to the data area in CNC by PMCRC application.
Setting the forward data set or group in data attribute M.
Setting the original read address for the offset address from nonvolatile
memory top address in address N.
Setting the total byte No. of original data set in address L.
Setting the original structure of set in data.
And the data of set or group can be transferred from nonvolatile memory
to data area.

[Structure of input data]

Top address + 0 The following End Code is output at reading end.

(Function code) 0 : normal end


184 3 : The incorrect data is set in Address.
4 : The incorrect data is set in Data attribute.
2
(End Code)

(No need to set)

4 L = Set the total byte No. of the data structure


(Data length) for 1 set in nonvolatile memory.
L This data must be set in case of transferring
the data group.
(Noneed to set in case of transferring the set)
6
(Group No.) N = Set the original address by the offset from
N the top address of nonvolatile memory.

8
M = Set the kind of data set or group to transfer
(Data attribute)
M 110 : Set of processing data
101103 : Set of piercing d data
10 201205 : Set of edge process data
(Data) 1000 : Group of processing data
1001 : Group of piercing data
1002 : Group of edge process data

Structure of data set


Set the correspondence of 1 set of data item in
data area and data item in nonvolatile memory
by relative address for nonvolatile memory.
(See note for details.)

1333
D. WINDOW FUNCTION DESCRIPTION
(FS16/16iLA) APPENDIX B61863E/14

(3) Data structure of data area


(a) Processing data set
Address Data item Byte No.
0 Feedrate 4
4 Peak power 2
6 Pulse frequency 2
8 Pulse duty 2
10 Assist gas pres. 2
12 Assist gas select 2
14 Assist gas settling time 2
16 Reference displacement 2
18 Offset amount 4
22 Edge process select 2
24 Startup process select 2

(b) Piercing data set


Address Data item Byte No.
0 Peak power 2
2 Initial frequency 2
4 Initial duty 2
6 Frequency increment 2
8 Duty increment 2
10 Step time 2
12 Step No. 2
14 Piercing time 4
18 Assist gas pres. 2
20 Assist gas select 2
22 Assist gas settling time 2
24 Reference displacement 2

(c) Edge processing data set


Address Data item Byte No.
0 Judge angle 2
2 Peak power 2
4 Pulse frequency 2
6 Pulse duty 2
8 Piercing time 4
12 Assist gas pres. 2
14 Assist gas select 2
16 Return distance 4
20 Return feed rate 2
22 Return frequency 2
24 Return duty 2

1334
D. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16/16iLA)

NOTE
Example of data set
The address in Data is set as follows, for example, in case
of the following data structure of processing condition file in
nonvolatile memory.

Data structure of data area The example of data structure for


the processing condition file in
nonvolatile memory

Address Data Address Data

0 Feedrate 0 Feedrate

4 Peak power 4 Peak power

6 Pulse frequency 6 Pulse frequency


8 Pulse duty 8 Pulse duty

10 Assist gas pres. 10 Focus distance

12 Assist gas select 12 Assist gas pres.

14 Assist gas time 14 Assist gas select

16 Ref. displacement 16 Assist gas time

18 Offset amount 18 Ref. displacement

22 Edge select 20 Offset amount

24 Startup select 24 Pulse type

26 Edge select

28 Startup select

Data item in data area Address Data setting value

Feedrate Top address +10 0


Peak power Top address +12 4
Pulse frequency Top address +14 6
Pulse duty Top address +16 8
Assist gas pres. Top address +18 12
Assist gas select Top address +20 14
Assist gas time Top address +22 16
Ref. displacement Top address +24 18
Offset amount Top address +26 20
Edge select Top address +28 26
Startup select Top address +30 28

1335
D. WINDOW FUNCTION DESCRIPTION
(FS16/16iLA) APPENDIX B61863E/14

D.2.2 The data in the parentheses is written in the comment area, if the following
Reading of the Mcode is commanded in a part program. This comment can be read from
PMC.
Comment
Mxxx (* * * * * * *) ;

Less than 24 characters,


including alphabet, numeral, decimalpoint and +/

[Contents of data]
Contents of the data can be read for ASCII code.

[Structure of input data]

Top address + 0 The following End Code is output at writing end.

(Function code) 0 : normal end


140 1 : The data length of comment data is over 24
bytes
2
(End Code)

(No need to set)

4
L = Data length of the comments read in.
(Data length) (Added 1 in case of the odd number.)
L

(Group No.)

8
(Data attribute)

10
(Data) The read comment data is set.

NOTE
1 The comment is overwritten if the next comment is input.
2 Mcode number for reading of the comment is set to
parameter number 15350.
Setting value is 0 to 999.

1336
D. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16/16iLA)

D.2.3 (1) Reading the laser command data and laser setting data
Reading and Writing (:highspeed type)
the Laser Command
Data and Laser Setting [Contents of the data]
Data The laser command data and laser setting data for CNC can be read by
PMCRC application. The data are separated to groups and can be read
by the group.

[Structure of input data]

Top address + 0 The following End Code is output at writing end.

(Function code) 0 : normal end


186 2 : The incorrect data is set for Data length.
3 : The incorrect data is set for Data No.
2
(End Code)

(No need to set)

4
L = Set the byte No. assigned for the group.
(Data length)
L

6
N = Set the group No.
(Group No.)
N

8
(Data attribute)

(No need to set)
10
(Data)

1337
D. WINDOW FUNCTION DESCRIPTION
(FS16/16iLA) APPENDIX B61863E/14

(2) Writing the laser command data and laser setting data (:lowspeed
type)

[Contents of the data]


The data can be written to the laser command data for CNC by PMCRC
application. The data are separated to groups and can be written by the
group.

[Structure of input data]

Top address + 0 The following End Code is output at writing end.

(Function code) 0: normal end


187 2: The incorrect data is set for Data length.
3: The incorrect data is set for Data No.
2 5: The data beyond the allowable range is set
(End Code) for data command to write.

(No need to set)

4
L = Set the byte No. assigned for the group.
(Data length)
L

6
N = Set the group No.
(Group No.)
N

8
(Data attribute)

(No need to set)
10
(Data)

1338
D. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16/16iLA)

(3) The data structure of the laser command data and laser setting data

Group No. Address Top Byte No. Data length Item


add. + for every item Byte No.
0 10 2 4 Power control duty const
12 2 Power control minimum duty
1 10 2 10 Power monitor (Read only)
12 2 Power offset (Read only)
14 2 Actual power (Read only)
16 4 Actual feedrate (Read only)
2 10 2 2 Power input offset coe.
3 10 2 4 Assist gas select
12 2 Assist gas flow select
4 10 2 30 Assist gas flow1 pretime
12 2 prepres
14 2 wrkpres
16 2 afttime
18 2 aftpres
20 2 Assist gas flow2 pretime
22 2 prepres
24 2 wrkpres
26 2 afttime
28 2 aftpres
30 2 Assist gas flow3 pretime
32 2 prepres
34 2 wrkpres
36 2 afttime
38 2 aftpres
5 10 2 6 Processing peak power
12 2 Processing pulse frequency
14 2 Processing pulse duty
6 0 2 10 Piercing peak power
12 2 Piercing pulse frequency
14 2 Piercing pulse duty
16 4 Piercing time
7 10 4 22 Feedrate command
14 2 Peak power command
16 2 Pulse frequency command
18 2 Pulse duty command
20 2 Assist gas select command
22 2 Assist gas settling time
24 2 Assist gas pressure
26 2 Reference displacement
28 4 Offset amount
10 10 2 2 Ref. displacement command

1339
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

E WINDOW FUNCTION DESCRIPTION (FS16W)

1340
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.1 [Description]
READING THE WIRE The wire diameter offset value recorded in the CNC can be read.
DIAMETER OFFSET
[Input data structure]
Top address
(Function)
13
+2
(Completion)

+4
(Data length)
L Offset CornerR Clearance Condition
+6
(Number)
N 015 16 17

+8
(Attribute)
0 0 0 1
M
+ 10
(Data area)

[Output data structure]


Top address
(Function)
13
+2
(Completion)
? Offset CornerR Clearance Condition
+4
(Data length) 4 4 4 8
L
+6
(Number)
015 16 17
N
+8
(Attribute) 0 0 0 1
M
+ 10
(Data area)
Offset value CornerR value Clearance value Actual offset value
D
+ 14
Direction
0, 1, 2
+ 16
Offset mode
0, 1
+ 18

1341
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

[Data number]
015 : Reads the Offset value.
016 : Reads the CornerR value.
017 : Reads the Clearance value.

[Data attribute]
0 : Reads the Offset value, CornerR value or Clearance value.
1 : Reads the condition.

[Contents of data]
a) Unit of Offset, CornerR, Clearance and actual offset value
Metric system input : 103 [mm]
(In case the incremental system is 1/10,
output data unit is 104 [mm].)
Inch system input : 105 [inch]
b) Direction in condition data
0 : Cancel offset (G40)
1 : Wire diameter compensation left (G41)
2 : Wire diameter compensation right (G42)
c) Offset mode in condition data
0 : Offset mode is 0.
1 : Offset mode is 1.

[Completion codes]
0 : The data has been read normally.
3 : Invalid data is specified as the data number.
4 : Invalid data is specified as the data attribute.

1342
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.2 [Description]
WRITING THE WIRE The wire diameter offset value can be written into the CNC.
DIAMETER OFFSET
(:LOWSPEED
RESPONSE) [Input data structure]
Top address
(Function)
14
+2
(Completion)
Offset CornerR Clearance Condition
+4
(Data length) 4 4 4 8
L
+6
(Number)
015 16 17
N
+8
(Attribute) 0 0 0 1
M
+ 10
(Data area)
Offset value CornerR value Clearance value 0, 1
D
+ 12

+ 14

[Output data structure]


Top address
(Function)
14
+2
(Completion)
?
+4
(Data length)
L
+6
(Number)
N
+8
(Attribute)
M
+ 10
(Data area)
D

1343
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

[Data number]
015 : Writes the Offset value.
016 : Writes the CornerR value.
017 : Writes the Clearance value.

[Data attribute]
0 : Writes the Offset value, CornerR value or Clearance value.
1 : Writes the condition.

[Contents of data]
a) Unit of Offset, CornerR, Clearance and actual offset value
Offset, CornerR, Clearance or Actual offset value is signed
binary in 4 bytes. A negative value is represented in 2s
complement.
b) Offset mode in condition data
0 : Offset mode is 0.
1 : Offset mode is 1.

[Completion codes]
0 : The data has been written normally.
2 : Invalid data is specified as the data length.
3 : Invalid data is specified as the data number.
4 : Invalid data is specified as the data attribute.
5 : Invalid data is specified as the data value.

1344
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.3 [Description]
READING THE Parameter data in the CNC can be read.
PARAMETER There are four types of parameters in the CNC: Bit parameters having a
(:LOWSPEED definite meaning for each bit, byte parameters holding 1byte data, word
parameters holding 2byte data, and double word parameters holding
RESPONSE) 4byte data. Therefore, the length of the read data varies according to the
parameter number specified.
Note that bit parameters cannot be read in bit units. The eighth bits (one
byte) for a parameter number must be read at a time.
For axis parameters (servo parameters), data for a specific axis can be
read, or data for all axes can be read at a time.

[Input data structure] [Output data structure]


Top address Top address
(Function) (Function)
17 17
+2 +2
(Completion) (Completion)
?
+4 +4
(Data length) (Data length)
L
+6 +6
(Number) (Number)
N N
+8 +8
(Attribute) (Attribute)
M M
+ 10 + 10
(Data) (Data)

[Data length]
L = 1 : Reads bit or byte type parameter or pitch error compensation
value.
2 : Reads word type parameter.
4 : Reads 2 words type parameter.
When the servo parameter all axis is specified
L = 18 : Reads bit or byte type parameter.
28 : Reads word type parameter.
48 : Reads 2 words type parameter.

[Data number]
When the pitch error compensation value
N = 11000 to 11511 : Pitch error compensation value of the 1st (X) axis
N = 12000 to 12511 : Pitch error compensation value of the 2nd (Y) axis
N = 13000 to 13511 : Pitch error compensation value of the 3rd (U) axis
N = 14000 to 14511 : Pitch error compensation value of the 4th (V) axis
N = 15000 to 15511 : Pitch error compensation value of the 5th (Z) axis

1345
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

N = 16000 to 16511 : Pitch error compensation value of the 6th (W) axis
N = 17000 to 17511 : Pitch error compensation value of the 7th (A) axis
N = 18000 to 18511 : Pitch error compensation value of the 8th (E) axis

[Data attribute]
When the servo parameter
M= 0 : Reads the no axis parameter.
1 to n : Reads the specific axis parameter
1 : Reads the all axes parameter.
(Note: n is the axis number.)
If a parameter other than the servo parameters is read, M is set to 0.
[Completion code]
0 : Parameter data has been read normally.
3 : Invalid data is specified as the data number.
4 : Invalid data is specified as the data attribute.
6 : When the data with the parameter number specified for reading
cannot be used if options such as pitch error compensation are not
available, those options are not provided.

1346
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.4 [Description]
WRITING THE Parameter data in the CNC can be written.
PARAMETER There are four types of parameters in the CNC: Bit parameters having
(:LOWSPEED a definite meaning for each bit, byte parameters holding 1byte data, word
parameters holding 2byte data, and double word parameters holding
RESPONSE) 4byte data. Therefore, the length of the written data varies according to
the parameter specified.
Note that bit parameters cannot be written in bit unit. The eighth bits (one
byte) for the parameter number must be written at a time. This means that
when a bit needs to be written, the whole data for the corresponding
parameter number shall be read first, then the target bit in the read data
shall be written.
For axis parameters (servo parameters), data for a specific axis can be
written, or data for all axes can be written at a time.
Some parameters cause a P/S alarm 000 when data is written. (The power
must be turned off before continuing operation.)

[Input data structure] [Output data structure]


Top address Top address
(Function) (Function)
18 18
+2 +2
(Completion) (Completion)
?
+4 +4
(Data length) (Data length)
L L
+6 +6
(Number) (Number)
N N
+8 +8
(Attribute) (Attribute)
M M
+ 10 + 10
(Data) (Data)
Parameter data D

[Data length]
L = 1 : Reads bit or byte type parameter or pitch error compensation
value.
2 : Reads word type parameter.
4 : Reads 2 words type parameter.
When the servo parameter all axis is specified
L = 18 : Writes bit or byte type parameter.
28 : Writes word type parameter.
48 : Writes 2 words type parameter.

[Data number]
When the pitch error compensation value
N = 11000 to 11511 : Pitch error compensation value of the 1st (X) axis

1347
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

N = 12000 to 12511 : Pitch error compensation value of the 2nd (Y) axis
N = 13000 to 13511 : Pitch error compensation value of the 3rd (U) axis
N = 14000 to 14511 : Pitch error compensation value of the 4th (V) axis
N = 15000 to 15511 : Pitch error compensation value of the 5th (Z) axis
N = 16000 to 16511 : Pitch error compensation value of the 6th (W) axis
N = 17000 to 17511 : Pitch error compensation value of the 7th (A) axis
N = 18000 to 18511 : Pitch error compensation value of the 8th (E) axis

[Data attribute]
M= 0 : Writes the no axis parameter.
1 to n : Writes the specific axis parameter
1 : Writes the all axes parameter.
(Note: n is the axis number.)
If a parameter other than the servo parameters is written, M is set to 0.

[Completion code]
0 : Parameter data has been written normally.
2 : Invalid data is specified as the data length.
3 : Invalid data is specified as the data number.
4 : Invalid data is specified as the data attribute.
6 : When the data with the parameter number specified for writing
cannot be used if options such as pitch error compensation are not
available, those options are not provided; or, the system is not in
the parameter writing state.

1348
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

[Types of parameters] In the B908 system, data type of ( ) are used.


No. Length No. Data type No. Data type No. Data type
0000 Bit 0070 Byte 0140 Byte 0210 2W()
0001 Bit 0071 Byte 0141 Byte 0211
0002 Bit 0072 Byte 0142 Byte 0212
0003 Bit 0073 Byte 0143 Byte 0213
0004 Bit 0074 Byte 0144 Byte 0214
0005 Bit 0075 Byte 0145 Byte 0215
0006 Bit 0076 Byte 0146 Word 0216
0007 Bit 0077 Byte 0147 Word 0217
0008 Bit 0078 Byte 0148 Word 0218
0009 Bit 0079 Byte 0149 Word 0219
0010 Bit 0080 Byte 0150 Word 0220
0011 Bit 0081 Byte 0151 Word 0221
0012 Bit 0082 Byte 0152 Word 0222
0013 Bit 0083 Byte 0153 Word 0223
0014 Bit 0084 Byte 0154 Word 0224
0015 Bit 0085 Byte 0155 Word 0225
0016 Bit 0086 Byte 0156 Byte 0226
0017 Bit 0087 Byte 0157 Word 0227
0018 Bit 0088 Byte 0158 Word 0228
0019 Bit 0089 Byte 0159 Word 0229
0020 Bit 0090 Byte 0160 Word 0230
0021 Bit 0091 Byte 0161 Word 0231
0022 Bit 0092 Word 0162 Word 0232
0023 Bit 0093 Word 0163 Word 0233
0024 Bit 0094 Word 0164 2words 0234
0025 Bit 0095 Word 0165 Word 0235
0026 Bit 0096 Word 0166 2words 0236
0027 Bit 0097 Word 0167 Word 0237
0028 Bit 0098 Word 0168 Word 0238
0029 Bit 0099 Word 0169 Word 0239
0030 Bit 0100 Word 0170 Word 0240
0031 Bit 0101 Word 0171 Word 0241
0032 Bit 0102 Word 0172 Word 0242
0033 Bit 0103 Word 0173 Word 0243
0034 Bit 0104 Word 0174 Word 0244
0035 Bit 0105 Word 0175 Word 0245
0036 Bit 0106 Word 0176 Word 0246
0037 Bit 0107 Word 0177 Byte 0247
0038 Bit 0108 Word 0178 2W(Byte) 0248
0039 Bit 0109 Word 0179 2words 0249
0040 Byte 0110 Word 0180 Byte(2W) 0250
0041 Byte 0111 Word 0181 Byte 0251
0042 Word 0112 2words 0182 Byte 0252
0043 Word 0113 Word 0183 Byte 0253
0044 Word 0114 Word 0184 Byte 0254
0045 Word 0115 Word 0185 Byte 0255
0046 Byte 0116 Word 0186 Byte 0256
0047 Word 0117 Word 0187 Byte 0257
0048 Word 0118 Word 0188 Word 0258
0049 Word 0119 Word 0189 Byte 0259
0050 Word 0120 Word 0190 Byte 0260
0051 Word 0121 Word 0191 2words 0261
0052 Word 0122 Word 0192 2words 0262
0053 Word 0123 2words 0193 2words 0263
0054 Word 0124 Byte 0194 2words 0264
0055 Word 0125 Byte 0195 2words 0265
0056 Word 0126 Byte 0196 Word 0266
0057 Word 0127 Byte 0197 2words 0267
0058 Byte() 0128 Byte 0198 Byte 0268
0059 Byte() 0129 Byte 0199 2words 0269
0060 Byte 0130 Byte 0200 Byte 0270
0061 Byte 0131 Byte 0201 word 0271
0062 Byte 0132 Byte 0202 0272
0063 Byte 0133 Byte 0203 0273
0064 Byte 0134 Byte 0204 0274
0065 Byte 0135 Byte 0205 0275
0066 Byte 0136 Byte 0206 0276
0067 Byte 0137 Byte 0207 0277
0068 Word 0138 Byte 0208 0278
0069 2words 0139 Byte 0209 0279

1349
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

No. Length No. Data type No. Data type No. Data type
0280 0350 2words 0620 Byte 0690 Word
0281 0351 Byte 0621 Byte 0691 Word
0282 0352 Byte 0622 Byte 0692 Word
0283 0353 Byte 0623 Byte 0693 Word
0284 0354 Byte 0624 Word 0694 Word
0285 0355 Byte 0625 Word 0695 Word
0286 0356 Byte 0626 Word 0696 Word
0287 0357 Word 0627 Word 0697 Word
0288 0358 0628 Word 0698 Word
0289 0359 0629 Word 0699 Word
0290 0360 Word 0630 Word 0700 Word
0291 0361 2words 0631 Word 0701 Word
0292 0362 2words 0632 2words 0702 Word
0293 0363 2words 0633 2words 0703 Word
0294 0364 2words 0634 2words 0704 Word
0295 0365 2words 0635 2words 0705 Word
0296 0366 2words 0636 2words 0706 Word
0297 0367 2words 0637 2words 0707 Word
0298 0368 2words 0638 2words 0708 Word
0299 0369 2words 0639 2words 0709 Word
0300 Bit 0370 2words 0640 2words 0710 Word
0301 Bit 0371 2words 0641 2words 0711 Word
0302 Bit 0372 2words 0642 2words 0712 Word
0303 Bit 0373 2words 0643 2words 0713 Word
0304 Bit 0374 2words 0644 2words 0714 Word
0305 Bit 0375 2words 0645 2words 0715 Word
0306 Bit 0376 2words 0646 2words 0716 Word
0307 Bit 0377 2words 0647 2words 0717 Word
0308 Bit 0378 2words 0648 Word 0718 Word
0309 Bit 0379 2words 0649 Word 0719 Word
0310 Bit 0380 2words 0650 Word 0720 Word
0311 Bit 0381 2words 0651 Word 0721 Word
0312 Bit 0382 2words 0652 Word 0722 Word
0313 Bit 0383 2words 0653 Word 0723 Word
0314 Bit 0384 2words 0654 Word 0724 Word
0315 Bit 0385 0655 Word 0725 Word
0316 Word 0386 2words 0656 Word 0726 Word
0317 0387 2words 0657 Word 0727 Word
0318 0388 0658 Word 0728 Word
0319 0389 0659 Word 0729 Word
0320 Byte 0390 0660 Word 0730 Word
0321 Byte 0391 0661 Word 0731 Word
0322 Byte 0392 0662 Word 0732 Word
0323 Byte 0393 0663 Word 0733 Word
0324 Byte 0394 0664 Word 0734 Word
0325 Byte 0395 0665 Word 0735 Word
0326 Byte 0396 0666 Word 0736 Word
0327 Byte 0397 0667 Word 0737 Word
0328 Byte 0398 0668 Word 0738 Word
0329 Byte 0399 0669 Word 0739 Word
0330 Word 0600 Bit 0670 Word 0740 Word
0331 Word 0601 Bit 0671 Word 0741 Word
0332 2words 0602 Bit 0672 2words 0742 Word
0333 2words 0603 Bit 0673 2words 0743 Word
0334 Word 0604 Bit 0674 2words 0744 Word
0335 Word 0605 Bit 0675 2words 0745 Word
0336 2words 0606 Bit 0676 2words 0746 Word
0337 2words 0607 Bit 0677 2words 0747 2words
0338 2words 0608 Bit 0678 2words 0748 2words
0339 2words 0609 Bit 0679 2words 0749 2words
0340 2words 0610 Bit 0680 Word 0750 2words
0341 2words 0611 Bit 0681 Word 0751 2words
0342 2words 0612 Bit 0682 Word 0752 2words
0343 Byte 0613 Bit 0683 Word 0753 2words
0344 Word 0614 Bit 0684 Word 0754 2words
0345 Byte 0615 Bit 0685 Word 0755 Word
0346 Word 0616 Byte 0686 Word 0756 Word
0347 Byte 0617 Byte 0687 Word 0757 Word
0348 2words 0618 Byte 0688 Word 0758 2words
0349 2words 0619 Byte 0689 Word 0759 2words

1350
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

No. Length No. Data type No. Data type No. Data type
0760 2words 0810 2words 0860 Word 0910
0761 2words 0811 Byte 0861 Bit 0911
0762 2words 0812 Byte 0862 Bit 0912
0763 2words 0813 Byte 0863 Byte 0913
0764 2words 0814 Byte 0864 Byte 0914
0765 2words 0815 Byte 0865 Byte 0915
0766 2words 0816 Byte 0866 Byte 0916
0767 2words 0817 Byte 0867 Byte 0917
0768 2words 0818 Byte 0868 Byte 0918
0769 2words 0819 Word 0869 Byte 0919
0770 2words 0820 Word 0870 Byte 0920
0771 2words 0821 Word 0871 Byte 0921
0772 2words 0822 Word 0872 Word 0922
0773 2words 0823 Word 0873 Word 0923
0774 2words 0824 Word 0874 Word 0924
0775 2words 0825 Word 0875 Word 0925
0776 2words 0826 Word 0876 Word 0926
0777 2words 0827 Word 0877 Word 0927
0778 2words 0828 Word 0878 Word 0928
0779 2words 0829 Word 0879 Word 0929
0780 2words 0830 Word 0880 Word 0930
0781 2words 0831 Word 0881 Word 0931
0782 2words 0832 Word 0882 Word 0932
0783 2words 0833 Word 0883 Word 0933
0784 2words 0834 Word 0884 Word 0934
0785 2words 0835 0885 Word 0935
0786 2words 0836 Word 0886 Word 0936
0787 2words 0837 Word 0887 Word 0937
0788 2words 0838 Word 0888 Word 0938
0789 2words 0839 Word 0889 Word 0939
0790 2words 0840 Word 0890 Word 0940
0791 2words 0841 Word 0891 Word 0941
0792 2words 0842 Word 0892 Word 0942
0793 2words 0843 Word 0893 Word 0943
0794 2words 0844 Word 0894 Word 0944
0795 2words 0845 Word 0895 Word 0945
0796 2words 0846 Word 0896 Word 0946
0797 2words 0847 Word 0897 Word 0947
0798 2words 0848 Word 0898 Word 0948
0799 2words 0849 Word 0899 (Word) 0949
0800 2words 0850 Word 0900 (Bit)
0801 2words 0851 Word 0901 (Bit)
0802 2words 0852 Word(2W) 0902 (Bit)
0803 2words 0853 Word(2W) 0903
0804 2words 0854 Word(2W) 0904 (Byte)
0805 2words 0855 Word(2W) 0905 (Byte)
0806 2words 0856 Word(2W) 0906
0807 2words 0857 Word(2W) 0907
0808 2words 0858 Word(2W) 0908
0809 2words 0859 Word(2W) 0909

1351
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

E.5
READING SETTING [Data contents]
DATA Setting data on the CNC can be read.

[Input data structure] [Output data structure]


Top address Top address
(Function code) (Function code)
19 19
+2 +2
(Completion code) (Completion code)
?
+4 +4
(Data length) (Data length)
L
+6 +6
(Data number) (Data number)
N Input data
+8 +8
(Data attribute) (Data attribute)

+ 10 + 10
(Data area) (Data area)
Setting data

[Data number]
See the setting data list.
[Completion code]
0 : Read operation was terminated normally.
3 : An incorrect data number was specified.

1352
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.6
WRITING SETTING
DATA
[Data contents]
(LOWSPEED TYPE)
Setting data on the CNC can be written.

[Input data structure] [Output data structure]


Top address Top address
(Function code) (Function code)
20 20
+2 +2
(Completion code) (Completion code)
?
+4 +4
(Data length) (Data length)
L Input data
+6 +6
(Data number) (Data number)
N Input data
+8 +8
(Data attribute) (Data attribute)

+ 10 + 10
(Data area) (Data area)
Setting data Input data

[Data length]
See the setting data list.
[Data number]
See the setting data list.
[Completion code]
0 : Read operation was terminated normally.
2 : An incorrect data length was specified.
3 : An incorrect data number was specified.

1353
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

Setting Data List


Setting data Screen Data number Data length Bit name
X mirror image Handy 1 1 Bit 0
Y mirror image Handy 1 1 Bit 1
Axis switching Handy 1 1 Bit 2
TV check Handy 1 1 Bit 3
Output code Handy 1 1 Bit 4
Input unit Handy 1 1 Bit 5
Parameter writable Handy 1 1 Bit 6
Input unit multiplication by 10 times Handy 1 1 Bit 7
Automatic recovery from power failure Handy 2 1 Bit 3
Automatic poweroff M20/M30 Handy 3 1 Bit 0
Automatic poweroff M00/M10 Handy 3 1 Bit 1
Automatic power backward movement Handy 3 1 Bit 2
alarm
Automatic power disconnection Handy 3 1 Bit 3
Input/output device Handy 4 1
Figure magnification ratio Handy 5 4
Figure rotation angle Handy 6 4
Taper machining mode Taper 15 1
Guide type Taper 16 1 Bit 0
Program surface position Taper 17 4
Workpiece thickness Taper 18 4
Drawing surface position Taper 19 4
Upper guide position Taper 20 4
(Lower guide position) Taper 21 4
(Vertical position U) Taper 22 4
(Vertical position V) Taper 23 4
Enable/disable PWB 2 1
Wire diameter PWB 7 4
Machining groove width PWB 8 4
Workpiece thickness PWB 9 4
Wire deflection PWB 10 4
Effectiveness of concave PWB 11 4
Effectiveness of convex PWB 12 4
Automatic override
Enable/disable PWB 2 1 Bit 5
Differential voltage PWB 13 2
Enable/disable AWF 2 1 Bit 2
Disconnection repair AWF 2 1 Bit 1
Prepared hole of 0.5 AWF 2 1 Bit 6
Sump machining AWF 2 1 Bit 7
Portion to be left uncut AWF 14 1
Power reduction ratio (setting) AWF 24 1
Connection position U1 AWF 26 4
Connection position V1 AWF 27 4
Connection position Z1 AWF 28 4
Number of retries (setting) AWF 40 1
Number of allowable disconnections AWF 41 1
(setting)
Number of retries (current) AWF 42 1
Number of allowable disconnections AWF 43 1
(current)
WIRE REST LIFE 30 2
WIRE CUTTER REST LIFE 31 2
( ) REST LIFE 32 2
( ) REST LIFE 33 2
( ) REST LIFE 34 2
( ) REST LIFE 35 2
( ) REST LIFE 36 2
( ) REST LIFE 37 2

1354
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

Setting Data List


Setting data Screen Data number Data length Bit name
OP. BLOCK SKIP /0 Others 38 1 Bit 0
OP. BLOCK SKIP /1 Others 38 1 Bit 1
OP. BLOCK SKIP /2 Others 38 1 Bit 2
OP. BLOCK SKIP /3 Others 38 1 Bit 3
OP. BLOCK SKIP /4 Others 38 1 Bit 4
OP. BLOCK SKIP /5 Others 38 1 Bit 5
OP. BLOCK SKIP /6 Others 38 1 Bit 6
OP. BLOCK SKIP /7 Others 38 1 Bit 7
OP. BLOCK SKIP /8 Others 39 1 Bit 0
OP. BLOCK SKIP /9 Others 39 1 Bit 1
Number or tries AWF 40 1
Number of retries AWF 41 1
Number or tries AWF 42 1
Number of retries AWF 43 1
Program number Graphic 44 2
(for machining distance calculation)

1355
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

E.7 [Description]
READING THE CNC When the CNC is placed in the alarm status, the alarm status data can be
ALARM STATUS read.

[Input data structure] [Output data structure]


Top address Top address
(Function) (Function)
23 23
+2 +2
(Completion) (Completion)
0
+4 +4
(Data length) (Data length)
2
+6 +6
(Number) (Number)

+8 +8
(Attribute) (Attribute)

+ 10 + 10 First byte
(Data area) (Data area)
+ 11 Alarm status
Second byte
+ 12

[Contents of data]
(1) Alarm status data in first byte.
#7 #6 #5 #4 #3 #2 #1 #0
EOR OTM OTS OH SV OTH PS

PS : P/S alarm
OTH : Over travel alarm
SV : Servo alarm
OH : Overheat alarm
OTS : First stroke limit alarm
OTM : Second stroke limit alarm
EOR : Edit alarm
(2) Alarm status data in second byte.
#7 #6 #5 #4 #3 #2 #1 #0
APCER

APCER : Absolute pulco alarm

[Completion codes]
0 : This alarm status in the CNC has been read normally.

1356
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.8 [Description]
READING MODEL Modal information in the CNC can be read.
DATA (1) Format and types of modal data for the G function
Data with a specified identification code is read and stored in the data
area. Whether the data is located in the block specified with the data
attribute can be determined with the most significant bit.

7 6 5 4 3 2 1 0

Code in a group : 1 byte

0 : Not specified in the current block


1 : Specified in the current block

Identification code Data type Data Identification code Data type Data
0 G04 0 5 G94 0
G19 1 G95 1
G28 5 6 G20 0
G30 7 G21 1
G92 14
7 G40 0
G31 15
G41 1
G70 16
G42 2
G71 17
G72 18 8 G50 0
G73 19 G51 1
G74 20 G52 2
G75 21 9 G60 0
G76 22 G61 1
G77 23 G62 2
G78 24 G63 3
G79 25 10 G48 1
G49 0
1 G00 0
G01 1 11 G65 26
G02 2 G66 0
G03 3 G67 1
2 G17 0
3 G90 0
G91 1
4 G22 1
G23 0

1357
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

(2) Format and types of modal data for other than the G function

Data : 4 bytes

Flag
: 1 byte

7 6 5 4 3 2 1 0


1 byte

Number of input digits


0 : Positive
1 : Negative

0 : Not specified in the current block


1 : Specified in the current block

Identification code Specified address Meaning of value


100 B
101 D
102 E Offset number
103 F
104 H Feedrate
105 L
106 M
107 S
108 T Tapper data
109 R
110 P
111 Q

[Input data structure]


Top address
(Function)
32
+2
(Completion)

+4
(Data length)

+6
(Number)
N
+8
(Attribute)
M
+ 10
(Data area)

1358
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

[Output data structure]


Top address
(Function code)
32
+2
(Completion code)
?
+4
(Data length)
L
+6
(Data number)
Input data
+8
(Data attribute)
Input data
+ 10
(Data area) Modal data of oth- Modal data of Modal data of
Modal data of er than ID code 0 ID code 100
G functions G functions
+ 12
Modal data of
ID code 1

+ 14
Flag part of Modal data of Flag part of data
modal data ID code 2 of ID code 100

+ 16
X X X

Modal data of Modal data of


ID code 16 ID code 111

+ 44

Flag part of data


of ID code 111

+ 78

[Data length]
L= 2 : G function
2*16 : All data of G functions
6 : Other than G functions
6*12 : All data of other than G functions
[Data number]
N = 0 and up: See each data list.
1 : All data of G functions
2 : All data of other than G functions
[Data attribute]
M = 0 : Current block
1 : Next block
2 : Block after the next block

1359
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

[Completion code]
1 : The modal data read command could not be executed. This
means that, because the modal data was being updated on
the CNC, the command could not be executed.
0 : Modal data read operation terminated normally.
3 : An incorrect data number was specified.
4 : An incorrect data attribute was specified.

1360
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

E.9
READING [Data contents]
MACHINING The distance (machining distance) from the machining start point to the
DISTANCES current point, and the distance (whole distance) from the machining start
point to the point where M02 or M30 is specified can be read.

[Input data structure] [Output data structure]


Top address Top address
(Function code) (Function code)
182 182
+2 +2
(Completion code) (Completion code)
?
+4 +4
(Data length) (Data length)
4
+6 +6
(Data number) (Data number)
N Input data
+8 +8
(Data attribute) (Data attribute)

+ 10 + 10
(Data area) (Data area)
Machining distance

+ 14

[Data number]
N= 0 : Machining distance
N= 1 : Whole length obtained with the dry run function
N= 2 : Whole length obtained by drawing
N= 3 : Whole length obtained with the machining distance
calculation function
[Data unit]
Metric input : 103 [mm]
(When the increment system is 1/10: 104 [mm])
Inch input : 105 [inch]
[Completion code]
1 : Data could not be read. This means that, because the data was
being updated on the CNC, the command could not be executed.
0 : Data read operation terminated normally.
3 : An incorrect data number was specified.

1361
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

E.10 [Description]
READING THE The measured point that are get by positioning can be read. Also, the slit
MEASURED POINT width by slitting and the hole diameter by centering can be read.

[Input data structure]


Top address
(Function)
185
+2
(Completion)

+4
(Length) Reads Reads slit width
measured point of hole diameter
+6
(Number) Point number 0
N
+8
(Attribute) 0 1
M
+ 10
(Data area)

[Output data structure]


Top address
(Function)
185
+2
(Completion) Reads Reads slit width
? measured point of hole diameter
+4
(Length) 10 4
L
+6
(Number)
Point number 0
N
+8
(Attribute) 0 1
M
+ 10
Type Slit width of hole
(Data area)
diameter
+ 12

Machine
+ 14 coordinate of
X axis

+ 16

Machine
+ 18 coordinate of
Y axis

+ 20

1362
E. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16W)

[Data unit]
Metric system input : 103 [mm]
(In case the incremental system is 1/10, output
data unit is 104 [mm].)
Inch system input : 105 [inch]

[Completion codes]
0 : The measured point has been read normally.
3 : Invalid data is specified as data number.
4 : Invalid data is specified as data attribute.

1363
E. WINDOW FUNCTION DESCRIPTION
(FS16W) APPENDIX B61863E/14

E.11
WRITING THE
MEASURED POINT
[Description]
(:LOWSPEED
The measured point that are get by positioning can be written. Also, the
RESPONSE) slit width by slitting and the hole diameter by centering can be written.

[Input data structure] [Output data structure]


Top address Top address
(Function) (Function)
186 186
+2 +2
(Completion) (Completion)
?
+4 +4
(Length) (Length)
10 10
+6 +6
(Number) (Number)
Point number N
+8 +8
(Attribute) (Attribute)
0 0
+ 10 + 10
(Data area) (Data area)
Type
+ 12 + 12
Machine
coordinate of X axis
+ 14 + 14

+ 16 + 16
Machine
coordinate of Y axis
+ 18 + 18

+ 20 + 20

[Data unit]
Metric system input : 103 [mm]
(In case the incremental system is 1/10, output
data unit is 104 [mm].)
Inch system input : 105 [inch]

[Completion codes]
0 : The measured point has been written normally.
3 : Invalid data is specified as data number.
4 : Invalid data is specified as data attribute.

1364
F. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16PA)

F WINDOW FUNCTION DESCRIPTION (FS16PA)

1365
F. WINDOW FUNCTION DESCRIPTION
(FS16PA) APPENDIX B61863E/14

F.1 [Description]
READING OF TOOL Various Tool setting data recorded in the CNC can be read.
SETTING DATA
[Input data structure]
Top address + 0
(Function code)
188

2
(Completion code)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data Number)
N
(See 1.1)

8
(Data attribute)
M
(See 1.1)

10
(Data area)

(Need not be set)

[Completion codes]
0: The tool setting data has been read normally.
3 : The data number specified for reading is invalid.
4 : There are mistakes in the data attribute that specifies the type of
the tool setting data to be read.
6 : For the tool setting data specified for reading, an additional option
(graphic or multitool control) is required, but it is missing.

1366
F. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16PA)

[Output data structure]


Top address + 0
(Function code)
188

2
(Completion code)
?
(See the explanation of codes)

4
(Data length)
?
(See 1.1)

6
(Data Number)
N
(N : Input data)

8
(Data attribute)
M
(M : Input data)

10
(Data area)
?
(See 1.1)

X X

48

1367
F. WINDOW FUNCTION DESCRIPTION
(FS16PA) APPENDIX B61863E/14

F.1.1 Data number, data attribute, data length and data area of various tool
Data Number, setting data are as follows.
Data Attribute,
Data Length, Data Area
Various tool setting data Data number (N) Data attribute (M) Data length Data area
Used tool number 0 2 bytes Binary
1 to 136
Number of turret indexing 1 2 bytes Binary
1 to 136
Tool number of reference point 2 2 bytes Binary
0
1 to 136
Feed amount per revolution of 3 4 bytes Binary
turret 1 to 99999999
Total punch count 4 8 bytes Binary
1 to 99999999
Tool number 0 2 bytes Binary
1 to 9999
Punch count 1 4 bytes Binary
1 to 99999999
Tool position compensation of X 2 4 bytes Binary
99999999
Tool position compensation of Y 3 4 bytes Binary
99999999
Machine position of tool 4 4 bytes Binary
Number of tool 99999999
Tool number for tool change setting data 5 2 bytes Binary
1 to 136
1 to 136
(Not used) 6 4 bytes
Tool shape (C) for graphic 7 2 bytes Binary
High byte=0 0 to 4
Tool shape (I) for graphic 8 4 bytes Binary
0 to 999999
Tool shape (J) for graphic 9 4 bytes Binary
0 to 999999
Tool shape (K) for graphic 10 4 bytes Binary
0 to 360000
Tool number for multitool 0 2 bytes Binary
High byte=0 0 to 99
Tool angle for multitool 1 4 bytes Binary
360000
Tool position compensation of Y 2 4 bytes Binary
Number of 99999999
Multitool setting
Tool shape (C) for multitool 3 2 bytes Binary
data +200
High byte=0 0 to 4
Tool shape (I) for multitool 201 to 264 4 4 bytes Binary
0 to 999999
Tool shape (J) for multitool 5 4 bytes Binary
0 to 999999
Tool shape (K) for multitool 6 4 bytes Binary
0 to 360000

1368
F. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16PA)

data unit
Machine Input of ISA Input of ISB

Tool position mm 0. 01 0. 001


compensation inch 0. 001 0. 0001

Input unit Input of ISA Input of ISB

Tool shape and mm 0. 01 0. 001


angle for graphic inch 0. 001 0. 0001
Tool angle for deg 0. 01 0. 001
multitool

1369
F. WINDOW FUNCTION DESCRIPTION
(FS16PA) APPENDIX B61863E/14

F.2 [Description]
WRITING OF TOOL The various tool setting data can be directly written into the CNC.
SETTING DATA
(LOWSPEED
RESPONSE) [Input data structure]
Top address + 0
(Function code)
189

2
(Completion code)

(Need not be set)

4
(Data length)
?
(See 1.1)

6
(Data Number)
N
(See 1.1)

8
(Data attribute)
M
(See 1.1)

10
(Data)
?
(See 1.1)

[Completion code]
0 : The tool setting data has been written normally.
2 : The data length specified for writing is invalid.
3 : The data number specified for writing is invalid.
4 : The data attribute specified for writing is invalid.
5 : The data specified for writing is invalid.
6 : The additional option (multitool control or graphic) is required
but it is missing.

1370
F. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16PA)

[Output data structure]


Top address + 0
(Function code)
189

2
(Completion code)
?
(See the explanation of codes)

4
(Data length)
?
(See F.1)

6
(Data Number)
N
(N : Input data)

8
(Data attribute)
M
(M : Input data)

10
(Data area)
?
(See F.1)

X X

48

NOTE
See Sec. F. 1 for data unit.

1371
F. WINDOW FUNCTION DESCRIPTION
(FS16PA) APPENDIX B61863E/14

F.3
READING TOOL [Description]
SETTING DATA BY Setting data for a tool (such as registration order, tool punch count, and
SPECIFYING TOOL tool shape) can be read by specifying the tool number.
NUMBER
[Input data structure]
Top address + 0
(Function code)
141

2
(Completion)

(Need not be set)

4
(Data length)

(Need not be set)

6
(Data number)
N
(N=Tool number)

10
(Data attribute)
M
(See F.1)

12
(Data area)

(Need not be set)

NOTE
1 The area for specifying the data number consists of four
bytes.
2 As the data attribute, specify the type of the tool setting data
to be read, in the same way as for function code 188. If 0
is specified as the data attribute, the registration order of the
tool is read.

1372
F. WINDOW FUNCTION DESCRIPTION
B61863E/14 APPENDIX (FS16PA)

[Completion code]
0: The tool setting data has been read normally.
3: The specified data number is invalid.
4: The specified data attribute is invalid.
6: For the tool setting data specified for reading, an additional option
(graphic or multitool control) is required, but it is missing.

[Output data structure]


Top address + 0
(Function code)
141

2
(Completion code)
?
(See the explanation above)

4
(Data length)
?
(See F.1)

6
(Data number)
N
(N: Input data)

10
(Data attribute)
M
(M: Input data)

12
(Data area)
?
(See F.1)

X
A X
A

48

1373
F. WINDOW FUNCTION DESCRIPTION
(FS16PA) APPENDIX B61863E/14

F.4 The FS16PA supports the following window functions, described in


Appendix B of this manual.
OTHER WINDOW
FUNCTIONS
Number Function
code
1 Reading CNC system information 0
2 Reading a tool offset 13
3 Writing a tool offset :lowspeed response 14
4 Reading a workpiece origin offset 15
5 Writing a workpiece origin offset :lowspeed response 16
6 Reading a parameter :lowspeed response 17
7 Writing a parameter :lowspeed response 18
8 Reading setting data :lowspeed response 19
9 Writing setting data :lowspeed response 20
10 Reading a custom macro variable :lowspeed response 21
11 Writing a custom macro variable :lowspeed response 22
12 Reading the CNC alarm state 23
13 Reading the current program number 24
14 Reading the current sequence number 25
15 Reading an actual velocity for a controlled axis 26
16 Reading an absolute position on a controlled axis 27
17 Reading a machine position on a controlled axis 28
18 Reading a skip position on a controlled axis 29
19 Reading a servo delay amount on a controlled axis 30
20 Reading an acceleration/deceleration delay amount on a controlled axis 31
21 Reading modal data 32
22 Reading diagnostic data :lowspeed response 33
38 Reading clock data (date and time) 151
41 Reading a parameter 154
42 Reading setting data 155
43 Reading diagnostic data 156
44 Reading a character string of the CNC program being executed in the buffer 157
45 Reading the relative position on a controlled axis 74
46 Reading the remaining travel on a controlled axis 75
47 Reading CNC status information 76
48 Reading an operator message 83

1374
G. SIGNAL ADDRESS CONVERSION
(FROM THE PMCMODEL L/M TO
B61863E/14 APPENDIX THE PMCMODEL SB/SC)

G SIGNAL ADDRESS CONVERSION (FROM THE


PMCMODEL L/M TO THE PMCMODEL SB/SC)

1375
G. SIGNAL ADDRESS CONVERSION
(FROM THE PMCMODEL L/M TO
THE PMCMODEL SB/SC) APPENDIX B61863E/14

G.1 DI/DO signals used in the PMCMODEL L/M can be converted to


signals for the PMCMODEL SB/SC using the FANUC LADDER
GENERAL program for the PMCMODEL SB/SC.

G.2 The DI/DO signals used between the NC unit and the PMC correspond
to word addresses consisting of addresses and values. Word addresses of
FUNCTION bit type are converted. The program is not logically converted.
The conversion is performed under the following conditions.
(1) A word address of bit type used in a basic instruction is to be
converted.
(2) A word address of byte type used in a functional instruction is not
converted.
(3) Word addresses used in the standard FANUC Series 0T/M are
converted to those used in the standard FANUC Series 16T/M. If
a value in a word address is 1000.0 or more, the address is not
converted.
(4) When the same signal name is used in the FANUC Series 0 and 16,
and the addresses corresponding to the signal in the Series 0 and 16
have onetoone relationship, the word address is converted. For
details, see the signal conversion table.

G.3 (1) Load the FANUC LADDER program for the PMCSB/SC.
CONVERSION (2) Press the R0 key to display the programmer menu screen.
(3) Press the F2 key. Enter 2 and press the <NL> key. then the following
message appears on the screen. Insert a data floppy for the
PMCSB/SC. Select the name of the file corresponding to the
conversion from Table G.3 and enter it.
SET FD & KEYIN OK, KILL OR NO
FD0 = OK<DRIVE> <@NAME OR :NUMBER>
FD0 =

Table G.3 File Name in the Data Floppy for the PMCRB/RC

File name
FS0T FS16T COMV.FS0T
FS0M FS16M COMV.FS0M

(4) Read a source ladder program created with FANUC LADDER for
the PMCL/M from the floppy in the same way as in Item 3.
If an address not listed in the signal conversion table is used in the
ladder program file, an error occurs. In this case, enter E, then press
the <NL> key to return to the programmer menu screen.
PART= E <NL>
(5) Entering 9 and pressing the <NL> key on the programmer menu
screen changes the screen. The following message appears at the
lower left corner of the screen. Enter 2, then press the <NL> key to
delete the symbol data.
KEYIN 1, 2, 3, 4, 5 OR 6 OR NO
CLEAR/KEEP=

1376
G. SIGNAL ADDRESS CONVERSION
(FROM THE PMCMODEL L/M TO
B61863E/14 APPENDIX THE PMCMODEL SB/SC)

G.4 The above operation terminates the conversion. Check the converted
program. If an error occurs in the conversion, modify the program.
MODIFYING THE
CONVERTED Enter 1 on the programmer menu to change the screen to the screen for
editing a sequence program. Editing operation is the same as usual.
SEQUENCE
PROGRAM NOTE
Some addresses not converted have no error indication.
After modifying the program, check that all addresses are
correct according to the signal conversion table and the
connecting manual.

G.4.1 (1) When the Series 0 and 16 differ in the number of parameters used in
a functional instruction
Modification Procedure
Because the Series 0 and 16 differ in the numbers of parameters used
for TMR (timer), TMRB (timer), and CTR (counter), errors are
indicated at the parameters. Check the program, then delete the
parameter. Set the timer and counter again.
(2) When an address not used in functional instructions is specified
When an address used in the ladder program for the Series 0 is not
defined in the Series 16, the messages (NO PARAMETER) and
#PARAM.ERROR# appear as follows. Set the parameter again and
delete the latter message.
Example
00001 RD XXX.X
00002 SUB 8
00003 XXXX
00004 XXXX
00005 XXXX
00006 (NO PARAMETER) . . Set the parameter again.
00007 #PARAM.ERR# . . . . . Delete the message. This
message may not appear.
(XXX.X and XXXX are addresses and values.)
(3) Deleting SUB48 (END3) (In the PMCSB)
If SUB48 (END3) is specified in the PMCSB, an error occurs
because the PMCSB is not provided with SUB48 (END3). When
this error occurs, delete thirdlevel programs, or change the
thirdlevel programs to secondlevel programs and delete SUB48.
(4) Address conversion for signals not listed on the signal conversion
table Modify the address for a signal by referring to the connection
manual.

1377
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
FS18, FS21, OR Power Mate APPENDIX B61863E/14

H CONNECTING THE OPERATORS PANEL FOR FS 0 WITH


FS16, FS18, FS21, OR Power Mate

1378
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
B61863E/14 APPENDIX FS18, FS21, OR Power Mate

H.1 The Series 0 operators panel consists of key switches, LEDs, a rotary
switch, and so on. Because the states of key switches and lamps are coded,
GENERAL the number of the signal lines required for connecting the operators panel
with the CNC may not be the same as the number of actual switches. PMC
management software automatically codes the states of the key switches
and lamps and transmits data.
Therefore, simple bit images of switches and LEDs must only be
manipulated with the PMC ladder program.

I/O unit
CNC (Series 16 or 18) I/O card

Bit image Input Coding


Keyboard
Rk and on Xn and on
PMC
management
software
Bit image Output Coding
LED
Rl and on Ym and on

Protect key
Input Contact Emergency stop
X* and on button
Override rotary
switch
etc.

Series 0 operators manual

G* and Input
after (X) X* and on
PMC ladder
CNC Interface with
program
software other machines
(of the user)
Output
F* and on Y* and
after

Fig. H.1 (a) Connection between the CNC and the operators panel

1379
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
FS18, FS21, OR Power Mate APPENDIX B61863E/14

The operators panel is made up of the following keys, LEDs, etc.


D Key switch (Seat key)
D 42 keys (0TC)
D 46 keys (0MC)
D LEDs (red) .......................Prepared for all key switches
D Override rotary switch ..... 4 bits
D Emergency stop button .... 1 bit
D Program protect key ........ 1 bit

(Coordinate)

Fig. H.1 (b) Front view of operators panel for 0TC

(Coordinate)

Fig. H.1 (c) Front view of operators panel for 0MC

1380
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
B61863E/14 APPENDIX FS18, FS21, OR Power Mate

(Coordinate)

Fig. H.1 (d) External view of operators panel for 9 CRT/MDI with fullkeyboard (0TC)

(Coordinate)

Fig. H.1 (e) External view of operators panel for 9 CRT/MDI with fullkeyboard (0MC)

1381
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
FS18, FS21, OR Power Mate APPENDIX B61863E/14

H.2
CONNECTION

H.2.1
Connecting the I/O Unit

CNC (Series 16 or 18)

MAIN CPU
I/O unit Series 0 operators panel

JD1A
JD1B DI M1A
(I/O Link)
module

CP32

PSU DO M2A
CP6 JD1A module

24 VDC Another I/O unit

DI module : +24 V common, 20 ms


Example) AID32A1

DO module : 0 V common
Example) AOD32A1

H.2.2
Connecting the I/O CNC (Series 16 or 18)
To another I/O unit
Card MAIN CPU

JD1A Interface with other machines


(I/O Link)

Series 0 operators panel

I/O card
DI M1A
connector

DO
M2A
connector

1382
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
B61863E/14 APPENDIX FS18, FS21, OR Power Mate

H.3
SIGNALS FOR
CONNECTING THE
OPERATORS PANEL

H.3.1 This signal is used for the fixed address directly monitored by the CNC.
Emergency Stop Signal For connecting the signal, refer to the description of the interface between
(*ESP) the CNC and the PMC in the Series 16 or 18 Connection Manual.

H.3.2 Their key switch contact signals are directly input to the PMC. Handle
Override Signals (*OV1 them with the PMC ladder program.
to *OV8) and Program For connecting these signals, refer to the description of the interface
Protect Key Signal between the CNC and the PMC in the Series 16 or 18 Connection
(KEY) Manual.

H.3.3 The key switch signals are coded by the PMC management software, and
input to the area indicated by address R in the form of to the bit image.
Key Switch Signals
(Xn, Xn+2) Whether necessary keys are already pressed can be checked by the bit
image of the key switches using the user PMC ladder program. (See
Tables H.3.4 (a), H.3.4 (b), and H.3.4 (c))
While a key is pressed, the bit corresponding to the key is 1.
Two keys can be pressed at the same time. Create a user PMC program
so that it does not require pressing more than two keys at a time. If more
than two keys are pressed simultaneously, the relevant data is not entered
correctly.
A maximum of 60 ms is required before the corresponding bit is set to 1
or 0 after a key is pressed (released).
Key switch signal addresses (Xn to Xn+2: Table H.3.4 (a)) and their bit
image addresses (Rk to Rk+7: Tables H.3.4 (b) and H.3.4 (c)) can be
defined using fixed addresses or unused addresses as desired. (In Series
0, the key switch signal addresses are fixed to X20 and after. The bit
image addresses are fixed to F292 and after.)

1383
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
FS18, FS21, OR Power Mate APPENDIX B61863E/14

H.3.4 Specify the LED signals at PMC address R using the user PMC ladder
LED Signals (Ym) program in the form of a bit image. PMC management software changes
the bit image LED signals to the coded output signals. (See Tables H.3.4
(a), H.3.4 (b), and H.3.4 (c))
While 1 is written in a LED bit image, the relevant LED automatically
goes on. When 0 is written in the LED bit image, the relevant LED goes
off. All LEDs are off before the power is turned on.
A maximum of 200 ms is required before the LED goes on or off after 1
or 0 is written in a bit image in the PMC.
LED signal address (Ym: Table H.3.4 (a)) and the bit image addresses (Rl
to Rl+7: Tables H.3.4 (b), and H.3.4 (c)) can be defined using fixed
addresses or unused addresses as desired. (In Series 0, the LED signal
address is fixed to Y51. The bit image addresses are fixed to G242 and
after.)

Table H.3.4 (a) Key switch and LED signal addresses


#7 #6 #5 #4 #3 #2 #1 #0
Xn KD7 KD6 KD5 KD4 KD3 KD2 KD1 KD0

Xn+1

Xn+2 KST KA3 KA2 KA1 KA0

Ym LD7 LD6 LD5 LD4 LD3 LD2 LD1 LD0

Table H.3.4 (b) Bit Image addresses of key switch and LED signals
(for the small operators panel)
#7 #6 #5 #4 #3 #2 #1 #0
KEY/LED F3 F2 F1 D1 C1 B1 A1

Rk/Rl F4 D2 C2 B2 A2

Rk+1/Rl+1 D4 D3 C4 C3 B4 B3 A4 A3

Rk+2/Rl+2 F6 F5 D5 C5 B5 A5

Rk+3/Rl+3 F8 D6 C6 B6 A6

Rk+4/Rl+4 D8 C8 B8 A8 A7

Rk+5/Rl+5 F9 D9 C9 B9 A9

Rk+6/Rl+6 F10 D10 C10 B10 A10

1384
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
B61863E/14 APPENDIX FS18, FS21, OR Power Mate

Table H.3.4 (c) Bit image addresses of key switch and LED signals
(for the operators panel with the full keyboard)
#7 #6 #5 #4 #3 #2 #1 #0
KEY/LED E1 C1 A1 E6 D6 C6 B6 A6

Rk/Rl E2 C2 A2 E7 D7 C7 B7 A7

Rk+1/Rl+1 E3 C3 A3 E8 D8 C8 B8 A8

Rk+2/Rl+2 E5 C4 A4 E9 D9 C9 B9 A9

Rk+3/Rl+3 D2 C5 A5 E10 D10 C10 B10 A10

Rk+4/Rl+4 D4 D5 B2 E11 D11 C11 B11 A11

Rk+5/Rl+5 D1 B1 B4 E12 D12 C12 B12 A12

Rk+6/Rl+6 D3 B3 B5 E13 D13 C13 B13 A13

1385
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
FS18, FS21, OR Power Mate APPENDIX B61863E/14

H.4 The following section describes how to specify key switch and LED
signal addresses and the bit image addresses.
SPECIFYING
ADDRESSES

H.4.1
Parameter Menu
KEY IN ONE OF THE FOLLOWING NO.S WHICH YOU WANT TO SET PARA.S

NO. ITEMS CURRENT PARAMETERS

01 (UNUSED) ;
02 COUNTER DATA TYPE ; BINARY

03 OPERATOR PANEL ; YES

KEY/LED ADDRESS ; X0000/Y0000

KEY/LED BIT IMAGE ADRS. ; R0900/R0910

04 PMC TYPE ; PMCRB


05 (UNUSED) ;

06 (UNUSED) ;

07 (UNUSED) ;

08 (UNUSED) ;

09 IGNORE DIVIDED CODE ; NO


10 (UNUSED) ;

00 NOTHING TO SET ;

; ROM WRITER = FA WRITER

NO. =

H.4.2 1) Select 3 from the parameter menu. Then, the following message is
Procedure displayed:
EXAMPLE 0:NO, 1:YES
OP.PANEL=_

2) Select 1(:YES). Then, the following message is displayed:


SET KEY/LED ADDRESS(KEY ADRS., LED ADRS.)
ADDR=_

3) Specify a key or LED address (X or Y). For example, to specify a


key switch address as X0 and LED address as Y0, enter X0,Y0 and
press the [NL] key ([NL]: New line key). The following message is
then displayed:
SET KEY/LED BIT IMAGE ADDRESS(KEY ADRS., LED ADRS.)
ADDR=_

1386
H. CONNECTING THE OPERATORS
PANEL FOR FS 0 WITH FS16,
B61863E/14 APPENDIX FS18, FS21, OR Power Mate

4) Specify bit image addresses. For example, to specify R900 and


R910, enter R900,R910 and press the [NL] key.
Then, the current display returns to the original parameter menu, and
the following message appears:

: : :
03 OPERATOR PANEL ; YES

KEY/LED ADDRESS ; X0000/Y0000


KEY/LED BIT IMAGE ADRS. ; R0900/R0910
: : :

CAUTION
1 After the above procedure, the addresses in Tables 3.1,
3.2A, and 3.2B are defined as the following PMC
addresses:
Xn X0000 Rk / Rl R0900/R0910
Xn+1 X0001 Rk+1 / Rl+1R0901/R0911
Xn+2 X0002 Rk+2 / Rl+2R0902/R0912
Rk+3 / Rl+3R0903/R0913
Ym Y0000 Rk+4 / Rl+4R0904/R0914
Rk+5 / Rl+5R0905/R0915
Rk+6 / Rl+6R0906/R0916
Rk+7 / Rl+7R0907/R0917
2 Since the PMC addresses for the I/O card are already fixed,
specify the signals to be used at the fixed addresses.

Examples To use X1000, X1001, X1002, and Y1000 for key switches and LEDs,
enter the following:
SET KEY/LED ADDRESS(KEY ADRS., LED ADRS.)
ADDR= X1000,Y1000 [NL]

1387
I. EDITING FOR Power MateMODEL D
(PMCPA1/PA3) APPENDIX B61863E/14

I EDITING FOR Power MateMODEL D (PMCPA1/PA3)

1388
I. EDITING FOR Power MateMODEL D
B61863E/14 APPENDIX (PMCPA1/PA3)

I.1 Ladder diagram editing function for FANUC PMCMODEL PA1/PA3


has high compatibility in a basic specification between ladder diagram
OUTLINE editing function for FANUC PMCMODEL SA1/SA2.
Following abbreviations are used in this chapter.

CNC Model Product/Card Name Abbr.


FANUC Power MateMODEL D FANUC PMCMODEL PA1 PMCPA1
FANUC PMCMODEL PA3 PMCPA3
Ladder diagram editing Editing card
memory card
FANUC Series 18 FANUC PMCMODEL SA1 PMCSA1
FANUC PMCMODEL SA2 PMCSA2

I.2 Editing card described herein apply to the following software or later.
COMPATIBILITY CNC
WITH CNC BASIC Version 08(H) or later of Power MateMODEL D basic software
8830 Series.
SOFTWARE
PMC
Version 04(D) or later of PMCPA1/PA3 control software 4075
Series.

1389
I. EDITING FOR Power MateMODEL D
(PMCPA1/PA3) APPENDIX B61863E/14

I.3 This function is used to set PMC system parameters and also generate and
execute sequence programs by using soft keys a on the CRT/MDI unit or
PMC PROGRAMMER PDP/MDI unit. You can not use following function because FANUC
(CRT/MDI OR Power MateMODEL D does not use ROM for sequence program.
PDP/MDI) [LADDER Sequence Program Copy Function
EDITING FUNCTION] Writing, Reading, and Verification of the Sequence Program and
PMC Parameter Data to/from/with ROM.

I.3.1 The units required for generating a sequence program and connection
methods are described below.
Component Units and
Connections

1390
I. EDITING FOR Power MateMODEL D
B61863E/14 APPENDIX (PMCPA1/PA3)

I.3.1.1 (1) Editing card


Component units This is used for editing sequence program.
If this card is inserted in CNC at the time of its poweron, PMC
displays the programmer menu.
When you want to put on and take off, you must turn off the CNC
power.

CAUTION
Please do not release the write protect switch of editing card
for preventing a mistake deleting.

WRITE PROTECT

Editing Card
(A02B0166K701#4076)

Fig. I.3.1.1

(2) CRT/MDI unit, PDP/MDI unit


CRT/MDI unit or PDP/MDI unit are necessary when you generate
or edit sequence program using editing card.
CRT/MDI unit (A02B0166C001)
PDP/MDI unit (A02B0166C010, A02B0166C011)

1391
I. EDITING FOR Power MateMODEL D
(PMCPA1/PA3) APPENDIX B61863E/14

I.3.1.2 Feed the editing card into connector CNMC of the CNC.
Connection of When you want to put on and take off, you must turn off the CNC power.
components (Refer to the fig. I.3.1.2)

Fig. I.3.1.2

I.3.1.3 Please set bit 1 in K17 of keep relay area for PMC parameters.
#7 #6 #5 #4 #3 #2 #1 #0
Parameter
K17 PRGRAM

PRGRAM 0: The programmer function is disabled.


(The programmer menu is not displayed.)
1: The programmer function is enabled.
(The programmer menu is displayed.)

1392
I. EDITING FOR Power MateMODEL D
B61863E/14 APPENDIX (PMCPA1/PA3)

I.3.2 FANUC Power MateMODEL D can set only COUNTER DATA TYPE.
Specification and The meaning of this parameter is same as PMCSA1/SA2.
Display of System
Parameters (SYSPRM)
PMC SYSTEM PARAMETER
COUNTER DATA TYPE = BINARY/BCD

[BINARY] [ BCD ] [ ] [ ] [ ]

Fig. I.3.2 PMCPA1 or PA3 System Parameter Screen

I.3.3 When the following condition is satisfied, the CONDNS key will be used
in FANUC Power MateMODEL D.
Condense
Some unused area remain by repeating the addition or the deletion
of the symbol/comment and the message in the memory.
Ladder might be able to be made more by compressing the unused
area by pushing [CONDNS] key when the memory is insufficient
while ladder is added.
[Example: When you want to expand ladder area by deleting
symbol/comment data at the memory status Fig.I.3.3 (a)]
(1) Delete symbol data(0.2KB).
(2) Push [CONDNS] key.
(3) The memory status becomes as Fig.I.3.3 (c) and LADDER can be
edited more.

NOTE
1 Sequence program area in Fig. I.3.3 (a) (c) is 64KB.
2 The underlined memory in Fig. I.3.3 (a) (c) is the same as
the memory display of the TITLE screen.
3 The symbol/comment area in Fig. I.3.3 (a) is 20KB (Unused
area 0.9KB is contained.)
4 In case of deleting message and expending another area,
it is as same as this example.

1393
I. EDITING FOR Power MateMODEL D
(PMCPA1/PA3) APPENDIX B61863E/14

Message Message Message


10.0KB 10.0KB 10.0KB

Symbol/Comment Symbol/Comment Executed Symbol/Comment


19.1KB 18.9KB Condense 18.9KB
Symbol/
Comment
0.2KB 19.0KB
Delete
20.0KB (Unused area 1.1KB) (Unused area 0.1KB)

(Unused area 0.9KB)

Ladder Ladder Ladder


34.0KB 34.0KB 34.0KB

(Unused area 1.0KB)

Fig. I.3.3 (a) Fig. I.3.3 (b) Fig. I.3.3 (c)

1394
I. EDITING FOR Power MateMODEL D
B61863E/14 APPENDIX (PMCPA1/PA3)

I.4
SYSTEM DIAGRAM
OF SOFT KEY

PCLAD PCDGN PCPRM

NEXT

STOP EDIT I/O SYSPRM

RETURN

TITLE LADDER SYMBOL MESAGE

NEXT

MODULE CROSS CLEAR

Fig. I.4 (a)

TITLE LADDER SYMBOL MESAGE

FUNCTN

RETURN NEXT

COMAND

INSNET DELNET INSERT ADRESS SEARCH

NEXT

COPY MOVE CHANGE

Fig. I.4 (b)

1395
J. APPLICABLE FANUC LADDER EDITIONS APPENDIX B61863E/14

J APPLICABLE FANUC LADDER EDITIONS

The following tables list the editions of offline programs required to


program each PMC model.

1396
B61863E/14 APPENDIX J. APPLICABLE FANUC LADDER EDITIONS

J.1 Body of FANUC LADDER (PC9801) A08B9200J502#JP


FANUC LADDER, Body of FANUC LADDER (IBM PC/AT) A08B9201J502#EN
FANUC LADDERII, PMCSA module (PC9801) A08B9200J603#JP
PMCSA module (IBM PC/AT) A08B9201J603#EN
FANUC LADDERIII,
PMCSB/SC module (PC9801) A08B9200J604#JP
LADDER EDITING
PMCSB/SC module (IBM PC/AT) A08B9201J604#EN
PACKAGES FANUC
PMCNB module (PC9801) A08B9200J606#JP
LADDERIII (IBM PMCNB module (IBM PC/AT) A08B9201J606#EN
PC/AT) FANUC LADDERII (IBM PC/AT) A08B9201J503
A08B9210J505, Ladder editing package (IBM PC/AT) A08B9201J510
LADDER EDITING FANUC LADDERIII (IBM PC/AT) A08B9210J505
PACKAGE Ladder editing package
(WINDOWS) (IBM (Windows) (IBM PC/AT) A08B9210J511
PC/AT)
A08B9210J511)
Model PMC PMC PMC PMC PMC PMC PMC PMC PMC
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3
Drawing number

A08B9200J502#JP 5.0 5.0 2.0 2.0 5.0 6.2 1.0 2.0 5.0
A08B9201J502#EN and later and later and later and later and later and later and later and later and later
(Note)

A08B9200J603#JP 4.0 4.0 1.0 1.0 4.0 4.2


A08B9201J603#EN and later and later and later and later and later and later
(Note)

A08B9200J604#JP 1.0 3.0 4.5


A08B9201J604#EN and later and later and later

A08B9201J503 1.0 2.0 1.0 2.0 1.0


and later and later and later and later and later

A08B9201J510 2.1 1.3 2.2 1.0


and later and later and later and later

A08B9210J505 1.0 1.0 1.0 1.0 1.0


and later and later and later and later and later

A08B9210J511 1.0 1.0 1.0 1.0


and later and later and later and later

1397
J. APPLICABLE FANUC LADDER EDITIONS APPENDIX B61863E/14

Model PMC PMC PMC PMC PMC PMC PMC PMC PMC PMC
SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6
Drawing number

A08B9200J502#JP 7.1 8.5 8.5 1.0 5.0 7.1 6.1 8.5


A08B9201J502#EN and later and later and later and later and later and later and later and later

A08B9200J603#JP 1.0 4.5 5.0


A08B9201J603#EN and later and later and later

A08B9200J604#JP 5.0 7.0 7.0 1.0 3.0


A08B9201J604#EN and later and later and later and later and later

A08B9201J503 1.0 1.1 1.1 1.0 1.0 1.0 1.0 3.2


and later and later and later and later and later and later and later and later

A08B9201J510 1.0 1.0 1.0 1.0 1.0 2.1 2.1 3.1


and later and later and later and later and later and later and later and later

A08B9210J505 1.0 1.0 1.0 2.0 1.0 1.0 1.0 1.0 1.0
and later and later and later and later and later and later and later and later and later

A08B9210J511 1.0 1.0 1.0 2.0 1.0 1.0 1.0 1.0 1.0
and later and later and later and later and later and later and later and later and later

NOTE
When a PMCSA5 ladder is to be created in the FANUC
LADDER, set the model to PMCSA3 (RA3).

1398
B61863E/14 APPENDIX J. APPLICABLE FANUC LADDER EDITIONS

J.2 A08B0035J595#E (PG Mark II): FANUC LADDER


PMCSA1/SA2
FANUC LADDER
(SYSTEM P SERIES) A08B0036J595#E (PG Mate):
Model PMC PMC PMC PMC PMC
Edition PA1 PA3 SA1 SA2 SA3
1.1 and later
2.1 and later n
3.1 and later
4.1 and later n
: Not supported, : Supported, n: Restrictedly supported (Note)

NOTE
A sequence program cannot be transferred from the
PMCSA1 of the FANUC Series 20 to the offline
programmer (edition 6.0 or an earlier edition). If this is
attempted, alarm 89 occurs in the offline programmer.

A08B0036J964 (PG Mark II and PG Mate):


PMCSA1/SA2/SB/SC/PA1/PA3 data
Model PMC PMC PMC PMC PMC
Edition PA1 PA3 SA1 SA2 SA3
1.1 and later
2.1 and later
: Not supported, : Supported, n: Restrictedly supported (Note)

A08B0035J595#E (PG Mark II):


FANUC LADDER PMCSB/SB2/SC
A08B0036J595#E (PG Mate):
Model PMC PMC PMC PMC PMC PMC
Edition SB SB2 SB3 SC SC3 NB
1.1 and later
4.1 and later n
: Not supported, : Supported, n: Restrictedly supported (Note)

1399
J. APPLICABLE FANUC LADDER EDITIONS APPENDIX B61863E/14

NOTE
The edition of FANUC LADDER adopted for the PMCSA2
or PMCSB2 can be used to program the PMCSA3 or
PMCSB3 as long as some functional instructions including
structured programming are not used (as long as FANUC
LADDER is used within the range of the specifications of the
PMCSA2 or PMCSB2).
When this edition is used:

(1)The following functional instructions cannot be used. (For


details, see Section 5 of Part I.)
MOVB, MOVW, MOVN
DIFU, DIFD
AND, OR, NOT, EOR
END, CALL, CALLU, SP, SPE
JMPB, JMPC, LBL

(2)A sequence program created by the editing function (ladder


editing module) contained in the PMCSA3/SB3 cannot be
edited after it is read into the offline programmer.

(3)A sequence program created by the offline programmer and


transferred to the PMC (sequence program transferred and
edited by the builtin editing function) can be edited again
after it is read into the offline programmer.

1400
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
B61863E/14 APPENDIX WITH MEMORY CARD

K LEVEL UP OF INPUT/OUTPUT FUNCTION WITH


MEMORY CARD

1401
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
WITH MEMORY CARD APPENDIX B61863E/14

K.1 The function is leveled up, that is Input/Output function with Memory
Card by CNC or Offline Programmer. The leveled up contents are as
OUTLINE OF follows.
LEVELED UP
(1) The time is reduced in Inputing/Outputing between CNC and
CONTENTS Memory Card by PMC I/O function. This is the same between
Offline Programmer and Memory Card.
(2) Sequence programs can be inputted from Memory Card by BOOT
SYSTEM, by which CNC management software or so can be
inputted.
Memory Card function can be used in the following editions of CNC
basic software and PMC management software and FANUC
LADDER for Personal Computer.

CNC basic software


non leveled up leveled up
FANUC Series 20FA basic software (D001) 0506 More than 07
FANUC Series 20TA basic software (D101) 02 More than 03

PMC management software


non leveled up leveled up
PMCSA1/SA3 management software (4080) 0405 More than 06

FANUC LADDER for Personal Computer


non leveled up leveled up
FANUC LADDER PMCSA1/SA2/SB/SB2/SC
SYSTEM
6.1 6.2 More than 6.3
(A08B9200J502#JP (PC9801))
(A089201J502#EN (IBM PC/AT))
PMCSA1/SA2 MODULE
(PMCSA1/SA2/SA3/PA1/PA3)
4.1 More than 4.2
(A08B9200J603#JP (PC9801))
(A089201J603#EN (IBM PC/AT))

1402
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
B61863E/14 APPENDIX WITH MEMORY CARD

K.2
OPERATION

K.2.1 (1) Operation of CNC


CNC Offline 1)On PMC I/O screen, specify MCARD as DEVICE, WRITE
Programmer as FUNCTION, LADDER as DATA KIND, any file name,
which is omissible, as FILE NO. (See Fig. K.2.1 (a)) and
press the soft key [EXEC].

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1
DEVICE = MCARD
FUNCTION = WRITE
DATA KIND = LADDER
FILE NO. =
( #NAME )

[ EXEC ][CANCEL][ WRITE ][ READ ][COMPAR]

[DELETE][ LIST ][FORMAT ][ ][SETUP ]

Fig. K.2.1 (a) PMC I/O screen

(2) Operation of Offline Programmer (FANUC LADDER for Personal


Computer)
2) Mount a Memory Card interface on the personal computer.
3) Select [INOUT] (I/O) from the main menu.
4) Select [MCARD] (Memory Card) from the I/O menu. (See
Fig. K.2.1 (b))

I/O PMCRA1 <O>[A:FLADDER ]

F1 KEY : FA WRITER

F2 KEY : PMC WRITER


F3 KEY : PMC

F4 KEY : Handy File

F5 KEY : Memory Card

F10 KEY : END

FAWRT PMC PMC FDCAS M END


WRT CARD

Fig. K.2.1 (b) I/O Menu screen

1403
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
WITH MEMORY CARD APPENDIX B61863E/14

5) Select [READ] (PROGRAMMER Memory Card). (See Fig.


K.2.1 (c))

I/O (M_CARD) PMCRA1 <O> [A:FLADDER ]

F1 KEY : WRITE (PROGRAMMER > Memory Card)

F2 KEY : READ (PROGRAMMER < Memory Card)

F10 KEY : END

WRITE READ END

Fig. K.2.1 (c) I/O (I/O M_CARD) screen

6) Specify the followings:


Name of the Memory Card file
Specify the name of the file in the Memory Card which is to be
converted and the Memory Card drive on which the Memory
Card is mounted.
Name of the ROM format file to be created
Specify a file name to be given to the converted ROM format
data.

I/O (FROM MC) PMCRA1 <O> [A:FLADDER ]

READ (PROGRAMMER < Memory Card)

Memory Card FILE NAME :


(Specify the MEMORY CARD drive)

ROM FORMAT FILE NAME :

EXEC END

Fig. K.2.1 (d) I/O (FROM MC) screen

7) After it is decompiled, the converted ROM format file can be


edited by the personal computer.

1404
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
B61863E/14 APPENDIX WITH MEMORY CARD

K.2.2 (1) Operation of Offline Programmer (FANUC LADDER for Personal


Offline Programmer computer)
CNC 1) Mount a Memory Card interface on the personal computer.
2) Compile a source program and create a ROM format file.
3) Return to the main menu and select [INOUT] (I/O).
4) From the I/O menu, select {MCARD] (memory Card).
5) Select [WRITE] (PROGRAMMER Memory Card). (See
Fig. K.2.1(c)).
6) Specify the following:
Name of the ROM format file
Specify the name of the ROM format file to be converted.
Name of Memory Card file name
Specify the name to be given to the converted Memory Card
file and the Memory Card drive to which the data is output.
(The file can be accessed by the Memory Card interface
incorporated into the CNC.)

I/O (TO MC) PMC RA1 <O> [A:FLADDER ]

WRITE(PROGRAMMER > Memory Card)

ROM FORMAT FILE NAME :

Memory Card FILE NAME :


(Specify the MEMORY CARD drive)

EXEC END

Fig. K.2.2 I/O (TO MC) screen

(2) Operation of CNC


There are 2 methods by which the sequence program can be inputted
from Memory Card.
The method of using I/O function of PMC
On PMC I/O screen, specify MCARD as DEVICE, READ
as FUNCTION, the file name or file No. you want to input as
FILE NO. and press the soft key [EXEC].
The method of using BOOT SYSTEM (When CNC starting up)
Refer to K.2.3.

1405
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
WITH MEMORY CARD APPENDIX B61863E/14

K.2.3 Sequence programs which are output from leveled up CNC or Offline
Note Programmer to Memory Card can not be input to non leveled up CNC or
Offline Programmer. (Refer to the table of K.1)

(1) (4)

(2) (3)

CNC Offline Programmer

: Leveled up : Available with no condition

: Available with some condition

: Non leveled up

The case of (1), (2), (3) and (4) are explained as follows.
In case of (1), (2)
Output operation : There is no special operation
Input operation : Input sequence programs buy BOOT SYSTEM.
(Refer to K.2.3)

1406
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
B61863E/14 APPENDIX WITH MEMORY CARD

In case of (3)
Output operation : Output sequence programs by setting the output
format to 1 (:SFORMAT) on the following
SETUP screen PMC I/O. The default output
format is 0 (:BINARY).

PMC I/O PROGRAM MONIT STOP

CHANNEL = 1
DEVICE = MCARD
FUNCTION = WRITE
DATA KIND = LADDER
FILE NO. =
( #NAME )

[ EXEC ][CANCEL][ WRITE ][ READ ][COMPAR]

[DELETE][ LIST ][FORMAT ][ ][SETUP ]

PMC SETUP MCARD MONIT STOP

OUTPUT FORMAT (PROGRAM) = 1


(0:BINARY,1:SFORMAT)

[ INPUT ][ ][ ][ ][ INIT ]

Press [INIT] key to reset default value 0.

Input operation : Input sequence programs by selecting F6:I/O


on main menu screen of FANUC LADDER, then
F3:Handy File & Memory Card.
In case of (4)
Output operation : Output sequence programs by selecting F6:I/O
on main menu screen of FANUC LADDER, then
F4:Handy File.
Input operation : Input sequence programs by selecting F6:I/O on
main menu screen of FANUC LADDER, then
F3:Handy File & Memory Card.

1407
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
WITH MEMORY CARD APPENDIX B61863E/14

K.3 Ladder data can be transferred by using a memory card.


NB/NB2 DATA Two data formats are used:
COMPATIBILITY Handy file format
Memory card format
The handy file format defines the S format data used with RS232C.
The memory card format defines the binary format data used for a boot.
Data output to a memory card from the I/O screen of an NB of the 4047
series is handy file format data.
Data output to a memory card from the I/O screen of an NB/NB2 of the
4048 series is memory card format data.

K.3.1
Data Transfer Between
NB (4047 Series) and
FANUC LADDER

Transfer in handy file format FANUC LADDER Transfer function not provided
(personal computer
version)

PMC I/O screen Transfer function not provided NC boot function


NB (4047) NB (4047)

K.3.2
Data Transfer Between
NB/NB2 (4048 Series)
and FANUC LADDER

Transfer in memory card format


FANUC LADDER Transfer in memory card format
(personal computer
version)
Transfer in handy
file format

PMC I/O screen Transfer in memory card format


NC boot function
NB/NB2 (4048) NB/NB2 (4048)

1408
K. LEVEL UP OF INPUT/OUTPUT FUNCTION
B61863E/14 APPENDIX WITH MEMORY CARD

K.3.3
Data Transfer Between
NB (4047 Series) and
NB (4048 Series)

PMC I/O screen Transfer in handy file format PMC I/O screen
NB (4047) NB (4048)

Transfer in handy file format FANUC LADDER Transfer in memory card format
(personal computer
version)

NC boot function Transfer in memory card format NC boot function


NB (4047) NB (4048)

Transfer function not provided

1409
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS APPENDIX B61863E/14

L MIGRATION OF LADDER PROGRAMS BETWEEN


DIFFERENT MODELS

1410
L. MIGRATION OF LADDER PROGRAMS
B61863E/14 APPENDIX BETWEEN DIFFERENT MODELS

L.1 The PMCSB5/SB6 for the Power Mate iD/H are upwardcompatible
with the PMCPA1/PA3 for the Power MateD/H, according to their
MIGRATION OF basic specifications. Because, however, sequence programs are not
LADDER PROGRAMS objectcompatible with the PMCPA1/PA3 for the MateD/H, Ladder
FROM programs sent from the Power MateD/H to a memory card cannot be
directly loaded into the Power Mate iD/H. For this reason, to migrate
Power MateD/H TO
from the Power MateD/H to the Power Mate iD/H, you must convert
Power Mate iD/H the PMC sequence programs.
This section provides information about the PMC programming
compatibility that should be noted when you convert sequence programs.

Differences between the (1) PMC model change


PMCPA1/PA3 for the Sequence programs for one PMC model must be converted to those
Power MateD/H and the for the other. These models are Laddersource compatible with each
PMCSB5/SB6 for the other, and conversion is possible using the procedure described in the
Power Mate iD/H following manual:
Appendix 3.3, Converting Sequence Programs for One PMC Model
to Those for the Other in the FANUC LADDERII Operators
Manual
(2) Changes in the interface signals between CNC and PMC and between
PMC and machine
The F, G, X, and Y address signals have been partially changed.
Change the sequence programs, referring to the following manual:
FANUC Power Mate iMODEL D/H Connection Manual
(Functions)
(3) Change in the basic command processing time
Because of the increase in command execution time, the following
changes may occur:
D Changes in the execution cycle at the second Ladder level
D Changes in the timing of secondlevel division and firstlevel
execution
D Changes in the timing of Ladder program execution and I/O
transfer
(4) PMC addresses expansion
In the PMCSB5, the inner relay (R) and the data table (D) have been
expanded.
In the PMCSB6, the inner relay (R), message request signal (A),
variable timer (T), counter (C), keep relay (K), data table (D), and
subprogram number (P) have been expanded.

1411
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS APPENDIX B61863E/14

Model

PMC address type Power MateD Power MateD/H Power Mate iD/H

PMCPA1 PMCPA3 PMCSB5 PMCSB6

Inner relay (R) R0 to R999 R0 to R999 R0 to R1499 R0 to R2999


R9000 to R9099 R9000 to R9117 R9000 to R9117 R9000 to R9199

Message request signal (A) A0 to A24 A0 to A124

Variable timer (T) T0 to T79 T0 to T299

Counter (C) C0 to C79 C0 to C199

Keep relay (K) K0 to K19 K0 to K39, K900 to K909

Data table (D) D0 to D1859 D0 to D2999 D0 to D7999

Subprogram number (P) P1 to P512 P1 to P2000

(5) Function command specification expansion


Expanded specifications have been added to the function commands
DECB, NUMEB, XMOVB, and PSGN2. The conventional, basic
specifications are still valid and, therefore, sequence programs need
not be changed for migration. For an explanation of the expanded
specifications, see Section I.5, PMC Function Commands.
(6) Changes in a window function
The CNC alarm state read function code has been changed from 23 to
186. In addition, the window function has been changed to the
lowspeed type. For details, see Section B.4.83.

1412
L. MIGRATION OF LADDER PROGRAMS
B61863E/14 APPENDIX BETWEEN DIFFERENT MODELS

L.2 If you previously used the Series 15B PMCNB/NB2, you must convert
from the PMCNB/NB2 to the PMCNB6. The conversion procedure is
MIGRATION FROM as described below.
THE PMCNB/NB2 TO (1) Model change from the PMCNB/NB2 to the PMCNB6 (source
THE PMCNB6 programs)
When changing the model from the PMCNB/NB2 to the NB6, you
must convert the source programs for one PMC model to those for the
other using FANUC LADDERII. Conversion is possible using the
procedure described in the following manual:
Appendix 3.3, Converting Sequence Programs for One PMC
Model to Those for the Other in the FANUC LADDERII
Operators Manual (B66184EN)
The mnemonic file format for the PMCNB6 system parameters used
for model conversion is as follows:

%@0

2 BCD 2. Counter data type (BINARY or BCD)

3 NO 3. Whether the operator panel exists


(exits: YES, does not exist: NO)
4 PMCNB6 4. PMC type (PMCNB6)

7 100 7. Ladder execution time (100%)

The specification changes in the NB6, described in Section I.1.2,


Overview of the Ladder Specifications, must be dealt with
separately.
(2) When using FANUC LADDER
When creating Ladder programs for the PMCNB6 using FANUC
LADDER, specify use of the PMCNB2. When PMCNB2 is
specified, however, the following restrictions are imposed:
a) Do not use the functions supported by the PMCNB6. (See
Section I.1.2, Overview of the Ladder Specifications for details.)
b) Do not use sequence programs with C programs linked.
(3) If using sequence programs located on the FANUC Series 15B
a) If using sequence programs for the PMCNB2 that are located on
the Series 15B in the Series 15i, the same restrictions as those
described in (2) are imposed. Provided that these restrictions are
observed, programs for the PMCNB2 can be output to a memory
card (by specifying LADDER for DATA KIND on the I/O
screen) and directly loaded into the Series 15i.
b) Sequence programs for the PMCNB that are located on the Series
15B cannot be used in the Series 15i, without first being
converted. They must be converted into programs for the
PMCNB6 with the model change procedure using FANUC
LADDERII, described in (1).

1413
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS APPENDIX B61863E/14

L.3 When you want to change ladder from PMC SA5/SB5/SB6 to


PMCSB7, you can convert the source program using FANUC
MIGRATION FROM LADDERIII. Please refer to following manual for details.
THE PMCSA5/ FANUC LADDERIII OPERATORS MANUAL B66234EN
SB5/SB6 TO THE 10.3 CONVERTING SEQUENCE PROGRAM BETWEEN PMC
PMCSB7 MODELS
The sequence of the conversion is as follows.
i) Convert a source program into the mnemonic file by FANUC
LADDERIII.
ii) Change the system parameters in the mnemonic file for PMCSB7
by text editor.
iii) Create a new source program for PMCSB7 by FANUC
LADDERIII.
D If you want to change the model PMCSA5/SB5/SB6 to model
PMCSB7, change the item PMC TYPE to PMCSB7.
D If the mnemonic file has insufficient parameters for PMCSB7, the
initial values are set with conversion for the source program.
D The mnemonic file format of the system parameter for PMCSB7
is as follows.

%@0
2 BINARY 2. Counter type (BINARY or BCD)
3 NO 3.Operator panel (YES or NO)
4 PMCSB7 4. PMC type
7 150 7. Ladder execution ratio (150%)*
%

NOTE
The default value is 150. The meaning is described in L.3.1
Addition of LADDER EXEC in the system parameter

iv) Convert the mnemonic file to the source program and overwrite it
on the new source program for PMCSB7.

1414
L. MIGRATION OF LADDER PROGRAMS
B61863E/14 APPENDIX BETWEEN DIFFERENT MODELS

L.3.1 For the PMCSB7, with addition of the third ladder level, the ladder
Addition of System execution time is added as a system parameter.
Set the time by which the processing time for the first and second levels
Parameter Ladder is to be increased or decreased.
Execution Time
Initial value 150 Range of valid settings 1 to 150

D If the ladder uses only the first and second levels, set the upper limit
(150).
D If the upper limit (150) is set for a ladder which uses the third level,
the third level may not operate satisfactorily. In this case, set this
parameter so that the processing time for the first and second levels is
decreased.
The processing time for the first and second levels of a ladder is
obtained using the following expression:
Processing time for the first =5msec Ladder execution time
and second levels of a ladder 100

The processing time for the third level of a ladder is obtained using the
following expression:
Processing time for the third level of a ladder =
7.5 msec (processing time for the first and second levels of the ladder)
For example, when this parameter is set to 100, the processing time for
the first and second levels of the ladder is 5 ms and that for the third
level is 2.5 ms in a cycle of 8 ms.

1415
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS APPENDIX B61863E/14

L.4
MIGRATION FROM
THE SERIES 0 AND
SERIES 21B TO
SERIES 0i

L.4.1 The object and the source of the ladder program are not compatible
between PMCSA1/SA3 for Series 0i and PMCL/M for Series 0.
Compatible With
Therefore, to apply the ladder program of PMCL/M for Series 0 to the
Series 0 ladder program of PMCSA1/SA3 for Series 0i, you need to convert from
the ladder program of PMCL/M to the mnemonic form, correct the
mnemonic form data, and convert from the mnemonic form data to the
ladder program of PMCSA1/SA3.
D The difference between PMCL/M for Series 0 and PMCSA1/SA3
for Series 0i and the countermeasure
1. TMR, TMRB, and CTR instruction.
PMCSA1/SA3 are different from PMCL/M in the number of the
parameter in TMR,TMRB and CTR instructions. Therefore, please
check the mnemonic form data, and delete the parameter, and set
up the timer or the counter.
(Example)
Instruction Before the modification After the modification
(PMCL/M) (PMCSA1/SA3)

TMR RD R400.0 RD R400.0


TMR 1 TMR 1
D300 WRT R401.1
WRT R401.1

TMRB RD R400.1 RD R400.1


SUB 24 SUB 24
2 2
1000 1000
D310 WRT R401.2
WRT R401.2

CTR RD.STK R400.2 RD.STK R400.2


SUB 5 SUB 5
1 1
D320 WRT R401.3
WRT R401.3

2. END3(SUB48), PACTL(SUB25) and DISP(SUB49) instruction


Instruction Countermeasure

END3 (SUB48) This instruction has not been supported in PMCSA1/SA3.


Please delete the ladder program of third level. Or, please move to second level
from third level, and delete END3(SUB48).

PACTL (SUB25) This instruction has not been supported in PMCSA1/SA3.


Please delete PACTL(SUB25).

DISP (SUB49) This instruction has not been supported in PMCSA1/SA3.


Please change the ladder, and use the DISPB instruction.
Please delete DISP(SUB49).

1416
L. MIGRATION OF LADDER PROGRAMS
B61863E/14 APPENDIX BETWEEN DIFFERENT MODELS

3. The difference of the addresses


Converting of the addresses except F/G/X addresses
Please correct the range of the address when the address which
is out of range in PMCSA1/SA3 is used.
(Example) The below address cannot be used in PMCSA1/
SA3.
D3584D3839, R3840R4095 etc.
Converting of F/G/X addresses
Please refer to the connection manual of Series 0 and Series 0i,
and convert F/G/X addresses.
Also, FANUC LADDER and FANUC LADDERII can
convert the F/G signals between NC and PMC from Series 0 to
Series 0i.
This conversion has the following limitations.
(1) The ladder program converted into a mnemonic form is
necessary.
(2) The bit address that is used in basic instruction is
converted.
(3) The byte address that is used in functional instruction is not
converted.
(4) This conversion can avail only the case that the addresses
are converted from standard Series 0T/M to standard
Series 0iTA/MA. The F/G addresses of 1000.0 or more
are not converted.
(5) When the same signal name is used in the Series 0 and
Series 0i, and the addresses corresponding to the signal in
the Series 0 and Series 0i have onetoone relationship, the
bit address is converted.

NOTE
FANUC LADDERIII cannot convert the address.

[Operation of conversion]
In case of FANUC LADDER (Example: Converting the ladder to
PMCSA1 for Series 0iMA from PMCM for Series 0M)
(1) Prepare the mnemonic form file of PMCM that you want to convert.
(*A)
(2) Input a new source program name in EDIT of FANUC LADDER,
and select the PMCRA1(SA1) in SETUP, and quit the edit screen
without edit operation.
(3) Convert to the mnemonic form file from source program of (2). (*B)
The empty mnemonic form file is made.
(4) Exit FANUC LADDER, and start up the text editor.
Specify the mnemonic form file of (3) as the edit file name.
(5) Replace the symbol data of the mnemonic form file(PMCSA1) of (3)
with the converter file of FS0T_CNV.SYM or FS0M_CNV.SYM.
(*C)

1417
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS APPENDIX B61863E/14

The converter file is stored in OAppendix of the installed


directory of FANUC LADDER.
FS0MCNV.SYM: For converting to Series 0iMA from
Series 0M
FS0TCNV.SYM: For converting to Series 0i TA from
Series 0T

(6) Replace the ladder data of the mnemonic form file(PMCSA1) of (3)
with the ladder data of the mnemonic form file(PMCM) of (1). (*D)
(7) Exit the text editor, and start up FANUC LADDER.
(8) Specify the PMCRA1(SA1) as PMC model, and convert to the
source program from the mnemonic form file of (5).
(9) Delete all symbols and comment on the EDIT screen.

*A Original mnemonic file Converter file *B Converted mnemonic file


(PMCM) FS0MCNV.SYM (PMCSA1)

%@A %@2 %@A


%@0 G000.0 G100.0 %@0
1 400 G000.1 G100.1 2 BINARY
20 G000.2 G100.2 *C insertion 3 NO
30 G000.3 G100.3 " 4 PMCRA1
40 ... *D insertion %
"
50 %@1
60 %
7 100 %@2
80 %
90 %@3
%
%@1
%
%@2
%

In case of FANUC LADDERII (Example: Converting the ladder to


PMCSA3 for Series 0iTA from PMCM for Series 0T)
(1) Prepare the mnemonic form file of PMCM that you want to convert.
(**A)
(2) Input the new source program name on the Program Selection in
FANUC LADDERII, and select the PMCSA3/RA3, and select
the OffLine function.
(3) Convert to the mnemonic form file from source program of (2). (**B)
Select the MNEMONIC EDIT, and specify the SOURCE
PROGRAM MNEMONIC FILE. The empty mnemonic form file
is made.
(4) Exit FANUC LADDERII, and start up the text editor.
Specify the mnemonic form file of (3) as the edit file name.

1418
L. MIGRATION OF LADDER PROGRAMS
B61863E/14 APPENDIX BETWEEN DIFFERENT MODELS

(5) Replace the symbol data of the mnemonic form file(PMCSA3) of (3)
with the converter file of FS0T_CNV.SYM or FS0M_CNV.SYM.
(**C)

The converter file is stored in \Appendix of the installed


directory or system floppy of FANUC LADDERII.
FS0MCNV.SYM: For converting to Series 0iMA from
Series 0M
FS0TCNV.SYM: For converting to Series 0iTA from
Series 0T

(6) Replace the ladder data of the mnemonic form file(PMCSA3) of (3)
with the ladder data of the mnemonic form file(PMCM) of (1). (**D)
(7) Exit the text editor, and start up FANUC LADDERII.
(8) Select the PMCRA1(SA1) as PMC model, and convert to the source
program from the mnemonic form file of (5). Select the
MNEMONIC EDIT, and specify the MNEMONIC FILE
SOURCE PROGRAM.
(9) Delete all symbols and comment data on the SYMBOL &
COMMENT of the EDIT.

*A Original mnemonic file Converter file **B Converted mnemonic file


(PMCM) FS0TCNV.SYM (PMCSA3)

%@A %@2 %@A


%@0 G000.0 G100.0 %@0
1 400 G000.1 G100.1 2 BINARY
20 G000.2 G100.2 **C insertion 3 NO
30 G000.3 G100.3 " 4 PMCRA3
40 ... **D insertion %
"
50 %@1
60 %
7 100 %@2C
80 %
90 %@3
%
%@1
%
%@2
%

1419
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS APPENDIX B61863E/14

L.4.2 The ladder program of PMCSA1/SA3 for Series 0i has the objective
Compatibility With compatibility with the ladder program of PMCSA1/SA3 for Series 21B
or PMCSA1/SA5 for Series 21i/210i.
Series 21MODEL B Therefore, you can load the ladder program outputted from Series 21B
by using memory card on BOOT screen of Series 0i.
However, correction of the ladder program might be needed in the
following cases.
(1) Ladder program depending on execution time
The execution timing might change as follows because the execution
time of the instruction is changed.
Change in the execution cycle at the second ladder level.
Change in the timing of secondlevel division and firstlevel
execution.
Change in the timing of ladder program execution and I/O transfer.

L.4.3 The PMC specification of Series 0i is the same as PMCSA1/SA3 for


Series 21B. However, the following function is not supported.
Limited Function
The memory card cannot be used on the I/O Screen of PMC.
In other words, the ladder program and the PMC parameter cannot be
input or output on the PMC screen with a memory card.
Please use the BOOT screen when you input or output the ladder program
with a memory card.
Please use the FANUC floppy disk cassette, the Handy File or
PC(personal computer) when you input or output the PMC parameter.
The online function of FANUC LADDERII or FANUC LADDERIII
is not supported.

1420
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

M ALARM MESSAGE LIST

1421
M. ALARM MESSAGE LIST APPENDIX B61863E/14

M.1
ALARM MESSAGE
(PMCPA1/PA3/SA1/
SA2/SA3/SA5/SB/
SB2/SB3/SB4/SB5/
SB6/SC/SC3/SC4/NB/
NB2/NB6)
Alarm messages 1 (alarm screen)
Message Contents and solution
ALARM NOTHING Normal status
or
NO ALARM (In case of PMCNB6)
ER00 PROGRAM DATA ERROR (ROM) The sequence program in the ROM is not written correctly.
(solution) Please exchange ROM for the sequence program.
ER01 PROGRAM DATA ERROR (RAM) The sequence program in the debugging RAM is defective.
(solution) Please clear the debugging RAM and input LADDER again.
The debugging RAM is not installed though the RAM is selected.
(solution) Please install the debugging RAM or install ROM for sequence
program and select ROM with K17#3=0.
ER02 PROGRAM SIZE OVER The size of a sequence program exceeded the maximum allowable
ladder size.
(solution) The ordered RAM size is smaller than the option. Contact FA-
NUC.
Change the value of MAX LADDER AREA SIZE on the SYSPRM
screen, then turn the power off then back on (only with PMCSC).
ER03 PROGRAM SIZE ERROR (OPTION) The size of sequence program exceeds the option specification size.
(solution) Please increase the option specification size.
Or, reduce the size of sequence program.
ER04 PMC TYPE UNMATCH The PMC model setting of the sequence program is not corresponding to
an actual model.
(solution) Please change the PMC model setting by the offline program-
mer.
ER05 PMC MODULE TYPE ERROR The module type of the PMC engine is not correct.
(solution) Please exchange the module of PMC engine for a correct one.
ER06 PROGRAM MODULE NOTHING Both ROM for sequence program and the debugging RAM do not exist
(PMCSC only).
For a 3path system, the PMC model must be SB6.
(solution) Contact FANUC.
ER07 NO OPTION (LADDER STEP) There is no step number option of LADDER.
ER08 OBJECT UNMATCH Sequence Program has 2 channels of I/O Link, but PMC control software
or Ladder Editor Card or PMC C language control software does not
support the I/O Link expansion.
(solution) To use only the I/O Link channel 1, use sequence program for
only channel 1. To use the I/O Link channel 2, update PMC
control software and Ladder Editor Card and PMC C language
control software supported the I/O Link expansion.
ER10 OPTION AREA NOTHING The PMCSB management software is not transferred.
(SERIESNAME) (solution) There is a mismatch between the order and delivered the soft-
ware. Contact FANUC.
ER11 OPTION AREA NOTHING The PMC C language board management software is not transferred.
(SERIESNAME) (solution) There is a mismatch between the order and delivered the soft-
ware. Contact FANUC.
ER12 OPTION AREA ERROR (SERIESNAME) There is a series mismatch between the basic and option of the PMCSB
management software.
(solution) Contact FANUC.

1422
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

Message Contents and solution


ER13 OPTION AREA ERROR (SERIESNAME) There is a series mismatch between the basic and option of the PMC C
language board management software.
(solution) Contact FANUC.
ER14 OPTION AREA VERSION ERROR There is an edition mismatch between the basic and option of the
(SERIESNAME) PMCSB management software.
(solution) Contact FANUC.
ER15 OPTION AREA VERSION ERROR There is an edition mismatch between the basic and option of the PMC C
(SERIESNAME) language board management software.
(solution) Contact FANUC.
ER16 RAM CHECK ERROR (PROGRAM RAM) The debugging RAM cannot be read/written normally.
(solution) Please exchange the debugging RAM.
ER17 PROGRAM PARITY The parity error occurred on ROM for sequence program or the
debugging RAM.
(solution) ROM: The deterioration of ROM may be deteriorated
Please exchange ROM for the sequence program
RAM: Please edit the sequence program once on PMC
Still the error occurs, exchange the debugging
RAM.
FROM: (PMCNB/FS20)
Please edit the sequence program once on PMC
and write sequence program to FROM again.

NOTE
1 The PMCSB3/SC3 for the Series 16 MODELB does not support ER00 and ER06.
2 For the PMCSB3/SC3 for the Series 16 MODELB, the debugging RAM and ROM for
sequence program, described in the table, are not supported but the relevant descriptions
apply to ordinary RAM.

1423
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Alarm messages 2 (alarm screen)


Message Contents and solution
ER18 PROGRAM DATA ERROR BY I/O Transferring the sequence program from offline programmer was
interrupted by the power off etc.
(solution) Please clear the sequence program and transfer the se-
quence program again.
ER19 LADDER DATA ERROR Editing the LADDER was interrupted by the power off or by the switch to
the CNC screen by the function key etc.
(solution) Please edit LADDER once on PMC.
Or, please input LADDER again.
ER20 SYMBOL/ COMMENT DATA ERROR Editing the symbol and comment was interrupted by the power off or by
the switch to the CNC screen by the function key etc.
(solution) Please edit symbol and comment once on PMC.
Or, please input symbol and comment again.
ER21 MESSAGE DATA ERROR Editing the message data was interrupted by the power off or the switch to
the CNC screen by the function key etc.
(solution) Please edit message data once on PMC.
Or, please input message data again.
ER22 PROGRAM NOTHING There is no sequence program.
or (solution) Load a proper program at I/O screen or create program at LAD-
ER 22 NO PROGRAM(In case of PMCNB6) DER Diagram Editor screen. After a program is loaded or
created, you have to write it to flash ROM not to lose it at power
off.
ER23 PLEASE TURN OFF POWER There is a change in setting LADDER MAX AREA SIZE etc.
(solution) Please restart the system to make the change effective.
ER24 LADDER, LANGUAGE AREA OVERLAP The ladder area overlaps the C language area.
(solution) Adjust the C program address range.
ER25 SOFTWARE VERSION ERROR (xx) xx=PMCAOPT : The version in the PMCSB management software
does not match.
xx=PMCBAS2 : The version in the PMCNB6 management software
does not match.
ER26 PMC CONTROL MODULE ERROT (xx) xx=PMCAOPT : The PMCSB management software has not been
initialized.
xx=PMCBAS2 : The PMCNB6 management software has not been
initialized.
ER28 NO OPTION(I/O LINK EXPANSION) Sequence Program has 2 channels of I/O Link, but the option of I/O Link
expansion is not provided.
(solution) To use only I/O Link channel 1, use sequence program for only
channel 1. To use the I/O Link channel 2, the option of the I/O
Link expansion is necessary.
ER29 NO SUPPORT HARDWARE(I/O LINK The I/O Link 2channel is not supported by the edition of printed circuit
2CH) board.
(solution) To use only the I/O Link channel 1, use sequence program for
only channel 1. To use the I/O Link channel 2, exchange main
CPU board with one which supports the I/O Link 2 channel.
ER32 NO I/O DEVICE Any I/O Unit or the connection unit etc. is not connected on each channel.
When builtin I/O card is connected, this message is not displayed.
(solution) When builtin I/O card is used:
Please confirm whether the builtin I/O card is certainly con-
nected with.
When I/O Link is used:
Please confirm whether the DI/DO units turning on. Or please
confirm the connection of the cable.
ER33 SLC ERROR The LSI for I/O Link is defective.
or Display of CH2 means the defectiveness of I/O Link channel 2.
ER33 SLC ERROR(CH2) (solution) Please exchange the module of PMC engine.

1424
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

Message Contents and solution


ER34 SLC ERROR(xx) The communication with the DI/DO units of the xx group of I/O Link failed.
or Display of CH2 means the xx group of I/O Link channel 2.
ER34 SLC ERROR(CH2 xx) (solution) Please confirm the connection of the cable connected to the
DI/DO units of the xx group.
Please confirm that the DI/DO units turned on earlier than CNC
and PMC. Or, please exchange the main CPU board.
ER35 TOO MUCH OUTPUT DATA IN GROUP The amount of the output data in the xx group of I/O Link exceeded the
(xx) max. The data, which exceed 32 bytes, become ineffective.
or Display of CH2 means the xx group of I/O Link channel 2.
ER35 TOO MUCH OUTPUT DATA (CH2 xx) (solution) Please refer to the following for the number of the data for each
group.
FANUC I/O UnitMODEL A connecting and maintenance
manual (B61813E) FANUC I/O UnitMODEL B connecting
manual(B62163E)
ER36 TOO MUCH INPUT DATA IN GROUP (xx) The number of the input data in the xx group of I/O Link exceeded the
or max. The data, which exceed 32 bytes, become ineffective.
ER36 TOO MUCH INPUT DATA (CH2 xx) Display of CH2 means the xx group of I/O Link channel 2.
(solution) Please refer to the following for the number of the data for each
group.
FANUC I/O UnitMODEL A connecting and maintenance
manual (B61813E) FANUC I/O UnitMODEL B connecting
manual(B62163E)
ER38 MAX SETTING OUTPUT DATA OVER (xx) The assignment data for a group exceeds 128 bytes.
or (The assignment data of output side of xx group or later become
ER38 MAX SETTING OUTPUT DATA (CH2 xx) ineffective.)
Display of CH2 means the xx group of I/O Link channel 2.
(solution) Please reduce the assignment data to 128 bytes or less for the
number of the output data of each group.
ER39 MAX SETTING INPUT DATA OVER (xx) The assignment data for a group exceeds 128 bytes.
or (The assignment data of input side of xx group or later become infective.)
ER39 MAX SETTING INPUT DATA (CH2 xx) Display of CH2 means the xx group of I/O Link channel 2.
(solution) Please reduce the assignment data to 128 bytes or less for the
number of the input data of each group.
ER48 STEP SEQUENCE TIME OVER (xxH) Timeout occurred during step sequence processing. For details, see
IV6.2.2.
ER98 ILLEGAL LASER CONNECTION The I/O unit group for the laser does not match the assignment data.
(solution) Make sure that the actual I/O unit configuration matches the
assignment data in the ladder.
ER99 X, Y96127 ARE ALLOCATED Laser I/O assignments are assigned to X96 to X127 and Y96 to Y127
when the laser I/O link is supported.
(solution) Delete I/O assignment data of X96 to X127 and Y96 to Y127.

1425
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Alarm messages 3 (alarm screen)


Message Contents and solution
WN01 LADDER MAX SIZE ERROR The MAX LADDER AREA SIZE in the system parameter is illegal.
(solution) Set the correct value to MAX LADDER AREA SIZE and restart
the system.
WN02 OPERATE PANEL ADDRESS ERROR The address setting data of the operators panel for FS0 is illegal.
(solution) Please correct the address setting data.
WN03 ABORT NCWINDOW/EXIN LADDER was stopped while CNC and PMC were communicating.
The functional instruction WINDR, WINDW, EXIN, DISPB, and etc. may
not work normally.
(solution) When restarting the system, this alarm will be released.
Execute the sequence program(Press RUN key) after confirm-
ing whether there is a problem in LADDER or not.
WN04 UNAVAIL EDIT MODULE The LADDER editing module cannot be recognized.
(PMCSA1/SA2/SA3/SB/SB2/SB3, except SA1/SA3 for FS20)
(solution) Please confirm the slot position installed.
Please confirm the installed module.
WN05 PMC TYPE NO CONVERSION A PMCSA3/SA5 ladder was transferred to PMCSB5.
(solution) Correct the ladder type.
WN06 TASK STOPPED BY DEBUG FUNC Some user tasks are stopped by break point of the debugging function.
WN07 LADDER SP ERROR (STACK) When functional instruction CALL(SUB65) or CALLU(SUB66) was
executed, the stack of the LADDER overflowed.
(solution) Please reduce the nesting of the subprogram to 8 or less.
WN09 SEQUENCE PROGRAM IS NOT The sequence program has been modified at LADDER Diagram Editor
WRITTEN TO FROM screen, I/O Unit Allocation Editor screenor or I/O screen, and the modified
program has not written to flash ROM yet. If CNCs power is turned off
before writing the modified program to flash ROM, it will be lost at power
off.
(solution) If the modified program is expected to run also at next time
when CNCs power is turned on, write the modified program to
Flash ROM at I/O screen. If the sequence program has been
modified by accident, read correct program from flash ROM at
I/O screen.
WN17 NO OPTION (LANGUAGE) There is no C language option.
WN18 ORIGIN ADDRESS ERROR The LANGUAGE ORIGIN address of the system parameter is wrong
(solution) Please set the address of symbol RC_CTLB_INIT in the map file
to the LANGUAGE ORIGIN of the system parameter.
WN19 GDT ERROR (BASE, LIMIT) The value of BASE, LIMIT or ENTRY of user defined GDT is illegal.
(solution) Please correct the address in link control statement and build file.
WN20 COMMON MEM. COUNT OVER The number of common memories exceeds 8.
(solution) Please reduce the number of common memories to 8 or less.
It is necessary to correct a link control statement,build file and the
source file for the common memory.
WN21 COMMON MEM. ENTRY ERROR GDT ENTRY of the common memory is out of range.
(solution) Please correct the address of GDT ENTRY of the common
memory in the link control statement.
WN22 LADDER 3 PRIORITY ERROR The priority of LADDER LEVEL 3 is out of range.
(solution) Please correct the value of LADDER LEVEL 3 in the link con-
trol statement within the range of 0 or 1099 or 1.
WN23 TASK COUNT OVER The number of user tasks exceeds 16.
(solution) Please confirm TASK COUNT in the link control statement.
When the number of tasks is changed, it is necessary to cor-
rect the link control statement, build file and the composition of
the files to be linked.
WN24 TASK ENTRY ADDR ERROR The selector of the entry address to the user task is out of range.
(solution) Please correct the table of GDT in build file to the value within
32(20H)95(5FH).

1426
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

Message Contents and solution


WN25 DATA SEG ENTRY ERROR The entry address of the data segment is out of range.
(solution) Please correct DATA SEGMENT GDT ENTRY in the link con-
trol statement and the table of GDT in build file within
32(20H)95(5FH).
WN26 USER TASK PRIORITY ERROR The priority of the user task is out of range.
(solution) Please correct the TASK LEVEL in link control statement within
the range of 1099 or 1.
Note: Only one task can have TASK LEVEL 1 (including LAD-
DER LEVEL 3).
WN27 CODE SEG TYPE ERROR The code segment type is illegal. The code segment of RENAMESEG in
the binding control file is wrong.
(solution) Please correct the entry of the code segment in the link control
statement to correspond to the entry in the build file.
WN28 DATA SEG TYPE ERROR The data segment type is illegal. The data segment of RENAMESEG in
the binding control file is wrong.
(solution) Please correct the entry of the code segment in the link control
statement to correspond to the entry in the build file.
WN29 COMMON MEM SEG TYPE ERROR The segment type of common memory is illegal. The segment of
RENAMESEG in the building control file of the common memory is
wrong.
(solution) Please correct the entry of common memory in the link control
statement to correspond to the entry in the build file.
WN30 IMOPSSIBLE ALLOCATE MEM. The memories for the data and stack etc. cannot be allocated.
(solution) Please confirm whether the value of code segment in build file
and USER GDT ADDRESS in link control statement is correct
or not.
Or please reduce the value of MAX LADDER AREA SIZE of
the system parameter and the size of the stack in link control
statement at the least.
WN31 IMPOSSIBLE EXECUTE LIBRARY The library function cannot be executed.
(solution) Please confirm the object model of the library.
Or, system ROM of PMC must be replaced with one of later ver-
sion.
WN32 LNK CONTROL DATA ERROR Link control statement data is illegal.
(solution) Please confirm whether the address of symbol
RC_CTLB_INIT in map file is set to LANGUAGE ORIGIN of the
system parameter. Or, please make the link control statement
again.
WN33 LNK CONTROL VER. ERROR A link control statement data version error occurred.
(solution) Correct the link control statement in the C program.
WN34 LOAD MODULE COUNT OVER There are more than eight independent load modules.
(solution) Reduce the number of independent load modules to eight or
less.
WN35 CODE AREA OUT OF RANGE The code segment area is outside the RAM area.
(solution) Check the link map, and place segments within the RAM area.
WN36 LANGUAGE SIZE ERROR (OPTION) The size of the language area exceeds the option.
(solution) Check the free space, and increase the option.
WN37 PROGRAM DATA ERROR (LANG.) The language program area is invalid.
(solution) Install the correct language program.
WN38 RAM CHECK ERROR (LANG.) A RAM check error occurred in the language program area.
(solution) Replace the RAM.
WN39 PROGRAM PARITY (LANG.) A parity error occurred in the language program area.
(solution) Reenter each language program. If an error still occurs, re-
place the RAM.
WN40 PROGRAM DATA ERROR BY I/O Language program read operation was interrupted.
(LANG.) (solution) Reenter the language program.

1427
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Alarm messages 4 (alarm screen)


Message Contents and solution
WN41 LANGUAGE TYPE UNMATCH There is a C program type mismatch.
(solution) Correct the C program.
WN42 UNDEFINE LANGUAGE ORIGIN No language origin address is set.
ADDRESS (solution) Set a language origin address.

1428
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

M.2
ALARM MESSAGE
(PMCSB7)
Alarm number Faulty location/corrective action Contents
ER01 PROGRAM DATA ERROR 1) Reinput the sequence program. The sequence program is invalid.
2) Replace the master printed circuit
board.
ER02 PROGRAM SIZE OVER 1) Reduce the sequence program. The sequence program is too large.
2) Contact FANUC to have a larger The sequence program is invalid.
numberofLaddersteps option
specified.
ER03 PROGRAM SIZE ERROR 1) Reduce the sequence program. The sequence program exceeds the
(OPTION) 2) Contact FANUC to have a larger size specified by the numberof
numberofLaddersteps option Laddersteps option.
specified.
ER04 PMC TYPE UNMATCH Using an offline programmer, change The setting of the type in the sequence
the sequence program to that for the program differs from the actual type.
correct PMC type.
ER06 PMC CONTROL SOFTWARE Contact FANUC to specify certain PMC The combination of CNC system
TYPE UNMATCH type configuration and PMC type is invalid.
(Example: PMCSB5 is used for a
3path CNC system.)
ER07 NO OPTION (LADDER STEP) 1) Restore the backed up CNC No numberofLaddersteps option is
parameter data. found.
2) Check the data sheet and reinput
the CNC parameters.
3) Contact FANUC to specify a
numberofLaddersteps option of
the necessary size.
ER08 OBJECT UNMATCH 1) Contact FANUC. An unsupported function is used in the
sequence program.
ER09 PMC LABEL CHECK 1) Press and hold down the O and Z With a change in the PMC type, for
ERRORPLEASE TURN ON POWER key combination, and turn the CNC example, the retentiontype memory of
AGAIN WITH PUSH O&Z. back on. the PMC must be initialized.
(CLEAR PMC SRAM) 2) Replace the backup battery.
3) Replace the master printed circuit
board.
ER10 OPTION AREA NOTHING Contact FANUC to reconfigure the PMC The PMC management software is not
(xxxx) management software. loaded correctly.
ER11 OPTION AREA NOTHING Contact FANUC to reconfigure the PMC The PMC C board management
(xxxx) management software. software is not loaded correctly.
ER12 OPTION AREA ERROR (xxxx) Contact FANUC to reconfigure the PMC The PMC management software is
management software. invalid.
(The series of BASIC and OPTION do
not match.)
ER13 OPTION AREA ERROR (xxxx) Contact FANUC to reconfigure the PMC The PMC C board management
management software. software is invalid.
(The series of BASIC and OPTION do
not match.)
ER14 OPTION AREA VERSION Contact FANUC to reconfigure the PMC The PMC management software is
ERROR (xxxx) management software. invalid.
(The editions of BASIC and OPTION do
not match.)
ER15 OPTION AREA VERSION Contact FANUC to reconfigure the PMC The PMC C board management
ERROR (xxxx) management software. software is invalid.
(The editions of BASIC and OPTION do
not match.)

1429
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Alarm number Faulty location/corrective action Contents


ER16 RAM CHECK ERROR Replace the master printed circuit board The initialization of the memory used to
(PROGRAM RAM) store the sequence program failed.
ER17 PROGRAM PARITY 1) Reinput the sequence program. The parity of the sequence program is
2) Replace the master printed circuit invalid.
board.
ER18 PROGRAM DATA ERROR BY Reinput the sequence program. While the sequence program was being
I/O read, an interrupt command was
generated.
ER19 LADDER DATA ERROR Display the Ladder edit screen again During Ladder editing, the system was
and exit from editing by using the [<<] forcibly switched to the CNC screen with
key. a function key.
ER20 SYMBOL/COMMENT DATA Display the symbol/comment edit During symbol/comment editing, the
ERROR screen again and exit from editing by system was forcibly switched to the
using the [<<] key. CNC screen with a function key.
ER21 MESSAGE DATA ERROR Display the message data edit screen During message data editing, the
again and exit from editing by using the system was forcibly switched to the
[<<] key. CNC screen with a function key.
ER22 PROGRAM NOTHING 1) Reinput the sequence program. The sequence program is empty.
2) Replace the master printed circuit
board.
ER23 PLEASE TURN OFF POWER Turn the CNC off and then back on. With a change in the PMC type, for
example, the power must be turned off
and then back on.
ER25 SOFTWARE VERSION ERROR Contact FANUC to reconfigure the PMC The PMC management software is
(PMCAOPT) management software. invalid.
(The edition of PMCAOPT does not
match.)
ER26 PMC CONTROL MODULE 1) Contact FANUC to reconfigure the The initialization of the PMC
ERROR (PMCAOPT) PMC management software. management software failed.
2) 2) Replace the master printed circuit
board.
ER27 LADDER FUNC. PRM IS OUT Modify the sequence program. Change An outofrange parameter number is
OF RANGE the parameter number of the function specified with function instruction TMR,
instruction to a value within the valid TMRB, CTR, DIFU, or DIFD.
range.
ER32 NO I/O DEVICE 1) Check that the I/O device is on. An I/O device such as the I/O Link,
2) Check that the I/O device was turned connection unit, and Power Mate is not
on before the CNC was turned on. connected.
3) Check the connection of the cable.
ER33 I/O LINK ERROR Replace the master printed circuit The LSI of the I/O Link is defective.
board.
ER34 I/O LINK ERROR (xx) 1) Check the connection of the cable In a slave in group xx, an error occurred
leading to a device in group xx. in communication with an I/O device.
2) Check that the I/O device was turned
on before the CNC.
3) Replace that device in group xx in
which the PMC control module is
installed.
ER35 TOO MUCH OUTPUT DATA IN Reduce the amount of output data in The amount of output data in I/O Link
GROUP (xx) group xx. group xx exceeds the limit (33 bytes).
The excess data is nullified.
ER36 TOO MUCH INPUT DATA IN Reduce the amount of input data in The amount of input data in I/O Link
GROUP (xx) group xx. group xx exceeds the limit (33 bytes).
The excess data is nullified.
ER38 MAX SETTING OUTPUT DATA Modify the total amount of output data in The I/O Link I/O area is insufficient.
OVER (xx) each group to 128 bytes or less. (The allocation of any group after group
xx on the output side is nullified.)

1430
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

Alarm number Faulty location/corrective action Contents


ER39 MAX SETTING INPUT DATA Modify the total amount of input data in The I/O Link I/O area is insufficient.
OVER (xx) each group to 128 bytes or less. (The allocation of any group after group
xx on the input side is nullified.)
ER40 I/O LINKII SETTING ERROR Reconfigure the I/O LinkII. The I/O LinkII setting is invalid.
(CHx) (CH1: Primary board, CH2: Secondary
board)
ER41 I/O LINKII MODE Reconfigure the I/O LinkII. The I/O LinkII mode setting is invalid.
ERROR(CHx) (CH1: Primary board, CH2: Secondary
board)
ER42 I/O LINKII STATION Reconfigure the I/O LinkII. The I/O LinkII station number setting is
NO.ERROR (CHx) invalid.
(CH1: Primary board, CH2: Secondary
board)
ER97 IO LINK 1) Check whether the cables of I/O The number of assigned I/O modules in
(CHxyyGROUP) devices in group yy are connected group yy differs from that of I/O devices
properly. actually connected.
2) Check the power to each I/O device.
3) Check the parameter setting of the
I/O link assignment data selection
function.
ER98 ILLEGAL LASER Modify the allocation of the I/O module. When an I/O device for a laser is used,
CONNECTION the allocation of the I/O module does not
match the actual I/O device
configuration.
ER99 X,Y96127 ARE ALLOCATED Modify the allocation of the I/O module. When an I/O device for a laser is used,
another I/O device is allocated to
X96127/Y96127.
X96127/Y96127 are used for I/O
devices for a laser, and cannot be used
for other devices.
WN02 OPERATE ADDRESS ERROR Modify the setting of the PMC system The setting of the PMC system
parameter, address of the operators parameter, address of the operators
panel for Series 0. panel for Series 0, is invalid.
WN03 ABORT NCWINDOW/EXIN 1) Check that the Ladder program is The Ladder program was stopped
free from problems and then restart during communication between the
the Ladder program (by pressing the CNC and PMC.Function instructions
RUN key). such as WINDR, WINDW, EXIN, and
2) Turn the CNC off and then back on. DISPB may not be executed normally.
WN05 PMC TYPE NO CONVERSION Using an offline programmer, change The setting of the type in the sequence
the sequence program to that for the program differs from the actual type.
correct PMC type. (Example: For the PMCSB5, the
Ladder program of the PMCSA3/SA5
was transferred.)
WN06 TASK STOPPED BY DEBUG To restart a user task that has been When a PMC C board is used, a user
FUNC stopped, stop the sequence program task has been stopped due to a break by
and then execute it again. a debug function.
WN07 LADDER SP ERROR (STACK) Modify the sequence program so that For a subprogram call with the function
the subprogram nesting level is eight or instruction CALL or CALLU, the nesting
less. level is too deep (exceeds 8).
WN17 NO OPTION (LANGUAGE) 1) Restore the backed up parameter When a PMC C board is used, no PMC
data. C program option is found.
2) Check the data sheet and reinput
the parameters.
3) Contact FANUC to specify a PMC C
program option of the necessary
size.

1431
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Alarm number Faulty location/corrective action Contents


WN18 ORIGIN ADDRESS ERROR 1) On the PMC system parameter When a PMC C board is used, the PMC
screen, press [ORIGIN]. system parameter, LANGUAGE
2) Set the PMC system parameter, ORIGIN, is invalid.
LANGUGE ORIGIN, to the address
indicated by the RC_CTLB_INIT in
the map file.
WN19 GDT ERROR (BASE,LIMIT) Modify the setting in the userdefined When a PMC C board is used, the
GDT in the link control statement or build BASELIMIT or ENTRY in the
file. userdefined GDT is invalid.
WN20 COMMON MEM. COUNT Change the number of shared When a PMC C board is used, the
OVER memories to eight or less.Modify the link number of shared memories exceeds
control statement, build file, or other eight.
source files for shared memories.
WN21 COMMON MEM. ENTRY Modify the ENTRY in the shared When a PMC C board is used, the
ERROR memory GDT in the link control ENTRY in the shared memory GDT is
statement. out of range.
WN22 LADDER 3 PRIORITY ERROR Change the value of the TASK LEVEL When a PMC C board is used, the
(LADDER LEVEL 3) in the link control priority of LADDER LEVEL 3 is out of
statement to 0, 10 to 99, or 1. range.
WN23 TASK COUNT OVER Change the TASK COUNT in the link When a PMC C board is used, the
control statement to 16 or less. number of user tasks exceeds 16.
(To change the task count, modify the
link control statement, build file, and the
configuration of the files to be linked.)
WN24 TASK ENTRY ADDR ERROR Change the GDT table in the build file to When a PMC C board is used, the user
32 (20H) to 95 (5FH) task entry address selector is out of
range.
WN25 DATA SEG ENTRY ERROR Change the DATA SEGMENT GDT When a PMC C board is used, the data
ENTRY value in the link control segment entry address is out of range.
statement and the GDT table in the build
file to 32 (20H) to 95 (5FH).
WN26 USER TASK PRIORITY Change the TASK LEVEL of each task When a PMC C board is used, the
ERROR in the link control statement to a value priority of the user task is out of range.
from 10 to 99 or 1. (Note that 1 can be
specified for the TASK LEVEL of only
one task, including the third Ladder
level)
WN27 CODE SEG TYPE ERROR Change the value of the code segment When a PMC C board is used, the code
according to the segment setting in the segment type is invalid. The setting of
link control statement and build file. the RENAMESEG code segment in
the bind control file is wrong.
WN28 DATA SEG TYPE ERROR Change the value of the data segment When a PMC C board is used, the data
according to the segment setting in the segment type is invalid. The setting of
link control statement and build file. the RENAMESEG data segment in the
bind control file is wrong.
WN29 COMMON MEM SEG TYPE Change the value according to the When a PMC C board is used, the
ERROR segment setting in the link control shared memory segment type is invalid.
statement and build file. The setting of the RENAMESEG
segment in the shared memory bind
control file is wrong.

1432
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

Alarm number Faulty location/corrective action Contents


WN30 IMPOSSIBLE ALLOCATE 1) Check that the USER GDT When a PMC C board is used, the
MEM. ADDRESS in the link control memory area for data, stacks, and
statement and the start address of others cannot be reserved.
the code segment in the build file are
correct.
2) Change the PMC system parameter,
MAX LADDER AREA SIZE, to a
minimum.
3) Change the stack size in the link
control state to a minimum.
WN31 IMPOSSIBLE EXECUTE 1) Check the types supported by the When a PMC C board is used, library
LIBRARY library. functions cannot be executed.
2) Reconfigure the PMC management
software and contact FANUC.
WN32 LNK CONTROL DATA ERROR 1) Check that the address of When a PMC C board is used, link
RC_CTLNB_INIT is set for the PMC control statement (program control)
system parameter, LANGUAGE data is invalid.
ORIGIN.
2) Create the link control statement
again.
WN33 LNK CONTROL VER.ERROR Modify the link control statement in the When a PMC C board is used, a link
PMC C program. control statement data edition error has
occurred.
WN34 LOAD MODULE COUNT Change the number of independent When a PMC C board is used, the
OVER load modules to eight or less. number of independent load modules
exceeds eight.
WN35 CODE AREA OUT OF RANGE Check the link map and allocate When a PMC C board is used, the code
segments within the range of RAM. segment area is out of the range of the
RAM.
WN36 LANGUAGE SIZE ERROR 1) Reduce the PMC C program. When a PMC C board is used, the PMC
(OPTION) 2) Contact FANUC to specify a PMC C C program exceeds the size specified
program option of a larger size. for the PMC C program option.
WN37 PROGRAM DATA ERROR Initialize the PMC C program memory. The PMC C program memory must be
(LANG.) ([EDIT] [CLEAR] [CLRLNG] initialized.
[EXEC])
WN38 RAM CHECK ERROR (LANG.) Replace the master printed circuit The initialization of the PMC C program
board. memory failed.
WN39 PROGRAM PARITY (LANG.) 1) Reinput the PMC C program. The parity of the PMC C program parity
2) Replace the master printed circuit is invalid.
board.
WN40 PROGRAM DATA ERROR BY Reinput the language program. While the PMC C program was being
I/O (LANG.) read, an interrupt command was
generated.
WN41 LANGUAGE TYPE UNMATCH 1) Reinput the PMC C program. When a PMC C board is used, an
2) Replace the master printed circuit unusable C program is input.
board.
WN42 UNDEFINE LANGUAGE 1) On the PMC system parameter When a PMC C board is used, the PMC
ORIGIN ADDRESS screen, click [ORIGIN]. parameter, LANGUAGE ORIGIN, is not
2) Set the PMC system parameter, set.
LANGUGE ORIGIN, to the address
indicated by the RC_CTLB_INIT in
the map file.
WN48 UNAVAIL LANGUAGE BY CNC Remove the PMC C board. A PMC C board is installed in a CNC in
UNMATCH which a PMC C board cannot be used.

1433
M. ALARM MESSAGE LIST APPENDIX B61863E/14

M.3
SYSTEM ALARM
MESSAGES
(PMCSC)
Message STATUS LED Contents and solution
PC1nn CPU INTERPT xxxx yyyyyy A CPU error (abnormal interrupt) occurred.
nn : CPU exception handling code
It is an exception code of i80386. For details, please refer to
the manual of the CPU.
00 Division error such as a divisor is 0 in division instruction.
12 Stack exception such as violations of limit of stack segment.
13 General protection exception such as segment limit over.
xxxx : Segment selector where system error occurred.
The selector of 010302FB is used by C language.
STATUS LED lL yyyyyy: Offset address where system error occurred.
PC130 RAM PARITY aa xxxx yyyyyy The parity error occurred on the debugging RAM of PMC.
aa : RAM PARITY ERROR information.
xxxx : Segment selector where system error occurred.
STATUS LED jL yyyyyy: Offset address where system error occurred.
PC140 NMI BOC bb xxxx yyyyyy The RAM parity error or NMI(Non Maskable Interrupt) generated in
module of PMC engine.
bb : RAM PARITY ERROR information.
1, 2, 4, 8 Parity error occurred on basic DRAM.
14, 18 Parity error occurred on option DRAM.
20, 60, A0, E0 Parity error occurred on SRAM.
xxxx : Segment selector where system error occurred.
STATUS LED LJ yyyyyy: Offset address where system error occurred.
PC150 NMI SLC aa cc The communication error occurred in the I/O Link.
aa, cc : I/O Link error information.
This error may occur by the following causes.
1.When I/O UnitMODEL A is used, base1, 2 or 3 is not connected
though allocated.
2.The connection of cable is insufficient.
3.Defects of cable.
4.Defects of DI/DO units (I/O unit, Power Mate etc.)
5.Defects of PMC board (printed circuit board on host side where I/O
Link cable is connected.)
(solution) Investigate the cause of error.
1.Please confirm the allocation data (by EDITMODULE screen)
and compare with the actual connection.
2.Please confirm whether the cable is correctly connected.
If you cannot find the cause with the ways above, it may be the defect
of hardware.
Please investigate a defective place by the following methods.
3.Please confirm the specification of the cable referring to FANUC I/O
UnitMODEL B connecting manuals(B62163E).
4.Exchange the interface module of I/O Unit, the cable and the PMC
board, etc. one by one and, confirm whether this error occurs again.
The communication may fail by the noise etc. when this error still
occurs after replacing all DI/DO units.
STATUS LED JL Please investigate the cause of noise.
PC160 FBUS ERROR xxxx:yyyyyyyy A bus error occurred on the PMC.
PC161 FBUS ERROR xxxx:yyyyyyyy xxxx : Segment selector for which a bus error occurred.
PC162 FBUS ERROR xxxx:yyyyyyyy yyyyyyyy : Offset address where a bus error occurred.
STATUS LED Lj
PC170 LBUS ERROR xxxx:yyyyyyyy A bus error occurred on the PMC.
PC171 LBUS ERROR xxxx:yyyyyyyy xxxx : Segment selector for which a bus error occurred.
PC172 LBUS ERROR xxxx:yyyyyyyy yyyyyyyy : Offset address where a bus error occurred.
STATUS LED Lj
PC199 ROM PARITY eeeeeeee The parity error occur in PMC system ROM.
STATUS LED Ll eeeeeeee : ROM parity error information.

1434
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

STATUS LED (green) are LED1, LED2 on PMCRC. CAPII is LED3


and LED4.
j : Off J : On lL : Blinking

NOTE
The system error on PMCSA1,SA2,SA3,SB,SB2 and SB3
is displayed as a system error on the CNC side.
(Refer to the FANUC Series 16MA Operators Manual
(B61874E) and FANUC Series 16TA Operators Manual
(B61804E).)

1435
M. ALARM MESSAGE LIST APPENDIX B61863E/14

M.4
SYSTEM ALARM
MESSAGES (C
LANGUAGE
FUNCTION FOR
PMCNB/NB2/NB6)
Message STATUS LED Contents and solution
RAM ERROR <a> bbcc xxxx: yyyyyyyy: PC010 The parity error occurs on the debugging RAM of PMC.
a : RAM which generates RAM parity.
B BASIC RAM
O OPTION RAM
S STATIC RAM
bb, cc : RAM PARITY information.
xxxx : Segment selector where system error occurred.
STATUS LED LJ or jL yyyyyyyy : Offset address where system error occurred.
ROM ERROR aaaaaaaa: PC020 The parity error occurs in PMC system ROM.
STATUS LED lL aaaaaaaa : ROM parity information
DIVIDE ERROR xxxx: yyyyyyyy: PC040 Division error occurs such as a divisor is 0 in the division instruction.
xxxx : Segment selector where system error occurred.
STATUS LED lL yyyyyyyy : Offset address where system error occurred.
BUS ERROR xxxx: yyyyyyyy: PC040 The BUS error (access on illegal address).
xxxx : Segment selector where system error occurred.
STATUS LED lL yyyyyyyy : Offset address where system error occurred.
STACK FAULT xxxx: yyyyyyyy: PC040 The stack exception such as the violation of the limit of the stack.
xxxx : Segment selector where system error occurred.
STATUS LED lL yyyyyyyy : Offset address where system error occurred.
GENERAL PROTECTION xxxx: yyyyyyyy: The general protection exception such as segment limit over was
PC040 generated.
xxxx : Segment selector where system error occurred.
STATUS LED lL yyyyyyyy : Offset address where system error occurred.
SLC ERROR aa (cc) : PC050 The communication error occurred in the I/O Link.
aa, cc : I/O Link error information.
This error may occur by the following causes.
1.When I/O UnitMODEL A is used, base1, 2 or 3 is not connected
though allocated.
2.The connection of cable is insufficient.
3.Defects of cable.
4.Defects of DI/DO units (I/O unit, Power Mate etc.)
5.Defects of PMC board (printed circuit board on host side where I/O
Link cable is connected.)
(solution) Investigate the cause of error.
1.Please confirm the allocation data (by EDITMODULE screen)
and compare with the actual connection.
2.Please confirm whether the cable is correctly connected.
If you cannot find the cause with the ways above, it may be the defect
of hardware.
Please investigate a defective place by the following methods.
3.Please confirm the specification of the cable referring to FANUC I/O
UnitMODEL B connecting manuals(B62163E).
4.Exchange the interface module of I/O Unit, the cable and the PMC
board, etc. one by one and, confirm whether this error occurs again.
The communication may fail by the noise etc. when this error still
occurs after replacing all DI/DO units.
STATUS LED JL Please investigate the cause of noise.

STATUS LED (green) are LED1, LED2 on PMCNB.

j : Off J : On lL : Blinking

1436
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

M.5
SYSTEM ALARM
MESSAGES
(PMCSB5/SB6/NB6)
Message Contents and solution
PC0nn CPU INTERRUPT xxxxxxxx CPU error

nn :Exception code
xxxxxxxx :Address at which an error occurred
PC004 CPU ERR xxxxxxxx:yyyyyyyy A CPU error occurred on the PMC.
PC006 CPU ERR xxxxxxxx:yyyyyyyy xxxxxxxx and yyyyyyyy represent an internal error code.
PC009 CPU ERR xxxxxxxx:yyyyyyyy
PC010 CPU ERR xxxxxxxx:yyyyyyyy This error may be caused by a main board failure.

(solution)
Replace the main board, then check if this error occurs again. If this error
still occurs, contact FANUC with the error status information (system con-
figuration, operation, error occurrence timing, error occurrence frequen-
cy, and so forth).
PC030 RAM PARITY aa:bb A RAM parity error occurred on the PMC.
aa and bb represent an internal error code.

This error may be caused by a main board failure.

(solution)
Replace the main board, then check if this error occurs again. If this error
still occurs, contact FANUC with the error status information (system con-
figuration, operation, error occurrence timing, error occurrence frequen-
cy, and so forth) and the internal error code above.
PC040 NMI BOC xxxxxxxx A nonmaskable interrupt (NMI) occurred in the PMC control module.

xxxxxxxx :Address at which an error occurred


PC050 NMI SLC (CHn) a0:d0 a1:d1 A communication error occurred on the I/O Link channel n.
or a0 and d0 represent an internal error code for the I/O Link channel 1.
PC050 I/O Link (CHn) a0:d0 a1:d1 a1 and d1 represent an internal error code for the I/O Link channel 2.

This error may occur as a result of one of the followings:


(1) When I/O Unit A is used, an I/O assignment is made for base expan-
sion, but no base is connected.
(2) Cables are not connected correctly.
(3) Cables are faulty.
(4) I/O devices (I/O Unit, Power Mate, and so forth) are faulty.
(5) Power failure of Master or Slave device on I/O Link
(6) Short circuit of DO terminal on I/O device
(7) The main board is faulty.

(solution)
(1) Check if the I/O assignment data matches the actual connections of
the I/O devices.
(2) Check if the cables are connected correctly.
(3) Check the cable specifications by referring to the FANUC I/O Unit
MODEL A Connection and Maintenance Manual (B61813E) or
FANUC I/O UnitMODEL B Connection Manual (B62163E).
(4) Replace the interface module, cables, and main board of the I/O Unit,
then check whether this error occurs again.
(5) Check the power line and stability of power for Master and Slave de-
vices.
(6) Check the connection of DO terminal line.

If this error still occurs after replacement of all the devices related to the
I/O Link according to Action (4), the communication error may have been
caused by noise. Attempt to identify the source of the noise.

1437
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Message Contents and solution


PC060 FBUS xxxxxxxx:yyyyyyyy A bus error occurred on the PMC.
PC061 FLR xxxxxxxx:yyyyyyyy aa, xxxxxxxx, and yyyyyyyy represent an internal error code.
PC062 FLW aa:xxxxxxxx:yyyyyyyy
This error may be caused by a hardware failure.

(solution)
Contact FANUC with the error status information (system configuration,
operation, error occurrence timing, error occurrence frequency, and so
forth), the internal error code above, and the LED statuses on each
board.
PC070 SUB65 CALL (STACK) A stack error occurred with the ladder functional instruction CALL/CAL-
LU.

(solution)
Check the correspondence between the CALL/CALLU instruction and
the SPE instruction. If the cause of the fault cannot be found, contact FA-
NUC with the error status information and the ladder program.
PC080 SYS EMG xxxxxxxx:yyyyyyyy A system alarm was issued due to other software.
PC081 FL EMG xxxxxxxx:yyyyyyyy
(solution)
Contact FANUC with the error status information (system configuration,
operation, error occurrence timing, error occurrence frequency, and so
forth), the internal error code above, and the LED statuses on each
board.
PC097 PARITY ERR (LADDER) A parity error occurred on the PMC system.
PC098 PARITY ERR (DRAM)
PC099 PARITY ERR (SRAM) This error may be caused by a main board failure.

(solution)
Replace the main board, then check whether this error occurs again. If
this error still occurs, contact FANUC with the error status information
(system configuration, operation, error occurrence timing, error occur-
rence frequency, and so forth).

1438
B61863E/14 APPENDIX M. ALARM MESSAGE LIST

M.6
PMC SYSTEM
ALARM MESSAGES
(PMCSB7)
Alarm number Faulty location/corrective action Contents
PC004 CPU ERR xxxxxxxx:yyyyyyyy 1) Replace the master printed circuit A CPU error occurred in the
PC006 CPU ERR xxxxxxxx:yyyyyyyy board. PMC.xxxxxxxx and yyyyyyyyy are
PC009 CPU ERR xxxxxxxx:yyyyyyyy 2) If the error recurs even after the internal error codes.
PC010 CPU ERR xxxxxxxx:yyyyyyyy replacement, contact FANUC to
PC012 CPU ERR xxxxxxxx:yyyyyyyy report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.)
PC030 RAM PARITY aa:bb 1) Replace the master printed circuit A RAM parity error occurred in the
board. PMC.aa and bb are internal error codes.
2) If the error recurs even after the
replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.) and the
above internal error codes.
PC050 NMI SLC aa:bb 1) Check that the I/O allocation data A communication error occurred in the
PC050 I/O LINK(CH_) aa:bb aa:bb matches the actual I/O device I/O LINK.
PC050 IOLINK CH_ aaaa connection. aa, bb and cc are internal error codes.If
bbbb:cccc 2) Check that the cable is connected this alarm is generated, probable
properly. causes include the following:
3) Check the cable specifications. 1) Although the base expansion is
4) Replace the I/O device interface assigned when the I/O Unit A is
module, cable, master printed circuit used, the base is not connected.
board, etc. 2) A cable is not connected securely.
3) Cabling is faulty.
4) I/O equipment (I/O unit, Power Mate,
etc.) is faulty.
5) Power failure of Master or Slave
device on I/O Link.
6) Short circuit of DO terminal on I/O
device.
7) The motherboard is faulty.
PC060 FBUS xxxxxxxx:yyyyyyyy 1) Replace the master printed circuit A bus error occurred in the PMC.
PC061 FLR xxxxxxxx:yyyyyyyy board.
2) If the error recurs even after the
replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.)
PC070 SUB65 CALL (STACK) Check the correspondence between A stack error occurred in Ladder
the CALL/CALLU and SPE instructions function instruction CALL/CALLU.
PC090 NMI(___) xxxxxxxx:yyyyyyyy 1) Replace the master printed circuit An NMI with an unknown cause
board. occurred in the PMC management
2) If the error recurs even after the software.
replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.)

1439
M. ALARM MESSAGE LIST APPENDIX B61863E/14

Alarm number Faulty location/corrective action Contents


PC092 USER TRAP aa:xxxxxxxx 1) Replace the master printed circuit The TRAP instruction, which is not used
board. in the PMC management software, was
2) If the error recurs even after the executed.
replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.)
PC093 INT(SYS) xxxxxxxx:yyyyyyyy 1) Replace the master printed circuit An interrupt with an unknown cause
PC094 INT(TRAP) xxxxxxxx:yyyyyyyy board. occurred in the PMC management
PC095 INT(EX) xxxxxxxx:yyyyyyyy 2) If the error recurs even after the software.
PC096 INT(IN) xxxxxxxx:yyyyyyyy replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.)
PC087 PARITY ERR (LADDER2) 1) Replace the master printed circuit An error occurred in a RAM check.
PC097 PARITY ERR (LADDER) board.
PC098 PARITY ERR (DRAM) 2) If the error recurs even after the
replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.).
PC501 NC/PMC INTERFACE ERR 1) Replace the master printed circuit The reading/writing of signals between
PATH_ board. the CNC and the PMC failed.
2) If the error recurs even after the
replacement, contact FANUC to
report the status (displayed
message, system configuration,
operation, when the error occurs,
occurrence frequency, etc.)
PC502 ILLEGAL FUNCTION (SUB xx) Modify the sequence program so that Unsupported function instruction xx is
instruction function xx is not used. used.

1440
N. EXAMPLE OF STEP SEQUENCE
B61863E/14 APPENDIX PROGRAMS

N EXAMPLE OF STEP SEQUENCE PROGRAMS

The CNC is connected two or three Power Mate units.

CNC Connection Unit.

I/O Unit

X0.0:Safety switch Y0.0:Safety switch


Y1.0:Ready end#1
Y1.1:Drive start#1
Y2.0:Ready end#2
Y2.1:Drive start#2
Y3.0:Ready end#3
Y3.1:Drive start#3

Power Mate #1

X100.0:Ready end#1 Y100.0:Emergency#1


X100.1:Driving#1 Y100.1:Drive start#1

Power Mate #2

X110.0:Ready end#2 Y110.0:Emergency#2


X110.1:Driving#2 Y110.1:Drive start#2

Power Mate #3

X120.0:Ready end#3 Y120.0:Emergency#3


X120.1:Driving#3 Y120.1:Drive start#3

NOTE
The addresses indicate the single addresses, as viewed
from the CNC.

The CNC controls the Power Mate units at the following signal timing.

Ready end #1
(Power Mate to CNC)

Drive start #1
(CNC to Power Mate)
1sec 1sec

Driving #1
(Power Mate to CNC) 1sec

1441
N. EXAMPLE OF STEP SEQUENCE
PROGRAMS APPENDIX B61863E/14

The following flowchart illustrates the interface with the Power Mate
units.

CNC Power Mate x

When the ready and signal is off,


the driving start common is not sent.

The start signal (STx) is set on.


STx

The start signal (STx) is set off


after 1 second.
STx

Start moving by the start signal and


the DEN signal (DENx) is set on for
CNC.
DENx
When the moving finishes, the NC
program is rewound and the DEN
signal (DENx) is set off.

DENx

Waiting for that the moving


finishes.

Finished

The interface with the Power Mate units is changed to the Step Sequence
program.

Step Sequence for the Power Mate

Dummy Step

Ready end Ready

The start signal is set on. finished

Wait for 1 second.

The start signal is set off.

Wait for that the TIMER finishes.

The moving status is set the LED.

Wait for that the moving finishes.

finished

1442
N. EXAMPLE OF STEP SEQUENCE
B61863E/14 APPENDIX PROGRAMS

Example 1 The Step sequence program for three sequentially driven Power Mate
units:

Main program

L1
The input signal is set the LED.

The input signal is 1 (true).


Drive Power Mate#1

Dummy trasition
Drive Power Mate#2

Dummy trasition

Drive Power Mate#3

Dummy trasition

Start the timer.

Wait for one second.

Clear the timer.


Wait for that the timer finishes.

L1

1443
N. EXAMPLE OF STEP SEQUENCE
PROGRAMS APPENDIX B61863E/14

Example 2 The Step Sequence program for three simultaneously driven Power Mate
units:

Main program

L1
The input signal is set the LED.

The input signal is 1 (true).

Drive Power Drive Power Drive Power


Mate#1 Mate#2 Mate#3

Dummy trasition

Start the timer.

Wait for one second.

Clear the timer.

Wait for that the timer finishes.

L1

1444
O. STEP SEQUENCE CORRESPONDED
B61863E/14 APPENDIX C LANGUAGE

O STEP SEQUENCE CORRESPONDED C LANGUAGE

1445
O. STEP SEQUENCE CORRESPONDED
C LANGUAGE APPENDIX B61863E/14

O.1 The operation is continued while the condition is true.


WHILE STATEMENT
Format

L1
condition

The condition is false. The condition is true.


operation

Operation finished.

L1

1446
O. STEP SEQUENCE CORRESPONDED
B61863E/14 APPENDIX C LANGUAGE

Examples

L1
S1
(P10)

P11 P12
S2
(P20)
P21

L1

P10

P11
R9091.1
COMPB 1
30
R10
R9000.0
TRSET

P12
R9091.1
COMPB 1
30
R10
R9000.0
TRSET

P20
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 5
R12

R9091.0
R0.0
ADDB 1 ( )
R10
R9091.1 1
R10

P21
R9091.1
TRSET

1447
O. STEP SEQUENCE CORRESPONDED
C LANGUAGE APPENDIX B61863E/14

O.2 The operation is continued while the condition is true after executing the
operation.
DOWHILE
STATEMENT The difference between dowhile and while is that the operation is
executed at least one time.

Format
L1
operation

condition

The condition is false. The condition is true.

L1

1448
O. STEP SEQUENCE CORRESPONDED
B61863E/14 APPENDIX C LANGUAGE

Examples

L1
S1
(P20)
P21
S2
(P10)

P11 P12

L1

P10

P11
R9091.1
COMPB 1
30
R10
R9000.0
TRSET

P12
R9091.1
COMPB 1
30
R10
R9000.0
TRSET

P20
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 5
R12

R9091.0
R0.0
ADDB 1 ( )
R10
R9091.1 1
R10

P21
R9091.1
TRSET

1449
O. STEP SEQUENCE CORRESPONDED
C LANGUAGE APPENDIX B61863E/14

O.3 After the initial data is set, the operation is continued while the condition
is true.
FOR STATEMENT
Format
Set the initial data.

L1
operation

condition

The condition is false. The condition is true.

L1

1450
O. STEP SEQUENCE CORRESPONDED
B61863E/14 APPENDIX C LANGUAGE

Examples
S1
(P1)
P2

L1
S2
(P20)
P21
S3
(P10)

P11
P12
L1
P1
R9091.1
NUMEB 1
0
R10

P2
R9091.1
TRSET

P20
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 5
R12

P21
R9091.1
TRSET

P10
R9091.0
R0.0
ADDB 1 ( )
R10
R9091.1 1
R10

P11
R9091.0
COMPB 1
30
R10
R9000.0
TRSET

P21
R9091.0
COMPB 1
30
R10
R9000.0
TRSET

1451
O. STEP SEQUENCE CORRESPONDED
C LANGUAGE APPENDIX B61863E/14

O.4 If the condition is true, the operation 1 is executed and if the condition is
false, the operation 2 is executed.
IF ELSE STATEMENT
Format
condition

The condition is true. The condition is false.

operation1 operation2

1452
O. STEP SEQUENCE CORRESPONDED
B61863E/14 APPENDIX C LANGUAGE

Examples
S1
(P10)

P11 P12

S2 S3
(P20) (P22)
P21 P23

P1
0

P1
1
R9091.0
COMPB 1
30
R10
R9000.0
TRSET

P12
R9091.0
COMPB 1
30
R10
R9000.0
TRSET

P20
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 8
R12

P21
R9091.1
TRSET

P22
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 10
R12

P23
R9091.1
TRSET

1453
O. STEP SEQUENCE CORRESPONDED
C LANGUAGE APPENDIX B61863E/14

O.5 The operation connected to the condition is executed.


SWITCH STATEMENT
Format
condition

condition1 condition2 condition3


operation1 operation2 operation3

1454
O. STEP SEQUENCE CORRESPONDED
B61863E/14 APPENDIX C LANGUAGE

Examples
S1
(P10)

P11 P12 P13


S2 S3 S4
(P20) (P22) (P24)
P21 P23 P25

P1
0

P1
1
R9091.1
COMPB 1
30
R10
R9000.0
TRSET

P12
R9091.0
COMPB 1
40
R10
R9000.0
TRSET

P13
R9091.1
TRSET

P20
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 5
R12

P21
R9091.1
TRSET

P22
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 10
R12

1455
O. STEP SEQUENCE CORRESPONDED
C LANGUAGE APPENDIX B61863E/14

P23
R9091.1
TRSET

P24
R9091.0
R0.0
MULB 1 ( )
R10
R9091.1 15
R12

P25
R9091.1
TRSET

1456
P. CHINESE CHARACTER CODE, HIRAGANA
B61863E/14 APPENDIX CODE, AND SPECIAL CODE LIST

P CHINESE CHARACTER CODE, HIRAGANA CODE, AND


SPECIAL CODE LIST

Pronun Shift Segment and point


JIS
ciation JIS 0 1 2 3 4 5 6 7 8 9 A B C D E F

hThe characters with mark h cannot be displayed on FANUC Series 16/18MODEL A.

1457
P. CHINESE CHARACTER CODE, HIRAGANA
CODE, AND SPECIAL CODE LIST APPENDIX B61863E/14

Pronun Shift Segment and point


JIS
ciation JIS 0 1 2 3 4 5 6 7 8 9 A B C D E F

shows the character which is impossible to display.

1458
P. CHINESE CHARACTER CODE, HIRAGANA
B61863E/14 APPENDIX CODE, AND SPECIAL CODE LIST

Pronun Shift Segment and point


JIS
ciation JIS 0 1 2 3 4 5 6 7 8 9 A B C D E F

shows the character which is impossible to display.

1459
P. CHINESE CHARACTER CODE, HIRAGANA
CODE, AND SPECIAL CODE LIST APPENDIX B61863E/14

Pronun Shift Segment and point


JIS
ciation JIS 0 1 2 3 4 5 6 7 8 9 A B C D E F

shows the character which is impossible to display.

1460
P. CHINESE CHARACTER CODE, HIRAGANA
B61863E/14 APPENDIX CODE, AND SPECIAL CODE LIST

Pronun Shift Segment and point


JIS
ciation JIS 0 1 2 3 4 5 6 7 8 9 A B C D E F

93BE

shows the character which is impossible to display.

1461
P. CHINESE CHARACTER CODE, HIRAGANA
CODE, AND SPECIAL CODE LIST APPENDIX B61863E/14

Pronun Shift Segment and point


JIS
ciation JIS 0 1 2 3 4 5 6 7 8 9 A B C D E F

shows the character which is impossible to display.

1462
B61863E/14 Index
A C
About connection log of Ethernet, 603, 897 C input/output, 556
About the FS15i PMCNB6 programmer, 498 CALL (conditional subprogram call), 330

About the FS16i/18i/21iB PMCSA1/SB7 programmer, 498 Calling screen, 832

ADD (addition), 239 CALLU (unconditional subprogram call), 331


Caution screen of the setting parameter for the selectable I/O link
ADDB (binary addition), 241 assignment function, 795
Addition of system keep relays, 788, 790 Cautions for subroutines, 378
Addition of system parameter ladder execution time, 1415 Chinese character code, Hiragana code, and special code list, 1457
Additions to sequence programs, 1025 Clearing the PMC parameter, 545
Address, 59 Clearing the sequence program, 412, 544
Address change of sequence program, 532 Clearing the sequence program and condensation of the sequence
program, 544
Address of counter (C), 104
CNC Offline Programmer, 1403
Address of data table (D), 108 COD (code conversion), 189
Address of keep relay and nonvolatile memory control (K), 106 CODB (binary code conversion), 192
Addresses, 363 Coding (step 5), 38
Addresses between PMC and CNC (PMCNC), 74 COIN (coincidence check), 220
Addresses between PMC and machine tool, 75 Collation of program, 1017
Addresses between PMC and machine tool (PMCMT), 75 Collation of source programs, 1017
Addresses for message selection displayed on CRT (A), 102 Collective monitor function, 747

Addresses, signal names, comments, and line numbers, 363 Collective monitor function (PMCSB7), 831

Alarm message (PMCPA1/PA3/SA1/SA2/SA3/SA5/SB/ COM (common line control), 197


SB2/SB3/SB4/SB5/SB6/SC/SC3/SC4/NB/NB2/NB6), 1422 COME (common line Control end), 203
Alarm message (PMCSB7), 1429 Comments, 364
Alarm message and countermeasure, 837, 858 Communication Status, 602
Alarm message list, 1421 Communication status, 895
Alarm screen (ALARM), 428, 639 COMP (comparison), 216

ALLOW PMC STOP (PMCSB7: K902.2, PMCSA1: K19.2), 799 Comparison with the function of FS15B (PMCNB/NB2), 650
Compatibility of ladder diagram, 963
Alter, 997
Compatibility with CNC basic software, 1389
Alteration of sequence programs, 524
Compatibility with Series 21MODEL B, 1420
AND, 122
Compatible with Series 0, 1416
AND. NOT, 122
COMPB (comparison between binary data), 218
AND. STK, 125
Component units, 500, 971, 1391
Applicable FANUC ladder editions, 1396
Component units and connections, 499, 970, 1390
Applications, 371 Compress the sequence program, 545
Arbitrary functional instructions, 294 Compressed input by [COMAND] key, 1034
Area managed by the system program, 97 Condense, 1393
Assignment of I/O module addresses, 77 Condense command release of deleted area, 1045
Automatic operation when the power is turned on, 412 Configuration and operation of stepsequence programs, 922
Automatic start of trace setting, 874 Configuration of command, 1042

Automatic tracing function at power on, 431 Confirming the ladder mnemonics, 614

AXCTL (axis control by PMC), 337 Connecting component units, 505


Connecting the I/O card, 1382
Connecting the I/O unit, 1382
Connecting the operators panel for FS 0 with FS16, FS18, FS21, or
B Power Mate, 1378

Block step, 931 Connection, 1382

Brief screen, 826 Connection of components, 1392


Connections of units, 972

i1
Index B61863E/14

Continuous data entry, 665 Detail screen, 824


Convergence of selective sequence, 927 Details of basic instructions, 116
Convergence of simultaneous sequence, 929 DIFD (falling edge detection), 306
Conversion, 1376 Difference of status of signals between 1st level and 2nd level, 53
Copy a ladder program [CPYLAD], 575 DIFU (rising edge detection), 305
Copy I/O module data [CPYMDL], 576 Direct editing by ladder diagram, 1020
Copy message data [CPYMSG], 575 DISP (message display) (PMCSB/SB2/SB3/SB4/SB5/SB6/SC/
SC3/SC4 Only), 258
Copy symbol data and comment data [CPYSYM], 575
DISPB, 272
Copy the sequence programs [CPYALL], 576
Display format for parameters, 818
Copy title data [CPYTTL], 575
Display of ladder diagram, 1003
Copying a sequence program, 1031
Display of signal status (STATUS), 427
Copying message data (COPY), 543
Display PMC input/output signals and internal relay (PMCDGN),
Copying the sequence program, 530 635
Corresponding function, 962 Displayed items, 583
Counter screen (COUNTR), 464, 667 Displaying and setting the configuration status of I/O devices
(IOCHK), 442
Creating a program, 376
Displaying input code (DSPMOD), 543
Creation of interface specifications (steps 1 to 3), 37
Displaying of sequence program, 947
Creation of ladder diagram (step 4), 37
Displaying the contents of memory, 432
Cross reference display, 546
Displaying the GDT (global descriptor table), 578
CRT/MDI operation, 946
Displaying the memory allocation information of a user program
CTR (counter), 172 Coded in C., 581
CTRB (fixed counter), 178 Displaying the running state of a user task (USRDGN), 440
CTRC (counter), 180 Displaying title data, 425
Distribution I/O connection I/O module and distribution I/O opera-
tors panel I/O module assignment methods, 89

D DIV (division), 251


DIVB (binary division), 253
Data display and setting (title, symbol, ladder program, comment,
message, I/O module), 990 Divergence of selective sequence, 927

Data input to and output from other devices, 569 Divergence of simultaneous sequence, 928

Data keys and screen scroll key, 978 Dividing display of ladder diagram, 489

Data number, data attribute, data length, data area, 1368 Dowhile statement, 1448

Data table (DATA), 470, 670 DSCH (data search), 224

DATA TBL CNTL SCREEN (PMCSB7: K900.7, PMCSA1: DSCHB (binary data search), 227
K17.7), 800 DUMP display on ladder diagram, 481
Data transfer between NB (4047 series) and FANUC LADDER,
1408
Data transfer between NB (4047 series) and NB (4048 series), 1409
Data transfer between NB/NB2 (4048 series) and FANUC LADDER,
E
1408 EDIT ENABLE (PMCSB7: K901.6, PMCSA1: K18.6), 799
DCNV (data conversion), 212 Editing a character string in message data, 542
DCNVB (extended data conversion), 214 Editing character strings of symbol data and comment data, 539
Debugging, 584 Editing character strings of title data, 517
DEC (decode), 167 Editing end, 1004
DECB (binary decoding), 169 Editing for Power MateMODEL D (PMCPA1/PA3), 1388
Delete, 1001 Editing function of ladder diagram, 957
Delete of sequence program, 527 Editing ladder mnemonics, 613
Delete of symbol data and comment, 538 Editing of sequence program (EDIT), 515
Deleting a sequence program, 1028 Editing symbol data and comment at once, 532
Deleting title data, 516 Editing the sequence program (EDIT), 612
Deletion of programs, 1018 Emergency stop signal (*ESP), 1383
Descriptions of displayed items, 580 Enabling automatic debugging at poweron, 588

i2
B61863E/14 Index

END (end of a ladder program), 329 For the FS16 (PMCSC or PMCSC3), 493
End of block step, 932 Forced input/output function, 449
END1 (1st level sequence program end), 157 Forcibly stopping the sequence program, 553
END2 (2nd level sequence program end), 158 Format and details of the control data of the WINDR functional
instruction, 1256
END3 (end of 3rd level sequence) (PMCSC/SC3/SC4/NB/
NB2/NB6/NB7 only), 159 Format and details of the control data of the WINDW functional
instruction, 1309
Ending edit of a sequence program, 1034
Formats and details of control data, 1059
Ending ladder mnemonics editing, 618
FS15i PMCNB6 operating procedure, 413
Entering data on the program check screen (*lowspeed response)
(not available for Power MateD/F, Series 21TA), 1141 FS16iLA assignment, 88

Entering title data, 516 FS16i/18i/21iB PMCSA1/SB7 operating procedure, 413


Function, 374, 1055, 1250, 1332, 1376
Entering torque limit data for the digital servo motor (*lowspeed
response), 1145 Function for displaying signal waveforms (ANALYS), 434
EOR (exclusive OR), 307 Function for storing data in memory, 433
Error codes list (for FANUC Ladder PG), 1051 Function of copying symbol and comment data, 540
Error details, 622 Functional instruction data table editor screen, 854
Error list, 626 Functional instruction data table viewer screen, 821
Error messages (for EDIT), 605 Functional instruction list screen, 853
Error messages (for I/O), 607 Functional instruction TRSET, 934
Error messages (for ladder mnemonics editing), 620 Functional instruction WINDR, 1252

Example, 879 Functional instruction WINDW, 1254

Example for setting parameters, 801 Functional instructions, 130

Example of step sequence programs, 1441 Functions for displaying memory areas and debugging the program
(MONIT), 577
Examples of structured programming, 370 Functions of processing, 968
Exclusive control for functional instructions, 943
Execution method, 375
Execution of a sequence program, 551 G
Execution of step sequence, 918
General rules, 937
Execution of Trace, 647
Graphical symbols, 905
Execution of trace, 870
Execution procedure of sequence program, 42
Execution time, 396 H
EXIN (external data input), 283
Help screen, 1004
Expansion of symbol size, 790
HIDE PMC PROGRAM (PMCSB7: K900.0, PMCSA1: K17.0),
Extended ladder instructions, 933 798
How to pick up a ladder diagram net, 750
How to set at NC parameter, 597

F How to set at NC parameter (Power MateD/H), 598


How to set at PMC screen, 596, 889
F keys (F1 to F0), 976
FANUC LADDER (system P series), 1399
FANUC LADDER system floppy loading, 985
FANUC LADDER, FANUC LADDERII, FANUC LADERIII,
I
ladder editing packages, FANUC LADDERIII (IBM PC/AT) I/O error messages, 573
A08B9210J505, ladder editing package (windows) (IBM PC/
AT) A08B9210J511, 1397 I/O Link connecting check screen, 444

FDLIST command file attribute display, 1043 I/O link connecting check screen, 886

File editing function, 1038 I/O Link connection unit assignment, 84

Floppy list screen, 773 I/O LinkII parameter setting screen, 446
I/O screen, 757
For MDI Units other than Standard MDI Units (for FS20 PMCSA1
and SA3), 412 I/O screen error messages (PMCNB6), 779
For statement, 1450 I/O signals to CNC, 52
For the FS15 (PMCNB), 493 I/O unit address setting (MODULE), 534

i3
Index B61863E/14

I/O Unit MODEL B assignment, 86 Ladder diagram display, 480


If else statement, 1452 Ladder diagram editor function (PMCSB7), 838
Implementation techniques, 370 LADDER diagram editor screen, 702
Infinite number of relay contacts, 367 Ladder diagram format, 362, 366
Initial block step, 932 LADDER diagram monitor (PMCSB7), 803
Initial step, 925 Ladder diagram monitor and editor, 678
Input of program, 1005 LADDER diagram monitor screen, 681, 805
Input PMC parameters from MDI panel, 462 Ladder password function, 414
Input signal processing, 51 Ladder screen, 950, 960
Input with a katakana identification code, 543 Lader diagram editor screen, 839
Input/outpupt signal processing, 395 LBL (label), 336

Input/output ladder/PMCparameter by MDI/DPL, 623 Level up of input/output function with memory card, 1401

Input/output method to FANUC FLOPPY CASSETTE (fixed Limitations in SYSTEM P Mate, 1020
4800bit/sec.), 623 Limitations with the SYSTEM P Mate, 984
Input/output method to office programmer (Pg Mate/Mark II) (fixed Limited function, 1420
9600bit/sec.), 623
Line numbers, 364
Input/output of ladder program with PG and floppy cassette/FA
card, 1035 List of window functions, 1056
Inputting a multibyte character (D.CHAR), 543 LOAD key (system program loading key), 976
Insert, 1000 Loading of floppy, 984
Insert of sequence program, 524 Loading the standard ladder (for Power MateD/F PMCPA1 and
PA3), 413
Interlocking, 54
Location search, 1001
Internal relay addresses (R), 95
Logical AND, 309
Interrupt enable/disable/clear, 396
Logical OR, 311
Interrupt processing, 394
Lowspeed response and highspeed response of window function,
Interrupt program, 394 1055, 1251
Interrupttype PMC function, 391
IO GROUP SELECTION (K906.1), 800
M
Memory card list screen, 764
J Message data input, 542
JMP (jump), 204 Message data setting (MESSAGE), 541
JMP Instructions with Label Specification, 380 Method for entering PMC parameters, 664
JMPB (label jump), 334 Migration from the PMCNB/NB2 to the PMCNB6, 1413
JMPC (label jump), 335 Migration from the PMCSA5/SB5/SB6 to the PMCSB7, 1414
JMPE (jump end), 209 Migration from the Series 0 and Series 21B to Series 0i, 1416
Jump, 930 Migration of ladder programs between different models, 1410
Migration of ladder programs from Power MateD/H to Power Mate
iD/H, 1411
Miscellaneous item, 368
K MMC3 R (MMCIII window data read), 315
Keep relay (KEEPRL), 464 MMC3W (MMCIII window data write), 318
Keep relay screen (KEEPRL), 668 MMCWR (reading MMC window data) (other than PMCPA1/PA3),
Key switch signals (Xn, Xn+2), 1383 297

Keyboard of system P series, 975 MMCWW (writing MMC window data) (other than PMCPA1/PA3),
299
Modification procedure, 1377
Modifying the converted sequence program, 1377
L Modifying the ladder mnemonics, 616
Label, 930 Modifying the values of signals by forced input/output, 457
Label addresses (JMPB, JMPC, LBL) (L), 112 Monitor time screen, 955
Ladder debugging function, 589 Monitoring elapsed time, 954

i4
B61863E/14 Index

MOVB (transfer of 1 byte), 301 Override signals (*OV1 to *OV8) and program protect key signal
(KEY), 1383
MOVD (transfer of 4 bytes), 304
MOVE (logical product transfer), 194
Moving a sequence program, 1032
Moving the sequence program, 531
P
Paper command, 1013
MOVN (transfer of an arbitrary number of bytes), 303
Parameter, 1392
MOVOR (data transfer after logical sum), 196
Parameter display on ladder diagram, 482
MOVW (transfer of 2 bytes), 302
Parameter menu, 1386
MUL (multiplication), 247
Parameter screen, 435, 585
MULB (binary multiplication), 249
Parameter setting and display, 987
Multiple data input, 462
Parameter setting screen, 429, 547
PARI (parity check), 210
Password and switching screen, 754
N Password protection, 752
NB/NB2 data compatibility, 1408 PMC address (S ADDRESS), 934
Net editor screen, 846 PMC basic instructions, 114
Nonvolatile memory, 353 PMC basic manu, 631
NOP (no operation), 351 PMC data setting and display (PMCPRM), 662
NOT (logical NOT), 313 PMC data table, 357
Notes, 883 PMC I/O signal display and internal relay display (PMCDGN), 424
Notes on using an MDI keyboard without cursor keys (when using PMC ladder diagram display (PMCLAD), 479
the FS20 PMCMODEL SA1/SA3), 572
PMC menu selection procedure by softkey, 418
NUME (definition of constant), 255
PMC operation for loader control function, 417
NUMEB (definition of binary constants), 256
PMC parameters setting and display (PMCPRM), 460
PMC programmer (CRT/MDI or PDP/MDI) [ladder editing function],
1390

O PMC programmer (DPL/MDI) (only for the Power MateD/F/H),


608
Offline Programmer CNC, 1405 PMC screen transition and related soft keys, 633
Online debugging function (only for Power MateD/H), 624 PMC system alarm messages (PMCSB7), 1439
Online edit, 490 Port setting screen, 777
Online function, 594, 887 Power Mate assignment, 87
Online function by Ethernet, 891 Preparation before operation, 984
Online function by ethernet, 599 Priority of execution (1st level, 2nd level and 3rd level), 44
Online setting screen, 595, 888 Procedure, 1386
Operation, 429, 432, 434, 546, 578, 581, 584, 981, 1403 Processing I/O signals, 50
Operation after execution of trace, 648, 871 Program collation, 1037
Operations, 559, 808, 822, 827 Program configuration list (main screen), 947, 957
OR, 122 Program editing, 990
OR. NOT, 122 Program input, 1035
OR. STK, 125 Program list editor screen, 742, 855
Other setting screens, 475 Program list viewer screen, 735, 824
Other window functions, 1374 Program output, 1036
Outline, 876 PROGRAMMER ENABLE (PMCSB7: K900.1, PMCSA1:
K17.1), 798
Outline of leveled up contents, 1402
Programmer menu screen, 986
Output of program, 1010
Programmer protection function, 797
Output signal processing, 51
Programming, 906
Outputting to and inputting from flash ROM, 766
Programming from keyboard, 996
Outputting to and inputting from floppy, 769
PSGN2 (position signal output 2), 347
Outputting to and inputting from memory cards, 760 PSGNL (position signal output), 343
Outputting to and inputting from other input/output devices, 774

i5
Index B61863E/14

R Reading set data (not available for Power MateD/F, Series 21TA),
1151
R keys (R0 to R3), 977 Reading setting data, 1352
RAM WRITE ENABLE (PMCSB7: K900.4, PMCSA1: K17.4), Reading setting data (*lowspeed response), 1074
800
Reading signals automatically at power on, 439
RD, 118
Reading the absolute position (absolute coordinates) of controlled
RD. NOT, 119 axes, 1094
RD. NOT. STK, 124 Reading the absolute position on a controlled axis, 1264
RD. STK, 123 Reading the acceleration/deceleration delay on controlled axes,
1102, 1268
Reading a character string of the CNC program being executed in the
buffer, 1153 Reading the actual spindle speed, 1139
Reading a custom macro variable (*lowspeed response), 1078 Reading the actual velocity of controlled axes, 1092
Reading a custom macro variable (lowspeed response), 1260 Reading the actual velocity of controlled axes (lowspeed response),
1264
Reading a parameter (*lowspeed response), 1070
Reading the CNC alarm status, 1083, 1356
Reading a parameter (not available for Power MateD/F, Series
21TA), 1150 Reading the CNC alarm status (lowspeed response), 1261
Reading a parameter (setting data) (lowspeed response), 1259 Reading the current program number, 1088
Reading a skip position (stop position of skip operation (G31)) of Reading the current program number (8digit program numbers)
controlled axes, 1098 (not available for Power MateD/F, Series 21TA), 1193
Reading a skip position (stop position of skip operation (G31)) of Reading the current program number (lowspeed response), 1262
controlled axes (lowspeed response), 1267
Reading the current screen number, 1242
Reading a tool offset, 1062 Reading the current sequence number, 1090
Reading a tool offset (lowspeed response), 1256 Reading the current sequence number (lowspeed response, 1263
Reading a workpiece origin offset value, 1258 Reading the estimate disturbance torque data, 1189
Reading a workpiece origin offset value (not supported by the Power Reading the load current (A/D conversion data) for the spindle mo-
MateD or F), 1066 tor, 1293
Reading A/D conversion data, 1111 Reading the machine position (machine coordinates) of controlled
Reading A/D conversion data for the feed motor, 1276 axes, 1096, 1266

Reading actual spindle speeds, 1213 Reading the machining time (lowspeed response), 1292

Reading an estimate disturbance torque data, 1291 Reading the measured point, 1362
Reading the parameter (*lowspeed response), 1345
Reading and writing of nonvolatile memory data, 356
Reading the relative position on a controlled axis, 1155, 1289
Reading and writing the laser command data and laser setting data,
1337 Reading the remaining travel, 1157, 1290
Reading clock data (date and time) (not available for Power MateF), Reading the servo delay for controlled axes, 1100, 1268
1143
Reading the tool life management data (number of tool groups)
Reading clock data (lowspeed response), 1288 (lowspeed response), 1279
Reading CNC status information, 1159 Reading the tool life management data (tool group number) (low
speed response), 1278
Reading CNC system information, 1060
Reading the tool life management data (tool life counter type) (not
Reading detailed alarm information (*lowspeed type), 1245 available for Power MateD/F, Series 21TA), 1165
Reading diagnosis data (*lowspeed response), 1109 Reading the tool offset data according to the specified tool number,
Reading diagnosis data (lowspeed response), 1275 1294
Reading the wire diameter offset, 1341
Reading diagnosis data (not available for Power MateD/F, Series
21TA), 1152 Reading tool lefe management data (cutter compensation number 1)
(lowspeed type), 1297
Reading fine torque sensing data (statistical calculation results), 1217
Reading tool life management data (cutter compensation No. (1):
Reading fine torque sensing data (store data), 1219 tool No.) (not available for Power MateD/F, Series 21TA), 1129
Reading load information of the spindle motor (serial interface), Reading tool life management data (cutter compensation No. (2):
1147 tool order No.) (not available for Power MateD/F, Series 21TA),
Reading machining distances, 1361 1131

Reading modal data, 1104 Reading tool life management data (cutter compensation No.1) (low
speed response), 1284
Reading modal data (lowspeed response), 1269
Reading tool life management data (cutter compensation No.2) (low
Reading model data, 1357 speed response), 1285
Reading of the comment, 1336 Reading tool life management data (number of tool groups) (not
available for Power MateD/F, Series 21TA), 1117
Reading of tool setting data, 1366
Reading tool life management data (number of tools) (lowspeed
Reading real parameters (lowspeed type), 1299 response), 1279

i6
B61863E/14 Index

Reading tool life management data (number of tools) (not available RST, 128
for Power MateD/F, Series 21TA), 1119
Reading tool life management data (tool diameter offset number 1)
(not available for Power MateD/F, Series 21TA), 1199
Reading tool life management data (tool group No.) (not available S
for Power MateD/F, Series 21TA), 1115
Scratch command deletion of files, 1045
Reading tool life management data (tool group number) (not avail-
able for Power MateD/F, Series 21TA), 1195 Screen configuration, 833, 840, 846

Reading tool life management data (tool group numbers) (lowspeed Screen display, 454
type), 1295 Screen for displaying general settings (GENERAL), 673
Reading tool life management data (tool information (1) : tool No.) Screen for displaying setting data related to C language function, 677
(not available for Power MateD/F, Series 21TA), 1133
Screen for displaying the setting data related to editing and debug-
Reading tool life management data (tool information (2): tool order ging, 674
No.) (not available for Power MateD/F, Series 21TA), 1135
Screen for displaying traced data, 588
Reading tool life management data (tool information 1) (lowspeed
response), 1286 Screen for setting/displaying online monitor parameters (ONLINE),
675
Reading tool life management data (tool information 1) (lowspeed
type), 1298 Screen of ladder debugging function, 589
Reading tool life management data (tool information 1) (not avail- Screen operation for PMCSA1, 788
able for Power MateD/F, Series 21TA), 1201
Screen operation for PMCSA1/SB7, 787
Reading tool life management data (tool information 2) (lowspeed
response), 1287 Screen operation for PMCSB7, 789

Reading tool life management data (tool length compensation No. Screen operations, 834, 841, 847, 856
(1): tool No.) (not available for Power MateD/F, Series 21TA), Screen Structure, 806
1125
Screen Structures, 822
Reading tool life management data (tool length compensation No.
(2): tool order No.) (not available for Power MateD/F, Series Search of sequence program, 528
21TA), 1127
Search of specified relay coil points in ladder diagram, 486
Reading tool life management data (tool length compensation No.1)
(lowspeed response), 1282 Searching a sequence program, 1029

Reading tool life management data (tool length compensation num- Searching for an address (SRCH), 542
ber 1) (lowspeed type), 1296 Selectable I/O link assignment function (PMCSB7), 875
Reading tool life management data (tool length offset number 1) (not Selecting the PMC programmer menu, 610
available for Power MateD/F, Series 21TA), 1197
Selection of program menu by soft keys, 1020
Reading tool life management data (tool life counter type) (low
speed response), 1281 Selection of programmer menus by softkeys, 506
Reading tool life management data (tool life counter) (lowspeed Sequence program, 41
response), 1280
Sequence program check and write into ROM (steps 8 to 11), 39
Reading tool life management data (tool life counter) (not available
for Power MateD/F, Series 21TA), 1123 Sequence program copy function, 575

Reading tool life management data (tool life) (lowspeed response), Sequence program creating procedure, 3
1280 Sequence program entry (steps 6, 7), 39
Reading tool life management data (tool life) (not available for Pow- Sequence program examples, 400
er MateD/F, Series 21TA), 1121
Sequence program generation (LADDER), 519
Reading tool life management data (tool No.) (not available for Pow-
er MateD/F, Series 21TA), 1137 Sequence program input, 520, 1022
Reading tool life management data (tool number) (lowspeed re- Sequence program memory capacity, 57
sponse), 1287
Sequence program processing time, 55
Reading tool setting data by specifying tool number, 1372
Sequence program structuring, 48, 369
Reading value of the Pcode macro variable (*lowspeed response),
1161 SET, 126

Registering the tool life management data (tool group) (*lowspeed Set items, 557
response) (not available for Power MateD/F, Series 21TA), 1167 Setting, 393
Remove command file copy, 1046 Setting and display screen, 463
Rename command file attribute change, 1044 Setting and displaying system parameters (SYSTEM PARAM), 611
Repetitive operation, 43 Setting function, 791
Respomse time, 395 Setting I/O commands, 1035
Restrictions, 385, 576 Setting menu (SETING), 672
ROM format program, 1007, 1014, 1017 Setting of Ethernet parameters, 599, 891
ROT (rotation control), 183 Setting of I/O device, 979
ROTB (binary rotation control), 186 Setting of online connection, 595, 889

i7
Index B61863E/14

Setting of online connection by NC parameter, 890 Step sequence basics, 908


Setting of sampling address, 868 Step sequence corresponded C language, 1445
Setting of Trace Parameter, 641 Step sequence method, 902
Setting of trace parameter, 866 Step sequence screen, 948, 958
Setting parameter screen for the selectable I/O link assignment func- Stop function of break with condition [BRKCTL], 592
tion, 796
Stop of ladder diagram display by trigger of signal, 487
SETTING screen, 472 Storage and control of sequence program (steps 12 to 14), 40
Setting Screen, 828 Storage to a memory card, 563
Setting screen, 844, 857 Storage to Flash ROM, 561
Setting screen of general function, 793 Storing the sequence program into flash EEPROM (I/O) (only for the
Setting the screen, 812 Power MateH), 621

Setting the transfer speed ([SPEED] soft key), 570 Structure of software key in PMC, 788, 789

Setting/clearing OVERRIDE, 458 Structure of valid net, 852


SUB (subtraction), 243
Setting/operation for enabling forced input/output, 453
SUBB (binary subtraction), 245
SFT (shift register), 222
Subprogram numbers (CALL, CALLU, SP) (P), 113
Signal address conversion (from the PMCMODEL L/M to the
PMCMODEL SB/SC), 1375 Subprogramming and nesting, 374
Signal diagnosis screen, 438 Substitution of sequence programs, 1025
Signal names, 364 Summary of specification of ladder program, 28
Signal status display (STATUS), 638 Switch statement, 1454
Signal trace function (PMCSB7), 864 Switching screens for setting parameters, 792
Signal trace screen (initial screen), 865 Symbol and comment display, 485
Signals for connecting the operators panel, 1383 Symbol data and comment input, 538
Soft key menu of ladder debugging function, 590 Symbol data display, 1033
Soft keybased PMC menu selection procedure, 630 Symbol data search (SRCH), 538
Source program, 1005, 1010 Symbol data setting (SYMBOL), 537

SP (subprogram), 332 Symbols used in the ladder diagram, 365

SPCNT (spindle control), 321 System alarm messages (C language function for PMCNB/
NB2/NB6), 1436
SPE (end of a subprogram), 333
System alarm messages (PMCSB5/SB6/NB6), 1437
Special uses of the R3 key, 1019
System alarm messages (PMCSC), 1434
Specification, 936 System diagram of soft key, 1395
Specification and display of system parameters (SYSPRM), 1393 System floppy, 984
Specification of PMCs, 5 System parameter (PMCSB7), 884
Specification of step sequence, 935
Specifications, 373, 381, 434, 584
Specifications of password, 753 T
Specifying addresses, 1386
Terminology, 909
Specifying and displaying system parameters (SYSPRM), 508
The value of functional instruction parameter, 483
Specifying and displaying title data (TITLE), 516 Time screen, 953
Specifying the number of the program for I/O Link, 1227 Timer addresses (T), 110
Start and stop of a sequence program, 552 Timer screen, 953
Starting and stopping sequence programs, 783 Timer screen (TIMER), 463, 666
Starting and stopping the online debugging function, 624 Timer set time address, 165
Starting and stopping the sequence program (RUN/STOP), 619 Timer, counter, keep relay, nonvolatile memory control, data table,
Starting ladder mnemonics editing, 613 354
Title data display (TITLE), 636
Starting online communication by offline programmer (Ethernet
connection), 600 Title data editor screen, 637
Starting or stopping the trace function, 430 TMR (timer), 160
Starting the sequence program, 553 TMRB (fixed timer), 162
Step, 923 TMRC (timer), 164
Step operation [STEP], 591 Trace function (TRACE), 429

i8
B61863E/14 Index

Trace screen, 431, 640 Writing the tool life management data (cutter compensation number
2), 1318
Transfer between data area and nonvolatile memory, 1332
Writing the tool life management data (tool condition (1) : tool num-
Transfer to and from a FANUC FD Cassette, 559 ber) (*lowspeed response) (not available for Power MateD/F,
Series 21TA), 1183
Transfer to and from a FANUC LADDER, 559
Writing the tool life management data (tool group number), 1315
Transfer to and from a ROM WRITER, 571
Writing the tool life management data (tool information 1), 1319
Transition, 926
Writing the tool life management data (tool information 2), 1319
Writing the tool life management data (tool length compensation
number 1), 1317
U Writing the tool life management data (tool length compensation
number 2), 1317
User PMC Screen (PMCMDI), 492
Writing the tool life management data (tool length offset number (1) :
tool number) (*lowspeed response) (not available for Power
MateD/F, Series 21TA), 1175
Writing the tool life management data (tool length offset number (2) :
W tool operation sequence number) (*lowspeed response) (not
available for Power MateD/F, Series 21TA), 1177
What is a sequence program?, 35 Writing the tool life management data (tool life counter type), 1316
While statement, 1446 Writing the tool life management data (tool life counter type) (*low
Window function description (FS16PA), 1365 speed response) (not available for Power MateD/F, Series
21TA), 1173
Window function description (FS16W), 1340 Writing the tool life management data (tool life counter), 1316
Window function description (FS16/16iLA), 1330 Writing the tool life management data (tool life counter) (*low
Window function description (PMCNB/NB2/NB6), 1249 speed response) (not available for Power MateD/F, Series
21TA), 1171
Window function description (PMC
PA1/PA3/SA1/SA2/SA3/SA5/SB/SB2/SB3/SB4/SB5/SB6/SC/ Writing the tool life management data (tool life), 1315
SC3/SC4), 1054 Writing the tool life management data (tool life) (*lowspeed re-
sponse) (not available for Power MateD/F, Series 21TA), 1169
WINDR (reading CNC window data), 288
Writing the tool life management data (tool number), 1320
WINDW (writing CNC window data), 291
Writing the tool life management data (tool number) (*lowspeed
Writing (registering) tool life management data (tool group number) response) (not available for Power MateD/F, Series 21TA), 1187
(*lowspeed response) (not available for Power MateD/F, Series
21TA), 1203 Writing the tool management data (tool condition (2) : tool operation
sequence number) (*lowspeed response) (not available for Power
Writing a custom macro variable, 1312 MateD/F, Series 21TA), 1185
Writing a custom macro variable (*lowspeed response), 1081 Writing the tool offset data according to the specified tool number,
1321
Writing a data on the program check screen, 1313
Writing the torque limit override, 1314
Writing a parameter (*lowspeed response), 1072
Writing the wire diameter offset (*lowspeed response), 1343
Writing a parameter (setting data), 1311
Writing tool life management data (cutter compemsation number 1),
Writing a tool offset (*Lowspeed response), 1064 1327
Writing a tool offset data, 1310 Writing tool life management data (tool group numbers), 1325
Writing a workpiece origin offset value (*lowspeed response) (not Writing tool life management data (tool information 1), 1328
supported by the Power MateD or F), 1068
Writing tool life management data (tool information 1) (*lowspeed
Writing of tool setting data (lowspeed response), 1370 response) (not available for Power MateD/F, Series 210TA), 1210
Writing real parameters (lowspeed type), 1329 Writing tool life management data (tool length compensation number
1), 1326
Writing setting data (*lowspeed response), 1076
Writing tool life management data (tool length offset number 1)
Writing setting data (lowspeed type), 1353 (*lowspeed response) (not available for Power MateD/F, Series
21TA), 1206
Writing the feedrate, 1324
Writing tool life management data (tool radius offset number 1)
Writing the measured point (*lowspeed response), 1364 (*lowspeed response) (not available for Power MateD/F, Series
21TA), 1208
Writing the parameter (*lowspeed response), 1347
Writing value of the Pcode macro variable (*lowspeed response),
Writing the superposition move command, 1322 1163
Writing the tool life management data (cutter compensation number Writing, reading, and comparing sequence programs and PMC pa-
(1) : tool number) (*lowspeed response) (not available for Power rameters, 756
MateD/F, Series 21TA), 1179
Writing, reading, and verifying the sequence program and PMC
Writing the tool life management data (cutter compensation number parameter data, 554
(2) : tool operation sequence number) (*lowspeed response) (not
available for Power MateD/F, Series 21TA), 1181 WRT, 120
Writing the tool life management data (cutter compensation number WRT. NOT, 121
1), 1318

i9
Index B61863E/14

X
XMOV (indexed data transfer), 229
XMOVB (binary index modifier data transfer), 232

i10
Revision Record
FANUC PMCMODEL PA1/PA3/SA1/SA2/SA3/SA5/SB/SB2/SB3/SB4/SB5/SB6/SC/SC3/SC4/NB/NB2/NB6
LADDER LANGUAGE PROGRAMMING MANUAL (B61863E)

07 Apr.,95 Total revision 14 Jul., 2001 Addition of PMCSB7

S Addition of ladder display/editing function for PMCNB6


S Addition of expansion of I/O Link points for FS 16i/18i/21i
06 Nov.,94 Corresponds to 18B 13 May, 2000 S Addition of window functions (tool life management
B function and so forth)
S Correction of errors
Addition of PMCMODEL RB4/RC4
Addition of the following Appendix.
S Window function description (FS16LA)
05 May,94 S Window function description (FS16W) 12 Mar., 99 Addition of PMCNB6
S Window function description (FS16PA)
S PMC MODEL RA1/RA3 Supplementary Explanation of
Programming

Addition of PMCMODEL
04 Aug.,93 11 Nov., 98 Addition of Power Mate i
PA1/PA3/RA3/RB3/RC3/NB.

03 Mar., 92 Addition of PMCMODEL RA1/RA2/RB2 10 Dec., 97 Corresponds to 16i/18i/21iMODEL A

All pages are revised.


02 Aug., 91 09 Mar.,96 Addition of PMCNB2
PMCMODEL RC is added.