Documente Academic
Documente Profesional
Documente Cultură
Application Guide
ACS800 Common DC System
ACS800 Common DC System
Application Guide
Table of contents
Introduction
Design
Power limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Allowed braking power and need for a brake resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Calculation of the allowed braking power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Internal brake chopper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
External brake chopper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Contactors, DC-bus and brake circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring
Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Powering the AC-fans in R7 and R8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Brake resistor circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connecting the contactor of the resistor circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Phase loss guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Start-up
Introduction
Note: The common DC-application is not tested according to the EMC requirements
of conducted and radiated emissions.
Introduction
2
F8 F7 F6 F8 F8
R8 R7 R6 R8 R8 R8
- + - + - + - + - + - +
M M M M M M
3~ 3~ 3~ 3~ 3~ 3~
F6 F8 F7 F7
R6 R8 R7 R7 / R6 R7 R7 / R5
- + - + - + - + - + - +
M M M M M M
3~ 3~ 3~ 3~ 3~ 3~
Cases b, c and d can be used when the total power taken from the main supply,
Pout.tot, is smaller than the drive power rating, Pcont.max, of the biggest converter.
Case a)
The most common set-up, where all converters are connected to the main supply.
When the charging circuits of the converters are different, this connection is not
always allowed. Table 1 shows when the connection cannot be used.
Case b)
Converters are identical and only one converter is connected directly to the main
supply.
Case c)
Converters are not identical and only the biggest converter is connected directly to
the main supply. The AC-cables to the other converters are protected by drive-
specific fuses.
Case d1)
Converters are identical and only one converter is connected directly to the main
supply. The charging circuit of the connected converter is capable of charging the
whole DC-bus.
Case d2)
Converters are not identical and only the biggest converter is connected to the main
supply. Charging circuit of the connected converter is capable of charging the whole
DC-bus.
Note: If the charging circuit in case d1/d2 is not capable of charging the DC-bus,
connection presented in case b/c must be used.
Note: With frame sizes R5-R8 the charging circuit in case d1/d2 might not be able to
withstand the three times larger charging energies. In this case the main supply
cable is wired to all of the input rectifiers as presented in case b/c.
Table 3 in Appendix A When one charging circuit is enough lists the allowed drive
combinations when only one charging circuit is enough.
1) Select the converters and preselect the main supply connection. See Possible
main supply connections.
2) Check from Table 1, Power correction factors, that the connection is possible.
3) Check by using equation 1 that the load does not exceed the total power limit,
Pout.tot, of the system. See Power limit.
4) Select the fuses, cables and possible contactors for the DC-side. See Fuses,
Cables and Contactors, DC-bus and brake circuit .
5) Calculate the braking power and determine whether the braking cycle can be
performed and whether an internal or an external brake chopper is needed. See
Allowed braking power and need for a brake resistor.
6) If resistor braking is needed, select the internal or external brake chopper, the
resistor and the contactor. See Internal brake chopper, External brake chopper and
Contactors, DC-bus and brake circuit .
7) Set up the common DC-system according to the wiring instructions. See Wiring.
8) If the input terminals of frame sizes R7 and R8 are left unconnected, make sure
that the AC-fans are powered separately. See Appendix B Powering the AC-fans of
R7 and R8.
9) Set the common DC-system related parameter values. See Start-up.
Design
Power limit
Total output power limit of the common DC-system can be calculated with
equation 1.
Pout.tot is the instantantaneous power limit of the installation. P1cont.max is the lowest
and P3cont.max the highest drive power rating of the three converters.
Only converters, which are connected to the main supply, are used for the power
limit calculations.
The power correction factor, k, for each combination can be found from Table 1.
When all three converters are connected to the main supply, the least efficient power
correction factor is chosen from table 1, i.e. the smallest factor. See Example1 and
Example2.
Table 1. Power correction factors
ACS 800
R2-R3 R4 R5-R6 R7-R8
R2-R3 k=0.5 NO NO NO
R4 NO k=0.7 k=0.7 C k=0.7 C
R5-R6 NO k=0.7 C k=0.7 k=0.6
R7-R8 NO k=0.7 C k=0.6 k=0.7
Explanations of Table 1:
NO: The supply of the smaller converter MUST not be connected, because the
converters have different input chokes. Frame sizes R2-R3 have DC-chokes and
frame sizes R4-R8 AC-chokes.
C: If both converters are connected to the main supply, the DC-links MUST be
connected together via contactor because the converters have different charging
circuits. In R2-R4 the charging resistors are in series with the DC-capacitors and in
R5-R8 the charging resistor is in parallel with the input bridge. The DC-contactors
are switched on after all of the DC-links are charged and the converters are in the
READY state.
Note: The Pout.tot value is higher if the smallest converter is not connected to the
main supply.
Design
6
Example1
The DC-buses of three converters ACS800-0004-5, 2.2 kW, R2; ACS800-0025-5,
18.5 kW, R3 and ACS800-0025-5,18.5 kW, R3 are connected together. The input
terminals of the 2.2 kW converter are left unconnected. According to Table 1, k = 0.5
when two R3s are connected to the main supply, therefore Pout.tot is
Example2
The DC-buses of three converters ACS800-0050-5, 37 kW, R5; ACS800-0140-5,
110 kW, R6 and ACS800-0320-5, 250 kW, R8 are connected together. All three
converters are connected to the main supply. According to Table 1, k = 0.7 when R5
and R6 are connected to the main supply and k = 0.6 when R6 and R8 are
connected to the main supply. The worst case is chosen for the calculations, i.e.
k = 0.6, therefore Pout.tot is
Fuses
Use fuses listed in the appropriate Hardware Manual for input cable protection.
The recommendations for obligatory DC-side semiconductor fuses, aR-fuses, are
listed in Table 2. Use 690 VAC rated fuses for 230-500 V converters and 1000 VAC
rated fuses for 690 V converters. The aR-fuses protect the converter against short
circuits in other converters. Because of the complicated fault current paths the
selectivity of the fuses cannot be guaranteed in all conditions.
aR-fuses must be installed on both DC-wires.
Design
7
Design
8
Cables
Select the input power cables as described in the Hardware Manual. The cross-
sectional area of the DC-cables must be the same as the cross-sectional area of
the AC-side cables.
If screened DC-cables are used, ground the screen at the other end only.
The lengths of the supply cables must not differ more than 15%. This applies
especially to converters equipped with DC-chokes.
Maximum length of the DC-cables between two converters is 50 m.
If the system consists of three converters, the DC-links must be connected in an
external terminal box. Do not use the terminals of one of the converters for this
purpose.
Design
9
P
Drive A
duty cycle
P
Drive B
duty cycle
P
Drive C
duty cycle
P
Common DC
duty cycle
t
Design
10
P br P cont.max
Condition 2
The power flowing through the converter's DC-bus terminals to the other drives may
not exceed the drive power rating. This might happen when drive brakes and takes
power from the main supply at the same time. The power rating of the terminals is
not exceeded when the following condition is valid, i.e. the sum of the drive input
power and the drive braking power has to be equal or smaller than the drive power
rating.
P 1 P br + P 2
-------------------------------- P cont.max + P br P cont.max
P out.tot
Design
11
Example 3
The DC-buses of three converters ACS800-0140-5, 110 kW, R6; ACS800-0140-5,
110 kW, R6, and ACS800-0070-5, 55 kW, R5 are connected together. Only one
110 kW converter is connected to the main supply. The duty cycle is shown in the
table below.
Phase Converter powers (kW) Common DC
duty cycle (kW)
R6 (AC supplied) R6 R5
t1t2 60 0 30 90
t2t3 -70 70 30 30
t4t5 0 -30 30 0
Design
12
P DC P cont.max (equation 4)
U DC = 1.35 U 1
Pcont.max is the drive power rating of the biggest converter and U1 is the supply
voltage of the converter.
Design
13
Peak current through the contactor in brake resistor circuit can be calculated with
equation 5.
1.21 U DC
I = ------------------------- (equation 5)
R brake
The rms current during the braking can be calculated with equation 6.
P br
I rms = ------------- (equation 6)
R brake
Rbrake is the brake resistors resistance. Pbr is the applied braking power.
Design
14
Wiring
Supply
Use the same supply connection point. All converters must be fed from the same
transformer. The supply impedance is an important parameter, which influences the
current distribution. All converters must have equal supply impedance.
Warning! Application macro change resets the settings. Restore the settings to
correct values after the macro change.
Wiring
15
F8 F7 F4
R8 R7 R4
+ - + - + -
- +
IC - + -
EC
M M M
3~ 3~ 3~
K2
IC K1 EC
X22 +
+24V 28
-
29
2
10
DIIL 2
11
X27
21
RO3 22 230 V~
23
Wiring
16
Wiring
17
Start-up
Start-up
18
Table 3 lists all the allowed combinations with two and three rectifiers when only the
biggest converter, drive a, is connected to the main supply.
When all of the converters are identical and two of them are directly connected to the
main supply, the system is always capable of charging the DC-bus. With frame sizes
R2-R4 only one direct main supply connection is enough.
Table 3. Allowed drive combinations when only the biggest drive is connected to the
main supply.
UN Drive a Drive b Drive c
R6 ** R2-R6 ** R2-R5 **
R7 R2-R7 R2-R7
R8 ** R2-R8 ** R2-R7 **
R6 ** R2-R5 ** R2-R4 **
R7 R2-R7 R2-R7
R8 ** R2-R7 ** R2-R6 **
R6
R7 R2-R6 R2-R6
R7 ** R2-R7 **
R8 ** R2-R7 ** R2-R7 **
**The DC-links are allowed to be energized once during three minutes. The nominal
cycle is five chargings during ten minutes.
If the supply of frame size R7 or R8 is not connected to the main supply, the AC-fan
must be powered separately.
Feed the primary of the fan circuit transformer with the converters nominal main
supply voltage, V- and W-phases, via the built-in fan circuit. The original cables
between the busbars and the fuses have to be removed. The feeding cable must be
protected against short circuits despite of the used built-in fuses.
The fuse locations are shown in the following picture.
500 V 690 V
R7
R8