HC900 Controller
08/10/04 1 of 13
General Guidelines:
The HC900 Hybrid Controller is sold in modules and components that are assembled on-site.
After the type and quantity of I/O and the quantity of I/O racks needed for the installation based
on the distribution of I/O have been determined, use the procedure below to specify the
appropriate hardware and software components.
UMC900 Hardware
Rack
I/O
Power CPU
Supply Terminal
Boards
1 2 3 4 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 10 11 12
Power Supply
Processor
To select a rack(s), first total the number of I/O cards needed by taking the total I/O by type and
dividing it by the number of channels per card, rounding up the result to the next largest whole
number. The table below indicates the card density by type:
08/10/04 2 of 13
Card Type Channels per card I/O needed Cards needed
Analog Input 8
Analog Output 4
Digital Input Contact 16
type
Digital Input VDC 16
Type
Digital Input VAC 16
Type
Digital Output VDC 16
type
Digital Output VAC 8
Type
Digital Output Relay 8
Type
Total Cards Needed
After determining the total number of I/O cards, determine the number of controller racks needed.
If the total number of I/O cards needed is 12 or less, and the users enclosure for the rack can
accommodate rack sizes up to 22.5 inches wide, the I/O can be mounted in a single rack. Specify
a rack size large enough to accommodate the total number of I/O cards from the table below:
Total number of I/O cards I/O cards per rack Rack Model Number
From 1 to 4 4 900R04 0001
From 1 to 8 8 900R08 0001
From 1 to 12 12 900R12 0001
If the total number of I/O requires more than 12 cards, or if the users enclosure cannot
accommodate rack sizes up to 22.5 inches wide, more than one rack will be needed. Determine
the total number of racks and rack sizes based on the number of I/O cards that are to be located in
a specific location. Use the table above to select the appropriate rack size for each location. The
total number of racks supported by a single controller is 5, one for the main controller and 4
remote racks.
08/10/04 3 of 13
The P02 Power Supply is lower cost but has I/O quantity & type limitations for the individual
rack(s). For multiple rack HC900 configurations, you can have a mixture of P01 and P02 power
supplies. The limitations apply to the I/O cards within the rack containing a P02 power supply.
Reference the below chart to determine if you can use the P02 Power Supply for each rack.
08/10/04 4 of 13
Selecting Scanner Modules
If the amount of I/O for the application requires more than one rack, racks 2, 3, 4 and 5 of the
system will require a Scanner Module in place of the CPU module. Scanner modules replace CPU
modules in remote racks and its slot location does not count against the total available I/O slots of
the rack. Specify one (1) scanner module for each controller expansion I/O rack using the model
number below:
Description Application Model Number
Scanner Module Remote rack interface module 900C53-0020
Choose from the following I/O modules to satisfy the applications requirements:
08/10/04 5 of 13
EURO Style BARRIER Style
Specify one each of the following terminal board types for I/O modules:
Analog Inputs, Analog Outputs, Contact Digital Inputs, DC Digital Inputs, DC Digital Outputs.
Specify one each of the following terminal board types for I/O modules:
AC Digital Input, AC Digital Output, Relay Output
08/10/04 6 of 13
Unused I/O slot Covers
It is recommended that unused I/O slots in the controller rack be covered with a connector style
cover. Specify the number of Filler Covers needed to cover unused slots using the number below.
Plantscape, SpecView or
3rd party software
Honeywell or commercial
hub or switch
Direct Ethernet 10 base T
Null Modem Cable
RS232
Null Modem Cable
08/10/04 7 of 13
PC to HC900 Direct via Ethernet
When connecting a PC to the HC900 controller Ethernet port, an Ethernet Cross-over cable is
required.
Plantscape, SpecView,
Workbench or
3rd party software
Cross-overEthernet 10 base T
24VDC Power supply For connection to a PC without using a Hub
PS and user supplied wiring
Specify one 20 foot Ethernet crossover cable for the connection between a PC and the UC900
Controller using the number below:
Cross-over Ethernet Cable 20 feet long 51451996-020
Note: If longer or shorter cable lengths are required, Honeywell recommends the user purchase
the needed Ethernet cable from commercial suppliers. A few such suppliers and products are:
Rs-485 cable
2-Wire Shielded 300V Twinax NA 9271
08/10/04 8 of 13
HC900 Controller to HC900 Controller, or HC900 to Switch via Ethernet
If a HC900 controller is to be directly connected to another HC900 controller for peer to peer
communications, or if a HC900 controller is connected to a Hub or switch for peer to peer
communications between up to eight (8) controllers, a direct 10 Base T Ethernet cable is used.
Direct Ethernet
10 base T
100 meters, (328 feet)
Peer to Peer
Peer to Peer
C t ll
Select one of the cables below for each of the network connections in the above architectures.
08/10/04 9 of 13
HC900 to Remote I/O via Ethernet
A HC900 controller can support one direct connected expansion rack for distances up to 100
meters, 328 feet between racks. When more than one remote rack is used, an Ethernet hub is
required to provide a star connection between the controller and the remote racks. The maximum
number of remote racks supported by a single HC900 controller is four (4). The maximum
distance between the controller and one hub is 100meters, 328 feet, and hub to remote racks is
100 meters, 328 feet, for a maximum distance of 200 meters, 656 feet.
HC900 Controller
Direct Ethernet
10 base T
100 meters, (328 feet)
Remote Rack
Remote Rack
HC900 Controller
Remote Rack
Remote Rack
Multiple Remote Racks
08/10/04 10 of 13
The maximum distance between the controller and the most distant remote rack may be up to 300
meters, 984 feet using two cascaded hubs as indicated below.
Controller
Crossover cable
100 meters (328 feet)
Honeywell Hub
Crossover Cable
Crossover Cable
100 meters (328 feet)
100 meters (328 feet)
Honeywell Hub
Remote
Remote
Rack
Rack
Controller
Crossover Cable
100 meters (328 feet)
Remote
Direct Cable Rack
100 meters (328 feet)
Remote
Rack
08/10/04 11 of 13
Select one of the cables below for each of the remote I/O connections in the above architectures.
Note: If longer or shorter cable lengths are required, Honeywell recommends the user purchase
the needed Ethernet cable from commercial suppliers.
Note: Use of non-qualified commercial hubs or switches is not supported for Remote I/O
connections. Specify a Honeywell Hub when two or more remote racks are needed.
The Honeywell Hub requires 24VDC power at 130mA. If 24VDC power is not available, specify
the Honeywell power supply accessory below or substitute a commercially available power
supply with appropriate voltage and current specifications.
Product Documentation
A Compact Disk (CD) containing documentation on the HC900 product is provided with the
controller CPU assembly 900C51-0011 & 900C31-0011. The CD provides all documentation in
PDF format and supports printing of each manual separately. If extra copies of the
documentation on CD are desired, specify one each of the model numbers below for the needed
CDs.
If hard copy manuals are desired, these may be ordered as a complete set or as individual
manuals. To specify a complete set of hard copy manuals, specify the model number below.
08/10/04 12 of 13
Controller Manual 51-52-25-107
1042 Operator Interface Manual 51-52-25-108
Hybrid Control Designer Configuration Software 51-52-25-110
Function Block Reference Guide 51-52-25-109
Communications Manual 51-52-25-111
Software
Hybrid Control Designer Configuration Software The configuration software will be included
with the Controller CPU assembly if model number 900C51-0011 or 900C31-0011 is specified.
If additional copies are needed, specify one the model number below.
Connection of the Operator Interface to the HC900 controller is with a commercially available
communication cable. A 50 foot length of cable is provided with the Operator Interface. The
Operator Interface may be mounted up to 2000 feet away from the controller. Longer lengths of
communication cable must be purchased from commercial vendors. The recommended cable is a
single twisted pair with shield, Belden 9271 or equivalent.
If the floppy disk (or Zip drive)of the Operator Interface is to be used to store process data, a data
analysis software program will be needed for a PC to allow the import and analysis of the data.
Specify SDA software from the 1042 OI model selection guide. The documentation for SDA
software is not included in the HC900 documentation set but is supplied separately when the
software is ordered.
08/10/04 13 of 13