Sunteți pe pagina 1din 3

CALCULATION SHEETS APPENDIX-B : SOIL RESISTIVITY SUMMARY

NORTH AWQAD II PRIMARY SUBSTATION

*-Co-ordinates Electrode Spacing Average Resistivity


Test No.
(m) (Ohm-m)
Northing Easting

1.5 164.850
SRT-1 1885684 182636 3 122.460
5 157.000
10 188.400
1.5 226.080
SRT-2 1885702 182612 3 273.180
5 204.100
10 125.286
1.5 117.750
SRT-3 1885703 182649 3 131.880
5 109.900
10 188.400
1.5 273.180
SRT-4 1885670 182627 3 226.080
5 204.100
10 179.294

Average Soil resistivity (Sr) 180.746

S Spacing between adjacent electrodes in mtrs


R Resistance in ohms
D Depth of Spike in mm
Sr Soil Resistivity in ohm meter
(2*3.14*S*R)

352222013.xls Page B2 of B2
CALCULATION SHEETS abc
ANNEXURE - I

SOIL RESISTIVITY TEST RESULT

Name of Substation Plot : Al Wasit

Spike Driven
Test Point Resistance Resistivity
Spacing (m) for depth Remarks
Direction (ohms) (ohm meter)
(mm)

OA 0.5 250 57.7

OB 0.5 250 50.6

OC 0.5 250 46.3

OD 0.5 250 36.6

Average 1 47.8 150.2

OA 1 250 43.9

OB 1 250 28.5

OC 1 250 28.1

OD 1 250 48.6

Average 2 37.275 234.2

OA 2 250 24.8

OB 2 250 19.5

OC 2 250 18.6

OD 2 250 20.2

Average 3 20.775 261.1

OA 5 250 11.64

OB 5 250 2.57

OC 5 250 6.53

OD 5 250 12.2

Average 4 8.235 258.7

OA 10 500 8.01

OB 10 500 7.67

OC 10 500 7.36
OD 10 500 5.25

Average 5 7.0725 444.4

Final Average of 5 readings 269.7