Abstract- The flexible alternating current transmission controllers forms an alternative effective solutions [2] to
system (FACTS), a new technology based on power electronics the major power flow related problems that occur in power
can be used to improve controllability, stability, and power system by controlling the power flow along the transmission
transfer capability of AC transmission systems. In this paper lines and improving power oscillations damping [3]. The usage
SSSC damps or decrease Sub Synchronous Resonance in the of these controllers increases the flexibility of the power flow
power system caused during fault or at disconnection of fault. PI operation by providing more options to the power system
or Fuzzy Logic Controller along with an additional controller operators. Recent FACTS controllers are nowadays designed
such as Sub Synchronous Supplementary Damping Controller is in such a way that they overcome the limitations of the present
used to the damp the Sub Synchronous Resonance oscillations.
mechanically controlled power systems and enhance power
Here Voltage Source Converter acts as an SSSC FACTS device.
Digital simulations are performed in the MATLAB/Simulink
flow. Fuzzy logic controller used here will control the DC
environment to provide comprehensive understanding of the voltage (Vdc) and SSDC will damp the Sub Synchronous
issue. Simulation studies validate the effective performance of Oscillations. In this paper a SSSC along with SSDC is
the designed controllers at several test conditions. connected to the transmission line to damp SSR [4]. The VSC
here acts a SSSC. The effectiveness of the proposed controllers
Keywords: SSR; SSSC; FACTS; PI Controller; fuzzy logic is compared under three different operating condition cases.
controller; SSDC; Parks Transformation. The first case is based on the increase of mechanical power and
the second case is tested with disconnection of a transmission
I. INTRODUCTION line and third case test is done by creation/ injection of three
phase fault in the system. The simulation work is carried out in
MATLAB/Simulation software. A detailed comparison of the
The main importance in a power system operation are its effectiveness of two controllers at various operating condition
security and stability, so a control system designed should is done.
maintain its frequency and voltage at a fixed level against any
kind of disturbance such as a sudden increase in load, a
II. SYSTEM MODEL
generator being out of circuit, or failure of a transmission line
due to various factors such as human faults, technical defects of
equipments, natural disasters, due to malfunction of some A Single Machine Infinite Bus System(SMIB) along with
advanced power electronics devices and compensators etc. series compensator as shown in Fig.1 is the system model
Conventional and easier methods to damp or reduce the effects considered for our study. The system has a synchronous
in power system are the use of capacitor banks connecting in generator connected to an infinite bus having two transmission
series in the transmission line. But the drawback in the use of lines in parallel. In the considered study system one of the
series capacitance lead to risk of interaction between power transmission line is compensated by a series capacitor [5, 6]. A
transmission lines and generator knows as Sub Synchronous 600 MVA turbine-generator is connected to an infinite bus,
Resonance (SSR) effect[1].Many techniques have been with the rated line voltage of 500KV, while the rated frequency
implemented in order to damp or suppress the resonance. The is 60Hz. The SSSC is designed by a combination of one 6
first thing is controlling of excitation system of the generator IGBT (Voltage source Converter) based on Pulse Width
which is the conventional method, and the second thing is by Modulation (PWM) technique along with a filter and step-
using the FACTS devices. The recent developments in power down transformer. The shaft system as shown in Fig.2 consists
electronics have resulted in the effective usage of FACTS of four masses: the generator (G) and rotating Exciter (EX),
devices in power transmission systems. FACTS damping low pressure turbine (LP), and a high pressure turbine (HP).
Veltech Multitech Dr.Rangarajan Dr.Sakunthala Engineering College, All the masses are mechanically connected to each other by
Avadi, Chennai (Sponsors)
Fig. 3. Block diagram of power flow control of the SSSC along with SSDC
EX GE LP H
CC P Va=Vm *Sinwt
Vb=Vm *Sin(wt+120)
Fig. 2. . Model of the turbinegenerator system. Vc=Vm*Sin(wt-120) (1)
7$%L(,
A. Error Calculation
The error rate is found by taking the difference between
supply voltage data and the reference voltage data. D. Defuzzification
It is the process of converting the controller outputs fuzzy
set to real control (analog) signals.This process is done because
B. Fuzzification the fuzzy results generated cannot be used as such to our
applications, hence we convert the by defuzzification process.
Fuzzification is fuzzy logic theory means the process where
Centroid method is used for defuzzification in the present
the input quantities are converted to fuzzy set by mapping with
studies. The control signal is represented by equation (4).
membership functions. This fuzzification unit here transforms
the numeric input variable measurements into the fuzzy set
(linguistic) variable that is a clearly defined boundary, without
a crisp value. The error and error rate measured here are
declared has linguistic variables like negative small (NM),
negative big (NB), negative medium (NM), zero (Z), positive E. Signal Processing
small (PS), positive medium (PM) and positive big (PB)
characterized by membership functions as given in Fig 5. The outputs of FLC process are the control signals that are
used in generation of switching signals for the PWM inverter
by comparing with a carrier signal.
CONCLUSION
This paper investigated the comparison between PI and
Fuzzy Logic based controlle of SSSC in a single machine
infinite bus power system to damp sub synchronous resonance.
The Matlab/Simulation is carried out on IEEE second bench
mark system. The simple signal(w) is chosen as the input of
the SSDC. This signal considered contains all the torsional
modes so that the SSSC along with the proposed SSDC can
improve the stability of system. The SSSC is used as a voltage
source in series with a fixed capacitor and this prevents the sub
synchronous oscillations that may be caused by conventional
fixed capacitor. The effectiveness of the system is tested with
small disturbance as well as with large disturbance. During all
the test conditions, we have observed that Fuzzy Logic
Controller is able to damp the oscillations more quickly than PI
controller. Further analysis on the proposed controller can be
done in a wind power plant integrated power system or with a
ANFIS controller.
REFERENCES
[1] H. Barati, Application of Static Synchronous Series Compensator to
damp Sub Synchronous Resonance, International conference on Power
Electronics , Drives and Energy System.PEDES06.